Permit No: M97 -0134
Type: B -MECH
Category: NRES
Address: 665 ANDOVER PK W
Location: BUILDING #9
Parcel #: 262304 -9075
Contractor License No: COMFOP *064D2
MECHANICAL PERMIT
INSTALLATION OF ONE USED 6 1/4 TON UNIT FOR
SUPPLEMENTAL A/C DURING AFTER HOURS OPERATION.
UMC Edition: 1994 Valuation:
Total Permit Fee:
Permit Center Authorized Signature
Date
Print Name: QT' Title:
Status: ISSUED
Issued: 09/29/1997
Expires: 03/28/1998
TENANT MIDCOM
665 ANDOVER PK W, TUKWILA WA 98168
OWNER LOWE NORTHWEST INVESTOR ENT
600 UNIVERSITY ST #2820, SEATTLE WA 98188
CONTACT GERALD WARE Phone: 425- 251 -9840
6617 S 193RD STREET, KENT, WA 98032
CONTRACTOR COMFORT PLUS
P.O. BOX 913, KENT, WA 98035
********************************************* ** * **** *** * ** * *•k *** ** ** * * *****
Permit Description:
Phone: 206 251 -9840
3,000.00
42.81
**** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
I hereby certify that I have read and examined this permit and know the
same to be true and correct: All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate
or cancel the provisions of any other state or local laws regulating
construction.or the performance of work. I am authorized to sign for and
obtain this building permit.
Signature: _ C1.t�_� Date:
This permit shall become null and void if the work is not commenced within
180 days from the date of issuance, or if the.work is suspended or
abandoned for a period of 180'days from 'the last inspection.
Project Name/Tenant:
teak \
Description of work to be done: 11---161 Ile U '"' t d T •N V t--- t.'"\ 'OFD St.s '1.h tr> E Y
i • s i - i~ r b • tf,, -. a . -
Will there be storage of flammable /combustible hazardous material In the building? ❑ yes ❑ no
Attach list of materials and stora • e location on se • arate 8 1/2 X 11 • a • er indlcatin• • uantities & Material Safet Data Sheets
■ Above Ground Tanks ■ Antennas /Satellite Dishes ■ Bulkhead/Docks ■ Commercial Reroof
❑ Demolition Cl Fence g Mechanical ❑ Manufactured Housing - Replacement only
❑ Parking Lots El Retaining Walls Temporary Pedestrian Protection/Exit Systems
❑ Temporary Facilities ❑ Tree Cutting
Value of Cons uction:
b --
Site Address: C-, t c % g ,
r 1 _ t< lab ` 1 t.
640 ` ,- I City State/Zip:
M w
City /State /Zip:
0 Water
0 Sewer
Property Owner:
►.
.F.
Phone:
Street Address:
City State/Zip:
Fax #:
Contact Person:
Phone:
Street Address:
City State2ip:
Contractor:
C. t. t-
?
..,`'s Q.
Phone:
Lt P..
. r, f - c‘ l?
Street Address:
r .. q *
v
City State/Zip:
_ - ..
1
Fax #:
-
Architect:
Phone:
Street Address:
City State2ip:
Engineer:
Street Address:
City State /Zip:
MISCELLANEOUS; PERMIT` REVIEW AND'AP.PROVAL:REQUESTED', 0 BE FILLED OUT BY APPL'ICANT).>
Description of work to be done: 11---161 Ile U '"' t d T •N V t--- t.'"\ 'OFD St.s '1.h tr> E Y
i • s i - i~ r b • tf,, -. a . -
Will there be storage of flammable /combustible hazardous material In the building? ❑ yes ❑ no
Attach list of materials and stora • e location on se • arate 8 1/2 X 11 • a • er indlcatin• • uantities & Material Safet Data Sheets
■ Above Ground Tanks ■ Antennas /Satellite Dishes ■ Bulkhead/Docks ■ Commercial Reroof
❑ Demolition Cl Fence g Mechanical ❑ Manufactured Housing - Replacement only
❑ Parking Lots El Retaining Walls Temporary Pedestrian Protection/Exit Systems
❑ Temporary Facilities ❑ Tree Cutting
MONTHLY SERVICE BILLINGS .TO:...
J Phone:
Name:
Address:
City /State /Zip:
0 Water
0 Sewer
0 Metro 0 Standby
CITY OF 'pi IKWILA
Permit Center
6300 Southcenter Boulevard, Suite 100
Tukwila, WA 98188
(206) 431 -3670
Miscellaneous Permit Application
Application and plans must be complete In order to be accepted for plan review.
Applications will not be accepted through the mall or facsimile.
'.. APPLICANrREQUESTFOR 'MISCELLANEOUS,PUBL'IC :WORKS: PERMITSr:s.`>
❑ Channelization /Striping
❑ Flood Control Zone
❑ Landscape Irrigation
❑ Storm Drainage
❑ Water Meter /Exempt # Size(s):
❑ Water Meter /Permanent # Size(s):
❑ Water Meter Temp # Size(s : Est. quantity: gal Schedule:
❑ Miscellaneous On Moving Oversized Load/Hauling
WATER METER DEPOSIT /REFUND BILLING:
Name:
Address:
Data application accepted; ; -
l (`- 7
MISCPMT.DOC 7/11/96
❑ Curb cut/Access /Sidewalk ❑ Fire Loop /Hydrant (main to vault) #: Size(s)
❑ Land Altering: 0 Cut cubic yards 0 Fill cubic yards 0 sq. ft.grading/clearing
❑ Sanitary Side Sewer #: ❑ Sewer Main Extension 0 Private 0 Public
❑ Street Use ❑ Water Main Extension 0 Private 0 Public
0 Deduct 0 Water Only
Phone:
City /State /Zip:
Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review - Applications for which no permit is issued within 180 days following the date of application shall
expire by limitation. The building official may extend the time for action by the applicant for a period not exceeding 180 days
upon written request by the applicant as defined in Section 107.4 of the Uniform Building Code (current edition). No application
shall be extended more than once.
Date application expiras� Application taken b : (Initials)
BUILDING OWNER OR AUTHORIZED' AGENT:
Signature �,4 .t \t-.-c3.-"r-.4)
Phone:
Date: t _
` �..S — 1
S - q r T
Fax #: `t —
Print name:
Add a s:
6,6,11 SID, \
cP — \t
City /State /Zip:
k T \A .. etK
ALL MISCELLANEOUS PE' 'IT APPLICATIONS MUST BE SUB ED WITH THE FOLLOWING:
> ALL DRAWINGS SHALL BE AT A LEGIBLE SCALE AND NEATLY DRAWN
• BUILDING SITE PLANS AND UTILITY PLANS ARE TO BE COMBINED
> ARCHITECTURAL DRAWINGS REQUIRE STAMP BY WASHINGTON LICENSED ARCHITECT
> STRUCTURAL CALCULATIONS AND DRAWINGS REQUIRE STAMP BY WASHINGTON
LICENSED STRUCTURAL ENGINEER
> CIVIL/SITE PLAN DRAWINGS REQUIRE STAMP BY WASHINGTON LICENSED CIVIL ENGINEER
(P.E.)
SUBMIT APPLICATION AND REQUIRED CHECKLISTS FOR PERMIT REVIEW
❑ Above Ground Tanks/Watet Tanks Supported ;directiy'upon'
exceeding 5;000 gallons.and ; a ratio of height to diameter or width
which exceeds 2 :1
❑ Antennas /Satellite DIshes°,
❑ Awnings/Canopies,: No.signage
❑ Bulkhead/Dock ::
❑ ,Commercial:Reroofii'
❑ • Demolition:'
❑
Fences 'Over "6'feet in Height
Land Ailtering/Grading/P
❑ I LoadingDoc
Mechanical{(Residential& Commercial
Miscellaneous.Public;Works Permits
❑ ManufacturedHbusinw(RED'INSIGNIA:ONLY
❑ Moving
❑ Parking Lots
❑ RetainingWalls -. Over 4'feet height'
❑ Temporary Facilities
❑ Temporary; Pedestrian Protection/Ezit ;Systeths
❑ Tree Cutting,
MISCPMT.DOC 7/11/96
•
❑ Residential Reraof - Exempt with following exception:! If roof structure'
to be repaired replaced•
Submit checklist. No::': M -9
Submit checklist . No: M -1
Commercial`Tenant Improvement
Permit
Submit checklist.: No: M -10
Submit checklist :. No: M -6
Submit checklist No: M 3;:. M -3a
Submitchecklist. No: M -9
Submit checklist ; No: M -2
Submit ,checklist No ::: M- 8,
Residential'oniy H- 6;,H -1 " 6
Submit checklist No: H -9
Submit checklist; No:. M -5
Connmercial .Tenant
Perrriit :' :SUbrnit'Checklist No: H -17
Submit checklist Nor, M -5
Submit. checklist No: M-4
Building Permit
Submit checklist . ' No:. M -6
Submitcheckiist ' No: M -1
Submit checklist : No :: M -7
Submit. checklist
Submit checklist No: M -2
Copy of Washington State Department of Labor and Industries Valid Contractor's License. If
not available at the time of application, a copy of this license will be required before the
permit is issued, unless the homeowner will be the builder OR submit Form H -4, "Affidavit
in Lieu of Contractor Registration ".
Building::Owner/Authorized Agent. If the applicant is other than the owner, registered architect / engineer, or contractor. licensed ,
by the State of Washington, a notarized letter from the property. owner authorizing the. agent to submit this. permit application and
obtain the permit will be required as part of this submittal.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS
PERMIT.
