HomeMy WebLinkAboutPermit M92-0076 - SOUTHCENTER MALL - COUNTY SEATm92-0076 county seat hvac
1062 southcenter mall
Community Development / Public Works • 6300 Southcenter Boulevard, Suite 100 • Tukwila, Washington 98188
Permit No: M92 -0076
Type: B -MECH
Category: NRES
Address: 633 SOUTHCENTER MALL
Location:
Parcel *: 262304 -9023
MECHANICAL PERMIT
TENANT COUNTY SEAT
1062 SOUTHCENTER MALL, TUKWILA, WA 98188
OWNER SOUTHCENTER JOINT VENTURE
ATTN: JAMES J GUDIN, 25425 CENTER R, CLEVELAND OH 44145
CONTACT KOZICH RICH Phone: 310 649 -1475
8936 S SEPULVEDA BLVD #103, LOS ANGELES, C 90045
CONTRACTOR PAC -AIRE, INC. Phone: 206 395 -4004
1702 PIKE STREET NW SUITE 1, AUBURN, WA 98001
********************************************* * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
Permit Description:
INTERIOR TENANT ALTERATION.
UMC Edition:: 1988
r * * * * ** * **4 * * * *, ********************, r * * *, * * * ** * * * * * * * *Ii* * ** * * * * *',s it ** * * **
" Permit Ce Authorized SSignature ;. Date
I hereby certify that I'have.read'and examined this permit and know the
same to :be true and co.rrect.. All provisions of law and ordinances '
governing ' this work will' be complied with,'whether specified. herein: or not
The granting of this permit does not presume to give authority to violate
or cancel the provisions of any other or local laws regulating
construc oar he performance of work. 'Iam authorized to sign for and
obtain thi's.'b l ', n per
Signature:
Print Name:
Valuation:
Total Permit Fee:
Date: 9 —
Title
: L lcls
Status: ISSUED
Issued: 06/01/1992
Expires: 11/28/1992
This permit shall become null and void' if ::the work is commenced within
180 days from the date : of;• ; issuance ° or; i'he work :i: or
abandoned for a
period of;�180 from thelast
PERMIT NO.
CONTACTED
DATE NOTIFIED
Ch ��� �
S - — CI
BY:
'
,�D,� D
DATE READY
PERMIT EXPIRES
2nd NOTIFICATION
BY :
(init.)
AMOUNT OWING
35 , O
3RD NOTIFICATION
BY:
(init.)
PLAN CHECK
NUMBER
mg
0011D
IS -
initial review
* !IRE
O PLANNING
O OTHER
BUILDING -
final rAviAw
PROJECT NAME
SITE ADDRESS
REVIEW COMPLETED
q_3 <
(ROUTE
C-1/ --
� 2-- INIT:
INIT:
INIT:
INIT:
MECHANICAL PERMIT
APPLICATION TRACKING
.TI
Comb fiert+
Jo LoQ Sxrt m(01
INSTRUCTIONS TO STAFF
• Contacts with applicants or requests for information should be summarized in writing by staff so that
any time the status of the project may be ascertained.
• Plan corrections shall be completed and approved prior to sending on to the next department.
• Any conditions or requirements for the permit shall be noted on the plans or summarized concisely
in the form of a formal letter or memo, which will be attached to the permit.
• Please fill out your section of the tracking chart completely. Where information requested is not
applicable, so note by using "N /A ".
DEPARTMENTAL REVIEW
"X" in box indicates which departments need to review the project.
6A c Per CT.1) 6 WA
RO
CONSULTANT:
FIRE PROTECTION:
REQ
Date Sent
SCREENING REQUIRED? fYes
REFERENCE FILE NOS.:
UMC EDITION ( ear):
it
No
SUITE NO.
C�M
Date Approved -
S•rinklers ` Detectors ( N/A
FIRE DEPT. LETTER DATED: �7. fZ INSPECTOR: �y
ZONING: BAR/LAND USE CONDITIONS?
)Yes I I No
PROPERTY OWNER
c. �c. � 'b a
�
___ e J
u PRF - c-) R l it ���, r T
• • 1—cE 4.).--1 �1ELS C6
PHONE. 5lo
PHONE
) Cei-9 2
ZIP ci
G
ADDRESS 3� PLIL` ./F1D4'
CONTRACTOR
rn LT' TO Fur-)
ADDRESS
UNIT(S) : :: FEE
ZIP
PLAN CHECK FEE :::
WA. ST. CONTRACTOR'S LICENSE #
OTHER ...
EXP. DATE
»DESCRIPTION
: AMOUNT :
RCPT #'?
: ` , :.DATE >::..
BASIC >.
;$15.00.
UNIT(S) : :: FEE
PLAN CHECK FEE :::
OTHER ...
.TOTAL
CITY OF TUKWILA
Department of Community Development - Building
6300 Southcenter Boulevard, Tukwila WA 98188
(206) 431 -3670
PLAN CHECK �
NUMBER 1 1 1 vl - 00
APPLICATION MUST BE FILLED OUT COMPLETELY
SITE ADDRESS
( 3,0 rH CEivTE2 NAC.c_
PROJECT NAME/TENANT
Cou N`f�I
TYPE OF WORK: O New /Addition f0 Modifications O Repair
BUILDING OWNER
OR
AUTHORIZED
AGENT
BUILDING USE (office, warehouse, etc.)
' 1,,a.i L M4L1.�
NATURE OF BUSINESS:
WILL THERE BE A CHANGE IN SE? No 0 Yes IF YES, EXPLAIN:
SIGNATURE co - "T`r S % EX -19
12 .
PRINT NAME SARA L. KARa1C M5
DATE APPLICATION ACCEPTED
SUITE #
D. yn
XAMIN
MECHAICAL PERMIT
APPLICATION
Mechanical Fee Worksheet must also be filled out
and attached to this application.
C) Other:
FEES (for staff use only)
VALUE OF CONSTRUCTION - $
DESCRIBE WORK TO BE DONE:
gtot2 t�a�tT hLT1= Q�TIO�
WILL THERE BE STORAGE OR USE OF FLAMMABLE, COMBUSTIBLE OR HAZARDOUS MATERIALS IN THE
BUILDING? No C) Yes IF YES, EXPLAIN:
HEREBY: C YT
RUE AND:TCOR RlC'1
DATE APPLICATION EXPIRES
DATE D v /a e'9 %- (9/2,o0
PHONE(310) cf4 1fn
ADDRESS SEPt .11 yam[ 103 CITY /ZIP ,6,L
CONTACT PERSON,IG4_1 kOZlCt -1 PHON �\ ?F500
APPLICATION SUBMITTAL In order to ensure that your application is accepted for plan review, please make sure to fill
out the application completely and follow the plan submittal checklist on the reverse side of this form. A completed
'Mechanical Permit Fee Worksheet" must accompany this permit application. Handouts are available at the Building
counter which provide more detailed information on application and plan submittal requirements. Application and
plans must be complete in order to be accepted for Dian review.
BUILDING OWNER / AUTHORIZED AGENT If the applicant is other than the owner, registered architect/engineer, or
contractor licensed by the State of Washington, a notarized letter from the property owner authorizing the agent
to submit this permit application and obtain the permit will be required as part of this submittal.
VALUATION OF CONSTRUCTION The valuation is for the work covered by this permit and must be filled in by the
applicant. This figure is used for budget reporting purposes only and not to calculate your fees.
EXPIRATION OF PLAN REVIEW Applications for which no permit is issued within 180 days following the date of
application shall expire by limitation. The Building Official may extend the time for action by the applicant for a
period not exceeding 180 days upon written request by the applicant as defined in Section 304(d) of the Uniform
Mechanical Code (current edition). No application shall be extended more than once.
If you have any questions about our process or plan submittal requirements,
please contact the Department of Community Development at 431 -3670.
IC)` - _
0 6/18/90
DESCRIPTION
UNIT COST
U No. OF
NITS
X
T OST
BASIC FEE
$15.00
$4.50
SUPPLEMENT PERMIT FEE
1
Installation or relocation of each forced -air gravity -type furnace or
burner, including ducts and vents attached to such appliance, up to and
including 100,000 Btu /h.
$9,00
X
2
Installation or relocation of each forced -air or gravity -type furnace or
burner, including ducts and vents attached to such appliance over
100,000 Btu /h.
$11.00
X
3
Installation or relocation of each floor furnace, including vent.
$9.00
X
4
Installation or relocation of each suspended heater, recessed wall heater
or floor - mounted unit heater.
$9.00
X
5
Installation, relocation or replacement of each appliance vent installed and
not included in an appliance permit.
$4.50
x
6
Repair of, alteration of, or addition to each heating appliance,
refrigeration unit, cooling unit, absorption unit, or each heating, cooling,
absorption, or evaporative cooling system, including installation of
controls regulated by this code.
$9.00
X
7
Installation or relocation of each boiler or compressor to and including
three horsepower, or each absorption system to and including 100,000
Btu /h.
$
X
8
Installation or relocation of each boiler or compressor over three
horsepower to and including 15 horsepower, or each absorption system
over 100,000 Btu /h and including 500,000 Btu /h.
$16.50
X
9
Installation or relocation of each boiler or compressor over 15
horsepower to and including 30 horsepower, or each absorption system
over 500,000 Btu /h to and including 1,750,000 Btu /h.
$22.50
X
10
Installation or relocation of each boiler or compressor over 30
horsepower to and including 50 horsepower, or for each absorption
system over 1,000,000 Btu /h to and including 1,750,000 Btu /h.
$33.50
x
11
Installation or relocation of each boiler or refrigeration compressor over
50 horsepower, or each absorption system over 1,750,000 Btu /h.
$56.00
X
12
Each air - handling unit to and including 10,000 cubic feet per minute,
including ducts attached thereto. (NOTE: This fee shall not apply to an
air - handling unit which is a portion of a factory- assembled appliance,
cooling unit, evaporative cooler or absorption unit for which a permit is
required elsewhere in this code.)
$6.50
X
13
Each air - handling unit over 10,000 cfm.
$11.00
X
14
Each evaporative cooler other than a portable type.
$6.50
X
15
Each ventilation fan connected to a single duct.
$4.50
X
16
Each ventilation system which is not a portion of any heating or
air - conditioning system authorized by a permit.
$6.50
X
17
Installation of each hood which Is served by mechanical exhaust, including
the ducts for such hood.
$6.50
X
18
Installation or relocation of each commercial or industrial -type incinerator.
$11.00
X
19
Installation or relocation of each commercial or industrial -type incinerator.
$45.00
x
20
Each appliance or piece of equipment regulated by the code but not
classed in other appliance categories, or for which no other fee Is listed in
this code.
$6.50
X
SUBTOTAL
PLAN CHECK FEE (% of
subtotal)
GRAND TOTAL
$
CITY OF TUKWILA
Department of Community Development - Building Division
6300 Southcenter Boulevard, Tukwila WA 98188
(206) 431 -3670
THIS WORKSHEET MUST ACCOMPANY
YOUR MECHANICAL PERMIT APPLICATION.
MECHANh;AL PERMIT
FEE WORKSHEET
INSTRUCTIONS - .Co mplete the : worksheet,
indicating number of units being
in stalled in each catego A time of
i bmittal,. s taff will calculate the fees.
Fire Department Review
Control #M92 -0076
(513)
Re: County Seat - 1062 Southcenter Mall
Dear Sir:
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188 -7661
(206) 575 -4404
May 11, 1992
John W. Rants, Mayor
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. Sprinkler protection shall be extended to all areas
where required, including all enclosed areas, below
obstructions and under overhangs greater than four feet
wide. (NFPA 13- 4 -1.1, 4- 4.1.7.1.1, 4- 4.1.7.5, 4- 4.1.7.6.1)
Ignition sources (such as roll -up door motors) and
combustible material located above the ceiling must be
provided with sprinkler protection. (UFC
10.501(a)(b))
All new sprinkler systems and all modifications to
existing sprinkler systems shall have fire department
review and approval of drawings prior to installation
or modification. New sprinkler systems and all
modifications to sprinkler systems involving more than
25 heads shall have the written approval of the
W.S.R.B., Factory Mutual, Industrial Risk Insurers,
Kemper or any other representative designated and /or
recognized by The City of Tukwila, prior to submittal
to the Tukwila Fire Prevention Bureau. No sprinkler
work shall commence without approved drawings. (City
Ordinance #1528)
All sprinkler system plans, calculations and the
contractors Materials and Test Certificates submitted
to The Tukwila Fire Prevention Bureau must be stamped
with the appropriate level of competency seal. (WAC
212 -80)
Page number 2
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188 -7661
(206) 575 -4404
John W. Rants, Mayor
2. H.V.A.C. units rated at 2,000 cfm require
auto- shutdown devices. These devices shall be separately
zoned in the alarm panel and local U.L. central station
supervision is required. (City Ordinance #1528)
3. Required fire resistive construction, including
occupancy separations, area separation walls, exterior
walls due to location on property, fire resistive
requirements based on type of construction, draft stop
partitions and roof coverings shall be maintained as
specified in the Building Code and Fire Code and shall be
properly repaired, restored or replaced when damaged,
altered, breached, penetrated, removed or improperly
installed. (UFC 10.601)
Yours truly,
trzA
The Tukwila Fire Prevention
cc: •T.F.D..file
ncd
* k****** k*** k***** k******** k**** k kk k* ** ******
CITY OF TUKWILA, WA TRANSMIT
k*** k*************kkkk*******kk kk *** * * ** * **** * * *kkkkkkk **** k***
TRANSMIT Number: 92000498 Amount: 35.63 06/01/82'10; 41
Permit No M92-0076 Type. 13 -MCCH MECHANICAL , PERMIT
Parcel; No 26230.4. 9.023
S i t e Address: G13 SOUTHCENTER MALI
Payment Method: .;.CHECK 'Notation: PAC- AIRE. INC.
********* k** k**•*** * * * * *kkk ** * ** * * * * **k *k *�k:k 4*
GENERA
GENERA •
GENERA
GENERA
TOTAL,
CHECK,
7.13
2
8.25
33.00
76.88
76.80
CHANGE 0.00
0307A000 09 :39
Account' Cade Descry i pti an Paid'.
' 000/345.133 PLAN CHECK NONRCS. 7.13 .',
00.0/ MECHANICAL .= NONRES. 2850'
Total (This Payment)t 35.63'
Address:
Tenant:
Type:
Parcel #:
Wash
CITY OF TUKWILA
633 SOUTHCENTER MALL
COUNTY SEAT
8 -MECH
262304 -9023
* k** *•k * *•k* k***** * * * * * * * *•k * * *** * * ** Mfr************ ** *** *** * * * *** * *• * * *•k * * ****
Permit Conditions:
1. No changes will be made to the plans unless approved by the
Architect and the Tukwila Building Division,
2. Electrical permit shall be ; d the Washington
State Division of Labor,; l In us;�tr ,ies�..antl a.11 electrical
work will be insp cte`d by that agency (`277;
3. All permits, ins e:ri:�on r�eco ds, arch, approve 4411ans shall be
maintained .ava11 b °Te e Jobsi prior to thr st of
any con str ucrt �i . , N ese, co'bu,men ahe to 'bre" r a i nta
available u°,:�r1 flin`al i rspectio�n, approval �is rgran
� Y ` . , .� 4 b! i t , a r1, ted'
4. Any expos ns+s� la to ons back i , mater'i ail �;; sha l' ` °hava F�i,
Spread 4,t�,ingl'of �2 �) or +.less, apc ,,material "shall 1;b,ea�r.,ide:h
ficatio dd
5. All co
plan s1
Permit No: M92 -0076
Status: ISSUED
Applied: 04/30/1992
Issued: 06/01/1992
shorfii' tg theE,rf ire er 'r,r rating ` thereof . „. �' �
r tr ' ct1Orf to don ,,ln con wit �a ,
a 4 d d ote , quIre,p'ents = 0fig . t� 'hie Uniform • Building Code (1,9 i`at,
• Edit n);'U,niform Mechanical { o.d.,e .'`•(1988 Edition), anii' th'e `r��
i'''.i '7 Energy Code ( 99i - Edition)
Val ty of'P.e mit. Th'e' issuance of ='a permit or app:rov,a` o o
p1 S 1 spec f 11catio x41.14, co •'S'ha.l not be `cony' G.
str ` e1d to be a• per =lir..it fo.r, t o a !approval.. :of , any vi61a
of i' of the, pr�`o•v.i.sions o i hil , ,,,, ciode1 or' of ;any other . fir,;
ordt1f anrc`e=xof the 3urri s 1 ct. o . Ng p'ermi•t ":presuming . t y o give;
authorit!:fior Violate ,._or•- canc,,e1\the prov�lsiorrs of th1so coder 4.3
a r ey,V.400 '
s Ii " ' 1 ' b'eu:,; 1 i d f ,� ; , , ''
roect
'&11 ���
—
--t/k
w
ypeo nspe� �.•.
