HomeMy WebLinkAboutPermit M07-011 - WESTFIELD SOUTHCENTER MALL - RADIO SHACKRADIO SHACK
929 SOUTHCENTER MALL
M07 -011
Parcel No.:
Address:
Suite No:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
6364200010
929 SOUTHCENTER MALL TUKW
Tenant:
Name: RADIO SHACK
Address: 929 SOUTHCENTER MALL , TUKWILA WA
Owner:
Name: WEA SOUTHCENTER BL
Address: 11601 WILSHIRE BL , LOS ANGELES CA
Contact Person:
Name: DANI MEYERS
Address: 1221 2 AV N , KENT WA
Contractor:
Name: HERMANSON COMPANY LLP
Address: 1221 2ND AV N , KENT, WA
Contractor License No: HERMACLOO5BJ
Value of Mechanical: $32,000.00
Type of Fire Protection:
Furnace: <100K BTU
>100K BTU
Floor Furnace
Suspended/Wall/Floor Mounted Heater
Appliance Vent
Repair or Addition to Heat/Refrig /Cooling System....
Air Handling Unit <10,000 CFM
>10,000 CFM
Evaporator Cooler
Ventilation Fan connected to single duct
Ventilation System
Hood and Duct
Incinerator: Domestic
Commercial/Industrial
doc: I MC -10/06
MECHANICAL PERMIT
EOUIPMENT TYPE AND OUANTITY
0
0
0
0
0
0
0
1
0
0
0
0
0
0
* *continued on next page **
Permit Number:
Issue Date:
Permit Expires On:
Phone:
Phone: 206 575 -9700
Phone: 206 - 575 -9700
Expiration Date: 08/25/2008
DESCRIPTION OF WORK:
INSTALL (1) NEW 8.5 TON ROOFTOP HEAT PUMP UNIT WITH AIRSIDE ECONOMIZER AND
COMPLETE LOW PRESSURE DUCTWORK BUILDOUT AND (1) TOILET EXHAUST FAN DISCHARING
AT ROOF.
Steven M. Mullet, Mayor
Steve Lancaster, Director
M07 -011
02/08/2007
08/07/2007
Fees Collected: $523.13
International Mechanical Code Edition: 2003
Boiler Compressor:
0-3 HP /100,000 BTU 0
3 -15 HP /500,000 BTU 0
15-30 HP /1,000,000 BTU.. 0
30 -50 HP /1,750,000 BTU.. 0
50+ HP /1,750,000 BTU 0
Fire Damper 0
Diffuser 0
Thermostat 0
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment
M07 -011 Printed: 02 -08 -2007
Permit Center Authorized Signature:
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinance
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulatinc
construction or the performance of work. I am authorized to sign and obtain this mechanical permit.
Signature: Date:
Print Name:
doc: IMC -10/06
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: httn: / /www.ci.tukwila.wa.us
s
Steven M. Mullet, Mayor
Steve Lancaster, Director
Permit Number: M07 -011
Issue Date: 02/08/2007
Permit Expires On: 08/07/2007
Date: `2 - dQ
' W 6 7
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspende
or abandoned for a period of 180 days from the last inspection.
M07 -011 Printed: 02 -08 -2007
City of Tukwila
Parcel No.: 6364200010
Address: 929 SOUTHCENTER MALL TUICW
Suite No:
Tenant: RADIO SHACK
1: ** *BUILDING DEPARTMENT CONDITIONS * **
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http://www.ci.tukwila.wa.us
PERMIT CONDITIONS
Permit Number: M07 -011
Status: ISSUED
Applied Date: 01/29/2007
Issue Date: 02/08/2007
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431- 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: Ventilation is required for all new rooms and spaces of new or existing buildings and shall be in conformance with the
International Building Code and the Washington State Ventilation and Indoor Air Quality Code.
6: All electrical work shall be inspected and approved under a separate permit issued by the Washington State Department
of Labor and Industries (206/248 - 6630).
7: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
8: ** *FIRE DEPARTMENT CONDITIONS * **
9: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
10: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
11: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. °MC 606.1, 606.2.1)
12: Dedicated fire alarm system circuit breaker(s) shall be equipped with a mechanical lockout device. (NFPA 72
(4.4.1.4.2.1))
13: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
14: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
15: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
doc: Cond -10/06 M07 -011 Printed: 02 -08 -2007
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
16: An electrical permit from the Washington State Department of Labor and Industries is required for this project.
17: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
18: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
19: .Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
20: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: Cond -10/06
* *continued on next page **
M07 -011 Printed: 02 -08 -2007
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work
construction or the performance of work.
Signature:
-47K)
Print Name:``'( ( N2 erS
doc: Cond -10/06
Date: (W O 7
ordinances governing
or local laws regulating
M07 -011 Printed: 02 -08 -2007
Site Address: /Mr) }h e rifX r TY)cQ Q,Q
Tenant Name: kb din
Property Owners Name: ('� to , Shy r k .
Mailing Address: 1070 c- cAL 1 ovItet Mrt a, ° k_ (Join cKIZV
cit
Name: vi P - S
Mailing Address: 1 r i y nd .d v P 1.`r W1 cj R(1?-0,
E -Mail Address:
Company Name:
Mailing Address:
Company Name:
Mailing Address:
Contact Person:
E -Mail Address:
Community Developm Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
hap://www.ci. tukwila. wa. us
Company Name: 7 l Q r c t�
Mailing Address: / ,t a 1 3 vci (2 i; l A) k 1 - f
‘tact Person: 1
E -Mail Address: C ›, - J c ct h e - P 11
Q:1Applicatio, orms- Applications On Line \3 -2006 - Mechanical Permit Applicalion.doc
Revised: 4-2006
bh
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
King Co Assessor's Tax No.: 67 ? w ieric/
Suite Number: " la`1 Floor:
New Tenant: 0 .... Yes
e Con w en yopr perm
Day Telephone: -L(,-) S 7S 9 7&
City
Fax Number:
�,k)A (4sO3a
City
State
State
` ity State
Contact Person: / ) 1 l_ ; \ C _ /S Day Telephone:
E -Mail Address: t T LCi_= 0-1 "'�' > ✓�Y' r%')` c7i c, , C >2F x Number:
Contractor Registration Numb
g: : F-TiC )0- p � � � `�?,� Expiration Date:
State
Zip
City
Day Telephone:
Fax Number:
State Zip
Day Telephone: ;900 t7 5 7r)
Zip
)(Qv- ekr Scr? , Fax Number: Z,Z DX)
(0 �jT / ?A
L • 1 1
Zip
Zip
Page 1 of2
0
Unit 'Ype:..
Qty
. Unit Type:
Qty
Unit Type:
Qty
Boiler /Compressor:
Qty
Furnace<100K BTU
Air Handling Unit >10,000
CFM
I
Fire Damper
0-3 HP /100,000 BTU
Furnace>100K BTU
Evaporator Cooler
Diffuser
3 -15 HP /500,000 BTU
Floor Furnace
Ventilation Fan Connected
to Single Duct
Thermostat
15 -30 HP /1,000,000 BTU
Suspended/Wall/Floor
Mounted Heater
Ventilation System
Wood/Gas Stove
30 -50 HP /1,750,000 BTU
Appliance Vent
Hood and Duct
Water Heater
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Refrig /Cooling
System
Incinerator - Domestic
Emergency
Generator
Air Handling Unit
<I0,000 CFM
Incinerator – Comm/1nd
Other Mechanical
Equipment
I
Valuation of Project (contractor's bid prlca): $ ,/ Vl/)
Scope of Work (please provide detailed information):
— Scope of Work: (1) new 8.5 ton rooftop heat pump unit with airside economizer and
— complete low pressure ductwork buildout. (1) toilet exhaust fan discharging at roof.
Use: Residential: New ....0 Replacement ....
