Loading...
HomeMy WebLinkAboutPermit M06-184 - HIGHLINE MEDICAL CENTERHIGHLINE MEDICAL CENTER 12844 MILITARY RD S M06 -184 CITY OF TUKW lA DEPT 07 CC7.7.;U ..TY C:-", 6C, ' f. J; : n . " TUKWiiA, Parcel No.: 1623049001 Address: 12844 MILITARY RD S TUKW Suite No: Tenant: Name: HIGHLINE MEDICAL CENTER Address: 12844 MILITARY RD S, TUKW ILA WA Contact Person: Name: DIANNE MUNROE Address' 16251 SYLVESTER RD SW, BURIEN WA Value of Mechanical: 110,000.00 Furnace: <100K BTU >100K BTU Floor Furnace Suspended/Wall /Floor Mounted Heater Appliance Vent Repair or Addition to Heat/Refrig /Cooling System.... Air Handling Unit <10,000 CFM >10,000 CFM Evaporator Cooler Ventilation Fan connected to single duc Ventilation System Hood and Duct Incinerator: Domestic Commercial /Industrial doc: !MC-Permit MECHANICAL PERMIT Owner: Name: HCH SPECIALTY CENTER Address: ATTN ACCOUNTING DEPT, 12844 MILITARY RD S Contractor: Name: PSF MECHANICAL, INC. Address: 9322 14TH AVENUE SOUTH, SEATTLE, WA Contractor License No: PSFMEI *090NZ DESCRIPTION OF WORK: PROVIDE NEW AIR HANDLING UNIT TO SERVE (9) PATIENT ROOMS ON 2ND FLOOR. PROVIDE (12) AIR TERMINAL BOXES WITH HOT WATER HEATIN COILS FOR EACH ZONE. CONNECT TO EXISTING HEATING AND CHILLED WATER SYSTEMS. PROVIDE EXTENSION OF EXISTIN DDC CONROL SYSTEM. NOTE: AIR TERMINAL BOXES REPLACE (14) EXISTING FAN COIL UNITS SERVED BY AND EXISTING AIR HANDLING UNIT. EXITING GAS BOILERS ARE HEATING SOURCE. Type of Fire Protection: International Mechanical Code Edition: 2003 EQUIPMENT TYPE AND QUANTITY 0 0 0 0 0 0 1 0 0 0 0 0 0 0 Permit Number: Issue Date: Permit Expires On: ''ERMIT CENT Phone: Phone: 206 431 -5343 Phone: 206 764 -9663 Expiration Date:10 /03/2007 M06 -184 09/25/2006 03/24/2007 Fees Collected: $1,087.88 Boiler Compressor: 0 -3 HP /100,000 BTU 0 3 -15 HP /500,000 BTU 0 15 -30 HP /1,000,000 BTU 30 -50 HP/1,750,000 BTU 50+ HP/1,750,000 BTU 0 Fire Damper 46 Diffuser 42 Thermostat 12 Wood /Gas Stove 0 Water Heater 0 Emergency Generator 0 Other Mechanical Equipment M06 -184 Printed: 09 -25 -2006 CITY OF TUKWI A DEPT. OF CO`.C'.:U ?: iY DCV:1C'I1.1-NT`„ ' 6300 CLUTI-i.::.N'iLRCLVO. TUKWILA, WA 93188 doc: IMC- Permit "continued on next page ** M06 -184 QERMIT CENTE T Printed: 09 -25 -2006 CITY r^ r r ■•••■ DEPT OF 6303 ;I, .; ✓D. TUFO, ILA, WA 9d188 ordinances governing this work will Print Name: doc: IMC- Permit ■' PERMIT CENTEr' Permit Number: M06 -184 Issue Date: 09/25/2006 Permit Expires On: 03/24/2007 Permit Center Authorized Signature Att—ik Q Date: al I ? /ao I hereby certify that I have read and ex mired t is permit and know the same to be true and correct. All provisions of law and with, whether specified herein or not. The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this mechanical permit. Signature: Nl !� Date: glo VVVV r M f <Orl, ark-f This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended or abandoned for a period of 180 days from the last inspection. M06 -184 Printed: 09 -25 -2006 CITY OF TUKWIL.A DEPT. OF CO^;% :UNITY OEV,'LOPMiNT 6300 lOTN! !T r'!VD TUKbiitA, V:% • 1: ***BUILDING DEPARTMENT CONDITIONS*** PERMIT CENTEr. PERMIT CONDITIONS Parcel No.: 1623049001 Permit Number: M06 -184 Address: 12844 MILITARY RD S TUKW Status: ISSUED Suite No: Applied Date: 08/18/2006 Tenant: HIGHLINE MEDICAL CENTER Issue Date: 09/25/2006 2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the Building Official. 3: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to start of any construction. These documents shall be maintained and made available until final inspection approval is granted. 4: Readily accessible access to roof mounted equipment is required. 5: All construction shall be done in conformance with the approved plans and the requirements of the International Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code. 6: Manufacturers installation instructions shall be available on the job site at the time of inspection. 7: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the Cityof Tukwila Permit Center. 8: All electrical work shall be inspected and approved under a separate permit issued by the Washington State Department of Labor and Industries (206/248- 6630). 9: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the Building Official from requiring the correction of errors in the construction documents and other data. 10: ***FIRE DEPARTMENT CONDITIONS * ** 11: H.V.A.C. units rated at greater than 2,000 cfm require auto-shutdown devices These devices shall be separately zoned in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051) 12: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the air - moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the manufacturer's Installation Instructions. (IMC 606.1, 606.2.1) 13: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051) 14: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051) 15: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051) doc: Conditions M06 -184 Printed: 09-25 -2006 CITY OF TUKWI A DEPT OF CO? ,? ;UNITY DEV LO^f!`I'IT 6300 SCJUTh i gR1B TUKWILA NIA PERMIT CENTER' 16: An electrical permit from the Washington State Department of Labor and Industries is required for this project. 17: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC 104.2) 18: Any overlooked hazardous condition and /or violation of the adopted Fire or Building Codes does not imply approval of such condition or violation. 19: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at (206)575 -4407. doc: Conditions **continued on next page** M06 -184 Printed: 09-25-2006 CITY OF TUIMIlA DEPT. OF CC ?2 R f ^ • • 1T >ad 63c0 TUKWILA, WA 98188 I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing this work will be complied with, whether specified herein or not. The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating construction or the performance of work. Signature: Print Name: doc: Conditions kjia Nt fr vwkf `PERMIT CENTER Date: T( /o M06 -184 Printed: 09 -25 -2006 E -Mail Address. CITY OF TUKWILiL Community DevelopmelleDepartment Public Works Department Permit Center 6300 Southcenter Blvd., Suite 100 Tukwila, WA 98188 http: /Avww.ci.tukwila. we.us Applications and plans must be complete in order to be accepted for plan review. Applications will not be accepted through the mail or by fax. "Please Print** Site Address: raY44 VIILATM Tenant Name: �Ifa.4eL +b ITLSl Property Owners Name - 4A1441 A 1 4F. 1111 -1 1r ttat Mailing Address I24 Tll I.tTAar f F-0 C, Name: pit ltlprr - Mailing Address: 1 ln1Ca1 C ") - 0 AIPSTU _. g0 S.%) •%. -tat t aq.I Company Name ALT Cao- 15-112- t1CCTiCt4 Contact Person:Dhal S4-4442-11.1.61 E - Mail Address: Thal r% . ex i t.. '. en-, Contractor Registration Number: 4I:17. ml tl'col?u11 Cxxr7'ECT¢ : RTjC 1 • t ,All piansmust -be wet namp Mailing Address 4€S ST. ri . Contact Person: t-1 Y'1 Mit E -Mail Address: - th•-IC ( 1 i-IC ,. Cor Q:Upplicetiomforme- Applications On IineV -2006 - Permit Appliationdac Revised: 42006 bh King Co Assessor's Tax No.: I tot- Est - CIC I Suite Number: Floor: Z New Tenant: ❑ Yes of ..No / ern rail LA. City tk State 511,9n Zip Day Telephone: id ,, - 424. S 34b 1 17 1bTl (NIA ce131I.11 n City State Zip Fax Number: 2C(o • 2-4(..0 < e Mailing Address I S L A t t e ¶ - lt 'l(.IK TA astir. City lac) 1 tan( 1k16s °IBS State Zip Day Telephone: 42S .401. 11 Fax Number: 425 - 4(61 - I %LYL Expiration Date: C l /30 /CIp Company Name: FLcRZl1lie5—T moat" tz..a C-01 - t ,644 Mailing Address Z ZOI (aiM Ciirra Sew--n F. + 9` -12 ( City State Zip Contact Person: aJ151✓ ` Day Telephone: totes. 44%. 41SZZ E -Mail Address: Fax Number: #+. 441 , 1 GTNEER QE RECORD -,Mi plans must be jvet stamped Engineer of Company Name: 6-1/A rx. C. + St i rn4 42 .117.4. crLIMAI . airi1 k tC 7-C---, -, 5 c t itet% b11t C IF I C l City State ZIP Day Telephone: '1 425. 