� ddre ;r) 1 V t
1 Tom-- o A e d
Date Called —7—)---7— Q r
I
a� r
Date Wanted: .
Requester: o
Phone No.: -361 S `i oo Li!
w.-
INSPECTION RECORD (
Retain a copy with permit
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
M61 -o0/
PERMIT NO.
(206) 431 -3 0
COMMENTS:
Approved per app Jlcable codes: --- - - -0 —Corr- ions required prior to approval.
d $30.1 ' REINSPECTION FEE REQUIRED. Prior to reinspection, fee must be paid at
6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Recept No.:
Date:
Project:
CO U I''1 5e l}.'-k-
Type of Inspection:
5m o c,e
-rQ. -
Address
r 53umhc_n�
Date Called:
_
.
Special Instructions: mail
3: OO ` * .e%.e. k O hker:
U.) \k1 \a-e -� h.er Q. .
Date Wanted:
_
��as
_
a
- /a am. C
Requester:
r) n b
Phone No.:
3 q s - 4001 -i
❑ Approved per applicable codes.
INSPECTION RECORD --
Retain a copy with permit
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188'
' n -or
PERMIT
(206) 431 -3670
❑ Corrections required prior to approval.
COMMENTS:
A-9 P #-o "o .
t , ,.\ rte-, I 1J & P *zT t,z, r,1 A P pR-a V✓K_.
RI it f-1.
nspector:
Date: 7— 2'2 - 7 Z
❑ $30.00 REINSPECTION FEE REQUIRED. Prior to reinspection, fee must be paid at
6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
Post-It" brand fax transmittal memo 7671
of of paves e
From b
es. al
• ,a
a1
*elt * * ** ** *** **
* QUOTATZON
01* * * * * *0 * ** **
DATE t June 4, 1992
NAM: A966
NATt 0CCY1 COUNTY SPY
JOes County Moat Store 0672
South Cer►tse Mall
Seattle, WA
A960.926i00 - 024
MARK QUANTITY DESCRIPTION
AcCV - 1 1 H$17 - 1033V 2 - Spd, 1ST CV, 2011/250 - 3
1 LI- 1070N1A, Timed Oft Ctl tZ1132F21)
1 LO DSanctMtoltt /133/163/275
AHU -1 i COHl7 -185V Nz Slower Coil w/o Drive
1 DA017- 145/27$ °$ -L4. 200/230/460'3
1 EN17- 108 /275- 15,200 /230v -Sph Neater
nt a Oy •
Am$1Ol - 4 Light Sons T'Stat w/
DR - 10 Zone Damper (LO" Dia)
FREIGHT - FFA First Destination •
NIT TOTAL. PANE
pan Otetott (2/4) 447 -3090
1- 000 - 625 -*269
1r. Matiomel Amounts Lwsoutiv.
RATA. #
10263
40020
230,9
14263
2641•
26297
r
Sense 1IH26
17P01
-
if
Delidiryt ASAP
CITY OF TUKWILA Id: ROUT130 Keyword: UACT
Activity document routing maintenance.
Permit No: M92 -0076
F1 =Help, ESC =Exit current screen.
User: 1677
05/08/92
MECHANICAL PERMIT
Route: 1 Current Route Line: 2 of 3
Packet Units Description Station Status Received Assigned Complete
Packet Units Action Station Initials Status Received Assigned Completed
MECH 01 01 C FNLREV `; Ap Cont. 04/30/92 05/08/92 05/08/92
Priority (0 /low..9 /high): 0
Regular hours (HH.MM): .00 Overtime Hours(HH.MM):
Comments ;;1[SMOKE "DETECTOR REQUIRED`
2[
3?[FfiRE' t = ;PLEASE ; , REVIEW AND COMMENT :' 1
5[
6[
7[
8[
9[
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
,I'. TUANT'S PLUMBING SHALL NOT SE CHASED OR CUT INTO OR THROUGH THE
''..DEMISING WALLS (SEPARATING TENANT'S LEASE SPACE FROM ADJOINING
• 'TENANT SPACES, ETC.) OR EXTERIOR WALLS.
2. VENTS SHALL NOT BE LOCATED WITHIN 25'0" OF AN EXTERIOR WALL.
ROOF FLASHING SLEEVES MUST tsE INSTALLED AS PER LANDLORD
REQUIREMENTS.
3. LANDLORD FURNISHED SANITARY OUTLET BELOW SLAB: LOCATION
SHOWN ON PLUMBING SHEETS.
. LANDLORD INSTALLED COLD WATER LINE: LOCATION SHOWN ON
PLUMBING SHEETS.
. PLUMBING CONTRACTOR IS RESPONSIBLE TO VERIFY ALL EXISTING
CONDITIONS IN THE FIELD AND REPORT ALL DISCREPANCIES TO THE
TENANT'S REPRESENTATIVE.
6. ALL TOILET AREAS ARE TO HAVE 1 EACH 6 GALLON ELECTRIC WATER
HEATER (110 DECREES F.) PROVIDED BY THE CONTRACTOR.
7. HOT /COLD WATER PIPING AND WASTE LINE BELOW LAVATORY SHALL
BE INSULATED AS REQUIRED BY LOCAL CODE.
'8. ALL PIPE INSULATION SHALL BE NONCOMBUSTIBLE MATERIALS AS
REQUIRED BY LOCAL CODE.
9. WATER METER IF REQUIRED SHALL HAVE SHUT -OFF VALVES ON BOTH
SIDES OF METER.
10. GAS LINES AND REFRIGERATION LINES ON ROOF SHALL BE SUPPORTED BY
TREATED WOOD BLOCKS ON ROOF PADS BY LANDLORD. ROUTING OF LINES
SHALL BE COORDINATED WITH LANDLORD'S PROJECT MANAGER.
1A. FOR ADDITIONAL PLUMBING INFORMATION, REFER TO SPECIFICATIONS
AND DETAILS ON PLUMBING DRAWINGS.
1Z. FIXTURES
A. WATER CLOSET - CRANE /GALAXY 3 -190 REGULAR RIM WITH 3 -222
TANK OR APPROVED EQUAL. SEAT AND COVER BY CHURCH OR EQUAL.
CLOSET SHALL BE SIPHON JET DESIGN, INCLUDE ALL FITTINGS,
VALVES AND SUPPLIES AS REQUIRED.
B. WATER CLOSET - HANDICAPPED: CRANE. (OR EQUAL) GALAXY 3 -190
WITH 18" HIGH BOWL (SPECIALLY MANUFACTURED FOR BARRIER
FREE APPLICATIONS) WITH 3 -222 TANK AND CHURCH SEAT /COVER.
INCLUDE ALL FITTINGS, VALVES AND SUPPLIES AS REQUIRED.
C. LAVATORY; CRANE (OR EQUAL) NORWICH 1H -195 WALL HUNG FIXTURE
MADE OF VITREOUS CHINA WITH INTEGRAL BACK. UNIT SHALL HAVE
AN OVERALL DIMENSION OF 18 "X15 ". INSTALL A CRANE CH -8027
DIAL -ESE SUPPLY FITTING WITH AERATOR FAUCET WITH POP -UP
DRAIN (CHROME). INCLUDE ADJUSTABLE "P" TRAP.
D. LAVATORY- HANDICAPPED: CRANE (OR EQUAL) 1H -360 WITH CH -8058
TRIM OR EQUAL.. UNIT IS WALL HUNG FIXTURE MADE OF VITREOUS
r'uTUA WYTW TUTRr:?AT RA('R . !NTT SIZE SHAL.i. HAVE AN OVERALL
DIMENSION OF 20 "X27" PROVIDE LOOSE NECK FAUCET WITH LEVER
HANDLES. ALL OTHER FITTINGS SIMILAR TO "C" ABOVE.
E. FLOOR DRAIN: TYLER OR MILWAUKEE CAST IRON DRAIN WITH
NICKEL - BRONZE ADJUSTABLE STRAINER, INSIDE CAULK, OUTLET,
CLAMPING DEVICE, AND CONCEALED CLEANOUT.
F. HOT WATER HEATER - DAYTON (OR EQUAL) 1.5KW, 120 VOLT , 1
PHASE, 6 GALLON.
13.MATERIALS
A. SANITARY SEWER - CAST IRON OR COPPER PIPING MAY BE USED
EXCEPT THAT ALL PIPING BELOW GRADE SHALL BE CAST IRON. VENTS
TWO (2 ") INCHES IN SIZE AND SMALLER MAY BE EITHER SCHEDULE
40 GALVANIZED STEEL OR COPPER PIPING.
B. DOMESTIC WATER AND HOT WATER PIPING SHALL BE COPPER TYPE "L"
WITH WROUGHT COPPER FITTINGS. ALL HOT WATER PIPING SHALL BE
INSULATED WITH ARMAFLEX OR EQUIVALENT INSULATING TO A
THICKNESS OF 1 ".
C. GAS PIPING SHALL BE BLACK STEEL SCHEDULE 40 WITH SCREWED
FITTINGS.
D. CHILLED WATER SUPPLY AND RETURN PIPING SHALL BE GALVANIZED
STEEL PIPE (STANDARD WALL) OR TYPE "M" HARD COPPER TUBING.
ALL PIPING SHALL BE INSULATED WITH 1" THICK OWENS CORNING
FIBERGLASS 25 ASJ /SSL OR EQUAL.
so
'.14T : MAKING UP PIPE
. A. SCREWED PIPE SHALL BE MADE WITH PIPE COMPOUND APPLIED TO THE
MALE THREAD WITH NOT MORE THAN TWO THREADS LEFT EXPOSED.
PIPE SHALL BE kEAMED AFTER THREADING.
B . BELOW GRADE SANITARY PIPING SHALL BE CAST IRON PIPE AND SHALL
BE MADE UP WITH ONE.THIRD OF THE HUB CAULKED WITH FIRST
QUALITY OAKUM, AND THE REMAINDER FILLED WITH FIRST QUALITY
CAULKING AT ONE POURING AND CAULKED TIGHT.
C. COPPER JOINTS SHALL BE MADE UP WITH 95 -5 SOLDER.
15. HANGERS AND SUPPORTS
HORIZONTAL PIPING SHALL BE SUPPORTED AT INTERVALS NOT TO EXCEED
10'0" WITH SWIVEL SPLIT PIPE HANGERS EQUAL TO CRANE NO. 199F OR
GRINNELL NO. 104. VERTICAL PIPING SHALL BE SUPPORTED BY MEANS OF
WROUGHT IRON CLAMPS SUSPENDED FROM THE UNDERSIDE OF STRUCTURE
WITH HANGER RODS.
16. CLEANOUTS
CLEANOUTS SHALL BE A MANUFACTURED BY TYLER, MILWAUKEE, OR EQUAL
AND SHALL BE INSTALLED AT ALL BENDS, ANGLES, AND ENDS OF ALL
WASTE AND SEWER EINES A3 CALLED FOR ON THE DRAWINGS AND AS
REQUIRED BY LOCAL CODES. ALL CLEANOUTS SHALL BE BROUGHT TO
GRADE, AND IN ALL CASES, SHALL BE PROVIDED WITH SUFFICIENT SPACE
FOR RObDING.
HEATING, VENTILATING AND AIR CONDITIONING
ALL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS MUST BE
DESIGNED AND INSTALLED IN CONFORMANCE WITH THE STATE AND LOCAL
BUILDING CODES, LOCAL FIRE DEPARTMENT REGULATIONS, AND THE
LATEST EDITION OF SMACNA AND ASHRAE STANDARDS.
2. DUCTWORK AND ALL OTHER HVAC CONSTRUCTION MUST BE DESIGNED TO
CLEAR ANY INTERIOR ROOF LEADERS, DOWNSPOUTS, GAS LINES, OR
OTHER EXISTING CONSTRUCTION THAT OCCURS IN TENANT'S LEASED
SPACE.
. EXHAUST DUCT, PLUMBING VENTS AND FLUES SHALL NOT BE LOCATED
WITHIN 10' -O" OF ANY EXTERIOR WALL. WHEREVER POSSIBLE,
EXHAUSTS SHALL BE A MINIMUM OF 20'- 0" FROM ANY FRESH AIR
INTAKES FOR HVAC EQUIPMENT; NOTE THAT THIS LIMIT ALSO APPLIES
TO DISTANCE BETWEEN ADJOINING TENANT'S ROOF WORK, THAT SUCH
COORDINATION MUST BE DONE THROUGH THE LANDLORDS
REPRESENTATIVE.
. ALL ROOF WORK SHALL BE COORDINATED WITH.THE
LANDLORD'S FIELD REPRESENTATIVE. THE HVAC CONTRACTOR IS
REQUIRED TO USE LANDLORD'S ROOFING CONTRACTOR FOR ALL ROOF
WORK. THE HVAC CONTRACTOR SHALL INCLUDE THE COST OF SAME
"- IN HIS BID.
. HVAC CONTRACTOR WILL PROVIDE PERMANENT IDENTIFICATION OF THE
STORE NAME ON ROOF TOP EQUIPMENT FOR THE CONVENIENCE OF
MAINTENANCE AND REPAIR WORK. ALL NEW ROOFTOP EQUIPMENT SHALL
BE PAINTED AS PER LANDLORD REQUIREMENTS.
. HVAC CONTRACTOR SHALL PAY ALL FEES, OBTAIN ALL PERMITS AND
INSPECTIONS AS REQUIRED FOR THIS PORTION OF THE WORK.
. HVAC CONTRACTOR SHALL VISIT THE SITE TO DETERMINE THE FULL
EXTENT OF HIS WORK. ANY DISCREPANCIES WITH PLANS TO BE
REPORTED TO TENANT'S REPRESENTATIVE PRIOR TO THE SUBMISSION
OF A BID.
ALL.NEW MATERIALS, EQUIPMENT AND WORK SHALL BE GUARANTEED FOR
A PERIOD OF ONE YEAR FOLLOWING DATE OP ACCEPTANCE BY
TENANT, EXCEPT WHERE A LONGER WARRANTY PERIOD IS PROVIDED BY
THE MANUFACTURERS OF EQUIPMENT OR COMPONENTS.
PRIOR TO THE START UP OF RVAC SYSTEM, THE HVAC
CONTRACTOR SHALL CLEAN ALL DUCTWORK AND EQUIPMENT TO REMOVE
ANY DIRT, RUBBISH OR DEBRIS.
10. IRE COMPLETE HVAC SYSTEM SHALL BE TESTED AND BALANCED BY THE
HVAC CONTRACTOR TO INSURE PROPER AIR FLOW TO ALL AREAS. THE
GENERAL CONTRACTOR SHALL CONTRACT WITH AN INDEPENDENT TESTING
ASSOCIATION TO VERIFY ALL AIR FLOW. A COPY SHALL BF FURNISHED
TO THE TENANT.
11. ALL ROOF TOP EQUIPMENT SHALL BE CONVEYED VIA A RUNWAY OF 3/4"
PLYWOOD SHEETS 2" X 10" RUNNERS AND A RUBBER TIRED
CONVEYANCE VEHICLE OR /AND AS APPROVED BY LANDLORD THE HVAC
CONTRACTOR IS RESPONSIBLE TO VERIFY APPROVED METHOD AND INCLUDE
THIS IN HIS BID.
12. SPLASH PANS OR BLOCKS ARE REQUIRED ON THE ROOF AT ALL ROOF
TOP UNIT CONDENSATES, OR AS DIRECTED BY LANDLORD.
