HomeMy WebLinkAboutPermit M07-283 - WESTFIELD SOUTHCENTER MALL - BARE ESCENTUALSBARE ESCENTUALS
827 SOUTHCENTER MALL
M07 -283
Parcel No.:
Address:
Suite No:
Tenant:
Name:
Address:
Owner:
Name:
Address:
Contact Person:
Name:
Address:
6364200010
827 SOUTHCENTER MALL TUKW
BARE ESCENTUALS
827 SOUTHCENTER MALL , TUKWILA WA
WEA SOUTHCENTER LLC
11601 WILSHIRE BLVD , LOS ANGELES CA
BOB ROBINSON
37936 23 PL S , FEDERAL WAY WA
Contractor:
Name: AMERICA'S BEST HEATING & A/C
Address: 16122 STATE RT 9 SE , SNOHOMISH WA
Contractor License No: AMERIBH951 O 1
DESCRIPTION OF WORK:
TENANT IMPROVEMENT: NEW VAV -BOX WITH NEW DUCTWORK & TOILET EXHAUST FAN.
Value of Mechanical: $10,800.00
Type of Fire Protection: SPRINXLERS /AFA
Furnace: <100K BTU
>100K BTU
Floor Furnace
Suspended/Wall/Floor Mounted Heater
Appliance Vent
Repair or Addition to Heat/Refrig /Cooling System....
Air Handling Unit <10,000 CFM
>10,000 CFM
Evaporator Cooler
Ventilation Fan connected to single duct
Ventilation System
Hood and Duct
Incinerator: Domestic
Commercial/Industrial
City'tif Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
MECHANICAL PERMIT
EQUIPMENT TYPE AND OUANTITY
0
0
0
0
0
0
1
0
0
0
1
0
0
0
* *continued on next page **
Permit Number: M07 -283
Issue Date: 05/29/2008
Permit Expires On: 11/25/2008
Phone:
Phone: 253 677 -6874
Phone: 425 -338 -4310
Expiration Date: 09/21/2009
Fees Collected: $281.10
International Mechanical Code Edition: 2006
Boiler Compressor:
0-3 HP/100,000 BTU 0
3-15 HP /500,000 BTU 0
15-30 HP /1,000,000 BTU.. 0
30-50 HP /1,750,000 BTU.. 0
50+ HP /1,750,000 BTU 0
Fire Damper 0
Diffuser 15
Thermostat 0
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment 0
doc: IMC -10/06 M07 -283 Printed: 05-29 -2008
Permit Center Authorized Signature:
The granting of
construction or
Signature:
Print Name:
doc: IMC-10 /06
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
"Lag
Permit Number: M07 -283
Issue Date: 05/29/2008
Permit Expires On: 11/25/2008
I hereby certify that I have read and e - ed this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied whether specified herein or not.
not presume to give authority to violate or cancel the provisions of any other state or local laws regulatinc
work. I am au . • % ed to sign and obtain this mechanical permit.
Date: 05 f 74 VV"
Date:
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspender
or abandoned for a period of 180 days from the last inspection.
M07 -283 Printed: 05-29 -2008
Parcel No.: 6364200010
Address:
Suite No:
Tenant:
827 SOUTHCENTER MALL TUKW
BARE ESCENTUALS
1: ** *BUILDING DEPARTMENT CONDITIONS * **
7: ** *FIRE DEPARTMENT CONDITIONS * **
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
PERMIT CONDITIONS
Permit Number:
Status:
Applied Date:
Issue Date:
M07 -283
ISSUED
12/19/2007
05/29/2008
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
4: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
5: Manufacturers installation instructions shall be available on the job site at the time of inspection.
6: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
8: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
9: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
10: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
11: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
12: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
13: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
14: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
15: An electrical permit from the City of Tukwila Building Department Permit Center (206 - 431 -3670) is required for this
project.
doc: Cond -10/06 M07 -283 Printed: 05-29 -2008
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
16: All electrical work and equipment shall conform strictly to the standards of the National Electrical Code. (NFPA 70)
17: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
18: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 - 4407.
doc: Cond -10/06
* *continued on next page **
M07 -283 Printed: 05-29 -2008
Signa
Print Name:
doc: Cond -10/06
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not pre; e to give authority to violate or cancel the provision of any other work or local laws regulating
construction or the performance of wo
///ICI
earl 11 A
M07 -283 Printed: 05-29 -2008
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http: / /www. ci. tukwila. wa. us
/ i/
Building Permit No.
Mechanical Permit No.
Plumbing/Gas Permit No.
Public Works Permit No.
Project No. i
office use only)
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by
* *Please Print **
� ,.��p F ,� King Co Assessor's Tax No.: � �7 I L I 0 ` 001 v
e,.� r So 4 , t Tl CEN 1 Cf" 1 j�► 1 Suite Number: r Floor:
Tenant Name: trif -C �S C JT
Site Address:
New Tenant: ❑ Yes ❑ ..No
Property Owners Name: W EST F1 ,p 4 CQ�QO 2 f T, t>fY
Mailing Address: Iilvb 0 WILSI t1'E SLVP • 1 1411 - 1 FL / City LOS k615 sp y ' DO15 Zip
CONTACT PERSON —who ao we contact when your peril* la ready to be toned
_
Name: P I Y! ✓) Day Telephone: z 47 7_&7t
�� yy{{
Mailing Address: 1 -5 6%' 3 2 V 1 Y� . e�rl� 1!t/• 9 Op
1 Cit State Zip
E -Mail Address: ,ppr"? 4 ce e_-- e m • , 1 Fax Number: 2 S `
„r
GENERAL CONTRACTOR INFORMATION ,
(Contractor Information for Mecblinieai (pg 4j for,Plumbing and Gal Plptng (pg 5))
Company Name: - 92A-IN O
Mailing Address:
ARCHITECT OF RECORD All plans must be wet stamped by Architect of Recd
Mailing Address:
CON s .hc-f ON zNC . •
1 p / City u Sta Zip
Contact Person: BR Pd' TRAIN O e Day Telephone :: l, 26 " b2-t) 0
E -Mail Address: ?T@ T1 0Nbf ICTIDM. (Air Fax Number: (, t1 I) ) Z- - V2-?)
Contractor Registration Number: Expiration Date:
Company Name: T aft _ASSOC-4 /TTeS
Q:Mpplications\Forms- Applications On Lme\3 -2006 - Permit Application.doc
Revised: 9-2006
bh
City
Contact Person: �� ' ►1 1 Y t �' Day T elephone: r e Z- "S p
E -Mail Address: Fax Number. a - (02 - '
C9 3
ENGINEER OF RECORD - Alt plans must be wet stamped by Engineer of Record
Company Name: ! f t ►' 1 S esI G I to Z1 N 4
Mailing Address:
City State Zip
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Page 1 of 6
0
WILDING PERMIT INFORMATION - 206-431-3670
Valuation of Project (contractor's bid price): $ 8 3 000.00
Scope of Work (please provide detailed information):
IN ion I m Pezva►1
Will there be new rack storage? ■ Yes No If yes, a separate permit and plan submitta • ill be required.
vide All Building Areas in Square Footage Below
NIA
NiPs
i
N 1ft-
„,”
• rltemoaet
13 = S•T
til ..
FIRE PRO CTION/BAZARDOUS MATERIALS:
Addition to
Existing
Structure
l
Type of
Construction per
N /R—
1
T'Pe of
Occupancy per
IBC
PLANNING DIVISION:
Single family building footprint • a of the foundation of all structures, plus any decks over 18 inches an • verhangs greater than 18 inches) N/A
*For an Accessory dwelling, ovide the following: 14 _
Lot Area (sq ft): Floor area principal dwelling: Floor of accessory dwelling:
*Provide docum tation that shows that the _principal l owner lives in one of the dwellings as his or her p ary residence. -
Number of Parking S • is Provided: Standard: N /4— Compact: Handicap:
Will there beach: ge in use? ❑ Yes 14 No If "yes", explain:
Sprinklers Automatic Fire Alarm ❑ None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes No
If `yes', attach list of materials and storage locations on a separate 8-1/2" x 11 paper including quantities and Material Safe Data Sheets.
SEPTIC SYSTEM N
❑ On -site Septic' System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
Q: \ Applications On LmeO.2006 - Permit Application.doc
Revised: 9 -2006
bh
Existing Building Valuation: $
Page 2 of 6
Unit Type:
Qty
Unit Type:
Qty
Unit Type:
Qty -
Boiler /Compressor:
Qty
Furnace<100K BTU
Air Handling Unit >10,000
CFM
Fire Damper
0-3 HP /100,000 BTU
Fumace>100K BTU
Evaporator Cooler
Diffuser
L5
3 -15 HP /500,000 BTU
Floor Furnace -
Ventilation Fan Connected
to Single Duct
Thermostat
15 -30 HP /1,000,000 BTU
Suspended/Wall/Floor
Mounted Heater
Ventilation System
Wood/Gas Stove
30-50 HP /1,750,000 BTU
Appliance Vent
Hood and Duct
Emergency
Generator
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Refrig/Cooling
System
Incinerator - Domestic
Other Mechanical
Equipment
Air Handling Unit
<10,000 CFM
I
Incinerator — Comtn/Ind
MECHANICAL PERMIT INFORMATION - 206 -431 -3670
MECHANICAL CONTRACTOR INFORMATION
Company Name:
Mailing Address:
City
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date:
Valuation of Mechanical work (contractor's bid price): f" o, 1306
Scope of Work (please provide detailed information): 7'. . bR. . , I Jel v V "' g U Y
w 1 ni Nen/ 3IAG1 ' 7b1 L- T" e ciAI S
Use: Residential: New .... ❑ Replacement .... ❑
Commercial: New .... ® Replacement .... ❑
Fuel Type: Electric ❑ Gas....❑ Other. V AV J v�
Indicate type of mechanical work being installed and the quantity below:
Zip
Q: ApplicationsWonns Application On Line\3 - 2006 - Permit Application.doc
Revised: 9 - 2006
bh
State
t
Page 4 of 6
PUBLIC WORKS PERMIT INFORMATION - 206 -433 -0179
Scope of Work (please provide detailed information):
Water District
❑ ...Tukwila
❑ ...Water Availability Provided
❑ ...Total Cut
❑ ...Total Fill
❑ ...Sanitary Side Sewer
❑ ...Cap or Remove Utilities
❑ ...Frontage Improvements
❑ ...Traffic Control
❑ ...Backflow Prevention - Fire Protec
Irrigation
Domes
❑ ...Permanent Water Meter S
❑ ...Temporary Water Meter Ize ..
