HomeMy WebLinkAboutPermit D2000-348 - LEVEL 3 COMMUNICATIONS - TENANT IMPROVEMENTD2000 -348
LEVEL 3
COMMUNICATIONS
3511 So. 120t`' Pl.
EXPIRED - PERMIT
NEVER ISSUED
Cra
CM o
.1 3
ca 3 r
= C
—•
0 0
� w
•
NOTICE: IF THE DOCUMENT IN THIS FRAME IS LESS CLEAR THAN
THIS NOTICE IT IS DUE TO THE QUALITY OF THE DOCUMENT. _,
•
City of Tukwila
Community Development / Public Works • 6300 Southcenter Boulevard, Suite 100 • Tukwila, Washington 98188
WARNING: IF CONSTRUCTION BEGINS BEFORE APPEAL PERIOD EXPIRES,
APPLICANT IS PROCEEDING AT THEIR OWN RISK.
Parcel No: 271600 -0075
Address: 12770 GATEWAY DR
Suite No:
Location:
Category:
Type:
Zoning:
Const Type:
Gas /Elec.:
Units: 001
Setbacks: North: .0 South:
Water: TUKWILA Sewer:
Wetlands: Slopes:
4TH FLOOR
AOFF
DEVPERM
C /LI
Contractor License No: SELLEC *372ND
Construction Valuation: $
PUBLIC WORKS PERMITS: *(Water
Curb Cut /Access /Sidewalk /CSS:
Fire Loop Hydrant:
Flood Control Zone:
Hauling:
Land Altering:
Landscape Irrigation:
Moving Oversized Load:
Sanitary Side Sewer:
Sewer Main Extension:
Storm Drainage:
Street Use:
Water Main Extension:
DEVELOPMENT PERMIT
Meter
N
N
N
N
N
N
N
N
N
.0
SEPTIC
Y
Fire
East:
Permit No:
Status:
Issued:
Expires:
Occupancy:
UBC:
Protection:
.0 West:
Streams:
Phone:
Phone: (206)439 -5961
Phone: 206 - 812 -5131
Phone: 206 -682 -7770
OCCUPANT BOEING EMPLOYEES CREDIT UNION
12770 GATEWAY DR, TUKWILA, WA 98168
OWNER BOEING EMPLOYEES CREDIT UN
PO BOX 97050, SEATTLE WA 981249750
CONTACT CLAIRE MADSEN
12770 GATEWAY DR, TUKWILA, WA 98168
CONTRACTOR SELLEN CONSTR CO INC
PO BOX 9970, SEATTLE, WA 98109
****************************************************** * * ** * * * * * * ***** * * * * * ** ** ** ** **
Permit Description:
TENANT IMPROVEMENT - CREATE PRIVATE OFFICE ON
FOURTH FLOOR.
****************************************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *'
5,500.00
Permits Listed Separate) Eng. Appr:
No: Size(in): .00
Start Time: End Time:
Cut: Fill:
Start Time: End Time:
No:
Private: N Public: N
Private: N Public: N
•******************************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * *;
TOTAL DEVELOPMENT PERMIT FEES: $ 211.16
****************************************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
' Permit Center Authorized Signature:
I hereby certify that I have read and examined this 'ermit and know the same
to be true and correct. All provisions of law and ordinances governing this
work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or
cancel the provision of any other state or local laws regulating construction
or the performance of work. I am authorized to sign for and obtain this
development permit. ��vlvltTMG/�
Signature: , f��'V
Print Name: __ Sa1a`e I 4kl
This permit shall become null and void if the work is not commenced within
180 days from the date of issuance, or if the work is suspended or abandoned
for a period of 180 days from the last inspection.
Date:
(206) 431 -3670
D2000 -349
ISSUED
11/27/2000
05/26/2001
OFFICE
1997
SPRINKLERED /AFA
.0
ate
27
Q
CL 2
6
c)0
rn 0 .'
W =
W
W �!
