HomeMy WebLinkAboutPermit M06-184 - HIGHLINE MEDICAL CENTERHIGHLINE MEDICAL
CENTER
12844 MILITARY RD S
M06 -184
CITY OF TUKW lA
DEPT 07 CC7.7.;U ..TY C:-",
6C, ' f. J; : n . "
TUKWiiA,
Parcel No.: 1623049001
Address: 12844 MILITARY RD S TUKW
Suite No:
Tenant:
Name: HIGHLINE MEDICAL CENTER
Address: 12844 MILITARY RD S, TUKW ILA WA
Contact Person:
Name: DIANNE MUNROE
Address' 16251 SYLVESTER RD SW, BURIEN WA
Value of Mechanical: 110,000.00
Furnace: <100K BTU
>100K BTU
Floor Furnace
Suspended/Wall /Floor Mounted Heater
Appliance Vent
Repair or Addition to Heat/Refrig /Cooling System....
Air Handling Unit <10,000 CFM
>10,000 CFM
Evaporator Cooler
Ventilation Fan connected to single duc
Ventilation System
Hood and Duct
Incinerator: Domestic
Commercial /Industrial
doc: !MC-Permit
MECHANICAL PERMIT
Owner:
Name: HCH SPECIALTY CENTER
Address: ATTN ACCOUNTING DEPT, 12844 MILITARY RD S
Contractor:
Name: PSF MECHANICAL, INC.
Address: 9322 14TH AVENUE SOUTH, SEATTLE, WA
Contractor License No: PSFMEI *090NZ
DESCRIPTION OF WORK:
PROVIDE NEW AIR HANDLING UNIT TO SERVE (9) PATIENT ROOMS ON 2ND FLOOR. PROVIDE
(12) AIR TERMINAL BOXES WITH HOT WATER HEATIN COILS FOR EACH ZONE. CONNECT TO
EXISTING HEATING AND CHILLED WATER SYSTEMS. PROVIDE EXTENSION OF EXISTIN DDC
CONROL SYSTEM.
NOTE: AIR TERMINAL BOXES REPLACE (14) EXISTING FAN COIL UNITS SERVED BY AND
EXISTING AIR HANDLING UNIT. EXITING GAS BOILERS ARE HEATING SOURCE.
Type of Fire Protection: International Mechanical Code Edition: 2003
EQUIPMENT TYPE AND QUANTITY
0
0
0
0
0
0
1
0
0
0
0
0
0
0
Permit Number:
Issue Date:
Permit Expires On:
''ERMIT CENT
Phone:
Phone: 206 431 -5343
Phone: 206 764 -9663
Expiration Date:10 /03/2007
M06 -184
09/25/2006
03/24/2007
Fees Collected: $1,087.88
Boiler Compressor:
0 -3 HP /100,000 BTU 0
3 -15 HP /500,000 BTU 0
15 -30 HP /1,000,000 BTU
30 -50 HP/1,750,000 BTU
50+ HP/1,750,000 BTU 0
Fire Damper 46
Diffuser 42
Thermostat 12
Wood /Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment
M06 -184 Printed: 09 -25 -2006
CITY OF TUKWI A
DEPT. OF CO`.C'.:U ?: iY DCV:1C'I1.1-NT`„ '
6300 CLUTI-i.::.N'iLRCLVO.
TUKWILA, WA 93188
doc: IMC- Permit
"continued on next page **
M06 -184
QERMIT CENTE T
Printed: 09 -25 -2006
CITY r^ r r ■•••■
DEPT OF
6303 ;I, .; ✓D.
TUFO, ILA, WA 9d188
ordinances governing this work will
Print Name:
doc: IMC- Permit
■' PERMIT CENTEr'
Permit Number: M06 -184
Issue Date: 09/25/2006
Permit Expires On: 03/24/2007
Permit Center Authorized Signature Att—ik Q Date: al I ? /ao
I hereby certify that I have read and ex mired t is permit and know the same to be true and correct. All provisions of law and
with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws
regulating construction or the performance of work. I am authorized to sign and obtain this mechanical permit.
Signature: Nl !� Date: glo
VVVV r M f <Orl, ark-f
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is
suspended or abandoned for a period of 180 days from the last inspection.
M06 -184 Printed: 09 -25 -2006
CITY OF TUKWIL.A
DEPT. OF CO^;% :UNITY OEV,'LOPMiNT
6300 lOTN! !T r'!VD
TUKbiitA, V:% •
1: ***BUILDING DEPARTMENT CONDITIONS***
PERMIT CENTEr.
PERMIT CONDITIONS
Parcel No.: 1623049001 Permit Number: M06 -184
Address: 12844 MILITARY RD S TUKW Status: ISSUED
Suite No: Applied Date: 08/18/2006
Tenant: HIGHLINE MEDICAL CENTER Issue Date: 09/25/2006
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
4: Readily accessible access to roof mounted equipment is required.
5: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
6: Manufacturers installation instructions shall be available on the job site at the time of inspection.
7: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the Cityof Tukwila
Permit Center.
8: All electrical work shall be inspected and approved under a separate permit issued by the Washington State Department
of Labor and Industries (206/248- 6630).
9: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
10: ***FIRE DEPARTMENT CONDITIONS * **
11: H.V.A.C. units rated at greater than 2,000 cfm require auto-shutdown devices These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
12: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air - moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's Installation Instructions. (IMC 606.1, 606.2.1)
13: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
14: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
15: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
doc: Conditions
M06 -184 Printed: 09-25 -2006
CITY OF TUKWI A
DEPT OF CO? ,? ;UNITY DEV LO^f!`I'IT
6300 SCJUTh i gR1B
TUKWILA NIA
PERMIT CENTER'
16: An electrical permit from the Washington State Department of Labor and Industries is required for this project.
17: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
18: Any overlooked hazardous condition and /or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
19: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: Conditions
**continued on next page**
M06 -184 Printed: 09-25-2006
CITY OF TUIMIlA
DEPT. OF CC ?2 R f ^ • • 1T >ad
63c0
TUKWILA, WA 98188
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws
regulating construction or the performance of work.
Signature:
Print Name:
doc: Conditions
kjia Nt fr vwkf
`PERMIT CENTER
Date: T( /o
M06 -184 Printed: 09 -25 -2006
E -Mail Address.
CITY OF TUKWILiL
Community DevelopmelleDepartment
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http: /Avww.ci.tukwila. we.us
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
"Please Print**
Site Address: raY44 VIILATM
Tenant Name: �Ifa.4eL +b ITLSl
Property Owners Name - 4A1441 A 1 4F. 1111 -1 1r ttat
Mailing Address I24 Tll I.tTAar f F-0 C,
Name: pit ltlprr -
Mailing Address: 1 ln1Ca1 C ") - 0 AIPSTU _. g0 S.%)
•%. -tat t aq.I
Company Name ALT Cao- 15-112- t1CCTiCt4
Contact Person:Dhal S4-4442-11.1.61
E - Mail Address: Thal r% . ex i t.. '. en-,
Contractor Registration Number: 4I:17. ml tl'col?u11
Cxxr7'ECT¢ : RTjC 1 • t ,All piansmust -be wet namp
Mailing Address 4€S ST. ri .
Contact Person: t-1 Y'1 Mit
E -Mail Address: - th•-IC ( 1 i-IC ,. Cor
Q:Upplicetiomforme- Applications On IineV -2006 - Permit Appliationdac
Revised: 42006
bh
King Co Assessor's Tax No.: I tot- Est - CIC I
Suite Number: Floor: Z
New Tenant: ❑ Yes of ..No
/
ern rail LA.
City
tk
State
511,9n
Zip
Day Telephone: id ,, - 424. S 34b
1 17 1bTl (NIA ce131I.11 n
City State Zip
Fax Number: 2C(o • 2-4(..0 < e
Mailing Address I S L A t t e ¶ - lt 'l(.IK TA astir.
City
lac) 1 tan( 1k16s °IBS
State Zip
Day Telephone: 42S .401. 11
Fax Number: 425 - 4(61 - I %LYL
Expiration Date: C l /30 /CIp
Company Name: FLcRZl1lie5—T moat" tz..a C-01 - t ,644
Mailing Address Z ZOI (aiM Ciirra Sew--n F. + 9` -12
( City State Zip
Contact Person: aJ151✓ ` Day Telephone: totes. 44%. 41SZZ
E -Mail Address: Fax Number: #+. 441 , 1
GTNEER QE RECORD -,Mi plans must be jvet stamped Engineer of
Company Name: 6-1/A rx. C. + St i rn4 42 .117.4. crLIMAI . airi1 k tC 7-C---,
-, 5 c t itet% b11t C IF I C l
City State ZIP
Day Telephone: '1 425. 3(4Pt .. IOI 1
4
Fax Number: 42-s. 2 . \ IS1
Page 1 of 6
Valuation of Project (contractor's bid price): $ ,r c oo
Scope of Work (please provide detailed information):
Q:IAppacatio,a\Fonnr- Applications On Lina3- 2006 - Permit Application. dx
Revised: 9-2006
be
Existing Building Valuation: $ -'
— 1\ •
alb — _. . Sr- �a- _It
•
r alea • _ II • - — ►•tar- ••] •'L3 ate ta I►
�Jlar
Will there be new rack storage? ❑ .. Yes (If yes, a separate permit and plan submittal will be required)
- II Raclin
Isite`13e
ico
1 —Z
PLANNING DIVISION:
Single- family building footprint (area of the foundation of all structures, phis any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area for accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑....Yes ❑..No If `yes ", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
d . Sprinklers ❑..Automatic Fire Alarm ❑..None ❑..Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑.. Yes 0.. No
If"yes", attach list of materials and storage locations on a separate 8 -1/2 x 11 paper indicating quantities and Material Safety Data Sheets.
SEPTIC SYSTEM:
❑ On -site Septic System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
Page 2 of 6
•
Scope of Work (please provide detailed information):
Water District
❑...Tukwila ❑...Water District #125
❑ ...Water Availability Provided
$ewer District
❑ ...Tukwila
❑ ...Sewer Use Certificate
Please refer to Public Works Bulletin #1 for fees and estimate sheet.
❑ ...Total Cut cubic yards
❑ ...Total Fill cubic yards
❑... ValVue
0... Sewer Availability Provided
Submitted with Application (mark boxes which apply):
❑ ...Civil Plans (Maximum Paper Size — 22" x 34 ")
❑ ...Technical Information Report (Storm Drainage)
❑ ...Bond ❑ .. Insurance ❑ .. Easement(s)
DI oposed Activities (mark boxes that apply):
...Right -of -way Use - Nonprofit for less than 72 hours
❑ ...Rightof -way Use - No Disturbance
❑ ...Const ruction /Excavation/Fill - Right-of-way
Non Right-of-way
❑...Sanitary Side Sewer
❑...Cap or Remove Utilities
❑...Frontage Improvements
❑ ...Traffic Control
❑ ...Backflow Prevention - Fire Protection
Irrigation
Domestic Water
❑...Permanent Water Meter Size..
❑ ...Temporary Water Meter Size .
❑ ...Water Only Meter Size
❑ ...Sewer Main Extension Public _ Private
❑...Water Main Extension Public _ Private
QMppNndoMrmme- Applications On Lin&3 -2006 - Permit Application.dac
Revised: 42006
bti
❑ .. Abandon Septic Tank
❑ .. Curb Cut
❑ .. Pavement Cut
❑ .. Looped Fire Line
Call before you Dig: 1 800 - 424 - 5555
❑ .. Highline
❑ .. Renton ❑.. Seattle
❑ .. Approved Septic Plans Provided
❑ .. Geotechnical Report
❑ .. Maintenance Agreement(s)
❑ ..
Right-of-way Use - Profit for less than 72 hours
❑ .. Right-of-way Use — Potential Disturbance
❑ .. Work in Flood Zone
❑ .. Storm Drainage
❑ .. Renton
❑ .. Grease Interceptor
❑ .. Channelization
❑ .. Trench Excavation
❑ .. Utility Undergrounding
❑ ...Deduct Water Meter Size
❑ ...Traffic Impact Analysis
❑ ... Hold Harmless — (SAO)
❑ ...Hold Harmless— (ROW)
FINANCE INFORMATION
Fire Line Size at Property Line
❑...Water
Number of Public Fire Hydrant(s)
❑ ...Sewer ❑ ...Sewage Treatment
Monthly Service Billing tn-
Name: Day Telephone:
Mailing Address:
Cory State Zip
Water Meter Refund/Billing:
Name: Day Telephone:
Mailing Address:
City
State
Zip
Page 3 of 6
.. 2 2. :.
'Unit Type: _ .
:_ > : - :;_> :
., ..
.1?4Y'`
safiiiEType .. ... , ..:
,Qty :::
tiiit ...
wtTypei
...
Qty::
Botlec /Compresso'r-.
0-3 HP /100,000 BTU
>Qti� ::
Furnace<100K. BTU
Air Handling Unit >10,000
CFM
Fire Damper
Fumace>100KBTU
Evaporator Cooler
Diffuser
3 -15 HP /500,000 BTU
Floor Furnace
Ventilation Fan Connected
to Single Duct
Thermostat
15 -30 HP /1,000,000 BTU
_
Suspended/Wall/Floor
Mounted Heater
Ventilation System
Wood/Gas Stove
30-50 HP /1,750,000 BTU
Appliance Vent
Hood and Duct
Water Heater
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Re1 ig/Cooling
System
Incinerator - Domestic
Emergency
Generator
Air Handling Unit
<10,000CFM
r
Incinerator— Comm /Ind
Other Mechanical
Equipment
ht FR TES-r' tt -- L 2
$O sett {
MECHANICAL CONTRACTOR INFORMATION
Company Name. Ps P N E-Ctiea. ces. L.