Commercial: New .... Replacement ...�
Fuel Type: Electric p Gas ....p Other:
Indicate type of mechanical work being installed and the quantity below:
BUILDING OWNER OR AUTHORIZED AGENT:
Signature: ri
Print Name: /9 / )0)el
Mailing Address: h9a, ) pp�
Date Application Accepted:
N12-6111)1-
On Line 3 -2006 - Mechanical Permit Appliation.doc
Revised: 4-2006
bh
Date Application Expires:
Value of Construction – In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review – Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested
in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
Day Telephone: c9-5 7t - 703
City
01 12- ti-
Date:
1 ` �.1 7
State Zip
Staff Initials:
Page2of2
Parcel No.: 6364200010 Permit Number: M07 -011
Address: 929 SOUTHCENTER MALL TUKW Status: APPROVED
Suite No: Applied Date: 01/29/2007
Applicant: RADIO SHACK Issue Date:
Receipt No.: R07 -00189 Payment Amount: 5424.50
Initials: BLH Payment Date: 02/08/2007 01:25 PM
User ID: ADMIN Balance: 50.00
Payee: HERMANSON CORPORATION
TRANSACTION LIST:
Type Method Description
Payment Check 1689 424.50
ACCOUNT ITEM LIST:
Description
MECHANICAL - NONRES
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Amount
Account Code Current Pmts
000/322.100 424.50
Total: $424.50
•;`y )2/09 971A T iT L , 7
doc: Receiot -06 Printed: 02 -08 -2007
Payee: HERMANSON CO. LLP
ACCOUNT ITEM LIST:
Description
PLAN CHECK - NONRES
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: Permit Number: M07 -011
Address: 1070 SOUTHCENTER MALL TUKW Status: PENDING
Suite No: Applied Date: 01/29/2007
Applicant: RADIO SHACK Issue Date:
Receipt No.: R07 -00128 Payment Amount: $98.63
Initials: JEM Payment Date: 01/29/2007 02:28 PM
User ID: 1165 Balance: $424.50
TRANSACTION LIST:
Type Method Description Amount
Payment Check 1686 98.63
Account Code Current Pmts
000/345.830 98.63
Total: $98.63
.. 'i 01/29 9716 TOTAL
doc: Receiot -06 Printed: 01 -29 -2007
Project:
/7' //U S h //(
Type of Inspection:
7 - 7 / / t . / / - - /
Address:
7-2-5" sni /%
"/ /e-,
/7 im
Date Called:
//
Special Instructions:
Date Wanted:
.1 - /. - d 7
(
p.m.
Requester:
Phone No:
6 L -q7 >GU
INSPECTImN NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
Approved per applicable codes. J Corrections required prior to approval.
COMMENTS:
INSPECTION RECORD
Retain a copy with permit
Inspector
/) 7 -a / /
PERMI
Date:
2 -/ 7
�� ,2
E $58.00 REINSPECTION E REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to sechedule reinspection.
Receipt No.:
206 - 36 0
Date:
Project:
i-?. � j/ v _s 4,7 e /(
Type of Inspection:
;,v,/
Address:
q a2 S So/- //Yr r /1 /.-7
/ /
Date Called:
Special Instructions:
Date Wanted:
,,2 -/4/ c' 7
0.
P.m.
Requester:
Phone No:
a&E - y/ - 5650
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
Ei Approved per applicable codes.
INSPECTION RECORD
Retain a copy with permit
(206) 31 -3
0 Corrections required prior to approval.
COMMENTS:
/) A-75a
Inspector:
Date__ tt _a7
El $58.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to sechedule reinspection.
Receipt No.:
Date:
Project:
/? i3/4 U 5/74,
Type of Inspection: L
547,K,- o 7/, ( / a ✓
Address:
j,Z 7 .SCnr/ %t' -,t/7 - /7
241/
Date Called:
Special Instructions:
? :67)
Date Wanted:
Requester:
Phone No:
a 06- v9/ 5 6 5 v
INSPECTION RECORD
Retain a copy with permit
INSPE • NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
, 7- //
COM ENTS:
'Inspector:
Approved per applicable codes. J Corrections required prior to approval.
IDate:� /
_ yam
$58.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to sechedule reinspection.
'Receipt No.:
'Date:
Project:�10 /
/�/! ?� !� /'e'e
Type of Inspection: \-
2o/ II., 4 A fr, /'(/
Address:
2- , Cri ,
Date Called: i
Special Instructions:
Date Wanted:
-- 7 p.m.
Requester:
Phone Na., (0 r5 /o - /1 /a.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
r ff)
/ O
PE
IT N
(206)43 1 -3
MENTS:
Approved per applicable codes. D Corrections required prior to approval.
$58. I T INSPECTION E REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to sechedule reinspection.
Receipt No.:
Date:
COMMENTS:
Project: r .
Sprinklers: `
Fire Alarm:
Type of Inspection:
Address: -
Suite #:
-� ,
1,`• t_ .
Contact Person:
Special Instructions:
Occupancy Type:
Phone No.:
Project: r .
Sprinklers: `
Fire Alarm:
Type of Inspection:
Address: -
Suite #:
-� ,
1,`• t_ .
Contact Person:
Special Instructions:
Occupancy Type:
Phone No.:
Needs Shift Inspection: Y
Sprinklers: `
Fire Alarm:
r"
Hood & Duct:
Monitor:
Pre -Fire: 11
Permits:
Occupancy Type:
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA FIRE DEPARTMENT
444 Andover Park East, Tukwila, Wa. 98188 206 - 575 -4407
- Approved per applicable codes.
Word /Inspection Record Form.Doc 1/13/06
PERMIT NUMBERS
[ Corrections required prior to approval.
Inspector:_
Date: 1
Hrs.:
(s›
$80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
T.F.D. Form F.P. 113
MO
ABKJ'
ANDERSEN • EJORNSTAD • KANE • JACOBS
Consulting Civil and Structural Engineers
800 Fifth Avenue, Suite 2500 Seattle, Washington 98104
STRUCTURAL ENGINEERING CALCULATIONS
Tel: 206.340.2255
(TIRES 1t OR
Submitted to:
BN Builders, Inc.
2601 4 AVE # 350
Seattle, WA 98121
Tel: (206)- 382 -3443
Fax: (206)- 382 -3440
Fax: 206.340.2266 I www.abkj.com
24 January 2007
ABKJ Project Number (07009.00)
Radio Shack T.I.
Unit HP -1 Roof Top Installation Design
Tukwila, WA
REG' P°
FED .. .
DEPARTMENT
Volume (1 of 1)
ABKJI
Consulting Civil and Structural Engineers STRUCTURAL ENGINEERING CALCULATIONS
800 Fifth Avenue, Suite 2500 Seattle, Washington 98104
Partial Plan and Structural Detail
Tel: 206.340.2255
Index to Structural Calculations:
Existing Member Capacities Check
Equipment Seismic Anchorage Design
Fax: 206.340.2266 I www.abkj.com
24 January 2007
ABKJ Project Number (07009.00)
Pages:
B1 -- B3
L1 — Li
D1 —D2
ABKJIII
ANDERSEN • BJORNSTAD • KANE • JACOBS
Consulting Civil and Structural Engineers
800 Fifth Avenue, Suite 2500 Seattle,Washington 98104
PROJECr .e qp / o cSH ,4GC 7 - ; -or.
SUBJECT R "A 7D e E &v,PMbv i
�
v,411.-c, A r Tic 4 co ,4
PR PoJao
O
o .
