doc: Mech
City of Tukwila
Department of Community Development / 6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
2523049071
1162 INDUSTRY DR TUKW
MOBILE SYSTEMS
1162 INDUSTRY DR, TUKWILA, WA
MECHANICAL PERMIT
CALWEST INDUSTRIAL PROP
C/O DELOITTE & TOUCHE LLP, 2235 FARADAY AVE #0
PETER CRELLEY
P.O. BOX 33370, SEATTLE, WA
PRO STAFF MECHANICAL INC
Address: PO BOX 33370, SEATTLE WA
Contractor License No: PROSTMI072NG
DESCRIPTION OF WORK:
LIKE FOR LIKE AC REPLACEMENT. REPLACING ONE EXISTING 3 -TON AC UNIT WITH NEW
3 -TON AC UNIT
Value of Construction: $4,000.00
Type of Fire Protection: N/A
Fees Collected:
Uniform Mechnical Code Edition:
MO2 -138
Permit Number:
Issue Date:
Permit Expires On: 10/11/1810
Phone:
Phone: 206 361 -0071
Phone: 206 - 361 -0071
Expiration Date: 06/30/2004
Date: 7 "5 Z
MO2 -138
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and
ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws
regulating constr ction or the performa - of work. I am authorized to sign and obtain this mechanical permit.
Ze)t--7
Date: 7-5 = - 0 Z
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is
suspended or abandoned for a period of 180 days from the last inspection.
$46.50
1997
Printed: 07 -05 -2002
ct 2
V Q
N
�W
W
J
52 a
z
Lti
M p
U
0 H
WW
U
U. O
.. z
W
U N '
p.- H
O
z
1
ACTIVITY NUMBER: MO2 -138
PROJECT NAME: MOBILE SYSTEMS
SITE ADDRESS: 1162 INDUSTRY DRIVE
X Original Plan Submittal
Response to Correction Letter #
DATE: 6 -27 -02
Response to Incomplete Letter #
Revision # After Permit Is Issued
DEPARTMENTS: u 12 '�L
Building'Di"vision
Public Works ❑
PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete [I]�
APPROVALS OR CORRECTIONS:
Documents/routing slip.doc
2-28-02
612 .I'2.'
Fire Prevention [, O' Planning Division
Structural ❑ Permit Coordinator
Incomplete
REVIEWER'S INITIALS:
PERMIT COORD COPY
DUE DATE: 7-02 -02
DUE DATE: 7-30 -02
Not Applicable E1
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROUTING:
Please Route [J Structural Review Required ❑ No further Review Required ❑
REVIEWER'S INITIALS: DATE:
Approved ❑ Approved with Conditions Not Approved (attach comments) ❑
Notation:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire 0 Ping ❑ PW ❑ Staff Initials:
z
Fz
„ w
QQ 2
J U
0 0 0
to
H
N LL
W
2
LL
W
Z1.-
F- 0
Z I—
w
W
Ucl
U?
0 I—
WW
H
9 - - O
w Z
O
Z
DEPARTMENTS:
Building Division
Public Works
Complete
APPROVALS OR CORRECTIONS:
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: MO2 -138 DATE: 6 -27 -02
PROJECT NAME: MOBILE SYSTEMS
SITE ADDRESS: 1162 INDUSTRY DRIVE
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter.# Revision # After Permit Is Issued
Fire Prevention
Structural
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Incomplete
Planning Division
❑ Permit Coordinator ❑
DUE DATE: 7 -02 -02
Not Applicable ❑
Comments:
Permit. Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROUTING:
Please Route ❑ Structural Revie equired ❑ No further Review Required
REVIEWER'S INITIALS: DATE:
DUE DATE: 7 -30-02
Approved ❑ Approved with Conditions tge Not Approved (attach comments) ❑
Notation: / t
REVIEWER'S INITIALS:
DATE:
Permit, Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents/routing slip.doc
2.28.02
n..... taet ..r«»mr.:rx- rne�....e•a::.xn-. orcjfrwasm ....
PERMIT NO.: M D 2 C3€j
MECHANICAL PERMIT APPLICATIONS
INSPECTIONS
❑ 2 Pre - construction
❑ 50 WSEC Residential
❑ 60 WA Ventilation/Indoor AQC
❑ 610 Chimney Installation/All Types
❑ 700 Framing
❑ 1080 Woodstove
1090 Smoke Detector Shut Off
1100 Rough -in Mechanical
❑ 1101 Mechanical Equipment/Controls
❑ 1102 Mechanical Pip /Duct Insul
❑ 1105 Underground Mech Rough -in
❑ 1115 Motor Inspection
❑ 1400 Fire - Final
4 1800 Mechanical - Final
❑ 4015 Special -Smoke Control System
CONDITIONS
' 10001 No changes to plans unless approved by Bldg
Div
❑ 10002 Plumbing permits shall be obtained through King
Co
10003 Electrical permits obtained through L & I
10005 All permits, insp records & approved plans
available
r 10014 Readily accessible access to roof mounted
equipment
❑ 10016 Exposed insulation backing material
jr 10019 All construction to be done in conformance
w /approved plans
g 10027 Validity of Permit
10036 Manufacturers installation instructions required
on site
❑ 10041 Ventilation is required for all new rooms &
spaces
❑ 10042 Fuel burning appliances
❑ 10043 Appliances, which generate....
