HomeMy WebLinkAboutPermit 0050 - Airco Ohio Medical CompanyThis record contains information which is exempt from public disclosure
pursuant to the Washington State Public Records Act, Chapter 42.56 RCW
as identified on the Digital Records Exemption Log shown below.
050
Airco Ohio Medical Company
531 Strander Boulevard
RECORDS DIGITAL D- ) EXEMPTION LOG
THE ABOVE MENTIONED PERMIT FILE INCLUDES THE FOLLOWING REDACTED INFORMATION
Page # tode Exemption = 8rlef Explanatory DeSclriptiop �t�tutel ule
The Privacy Act of 1974 evinces Congress'
intent that social security numbers are a private
concern. As such, individuals' social security
Personal Information —
numbers are redacted to protect those
Social Security Numbers
individuals' privacy pursuant to 5 U.S.C. sec.
5 U.S.C. sec.
2
DR1
Generally — 5 U.S.C. sec.
552(a), and are also exempt from disclosure
552(a); RCW
552(a); RCW
under section 42.56.070(1) of the Washington
42.56.070(1)
42.56.070(1)
State Public Records Act, which exempts under
the PRA records or information exempt or
prohibited from disclosure under any other
statute.
Redactions contain Credit card numbers, debit
card numbers, electronic check numbers, credit
Personal Information —
expiration dates, or bank or other financial
RCW
DR2
Financial Information —
account numbers, which are exempt from
42.56.230(5)
RCW 42.56.230(4 5)
disclosure pursuant to RCW 42.56.230(5),
except when disclosure is expressly required by
or governed by other law.
71-050 531 strander boulevard
airco ohio medical company
hs ferguson construction
LEGAL
1 DESCR.
LOT NO,
BLK
TRACT
(17(1SEE ATTACHED SHEET)
OWNER MAIL ADDRESS ZIP PHONE
2 hi QrCio .. 0 1'1 1 0 PC:--DI CAL- • ::<.% .
CONTRACTOR MAIL ADDR C ). PHONE LICENSE NO.
3 `' �c� T W
t4 S . 'e- re.c CouS � `7 c1 , - Aue S. I2a7 ? P)10
ARCHITECT OR DESIGNER MAIL ADDRESS PHONE LICENSE NO,
: c ic: <1 J€ �...se -tJ A VC.44. 1Z64-1 lUr -f C( ?Z C-1kTri t.. A.1 t12Ach2 i .3- 7 -
ENGINEER MAIL ADDRESS PHONE LICENSE NO. -
5
LENDER MAIL ADDRESS - B11MMH
6 F e r t.c S O - C ` S es7. -- ,73 . /
USE OF BUILDING
8 Class of work: NEW ❑ ADDITION 0 ALTERATION 0 REPAIR • MOVE • REMOVE
9 Describe work: f�0 Ttz..i..)G h.' (7 _. A .
'T A T - I) r Gna.1C' 12 � - 7 t — rR) wr.l.,0 t D el
10 Change of use from
Change of use to
11 Valuation of work: $ 'I`_ /"f,F1/I^s
t[.7/ CJL L'
PLAN CHECK FEE �.
Type ofW
Const.
Occupancy
Group
PERMIT FEE
F
/ 9 c � > ^" �
Division 2
SPECIAL CONDITIONS:
$O G`? /) , P� N, �/
l
/ , /
Size of Bld
(Total) Sq. g. (Total)
No. of
Stories /
Occ. Load
' /
R / ` .
Fire
Zone 3
Use M
Zone / I
Fire Sprinklers
Required •N/es giro
APPLICATION ACCEPTED,SS:
k-,
HE KED 0Y.
4 /6 L
APPR VE FOR IS UANC Y:
r
No, of
Dwelling Units
OFFSTREET PARKING SPACESI
Covered Uncovered /
i.
N Oj E
SEPARATE PERMITS ARE REQUIRED FOR ELECTRICAL, PLUMB-
ING, HEATING, VENTILATING OR AIR CONDITIONING.
THIS PERMIT BECOMES NULL AND VOID IF WORK OR CONSTRUC-
TION AUTHORIZED IS NOT COMMENCED WITHIN 60 DAYS, OR IF
CONSTRUCTION OR WORK IS SUSPENDED OR ABANDONED FOR A
PERIOD OF 120 DAYS AT ANY TIME AFTER WORK I$ COM•
MENCED.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS
APPLICATION AND KNOW THE SAME TO BE TRUE AND CORRECT.
