HomeMy WebLinkAboutPermit M92-0239 - BOEING #2-44M92-0239 BOEING #2.44 BUILDING
7755 EAST MARGINAL WAY SOUTH
HVAC
.
City of ?lcikwili
Community Development / Public Works • 6300 Southcenter Boulevard, Suite 100 • Tukwila, Washington 98188
Permit No: M92 -0239
Type: B -MECH
Category: NRES
Permit Description:
INSTALL AHU
UMC Edition: :1991
Permit Center Authorized Signature
MECHANICAL PERMIT
Address: 7755 EAST MARGINAL WY S
Location:
Parcel #: 000160 -0020
Contractor License No:
TENANT BOEING #2.44
7755 EAST MARGINAL WY S, TUKWILA, WA
OWNER THE BOEING COMPANY
PO BOX 3707 - M/S 1F-09, : SEATTLE = > WA.. 98124
CONTACT BROWNE SID
7755 EAST MARGINAL WY S, SEATTLE, WA 98124
Date
' *' *
********************.** * * * * ** * * ** * * * * * * * * * * * **'A•*
Date
Valuation:
Total Permit Fee:
to as
(206) 431-3670
Status: ISSUED
Issued: 12/23/1992
Expires: 06/21/1993
Phone: 206 655 -9923
45;'000.00
35.00
* * * * * * * ** * * * **itr*. * * * * * * * * * ** * * * * * *** 4******** * * * * * ** * *** * * * * * *, * *' * * * * * **
I hereby certify that I have read'and examined. this permit and know the
same to be true and correct. All provisions of law and ordinances
governing, this work will be complied with, whether specified herein or not
The granting of this permit does not presume to give authority to violate
or cancel: the_provis,ions of any other state. or local laws regulating
construction `or the performance of work. ; I, am authorized to sign for and
obtain this. bu,i l in �erm4t.
Print Name: . aid &€ 4.'44 Title: _` i7'"' enC>,e_b //t/d7,74
This permit shall b'e`come null an.d. vo.id. the work is no:t commenced within
180 days from the date ,of issuance, ar i`.t the work i „s su or
abandoned for a period:oi~ :180 days -;,fro'm, the?'last,.,..in:spection.
PERMIT N0.
CONTACTED
Lek-k ( Reci
DATE READY
DATE NOTIFIED
2nd NOTIFICATION
��rr�� ✓ " (� BY:
`� r� `o!d Q. 1� (snit.)- -'.iL/
BY:
(snit.)
PERMIT EXPIRES
AMOUNT OWING
0 Q
3RD NOTIFICATION
BY:
(snit.)
MECHANICAL. PERMIT
APPLICATIOW TRACKING
PROJECT NAME
1 � aCt5
SITE ADDRES SUITE NO.
'7 Asr Ili ;PAL S,
INSTRUCTIONS TO STAFF
• Contacts with applicants or requests for information should be summarized in writing by staff so that
any time the status of the project may be ascertained.
PLAN CHECK
NUMBER
Mq &- 039
• Plan corrections shall be completed and approved prior to sending on to the next department.
• Any conditions or requirements for the permit shall be noted on the plans or summarized concisely
in the form of a formal letter or memo, which will be attached to the permit.
• Please fill out your section of the tracking chart completely. Where information requested is not
applicable, so note by using "N /A ",
DEPARTMENTAL REVIEW
"X" In box indicates which departments need to review the project.
PARTMIIEN
BUILDING -
itial review
FIRE
FIRE PROTECTION: ( ) Sprinklers Detectors ( ) N/A
FIRE DEPT. LETTER DATED: / / /9Z,_- ` ' INSPECTOR: 4 c . " 2.-
ZONING:
SCREENING REQUIRED? fl Yes (I No
BAR/LAND USE CONDITIONS? Yes
O PLANNING
11
11140U:12R
O OTHER
BUILDING - 22
fi nal raviaw . Z I ((Z
I t NO0g2
ROUTED)
INIT:
1 !(tt q2
INIT:
INIT:
2 tq
INIT:
tEQUIREME[ TS ' OOMN ENT:
CONSULTANT: Date Sent -
Date Approved -
REFERENCE FILE NOS.:
UMC EDITION (year):
REVIEW COMPLETED
SITE ADDRESS SUITE #
'7 7,3-6— - ,, f. �/4 1 ) y 3 ,
VALUE OF CONSTR}J CTION - $
-7' 9s, D9
PROJECT NAME/TENANT
47--.z2 -,; /,
: : DATE : .