❑ ...Water Only Meter Si
❑ ...Sewer Main Extens , Public
❑ ...Water Main Exte t on Public
FINANCE INFO ' . ATION
Fire Line Size at Property Line
❑...Water ❑...Sewer
Monthly Service Billing to:
Name:
Water Meter Refund/Billing:
Name:
Mailing Address:
Please refer to Public Works Bulletin #1 for fees and estimate sheet.
cubic yards
cubic yards
.Water District #125
Sewer District
❑ ...Tukwila ❑ ...Val
❑ ...Sewer Use Certificate ❑ ...Sewer ailability Provided
Septic System:
❑ On -site Septic System — For on -site septic syste provide 2 copies of a current septic d gn approved by King County Health Department.
Submitted with Application (mark boxes which apply
❑ ...Civil Plans (Maximum Paper Size — 22" x 34")
❑ ...Technical Information Report (Storm Drainage) ❑ .. Geote . ical Report
❑ ...Bond ❑ .. Insurance ❑ .. Easement( ❑ .. Ma' nance Agreement(s)
Proposed Activities (mark boxes that apply):
❑ ...Right -of -way Use - Nonprofit for less than 72 hours
❑ ...Right -of -way Use - No Disturbance
❑ ...Construction/Excavation/Fill - Right -of -way
Non Right -of -way
n
Water
I ,
II
Q:\ApplicationsWonns- Applications On Line\3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
Call before you Dig: 1- 800 - 424 -5555
Abandon Septic Tank
.. Curb Cut
.. Pavement Cut
❑ ..Looped Fire Line
II
❑ .. Highline
❑ .. Renton
❑ . Wo
❑ .. Storm
WO #
WO #
WO #
Private
Private
.. Right -of -way Use - Profit for less than 72 hours
. Right -of -way Use — Potential Disturbance
in Flood Zone
inage
Number of Public Fire Hydrant(s)
❑ ...Sewage Treatment
❑ .. Renton
❑ . attle
❑ ...Traffic Impact Analysis
❑ ...Hold Harmless — (SAO)
El ...Hold Harmless — (ROW)
0 .. Grease Interceptor
❑ .. Channelization
❑ .. Trench Excavation
❑ .. Utility Undergrounding
❑ ...Deduct Water Meter Size
Day Telephone:
Mailing Address:
City State Zip
Day Telephone:
City
State
Zip
Page 3 of 6
PERMIT APPLICATION NOTES Applicable to all permits in this application
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
Building and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension "shall be requested
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing Code (current edition).
Plumbing Permit
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDINGcR UTHORIZCD AGENT:
Signature: Date: 1 7/q /et 7
�� ► ,h e r'\
Print Name:
Mailing Address: 5 ,'ei a L S
Date Application Accepted:
11-111, 10
Q: ApplicationsWonns- Applications On Line \3.2006 - Permit Application.doc
Revised: 9 -2006
bh
Day Telephone:
FtMeal 149,1
City
41 C--L
State Zip
Date Application Expires: 49 / 1110-b
Staff Initials:
Page 6 of 6
Fixture Type:
Qty
Fixture Type: '
Fixture Type:
Qty `
:Fixture Type:
Qty
Bathtub or combination
bath/shower
Drinking fountain o ater
cooler (per head)
Wash fountain
Gas piping outlets
Bidet
Food -waste grin r,
commercial
Receptor, indirect
to
Clothes washer, domestic
Floor drain
I
S' s
1
Dental unit, cuspidor
Shower, si a head trap
Urin
Dishwasher, domestic,
with independent drain
Lavatory
Water oset
'
Building sewer or trailer
park sewer
Rain ter system — per
dm' inside building)
Water heat and/or
vent
1
Additional medical gas
inlets/outlets — six or more
Industrial waste
pretreatment interceptor,
including its trap and vent,
except for kitchen type
grease interceptors
R it or alteration of water
p' ng and/or water treating
uipment
Repair or alters n
of drainage or ven
piping
Medical gas piping system
serving one to five
inlets/outlets for specific gas
PLUMBING AND GAS PIPING PERMIT INFORMATION -206 - 431 -3670
PLUMBING AND GAS PIPING CONTRACTOR INFORMATION
Company Name:
Mailing Address:
City
Contact Person: Day Telephone:
E -Mail Ad•. - ss: Fax Number:
Contractor Re _'stration Number: Expiration Date;
Indicate type of plumbing fixtures and/or gas piping ou
Q:\ApplicationsTom s- Applications On Line\3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
Valuation of Plumbing • ork (contractor's bid price): $
Valuation of Gas Piping k (contractor's bid price): $ !�A'
Scope of Work (please provi m , de . iled information): 0 ' 1 V e " �1
1NGAA11 C 1c 'Tee
Building Use (per Int'1 Building Code): 1
Occupancy (per Int'l Building Code):
Utility Purveyor: Water:
being installed and the quantity below:
State
T
Zip
Sewer:
Page 5 of 6
Parcel No.: 6364200010 Permit Number: M07 -283
Address: 827 SOUTHCENTER MALL TUKW Status: APPROVED
Suite No: Applied Date: 12/19/2007
Applicant: BARE ESCENTUALS Issue Date:
Receipt No.: R08 -01848
Initials: JEM
User ID: 1165
Payee: AMERICA'S BEST HEATING
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: //www.ci.tukwila.wa.us
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 12070 230.88
ACCOUNT ITEM LIST:
Description
MECHANICAL - NONRES
RECEIPT
Account Code Current Pmts
000/322.100 230.88
Total: $230.88
Payment Amount: $230.88
Payment Date: 05/29/2008 11:53 AM
Balance: $0.00
2973 05/29 9711 TOTAL 230.88
doc: Receiot -06 Printed: 05-29 -2008
Receipt No.: R07 -02802
Initials: JEM
User ID: 1165
Payee: TECTA ASSOCIATES
ACCOUNT ITEM LIST:
Description
PLAN CHECK - NONRES
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 6364200010 Permit Number: M07 -283
Address: 827 SOUTHCENTER MALL TUKW Status: PENDING
Suite No: Applied Date: 12/19/2007
Applicant: BARE ESCENTUALS Issue Date:
TRANSACTION LIST:
Type Method Description Amount
Payment Check 2675 50.22
Account Code Current Pmts
000/345.830 50.22
Total: $50.22
Payment Amount: $50.22
Payment Date: 12/19/2007 10:23 AM
Balance: $230.88
6262 12/19 9710 TOTAL 50.22
doc: Receipt -06 Printed: 12 -19 -2007
Project: /
Type of Inspection: /-,4,1,
Address : 21 41 id q
/
Date Called:
Special Instructions:
Date Wanted: m.
'
�/6/ d P.m.
7 / /e )
Requester:
Phone No:
$T& .?5 0 :RC)
INSPECTION RECORD
Retain a copy with permit .
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Approved per applicable codes. ' Corrections required prior to approval.
COMMENTS:
Coi
Inspector:
'Date: /
REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
Project:
Project: € S (P 4�et i
s e f/
of Inction: Type 5A.4.1:10G
, 1
Address:
F Z7 j AL c-
Date Called:
Special Instructions:
Date Wanted: 7
/ 1 �lO�
!
a.m.
p.m.
Requester:
Phone No:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
PQ
P.4 - u er% Ocld r4s.S ✓)0.777
rt!< 1'4- (4c- is
Date: 7/` 6 /p
$58.00 REINSPECTION FEE R QUIRED. Prior to inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call the schedule reinspection.
'Receipt No.:
!Date:
ti
Project:
�� Es si�ch
Type of Inspection:
��y
Address:
y2 7
/14,,t4
Date Called:
Special Instructions:
Date Wanted: 7 /� /Ote
p.m.
Requester:
Phone No:
1 3
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431-
COMMENTS: Dtc
'Inspector:
INSPECTION RECORD
Retain a copy with permit
Approved per applicable codes. Corrections required prior to approval.
Date: 7—Lf
n $60.00 REIN PECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
Proj ,6$ �J /V
4 � f InsP f �/y /4,
Ad rre_si•s� 17//54((
Date Called:
Special Instructions:
Date grit,W
Requester:
P ��
2
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION g
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
ID Approved per applicable codes. Lm Corrections required prior to approval.
COMMENTS
POI C
4n - r _h t<
Inspector:
C
'Date:
$60.0 INS
ri PECTION FEE REQUIRED. Prior to inspection, fee must be
p aid 300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
(Receipt No.:
'Date:
Project:
(AIL t 5 revi ti 1 5
Type of Inspection:
gi fleati
Address:
a'7 Mari
Date Called:
Special Instructions:
Date Wanted:
5-_3- ..i
Pam
Requester:
Phone No:
2G c0 0172
1
INSPE ION NO.
INSPECTION RECORD
Retain a copy with permit
t1 0 7-?)
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Approved per applicable codes. EJ Corrections required prior to approval.
COMMENTS: J
s/ clu,r.
Inspector:
Date:
fJ $60 EINSPECTION FEE REQUIRED. Prior to inspection, fee must be
pai t 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
Project:
614 F" C-e iv$r v A- i S
Type of nspection:
c" S f'
Address:
Suite #: 6c) 7 -
. C C (v\AL (-
Contact erson:
Special Instructions:
Permits:
Phone No.:
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
INSPECTION NUMBER
IX -Approved per applicable codes.
INSPECTION RECORD
Retain a copy with permit
f I
CITY OF TUKWILA FIRE DEPARTMENT
Word/Inspection Record Form.Doc 1/13/06
env` °151
PERMIT NUMBERS
444 Andover Park East Tukwil Wa. 98188 ■•■
I I Corrections required prior to approval.
