HomeMy WebLinkAboutPermit D08-426 - WELLS FARGO - PARTITION WALLS AND DOORWELLS FARGO
6815 S 180 ST
D08 -426
Parcel No.: 3623049095
Address: 6815 S 180 ST TUKW
Suite No:
Tenant:
Name: WELLS FARGO
Address: 6815 S 180 ST , TUKWILA WA
Contact Person:
Name: KATHRYN TAYLOR
Address: 1932 1ST AVE #408 , SEATTLE WA 98104
Phone: 206 -720 -7001
Contractor:
Name: POE CONSTRUCTION
Address: PO BOX 1838 , AUBURN WA 98071 -1838
Phone: 253 833 -2400
Contractor License No: POECOI *247QZ
doc: IBC -10/06
Cityllif Tukwila •
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
Owner:
Name: FIRST INTER BNK- KIRKLAND
Address: WELLS FARGO BANK - 92685 , PO BOX 63931 94163
Phone:
DEVELOPMENT PERMIT
Permit Number: D08 - 426
Issue Date: 10/29/2008
Permit Expires On: 04/27/2009
Value of Construction: $5,000.00 Fees Collected: $239.63
Type of Fire Protection: SPRINKLERS /AFA International Building Code Edition: 2006
Type of Construction: III-B Occupancy per IBC: 0008
DESCRIPTION OF WORK:
NEW PARTITION WALLS, (1) NEW DOOR , 83 SQ FT TO BE CONSTRUCTED IN EXISTING OFFICE SPACE
* *continued on next page **
Expiration Date: 05/01/2009
D08 -426 Printed: 10-29 -2008
Public Works Activities:
Channelization / Striping: N
Curb Cut / Access / Sidewalk / CSS: N
City 4Tukwila •
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http://www.ci.tukwila.wa.us
Permit Number: D08 - 426
Issue Date: 10/29/2008
Permit Expires On: 04/27/2009
Fire Loop Hydrant: N Number: 0 Size (Inches): 0
Flood Control Zone:
Hauling: N Start Time: End Time:
Land Altering: Volumes: Cut 0 c.y. Fill 0 c.y.
Landscape Irrigation:
Moving Oversize Load: Start Time: End Time:
Sanitary Side Sewer:
Sewer Main Extension:
Storm Drainage:
Street Use:
Water Main Extension:
Water Meter:
N
Private: Public:
Profit: N Non - Profit: N
Private: Public:
Permit Center Authorized Signatu
I hereby certify that I have read - d ex- ed this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be comp d th, whether specified herein or not.
The granting of this permit does not • • = ume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction • r perf rmance of w • k. I am autl�prized to sign and obtain this development permit.
Signature: iL I_ .� Date: /
Print Name: A-
I'7 C l fct- r\J F 1�---
Date: P v dcb
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: IBC-10/06 D08 -426 Printed: 10 -29 -2008
Parcel No.: 3623049095
Address: 6815 S 180 ST TUKW
Suite No:
Tenant: WELLS FARGO
1: ** *BUILDING DEPARTMENT CONDITIONS * **
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206-431-3665
Web site: http://www.ci.tukwila.wa.us
PERMIT CONDITIONS
•
Permit Number: D08 - 426
Status: ISSUED
Applied Date: 09/05/2008
Issue Date: 10/29/2008
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431- 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: Partition walls that are tied to the ceiling and all partitions greater than 6 feet in height shall be laterally braced
to the building structure.
6: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
7: Ventilation is required for all new rooms and spaces of new or existing buildings and shall be in conformance with the
International Building Code and the Washington State Ventilation and Indoor Air Quality Code.
8: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206 - 431 - 3670).
9: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
10: ** *FIRE DEPARTMENT CONDITIONS * **
11: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
12: The total number of fire extinguishers required for a light hazard occupancy with Class A fire hazards is calculated at
one extinguisher for each 3,000 sq. ft. of area. The extinguisher(s) should be of the "all purpose" (2A, 10 B:C) dry
chemical type. The travel distance to any extinguisher must be 75' or less. (IFC 906.3) (NFPA 10, 3 -2.1)
13: Portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or
brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation
instructions. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so
that its top is not more than 5 feet (1524 mm) above the floor. Hand -held portable fire extinguishers having a gross
weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the
floor. The clearance between the floor and the bottom of the installed hand -held extinguishers shall not be less than 4
inches (102 mm). (IFC 906.7 and IFC 906.9)
doc: Cond -10/06
D08 -426 Printed: 10 -29 -2008
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206-431-3665
Web site: http: / /www.ci.tukwila.wa.us
•
14: Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot
be completely avoided, means shall be provided to indicate the locations of the extinguishers. (IFC 906.6)
15: Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available
for use. These locations shall be along normal paths of travel, unless the fire code official determines that the
hazard posed indicates the need for placement away from normal paths of travel. (IFC 906.5)
16: Fire extinguishers require monthly and yearly inspections. They must have a tag or label securely attached that
indicates the month and year that the inspection was performed and shall identify the company or person performing the
service. Every six years stored pressure extinguishers shall be emptied and subjected to the applicable recharge
procedures. If the required monthly and yearly inspections of the fire extinguisher(s) are not accomplished or the
inspection tag is not completed, a reputable fire extinguisher service company will be required to conduct these
required surveys. (NFPA 10, 4 -3, 4 -4)
17: Maintain fire extinguisher coverage throughout.