— /
.woe= /tip A4 ,e /q-- , a. fr/4
TYPE OF WORK: 0 New /Addition 0 Modifications 0 Repair 0 Other: 7 v48
DESCRIBE WORK TO BE DONE: _
L/IC Ji42C 494/
: .:TYP,E.:,;:.:.....:.::.:. : . :: RATING/Si,ZE _ ,..••::>' ,:" ;; NUMBER .OF:;UNITS.::<;:«::s
ZIP , e/ Zj /
CONTRACTOR //ligru
PLAN CHECK
BUILDING USE (office, warehouse, etc.)
/44/1/2,/,€;/e. T2bei4/ _
NATURE OF BUSINESS:
WILL THERE BE A CHANGE IN USE? (3' l0 0 Yes IF YES, EXPLAIN:
WILL THERE BE STORAGE OR USE OF FLAMMABLE, COMBUSTIBLE OR HAZARDOUS MATERIALS IN THE
BUILDING? 0 No 0 Yes IF YES, EXPLAIN: (/ ,xy el)
",ter �,-- ei57 /_s e_ edi v , i .
PROPERTY OWNER Z i //1/.
(' .
RCPT #
: : DATE : .
PHONE �— 1j 9.2-3
ADDRESS 776
"- iirl
a-//l/ ..
Ge)y ..S
ZIP , e/ Zj /
CONTRACTOR //ligru
PLAN CHECK
PHONE A
ADDRESS 1.M(. -/�
OTHER:::.
ZIP
WA. ST. CONTRACTOR'S LICENSE #
EXP. DATE
DESCRIPTION
AMOUNT::;
RCPT #
: : DATE : .
BASIC: PERMIT; FEE
$15.00
UNIT(S) FEE
PLAN CHECK
OTHER:::.
TOTAL
CITY OF TUKWILA
Department of Community Development - Building
6300 Southcenter Boulevard, Tukwila WA 98188
(206) 431 -3670
PLAN CHECK n � ` ) �
NUMBER c) / 1/
APPLICATION MUST BE FILLED OUT COMPLETELY
[bATAPPLICATION ACCE . .Epc NOV
MECHAI ICAL PERMIT
APPLICATION
Division
Mechanical Fee Worksheet must also be filled out
and attached to this application.
FEES (for staff use only)
EREBY CERT1 ..
UE AND !:CORR
BUILDING OWNER
OR
AUTHORIZED
AGENT
FY THAT t HAVE READ AND EXAMINED; THIS APPLICATION AND.'KNOW;THE;SAME
ACT, AND I AM : AU ; THIS . ORI D TO; APPL Y FOR :PERMIT.
. ,..... ,..: . ,...,.:. ,.:...:.
SIGNATU
PRINT NAME
ADDRESS
77SY"
CONTACT PERSON
DATE
PHONE - �9
CITY /ZIP
PHONE 6n — 99
APPLICATION SUBMITTAL In order to ensure that your application is accepted for plan review, please make sure to fill
out the application completely and follow the plan submittal checklist on the reverse side of this form. A completed
"Mechanical Permit Fee Worksheet" must accompany this permit application. Handouts are available at the Building
counter which provide more detailed information on application and plan submittal requirements. Application and
plans must be complete in order to be accepted for Plan review.
BUILDING OWNER / AUTHORIZED AGENT If the applicant is other than the owner, registered architect/engineer, or
contractor licensed by the State of Washington, a notarized letter from the property owner authorizing the agent
to submit this permit application and obtain the permit will be required as part of this submittal.
VALUATION OF CONSTRUCTION The valuation is for the work covered by this permit and must be filled in by the
applicant. This figure is used for budget reporting purposes only and not to calculate your fees.
EXPIRATION OF PLAN REVIEW Applications for which no permit is issued within 180 days following the date of
application shall expire by limitation. The Building Official may extend the time for action by the applicant for a
period not exceeding 180 days upon written request by the applicant as defined in Section 304(d) of the Uniform
Mechanical Code (current edition). No �pp,�ication shall be extended more than once.
