DESCRIPTION OF WORK:
INSTALLATION OF STORAGE RACK PER ENCLOSED LAYOUT. THIS WORK HAS ALREADY BEEN COMPLETED BY
GRAINGER
PERSONNEL.
Value of Construction: $0.00 Fees Collected: $596.11
Type of Fire Protection: SPRINKLERS /AFA Uniform Building Code Edition: 1997
Type of Construction: RACKS Occupancy per UBC: 0025
doe: Devperm
Public Works Activities:
Sanitary Side Sewer: N
Sewer Main Extension: N
Storm Drainage: N
Street Use: N
Water Main Extension: N
Water Meter:
Channelization / Striping:
DEVELOPMENT PERMIT
Private: N
Private: N
** Continued Next Page **
D03 -102
Permit Number: D03 -102
Issue Date: 04/11/2003
Permit Expires On: 10/08/2003
Phone:
Phone: 847 - 535 -0595
Phone: 6' 535
Expiration Date: 1 4-
Curb Cut/Access /Sidewalk /CSS: N
Fire Loop Hydrant: N Number: 0 Size (Inches): 0
Flood Control Zone: N
Hauling: N Start Time: End Time:
Land Altering: N Volumes: Cut 0 c.y. Fill 0 c.y.
Landscape Irrigation: N
Moving Oversize Load: N Start Time: End Time:
Public: N
Public: N
Printed: 04 -11 -2003
• 1 •
City of Tukwila
Department of Community Development / 6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
Permit Center Authorized Signature:
Signature:
Print Name:
doc: Devperm
Date: �� -
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and
ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws
regulating construction or the performance of work. I am authorized to sign and obtain this development permit.
ATE-( A tJ p A 4,-A
1�
Date: 2 ///f it, 3
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is
suspended or abandoned for a period of 180 days from the last inspection.
D03 -102
Printed: 04 -11 -2003
CITY OF TUIk vWILA
Permit Center
6300 Southcenter Boulevard, Suite 100, Tukwila, WA 98188
Telephone: (206) 431 -3670
AFFIDAVIT IN LIEU OF CONTRACTOR REGISTRATION
STATE OF WASHINGTON )
COUNTY OF KING
AFFCONT 1/13/00
ss.
COW G r a i r7 e vi G , states as follows:
1. I have made application for a building permit from the City of Tukwila, Washington.
2. I understand that state law requires that all building construction contractors be registered with the
State of Washington. The exceptions to this requirement are stated under Section 18.27.090 of the
Revised Code Washington, a copy of which is printed on the reverse side of this Affidavit. I have
read or am familiar with RCW 18.27.090.
3. I understand that prior to issuance of a building permit for work which is to be done by any
contractor, the City of Tukwila must verify either that the contractor is registered by the State of
Washington, or that one of the exemptions stated under RCW 18.27.090 applies.
4. In order to provide verification to the City of Tukwila of my compliance with this requirement, I hereby
attest that after reading the exemptions from the registration requirement of RCW 18.27.090, I
consider the work authorized under this building permit to be exempt under No. 13 , and
will therefore not be performed by a registered contractor.
I understand that I may be waiving certain rights that I might otherwise have under state law in any decision to
engage an unregistered contractor to perform construction work.
GE A. Dp�%
. \c�g10/V
• i : o N OTAR Y .
: o �•
%
PUBLIC i
• ;
APP ANT
Signed and sworn to before me this
11 th day of A pr; I , 20 6
atie.e, Ate.a44
NOTARY PUBLIC in and the State of Washington,
residing at knhg
Name as commissioned:
My commission expires:
H -4
r/JiAr60-- R
County.
Alice A. Deacy
6 -16 -04
18.27.090 Exemptions. This chapter shall not apply to:
1. An authorized representative of the United States
Government, the State of Washington, or any
incorporated city, town, county, township, irrigation
district, reclamation district, or other municipal or
political corporation or subdivision of this state;
2. Officers of a court when they are acting within the
scope of their office;
3. Public utilities operating under the regulations of the
utilities and transportation commission in
construction, maintenance, or development work
incidental to their own business;
4. Any construction, repair, or operation incidental to the
discovering or producing of petroleum or gas, or the
drilling, testing, abandoning, or other operation of any
petroleum or gas well or any surface or underground
mine or mineral deposit when performed by an owner
or lessee;
5. The sale or installation of any finished products,
materials, or articles of merchandise which are not
actually fabricated into and do not become a
permanent fixed part of a structure;
6. Any construction, alteration, improvement, or repair
of personal property, except this chapter shall apply
to all mobile /manufactured housing. A
mobile /manufactured home may be installed, set up,
or repaired by the registered or legal owner, by a
contractor licensed under this chapter, or by a
mobile /manufactured home retail dealer or
manufacturer licensed under chapter 46.70 RCW;
7. Any construction, alteration, improvement, or repair
carried on within the limits and boundaries of any site
or reservation under the legal jurisdiction of the
federal government;
8. Any person who only furnished materials, supplies, or
equipment without fabricating them into, or
consuming them in the performance of, the work of
the contractor;
9. Any work or operation on one undertaking or project
by one or more contracts, the aggregate contract
price of which for labor and materials and all other
items is less than $500, such work, or operations
being considered as of a casual, minor, or
inconsequential nature. The exemption prescribed in
this subsection does not apply in any instance
wherein the work or construction is only a part of a
larger or major operation, whether undertaken by the
same or a different contractor, or in which a division
AFFCONT 1/13/00
of the operation is made into contracts of amounts
less than $500 for the purpose of evasion of this
chapter or otherwise. The exemption prescribed in
this subsection does not apply to a person who
advertises or puts out any sign or card or other
device which might indicate to the public that he is a
contractor, or that he is qualified to engage in the
business of contractor;
10. Any construction or operation incidental to the
construction and repair of irrigation and drainage
ditches of regularly constituted irrigation districts or
reclamation districts; or to farming, dairying,
agriculture, viticulture, horticulture, or stock or poultry
raising; or to clearing or other work upon land in rural
districts for fire prevention purposes; except when
any of the above work is performed by a registered
contractor;
11. An owner who contracts for a project with a
registered contractor;
12. Any person working on his own property, whether
occupied by him or not, and any person working on
his residence, whether owned by him or not but this
exemption shall not apply to any person otherwise
covered by this chapter who constructs an
improvement on his own property with the intention
and for the purpose of selling the improved property;
owners of commercial properties who use their own
employees to do maintenance, repair, and alteration
work in or upon their own properties;
14. A licensed architect or civil or professional engineer
acting solely in his professional capacity, an
electrician licensed under the laws of the state of
Washington, or a plumber licensed under the laws of
the state of Washington while operating within the
boundaries of such political subdivision. The
exemption provided in this subsection is applicable
only when the licensee is operating within the scope
of his license;
15. Any person who engages in the activities herein
regulated as an employee of a registered contractor
with wages as his sole compensation;
16. Contractors on highway projects who have been
prequalified as required by chapter 13 of the Laws of
1961, RCW 47.28.070 with the department of
transportation to perform highway construction,
reconstruction, or maintenance work.
City of Tukwila
Department of Community Development / 6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
Parcel No.: 7888900153
Address: 18370 OLYMPIC AV S TUKW
Suite No:
Tenant: WW GRAINGER INC
6: ** *FIRE DEPARTMENT CONDITIONS * **
8: ** *FIRE EXTINGUISHERS * ** - UFC Article 10 and NFPA 10.
doc: Conditions
PERMIT CONDITIONS
1: ** *BUILDING DEPARTMENT CONDITIONS * **
2: No changes will be made to the plans unless approved by the Engineer and the Tukwila Building Division.
3: All permits, inspection records, and approved plans shall be available at the job site prior to the start of any
construction. These documents are to be maintained and available until final inspection approval is granted.
4: All construction to be done in conformance with approved plans and requirements of the Uniform Building Code (1997
Edition) as amended, Uniform Mechanical Code (1997 Edition), and Washington State Energy Code (1997 Edition).
5: Validity of Permit. The issuance of a permit or approval of plans, specifications, and computations shall not be
construed to be a permit for, or an approval of, any violation of any of the provisions of the building code or of any
other ordinance of the jurisdiction. No permit presuming to give authority to violate or cancel the provisions of this
code shall be valid.
7: The attached set of plans have been reviewed by The Fire Prevention Bureau and are acceptable with the following
concerns:
9: Maintain fire extinguisher coverage throughout.
10: The total number of fire extinguishers required for your establishment is calculated at one extinguisher for each 3000
sq. ft. of area. The extinguisher(s) should be of the "All Purpose" (2A, 10B:C) dry chemical type. Travel distance to
any fire extinguisher must be 75' or less. (NFPA 10, 3 -1.1)
11: Portable fire extinguishers shall be securely installed on the hanger or in the bracket supplied, placed in cabinets or
wall recesses. The hanger or bracket shall be securely and properly anchored to the mounting surface in accordance with
the manufacturer's instructions. The extinguisher shall be installed so that the top of the extinguisher is not more
than 5 feet above the floor and the clearance between the bottom of the extinguisher and the floor shall not be less
than 4 inches.
