HomeMy WebLinkAboutPermit M97-0159 - EXODUS COMMUNICATIONSnD5\
City of Tukwila (206) 431 -3670
Community Development / Public Works • 6300 Southcenter Boulevard, Suite 100 • Tukwila, Washington 98188
Address: 2811 S 102 ST
Location:
Parcel #: 042304 -9182
Contractor License No: SHINNMI060QP
TENANT EXODUS COMMUNICATIONS
OWNER BOEING
CONTRACTOR SHINN MECHANICAL Phone: 425 - 392 -7028
19709 S.E. 19TH ST., ISSAQUAH, WA 98027
CONTACT DALE WENTWORTH Phone: 425 -392 -7028
19709 SE 19 ST, ISSAQUAH, WA 98027
******************************************** * * * * * * * * * * * * * ** * * * * * * * * * * * * * * **
Permit Description:
UMC Edition:, 1994 Valuation:
Total Permit Fee:
* * * * * * * * * ** * * * ** *********************** * * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Permit No: M97 -0159
Type: B -MECH
Category: NRES
INSTALL 7 LIEBERT AIR CONDITIONING UNITS (SPLIT
SYSTEMS) ROUGH IN 6 AND COMPLETE 1.
Permi Center horized Signature Date
I hereby certify that I have read and examined this permit and know the
same to be true and correct. All provisions of law and ordinances .
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate
or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign for and
obtain this bu lding permit.
Signature. Date: J2-,�.2Y]
Print Name :j _C„_ Title:
F�
Dale Wentworth
Cont.Llc.SHINNM1060QP
19709 S.E. 19th St. Phone (206) 392-6959
392 -7028
ISSAQUAH, WA 98027 FAX (206) 807-7365
MECHANICAL PERMIT
Status: ISSUED
Issued: 10/28/1997
Expires: 04/26/1998
20 000.00
184.13
This permit shall become null and void if: the work is not commenced within
180 days from the date of issuance, or if the work is suspended or
abandoned for a period of 180 days from the last inspection.
Project Namerienant:
XocYOS
Description of work to be done: Roc 4 &i
/.ct ..,,T4/ 6
5J id 9 = / �rr�` 4 ,v,� /.:/ cbts0,_3 0, 4 % ■
Value of Construction:
g
Site Address: �
• �'�'` V �✓.. . •
City State /Zip:
Tax Parcel Number:
D `7`
Property Owner:
cSc
Phone:
.1
Phone:
g/ X7
Fax #:
Street Address: City State /Zip:
_ /o/ 47/,/ Ai 42 J /A. 830 78'//3
Contact Person:
( Dede_ 4) e/v2zAi 0,7'4_
Phone:
V ' 702
Street Address:
. 70 S S, /7 /L J7
City State /Zip:
Fax #:
iz 0 ?z-- C 2 r
Phone:
Contractor:
C �4/ ;VA/ / c.`,
0 Standby
Street Address:
City State /Zip:
Fax #:
Architect:
/
Phone:
Street Address:
City State /Zip:
Fax #:
Engineer:
Phone:
Street Address:
City State /Zip:
Fax ft:
MISCELLANEOUS PERMIT REVIEW AND APPROVAL REQUESTED: (TO BE OUT BY APPLICANT)
Description of work to be done: Roc 4 &i
/.ct ..,,T4/ 6
5J id 9 = / �rr�` 4 ,v,� /.:/ cbts0,_3 0, 4 % ■
s )
Will there be storage of flammable /combustible hazardous material in the building? ❑ yes ❑ no
Attach list of materials and storage location on separate 8 1/2 X 11 paper indicating quantities & Material Safety Data Sheets
tJ Ab — ove Ground Tanks LJ Antennas /Satellite Dishes CI Bulkhead/Docks ❑ Commercial Reroof
❑ Demolition ❑ Fence Mechanical ❑ Manufactured Housing - Replacement only
❑ Parking Lots ❑ Retaining Walls El Temporary Pedestrian Protection /Exit Systems
❑ Temporary Facilities El Tree Cutting
MONTHLY SERVICE BILLINGS TO:
Name:
Phone:
Address:
City /State /Zip:
0 Water
0 Sewer
0 Metro
0 Standby
CITY OF TI "KWILA
Permit Center
6300 Southcenter Boulevard, Suite 100
Tukwila, WA 98188
(206) 431 -3670
Miscellaneous Permit Application
Application and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or facsimile.
WATER METER DEPOSIT /REFUND BILLING:
Name:
Address:
Data application accepted:
)o -1
MISCPMT.DOC 7/11/96
APPLICANIREQUEST,FOR MISCELLANEOUS PUBLIC WORKS. PERMITS
❑ Channelization /Striping ❑ Curb cut/Access /Sidewalk El Fire Loop /Hydrant (main to vault) #: Size(s):
❑ Flood Control Zone ❑ Land Altering: 0 Cut_ cubic yards 0 Fill cubic yards 0 sq. ft.grading /clearing
El Landscape Irrigation ❑ Sanitary Side Sewer #: ❑ Sewer Main Extension 0 Private 0 Public
❑ Storm Drainage ❑ Street Use ❑ Water Main Extension 0 Private 0 Public
❑ Water Meter /Exempt # Size(s): 0 Deduct 0 Water Only
❑ Water Meter /Permanent It Size(s):
❑ Water Meter Temp # Size(s): Est. quantity: gal Schedule:
❑ Miscellaneous ❑ Moving Oversized Load/Hauling
Dale applic n expires:
Phone:
City /State /Zip:
Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be
reviewed and is subject to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review - Applications for which no permit is issued within 180 days following the date of application shall
expire by limitation. The building officialmay extend the time for action by the applicant for a period not exceeding 180 days
upon written request by the applicant as defined in Section 107.4 of the Uniform Building Code (current edition). No application
shall be extended more than once.
Application taken by: (initials)
BUILDING OWNER OR AUTHORIZED AGENT:
SUBMIT APPLICATION AND REQUIRED CHECKLISTS FOR PERMIT REVIEW
El
Signature:
Submit checklist No: M -9
71
pate: /O --/ 7 _ 27
- '� --1
Print name:
Awnings /Canopies - No signage
Commercial Tenant Improvement
Permit
Phone:
Fax it:
Address:
El
• � ;�
City /State /Zip:
z
ALL MISCELLANEOUS P • AT APPLICATIONS MUST BE SUB ' ED WITH THE FOLLOWING:
• ALL DRAWINGS SHALL BE AT A LEGIBLE SCALE AND NEATLY DRAWN
> BUILDING SITE PLANS AND UTILITY PLANS ARE TO BE COMBINED
• ARCHITECTURAL DRAWINGS REQUIRE STAMP BY WASHINGTON LICENSED ARCHITECT
> STRUCTURAL CALCULATIONS AND DRAWINGS REQUIRE STAMP BY WASHINGTON
LICENSED STRUCTURAL ENGINEER
• CIVIL/SITE PLAN DRAWINGS REQUIRE STAMP BY WASHINGTON LICENSED CIVIL ENGINEER
(P.E.)
Copy of Washington State Department of Labor and Industries Valid Contractor's License. If
not available at the time of application, a copy of this license will be required before the
permit is issued, unless the homeowner will be the builder OR submit Form H -4, "Affidavit
in Lieu of Contractor Registration ".
Building Owner /Authorized Agent If the applicant is other than the owner, registered architect/engineer, or contractor licensed
by the State of Washington, a notarized letter from the properly owner authorizing the agent to submit this permit application and
obtain the permit will be required as part of this submittal.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND / AM AUTHORIZED TO APPLY FOR THIS
PERMIT.
MISCPMT.DOC 7/11/96
SUBMIT APPLICATION AND REQUIRED CHECKLISTS FOR PERMIT REVIEW
El
Above Ground Tanks/Water Tanks - Supported directly upon grade
exceeding 5,000 gallons and a ratio of height to diameter or width
which exceeds 2:1
Submit checklist No: M -9
71
Antennas /Satellite Dishes
Submit checklist No: M -1
El
Awnings /Canopies - No signage
Commercial Tenant Improvement
Permit
0
Bulkhead /Dock
Submit checklist No: M -10
El
Commercial Reroof
Submit checklist No: M -6
0
Demolition
Submit checklist No: M -3, M -3a
El
Fences - Over 6 feet in Height
Submit checklist No: M -9
0
Land Altering/Grading /Preloads
Submit checklist No: M -2
0
Loading Docks
Commercial Tenant Improvement
Permit. Submit checklist No: H -17
E
Mechanical (Residential & Commercial)
Submit checklist No. M-8,
Residential only - H -6, H -16
Submit checklist No: H -9
®
Miscellaneous Public Works Permits
®
Manufactured Housing (RED INSIGNIA ONLY)
Submit checklist No: M -5
El
Moving Oversized Load /Hauling
Submit checklist No: M -5
to
Parking Lots
Submit checklist No: M -4
0
Residential Reroof - Exempt with following exception: If roof structure
to be repaired or replaced
Residential Building Permit
Submit checklist No: M -6
J
Retaining Walls - Over 4 feet in height
Submit checklist No: M -1
J
Temporary Facilities
Submit checklist No: M -7
El
Temporary Pedestrian Protection/Exit Systems
Submit checklist No: M -4
0
Tree Cutting
Submit checklist No: M -2
ALL MISCELLANEOUS P • AT APPLICATIONS MUST BE SUB ' ED WITH THE FOLLOWING:
• ALL DRAWINGS SHALL BE AT A LEGIBLE SCALE AND NEATLY DRAWN
> BUILDING SITE PLANS AND UTILITY PLANS ARE TO BE COMBINED
• ARCHITECTURAL DRAWINGS REQUIRE STAMP BY WASHINGTON LICENSED ARCHITECT
> STRUCTURAL CALCULATIONS AND DRAWINGS REQUIRE STAMP BY WASHINGTON
LICENSED STRUCTURAL ENGINEER
• CIVIL/SITE PLAN DRAWINGS REQUIRE STAMP BY WASHINGTON LICENSED CIVIL ENGINEER
(P.E.)