18: Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
(IFC 1008.1.8.3 subsection 2.2)
19: Dead bolts are not allowed on auxiliary exit doors unless the dead bolt is automatically retracted when the door handle
is engaged from inside the tenant space. (IFC Chapter 10)
20: Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the
International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. (IFC
1008.1.8.1)
21: Exit hardware and marking shall meet the requirements of the International Fire Code. (IFC Chapter 10)
22: Maintain sprinkler coverage per N.F.P.A. 13. Addition/relocation of walls, closets or partitions may require relocating
and/or adding sprinkler heads. (IFC 901.4)
23: Sprinklers shall be installed under fixed obstructions over 4 feet (1.2 m) wide such as ducts, decks, open grate
flooring, cutting tables, shelves and overhead doors. (NFPA 13- 8.6.5.3.3)
24: All new sprinkler systems and all modifications to existing sprinkler systems shall have fire department review and
approval of drawings prior to installation or modification. New sprinkler systems and all modifications to sprinkler
systems involving more than 50 heads shall have the written approval of the W.S.R.B., Factory Mutual, Industrial Risk
Insurers Kemper or any other representative designated and/or recognized by the City of Tulcwila, prior to submittal to
the Tukwila Fire Prevention Bureau. No sprinkler work shall commence without approved drawings. (City Ordinance #2050)
25: Maintain automatic fire detector coverage per N.F.P.A. 72. Addition/relocation of walls, closets or partitions may
require relocating and/or adding automatic fire d.etectors.
26: Maintain fire alarm system audible /visual notification. Addition/relocation of walls or partitions may require
relocation and/or addition of audible /visual notification devices. (City Ordinance #2051)
27: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
28: An electrical permit from the City of Tukwila Building Department Permit Center (206- 431 -3670) is required for this
project.
29: All electrical work and equipment shall conform strictly to the standards of the National Electrical Code. (NFPA 70)
doc: Cond -10/06
D08 -426 Printed: 10 -29 -2008
• •
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
30: When walls and ceilings are required to be of fire resistive or noncombustible construction, interior finish materials
shall meet the requirements of International Building Code 803.
31: The maximum flame spread class of finish materials used on interior walls and ceilings shall not exceed that set forth
in Table No. 803.5 of the International Building Code.
32: This review limited to speculative tenant space only - special fire permits may be necessary depending on detailed
description of intended use.
33: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
34: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
35: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: Cond -10/06
* *continued on next page **
D08 -426 Printed: 10 -29 -2008
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating
construction or the performance of work.
Signature:
Print Name:
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
J EP
Date:
doc: Cond -10/06 D08 -426 Printed: 10 -29 -2008
SITE LOCATION
S S �Q King Co Assessor's Tax No.: VP 23 019 Y
Site Address: I
Suite Number: Floor:
Tenant Name: \N FT 4 -1 0 New Tenant: ❑ Yes P!. No
Property Owners Name: W Fl,(--S y P J-9 (7 ,, - TOM
Mailing Address: go( 9 3 I�CVQ. � YGl e (}] ct E 10 f
Zip
CONTACT PERSON - who d
contact
hen your permit is ready to be issued
K.c0 j y. �sct.0 Y Day Telephoner 20(.0 - 5 2/2 700
Mailing Address: l 32 St' At/e # 4O Q Ge_ t✓ LO Y - - ! S 1 O f
`, , /� �y�► �y State Zip
K_� ol 1 V � �'r"Q ' L Fax Number Zap- 7LO - 251
Name:
E -Mail Address:
GENERAL CONTRACTOR INFORMATION —
(Contractor Information for Mechanical (pg 4) for Plumbing and Gas Piping (pg 5))
Company Name:
Mailing Address:
Company Name:
Mailing Address:
Contact Person:
E -Mail Address:
Company Name:
Mailing Address:
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.ci.tukwila.vva.us
Bu Perm No. be . ' l
Plumbing /Gas Permit No.
Public Works Permit No.
riVO OV1
(For office use only)
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
City
State
'Oe GDIOS uC.11013
1 w V'Ule y --0/ S ■c 1e (,) - q8 ID
City State
Day Telephone: 02 S 3 - 29 0 O
k�lea7 potc614, - od io .S-3- Q3 - 1PRO S
Zip
ale
Contact Person:
E -Mail Address:
Contractor Registration Number: ?OE/10L2-1 2, I ' l al 2009
Fax Number:
Expiration Date:
ARCHITECT OF RECORD - All plans must be wet stamped by Architect of Record
0 132- 1 S r- 8 $- ectt't e.
t�l'VI r 4In T � r City
Day Telephone:
0(k-et I ,� I - ,
LC G(� �/ t 9 r -T avekikL ( 'ax Number:
u Dyi. 9 P (0I
State Zip
Zcl - �Lo -7001
2oCo Z_a4 cj
cord
ENGINEER OF RECORD - All plan
must be wet stamped by Engineer of R
V/
Contact Person:
E -Mail Address:
Q:\Applications \Fortes- Applications On Line \3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
cit
Day Telephone:
Fax Number:
Page 1 of 6
State
Zip
BUILDING PERMIT INFORMATION - 206 -431 -3670
Valuation of Project (contractor's bid price): $ ( 000 Existing Building Valuation: $ s i : 5Bk3(CX:20
Scope of Work (please provide detailed information): N FAA) PAIaTIT 0 U\D PcLL5 Cl) VU W
Grp 12 — e a - 6 SF - '['p 1;5E- C 3QS o► tN YtSTl N)(3 o rF1( ---=
SPA .
Will there be new rack storage? ❑ Yes
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes El No If "yes ", explain:
FIRE PRO TECTION /HAZARDOUS MATERIALS:
Sprinklers X Automatic Fire Alarm ❑ None ❑ Other (specify)
Will tl{ere be storage or use of flammable, combustible or hazardous materials in the building? El Yes ❑ No
If `yes', attach list of materials and storage locations on a separate 8-1/2" x 11" paper including quantities and Material Safety Data Sheets.
Provide All Building Areas in Square Footage Below
Q:\Applications \Fortes- Applications On Line \3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
No If yes, a separate permit and plan submittal will be required.
611
SEPTIC SYSTEM
❑ On -site Septic System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
Page 2 of 6
Existing
Interior Remodel
Addition to
Existing
Structure
New
Type of
Construction, per
IBC
Type of
Occupancy per
IBC
1 Floor
( O l
3 0
11B
2 Floor
3r Floor
Floors thru
Basement
Accessory Structure*
Attached Garage
Detached Garage
Attached Carport
Detached Carport
Covered Deck
Uncovered Deck
BUILDING PERMIT INFORMATION - 206 -431 -3670
Valuation of Project (contractor's bid price): $ ( 000 Existing Building Valuation: $ s i : 5Bk3(CX:20
Scope of Work (please provide detailed information): N FAA) PAIaTIT 0 U\D PcLL5 Cl) VU W
Grp 12 — e a - 6 SF - '['p 1;5E- C 3QS o► tN YtSTl N)(3 o rF1( ---=
SPA .