VI/I%
est/ niAT LP eC,?
w
Tel: 206.340.2255
oP (EJ / 6ys
P
3 42.6 #
/8,5 8 k -' = Z22, 9 k-
h
D,, X /S7/# 4 / 6 wS
2 s k - '' > H4.,,' = ZZZ.9 k - "
V A .o w = 1,3 k > /,m = 3 C Z k ✓
/ox
Fax 206.340.2266 I www.abkj.com
JOB # 07 ? .J
00 DATE Z? JAN
BY 0. -si S01 -/X T20N SHEET# a !03
Jr /srs .S'v�' tyre n..J 4
(6) /G ki J' r
JL-s- - rin-Gi fO
Z- ,4 19
I0k
rL) / C y 5 a • w. J'.T, ARE A-g 4 V,4 7 & P8'12 J' P, r OF'
i=yE' paJea /-/P -/ vr... ( 0,PDi./ G 7 v o Jv ld rs
�✓ J T1? ry iN ,s TA i ' ° Pie A-77 "f 4 wE7 GR.,' 0, /7 0 0
STANDARD LOAD TABLE OPEN WEB STEEL JOISTS, 11-SERIES
Allowable total safe loads in pounds per linear foot based on allowa+le stress of 30,000 psi
Joist Designation
'Depth in Inches
Resisting Moment
in Inch Kips
aximum End Reaction
in Pounds
**Approximate
iPond e per
Span in Feet
3200
14H3
165
5.5
457
427
340
292
176
109
163
96
151
86
140
77
14H4
14
212
3500
6.5
500
467
389
354
368
301
350
258
267
169
O I i
245
149
194
104
18
94
14H5
14
259
3800
7.4
543
507
475
447
422
400
364
255
142
237
127
220
114
14H6
14
307
4200
8.6
vvv
600
56o
525
o ho
494
442
437
420
374
327
191
303
170
281
152
261
136
14H7
14
369
4600
10.0
511
484
438
375
418
326
400
286
r - —
383
251
368
222
MEI
EMI MIMI
raciciss
16
6.6
422
400
399
368
342
188
124
175
112
164
101
153
91
144
83
16
MI MI
538
506
478
453
246
150
229
135
214
122
200
111
8.6
541
484
339
226
- - -
315
201
293
181
273
162
255
147
224
121
16H7
4900
10.3
613
570
544
516
490
467
445
434
426
379
408
334
392
295
350
210
327
189
306
171
287
155
347
195
332
177
311
161
16H8
16
5200
11.4
650
612
578
547
520
495
473
433
382
416
338
371
240
359
216
ABKJIII
ANDERSEN • BJORNSTAD • KANE • JACOBS
Consulting Civil and Structural Engineers
800 Fifth Avenue. Suite 2500 Seattle,Washington 98104
PROJECT RA / o JSs T,1
SUBJECT ,E'o O 7. P GQ G /Pjiy r
G6/jCk ex/ ST"^' 4
43Artc ;
L ,.
z / (�'O
Wz f6PJ�
1/" ( &) ft
/G2 6 #/
G T/
L\ - ° � 2 33 /17 z ,P
.eo 8a4)14 7o JvPPaig?' PQoP,' HP- / „ i7
iD
/3,'
z 2 t/76 6 = 856 #
/ - = SS 47 k C c 8 0 1-o
s.
Tel: 206.340.2255
P 1'
F , ,CC (3Cood)
JOB# 0706 9, o
BY V S, s7bilf Vain /V
Stec-it
Lrecr. -
R2 ° biz,/814
MA'x. _ C (° 8 0 1E4 70#4 2 8,, in 3< 5 T ✓oFc
( ) h/ /6 x 3/ A-04 BE /5 , z 4 (.4 re- / o,e
SuPPJ? T off' PP o P &6100 lick / T i-/P —/
Fax 206.340.2266 I www.abkj.com
DATE Z It J 'z.v 107
SHEET# B 3 / 83
(8)W /C x3/ A3C
5f7.Zn,
3 75 rn
ABKJI
ANDERSEN • BJORNSTAD • KANE • JACOBS
Consulting Civil and Structural Engineers
800 Fifth Avenue, Suite 2500 Seatde,Washington 98104
PROJECT /eAeD/ 0 J/'l /a G K 7 .F
suBJECT Roor Td P FQv/®A/6WT
Derne 4/'v
5 r - 43 /LET`', 0,4 oe' (7 0 tc'
f E /sM G
WP
/70
Je7s,ni c. P•O.ecE
o•�ui� wP
R
I
= 0,f 0)0 0 4 7 ) (1 e ( 7
— D. 5 L /e
r ge
0. eSvf 17
z (f))
�. -k - N/ t F = 0
V = 820 #
fi
2g = Ev - Wr a- C
CL 311
CI 1 °1 9 #
o ° o /1/ 6 Gov /T c/P`, r, Aw cH0/2
0
.{- .g t‘ A r - Fr (zits) +• Wr (2.5)
Ct. (s) = O
Tel: 206.340.2255 I Fax: 206.340.2266 I www.abkj.com
JOB# 07009, 0
BY 1 , abi4Ai 7b N
/J a A4 e7)434 C--
-
e s. (2
C/'V/ T /li✓s0
DATE 2 / / 0 7
SHEET# L-► A 1
e L a art 4- a g
, o/ Xl- e/1 ice-. 1e are ti
O v(3Er?1J #PMni 4
o ►4aeive,.4.r y
Z. 2 St
2. zs'
t \Tv te2.0*
L C . Iog ,
IPII
ABKJI
ANDERSEN • BJORNSTAD • KANE • JACOBS
Consulting Civil and Structural Engineers
800 Fifth Avenue, Suite 2500 Seattle,Washington 98104
!PER . P4 ,4A1 -
PROJECT /QA-D / O „Si/,' C k Ti 1 JOB # 07009,00 DATE ZT- JAN '07
SUBJECT 1-)67.4/L-5 By D. 5. 7OHN Cron/ SHEET# d Z /Z'Z
(E) Ro vp=
YeDIA sags
L 3 x 3 x 5RAPE TO
fir FL vs`/ To P✓oTToM
of= ROOF DEck/.>/C
o wsT Top
in/srAic e aw
UNIT cvR.B 7tf
Tel: 206.340.2255 I Fax 206.340.2266 I www.abkj.com
5X /A
/&H0.c,
rfp.