Mailing Address: 22- 14I'rr}4- Avis S
Contact Person: r Ile-e. Cb,.totl�W
E -Mail Address: t1pOt.4C i{t~INe P'1&4+ . f._or1
Contractor Registration Number: r 1 f * CP10 N
ih1C
Indicate type of mechanical work being installed and the quantity below:
Q: AppGcithon none,- Appliceaom Oa Liee3-2096. remit Atpam!ionme
aevim3 #2096
City
Day Telephone:
Fax Number:
Expiration Date:
.S IlljA °� 131o$
State yip
?rf n.1t4.9OI.Ob
Zoto. 1 Cot - S351
I of3 /oc.o
Valuation of Project (contractor's bid price): $ 1 t O , 7.00Th
Scope of Work (please provide detailed information): r1 b C. p.•2'0 P i Pa- t17"1" -
tO sER."e tair'E rt. 1PGnrt-sO)' rs -ov)b t' Alit.
- rcP r'► ►t --lit - Gbr. vir t+OT 4 ✓r.TEP' Ft e-7,-r) rG Cot 1.-S Fo P- Se 1/404 toNt .
col-,at.c r To r - G - 1/4, 0- 141.+L>_ y ' ram- c rEMp
P1zo.. t.b a Ese-TErs to +-e OF C,-' c t`- G tt C
sei Residential: New.... ❑ Replacement .... ❑
Commercial: New .... Replacement .... ❑
Fuel Tvue: Electric .....0 Gas....( Other:
NOTC r> te)a- -1;PT's s.. BOX ac ►zEAt -r. 1 4- e - cr► r'G
�►- ' col ., its sC- van t ( ,>✓a
P%tF_tomr'bt -t t-JG 'P- IT,
��c)STtYG t5- .c go'LElar htz� i�Bs^•Ttr�soifl.C++ .
Page 4 of 6
...
Fixture Type::. ,.:
-QtY
Fixture Type: :. ::: �; :
; .. ;:
ture:T,ype:
ty..:
re Type:
Qty '
Bathtub or combination
bath/shower
Drinking fountain or water
cooler (per head)
Wash fountain
Gas piping outlets
Bidet
Food -waste grinder,
commercial
Receptor, indirect
waste
Clothes washer, domestic
Floor drain
Sinks
Dental unit, cuspidor
Shower, single head trap
Urinals
Dishwasher, domestic,
with independent drain
Lavatory
Water Closet
Building sewer or trailer
park sewer
Rain water system — per
drain (inside building)
Water heater and/or
vent
Industrial waste
pretreatment interceptor,
including its trap and vent,
except for kitchen type
grease interceptors
Repair or alteration of water
piping and/or water treating
equipment
Repair or alteration
of drainage or vent
piping
Medical gas piping system
serving one to five
inlets/outlets for specific
gas
Additional medical gas
inlets/outlets —six or more
36
allar
PLUMBING AND GAS PPING CONTRACTOR INFORMATION
Company Name: fl F He.ctr .t'-'L C.Pct-
Mailing Address: q 3?•?- LkriA iSte. S ytestl .8
City
Contact Person: f"f uce ')tx.1 otke»J
Contractor Registration Nurnber. P '1Eo9ot4t
Q Appiic.uor.worres- Applicati.n. Oa L100-2006- ?melt AppIiuiiondoe
Revise& 4-2006
bb
Indicate type of plumbing fixtures and/or gas piping outlets being installed and the quantity below:
° 18ib8 - SI oZ
stale zip
Day Telephone: Zclo. 1I.04 . gCoto3
E -Mail Address: tient-lob e t'1a-44 Lot-I Fax Number. Zoo. 1ic2. E'r32:51
Expiration Date: a,
C / 3 /O(,
Valuation of Project (contractor's bid price): $ 4o, r tCr . oO
Scope of Work (please provide detailed information): nzo ` t C E 3G I. bb t'T 16 i '" t_ P —1 E h t Lr4 t_
(fp ov 'R-eT ) 1-0 t%4 i-•t t-C Ye% n l-r r Hoot -Lr Fizo t`7 T r4E
S`CcT E t--t -e C 19 ) j at "%I R I t o. c'tG-e P r g ..,a. eL
Page 5 of 6
Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review - Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
Buildinf and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
Plumbing Permit
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
Print Name: I artAtc G
I Date Application Accepted:
D AGENT:
g b/.y.-0 0 4' e- t And
Mailing Address: 21c:I (cnf4 Age, .tttte
•
tB ta1
Q:\ApplicationsWorms- Applianions On Liae'3 -2006 -Permit Appliwlondoc
Revised: 4-2006
an
r
Date: P) .IS • oCO
Day Telephone: 7,t n . 44 t 42Z
Scion -, V IAT Tit Z.1
City State Zip
Date Application Expires: �$ l
Staff Initials:
Page 6 of 6
City of Tukwila
6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
Parcel No.: 1623049001 Permit Number: M06 -184
Address: 12844 MILITARY RD S TUKW Status: APPROVED
Suite No: Applied Date: 08/18/2006
Applicant: HIGHLINE MEDICAL CENTER Issue Date:
Receipt No.: R06 -01498 Payment Amount: 876.30
Initials: JEM Payment Date: 09/25/2006 10:17 AM
User ID: 1165 Balance: 50.00
Payee: HIGHLINE MEDICAL CENTER
TRANSACTION LIST:
Type Method Description
Amount
doe: Receipt
Payment Check 326205 876.30
ACCOUNT ITEM LIST:
Description
Current Pints
MECHANICAL - NONRES
RECEIPT
Account Code
000/322.100 876.30
Total: 876.30
0096 09/25 9716 TOTAL 3654.78
Printed: 09 -25 -2006
RECEIPT NO: RO6 -01298
Initials: JEM
User ID: 1165
Payee: HIGHLINE MEDICAL CENTER
SET TRANSACTIONS:
Set Member Amount
006 -323
M06 -184
TOTAL:
iC i ty of Tukw Steven M. 1•tmavor
Department of Community Development Steve Lancaster. Director
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
SET ID: S000000542 SET NAME: Tmp set/Initialized Activities
1,835.26
211.58
2,046.84
TRANSACTION LIST:
Type Method Description
Payment Check 324485
ACCOUNT ITEM LIST:
Description
BUILDING - NONRES
PLAN CHECK - NONRES
SET RECEIPT
TOTAL:
Payment Date: 08/18/2006
Total Payment: 2,046.84
Amount
2,046.84
2,046.84
Account Code Current Pmts
000/322.100 19.50
000/345.830 2,027.34
TOTAL: 2,046.84
8784 08/18 9710 TOTAL 2046.84
Project:
Project: L , � 4 7 r Altar
T pti NJ
' e of Inspection: 2 1797d1/Q$..4
/ F d:
Address:
/7/ 4 /��y
Date ailed:
'� If
Special Instructio s:
/
Date Wanted:.
a.m.
Requester.
Phone No:
IN3RELYION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
OMMENTS:
Inspector:
INSPECTION RECORD
Retain a copy with permit
/7r" /} /)-( S 4 r 97
ft
(206)431
I y l Approved per applicable codes. O Corrections required prior to approval.
Alf Ariz #t
40 doe
11/47s
7 - 5 - a224 , ____
Date / rN
❑ $58.00 REINSPECTION E REQUIkED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to sechedute reinspection.
Receipt No.: 'Date:
Project:
Type o Inspection: "," #'T
'II
Address I
l egW9 til.'J. 29
ate Called:
i
Special Instructions:
—e.
Date Wanted:
//
�
Request
Phone No:
r
2,
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISIO G� .
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (20k)431 -3
MENTS:
A pproved per applicable codes 11 Corrections required prior to approval.
ri $58.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to sechedule reinspection.
Receipt No.:
!Date:
Project: /
r % A / • � ' /�/J A
Type eooffIInspection: /
-a7 42077
Address:
JlI 1 1 it r, 1 ..
A C 8
Dat all d:
Special Instructions:
Date Wanted: a.m. _
C�?J'T
Requester:
Phone No:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
(206)431 -$ 6
0 Approved per applicable codes. El Corrections required prior to approval.
COMMENTS:
I t !7'llji /A
/
wok � � , - c g %.I
/ n�� et
n s� r iv 0104 . 5_37
7 -43 7 rn-
ri $58.0 INSPECTION FE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to sechedule reinspection.
Receipt No.:
!Date:
IIIMIssatirtorsoliassiraiailo
ACTIVITY NUMBER: M06 -184 DATE: 08 -18 -06
PROJECT NAME: HIGHLINE MEDICAL CENTER
SITE ADDRESS: 12844 MILITARY RD S
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter # Revision # After Permit Issued
DEPARTMENTS:
Bui dl Di"vi"sion
Public Works
DETERMINATIQN OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Approved ❑
Notation:
Documents/routing sIip.doc
2 -28-02
REVIEWER'S INITIALS:
pod PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
APPROVALS OR CORRECTIONS:
u MC' D
Fire Prevention
Structural
Incomplete ❑
❑ Permit Coordinator ❑
TUES/THURS ROU ING:
Please Route Structural Review Required
REVIEWER'S INITIALS:
Approved with Conditions
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
DUE DATE: 08-22 -06
Not Applicable ❑
No further Review Required
DATE:
DUE DATE: 09-19-06
Not Approved (attach comments) ❑
DATE:
Planning Division
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
License Information
License
PSFMEI *090NZ
Licensee Name
P S F MECHANICAL INC
Licensee Type
CONSTRUCTION CONTRACTOR
UBI
601318369
Ind. Ins. Account Id
Business Type
CORPORATION
Address 1
9322 14TH AVE S
Address 2
City
SEATTLE
County
KING
State
WA
Zip
98108
Phone
2067649663
Status
ACTIVE
Specialty 1
SHEET METAL
Specialty 2
AIR HEAT,VENTILATION,EVAPORAT
Effective Date
8/9/1991
Expiration Date
10/3/2007
Suspend Date
Separation Date
Parent Company
Previous License
EDENN * *225LK
Next License
Associated License
Business Owner Information
Name
Role
Effective Date
Expiration Date
BEARDSLEY, WARREN S
01/01/1980
CRITCHLOW, JAMES D
01/01/1980
Look Up a Contractor, Electrician or Plumber License Detail Page 1 of 2
Now
Washington State Department of Labor and Industries
General/Specialty Contractor
A business registered as a construction contractor with L &I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
FEDERAL
Bond Information
Bond
# 2
Bond
Company
Name
FEDERAL
INS Co
Bond
Account
Number
81241859
Effective
Date
08/08/2001
Expiration
Date
Until
Cancelled
Cancel
Date
Impaired
Date
Bond
Amount
$6,000.00
Received
Date
10/01/2001
https: // fortress. wa. gov /lni/bbip /printer.aspx ?License= PSFMEI *090NZ 09/25/2006
- e 44.:V' =rG 747.10 as Q AI v.�s
2W HVAC UPGRADES
HIGHLINE COMMUNITY HOSPITAL, SPECIALTY CENTER
OWNER
CONTACT: DIANE MUNROE
ARCHITECT
CONTACT: RICHARD SALOGGA.
STRUCTURAL
CONTACT: JOHN SMITH, P.E., S.E.
MECHANICAL
CONTACT: RON EUASON. P.E.
ELECTRICAL
CONTACT: BRYAN BOEHOLT, P.E.
PROJECT INFORMATION
JOB SITE ADDRESS:
OWNER:
CONTACT:
TAX PARCEL NUMBER:
PROPERTY CLASSIFICATION:
PROJECT CLASSIFICATION:
PERMITTING AUTHORITY:
BUILDING INFORMATION
BUILDING CODE:
OCCUPANCY TYPE:
CONSTRUCTION TYPE:
WEST WANG
AREA SEPARATION:
OCCUPANCY SEPARATION:
SMOKE COMPARTMENTATION:
WEST WANG
ARCHITECTURAL SYMBOLS
e--
L. •
149E
R1498
ROOM NAME
101
0
1
4
MA
12844 MIUTARY ROAD SOUTH
TUKIMLA. WA
HIGHUNE COMMUNITY HOSPITAL
16251 SYVESTER ROAD S.W.
BURIEN, WASHINGTON 98166
NORTHWEST ARCHITECTURAL COMPANY
2201 SIXTH AVE, SUITE 1405
SEATTLE. WASHINGTON 98121
162- 304 -9001
RM -900 14/ RS -7200 SINGLE FAMILY
PERMITTED USE - HOSPITAL
CITY OF TUKWALA
KING COUNTY, WASHINGTON
WASHINGTON STATE BUILDING CODE
(1994 UNIFORM BUILDING CODE AS AMMENDED)
1 -2
TYPE II - ONE HOUR. FIRE SPRINKLERED
WEST WING TO NORTH YANG - TWO HOUR
NO MIXED OCCUPANCY THIS PROJECT
EXISTING. NO CHANGE
GRID UNE
REVISION
REGIONAL HOSPITAL
12844 MIUTARY ROAD SW., TUKW ILA, WA 98168
NORTHWEST ARCHITECTURAL COMPANY, P.S.
2201 SIXTH AVENUE, SEATTLE. WA 98121 (206) 441 -4522
COLLONS & SMITH STRUCTURAL ENGINEERS
485 FRONT STREET NORTH, SUITE F -3. ISSAQUAH, WA 98027 (425) 369 -1101
HARGIS ENGINEERS, INC
600 STEWART STREET, SUITE 1000. SEATTLE. WA 98101 (206) 448 -3376
BrN ENGINEERING, INC
2101 9111 AVE, SUITE 202. SEATTLE. WA 98121 (206) 223 -6446
DOOR IDENTIFICATION
REUTE IDENTIFICATION
MATCH UNE
Shaded area is side considered
WORK POINT. DATUM POINT.