Copy of Washington State Department of Labor and Industries Valid Contractor's License. If
not available at the time of application, a copy of this license will be required before the
permit is issued, unless the homeowner will be the builder OR submit Form H -4, "Affidavit
in Lieu of Contractor Registration ".
Building Owner /Authorized Agent If the applicant is other than the owner, registered architect/engineer, or contractor licensed
by the State of Washington, a notarized letter from the properly owner authorizing the agent to submit this permit application and
obtain the permit will be required as part of this submittal.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND / AM AUTHORIZED TO APPLY FOR THIS
PERMIT.
MISCPMT.DOC 7/11/96
READY FOR ISSUANCE
l�'� •
13 BALANCE DUE
YES O STATE CONTRACTORS LICENSE REQUIRED?
IS THIS CONTRACTOR IN THE SYSTEM? YES NO
APPLICANT. CONTACTED
Address: 2811. S
Su`i te:
Tenant: EXODUS 'COMMUNICATIONS
T?ype: B-MECH
• f
P'ar'se <l # :.042304- 9182.
Permit No: M97 -01
Status: ISSUED
Applied: , 10/17/1997
Issued: 10/20/1997
*•k k fi*'+ h ** * * *•k•k * k* * ***•k•4 k:4 k k ** * 'AA*•4 kk* *'k* * * ** k•k **•k•k k* *A•k *•k•k k*
Permit Conditions:
1 . No changes w i l l ; be made to the plans unless approved by the
Architect or Engineer and the Tu,kw la,;Bui lding. Division.
All permits , <inspection , t e' cads and: apo plans shall be
available at the ,o 6i.te Priors to the start:; of any con-
struction. These are to :;be maintained ; and avail-
Able until final inspect ion approval is granted
3. All construction to: be done`: i.n = c'otifcirmance wi Ch approved
plans and { requirements . •'of the. Uniform Bu i 1 d i;ng Code (1994
Edition) r a amendei;, Uniform•'Mechan Code (1 994.. Edition)
j '
and .Wash ngton: State E.n'ergy .Code (1994 Edition).
4. Electrical permits shall be obtained through' the' <Washington,
State DTv i si on of Labor And Industries and all el ectr,i ca l' .
work will ;he:. inspected..`by that agency (248- 6636, .,
5. MANUF�ACTURERS.INSTALLATION INSTRUCTIONS REQUIRED ON SITE
FOR INE ` BUILDING INSPECTORS REVIEW. ,
Va l idl°ty of Pei.mi t. Th�iissuance of ' 4 permit or approval o
plan, , spec)fications, and coniputaOons,shall not be, con -,,
st5ue'd to be a` per Mit for,-,o( an of, any violation
of ;any of.....he' prov:•ls, ions oMthe build code or of anv
otw or dinan Ftf jut od,ictitiif , f No per'mi t presuming
g i v eau tha i ty tot violate t or` cancel :the provisions ' of tli i
code. ys'hall"';•bec'vall4ci;,
DETERMINATION OF COMPLETENESS: (T,Th)
COMPLETE NOT COMPLETE
COMMENTS
TUES /THURS ROUTING: PLEASE ROUTE d NO FURTHER REVIEW REQUIRED E
ROUTED BY STAFF El (If routed by staff, make copy to master file & enter Sierra.)
flv'ii4' Cb REVIEW / ROUTINGLIP
ACTIVITY NUMBER M97 -0159 DATE 10/17/97
PROJECT NAME EXODUS T.I
DEPARTMENT: 0
BUILDING DIVISION El FIRE PREVENTION El PUBL C W ORKS f STRU'TURAL I P E
REVIEWERS INITIAL
APPROVALS OR CORRECTIONS: (ten days)
APPROVED n APPROVED WI CONDITIONS NOT APPROVED (attach comments) fl
REVIEWERS INITIAL
C:ROUTE -F
DATE
DATE
CORRECTION DETERMINATION:
APPROVED I I APPROVED W/ CONDITIONS
REVIEWERS INITIAL DATE
PLANNING DIVISION
0
to-ad-q
7
PERMIT COORDINATOR ❑
DUE DATE 10/21/97
NOT APPLICABLE El
DUE DATE 10/31/97
DUE DATE
NOT APPROVED (attach comments) Q
(Cetdficadon of occupancy required. )
Projgct: i� `/f
Type of iq ecti :
Addr e$yi ,� 11 k7
(�
Date called: c.:, `) .,.
Speci instructions:
•1 - .4.4 i.e. �" ' "t -c
1 .0
'��
Date wanted:
7' l - 7 - c i g
p.m.
Requester: ` 1� `
Phone No.:
L •IAS*39
-)O
•s..yY ;Y'�/1
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 9818
Of ... Approved per applicable odes.
COMMENTS:
I Receipt No.:
INSPECTION RECORD I
Retain a copy with perm & ; 1 ( - 1
0 - ID Pi N .
PERMIT NO.
(206) 431 -3670
Corrections required prior to approval.
Inspector:
Date: 2 !(
16
$42.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must
be paid at 6300 Southcenter Blvd., Suite 100. Call to schedule relnspection.
Date:
COMMENTS:
Type of inspecSion: , /
.M eC) - $6. Y) l c �,..f
fiv itJ r p'? /NSr4r,� -nd� / A
Address:
,-,2R)) S Ica
Date called:
11- .714-97
Date wanted:
Ii-?0
0229
p.m.
Special instructions:
Requester:
Gn ee-A
Phone No.: 1(n7- 64ALI9
c .Pt - w1 T14. e re /9<c r ." 0 ri !1,-Ari
4:, y„a k.£ 5ftµ Da 1 li /2,4 ,jtA"rn l .
4
ff++
I
Project: �1--
re...." vs xo-� Com m WI I < 4;..U
Type of inspecSion: , /
.M eC) - $6. Y) l c �,..f
2r
Address:
,-,2R)) S Ica
Date called:
11- .714-97
Date wanted:
Ii-?0
0229
p.m.
Special instructions:
Requester:
Gn ee-A
Phone No.: 1(n7- 64ALI9
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
Approved per applicable codes.
Inspector:
INSPEQRIC N RECORD
Retain a copy with perm'
I I
.,Mc\ 1 -0I 59
PERMIT NO,
Date: I Z4
(206) 431 -3670
Corrections required prior to approval.
ON FEE REQUIRED. Prior to inspection, ,ee must
$42.00 R INSPECTI
be paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Project:
S �
Type of inspect ���
Date called:
Address /
S D
Special instructions:
Date wanted: /F..5
Requester:
Phone No.:
..d .d1
Inspector:
$42.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must
be paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
Date:
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
Approved per applicable codes.
COMMENTS:
INSPECTION RECORD -
Retain a copy with permit
PERMIT NO.
(206) 431 -3670
' \ Corrections required prior to approval.
l oot i, -6 ' 4 `6/4,
�-Z-
Projec Xmas e eki\moKIscriraot ype
of ii
Address.
a llS. Ioa +rte
Date called:
lo-a-9
Special instructions:
Date
10
C s...
P.m.
Requester.
Phone No.: - „767_ L+cl
Approved per applicabl9 codes.
COMMENTS:
Inspector:
INSPECTION RECORD
Retain a copy with perm!
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
PERMIT NO.
Date: ( ' 7
I I $42.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must
be paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
(206) 431 -3670
Corrections required prior to approval.
Receipt No.:
Date:
* 4*** k.* * * * * * *•A * *k* * * * *:l * ** *** %k *• * A* * **A* * * ** * * **•A• * * * •1• *k *k *k
I1'.Y or 1•UKWILAw WA y. G� ..• p, 69 TRANSMIT
* 1. ** * * * ; ** ** t7:l A• * *.•k *+V * ti* ha* A *A• ** k * *k **A *A k * *:l •.k k•A *** kA•*:l••k *A **•kk **
TR NSMIT NuniN:r: 89700668 `Amount;:, 184.43 10/2J/97 11 :39
P vrent Method: .CHUCK Notation: SHINN .Mi:CI9t4ICAi.. 'nit: NAB
Permit No M97-0,159 Type: I3-MI:CH MECHANICAL PERMIT
MIT
Parcel No: 04230'- 91E32
Site Address: 2811 8 102 ST
Total Fees: 184..13
This P:?',yment 184.13 Total ALL Pmts: 104.13
Balance: .00
* * *Ak *** *kA *A *A **AA•A * *:9A+1• * * *•AA *AAA'• *4 *AAA *AiIA*• *AAAAAA•A AAA *A*
Account Code I)esc.r•iptian
000 /345.830 PLAN CHECK 7 NONRES
000/322.100' `MECHANICAL_ •- NONRES
Amount
36.33
.147.30
7q
10/30 9717 TOTAL.
