DESCRIPTION OF WORK:
PROVIDE VAV UNIT AND AIR DISTRIBUTION SYSTEM FOR A RETAIL STORE
Value of Mechanical: $20,000.00
Type of Fire Protection:
Furnace: <100K BTU
>100K BTU
Floor Furnace
Suspended/Wall/Floor Mounted Heater
Appliance Vent
Repair or Addition to Heat/Refrig /Cooling System....
Air Handling Unit <10,000 CFM
>10,000 CFM
Evaporator Cooler
Ventilation Fan connected to single duct
Ventilation System
Hood and Duct
Incinerator: Domestic
Commercial/Industrial
CitAbf Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
MECHANICAL PERMIT
EQUIPMENT TYPE AND QUANTITY
0
0
0
0
0
0
0
0
0
1
0
0
0
0
* *continued on next page **
•
Permit Number:
Issue Date:
Permit Expires On:
Phone:
Phone: 206 341 -9875
Phone: 425 - 486 -4327
Expiration Date: 05/27/2008
M08 -094
04/24/2008
10/21/2008
Fees Collected: $395.00
International Mechanical Code Edition: 2006
Boiler Compressor:
0 -3 HP /100,000 BTU 0
3 -15 HP /500,000 BTU 0
15 -30 HP /1,000,000 BTU.. 0
30 -50 HP /1,750,000 BTU.. 0
50+ HP /1,750,000 BTU 0
Fire Damper 0
Diffuser 14
Thermostat 1
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment 1
doc: IMC -10/06 M08 -094 Printed: 04 -24 -2008
Permit Center Authorized Signature:
Signature:
Print Name.
doc: IMC - 10/06
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
I hereby certify that I have read and ex n d this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied w , ' hether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
constructioAor the performance of work,/`I am authorized to sign and obtain this mechanical permit.
•
Permit Number: M08 -094
Issue Date: 04/24/2008
Permit Expires On: 10/21/2008
7i
bi)J? Date: Oq l 9)-
Date: L 1 — z — D
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
M08 -094 Printed: 04 -24 -2008
•
City of Tukwila
Parcel No.: 6364200010
Address: 2646 SOUTHCENTER MALL TUKW
Suite No:
Tenant: ZUMIEZ
1: ** *BUILDING DEPARTMENT CONDPITONS * **
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
PERMIT CONDITIONS
Permit Number: M08 - 094
Status: ISSUED
Applied Date: 03/28/2008
Issue Date: 04/24/2008
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431- 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
6: Manufacturers installation instructions shall be available on the job site at the time of inspection.
7: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431 - 3670).
8: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
9: ** *FIRE DEPARTMENT CONDITIONS * **
10: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
11: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
12: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
13: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
14: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
15: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
doc: Cond -10/06
M08 -094 Printed: 04 -24 -2008
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
•
16: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
17: An electrical permit from the City of Tukwila Building Department Permit Center (206- 431 -3670) is required for this
project.
18: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
19: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
20: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: Cond - 10/06
* * continued on next page **
M08 -094 Printed: 04 -24 -2008
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating
construction or the performance of work.
Signature:
Print Name: — c) t"A' 5 u LP r
doc: Cond -10/06
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
•
gctiZ))–■ Date: ` CI ° S
M08 -094 Printed: 04 -24 -2008
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.ci.tukwila.wa.us
Tenant Name: ZLIM 1 E--
Name: bAJ ip M FA -1-1`'
Mailing Address: 2.101 of -(`^ AVM -- 211
E -Mail Address: m or u An or rli,va re, CoM
Company Name: 1
Contact Person:
E -Mail Address:
Contractor Registration Number:
Company Name: MV R Pla'( 1'A( , f'S
Mailing Address: 21 O I �' /ids 211
Contact Person: DA" ' Mug-M-1 Y
E -Mail Address: a 14", N_ urp % '12 re 5 . CnM
Q:Applications \Forms-Applications On Linel3 -2006 - Permit Applieation.doc
Revised: 9 -2006
bh
City
Building Permit No.
Mechanical Permit No.
Kock oq
Plumbing/Gas Permit No.
Public Works Permit No. (�
Project No. P o �'
(For office use only)
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
SITE LOCATION
`` King Co Assessor's Tax No.:
Site Address: Zb4 c G>~pJT — Mau_ 4 .LL- Suite Number: Floor: Z
New Tenant: t54 Yes ❑ ..No
Property Owners Name: \ 1 4 t�t� (o 'OF.Arf CIO 1 .
Mailing Address: U(, 01 VJI l SI4 tgz K D t KS 1100 LoS A4 L-C' CA gDOZS
t city r State Zip
CONTACT PERSON - who do we contact when your permit is ready to be issued
Day Telephone: (206) 41 — 15
-Airy el e 121
City
Fax Number: ( 7 c,) 344 – 91 41-
State Zip
GENERAL CONTRACTOR INFORMATION —
(Contractor Information for Mechanical (pg 4) for Plumbing and Gas Piping (pg 5))
Mailing Address:
City
Day Telephone:
Fax Number:
Expiration Date:
State
Zip
ARCHITECT OF RECORD - All plans must be wet stamped by Architect of Record
Lill L-lr \NA el $1 z 1
State Zip
Day Telephone: (Z06) %j I — 9q
Fax Number: (.206 > 3L1 I —11 1
ENGINEER OF RECORD - All plans must be wet stamped by Engineer of Record
Company Name: HAF -P-1 SoiN1 ttI)G1• -1 d' QS A .S
Mailing Address: tr' 0 1 S*PI "A' ?so-v:7 , w (L.4..5- AID. '41412
City State Zip
Contact Person: '- '(AI.I le-A1' Day Telephone: (441) W1 - o3.G
E -Mail Address: (' , r a y N ✓ Lenr1 sM -Frencl, , (oM Fax Number: CI-P 2i3 - Lj 4'b
Page 1 of6
Unit Type:
Qty
Unit Type:
Qty
Unit Type:
Qty
Boiler /Compressor:
Qty
Furnace <100K BTU
Air Handling Unit >10,000
CFM
Fire Damper
0 -3 HP /100,000 BTU
Furnace >100K BTU
Evaporator Cooler
Diffuser
i4
3 -15 HP /500,000 BTU
Floor Furnace
Ventilation Fan Connected
to Single Duct
1
1
Thermostat
15 -30 HP /1,000,000 BTU
Suspended/Wall/Floor
Mounted Heater
Ventilation System
Wood/Gas Stove
30 -50 HP /1,750,000 BTU
Appliance Vent
Hood and Duct
Emergency
Generator
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Refrig /Cooling
System
Incinerator - Domestic
Other Mechanical
Equipment
I
Air Handling Unit
<10,000 CFM
Incinerator — Comm/Ind
ti
MECHANICAL CONTRACTOR INFORMATION
Company Name: T '
Mailing Address:
Use: Residential: New .... ❑ Replacement .... ❑
Commercial: New .... Er Replacement .... ❑
Indicate type of mechanical work being installed and the quantity below:
Q:MpplicabensTonns- Applications On Lane \3 -2006 - Pemut Apphcation.doc
Revised: 9 -2006
bh
MECHANICAL PERMIT INFORMATION - 206 -431 -3670
City State Zip
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date:
Valuation of Mechanical work (contractor's bid price): $ 20, Ot' 2
Scope of Work (please provide detailed information): p#- -O'd 1 p . /AV t )1J iT - AIR 1Z 1 I .01 I O •3
�`:TENI C.0(r. A iZtTAh S;tn(z�
Fuel Type: Electric Er Gas .... ❑ Other:
Page 4 of 6
PERMIT APPLICATION NOTES — Applicable to all permits in this application
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWN OR AUTHO
Signature:
Building and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
Plumbing Permit
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing Code (current edition).
Print Name: A M 1)
Mailing Address: '2
Date Application Accepted:
Date:
Day Telephone: '2406o 34 — '1 8lS
v
Q:\Applications \Forms - Applications On Line \3 -2006 - Permit Application.doc
Revised: 9 -2006
bh
City
Date Application Expires: V t W
2
State Zip
Staff Initials: I
Page 6 of 6
RECEIPT NO: R08 -01329
Initials: JEM
User ID: 1165
Payee: FUTURE BUILDERS, INC.