5K/. A
COPE L. L4
AS RE Givi.eeP
CV R13,
& L
cvR8 P@2 EquiP
MP4R
l3 "MRN
( 1'
:T 2x
SIPAPEa
BRy
BLocKw4
A-S REci
Se cT! oN SK : / -SK/,
-/ c H (IN /T /NSrA UA T /oN T�a
-(E) 0-W. 5 FRAM//VG
ACTIVITY NUMBER: M07 -011 DATE: 01 -29 -07
PROJECT NAME: RADIO SHACK
SITE ADDRESS: 1070 SOUTHCENTER MALL
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter # Revision # After Permit Issued
DEPARTMENTS:
6f 410
Built�i ig "Division
Public Works ❑
Complete
Comments:
APPROVALS OR CORRECTIONS:
Documents/routing slip.doc
2 -28 -02
PERMIT COORD COPY..-
PLAN REVIEW /ROUTING SLIP
614 M / " 1 ° 7
Fire Prevention gi
Structural
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Incomplete ❑
TUES/THURS ROU ING:
Please Route Structural Review Required
REVIEWER'S INITIALS:
1
n
❑ Permit Coordinator n
DATE:
DUE DATE: 01-30-07
Not Applicable ❑
DATE:
Planning Division
•
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
No further Review Required
DUE DATE: 02-27 -07
Approved ❑ Approved with Conditions Not Approved (attach comments)
Notation:
REVIEWER'S INITIALS:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
License Information
License
HERMACLOO5BJ
Licensee Name
HERMANSON COMPANY LLP
Licensee Type
CONSTRUCTION CONTRACTOR
UBI
602004844
Ind. Ins. Account Id
PARTNER/MEMBER
Business Type
LIMITED LIABILITY COMPANY
Address 1
1221 2ND AVE N
Address 2
City
KENT
County
KING
State
WA
Zip
980322945
Phone
2065759700
Status
ACTIVE
Specialty 1
GENERAL
Specialty 2
UNUSED
Effective Date
1/11/2000
Expiration Date
8/25/2008
Suspend Date
Separation Date
Parent Company
Previous License
HERMAC *217NT
Next License
Associated License
Business Owner Information
Name
Role
Effective
Date
Expiration
Date
HERMANSON,
RICHARD L
PARTNER/MEMBER
01/01/1980
Bond
Amount
ALMON, KEVIN
PARTNER/MEMBER
01/01/1980
MACDONALD, JAMES
PARTNER/MEMBER
01/01/1980
Bond Information
Bond
Bond
Company
Name
Bond Account
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Bond
Amount
Received
Date
Washington State Department of Labor and Industries
General/Specialty Contractor
A business registered as a construction contractor with L &I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
https: // fortress. wa. gov /lni/bbip /printer.aspx ?License= HERMACL005BJ 02/08/2007
MINIMUM DUCT INSULATION (R-VALUE) LAST UPDATED: 12 /20/04
DUCT TYPE
DUCT LOCATION
INSULATION
R -VALUE
REMARKS
SUPPLY, RETURN
NOT WITHIN CONDITIONED SPACE: ON EXTERIOR OF
BUILUNG, ON ROOF, IN ATTIC, IN ENCLOSED CEILING
co_Si- :% WALLS, ;N GARAGE, IN CRAWL SPACES
R -7
1,2,3
OUTSIDE MR INT;E
'„1TH:N CONDITIONED SPACE
VARIES
1,2,4,5
SUPPLY, RETURN, oissa
AIR INTAKE
N WiTBN CONDMONED SPACE:
IN CONCRETE, IN GROUND
R -5.3
1,2
I SUPPLY WITH <55' (1.
> 105' AIR TEMPER +TUL=
`�6 T� :II CONDITIONED SPACE
R -3.3
1,2
MINIMUM PIPE INSULATION (INCHES) LAST UPDATED: 12/01/04
S• E I E
� :`
Top
a . .:;.,,, /'_�'- ,..,, v
1W.,V�`AL PIPE DS 1.. (IN)
- _, -.
: - -- , I
.l7
try ': ' - -V-,
•.• •-1.3
.
C.:.
_ JTS
:./ L
&
LESS
>1 TO
2
>2 TO
4
>4 TO
6
>6
IfA &R
' 4 's -2C0
C.25 -:.2a
125
3.5
1.5
1.5
1.5
1.5
1.5
Hi45.
T.05-;4;
: _' -,.�:
.._
:,
1.0
1.0
1.0
1
1.5
C =~d4:,&R
40 - -'S
..1 : -Cr.:::
__
3 5
0.5
0.75
1.0
1.0
1.0
I Ch'�t�S -I'
<4::
: .. 2
'.0
1.0
t.5
6 1.5
1.5
15
, .;AS &R
40-L5
Z.: z - ; 2 _
-
:.:
0.5
1 0.75
1.0
_ 1.5
1.0
t •
A
AC
ACH
ACT
AD ANA AD
AFF
AFG
AHU
ALUM
AMP /AMPS
AP
ARCH
BC
BDD
BF
BHP
BLDG
BOD
BOP
BOT
BS
BTU
BTUH
CAP
CC
CD
CDWR
COWS
CFM
CHWR
CHWS
CLG
COL
CONC
COND
CONN
CONT
CONTR
COORD
COP
CT
CU
CW
DB
DBA
DDC
DEFL
DEG
DG
DIA
DMPR
DN
DT
DWG
EXH
EA
EAT
EC
EER
EF
EFF
EL
[EEC/ELECT ELECTRICAL /ELECTRIC
EP END PLUG
FMCS ENERGY MANAGEMENT CONTROL SYSTEM
ENT ENTERING
EQUIP
ESP
EWT
EXIST
F
FAC
FD
FDC
FF
FIC
FIO
FLA
FLEX
FLR
FOB
FDIC
FOS
FOT
FP
FPP'
FSD
FT
D!T
FV
G
C-A
Mt'
GC
C-EN
GPm
CR
GRD
GAB
H3 Si
HATC
AMPS
AIR CONDITIONING
AIR CHANGES PER HOUR
ACOUSTICAL TILE CEILING
ACCESS DOOR
ADDITIONAL
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
ALUMINUM
AMPERAGE
ACCESS PANEL
ARCHITECT
BEADED COLLAR
BACKDRAFT DAMPER
BELOW FLOOR
BRAKE HORSEPOWER
BUILDING
BOTTOM OF DUCT
BOTTOM OF PIPE
BOTTOM
BIRD SCREEN
BRITISH THERMAL UNIT
BRITISH THERMAL UNITS PER HOUR
CAPACITY
CONTROLS CONTRACTOR
CEILING DIFFUSER /CONDENSATE DRAIN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CUBIC FEET PER MINUTE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CEILING
COLUMN
CONCRETE
CONDENSATE
CONNECT /CONNECTED /CONNECTION
CONTINUOUS /CONTINUATION
CONTRACTOR
COORDINATE
COEFFICIENT OF PERFORMANCE
COOLING TOWER
CUBIC /CONDENSER UNIT
DOMESTIC COLD WATER /CONDENSER WATER
DUCTBOARD /DRY BULB
DECIBEL
DIRECT DIGITAL CONTROL
DEFLECTION
DEGREE/ DEGREES
MODULAR DIFFUSER (GWB CEILING)
DIAMETER
DAMPER
DOWN
MODULAR DIFFUSER ("T -BAR" CEILING)
DRAWING
EXHAUST
EACH
ENTERING MR TEMPERATURE
EGGCRATE GRILLE /END CAP /ELEC CONTRACTOR
ENERGY EFFICIENT RATING
EXHAUST FAN
EFFICIENCY
ELEVATION
MECHANICAL ABBREVIATIONS
HZ HERTZ
IBC INTERNATIONAL BUILDING CODE
ICW INDUSTRIAL COLD WATER
ID INSIDE DIAMETER /DIMENSION
lE INVERT ELEVATION
IMC INTERNATIONAL MECHANICAL CODE
IN INCHES
IN WG INCHES WATER GAUGE
IPLV INTEGRATED PART LOAD VALUE