Will there be new rack storage? ❑ Yes
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes El No If "yes ", explain:
FIRE PRO TECTION /HAZARDOUS MATERIALS:
Sprinklers X Automatic Fire Alarm ❑ None ❑ Other (specify)
Will tl{ere be storage or use of flammable, combustible or hazardous materials in the building? El Yes ❑ No
If `yes', attach list of materials and storage locations on a separate 8-1/2" x 11" paper including quantities and Material Safety Data Sheets.
Provide All Building Areas in Square Footage Below
Q:\Applications \Fortes- Applications On Line \3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
No If yes, a separate permit and plan submittal will be required.
611
SEPTIC SYSTEM
❑ On -site Septic System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
Page 2 of 6
PERMIT APPLICATION NOTES — Applicab
e to all per
its in this application
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
Print Name:
Mailing Address:
Building and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
Plumbing Permit
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER I R • UT; !_ I ENT: �
-
Signature: � /Aril , i
_ we -
Date Application Accepted:
491-wi n v► ficu,�(cn-
I�32 I 4- Ave_ -* 4
Q:AApplications \Forms - Applications On Line A3 -2006 - Permit Application.doc
Revised: 9 -2006
hh
Day Telephone:
City
Date: 0 9/
4 —Tw — O/
c 4m °(lb 3
State Zip
Date Application Expires:
Staff Initials:
g_
Page 6 of 6
Parcel No.: 3623049095
Address: 6815 S 180 ST TUKW
Suite No:
Applicant: WELLS FARGO
Receipt No.: R08 -03163
Payee: CRAFT ARCHITECTS
ACCOUNT ITEM LIST:
Description
BUILDING - NONRES
PLAN CHECK - NONRES
STATE BUILDING SURCHARGE
ID
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 3695 239.63
RECEIPT
Initials: WER Payment Date: 09/05/2008 03:41 PM
User ID: 1655 Balance: $0.00
Account Code Current Pmts
000/322.100
000/345.830
000/386.904
142.50
92.63
4.50
Total: $239.63
•
Permit Number: D08 -426
Status: PENDING
Applied Date: 09/05/2008
Issue Date:
Payment Amount: $239.63
7072 N/08 ° <707 TOTAL 239.63
doc: Receiot -06 Printed: 09 -05 -2008
Project:
Project:
� le
Type of Inspection:
/ 7o a F,,., et (
Address:
ill S i4 S/-
Date Called:
Special Instructions:
- . r i „/, ?• 'C> v 4,...
030&70 - 0 J
Date Wanted:
42 — 9
m.
Requester:
Phone No: _
1 -0‘• ---- 5 s - / — /377
INSPECTION NO.
CITY OF TUKYVILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
Approved pet applicable codes. Corrections required prior to approval.
COMMENTS:
INSPECTION RECORD
Retain a copy with permit
Date:
PERMIT NO.
(206)431 -3670
El $60.00 REINSPEC:TION FEE REQUIRED. Prior to inspectiorf, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
(Receipt No.: 'Date:
Project:_ e )
Type ofpectiotl:
v
Address: ' ,.
. JOAtl f &a .s'r
Date Called:
/
/
Special Instructions:
a.3 542 Fr Dr-f e. .e
Stite_.
Date Wanted:
� Z — s
a.m.
Requester:
Phone No:
7.0.5— 5 i t — 397
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431-
N
0
❑ Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
Inspect
a-'
:l
Date: /2 - s
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.: 'Date:
Project:
Type of Inspection:
Ad ess:
1641
n-�
J�
Date Called:
«f
Special Instructions:
Date Wanted:
J 1--/ 2 - ()
` aa.
p.m.
Requester:
Phone No:
7,1)c4 — Sn — X 377
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISIO N
6300 Southcenter Blvd., #100, Tukwila, WA 98188
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
r
60.0 ' EINSPECTION FE � UIRED. Prior to inspection, fee must be
pal . -t 6300 Southcenter Bl , Suite 100. Call to schedule reinspection.
Date: 1/ -2—`)
,
!Date:
PER
T NO.
Complete
Comments:
ACTIVITY NUMBER: D08 -426
PROJECT NAME: WELLS FARGO
SITE ADDRESS: 6815 S 180 ST
X Original Plan Submittal Response to Incomplete Letter #
Documents/routing slip.doc
2 -28-02
• PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
Response to Correction Letter #
DEPARTMENTS: „�p,pg p,,,,� 'ot.
