HomeMy WebLinkAboutPermit M96-0070 - HIGHLINE COMMUNITY HOSPITALFH&#LJ N • Cim,!YlUij iTy
I L
M q0--0010
City of Tukwila �
Community Development / Public Works • 6300 Southcenter Boulevard, Suite 100 • Tukwila, Washington 98188
MECHANICAL PERMIT
Permit No: M96 -0070 Status: ISSUED
Type: B- MECHAN Issued: 07 /31/1996
Category: NRES Expires: 01/27/1997
Address: 12844 MILITARY RD S
Location:
Parcel #: 162304 -9001
Contractor License No: SELLEC *372ND
TENANT HIGHLINE COMMUNITY HOSPITAL
12844 MILITARY RD S, TUKWILA, WA 98168
OWNER HIGHLINE COMMUNITY HOSPITAL Phone: (206)000 -0000
16251 SYLVESTER RD SW, SEATTLE WA 98166
CONTACT BRUCE HIGGS Phone: 206 441 -5172
600 STEWART STREET.41400, SEATTLE , •
CONTRACTOR SELLEN CONSTRUCTION CO., INC., Phone: 206 682 -7770
P.O. BOX WA,98109
* *•k* *•k** * * * ** *** *k *�lkk * *'k * * * * *k ** ***** •k * *4'k ** * *�I**41** **** *�I** ** *SFr #"k **
Permit Descript;i•on:
REPLACE /RELOCATE TYPE I KI TCHEN HOOD EXHAUST DUCT
AND FAN (NO INDOOR SHAFT, DUCT RISER OUTDOORS).
UMC Edition: 19,94
k* k**** k******• k'* k** k*k k***•****** k* ***** k**• k' k** k' k * *'k *•k *•k* * * * * * * * *, ** ** * * *'k **
PermitCenter Authorized Signature
I hereby, certify. that I have read and examined this permit,and know the
same to ".be true and correct. 'All provisions of law and ordinances
governing this mark will be complied with, whether specified herein or not
The granting of this permit does not presume to give ,authority to violate
or cancel theprovisions of any other state or local laws regulating
construction or the performance of work. 'I am authorized to sign for and
obtain this building permit.
Signature;
Print Name: rt..le.44 1.. `46c--..D1
Valuation:
Total Permit Fee:
(206) 431 -3670
Date
Date: T G IL
Title: )UrX'
5,000.00
59.38
This permit shall beooMe null and void if the work Is not commenced within
180 days from the date of '.issuance, or if the. work is suspended or
abandoned for a period of 180' 2 daysfrom the last inspection.
Address:,
Suite:
`Ter�iatit:"
Type':
Parcel. #:
12844. MILITARY RD s
HIGHLINE COMMUNITY HOSPITAL
B- MECHAN
162304' -9001
. CITY OF TUKWILA
Permit No: M96 -0070
Status: ISSUED
Applied: 06/07/1996
Issued: 07/'31/1.996
4.444•4 4** k k•k•k•k k ' k•k • k ' k • h•kk•k•k•k•k*•k k•*•k k k•k•k.•k•k k•k*•k•k•* k•k•k•k k k•k•k•k•k•k k•k•k•k k k•k•k k
Permit Conditions.:
1. ,Na changes w i l l l be made to the plans unless ;approved by the
Architect or Engineer and the :Tuk•;wi. a B u i l d i n g D i v i s i o n .
All permits, inspection r'ecor'ds, and approved plans. shall be
available at the ..job, " prior to the .tar. t of any con-
struction. These ;documents" a r e to be m a i n t a i n e d ".and a v a i l -
a b l e until t,•ina1 i nsp'ect i onr a pprova 1 is granted
3. All construction to 'be' ",done in` conformance:with approved
plans and, r °e•qu i remen is of the ,. Uniform B u i l d i n g `Code `(1994
Edition/as amended; Uniform Mechan ical Code (1994 Edition),
and Waington 'StateEnergy',.Co.de (1994 Edition),
4, Va1iditv.of Permit The issuance, of a permit or approval,of
plans : ,:/.Specifications, and computations shall not -be con
strued to be a permit for, " an approval of, any violation,
of any of the provisions of the building code or of any
other^ or distance of the jurisdiction. No permit p're_uming to;
-yi j re3 authority to; violate• or cancel th'e provisions of this
coaet shai l . be ve l j d5 a .
MANUFACTURER'? INSTALLATION; ?INSTRUCTIONS REQUIRED ON SITE
FOR';THE.,_BUILDING , IN'SPECTORS. REVIEW.
6, . E ie+ i ca1.. perfni is he 1 1 be'.obtai.,ned " through the Washington
'Sta`ite UI`vision of Labor and Industr, ies and all electrical;;
woi i wi 1 1 ' be' i ncja ctecl by,: that. agency" .(248-6630).
7. Re'a`dily accessible`acce4s to.'rroof mounted' "equipment is
requi re;d;`.
AMOUNT
OWING:
4 t" �
�
CONTACTED
tI r U C' ,
SUITE NO.
mit ii-ay L1 Rd _.
DATE NOTIFIED
— q
BY:
(snit.)
/�/'
0
2nd NOTIFICATION
BY:
(snit.)
3RD NOTIFICATION
BY:
(init.)
PROJECT NAME
V i n.q- C_orn mean i
Boy itoi
SITE ADDRESS
la<rsqU
SUITE NO.
mit ii-ay L1 Rd _.
PLAN CHECK
NUMBER
m (0
CITY OF TUKW
Department of Community Development — Permit Center
6300 Southcenter Boulevard - #100, Tukwila, WA 98188
(206) 431 -3670
Mechanical Permit Application Tracking
INSTRUCTIONS TO STAFF
• Contacts with applicants or requests for information should be summarized in writing by staff so
that the status of the project may be ascertained at any time.
• Plan corrections shall be completed and approved prior to sending to the next department.
• Any conditions or requirements for the permit shall be noted in the Sierra system or summarized
concisely in the form of a formal letter or memo, which will be attached to the permit.
• Please fill out your section of the tracking chart completely. Where information requested is not
applicable, so note by using "N /A ", date and initial.
DEPARTMENTAL REVIEW
"X" In box indicates which departments need to review the project.
DEPARTMENT
►'4 BUILDING -
initial review
. iJ FIRE
O PLANNING
O OTHER
BUILDING -
final review
BUILDING
OFFICIAL
DATE IN :
17 /q,
DATE
APP..RO ED:
1 1 7 y�
('OU ED)
"7t2-
INIT: (G-
INIT:
INIT:
Rtb
INIT:
2
INIT:
CONSULTANT: Date Sent -
EQUjREMENTS / COMMENTS'.