3(4Pt .. IOI 1 4 Fax Number: 42-s. 2 . \ IS1 Page 1 of 6 Valuation of Project (contractor's bid price): $ ,r c oo Scope of Work (please provide detailed information): Q:IAppacatio,a\Fonnr- Applications On Lina3- 2006 - Permit Application. dx Revised: 9-2006 be Existing Building Valuation: $ -' — 1\ • alb — _. . Sr- �a- _It • r alea • _ II • - — ►•tar- ••] •'L3 ate ta I► �Jlar Will there be new rack storage? ❑ .. Yes (If yes, a separate permit and plan submittal will be required) - II Raclin Isite`13e ico 1 —Z PLANNING DIVISION: Single- family building footprint (area of the foundation of all structures, phis any decks over 18 inches and overhangs greater than 18 inches) *For an Accessory dwelling, provide the following: Lot Area (sq ft): Floor area of principal dwelling: Floor area for accessory dwelling: *Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence. Number of Parking Stalls Provided: Standard: Compact: Handicap: Will there be a change in use? ❑....Yes ❑..No If `yes ", explain: FIRE PROTECTION/HAZARDOUS MATERIALS: d . Sprinklers ❑..Automatic Fire Alarm ❑..None ❑..Other (specify) Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑.. Yes 0.. No If"yes", attach list of materials and storage locations on a separate 8 -1/2 x 11 paper indicating quantities and Material Safety Data Sheets. SEPTIC SYSTEM: ❑ On -site Septic System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health Department. Page 2 of 6 • Scope of Work (please provide detailed information): Water District ❑...Tukwila ❑...Water District #125 ❑ ...Water Availability Provided $ewer District ❑ ...Tukwila ❑ ...Sewer Use Certificate Please refer to Public Works Bulletin #1 for fees and estimate sheet. ❑ ...Total Cut cubic yards ❑ ...Total Fill cubic yards ❑... ValVue 0... Sewer Availability Provided Submitted with Application (mark boxes which apply): ❑ ...Civil Plans (Maximum Paper Size — 22" x 34 ") ❑ ...Technical Information Report (Storm Drainage) ❑ ...Bond ❑ .. Insurance ❑ .. Easement(s) DI oposed Activities (mark boxes that apply): ...Right -of -way Use - Nonprofit for less than 72 hours ❑ ...Rightof -way Use - No Disturbance ❑ ...Const ruction /Excavation/Fill - Right-of-way Non Right-of-way ❑...Sanitary Side Sewer ❑...Cap or Remove Utilities ❑...Frontage Improvements ❑ ...Traffic Control ❑ ...Backflow Prevention - Fire Protection Irrigation Domestic Water ❑...Permanent Water Meter Size.. ❑ ...Temporary Water Meter Size . ❑ ...Water Only Meter Size ❑ ...Sewer Main Extension Public _ Private ❑...Water Main Extension Public _ Private QMppNndoMrmme- Applications On Lin&3 -2006 - Permit Application.dac Revised: 42006 bti ❑ .. Abandon Septic Tank ❑ .. Curb Cut ❑ .. Pavement Cut ❑ .. Looped Fire Line Call before you Dig: 1 800 - 424 - 5555 ❑ .. Highline ❑ .. Renton ❑.. Seattle ❑ .. Approved Septic Plans Provided ❑ .. Geotechnical Report ❑ .. Maintenance Agreement(s) ❑ .. Right-of-way Use - Profit for less than 72 hours ❑ .. Right-of-way Use — Potential Disturbance ❑ .. Work in Flood Zone ❑ .. Storm Drainage ❑ .. Renton ❑ .. Grease Interceptor ❑ .. Channelization ❑ .. Trench Excavation ❑ .. Utility Undergrounding ❑ ...Deduct Water Meter Size ❑ ...Traffic Impact Analysis ❑ ... Hold Harmless — (SAO) ❑ ...Hold Harmless— (ROW) FINANCE INFORMATION Fire Line Size at Property Line ❑...Water Number of Public Fire Hydrant(s) ❑ ...Sewer ❑ ...Sewage Treatment Monthly Service Billing tn- Name: Day Telephone: Mailing Address: Cory State Zip Water Meter Refund/Billing: Name: Day Telephone: Mailing Address: City State Zip Page 3 of 6 .. 2 2. :. 'Unit Type: _ . :_ > : - :;_> : ., .. .1?4Y'` safiiiEType .. ... , ..: ,Qty ::: tiiit ... wtTypei ... Qty:: Botlec /Compresso'r-. 0-3 HP /100,000 BTU >Qti� :: Furnace<100K. BTU Air Handling Unit >10,000 CFM Fire Damper Fumace>100KBTU Evaporator Cooler Diffuser 3 -15 HP /500,000 BTU Floor Furnace Ventilation Fan Connected to Single Duct Thermostat 15 -30 HP /1,000,000 BTU _ Suspended/Wall/Floor Mounted Heater Ventilation System Wood/Gas Stove 30-50 HP /1,750,000 BTU Appliance Vent Hood and Duct Water Heater 50+ HP /1,750,000 BTU Repair or Addition to Heat/Re1 ig/Cooling System Incinerator - Domestic Emergency Generator Air Handling Unit <10,000CFM r Incinerator— Comm /Ind Other Mechanical Equipment ht FR TES-r' tt -- L 2 $O sett { MECHANICAL CONTRACTOR INFORMATION Company Name. Ps P N E-Ctiea. ces. L. Mailing Address: 22- 14I'rr}4- Avis S Contact Person: r Ile-e. Cb,.totl�W E -Mail Address: t1pOt.4C i{t~INe P'1&4+ . f._or1 Contractor Registration Number: r 1 f * CP10 N ih1C Indicate type of mechanical work being installed and the quantity below: Q: AppGcithon none,- Appliceaom Oa Liee3-2096. remit Atpam!ionme aevim3 #2096 City Day Telephone: Fax Number: Expiration Date: .S IlljA °� 131o$ State yip ?rf n.1t4.9OI.Ob Zoto. 1 Cot - S351 I of3 /oc.o Valuation of Project (contractor's bid price): $ 1 t O , 7.00Th Scope of Work (please provide detailed information): r1 b C. p.•2'0 P i Pa- t17"1" - tO sER."e tair'E rt. 1PGnrt-sO)' rs -ov)b t' Alit. - rcP r'► ►t --lit - Gbr. vir t+OT 4 ✓r.TEP' Ft e-7,-r) rG Cot 1.-S Fo P- Se 1/404 toNt . col-,at.c r To r - G - 1/4, 0- 141.+L>_ y ' ram- c rEMp P1zo.. t.b a Ese-TErs to +-e OF C,-' c t`- G tt C sei Residential: New.... ❑ Replacement .... ❑ Commercial: New .... Replacement .... ❑ Fuel Tvue: Electric .....0 Gas....( Other: NOTC r> te)a- -1;PT's s.. BOX ac ►zEAt -r. 1 4- e - cr► r'G �►- ' col ., its sC- van t ( ,>✓a P%tF_tomr'bt -t t-JG 'P- IT, ��c)STtYG t5- .c go'LElar htz� i�Bs^•Ttr�soifl.C++ . Page 4 of 6 ... Fixture Type::. ,.: -QtY Fixture Type: :. ::: �; : ; .. ;: ture:T,ype: ty..: re Type: Qty ' Bathtub or combination bath/shower Drinking fountain or water cooler (per head) Wash fountain Gas piping outlets Bidet Food -waste grinder, commercial Receptor, indirect waste Clothes washer, domestic Floor drain Sinks Dental unit, cuspidor Shower, single head trap Urinals Dishwasher, domestic, with independent drain Lavatory Water Closet Building sewer or trailer park sewer Rain water system — per drain (inside building) Water heater and/or vent Industrial waste pretreatment interceptor, including its trap and vent, except for kitchen type grease interceptors Repair or alteration of water piping and/or water treating equipment Repair or alteration of drainage or vent piping Medical gas piping system serving one to five inlets/outlets for specific gas Additional medical gas inlets/outlets —six or more 36 allar PLUMBING AND GAS PPING CONTRACTOR INFORMATION Company Name: fl F He.ctr .t'-'L C.Pct- Mailing Address: q 3?•?- LkriA iSte. S ytestl .8 City Contact Person: f"f uce ')tx.1 otke»J Contractor Registration Nurnber. P '1Eo9ot4t Q Appiic.uor.worres- Applicati.n. Oa L100-2006- ?melt AppIiuiiondoe Revise& 4-2006 bb Indicate type of plumbing fixtures and/or gas piping outlets being installed and the quantity below: ° 18ib8 - SI oZ stale zip Day Telephone: Zclo. 1I.04 . gCoto3 E -Mail Address: tient-lob e t'1a-44 Lot-I Fax Number. Zoo. 1ic2. E'r32:51 Expiration Date: a, C / 3 /O(, Valuation of Project (contractor's bid price): $ 4o, r tCr . oO Scope of Work (please provide detailed information): nzo ` t C E 3G I. bb t'T 16 i '" t_ P —1 E h t Lr4 t_ (fp ov 'R-eT ) 1-0 t%4 i-•t t-C Ye% n l-r r Hoot -Lr Fizo t`7 T r4E S`CcT E t--t -e C 19 ) j at "%I R I t o. c'tG-e P r g ..,a. eL Page 5 of 6 Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Permit Center to comply with current fee schedules. Expiration of Plan Review - Applications for which no permit is issued within 180 days following the date of application shall expire by limitation. Buildinf and Mechanical Permit The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition). Plumbing Permit The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing code (current edition). I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. Print Name: I artAtc G I Date Application Accepted: D AGENT: g b/.y.-0 0 4' e- t And Mailing Address: 21c:I (cnf4 Age, .tttte • tB ta1 Q:\ApplicationsWorms- Applianions On Liae'3 -2006 -Permit Appliwlondoc Revised: 4-2006 an r Date: P) .IS • oCO Day Telephone: 7,t n . 44 t 42Z Scion -, V IAT Tit Z.1 City State Zip Date Application Expires: �$ l Staff Initials: Page 6 of 6 City of Tukwila 6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670 Parcel No.: 1623049001 Permit Number: M06 -184 Address: 12844 MILITARY RD S TUKW Status: APPROVED Suite No: Applied Date: 08/18/2006 Applicant: HIGHLINE MEDICAL CENTER Issue Date: Receipt No.: R06 -01498 Payment Amount: 876.30 Initials: JEM Payment Date: 09/25/2006 10:17 AM User ID: 1165 Balance: 50.00 Payee: HIGHLINE MEDICAL CENTER TRANSACTION LIST: Type Method Description Amount doe: Receipt Payment Check 326205 876.30 ACCOUNT ITEM LIST: Description Current Pints MECHANICAL - NONRES RECEIPT Account Code 000/322.100 876.30 Total: 876.30 0096 09/25 9716 TOTAL 3654.78 Printed: 09 -25 -2006 RECEIPT NO: RO6 -01298 Initials: JEM User ID: 1165 Payee: HIGHLINE MEDICAL CENTER SET TRANSACTIONS: Set Member Amount 006 -323 M06 -184 TOTAL: iC i ty of Tukw Steven M. 1•tmavor Department of Community Development Steve Lancaster. Director 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 -431 -3670 Fax: 206 -431 -3665 SET ID: S000000542 SET NAME: Tmp set/Initialized Activities 1,835.26 211.58 2,046.84 TRANSACTION LIST: Type Method Description Payment Check 324485 ACCOUNT ITEM LIST: Description BUILDING - NONRES PLAN CHECK - NONRES SET RECEIPT TOTAL: Payment Date: 08/18/2006 Total Payment: 2,046.84 Amount 2,046.84 2,046.84 Account Code Current Pmts 000/322.100 19.50 000/345.830 2,027.34 TOTAL: 2,046.84 8784 08/18 9710 TOTAL 2046.84 Project: Project: L , � 4 7 r Altar T pti NJ ' e of Inspection: 2 1797d1/Q$..4 / F d: Address: /7/ 4 /��y Date ailed: '� If Special Instructio s: / Date Wanted:. a.m. Requester. Phone No: IN3RELYION NO. CITY OF TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila, WA 98188 OMMENTS: Inspector: INSPECTION RECORD Retain a copy with permit /7r" /} /)-( S 4 r 97 ft (206)431 I y l Approved per applicable codes. O Corrections required prior to approval. Alf Ariz #t 40 doe 11/47s 7 - 5 - a224 , ____ Date / rN ❑ $58.00 REINSPECTION E REQUIkED. Prior to inspection, fee must be paid at 6300 Southcenter Blvd., Suite 100. Call to sechedute reinspection. Receipt No.: 'Date: Project: Type o Inspection: "," #'T 'II Address I l egW9 til.'J. 29 ate Called: i Special Instructions: —e. Date Wanted: // � Request Phone No: r 2, INSPECTION RECORD Retain a copy with permit INSPECTION NO. CITY OF TUKWILA BUILDING DIVISIO G� . 