13. FOR ADDITIONAL HVAC INFORMATION REFER TO MECHANICAL DETAILS AND
DRAWINGS .
14. ALL DUCT WORK SHALL BE METAL. FIBERGLASS SHALL NOT BE USED IN
ANY SITUATION REFER TO NOTE 18.
15. HANGERS AND SUPPORTS
A. ALL HORIZONTAL DUCTS HAVING A DIMENSION OF 40 INCHES AND
LESS SHALL BE SUPPORTED BY MEANS OF BAND IRON HANGERS CF
NO. 18 U.S. GAUGE ATTACHED TO THE DUCT BY MEANS OF
RIVETS, SCREWS, OR CLAMPS, AND FASTENED TO STRUCTURE
ABOVE BY TOGGLE BOLTS OR OTHER MEANS. EACH SECTION OF
DUCTWORK SHALL HAVE AT LEAST ONE PAIR OF SUPPORTS.
VERTICAL DUCTS SHALL BE SUPPORTED WITH 1 -1/4" X 1 -1/4" X
1/4" ANGLES WHERE THEY PASS THROUGH THE FLOOR LINES.
B. ALL HORIZONTAL DUCTS HAVING A DIMENSION OF 40 INCHES AND
MORE SHALL BE SUPPORTED BY MEANS OF ANGLE IRON TRAPEZE
HANGERS. EACH SECTION OF DUCTWORK SHALL HAVE AT LEAST
ONE PAIR OF SUPPORTS.
16. FLASHING
A. CONTRACTOR WILL PROVIDE WATER TIGHT 24 GAUGE SHEET
METAL FLASHING AT ALL EXTERIOR WALLS AND ROOF
PENETRATIONS.
B. ALL CUTTING OF ROOF OPENINGS, SUPPORTS FOR THE ROOF
OPENINGS, PITCH PANS, ROOF CURBS, FLASHINGS, COUNTER
FLASHINGS, REPAIR TO ROOF, ETC., ASSOCIATED WITH HVAC
SUBCONTRACTOR SHALL BE THE RESPONSIBILITY OF HVAC
CONTRACTOR. HE SHALL EMPLOY LANDLORD'S ROOFERS FOR THIS
WORK SO AS TO MAINTAIN LANDLORD'S ROOF BOND.
17. TOILET EXHAUST SHALL BE LOREN COOK iGEN -1 65 CFM WITH
INTEGRAL BACK DRAFT DAMPER (OR APPROVED EQUAL).
18. DUCTWORK
A. SQUARE AND RECTANGULAR DUCTWORK SHALL BE CONSTRUCTED OF
NEW GALVANIZED PRIME SHEET STEEL OF THE FOLLOWING
GAUGES:
DUCT SIZE
12" AND LESS
13" TO 30"
31" TO 54"
55" TO 84"
85" AND OVER
B. SQUARE AND RECTANGULAR
FOLLOWS:
DUCT SIZE
17" AND LESS
18" TO 30"
31" TO 54"
GAGE
NO. 26 U.S.
NO. 24 U.S.
NO. 22 U.S.
NO. 20 U.S.
NO. 18 U.S.
DUCTWORK SHALL BE CONSTRUCTED AS
METHOD
S" AND DRIVE CLEATS
1" STANDING SEAMS ON
3'0" CENTERS
1 -1/4" STANDING SEAMS
ON 3'0" CENTERS
ROUND DUCTWORK SHALL BE CONSTRUCTED OF NEW GALVANIZED
PRIME GRADE SHEET STEEL OF THE FOLLOWING GAUGES:
DUCT SIZE (DIAMETER) DUCTS FITTING
8" AND LESS 24 22
9" TO 18" 22 20
19" TO 30" 20 18
ALL 90 ELBOWS FOR ROUND DUCTWORK SHALL BE FIVE (5)
PIECE. ALL LONGITUDINAL SEAMS SHALL BE FORMED BY
PITTSBURGH LOCKS. JOINTS SHALL BE SWAGGED WITH ONE -
HALF INCH (1/2 ") OVERLAP.
C. ALL DUCTWORK SHALL BE MADE AIR TIGHT WITH MASTIC AND
PRESSURE SENSITIVE TAPE.
D. ALL SUPPLY, RETURN AND OUTSIDE AIR DUCTWORK LOCATED
WITHIN THE BUILDING SHALL BE INSULATED WITH ONE AND
ONE -HALF (1 -1/2 ") THICK FOIL -FACED FIBERGLASS
INSULATION.
E. ALSO SUPPLY AND RETURN, AIR DUCTS LOCATED OUTSIDE OF
BUILDING OR EXPOSED TO WEATHER SHALL HAVE ONE AND
ONE -HALF INCH (1 - 1/2 ") RIGID INSULATION ON INTERIOR
OF DUCT.
F. CONTRACTOR WILL INSTALL INSECT SCREENS ON ALL DUCT
OPENINGS WHICH LEAD TO OR ARE OUTDOORS. INSECT SCREENS
SHALL HAVE REMOVABLE REMOVABLE GALVANIZED STEEL FRAMES.
19. DAMPERS
A. SPLITTER DAMPERS SHALL BE FABRICATED OF SHEET STEEL NOT
LESS THAN NO. 16 U.S. GAUGE WITH THE LEADING EDGE
HEMMED. EACH DAMPER SHALL BE LARGE ENOUGH TO COVER THE
SMALLER OF THE TWO OPENINGS IT CONTROLS. DAMPERS SHALL
BE CONTROLLED AS FOLLOWS:
EXPOSED OR ACCESSIBLE DUCTWORK - LOCKING QUADRANTS EQUAL
TO YOUNG REGULATOR NO. 1 WITH DAMPER ROD END BEARINGS ON
OPPOSITE END.
CONCEALED OR INACCESSIBLE DUCTWORK - LOCKING QUADRANT EQUAL
TO YOUNG REGULATOR NO.315 (CHROMIUM PLATED WITH DAMPER ROD
END BEARINGS ON BOTH ENDS).
B. VOLUME DAMPERS SHALL BE OF THE OPPOSED INTERLOCKING
TYPE AS MANUFACTURED BY AMERICAN FOUNDRY AND FURNACES
CO. (AFFCO) OR EQUAL. BLADES SHALL BE OF NO.16 GAUGE
. SHEET METAL AND SHALL NOT EXCEED 48" IN LENGTH OR 12"
IN WIDTH. BLADES SHALL BE ON ONE - HALF INCH (1/2 ")
DIAMETER RUSTPROOF AXLE. BEARINGS. SHALL BE OF THE SELF -
LUBRICATING FERRULE TYPE.
C. DOUBLE THICKNESS TURNING VANES SHALL BE IN SQUARE ELBOWS.
PROVIDE AND INSTALL BARBER - COLMAN AIRTURNS OR EQUAL.
TURNING VANES SHALL BE OF THE SAME GAUGE METAL AS THE
DUCT IN WHICH THEY ARE INSTALLED. RADIUS ELBOWS SHALL
HAVE A CENTERLINE RADIUS OF ONE AND ONE -HALF (1 -1/2 ")
TIMES THE DUCT WIDTH.
20. DUCTWORK - EXCEPTIONS
DUCTWORK FOR EXHAUSTING AIR OR OUTSIDE SUPPLY AIR SHALL BE
ALL METAL AND CONSTRUCTION ACCORDING TO RECOMMEND PRACTICES
AS FOUND IN THE LATEST ISSUE OF ASHRAE.
21. SUPPORT OF DIICT SYSTEM
DUCTWORK SHALL BE SUPPORTED AT ALL TURNS AND TRANSITIONS PLUS
NOT MORE THAN 8' -0" O.C. FOR STRAIGHT DUCTS UP TO 35" TO 59"
MAXIMUM DIMENSIONS, 6' O.C. AND DUCTS OVER 60" MAXIMUM
DIMENSION, 4' O.C.
RANGE DESIGN SHALL BE AS DESCRIBED IN THE LATEST EDITION OF
THE " SMACNA" MANUAL. REINFORCEMENT MEMBERS MAY BE USED TO
SUPPORT THE DUCT SYSTEM PROVIDED DETAILS OUTLINED IN THE
AFOREMENTIONED DOCUMENTS ARE ADHERED TO.
22. REINFORCEMENT
ALL DUCTS REQUIRING REINFORCEMENT SHALL BE REINFORCED
ACCORDING TO THE LATEST EDITION OF " SMACNA" MANUAL AS
OUTLINED ON PAGES 8 AND 9 OF THE MANUAL.
MATERIALS FOR REINFORCEMENT MEMBERS SHALL BE GALVANIZED
STEEL. ALL SCREWS AND WASHERS SHALL BE PLATED OR
GALVANIZED.
23. ACCESSORY ITEMS
ALL MANUAL DAMPERS, 'SIRE DAMPERS, TURNING VANES, REGISTER
CONNECTIONS, ACCESS DOORS OR OTHER ASSOCIATED ACCESSORIES
SHALL BE INSTALLED ACCORDING TO THE LATEST PUBLICATION
OF "SMACNA" MANUAL.
24. PIPING
A. PIPING AND FITTINGS SHALL BE OF THE WEIGHTS AND TYPES
SHOWN ON THE DRAWINGS. SIZES SHOWN ON THE DRAWINGS
ARE NOMINAL PIPE SIZES.
B. ALL PIPES SHALL BE INSTALLLED PARALLEL TO, OR AT RIGHT
ANGLES WITH THE BUILDING WALLS AND PARTITIONS AND
SHALL F.. INSTALLED WITH THE PROPER PITCH.
C. ALL PIPING SHALL BE UPENDED AND POUNDED TO REMOVE
ANY FOREIGN MATTER PRESENT AND SHALL BE SWABBED IF
NECESSARY.
D. REFRIGERANT PIPING SHALL BE COPPER TYPE "L" WITH
WROUGHT COPPER FITTINGS. JOINTS SHALL BE MADE
USING SILFOS OR 95 -5 SOLDER.
E. REFRIGERANT SUCTION LINES SHALL BE INSULATED WITH
ONE INCH (1 ") THICK INSULATION. PROVIDE A
CONTINUOUS VAPOR SEAL.
25. ALL DUCT WORK SHALL BE PULLED AS TIGHT AS POSSIBLE AGAINST MALL
JOIST.
1. FOk ADDITIONAL ELECTRIC INFORMATION SEE ELECTRICAL DRAWINGS
AND SPECIFICATIONS.
2. ELECTRICAL CONTRACTOR TO PROVIDE ALL BREAKERS TO BE BOLT DOWN
TYPE.
3. ELECTRICAL CONTRACTOR SHALL PROVIDE PULL WIRE IN AN EMPTY CONDUIT
FOR TELEPHONE OR AS REQUIRED BY LOCAL PHONE COMPANY.
4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE WIRING OF THE
INTERLOCK SWITCH AND ALL CONTROLS FOR MOTORIZED OVERHEAD
GRILLE.
5. THE ELECTRICAL CONTRACTOR SHALL THOROUGHLY FAMILIARIZE HIMSELF
WITH THE PLANS (ARCHITECTURAL, MPE, LANDLORD DRAWINGS AND
DETAILS, ETC) AND SHALL VERIFY EXISTING CONDITIONS AT THE JOB
SITE.
6. ENTIRE INSTALLATION SHALL BE PREPARED IN A FIRST -CLASS
WORKMANLIKE MANNER. THE COMPLETED SYSTEMS SHALL BE FULLY
OPERATIONAL. ACCEPTANCE BY OWNER SHALL BE A CONDITION OF THE
CONTRACT. ALL WORK SHALL BE COORDINATED WI"H OTHER TRADES IN
ORDER TO AVOID INTERFERENCES OR DISPUTES AMONG RESPECTIVE TRADES.
7. ALL NEW MATERIALS, WORKMANSHIP, AND EQUIPMENT SHALL BE
GUARANTEED FOR ONE YEAR AFTER SYSTEM ACCEPTANCE.
8. ALL WIRING SHALL BE IN CONDUIT AS REQUIRED BY LOCAL CODE AND
SHALL BE CONCEALED WHERE POSSIBLE. WHERE EXPOSED; RUN IN STRAIGHT
LINES PARALLEL AND /OR PERPENDICULAR TO BUILDING LINES.
9. ELECTRICAL CONTRACTOR SHALL INCLUDE ALL MISCELLANEOUS ITEMS
REQUIRED TO COMPLETE THE WORK.
10. ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS FOR DIMENSIONS
BUT SHALL CONTACT THE OWNERS REPRESENTATIVE REGARDING ANY
DIMENSIONAL DATA REQUIRED AND SHALL VERIFY EXACT LOCATION
AND.MOUNTING HEIGHTS OF ALL FIXTURES, NOT SPECIFIED ON DRAWINGS
OR DETAILS WITH TENANT'S REPRESENTATIVE PRIOR TO INSTALLATION.
11. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL FIXTURES,
LAMPS AND REPLACEMENTS WORK THAT ARE NOT INDICATED ON DRAWINGS
OR FURNISHED BY TENANT. TENANT TYPICALLY SUPPLIES ALL LIGHTING
FIXTURES, EXIT SIGNS AND LAMPS. REFER TO ELECTRICAL DRAWINGS AND
SCHEDULES. ALL SUCH INSTALLATIONS AND HOOK -UPS ARE BY ELECTRICAL
CONTRACTOR.
12. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO INSTALL OR
REMOVE AND REPLACE AS NECESSARY ALL DAMAGED LIGHT FIXTURES
LENSES, LOUVERS, EAFFLES, HOUSINGS, ETC., RECEIVED ON JOB IN
DAMAGED OR DEFECTIVE CONDITION; WITH REPLACEMENT UNITS.
13. THE ELECTRICAL CONTRACTOR'S CONTRACT, ALONG WITH THE PREVIOUS
LISTED ITEMS, SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING:
WIRING, PANEL BOXES, TRANSFORMERS, SWITCHES, DUPLEX RECEPTACLES,
SIGN TIME CLOCK, JUNCTION BOXES, AND LABOR.
14. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE ANY AND ALL ITEMS
NECESSARY TO COMPLETE THIS PROJECT AS DRAWN.
15. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL
ELECTRICAL EQUIPMENT AND WIRING IN ACCEPTANCE WITH LANDLORD'S
DESIGN CRITERIA.
16. ELECTRICAL CONTRACTOR TO PROVIDE CIRCUIT "LOCK-ON" CLIPS AND
INSTALL SAME ON THE FOLLOWING CIRCUITS:
- CASH -WRAP RECEPTACLES
- HOT WATER HEATER
- STOREFRONT SIGN TIME CLOCK
- ALL CONVENIENCE DUPLEXES
- STOCKROOM LIGHT SWITCH
- NIGHT /EMERGENCY LIGHTING CIRCUIT
- O.H. GRILLE
- HVAC EQUIPMENT
- PHONE
- TRANSFORMER
- WATER HEATER
17. EQUIPMENT IDENTIFICATION
A. IDENTIFY ALL EQUIPMENT AND APPARATUS WITH ENGRAVED
BAKELITE NAMEPLATE OR IMPRESSED, PLASTIC STRIP.
REFER TO NOTE 22.
18. ELECTRICAL CONTRACTOR SHALL BALANCE THE LOADS ACROSS ALL
PHASES AN!) SHALL PROVIDE A CIRCUIT DIRECTORY WITH TYPED
CIRCUIT DESIGNATION CARD UNDER PLASTIC COVER ON THE INSIDE
OF EACH PANEL DOOR. ELECTRICAL CONTRACTOR SHALL ALSO FURNISH
AND INSTALL NAMEPLATE ON ALL DISCONNECT SWITCHES AND PANELS.
ALL NEW ELECTRICAL MATERIALS, PRODUCTS AND EQUIPMENT
(INCLUDING ALL COMPONENTS THEREOF) SHALL BEAR THE
UNDERWRITER'S LABORATORIES LABEL AND MEET THE APPROPRIATE
ASTM. NEC AND NEMA STANDARDS.