Date Approved -
FIRE PROTECTION: (Sprinklers
0 Detectors
O N/A
FIRE DEPT. LETTER DATED: 70Y /KK INSPECTOR: 6/2
ZONING: JBAR/LAND USE CONDITIONS? O Yes No
SCREENING REQUIRED? 0 Yes 0 No
REFERENCE FILE NOS.:
UMC EDITION (year):
REVIEW COMPLETED
01/07/93
SITE ADD6ESS 1 2.6.44 NIA Lanai' (Zc�u Sa SUITE #
TuvLlLk Wk 92)1loPj
VALUE OF CONSTRUCTION -
`• IS oo.00 .
( - 1 k3 IV 0 6p I-01
ASSESSOR ACCOUNT #
IC= Z — 30-1 - yo01
1� _
TYPE OF WORK: ■ New /Addition' ■ Modifications Repair
■ Other; t.('►. • . t„g C A�`r1NG,
D � a.� SCllee WORK TO BE DONE: (t TNo to S ys •c ,
.�/ �ra►)c:a - 1 - S i fi \ Z- VITAL 41-..) ! = 3 c ,; ' 12.) DC:c FA-4 -) T (►i►E,e ou«ks
w'4, 1 •w , `N:F NEMPO:LlagCl'!?t:e.r , : , .f' h.•i.'IlE'$ .:a :p :g ' Pt'ME '' 4 . : .�r'�',�.•13 "`• •;Nl'1M EFC lie1:inr ^..,,e
dm La-i) S 64645 r/4-- -iLoo 3 IBS' GN>s
ZIP 9811,,(4
CONTRACTOR C >T2. �►
Co T�
BUILDING USE (office, warehouse, etc.)
1�� osPr'r4.L
NATURE OF BUSINESS: P� -T► r t
1�1�15�� 1'z�K C -n R IA. 4
WILL THERE BE A CHANGE IN USE? . 073 No • es IF YES, EXPLAIN:
WI THERE BE STORAGE OR USE OF FLAMMABLE, COMBUSTIBLE OR HAZARDOUS MATERIALS IN THE BUILDING?
No O Yes .
YES, EXPLAIN: ,
PROPERTY OWNER 1 •1 micut�C Co►. u�ul ,r�
1 �P I ri L
PHONE �.d. _ y `) U
ADDRESS • 1(DZSI Sit_ .1tsT1`. (.
S e:A.,e.►►
(
ZIP 9811,,(4
CONTRACTOR C >T2. �►
Co T�
PPHONE G �iZ - 1170
ADDRESS L7,8 1J1 t k.)E 1�
5141 1 1/- .
f ZIP `1810`f
WA, ST. CONTRACTOR'S LICENSE # S a1 LiEC
,- • � Z N 2S
'EXP. DATE . .1.---ms 1, 1997
CITY OF TUKWILA
Department of Community Development - Building Division
6300 Southcenter Boulevard, Tukwila WA 98188
(206) 431 -3670
PLAN CHECK
NUMBER
Mq (j- 0 CD — )0
APPLICATION MUST BE FILLED OUT COMPLETELY
BUILDING OWNER
OR
AUTHORIZED
AGENT
JUI•I 06 '96 09 :01A1.1_TUKWILA DCD /PI
SIGNATURE
PRINT NAME.
DATE APPLICATION ACCEPTED
ADDRESS LI 1 i��S �c TIC
q lD
MECHANIC NL PERMIT
APPLICATION
FEES (tor staff use only)
°irtiOr.. r ESC 1 ':TI° :axra
BASIm• ?
PLAN1:CH 1<yt=
'APIA; erti!r t..��:�•1; TOT %AL'�i -rr
14l'
»envy
s V
ti�.',!xG ^�r17r
ElliMMEZERINMEINEM
MEM k;wGN. ganliggi
� a '1.
� 1(..cc.c ( 1- , 11 ��.► 0.1..E = INA .
DATE APPLICATION EXPIRES
•
;I 4114Th
DATE 6 /( /e,
PHONE -44 t -, 51 2
CITY/ZIP S TflJ 58101
CONTACT PERSON boo S 14ov PHONE ,g.1 t _ r i -i z,
APPLICATION SUBMITTAL In order to ensure that your application is accepted for plan review, please make sure to till out the
' application completely and follow the plan submittal checklist on the reverse .side of this form. Application and plans
must be complete in order to be accepted for plan review.
BUILDING OWNER/AUTHORIZED AGENT If the applicant Is other than the owner, registered architect/engineer, or contractor licensed
by the State of Washington, a notarized letter from the property owner authorizing the agent to submit this permit
application and obtain the permit will be required as part of this submittal.
VALUATION OF CONSTRUCTION The valuation Is for the work covered by this permit and must be filled in by the applicant. Thls
figure Is used for budget reporting purposes only and not to calculate your fees.
EXPIRATION OF PLAN REVIEW Applications for which no permit Is Issued within 180 days following the date of application shall
expire by limitation. The Building Official may extend the time for action by the applicant for a period not exceeding 160
days upon written request by the applicant as defined in Section 304(d) of the Uniform Mechanical Code (current
edition). No application shall be extended more than once.
If you have any questions about our process or plan submittal requirements,
please contact the Department of Community Development at 431 -3670.
. kti l*** kA***** A* **** **•+•A *A*A**h•kx**A*A* * ** *? A****
CITY OF TUKWILA.. WA 1„—
*A•A*.k * *,lehk *;14vd * *k•k;k•k* A• * *• tilt 0 * *A *'k •k•kk **
TRANSMIT Number 96004559 Amount: 59.
Payment hiethodt CHECK Natation: HIGHLINI. HOS
44•1.*h4*••1A *:4A * +A *A*
TI:AN8M1T
*•A * *Aok A** * * ** *kA k•k
38 07/31./96 09:34
PI1A Init: SLt3
Permit No :"M96-0070 Type: 13•-MI CHAN MECHANICAL. PERMIT
Parcel No: 162304-9001
Site Address: 12E344 MILITARY RD a
Total Fees: 59.38
59.38 • Total ALL Pmts: 59.38
• U tl anca. .00
*k, **** k* A * * * *A*.\ '. til•k * * * *A ** *** *A *•** ** * *A*A•A*s1*** *'•** *,t** **** **
This Puvment
(Account Code
000/345.830
000/322.1.00
Description
PLAN CHECK --. NONRES
MECHANICAL 7 NONRES
Amount
11.11
4'7.50
Address
Project Name
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permits:
FINALAPP.FRM
City of Tukwila
Fire Department
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
X Retain current inspection schedule
Needs shift inspection
Approved with correction notice issued
Permit No.