CONTROL POINT
DETAIL
Upper mark denotes drawing number
Lower mark denotes sheet
A 'dash' in the sheet reference location
indicates that the detail occurs on the
some sheet that R is flogged
PARTIAL BUILDING SECTION
INTERIOR ELEVATION
Elevation number denoted in arrow
Sheet number denoted in box
ROW IDENTFICATION
COOED NOTE
WALL TYPE
DASHED LINE
Used to denote items hidden, overheod,
not in contract (lac). or to be removed
BREAK LAE
Wateid to continue
CENTER LRL GM UNE
PROPERTY LINE
LEGAL DESCRIPTION
IN THE COUNTY OF KING. STATE OF WASHINGTON:
THAT PORTION OF THE NORTH ONE -HALF OF THE NORTH NORTHEAST ONE- QUARTER
OF SECTION 16, TWP, 23N. RANGE 4E. WN M., IN KING COUNTY, WASHINGTON. LYING
EASTERLY OF MILITARY ROAD, EXCEPT THAT PORTION OF THE NORTHEAST
ONE - QUARTER OF THE NORTHEAST ONE - QUARTER OF SECTION 16. TAP, 2314 RANGE
4E, W.M., IN KING COUNTY, WASHINGTON. DESCRIBED AS FOLLOWS:
1. BEGINNING AT A POINT ON THE SOUTH UNE OF THE NORTHEAST 1/4 OF
THE NORTHEAST 1/4 OF SAID SECTION 16, DISTANT EAST 561 FEET FROM
THE SOUTHWEST CORNER THEREOF; THENCE NORTH, AT RIGHT ANGLES
184 FEET. THENCE WEST ON A UNE PARALLEL WMTH SOUTH UNE OF
SAID SUBDIVISION 225 FEET; THENCE NORTH AT RIGHT ANGLES 210
FEET; THENCE WEST ON A LINE PARALLEL WITH SOUTH UNE OF SAID
SUBDIVISION TO THE EASTERLY UNE OF MILITARY ROAD; THENCE
SOUTHERLY ALONG SAID EASTERLY UNE OF MIUTARY ROAD TO AND
INTERSECTING WITH THE SOUTH UNE OF SAID SUBDIVISION TO POINT OF
BEGINNING.
AND EXCEPT THAT PORTION OF THE NORTHEAST 1/4 OF THE NORTHEAST 1/4 OF
SECTION 16. MP, 23N. RANGE 4E. W.M.. IN KING COUNTY. WASHINGTON, DESCRIBED
AS FOLLOWS:
2. BEGINNING AT THE INTERSECTION OF THE SOUTH UNE OF THE NORTH 160
FEET OF SAID SUBDIVISION WITH THE EASTERLY MARGIN OF MIUTARY
ROAD; THENCE EASTERLY ALONG SAID SOUTH LINE 200 FEET; THENCE
NORTHERLY AT RIGHT ANGLES 160 FEET TO THE NORTH UNE OF SAID
SUBDIVISION; THENCE WESTERLY ALONG SAID NORTH UNE TO THE
EASTERLY UNE OF SAID MLITARY ROAD; THENCE SOUTHERLY ALONG
SAID EASTERLY UNE TO THE POINT OF BEGINNING; EXCEPT THAT
PORTION IF ANY, CONVEYED TO KING COUNTY FOR 128TH STREET, BY
DEED RECORDED UNDER AUDITOR'S FILE NO.5274608.
ARCHITECTURAL MATERIALS
DETAIL INDICATIONS
•
•
I I GYPSUM BOARD
INSULATION. BATT
INSULATION. RIGID
I
t
iIIIIIto
PLAIN INDICATIONS
ACOUSTIC TILE OR BOARD
ROOFING
BRICK
CERAMIC TILE
CONCRETE
PRECAST CONCRETE
CONCRETE MASONRY UNIT
EARTH/FINISH GRADE
GLASS
GRAVEL
METAL
METAL LATH
MORTAR, PLASTER, SAND
PLYWOOD
WOOD. F01MSH
EOGSTING WALL
EIEMEMBISIEBEE NEVI STUD MALL
ARCHITECTURAL ABBREVIATIONS
L
g
C
e
T
AB
A/C
ACOUS
ADJ
ADJT
AFT
AL
ALT
ANC
APPD
APPROX
ARCH
AUTO
BD
BLDG
BLK
BLKG
EIM
BOF
BOTT
ERG
89417
CAB
COA
CER
CG
CP
cLG
CUCG
0.0
CZR
COL
COMP
CONC
CONN
CONST
CONT
CONTR
CORR
CPT
CT
c m
and
angle
of
centerline
channd
diameter or round
plate
pound or number
tee
anchor bolt
or
acousticol
odpstable
odjacent
above finished floor
aluminum
alternate
onchor(oge)
approved
approximate
architectural
automatic
board
between
block
blodcing
buidng
beam
bottom of frame
bottom
bearing
basement
cabinet
cement
ceramic
corner guard
cost in place concrete
control jot, construction joint
coW ng
closet
cering
dear
column
composition. composite
concrete
connection
construction
continuous
controctor
corridor
oorPot
gamic tie
center
•
DBL
DEMO
DIA
DIAG
DIM
DN
OAV
OR
DWG
OWR
EA
EJ
EL
ELEC
ELEV
EMER
ENCL
EP
EQ
EQUIP
EMiC
EXH
EXIST
(E)
EXP
EXPO
EXT
FA
FAB
FD
FE
FEC
FEC -S
FIN
FL
FLUOR
FiOF
FOS
F091
FP
FR
itdfG
FT
FTG
PURR
FUT
GA
GALV
GEN
GL
GLZ
GYP
N
CO VICINITY PLAN
NO SCALE
deep. depth
double
demolish, demolition
diameter
diagonal
dimension
division
down
door
drawing
drawer
east
each
expansion joint
devotion
electrical
elevator
emergency
enclosure
d triad pondboard
equal
equipment
electric water coder
exhaust
existing
• n9
expansion
exposed
exterior
fire dorm
fabricate
floor drain
fire extinguisher
fore • (recessed)
cabinet extinguisher ( )
finish
floor
fluorescent
face of finish
face of studs
face of shecthig
feepraof
fee resistant
fraying
g
foot. feet
Sooting
fEurrrq
future
gouge
galvanized
grab bar
general
foss
glazing
gypsum board
H
FIN
HC
N C
HO
HOW
HORIZ
HSS
HT
HTG
HVAC
INCL
INFO
INNSU L
INTERCOM
JAN
• T
Jr
L
LAB
LAM
LAV
LT
MACH
MAIL
MAX
Y9R
MC
MECH
MED
MOB
11FR
ISSC
11T(0)
YTS
N
MC
NOOR#
NOM
NTS
OA
OC
OP G
OPP
cG
high
hose bibb
hollow core
handicap (accessible)
head
hardware
horizontal
hollow sled section
height
heating
heating/ventilating/air-
conditioning
inside diameter (dm.)
include
information
insulation
interior
intercommunication
janitor
joist
joint
length. long
laboratory
laminate
lavatory
light, left
machine
material
maximum
member
medicine cabinet
mechanical
medium
membrane
manufacturer
manhole. mop holder
minimum
mirror
miscellaneous
maunt(ed)
metal
north
not in contract
number
named
not to scare
over -dl
on center
outside diameter
h9
opposite
original
PAR
PERF
PERP
PLAN
PL
PLUMB
PLYWD
PNL
POS
PR
PROW
PROJ
PT
QT
RCP
RECa
REEL
REWF
RESIL
RY
R
S
SC
SCHED
SECT
SHR
SH
SHT
SUNG
SPEC
SO
SS1C
SS
SID
STL
STOR
STRUCT
SUlB
SU'SP
SYS
porolld
perforated
perpendicular
plastic lominate
plate
plumbing
Pirwood
panel
positive
Pair
prefabricote(d)
prefaiish(ed)
project
pmt, point
quarry tie
riser. radius
reflected ceiling plan
roof drain
received
reference
reflected
refrigerator
reinfarce(d)(ng)
required
resilient
roof
room
rough opening
right
south
solid core
schedule
section
shower
sheeting
sheet
sheathing
ssmior
UMW*
an
service sink
stoniess steel
standard
steel
storage
stnrcturd
substitute
suspended
symmetrical
system
• C
104
TEL
TEMP
TF
THK
THEW
TOF
TS
TV
TVB
TW
TYP
�N
UR
ye
VCT
VENT
IAZR
VERT
VEST
w
w/
sow
vas
W/O
WP
WSCT
WS
WT
NITR
WNF
AREA OF WORK
REGIONAL HOSPITAL,
WEST WING
telephone
temporary
top of footing
thick
through
top of frame
tube steel
television
television bracket
top of wSIPARATE
typical PERMIT AND
unfinished
unless noted otherwise
urinal
vapor barrier
vinyl composition tie
ventiote
verify
vend
vestibule
volume
west. wide; width
with
wood
window
well hung
without
waterproof
wainscot
weather stripping
wdght
water
welded we fabric
S: PARATE
. "; i AND
' ?OVAL
INDEX OF DRAWINGS
GENERAL
G0.1
COVER SHEET
CODE SUMMARY PUN
N
CD SITE PLAN
SCALE: 1" = 2400'
X \
ARCHITECTURAL
A3.1 SECOND FLOOR PLAN
AND ROOM FINISH SCHEDULE
A4.1 BUILDING SECTION
A7.1 INTERIOR ELEVATIONS
A9.1 SECOND FLOOR REFLECTED CEILING PLAN
TRUCTURAL.
ST GENERAL STRUCTURAL NOTES
FRAMING PLAN AND DETAILS
MECHANICAL
MO1 MECHANICAL SYMBOLS & LEGENDS
MO.2 SCHEDULES- PIPING AND HVAC
Y1_1 OEHOU11ON PLAN - PIPING
111.2 OEYOUTION PLAN - HVAC
M2.1 SECOND FLOOR PLAN - PIPING
Mil SECOND FLOOR PLAN - HVAC
113.2 PENTHOUSE PLAN - PIPING AND HVAC
114.1 DETAILS - PIPING AND HVAC
115.1 CONTROL DIAGRAMS
1152 CONTROL DIAGRAMS
ELECTRICAL
EO SYMBOL AND ABBREVIATIONS
E2.1 2110 FLOOR POWER PLAN NEST
E3.1 2ND FLOOR UGHTe1G PLAN *EST
E4.1 ONE -LLVE Mat DIAGRAM
E4.2 PANG. SOBS
SEPARATE mar
REQUIRED MR:
IEEtterical
gpinbtv
irGus Plying
City of
BUILDING DIVISION
By
tote:
COP'S PILE
PennftNo.
