HomeMy WebLinkAboutPermit M2000-252 - SOUTHCENTER MALL - NOR SUSHI AND GRILLM2000 -252
Nori Sushi &
Grill
896 Southcenter
Mall
• City of Tukwila (206) 431.3670
Community Development / Public Works • b300 Southcenter Boulevard, Suite 100 • Tukwila, Washington 98188
Permit No: M2000 -252
Type: B -MECH
Category: NRES
Address: 896 SOUTHCENTER MALL
Location:
Parcel *: 262304 -9004
Contractor License No: NORTHS *01681
INSTALL CLASS I HOOD.
aTrIT
Permit Center
MECHANICAL PERMIT
TENANT NORI SUSHI AND GRILL
896 SOUTHCENTER MALL, TUKWILA WA 98188
OWNER SOUTHCENTER JOINT VENTURE
ATTN:, 25425 CENTER RIDGE RD, CLEVELAND OH 44145 _
CONTACT DON ANGELINE Phone: 253 -606 -0525
9318 SR 162, PUYALLUP, WA 98374
CONTRACTOR NORTHWEST STAINLESS
14528 128th ST E, PUYALLUP WA 98374
***************,*************************** * * ** * * * * * * * * * * * * * * * * * * * * * ** * * **
Permit Description:
UMC Edition: 1997 Valuation:
Total Permit Fee:
�..
12. (0--
horized Signature Date
Status: ISSUED
Issued: 12/06/2000
Expires: 06/04/2001
6,500.00
51.75
*** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
1 hereby certify that I have read and examined this permit and know the
same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate
or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign for and
obtain this building permit.
Slgneture:A .__4_ . Date: +
Print Name: .= _,..,L ,. �t t? Title: amd/L t-�
This permit shall become null and void if the work is not commenced within
180 days from the date of issuance, or if the work is suspended or
abandoned for a period of 180 days from the last inspection.
Address: 896 SOUTHCENTER MALL
Suite:
Tenant: NORI SUSHI AND GRILL
Type: B-MECH
Parc41 #: 262304-9004
CITY OF TUKWILA
Permit No M2000-252
Status: ISSUED
Applied: 11/09/2000
Issued: 12/06/2000
A**********k*A*k***********k***A***k****A****Akkhk****k***********khk4***k*
Permit Conditions:
1, Readily accessible access to roof mounted equipment is
required,
2. Plumbing permits shall be obtained through the Seattle-King
County Department of Public Health, Plumbing will be
inspected by that agency, including all gas piping
(296-4722).
3. Electrical permits shall be obtained through the Washington
State Division of Labor and Industries and all electrical
work will be inspected by that agency (248-6630).
4. No changes will be made to the plans unless approved by the
Engineer and the Tukwila Building Division.
5. All permits, inspection records, and approved plans shell be
available at the iob site prior to the start of any con-
struction. These documents are to be maintained and avail-
able until final inspection approval is granted.
6. All construction to be done in conformance with approved
plans and requirements of the Uniform Building Code (1997
Edition) as amended. Uniform Mechanical Code (1997 Edition).
and Washington State Energy Code (1997 Edition).
7. Validity of Permit. The issuance of a permit or approval of
plans, specifications, and computations shall not be con-
strued to be a permit for, or an approval of, any violation
of any of the provisions of the building code or of any
other ordinance of the iurisdiction. No permit presuming to
give authority to violate or cancel the provisions of this
code shall be valid,
8. Manufacturers installation instructions required on site
for the building inspectors review,
9. The attached set of plans have been reviewed by The Fire
Prevention Bureau and are acceptable with the following
concerns:
10. Commercial-type food heat-processing equipment from which
grease-laden vapors emanate in normal cooking application
shall be protected by an approved automatic extinguishing
system. The extinguisher system shall be interconnected to
the fuel and current supply so that the fuel or current is
automatically shut off to all equipment under the hood,
when the system is actuated. (UFC 1006)
1i A wet chemical portable fire extinguisher having a minimum
rating of 2A:18:C:1( shall be installed within 30 feet of
commercial food heat-processing equipment, as measured
along an obstructed path of travel. (UFC 1006.2.7).
12. A fire alarm system is required for this project. The fire
alarm system shall meet the requirements of N.F.P.A. 72 and
City Ordinance #1900.
13. Local U.L. central station supervision is required, (City
Ordinance #1900)
A 4.. All new fire alarm systems or modifications to existing
systems shall have the written approval of the Tukwila Fire
Prevention Bureau. No work shall commence until a fire
department permit has been obtained, (City Ordinance
. #190(1) (UFC 1001.3)
5. Call the Tukwila Fire Department at 575 -4407 for approval
of any system shut down. Have lob site address. name and
•Tukwila Fire Department Job Number available to confirm
shut down approval. (City Ordinance #1900)
j Contact the Tukwila Fire Prevention Bureau to witness all
required inspections and tests. (UFC 10.503) (City
Ordinance #1900 and #1901)
17. All electrical work and equipment shall conform strictly to
the standards of The National Electrical Code. (NFPA 70)
18. This review limited to speculative tenant space only
special fire permits may be necessary.dopending on detailed
description of intended use. .
19. Any overlooked Hazardous condition and/or. violation of the
.adopted Fire: or Bui ldinq Codes does not imply apprcava1 of
such condition or Violation.
;THESE PLANS WERE REVIEWED BY .INSPECTOR 512 IF YOU HAVE
ANY OUESTIONS . `PLEASE CALL THE TUKWILA FIRE PJEVENTION
BUREAU AT (206)575 -4407.