19. ONLY U.L. APPROVED CUT -OUTS WILL BE PERMITTED IN DEMISING
AND OTHER FIRE RATED PARTITIONS FOR ELECTRICAL
CIRCUITS /SWITCHES, AND FOR ALL UTILITY PENETRATIONS.
20. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A
TEMPORARY LIGHTING AND POWER SYSTEM FOR THE WORK OF ALL
TRADES DURING CONSTRUCTION, AND SHALL REMOVE THE SAME PRIOR
TO THE COMPLETION OF THE PROJECT.
21. TENANT'S ELECTRICAL CONTRACTOR SHALL BE REQUIRED TO PROVIDE
TEMPORARY POWER. WITH GROUND FAULT PROTECTION FOR ALL POWER
EQUIPMENT USED IN THE PREMISES. ALL TEMPORARY SERVICES ARE TO BE
REMOVED UPON COMPLETION OF THE WORK AND PRIOR TO OPENING.
22. ELECTRICAL WORK (RECESSED DUPLEX OUTLETS, ETC.) IS ALLOWED
IN THE DIVIDING PARTITIONS BETWEEN TENANTS WHERE (1) NO
WORK CONFLICTS WITH OR DAMAGES WORK PREVIOUSLY INSTALLED BY
AN ADJOINING TENANT, AND (2) CODES'AND BUILDING DEPARTMENT
DO NOT RESTRICT PROPOSED WORK.
23. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE ANY AND ALL
BLOCKING, CHAINS, HANGERS, ETC., AS NECESSARY TO SUPPORT
LIGHTING SYSTEMS.
24. BUZZERS /CHIMES /PUSH BUTTONS
A. BUZZERS, CHIMES, AND PUSH BUTTONS SHALL BE EQUAL TO
THOSE MANUFACTURED BY EDWARDS AND SHALL OPERATE FROM
A 24 VOLT TRANSFORMER ON THE STOCKROOM RECEPTACLE CIRCUIT.
B. WHEN USED IN AN EXTERIOR CONDITION, THE PUSH BUTTON
SHALL MEET NEMA STANDARDS FOR EXTERIOR OPERATION.
C. CHIMES AND BUZZERS SHALL BE MOUNTED ON THE WALL,(BENEATH
THE CEILING) IN THE STOCKROOM AND WITHIN THE CASH /WRAP
IN THE SALES AREA.
D. SIGNAL CONDUCTORS WIRING FOR ANUNCIATOR DEVICES AND BETWEEN
MULTIPLE DEVICES AND THEIR ACTIVATORS, SHALL BE ROUTED
AND SHIELDED ACCORDING TO PREVAILING ORDINANCES.
25. RECEPTACLES
A. CONVENIENCE OUTLETS /RECEPTACLES SHALL BE NEMA, 5 -15R,
RATED AT 125VAC/15A AS MANUFACTURED BY LEVITON, PASS
AND SEYMOUR OR EQUAL . RECEPTACLE AND COVER PLATE
SHALL BE OF HIGH - IMPACT WHITE NYLON, EXCEPT IN JEANS
BIN BASE (NOTE 24 -B.)
2. CONVENIENCE OUTLETS /RECEPTACLES LOCATED IN THE BASE OF JEANS
BINS SHALL BE SIMILAR TO 24-A ABOVE. RECEPTACLE AND COVER
PLATE SHALL BE OF HIGH IMPACT DARK -GRAY NYLON.
C: OUTLETS /RECEPTACLES FOR DEDICATED CIRCUITS WITH ISOLATED
GROUNDS SHALL BE 20A /125VAC, NEMA 5 -20R AS MANUFACTURED BY
PASS AND SEYMOUR (OR EQUAL) WITH ORANGE NYLON RECEPTACLE PACE
AND MATCHING ORANGE THERMO PLASTIC WALL PLATE WITH THE WORDS
"ISOLATED GROUND" ENGRAVED THEREON.
D. ALL CONVENIENCE DUPLEX RECEPTACLES AND OVERHEAD GRILLE
SWITCH PLATES SHALL BE LOCATED 12" A.F.F. UNLESS OTHERWISE
NOTED ON PLANS. (NOTE: MANAGERS DESK AT STOCKROOM IS A
PARTICULAR EXCEPTION).
•
•
1.
E. GROUND FAULT INTERRUPTER RECEPTACLES SHALL BE AS
FOLLOWS:
1. FOR INTERIOR APPLICATIONS: INSTALL GFI
RECEPTACLE DESIGNED TO TRIP AT 5 11* IN 1/30TH
OF A SECOND RATED AT 115VAC /20A WITH WHITE
FACE AND STAINLESS STEEL COVER PLATE AS
MANUFACTURED BY PASS AND SEYMOUR OR EQUAL.
2. FOR EXTERIOR APPLICATIONS, INSTALL CFI
RECEPTACLE AS DESIGNED FOR TRIP AND RATING
ABOVE. RECEPTACLE SHALL BE MOUNTED IN A BOX
RATED NEMA 3R AND SHALL COVER PLATE AS
MANUFACTURED BY PASS AND SEYMOUR OR EQUAL.
F. NO CONVENIENCE DUPLEX RECEPTACLES SHALL BE LOCATED ON
CERAMIC TILE OR A MIRRORED SURFACE UNLESS SPECIFICALLY
REQUIRED BY CITY CODE. •
26 LIGHT SWITCH BOXES
ENCLOSURE BOXES TO SERVE AS RECEIVER FOR VARIOUS, LIGHT
CONTROL SWITCHES (PER PLANS) MEET SAME CRITERIA AS FOR
OUTLET /BOXES (ABOVE). ALL BOXES SHALL (AS.A MINIMUM
STANDARD.) BE RATED FOR THE VOLTAGE AND AMPERAGE OF THE CIRCUIT.
BEING SWITCHED AND /OR TO MEET LOCAL CODES AND ORDINANCES.
27. LIGHT SWITCHES •
A. GENERAL -USE SNAP SWITCHES AS INDICATED ON PLANS
ARE AS MANUFACTURED BY LEVITON, PASS AND SEYMOUR
OR EQUAL AND SHALL BE RATED AT 20A /125VAC. THE
SWITCH FACE AND COVER PLATE SHALL BE OF WHITE
HIGH - IMPACT NYLON UNLESS NOTED OTHERWISE.
B. SNAP - SWITCHES USED TO CONTROL OUTLETS /RECEPTACLES
SHALL BE OF THE HEAVY- DUTY'TYPE RATED AT THE
VOLTAGE /AMPERAGE INDICATED•ON PLANS AND DIAGRAMS
AND SHALL BE FURTHER QUALIFIED TO CONTROL MOTOR LOADS
UP TO 2 H.P., UNLESS NOTED OTHERWISE, AS MANUFACTURED
BY PASS AND SEYMOUR OR EQUAL,(WHITE BODY AND COVER
PLATE).
C. 277VAC /20A LIGHTING CIRCUITS WILL NOT BE CONTROLLED
ON GENERAL -USE SNAP SWITCHES. 277 /VAC FIXTURES WILL
BE CONTROLLED FROM THE PRIMARY PANEL AS INDICATED
AT RISER DIAGRAMS. THESE 1P20A CIRCUIT BREAKERS SHALL
BE RATED FOR "SWITCHING- DUTY."
28. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO WIRE INDIVIDUAL
FIXTURES INSIDE TENANT FURNISHED LIGHT BOXES. FINAL HOME
RUNS, CONNECTIONS, AND LAMPING SHALL ALSO BE INCLUDED.
29. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ELECTRICAL
CONNECTORS TO OVERHEAD GRILLE INCLUDING BUT NOT LIMITED TO GRILLE
MOTOR, ALL LIMIT SWITCHES, AND INTERLOCK SWITCHES. •
30. GENERAL
ALL WIRING CONFORM TO THE. STANDARDS OF THE
NATIONAL ELECTRICAL CODE AND MEET ALL LOCAL REGULATIONS.
31. LIGHTING AND POWER. PANELS'
A. ALL LIGHT AND POWER PANELS SHALL BE GENERAL ELECTRIC,
WESTINGHOUSE, OR I -T -E; UTILIZING BOLTED BREAKERS
WITH INTEGRAL MAIN BREAKER (SIZE PER PLANS).
32. ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL SEVEN (7) DAY
24 HOUR TIME CLOCK FOR STOREFRONT SIGNAGE. TIME CLOCK SHALL
BE AMF PARAGON 7000 SERIES 7 -DAY TIME CONTROL WITH MANUAL
HAND TRIP OR EQUAL.
33. STEP'DOWN TRANSFORMERS
A. STEP DOWN TRANSFORMERS SHALL BE EQUAL TO GE OR
WESTINGHOUSE, 600 VOLT. CLASS "DRY. TYPE" SINGLE OR
• THREE PHASE PER PLANS CLASS "R" INSULATION WITH
MULTIPLE TAPS ABOVE AND BELOW RATED VOLTAGE.
34. CONDUIT
A. ALL CONDUIT SHALL BE CONCEALED, 11i FINISHED AREAS.
ALL CONDUIT UNDER GROUND OR IN CONCRETE SLAB SHALL BE
RIGID CONDUIT. ALL OTHER CONDUIT MAY BE ELECTRICAL
METALLIC TUBING (E.M.T.). ALL OUTLETS SHALL'BE FLUSH
MOUNTED, ALL CONDUITS SHALL BE RUN PARALLEL WITH AND
AT RIGHT ANGLES TO THE BUILDING CONSTRUCTION AND
SHALL BE LEVEL. FLEXIBLE METALLIC TUBING (F.M.T.) MAY
BE USED WHERE PERMITTED (BY N.E.C. ARTICLE 349 OR
LOCAL RESTRICTIONS)
B. CONTRACTOR WILL PROVIDE NECESSARY CABLES, JUMPERS,
ETC., TO INSURE CONTINUOUS GROUND 'IN CONDUIT SYSTEM.
C. ECR(S) REQUIRE TRUE THREE WIRE DEDICATED LINES.
THIS IS A TRUE GROUND NOT A NEUTRAL. CONDUIT MUST
NOT BE USED AS THE ONLY GROUNDING MEANS.
D. ALL WIRING CONDUITS, ETC., REQUIRED FOR THE PROPER
CONTROL OF THE HVAC SYSTEMS SHALL BE THE RESPONSIBILITY
OF THE ELECTRICAL SUB - CONTRACTOR. THE MECHANICAL
SUB - CONTRACTOR SHALL SUPPLY THE CONTROLS AND WIRING
DIAGRAMS TO THE ELECTRICAL SUB- CONTRACTOR. ALL UNITS
SHALL BE PROVIDED WITH INDIVIDUAL DISCONNECTS AT EACH
UNIT IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE.
E. WHERE STORE IS ON ANY LEVEL BUT GROUND LEVEL, THE
TENANT'S GENERAL CONTRACTOR SHALL RUN ALL CONDUIT FOR
ELECTRICAL FLOOR OUTLETS AND TELEPHONE FLOOR OUTLETS,
TIGHT AGAINST THE UNDERSIDE OF THE SECOND FLOOR LEVEL.
THE SECOND FLOOR STRUCTURAL SLAB SHALL BE CORED AS
REQUIRED TO INSTALL THESE ITEMS AT THE LOCATIONS SHOWN
ON THE PLANS.
F. ALL TELEPHONE WIRE SHALL BE INSTALLED IN CONDUIT. ALL
WIRES SHALCBE COPPER.
35. CONDUCTORS
A. NO ALUMINUM WIRING I5 ACCEPTABLE.
B. NO.8 AND SMALLER, SOLID CONDUCTOR, COPPER TYPES,
TW, THW, THWN, R, RH, RHW, WITH IDEAL WINGNUTS,
SCOTCHLOCK CONNECTORS.
C. N0.6 AND LARGER, STANDARD CONDUCTOR, COPPER TYPES,
THW, THWN, RHW, RHWN, WITH SOLDEELESS BOLTED
PRESSURE CONNECTORS.
D. FIXTURE WIRING IN CHANNELS OF FLUORESCENT
FIXTURES SHALL BE EITHER RHH ON THERMOPLASTIC
'APPLIANCE WIRE' - 105 DEGREE C COPPER (CSATYPE
THW).
E. MINIMUM SIZE, SHALL BE N0.12 AWG, RHWN, EXCEPT
FOR CONTROL CIRCUITS.
36. OUTLET BOXES
OUTLET BOXES SHALL BE PRESSED STEEL KNOCKOUT TYPE CAST IRON
WITH DRILLED, TAPPED, AND PLUGGED HOLES OR PVC. CAST IRON
BOXES SHALL BE HOT DIPPED GALVANIZED OR SHERARDIZED. ALL
BOXES SHALL BE OF PROPER CODE SIZE FOR THE NUMBER OF WIRES OR
CONDUITS PASSING THROUGH OR TERMINATING THEREIN.
37. HVAC EQUIPMENT
A. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WIRING,
CONDUIT, FINAL CONNECTIONS, DISCONNECTS, INTERLOCKS,
DAMPER ACTUATORS, ALL PDURIFAND CONTROL WIRING DIAGRAMS
ALL HVAC EQUIPMENT SHALL B FURNISHED'BY HVAC
CONTRACTOR.
B. ELECTRICAL CONTRACTOR SHALL INSTALL OWNER FURNISHED (UNLESS)
OTHERWISE NOTED) THERMOSTAT.IF THERMOSTAT EMPLOYS ISOLATED
SENSOR, WIRING FOR THESE ELEMENTS SHALL BE SHIELDED CABLE.
THERMOSTAT SHALL BE LOCATED IN THE STOCKROOM BY FANAGER'S
DESK.SENSOR SHALL BE LOCATED ON SALES AREA CEII IN A
CENTRAL LOCATION, AWAY FROM ALL HEAT SOURCES.
C. SHIELDED CABLE FOR REMOTE SENSORS (THERMOSTAT) SHALL Be. EQUAL
TO ONE OF THE FOLLOWING:
- BELDON 18760
- AMERICAN WIRE #A22602
- COLUABIA WIRE •C2534
TEMPORARY SERVICES
THE GENERAL CONT;.'CTOR SHALL PROVIDE THE FOLLOWING SPECIFIC ITEMS
OF TEMPORARY SERVICES:
D. TEMPORARY HEAT: WHEN REQUIRED FOR PROPER INSTALLATION OR
..:q., !- :..,.,� x' ....,ten . {�J.�l. . ..m. s.: ".A •.. r r . :Y ". :',.. ,• 1.1'ie'.K .,.4 .. q E Y.: R .ENE N VEt S .L,.
IIIII!r
II III l r i� r�r
2I I 31 ( 41 I 5 1 6.
No.1e a w %r?"" i.
T E T.. T I I T 6 8 L 9 9 T11641110 al
il 11111[ ii�i��i 1I T 11II ��i 41
•
A. TELEPHONE - THE TENANT'S GENERAL CONTRACTOR SHALL. INSTALL A
JOB SITE TELEPHONE AND NOTIFY TENANT OF THE TELEPHONE NUMBER
AND THE NAME OF THE SUPERINTENDENT ON OR BEFORE JOB START -UP.
B. TEMPORARY WATER - WATER REQUIRED IN THE PERFORMANCE OF THE
CONTRACT SHALL BE PROVIDED AND PAID FOR BY THE CONTRACTOR.
WATER USED FOR HUMAN CONSUMPTION SHALL CONFORM TO
REQUIREMENTS OF STATE AND LOCAL AUTHORITIES. FOR POTABLE
t)ATER.
C . TEMPORARY ELECTRICITY - TEMPORARY ELECTRIC SERVICE REQUIRED
IN THE PERFORMANCE OF THE CONTRACT SHALL BE FURNISHED AND
MAINTAIN ALL TEMPORARY OVERHEAD CONSTRUCTION, EASTERS, DROPS,
AND OTHER WIRING AND FITTINGS FOR BOTH LIGHT AND POWER AT
LOCATIONS REQUIRED IN THE WORK AND SHALL BEAR THE COST OF
MAKING THE SERVICE CONNECTIONS. BEFORE FINAL ACCEPTANCE,
TEMPORARY ELECTRICAL SERVICE FACILITIES INSTALLED BY THE
CONTRACTOR SHALL BE REMOVED AND OR SERVICE DISCONNECTED
IN ACCEPTABLE MANNER.
