HomeMy WebLinkAboutPermit M07-286 - WESTFIELD SOUTHCENTER MALL - STRIDE RITESTRIDE RITE
1077 SOUTHCENTER MALL
M07 -286
Parcel No.:
Address:
Suite No:
Tenant:
Name:
Address:
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Cityif Tukwila
6364200010
1077 SOUTHCENTER MALL TUKW
STRIDE RITE
1077 SOUTHCENTER MALL , TUKWILA WA
WEA SOUTHCENTER LLC
11601 WILSHIRE BLVD , LOS ANGELES CA
LAUREN CHASE
191 SPRING ST , LEXINGTON MA
Contractor:
Name: MERIT MECHANICAL INC.
Address: PO BOX 2109 , REDMOND, WA
Contractor License No: MERITMI163CM
Value of Mechanical: $10,000.00
Type of Fire Protection: SPRINKLERS
Furnace: <100K BTU
>100K BTU
Floor Furnace
Suspended/Wall/Floor Mounted Heater
Appliance Vent
Repair or Addition to Heat/Refrig /Cooling System....
Air Handling Unit <10,000 CFM
>10,000 CFM
Evaporator Cooler
Ventilation Fan connected to single duct
Ventilation System
Hood and Duct
Incinerator: Domestic
Commercial/Industrial
doc: IMC-10 /06
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
MECHANICAL PERMIT
DESCRIPTION OF WORK:
INSTALL FAN POWERED INTERNAL, DUCTED SUPPLY AND RETURN .AIR SYSTEM AND CONTROLS.
EQUIPMENT TYPE AND QUANTITY
0
0
0
0
0
0
0
0
0
0
0
0
0
0
* *continued on next page **
M07 -286
Permit Number: M07 -286
Issue Date: 06/18/2008
Permit Expires On: 12/15/2008
Phone:
Phone: 410 - 454 -1700
Phone: 425 883 -9224
Expiration Date: 06/01/2009
Fees Collected: $269.58
International Mechanical Code Edition: 2006
Boiler Compressor:
0-3 HP /100,000 BTU 0
3 -15 HP /500,000 BTU 0
15-30 HP /1,000,000 BTU.. 0
30 -50 HP /1,750,000 BTU.. 0
50+ HP /1,750,000 BTU 0
Fire Damper 0
Diffuser 0
Thermostat 0
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment 0
Printed: 06 -18 -2008
Permit Center Authorized Signature:
I hereby certify that I have read and
governing this work will be complie
The granting of
construction or
Signature:
Print Name:
doc: IMC -10/06
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
Permit Number: M07 -286
Issue Date: 06/18/2008
Permit Expires On: 12/15/2008
Date:
ed this permit and know the same to be true and correct. All provisions of law and ordinances
whether specified herein or not.
t does not pr - • e to give authority to violate or cancel the provisions of any other state or local laws regulating
onnance of work. authorize • to sign and obtain this mechanical permit.
Date:
This permit shall become null and void if the work is not co enced within 180 days from the date of issuance, or if the work is suspender
or abandoned for a period of 180 days from the last inspection.
M07 -286 Printed: 06-18 -2008
City of Tukwila
Parcel No.: 6364200010
Address: 1077 SOUTHCENTER MALL TUKW
Suite No:
Tenant: STRIDE RITE
1: ** *BUILDING DEPARTMENT CONDITIONS * **
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
5: Readily accessible access to roof mounted equipment is required.
PERMIT CONDITIONS
Permit Number: M07 - 286
Status: ISSUED
Applied Date: 12/21/2007
Issue Date: 06/18/2008
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431 - 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
6: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
7: Manufacturers installation instructions shall be available on the job site at the time of inspection.
8: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206 - 431 - 3670).
9: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
10: ** *FIRE DEPARTMENT CONDITIONS * **
11: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
12: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
13: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
14: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
15: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
16: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
doc: Cond -10/06
M07 -286 Printed: 06-18 -2008
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
17: An electrical permit from the City of Tukwila Building Department Permit Center (206 - 431 -3670) is required for this
project.
18: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
19: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
20: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: Cond - 10/06
* *continued on next page **
M07 -286 Printed: 06-18 -2008
Iso
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating
construction or tit - • - rformance of wor
Signature:
doc: Cond -10/06
Print Name: I !L
Date:
SCI, a108
M07 -286 Printed: 06-18 -2008
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.ci.tukwila.wa.us
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
SITE LOCATION
10-77 King Co Assessor's Tax No.: :F . MO )- i 1 0010
Site Address. SOtffN CEN7BL MALL ,TuKrti 14:1 , \rfA 98 Suite Number. 3 ` 1.300 Floor: j
Tenant Name: 5 Z17 New Tenant: Na Yes ❑ ..No
Property Owners Name: THE WESTFIE GROUP (A7TN: JOSHUA KIMMEL.)
Mailing Address: 11TH PL0O1Z, 1 1601 Wit-SHIRE 17t.VO 1..05 ANGELES CALIFORNIA X10025
City State
CONTACT PERSO ho do we contact when �
your permit 15 ready to be issued 4 (lt . :1 ,, t
Name: JEFF Mt &ARRY ( .t3J&Vl C.l 7 / Day Telephone: (617) 132q- 6L103
Mailing Address: 1 11 SPRING 57414. 41' rit 1142 L - YJNGTOA1 MA 02
n City State Zip
E -Mail Address: jetr,mcoarr corn Fax Number: (617) 616-6403
GENERAL CONTRACTOR INFORMATION — 7'o gt 7E yre
(Contractor Information for Mechanical (pg 4) for Plumbing and Gas Piping (pg 5)) ,. f ..7 /7 TO 0
Company Name:
Mailing Address:
City
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Expiration Date:
Contractor Registration Number:
Company Name: D tJA I,S T. 1`ITC 1- 1(11.- Milk r)
Public Works Permit No.
Building Permit No
Mechanical Permit No. t 7 -
Plumbing/Gas Permit No.
Project No.
or office use cnly)
State
Zip
Zip
ARCHITECT OF RECORD — All plans must be wet stamped by Architect of Record
Mailing Address: (003! 1 - Z.0 WEST, 51k CIE Z(oo Ae J keT010 --0( -4.60 11-
City State
Zip
Contact Person: Day Telephone: (817) Z65 - - N/ S
Fax Number: ( gl7) 41I3 — 73
E -Mail Address: [TfN1AeC}1 TIECT CLi . (nM
ENGINEER OF RECORD All plans must be wet stamped by Engineer of Record .'
Company Name: H€ N ILy a' A oc44 - TF$
Mailing Address:
_ .4
.
■ &• o _IL
City State Zip
Day Telephone: (V (o) 2.9 Z. Yt09 to
E- Mail Address: HAIL( MC!- ierJetiA55O 'IATF5. rpm Fax Number: (Z( (o) Z92- - 55 P -(
Q: NApplicationsTottna- Applications On Line\3 -2006 - Permit Application.doe
Revised: 9 -2006
bit
Contact Person: t 1 0-1 b4t.11 -4
Page 1 of 6
Unit Type:
Qty
Unit Type:
Qty
Unit Type:
Qty
Bonner /Compressor:
Qty
Furnace <I00K BTU
Air Handling Unit >10,000
CFM
Fire Damper
0-3 HP /100,000 BTU
Furnace>I00K BTU
Evaporator Cooler
Diffuser
4-
3 -15 HP /500,000 BTU
Floor Furnace
Ventilation Fan Connected
to Single Duct
Thermostat
15 -30 HP /1,000,000 BTU
Suspended/Wall/Floor
Mounted Heater
Ventilation System
Wood/Gas Stove
30 -50 HP /1,750,000 BTU
Appliance Vent
Hood and Duct
Emergency
Generator
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Refrig/Cooling
System
Incinerator - Domestic
Other Mechanical
Equipment
Air Handling Unit
<10,000 CFM
1
Incinerator — Comm/Ind
MECHANICAL PERMIT INFORMATION - 206- 431 -3670
MECHANICAL CONTRACTOR INFORMATION
Company Name:
Mailing Address:
City State Zip
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date:
Valuation of Mechanical work (contractor's bid price): $ r ' 7 70 dfb (4 7� Vrcva $86 O
Scope of Work (please provide detailed information): /i( , a.4V7E01ijjt,4St__, d
f bm/ l r- ex/7.ects. "64 - ,,c1>4L C c:v.c.4'e.7 2 . 7►D
•
•
1 4r
Use: Residential: New .... ❑ Replacement .... ❑
Commercial: New ... Replacement .... ❑
Fuel Type: Electric ❑ . Gas ....0 Other: 41.611. yeO Nv, A vg
Indicate type of mechanical work being installed and the quantity below:
Q1Applications\Forns- Applications On Line\3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
Page 4 of 6
Date Application Accepted:
Date Application Expires:
Staff finials:
I� �g��7
L9 d
1
PERMIT APPLICATION NOTES - Applicable to all permits in this application
Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review - Applications for which no permit is issued within 180 days following the date of applii:ation shall expire by limitation.
Building and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
Plumbing Permit
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing Code (current edition).
I HEREBY CERTIFYTHAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE SIAM' OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
E /91A44*— c I f-
BUILDING
Signature:
,Pnnt Name:
Mailing Address:
� `\ 1 See-MAz
D AGENT:
LUX /ft-t5 1 02 *Zt
Q: \Applications\Fonn,-Applications On Line\3-2006 - Permit Application.doc
Revised: 9 -2006
bh
Day Telephone: 1 59 1 i ar'
City
State
iiMkt g
c�� reA.
1-6C fNC
L zL C Aoht (et T)
$r (t°
Date: / - -
Z ip
Page 6 of 6
Parcel No.: 6364200010 Permit Number: M07 -286
Address: 1077 SOUTHCENTER MALL TUKW Status: APPROVED
Suite No: Applied Date: 12/21/2007
Applicant: STRIDE RITE Issue Date:
Receipt No.: R08 - 02175
[nitials. JEM Payment Date: 06/18/2008 02 :58 PM
User ID: 1165 Balance: $0.00
Payee: MRS. CARRIE N. SNYDER
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: //www.ci.tukwila.wa.us
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 4524 221.66
ICCOUNT ITEM LIST:
Description
MECHANICAL - NONRES
RECEIPT
Account Code Current Pmts
000/322.100 221.66
Total: $221.66
Payment Amount: $221.66
3780 06/18 9711 TOTAL 221.66
Receipt No.: R07 - 02871
Initials: WER
User ID: 1655
Payee: NATIONAL SERVICES GROUP
ACCOUNT ITEM LIST:
Description
PLAN CHECK - NONRES
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 6364200010 Permit Number: M07 -286
Address: 1077 SOUTHCENTER MALL TUKW Status: PENDING
Suite No: Applied Date: 12/21/2007
Applicant: STRIDE RITE Issue Date:
TRANSACTION LIST:
Type Method Description Amount
Payment Check 333600 47.92
Account Code Current Pmts
000/345.830 47.92
Total: $47.92
Payment Amount: $47.92
Payment Date: 12/28/2007 03:45 PM
Balance: $221.66
6615 12/31 9710 TOTAL 861.99
riot. RAc int -06 Prints: 12 -28 -2007
Project___: i
Z. ■)-�
Type of Inspection: 4.6
Address:4 ni�4 f/ /
Date Called:
Special Instructions:
Date Wanted:
/
d O
7 /2/
a.m.
P.m.
Requester:
Phone No:
IIVVECTION RECORD
Retain a copy with permit"`
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION 1
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
COMMENTS:
� co flip leo_7te
Approved per applicable codes. El Corrections required prior to approval.
'Inspector:
El $60.00
paid at
r ate: /264 8
IN SPECTION FEE REQUIRED. Prior to inspection, fee must be
00 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
1Mol-2-70
1
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION -
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Project:
Address:
lo 'I 7 /17, -
Special Instructions:
Type of Inspection:
0 K-Q
ckk-tcto 441
Date Called:
Date Wanted:
111V07
a.m.
p.m.
Requester:
Phone No:
7 5 - S — c Z . 4o0
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
: ' ( 11.0-.0-. 4,0,4_4,5 n o • 21 - P p1
'ci tics (ter# (Ac - -I
'Inspector:
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
NPA
Date: 9 7 i)1I 0 e
JJ $60.00 REINSPECTION F EE RR) RED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
Projtc- -ru i7(
TYP (n% l i7 I
Addr D 77 /91/9//
Date Called:
Special Instructions:
Date Wanted:
7 /6
p.m.
Requester:
Ph L7 68G --
C'
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION 1
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
DEC 4r rc ///
(Date: 7 /c /
El $6 . EINSPECTION FEE REQUIRED. Prior to inspection, fee must be
pa , • t 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
Project:
Type of Inspection:
Address:
/0 77 041/
Date
Frn.
Itily
Special Instructions:
Date Wanted:
/ , i „.
v/'F
Requester:
Phone No:
3
0 Approved per applicable codes.
INSPECTION RECORD
Retain a copy with permit
NO 7 . " - ,ce&
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION 1 °-•
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431-3670
EI Corrections required prior to approval.
COMMENTS:
Aolj se.c5AA Aret41,i
LIA
ri $60.0 NSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid t1300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
COMMENTS:
p /l
Ty 7f Inspection: /'�
i rv/e
Address
/07 7 /2)
ct?"
P at '`ti
Sn 1 e 5
4 / eh
Date W nted / , a.
Requester:
Phone N
- 7�S - z — MC)/
( •10( G
ge Le" A,
rrc, -1 SFr/
to
5 120, ,
Proj
R17/.
Ty 7f Inspection: /'�
i rv/e
Address
/07 7 /2)
/9 /
Date Called_
Special Instructions:
„----
if
Date W nted / , a.
Requester:
Phone N
- 7�S - z — MC)/
2
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3f 7
EI Approved per applicable codes. El Corrections required prior to approval.
Inspector:
Date:
e- A6-05
'l $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
1 1 1
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION le-
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Project:
5fiiacRk
Approved per applicable codes.