I hereby oertifv that 1 have read these conditions and will comply
w i th : them e.s Outlined.' All P r o v i s i o n s of law and orci,i nances govern i na
this work will b e corplled with, whether specified hereinfor not,
The grertt:l ng o.? this permit does .not presume to g i v e author l tV t
v.l o l e to or cancel the provisions-of nnv' other work or local laws
roquletln9 construction or the performanoe of work.
Project Name/Tenant:
Signature
Date: ., pip
Print name: -
V lue of Mechanical Equipment:
Fax #: 1ZT ) / s- 3
Address:
Site Address :
City State/Zip:
Tax P c • I a • Atig
i .,
Property Owner:
Phone: (
Street Address:
City State/Zip:
Fax #: (
Contractor:
A/ Le >
r
S l�(, i ltd
.sS
Phone: (23 ) 4
.2 ? S
Street'Address:
Cit State/Zip:
Fax #: ( )
Cont t Person:
Phone: ( )
Street Address:
City State/Zip:
Fax It: ( )
BUILDING OWNER OR RUTH • RIZED ENT:
Signature
Date: ., pip
Print name: -
Phone: (?A) ec, 6° c al-
Fax #: 1ZT ) / s- 3
Address:
City / State/Zip:
Date applicrefcceo
Date applicatio
5-
xpires:
l
Application taken by: (initials)
CITY OF T; CWILA
Permit Center
6300 Southc:enter Boulevard, Suite 100
Tukwila, WA 98188
(206) 431 -3670
Mechanical Permit Application
Application and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or facsimile.
MECHANICAL PERMIT REVIEW AND APPROVAL REQUESTED: (TU RE FILLED OUT BY APPLICANT)
Description of work to be done please be specifi9:
Current copy of Washington State Department of Labor and industries Valid Contractor's License. If not available at the time of
application, a copy of this license will be required before the permit is issued OR submit Form H•4, "Affidavit in Lieu of Contractor
Registration ".
Building Owner /Authorized Agent: If the applicant is other than tho owner, registered architect/engineer, or contractor licensed by the
State of Washington, a notarized letter from ilia property owner authorizing the agent to submit this permit application and obtain the
permit will be required as part of this submittal,
I HEREBY CERTIFY THAT I IMYE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PER JURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
Expiration of Plan Review • Applications for which no permit is issued within 100 days following the date of application shall expire by
limitation. The building official may extend the time for action by the applicant for a period not exceeding 180 days upon written
request by the applicant as defined in Section 114.4 of the Uniform Mechanical Code (current edition). No application shall be
extended more than once.
11/2/99
'arch prrmis.doc
✓
Submittal Requirements
Floor plan and system layout
Roof plan required to identify individual equipment and the location o: each installation (Uniform
Mechanical Code 504 (e))
Details and elevations (for roof mounted equipment) and proposed screening
Heat Loss Calculations or Washington State Energy Code Form #H -7
H.V.A.C. over 2,000 CFM (approximately 5 ton and larger) must be provided with smoke detection shut-
off and will be routed to the Fire prevention division for additional comments (Uniform Mechanical
Code 1009).
Specifications must be provided to show that replacement equipment complies with the efficiency ratings
and other applicable requirements of the Washington State Nonresidential Energy Code.
Structural engineer's analysis is required for new and the replacement of existing roof equipment
weighing 400 pounds and greater (Uniform Building Code 1632.1). Structural documentation shall be
stamped by a Washington State licensed Structural Engineer.
Mechanical Permits
COMMERCIAL: Two complete sets of drawings and attachments required with application submittal
NOTE: Water heaters and vents are included in the Uniform Mechanical Code — please include any water
heaters or vents being Installed or replaced.
RESIDENTIAL: Two complete sets of attachments required with application submittal
Submittal Requirements
New Sin lgle Fam ily Resid
Heat loss calculations or Form I=1.G.
Equipment specifications.
Chan nge'nut or replacement of exlstin, mechanical e ul 'ment
Narrative of work to be done Includin modification to duct work.
Installation of Gies Flre lace
Narrative with specification of equipment and chimney type.
If using existing chimney, provide a letter by a certified chimney sweet= stating ih'ft the chimney Is in safe
condition.
NOTE: Water heaters and vents are included In the Uniform Mechanical Code — please include any water,
heaters or vents being Installed or replaced,
112/99
niscprLdac
z
1
O 0
2 w
O o
O a
8 St
:Y * ** * ** ** *s ******************** * ****** *****k * *******k * **** ***
1Y-OF ttfh WLts1 . WI.; r .. ' ' 1Kra ;yfh1 s
*
* *' * ** * * * ** 4 * * * **** * 24z ** * * * # * * * * * ** ** * * *** ** * * *1 **
40411.3M1I NUmbe"rt k9.1f0 401 Amounts . :il.la 12rQ6 /0t, L s :L%
tfnt Matnod CHECK. Notations 0001 ANOULLNE 1n. t;: mo
• .+ac. a *s...,. -.r.w
iteN 1; Bldg. M2000-252 rvngs U 'MECN MECHANICAL PERM, f
Pirct l tlo t ;62304 -9004
tssAddruuu s 096" 13Qt1 TNCEN TER MALL
total Venus 31. 3
: h t a °Fs visamyst 01.,75 lots! ALL Pmts s bL.7b
dnlans:ea .V0
* *** *44* *f►14##'* ** '*********** *11t *e****lr*tA'***A66* *1l#th** *fir *** *iY****
'Nucou .l: UosGr s ut i Fyn
000/345.030 PLAN CHECK — NuNREb
000/J22.100 MECHANICAL NUNRCS
a.—.Oft - - a --- — 4..a .a a. a.*1- •
051.2 1,2/08 9710 TOTAL
i
PERMIT NO.: AA i00045i.
