DESCRIPTION OF WORK:
HVAC SYSTEMS FOR TENANT IMPROVEMENT OF NEW MALL SPACE
Value of Mechanical: $15,000.00
Type of Fire Protection:
CitAf Tukwila
WEA SOUTHCENTER LLC
11601 WILSHIRE BLVD , LOS ANGELES CA
Furnace: <100K BTU 0
>100K BTU 0
Floor Furnace 0
Suspended/Wall/Floor Mounted Heater 0
Appliance Vent 0
Repair or Addition to Heat/Refrig /Cooling System.... 0
Air Handling Unit <10,000 CFM 0
>10,000 CFM 1
Evaporator Cooler 0
Ventilation Fan connected to single duct 0
Ventilation System 0
Hood and Duct 0
Incinerator: Domestic 0
Commercial/Industrial 0
doc: IMC-10/06
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http://www.ci.tukwila.wa.us
MECHANICAL PERMIT
EQUIPMENT TYPE AND QUANTITY
* *continued on next page **
M08 -019
Permit Number:
Issue Date:
Permit Expires On:
Phone:
Phone: 503 - 577 -8859
Phone: 253- 405 -6206
Expiration Date: 10/23/2009
M08 -019
06/13/2008
12/10/2008
Fees Collected: $327.20
International Mechanical Code Edition: 2006
Boiler Compressor:
0 -3 HP /100,000 BTU 0
3 -15 HP /500,000 BTU 0
15 -30 HP /1,000,000 BTU.. 0
30 -50 HP /1,750,000 BTU.. 0
50+ HP/1,750,000 BTU 0
Fire Damper 0
Diffuser 0
Thermostat 0
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment
Printed: 06-13 -2008
Permit Center Authorized Signature:
doc: IMC -10/06
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
Permit Number: M08 -019
Issue Date: 06/13/2008
Permit Expires On: 12/10/2008
Date: c3 - 09
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not .. to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the perfv fiance • J • .am authorized to sign and obtain this mechanical permit.
Signature: , _ �/ /� _ Date
Print Name: (le '(----
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
M08 -019 Printed: 06-13 -2008
1: ** *BUILDING DEPARTMENT CONDITIONS * **
•
City of Tukwila
Parcel No.: 6364200010
Address: 856 SOUTHCENTER MALL TUKW
Suite No:
Tenant: TEAVANA
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
PERMIT CONDITIONS
Permit Number: M08 - 019
Status: ISSUED
Applied Date: 01/17/2008
Issue Date: 06/13/2008
2: No changes shall be made to the approved plans unless approved by the design professional m responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431 - 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
6: Manufacturers installation instructions shall be available on the job site at the time of inspection.
7: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431 - 3670).
8: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
9: ** *FIRE DEPARTMENT CONDMONS * **
10: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
11: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
12: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
13: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
14: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
15: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
doc: Cond -10/06
M08 -019 Printed: 06 -13 -2008
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
16: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
17: An electrical permit from the City of Tukwila Building Department Permit Center (206- 431 -3670) is required for this
project.
doc: Cond -10/06
* *continued on next page **
M08 -019 Printed: 06-13 -2008
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work
construction or the performance of work.
doc: Cond -10/06 M08 -019
Date: e /✓
ordinances governing
or local laws regulating
Printed: 06-13 -2008
JAN 17 2008
SITE LOCATION
Site Address: c3t4 - 1C-A- -
Tenant Name /
Property Owners Name: Lt.
Mailing Address:
Company Name:
Company Name:
Mailing Address:
CITY OF TUKWIL"
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.citukwila.wa.us
MECHANICAL PERMIT APPLICATION
Mechanical Permit No. r' ■(
Project No. 906'0 d 1
(For office use only)
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
King Co Assessor's Tax No.: (9, ) 0 — CI)O ( 0
Suite Number:
Floor:
New Tenan • • '.... Yes El ..No
e-j
CONTACT PERSON - who do we con
Name\yY\ e r Y
Mailing Address: f, 3 3 G.
E -Mail Address: X. %'‘111C 5-D r e,( G Vr i'v C 1 A._
City
v
State
Zip
ct when your permit is ready to he issued
Day Telephone:`] 0 ,5' 77 7 - '&
Or_ ')72J3
City C _ State Zip
Fax Number: D `. o f 2 3 0
MECHANICAL CONTRACTOR INFORMATION
"Mb
Mailing Address:
City
Day Telephone:
Fax Number:
Expiration Date:
Contact Person:
E -Mail Address:
Contractor Registration Number:
Company Name: -1— 1r( f () (. � C
Mailing Address: k"1
( C6 0 e 3P))
(JO
State
Zip
ARCHITECT OF RECORD -; All pl
Lou r3 014
City Slate L� Z
Contact Person: Day Telephone: 3 1 4a� 5 `2-40 l/
E -Mail Address: Fax Number: 'R I 7 4.IcS 1,30
ENGINEER OF RECORD — All pl
m u
be wet stamped by Engineer of Record
Zip
Contact Person:
E -Mail Address:
Q:\Applications\Forms- Applications On Linen -2006 - Mechanical Permit Application.doc
Revised: 4 -2006
bh
City
Day Telephone:
Fax Number:
State
Page 1 of 2
Unit Type:
Qty
Unit Type:
Qty
Unit Type:
Qty
Boiler /Compressor:
Qty
Furnace <100K BTU
Air Handling Unit >10,000
CFM
`
Fire Damper
0 -3 HP /100,000 BTU
Furnace >100K BTU
Evaporator Cooler
Diffuser
3 -15 HP /500,000 BTU
Floor Furnace
Ventilation Fan Connected
to Single Duct
Thermostat
15 -30 HP /1,000,000 BTU
Suspended /Wall/Floor
Mounted Heater
Ventilation System
Wood /Gas Stove
30 -50 HP /1,750,000 BTU
Appliance Vent
Hood and Duct
Water Heater
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Refrig /Cooling
System
Incinerator - Domestic
Emergency
Generator
Air Handling Unit
<10,000 CFM
Incinerator — Comm /Ind
Other Mechanical
Equipment
Valuation of Project (contractor's bid price): $ rj °j
Scope of Work (please provide detailed information):
a
Use: Residential: New .... ❑ Replacement .... ❑
Commercial: New ..Z Replacement .... ❑
Fuel Type: Electric Gas .... ❑ Other:
Indicate type of mechanical work being installed and the quantity below:
PERMIT APPLICATION NOTES — Applicable to all, permits in
s d'p- pllca'
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested
in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING 0 ( '_ UTHORIZED AGENT:
Signatur
Print Name:
Mailing Address:
Date Application Accepted:
QAApplications\Fonns- Applications On Line \3 -2006 - Mechanical Permit Application.doc
Revised: 4 -2006
bh
Date: I Vv
a y Telephone: � 9" ,
z2._
City
C (7 J
State
Zip
Date Application Expires:
7 - L7_0
Staff Initials:
Page 2 of 2
Receipt No.: R08 -00164
Payee: PRECISION PERMITSERVICE
ACCOUNT ITEM LIST:
Description
PLAN CHECK - NONRES
RECEIVE D
JAN 18 2008
OOMWIUNiTY
DEVELOPMENT
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 6364200010 Permit Number: M08 -019
Address: 856 SOUTHCENTER MALL TUKW Status: PENDING
Suite No: Applied Date: 01/17/2008
Applicant: TEAVANA Issue Date:
Initials: WER Payment Date: 01/17/2008 02:10 PM
User ID: 1655 Balance: $267.76
TRANSACTION LIST:
Type Method Description Amount
Payment Check 5386 59.44
Account Code Current Pmts
000/345.830 59.44
Total: $59.44
Payment Amount: $59.44
7377 01/17 9710 TOTAL 713.99
doc: Receipt -06 Printed: 01 -17 -2008
Project:
1 eQ.1/' �
Type of Inspection:
.A
Address:
`°
Date Called:
Special Instructions:
Date Wanted:
74/4 f
a.m.
P.m.
Requester:
Phone No:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION l
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
1)708'-0/
rzi Approved per applicable codes.
Corrections required prior to approval.
❑ $60.0r EINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
COMMENTS:
Receipt No.:
Date:
Project:
7 "e ((A
Type of Inspection:
d <<6,,..-E of 1 o tw/ d•
Address: $
5 G VnAi L
Date Called:
Special Instructions:
Date Wanted:... ■ ( I /
l d
a.m.
p.m.
Requester:
Phone No:
i # — C.
1
.
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION 'R
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Ig Approved per applicable codes.
COMMENTS:
V A tJ -' 1 .c ��d r{S�s n yS I — Q15Se
Date: .. d 7
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Inspector:
'Receipt No.:
INSPECTION RECORD
Retain a copy with permit
Date:
PERMIT NO.
`
Corrections required prior to approval.
Project:
. "'"7 - E. c,..4 0- tea.
Type of Ins ection:
..440)1.0e.
'
,.4&r;k
Address:
it 15C
)\4 \\
Date Called:
Special Instructions:
Date Wanted:
. a. m.
.m.
Requester:
Phone No:
.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
114
PERMIT NO. •
(206)431 -3670
COMMENTS:
Approved per applicable codes.
El $60.00 REINSPECTION FEE REQI)IRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
Corrections required prior to approval.
Project: w { 4
_ Type gflnspectio ,� V
Addr s:
Date Called:
Special Instructions:
Date Wanted: �m
- 7 - i 6 -Q p.m.
'Requester:
Phone No:
7Go - 371`7
a
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. 1 PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
Approved per applicable codes. El Corrections required prior to approval.
COMMENTS:
Inspector:
❑ $60.00 INSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
(Receipt No.: Date:
(206)431 -3670
!d dam'
Project: 0 VA-
Type of Inspection:
Address:
"5 /1147/
Date Called: /
Special Instructions:
Date Wanted: O
4 --/6- e
p.m.