12: Extinguishers shall be located so as to be in plain view (if at all possible), or if not in plain view, they shall be
identified with a sign stating, "Fire Extinguisher ", with an arrow pointing to the unit. (NFPA 10, 106.3) (UFC Standard
10 -1)
13: Clear access to fire extinguishers is required at all times. They may not be hidden or obstructed. (NFPA 10, 1 -6.5)
14: * ** EXITS * ** - UFC Article 12
15: No point in a sprinklered building may be more than 250 feet from an exit, measured along the path of travel. (UBC
1004.2.5.2.2)
16: Gates and barriers installed across an exit shall be of sufficient size as to be capable of opening so that the clear
D03 -102
Permit Number: D03 -102
Status: ISSUED
Applied Date: 04/02/2003
Issue Date: 04/11/2003
Printed: 04 -11 -2003
st
City of Tukwila
Department of Community Development / 6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
width of the opening is not less than the exit width required by the Building Code. (UFC 1208.3)
17: Aisles leading to required exits shall be provided from all portions of buildings. Aisles located within an accessible
route of travel shall also comply with the Building Code requirements for accessibility. (UFC 1204.1)
18: Exit hardware and marking shall meet the requirements of the Uniform Fire Code. (UFC 1207 -1212)
19: * ** SPRINKLER SYSTEMS * ** - UFC ARTICLE 10 - NFPA 13
20: Maintian sprinkler coverage per N.F.P.A. 13. Addition /relocation of walls, closets or partitions may require relocating
and /or adding sprinkler heads.
21: Sprinkler protection shall be extended to all areas where required, including all enclosed areas, below obstructions
and under overhangs greater than four feet wide. (NFPA 13- 4- 5.5.3.1)
22: All new sprinkler systems and all modifications to existing sprinkler systems shall have fire department review and
approval of drawings prior to installation or modification. New sprinkler systems and all modifications to sprinkler
systems involving more than 50 heads shall have the written approval of the W.S.R.B., Factory Mutual, Industrial Risk
Insurers, Kemper or any other representative designated and /or recorgnized by the City of Tukwila, prior to submittal
to the Tukwila Fire Prevention Bureau. No sprinkler work shall commence without approved drawings. (City Ordinance
#1901)
23: All sprinkler system plans, calculations and the contractors Materials and Test Certificates submitted to the Tukwila
Fire Prevention Bureau must be stamped with the appropriate level of competency seal. (WAC 212 -80)
24: ** *STORAGE PRACTICES * ** - UFC Article 81 @ 11
25: The critical storage height for high -piled combustible stock in closely packed piles is 12 feet. (UFC 9.110) Storage
above 12 feet may necessitate increasing the sprinkler density to extra hazard and adding smoke removal capabilities.
(UFC 8101) (NFPA 231)
26: To use any building or portion thereof exceeding 500 square feet for the storage of high -piled combustible stock. A
floor plan showing the dimensions and location of the stockpiles and aisles shall be submitted with applications for
such permits. (UFC 8101)
27: In double row racks with heights of storage up to and including 25', an average nominal 6" transverse flue space
between loads or at rack uprights shall be maintained. (NFPA 13)
28: High -piled combustible storage is combustible materials in closely packed piles more than 12 feet in height or
combustible materials on pallets or in racks more than 12 feet in height. For certain special- hazard commodities such
as rubber tires, plastics, some flammable liquids, idle pallets, etc., the critical pile height may be as low as 6
feet. (UFC article 2, sec. 209 -H)
29: Maintain minimum 6" longitudinal flue space between back to back racks. (NFPA 13)
30: Where storage height exceeds 15 feet and ceiling sprinklers only are installed, fire protection by one of the following
methods is required for steel building columns located within racks: (a) one -hour fire proofing, (b) sidewall
sprinklers at the 15 foot elevation of the column, (c) ceiling sprinkler density minimums as determined by the Tukwila
Fire Prevention Bureau. (NFPA 13)
31: Depending on the classification of the commodity being stored and the size of the storage area, smoke vents, small hose
stations and curtain boards may be required by Table 81 -A of the Uniform Fire Code. Contact the Tukwila Fire Prevention
Bureau for further information.
32: Storage of combustible materials in buildings shall be orderly and maintained not less than two feet from the ceiling
and not less than 18 inches below sprinkler heads deflectors. (UFC 1103.3.2.2)
doc: Conditions
D03 -102
+ ". Mti 4 L : `i� n.431Y �X:. '+i''.3
�,�k . .�9-t
Printed: 04 -11 -2003
City of Tukwila
Department of Community Development / 6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
33: Racks designed for high -piled storage must comply with section 2207 of the Uniform Building Code. Please contact the
Tukwila Building Department for details pertaining to design and installation standards.
34: Aisles in sprinklered building shsall be 44 inches (1117.6 mm) or more in width. Aisles shall be 96 inches (2436.4 mm)
or more in width in high -piled storage areas exceeding 2,500 square feet (232.26 m2) in area and designated to contain
high- hazard commodities. Aisles shall be 96 inches (2438.4 mm) or more in width in public accessible areas where
mechanical stocking methods are used. (U.F.C. 8102.10.2.2)
35: The required aisles width shall extend from floor to ceiling. Rack structural supports and catwalks are allowed to
cross to a height 6 feet 8 inches (2032 mm) or more above the level of the finished floor, provided that such supports
do not interfere with fire department hose stream trajectory. (U.F.C. 8102.10.3)
36: Any overlooked hazardous condition and /or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
37: These plans were reviewed by Inspector 510. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws
regulating construction or the performance of work.
Signature:
Print Name: .Ot D -k' \ A-A
doc: Conditions
D03 -102
Date: 9 A 3
Printed: 04 -11 -2003
iLii+G ?3.�va3 v'i ft.Itd4�' : u�:+C
Received: 2/19/03 1:49PM;
FEB 19 '03 12:51PM TUKW1 DCD /PW
Site Address:
Tenant Name: LA . w. C.7-- rf /Ai o-rzn
Property Owners Name: Ac AJ
Mailing Address:
u i�i'l• "it t ~ i , 'i"I�I;
t +'� d1 , , I Iy! (� �' �d 1 n
^ ik�:'t 1'r:tyF1� �i:t ' { `��T,�niil �8 tiKaI. tNj
4 .1/11
Nance: /Qo A r rz — R ".r' 6
w . w • G-,.. ra /,v G- et_
po
Mailing Address:
Company Name:
Mailing Address:
Contractor Registration Number:
* *An original or notarized copy of current Washington State
Company Name:
Mailing Address:
Contact Person:
E -Mail Address:
Company Name:
Mailing Address:
Contact Person:
E -Mail Address:
\Ipplic tiona\permitapplication(14003)
IR003
CITY OF TUKWIIA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
King Co Assessor's Tax No.: 7€'2/q0 - 0 t S3
V E. SbtJ
ANC- •
Alodu
S E /
/6 • La — /
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
'!*Please Print"
i
�iLJ .
LA/
2064313885 -> GRAINGER; Page 2
PaRc 1
Suite Number:
New Tenant:
Day Telephone:
8
k- E •ter
Ciq
Fax Number: 8
City
Day Telephone:
Fax Number.
G
Floor:
... Yes
Slate
Scale
P.2/6
EJ ..No
State Zip
Zip
City
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Expiration Date:,
Contractor License must be presented at the time of permit issuance **
4 1, a l 4
I 11' ld,., tl,. F�d ki171 ' i1AT 54
� t � . ,; ,`'x { i ^ i1'*,', al' It'rli44 "ably ,
,;, c lR•i 1 tl l �', ,p r t i , x I ,� ^ L , I
1 a.,., N> ,r1a i� I II`, d i�., i1. I,ImC
Zip
city
Day Telephone:
Fax Number:
G7 /
Stem Zip
?c 7/ P4 9 — c7 7.9
'107/ (' o7 ?f
'' ; ; ; :': w !
;
„'
..,;.• ., r ',] • •
...Existm "
• .; • ,; , ,,,.
;liite :or ; ::,
::.4.I el; iiodej d
,'ljddittbla ....:::;;I:
1 ' :Emt,,
,;.w .Stru'ctti b,r- ,
•;; ;. � ";' , r „ � ;^"';
. l . ''
,',:. ,2� ;.,,r
.Ir;,,;,; % :' ; yp e �; v, £ ' :
' ' 1Cofi4p t - 45;
, r l ^ e r, :t $ t i..
r ',;: )' . pa ' � t►f ' ' ' w' „ w ' ;
' - 7,1,.,, i; er
C;'„,; rr
"' t ..
r ...: ' w i. r . .. . iw . ii i
.r;
F}i JJ((r�
�';,"7.IX.lituiri... i'',...;.: :• nlnn r
',Y1' „ � h .. .m
::Pb(NS . � L:. i ' � :7 , i y
-
iu'1 .� ,..1.,1.11l. wn . •'
':Act:e'sspry„Siructu:kb,$7: ' :;
„ IfFtuched, Outage; ;, .r.....7.'
' ‘'.' . ,..w: :.r,:x.l:.�.w.
w
; ,Att4Ch p, ; .. ....;;17 , ,,
, Derab!( 1$:0axpoltt; ';"i'' ";r„
.;. :1.4 , .,
-
}
Received: 2/19/03 1:50PM;
FEB 19 '03 12 :53PM TUKW1 DCD /PW
Valuation of Project (contractor's bid price): S
Scope of Work (please provide detailed information): N 'J
7 'lL i •r C„t -s .. 4.
C✓c,
wpplicuioasy+ermk applk:Mion (1 -2003)
Inou3
2064313685 -> GRAINGER; Page 3
Page 2
,e G-
P.3 /6
Existing Building Valuation: S
Will there be new rack storage? j d .. No If "ycs ". see Handout No. for requirements.