SET ID: 0424 SET NAME: ZUMIEZ
SET TRANSACTIONS:
Set Member Amount
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
D08 -137 2,174.50
D08 -157 93.00
77M0; 4 316.00
PG08 -097 140.00
TOTAL: 2,723.50
TRANSACTION LIST:
Type Method Description
Payment Check 3065
ACCOUNT ITEM LIST:
Description
BUILDING - NONRES
MECHANICAL - NONRES
PLUMBING - NONRES
STATE BUILDING SURCHARGE
SET RECEIPT
TOTAL:
Payment Date: 04/24/2008
Total Payment: 2,723.50
Amount
2,723.50
2,723.50
Account Code Current Pmts
000/322.100 2,258.50
000.322.102.00.0 316.00
000.322.103.00.0 140.00
000/386.904 9.00
TOTAL: 2,723.50
1582 04/24 9711 TOTAL 2723.50
RECEIPT NO: R08 -00957
User ID: 1165
Payee: MURPHY VAREY, P.S.
SET TRANSACTIONS:
Set Member Amount
ACCOUNT ITEM LIST:
Description
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http.• / /www. ci. tukwila. wa. us
Initials: JEM Payment Date: 03/28/2008
SET ID: S000000989 SET NAME: Tmp set/Initialized Activities
D08 -157 57.53
ELO 328 143.50
aiSITOVr 79.00
PGO8 -097 32.00
TOTAL: 312.03
TRANSACTION LIST:
Type Method Description Amount
Payment Check 12013 312.03
TOTAL: 312.03
ELECTRICAL PLAN - NONRES
PLAN CHECK - NONRES
SET RECEIPT
Total Payment: 312.03
Account Code Current Pmts
000.345.832.00.0 143.50
000/345.830 168.53
TOTAL: 312.03
17 .7R
Project:
ZLis i I FS
Type of Inspection:
° s'si 14L •
Address:
26 4 wt A I(
Date Called:
Special Instructions:
Date Wanted:
- 7-2W
-
a.m.
Requester:
Phone No:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
M Of°3-c
PERMIT NO.
(206)431 -3 7
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
of -J
n' -P .r v irj k 0 ? `F
(TeeLIPANny r'+ ti nts
Date:
7-zy-
¢0.00 • EINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paN at .300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt •.:
'Date:
Project: •
ZL'r L Z.
Ty e Inspection:
/vq7it._t_ S'1, (..4- cLo cNs1
Address:
24 to
1- —
Date Called:
Special Instructions:
Date Wanted: 7 ! 1 i /
c3
a.m.
p.m.
Requester:
Phone No:
/
l
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION I?'"
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
El Approved per applicable codes. ❑ Corrections required prior to approva
COMMENTS:
\100 9,4444ri, AktA .lS r b . 71 — r
t
Ins pecto
INSPECTION RECORD
Retain a copy with permit
[Pate:
$60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
'Date:
COMMENTS:
Sprinklers:
Fire Alarm;_
, r, 1
( Doi - 7' ",1
- 6 IL-
17 c u
Contact Person:
Special Instructions:
Sprz. ; r IL_ .0 i " -- OCIN
— 0 i
Project: 7 v fr , ( L
Sprinklers:
Fire Alarm;_
Type of Inspection:
,; / 1'12 .4r.w -/ jINc.IL / i -4_,a+
Address: f iat -. t j C
Suite #:
rn
0..4_._-
Contact Person:
Special Instructions:
Phone No.:
Needs Shift`Inspection:
Sprinklers:
Fire Alarm;_
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
INSPECTION NUMBER
Approved per applicable codes.
Word /Inspection Record Form.Doc
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA FIRE DEPARTMENT
1/13/06
t � I pO
o S - 22 0
PERMIT NUMBERS
444 Andover Park East, Tukwila, Wa. 98188 206 - 575 -4407
Corrections required prior to approval.
In_ '.r:
u■i
r> 1Z-
Date:
2c
H
$80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
City of Tukwila Finance Department. CaII to schedule a reinspection.
T.F.D. Form F.P. 113
ACTIVITY NUMBER: M08 -094 DATE: 03 -28 -08
PROJECT NAME: ZUMIEZ
SITE ADDRESS: 2646 SOUTHCENTER MALL
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # After Permit Issued
DEPARTMENTS:
Bui a ng Division
Public Works
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete g Incomplete n
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
LETTER OF COMPLETENESS MAILED:
TUES /THURS ROUT G:
Please Route Structural Review Required
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Documents/routing slip.doc
2 -28 -02
• PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
n
7 l Mvvc,
Fire Prevention Al
Structural
Planning Division
Permit Coordinator
n
n
DUE DATE: 04-01-08
Not Applicable n
No further Review Required
DATE:
n
DUE DATE: 04-29-08
Approved n Approved with Conditions VI Not Approved (attach comments) n
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
License Information
License
TNTMEL *011 K7
Licensee Name
T -N -T MECHANICAL LLC
Licensee Type
CONSTRUCTION CONTRACTOR
UBI
601950443
Ind. Ins. Account Id
PARTNER/MEMBER
Business Type
LIMITED LIABILITY COMPANY
Address 1
22833 BOTHELL - EVERETT HWY 1164
Address 2
City
BOTHELL
County
SNOHOMISH
State
WA
Zip
98021
Phone
4254864327
Status
ACTIVE
Specialty 1
GENERAL
Specialty 2
UNUSED
Effective Date
5/27/1999
Expiration Date
5/27/2008
Suspend Date
Separation Date
Parent Company
Previous License
Next License
Associated License
Business Owner Information
Name
Role
Effective Date
Expiration Date
HARRISON, SCOTT
PARTNER/MEMBER
01/01/1980
Impaired
Date
LIBSACK, JERI
PARTNER/MEMBER
01/01/1980
DEVELOPERS
SURETY &
INDEM CO
Bond
Information
Bond
Bond
Company
Name
Bond
Account
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Bond
Amount
Received
Date
#3
DEVELOPERS
SURETY &
INDEM CO
850223C
05/27/2002
Until
Cancelled
$12,000.00
03/18/2000
Look Up a Contractor, Electra or Plumber License Detail
Washington State Department of Labor and Industries
General/Specialty Contractor
A business registered as a construction contractor with L &I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Page 1 of 2
https: // fortress. wa. gov /lni/bbip /printer.aspx ?License= TNTMEL *011 K7 04/24/2008
HVAC SYSTEM LOAD SUMMARY
MARK
TENANT NAME: Zumiez SPACE #
2115
SQ. FT.:
3193
EF -1
NUTONE
QT100LM
38
3.5
DESIGN CONDTIONS:
SUMMER: 79T D.B. & 647 W.B. (Outside), 75T (Inside)
WINTER: 26T D.B. (Outside), 70T (Inside)
120/1/60
GENERAL INFORMATION (ALL UNITS):
1. FAN OPERATION CONTROLLED VIA MOTION SENSOR.
2. CONTRACTOR SHALL CHOOSE A SCHEDULED UNIT OR A COMPARABLE
UNIT OF A DIFFERENT MANUFACTURER.
LOAD CALCULATIONS: (below ceiling) COOLING (BTUH)
Sensible: Latent:
WALL: 0 0
Total:
0
HEATING
(BTUH)
0
GLASS: 0 0
0
0
ROOF: 0 0
0
0
PEOPLE: 19814 16018
35832
0
VENTILATION: 0 0
0
0
LIGHTS: 26905 0
26905
0
MISCELLANEOUS: 1706 0
1706
0
Total: 48425 16018
64443
0
EXHAUST FAN SCHEDULE
MARK
MANUFACTURER /
MODEL
INPUT WATTS
SONES
ESP
CFM
V /PH /HZ
EF -1
NUTONE
QT100LM
38
3.5
0.375
100
120/1/60
GENERAL INFORMATION (ALL UNITS):
1. FAN OPERATION CONTROLLED VIA MOTION SENSOR.
2. CONTRACTOR SHALL CHOOSE A SCHEDULED UNIT OR A COMPARABLE
UNIT OF A DIFFERENT MANUFACTURER.
EF1 100 CFM, MOUNT ABOVE
CEIUNG. CONNECT 6" TO
EXISTING DUCTWORK
CDa- --
6
100
6 "o
SPIN —IN FITTINGS
W /SCOOPS ARE
NOT ACCEPTABLE
45' LEAD IN
MARK
CD1
SAW
TG
SERVICE
SUPPLY
SUPPLY
TRANSFER
REF PLANS FOR
i -
RUNOUT SIZES
�I
BRANCH DUCT FITTING
NTS 08.13.01
CD1
6"
100
1
6 "0
1/4" = 1' -0"
1
CONNECT TO EXISTING
LANDLORD SUPPLY
DUCT. FIELD VERIFY
EXACT LOCATION.