Requester:
Phone o:
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
En
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION P'
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Approved per applicable codes. Ij Corrections required prior to approval.
COMMENTS: %]/
Inspector:
Date:
$60. REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
Project: _ - V �N
Sprinklers:
Hood & Duct:
Type of Inspection:
Hi fs c. se c' 6 L
Address: c5--(.0 s • C .
Suite #:
iv+.l i_.
Contact Person:
6r1L.�
Special Instructions:
Phone No.:
Needs Shift Inspection:
Sprinklers:
Hood & Duct:
Fire Alarm:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
INSPECTION NUMBER
r Park East Tukwila, Wa. 98188 206- 575 -4407
Approved per applicable codes.
COMMENTS:
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA FIRE DEPARTMENT
PERMIT NUMBERS
Corrections required prior to approval.
Inspector: pv, s , v Date: / , / r? 8
■:
e $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
City of Tukwila Finance Department. CaII to schedule a reinspection.
Word /Inspection Record Form.Doc 1/13/06 T.F.D. Form F.P. 113
06 -05 -2008
JAMES MOORE
833 SE MAIN #242
PORTLAND OR 97213
RE: Permit Application No. M08 -019
856 SOUTHCENTER MALL TUKW
Dear Permit Applicant:
In reviewing our current permit application files, it appears that your permit application applied for on 01/17/2008 , has not been
issued by the City of Tukwila Permit Center. Per the International Codes, Uniform Plumbing Code and/or the National Electrical
Code, every permit application not issued within 180 days from the date of application shall expire by limitation and become null and
void. Your permit application expires on 07/15/2008 .
If you choose to pursue your project, a written request for extension of your application addressed to the Building Official,
demonstrating justifiable cause, will need to be received at the Permit Center prior to your expiration date of 07/15/2008. If it is
determined that an extension is granted, your application will be extended for an additional 90 days from the expiration date.
In the event we do not receive your written request for extension, your permit application will become null and void and your project
will require a new permit application, plans and specifications, and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
4.42
xc:
ifer Marshall
it Technician
Permit File No. M08 -019
City of Tukwila
Jim Haggerton, Mayor
11
epartment of Community Development Jack Pace, Director
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665
Public Works
Complete
Comments:
Please Route
Documents/routing slip.doc
2 -28 -02
•
PLAN
DEPARTMENTS:
Bui • i j g (vision
n
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
d
TUES/THURS ROUTING:
APPROVALS OR CORRECTIONS:
611 4iA -
Fire Prevention
Structural
Incomplete
Structural Review Required
•
ING SLIP
ACTIVITY NUMBER: M08 -019 DATE: 01 -17 -08
PROJECT NAME: TEAVANA
SITE ADDRESS: 856 SOUTHCENTER MALL
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # After Permit Issued
n
Planning Division n
Permit Coordinator
DUE DATE: 01 -24 -08
Not Applicable
lip
►4
Permit Center Use Only
-
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
❑ No further Review Required
DUE DATE: 02 -21 -08
Approved ❑ Approved with Conditions d Not Approved (attach comments) U
Notation:
REVIEWER'S INITIALS:
n
REVIEWER'S INITIALS: DATE:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Receipt No.: R08 -02108
Payee: AIR MOTION
ACCOUNT ITEM LIST:
Description
MECHANICAL - NONRES
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http://www.ci.tukwila.wa.us
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 20193 257.76
Payment Cash 10.00
RECEIPT
Account Code Current Pmts
000/322.100 267.76
Total: $267.76
Parcel No.: 6364200010 Permit Number: M08 -019
Address: 856 SOUTHCENTER MALL TUKW Status: APPROVED
Suite No: Applied Date: 01/17/2008
Applicant: TEAVANA Issue Date:
Payment Amount: $267.76
Initials: WER Payment Date: 06/13/2008 12:19 PM
User ID: 1655 Balance: $0.00
3602 06/13 9710 TOTAL 267.76
doc: Receipt-06 Printed: 06 -13 -2008
License Information
License
AIRMOI *077PM
Licensee Name
AIR MOTION INC
Licensee Type
CONSTRUCTION CONTRACTOR
UBI
601495387
Ind. Ins. Account Id
Business Type
CORPORATION
Address 1
5624 128TH ST E
Address 2
City
PUYALLUP
County
PIERCE
State
WA
Zip
98373
Phone
2537708270
Status
ACTIVE
Specialty 1
HTGNENT /AIR CONDITIONING
Specialty 2
UNUSED
Effective Date
10/14/1993
Expiration Date
10/23/2009
Suspend Date
Separation Date
Parent Company
Previous License
Next License
Associated License
Business Owner Information
Name
Role
Effective Date
Expiration Date
VERT, LYNN V
01/01/1980
DOWNS, WILLIAM R
01/01/1980
VERT, LYNN V
AGENT
01/01/1980
Look Up a Contractor, Electrician or Plumber License Detail
•
Washington State Department of Labor and Industries
General/Specialty Contractor
A business registered as a construction contractor with L &I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Bond Information
No Matching Information
Savings Information
Bank I Assignment
Page 1 of 2
https:// fortress .wa.gov /lni/bbip /printer.aspx ?License= AIRMOI *077PM 06/13/2008
AIR DEVICE SCHEDULE 8
PLAN
MARK
,
Q '
MODEL NO.
MODULE
SIZE
FACE
SIZE
NECK
SIZE
FLEX
SIZE
T
NOTES
A
2
TMSA -1 /AG -75
24 "x24"
18 "x18"
10" RD.
10" RD.
DIFF.
1,2,3
B
1
PAR
24 "x24"
N/A
22 "x22"
N/A
R.G.
2
C
1
PAR
24 "x24"
N/A
22 ° x22"
N/A
R.G.
4
D
1
PAR
24 "x24"
18 "x18"
12" RD.
12" RD.
DIFF.
1,2,3
E
1
TMSA- 1/AG -75
24 "x24"
18 "x18"
8" RD.
8" RD.
DIFF.
1,3,4
NOTES
PLAN FOR THROW PATTERN
FIT LAY —IN CEILING MODULE
INSTALL MANUAL VOLUME DAMPER
FIT GYP BOARD ROUGH IN, USE TRM FRAME FOR ACCESS PANEL
1. REFER TO
2. FRAME SHALL
3. PROVIDE &
4. FRAME SHALL
VAV BOX SCHEDULE
MANUFACTURER
MODEL NO.
MINIMUM
AIR CFM
TOTAL
CFM
INLET
SIZE
DISCHARGE
SIZE
BASE UNIT
WEIGHT
*TRANE
VPFC12
200
925
12"
19 "x16"
85 LBS
COOLING CAPACITY
HEATING
CAPACITY
FAN
SIZE
FAN
HP
VOLTS
PH
HZ
FLA
ACCESSORIES:
1. SOUND ATTENUATOR
2. ELECTRONIC CONTROLS (COORDINATE WITH
LANDLORD ON EXACT TYPE OF CONTROLS
REQUIRED, PRIOR TO BID)
18,981 BTUH
N/A
3SQ
1/3
115
1
60
5.5
LANDLORD'S SUPPLY
AIR DUCT MAIN
H.P. FLEX DUCT
MAX. 1' —O"
115V WIRING &
J —BOX BY
ELECTRICAL
CONTRACTOR J —BOX
r'
* THERMOSTAT WIRING — '
BY HVAC CONTRACTOR
MEDIMUM
PRESSURE DUCT
ELECTRONIC
DAMPER
OPERATOR
* FOLLOW MANUFACTURER'S WIRING DIAGRAM
ROOM THERMOSTAT
A CONICAL OR CENTERLINE
TAPER FITTING SHALL BE
UTILIZED FOR THE PRIMARY
DUCT TAP
HANGERS
(TYP. OF 4)
VAV BOX
VAV BOX CONNECTION DETAIL
I SCALE NODE
BEAM
N
CLEVIS HANGER
OVERSIZED FOR
INSULATION
WITH 18" ROLLED
SLEEVE FOR
SUPPORT 180'
BEAM CLAMP
PIPE HANGER DETAIL
I SCALE MOPE
HANGER SPACING AND ROD SIZE
PIPE MAX ROD
SIZE SPAN SIZE
1/2" 7' 3/8"
3'4 7' 3/8"
1 7' 3/8"
1 1/4" 7' 3/8"
1 1/2" 9' 3/8"
2" 10' 3/8"
2 1/2" 11' 1/2"
3 12' 1/2"
"
3 1/2" 13' 1/2"
4" 14' 5/8"
5" 16' 5/8"
6" 17' 3/4"
8" 19' 3/4"
10" 22' 7/8"
12" 23' 7/8"
14" 25' 1
16" 27' 1"
18" 28' 1"
20" 30' 1 1/4"
24 32' 1 1/4"
ROOF JOIST
HANGER WIRE
SHEET MTL. DUCT HANGER
SPIRAL DUCT
EXTERNAL INSULATION SHALL
BE RUN CONTINUOUS THRU
HANGERS
ROUND DUCT HANGER DETAIL
SCALE NONE
ROOF JOIST
HANGER WIRE
SHEET MTL. DUCT HANGER
DUCT HANGER DETAIL
SCALE NONE
RECTANGULAR DUCT
EXTERNAL INSULATION SHALL
BE RUN CONTINUOUS THRU
HANGERS
MECHANICAL SPECIIRCAT1ONS
ORDINANCES. PERMITS. AND CERTIFICATES
ALL WORK UNDER THIS DMSION OF THE SPECIFICATIONS SHALL BE INSTALLED IN FULL ACCOR—
DANCE WITH ALL LAWS, ORDINANCES AND REGULATIONS OF ALL GOVERNMENTAL AUTHORITIES
(LOCAL, STATE, AND FEDERAL) HAVING JURISDICTION WHICH IN ANY WAY WILL AFFECT THIS
WORK. THIS CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND CERTIFICATES OF IN—
SPECTION REQUIRED BY THE FOREGOING GOVERNMENTAL AUTHORITIES. ALL WORK SHALL BE IN—
STALLED IN FULL ACCORDANCE WITH REGULATIONS OF THE UNDERWRITERS HAVING JURISDICTION.