-Provide All Buildirt rg re
teamin:S ua,E'oota a 1'
PLANNING DIVISION:
Single family building footprint (,area of the foundation oPatl structures, plus any decks over 18 inches and overhangs greater than 18 inches)
"For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area for accessory dwelling:
'Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑...Yes ❑ ..No If "yes'', explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
Sprinklers Automatic Fire Alarm ❑...None ❑ .. Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ .. Yes
If "yes", attach list of materials and storage locations on a separate 8 -1/2 x 11 paper Indicating quantities and aterial Safety Data Sheets,
UTILITY DISTRICTS:
Note: If the utility district is not City of Tukwila, you must provide written verification and approval from that utility district at the time of permit
application.
Water
❑ .. City of Tukwila Water District ❑.. Water District #125 D. Highline Water District 0... City of Renton Water District
Sewer
❑ .. City of Tukwila Sewer District 0.. Val Vue Sewer District 0.-City of Renton Sewer District ❑ ... City of Seattle Sewer District
❑ .. Septic System (If property is served by a. septic system, 2 copies of approved septic design from King County Health Department must be
submitted at the time of permit Application)
v ti
Received: 2/19/03 1:51PM;
FEB 19 '03 12 :53PM TUKW: DCD /PW
e•.r. .r�.�1. yr..IV w.nlyu q T - y , .. +t.- a �o a � .yg 1 ��
' ,•. rµ r . 4 I��'� i• ^� ..1 Y ¢ i 1 I \I F l�I ✓ ^� �J 1 I ' .�• �� ! \� J.f
L4 •• _ ... 4. .. 1!11. 'CJ
1 1'11 II( •N 1'
•t� U 1.1 nl ` 1 1 1r 1 1r I 1 1 V 1 w l
Yr � !i • �II '1' 1 . 11 I.N I• r f' � .�iMY• IV YYI\ !
Scope of Work (please provide detailed Information): A/c, P' l
Street Use:
❑ .. Street Use
Land Altering and/or Hauling`
0 r, Land Altering: ❑...Cut
'Please ryi'e'�;to;u4lic Works;;Buyletirr;1�fdr•' fe, ��'Otid'e�it�ii►ate;slice;;1;:' ' , r,
❑... Channelization/Striping
Storm Drainage:
[] .. Storm Drainage ❑...Flood Control Zone
cubic yards
Sewer Information:
.• • City of Tukwila Sewer District ❑ ,. Val Vue Sewer District
.. • Sanitary Side Sewer ❑ ., Sewer Main Extension
Water Information:
❑ .. City of Tukwila Water District ❑ .. Water District #I25
❑ .. Water Main Extension 0 .. Private
.. • Water Meter/Exempt:
0 .. Water Meter Permanent #:
❑ .. Water Mctcr Temporary #:
0 .. Fire Loop/Hydrant (main to vault) #:
Monthly Service Billing to:
Name:
Mailing Address:
Water ... ❑
Water Meter Refund/Billing:
Name:
Mailing Address:
\pilemiea►tponnit application (1 - 2001)
112003
2064313665 -> GRAINGER; Page 4
Call before you Dig: 1- 800 - 424-5555
Sewer ... []
❑... Curb cut/Access/Sidewalk
Paae 3
❑...City of Renton Sewer District
❑
.. Private 0.. Public
0... Highlinc Water District
City
Sewage Treatment ❑
Day Telephone:
❑...Fill cubic yards ❑ .. Hauling
Size(s): ❑ .. Landscaping Irrigation
0 ,. City of Seattle Sewer District
❑ ...City of Renton Water District
❑...Public
Sizc(s): ❑ .. Deduct O ... Water Only
Sizc(s):
Sizc(s): ❑ .. Est. Quantity: gallons
0 .. Miscellaneous:
Day Telephone:
sore
Fire Line .... ❑
Cily Stuo Zip
P.4/6
zip
;,U ~;Type,: "1' . ;? . ;I::::::. ' ..
,:;: ri!.,
,1 nif TYte `;,; ; °..:::';,.., '; , ,.,. ; . :.;
Qtt!:-:
; :17p : 'hVg: :: . ., . :• , QM , .:
Mili,1,Or' /GOOl r0i?QX�', ' : ;;''i ";, .;r'QiS
Furnace<100K BTU
Air Handling Unit
>=10,000 CFM
Other Mechanical
Equipment
0-3 HP /100,000 BTU
y
Fumacc>100K BTU
Evaporator Cooler
3 -15 HP /500,000 BTU
oor Furnace
Ventilation Fan
15 -30 HP /1,000,000 BTU
Suspended /Wall /Floor
Mounted Heater
Ventilation System
30 -50 lJF /1,750,000 BTU
•
Appliance Vent
Hood
50+ H1' /1,750,000 BTU
Heat/Rcfrig/Cooling
System
Incinerator - Domestic
Air Handling Unit
<=10,000 CFM
Incinerator— Comm /Ind
Received: 2/19/03 1:51PM;
FEB 19 '03 12 :54PM TUKW1 DCD /PW
I "'1 ,y r r
r J u�hlbiJ YS�1L , G1 iII;
'tai r:7 X77 7 . 7 �.., s7 ..1� „�
, ,ri, . 7
, �1'l i 1 ' l t } : i
• {, �1�NN I "J'�/1;
Vl,lfl h� I ►ills 1,
1
I'
a
1, ;#
.1 � 1;1-
�.1'.l'lilr.' 4 1
u iy i i l COtntiIrf �' r 1 1� f.
l ' a 1 orta,l�ttlexam l
;iity r
0,1:91
MECHANICAL CONTRACTOR INFORMATION
Company Name: __ /tJ
Mailing Address:
City
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date:
**An original or notarized copy of current Washington State Contractor License must be presented at the time of permit issuance **
Valuation of Project (contractor's bid price): $
Scope of Work (please provide detailed information):
Use: Residential: New ....0 Replacement .... Q
Commercial: New .... ❑ Replacement ....ID
Fuel Type: Electric 0 Gas ....❑ Other:
Indicate type of mechanical work being installed and the quantity below:
/ • r `a p � 1 � 1fµ r 1• tJ1���� 4 1 �t`
1
1'4 !•1 1. •� 91�� 1 1 11 - ,r i' ��}p��{ "' L, ` al �'r'' 1 i a,a+-I ,1 f i n �A�1
� ., a ' Y �� '. � . 1 � .•{ �� l '1 "'111,,,111"""IIIWWW 1' u 9 x� ���!�11 1v � ����, ��fU:�� l iq!'i �;;U
s w; hr' y fell t 1 141 un 1 �,. „ J �'1 J ( 4 4.44 ' '' ����. � . F' If''I Il + r
11,, 9;i,y111 Ifs �i.1.Nq 1tly��!y11 9:i„ 4 1 at6y1f 'r „4 {•1 1,111{ a1,Y ,JW , 1 �Y1 ^� 71f � ■ Y fi r. l ,1� j r���l �r 1 �` 1 t 'I I1 Y ,.
,�F.W ]'diM IMI Al ��P. IMtV 1r I.Jr(,14 . �I ..� 1 , 1 ..�f•'A.r.'!.. ...I.f . �In 1.. �JJf. w. Ali. LI �il.�ll '1 �M ��r /21•.14 �nl�'f•i� a�
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may extend the time for action by the applicant for a period not exceeding 180 days upon written request by the applicant as
defined in Section 107.4 of the Uniform Building Code (current edition). No i pplication shall be extended more than once.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
Date Application Accepted:
1oppgcat;o0u\pamit a0pticadon (1-2003)
1/2003
I3UILDING OWNS AUTHORIZED AGENT:
Signature: j 6 � 4 -
2064313665 -> GRAINGER; Page 5
Print Name: iQo,0 ,— A - . ,C7 / \r ",4,A Day Telephone: ef
L.v • c,1.. G 12.4 -4i 'O Mel—
Mailing Address: ov ,•a .. . . ' r
Date Application Expires:
- t -o
Page 4
c;n� „ v ;.;maxr*•;Dy6r:Y3'�rr ? ?. +r,.r; h'; ^.i
State
Date:
City Statc Zip
Staff Initials:
P.5/6
to
Zip
Parcel No.: 7888900153 Permit Number: D03 -102
Address: 18370 OLYMPIC AV S TUKW Status: PENDING
Suite No: Applied Date: 04/02/2003
Applicant: WW GRAINGER INC Issue Date:
City of Tukwila
6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
z
W
JU
O 0
c
w
J
�
W O
2
Receipt No.: R03 -00421 Payment Amount: 145.11
cn
Initials: BLH Payment Date: 04/02/2003 12:32 PM = d
User ID: ADMIN Balance: $227.75 _
z �
�
z I-
uj
O • N
O H
W
- O
..Z
U =
O H
Payee: JONATHAN RAGAN
RECEIPT
TRANSACTION LIST:
Type Method Description Amount
ACCOUNT ITEM LIST:
Description
doc: Receipt
Payment Check 1937
PLAN CHECK - NONRES
145.11
Account Code Current Pmts
000/345.830 145.11
Total: 145.11
7261 04/03 971.6 TOTAL. 145. 1:1.
Printed: 04 -02 -2003
z
Parcel No.:
Address:
Suite No:
Applicant:
Receipt No.:
Initials:
User ID:
Payee:
TRANSACTION LIST:
Type Method
doc: Receipt
Payment
City of Tukwila
6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
7888900153
18370 OLYMPIC AV S TUKW
WW GRAINGER INC
R03 -00457
SKS
1165
GRAINGER
ACCOUNT ITEM LIST:
Description
Check
BUILDING - NONRES
STATE BUILDING SURCHARGE
Description
1630842
RECEIPT
Account Code
000/322.100
000/386.904
Permit Number:
Status:
Applied Date:
Issue Date:
Payment Amount: 451.00
Payment Date: 04/11/2003 10:57 AM
Balance: $0.00
Amount
451.00
Current Pmts
446.50
4.50
Total: 451.00
D03 -102
APPROVED
04/02/2003
7620 04/11 4 716 TOTAL 45100
Printed: 04 -11 -2003
COMMENTS: / ,I' / 7' �
. 1 _, Ltr4 ! ,..r e
S
p �t �,., - ,e, �a 4,� ,1--7' :4;7 ~
. ,,,47
cApac rre( .