6300 Southcenter Blvd., #100, Tukwila, WA 98188 (20k)431 -3 MENTS: A pproved per applicable codes 11 Corrections required prior to approval. ri $58.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be paid at 6300 Southcenter Blvd., Suite 100. Call to sechedule reinspection. Receipt No.: !Date: Project: / r % A / • � ' /�/J A Type eooffIInspection: / -a7 42077 Address: JlI 1 1 it r, 1 .. A C 8 Dat all d: Special Instructions: Date Wanted: a.m. _ C�?J'T Requester: Phone No: INSPECTION RECORD Retain a copy with permit INSPECTION NO. CITY OF TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -$ 6 0 Approved per applicable codes. El Corrections required prior to approval. COMMENTS: I t !7'llji /A / wok � � , - c g %.I / n�� et n s� r iv 0104 . 5_37 7 -43 7 rn- ri $58.0 INSPECTION FE REQUIRED. Prior to inspection, fee must be paid at 6300 Southcenter Blvd., Suite 100. Call to sechedule reinspection. Receipt No.: !Date: IIIMIssatirtorsoliassiraiailo ACTIVITY NUMBER: M06 -184 DATE: 08 -18 -06 PROJECT NAME: HIGHLINE MEDICAL CENTER SITE ADDRESS: 12844 MILITARY RD S X Original Plan Submittal Response to Incomplete Letter # Response to Correction Letter # Revision # After Permit Issued DEPARTMENTS: Bui dl Di"vi"sion Public Works DETERMINATIQN OF COMPLETENESS: (Tues., Thurs.) Complete Comments: Approved ❑ Notation: Documents/routing sIip.doc 2 -28-02 REVIEWER'S INITIALS: pod PERMIT COORD COPY PLAN REVIEW /ROUTING SLIP APPROVALS OR CORRECTIONS: u MC' D Fire Prevention Structural Incomplete ❑ ❑ Permit Coordinator ❑ TUES/THURS ROU ING: Please Route Structural Review Required REVIEWER'S INITIALS: Approved with Conditions Permit Center Use Only INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED: Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials: DUE DATE: 08-22 -06 Not Applicable ❑ No further Review Required DATE: DUE DATE: 09-19-06 Not Approved (attach comments) ❑ DATE: Planning Division Permit Center Use Only CORRECTION LETTER MAILED: Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials: License Information License PSFMEI *090NZ Licensee Name P S F MECHANICAL INC Licensee Type CONSTRUCTION CONTRACTOR UBI 601318369 Ind. Ins. Account Id Business Type CORPORATION Address 1 9322 14TH AVE S Address 2 City SEATTLE County KING State WA Zip 98108 Phone 2067649663 Status ACTIVE Specialty 1 SHEET METAL Specialty 2 AIR HEAT,VENTILATION,EVAPORAT Effective Date 8/9/1991 Expiration Date 10/3/2007 Suspend Date Separation Date Parent Company Previous License EDENN * *225LK Next License Associated License Business Owner Information Name Role Effective Date Expiration Date BEARDSLEY, WARREN S 01/01/1980 CRITCHLOW, JAMES D 01/01/1980 Look Up a Contractor, Electrician or Plumber License Detail Page 1 of 2 Now Washington State Department of Labor and Industries General/Specialty Contractor A business registered as a construction contractor with L &I to perform construction work within the scope of its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of account and carry general liability insurance. FEDERAL Bond Information Bond # 2 Bond Company Name FEDERAL INS Co Bond Account Number 81241859 Effective Date 08/08/2001 Expiration Date Until Cancelled Cancel Date Impaired Date Bond Amount $6,000.00 Received Date 10/01/2001 https: // fortress. wa. gov /lni/bbip /printer.aspx ?License= PSFMEI *090NZ 09/25/2006 - e 44.:V' =rG 747.10 as Q AI v.�s 2W HVAC UPGRADES HIGHLINE COMMUNITY HOSPITAL, SPECIALTY CENTER OWNER CONTACT: DIANE MUNROE ARCHITECT CONTACT: RICHARD SALOGGA. STRUCTURAL CONTACT: JOHN SMITH, P.E., S.E. MECHANICAL CONTACT: RON EUASON. P.E. ELECTRICAL CONTACT: BRYAN BOEHOLT, P.E. PROJECT INFORMATION JOB SITE ADDRESS: OWNER: CONTACT: TAX PARCEL NUMBER: PROPERTY CLASSIFICATION: PROJECT CLASSIFICATION: PERMITTING AUTHORITY: BUILDING INFORMATION BUILDING CODE: OCCUPANCY TYPE: CONSTRUCTION TYPE: WEST WANG AREA SEPARATION: OCCUPANCY SEPARATION: SMOKE COMPARTMENTATION: WEST WANG ARCHITECTURAL SYMBOLS e-- L. • 149E R1498 ROOM NAME 101 0 1 4 MA 12844 MIUTARY ROAD SOUTH TUKIMLA. WA HIGHUNE COMMUNITY HOSPITAL 16251 SYVESTER ROAD S.W. BURIEN, WASHINGTON 98166 NORTHWEST ARCHITECTURAL COMPANY 2201 SIXTH AVE, SUITE 1405 SEATTLE. WASHINGTON 98121 162- 304 -9001 RM -900 14/ RS -7200 SINGLE FAMILY PERMITTED USE - HOSPITAL CITY OF TUKWALA KING COUNTY, WASHINGTON WASHINGTON STATE BUILDING CODE (1994 UNIFORM BUILDING CODE AS AMMENDED) 1 -2 TYPE II - ONE HOUR. FIRE SPRINKLERED WEST WING TO NORTH YANG - TWO HOUR NO MIXED OCCUPANCY THIS PROJECT EXISTING. NO CHANGE GRID UNE REVISION REGIONAL HOSPITAL 12844 MIUTARY ROAD SW., TUKW ILA, WA 98168 NORTHWEST ARCHITECTURAL COMPANY, P.S. 2201 SIXTH AVENUE, SEATTLE. WA 98121 (206) 441 -4522 COLLONS & SMITH STRUCTURAL ENGINEERS 485 FRONT STREET NORTH, SUITE F -3. ISSAQUAH, WA 98027 (425) 369 -1101 HARGIS ENGINEERS, INC 600 STEWART STREET, SUITE 1000. SEATTLE. WA 98101 (206) 448 -3376 BrN ENGINEERING, INC 2101 9111 AVE, SUITE 202. SEATTLE. WA 98121 (206) 223 -6446 DOOR IDENTIFICATION REUTE IDENTIFICATION MATCH UNE Shaded area is side considered WORK POINT. DATUM POINT. CONTROL POINT DETAIL Upper mark denotes drawing number Lower mark denotes sheet A 'dash' in the sheet reference location indicates that the detail occurs on the some sheet that R is flogged PARTIAL BUILDING SECTION INTERIOR ELEVATION Elevation number denoted in arrow Sheet number denoted in box ROW IDENTFICATION COOED NOTE WALL TYPE DASHED LINE Used to denote items hidden, overheod, not in contract (lac). or to be removed BREAK LAE Wateid to continue CENTER LRL GM UNE PROPERTY LINE LEGAL DESCRIPTION IN THE COUNTY OF KING. STATE OF WASHINGTON: THAT PORTION OF THE NORTH ONE -HALF OF THE NORTH NORTHEAST ONE- QUARTER OF SECTION 16, TWP, 23N. RANGE 4E. WN M., IN KING COUNTY, WASHINGTON. LYING EASTERLY OF MILITARY ROAD, EXCEPT THAT PORTION OF THE NORTHEAST ONE - QUARTER OF THE NORTHEAST ONE - QUARTER OF SECTION 16. TAP, 2314 RANGE 4E, W.M., IN KING COUNTY, WASHINGTON. DESCRIBED AS FOLLOWS: 1. BEGINNING AT A POINT ON THE SOUTH UNE OF THE NORTHEAST 1/4 OF THE NORTHEAST 1/4 OF SAID SECTION 16, DISTANT EAST 561 FEET FROM THE SOUTHWEST CORNER THEREOF; THENCE NORTH, AT RIGHT ANGLES 184 FEET. THENCE WEST ON A UNE PARALLEL WMTH SOUTH UNE OF SAID SUBDIVISION 225 FEET; THENCE NORTH AT RIGHT ANGLES 210 FEET; THENCE WEST ON A LINE PARALLEL WITH SOUTH UNE OF SAID SUBDIVISION TO THE EASTERLY UNE OF MILITARY ROAD; THENCE SOUTHERLY ALONG SAID EASTERLY UNE OF MIUTARY ROAD TO AND INTERSECTING WITH THE SOUTH UNE OF SAID SUBDIVISION TO POINT OF BEGINNING. AND EXCEPT THAT PORTION OF THE NORTHEAST 1/4 OF THE NORTHEAST 1/4 OF SECTION 16. MP, 23N. RANGE 4E. W.M.. IN KING COUNTY. WASHINGTON, DESCRIBED AS FOLLOWS: 2. BEGINNING AT THE INTERSECTION OF THE SOUTH UNE OF THE NORTH 160 FEET OF SAID SUBDIVISION WITH THE EASTERLY MARGIN OF MIUTARY ROAD; THENCE EASTERLY ALONG SAID SOUTH LINE 200 FEET; THENCE NORTHERLY AT RIGHT ANGLES 160 FEET TO THE NORTH UNE OF SAID SUBDIVISION; THENCE WESTERLY ALONG SAID NORTH UNE TO THE EASTERLY UNE OF SAID MLITARY ROAD; THENCE SOUTHERLY ALONG SAID EASTERLY UNE TO THE POINT OF BEGINNING; EXCEPT THAT PORTION IF ANY, CONVEYED TO KING COUNTY FOR 128TH STREET, BY DEED RECORDED UNDER AUDITOR'S FILE NO.5274608. ARCHITECTURAL MATERIALS DETAIL INDICATIONS • • I I GYPSUM BOARD INSULATION. BATT INSULATION. RIGID I t iIIIIIto PLAIN INDICATIONS ACOUSTIC TILE OR BOARD ROOFING BRICK CERAMIC TILE CONCRETE PRECAST CONCRETE CONCRETE MASONRY UNIT EARTH/FINISH GRADE GLASS GRAVEL METAL METAL LATH MORTAR, PLASTER, SAND PLYWOOD WOOD. F01MSH EOGSTING WALL EIEMEMBISIEBEE NEVI STUD MALL ARCHITECTURAL ABBREVIATIONS L g C e T AB A/C ACOUS ADJ ADJT AFT AL ALT ANC APPD APPROX ARCH AUTO BD BLDG BLK BLKG EIM BOF BOTT ERG 89417 CAB COA CER CG CP cLG CUCG 0.0 CZR COL COMP CONC CONN CONST CONT CONTR CORR CPT CT c m and angle of centerline channd diameter or round plate pound or number tee anchor bolt or acousticol odpstable odjacent above finished