KW KILOWATTS
LAT LEAVING AIR TEMPERATURE
LB /LBS POUND /POUNDS
LD /LAN DIFF LINEAR DIFFUSER
LF /LIN FT LINEAL FOOT /FEET
LPG
LVG
LWA
LING
LWR
LINT
MAX
MAU
MBH
MCA
MD
MFR
MISC
MIN
MT
MID
MUW
N/A
NC
NG /NGAS
NIC
NO
NPW
OA /OSA
OB
OBD
OD
P
EQUIPMENT
EXTERNAL STATIC PRESSURE
ENTERING WATER TEMPERATURE
EXISTING
FAHRENHEIT
FIRE ALARM CONTRACTOR
FIRE DAMPER
FIRE DEPARTMENT CONNECTION
FINISHED FLOOR
FURNISHED AND INSTALLED BY CONTRACTOR
FURNISHED AND INSTALLED BY OWNER
FULL LOAD AMPS
FLEXIBLE
FLOOR
FIAT ON BOTTOM
FURNISHED BY OTHERS. INSTALLED BY CONTRACTOR
FLAT ON SiDE
FLAT ON TOP
FIRE PROTECTION
FEET PER MINUTE
FIRE /SMOKE DAMPER
FOOT /FEET
FUTURE
FACE VELOCITY
GRILLE
GAUGE /GALLON
CALvANIZED
GENERAL GFNERAL CO`i T RACTCR
Gm
GALLONS PER V :N;; T E
GRILLE
GI tE /REGISTER /C :t FUSER
GYPS! IV Wk_L BOARD
HEAD
i i.2PiZOTAL ;,
� &
HOUR
HEATING I:NG SEA' SCl '' PEP CRUA' C E FACTOR
BALL TRANSFER C.R ai
fO WATER F � -. . is ��a
WA E RE_ '
HOT WATER SUPPLY
HEAT ExC; AV: R
PCF
PD
PH
POC
PRESS
PSI
PSIG
QTY
R
RA
RD /RND
REF
REG
REO'D
RF
RG
RL
RPM
RS
S
SA
SAT
SD
S/D
SEER
SENS
SG
SL
SM
SPEC
SO
SOG
SP
SOFT
SR
SS
STRUC
T
TA
TEMP
TBO
TG
TOC
TOD
TOS
TOT
TSP
TSTAT
TYP
UH
UNO
v
V1AOC
VD
VEL
VERT
iA'FD
Ili
WG
w/J
WiSF
WSEC
LIQUID PROPANE GAS
LEAVING
SOUND POWER
LOW WALL GRILLE
LOW WALL REGISTER
LEAVING WATER TEMPERATURE
MAXIMUM
MAKE UP AIR UNIT
1000 BRITISH THERMAL UNITS
MINIMUM CIRCUIT AAPACITY
MOTORIZED DAMPER
MANUFACTURER
MISCELLANEOUS
MINIMUM /MINUTE
MOUNT
MOUNTED
MAKE -UP WATER
NOT APPLICABLE
NORMALLY CLOSED /NOISE CRITERIA
NATURAL GAS
NOT IN CONTRACT
NORMALLY OPEN /NUMBER
NON - POTABLE WATER
OUTSIDE AIR
OPPOSED BLADE
OPPOSED BLADE DAMPER
OUTSIDE DIAMETER /DIMENSION
PUMP
POUNDS PER CUBIC FOOT
PRESSURE DROP
PHASE
POINT OF CONNECTION
PRESSURE
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH GAUGE
QUANITY
RETURN GRILLE /RELOCATED /RETURN
RETURN AIR
ROUND
REFERENCE
REGISTER
REQUIRED
RELIEF
RETURN GRILLE
REFRIGERANT LIQUID
REVOLUTIONS PER MINUTE
REFRIGERANT SUCTION
SUPPLY
SUPPLY AIR
SATURATION
SMOKE DETECTOR
SLIP & DRIVE CONNECTION
SEASONAL ENERGY EFFICIENCY RATING
SENSIBLE
SUPPLY GRILLE
SOUND LINED
SPIRALMATE /SHEETMETAL
SPECIFICATION
SCREENED OPENING
SLAB ON GRADE
STATIC PRESSURE
SQUARE FEET
SIDE WALL REGISTER
STAINLESS STEEL
STRUCTURAL
TRANSFER
TRANSFER AIR
TEMPERATURE/TEMPORARY
TO BE DETERMINED
TRANSFER GRILLE
TOP OF CONCRETE /CURB
TOP OF DUCT
TOP OF STEEL/TOP OF SLAB
TOTAL
TOTAL STATIC PRESSURE
THERMOSTAT
TYPICAL
UNIT HEATER
UNLESS NOTED OTHERWISE 'TOOT
VENT. AND INDOOR AIR QUALITY CODE
VOU JOIE DAVPER
VEL0CiTY
VERTICAL
VAR ABLE EREIDUENCY DRIVE
VOLUME
TAPE. / A LS. +ARA.-PLD DUCT
'ABET BULB
RATER GA:
MTH
WiTFIOU3e
WATTS PER SQUARE FOOT
WXST-WTON STATE ENERGY CODE
t
MECHANICAL LEGEND
10x10 ►1 RECTANGULAR SUPPLY AIR DUCT -
10x,_. 10 TURNING UP OR TOWARD
i 10x 10 � x :1
10x10
f ii 0 • DUCT OVERLAP
0
1 it
BOOT TAP
-,r-i
1:110
0
2 - CHM
r-- a.r aMR -s
r---- ______ r ---- -- IPG
cows ----- ws cons
s
coon can --5
t-- aa ao
o ao -5
RECTANGULAR SUPPLY AIR DUCT -
TURNING DOWN OR AWAY
RECTANGULAR EXHAUST OR RETURN AIR
DUCT - TURNING UP OR TOWARD
RECTANGULAR EXHAUST OR RETURN AIR
DUCT - TURNING DOWN OR AWAY
ROUND DUCT - TURNING UP OR TOWARD
ROUND DUCT - TURNING DOWN OR AWAY
OVAL DUCT - TURNING UP OR TOWARD
OVAL DUCT - TURNING DOWN OR AWAY
45' TAP
VOLUME DAMPER
CHANGE OF ELEVATION RISE(R) DROP(D)
TRANSITION
TURNING VINES /SPUTTERS
DUCT MOUNTED SMOKE DETECTOR
BACK DRAFT DAMPER FLEXIBLE DUCT
AIR FLOW DIRECTION (FORCED AIR)
AIR FLOW DIRECTION (DRAWN AIR)
MOTOR OPERATED DAMPER
FLEX CONNECTION
SMOKE DAMPER
FIRE DAMPER
COMBINATION FIRE & SMOKE DAMPER
SOUND TRAP
ACCESS DOORS
ACOUSTICALLY LINED DUCT (SOUND LINED)
DUCT BOARD
FABRIC DUCT
VAV BOX
CEIUNG SUPPLY AIR DIFFUSER (SHOWN
WITH REDIRECTED AIR CORE)
CEILING RETURN, TRANSFER OR
EXHAUST AIR GRILLE
SLOTTED DIFFUSER (PLAN VIEW)
ROUND DUCT SYMBOL
FLAT OVAL DUCT SYMBOL
DEGREES SYMBOL
POINT OF CONNECTION
GRD TAG IDENTIFIER = TYPE
SIZE
THERMOSTAT /TEMPERATURE SENSOR
HUMIDITY SENSOR
SMOKE DETECTOR
STATIC PRESSURE SENSOR
EXISTING DUCTWORK
DEMO DUCTWORK
WALL - MOUNTED GRILLE
o PIPE ELBOW UP
PIPE [1807) ON
t DIRECTION OF FLOW
z DIRECTION OF SLOPE DOWN
j PLUG OR CAP
GAS PRESSURE REDUCING ASSEMBLY
SOLENOID VALVE
PUvP
CiaLED WATER SUPPLY CH:! LED WATER RETURN
REFRIGERANT MUD
REFRIGERANT SUCTION
NATURAL GAS
LIQU:D PROPANE GAS
COMW ?TER SUPPLY
CONDENSER WATER RETURN
HEATING *ATER SUPPLY
HEATING WATER RETURN
CONDENSATE
•
MECHANICAL GENERAL NOTES
1. ALL WORK SHALL CONFORM 10 ALI. APPLICABLE CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO
THE 2.003 IBC, 2003 WSEC, 2003 IMC St 2003 WSVIAQC.
2. DIMENSIONS ARE 10 1 ACE OF STUD, CONCRETE, OR MASONRY UNLESS NOTED OTHERWISE.
3. DO NOT SCALE DRAWINGS. DIMENSIONS GOVERN.
4. D SCREPANC ES OCSL'ED1NG Wj ETC. NOTIFY ENGINEER OF ANY
5. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK DETAILS
SHALL BE THE SAME AS FOR OTIIER SIMILAR WORK. IF QUESTIONS CAN NOT BE RESOLV IN THIS
MANNER, CONTACT THE ENGINEER PRIOR TO PROCEEDING.
6. ALL STRUCTURAL OPENINGS AND PLATFORMS SHALL. BE PROVIDED BY THE GENERAL CONTRACTOR UNLESS
NOTED OTHERWISE.