PROTECTION OF ANY PORTION OF TOE WORK; CONTRACTOR SHALL
•FURNISH AND INSTALL TEMPORARY HEATING UNITS'AS APPROVED BY
THE LANDLORD OR LOCA.*.. AUTHORITY. •
E. COST'OF LANDLORD PROVIDED UTILITY SERVICES: IF THE LANDLORD
ELECTS TO PROVIDE TEMPORARY UTILITY SERVICES, THE CONTRACTOR
WILL BE SO INFORMED BY THE TENANT. • THE CONTRACTOR SHALL
MAKE PROVISIONS OR COORDINATE WITH LANDLORD'S GENERAL .
CONTRACTOR TO PAY THE COST OF SAID TEMPORARY CONSTRUCTION
AND UTILITY SERVICES.
.,.1 :,r..;Jt+��,ia lr�:it;'m..'Et.•f'. C� +�'ips�s,•,��, »•M'Ac3. :.. ,•:2SsR
tJaee s•
'ItJCW1)
s UI\RN- A p
WOO
E cO» titartit • UtZrt
har appro re
QP a
Plan C approva
a
o errors that the om i s sions and a;OY
t understand error$ and violation of
ans to authorize the t of con-
rce.• P.ere1P dged'
,lava adopted c not Ordina a
;, . ckn
tractor's code #a;ved 1�: s
C °P
BY
Date
i Permit {3a
Ok' WOO
' OA
i 6
• RECEIVED
CITY OF TIiKWIIA
APR. 3 0
PERMIT CENTER
gaol 000l
u t21
d u
i•A" -
vSz ..t..
c- u
IL" ce
werw
• •
1
PANEL CIRCUIT LOADING
21
23
4
25
27
'r'29
1_1_4122
3 1
5 1Wc)
•7 7--0 )
•
13 is
15 j
17 I
19
I
e
Sa)
33 Imo I T 34
35 �'' Fi r-r I
*37 a Ott
i 138
409 1a) ' 40
41 `•= 16j ; % i 4'
r c�. 161 i / 4;-1, i
31 (XX)%'f`,ri,C' I
PANEL A.
TOTAL WATTS
I� �0 x 1:25 =
2 i AM 208 VOLTS 3 D -!ASE. 4 w:RE
MAINS 7i Z411 I`le +3; MOO; TiNG SURFACE
TYPE NLAB SOLID BUSS
PANEL RISER DIAGRAM
LAMPS & FIXTURES
FURNISHED BY
INSTALLED BY
-Y'
F AB C -
1 30
SUB -TOTAL
208/120, 3PH, 4W
ELEC SER V CE
BY U..
ELEC METER
BY 1 •
200A/3P DISCONNECT
,FUSE 0 200AMPS.
BY T.G.C.
4 p4 /OTHHN IN 2"C.
QUAN MANUFACTURER
1 P120 AMP BREAKERS TYPICAL UNLESS NOTED OTHERWISE
2
36
•
CATALOG NO.
LOCATION
i- -. F -
ef20-2/bseri
214 14
T...
-r - -.-
z
011 _ _.
p
P4_ . _ __
MANUFACTURER MODEL NO.
MANUFACTURER MODEL NO,
ELECTRIC HEATER
MANUFACTURER MODEL NO.
7A`rta I=1 _ z
B.T.U. CAPACITY
TYPE
SIZE
C.F.M.
S.P. I H.P.
C.F.M. S.P. H.P.
B.T.U. CAPACITY
1L :.
RESPONSIBILITY NOTES
1. ALL CUTTING OF ROOF OPENINGS, SUPPORT FOR ROOF OPENINGS, PITCH PANS.
ROOF CURBS, FLASHINGS, REPAIR TO ROOF, ETC., ASSOCIATED WITH THE HVAC
SUB- CONTRACTOR SHALL BE THE RESPONSIBILITY AND PART OF THE CONTRACT
WITH THE HVAC SUB - CONTRACTOR. SUB - CONTRACTOR SHALL EMPLOY THE LANDLORD'S
ROOFERS FOR THIS WORK SO AS TO MAINTAIN THE ROOF BOND.
2. ALL CUTTING OF ROOF OPENINGS, SUPPORT FOR ROOF OPENINGS, PITCH PANS, ROC:
CURBS, FLASHINGS, REPAIR TO ROOF, ETC., ASSOCIATED WITH THE PLUMBING
SUB - CONTRACTOR SHALL BE THE RESPONSIBILITY AND PART OF THE CONTRACT WITH
THE PLUMBING SUB - CONTRACTOR. SUB - CONTRACTOR SHALL EMPLOY THE
LANDLORD'S ROOFERS FOR THIS WORK SO AS TO MAINTAIN THE ROOF BOND.
3. ALL WIRING CONDUITS, ETC., REQUIRED FOR THE PROPER CONTROL OF THE
HVAC SYSTEMS SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL SUB -- CONTRACTOR.
THE MECHANICAL SUB - CONTRACTOR SHALL SUPPLY THE CONTROLS AND WIRING
DIAGRAMS TO THE ELECTRICAL SUB - CONTRACTOR.
4. SANITARY SEWER AND DOMESTIC WATER SHALL BE STUBBED INTO THE PREMISES
3Y THE LANDLORD. SEE MECHANICAL SHEETS FOR LOCATION OF STUB- -INS.
5. THE SPRINKLER CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO THE TENANT'S
LANDLORD AND TO THE APPROPRIATE RATING BUREAU FOR THEIR APPROVAL.
A COPY OF THE APPROVAL LETTER FROM THE RATING BUREAU SHALL BE FORWARDED
TO THE TENANT'S LANDLORD.
6. THE TENANT'S GENERAL CONTRACTOR SHALL RUN ALL CONDUIT FOR ELECTRICAL
FLOOR OUTLETS, TELEPHONE OUTLETS, AND LINES REQUIRED FOR PLUMBING
ROUGH -IN TIGHT AGAINST THE UNDERSIDE OF THE SECOND FLOOR LEVEL. THE
SECOND FLOOR STRUCTURAL SLAB SHALL BE CORED AS REQUIRED TO INSTALL
THESE ITEMS AT THE LOCATIONS SHOWN ON TH,E PLANS.
7 ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ELECTRICAL
CONNECTIONS TO OVERHEAD DOOR INCLUDING BUT NOT LIMITED TO DOOR MOTOR
AND ALL LIMIT SWITCHES.
8. THE HVAC SUB - CONTRACTOR SHALL IDENTIFY ALL ROOF MOUNTED HVAC EQUIPMEN'
AND APPARATUS WITH 6" HIGH PAINTED STENCILED STORE NAME ON ALL SIDES
OF EQUIPMENT.
9. THE TENANT'S GENERAL CONTRACTOR SHALL MODIFY EXSITING SPRINKLER LOCATIONS
AND ADD ADDITIONAL HEAD WHERE REQUIRED TO CONFORM WITH NEW FLOOR PLAN
AND CEILING DESIGN LAYOUT AS REQUIRED BY LOCAL CODES.
VOLT /PHASE
K. W.
3 .
TOTAL F.L.A.
FAN MOTOR DATA
VOLTS PHASE ' R.P.M.
VOLTS PHASE
O pa l
ACCESSORIES
ACCESSORIES
STAG'S
1
REF.
NOTE 1
REF.
NOTE
REF.
NOTE
NOTES
NOTES
I) kl /c�v I.4 Ig'146.16
se-e lat-1"A 1 tr.• 061 riI-
8 -
C -2
C -3
A
B
C
C -4
A
B
C -a
C -8
RESPONSIBILITIES
E -- EXISTING T -- TENANT
L - LANDLORD
C - TENANT'S GENERAL CONTRACTOR
A MECHANICAL .
A ROOFTOP PACKAGE UNIT
B AIR HANDLING UNIT
C CONDENSING UNIT
D CHILLED WATER COIL
E ELECTRIC STRIP HEATER
F _DUCTWORK & INSULATION
G GRILLES & REGISTERS
H THERMOSTAT
I STARTERS, RELAYS, CONTACTORS, ETC.
J HVAC WIRING DIAGRAM
CONDENSATE DRAIN
L OPENING THRU ROOF
M ROOF CURB
B EXHAUST SYSTEM
m IF
C C
C
G
G
C
T
C
4
a
PANEL B
T" t 'E NHB SOLID BUSS
J
7 -3 # 16 THHN 1N 3 /4" C.
2P /30A DISC 0 UNIT HEATER
NOTE: T.G.C. SHALL PROVIDE ITEMS NECESSARY TO COMPLETE RISER AS
INDICATED ABOVE. T.G.C. SHALL REUSE EXISTING DISTRIBUTION
EOUIPMENT WHERE POSSIBLE. •
. -. .
REF.
NOTE
TIME COCK FOR SHOw WINDOW
AND SIGN CIRCUITS.
LIGHT FIXTURE SCHEDULE
�t
r
SUB -TOTAL
MOUNTING
REC SURF PEND WALL
127T
TOTAL WATTS x 1.25 =
AM °S AT 277 VOLTS 3
MANS ti
Ptl
0 Amor?
THHN IN 1- /4" C.
3P /200A WP /DISC 0 RTU. FUSE 0 110A.
, LIGHTING FIXTURE SCHEDULE NOTES:
1. EQUIP ALL FLUORESCENT LIGHT FIXTURES WITH MAXIMIZER BALLASTS AND REDUCED
WATTAGE LAMPS.
2. PLACE ALL CROSS HATCHED LIGHTS AND TOILET LIGHT ON 24 HOUR CIRCUIT.
3: PROVIDE EMERGENCY POWER BATTERY PACK BAI LASTS FOR ALL EMERGENCY LIGHTS.
(CROSS- HATCHED AND EXIT LIGHTING) • • .
4. • LAMP' COLOR TEMPERATURE - 3200 DEG KELVIN., • •
5. • REFER TO LIGHT TPACK SYSTEMS DETAIL ON LIGHTING PLAN. .
lam. FA11.1 - r A f ., �►� -w-� . • .
* - 24 HO. R CIRCUIT (PROVIDE LOCK -ON DEVICES)
LAMP_SCHEDULE
PHASE 4 WIRE
SURFACE
NOTE:
TENANT'S GENERAL CONTRACTOR SHALL PROVIDE
. AND INSTALL ALL COPPER CONDUCTERS.
•
SYMBOL DESCRIPTION
----/ - HOME RUN TO PANEL - CIRCUIT AS INDICATED
- -- - -- CONDUIT CONCEALED IN FLOOR
® LOW VOLTAGE TRANSFORMER - VOLTAGE AS REQUIRED
RECESSED LIGHT FIXTURE - TYPE AS INDICATED
SURFACE MOUNTED LIGHT FIXTURE - TYPE AS INDICATED
NIGHT LIGHT
INCANDESCENT FIXTURE / LOW VOLTAGE FIXTURE - TYPE AS INDICATED
PORCELAIN RECEPTACLE - KEYLESS - 100 WATT
JUNCTION BOX "-- SIZE AND TYPE AS REQUIRED - FLOOR TO HEIGHT AS INDICATED
S
LAMP SIZE NOTES
•
WALL SWITCH. SPST. COLOR PER SPECS. SIERRA
FLOOR RECEPTACLE - FLUSH IN FINISH FLOOR. STL CITY --
REFERENCE SHEET El, NOTE # 10.
DUPLEX CONVENIENCE RECEPTACLE - GROUNDED. 15A, 125V, 3P, 3W, COLOR PER
SPECS. FLOOR TO HEIGHT AS INDICATED, SIERRA 1802
TELEPHONE OUTLET - FLOOR. STEEL CITY - NO. 602 AL CAST BOX, NO. P602 AL
COVER, NO. P60 CP AL CARPET FLANGE, AND NO. 700 AL BELL NOZZEL
SERVICE BUZZER - EDWARDS 24V NO. 115 -165 W/ NO. 592 SIGNAL TRANSFORMER
PUSHBUTTON - EDWARDS NO. 620, WEATHERPROOF W/ STAINLESS STEEL COVER,
NO. 147 ENGRAVED "SERVICE BELL" MOUNTED 54" ABOVE FINISHED FLOOR
TELEPHONE OUTLET - WALL. OUTLET BOX W7 ARROW -HART 3144 -22 SUB - FRAME.
ONE HOLE BUSHED COVER
MOTOR - H.P. AS INDICATED .
SIGN OUTLET - MOUNTED ABOVE CEILING
MANUFACTURER
J
MECHANICAL EQUIPMENT SCHEDULE
EXHAUST FANS
MANUFACTURER MODEL NO.
GRILLES AND REGISTERS
MODEL NO,
;4 L.v l �> A
1•1SULATiO'r' iN C !LING
NSULA r 0'. REQU'RE D !Pi WALL
r
TYPE C.F.M.
I So
TYPE FRAME TYPE = MAX. NOISE
CRITERIA
INSULATION REQUIREMENTS
- I �
S.P.
•
III II�IiIII�IIl�I111' L1I1 � ( 1111111i111113l�II IIIIIII�IIIIIIII
I 1
No 18
(lillllli lillllil� Illllllll li 'li iliihI � : iI l lii�lli� [Ill �l IIlI�1rl! Ili�lf ll gi lll � lilllllli
FAN MOTOR DATA
VOLTS PHASE R.P.M.
11
NO
I:
H.P.
FIRE - t VOLUME
DAMPERS PATTERN: QUANTITY E A.
2 :90 2 :180 3 4
NOTES
ACCESSORIES
61 Efr. eJtvi e ly
•
REF.
NOTE
2
11•••••••■■••■10•KaMMM MON • •■■•••■••■•••■•• 111111 • 11 1• 4111 • 1 • 11 ■1•••••••••••••••1•MMIYAMMINIMM••■••••••mi
2
gitP 2 1
NOTES
• •h.
C
D -1
D -9
A
B_
C
D
TOILET EXHAUST, EP -1
EXHAUST FANS
DUCTWORK
GRILLES
OPENING THRU ROOF
C PLUMBING
C -1 J WATER CLOSETS
A WATER CLOSETS
B UNDERSLAB ROUGH IN
C FINAL CONNECTIONS & VENTS
C -6
A
B
C -7
A
B
SERVICE SINK
SERVICE SINK WITH RIM GUARD
UNDERSLAB ROUGH -IN
FINAL CONNECTIONS & VENTS
SINK AT COUNTER
SINK
UNDERSLAB ROUGH -IN
FINAL CONNECTIONS & VENTS
FLOOR DRAINS
FLOOR DRAINS
UNDERSLAB ROUGH -IN
FINAL CONNECTIONS & VENT_ S
A
D ELECTRICAL
D -2
D -3
D-_.4
D -5
D - 6I
D -7
D -8
LAVATORIES
LAVATORIES _
UNDERSLAB ROUGH -IN
FINAL CONNECTIONS ' & VENTS
CLEANOUTS
CLEANOUTS
• UNDERSLAB ROUGH -IN & FINAL CONN.
ELECTRIC WATER COOL
ELECTRIC WATER COOLER
UNDERSLAB ROUGH -IN
FINAL CONNECTIONS & VENT
WATER HEATER
WATER HEATER
FINAL CONNECTIONS
INSULATION - HOT WATER LINE
MISCELLANEOUS
WATER DEPOSIT .... _.._. _ . .
ONLY
CH. WTR, SUP. & RET. AND PIPING INSUL.
HOT WTR. SUP. & RET AND. PIPING INSUL.
ALL CONTROLS CH & HOT WTR. .,PIRIAIG
ALL GAP FEES
OP:iiie!igli .
SPRINKLER S
ENGINEERING
EQUIPMENT '
'EMPTY' ELEC. CONDUIT TO SPACE
MAIN DISCONNECT SWITCH .
LIGHTING PANELS
CONTACTORS & TIME SWITCH
STEP DOWN TRANSFORMER
LIGHT FIXT. S LAMPS [REF. SCHED.1
ROUGH-IN. TO LIGHT FIXTURES �-
FINAL CONNECT TO LIGHT FIXTURES .