❑ 10044 Water heater shall be anchored....
Additional Conditions:
TENANT NAME:
FEES
Basic Fee (Y/N)
Supplemental Fee (Y/N)
Plan Check Fee (Y/N)
Furnace/Burner
to 100,000 BTU (qty)
Over 100,000 BTU (qty)
Floor Furnace (qty)
Suspended/Wall/Floor - mounted Heater (qty)
Appliance Vent (qty)
Heating/Refrig/Cooling Unit/System (qty)
Boiler /Compressor
to 3 HP /100,000 BTU (qty)
to 15 HP /500,000 BTU (qty)
to 30 HP /1,000,000 BTU (qty)
to 50 HP /1,750,000 BTU (qty)
over 50 HP /1,750,000 BTU (qty)
Air Handling Unit
to 10,000 cfm (qty)
over 10,000 cfm (qty)
Evaporative Cooler (qty)
Ventilation Fan (qty)
Ventilation System (qty)
Hood (qty)
Incinerator — Domestic (qty)
Incinerator — Comm /Ind (qty)
Other Mechanical Equipment (qty)
Other Mechanical Fee (enter $$)
Add' I Fees — Work w/o Permit (Y/N)
Insp Outside Normal Hours (hrs)
Reinspections (hrs)
Miscellaneous Inspections (hrs)
Add'l Plan Review (hrs)
Plan Reviewer:
Date:
t
Permit Tech: Date:
e
ACTIVITY NUMBER: MO2 -138 DATE: 6 -27 -02
PROJECT NAME: MOBILE SYSTEMS
SITE ADDRESS: 1162 INDUSTRY DRIVE
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter # Revision # After Permit Is Issued
DEPARTMENTS:
Building Division
Public Works
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete ❑
APPROVALS OR CORRECTIONS:
Documents/routing slip.doc
2 -28 -02
PLAN REVIEW /ROUTING SLIP
Fire Prevention
Structural
Incomplete
REVIEWER'S INITIALS:
TUES /THURS ROUTING:
Please Route ❑ Structural Review Required ❑ No further Review Required
REVIEWER'S INITIALS: .._,c572_
Planning Division
❑ Permit Coordinator ❑
DUE DATE: 7 -02 -02
Not Applicable ❑
Comments:
Permit Center Use Only
INCOMPLETE. LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
DATE:
V-/6 2--
DUE DATE: 7 -30 -02
Approved ❑ Approved with Conditions ❑ Not Approved (attach comments) ❑
Notation:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
z
W
0 0
co o
11.1_
N LL
WO
CO D
W
Z �
W
U �
O
0 I—
W W
tii
O F
O
Project Name /Tenant:
IZED;iAGENT1; lk:.: ,_; ; .: _`'i ..,
Si r
s
Value of Mechanical
Site Address
N• , t VI R I ..t._
Date: 6 , 4 7 2.
%
Fax #: ('�v L) SW — 09'24
City •tate/Zip:
k LA. .$
Tax Parcel Number:
2- 3 • ' O
Propert Owner:
r ra P
PA eTHees 42N L.
City /state2ip: � / / X133
City State/Zip:
td MCA - .
Phone: (LO(. )
Fax #: ( 2.0 L ).
515* 0 7 K
5-75_ 0 7 2 )
Street Address:
-
• N it 3L ✓D.5
Contractor:
F DATA
Mat0 4A+IlCAL. 2N-4--
Phone: (2.o(.)
34,/ -- Po 71
Street Address:
P. U. Box
3337 0
A t ?LE
City State/Zip:
c/,3
Fax #: ( 2.o(.)
36:4— 0424
Contact Person:
F -ir_ z
C4z i.( •J,/
Phone: (242 G. )
3 L I — 0
Street Address:
R ► 3337 '
4
City State /Zip:
geI
Fax #: ( y0L)
36o _ 0424
4BrJIL
IZED;iAGENT1; lk:.: ,_; ; .: _`'i ..,
Si r
s
Phone: (Z u g) 3 � � 7 l
Date: 6 , 4 7 2.
%
Fax #: ('�v L) SW — 09'24
P ' name: �sssE
:dress: 0_ Sox
333 71
City /state2ip: � / / X133
CITY OF : - V KWI LA
Permit Center
6300 Southcenter Boulevard, Suite 100
Tukwila, WA 98188
(206) 431 -3670
Project Number:
:Permit Number:.: •
Mechanical Permit Application
Application and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or facsimile. N
t : :.34 G AN 61 APPROVALUREQUESTED: (TO BE FILLED OUT'BYAPPLI
Description of work to be done (please be specific):
LI Kr- - F-ot2- Lji -C /�C. 12f;y�acEVv1A/'T; P�,AC 0'$i
1 xL i i'N-ex 3 -"TOM A-4, Ut4 rr w iTh N E w - ibN Ac- tit rr
Current copy of Washington State Department of Labor and Industries Valid Contractor's License. If not available at the time of
application, a copy of this license will be required before the permit is issued OR submit Form H-4, "Affidavit in Lieu of Contractor
Registration ".