7 �n� ii ' 4'1C -;, ,,. •- /�G
.
ef � ~ r . / 2�, 44 c .Z6 de,oef
Ada s s:
l 'q)�
3 Q,�, -,..4 e .,--i- c ,-;y - h S
,..,,
c _e,a, 4.7/ ,//', .rt" --i-,
"ze.,,
%>, m « - ,fir, /./eidi,
A e.f d I4 „ .A 7,/ 1 .
"5) 4�d /21i5 / 4/ ,..4_,,t4.,o.e.r ,....,
Speci4l ,n. ,ructions:
�,�
) A0 . a-7.7,,'>70,5„.0.7,..., `, 1-. li /.4
Project:
/1� IA)
IV A
Type of Ins ection:
/1
Ada s s:
l 'q)�
Yale
AV
Date Called:
- e,c9,
3 3 h
Speci4l ,n. ,ructions:
�,�
Date Wanted:
i
a.m
Re nester:
t T
x ,4/1
or 7 G
.. z
INS ' CTION RECORD
Retain a copy with permit
INSPECTI N NO.
CITY OF TUKWILA BUILDING DIVISION_
6300 Southcenter Blvd., #100, Tukwila, WA 98188/ (/ /3- (206)431 -3670
Approved per applicable codes.
D040.),
PER
NO.
Corrections required prior to approval.
A iY
Date: 17?
--0
Ej $47.00 REINSPECTY6N FEE REQUIRED. Prior to`inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
_58
COMMENTS:
^^
1 l"
n h
(� L
Type of Inspectikn:
H 1
Tess:
i .370
( 0
e "---- CG
t 6, ,1(a
4 00 .0_ PrSi lit r'(4..1/--
,
" i''' (0 L.--I t L i g 'S'i 6 "7 —
, 4-�
/
. �j4 ,r a.m.
1
7 P 1
- ° d-f/L 0 f T (} A.
Phone No: �Cl
X *-- 2-x"4 - cba k..1
z 7
I/3„,,,
/..( /19( f�>r i
/ ` . r -
,,�1
I
Project:
11
^^
1 l"
n h
(� L
Type of Inspectikn:
H 1
Tess:
i .370
( 0
d
it
Date Called:
C '3
/
Special Instructions:
C
, 4-�
Date Waned:
. �j4 ,r a.m.
1
Requester:
O iA i
- ° d-f/L 0 f T (} A.
Phone No: �Cl
X *-- 2-x"4 - cba k..1
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
Approved per applicable codes.
Inspector:
INSPECTION RECORD
Retain a copy with permit
0 LCorrections required prior to approval.
Date:
,
$47.00 REINSPECTION FEE ItEQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
COMMENTS:
Type of Intiorr:
y J
/
l 6 ( —fa A .9-,✓
/'t� ah" :v
cf J .rFf.r1 �.✓�
Cl' -, odic -.'
Special Instructions:' ,
Date Wanted:
a m,
Requester: f
Phone NfS
��S �..) °5
l
73�,2
c1e
4 4A/f , A
J 'h'»5
A,rr✓ `A
%T
s; �,4• s
v
r'ss ;.-v (
r,77;-7 dam-
J .
Project: .
//I t26
Type of Intiorr:
y J
Address:
/8376' �4 //�!r)/ /,
/4,3 --
Date Called: ; . �,
/ - 5-0 y ; "1 • L.
Special Instructions:' ,
Date Wanted:
a m,
Requester: f
Phone NfS
��S �..) °5
Io
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
❑ Approved per applicable codes. N O Corrections required prior to approval.
In spect •
l u.Mw.a
Date:
/` g— e/
v
f0.00 REINSPECTION REQU) 1{ED. Prior to inspection, fee must be
i aid at 6300 Southcenter Blvd., SGite 100. Call to schedule reinspection.
Receipt No.:
Date:
COMMENTS:
Rz 1(4./4 p..., G.)‘//44 X
49 fr-koi--- 7p7 1 le-4
Ai /,4- E.., )
hi
r,47/ ri fc-twi-
c ,
5 4 e 4( 17 e ie.,./.. .,z r7e..is-s-4-
.4-A., 4-, rx7
kr o
/fr/
A
Project: ,
k, ) Li) • eV6,e Oteit
Type of In ect
Address:
1 C ? 7 0 D (214,e4APC /4"Of
Date Called: i _ t2•3
3. gicq- I
Date Wanted:7, 1 a.m.
9 . 14442P-? P.m.
Sprecial Instructions:
c ,,, cr
?
V4 ill
Requester()
Li
PhoM 5 ) _57 _ 5 c(
2 ] Approved per applicable codes.
Inspecto
•
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 981 88
Date:
9z
PERMIT
(206)431
orrections required prior to approval.
El $47.00 REINSPECTd9#J FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
City of Tukwila
Fire Department
Project Name 61 r c
:Address '
Retain current inspection scheduls
Needs shift inspection
\/
/ Approved without correction notice
Approved with correction notice issued
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre-Fire:
Permits:
r ; ;
Authorized Signture
FINALAPP.FRM Rev. 2/19/98
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
Steven M. Mullet, Mayor
Thomas P. Keefe, Fire Chief
Permit No. '.A%S'
Suite #
Date
T.F.D. Form F.P. 85
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: 206-575-4404 • Fax: 206-575-4439
41 •••■ ipt • v.... • • r
STORAGE RACKS
DRIVE-IN RACKS
CANTILEVER RACKS
MEZZANINES
CONVEYORS
CAROUSELS
STEEL SHELVING
MOVABLE SHELVING
STORAGE TANKS
MODULAR OFFICES
GONDOLAS
BOOKSTACKS
161 ATLANTIC STREET
SEIZMIC
MATERIAL HANDLING ENGINEERING
• POMONA
EST. 1985
CITY APPROVALS
STATE APPROVALS
PERMITTING SERVICES
PRODUCT TESTING
FIELD INSPECTION
SPECIAL FABRICATION
SEISMIC ANALYSIS
OF STORAGE RACKS FOR
W.W. GRAINGER
18370 OLYMPIC AVE
TUKWILA WA
#03 -1360
APPROVED BY
r X PIRES
APR 12 2894- i
PF\/t1ON NO
R ECETVCO
or? OF
OEC 1 6 1003
pERMII Vc ,v� i n
ALASKA NEVADA
AR¢ONA NEW MEXICO
CALIFORNIA CREGCN
COLORADO PENNSYLVANIA
IDAHO UTAH
MISSOURI WASHINGTON
• CA 91768 • TEL: (909)869 -0989 • FAX: (909)869 -0981
a� y iarvnN;.u��� r- rat('z*tl:"' ^.�(u' 14�R.Og4tNanxw,
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 2
CALCULATED BY RF
17
OF
DATE 10 -15 -2003
TABLE OF CONTENTS
DESCRIPTION PAGE #
COVER SHEET 1
TABLE OF CONTENTS 2
SCOPE 2
PARAMETERS 3
CONFIGURATIONS 4 - 5
COMPONENTS & SPECS. 6- 8
LOADS AND DISTRIBUTION 9
LONGITUDINAL ANALYSIS 10
COLUMN 11
BEAM 12
BEAM TO COLUMN 13
BRACING 14
OVERTURNING 15
BASE PLATE 16
SLAB & SOIL 17
SCOPE:
THIS ANALYSIS OF THE STORAGE SYSTEM IS TO DETERMINE ITS COMPLIANCE WITH
THE APPROPRIATE BUILDING CODES WITH RESPECT TO STATIC AND SEISMIC FORCES.
THE STORAGE RACKS ARE PREFABRICATED AND ARE TO BE FIELD ASSEMBLED ONLY,
WITHOUT ANY FIELD WELDING.
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 3 OF 1 7
CALCULATED BY RF DATE 10 -15 -2003
PAHAMETEHS:
STORAGE RACKS CONSIST OF SEVERAL BAYS, INTERCONNECTED IN ONE OR BOTH
DIRECTIONS WITH THE COLUMNS OF THE VERTICAL FRAMES BEING COMMON BETWEEN
ANY ADJACENT BAYS.
THE ANALYSIS WILL FOCUS ON A TRIBUTARY BAY TO BE ANALYZED IN BOTH
LONGITUDINAL AND TRANSVERSE DIRECTION.
STABILITY LONGITUDINALLY IS DEPENDANT ON BEAM TO COLUMN MOMENT,
WHILE THE BRACING ACT TRANSVERSELY.
1. COLUMN.
2. BEAM.
3. BEAM TO COLUMN.
4. BASE PLATE.
5. HORIZONTAL BRACING.
6. DIAGONAL BRACING.
7. BACK CONNECTOR.
TRANSVERSE
TRIBUTARY AREA
LONGITUDINAL
TOP VIEW
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
W.W. GRAINGER
W.W. GRAINGER
4 OF
PROJECT
FOR
SHEET NO.
17
CALCULATED BY RF DATE 10-1 -2003
CONFIGURATIONS
TYPE A
40"
108"
79"
3
3,000 lb.