• . . ,,
L!
rs`SAQUAH WA: '9802 r
00 • NLs'"I' . ( Oh
}7(eimtiON_D TEi:,;
DEPARTMENT OF LABOR AND INDUSTRIES
THIS CERTIFIES THAT THE PERSON NAMED HEREON IS REGISTERED AS PROVIDED BY LAW AS A
STATE OF WASHINGTON
RECEIVED
CITY OF TUKWILA
OCT 281997
PERMIT CENTER
F825.052.00013.92) [[
City of Tukwila
Fire Department
oc -hoc- a� f I °I 17
Fire Department Review
Control # (�C1l -, o t69
•
Re: T.I. at GXOc&tf, Corn MU() CGC.( UY1
�g1 I s t oD. 5+ :A R,
Dear Sir:
./n.xh*N'rt��vn.xCh�lvlRtl'Y <Yih/F6Y'P•14+�k%' ERCiBFiA1i'..T:N.!EK M1::Alw'{.tiT.t"n "e�}
Thomas P. Keefe, Fire Chief
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. The total number of fire extinguishers required for
your establishment is calculated at one extinguisher for
each 3000 sq. ft. of area. The extinguisher(s) should be
of the "All Purpose" (2A, 10B:C) dry chemical type. Travel
distance to any fire extinguisher must be 75' or less.
(NFPA 10, 3 -1.1)
Extinguishers shall be installed on the hangers or in
the brackets supplied, mounted in cabinets, or set on
shelves (NFPA 10, 1 -6.9), and shall be installed so
that the top of the extinguisher is not more than 5
feet above the floor. (NFPA 10, 1 -6.9)
Extinguishers shall be located so as to be in plain
view (if at all possible), or if not in plain view,
they shall be identified with a sign stating, "Fire
Extinguisher ", with an arrow pointing to the unit.
(NFPA 10, 1-6.3) (UFC Standard 10 -1)
Clear access to fire extinguishers is required at all
times. They may not be hidden or obstructed. (NFPA
10, 1 -6.5)
Fire extinguishers require monthly and yearly
inspections. They must have a tag or label securely
attached that indicates the month and year that the
inspection was performed and shall identify the
company or person performing the service. (NFPA 10,
4 -3, 4 -4 and 4 -4.3) Every six years, dry chemical and
John W. Rants, Mayor
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 5754404 • Fax (206) 575.4439
r
City of Tukwila
Fire Department
Page number 2
., a.. .... .M,..r......,,.K »..,.,...«..... ..*.nn.: s.aZR+»x.e.%111 a4xM:11:An.;t4 v:r.r: nits::
Thomas P. Keefe, Fire Chief
halon type fire extinguishers shall be emptied and
subjected to the applicable r'ecliarge procedures. (NFPA
10, 4 -4.1) If the required monthly and yearly
inspections of the fire extinguisher(s) are not
accomplished or the inspection tag is not completed, a
reputable fire extinguisher service company will be
required to conduct these required surveys. (NFPA
10A -4 -4)
Maintain fire extinguisher coverage throughout.
2. No point in an unsprinklered building may be more than
150 feet from an exit, measured along the path of travel.
(UBC 1003.4)
No point in a sprinklered building may be more than
200 feet from an exit, measured along the path of
travel. (UBC 1003.4)
Exit doors shall swing in the direction of exit travel
when serving any hazardous area or when serving an
occupant load of 50 or more. (UBC 1004.2)
3. Exit doors shall be openable from the inside without
the use of a key or any special knowledge or effort. Exit
doors shall not be locked, chained, bolted, barred, latched
or otherwise rendered unusable. All locking devices shall
be of an approved type. (UFC 1207.3)
Dead bolts are not allowed on auxiliary exit doors
unless the dead bolt is automatically retracted when
the door handle is engaged from inside the tenant
space.
4. When two or more exits from a story are required, exit
signs shall be installed at the required exits and where
otherwise necessary to clearly indicate the direction of
egress. (UBC 1013.1)
When two or more exits from a story are required and
,when two or more exits from a room or an area are
John W. Rants, Mayor
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 5754404 • Fax (206) 575.4439
City cy'llAltAta John W. Rants, Mayor
Fire Department Thomas P. Keefe, Fire Chief
Page number 3
required by U.B.C. Section 3303, exit signs shall be
illuminated. (UBC 1013.3)
Internally illuminated exit signs shall have both
bulbs working at all times. (UBC 1013.3)
5. Exits shall be illuminated any time the building is
occupied with light having an intensity of not less than 1
foot candle at floor level. Fixtures required for exit
illumination shall be supplied from separate sources of
power for. Group I, Divisions 1.1 and 1.2 occupancies and
for all other occupancies where the exiting system serves
an occupant load of 100 or more. (UBC 1012.1, 1012.2)
The power supply for the exit pathway illumination
shall normally be provided by the premise's wiring
system. In the event of its failure, illumination
shall be automatically provided from an emergency
system. Emergency system shall be supplied from
storage batteries or an on -site generator set and the
system shall be installed in accordance with the
requirements of the Electrical Code. (UBC 1012.2)
6. Maintain sprinkler coverage per N.F.P.A. 13.
Addition /relocation of walls, closets or partitions may
require relocating and /or adding sprinkler heads.
Sprinkler rotection shall be extended to all areas
where required, including all enclosed areas, below
obstructions and under overhangs greater than four
feet wide. (NFPA 13 -4- 4.1.3.2.1)
7. Maintain hose station coverage per City Ordinance
#1742 and N.F.P.A. 14. Addition /relocation of walls or
partitions may require relocating and /or adding hose
stations.
8. An approved hose station requires plans review.
(Plans must be submitted to the Fire Marshal for approval
prior to installation.) (City Ordinance #1742)
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575.4404 • Fax (206) 57$4439
•
C.:
City of Tukwila
Fire Department
Page number 4
.r .e,.v,�r..�.. r .r uwv rn a+. >.. +.r.xv.�nx•- s«..•:. mug.. n +rm ewrs, e..•. m..•v..•r•e.xy1,,, rn,.»•a dm ,*v.»r..x4 "Yrv,ner.`41•2..V.Vir •.r.te!TA :; 'i"r�u
9.. All new sprinkler systems and all modifications to
existing sprinkler systems shall have' fire department
review and approval of drawings prior to installation or
modification. New sprinkler systems and all modifications
to sprinkler systems involving more than 50 heads shall
have the written approval of the W.S.R.B., Factory Mutual,
Industrial Risk Insurers, Kemper or any other
representative designated and /or recognized by The City of
Tukwila, prior to submittal to the Tukwila Fire Prevention
Bureau. No sprinkler work shall commence without approved
drawings. (City Ordinance #1742)
All sprinkler system plans, calculations and the
contractors Materials and Test Certificates submitted
to The Tukwila Fire Prevention Bureau must be stamped
with the appropriate level of competency seal. (WAC
'212 -50)
10. Maintain automatic fire detector coverage per
N.F.P.A. 72. Addition /relocation of walls, closets or
partitions may require relocating and /or adding automatic
fire detectors.
Maintain square foot coverage of detectors per
'manufacturer's specifications in all areas including:
closets, elevator shafts, top of stairwells, etc.
(NFPA 72, 5- 1.3.4)
11. All new fire alarm systems or modifications to
existing systems shall have the written approval of The
Tukwila Fire Prevention Bureau. No work shall commence
until a fire department permit has been obtained. (City
Ordinance #1742) (UFC 1001.3)
12. All electrical work and equipment shall conform
strictly to the standards of The National Electrical Code.
(NFPA 70)
13. Required .fire resistive construction, including
occupancy separations, area separation walls, exterior
walls„ due to location on property, fire resistive
John W. Rants, Mayor
Thomas P. Keefe, Fire Chief
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575.4404 • Fax (206) 575.4439
City of Tukwila
Fire Department
Page number 5
requirements based on type of construction, draft stop
partitions and roof coverings shall` be maintained as
specified in the Building Code and Fire Code and shall be
properly repaired, restored or replaced when damaged,
altered, breached, penetrated, removed or improperly
installed. (UFC 701)
The maximum flame spread class of finish materials
used on interior walls and ceilings shall not exceed
that set forth in Table No. 8 -B of The Uniform
Building Code. (UBC 804.1)
14. Your street address must be conspicuously posted on
the building and shall be plainly visible and legible from
the street. Numbers shall contrast with their background.
(UFC 901.4.4)
In order to provide you with the fastest police and
fire protection under emergency conditions, please
post your suite, room or apartment number in a •
conspicuous place near the main entry door. Numbers
shall contrast with their background. (UFC 901.4.4)
Contact The Tukwila Fire Prevention Bureau to witness all
required inspections and tests. (UFC 10.503) (City
Ordinance #1742)
This review limited to speculative tenant space only -
special fire permits may be necessary depending on detailed
description of intended use.
Any overlooked hazardous condition and /or violation of the
adopted Fire or Building Codes does not imply approval of
such condition or violation.
Fs9i± t4. YhIh: �36�0' .NM1'i#+YY��StP'a'C ?7{41�'liY
John W. Rants, Mayor
Thomas P. Keefe, Fire Chief
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575-4404 • Fax (206) 5754439
City of Tukwila
Fire Department
John W. Rants, Mayor
Yours. truly,
7 464 4--
The Tukwila Fire Prevention Bureau
cc: TFD file
ncd
Thomas P. Keefe, Fire Chief
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 5754404 • Fax (206) 5754439
.1 7N': �yrytif,` si' e' Rw.' 4Sy""'. aG�,*: r�at�.,..}'%i�.•i, •
Project . Name K a I,
Address
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permits:
Authorized Signature
FINALAPP.FRM
City of Tukwila
Fire Department
,TUICWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
'3// 5. /v2 "—
Retain current inspection schedule
Needs shift inspection
Approved without correction notice
Approved with correction notice issued
Permit No.
a /2 7
Date
T.F.D. Form F.P. 85
John W. Rants, Mayor
Thomas P. Keefe, Fire Chief
Suite #
9s
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 575.4404 • Fax (206) 5754439
•
' I
Dato
Permit I li
0
FILE COPY
:1 Plan ChocP
and omissions an..
no: authoriall
code or ordindilik 1Jit c.
co;:y of app
J
(S9
reAt-4a4a F1.414
& ri:
xis Va1tFiV447 7ice4, pARK
E.Lni-VolIJG 2A -0x.8ava Coieff• MARK
ROOF nom cola ed•wr ADDIT7c
. cP5 (I S. 100,- • I
ENGINEERS NORTHWEST, INC. Parte- I - 4+
6869 WOODLAWN AVE. N.E.
SEATTLE, WASHINGTON 98115 ( -J` - rc' 9- -:-'u'4
53
E xAG
4
x
■•••••••••••4
1/1
EXPIRES 11/12/ 'zi9
CITY OF TUKWILA
APPROVED
OCT 27 1997
AS
WED
EV.1 frairT(TIVEr0 N
EPARATE PERMIT
11EQU1ED FOR:
Ci MECHANICAL
VELECTRICAL
ri PLUMBING
C PIPING
•
I DIVISION
TUKWILA
RECEIVED
CITY OF TUKWILA
OCT 1 7 1997
1 PERMIT CENTER
OWN: HAP
ENG'D: AAP
JOB NO:
"4.0E03
SHEET
S 0 :*
1•01111•1111■1111111/
DATE:6414197
ZXO. pt/5 T.,Z'.