•
R VIE D fOR
CODE CO! PL N
M629
BUILDP f`'iTS
Ran review approval Is subject to ems ar
Apptoval at construction documents don not oultolso
the vlola'oi c ` any accepted code co' ordlro fpe„ Illy
at a: _ C : a. aof>dtfpns b ad:nollN140
1,4111DING DIVISION
REC6VED
afY0FTIMMIU
Alit 10 2606
PERICCENTER
kAD(o-1
AIDLISti
R SHEET
l
REVISIONS
2207 9XTh A NI.:E
SulE T4
SEATTLE. AA 98
(206) 44i -4522
FAX (2t,6) «j -79:
I
tixc no_ 2 - 06005
::LE GO-1
.cm; LWW
C _C-(ED RAS
DcE 7- 28 -06
G
0.1
C Ye4 41. - -Awcz O ieracavi Cs ?r'
r '4'
SYMBOLS /ABBREVIATIONS MECHANICAL LEGEND
1 AHU -01 I
DRAWING NOTE CALLOUT
FLAG NOTE CALLOUT
• INVERT ELEVATION OR POC
GRILLE REGISTER OR DIFFUSER TYPE
341 - 7 - 1 - -- ---SCHEDULE MARK
2 00 `FAIR QUANTITY (CFM)
ABV
AD
AFF
BDD
BOD
CD
CG
COND
CONT
CLG
DIM
DN
DWV
(E)
EXH
EG
ESP
F
FD
F/S
FLEX
GPM
lE
MBH
MC
MFR
MTG
NO
POC
RA
RG
R /E/T
RPBP
SA
SIM
SG
TG
TYP
0
t + 4
MECHANICAL EQUIPMENT TAG
DETAIL /SECTION IDENTIFIER
ABOVE
ACCESS DOOR
ABOVE FINISHED FLOOR
BACKDRAFT DAMPER
BOTTOM OF DUCT
CEIUNG DIFFUSER
CEIUNG GRILLE
CONDENSATE
CONTINUATION /CONTRACTOR
CEIUNG
DIMENSION
DOWN
DRAIN WASTE AND VENT
EXISTING
EXHAUST
EXHAUST GRILLE
EXTERNAL STATIC PRESSURE
FAHRENHEIT
FIRE DAMPER
FIRE /SMOKE DAMPER
FLEXIBLE DUCT
GALLONS PER MINUTE
INVERT ELEVATION
THOUSANDS BTU PER HOUR
MECHANICAL CONTRACTOR
MANUFACTURER
MOUNTING
NORMALLY OPEN
POINT OF CONNECTION
RETURN /RELIEF AIR
RETURN GRILLE
RETURN /EXHAUST/TRANSFER
REDUCED PRESSURE BACKFLOW PREVENTER
SUPPLY AIR
SIMILAR
SUPPLY GRILLE
TRANSFER GRILLE
TYPICAL
DIAMETER
•
i
71311• tJI F
4 r:= 1
- ►R
20x10
--;4 D 4 D
1:2611: D
CM'
■
FD
1 T#
t1
RISE IN DUCT - (D =DROP IN DUCT)
DUCT SIZE (CLEAR INSIDE DIMENSION)
SOUNDLINED DUCTWORK
-- RECTANGULAR DUCT UP
- RECTANGULAR DUCT DN
ROUND DUCT UP
ROUND DUCT DN
- FLEXIBLE CONNECTION
DUCT RISE /DROP W/ 90' ELBOWS
(RECTANGULAR DUCTS)
_ DUCT RISE /DROP W/ 45' ELBOWS
(RECTANGULAR DUCTS)
_ DUCT RISE /DROP W/ 90' ELBOWS (ROUND
OR OVAL DUCT)
_ DUCT RISE /DROP W/ 45' ELBOWS (ROUND
OR OVAL DUCTS)
SECTION THRU SUPPLY AIR DUCT
SECTION THRU RETURN, EXHAUST OR OUTSIDE
AIR DUCT
- EXHAUST /RETURN ROOF PENETRATION
FSD
FD
EXISTING WORK TO BE DEMOLISHED
- VOLUME DAMPER
- TRANSITION - FROM RECTANGULAR TO ROUND
•
SUPPLY ROOF PENETRATION
FIRE SMOKE DAMPER
CEILING RADIATION FIRE DAMPER
DUCT SMOKE DETECTOR
CD CEIUNG DIFFUSER
RG RETURN /RELIEF AIR GRILLE
EG EXHAUST AIR GRILLE
- RET /EXH AIRFLOW
SUPPLY AIR FLOW
T'STAT THERMOSTAT OR TEMP SENSOR
- MOTORIZED DAMPER
- AUTOMATIC CONTROL VALVE, 3 -WAY
- AUTOMATIC CONTROL VALVE, 2 -WAY
CBV CIRCUIT SETTING BALANCING VALVE
RV PRESSURE RELIEF VALVE
PRV PRESSURE REDUCING VALVE
FCO CLEANOUT - FLUSH WITH FLOOR
WCO WALL CLEANOUT
PIPE UP
PIPE ELL DOWN
PIPE TEE UP
PIPE TEE DOWN
•
HWS
- HWR
•
CWS
- CWR -
MV
02
MA
HWS
- HWR
CWS
CWR
MV
02
MA
DRAWING SCHEDULE
M0.1 MECHANICAL SYMBOLS AND LEGEND
MO.2 SCHEDULES - PIPING AND HVAC
M1.1 DEMOUTION PLAN - PIPING
M1.2 DEMOLITION PLAN - HVAC
M2.1 SECOND FLOOR PLAN - PIPING
M3.1 SECOND FLOOR PLAN - HVAC
M3.2 PENTHOUSE PLAN - PIPING AND HVAC
M4.1 DETAILS - PIPING AND HVAC
M5.1 CONTROL DIAGRAMS
145.2 CONTROL DIAGRAMS
ENERGY CODE NOTES
SANITARY WASTE ABOVE GRADE
SANITARY WASTE BELOW GRADE
EXISTING PIPING
COLD WATER PIPING (CIA)
HOT WATER PIPING (HW)
HOT WATER RECIRCULATING PIPING
VENT PIPING
HOT WATER HEATING SUPPLY
HOT WATER HEATING RETURN
PIPE CONNECTION
PIPE CAP
UNION
WYE STRAINER
ISOLATION VALVE
CHECK VALVE
POINT OF CONNECTION TO EXISTING
BALANCING VALVE
CHILLED WATER SUPPLY
CHILLED WATER RETURN
MEDICAL VACUUM
OXYGEN
MEDICAL AIR
1 _ MOTORS: COMPLY WITH MINIMUM FULL LOAD EFFICIENCIES USTED IN
WSEC, SECTION 1437 AND TABLE 14-4.
2. PIPING AND DUCT INSULATION: COMPLY WITH THICKNESS AND TYPES
USTED IN WSEC, SECTION 1415.1 AND TABLE 14 -6 FOR PIPING AND
SECTION 1414.2 AND TABLE 14 -5 FOR DUCTS UNLESS MORE
STRINGENT INSULATION REQUIREMENTS ARE SPECIFIED.
3. DUCT SEAUNG: SEAL DUCT TRANSVERSE JOINTS AND LONGITUDINAL
SEAMS PER WSEC, SECTION 1414.1 UNLESS MORE STRINGENT
SEALING REQUIREMENTS ARE SPECIFIED.
4_ RECORD DRAWINGS: SUBMIT TO THE BUILDING OWNER WITHIN 90
DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE OR PER WSEC,
SECTION 1416.1.
5. OPERATION AND MAINTENANCE MANUAL SUBMIT TO THE BUILDING
OWNER PER WSEC, SECTION 1416.2. PROVIDE COMPLETE NARRATIVE
OF HOW EACH SYSTEM SHOULD WORK INCLUDING RECOMMENDED SET
POINTS."
6_ SYSTEM BALANCING: BALANCE HVAC SYSTEMS PER WSEC SECTION
1416.3 AND SUBMIT A WRITTEN REPORT TO THE BUILDING OWNER.
REFER TO SPECIFICATIONS FOR ADDITIONAL TESTING, ADJUSTING, AND
BALANCING (TAB) REQUIREMENTS.
7. THE MECHANICAL WORK SHALL BE COMMISSIONED IN ACCORDANCE
WITH SECTION 1416.4 OF THE WA STATE ENERGY CODE INCLUDING
THE REQUIREMENTS FOR SIMPLE SYSTEMS, OTHER SYSTEMS,
DOCUMENTATION, COMMISSIONING REPORTS (PRELIMINARY AND ANAL),
AND ACCEPTANCE. THE BUILDING WILL NOT BE ACCEPTED AND
ISSUED A FINAL CERTIFICATE OF OCCUPANCY UNTIL THE BUILDING
OFFICIAL DETERMINES THAT A PREUMINARY COMMISSIONING REPORT
HAS BEEN COMPLETED.
8. AN AR BALANCE REPORT IS REQUIRED SHOWING AIR FLOW RATES
MEASURED AND ADJUSTED TO WITHIN 10% OF DESIGN RATES.
WRITTEN BALANCE REPORT SHALL BE PROVIDED TO THE OWNER.
GENERAL MECHANICAL NOTES
GENERAL NOTES - MECHANICAL
1. EXPOSED PIPING: PROVIDE CHROME PLATING FOR EXPOSED PIPING
IN FINISHED ROOMS.
2. LIGHT FIXTURE CLEARANCE: COORDINATE LOCATIONS OF MECHANICAL
WORK TO PROVIDE CLEARANCES OVER UGHTING FIXTURES FOR
REMOVAL AND REPLACEMENT.
3. CABLE TRAYS: DUCTWORK AND PIPING INSTALLED ADJACENT TO
ELECTRICAL CABLE TRAYS SHALL ALLOW MINIMUM ACCESS OF 12"
ABOVE AND TO THE SIDE OF CABLE TRAYS.
4. DO NOT RUN ANY PIPES OR DUCTS OVER ANY ELECTRICAL PANEL OR
SWITCHGEAR. COORDINATE /LOCATE PIPE AND DUCT LOCATIONS TO
AVOID ELECTRICAL PANELS.
5. CONTRACTOR SHALL COORDINATE /LOCATE DMSION 15 WORK WITH
THAT OF OTHER TRADES ( ELECTRICAL. ARCHITECTURAL, STRUCTURAL).
REFER TO ELECTRICAL, ARCHITECTURAL, AND STRUCTURAL DRAWINGS
AND SPECIFICATIONS.
6. PROVIDE MANUFACTURER'S RECOMMENDED AND CODE REQUIRED
CLEARANCE AROUND ALL PIECES OF EQUIPMENT. PIPING AND
CONDUIT SHALL NOT INTERFERE WITH REQUIRED ACCESS.
7. EQUIPMENT LAYOUT IS BASED ON EQUIPMENT USTED IN EQUIPMENT
SCHEDULES. OTHER EQUIPMENT USED IS SUBJECT TO MEETING
PERFORMANCE REQUIREMENTS OF SCHEDULED EQUIPMENT.
CONTRACTOR SHALL MAKE ALL NECESSARY ADJUSTMENTS /DESIGN
CHANGES TO ASSURE EQUIPMENT, OTHER THAN SCHEDULED, WILL FIT
IN AVAILABLE SPACE.
MECHANICAL EQUIPMENT INSTALLATION NOTES
1. ACCESS CLEARANCES FOR MAINTENANCE AND REPLACEMENT: VERIFY
PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT ACCESS
CLEARANCES CAN BE MET. COORDINATE LOCATIONS OF MECHANICAL
WORK AND WORK OF OTHER TRADES TO PROVIDE ACCESS
CLEARANCES FOR SERVICE AND MAINTENANCE.
DEMOLITION NOTES
1. PIPING: REMOVE EXISTING PIPING SERVING ITEMS TO BE REMOVED.
REMOVE UNUSED BRANCH PIPING LEAVING NO DEAD PIPE LEGS.
CAP OR PLUG IN A CONCEALED MANNER.
2. DUCTWORK: REMOVE EXISTING DUCTWORK AS INDICATED. CAP
EXISTING OPENINGS NOT BEING REUSED WITH SHEET METAL AND
COVER EXISTING OPENINGS BEING REUSED WITH PLASTIC SHEETING
COMPLETELY SEALED WITH TAPE.
3. EQUIPMENT: REMOVE EXISTING HVAC EQUIPMENT AS INDICATED,
INCLUDING ASSOCIATED PIPING, CONTROL SYSTEMS, AND
APPURTENANCES.
PIPING NOTES
1. DISASSEMBLY PROVISIONS: PROVIDE UNIONS OR FLANGES AT PIPING
CONNECTIONS TO EQUIPMENT, COILS, TRAPS, CONTROL VALVES, AND
OTHER COMPONENTS TO ALLOW DISASSEMBLY FOR MAINTENANCE.
2. REDUCERS: PROVIDE AS REQUIRED FROM UNE PIPE SIZE TO
EQUIPMENT, TRAP, COIL, AND CONTROL VALVE CONNECTION SIZES.
3. OFFSETS: PROVIDE FOR BRANCH UN ES TO EQUIPMENT.
4. DIELECTRIC UNIONS: PROVIDE AT CONNECTIONS OF DISSIMILAR PIPE.
5. COIL PIPING: COORDINATE LOCATIONS WITH DUCT LAYOUT DRAWINGS.
PIPE SUPPLY WATER UNES TO COIL LEAVING AIR SIDES (AT BOTTOM)
TO OBTAIN COUNTERFLOW ARRANGEMENT.
6. PETE'S PLUGS: PROVIDE AT SUPPLY AND RETURN CONNECTION TO
ALL EQUIPMENT. TEST PLUGS FOR EQUIPMENT SHALL BE LOCATED
IMMEDIATELY ADJACENT TO THE EQUIPMENT SUCH THAT THERE ARE
NO FITTINGS BETWEEN THE TEST PLUG AND THE FINAL EQUIPMENT
CONNECTION POINT. PROVIDE TEST PORTS IMMEDIATELY ADJACENT TO
ALL SENSORS, GAGES, AND THERMOMETERS.
7. BALANCING /MEASURING VALVES: SIZE SMALLER THAN UNE SIZE IF
REQUIRED TO RESULT IN MINIMUM 1 FT PRESSURE DROP AT DESIGN
FLOW, AS CLOSE TO UNE SIZE AS POSSIBLE. PROVIDE REDUCERS
UPSTREAM AND DOWNSTREAM AS REQUIRED. INSTALL VALVES WITH
STRAIGHT PIPE UPSTREAM AND DOWNSTREAM AS REQUIRED BY
MANUFACTURER'S INSTRUCTIONS.
8. HEATING AND CHILLED WATER PIPING: 3/4 INCH MINIMUM PIPE SIZE.
INSULATION /LINING NOTES
1. EXTENT OF INTERNAL DUCT UNING: NONE.
2. EXTENT OF EXTERNAL DUCT INSULATION:
A. SUPPLY NR DUCTS ABOVE COUNGS OR EXPOSED_
B_ SUPPLY AND RETURN AIR DUCTS OUTDOORS.
3. MISCELLANEOUS DUCT FITTINGS (CONICAL TAKEOFFS, ETC.): WRAP
WITH INSULATION FOR CONDENSATION CONTROL
PLUMBING NOTES
1. COOLING COIL CONDENSATE DRAINS: PIPE WITH TRAP PER
MANUFACTURER'S RECOMMENDATIONS, AND ROUTE OUTDOORS AS
INDICATED_ TERIAINATE WITH 1" AIR GAP.
FIRE PROTECTION NOTES
.
1. RELOCATE EXISTING SPRINKLER HEADS AS REQUIRED TO _: :
ACCOMMODATE AR DISTRIBUTION SYSTEM_ --
SHEET METAL NOTES
1. REFERENCE: SMACNA I-VAC DUCT CONSTRUCTION STANDARDS,
METAL AND FLEXIBLE, SECOND EDITION, 1995 ( SMACNA
HVACDCS).
2. CLEARANCE: COORDINATE DUCTWORK WITH MISCELLANEOUS
OBSTRUCTIONS IN CEILING SPACE.
3. DUCT SIZES: SIZES INDICATED ARE INSIDE CLEAR DIMENSIONS.
4. ROUND AND FLAT OVAL ELBOWS AND OFFSETS: FULL RADIUS
(R /D = 1.5). 5 -PIECE SEGMENTED OR STAMPED. REFER TO
SMACNA HVACDCS' FIGURES, 3 - 3 AND 3 - 6. REFER TO SMACNA
HVACDCS FIGURE 2.7 FOR OFFSETS. DO NOT USE ANGLED
OFFSET (TYPE 1). MITERED OFFSET (TYPE 2) MAY BE USED UP
TO 30 DEGREE OFFSET ANGLE.