2
3,000 lb.
1
61"
61"
39"
2
2
3,000 lb.
96" — 4
TYPE B
4 96"
61"
• . 33" — 71' 6I` 33'4
40"
115"
4,500 lb.
2
4,500 lb.
1
61"
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 5 OF 1 7
CALCULATED BY RF DATE 10 -1 -2003
litf % ' -. s,4,k'ii0J+ o
1 4,605 lb. 811 in.lb. 7,651 in.lb. <- std.conn.
2 3,070 lb. 10,490 in.lb. 12,233 in.lb. <- std.conn.
3 1,535 lb. 9,977 in.lb. 6,988 in.lb. <- std.conn.
TYPE A DESIGN LOAD = 3000#
BASE PLATE
COLUMN
BEAM
11
5 X 3 X .375
BASE PINNED
"I
COLUMN
3x1- 5/8x10ga
STRESS =0.77
-I
4x2- 1/2x13GA / 3400
MAX LOAD /LEVEL = 4,533 lb.
BEAM IS O.K.
OVERTURNING
BRACING
SLAB & SOIL
•NI
ANCHOR STRESS = 0.01
# OF ANCHORS = 1
HORIZONTAL J
2 1/4 X 1 1/2 X 16 GA (NEW)
STRESS = 0.10
DIAGONAL -
2 1/4 X 1 X 16 GA (NEW)
STRESS = 0.48
PUNCT. STRESS = 0.99
BENDING STRESS =0.99
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 6 OF 1 7
CALCULATED BY RF DATE 10-15 -2003
TYPE A
SPECIFICATION
- MAIN STEEL 50000 PSI
- BASE PLATE STEEL 36000 PSI
- ANCHOR - WEDGE TYPE 1/2 x 3 -1/2 MIN. EM
- FLOOR SLAB 5" X 2500 PSI. REINFORCED 2
- SOIL BEARING PRESSURE 1000 PSF
- SEISMIC ZONE 3.
- TYPE = INTERCONNECTED UNITS.
SECTION
AXIAL FORCE
3,000 lb.
3
3,000 lb.
2
3,000 lb.
1
36E 61"
o h_
61"
161 61"
• J�
fi 96" — 71'
lu = 96"
MOMENT BEAM MOMENT
fi 33" _'
12#
•
470#
205#
0
1 4,570 lb. 799 in.lb. 9,751 in.lb. <- std.conn.
2 2,285 lb. 14,704 in.lb. 9,352 in.lb. <- std.conn.
TYPE B DESIGN LOAD = 4500#
BASE PLATE
COLUMN
BEAM
q
5 X 3 X .375
BASE PINNED
COLUMN
3x1 -5/8x1 Oga
STRESS =1.12
g
4x2-1/2x13GA / 3400
MAX LOAD/LEVEL = 4,533 lb.
BEAM IS O.K.
OVERTURNING
BRACING
SLAB & SOIL
q
ANCHOR STRESS = 0.01
# OF ANCHORS = 1
HORIZONTAL \I
2 1/4 X 1 1/2 X 16 GA (NEW)
STRESS = 0.10
DIAGONAL \I
2 1/4 X 1 X 16 GA (NEW)
STRESS = 0.4 8
PUNCT. STRESS = 0.85
BENDING STRESS =0.81
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 7 OF 1 7
CALCULATED BY RF DATE 10 -15 -2003
TYPE B
SPECIFICATION
- MAIN STEEL 50000 PSI
- BASE PLATE STEEL 36000 PSI
- ANCHOR - WEDGE TYPE 1/2 x 3 -1/2 MIN. EM ED.
- FLOOR SLAB 5" X 2500 PSI. REINFORCED
- SOIL BEARING PRESSURE 1000 PSF
- SEISMIC ZONE 3.
- TYPE = INTERCONNECTED UNITS.
SECTION
AXIAL FORCE
240"
115"
4,500 lb.
4,500 lb.
96 " --71'
lu = 96"
MOMENT BEAM MOMENT
61"
61"
511#
61"
21# 39"
33"
650#
■111=1111e
i 7#
s'r�:�- ritiXsz:
1 2,285 lb. 15,479 in.lb. 7,739 in.lb. <- standard conn.
TYPE C DESIGN LOAD = 4500#
BASE PLATE
COLUMN
BEAM
- q
5 X 3 X .375
BASE PINNED
\I
COLUMN
3x1- 5/8x10ga
STRESS =1.20
4x2 -1 /2x13GA / 3400
MAX LOAD /LEVEL = 4,53 3 lb.
BEAM IS O.K.
\I
OVERTURNING
BRACING
SLAB & SOIL
ANCHOR STRESS = 0.04
# OF ANCHORS = 1
HORIZONTAL 'j
2 1/4 X 1 1/2 X 16 GA (NEW)
STRESS = 0.10
DIAGONAL '
2 1/4 X 1 X 16 GA (NEW)
STRESS = 0.47
PUNCT. STRESS = 0.61
BENDING STRESS =0.51
\I
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 8 OF 1 7
CALCULATED BY RF DATE 10 -15 -2003
TYPE C
SPECIFICATION
- MAIN STEEL 50000 PSI
- BASE PLATE STEEL 36000 PSI
- ANCHOR - WEDGE TYPE 1/2 x 3 -1/2 MIN. EM :ED.
- FLOOR SLAB 5" X 2500 PSI. REINFORCED 240"
- SOIL BEARING PRESSURE 1000 PSF
- SEISMIC ZONE 3.
- TYPE = SINGLE ROW UNITS.
SECTION
AXIAL FORCE
120"
4,500 lb.
61"
61"
262#
-Ie- 9 6"
lu = 96"
MOMENT BEAM MOMENT
61"
39"
33" 4
�j
rg i n li Z 11 1 11 6 1111111111 1
INC.
MATERIAL HANDLING ENGINEERING CALCULATED BY RF DATE 10 -15 -2003
TEL: (909) 869-0989 • FAX: (909) 869 -0981
161 ATLANTIC AVENUE • POMONA • CA 91768
LOADS & DISTRIBUTION: TYPE B
LIVE LOAD PER SHELF (BASED ON CLIENT SUPPLIED DATA) = wLL
DEAD LOAD PER SHELF = wDL
SEISMIC BASE SHEAR DETERMINED IN ACCORDANCE WITH SECTION 1630.2.1 OF THE 1997 UBC = V.
WHERE: V = ((2.5 x Ca x I) / R) x Wtotal
Wtotal = (wLL/2 + wDL)
SEISMIC ZONE = 3
Ca = 0.36
I = 1.00
SOIL COEF. = Sd
R (LONGITUDINAL) = 5.6
R (TRANSVERSE) = 4.4
wDL = 70 LB
n =2
DEPTH= 33 in
LONGITUDINAL DIRECTION:
Viong = [2.5 *0.36* 1 *(9000/2 +140)/5.6]/1.4
= 533 lb
Fl = V Whi /EWh
TRANSVERSE DIRECTION:
Vtrans = [2.5 *0.36 *1 *(9000/2 +140) /4.4]I1.4
= 678 lb
Fi = V Wh1 /EWh
LEVEL
1
2
TOTAL FRAME LOAD = 9140 LB
(SECTION 2228.5.2 )
(SECTION 2228.5.2 )
INTERCONNECTED UNITS
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 9 OF 1 7
'SEISMIC DISTRIBUTION:
5.0 4,500
115.0 4,500
120 IN
IN
WEIGHT
LB
HEIGHT
IN
5.0
120.0
WXH
LB -IN
22,500
540,000
562,500
Fi (long)
LB
21.3
511.3
533 LB
Fi (trans)
LB
27.1
650.8
678 LB
Mot
IN -LB
135.6
78,096.6
78,232 IN -LB
4
SEIZMIC
wc.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 - 0981
161 ATLANTIC STREET • POMONA • CA 91768
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 10 OF 1 7
CALCULATED BY RF DATE 10-15 -2003
LONGITUDINAL ANALYSIS :TYPE B
THE ANALYSIS IS BASED ON THE PORTAL METHOD, WITH THE POINT OF CONTRA FLEXURE OF THE
COLUMNS ASSUMED AT MID - HEIGHT BETWEEN BEAMS, EXCEPT FOR THE LOWEST PORTION, WHERE
THE BASE PLATE PROVIDES ONLY PARTIAL FIXITY, THE CONTRA FLEXURE IS ASSUMED TO OCCUR
CLOSER TO THE BASE.(OR AT THE BASE FOR PINNED CONDITION, WHERE THE BASE PLATE CANNOT
CARRY MOMENT).
Vlong = 2 * Vcol = 533 lb.
Vcol = 266 lb.
F1 = 11 lb.
F 2 = 256 lb.
BASE ASSUMED PINNED.
Mbase = 0 in.lb.
Mupper + Mlower = Mconn'R' + Mconn'L'
Mconn'R' = Mconn'L'
Mconn * 2 = Mupper + Mlower
Mconn = [Mupper + Mlower] /2
RESULTING FORCES ON COLUMN
SECTION AXIAL LOAD MOMENT
1 4570 799
2 2285 14703
Mconn
9751
F2
Mconn "L"
M
Mupper
- 7
LI
Mbase
g SLAB
Beam to
Col. Conn.
Col. to slab.
Mconn "R"
.r.
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
W.W. GRAINGER
PROJECT
FOR
SHEET NO. OF
W.W. GRAINGER
11
17
CALCULATED BY RF DATE 1 0- 15-2003
COLUMN ANALYSIS :TYPE B
COLUMN IS ANALYZED PER AISI COLD - FORMED STEEL DESIGN MANUAL.