CITY OF. TUIWILA
Address': 665 ANDOVER PF'•. W
_ ui
Te:n n.t: 1$000M
Type;: B -MECH `
P #: '262304 -9075
•k •k k 4 .k. •k k •k * •k •k `k * * •k * •k k •k 'k 'k *'. * 'k •* k •k •k k k •k * �k 'k Ac * •* k •k •k •k •k 'k''* * 'k •k •k 4 :k A 'k •* •k 'k •k •k •k •* k k 'k ,k.•k. k •* •k •k *' �* k k k
Permit No; M97 -01:34
Status: ISSUED
Applied: "09/15/1997
Issued: 09/29/1997
Permit Conditions:
1 No i.C.hanges isqi 11 be made to the plart� .u;�less approved. by the
Arch i test: or Eng i neer4 and,. •the Tukwila Bu i l d i ng i o n
A1:1', per•ml ts, inspect lon rr eudr!1 a pl.a shall be
available at . the 2uli;',' ite prior. to the any con ,
truce i c�ri These 'documart,ts, 'a re ta,`: ie' nra i n_ta') ned :.; and avail -
able :unt1 l , f ina1 spe *pi r oval`:,: is g t antet
. Al l 'a.an:,trirct lan to;..be carte, to "contor�►nan��•e wit appr v d
plans. and requirenr r' i� <a the,, Uniform Bui'1diricl +rode ' 21994
Edition) as amende;d :, 'WI if:orni` Meehan ica 1 '.Code `'`t199 Edit`,1art),
and Was hi,ngt'on,, state Energy,.Code, (.1994 Ed t.i,pn)
')/a 1 i d i G'y, ,;cif Perini t , 'The 1 sstiance , of a perm i t' ,ors apprdva 1
plans f.i cat ions, ; and ; .omputat sha11 not
..strue, be a pe,rnri .fii:r o'rL an approval of, anv violas, ion
of any. :of trie pr;.:tiv i s i on; of t h e ' : ! u i 'l d i n g code or' of anv
o tl•ie'r ~ ` " :ordi nap ce�'of the; ;auris:d.1'ct1 No permit presciriiing
give��` .vio1,ate` cancel the pro visiores
codeA.Sha11 be valid -
:
5. MANUFACTURERS `'IN,STALLATION' IN'STRUCFIONS 'REOUIRED ON , -SITE, ,
FOR "tTHE. g�II,LOING'" INSPECTORS`,,PEVIEW• t.
6. Re ii+ly aeoe. -S 1 h l e. acres.`• `to; roof maun t:ed equ i pnient "i s
reclu , red
7.. E1e'kkica1 permit ::�ha1 ; 1 , ,be ob:.tained' :tlir.ciugh the Washingt
5taat D .Labor'= " °`'a "`rid I nd'uct;rie. arlci a1 -,) . electri ; ;
sNor'IS' ` i,11 , =be trt.pected by that a } jenny' (4C -hb30) . ' ` s
•
ACTIVITY NUMBER M97 -0134
PROJECT NAME MIDCOM
DEPARTMENT:
BUILDING DIVISION ❑
PUBLIC WORKS ri
r a 9 - 1 6 - q 1
DETERMINATION OF COMPLETENESS: (T,Th)
COMPLETE r NOT COMPLETE ❑
COMMENTS
TUES /THURS ROUTING: PLEASE ROUTE n NO FURTHER REVIEW REQUIRED ► I
ROUTED BY STAFF n (If routed by staff, make copy to master file & enter Sierra.)
REVIEWERS INITIAL
APPROVALS OR CORRECTIONS: (ten days)
APPROVED n APPROVED W/ CONDITIONS ❑ NOT APPROVED (attach comments) ❑
REVIEWERS INITIAL
C:ROUTE -F
94eartAlets CZOT6:111atir tre9
PLAN REVIEW / ROUTING SLIP
DATE
DATE
REVIEWERS INITIAL DATE
DATE 9/15/97
FIRE w e_ ci PREVENTION n P� ? 1NING r ❑
`lr (a
STRUCTURAL PERMIT OORDINATOR
DUE DATE 9/16/97
NOT APPLICABLE ❑
DUEDATE 9/30/97
CORRECTION DETERMINATION: DUE DATE
APPROVED ❑ APPROVED W/ CONDITIONS ❑ NOT APPROVED (attach comments) ❑
(Certification of occupancy required. )
•,4
*.0****A*AkkkA*****kAl
CITV Ur •TUKWILA, WA 100.---QI 1 ItfASMI1
**A kicA.8.1•Air.k**A.4.1,1ficA*Air**• kk *NA rst. 10**k4r-frrik.A-1.-kkA h—k*Air*A*1% A k**1
TRANSMIT Number: R9700149 •Amount; 42.81 09/29/97 J320
Payment Method: CHECK Notation: COMFORT PLUS Init: 3L8
Nrmit No: M97-0134 Type: 0-MECH MECHANICAL PERMIT
Parcel No: 262304-9075
Site Address: 665 ANDOVER PK W
Location: BUILDING $49
, Total Fees: 42.81
This Pztyment 42.01 Total ALL Pmts: 42.81
, Bitlance: .00
A**A444(it*A****4
Account Code Description Amount
000/345.830 PLAN CHECK - NONRES 0.56
000/322.100 MECHANICAL - NONRES 34.23
. . 454899./30: 9719 TOTAL f 42.011
P� -ct
10 —�
1 ..I `
Type o nsp :ctign:
All
Add a s: ,,,.. i
t p t 0 5 it
II
Date called:
)0 ( 1
Date wanted: O , 2 , GO
Special instructions'
Requester: 1 4
( O
Phone No.: (_ 9 t40
ki7A'ergrm11o.aw
1 ( J INSPECTION RECORD
Retain a copy with permit � 34
INSPECTION Nb.
CITY OF TUKWILA BUILDING DIVISION
Approved per applicable codes, r i Corrections required prior to approval.
COMMENTS: i Ibi"( � eleitM
Inspector
[Receipt No.:
r -n a^.•
6300 Southcenter Blvd., #100, Tukwila, WA 98188
L • mar V�...� � /L` ors.
� r
L
Date:
Date:
206) 431 -3670
ar41-. 41
$42 � ' EINSPECTION FEE RE ' IRED. Prior to inspection, fee ust
be paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
READY FOR ISSUANCE
$ L-Ya ,S I BALANCE DUE
YES 'NO) STATE CONTRACTORS LICENSE RE U RED?
IS THIS CONTRACTOR IN THE SYSTEM? ES NO
• . APPLICANT CONTACTED DATE CALLED
Mea
•
CALLED BY
Address
City of Tukwila
Fire Department
Retain current inspection schedule
A Needs shift inspection
Approved without correction notice
Approved with correction notice issued
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre-Fire:
Permits:
FINALAPP.FRM
Authorized Signature
■••
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
Al? 1(1/
Perm
T.F.D. Form F.P. 85
Suite #
mite
John W. Rants, Mayor
Thomas P. Keefe, Fire Chief
it No.
/PC
Project Name /" J: cc)fril
4/.
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-4439
•
FILE COPY
I understand that the Plan Check approvals are
sut►iect to errors and omissions and approval of
plans does not authorize clee Receiptnof of
on
ciclr,pted code or ordinance.
approved plans acknowledged tractor's copy of app
By
Date
Permit 3
1J •�
f: .QUIRE:F, FOS.
0 MIECHANICAL
ELECTRICAL
p ` PLUMBING
h. PIPING
a'l t t L.% i ' +.d+
CITY OF TUKWILA
APPROVED
S , P,2 9 1997
gel, DING DIVISION
0 TE: 9/11/97
LOCATE ROOF TOP UNIT
ON EXISTING 4X12
PURLINS & GLU LAM BEAM.
CONTRACTOR VERIFY PURUN SIZE.
MAX UNIT WEIGHT = 565 LB
EXISTG 4x12 PURLIN
0
EXISTG 4x12 PURUN *d
o
EXISTG 4x12 PURUN
RTU LOCATION
SCALE: NTS
BUILDING PERMIT CENTER
OUTH CENTER CORP. SQUARE
RECEIVED
CITY OF TUKWILA
SEP'12 '97 09:18 HUDSON AND ASSOC
September 11, 1997
Michael Lough, Superintendent
SGA Corporation
Fax No. 206- 778 -2196
Re: South Center Corporate Square
Building 19
Andover Park West
Tukwila, WA.
Dear Mike:
As you requested we checked the roof framing for the new Roof Top
Unit weighing 565 lbs. I had reviewed several other buildings at
South Center Corporate Square earlier this year for new roof top
units and had taken some notes on the roof framing. X reviewed the
notes to verify the purlin size and spacing information that you
gave us. The plans that we had for these buildings called out 4x12
purlins at 8' -0" oc framing into 5 -1/8 x 25 -1 /2 glu -lam beams at
16' -0" oc., and 2x4 subpurlins at 16" oc. During my site visit to
review the framing I found 4x12 and 4x14 purlins with average
spacings of 4'--0" oc at the vicinity of the main roof top unit.
I checked a 4x12 purlin (spaced at 48" oc) for the new roof top
unit load along with the 4' tributary roof load. The 4x12 purlin
can support the new roof top unit by locating it as shown on the
attached partial roof framing plan. Please note that you will need
to add a 4x6 to support one edge of the roof top unit.
Please verify the size and spacing of the purlins to confirm that
they are 4x12's at 48" oc. If you have any questions, please call -
me.
Sincerely,
Bdew44#6i
Bill Whipkey, P
RICHARD HUDSON & ASSOCIATES, INC.