5. ROUND AND FLAT OVAL TEES AND LATERALS: CONICAL TEE
FITTING OR TAP PER SMACNA HVACDCS FIGURE 3 -5.
90- DEGREE TEE WITH OVAL TO ROUND TAP, 45- DEGREE
LATERAL FITTING, TAP, OR SADDLE TAP, AND 45- DEGREE
RECTANGULAR LEAD -IN PER SMACNA HVACDCS FIGURE 3 -4. DO
NOT USE STRAIGHT TEE. DO NOT USE CONICAL OR 45- DEGREE
LATERAL SADDLE TAP FOR EXPOSED DUCTWORK IN FINISHED
SPACES.
6. RECTANGULAR ELBOWS AND OFFSETS: FULL RADIUS WHERE
MINIMUM 5 DUCT WIDTHS IS AVAILABLE DOWNSTREAM OF ELBOW
PRIOR TO BRANCH TAKEOFFS AND FIRINGS, R/W = 1.5.
OTHERWISE, USE SQUARE CORNER ELBOW WITH TURNING VANES.
REFER TO SMACNA HVACDCS FIGURE 2 -7 FOR OFFSETS. DO
NOT USE ANGLED OFFSET (TYPE 1). MITERED OFFSET (TYPE 2)
MAY BE USED UP TO 30 DEGREE OFFSET ANGLE.
7. RECTANGULAR DMDED FLOW FITTINGS: USE GENERALLY, EXCEPT
BRANCHES TO TERMINALS; REFER TO SMACNA HVACDCS FIGURE
2 -5.
8. TURNING VANES: H.E.P. MANUFACTURER OR APPROVED HIGH
EFFICIENCY PROFILE AIRFOIL TYPE FOR RECTANGULAR AND FLAT
OVAL SQUARE THROAT ELBOWS. ACOUSTICAL TYPE FOR RETURN
AIR MITERED ELBOWS.
9. TAKEOFFS TO OPENINGS:
10.VOLUME DAMPERS: PROVIDE A MANUAL VOLUME DAMPER FOR
EACH SUPPLY AND EXHAUST OPENING, LOCATED AS FAR
UPSTREAM AS POSSIBLE FROM THE OPENING. PROVIDE A
MANUAL VOLUME DAMPER FOR BRANCH MAINS SERVING MORE
THAN ONE OPENING.
11. DUCTS UPSTREAM OF AIR TERMINAL UNITS:
A. CONICAL TYPE WITH VOLUME DAMPER FOR ROUND DUCT
BRANCHES PER SMACNA HVACDCS FIGURE 2 -6, MINIMUM
INLET DIAMETER 2 INCHES LARGER THAN DUCT SIZE. 45
DEGREE ENTRY FITTING FOR RECTANGULAR DUCT BRANCHES
PER SMACNA HVACDCS FIGURE 2 -6.
B. FLEX DUCTS: LOW PRESSURE FLEX DUCTS MAY BE USED
WHERE SPACE PERMITS. DO NOT INSTALL IN CORRIDOR
CEIUNG SPACES WHERE FIRE RATING IS REQUIRED. MAXIMUM
DEVELOPED LENGTH 7 FT. GENERALLY INSTALL WITH
STRAIGHT SECTIONS, WITHOUT BENDS; PROVIDE SHEET METAL
ELBOWS FOR CHANGES IN DIRECTION TO RESULT IN STRAIGHT
FLEX DUCT RUNS. IF BENDS ARE ABSOLUTELY NECESSARY,
R/D SHALL BE 2.5 OR GREATER. NO KINKS ALLOWED.
SUPPORT WITH MINIMUM 1 INCH WIDE STRAPS AROUND DUCT,
MAXIMUM UNSUPPORTED LENGTH 5' -0 ", MAXIMUM SAG 0.5
INCH PER FOOT OF SUPPORT SPACING. SUPPORT SYSTEM
SHALL NOT CAUSE OUT OF ROUND SHAPE. REFER TO
SMACNA HVACDCS FIGURES 3 -9 AND 3 -10.
A FLEX DUCTS: MEDIUM PRESSURE FLEX DUCTS MAY BE USED
ONLY WHERE SPACE IS UMMTED. GENERALLY INSTALL WITH
STRAIGHT SECTIONS, WITHOUT BENDS; PROVIDE SHEET METAL
ELBOWS FOR CHANGES IN DIRECTION TO RESULT IN STRAIGHT
FLEX DUCT RUNS. IF BENDS ARE ABSOLUTELY NECESSARY,
R/D SHALL BE 2.5 OR GREATER. NO KINKS ALLOWED.
SUPPORT WITH MINIMUM 1 INCH WIDE STRAPS AROUND DUCT,
MAXIMUM UNSUPPORTED LENGTH 5' -0 ", MAXIMUM SAG 0.5
INCH PER FOOT OF SUPPORT SPACING. SUPPORT SYSTEM
SHALL NOT CAUSE OUT OF ROUND SHAPE. REFER TO
SMACNA HVACDCS FIGURE 3 -9.
B. NR TERMINAL UNIT INLET CONNECTIONS: PROVIDE TWO FEET
OR THREE EQUIVALENT DUCT DIAMETERS, WHICHEVER IS
GREATER, OF STRAIGHT SHEET METAL DUCT AT INLET OF EACH
AIR TERMINAL UNIT, SIZE EQUAL TO UNIT INLET CONNECTION
SIZE. PROVIDE TRANSITION IF PRIMARY DUCT SIZE IS LARGER
THAN INLET INLET CONNECTION SIZE, LOCATED AT UPSTREAM
END OF STRAIGHT SHEET METAL DUCT.
12.DUCTS DOWNSTREAM OF AIR TERMINAL UNITS:
A. TRUNK DUCT: EXTENDED PLENUM OF CONSTANT SIZE TO
MATCH UNIT DISCHARGE CONNECTION SIZE, OR MINIMUM SIZE
PER SCHEDULE WITH TRANSITION FROM BOX DISCHARGE
CONNECTION SIZE. MINIMUM 4 FT. OF RUN PRIOR TO FIRST
TAKEOFF.
B. TAKEOFFS TO OPENINGS: REFER TO PARAGRAPH ABOVE. IN
GENERAL, ONE TAKEOFF FROM TRUNK DUCT FOR EACH
OPENING.
13.ACCESS DOORS: PROVIDE AT ARE /SMOKE DAMPERS AND
DUCT SMOKE DETECTORS.
CRYOFTHIC
AUG 18 ?cti
PERMIT
•
MECHANICAL SYMBOLS AND LEGEND
REVISIONS
2201 SIXTH AMIDE
SATE 1405
SEATTLE, WA 98121
(206) 441 -4522
FAX (206) 441 -7917
Ihi 44
�f !,1
1
N IAC No. 2 -06005
ALE
DRAIN
CHECKED
DATE 7 -28 -06
AIR TERMINAL UNIT SCHEDULE
SCHEDULE
HEATING COIL -
ELECTRICAL/FAN(S)
MARK
AREA SERVED
ASSOCIATED
AHU
MAN. /MODEL NO.
AIRFLOW
(CFM)
INLET
DUCT
(IN)
OUTLET DUCT
(IN)
W x H
MBH
EAT
('F)
EAT
CO
ROWS
(I)
GPM
EWT
co
MAX H2O
PD
(FT)
RUNOUT
SIZE
(IN)
VALVE
TYPE
DIMENSIONS
(LxWxH)
(INxINxIN)
REMARKS
TU -32
CLEAN UTILITY, SOILED UTILITY
AHU -6
TITUS DEW
310
6
12 8
5.1
60
75
1 `
0.5
180
2.5
3/4
2 -WAY
23 12 8
1900
TU -33
PATIENT ROOM, TOILET
AHU -6
TITUS DEW
250
5
12 8
4.1
60
75
1
0.4
180
2.5
3/4
3/4
2 -WAY
2 -WAY
23 12 8
23 12 8
54
TU -34
PATIENT ROOM, TOILET, EQUIP.
AHU -6
TITUS DESV
250
5
12 8
4.1
60
75
1
0.4
180
2.5
TU -35
PATIENT ROOM, TOILET
AHU -6
TITUS DESV
300
6
12 8
5.0
60
75
1
0.5
180
2.5
3/4
3/4
2 -WAY
2 -WAY
23 12 8
23 12 8
180
TU -36
PATIENT ROOM, TOILET
AHU -6
TITUS DEW
250
5
12 8
4.1
60
75
1
0.4
__
180
2.5
TU -37
PATIENT ROOM, TOILET
AHU -6
TITUS DESV
310
6
12 8
5.1
60
75
1
0.5
180
2.5
3/4
2 -WAY
23 12 8
-70
TU -38
CORRIDOR
AHU -6
TITUS DEW
490
7
12 10
8.1
60
75
1
0.8
180
2.5
3/4
2 -WAY
23 12 10
PATIENT ROOM
TU -39
FUTURE PATIENT ROOM, TOILET
AHU -6
TITUS DESV
250
5
12 8
4.1
60
75
1
0.4
180
2.5
3/4
2 -WAY
23 12 8
TU -36
TU -40
PATIENT ROOM, TOILET
AHU -6
TITUS DEW
290
6
12 8
4.8
60
75
1
0.5
180
2.5
3/4
2 -WAY
23 12 8
10
TU -41
PATIENT ROOM, TOILET
AHU -6
THUS DEW
240
5
12 8
4.0
60
75
1
0.4
180
2.5
3/4
2 -WAY
23 12 8
0
TU - 42
PATIENT ROOM, TOILET
AHU - 6
TITUS DEW
240
5
12 8
4.0
60
75
1
0.4
180
2.5
3/4
2 - WAY
23 12 8
70
TU - 43
SHOWER, TOILET
AHU -6
TITUS DESV
165
4
12 8
2.7
60
75
1
0.3
180
2.5
3/4
2 -WAY
23 12 8
TOILET ROOM
AIR HANDLING UNIT SCHEDULE
SCHEDULE
MAX
CFM /FT
< 25 NC
ELECTRICAL/FAN(S)
FINISH
MATERIAL
COIL
MAX APD/
FACE VEL FPM
COOLING
GPM
ENT H2O
DB/W8
LEV H2O
DB/W8
(
MAX
WATER
PD FT)
VALVE
TYPE
WEIGHT
LBS)
RUN OUT
SIZE CW
IN
NOMINAL
DUCT WIDTH
(IN)
MARK
AREA SERVED
MANUFACTURER /MODEL NO.
SUPPLY
FAN
CFM
RETURN/
EXH FAN
(CFM)
MIN OA
CFM
MAX OA
CFM
SUPPLY FAN
MOTOR
HP
ESP
IN)
TSP
IN
RPM
RETURN FAN
MOTOR
HP
ESP
IN
TSP
IN
RPM
V/0
(MBH) '
ENT AIR
DB/WB
F)
LEV AIR
DB/WB
(F)
REMARKS
AHU -6
2ND FLOOR WEST
HAAKON CUSTOM
3500
1900
1600
3500
5
2
4
3450
1
0.5
1
1750
208 1 3
104
80.1 / 62.0
53.2 / 51.0
0.7 / 450
21.4
44
54
15
3 -WAY
4430
2
NOTE 1
1.
2.
NOTES
SUM OF SA AND RA GRILLES AND DIFFUSERS. CAPACITIES ARE ADJUSTED FOR DUCT LEAKAGE.
DRIVE (VFD).
AHU -6
FACE VELOCITY OF 1000 FPM
6
FAN AIRFLOWS DO NOT MATCH THE
FAN CONTROLLED BY VARIABLE FREQUENCY
AIR DEVICE
MARK
SCHEDULE
MAX
CFM /FT
< 25 NC
FRAME
TYPE
FINISH
MATERIAL
REMARKS
TYPE
MANUFACTURER
SUPPLY /
RETURN /
EXHAUST
BORDER TYPE
NECK SIZE
(L "xW")
FACE SIZE
(L "xW")
(IN)
CFM
RANGE
< 25 NC
NOMINAL
DUCT WIDTH
(IN)
CD -1
CEIUNG DIFFUSER
TITUS MCD
SUPPLY
HARD OR LAY -IN
6 x 6
24x24
0 - 150
NA
NA
1 OR 3
WHITE
STEEL
NOTE 1, 2
8x8
155 -310
-
RG -1
RETURN GRILLE
TITUS 350RL
RETURN
HARD OR LAY -IN
8 x 8
-
0 - 150
NA
NA
I
1 OR 3
l
WHITE
STEEL
NOTE 1
12 x 12
155 - 350
IAC / HLFM
EG-1
EXHAUST GRILLE
TITUS 350RL
RETURN
HARD OR LAY -IN
8 x 8
-
0 - 150
NA
NA
1 OR 3
WHITE
STEEL
NOTE 1
12 x 12
155 - 350
MOTES
1. FACE SIZE FOR HARD CEIUNG IS NECK SIZE PLUS 5 INCHES.
2. DUCT RUNOUT SIZE SHALL BE THE ROUND EQUIVALENT OF DIFFUSER OR GRILLE NECK SIZE.
EXISTING FAN SCHEDULE
MARK
LOCATION
AREA SERVED
I MANUFACTURER/MODEL NO.
SUPPLY
FAN
(CFNI)
TSP
(IN)
FAN '
RPM
MOTOR
(HP)
V/0
REMARKS
EF -3
ROOF
2 WEST. 3 WEST 4 WEST
ALADDIN F2226
4680
5/8
415
1 -1/2
208 / 3
NOTE 1
-
-
-
-
4375
7/8
450
1 -1/2
208 / 3
NOTE 2
-
- _
-
-
5225
1.25
538
2
208 / 3
NOTE 3
1 _ DESIGN AIFLOWS
2_ DATA BASED
3. DESIGN AIRFLOW
NOTES
OF 2 WEST (WEST WING).