•
INSPECTION RECORD
Retain a copy with permit
I N -
Address'
X 0)2 MAU
Special Instructions:
Type of Inspection:
t t r'
Date Called:
Date Wanted:
p.m.
Requester:
Phone No:
a s 1 1‘11 670
Corrections required prior to approval.
COMMENTS: p/
t : W ' -fro 1 'S,A Q
I . I
$6 - EINSPE C FEE REQUIRED. Prior to inspection, fee must be
p at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
COMMENTS:
l R f
-
Type of Insp ion:
Address: it ; -7 -
Suite #:
- , (
- ixjev(,
(' k_
/tic / t,,\
r
kl AS Ak -
O
Phone No.:
7:1 li -L __
g.
,
c _ or<
Project: j-
l R f
-
Type of Insp ion:
Address: it ; -7 -
Suite #:
- , (
/Al , 3. L. L
Contact Peron:
Special Instructions:
Phone No.:
Needs Shift Inspection:
Sprinklers: 5'
Are Alarm:
Hood & Duct: &
Monitor: 6-1.4, a i✓
Pre -Fire: TO
Permits: N
Occupancy Type: y✓\,
INSPECTION NUMBER
.Approved per applicable codes.
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA FIRE DEPARTMENT
Word/Inspection Record Form.Doc 1/13/06
PERMIT NUMBERS
444 Andover Park East, Tukwila, Wa. 98188 206 - 575 -4407
I I Corrections required prior to approval.
nspector:
Date: 7
Hrs.:
)
/On $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
T.F.D. Form F.P. 113
Ptar rCV `''1'
4'1"
DWG. ACTION REOUIRED
Ell
FILE COPY
Permit No.
.. -� '
Southcenter Malt
Tukwila, Washington
Mechanical and Electrical Review Notes for
Provide complete Fire Suppression System Design per Tenant Criteria Manual and
Bulletin #1.
HP ENGINEERING, CONSULTING ENGINEERS, P.C.
Tel: 203.239.9425 Fax: 203.239.9445
No i z 101
Stride Rite #1300
These review notes are to be incorporated into the drawings per direction of the Westfield Tenant
Criteria Manual (TCM) and Code Requirements. All drawing changes shall be clouded and a written
response to each of the following items below shall accompany drawings being resubmitted for review.
A
NUAL DIFFERENCES
Effective July 1, 2007 the City of Tukwila will be under the 2006 International Codes
and all permit submittals need to be in conformance with this edition.
It Is the Tenant's/Tenant Architects responsibility to verify and conform to all
applicable codes and regulations. Subsequent plans will be reviewed under the then
current codes and ordinances.
Landlord provided a Tenant Fire Service Main with branch piping stubbed into each
Tenant's space. Landlord's sprinkler system is designed per Ordinary Hazard Group 2
and the latest requirements of NFPA 13. No isolation valves will be provided or
permitted.
Tenant shall connect a fire sprinkler system to Landlord's sprinkler system within the
demised premises using approved mechanical fittings. Tenant shall provide and
install all branch piping and sprinklers required to complete the sprinkler system
within the Tenant space. Tenant's sprinkler system designs shall be based upon the
requirements of the State of Washington, City of Tukwila Fire Department. Tenant
shall engage the services of a landlord preferred Fire Sprinkler contractor to design,
permit and install Tenant's Fire Sprinkler system in accordance with the base building
design specifications. Sprinkler layout and pipe sizing shall be hydraulically designed
according to Ordinary Hazard Group 2 and the latest requirements of NFPA 13.
• Duct smoke detector wiring diagram shall note fan - powered VAV box not AC unit.
Coordinate voltage with VAV terminal specification.
• Mechanical floor plan provide mechanical coded note for supply register. Note #7 not
applicable.
Page 2
CTIV
DEC 2'el 2007
B-1'M114 CENTEt
i2
Southcenter Mall
Tukwila, Washington
Mechanical and Electrical Review Notes for
Stride Rite #1300
• Remove emergency light fixture from common mall space at store entry. Common
mall space has emergency lighting.
• Landlord provided a main disconnect means for Tenant in a Landlord Electrical Room
as well as conduit and conductors (feeder) from the main disconnect means to a
Landlord provided fused disconnect switch located within the Tenant space. If needed
to accommodate Tenant construction, the Tenant shall relocate the Landlord provided
disconnect switch and associated feeder. Tenant shall fumish and install conduit and
conductors from fused disconnect switch to Tenants' main fused disconnect switch or
main circuit breaker equipped panelboard.
• Electrical contractor shall utilize Landlord provided fused disconnect switch located
within the Tenant space, on back wall, for temporary electrical for construction.
Electrical contractor shall provide temporary transformer and panel as required within
Tenant space.
• Landlord provided master metering equipment in the Landlord's Electrical Room. The
Landlord -owned network metering system will meter tenant power consumption.
• Transformers are to be floor mounted.
• Landlord will provide a communication cable tray located in the utility corridor for
Tenant's use. No conduit will be provided. Landlord will provide a communications
terminal board within each Landlord electrical room. Tenant shall provide and install
a complete telephone service support facilities as required by the serving telephone
company. All Tenant telephone equipment shall be contained within the Tenant's
space. Tenant shall provide plenum rated wire from the telephone room to the
Tenant's telephone equipment within the demised premises utilizing the Landlord
supplied cable tray. Any corridor wall penetrations will need to be fire caulked as
required.
• Tenant shall install within Tenant's Premises a fire alarm system or components as
delineated through design documents issued by Landlord's Designated Fire Alarm
Contractor (at Tenant's expense). Drawings shall comply with all aspects of the
Tenant Criteria Manual - Fire Alarm System - Tenant work and drawing
requirements. A copy of fire alarm drawings shall be issued to the local Fire Marshal's
Office.
• Landlord's Designated Fire Alarm Contractor shall make final connections to
Landlord's fire alarm system at the Tenant's sole cost and expense.
• Refer to tenant design criteria - Bulletin no. 7 for required fire alarm sub contractor.
HP ENGINEERING, CONSULTING ENGINEERS, P.C.
Tel: 203.239.9425 Fax: 203.239.9445
Page 3
DEC 2 8 cuui
PEI iv ^ \t;
MU
Southcenter Mall
Tukwila, Washington
Mechanical and Electrical Review Notes for
Stride Rite #1300
• Provide a lock -on device on panel circuit breakers for exit & emergency lighting, fire
alarm system, security system, etc.
• Electrical system - A. Scope 2. Landlord electrical service is 277/480v.
• No attachment or support from any roof deck is allowed. Hangers, clamps and
supports shall be fastened to bar joists or beams only.
• No BX, AC, MC or Romex type wiring allowed.
• All cabling shall be plenum rated. All Tenants served by Landlords air conditioning
units have plenum returns.
• K. Telephone service - See comment on drawings E2 for requirements.
HP ENGINEERING, CONSULTING ENGINEERS, P.C.
Tel: 203.239.9425 Fax: 203.239.9445
Page 4
DEC 213 2001
PERMIT CEI`I-t-t.-
05 -08 -2008
LAUREN CHASE
191 SPRING ST
LEXINGTON MA 02421
RE: Permit Application No. M07 -286
1077 SOUTHCENTER MALL TUKW
Dear Permit Applicant:
In reviewing our current permit application files, it appears that your permit application applied for on 12/21 /2007 , has not been
issued by the City of Tukwila Permit Center. Per the International Codes, Uniform Plumbing Code and/or the National Electrical
Code, every permit application not issued within 180 days from the date of application shall expire by limitation and become null and
void. Your permit application expires on 06/18/2008 .
If you choose to pursue your project, a written request for extension of your application addressed to the Building Official,
demonstrating justifiable cause, will need to be received at the Permit Center prior to your expiration date of 06/18/2008. If it is
determined that an extension is granted, your application will be extended for an additional 90 days from the expiration date.
In the event we do not receive your written request for extension, your permit application will become null and void and your project
will require a new permit application, plans and specifications, and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
xc:
er Marshall
t Technician
Permit File No. M07 -286
City of Tukwila
Jim Haggerton, Mayor
Department of Community Development Jack Pace, Director
6300 Southcenter Boulevard. Suite #100 • Tukwila. Washington 9R1RR • PhnnP• 2(M-471-U711 • FPv. 2fA_A2L_2/.. C
ACTIVITY NUMBER: M07 -286 DATE: 12 -28 -07
PROJECT NAME:. STRIDE RITE
SITE ADDRESS: 1077 SOUTHCENTER MALL
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # After Permit Issued
DEPARTMENTS:
BuI ng Division
Public Works ❑
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Please Route
PLAN REVIEW %ROUT SLIP
(J
Fire r ention
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES/THURS ROUTING:
Incomplete
Structural Review Required
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
Notation:
REVIEWER'S INITIALS:
Documents/routing slip.doc
2 -28 -02
Structural ❑ Permit Coordinator
Planning Division
DUE DATE: 01 -03 -08
DATE:
Not Applicable
❑ No further Review Required
DATE:
DUE DATE: 01 -24 -08
Not Approved (attach comments) ❑
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Business Owner Information
Name
Role
Effective
Date
Expiration
Date
KIRKWOOD, RODERICK V
PRESIDENT
02/14/1984
Bond
Amount
KIRKWOOD, JOAN M
SECRETARY
02/27/2006
FRICKBERG, WILLIAM
MICHAEL
VICE
PRESIDENT
02/27/2006
Bond Information
Bond
Bond
Company
Name
Bond Account
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Bond
Amount
Received
Date
r -- -- --- -- - - - --� - - - - - -- - ---- - o
Washington State Department of Labor and Industries
General/Specialty Contractor
A business registered as a construction contractor with L &I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
License Information
License
Licensee Name
Licensee Type
UBI
Ind. Ins. Account Id
Business Type
Address 1
Address 2
City
County
State
Zip
Phone
Status
Specialty 1
Specialty 2
Effective Date
Expiration Date
Suspend Date
Separation Date
Parent Company
Previous License
Next License
Associated License
MERITMI163CM
MERIT MECHANICAL INC
CONSTRUCTION CONTRACTOR
600517946
46817500
CORPORATION
PO BOX 2109
REDMOND
KING
WA
980732109
4258839224
ACTIVE
GENERAL
UNUSED
2/14/1984
6/1/2009
AUTOMMC044QH
https:// fortress. wa. gov /lni/bbip /printer.aspx ?License= MERITMI163CM 06/18/2008
ELBOW WITH
AIRFOIL
TURIN'S VANES
ROOM AREA (ft2)
ACous11C
LINED DUCT
(SEE NOTE III)
OUTDOOR AIR
CLASSIFICATION
PERSONS
PER 1000 ft2
( Net Area)
NO. OF
OCCUP.
GFM/PERSON
PER IMC
TABLE 403.3
CFM/ft2
PER IMC TABLE 403.3
(Gross Area)
REGUIREP
O.A.
DESIGN
O.A.
6ROSS
BRANCH
TAKE-OFF
RECTANGULAR
T ROGTANSCLAR
BRANCH
TAK -QFF
RECTANGULAR
TO ROUND
45°O
VD
SALES
500
45°
MYD
BRANCH
TAKE-OFF
RDUND TO
ROUND
150
150
SQUARE TO
TRANSITION
FITTING
400
STOCK ROOM
0.15
■'
60
CPU M
30
PORPORTIONAL
SPLIT
III
FLEXIBLE
DUCT
ERAI TO
\zxT GH DIFFI
iaaaaaa
MAX LENGTH = 48'
!A
II,
III
MANUAL
VOLU
DAMPER
)
Nom_
DASHED LINE INDICATES I' INTERIOR
AGOU511C LINING UItESS OTHERWI51r
NOTED. DUCT 51ZE I5 EXTERIOR
AND INCLUDES LIPNIN6.
ROOM NAME
ROOM AREA (ft2)
OCCUPANCY
OUTDOOR AIR
CLASSIFICATION
PERSONS
PER 1000 ft2
( Net Area)
NO. OF
OCCUP.
GFM/PERSON
PER IMC
TABLE 403.3
CFM/ft2
PER IMC TABLE 403.3
(Gross Area)
REGUIREP
O.A.
DESIGN
O.A.
6ROSS
SALES
500
RETAIL SALES
0.3
150
150
STOCK
400
STOCK ROOM
0.15
60
60
TOTALS
210
210
TYPICAL DUCT TAKE-OFF DETAIL
SCALE: NONE
N07E5:
L ALL WIRING TO BE RR MANUFACTURERS
WIRING DIAGRAMS.
2. LOCATION OF DUCT DETECTOR TO BE
VERIFIED WITH LOCAL FIRE MARSHAL.
DETECTOR 15 TO BE INSTALLED IN AN
ACC SSABLE LOCATION.
3. PROVIDE AUXILLARY CONTAGT5 FOR
FIRE ALARM SYSTEM BY E.G.
PROVIDE LABEL INDICATING
ASS GIATEP AG UNIT SERVED.
INSTALL ADJACENT T-STAT OR
IN LOCATION APPROVED BY
FIRE MAR
NOTE:
SUBMIT SHOP DWGS 4 DERAILS
OF SMOKE DETECTOR
INSTALLATION TO LOCAL
BUILDING DEPT. 6 FIRE
MARSHAL FOR APPROVAL
PRIOR TO ANY HORK
#IS
PER 2006 IMC SECTION 606
Install smoke detector to shut down air distribution
by VAV's when the total combined C F M of all
VAV's (to include other tenants) sharing the same
plenum space exceeds 2000 CFM.
(See IMC 606.2.2 for approved method of detection)
4 -!MIRE PHOTO - ELECTRIC DUCT
DETECTOR IN RETURN AIR DUCT WITH
SAMPLING TUBES SIZED AS REQUIRED.