rCf V�� R _
Building ivlsion Fire Prevention
P Words, glior) Structural n
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Incomplete
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES/THURS RO TING:
Please Route Structural Review Required ❑ No further Review Required ❑
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved Approved with Conditions I
Notation:
REVIEWER'S INITIALS:
n
DATE: 09 -05 -08
Revision # After Permit Issued
DUE DATE: 09-09-08
DUE DATE: 10-07-08
Not Approved (attach comments) ❑
DATE:
JP- q -q -ob
Planning Division
Permit Coordinator
Not Applicable
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
u
Bond
Bond
Company
Name
Bond
Account
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Bond
Amount
Received
Date
4
SAFECO
INS CO OF
AMERICA
5698019
05/01/2002
Until
Cancelled
03/12/2003
$12,000.00
03/05/2002
3
SAFECO
INS CO
5698019
05/01/1998
05/01/2002
01/16/2006
REIFSCHNEIDER, CAROL M
$6,000.00
01/01/1980
2
SAFECO
INS CO OF
AMERICA
5698019
05/01/1992
05/01/1998
POE, FRED W
$6,000.00
01/01/1980
1
AMERICAN
INS CO
SLR6355162
11 /09/1981
05/01/1992
$4,000.00
Name
Role
Effective Date
Expiration Date
POE, CHARLES E
PRESIDENT
03/01/1996
PETERSON, ALAN D
SECRETARY
04 /25/2000
FRY, KYLE R
TREASURER
03/12/2003
WILLIAMS, WAYNE W
VICE PRESIDENT
03/01/1996
CLARK, DENNIS M
CHIEF OPERATING OFFICER
07/09/2003
01/16/2006
REIFSCHNEIDER, CAROL M
SECRETARY
01/01/1980
07/09/2003
WELFRINGER, SUZANNEM
TREASURER
11/09/1976
07/09/2003
POE, FRED W
01/01/1980
01/01/1980
Untitled Page
General /Specialty Contractor
A business registered as a construction contractor with L£tI to perform construction work
within the scope of its specialty. A General or Specialty construction Contractor must
maintain a surety bond or assignment of account and carry general liability insurance.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent
Company
Bond Information
POE CONSTRUCTION
INC
2538332400
PO BOX 1838
AUBURN
WA
980711838
KING
CORPORATION
Business Owner Information
•
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Previous License
Next License
Associated
License
Specialty 1
Specialty 2
171004362
•
ACTIVE
POECOI *247QZ
CONSTRUCTION
CONTRACTOR
11/9/1976
5/1/2009
GENERAL
UNUSED
https: // fortress .wa.gov /lni/bbip/Detail. aspx ?License= POECOI *247QZ
Page 1 of 3
10/29/2008
FA
FBO
FCIC
V
0
J
L
rt
AB
AC
A/C
ACP
ACT
ADH
ADJ
ADJT
AF
AFF
AL
ALT
AP
APPROX
ARCH
ASPH
BD
BETW
BLDG
BLK
BLDG
BM
BRG
BOT
BSMT
BUR
CAB
CB
CBU
CEM
CER
CFM
CFT
CG
CHBD
CI
CJT
CLF
C LG
CJ
CLK
CLO
CLR
CM U
CNTR
CO
COL
CONC
CONSTR
CONT
CORR
CPT
CT
CTR
CY
DBL
DEPT
D ET
DF
DIA
D TAG
DIM
DISP
DN
DR
DWR
DS
DW
DWG
E
EA
EB
EJ
EL
ELEC
ELEV
EM
EMER
ENCL
EP
EWC
EPX
EQ
EQPT
EST
EX
EXIST
EXT
FCTY
FD
FDN
FE
FEC
FIN
ABBREVIATIONS
ANGLE
CENTER LINE
DIAMETER OR ROUND
NUMBER OR POUND
PENNY
PERPENDICULAR
PLATE
ANCHOR BOLT
ACOUSTICAL OR
AIR CONDITIONING
ACOUSTICAL PANEL
ACOUSTICAL TILE
ADHESIVE
ADJACENT
ADJUSTABLE
ACCESS FLOOR
ABOVE FINISH FLOOR
ALUMINUM
ALTERNATE
ACCESS PANEL
APPROXIMATE
ARCHITECTURAL
ASPHALT
BOARD
BETWEEN
BUILDING
BLOCK
BUILDING
BEAM
BEARING
BOTTOM
BASEMENT
BUILT UP ROOF
CABINET
CATCH BASIN
CEMENTITIOUS BACKER UNIT
CEMENT
CERAMIC
CUBIC FEET PER MINUTE
CONDUCTIVE FLOOR TILE
CORNER GUARD
CHALK BOARD
CAST IRON
CONTROL JOINT
CHAIN LINK FENCE
CEILING
CONSTRUCTION JOINT
CAULKING
CLOSET
CLEAR
CONCRETE MASONRY UNIT
COUNTER
CLEANOUT
COLUMN
CONCRETE
CONSTRUCTION
CONTINUOUS
CORRIDOR
CARPET
CERAMIC TILE
CENTER
CUBIC YARD
DOUBLE
DEPARTMENT
DETAIL
DRINKING FOUNTAIN(W /0 COOLER)
DIAMETER
DIAGONAL
DIMENSION
DISPENSER
DOWN
DOOR OR DRAIN
DRAWER
DOWNSPOUT
DISHWASHER
DRAWING
EAST
EACH
EXPANSION BOLT
EXPANSION JOINT
ELEVATION
ELECTRIC
ELEVATOR
ENTRY MAT
EMERGENCY
ENCLOSURE OR ENCLOSED
ELECTRICAL PANEL
ELECTRIC WATER COOLER
EPDXY
EQUAL
EQUIPMENT
ESTIMATE
EXPANSION
EXISTING
EXTERIOR
FIRE ALARM
FURNISHED BY OTHERS
FURNISHED BY CONTRACTOR
INSTALLED BY CONTRACTOR
FACTORY
FLOOR DRAIN
FOUNDATION
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISH
FL
FLG
FLUOR
FM
FOC
FOF
FOI C
F010
FOS
FS
FT
FTG
FTC
FTIO
FURR
FUT
FUTURE -
RIO
FX FIXED
GA
GALV
GB
GL
GLBM
GEN CONTR
GND
GR
GWB
HB
HC
HDR
HDWD
HDWE
HM
HORIZ
HR
HT
HTG
HVAC
HWH
ID
IG
IHM
IN
INCL
INSUL
INT
JAN
JT
KIT
KO
KS
LAM
LAV
LB
LF
LG
LH
LKR
LT
MACH
MAIL
MAX
MECH