floor aluminum alternate onchor(oge) approved approximate architectural automatic board between block blodcing buidng beam bottom of frame bottom bearing basement cabinet cement ceramic corner guard cost in place concrete control jot, construction joint coW ng closet cering dear column composition. composite concrete connection construction continuous controctor corridor oorPot gamic tie center • DBL DEMO DIA DIAG DIM DN OAV OR DWG OWR EA EJ EL ELEC ELEV EMER ENCL EP EQ EQUIP EMiC EXH EXIST (E) EXP EXPO EXT FA FAB FD FE FEC FEC -S FIN FL FLUOR FiOF FOS F091 FP FR itdfG FT FTG PURR FUT GA GALV GEN GL GLZ GYP N CO VICINITY PLAN NO SCALE deep. depth double demolish, demolition diameter diagonal dimension division down door drawing drawer east each expansion joint devotion electrical elevator emergency enclosure d triad pondboard equal equipment electric water coder exhaust existing • n9 expansion exposed exterior fire dorm fabricate floor drain fire extinguisher fore • (recessed) cabinet extinguisher ( ) finish floor fluorescent face of finish face of studs face of shecthig feepraof fee resistant fraying g foot. feet Sooting fEurrrq future gouge galvanized grab bar general foss glazing gypsum board H FIN HC N C HO HOW HORIZ HSS HT HTG HVAC INCL INFO INNSU L INTERCOM JAN • T Jr L LAB LAM LAV LT MACH MAIL MAX Y9R MC MECH MED MOB 11FR ISSC 11T(0) YTS N MC NOOR# NOM NTS OA OC OP G OPP cG high hose bibb hollow core handicap (accessible) head hardware horizontal hollow sled section height heating heating/ventilating/air- conditioning inside diameter (dm.) include information insulation interior intercommunication janitor joist joint length. long laboratory laminate lavatory light, left machine material maximum member medicine cabinet mechanical medium membrane manufacturer manhole. mop holder minimum mirror miscellaneous maunt(ed) metal north not in contract number named not to scare over -dl on center outside diameter h9 opposite original PAR PERF PERP PLAN PL PLUMB PLYWD PNL POS PR PROW PROJ PT QT RCP RECa REEL REWF RESIL RY R S SC SCHED SECT SHR SH SHT SUNG SPEC SO SS1C SS SID STL STOR STRUCT SUlB SU'SP SYS porolld perforated perpendicular plastic lominate plate plumbing Pirwood panel positive Pair prefabricote(d) prefaiish(ed) project pmt, point quarry tie riser. radius reflected ceiling plan roof drain received reference reflected refrigerator reinfarce(d)(ng) required resilient roof room rough opening right south solid core schedule section shower sheeting sheet sheathing ssmior UMW* an service sink stoniess steel standard steel storage stnrcturd substitute suspended symmetrical system • C 104 TEL TEMP TF THK THEW TOF TS TV TVB TW TYP �N UR ye VCT VENT IAZR VERT VEST w w/ sow vas W/O WP WSCT WS WT NITR WNF AREA OF WORK REGIONAL HOSPITAL, WEST WING telephone temporary top of footing thick through top of frame tube steel television television bracket top of wSIPARATE typical PERMIT AND unfinished unless noted otherwise urinal vapor barrier vinyl composition tie ventiote verify vend vestibule volume west. wide; width with wood window well hung without waterproof wainscot weather stripping wdght water welded we fabric S: PARATE . "; i AND ' ?OVAL INDEX OF DRAWINGS GENERAL G0.1 COVER SHEET CODE SUMMARY PUN N CD SITE PLAN SCALE: 1" = 2400' X \ ARCHITECTURAL A3.1 SECOND FLOOR PLAN AND ROOM FINISH SCHEDULE A4.1 BUILDING SECTION A7.1 INTERIOR ELEVATIONS A9.1 SECOND FLOOR REFLECTED CEILING PLAN TRUCTURAL. ST GENERAL STRUCTURAL NOTES FRAMING PLAN AND DETAILS MECHANICAL MO1 MECHANICAL SYMBOLS & LEGENDS MO.2 SCHEDULES- PIPING AND HVAC Y1_1 OEHOU11ON PLAN - PIPING 111.2 OEYOUTION PLAN - HVAC M2.1 SECOND FLOOR PLAN - PIPING Mil SECOND FLOOR PLAN - HVAC 113.2 PENTHOUSE PLAN - PIPING AND HVAC 114.1 DETAILS - PIPING AND HVAC 115.1 CONTROL DIAGRAMS 1152 CONTROL DIAGRAMS ELECTRICAL EO SYMBOL AND ABBREVIATIONS E2.1 2110 FLOOR POWER PLAN NEST E3.1 2ND FLOOR UGHTe1G PLAN *EST E4.1 ONE -LLVE Mat DIAGRAM E4.2 PANG. SOBS SEPARATE mar REQUIRED MR: IEEtterical gpinbtv irGus Plying City of BUILDING DIVISION By tote: COP'S PILE PennftNo. • R VIE D fOR CODE CO! PL N M629 BUILDP f`'iTS Ran review approval Is subject to ems ar Apptoval at construction documents don not oultolso the vlola'oi c ` any accepted code co' ordlro fpe„ Illy at a: _ C : a. aof>dtfpns b ad:nollN140 1,4111DING DIVISION REC6VED afY0FTIMMIU Alit 10 2606 PERICCENTER kAD(o-1 AIDLISti R SHEET l REVISIONS 2207 9XTh A NI.:E SulE T4 SEATTLE. AA 98 (206) 44i -4522 FAX (2t,6) «j -79: I tixc no_ 2 - 06005 ::LE GO-1 .cm; LWW C _C-(ED RAS DcE 7- 28 -06 G 0.1 C Ye4 41. - -Awcz O ieracavi Cs ?r' r '4' SYMBOLS /ABBREVIATIONS MECHANICAL LEGEND 1 AHU -01 I DRAWING NOTE CALLOUT FLAG NOTE CALLOUT • INVERT ELEVATION OR POC GRILLE REGISTER OR DIFFUSER TYPE 341 - 7 - 1 - -- ---SCHEDULE MARK 2 00 `FAIR QUANTITY (CFM) ABV AD AFF BDD BOD CD CG COND CONT CLG DIM DN DWV (E) EXH EG ESP F FD F/S FLEX GPM lE MBH MC MFR MTG NO POC RA RG R /E/T RPBP SA SIM SG TG TYP 0 t + 4 MECHANICAL EQUIPMENT TAG DETAIL /SECTION IDENTIFIER ABOVE ACCESS DOOR ABOVE FINISHED FLOOR BACKDRAFT DAMPER BOTTOM OF DUCT CEIUNG DIFFUSER CEIUNG GRILLE CONDENSATE CONTINUATION /CONTRACTOR CEIUNG DIMENSION DOWN DRAIN WASTE AND VENT EXISTING EXHAUST EXHAUST GRILLE EXTERNAL STATIC PRESSURE FAHRENHEIT FIRE DAMPER FIRE /SMOKE DAMPER FLEXIBLE DUCT GALLONS PER MINUTE INVERT ELEVATION THOUSANDS BTU PER HOUR MECHANICAL CONTRACTOR MANUFACTURER MOUNTING NORMALLY OPEN POINT OF CONNECTION RETURN /RELIEF AIR RETURN GRILLE RETURN /EXHAUST/TRANSFER REDUCED PRESSURE BACKFLOW PREVENTER SUPPLY AIR SIMILAR SUPPLY GRILLE TRANSFER GRILLE TYPICAL DIAMETER • i 71311• tJI F 4 r:= 1 - ►R 20x10 --;4 D 4 D 1:2611: D CM' ■ FD 1 T# t1 RISE IN DUCT - (D =DROP IN DUCT) DUCT SIZE (CLEAR INSIDE DIMENSION) SOUNDLINED DUCTWORK -- RECTANGULAR DUCT UP - RECTANGULAR DUCT DN ROUND DUCT UP ROUND DUCT DN - FLEXIBLE CONNECTION DUCT RISE /DROP W/ 90' ELBOWS (RECTANGULAR DUCTS) _ DUCT RISE /DROP W/ 45' ELBOWS (RECTANGULAR DUCTS) _ DUCT RISE /DROP W/ 90' ELBOWS (ROUND OR OVAL DUCT) _ DUCT RISE /DROP W/ 45' ELBOWS (ROUND OR OVAL DUCTS) SECTION THRU SUPPLY AIR DUCT SECTION THRU RETURN, EXHAUST OR OUTSIDE AIR DUCT - EXHAUST /RETURN ROOF PENETRATION FSD FD EXISTING WORK TO BE DEMOLISHED - VOLUME DAMPER - TRANSITION - FROM RECTANGULAR TO ROUND • SUPPLY ROOF PENETRATION FIRE SMOKE DAMPER CEILING RADIATION FIRE DAMPER DUCT SMOKE DETECTOR CD CEIUNG DIFFUSER RG RETURN /RELIEF AIR GRILLE EG EXHAUST AIR GRILLE - RET /EXH AIRFLOW SUPPLY AIR FLOW T'STAT THERMOSTAT OR TEMP SENSOR - MOTORIZED DAMPER - AUTOMATIC CONTROL VALVE, 3 -WAY - AUTOMATIC CONTROL VALVE, 2 -WAY CBV CIRCUIT SETTING BALANCING VALVE RV PRESSURE RELIEF VALVE PRV PRESSURE REDUCING VALVE FCO CLEANOUT - FLUSH WITH FLOOR WCO WALL CLEANOUT PIPE UP PIPE ELL DOWN PIPE TEE UP PIPE TEE DOWN • HWS - HWR • CWS - CWR - MV 02 MA HWS - HWR CWS CWR MV 02 MA DRAWING SCHEDULE M0.1 MECHANICAL SYMBOLS AND LEGEND MO.2 SCHEDULES - PIPING AND HVAC M1.1 DEMOUTION PLAN - PIPING M1.2 DEMOLITION PLAN - HVAC M2.1 SECOND FLOOR PLAN - PIPING M3.1 SECOND FLOOR PLAN - HVAC M3.2 PENTHOUSE PLAN - PIPING AND HVAC M4.1 DETAILS - PIPING AND HVAC M5.1 CONTROL DIAGRAMS 145.2 CONTROL DIAGRAMS ENERGY CODE NOTES SANITARY WASTE ABOVE GRADE SANITARY WASTE BELOW GRADE EXISTING PIPING COLD WATER PIPING (CIA) HOT WATER PIPING (HW) HOT WATER RECIRCULATING PIPING VENT PIPING HOT WATER HEATING SUPPLY HOT WATER HEATING RETURN PIPE CONNECTION PIPE CAP UNION WYE STRAINER ISOLATION VALVE CHECK VALVE POINT OF CONNECTION TO EXISTING BALANCING VALVE CHILLED WATER SUPPLY CHILLED WATER RETURN MEDICAL VACUUM OXYGEN MEDICAL AIR 1 _ MOTORS: COMPLY WITH MINIMUM FULL LOAD EFFICIENCIES USTED IN WSEC, SECTION 1437 AND TABLE 14-4. 2. PIPING AND DUCT INSULATION: COMPLY WITH THICKNESS AND TYPES USTED IN WSEC, SECTION 1415.1 AND TABLE 14 -6 FOR PIPING AND SECTION 1414.2 AND TABLE 14 -5 FOR DUCTS UNLESS MORE STRINGENT INSULATION REQUIREMENTS ARE SPECIFIED. 3. DUCT SEAUNG: SEAL DUCT TRANSVERSE JOINTS AND LONGITUDINAL SEAMS PER WSEC, SECTION 1414.1 UNLESS MORE STRINGENT SEALING REQUIREMENTS ARE SPECIFIED. 4_ RECORD DRAWINGS: SUBMIT TO THE BUILDING OWNER WITHIN 90 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE OR PER WSEC, SECTION 1416.1. 5. OPERATION AND MAINTENANCE MANUAL SUBMIT TO THE BUILDING OWNER PER WSEC, SECTION 1416.2. PROVIDE COMPLETE NARRATIVE OF HOW EACH SYSTEM SHOULD WORK INCLUDING RECOMMENDED SET POINTS." 6_ SYSTEM BALANCING: BALANCE HVAC SYSTEMS PER WSEC SECTION 1416.3 AND SUBMIT A WRITTEN REPORT TO THE BUILDING OWNER. REFER TO SPECIFICATIONS FOR ADDITIONAL TESTING, ADJUSTING, AND BALANCING (TAB) REQUIREMENTS. 