COMMENTS:
Pit
se c.ft-ift-i-
E--( l,CT(
Inspector: - Cf` I Date: 7/ f4'
n $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
T.F.D. Form F.P. 113
05 -08 -2008
BOB ROBINSON
37936 23 PL S
FEDERAL WAY WA 98003
RE: Permit Application No. M07 - 283
827 SOUTHCENTER MALL TUKW
Dear Permit Applicant:
In reviewing our current permit application files, it appears that your permit application applied for on 12/19/2007 , has not been
issued by the City of Tukwila Permit Center. Per the International Codes, Uniform Plumbing Code and/or the National Electrical
Code, every permit application not issued within 180 days from the date of application shall expire by limitation and become null and
void. Your permit application expires on 06/16/2008 .
If you choose to pursue your project, a written request for extension of your application addressed to the Building Official,
demonstrating justifiable cause, will need to be received at the Permit Center prior to your expiration date of 06/16/2008. If it is
determined that an extension is granted, your application will be extended for an additional 90 days from the expiration date.
In the event we do not receive your written request for extension, your permit application will become null and void and your project
will require a new permit application, plans and specifications, and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
xc:
fer Marshall
't Technician
Permit File No. M07 -283
City of Tukwila Jim Haggerton, Mayor
Department of Community Development Jack Pace, Director
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665
ACTIVITY NUMBER: M07 -283 DATE: 12 -19 -07
PROJECT NAME: BARE ESCENTUALS
SITE ADDRESS: 827 SOUTHCENTER MALL
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # After Permit Issued
DEPARTMENTS:
�� � (2- ( -01
Bui lding Division j
Public Works
Complete
Comments:
HERMIT COORD COPY 'ft
PLAN REVIEW /ROUTING SLIP
TUES/THURS ROUT G:
Please Route Structural Review Required
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Documents/routing slip.doc
2 -28 -02
Fire Prevention
Structural
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Incomplete n
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
n
❑ Permit Coordinator n
Planning Division
DUE DATE: 1 2-20-07
Not Applicable ❑
No further Review Required
DATE:
n
DUE DATE: 01-17 -08
Approved ❑ Approved with Conditions Not Approved (attach comments)
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Business Owner Information
Name
Role
Effective Date
Expiration Date
SWETMAN, SETH T
AGENT
09 /21/2005
SWETMAN, SETH T
PRESIDENT
09 /21/2005
Washington State Department of Labor and Industries
Electrical Contractor
A business licensed by L &I to contract electrical work within the scope of
its specialty. Electrical Contractors must maintain a surety bond or
assignment of savings account. They also must have a designated
Electrical Administrator or Master Electrician who is a member of the
firm or a full -time supervisory employee.
License Information
License
Licensee Name
Licensee Type
UBI
Ind. Ins. Account Id
Business Type
Address 1
Address 2
City
County
State
Zip
Phone
Status
Specialty 1
Specialty 2
Effective Date
Expiration Date
Suspend Date
Separation Date
Parent Company
Previous License
Next License
Associated License
AMERIBH951 O1
AMERICA'S BEST HEATING & A/C
ELECTRICAL CONTRACTOR
602527765
CORPORATION
16122 STATE ROUTE 9 SE
SNOHOMISH
SNOHOMISH
WA
98296
4253384310
ACTIVE
HVAC/RFRG LTD ENERGY
UNUSED
9/21/2005
9/21/2009
AMERIBH967L5
SWETMST962L5
Electrical Administrator Information
License
Name
Status
SWETMST962L5
SWETMAN, SETH T
ACTIVE
Bond Information
v
https: // fortress .wa.gov /lni/bbip /printer.aspx ?License= AMERIBH95101 05/29/2008
VA A STOCKROOM STOCKROM
1
GENERAL NOTES
A
800 CD AU
1 SD 2FM
FIELD VERIFY ALL CONDITIONS
DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT THE
SITE PRIOR i0 BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING
FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL LABOR AND
MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING
CONDITIONS.
THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR
OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS
OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE
DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER
OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED
AT CONTRACTORS COST.
BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL
CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE
COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH
GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT
WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER
OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING
CODES AND DESIGN INTENT.
FILE COPY
Permit No.
!rill
111
Plan review approval Is subject to erns
Approval of won documents
the violation of any adopted code or
o f a p p r o v e d • ,,.. ` and r . 1 a : , r !--,.----
By
and onVssions.
does not awe
OidillatiCe. Receipt
-' - -,. ; i- 1 1 • : . * ! • ; , a
\ *16 CONY ft'
City of Tukwila
BUILDING DIVISION
AAP
bi
RECEIVED
CITY OF TUKW ILA
DEC 19 2007
PEHMIT CENTER
ns
274719th STREET
SAN FRANCISCO, CA 94110
PH: 415 - 362 -5857
EX: 415 - 362 -5044
BARE
E SCENTUALS
71 STEVENSON STREET
22ND FLOOR
SAN FRANCISCO, CA 94105
(415) 489 -5478
THESE PLANS AND SPECIFICATIONS. AS WELL AS BARE ESCENTUALS NAME
AND LOGO, TRADEMARKS AND DESIGNS ARE THE EXCLUSIVE PROPERTY OF
BARE ESCENTUALS. ANY REPRODUCTION, MODIFICATION, DISCLOSURE
AND /OR USE OF THESE MATERIALS (OR ANY PORTION OF THEM WITHOUT
PRIOR WRITTEN CONSENT 15 STRICTLY PROHIBITED.
REV DATE DESCRIPTION
10/12/07 DD SET
12/07/07 CD SET
C. v.
S.
1 Southcenter
iter Parkway
98188 -2888
g County
f
H.C. UNISEX
'
0 %
•
• RESTROON
PROJ. NO.: 7.112
PM: A.M.
JC: A.C.
CHECKED:
•
SCALE:
(DO NOT SCALE DRAWINGS)
SHEET TITLE:
HVAC PLAN
6'0
r
10 "
J
�
' , 6
/
6X6 Cr
Fi
8X8 100 CC
CFM
SD -2
� �
50 -3
SD -3
A
KEY NOTES
01 NEW DOUBLE DUCT SIZE 12 MIXING BOX TO REMAIN
®2 MECHANICAL CONTRACTOR SHALL PROVIDE THERMOSTAT AS
INDICATED ON PLANS AT 5 FT. ABOVE FINISHED FLOOR.
V NEW EXH. FAN RUN 615 EXHAUST DUCT TO EXISTING EXHAUST DUCT.
V �, PROVIDE DUCT SMOKE DETECTOR, DUCT SMOKE DETECTOR
�/ TO SHUT DN. THE BOX UPON ACTIVATION. PROVIDE AUDOI /VISUAL DEVICE,
LOCATED IN CEILING FOR DUCT SMOKE DETECTOR.
V INSTALL 1" INTERNALLY LINED SUPPLY DUCT AS SHOWN.
RETURN AIR CEILING PLENUM.
GENERAL NOTES
ii
\
FIELD VERIFY ALL CONDITIONS
DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT THE
SITE PRIOR i0 BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING
FIELD CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL LABOR AND
MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING
CONDITIONS.
THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR
OWNER PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS
OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO MEET THE
DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER
OR OWNER AFTER BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED
AT CONTRACTORS COST.
BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL
CODES AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE
COSTS FOR ALL WORK INSTALLED IN STRICT ACCORDANCE WITH
GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT
WITHSTANDING. THE CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER
OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN GOVERNING
CODES AND DESIGN INTENT.
FILE COPY
Permit No.
!rill
111
Plan review approval Is subject to erns
Approval of won documents
the violation of any adopted code or
o f a p p r o v e d • ,,.. ` and r . 1 a : , r !--,.----
By
and onVssions.
does not awe
OidillatiCe. Receipt
-' - -,. ; i- 1 1 • : . * ! • ; , a
\ *16 CONY ft'
City of Tukwila
BUILDING DIVISION
AAP
bi
RECEIVED
CITY OF TUKW ILA
DEC 19 2007
PEHMIT CENTER
ns
F
1-
L -_ J
L -_ _�
HVAC PLAN
SCALE: 1/2" = 1
J
I -- I
I 0, I
I --
e
0
SD -1 F...
1
x-50 • CFM I
0
•
>,:a ; ;;"
1
10/
I , - •
0;1
,- 1
l 0 i
I. I
■�E ��■■■_ ■_
F °11 1111
I i Li D i I . •-
-
10 0
■
4:1`U -..
11 EEL_
' 1
SD -1
u
I -0 CFM I
1 1 0 j l I I
1 I I
SALES 10"0 I
111■■I■II hI■��1 hiiii
I 0 I 1111111/11111 �■HI oil 1
r •f • , I
Q } I 1 1011 01
I • .J
I 10I1
' -SD-1
0
50
10"d
I 1
I
0;1 VAV -1
4)
▪ Er - R =:
SD -1
250 CFIff
Q � I
I I 1 •
011 /01
SD -1 I 1
250 CFM
Q_®
1
4X24
o � 1
1-
250 CFM
_0 __ - - - -- .0 ._42
1 0 1 1
L I
1, 01
I • I •
CFM
I
0 I 1
f, o'
I 1
I !
I I
I I
1 01
I I
D ¢ -
... ..
1 I - -Q
SD -1
250 CFM
L
1 "0 - -J
1
l �J
1
2501 CFM
It_ d141C4
daeavy ah re�h�,rn t id e.
aF Iuwi p�' Mmr4tAditoW4s
IASrit1i crccs.