MECHANICAL PERMIT APPLICATIONS
INSPECTIONS
❑ 00002 Pre•construction
❑ 00050 WSEC Residential
❑ 00060 WA Ventilation/Indoor AQC
00610 Chimney Installation/All Types
00700 Framing
01080 Woodstove
❑ 01090 Smoke Detector Shut Off
01100 Rough -in Mechanical
❑ 01101 Mechanical Equipment/Controls
❑ 01102 Mechanical Pip/Duct tnsul
12 01105 Underground Mech Rough -in
01115 Motor inspection
1400 Fire Final
01800 Final Mechanical
04015 Special -Smoke Control System
COND1TTO 4S
0001 No changes to plans unless approved by Bldg
Div
4,1e 0014 Readily accessible access to roof mounted
equipment
0016 Exposed insulation backing material
0019 MI construetlon to be done in conformance
w /approved plans
0002 Plumbing permits shall be obtained through KIng
Co
0027, Validity of Permit
0003 Electrical permits obtained through L, & 1
0036 Manufacturers installation instructions required
on site
"BTU maximum allowed per 1997 WA State Energy Code"
0041 Ventilation is required for all new rooms &
spaces
"Fuel burning appliances
"Appliances, which generate...."
"Water heater shall be anchored....
8
11
TENANT NAME:
FEES
Permit Tech:
Plan Reviewer liret
•
Basic Fee (Y/N)
Supplemental Fee (Y/N)
Plan Check Fee (Y/N)
Furnace/Burner •
to 100,000 BTU (qty)
Over 100,000 BTU (qty)
Floor Furnace (qty)
Suspended/Wall/Floor-mounted Heater (qty)
Appliance Vent (qry)
Heating/Refrfg/Cooling UniWSystem (qry)
Boiler /Compressor
to 3 HP /100,000 BTU (qry)
to 15 HP /500,000 BTTJ (qry)
to 30 HP /1,000,000 BTU (qry)
to 30 HP/1,750,000 BTU (qty)
over 30 HP/1,750,000 BTU (qry)
Mr Handling Unit
to 10,000 ctlm (qry)
over 10,000 cfrn (qry)
Evaporative Cooler (qry)
Ventilation Fan (qry)
Ventilation System (qry)
Hood (qry)
Incinerator - Domestic (qry)
incinerator — Comm/ind (qry)
Other Mechanical Equipment (qty)
Other Mechanical Fee (enter SS)
Add'I Fees — Work w/o Permit (Y/N)
Insp Outside Normal Hours (hrs)
Rainspections (hrs) .
Miscellaneous Inspections (hrs)
Add'1 Plan Review (hrs)
s
8 Y i , ��....
ns ecti , r
A o r r ` s+
eh C TP : " " '" --
Date aged:
2G ' o /
Special instructions:
Date wanted:
a.
Requester:
Phone:
& 3 ,., cfi
0 MENTS:
Receipt No:
Date:
Date:
Inspector '�.
$47.00 REINSPECTION FEE REQUIRED Prior to inspection, fee must be paid
at 6300 Southcenter Blvd. Suite 100. Cali to schedule reins ' ection.
INSPECTION NO
INSPECTION RECORD
Retain a copy with permit
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION J
6300 Southcenter Blvd, #100, Tukwila, WA 98186.___._... 206)431 -367
•
Approved per applicable codes.
Corrections required prior to approval,
"§
ea
IF ,.,
Ty e 4' Insp ction
:,
WA, ,
! ate oiled: 1 26
Special instructions:
Date wanted: 2.0
!
�•.
,
,,�
Requester:
/A
Phone:
42 -
/ �
A, ' :•
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd, #100, Tukwila, WA 98188
LJ Approved per applicable codes,
PERMIT NO.
(206)431 -3
Corrections required prior to approval.
$47.00 REINSPECTION ° E REQUIRED. Prior to inspection, fee must be paid
at 6300 Southcenter Blvd., Suite 100, CaII to schedule reins action.
Receipt No: Date:
1 g
r Ai,.rf' Y
Project Name
Address
o of
eg3 14 r j kr4- -4:4 i - 4- .Al+1Y'Ir S1Tn L4f' -JVid •;1J at tir ri 77';; 7'•. - ti
City of Tukwila
Fire Department
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL PORN
:
e; #411°
Retain current inspection schedule
Needs shift inspection
Approved without correction notice
Approved with correction notice issued
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
permits:
104? 0
Authorized Signature
FINAIJAPP . FRM
r
T 11•01•1
€ //ra / Ilan)
Permit No
l e ; l
T.F.D. Form F.P. 85
John W. Rants, Mayor
Thomas P. Xeefe, Are Chief
Suite #
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206 5754404 • Fax (206) 575409
Project: Ay
/70 4,5-.
4, '
Type ofIpectio;:
z ry., .... /I
_
Address:
Date call d:
Special instructions:
Date wante .
11
Phone:
ri Approved per applicable codes.
El Corrections required prior to approval.
COMMENTS!
:2-----,4inete.4ek
At.
.4
OM*
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd, #100, Tukwila, WA 9818
PERMIT NO.
(206)431-3670
$47.00 REINSFECTIO TEE REQUIRED. Prior to Inspection, fee must be paid
at 6300 Southcenter Blvd., Suite 100. Call to schedule reins ection.
. • i
•
Project: OY/ 5OA;
Ty.e of Inspection:
Address:
(4 5 W ce� , fir Mal
bat all d:
/'1l0/
....
Special instructions:
6 0-1 ?" 1,14
/4"---74)
Da t wanted:
,),
—_�._
( a, m.