7. THE MECHANICAL WORK SHALL BE COMMISSIONED IN ACCORDANCE WITH SECTION 1416.4 OF THE WA STATE ENERGY CODE INCLUDING THE REQUIREMENTS FOR SIMPLE SYSTEMS, OTHER SYSTEMS, DOCUMENTATION, COMMISSIONING REPORTS (PRELIMINARY AND ANAL), AND ACCEPTANCE. THE BUILDING WILL NOT BE ACCEPTED AND ISSUED A FINAL CERTIFICATE OF OCCUPANCY UNTIL THE BUILDING OFFICIAL DETERMINES THAT A PREUMINARY COMMISSIONING REPORT HAS BEEN COMPLETED. 8. AN AR BALANCE REPORT IS REQUIRED SHOWING AIR FLOW RATES MEASURED AND ADJUSTED TO WITHIN 10% OF DESIGN RATES. WRITTEN BALANCE REPORT SHALL BE PROVIDED TO THE OWNER. GENERAL MECHANICAL NOTES GENERAL NOTES - MECHANICAL 1. EXPOSED PIPING: PROVIDE CHROME PLATING FOR EXPOSED PIPING IN FINISHED ROOMS. 2. LIGHT FIXTURE CLEARANCE: COORDINATE LOCATIONS OF MECHANICAL WORK TO PROVIDE CLEARANCES OVER UGHTING FIXTURES FOR REMOVAL AND REPLACEMENT. 3. CABLE TRAYS: DUCTWORK AND PIPING INSTALLED ADJACENT TO ELECTRICAL CABLE TRAYS SHALL ALLOW MINIMUM ACCESS OF 12" ABOVE AND TO THE SIDE OF CABLE TRAYS. 4. DO NOT RUN ANY PIPES OR DUCTS OVER ANY ELECTRICAL PANEL OR SWITCHGEAR. COORDINATE /LOCATE PIPE AND DUCT LOCATIONS TO AVOID ELECTRICAL PANELS. 5. CONTRACTOR SHALL COORDINATE /LOCATE DMSION 15 WORK WITH THAT OF OTHER TRADES ( ELECTRICAL. ARCHITECTURAL, STRUCTURAL). REFER TO ELECTRICAL, ARCHITECTURAL, AND STRUCTURAL DRAWINGS AND SPECIFICATIONS. 6. PROVIDE MANUFACTURER'S RECOMMENDED AND CODE REQUIRED CLEARANCE AROUND ALL PIECES OF EQUIPMENT. PIPING AND CONDUIT SHALL NOT INTERFERE WITH REQUIRED ACCESS. 7. EQUIPMENT LAYOUT IS BASED ON EQUIPMENT USTED IN EQUIPMENT SCHEDULES. OTHER EQUIPMENT USED IS SUBJECT TO MEETING PERFORMANCE REQUIREMENTS OF SCHEDULED EQUIPMENT. CONTRACTOR SHALL MAKE ALL NECESSARY ADJUSTMENTS /DESIGN CHANGES TO ASSURE EQUIPMENT, OTHER THAN SCHEDULED, WILL FIT IN AVAILABLE SPACE. MECHANICAL EQUIPMENT INSTALLATION NOTES 1. ACCESS CLEARANCES FOR MAINTENANCE AND REPLACEMENT: VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ACCESS CLEARANCES CAN BE MET. COORDINATE LOCATIONS OF MECHANICAL WORK AND WORK OF OTHER TRADES TO PROVIDE ACCESS CLEARANCES FOR SERVICE AND MAINTENANCE. DEMOLITION NOTES 1. PIPING: REMOVE EXISTING PIPING SERVING ITEMS TO BE REMOVED. REMOVE UNUSED BRANCH PIPING LEAVING NO DEAD PIPE LEGS. CAP OR PLUG IN A CONCEALED MANNER. 2. DUCTWORK: REMOVE EXISTING DUCTWORK AS INDICATED. CAP EXISTING OPENINGS NOT BEING REUSED WITH SHEET METAL AND COVER EXISTING OPENINGS BEING REUSED WITH PLASTIC SHEETING COMPLETELY SEALED WITH TAPE. 3. EQUIPMENT: REMOVE EXISTING HVAC EQUIPMENT AS INDICATED, INCLUDING ASSOCIATED PIPING, CONTROL SYSTEMS, AND APPURTENANCES. PIPING NOTES 1. DISASSEMBLY PROVISIONS: PROVIDE UNIONS OR FLANGES AT PIPING CONNECTIONS TO EQUIPMENT, COILS, TRAPS, CONTROL VALVES, AND OTHER COMPONENTS TO ALLOW DISASSEMBLY FOR MAINTENANCE. 2. REDUCERS: PROVIDE AS REQUIRED FROM UNE PIPE SIZE TO EQUIPMENT, TRAP, COIL, AND CONTROL VALVE CONNECTION SIZES. 3. OFFSETS: PROVIDE FOR BRANCH UN ES TO EQUIPMENT. 4. DIELECTRIC UNIONS: PROVIDE AT CONNECTIONS OF DISSIMILAR PIPE. 5. COIL PIPING: COORDINATE LOCATIONS WITH DUCT LAYOUT DRAWINGS. PIPE SUPPLY WATER UNES TO COIL LEAVING AIR SIDES (AT BOTTOM) TO OBTAIN COUNTERFLOW ARRANGEMENT. 6. PETE'S PLUGS: PROVIDE AT SUPPLY AND RETURN CONNECTION TO ALL EQUIPMENT. TEST PLUGS FOR EQUIPMENT SHALL BE LOCATED IMMEDIATELY ADJACENT TO THE EQUIPMENT SUCH THAT THERE ARE NO FITTINGS BETWEEN THE TEST PLUG AND THE FINAL EQUIPMENT CONNECTION POINT. PROVIDE TEST PORTS IMMEDIATELY ADJACENT TO ALL SENSORS, GAGES, AND THERMOMETERS. 7. BALANCING /MEASURING VALVES: SIZE SMALLER THAN UNE SIZE IF REQUIRED TO RESULT IN MINIMUM 1 FT PRESSURE DROP AT DESIGN FLOW, AS CLOSE TO UNE SIZE AS POSSIBLE. PROVIDE REDUCERS UPSTREAM AND DOWNSTREAM AS REQUIRED. INSTALL VALVES WITH STRAIGHT PIPE UPSTREAM AND DOWNSTREAM AS REQUIRED BY MANUFACTURER'S INSTRUCTIONS. 8. HEATING AND CHILLED WATER PIPING: 3/4 INCH MINIMUM PIPE SIZE. INSULATION /LINING NOTES 1. EXTENT OF INTERNAL DUCT UNING: NONE. 2. EXTENT OF EXTERNAL DUCT INSULATION: A. SUPPLY NR DUCTS ABOVE COUNGS OR EXPOSED_ B_ SUPPLY AND RETURN AIR DUCTS OUTDOORS. 3. MISCELLANEOUS DUCT FITTINGS (CONICAL TAKEOFFS, ETC.): WRAP WITH INSULATION FOR CONDENSATION CONTROL PLUMBING NOTES 1. COOLING COIL CONDENSATE DRAINS: PIPE WITH TRAP PER MANUFACTURER'S RECOMMENDATIONS, AND ROUTE OUTDOORS AS INDICATED_ TERIAINATE WITH 1" AIR GAP. FIRE PROTECTION NOTES . 1. RELOCATE EXISTING SPRINKLER HEADS AS REQUIRED TO _: : ACCOMMODATE AR DISTRIBUTION SYSTEM_ -- SHEET METAL NOTES 1. REFERENCE: SMACNA I-VAC DUCT CONSTRUCTION STANDARDS, METAL AND FLEXIBLE, SECOND EDITION, 1995 ( SMACNA HVACDCS). 2. CLEARANCE: COORDINATE DUCTWORK WITH MISCELLANEOUS OBSTRUCTIONS IN CEILING SPACE. 3. DUCT SIZES: SIZES INDICATED ARE INSIDE CLEAR DIMENSIONS. 4. ROUND AND FLAT OVAL ELBOWS AND OFFSETS: FULL RADIUS (R /D = 1.5). 5 -PIECE SEGMENTED OR STAMPED. REFER TO SMACNA HVACDCS' FIGURES, 3 - 3 AND 3 - 6. REFER TO SMACNA HVACDCS FIGURE 2.7 FOR OFFSETS. DO NOT USE ANGLED OFFSET (TYPE 1). MITERED OFFSET (TYPE 2) MAY BE USED UP TO 30 DEGREE OFFSET ANGLE. 5. ROUND AND FLAT OVAL TEES AND LATERALS: CONICAL TEE FITTING OR TAP PER SMACNA HVACDCS FIGURE 3 -5. 90- DEGREE TEE WITH OVAL TO ROUND TAP, 45- DEGREE LATERAL FITTING, TAP, OR SADDLE TAP, AND 45- DEGREE RECTANGULAR LEAD -IN PER SMACNA HVACDCS FIGURE 3 -4. DO NOT USE STRAIGHT TEE. DO NOT USE CONICAL OR 45- DEGREE LATERAL SADDLE TAP FOR EXPOSED DUCTWORK IN FINISHED SPACES. 6. RECTANGULAR ELBOWS AND OFFSETS: FULL RADIUS WHERE MINIMUM 5 DUCT WIDTHS IS AVAILABLE DOWNSTREAM OF ELBOW PRIOR TO BRANCH TAKEOFFS AND FIRINGS, R/W = 1.5. OTHERWISE, USE SQUARE CORNER ELBOW WITH TURNING VANES. REFER TO SMACNA HVACDCS FIGURE 2 -7 FOR OFFSETS. DO NOT USE ANGLED OFFSET (TYPE 1). MITERED OFFSET (TYPE 2) MAY BE USED UP TO 30 DEGREE OFFSET ANGLE. 7. RECTANGULAR DMDED FLOW FITTINGS: USE GENERALLY, EXCEPT BRANCHES TO TERMINALS; REFER TO SMACNA HVACDCS FIGURE 2 -5. 8. TURNING VANES: H.E.P. MANUFACTURER OR APPROVED HIGH EFFICIENCY PROFILE AIRFOIL TYPE FOR RECTANGULAR AND FLAT OVAL SQUARE THROAT ELBOWS. ACOUSTICAL TYPE FOR RETURN AIR MITERED ELBOWS. 9. TAKEOFFS TO OPENINGS: 10.VOLUME DAMPERS: PROVIDE A MANUAL VOLUME DAMPER FOR EACH SUPPLY AND EXHAUST OPENING, LOCATED AS FAR UPSTREAM AS POSSIBLE FROM THE OPENING. PROVIDE A MANUAL VOLUME DAMPER FOR BRANCH MAINS SERVING MORE THAN ONE OPENING. 11. DUCTS UPSTREAM OF AIR TERMINAL UNITS: A. CONICAL TYPE WITH VOLUME DAMPER FOR ROUND DUCT BRANCHES PER SMACNA HVACDCS FIGURE 2 -6, MINIMUM INLET DIAMETER 2 INCHES LARGER THAN DUCT SIZE. 45 DEGREE ENTRY FITTING FOR RECTANGULAR DUCT BRANCHES PER SMACNA HVACDCS FIGURE 2 -6. B. FLEX DUCTS: LOW PRESSURE FLEX DUCTS MAY BE USED WHERE SPACE PERMITS. DO NOT INSTALL IN CORRIDOR CEIUNG SPACES WHERE FIRE RATING IS REQUIRED. MAXIMUM DEVELOPED LENGTH 7 FT. GENERALLY INSTALL WITH STRAIGHT SECTIONS, WITHOUT BENDS; PROVIDE SHEET METAL ELBOWS FOR CHANGES IN DIRECTION TO RESULT IN STRAIGHT FLEX DUCT RUNS. IF BENDS ARE ABSOLUTELY NECESSARY, R/D SHALL BE 2.5 OR GREATER. NO KINKS ALLOWED. SUPPORT WITH MINIMUM 1 INCH WIDE STRAPS AROUND DUCT, MAXIMUM UNSUPPORTED LENGTH 5' -0 ", MAXIMUM SAG 0.5 INCH PER FOOT OF SUPPORT SPACING. SUPPORT SYSTEM SHALL NOT CAUSE OUT OF ROUND SHAPE. REFER TO SMACNA HVACDCS FIGURES 3 -9 AND 3 -10. A FLEX DUCTS: MEDIUM PRESSURE FLEX DUCTS MAY BE USED ONLY WHERE SPACE IS UMMTED. GENERALLY INSTALL WITH STRAIGHT SECTIONS, WITHOUT BENDS; PROVIDE SHEET METAL ELBOWS FOR CHANGES IN DIRECTION TO RESULT IN STRAIGHT FLEX DUCT RUNS. IF BENDS ARE ABSOLUTELY NECESSARY, R/D SHALL BE 2.5 OR GREATER. NO KINKS ALLOWED. SUPPORT WITH MINIMUM 1 INCH WIDE STRAPS AROUND DUCT, MAXIMUM UNSUPPORTED LENGTH 5' -0 ", MAXIMUM SAG 0.5 INCH PER FOOT OF SUPPORT SPACING. SUPPORT SYSTEM SHALL NOT CAUSE OUT OF ROUND SHAPE. REFER TO SMACNA HVACDCS FIGURE 3 -9. B. NR TERMINAL UNIT INLET CONNECTIONS: PROVIDE TWO FEET OR THREE EQUIVALENT DUCT DIAMETERS, WHICHEVER IS GREATER, OF STRAIGHT SHEET METAL DUCT AT INLET OF EACH AIR TERMINAL UNIT, SIZE EQUAL TO UNIT INLET CONNECTION SIZE. PROVIDE TRANSITION IF PRIMARY DUCT SIZE IS LARGER THAN INLET INLET CONNECTION SIZE, LOCATED AT UPSTREAM END OF STRAIGHT SHEET METAL DUCT. 12.DUCTS DOWNSTREAM OF AIR TERMINAL UNITS: A. TRUNK DUCT: EXTENDED PLENUM OF CONSTANT SIZE TO MATCH UNIT DISCHARGE CONNECTION SIZE, OR MINIMUM SIZE PER SCHEDULE WITH TRANSITION FROM BOX DISCHARGE CONNECTION SIZE. MINIMUM 4 FT. OF RUN PRIOR TO FIRST TAKEOFF. B. TAKEOFFS TO OPENINGS: REFER TO PARAGRAPH ABOVE. IN GENERAL, ONE TAKEOFF FROM TRUNK DUCT FOR EACH OPENING. 