SEPARATE PERMIT
REQUIRED FOR:
❑ Mechanical
di.Electrical
Hi Plumbing
IGas Piping
City of Tukwila
LB`ILDII;.! G DIVISION
CODE. COMP CE
PR OVED
SAN p 20
City Of Tu \tilt
BUILDING ovi510__
ii
\
\
!rill
111
4r
/
\ *16 CONY ft'
w
ill ■ ■
associates
• ARCHITECTURE
• INTERIORS
• PLANNING
274719th STREET
SAN FRANCISCO, CA 94110
PH: 415 - 362 -5857
EX: 415 - 362 -5044
BARE
E SCENTUALS
71 STEVENSON STREET
22ND FLOOR
SAN FRANCISCO, CA 94105
(415) 489 -5478
THESE PLANS AND SPECIFICATIONS. AS WELL AS BARE ESCENTUALS NAME
AND LOGO, TRADEMARKS AND DESIGNS ARE THE EXCLUSIVE PROPERTY OF
BARE ESCENTUALS. ANY REPRODUCTION, MODIFICATION, DISCLOSURE
AND /OR USE OF THESE MATERIALS (OR ANY PORTION OF THEM WITHOUT
PRIOR WRITTEN CONSENT 15 STRICTLY PROHIBITED.
REV DATE DESCRIPTION
10/12/07 DD SET
12/07/07 CD SET
C. v.
S.
1 Southcenter
iter Parkway
98188 -2888
g County
PROJ. NO.: 7.112
PM: A.M.
JC: A.C.
CHECKED:
SCALE:
(DO NOT SCALE DRAWINGS)
SHEET TITLE:
HVAC PLAN
M
F
1-
L -_ J
L -_ _�
HVAC PLAN
SCALE: 1/2" = 1
J
I -- I
I 0, I
I --
e
0
SD -1 F...
1
x-50 • CFM I
0
•
>,:a ; ;;"
1
10/
I , - •
0;1
,- 1
l 0 i
I. I
■�E ��■■■_ ■_
F °11 1111
I i Li D i I . •-
-
10 0
■
4:1`U -..
11 EEL_
' 1
SD -1
u
I -0 CFM I
1 1 0 j l I I
1 I I
SALES 10"0 I
111■■I■II hI■��1 hiiii
I 0 I 1111111/11111 �■HI oil 1
r •f • , I
Q } I 1 1011 01
I • .J
I 10I1
' -SD-1
0
50
10"d
I 1
I
0;1 VAV -1
4)
▪ Er - R =:
SD -1
250 CFIff
Q � I
I I 1 •
011 /01
SD -1 I 1
250 CFM
Q_®
1
4X24
o � 1
1-
250 CFM
_0 __ - - - -- .0 ._42
1 0 1 1
L I
1, 01
I • I •
CFM
I
0 I 1
f, o'
I 1
I !
I I
I I
1 01
I I
D ¢ -
... ..
1 I - -Q
SD -1
250 CFM
L
1 "0 - -J
1
l �J
1
2501 CFM
It_ d141C4
daeavy ah re�h�,rn t id e.
aF Iuwi p�' Mmr4tAditoW4s
IASrit1i crccs.
SEPARATE PERMIT
REQUIRED FOR:
❑ Mechanical
di.Electrical
Hi Plumbing
IGas Piping
City of Tukwila
LB`ILDII;.! G DIVISION
CODE. COMP CE
PR OVED
SAN p 20
City Of Tu \tilt
BUILDING ovi510__
H.V.A.C. LEGEND
SYMBOL
ABBREV,
DESCRIPTION
MANUFACTURER
AND MODEL
B,D.D,
BACK DRAFT DAMPER
WEIGHT
LBS
M,BH
THOUSAND BTUH
S.P.
IN.W.G.
DUCT SECTI ❑N (SUPPLY)
f ®
HP
WATT
VOLTS
DUCT SECTI ❑N (RETURN)
r_ -1 0
AIL
w
w�� 0
CEILING
DUCT SECTION AU
EC (EXHAUST)
100
0.125
C.D.
CEILING DIFFUSER
1- Fa ->
r 4 I - N -
R,A.R.
RETURN AIR REGISTER
I4- -
E,G,/ E.R.
EXAUST GRILLE/ REGISTER
L.D.
LINEAR DIFFUSER
M.C.A.
MAX. CIRCUIT AMPACITY
T.S.P.
TOTAL STATIC PRESSURE
F.L.A.
FULL LOAD AMP
M.V.D.
MANUAL VOLUME DAMPER
A.F,D.
AUTOMATIC FIRE DAMPER
- 1D
A.V.D.
AUTOMATIC VOLUME DAMPER
I•
A.D.
ACCESS DOOR
Q
STAT
ROOM THERMOSTAT
C
REMOTE TEMP. SENSOR
u /
U.C.
UNDER -CUT
c ).
-cvs-
C.W.S.
COND. WATER SUPPLY
- cam -
C.W.R.
COND. WATER RETURN
-HVS-
H,V,S,
HOT WATER SUPPLY
-HWR-
H.W.R.
HOT WATER RETURN
- cl -ivs-
CH,W.S,
CHILLED WATER SUPPLY
- ci-sdR-
CH•W,R,
CHILLED WATER RETURN
DIRECTION OF FLOW
)
-- Da -
G.V.
GATE VALVE
Doi
G.L.V.
GLOBE VALVE
--I\)-
C.V.
CHECK VALVE
- I f I
B.V.
BUTTERFLY VALVE
A.P.
ACCESS PANEL
S.A,
SUPPLY AIR
R,A.
RETURN AIR
E,A,
EXHAUST AIR
U.T.R.
UP THRU ROOF
D.S.A.
OUTSIDE AIR
DN.
DOWN
CLG,
CEILING
N.C.
NORMALLY CLOSED
N.D.
NORMALLY OPEN
N.I.C.
NOT IN CONTRACT
P.D.C.
POINT OF CONNECTION
G.C.
GENERAL CONTRACTOR
P.C.
PLUMBING CONTRACTOR
E.C.
ELECTRICAL CONTRACTOR
Q
FURN. & INST, BY ELEC.
0
FURN, & INST, BY MECH,
EXHAUST FAN SCHEDULE
SYMBOL
SERVICE
LOCATION
MANUFACTURER
AND MODEL
FAN DATA
MOTOR DATA
WEIGHT
LBS
NOTES .
AC
CFM
S.P.
IN.W.G.
R.P.M.
DRIVE
HP
WATT
VOLTS
PHASE
HZ
AIL
w
BATHROOM
CEILING
C OOK GEM -240
100
0.125
-
DIRECT
^
6O
120
1
60
15
A -C
HANGER AND BRACE SCHEDULE
TERMINAL BOX
WEIGHT
MAX. LOAD
EACH HANGER
HANGER STRAP
SIZE
DIAGONAL BRACE
SIZE
UP TO 100#
72# /HANGER
1 1/2 "x 18 GA.
1 1/2 1/2 GA.
101 TO 225#
160# /HANGER
1 1/2 "x 16 GA.
11/n11/2%18 GA.
GENERAL NOTES:
1. CODES, RULES AND REGULATIONS- DESIGN OF SYSTEM
A) ALL WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE
WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL
LAWS, ORDINANCES AND CODES.
B) WHEN THE DRAWINGS CALL FOR MATERIALS OR
CONSTRUCTION OF A BETTER QUALITY OR LARGER
SIZES THAN REQUIRED BY THE ABOVE MENTIONED
CODES AND RULES, WORK SHALL BE AS SPECIFIED
OR SHOWN RATHER THAN AS REQUIRED BY CODE.
All ITEMS OR FEATURES OF THE MECHANICAL
SYSTEMS REQUIRED BY CODE SHALL BE INCLUDED,
EVEN THOUGH NOT SPECIFIED HERON,
C) INSTALLATION OF THE SYSTEMS SHALL BE IN ACCORDANCE
WITH THE ABOVE MENTIONED CODES AND REGULATIONS AND
ALSO SHALL CONFORM TO GOOD, ACCEPTED MECHANICAL
PRACTICES.
2. FLEXIBLE CONNECTIONS AT SUPPLY AND RETURN AIR OPENINGS OF
ALL AIR CONDITIONING UNITS.
3. FLEXIBLE DUCTS TO BE GLASS -FLEX 5' -0 ", MAXIMUM IN LENGTH,
WHERE APPLICABLE.
4. PLUMBING CONTRACTOR TO FURNISH & INSTALL ALL CONDENSATE
PIPING, INCLUDING FINAL CONNECTIONS.
5. CEIUNG DIFFUSERS TO BE EQUAL TO TITUS SERIES FL15 UNEAR
DIFFUSER & PDS W/ O.B.D.
6. RETURN AND EXHAUST REGISTERS TO BE EQUAL TO TITUS 50F.
7. COORDINATE EXACT LOCATION OF ALL AIR OUTLETS AND INLETS
(DIFFUSERS AND REGISTERS) WITH APPROPRIATE ARCHITECTURAL
PLANS REFLECTED CEIUNG, ELEVATIONS,ETC.) COLOR AS
DIRECED BY ARCHITECT.
8. PROVIDE DUCT LINING TO SUPPLY DUCT OF EACH AC UNIT FOR
MINIMUM OF 10 FT. DUCT LINING TO BE EQUAL TO JOHNS - MANVILLE,
1" THICK x 1-1/ PCF DENSITY DUCT LINER. DUCTWORK TO BE
INCREASED IN EACH DIMENSION TO INCORPORATE THICKNESS OF
LINING,
9. DUCT INSULATION TO CONFORM TO LOCAL ENERGY
CONSERVATION STANDARD CODES.
10. WIRING DIAGRAM I5 INTENDED TO INDICATE SEQUENCE OF
CONTROL AND DOES NOT NECESSARILY SHOW ALL CONNECTIONS
REQUIRED BY LOCAL CODES.
11. AUTOMATIC TEMPERATURE CONTROL DEVICE FOR REGULATION OF
SPACE TEMPERATURE SHALL BE CAPABLE OF BEING SET FROM 55
TO 857, AND HAVE THE ABIUTY TO OPERATE THE HEALING
AND COOUNC IN SEQUENCE. CONTROL SHALL BE ADJUSTABLE
TO PROVIDE A RANGE OF UP TO 107 BETWEEN FULL HEATING
AND FULL COOLING AND HAVE CAPABILITY OF TERMINATING ALL
HEATING AT A TEMPERATURE NO MORE THAN 707, AND COOLING
AT A TEMPERATURE NOT LESS THAN 787.
T'STATS TO BE HONEYWELL T7300A PROGRAMMABLE COMMERCIAL
TSTAT WITH APPROPRIATE 07300 SUB -BASE.