•1rlvERR1eOM' 7 CN. • PAR K
.69ciat -p/MG ?,A' cx�ekaai Caen PARK)
'`' ov wAShr,y9
• ` s • o
7 � : ; x
DWN: NAP
ENG '0: 4P :
ROOF 77,P CotaPE S� . 4N,T A'D1 /
I
I
.d ,
Ifs .1
+4. 10039 ,..s;• A
S SjoNA1.olG
JOB NO: •
NO
°�ti0'8
DATE:
fob 16 l 9 7
• ENGINEERS. NORTHWEST, INC.
6869 WOODLAWN AVE. N.E. -
SEATTLE. WASHINGTON 98115
SHEET•
4'
•
EXPIRES 11/12/ 4
d
:J
f PQ7
34x2(-
TYP
6 Ko2..
Fr F-.ar
CON
e I I A/1W
•
V
umeirroommolornmzarimmi
alliirwrAml•hilliWrAMINETIO
vPY
4Y-4. nP, Z
thvOem goot
w / PS � RUi¢+ '
Ar7•rDP
(4 REG'o")
CA Gp.m
DAFT /AL Roof' frnAM1 1/4/6 PLAtW/
NorEs : vver RIF`/ 4I- _ 7a�7,F.Ns✓c�vs
A ALL t1 d s ARE. A0644/ (1ML6
Not D AS OC/s rw.o.
izezio
tt GQ'9
/et - /=o
' o)
,ex/51":
& %-x /9'
CRY OF TURWILA
APPROVED
OCT 27 1997
A': N D
BUILDING D1h_tION
RECEIVED
CITY OF TUKWILA
OCT 1 7 1997
PERMIT CENTER
&-xopus rr.
•ileA/g1tP7e047 re:cw.. PAfek •
eatia-INNG OA ..oxavw CoP ,.......,
c
•
9
V 1 ..
OWN: HAP
ENG.!):
MP
Roar iv P CoraPEN,561C thy tr Alzerwrizoi
• '
JOB t40: •
e0o
. gol 61-17
ENGINEERS NORTHWEST,' INC.
6869 WOODLAWN AVE. N.E. , • ', ,
SEATTLE, WASHINGTON 98115
SHEET:
S '2. o p 4.
.........,
ElRES 11/12/ 'At • : I
r
v
st-o"
4,70
CZrj5 i
pART'/Al- Raor f PLAN
V DitilElLISto■vs. 1 /9"--Jto-
Z ALL. /7E715 ARE "%yew L/A-44E55 otio7a/...),4s
AX/SVA/0.
•
CITY OF TUKWILA
APPROVED
OCT 2 7 1997
A::') MO lE
Ult.t):NO DI VT;InOt
. c4gtrobvILA
OCT 1 7 1997
Peurrearisa
,'xoP'/5 T.2:
!esvale 1eohrr Targ PARK
i co l_____44
PS_J�t.D11.4 2A �X,Ao 4F�
\ 4, ? /,
;• -, c G
o
� ► :. . •� `
K1 �
o- � s � G lS r e viv
DWN: RAP
ENG'D:
1
Roo, 773 Co .I ENsalt UNIT A•D)177
JOB N0:
9/
DATEz(o 19 7
ENGINEERS NORTHWEST, INC.
6869 WOODLAWN AVE. N.E.
SEATTLE,. WASHINGTON 98115 ..
SHEET
5 4 0 ,
!EXPIRES 11/12/ 98 . 1
'Gai }r ;;�`SLi k:u: +nrxv.rnt, %%42. 4.4c rus • ..,,,.nrawnr'wacn. -
�
4
P2.45N/ '
13y oT//erm
'0 /s' i7
,�1• Le - (5
PLAN v/ee-/
5E art ON A
PERMIT CENTER
f
y ,C455 / - 7 - W 7
*AO LAG 8odd'
44861). 3
/M•> ix* .867-0
/
GriNci3 Pr.
y
4x
D. F1"
CITY OF TUKWILA
APPROVED
'OCT 2 7 1997
AS NO1 ED
EiGUt13G C)1V1:�if" N
RECEIVED
CITY OF TUKWILA
OCT 1 7 1997
,
•
c riCampbtl
Company
I N C O P P O R A T I O
EXODUS
I 20 -TON DOWNFLOW I
1515 - 4 Avenue South, Suite A • Ivatle, WA 98134 -1512
206/622 -3403 FAX 206/623 -6978 Internet campbell @campbell- co.com
Campbell Company Inc., on the behalf of Liebert Corporation, is pleased to submit on
equipment as follows:
ONE (1) - LIEBERT "DELUXE SYSTEM /3" AIR COOLED PRECISION
COOLING SYSTEM complete with the following:
A.) Indoor unit:
• Vertical downflow configuration
• Infrared humidifier with autoflush cycle - provides pure water vapor with quick
response
• Finned tubular electric reheat coils, 3 -stage
• Non - locking through the door disconnect, accessible from front of system
• 4 inch filters
• Blower package with high efficiency motor, 200% drive
• High voltage circuit protection for all components
• Advanced Microprocessor Control CITY OF TUKWILA
Status /Alarm Data Unit Alarms APPROVED
Active Alarms High / Low Temperature OCT 2 7 1997
Operating Status High / Low Humidity t,S NO l LO
Alarm History Log Loss of Air Flow
Component Run Time Log Short Cycle BUILDING Divtu1ON
Change Air Filters
Local Alarms (2)
Humidifier Problem
High Head Pressure 1, 2
Low Suction Pressure
Loss of Power
Custom Alarms (up to 4 ea.)
Smoke
I
Y
tak OR, +1.01k4 .14
Ca Camp1SLl
Company
INCO rO**tto
Model Weight, # (shippin
FH290A -AAG - Indoor unit 2100
DCDF 308L - Condenser ' 8 (di 0
1515.4`h Avenue South, Suite A • .,edttle, WA 98134 -1512
206/622 -3403 FAX 206 / 623 -6978 Internet campbell@campbell- co.com
B.) Outdoor condenser with fan speed control for low- ambient control to -20 °F
Capacity @ 72/50% RH/95° ambient. is 18.7 sensible tons
Capacity @ 72/45% RH/95° ambient Is 20.9 sensible tons
• Smoke detector, with auxiliary contacts for remote monitoring
• Liquitect (2)
• Fire detector •
• Remote alarm interface (1 normally open contact to close on alarm)
• Dual Refrigeration System:
• Semi - hermetic compressors (two) 4 Step. Unloading
• TX valves, filter /drier, site glasses, dehydrators, mufflers, high/low pressure
switches
• A -frame coil with intertwined refrigeration circuits
• Stainless steel condensate pan
• . All side panels painted and finished - autophoretic powder paint
• Shut down contacts
A -
B
C
D
CABINET SECTION
Downflow
Upflow (Rear Return)
Upflow (Front Return)
Upflow (Bottom Return)
Cut Down Frame (FH Only)
Top Plenum ' ( mm) Hiah I !Too 1 IFront I [Rear 1 1 Grille 1 11" (25.4 mm) Flange
Colors: Main -z- 0K3 p Accent -
NET CAPACITY DATA
BTU /hr (kW)
❑ with Econ -O -Coil
(FE/UE Units only)
°F ( °C) DB —_(e 0 •F ( •C) WB
Total
2 '18 y0
.i 2 _
5V _% RH
Sensible
.2 y, jf CM •
•Econ- O•Coil Capacity Based on 45'F (7.2 °C) E.W.T.,
GPM (__ Ifs), psig ( kPa)
Total'
Sensible'
--
EVAPORATOR
FAN SECTION
Fan Motor Horsepower (kW) 1 • ( - P
Air Volume - CFM (I/s) L2..00
External Static Pressure - Inches of Water (Pa) O•
FILTER SECTION
— Efficiency Based
on ASHRAE
Standard 52-76
Depth
Size Quantity /Unit
! 4" (102 mm) 20 %• •
24" x 24" (610 mm x 610 mm)
4" (102 mm) 30%• •
20" x 25" (508 mm x 635 mm)
6" (153 mm) 65 %• •
18" x 24" (457 mm x 610 mm)
16" x 20" (406 mm x 508 mm�__ •
2" ( 51 mm) 20 %• •
No Filters Supplied
Extra Sets
HUMIDIFIER SECTION
111 Infrared with Autoflush
Capacity - lbs/hr (kg /hr)
kW
J Steam
Capacity - lbs/hr (kg/hr)
Steam Supply - psig (kPa)
Steam Generator
Capacity - lbs/hr ( kg/hr) I kW
Ultrasonic (Downflow)
Capacity - lbs/hr (kg/hr) kW
No Humidifier Supplied
REHEAT SECTION
#Includes Fan
Motor
Electric - 3 Stage
Capacity - BTU/hr (kW)t
Hot Water • Based on
Capacity - BTU/hr (kW)t
180 °F (82.2 °C) E.W.T.