MET OR
MEZZ
MFR
MH
MIN
MIR
MISC
MLD
MRGWB
MTD
MULL
NIC
NOM
NTS
OA
OC
OD
OFF
OH
OPH
OPNG
OPP
PERP
PFN
PL
P LAM
PLYWD
PNL
PNT
PR
FLOOR
FLASHING
FLUORESCENT
FACTORY MUTUAL
FACE OF CONCRETE
FACE OF FINISH
FURNISH BY OWNER
INSTALL BY CONTRACTOR
FURNISH BY OWNER
INSTALL BY OWNER
FACE OF STUD
FULL SIZE
FEET
FOOTING
FURNISHED BY TENANT
INSTALLED BY CONTRACTOR
FURNISHED BY TENANT
INSTALLED BY OWNER
FURRING
FUTURE
FUTURE ROUGH IN ONLY
GAGE
GALVANIZED
GRAB BAR
GLASS OR GLAZING
GLU -LAM BEAN
GENERAL CONTRACTOR
GROUND
GRADE
GYPSUM WALL BOARD
HOSE BIB
HOLLOW CORE OR HANDICAP
HEADER
HARDWOOD
HARDWARE
HOLLOW METAL
HORIZONTAL
HOUR
HEIGHT
HEATING
H EATING /VENTI LIATIO N/
AIR CONDITIONING
HOT WATER HEATER
INSIDE DIAMETER/
DIMENSION
INSULATED GLAZING
INSULATED HOLLOW METAL
INCH
INCLUDE
INSULATION
INTERIOR
JANITOR
JOINT
KITCHEN
KNOCK OUT
KNEE SPACE
LAMINATE
LAVATORY
LAG BOLT
LINEAL FOOT
LENGTH
LEFT HAND
LOCKER
LIGHT
MACHINE
MATERIAL
MAXIMUM
MECHANICAL
MTL METAL
MEZZANINE
MANUFACTURER
MANHOLE
MINIMUM
MIRROR
MISCELLANEOUS
MOLDING
MOISTURE RESISTANT GYP BD
MOUNTED
MULLION
NORTH
NOT IN CONTRACT
NUMBER
NOMINAL
NOT TO SCALE
OVERALL
ON CENTER
OUTSIDE DIAMETER/
DIMENSION
OFFICE
OVERHEAD
OPPOSITE HAND
OPENING
OPPOSITE
PERPENDICULAR
PREFINISHED
PLATE OR PROPERTY LINE
PLASTIC LAMINATE
PLYWOOD
PANEL
PAINT
PAIR
PS
PSF
PSI
PT
PTD
PTD /R
PTN
PTR
PVMT
R
RA
RAD
RB
R &S
RD
RD /0
REBAR
REF
REFR
REINF
REQ'D
REV
RH
RESIL
RM
RO
RT
RUB
RVS
RW
RWL
PAINT SYSTEM
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
PRESSURE TREATED
PAPER TOWEL DISPENSER
PAPER TOWEL DISPENSER
AND RECEPTABLE
PARTITION
PAPER TOWEL RECEPTABLE
PAVEMENT
QT QUARRY TILE
RISER
RETURN AIR
RADIUS
RESILIENT BASE
ROD & SHELF
ROOF DRAIN
ROOF DRAIN OVERFLOW
REINFORCING BAR
REFERENCE
REFRIGERATOR
REINFORCED
REQUIRED
REVISION
RIGHT HAND OR ROBE HOOK
RESILIENT
ROOM
ROUGH OPENING
RESILIENT TILE
RUBBER
REVERSE
RAIN WATER
RAIN WATER LEADER
S SOUTH
SC SOLID CORE
SCD SEAT COVER DISPENSER
SCHD SCHEDULE
SD SOAP DISPENSER OR
SECT SECTION
SF SQUARE FEET
SHTG SHEATHING
SIM SIMILIAR
SK SINK
SLR SEALER
SND SANITARY NAPKIN
DISPENSER
SNR SANITARY NAPKIN
RECEPTACLE
SNT SEALANT
SPEC SPECIFICATION
SQ SQUARE
SST STAINLESS STEEL
SSK SERVICE SINK
ST STONE /STONE TILE
STA STATION
STC SOUND TRANSMISSION
CLASS
STD STANDARD
STL STEEL
STOR STORAGE
STRL STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
SYM SYMMETRICAL
T TREAD
TB TOWEL BAR
T &B TOP & BOTTOM
TG TEMPERED GLASS
THK THICK
THR THRESHOLD
TIG TEMPERED INSULATED
GLAZING
TO TOP OF
TOC TOP OF CONCRETE
TOP TOP OF PAVEMENT
TOS TOP OF STEEL
TOSL TOP OF SLAB
TOW TOP OF WALL
TPD TOILET PAPER DISPENSER
TPH TOILET PAPER HOLDER
TPTN TOILET PARTITION
TS TUBULAR STEEL
TV TELEVISION
TYP TYPICAL
UL UNDERWRITERS LABORATORY
UNF UNFINISHED
UON UNLESS OTHERWISE NOTED
UR URINAL
VAR VARIES
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIN VINYL
VWC VINYL WALL COVERING
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WF WIDE FLANGE
WG WIRE GLASS
WP WATER PROOF
WR WATER RESISTANT
WSCT WAINSCOT
WT WEIGHT
XFMR TRANSFORMER
YD YARD
11
REVISION
CLOUD AROUND REVISION
SYMBOLS
COLUMN LINE /GRID LINE
DOOR NUMBER TO COORESPOND
TO ROOM ENTERING
KEY NOTE
PARTITION TYPE
MATCH LINE
SHADED PORTION IS THE SIDE
CONSIDERED
WORK POINT, CONTROL POINT
OR DATUM POINT
EQUIPMENT NUMBER
GENERAL NOTES
BUILDING SECTION (IDENTIFY ON PLAN)
SECTION IDENTIFICATION
SHEET WHERE SECTION IS DRAWN
SECTION IDENTIFICATION
SHEET WHERE SECTION IS DRAWN
WALL SECTION (IDENTIFY ON ELEVATIONS)
DETAIL
DETAIL IDENTIFICATION
SHEET WIIERE DETAIL IS DRAWN
9 , -0 "
OFFICE
102
68.5
„
INTERIOR ELEVATION(S)
ELEVATION IDENTIFICATION
SHEET WHERE ELEVATION IS
DRAWN
ROOM IDENTIFICATION
ROOM NAME
ROOM NO.
ROOM FINISH GRADE
EXISTING GRADE
PROPERTY LINE
NEW OR FINISHED CONTOURS
EXISTING CONTOURS
TOP OF WALL
TOP OF CURB
TOP OF PAVEMENT
ACTUAL NORTH
DENOTES CHANGE IN
E LEVATION
1. THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS ON THE JOB SITE, INCLUDING THE SAFETY OF
ALL PERSONS, PROPERTY, AND FOR ALL NECESSARY INDEPENDENT ENGINEERING REVIEWS OF THESE CONDITIONS, AND FOR COMPLIANCE
WITH O.S.H.A. SAFETY STANDARDS. ARCHITECTS AND THEIR CONSULTANTS' JOB SITE OBSERVATIONS ARE NOT INTENDED TO INCLUDE
REVIEW OF THE ADEQUACY OF THE CONTRACTOR'S SAFETY MEASURES.