13.ACCESS DOORS: PROVIDE AT ARE /SMOKE DAMPERS AND DUCT SMOKE DETECTORS. CRYOFTHIC AUG 18 ?cti PERMIT • MECHANICAL SYMBOLS AND LEGEND REVISIONS 2201 SIXTH AMIDE SATE 1405 SEATTLE, WA 98121 (206) 441 -4522 FAX (206) 441 -7917 Ihi 44 �f !,1 1 N IAC No. 2 -06005 ALE DRAIN CHECKED DATE 7 -28 -06 AIR TERMINAL UNIT SCHEDULE SCHEDULE HEATING COIL - ELECTRICAL/FAN(S) MARK AREA SERVED ASSOCIATED AHU MAN. /MODEL NO. AIRFLOW (CFM) INLET DUCT (IN) OUTLET DUCT (IN) W x H MBH EAT ('F) EAT CO ROWS (I) GPM EWT co MAX H2O PD (FT) RUNOUT SIZE (IN) VALVE TYPE DIMENSIONS (LxWxH) (INxINxIN) REMARKS TU -32 CLEAN UTILITY, SOILED UTILITY AHU -6 TITUS DEW 310 6 12 8 5.1 60 75 1 ` 0.5 180 2.5 3/4 2 -WAY 23 12 8 1900 TU -33 PATIENT ROOM, TOILET AHU -6 TITUS DEW 250 5 12 8 4.1 60 75 1 0.4 180 2.5 3/4 3/4 2 -WAY 2 -WAY 23 12 8 23 12 8 54 TU -34 PATIENT ROOM, TOILET, EQUIP. AHU -6 TITUS DESV 250 5 12 8 4.1 60 75 1 0.4 180 2.5 TU -35 PATIENT ROOM, TOILET AHU -6 TITUS DESV 300 6 12 8 5.0 60 75 1 0.5 180 2.5 3/4 3/4 2 -WAY 2 -WAY 23 12 8 23 12 8 180 TU -36 PATIENT ROOM, TOILET AHU -6 TITUS DEW 250 5 12 8 4.1 60 75 1 0.4 __ 180 2.5 TU -37 PATIENT ROOM, TOILET AHU -6 TITUS DESV 310 6 12 8 5.1 60 75 1 0.5 180 2.5 3/4 2 -WAY 23 12 8 -70 TU -38 CORRIDOR AHU -6 TITUS DEW 490 7 12 10 8.1 60 75 1 0.8 180 2.5 3/4 2 -WAY 23 12 10 PATIENT ROOM TU -39 FUTURE PATIENT ROOM, TOILET AHU -6 TITUS DESV 250 5 12 8 4.1 60 75 1 0.4 180 2.5 3/4 2 -WAY 23 12 8 TU -36 TU -40 PATIENT ROOM, TOILET AHU -6 TITUS DEW 290 6 12 8 4.8 60 75 1 0.5 180 2.5 3/4 2 -WAY 23 12 8 10 TU -41 PATIENT ROOM, TOILET AHU -6 THUS DEW 240 5 12 8 4.0 60 75 1 0.4 180 2.5 3/4 2 -WAY 23 12 8 0 TU - 42 PATIENT ROOM, TOILET AHU - 6 TITUS DEW 240 5 12 8 4.0 60 75 1 0.4 180 2.5 3/4 2 - WAY 23 12 8 70 TU - 43 SHOWER, TOILET AHU -6 TITUS DESV 165 4 12 8 2.7 60 75 1 0.3 180 2.5 3/4 2 -WAY 23 12 8 TOILET ROOM AIR HANDLING UNIT SCHEDULE SCHEDULE MAX CFM /FT < 25 NC ELECTRICAL/FAN(S) FINISH MATERIAL COIL MAX APD/ FACE VEL FPM COOLING GPM ENT H2O DB/W8 LEV H2O DB/W8 ( MAX WATER PD FT) VALVE TYPE WEIGHT LBS) RUN OUT SIZE CW IN NOMINAL DUCT WIDTH (IN) MARK AREA SERVED MANUFACTURER /MODEL NO. SUPPLY FAN CFM RETURN/ EXH FAN (CFM) MIN OA CFM MAX OA CFM SUPPLY FAN MOTOR HP ESP IN) TSP IN RPM RETURN FAN MOTOR HP ESP IN TSP IN RPM V/0 (MBH) ' ENT AIR DB/WB F) LEV AIR DB/WB (F) REMARKS AHU -6 2ND FLOOR WEST HAAKON CUSTOM 3500 1900 1600 3500 5 2 4 3450 1 0.5 1 1750 208 1 3 104 80.1 / 62.0 53.2 / 51.0 0.7 / 450 21.4 44 54 15 3 -WAY 4430 2 NOTE 1 1. 2. NOTES SUM OF SA AND RA GRILLES AND DIFFUSERS. CAPACITIES ARE ADJUSTED FOR DUCT LEAKAGE. DRIVE (VFD). AHU -6 FACE VELOCITY OF 1000 FPM 6 FAN AIRFLOWS DO NOT MATCH THE FAN CONTROLLED BY VARIABLE FREQUENCY AIR DEVICE MARK SCHEDULE MAX CFM /FT < 25 NC FRAME TYPE FINISH MATERIAL REMARKS TYPE MANUFACTURER SUPPLY / RETURN / EXHAUST BORDER TYPE NECK SIZE (L "xW") FACE SIZE (L "xW") (IN) CFM RANGE < 25 NC NOMINAL DUCT WIDTH (IN) CD -1 CEIUNG DIFFUSER TITUS MCD SUPPLY HARD OR LAY -IN 6 x 6 24x24 0 - 150 NA NA 1 OR 3 WHITE STEEL NOTE 1, 2 8x8 155 -310 - RG -1 RETURN GRILLE TITUS 350RL RETURN HARD OR LAY -IN 8 x 8 - 0 - 150 NA NA I 1 OR 3 l WHITE STEEL NOTE 1 12 x 12 155 - 350 IAC / HLFM EG-1 EXHAUST GRILLE TITUS 350RL RETURN HARD OR LAY -IN 8 x 8 - 0 - 150 NA NA 1 OR 3 WHITE STEEL NOTE 1 12 x 12 155 - 350 MOTES 1. FACE SIZE FOR HARD CEIUNG IS NECK SIZE PLUS 5 INCHES. 2. DUCT RUNOUT SIZE SHALL BE THE ROUND EQUIVALENT OF DIFFUSER OR GRILLE NECK SIZE. EXISTING FAN SCHEDULE MARK LOCATION AREA SERVED I MANUFACTURER/MODEL NO. SUPPLY FAN (CFNI) TSP (IN) FAN ' RPM MOTOR (HP) V/0 REMARKS EF -3 ROOF 2 WEST. 3 WEST 4 WEST ALADDIN F2226 4680 5/8 415 1 -1/2 208 / 3 NOTE 1 - - - - 4375 7/8 450 1 -1/2 208 / 3 NOTE 2 - - _ - - 5225 1.25 538 2 208 / 3 NOTE 3 1 _ DESIGN AIFLOWS 2_ DATA BASED 3. DESIGN AIRFLOW NOTES OF 2 WEST (WEST WING). UNDER THIS CONTRACT IS COMPLETED_ (ORIGINAL) INCLUDING REMODEL UPON EXHAUST FAN NAMEPLATE. WHEN 2 WEST EAST WING REMODEL SOUND ATTENUATOR SCHEDULE / PRESSURIZATION SCHEDULE ROOM NAME VOLUME ( FT"3) AHU NOISE REDUCTION (Db) WAC 246- 320 -525 DESIGN AIRFLOW (CFM) MARK LOCATION / AREA SERVED MANUFACTURER /MODEL NO. EA (ACH) TYPE SIZE (WxH) AIRFLOW (CFM) 63 (HZ) 125 (HZ) 1 _ _ N N a 500 (HZ) 1000 (HZ) 2000 (HZ) _ _ 1 i _ _ 1 i FACE VELOCITY (FPM) LENGTH (FT) I REMARKS SA -1 AHU -6 SUPPLY IAC / HLFM 110 5 HLFM 24x18 3500 10 12 21 23 22 16 12 10 1000 5 1 200 SA -2 AHU -6 RETURN IAC / HLFM _5 HLFM 24x18 1900 10 12 21 23 22 16 12 10 1000 5 1 PATIENT ROOM 1. AHU -6 FACE VELOCITY OF 1000 FPM 6 170 NOISE REDUCTION BASED UPON A AIR BALANCE ROOM / PRESSURIZATION SCHEDULE ROOM NAME VOLUME ( FT"3) AHU TU WAC 246- 320 -525 DESIGN AIRFLOW (CFM) REMARKS SA (ACH) SA (CFM) EA (ACH) EA (CFM) PRESS (1) SA RA EA P 225 227 CLEAN UTILITY 1200 AHU -6 TU -32 4 80 0 0 P 180 110 _ 0 70 SOILED UTILITY 760 AHU -6 TU -32 2 30 10 130 N 130 0 200 -70 229A TOILET ROOM 120 AHU -6 TU -33 0 0 10 20 N 0 0 70 -70 229 PATIENT ROOM 1640 AHU -6 TU -33 6 170 0 0 P 250 180 0 70 231 PATIENT ROOM 1640 AHU -6 i TU -34 6 170 0 0 P 250 180 0 70 231A TOILET ROOM 120 AHU -6 TU -34 0 0 10 20 N 0 0 70 -70 235A TOILET ROOM 120 AHU -6 TU -35 0 0 10 20 N 0 0 70 -70 233 SUPPUES 80 AHU -6 TU -35 0 0 0 0 NA 50 50 0 0 235 PATIENT ROOM 1640 AHU -6 TU -35 6 170 0 0 P 250 180 0 70 237 PATIENT ROOM 1640 AHU -6 TU -36 6 170 0 0 P 250 180 0 70 237A TOILET ROOM 120 AHU -6 TU -36 0 0 10 20 N 0 0 70 -70 241A TOILET ROOM 120 AHU - 6 TU - 37 0 0 10 20 N 0 0 70 - 70 241 PATIENT ROOM 1640 AHU -6 TU -37 6 170 0 0 P 310 240 0 70 242 FUTURE PATIENT ROOM 1640 AHU -6 TU -39 6 170 0 0 P 250 180 0 70 242A TOILET ROOM 120 AHU - 6 TU - 39 0 0 10 20 N 0 0 70 - 70 238* TOILET ROOM 120 AHU -6 TU -40 0 0 10 20 N 0 0 70 -70 238 PATIENT ROOM 1600 AHU -6 TU -40 6 160 0 0 P 240 170 0 70 236 PATIENT ROOM 1600 AHU -6 TU -41 6 160 0 0 P 240 170 0 70 240 EQUIPMENT STORAGE 120 AHU -6 TU -41 0 0 0 0 NA 50 0 0 0 236A TOILET ROOM 120 AHU -6 TU -41 0 0 10 20 N 0 0 70 -70 232A TOILET ROOM 120 AHU - 6 TU - 42 0 0 10 20 N 0 0 70 - 70 232 PATIENT ROOM 1600 AHU - 6 113 6 160 0 0 P 240 170 0 70 230 TOILET ROOM 400 AHU -6 TU -43 0 0 10 70 N 0 0 70 -70 228 SHOWER 1480 AHU -6 1U -43 0 0 10 250 N 165 0 235 -70 226 JANITOR 120 AHU -6 TU -43 0 0 10 20 N 0 0 70 -70 239 EQUIPMENT STORAGE 320 AHU -6 TU -43 0 0 0 0 N 0 0 70 -70 234 JANITOR 120 AHU -6 TU -43 0 10 0 0 N 0 0 70 -70 243 EQUIPMENT STORAGE 120 AHU -6 1U -43 0 0 0 0 NA 50 50 0 0 CORRIDOR 4880 AHU -6 _ TU -38 4 490 0 0 P 490 0 0 490 1. NOTES E= EQUAL, NA = NOT APPLICABLE P = POSITIVE, N = NEGATIVE, • • • • • • lb - - : • RECEIVED CITY NA AUG 18100i PERRI CENTER I one wutart I SCHEDULES - PIPING AND HVAC REVISIONS 0$ 2201 SIXTH AVENUE SUITE 1405 SEATTLE, WA 98121 (206) 441 -4522 FAX (206) 441 -7917 NAC No. 2 -06005 FILE DRAIN CHECKED DATE 7 -28-06 • M 0.2 1 C ?rif iw#..tskc1 last G PS i 12844 MIL • • • 1 • D g g z 0 ci? m e a 81" 2g PR a gi • 1•• HIGHLINE MEDICAL CENTER, SPECIALTY CAMPUS i • • I - .. • REGIONAL HOSPITAL 2W HVAC UPGRADES 12844 MILITARY ROAD SOUTH, TUKWILA, WA 98168 I i '� t 1r� • ' • I / • • r'y .. • cop 1 I 1I I • L,1 L.rT------ - - - - -- + r+ 1 I � r--- w--- r - - - - - I •• .., ') bi b t... 1 1 1 ;11 • . —....- I 1 t 1 I 11 I; 1 1 II • rr • — — — • — • — • • • IM — ' 1 1 1 II ;' I�w I •I KN 1 I o 15 na I . • • ro I I - -• MWR • f � ', WR Hw I - { � y,V MA HARGIS • J • • KO MIMI Mil w .000 w.•w1, «,a 02 MV rAV Qr SearaseaS 8/8011101 • loloomitracollare r, 1 II 1 1 • I t I I 41 w-------- .ww�w.w.w L 41. � , - .1 IMO. - - - - - -- I HMV MA . - T ; •J • 1 ■ • i Hw, HWn^ �•- 1 • -- - MV -- • 1 i I; ,! 1 1 N A c 0 g c 2 I 1 1 1 RG-1 " 1 150 r �7 1 l _ 1 1 FC ' 1 1 1 a • • CD - 150 85 ) - 1 :_� .7 -3 T( = 9x6 -r-- - - -- -r te 1 20x9 : � 18x9 E 1 1 225 _00 ; • -7 w • i 1 1 1 1 1 1 1 1 1 1 1 1 1 • • CD -1 r= :�1 RG -1 • , 160 _- Ft -1 I. - -� 270 r' e � EG -1 at: J CD- 1 CD -1 x -1!'1' 165 165 T " � 35• _. CD -.1 160 CO x to 1• a 14 k t % \ ti - - -- EG-1 . iv r - t� 4 -r" � -.:L � j. x, >- 1 12x71 � . - . - - - ' %ra•) w -i % , 1 \ V -- CD -1 '- 165 E--1 CD -1 fix, 200 16x9 - RG =1 RG -1 1 1 1 1 I 1 1 1 1 1 1 1 1 1 1 r - 270 L` 7 • 270 V —# 1 1 / T T .T 1 J- 1. 'slit/AO-1 0 a . _ 1- -1 — r — r FC-1 L_ 11 - .1- -1- --- - , ' - 1 1 TT RG -1 270 10 x 0) /- -1 1 1120 '1 • < `` \ '1= CD -1- 1iN 160 I IL' i — 7 _- _ 1 I _z -- -..,, ♦` I - I- - - - <- - - -. • / . Z- - -� }� r- t. • I %i —r —j• •- % i Pi ~Et:- -.- t • I 1 • 1 I • • 1 • • 1 ° • EG -1 1 1 j j - r l. T 55 - 1 1 1 1 ; ; � ' .1 . 1 1 CD - 1 :-4- -I- t,_ T ' i y _ 165 _ � 1 0x6 10x6 11 _ . `' � lizzii N ICD DEMOLITION PLAN - HVAC Scale: 1 /4" = 1' -0" • 165 CD -1 CD-1 1 11 1 460 CD -1 200 RG -1 k - I- 4 -- 1 • 1 1 • at 1 -L 8x5 • co-1 165 0 1 2 4 8 \ 1 1 I- - 1 , i -- - r te 1-271;7- 2x7 1 , A t; 'i 1" wig zt _ � 270 L` =.'J E{ T-4 55 _ _ 1 _ L 1 I ` ;. RG -1 r - - u 1 z � ; i 270 L. !'a J • 1:i -.CD -1 . • }.1 I I `- 160 ♦ ti- _ -r ,. - � / . ' ; v i -t�- . -- 9x7 i • 1 N T i •+ (•� - - -- r-? -_. J 1 -- 1 1 FC -3 400 - ; T . T T / 11 1 1 1 1 1 1'1 1 1 V 1 1 r r =" 1 CD -1. ----- 1,'. I 1 1 225 d--11 1 1 r 11 1 r • 1 • 11 1 1 • • ! 1 '- % � ` - •. is 1 -� , ` ; 1 1 ;` f 1 r � 1 - - .C\'' -4 r r ` % `� 1 1 M811111:41 8.