Pmax = 2,285 lb. Mmax = 14,704 in.lb.
Kxlx /rx = 1.2 * 115 / 1.236 = 111.6 <- GOVERNS
Kyly /ry = .8 * 61 / .594 = 82 . 2
Cc = (27c "2E /Fy) ".5
= 107.0
SINCEaKI/# > 2 2E /23(KI /r) "2
Fa = 11,979 psi.
fa /Fa = Pmax /(area *Fa) = 0.26 >.15
F'e = 12n "2E /23(Kxlx /rx) "2
F'e = 11,979 psi.
Fb = .6 *Fy = 30,000 psi.
Cm *fb /Fb[1- fa /F'e] = 0.87
COMBINED STRESS =1.12
Front View
A
�T� ---
B
. � _
SECTION PROPERTIES
A = 3" B = 1.625"
C= .5" D = 0"
E =0" Wt. = 0#
t1 = .1345" t2 = 0"
Area = .747 "2
Ix = 1.141 "^4 ly = .264 "4
Sx = .76 "3 Sy = .302 "3
rx = 1.236" ry = .594"
108"
113"
Side Vie
61"
39"
r ili t i ;;; IIIIIIIII II
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 12 OF 1 7
RF
CALCULATED BY DATE 10 -15 -2003
BEAM ANALYSIS :TYPE B
BEAM TO COLUMN CONNECTIONS PROVIDE ADEQUATE MOMENT CAPACITY TO STABLIZE THE SYSTEM,
ALTHOUGH IT DOES NOT PROVIDE 100% FIXITY. THUS, THE BEAMS WILL BE ANALYSED ASSUMING
THEY HAVE PINNED ENDS. FOR THE COMPUTATION OF BEAM TO COL. MOMENT CAPACITY, THE
PARTIAL FIXITY OF THE BEAM,(ASSUMED AT AN ARBITRARY 25% OF THE FIXED END MOMENT OR
2,000 in.Ib. WHICH EVER IS SMALLER) WILL BE ADDED.
lact = 96.0 in. 2.5"
Imax = [1950 + 1200(M1/M2)]b/Fy 1.75 " —i
SINCE M1 /M2 = 1.0
Imax = 3150 *b /Fy = 158 in.
SINCE Imax > lact Fb = .60Fy = 30,000 psi.
MAXIMUM STATIC LOAD PER LEVEL DEPENDS ON 4"
1) BENDING CAPACITY
M = Sx* Fb = wI "2/8
= 30600in.Ib.
CAPACITY = 2(8 *M /I) = 45331b.
2) MAXIMUM ALLOWABLE DEFLECTION (L/180).
A = 5w1 "4/384E1
CAPACITY = 2[(384E1)/(5 *180 *1 "2)] = 57631b.
MAXIMUM STATIC LOAD PER LEVEL IS 4,533 lb.
ALLOWABLE AND ACTUAL BENDING MOMENT AT EACH LEVEL.
Mstatic = wI "2/8 = LIVE.LOAD *L/(2 *8) Mallow(static) = Sx * Fb
Mimpact = 1.125 *Mstatic Mallow(seismic) = 1.33 * Sx * Fb
Mseismic = Mconn (SEE LONG. ANALYSIS)
LEVEL Mstatic Mimpact Mallow Mseismic Mallow RESULT
1.125 Mstatic (static) (seismic)
1 27000 30375 30600 9751 40799 GOCD
2 27000 30375 30600 9351 40799 GOOD
1
1
I
1
= .0897 in.
Sx = 1.020 in. "3
Ix = 2.110 in. "4
1.625"
MATERIAL HANDLING ENGINEERING
TEL: (909) 869 -0989 • FAX: (909) 869 -0981
161 ATLANTIC AVENUE • POMONA • CA 91768
BEAM TO COLUMN ANALYSIS: UNARCO
Mconn max= Mconn. seismic + Mend
112,233 IN -LB I
CONNECTION CAPACITY DEPENDS ON THE FOLLOWING PARAMETERS:
1) SHEAR CAPACITY OF BOLTS
BOLT 0= 1/2 IN
Fv= 21,000 PSI
Fy= 50,000 PSI
Pmax- shear= Fv * Area
= 21000 PSI * (0.5 IN)A2 * n/4
= 4,123.3 LB
2) BEARING CAPACITY ON COLUMN
Fu= 65,000 PSI
PROJECT W.W. GRAINGER
r ili rr i At iallialil lFOR W.W. GRAINGER
INC. SHEET NO. 13 OF 1 7
CALCULATED BY RF DATE 1 -15 -2003
Pmax -brg= Bearing Area * Fbearing
= (0.5 * thickness) * (1.0 * Fu)
= (0.5 * 0.1875 IN) * (1.0 *65000 PSI)
= 6,093.8 LB > 4123.3 LB
3) MOMENT CAPACITY OF BRACKET
Mcap= Sbracket * Fbending
= 0.11 INA3 * 0.66 * Fy
= 3,630 IN -LB
C= Mcap /0.75 = 1.11 * P1
THUS, P1= 1.20 * Mcap
= 4,356 IN -LB > 4123.3 LB
THUS, GOVERNING VALUE IS THE MIN VALUE OF P1,
P1 -eff= 4,123 LB
Mconn- allow= P1 *4.5 IN + P2 *0.5 IN
= 4.55 * P1 -eff * 1.33
= 25,015 IN -LB > Mconn max, OK
3"
Mconn Mconn
1 -5/8"
P1
P2
C
Mupper
Ml.ower
1"
4"
C= P1 + P2
= P1+ P1 *(0.5/4.5)
= 1.11 *P1
Sbracket= 0.110 INA3
1/2"
,- 1/2"
fr w
cc J O
O 0
CO
J
N LL
W 0
2
5
u.
co
I
�
z =
W
w
U �
O —
(a
W
LLO
w z
U=
0
z
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 - 0981
161 ATLANTIC STREET • POMONA • CA 91768
W.W. GRAINGER
W.W. GRAINGER
14
PROJECT
FOR
SHEET NO. OF
CALCULATED BY
RF
17
DATE 10 -15 -2003
TRANSVERSE ANALYSIS : BRACING :TYPE B
IT IS ASSUMED THAT THE LOWER PANEL RESISTS THE FRAME SHEAR IN TENSION AND
COMPRESSION. IF HORIZONTAL AND DIAGONAL MEMBERS ARE THE SAME, ANALYSIS WILL BE DONE
ON THE DIAGONAL MEMBER AS IT WILL GOVERN.
HORIZONTAL BRACING : COMPRESSION MEMBER
Vtrans = 677#
kI /rmin = [ .8 * 33 ] / .485
54.4
Fa = .522Fy- [kI /r *Fy/1494] "2
= 22781 psi.
fa /Fa = Vtrans /(Area *Fa)
= 0.10
DIAGONAL BRACING : COMPRESSION MEMBER
L diag. = [(L- 6) "2 +(D- 2 *Bcol)"2] ".5
= 42.6
Vdiag = Vtrans * Ldiag. / D
= 875#
k I /rmin = [ 1 * 42.6 ] / .311
= 137.0
Fa = [12rr. "2E] /[23(kI /r) "2]
= 7944 psi.
fa /Fa =Vdiag /(Area *Fa)
= 0.48
D= 33"
HORIZONTAL BRACING
w .J
DIAGONAL BRACING
w
Area= .308 "A2
rmin= .485 "
H W= 2.25 "
H= 1.5 "
Area= .231 "A2
rmin= .311 "
t =.06
W= 2.25 "
H = 1 "
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909) 869 -0989 • FAX: (909) 869 -0981
161 ATLANTIC AVENUE • POMONA • CA 91768
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 15 OF 1 7
CALCULATED BY RF DATE 10-15 -2003
OVERTURNING ANALYSIS: TYPE B
ANALYSIS OF OVERTURNING WILL BE BASED ON SECTION 2228.7.1 OF THE 1997 UBC
DEPTH = 33 in
TOP LEVEL HEIGHT = 120 in
FULLY LOADED:
Total Shear= 678 Ib EL n
Mot = E(Fi *hi) * 1.15
= 89,967 in -Ib
Mst = X(Wp +wDL) *D /2
= (9000 Ib + 140 Ib) *33 in /2
= 150,810 in -Ib
Puplift = 1(Mot - Mst)/Depth
= (89967- 150810)/33
= 0. Ib <= NO UPLIFT
TOP SHELF LOADED:
SHEAR = 339 Ib
Mot = Vtop * ht
= 3391b * 120 in
= 40,675 in -Ib
Mst = (Wp +wDL) *D /2
= (4500 Ib + 140 Ib) *33/2
= 76,560 in -Ib
Puplift = 1(Mot - Mst) /Depth
= 0 Ib <= NO UPLIFT
ANCHORS
QUANTITY= 2
PULLOUT = 1250 LB
SHEAR = 2453 LB
EL 5
EL 4
EL 3
EL 2
EL 1
<_= 33 1/3% INCREASE FOR SHORT TERM LOADING DUE TO SEISMIC FORCES.
<=== 33 1/3% INCREASE FOR SHORT TERM LOADING DUE TO SEISMIC FORCES.
Eq. = (Ps/Pt) ^5/3 + (VsNt) ^5/3 s 1.0
INTERACTION EQUATION:
FULLY LOADED = (0 LB /2500 LB) ^5/3 + (339 LB/4906 LB) ^5/3
= 0.01 < 1.0 OK
TOP SHELF LOADED = (0 LB /2500 LB) ^5/3 + (169 LB/4906 LB) ^5/3
= 0.00 <1.00K
F2
F1
F3
F4
USE (2) 1/2 "0x3 -1/2 "MIN. EMBED. HILTI KWIK BOLT II ( I.C.B.O. #4627) OR APPROVED EQUAL
PULL OUT CAPACITY IS THAT OF WITHOUT SPECIAL INSPECTION.