6"o
6 ° s
CD1
6"
100
HVAC PLAN
(15.100)
r200
VAV1
MOUNT AS
HIGH AS
POSSIBLE
MOUNT AS
HIGH AS
POSSIBLE
MANUFACTURER/
MODEL
TITUS / TMSA
TITUS / 300RS
TITUS / 50F
W
J
AIR DEVICE SCHEDULE
200
STYLE
CEILING DIFFUSER
DUCT MOUNTED
WALL REGISTER
BRANCH DUCT
PIVOT BUSHING
INSULATION STAND
OFF BRACKET
N TS
FRAME
TYPE
SURFACE
SURFACE
SURFACE
FACE
SIZE
12 X 12
REF DWGS
REF DWGS
GENERAL INFORMATION (ALL DEVICES):
1. CONTRACTOR MUST SELECT SCHEDULED MATERIALS OR APPROVED EQUAL.
ACCEPTABLE MANUFACTURERS ARE TITUS, CARNES, METAL —AIR, AND J & J.
NOTES:
1. ALL STEEL CONSTRUCTION.
2. ALL ALUMINUM CONSTRUCTION.
3. BRANCH DUCT SIZE SHALL BE SAME AS NOTED DIFFUSER NECK SIZE UNLESS NOTED OTHERWISE.
4. REFER TO ARCHITECTURAL SHEETS FOR DIFFUSER COLOR.
5. PROVIDE NECK FOR DUCT CONNECTION.
6. OPPOSED BLADE DAMPER IN NECK
7. SUPPORT REGISTER INDEPENDENT OF DUCTWORK.
MEI
MANUAL DAMPER
05.17.04
NOTES
2, 3, 6, 7
1, 4, 5, 6
2
H-6
MARK
VAV -1
ACCESSORIES:
A. DOUBLE WALL INSULATION— DENSITY.
B. 24 VAC CONTROL POWER TRANSFORMER.
C.
D.
E.
F.
G.
POWER FUSE.
FACTORY DISCONNECT SWITCH.
DUCT SENSOR.
FACTORY ACTUATOR.
DIFFERENTIAL PRESSURE FLOW TRANSDUCER..
NOTES:
1. CONTRACTOR SHALL CHOOSE A SCHEDULED UNIT OR A COMPARABLE UNIT OF A
DIFFERENT MANUFACTURER.
PIVOT BUSHING
18 GA. DAMPER
LOCKING QUADRANT
LEVER HANDLE
200
Ld
r'n r -- r
MANUFACTURER/
MODEL
TRANE /VCEF
VARIABLE AIR VOLUME UNIT
200
DAMPER SIZE
14" ROUND
n
COOLING
CFM
2600
PaNaiir
MINIMUM
CFM
850
PER 2006 IMC SECTION 606
Install smoke detector to shut down air distribution
by VAV's when the total combined C F M of all
VAV's (to include other tenants) sharing the same
plenum space exceeds 2000 CFM.
(See IMC 606.2.2 for approved method of detection)
•
HEATING
CFM
1600
15
200
KW
t
ELEC.
V /PH
480/3
ACCESS.
& NOTES
A —G, 1
REMOVE ALL EXISTING EQUIPMENT AND ASSOCIATED
DUCTWORK, AIR DEVICES AND CONTROLS NOT BEING
REUSED PER PLANS. CAP OFF AND REMOVE ALL
DWV AND WATER PIPING NOT BEING REUSED.
COORDINATE ALL DEMOLITION WITH LANDLORD.
MECHANICAL SYMBOLS
I><1
Fa]
CD
12"
450
L'JRH1
200
SAW
12
225
TYP OF 10
1
DEMOLITION NOTES
RECTANGULAR DUCT 18" WIDE BY 12"
DEEP
12" DIAMETER ROUND DUCT
SUPPLY DUCT IN SECTION
RETURN OR EXHAUST DUCT IN SECTION
ELBOW WITH TURNING VANES
ROUND (OR OVAL) ELBOW
SUPPLY AIR DIFFUSER WITH ROUND
SUPPLY DUCT
RETURN OR EXHAUST AIR DIFFUSER WITH
ROUND DUCT
DIFFUSER OR GRILLE TYPE
BRANCH DUCT & NECK SIZE
CFM
THERMOSTAT
KEYED NOTES
15.100 NEW THERMOSTAT PER MALL REQUIREMENTS.
COORDINATE LOCATION WITH TENANT AND CONTROLS
WITH MALL BUILDING AUTOMATED SYSTEM. MOUNT
46" A.F.F.
HVAC NOTES
1. EACH CONTRACTOR IS RESPONSIBLE FOR HAVING
THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
SPECIFICATIONS AS THEY RELATE TO THIS WORK.
NO ADDITIONAL COMPENSATION SHALL BE
ALLOWED DUE TO LACK OF THIS KNOWLEDGE.
2. PROVIDE ALL MATERIALS FOR A COMPLETE
INSTALLATION IN ALL RESPECTS READY FOR
INTENDED USE AND IN STRICT ACCORDANCE WITH
STATE AND LOCAL CODES AND MANUFACTURER'S
RECOMMENDATIONS.
3. SPRINKLER HEAD AND LIGHTING FIXTURE
LOCATIONS TAKE PRECEDENCE OVER DIFFUSER
LOCATIONS. COORDINATE WITH ELECTRICAL
CONTRACTOR AND FIRE PROTECTION
CONTRACTOR.
4. DUCTWORK IDENTIFICATION AND INSTALLATION TO
ADHERE TO GOVERNING CODES.
5. DUCT SIZES INDICATED ARE INSIDE CLEAR
DIMENSIONS. IF DUCT LINING IS REQUIRED,
INCREASE DUCT SIZE TO MAINTAIN ORIGINAL
INSIDE DIMENSIONS.
6. FLEXIBLE DUCTWORK MAINS ARE NOT PERMITTED.
PROVIDE MAXIMUM 5' -0" FLEXIBLE DUCT
CONNECTIONS TO CEILING DIFFUSERS.
7. TYPICAL BRANCH FITTING DETAILS ARE
APPLICABLE THROUGHOUT.
8. FURNISH AND INSTALL VOLUME /BALANCE
DAMPERS AT ALL BRANCH DUCTS TO DIFFUSERS.
LOCATE DAMPERS A MINIMUM 4' -0" AWAY FROM
DIFFUSERS. PROVIDE ACCESS DOORS AS
REQUIRED.
9. PROVIDE FIRE SEAL WHERE PIPING AND
DUCTWORK PENETRATE FIRE RATED ASSEMBLY.
10. PROVIDE SEISMIC BRACING BASED ON
APPROPRIATE SEISMIC ZONE REQUIREMENTS PER
SMACNA PUBLISHED SEISMIC DETAILS, LOCAL
AND NATIONAL CODES. CONTRACTOR'S
RESPONSIBILITY INCLUDES STRUCTURAL
ENGINEER'S CERTIFICATION ON DETAILS
SUBMITTED FOR PERMITTING.
11. INSTALL VTR'S, EXHAUST FANS, AND FLUES A
MINIMUM 5' -0" FROM PARAPET OR OUTSIDE
WALL AND 10' —O" MINIMUM FROM EQUIPMENT
WITH OUTSIDE AIR INTAKE.
12. ALL TEMPERATURE SENSORS, FAN SWITCHES,
AND SPEED CONTROLS SHALL BE MOUNTED 43
INCHES ABOVE THE FLOOR FOR ADA
ACCESSIBILITY.
13. PROVIDE A COMPLETE TEST AND BALANCE FOR
HVAC SYSTEM. TEST TO BE PERFORMED BY
MALL APPROVED TEST AND BALANCE COMPANY.
AIR BALANCE SHALL BE WITHIN 10% OF
SCHEDULED AIRFLOWS.
14. PROVIDE SHEET METAL COLLAR WHERE
DUCTWORK PENETRATES DEMISING WALL.
15.ALL DUCTWORK TO BE GALVANIZED SPIRAL
DUCTWORK. USE SILICONE DUCT SEALANT IN
LIEU OF VISIBLE HARDCOAT SEALANT.
SEPARATE PERMIT
REQUIRED FOR:
❑ Mechanical
Electrical
, , Iumbing
L Gas Piping
City of Tukwila
St DING DIVISION
FILE COPY
Permit No.
Piar review approval is subject to errors and omissions.