2. EACH CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH ALL SPECIFIED PRODUCTS RELATING TO THEIR WORK. THEY ARE TO SUBMIT WRITTEN
OBJECTIONS PRIOR TO BIDDING, IF THE CONTRACTOR HAS AN OBJECTION TO ANY PRODUCT AND /OR DISCREPANCIES BETWEEN DRAWINGS
AND SPECIFICATIONS.
3. THE GENERAL CONTRACTOR SHALL COORDINATE THEIR WORK WITH THAT OF OTHER SEPARATE CONTRACTS SUCH AS SIGNS, & OWNER FURNISHED
ITEMS, WHICH ARE BEING DONE BY OTHERS.
4. THE GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD. THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ANY
DISCREPANCIES BETWEEN ACTUAL FIELD CONDITIONS AND CONSTRUCTION DOCUMENTS. ALL WORK IN THAT AREA SHALL BE HELD UNTIL SUCH
DISCREPANCIES ARE RESOLVED.
5. THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION, A.I.A. DOCUMENT A201, THE LATEST EDITION, SHALL BE INSPECTED AT
THE ARCHITECTS OFFICE.
6. SEPARATE PERMITS, WHEN REQUIRED AND /OR WHEN WORK ITEMS ARE DESIGN /BUILD IN NATURE, SHALL BE OBTAINED BY THE CONTRACTOR FOR
MECHANICAL, PLUMBING, FIRE SPRINKLERS,ELECTRICAL AND FIRE ALARM. DESCRIPTIVE, DETAILED DESIGN AND REQUIRED SUBMITTAL
DOCUMENTS INFORMATION SHALL BE PROVIDED FOR REVIEW BY THE REGULATING AUTHORITIES AND BY THE OWNER /TENANT /ARCHITECT FOR
APPROVAL PRIOR TO ANY WORK BEING PERFORMED. SEE SPECIFICATIONS FOR REQUIREMENT FOR DESIGN /BUILD FRE
SPRINKLER SYSTEM. SUBMIT PLAN TO AND OBTAIN PERMIT FROM THE FIRE PREVENTION BUREAU FOR FIRE SPRINKLER SYSTEM INSTALLATION OR MODIFICATION.
7. COMPLETE FIRE SPRINKLER DRAWINGS WILL BE SUBMITTED BY THE FIRE PROTECTION CONTRACTOR.
8. THE INSTALLATION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SHALL COMPLY WITH THE INTERNATIONAL BUILDING CODE
9. SPECIAL INSPECTIONS WHERE REQUIRED BY THE BUILDING OFFICIAL SHALL BE PERFORMED BY INSPECTORS APPROVED BY THE BUILDING OFFICIAL.
10. ALL WORK DONE SHALL BE IN CONFORMANCE WITH THE APPROVED PLANS AND PROJECT SPECIFICATIONS.
THE APPROVED, PERMITTED, STAMPED PLANS ARE TO REMAIN ON SITE AT ALL TIMES.
11. DIMENSIONS ARE TO FACE OF STUD, CONCRETE, OR MASONRY UNLESS OTHERWISE NOTED.
12. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN.
13. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK, DETAILS SHALL BE THE SAME AS FOR OTHER SIMILAR
WORK. IF QUESTIONS CAN NOT BE RESOLVED IN THIS MANNER, CONTACT THE ARCHITECT PRIOR TO PROCEEDING.
14. GENERAL CONTRACTOR SHALL PROVIDE OWNER WITH DETAILED CRITICAL PATH SCHEDULE FOR REVIEW AND APPROVAL PRIOR TO
START OF CONSTRUCTION. UPDATES OF SCHEDULE SHALL BE MADE AS NECESSARY WITH COPIES PROVIDED TO OWNER.
15. ALL WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE WITH THE LATEST RULES AND REGULATIONS OF THE INTERNATIONAL BUILDING CODE,
NATIONAL ELECTRICAL CODE AND ALL OTHER APPLICABLE STATE OR LOCAL LAWS AND REGULATIONS. NOTHING IN THESE DRAWINGS IS TO BE
CONSTRUED AS TO PERMIT WORK WHICH IS NOT CONFORMING TO THE PREVIOUS LISTED CODES.
16. PROTECTIVE MEASURES SHALL BE TAKEN BY THE CONSTRACTOR TO PROTECT ADJACENT PROPERTY AT ALL TIMES DURING CONSTRUCTION.
17. THE CONTRACTOR SHALL COMPLY WITH ALL CURRENT APPLICABLE LOCAL ORDINANCES FOR UTILITY SERVICES.
18. LIGHT AND VENTILATION SHALL COMPLY WITH I.B.C., SECTION 1203, 1204 & 1205.
19. FIRE BLOCKING SHALL BE PROVIDED AT ALL FRAMED WALLS AT 10' -0" 0.c. AND ALSO AT ANY LOCATION WHERE
WALL FRAMING PENETRATES CEILINGS. REFER TO IBC SEC. 708 FIRE BLOCKING AND DRAFT STOPS FOR CONSTRUCTION.
20. ALL WATER FIXTURES MUST COMPLY WITH WAC 51 -26 -180 WATER CONSERVATION AND /OR ANY JURISDICTION'S PERFORMANCE STANDARDS.
21. WHEN CHANGES TO THE MECHANICAL SYSTEM REQUIRE A MECHANICAL PERMIT THEY SHALL COMPLY WITH THE MOST CURRENT
UNIFORM MECHANICAL CODE AND WITH ANY LOCAL JURISDICTION REQUIREMENTS.
