HomeMy WebLinkAboutPermit M07-290 - SABEY CORPORATIONSABEY CORPORATION
3355 S 120 PL
M07 -290
Parcel No.: 1023049069
Address:
Suite No:
Tenant:
Name:
Address:
3355 S 120 PL TUKW
SABEY CORPORATION
3355 S 120 PL , TUKWILA WA
Owner:
Name: SABEY CORPORATION
Address: 12201 TUKWILA INTL BLVD 4THFL , SEATTLE WA
Contact Person:
Name: TONY MARINO
Address: 5005 3RD AVE S , SEATTLE WA
Contractor:
Name: MCKINSTRY CO LLC
Address: PO BOX 24567 , SEATTLE WA
Contractor License No: MCKINCL942DW
DESCRIPTION OF WORK:
INSTALL EXHAUST DUCTWORK FROM EMERGENCY GENERATOR TO ROOF. PROVIDE 4 EXHAUST
FANS. PROVIDE NEW FUEL OIL PIPING FROM EXISTING CONNECTION POINT TO DAY TANK
THAT WILL ALSO BE PROVIDED. PROVIDE FUEL OIL PIPING FROM DAY TANK TO GENERATOR.
ALL FUEL OIL PUMPS WILL ALSO BE PROVIDED.
Value of Mechanical: 277,000.00
Type of Fire Protection:
Furnace: <100K BTU 0
>100K BTU 0
Floor Furnace 0
Suspended/Wall/Floor Mounted Heater 0
Appliance Vent 0
Repair or Addition to Heat/Refrig /Cooling System.... 0
Air Handling Unit <10,000 CFM 0
>10,000 CFM 0
Evaporator Cooler 0
Ventilation Fan connected to single duct 0
Ventilation System 0
Hood and Duct 0
Incinerator: Domestic 0
Commercial/Industrial 0
doc: IMC -10/06
City'itif Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
MECHANICAL PERMIT
EOUIPMENT TYPE AND OUANTITY
* *continued on next page **
Permit Number: M07 -290
Issue Date: 01/28/2008
Permit Expires On: 07/26/2008
Phone:
Phone: 206 - 832 -8462
Phone: (206)762 -23311
Expiration Date: 03/16/2008
Fees Collected: $2,561.79
International Mechanical Code Edition: 2006
Boiler Compressor:
0-3 HP /100,000 BTU 0
3-15 HP /500,000 BTU 0
15-30 HP /1,000,000 BTU.. 0
30 -50 HP /1,750,000 BTU.. 0
50+ HP /1,750,000 BTU 0
Fire Damper 0
Diffuser 0
Thermostat 0
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment 0
M07 -290 Printed: 01 -28 -2008
Permit Center Authorized Signature:
Signatur
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
Permit Number: M07 -290
Issue Date: 01/28/2008
Permit Expires On: 07/26/2008
Date: 011 n Cal
I hereby certify that I have read and a ed this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied th, hether specified herein or not.
The granting of this permit does not presuYne to give authority to violate or cancel the provisions of any other state or local laws regulatinc
construction or the • • rmance of work. I am authorized to sign and obtain this mechanical permit.
Date:
Print Name: / /T Je
e i
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspende
or abandoned for a period of 180 days from the last inspection.
doc: IMC -10/06 M07 -290 Printed: 01 -28 -2008
Parcel No.: 1023049069
Address:
Suite No:
Tenant:
3355 S 120 PL TUKW
SABEY CORPORATION
1: ** *BUILDING DEPARTMENT CONDITIONS * **
�lri �.iC
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
PERMIT CONDITIONS
Permit Number:
Status:
Applied Date:
Issue Date:
MOT -290
ISSUED
12/26/2007
01/28/2008
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431- 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
6: Manufacturers installation instructions shall be available on the job site at the time of inspection.
7: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the Cityof Tukwila
Permit Center.
8: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431 - 3670).
9: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
10: ** *FIRE DEPARTMENT CONDITIONS * **
11: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
12: Maintain coverage and operability of portable fire extinguishers, sprinkler systems and fire alarm systems during
demolition and construction.
13: Maintain fire extinguisher coverage throughout.
14: The total number of fire extinguishers required for an extra hazard occupancy with Class A fire hazards is calculated
at one extinguisher for each 1,000 sq. ft. of area. The extinguisher(s) should be of the "all purpose" (4A 40 B:C) dry
chemical type. The travel distance to any extinguisher must be 75' or less. (IFC 906.3) (NFPA 10, 3 -2.1)
15: Portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or
brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation
instructions. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so
doc: Cond -10/06
M07 -290 Printed: 01 -28 -2008
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 - 3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
that its top is not more than 5 feet (1524 nun) above the floor. Hand -held portable fire extinguishers having a gross
weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the
floor. The clearance between the floor and the bottom of the installed hand -held extinguishers shall not be less than 4
inches (102 mm). (IFC 906.7 and IFC 906.9)
16: Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot
be completely avoided, means shall be provided to indicate the locations of the extinguishers. (IFC 906.6)
17: Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available
for use. These locations shall be along normal paths of travel, unless the fire code official determines that the
hazard posed indicates the need for placement away from normal paths of travel. (IFC 906.5)
18: No point in a building may exceed the maximum exit access travel distance listed in Chapter 10, section 1015, Table
1015.1 of the International Fire Code and International Building Code.
19: Maintain sprinkler coverage per N.F.P.A. 13. Addition/relocation of walls, closets or partitions may require relocating
and/or adding sprinkler heads. (IFC 901.4)
20: Sprinkler design shall be a minimum Ordinary Hazard Group II with a minimum design area of 3,000 square feet.(IFC Sect.
2704.6 {2006 Edition })
21: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
22: Maintain automatic fire detector coverage per N.F.P.A. 72. Addition/relocation of walls, closets or partitions may
require relocating and/or adding automatic fire detectors.
23: Material safety data sheets for all hazardous materials on the premise shall be readily available on site for emergency
personnel. (IFC 2703.4)
24: Visible hazard identification signs shall be placed at entrances to locations where hazardous materials are stored,
dispensed, used or handled in quantities requiring a permit. Individual containers, cartons or packages shall be
conspicuously marked or labeled in accordance with nationally recognized standards. (IFC 2703.5) (NFPA 704))
25: "No Smoking" signs shall be conspicuously posted within and at all entrances to hazardous materials storage areas. (IF'C
2703.7.1(1 -4))
26: Above ground flammable liquid tanks shall be U.L listed and comply with NFPA 30. Tank installation shall comply with
Sections 2704,2705, and 3404 of the International Fire Code(2006 edition)
27: Spill containment systems or means to render a spill harmless to people or property shall be provided where a spill is
determined to be a plausible event and where such an event would endanger people or property. (IFC 2701.3.3.4)
28: Fuel oil piping shall be installed in compliance with Chapter 13 of the International Mechanical Code and tested in
compliance with NFPA 31, Section 8.9.
29: Due to quantity of fuel oil exceeding maximum allowable quantities, generator room needs to meet rquirements of an H -3
occupancy.(IFC Table 2703.1.1)
30: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
31: To schedule all construction fire - related inspections send an e-mail to fireinsprequest @ci.tukwila.wa.us. Include your
name, telephone number, permit number, project name and address and type of inspection requested.
doc: Cond -10/06
M07 -290 Printed: 01 -28 -2008
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
32: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes
such condition or violation.
33: These plans were reviewed by Inspector 512. If you have any questions, please call Tukwila
(206)575 -4407.
* *continued on next page **
doc: Cond - 10/06 M07 - 290
does not imply approval of
Fire Prevention Bureau at
Printed: 01 -28 -2008
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating
construction or the performance of work.
Print Name:
/l� �✓ l�/P f'/
Date:
doc: Cond -10/06 M07 -290 Printed: 01 -28 -2008
CITY OF TUKWIL
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
htqx//www.ci.tukwila.wa.us
SITE LOCATION
Site Address: 6355 S / 20 "ter Tick nrt lo' h1I3
Tenant Name: 5a bey CQ //9oraJ) C \
Property Owners Name: !! 5a/X
Mailing Address: 3355 5. /ZOO ?/C-
CONTACT PERSON - who do we contact when your permit is ready to be issued
Name: 7:0/7y ///ot ri W / ck Z'i5 'Y 4Q • Day Telephon«C2ao \ S3 2 - 8 6 2 -
) Mailing Address: 5601 3I'd /'✓P, s . t!O �g/ 3
i City State Zip
Fax Number: (206 S 3i - $(n (ci 2-
E -Mail Address: fon y 177 e fi C k nsivy . cam
GENERAL CONTRACTOR INFORMATION —
(Contractor Information for Mechanical (pg 4) for Plumbing and Gas Piping (pg 5))
Company Name: l y COrp# 'Jio,
Mailing Address: 270 T f/1f?'rnRheneza
Contact Person: /IArCP /O ( el 'Cc" S
E -Mail Address: P Y i / A p ' C e ' / 0 ✓ q Z SCi 1 ( j . CO m
Contractor Registration Number:
ARCHITECT OF RECORD - All plans must be wet stamped by, Architect of Record
Company Name:
Mailing Address:
Contact Person:
E -Mail Address:
ENGINEER OF RECORD - All plans must be wet stamped by Engineer of Record
Company Name: Meitins
Mailing Address: SD 0 5
Contact Person: / iVa /' it2y'
E -Mail Address:
Q:Wpplications\Porms- Applications On
Revised: 9 -2006
bit
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
2006 - Permit Application.doc
C 0 .
3rd /,vr .
// I 14.
Public Works Permit No.
Project No.
(For office use only)
Building Permit No.
Mechanical Permit No. '4( - )
Plumbing/Gas Permit -No.
King Co Assessor's Tax No.: /04:2 3o `/ fay' q
Suite Number: 520/ Floor:
New Tenant: ❑ Yes b K.No
Tvx w. /
City
w / T State
90 /ro
Zip
/3/ ✓0 4/ F /oav Sea- wf3. 9 $ 1 4:4
City
State /Zip 512
Day Telephone: 2 — 321 4
Fax Number: ZO(, — 243 I — Q92C'
Expiration Date:
State
Zip
City
Day Telephone:
Fax Number:
City ' State Zip
Day Telephone:( ) 03 2-- 94(0 a
Fax Number.2 /Z ) Fi,3 Z - e362l„
Page 1 of 6
Unit Type:
Qty
Unit Type:
Qty
Unit Type:
Qty '
Boiler /Compressor:
Qty
Fumace<100K BTU
Air Handling Unit >10,000
CFM
Fire Damper
0 -3 HP /100,000 BTU
Fumace>100K BTU
Evaporator Cooler
Diffuser
3 -15 HP /500,000 BTU
Floor Furnace
Ventilation Fan Connected
to Single Duct
Thermostat
15 -30 HP /1,000,000 BTU
Suspended/Wall/Floor
Mounted Heater
Ventilation System
Wood/Gas Stove
30 -50 HP /1,750,000 BTU
Appliance Vent
Hood and Duct
Emergency
Generator
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Refrig/Cooling
System
Incinerator - Domestic
Other Mechanical
Equipment
Air Handling Unit
<10,000 CFM
Incinerator – Comm/Ind
MECHANICAL PERMIT INFORMATION 206 -431 -3670
MECHANICAL CONTRACTOR INFORMATION
_Company Name: / �—,/ C .� f ,+ t � I nSfry
Mailing Address: CO" #k
1„ `��1i3�1
City /' `e Zip
Contact Person: ! f>/l V ino Day Telephone: C: z / t 32^ gqG2
E -Mail Address: 10/1V ( /t'/@ An /f?(iZs fl cao Fax Number: G Z6 )) q12-
$ ' Z
Contractor Registration Number: /' 1 E' 1/N L 7L( )(4) Expiration Date: 3/I&/2 00 8
Valuation of Mechanical work (contractor's bid price): $
Scope of Work (please provide deta ed information): H7
Use: Residential: New .... ❑ Replacement .... ❑
Commercial: New ... Replacement .... ❑
Indicate type of mechanical work being installed and the quantity below:
Q: Applications \Forms- Applications On Line\3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
IsvOrk - ett 7 r* 1 &p_8 e
Fuel Type: Electric ❑ Gas ....0 Other:
Page 4 of 6
Fixture Type:
Qty
Fixture Type:
Qty
Fixture Type:
Qty
Fixture Type:
Qty
Bathtub or combination
bath/shower
Drinking fountain or water
cooler (per head)
Wash fountain
Gas piping outlets
Bidet
Food -waste grinder,
commercial
Receptor, indirect
waste
Fir al Va T nkS
2
Clothes washer, domestic
Floor drain
Sinks
Dental unit, cuspidor
Shower, single head trap
Urinals
Dishwasher, domestic,
with independent drain
Lavatory
Water Closet
Building sewer or trailer
park sewer
Rain water system — per
drain (inside building)
Water heater and/or
vent
Additional medical gas
inlets/outlets — six or more
Industrial waste
pretreatment interceptor,
including its trap and vent,
except for kitchen type
grease interceptors
Repair or alteration of water
piping and/or water treating
equipment
Repair or alteration
of drainage or vent
piping
Medical gas piping system
serving one to five
inlets/outlets for specific gas
PLUMBING AND GAS PIPING PERMIT INFORMATION — 206 - 431 -3670
PLUMBING AND GAS PIPING CONTRACTOR INFORMATION
Company Name: / - 1[. h Ipl5 i
Mailing Address: J 2 UC S
Contact Person: 1y )r,r4D
E - Mail Address: f D Cie/04' /'t t1?SF/ . Cp/+s
Contractor Registration Number: MEKIIJGL gitol AA.}
Q: Wpplications\Forms- Applications On Linel3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
Valuation of Plumbing work (contractor's bid price): $
Valuation of Gas Piping work (contractor's bid price): $
Scope of Work (please provide detailed information):
Seit
grr
tate Zip
City
Day Telephone: 004 $32.-- & f6
Fax Number:. (a: ) e.??- aa
Expiration Date: 3 14,17...008 --
� . I n • .