Flow Rate - GPM (I /s)
Pressure Drop - psiq (kPa)
Steam
Capacity - BTU /hr (kW)t
Steam Supplied - °F ('C)
No Reheat Supplied
AIR COOLED
CONDENSER SECTION
Air Cooled Condenser Part Number • Direct Drive “- F --308 L..
Design Ambient - 'F (•C) c' s- cr-^
Lee -Temp Control (115V) Lee -Temp Control (208/230V)
300 Watt Heater Pads
11Fan
Speed Control 'Condenser Disconnect Switch
Heat Reclaim Module:
No Condenser and No Condenser Controls (one /circuit
CONTROL SECTION Standard Microprocessor I I Advanced Microprocessor Advanced Microprocessor w/Graphlcs
#$Terminals Located on
Wire Raceway. All Alarms
Require N.O. Contacts.
No. Local Alarms (1 only for Std.; 4 max. for Advanced & Graphics) Terminalstt, 4 Step System
1
2
3
4
I II I I I MI I I 1 1 1 I 1 1 1 I 1
—
—
—
50
51
55
24
I I i i i I i i i i i i 1 I I 1 I
1 1 1, 1 1, 1., L I 1 1 t l l L t
I I I I I I I I I I I I I I I I I I I
_�
❑ Main Fan Overload ❑ Compressor Overloads 24 Volt A.C. —
OPTIONAL EQUIPMENT
`Nonlocking
Disconnect Switch
IFloorstand ❑ w/Turning Vanes
4 yr. Extended Comp. Warranty
Locking Disconnect Switch
" ( mm) High
Liqui- Tector Panel
Quantity Liqui-Tects Unit
11Firestat
Condensate Pump
.Hot Gas Bypass
❑ One Circuit ❑ Both Circuits
Smoke Detector
Crankcase Heaters
1Quantity Encased Recorders
(Temp. & Humid) JOrder
Remote Temp. /Humid. Sensors
ft mm) Cable
Ground Wires
DI Bottle
I DI Bottle Hose Kit
(
Liebert
'090O,a.°or "aw! Po Bo. 29 '96 Cownsous Oho 43229
Project Name EXO Jl k S
Model No. F1-4 29 o A ti 6-
REMARKS
DELUXE SYSTEM /3 SPEC 4FICATION SHEET
Air Cooled Systems
Liebert Invoice No
Quantity I Date L — 7
ELECTRICAL SUPPLY REQUIREMENTS
Liebert Room Unit 460 Volt, 3 Phase, Co 0 Hertz, Z 0 Full Load Amps,
Cooled Condenser I '1fo0 Volt, 3 Phase. Co C) Hertz, G • Y Full Load Amps
8'Y. 7
'1 • 0
Wire Sizing Amps
Wire Sizing Amps
LIEBERT AIR COOLED MObILS
STANDARD FEATURES
COMPRESSORS Semi- hermetic with a suction gas cooled motor, vibration isolators, thermal overloads, oil sight glass, manual reset
high pressure switch, pump down low pressure switch, suction line strainer, reversible oil pumps, and operating at 1750 RPM CO
60 HZ and 1450 RPM ® 50 HZ. The lead/lag sequence of the compressors may be manually reprogrammed at the processor
board.
REFRIGERATION SYSTEM Dual refrigeration circuits, each including hot gas mufflers, liquid line filter dryers, refrigerant sight
glass with moisture indicator; adjustable externally equalized expansion valves, and liquid line solenoid valves.
COOLING COIL A -Frame design with interwoven circuiting constructed of copper tubes and aluminum fins manufactured by
Liebert. A stainless steel condensate drain pan is provided.
FANS Centrifugal type, double width, double inlet, dynamically balanced to a vibration tolerance of two mils in any plane with lifetime
lubricated self - aligning ball bearings rated at a minimum life of 100,000 hours. The fan motor operates at 1750 RPM for 60 HZ
and 1450 RPM for 50 HZ. The drive package is two belt, variable speed, sized for 200% of the fan motor horsepower.
FILTERS Deep pleated with a minimum efficiency rating of 20% (based onASHRAE 52 -76) located within the cabinet and serviceable
from either end of the unit (or top on downflow models).
..... . �..,,...,.,..,......._.�.; :_...
- • ..... , ... nom. tour. ot. t, nt�t. TXA •Llit•tati�tivtunrt�,. y.
•
display -fe
eeeeledr
CABINET AND FRAME Custom powder painted steel panels with 1' (25.4mm), 1 1/2 lbs. (.68 kg) insulation. A hinged control access
panel opens to a second front panel which is a protection enclosure for all high voltage components. Frame is constructed of 14
gauge heliarc welded tubular steel and painted using an autodeposition coating system.
HUMIDIFIER High intensity infrared quartz lamps over a stainless steel humidifier pan. An automatic water supply system
continuously maintains water level and an automated flush system greatly reduces mineral precipitation. A flow control valve
permits operation at water pressure between 5 and 150 PSIG (34.5 and 1034 kPa).
REHEAT Electric low watt density reheat elements of rugged finned tubular construction provides three stages of nonionizing
reheat with maximum sheath temperatures below 420 °F (215.5 °C).
4/1y
OPTIONAL FEATURES (Refer to specification sheet for options supplied)
STEAM GRID HUMIDIFICATION "Armstrong" steam separator type with an internal drying chamber and steam jacketed stainless steel
distribution manifold. The complete system includes a prepiped solenoid control valve, inverted bucket steam trap and cleanable Y
strainer.
STEAM REHEAT System is factory piped with a two -way modulating control valve and cleanable Y strainer. A F & T steam trap is factory
supplied for field installation. Reheat coil is of copper tube and aluminum fin construction.
HOT WATER REHEAT System is factory piped with a two -way modulating control valve and cleanable Y strainer. Reheat coil is of copper
tube and aluminum fin construction.
CONDENSATE PUMP Has capacity of 145 GPH (548 I/h) at 20 ft. head (58 kPa). Pump is complete with integral float switch, pump, motor
assembly, and reservoir.
UNIT DISCONNECT SWITCH Two types of switches are available.The "Nor - ockin Tvpe" consists of a non - automatic molded case switch
operational from the outside of the unit.Access to the high voltage electnc panel ompartment can be obtained with the switch in either
the "on" or "off" position. The "Locking Type" is identical except access to the high voltage electric panel compartment can be obtained
only with the switch in the "off' position.
FIRESTAT Is mounted in the electric panel compartment with the sensing element in the return air flow. Upon activation the Firestat will
immediately shut down the entire unit.
SMOKE DETECTOR Is mounted in the unit with the sensing element in the return air flow. Upon activation the smoke detector will immedi-
/"� ately shut down the entire unit and activate the alarm system.
FILTERS Three optional filters are available. A 20% prefilter, and 30% or 65% main filter may be specified (efficiency based onASHRAE 52-
76).
L1QUI -TECT SENSOR Is a solid state water sensor that has no moving parts and is hermetically sealed to keep out dust and dirt. When the
—"7 sensor detects the presence of moisture the alarm system is activated. .7.-1Ktv g
REMOTE TEMPERATURE AND HUMIDITY SENSORS Are provided in a vented case for mounting in the room to be conditioned. Includes
30 ft. (9m) of cable supplied for connecting sensors to unit.
FLOORSTAND Is constructed of heliarc welded tubular steel and available in heights from 9" to 24" (229mm to 610mm) with vibration
isolation pads provided on the adjustable legs. An optional factory supplied turning vane is available for field installation if desired.
PLENUM Constructed of steel panels with 1" (25.4mm), 1 1/2 lb. (.68kg) insulation custom painted in unit matching colors. Available in
nominal heights of 20" (508mm), 24" (610mm) and 36" (914mm) in several standard configurations.
ADVANCED MICROPROCESSOR CONTROL (AM) The advanced control system includes the following control, monitor and alarm fea-
tures: BACKLIT 4x20 LCD, SELECTABLE CONTROL LOGIC (Proportional, PID, INTELLIGENT', PROGRAMMABLE ANALOG IN-
PUTS, COMPONENT RUN HOUR DATA, TEMPERATURE ANTICIPATION, SELECTABLE HUMIDITY CONTROL, AUTOMATIC RE-
HEAT SEQUENCING, SEQUENTIAL LOAD ACTIVATION, SEQUENTIAL AUTO RESTART, PROGRAMMED HUMIDIFIER WATER
CYCLE, COMPRESSOR SHORT CYCLE CONTROL, SENSOR CALIBRATION, MANUAL COOLING OVERRIDE SWITCHES, PRO-
GRAMMABLE COMMON ALARM, ALARM HISTORY LOG, PROGRAMMABLE COiL FLUSH CYCLE, UNiT AND CONTROL DIAG-
NOSTICS, BATTERY BACKUP.
ADVANCED MICROPROCESSOR CONTROL W/ GRAPHICS (AG) Includes all the features of the Advanced Microprocessor Control
above, except the 4x20 LCD is replaced with a backlit 240x128 dot matrix graphics display. In addition, the AG includes a larger alarm
a history file, graphical plots of temperature, humidity, and the analog inputs, bar graph plots of component run history, and a graphical
floor plan layout for an optional water detection cable system.