CONSULTING ENGINEERS
1605 12TH AVENUE • SUITE 18
SEATTLE, WASHINGTON 98122
206- 324 -6160
FAX 324 -6248
Rick P.E.
Chuck Morris, P.E.
CITY OF
RECEIVED
aEP 1 5 1997
PERMIT CENTER
11/11 8
' 1 1
S S " x 8" CD, 228 .�'
IITYP OO 10 O
I 1 4C =2 GrTVM)I
11111 11111111111 :r 11
11111
lilt
i
--3(7)
n
O
I 01
F ni
REFER PIPING
ON ROOF
NEW ROOF Mc
CON GLEEPEF '
OPEN
(
-
V WSJ x04
I' y
11 1
y
1.,g ,
, 1 A
j_
f
i j
j !
' � ►� � ■ !
! I
!i f
- i
'
I �
3
� �
,, 1
1 I
1\1]d0 �
�. I
I I !
!/ I
I I 1
(--- �
�--) i )
)
i
J
J33Y1i3?4 -7 �
�
. , r
r i
! i
il� /i n j��l� ;
;■ ' > 1
1
I I
I I i
i . �
�I f
f
_: :_ i �
ce ' L
L� !
— —
! i
�j c
i.
I t r
9 4
4! r..
r 9
4 t
r — f
— —
t — �
� ; r
ttttttt —
— -
f -
- I —
— t
11 ,
—� — —
- t-- 4
— —, —
ii 1
L _
_ j
j(ulrrrr 1
11 NilP�; �
z i
I C I _
� . i
_ I
I t
_ �
— I
i� �
� I
I i
i �
1 �
— �
a I r
r.G -
- tea, i = �\ \
\ ! ! j i
i 1
1 ,
,ii t
a
-- .
- -
-- .
.12! f
f '
' , -- �
� -
. --,—
-, -
1 -- -
1 1
11 i
.
..a ,
..1 -
I �
�Jll ,
t I
_ •
� � I
i t
II t "
1 N
, 1
I t
-- MIA 4
4- t
1 _
t i
i �
. tnu n
�
{t {uulul I
--- i
I.
i !; 1
�\ i� _
1
_I I
I -
- fi i
1( -
� . 1
I 1
s.�s t =
=ter "
"'
f 1
-1 I
'Q? he X
l j I
I
1 i
i '
! 8y I
I I
___Ii _
I f
f
__ '
_ i
_ —
**
•
L.,
Trane Air Conditioning Economics
By: COMFORT PLUS INC
********************************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
********************************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
** **
** by COMFORT PLUS INC **
** **
********************************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
********************************************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
MIDCOM @ CORP SQUARE
TUKWILA, WA
DATA ROOM AC UNIT
TRACE 600 ANALYSIS **
Weather File Code: SEATTLE
Location: SEATTLE, WA
Latitude: 47.0 (deg)
Longitude: 122.0 (deg)
Time Zone: 8
Elevation: 386 (ft)
Barometric Pressure: 29.5 (in. Hg)
Summer Clearness Number: 0.95
Winter Clearness Number: 0.95
Summer Design Dry Bulb: 82 (F)
Summer Design Wet Bulb: 66 (F)
Winter Design Dry Bulb: 24 (F)
Summer Ground Relectance: 0.20
Winter Ground Relectance: 0.20
Air Density:
Air Specific Heat:
Density- Specific Heat Prod:
Latent Heat Factor:
Enthalpy Factor:
0.0749 (Lbm /tuft)
0.2444 (Btu /lbm /F)
1.0988 (Btu- min. /hr /cuft /F)
4,836.9 (Btu- min. /hr /cuft)
4.4953 (Lb- min. /hr /cuft)
Design Simulation Period: June To November
System Simulation Period: January To December
Cooling Load Methodology: TETD /Time Averaging
Time /Date Program was Run: 9: 5:25 9/15/97
Dataset Name: 735DATA .EZT
RECEIVED
CITY OF TUKWILA
S E J ' I , 19 \j */
PERMIT CENTER
V 600
PAGE 1
Trane Air Conditioning Economics
By: COMFORT PLUS INC
AIRFLOW - ALTERNATIVE 1
System System
Number Type
1 VTCV
Totals
CAPACITY - ALTERNATIVE 1
Main Sys. Aux. Sys. Opt. Vent
System System Capacity Capacity Capacity
Number Type (Tons) (Tons) (Tons)
1 VTCV
Totals
Outside
Airflow
(Cfm)
ENGINEERING CHECKS - ALTERNATIVE 1
System Main/ System
Number Auxiliary Type
Cooling
Percent
Outside
Air
1 Main VTCV 10.48
SYSTEM SUMMARY
(Design Airflow Quantities)
Main Auxil. Room
Cooling Heating Return Exhaust Supply Exhaust
Airflow Airflow Airflow Airflow Airflow Airflow
(Cfm) (Cfm) (Cfm) (Cfm) (Cfm) (Cfm)
360 3,436 3,436 3,436 360 0 0
360 3,436 3,436 3,436 360 0 0
Cooling
Totals
(Tons)
SYSTEM SUMMARY
(Design Capacity Quantities)
Main Sys.
Capacity
(Btuh)
6.4 0.0 0.0 6.4 - 36,001
6.4 0.0 0.0 6.4 - 36,001
Aux. Sys.
Capacity
(Btuh)
ENGINEERING CHECKS
0
0
Cooling
Cfm/ Cfm/ Sq Ft Btuh/
Sq Ft Ton /Ton Sq Ft
2.17 533.1 245.7 48.84
Preheat
Capacity
(Btuh)
The building peaked at hour 13 month 9 with a capacity of
Heating
0 0
0 0
6.4 tons
-- Heating - - --
Cfm/ Btuh/
Sq Ft Sq Ft
2.17 -22.73
Reheat Humidif. Opt. Vent
Capacity Capacity Capacity
(Btuh) (Btuh) (Btuh)
0
0
Floor Area
Sq Ft
1,584
V 600
PAGE 2
Heating
Totals
(Btuh)
0 - 36,001
0 - 36,001
Trane Air Conditioning Economics
By: COMFORT PLUS INC
SYSTEM CHECKSUMS
System 1 Peak
* * * * * * * * * * * * * * * * * * * * * * * ** COOLING COIL PEAK * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** CLG SPACE PEAK * * * * * * * * * * ** HEATING COIL PEAK * * * * * * **
Peaked at Time =_> Mo /Hr: 9/13 * Mo /Hr: 10/13 *
Outside Air = => OADB /WB /HR: 74/ 61/ 63.0 * OADB: 64 *
Space
Sens. +Lat.
Envelope Loads
Skylite Solr
Skylite Cond
Roof Cond
Glass Solar
Glass Cond
Wall Cond
Partition
Exposed Floor
Infiltration
Sub Total = =>
Internal Loads
Lights
People
Hisc
Sub Total = =>
Ceiling Load
Outside Air
Sup. Fan Heat
Ret. Fan Heat
Duct Heat Pkup
OV /UNDR Sizing 0
Exhaust Heat
Terminal Bypass
Grand Total = =>
(Btuh)
0
0
0
43,560
-418
824
0
0
0
43,966 2,222
8,109 0
9,180
13,515
30,805
261
0
HEATING COIL SELECTION
Capacity Coil Airfl Ent
(Mbh) (cfm) Deg F
Hain Htg -36.0
Aux Htg 0.0
Preheat -0.0
Reheat 0.0
Humidif 0.0
Opt Vent 0.0
Total -36.0
Ret. Air Ret. Air
Sensible Latent
(Btuh) (Btuh)
0
0
1,678
0
0
544
3,436 62.6
0 0.0
3,436 62.6
0 0.0
0 0.0
0 0.0
0 0
0 0
-261
0 0
0
0
-205 0
0 0
75,032 1,756 0
;DOLING COIL SELECTION
Total Capacity Sens Cap. Coil Airfl Entering DB /WB /HR
(Tons) (Mbh) (Mbh) (cfm) Deg F Deg F Grains
Main Clg 6.4 77.4 71.6 3,436 75.3 61.1 59.0
Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0
Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0
Totals 6.4 77.4
Lvg
Deg F
72.1
0.0
56.0
0.0
0.0
0.0
Type
Vent
Infil
Supply
Mincfm
Return
Exhaust
Rm Exh
Auxil
VTCV - VARIABLE TEMP CONSTANT VOL
Mo /Hr: 13/ 1
OADB: 24
* *
Net Percnt * Space Percnt * Space Peak Coil Peak Percnt
Total Of Tot * Sensible Of Tot * Space Sens Tot Sens Of Tot
(Btuh) ( %) * (Btuh) ( %) * (Btuh) (Btuh) ( %)
0 0.00 * 0 0.00 * 0 0 0.00
0 0.00 * 0 0.00 * 0 0 0.00
1,678 2.17 * 0 0.00 * 0 -3,414 9.48
43,560 56.31 * 47,784 66.60 * 0 0 0.00
-418 -0.54 * -3,162 -4.41 * - 14,498 - 14,498 40.27
1,368 1.77 * 801 1.12 * -627 -1,037 2.88
0 0.00 * 0 0.00 * 0 0 0.00
0 0.00 * 0 0.00 * 0 0 0.00
0 -0.00 * 0 -0.00 * 0 0 0.00
46,188 59.71 * 45,423 63.31 * - 15,126 - 18,949 52.64
* *
8,109 10.48 * 8,109 11.30 * 0 0 0.00
9,180 11.87 * 4,590 6.40 * 0 0 0.00
13,515 17.47 * 13,515 18.84 * 0 0 0.00
30,805 39.82 * 26,215 36.54 * 0 0 0.00
0 0.00 * 108 0.15 * -449 0 0.00
568 0.73 * 0 0.00 * 0 - 17,405 48.35
0 0.00 * 0.00 * 0 0.00
0 0.00 * 0.00 * 0 0.00
0 0.00 * 0.00 * 0 0.00
0 0.00 * 0 0.00 * 0 0 0.00
-205 -0.27 * 0.00 * 354 -0.98
0 0.00 * 0.00 * 0 0.00
* *
77,356 100.00 * 71,746 100.00 * - 15,574 - 36,001 100.00
AIRFLOWS (cfm)
Cooling Heating
360 360
0 0
3,436 3,436
0 0
3,436 3,436
360 360
0 0
0 0
Leaving DB /WB /HR Gross Total Glass (sf) ( %)
Deg F Deg F Grains Floor 1,584
56.0 53.2 57.0 Part 0
0.0 0.0 0.0 ExFlr 0
0.0 0.0 0.0 Roof 1,584 0 0
Wall 528 264 50
-- ENGINEERING CHECKS- -
Clg % OA 10.5
Clg Cfm /Sqft 2.17
Clg Cfm /Ton 533.09
Clg Sqft/Ton 245.72
Clg Btuh /Sqft 48.84
No. People 18
Htg % OA 10.5
Htg Cfm /SqFt 2.17
Htg Btuh /SqFt -22.73
AREAS
V 600
PAGE 3
-- TEMPERATURES (F) - --
Type Clg Htg
SADB 56.0 72.1
Plenum 75.5 67.1
Return 75.5 67.1
Ret /OA 75.3 62.6
Runarnd 75.0 68.0
Fn HtrTD 0.0 0.0
Fn B1dTD 0.0 0.0
Fn Frict 0.0 0.0
Trane Air Conditioning Economics
By: COMFORT PLUS INC
MAIN SYSTEM COOLING - ALTERNATIVE 1
MAIN SYSTEM HEATING - ALTERNATIVE 1
PEAK COOLING LOADS
(Main System)
V 600
PAGE 4
Space Coil
Peak OA Rn Supp. Space Space Space Peak OA RI Supp. Coil Coil Coil
Time Cond. Dry Dry Air Sens. Lat. Time Cond. Dry Dry Air Sens. Lat.