Approval of construction documents does not authorize
the violation of any adopted code or ordinance. Receipt
of approved Field C atld ditions is wedged:
By
City of Tukwila
BU LD N UV/WIN
REVIEWED FOR
CO DE COMPLIANCE i
APPROVED
AP R 1 I �2n0/
, ,, Of Tukwila 1
BUILDING DIVISIOi'j
REVISIONS -- 1
No changes shall be m'aria to thn srorA
of work without prior approval of
Tukwila Building Division 1
I NOTE: Revisions will require a new plan slshm. ”. 1
and may include additional plan re'H'. fnes
CITY OF TUKwuLA
MAR 2 8 2008
PERMIT CENTER
zumez
SOUTScENTER MALL
SPACE # 2n5
633 Svursc»i
SEATTLE, WA 98188
MURPHY VAR.EYPS
DAVID J. MURPHY, AIA
uomNags Arm Elcarg 1a
Arms, Y1Iwcz . ga>u
T: so6. .9875
F :10s.W.9Pn
E: m.lfssisiYassao.
Harrison French and
Associates
809 S.W. "A" Street
Bentonville, AR 72712
(479) 273 -7780
fax (479) 273 -9436
PROJECT NUMBER: 05 -08 -02008
ZUMIEZ STORE NUMBER: 19
ISSUED FOR:
PRELIMINARY MALL
REVIEW
DATE:
02 -08 -08 PRELIMINARY MALL REVIEW
SHEET TITLE:
HVAC PLAN
SHEET NUMBER:
Mechanical Permit Plans Checklist
2004 W State Nonresidential Energy Code Compliance Form:
Project Address}
The following information is nery fn check a mechanical permd application for compliance with the mechanical requirements in the
vVashington State Nonresidential Energy Code.
Applicabliity Code 'Component
(yes, no, n.a.) Section
HVAC REIQIIIREIUIENTS (Sections 1401 -1424)
n,a.
yes
yes
n.a.
yes
yes
nee,
n,a.
n.a.
yes
yes
n.a.
n,a.
n.a.
n,a.
n.a.
n ,a.
yes
yes
yes
yes
n,a.
yes
yes
n,a.
n.a.
n,a.
n.a.
n .a.
n,a. }
ilk 1413.1
• 1413.3
tt 1 452
Zumiez
1411 Equipment performance
1411.4
1411.1
1411.1
1412 HVAC controls
53 1412.1 Temperature zones
14122 headband control
1412.3 Humidity control
1412.4 Automatic setback
• 1412.4.1 Dampers
1412.4.2 Optimum Start
1412.5 Heat pump confrol
1412.6
• 1412.7 Balancing
1422 Thermostat interlock
1423 Economizers
1413
1413.1
14132
1413.4
1414
1414.1
14142
1415.1
1416
1416.182
1416.3.2
1416.3.3
1415.4
1424
SERVICE WATER HEATING AND HEATED POOLS (Sections 1440 -1454)
1440
1441
1442
1443
1452
1453
1454
1454
Pkg. elec. htg.& clg.
Minimum efficiency
Combustion htg.
Combustion big.
Air economizers
Air Econo Operation
Vuttr Econo Operation
a ter Econo DoC
Integrated operation
Hie midrfication
Ducting systems
Duct searing Indicate sealing nec
Duct insulation indicate R -value of insulation on duct
Piping insulation ( Indicate R -value of insulation on piping
Completion Requirements
Drawings 8 Manuals
Air Balancing
Hydronic Balancing
Commissioning
Separate air sys.
Mechanical Completed and attached. Equipment schedule with types,
Summary Form klputloultaut, efficiency, cfm, hp, economizer
Service water htg.
Elec. writer heater
Shut -off controls
Pipe insulation
Heat Pump COP
Heater Efficiency
PncI heater controls
Pawl covers
Pools SO+ degrees
Information Required
List heat pumps on schedule
Equipment schedule wfh type, capacity, efficiency
h - dcate intermittent igrdicn, fluetdraft damper 8 Jacket loss
Indicate locations on plans
Include 5 degree deadband minimum
Indicate humidistat
Indicate thermostat with night setback and 7 dill. day types
indicate damper location and auto. controls & max. leakage
Indicate optimum start controls
Indicate microprocessor on thermostat schedule
intricate modulating or staged control
Indicate balancing features on plans
Indicate thermostat interlock on plans
Equipment schedule
Indicate 100% capability on schedule
Indicate 103% capacity at 45 degF db & 40 deg F wib
Indicate clg bad & water eCOnoe 8 clg tower performance
lncficate capabifrtyy for partial cooling
Indicate direct evap or fog atomization wI air economizer
hdicate requirement for record drawings and operation dons_
Indicate air system balance requirements
Indicate hydronic system balance requirements
Indicate requirements for commissioning and prelim. Report
Indicate separate systems on plans
Incicate R -10 insulation under tank
Indicate automatic shut -off
Indicate R -value of inulation on piping
Indicate minimum COP of 4.0
Indicate port heater efficiency
In Icate swich and 65 degree control
Indite vapor retardant cover
Indicate R -1 2 pool cover
If "no" is circled for any question, provide explanation:
Date
3/14/2000
Revised May 2005
ion Builds Department
g ep artment
on Plans Notes
2004 Washington Stole Nanresident"al Energy Cade Compliance Forms
iVl frztrticaI - General Requirements
1411.1 General: Equipment shall have a minimum performance at the
specified rating condi riot less an the values show n in Table 14-1A
through 14 -1 G. tfa nail onaltyrecognized certification program exists fora
product covered in Tables 14-1 A throu gh 14-16, and it includes provisions
for verification and challenge ofequipment effioienc}rratirtes.thenthe
product shall be fisted in the certification program.
Gas -ired and oil -fired forced air furnaces with input ratings . 225,0015
Been (pis Wulf) shall also have an intermittent ignition or interrupted device
(IID), and have ether mechanical draft [Including power venting)or a flue
d amper.Avent damper ran acceptable alternative to a flue damper fir
furnaces where combustion air is drawn from the conditioned space. All
furnaces with input ratings > 226 1100 13teth (Bra kW), including electric
fumaces,that are nat located within the conditioned space shall have
jacket losses not exceeding D.76% of the input rating.
1411.2 R Conditions: Cooling equipment shall be rated at ARlteet
c onditions and prooedurgs when available. Where no applicable
procedures exist. data shall be furnished bythe equipment manufacturer.
1411.3 Combination Space and Sere esWater Heating: For
combination space and service waterheaters with a principal function of
providing space heat, the Combined Peinual Efficiency(CAE)maybe
calculated byusing AS HRAE Standard 124-11:1131. Storage water heaters
used in combination space heat and water applications shall have
eerier en Energy FA&tar (EF) or a CAE of not less th an th a followin
1411.4 Packaged eiec#ric He end Cooling Equipment: Packaged
electric equipment providing both heating and cooling with a total oevfing
c apacity greater th an 20,000 Btu Ai shall be a heat pump.
Exception: Urrs equipment shaelters or cabinets used
solely far personal wireless service facilities.
9 412 Controls
1412.1 Temperature Controls: Each system shall be provided with at
It one temperature central device. Each zone shall be controlled by
individual thermostaticconteals responding to temperature w Min the zone.
Lid a minimum. each floor of building shall be considered as a separate
zone.
14122 Deadband Controls; tJUhen used to co ntrol bath comfortheating
and cooling, zo ne thermostatic controls shall be capable of deadband of
at least 5 degrees F within which the supply of heating and coaling energy
to the zone is shut off or reduced to a minimum.
Exceptions:
1. Special eeeupenvy,special usage, or code requirements
where deadband controls are not appropriate_
2. Buildings complying with Section 1141.4, ifin the proposed
building energy analysis, heating and coating thermcetel
setpoints are set to the same temperature between 7Q
degrees F and 73 degrees F inclusive, and assumed to be
constentthroughout the year.
3. Thermo stets that require manual changeover between
heatinng and caa5hg modes.
1412.3 Humidity Controls: Ile system is equipped with a means for
adding moisture ,a humidislat shall be provided.
1412.4 Setback and Shut -Off: H VAC systems shall be equipped with
automatic controls capable of accomplishing a reduction oferrergyuse
through control setback or equipment shutdown during periods of non -use
or alternate use of the spaces served bythe system. The automatic
oontmis shall have a minimum seven -day clack and be capable of being
set for seven different daytypes per week.
Exceptions:
1. Systems sewing areas which require continuous operation at
the same temperature setpoint.
2. Equipment with full Toad demands of2kW (OB20 9tu/h)or
less maybe controlled by readily acc ma nut I off -hour
controls.
1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets
serving conditioned spaces shall be equipped with dampers which close
a utomaticaliyw hen the system is affor upon power failure.
Exceptions:
1. Systems serving areas which require continuous operation.
2. Combustion air intakes.
3. Gravity lei onmotor'zed)dampere are acceptable in buildings
less than 3 stories in height.