ECON -O -COIL (Available on Downflow (FH) units only) Is a custom designed 6 -row coil of copper tubes and aluminum fins installed in
the return air portion of the unit. Full capacity of the coil is obtained at 45 °F (7.2 °C) entering fluid temperature.The coil will also provide
partial cooling as long as the entering fluid temperature is 3 °F (1.7 °C) below the room temperature and is activated at that point by the
solid state comparative circuit that compares the entering fluid temperature to the return air temperature.
4 STEP SYSTEM (Available on 8 -30 ton units only) Includes cylinder unloaders on one head of each compressor. Four steps of DX
cooling are obtained as follows: Step 1 - one compressor unloaded, one compressor off. Step 2 - both compressors unloaded. Step 3
- one compressor unloaded, one compressor on full. Step 4 - both compressors on full.
HOT GAS BYPASS Factory piped hot gas solenoid valve and externally equalized regulating valve in one or both refrigerant circuits (Not
available with 4 -Step option).
STEAM GENERATING CANISTER HUMIDIFIER This system is housed in a steel enclosure and includes a replaceable canister with
integral fill cup, fill and drain valves, and high water indicator. System automatically fills and drains as well as maintains the required
water level based on conductivity.
ULTRASONIC HUMIDIFIER (Available on Downflow (FH) units only) This system contains PIEZO electric ceramic transducers, supply
and drain valves and all electronic level sensing and other safety devices. Operational and fault indications are displayed on the
humidifier status panel. Humidifier requires DI water to operate.
DI WATER BOTTLE This is required for ultrasonic humidifier. It contains a mixed bed resin for removing minerals from the water supply.
LIEBERT AIR COOLED MODELS
"The Intelligent control approximates the actions that a human operator would take to maintain precise, stable control. The control logic uses Artificial
Intelligence Techniques including "Fuzzy Logic" and "Expert Systems" methods.
(Two refrigeration circuits required = Single circuit shown only for clarity)
Traps Every I I
25 Ft. (7.6m) 1
Of Rise
�,... 11
11
11
11
11
11
11
11
11
11
11
1
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11 '11 11 11
It ,'
11
11 1:
11 11
11
Liquid
Return
11
11
11 Shut.
Off
1 Valve
•1
11
11
11 1
11 �,
Filter
• Dryer U
I1
11
11
11
11
11
11
11
r r�I� ii
•
..
- .4
1
11
11
11
11
11
Muffler
1
1
11
11
II Hot Gas
Di scharge
•
11 14
1 1 1.
•
Fusible
1 ; '•= ' Plug
Sight
Glass
RR ANGEM ENT DIAGRAM
IR COOLED MODELS
Solenoid
Valves
Service
Valves
Schrader
Valve
Compressor
= FIELD PIPING
* Components are not supplied by Llebert
but are recommended for proper
circuit operation and maintenance
Condenser Coil
Inverted Traps on discharge'
and return lines to extend
above base of coil by a
minimum of 7 1/2 "(19Omm)
Expansion
Valve
SINGLE REFRIGERATION CIRCUIT SHOWN
FACTORY PIPING
�.. = v OPTIONAL PIPING
Evaporator
Coil
Sensing
Bulb
* Components supplied by Uebert
and must be field Installed
(FHIUH and FE/UE 245A, 290A'
and 380A models only).
AIR COOLED
MODELS
DIMENSIONAL DATA inches (mm).
SHIPPED
WEIGHT
lbs (kg)
A
B
C
D
E
F
G
H
J
50 HZ
60 HZ
—
FH -75A
FH -75A
74
(1880)
70
(1778)
33
(838)
30
(762)
72
(1829)
31
(787)
14
1/4
(362)
54 3/4
(1391)
33
5/8
(854)
1510
(685)
F4-115A
FH -114A
74
(1880)
70
(1778)
33
(838)
30
(762)
72
(1829)
31
(787)
14
1/4
(362)
54 3/4
(1391)
33
5/8
(854)
1660
(753)
114-130*
F14-125A
74
(1880)
70
(1778)
33
(838)
30
(762)
72
(1829)
31
(787)
14
1/4
(362)
54 3/4
(1391)
33
5/8
(854)
1650
(748)
114-199*
111-199A
92
(2337)
88
(2235)
33
(83
30
(762)
90
(2286)
31
(787)
14
1/4
(362)
72 3/4
(1848)
33
5/8
(854)
1880
(853)
111- 245*
141-245A
99
(2515)
95
(2413)
35
(889)
32
(813)
97
(2464)
33
(838)
16
1/4
(413)
77 3/4
(1975)
35
5/8
(905)
2100
(953)
—
FH -290A Illk
114-290A
99
(2515)
95
(2413)
35
(889)
32
(813)
97
(2464)
33
(838)
161/4
(413)
773/4
(1975)
355/8
(905)
2240
(1016)
1H -380A
114-380A
122
(3098)
118
(2997)
35
(889)
32
(813)
120
(3048)
33
(838)
16 1/4
(413)
100 3/4
(2559)
35 5/8
(905)
2780
(1260)
CABINET 'AND FLOOR PLANNING DIMENSIONAL DATA
J
Overe % Dimension
PROJECTION OF
DISPLAY BEZEL
518116mm)
7 2'
(1829mm)
SHADED AREAS
INDICATE A RECOMMENDED
CLEARANCE OF 34'(864mm)
BE PROVIDED FOR COMPONENT
ACCESS AND FILTER REMOVAL.
FOR RECOMMENDED MINIMUM
CLEARANCE REFER TO THE
INSTALLATION MANUAL.
9'
(228mm)
1'
(25.4mm)
2'
(5O.8mm)w
F
STANDARD PIPING
& ELECTRICAL OPENING
DOWNFLOW (FH) MODELS
UNIT DIMENSIONAL DATA
25.4mm)
/ I
over 0 menslon
B
PIPING OPENING
FLOOR CUTOUT DIMENSIONS
2'
"~ (50.8mm)
AIR DISCHARGE
OPENING
1'
(25.4mm)
18'
(457mm)
7/, y
UNIT PIPING OUTLET CONNECTION SIZES, inches
AIR COOLED
MODELS
A
OD CU
B
OD CU
C
NPT MALE
D
OD CU
E
NPT MALE
F
OD CU
50 HZ
60 HZ
FH -75A
FH -75A
5/8
1/2
1/2
5/8
1/2
5/8
RI -115A
FH -114A
5/8
1/2
1/2
5/8
1/2
5/8
R1 -130A
FH -125A
5/8
1/2
1/2
5/8
1/2
5/8
RI -199A
FH -199A
7/8
1/2
3/4
7/8
3/4
7/8
F11-245A
FH -245A
11/8
5/8
3/4
7/8
3/4
7/8
Fit -290A
ND
FH -290A
11/8
5/8
NA
NA
NA
NA
r
FH -380A
RI -350A
11/8
5/8
NA
NA
NA
NA
a
C - m Reheat Supp
0 - � • er Reheat
Lin
E - Stea eat R (Field sup- \ fa► sup-
plied ste. \;, th
vacuum b
F - Hot Water •, Return ---• —f
Line.
1/2" I b eam - - - --
Humi ine.
1/2"
Hu
LY
OPTIONAL STEAM HUMIDIFIER
NAL STEAM REHEAT
PIPIT .G: AIR COOLED MOL 2.LS
DOWNFLOW (FH) MODELS
PIPING OUTLET LOCATIONS
(See Cabinet And Floor Planning
Dimensions For Piping Opening Sizes.)
MONITORING
PANEL
I A
or 0
I,'' - -3/4" NPT Condensate Drain. Field pitch a min. of
: 1 /8 " (3.2mm) per ft. (305mm). A trap is
II required.
L__1/4" OD CU Humidifier Supply Line (Steam Gen /Infrared)
``- - B - Liquid Refrigerant Lines.
I
I
L - - - -A - Hot Gas Refrigerant Lines (Field install factory
supplied muffler on 245A, 290A and 380A
models).
•
RETURN
SUPPLY
Y•STRAINER
-STRAINER
STE IER
STEAM TRA
ACTUATOR
SUPPLY
Y-STRAINER
HOT WATER REHEAT COIL
ACTUATOR
HOT WATER REHEA
RETURN
SUPPLY
Y•S
ACTUATOR
HOT WATER REHEAT (2 -WAY VALVE)
OPTIONAL HOT WATER REHEAT (3-WAY VAL
//y
L Three phase electric service not by
Liebert.
Three phase connection. Electric
service connection terminals when
factory disconnect switch is supplied.
Factory installed disconnect switch
.(' *°
Smoke detector alarm connections
Field supplied 24V. Class 2 wire to
remote alarm circuits. Factory wired
contacts from optional smoke detector
are #91- comm., #92 -NO, and #93 -NC.
Common alarm connection. Field
supplied 24V. Class 2 wiring to
common alarm from pigtails 75 + 76
which are factory connected to
common alarm relay (R3).
Electrical handy box factory installed
with cover.
Hut rejection connection. Field
supplied 24V. Class 1 wiring to
interlock heat rejection from pigtails
70 + 71 which are factory connected
to compressor side switches.
Remote unit shutdown. Replace existing
jumper between terminals
37 + 38 with normally closed switch
having a minimum 50VA rating. Use
field supplied 24V Class 1 wire.
ELECTRICAL FIELD CONNECTIONS
Field supplied disconnect switch when factory installed
unit disconnect switch is not provided.
Factory installed unit disconnect switch (optiooat).
Monitoring panel.
Factory wired to components on electric
panel.
Electric service connection block.
T 'ce
ed. $
Earth ground connection (60 HZ).
Connection terminal for field supplied
earth grounding wire.
fronheaelhhignauoitage=componentlmtiftid
su
Three phase electric service not by
Liebert.