12. ROOF MOUNTED EQUIPMENT SHALL BE LABFIFD AS TO THE SPACE
IT SERVES.
13. APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE
FASTENED IN PLACE.
14. PROVIDE SEISMIC BRACING FOR ALL MECHANICAL EQUIPMENT
STRUCTURE MOUNTED, 400 LBS. OR HEAVIER.
15. A MAINTENANCE LABEL SHALL BE AFFIXED TO MECHANICAL
EQUIPMENT AND A MAINTENANCE MANUAL SHALL BE PROVIDED
FOR THE OWNERS USE.
16. CONCEALED BUILDING SPACES USED AS RETURN AIR PLENUMS
SHALL BE OF NON- COMBUSTIBLE MATERIAL
17. PROVIDE ACCESS PANEL FOR ALL CEIUNG MOUNTED EQUIPMENT
& VOLUME DAMPERS.
18. TRANSVERSE JOINTS FOR ALL AIR SUPPLY DUCTS INSTALLED
WHERE AIR LEAKAGE WOULD BE NON - BENEFICIAL TO THE
OCCUPIED AREA TEMPERATURE REQUIREMENTS SHALL BE SEALED
WITH APPROVED MASTIC OR TAPE.
19. PROVIDE GALVANIZED SHEET METAL DUCTS FABRICATED AND
INSTALLED TO ASHRAE AND SMACNA STANDARDS OR THE
REQUIREMENTS OF GOVERNMENTAL AGENCIES HAVING
JURISDICTION WHOSE STANDARDS ARE MORE STRINGENT.
(UMC CHAPTER 6 OF 2003)
20. DUCTWORK CONSTRUCTION DETAILS:
A. METARIAL• CAL SHEET METAL GAGE 26 FOR UP TO 14% & GAGE 24
FOR UP TO 23 "0 DUCT.
B. SUPPORT: UP TO 10 ° 0 DUCT SAME GAGE AS GAL. STEEL DUCT, 1" WIDE
OR (NO. 18 GAGE GAL STEEL WIRE) ON 10 FT. CRNTERS,
AND UP TO 40 ° 0 DUCT SAME GAGE AS GAL. STEEL DUCT, 1 WIDE
OR (NO. 8 GAGE GAL. STEEL WIRE) TIED TO 1" GAL SILLL BAND
AROUND DUCT ON 10 FT. CRNTERS.
C. HANGER: UP TO 360 DUCT 1/4" ROUND ROD OR 1' X 1" X 1 /8"
ANGLE,
20. PROVIDE FIRE DAMPER WHERE DUCT PENETRATES FIRE RATED
CEIUNG OR WALL IF APPUCABLE, PER LOCAL BUILDING CODE,
BE OF APPROVED CONSTRUCTION AND HAVE PERMANENT I.D.
AND ACCESS.
21. DUCT SIZES SHOWN ARE NET SIZED REQUIRED. INCREASE SIZES FOR
THE LINED DUCT AS REQUIRED.
22. THE PROJECT SHALL BE AIR BALANCED AND A COPY OF THE
FINAL REPORT S-IALL BE PRESENTED TO B.E. PROJECT
MANAGER.
23. THE MECHANICAL CONTRACTOR SHALL SECURE AND PAY FOR ALL
REQUIRED PERMITS AND FEES.
24. MECHANICAL CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO
BID AND VERIFY EXISTING LOCATION OF ALL EQUIPMENT AND
THEIR WORKING CONDITION PRIOR TO WORK. ANY DISCREPANCY
SHALL BE REPORTED TO ARCHITECT.
25. GENERAL CONTRACTOR 15 RESPONSIBLE FOR DETERMINING THE
ADEQUACY OF THE STRUCTURE TO SUPPORT THE EQUIPMENT
SPECIFIED.
26. GENERAL CONTRACTOR TO PROVIDE WEATHERPROOF EQUIPMENT
AT LOCATIONS AGREED UPON IN CONSULTATION WITH H.V.A.C.
CONTRACTOR.
27. ALL ROOF PENETRATIONS TO BE WEATHERPROOF.
28. EACH SINGLE SYSTEM PROVIDING HEATING OR COCUNG AIR IN
EXCESS OF 2000 CFM SHALL BE EQUIPPED WITH AN AUTOMATIC
SHUT -OFF. THE SMOKE DETECTOR SHALL BE INSTALLED IN THE MAIN
SUPPLY AIR DUCT DOWNSTREAM OF THE FILTERS OR THEY
MAY BE INSTALLED IN EACH ROOM OR SPACE SERVED BY THE
SUPPLY AIR DUCT. D CTOpS SHALL ALSO BE INSTALLED IN THE
MAIN RETURN DUCT (IFF REQ D. BY THE LOCAL CODE) AHEAD OF
OSA INTAKE. SEE CODE FOR EXEMPTIONS AND LOCAL AUTHORITY
FOR CODE INTERPRETATION, OR AS INDICATED ON PLAN.
29. AIR CONDITIONING CONTRACTOR TO REMOVE AND DISPOSE OF ALL
EXISTING EQUIPMENT AND DUCTWORK THAT ARE NOT USED.
NOTE /ACCESSORY DESIGNATION:
A - PROVIDE BACKDRAFT DAMPER
B - SAFETY DISC. SWITCH
C - INTERLOCK WITH LIGHT SWITCHD
GRILLE, REGISTER, AND
DIFFUSER SCHE
DULE
TAG
SD -1
SD -2
SD -3
RG -1
RG -2
SERVICE
AIR SUPPLY
AIR SUPPLY
AIR SUPPLY
AIR RETURN
AIR RETURN
MAKE
TITUS
TITUS
TITUS
TITUS
TITUS
MODEL
FL15
TMS
MCD
50 -F
50 -F
TYPE
BORDER TYPE/
HARD OR LAY -IN
BORDER TYPE/
HARD OR LAY -IN
BORDER TYPE/
HARD OR LAY -IN
BORDER TYPE/
HARD OR LAY -IN
BORDER TYPE/
HARD OR LAY -IN
NECK SIZE
& CFM
SEE DWG.
SEE DWG.
SEE DWG.
SEE DWG.
SEE DWG.
FACE E
XW")
4' -0 ", 1 SLOT/
2" SLOT WIDE
24" x 24"
24" x 24"
24" x 12"
FINISH
STANDARD
WHITE
WHITE
WHITE
WHITE
TYPE
1
1
1
1
1
NOTES
ACCESS.
A
B
B
B
B
NOTE /ACCESSORY DESIGNATION:
A - FRAM TYPE 22, PROVIDE FBPI -20 INSULATED
B - FRAM TYPE 3
HVAC SPECIFICATION
GENERAL•
General Provisions of the Contract including General and Supplementary Conditions and General Requirements
apply to work of this section.
SCOPE_
The base bid includes furnishing all materials, labor, tools, and equipment and the performance of all work
required to install a complete heating and air conditioning system as outlined herein.
QUALITY ASSURANCE :
Provide a complete installation in conformance with the following standards.
AGA American Gas Association
ASHRAE American Society of Heating, Refrigerating and Air Conditioning Engineers
NFPA National Fire Protection Association
SMACNA Sheet Metal and Air Conditioning Contractors National Association.
Commonwealth of STATE Uniform Statewide Building Code
Indiana Mechanical Code
WORK IN EXISTING SPACES :
General: Care shall be taken when working in existing spaces so as not to damage existing walls and ceilings
where work is being performed.
Ceilings: Where work is being performed above ceilings, and the architectural drawings do not indicate ceiling
modifications by the general contractor, it shall be the responsibility of this contractor to remove and replace
existing ceilings where work is being performed. In those instances, all repair and installation of new grid,
ceiling panels, etc shall be the responsibility of this contractor. Match existing finishes.
Walls & Floors: It shall be the responsibility of this contractor to patch existing walls and floors and match
existing finishes where work is being removed or installed and patching is being performed, unless noted
otherwise an the architectural drawings.
TESTS AND ADJUSTMENTS :
No ducts, piping, fixtures or equipment shall be concealed or covered until they have been inspected and
approved by the Architect and the inspector who shall be notified by the contractor when the work is ready for
inspection.
Work shall be completely installed, tested and leak tight before inspection is required. All tests shall be
repeated to the satisfaction of those making the inspection.
EXECUTION
INSTALLATION OF METAL DUCTWORK
General: Assemble and install ductwork in accordance with recognized industry practices which will achieve
air - tight (5 %' leakage for systems rated 3" and under, 1 % for systems rated over 3 ") and noiseless (no
objectionable noise) systems, capable of performing each indicated service. Install each run with minimum
number of joints. Align ductwork accurately at connections, within 1/8" misalignment tolerance and with
internal surfaces smooth. Support ducts rigidly with suitable ties, braces, hangers and anchors of type which
will hold ducts true -to- -shape and to prevent buckling. Support vertical ducts at every floor.
Sealing: Seal all longitudinal seams, S's and drives and all joints with mastic or cement. Install according to
SMACNA standards.
Balancing Dampers: The sheet metal contractor shall be fully responsible for installing balancing dampers in the
ductwork, (whether shown on the drawing or not) in order to arrive at the intended air flow. The balancing
sub- contractor shall provide direction and assistance in determining locations where dampers are required.
Additional dampers, if required shall be installed at no additional cost to the owner.
Wall Penetrations: Seal and pack around all ducts and piping sleeves which pass through walls that extend to
bottom side of structure and rated walls.
Field Fabrication: Complete fabrication of work at project as necessary to match shop - fabricated work and
accommodate installation requirements.
Routing: Locate ductwork runs, except as otherwise indicated, vertically and horizontally and avoid diagonal
runs wherever possible. Run ductwork in shortest route which does not obstruct useable space or block access
for servicing building and its equipment. Hold ducts close to walls, overhead construction, columns, and other
structural and permanent enclosure elements of building. Limit clearance to 1/2" where furring is shown for
enclosure or concealment of ducts, but allow for insulation thickness, if any. Where possible, locate insulated
ductwork for 1" clearance outside of insulation. Wherever possible in finished and occupied spaces, conceal
ductwork from view, by locating in mechanical shafts, hollow wall construction or above suspended ceilings. Do
not encase horizontal runs in solid partitions, except as specifically shown. Coordinate layout with suspended
ceiling and lighting layouts and similar finished work.