4. Gravity(nonmotorized)dampers are acceptable in exhaust
and relief outlets in the first story and levels below the fast
stone ofbuildingsthree v rmore stories in height.
141242 Optimum Start Centrals: Heating and cooling systems with
design supply air cepecities exceeding 10,000 cfm shall have optimum
start controls. Optimum start oentrel5 shall be designed tc automatically
a djustthe start time of an HV Qsystemeach day to bring the space
desired occupied temperature levels immediately before scheduled
occupancy. The control algorithm shall, as minimum, be a function of the
difference between space temperature and occupied setpoint and the
amount oftime prierte scheduled occupancy_
1412.5 Heat Pump Controls: Unitary air coaled heat pumps shall Include
micraprocessor controls that minimize supplemental heat usage during
start- upset -up, and defter candelans. These controls shall anticipate
need for heat and use compression heating asthe fret stageofheet.
Controls shall indicate when supplemental heating is being used through
visual means (e.g., LED indicators).
1412.6 Combustion Healing Equipment Controls: Combustion heating
equipment with a capacity over 226.000 Blunt shall have modulating or
staged combustion control_
E;' eptions:
1. @oilers.
2_ Radiant Heaters.
1412.7 Balancing: Each air supply outlet or air or watertemtinal device
shall have a means for balancing. including but not Clinked to, dampers
temperature and pressure testoennections and balancing valves.
1413 Air Economizers
1413.1 iCperation:.Air economizers shall be of euternetically medulatirig
outside and return air dampers to provide 100 percent ofthe design supply
air as outside air to reduce or eliminate the need for mechanical cooling.
Water economizers shall be capable of providing the total co ncurrent
codling load served by-the connoted terminal equipment lacing airside
economizer, at outside air temperatures of45 dry - bulb /40 F wet -bulb
and below. For this calculation. all fdotor5 including solar and internal load
shall be the same a3 thvse used for peak load calculations, except forthe
outside temperatures.
Exception: Water economizers using air- coaled heat rejection
equipment may use a eeF dry -bulb outside airtemperature for
this calculation. This exception is limited to a maximum of 20 torts
per building.
1413.2 Docu d.tion: Water economizer plans submitted for apprvval
shall include the following information:
1. Maximum outside air conditions for which e4ronemizer is sized to
provide full cooling.
2. Design cooling load to be provided byecenemizeretthis outside
air condition.
3. Heat rejection and terminel equipment performance data
including model number, low rate , capacity. entering and leaving
temperature in full ecenomizer cooling mode.
1413.3 hfegr4ed Operation: Air economizers shall be capable of
providing partial cooling even when additional meohanivaI ovvlin is
required to meet the remainder of the cool ng load.
Exceptions:
1. Individual, direct expansion units that hat rated capacity
less than 055,000 Utulh and use nonintegrated economizer
o ontrolsthat preclude simultaneous operation of the
economizer and mechanical cooling.
2_ Water - cooled water chillers with waterside econamiz
1413.4 Humidrfication:'fen air economizer is required on a cooling
system for w hi ch humidification equipment Is to be provided to maintain
minimum indoor humidity levels, then the humidifier shall be of the
adiabatic type (direct evaporative media or fog atomization type).
Exceptions:
1. Health care facilities where WAC 246- 320 -526 allows only
steam injection hurniditiers in ductwork downstream of final
elters,1412.6 Combustion Heating Equipment Controls:
Combustion healing equipment with a capacity over 226,1300
Btu/h shall have modulating or eel ged combustion cone
2. Systems with water economizer
3. 100' outelde air systemswith no provisions fer air
recirculation to the central supplyfan.
4. Nenadirabatie humidifiers oumulativelysenang no more than
10% of buildings air economizer capacity es measured In
c fn . This refers to the system c f m serving rooms w ith stand
alone or duct mounted humidifiers.
1414 Ducting Systems
1414.1 Sealing: Ductwork which is designed to operate at pressures
above 1/2 inch water column static pressure shall be sealed in accordance
with Standard RS - 1e. Extent ofsealing required isas follows:
1_ Static pressure: 1/2 inch to 2 inches; seal transverse joints_
2. Static pressure: 2 inches to 3 inches :seal all transverse joints
and longitudinal seams.
3_ Static pressure: above 3 inches: seal all transverse jail
longitudinal seams and duct wall penetrations.
Duct tape and other pressure sensitive to pe shall no used as the
primary sea lam where ducts are designed to operate at static pressures of
1 inch W.C. or greater.
1414.2 hwlation: Duels and plenums that are constructed and function
as part of the building envelope,byseparating interior space from exterior
space, shall meet all applicable requirements of Chapter 13. The
requiremente Include insulation installation, moisture canto!, airleakage,
and building envelope insulation levels_ unheated equipment rooms with
combustion air louvers mu be isolated from the conditioned space by
insulating interior surfaces to a minimum of R -11 and any exterior
envelope surfaces per Chapter 13. Outside air ducts serving individual
supply air units with less than 2 ,800 cfm often! supply air caps city shall be
insulated to a minimum of R- -7 and are not considered building envelope.
Otheroutside air duct runs are considered building envelope until they,
1. connect to the heating or ma equipment, or
2_ are isolated from the exterior with an automatic shut- offdamper
complying with Section 14124.1.
On outside air ducts meet the above listed requirements,any runs
within conditioned space shall comply with Table 14-3 requirements.
Other ducts and plenums shall be thermally insulated per Table 14-6.
Exceptions:
1. Within the HVAC equipment.
2. Exhaust air duets not subject to condensation.
3. Exposed ductwork within a z one that serves that gene.
1415 Piping Systems
1415.1 hsulation: Piping shall bethermallyinsulated in accordance with
Table 146.
Exception: Piping installed within unitary HVAC equipment.
Water pipes outside the conditioned space shall be Insulated in
accordance with Washington State Plumbing Code MAC 51 -20)
1416 Completion Requirements (,Refre filREC Section f 415aadthe
Ekrlldiag Coirtmrssio!rirtg GenideL 'rres(itt6✓!•rst.eo'byer& Eaila'fng
Co diet l sia nine Assoclatian,farcae texl•and guieielings far bua•'dlreg
cempleuan and 'moat L;smalrfg re
1412.7 Balancing: Each air supply outlet or air or water terminal device
shall have a means for balancing, including but not limited to, dampers,
temperature and pressure test connections and balancing valves.
1413 Air Economizers
1413.1 Operation: Air economizers shall be of automatically modulating
outside and return air dampers to provide 100 percent of the design supply
air as outside air to reduce or eliminate the need for mechanical cooling.
Water economizers shall be capable of providing the total concurrent
cooling load served by the conneted terminal equipment lacking airside
economizer, at outside air temperatures of 45 ° F dry- bulb /40 ° F wet -bulb
and below. For this calculation, all factors including solar and internal load
shall be the same as those used for peak toad calculations, except for the
outside temperatures.
Exception: Water economizers using air - cooled heat rejection
equipment may use a 35 ° F dry-bulb outside air temperature for
this calculation. This exception is limited to a maximum of 20 tons
per building.
1413.2 Documentation: Water economizer plans submitted for approval
shall include the following information:
1. Maximum outside air conditions for which economizer is sized to
provide full cooling.
2. Design cooling load to be provided by economizer at this outside
air condition.
3. Heat rejection and terminal equipment performance data
including model number, flow rate, capacity, entering and leaving
temperature in full economizer cooling mode.
1413.3 Integrated Operation: Air economizers shall be capable of
providing partial cooling even when additional mechanical cooling is
required to meet the remainder of the cooling load.
Exceptions:
1. Individual, direct expansion units that have a rated capacity
less than 65,000 Btu/h and use nonintegrated economizer
controls that preclude simultaneous operation of the
economizer and mechanical cooling.
2. Water - cooled water chillers with waterside economizer.
1413.4 Humidification: If an air economizer is required on a cooling
system for which humidification equipment is to be provided to maintain
minimum indoor humidity levels, then the humidifier shall be of the
adiabatic type (direct evaporative media or fog atomization type).
Exceptions:
1. Health care facilities where WAC 246 - 320 -525 allows only
steam injection humidifiers in ductwork downstream of final
filters. 1412.6 Combustion Heating Equipment Controls:
Combustion heating equipment with a capacity over 225,000
Btu/h shall have modulating or staged combustion control.
2. Systems with water economizer
3. 100% outside air systems with no provisions for air
recirculation to the central supply fan.
4. Nonadiabatic humidifiers cumulatively serving no more than
10% of a building's air economizer capacity as measured in
cfm. This refers to the system cfm serving rooms with stand
alone or duct mounted humidifiers.