Special alarm connections. Field
supplied 24V. Class 1 wire for special
alarms. Connections made by adding
normally open contact between terminals
(24 + 50), for Standard Microprocessor.
he Advanced Microprocessor has four
alarms at terminal (24 + 50),
(24 + 51), (24 + 55), and (24 4- 56).
Analog inputs. Optional terminals 41 to 48
provide connections for shielded, twisted
pair cable to as many as four customer
supplied analog sensors (AM and AG only).
s
on
on
tilers)
t
e
Electric conduit knockouts on bottom of
wire raceway. Knockout sizes 1 3/8"
(34.9mm) or 1 3/4" (44.5mm) or
2 1/2" (63.5mm).
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
p/V
GENERAL
DISPLAY A 240 x 128 backlit dot matrix graphic LCD displays all monitoring, control, alarm, diagnostic and graphical information.
KEYPAD 5 membrane keys for easy movement through the menu - driven control.
STANDARD ALARMS
TEMPERATURE The high and low temperature thresholds are programmable between 35 °F and 90 °F (1.6 °C and 32.2 °C). The alarm
indicates excessive high or low retum air temperature.
HUMIDITY The high and low humidity thresholds are programmable between 15% and 85% R.H. The alarm indicates excessive high
or low retum air humidity.
HUMIDIFIER PROBLEM Indicates excessive high or low water levels in the humidifier pan or full canister.
HIGH HEAD Indicates a head pressure above a factory preset point. Unit is equipped with a factory preset compressor safety cutout
switch. (Provided on DX units only.)
CHANGE FILTERS Indicates the pressure drop across the filters has exceeded the customer -set level.
LOSS OF AIR Indicates a Toss of air flow in the unit based on mechanical sensing switches.
LOW SUCTION PRESSURE Indicates a suction pressure below the preset cutout point. (on DX units)
SHORT CYCLE ALARM Indicates the compressor has tumed off-on -off at least 10 times in a one hour period.
LOSS OF POWER Indicates that a power interruption has occurred.
OPTIONAL ALARMS
The following alarms are available when th
CINFAMIINGSPerlentizladra
(4) Local Alarms from below
Water Under Floor
Smoke Detected
w
.by`- Unit -An
MONITORING PANEL AND UNIT ALARMS
ADVANCED MICROPROCESSOR CONTROL W /GRAPHICS
(AG)
1 1
v ■�7► lam, 1�
e appropriate options are included with the unit.
Special Message 1
Special Message 2
Special Message 3
Special Message 4
FEATURES OF THE MONITOR
MONITOR Room conditions, user analog sensors, run hours, alarm history, unit operating status.
GRAPH Temperature, humidity, analog inputs, component run history, water detection floor plan.
SET Password protected programming of various time delays and unit configurations.
SETPOINT Password protected programming of operational setpoints/alarms.
STANDARD FEATURES
OPTIONAL FEATURE
LIEBERT AIR COOLED FAN SPEED CONTROL"CONDENSER
1j• UNIT DISCONNECT SWITCH A locking disconnect factory Installed and wired in enclosed condenser control section.
COIL Liebert manufactured coil is constructed of copper tubes in a staggered tube pattern. Tubes are expanded into continu-
ous, rippled or enhanced aluminum type fins. The fins have full depth fin collars completely covering the copper tubes
which are connected to heavy wall type L headers. Inlet coil connector tubes pass through relieved holes in the tube
sheet for maximum resistance to piping strain and vibration. Coils are factory leak tested at a minimum of 300 PSIG,
dehydrated, then filled with a nitrogen and refrigerant holding charge and sealed.
FAN(S) Blades are constructed of zinc plated steel or aluminum with a maximum diameter of 30 Inches and secured to the fan
shaft by a heavy duty hub with set screw. Fan guards are heavy gauge, close meshed, steel wire with corrosion resistant
finish. Fans are factory balanced and tested before shipment.
FAN MOTOR(S) Are provided with rain slingers, permanently lubricated bearings, and individual built -in overload protection.
Motors are rigidly mounted on die - formed galvanized steel supports.
HEAD PRESSURE CONTROL A Liebert fan speed control system is furnished consisting of a variable speed fan motor operat-
ing from 80 to 1075 RPM in 60 HZ operation and 180 to 900 RPM in 50 HZ operation. The fan motor is a specially designed
single phase motor with permanently lubricated ball bearings and internal overload protection. The control system is
complete with transducers, thermostats, and electrical control circuit factory wired in the control panel. Fan speed con-
trol is always furnished on the fan adjacent to the connection end of the condenser which runs continuously with the
compressors. Other condenser fans are controlled by ambient thermostats and are either "on" or 'off ". This system
allows for operation at ambient conditions as low as — 20 °F (— 28.9 °C).
HOUSING The condenser housing is constructed of bright aluminum sheet and divided into individual fan sections by full
width baffles. Structural support members, including coil support frame, motor, and drive support, are galvanized steel
for strength and corrosion resistance. Aluminum legs are provided with rigging holes for hoisting the unit into position.
RECOMMENDED REFRIGERANT LINE SIZES CU. OD.
UNIT
MODEL
NUMBER
TOTAL EQUIV.
LENGTH
FT m
HOT GAS
UNE
IN. mm
CSF -065
LIQUID
UNE
IN. mm
1/2 (12.7)
50 (152)
5/8 (15.9
1/2 (12.7)
1/2 (12.7)
BFBU42A
100 (30.5)
7/8 (22.2)
1/2 (12.7)
12 (12.7)
BF/13U40A
150 (45.7)
7/8 (22.2)
COF -086
5/8 (15.9)
1/2 (12.7)
50 (152)
7/8 (222)
5/8 (15.9)
1/2 (12.7)
BFBU67A
100 (30.5)
7/8 (222)
1 1/8 (28.6)
1/2 (12.7)
BF/BU65A
150 (45.7)
7/8 (222)
CSF -130
5/8 (15.9)
7/8 (22.2)
50 (152)
5/8 (15.9)
5/8 (15.9)
1/2 (12.7)
FH/UH -75A
100 (30.5)
7/8 (22.2)
7/8 (22.2)
1/2 (12.7)
CSF -175
150 (45.7)
7/8 (22.2)
COF -175
5/8 (15.9)
5/8 (15.9)
50 (152)
7/8 (22.2)
7/8 (22.2)
1/2 (12.7)
FWUII.114A1115A
100 (30.5)
7/8 (22.2)
1 1/8 (28.6)
5/8 (15.9)
FH/UII.125A/130A
150 (45.7)
7/8 (222)
CSF /CDF -291
5/8 (15.9)
1 1/8 (28.6)
50 (152)
7/8 (22.2)
4-446-424.6.).
5/8 (15.9)
FHNII.199A
100 (30.5)
1 1/8 (28.6)
7/8 (222)
C0F -330L
150 45.7
1 118 28.6
CSF /CDF- 360/349C
7/8 22.2
1 1/8 (28.6)
50 (152)
1 1/8 (28.6)
1 1/8 (28.6)
7/8 (22.2)
FWUH•245A
100 (30.5)
1 118 (28.6)
2 1/8 (54.0)
7/8 (222)
FWUH•290A
150 45.7
1 1/8 28.6
CSF -510C
7/8 22.2
1 3/8 (34.9)
50 (152)
3/4 (19.1)
1 1/8 (28.6)
1/2 (12.7)
FH/l1H•114AW115AU
100 (30.5)
3/4.(19.1)
518 (15.9)
150 (45.7)
7/8 (22.2)
5/8 (15.9)
50 (152)
3/4 (19.1)
1/2 (12.7)
FHA1H- 125AU/130AU
100 (30.5)
7/8 (222)
5/8 (15.9)
150 (45.7)
7/8 (222)
5/8 (15.9)
50 (152)
7/8 (22.2)
5/8 (15.9)
F}WII.199AU
100 (30.5)
7/8 (222)
•
7/8 (22.2)
150 (45.7)
1 1/8 (28.6)
7/8 (22.2)
50 (152)
7/8 (22.2)
7/8 (22.2)
FWUH•245AU
100 (30$)
1 1/8 (28.6)
7/8 (22.2)
150 (45.7)
1 1/8 (28.6)
7/8 (222)
50 (152)
1 118 (28.6)
7/8 (222)
1 FWUII.290AU
100 (30.5)
1 1/8 (28.6)
7/8 (22.2)
150 45.7
1 1/8 28.6
7/8 22.2
50 (152)
1 3/8 (34.9)
7/8 (222)
Fl1/UH -380A
100 (306)
1 3/8 (34.9)
7/8 (22.2)
150 (45.7)
1 3/8 (349)
1 1/8 (28.6)
50 (152)
7/8 (222)
12 (12.7)
UP126A/120A
100 (30.5)
7/8 (22.2)
518 (15.9)
150 (45.7)
7/8 (22.2)
5/8 (15.9)
50 (152)
7/8 (22.2)
518 (15.9)
UP18TA/180A
100 (30.5)
1 1/8 (28A)
7/8 (22.2)
150 45.
1 1/8 28.6
7/8 22.2
50 (152)
1 1/8 (28.6)
1/8 (22.2)
UP23942384
100 (30.5)
1 1/8 (28.6)
7/8 (22.2)
150 (45.7)
1 1/8 (28.6)
7/8 (22.2)
50 (152)
1 1/8 (28.6)
7/8 (22.2)
UP375Af374A
100 (30.5)
1 3/8 (349)
7/8 (22.2)
150 (45.7)
1 3/8 (34.9)
1 1/8 (28.6)
50 (15)
1 1/B (28.6)
7/8 (22.2)
UP475N474A
100 (30.5)
1 3/8 (34.9)
7/8 (22.2)
150 (45.7)
1 318 (34.9)
1 1/8 (28.6)
CONDENSER PIPING CONNECTION SIZES CU. OD.