SYSTEM 5134SOR #DHIOOAGDCLP
I2CN POWIR FROM
AG UNIT
INTERLOCK TO SHUT
DOWN UNIT ON ALARM
5Y5TEM SENSOR 155K45I
COMBINATION ALARM, TROUBLE,
HORN E KEY TEST STATION
DUCT SMOKE DETECTOR WIRING DIAGRAM
SCALE NONE
of
4' -0° MAX OF STRAIGHT MEDIUM
PRE59,1RE RATED FI-EXII3LF
INSULATED DUCT. NO BLENDS
GREATER THAN 22 ARE
PERMITTED.
FILE COPY
Permit No.
BOTTOM ACCESS
PANE
ELECTRIC
HEATING COIL
�AD1" 20b
City of Tukwila
BU DING DIVISION
FAN POWERED TERMINAL DETAIL
SERIES FLOW WITH ELECTRIC
REHEAT
SCALE: NONE
'X' OR
MECHANICAL LEGEND
GTX
0
MEGHANIGAL VURri LATION (OUTSIDE AIR) 50EDULE
Plan review epprowd =bleat to enoRI end wisdom.
Approval of ..: , ,_ _< _ does not aultalze
the r of �r , . {; o0f • ordnance.floceipt
.. .
I" AC LINED
RETURN
EXISTING TO REMAIN
COINGGT TO EXISTING
INDICATES CODED NOTE
MVD MANUAL VOLUME DAMPER
aT THERMOSTAT
GEMERAL REQUIREMENTS FOR COMPLIANCE WITH WASHINGTON
Y
I. SUPPLY AND RETURN AIR DUCTWORK IN UNCONDITIONED SPACES SHALL
BE INSULATED PL=R TABLE 5-11 OF THE ENERGY CODE.
2. ALL DUCTWORK SHALL BE SEALED PER 5EG110N 1414.1 OF 11-E ENERGY
CODE
3. TH®RMOSTAT SHALL PROVIDE FRO&RAMMABLE CONTROLS CAPABLE
OF REDUCING EAR6Y USE THROUGH AUTOMATIC SHNJIVOWN DURING
PERIODS OF NON -USE OR ALTERNATE USE OF SPACES. AUTOMATIC
CONTROL SYSTEM SHALL HAVE A MINIMUM SEV134 -DAY CLOCK AND BE
CAPABLE OP MINE SET FOR SEVEN DIFRT DAY TYPES PER WEEK
4. ZONE CONTROLS SHALL BE CAPABLE OF PROVIDING A TEMPERATURE
RANGE OR DEADSAdD OF AT LEAST 5 PR F WITHIN WHICH THE
SUPPLY OF HEATING AND COOLING EMERY TO THE ZONE 15 SFIff OFF
OR REDUCED TO A MINIMUM.
No changes shelf ade f'!he scope
of work 14 7,7),I7 approval of
Tukwila BiJ$s R?g
VSDY3.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
FFB TERMINAL
WITH HEATING
COIL.
SEPARATE PERMIT
REQUIRED FOR:
❑ Mechanical
IiElectrical
Plumbing
L(Gas Piping
City of Tukwila
BUILDING DIVISION
U1. LISTED
CONTROL PANEL
. IN AC LINED 5A MAIN.
INSTALL LINING 24' FROM
REHEAT COIL 4 INSULATE
DUCT WHERE LINING IS
OMITTED.
I" AC LINED
SUPPLY
MECHANICAL GENERAL NOTES:
A HVAG CONTRACTOR MUST REVIEW THE EQIU I PM ENT SCHEDULES,
SPECIFICATIONS, AND DRAWIN65 IN ALL CONTRACT DOCUMENTS AND
SUBSEQUENT SHOP DRAWI N65. PROVIDE ALL. LABOR AND MATERIALS
FOR A COMPLETE AND OPERABLE SYSTEM AS PART OF THE CONTRAGT.
FAILURE TO REVIEW DOES NOT RELIEVE THE CONTRACTOR OF
FULFILLIN6 THE CONTRACTUAL OBLI6ATIONS.
B REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR CEILING
DIFFUSER AND GRILLE MOUNCTIN6 LOCATIONS.
E COORDINATE INSTALLATION OF ALL NEK MORK WITH ARCHITECTURAL
Alm STRUCTURAL FLANS AND ALL OTHER TRADES. GONTRAGTOR SHALL
TAKE ALL INTERFEREW,E5 INTO CONSIDERATION. PROVIDE ALL
NECESSARY OFFSETS AND TRANSITIONS WITH AREAS EQJ I VALENT TO
DUCT SIZES INDICATED ON DRAWINGS.
D ALL DUCTWORK SHALL BE INSTALLED TI6HT TO UNDERSIDE OF ROOF
STRUCTURE OR AS HIGH AS POSSIBLE TO AVOID OBSTRUCTIONS.
E DO NOT INSTALL ANY MECHANICAL WORK ABOVE ELECTRICAL PANELS
OR EQUIPMENT.
F FOR ALL BRANCH DUCT COPCTIONS TO MAIN TRUNK, PROVIDE 45
D1E6REE TRANSITION FITTING OR CONICAL TAP FOR ROUND DUCT.
BUTT FITTINGS ARE NOT PERMITTED. PROVIDE MANUAL VOLUME
DAMPER WITH LOCKING QUADRANT IN ALL BRANCH RJNOUTS TO
GRILLES AND DIFFUSERS.
6 PROVIDE MITERED ELBOW WITH TURNING VANES OR ftBOK WITH
CENTERLINE RADIUS EQUAL TO 1 .5 TIMES DUCT WIDTH AT ALL
U- IAN6F5 IN DIRECTION.
H MECHANICAL CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING PROCESS
AND FIELD VERIFY EXISTING CONDITIONS. CONTRACTOR SHALL TAKE ALL
INTERPMENCE5 INTO GON5IPERATION .
I THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL FERMITS, LICENSES,
DOCUMENTS AND 51ERVIGES RELATED TO INSTALLATION! OF 1T-rE P.
J NO THERMOSTATS Al RE TO BE LOCATED OVER HEAT PRODUGI NS EQUIPMENT.
K HVAG DUCTWORK SHALL BE FABRICATED AND FELTED IN ACCORDANCE
WITH ASFRAE AND LATEST SHAGNA STANDARDS. PROVIDE TURNING
VANES IN ALL ELBOWS.
L CONTRACTOR SHA LI. BE FAMILIAR WITH LANDLORD'S AND TENANTS
STANDARDS, RILE, AND REGULATIONS. ALL LANDLORD AND TENANT
CRITERIA SHALL SE COMPLIED WITH AND INCLUDED IN THIS BID.
M AN AIR -BALANCE OF THE SYSTEM M15T BE PEP—FORMED BY AN INDEPENDENT
TEMEPERATIRE CONTROL /AIR BALANCE CONTRACTOR AS REWIRED BY
LANDLORD, WITH A CERTIFIED AIR - BALANCE REPORT SUBMITTED TO
LANDLORD'S NTAIIVE PRIOR TO STORE OPENING.
N FIRE PROTECTION CONTRACTOR SHALL BE LANDLORD APPROVED AND
SHALL COORDINATE SPRINKLER SYSTEM WITH DUCTWORK AND LIGHTS.
SUBMIT SPRINKLER DRAWINGS AND HYDRAJJLIC CALCULATIONS TO
LANDLORD'S INSURANCE COMPANY AND AUTHORITY HAVING J. ISDICA11Oi
FOR APPROVAL
O ALL LIFE 5AF E IY/5FF2INKLER SYSTEM WORK SHALL SE SCHEDULED WITH
LANDLORD'S REPRESENTATIVE
SET UNIT AT
IOOO CFM CONSTANT VOLUME
1000 CFM PRIMARY AIR MAX
210 GFM PRIMARY AIR MIN
'X' -I4" MED.
PRESSURE
SA DUCT
OT _Ft, _pIEIJSI a AND_ RF6ISTf325:
MECHANICAL EQUIPMENT SCHEDULE
FPB/I FAN POWERED VAV TERMINAL - TITUS MODEL TG5-B-10 PRESaRE
INPEPEHP r CONSTANT VOLUME SERIES FLOW FAN PoPERED VAV TERMINAL,
IO" DIA. INLET SIZE, CFM RANEE 600 -1400 CFM, 0.4' ESP., INSULATED CABINET,
I' TA FILTER AND SPARE, IHTE6R.AL NON -FUSED DISCONNECT, V4 EP (211/1160)
ECM MOTOR WITH MATCHING VARIABLE SPEED SCR CONTROL 5 KIN (460/3/60)
ELECTRIC I-EA1tR WITH SCR CONTR011_ER, SINGLE POINT POPER CONNECTION,
DAMPER ACTUATOR AND MATCHING 7 -DAY PROGRAMMABLE WALL MOUNTED
11-ERMOSTAT WITH NIGHT SETBACK PROVIDE REQUIRED INLET AND DI
DUCT TRANSITIONS FROM BOX CONNC- CTIONS TO SUPPLY AND DISCHARGE DUCT
SIZES INDICATED ON PLAN. CONTRACTOR SHALL VERIFY EQUIPMENT' MAKE,
MODEL, ACCESSORIES, AND CONTROL REQUIREMENTS WITH MALL CRITERIA AND
LANDLORD'S REPRESENTATIVE PRIOR TO CRDEHJN6. PROVIDE ALL REWIRED
CONTROLS, CONTROL WIRING, AND INTERLOCKS. ALL CONTROL WIRJNG SHALL
BE IN CONDUIT PEER NEC.
CD/1 CEILING DIFFUSER - 111115 MODEL TMS, 24X24 MODULE, LAY -IN, STEEL,
HHITE, WITH OPPOSED BLADE PftJFER.
SR/ 1 SUPPLY REGISTER - TITUS MODEL 30OIR)-, DOUBLE DEFLECTION,
SURFACE MOUNT, STEEL, OFF AMITE.
66 /I�URN GRILLE - TAUS MODE_ 350RL, SURFACE MOUNT, 5TEEL,
WHITE.
A. EQUIVALENT BY ANIEEMIOSTAT, PRICE, KRUE6ER OR NAILOR
INDUSTRIES.
B. EQUIVALENT DIFFUSERS SHALL HAVE MAX NC RATING OF 22 FOR GFM
LISTED ON PLANS.
G. ALL FRAME TYPES SHALL. BE COMPATIBLE WITH ADJACENT
CONSTRU TION. REFER TO ARCHITEECIUAL PLANS FOR CONSTRUCTION
DETAILS.
MECHANICAL CODED NOTES: 0
I SUPPORT FAN POKBRED TERMINAL AS HIGH AS POSSIBLE ABOVE FINISHED
13.Or?R FROM FLOOR STRUCTURE ABOVE. MAINTAIN ALL REQUIRED UNIT SE2VIGE
CLEARANCES. REFER TO INSTALLATION DETAIL THI5 DRAWING.
2 DASHED LINE INDICATES I INTERNAL ACOUSTIC LINING. DUCT
DIMe''IONS ARE EXTERIOR AND INCLUDE LINING - TYPICAL.
3 MOLT TOP OF THERMOSTAT ON WALL AT 46° APP. COORDINATE EXACT
MOtkd11w6 LOCATION 1^IITH ARCHITECT AND TENANT PRIOR TO ROUGH -IN. ALL
CONTROL WIRING SHALL BE INSTALLED IN CONDUIT PER NEC. MOUNT DUCT
SMGK.. DETECTOR TEST STATION ABOVE TlifERMOSTAT AND WIRE TO SMOKE
DETGTOR MOUNTED IN FAN POWERED TERMINAL RETURN AIR DUCTWORK
5 V'( EXACT SIZE, LOCATION, AND CONNECTION POINT TO F.XI511N6 LANDLORD
DMTHORK IN FIELD.
6 PRO - iDE OPENING WITI4 V2' MESH SCREEN IN RETURN AIR DUCTWORK ABOVE
GEIL ':. IN SALES AREA.
1 PHOrOSFGTWG DUCT SMOKE DETECTOR FIELD INSTALLED IN FAN POWERED
TER.: ; LAI_ RETURN AIR DUCT, WIRED TO SHUT DOWN UNIT UNDER ALARM. SEE
DETAIL THIS SHEET. ALL WIRING SHALL BE IN CONDUIT PER N. E. C.
'X' 14x14 AIR
® 7R P15FER DUCT
5
,,, CD-I, 10'0
260 CFM
TYP. (3)
MECHANICAL FLOOR PLAN
1/4" = I' -e)"
Mop -186
DEC 2 8 2007
PE 1 v s i CENTEB
1.4 1`77
�XP1RE5
CONTRACTOR MUST VERIFY
ALL CLEARANCES AND
DIMENSIONS IN FIELD
•
DATE
08- 11 -0'i
L EI
tin
el
F og
1 ; 4( 1
W
O �� ttn
ISSUE
BID/FERMIT
stride rite EOLM4 CSR
MECHANICAL
FLOOR
PLAN
M1
Project Info
Project Address Stride Rite South Center Mall Space #1300
Date 8/6/2007
633 South Center Mall
For Building Department Use
Tukwila, WA
Applicant Name: Eawara P- MCHgnry
Applicant Address: 25001 EfmezY Rd, warensville Efts -, Ohio 44128
Applicant Phone: 216- 292 --4696
Project Description
FPS /1
111 New Building ❑ Addition ❑ Alteration
IN Plans Included
Refer to WSEC Section 1513 for controls and commissioning requirements.
Compliance Option
Q Prescriptive Q Lighting Power Allowance 0 Systems Analysis
(See Qualification Checklist (over). Indicate Prescriptive & LPA spaces clearly on plans.)
Alteration Exceptions
(check appropriate box - sec. 1132.3)
N/A
STOCK
J No changes are being made to the lighting
Maximum limit per switch
• Less than 60% of the fixtures new, installed wattage not increased, & space use not changed.
Cooling Equipment Schedule
Equip.
ID
Brand Name'
Model No
Capacity'
Bluth
Total CFM
OSA CFM
or Econo?
SEER
or EER
IPLV1
Location
FPS /1
Titus
TQO -3 -10
N/A
1000
N/A
N/A
N/A
STOCK
Area controls
Maximum limit per switch
n.a.