CONVENIENCE OUTLETS
0 - 10 MISCELLANEOUS
D -11 FINAL CONNECTIONS TO SIGN
D--12 FINAL CONNECTIONS TO HVAC EQUIPMENT
D -13 FINAL CONNECTIONS TO WATER HEATER
0---14 TEMPERATURE CONTROL WIRING
D -15 PUSHBUTTON & BUZZER /C d- }II*1I; GAt,L
0'18 TELEPHONES
A PLYWOOD PANEL BOARDS
B EQUIPMENT .
FLOOR BOXES .& EMPTY 3/4" CONDUIT
WALL BOXES & EMPTY 3/4'r CONDUIT
TELEPHONE SERVICE TO /INCLUDE PREMISES
0-17 FLOOR OUTLETS
A EMPTY CONDUIT & FLOOR BOXES
B FINAL WIRING .
a : 'Lcr 'ra , L; ,a►.I si.k.rt 4
D -18 ELECTRICAL CONN. TO OVERHEAD GRILLE,
RECEIVED
CITY OF TUKWILA
AM 3 U i'$2
PERMIT CENTER
dp Don Posen PIE
Con urblt n9tne
aoi r' e1 n gaA •
8.4.04:120.004. 7wrgsYmon ' SWIM/ NM*
any *twig
DATE:1'044• cie
DRAWN BY: t,
CHECKED BY;
SHEET:
z
P aw
b aile
CYz
cba
ca
< LLI
N
JIc
� T
u
„Figz
� J
4
L,
LL INCOMING 3/4" C.W.
\ VERIFY LOCATION AT
.O8SITE
UNION
GATE VALVE
6 GALLON WATER HEATER ABOVE TOILET CEILING.
PROVIDE 3" DEEP GALV PAN W /SOLDERED SEAMS.
ROUTE T&P MO AUX. DRAIN '11 /INTO FLOOR DRAIN
WATER RISER DIAGRAM
NO SCALE
MECHANICAL PLAN
WASTE RISER DIAGRAM
NO SCALE
3/4"
EXTEND 4" SS TO LL SYSTEM, VERIFY EXACT
LOCATION, FLOW AND DEPTH.
1/2"
LAV 3" FD W /TRAP PRIMER
12" HIGH AIR
CHAMBER (TYP)
Wi4 •
WCO
HC /WC
1/2
1/2"
IV
•1/2"
WC
LAV W /TRAP PRIMER
TERMINATE AT EACH
FIXTURE CONN. WITH
3/8" STOP VALVE.
150. bV211
I I I -Iok2
8
M II�IIIII 11 I 21 1l1lO11 'llll I II'II 4I I I IIIIO I IIII' S I IIIIIIIIIIII1 6.
No.18 it'i:*"
TRANSFORMER FROM LINE VOLTAGE TO 24 V Ft)R T -STAT ---
CARPER
(MOTORIZED)
FURNISHED BY TEN.
INSTALLED BY TGC.
MOTORIZED OAAmER SHALL BE LENNOx FLENZONE M0001 OS (Slit SHORN ON DRAPING)
UMt HEATER sw&L BE DAYTON 3.3 K 208V, t- PHASE, HMI. 2(635
THERMOSTAT SHALL BE $ONEVIIELL TRAMLINE; ITBTCCIO,e w/SU88ASE 10674E1049.
TRAHS$ORNER FOR T -STAT SHALL BE WIVE- ROOCERS 05842 -90.
CONTACTOR Foot STATCHNG UNIT moat SHALL BE F1/RNAS /43QA20u
CEILING
CONTACTOR wimple) 9r Inc
RISTALLLD BY T.C.C. (T.C.C. SHALL
FURNISH ALL BOXES a COVERS FOR
TRANSFORMERS NOODLES a
CONDUCTORS TO PANEL
THERMOSTAT w/M S.:MSC BY TENANT pr 0 —L3 CONDUCTORS TO PANEL
SE:UENCE OF OPERATION:
T. T -STAT DETECTS 00.0N0 FOR COOLING'
A ItOTOR12CD DAMPER S FUU.r OPEN (NORMµ, CONIXDON)
B. UNIT HEATER LS 'OR•
2. T -STAT STAGE 1 DETECTS .DEMAND FOR HEAT:
A MOTOfl1ZED DAMPER IS FULLY CLOSED
B. weir HEATER IS 'ah'T` �[
3. f -STAT STAGE 2 DETECTS DEMAND FOR Kr,A7
A MOTOWZED DAHPER IS FUMY CLOSED
B. NIT HEATER IS 'ON'
ELECTRIC
UNIT
HEATER
BY TENANT
MOTOR FURNISHED //QM�ER A
Y 208V UNIT HEATER CONTROLS
NOT TO SCALE
2
■
14
v
14
i2 /l
2 . 1 0"
j
MECHANICAL NOTES:
12 1 .0"
.1
12. 4'
1. FIRST TWENTY FEET OF SUPPLY /RETURN DUCTWORK FROM/TO UNIT SHALL BE INSULATED INTERNALLY
WITH 1' ACOUSTICAL LINER. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR.
2. FLEX DUCT SHALL BE PREINSULATED WITH 1.1/2' THICK FIBERGLASS, 1 # DENSITY FLEXMASTER OR
EQUAL. PROVIDE SPIN"IN FITTING WITH INTEGRAL VOLUME DAMPER AT EACH TAP. MAXIMUM FLEX
RUN - SIX FEET (6' -0 ").
3. T.G.C. SHALL VERIFY EXACT LOCATION OF HVAC EQUIPMENT BEFORE FABRICATING DUCTWORK.
4. INSTALL HEAT(ER) WITH AIR -FLOW SWITCH, TEMPERATURE SAFETY CUT -OUTS AND INTERLOCK WITH
COOLING SO THAT COOLING AND HEATING WILL NOT RUN SIMULTANEOUSLY.
5. ROUTE CONDENSATE TO FLOOR DRAIN. (ROUTE ROOFTOP UNIT CONDENSATE THRU CONFINES OF
ROOF CURB)
6. T.G.C. SHALL PROVIDE ACCESS AND /OR CATWALK (PER LOCAL CODES) FOR HVAC EQUIPMENT
MOUNTED ABOVE CFIUNG.
7. UPON COMPLETION OF CONSTRUCTION T.G.C. SHALL CLEAN COILS, ADJUST BELTS AND REPLACE
FILTER MEDIA TO OBTAIN MAXIMUM EFFICIENCY.
8. T.G.C. SHALL INSTALL TENANT FURNISHED UNIT HEATER IN STOCK ROOM. SEE DETAIL.
9. T.G.C. SHALL PROVIDE AND INSTALL THERMOSTAT REMOTE SENSOR WIRING PER LOCAL CODE. WIRE
SHALL BE BELDON # 8760, AMERICAN WIRE CO. # A22602 OR COLUMBIA # C2534 18 GA. SHIELDED.
I0'4
, r
2� IoII
10/1+
1
24 -0'
TN- role.„ ptp
14!o
Ni rEn
411 21011
RCCEIVE
I TY tM.I.A
I id• OF 3U1w
P C E RMIT CENTE
r
en
-0
—0
—.
(
z
i nee
LJ
.-CYZ
UNION o UNN -
J
U VJ
®
:c U
�� VI
:Z _ &
H
s L 4
X
M -1
DATE: / II — el l
DRAWN BY
CHECKED B
SHEET:
a
fV
F
HVAC SPECIFICATIONS
HVAC CALCULATIONS
I. GENERAL .
A. ALL EOM SHALL BE PERFORMED IN CONFORMANCE WITH ALL APPLICABLE CODES AND LANDLORD `S MINIMUM REQUIRKENT8 AS
STATED:H,EREIN;IN THE LEASE; IN THE TENANT M MJAL;MD AS SPECIFIED OR INDICATED ON THE TYPICAL TENANT DRAWING.
CODE REQUIREMENTS, IF MORE RESTRICTIVE THAN LANDLORD REQUIREMENTS, SHALL. TAKE PRECEDENCE.
B. GENERAL AND SPECIAL CONDITIONS OP ALA 201 ANiD TENANT'S (*Am CONDITIONS REQUIREMENTS SMALL APPLY UNLESS
OTHERWt$E NOTED.
C. ALL WORK SHALL BE PERFORMED . AS MEWED 0% DRAWINGS UNLESS FIELD CONDITIONS REQUIRE MI000 CIiAiICLS TO SE MADE,
MINOR CHANGES SHALL BE MADE WITH iO ADDITIONAL COST.
A.' ALL WORK SfALL GUARANTEED FOR ONE YEAR AFTER ACCEPTAIiCE OF WORE BY THE TENANT.
E. SUBMIT SHOP ' DRAWINGS OP ALL MAJOR EQUIPMENT TOR APPROVAL.
F. ACTUAL' OF LANDLORD'S sKRVICES MUST EE FIELR VERIFIED. CHANCES TO CONFORM TO LANDLORD'S LOCATION
SHALL SE MADE AT NO ADDITIONAL COST.
G. MANUFACTURERS' NAMES ON WHICH TIM SPECIM'tCATtON IS BASE? INDICATE THE MINIMUM QUALITY Of PRODUCT REQUIRED BY
LANDLORD. SUBSTITUTIONS MAY BE MADE TO THOSE SPECIFIED IT DEEMED EQUIVALENT BY LANDLORD. ITEMS MOT SPECIFIED
HEREIN SHELL P ET LANDLORD'S REQUIRMEETS. IF A CONTLLCT OCCURS, THE LANDLORD STALL RESOLVE SUCH CONFLICT MD
THE CONTRACTOR SHALL CONFORM TO THE LANDLORD'S DECISION,
H. AS BUILT DRAWINGS • PREPARE AND SUBMIT TO LANDLORD AND TO TENANT "AS BUILT" DRAWINGS INDICATING THE ACTUAL
MANUFACTURER S OF THE EQUIPMENT INSTALLED, THE EXACT LOCATION OF ALL DUCTWORK, PIPING, AND ALL EQUIPMENT WITH
THE 'EQUIPM4ENT' S "AS INSTALLED" SIZE(S).
I. EC(/MEET. PIPING, DUCTWORK, OR ANY OTHER ACCESSORY SHALL MOT SE SUPPORTED FROM LANDLORD'S: CEILING; SEEFIY;
NEUTRAL PIERS; 'PIPING; DUCTWORK; METAL ROOF DECK; LATERAL BRACING; BRIDGING; OR CONDUIT. ITEMS SHALL ONLY BE
SUPPORTED FROM STRUCTURE WHICH HAS BEEN APPROVED BY LANDLORD FOR SUPPORT.
J. ALL ROOF WORK PENETRATIONS AND REPAIRS SHALL SE TOTALLY PERFORMED BY ONLY THOSE ROOFING CONTRACTORS APPROVED
BY LANDLORD. CONTRACTOR SMALL EMPLOY THOSE ROOFING CONTRACTORS APPROVED BY LANDLORD POI ALL ROOF WORK REQUIRED
BY TENANT'S APPROVED DESIGN.
INSTALLA'TION • OF ALL ROOF ROMEO EQUIPMENT SHALL SE CO- ORDINATED WITH LANDLORD'S DESIGNATED UEPRESE$TATtVE.
DEFICIENCIES AND 11011 CONFORMING ITEMS SHALL BE CORRECTED SY CONTRACTOR. FAILURE TO CORRECT SANE SMALL PERMIT
LANDLORD TO CORRECT SAME. TENANT SHALL REIMOORSE LANDLORD POI ALL COSTS INVOLVED tN CORRECTING THE MDR
CONFORMING ITEMS. TENANiT SHALL BE PERMITTED TWO DEDUCT SAME FROM CONTRACTOR'S CONTRACT.
M. FOR INSTALLATION OF SPECIAL EQUIPMENT SUCH AS PANE, CREASE PANS, ETC.; CONFORM TO LANDLORDS MISCELLANEOUS
DETAIL DRAWING,
K.
L.
II. PLUMBING
A. WHERE REQUIRED BY CODE, FURNISH AND IEriS?ALL A MINIMUM OF ONE WATER CLOSET, OWE LAVATORY, ONE FLOOR DRAIN, ONE 6
CALLOt HOT WATER HEATER, AND ALL OTHER REQUIRED MATERIAL AND EQUIPMENT FORA MINIMUM OF OWE COMPLETE TOILET
ROOM, HANDICAPPED FACILITIES AND ALL OTHER FIXTURES MD /OR ADDITIONAL TOILET ROOMS SHALL BE AS REQUIRED SY
APPLICABLE CODES.
B. MATERIALS
11 ALL MATERIALS SHALL BE OF NEW QUALITY. USED MATERIAL SHALL ' iIOT BE PERMITTED. .
2. GAS IS NOT AVAILABLE UNLESS APPROVED BY LANDLORD. GAS PIPING SHALL NE SCHEDULE 40 BLACK STEEL PIPE WITS
MALLEABLE FITTINGS INSTALLED PEE LANDLORD'S, STATE AND LOCAL AUTHORITIES, AND THE UTILITY COMPANY'S
REQUIREMENTS. PAINT ALL GAS PIPING AND ACCESSORIES EXTERIOR TO THE BUILD /NG, WHICH WAS INSTALLED UNDER
THIS CONTRACT, WITH DARK BROWN LEAD OXIDE PAINT. PIPE SHALL t3E CLEANED PRIOR TO PAINTING. CAS PIPING SHALL
NOT BE INSTALLED IN PLENUM AREAS. CAS PIPING ON ROOF SHALL BE INSTALLED AND SUPPORTED PER DETAILS.
3. UNDERGROUND SEWER PIPING SHALL BE SERVICE WEIGHT CAST IRON BELL AND SPIGOT PIPE INSTALLED WITH APPROVED
COMPRESSION (TYLER) JOINTS. UNDERGROUND SEWER PIPING SHALL BE A MINIMUM SIZE OF 2 ".
4. ABOVE GROUND SEWER AND VENT PIPING SHALL i1E SERVICE WEIGHT CAST IRON PIPE WITH NO HUB JOINTS OR AS APPROVED
BY CODE. •PVC AND ABS PIPING ARE NOT PERMITTED.
5. UNDERGROUND HOT AND COLD WATER LIMITS SHALL BE TYPE "K" COPPER PIPE OR TUBIAC WITH SILPOS 5 SILVER BRAZED
Q
6. ABOVE GROUND HOT AND COLD WATER PIPING ,SHALL BE TYPE "L" COPPER WITH 95 -5 SOLDERED JOINTS OR SILPOS 5
SILVER BRAZED JOINTS.
7. ALL ABOVE GROUND HOT AND COLD WATER PIPING SHALL. BE INSULATED WITH A MINIMUM OF 1" rims ; TiBERCLASS PIPE
INSULATION WITH A VAPOR BARRIER. ELL JOINTS SHALL BE INSULATED AND SEALED WITH VAPOR BARRIER CEMENT. USE
OF PLASTIC JACKETS OVER FITTINGS - ,...LL BE PROHIBITFE IN PLENUMS EXCEPT WHERE JACKETS HAVE BEEN CODE
APPROVED.
8. FURNISH AND INSTALL ALL BACKFLOW PREVENTORS, VALVES, UNIONS AND BYPASS PIPING AS REQUIRED BY THE LOCAL
UTILITY AND STALL, - ION WITH REMOTE READER
WATER MO'TttR INSTALL AT Pq EXPENSE TO LANDLORD , A WATER METER IN AM APPROVED LOCATION
PER THE LOCAL WATER UTILITY COMPANY AND THE LANDLORD'S REQUIREMENTS. CONTRACTOR SHALL PAY ALL FEES AND
LANDLORD CHARGES ASSOCIATED WITH METER AND METER INSTALLATION. (SEE TYPICAL TENANT DRAWING FOR METER
REN IREMENTS) .
D. GAS METER WHERE SERVICE IS AVAILABLE AND IS REQUIRED BY TENANT'S APPROVED DESIGN, INSTALL OR AT MO EXPENSE
, A GAS METER COMPLETE WITH REGULATOR(S), SHUT OFF VALVES, AND ALL OTHER ACCESSORIES PER THE LOCAL
UTILITY COMPANY. LOCATE METER AS DIRECTED BY LANDLORD AND UTILITY COMPANY.