< r. I . ; ��- L..1�` % 1 t1 't =1 \ 1 1 - 50 I- -I I • - rr - - s. s = -�I 1 1 1 Ir = —� 1 r; a , , 55 - - - - - - T T r- ffx4 _ -_�:., - - - - 6x4 - - -k =T►- - - - i CD -1 • / 40 x 0) 1- 1 1 / TT � j 1 � 1 ,1% - `; ` • , . / \f - 1 ' 1 I . • trao k& CD -1 Il 225 225 1 1 1(01 • i°' • i • 1 1 I I }� Isit 0 iv I GENERAL NOTES: CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURER' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS. FLAG NOTES: DEMOUSH EXISTING TERMINAL BOX ALONG WITH AU. ASSOCIATED SUPPLY DUCT AND AIR TERMINAL DEVICES. DEMOLISH EXHAUST DUCT BACK TO MAINS AND CAP. PRIOR TO DEMOLITION, OBTAIN AIRFLOW READINGS AND REBALANCE SYSTEM AT COMPLETION OF CONSTRUCTION TO THESE MEASURED AIRFLOWS. CAP DUCT IN CEILING. DO NOT DISTURB ANY AREAS NOT IN THIS SCOPE OF WORK. ABANDON REMAINING DUCT IN CEILING. COORDINATE DEMOLITION OF EXISTING WORK AND CONSTRUCTION OF NEW WORK IN ORDER TO MINIMIZE THE DURATION THAT BOTH THE SOILED UTILITY AND CLEAN UTILITY ROOMS ARE OFFUNE. COORDINATE CONSTRUCTION AND INFORM OWNER WHEN AND FOR HOW LONG THESE ROOMS WILL BE OFFUNE. r r i L L• ! �:•—; T• • RECEIVED CRYOFT1IKVALP AUG 2606 KIWI CENTER Wit/2067 1 DEMOLITION PLAN - HVAC I REVISIONS • U J � a W eL VI W W U < O- 0 Z U W O a Z J 2 0 Isla OC N 2201 SIFXIH AVENUE SU11E 1406 SEATTLE. WA 98121 (206) 441 -4522 FAX (200) 441 -7917 e4AC HO. 2 - 06005 FU DRAM OOCED DATE 7 -28 -06 • 1 M 1.2 C .1 Soolt ,rr.ccr raf Cs PS ►;,;4 -- -_ -0 • I 1 1 GENERAL NOTES: FLAG NOTES: 1 -1/4" 1 -1/4" CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTDIANCES M1 ACCORDANCE WTIH MANUFACTURER' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS. PROVIDE NEW PIPING AND MEDICAL GAS OUTLETS. OUAANTRY AND LOCATION ARE SHOWN ON ARCH. SHEET A7_ REFER TO THE APPROPRIATE' DETAIL FOR EACH ROOM. SEE COIL D1STAUATIOIN DUAL ON SHEET M4.1. SEE COOLR1G COIL CONDENSATE Dive DETAIL ON SHEET M4.1. i;. • A {! w 11U-42 I ' - ro:i F' 2iw i (TYP) T= ; 1 1u-41 102 MA N (I) SECOND FLOOR PLAN - PIPING Scale: 1/4" = 1' -0" o , 2 4 8 1091111111 1 I 7U-4o I I CI . • 3 . - . • ;. f CALL 3/ 4 "' 1 ; - 1 2-1 7 I 7U-37 11 PIPE RUNS UP WALL FROM WALKWAY TO ROOF. SEE SHEET M3.2 FOR CONTINUATION. 241 i f -J-3 1f • RECEIVED cnvOFTI w"::V , 3 C:.° PERMIT CENTER I MIES IMIJIM I SECOND FLOOR PLAN - PIPING REVISIONS I 4. 2201 SIXTH AWNUE SITE 1406 SEATTLE. WA 98 (206) 441 -4522 FAX (206) 441 -7917 No. 2 -06005 FR E DRAM CHECKED ` /ATE 7 -28-06 1 M 2.1 t • FD EG -1 70 fir N (0 SECOND FLOOR PLAN - HVAC Scale: 1/4' = 1' -0' 0 1 2 4 8 61 EG -1 I D i I11)-;37 I 24x18 1%4 OID I 191 GENERAL NOTES: tZNUT1III 11 rsq r i 14x10 VOLUME DAMPER (TYP) • DUCT STATIC PRESSURE SENSOR RG -1 RG -1 170 170 14x10 RG -1 ` RG -1 180 180 20x14 FD CD -1 165 Efl ELT ;70 CD -1 50 -., 39 ti1Tlagr. FD «--- EG -1 • -.70 ' 16x10 t.r =1r n :lot/ i �• 16x10 I .' FLAG NOTES: 22x14 RA ABOVE 24x18 SA BELOW CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURER' RECOMMENDATIONS. CONTRACT DOCUMENTS. AND APPLICABLE CODES AND REGULATIONS. DUCT SMOKE DETECTOR. FURNISHED AND POWERED BY DMSION 16, INSTALLED BY DMSION 15. SEE CEIUNG RADIATION FIRE DAMPER DETAIL ON SHEET M4.1. SEE COMBINATION Fl RE /SMOKE DAMPER DETAIL ON SHEET M4.1. SEE MR TERMINAL UNIT INSTALLATION DETAIL ON SHEET M4.1. COORDINATE DEMOLITION OF EXISTING WORK AND CONSTRUCTION OF NEW WORK IN ORDER TO MINIMIZE THE DURATION THAT BOTH THE SOILED UTILITY AND CLEAN UTILITY ROOMS ARE OFFUNE. COORDINATE CONSTRUCTION AND INFORM OWNER WHEN AND FOR HOW LONG THESE ROOMS WILL BE OFFUNE. r ^•1 L .- • • 4011.1-6 • 1 t RECEIVED CITvornimwILA AUG 1 92'06 PERMff GOITER SECOND FLOOR PLAN - HVAC • • • REVISIONS 0 ac 1 Ie� 2201 SIXTH AWN!lE 9 1E 1405 SEATTLE. WA 98121 (206) 441 -4522 FAX (206) 441 - 7917 P IAC NO. 2 -06005 DRAIN �� DATE 7 -28 -06 M 3.1 , 0 20/4 Striborse Amlierairat C. PS i • • I EF-2 1 I CHe—1 odi o on oC, � I I I P -1 I • CA • N OD PENTHOUSE PLAN - PIPING AND HVAC Scale: Mir 8' = 1' -0 0 2 4 8 16 PENTHOUSE • GENERAL NOTES: FLAG NOTES: CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURER' RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS. DUCTWORK SHOW IS DIAGRAMATICAL ONLY AND DOES NOT INCLUDE ALL DUCTWORK EXISTING IN THE PENTHOUSE. INCREASE MOTOR SIZE FROM 1 - 1/2 HP TO 2 HP. INSTALL PIPE 12' ABOVE ROOF DECK. DOWN TO AHU -1. SEE SHEET M2.1 FOR CONTINUATION CU try ' .� �•• .. . s. • 1\41 61- I 6 PENTOUSE PLAN - PIPING AND HVAC • am OFTIMILP AUG 1 8 2408 PERIATCENTEfs Ions tom 1 REVISIONS i 2201 9X1H AVENUE SMITE 1405 SEATTLE. WA 98121 (206) 441 -4522 FAX (206) 441 -7917 NAC NO. 2 -06005 FTLE DRAWN CHECKED DATE 7 -28 -06 M 3.2 C 24" .6cOmeraraf G PS • SP ABOVE DRAIN PAN, IN. WG H, INCHES X. INCHES Z, INCHES -1 2 1 5 -2 3 1.5 6.5 -3 _ 4 I 2 8 t STEEL DUCT ARE- RESISTIVE THERMAL BLANKET MATERIAL RADIATION DAMPER ASSEMBLY NOT TO SCALE RADIATION DAMPER ASSEMBLY INSTALLATION WITH STEEL DUCTWORK DIFFUSER OR GRILLE INSTALLATION WITH FLEXIBLE DUCT (DUCTLESS SIMILAR) CEILING RADIATION DAMPER INSTALLATION DETAIL • 1 0 (A) (E) (C) DUCT (D) (F) • NOTES: SUPPORT (TYP) STEEL DUCT CONNECTION FASTENERS RETAINING ANGLES, LAP OPENING 1" MINIMUM AND COVER CORNERS OF OPENING. CLEARANCE BETWEEN WALL AND SLEEVE BOTH DIMENSIONS. STEEL SLEEVE. APPROVED COMBINATION FIRE /SMOKE DAMPER. SECURE RETAINING ANGLES TO SLEEVE ONLY. SECURE DAMPER TO SLEEVE. CONNECT DUCT TO SLEEVE WITH BREAK -AWAY CONNECTION (TYP). ACCESS DOOR, SIZE TO MEET Al-11 REQUIREMENTS (6x6 MINIMUM). 1. COMPLY WITH SMACNA FSRDIG AND MANUFACTURER'S INSTRUCTIONS. 2. DAMPER FREE AREA SHALL BE MINIMUM 90% OF AREA OF CONNECTING DUCT. INCREASE DAMPER SIZE AND PROVIDE TRANSITIONS TO CONNECTING DUCTS AS NECESSARY TO MEET THIS REQUIREMENT. COMBINATION FIRE /SMOKE DAMPER INSTALLATION DETAIL NOT TO SCALE DIFFUSER OR GRILLE FLEXIBLE DUCT ARE- RESISTIVE THERMAL BLANKET MATERIAL CONICAL SPIN -IN FITTING WITH VD (TYP) ROUND BRANCH DUCT (TYP) EXTENDED PLENUM LOW PRESSURE FLEX DUCT (TYP) NOTES: 1. PROVIDE SHEET METAL ELBOWS TO RESULT IN STRAIGHT FLEX DUCT. AIR TERMINAL UNIT INSTALLATION DETAIL NOT TO SCALE EUMINATE BYPASS LEG AND BALANCING VALVE FOR TWO WAY CONTROL VALVE INSTALLATIONS NOT TO SCALE NOTE 1. (TYP) DIFFUSER (TYP) 30" MIN HEATING COIL MANUAL AIR VENT 30" MIN COIL FU LL LENGTH OF BOX OR 30 " MIN CLEAR ACCESSIBLE SPACE BY FULL HEIGHT OF BOX (TYP) CONTROLS STRAIGHT SHEET METAL DUCT AT BOX INLET, LENGTH =24" OR 3 DUCT DIAMETERS, WHICHEVER IS GREATER. SIZE TO MATCH TU INLET SIZE. FLEX DUCT IS ALLOWED PER GENERAL SHEET METAL NOTE #11. INSULATED DRAIN PAN (COOLING COILS ONLY) DRAIN PLUG DRAIN TRAP AND PIPING SEE DETAIL NOTE: ARRANGE PIPING TO BE CLEAR OF COIL REMOVAL SPACE. NOTE: 1. AHU -1 COIL PIPING SHALL BE CONFIGURED WITH THREE -WAY CONTROL VALVES. SINGLE WATER COIL INSTALLATION DETAIL (r REDUCER TO BOX INLET SIZE BRANCH DUCT SIZE 6" 7" 8" 9" 10" 12" NOT TO SCALE CONDENSATE DRAIN PAN AND PIPE OUTLET CONNECTION REMOVABLE CLEANOUT PLUG OR CAP (TYP) - 6" L OPEN VENT INVERT (OUTLET) -\ INVERT NOT TO SCALE "X" DIMENSION 13" 14" 15" 16 17" 19" i a L- TO DISPOSAL POINT WITH 1" AIR GAP (FLOOR DRAIN, SERVICE SINK, ETC, AS INDICATED) (B) GALVANIZED STEEL DIFFUSER OR GRILLE BOX. (C) SECURE TO DIFFUSER OR GRILLE NECK WITH SHEET METAL SCREWS, MIN. ONE PER SIDE OR EVERY 90 DEGREES; SEAL AIR TIGHT. AUTOMATIC AIR VENT l"" T� FLOOR G DRAIN -L DRAIN NOTE PROVIDE AT HIGH POINTS IN MECHANICAL ROOMS & WHERE INDICATED AUTOMATIC AIR VENT DETAIL SCALE: NONE REQUIRED IN ALL MECHANICAL ROOMS ONLY NOTES (A) CEILING DIFFUSER OR RETURN GRILLE (D) CEILING DIFFUSER (CD -1), RETURN AND EXHAUST GRILLE (RG- I , EG-1 ) CONNECTION DETAIL rr (E) SP. INCHES WG- L- EQUIPMENT INDIRECT DRAIN PIPING, SIZE PER CODE OR TO MATCH PAN CONNECTION SIZE (WHICHEVER iS LARGER) DIFFUSER BOX, SUPPORT TO STRUCTURE, 2 PER BOX. EQUALIZING GRID FULL WIDTH OF DIFFUSER NECK. PERFORATED 20 GA GALVANIZED STEEL WITH .156" HOLES ON 3/16" STAGGERED CENTERS (63% FREE AREA). TOP AT HORIZONTAL CENTERLINE OF BRANCH DUCT, BOTTOM AT 3" BELOW BOTTOM OF BRANCH DUCT. 1/2" HEM EDGE TOP AND BOTTOM 3/4" 90' BEND EACH END AND MINIMUM 3 SPOT WELDS, RIVETS OR SCREWS TO BOX. EQUALIZING GRID NOT REQUIRED FOR RETURN GRILLES. (F) BRANCH DUCT - INSULATED FLEX. (G) DUCT COLLAR SECURELY ATTACHED TO BOX. • • (H) DUCT SUPPORT TO STRUCTURE PER SMACNA HVACDCS AND AS SPECIFIED. (I) TYPICAL CEILING (TEE -BAR SUSPENDED CEIUNG SHOWN). (J) UGHT FIXTURE (AS APPLICABLE). NOTE CONDENSATE DRAIN PAN SHALL POSITIVELY SLOPE DOWN TO PIPE OUTLET CONNECTION TO RESULT IN FREE AND COMPLETE DRAINAGE. COOLING COIL CONDENSATE DRAIN TRA INSTALLATION DETAIL RECBVED CT�f OFTLIKWiLli AUG 13210» PERMITCENTEh DETAILS - PIPING AND HVAC REVISIONS 11 111 N ot 0 = 1< 1 no 51X*i AVENUE SUM 1405 SEATRE. WA 98121 (206) 441 -4522 FAX (206) 441 -7917 RAV HECK D DATE 7 -28 -06 M 4.1 s arc •erskta ■xo f. PS • SEQUENCE OF OPERATION: CHILLED WATER SYSTEM A. GENERAL 1. THE EXISTING CHILLED WATER SYSTEM CONSISTS OF ONE AIR- COOLED CHILLER CH -1, SERVED BY ONE CHILLED WATER PUMP P -1. CH -1 SERVES FOUR COOUNG COILS (CC -1 THRU CC -4) IN THE EXISTING MAKE -UP AIR UNITS THAT SERVE FAN -COIL UNITS THROUGHOUT THE BUILDING. 