Applicant Address:
25001 E mery Road, Warrensville
Hts.,
Ohio
44128
Applicant Phone:
216 -292 -4696
Combustion htg.
Indicate intermittent ignition, flue /draft damper &jacket loss
vertical glazing
Indicate vertical glazing on plans
1412
HVAC controls
yes
1412.1
Temperature zones
Indicate locations on plans
Ml
yes
yes
1412.2
Deadband control
Indicate 5 degree deadband minimum
M2
n.a.
1412.3
Humidity control
Indicate humidistat
(a) timer w /backup
yes
1412.4
Automatic setback
Indicate thermostat with night setback and 7 diff. day types
Ml , 52
(b) photocell.
n .a.
1412.4.1
Dampers
Indicate damper location and auto. controls & max. leakage
Fan Equipment Schedule
Equip.
ID
Brand Name'
Model No
CFM
Sp
HP /BHP
Flow Contra&
Location of Service
FPS /1
Titus
TQS -3 -10
1000
0.4"
1/4
vs
STOCK
17000
N/A
Area controls
Maximum limit per switch
n.a.
Applicant Address:
25001 E mery Road, Warrensville
Hts.,
Ohio
44128
Applicant Phone:
216 -292 -4696
Combustion htg.
Indicate intermittent ignition, flue /draft damper &jacket loss
vertical glazing
Indicate vertical glazing on plans
1412
HVAC controls
yes
1412.1
Temperature zones
Indicate locations on plans
Ml
yes
yes
1412.2
Deadband control
Indicate 5 degree deadband minimum
M2
n.a.
1412.3
Humidity control
Indicate humidistat
(a) timer w /backup
yes
1412.4
Automatic setback
Heating Equipment Schedule
Equip,
ID
Brand Name
Model No'
Capacity
8tu/h
Total CFM
OSA cfm
or Econo?
Input Btuh
Output Btuh
Efficiency'
FPS /1
Titus
TQS -3 -10
17000
1000
N/A
17000
17000
N/A
Area controls
Maximum limit per switch
n.a.
Applicant Address:
25001 E mery Road, Warrensville
Hts.,
Ohio
44128
Applicant Phone:
216 -292 -4696
Combustion htg.
Indicate intermittent ignition, flue /draft damper &jacket loss
vertical glazing
Indicate vertical glazing on plans
1412
HVAC controls
yes
1412.1
Temperature zones
Indicate locations on plans
Ml
yes
yes
1412.2
Deadband control
Indicate 5 degree deadband minimum
M2
n.a.
1412.3
Humidity control
Indicate humidistat
(a) timer w /backup
yes
1412.4
Automatic setback
Indicate thermostat with night setback and 7 diff. day types
Ml , 52
(b) photocell.
n .a.
1412.4.1
Dampers
Indicate damper location and auto. controls & max. leakage
Project Info
Project Address
Stride Rite South Center Mall
Space 41300
0 58
Date 8/2/2007
50 to 70 cal storage
633 South Center mall
0 71
711 gal sp,rarjp
f1 55
For Building Dept. Use
1513.1
Tukwila, WA
Equipment performance
n.a.
1411.4
Applicant Name:
adward P. McHenry
Area controls
Maximum limit per switch
n.a.
Applicant Address:
25001 E mery Road, Warrensville
Hts.,
Ohio
44128
Applicant Phone:
216 -292 -4696
Combustion htg.
Indicate intermittent ignition, flue /draft damper &jacket loss
vertical glazing
Mechanical Permit Plans Checklist . MECH =CHK
EF
CAE
is 50 gal storage
0 58
0 71
50 to 70 cal storage
0 57
0 71
711 gal sp,rarjp
f1 55
rI 70
Mechanical Permit Plans Checklist . MECH =CHK
20174 Washington State Nonresidential Energy Code Compliance Forms Revised May 2095
Project Address Stride Rite South Centex Mall Space 41300
Date 3/2/2007
The following information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the
Washington State Nonresidential Energy Code.
Applicability
(yes, no, n.a.)
Code
Section
Component
Information Required
Location
on Plans
Building Department
Notes
HVAC REQUIREMENTS (Sections 1401 -1424)
1513.1
1411
Equipment performance
n.a.
1411.4
Pkg. elec. htg.& clg.
List heat pumps on schedule
Area controls
Maximum limit per switch
n.a.
1411.
Minimum efficiency
Equipment schedule with type, capacity, efficiency
Daylight zone control
Schedule with type and features, indicate locations
n.a.
1411.1
Combustion htg.
Indicate intermittent ignition, flue /draft damper &jacket loss
vertical glazing
Indicate vertical glazing on plans
1412
HVAC controls
yes
1412.1
Temperature zones
Indicate locations on plans
Ml
yes
yes
1412.2
Deadband control
Indicate 5 degree deadband minimum
M2
n.a.
1412.3
Humidity control
Indicate humidistat
(a) timer w /backup
yes
1412.4
Automatic setback
Indicate thermostat with night setback and 7 diff. day types
Ml , 52
(b) photocell.
n .a.
1412.4.1
Dampers
Indicate damper location and auto. controls & max. leakage
1513.6
Inter. auto shut -off
n.a.
1412.4.2
Optimum Start
Indicate optimum start controls
Schedule with type and locations
n.a.
1412.5
Heat pump control
Indicate microprocessor on thermostat schedule
Schedule with type and features (back -up, override capability);
Indicate size of zone on plans
El
n.a.
1412.6
Combustion htg.
Indicate modulating or staged control
Commissioning
Indicate requirements for lighting controls commissioning
yes
1412.7
Balancing
Indicate balancing features on plans
Ml
Lighting Sum. Form
n.a.
1422
Thermostat interlock
Indicate thermostat interlock on plans
r1 - a• 1
1437
n.a
1423
Economizers
Equipment schedule
1413
Air economizers
n.a.
1413.1
Air Econo Operation
Indicate 100% capability on schedule
n.a.
1413.1
Wtr Econo Operation
Indicate 100% capacity at 45 degF db & 40 deg F wb
n.a.
1413 7
Water Fcono Doc
Indicate clg load & water econoe & clg tower performance
MI
n.a.
1413.3
Integrated operation
Indicate capability for partial cooling
n.a.
1413.4
Humidification Indicate direct evap or fog atomization w/ air economizer
1414
Ducting systems
yes
1414.1
Duct sealing
Indicate sealing necessary
51,52
yes
1414.2
Duct insulation
indicate Ft-value of insulation on duct
Ml,M2
n .a.
1415.1
Piping insulation
Indicate R -value of insulation on piping
1416
Completion Requirements
yes
1416.1 &2
Drawings & Manuals
Indicate requirement for record drawings and operation dots.
52
yes
1416 3,2
Air Balancing
Indicate air system balance requirements
Ml,M2
n.a
1416.3 .3
Hydronic Balancing
Indicate hydronic system balance requirements
yes
1416.4
Commissioning
Indicate requirements for commissioning and prelim. Report
52
yes W✓
1424
Separate air sys
Indicate separate systems on plans
M1
yes
Mechanical
Summary Form
Completed add attached. Equipment schedule with types,
input /output, efficiency, cfm, hp, economizer
52
SERVICE - WATER HEATING AND HEATED IDOLS - (S - actions 1440 - 14541 -
1440
Service water htg.
• a • 1441
Elec water heater
Indicate 8 -10 insulation under tank
1442
1443
Shut -off controls
Pipe Insulation
Indicate automatic shut -off
Indicate R -value of insulation oil piping
1452
Heat Pump COP
Indicate minimum COP of 4 0
.a. 1452
Heater Efficiency
Indicate pool heater efficiency
1453
Pool heater controls
Indicate switch and 65 degree control
. a . 1454
.a . 1A54
Pool covers
Indicate vapor retardant cover
Pools 90+ degrees
Indicate R -12 pool cover
Li ht In Permit•. Pla ns Checklist-
2004 Washington State Nonresidential Energy Code Compliance Forms Revi May 2005
Project Address Stride Rite South Centex Mall Space e1300
Date 8/6/2007
The following information is necessary to check a lighting permit application for compliance with the lighting requirements in the
2004 Washington State Nonresidential Energy Code.
Applicability
(yes, no, n.a.)
Code
Section
Component
Information Required
Location
on Plans
Building Department
Notes
LIGHTING CONTROLS (Section 1513)
yes
1513.1
Local control/access
Schedule with type, indicate locations
El
Strip Fluorescent
yes
1513.2
Area controls
Maximum limit per switch
El
0.2 W/ft
no
1513.3
Daylight zone control
Schedule with type and features, indicate locations
0.25 W /fl
no
Bldg. (by perim)
vertical glazing
Indicate vertical glazing on plans
no
overhead glazing
Indicate overhead glazing on plans
yes
1513.4
Displaylexhib /special
Indicate separate controls
El
1513,5
Exterior shut -off
Schedule with type and features, indicate location
(a) timer w /backup
Indicate location
no
(b) photocell.
Indicate location
-
1513.6
Inter. auto shut -off
Indicate location
no
1513.6.1
(a) occup. sensors
Schedule with type and locations
yes
1513.6,2
(b) auto, switches
Schedule with type and features (back -up, override capability);
Indicate size of zone on plans
El
1513.7
Commissioning
Indicate requirements for lighting controls commissioning
n• a.
Lighting Sum. Form
Completed and attached,
Schedule with fodure types,
lamps, ballasts, watts per fixture
r1 - a• 1
1437
Elec motor efficiency
MECH -MOT or Equipment Schedule with hp, rpm, efficiency
Location
(floor /room no.)
Occupancy Description
Allowed
Watts per ft2 -
Area in ft2
Allowed x Area
Retail
noen Lights
Retail
1.50
900.0
1350.0
2x2 Parabolic
7
80.0
560.0
Retail
Strip Fluorescent
7
58.0
406.0
Total Proposed Watts may not exceed Total Allowed Watts for Interior Total Proposed Watts
1337.0
0.2 W/ft
** From Table 15-1 (over) - document all exceptions on form LTG -LPA Total Allowed Watts
1350.0
Location
(floor /room no.)
Fixture Description
Number of
Fixtures
Watts/
Fixture
Watts
Proposed
Retail
noen Lights
7
53.0
371.0
Retail
2x2 Parabolic
7
80.0
560.0
Retail
Strip Fluorescent
7
58.0
406.0
Total Proposed Watts may not exceed Total Allowed Watts for Interior Total Proposed Watts
1337.0
Location
Description
Allowed Watts
per ft or per If
Area in ft2
(or If for perimeter)
Allowed Watts
x ft (or x If)
Covered Parking
(standard paint)
N/A
0.2 W /ft
Covered Parking
(reflective paint)
N/A
0.3 W /ft
Open Parking
N/A
0.2 W /ft
Outdoor Areas
N/A
0.2 W/ft
Bldg. (by facade)'
N/A
0.25 W /fl
Bldg. (by perim)
N/A
7.5 W /If
1. Choose either the facade area or the perimeter method, but not both) Total Allowed Watts
Location
Fixture Description
Number of
Fixtures
Watts/
Fixture
Watts
Proposed
N/A
Total Proposed Watts may not exceed Total Allowed Watts for Exterior Total Proposed Watts
20114 Washington State Nonresidential Energy Code Compliance Forms
Project Description
Briefly describe mechanical
system type and features.
El Includes Plans
2004 Washin• on State Nonresidential Ener. Code Compliance Form
Drawings must contain notes requireing compliance with commissioning requirements - Section 1416
Revised May 2005
Compliance Option
Simple System 0 Complex System 0 Systems Analysis
(See Decision Flowchart (over) for qualifications. Use separate MECH -SUM for simple & complex systems.)
Equi men
t Schedules The following information is required to be incorporated with the mechanical equipment schedules on the
Equipment plans. For projects without plans, ill in the required information below.
If available. As tested accord ng to Table 14 -1A through 14 -1G. ' f required 4 COP, HSPF, Combustion Efficiency, or AFUE, as
applicable. ' Flow control types variable air volume(VAV), constant volume (CV), or variable speed (VS).
umma
2004 Washington State Nonresidential Energy Code Compliance Forms
Maxim
Allowed Lighting Wattage (Interior)
Proposed Lighting Wattage (Interior)
2004 Washington State Nonresidential Energy Code Compliance Form
Maximum Allowed Lighting Wattage (Exterior)
Notes:
1. Use manufacturer's listed maximum input wattage. For hard -wired ballasts only,
the default table in the NREC Technical Reference Manual may also be used
2. Include exit lights unless less than 5 watts per fixture.
3. List all fixtures. For exempt lighting, not exception and leave Watts /Fixture blank.
f Vl IIALUI GJ riILII IICI U ^Yx11GU uc,laoLJ Vllly
Proposed Lighting Wattage (Exterior) the default table in the NREC Technical Reference Manual may also be used.
2004 Washington State Nonresidential Energy Code Compliance Form
no is circl f or any question, provide explanation:
Revised May 2005
If "no" is circled for any question, provide explanation:
Mechanical :- Permit Plans Checklist
2004 Washington State Nonresidential Energy Code Compliance Forms
MECH -CHK
Revised May 2005
Mechanical - General Requirements
1411.1 General: Equipment shall have a minimum performance at the
specified rating conditions not less than the values shown in Table 14 -1A
through 14.1G If a nationally recognized certification program exists for a
product covered in Tables 14.1A through 14.1G, and it includes provisions
for venflcanon and challenge of equipment efficiency ratings. then the
product Shall be listed in the certification program
Gas -fired and oil -fired forced air furnaces with input ratings ? 225,000
Bturh (65 kW) Shall also have an intermittent ignition or interrupted device
(IID), and have either mechanical draft (including power venting) or a flue
damper A vent damper is an acceptable alternative to a flue damper for
furnaces where combustion air is drawn from the conditioned space All
furnaces with input ratings , 225,000 Btu /h (65 kW), including electric
furnaces. that are not located within the conditioned space shall have
jacket losses not exceeding 0 75% of the input rating
14112 Rating Conditions: Cooling equipment shall be rated at ARI test
conditions and procedures when available Where no applicable
procedures exist, data Shall be furnished by the equipment manufacturer
1411 3 Com bination Space and Service Water Heating: For
combination space and service water heaters with a principal function of
providing space heat, the Combined Annual Efficiency (CAE) may be
calculated by using ASHRAE Standard 124 -1991 Storage water heaters
used in combination space heat and water heat applications shall have
either an Energy FAtter (EF) or e CAE of not less than the following
1411.4 Packaged Electric Heating and Cooling Equipm en : Packaged
electric equipment providing both heating and cooling with a total cooling
capacity greater than 20.000 Bluth shall he a heat pump
Exception: Unstaffed equipment shaelters or cabinets used
solely for personal wirvh.ss service tontines.