Approved without correction notice ,
T.F.D. Form F.P. 85
John W. Rants, Mayor
Thomas P. Keefe, Fire Chief
Date
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Plane: (206) 575.4404 • Fax (206) 5754439
Project: J /?,(
i
/h
/
, -Mt
/ /p'
of
'
/ d7�C�C!_.
Addre�s� i ,r C,
/V G
/p�te calla .
Special instructions:
'
i/-313'
i
Date wanted:
/
z3 �// a.m
Requester:
Phone No.:
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISIO
6300 Southcenter Blvd., #100, Tukwila. WA 981
Approved per.applicable codes.
be paid at 6300 Southcent
INSPECTION RECOR6
Retain a copy with permit
I
PERMIT NO.
206)431 -3670
COMMENTS
f
Corrections required prior to approval.
$42.00 REINSPECTION C E REQUIRED. Prior to fee must
Blvd., Suite 100. CaII to schedulereinspection..
Receipt No.:
Date:
COMMENTS:
Type of inspection:
r
I_ .a .
Address - v /
/� "' A/I
-4.--*-524-A2n--1-6_
chv 4.17
el, M.C., ,
Special instruc io s: � 't"{'
G/ .g.a G/4 c 4& 1 iye._
_5ew
Phone No.:
_ 6
1
�✓;.�
o
v at.eca _/-2
A - a ex.i.-747
Sti J;
."& '
e'Q /v-- st _ /
-
0.7 ,
1 .
r (,
..4 w •
ha
4 , .14 h
ll / �� t� � �
j'-"`" «ICJ
)6 /
o __'
/
Project:
d / r • i i •
Type of inspection:
r
I_ .a .
Address - v /
/� "' A/I
ate called:
-2.46. ,-6
Special instruc io s: � 't"{'
Date wanted: Cf 23- a.rT
(C? p.m.
Requester:
Phone No.:
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
INSPECTION RECORD
Retain a copy with permit
Jo
Zst? 74
PERMIT NO.
(206) 431 -3670
-Approved per applicable codes. [:>4 Corrections required prior to approval.
Inspector:
$42.b0 REINSPECTI • N FEE REQUIRED. Prior to inspection, fee must
be paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
Date:
11 t
Project: � � �� y �
Type of inspect:
C.�7 w ,r
Address:
14 < ,Q4.
Date called:
/
Special instructions: !
Date wanted:
`� - / g(fl
a.m.
p.m.
Requester:
Phone No.:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 9818
Approved per applicable codes.
Receipt No.:
Corrections required prior to approval.
COMMENTS:
A (A c0.3 (4-k._ ( a-, a A 0�►�G�N�' r
Inspector:
2
Date : ter , ( Z -4(a
C
$42.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must
be paid at 6300 Southcenter Blvd., Suite 100, . Call to schedule reinspection.
Date:.
lM RV oo70
PERMIT NO.
(206) 431 -3670
City of Tukwila
Fire Department
Fire Department Review
Control #M96 -0070
(512)
July 24, 1996
Re: Highline Community Hospital - 12844 Military Road
South
Dear Sir:
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. An approved automatic fire - extinguishing system is
required for this project.
Commercial -type food heat - processing equipment from
which grease -laden vapors emanate in normal cooking
application shall be protected by an approved
automatic extinguishing system. The extinguisher
system shall be interconnected to the fuel and current
supply so that the fuel or current is automatically
shut off to all equipment under the hood, when the
system is actuated. (UFC 1006)
All new automatic fire - extinguishing systems and all
modifications to existing automatic fire- extinguishing
systems shall have fire department review and approval
of drawings prior to installation or modification.
2. All new sprinkler systems and all modifications to
existing sprinkler systems shall have fire department
review and approval of drawings prior to installation or
modification. New sprinkler systems and all modifications
to sprinkler systems involving more than 50 heads shall
have the written approval of the W.S.R.B., Factory Mutual,
Industrial Risk Insurers, Kemper or any other
representative designated and /or recognized by The City of
Tukwila, prior to submittal to the Tukwila Fire Prevention
Bureau. No sprinkler work shall commence without approved
John W. Rants, Mayor
Thomas P. Keefe, Fire Chief
Headquarters Station: 444 Andover Park East • Tukwila, Washington 98188 • Phone: (206) 5754404 • Fax (206) 575.4439
Page number 2
City of Tukwila
Fire Department
drawings. (City Ordinance #1742)
Contact The Tukwila Fire Prevention Bureau to witness
all required inspections and tests. (UFC 10.503)
(City Ordinance #1742)
3. All new fire alarm systems or modifications to
existing systems shall have the written approval of The
Tukwila Fire Prevention Bureau. No work shall commence
until a fire department permit has been obtained. (City
Ordinance #1742) (UFC 1001.3)
Local U.L. central station supervision is required.
(City Ordinance #1742)
Call the Tukwila Fire Department at 575 -4407 for
approval of any system shut down. Have job site
address, name and the Tukwila Fire Department Job
Number available to confirm shut down approval. (City
Ordinance #1742)
4. All electrical work and equipment shall conform
strictly to the standards of The National Electrical Code.
(NFPA 70)
5. This review limited to speculative tenant space only -
special fire permits may be necessary depending on detailed
description of intended use.
Any overlooked hazardous condition and /or violation of the
adopted Fire or Building Codes does not imply approval of
such condition or violation.
John W. Rants, Mayor
Thomas P. Keefe, Fire Chief
Headquarters Station: 444 Andover Pants East • Tukwila, Washington 98188 Phone: (206) S7S -4404 • Fax (206) 5754439
Page number
Yours truly,
SQ- f2-
The Tukwila Fire Prevention Bureau
cc: TFD file
ncd
City of Tukwila
Fire Department
John W. Rants, Mayor
Thomas P. Keefe, Fire Chief
Headquarters Station: 444Andover' East • TO Washlnlgton 98188. o phple.'(206)175-4404 Fax .(2A0) .5,7,-.4439
CITY OF TUKWILA Id: ROUT130 Keyword: UACT
F1 =Help, ESC =Exit current screen.
.User: 1677
07/17/96
Activity document routing maintenance. MECHANICAL PERMIT
Permit No: M96 -0070 Tenant:.HIGHLINE COMMUNITY HOSPITAL
Status: PENDING Address: 12844. MILITARY RD S
Route: 1 Current Route Line: 2 of 5
Packet Units Description Station Status Received Assigned Complete
aaaaaaaaaaaaaaaaaadaadaaaadadaaaaadaaaadaaaadadadadgaddaaaaadadadaaaaaaaaagaadaa
Packet Units Action Station Initials Status Received Assigned Completed
MECH 01 01 C BLDG KEN Assigned 06/07/96 06/13/96 /.. /..