7. ALL JOINTS IN SUPPLY AND RETURN AIR DUCTS SHALL BE SEALED TO SMACNA C CLASS, OR ABOVE.
8. ALL CEILING DIFFUSERS ARE 4 - -WAY THROW UNLESS NOTED OTHERWISE.
9. ALL DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS AFTER LINING HAS B INSTALLED.
10. OUTSIDE A IR INTAKES ON ALL AIR HANDLING UNITS SHALL BE 10 FEET AWAY FROM ANY FUEL
BURNING EQUIPMENT, AND 10 FEET AWAY FROM, OR 3 FEET BELOW ANY PLUMBING VENT OR EXHAUST
OUTLET.
11. ALL AIR ECONIMIZERS SHALL BE CAPABLE OR THE FOLLOWING:
A. 0% TO 100% OF THE DESIGN SUPPLY AIR
B. CONTROLLED BY A CONTROL SYSTEM DETERMINING IF THE OUTSIDE AIR CAN MEET PART OR ALL OF THE
BUILDING COOLING LOADS.
C. INTEGRATED TO PROVIDE PARTIAL COOLING EVEN WHEN MECHANICAL COOLING IS REQUIRED.
12 DAMPERS U ICALLY WHEN OPENINGS IS OFF OR UPON POWER MOTORIZED A OR BY
ENERGY CODE.
13. THE CONTROL SYSTEM SHALL BE 7 -DAY PROGRAMABLE CAPABLE OF BEING SET FOR SEVEN DIFFERENT DAY
TYPES PER WEEK AND HAVE DEADBAND SETTING OF Al LEAST 5 DEGREES F. BETWEEN THE HEATING AND COOLING
SETPOINTS. AHU CONTROL SYSTEM SHALL INCLUDE MICROPROCESSOR AND BE CAPABLE OF RESETTING
SUPPLY AIR TEMPERATURES BY REPRESENTATIVE BUILDING LOADS.
14. RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER WITHIN
90 DAYS OF THE DATE OF SYSTEM ACCEPTANCE PER THE WASHINGTON STATE ENERGY CODE. AN OPERATING
MANUAL AND MAINTENANCE MANUAL SHA BE PROVIDED TO THE B U IL DIN G OWNER. ALL I SYSTEMS
S BE BAL AND A WRITTEN BALANCING REPORT SHALL BE PROVIDED TO THE OWNER.
HVAC CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT THEY OPERATE IN ACCORDANCE
WITH SPECIFICATIONS AND APPROVED PLANS. A PRELIMINARY COMMISIONING REPORT OF TEST PROCEDU
AND RESULTS SHALL BE PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY. A
COMPLETE FINAL COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE PROVIDED TO THE
OWNER. COMMISIONING, SYSTEM BALANCING, RECORD DRAWINGS AS REQUIRED PER THE WASHINGTON STATE
ENERGY CODE.
15. DUCT SYSTEMS SHALL COMPLY WITH MECHANICAL CODES AND SMACNA STANDARDS. DUCTS 28" AND LARGER,
WHICH ARE SUSPENDED MORE THEN 12" BELOW STRUCTURAL SYSTEM, SHALL BE EARTHQUAKE BRACED.
16. PROVIDE EARTHQUAKE RESTRAINTS FOR HVAC EQUIPMENT AS REQUIRED BY SMACNA SEISMIC RESTRAINT
M EQUIPMENT SUPPORTS. HAZARD B WIRES FOR CEILING SYSTEM ETC. SHALL NOT BE HUNG OFF HVAC EQUIPMENT OR
17. PROVIDE ARE AND COMBINATION FIRE /SMOKE DAMPERS WHERE SHOWN ON PLANS AND WHERE REQUIRED
PER CODE.
18. ALL PIPING PENETRATIONS THROUGH RATED ASSEMBLIES SHALL BE SEALED WITH AN UL APPROVED FIRE
CAULKING.
19. SMOKE DETECTORS PROVIDING AUTOMATIC SHUTDOWN SHALL BE PROVIDED FOR HVAC EQUIPMENT DEUVERING
IN EXCESS OF 2000 CFM PER CODE. SMOKE DETECTORS SHALL BE FURNISHED AND NSTALLED BY ELECTRICAL
CONTRACTOR UNLESS NOTED OTHERWISE. POWER- WIRING AND INTERLOCK TO FIRE ALARM SYSTEM BY ELECTRICAL
CONTRACTOR AS APPLICABLE.
20. ACCESS PANELS SHALL BE PROVIDED BY MECHANICAL CONTRACTOR AND INSTALLED BY GENERAL CONTRACTOR.
21. ALL MOTOR STARTERS NOT SHOWN IN EQUIPMENT SCHEDULES SHALL BE FURNISHED AND INSTALLED BY
ELECTRICAL CONTRACTOR.
22. A. ALL VERTICAL AIR IDE SHAFTS OR R BE FOLLOWING R ITH A CONTINUOUS SEAL FOR THE
LENGTH OF THE JOINT, INCLUDING THE SHAFT CORNERS (BY GC
B. TOP AND BOTTOM WALL TRACKS SHOULD BE CAULKED ALONG THEIR ENTIRE LENGTH (BY GC)
C. ANY FLOOR CDECKING PERPENDICULAR TO THE SHAFT SHALL BE CAULKED (BY GC)_ FILUNG WITH ROCK WOOL
D. ANY PENETRATIONS OF THE SHAFT CONSTRUCTION (DUCTWORK, CONDUIT, PIPING, ...) SHALL BE
SEALED ON BOTH SIDES OF THE PENETRATION.
E. USE SECTION 905 OF THE 2003 IBC FOR MAXIMUM ALLOWABLE LEAKAGE AREA, FOLLOWING THE
GUIDELINES FOR TIGHT STAIR SHAFT CONSTRUCTION.
F. ALL DOORS SHALL BE PROVIDED WITH TIGHT FITTING GASKETS, AND OPEN AGAINST THE DIRECTION OF
ROOM /SHAFT PRESSURE.
23. MAXI LENGTH OF F LE X IBL E DUCT SHALL BE 5 FEET_ REFER TO INSTA DETAI FOR SUPPORT
REQUIREMENTS. FLEXIBLE DUCT FLAME SPREAD RATING SHALL BE < 25 AND SMOKE DEVELOPED RATING
SHALL BE < 50. USE FLEXIDUCT MODEL G -KM FOR LOW AND MEDI PRESU AP OR APPROVED EQUAL
INSULATE DUCT PER NOTE 11 ABOVE.
24. LOCATION AND DETAILS OF EQUIPMENT DUCT ROUTING, AND CONNECTIONS ME APPROXIMATE.
COORDINATE FINAL LOCATIONS WITH OMER TRADES_ INSTALL IN ACCORDANCE WITH APPROVED SUBMITTALS
AND DETAIL DRAWINGS WHEN APPLICABLE.
1_ REFER TO ENERGY COLE SECTION 1414.2 FOR FURTHER REQUIREMENTS
2. REQUIREMENTS APPLY TO HEATED AND VECH. Nt'LLY COOLED DUCT SYSTEMS AS NOTED. INSULATED COOLED
DUCTS REOUIRED 1YETA :DER (PERU < 0.51 AND SEALED JOINTS.
'M
3. ATHERPROCF EtP: ER R .C;j:RED A P . ' NO CUCF, %CRlc TO MAINTAIN WATER TIGHTNESS.
4_ INSULATE OUTSiCE r•R DUC S u 66 ;:_ri NG D• ELCFE LEAL PER ENERGY CODE CHAPTER 13 UNTIL
CONNECTED INSTA T Nj TO. . EC_i:c±.'ENT, SEPiED OR TO THE CCJE REOU!RED SHUTOFF DAVPER (THEN R -7 FOR REST OF
L
5. P -7 CAN 6: USE,' :N LIEU C= E ELOPE I`+SuiAT:ON LEVEL IF CELXCATED OUTSIDE RR SYSTEM
AND LESS THAN 2.7;, -3 CFv.