MIM
,0•7/..1 141/ 0 S,6
Building Use (per Int'l Building Code):
Occupancy (per Intl Building Code):
Utility Purveyor: Water:
Indicate type of plumbing fixtures and/or gas piping outlets being installed and the quantity below:
Sewer:
Page 5 of 6
PERMIT APPLICATION NOTES — Applicable to all permits in this application
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center -to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days.following the date of application shall expire by limitation.
Building and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section. 105.3.2 International Building Code (current edition).
Plumbing Permit
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
Signature:
Print Name:
in writing and justifiable cause'demonstrated. Sectionl 01 :4.3 Uniform Plumbing Code (current edition).
BUILDING OWNER .0
Mailing Address: /
Date Application Accepted:
I.)--.)-Co -07
Date Application Expires: to
-( -0
Staff Initials: , ,n
i
Q:\Applications\Forms - Applications On Line\3 -2006 - Permit Application.doc
Revised: 9 - 2006
bh
Sgfirize
City
Date: 47 — a -O L�
f Cep Day Telephone:
Sz j
State Zip
Page 6 of 6
Receipt No.: R08 -00235
Payee: MCKINSTRY
ACCOUNT ITEM LIST:
Description
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: //www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 1023049069 Permit Number: M07 -290
Address: 3355 S 120 PL TUKW Status: APPROVED
Suite No: Applied Date: 12/26/2007
Applicant: SABEY CORPORATION Issue Date:
Initials: JEM Payment Date: 01/28/2008 09:08 AM
User ID: 1165 Balance: $0.00
TRANSACTION LIST:
Type Method Description Amount
Payment Check 273200 2,202.82
MECHANICAL - NONRES 000/322.100
PLAN CHECK - NONRES 000/345.830
Account Code Current Pmts
Payment Amount: $2,202.82
2,055.43
147.39
Total: $2,202.82
7724 01/28 9710 TOTAL 2202.82
doc: Receiot -06 Printed: 01 -28 -2008
Parcel No.: 1023049069
Address: 3355 S 120 PL TUICW
Suite No:
Applicant: SABEY CORPORATION
Payee: MCBINSTRY CO
TRANSACTION LIST:
Type Method Description
ACCOUNT ITEM LIST:
Description
PLAN CHECK - NONRES
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Receipt No.: R07 -02854 Payment Amount: $358.97
Initials: WER Payment Date: 12/26/2007 10:11 AM
User ID: 1655 Balance: $1,465.88
Amount
Payment Check 9277 358.97
Account Code Current Pmts
000/345.830 358.97
Total: $358.97
Permit Number: M07 -290
Status: PENDING
Applied Date: 12/26/2007
Issue Date:
6481 12/26 9710 TOTAL 358.97
doc: Receiot -06 Printed: 12 -26 -2007
Project:
5 +3
(-,-) pit 4- -,\
T of Inspecti n:
lute � .
t
&j
Address:
r p c.,
Date Called:
Special Instructions:
Date Wanted:
J
Requester:
Phone No:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
pproved per applicable codes. Corrections required prior to approval.
COMMENTS:
P
{
'Inspector:
O ` (Date: 0 Z L V y
❑ $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
Projec
Type of Inspection; n
Address: Vi+
"?.3.5 10 /Iv �.,
Date Called: fl_..)....
/
--- - f--s-
Special Instructions:
Date Wanted:
S : (c 'i)
f ` a.
p.m.
Requester:
Phone No: �_��
SO4, USC(
— mil
Z,&3
Mo'7.2 go
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION 12 '
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
•
ve
COMMENTS:
(Date: 0/2
Corrections required prior to approval.
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
COMMENTS:
� / '�( ,
Type of I nspect I ion:
1 L. . /� ` \ Tr-_,,
1,4 f .
ok
�J (.e
, :
t'.. -o! / -e--c:7 ) t. or -!�
S `' -.IAt c
!, r ti <.— •S ; ,1..1 fyi - f'-
-- 0 ; i
"a.m.
r‘ ,s n--r
7 / e 4 ,
r
Project:
).A4-›-e2/ � / �
� / '�( ,
Type of I nspect I ion:
1 L. . /� ` \ Tr-_,,
1,4 f .
Address:
33 sS S,
(t
/20 '�
Date Called: ti
�-
Special Instructions:
Date Wanted:
"a.m.
Requester:
Phone No:
44(
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3q7
0 Approved per applicable codes.
Ei orrect ions required prior to approval.
l inspec or: ' / \ 1Date:7 d
❑ $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
)or1. - 11v
PERMIT NO.
06 -05 -2008
TONY MARINO
5005 3RD AVE S
SEATTLE WA 98134
RE: Permit No. M07 -290
3355 S 120 PL TUKW
Dear Permit Holder:
In reviewing our current records the above noted permit has not received a final inspection by the City of Tukwila Building Division.
Per the International Codes, Uniform Plumbing/Fuel Gas Code and/or the National Electrical Code, every permit issued by the
Building Division under the provisions of the code shall expire by limitation and become null and void if the building or work
authorized by such permit is not commenced within 180 days from the date of such permit issuance, or if the building or work
authorized by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days.
Based on the above, you are hereby advised to:
Call the City of Tukwila Inspection Request Line at 206 -431 -2451 to schedule for the next or final inspection.
This inspection is intended to determine if substantial work has been accomplished since issuance of the permit or last inspection; or if
the project should be considered abandoned.
If such determination is made, the International Codes, Uniform Plumbing/Fuel Gas Code and/or the National Electrical Code does
allow the Building Official to approve one extension of time for an additional period not exceeding 180 days. Extension requests
must be in writing and provide satisfactory reasons why circumstances beyond the applicants control have prevented action from
being taken.
In the event you do not call for the above inspection and receive an extension prior to 07/26/2008 , your permit will become null and
void and any further work on the project will require a new permit application and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
Je if r Marshall
Permit Technician
xc: Permit File No. M07 -290
City of Tukwila
Jim Haggerton, Mayor
Department of Community Development Jack Pace, Director
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206- 431 -3665
December 27, 2007
Tony Marino
5005 3` Ave S
Seattle WA 98134
RE: Letter of Incomplete Application # 1
Development Permit Application M07 -290
Sabey Corporation — 3355 S 120 P1
Dear Mr. Marino,
This letter is to inform you that your permit application received at the City of Tukwila Permit Center on December 26,
2007 is determined to be incomplete. Before your application can continue the plan review process the attached items
from the following department needs to be addressed:
Building Department: Allen Johannessen, at 206 433 -7163, if you have any questions concerning the
attached comments.
Please address the comment above in an itemized format with applicable revised plans, specifications, and/or other
documentation. The City requires that two (2) sets of revised plans, specifications and/or other documentation be
resubmitted with the appropriate revision block.
In order to better expedite your resubmittal a `Revision Submittal Sheet' must accompany every resubmittal. I have
enclosed one for your convenience. Revisions must be made in person and will not be accepted throuch the mail or by
a messen'er service.
If you have any questions, please contact me at the Permit Center at (206) 431 -3670.
Sincerely,
Bill Rambo
Permit Technician
Enclosures
File: M07 -290
City of Tukwila
Department of Community Development Steve Lancaster, Director
ROE4QJ-
P:\Permit Centerllncomplete Letters\2007\M07 -290 Incomplete Ltr #1.DOC
vier
Steven M Mullet, Mayor
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665
Determination of Completeness Memo
Date: . December 27, 2007
Project Name: Sabey Corporation
Permit #: M07 -290
Plan Review: Allen Johannessen, Plans Examiner
Tukwila Building Division
Allen Johannessen, Plan Examiner
The Building Division has deemed the subject permit application incomplete. To assist the applicant in
expediting the Department plan review process, please forward the following comments.
(GENERAL NOTE)
PLAN SUBMITTALS: (Min. size 11x17 to maximum size of 24x36; all sheets shall be the same size).
(If applicable) Structural Drawings and structural calculations sheets shall be original signed wet stamped,
not copied.)
1. Mechanical and energy codes reference outdated codes. Please revise code notes and review plan design
including energy code references to show compliance with the current 2006 International Mechanical
codes and 2006 Washington State Energy codes with Washington State Amendments.
Should there be questions concerning the above requirements, contact the Building Division at 206 -431 -3670.
No further comments at this time.
DEPARTMENTS:
Bui g P I sion
Public Works
Complete
Comments:
Documents/routing slip.doc
2 -28 -02
e
PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: M07 -290 DATE: 01 -03 -08
PROJECT NAME: SABEY CORPORATION
SITE ADDRESS: 3355 S 120 PL
Original Plan Submittal X Response to Incomplete Letter # 1
Response to Correction Letter # Revision # After Permit Issued
Fire Prevention
Structural
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Incomplete ❑
TUES/THURS ROUT NG:
Please Route Structural Review Required
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
Notation:
REVIEWER'S INITIALS:
❑ Permit Coordinator
DUE DATE: 01 -08-08
Not Applicable ❑
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
No further Review Required
DATE:
DATE:
Planning Division
n
C
n
DUE DATE: 02 -05-08
Not Approved (attach comments) n
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
`PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: M07 -290 DATE: 12 -26 -07
PROJECT NAME: SABEY CORPORATION
SITE ADDRESS: 3355 S 120 PL
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter # Revision # After Permit Issued
DEPARTMENTS:
Building Division Xi
Public Works ❑ Structural ❑ Permit Coordinator
6I2 AA 12 ' '
Fire Prevention X
Planning Division
DETERMINATION OF COMPLETENESS: (Tues., Thu s.) DUE DATE: 'I 2 -27 -07
Complete ❑ Incomplete Not Applicable ❑
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: I) ")- `D7 LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg er Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES/THURS ROUTING:
Please Route ❑ Structural Review Required ❑ No further Review Required ❑
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions ❑ Not Approved (attach comments) C
Notation:
REVIEWER'S INITIALS: DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents/routing slip.doc
2 -28 -02
DUE DATE: 01 -24 -08
Date:
, 13 � 0F
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
Revision submittals must be submitted in person at the Permit Center. Revisions will not be accepted through
the mail, fax, etc.