1414 Ducting Systems
1414.1 Sealing: Duct work which is designed to operate at pressures
above 1/2 inch water column static pressure shall be sealed in accordance
with Standard RS -18. Extent of sealing required is as follows:
1. Static pressure: 1/2 inch to 2 inches; seal transverse joints.
2. Static pressure: 2 inches to 3 inches; seal all transverse joints
and longitudinal seams.
3. Static pressure: above 3 inches; seal all transverse joints,
longitudinal seams and duct wall penetrations.
Duct tape and other pressure sensitive tape shall not be used as the
primary sealant where ducts are designed to operate at static pressures of
1 inch W.C. or greater.
1414.2 Insulation: Ducts and plenums that are constructed and function
as part of the building envelope, by separating interior space from exterior
space, shall meet all applicable requirements of Chapter 13. These
requirements include insulation installation, moisture control, air leakage,
and building envelope insulation levels. Unheated equipment rooms with
combustion air louvers must be isolated from the conditioned space by
insulating interior surfaces to a minimum of R -11 and any exterior
envelope surfaces per Chapter 13. Outside air ducts serving individual
supply air units with less than 2,800 cfm of total supply air capacity shall be
insulated to a minimum of R -7 and are not considered building envelope
Other outside air duct runs are considered building envelope until they,
1. connect to the heating or cooling equipment, or
2. are isolated from the exterior with an automatic shut - off damper
complying with Section 1412.4.1.
Once outside air ducts meet the above listed requirements, any runs
within conditioned space shall comply with Table 14 -5 requirements.
Other ducts and plenums shall be thermally insulated per Table 14 -5.
Exceptions:
1. Within the HVAC equipment.
2, Exhaust air ducts not subject to condensation.
3. Exposed ductwork within a zone that serves that zone.
1415 Piping Systems
1415.1 Insulation: Piping shall be thermally insulated in accordance with
Table 14 -6.
Exception: Piping installed within unitary HVAC equipment.
Water pipes outside the conditioned space shall be insulated in
accordance with Washington State Plumbing Code (WAC 51 - 26)
1416 Completion Requirements (Refer to NREC Section 1416 and the
Building Commissioning Guidelines, published by the Building
Commissioning Association, for complete text and guidelines for building
completion and commissioning requirements.)
2004 V State Nonresidential Energy Code Compliance Forms
Project Info
Project Address
Applicant Address:
Applicant Phone: 479 - 213 - ?W0
889 S_V_ A Street; Suite 2111, Bentonville, AR 72712
Project 1)0scripticrn
Briefly describe mechanical
system type and features.
❑ Includes PIar1
Compliance Option
Equipment Schedules
Applicant fume:
Cooling E guigrnent Schedule
Trani
Equip.
ID
TAY1
Brand Name
Heating E�quigment Schedule
Equip.
ID
VAV1
Fan Equipment Schedule
Equip.
ID
BHA
VCEF14
Model No
Zumiez
South Center Mali
Tukwila, VA
Greg Sehlutermam
Include documentation requiring compliance with commissioning requirements, Section 1416.
0 Simple System i Cornplex System ° Systems Analysis 0 Clear
(See Decision Flowchart (Dyer) for qual'rfications. Use separate MECH -SUM for simple & complex systems.)
The following information is required to be incorporated with the mechanical equipment schedules on
the plans. For projects without plans, fill in the required information below.
Capacity
Bluhi
55F air
Total CFM
2600
OSA CFM
or Econo?
SEER
or EER
Dart
1 If available. 2 AS tested according to Table 14 through 14 3 I required_ e ' COP, HSPF, Combustion Efficiency, or AFUE, as
applicable. $ Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS).
REVIEWED CODE COMPLIANCE
APPROVED
Al R 1 0 200B
City Of Tukwila
BUII DIN DIVISION
g
IPLV
Revised May 2005
3/14/2003
For Building Dept. Use
Location
stockroom
Trace
Brand Nam&
Model No.
VCEF14
Capacity
Etu 1i
Total CFM
1600
OSA cfm
or Canoe
input Btuh
51195
Efficiency
RECEIVED
CITY OF TUKWILA
MAR 2 8 2008
PERMIT CENTER
100.1100
Brand Name
Model No.
CFM
sP
HPiDHP
Flow Control'
Location of Service
zumuez
SOu'1'HCENTER MALL
SPACE # 2115
633 SouncENrxR
SEATTLE, WA 98188
MURPHY VAREYps
DAVID J. MURPHY, AIA
amt Nora dmtni Born is
flume lr1arcmer 98m
1: 106 . sp . 9
F: 106.34.9m
Sr v. lifinairriruccont
Harrison French and
Associates
809 S.W. "A" Street
Bentonville, AR 72712
(479) 273 -7780
fax (479) 273-9436
DATE:
141
02 - - PRELIMINARY MALL REVIEW
ISSUED FOR:
PROJECT NUMBER: 05 - - 02008
ZUMIEZ STORE NUMBER: 19
PRELIMINARY MALL
REVIEW
SHEET TITLE:
1 EXPIRES: 02/23/10 ,
ENERGY
CODE FORMS
SHEET NUMBER:
M2
EF
CAE
z 50 gal storage
0.68
0.71
50 to 70 pal storage
0.57
0.71
> 70 pal sterape
0.56
0.70
Mechanical Permit Plans Checklist
2004 W State Nonresidential Energy Code Compliance Form:
Project Address}
The following information is nery fn check a mechanical permd application for compliance with the mechanical requirements in the
vVashington State Nonresidential Energy Code.
Applicabliity Code 'Component
(yes, no, n.a.) Section
HVAC REIQIIIREIUIENTS (Sections 1401 -1424)
n,a.
yes
yes
n.a.
yes
yes
nee,
n,a.
n.a.
yes
yes
n.a.
n,a.
n.a.
n,a.
n.a.
n ,a.
yes
yes
yes
yes
n,a.
yes
yes
n,a.
n.a.
n,a.
n.a.
n .a.
n,a. }
ilk 1413.1
• 1413.3
tt 1 452
Zumiez
1411 Equipment performance
1411.4
1411.1
1411.1
1412 HVAC controls
53 1412.1 Temperature zones
14122 headband control
1412.3 Humidity control
1412.4 Automatic setback
• 1412.4.1 Dampers
1412.4.2 Optimum Start
1412.5 Heat pump confrol
1412.6
• 1412.7 Balancing
1422 Thermostat interlock
1423 Economizers
1413
1413.1
14132
1413.4
1414
1414.1
14142
1415.1
1416
1416.182
1416.3.2
1416.3.3
1415.4
1424
SERVICE WATER HEATING AND HEATED POOLS (Sections 1440 -1454)
1440
1441
1442
1443
1452
1453
1454
1454
Pkg. elec. htg.& clg.
Minimum efficiency
Combustion htg.
Combustion big.
Air economizers
Air Econo Operation
Vuttr Econo Operation
a ter Econo DoC
Integrated operation
Hie midrfication
Ducting systems
Duct searing Indicate sealing nec
Duct insulation indicate R -value of insulation on duct
Piping insulation ( Indicate R -value of insulation on piping
Completion Requirements
Drawings 8 Manuals
Air Balancing
Hydronic Balancing
Commissioning
Separate air sys.
Mechanical Completed and attached. Equipment schedule with types,
Summary Form klputloultaut, efficiency, cfm, hp, economizer
Service water htg.
Elec. writer heater
Shut -off controls
Pipe insulation
Heat Pump COP
Heater Efficiency
PncI heater controls
Pawl covers
Pools SO+ degrees
Information Required
List heat pumps on schedule
Equipment schedule wfh type, capacity, efficiency
h - dcate intermittent igrdicn, fluetdraft damper 8 Jacket loss
Indicate locations on plans
Include 5 degree deadband minimum
Indicate humidistat
Indicate thermostat with night setback and 7 dill. day types
indicate damper location and auto. controls & max. leakage
Indicate optimum start controls
Indicate microprocessor on thermostat schedule
intricate modulating or staged control
Indicate balancing features on plans
Indicate thermostat interlock on plans
Equipment schedule
Indicate 100% capability on schedule
Indicate 103% capacity at 45 degF db & 40 deg F wib
Indicate clg bad & water eCOnoe 8 clg tower performance
lncficate capabifrtyy for partial cooling
Indicate direct evap or fog atomization wI air economizer
hdicate requirement for record drawings and operation dons_
Indicate air system balance requirements
Indicate hydronic system balance requirements
Indicate requirements for commissioning and prelim. Report
Indicate separate systems on plans
Incicate R -10 insulation under tank
Indicate automatic shut -off
Indicate R -value of inulation on piping
Indicate minimum COP of 4.0
Indicate port heater efficiency
In Icate swich and 65 degree control
Indite vapor retardant cover
Indicate R -1 2 pool cover
If "no" is circled for any question, provide explanation:
Date
3/14/2000
Revised May 2005
ion Builds Department
g ep artment
on Plans Notes
2004 Washington Stole Nanresident"al Energy Cade Compliance Forms
iVl frztrticaI - General Requirements
1411.1 General: Equipment shall have a minimum performance at the
specified rating condi riot less an the values show n in Table 14-1A
through 14 -1 G. tfa nail onaltyrecognized certification program exists fora
product covered in Tables 14-1 A throu gh 14-16, and it includes provisions
for verification and challenge ofequipment effioienc}rratirtes.thenthe
product shall be fisted in the certification program.