- co cT - - -.4 - �a '�� _- �y' � l i NO p� i .R
DRAWING INDEX
SHEET N0.
110.00
Al2.01
SHEET TITLE
LEGEND. ABBREVIATIONS. GENERA. NOTES. & SHEET INDEX - HVAC
FIRST FLOOR & ROOF PLAN, SCHEDULES & DETNLS - HVAC
13-14 & INTERURBAN ADD 10 SEATTLE POR OF NW I/4 OF NE 1/4 OF SEC 26 do OF NE 1/4 OF
NW 1/4 OF SEC 26 do OF SW 1/4 OF SE 1/4 OF SEC 23 & GI SE I/4 OF SW 1/4 OF SEC 23 do
OF INTERURBAN ADD TO SEATTLE & OF BROOKVALE GARDEN TRACTS & OF W H GLUM DONATION LAND
CLAIM NO 40 - BEG SW C0R OF SW 1/4 OF SE 1/4 OF SEC 23 TH N 89 -40 -24 W 217 FT TH N
0 -19 -36 E 150 FT TO TPOB TH S 89 -40 -24 E 151.60 FT TH N 0 -19 -36 E 72 FT TH S 89 -40 -24
E 406.80 FT TH S 0 -19 -36 W 182 FT TH S 89 -40 -24 E 179.20 FT TH N 0 -19 -36 E 366.84 FT
1H S 87 -25 -13 E 253.52 FT TH N 0 -19 -36 E 208.77 FT TO BEG OF CURVE TO ROT 45 FT RAD 1H
PLC SD CURVE 45.96 FT TAW OF COMPOUND CURVE TH ALG CURVE TO MT 122.35 FT RAD 63.68 FT
TO SLY MGR OF TUKWILA PARKWAY TH S 88 -40-00 W ALG SD SLY MGR 76.15 FT TO DEG OF CURVE
TO RGI 1472.39 FT RAD TH ALG SD CURVE & SLY MGR 423.38 IT 1H N 74 -51 -30 W 407.05 FT TO
BEG OF CURVE TO LFT 552.62 FT RAD TH ALG SD CURVE & SLY IIGN 185.63 FT TAP FR WM THE
TPOB BEARS S 0 -19 -36 W TH S 0 -19 -36 W 678.90 FT TO TPOB AEU PARCEL B OF CITY OF
TUKWILA DORY LN ADJ NO 87 -8 -BLA RECORDING NO 8712291101
3
.
a
- ple+mt No.
„San review aPProval IBS'b11)edt blows .14 omhs all
• AipitvaloVoonstroction elsidirnenb does not awbodiv-
tl1et violation . Qf,any Dods oc
of approved Id tonal= sledge
s g.q-ch:'-des Oa be made to the s?oopa
with6ut Pier approval cf
1 7:::Fitip B alnding Dlv'i n.
11:7 : : :cns vat require a new p'.an zu:::rl:t -
r..d may indude additional plan review fees.
id'. :,,
LEGAL DESCRIPTION
1'
APN NUMBER
3597000245
aty o.- - Tla .„._.
BUILDING OVISION
,..ti hrr
2.sr4o ..4
VICINITY MAP
NO SCALE
SITE
fo
SITE MAP
NO SCALE
NO SCALE
a
r
•1•
IMILA MOW
MOM
4,4EPARATE PERtyz
C 4 JI)ED FOR:
.K: 'b r ? re a1
1110
IT GPFP 1 Ong
City of Tukwila
6UJLOINa DIVISION
t
N.n .•
SITE AERIAL MAP AN )
ISSUE FOR PERMIT
cv
Hermanson
Hennonson Company LLP
1221 2nd Avenue North
Keud. Woshington 98032
T&: (206) 575 -9700
Fax: (206) 575 -9800
www.hermanson.com
Conlroctor Reg 1: HERWVCL0058J
RADIO SHACK Ti
SOUTHCENTER MALL SPACE 320
633 SOUTHCENTER BLVD
TUKWILA, WASHINGTON 98188
1 EXPIRES 1/29/2008 I
Revisions
REVIEWED FOR I
CODE COMPLIANCE
_1E8 - 7 7001
City Of Tukwila
BUICfl1N6 ul`fTSTIN
01 -23 -07 ON ISSUE FOR PERMIT
No. Dote By Description
Design Team
Design DN
Drown ER
Necked DN
Scale AS NOTED
Drawing Number C --0119 -781
Project Number 11 -7 -781
Issue Dote
01 -23-07
LEGEND, ABBREVIATIONS,
GENERAL NOTES, &
SHEET INDEX - HVAC
M0.00
CITYOFTPNANNA
JAN 2�
0 1 (
MI )
H ermanson
Hermonson Compony UP
1221 2nd Avenue North
Kent. Washington 98032
Tel: (206) 575 -9700
Fax: (206) 575 -9800
www.hermanson.com
Contractor Reg j: HERTMCL005W
RADIO SHACK TI
SOUTHCENTER MALL SPACE 320
633 SOUTHCENTER BLVD
TUKWILA, WASHINGTON 98188
% 1 ir .
1r i
to , o
rl
N
1 EXPIRES 1/29/2008 1
Revisions
01-23-07 DN ISSUE FOR PERMIT
No. Dote By Description
Design Team
Design DN
Drown ER
Checked DPI
Scale AS NOTED
Drawing Number C --0119 -781
Project Number 11 -7 -781
Issue Dote 01 -23-07
FIRST
SCHEDULES
II
w
FLOOR & ROOF PLAN
& DETAILS
- HVAC
M2. I
...,.: Z I
arfOCTUKWILA
JM 2 9 2CO1
PERIKCINTER
r
PACKAGED ROOFTOP HEAT PUMP UNIT SCHEDULE
LAST UPDATED: 01/16/07
UNIT
TAG
HP -1
LOCATION
ROOF
AREA
SERVED
RADIO SHACK - SUITE 320
BASIS OF
DESIGN
YORK PREDATOR 13P- 102E18C2
ENT AIR TEMP
DB. DEG. F
80.0
WB. DEG. F
65.0
SUPPLY
CFM
3,000
MIN. OA
CFA
700
E.S.P
IN. NG.
0.80
SEER/EER
10.3 EER
HSPF /COP
3.2 COP
COOLING CAPACITY
TOTAL BTUH
SENS. BIUH
82
HP HEAT CAPACITY
STAGES
99
BTUH
58
ADO'L HEAT
KW
NOTE 3
TYPE
DRIVE
SUPPLY FAN
RPM BHP
HP
FC
BELT
880
1.5
2
TYPE
DRNE
RETURN 'i ' t FAN
RPM BHP ' HP
1,075
ELEC
MCA r V/PH
3/4
118
208/3
WOW
IN POUNDS
1673
REMARKS
1.2.3,4,5
NOTES:
1
2
3
4
5
l R= 1 -1/2 "W
RADUIS ELBOW
R
SELF - ADHESIVE 1/4"
FOAM GASKET
(3) ff10- 16x3/4" SELF
TAPPING SMS 0
EA 18GA METAL
CONNECTOR
2" INSULATION
BY G.C.
FOR 20+ TON UNITS,
2 LAYERS OF 1/2" GWB
AND 4" FIBERGLASS IF
ROOF OPENING IS
LARGER THAN DUCT
% • a
PROVIDE FULL ECONOMIZER CYCLE WITH POWERED EXHAUST.