Priority (0 /low..9 /high): 0
Regular hours (HH.MM): Overtime Hours(HH.MM):
Comments 1[letter sent 6 /13/96 by KEN ]
2(
3(TYPE I KITCHEN HOOD ]
4[
5[FIRE PLEASE REVIEW AND COMMENT. by KEN ]
6[
7(
BE l
l
l
9[
10[
adaaadaaaaaddadda666dda666 6. 6a66a666aaaaadaadaaaaaaaaadaaadaaaaadadaaaaadadaadda6
CITY OF TUKWILA
Department of Community Development
Building Division - Permit Center
6300 Southcenter Boulevard, Tukwila, WA 98188
Telephone: (206) 431 -3670
CONTACT PERSON: gr LL. 'S
SHEET NUMBER(S) N\ 1 - ( Z
"Cloud" or highlight all areas of revisions and date revisions.
SUBMITTED TO: " fl
RECEIVED
CITY OF TUKWILA
JUL 091996
PERMIT CENTER
REVISION SUBMITTAL
DATE: / %' PLAN CHECK/PERMIT NUMBER: ` ` O " 007 0
PROJECT NAME: )-(sIc,p-t.11— C ) It~t L4,,-c\> tiosrErt— Seca.:t tt-)
PROJECT ADDRESS: ZS 14 M 1..11 P--;' (ZI-0 C�` - )4u Qs- 9 , v
PHONE: '`('`C`
�"'�Clil>3alG�l- l�Ji�I�IE
0 0 0 ' J<;I' (7y�S
REVISION SUMMARY: r.
R:) c " �I � t a- ice r DL-c- 7 - 7 1
cAr 14--ccik1/4-4,..) w.:.(z, k(J ET
�T� L 2I .1 --) �tc.l Lt�t�C . - a t� t� 1 - \ < a AL lY
& c 01.11- .I'!�� �ci J D Fie-al-1)170 18 To W I lR e
C I
�r
Et-e c) OLc- 4
1<��Ctp��l tom.
Cc: )1-4 \I ��a11��1�C f��_�t �r� t lii�.1G� .
3/19/96
June 19, 1996
Dear Mr. Higgs,
Sincerely,
Ken Nelsen
Plans Examiner
City of Tukwila
Department of Community Development
Bruce J. Higgs P.E.
Wieland Lingren & Associates, Inc.
600 Stewart Street
Seattle, WA 98101
•
RE: Highline Community Hospital Kitchen Hood
Plan check number M96 -0070
John W Rants, Mayor
Steve Lancaster, Director
Thank you for your response to my June 7, 1996 letter. Staff review of your June 17,
1996 proposal and other acquired information regarding this building has determined our
department would .not approved the omission of the 2 -Hour shaft enclosure. This
determination is primarily due to a lack of 2 -Hour occupancy separations between the
existing kitchen /cafeteria and other floors or adjoining spaces. Presently it appears the
fire resistive requirements for this facility are already compromised.
Should you have questions or wish to discuss this further please call me at 431 -3677.
h.�M .Snuthrenter Rnalpvarrl_ Ruth? limn. • Tilkwtla_ Washtndtnn OR 1 RR • • . /2Ah) 4 1. ?h7n • • Far. 12nhi ttl hghM
JUN -17 -1996 16:18
Wieland Lin
•
•
•
ENGINEERS
City of Tukwila
Department of Community Development
6300 Southcenter Blvd, Ste 100
Tukwila, WA 98188
Attention: Ken Nelsen, Plans Examiner
Reference: Highline Community Hospital Specialty Center
Kitchen Hood Exhaust Duct
Plan Check Number M96 -0070
Dear Mr. Nelsen:
Wieland Lindgren 206 441 5175 P.001
Plaza 600 Suite 1400
600 Stewart Street
Seattle, Washington 98101
(206) 441 -5172
(206) 441 -5175 FAX
June 17, 1996
We received your preliminary review comment that notes the UMC 507 requirement for
a fire -rated enclosure around that portion of the grease duct concealed above the
suspended ceiling assembly. We are aware that this requirement applies in certain
situations, but request that you consider an alternate NFPA viewpoint and our proposal
that such a duct enclosure may be omitted for this project,
• NFPA 96, Figure A- 1- 31(c), illustrates that a duct enclosure is not required until
the duct passes vertically through a fire -rated floor. In this project, the entire run
of duct inside the building is located above the ceiling of the room in which the
hood is located. Since this duct does not penetrate a fire -rated floor, NFPA does
not require a duct enclosure.
A mitigating factor is that both the room and the ceiling cavity are presently
protected with automatic fire sprinklers. The jurisdiction that approved the
present installation, which has no duct enclosure in this ceiling space, likely
considered the positive aspect of non - required sprinklers above the ceiling when
they interpreted requirements of applicable codes and standards.
The new duct will be protected with sprinkler heads inside the duct, which is an
Improvement when compared to the present installation which has no such
sprinklers,
The new duct will run directly as possible to outdoors, which is again an
improvement when compared to the present installation which routes through
three floors of Hospital space.
F.- E C
JUN 8 1996
coMm i..UN =Ty
rtirin•�, w
JUN -17 -1996 16:19
Wie1ag ij ,xen
Bruce . Higgs, P.E.
Project Engineer
Wieland Lindgren
3.75" Remaining space available to install duct
Sincerely,
WI • N ', INDGREN AND ASSOCIATES, INC
Enclosure: 1994 NPFA 96, page 23
206 441 5175 P.002
Mr, Ken Nelson
June 17, 1996
Page 2 of 2
• Existing construction severely limits the space available to install a duct
enclosure. If a UL Listed duct enclosure, such as the Pabco "Super Firetemp -L"
system is used, remaining space to install the duct would be as follows:
19.50" Available bottom of ceiling to bottom of concrete structure
- 1.50" Ceiling runner
- 1.00" Clearance to remove ceiling tile
- 6.25" Height required to slope duct 1/4" per foot over 25' run
- 3,00" UL Listed enclosure on bottom of duct
- 0.50" Clearance between bottom of duct and duct enclosure
- 0.50" Clearance between top of duct and duct enclosure
- 3.00" UL Listed enclosure on top of duct
The minimum duct size for 4200 CFM (for medium temperature appliances
presently installed) at 2500 FPM would be 64.5" x 3.75 ", while the minimum duct
size for 5600 CFM (as designed for possible future high temperature appliances)
would be 86" x 3.75 ". Neither of these duct sizes are practical.