If you have any •,pr I : ; t-vg t our process or plan submittal requirements,
please contacfii "e .artment of Community Development at 431 -3670.
5- 2 DATE APPLICATION EXPIRES
i{
SU MITTAL CHECKLST
MECHANICAL
n Completed mechanical permit application (one for each structure or tenant)
0 Two (2) sets of mechanical plans, which include:
• Floor plan
• System layout
• Elevations (for roof mounted equipment)
• Heat Loss Calculations
n Structural calculations stamped by a Washington State licensed engineer may be
required if structural work is to be done (2 sets)
Note: Hood and duct systems require a building permit for the duct shaft.
�rf n� jf+
** * * * ***k * ***h*** * ***** ***** ** her *h * ***** t• *k ****** * **** ****** 0;*
..:CITY OF TUKWILA, WA TRANSMI;.T:
* ** *h * * * * * * ** * **4 * * * ** * * * ** ** ** * *** *k * *h* k * ** ** *** * * *h * * * **
TRANSMIT •:Number,: 52001453 Amount: 35..00:• 12/23/92 Q5:45
Permit No': M92-0239 :Type: B. -MECH MECHANICAL PERMIT:
Parcel Nn. 0001.60 -002Q •
S its .Address: 7755 EAST MARGINAL WY S
Payment Method: CHECK . Notation: .SID BROWNE.
.********* k*** h****** k***** k * * * * * *k * * * * * **k * * * * * * *h *k **k **
,Arrau,nt Code .: Description
12/23/92'.
it SLB
GENERA 7.00
GENERA 28.00
.TOTAL. . 35,00
CHECKS 35.00
CHANGE • . 0.0.0 ..
6293A000 16 :24
Paid.
000/3.45.8.30 PLAN CHECK - NONRES 7.00,
000/322.1.00 MECHANICAL NONRES 28.00
Total (This Payment): 33.00
CITY OF TUKWILA
Address: 7755 EAST MARGINAL WY S
Tenant: BOEING #2.44
Type: B -MECH
Parcel #: 000160 -0020
Permit No: M92 -0239
Status: ISSUED
Applied: 11/05/1992
Issued: 12/23/1992
*** k***** * ** * * * * * * * ** ** * ** ** * * * *-k * *** k * **•k **
Permit Conditions:
1. No changes will be made to the plans unless approved by the
Architect and the Tukwila Building Division.
2. Electrical permit shall be obained-,through the Washington
State Division of Labor~. at` iij4'.,a,l l electrical
work will be i nspece'd by'
t -that agency x '(24'865
.- 67•)_ .
3. All permits, insp.eo,t;ion records, and approved plans shall be
maintained available at, t'h,e? fob site:,prior °to the start of
any construc,, i b an' These., ;documents arse , to be 4 mainta=ned
available 4 0 .,i�'I fi approval n s }I�grapted
4. Readily. acoessib:le',access to = roof "mounted, equipment is
required, : , ar Y :._:
,
5 Any exp '`d its. 1 a't i ans ba k i t` :� e
r r, ti
� , u c l,gf jria,terial shal1� haV,e �a ,Elena.'\
Spread Rating of�s 25,'�or ies;' i rial shall ';.,be ir.' 1dent�i.
f i cat ip { s�i owi ng the f i re;�
•e and mag gormance rating thereof. `�': .V4 \,.