Building Owner /Authorized Agent: If the applicant is other than the owner, registered architect/engineer, or contractor licensed by the ,
State of Washington, a notarized letter from the property owner authorizing the agent to submit this permit application and obtain the
permit will be required as part of this submittal.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
Expiration of Plan Review - Applications for which no permit is issued within 180 days following the date of application shall expire by
limitation. The building official may extend the time for action by the applicant for a period not exceeding 180 days upon written
request by the applicant as defined in Section 114.4 of the Uniform Mechanical Code (current edition). No application shall be
extended more than once.
Date application accepted:
' c7 7- 0.0Z
Date application expires:
/a -a 7-002.
Application taken by: (initials)
SAS
11/2/99
mech penel.duc
..rw.wnrv'.
✓
Submittal Requirements
Floor plan and system layout
Roof plan required to identify Individual equipment and the location of each installation (Uniform
Mechanical Code 504 (e))
Details and elevations (for roof mounted equipment) and proposed screening
Heat Loss Calculations or Washington State Energy Code Form #H -7
H.V.A.C. over 2,000 CFM (approximately 5 ton and larger) must be provided with smoke detection shut-
off and will be rooted to the Fire Prevention division for additional comments (Uniform Mechanical
Code 1009).
Specifications must be provided to show that replacement equipment complies with the efficiency ratings
and other applicable requirements of the Washington State Nonresidential Energy Code.
Structural engineer's analysis is required for new and the replacement of existing roof equipment
weighing 400 pounds and greater (Uniform Building Code 1632.1). Structural documentation shall be
stamped by a Washington State licensed Structural Engineer.
Mechanical Permits
COMMERCIAL: Two complete sets of drawings and attachments required with application submittal
11/2/99
ndnpmi.doc
NOTE: Water heaters and vents are included in the Uniform Mechanical Code — please include any water
heaters or vents being installed or replaced.
RESIDENTIAL: Two complete sets of attachments required with application submittal
Submittal Requirements
New Single Family Residence
Heat loss calculations or Form H -6.
Equipment specifications.
Change - out or replacement of existing mechanical equipment
I Narrative of work to be done, including modification to duct work.
Installation of Gas Fireplace
Narrative with specification of equipment and chimney type.
If using existing chimney, provide a letter by a certified chimney sweep stating that the chimney is in safe
condition.
NOTE: Water heaters and vents are included in the Uniform Mechanical Code — please include any water .
heaters or vents being installed or replaced.
re w
QQ
JU
00
0
N
w0
2 < .
I-0
z I-
w uj
U
O N
0 t—
w
I U
O
W Z
I;!
Print Name:
doc: Conditions
City of Tukwila
Department of Community Development / 6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
Parcel No.: 2523049071
Address: 1162 INDUSTRY DR TUKW
Suite No:
Tenant: MOBILE SYSTEMS
1: ** *BUILDING DEPARTMENT * **
2: No changes will be made to the plans unless approved by the Engineer and the Tukwila Building Division.
3: Electrical permits shall be obtained through the Washington State Division of Labor and Industries and all electrical work will be
inspected by that agency
(206- 835 - 1111).
4: All permits, inspection records, and approved plans shall be available at the job site prior to the start of any construction. These
documents are to be
maintained and available until final inspection approval is granted.
5: Readily accessible access to roof mounted equipment is required.
6: All construction to be done in conformance with approved plans and requirements of the Uniform Building Code (1997 Edition) as
amended, Uniform Mechanical Code
(1997 Edition), and Washington State Energy Code (1997 Edition).
7: Validity of Permit. The issuance of a permit or approval of plans, specifications, and computations shall not be construed to be a
permit for, or an approval
of, any violation of any of the provisions of the building code or of any other ordinance of the jurisdiction. No permit presuming to
give authority to violate
or cancel the provisions of this code shall be valid.
8: Manufacturers installation instructions required on site for the building inspectors review.
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws
regulating construction or the performan of work.
Signature: : /f6.110
T 1 ,5
PERMIT CONDITIONS
MO2 -138
Permit Number: MO2 -138
Status: ISSUED
Applied Date: 06/27/2002
Issue Date:
Date: /' �`� 2-
Printed: 07 -05 -2002
Payee: PRO STAFF
TRANSACTION LIST:
doc: Receipt
City of Tukwila
6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
Parcel No.: 2523049071 Permit Number: MO2 -138
Address: 1162 INDUSTRY DR TUKW Status: APPROVED
Suite No: Applied Date: 06/27/2002
Applicant: MOBILE SYSTEMS Issue Date:
Receipt No.: R020000924 Payment Amount: 46.50
Initials: KAS Payment Date: 07/05/2002 10:29 AM
User ID: 1684 Balance: $0.00
Amount
Payment Check 6922
ACCOUNT ITEM LIST:
Current Pmts
MECHANICAL - NONRES
PLAN CHECK - NONRES
Type
RECEIPT
Method Description
46.50
Description Account Code
000/322.100 37.20
000/345.830 9.30
Total: 46.50
Printed: 07 -05 -2002
INSPECTION REC
*Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd #100 Tukwila, WA 98188
pproved per applicable codes.