UNDER THIS CONTRACT IS COMPLETED_
(ORIGINAL) INCLUDING REMODEL
UPON EXHAUST FAN NAMEPLATE.
WHEN 2 WEST EAST WING REMODEL
SOUND ATTENUATOR SCHEDULE
/ PRESSURIZATION SCHEDULE
ROOM NAME
VOLUME
( FT"3)
AHU
NOISE REDUCTION (Db)
WAC 246- 320 -525
DESIGN AIRFLOW (CFM)
MARK
LOCATION / AREA SERVED
MANUFACTURER /MODEL NO.
EA (ACH)
TYPE
SIZE
(WxH)
AIRFLOW
(CFM)
63
(HZ)
125
(HZ)
1
_ _
N
N a
500
(HZ)
1000
(HZ)
2000
(HZ)
_ _
1 i
_ _
1 i
FACE
VELOCITY
(FPM)
LENGTH
(FT)
I
REMARKS
SA -1
AHU -6 SUPPLY
IAC / HLFM
110
5 HLFM
24x18
3500
10
12
21
23
22
16
12
10
1000
5
1
200
SA -2
AHU -6 RETURN
IAC / HLFM
_5
HLFM
24x18
1900
10
12
21
23
22
16
12
10
1000
5
1
PATIENT ROOM
1.
AHU -6
FACE VELOCITY OF 1000 FPM
6
170
NOISE REDUCTION BASED UPON A
AIR BALANCE
ROOM
/ PRESSURIZATION SCHEDULE
ROOM NAME
VOLUME
( FT"3)
AHU
TU
WAC 246- 320 -525
DESIGN AIRFLOW (CFM)
REMARKS
SA (ACH)
SA (CFM)
EA (ACH)
EA (CFM)
PRESS (1)
SA
RA
EA
P
225
227
CLEAN UTILITY
1200
AHU -6
TU -32
4
80
0
0
P
180
110
_ 0
70
SOILED UTILITY
760
AHU -6
TU -32
2
30
10
130
N
130
0
200
-70
229A
TOILET ROOM
120
AHU -6
TU -33
0
0
10
20
N
0
0
70
-70
229
PATIENT ROOM
1640
AHU -6
TU -33
6
170
0
0
P
250
180
0
70
231
PATIENT ROOM
1640
AHU -6
i
TU -34
6
170
0
0
P
250
180
0
70
231A
TOILET ROOM
120
AHU -6
TU -34
0
0
10
20
N
0
0
70
-70
235A
TOILET ROOM
120
AHU -6
TU -35
0
0
10
20
N
0
0
70
-70
233
SUPPUES
80
AHU -6
TU -35
0
0
0
0
NA
50
50
0
0
235
PATIENT ROOM
1640
AHU -6
TU -35
6
170
0
0
P
250
180
0
70
237
PATIENT ROOM
1640
AHU -6
TU -36
6
170
0
0
P
250
180
0
70
237A
TOILET ROOM
120
AHU -6
TU -36
0
0
10
20
N
0
0
70
-70
241A
TOILET ROOM
120
AHU - 6
TU - 37
0
0
10
20
N
0
0
70
- 70
241
PATIENT ROOM
1640
AHU -6
TU -37
6
170
0
0
P
310
240
0
70
242
FUTURE PATIENT ROOM
1640
AHU -6
TU -39
6
170
0
0
P
250
180
0
70
242A
TOILET ROOM
120
AHU - 6
TU - 39
0
0
10
20
N
0
0
70
- 70
238*
TOILET ROOM
120
AHU -6
TU -40
0
0
10
20
N
0
0
70
-70
238
PATIENT ROOM
1600
AHU -6
TU -40
6
160
0
0
P
240
170
0
70
236
PATIENT ROOM
1600
AHU -6
TU -41
6
160
0
0
P
240
170
0
70
240
EQUIPMENT STORAGE
120
AHU -6
TU -41
0
0
0
0
NA
50
0
0
0
236A
TOILET ROOM
120
AHU -6
TU -41
0
0
10
20
N
0
0
70
-70
232A
TOILET ROOM
120
AHU - 6
TU - 42
0
0
10
20
N
0
0
70
- 70
232
PATIENT ROOM
1600
AHU - 6
113
6
160
0
0
P
240
170
0
70
230
TOILET ROOM
400
AHU -6
TU -43
0
0
10
70
N
0
0
70
-70
228
SHOWER
1480
AHU -6
1U -43
0
0
10
250
N
165
0
235
-70
226
JANITOR
120
AHU -6
TU -43
0
0
10
20
N
0
0
70
-70
239
EQUIPMENT STORAGE
320
AHU -6
TU -43
0
0
0
0
N
0
0
70
-70
234
JANITOR
120
AHU -6
TU -43
0
10
0
0
N
0
0
70
-70
243
EQUIPMENT STORAGE
120
AHU -6
1U -43
0
0
0
0
NA
50
50
0
0
CORRIDOR
4880
AHU -6 _
TU -38
4
490
0
0
P
490
0
0
490
1.
NOTES
E= EQUAL, NA = NOT APPLICABLE
P = POSITIVE, N = NEGATIVE,
•
• •
•
• •
lb
- - :
•
RECEIVED
CITY NA
AUG 18100i
PERRI CENTER
I one wutart I
SCHEDULES - PIPING AND HVAC
REVISIONS
0$
2201 SIXTH AVENUE
SUITE 1405
SEATTLE, WA 98121
(206) 441 -4522
FAX (206) 441 -7917
NAC No. 2 -06005
FILE
DRAIN
CHECKED
DATE 7 -28-06
•
M
0.2 1
C ?rif iw#..tskc1 last G PS
i 12844 MIL
•
•
•
1
•
D
g
g
z
0
ci?
m
e
a
81" 2g
PR a
gi
•
1••
HIGHLINE MEDICAL CENTER, SPECIALTY CAMPUS
i • •
I - ..
•
REGIONAL HOSPITAL
2W HVAC UPGRADES
12844 MILITARY ROAD SOUTH, TUKWILA, WA 98168
I
i '�
t
1r� • ' •
I /
•
•
r'y
..
•
cop
1
I
1I
I
•
L,1
L.rT------ - - - - -- + r+
1
I
� r--- w--- r - - - - -
I •• .., ')
bi b t...
1 1 1
;11
• . —....- I 1
t 1
I 11
I;
1 1
II
•
rr • — — — • — • — • • • IM — '
1
1 1 II
;'
I�w
I •I
KN
1
I o
15
na
I . •
•
ro
I I - -•
MWR • f � ', WR
Hw
I - { � y,V
MA
HARGIS
•
J •
•
KO MIMI Mil
w .000
w.•w1, «,a
02
MV
rAV
Qr
SearaseaS
8/8011101 • loloomitracollare
r,
1 II
1 1
• I t
I I 41 w-------- .ww�w.w.w
L 41. � ,
- .1 IMO. - - - - - --
I
HMV
MA
. - T ;
•J
• 1 ■
•
i
Hw,
HWn^ �•- 1 •
-- - MV --
• 1
i
I;
,! 1 1
N
A c 0
g c
2
I 1
1 1
RG-1 "
1
150 r �7
1 l
_ 1 1
FC ' 1 1
1
a • •
CD -
150
85
) - 1
:_� .7 -3 T( =
9x6
-r-- - - -- -r te
1 20x9 : � 18x9 E 1
1
225
_00 ;
•
-7 w • i
1 1
1 1
1 1
1 1
1 1
1
1 1 • • CD -1
r= :�1 RG -1 • , 160
_-
Ft
-1 I. - -� 270 r'
e � EG -1
at: J
CD- 1
CD -1 x -1!'1' 165
165
T " �
35•
_. CD -.1
160
CO
x
to
1• a 14 k
t % \ ti - - -- EG-1
. iv r - t� 4 -r" � -.:L � j. x,
>- 1 12x71 � . - . -
- - ' %ra•) w -i %
, 1 \
V --
CD -1 '-
165
E--1
CD -1
fix, 200
16x9 -
RG =1
RG -1
1 1
1 1
I 1
1 1
1 1
1 1
1 1
1
r -
270 L` 7 •
270
V —#
1 1
/
T T
.T 1 J-
1.
'slit/AO-1
0
a .
_
1- -1
— r — r
FC-1
L_
11
- .1- -1- --- - , ' -
1 1
TT
RG -1
270
10
x
0)
/- -1
1
1120 '1 • < ``
\
'1= CD -1-
1iN 160
I IL' i — 7 _- _ 1 I _z -- -..,, ♦` I - I- - - - <- - - -. •
/ . Z- - -� }� r- t. • I %i —r —j• •- %
i Pi ~Et:- -.- t
• I 1 •
1 I • •
1 • •
1 ° • EG -1 1
1 j j - r l. T 55 - 1
1 1 1 ; ; � ' .1 . 1 1 CD - 1
:-4- -I- t,_ T ' i y _ 165
_ � 1 0x6 10x6 11 _ . `' � lizzii
N
ICD DEMOLITION PLAN - HVAC
Scale: 1 /4" = 1' -0"
•
165
CD -1
CD-1 1 11 1
460
CD -1
200
RG -1
k
-
I- 4 --
1
•
1
1
•
at
1
-L
8x5
• co-1
165
0 1 2 4 8
\
1
1
I- - 1 , i
-- - r te
1-271;7-
2x7 1 , A
t; 'i 1" wig zt
_ �
270 L` =.'J
E{
T-4
55
_ _ 1 _
L 1
I ` ;. RG -1 r - - u 1
z � ; i 270 L. !'a J
• 1:i -.CD -1 . • }.1
I I `- 160 ♦ ti- _ -r ,. - � /
. ' ; v i
-t�- .
-- 9x7 i • 1 N T i •+ (•�
- - -- r-? -_. J 1 --
1 1
FC -3
400
- ; T . T T /
11 1 1
1
1 1 1'1
1 1 V 1 1
r r =" 1 CD -1. ----- 1,'. I
1 1 225 d--11 1 1 r 11
1 r •
1 • 11
1 1 • •
! 1 '- %
� ` - •. is 1 -� , ` ; 1 1 ;`
f 1 r �
1
- - .C\'' -4
r r ` % `� 1 1 M811111:41
8.< r. I
. ; ��- L..1�` % 1
t1 't =1 \ 1
1
- 50 I- -I I • -
rr - -
s. s = -�I
1
1
1
Ir = —� 1
r; a , , 55 - - - - - -
T T r-
ffx4 _ -_�:., - - - - 6x4 - - -k =T►- - - -
i CD -1
•
/
40
x
0)
1-
1 1
/
TT � j
1 �
1 ,1% - `; ` • ,
.
/ \f - 1 '
1 I .
•
trao
k& CD -1
Il 225
225
1 1
1(01 •
i°' •
i
•
1 1
I I }�
Isit 0 iv I
GENERAL NOTES:
CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE
DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY.
INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN
ACCORDANCE WITH MANUFACTURER' RECOMMENDATIONS, CONTRACT
DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
FLAG NOTES:
DEMOUSH EXISTING TERMINAL BOX ALONG WITH AU. ASSOCIATED
SUPPLY DUCT AND AIR TERMINAL DEVICES.
DEMOLISH EXHAUST DUCT BACK TO MAINS AND CAP.
PRIOR TO DEMOLITION, OBTAIN AIRFLOW READINGS AND REBALANCE
SYSTEM AT COMPLETION OF CONSTRUCTION TO THESE MEASURED
AIRFLOWS.
CAP DUCT IN CEILING. DO NOT DISTURB ANY AREAS NOT IN THIS
SCOPE OF WORK. ABANDON REMAINING DUCT IN CEILING.
COORDINATE DEMOLITION OF EXISTING WORK AND CONSTRUCTION OF
NEW WORK IN ORDER TO MINIMIZE THE DURATION THAT BOTH THE
SOILED UTILITY AND CLEAN UTILITY ROOMS ARE OFFUNE.
COORDINATE CONSTRUCTION AND INFORM OWNER WHEN AND FOR
HOW LONG THESE ROOMS WILL BE OFFUNE.
r r
i L L•
! �:•—;
T•
•
RECEIVED
CRYOFT1IKVALP
AUG 2606
KIWI CENTER
Wit/2067 1
DEMOLITION PLAN - HVAC
I
REVISIONS
•
U
J �
a
W
eL
VI
W W
U
< O-
0
Z U
W O a
Z
J
2
0 Isla
OC N
2201 SIFXIH AVENUE
SU11E 1406
SEATTLE. WA 98121
(206) 441 -4522
FAX (200) 441 -7917
e4AC HO. 2 - 06005
FU
DRAM
OOCED
DATE 7 -28 -06
•
1 M
1.2
C .1 Soolt ,rr.ccr raf Cs PS
►;,;4 --
-_ -0
•
I 1 1
GENERAL NOTES:
FLAG NOTES:
1 -1/4" 1 -1/4"
CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE
DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY.
INSTALL ALL MECHANICAL EQUIPMENT AND APPURTDIANCES M1
ACCORDANCE WTIH MANUFACTURER' RECOMMENDATIONS, CONTRACT
DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
PROVIDE NEW PIPING AND MEDICAL GAS OUTLETS. OUAANTRY AND
LOCATION ARE SHOWN ON ARCH. SHEET A7_ REFER TO THE
APPROPRIATE' DETAIL FOR EACH ROOM.
SEE COIL D1STAUATIOIN DUAL ON SHEET M4.1.
SEE COOLR1G COIL CONDENSATE Dive DETAIL ON SHEET M4.1.
i;.