We respectfully request that you consider all factors discussed herein, particularly the
interpretation by NFPA and the presence of sprinklers above the ceiling, and approve
the design as proposed.
' JUN -17 -1996 16:19
C
C
C
Fire -rated
roof-ceiling
assembly
4- e.2.1(b)
4-7.1:
Non -tire -rated ceiling
Idieland Lindgren
4.82.1(a) Di roe
4--10 ft 0 in. 4 / Exhaust fart
4-3.3 & 1. 3.1.3:
access panel
access panel
40 in.
weather•prot • opening
sealed around the duct at
this point, since fire -rated
roof - ceiling assembly
Fur SI uniu: 1 in. • 25.4 mm: 1 fl • 0.505 m
Figure A- l..2(b) Typical action view for one -story building with fire -ratad rookeiUag assembly,
4.8,2,1(a)
48.2.1(b)
4 -72.1: not less than 1 -hr fire resistance
for building less than 4 stories in height
4- 7.2.2: not less than 2 -hr fire resistance
for building 4 stories or more in height
Fire -rated floor --►
4 -5.1:
duct
Exhaust hood
Discharge
10 1r 01n. ---► 4
4.7.1:
sealed around the duct at
this ins since fire -rated
APPENDIX A
apply
Exhaust fan
4-3,3 a 1- 3.1.3:
access panel
e:
206 441 5175 P.003
.--- Root
4-7.2.1: 1-hr rated
continuous
enclosure
nee notes in Figure A- 1.3.2(a)
to this drawing.
access panel
4-7.1:
weatheaprotadad opening
►� ,' f
IM�t
_`•.•_m it ■r Second story
4.5.1: giease duct
1,
f 1
/
Exhaust hood
4— Roof
4-3.4.3: access panel
4 -7.5: opening in enclosure
Note:
Clearance notes in Figure A-1-3.2(a)
apply also to this drawing.
96 -23
For St, unit 1 in. • 25.a sum; I ft • 0.503 in
Figure *14.2(c) Typical sedan view for buildlai wide two 'mica or now will .orals -enai ailing and iretawd Scar.
104 Edition
Tr 0 MC14
June 13, 1996
City of Tukwila
Department of Community Development Steve Lancaster, Director
Bruce J. Higgs P.E.
Wieland Lingren & Associates, Inc.
600 Stewart Street
Seattle, WA 98101
RE: Highline Community Hospital Kitchen Hood
Plan check number M96 -0070
Dear Mr. Higgs,
John W Rants, Mayor
Initial review of the subject project appears to show the proposed grease duct will be
concealed within a suspended ceiling assembly. If this is the case, a separate building
permit for a two hour duct enclosure conforming with U.M.C. Section 507 will be required
prior to approval of this mechanical application.
To confirm you have received these comments, contact. this office and /or submit
revisions within ten working days. Feel free to call me if there are any questions
8:30am to 5:00pm at 431 -3670.
Sincerely,
Ken Nelsen
Plans Examiner
6300 Southcenter Boulevard. Suite #100 . Tukwila. Washtnaton 98188 • 120614313670 • Fax 12061 431-3665
' '" . REGISTRATION NUMBERS :
EXPIRATION DATE '
0 I
• :'.. SELLS w*372NQ..
LFF :git I'VE.- . ..DATE•'
•
0a
06/20/63.-
t.C.t1�J�aT . trOl�l7' . �.�EI .AL
111
EL:Eh et 310TR' CO INC
, P 0 BOX 9970
SEATTLE WA 901x.15'
. By: th,
Gary D. Haut
General Contractors
Construction Management
SELLEN
Construction Company
r u...u. „+ �
, •1,, .,•R1,ar t+,,.•i•FTi1'1,,. ii,w T ...
I
Pi yI
•
4
1!; STATE OF WASHINGTON
i;
'ss
31
DEPARTMENT OF LABOR AND INDUSTRIES
THIS CERTIFIES THAT THE PERSON NAMED HEREON IS REGISTERED AS PROVIDED BY LAW AS A
F525.442•S00,34Z
I certify that the above registration number is true and accurate as a sworn notary in the
City of Seattle, State of Washington, County•of King.
Date
228 Ninth Avenue N
Post Office I3ox 9970
Seattle, Washington Tel (206)• 682.7770
98109 : 0970 Fax (2064623.5206
KITCHE
HIGHLINE COMMUNITY HOSPITAL, SPECIALTY CENTER
OWNER
CONTACT: MARK BENEDUM
ARCHITECT
CONTACT: RICHARD SALOOGA. RA.
STRUCTURAL
CONTACT: ROBERT ANDERSON, P.E.
MECHANICAL
CONTACT: BRUCE HIGGS, P.E.
ELECTRICAL
CONTACT: DOUG BOBS, P.E.
CONTRACTOR
CONTACT: DENNIS DICKERT
PROJECT INFORMATION
JOB SITE ADDRESS:
OWNER:
CONTACT:
TAX PARCEL NUMBER:
LEGAL DESCRIPTION
12844 MILITARY ROAD SOUTH
NI. , WA 98168
HIGHUNE COMMUNITY HOSPITAL
16251 SYVESTER ROAD S.W.
BURIEN. WASHINGTON 98166
WIELAND UNDGREN AND ASSOCIATES, INC.
600 STEWART STREET, SURE 1400
SEATTLE, WASHINGTON 98101
162- 3049001
PROPERTY CLASSIFICATION: RM -900 w/ RS -7200 SINGLE FAMILY
PROJECT CLASSIFICATION: PERMITTED USE - HOSPITAL
PERMITTING AUTHORITY: CITY OF TUKWILA
KING COUNTY, WASHINGTON
IN THE COUNTY OF KING. STATE OF WASHINGTON:
THAT PORTION OF THE NORTH ONE -HALF OF THE NORTH NORTHEAST ONE - QUARTER OF SECTION 16,
TIVP, 23N, RANGE 4E. W.N.. IN KING COUNTY, WASHINGTON, LYING EASTERLY OF MILITARY ROAD.