CONDENSER
MODEL
NUMBER
ENTERING
HOT GAS LINE
IN. (mm)
RETURNING
LIQUID LINE
IN. (mm)
CSF -065
7/8 (22.2)
1/2 (12.7)
COF -065
1/2 (12.7)
1/2 (12.7)
CSF -083L
7/8 (22.2)
5/8 (15.9)
CDF -083L
1/2 (12.7)
1/2 (12.7)
CSF -086
7/8 (22.2)
5/8 (15.9)
COF -086
7/8 (22.2)
1/2 (12.7)
CSF -097 /107C
1 1/8 (28.6)
5/8 (15.9)
CDF/097/107C
7/8 (22.2)
1/2 (12.7)
CSF•104L
1 1/8 (28.6)
5/8 (15.9)
COF -104L
7/8 (22.2)
1/2 (12.7)
CSF -130
1 1/8 (28.6)
7/8 (22.2)
COF -130
7/8 (22.2)
5/8 (15.9)
CSF•165L
1 1/8 (28.6)
7/8 (22.2)
CDF -165L
7/8 (22.2)
5/8 (15.9)
CSF -175
1 1/8 (28.6)
7/8 (22.2)
COF -175
7/8 (22.2)
5/8 (15.9)
CSF /CDF -205L
1 1/8 (28.6)
7/8 (22.2)
CSF /CDF•217C216C
1 1/8 (28.6)
7/8 (22.2)
CSF /CDF -251L
1 1/8 (28.6)
7/8 (22.2)
CSF /CDF -258
1 1/8 (28.6)
7/8 (22.2)
CSF /CDF -291
1 3/8 (34.9)
1 1/8 (28.6)
- YYFMM."-
1-681001444
4-446-424.6.).
CDF -308L
1 3/8 (34.0)
1 1/8 (28.6)
_
C0F -330L
1 3/8 (34.9)
1 1/8 (28.6)
CSF /CDF- 360/349C
1 3/8 (34.9)
1 1/8 (28.6)
CSF -415L
2 1/8 (54.0)
1 1/8 (28.6)
CDF -415L
1 3/8 (34.9)
1 1/8 (28.6)
CSF480C
2 1/8 (54.0)
1 3/8 (34.9)
CDF•460C
1 5/8 (41.3)
1 1/8 (28.6)
CSF -510C
2 1/8 (54.0)
1 3/8 (34.9)
CDF 510C
1 5/8 (41.3)
1 1/8 (28.6)
PIPING: FAN SPEED CONTROL" CONDENSERS''
RETURNING LIQUID LINE (TYP.) �o
ENTERING HOT GAS LINE (TYP.)
INVERTED TRAPS ARE TO BE
FIELD SUPPLIED AND INSTALLED (TYP.)
WHEN INSTALLING TRAPS, CLEARANCE
MUST BE PROVIDED FOR SWING OF
END ACCESS DOOR. TRAPS TO EXTEND ABOVE
BASE OF COIL BY A MINIMUM OF 7 1/2' (190mm).
FOR RUNS LONGER THAN 150 FT. (45.7M) EQUIV. LENGTH CONSULT FACTORY FOR
PROPER LINE SIZING.
12/0
UEBERT MODEL
NO.
Note 1
NO.
FANS
A
B
C
D
TOTAL HEAT REJECTION
60 HZ Note 3
CFM (Vs)
60 HZ
Note 2
TOTAL HEAT REJECTION
50 HZ Note 3
CFM (Vs)
50 HZ
NET
WEIGHT
IN. MM.
IN. MM.
IN. MM.
IN. MM.
BTWW'F
KW/'
BTLVW F KwP
Nota 2
LBS. KG.
CSF/CDF-065
1
511/21308
441118
421067
- -
1464
.772
6866(3240)
1349
.712
5722(2700)
295 134
CSF/CDF -083L
1
511/2 1308
44 1118
42 1067
- -
1655
.873
6000(2831)
6633(3130)
6322 (2983)
5400(2548)
6322(2984)
13732(6480)
12000(56631_
1526
1751
1995
1733
1750
2698
3051
.805
.924
1.053
.914
.923
1.423
1.610
5000(2359)
5527(2608)
5268(2486)
4500(2123)
5265(2485)
11443(5400)
10000(4719)
295 134
315 143
335 152
315 143
• 420 191
425 193
425 193
CSF/CDF -086
1
511/2 1308
44 1118
42 1067
- -
1921
1.013
CSF/CDF-097
1
51 1/2 1308
44 1118
42 1067
- -
2228
1.176
1.026
CSF /CDF -104L
1
51 1/2 1308
44 1118
42 1067
- -
1945
CSF /CDF -107C
1
511/2 1308
44 1118
42 1067
- -
1938
1.022
1.545
CSF /CDF -130
2
911/2 2324
84 2134
82 2083
- -
2928
CSF/CDF-165L
2
911/2 2324
84 2134
82 2083
- -
3310
1146
CSF/CDF-175
2
911/2 2324
84 2134
82 2063
- -
3842
2.027
13266(6260)
10443(4928)
12176(5747)
12644(5967)
3502
3509
3836
4204
1.847
1.851
2.023
2.218
11055(5217)
8703(4107)
10132(4782)
10537(4972)
495 225
495 225
655 297
515 234
CSF/CDF-205L
2
911/2 2324
84 2134
82 2083
- -
3976
2.098
CSF /CDF -216C
2
911/2 2324
84 2134
82 2083
- -
4324
2.281
2.491
CSF /CDF -217C
2
911/2 2324
84 2134
82 2083
- -
4721
CSF/CDF-7.51L
3
1311/2 3340
124 3150
122 3099
- -
4965
2.819
18000(8494)
19899(9390)
11091(1W)
4577
5252
-ice
2.415
2.771
Wes-
15000(7078)
16582(7825)
1SN9j 1 Y1
, 500 227
670 305
CSF/CDF-2.58
3
1311/2 3340
124 3150
122 3099
- -
5763
3.040
�wMlrs
C D1- r
0MM4/'8848--
- -
.._486 --
SF/CDF.18L.
3
131112 3340
124 3150
122 3099
- -
5664
2.988
15665 (7392
teetle(UIe01
670 305
CSFNW•48/tr
-
..
.. ••.
..60*-
.a.480.16
24O4101Mi)
£110
-SPPO-
Ja9.a8
CSF/CDF -3490
3
131 1/2 3340
124 3150
122 3099
- -
-
6984
3.684
4.104
17397(8211)
21600(10193)
8174
6932
_�MII(IIBQr
3.256
3.657
14532(6859)
18000(8494)
916 415
815 370
CSF/CDF -4151.
4
171 1/2 4356
164 4166
82 2083
80 2032
7779
CSF/CDF -410C
4
1711/2 4356
164 4166
82 2083
80 2032
8915
4.703
25280(11933)
7981
4.211
21073(9944)
1025 466
CSF/CDF-510C
4
711/2 4356
164 4166
82 2083
80 2032
10086
5.321
21687(10234)
8763
4.623
18072(8528)
1188 540
EYE BOLTS FOR LIFTING CONDENSER
PROVIDED ON FOUR FAN
MODELS ONLY
CABINET & ANCHOR DIMENSIONAL DATA
FAN SPEED CONTROL CONDENSERS
1 3/4'
1' (44.5mm)
(25.4mm)
1 3/4'
(44.5mm)
` 4 1/4'
(108mm
4 114'
(108mm)
TYPICAL FOOTPRINT
A
70" (1778mm)
37 1 /16'I 4 LEGS FURNISHED FOR 1, 2 & 3 FAN MODELS
6 LEGS FURNISHED FOR 4 FAN MODELS
( 957mm)
PS
IL.
.ss>r
C
1/2 (12.7mm) DIAMETER
ANCHOR BOLTS (TYP.)
43 9/16'
(1107mm) �r
UNIT ANCHOR PLAN
HEIGHT TO
TOP OF
37 7/8• FAN GUARD
(962mm) 431/8'
(1095mm)
A CLEARANCE OF 30 IN. (914.4mm) IS
RECOMMENDED ON ALL SIDES FOR PROPER
OPERATION AND COMPONENT ACCESS.
1
1 . CSF model prefix is for single refrigeration circuit. CDF model prefix is for dual refrigeration circuits.
2. All condenser fan motors are 3/4 H.P.
3. Total Heat Rejection given above is per circuit for CDF models. For CSF models double the capacity shown. The Total Heat Rejection Is for each degree dif• ( /i
ferential between saturated condencing temperature and entering ambient air temperature. To calculate Total Heat Rejection per condenser, multiply table
value by temperature differential.
Electric service connection
and fuse block.
Factory wired to 24V
Class 2 control circuit.
Control interlock
Field supplied
Class 2 wiring to
interlock condenser 24V
controls to Liebert
room unit. 7/8 In.
(22.2mm) diameter
hole provided in
bottom of electric box.
Factory wired to components
on electric panel.
E
ry
gr
eld
suppiiscksaftltEgeeesedhipwire
T
soteiviied.r-
Earth ground connection (60 HZ).
Connection terminal for field
supplied earth grounding wire
when factory disconnect is
supplied.
ELE CT {{ � - -
HICAL FIELD CONNECTIONS
FAN SPEED CONTROL CONDENSERS
NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.
Electric service connection
terminals when factory
disconnect is supplied.
Factory installed disconnect
switch (opts
Electric service entrance. A 7/8
In. (22.2mm) diameter hole in a
1 1/8 in (28.6mm) knockout
provided in bottom of electric box.
Electric service, not by Lieber!.
SiogleyheurSevisitiNgwer
-09fimei■4403, Three phase br.
a Is.
I