Room Mo /Hr DB /WB Blb Bulb Flow Load Load Mo /Hr DB /WB Blb Bulb Flow Load Load
Number Description (F) (F) (F) (Cfm) (Btuh) (Btuh) (F) (F) (F) (Cfm) (Btuh) (Btuh)
1 HP -1 10/13 64 55 75 56.0 3,436 71,746 4,590 9/13 74 61 75 56.3 3,436 71,644 5,712
Zone 1 Total /Ave. 64 55 75 56.0 3,436 71,746 4,590 74 61 75 56.3 3,436 71,644 5,712
Zone 1 Block 10/13 64 55 75 56.0 3,436 71,746 4,590 9/13 74 61 75 56.3 3,436 71,644 5,712
System 1 Total /Ave. 64 55 75 56.0 3,436 71,746 4,590 74 61 75 56.3 3,436 71,644 5,712
System 1 Block 10/13 64 55 75 56.0 3,436 71,746 4,590 9/13 74 61 75 56.3 3,436 71,644 5,712
PEAK HEATING LOADS
(Main System)
Space Coil
Peak OA RI Supp. Space Space Peak OA Rm Supp. Coil Coil
Floor Tine Cond. Dry Dry Air Sens. Tine Cond. Dry Dry Air Sens.
Room Area Mo /Hr DB /WB Blb Bulb Flow Load Mo /Hr DB /WB Blb Bulb Flow Load
Number Description (Sq Ft) (F) (F) (F) (Cfm) (Btuh) (F) (F) (F) (Cfm) (Btuh)
1 HP -1 1,584 13/ 1 24 21 68 72.1 3,436 - 15,574 13/ 1 24 21 68 72.1 3,436 - 36,001
Zone 1 Total /Ave. 1,584 24 21 68 72.1 3,436 - 15,574 24 21 68 72.1 3,436 - 36,001
Zone 1 Block 1,584 13/ 1 24 21 68 72.1 3,436 - 15,574 13/ 1 24 21 68 72.1 3,436 - 36,001
System 1 Total /Ave. 1,584 24 21 68 72.1 3,436 - 15,574 24 21 68 72.1 3,436 - 36,001
System 1 Block 1,584 13/ 1 24 21 68 72.1 3,436 - 15,574 13/ 1 24 21 68 72.1 3,436 - 36,001
Trane Air Conditioning Economics
By: COMFORT PLUS INC
COOLING LOADS AT COIL PEAK - ALTERNATIVE 1
HEATING LOADS AT COIL PEAK - ALTERNATIVE 1
INTERNAL COOLING LOADS
(At time of Coil Peak)
Lights Lights Misc. Misc. Misc.
Room Ret. Air Lites People People Peopl Space Space Ret. Air Misc.
Room Sensible Sensible CLF Sensible Latent CLF Sensible Latent Sensible CLF Total
Number Description (Btuh) (Btuh) (Btuh) (Btuh) (Btuh) (Btuh) (Btuh) (Btuh)
1 HP-1 8,109 0 1.000 4,590 4,590 1.000 13,515 0 0 1.000 30,805
Zone 1 Total /Ave. 8,109 0 1.000 4,590 4,590 1.000 13,515 0 0 1.000 30,805
Zone 1 Block 8,109 0 1.000 4,590 4,590 1.000 13,515 0 0 1.000 30,805
System 1 Total /Ave. 8,109 0 1.000 4,590 4,590 1.000 13,515 0 0 1.000 30,805
System 1 Block 8,109 0 1.000 4,590 4,590 1.000 13,515 0 0 1.000 30,805
INTERNAL HEATING LOADS
(At time of Coil Peak)
Lights Lights Misc. Misc.
Room Ret. Air Lites People Peopl Space Ret. Air Misc.
Room Sensible Sensible CLF Sensible CLF Sensible Sensible CLF Total
Number Description (Btuh) (Btuh) (Btuh) (Btuh) (Btuh) (Btuh)
1 HP -1 0 0 0.000 0 0.000 0 0 0.000 0
Zone 1 Total /Ave. 0 0 0.000 0 0.000 0 0 0.000 0
Zone 1 Block 0 0 0.000 0 0.000 0 0 0.000 0
System 1 Total /Ave. 0 0 0.000 0 0.000 0 0 0.000 0
System 1 Block 0 0 0.000 0 0.000 0 0 0.000 0
V. 600
PAGE 5
Trane Air Conditioning Economics
By: COMFORT PLUS INC
COOLING LOADS AT COIL PEAK - ALTERNATIVE 1
BUILDING ENVELOPE COOLING LOADS
(Roof - Skylight)
(At time of Coil Peak)
Roof Roof Skylight Skylight
Return Air Roof Space Roof Skylight Skylight Skylt Return Air Skylt Space Skylt
Sensible R.A. Sensible Space Return Air Space Solar Conduction R.A. Conduction Space
Roon Load CLTD Load CLTD Solar Solar CLF Load CLTD Load CLTD
Number Description (Btuh) (F) (Btuh) (F) (Btuh) (Btuh) (Btuh) (F) (Btuh) (F)
V 600
PAGE 6
1 NP -1 1,678 21.2 0 21.7 0 0 0.000 0 0.0 0 0.0
Zone 1 Total /Ave. 1,678 21.2 0 21.7 0 0 0.000 0 0.0 0 0.0
Zone 1 Block 1,678 21.2 0 21.7 0 0 0.000 0 0.0 0 0.0
System 1 Total /Ave. 1,678 21.2 0 21.7 0 0 0.000 0 0.0 0 0.0
System 1 Block 1,678 21.2 0 21.7 0 0 0.000 0 0.0 0 0.0
BUILDING ENVELOPE COOLING LOADS
(Wall - Window)
(At time of Coil Peak)
Wall Wall Wail Wall Glass Glass Glass Glass Glass Glass Glass
Plenum Plena Space Space Space Return Air Solar Space Space Return Air R.A.