-
6. All g str*u,ction�.to be:done i'r�,.,con with apl rov;ed'° `�''tt
planiSp ani , na uir'ementsaf the Building Code.�(199.1`
Editigqn)c,as =amended by ''the...,,Wa hingt,on`' State Building Code ` ,ham
Un i'o m Mech'an: ca l Code 4,1991 Ed i t i o;n.)'; and Washingt State
En r g r Code (1.991 E i t i on ):•..� ' j ': of
7. Va l tdi ty of Per '1_t.. The i s'`s¢iian'ce `'pf• a,i;p or appr ova l'i of
plans, specifications ` and` .co�mputat i ons - sha�l: not be c�' n =` "'`
steued to a ; pep mi t.. ��'o ` n a pp ,' , , any vio$lation
' �, an a r f�v a'l�� ✓ o f an }s
of an of the ,,provi "s'i otisr 9f f ��>t h zi s code or of any other"
ord o the .ii'!°r��irs�d.i<c;tsion. ,,No,pe.t it resumin 6o give
� `;r '�pr. g �
aut o � it
y o r v or cancel le'fp ` .is this co"
s h a l e .��v a i d.° r". r 4
r� 1 a s ,_� , � ' i ti ....., ,
1� i " • 4J
Dear Sir:
City of Tukwila
FIRE DEPARTMENT
444 Andover Park East
Tukwila, Washington 98188 -7661
(206) 575 -4404
Fire Department Review
Control #M92 -0239
(512)
John W. Rants, Mayor
November 12, 1992
Re: Boeing Company Building #2 -44 - 7755 East Marginal Way
South
The attached set of building plans have been reviewed by
The Fire Prevention Bureau and are acceptable with the
following concerns:
1. H.V.A.C. units rated at 2,000 cfrn require
auto - shutdown devices. These devices shall be separately
zoned in the alarm panel and local U.L. central station
supervision is required. (City Ordinance #1528)
Remote indicator lights are required on all above
ceiling smoke detectors. (City Ordinance #1528)
All new fire alarm systems or modifications to
existing systems shall have the written approval of
The Tukwila Fire Prevention Bureau. No work shall
commence until a fire department permit has been
obtained. (City Ordinance #1528) (UFC 10,503)
Call the Tukwila Fire Department at 575 -4404 for
approval of any system shut down. Have job site
address, name, and the Tukwila Fire Department Job
Number available to confirm shut down approval. (City
Ordinance #1528)
2. This review limited to speculative tenant space only -
special fire permits may be necessary depending on detailed
description of intended use.
Any nvArinnkAd ha,arriniic rnndifinn anrd /nr v;n104-4nr, .,F 4.k
�1�A City of Tukwila
▪ 1908
" W A NIIII - �' '0t$'in' PA WIWTA Wtt . ' ,il 7Kr 1 ' qY ;. i"' MZAPWW4 , yr
C
FIRE DEPARTMENT
444 Andover Park East
▪ Tukwila, Washington 98188 -7661
(206) 575-4404
Sprinklers:
Fire Alarm:
Hood & Duct:
Halon:
Monitor:
Pre -Fire:
Permits:
�r 7/..P L.,,1143 5 l o
TUKWILA FIRE DEPARTMENT
FINAL APPROVAL FORM
Project Name i f n.)4 (‘r).
Address 775 5 £MG✓S
Y Retain current inspection schedule
Needs shift inspection
X Approved without correction notice
Approved with correction notice issued
Authorized Si¢ nature Date
Gary L. VanDusen, Mayor
112 - a 2 ,
Control No.
Permit No.
Suite ' #,-.2-
FINALAPP.FRM T.F.D. Form F.P. 85
ro ect: t• - t
Type oflns = ton: ^—
Address
' = e • 1= . : .. Gickg
Special Instructions:
Date Wanted:
am. p.m.
Requester: ,...
Phone No.:
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
Approved per applicable codes.
COMMENTS:
Inspector:
4 � AP P it , Ve 0 tch
G .'c
(206) 431 -3670
❑ Corrections required prior to approval.
Date: — r(c,
02-3
PRRMiT NO.
❑ $30.00 REINSPECTION FEE REQUIRED. Prior to reinspection, tee must be paid at
6300 Southcenter Blvd., Suite 100. Call to schedule reinspectlon.
PLAN CHECK NUMBER
TYPE OF REVISION:
CITY OF TUKWILA
6300 SOUTHCEN'I'ER BOULEVARD
TUKWILA, WA 98188
* * REVISION SUBMITTAL * *
DATE ` ��y
PROJECT NAME
ADDRESS 77 6 44~/il/.f4 - L. L3 y S •
CONTACT PERSON 6/..2 /'eet."-WE PHONE
ARCHITECT OR ENGINEER /AL'W
PERMIT NUMBER /I 9a. - 9 (If previously issued)
06/75//). ce)/iti .a.✓
tiL41 - /1 s
GO e4-T/DA/ 49,e O d -AJ * ,e.---ct)
SHEET NUMBER(S) / M -;20 , o / s 5 V .,2 �
"Cloud" or highlight all areas of revisions and date revisions.