Moll I 3 g
(206)431-3670
S4644
Dr
pecia1 nstructions:-
. .
Typepf-Inspectio
Date C7I:
C i 7-
DaterAla Z7
P.m.
ke v1/1
Phone No:
_ 5902
Corrections required prior to approval.
COMMENTS:
- • r
I .
--;
•
$47.00 REINSPECTION F: REQUIRED. Prior to inspection, fee must be
'paid at t 300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:.
'Date:
, s'• • • •t`
• Project:.
eligitE ,.5Y17
Type of Inspection:
FR — / - 7/1/4(
gistress:
-1 Wwy,(c Y .4?)
ate calle /
(/72
Date w : /
6/0 t:g
-
a.m.
Special instructions:
/ -,-:::,
• ,
, .
Requ s r:
one:
/
— 607/
INSPECTION RECORD
J Retain a copy with permit
INSPECTION NO,
CITY OF'TiUkWILA BUILDING DIVISION
6300 Southcenter Blvd, #100, Tukwila, WA . 98188
PERMIT NO.
(206)431-3670
roved per applicable codes.
'Corrections required prior to approval.
ENTS:
•
A
ae L./14d IA
$4 • REINSPECT E REQUIRED. Prior to inspection, fee must be paid
at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No:
Date:
4t giVitiklitaSAMaUWai Oen.''.4:t.;.';;,14.,:;Vi...A4A:,..:-IlatMp.,.4,•,,igiv,4
File: M 02 -0138
35mm Drawing
#1
W
-JU
00
N0
�W
N W.
W 0:
2
gQ
3.
0:
W
Z,
O'
W
3 ° co
0—
0H
WW
u. 0
wZ
TRANE®
IP
Packaged Gas/Electric
Rooftop Units
Precedent
3- 10Tons — 60 Hz
October 2001
FILE_ COPY __.. .
(i c7 ►3 ILA 5Y51
11 lIJDUs-rev D vs
3LDG,a 42-
MO2- /38
RT- PRC006 -EN
RECEIVED
CITY OF TUKWILA
JUN 2 7 2002
PERMIT CENTER
�e >r 4•*ri:a. , ..;.....ra:r.: err...{:,; A � -•r�
z
w
J U
0
CO
W
J H
U) IL,
w
LLQ
_°
�
z �
Zo
w
w
U�
0-
ci
WW
u.
z
W
O ~'
z
r
(
411) .
Table GD-1 — General Data
Cooling Performance'
Gross Cooling Capacity
SEER'
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
System Power (KW)
Heating Performance'
Heating Models
Heating Input (Btu)
Heating Output (Btu)
AFUE %"
Steady State Efficiency ( %)
No. Burners
No. Stages
, Gas Connection Pipe Size (In.)
Compressor
No/Type
Outdoor Sound Rating (dB)"
12
Th
Low Med um Hig i Low Mediu High
60,000 80, 00 120,000 60,000 80,0' r 120,000
47,000 63, 00 95,0 )0 48,000 , • .00 96,000
80 8 BC 81 81 81
80 8 BC 81 81 81
2 3 2 3
1 1 1 1
1/2 1/2 1/I 1/2 1/2 1/2
1 /Climatuff® Hermetic
84
Belt Drive Indoor Fan -Type — FC Ce rifugal
No. Used/Diameter (in.) — 1/11 11
DriveType/No. Speeds — BelWariabl: Sheave
No. Motors — 1
Motor HP (Standard/Oversized) — 1.00/
Motor RPM ( Standard/Oversized) — 1,75
Motor Frame Size (Standard/Oversized) — 56/
(3 - 4Tons)
General Data Standard Efficiency
3 -Ton Convertible Units
Outdoor Coil -Type Lanced : nced ' nced Lan ed
Tube Size (in.) OD 0.3125 '.3125 • 3125 0.3 25
Face Area (sq ft) 7.19 7.19 3.172 9.