Roos Load CLTD Load CLTD Solar Solar CLF Conduction CLTD Conduction CLTD
Number Description (Btuh) (F) (Btuh) (F) (Btuh) (Btuh) (Btuh) (F) (Btuh) (F)
1 HP -1 544 57.3 824 57.8 43,560 0 1.000 -418 -1.4 0 0.0
Zone 1 Total /Ave. 544 57.3 824 57.8 43,560 0 1.000 -418 -1.4 0 0.0
Zone 1 Block 544 57.3 824 57.8 43,560 0 1.000 -418 -1.4 0 0.0
System 1 Total /Ave. 544 57.3 824 57.8 43,560 0 1.000 -418 -1.4 0 0.0
System 1 Block 544 57.3 824 57.8 43,560 0 1.000 -418 -1.4 0 0.0
BUILDING ENVELOPE COOLING LOADS
(Exposed Floor - Partitions - Infiltration)
(At time of Coil Peak)
Exposed Expsd Plena Ceiling
Floor Floor Partition Part. Infilt. Infilt. Infilt. Dry B Sensible Envelope
Root Sensible CLTD Sensible CLTD Airflow Sensible Latent Temp. Load Total
Number Description (Btuh) (F) (Btuh) (F) (Cfn) (Btuh) (Btuh) (F) (Btuh) (Btuh)
1 HP -1 0 0.0 0 0.0 0 0 0 75.5 261 46,449
Zone 1 Total /Ave. 0 0.0 0 0.0 0 0 0 75.5 261 46,449
Zone 1 Block 0 0.0 0 0.0 0 0 0 75.5 261 46,449
System 1 Total /Ave. 0 0.0 0 0.0 0 0 0 75.5 261 46,449
System 1 Block 0 0.0 0 0.0 0 0 0 75.5 261 46,449
Trane Air Conditioning Economics
By: COHFORT PLUS INC
HEATING WADS AT COIL PEAK - ALTERNATIVE 1
BUILDING ENVELOPE HEATING LOADS
(Roof - Skylight)
(At time of Coil Peak)
Roof Roof Skylight Skylight
Return Air Roof Space Roof Skylight Skylight Skylt Return Air Skylt Space Skylt
Sensible R.A. Sensible Space Return Air Space Solar Conduction R.A. Conduction Space
Room Load CLTD Load CLTD Solar Solar CLF Load CLTD Load CLTD
Number Description (Btuh) (F) (Btuh) (F) (Btuh) (Btuh) (Btuh) (F) (Btuh) (F)
1 HP -1 -3,414 -43.1 0 -44.0 0 0 0.000 0 0.0 0 0.0
Zone 1 Total /Ave. -3,414 -43.1 0 -44.0 0 0 0.000 0 0.0 0 0.0
Zone 1 Block -3,414 -43.1 0 -44.0 0 0 0.000 0 0.0 0 0.0
System 1 Total /Ave. -3,414 -43.1 0 -44.0 0 0 0.000 0 0.0 0 0.0
System 1 Block -3,414 -43.1 0 -44.0 0 0 0.000 0 0.0 0 0.0
BUILDING ENVELOPE HEATING LOADS
(Wall - Window)
(At time of Coil Peak)
V 600
PAGE 7
Wall Wall Wall Wall Glass Glass Glass Glass Glass Glass Glass
Plenum Piens Space Space Space Return Air Solar Space Space Return Air R.A.
Room Load CLTD Load CLTD Solar Solar CLF Conduction CLTD Conduction CLTD
Number Description (Btuh) (F) (Btuh) (F) (Btuh) (Btuh) (Btuh) (F) (Btub) (F)
1 HP -1 -410 -43.1 -627 -44.0 0 0 0.000 - 14,498 -44.0 0 0.0
Zone 1 Total /Ave. -410 -43.1 -627 -44.0 0 0 0.000 - 14,498 -44.0 0 0.0
Zone 1 Block -410 -43.1 -627 -44.0 0 0 0.000 - 14,498 -44.0 0 0.0
System 1 Total /Ave. -410 -43.1 -627 -44.0 0 0 0.000 - 14,498 -44.0 0 0.0
System 1 Block -410 -43.1 -627 -44.0 0 0 0.000 - 14,498 -44.0 0 0.0
BUILDING ENVELOPE HEATING LOADS
(Exposed Floor - Partitions - Infiltration)
(At time of Coil Peak)
Exposed Expsd Plenm Ceiling
Floor Floor Partition Part. Infilt. Infilt. Infilt. Dry B Sensible Envelope
Room Sensible CLTD Sensible CLTD Airflow Sensible Latent Temp. Load Total
Number Description (Btuh) (F) (Btuh) (F) (Cfm) (Btuh) (Btuh) (F) (Btuh) (Btuh)
1 HP -1 0 0.0 0 0.0 0 0 0 67.1 -449 - 19,398
Zone 1 Total /Ave. 0 0.0 0 0.0 0 0 0 67.1 -449 - 19,398
Zone 1 Block 0 0.0 0 0.0 0 0 0 67.1 -449 - 19,398
System 1 Total /Ave. 0 0.0 0 0.0 0 0 0 67.1 -449 - 19,398
System 1 Block 0 0.0 0 0.0 0 0 0 67.1 -449 - 19,398
Trane Air Conditioning Economics
By: COMFORT PLUS INC
BUILDING U- VALUES - ALTERNATIVE 1
Room U- Values Room Room
(Btu /hr /sqft /F) Mass Capac.
Room Summr Wintr Summr Wintr (lb/ (Btu/
Number Description Part. ExFlr Skylt Skylt Roof Windo Windo Wall Ceil. sqft) sqft /F)
1 HP -1 0.000 0.000 0.000 0.000 0.050 1.130 1.247 0.090 0.317 24.6 7.06
Zone 1 Total /Ave. 0.000 0.000 0.000 0.000 0.050 1.130 1.247 0.090 0.317 24.6 7.06
System 1 Total /Ave. 0.000 0.000 0.000 0.000 0.050 1.130 1.247 0.090 0.317 24.6 7.06
Building 0.000 0.000 0.000 0.000 0.050 1.130 1.247 0.090 0.317 24.6 7.06
BUILDING AREAS - ALTERNATIVE 1
Floor Total Exposed
Number of Area /Dupl Floor Partition Floor Skylight Skl Net Roof Window Win Net Wall
Room Duplicate Room Area Area Area Area /Rf Area Area /W1 Area
Number Description Flr Rm (sqft) (sqft) (sqft) (sqft) (sqft) ( %) (sqft) (sqft) ( %) (sqft)
1 HP -1 1 1 1,584 1,584 0 0 0 0 1,584 264 50 264
Zone 1 Total /Ave. 1,584 0 0 0 0 1,584 264 50 264
System 1 Total /Ave. 1,584 0 0 0 0 1,584 264 50 264
Building 1,584 0 0 0 0 1,584 264 50 264
ASHRAE 90 ANALYSIS - ALTERNATIVE 1
ASHRAE 90 ANALYSIS
Overall Roof U -Value = 0.050 (Btu /Hr /Sq Ft /F)
Overall Wall U -Value = 0.610 (Btu /Hr /Sq Ft /F)
Overall Building U -Value = 0.190 (Btu /Hr /Sq Ft /F)
BUILDING U- VALUES
BUILDING AREAS
Roof Overall Thermal Transfer Value (OTTVr) = 2.63 (Btu /Hr /Sq Ft)
Wall Overall Thermal Transfer Value (OTTVw) = 59.87 (Btu /Hr /Sq Ft)
V 600
PAGE 8
_/
1
SEP -09 -97 TUE 04;10 FM ROBERTS TRANE
Performance
Data
Table 4 914 Tqn HMtlf11
sand Heeds Capacity At
lncicated lndoXr Dry Bulb Tamp,
60 70 80
154 13.9 12.3
• 8 18.1 161 15.0
• 3 21,0 1 9.4 171
2 24.0 22.4 2013
7 273 25.7 241
12 30.9 23.3 278
17 34,6 333 31.2
22 396 36.9 35,1
• 27 42.7 41.0 39.2
32 47A 45.2 414
37 51.5 49,7 47.9
42 56.0 54.2 �4
52 79.7 78.4 73.6
57 86.4 82.8 791
62 91.5 89.3 85
67 98.1 86.2 91.1
72 1061 1028 97.7
Otmdoor
Dry Bulb
Tara.
F.
.13
F91 at* a, flew ar+accn sal Hat* Cortecocn fycwr (Table 61
Net ttoadnp tapeoky end poem ?ptrt noon liwoor fan Mot at nominal C rn and 25 hen ELI To Paton itat h. sdn M pear
con8ll eubcv4 fan heat M Mk oYeldian ant wit tan mac tt Awe oodloon,
timing up3014K od pews ail i1agrsoad to Mdudo M "COI of ddreat m tea tau tow.
At hosting CrooliN ale moors as lt 70% 00 rolftt hwn4ity oral 70 nwRad how; ryW.
Table 5 71/2 Ton Holing Cepectties (Not) WC -090A At 3000 Cfm
Outdoor
Dry Out)
Tamp.
F.
Integrated F1aatirq Cap.dty At Total Foveae in Kilowvaa At
f'iceted tndow Ory But Two. lrttiatrl lnbgor Dry Bulb Temp.
60 70 80 60 70 80
.13 18.0 132 2.0 4.18 425 4.30
.8 19.8 17.6 •.6 4.47 4.55 4.62
• 3 23.7 21.6 1 . 4.75 4.84 4,94
2 27.8 25,5 23. 503 5.14 5.24
7 32.1 29.7 27.2 5.31 5.43 956
12 38.7 34.2 31.7 5,59 5.72 988
17 411 39.0 6,86 6.01 6.18
22 46.8 44,1 4 8.12 6.29 6.48
27 52.4 49.8 •.7 6.39 6.58 6.70
32 582 55.3 2.3 8,56 6,86 7.00
37 64.6 61.5 58.5 6.94 7.15 7.35
42 71,2 58.1 65.1 7,21 7,43 7.65
47 85.5 82.0 783 6.33 8.58 982
52 82.5 88.7 853 8.73 9.01 9.28
57 99,5 95.7 97.9 913 9.43 9.73
62 106,7 102.9 99.0 9 42
515 1018
61
113.9 1101 106.3 9.8882 1028 10.63
72 121.2 117.5 119.7 10.1 10.70 11.09
Fa cote air how uas* Qn WC HUM' Carrvauon New (Toad E)
Mot temp tingly Yid pourot tnp t rritk fltlgUr fan heat M nominal Om 000.25 fitpt ESP. To spent rot Peony of shoo
orattonr, Wan= file Mat at Otis cwYYon ono add fan Mat at note aces960n.