R +u star:
'
:
Phone:
Approved per apptIcab1 ed ,
COMMENTS:
INSPECTION RECORD
Retain a copy with permit
INSPECt10RNO,
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd, #100, Tukwila, WA 98188
4.�
PERMIT NO,
(206)431 -3670
Corrections required prior
approval.
$47,00 REINSPECTIO ' FEE REQUIRED, Prior to Inspection, fee must be paid
at 6300 Southcenter Blvd., Suite 100. Call to schedule reins • action.
Project:
Type o spectio•: ..
Addres ,
D.te called:
Special instructions:
. ate wan ed:
Request .r:
Phone:
INSPECTION RECORD
Retain a copy with permit
INSPtCtION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd, #100, Tukwila, WA 98188
Corrections required prior to approval.
Approved per applicable codes.
0 $47.00 REINSPECTIO FEE REQUIRED. Prior to inspection, fee must be paid
at 6300 Southcenter Blvd, Suito 100. CaII to schedule reins action.
PERMIT NO.
(206)431-3
Project: / c , •
fvfy, ._)6/3„,/ ....
e of Inspection: -
Address:, --..,
X16:$ (1 50,
D e
/ (, 0 /
Special instructions:
X pi clay IP atiouick
0( a r/I vet/
Date w nted:
0/
a.m.
.m.
pippiter:
P one:
- 1) -
44,
COMMENTS:
Date:
E3 $47,00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be paid
at 6300 Southcenter Blvd., Suite 100. Call to schedule reins ection.
Receipt No:
Date:
. INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd, #100, Tukwila, WA 98188
Approved per appl codes,
Corrections required prior to approval.
PERMIT NO.
(206)431-3670
project: -
GY t USat
Typ o
Insp • etion: '
CrITd Wit(
• dress:
—D S o * t'
t
Date cal at:
1Z -x--00
Special instructions:
Date wanted'
Requeste
Ph' '7Cft , Gb — 9 I 05
INSPMCBION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd, #100, Tukwila, WA 98188
INSPECTION RECORD
Retain a ropy with permit
(206)431-3670
Approved per applicable codes.
Corrections required prior to approval.
7.00 REINSPECTIO 'TAE REQUIRED, Prior to Inspection, fee mutt be paid
at 6300 Southcenter Blvd., Suite 100, Call to schedule reinspec
Receipt No; Date;
Fam
EAliiiil
PGalliii
r i l
61
tt-,.,k.:,:f1.:;:..:,:i, .;
r
131.i
Pr
131
IM M Iatra J
eswort
MI s 211 a
• 1 l*AI K 1! NIM S OM m
pal
mail 1, ,t 1,i: i '• � /. • �. •
j • t
.LM.n
Willi 1 1a r fo
RErinsrowip
el1
OCT.10.2000 11:08AM
Fi1'p!MtiatCPe FAStWl'iij+
Commercial Kitchen Grease Duct Pare Protection System
Product Dots
endosun for
MOM
combustibles
WM" 1000 WO
�oa�n� bin � Ma�r'wh.n�
CAPTIVE AIRE
r * low �IMM no
used Aor �Nowarl w�fw�, lire
rMM►tt to Mr! mie0 ,M*
ttM PIreee MNr Frost ripr.
AM ON* to Poe Iln we
%lib Its mrooNent
or oder kb oasnaclid
r�r a�nrr
Male t used ki dor I 1.4
shahs **wino dial when It
wide end Noah
rroallle: Posittlso
• LOW bloperslellint klauMt on blanket
• NW eliernotlio
• Zero Ito oarless*** protection it lhs
• WOO" 04MPsot destan t
• Pledbla *quints Oilman Mbar
• Problsm S OW tar light congested ariii
• rn
.nWemuvs
kitchen wpm nN o whour dud*,
F eletarwe
o prattles or F�Uo
r ti .p►.a unstop
tiro nerd wiser and float
YL1zb 2S2
S, Physical Import is
MO.789 P.1
4 BpwoWloatfon$
FIr lor 10 o" r�►�tw and 000 w18
Moons 11AMIN1t
OA NroNsW restW should be Welled In
moarde w1 tt* Marian Initiations on the
=aerPitifitterretwoaduciil d ,w s ha Mm Ind MMi should be *WPM P IA I M FI~er risiWnop+,
r, Paelonn.rtaa
A,1'ypioal P11yduI Popertles
iM pIIMAoiMr PopkWrops.
Calor: Milo
ris0 p m wide roll olb45
0" , 18 m) wide roll 41 ta• ,o)
FIMIIIUPU ly (*$1M 1 MIL 70)
Polk Flume mod 8
pilwNM' Fevre 0 0
Them* Ileeleieneo
Ft VOW per ASV 0 518; 4.14 pvr inch (0,10 m) at
ACTIVITY NUMBER: M2000 - 252 DATE: , 11 -9-2000
PROJECT NAME: . .NORI SUSHI AND GRILL
SITE ADDRESS: _._896 SO SUITE NO:
_,Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter # i ,
_Revision If After Permit Is Issued
DEPARTMENTS:
Building givision
Public Wo ��
DETERMINATION OF COMPLETENESS: (rues,, Thurs.)
Incomplete
Complete
Comments:
TUES /THURS ROUTING:
Please Route
Aft,
PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
Fire Prevention El
MAX. II -LV•W
Structural
Structural Review Required
REVIEWER'S INITIALS:
A_RSZY 1.F CDERE.CTI N : (ten days)
Approved L__.. Approved with Conditions
REVIEWER'S INITIALS:
CO EST, ON D E M NA ON:
Approved L Approved with Conditions L
REVIEWER'S INITIALS:
Planning Division
Permit Coordinator
lir
DUE DATE: 1 1
Not Applicable
No further Review Required
DATE:
DUE DATE 12- 12-2000
Not Approved (attach comments) E1
DATE:
DUE DATE .....