Rows/FPI 2/17 2/17 17 11
indoor Coil -Type Lanced Lanced Laced Lan :d
Tube Size (In.) 0.3125
0.3125 0, 25 .31 5
Face Area (sq ft) 5.67 5.67 6..: 6.1
Rows/FPI 2/16 2/16 3/ 6 3/1
Refrigerant Control Short Orifice Sho Orifice Short t rifice Short t rifice
Drain Connection NoiSize (in.) 1 /z/. NPT 1/ PT 1/34 PT 1/ PT
Direct Drive Indoor Fan -Type FC Centrifugal FC .ntrifugai FC Cent
No. Used/Diameter (in.) 1/10 x 10 1 0 x 10 1/11
DriveType/No. Speeds Direct/2 lirect/2 Dire
No. Motors 1 1 1
Motor HP (Standard/Oversized) 0.33/0.50 0.33/0.50 0.60
Motor RPM (Standard/0versized) 950 /1,100' 30/1,100' 1,000/1
Motor Frame Size ( Standard/0versized) 48/48 •8/48 48/
YSCO36A1 YS 36A3, A4, AW YS( 48A1 YSC048A3, • 4, AW
37,400 37,400 0,300 49,20
10.5 10.7 10.0 10.0
1,200/1,200 1,200/1,200 600/1,600 1,600/1,:00
36,000 36,000 48,000 47,00
3.91 9 5.28 5.40
1 /Climat ff Hermetic
Lo Medium High Low Me ium High
60,0 0 80,000 120,000 60,000 80 +00 120,000
47,0 63,000 95,000 48,000 64 r 00 96,000
80 80 80 81 :1 81
80 80 80 81 1 81
2 2 3 2 3
1 1 1 1 1
1/2 1/2 1/2 1/2 1/2
1/CI' ' atuff Scroll 1 /Climat ff Scroll
Outdoor Fan -Type Propeller Prope er Prop Iler Prop .liar
No. Used/Diameter fin.) 1/22 1/2 1 '' 1
DriveType/No. Speeds Direct/1 Dire • 1 Dire 1 Dire
CFM 2,550 2,5 0 2,8' r 3,6
No. Motors/HP 1/0.20 1/r 0 1/0. 3 1/0.
Motor RPM 1,075 1 +75 1,0 - 1,0
4-Ton Convertible Units
FC Cent ifugal
1/11 11
Dire
1
0.60/0. ' 0
1,000/1, r 0
48/48
Filters -Type Throwaway Thro away Throws ay Throwawa
Furnished? Yes s Yes Yes
(No.) Size Recommended (2) 20 x 25 x 1' (2) 20 25 x 1" (2) 20 x 2 x 1" (2) 20 x 25 1"
Refrigerant Charge (Lbs of R -22) 3.8 s,8 4.4
NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb. 67 F entering wet bulb. Gr ss capacity does not include the effect of Ian motor heat. ARI capacity is ne and
Includes the effect of fan motor heal. Units are suitable for operation to *20% of nominal cfm. Units are certified in accordance with the Unitary Air - Conditioner Equipment certification
program, which Is based on ARI Standard 210/240.
2. EER and /or SEER are rated at ARI conditions and In accordance with DOE test procedures.
3. Integrated Part Load Value is rated in accordance with ARI Standard 210/240 or 360. Units are rated at 60° F ambient, 80° F entering dry bulb, and 67° F entering wet bulb at ARI rated
cfm.
4. Heating Performance limit settings and rating data were established and approved under laboratory test conditions using American National Standards institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feel above sea level
5. AFUE is rated in accordance with DOE lest procedures.
6. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270. For additional information refer to Table P0-85.
7. Refrigerant charge Is an approximate value, For a more precise value, see unit nameplate and service instructions.
8. 20 x 25 filler on medium and low heat models. 20 x 30 filter on high heat models
9. Motor RPM shown is low speed. High speed RPM Is 1,060/1,145.
0
3
5
3.8
1
RT- PRC006 -EN
1
•
Unit
Tons Model No.
3 Y#CO36A3
Y #CO36A4
Y #CO36AW
4 Y#C048A3
Y#C048A4
Y #C048AW
5 Y #C060A3
Y #C060A4
Y #C060AW
66
1. HACK breaker per NEC.
Table ED-2 - Electrical Characteristics - Evaporator Fan Motors - Belt Drive l 1
Y #S072A3
6 Y #S072A4
Y #S072AW
YSC090A3
YSC090A4
71/2 YSC090AW
Y #C092A3
Y #C092A4
Y #C092AW
Y #C102A3
81/2 Y #C102A4
Y #C102AW
Y #C120A3
10 Y #C120A4
Y #C120AW
#Indicates both standard and high efficiency airflow.
Electrical
Data
Standard Evaporator Fan Motor
Oversized Evaporator Fan Motor
Amps Amps
No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA
1 208-230 3 1.0 5.0 32.2 - - - - - -
1 460 3 1.0 2.5 16.1 - - - -
1 575 3 1.0 1.7 13.2 - - -
1 208 -230 3 1.0 5.0 32.2 - - -
1 460 3 1.0 2.5 16.1 - - -
1 575 3 1.0 1.7 16.1 - - -
1 208 -230 3 1.0 5.0 32.2 - - -
1 460 3 1.0 2.5 16.1 - -
1 575 3 1.0 1.7 16.1 - - - - - -
1 208-230 3 1.00 5.00 32.20 1 208 -230 3 2.00 6.30 48.00
1 460 3 1.00 2.50 16.10 1 460 3 2.00 3.10 24.00
1 575 3 1.00 1.70 13.20 1 575 3 2.00 2.50 18.20
1 208-230 3 2.00 6.30 48.00 1 206 -230 3 3.00 9.40 83.00
1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
1 208 -230 3 2.00 6.30 48.00 1 208 -230 3 3.00 9.40 83.00
1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
1 208 -230 3 2.00 6.30 48.00 1 208 -230 3 3.00 9.40 83.00
1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
1 208 -230 3 3.00 9.40 83.00 1 208 -230 3 5.00 13.40 112.00
1 460 3 3.00 4.60 42.00 1 460 3 5.00 6.60 56.00
1 575 3 3.00 3.70 31.00 1 575 3 5.00 5.40 41.00
RTPRC006 -EN
a -
Standard Indoor Fan Motor
Ov- size Indoor Fan
otor
Opt nal Belt Drive Indoor Fan
Motor
Unit
Minimum
Maximum Fuse
Min mum
Maximu
Fuse
Mini
urn Maximu Fuse
Unit
Operating
Circuit
Size Or Maximum
C' cult
Size Or
ximum
Cir
uit Size or Ma imum
Tons
Model No.