Plan Check/Permit Number: M07 -290
• Response to Incomplete Letter # 1
❑ Response to Correction Letter #
❑ Revision # after Permit is Issued
❑ Revision requested by a City Building Inspector or Plans Examiner
Project Name: Sabey Corporation
Project Address: 3355 S 120 PI
Contact Person: Tony Marino Phone Number: 206` Z32' $y62
Summary of Revision: 0/17.2.4 / OLit ✓.it /eTCn iio J 2(22(1 Lcie
d a it / /1/e s � � y� fi
Sheet Number(s): /162
"Cloud" or highlight all areas of revision including date of r: ision
Received at the City of Tukwila Permit Center by,
Entered in Permits Plus on I I
\applications\forms - applications on line\revision submittal
Created: 8 -13 -2004
Revised:
Steven M. Mullet, Mayor
Steve Lancaster, Director
ofi rr0kwit.4
JAN - 3 2 008
~EyMi7 4ENTE6
License Information
License
MCKINCL942DW
Licensee Name
MCKINSTRY CO LLC
Licensee Type
CONSTRUCTION CONTRACTOR
UBI
602569922
Ind. Ins. Account Id
70616500
Business Type
LIMITED LIABILITY COMPANY
Address 1
PO BOX 24567
Address 2
City
SEATTLE
County
KING
State
WA
Zip
98134
Phone
2067623311
Status
ACTIVE
Specialty 1
GENERAL
Specialty 2
UNUSED
Effective Date
3/16/2006
Expiration Date
3/16/2008
Suspend Date
Separation Date
Parent Company
Previous License
MCKIN * *372N0
Next License
Associated License
Business Owner Information
Name
Role
Effective
Date
Expiration
Date
PEDERSEN, JAMIE
D
AGENT
03/16/2006
ALLEN, DEAN C
PARTNER/MEMBER
03/16/2006
MOORE, DOUGLAS
J
PARTNER/MEMBER
03/16/2006
ALLEN, DAVID E
PARTNER/MEMBER
03/16/2006
TEPLICKY, JOSEPH
PARTNER/MEMBER
03/16/2006
Washington State Department of Labor and Industries
General/Specialty Contractor
A business registered as a construction contractor with L &I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Bond Information
https: // fortress .wa.gov /lni/bbip /printer.aspx ?License= MCKINCL942DW 01/28/2008
F625-052-000 (8/97)
DEPARTMENT OF LABOR AND INDUSTRIES
REGISTERED AS PROVIDED BY LAW AS
CONST CONT GENERAL
3/16/2006
IS .. ,
INCI942DW
• EFFECTIVE DATE
MCKINSTRY CO LLC
:PO BOX 24567
SEATTLE WA 98134
I certify this to be a true copy of the original
Dated this 22nd day of May 2006.
W C�
Notary Public in and for
the State of Washington
Residing in Kent
My commission expires 4 -19 -07
SHEET NUMBER
SHEET TITLE
MO.0
DRAWING INDEX, SYMBOLS AND ABBREVIATIONS
MO.1
SEISMIC INFORMATION
M2.1
HVAC 1ST FLOOR PLAN
P2.1
PLUMBING 1ST AND 2ND FLOOR PLAN
P6.0
PLUMBING DIAGRAMS
P7.0
SCHEDULES - PLUMBING
ABBREVIATIONS
GENERAL
AD
ADJ
AFF
AFG
AG
AMP
ARCH
AUTO
AUX
BD
BHP
BLDG
BOP
BOT
Bs
BTU
BTUH
CA
CAB
COND
C/L
CLG
CFM
CLG
CO
CO2
COL
CONC
COND
CONN
CONSTR
CONTR
CTL
DET
DIA
DLAG
DIM
DISCH
DIV
DN
DS
DWDI
DWG
DWV
(E)
EA
EC
EL
ELEC
ELEV
EP
EQUIP
ESP
EXH
EXIST
(F)
F
FA
FCO
FDC
FDN
FIG
FIN
no
FLEX
FLG
FLR
FO
FP
FPM
Fr
FTG
FURN
GA
GALV
GC
GEN
GPM
GWB
HP
HR
HS
HTG
HTR
ID
LAB
LF
MAU
MAX
MBH
MED
MEZZ
MFR
MH
MIN
MISC
MTD
N/A
NC
NEG
NIC
NO
NOM
NTS
OA
OC
OD
OVHD
SECT
SF
SIM
SPEC
SQ
STD
STRUC
ACCESS DOOR
ADJUSTABLE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
ABOVE GROUND
AMPERE
ARCHITECT; ARCHITECTURAL
AUTOMATIC
AUXILIARY
BOARD
BRAKE HORSEPOWER
BUILDING
BOTTOM OF PIPE
BOTTOM
BIRD SCREEN
BRITISH THERMAL UNIT
BRITISH THERMAL UNITS PER HOUR
COMPRESSED AIR
CABINET
CONDENSATE
CENTER LINE
CEILING
CUBIC FEET PER MINUTE
CEILING
CARBON MONOXIDE
CARBON DIOXIDE
COLUMN
CONCRETE
CONDENSER; CONDENSATE
CONNECT; CONNECTION
CONSTRUCTION
CONTRACTOR
CONTROL
QTY QUANTITY
DETAIL
DIAMETER
DIAGONAL
DIMENSION
DISCHARGE
DMSION
DOWN
DISCONNECT SWITCH; DOOR SWITCH
DOUBLE WIDTH, DOUBLE INLET
DRAWING
DRAIN, WASTE, VENT
EXISTING
EACH
ELECTRICAL CONTACTOR; END CAP
ELEVATION
ELECTRICAL
ELEVATION
ELECTRICAL PANEL; END PLUG
EQUIPMENT
EXTERNAL STATIC PRESSURE
EXHAUST
EXISTING
FUTURE
FAHRENHEIT
A RE ALARM
FLOOR CLEANOUT
FIRE DEPARTMENT CONNECTION
FOUNDATION
FIGURE
FINISH
FURNISHED AND INSTALLED BY OWNER
FLEXIBLE
FLANGE
FLOOR
FUEL OIL
FIRE PROTECTION
FEET PER MINUTE
FOOT; FEET
FOOTING
FURNISH
GAGE
GALVANIZED
GENERAL CONTRACTOR
GENERATOR
GALLONS PER MINUTE
GYPSUM WALL BOARD
HIGH
HORSEPOWER; HIGH PRESSURE
HEATING RETURN
HEATING SUPPLY
HEATING
HEATER.
INSIDE DIAMETER /DIMENSION
LABORATORY
LINEAL FOOT
MAKE -UP AIR UNIT
MAXIMUM
1000 BRITISH THERMAL UNITS PER HOUR
MEDIUM
MEZZANINE
MANUFACTURER
MANHOLE
MINIMUM; MINUTE(S)
MISCELLANEOUS
MOUNTED
NOT APPLICABLE
NORMALLY CLOSED
NEGATIVE
NOT IN CONTRACT
NORMALLY OPEN; NUMBER
NOMINAL
NOT TO SCALE
OVERALL
ON CENTER
OUTSIDE DIAMETER
OVERHEAD
POC POINT OF CONNECTION
PRELIM PRELIMINARY
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
R RELOCATED
RAD RADIUS
REQD REQUIRED
RPM REVOLUTIONS PER MINUTE
SECTION
SQUARE FOOT
SIMILAR
SPECIFICATION
SQUARE
STANDARD
STRUCTURAL
TBD
TI
TOC
TOS
TYP
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
VAV
VD
VER
VFD
VSD
W/ WITH
W/O WITHOUT
HVAC
AC
ACT
AHU
BDD
BOO
CC
CRU
CT
CV
DB
DIFF
DMPR
EA
EAT
ECG
EF
FCU
FD
FM
FP
FTU
HC
HR
HVAC
TO BE DETERMINED
TENANT IMPROVEMENTS
TOP OF CONCRETE
TOP OF STEEL
TYPICAL
VARIABLE AIR VOLUME
VOLUME DAMPER
VERIFY
VARIABLE FREQUENCY DRIVE
VARIABLE SPEED DRIVE
AIR CONDITIONING
ACOUSTICAL CEILING TILE
AIR HANDLING UNIT
BACKDRAFT DAMPER
BOTTOM OF DUCT
COOLING COIL
COMPUTER ROOM UNIT
COOLING TOWER
CONSTANT VOLUME
DRY BULB
DIFFUSER
DAMPER
GRD GRILLE, REGISTER, DIFFUSER
LAT LEAVING AIR TEMPERATURE
LD LINEAR DIFFUSER
MC
MECH
MOD
MUA
OA OVERALL; OUTSIDE AIR
OBD OPPOSED BLADE DAMPER
RA
RAT
RCP
RTU
SA
SAT
SD
SF
S /FD
SL
SLSM
SM
SP
TOFI
TG
TOD
TSP
UH
WB
WC
WG
TOTAL DYNAMIC HEAD
TRANSFER GRILLE
TOP OF DUCT
TOTAL STATIC PRESSURE
UNIT HEATER
WET BULB
WATER COLUMN
WATER GAUGE
PLUMBING
AD AREA DRAIN
CO
DCW
DHW
DHWC
DSP
EXHAUST AIR
ENTERING AIR TEMPERATURE
EGGCRATE GRILLE
EXHAUST FAN
FAN COIL UNIT
FIRE DAMPER
FREQUENCY MODULATION
FIRE PROTECTION; FAN POWERED
FAN TERMINAL UNIT
HEATING COIL
HEATING RETURN
HEATING, VENTILATION AND
AIR CONDMONING
MECHANICAL CONTRACTOR
MECHANICAL
MOTOR OPERATED DAMPER; MODULATING
MAKE UP AIR
RETURN AIR
RETURN AIR TEMPERATURE
REFLECTED CEILING PLAN
ROOF TOP UNIT
SUPPLY AIR
SUPPLY AIR TEMPERATURE
SMOKE DAMPER
SUPPLY FAN
SMOKE FIRE DAMPER
SOUND LINED
SOUND LINED SHEET METAL
SHEET METAL
STATIC PRESSURE
CLEAN OUT; CARBON MONOXIDE
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RECIRCULATION
DRY STANDPIPE
EWC ELECTRICAL WATER COOLER
FD FLOOR DRAIN
IE INVERT ELEVATION
IN WC INCHES WATER COLUMN
IW IONIZED WATER; INDIRECT WASTE
NPCW NON POTABLE COLD WATER
ORL OVERFLOW RAINWATER LEADER
PD
PERF
PLBG
PRV
PLANTER DRAIN; PRESSURE DROP
PERFORATED
PLUMBING
PRESSURE REDUCING VALVE
RPBP REDUCED PRESSURE
BACKFLOW PREVENTER
SD STORM DRAIN
SS SANITARY SEWER
VTR
WC
WH
WSP
CD
CHW
CHR
CHS
CT
VENT THROUGH ROOF
WASTE
WATER CLOSET
WATER HEATER
WET STANDPIPE
PIPING
BP BACKFLOW PREVENTER
CONDENSATE DRAIN
CHILLED WATER
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONICAL TEE
EWT ENTERING WATER TEMPERATURE
FHV FIRE HOSE VALVE
LWT LEAVING WATER TEMPERATURE
TOP TOP OF PIPE
PIPING IDENTIFICATION
FIVAC
PLUMBING
A
COND
- CDR -
CDS
CHS
- CHR -
0
HR
HS
RL
- --- RS
ST
GRW
GAW
ID
IRR
NP
ORL
rW
PSD
RWL
SD
-- SS
- --- UD
-
W
FIRE PROTECTION
DSP
FDC
F
PIPING FITTINGS lc.