ALL PROVISIONS OF LAWS AND ORDINANCES GOVERNING THIS
TYPE OF WORK WILL BE COMPLIED WITH WHETHER SPECIFIED
HEREIN OR NOT, THE GRANTING OF A PERMIT DOES NOT
PRESUME TO GIVE AUTHORITY TO VIOLATE OR CANCEL THE
PROVISIONS OF ANY OTHER STATE OR LOCAL LAW REGULATING
CONSTRUCTION OR THE PERFORMANCE OF CONSTRUCTION.
Special Approvals
Required
Not Required
Approved
ZONING
HEALTH DEPT.
FIRE DEPT.
SOIL REPORT
OTHER (Specify)
FOUNDATION
FRAMING
FINAL
9 GtJ TU RE or `OW ER BUILDER)
1_' ❑/ E q
A TH R D AGEN D ATE)
SIGNATURE R U O 12
'I
' BUILDING PERMIT
Applicant to complete numbered spaces only.
at OF TUKWILA BUILDING Ft, :MIT
14475 - 59th Ave. So. / Tukwila, Washington 98067
WHEN PROPERLWVALIDATED (IN THIS SPACE) THIS IS YOUR PERMIT
PLAN CHECK VAL ION cK. M.O. CASH PERMIT VALIDATION ctt. M.O. ' CASH
OCCUPANCY PERMIT REQUIRED 1-
BUILDING
PERMIT NO.
N 050
footing inspection
LEGAL DESCRIPTION OF PORTION OF LOT 4, ANDOVER
INDUSTRIAL PARK NO.' .3
That portion of Lot 4 of the Plat of Andover Industrial
Park No. 3 as recorded in Volume 78 of Plats, pages 6
and 7, records of King County, Washington described as
follows:
BEGINNING of the southwest corner of said Lot 4, thence
•S 88 0 15'33" E along the south line of said Lot 4 a
• •distance of 277.00 feet to the true point of beginning;
.thence N Ol °44 E a distance of 164.19 feet; thence
• 5 88 ° 15 "33 " -E a distance of 92.96 feet; thence S 24 ° 58'35"
E along east line of said Lot 4 a distance of 102.67 feet;
thence along a curve to the right having a radius of
:• •50.00 feet an arc distance of 101.85 feet through a,
central angle of 116 °43 "02" to the south line of said
Lot 4; thence N 88°15'131 W • along said south line a
distance of 94.45 -feet to the true point of beginning.
Subject to an easement for ingress and egress over
west 10 feet of the above described portion of Lot 4'.•
Together with an easement for ingress and:egress over •
a of land 10 feet • in width lying westerly of and
• •adjacent to the west line -of the above' described portion
of Lot 4.
October 14, 1971
AIRCO OHIO
Plan Check'No. 0 -406
Hubert H. Crawley
ire Marshal
cc
Fire Protection of Building: NOT COVERED BY COVER LETTER.
Fire extinguishers placement must conform to N.F.P.A. Phamplets 10 & 10a.
Q
2. Interior hose stations must conform to N.F.P.A. Phamplet No. 14. Hose
station must be Class II type of system. Sprinkler system may be used
for water supply to 'these systems.
3. Installation of sprinkler system must conform to the standards adopted
by the City of Tukwila, Bureau of Fire Prevention.
,a. Fire department connection Must be located at the curb side of
Strander Blvd.
. Post Indicator Valve must be located at the curb side of Strander
Blvd.
If.valve pit is 'used must:be provided with a drain capable of maint-
aining the
Fire department connection and Post indicator valve, must be painted
Rustoleum # 659 yellow, as'the curb 5' [five feet]. in both direct-
ion :of the fire protection items.
.4. Exterior alarm bell must, be water operated.
0 Hose used on hose stations must be single jacket- rubber lined.
0 Nozzles must be combination fog, of the new plastic type.
Should further informtion be required, feel free to contact this office at .
any time.
0 Medical Products ucts 3623 EAST MARGINAL WAY SOUTH • SEATTLE • WASHINGTON 98134
Gentlemen:;
This will advise that we intend to use this building`
as an':office facility and for the storage, transfer and
distribution of nonflammable medical gases and related.
p roducts.
DIVI SION ,.OF AIR'.;REDU,CTION COMPA'NY,.',INCORP;O'RATED
highest purity medical gases
airco
Ohio Medical Products
HOW
TO
READ
CYLINDER
GAUGES
14,
ecfrat
Ohio Medical Products
1400 East Washington Avenue, Madison, Wisconsin 53701
Cable Address: OHIOMED
C .....b M,.. 170 6•]'lo n/ln
1600
1200 C 2800+
USE 3200
800
400
LB B SO.IN.3600
1d c•. 400
In cylinders containing liquefied com-
pressed gas and vapor in equilibrium, the
pressure in the container is determined
almost solely by the vapor pressure of
the liquid at the existing temperature,
and bears no relation to the amount of
H G M E D
tCyclopropane cylinders are Chromium plated and bear orange labels for color coding.