Not Approved (attach comments) LJ
DATE:
,
•
:: .:
I'
Apt t ,t
rb i' i. tLi 't"�x. ';!' ?; of'Efri' uluf -S
i Ara 5PAc.0 - :=
MEJAL
g{{'FT 'Dir t tei ti.
Ct~as5_.' •NooV
I understand that the Flan f ie K e rip ^ l:a+s c.re
subject to errors and or;isski as a ci- a pprevaPof
plans does not authorize the vlolat,on of any
adopted code or ordinance. Receipt of con:-
tractor's copy of approved plans'ackr owteec & d
1,s cA: a
00144 W*FP.21
•
wAt.G 9ff' S 1'
'Zoe F f e i e N i o` FI 3,r*
ra«e irt 1kri -4 t. F •
are. pe , . Li J ) ,.
Date : 2'..6
Permit No /
SEPARATE PERMIT
REQUIRED FOR.
OyIECHANIOL
E-LECTRi,CA•L'
❑. PLUIMEBING
0 OAS. PIPING . .::.. .
CITY OF TUKWILA
BUILDING DIVISION
j,IZE� c CV
(.41' •
PICT EP,
e e
we
P >
to
CAftilac.1Vfz I1
— .. /UO1 vtiE4..7T 6a 6
LY 5.2'112
t'p ALwP, :..
'`. n olz,Tri4 0.1 /oar >.
R V SJONS
OF 'WON< WITHOUT PR'.!Or'.
(v'AL 0 lt
Tilt � .A' BOIL D1,I�afl O!r..
•
, tL
A D MAY Iier.LUL AD DiTiot AI PLRtdHE.y E Ei i ':
DIFFUSER, GRILLE & REGISTER SCHEDULE
EQUIP
LETTER
SERVICE
MOUNTING TYPE
DESCRIPTION
ACCESSORIES
FINISH
MANUF
MODEL NO
A
SUPPLY
LAY –IN
24 "x24"
OPPOSED BLADE DMPR
WHITE
TITUS
TMSA
8
LINEAR
SURFACE
24"
- --
WHITE
TITUS
ML -39
C
RETURN
LAY –IN
24 "x24"
____
WHITE
TITUS
50F
D
RETURN
LAY –IN
12 "x12"
____
WHITE
TITUS
50F
AIR BALANCE SCHEDULE
UNIT SUPPLY RETURN OUTSIDE
NUMBER - AIR AIR AIR
EXHAUST NOTES
AIR
RTU -1 2655 1930 725
- -- –
EF -1 - -- - -- - --
3625 –
MUA -1 2540 - -- 2540
- -- –
TOTAL 5195 1930 3265
3625 –
1. EF -1 AND MUA -1 PROVIDED BY KITCHEN CONTRACTOR.
2. BUILDING NEGATIVE PRESSURE 360 CFM.
3" PVC AIR INTAKE
&3"PVC FLUE
EXHAUST UP TH,!J ROOF
MECHANICAL NOTES:
LANDLORD NOTES:
HVAC PLAN
1/4=1'-4 "
EXHAUST HOOD
PROVIDED BY KEC
EXHAUST FAN
PROVIDED BY KEC
18 ° x16 ° DUCT
UP TO EXHAUST FAN
MAKE –UP AIR UNIT
� PROVIDED BY KEC
SMOKE DETECTOR IN SUPPLY
AR AND RETURN AR DUCT
26"x27' RETURN AIR
OPENING
12"0 DN WITH
BALANCING DAMPER (TYP)
1. FIRE SPRINKLER, FIRE ALARM, AND ROOFING WORK BY LANDLORD'S CONTRACTOR AT TENANT EXPENSE.
2. FLEX DUCT SHALL BE PRE INSULATED WITH 1 -1/2" THICK FIBERGLASS, 1/J DENSITY FLEXMASTER OR EQUAL. PROVIDE
SPIN –IN FITTING WITH INTEGRAL VOLUME DAMPER AT EACH TAP. MAXIMUM FLEX RUN – FIVE FEET (5' -0").
3. FINAL AIR SYSTEM TESTING AND BALANCING SHALL BE PERFORMED BY THE TENANT'S DESIGNATED CONTRACTOR.
4. UTILITIES ARE AVAILABLE AT DESIGNATED LOCATIONS WHICH MAY NOT BE IN THE DEMISED PREMISES. COORDINATE
THE FINAL CONNECTION OF ALL UTILITIES WITH THE LANDLORD'S FIELD REPRESENTATIVE.
5. MECHANICAL CONTRACTOR SHALL PROVIDE AND INSTALL DUCTWORK (BLACKIRON WIELDED DUCT) & EXTINGUISHING
SYSTEM PER NFPA 96. PROVIDE ANSUL TYPE SYSTEM IN ALL EXHAUST HOODS, PROVIDE SPRINKLER HEADS &
ACCESS IN EXHAUST DUCTS AS REQUIRED BY NFPA 96.