1t1
1I
101
VALVES
FP
FW
WSP
4 uv
1,AV
4 ""V
Q
Y
I�I
PIPING ACCESSORIES
RPBP
0
D
I
IT
. ❑4
-# # WATTS /LF
A
COND
CDR
CDS
CHS
CHR
G
HR
HS
RL
RS
ST
CW
GRW
GAW
HW
HWC
ID
IRR
NPCW
ORL
PW
PSD
RWL
RWL
SD
SS
UD
V
W
W
DSP
FDC
FP
FW
WSP
COMPRESSED AIR PIPE
CONDENSATE DRAIN PIPE
CONDENSER WATER RETURN PIPE
CONDENSER WATER SUPPLY PIPE
CHILLED WATER SUPPLY PIPE
CHILLED WATER RETURN PIPE
NATURAL GAS PIPE
HEATING WATER RETURN PIPE
HEATING WATER SUPPLY PIPE
REFRIGERANT LIQUID PIPE
REFRIGERANT SUCTION PIPE
STEAM SUPPLY
COLD WATER PIPE (POTABLE)
GREASE WASTE
GARAGE WASTE
HOT WATER PIPE (POTABLE)
HOT WATER CIRCULATING (POTABLE)
INDIRECT DRAIN
IRRIGATION WATER PIPE
NON- POTABLE CW PIPE
OVERFLOW RAINWATER LEADER
PUMPED WASTE
PUMPED STORM DRAIN
RAINWATER LEADER BELOW GRADE
RAINWATER LEADER
STORM DRAIN PIPE
SANITARY SEWER PIPE (SITE)
UNDERDRAIN PIPE
VENT PIPE (SANITARY)
WASTE PIPE
WASTE PIPE BELOW GROUND
DRY STAND PIPE
FIRE DEPT. CONNECTION PIPE
FIRE SPRINKLER PIPE
FIRE PROTECTION WATER PIPE
FIRE PROTECTION WASTE PIPE
WET STAND PIPE
TEE W /PIPE UP
TEE DOWN W /ELBOW
TEE UP W/ ELBOW
TEE UP
TEE DOWN
90' ELBOW UP
g0' ELBOW DN
CAP
UNION
FLANGE
FLEX HOSE CONNECTION
DOUBLE BELLOWS FLEX CONNECTION
SINGLE BELLOWS FLEX CONNECTION
FLOW ARROW
CONCENTRIC REDUCER
ECCENTRIC REDUCER
SLOPE SYMBOL -
BREAK OR CONTNUATION SYMBOL
DOWN SPOUT NOZZLE
CLEANOUT
45' ELBOW
45' ELBOW
90' ELBOW
90' ELBOW
CROSS
TEE
WYE
TAP
HOSE CONNECTION
MOTORIZED 2 -WAY VALVE
MOTORIZED 3 -WAY VALVE
PRESSURE REDUCING VALVE
CONTROL VALVE
RELIEF VALVE
BALL VALVE
3 -WAY GATE VALVE
BUTTERFLY VALVE
DIAPHRAGM VAVLE
CHECK VALVE
NEEDLE VALVE
GLOBE VALVE
GLOBE VALVE ANGLE
GLOBE VALVE 3-WAY
GATE
PLUG VALVE
BALANCING VALVE
HOSE BIBB
PUMP
MANUAL AIR VENT
AUTOMATIC AIR VENT
HIGH CAPACITY AIR VENT
SHOCK ARRESTOR
FLOW SWITCH
VACUUM BREAKER
PRESSURE GAUGE
TEMPERATURE SENSOR
TEMPERATURE INDICATOR
AUTO FLOW VALVE
FLOW METER
Y STRAINER
Y STRAINER W/ BALL VALVE
PIPE SLEEVE
STEAM TRAP
PETES PLUG
HEAT TRACING
SUCTION DIFFUSER W/ STRAINER
REDUCED PRESSURE
BACKFLOW PREVENTOR
FUNNEL DRAIN
FLOOR DRAIN
ROOF DRAIN
ROOF OVERFLOW DRAIN
FLOOR SINK
DUCTWORK ACCESSORIES
IF
�
i=T=t
{
r AD �
L J
AD
12x12 SL
12x12 2 -
DUCTWORK
RECTANGULAR DUCT
RECTANGULAR DUCT
r ,
I X
L. "
RECTANGULAR DUCT
RECTANGULAR DUCT
ElaD
I I
I BIRDSCREEN OR SCREENED OPENING
SUPPLY GRILLE
RETURN OR EXHAUST GRILLE
VOLUME DAMPER
MOTOR OPERATED DAMPER
AIRFLOW MONITOR
REMOTELY OPERATED VOLUME DAMPER
(YOUNG REGULATOR OR APPROVED)
BACK DRAFT DAMPER
COORDINATE WITH CEILING APPURTENANCES_
FLEX CONNECTION
FIRE DAMPER THROUGH WALL
FIRE DAMPER THROUGH FLOOR
FIRE /SMOKE DAMPER THROUGH WALL
FIRE /SMOKE DAMPER THROUGH FLOOR
ACCESS DOORS
1' ACOUSTICALLY LINED DUCT
2' ACOUSTICALLY LINED DUCT
CHANGE OF ELEVATION RISE(R) DROP(D)
TRANSITION
TURNING VANES
SMOKE DETECTOR
C�>
THERMOSTAT
SENSOR
RETURN / EXHAUST / OUTSIDE AIR
SUPPLY / TRANSFER AIR
TERMINAL UNITS - SEE SCHEDULE FOR TYPE
SUPPLY AIR DUCT
TURNING UP OR TOWARD
SUPPLY AIR DUCT
TURNING DOWN OR AWAY
EXHAUST OR RETURN AIR DUCT
TURNING UP OR TOWARD
EXHAUST OR RETURN AIR DUCT
TURNING DOWN OR AWAY
ROUND DUCT
TURNING UP OR TOWARD
ROUND DUCT
TURNING DOWN OR AWAY
OVAL DUCT
TURNING UP OR TOWARD
OVAL DUCT
TURNING DOWN OR AWAY
FLEXIBLE DUCT
INSTRUMENTATION AND CONTROLS
CARBON MONOXIDE SENSOR
VISUAL ALARM LIGHT - WALL MOUNTED
TL �4
GRILLE/REGISTER /DIFFUSER
DOUBLE LINE
4-
x
t
X
I
S- C8 -09 -A
000
000
▪ CEILING SUPPLY AIR DIFFUSER
HVAC - ANNOTATION
VAV BOX TAG
1 -23
S- C8 -09- -A
1 1 •
DUCTWORK
EQUIPMENT TAG
CEILING RETURN, EXHAUST
OR TRANSFER AIR GRILLE
LINEAR DIFFUSER (CEILING)
LINEAR DIFFUSER (WALL)
LOUVER PLAN VIEW
LOUVER (ELEVATION VIEW)
95 ROUND DUCT SYMBOL
-8- FLAT OVAL DUCT SYMBOL
IEF -2 -1I
— CONSECUTIVE
EQUIP. II
FLOOR OF EQUIP_
LOCATION
EQUIPMENT
DESIGNATION
GRILLE, REGISTER, OR DIFFUSER TAG
DT5 -618 CFM EACH
SIZE
TYPE CODE
LOUVER TAG
LEGAL DESCRIPTION
LOCATION / SITE MAP
CEILING SUPPLY AIR DIFFUSER
(SHOWN WITH THROW ARROWS)
I CONSECUTIVE
LOUVER it_
FLOOR LOCATED
FLOOR # - DISCRETE BOX #
SEE BELOW
PRIMARY CFM
FAN CFM
ACOUSTICAL ACCESSORIES (IF REQ'D)
KW OF AUX. HEAT.
VAV BOX SIZE; SEE SCHED_
SERIES FAN POWERED BOX (5)
PARALLEL FAN POWERED BO (P)
EQUIPMENT TAG
1-1)513 CFM DIFFUSER GRILLE
1 CFM EACH
I ACTIVE LENGTH IN FT.
TOTAL LENGTH IN FT.
TYPE CODE
LOUVER TAG
FACADE DESIGNATION
B - BANK
M - MUSEUM
NE 1/4 OF THE SE 1/4 AND SE 1/4 OF THE SE 1/4
OF SECTION 9 AND GOV'T LOT 15 AND SW 1/4 OF
THE SW 1 /4 OF SECTION 10, T23N., R4E., W.M. CITY
OF TUKWILA, KING COUNTY, WASHINGTON_
GENERAL INFORMATION SYMBOLS
X X X X X X X X X X X X
X
X
GENERAL NOTES:
DRAWING INDEX
NEW MECHANICAL WORK
FUTURE TI SCOPE & NEW WORK OTHER THAN MECHANICAL
DEMO MECHANICAL WORK
DETAIL OR DIAGRAM NUMBER
SHEET NUMBER
WHERE DETAIL /DIAGRAM SHOWN
SECTION LETTER
SHEET NUMBER WHERE SECTION SHOWN
PLAN NUMBER
SHEET NUMBER WHERE, PLAN SHOWN
REVISION NUMBER - DENOTES NUMBER AND DATE
WHEN REVISION OR ISSUE OCCURED
REVISION CLOUD - DENOTES AREA OF CHANGE
DETAIL REFERENCE OUTLINE
WITH NUMBER AND SHEET LOCATION
MATCHLINE
PLUMBING FIXTURE CALL -OUT
(SEE PLUMBING SCHEDULES)
DRAWING NOTE REFERENCE
POINT OF CONNECTION
CENTERLINE
STRUCTURAL BEAM PENETRATION (SEE M503)
STRUCTURAL BEAM HAUNCH (SEE M503)
1_ VERIFY LOCATIONS AND DIMENSIONS OF ALL EQUIPMENT AND COORDINATE.
ALL WORK PRIOR TO START OF CONSTRUCTION_
2. OBTAIN WRITTEN APPROVAL OF STRUCTURAL ENGINEER PRIOR TO
INSTALLATION OF PENETRATIONS IF NOT SHOWN ON DRAWINGS_
3. REFER TO CIVIL DRAWINGS FOR UTILITY WORK 5' -0 BEYOND THE
BUILDING LINE.
4. CONCRETE EQUIPMENT CURBS, PIPING RAT SLABS, SUMP BASINS, AND ,
HOUSEKEEPING PADS ARE SHOWN FOR APPROXIMATE LOCATION AND SIZE
AND WILL BE PROVIDED BY GENERAL CONTRACTOR. SEE STRUCTURAL
DRAWINGS FOR CONSTRUCTION DETAILS.
5_ COMPLETION AND COMMISSIONING FOR MECHANICAL SYSTEMS
A. RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE
PROVIDED TO THE BUILDING OWNER PER 2006 WASHINGTON STATE
ENERGY CODE (WSEC) SECTION 1416.2.4.3
B_ AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE
PROVIDED TO THE BUILDING OWNER PER WSEC SECTION 1416 :2.4.2
C_ ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRITTEN BALANCE
REPORT SHALL BE PROVIDED TO THE OWNER PER WSEC SECTION
1416.2.1
D_ HVAC CONTROL SYSTEMS SHALL BE TESTED, CALIBRATED AND
ADJUSTED, SEQUENCES OF OPERATION SHALL BE TESTED TO
ENSURE THAT THEY OPERATE IN ACCORD WITH SPECIFICATIONS ,AND
APPROVED PLANS PER WSEC SECTION 1416.2.3.2; NECESSARY
TESTS SHALL BE IDENTIFIED PER WSEC SECTION 1416.2.4.2; A
PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURE AND
RESULTS SHALL BE PREPARED PRIOR TO ISSUANCE OF A FINAL
CERTIFICATE OF OCCUPANCY PER WSEC SECTION 1416.4.2.5.1 AND
1416.3.1; AND A COMPLETE FINAL COMMISSIONING REPORT OF TEST
PROCEDURES AND RESULTS SHALL BE FILED WITH THE OWNER
PER WSEC SECTION 1416.2.52_
6_ THE BUILDING MECHANICAL SYSTEM SHALL COMPLY OR EXCEED THE
REQUIREMENTS AS SET FORTH IN THE 2006 WASHINGTON STATE ENERGY
CODE SECTION 1410 - GENERAL REQUIREMENTS_
7_ THE MINIMUM REQUIREMENTS FOR VENTILATION SHALL COMPLY OR EXCEED
THE 2006 WASHINGTON STATE VENTILATION AND INDOOR AIR QUALITY CODE_
8_ ALL MOTORS PROVIDE BY THE MECHANICAL CONTRACTOR SHALL COMPLY
WITH THE 2006 WASHINGTON STATE ENERGY CODE CHAPTER 15.
9_ INSULATE ALL SYSTEMS AS REQUIRED TO MEET THE 2006 WASHINGTON
STATE ENERGY CODE CHAPTER 14, TABLE 14 -5.