I I
U
0 co
C3 r—
= W'
H V '
111
= ;
z
1
CITY OF TUKWILA
Address: 12770 GATEWAY DR Permit No: D2000-349
Suite:
Tenant: Status: ISSUED
Type DEVPERM Applied: 10/31/2000
Parcel #: 271600-0075 Issued: 11/27/2000
kkkkA****A*A***A*A*AkkAAkk**kk *kAAAAAAVWW****Akk*AkkkA***Akilk****Ak*A4A
Permit Conditions:
I. No changes will be made to the plans unless approved by the
,Engineer and the Tukwila Building Division.
2. All construction to be done in conformance with approved
;plans and requirements of the Uniform Building Code (1997
Edition) as amende Uniform Mechanical Code . (1997 Edition),
and Washingtop"State
0, ;Validity of':' TlYe issuance of a permit or approval of
.
.plans, specificatVons.,- and computations shall not be_con-
strued to be a‘permit for, or an approval of; any violation
,
of any,OLfthe provisions of the building code or of any
(11ther.brdinance,of the juriStietiOn. No permit presuming:to
give ,authority to cancel the proviSions'of,thVS
odeahall:be valid.
Electrical permits shall be obtained through the'Washingtbn
_
State Division of Labor and Industries and all electrical ..-.
work ..„ -
will
be inspected by agency.(248 -6630).
inspection records. ,arid approved plans, shall be
available at the job.site'irior:tothe start of any-con-
TheSe to be maintained and avail-
able until ,tnspection approval is —granted.
6. Partition walls attached to ceiling grid must be laterally
7.
braced if over ei'ght in length. Any new ceiling grid - and light fixture installation is
regdfred,to lateral bracing requirements for Seismic
Zone 3.
• '***F4:0E DEPARTMENT CONDITIONS***:
9. The attached set of plans have been reviewed by The Fire
Prevention Bureau and are acceptable with the following
.
concerns
10. 'The totalThumber:of fire extinguishers required for your
establishment is calculated at one extinguisher for each
3000 sq. ft. of area. The extinguisher(s) should be of the
Purpose" (2A, 106:C) dry chemical type. Travel
distance to any fire extinguisher must be 75
(NFPA 10, 3-1.1)
11. Portable fire extinguishers she') be securely insta I 1 ed on
the hanger or in the bracket‘supplied,, placed in cabinets
or wall recesses. The hanger or bracket shall be securely
and properly anchored to the mounting surface in accordance
with the manufacturer's instructions. The extinguisher
shall be installed so that the top of the extinguisher is
'not more than 5 feet above the floor and the clearance
between the bottom of the extinguisher and the floor shall
not be less than 4 inches.
12. Extinguishers shall be located so as to be in plain view
(if at all possible), or if not in plain view, they shall
be identified with a sign stating, "Fire Extinguisher",
wi th an arrow pointing to the uni t. ( NFPA 10, 106.3) (UFC
Standard 10-1)
13. Clear access to f ire extinguishers is required at al 1
times. They may not be hidden or obstructed. (NFPA 10,
14. Fire extinguishers require monthly and yearly inspections.
They must have a tag or label securely attached that
indicates the month and year that the inspection was
performed and sha 1 1 identify the company or person
performing the service. (NFPA 10, 43, 4-4 and 4-4.3)
Every six years, dry chemical and ha ion type f ire
extinguishers s h a l l be emptied and subjected to the
app l i cab 1 e recharge procedures, (NFPA 10, 4-4.1) If the
required monthly and yearly inspections of the f ire
ext ingui sher( s) are not accomp 1 ished or the inspection tag
is not complete, a reputable ,f ire extinguisher service
company w i l l be required to conduct these required surveys.