1412 Controls
1412.1 Temperature Controls: Fart syotern shall rr provided with at
leah,t one temperature nntrnllod by
individual thermostatic controls reap! ndlnq to temperature within the zone
At a minimum. each floor .:.r 9 I •:: ;1'tr._7 ehall sid "red n; e °ep,ti ate
zone
14122 Deadband Controls: , :rt II„,t:rlr_t
and cooling, zone tnelm,)S[atlt ,ii ti .i'. SYi ail biz dpat.i ^• lit a JeaJh,Em1 „ I
it . - i - t +,n.lrr - r ' . r. 'r. .:tri: rf h, , tic l.,n n r_rr r,I!in _jr.r. ,,
to the rime IS shut nit rodu! h, i minmr,ini
Exceptions:
1 ' :r!!:i,,l , :ul , .an , .v ' iiS 'tit- . r „h n•,1u v'•m fit
(.11, (n , .,,, h „I . ,tl: n,t itrfrIr.trtt .
F 1 1 1 1 , 1 1 1 1 ' t ' . , n l . , ' , I „ , . I , • ! .. 1 1 1 4 1 -t , Ir un ;n ■t n
,
I 1. tti It i 1. ,I. ;I .,,. Hit.] In G
5 e t i n , 1 l rt , + r . • r i t , am- I.• Int , •r . ahrr•. rt
ISenn „ ' ; ❑, •I , tai n,
1412.3 Hum idity Controls: I r
adding Itlnl'.tiire ,1 notionL .i,,i -.n an
1412.4 Setback and Shut -Off r
t .. I• „r, .1. ,.r , !li.
fir atir.rnai• .• fit rh.. ,
r.. nti..
Exceptions.
II I , ... ,.1.. „ ,n; ,
r ir I Ili ttr.irt r I I
IItr1
1412.4.1 Dampers: "ri 11. ti
Serving r,lri litlt "1 ., •., ,•. . ,' I it .. , ..1 it , I
dut„nl atl,,dily .r1,•-o ti„
Exceptions
I ,
1'1 :1 ,
• i J, n.
2 Padiant H
2004 Washington State Nonresidential Energy Code Compliance Form
2004 Washington State Nonresidential Energy Code Compliance Form
1412.4.2 Optimum Start Controls.
Start( 't t- .1771
adjust the ,(:+it tut,,. �i .u
de.sired,:,crui -1 t,.n,L,.r. n
occupan .0 111 � 1 1 1 1 „ ! : .. .' it III ,, ,
1412.5 Heat Pump Controls
mlrrr, ornr e ,_r,I , „ nti , tI -. 1 110171 ,. , . 1 fit
start up set up arro , 1r•rr • I '' I' ;, II 1
f I e, and a ,,, ,. I I „•111 r I
need ul ,.?t a ".,
L, 711411 111711 ,,l .-,b..,. , Na �• 1 � • , 7 "
visual moon :, f:. Lt I -,il ,t
1412.6 Combustion Heating Equipment Controls
e,4ulpmerl[ with d , opt„ I.,.. - -1 _ . I !' to , i, ,i l ;.,
staged
Exceptions
711111'1711 7.7177 , I 7 777771 11
,
I ., •,,, I II i
, Inn, II
.
771,111 r
a ant ng: act air supply outlet or air or water termina evice
shall have a means for balancing, including but not limited to. dampers.
temperature and pressure test connections and balancing valves
1413 Alr Economizers
1413.1 Operation: Air economizers shall be of automatically modulating
outside and return air dampers to provide 100 percent of the design supply
an as outside air to reduce or eliminate the need for mechanical cooling
Water economizers shall be capable of providing the total concurrent
cooling load served by the conneted terminal equipment lacking airside
economizer, at outside air temperatures of 45 ° F dry- bulb /40 ° F wet -bulb
and below For this calculation, all factors including solar and internal load
shall be the same as those used ter peak load calulations, except for the
outside temperatures
Exception Water economizers using air•cooied heat retechon
equipment may use a 35 ° F dry-bulb outside air temperature for
this calculation This exception is limited to a maximum of 20 tons
per building
1413.2 Documentation: Water economizer plans submitted for approval
shall include the following information
1 Maximum outside air conditions for which economizer is sized to
provide full cooling
2 Design cooling load to be provided by economizer at this outside
air condition
3 Heat rejection and terminal equipment performance data
including model number, flow rate, capacity. entering and leaving
temperature in full economizer cooling mode
1413.3 integrated Operation: Air economizers shall be capable of
providing partial cooling even when additional mechanical cooling is
required to meet the remainder of the cooling load
E xceptions:
ndividual, direct expansion units that have a rated capacity
less than 65,000 Btu /h and use nonintegrated economizer
controls that preclude simultaneous operation of the
economizer and mechanical cooling
2 Water-cooled water chillers with waterside economizer
1413.4 Humidification: If an air economizer is required on a cooling
system hit which humidification equipment is to be provided to maintain
minimum indoor humidity levels, then the humidifier shall be of the
adiabatic type (direct evaporative media or fog atomization type)
Exceions:
I He care facilities where W AC 246- 320 -525 allows only
steam injection humidifiers in ductwork downstream of final
niters 1412 b combustion Heanng Equipment Controls
c , m buntn: , n heating equipment with a capacity over 225.000
hitlilh shall have modulating or staged combustion control
'Svstrms with water economizer
n x r air systems with no provisions for air
z',' irrulation to the central supply fan
,1 y „nr,d:,- il.abr humidifiers cumulatively serving no more than
Irla at a building's air eronomlrer capacity as measured in
.'nn Thy, r,•fers to the system cfm serving rooms with Stand
alone pr duct mounted humidifiers
1414 Ducting Systems
1414 1 Sealing .••,h rrhm ll i•, dn'.uined to nperzte at pressure'.
it. , • I:' III I, w,itr - r '' -iurnn static pressure shall be sealed in accordance
r 1'. C -tent :,f sealing required is as follows
I,tti t•i„.;ure 1 ,n r1 to 2 inches, seal transverse joints
. .. ' :n.: hoc to ?.:riches. seat all transverse joint.
-rid 1. mgitl,dinai seams
.r. iii. I fi1' ih ;P A man es, seal all transverse joints
duct wall r,enarretlnn5
1 - . pt. r ;ensltive tape shall not be used as the
r„ . • , , , l 1: 0 '.17 .., „ , t y„- , I"i , iric , J t0 OpPf ale et static pteSSiirCS of
1414 2 Insulation: L' o and pieriums that are constructed and function
11 .,, .,In, .•n , .Int , .' I r•pdrating Interior s kat e line e xtefidi
,i n,,.,. iii i,, do p',Ir• rarl4 from ants or r nar lz I vas e
lI „r1 ln'.t.,llehr,n moisture COi air leakage,
=l .. I Inheated agwpment rooms with
■ inir.t tie isolated from the conditioned space by
I mrur i =..,iI 1, r•s Ina mmirnum of R -11 and any exterior
' i:r'' , I , , , rialger I hillside air ducts serving individual
.I,r unit . wittl I'•', S tri::ri , 011IJ rim of total supply air capacity shall be
I ^I "„ iI
III I are not considered building envelope
r, .., r, -I ,iii i1:- I Ilia; ,, le considered building envelope until they,
, I I„ I l,r- IF-'n,nil ,If 11111 . 11111p R,'llt ur
,,
.L,t. till uii exterior with an automatic shut-off damper
1. .• , .,t,i , l. an hicts n,ae[ tine above listed requirements. runs
•i lih•11 a =1',, ., art ,1u rim ply with Table 14 -5 requirements
1 . I r ..(•( i.lrnu ,ndll be thermally insulated per Table 14 -
Exceptions -
1 till: HVAC argllirimanl
. r 1 1u t iii .1u, t, 11,4 sublet to condensation
! r •! •:1 - :i �:c•rF rnithul a zone that serves that zone
1415 Piping Systems
1415.1 Insulation ,r,.ill tie thermally insulated In accordance with
Exception . r l In•,lall, within unitary HVAC equipment
'' .IL•r la! c•utsia the ienditioned space shall be insulated in
'dv ashinghm State Plumbing Code (W AC 51 -26)
1416 Completion Requirements (Refer to NREC 'Electron 1416 and the
1'r„ ; r mnri r ;tndef.es. Orrblished by lie Building
vzorcraiion. for complete !eV and guideiines for building
I. ii,,. , . ;roving requirements I
Mop - 28 G
�3, ... c ltt
DEC 2 8 2007
PERMiT CENTEF
CONTRACTOR MUST VERIFY
ALL CLEARANCES AND
DIMENSIONS IN FIELD
DATE
08 -17 -01
ZI
0
'tf
BID/ PERMIT
tends rlta ep./114 CetTER
MECHANICAL
ENERGY CODE
FORMS
M2
ISSUE
GENERAL INFORMATION
SPECIFICATIONS
A 6EtNBRAL
I. CONFORM TO ALL GRAIL AND SPECIAL CONDITIONS OF CONTRACT AS
SF'EGIFIED SY ARCI-HTEGT, TIENANT MD OWNER
2. SFECIPIGATIONS ARE AFFLIGASLE TO ALL CONTRACTORS MP
BE ONTRAGTORS FOR hEGHANIGAL AND ELECTRIGAL SYSTEE S.
3. GONTRACTOR SHALL COMPLY WITH LANDLORDS STANDARDS, FAGWTY
SPECIFICATIONS, RILES AND RESUATIONIS. ALL LANDLORD
CRITERIA SHALL BE CONKED WITH AND INCLUDED IN THIS BID.
CHECK OTHER PLANS AND SPEGIFIGATIONS AND FULLY COORDINATE
WITH OTHER TRADES AND ARCHITECT'S REQUIREMENTS.
4. VISIT SITE, CHECK FACILITIES AND CONDITIONS, AND VERIFY ALL
UTILITY COMPANY REQLJIREMIENTS AND CONNECTION POINTS IN FIELD
PRIOR TO STARTING WORK TAKE ALL ITEMS INTO CONSIDERATION
IN BID.
5. SYSTEMS ARE TO BE COMPLETE AND WORKABLE IN ALL RESPECTS,
PLACED IN OPERATION AND PROPERLY ADJUSTED.
6. EACH CONTRACTOR SHALL PROVIDE FOR HIS OWN CLEAN -UP, REMOVAL
AND LEGAL DISPOSAL OF ALL RUBBISH DAILY.
1. ARRANGE FOR AND OBTAIN LANDLORD'S AND INEURAJNGE
REPRESENTATIVES EMISSION FOR ANY SERVICE SHIJTDOMLS.
SHUTDOPES MST BE PERFORM? WITHOUT DISRUPTION TO FACILITY
OPERATIONS, AS SCHEDULED WITH 11-E LANDLORDS REPRESENTATIVE
INCLUDE ANY PREMIUM TIME REGIJIRED IN BID.
S. TIE CONTRACTOR SNAIL DE SOLELY RESPONSIBLE FOR CONSTRUCTION
MEANS, METHODS, SEMENCE OF CONSTRUCTION AND TIE SAFETY OF
WORKMEFL COMPLY WITH ALL OSHA RESU.ATION5.
q. NO PIPING, DUCTWORK, CONTROLS, ETC., SHALL BE INSTALLED OR
ROUTED ABOVE ELECTRICAL PANGS AND EQUIPM
10. THE MECHANICAL AND ELECTRICAL CONTRACTORS SHALL COORDINATE
TILE E.EGT REGAL CHARACTEJJ5TIGS OF ALL MECHANICAL E IIIRENT
PRIOR TO ORDERING OF ECEIPM E NT. NO ADDITIONAL PAYMENT WILL
BE MADE FOR LACK OF CONTRACTOR COORDINATION OF ELECTRICAL
CHARACTERISTICS.
II. CEILING PLENUM 15 UTILIZED AS A RETURN AIR FLEW. ONLY
PLENUM RATED MATERIALS WILL BE PERMITTED.
12. ALL MECHANICAL AND ELECTRICAL SYSTEM COMPONENTS SHALL BE
ROUTED TIGHT TO UNDERSIDE OF STRUCTURE AND THROUGH JOISTS OR
TRUSSES I POSSIBLE. COORDINATE INSTALLATION TO PRESERVE
HEADROOM, EQUIPMENT ACCESS, AND ARCHITECTURAL CLEARANCES FOR
FINISHES, INCLUDING CEILING HEIGHTS. COORDINATE WITH ALL
OTHER TRADES AND DO NOT CONFLICT WITH TINE ARCHITECTURAL
REQUIRBN-NT5 FOR 11-E FINISHED CONSTRUCTION. PROVIDE OFFSETS
h1-ERE REQUIRED TO COORDINATE WITH OTHER TRADES.
13. REFER TO ARCHITECTURAL RkFLEGTID GEILING PLANS FOR LOCATIONS
OF ALL GRILLES AND DIFFUSERS.
B. CODES, STANDARDS AND REGULATIONS
L CONFORM TO ALL APPLICABLE GODES, GOVERNMENT REGULATIONS,
UTILITY COMPANY RE MRENEENTS, AND NATIONAL ELECTRICAL CODE
2. OBTAIN PERMITS AND PAY ALL FEES. ARRANGE FOR ALL REQUIRED
INSPECTIONS AND APPROVALS.