•
A {! w
11U-42 I
' -
ro:i
F'
2iw i
(TYP)
T=
;
1 1u-41
102
MA
N
(I) SECOND FLOOR PLAN - PIPING
Scale: 1/4" = 1' -0" o , 2 4 8
1091111111
1
I
7U-4o
I
I CI
.
• 3 . - . •
;.
f CALL
3/ 4 "'
1
; -
1
2-1 7
I 7U-37
11
PIPE RUNS UP WALL
FROM WALKWAY TO ROOF.
SEE SHEET M3.2 FOR
CONTINUATION.
241 i
f -J-3
1f
•
RECEIVED
cnvOFTI
w"::V , 3 C:.°
PERMIT CENTER
I MIES IMIJIM I
SECOND FLOOR PLAN - PIPING
REVISIONS
I
4.
2201 SIXTH AWNUE
SITE 1406
SEATTLE. WA 98
(206) 441 -4522
FAX (206) 441 -7917
No. 2 -06005
FR E
DRAM
CHECKED
` /ATE 7 -28-06
1 M
2.1
t •
FD
EG -1
70
fir
N
(0 SECOND FLOOR PLAN - HVAC
Scale: 1/4' = 1' -0'
0 1 2 4 8
61
EG -1
I D i
I11)-;37 I
24x18
1%4 OID I 191
GENERAL NOTES:
tZNUT1III
11
rsq
r
i
14x10
VOLUME
DAMPER
(TYP)
• DUCT STATIC
PRESSURE
SENSOR
RG -1 RG -1
170 170
14x10
RG -1 ` RG -1
180 180
20x14
FD
CD -1
165
Efl ELT
;70
CD -1
50
-., 39
ti1Tlagr.
FD «---
EG -1
• -.70
' 16x10
t.r =1r n :lot/
i �•
16x10 I .'
FLAG NOTES:
22x14 RA ABOVE
24x18 SA BELOW
CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE
DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY.
INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN
ACCORDANCE WITH MANUFACTURER' RECOMMENDATIONS. CONTRACT
DOCUMENTS. AND APPLICABLE CODES AND REGULATIONS.
DUCT SMOKE DETECTOR. FURNISHED AND POWERED BY DMSION 16,
INSTALLED BY DMSION 15.
SEE CEIUNG RADIATION FIRE DAMPER DETAIL ON SHEET M4.1.
SEE COMBINATION Fl RE /SMOKE DAMPER DETAIL ON SHEET M4.1.
SEE MR TERMINAL UNIT INSTALLATION DETAIL ON SHEET M4.1.
COORDINATE DEMOLITION OF EXISTING WORK AND CONSTRUCTION OF
NEW WORK IN ORDER TO MINIMIZE THE DURATION THAT BOTH THE
SOILED UTILITY AND CLEAN UTILITY ROOMS ARE OFFUNE.
COORDINATE CONSTRUCTION AND INFORM OWNER WHEN AND FOR
HOW LONG THESE ROOMS WILL BE OFFUNE.
r ^•1
L .-
•
•
4011.1-6
• 1
t
RECEIVED
CITvornimwILA
AUG 1 92'06
PERMff GOITER
SECOND FLOOR PLAN - HVAC
•
•
•
REVISIONS
0
ac
1
Ie�
2201 SIXTH AWN!lE
9 1E 1405
SEATTLE. WA 98121
(206) 441 -4522
FAX (206) 441 - 7917
P IAC NO. 2 -06005
DRAIN
��
DATE 7 -28 -06
M
3.1 ,
0 20/4 Striborse Amlierairat C. PS
i • •
I EF-2 1
I CHe—1
odi o
on
oC,
� I I
I P -1 I
•
CA
•
N
OD PENTHOUSE PLAN - PIPING AND HVAC
Scale: Mir 8' = 1' -0 0 2 4 8
16
PENTHOUSE
•
GENERAL NOTES:
FLAG NOTES:
CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE
DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY.
INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN
ACCORDANCE WITH MANUFACTURER' RECOMMENDATIONS, CONTRACT
DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
DUCTWORK SHOW IS DIAGRAMATICAL ONLY AND DOES NOT INCLUDE ALL
DUCTWORK EXISTING IN THE PENTHOUSE.
INCREASE MOTOR SIZE FROM 1 - 1/2 HP TO 2 HP.
INSTALL PIPE 12' ABOVE ROOF DECK.
DOWN TO AHU -1.
SEE SHEET M2.1
FOR CONTINUATION
CU try ' .�
�•• .. . s. •
1\41 61- I 6
PENTOUSE PLAN - PIPING AND HVAC
•
am OFTIMILP
AUG 1 8 2408
PERIATCENTEfs
Ions tom 1
REVISIONS
i
2201 9X1H AVENUE
SMITE 1405
SEATTLE. WA 98121
(206) 441 -4522
FAX (206) 441 -7917
NAC NO. 2 -06005
FTLE
DRAWN
CHECKED
DATE 7 -28 -06
M
3.2
C 24" .6cOmeraraf G PS
•
SP ABOVE
DRAIN PAN,
IN. WG
H,
INCHES
X.
INCHES
Z,
INCHES
-1
2
1
5
-2
3
1.5
6.5
-3 _
4
I 2
8
t
STEEL DUCT
ARE- RESISTIVE
THERMAL BLANKET
MATERIAL
RADIATION
DAMPER ASSEMBLY
NOT TO SCALE
RADIATION
DAMPER ASSEMBLY
INSTALLATION WITH STEEL DUCTWORK
DIFFUSER OR
GRILLE
INSTALLATION WITH FLEXIBLE DUCT (DUCTLESS SIMILAR)
CEILING RADIATION DAMPER INSTALLATION
DETAIL
•
1
0
(A)
(E)
(C)
DUCT
(D)
(F)
•
NOTES:
SUPPORT (TYP)
STEEL DUCT
CONNECTION
FASTENERS
RETAINING ANGLES, LAP OPENING 1" MINIMUM
AND COVER CORNERS OF OPENING.
CLEARANCE BETWEEN WALL AND SLEEVE BOTH
DIMENSIONS.
STEEL SLEEVE.
APPROVED COMBINATION FIRE /SMOKE DAMPER.
SECURE RETAINING ANGLES TO SLEEVE ONLY.
SECURE DAMPER TO SLEEVE.
CONNECT DUCT TO SLEEVE WITH BREAK -AWAY
CONNECTION (TYP).
ACCESS DOOR, SIZE TO MEET Al-11 REQUIREMENTS
(6x6 MINIMUM).
1. COMPLY WITH SMACNA FSRDIG AND MANUFACTURER'S
INSTRUCTIONS.
2. DAMPER FREE AREA SHALL BE MINIMUM 90% OF
AREA OF CONNECTING DUCT. INCREASE DAMPER
SIZE AND PROVIDE TRANSITIONS TO CONNECTING
DUCTS AS NECESSARY TO MEET THIS REQUIREMENT.
COMBINATION FIRE /SMOKE DAMPER
INSTALLATION DETAIL
NOT TO SCALE
DIFFUSER OR
GRILLE
FLEXIBLE DUCT
ARE- RESISTIVE
THERMAL BLANKET
MATERIAL
CONICAL SPIN -IN FITTING
WITH VD (TYP)
ROUND BRANCH
DUCT (TYP)
EXTENDED PLENUM
LOW PRESSURE
FLEX DUCT (TYP)
NOTES:
1. PROVIDE SHEET METAL ELBOWS TO RESULT IN STRAIGHT FLEX DUCT.
AIR TERMINAL UNIT INSTALLATION DETAIL
NOT TO SCALE
EUMINATE BYPASS LEG AND
BALANCING VALVE FOR TWO WAY
CONTROL VALVE INSTALLATIONS
NOT TO SCALE
NOTE 1. (TYP)
DIFFUSER (TYP)
30" MIN
HEATING COIL
MANUAL AIR VENT
30" MIN
COIL
FU LL LENGTH OF BOX
OR 30 " MIN
CLEAR ACCESSIBLE SPACE
BY FULL HEIGHT OF BOX (TYP)
CONTROLS
STRAIGHT SHEET METAL
DUCT AT BOX INLET,
LENGTH =24" OR 3 DUCT
DIAMETERS, WHICHEVER IS
GREATER. SIZE TO MATCH
TU INLET SIZE. FLEX DUCT
IS ALLOWED PER GENERAL
SHEET METAL NOTE #11.
INSULATED DRAIN PAN
(COOLING COILS ONLY)
DRAIN PLUG
DRAIN TRAP AND PIPING
SEE DETAIL
NOTE:
ARRANGE PIPING TO BE CLEAR
OF COIL REMOVAL SPACE.
NOTE:
1. AHU -1 COIL PIPING SHALL BE CONFIGURED WITH THREE -WAY CONTROL VALVES.
SINGLE WATER COIL INSTALLATION DETAIL
(r
REDUCER TO BOX
INLET SIZE
BRANCH
DUCT SIZE
6"
7"
8"
9"
10"
12"
NOT TO SCALE
CONDENSATE DRAIN PAN AND
PIPE OUTLET CONNECTION
REMOVABLE CLEANOUT
PLUG OR CAP (TYP) -
6" L OPEN VENT
INVERT (OUTLET) -\
INVERT
NOT TO SCALE
"X"
DIMENSION
13"
14"
15"
16
17"
19"
i
a
L- TO DISPOSAL POINT WITH
1" AIR GAP (FLOOR DRAIN,
SERVICE SINK, ETC, AS
INDICATED)
(B) GALVANIZED STEEL DIFFUSER
OR GRILLE BOX.
(C) SECURE TO DIFFUSER OR GRILLE
NECK WITH SHEET METAL SCREWS,
MIN. ONE PER SIDE OR EVERY 90
DEGREES; SEAL AIR TIGHT.
AUTOMATIC
AIR VENT
l"" T� FLOOR
G DRAIN
-L DRAIN
NOTE
PROVIDE AT HIGH POINTS
IN MECHANICAL ROOMS
& WHERE INDICATED
AUTOMATIC AIR VENT DETAIL
SCALE: NONE
REQUIRED IN ALL MECHANICAL ROOMS ONLY
NOTES
(A) CEILING DIFFUSER OR RETURN GRILLE (D)
CEILING DIFFUSER (CD -1), RETURN AND EXHAUST
GRILLE (RG- I , EG-1 ) CONNECTION DETAIL
rr
(E)
SP. INCHES WG-
L- EQUIPMENT
INDIRECT DRAIN PIPING, SIZE
PER CODE OR TO MATCH PAN
CONNECTION SIZE (WHICHEVER
iS LARGER)
DIFFUSER BOX, SUPPORT TO
STRUCTURE, 2 PER BOX.
EQUALIZING GRID FULL WIDTH OF
DIFFUSER NECK. PERFORATED 20
GA GALVANIZED STEEL WITH .156"
HOLES ON 3/16" STAGGERED
CENTERS (63% FREE AREA). TOP
AT HORIZONTAL CENTERLINE OF
BRANCH DUCT, BOTTOM AT 3"
BELOW BOTTOM OF BRANCH DUCT.
1/2" HEM EDGE TOP AND BOTTOM
3/4" 90' BEND EACH END AND
MINIMUM 3 SPOT WELDS, RIVETS
OR SCREWS TO BOX. EQUALIZING
GRID NOT REQUIRED FOR RETURN
GRILLES.
(F) BRANCH DUCT - INSULATED FLEX.
(G) DUCT COLLAR SECURELY ATTACHED
TO BOX.
•
•
(H) DUCT SUPPORT TO STRUCTURE PER
SMACNA HVACDCS AND AS SPECIFIED.
(I) TYPICAL CEILING (TEE -BAR
SUSPENDED CEIUNG SHOWN).
(J) UGHT FIXTURE (AS APPLICABLE).
NOTE CONDENSATE DRAIN PAN SHALL
POSITIVELY SLOPE DOWN TO PIPE OUTLET
CONNECTION TO RESULT IN FREE AND
COMPLETE DRAINAGE.
COOLING COIL CONDENSATE DRAIN TRA
INSTALLATION DETAIL
RECBVED
CT�f OFTLIKWiLli
AUG 13210»
PERMITCENTEh
DETAILS - PIPING AND HVAC
REVISIONS
11
111
N
ot
0
= 1<
1
no 51X*i AVENUE
SUM 1405
SEATRE. WA 98121
(206) 441 -4522
FAX (206) 441 -7917
RAV
HECK D
DATE 7 -28 -06
M
4.1
s arc •erskta ■xo f. PS
•
SEQUENCE OF OPERATION: CHILLED WATER SYSTEM
A. GENERAL
1. THE EXISTING CHILLED WATER SYSTEM CONSISTS OF ONE
AIR- COOLED CHILLER CH -1, SERVED BY ONE CHILLED WATER
PUMP P -1. CH -1 SERVES FOUR COOUNG COILS (CC -1 THRU
CC -4) IN THE EXISTING MAKE -UP AIR UNITS THAT SERVE
FAN -COIL UNITS THROUGHOUT THE BUILDING.
2. THE SYSTEM WILL BE EXTENDED TO SERVE CC -5 WHICH IS
LOCATED IN AHU -1.
3. THE CHILLED WATER SYSTEM SYSTEM SHALL CONTINUE TO RUN
UNDER THE EXISTING START /STOP PROCEDURE WHICH IS
NON -DDC.