10_ BEFORE MAKING CONNECTIONS TO EQUIPMENT FURNISHED BY THE
OWNER OR OTHERS VERIFY THAT EXACT INFORMATION IS PROVIDED_
11. REFER TO STRUCTURAL DRAWINGS FOR EQUIPMENT SUPPORTS. REFER
TO SHEET M0.1 FOR ADDITIONAL SEISMIC INFORMATION.
Fuel Oil Piping:
Isolate and test existing fuel oil supply and return pipe for leaks. Replace all
pipe that fails test with new as specified in pipe matrix. Replace all existing
sensors and test existing probes.
Provide new pipe from capped and valved end of existing to new emergency
generator.
Test contents of existing fuel oil storage tanks and dispose of all fluids properly.
Install pumps (from building stores) in existing fuel storage tank and connect
to existing double walled fuel oil pipe.
Install new day tanks with pumps. Provide and install all sensors and probes.
Day tank to be provided with float level controls to indicate low level fuel
condition (alarmed), turn on pump at main tank, turn off the main storage tank
pump, and to alarm a high fuel level situation in the day tank and turn on the
return pump.
Controls provided by day tank manufacturer.
FILE COPY
Permit No.
Plan review approval Is slant to emu and
Approval of constnalon documents does not authorize
the violation of any adopted code or ordnance. Receipt
of approved Fwd Copy ands is aclmowledgect
By. — P U e
Date:
City of Tukwila
BUILDING DIVISION
6EPARATE PERMIT
REQUIRED FOR:
❑ Mechanical
❑ ✓Electrical
[ Plumbing
I nrGas Piping
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JAN 0 44008
QEI1MIT CENTER
REVISIONS
No changes shall be mane to the scope
of Veo. - k with:,; i + 1 , )t - '; , i)p)1 . '.i1
r
+ ukw{Ia bu:111,1 i -, n11J;svon
NOTE: Revisions will require
and may include additional onal plan re ew fees. submittal
REVIEWED
CODE APPROVED
3!\ \
S
of Tu QI4 a
DIl
YEN
INCOMPLETE
LTR# I ...
210
GENERATOR ROOM
DESIGN DRAWINGS
instr
fe Of Your Building
SEATTLE:
5005 3RD AVENUE S
PO BOK 24567
SEATTLE, WA 98124
1- 800 -669 -6223
PORTLAND:
12021 NE AIRPORT WAY
SUITE G
PORTLAND, OR 97220
503- 331 -0234
www.mckinstry.com
PROJECT
KING COUNTY
DATA CENTER
AT SABEY CORP
TUK 5 BUILDING
SBC 5201
3355 S. 120th Place
Tukwila, WA 98168
REGISTRATION:
I EXPIRES: 05 - 11 - 09
REVISIONS:
NO DATE
10/3/07
11/13/07
12/5/07
0 01/2/08
McKINSTRY DMSION:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
JOB NUMBER:
DATE
SCALE:
SHEET TITLE:
DESCRIPTION
SCHEMATIC HVAC DESIGN FOR REVIEW
DESIGN DEVELOPMENT
PERMIT SET
REVISION 11
ENGINEERING
T_ DIAZ
B. HUCKINS
M_ WEBB
35776
9 -28 -07
SEE DRAWING
DRAWING INDEX,
SYMBOLS, AND
ABBREVIATIONS
MECHANICAL, PIPING, AND PLUMBING IMPORTANCE FACTOR TABLE
COMPONENT DESCRIPTION
STANDARD
COMPONENT
IP =1.0
CRITICAL
COMPONENT
IP =1.5
NOTES:
HVAC - SHEETMETAL/EQUIPMENT
g Load
g Load,
with Exp.
Anchors
HVAC SUPPLY - MEDIUM PRESSURE
X
.61 g
.55 g
HVAC SUPPLY - LOW PRESSURE
X
.26 g
.44 g
HVAC OUTSIDE AIR
X
Level 1 Ceiling
.23 g
HVAC RETURN
X
.48 g
Level 1
HVAC EXHAUST
X
.34 g
.34 g
TRANSFER AIR DUCT
X
GARAGE EXHAUST
X
GREASE KITCHEN EXHAUST DUCT
(TYPE 1 HOOD EXHAUST)
X
NON - GREASE KITCHEN EXHAUST DUCT
(TYPE 2 HOOD EXHAUST)
X
FLUES - BOILERS, HW HEATERS
X
PIPING
HEATING WATER
X
CONDENSER WATER
X
NATURAL GAS
X
MAKEUP WATER
X
REFRIGERANT
X
PLUMBING
COLD WATER (POTABLE)
X
COLD WATER (NON - POTABLE)
X
HOT WATER (POTABLE)
X
HOT WATER RECIRC (POTABLE)
X
CONDENSATE INDIRECT WASTE
X
NATURAL GAS MEDIUM PRESSURE (2 -5 PSIG)
X
NATURAL GAS LOW PRESSURE ( <14' WC)
X
RAINWATER LEADER/
OVERFLOW RAINWATER LEADER
X
UNDERSLAB DRAINAGE
X
SANITARY VENT
X
SANITARY WASTE
X
Piping Systems - Limited deformability elements and
attachments (Converted to ASD)
Level
Component
Ip = 1.0
Component
Ip = 1.5
g Load
g Load,
with Exp.
Anchors
g Load
g Load,
with Exp.
Anchors
Level 3 Ceiling / Roof
.36 g
.61 g
.55 g
.91 g
Level 2 Ceiling
.26 g
.44 g
.39 g
.65 g
Level 1 Ceiling
.23 g
.32 g
.34 g
.48 g
Level 1
.23 g
.23 g
.34 g
.34 g
Piping Systems - High deformability elements and attachments
(Converted to ASD)
Level
Component
Ip = 1.0
Component
Ip = 1.5
g Load
g Load,
with Exp.
Anchors
g Load
g Load,
with Exp.
Anchors
Level 3 Ceiling / Roof
.26 g
.61 g
.39 g
.91 g
Level 2 Ceiling
.23 g
.44 g
.34 g
.65 g
Level 1 Ceiling
.23 g
.32 g
.34 g
.48 g
Level 1
.23 g
.23 g
.34 g
.34 g
General Mechanical Equipment -
Pressure Vessels and skirts free standing (Converted to ASD)
Level
Component
Ip = 1.0
Component
Ip = 1.5
g Load
g Load,
with Exp.
Anchors
g Load
g Load,
with Exp.
Anchors
Level 3 Ceiling / Roof
.91 g
1.21 g
1.36 g
1.82 g
Level 2 Ceiling
.65 g
1.09 g
.98 g
1.63 g
Level 1 Ceiling
.48 g
.8 g
.72 g
1.2 g
Level 1
.3 g
.5 g
.45 g
.76 g
Piping Systems - Low deformability elements and attachments
(Converted to ASD)
Level
Component
Ip = 1.0
Component
Ip = 1.5
g Load
g Load,
with Exp.
Anchors
g Load
g Load,
with Exp.
Anchors
Level 3 Ceiling / Roof
.61 g
.61 g
.91 g
.91 g
Level 2 Ceiling
.44 g
.44 g
.65 g
.65 g
Level 1 Ceiling
.32 g
.32 g
.48 g
.48 g
Level 1
.23 g
.23 g
.34 g
.34 g
General Mechanical Equipment - Boiler and
furnaces, Other (Converted to ASD)
Level
Component
Ip = 1.0
Component
Ip = 1.5
g Load
g Load,
with Exp.
Anchors
g Load
g Load,
with Exp.
Anchors
Level 3 Ceiling / Roof
.36 g
.61 g
.55 g
.91 g
Level 2 Ceiling
.26 g
.44 g
.39 g
.65 g
Level 1 Ceiling
.23 g
.32 g
.34 g
.48 g
Level 1
.23 g
.23 g
.34 g
.34 g
HVAC Systems - Non - vibration Isolated,
Mounted in -line with ductwork,
Other (Converted to ASD)
Level
Component
Ip = 1.0
Component
Ip = 1.5
g Load
g Load,
with Exp.
Anchors
g Load
g Load,
with Exp.
Anchors
Level 3 Ceiling / Roof
.36 g
.61 g
.55 g
.91 g
Level 2 Ceiling
.26 g
.44 g
.39 g
.65 g
Level 1 Ceiling
.23 g
.32 g
.34 g
.48 g
Level 1
.23 g
.23 g
.34 g
.34 g
HVAC Systems -
Vibration Isolated (Converted to ASD)
Level
Component
Ip = 1.0
Component
Ip = 1.5
g Load
g Load,
with Exp.
Anchors
g Load
g Load,
with Exp.
Anchors
Level 3 Ceiling / Roof
.91 g
1.21 g
1.36 g
1.82 g
Level 2 Ceiling
.65 g
1.09 g
.98 g
1.63 g
Level 1 Ceiling
.48 g
.8 g
.72 g
1.2 g
Level 1
.3 g
.5 g
.45 g
.76 g
General Mechanical Equipment -
Boiler and furnaces, Other
Level
Component
Ip = 1.0
Component
Ip = 1.5
SHL
SHL,
with Exp.
Anchors
SHL
SHL,
with Exp.
Anchors
Level 3 Ceiling / Roof
A
AA
AA
AA*
Level 2 Ceiling
B
A
A
AA
Level 1 Ceiling
B
A
A
A
Level1
B
B
A
A
General Mechanical Equipment -
Pressure Vessels on skirts and free standing
Level
Component
Ip = 1.0
Component
Ip = 1.5
SHL
SHL,
with Exp.
Anchors
SHL,
SHL with Exp.
Anchors
Level 3 Ceiling / Roof
AA*
AA*
AA* - NA -
Level 2 Ceiling
AA
AA*
AA* - NA -
Level 1 Ceiling
A
AA*
AA* AA*
Levell
B
AA
A r AA*
Piping Systems -
High deformability elements and attachments
Level
Component
Ip =1.0
Component
Ip =1.5
SHL
SHL,
with Exp.
Anchors
SHL
SHL,
with Exp.
Anchors
Level 3 Ceiling / Roof
B
AA
A
AA*
Level 2 Ceiling
B
A
A
AA
Level 1 Ceiling
B
A
A
A
Level1
B
B
A
A
Piping Systems -
Low deformability elements and attachments
Level
Component
Ip = 1.0
Component
Ip = 1.5
SHL
SHL,
with Exp.
Anchors
SHL
SHL,
with Exp.
Anchors
Level 3 Ceiling 1 Roof
AA
AA
AA*
AA*
Level 2 Ceiling
A
A
AA
AA
Level 1 Ceiling
A
A
A
A
Levell
B
B
A
A
Piping Systems -
Limited deformability elements and attachments
Level
Component
Ip =1.0
Component
Ip =1.5
SHL
SHL,
with Exp.
Anchors
SHL
SHL,
with Exp.
Anchors
Level 3 Ceiling / Roof
A
AA
AA
AA*
Level 2 Ceiling
B
A
A
AA
Level 1 Ceiling
B
A
A
A
Level1
B
B
A
A
HVAC Systems -
Vibration Isolated
Level
Component
Ip = 1.0
Component
Ip = 1.5
SHL
SHL,
with Exp.
Anchors
SHL
SHL,
with Exp.
Anchors
Level 3 Ceiling / Roof
AA*
AA*
AA*
- NA -
Level 2 Ceiling
AA
AA*
AA*
- NA -
Level 1 Ceiling
A
AA*
AA*
AA*
Levell
B
AA
A
AA*
HVAC Systems -
Non-vibration Isolated, Mounted in -line with ductwork,
Other
Level
Component
Ip = 1.0
Component
Ip = 1.5
SHL
SHL,
with Exp.
Anchors
SHL
SHL,
with Exp.