6. ALL WORK, EQUIPMENT, AND INSTALLATIONS SHALL CONFORM TO ALL APPLICABLE CODES.
7. FIELD VERIFY LOCATION OF ROOF OPENINGS IN CONJUNCTION WITH EXISTING ROOF STRUCTURE.
8. ALL CEILING PLENUM CAVITIES SHALL BE PLENUM RATED FOR CEILING PLENUM RETURN AIR PASSAGE WAY.
9. PROVIDE APPROVED FIRE DAMPERS IN ALL DUCTWORK RUNNING THROUGH FIRE RATED WALLS, FLOORS AND ROOF.
0. ALL AIR INTAKES LOCATED ON ROOF TO MAINTAIN A 15' -0" SEPARATION FROM EXHAUST OUTLETS.
1. ALL PIPING SHALL BE INSULATED INCLUDING WASTE PIPING SUBJECT TO COLD WATER WASTE, CONDENSATE, ETC.
2. TENANT MUST USE A LANDLORD APPROVED ROOFING CONTRACTOR FOR ALL ROOF PENETRATIONS.
3. ALL HVAC WORK TO BE PERFORMED IN COMPLIANCE WITH LOCAL CODES AND LANDLORD CRITERIA.
4. TENANT IS RESPONSIBLE AT JOB COMPLETION TO HIRE INDEPENDENT AIR BALANCE CONTRACTOR TO BALANCE SPACE
AND SUBMIT REPORT TO LANDLORD.
5. OBTAIN "TYPICAL TENANT DRAWINGS" FROM LANDLORD'S TENANT COORDINATOR PRIOR TO BID.
SENS. LOAD
TOTAL LOAD
TOTAL CFM
ROOFTOP AIR HANDLING UNIT SCHEDULE
MFGR- & MODEL CARRIER 480J0007 (6 TON)
CFM 2655
SP 0.5"
H.P SEE ELEC
VOLTAGE SEE ELEC
ENT. DB 77.5
ENT. WB 63.1'
OPERATING WEIGHT 680 LBS
SPACE LOAD CALCULATIONS
DESIGN TEMPS
SUMMER
84 DEG F
65 DEG F
75 DEG F
OADB
0.A.W.B.
IADB
GAINS
ROOF LOAD BTUH
GLASS LOAD - -- 8TUH
WALL LOAD - -- BTUH
LIGHTS 7336 BTUH
PEOPLE 6
PEOPLE (SENS) 1467 BTUH
PEOPLE (LAT) 1620 BTUH
MISC. EQUIP. 46912 BTUH
VENT. HEAT GAIN', 6949 BTUH
788
WITH ROOF CURB & ECONOMIZER
OUTSIDE AIR CFM 725
SENSIBLE M.B.H. 63.30
TOTAL M.B.N. 77
HEATING CAP 56.83
LEAVING DB 55.1
LEAVING WB 53.1
WINTER
0.A.D.B. 21 DEG F
I.A.D.B. 70 DEG F
LOSS
1976
NOTE:
BTUH
BTUH
BTUH
37835 BTUH
64632 BTUH HEAT REQ'D, 39811 BTUH
69553 BTUH VENTILATION 725 CFM
2655 BTUH
SZ
HVAC SYMBOLS
NEW DUCT
EXISTING DUCT
X
RETURN GRILLE
0 THERMOSTAT
BALANCING DAMPER
POINT OF CONNECTION
e
SUPPLY DIFFUSER
FACE MOUNTED VOLUME DAMPERS SHALL BE USED IN GYPSUM CEILIINGS.
BALANCING DAMPER
W/ LOCKING QUADRANT
FLEXIBLE DUCT,
5 FT. MAX. LENGTH,
MAX. ALLOWABLE
OFFSET FROM
CENTERLINE TO BE
HALF OF NECK
DIAMETER
ROUND RIGID DUCT
�■IIIII"I' ®'
i
DIFFUSER —�
NOTE:
— CONICAL TAKEOFF
SUPPLY DUCT
7
— FLEXIBLE DUCT
TOP DETAIL IS TO BE FOLLOWED WHEN CENTERLINE OF
DIFFUSER I5 UNDER THE DUCT ENOUGH TO PERMIT
A BOTTOM TAKEOFF WITH A FLEXIBLE DUCT OFFSET
OF LESS THAN HALF THE NECK DIAMETER. BOTTOM
DETAIL TO BE USED IN ALL OTHER CASES.
CEILING DIFFUSER RUNOUT DETAIL
NO SCALE
— WORM DRIVE CLAMPS
OR DRAWBANDS AND
ADHESIVE
Name
Date
Registra
118A0 PLAN
General Notes
Revision /Issue
Dunham Associates Consulting Engineers
8200 Normanda6 600, #500
Minneapolis, MN 55437 -1075
Tel: 952420 -1400
Fax: 952- 820 -2760
OunhareAssociates.com
Certification.
I hereby certify that this drawing
was perpared by me or under my
direct supervision and that I am
a duly Licensed Professional
E ngineer unde ,.s- ° ne
State of W e,2r f
SLgnalur��
NOFIO SUSHI
SOIPTd8CB94TE8
NAME, WASHON8TON
ON A
Date
J. CGHO DEMON INC.
WIVE 204, 8901 WOODBINE AVE.
88868894, ON, CANADA LER 9M4
488,.: (909) 949-1783
FAX: (905) 948 -9790
J
(
400995.08
Date
5119818, 2000
Scale
\ 1/4" =94"
Sheet
941
1
OEt4 E
I!,LcL
NO.
I NA...AL
TAG
1 .1\AI
PACKAGE #
-T.7
LOCATION
SWITCHES
ROOFTOP
STARTERS
OPTION �
FANS CONTROLLED
LOCATION
QUANTITY
TYPE
0
H.P.
VOLT.