Electrical Equipment Spaces: Do not route ductwork through transformer vaults and their electrical equipment
spaces and enclosures.
Penetrations: Where ducts pass through interior partitions and exterior walls, and are exposed to view, conceal
space between construction opening and duct or duct insulation with sheet metal flanges of same gage as
duct Overlap opening on 4 sides by at least 1 - 1/2 ". Fasten to duct and substrate.
Where ducts pass through fire-rated floors, walls, or partitions, provide fire dampers and firestopping between
duct and substrate, in accordance with requirements of Division -7 Section ° Firestopping ° .
Coordination: Coordinate duct installations with installation of accessories, dampers, coil frames, equipment,
controls and other associated work of ductwork system.
INSTALLATION OF DUCT LINER
General: Install duct liner in accordance with SMACNA HVAC Duct Construction Standards. Size of ductwork
shown on the drawings is free net area, outside dimension of ducts will need to be increased if lined duct is
Store internally lined ductwork up off of the floor. Protect internally lined ductwork from water and dust.
"Butter the leading edge of all internal duct lining with the manufacturer's recommended adhesive.
Inspect and repair all damaged lining prior to installation of ductwork.
INSTALLATION OF FLEXIBLE DUCTS
Maximum Length: For any duct run using flexible ductwork, do not exceed 5 - 0" extended length.
Installation shall have smooth full radius turns down to diffuser.
Installation not permitted above inaccessible ceilings.
ACCESS PANELS
Furnish all access panels required for proper servicing of equipment. Provide access panels for all concealed
valves vents, controls and c out doors, and devices required tro lean or sprinkler vices re eel b NFP Provide frame as required for
p q by A_ from require r
finish. Furnish panels to Gen Contractor. Exact locations approved p els General actor. ct lac s to be pproved by the Architect. Minimum size to
be 12" x 12', units to be 16 gauge steel, locking device shall be screwdriver cam locks.
HANGERS AND SUPPORTS
Support all piping, ductwork and equipment by hangers or brackets. Fumish structural steel members where
required to support piping and equipment No portion of piping or valves shall be supported by equipment.
Ductwork - Support by means of hangers as follows:
Duct Width Hanger Size and Type Max. Spacing
60 or less 1 "x.109" (#12 gage) 8
61 to 90 3/8" dia. Rod 8
A pair of hangers shall be located at every transverse joint and elsewhere according to the table.
SEQUENCE OF OPERATION :
HVAC UNIT : During occupied hours, supply fan shall operate continuously, and the outside air
damper shall be open to the minimum position. Condensing unit shall cycle to maintain the required
temperature set point. During unoccupied hours the outside air damper shall be closed and the supply
fan and condensing unit shall maintain the space set point.
A differential enthalpy controlled economizer shall activate whenever the outside air enthalpy is lower than
the enthalpy control setting. Economizer dampers shall modulate to full open position, as required, to
maintain discharge air temperature between 52 and 56 degrees fahrenheit When the space temperature
set point is satisfied, the damper shall return to the minimum outside air position during occupied mode
and close completely during unoccupied mode.
Upon a signal from the duct smoke detectors or zone fire alarm system, units shall shut dawn and
outside air damper shall close.
Exhaust Fans
Toilet Exhaust Fans (Manual)
Exhaust fans shall be controlled by local manual switch furnished, installed and wired by electrical
contractor. When activated, exhaust fon motor damper shall open and fan shall start
(Indicated by EC an MESCH schedule)
Specialty Controls
CONTROL WIRING
Low Voltage Thermostats
Low voltage thermostats shall be furnished, installed and wired by the HVAC contractor. The electrical
contractor shall provide 4" square x 1- W" deep wall outlet boxes at 60" above finished floor (with
single -gang rings) for all thermostats /sensors. The electrical contractor shall provide one 3/4° empty
conduit from each thermostat /sensor location, tumed out above accessible ceilings (in joist space or
against overhead slab /deck). The HVAC /Temperature Control Contractor shall provide all other necessary
conduit, raceway and wiring related wo Conduit shall be identified in ceiling cavity and shall be
provided with sweep bends, bushings and dragline.
Line Voltage Thermostats
General Control Wiring Requirements and Installation Methods
Except where specifically indicated otherwise above, the HVAC /Temperature Control Contractor shall
provide all electrical work as required for all temperature control related wiring (i.e. conduit, raceway,
outlet boxes, junction boxes, wiring, etc.) in accordance with Division 16 requirements. All conduit shall
be 3/4" minimum.
CONTROLS:
Electrical contractor will provide power wiring. HVAC contractor shall provide all the low voltage wiring of
HVAC units and controls, thermostats and controllers. Thermostat shall be by the manufacturer of the
HVAC unit (heat /coal /auto /off) with night setback. Provide plastic protective cover far all thermostats.
Replace controls on existing unit, adjust and calibrate controls.
GUARANTEE
The contractor shall provide a guarantee in written form stating that all work under this section shall be
free of defective work, materials, or parts for a period of one year from the date of owner's final
acceptance and shall repair, revise or replace at no cost to the owner any such defects occurring within
the guarantee period. Contractor shall also state in written form that any items or occurrences arising
during the guarantee period will be attended to in a timely manner and will in no case exceed four (4)
working days from date of notification by owner.
FOR ADDITIONAL MALL REQUIREMENTS, SEE MALL DESIGN AND CONSTRUCTION CRITERIA.
VAV UNIT SCHEDULE
TAG
VAV -1
QUNT.
1
NOMINAL
CFM
2600
TYPE
SINGLE
DUCT
MAKE & MODEL
KRUEGER
LMHS
ELECTRICAL
VOLTS
N/A
PHASE
N/A
HZ
N/A
MCA
N/A
MOCP
N/A
COOLING
CAPACITY
(BTU)
HEATING
CAPACITY
(KW)
SUPPLY
AIR
CFM
ESP
INCH
MIN
AIR
CFM
1300
SEER
OR
EER
WT.
LBS
PRESSURE INDEPENDANT WITH DIGITAL CONTROL
PLENUM - INSULATED FOR SUPPLY
EXHAUST -NOT INSULATED
ACOUSTICAL LINING
NOT TO SCALE
as
DUCT COLLAR
CEILING
FLEXIBLE DUCT
(MAX. 5' -0 ".)
LINEAR DIFFUSER CONNECTION DETAIL
REVIEWED FOR
CODE COMPLIANC
APPROVED
2 2008
City Of Tukwila
E. ILDING DIVISION
GALVANIZED STEEL HANGE
STRAP- MIN. (4) PER
MIXING BOX- SEE
SCHEDULE FOR SIZE.
FOLD STRAP FOR DOUBLE
THICKNESS- TYPICAL FOR
ALL HANGER STRAPS.
AIR TER
NOT TO SCALE
DRAWING LIST
M -1
M -2
MECHANICAL CEIUNG PLAN
MECHANICAL NOTES AND SCHEDULES & DETAILS
SECURE TO CONCRETE
STRUCTURE WITH 3/8" DIA.
REDHEAD- TYPICAL EACH
HANGER, STRAP OR BRACE
MDR -283
IAGONAL BRACE
TYPICAL -SEE
SCHEDULE FOR SIZE
(2) EACH SIDE.
VIINAL BOX MOU \TING DETAIL
RECE
CITY OFT
DEC 1
PERMIT C
VED
u KVI
2007
ENTE
ff
r ,....,
i
Ir d i
•
„lid
,. _
•
•
•
INTERIORS
\ ri,
. .ii
L 41i
____...iLi........._
associates
ARCHITECTURE
PLANNING
274719Th STREET
SAN FRANCISCO, CA 94110
PH: 415 - 362 -5857
FX: 415- 362 -5044
BARE
ESCENTUALS
71 STEVENSON STREET
22ND FLOOR
SAN FRANCISCO, CA 94105
(415) 489 -5478
THESE PLANS MD SPECIFICATIONS, M WELL AS BARE ESCENTUALS NAME
AND LOGO, TRADEMARKS AND DESIGNS ME THE EXCLUSIVE PROPERTY OF
BARE ESCENTUALS, ANY REPRODUCTION, MODIFICATION, DISCLOSURE
AND /OR USE DF THESE MATERIALS (OR ANY PORTION OF THEMI WITHOUT
PRIOR WRITTEN CONSENT IS STRICTLY PROHIBITED
REV
DATE
DESCRIPTION
10/12/07 DD SET
12/07/07 CD SET
C. V.
t" 1. 11A89/44,.
' Y . .--
Al blike.a 4
�
41814111, O ti•
- 3SCEN'
Meld Soutl
ithcenter Park
, WA 98188 -2
& King Count
PROJ. NO.: 7.112
PM: A.M.
JC: A.C.
CHECKED:
SCALE:
(DO NOT SCALE DRAWINGS)
SHEET TITLE:
MECHANICAL
NOTES DETAILS
& SCHEDULE
ILA NA -2
:R
GENERAL NOTES:
1. CODES, RULES AND REGULATIONS- DESIGN OF SYSTEM
A) ALL WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE
WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL
LAWS, ORDINANCES AND CODES.
B) WHEN THE DRAWINGS CALL FOR MATERIALS OR
CONSTRUCTION OF A BETTER QUALITY OR LARGER
SIZES THAN REQUIRED BY THE ABOVE MENTIONED
CODES AND RULES, WORK SHALL BE AS SPECIFIED
OR SHOWN RATHER THAN AS REQUIRED BY CODE.
All ITEMS OR FEATURES OF THE MECHANICAL
SYSTEMS REQUIRED BY CODE SHALL BE INCLUDED,
EVEN THOUGH NOT SPECIFIED HERON,
C) INSTALLATION OF THE SYSTEMS SHALL BE IN ACCORDANCE
WITH THE ABOVE MENTIONED CODES AND REGULATIONS AND
ALSO SHALL CONFORM TO GOOD, ACCEPTED MECHANICAL
PRACTICES.