EXCEPT THAT PORTION OF THE NORTHEAST ONE -0UARTER OF THE NORTHEAST ONE - QUARTER OF
SECTION 16, TWA, 23N RANGE 4E, W.M., IN KING COUNTY, WASHINGTON, DESCRIBED AS FOLLOWS:
1. BEGINNING AT A POINT ON THE SOUTH UNE OF THE NORTHEAST 1/4 OF THE
NORTHEAST 1/4 OF SAID SECTION 18, DISTANT EAST 561 FEET FROM THE SOUTHWEST
CORNER THEREOF; THENCE NORTH, AT RIGHT ANGLES 184 FEET, THENCE WEST
ON A UNE PARALLEL WITH SOUTH UNE OF SAID SUBDIVISION 225 FEET; THENCE
NORTH AT RIGHT ANGLES 210 FEET THENCE WEST ON A UNE PARALLEL WITH
SOUTH UNE OF SAID SUBDIVISION TO THE EASTERLY UNE OF MILITARY ROAD;
THENCE SOUTHERLY ALONG SAID EASTERLY UNE OF MILITARY ROAD TO AND
INTERSECTING WITH THE SOUTH UNE OF SAD SUBDIVISION TO POINT OF BEGINNING,
AND EXCT THAT PORTION OF THE NOTHEAST 1/4 OF E TH NORTHEAST /4 F SECTION 18,
TWA, 23N, EP RANGE :e . IN KING CO WASHINGTON. DESCRIBED AS 1 FOLL
2. BEGINNING AT THE INTERSECTION OF THE SOUTH UNE OF THE NORTH 150 FEET OF
SAID SUBDIVISION WITH THE EASTERLY MARGIN OF MILITARY ROAD; THENCE EASTERLY
ALONG SAD SOUTH UNE 200 FEET; THENCE NORTHERLY AT RIGHT ANGLES 160
FEET TO THE NORTH UNE OF SAD SUBDIVISION; THENCE WESTERLY ALONG SAD
NORTH UNE TO THE EASTERLY UNE OF SAID MILITARY ROAD; THENCE SOUTHERLY
ALONG SAID EASTERLY UNE TO THE POINT OF BEGINNING; EXCEPT THAT PORTION
IF ANY, CONVEYED TO KING COUNTY FOR 128TH STREET, BY DEED RECORDED
UNDER AUDITOR'S FILE NO.5274608.
tYb 000
HOOD EXHAUST DUCT
HIGHLINE COMMUNITY HOSPITAL
16251 SYLVESTER ROAD S.W., BURIEN, WA 98166
NORTHWEST ARCHITECTURAL COMPANY, P.S.
303 BATTERY STREET, SEATTLE, WA 98121 (206) 441 -4522
ANDERSEN BJORNSTAD KANE JACOBS, INC.
800 5TH AVENUE, SURE 3800, SEATTLE, WA 98104 (206) 340 -2255
WIELAND LINDGREN AND ASSOCIATES, INC.
600 STEWART STREET, SURE 1400, SEATTLE, WA 98101 (206) 141 -5172
SPARLING, INC.
720 OUVE WAY, SUITE 1100, SEATTLE, WA 98101 (208) 667 -0520
SELLEN CONSTRUCTION CO.
228 NINTH AVENUE NORTH, SEATTLE, WA 98101 (206) 682 -7770
BUILDING INFORMATION
BUILDING CODE:
OCCUPANCY TYPE:
CONSTRUCTION TYPE:
NORTH WINO
WAS HINGTON STATE BUILDING CO
(199 UNIrDRN BUILDING CODE AS IVAMENOED)
GROUP I, DMSION 1.1
TYPE II - ONE HOUR, FIRE SPRINKLERED
N
O VICINITY PLAN
NO SCALE
CONSTRUCTION
\I� PARKING
-
\
DUMPSTER AREA
\
N
N
E CAMPUS PLAN
NO SCALE
INDEX OF DRAWINGS
MO.1 COVER SHEET
MECHANICAL
M1,1 DEMOLITION AND I-NRC PLANS
52.1 SECTIONS AND DETAILS
ELECTRICAL
E1.1 PLAN AND PANEL SCHEDULE
F 1
- - 1
EXTERIOR
MATERIAL
STORAGE
AREA
MATERIAL
DELIVERY
AT FLR. 1
1 W _CT
Ho
L � Pul EU NN �o
n III
Ulwur.
JUL' 9 1
7
7
. i I v r iV�rcwil n
11 it I IY 6
,Lin, CENTER
7 A k e
rnvrp currT
REVISIONS
E 7/8/96 REISSUE
•
b
C,
M
0.1
% WU NO 2458 -02
TILE 245850 -1
DRAWN AEW
CHLCKED 9JH
DATE 6/7/96
NA>WAr- —
.11
L
Lk
CURRENTLY INSTALLED INCLUDING
n -� a RANGE
NEW FAN DUCT -
SIZED TO ..: FUTURE
TO 5 CFM FOR
DGR
10 8
k r% 36/ y.
11ra k�
M2.1
SPRINKLER H
IN HOOD (E) ( 2)
' ^u�= '.ENC
POC, 4
TYPE Bf 0ST HOOl (E),
14'x4 "FF;JTPRINT, (8) pO'x20'
EXPANDED METAL FIL �'. (E),
4200 CFM REQUIRED i.R
• MEDIUM TEMP APP
CUR
"CNF=RENGC!a NO C1 =
R
AND OVENS,
WORK
INCREASE
HIGH TEMP APP
HOOD SPRINKLER CO F •
VALVE BELOW CEILING E)
18' WAINLESS $FEEL SOFFIT (E)—
I� I ,
Ij I —
S ORAGE
200.5
N
TIC
M1.
ET>IRAY
OC/
GM I,'S
AINITGR IE E� EDOM WOMEN
0 E I B a
BASEMENT PLAN
SCALE: 1/8 = 1' -0"
HIGH & LOW SPEED KITCHEN HOOD
EXHAUST FAN SWITCHES (E)
•
AUTOMATIC WET SPRINKLER
COVERAGE (E) PROVIDED
`ABOVE AND BELOW CEILINGsER
IN KITCHEN.
ao
or. -
NC.
STORAGE
a0i
N N;
55' -8'
NJ
- -25' CE WEB OF CONCRETE
PAN JOIST FOR / 1ST
+� CL WINDO�W,�uu(E) ANDRNEW SLAB.
DUCT
ROUTE DUCT THROUGH
EXISTING WINDOW
OPENING
34 10
ER /)10
LIG FIXTURE (E)
SPRII1 R HEAD (E)[
DIFFUSER (E)
NF
ND.
NB
M1.1
N N)--
N NE-
NG
N C:- --
N A ;W
�n F T—f DTI
jJ
M 000
m PARTIAL FIRST FLOOR PLAN
NB
NB
NC;
NC.
t
ED = FLOOR FLOOR PLAN
SCALE: 1 1 -0
4) PARTIAL THIRD FLOOR PLAN
ND
—
— —NA
'N
7
GENERAL NOTES:
ROOF PLAN
SCALE: 1/8" = 1
KITCHEN HOOD EXHAUST FAN
1. SCOPE OF WORK INCLUDES ALL LABOR AND MATERIALS (I.E. MECHANICAL, ELECTRICAL, GENERAL,
ETC.) TO: 1) PROVIDE A COMPLETELY OPERATIONAL KITCHEN HOOD EXHAUST SYSTEM DOWNSTREAM
OF POINT OF CONNECTION TO EXISTING HOOD, AND 2) REMOVE EXISTING DUCTWORK AND
REPAIR ADJACENT GENERAL CONSTRUCTION AS REQUIRED.