(NFPA 10 , 4 4•.4)
15. Maintain f ire extinguisher coverage throughout.
16.. No point i n ' an unsprink 1 ered bui 1 d ing may be more than 200
- feet from ern ex i t, measured along the path of travel . (UBC
• .• • r , • • ••
17. No point - in a,sprfnk 1 ered building may be more than 250
feet fropto an exit, measured'a icing the path of travel (UBC
1004,2.5.2.2)
1 8 . Ex i t-doorS .:shall swincrin the direction of e x i t 'travel wheh-,,
serving any hazardous1area Or' when serving an occupant load
,
of 5 0,' or more (UBC 1093. 3. s)
19. 'Ex i t doors .1Shal I be , openab le' from the , inside without the
:::: '
use of a key :or any 'special knowledge Or effort. Ex i
doors sha 11 not:be chained, 'tiO1 ted, barred, 1 atche
or. otherwise 'unusable. - All :lockfrig devices shall
be of an approved tvpe- (UFC 1207.1)
20. cDead bolts are not- allowed on auxi 1 iary exit doors unless:
the ; bolt . is adOmat lea 1 ly ',retracted when the door
• ,
'handle is engaged from inside the tenant space. tUFC
.1207;1)
2 1 . When two /or more exits from a story,are.:required, e x i t
sit;1 1 •be insta 11 ed at the .required 'exits and where '
otherwise necessary , to clearly ;indicate the direction of
egress - 1UBC, 1003.2.8.2)
When tWoor mOre, exits from a story are required and when
two or mare exits from . a room or an area are requi red, ex i t
sighs shall fltuminated. (UBC, 1003.2.8.4)
23. Internal bt-Alluminated exit signs sha 1 I have both bulbs
working at all times. (UBC 1003.2.8-4)
24 Exits shall be .1) luminated any time the bui I ding . is
occupied wi th 1 ight - having an intensi tv of not less than 1
foot candle at f loor levet. F Fixtures -required for exit
111 um i net ion she 11 be supp 1 ied from separate sources of
power for Group I. Division 1.1 and 1.2 occupancies and for
al 1 other occupancies where the ex i ting system serves an
occupant load of 100 or more. (UBC 1003.2.9, 1003.2.9.2)
25. The power supply for means of egress i 1 1 umi nat i on sha 11
normally be provided by the premises • electrical Iectr supply.
in the event of it's failure, i 1 luminat ion shall be
automat i ea 11 y provided from an emergency system for Group
I, Divisions 1.1. and 1.2 occupancies and for a 11 other
occupancies where the means of egress system serves an
occupant load of 100 or more. Such emergency systems sha 1 1
z
1-z
wi
6 5
C.) 0
0) 0
tu
W I
ILL
0
g
IL. <
ev
•
111
m.
Z
I— 0
Z
WUJ:
2 a
D
0 to
0 -
0 I-
uJ
I 0
— 0
. z
fu
z
be installed in accor dance with the electrical /,de. (UBC
1003.9.2) •
'26. All exit signs shad be illuminated at all times. To
ensure continued illumination for a duration of not less
than 1 1/2 hours in case of primary power loss, the exit
signs shall also be connected to an emergency electrical
system provided from storage batteries, unit equipment or
an on site generator set, and the system shall be installed
in accordance with the electrical code. (UBC 1003.2.8.5)
27. Maintian sprinkler coverage per N.F.P.A. 13.
Addition /relocation of walls, closets or partitions may
require relocating and /or adding sprinkler heads.
Sprinkler protection shall be extended to all areas where
required, including all enclosed areas, below obstructions
and under overhangs greater, than four feet wide. (NFPA
.13-4-5.5.3.1)
All new sprinkler .systems and all modifications to existing
sprinkler systems shal l have fire department review and
.approval of drawings prior to installation or modification.
New sprinkler systems and all modifications to ;sprinkler, I co LL.
systems in more than 50 heads shall have the written wO
approval r.of the W.S.R.B. g
. , Factory Mutual, Industrial `Risk 5'.