2. FLEXIBLE CONNECTIONS AT SUPPLY AND RETURN AIR OPENINGS OF
ALL AIR CONDITIONING UNITS.
3. FLEXIBLE DUCTS TO BE GLASS -FLEX 5' -0 ", MAXIMUM IN LENGTH,
WHERE APPLICABLE.
4. PLUMBING CONTRACTOR TO FURNISH & INSTALL ALL CONDENSATE
PIPING, INCLUDING FINAL CONNECTIONS.
5. CEIUNG DIFFUSERS TO BE EQUAL TO TITUS SERIES FL15 UNEAR
DIFFUSER & PDS W/ O.B.D.
6. RETURN AND EXHAUST REGISTERS TO BE EQUAL TO TITUS 50F.
7. COORDINATE EXACT LOCATION OF ALL AIR OUTLETS AND INLETS
(DIFFUSERS AND REGISTERS) WITH APPROPRIATE ARCHITECTURAL
PLANS REFLECTED CEIUNG, ELEVATIONS,ETC.) COLOR AS
DIRECED BY ARCHITECT.
8. PROVIDE DUCT LINING TO SUPPLY DUCT OF EACH AC UNIT FOR
MINIMUM OF 10 FT. DUCT LINING TO BE EQUAL TO JOHNS - MANVILLE,
1" THICK x 1-1/ PCF DENSITY DUCT LINER. DUCTWORK TO BE
INCREASED IN EACH DIMENSION TO INCORPORATE THICKNESS OF
LINING,
9. DUCT INSULATION TO CONFORM TO LOCAL ENERGY
CONSERVATION STANDARD CODES.
10. WIRING DIAGRAM I5 INTENDED TO INDICATE SEQUENCE OF
CONTROL AND DOES NOT NECESSARILY SHOW ALL CONNECTIONS
REQUIRED BY LOCAL CODES.
11. AUTOMATIC TEMPERATURE CONTROL DEVICE FOR REGULATION OF
SPACE TEMPERATURE SHALL BE CAPABLE OF BEING SET FROM 55
TO 857, AND HAVE THE ABIUTY TO OPERATE THE HEALING
AND COOUNC IN SEQUENCE. CONTROL SHALL BE ADJUSTABLE
TO PROVIDE A RANGE OF UP TO 107 BETWEEN FULL HEATING
AND FULL COOLING AND HAVE CAPABILITY OF TERMINATING ALL
HEATING AT A TEMPERATURE NO MORE THAN 707, AND COOLING
AT A TEMPERATURE NOT LESS THAN 787.
T'STATS TO BE HONEYWELL T7300A PROGRAMMABLE COMMERCIAL
TSTAT WITH APPROPRIATE 07300 SUB -BASE.
12. ROOF MOUNTED EQUIPMENT SHALL BE LABFIFD AS TO THE SPACE
IT SERVES.
13. APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE
FASTENED IN PLACE.
14. PROVIDE SEISMIC BRACING FOR ALL MECHANICAL EQUIPMENT
STRUCTURE MOUNTED, 400 LBS. OR HEAVIER.
15. A MAINTENANCE LABEL SHALL BE AFFIXED TO MECHANICAL
EQUIPMENT AND A MAINTENANCE MANUAL SHALL BE PROVIDED
FOR THE OWNERS USE.
16. CONCEALED BUILDING SPACES USED AS RETURN AIR PLENUMS
SHALL BE OF NON- COMBUSTIBLE MATERIAL
17. PROVIDE ACCESS PANEL FOR ALL CEIUNG MOUNTED EQUIPMENT
& VOLUME DAMPERS.
18. TRANSVERSE JOINTS FOR ALL AIR SUPPLY DUCTS INSTALLED
WHERE AIR LEAKAGE WOULD BE NON - BENEFICIAL TO THE
OCCUPIED AREA TEMPERATURE REQUIREMENTS SHALL BE SEALED
WITH APPROVED MASTIC OR TAPE.
19. PROVIDE GALVANIZED SHEET METAL DUCTS FABRICATED AND
INSTALLED TO ASHRAE AND SMACNA STANDARDS OR THE
REQUIREMENTS OF GOVERNMENTAL AGENCIES HAVING
JURISDICTION WHOSE STANDARDS ARE MORE STRINGENT.
(UMC CHAPTER 6 OF 2003)
20. DUCTWORK CONSTRUCTION DETAILS:
A. METARIAL• CAL SHEET METAL GAGE 26 FOR UP TO 14% & GAGE 24
FOR UP TO 23 "0 DUCT.
B. SUPPORT: UP TO 10 ° 0 DUCT SAME GAGE AS GAL. STEEL DUCT, 1" WIDE
OR (NO. 18 GAGE GAL STEEL WIRE) ON 10 FT. CRNTERS,
AND UP TO 40 ° 0 DUCT SAME GAGE AS GAL. STEEL DUCT, 1 WIDE
OR (NO. 8 GAGE GAL. STEEL WIRE) TIED TO 1" GAL SILLL BAND
AROUND DUCT ON 10 FT. CRNTERS.
C. HANGER: UP TO 360 DUCT 1/4" ROUND ROD OR 1' X 1" X 1 /8"
ANGLE,
20. PROVIDE FIRE DAMPER WHERE DUCT PENETRATES FIRE RATED
CEIUNG OR WALL IF APPUCABLE, PER LOCAL BUILDING CODE,
BE OF APPROVED CONSTRUCTION AND HAVE PERMANENT I.D.
AND ACCESS.
21. DUCT SIZES SHOWN ARE NET SIZED REQUIRED. INCREASE SIZES FOR
THE LINED DUCT AS REQUIRED.
22. THE PROJECT SHALL BE AIR BALANCED AND A COPY OF THE
FINAL REPORT S-IALL BE PRESENTED TO B.E. PROJECT
MANAGER.
23. THE MECHANICAL CONTRACTOR SHALL SECURE AND PAY FOR ALL
REQUIRED PERMITS AND FEES.
24. MECHANICAL CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO
BID AND VERIFY EXISTING LOCATION OF ALL EQUIPMENT AND
THEIR WORKING CONDITION PRIOR TO WORK. ANY DISCREPANCY
SHALL BE REPORTED TO ARCHITECT.
25. GENERAL CONTRACTOR 15 RESPONSIBLE FOR DETERMINING THE
ADEQUACY OF THE STRUCTURE TO SUPPORT THE EQUIPMENT
SPECIFIED.
26. GENERAL CONTRACTOR TO PROVIDE WEATHERPROOF EQUIPMENT
AT LOCATIONS AGREED UPON IN CONSULTATION WITH H.V.A.C.
CONTRACTOR.
27. ALL ROOF PENETRATIONS TO BE WEATHERPROOF.
28. EACH SINGLE SYSTEM PROVIDING HEATING OR COCUNG AIR IN
EXCESS OF 2000 CFM SHALL BE EQUIPPED WITH AN AUTOMATIC
SHUT -OFF. THE SMOKE DETECTOR SHALL BE INSTALLED IN THE MAIN
SUPPLY AIR DUCT DOWNSTREAM OF THE FILTERS OR THEY
MAY BE INSTALLED IN EACH ROOM OR SPACE SERVED BY THE
SUPPLY AIR DUCT. D CTOpS SHALL ALSO BE INSTALLED IN THE
MAIN RETURN DUCT (IFF REQ D. BY THE LOCAL CODE) AHEAD OF
OSA INTAKE. SEE CODE FOR EXEMPTIONS AND LOCAL AUTHORITY
FOR CODE INTERPRETATION, OR AS INDICATED ON PLAN.
29. AIR CONDITIONING CONTRACTOR TO REMOVE AND DISPOSE OF ALL
EXISTING EQUIPMENT AND DUCTWORK THAT ARE NOT USED.
NOTE /ACCESSORY DESIGNATION:
A - PROVIDE BACKDRAFT DAMPER
B - SAFETY DISC. SWITCH
C - INTERLOCK WITH LIGHT SWITCHD
GRILLE, REGISTER, AND
DIFFUSER SCHE
DULE
TAG
SD -1
SD -2
SD -3
RG -1
RG -2
SERVICE
AIR SUPPLY
AIR SUPPLY
AIR SUPPLY
AIR RETURN
AIR RETURN
MAKE
TITUS
TITUS
TITUS
TITUS
TITUS
MODEL
FL15
TMS
MCD
50 -F
50 -F
TYPE
BORDER TYPE/
HARD OR LAY -IN
BORDER TYPE/
HARD OR LAY -IN
BORDER TYPE/
HARD OR LAY -IN
BORDER TYPE/
HARD OR LAY -IN
BORDER TYPE/
HARD OR LAY -IN
NECK SIZE
& CFM
SEE DWG.
SEE DWG.
SEE DWG.
SEE DWG.
SEE DWG.
FACE E
XW")
4' -0 ", 1 SLOT/
2" SLOT WIDE
24" x 24"
24" x 24"
24" x 12"
FINISH
STANDARD
WHITE
WHITE
WHITE
WHITE
TYPE
1
1
1
1
1
NOTES
ACCESS.
A
B
B
B
B
NOTE /ACCESSORY DESIGNATION:
A - FRAM TYPE 22, PROVIDE FBPI -20 INSULATED
B - FRAM TYPE 3
HVAC SPECIFICATION
GENERAL•
General Provisions of the Contract including General and Supplementary Conditions and General Requirements
apply to work of this section.
SCOPE_
The base bid includes furnishing all materials, labor, tools, and equipment and the performance of all work
required to install a complete heating and air conditioning system as outlined herein.
QUALITY ASSURANCE :
Provide a complete installation in conformance with the following standards.
AGA American Gas Association
ASHRAE American Society of Heating, Refrigerating and Air Conditioning Engineers
NFPA National Fire Protection Association
SMACNA Sheet Metal and Air Conditioning Contractors National Association.
Commonwealth of STATE Uniform Statewide Building Code
Indiana Mechanical Code
WORK IN EXISTING SPACES :
General: Care shall be taken when working in existing spaces so as not to damage existing walls and ceilings
where work is being performed.