Anchors
Level 3 Ceiling / Roof
A
AA
AA
AA*
Level 2 Ceiling
B
A
A
AA
Level 1 Ceiling
B
A
A
A
Level1
B
A
A
A
OR
SEIS
V
IC BASIS OF DESIG \
BRACE ALL DUCTWORK AND PIPING PER SMACNA'S "SEISMIC RESTRAINT MANUAL" OR MASON INDUSTRIES "SEISMIC RESTRAINT MANUAL"
IN ACCORDANCE WITH THE COMPONENT IMPORTANCE FACTOR AND THE SEISMIC HAZARD LEVEL (SHL) OR 'g' LOAD LISTED IN THE
APPLICABLE TABLE. OBTAIN THE COMPONENT IMPORTANCE FACTOR FROM THE DUCT WORK OR PIPING MATRIX.
SEISMIC RESTRAINTS MAY BE EXCLUDED WHEN Ip, = 1.0:
• MECHANICAL AND ELECTRICAL COMPONENTS IN SEISMIC DESIGN CATEGORIES D, E, AND F WHERE Ip - 1.0 AND FLEXIBLE
CONNECTIONS BETWEEN THE COMPONENTS AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT ARE PROVIDED AND THAT ARE
MOUNTED AT 4 FT (1.22M) OR LESS ABOVE A FLOOR LEVEL AND WEIGH 400 LB (1780 N) OR LESS.
[ASCE 7 -02 SECTION 9.6.1 - EXCEPTION #5]
• MECHANICAL AND ELECTRICAL COMPONENTS IN SEISMIC DESIGN CATEGORIES D, E, AND F WEIGHING 20 LB (95 N) OR LESS WHERE
Ip = 1.0 AND FLEXIBLE CONNECTIONS BETWEEN THE COMPONENTS AND ASSOCIATED DUCTWORK, PIPING, AND CONDUIT ARE
PROVIDED, OR FOR DISTRIBUTION SYSTEMS WEIGHT 5 LB /FT (7N /M) OR LESS.
[ASCE 7 -02 SECTION 9.6.1 - EXCEPTION #6]
• SEISMIC RESTRAINTS ARE NOT REQUIRED FOR HVAC DUCTS WITH Ip - 1.0 IF EITHER OF THE FOLLOWING CONDITIONS ARE MET:
A. HVAC DUCTS ARE SUSPENDED FROM HANGERS 12 IN. (305 MM) OR LESS IN LENGTH FROM THE TOP OF THE DUCT TO THE
SUPPORTING STRUCTURE. THE HANGERS SHALL BE DETAILED TO AVOID SIGNIFICANT BENDING OF THE HANGERS AND THEIR
ATTACHMENTS.
B. HVAC DUCTS HAVE A CROSS- SECTIONAL AREA OF LESS THAN 6 FT (0.557M
[ASCE 7 -02 SECTION 9.6.3.10]
• DUCTILE PIPING IN SEISMIC DESIGN CATEGORIES D, E, OR F DESIGNATED AS HAVING AN Ip = 1.0 AND A NOMINAL PIPE SIZE OF 3
IN. (75 MM) OR LESS.
[ASCE 7 -02 SECTION 9.6.3.11.D.3]
SEISMIC RESTRAINTS MAY BE EXCLUDED WHEN
1 = 1.0 OR I. = 1.5:
• EQUIPMENT ITEMS INSTALLED IN -LINE WITH THE DUCT SYSTEM (E.G. FANS, HEAT EXCHANGERS, AND HUMIDIFIERS) WEIGHING LESS
THAN 75 LB (344 N) DO NOT NEED TO BE BRACED INDEPENDENT OF THE DUCT SYSTEM. [INTERPRETED FROM ASCE 7 -02 SECTION
9.6.3.10] UNBRACED PIPING ATTACHED TO IN -LINE EQUIPMENT SHALL BE PROVIDED WITH ADEQUATE FLEXIBILITY TO ACCOMMODATE
DIFFERENTIAL DISPLACEMENTS.
[ASCE 7 -02 SECTION 9.6.3.10]
• PIPING - ROD HANGERS SHALL NOT BE USED AS SEISMIC SUPPORTS UNLESS THE LENGTH OF THE HANGER FROM THE SUPPORTING
STRUCTURE IS 12 IN. (305 MM) OR LESS. ROD HANGERS SHALL NOT BE CONSTRUCTED IN A MANNER THAT SUBJECTS THE ROD
TO BENDING MOMENTS.
[ASCE 7 -02 SECTION 9.6.3.11.4.C]
S
V
AC \A SEJSV
IC HAZARD LEVEL DESIG\
• SEISMIC DESIGN VALUES ARE CALCULATED IN ACCORDANCE WITH IBC 2003. IBC FORCES ARE
"STRENGTH DESIGN" BASED. VALUES HAVE BEEN USED TO SELECT FROM SMACNA ADDENDUM NO. 1
TABLE AA -10 "NEW" VALUES IN ORDER TO USE THE SMACNA SEISMIC RETRAINT MANUAL.
VALUES:
* 1/2 Brace Spacing Required
* 1/2 Brace Spacing Required
HVAC/SHEETV ETAL/EQUIPV E\T
SHL DESIG\ VALUES
* 1/2 Brace Spacing Required
* 1/2 Brace Spacing Required
PIPI\
SHL
* 1/2 Brace Spacing Required
Highly Deformable Pipe Includes: Steel or Copper Piping
with weld/braze /groove fitted joints.
* 1/2 Brace Spacing Required
Limited Deformable Pipe Includes: PVC or PVDF Piping
G A \J
DESIG\
PLUVB\G
VALUES:
* 1/2 Brace Spacing Required
Low Deformability Piping Includes: Cast Iron, Glass Pipe,
FRP (Fiberglass Reinforced Pipe)
SETS
V
IC ALLOWABLE STRESS DESIG\ VALUES:
• SEISMIC DESIGN VALUES ARE CALCULATED IN ACCORDANCE WITH IBC 2003. IBC FORCES ARE
"STRENGTH DESIGN" BASED. VALUES HAVE BEEN CONVERTED TO "ALLOWABLE STRESS DESIGN" VALUES
IN ORDER TO UTILIZE MASON INDUSTRIES SEISMIC RESTRAINT GUIDELINES.
THESE VALUES CAN BE USED TO SELECT SEISMIC BRACING FROM MASON INDUSTRIES SEISMIC
RESTRAINT GUIDELINES.
HVAC /SHEETV ETAL/EQUH
SEISVC 'g' LOAD:
V
E
\T
PIPI \G
SEIS
Highly Deformable Pipe Includes: Steel or Copper Piping with
weld/braze /groove fitted joints.
Limited Deformable Pipe Includes: PVC or PVDF Piping
J PLUV1R\
'g' LOAD
G
Low Deformability Piping Includes: Cast Iron, Glass Pipe,
FRP (Fiberglass Reinforced Pipe)
Mod - 290
I REVIEWED FOR 1
CODE COMPLIANCE
APPROVED
i/'N 1. 11 2008
GENERATOR ROOK
DESIGN DRAWINGS
City Of Tukwila
+�
B . ILDING DMSIDN
instry
le Of Your Building
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
PORTLAND:
12021 NE AIRPORT WAY
SUITE G
PORTLAND, OR 97220
503- 331 -0234
www.mckinstry.com
KING COUNTY
DATA CENTER
AT SABEY CORP
TUK 5 BUILDING
SBC 5201
3355 S. 120th Place
Tukwila, WA 98168
REGISTRATION:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
JOB NUMBER:
DATE:
SCALE:
SHEET NUMBER:
I EXPIRES: 05-11-09
REVISIONS:
NO DATE DESCRIPTION
10/3/07 SCHEMATIC HVAC DESIGN FOR REVIEW
11/13/07 DESIGN DEVELOPMENT
12/5/07 PERMIT SET
McKINSTRY DMSION:
ENGINEERING
T. DIAZ
B. HUCKINS
M. WEBB
35776
9 -28 -07
SEE DRAWING
SHEET TITLE:
SEISMIC
INFORMATION
M0.1
RECEIVED
DEC 2 6 2007
PERMIT CEN 1 F4:
GENERATOR FAN SCHEDULE
TAG #
EF -1
EF -2
EF -3
EF-4
BASIS OF DESIGN MANUF.
GREENHECK
GREENHECK
GREENHECK
GREENHECK
MODEL
S2- 30- 615 -B15
S2- 30- 620 -B20
S2 -30- 620 -B20
52- 30- 620 -B20
SERVICE
GENERATOR EXHAUST
GENERATOR EXHAUST
GENERATOR EXHAUST
GENERATOR EXHAUST
FAN TYPE
PROPELLER
PROPELLER
PROPELLER
PROPELLER
MOUNTING
SIDEWALL
SIDEWALL
SIDEWALL
SIDEWALL
CFM @ 70F
10,800
10,800
10,800
10,800
E.S.P.
.25"
.25"
.25"
.25"
BHP /HP
1.72/1.5
1.72/1.5
1.72/1.5
1.72/1.5
VOLTAGE/PHASE
460/3
460/3
460/3
460/3
MOTOR EFFICIENCY
CODE MIN.
CODE MIN.
CODE MIN.
CODE MIN.
OVERALL WIDTH
22
22
22
22
OVERALL LENGTH
38
38
38
38
TOTAL WEIGHT (LBS)
130
130
130
130
SOUND CELLS
(120 SF MIN.)I,
•"1
ND SCREEN
SEE NOTE #2
14" INLET, X 18" CUTLET,
"Y' FITTING
MUFFLER PROVIDED BY OTHERS.
SEE, PLAN NOTE #1:
L
18" STACK. TERMINATE WITH RAIN CAP.
MATCH EXISTING MATERIALS. PROVIDE
DRAIN SECTION AT - EXTERIOR ELBOW !}
PROVIDE WALL SUPPORTS SPACED TO
MATCH EXISTING. <;
4
NOTE: FOR FUEL OIL PIPING SEE PLUMBING DRAWINGS
Note:
Control with wall mounted thermostat. Fan on at 90' F., off at 80' F (adjustable).
Fans EF -3 and EF -4 are future fans.
JCILI
SOUND CELLS AND SCREEN
(288 SF MIN.) SEE NOTE #2
1 HVAC 1ST FLOOR GENERATOR ROOM 400
M2.1 SCALE : 1/8" 1' -0"
F=
FE
�Ir
PLAN NOTES:
® PROVIDE 14" PIPE FROM GENERATOR EXHAUST
TO MUFFLER INLET AND ALL PIPE DOWNSTREAM
OF MUFFLER OUTLET. HANG MUFFLER AND
ALL PIPE FROM CEILING. INSULATE ALL PIPE
AND MUFFLER IN GENERATOR ROOM.
Q USE EXISTING SOUND CELLS FROM BUILDING
STORES. IF ADDITIONAL SOUND CELLS ARE
REQUIRED, PROVIDE DYNASONIC MODEL LBB
(5 FT. LONG) 24" x24" OR 48"x24" TO
PROVIDE REQUIRED AREA.
REVIEWED FOR
CODE COMPLIANCE
APPROVE
10 1F?
City Of iukvvil
ILDING DI`IIS1Q
BUILDING KEY PLAN
NO SCALE
t4O12c?O
GE
ERATOR R00
DESIGN DRAWINGS
KING COUNTY
DATA CENTER
AT SABEY CORP
TUK 5 BUILDING
SBC 5201
3355 S. 120th Place
Tukwila, WA 98168
REGISTRATION:
REVISIONS:
NO DATE DESCRIPTION
10/3/07 SCHEMATIC HVAC DESIGN FOR REVIEW
11/13/07 DESIGN DEVELOPMENT
12/5/07 PERMIT SET
McKINSTRY DMSION:
ENGINEERING
DESIGNED BY:
DRAWN BY:
CHECKED BY:
JOB NUMBER:
DATE:
SCALE
SHEET TITLE:
HVAC 1ST FLOOR PLAN
SHEET NUMBER:
T. DIAZ
B. HUCKINS
M. WEBB
35776
9 -28 -07
SEE DRAWING
instr
le Of Your Building
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1 -800- 669 -6223
PORTLAND:
12021 NE AIRPORT WAY
SUITE G
PORTLAND, OR 97220
503-331-0234
M2,1
www.mckinstry.com
I EXPIRES: 05 -11 -09
RECEIVED
DEC 2 6 Z00
PERMIT CEN I I.