VISIT JOB SITE
VISIT JOB SITE AND BE FAMILIAR WITH LANDLORD'S REQUIREMENTS. NO ALLOWANCE WILL BE
MADE FOR EXTRAS DUE TO CONTRACTOR'S FAILURE TO VISIT THE JOB SITE AND /OR FAILURE
TO PREDETERMINE ALL CONDITIONS IMPOSED BY THE LANDLORD OR OTHER AUTHORITIES.
GUARANTEE
ALL LABOR AND MATERIAL FURNISHED UNDER THIS CONTRACT WILL. BE GUARANTEED FOR A
PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE BY THE TENANT. DURING THIS TIME,
THIS CONTRACTOR SHALL REPAIR ALL LEAKS AND CORRECT ALL DISCREPANCIES WITH CODES
OR THE SPECIFICATIONS AT HIS OWN EXPENSE
DUCTWORK
PRESSURE CLASS: 1" W.G.
SEAL CLASS: B
ALL NEW SUPPLY AIR DUCTS SHALL BE MADE OF GALVANIZED SHEET METAL WRAPPED WITH 2
OF INSULATION (UNLESS OTHERWISE NOTED). NEW DUCTWORK SHALL BE INSTALLED ACCORDING
TO SMACNA AND ASHRAE CURRENT STANDARDS DISCREPANCIES SHALL BE BROUGHT TO THE
ATTENTION OF ARCHITECT /ENGINEER.
ALL DUCTS WILL BE MADE AIRTIGHT WITH THE USE OF APPROVED DUCT JOINTS, CAULKING AND
SHEET METAL SCREWS. ALL DUCT TAPE OR SIMILAR MATERIALS WILL BE REJECTED BY THE
TENANT. NO GLASS FIBER OR SIMILAR MATERIALS WILL BE ACCEPTED AS A SUBSTITUTE FOR
SHEET METAL DUCTWORK. FLEXIBLE INSULATED, ROUND DUCT WILL BE PERMITTED FOR F1NAL
CONNECTIONS TO DIFFUSERS AND OUTLETS PROVIDED THAT IN NO CASE SHALL THIS FLEXIBLE
DUCT EXCEED 5' —O" IN LENGTH. CONNECTIONS BETWEEN DIFFUSERS AND OUTLETS, AND BE—
TWEEN FLEXIBLE DUCT AND SHEET METAL DUCTS, SHALL BE MADE WITH HOSE CLAMPS, OR
COLLARS SECURED WITH SHEET METAL SCREWS. SHORT RADIUS BEND WILL BE MADE WITH
ADJUSTABLE SHEET METAL ELBOWS. DO NOT ATTEMPT SHORT RADIUS BENDS USING FLEXIBLE
DUCT.
ALL JOINTS, LONGITUDINAL AND TRANSVERSE SEAMS, AND CONNECTIONS IN DUCTWORK MUST BE
SECURELY SEALED USING WELDMENTS; MECHANICAL FASTENERS WITH SEALS, GASKETS, OR
MASTICS; MESH AND MASTIC SEALING SYSTEMS; OR TAPES. TAPES AND MASTICS MUST BE LISTED
AND LABELED IN ACCORDANCE WITH UL 181A OR UL 181B. ALL LONGITUDINAL AND TRANSVERSE
JOINTS, SEAMS AND CONNECTIONS OF SUPPLY AND RETURN DUCTS OPERATING AT STATIC
PRESSURES LESS THAN OR EQUAL TO 2" W.G. SHALL BE SECURELY FASTENED AND SEALED
WITH WELDS GASKETS, MASTICS (ADHESIVES), MASTIC —PLUS— EMBEDDED FABRIC SYSTEMS OR
TAPES INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.
MECHANICAL FASTENERS AND SEALS, MASTICS, OR GASKETS MUST BE USED WHEN CONNECTING
DUCTS TO FANS AND OTHER AIR DISTRIBUTION EQUIPMENT.
INSULATION
SUPPLY DUCTWORK CONCEALED ABOVE CEILING SHALL HAVE 2" FIBERGLASS "Owens—Corning"
DUAL TEMP TYPE 100 WITH REINFORCED ALUMINUM FOIL FACING, APPLIED WITH ADHESIVE AND
STRAPPED 8' -0" ON CENTERS WITH STICK CUPS.
AIR DISTRIBUTION
CEILING OUTLETS, REGISTER AND GRILLES SHALL BE MADE BY TITUS COMPANY OF SIZE AND
TYPE SHOWN ON THE DRAWINGS AND ACCORDING TO THE AIR DEVICE SCHEDULE WITH BAKED
WITH ENAMEL FINISH, UNLESS OTHERWISE NOTED. EACH OUTLET SHALL BE COMPLETE WITH
INTEGRAL OPPOSED BLADE DAMPER.
AIR BALANCE
WHEN THE AIR DISTRIBUTION SYSTEM IS 100% COMPLETE ENTIRE SYSTEM MUST BE BALANCED
TO THE AIR QUANTITIES AS INDICATED ON THE PLANS, IN ACCORDANCE WITH THE AABC OR
NEBB SPECIFICATIONS. REPORTS MUST BE SUBMITTED (4) COPIES FOR EACH SYSTEM FOR
APPROVAL TO THE TENANT AND ARCHITECT. COPY OF REPORT MUST ALSO BE SUBMITTED TO
MALL LANDLORD. BALANCING COMPANY SHALL BE AN INDEPENDENT COMPANY AFFILIATED WITH
THE AMERICAN AIR BALANCING COUNCIL.
TESTING AND ADJUSTING
CONTRACTOR SHALL DEMONSTRATE OPERATION OF SYSTEM TO FULL SATISFACTION OF TENANT,
SHALL BALANCE AIR FLOW IN ACCORDANCE WITH AIR QUANTITIES ON DRAWINGS AND SHALL
RECORD VOLUME READINGS IN ACCORDANCE WITH ASHRAE AND PROVIDE SAME TO TENANT.
OPERATION AND MAINTENANCE DOCUMENTATION MUST BE PROVIDED TO THE OWNER THAT
INCLUDES AT LEAST THE FOLLOWING INFORMATION:
A. EQUIPMENT CAPACITY (INPUT AND OUTPUT) AND REQUIRED MAINTENANCE ACTIONS.
B. EQUIPMENT OPERATION AND MAINTENANCE MANUALS.
C. HVAC SYSTEM CONTROL MAINTENANCE AND CALIBRATION INFORMATION, INCLUDING WIRING
DIAGRAMS, SCHEMATICS, AND CONTROL SEQUENCE DESCRIPTIONS; DESIRED OR FIELD —
DETERMINED SET POINTS MUST BE PERMANENTLY RECORDED ON CONTROL DRAWINGS, AT
CONTROL DEVICES, OR, FOR DIGITAL CONTROL SYSTEMS, IN PROGRAMMING COMMENTS.
D. COMPLETE NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE.
DRAWINGS
THIS CONTRACTOR SHALL SUBMIT 4 COPIES OF RECORD DRAWINGS SHOWING EXACT LOCATIONS
OF THE UNIT, DUCTS, DIFFUSERS, ETC., FOR FUTURE REFERENCE.
UPON COMPLETION OF INSTALLATION, SUBMIT A CERTIFIED TEST AND BALANCE REPORT TO
LANDLORD FOR REVIEW AND APPROVAL THE REPORT SHALL INCLUDE ALL AIR FLOW BALANCE
DATA.
MECHANICAL GENERAL NOTES
PRIOR TO SUBMITTING A PROPOSAL, THE CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY
INSPECT EXISTING CONDITIONS TO ENSURE THAT WORK REPRESENTED ON DRAWINGS CAN BE
INSTALLED AS INDICATED. COORDINATE DISCREPANCIES BETWEEN DOCUMENTS AND FIELD
CONDITIONS WITH THE TENANT OR HIS AUTHORIZED AGENT. COORDINATE THE EXTENSION,
MODIFICATION, FINAL CONNECTION AND TESTING OF ALL UTILITIES OR INTERFACED SYSTEMS
WITH THE LANDLORD'S FIELD REPRESENTATIVE.
ARRANGE WITH LOCAL AND STATE AUTHORITIES AND UTILITY COMPANIES FOR PERMITS, FEES,
AND SERVICE CONNECTIONS FOR TEMPORARY AND PERMANENT WATER, SANITARY SEWER, STORM
AND INDUSTRIAL WASTE SERVICES IF APPUCABLE, VERIFYING LOCATIONS AND ARRANGEMENT,
AND PAY ALL CHARGES INCLUDING INSPECTIONS.
DRAWINGS ARE GENERALLY DIAGRAMMATIC AND ARE INTENDED TO ENCOMPASS A SYSTEM THAT
WILL NOT INTERFERE WITH THE STRUCTURAL AND ARCHITECTURAL DESIGN OF THE BUILDING.
COORDINATE WORK TO AVOID INTERFERENCE BETWEEN PIPING, EQUIPMENT, ARCHITECTURAL, AND
STRUCTURAL WORK.
NO COMPONENTS MAY BE ABANDONED IN PLACE. ALL COMPONENTS THAT ARE NOT REUSED
MUST BE REMOVED AND DISPOSED OF. COORDINATE DISPOSAL OF ALL REMOVED EQUIPMENT
WITH THE LANDLORD.