SOUND ATTENUATOR
t'44+4
:44$144
I SA -2
MEDICAL GAS RISER
(E�AEO. A CM
PANEL
(E) SERVICE VALVES
MUST BE LOCKED OPEN
• •
EA DAMPER
I REF -1 I
SRN/
EXMMJST FAN
f
AIR HANDLING SYSTEM (AHU -6)
AIRFLOW AND CONTROL DIAGRAM
SCALE: NONE
(E) PRESSURE
SENSORS
MA
I
I
I
L
� - (E) ZONE
VALVES
OA DAMPER
0
RA DAMPER
L
rzca
CL
(t
l PATIENT ROOM I
AIRFLOW MEASURING
STATION
Q J
SCALE:
COOLING COIL
Lcc
-tI
SCALE NONE
I PATIENT ROOM I
PATIENT ROOM
SUPPLY FAN
AHU -1
FINAL FILTER
I CC -2 I
3" -
I PATIENT ROOM
I PATIENT ROOM
MEDICAL GAS PIPING DIAGRAM
cc -fl
SOUND ATTENUATOR
SA -1
I PATIENT ROOM I
•
I PATIENT ROOM I
I CC -4 I
CHILLED WATER AND CONTROL DIAGRAM
TERMINAL UNIT
TU -X
L ' . -..- •
ICHIRL PANELI- DOC INTERFACE
- T r
I PATIENT ROOM
I CC-5 1
(TYP)
•
SEQUENCE OF OPERATION: AHU -1
A. GENERAL
1. SYSTEM IS CONSTANT VOLUME WITH TERMINAL UNIT R
2. SYSTEM PROVIDES COOUNG, VENTILATION, AND SPACE
3. SUPPLY AND RETURN FAN MOTORS ARE CONTROLLED
MONITORED THROUGH CURRENT SENSORS IN THE VFD
4. AN ALARM IS ENERGIZED UPON FAILURE OF ANY DEVI
5. FILTER PRESSURE DROP SETPOINTS ARE (PREFILTERS
B. SYSTEM START /STOP:
1. PROGRAMMED SCHEDUUNG: AIR HANDUNG SYSTEM IS STARTED AND STOPPED BASED UPON PROGRAMMED
OCCUPIED AND UNOCCUPIED TIMES, WITH WEEKDAY, WEEKEND AND HOUDAY SCHEDULES. INITIAL SCHEDULE
CALLS FOR CONTINUOUS OPERATION.
2. DDC SYSTEM SHALL PROVIDE START /STOP AND SPEED CONTROL FOR EACH VFD. DDC SYSTEM SHALL MONITOR
THE FOLLOWING INPUTS THROUGH EACH VFD: KW, HERTZ, PERCENTAGE OUTPUT, STATUS, AND FAULT ALARM.
3. INTERLOCKING IS PROGRAMMED AS FOLLOWS:
a. RETURN /EXHAUST FAN IS INTERLOCKED WITH SUPPLY FAN OPERATION.
4. NORMAL SHUTDOWN: DAMPERS SHALL BE IN THE FOLLOWING POSITIONS WHEN UNIT IS OFF FOR ANY REASON:
a. OUTDOOR AIR DAMPER: CLOSED.
b. RETURN AIR DAMPER: OPEN.
c. EXHAUST AIR DAMPER (AHU): CLOSED.
d. CHILLED WATER VALVE: CLOSED.
5. SAFETY SHUTDOWN:
a. FREEZE PROTECTION CONTROL A HARD -WIRED FREEZE PREVENTION THERMOSTAT SHUTS DOWN THE AIR
HANDUNG UNIT AND CLOSES THE OUTDOOR AIR DAMPERS.
b. HIGH LIMIT DUCT STATIC PRESSURE (HIPS): SHUT DOWN AHU SUPPLY AND RETURN /EXHAUST FANS IF
SUPPLY DUCT STATIC PRESSURE EXCEEDS 3.5 IN. WG.; DDC AUTOMATIC RESET. AN ALARM IS ENERGIZED.
PRESSURE SWITCH SHALL BE ADJUSTABLE PLUS /MINUS 1 IN. WG.
c. LOW UMIT STATIC PRESSURE (CEPS): SHUT DOWN AHU SUPPLY AND RETURN /EXHAUST FANS IF RETURN
AIR DUCT STATIC PRESSURE EXCEEDS 1.5 IN. WG. NEGATIVE STATIC PRESSURE; DDC AUTOMATIC RESET.
AN ALARM IS ENERGIZED. SHUT DOWN AHU SUPPLY, RETURN /EXHAUST, AND EXHAUST FANS IF AHU
STATIC PRESSURE UPSTREAM OF THE COIUNG COIL EXCEEDS 3.5 IN. WG. NEGATIVE STATIC PRESSURE; DDC
AUTOMATIC RESET. AN ALARM IS ENERGIZED. PRESSURE SWITCH SHALL BE ADJUSTABLE PLUS /MINUS 1 IN.
WG.
d. FIRE ALARM: SUPPLY AND RETURN /EXHAUST FAN SHALL SHUT DOWN THROUGH THE FIRE ALARM SYSTEM
UPON A SIGNAL FROM DUCT SMOKE DETECTORS. (REFER TO DIV. 16)
C. AHU DISCHARGE AIR TEMPERATURE CONTROL:
1. ECONOMIZER DAMPERS AND CHILLED WATER CONTROL VALVE ARE CONTROLLED IN SEQUENCE TO MAINTAIN THE
DISCHARGE AIR TEMPERATURE (DAT) SETPOINT; INITIAL SETPOINT IS 56 F. THE DAT SHALL BE RESET BETWEEN
53F AND 59F AS DESCRIBED BELOW.
2. INCREASE DAT - THE DDC SYSTEM SHALL RUN A QUERY EVERY 10 MINUTES: IF THE DAT SETPOINT IS LESS
THEN THE MAXIMUM DAT SETPOINT (59F), AND THE LOWEST TU HEATING VALVE OUTPUT IS GREATER THEN 10
PERCENT; THEN INCREASE THE DAT SETPOINT BY 1F.
3. DECREASE DAT - THE DDC SYSTEM SHALL RUN A QUERY EVERY 10 MINUTES: IF THE DAT SETPOINT IS
GREATER THEN THE MINIMUM DAT SETPOINT (53F). AND THE LOWEST TU HEATING VALVE OUTPUT IS GREATER
THEN 5 PERCENT; THEN DECREASE THE DAT SETPOINT BY 1F.
4. DURING COOLING. THE ECONOMIZER DAMPERS AND CHILLED WATER CONTROL VALVE ARE CONTROLLED IN
SEQUENCE TO MEET THE COOLING REQUIREMENT.
5. ENABLE THE ECONOMIZER WHEN THE OUTSIDE AIR TEMPERATURE IS LESS THEN OR EQUAL TO THE RETURN AIR
TEMPERATURE MINUS 2F. DISABLE THE ECONOMIZER WHEN THE OUTSIDE AIR TEMPERATURE IS GREATER THEN
OR EQUAL TO THE RETURN AIR TEMPERATURE PLUS 2F.
6. A LOW UMIT CONTROL OVERRIDES ECONOMIZER CYCLE CONTROL TO PREVENT THE DAT FROM DECREASING
BELOW 50 F.
EH EAT.
PRESSURIZATION.
BY VARIABLE FREQUENCY DRIVES (VFDS). FAN STATUS IS
S.
CE.
0.9" WC. FINAL FILTERS 1.4" WC).
D. MINIMUM OUTDOOR AIR: FLOW IS MEASURED VIA THE AIRFLOW MEASURING STATION, AND MAINTAINED AT A CONSTANT
VALUE BY MODULATION OF THE OUTDOOR AIR DAMPER. MINIMUM OUTDOOR AIRFLOW: 1600 CFA.
E. FAN SPEED CONTROL: THE SUPPLY FAN SPEED SHALL BE CONTROLLED BY THE VFD TO MAINTAIN DUCT STATIC
PRESSURE SETPOINT, INITIALLY 1 IN. WG. THE RETURN FAN SPEED SHALL BE CONTROLLED BY THE VFD TO MAINTAIN
A CONSTANT AIRFLOW DIFFERENTIAL WITH THE SUPPLY FAN.
1. REF -1 DIFFERENTIAL: -1,600 CFM
F. ZONE TEMPERATURE CONTROL:
1. ZONE TEMPERATURE SETPOINTS SHALL BE 75F FOR HEATING AND COOLING.
2. THE MR TERMINAL UNIT PRIMARY AIR DAMPER REMAINS SHUT UNTIL THE AHU IS STARTED.
3. WHEN ZONE TEMPERATURE DROPS BELOW SETPOINT, THE HEATING CONTROL VALVE MODULATES TO MAINTAIN
SETPOINT.
4. THE HEATING WATER PUMP SHALL START AS REQUIRED WHEN ANY TU CONTROL VALVE OPENS AND CALLS FOR
HEAT.
CONTROLS LEGEND
MS
® VARIABLE FREQUENCY DRIVE
FLAG NOTES:
MOTOR STARTER
WD ALARM
AIRFLOW MEASURING STATION
CURRENT SENSOR
O FFERENTNL PRESSURE SWITCH
DUCT SMOKE DETECTOR
GENERAL NOTES:
e FOGH MIT PRESSURE SWITCH
WD HERTZ
FIER Z
VFD KILOWATTS
® LOW MIT PRESSURE SWITCH
MOTOR OPERATED DAMPER
WD SPEED CONTROL
STATIC PRESSURE SENSOR
CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE
DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY.
COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS'
CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL PIPING
TRANSRIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS.
PROVIDE AN AIR VENT AT THE HIGH POINTS OF ALL HYDRONIC
SYSTEMS. ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE
END DRAIN VALVES AT THE BOTTOM OF ALL RISERS AND AT LOW
POIMS.
PRCNIDE NEW PPM AND MEDICAL GAS OUTLET'S. QUANTITY AND
LOCATION ARE SHOWN ON ARCH. SHEET Al. RE TO THE
APPROPRIATE DETAIL FOR EACH ROOM.
1\4 o tf. t
•
START /STOP
TEMPERATURE CONTROL VALVE
TEMPERATURE 'TRANSMITTER
VFD PERCENTAGE
C
5
s
RECEIVED
CITYOFTIRCWILis
AUG 182G06
PERMITCENTEft
CONTROL ofAGRAMS
REVISIONS
(I1
w W
Z ~ Oo
U i g
Q J0
0 � �
� Z U
W 0 ` Q
J J /
6 W
2 Cr N
2201 SIXTH AVENUE
SUITE 1405
SEATTLE. WA 98
(206) FAX (206) 441 77917
lit
g ; si i
di
N
0
o
( ti*c No 2 -06005
111.E
DRAWN
CHECKED
0ATE 7 -28 -06
C'++K 13.-Aw v.GcaresrafC. PS
•
• go
2 WEST (EAST HALF).
3 WEST AND 4 WEST
FANCOIL UNITS
- - • - GNti.s
! BLEND PUMP t
1ST FLOOR LAB.
RADIOLOGY, AND
OPERATING ROOM
rx -
DELIVERY. LABOR
NURSERY
-F^
BLEND PUMP HWR
TEMP CONTROL
SCOIE: NNE
- --
HIS
BLEED VALVE
5
I BLEND PUMP
,
f
. E: - -E I.•
I
BLEND PUMP HWR
TEMP CONTROL
HEATING WATER PUMP (E)
IP -2I
NAMPLATE DATA:
GPM: 35 GPM
HEAD: 35 FT
2 WEST (EAST HALF).
3 WEST AND 4 WEST
FANCOIL UNITS
1ST FLOOR LAB,
RADIOLOGY, AND
OPERATING ROOM
- - —I
—1 --1
DELIVERY, LABOR
NURSERY
tusS
HwP) _ — [X1 ----'I
141 R)— —1><
r
: —
A L L TERMINAL BOX
COILS (iYP)
f_
TCV
HAS
r — Y.—
,r
•
HEATING WATER PUMP (E)
HWP -2
NAMPLATE DATA:
GPM: 410 GPM
HEAD: 32 FT
HEATING WATER PUMP (E)
[HWP -1
NAMPLATE DATA
GPM: 410 GPM
HEAD: 32 FT
HEATING WATER PUMP (E),
VARIABLE
GPM: 250 GPM
—So—
BYPASS
HEATING WATER AND CONTROL DIAGRAM
ALL TERMINAL
BOX COILS OW)
SEQUENCE OF OPERATION: HEATING WATER SYSTEM
A. GENERAL
1. THE EXISTING HEATING WATER SYSTEM CONSISTS OF HEATING WATER PUMPS AND 2 BOILERS.
2. NEW PIPING WILL BE ADDED TO 2 WEST EAST WING AND CONNECTED TO EXISTING PIPING
SERVING THE REMAINDER OF 2 WEST AND 2 NORTH.
3. NEW AIR TERMINAL UNITS SHALL BE INTEGRATED INTO THE EXISTING DDC CONTROL STRATEGY.
B. SYSTEM START /STOP: PROGRAMMED SCHEDUUNG: ALL EQUIPMENT SHALL CONTINUE TO RUN
BASED UPON EXISTING PROGRAMMED SCHEDULE.
•
GENERAL NOTES:
CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE
DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY.
COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS'
CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL PIPING
TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS.
PROVIDE AN AIR VENT AT THE HIGH POINTS OF All HYDRONIC
SYSTEMS. ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE
END DRAIN VALVES AT THE BOTTOM OF ALL RISERS AND AT LOW
POINTS.
r ..
171• - ..
tvt o
•
•
AIX "H 8 not
Iems Wutaw I
CONTROL DIAGRAMS
REVISIONS
•
i
E
4,
U)
0
U
a '
0 Q
W
U)
W gi
te l
U
—J V
< 0
to Z U
O '
J V 1
w
N
2201 91X1$ MIME
91101E 1405
SEAT1tE. WA 98121
(206) 441 -4522
FAX (206) 441 -7917
NAC No. 2 -06005
FILE
DRAWN
cHEaOD
DATE 7 -28 -06
5M2 1
C YelE.Volimar.45waseobrarCa PS'
•