Ceilings: Where work is being performed above ceilings, and the architectural drawings do not indicate ceiling
modifications by the general contractor, it shall be the responsibility of this contractor to remove and replace
existing ceilings where work is being performed. In those instances, all repair and installation of new grid,
ceiling panels, etc shall be the responsibility of this contractor. Match existing finishes.
Walls & Floors: It shall be the responsibility of this contractor to patch existing walls and floors and match
existing finishes where work is being removed or installed and patching is being performed, unless noted
otherwise an the architectural drawings.
TESTS AND ADJUSTMENTS :
No ducts, piping, fixtures or equipment shall be concealed or covered until they have been inspected and
approved by the Architect and the inspector who shall be notified by the contractor when the work is ready for
inspection.
Work shall be completely installed, tested and leak tight before inspection is required. All tests shall be
repeated to the satisfaction of those making the inspection.
EXECUTION
INSTALLATION OF METAL DUCTWORK
General: Assemble and install ductwork in accordance with recognized industry practices which will achieve
air - tight (5 %' leakage for systems rated 3" and under, 1 % for systems rated over 3 ") and noiseless (no
objectionable noise) systems, capable of performing each indicated service. Install each run with minimum
number of joints. Align ductwork accurately at connections, within 1/8" misalignment tolerance and with
internal surfaces smooth. Support ducts rigidly with suitable ties, braces, hangers and anchors of type which
will hold ducts true -to- -shape and to prevent buckling. Support vertical ducts at every floor.
Sealing: Seal all longitudinal seams, S's and drives and all joints with mastic or cement. Install according to
SMACNA standards.
Balancing Dampers: The sheet metal contractor shall be fully responsible for installing balancing dampers in the
ductwork, (whether shown on the drawing or not) in order to arrive at the intended air flow. The balancing
sub- contractor shall provide direction and assistance in determining locations where dampers are required.
Additional dampers, if required shall be installed at no additional cost to the owner.
Wall Penetrations: Seal and pack around all ducts and piping sleeves which pass through walls that extend to
bottom side of structure and rated walls.
Field Fabrication: Complete fabrication of work at project as necessary to match shop - fabricated work and
accommodate installation requirements.
Routing: Locate ductwork runs, except as otherwise indicated, vertically and horizontally and avoid diagonal
runs wherever possible. Run ductwork in shortest route which does not obstruct useable space or block access
for servicing building and its equipment. Hold ducts close to walls, overhead construction, columns, and other
structural and permanent enclosure elements of building. Limit clearance to 1/2" where furring is shown for
enclosure or concealment of ducts, but allow for insulation thickness, if any. Where possible, locate insulated
ductwork for 1" clearance outside of insulation. Wherever possible in finished and occupied spaces, conceal
ductwork from view, by locating in mechanical shafts, hollow wall construction or above suspended ceilings. Do
not encase horizontal runs in solid partitions, except as specifically shown. Coordinate layout with suspended
ceiling and lighting layouts and similar finished work.
Electrical Equipment Spaces: Do not route ductwork through transformer vaults and their electrical equipment
spaces and enclosures.
Penetrations: Where ducts pass through interior partitions and exterior walls, and are exposed to view, conceal
space between construction opening and duct or duct insulation with sheet metal flanges of same gage as
duct Overlap opening on 4 sides by at least 1 - 1/2 ". Fasten to duct and substrate.
Where ducts pass through fire-rated floors, walls, or partitions, provide fire dampers and firestopping between
duct and substrate, in accordance with requirements of Division -7 Section ° Firestopping ° .
Coordination: Coordinate duct installations with installation of accessories, dampers, coil frames, equipment,
controls and other associated work of ductwork system.
INSTALLATION OF DUCT LINER
General: Install duct liner in accordance with SMACNA HVAC Duct Construction Standards. Size of ductwork
shown on the drawings is free net area, outside dimension of ducts will need to be increased if lined duct is
Store internally lined ductwork up off of the floor. Protect internally lined ductwork from water and dust.
"Butter the leading edge of all internal duct lining with the manufacturer's recommended adhesive.
Inspect and repair all damaged lining prior to installation of ductwork.
INSTALLATION OF FLEXIBLE DUCTS
Maximum Length: For any duct run using flexible ductwork, do not exceed 5 - 0" extended length.
Installation shall have smooth full radius turns down to diffuser.
Installation not permitted above inaccessible ceilings.
ACCESS PANELS
Furnish all access panels required for proper servicing of equipment. Provide access panels for all concealed
valves vents, controls and c out doors, and devices required tro lean or sprinkler vices re eel b NFP Provide frame as required for
p q by A_ from require r
finish. Furnish panels to Gen Contractor. Exact locations approved p els General actor. ct lac s to be pproved by the Architect. Minimum size to
be 12" x 12', units to be 16 gauge steel, locking device shall be screwdriver cam locks.
HANGERS AND SUPPORTS
Support all piping, ductwork and equipment by hangers or brackets. Fumish structural steel members where
required to support piping and equipment No portion of piping or valves shall be supported by equipment.
Ductwork - Support by means of hangers as follows:
Duct Width Hanger Size and Type Max. Spacing
60 or less 1 "x.109" (#12 gage) 8
61 to 90 3/8" dia. Rod 8
A pair of hangers shall be located at every transverse joint and elsewhere according to the table.
SEQUENCE OF OPERATION :
HVAC UNIT : During occupied hours, supply fan shall operate continuously, and the outside air
damper shall be open to the minimum position. Condensing unit shall cycle to maintain the required
temperature set point. During unoccupied hours the outside air damper shall be closed and the supply
fan and condensing unit shall maintain the space set point.
A differential enthalpy controlled economizer shall activate whenever the outside air enthalpy is lower than
the enthalpy control setting. Economizer dampers shall modulate to full open position, as required, to
maintain discharge air temperature between 52 and 56 degrees fahrenheit When the space temperature
set point is satisfied, the damper shall return to the minimum outside air position during occupied mode
and close completely during unoccupied mode.
Upon a signal from the duct smoke detectors or zone fire alarm system, units shall shut dawn and
outside air damper shall close.
Exhaust Fans
Toilet Exhaust Fans (Manual)
Exhaust fans shall be controlled by local manual switch furnished, installed and wired by electrical
contractor. When activated, exhaust fon motor damper shall open and fan shall start
(Indicated by EC an MESCH schedule)
Specialty Controls
CONTROL WIRING
Low Voltage Thermostats
Low voltage thermostats shall be furnished, installed and wired by the HVAC contractor. The electrical
contractor shall provide 4" square x 1- W" deep wall outlet boxes at 60" above finished floor (with
single -gang rings) for all thermostats /sensors. The electrical contractor shall provide one 3/4° empty
conduit from each thermostat /sensor location, tumed out above accessible ceilings (in joist space or
against overhead slab /deck). The HVAC /Temperature Control Contractor shall provide all other necessary
conduit, raceway and wiring related wo Conduit shall be identified in ceiling cavity and shall be
provided with sweep bends, bushings and dragline.
Line Voltage Thermostats
General Control Wiring Requirements and Installation Methods
Except where specifically indicated otherwise above, the HVAC /Temperature Control Contractor shall
provide all electrical work as required for all temperature control related wiring (i.e. conduit, raceway,
outlet boxes, junction boxes, wiring, etc.) in accordance with Division 16 requirements. All conduit shall
be 3/4" minimum.
CONTROLS:
Electrical contractor will provide power wiring. HVAC contractor shall provide all the low voltage wiring of
HVAC units and controls, thermostats and controllers. Thermostat shall be by the manufacturer of the
HVAC unit (heat /coal /auto /off) with night setback. Provide plastic protective cover far all thermostats.
Replace controls on existing unit, adjust and calibrate controls.
GUARANTEE
The contractor shall provide a guarantee in written form stating that all work under this section shall be
free of defective work, materials, or parts for a period of one year from the date of owner's final
acceptance and shall repair, revise or replace at no cost to the owner any such defects occurring within
the guarantee period. Contractor shall also state in written form that any items or occurrences arising
during the guarantee period will be attended to in a timely manner and will in no case exceed four (4)
working days from date of notification by owner.
FOR ADDITIONAL MALL REQUIREMENTS, SEE MALL DESIGN AND CONSTRUCTION CRITERIA.
VAV UNIT SCHEDULE
TAG
VAV -1
QUNT.
1
NOMINAL
CFM
2600
TYPE
SINGLE
DUCT
MAKE & MODEL
KRUEGER
LMHS
ELECTRICAL
VOLTS
N/A
PHASE
N/A
HZ
N/A
MCA
N/A
MOCP
N/A
COOLING
CAPACITY
(BTU)
HEATING
CAPACITY
(KW)
SUPPLY
AIR
CFM
ESP
INCH
MIN
AIR
CFM
1300
SEER
OR
EER
WT.
LBS
PRESSURE INDEPENDANT WITH DIGITAL CONTROL
PLENUM - INSULATED FOR SUPPLY
EXHAUST -NOT INSULATED
ACOUSTICAL LINING
NOT TO SCALE
as
DUCT COLLAR
CEILING
FLEXIBLE DUCT
(MAX. 5' -0 ".)
LINEAR DIFFUSER CONNECTION DETAIL
REVIEWED FOR
CODE COMPLIANC
APPROVED
2 2008
City Of Tukwila
E. ILDING DIVISION
GALVANIZED STEEL HANGE
STRAP- MIN. (4) PER
MIXING BOX- SEE
SCHEDULE FOR SIZE.
FOLD STRAP FOR DOUBLE
THICKNESS- TYPICAL FOR
ALL HANGER STRAPS.
AIR TER
NOT TO SCALE
DRAWING LIST
M -1
M -2
MECHANICAL CEIUNG PLAN
MECHANICAL NOTES AND SCHEDULES & DETAILS
SECURE TO CONCRETE
STRUCTURE WITH 3/8" DIA.
REDHEAD- TYPICAL EACH
HANGER, STRAP OR BRACE
MDR -283
IAGONAL BRACE
TYPICAL -SEE
SCHEDULE FOR SIZE
(2) EACH SIDE.
VIINAL BOX MOU \TING DETAIL
RECE
CITY OFT
DEC 1
PERMIT C
VED
u KVI
2007
ENTE