M0ot0ng capadtlal and Wears ail in0700 IV itakoda PM offal/ of tNatM h Wet fora onion.
al Mratnd tavach>ra and powers are at 70ik 00 rorto, hurnaly and 70 shoat. Mary c}Ok
Table 6 HM1009 Cagcity Consctlurt Factors
14 Variation of flominal Dim
Total Oros* Capacity MuttVllet
FAX NO. 206 643 4314 P. 02/11
. 20
At 2500 Om
• 10 0 •10 #20
Total Intwor in Kilowatts A:
Inclosed In000r Dry bulb Temp
80 70 80
3.71 3.77
007 4.09
4.11 4.23 433
431 4.45 497
4 51 4.66 4.80
4.72 4.88 5.03
492 5.09 5,28
6.11 531 5.49
6.31 5.52 5.72
5.50 5,72 5.95
969 5.93 8.18
5.88 0.f1 141
616 7.17 7.49
7.16 7.52 786
7.46 7.86 824
7.70 0.19 881
836 853 8.94
837 8.87 9.36
ECEIVED
OF TUKWILA
i
PERMIT CENTER
Q
)
SEP -09-97 TUE 04:11 PM ROBERTS TRANE
CI)
Table 11 Evaporator Fan Performance
Tors Unit
7n
WC0075n
WC1407•,+A
WC 30974
WCN090A
Ow, mom/ 1444/741 in tna444 tiros
S4rv144 fa anf W rd.4 motor 1,5.444rliOld mots 1.26. Motor 'Wormy s 72
Oats tnducel mows 7199 duo 13 4r4t ca1 1tY1 Ahem .
ion mops h4Jt 048h1. 3,15 X 4
FAX NO, 206 643 4314
Performance
Data
Table 7 Awoliary Electric Hut Capacity
Tabla 10 Electric Heater Temperature F(iaa Corrt5ctiort Factor*
9
P. 03/11
No Stieps 1 Stags 2 Total
(;nit Total of KW Blatt KW Droll KW 86A
Model No. KW $ 19 5 49 Input WW1 Mput 00194.8 rout Ot4put
8 1 9 30.7 9 30.7
-075A 17.3 1 17 59.0 173 59A
YN,11QpA 18 1 18 614 16 91.4
27 2 18 61.4 9 30.7 27 921
36 2 18 81A 16 61.4 36 122,8
Table 8 Electric Hater Voltage Cor,ec1;on
Factors (Apply to Auxiliary Haat
CaPaaity)
Capacity
Nominal Vohs Distribution Vohs Multiplier
208 0.75
240 230 0.92
240 1,00
440 0.84
480 0.92
480 1.00
540 0.81
600 575 0.92
600 1.00
Table 9 Air T.mperstura Rise Across
Electric Heaton
WC.07SA W0.090A
Kw Steam (2500 Om) (3000 Cfml
9 1 114 9.5
18 1 22.8 19.0
27 2 342 28.5
38 2 46.5 37.9
1
% Variation Porn Nominal Ctm • 20 • 15 • 10 -5 0 •5 • 10 • 15 4 20
Temp4rature Rile MultipNft 1.25 1.17 1.11 1.05 1.00 0.95 0.91 0.87 0.83
10° .20" .30 40" .50' .00' .70" .s0" ,90" 1.00" 1 25" 1.50"
0m RPM 8745 45.I IHI RPM I NP RPM 07P RPM 5745 aim BM 5$44 6H5 RPM 1745 RPM 4715 RPM 8NP RP7,4 BHP RPM 1N►
3000 607 .35 646 .44 892 60 738 ,S5 741 .60 424 44 466 .71 906 .74 948 .82 984 17 1011 .28 ••
2340 669 .53 704 .60 736 ,68 737 , 628 ,18 91' 44 904 .89 942 .96 978 1.03 1015 1.04 1141 1.22 1119 1,38
25303 724 .71 764 ,74 902 95 2609 .02 877 4 914 105 640 1.12 013 1.16 1017 1.25 1060 1.32 1127 1.43 - -.
3780 748 .93 626 1,9' 151 1100 895 114 029 1,23 943 1.31 9N 1,31 1029 1.46 1000 1.52
70311 8541,19 $17 1.27 921 1.36 993 1.44 8831,!2
2400 509 .59 740 .64 777 ,i9 515 .74 667 76 t911 A3 131 S7 906 , 1001 .14 1075 .07 1120 1.04 1201 1.09
2700 775 93 613 .63 3 .94 153 1370 915 1.04 813 149 987 1.15 1020 1,13 1051 1.24 1080 1.19 1160 1.38 1330 1,48
3000 354 I.11 5571,15 921 1.24 663 1.33 947 147 1015 1.42 1045 7.48 1077 1.53 1107 1.59 1135 1,64 1207 1.76 1277 1,87
5500 113 1,45 933 1.87 594 1,61 7024 191 1.76 101K3 1472 1109 14 1137 1,93 1140 1.69 1123 206 1241 - �• --
7600 1012 14 1340 1,18 1065 204 1006 212 1123 2.19 -
SEP -09 -97 TUE 04:11 PM ROBERTS TRP.NE FAX NO, 205 543 4314 P.04/11
ep t.
Performance
Data
0
Teets 2.04eiiCooing "Copie1199(MQA) 6 T• WC.075A
6e 106 11
6n1w019 ‘449 Gab Ny
am St
61 97 77 a1 87 73 61 67 77 41 e7 73
*40», (F) 1941 1110 hEtt WC 4th WC UP 0540 MM WC M6n $540 Meh $710 Wh PC 7955 5140. MM PC M$ WC h i 5110.
76 66.2 54.5 76,7 41,6 79.1 27.0 536 52.2 73.5 359 7111 26.6 66.3 49.2 68,4 37.2 736 244 51,6 441 60.6 33.2 0.3 224
2254 50 062 76.7 027 71.1 314 036 616 735 613 76.1 37.3 58,3 674 684 qA 736 359 52.0 620 606 447 69.7 737
5$ 0A2 471 76.7 644 79,1 31.3 6"00 61.0 715 621 769 60.3 61.4 41,4 614 604$ 734 417 !6A 65.9 60.8 SSA 61.3 44.1
60 719 70,3 70.7 73A 15A 69,1 e13 08.3 73.6 71.6 769 353 45.4 66.4 66A 07,3 738 96.7 598 666 604$ 60.6 653 53.1
75 09,6 67.4 76.3 43,6 647 255 449 56A 75o 424 759 27.2 W.5 61.8 816 31,2 73.3 29.7 629 473 621 748 70.7 23,7
3000 60 050 60,6 76.3 53.6 60.7 404 66.0 36D 760 '060 76S 363 U 604 690 61.5 75.3 37,9 541 946 621 47.0 70,7 38.6
85 71,3 71,3 76•,3 07.3 117 340 66.4 88,4 76A 601 70,5 634 616 646 08.8 W.6 75,3 51.2 166 656 621 6309 70,7 46.5
90 740 740 73.3 77,6 71.17 4;2.3 71,9 n4 74A 75.4 n4 61.4 661 68,6 719 70.9 703 6a7 63A MA 67.7 437 70.7 Sag
0
75 702 C Z 791 464 61A 29.9 454 973 756 44.1 75.3 294 6111 54.1 70,5 41,1 74,1 26.9 57.4 494 62.7 36+.7 71,4 24.6
60 720 724 70.1 163 21.4 42.5 4aa 453 761 66.7 79,3 410 654 03.4 704 541 76.1 30.' 57,9 57.5 4L7 44 714 37.3
96 746 749 no 747 51.6 66.7 71,5 713 731 01,4 794 55.5 67e 678 70.6 57A 76.' 615 61,7 41.7 62.7 614 71.4 10A
80 771 77,7 903 63.3 51.5 65.4 76.9 75.5 774 77,4 7173 644 722 722 74.4 744 76,1 627 642 M.1 681 64.7 714 69.4
76 70,9 62.5 719 47,7 620 31.0 66.1 459 76,3
60 744$ 746 71.9 505 823 441 709 70.6 76.6
AS 774 77.6 759 734 623 9 746 74.6 76.5
90 617 00.7 61,1 61,1 822 67,6 78.4 76.4 79,2
2750
9000
469
60.t
72.0
79.2
60A MA 547 36,6 71,2 427 703 250 53,9 61,5 67.3 351 72,1 256
40.0 429 661 665 72.2 362 706 41.2 901 59.7 63.3 M1 72.1 36.7
600 574 30A 70.4 71.2 M.6 769 369 e4,1 641 660 4A0 72.1 128
80.0 66,9 764 75D 744 76D 719 460 *7 667 17.4 70.4 no 41.8
I Ill Oet. utM and in 0.1t.e. P.
AllecogroN sto441 M4 5w l td 2w 4 n014Y114Mf.t1 i%qd Ian hoot. To 0b7441 Rot toorog We a9$I sa6troo hahor *I Nit
MAth o Tani tSro01 Cod4p Capon'
SIC 1 Nog* Not Caax+N
NOM:
1, NV srsl 03r 7 4111 0 04444 04p4.7ly 114131 Seb3W1 1014 MR Is not 400lilab9, 74 MO cool 1M San7610 Not 0404Clty 20/40.1 the 04 C 0ai y.
Table 3 • Gems Cooling Cop6chios (MBA) 7 Ton WC •080A
3700
3300
erne.