2. WORK SHALL COMPLY WITH CODE REQUIREMENTS OF ALL AUTHORITIES HAVING JURISDICTION,
INCLUDING STATE OF WASHINGTON, COUNTY OF KING, CITY OF TUKWILA, AND ALL OTHER
APPLICABLE FEDERAL, STATE, COUNTY AND LOCAL STATUTES AND ORDINANCES. THE EDITION
OF SUCH DOCUMENTS, INCLUDING AMENDMENTS AND UPDATES ADOPTED OR ISSUED BY NE
REGULATORY AGENCY, IN FORCE AT THE TIME OF SUBMISSION FOR PERMIT(S) SHALL APPLY.
WORK SHALL ALSO COMPLY WITH RECOGNIZED INDUSTRY STANDARDS AND PRACTICES. APPLICABLE
CODES AND STANDARDS INCLUDE, BUT ARE NOT UNITED TO, NE FOLLOWING:
UNIFORM BUILDING, MECHANICAL, PLUMBING, AND FIRE CODES, AS ADOPTED BY THE CITY OF TUKWILA.
NFPA STANDARDS, PARTICULARLY 13 AND 96.
3. ARRANGE AND PAY FOR ALL PERMITS, FEES AND INSPECTIONS EXCEPT THAT OWNER WILL
SUBMIT FOR MECHANICAL PERMIT.
4. SUBMIT PRODUCT DATA AND OPERATION AND MAINTENANCE MANUAL FOR EXHAUST FAN,
RECORD DRAWINGS AND BALANCING REPORT FOR APPROVAL BY ENGINEER.
5. SCHEDULE WORK FOR MINIMAL DISRUPTION OF NORMAL HOSPITAL OPERATIONS. INSTALL AS
MUCH WORK AS PRACTICAL DOWNSTREAM FROM PENETRATION THROUGH EXTERIOR WALL
PRIOR TO REMOVING EXISTING SYSTEM FROM SERVICE. SCHEDULE DOWNTIME WITH OWNER
AT LEAST ONE WEEK IN ADVANCE.
6. DUCTWORK SHALL BE CONSTRUCTED USING MATERIALS SPECIFIED BELOW, WITH ALL SEAMS AND
JOINTS CONTINUOUSLY AND EXTERNALLY WELDED LIQUID- TIGHT:
BASE BID - 18 GA STAINLESS STEEL WITH NO. 4 FINISH AND ALL WELDS GROUND SMOOTH.
ALTERNATE BID - INTERIOR DUCTWORK SAME AS BASE BID, EXTERIOR DUCTWORK 16 GA BLACK
CARBON STEEL, FINISHED WITH ONE PRIME COAT AND TWO FINISH COATS OF SEMI -GLOSS
ENAMEL SUITABLE FOR SERVICE TO 250'F, COLOR TO MATCH EXTERIOR WALLS.
7. DUCTWORK SUPPORTS SHALL BE CONSTRUCTED OF SAME MATERIAL AND FINISH AS DUCTWORK.
ANCHORAGE TO CONCRETE SHALL BE DRILLED EXPANSION TYPE INSERTS. ANCHORAGE TO
DUCTWORK SHALL NOT PENETRATE DUCT WALLS. SUPPORTS SHALL COMPLY W/ REQUIREMENTS
FOR UBC SEISMIC ZONE 3.
8. MOTOR STARTER AND POWER AND CONTROL WIRING FOR NEW FAN, AND DEMOLITION OF SAME
FOR EXISTING FAN. SHALL BE PROVIDED UNDER DIVISION 16.
A
/&
-'NB
CONSTRUCTION NOTES:
REMOVE DUCT FROM CONNECTION AT HOOD IN BASEMENT UP
TO AND INCLUDING EXHAUST FAN ON ROOF. CLEAN INSIDE OF
DUCTWORK W/ DETERGENT SOLUTION PRIOR TO DEMOLITION.
CAP DUCT OPENING IN TOP OF HOOD.
REMOVE SHAFT WALLS. INFTLL SLAB PER DETAIL 3/62.1.
PROVIDE FLOOR COVERING & LAY -IN CEILING TO MATCH
ADJACENT EXISTING CONSTRUCTION.
INFILL SLAB PER DETAIL 3/M2.1
4> INFlLL SLAB PER DETAIL 3/62.1. PATCH SHAFT WALL AND
PROVIDE FINISH TO MATCH ADJACENT EXISTING CONSTRUCTION.
›. REMOVE CURB. INFlLL SLAB PER DETAIL 3/M2.1. PATCH
ROOF TO MATCH ADJACENT EXISTING CsNSTRUCTION.
RELOCATE AND /OR ADD SPRINKLER HEADS IN CEILING
AS REQUIRED TO PROVIDE COMPLETE COVERAGE BENEATH
ENTIRE RUN OF NEW DUCT BELOW CEILING.
PROVIDE LISTED CORROSION- RESISTANT SPRINKLER HEAD W/
EXTRA HIGH TEMPERATURE (325 -375F) RATING AT 10' ON CENTER
IN DUCTWORK INSIDE BUILDING STARTING NO GREATER THAN 5'
FROM CONNECTION TO HOOD. INSTALL THROUGH TOP OF DUCT AND
PROVIDE 18'x7' ACCESS DOOR ADJACENT TO EACH SPRINKLER HEAD.
RELOCATE LIGHT FIXTURE (4 TYP)
REROUTE EXPOSED STEAM PIPE BENEATH EXPOSED DUCT.