F
I 7
„
' I -1 S 7- •
117 ‘--11--
r
I
FO ADDITIONAL FUEL OIL
PlpING WORK IN THIS AREA
SEE
2
P2.1
2
P2.1
SCALE: 1/8"=1'-0"
AZ
4
FA-10
-
' 1 P 7 FAT 11'4 2■ Jd SA
(f '
--M-
12L_Z - SL
ThP '11
L • 6 21'.1 .18 SA
1
1 03 1311.....
•
I dr •
1 •
FzI•1.1
FUTURE DAY TANKS
150:41 FLA
HOD 13
• ir
L6C1T, 10' -51"
r EF'• 2 S 71 5. '2CF110
i ry.:F 14.6
71. KNA
FOR ADDITIONAL INFORMATION
SEE PIPING DIAGRAM, P6.0
1 IL: LI
ENLARGED PLUMBING PLAN
NIA,: P.:
El ' BA1.2 SA. - ELM: '251, til
25.x' SA TY.1J
. II J
•
'7
AL)
- -
( 7"
, I
1 -1/2"
1
ROE: -,-.."
It..L:,' A1J LF1HAL"1 1 1
1
11.121.1 S 'J A05" .
1 FIA. "1.155'
AFC " F1.....1. "15
'-'IHkkr GI , 1'...511. ,.1
P.3,1 Br' rAl
MAN, . r.a,.: F Fe -1 . 7
• ,
1RAI•4'51 ' 55,44 151
H4' 11 9,5 1 019E F EX
A FAN
= I HANSI 11C1 8 4"
,32 PRO.k..IDE F LEY
Cr7.1F11^J.C 01 AT FAN
\-GENERATORS
(BY OWNER)
cA:x44 F.;
C
'LS1
1 .12* .
oD 11 -Li"
1.•
1-1/2 & FOR ®
'X' 1 C.: G.;
21^
. SA
Hir. •
L
1A Z
22:3 C11..1
/4k1^
FRfl
146 ,
1 16
7- 10,..0100#
A3[ EI-6;•
• -
- 1S1
14
1.4
• ‘) I
\ I I,
• i121x5'.7 IA.A■
' '
Cehr
'2
tr.ismi.I.p111
, ,
- AFF
-..
r THF J C
1
• 44A:131
I T (
I .
7 :IP . O r t1
LO
UF ALA
4 -11"
-
Try
c".14 „
.s m
',V:AdEN
. -1:14' in: :Jai
41 I CF[A
r
• •
12F LI
I
•
A
Z
A.
V A
I C; • '
7 : i
FUN • FA U.: L,
V FL. '. 41- • .
.PL '211"Fl F111 1-P1111
1 .14.1t1: A,L ALL PL.HE I.
r I
1
H
1::rJAkt t.0
I ['
- :'4"F/[A,
FAD '
1
1 5' '.
"'"Ar
F AA
.• cH 1,4 P
p A
'
.r.
FIFLA•
,e
Fi FA F.
-A LF
x
"Ar
EXISTI
SU PF
H[i 2[
POC
1
P2.1
'411 •
(3
ret [DELL:
0,1E'
'Jr,
74 F'A
1; TY ALT I
11
1 1. ^A^1
. I., •LFII
7
I 2,'RDSCR:E1 , HA
I DPL1.111
FA
CF
+37 17711
17 , TlD1
2,
• /
. 7
.•
,LE. 44 I r2
.4
FF:l1.1
:: '11-ttPH4f.
r_
E]ri
Mom
Ii nit L'
CIIST01.1ER..
1 7;0. 1 4 1 ,
• 2 .3E: F
•r,
1
•
H ,..94#.1 , Li.
b. 03,
60,^3 13'
PLAN NOTES:
O EXISTING FUEL OIL TANK IS FILLED WITH WATER.
TEST WATER QUALITY IN EXISTING FUEL TANK AND
PROPERLY DISPOSE.
C) ISOLATE AND TEST EXISTING DOUBLE WALLED PIPE
BETWEEN TANK AND POC.
® INSTALL FUEL OIL PUMP FROM BUILDING STORED.
CONNECT TO EXISTING FUEL OIL SUPPLY PIPE.
CONNECT FUEL OIL RETURN PIPE TO TANK.
0 PROVIDE VALVED AND CAPPED 1-1/2" FUTURE
CONNECTION.
•
•
12." .r Aft
•
•
5.1.t,.1 AlA
22
F. I
13FIF.1
71
•;.;"
O REPLACE ALL SENSORS AND VERIFY THE CONDITION
OF ALL PROBES.
® CONNECT NEW FUEL OIL SUPPLY AND RETURN PIPE
TO EXISTING.
O TWO FOS AND TWO FOR PIPES IN EXISTING TRENCH
TO DAYTAN K.
6;1 FA
E112') '
• S4AA RA F1' )F'
10= AC
r7' 1
T '1
17,
/ PT('
VI FM' 2,1
21_
•
•
1 SF 1
, _I FA, 52,
:11
.4 1
ALL SC HIAL P 1' ,r1,_
r.A44FLP.3 ak ee tic
.QE! I 2 1 ATI^ L;1^'
CAC.11.1c.: [Ka,
. 1 C
I
'"
84.01 FA
012E; 1 5'
64 I 2 F
4311 r.FIALI
.51"x42
K1C. ' 3' • 3' el-t.F
11
A'1 , :•Ft.F1
ii• ,
P 1:5A
?F1(.2.'IDE THANE ELF:271 . .11 - 111
-1E,TER, 1 ..10LIEL ..11-:EL 7.1•V,
YrA I. PReg
'AA, L
IFFAIT ,TAT •
cf;
C3,31:
2:51E1 r.F'm
I
A
AL
1- 1
Al')
V. FP.,..AV
a: .111.1
EXISTING FUEL 01
TO GE TANK
1 F
I : OF 1.i
•
1 .;,■
7
NEW FUL OIL PUMP
FOP-5201141 & 5201-B
A.
215
1.1
- I 26 011121. Of F12 .:)1 I Kn
".IM
7 EXISTING 7 1.J EAU_
SUPPLY RETURN PIPES (3
,,•6 IC Cr I
31 'TV
PARTIAL COMPOSITE FIRST FLOOR PLUMBING PLAN ED
SCALE: 1/16" = r-O"
2 '22 --i11•,=4
71
A3,I ,AAA
1
\71
,--114 Ps;
E3 12 4"
,
IA SpA
26.:17: • -
L. AF',' 1111P11,
GENERAL NOTES
1. ALL FUEL OIL PIPING LOW POINTS SHALL HAVE SUMP WITH LEAK
DETECTOR.
2. COORDINATE ALL WORK WITH PRE-PURCHASED EMERGENCY
GENERATOR.
3. DAY TANK SHALL BE INSTALLED BY CONTRACTOR FOR EACH
GENERATOR. CONTRACTOR SHALL PROVIDE ALL NECESSARY
COMPONENTS INCLUDING VALVES, GAGES, FLEX CONNECTIONS AND
FITTINGS AS INDICATED, SHOWN, OR REQUIRED.
4. ALL CONTROL AND POWER WIRING SHALL BE IN RIGID CONDUIT.
rn2 ni
•s4;`
:N]
FALL' 1tP.1,1
WALL A I
:1 1 ,
•
V rA V L
t rt
r Itr;
-r
1,
11. ( V l
1-25
AREA OF WORK
-; •
EaqteFe 6 HO . 1
2 IF'
INIERN41.
2, A.,f, Alt}
▪ 9nr. ILL r •
LLS
i,DEI 11' -0"
•
34'LA
22:
50,2 - 2'
•
•
, v
`...;r
• 7C7.7-1 5 11, , ,
•
-3
12 .T.1
C1,3
! 452 (A
LI --
.11 br.r..IAL
ZH
rt
, _ LINIF10
A4'
CF
1 lL
12 ILL
2'!
1 31,
• A
- 0." I
,.
.11.1r17,
NO SCALE
tit 0 1 yaw 1 7. 4. tr i
BUILDING KEY PLAN
GENERATOR ROO
DESIGN DRAWINGS
PROJECT:
KING COUNTY
DATA CENTER
AT SABEY CORP
TUK 5 BUILDING
SBC 5201
3355 S. 120th Place
Tukwila, WA 98168
REGISTRATION:
REVISIONS:
140 DATE DESCRIPTION
10/3/07 SCHEMATIC HVAC DESIGN FOR REVIEW
11/13/07 DESIGN DEVELOPMENT
r■r
rlawlp.■1.•
r■•
12/5/07 PERMIT SET
McKINSTRY DIVISION:
ENGINEERING
DESIGNED BY: T. DIAZ
DRAWN BY: B. HUCKINS
CHECKED BY: M. WEBB
JOB NUMBER: 35776
DATE: 9-28-07
SCALE: SEE DRAWING
SHEET TIME:
PLUMBING 1ST
FLOOR PLAN
SHEET NUMBER:
instr
le Of Your Building
P2.1
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1-800-669-6223
PORTLAND:
12021 NE AIRPORT WAY
SUITE G
PORTLAND, OR 97220
503-331-0234
www.mckinstry.com
I EXPIRES: 05-11-09
RECEWD
DEC 2 6 2007
PERMiT CEN rF
ISOLATION
VALVE (TYP)
NO
4 —I6N I 1" FOS 16
NC'
EMERGENCY FILL
SOLENOID VALVE
NORMAL FILL
SOLENOID VALVE
BYPASS VALVE
NC
1
NO �.
FUEL OIL SUPPLY
LD —N
LEAK DETECTOR
�I NC
1 "BYPASS —IFS
FUEL OIL OVERFLOW
LEVEL CONTROLLER
PRIMARY TANK
EMERGENCY VENT
M6.0
DAY TANK WILL INCLUDE:
TO FUEL
OIL RETURN
FLOW SWITCH
1" FOS
NOT TO SCALE
1 -1/2"
I
V
NOTE:
ONE RETURN PUMP PER DAYTANK.
SEE SCHEDULE, SHEET P7.0
(FOP 5202 —A & FOP 5202 -3)
NORMAL VENT
I CV FUEL OIL
OVERFLOW PUMP
(SEE NOTE)
PRESSURE
RELIEF VALVE
SECONDARY TANK
EMERGENCY VENT
HIGH LEVEL ALARM
I OVERFLOW PUMP ON
`l FUEL PUMP OFF
b FUEL PUMP ON
EP LOW LEVEL ALARM
ASV
--- GENERATOR
FUEL SUPPLY
■
FOR —I6
LG
LEVEL GAUGE
-I
_1
DAY TANK PIPING DIAGRAM (TYP. EACH GEN. SET)
FUEL OIL SYSTEM OPERATION NOTES:
ANTISIPHON VALVE
FIRE SAFETY
VALVE
FUEL PURIFIER (TYP)
GEN. SET
RUPTURE BASIN
DIP TUBE (TYP)
DOUBLE POPPET
FOOT VALVE (TYP)
FOR
LEAK DETECTION SENSOR FOR CONTAINMENT
FLOAT SWITCH TWO 5 LEVEL FLOAT SWITCH WITH BRASS STEM AND LOCKING
RINGS,
LOW LEVEL -- 45% FULL
SUPPLY PUMP ON - 50% FULL
ALL PUMPS OFF -- 85% FULL
HIGH RETURN PUMP ON - 90% FULL
HIGH LEVEL I LAG RETURN PUMP ON 95% FULL
FUEL LEVEL GUAGE -- FRACTIONAL LEVEL INDICATION.
• CONTROL PANEL (SHIPPED LOOSE; PROVIDED BY TANK MFR) SYSTEM
REQUIREMENTS: 240 /1 PH, 60 HZ.
FOS
AS FUEL IS CONSUMED FROM THE DAY TANK, THE "SUPPLY PUMP ON" FLOAT WILL MAKE
ON DROP, AUTOMATICALLY ENGAGING A SUPPLY PUMP. THE SUPPLY PUMP WILL
REMAIN ENGAGED, FILING THE DAY TANK UNTIL THE "PUMPS OFF" FLOAT BRAKES ON
RISE. PUMPS WILL AUTOMATICALLY ALTERNATE EACH TIME THE TANK CALLS FOR
FUEL.