SUBMITTED TO: K A/450^1
\ - ° ROV ES
P 1393
Clio OF 'ill ;1 ILI\
MAR 2 6'1396,
PERMIT CENTER
BOEING 2.40
PLANT 2
RETROFIT HEAT TREAT
LEGAL DESCRIPTION
BUILDING CODE NOTES
DRAWING INDEX
COVER SHEET
VICINITY MAP
CONSTRUCTION NOTES
PLAN VIEW
REFERENCE DRAWINGS DUCT WORK MECHANICAL MASTER
EQUIPMENT LIST
GENERAL NOTES
HEAT TREAT SYSTEM
CONSTRUCTION NOTES
DETAILS SECTIONS
DUCT FLANGE
EXISTING ROOF DECK; SEE CTRUCT' DWG.
MUD TO BE . 0 MPAT IBLE WI TH
Y OOF i f' G YSTEM
PAPER ;TO:BE.50f(MIN) ASPHALTIC.
:1 M521
MONORAIL HEADEP
SEE STRUCT' DWCS
LIGHT TO : E RELOCATED
BELOW DUC
EPAtRTMENT '
S C r
NONE 1M521
�� —�• C/L EXHAUST
•
T I (3N
trf y:
AOb>�C} HOOD LOCA
REVISED HRO gf .AEG + �
x y , r .,o• •• y a F v.i....+•+ / i +......, r +.a Y:.- w.p..t�- r!......
saga 7 p...lkr✓ n4+ ::. +.. .''""'. "'`�. -..r r �r
• t
,v 4
• r.
-S.
1�
•t1 -• :l
�! G
.1
:9•7j
J5
- - Y • S
''., `� ?C'•.yy✓?'•� "S #'r. `.`;- 4,i.,. h 'f': :. ?'• `4, r ..'�f. �..�1 rr..
r• ` A . r
. •Kt tar`, y . ' r �1
P/ED DATE SYM
e '
•
t •
REV IS1ON .
rr
.t•
V°
BUS
DUCT
LIGHT
. ACCEPTAB L I TY
THIS DESIGN AND /OR
SPEC! P I CAT ION 'ISAPPROVED
SK <,
I III I III I III J Il' I ' ° I '' I '' I '' I ' '
1111111111111111 ill I 'I' I 'It IIIII1'I' +'!'I'i'III'i 'i'I'i'II1 I I'I'III'I'!'I11 +'
3 4 5 _ 6 7 B
! NOTE: If the microfi document is less clear than this
notice, it is due to the quality of the original document.
0 18 THS INCH 1
3 s 1
C. y
IIIIIiIIIf11 11lIIIII11i1111IIIiII I1 hY 111p.IIIi1111i11
9 1 10 11 M*DEINGERMANY 12
0
O F 6Z ee Lz 9Z 5Z 4 7Z £Z zZ L4 OZ 6L Hl !.l 94 9l 'L CL ZL IL Ol 6 8 L r 9 C
I wo
lllilllln IIIIIIIII Ilil!LlIIIiIII!iill!II!I!Illi Iili!I!IIIIiIi!I,lllllililll , Itl�,lililllll!IIII Iili!ILII IIII� ,� Ul1 �i•II IIII!illl IIIIJIIII IIII!IIIL.�LIiIIlI! I�II�IIIIlII11!I {IL�IIIL�IiI Iill�llll 1 II { �!lillllll�llll illl�liil llll!IIII Ilnllili Illlllln Ililllllil
l
r n
13f�' t{
I I.
TITLE
`. PiRMi C
CONSTRUCT ON
[1›* PLACE HOODS AS LOW AS POSSIBLE BUT LEAVE CLEARANCE
FOR MAINTENANCE. SEE RALPH FEDERSPIEL (655 =3500)
FOR DETAILS.
HEAT TREAT SYSTEM, DUCTS
SECTIONS & DETAILS
BUILDING 2.44
\OYES
1 .
CITY C 1 LKI't r0
{ .. :.• Y « .ins''
HARDENING
FURNACE
2100 DEC F
ANNEALING
FURNACE
1400 DEG F
BC 340846
ANNEALING
FURNACE
1400 DEG F
BAC 311678
COOLING TOWER AT U/9
[_ PIT BELOW
• ' • REVISION .
NOTE; SEE DWG 2.44-1M520 FOR PiPiNG DETAILS
DDED LP REGS; ' Jf19634 • '
TO SAN' SEWER
1-1/4" —
AIR GAP
FROM OVERFLM
OIL
QUENCH
TEMP' CONTROLLER
OIL PUMP
SV-2 CV-2
•
+ES- ARTMENT-
7
1 1/2" (TYP.)