E. CONNECT TO LANDLORD'S SANITARY, VENT (WHERE PROVIDED), AND COLD WATER PIPING AT LANDLORD'S POINT OF SERVICE
CONNECTION. WHERE ADDITIONAL POINT(S) Of SERVICE ARE REQUIRED (AND APPROVED BY LANDLORD) DiPLOY LANDLORD'S
CON'T'RACTOR TO INSTALL THE ADDITIONAL SERVICE CONNECTIONS PER THE SHOPPING CENTER'S STANDARDS AT 14D EXPENSE TO
LANDLORD. '
F. WHERE AN EXISTING FLOOR MUST BE REMOVED FOR INSTALLATION 0? UNDERGROUND PIPINC, SAW CUT THE EXISTING FLOOR AND
REPLACE THE FLOOR PER LANDLORD'S REQUIREMENTS. (SEE DETAILS THIS SHEET) •
C. ALL UNDERGROUND PIPING AND AREAS WHERE FLOOR HAS BEEN REMOVED SHALL BE BACKPILLED WITH CLEAN SAND AND COMPACTED
TO 92% MDDIFIED PROCTOR. WHERE STRUCTURAL SLAB OCCURS, BACKFILL IS NOT REQUIRED.
H. FURNISH AND INSTALL 'AIR CHAMBERS ON EACH HOT AND COLD WATER SUPPLY TO EACH PLUMING FIXTURE.
I. PLUMBING FIXTURES - THE FOLLOWING IS A MINIMUM SPECIFICATION FOR FIXTURES:
I. WATER CLOSET - AMERICAN STANDARD 2109.405 CADET WITH CHROME SUPPLY AND STOP AND OPEN FRONT WHITE SEAT AND
SEAT COVER.
2. LAVATORY - AMERICAN STANDARD 0351.012 LUCERNE 20" X 18" WITH WALL HANGERS, CHROME SUPPLIES AND STOPS, AND
1-1/2" CHROME TRAP WITH CLEANOUT.
3. HOT WATER HEATER - A.O. SMITH - 6 CALLON, 1500 WATTS INSULATED PER ENERGY CODE. T 6 P VALVE SHALL BE PIPED
FULL SIZE AND SAFEWASTED TO A FLOOR DRA ?N. CONTRACTOR SHALL INSTALL A WATTS 36A VACUUM RELIEF VALVE Ohl
COLD WATER FEED LINE TO HEATER. HEATER SHALL HAVE A 5 -YEAR WARRANTY.
4. FLOOR DRAIN - JOSAM 30003 - FOR TILE FLOORS WIT'N A NICKEL, BRONZE OR BRASS FINISH.
5. CENTER SET FAUCET - AMERICAN STANDARD -• 2103.703 CHROME PLATED WITH POP UP WASTE.
C.
III. FIRE SUPPRESSION SYSTEMS
A. TENANT'S SPRINKLER SYSTEM SHALL BE INSTALLED FROM LANDLORD'S SPRINKLER BULK MAIN SERVICE PROVIDED BY LANDLORD
F Ft`THE PREMISES OR, IN THE EVENT A SPRINKLER SYSTEM EXISTS, MODIFY THE EXISTING SYSTEM. IN THE EVENT TENANT
REEOIRES LARGER OR ADDITIONAL SPRINKLER SERVICE, TENANTS CONTRACTOR SHALL EMPLOY LARDLORD'S CONTACTOR TO
INSTALL ADDITIONAL SERVICE OR INCREASED SIZE OF SERVICE(S).
E • FURNISH, INSTALL, EXTEND, OR MODIFY (IF EXISTING) 10 PROVIDE A. SPRINKLER SYSTEM FOR THE EiRTtRE PREMISES TO
INCLUDE ALL PIPING AND ACCESSORIES PER THE REQUIREMENTS OF ALL APPLICABLE CODES, N'FPA -13, LANDMOSD AND
LANDLORD'S FIRE AND CASUALTY INSURER. •
E. ALL !LPINCC SHALL BE DESIGNED AND INSTALLED PER NFPA -13 ORDINARY HAllARD PIPE SCHEDULE, OR, IF A HYDRAULICALLY
DESIGNED SYSTEM IS REQUIRED, CRITERIA FOR SYSTEM DESIGN SHALL BE DENSITY - SALES .15 CPM PER SQ.FT. STOCK
.18 CPM PER SQ.FT. FIRE AREA - MOST REMOTE 2500 SOFT. CLASSIFICATION GROUP II ORDINARY HOARD. OBTAIN FLOW
AND PRESSURE SUPPLIED AT TENANTS CONNECTION FROM LANDLORD.
D. XAXI?'EJM SPACING OF SPRINKLER HEADS SHALL BE 130 SQ.FT. PER HEAD IN SALES AREA AND 100 SQ.FT. PER HEM IN
STORAGE AREAS.
E. SPRINKLER` HEADS IN SALES AREA SHALL BE POLISHED CHROME PENDANT 212 DEGREES RATING WITH ORE (1) PIECE MAXIMUM
DEPTH 3/4" POLISHED CHROME ESCUTCHEONS. SPRINKLER HEADS IN STOCK ROOM SHALL BE PENDANT OR. UPRIGHT, BRASS OR
CHROME, 286 DEGREES RATING. SPRINKLER HEADS IN PO ?-CWT STORE FRONT SHALL BE FLUSH MOUNTED, 212 DECREES RATING
WITH POLISHED CHROME COVER PLATE.
F. CONTRACTOR SHALL OBTAIN FROM LANDLORD T}IE LANDLORD'S FIRE AND CASUALTY INSURERS NAME, ADDRESS, AND PROJECT
INDEX NUMBER. PRIOR TO INSTALLATION, CONTRACTOR SHALL SUBMIT SEVEN (7) SETS Of CALCULATIONS AND SEVEN (7) SETS
OF PRINTS OF SPRINKLER DESIGN TO LANDLORD'S FIRE ARO CASUALTY INSURER FOR APPROVAL. UPON APPROVAL' A1ND SWORE
INSTALLATION, CONTRACTOR SHALL ?REWARD OWE (I) REPRODUCIBLE SEPIA OF THE APPROVED DESIGN AND TWO (2) iSLUE LIRE
PRINTS, WHICH SHALL RAVE THE LANDLORD'S INSURER'S APPROVAL STAMP, TO THE LANDLORD FOR LANDLORD'S APPROVAL AND
RECORDS. CONTRACTOR TO OBTAIN ALL OTHER APPROVALS FROM API'LICASLE AUTHORITIES AND SUBMIT APPROVED PRINTS TO
'..ALORD FOR LANDLORD'S RECORDS.
G. .GODS SHALL INCORPORATE AN APPROVED AUTOMATIC FIRE EXTINGUISHING SYSTEM PER APPLICABLE CODES AND LANDLORD'S
'FIRE AND CASUALTY INSURER. .
H. FURNISH AND INSTALL INSPECTORS TEST CONNECTION, DRAINS, ETC., AS MAY BE REQUIRED BY LANDLORD.
I. REIMBURSE LANDLORD FOR COSTS OF DRAINING AND REFILLING LANDLORD'S SPRINKLER SYSTEM WHERE SAME: IS REQUIRED TO
COMPLETE TENANT'S SPRINKLER SYSTEM.
J. ALL OTHER CODE OR LANDLORD REQUIRED FIRE PREVENTION SYSTEMS MID ACCESSORIES SHALL BE INCORPORATED AS PART OF
THIS SCOPE OF WORK.
K. TENANT'S SPRINKLER PIPING 4" AND LARGER SHALL BE INSTALLED WITH HANGERS AT EVERY SAE JOIST WERE INSTALLED
PERPENDICULAR TO BAR JOISTS AND, WHEN INSTALLED PARALLEL TO JOISTS, WITH RANGERS SUPPORTED PROM TWO 'BAR JOISTS
EVERY 6'0" ON CENTERS. ALL HANGERS AND /OR SUPPORTS SHALL BE INSTALLED WITHIN 6" OF A JOIST PANEL POINT. •
1$
IV.
A. NAIf't RVEC SYS CRIT>LttIA :
I. WW1 LL SICK,,, FURNYSlt LIDO INSTALL A OD)WIZTE NVAc SYSTEN T8 HEAT MID COOL TER ENTIRE E'Rlt1IBES IN
STRICT CONFORHARCE.WITHTHE CR'tTEEIA AJSD: DESCRIPTION CONTAINED HEREINr
2. THE R. HEATL$G AND COOLIHC SYSTRMt DESIGN SHALL BE $ASSO OW T'HHE .APPLICABLE STATE AND .LOCAL CODES) ARiD THE
INFORMATION PROVIDED ON .TIME ATTACITED, CALCUI,ATIO$ FORM, *ICI IS ,DERIVED FROM THE NDS't RECENT DESIGN
CONDITIONS TESTED 1M THE AM+ERICAR .SOCILTTY Or NEATEN°, REFRIGER - ATM; AND AIR.CONDITION NC E110:'1ElRR8
(A.S.N.R.M0 NAPALM
3. MEAT GAIN CALCULATION MULL,SE BASED UPON THE MONTH, DAY AND HOUR OF PEAK SOLAR, :THERMAL AND INTERNAL NEAT '
GAINS USBINC CODE RSQUI*EO *IIDUM OUTSIDE AIR QUANTITIES AT DESIGN CONM3I•TIONS.
4. iEAT LOSS CALCULATIONS SHALL $ EASED UPON THE FULL NEAT LOSS AMP CODE' REQUIRED HININUM OUTSIDE AIR
REQUIREMENTS AT. DESIGN COHfIT.IONS (CREDIT , SNALLNOT BE TAKEN FOR INTERNAL' HEAT GAINS) .
5, THE FOLLOWING SHALL BE APPLICABLE TO THE CALCULATIONS TOR SPECIAL OCCUPANCIES (E.G., BEAUTY SALONS, PET
SHOPS, MASER SHOPS, CANE OM AIIIUSEMENT'FACILITtES, PHD':OFINISHtNG ESTABLISHMENTS, RESTAURANTS, ETC.) :
a) CODE REQUIRED OCCUPANCY LEVEL.
D) CODE REQUIRED OUTSIDIC AIR QUANTITIES.
C ) ALL MEAT Pi10VUCINC GAS OR SIACTSIC AIPPLIANCE LOADS WITH LANDLORD APPROVED DIVERSITY FACTORS.
d) LANDLORD MARE -LIP AIR REQU/REl173NTS,
6. EXCEPT FOR SPECIAL OCCUPANCIES, TENANT'S HVAC SYSTEM SHALL MAINTAIN A SLIGHT POSITIVE PRESSURE DIFFERENTIAL
BETWEEN TEE PREMISES AND TUE ENCLOSED WILE AND COMMON AREAS OF THE SHOPPING CENTER.
7. UNLESS OTHERWISE PERMITTED SE LANDLORD, OUTSIDE AIR, RELIEF AIR, EXHAUST AIR O'R ANY OTHER TYPE OF OPENING
OR GRILLE SHALL NOT SE PERMITTED IN OR ON ANY DEMISING PARTITION, SERVICE CORRIDOR WALL OR EXTERIOR WALL 0?
THE PREMISES OR EXTERIOR WALL Of PRE SHOPPING CENTER.
S. MAC SYSTEM OPERATION
a) IT, ' AT ANY TIME 17URING.TNE TERM OF THE LEASE, LANDLORD DETERMIM TENANT' S. NVAC EQUIPMENT OR STEM IS
NOT OPERATING IN ACCORDANCE NITN MANUFACTURER' S' RECOMMENDATIONS OR LA/MU:MA' S *EQUIRfsIA:NTS, ____ M
MAY, IN AIMITION TO ANT OT1 , U RIMS ARO REMEDIES MAY HAVE, AFTER GIVING FIVE (5) DAYS WETTER NOTICE •
TO ;ERMIT Of ITS INTENTION TO DO SE, CORRECT SUCH OPERATIONAL DE?tCtENCiES AS LANDLORD MAT ELECT TO
PENFOEM FOE AND ON TENAAR T' S 11 EL?. TENANT SMALL REIMBURSE LANDLORD FOR ALL COSTS INCURRED St LiIAI'DLORD
FOR THE CORRECTION Of SANK DIPVICIENCIES PLUS A EIFTMER PERCENT (15x) ADMINISTRATIVE.CHANCE AND THE
TOTAL AMOUNT SHALL SE DUE AND PAY/MILE TO LANDLORD UPOIS DLOMAND.
B. WHERE NVAC UNIT(S) IS TO SE REPLACED OR, WHERE A NEW .INSTALLATION IS REQUIRED, THE HVAC SYSTEM SHALL rs 'A
SPLIT SYSTEM AIR COOLED ROOT _ NDQMITED CONDENSING UNIT AND AM AIR HANDLING UNIT SUSPENDED IN AM ACCESSIBLE
LOCATION WITHIN 'T'HE TENANTS SPACE UTILIZING A DIRECT EXPANSION RErmesRANT 22 EVAPORATOR COIL, SENSIBLE
CAPACITY MUST WT OR EXCEED 'TP E CALCULATED LOAD. EQUIPMENT SHALL SE EQUAL, TO CAR4RER, TRANE, OR YORR.
C. AIR HANDLING UNIT SMALL HEAVY CONSTRUCTED INDIVIDUAL MIXED AIR, FILTER, COIL AND FM SECTIONS
ASSEMBLED IN A. MANNER TG ACCOMODATE REPAIR OR REPLACEMENT OF EACH SECTION-. UNIT ARRANGEMENT SHALL SE OF THE
DRAW THRU TYPE WITH A SW DRIVEN PAN CAPABLE Of EXTENDED FAN PERFORMANCE INL'LUDINC HIGH PRESSURE DUCT
APPLICATION. .
D. CONDENSING UNIT SMALL CONSIST Of A ION FUNGUS CONSTRUCTION CONDENSING COIL, PIERMETIC DESIGN COM 'REST R(B)
WITH EXTERNAL VIBRATION ISOLATOORS, DIRECT DRIVE.. PRO FELLER TYPE CONDENSING FANS AND FUSED DISCONNECT SWITCH PER
NATIONAL ELECTRIC CODE. UNIT CONTROLS SHALL it FACTORY WIRED. SAFETY DEVISES SHALL CONSIST Of HICK MO LCAI
PRESSURE SWITCHES AND COMPRESSOR OVERLOAD DEVISES, LAW OUTDOOR AIR T'EMPERA1'URE HEAD PRESSURE CONTROLLER TIMER
TO PREVENT SHORT CYCLING OF COMPRESSOR AND CRANKCASE HEATER.
E. REFRIGERANT PIPING SHALL WE TYPE "L" COPPER 'FUSING, CLEANED BY TOE MANUFACTURER, ENDS CAPPED. FITTINGS SHALL
BE FORGED OR WROUGHT COPPER VITN SILFMSS S SILVER BRAZED JOINTS. PIPE HANGER DESIGN SHALL PREVENT VIBRATION
FROM BEING TRANSMITTED TO.THE BUILDING STRUCTURE. INSULATE REFRIGERANT PIFOING WITH I" THICK AR/MELEE APPROVED
FOR PLENUM USE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS WITH ALL JOINTS SEALED VAPOR TIGHT. REFRIGERANT
PIPING SHALL Et ROUTED TO TENANTS SPACE BELOW ROOMP "IN CORRIDOR AS DESIGNATED BY LANDLORD.. CONTRACTOR TO •
INSTALL PIPING, ELECTRICAL POWER AND 24 VOLT CONTROL SERVICE TO CONDENSING UNIT IN EXISTING REFRIGERANT CEASE
OR, WREN PERMITTED, AS DETAILED ON THIS DRAWING. SEPARATE ROOF PENETRATION TOR EACH PIPE SMALL NOT BE
PERMITTED. PIPING LAYOUT SMALL ACCONW DATE MDVEMERT PROM PIPE EXPANSION AND BUILDING EXPANSION /EARTHQUAKE
JOINTS.