C. RELATED WORK SPEGIFIED E
I. OPENINGS AND CHAS WHEN SHOWN ON ARCHITECTURAL DRAWINGS.
P. DRAWINGS
I. THE SYSTEMS AS SHOWN ON THE CONTRACT DRAWINGS ARE
DIAGRAMMATIC.
2. II4E INTENT 15 FOR COMPLETE AND WORKABLE 5Y5TB'S. TIE
DRAWINGS AND THESE NOTES ARE TO BE USED TAR AS A BASIS
OF SHOWING AND /OR DESCRIBING THE SYSTEM REQUIREENTS FOR THE
FACILITY.
3. VERIFY ALL DIMENSIONS AND CLEARANCES BY FIELD ME SA RIME NT
AND GH'JCK FOR INTBNGFS PRIOR TO 5TART1N6 WORK.
E BASE EQUIPMENT AND MATERIALS AND SUBSTITUTIONS
I. ALL EQUIPMENT AND MATERIALS SHALL BE MA FREE OF DEFECTS
AND UL. LABELED.
2. SUBMIT SHOP DRAWINGS FOR ALL EQUIPMENT, FIXTURES, ETC.,
INCLUDING ALL ACCESSORIES TO BE FURNISHED. BASE BID
MANFACTURERS MD MODELS ARE INCLUDED IN SPECIFICATIONS OR
LISTED IN SCHEDULE ON DRAWING. ANY OTFER MANFAGTURER OR
MODEL 15 A SUBSTITUTION.
3. SUSSTIMIONS ARE SUE3.JEGT TO THE APPROVAL OF THE OWNER AND
SHALL BE LISTED ON THE FORM OF PROPOSAL FOR THE OWNERS
CONSIDERATION PRIOR TO CONTRACT AWARD. IF SUBSTITUTION 15
SUBMITTED, IT 15 THE CONTRACTORS RESPONSIBILITY TO EVALUATE
IT AND CERTIFY THAT THE SUBSTITUTION 15 EQUIVALENT IN ALL
RESPEGTS TO THE BASE SFEGIFIGATEONS.
4. IF SUBSTITUTIONS ARE APPROVED, NOTIFY ALL OTHER CONTRACTORS,
SUBCONTRACTORS OR TRADES A FEGTEJ BY SUJESTIIUTION AND FULLY
COORDINATE ANY COSTS REBATING FROM SUBSTITUTION, II-ETHER
BY CONTRACTOR OR OTHERS, SHALL SE RESPONSIBILITY OF AND PAID
FOR BY 51)SSTITUTIN6 CONTRACTOR
5. ALL EEQJIPNIBNT SHALL SE INSTALLED IN FILL ACCORDANCE KITH THE
MANJFAGTURER'S INSTALLATION INSTRUCTIONS. IT 15 THIS
CONTRACTOR'S RESPONSIBILITY TO CHECK AND CONFORM TO THESE
REGURENENTS PRIOR TO START1N6 WORK
F. CHECK„ TEST, START, ADJUST, BALANCE AND INSTRUCTIONS
I. AFTER INSTALLATION, CHECK ALL EQUIPMENT, AND PERFORM START
UP IN ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS.
2. ALL PIPING SHALL BE TESTED AND FREE OF LEAKS.
3. BALANCE ALL SYSTEMS, CALIBRATE CONTROLS, CHECK FOR PROPER
OPERATING SEQUENCE UNDER ALL CONDITIONS, AND MAKE ALL
NECESSARY ADJUSTMENTS.
4. ALL WIRING SHALL BE FILLY TESTED AND MADE FREE OF GROUNDS
AND SHORT CIRCUITS.
5. INSTRUCT OM ER IN OPERATION OF SYSTEMS AND SUBMIT OPERATING
AND MAINTENANCE MANUAL ON ALL EQUIPMENT AND SYSTEMS.
b. PROVIDE ENGRAVED LABELS AND IDENTIFICATION TAGS FOR ALL
PIPING SYSTEMS, VALVES AND EQUIPMENT.
1. PROVIDE TYPED PANNE_ DIRECTORIES AND ENGRAVED LABELS FOR ALL
PANES AND EQUIPMENT.
G. GUTTING, PATCHING AND DRILLING
I. ALL CUTTING AND CHASING OF THE BUILDING CONSIRUGTION
REQUIRED FOR THIS WORK SHALL BE BY THIS CONTRACTOR UNLESS
514044 ON ARCHITECTURAL DRAWINGS AND CONFIRMED AS TO SIZE AND
LOCATION PRIOR TO NE N CONSTRICTION. CUTTING SHALL BE IN A
NEAT AND WORKMANLIKE MANNER.
2. NEATLY SAW CUT ALL RECTANGULAR OPENINGS, SET SLEEVE THROUGH
OPENING, AND FINISH PATCH OR PROVIDE TRIM F!}4NGE AROUND
°PENLNS.
3. CORE DRILL AND SLEEVE ALL ROUND OPENINGS.
4. DO NOT CUT ANY STRUCTURAL COMFOFENTS WITHOUT ARCHITECTS
APPROVAL.
5. PATCH AND FINISH TO MATCH ADJACENT AREAS THAT HAVE BEN GUT,
DAMAGE) OR MODIFIED TO INSTALL EIJI'MENT FOR THIS PROJECT.
6. FIRE STOP ALL PENETRATIONS OF FIRE RATED CONSTRUCTION IN A
CODE APPROVED MANNER, USING IL LISTED FIRE RATED MATERIALS.
1. ALL GOt4TRACTOR5 SHALL CONFIRM WITH O S R, PRIOR TO BID,
TIMES AVAILABLE FOR NOISE PRODUCING WORK SUCH AS CUTTING AND
CORE DRILLING OF FLOORS, WALLS, ETC., AS PE LL AS TIMES FOR
WORK WHICH REQUIRE ACCESS INTO ADJOINING AREAS. INCLUDE ANY
PREMIUM TIME REQUIRED IN BID.
H. WARRANTY
I. FULLY WARRANT ALL MATT521ALS, EQUIPMENT AND WORKMANSHIP FOR
ONE (I) YEAR FROM DATE OF ACCEPTANCE.
2. EXTE V ALL MANUFACTURERS WARRANTIES TO OWNER
3. REPAIR OR REPLACE 4THGUT CHARGE TO THE OWtER ALL ITEMS
FOUND DEFECTIVE DURING THE WARRANTY PERIOD.
MECHANICAL 5YSTE 5
FIRE PROTECTION SPRINKLER SYSTEM
A SCOPE
I. FURNISH ALL LABOR, MATERIALS AND ECIU FM ENT AS REQUIRED TO
INSTALL COMPLETE FIRE PROTECTION SYSTEM FOR PROJECT.
2. SPRINKLER WORK FOR PROJECT ESSENTIALLY CONSISTS OF THE
FOLLOWING:
A. EXTEND FIRE PROTECTION SYSTEM FOR TENANT SPACE FROM
EXISTING F=IRE PROTECTION 5Y5TBy1, GAPPED STUB OUTS BY
LANDLORD.
B. FIRE PROTECTION SYSTEM FOR ALL AREAS OF 1W PRO..EGT.
C. PREPARE SUBMITTAL DRAWINGS AND HYDRAULIC CALCULATIONS
IN ACCORDANCE 41H OWNERS INSURANCE COMPANY, BUILDING
DEPARTMENT, AND LOCAL FIRE AUTHORITY'S REQUIREMENTS AND
SUBMIT TO LANDLORD AND LOCAL AUTHORITY HEAVING
.JURISDICTION FOR APPROVAL.
D. FLUSH Alm CONDUCT PRESSURE TEST OF COMPLETED SYSTEM IN
ACCORDANCE WITH FFIPA AND AUTHORITIES HAVING
JURISDICTION.
E. OTHER ITEMS INDICATED ON DRAWINGS OR REQUIRED FOR
COMPLETE INSTALLATION.
B. DESIGN BASIS
I. DE5I6N BASIS FOR SYSTEM SHALL BE PER ALL APPLICABLE NFPA
STANDARDS, INCLUDING, BUT NOT LIMITED TO, BULLETINS 13 AND
30, BOIL PING CODE, INSURANCE UND132NRITER, AND FIRE MARSHAL
RE UIRHENTS. SYSTEM SHALL BE A HYDRAULICALLY DESIGNED
SYSTEM.
C. DRAWINGS MD CALCULATIONS
I. CONTRACTOR SHALL PREPARE SUSMITFAL DRAWING AND HYDRAULIC
CALCULATIONS FOR SPACE IN ACCORDANCE WITH OPENERS INSURANCE
COMPANY AND BUILDING DEPARTMENT RECJIREhENT5.
2. CONTRACTOR SHALL OBTAIN FLOW TEST DATA ON GITY WATER MAIN
AND SUBMIT DATA WITH CALCULATIONS. PERFORM FLOW TEST IF
ACCURATE RECENT DATA 15 NOT AVAILABLE
3. CONTRACTOR AND PESIENBR SHALL BE STATE CERTIFIED.
4. CONTRACTOR SHALL INSTALL ALL SPRINKLER PIPING AS HIGH AS
POSSIBLE, TIGHT TO UNDERSIDE OF STRUCTURE, AND THROUGH
JOISTS OR TRUSSES WHERE POSSIBLE WITH DRAINS AND OFFSETS
BELCH BEAMS. SPRINKLER CONTRACTOR SHALL COORDINATE
SPRINKLER SYSTEM WITH DUCTWORK AND LIEHTTS. ALL COSTS
ASSOCIATED WITH RAISING SPRINKLER PIPING 4-ERE THE
ARCHITECTURAL DESIGN CANNOT BE ACCOMPLISHED SHALL BE THE
RESPONSIBILITY OF 11-E SPRINKLE CONT AAGTOR
D. PIPING
I. ALL PIPINS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
REQUIREMENTS AND FM APPROVED.
2. FIRE PROTECTION PIPING SHALL BE AS FOLLOWS:
A. INSIDE BUILDING - PIPE AND TUBING SHALL BE 5TIEi OR
COPPER IN ACCORDANCE WITH THE LATEST ACCEPTED EDITION
OF NFPA -I3.
B. PIPING SHALL MATCH EXISTING BUILDING STANDARDS.
C. CONTRACTOR SHALL ARRANGE FOR S-IlTDOWN OF EXISTING
SYSTEM WITH LANDLORD, OWNER AND INSURANCE UNDERN&ITER.
D. FLUSH ALL PIPING UPON COMPLETION OF PROJECT AND TEST
PER NFPA 13.
E. PLASTIC, PIPING 15 NOT APPROVED.
E SPRINKLER HEADS
I. SPRINKLER HEADS SHALL BE 1/2' ORIFICE, K=5.6, 165 DEGREE5 F,
U.L. LISTED, AND SHALL MATCH t ISTING BUILDING STANDARDS.
2. SPRINKLER HEADS SHALL SE AS FOLLOWS:
A. AREAS WITH EXPOSED STRUCTURE
I. UPRIGHT - ROUGH BRASS SPRINKLER HEAD.
S. AREAS WITH CEILINGS
I. FLUSH SPRINKLESR - FLUSH SPRINKLER HEAP WITH
OFF- H-111E CEILING DISC PER LANDLORD REQUIREMENTS.
3. INSTALL HIGHER. TEMPERATURE SFRINKLER HEADS WIND REQUIRED BY
CODE OR APPLICATION AND QUICK RESPONSE HEADS IN LIGHT HAZARD
OCCUPANCIES.
4. SUBMIT SAMPLES OF SPRINKLER HEADS TO ARCHITECT PRIOR TO
FABRICATION OF ANY PIPING.
5. SPRINKLER. HEADS SHALL BE CENTERED IN THE CEILING GRID IN
B0114 DIRECTIONS.
F. VALVES
I. INSTALL ALL VALVES REGIJIREEP BY NFPA 11-11C14 ARE TO LISTED
AND FM APPROVED.
2. ALL SHUT -OFF VALVES SHALL SE FITTED WITH TAMS SWITCHES BY
FIRE PROTECTION CONTRACTOR AND WIRED BY LEGTIRICAL
CONTRACTOR.
HEATING, VENTILATING AND AIR CONDITIONING
A SCOPE
I. FURNISH ALL EQUIPMENT, MATERIALS, LABOR, TOOLS, ETC., FOR
1W CONFL.ETE HVAC SYS7!E1. INSTALL COMPLETE AND PLACE IN
OPERATION.
2. HVAC SYSTEM ESSENTIALLY C0FL515T5 OF TW FOLLOWING:
A. FAN POPERED VAV TERMINAL UNIT.
B. DUCTWORK, GRILLES, DID AND OTTER ACCESSORIES.
C. INSULATION OF HVAC ITEMS.
D. BALANCING, TESTING AND START UP.
E. TEMPERATURE CONTROL 5, VT1EM.
F. OTHER ITEMS INDICATED ON DRAWINGS OR REWIRED FOR
COMPLETE INSTALLATION.
B. DUCTWORK
I. FABRICATE AND ERECT ALL DUCTWORK TO ASHRAE MD SMAGNA
STANDARDS FROM NO. I GALVANIZED STEEL COMPLY WITH SMACHA
STANDARDS, AND NFPA E L LETIN qoA REEQUIRaENTS.
2 DUCTWORK DOWMLSIREAM OF VAV TERMINALS SHALL BE SMAGNA LOW
PRESBRE CONSTRICTION 2' STATIC PRESSURE RATING WITH SEAL
GLASS B SEAM AND JOINTS.
3. DUCTWORK UPSTREAM OF VAV TERMINALS SHALL SE SMACNA MEDIUM
PRESSURE GONSTRUUCTION 3 STATIC PRESSURE RATING WITH SEAL
CLASS A SEAMS AND JOINTS SEALED 111TH EG-800 GOMPCU4D OR
SIMILAR. ALL FITTINGS SHALL BE CONICAL TYPE
4. ALL DUCTWORK SHALL BE INSTALLED 16H r TO UNDERSIDE OF ST EL
OR TO HEIGHT AS INDICATED ON PLANS.