22. PROVIDE ILLUMINATED EXIT SIGNAGE AT ALL REQUIRED EXITS.
23. PATCH AND REPAIR ALL EXISTING WALLS FLOORS AND CEILINGS THAT ARE ADJACENT TO AND AFFECTED BY NEW CONSTRUCTION.
24. CONTRACTOR IS TO COMPLY WITH CHAPTER 33 OF THE INTERNATIONAL BUILDING CODE CONCERNING PROTECTION OF PEDESTRIANS DURING CONSTRUCTION.
25. PRIOR TO FINAL INSPECTION, A CERTIFICATE OF CONSTRUCTION COMPLIANCE SHALL BE READY FOR THE INSPECTOR. THE CERTIFICATE SHALL
STATE "BASED UPON PERSONAL KNOWLEDGE, THAT THE WORK APPEARS TO HAVE BEEN PERFORMED, AND THE MATERIALS USED AND INSTALLED
APPEAR IN EVERY MATERIAL RESPECT IN COMPLIANCE WITH THE PLANS ". THE CERTIFICATE MUST BE SIGNED BY ONE OR MORE OF THE FOLLOWING:
(A) OWNER, (B) GENERAL CONTRACTOR, (C) AN APPROVED INDEPENDENT INSPECTOR OR INSPECTION AGENCY.
26. ASBESTOS AND HAZARDOUS WASTE EXCLUSION:
THE ARCHITECT HEREBY STATES, AND THE OWNER ACKNOWLEDGES, THAT THE ARCHITECT HAS NO PROFESSIONAL LIABILITY OR OTHER INSURANCE,
(AND IS UNABLE TO REASONABLY OBTAIN SUCH INSURANCE FOR CLAIMS ARISING OUT OF THE PERFORMANCE OF OR THE FAILURE TO PERFORM
PR OAFE S SIONAL S I NC L D ING BUT NOT BUT TO, HE PREPARATION OF REPORTS, DESIGNS, DRAWINGS, AND SPECIFICATIONS, AND
PROJECT DIRECTORY
ARCHITECT /CONTACT: CRAFT ARCHITECTS, PLLC.
1932 FIRST AVENUE, STE. 408
SEATTLE, WASHINGTON 98101
ARCHITECT OF RECORD:
TENANT /OWNER:
GENERAL CONTRACTOR:
TAX PARCEL #
3623049095
ZONING DISTRICT:
CODE EDITION:
CONSTRUCTION
EXISTING OCCUPANCY CLASSIFICATION:
TYPE OF CONSTRUCTION:
SPRINKLER SYSTEM:
ACTUAL FLOOR AREAS:
1ST FLOOR: OFFICE (B - EXISTING)
NEW SERVER ROOM (WITHIN EXISTING OFFICE)
TOTAL ACTUAL FLOOR AREA:
OCCUPANT LOAD:
(SEC. 1004.1 TABLE 10 A)
1ST FLOOR: OFFICE
TOTAL OCCUPANCY LOAD
ELECTRICAL, MECHANICAL
KATHRYN M. CRAFT
WELLS FARGO BANK
999 THIRD AVENUE
SEATTLE, WA 98104
LEGAL DESCRIPTION
POE CONSTRUCTION
1519 W VALLEY HW. STE 103
KENT, WA
PROJECT DESCRIPTION
EXISTING PARKING
LOT
PORS OF GL 4 & OF GL 1 IN SEC 35 LY S OF 1s LN EXTND DAF
BEG AT NW COR OF SEC 36 TH S ALG W LN THOF 1355.89 FT TO
TPOB & S MGN OF S 180TH ST TH ELY ON CRV LFT CTR BRG N
02 -45 -45 E RAD 336 FT C/A 01 -32 -04 A DIST OF 9 FT TO S LN
OF N 36 FT OF SD GL 4 TH S 88 -46 -19 E ALG SD S LN 274.81
FT TH ON CRV RGT RAD 50 FT C/A 90 -00 -00 A DIST OF 78.54 FT
TH S 01 -13 -41 W 58 FT TH N 88 -46 -19 W TO SWLY LN OF GL 1
IN SEC 35 TH NWLY ALG SD SWLY LN TO WLY EXT OF N LN OF SD
GL 4 TH S 88 -46 -19 E ALG SD WLY EXT TAP 142.38 FT W OFNW
COR SD GL 4 TH ON CRV LFT CTR BRG N 27 -59 -36 E RAD 336
FT 147.96 FT TO TPOB
TUKWILA URBAN CENTER (TUC)
2006 IBC
TENANT IMPROVEMENT
OFFICE - (B
STORAGE - S -2)
IIIB
YES SPRINKLERS, YES FIRE ALARM
20,197 SQ FT
83 SQ FT
20,197 SQ FT
20,197 SQ FT / 100 = 202
20,197 SQ FT = 202
EXIT REQUIREMENTS:
(SEC. 1019 TABLE 1019.1) NUMBER REQ'D NUMBER PROVIDED ACCESSIBLE PROVIDED
1ST FLOOR: OFFICE 2 2 1
SEPARATE PERMIT SUBMITTALS
NEW PARTITION WALLS AND NEW DOOR TO BE CONSTRUCTED IN EXISTING OFFICE BUILDING.
Contact: KATHRYN TAYLOR
Phone: (206) 720 -7001
Fax: (206) 720 -2949
Contact: TOM DAWES
Phone: (206) 292 -3181
Fax: (206) 292 -3475
Contact: KYLE FRY
Phone: (253) 833 -2400
Fax: (253) 939 -4805
SITE PLAN
NTS
EXISTING OFFICE BUILDING
AREA OF WORK
PROJECT INFO
WELLS FARGO
OFFICE BUILDING
18035 SPERRY DRIVE
TUKWILA, WA 98188
INDEX OF DRAWINGS
T1.1 GENERAL INFORMATION
A2.1 FLOOR PLAN, REFLECTED CEILING PLAN
WALL TYPES,D ETAI LS
PARKING REQUIRMENTS
SCOPE OF WORK WILL NOT AFFECT PLUMBING FIXTURE
REQUIREMENTS
By.
Date:.,../ v
F, tai i n�IS .