F. OUTSIDE AIR: CONNECT TO THE OUTSIDE AIR BRANCH DUCT PROVIDED BY LANDLORD AND EXTEND TO THE MIXT* BOX
SECTION OF THE AIR HANDLING UNIT. OUTSIDE AIR QUAtITtTY SHALL BE AT MINIMUM. DETERMINED EY LANDLORD'S CRITERIA,
FEDERAL, STATE, COUNTY OR CITY' CODES OR STANDARDS. OUTSIDE AIR DUCT SHALL BE EXTERNALLY INSULATED WITH FOIL
FACED 1" FIBERGLASS INSULATION. OUTSIDE AIR DAMPER NINON SHALL BE SPRING RETURN TYPE TO CLOSE WHEN HVAC
EQUIPMENT FAN IS OFF.
C. T!'MPONARY WORK PLATFORM (MIN. 4' VIDE) IS REQUIRED CONSISTING OF PLYWOOD COMPLETELY SURROUNDING THE
kCUOFTOP UNIT(SE•AND OTHER EtJIPMERT OR'DUCTS • THR'OUCH THE ROOF. THE ENTIRE WORKING AREA SHALL RMIMAIN OW ROOF
DURING THE ENTIRE PERIOD Of INSTALLATION AHD SHALL BE REMOVED E'ROM THE ROOF AND THE SHOPPING CENTER SITE UPON
COMPLETION OF THE INSTALLATION SY CONTRACTOR.
N. ALL ROaO? MOUNTED FMS, SMOKE RELIEF VENTS, TOILET EX/MUSTERS, AND MISCELLANEOUS EQUtPRRN'T SHALL OE OF
ALUMINUM CONSTRUCTION, WITH mews* ROO? CURBS AS DETAILED ON.THIS DRAWING. ALL SERVICES TO ROOF MOUNTED
EQUIPMENT SMALL BE INSTALLED WITHIN THE CONFINES OF THE EQUIPMENT CURB, EXCEPT CAS PIPING. SEPARATE ROOF
PENETRATIONS FOR UTILITIES TO ROOF MOUNTED EQUIPMENT WILL NOT BE PERMITTED.
1. GOOSENECKS !HALL NOT BE INSTALLED UNLESS SPECIFICALLY APPROVED BY LANDLORD.
J. LABE ALL TENANT ROOF MINTED EQIIP*NT WITH TENANT'S NAME AND UNIT RJMSER WITH A MINIMUM OF 1 - 1/2 60 STENCILED
.1.E RS.
K. FRAME ALL SIDES OF ROOF PENETRATIOHSS IT ONE SIDE OF PENETRATION IS GREATER THAN 12 INCHES WITH 3" X )" 1L 1/4"
ANGLE TO 9UPPORT THE METAL DECK. ANGLES SHALL BE CL.AHPED TO THE STRUCTURAL STEEL JOISTS, B! /AMS, OR GIRDERS AND
SHALL BE INSTALLED TIGHT TO THE BOTTOM OF THAN: • METAL DECK. INSTALLATION SHALL RE AS APPROVED BY THE LANDLORD.
L. FAN
L. EACH TOILET ROOM SHALL NAVE AtIOILET EXHAUST FAN• CONTROLLED BY THE LIGHT SWITCH SIZED PER CODE AND RATED
AT MINIMUM .10" EXTERNAL STATIC PRESSURE. TOILET(S) EXHAUST FANS SMALL BE CEILING MOUNTED WITH INTEGRAL
(MULES, BACKDRAFT DAMPER AND CEILISIG FIRE DAMPER. FAN SHALL BE PENN, FASCO, NUTONE OR OTHER APPROVED.
EXTEND TOILET EXHAUST DUCT TO THE EXTERIOR AS SHOWN ON THE TYPICAL TENANT DRAWING AND DETAILED ON THIS
SHEET.
2 . ALL FANS REQUIRED FOR RELIEP, HAKE -UP AIR OR EXHAUST (EXCEPT TOILET ROOM)'•SNALL BE ROOF MOUNTED MID OF A
CENTRIFUGAL TYPE WITH A BELT OR DIRECT DRIVEN ENCLOSED MOTOR OUTSIDE THE AIR STREAM. CLASS B TYPE MOTORS
SHALL BE USED FOR HIGH TEMPERATURE APPLICATIONS. ALL ROOF MDUNT?D FANS SHALL INCORPORATE COUNTERBALANCED
- EACH DRAFT DAMPERS AND A SERVICE DISCONNECT SWITCH AT THE FAN.
M. ROOF MOUNTED EQUIPMENT PROJECTIONS: NONE OF TENANT'S HVAC EQUIPMENT OR ANY OTHER TENANT ROOF MOUNTED
CONSTRUCTION SHALL BE VISIBLE ABOVE THE EXTERIOR WALL PARAPET, UNLESS OTTHF.RWISE PERMITTED BY LANDLORD. Ii'
PERMITTED,, TENANT SHALL, AT TENANT'S EXPENSE, PAINT ALL SUCH HVAC EQUIPMENT OR ROOF MOUNTED CONSTRUCTION AND /OR
PROVIDE SCREENING FOR SAME AS MAY BE REQUIRED BY LANDLORD. ,
N. ELECTRIC DUCT BEATERS SHALL BE OPEN COIL,,SLIP -IN, ZERO CLEARANCE, U.L. APPROVED HEATERS WITH FUSED
DISCONNECT SWITCH, AUTOMATIC RESET IN THE CONTROL CIRCUIT, KANUAL RESET THERMAL CUT -OUT IN THE POWER CIRCUIT,
24 VOLT HOLDINC COIL(S) FOR EACH STACE AND AN AIR FLOW SWITCH TO PROVE AIR FLOW PRIOR TO HEATER OPERATION.
0. DIFFUSERS 'GRILLES AND REGISTERS SHALL BE STEEL OR ALUMINUM AS HANUFACTURTD BY TITUS, BARBERECOLMIAN, CARNES,
OR OTHER APPROVED WITH OPPOSED BLADE DAMPERS, RETURN AIR BETWEEN STOCK AND SALES AREA SHALL MET RELY UPON ANY
ACCESS WAY BETWEEN STOCK AND SALES AREAS.
P. RETURN GRILLES' OR REGISTERS FOR CEILING PLENUM RETURN SYSTEMS SHALL BE SIZED BASED ON THE LARGER or 'DO rpm
MAXIMUM FACE VELOCITY OIi ONE SQUARE FOOT OF GRILLE. AREA PER 300 SQ.FT. OF GROSS LEASABLE AREA
Q. AIR BALANCE ALL EQUIPMIENT, DIFFUSERS, REGISTERS AND CEILLES TO THE AIR QUANTITIES INDICATED ON THE moms OR OH
THE SCHEDULE.
R. D'UCT'ED. RETURN AIR SYSTEMS SHALL ONLY 'BE INSTALLED WHEN REQUIRED OR APPROVED AY IANDLOAD. MAVEN A DUCTED
RETURN AIR SYSTEM IS REQUIRED (OR PERMITTED)' BY LANDLaORD, CONTRACTOR SHALL FURNISH AND INSTALL RELIEF GRILLES
IN CEILING TO PREVENT FREEZING. RELIEF SHALL SE SIZED AT 1 SQ. 2'T. PER 300 SQ. FT. LEASABLIS AREA.
DUCTED RETURN. AIR SYSTEM GRILLES SHALL SE SIZED FOR A MAXIMUM OF 500 F.P.M.VELOCITT:
S. IF A CONDITION THAT CAUSES CONDENSATE TO FORM ON MY MALL OR TENANT ' SURFACE, EXTERNALLY INSULATE ALL TiESE
SURFACES WITHIN THE PREMISES WITH I" THICK FIIBERGLASS INSULATION WITH AN INTEGRAL VAPOR BARRIER.
T. FLUME CONNECTORS ARE REQUIRED ON ALL DUCTWORK CONNECTIONS TO AIR MDVIllC EQUIPMENT INCLUDING AIR HANDLING
UNIT(S) AND EXHAUST YAWS),
U. f - TUNS AME 'REQUIRED TO !E INITALLA'D IN ALL CEILING DIFFUSERS, CRILLES AND REGISTERS, ANY OPENING IN TEE
PARTITION S*PAR1 ATIOG STOCK AND SALES AREAS MERE TOE OPENING OCCURS BELOW THE LEVEL OF THE SPRINKLER 11310
OR MINER& NO CEILING EXISTS IN TEE STOCK AREA AND PENETRATIONS Of FIRE RATED QDNSTRUCTION PEII COOS. " VIRE
DAMPERS !MALL SE U.L. LISTED AND INSTALISO PER MANUFACTURERS REQUIREMENTS. FIRE DAMPER(S) SHALL SE RIJSKIN, AIR
BALANCE, OR OTHER APPROVED.
V
V. ALI. � R, ►ITTINCa, RANGERS, i►ASRtCATtONS, INSTALLATIONS, MATERIALS AND PREMEDS SHALL BE CAL AiStZEi) SHEET
P4ETAL FABRICATED AND INSTALLED 10 S'1`aCT ACCORDANCE WITH THE 1969 FOURTH EDITION OF SMiACNA ,AND AS DETAILED.
WHERE APPROVED POE INSTALLATION NY THE LANDLORD, FIBERGLASS DUCTWORK SHALL SE 1" JOHNS MAINVILLE. TYPE - BOO - HD}'
FACING INSTALLED PEE THE NAMJ?ACT UEER' S AND SMACNA' S REQUIREMENTS. ALL DUCTWORK SHALL BE INSTALLED AS HIGH AS
POSSIBLE. ALL DUCTWORK AND EQUIPPKT IN PUBLIC AREAS SHALL BE CONCEALED. ROOF *RIOTED DUCTWORK SHALL NET BE
'PERMITTED UNLESS WRITTEN PERMESStOH IS OBTAINED FROM LANDLORD. WERE SAME IS PERMITTED BY i.ANDLORD, ALL SEAMS
SHALL BE SOLDERED AND. ALL DUCT' Wots SHALL BE INSTALLED. SUPPORTEt', AND INSULATED AS REQUIRED SY LANDLORD.
W. FLUES SHALL BE PF.TALBESBTOS TORE OR, IT ORE STEINCENT, AS REQUIRED BY CODE.
E. F X SLS CAICTWORK SHALL ORLY BE PERMITTED TO LSE INSTALLED:POOR FINAL CONNECTIONS TO DIFFUSERS. THE MOLA><IMiUM
LENQ'TE OF FLEXIBLE DUCT SHALL SE LIMITED TO 5' P0* ANY ONE DIFFUSER CONNECTION. FLEXIBLE DUCT MATERIAL
SHALL HAVE A PLAmt SPREAD LESS IRAN 25 AND A SNORE DEVELOPED RATlNC LESS THAN 50.
V. OONT'RACtOE SHALL SEAL. MALL DUCT PENETRATION AT DEMISING WALLS WITH MATERIAL APPROVED BY APPLICABLE CODE
AUTHORITIES.
•
,f
IIII ilI IIIIIIIlIIIIIII
I
No.18 ..'
r
1III1I1
re
I. CONTRODL8 Intuit • MID MISCELLANEOUS RE
. - • - -.- - . s s . r.
i X i. Solf. . L ,, f rt
., .._ v, , • S ,•
IREMRRTS :
•
f. TEMPERATN.M*E TROIA SHALL SE A ;MAXIMUM Of 24 VOLTS. ALL CONTROL WIRING SHALL RE INSTALLED IN S`KRICT
ACCWANGE WITH NATIONAL ELECTRIC CODE,
2. ALL. EXISTING MID NEW wi*IX Ill PLENUM AREAS SHALL BR N /PIED. AND /OR INSTALLED IN CONDUIT OR ;ASIA LISTED
FOR USE IN PLENUl1 AREAS. FIELD VERIFY ALL EXISTING WIRING TO OaURKINE THE EXTENT OF THE REQUIRED
3. CONTROL WIRING POE NVAC CONTROL: SHALL SE MMULTiCOIOREO CABLE.
4. THERMOSTATS FOR TEMPERATURE CONT'EOL SHALL SE OF THE MERCURY TYPE OR OTHER LANDLORD APPROVED, WITH SWITCH
BANE FOR FAN ON..OPF MD SELECTION OW HEATING AND COOLING WITH STAGING AS REQUIRED, MDIFY-•INSTALLAT'ION OT
ALL CONTROL WIRING AS REQUIRED BY LANDLORD FOR PROPER OPERATION OF THE HVAC SYSTEM. . •
S. FURNISH AND INSTALL STARTER FOR : EVAPORATOR FAN.
6. HVAC EQUIPMENT SMALL INCORPORATE A NIGH TEMPERATURE ,_LII:l? DEVICE TO DE-ENERGIZE THE EQUXPMEN? IF THE DEVICE
IS *CYtVATED.
7, ;;ll i;H "AS SU ZLT" DRAWtsCS Of THE TEMPERATURE ' CONTROL SYSTEM INCLUDING ALL CONTROL DIAGRAMS AS SUPPLIED By
TIE EQUIPMENT MANUFACTURER AND ALL FIELD INSTALLED WIRING AND CONTROLS.
AA. WHERE TNN!< TENANT EatIS TO RE - US!t, AND THE LANDLORD HAS APPROVED TEE RE - USE OR RENOVATION Of AP EXISTING 1 RVAC
SYSTEM, REPAIROR REPLACE ALL OR PART OF THE HVAC EQUIPMENT TO ENSURE PROPER AND EFFICIENT OPERATION OF THE
HVAC SYST Ii(S) ENSURES THE NVAC SYSTEM IS CAPABLE OF MAINTAINING THE SPACE TEMPERATURES WITHIN THE LEASED
PREMISES IN AC WITH THE LANDLORD'S, LOCAL, STATE, AND FEDERAL REQUIREMENTS; AND PROVIDE WRITTEN .
CONFIRMATION TO LANDLORD.
BB. TENANT ELECTS NOT TO RE EXISTING EQUIPMENT, COHOUIT, OR PIPING, INCLUDING BUT NOT LIMITED TO ANY ROOF
MTJUNTED 'ISQUIPMEIIT, TENAN SHALL AT TENANT'S EXPENSE REMOVE SUCH PARTS OF THE SYSTEM AND EQUIPMENT NOT BEING
RE-USED INCLUDING CURBS AND UTILITY SERVICES TO !RICH EQUIPMENT. TENANT SHALL PERFORM ALL NECESSARY REPAIRS TO
THE ROOFING SYSTEM ARD /c* ADJACENT CONSTRUCTION IN ACCORDANCE WITH THE LANDLORDS CRITERIA AND DETAILS INDICATED
ON TUNS DRAWING. .
CC . IldAIC t YPNLlR 96'!�A>I'tRiP ME10 I�VAC UNI'T'S
1.PRIOlt TOOPEIMMIVE *Rt11tSES FOR ROSINESS, COWTRAE"TOR iNEALL PROVIDE LANDLORD WITH WRITTEN VERIFICATION
PROM AN AUTNORI>LE REPRESENTATIVE OF TEE INSTALLED *VAC EQUIPMENT MANUFACTURER THAT THE INSTALLED HVAC
EQUIPMENT IS INSTALLED AND OPERATING IN ACCORDANCE VITM THE EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. IN
THE EVENT LANDLORD DETERMINES TINAIIT' S NVAC EQUIPMENT IS NOT OPERATING IN ACCORDANCE WITH THE
MRSUPACTURER' S .RECOMMENDATIONS, CONTRACTOR SHALL, WITHIN ?MIEN (15) DAYS FROM LANDLORD'S WRITTEN NOTICE
AN
TO TENANT OR CONTRACTOR Of SAWS, CO'RUCT SiOCA OPERATIONAL DEFICIENCY.
A
o.o•SMORE DETECTOR TO REPORT TO UNITED LABORATORIES LISTED CENTRAL
STATION MONITOR. CONSULT THE TUKWILA.FIRE PREVENTION BUREAU FOR
A CURRENT LIST OF APPROVED CENTRAL STATION MONITORS.
r •
C `
Dt.CCIVED:
CITY
oFTIIKWILP.
' APR 3 0 3
PORT E CENTTER
•
EEE
EEE
oESE
mechanical details and specifications
structural slab pipe penetration detail
vent pipe thru roof detail
exhauster detail
roof assembly