1
Q
31111000
Utility Cabinet Left
Hood # 1
Utility Cabinet Left
1 Light
1 Fan
BLOWER
J
Exhaust
3
1,500
208
NRTPB
080245
44 -3/4
30 -1/2
36
25
29
25
Supply
3
1.000
208
RTP
MODEL
EXH
FAN
AE
CE
A
B
C
D
F
G
H
L
M
N
P
Q
R
S
T
FILTD SIZE ER QTY
AN
BLOWER
J
K
j V
W
MAX:: WEIGHT
NRTPB
080245
44 -3/4
30 -1/2
36
25
29
25
104
32 -1/2
14
75
20
32 - 1/2
34
42 -1/2
59
23
6
TWO
20' x 25°
G -12
13 - 3/4
15 -7/8
N/A
N/A
780 LBS
NO,
PpN
ITEM
SIZE
UTILITY CABINET(S)
FIRE SYSTEM
1
# 1
Curb
32.500'W x 75.000'L x 20,000 /20.000'H Insulated
Vented
QTY
Rail
6.000'W x 33000'L x 20.000'H
QTY
TYPE
Rail
6.000'W x 33.000'L x 20.000'H
TYPE SIZE
HOOD
NO.
y V FILTER(S)
LIGHT(S)
MAX.
COOKING
TEMP,
UTILITY CABINET(S)
FIRE SYSTEM
ELECTRICAL
SWITCHES -
FIRE
SYSTEMS
PIPING
HOOD
WEIGHT
TYPE
QTY
HEIGHT
LENGTH
QTY
TYPE
C UTARD
LOCATION
TYPE SIZE
MODEL #
QUANTITY LOCATIQN
1
Alum. Baffle w/ Handles
1
16'
16'
5
Incandescent Lights
NO
Left
Ansul R -102 3.0/3.0
- 31111000
1 Light
1 Fan Outside
YES
898
LBS.
8
16°
20'
HOOD
NO.
MODEL
LENGTH
MAX.
COOKING
TEMP,
EXHAUST PLENUM
SUPPLY PLENUM
HOOD
CONSTRUCTION
HOOD CONFIGURATION
SWITCHES
ON HOOD
TOTAL
EXH. CFM
RISERCS)
TOTAL
SUP. CFM
RISERCS)
END TO
END
ROW
WIDTH
LENGTH
CFM
S.P.
WIDTH LENGTH CFM
S.P.
QUANTITY LOCATION
1
4824
ND -BR
6.
14' 00'
600
Deg,
3625
10'
16'
1813
- 0.520'
2538
NHMUA2,12B
7
430 SS
Where Exposed
0.500'
844
1.000
10'
16'
1813
- 0.520'
1 1
FAN
UNIT
NO.
1111 W1L31MIL,Ii.
FAN UNIT MODEL 8
EXHAUST FAN
SUPPLY FAN.
MODEL
TAG
CFM
S.P.
RPM
H.P.
0
VOLT
BLOWER
HOUSING
TAG
CFM
S.P.
RPM
H.P. -
- 0 '
VOLT
1
NRTP.B- NHMUA2.12 - G12 - CNU 245
CNU 245
1269
3625
- 1,000'
793
1.500
3
208
G12
NHMUA2,12B
7
2538
0.500'
844
1.000
3
208,
FAN
UNIT
NO.
FAN
UNIT
TAG
EXHAUST
SUPPLY
GREASE
CUP
GRAVITY
DAMPER
WALL
MOUNT
SIDE
DISCHARGE
GRAVITY
DAMPER
MOTORIZED
DAMPER
WALL
MOUNT
1
6.00'
YES
NO
2538
5.000'
36.000'
YES
1269
HOOD
NO
WIDTH
LENGTH
CHEESE
MELTER
SUPPORTS
TOTAL
SUPPLY
CFM
BOOT(S)
WIDTH
LENGTH
ANGLE
CFM
S.P.
1
6.00'
186.00'
NO
2538
5.000'
36.000'
Straight
1269
0.110'
5.000'
36.000'
Straight
1269
0.110'
48
m I 3600
Hood #1
® \
FAN
UNIT
NO,
BURNER
SIZE
BTU's
TEMP.
RISE
FREEZE
STAT
OUTSIDE AIR
OVERRIDE
TEMP.
SELECTOR
LOCATION
GAS
TYPE
1
12'
246694
90 deg F
/
YES
Unit
Natural
ANSI
FAN & L
SWITC
OOD INFORMATION
BACK RETURNS)
2' HIGH SUPPLY
COLLAR CONNECTION
7
27' TYP.
100W VAPORPROOF
INCANDESCENT LIGHT
HANGING ANGLE
EXHAUST RISER
i U.L. CLASSIFIED
BAFFLE -TYPE
GREASE FILTERS
SLOPED GREASE DRAIN
WITH REMOVABLE CUP
48'
EQUIPMENT
BY OTHERS
HOOD #1 PLAN VIEW - 14' 6.00' LUNG 4824ND -BR
w®11s Me = = _®
33' MIN
48' MAX
HOOD #1 SECTION- VIEW - MODEL 4824 - NDBR
24' NOM
78' TYP,
HOOD OPTIONS
HOOD
NO.