PROVIDE THE ENTIRE OPERATING SYSTEM AND ITS COMPONENT ITEMS OF EQUIPMENT FREE OF
OBJECTIONABLE VIBRATION OR NOISES. REFER TO ASHRAE HANDBOOK FOR RECOMMENDED
NOISE CRITERIA (NC) UNLESS OTHERWISE NOTED. STATICALLY AND DYNAMICALLY BALANCE
ROTATING EQUIPMENT, AND MOUNT OR FASTEN SO VIBRATION I5 PRODUCED OR TRANSMITTED
TO OR THROUGH THE BUILDING. IF OBJECTIONABLE NOISE OR VIBRATION IS PRODUCED OR
TRANSMITTED TO OR THROUGHOUT THE BUILDING STRUCTURE BY EQUIPMENT, PIPING, DUCTS
OR OTHER PARTS OF WORK, RECTIFY SUCH CONDITIONS AT NO ADDITIONAL COMPENSATION.
PROVIDE ADDITIONAL BALANCING DEVICES REQUIRED FOR COMPLETE SYSTEM BALANCING
INCLUDING BUT NOT LIMITED TO VOLUME DAMPERS, VALVES, AND SHEAVES OR PULLEYS AT
FANS.
VERIFY THE SIZE, LOCATION, AND CONDITION OF THE EXISTING PIPING BUILDING MANAGEMENT
SYSTEM CONNECTION POINTS, AND OUTSIDE AIR CONNECTIONS. REPLACE EXISTING
COMPONENTS IF THEY ARE INADEQUATE FOR THE NEW REQUIREMENTS.
COORDINATE ACCESS TO LANDLORD'S EQUIPMENT (VAV BOXES, FIRE DAMPERS, VOLUME
DAMPERS, ETC) WITH LANDLORD'S GENERAL CONTRACTOR /REPRESENTATIVE
TENANT G.C. SHALL ENGAGE LANDLORD'S DESINATED SEPARATE TEMPERATURE CONTROL
CONTRACTOR FOR FINAL SET —UP OF SYSTEM(S) OPERATIONS AND AIR BALANCING. GIVE ONE
COPY OF BALANCING REPORTED TO LANDLORD'S BUILDING ENGINEER.
PER 2006 IMC SECTION 606
Install smoke detector to shut down air distribution
by VAV's when the total combined C F M of all
VAV's (to include other tenants) sharing the same
plenum space exceeds 2000 CFM.
(See IMC 606.2.2 for approved method of detection)
HVAC -I- SPRINKLER KEYED NOTES 0
0 EXISTING LANDLORD SUPPLY AIR MAIN WITH VOLUME DAMPER. ADJUST DUCTWORK AS REQUIRED FOR
ACTUAL LOCATION OF LANDLORD'S SUPPLY AIR MAIN. COORDINATE WITH LANDLORD.
® NEW VAV BOX PROVIDED AND INSTALLED BY HVAC CONTRACTOR. REFER TO SCHEDULE FOR ADDITIONAL
INFORMATION AND CFM. PROVIDE ELECTRONIC CONTROLS AS REQUIRED PER LANDLORD.
®PROVIDE AND INSTALL THERMOSTAT WITH SUB —BASE AND LOCKING COVER. COORDINATE WITH ELECTRICAL
CONTRACTOR. MOUNTING HEIGHT 48" A.F.F. TURN KEY OVER TO STORE MANAGER.
® FLEXIBLE DUCT, MAXIMUM LENGTH 5' -0 ". PROVIDE SMOOTH TRANSITIONS AND PROPER SUPPORTS PER
S.MA.C.N.A. (TYPICAL). USE FLEXIBLE DUCT FOR F1NAL RUNOUT TO DIFFUSER ONLY. REFER TO SCHEDULE
FOR FLEXIBLE DUCT SIZES.
® NEW FIRE EXTINGUISHER SUPPLIED AND INSTALLED BY GENERAL CONTRACTOR. COORDINATE EXACT TYPE,
QUANTITY AND LOCATION WITH LANDLORD AND LOCAL FIRE MARSHALL.
® EXISTING SPRINKLER SYSTEM MAIN. FIELD VERIFY EXACT SIZE AND LOCATION.
®7 PROVIDE NEW OR RELOCATE EXISTING SPRINKLER HEAD AS REQUIRED. (TYP.). COORDINATE EXACT
LOCATION WITH NEW CEILING FIXTURES AND LIGHTS. MODIFY SUPPLY PIPING AS REQUIRED.
® NEW LOW PRESSURE SUPPLY AIR DUCT WITH 2" THICK EXTERNAL INSULATION (MIN. R -5) SUPPLIED AND
INSTALLED BY MECHANICAL CONTRACTOR. PROVIDE TRANSITIONS AS REQUIRED. DUCT DIMENSIONS ARE
CLEAR INTERNAL AIR PATH DIMENSIONS. HOLD ALL DUCTWORK AS HIGH AS POSSIBLE AND /OR PRACTICAL
IN JOIST SPACE.
® PROVIDE MANUAL VOLUME DAMPER AT ALL DIFFUSER CONNECTIONS (TYPICAL).
g 6" CLEAR HEIGHT ABOVE DEMISING WALLS TO BE USED AS PASSAGE FOR RETURN AIR BACK TO MALL'S
ROOFTOP UNIT..
MECHANICAL CONTRACTOR'S NOTES
ALL OF THE MECHANICAL & SPRINKLER WORK IS NOT NECESSARILY SHOWN OR NOTED ON THESE DRAWINGS.
THE CONTRACTORS SHALL VISIT THE JOB SITE AND VERIFY ALL EXISTING CONDITIONS RELATED TO THE WORK
PRIOR TO BIDDING. THOSE ITEMS NOT SHOWN OR NOTED, BUT ARE DEEMED NECESSARY FOR REMOVAL OR
RELOCATION BY THE OWNER OR HIS REPRESENTATIVE, SHALL BE PART OF THIS CONTRACT. THE SUBMISSION OF
THE PRO— POSALS SHALL BE CONSIDERED AS EVIDENCE THAT THE CONTRACTORS HAVE VISITED THE SITE. NO
EXTRA PAYMENTS WILL BE ALLOWED, DUE TO EXTRA WORK MADE NECESSARY BY THE CONTRACTOR'S FAILURE
TO VISIT THE JOB SITE.
2" WIDE MIN. DUCT STRAP
48" 0.C. MAX.
FIRE DAMPER
(LOCATION WHEN
REQUIRED)
VOLUME DAMPER
(FOR FINAL BALANCE
ADJUSTMENT)
SPIN —IN FITTING
WITH BALANCING DAMPER
AND 45' EXTRACTOR
(DAMPER USED FOR
ROUGH BALANCING)
RIGID ROUND METAL DUCT
EXTERNALLY INSULATED
RIGID ROUND DUCT ELBOW
EXTERNALLY INSULATED
INSULATED FLEXIBLE DUCT
MAX. LENGTH 5' —O ".
DIFFUSER
CEILING
HVAC DUCTWORK DETAIL
I SCALE NONE
METAL SUPPLY DUCT
EXTERNALLY INSULATED
LANDLORDS NOTES
1. LANDLORD PROVIDED A TENANT FIRE SERVICE MAIN WITH BRANCH PIPING STUBBED INTO EACH TENANT'S
SPACE. LANDLORD'S SPRINKLER SYSTEM IS DESIGNED PER ORDINARY HAZARD GROUP 2 AND THE LATEST
REQUIREMENTS OF NFPA -13. NO ISOLATION VALVES WILL BE PROVIDED OR PERMITTED.
2. TENANT SHALL CONNECT A FIRE SPRINKLER SYSTEM TO LANDLORD'S SPRINKLER SYSTEM WITHIN THE
DEMISED PREMISES USING APPROVED MECHANICAL FITTINGS. TENANT SHALL PROVIDE AND INSTALL ALL
BRANCH PIPING AND SPRINKLERS REQUIRED TO COMPLETE THE SPRINKLER SYSTEM WITHIN THE TENANT
SPACE. TENANT'S SPRINKLER SYSTEM DESIGNS SHALL BE BASED UPON THE REQUIREMENTS OF THE STATE
OF WASHINGTON AND THE CITY OF TUKWILA FIRE DEPARTMENT. TENANT SHALL ENGAGE THE SERVICES OF
A LANDLORD PREFERRED FIRE SPRINKLER CONTRACTOR TO DESIGN, PERMIT AND INSTALL TENANT'S FIRE
SPRINKLER SYSTEM IN ACCORDANCE WITH THE BASE BUILDING ACCORDING TO ORDINARY HAZARD GROUP 2
AND THE LATEST REQUIREMENTS OF NFPA -13.
3. ALL SPRINKLER HEADS IN THE FORWARD SELUNG AREA ARE TO BE CONCEALED POP OFF COVER TYPE.
4. ALL SUPPORTS SHALL BE FROM STRUCTURAL BEAMS AND JOISTS, NOT FROM FLOOR OR ROOF DECK
ABOVE.
5. TENANT'S CONTRACTOR SHALL INSTALL AN INSPECTORS TEST CONNECTION, PIPED TO A FLOOR SINK,
MOUNTED 3' —O" A.F.F.. INSTALL A 1" CORROSION RESISTANT SHUT —OFF VALVE.
6. TENANT SHALL INSTALL A VANE TYPE WATER FLOW DETECTOR IN THE MAIN SPRINKLER UNE IMMEDIATELY
AFTER CONNECTION TO THE LANDLORD'S MAIN, WHICH IS CONNECTED TO THE LANDLORD'S FIRE ALARM
SYSTEM.
FILE COPY
Permlt No.
Par review approval is subject to ORM and mss.