Gas -ired and oil -fired forced air furnaces with input ratings . 225,0015
Been (pis Wulf) shall also have an intermittent ignition or interrupted device
(IID), and have ether mechanical draft [Including power venting)or a flue
d amper.Avent damper ran acceptable alternative to a flue damper fir
furnaces where combustion air is drawn from the conditioned space. All
furnaces with input ratings > 226 1100 13teth (Bra kW), including electric
fumaces,that are nat located within the conditioned space shall have
jacket losses not exceeding D.76% of the input rating.
1411.2 R Conditions: Cooling equipment shall be rated at ARlteet
c onditions and prooedurgs when available. Where no applicable
procedures exist. data shall be furnished bythe equipment manufacturer.
1411.3 Combination Space and Sere esWater Heating: For
combination space and service waterheaters with a principal function of
providing space heat, the Combined Peinual Efficiency(CAE)maybe
calculated byusing AS HRAE Standard 124-11:1131. Storage water heaters
used in combination space heat and water applications shall have
eerier en Energy FA&tar (EF) or a CAE of not less th an th a followin
1411.4 Packaged eiec#ric He end Cooling Equipment: Packaged
electric equipment providing both heating and cooling with a total oevfing
c apacity greater th an 20,000 Btu Ai shall be a heat pump.
Exception: Urrs equipment shaelters or cabinets used
solely far personal wireless service facilities.
9 412 Controls
1412.1 Temperature Controls: Each system shall be provided with at
It one temperature central device. Each zone shall be controlled by
individual thermostaticconteals responding to temperature w Min the zone.
Lid a minimum. each floor of building shall be considered as a separate
zone.
14122 Deadband Controls; tJUhen used to co ntrol bath comfortheating
and cooling, zo ne thermostatic controls shall be capable of deadband of
at least 5 degrees F within which the supply of heating and coaling energy
to the zone is shut off or reduced to a minimum.
Exceptions:
1. Special eeeupenvy,special usage, or code requirements
where deadband controls are not appropriate_
2. Buildings complying with Section 1141.4, ifin the proposed
building energy analysis, heating and coating thermcetel
setpoints are set to the same temperature between 7Q
degrees F and 73 degrees F inclusive, and assumed to be
constentthroughout the year.
3. Thermo stets that require manual changeover between
heatinng and caa5hg modes.
1412.3 Humidity Controls: Ile system is equipped with a means for
adding moisture ,a humidislat shall be provided.
1412.4 Setback and Shut -Off: H VAC systems shall be equipped with
automatic controls capable of accomplishing a reduction oferrergyuse
through control setback or equipment shutdown during periods of non -use
or alternate use of the spaces served bythe system. The automatic
oontmis shall have a minimum seven -day clack and be capable of being
set for seven different daytypes per week.
Exceptions:
1. Systems sewing areas which require continuous operation at
the same temperature setpoint.
2. Equipment with full Toad demands of2kW (OB20 9tu/h)or
less maybe controlled by readily acc ma nut I off -hour
controls.
1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets
serving conditioned spaces shall be equipped with dampers which close
a utomaticaliyw hen the system is affor upon power failure.
Exceptions:
1. Systems serving areas which require continuous operation.
2. Combustion air intakes.
3. Gravity lei onmotor'zed)dampere are acceptable in buildings
less than 3 stories in height.
4. Gravity(nonmotorized)dampers are acceptable in exhaust
and relief outlets in the first story and levels below the fast
stone ofbuildingsthree v rmore stories in height.
141242 Optimum Start Centrals: Heating and cooling systems with
design supply air cepecities exceeding 10,000 cfm shall have optimum
start controls. Optimum start oentrel5 shall be designed tc automatically
a djustthe start time of an HV Qsystemeach day to bring the space
desired occupied temperature levels immediately before scheduled
occupancy. The control algorithm shall, as minimum, be a function of the
difference between space temperature and occupied setpoint and the
amount oftime prierte scheduled occupancy_
1412.5 Heat Pump Controls: Unitary air coaled heat pumps shall Include
micraprocessor controls that minimize supplemental heat usage during
start- upset -up, and defter candelans. These controls shall anticipate
need for heat and use compression heating asthe fret stageofheet.
Controls shall indicate when supplemental heating is being used through
visual means (e.g., LED indicators).
1412.6 Combustion Healing Equipment Controls: Combustion heating
equipment with a capacity over 226.000 Blunt shall have modulating or
staged combustion control_
E;' eptions:
1. @oilers.
2_ Radiant Heaters.
1412.7 Balancing: Each air supply outlet or air or watertemtinal device
shall have a means for balancing. including but not Clinked to, dampers
temperature and pressure testoennections and balancing valves.
1413 Air Economizers
1413.1 iCperation:.Air economizers shall be of euternetically medulatirig
outside and return air dampers to provide 100 percent ofthe design supply
air as outside air to reduce or eliminate the need for mechanical cooling.
Water economizers shall be capable of providing the total co ncurrent
codling load served by-the connoted terminal equipment lacing airside
economizer, at outside air temperatures of45 dry - bulb /40 F wet -bulb
and below. For this calculation. all fdotor5 including solar and internal load
shall be the same a3 thvse used for peak load calculations, except forthe
outside temperatures.
Exception: Water economizers using air- coaled heat rejection
equipment may use a eeF dry -bulb outside airtemperature for
this calculation. This exception is limited to a maximum of 20 torts
per building.
1413.2 Docu d.tion: Water economizer plans submitted for apprvval
shall include the following information:
1. Maximum outside air conditions for which e4ronemizer is sized to
provide full cooling.
2. Design cooling load to be provided byecenemizeretthis outside
air condition.
3. Heat rejection and terminel equipment performance data
including model number, low rate , capacity. entering and leaving
temperature in full ecenomizer cooling mode.
1413.3 hfegr4ed Operation: Air economizers shall be capable of
providing partial cooling even when additional meohanivaI ovvlin is
required to meet the remainder of the cool ng load.
Exceptions:
1. Individual, direct expansion units that hat rated capacity
less than 055,000 Utulh and use nonintegrated economizer
o ontrolsthat preclude simultaneous operation of the
economizer and mechanical cooling.
2_ Water - cooled water chillers with waterside econamiz
1413.4 Humidrfication:'fen air economizer is required on a cooling
system for w hi ch humidification equipment Is to be provided to maintain
minimum indoor humidity levels, then the humidifier shall be of the
adiabatic type (direct evaporative media or fog atomization type).
Exceptions:
1. Health care facilities where WAC 246- 320 -526 allows only
steam injection hurniditiers in ductwork downstream of final
elters,1412.6 Combustion Heating Equipment Controls:
Combustion healing equipment with a capacity over 226,1300
Btu/h shall have modulating or eel ged combustion cone
2. Systems with water economizer
3. 100' outelde air systemswith no provisions fer air
recirculation to the central supplyfan.
4. Nenadirabatie humidifiers oumulativelysenang no more than
10% of buildings air economizer capacity es measured In
c fn . This refers to the system c f m serving rooms w ith stand
alone or duct mounted humidifiers.
1414 Ducting Systems
1414.1 Sealing: Ductwork which is designed to operate at pressures
above 1/2 inch water column static pressure shall be sealed in accordance
with Standard RS - 1e. Extent ofsealing required isas follows:
1_ Static pressure: 1/2 inch to 2 inches; seal transverse joints_
2. Static pressure: 2 inches to 3 inches :seal all transverse joints
and longitudinal seams.
3_ Static pressure: above 3 inches: seal all transverse jail
longitudinal seams and duct wall penetrations.
Duct tape and other pressure sensitive to pe shall no used as the
primary sea lam where ducts are designed to operate at static pressures of
1 inch W.C. or greater.