85
WON*
(2/vi 47 73 et 67 61 67 73 61 67 73
maim 1) MIS &40. mm 93+0 mm WM AM SIC MM 5*40. SMC MOh $240 14111 WC Mph WC Mkt SMC AIM WC MP 5IC
76 623 446 92.3 5011 992 323 743 61,1 88,2 47,9 . 7 309 50.2 35.8 804 439 064 26.6 610 48.3 68.7 384 754 21.4
2700 90 11,1 77$ 92.3 WA 95.2 462 741 721 852 61,5 Al 447 602 05.1 648 67.7 00.4 MA 57.1 07.1 69,7 51.1 79.4 351
56 01.) 00.7 92.3 774 15.2 61,7 75.2 76.0 152 764 0717 09.7 69.7 M6 71,4 01,4 559 01.3 01.3 OQ7 044 764 02.1
00 917 03.7 02.3 *9 86,2 no 706 79.0 652 80.9 •,1 51$ 70.7 744 60.4 791 00.4 04.3 067 662 08,7 08.3 70.4 01.0
7S 521 650 04.2 623 87.1 362 790 063 800 644
90 829 61.4 944 451 87.1 44 780 760 910 648
IS 44,6 040 64.2 01D 97,1 36D 800 930 800 78
10 e11 811 Na 97.4 97,1 748 04A 600 614 91
75 116 71.7 16.1 56.3 58.1 35.5 76.4 511 109
00 116.7 55.7 31,1 701 141 51,1 799 793 20D
65 1511 651 96. 651 *1 562 64.0 NO 09
90 925 N5 91.4 96.4 02.1 7135 $1.2 002 114$
9 949 342 :2
0 16.9 40,4 0
.2 949 0116 77
91.6 049 772 624
75 e64 744 96,1 574 160 37.3 77A 711 91 553 190 159 669 ' 2 691 80,3 56.9 32.7 59.2 056 72,1 41.6 01.6 252
t6C 804 580 801 72.0 950 63.0 624$ 629 6t 714 963 513 747 74. 1321 061 059 03 66.5 WA 726 98.7 MA 437
46 825 92.3 061 8a0 190 70.1 47.2 872 61 564 146 85.1 603 90A 415 MA 693 65.3 703 704 73,5 70,6 81.6 696
80 NO 960 17.6 97,8 993 41.4 11,6 91.4 137 131:063 10.1 85.1 66.1 $8.3 64.8 649 761 75.7 74,3 79.5 76.5 513 710
Al twor3Nt.s to in dogtw4
All 449ee04 Owns aro rrs an3 two Mt W roid.TW o14001 fon now To Vum1 not 2oo14'0 u1 xow• tab►M7 int** San hoot
Mine Tout Crop C044r9 C41D9Cev
5740 • MIAOW Hoot 0404,
742210$,
1. ON col oof Wits Too amo C00104 Ca .h1V (NMI 01*on *V* et is na OOOSra*W, in OM CNs the Semi** Molt 010036v tO401 6154 %AM ;AWAY.
7
ertOs4Mn
106
116
67.6 569 52.2 467 661 310 510 011 71.1 400 90.0 256
eA4 61.6 12.2 647 661 44.2 50.1 501 71.1 13.0 800 411
73A 73.4 82.2 70,2 *1.2 69.9 64.3 645 71,1 674 600 64.9
701 72.1 13.5 83.5 80.1 491 N.1 q,1 730 730 100 642
61.5 63.0 444 68.0 91.6 56.0 644 711 420 071 211
720 013 63.7 194 464 122 62,7 716 685 806 411
77.0 830 790 88.0 62.9 67.7 07 714 70.e 900 570
*0 671 67.7 61.0 730 72.6 725 74,6 761 008 67,4
1
SE 97 TUE 0402 PM ROBERTS TRANS
IWO
General
Data
.••........... - a
Table 1 General DM
C.00ling s Coolinnggga Performance'
IAV Nel Coofing COsoacity
Nominal C!m
SYrt Kw
Heating Performance
Migh Temperature !Huh Rating
%Sant Power Kw /COP
Low Temperature Stun Rating
5wtem Power Kw /COP
Compreasor
No. =HP
Mow RPM
Outdoor Coif — Type
Tuts Size (m) OD
hoe Area (eq. R.)
ROws/FPI
Refrigerant Control
Indoor Coi — Noe
Tube Site (in,)
Face Area qq. ft.)
Roavd /FPt
Refrigerant Control
Orein Connection Site firt.)
Outdoor Fen — Type
No, Ua d/Dlantver (in,)
Chive
ChM Type/No. Spates
No. Motors /HP
Motor Rpm
FAX NO. 206 543 4314 P.05/11
7 9.5
2500
9,55
Pl a.3ro Fin
75
11.6
2/16
Exparrion Valve
Plate Pin
.376
7.00
• • . 2/16
Cadllaty Tube
PVC
W
Direct/1
1 /.50
" 1075
71,000
7,17/Z.90
33,000
5139 /1,90
1 /CYmatuft<M
1/6.25
3450
AR! Sound Rating (IELS) as
746 Ton
V 0,wCH090
90,000
e 8.30
3000
10.24
82.000
5.5E /2,80
6.01' /1 SQ
1/Mods M
1
1/7.5
3450
9.0
taro Fln
.375
12,9
2/16
Reoanafon Why
Plate Fin
.375
7.98
2/15
C»»UONube
T
P 1 24
6402
1/.50
1075
Indoor Fen — Type CenarifupW Centrifugal
No. U104 /0farnee r (in.) 1/12 x 9 1/12 x9
Drive Type/No. Speeds llett/1 Belt/)
Motor Rpm ' 1728 1 1725 0
Fitters --T Furnished) Yea Yes
No. /Size Recommended (1118 x 25. t (3116e 25 ti 1
Ref Omni Charge Obi. or R.22) 10,0 11.9
NOTES:
1, Mud in a000r0ena wkh ARI Stargara 240.
2. RIwo In aocord.Pce with 005 tan prec+drn.lfe:mna Swwnil Pwlormenoa Pacer (MCP) it at me mininum Galen
(wryi elet Region N. (WV/Nhn•hr.) '
S toted in swarm with AR senors 270.
4. £wiaaro atr.dry coil maw.
�. Aopanmase Yalaw P+7t mite preciN oh" fee talk nemeses Mrs lomat njtrucvane,
SEP . -09 -97 TUE 04113 PM ROBERTS TRANE
Weights
CG Length
Unit Comer and Shipping Weights (lbs.) end Pon* of Grw)ty
shpptng Wright$ Corner Weights Camas of Gravity
e-«. Model Unit No. Shening Net A 8 C D Length WuithWids1
W01)075 ? 865 653 218 163 118 156 39" 22"
WCH075' 865 853 229 174 107 143 39• 20"
W00090 873 661 225 164 114 158 38" 21"
WC14090 873 661 239 175 103 144 39" 19"
FAX NO. 206 643 4314
CENTER OF
0 -
f CG Width
COMPRESSOR
A
Accessory Weights (stet Ibs.)
Acetuory Net SNoolhe
Rookurt+ 82 90
Economiser a0* to
Manual 04 Damper 32 SO
Overarm! Mown 65 70
ENcla Meat
1118 Kw 20 26
2738 Kw 20 28
NOTE
1, Hut went should be slop to unit wept vAwt odwinl
Won innrise «ono nu t.
SEP -09 -87 TUE 04114 PM ROBERTS TRANE FAX NO. 206 643 4314
I MF � ..... Dimensional 6 Ton
Data Units
EVAPORATOR SECTION
ACCESS PANEL
2" ELECTRICAL CONNECTION
HEAT I )PIER WHEN
NOTE: Recommended Clearance — 48" From.
34" Sides, 18" Hear
•■•••••••■••■■••■■•••■••••••••■••••••••■■••••.........••■••••••••••••■•Ae
cONTAOLII . e e! / ' ,
ACCESS PANEL \ ►
t9 tilt'
CURB DIMENSIONS
TYPICAL ROOF OPENING
- CONDENSER FAN
OVERALL DIMENSIONS CRATED
38.8 "HX63.8 "WX88.5 "13
34"
CONDENSER COIL
2" DIAMETER HOLE
GOUT POWER WIRES)
7 /11" DIAMETER HOLE
(UNIT CONTROL WIRES)
P. 08/11
SEP -09 -97 TUE 04:14 P11
ROBERTS TRANE FAX NO, 206 643 4314
Dimensional 61/4-71/2 Ton
Data Units
4 11/.
Duct Connections -- Field Fabricated
Horisantsl Unit -- Supply /fltturn
17
1/2
1s.
RETURN
P. 09/11
2 7/1"
1
SEP -09 -97 TUE 04115, PM ROBERTS TRANE
Performance
Data
Tibia 12 Static Presume Naps Ilya .% Acs anoriea (tnchaa Wets Column)
Toni Modal No.'
Flaw
1'
NOTC:
t.1ath IBA* to Beth ho' aMtal and dw !*1w norms.