Approval of construction documents does not authorize
the violation of any adopted code or ordinance. Receipt
isadmowledged:
of approved Field
By
Date,
/3-0
City of Tukwila
BUILDING DIVISION
No VJS;or$
than 5th 's I ma to the scope
of work Mthout p€iot approval of
Tukwila Building
NOTE: Revisions will require a —.new n subitlal
and may include additional plan review fees.
* OR APPROVED EQUAL
* OR APPROVED EQUAL
MECHANICAL PLAN
SCALE w • ra
MO 0 q
REVIEWED R.
CODE COMPLIANCE
APPROVED
ty Of Tukwila
SEPARATE PERMIT
REQUIRED FOR:
i Mechanical
(Electrical
rio umbi ng Piping
City of Tukwila
BUILDING DIVISION
JAN 1 7 2008 x
HVAC SYMBOLS LECEND
SUPPLY AIR DIFFUSER
REFRIGERANT DISCHARGE UNE
REFRIGERANT SUCTION LINE
OUTDOOR AIR
RETURN AIR
SUPPLY AIR
TOILET EXHAUST
Z
--D—
RETURN AIR GRILLE
CONDENSATE DRAIN UNE
MOTORIZED DAMPER
SMOKE DETECTION DEVICE
THERMOSTAT
SMOKE DETECTOR
R.A.G.
DIFF.
M.D.
F.C.
RETURN AIR GRILLE
DIFFUSER
MANUAL DAMPER
FLEXIBLE CONNECTION
AIR DEVICE TYPE
AIR VOLUME IN
CUBIC FEET /MINUTE (CFM)
I
R.D.
R.S.
O.A.
S.A.
S.A.
T.E.
M
S
O
®
•
LANDLORD'S SUPPLY
AIR DUCT MAIN
H.P. FLEX DUCT
MAX. 1' —O"
115V WIRING &
J —BOX BY
ELECTRICAL
CONTRACTOR J —BOX
r'
* THERMOSTAT WIRING — '
BY HVAC CONTRACTOR
MEDIMUM
PRESSURE DUCT
ELECTRONIC
DAMPER
OPERATOR
* FOLLOW MANUFACTURER'S WIRING DIAGRAM
ROOM THERMOSTAT
A CONICAL OR CENTERLINE
TAPER FITTING SHALL BE
UTILIZED FOR THE PRIMARY
DUCT TAP
HANGERS
(TYP. OF 4)
VAV BOX
VAV BOX CONNECTION DETAIL
I SCALE NODE
BEAM
N
CLEVIS HANGER
OVERSIZED FOR
INSULATION
WITH 18" ROLLED
SLEEVE FOR
SUPPORT 180'
BEAM CLAMP
PIPE HANGER DETAIL
I SCALE MOPE
HANGER SPACING AND ROD SIZE
PIPE MAX ROD
SIZE SPAN SIZE
1/2" 7' 3/8"
3'4 7' 3/8"
1 7' 3/8"
1 1/4" 7' 3/8"
1 1/2" 9' 3/8"
2" 10' 3/8"
2 1/2" 11' 1/2"
3 12' 1/2"
"
3 1/2" 13' 1/2"
4" 14' 5/8"
5" 16' 5/8"
6" 17' 3/4"
8" 19' 3/4"
10" 22' 7/8"
12" 23' 7/8"
14" 25' 1
16" 27' 1"
18" 28' 1"
20" 30' 1 1/4"
24 32' 1 1/4"
ROOF JOIST
HANGER WIRE
SHEET MTL. DUCT HANGER
SPIRAL DUCT
EXTERNAL INSULATION SHALL
BE RUN CONTINUOUS THRU
HANGERS
ROUND DUCT HANGER DETAIL
SCALE NONE
ROOF JOIST
HANGER WIRE
SHEET MTL. DUCT HANGER
DUCT HANGER DETAIL
SCALE NONE
RECTANGULAR DUCT
EXTERNAL INSULATION SHALL
BE RUN CONTINUOUS THRU
HANGERS
MECHANICAL SPECIIRCAT1ONS
ORDINANCES. PERMITS. AND CERTIFICATES
ALL WORK UNDER THIS DMSION OF THE SPECIFICATIONS SHALL BE INSTALLED IN FULL ACCOR—
DANCE WITH ALL LAWS, ORDINANCES AND REGULATIONS OF ALL GOVERNMENTAL AUTHORITIES
(LOCAL, STATE, AND FEDERAL) HAVING JURISDICTION WHICH IN ANY WAY WILL AFFECT THIS
WORK. THIS CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND CERTIFICATES OF IN—
SPECTION REQUIRED BY THE FOREGOING GOVERNMENTAL AUTHORITIES. ALL WORK SHALL BE IN—
STALLED IN FULL ACCORDANCE WITH REGULATIONS OF THE UNDERWRITERS HAVING JURISDICTION.
VISIT JOB SITE
VISIT JOB SITE AND BE FAMILIAR WITH LANDLORD'S REQUIREMENTS. NO ALLOWANCE WILL BE
MADE FOR EXTRAS DUE TO CONTRACTOR'S FAILURE TO VISIT THE JOB SITE AND /OR FAILURE
TO PREDETERMINE ALL CONDITIONS IMPOSED BY THE LANDLORD OR OTHER AUTHORITIES.
GUARANTEE
ALL LABOR AND MATERIAL FURNISHED UNDER THIS CONTRACT WILL. BE GUARANTEED FOR A
PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE BY THE TENANT. DURING THIS TIME,
THIS CONTRACTOR SHALL REPAIR ALL LEAKS AND CORRECT ALL DISCREPANCIES WITH CODES
OR THE SPECIFICATIONS AT HIS OWN EXPENSE
DUCTWORK
PRESSURE CLASS: 1" W.G.
SEAL CLASS: B
ALL NEW SUPPLY AIR DUCTS SHALL BE MADE OF GALVANIZED SHEET METAL WRAPPED WITH 2
OF INSULATION (UNLESS OTHERWISE NOTED). NEW DUCTWORK SHALL BE INSTALLED ACCORDING
TO SMACNA AND ASHRAE CURRENT STANDARDS DISCREPANCIES SHALL BE BROUGHT TO THE
ATTENTION OF ARCHITECT /ENGINEER.
ALL DUCTS WILL BE MADE AIRTIGHT WITH THE USE OF APPROVED DUCT JOINTS, CAULKING AND
SHEET METAL SCREWS. ALL DUCT TAPE OR SIMILAR MATERIALS WILL BE REJECTED BY THE
TENANT. NO GLASS FIBER OR SIMILAR MATERIALS WILL BE ACCEPTED AS A SUBSTITUTE FOR
SHEET METAL DUCTWORK. FLEXIBLE INSULATED, ROUND DUCT WILL BE PERMITTED FOR F1NAL
CONNECTIONS TO DIFFUSERS AND OUTLETS PROVIDED THAT IN NO CASE SHALL THIS FLEXIBLE
DUCT EXCEED 5' —O" IN LENGTH. CONNECTIONS BETWEEN DIFFUSERS AND OUTLETS, AND BE—
TWEEN FLEXIBLE DUCT AND SHEET METAL DUCTS, SHALL BE MADE WITH HOSE CLAMPS, OR
COLLARS SECURED WITH SHEET METAL SCREWS. SHORT RADIUS BEND WILL BE MADE WITH
ADJUSTABLE SHEET METAL ELBOWS. DO NOT ATTEMPT SHORT RADIUS BENDS USING FLEXIBLE
DUCT.
ALL JOINTS, LONGITUDINAL AND TRANSVERSE SEAMS, AND CONNECTIONS IN DUCTWORK MUST BE
SECURELY SEALED USING WELDMENTS; MECHANICAL FASTENERS WITH SEALS, GASKETS, OR
MASTICS; MESH AND MASTIC SEALING SYSTEMS; OR TAPES. TAPES AND MASTICS MUST BE LISTED
AND LABELED IN ACCORDANCE WITH UL 181A OR UL 181B. ALL LONGITUDINAL AND TRANSVERSE
JOINTS, SEAMS AND CONNECTIONS OF SUPPLY AND RETURN DUCTS OPERATING AT STATIC
PRESSURES LESS THAN OR EQUAL TO 2" W.G. SHALL BE SECURELY FASTENED AND SEALED
WITH WELDS GASKETS, MASTICS (ADHESIVES), MASTIC —PLUS— EMBEDDED FABRIC SYSTEMS OR
TAPES INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.
MECHANICAL FASTENERS AND SEALS, MASTICS, OR GASKETS MUST BE USED WHEN CONNECTING
DUCTS TO FANS AND OTHER AIR DISTRIBUTION EQUIPMENT.
INSULATION
SUPPLY DUCTWORK CONCEALED ABOVE CEILING SHALL HAVE 2" FIBERGLASS "Owens—Corning"
DUAL TEMP TYPE 100 WITH REINFORCED ALUMINUM FOIL FACING, APPLIED WITH ADHESIVE AND
STRAPPED 8' -0" ON CENTERS WITH STICK CUPS.
AIR DISTRIBUTION
CEILING OUTLETS, REGISTER AND GRILLES SHALL BE MADE BY TITUS COMPANY OF SIZE AND
TYPE SHOWN ON THE DRAWINGS AND ACCORDING TO THE AIR DEVICE SCHEDULE WITH BAKED
WITH ENAMEL FINISH, UNLESS OTHERWISE NOTED. EACH OUTLET SHALL BE COMPLETE WITH
INTEGRAL OPPOSED BLADE DAMPER.