No changes shall be made to the
hal core
of work without prior approval
Building Division.
i NO`T`E: Revisions will require a new plan subm "1 +al
and may include additional plan rev fees.
DosLIz b
E PER, iI
I REQUIRED FOR:
L iVIF)chanical
LLElectrical
Plumbin
Gas Piping
RMATION City of Tukwila DIVISION
SCOPE OF WORK WILL NOT AFFECT PARKING REQUIREMENTS
PLUMBING FIXTURE REQ'S
City of Tul calla
BUILDING MOON
CO
E VI C E 0 v
COMPLIANCE E CONSULTANT
APPROVED
SEP 16 . 2008
City Of Tukwila
BUILDING DIVISION
Plar review approval is subject to errors and omissions.
Approval of construction documents does not authorize
the violation of any adopted code or ordinanco. Receipt
of approved Feld opy conditions is acknowledged;
RECEIVED
SEP 0520
PERMIT CENTER
Terminal Sales Building.
1932 First Avenue
Suite 408
Seattle, WA 98101
206.720.7001 phone
206,720.2949 Fax
www, c ra fta rch itects, co m
REGISTERED
ARCHITECT
KATH CRAFT
STATE OF WA
ISSUE
7052
09 -05 -08 FOR PERMIT
Revisions:
Sheet Title:
Date:
Design:
Drawn:
Project No:
Approved:
Sheet No:
Architect of Record
z
Q W
M II co
(3O>
a:
Q W�
_J co
W r
GENERAL INFORMATION
09/03/08
KMC
KLT
08- 161.06
KMR
Original drawing is 24" x 36 ".
Scale entities accordingly if reduced
COPYRIGHT CRAFTARCHITECTS 2008
T1.1
DOOR /RECITE TYPE
c,
LOCK -BOX SPACE
(SHADED AREA)
3' -0"
F (FLUSH)
DOOR TO MATCH EXISTING
OFFICE
SINGLE DOORSCOPE,
ASB PLASTIC,
CHARCOAL, BY G.C.
y CENTER IN DOOR
FRAME TYPE
1
FRAME TO MATCH EXISTING
3/4" , STUDS, OR WIRE @ 6' -0"
O.C. MAX. SECURE TO STRUCTURE
ABOVE & FLATTEN TO ATTACH TO
STUDS PER MFR'S RECOMMENDATIONS
& TO MEET UBC SEISMIC
REQUIREMENTS
ItmnunMUIREunmf mllfnnnnlll1nmtiDMmm111n1mff1nf
EXISTING ACP CEILING
5/8" GWB, - OVER 3 -5/8 "X20 GA.
MTL. STUDS @ 16" O.C. W/ SOUND
BATTS.
SERVER ROOM
INTERIOR PARTITION
MTL STUD RUNNER ATTACHED TO EXST.
CONC. SLAB W/ 5/32" DIA.
LOW - VELOCITY POWER- DRIVEN
FASTENER W/ 1 1/4" PENETRATION
MIN. PER STUD MANUFACTURER'S
RECOMMENDATIONS
WALL TYPES
NTS
F1
1/4" = 1' -0"
1 1/2" =
9
EXISTING
STORAGE ROOM
108
NEW
SERVER ROOM
109
BUILDING FLOOR PLAN
REFLECTED CEILING PLAN
1/4" = 1' -0"
EXISTING
OFFICE
101
1/4" = 1' -0"
EXISTING
OPEN OFFICE
100
//
OFFICE FLOOR PLAN
EXISTING
STORAGE ROOM
102
NEW
SERVER ROOM
103
GENERAL NOTES:
1. ALL EXISTING BUILDING COLUMNS, EXTERIOR WALLS, EXTERIOR
WINDOWS, AND STRUCTURAL MEMBERS TO REMAIN, U.O.N.
2. ALL NEW PARTITION WALLS TO BE WALL TYPE
3. EACH ROOM SHALL HAVE SEPARATE SWITCHING BY ELECTRICAL
DESIGN /BUILD TO MEET WSEC 1513.
4. ALL FLOORS AND FINISHES EXISTING TO REMAIN.
5. ALL 2X4 LAY -IN FLUORESCENT LIGHTS ARE EXISTING TO REMAIN
U.O.N.
6. ALL DOORS SHOWN ARE EXISTING TO REMAIN U.O.N.
LEGEND:
KEY NOTES:
•
0
0
EXISTING EXIT
2X4 LAY -IN FLUORESCENT LIGHT
EXISTING PARTITION WALL
NEW PARTITION WALL, FINISHED TO MATCH
EXISTING ADJACENT
EXISTING EXTERIOR WALL, TYP.
NEW DOOR WITH LEVER STYLE HARDWARE, CLOSER,
ELECTRIC STRIKE, AND CONTROLLED CARD ACCESS.
DOOR AND FRAME FINISH AND STYLE TO MATCH EXISTING.
EXISTING LIGHT FIXTURE TO BE RELOCATED
RELOCATED LIGHT FIXTURE, IN EXISTING CEILING GRID
ALIGN
EXISTING DOOR TO BE REMOVED
ROOM FINISH NOTES:
1. ALL NEW GWB WALLS SHALL RECEIVE A SMOOTH WALL FINISH.
2. PAINT TO MATCH EXISTING
bO892
R V1I VVED FOR
CODE COMPLIANCE
APPROVED
SEP 1 6 2008
City Of Tukwila
BUILDING DIVISION_
, U.O.N.
C
a r c h i t e c t s
Terminal Sales (Building
1932 First Avenue
Suite 408
S e a t t l e , WA 9.8 1 0 1
206.720,7001 phone
206.720.2949 fax
www. craftarchitects,crarn
CONSULTANT
RECEWED
SEP 052000
PERMIT CENTEh Sheet No:
Architect of Record
ISSUE
09 - 05 - 08 FOR PERMIT
Revisions:
Sheet Title:
Date:
Design:
Drawn:
Project No:
Approved:
FLOOR PLANS
09/03/08
KMC
KLT
08- 161.06
KMR
Original drawing is 24" x 36 ".
Scale entities accordingly if reduced
COPYRIGHT CRAFTARCHITECTS 2008
A2.1