Insurers, or any other representative designated t IL<
and /or recorgnized. by the City of ,Tukwila, prior to Y2 a
submittal. to the Tukwila Fire Prevention Bureau. No . xw
sprinkler ..work shall commence without approved drawings. zp ;
`(City', Ordinance #1901): i.--0 ;Al 1 spr inller ,system. plans, ,calculations and the w W`
con tractors Materials s ..and Test Certificates if i cates submitted . to 0+
the,'Tukwila Fire Prevention Bureau..:must`be stamped.with the O N
i
p --- level • . -seal. (WA 212-80) O;
H
Maintain ,automat is fire , detector cover age per N.F PA. 7 ; w '
Addi 7:r�
st ionelo,catiori of walls=, closetti par ~titionti may . �t�
:require r� /or adding automatic fire detector j �r
• Maintain square toot cnverage of detectors per z,
ma specifications in. all: . areas including: L b w
lo'sets , elevator shafts, top of stairwells, "etc. (NFPA ' 0 i-i
72, *5=-1.4.2) z ..
All new fire alarm systems or mo - to existing,
syste'ms shall have the written approval Of 'the Tukwila Fire
.Prevention ion Bureau. No work' shall l 1 commence mence _until a fire
department permit. has been obtained. (City Ordinance
#1900) ('UFC 1001:3)
All electrical work and equipment shall conform 'str•i,ctly to .
the standards of The National Electrical Code. (NFPA. 70)
•
An aisle to'and working space shall' be provided for each
electrical panel An aisle` width not 'Jess than 24' inches
shall provide access to the panel and 30 i n,ches of working
space shall be provided d ir-ect l y in front of the panel.
'(NEC 110- 16(a), NEC 110- 16(c))
36. Each circuit breaker shall be legibly marked to indicate
it's purpose. (NEC 110 -22)
37 Required fire resistive construction, including occupancy
separations, area separation wails, exterior walls due to
location on property, tire resistive requirements based on
type of construction, draft stop partitions and roof
coverings shall be maintained as specified in the Building
Code and Fire Code and shall be properly repaired, restored
or replaced when damaged, altered, breached, penetrated,
removed or improperly installed. (UFC 1111.1)
y
4
42.
'I hereby certify that I'have •r.ead these, conditions and will comply.
with them as out l teed . Al: 'pr ov s ions ` of, law" and ordinances—governing
this work? wi l :be comp l;i;ed °with-; ; whether `specif herein or n "at
The: grant;i ng of this per?mi.t ' does not pr esu to give authori ty to•'
v iolate or cancel `;the "pr°ovisi'ons of any. other ,worrk or local" Ya ws,.
r n
construction or the per formanc;e ot, work.
,
Signature l.�GtitGG (G LiAleDate: (1,2 ° 9 ' ZWO
F Tint Name 2 Ov dIGl /-�! l ie
38. The maximum flame spread class of finish materials used on
interior walls and ceilings shall not exceed that set forth
in Table No. 8-B of the Uniform Building Code. (UBC: 804.1)
3g Your street address must be conspicuously posted on the
building and shall be plainly visible and legible from the
street. Numbers shall contrast with their background.
(UFC 901.4.4)
40. In order to provide you with the fastest police and fire
protection under emergency conditions, please post. your
suite, room or apartment number in a conspicuous place near
the main entry door. (UFC 901.4.4)
. '`Fire Department lock boxes shall be provided for access to
all fire alarm panels and sprinkler risers. The
appropriate key(s) for access shall be placed in the
lockbox. Lockbox order forms: must be obtained from the
.Tukwila Fire Department. (City Ordinance '... #1900) .
Contact the Tukwila ",Fire Prevention Bureau, to witness all
required inspections and tests. (UFC 10.503) (City
Ordinance #1900 , and #1
4 . This review . l imi ted to speculative tenant space only
special fire` permits may be necessary depending on detailed
description of intended ; use.
4. Any overlooked hazardous c o n d i t i o n and/or'. v i o l a t i o n of the
adopted ;F ire or` Bu i l d i nq Codes 'does not imply approval of
,
uch condition or violation.
5, The ,plans were reviewed by I nspector 510. I f you have any:.
,ques call the Tukwila Fire Prevention Bureau
at (20(5) 57 4407.