Fn
F5
ie�.v. =. n:ct� �•v�
,1
1111
1
1
i I
r I SE7 ".11111 4/11C
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
CALCULATED BY
W.W. GRAINGER
W.W. GRAINGER
16 OF
PROJECT
FOR
SHEET NO.
RF DATE
17
10 -15 -2003
BASE PLATE :TYPE B
BASE PLATE WILL BE ANALYZED WITH THE RECTANGULAR STRESS R
LOAD P, COMBINED WITH THE TRIANGULAR STRESSES RESULTING
THERE ARE 3 CRITERIA IN DETERMINING Mb. THEY ARE 1) MOMENT
2) MOMENT CAPACITY OF THE ANCHOR BOLTS, AND 3) Vh /2 (FULL
VALUE OBTAINED FROM THE 3 CRITERIA ABOVE.
Pool = 7295 lb. B = 5 in.
D =3in.
b = 3 in.
P/A = Pcol /(D *B) = 486.3 psi.
Mbase = wl "2/2 = 1 "2 /2(fa)
Mbase = 243.2 in.lb.
Sbase = 1 *t "2/6 = 0.023 in. "3
Fbase = .75Fy * 1.33 = 36000 psi.
fb /Fb = Mbase /(Sbase *Fbase) = 0.288
ESULTING FROM THE VERTICAL
FROM THE MOMENT Mb (IF ANY).
CAPACITY OF THE BASE PLATE,
FIXITY). Mb IS THE SMALLEST
t = .375 in.
b1 = 1 in.
fa
bl
b
B
Pcol
bl
w..i r:4:f •.
r ili rETZ7 11°1141 1
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909)869 -0989 • FAX: (909)869 -0981
161 ATLANTIC STREET • POMONA • CA 91768
SLAB AND SOIL :TYPE B
THE SLAB IS CHECKED FOR PUNCTURE STRESS. IF NO PUNCTURE OCCURS, IT WILL BE ASSUMED TO
DISTRIBUTE THE LOAD OVER A LARGER AREA OF SOIL AND HENCE, WILL ACT AS A FOOTING.
(a) PUNCTURE
Pmax = 1.4 DEAD LOAD + 1.7 LIVE LOAD
Pmax = 1.4 * Pcol + 1.7 * (Mot /d)
= 11,031 lb.
Fpunct = 2 *sgrt(f'c) = 100.0 psi.
Apunct = [(w +t /2) +(d +t /2)] *2 *t = 130.0 in. "2
fv /Fv = Pmax /(Apunct *Fpunct) = 0.85
(b) SLAB TENSION
Asoil = Pmax /(1.33 * fsoil) = 8.27 ft. "2
= 1,191 in. "2
L = sqrt(Asoil) = 34.5 in.
B = sgrt(w *d) + t = 8.9 in.
b = (L -B)/2 = 12.8 in.
Mconc = wb "2/2 = (1.33 *fsoil *b "2)/(144 *2)
= 761.0 in.Ib.
Sconc = 1 *t "2/6 = 4.17 in. "3
Fconc = 50 *sgrt(f'c) = 225.00 psi.
fb /Fb = Mconc /(Sconc *Fconc) = 0.81
PROJECT W.W. GRAINGER
FOR W.W. GRAINGER
SHEET NO. 17 OF 1 7
CALCULATED BY RF DATE 10-15-2003
BASE PLATE
w = 5in.
d = 3 in.
CONCRE I b
t 5 in.
f'c = 2500 psi.
SOIL
fs = 1000 psf.
;;ca•,:x.:Jl.sha3- �ti {+:c+tia�rSAYi+Wt�p�.0
26' •
•
4— NORTH
•
(1,816 SF)
18'
40' 1
\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\\ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \ \\
12,051 SF total
(Including office)
—161 F— 24'
OFFICE
CITY (if' TUKWILA
APPROV'E°)
t nd th t the p1,2
APR — 3 ' 1a 3 un��rs c :1',
14:1 EU
+K ` •rSt.N
Seawest Building
18384 Olympic Ave S
y
a
•
0
00
—n
1
•
•
Pedestrian Exit DOCK -HIGH LOADING
S O'
22,149 SF to
ncluding offl
RECEIVED
CITY OF TUKWILA
APR 0 2 2003
PERMIT CENTER
•
•
L10_ 10_
Pedestrian Exit
v. 7rpxa•.
Emergency Exit .
48'
OFFICE
(2,100 SF)
N
r
16'
28' —►•
•
OFFICE
(1,816 SF)
4 — NORTH
78'
•
12,051 SF total
(including office)
77 0
- t C G'"
w
. . (_
36'
\
SEAWEST BUILDING
—13'
228'
•
•
DOCK -HIGH LOADING
150'
50'
Typical Column Spacing
SUBLEASE
AVAILABLE
22,149 SF total
(including office)
•
•
46'
OFFICE
(2,100 SF)
W
Q � Q �
J
O 0
CO 0
W z
W 0
u-Q
_ d
I- Ill
Z =
!- O
Z 1-
1/1
• W
O ( .
W W
I - 0
UO
w Z
O -
0~
z
FEATURES
• 24' clear height
• Corner location
• Strategic access
SIZES AVAILABLE
• 34,200 SF (3,916 SF
office) with 8 DH
• 21,149 SF (2,100 SF
office) with 6 DH
(sublease, vacant)
• 12,051 SF (1,816 SF
office) with 2 DH .‘,.;4•;1
(available ` \\I
immediately)
Standalone Southcenter South
18370.80 Olympic Avenue South, Tukwila, Washington
Office /Warehouse For Lease or Sale
34,200 SF Total (Divisible)
For additional information, please contact:
John C. Jewett 206.248.7311
405
j Southcenter
Mall ,
180th
To
d Blvd
m
m
I .
Y
0
SeaWet
Building
S 196th
SW 27th
I
1
W
m
V
j
Insignia
Valley
Medical•
Center
Kidder Mathews
h\nlder AIIIIhews, an independent read t•snne tier%ires Company
Aldwugh all iufurn furnished rt•guuIiug for sa rental ■r financing is (min sources wr th•rae•d n•IiuhL sneh information has not b verified, and Io espn,N u•pn•,tvuttiou i, Made nor i., an) m he implied as
Co the ureurnr thet■nf, nail it i++nhmiue.l subject to errors, omi ,Malts, change of price, reuul or other conditions, prior Nair. Iea,• or financing, nt uithdl;renl wnhom uuiire.
r, G;� i s i y; S? ik" t F� r ` °::li�• , ? , : 'ni r•'tl ••, tr- , . -
August 4, 2004
Robert Bishop
100 Grainger Parkway
Lake Forest, Illinois 60045
Dear Permit Holder:
Sincerely,
Stefania Spencer
Permit Technician
Xc: Permit File No. D03 -102
Bob Benedicto, Building Official
City of Tukwila
RE: Permit Application No. D03 -102
18370 Olympic Avenue South
Steven M. Mullet, Mayor
Department of Community Development Steve Lancaster, Director
In reviewing our current records the above noted permit has not received a final inspection by the City of Tukwila
Building Division. Per the International Building Code, International Residential Code and /or the International
Mechanical Code, every permit issued by the Building Official under the provisions of this code shall expire by
limitation and become null and void if the building or work authorized by such permit is not commenced within
180 days from the date of such permit, or if the building or work authorized by such permit is suspended or
abandoned at any time after the work is commenced for a period of 180 days.
Based on the above, you are hereby advised to:
• Call the City Of Tukwila Permit Center at (206) 431 -3670 to arrange for the next or final
inspection.
This inspection is intended to determine if substantial work has been accomplished since issuance of the permit
or last inspection; or if the project should be considered abandoned.
If such determination is made, the Building Code does allow the Building Official to approve a one -time
extension up to 180 days. Extension requests must be in writing and provide satisfactory reasons
why circumstances beyond the applicants control have prevented action from being taken.
In the event you do not call for the above inspection or request and receive an extension prior to September 28,
2004, your permit will become null and void and any further work on the project will require a new permit and
associated fees.
Thank you for your cooperation in this matter.
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206-431-3670 • Fax: 206 - 431 -3665
September 3, 2003
Robert Bishop
100 Grainger Parkway
Lake Forest, IL 60045
Dear Permit Holder:
Cizy of Tukwila
Department of Community Development Steve Lancaster, Director
RE: Permit Application No. D03 -102
18370 Olympic Avenue South
In reviewing our current records the above noted permit has not received a final inspection by the City of Tukwila
Building Division. Per the Uniform Building Code and /or Uniform Mechanical Code, every permit issued by the
Building Official under the provisions of this code shall expire by limitation and become null and void if the
building or work authorized by such permit is not commenced within 180 days from the date of such permit, or if
the building or work authorized by such permit is suspended or abandoned at any time after the work is
'commenced for a period of 180 days.
Based on the above, you are hereby advised to:
Sincerely,
Stefania Spencer
Permit Technician
Xc: Permit File No. D03 -102
Bob Benedicto, Building Official
• Call the City Of Tukwila Permit Center at (206) 431 -3670 to arrange for the next or final
inspection.
Steven M. Mullet, Mayor
This inspection is intended to determine if substantial work has been accomplished since issuance of the permit
or last inspection; or if the project should be considered abandoned.