OPTION
FIELD WRAPPER 18.00' High Front, Left,
18' FIELD WRAPPER
FRONT & LEFT
REMOVABLE, PERFORATED
STA :,_ESS STEEL PANEL
JOB
LOCATION
ALL ELECTRICAL AND PLUMBING
CONNECTIONS MUST BE LOCATED
BELOW THE BACK RETURN AIR PLENUM
DATE 05/11/2000
DWG #
NORI SUSHI AND GRILL
REV 09/15/2000 BT
JOB# 0
DRAWN BY CMS
SCALE 8.5' x 11'
CAPTIVE -AIRE HOODS ARE
BUILT IN COMPLIANCE WITH
NFPA #96
AND ARE RECOGNIZED BY ONE
OR MORE OF THE FOLLOWING:
NSF INTERNATIONAL
BOCA -ES Report #93 -16
ICBO -ES Report #4416
SBCCI PST & ESI #93137
LOS ANGELES RR #8085
U,L. LISTED #MH12106
0 ® &mtwA swot c =
e � la la law -
`.. if1ir - -=
(T/2Ooe-Z5 z
JOB NORI SUSHI AND GRILL
LOCATION
DATE 05/11/2000
DWG #
REV. 1,00
JOB :# 0
DRAWN BY CMS
SCALE 8.5' x 11'
FAN ACCESSORIES
-UP AIR UNITS
ROOF TOP PACKAGE (RTP)
WITH CNU SERIES UPBLAST EXHAUST FAN
DATA
EXHAUST FAN
CE
EXHAUST SIDE IS VENTED
3' CONTINUOUS
FLASHING
EXHAUST FAN
ELECTRICAL DROP
ROOF OPENING
AE
EXHAUST DUCT LOCATION L - 2
SUPPLY DUCT LOCATI
A A
G -2
EXTERNAL DISCONNECT
LOCATED ON SIDE OF UNIT
GALVANIZED
SUPPLY FAN
20 GA, ALUMINIZED
CONSTRUCTION
. NOTE 10 FT,I_ HORIZONTAL CLEARANCE
FROM SUPPLY FAN INLET TO EXHAUST
FAN OUTLET (COMPLIES WITH NFPA 96)
GALVANIZED TRUNKLINE
nrucnicrnn�c rni rn�ruc
eiTi #ppRO' 60
DEC 4260,0
EQUIPMENT RAIL
N O9 .. 9 2000
PERMIT CE9.ITER
/,SU
MAU
/ / • .7l,
/
% / %% % / / �/ / % % / //% % / /// / %% % / / %
' / // %%/ // % % / % / / / %% / /�� /%% / // %
/ / /
6.00
-
3,00 -��� 3.00
I 3600
GHT
48
m I 3600
Hood #1
® \
�
lo ---
7
U.L. Listed Incandescent Lights
10 o0
_
7,aD
III
I a I
-
i
""
1 -___16A0
---i600
00
.
TYPICAL
.
\
HANGING
LOCATION
.
4 -BOXES & CONDUIT
FOR
PREWIRED LIGHTS
ANGLE
_,,
a
nn_
43.50
43.50
07.00
14' Ann.
ANSI
FAN & L
SWITC
OOD INFORMATION
BACK RETURNS)
2' HIGH SUPPLY
COLLAR CONNECTION
7
27' TYP.
100W VAPORPROOF
INCANDESCENT LIGHT
HANGING ANGLE
EXHAUST RISER
i U.L. CLASSIFIED
BAFFLE -TYPE
GREASE FILTERS
SLOPED GREASE DRAIN
WITH REMOVABLE CUP
48'
EQUIPMENT
BY OTHERS
HOOD #1 PLAN VIEW - 14' 6.00' LUNG 4824ND -BR
w®11s Me = = _®
33' MIN
48' MAX
HOOD #1 SECTION- VIEW - MODEL 4824 - NDBR
24' NOM
78' TYP,
HOOD OPTIONS
HOOD
NO.
OPTION
FIELD WRAPPER 18.00' High Front, Left,
18' FIELD WRAPPER
FRONT & LEFT
REMOVABLE, PERFORATED
STA :,_ESS STEEL PANEL
JOB
LOCATION
ALL ELECTRICAL AND PLUMBING
CONNECTIONS MUST BE LOCATED
BELOW THE BACK RETURN AIR PLENUM
DATE 05/11/2000
DWG #
NORI SUSHI AND GRILL
REV 09/15/2000 BT
JOB# 0
DRAWN BY CMS
SCALE 8.5' x 11'
CAPTIVE -AIRE HOODS ARE
BUILT IN COMPLIANCE WITH
NFPA #96
AND ARE RECOGNIZED BY ONE
OR MORE OF THE FOLLOWING:
NSF INTERNATIONAL
BOCA -ES Report #93 -16
ICBO -ES Report #4416
SBCCI PST & ESI #93137
LOS ANGELES RR #8085
U,L. LISTED #MH12106
0 ® &mtwA swot c =
e � la la law -
`.. if1ir - -=
(T/2Ooe-Z5 z
JOB NORI SUSHI AND GRILL
LOCATION
DATE 05/11/2000
DWG #
REV. 1,00
JOB :# 0
DRAWN BY CMS
SCALE 8.5' x 11'
FAN ACCESSORIES
-UP AIR UNITS
ROOF TOP PACKAGE (RTP)
WITH CNU SERIES UPBLAST EXHAUST FAN
DATA
EXHAUST FAN
CE
EXHAUST SIDE IS VENTED
3' CONTINUOUS
FLASHING
EXHAUST FAN
ELECTRICAL DROP
ROOF OPENING
AE
EXHAUST DUCT LOCATION L - 2
SUPPLY DUCT LOCATI
A A
G -2
EXTERNAL DISCONNECT
LOCATED ON SIDE OF UNIT
GALVANIZED
SUPPLY FAN
20 GA, ALUMINIZED
CONSTRUCTION
. NOTE 10 FT,I_ HORIZONTAL CLEARANCE
FROM SUPPLY FAN INLET TO EXHAUST
FAN OUTLET (COMPLIES WITH NFPA 96)
GALVANIZED TRUNKLINE
nrucnicrnn�c rni rn�ruc
eiTi #ppRO' 60
DEC 4260,0
EQUIPMENT RAIL
N O9 .. 9 2000
PERMIT CE9.ITER