Voltage Range
Am acity
Circui Breaker'
A . acity
Circuit
reaker'
Am
acity Circuit Br ker'
+YSCO36A1
187 -253
5.3
40
7.7
-
3
YSCO36A3
187-253
17.9
25
2'.3
.6
30
YSCO36A4
414-506
9.2
15
11
4
1
.6
15
YSCO36AW
517-633
7.7
15
8.
.3
15
YSC048A1
187-253
34.0
50
36.
-
YSC048A3
187 -253
23.9
35
26.
.3
35
4
YSC048A4
414.506
12.8
20
14.
21
1
.6
20
YSC048AW
517 -633
9.8
15
10..
it
1
.0
15
YSC060A1
187 -253
47.3
60
49
r
6(
-
YSC060A3
187 -253
31.5
50
33
•
5(
3
.3
45
5
YSC060A4
414-506
16.0
25
1:3
2t
1
.6
25
YSC060AW
517 -633
12.2
15
1
8
2(
1.8
15
YSC072A3
187 -253
32.2
50
3.5
51
-
6
YSC072A4
414 -506
17.6
25
1:.2
2E
-
-
YSC072AW
517 -633
12.8
20
1
.6
2(
-
-
YSC090A3
187 -253
42.7
60
4'
.8
6(
-
-
YSC090A4
414 -506
22.6
35
2
.1
3l
-
-
7'/:
YSC090AW
517 -633
17.6
25
1
.8
2l
-
-
YSC092A3
187 -253
38.9
50
4.0
51
-
-
YSC092A4
414 -506
20.5
25
2
.0
2E
-
-
YSC092AW
517 -633
15.5
20
1
.7
21
-
-
YSC102A3
187- 253
44.4
60
•
'.5
6(
-
-
8'/x
YSC102A4
414 -506
24.0
30
2
.5
3E
-
-
YSC102AW
517 -633
19.5
25
2.7
2E
-
-
YSC120A3
187 -253
50.9
60
,9
61
-
-
10
YSC120A4
414 -506
26.9
35
2:
9
3E
-
-
YSC120AW
517 -633
21.8
25
2
3(
-
-
NOTES:
•
Unit
Tons Model No.
3 Y#CO36A3
Y #CO36A4
Y #CO36AW
4 Y#C048A3
Y#C048A4
Y #C048AW
5 Y #C060A3
Y #C060A4
Y #C060AW
66
1. HACK breaker per NEC.
Table ED-2 - Electrical Characteristics - Evaporator Fan Motors - Belt Drive l 1
Y #S072A3
6 Y #S072A4
Y #S072AW
YSC090A3
YSC090A4
71/2 YSC090AW
Y #C092A3
Y #C092A4
Y #C092AW
Y #C102A3
81/2 Y #C102A4
Y #C102AW
Y #C120A3
10 Y #C120A4
Y #C120AW
#Indicates both standard and high efficiency airflow.
Electrical
Data
Standard Evaporator Fan Motor
Oversized Evaporator Fan Motor
Amps Amps
No. Volts Phase HP FLA LRA No. Volts Phase HP FLA LRA
1 208-230 3 1.0 5.0 32.2 - - - - - -
1 460 3 1.0 2.5 16.1 - - - -
1 575 3 1.0 1.7 13.2 - - -
1 208 -230 3 1.0 5.0 32.2 - - -
1 460 3 1.0 2.5 16.1 - - -
1 575 3 1.0 1.7 16.1 - - -
1 208 -230 3 1.0 5.0 32.2 - - -
1 460 3 1.0 2.5 16.1 - -
1 575 3 1.0 1.7 16.1 - - - - - -
1 208-230 3 1.00 5.00 32.20 1 208 -230 3 2.00 6.30 48.00
1 460 3 1.00 2.50 16.10 1 460 3 2.00 3.10 24.00
1 575 3 1.00 1.70 13.20 1 575 3 2.00 2.50 18.20
1 208-230 3 2.00 6.30 48.00 1 206 -230 3 3.00 9.40 83.00
1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
1 208 -230 3 2.00 6.30 48.00 1 208 -230 3 3.00 9.40 83.00
1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
1 208 -230 3 2.00 6.30 48.00 1 208 -230 3 3.00 9.40 83.00
1 460 3 2.00 3.10 24.00 1 460 3 3.00 4.60 42.00
1 575 3 2.00 2.50 18.20 1 575 3 3.00 3.70 31.00
1 208 -230 3 3.00 9.40 83.00 1 208 -230 3 5.00 13.40 112.00
1 460 3 3.00 4.60 42.00 1 460 3 5.00 6.60 56.00
1 575 3 3.00 3.70 31.00 1 575 3 5.00 5.40 41.00
RTPRC006 -EN
,. ,,.A i�.SJ�1:wwLl.il.�t:•+u ' Stx..' ? :/:..�Jt�%i{sL..w.....ww:::vjf' �. .. •,
.