IF THE FUEL SHOULD EVER REACH A LOW CONDITION, THE LOW LEVEL FLOAT SWITC
WILL MAKE ON DROP. THE SYSTEM WILL DISPLAY A "LOW LEVEL" ALARM CONDTION
AND SOUND THE PANEL MOUNTED ALARM BUZZER.
IF THE FUEL SHOULD EVER EMPTY INTO A `FULL" TANK BEYOND THE PUMPS OFF FLOA
THE RETURN PUMP FLOAT SWITCH WILL MAKE ON RISE. THE RETURN PUMP WILL
ENGAGE UNTIL THE "PUMPS OFF" FLOAT MAKES ON DROP.
IF THE FUEL SHOULD EVER REACH A HIGH LEVEL CONDITION, THE HIGH LEVEL FLOAT
SWITCH WILL MAKE ON RISE. THE SYSTEM WILL DISPLAY A "HIGH LEVEL" ALARM
CONDITION, SOUND THE PANEL MOUNTED ALARM BUZZER AND THE RETURN PUMP WILL
ENGAGE. THE RETURN PUMP WILL REMAIN ENGAGED UNTIL THE "PUMP OFF" FLOAT
MAKES ON DROP.
IF LEAK DETECTOR SENSOR SWITCH MAKES, THE SYSTEM WILL DISPLAY A "DAYTANK
BASIN LEAK DETECTED" ALARM CONDITION AND SOUND THE PANEL MOUNTED ALARM
BUZZER.
THE SUPPLY PUMPS WILL BE LOCKED OUT IF THE SYSTEM RECEIVES A LEAK DETECTED,
OR A HIGH LEVEL OR LOW LEVEL SIGNAL UNTIL THE ALARM IS CLEARED AND THE
SYSTEM IS RESET.
1"O'7' 2q 0
REVIEWED
CEDE APPROVED
301( 'scab-
City Of TUIY4IIa
BO-DIN
GENERATOR R00
DESIGN DRAWINGS
V
:ya
PROJECT:
KING COUNTY
DATA CENTER
AT SABEY CORP
TUK 5 BUILDING
SBC 5201
3355 S. 120th Place
Tukwila, WA 98168
REGISTRATION:
REVISIONS:
NO DATE DESCRIPTION
10/3/07 SCHEMATIC HVAC DESIGN FOR REVIEW
11/13/07 DESIGN DEVELOPMENT
12/5/07 PERMIT SET
McKINSTRY DMSION:
ENGINEERING
DESIGNED BY: T. DIAZ
DRAWN BY: B. HUCKINS
CHECKED BY: M. WEBB
JOB NUMBER: 35776
DATE 9 -28 -07
SCALE: SEE DRAWING
SHEET TITLE:
PLUMBING DIAGRAMS
AND DETAILS
SHEET NUMBER:
instr
le Of Your Building
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1 -800- 669 -6223
PORTLAND:
12021 NE AIRPORT WAY
SUITE G
PORTLAND, OR 97220
503 - 331 -0234
www.mckinstry.com
I EXPIRES: 05 -11 -09
RECEIVED
DEC 2, 6 2007
PERMIT CENTER
P6.0
SERVICE ID
SERVICE DESCRIPTION
LOCATION / AREA
DESIGN
PRESSURE
(PSIG)
SIZE
MATERIAL
CONNECTION
TYPE & FITTINGS
FLANGES, UNIONS &
CPLGS
FLEX CONNECTIONS
EXPANSION
JOINTS
ISOLATION VALVE
TYPE
ISOLATION VALVE
ACTUAL MFR &
MODEL
CHECK VALVE
ACTUAL MFR &
MODEL
BALANCE
VALVE MFR &
MODEL
STRAINERS
ACTUAL MODEL
PRESSURE
GAUGES ACTUAL
MODEL
TEMPERATURE
GAUGES ACTUAL
MODEL
TEST PROCEDURE
NOTE: ISOLATE ALL EQUIPMENT PRIOR TO TESTING
TEST
PRESSURE
(PSIG) [3]
INSULATION
CATEGORY
SEISMIC
BRACING
IMPORTANCE
FACTOR
REMARKS
MEDIA
MINIMUM TEST
PRESSURE
MAXIMUM TEST
PRESSURE
MINIMUM DURATION
FOV
FUEL OIL VENT
ALL
25
2° AND SMALLER
CARBON STEEL PIPE
A53B ERW
STANDARD WEIGHT
SOCKETWELD
WHERE
CONCEALED OR
INACCESSIBLE,
THREADED
ELSEWHERE
M.I. UNION
Anvil Fig. 463
Class 150
300 psi WOG
INCLUDED IN FUEL
PACKAGE
SUBMITTAL
NA
MOTOR TYPE
NA
NA
VOLTAGE/PHASE
208/230 1 PH
208/230 1 PH
MOTOR EFFICIENCY
WATER OR AIR
WATER: 150% OF MAX.OPER.
PRESSURE
AIR: 110% OF
MAX. OPER.
PRESSURE, NOT
LESS THAN 5
PSIG
MAX. ALLOWABLE TEST
PRESSURE ANY
COMPONENT OR 90% OF
YIELD
NOT LESS THAN 10 MINUTES,
LOWER TO DESIGN PRESSURE FOR
24 HOURS AND PERFORM A VISUAL
INSPECTION WITH NO LEAKS
NO
STARTER, DISCONNECT
1.5
BY ELEC.
2 -1/2" AND
LARGER
BUTTWELD
150# WELD NECK
FLANGE
FOS & R
FUEL OIL SUPPLY &
RETURN
ALL
125
2" AND SMALLER
PVDF
DOUBLE WALL PIPE
SOCKETWELD
WHERE
CONCEALED OR
INACCESSIBLE,
THREADED
ELSEWHERE
M.I. UNION
Anvil Fig. 463
Class 150
300 psi WOG
INCLUDED IN FUEL
PACKAGE
SUBMITTAL
WATER OR AIR
WATER: 150% OF MAX.OPER.
PRESSURE
o
AIR: 110% OF
MAX. OPER.
PRESSURE, NOT
LESS THAN 5
PSIG
MAX. ALLOWABLE TEST
PRESSURE ANY
COMPONENT OR 90% OF
YIELD
NOT LESS THAN 10 MINUTES,
LOWER TO DESIGN PRESSURE FOR
24 HOURS AND PERFORM A VISUAL
INSPECTION WITH NO LEAKS
1.5
2 -1/2" AND
LARGER
BUTTWELD
150# WELD NECK
FLANGE
GEX
GENERATOR EXHAUST
ALL
150
ALL
CARBON STEEL PIPE
A53B ERW
STANDARD WEIGHT
BUTTWELD
150# WELD NECK
FLANGE
PROVIDED BY
OTHERS
UNISOURCE
SERIES CF
N/A
N/A
N/A
N/A
GENERATOR
EXHAUST TO 1100
1.5
TAG #
FOP - 5201 -A, 5201 -B
FOP - 5202 -A, - 5202 -B
QUANTITY
2
2
BASIS OF DESIGN
RED JACKET
RED JACKET
MODEL NUMBER
P7551
P7552
SERVICE
FUEL OIL
FUEL OIL
LOCATION
MAIN FUEL OIL TANK
FUEL OIL DAY TANK
FLOW
40 GPM
40 GPM
FT. TOTAL HEAD
60
60
MAX FLUID PRESSURE PSIG
CHILLED WATER
40 -55 0.23 -0.27
%g GLYCOL IN FLUID
NONE
NONE
MOTOR HP
3/4
3/4
MOTOR BRAKE HP
NA
NA
MOTOR TYPE
NA
NA
VOLTAGE/PHASE
208/230 1 PH
208/230 1 PH
MOTOR EFFICIENCY
PER WSEC
PER WSEC
VFD
NO
NO
STARTER, DISCONNECT
BY ELEC.
BY ELEC.
WEIGHT
PIPE & EQUIPMENT INSULATION SCHEDULE
PIPING
SYSTEM
TEMP
RANGE
THERMAL
COND.
MEAN RAT.
TEMP.
INSULATION
MATERIAL
INSULATION THICKNESS BY PIPE SIZE
INSUL.
HANGERS
RUNOUTS TO 2" (2)
1" AND LESS
1 1/4" TO 2"
2 1/2 TO 4"
5" TO 6"
OVER 6"
NON - POTABLE COLD
ALL 0.23 -0.27
75
FIBERGLASS
0.5
0.5
0.5
0.5
0.5
0.5
NOTES 4, 5
CHILLED WATER
40 -55 0.23 -0.27
75
FIBERGLASS
0.5
0.5
0.75
1.0
1.0
1.0
NOTES 4, 5
COIL CONDENSATE
ALL 1 0.23 -0.27
75
FIBERGLASS
0.5
0.5
0.5
0.5
0.5
0.5
NOTES 4, 5
DAY TANK SCHEDULE
TAG #
DT -1
DT -2
QUANTITY
1
1
BASIS OF DESIGN
ACE TANK
ACE TANK
MODEL NUMBER
AC00280U2R1
AC00280U2R2
SERVICE
FUEL OIL
FUEL OIL
LOCATION
GENERATOR ROOM
GENERATOR ROOM
CAPACITY
280 GALLONS
280 GALLONS
WEIGHT (EMPTY)
625 LBS
625 LBS
NOTES
HVAC PIPING SPECIFICATIONS
NOTES
1 HOT AND COLD PIPES LARGER THAN 2 ": RIGID INSERTS. INSULATION CONTINUOUS THROUGH THE HANGER. SHEETMETAL SHIELD.
2 COLD PIPES 2" AND SMALLER: RIGID INSERTS. INSULATION CONTINUOUS THROUGH THE HANGER. SHEETMETAL SHIELD.
3 JACKETING: METAL JACKET (SEALED WEATHER TIGHT) WILL BE USED AT ALL EXTERIOR INSULATION EXPOSED TO WEATHER (I.E.ROOFTOP PIPING). PVC JACKET WITH RIGID RIGID CALCIUM SILICATE
INSULATION WILL BE USED ON ALL HORIZONTAL PIPING AT OR NEAR THE FLOOR SUBJECT TO POTENTIAL FOOT TRAFFIC. PVC JACKET WILL BE UTILIZED ON ALL EXPOSED INSULATION WITHIN
6 FEET OF THE FLOOR ELEVATION (I.E. MECHANICAL ROOMS AND GARAGE HOSE BIBBS). PVC IS RECOMMENDED INSTEAD OF METAL IN EXPOSED AREAS DUE TO ITS RESILIENCY -METAL JACKETS DENT.
FUEL OIL PUMP SCHEDULE
SPECIFICATION SECTION 15131-3
.AX FLUID TEMPERATURE
VISCOSITY
I FT. NPSH
NOTE: PUMPS ARE EXISTING IN BUILDING STORES.
REVIEWED FOR
CODE COMPLIANCE
APPROVE
City Of 'Tukwila
ILDIN DWI ION
MO72'O
GENERATOR R00
DESIGN DRAWINGS
instr
y
le Of Your Building
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1 -800- 669 -6223
PORTLAND:
12021 NE AIRPORT WAY
SUITE G
PORTLAND, OR 97220
503- 331 -0234
www.mckinstry.com
PROJECT:
KING COUNTY
DATA CENTER
AT SABEY CORP
TUK 5 BUILDING
SBC 5201
3355 S. 120th Place
Tukwila, WA 98168
REGISTRATION:
REVISIONS:
NO DATE DESCRIPTION
10/3/07 SCHEMATIC HVAC DESIGN FOR REVIEW
11/13/07 DESIGN DEVELOPMENT
12/5/07 PERMIT SET
McKINSTRY DMSION:
ENGINEERING
DESIGNED BY:
DRAWN BY:
CHECKED BY:
JOB NUMBER:
DATE:
SCALE:
SHEET TITLE:
SHEET NUMBER:
I EXPIRES: 05-11-09
T. DIAZ
B. HUCKINS
M. WEBB
35776
9 -28 -07
SEE DRAWING
SCHEDULES - PLUMBING
RECE ED
DEC 2 6 2007
PERMIT CENTER
P7.0