5. FLEXIBLE DUCTS SHALL BE INDEPENDENTLY SUPPORTED FROM THE
STRUCTURE AND CONNECTED WITr+ METAL DRAW BANDS. FLEXIBLE
DUCTS SHALL BE LIMITED TO 60' STRAIGHT LENGTHS AND ARE NOT
PERMITTED IN ROOMS WITHOUT CEILINGS. FLEXIBLE DUCTS SHALL
BE ATCO REBBR TYPE 010, I I/2' INSULATION AND RATED AT 10'
WL. FOR SIZES THROUGH IT, U.L. LISTED, AND MEET 2550
LAME AND SMOKE TEST. NO INTERIOR COLOR OTTER THAN BLACK 15
PERMITTED FOR FLEXIBLE DUCTS. EQUIVALENT BY VALUREX, FLEX-
AIRE, FLEXIBLE TECHNOLOSIES, TH ERMAFLEX OR GENFIEX
b. INCLUDE ALL TURNING VANES, MANUAL DAMPERS, FLEXIBLE
CONNECTORS, GRILLE'S AND DIFFUSERS, ACOUSTIC LINING, AND
MILER SHEET METAL ACC FOR THE PROJECT. VOLUME
DAMPERS TO BE OF OPPOSED BLADE GONSTRUGTIOfiN HITH LOCKING
QUADRANTS. PROVIDE VOLUME DANFERS AT SUPPLY AIR RUNOUTS TO
ALL CEILING DEFRJSERS.
7. ALL BRANCH CONNECTION FITTINGS IN RECTANGULAR DUCTWORK SHALL
BE 45 DEGREE TRANSITION TYPE, CONICAL FITTIN65 OR SPIN -IN
FITT1N65 WITH INTEGRAL AIR SCOOPS. E3UTT FITTINGS ARE NOT
ACCEPTABLE.
8. AGOUSTIG LINE ALL REGTANSULAR DUCTS INDICATED ON DRAWINGS
4TH MINIMUM ONE (I) INCH THICK NON - FLAKING, COATED MEDIUM
DENSITY LIFER APPLY TO MANUFACTURERS RECOMMENDATIONS.
DUCT DIMENSIONS ARE OUTSIDE DIMENSIONS, AND INCLUDE ACG4 11G
LINING.
C. INSULATION
I. THE FOLLOWING DUCT SYSTEM SHALL BE INSULATED WHERE CONGEALED
ABOVE CEILINGS WITH I -I/2' THICK FOIL FACED REINFORCED KRAFT
.JACKET FIB DUCT WRAP:
A. UNLINED SUPPLY AIR DUCTS, INCLUDING SACKS OF CEILING
DIFFUSERS.
2. INSULATION SHALL BE FULLY SECURED TO DUGTIMORK. LAP $ TAPE
SEAMS AND SECURE TIGHTLY TO DUCTS WITH ARE OR STICK PINS.
3. ALL INSULATION TO SE APPLIED IN FULL ACCORDANCE WITH THE
MAN /FACTMBES CATIONS. ALL INSULATION SHALL COMPLY
WITH 2550 FLAB AND SMOKE HAZARD RATINEf PER ASTM E-84,
NFPA 255 AND UL 723.
D. EQUIPMENT
I. HVAC CONTRACTOR TO FURNISH ALL HVAC EQUIPMENT INDICATED
AND /OR SCHEMED ON THE DRA"IIF S COMPLETE WITH BASES,
ISOLATORS, SUPPORTS AND OTTER REQUIRED ACCESSORIES.
2. INSTALL COMPLETE AND PLACE IN PROPER OPERATION PER
MANUFACTURERS RECOMMENDATIONS, DATIONS, LUBRICATE AND ADJUST AS
'REQUIRED.
3. EGIAPNENT TO BE MAKE AND Mora_ AS 5GH®UIED UNLESS OWNER
APPROVED, !EQUIVALENT QUALITY AND FE FOR AN E EQUIPMENT 15
SUBMITTED AS SUESTITUTION. ALL SUBSTITUTIONS SUB.. EGT TO
ACCEPTANCE MTHOUT QUALIFICATION BY OWNER, LANDLORD AND
ARCHITECT.
4. CONTRACTOR TO OBTAIN VAV DEVICE SET (5) FROM LANDLORD
E BALANCING, START UP AND INSTRUCTIONS
I. AF=TER INSTALLATION AND ECIPM®NT IS PLACED IN OPERATION,
HVAG CONTRACTOR 15 RESPONSIBLE FOR BALANCING SISTINE/ TO
DEIGN FLOW NTH REPORT SUBMITTED TO OWNER. BALANCING SHALL
FEE PERFOR4ED BY AN INmEF'EJDENT AMC OR N EM CERTIFIED
SUBCONTRACTOR
2. START UP AHD PLACE ALL SYSTEMS IN OPERATION AND TAG ALL
SWITCHES AND CONTROLS NTH PERMANENT LABELS.
3. INSTRUCT OWNER ON PROPER OPERATION AND MAINTENANCE OF
SYSTEM.
F. CONTROLS
I. FURNISH MD INSTALL ALL CONTROLS FOR HVAC SYSTEMS. PROVIDE
ALL RELAYS AND DEVICES REQUIRED FOR COMM OPERATION.
MOUNT ALL CONTROLS WRNISHED AS ACCESSORIES TO EQUIPMENT AND
PROVIDE ALL CONTROL (LOW VOLTAGE) WIRING OR POWER WIRING
REWIRED FOR CONTROL SYSTEM WHERE NOT SPECIFICALLY SHOWN ON
ELECTRICAL PLANS. ALL POWER WIRING AND EXPOSED CONTROL
WIRING SHALL BE IN EMT CONDUIT. CONCEALED CONTROL WIRING IN
CEILING PLEI'LJMS MAY BE IL LISTED PLENUM RATED GABLE NEATLY
SUPPORTED IN WIRE RUNES. ALL CONDUIT SHALL BE INSTALLED PER
N.E.C.
2. SMOKE CONTROL
MECHANICAL CONTRACTOR SHALL FURNISH, INSTALL AND WIRE A
PHOTO - ELECTRIC DUCT SMOKE DETECTOR AND REMOTE TEST SWITCH
AND ALARM AT EACH FAN POWERED TERMINAL TO SHIT DOWN FAN ON
ALARM. REFER TO DETAIL OH DRAWING. LOCATE ALARM MD TEST
SWITCH PER FIRE MARSHALS DIRECTION.
3. NO TI-ER405TATS SHALL BE INSTALLED ABOVE ANY FEAT PRODUCING
EMIR -ENT.
4. CONTROL SEMENGE SHALL SE AS FOLLOWS:
A. FR3-I CONSTANT VOLUME FAN POWW TERMINAL - THERMOSTAT
SHALL MODULATE VAV DAMPf32, SUPPLY AIR FAN, AND ELECTRIC
DUCT HEATER TO MAINTAIN SPACE SET POINT. VAV DAMPER
SHALL OFEN AND FAN SHALL RUN CONTIM CUSLY DURING ALL
OCCUPIED HOURS. VAV DAMPER SHALL CLOSE AND FAN AND
ELECTRIC HEATER SHALL CYCLE TO MAINTAIN SPACE HEATING
SET POINT DURING/ UNOCCUPIED HOURS. VAV DAMPER SHALL
CLOSE TO 1-WHIM POSITION, FAN SHALL OPERATE, AND
ELECTRIC HEATER SHALL CYCLE TO MAINTAIN SPACE SET POINT
IN HEATING MODE. VAV DAB AND SUPPLY AIR FAN SHALL
MODULATE TO MAINTAIN SPACE SET POINT AND CONSTANT AIR
VOLUME DURING OCCUPIED HOURS IN COOLING MODE
ELECTRICAL SYSTEM
A SCOPE
I. INCLUDE ALL LABOR, E;TIJIPMENT, TOOLS AND MATERIALS FOR
R P(TRIG DISTRIBUTION, AS SHOEh4I ON DRAWINGS.
2 EXTEND NEW POWER SERVICE TO SPACE AS SHOWN ON DRAWINGS
THROUGH A 120/208 VOLT, 3 PHASE, 4 WIRE LANDLORD
SWITCHYARD.
3. ALL BEGTWGAL WORK, INCLUDING POKIER WIRING FROM PANEL IN
BUILDING AND HIRING Cr OTI ER 111515 INDICATED.
4. FURNISH AND INSTALL NEW LIGHTING, SE Y AND EXIT
LIGHTING AS INDICATED ON PRA/1M5.
5. PROVIDE FACILITIES FOR A NEW TELPHONE 9ERVICEE.
S. PROVIDE A MANUAL FIRE ALARM SYSTEM AS 51401 44 ON DRAWINGS.
I. OTHER ELECTRICAL ITEMS INDICATED ON DRAWINGS OR REQUIRED FOR
COMPLETE INSTALLATION, INCLUDING SOUND AND ANNUNCIATOR
SYSTEM.
S. ANY INSTALLATION COSTS ASSaSED BY UTILITY COMPANIES FOR
INCOMING SERVICE INSTALLATION SHALL BE INCLUDED IN BID AND
PAID FOR BY THE ELECTRICAL CONTRACTOR-
13. CONDUIT INSTALLATION
I. ALL WIRING TO BE INSTALLED IN CONDUIT IN ACCORDANCE WITH TEE
N.E.C. AND SO THE REQUIRED CONDUCTORS MAY BE PULLED WITHOUT
INJURY OR STRAIN AND PROPERLY SUPPORTED. INCREASE CONDUIT
TRADE SIZE AS RECIRED FOR LONG FULLS ABOVE MINIII.JM REQUIRED
SIZE
2. ALL CONDUIT SHALL BE ROUTED TO EVE HEADROOM, EQIJIPPMEMT
ACCESS, AND ARCHITECTURAL CLEARANCES FOR FINISHES, INCLUDING
CEILING HEIGFfTS WITHOUT ADDITIONAL CLARIFICATION.
COORDINATE HITH ALL 011-ER TRADES 50 THAT CONDUIT RUNS DO NOT
BLOCK ARCHITECTURAL REQUIREMENTS FOR FINISHED CONSTRUCTION.
3. ALL CONDUITS TO BE CONGEALED IN BUILDING FEN CONSTRUCTION
11-ERE AVAILABLE.
4. EXPOSED CONDUIT MAY BE RUN ON EXISTING MASONRY WALLS IN
EQUIPMENT ROOMS. VERIFY ALL LOCATIONS WITH OWNER PRIOR TO
RC J&I BIN.
5. INTERIOR WIRING TO SE INSTALLED IN EECTRIGAL METALLIC
TUBING EE1T) WITH STS SET SCREW TYPE COUPLINGS AND
CONEEGTORS. I1FERE CONGEALED, UJSE TYPE MG ARMORED CABLE. EMT
OR MC CABLE 15 NOT APPROVED FOR INSTALLATION IN CONCRETE
SLABS OR UNDFRSROUD.
6. CONDUIT ON BUILDING EXTERIOR SHALL BE RIGID ALUMINUM OR
GALVANIZED STEEL WITH WEATHER -TIGHT FITTINGS AND DEVIOUS.
PROVIDE EXPANSION F=ITTINGS WI-ERE CONDUITS EXIT FROM GRADE.
1. UNDERGROUND CONDUIT BELOW GRADE SHALL BE RIGID SULEDIAE 40
PVC WITH SOLVENT WELD FITTINGS. INSTALL CODE SIZED GROUND
CONDUCTOR IN ALL PVC, CONDUIT. PENETRATIONS OF FLOOR SLABS
SHALL 13E MADE WITH RIGID GALVANIZED STEEL., WHERE CONDUITS
ARE EXPOSED TO MECHANICAL DAMAGE. PVC PENE1R4TION5 ARE
ACCEPTABLE *ERE PROTECTED FROM PHYSICAL DAMAGE PROVIDE
EXPANSION FITTINGS AS RECOP BY 1T-E MANJFAGITJRER
S. NO CONDUIT TO BE RUN EXPOSED ON EXTERIOR OF BUILDING WALLS
OR ON THE FLOORS.
'1. PROVIDE ALL FULL BOXES AND FITTINGS V* EVER NECESSARY OR
SHOWN. ALL STRAIGHT CONDUIT RUNS SHALL NOT EXGEEED 100 FEET
WITHOUT FULL BOX, NOT aVE3R 15 FEET FOR RUN WITH ONE (I)
RIGHT ANGLE BBD AND NOT OVER 50 FEET FOR RUN WITH T (2)
RIGHT ANGLES.
IO. ALL CONDUIT SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH
THE NEC. CONDUIT SHALL SE INTOITENDEIRY SUPPORTED FROM
STRUCTURE AND NOT FROM DUCTWORK, CEILING HANGERS OR CEILING
SUPPORT WIRES. NO CONDUIT SHALL ROUTE THROUGH ROOFTOP
EQUIPMENT RETURN AIR OPENINGS.
II. FINAL CONNECTION TO LIGHT FIXTURES AND EQUIPMENT SHALL BE
MADE KITH FLEXIBLE STEEL CONDUIT ('GREFN - 6' MAXIMUM
LENGTH) IN DRY AREAS AND LIQUID TIGHT FLEXIBLE METALLIC
CONDUIT ('SEALTITE') IN DAMP OR WET AREAS.
12. ALL s' rr CONDUITS ARE TO BE PROVIDED WITH PULL WIRES AND
NYLON EUSHINGS AT BOTH ENDS.