All dimensions are in inches /millimeters.
3, 4, and 5 Ton Standard Efficiency — Low and Medium Heat
3 and 4 Ton High Efficiency — Low and Medium Heat
EVAPORATOR SECTION
ACCESS PANEL
ALTERNATE CONDENSATE DRAIN
CONNECTION 3/4.14 NPT DIA. HOLE
3, 4, and 5 Ton Standard Efficiency —High Heat
3 and 4Ton High Efficiency — . Heat
5Ton — High Efficiency — Low, M= . ' m, and High Heat
EVAPORATOR •ECTION
ACCE ANEL
ALTERNATE CONDENSATE DRAIN
CONNECTION 3/4.14 NPT DIA. HOLE
Dimensional
Data
4 1/4'
108 MM
23 9116'
599 MM
69 7/8 42 1/4'
1749 MM 1073 MM
1/2 NPT GAS CONNECTION
4 1/4'
108 MM
NPT GAS CONNECTION
5 5/8'
143 MM
95/8'
244 MM
CONTROL AND COMPRESSOR
ACCESS PANEL
5 5/8'
143 MM,.
9 5/8'
244 MM
CONTROL AND COMPRESSOR
ACCESS PANEL
(3 - 5Tons)
TOP PANEL
4 114'
108MM.
5 9/16'
141 MM
7 5/8'
194 MM
44 114'
1124 MM
TOP PANEL
58/1
141 MM
75/8'
194 MM
44 1/4'
1124 MM
MIMI
CONDENSER FAN
32 /4'
819 MM
UNIT POWER WIRE
1 302' (28MM) DIA HOLE
CONDENSER FAN
CONDENSER COIL
UNIT CONTROL WIRE
718' (22MM) DIA. HOLE
SERVICE GAUGE PORT ACCESS
1 3/8' (35MM) DIA. HOLE
36 14'
921 MM
CONDENSER COIL
UNIT CONTROL WIRE
7/8' (22MM) DIA. HOLE
SERVICE GAUGE PORT ACCESS
1 3/8' (35MM) DIA. HOLE
UNIT POWER WIRE
1 3132' (28MM) DIA HOLE
i
(
All dimensions are in inches.
3-5 Tons — DownflowAbllow Supply and Return;
Through the Base Utilities
L
3 -5Tons — HonfzontalAbflow Supply and
Return
3.5Tons — Unit Clearance and Roof Opening
Dimensional
Data
(� - 5Tons)
438MM
�
171/4'
22
M
e/ 5M
CLEARANCE 37' (940 MM)
CLEARANCE 48' (1219 MM)
314.14 NPT CONDENSATE DRAIN
\L ROOF OPENING
81MM
13 1/4'
337MM
23 /4'
581 MM
CLEARANCE
iipik HORIZONTAL FLOW - 18' (457 MM)
DOWNFLOW 38' (914 MM)
44 112'
(11]0 MM)
J/ CLEARANCE 36' (914 MM)
4 3/4'
121MM
RT- PRC006 -EN
1
Table W 1— Maximum UnitAnd Comer Weights (Lbs)And Center Of Gravity Dimensions (In.)
Tons Model No.
c
Unit Maximum Weights (Lbs)' Corner Weights (Lbs)1
YSCO36A
YHCO36A
4 YSC048A
YHC048A
5 YSC060A
YHC060A
6 YSC072A3 *H
YHC072A3 *H
YSC090A3 "H
7'h YSC092A3 "H
YHC092A3 "H
8V2 YSC102A3 *H
YHC102A3 "H
10 YSC120A3 "H
YHC120A3 *H
NOTE:
1. Corner weights are given for information only.
2. Weights are approximate.
Shipping
534
651
559
593
676
628
822
859
907
909
1010
986
1044
1074
1147
tY
Weights
CENTER OF
GRAVITY
WIDTH
Net
505
539
622
574
735
772
820
822
923
899
957
987
1060
D
CENTER OF GRAVITY
CENTER OF GRAVITY
a LENGTH - -+
TRANE'
Center of Gravity (In.)
A B C D Length Width
151 124 96 109 32 19
158 128 101 110 32 19
159 130 108 109 33 19
166 133 114 126 32 20
169 134 105 114 32 18
179 140 119 136 32 20
249 193 132 161 39 21
249 198 141 184 39 22
273 208 146 193 38 22
277 222 147 175 40 21
306 243 165 210 39 22
297 243 165 194 40 21
310 252 175 220 40 22
325 265 183 213 40 21
342 277 197 245 40 22
� W
C.)o
9 tU
W 0
CO 3
Z �
111 uj
O N ' .
toI-
W W`
W z
Ii!