WATER
QUENCH
TO SAN' SEWER
200'F MAX WATER TEMP
1 /4"
.AUBURN , WA. 98002
-:EVERETT , • WA.. 98201
0 :kENT , WA. 98031
0 PORTLAND, 97220
• 0 ,R12014, 98055
EATTLE, .WA, • 98124
ANNEALING
FURNACE
1400 DEC F
BAC 311677
1-1/4" AIR GAP
CHEST
FREEZER
COOLING
TOWER
MAKEUP
SEQUENCE OF CONTROL
THE COOLING SYSTEM SHALL BE
STARTED MANUALLY DURING HEAT TREAT
HOURS OF OPERATION (TURN ON P1).
Jail_ QUENCH:
MANUALLY OPERATE SELECTOR SWITCH TO HCT,
COLD, OR NEUTRAL.
COLD OIL QUENCH; TEMP' COTROLLER TC-1
OPERATES SV-1 TO MAINTAIN 100F + 10°F.
HOT OIL QUENCH; PUMP P2 ON AND SV-2 OPEN.
TEMP' SENSING BULB T-72 OPERATES CV-2 TO MAINTAIN
WATER TEMP AT 200 'F TO MAINTAIN QUENCH
TEMPERATURE OF 190F + 5'F.
SV-1 DEENERGIZED.
NEUTRAL; PUMP P1 CIRCULATES CTWS THRU GAS GEN.
HEAT EXCHANGER AND FURNACE BEARINGS. NO FLOW
THRU OIL QUENCH HT XCHGR, SV-1 IS DEENERGIZED.
laWATER WENCH:
. CV-3 OPERATES TO MAINTAIN A TEMP.
OF 200'F + 5°F. (CAPILLARY)
ACCEPTA131LI TY ..
THIS DES IGN .AND/OR
SPECIF ICAT IS APPROVED
, APPROVED BY - DEPT. )ATE
••••••••••••••••••••••••••
— HWS
eal••■•••■•••••••••/..........■■■••■■•
FST1
1.411MIPMMITV
C 1••••••■■■••••••••■••••■••••■••••••••••■•■••••
CTWS CTWR
••••••••■•■•**■•••••••* G omo•••••••■•••••■•••••*
HWR
STM -------
INSTALL CHEM' FEED SYSTEM
APPROVED ImEcHtiLcAugstEL:
1•••••••••
LEGEND
- AIR ••••■•■••.•■•• •
CONDENSATE
CITY WATER
''!"'"'" •
CONS 1 O\ NOTES
f ' •
,••,v •-; •
. _
COOLING TOWER WATER SUPPLY AND RETORN:
NATURAL GAS
GAS ATMOSPHERE
HEATING WATER SUPPLY AND RETURN ' •
STEAM
VENTILATION DUCTS
CONTROL WIRING OR CAPILLARY.
SIGHT FLOW INDICATOR
CONNECT STEAM LINE
CONNECT CONDENSATE LINE
CONNECT AIR LINE
INSTALL CW LINE W/AIR GAP
NOT USED
CONNECT CLWS AND CLWR LINES
TIE INTO EXISTING GAS LINE
INSTALL CALL VALVE AND CAP LINE
RUN TO SAN' SEWER W/ AIR GAP
CONNECT NATURAL GAS TO GC AND HARDENING FURNACES
CONNECT GA LINE FROM GG TO FURNACE(S)
•
_
CONNECT HWS, HWR, CLWS, & CLWR TO HEAT XCHGR IN Oft *WENCH TANv
•
HEAT TFRE PIPING SC.,1E AT 1c.s.
.
S.ET [ONS D'ETA I LS
••••■•■••ya•■•••••••••••■•••■• A•• •■••,••■•1••■•••••••••••*••••••••••6•••••*
T (TL
BUILDING 2a44
o lockr 10
toNk•\ sq3
nr.cENED
CITY. OF,1U
MAR •2 6 1.9
. ,
7,s,;}
. 7:"
•
5.
DETAIL PLAN
SECTION
GENERAL NOTES
EQUIPMENT
GENERAL NOTES
REFERENCE DRAWINGS
DUCT WORK