If such determination is made, the Building Code does allow the Building Official to approve a one -time
extension up to 180 days. Extension requests must be in writing and provide satisfactory reasons why
circumstances beyond the applicants control have prevented action from being taken.
In the event you do not call for the above inspection or request and receive an extension prior to October 8,
2003, your permit will become null and void and any further work on the project will require a new permit and
associated fees.
Thank you for your cooperation in this matter.
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665
DEPARTMENTS:
Building g ago0 •
Public Works ❑
Complete ❑
ACTIVITY NUMBER: D03 -102
PROJECT NAME: W W GRAINGER INC
SITE ADDRESS: 18370 OLYMPIC AVENUE
Original Plan Submittal
Response to Correction Letter #
DATE: 12 -16 -03
Response to Incomplete Letter #
X Revision # 1 lafter /before permit is issued
Documents /routing slIp,doc
2 -28 -02
PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
APPROVALS OR CORRECTIONS:
REVIEWER'S INITIALS:
Fire Prevention ❑ Planning Division
Structural ❑ Permit Coordinator
Incomplete
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROUTING:
Please Route ❑ Structural Review Required ❑ No further Review Required ❑
REVIEWER'S INITIALS: DATE:
Approved ❑ Approved with Conditions ❑ Not Approved (attach comments) ❑
Notation:
PERMIT COORD COPY
DUE DATE: 12 -18 -03
Not Applicable ❑
DUE DATE: 01 -15 -04
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
ACTIVITY NUMBER: D03 -102
PROJECT NAME: W. W. GRAINGER, INC.
SITE ADDRESS: 18370 OLYMPIC AV S
DATE: 04 -02 -03
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # After Permit Is Issued
DEPARTMENTS:
Av 4' ''�
Building Division ❑
Public Works
PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
67d 6 4-4-0
Fire Prevention
Structural ❑
Planning Division
Permit Coordinator
DETERMINATION OF COMPLETENESS: (Tues., Thurs.) DUE DATE: 04 -03 -03
Complete EY Incomplete ❑
Comments:
Not Applicable ❑
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROpTING:
Please Route Structural Review Required ❑ No further Review Required ❑
REVIEWER'S INITIALS: DATE:
DUE DATE: 05 -01 -03
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions Not Approved (attach comments) ❑
Notation:
REVIEWER'S INITIALS:
Documents /routing slip.doc
2 -28 -02
PERMIT COORD COPY
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Revision •
No.
Date I Staff I
Received I Initials I
Date
Issued
Date
Issued
Starr
Initials
"Staff
Initials
1 f2 -1L. -b skS 1 /T 3
•
I
,V711.1"
Summary of Revision: S.4,1. 4--_,- , ,,.„.. i,-/. 2.e . L
Ti ~1
_
, -TO -E,6 Cede/et/6 d xl 'TE
Received By:
N T,16,41 \f
Revision
No. "
Date
Received
Staff
Initials
Date
Issued
Starr
Initials
a
Summary of Revision:
• Received By:
Revision
No.
Date
Received
Staff
Initials
Date
Issued
Staff
Initials
I
Summary of Revision:
Received By:
•
PROJECT NAME: W. I,). E 2n_(,n.9 0�. Dn4C , . PERMIT N O :. " bO - ( d 2.
1$3'70 OL t c., f ,j - -- Original Issue Date: (i--//-0.5 REVISION LOG
Site Address:
Revision
No.
Summary of Revision:
Date
Received
Staff
Initials
Received By:
Date .
Issued
(please print)
(please print)
Staff
Initials
(please print)
p print
Revision
No.
Date
Received
Staff
Initials
Received By:
Date
Issued
Staff
Initials
Summary of Revision:
(please print)
•, gIr- VntR> r± G7Y}'ti?ks t2212 ,
i��
City of Tukwila
Department Of Community Development - Permit Center
6300 Southcenter Blvd, Suite 100
Tukwila, WA 98188
(206)431 -3670
z
'i �N �'j f '` rAy + .� :• ' . f �,. a, � y !, +.. . ��, ...... .,.. w
+ � �� 1 i i .... � . '4— z
k
,, n' i N �f4 S`�',
s! ` * a� °1�� F?S ,�c�y y �1 ' i ; � �7 .,- y{ 1 , „`i7T �1� 1� c
4-.- 'ha 4�`.7!'T yii`lti�l t�� 'j ak iF ., 5� -t 1. r .KC'7 ._. . . � . �'T i. wa �f G
rU
(no
o w
J =
H
w
2
u_Q
I • O
I- w
z
I- O
Z I-
Project Name: iJ Y
J & u i Ir1 C1 e r T e1G o
V) I f-
nn w
Project Address: 1 R X370 Olympic /� piC ve m o
Contact Person: J J R � & JJ p J Phone Number: ( 25) - 502q - z
ry En vne.ved dve ne.)ih�S Ye viSec/ fD v N
Summary of Re vision: _
Y//c7 f c h 15/ - o ;Foy - l' Lk /' 7 ! ' o I
CI z
Revision submittals must be submitted in person at the Permit Center. Revisions will not be accepted
through the mail, fax, etc.
Date: 12//(p/03
Plan Check/Permit Number:
O Response to Incomplete Letter #
O Response to Correction Letter #
[r Revision # 1 after Permit is Issued
0 Revision requested by a City Building Inspector or Plans Examiner
]b3- 102.
DEC 6 20o
PE NrER
Sheet Number(s):
"Cloud" or highlight all areas of revision including date of revision
Received at the City of Tukwila Permit Center by: S
J Entered in Permits Plus on OA 193
08/06/03
1/2" 0T-BOLT
� 1
1/4"I
1/8' V41/16' < TIP.
t-1 3/4"13/4
TYPICAL BRACE TO COLUMN CONNECTION
ATTACH W/ (2) 1 /2"0 BOLTS
ROW SPACER
GENERAL CONFIGURATION
HORIZONTAL BRACE
c-rry cw T: WWII A
DEC 1 6 2003
EST_ 1965
W.W. GRAINGER
18370 arc AVE
TucvILw, WA
TYPICAL BEAM TO COLUMN CONNECTION
STORAGE RACK DETAILS
1/2"0
T -BOLT
5 J
CONNECTOR
BEAM
TYP. X 1/6" V1/2`
09116'
BASE PLATE
1 5J6
1/8' V2 7/8r <`
3'
3 ' TI K
'
106"
240"
79 "
c :i STORAGE RACK ELEVATIONS
3 1/2'
MIN. EMBEDMENT
112' EEO
1 REQ"D PER BASE PLATE
ANCHOR
BASE PLATE
CONCRETE --\
TYPE a
FRONT VIEW
240"
115"
5
/2" 0 ANCHOR
TYPE a
96 t
L- _______
r ________
'.RONT VIEW
2.40
61"
61"
61"
39"
21 /4"
t- 33" --t- 30" -t- 33" -4
SIDE VIEW
1 1/2"
t
240' - -
120"
i
NOTES:
1. DESIGNED PER CHAPTER 22, DIVISION X OF THE 1997 U
2. STORAGE CAPACITY:
TYPE A- 3,000# PER LEVEL
TYPES B & C- 4,500# PER LEVEL
3. ASTM A570 FOR SHAPE Fy = 50,000 PSI GRADE 50:
4. ALL BOLTS A307( UNLESS OTHERWISE NOTED).
5. ANCHORS HILT! KWIK BOLT II, ICBO #4627 OR APPRO
6. SPECIAL INSPECTION IS NOT REQUIRED FOR ANCHOR IlikitALA
7. CONCRETE 5" THICK x 2,500 PSI.
8. SOIL BEARING PRESSURE 1,000 PSF_
1011111.110
TYPE c
t .
FRONT VIEW
61"
61"
61"
39"
SIDE VIEW
Z WE 3�
° 0
N 11.11
44:c
r
t7 ,
W
Ce
TYPICAL BRACE TO COLUMN CONNECTION
ROW SPACER
TYPICAL BEAM TO COLUMN CONNECTION
CONNECTOR
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
11r V2 7Ir <TYP
1/$' V41/16' < .
1 314` --4/4
STORAGE RACK ELEVATIONS
GENERAL CONFIGURATION
NOTES:
1. DESIGNED PER CHAPTER 22, DIVISION . X OF THE 1997 UBC.
SEISMIC ZONE 3 .
2. STORAGE CAPACITY: 4,500# PER LEVEL
3. ASTM A570 FOR SHAPE Fy = 55,000 PSI GRADE 55.
4. ALL BOLTS A307( UNLESS OTHERIMSE NOTED).
5. ANCHORS HILTI KWIK BOLT II, ICBO #4627 OR APPROVED EQUAL..
6. INSPECTION IS NOT REQUIRED FOR ANCHOR INSTALLATION.
7. CONCRETE 5' THICK x 2,000 PSI.
8. SOIL BEARING PRESSURE 1,000 PSF.
I understand that the Plan Check approvals are
subject to errors and omissions and approval of
plans does not authofiize the violation of any
adapted code or ordinance. Receipt of con-
tractds of approved plans acknowledged.
RECEIVED
CITY OF TUKW1LA
APR 0 2 2003
FILE COPY
W.W. GRAINGER
11970 mum AVE
1lKIMlA rlrl
ginD0 -102
, • • ' •
.... .
;�. a :
.; a
f' r
•• •
• • N
••
•
to
•
• • 'S„
a
•
i • ,
,
•_ f,
,,. ;. �, •
t ,�f a • ?► ♦ • . to
a
S
4