LICENSE DETAIL INFORMATION
Current Filter: None
Registration# or License PROSTMI072NG
Name PRO STAFF MECHANICAL INC
Address PO BOX 33370
Address
City SEATTLE
State WA
Zip 98133
Phone Number 2063610071
Effective Date 8/7/1993
Expiration Date 6/30/2004
Registration Status ACTIVE
Type CONSTRUCTION CONTRACTOR
Entity CORPORATION
Specialty Code GENERAL
Other Specialties
UBI Number 601038859
STATE OF WASHINGTON
DEPARTMENT OF LABOR AND INDUSTRIES
Specialty Compliance Services Division
P. O. Box 44000 Olympia, WA 98504 -4000
'VIEW *VIEW CROSS REFERENCE FILE FOR THIS LICENSE* * *
'VIEW *VIEW PRINCIPAL OWNER(S) FOR THIS LICENSE* * *
'VIEW *VIEW CONTRACTOR BOND /SAVINGS INFORMATION * * *
* * *CHECK INQUIRY FOR SUMMONS AND COMPLAINTS* * *
* * * VIEW CONTRACTOR INSURANCE INFORMATION * * *
LICENSE DETAIL INFORMATION Form Page 1 of 1
r
THE RESULT OF YOUR INQUIRY FOR LICENSE NUMBER SELECTED IS:
RECEIVED
CITY OF TUKWILA
JUL - 5 2002
PERMIT CENTER
New inquiry by CITY, NAME, PRINCIPAL OWNER NAME, NUMBER, UBI NUMBER or
return to the L &I Construction Compliance Home Page
M0a-138
https : / /wws2.wa.gov /lni /bbip /TF2Form .asp ?License= PROSTMI072NG 07/05/2002
ANA Agw.
Z
~ W
re JU
00
J
H
WD
2
u_
I-W
Z =
I-
Z I-
W
W
U �
0—
OH
W W
F
u. O
.. Z
W
U =
0
Z
File: M 02 -0138
35mm Drawing
#1
I I I i I I L . I 1 1 1 I u � i liii i i i
O Inch 1/16' � 2' y
111 '3 4I
^rrr(vr
�IIIILIIIILII ILIIIIIIIII11111 ` IIIIIIIIIIIII y 111�
II �IIIIILII111111MiliiiiIIIIIIMilidiiii,h111111111111111111111111 IIILIIIiIIIIIIIIIIIIII�I IIlii
5
O
rn
11 1II. 11
1 11
1
r I,,
11 ill' Ill
0.1,1:1111
1 ,1 1111,11
G OFFICE
Stra • er Blvd.
A,\uiteG
Minkler Blvd.
1 l
Pacific Gulf Business Park
0
Ob
z U)
c r�m
•
m
x
m
Str er Blvd.
1 �
Phase Ill
Pacific Gulf Business Park
Tract 11
SCOPE OF WORK:
• "Like- for - Like" Change -out Replace one existing 3 -Ton
AC unit with new 3 -Ton AC unit.
Parcel Number: 2523049071
NEW TRANE "Like- For - Like" AC U
HVAC Replacement
"Mobile Systems"
1162 Industry Drive
Pacific Gulf Business Park
Building #42
Tukwila, WA 98188
t
A
IT SCHEDULE
NOTES:
1) HORIZONTAL DUCT DISCHARGE.
2) 7 -DAY PROGRAMMALBE THERMOSTATS WITH 5 DEGREE DEADBAND.
3) FACTORY INSTALLED ECONOMIZER.
4) INSULATE AND SEAL ALL NEW DUCTWORK PER CODE.
5) OUTSIDE AIR INTAKES TO BE 10'-0" FROM EXHAUST OUTLETS, GAS FLUES & PLUMBING VENTS.
6) EXISTING UNIT BEING REPLACED: TRANE #BYCO36G1LOBA, WEIGHT= 470 LBS.
902 N. 1271}1 ST.
P.O. BOX 93370
SEATTLE. WA 90133 ,
(206) 361-0071
FAT(: 301.0424
Www.pro.etaf nechantcal.com
12, C� S A &Y °C
SA
&Y
TT c '''..;i
'7 -9i us) g el - A il
0 -0 to , 0
z — z
C3 c - 0 11 T H
PTh 7P 0 7
\0
z
AC I
0
TAG
AC -2
TRANE MODEL #
Precedent
YSCO36A1 EMA006M
SIZE
(Tons)
3
CFM
1,200
MIN
OSA
200
ECONO
MIZER
Yes
GROSS
Cooling
(BTUH)
37,400
Cooling
SEER
10.5
Heating
Input
(BTUH)
60,000
Heating
Output
(BTUH)
47,000
AFUE =80%
NOISE
RATING
84 dB
WEIGHT
(Ibs)
480
ELEC
208 - 230/1/60
MCA =25.3
FUSE =40
COMMERCIAL CONTRACTORS
SYSTEM DESIGN &INSTALLATION
SHEET METAL FABRICATION
24 HOUR EMEAGENCYSERVICE
PREVENTIVE MAINTENANCE
LICENSE 4 PROSTMI072NG