13. CONDUIT PE7NETRATIOi OF ROOFS SHALL BE MADE MIN PATE PIPE
CURBS OR PIPE SEALS AS REQUIRED, INSTALLED BY THE PROJECT
ROOFING CONTRACTOR FOR EXISTING ROOFS, TILE PENETRATION
SHALL BE MADE BY AN OIMJE3R APPROVED CONTRACTOR TO MAINTAIN
THE ROOF WARRANTY. CONNECTIONS TO ROOF TOP EQUIPMENT SHALL
SE MADE THROUGH THE ROOF CURB 11-ERE CURB 15 DESIGNED FOR
THIS CONNECTION.
14. PROVIDE SURFACE 4R1EM OLD AND BOXES FOR SURFACE WORK IN
FINSHEP AREAS *ERE SPECIFICALLY APPROVED BY TEE ARCHITECT.
15. CONDUITS ROJrW BELOW FLOOR SLAB ARE TO BE COORDINATED WITH
OTEEBR BELOW -SLAB UTILITIES. INSTALL CONDUITS BELOW TLOOR
SLAB, NOT IN FLOOR POUR GUT AND PATCH EXISTING FLOORS
WHERE CONDUIT MST BE CONCEALED IN OR BELOW FLOOR. CONDUITS
SHOWN RJN OVERHEAD CANNOT BE RUN BELLOW{ GRADE WITHOUT PRIOR
APPROVAL AND COORDINATION WITH 1W ENGINEER AND ALL AFFECTED
CONTRACTORS.
16. PROVIDE SEALS 1^11-EN CONDUIT 15 PASSING FROM GOLD TO WARM
ENVIRONMENTS. USE SILICONE SEALANT AROUND BOXES AND
EXTERIOR OF RAGBNAYS AND SEALING CONFOUND OR FOAM -IN -PLACE
SEALANT 4T14IN RACEWAYS.
G. CUTLET BOXES
I. SUPPORT ALL BOXES FROM BUILDING STRUCTURE INDEPENDENT OF THE
CONDUIT SYSTEM.
2. FLUSH DEVICE BOXES IN MASONRY WALLS SHALL BE DESIGNED FOR
THE PURPOSE WITH RAISED COVER.
3. HIRING DEVICE BOXES FOR SURFACE CONDUIT WORK SHALL BE FS
SERIES GAST BOXES.
4. DEVICES ON BUILDING EXTERIOR SHALL BE P ATHBRFROOF MEMA 3R
5. BOXES FOR (LUSH MOUNTING SHALL BE 4' SQUARE MINIMUM MIN
DEVICE RING FOR FIRING DEVICE= TO BE INSTALLED. COMMRNICATION
JUNCTION BOXES SHALL SE 2 -V8' DEEP MINIMUM.
6. PROVIDE CUSTOM MADE DEVICE BOXES TO ACCOMMODATE CONDUIT
PENETRATIONS SHOPF! ON PLANS.
D. HIRE AND CABLE
I. PURE AND CABLE SHALL BE AS FOLLO1
A. *12 AWS AND #IO AWE SOLID OR STRANDED CONDUCTOR COFFER,
600 VOLT, TYPE THINWTHNIN, )CHI4P4, OR THEN (I5/gO DEGREES
C).
B. #8 AH6 TO AND INCA JR: IN6 *500 KCMIL AWE, STRANDED
CONDUCTOR, COMM 600 VOLT, TYPE THIVITEN, XHM OR
THUD MAO DEGREES G,).
G. TYPE TINHNH (q0 DEGREES G,) HIRE FROM OUTLET BOX TO LIGHT
FIXTURES.
D. #I4 A S MAY BE USED FOR LOW VOLTAGE CONTROL HIRING
ONLY.
E BEGTRICAL CONTRACTOR MAY OPTION TO USE TYPE MG (METAL-
GLAD CABLE) FOR BRANCH CIRCUITS FOR CONGEALED WORK, IF
APPROVED BY OP'1ER AND LANDLORD PRIOR TO BID.
2. COLOR CODING SHALL SE USED FOR ALL WIRE AND CABLES IN
ACCORDANCE WITH NEC. CODING STANDARDS. CONTROL CONDUCTORS
SHALL BE CONTINUOUSLY COLOR CODED. GROUND CONDUCTOR SHALL
BE 6RI5=N.
3. JOINTS IN #10 APS AND SMALLER 4FRE SHALL BE MADE WITH
'SCOTCH LOCKS' (OR MA-) AND BE INSULATED WITH SCOTCH #33
ELECTRICAL TAPE
4. JOINTS IN #8 ANS AND LARGER SHALL EE MADE WITH PRESSURE TYFE
I.EGHANIGAL CONNECTOR AND INSULATED WITH E! EGTRICAL TAPE TO
150% OF THE INSULATING VALUE OF THE CONDUCTOR.
5. INCREASE WIRE SIZE BY ONE AMERICAN WIRE GAUGE SIZE FOR EVERY
- 5 LINEAR FEET OF HIRE RUN.
E. SWITCHES, SAFETY
I. SAFETY SWITCHES SHALL BE HEAVY DUTY, 517E AND ELECTRICAL
CHARACTERISTICS INDICATED, SURFACE MONIED, FUSIBLE RATED AT
250 VOLTS ON THE 208 VOLT SYSTEM AND 600 VOLTS ON TILE 480
VOLT SYSTEM, AMPERE RATINGS AS NOTED ON THE DRAWINGS, 60
HERTZ THREE (3) BLADES, INCORPORATING QUICK -MAKE, QUIGK-
BREAK TYPE SWITCHES.
2. FUSES: UNLESS INDICATED ON THE DRAWINGS AS NON -RINSED TYPE,
PROVIDE FUSES FOR SAFETY SWITCHES. FUSES TO BE TIME -DELAY,
CURRENT - LIMITING UL CLASS RKI, AND HAVE AN INTERRUPTING
RATING OF 200p00 RAMS AhPERES SY14h1EFRICAL
3. DISCONNECTS FOR 120 VOLTS, SINGLE PHASE EQUIPMENT SHALL BE
HEAVY DUTY TYPE SUITABLE FOR THE SERVICE INTENDED. INCLUDE
11- MAL OVERLOAD PROTECTION INTEGRAL WITH DISCONNECT FOR
MOTORS OR WHERE REQUIRED BY CODE.
4. SNITCHES. INSTALLED IN OUTDOOR LOCATIONS SHALL BE
WEATHERPROOF Ha.% 3R
5. PROVIDE BJSRAVED NAMEPLATE FOR EACH DISCONNECT SWITCH
INDICATING VOLTAGE, PHASE, LOAD SERVED, AND CIRCUIT ORIGIN.
F. LIGHTIHS AND POWER PANELBOARDS
I. PROVIDE MAD-FRONT SAF lY TYPE LIGHTING AND POWER
PANELBOARDS AS INDICATED, WITH SWITCHING AND PROTECTIVE
DEVICES IN QUANTITIES, RATINGS, TYPES AND ARRANGEMENT AS
SHOWN, EQUIPPED WITH STANDARD BUS BARS, RILL -SIZED NEUTRAL
BAR, WITH BOLT -IN TYPE MOLDED CASE BRANCH CIRCUIT BREAKERS
FOR EACH CIRCUIT, WITH TOG -:71..E HANDLES THAT INDICATE 11 EN
TRIPPED. PROVIDE A BARE UEIINSULATED GROUNDING BAR SUITABLE
FOR BOLTING TO ENCLOSURE. PROVIDE TYPED DIRECTORY.
2. PROVIDE B4SRAVED NAMEPLATE FOR EACH PANELBOARD INDICATING
VOLTAGE, PHASE, PANEL NAME, AND FEEDER ORIGIN.
3. MANUFACTURER SHALL PROVIDE INTERRUPTING G RATINGS FOR ALL
EQUIPMENT BASED ON FAULT GlRREttr 5Ho4N ON PLANS. SERIES
RATED EQUIPMENT SHALL BE LABELED 'SERIES RATED - REPLACE
WITH IDENTICAL COMPONENT PARTS' 111TH PERMANENT LABEL.
4. ALL CIRCUIT BREAKERS SERVING HID LIGHTING SHALL PROVIDE HID
CIRCUIT BR.E
5. ALL CIRCUIT BREAKERS SERV1 AIR CONDITIONING EQUIPMENT
SHALL BE °HAGR' RATED TO COMPLY WITH EQUIPN'E T LISTING.
b. PROVIDE ARC -FLASH HAZARD LABEL ON ALL PANELBOARDS.
6. GR0UNDIN6
I. ENTIRE POWER SYSTEM SHALL BE EFFECTIVELY GROUENDED, INCL.IIDING
ALL EXPOSED NON - CURRENT CARRYING PARTS OF ELECTRICAL.
EQUIPMENT IN FULL ACCORDANCE WITH N.E.C. ARTICLE 250.
2. A GREEN PIGTAIL SHALL BE INSTALLED FROM GROUNDING SLOTS OF
GROUNDING OUTLETS TO OUTLET BOXES IN EACH INSTANCE WFFERE
RECEPTACLE ATTACHMENT BAR 15 NOT IN DIRECT CONTACT WITH TILE
OUTLET BOX.
3. THE EXISTING BUILDING SYSTEM GROUND SHALL BE EXTENDED TO ALL
MEW WORK
4. TEST GROW SYSTEM AFTER INSTALLATION FOR A MAXIM . i 5 OHMS
TO GROUND AS MEAB. W IN FEBRUARY. PROVIDE ADDITIONAL
GROUND RODS AS REQUIRED.
5. ALL METAL PIPING, SYSTEMS, DUCTWORK AND STEEL FRAMES SHALL
SE BONDED TO ELECTRICAL SYSTEMS IN COMPLIANCE WITH TI-E
NEC.
H. LIGHTING
I. STRIDE RITE TO FURNISH LIGHTING FIXTURE WITH LAMPS AS 514014EN ON
SCHEDULE ON DRAWINGS. E.G. TO INSTALL
2. COORDINATE FIXTURE TYPE AND TRIM WITH CEILING GONSTR UGTION.
3. ALL LAMPS SHALL BE RATED BY MANUFACTURER FOR INSTALLATION IN
SPECIFIED FIXTURE.
4. ALL FIXTURES IN LAY -IN GEILING SHALL BE SUPPORTED FROM THE
STRUCTURE INDEPELDENT OF THE CEILING SYSTEM AT ALL FOUR (4)
CORNERS AND ATTACHED WITH GRID CLIPS.
5. THE MANUFACTURER OF EACH LIGHTING FIXTURE SHALL REVIEW THE
APPLICATION OF HIS EQUIPMENT AND CERTIFY AT TT-EE TIME O= SHOP
DRAWING SUBMITTAL THAT HIS FIXTURE HAS SEEN PROPERLY APPLIED
AND GAN BE INSTALLED, MAINTAINED AND SERVICED WI-HERE SHOWN ON
THE DRAWINGS.
6. ALL FLUORESCENT LAMPS SHALL SE COLOR CORRECTED, TRI- PHOSPHOR
LAMPS OF COLOR TEMPERATURE SPECIFIED. ALL LAMPS SHALL BE BY
THE SAME MANUFACTURER AND BE 6E SYLVANIA- OSRAM, OR
PHILIPS. IF NO COLOR IS SPECIFIED, IT WILL BE SELECTED BY
TIE ARCHITECT.
I. EMBN•Y LIGHTING AND EXIT SIGNS
I. FURNISH AND INSTALL BATTERY POWERED EN RGENGY LIGHTS AND
EXIT SIGNS AS SHOP 1 AND SCHEDULED ON TW DRAWINGS.
2. THE WIRING AND INSTALLATION SHALL CONFORM TO THE
REQUIRE1E4TS OF TIE NEC. AND NFPA LIFE SAFETY CODE
3. BATTERY PACKS INTEGRAL TO R.)ORE CE NT FIXTURES SHALL PROVIDE
A MINIMUM OF 1400 L.UEES AND OPERATE TWO LAMPS IN EACH
FIXTURE.
J. TEMPORARY
I. THIS CONTRACTOR TO PROVIDE ALL TEMPORARY LIGHTING AND POWER
AS REQUIRED FOR ALL TRADES.
2. ALL TEMPORARY WIRING INSTALLED SHALL SE REMOVED BY 11.15
CONTRACTOR.
K. TELE/ SERVICE
I. SERVICE CONSISTS OF AN EXISTING CONDUIT SYSTEM INCOMING
SERVICE AS INDICATED ON DRAWINGS. THIS CONTRACTOR SHALL
FULLY COORDINATE WITH AND PROVIDE FACILITIES REMIREBD BY THE
TELEPHONE UTILITY COMPANY FOR THE SERVICE INSTALLATION.
2. PROVIDE 3/4' FIRE RETARDANT TREATED PLYWOOD BACKBOARDS WHERE
INDICATED ON DRAWINGS FOR USE BY TELEPHONE SYSTEM.
BACKBOARDS SHALL BE PAINTED BOTH SIDES WITH TWO (2) COATS OF
GRAY ENAMEL PAINT. PROVIDE 120 VOLT DUPLEX RECEPTACLE
ADJACENT TO THE RIGHT SIDE LOCATED 1'-6' A.F.F.
3. PROVIDE *6 MG COPPER WIRE OR 5/4° CONDUIT FROM BACKBOARD TO
MAIN BJILDING GROUND.
4. PROVIDE E✓PTY CONDUIT SYSTEM WITH TWO (2) TWISTED PAIR #24
AWG CATEGORY 5 WIRE FROM EACH NEW oUTLET LOCATION TO
EXISTING TELIEMORE CABINETS AS SHOWN ON DRAWINGS.
5. ALL OUTLET LOCATIONS SHOWN ON DRAWING ARE TO BE VERIFIED
WITH THE OWNER PRIOR TO ROUGH -IN.
6. OUTLET BOXES TO BE 4' SQUARE WITH SINGLE COVER PLATE AND
OUTLET NOTED ON DRAWINGS.
DEC 2 8 2007
PEA rvii 6 f:
NOT
DATE
08 -I1 -01
ISSUE
SID/PERMIT
etr►ds rrts SOU114 MITER
C
a
d
s
MECHANICAL &
��++ RI ECT ? C d.
S�EGIHCAT ON3