NET CONTENTS OF CYLINDERS FOR ALL GASES
d which remains in the cylinder. At a
given temperature, the pressure in a cyl-
inder containing a liquefied compressed
gas such as nitrous oxide, cyclopropane,
or carbon dioxide, will remain approxi-
mately constant until all of the liquid has
been withdrawn, at which time the pres-
sure drops in relation to the rate at which
the remaining gas is withdrawn. As long
as liquid remains in the cylinder, the true
contents can be determined only by
weight.
In cylinders charged with a non - liquefied
compressed gas, the pressure in the con-
tainer is related both to temperature and
the amount of gas in the container. For
such gases as oxygen, ethylene, and heli-
um and oxygen mixtures, cylinder content
may be determined by pressure; i.e., at a
given temperature when the pressure is
reduced to half the original pressure, the
cylinder will be approximately half full.
tDD tBB tAA
EQUIVALENTS
1 Cubic Foot ... 7.48 gallons ... 28.3 liters
1 Gallon 3 785 liters 0.132 cubic feet
1 Liter 0 264 gallons 0.035 cubic feet
Printed in U.S.A.
OVERLAKE BCIILDING CONSULTANTS
16071 N.E. 2ND STREET
October 12, 1971
Mr. Hubert Crawley
Building Official
City Hall
Tukwila, Washington
Dear Hubert:
• BELLEVUE, WASHINGTON 98004 • BH. 6.6223
53(p Sb'w'i ibt) ►�Q
050 (iq7i) ?
Plan Check No. 0 -406
Uses Oxygen Storage Warehouse
Type III Group E 1
Fire Zone # 3 Stories
Total Floor Area 4465 Sq. Ft.
Occupant Load 17
Valuations S39,069.00
Seismic Zone # 3
1970 Uniform Building Code
AIRCO -Ohio
We are returning to you under separate cover the above subject
plan which has been checked for conformance with the Uniform
Building Code and following are the comments of our plan checkers
1. A fire - resistive occupancy separation in conformance with
Table No. 5 -B and Section 503 is required between the office and
warehouse, rated two - hours. The door and jamb shall be rated
for 1i hour.
2. Nonabsorbent finish and backing for toilet room walls and
floor should conform to Section 1711 (a).
3. Exterior walls of Type III buildings should be incombustible
construction. Section 2001.
4. Sufficient details are necessary to show that the building
is at least one -hour fire - resistive construction throughout in
accordance with Section 2001. Ceilings are to be protected with
an approved system.
5. Eave overhangs and similar architectural projections should
comply with Section 1710, this includes canopies over entry and
loading dock.
6. Envelope ceilings should satisfy the following conditions.
Section 4303 (a) -6.
a. Should not be used to provide fire protection for beam
and girders supporting more than one floor.
b. Columns should be individukly fire protected.
Page - 2 -
Item # 6 continued.
c. Duct and outlet openings are limited to 100 square
inches in each 100 square feet of ceiling area and
.should be protected with approved.fire dampers.
d. Electric outlet boxes should be of steel and not
greater than 16 square inches in area.
7. mechanical ventilating system in baths should provide a..
five- minute air change directly to the outside. Section 1005.
8. Ramp slopes should not exceed one foot in 8 feet. Section
3306 (c) (d).
9. Surface of ramps should be roughened or of a nonslip
material. Section 3306 (f).
10. An approved automatic fire - extinguishing system in the
warehouse is required. Section 3801.
11. Fire - extinguishing system plans should be submitted to
the building official to determine compliance with applicable
building and.plumbing codes.
12. Gypsum-wallboard (interior l ath:and plaster) cannot be
installed on weather- exposed surfaces. See Section 424:for
definition.
13. Special inspection in conformance with Section 305 is
required for the following works
a. Structural concrete based on an ultimate compressive
strength in excess of 2000 pounds per square. inch.
14. "Justifying calculations and details should be provided for
ceiling system supporting 5/8" type X wallboard attached.
15. Glued - laminated lumber should be fabricated in accordance.
with - Section 2513 (c). A certificate of inspection should be
submitted to the building official. Section 2513 (e).
All other code requirements appear to have been met...
legal description
site plan
code requirements
elevations
roof scupper details
floor plan