FAX N0. 206 643 4314
Economist w/ Eleetne Row
CW1tA Campos Aaoemsfy
100% CA 100%611.4 9.18 Kw 27.9E Kw
0.10
0,13
0.15
0.01
002
0.03
0,01 002
0.02 004
003 0.06
0.12 0.15 003 0.02 O
0.20 0.03 004 0.07
Tat* 13 Standard MotorShaava /Fan
*sad ptpm)
Shawn . WC.075A WC.094.1
No4kion Fan Soma Fin %sad
5 Tuna Open 865 540
4 Tams Open 733 910
3 Turns Open 1*06 990
2 Twin Open 873 1050
1 Turn Own 945 1120
Closed 101S 1190
Table 14 Ow aked Motor Shorts/Fan
Speed (11pt11)
Shaine WC•75A WC•090A
Po on Fan Weed Fan Speed
S Turns Open 840 990
4 Turns Open 910 1048
3 Turns Oren 900 _ 110E
2 Turns Open 1060 1184
1 Tum Open 1120 1222
Cloned 1190 12110
�
SEP-03-97 TUE 0415 PM ROBERTS TRANE
Tu's
co
Table 15 Electrical Charactedsties - "Actors -60 Cycle
COCOMICe MOICIP random. Fon Met& • Sardird finuorme Mrsar HOS** 0 /Am -
U141
Tons AWN N ½il P1 itA Lit Voill PI 11.4 1..“ Voss Fill1•0 5tA Lit Mao 11.4 1.R
24 124 3.263 I
13 84 403
10 51 575 1
■4C477543 333 3
WC.011JA 00 3
WCVSAW tin 3
We 45043 233 3
• TA WC.0O344 4$ 3
Wr.031104W 575 3 10 err 575
25 155 300235
13 74 eV
Electrical
Data
Table 16 Unit %Wino
Unit
MintMum
Circuit Maximum
Mcdol Voitage ROM* ArrP 5845 Sim
- 075A.3: . :, :'], :,-, 187.253 • 372 - 67) ---
.,:,, VVO4775A4 414-606 241 37
WC.076AW 617433 15.4 25
Ur* Operating
WC-050A3
714 AC•030A4
WC-MAW
FAX NO. 206 643 4314
14 1.7 3C8•23:V463 3
1.7 44 23.2243/500 3
t.4 15 575 3
1,7 44 11 g
1.6 1$ 575 3 •
mont
I. 3vr valio applIts to metInwro circuit brookaf sizo Iof Cimalan ;m11■113tico.
•■••••.......................,.......■,M11111■1,.....M0.1; .......411■•••••••■••• •••■•••• If 1. V"... me w• .. .... 4 OR • •!, 0 0* •■ .: . . . f • • I I
. . . .
. .
. .
. . . .
•
. .
•
. .
. .
4.5 245 205130/450 3 4.3 32.2
23 134 2002313/403 3 32 16.1
1.5 108 575 3 25 13.2
5.3
3.2 151 205211V580 3 44 25.5
32 112 575 3 3.1 114
8.5 510
22.2 30S .8'440 3
187.253 44.1
414106 202 37
517.633 16.6 2.5
Fan Equipment Schedule
Equip
ID
Brand Name'
Model No.'
CFM
SP'
HP /BHP
Flow Contr s
Locati of Service
Location
CEcono
Applicant Address: / 4 \. . % \‘\.% Ks
. �
Applicant Phone 1 ; ,., 5 ^ � ` --,zits‘.
.,.
a %b
)1.
, K t S
Rat,
.--
" .
` EIVED
i • . l _
,,,.'ke,%
PERMIT CENTER
Cooling Equipment Schedule L.) .xz:, v,s---.‘% -N• 1 $)_
Equip
ID
Brand Name'
Model No '
Capacrty
Total CFM
OSA CFM
SEER
or EER
IPLV
Location
CEcono
Applicant Address: / 4 \. . % \‘\.% Ks
. �
Applicant Phone 1 ; ,., 5 ^ � ` --,zits‘.
.,.
a %b
)1.
, K t S
Rat,
.--
" .
Heating Equipment Schedule t,
Equip.
ID
Brand Name'
Model No'
Capacrty
Total CFM
OSA cfm
Econo
Input Btuh
_..
OutpufBluh
'
E ICierr
Applicant Address: / 4 \. . % \‘\.% Ks
, C
Applicant Phone 1 ; ,., 5 ^ � ` --,zits‘.
•,
Yom
.--
" .
Project Info
P rotect Address `
re.‘ 0 mot -.� 1.•,p,
.
Date
q -\S -q'7
6. ft-NN>\v E C� PRAW.
v.1 41")""
For Building Department Use
fly? q [3
--„\,\./.....,.., ��, a
Applicant Name
��� � � ft. R. E"
Applicant Address: / 4 \. . % \‘\.% Ks
, C
Applicant Phone 1 ; ,., 5 ^ � ` --,zits‘.
1994 Washin State Nonresidential Ener Cods; - om•Iiance Form
Mechanical Summary
•
MECH -SUM
.99 % sn.r.gtor j :ale ^lorresWeni,al c "e•gy Code Coni Deane Forms
Project Description
Briefly describe mechanical system
type and features
Compliance Option
'It available 7 As tested according to Table 14-1, 14-2 or 143.
s Flow control types. VAV, constant volume, or vanable speed.
Apra '994
I N U
P
Simple System ❑ Complex System ❑ Systems Analysis
(See Decision Flowchart (over) for qualifications)
Equipment Schedules
The following information is required to be incorporated with the mechanical equipment schedules on the
plans For protects without plans, fill in the required information below
Af required.' ,t ` 1 COP,'HSPF, Combustion Efficiency, or AFUE, as applicable.
\`)lilt' ,t JU' .,,:
System Description
See Section 1421 for full description of
Simple System qualifications.
If Heating/Cooling
or Cooling Only:
❑ Constant vol?
❑ Split system? .Economizer
'Air cooled? ( Packaged sys? ❑ <54,000 Btuh?
included?
If Heating Only:
<
❑ <5000 cfm?
<
❑ <70% outside air?
MECH -SUM
1994 Washington State Nonresidential Energy Code Compliance Forms
Decision flowchart
Use this flowchart to determine if project qualifies for Simple System Option. If not, either the Complex
System or Systems Analysis Options must be used. ,
Start
r.
System T a
yp or Cooling Only
•
Heating Only
V
<5000 cfm ?' — •-.
yes -
no ;
1994 Washin -t State Nonresidential Ener• Co {° ,Com • !lance Form
•
<70 %OA—
yes
no
Complex Systems
Reference
Sec. 1421
<54,000 Btuh•
no 'iK 1900 cfm?
(Includes)
Econo? j
nor7 yes
yes
Reference
Sec. 1423 1
•
Constant
Volume? • no
yes
Air Cooled? -- .— ___.._..._.__...
no _ I
yes 1 .
V
Packaged._
System? no
Simple System
)1
L
Reference
Sec. 1420
i
' Split
',System? no
yes
<54,000 Btu�t
'wr 1900 cfm7 no
yes
April. 1994
Reference I
Sec. 1430 I
Refer to MECH -COMP Mechanical Complex Systems for assistance in determining which Complex
Systems requirements are applicable to this project.
c
City of Tukwila
Fire Department
Fire Department Review
Control #M97 -0134
(512)
September 24, 1997
Re: Midcom - 665 Andover Park West, second floor, Building
#9
Dear Sir:
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. H.V.A.C. units rated at greater than 2,000 cfm require
auto - shutdown devices. These devices shall be separately
zoned in the alarm panel and local U.L. central station
supervision is required. (City Ordinance #1742)
H.V.A.C. systems supplying air in excess of 2,000
cubic feet per minute to enclosed spaces within
buildings shall be equipped with an automatic shutoff.
Automatic shutoff shall be accomplished by
interrupting the power source of the air- moving
equipment upon detection of smoke in the main
supply -air duct served by such equipment. Smoke
detectors shall be labeled by an approved agency for
air -duct installation and shall be installed in
accordance with the manufacturer's installation
instructions. (UMC 608)
Duct smoke detectors shall be capable of being reset
from the alarm panel. (City Ordinance #1742)
All new fire alarm systems or modifications to
existing systems shall have the written approval of
The Tukwila Fire Prevention Bureau. No work shall
commence until a fire department permit has been
obtained. (City Ordinance #1742) (UFC 1001.3)
Remote alarm annunciation indication is required if
John W. Rants, Mayor
Thomas P. Keefe, Fire Chief
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 575-4439
City of Tukwila
Fire Department
Page number 2
Yours truly,
The Tukwila Fire
cc: TFD file
ncd
2
ention Bureau
the control panel is not visible from the main
entrance. (City Ordinance #1742)
Local U.L. central station supervision is required.
(City Ordinance #1742)
Call the Tukwila Fire Department at 575 -4407 for
approval of any system shut down. Have job site
address, name and the Tukwila Fire Department Job
Number available to confirm shut down approval. (City
Ordinance #1742)
2. All electrical work and equipment shall conform
strictly to the standards of The National Electrical Code.
(NFPA 70)
This review limited to speculative tenant space only -
special fire permits may be necessary depending on detailed
description of intended use.
Any overlooked hazardous condition and /or violation of the
adopted Fire or Building Codes does not imply approval of
such condition or violation.
John W. Rants, Mayor
Thomas P. Keefe, Fire Chief
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 5754404 • Fax (206) 575.4439
wearauwart
DEPARTMENT OF LABOR AND INDUSTRIES
;THIS PEBTIFIES THAT THE PERSON NAMED HEREON IS REGISTERED AS PROVIDED BY LAW AS A
1: ete-
' " lat N' i N'tc '.0.u.k:.' "ii . . 6 U. le. ' ■ '
ok. e i . ^'-.; 1' ts. 1 b lk • ; JP4Vg,
rag 2 alt Fri 1S 7 f kt, M2 ESSZ=13
7 2 7; 1
... '4. X, • ,,, A in. .:.' Atle..t-vrArit+r ■ .
4 '711'7
,,,_,.,,r,,,,z3.,,,,,„(74,:,.„.. ,,,:,.,,,,,;:,
. 0,..q..stt•di...:1 A , , ft, • ail ,... it t
1 e4i-E#A.".14;41.f- STATE OF WASHINGTON
er JA 1/ y...4 t. ,44,
...,.....,1 ,,, a g . tilary A !'
rt
I , :6'4 , : . $ . - ) ,
, , , , , ,,IA? .4114,,
... •:-.0 •
t. DETACH TO DISPLAY CERTIFICATE—J
RECEIVED
" Y OF TUKwiLA
-
b 199?
PERMIT CENTER
F625-1052-0100 (3-92)