2. THE SYSTEM WILL BE EXTENDED TO SERVE CC -5 WHICH IS LOCATED IN AHU -1. 3. THE CHILLED WATER SYSTEM SYSTEM SHALL CONTINUE TO RUN UNDER THE EXISTING START /STOP PROCEDURE WHICH IS NON -DDC. SOUND ATTENUATOR t'44+4 :44$144 I SA -2 MEDICAL GAS RISER (E�AEO. A CM PANEL (E) SERVICE VALVES MUST BE LOCKED OPEN • • EA DAMPER I REF -1 I SRN/ EXMMJST FAN f AIR HANDLING SYSTEM (AHU -6) AIRFLOW AND CONTROL DIAGRAM SCALE: NONE (E) PRESSURE SENSORS MA I I I L � - (E) ZONE VALVES OA DAMPER 0 RA DAMPER L rzca CL (t l PATIENT ROOM I AIRFLOW MEASURING STATION Q J SCALE: COOLING COIL Lcc -tI SCALE NONE I PATIENT ROOM I PATIENT ROOM SUPPLY FAN AHU -1 FINAL FILTER I CC -2 I 3" - I PATIENT ROOM I PATIENT ROOM MEDICAL GAS PIPING DIAGRAM cc -fl SOUND ATTENUATOR SA -1 I PATIENT ROOM I • I PATIENT ROOM I I CC -4 I CHILLED WATER AND CONTROL DIAGRAM TERMINAL UNIT TU -X L ' . -..- • ICHIRL PANELI- DOC INTERFACE - T r I PATIENT ROOM I CC-5 1 (TYP) • SEQUENCE OF OPERATION: AHU -1 A. GENERAL 1. SYSTEM IS CONSTANT VOLUME WITH TERMINAL UNIT R 2. SYSTEM PROVIDES COOUNG, VENTILATION, AND SPACE 3. SUPPLY AND RETURN FAN MOTORS ARE CONTROLLED MONITORED THROUGH CURRENT SENSORS IN THE VFD 4. AN ALARM IS ENERGIZED UPON FAILURE OF ANY DEVI 5. FILTER PRESSURE DROP SETPOINTS ARE (PREFILTERS B. SYSTEM START /STOP: 1. PROGRAMMED SCHEDUUNG: AIR HANDUNG SYSTEM IS STARTED AND STOPPED BASED UPON PROGRAMMED OCCUPIED AND UNOCCUPIED TIMES, WITH WEEKDAY, WEEKEND AND HOUDAY SCHEDULES. INITIAL SCHEDULE CALLS FOR CONTINUOUS OPERATION. 2. DDC SYSTEM SHALL PROVIDE START /STOP AND SPEED CONTROL FOR EACH VFD. DDC SYSTEM SHALL MONITOR THE FOLLOWING INPUTS THROUGH EACH VFD: KW, HERTZ, PERCENTAGE OUTPUT, STATUS, AND FAULT ALARM. 3. INTERLOCKING IS PROGRAMMED AS FOLLOWS: a. RETURN /EXHAUST FAN IS INTERLOCKED WITH SUPPLY FAN OPERATION. 4. NORMAL SHUTDOWN: DAMPERS SHALL BE IN THE FOLLOWING POSITIONS WHEN UNIT IS OFF FOR ANY REASON: a. OUTDOOR AIR DAMPER: CLOSED. b. RETURN AIR DAMPER: OPEN. c. EXHAUST AIR DAMPER (AHU): CLOSED. d. CHILLED WATER VALVE: CLOSED. 5. SAFETY SHUTDOWN: a. FREEZE PROTECTION CONTROL A HARD -WIRED FREEZE PREVENTION THERMOSTAT SHUTS DOWN THE AIR HANDUNG UNIT AND CLOSES THE OUTDOOR AIR DAMPERS. b. HIGH LIMIT DUCT STATIC PRESSURE (HIPS): SHUT DOWN AHU SUPPLY AND RETURN /EXHAUST FANS IF SUPPLY DUCT STATIC PRESSURE EXCEEDS 3.5 IN. WG.; DDC AUTOMATIC RESET. AN ALARM IS ENERGIZED. PRESSURE SWITCH SHALL BE ADJUSTABLE PLUS /MINUS 1 IN. WG. c. LOW UMIT STATIC PRESSURE (CEPS): SHUT DOWN AHU SUPPLY AND RETURN /EXHAUST FANS IF RETURN AIR DUCT STATIC PRESSURE EXCEEDS 1.5 IN. WG. NEGATIVE STATIC PRESSURE; DDC AUTOMATIC RESET. AN ALARM IS ENERGIZED. SHUT DOWN AHU SUPPLY, RETURN /EXHAUST, AND EXHAUST FANS IF AHU STATIC PRESSURE UPSTREAM OF THE COIUNG COIL EXCEEDS 3.5 IN. WG. NEGATIVE STATIC PRESSURE; DDC AUTOMATIC RESET. AN ALARM IS ENERGIZED. PRESSURE SWITCH SHALL BE ADJUSTABLE PLUS /MINUS 1 IN. WG. d. FIRE ALARM: SUPPLY AND RETURN /EXHAUST FAN SHALL SHUT DOWN THROUGH THE FIRE ALARM SYSTEM UPON A SIGNAL FROM DUCT SMOKE DETECTORS. (REFER TO DIV. 16) C. AHU DISCHARGE AIR TEMPERATURE CONTROL: 1. ECONOMIZER DAMPERS AND CHILLED WATER CONTROL VALVE ARE CONTROLLED IN SEQUENCE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE (DAT) SETPOINT; INITIAL SETPOINT IS 56 F. THE DAT SHALL BE RESET BETWEEN 53F AND 59F AS DESCRIBED BELOW. 2. INCREASE DAT - THE DDC SYSTEM SHALL RUN A QUERY EVERY 10 MINUTES: IF THE DAT SETPOINT IS LESS THEN THE MAXIMUM DAT SETPOINT (59F), AND THE LOWEST TU HEATING VALVE OUTPUT IS GREATER THEN 10 PERCENT; THEN INCREASE THE DAT SETPOINT BY 1F. 3. DECREASE DAT - THE DDC SYSTEM SHALL RUN A QUERY EVERY 10 MINUTES: IF THE DAT SETPOINT IS GREATER THEN THE MINIMUM DAT SETPOINT (53F). AND THE LOWEST TU HEATING VALVE OUTPUT IS GREATER THEN 5 PERCENT; THEN DECREASE THE DAT SETPOINT BY 1F. 4. DURING COOLING. THE ECONOMIZER DAMPERS AND CHILLED WATER CONTROL VALVE ARE CONTROLLED IN SEQUENCE TO MEET THE COOLING REQUIREMENT. 5. ENABLE THE ECONOMIZER WHEN THE OUTSIDE AIR TEMPERATURE IS LESS THEN OR EQUAL TO THE RETURN AIR TEMPERATURE MINUS 2F. DISABLE THE ECONOMIZER WHEN THE OUTSIDE AIR TEMPERATURE IS GREATER THEN OR EQUAL TO THE RETURN AIR TEMPERATURE PLUS 2F. 6. A LOW UMIT CONTROL OVERRIDES ECONOMIZER CYCLE CONTROL TO PREVENT THE DAT FROM DECREASING BELOW 50 F. EH EAT. PRESSURIZATION. BY VARIABLE FREQUENCY DRIVES (VFDS). FAN STATUS IS S. CE. 0.9" WC. FINAL FILTERS 1.4" WC). D. MINIMUM OUTDOOR AIR: FLOW IS MEASURED VIA THE AIRFLOW MEASURING STATION, AND MAINTAINED AT A CONSTANT VALUE BY MODULATION OF THE OUTDOOR AIR DAMPER. MINIMUM OUTDOOR AIRFLOW: 1600 CFA. E. FAN SPEED CONTROL: THE SUPPLY FAN SPEED SHALL BE CONTROLLED BY THE VFD TO MAINTAIN DUCT STATIC PRESSURE SETPOINT, INITIALLY 1 IN. WG. THE RETURN FAN SPEED SHALL BE CONTROLLED BY THE VFD TO MAINTAIN A CONSTANT AIRFLOW DIFFERENTIAL WITH THE SUPPLY FAN. 1. REF -1 DIFFERENTIAL: -1,600 CFM F. ZONE TEMPERATURE CONTROL: 1. ZONE TEMPERATURE SETPOINTS SHALL BE 75F FOR HEATING AND COOLING. 2. THE MR TERMINAL UNIT PRIMARY AIR DAMPER REMAINS SHUT UNTIL THE AHU IS STARTED. 3. WHEN ZONE TEMPERATURE DROPS BELOW SETPOINT, THE HEATING CONTROL VALVE MODULATES TO MAINTAIN SETPOINT. 4. THE HEATING WATER PUMP SHALL START AS REQUIRED WHEN ANY TU CONTROL VALVE OPENS AND CALLS FOR HEAT. CONTROLS LEGEND MS ® VARIABLE FREQUENCY DRIVE FLAG NOTES: MOTOR STARTER WD ALARM AIRFLOW MEASURING STATION CURRENT SENSOR O FFERENTNL PRESSURE SWITCH DUCT SMOKE DETECTOR GENERAL NOTES: e FOGH MIT PRESSURE SWITCH WD HERTZ FIER Z VFD KILOWATTS ® LOW MIT PRESSURE SWITCH MOTOR OPERATED DAMPER WD SPEED CONTROL STATIC PRESSURE SENSOR CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL PIPING TRANSRIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS. PROVIDE AN AIR VENT AT THE HIGH POINTS OF ALL HYDRONIC SYSTEMS. ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END DRAIN VALVES AT THE BOTTOM OF ALL RISERS AND AT LOW POIMS. PRCNIDE NEW PPM AND MEDICAL GAS OUTLET'S. QUANTITY AND LOCATION ARE SHOWN ON ARCH. SHEET Al. RE TO THE APPROPRIATE DETAIL FOR EACH ROOM. 1\4 o tf. t • START /STOP TEMPERATURE CONTROL VALVE TEMPERATURE 'TRANSMITTER VFD PERCENTAGE C 5 s RECEIVED CITYOFTIRCWILis AUG 182G06 PERMITCENTEft CONTROL ofAGRAMS REVISIONS (I1 w W Z ~ Oo U i g Q J0 0 � � � Z U W 0 ` Q J J / 6 W 2 Cr N 2201 SIXTH AVENUE SUITE 1405 SEATTLE. WA 98 (206) FAX (206) 441 77917 lit g ; si i di N 0 o ( ti*c No 2 -06005 111.E DRAWN CHECKED 0ATE 7 -28 -06 C'++K 13.-Aw v.GcaresrafC. PS • • go 2 WEST (EAST HALF). 3 WEST AND 4 WEST FANCOIL UNITS - - • - GNti.s ! BLEND PUMP t 1ST FLOOR LAB. RADIOLOGY, AND OPERATING ROOM rx - DELIVERY. LABOR NURSERY -F^ BLEND PUMP HWR TEMP CONTROL SCOIE: NNE - -- HIS BLEED VALVE 5 I BLEND PUMP , f . E: - -E I.• I BLEND PUMP HWR TEMP CONTROL HEATING WATER PUMP (E) IP -2I NAMPLATE DATA: GPM: 35 GPM HEAD: 35 FT 2 WEST (EAST HALF). 3 WEST AND 4 WEST FANCOIL UNITS 1ST FLOOR LAB, RADIOLOGY, AND OPERATING ROOM - - —I —1 --1 DELIVERY, LABOR NURSERY tusS HwP) _ — [X1 ----'I 141 R)— —1>< r : — A L L TERMINAL BOX COILS (iYP) f_ TCV HAS r — Y.— ,r • HEATING WATER PUMP (E) HWP -2 NAMPLATE DATA: GPM: 410 GPM HEAD: 32 FT HEATING WATER PUMP (E) [HWP -1 NAMPLATE DATA GPM: 410 GPM HEAD: 32 FT HEATING WATER PUMP (E), VARIABLE GPM: 250 GPM —So— BYPASS HEATING WATER AND CONTROL DIAGRAM ALL TERMINAL BOX COILS OW) SEQUENCE OF OPERATION: HEATING WATER SYSTEM A. GENERAL 1. THE EXISTING HEATING WATER SYSTEM CONSISTS OF HEATING WATER PUMPS AND 2 BOILERS. 2. NEW PIPING WILL BE ADDED TO 2 WEST EAST WING AND CONNECTED TO EXISTING PIPING SERVING THE REMAINDER OF 2 WEST AND 2 NORTH. 3. NEW AIR TERMINAL UNITS SHALL BE INTEGRATED INTO THE EXISTING DDC CONTROL STRATEGY. B. SYSTEM START /STOP: PROGRAMMED SCHEDUUNG: ALL EQUIPMENT SHALL CONTINUE TO RUN BASED UPON EXISTING PROGRAMMED SCHEDULE. • GENERAL NOTES: CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL ARRANGEMENT ONLY. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS' CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL PIPING TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS. PROVIDE AN AIR VENT AT THE HIGH POINTS OF All HYDRONIC SYSTEMS. ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END DRAIN VALVES AT THE BOTTOM OF ALL RISERS AND AT LOW POINTS. r .. 171• - .. tvt o • • AIX "H 8 not Iems Wutaw I CONTROL DIAGRAMS REVISIONS • i E 4, U) 0 U a ' 0 Q W U) W gi te l U —J V < 0 to Z U O ' J V 1 w N 2201 91X1$ MIME 91101E 1405 SEAT1tE. WA 98121 (206) 441 -4522 FAX (206) 441 -7917 NAC No. 2 -06005 FILE DRAWN cHEaOD DATE 7 -28 -06 5M2 1 C YelE.Volimar.45waseobrarCa PS' •