USE PIPE AND INSULATION TO MATCH EXISTING.
ft��N� <,1v1s1aN,
RECEIVED
,,I�v of ruKwn.n
111 ',I 1 1996
PERMIT CENTER
nmireI ITI/'D1.1 A kIPA II\ /A/s 191 A \IC'
REVISIONS
0 7/8/96 REISSUE
WLA NO 2458 -02
RILE 245861 -1
DRAWN AEW
CHECKED BJH
DATE 6/7/96
ROOF
THIRD FLOOR
SECOND FLOOR
FIRST FLOOR
KITCHEN EXHAUST
HOOD (E)
BASEMENT
1 77 1 /z 84'
DUCT
ESCUTCHEON ALL AROUND
EXISTING CONCRETE WALL 7
ESCUTCHEON ALL AROUND
SLEEPER
SEE DETAIL
18/24 STACK
M21 I M2.1
(A1 SECTION
M1.1 M2.1 SCALE: 1/4' = 1' -0'
M2.1
M2.1
M21
3
M2.1
CAP EXISTING OPENING 10/34
POC SLOPE 1 /4 '/FT ON -. 10/36
INFILL WALL DETAIL
2 /
WELD
SLOPE 1/4 /FT
SUPPORT P
79'
FAN INLET
ANGLE FIANCE
DUCT
r
BOLT
GASKET (1500'F)
TRANSITION FIAT IN BOTTOM
24'x9' ACCESS
DOOR SEE DETAIL
12/34 RISER
T
2' DRAIN W/
SCREWED CAP
SUP JOINT W/ GASKET
NOT EXPOSED TO AIR STREAM
M2.1 I M2.1
19
CEILI
'NHL WALL DETAIL
KNEE - BRACED 6' HIGH A TOP
SUPPORT (TYP) AND BOTTOM
M2.1 M2.1
95 /Z
18'x30' ACCESS DOOR
5/8' TYPE X GYPSUM BOARD
PAINT TO MATCH WALL
GALVANIZED METAL STUD,
STAGGER TO MATCH DEPTH
OF OPENING
MINERAL WOOL INSULATION
ALL AROUND
1/2' TYPE X GYPSUM BOARD
SELF FURRING GALVANIZED
METAL LATH OVER GRADE D
BUILDING PAPER
7/8' PORTLAND CEMENT PLASTER
(3 COAT, PAINT TO MATCH WALL)
FIRST FLOOR T
17'
BASEMENT
LJ
B1 SECTION
2 1'-0'
1 /4 0 STAINLESS STEEL BOLTS &
WING NUTS ® 8'O.C. (TYP)
1' WIDE x 1/e THICK NON - ASBESTOS
GASKET SUITABLE FOR 1500'F SERVICE
SAME MATERIAL AND GAUGE AS DUCT
CONCRETE PAN JOISTS
FOR 1ST FLOOR SLAB
34/10 DUCT
3' WIDE STAINLESS STEEL
ESCHUTCHEON PLATE, FORM
TO REVEAL AND CAULK
WATER - TIGHT, WELD TO DUCT.
REMOVE WINDOW, MODIFY
FRAME & GLASS TO SHORTEN
AS REQUIRED, AND REINSTALL.
CONCRETE REVEAL
ACCESS DOOR
M2.1 M2.1 SCALE: NONE
KITCHEN
EXHAUST DUCT
m q o - ovo
DRIP LEDGE
24/18 STACK
20'x20' ACCESS DOOR
24'
KITCHEN HOOD EXHAUST FAN
BACKWARD - INCUNED BELT -DRIVEN UTILTIY SET, GREENHECK /SWB -22 -30
SELECT FOR 5600 CFM AT 1 W.G. TSP (400' ELEVATION, 100'F)
1188 FRPM, 2.36 BHP, 3HP, 208V/3PH
BALANCE TO 4200 CFM ® 7 /e W.G. TSP, 899 FRPM
FURNISH W/
16 GA. SCROLL
WEATHERHOOD
BOLTED -TYPE SCROLL ACCESS DOOR
SCROLL DRAIN CONNECTION
BASE - MOUNTED NEOPRENE ISOLATORS
TWO -SPEED TWO- WINDING MOTOR (1007./50%)
ONE EXTRA SET OF DRIVES IF REQUIRED FOR BALANCING
i C 1 SECTION
M2.1 821 SCALE 1/4' = 1' -0'
ROOF MTD. EQUIP.,
ANCHOR TO SLEEPER
NEOPRENE PAD 0 EQUIP.
26 GA. GALV. MTL FLASHING,
ANCHOR TO CURB
MIN 1' DRAIN PIPE
3 GAL ALL- WELDED STAINLESS STEEL
DRAIN BOX W/ REMOVABLE UD
r 2 1 SLEEPER DETAIL
82.1162.1 SCALE: NONE
METAL CORNER
BEAD, TIP. —
1'c LARGE HEAD NAILS 0 6'O.C.
(3) 2x TREATED WD. CURB W/
i'c THRU BOLT TO MET. L
24'O.C., CSK.
CANT AND FLASHING PLIES
TREATED WD. NAILER CUT INTO
EXIST. ROOF, ANCHOR TO
EXISTING STRUCTURE
SEE ROOF PLAN FOR EXTENT
OF NEW ROOFING
EXIST. ROOF MEM:. & INSUL.
EXIST. CONC. FILL OVER MET. DECK
GALV. METAL FRAMING
TO STRUCTURE
VARIES FROM
11/ TO 61/2 '±-/
1' OVERLAP
MEANS OF ATTACHMENT
TO DUCT SHALL NOT
PROTRUDE INTO DUCT
18' MIN. ON BOTH
SIDES OF DUCT
SLAB (E) -
ONE -HOUR FIRE- RESISTIVE CONSTRUCTION (TO ALLOW 3' MIN.
CLEARANCE BETWEEN DUCT AND POTENTIAL COMBUSTIBLE CONSTRUCTION
ABOVE CEILING. CONSTRUCT WITH 1' TYPE °X' GYPSUM PANEL
2 METAL J -TRACK ALONG EACH SIDE, 21/2' METAL C -H
STUD 0 24' O.C. PERPENDICULAR TO J- TRACK, 5/B TYPE 'X'
GYPSUM BOARD, PAINT TO MATCH WALLS.
SPRINKLER PIPE
�. SEALANT (TYP)
SECTION
M2.1 22.1 SCALE: 1 -1/2' = 1' -0'
5'
(2) #4 EA SIDE/
SET IN EPDXY
ADHESIVE
36/10
NEW SLAB
IN FILL
ARMSTRONG 'CLASSIC MINABOARD-
FIRE GUARD' NON - COMBUSTIBLE
CEILING TILE (E), CUT TILES &
MODIFY GRID AS REQUIRED.
(TYP BOTH SIDES)
#4 0 12' O.C.
EA WAY BOT
1 -1/2'
3 1 INFILL SLAB DETAIL
M1.11 M2.1 SCALE: 3/4' = 1' -0'
CLOSURE PLATE, SAME
MATERIAL AS DUCT,
WELD TO DUCT, TYP.
ACCESS DOOR AT
SPRINKLER HEAD
PERMIT CENTER
SECTIONS AND DETAILS
REVISIONS
L 7/8/96 REISSUE
MEZEBELNENEEEN
wu No 2458 -02
FILE 245882 -1
DRAWN AEW
CHECKED BJH
DATE 6/7/96
M
2.■