MINIMUM UNIT EFFICENCY 10 MEET THE ENERGY CODE TABLE 14 -1
PROVIDE 7 -DAY PROGRAMMABLE T'STAT, 18 KW ELECTRIC BACKUP HEAT, RETURN DUCT SMOKE DETECTOR
DISCONNECT SWITCH AND POWER OUTLET WITHIN 25' OF UNIT ON ROOF BY ELECTRICAL CONTRACTOR
3/4' COPPER CONDENSATE DRAIN TO ROOF SPLASH BLOCK (PER OWNER TENANT STANDARDS) BY PLUMBING CONTRACTOR
•
SQUARE ELBOW
LOW PRESSURE
DEAD HEAD FITTING
AC UNIT, REFER TO MFG
DETAILS FOR EXACT
CONFIGURATION
(3) fl10- 16x3/4" SELF
TAPPING SMS 0 EA
18GA METAL CONNECTOR
EARTHQUAKE RESISTANT,
4" WIDE 18GA CONNECTOR
(TIP 4 PLACES -2 EA SIDE)
16GA GALVANIZED
FACTORY ROOF CURB
CANE STRIP/ FLASHING
CANT STRIP / FLASHING
BY GC
14 "UNO
ROOFING
FASTEN TO ROOF PER
STRUCTURAL PLANS
CONNECTIONS ( AC ROOF CURB SECTION
M`.01 NOT TO SCALE
APPROX 2" O.C.
DETAIL OF TURNING VANE
j t.=1/4"W. 4" MIN.
MEDIUM PRESSURE
BOOT DUCT TAP
POWER CABLE
TERMINATION
(BY E.C.)
ATTACH FAN
TO FRAMING
MEMBER
TURNING VANES REQUIRED
W AIR VELOCITY IS
GREATER THAN 800 FPM
TYPICAL DUCT FITTINGS
M2.01 NOT TO SCALE
CEILING
EXHAUST
GRILLE
LOW PRESSURE
DUCT TAP
EXHAUST
EQUAL SPLIT SQUARE TEE
CEILING MOUNTED FAN DETAIL
7 -07 NOT TO SCALE
MEDIUM PRESSURE
CONICAL TAP
SPACER
EXHAUST DUCT
—. CEILING JOIST
CEIUNG
MATERIAL
NOTES:
1. INTERLOCK FAN WITH WALL SWITCH AND SPEED CONTROL (BY GC)
2. POWER & LINE VOLTAGE INTERLOCK WIRING ( BY E.C.)
FLOOR PLAN CONSTRUCTION NOTES:
1. NEW LOW PRESSURE SUPPLY DUCT SUPPLIED AND
INSTALLED BY HVAC CONTRACTOR. PROVIDE
TRANSITIONS AS REQUIRED, DUCT DIMENSIONS
INDICATED ARE CLEAR INTERNAL MR PATH DIMENSIONS.
EXISTING METAL ROUND DUCTWORK MAY BE RE -USED
IF OF ADEQUATE SIZE AND IN GOOD CONDITION.
RE- INSULATE AS REQUIRED. HOLD ALL DUCTWORK
(NEW AND /OR EXISTING) AS HRH AS
POSSIBLE /PRACTP„AL IN JOIST SPACE.
GRILLES, REGISTERS, AND DIFFUSERS
LAST UPEMTEO: 12/04/2006
UNIT
TAG
WG -1
WG -2
WG -3
WHITE
WHITE
WC-4
WG -5
CO-1
CD-2
CD -3
CD -4
CD-5
CO -6
CD -7
CO -8
0G -1
CG -2
EG -1
EG -2
RG -1
RG -2
RG -3
RG -4
SERVICE
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
SUPPLY
RETURN
RENRN
RETURN
RETURN
RETURN
RETURN
BASIS OF
DESIGN
TINS 300F5
TITUS 300FS
TAUS 300FS
11115 300RL
TINS 30081.
TINS MCO
THUS MCO
TITUS MCO
TITUS MCD
TITUS MCD
TITUS MCO
TITUS LCD
TITUS LCD
TITUS PCS
TITUS PCS
TAUS 501
TITUS 50F
TINS 50F
TITUS 5OF
TITUS 50F
TITUS 8F
TYPE
GRILLE
GRILLE
GRILLE
GRILLE
GRILLE
4 -WAY CEILING
4 -WAY CEILING
4 -WAY CEILING
4 -WAY CEILING
4 -WAY CEILING
4 -WAY CEILING
4 -WAY CEILING
4 -WAY CEILING
PERFORATED
PERFORATED
EGGCRATE GRIUE
EGGCRATE GRILLE
EGGCRATE GRILLE
EGGCRATE GRILLE
EGGCRATE GRILLE
PERFORATED
MOUNTING
SURFACE
SURFACE
SURFACE
SURFACE
SURFACE
LAY N
LAIN
LAYN
LAPIN
SURFACE
SURFACE
SURFACE
SURFACE
LAPIN
LAYINN
LAN
LAIN
IAYN
SURFACE
LAY1N
FINISH
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHITE
WHRE
WHITE
WHITE
WHITE
WHITE
NECK SIZE
DUl N.
12
S0. IN.
34X34
48X48
12X12
12X6
6X6
10x10
8X8
6X6
12X12
10X10
8X8
6X6
12X12
18X18
6X6
10X10
24X12
24X24
24X24
12X6
FACE SUE
DIA. N.
WHITE
WHITE
SO. N
36X36
50X50
14X14
14X8
8X8
24X24
24X24
24X24
24X24
15X15
13X13
11X11
17X17
24X24
24X24
6X6
1
24X12
24X24
26X26
12X6
MAX
CFI(
4.500
8,750
450
250
120
350
230
110
500
350
230
110
500
2.330
200 -350
30 -100
105 -340
1.100
2200
2,200
200
NOISE
CRITERIA
30
32
16
19
15
24=
17
15
26
24
17
15
26
45
27
11
15
22
24
24
28
REMARKS
24X16SL UP
TO HP- I
ON ROOF
22X18SL UP TO
HP -1 ON ROOF
M �
0
6" WEATHER
/T CAP 0 3' ABOVE
. ROOLL[VEL
Y
1
2
3
4
FAN SCHEDULE
LAST UPDATED: 01/18/07
UNIT
TAG
EF -1
LOCATION
CELING
AREA
SERVED
TOILET RM
BASIS OF
DESIGN
G REENIECK SP -6110
TYPE
CEA.INGG
CRT
75
E.S.P.
N. W.G.
0.25
RPM
748
BHP
ELECTRICAL
V /PH
120/1
80W
LWIA
43
WEIGHT
N POUNDS
15
REMARKS
1.2.3.4
0 =2 -200
80
BOT AT LIGHT
ELEVATION
ELECTRICAL DISCOMECT AND MOTOR STARTER
BACKORATT DAMPER
SPEED CONTROLLER
CONTROLLED VIA WALL SWITCH (PROVIDED AND
ROOF PLAN - HVAC
SCALE 1/8 =
24X16SL
TV IN EL
Y
1
22X 185E
(AS REQUIRED) BY ELECTRICAL CONTRACTOR
INSTALLED BY ELECTRICAL CONTRACTOR)
24X24 OPENING NITER
CUT ABOVE CEILING
FIRST FLOOR PLAN - HVAC
e SCALE: 1/8' = 1' -(r
ROOF PLAN CONSTRUCTION NOTES:
1. CONDENSATE TO SPLASH BLOCK PER TENANT MANUAL
2. VERIFY LOCATION BY FIELD WITH BLDG OWNER PRIOR TO
INSTALLATION
3. SEE TENANT MANUAL FOR SPECIFIC CURB & SUPPORT
CRITERIA
4. 10' MIN FROM OUTSIDE AIR TO BUILDING EXHAUST OR VENTS
R6 -2 RG -2
180W 160W Ail
T ` DT4 -450
1120 (TIP 4)
OT4 -500
124"`
DT4 -500
120
8
ISSUE FOR PERMIT
•
1 a