AIR BALANCE
WHEN THE AIR DISTRIBUTION SYSTEM IS 100% COMPLETE ENTIRE SYSTEM MUST BE BALANCED
TO THE AIR QUANTITIES AS INDICATED ON THE PLANS, IN ACCORDANCE WITH THE AABC OR
NEBB SPECIFICATIONS. REPORTS MUST BE SUBMITTED (4) COPIES FOR EACH SYSTEM FOR
APPROVAL TO THE TENANT AND ARCHITECT. COPY OF REPORT MUST ALSO BE SUBMITTED TO
MALL LANDLORD. BALANCING COMPANY SHALL BE AN INDEPENDENT COMPANY AFFILIATED WITH
THE AMERICAN AIR BALANCING COUNCIL.
TESTING AND ADJUSTING
CONTRACTOR SHALL DEMONSTRATE OPERATION OF SYSTEM TO FULL SATISFACTION OF TENANT,
SHALL BALANCE AIR FLOW IN ACCORDANCE WITH AIR QUANTITIES ON DRAWINGS AND SHALL
RECORD VOLUME READINGS IN ACCORDANCE WITH ASHRAE AND PROVIDE SAME TO TENANT.
OPERATION AND MAINTENANCE DOCUMENTATION MUST BE PROVIDED TO THE OWNER THAT
INCLUDES AT LEAST THE FOLLOWING INFORMATION:
A. EQUIPMENT CAPACITY (INPUT AND OUTPUT) AND REQUIRED MAINTENANCE ACTIONS.
B. EQUIPMENT OPERATION AND MAINTENANCE MANUALS.
C. HVAC SYSTEM CONTROL MAINTENANCE AND CALIBRATION INFORMATION, INCLUDING WIRING
DIAGRAMS, SCHEMATICS, AND CONTROL SEQUENCE DESCRIPTIONS; DESIRED OR FIELD —
DETERMINED SET POINTS MUST BE PERMANENTLY RECORDED ON CONTROL DRAWINGS, AT
CONTROL DEVICES, OR, FOR DIGITAL CONTROL SYSTEMS, IN PROGRAMMING COMMENTS.
D. COMPLETE NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE.
DRAWINGS
THIS CONTRACTOR SHALL SUBMIT 4 COPIES OF RECORD DRAWINGS SHOWING EXACT LOCATIONS
OF THE UNIT, DUCTS, DIFFUSERS, ETC., FOR FUTURE REFERENCE.
UPON COMPLETION OF INSTALLATION, SUBMIT A CERTIFIED TEST AND BALANCE REPORT TO
LANDLORD FOR REVIEW AND APPROVAL THE REPORT SHALL INCLUDE ALL AIR FLOW BALANCE
DATA.
MECHANICAL GENERAL NOTES
PRIOR TO SUBMITTING A PROPOSAL, THE CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY
INSPECT EXISTING CONDITIONS TO ENSURE THAT WORK REPRESENTED ON DRAWINGS CAN BE
INSTALLED AS INDICATED. COORDINATE DISCREPANCIES BETWEEN DOCUMENTS AND FIELD
CONDITIONS WITH THE TENANT OR HIS AUTHORIZED AGENT. COORDINATE THE EXTENSION,
MODIFICATION, FINAL CONNECTION AND TESTING OF ALL UTILITIES OR INTERFACED SYSTEMS
WITH THE LANDLORD'S FIELD REPRESENTATIVE.
ARRANGE WITH LOCAL AND STATE AUTHORITIES AND UTILITY COMPANIES FOR PERMITS, FEES,
AND SERVICE CONNECTIONS FOR TEMPORARY AND PERMANENT WATER, SANITARY SEWER, STORM
AND INDUSTRIAL WASTE SERVICES IF APPUCABLE, VERIFYING LOCATIONS AND ARRANGEMENT,
AND PAY ALL CHARGES INCLUDING INSPECTIONS.
DRAWINGS ARE GENERALLY DIAGRAMMATIC AND ARE INTENDED TO ENCOMPASS A SYSTEM THAT
WILL NOT INTERFERE WITH THE STRUCTURAL AND ARCHITECTURAL DESIGN OF THE BUILDING.
COORDINATE WORK TO AVOID INTERFERENCE BETWEEN PIPING, EQUIPMENT, ARCHITECTURAL, AND
STRUCTURAL WORK.
NO COMPONENTS MAY BE ABANDONED IN PLACE. ALL COMPONENTS THAT ARE NOT REUSED
MUST BE REMOVED AND DISPOSED OF. COORDINATE DISPOSAL OF ALL REMOVED EQUIPMENT
WITH THE LANDLORD.
PROVIDE THE ENTIRE OPERATING SYSTEM AND ITS COMPONENT ITEMS OF EQUIPMENT FREE OF
OBJECTIONABLE VIBRATION OR NOISES. REFER TO ASHRAE HANDBOOK FOR RECOMMENDED
NOISE CRITERIA (NC) UNLESS OTHERWISE NOTED. STATICALLY AND DYNAMICALLY BALANCE
ROTATING EQUIPMENT, AND MOUNT OR FASTEN SO VIBRATION I5 PRODUCED OR TRANSMITTED
TO OR THROUGH THE BUILDING. IF OBJECTIONABLE NOISE OR VIBRATION IS PRODUCED OR
TRANSMITTED TO OR THROUGHOUT THE BUILDING STRUCTURE BY EQUIPMENT, PIPING, DUCTS
OR OTHER PARTS OF WORK, RECTIFY SUCH CONDITIONS AT NO ADDITIONAL COMPENSATION.
PROVIDE ADDITIONAL BALANCING DEVICES REQUIRED FOR COMPLETE SYSTEM BALANCING
INCLUDING BUT NOT LIMITED TO VOLUME DAMPERS, VALVES, AND SHEAVES OR PULLEYS AT
FANS.
VERIFY THE SIZE, LOCATION, AND CONDITION OF THE EXISTING PIPING BUILDING MANAGEMENT
SYSTEM CONNECTION POINTS, AND OUTSIDE AIR CONNECTIONS. REPLACE EXISTING
COMPONENTS IF THEY ARE INADEQUATE FOR THE NEW REQUIREMENTS.
COORDINATE ACCESS TO LANDLORD'S EQUIPMENT (VAV BOXES, FIRE DAMPERS, VOLUME
DAMPERS, ETC) WITH LANDLORD'S GENERAL CONTRACTOR /REPRESENTATIVE
TENANT G.C. SHALL ENGAGE LANDLORD'S DESINATED SEPARATE TEMPERATURE CONTROL
CONTRACTOR FOR FINAL SET —UP OF SYSTEM(S) OPERATIONS AND AIR BALANCING. GIVE ONE
COPY OF BALANCING REPORTED TO LANDLORD'S BUILDING ENGINEER.
PER 2006 IMC SECTION 606
Install smoke detector to shut down air distribution
by VAV's when the total combined C F M of all
VAV's (to include other tenants) sharing the same
plenum space exceeds 2000 CFM.
(See IMC 606.2.2 for approved method of detection)
HVAC -I- SPRINKLER KEYED NOTES 0
0 EXISTING LANDLORD SUPPLY AIR MAIN WITH VOLUME DAMPER. ADJUST DUCTWORK AS REQUIRED FOR
ACTUAL LOCATION OF LANDLORD'S SUPPLY AIR MAIN. COORDINATE WITH LANDLORD.
® NEW VAV BOX PROVIDED AND INSTALLED BY HVAC CONTRACTOR. REFER TO SCHEDULE FOR ADDITIONAL
INFORMATION AND CFM. PROVIDE ELECTRONIC CONTROLS AS REQUIRED PER LANDLORD.
®PROVIDE AND INSTALL THERMOSTAT WITH SUB —BASE AND LOCKING COVER. COORDINATE WITH ELECTRICAL
CONTRACTOR. MOUNTING HEIGHT 48" A.F.F. TURN KEY OVER TO STORE MANAGER.
® FLEXIBLE DUCT, MAXIMUM LENGTH 5' -0 ". PROVIDE SMOOTH TRANSITIONS AND PROPER SUPPORTS PER
S.MA.C.N.A. (TYPICAL). USE FLEXIBLE DUCT FOR F1NAL RUNOUT TO DIFFUSER ONLY. REFER TO SCHEDULE
FOR FLEXIBLE DUCT SIZES.
® NEW FIRE EXTINGUISHER SUPPLIED AND INSTALLED BY GENERAL CONTRACTOR. COORDINATE EXACT TYPE,
QUANTITY AND LOCATION WITH LANDLORD AND LOCAL FIRE MARSHALL.
® EXISTING SPRINKLER SYSTEM MAIN. FIELD VERIFY EXACT SIZE AND LOCATION.
®7 PROVIDE NEW OR RELOCATE EXISTING SPRINKLER HEAD AS REQUIRED. (TYP.). COORDINATE EXACT
LOCATION WITH NEW CEILING FIXTURES AND LIGHTS. MODIFY SUPPLY PIPING AS REQUIRED.
® NEW LOW PRESSURE SUPPLY AIR DUCT WITH 2" THICK EXTERNAL INSULATION (MIN. R -5) SUPPLIED AND
INSTALLED BY MECHANICAL CONTRACTOR. PROVIDE TRANSITIONS AS REQUIRED. DUCT DIMENSIONS ARE
CLEAR INTERNAL AIR PATH DIMENSIONS. HOLD ALL DUCTWORK AS HIGH AS POSSIBLE AND /OR PRACTICAL
IN JOIST SPACE.
® PROVIDE MANUAL VOLUME DAMPER AT ALL DIFFUSER CONNECTIONS (TYPICAL).
g 6" CLEAR HEIGHT ABOVE DEMISING WALLS TO BE USED AS PASSAGE FOR RETURN AIR BACK TO MALL'S
ROOFTOP UNIT..
MECHANICAL CONTRACTOR'S NOTES
ALL OF THE MECHANICAL & SPRINKLER WORK IS NOT NECESSARILY SHOWN OR NOTED ON THESE DRAWINGS.
THE CONTRACTORS SHALL VISIT THE JOB SITE AND VERIFY ALL EXISTING CONDITIONS RELATED TO THE WORK
PRIOR TO BIDDING. THOSE ITEMS NOT SHOWN OR NOTED, BUT ARE DEEMED NECESSARY FOR REMOVAL OR
RELOCATION BY THE OWNER OR HIS REPRESENTATIVE, SHALL BE PART OF THIS CONTRACT. THE SUBMISSION OF
THE PRO— POSALS SHALL BE CONSIDERED AS EVIDENCE THAT THE CONTRACTORS HAVE VISITED THE SITE. NO
EXTRA PAYMENTS WILL BE ALLOWED, DUE TO EXTRA WORK MADE NECESSARY BY THE CONTRACTOR'S FAILURE
TO VISIT THE JOB SITE.
2" WIDE MIN. DUCT STRAP
48" 0.C. MAX.
FIRE DAMPER
(LOCATION WHEN
REQUIRED)
VOLUME DAMPER
(FOR FINAL BALANCE
ADJUSTMENT)
SPIN —IN FITTING
WITH BALANCING DAMPER
AND 45' EXTRACTOR
(DAMPER USED FOR
ROUGH BALANCING)
RIGID ROUND METAL DUCT
EXTERNALLY INSULATED
RIGID ROUND DUCT ELBOW
EXTERNALLY INSULATED
INSULATED FLEXIBLE DUCT
MAX. LENGTH 5' —O ".
DIFFUSER
CEILING
HVAC DUCTWORK DETAIL
I SCALE NONE
METAL SUPPLY DUCT
EXTERNALLY INSULATED
LANDLORDS NOTES
1. LANDLORD PROVIDED A TENANT FIRE SERVICE MAIN WITH BRANCH PIPING STUBBED INTO EACH TENANT'S
SPACE. LANDLORD'S SPRINKLER SYSTEM IS DESIGNED PER ORDINARY HAZARD GROUP 2 AND THE LATEST
REQUIREMENTS OF NFPA -13. NO ISOLATION VALVES WILL BE PROVIDED OR PERMITTED.
2. TENANT SHALL CONNECT A FIRE SPRINKLER SYSTEM TO LANDLORD'S SPRINKLER SYSTEM WITHIN THE
DEMISED PREMISES USING APPROVED MECHANICAL FITTINGS. TENANT SHALL PROVIDE AND INSTALL ALL
BRANCH PIPING AND SPRINKLERS REQUIRED TO COMPLETE THE SPRINKLER SYSTEM WITHIN THE TENANT
SPACE. TENANT'S SPRINKLER SYSTEM DESIGNS SHALL BE BASED UPON THE REQUIREMENTS OF THE STATE
OF WASHINGTON AND THE CITY OF TUKWILA FIRE DEPARTMENT. TENANT SHALL ENGAGE THE SERVICES OF
A LANDLORD PREFERRED FIRE SPRINKLER CONTRACTOR TO DESIGN, PERMIT AND INSTALL TENANT'S FIRE
SPRINKLER SYSTEM IN ACCORDANCE WITH THE BASE BUILDING ACCORDING TO ORDINARY HAZARD GROUP 2
AND THE LATEST REQUIREMENTS OF NFPA -13.
3. ALL SPRINKLER HEADS IN THE FORWARD SELUNG AREA ARE TO BE CONCEALED POP OFF COVER TYPE.
4. ALL SUPPORTS SHALL BE FROM STRUCTURAL BEAMS AND JOISTS, NOT FROM FLOOR OR ROOF DECK
ABOVE.
5. TENANT'S CONTRACTOR SHALL INSTALL AN INSPECTORS TEST CONNECTION, PIPED TO A FLOOR SINK,
MOUNTED 3' —O" A.F.F.. INSTALL A 1" CORROSION RESISTANT SHUT —OFF VALVE.
6. TENANT SHALL INSTALL A VANE TYPE WATER FLOW DETECTOR IN THE MAIN SPRINKLER UNE IMMEDIATELY
AFTER CONNECTION TO THE LANDLORD'S MAIN, WHICH IS CONNECTED TO THE LANDLORD'S FIRE ALARM
SYSTEM.
FILE COPY
Permlt No.
Par review approval is subject to ORM and mss.
Approval of construction documents does not authorize
the violation of any adopted code or ordinance. Receipt
isadmowledged:
of approved Field
By
Date,
/3-0
City of Tukwila
BUILDING DIVISION
No VJS;or$
than 5th 's I ma to the scope
of work Mthout p€iot approval of
Tukwila Building
NOTE: Revisions will require a —.new n subitlal
and may include additional plan review fees.
* OR APPROVED EQUAL
* OR APPROVED EQUAL
MECHANICAL PLAN
SCALE w • ra
MO 0 q
REVIEWED R.
CODE COMPLIANCE
APPROVED
ty Of Tukwila
SEPARATE PERMIT
REQUIRED FOR:
i Mechanical
(Electrical
rio umbi ng Piping
City of Tukwila
BUILDING DIVISION
JAN 1 7 2008 x
v l I
LANDLORD'S SUPPLY
AIR DUCT MAIN
H.P. FLEX DUCT
MAX. 1' -0"
115V WIRING &
J —BOX BY
ELECTRICAL
CONTRACTOR J —BOX
r
i
* THERMOSTAT WIRING -�
BY HVAC CONTRACTOR
MEDIMUM
PRESSURE DUCT
ELECTRONIC
DAMPER
OPERATOR
* FOLLOW MANUFACTURER'S WIRING DIAGRAM
ROOM THERMOSTAT
A CONICAL OR CENTERLINE
TAPER FITTING SHALL BE
UTILIZED FOR THE PRIMARY
DUCT TAP
HANGERS
(TYP. OF 4)
VAV BOX
VAV BOX CONNECTION DETAIL
I SCALE: NONE
bE COMPLIANCE
CLEVIS HANGER
OVERSIZED FOR
INSULATION
WITH 18" ROLLED
SLEEVE FOR
SUPPORT 180'
HANGER SPACING AND
PIPE
SIZE
1/2"
3/4"
1
1 1/4"
1 1/2"
2
2 1/2"
3
3 1/2"
4"
5"
6"
8 "
10"
12"
14"
16"
18"
20"
24
MAX
SPAN
7'
7'
7'
7'
9'
10'
11'
12'
13'
14'
16'
17'
19'
22'
23'
25'
27'
28'
30'
32'
ROD SIZE
ROD
SIZE
3 /8"
3/8"
3/8"
1/2"
1/2"
1/2"
5/8"
5/8"
3/4"
3/4"
7/8"
1 '
1 "
1 "
1 1 /4
1 1 /4
PIPE HANGER DETAIL
I SCALE NONE
3
ROOF JOIST
HANGER WIRE
Lit/ Of T UkW €l
SPIRAL DUCT
FED f
SHEET MTL DUCT HANGER
EXTERNAL INSULATION SHALL
BE RUN CONTINUOUS THRU
HANGERS
ROUND DUCT HANGER DETAIL
SCALE: aoE
)/ lipp„
ROOF JOIST
HANGER WIRE
SHEET MTL DUCT HANGER
DUCT HANGER DETAIL
SCALE NONE
RECTANGULAR DUCT
EXTERNAL INSULATION SHALL
BE RUN CONTINUOUS THRU
HANGERS
MECHANICAL SPECIFICATIONS
ORDINANCES. PERMITS. AND CERTIFICATES
ALL WORK UNDER THIS DIVISION OF THE SPECIFICATIONS SHALL BE INSTALLED IN FULL ACCOR—
DANCE WITH ALL LAWS, ORDINANCES AND REGULATIONS OF ALL GOVERNMENTAL AUTHORITIES
(LOCAL, STATE, AND FEDERAL) HAVING JURISDICTION WHICH IN ANY WAY WILL AFFECT THIS
WORK. THIS CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND CERTIFICATES OF IN—
SPECTION REQUIRED BY THE FOREGOING GOVERNMENTAL AUTHORITIES. ALL WORK SHALL BE IN—
STALLED IN FULL ACCORDANCE WITH REGULATIONS OF THE UNDERWRITERS HAVING JURISDICTION.
VISIT JOB SITE
VISIT JOB SITE AND BE FAMILIAR WITH LANDLORD'S REQUIREMENTS. NO ALLOWANCE WILL BE
MADE FOR EXTRAS DUE TO CONTRACTOR'S FAILURE TO VISIT THE JOB SITE AND /OR FAILURE
TO PREDETERMINE ALL CONDITIONS IMPOSED BY THE LANDLORD OR OTHER AUTHORITIES.
GUARANTEE
ALL LABOR AND MATERIAL FURNISHED UNDER THIS CONTRACT WILL BE GUARANTEED FOR A
PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE BY THE TENANT. DURING THIS TIME,
THIS CONTRACTOR SHALL REPAIR ALL LEAKS AND CORRECT ALL DISCREPANCIES WITH CODES
OR THE SPECIFICATIONS AT HIS OWN EXPENSE
DUCTWORK
PRESSURE CLASS: 1" W.G.
SEAL CLASS: B
ALL NEW SUPPLY AIR DUCTS SHALL BE MADE OF GALVANIZED SHEET METAL WRAPPED WITH 2"
OF INSULATION (UNLESS OTHERWISE NOTED). NEW DUCTWORK SHALL BE INSTALLED ACCORDING
TO SMACNA AND ASHRAE CURRENT STANDARDS DISCREPANCIES SHALL BE BROUGHT TO THE
ATTENTION OF ARCHITECT /ENGINEER.
ALL DUCTS WILL BE MADE AIRTIGHT WITH THE USE OF APPROVED DUCT JOINTS, CAULKING AND
SHEET METAL SCREWS. ALL DUCT TAPE OR SIMILAR MATERIALS WILL BE REJECTED BY THE
TENANT. NO GLASS FIBER OR SIMILAR MATERIALS WILL BE ACCEPTED AS A SUBSTITUTE FOR
SHEET METAL DUCTWORK. FLEXIBLE INSULATED, ROUND DUCT WILL BE PERMITTED FOR FINAL
CONNECTIONS TO DIFFUSERS AND OUTLETS PROVIDED THAT IN NO CASE SHALL THIS FLEXIBLE
DUCT EXCEED 5' -0" IN LENGTH. CONNECTIONS BETWEEN DIFFUSERS AND OUTLETS, AND BE—
TWEEN FLEXIBLE DUCT AND SHEET METAL DUCTS, SHALL BE MADE WITH HOSE CLAMPS, OR
COLLARS SECURED WITH SHEET METAL SCREWS. SHORT RADIUS BEND WILL BE MADE WITH
ADJUSTABLE SHEET METAL ELBOWS. DO NOT ATTEMPT SHORT RADIUS BENDS USING FLEXIBLE
DUCT.
ALL JOINTS, LONGITUDINAL AND TRANSVERSE SEAMS, AND CONNECTIONS IN DUCTWORK MUST BE
SECURELY SEALED USING WELDMENTS; MECHANICAL FASTENERS WITH SEALS, GASKETS, OR
MASTICS; MESH AND MASTIC SEAUNG SYSTEMS; OR TAPES. TAPES AND MASTICS MUST BE LISTED
AND LABELED IN ACCORDANCE WITH UL 181A OR UL 1816. ALL LONGITUDINAL AND TRANSVERSE
JOINTS, SEAMS AND CONNECTIONS OF SUPPLY AND RETURN DUCTS OPERATING AT STATIC
PRESSURES LESS THAN OR EQUAL TO 2 W.G. SHALL BE SECURELY FASTENED AND SEALED
WITH WELDS GASKETS, MASTICS (ADHESIVES), MASTIC— PLUS — EMBEDDED FABRIC SYSTEMS OR
TAPES INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.
MECHANICAL FASTENERS AND SEALS, MASTICS, OR GASKETS MUST BE USED WHEN CONNECTING
DUCTS TO FANS AND OTHER AIR DISTRIBUTION EQUIPMENT.
INSULATION
SUPPLY DUCTWORK CONCEALED ABOVE CEILING SHALL HAVE 2" FIBERGLASS "Owens— Corning"
DUAL TEMP TYPE 100 WITH REINFORCED ALUMINUM FOIL FACING, APPLIED WITH ADHESIVE AND
STRAPPED 8' —O" ON CENTERS WITH STICK CUPS.
AIR DISTRIBUTION
CEILING OUTLETS, REGISTER AND GRILLES SHALL BE MADE BY TITUS COMPANY OF SIZE AND
TYPE SHOWN ON THE DRAWINGS AND ACCORDING TO THE AIR DEVICE SCHEDULE WITH BAKED
WITH ENAMEL FINISH, UNLESS OTHERWISE NOTED. EACH OUTLET SHALL BE COMPLETE WITH
INTEGRAL OPPOSED BLADE DAMPER.
AIR BALANCE
WHEN THE AIR DISTRIBUTION SYSTEM I5 100% COMPLETE ENTIRE SYSTEM MUST BE BALANCED
TO THE AIR QUANTITIES AS INDICATED ON THE PLANS, IN ACCORDANCE WITH THE AABC OR
NEBB SPECIFICATIONS. REPORTS MUST BE SUBMITTED (4) COPIES FOR EACH SYSTEM FOR
APPROVAL TO THE TENANT AND ARCHITECT. COPY OF REPORT MUST ALSO BE SUBMITTED TO
MALL LANDLORD. BALANCING COMPANY SHALL BE AN INDEPENDENT COMPANY AFFILIATED WITH
THE AMERICAN AIR BALANCING COUNCIL
TESTING AND ADJUSTING
CONTRACTOR SHALL DEMONSTRATE OPERATION OF SYSTEM TO FULL SATISFACTION OF TENANT,
SHALL BALANCE AIR FLOW IN ACCORDANCE WITH AIR QUANTITIES ON DRAWINGS AND SHALL
RECORD VOLUME READINGS IN ACCORDANCE WITH ASHRAE AND PROVIDE SAME TO TENANT.
OPERATION AND MAINTENANCE DOCUMENTATION MUST BE PROVIDED TO THE OWNER THAT
INCLUDES AT LEAST THE FOLLOWING INFORMATION:
A. EQUIPMENT CAPACITY (INPUT AND OUTPUT) AND REQUIRED MAINTENANCE ACTIONS.
B. EQUIPMENT OPERATION AND MAINTENANCE MANUALS.
C. HVAC SYSTEM CONTROL MAINTENANCE AND CALIBRATION INFORMATION, INCLUDING WIRING
DIAGRAMS, SCHEMATICS, AND CONTROL SEQUENCE DESCRIPTIONS; DESIRED OR FIELD —
DETERMINED SET POINTS MUST BE PERMANENTLY RECORDED ON CONTROL DRAWINGS, AT
CONTROL DEVICES, OR, FOR DIGITAL CONTROL SYSTEMS, IN PROGRAMMING COMMENTS.
D. COMPLETE NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE.
DRAWINGS
THIS CONTRACTOR SHALL SUBMIT 4 COPIES OF RECORD DRAWINGS SHOWING EXACT LOCATIONS
OF THE UNIT, DUCTS, DIFFUSERS, ETC., FOR FUTURE REFERENCE.
UPON COMPLETION OF INSTALLATION, SUBMIT A CERTIFIED TEST AND BALANCE REPORT TO
LANDLORD FOR REVIEW AND APPROVAL THE REPORT SHALL INCLUDE ALL AIR FLOW BALANCE
DATA.
MECHANICAL GENERAL NOTES
PRIOR TO SUBMITTING A PROPOSAL, THE CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY
INSPECT EXISTING CONDITIONS TO ENSURE THAT WORK REPRESENTED ON DRAWINGS CAN BE
INSTALLED AS INDICATED. COORDINATE DISCREPANCIES BETWEEN DOCUMENTS AND FIELD
CONDITIONS WITH THE TENANT OR HIS AUTHORIZED AGENT. COORDINATE THE EXTENSION,
MODIFICATION, FINAL CONNECTION AND TESTING OF ALL UTILITIES OR INTERFACED SYSTEMS
WITH THE LANDLORD'S FIELD REPRESENTATIVE.
ARRANGE WITH LOCAL AND STATE AUTHORITIES AND UTILITY COMPANIES FOR PERMITS, FEES,
AND SERVICE CONNECTIONS FOR TEMPORARY AND PERMANENT WATER, SANITARY SEWER, STORM
AND INDUSTRIAL WASTE SERVICES IF APPLICABLE, VERIFYING LOCATIONS AND ARRANGEMENT,
AND PAY ALL CHARGES INCLUDING INSPECTIONS.
DRAWINGS ARE GENERALLY DIAGRAMMATIC AND ARE INTENDED TO ENCOMPASS A SYSTEM THAT
WILL NOT INTERFERE WITH THE STRUCTURAL AND ARCHITECTURAL DESIGN OF THE BUILDING.
COORDINATE WORK TO AVOID INTERFERENCE BETWEEN PIPING, EQUIPMENT, ARCHITECTURAL, AND
STRUCTURAL WORK.
NO COMPONENTS MAY BE ABANDONED IN PLACE. ALL COMPONENTS THAT ARE NOT REUSED
MUST BE REMOVED AND DISPOSED OF. COORDINATE DISPOSAL OF ALL REMOVED EQUIPMENT
WITH THE LANDLORD.
PROVIDE THE ENTIRE OPERATING SYSTEM AND ITS COMPONENT ITEMS OF EQUIPMENT FREE OF
OBJECTIONABLE VIBRATION OR NOISES. REFER TO ASHRAE HANDBOOK FOR RECOMMENDED
NOISE CRITERIA (NC) UNLESS OTHERWISE NOTED. STATICALLY AND DYNAMICALLY BALANCE
ROTATING EQUIPMENT, AND MOUNT OR FASTEN SO VIBRATION IS PRODUCED OR TRANSMITTED
TO OR THROUGH THE BUILDING. IF OBJECTIONABLE NOISE OR VIBRATION IS PRODUCED OR
TRANSMITTED TO OR THROUGHOUT THE BUILDING STRUCTURE BY EQUIPMENT, PIPING, DUCTS
OR OTHER PARTS OF WORK, RECTIFY SUCH CONDITIONS AT NO ADDITIONAL COMPENSATION.
PROVIDE ADDITIONAL BALANCING DEVICES REQUIRED FOR COMPLETE SYSTEM BALANCING
INCLUDING BUT NOT LIMITED TO VOLUME DAMPERS, VALVES, AND SHEAVES OR PULLEYS AT
FANS.
VERIFY THE SIZE, LOCATION, AND CONDITION OF THE EXISTING PIPING BUILDING MANAGEMENT
SYSTEM CONNECTION POINTS, AND OUTSIDE AIR CONNECTIONS. REPLACE EXISTING
COMPONENTS IF THEY ARE INADEQUATE FOR THE NEW REQUIREMENTS.
COORDINATE ACCESS TO LANDLORD'S EQUIPMENT (VAV BOXES, FIRE DAMPERS, VOLUME
DAMPERS, ETC) WITH LANDLORD'S GENERAL CONTRACTOR /REPRESENTATIVE
TENANT G.C. SHALL ENGAGE LANDLORD'S DESINATED SEPARATE TEMPERATURE CONTROL
CONTRACTOR FOR FINAL SET —UP OF SYSTEM(S) OPERATIONS AND AIR BALANCING. GIVE ONE
COPY OF BALANCING REPORTED TO LANDLORD'S BUILDING ENGINEER.
_ F _