1414.2 hwlation: Duels and plenums that are constructed and function
as part of the building envelope,byseparating interior space from exterior
space, shall meet all applicable requirements of Chapter 13. The
requiremente Include insulation installation, moisture canto!, airleakage,
and building envelope insulation levels_ unheated equipment rooms with
combustion air louvers mu be isolated from the conditioned space by
insulating interior surfaces to a minimum of R -11 and any exterior
envelope surfaces per Chapter 13. Outside air ducts serving individual
supply air units with less than 2 ,800 cfm often! supply air caps city shall be
insulated to a minimum of R- -7 and are not considered building envelope.
Otheroutside air duct runs are considered building envelope until they,
1. connect to the heating or ma equipment, or
2_ are isolated from the exterior with an automatic shut- offdamper
complying with Section 14124.1.
On outside air ducts meet the above listed requirements,any runs
within conditioned space shall comply with Table 14-3 requirements.
Other ducts and plenums shall be thermally insulated per Table 14-6.
Exceptions:
1. Within the HVAC equipment.
2. Exhaust air duets not subject to condensation.
3. Exposed ductwork within a z one that serves that gene.
1415 Piping Systems
1415.1 hsulation: Piping shall bethermallyinsulated in accordance with
Table 146.
Exception: Piping installed within unitary HVAC equipment.
Water pipes outside the conditioned space shall be Insulated in
accordance with Washington State Plumbing Code MAC 51 -20)
1416 Completion Requirements (,Refre filREC Section f 415aadthe
Ekrlldiag Coirtmrssio!rirtg GenideL 'rres(itt6✓!•rst.eo'byer& Eaila'fng
Co diet l sia nine Assoclatian,farcae texl•and guieielings far bua•'dlreg
cempleuan and 'moat L;smalrfg re
1412.7 Balancing: Each air supply outlet or air or water terminal device
shall have a means for balancing, including but not limited to, dampers,
temperature and pressure test connections and balancing valves.
1413 Air Economizers
1413.1 Operation: Air economizers shall be of automatically modulating
outside and return air dampers to provide 100 percent of the design supply
air as outside air to reduce or eliminate the need for mechanical cooling.
Water economizers shall be capable of providing the total concurrent
cooling load served by the conneted terminal equipment lacking airside
economizer, at outside air temperatures of 45 ° F dry- bulb /40 ° F wet -bulb
and below. For this calculation, all factors including solar and internal load
shall be the same as those used for peak toad calculations, except for the
outside temperatures.
Exception: Water economizers using air - cooled heat rejection
equipment may use a 35 ° F dry-bulb outside air temperature for
this calculation. This exception is limited to a maximum of 20 tons
per building.
1413.2 Documentation: Water economizer plans submitted for approval
shall include the following information:
1. Maximum outside air conditions for which economizer is sized to
provide full cooling.
2. Design cooling load to be provided by economizer at this outside
air condition.
3. Heat rejection and terminal equipment performance data
including model number, flow rate, capacity, entering and leaving
temperature in full economizer cooling mode.
1413.3 Integrated Operation: Air economizers shall be capable of
providing partial cooling even when additional mechanical cooling is
required to meet the remainder of the cooling load.
Exceptions:
1. Individual, direct expansion units that have a rated capacity
less than 65,000 Btu/h and use nonintegrated economizer
controls that preclude simultaneous operation of the
economizer and mechanical cooling.
2. Water - cooled water chillers with waterside economizer.
1413.4 Humidification: If an air economizer is required on a cooling
system for which humidification equipment is to be provided to maintain
minimum indoor humidity levels, then the humidifier shall be of the
adiabatic type (direct evaporative media or fog atomization type).
Exceptions:
1. Health care facilities where WAC 246 - 320 -525 allows only
steam injection humidifiers in ductwork downstream of final
filters. 1412.6 Combustion Heating Equipment Controls:
Combustion heating equipment with a capacity over 225,000
Btu/h shall have modulating or staged combustion control.
2. Systems with water economizer
3. 100% outside air systems with no provisions for air
recirculation to the central supply fan.
4. Nonadiabatic humidifiers cumulatively serving no more than
10% of a building's air economizer capacity as measured in
cfm. This refers to the system cfm serving rooms with stand
alone or duct mounted humidifiers.
1414 Ducting Systems
1414.1 Sealing: Duct work which is designed to operate at pressures
above 1/2 inch water column static pressure shall be sealed in accordance
with Standard RS -18. Extent of sealing required is as follows:
1. Static pressure: 1/2 inch to 2 inches; seal transverse joints.
2. Static pressure: 2 inches to 3 inches; seal all transverse joints
and longitudinal seams.
3. Static pressure: above 3 inches; seal all transverse joints,
longitudinal seams and duct wall penetrations.
Duct tape and other pressure sensitive tape shall not be used as the
primary sealant where ducts are designed to operate at static pressures of
1 inch W.C. or greater.
1414.2 Insulation: Ducts and plenums that are constructed and function
as part of the building envelope, by separating interior space from exterior
space, shall meet all applicable requirements of Chapter 13. These
requirements include insulation installation, moisture control, air leakage,
and building envelope insulation levels. Unheated equipment rooms with
combustion air louvers must be isolated from the conditioned space by
insulating interior surfaces to a minimum of R -11 and any exterior
envelope surfaces per Chapter 13. Outside air ducts serving individual
supply air units with less than 2,800 cfm of total supply air capacity shall be
insulated to a minimum of R -7 and are not considered building envelope
Other outside air duct runs are considered building envelope until they,
1. connect to the heating or cooling equipment, or
2. are isolated from the exterior with an automatic shut - off damper
complying with Section 1412.4.1.
Once outside air ducts meet the above listed requirements, any runs
within conditioned space shall comply with Table 14 -5 requirements.
Other ducts and plenums shall be thermally insulated per Table 14 -5.
Exceptions:
1. Within the HVAC equipment.
2, Exhaust air ducts not subject to condensation.
3. Exposed ductwork within a zone that serves that zone.
1415 Piping Systems
1415.1 Insulation: Piping shall be thermally insulated in accordance with
Table 14 -6.
Exception: Piping installed within unitary HVAC equipment.
Water pipes outside the conditioned space shall be insulated in
accordance with Washington State Plumbing Code (WAC 51 - 26)
1416 Completion Requirements (Refer to NREC Section 1416 and the
Building Commissioning Guidelines, published by the Building
Commissioning Association, for complete text and guidelines for building
completion and commissioning requirements.)
2004 V State Nonresidential Energy Code Compliance Forms
Project Info
Project Address
Applicant Address:
Applicant Phone: 479 - 213 - ?W0
889 S_V_ A Street; Suite 2111, Bentonville, AR 72712
Project 1)0scripticrn
Briefly describe mechanical
system type and features.
❑ Includes PIar1
Compliance Option
Equipment Schedules
Applicant fume:
Cooling E guigrnent Schedule
Trani
Equip.
ID
TAY1
Brand Name
Heating E�quigment Schedule
Equip.
ID
VAV1
Fan Equipment Schedule
Equip.
ID
BHA
VCEF14
Model No
Zumiez
South Center Mali
Tukwila, VA
Greg Sehlutermam
Include documentation requiring compliance with commissioning requirements, Section 1416.
0 Simple System i Cornplex System ° Systems Analysis 0 Clear
(See Decision Flowchart (Dyer) for qual'rfications. Use separate MECH -SUM for simple & complex systems.)
The following information is required to be incorporated with the mechanical equipment schedules on
the plans. For projects without plans, fill in the required information below.
Capacity
Bluhi
55F air
Total CFM
2600
OSA CFM
or Econo?
SEER
or EER
Dart
1 If available. 2 AS tested according to Table 14 through 14 3 I required_ e ' COP, HSPF, Combustion Efficiency, or AFUE, as
applicable. $ Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS).
REVIEWED CODE COMPLIANCE
APPROVED
Al R 1 0 200B
City Of Tukwila
BUII DIN DIVISION
g
IPLV
Revised May 2005
3/14/2003
For Building Dept. Use
Location
stockroom
Trace
Brand Nam&
Model No.
VCEF14
Capacity
Etu 1i
Total CFM
1600
OSA cfm
or Canoe
input Btuh
51195
Efficiency
RECEIVED
CITY OF TUKWILA
MAR 2 8 2008
PERMIT CENTER
100.1100
Brand Name
Model No.
CFM
sP
HPiDHP
Flow Control'
Location of Service
zumuez
SOu'1'HCENTER MALL
SPACE # 2115
633 SouncENrxR
SEATTLE, WA 98188
MURPHY VAREYps
DAVID J. MURPHY, AIA
amt Nora dmtni Born is
flume lr1arcmer 98m
1: 106 . sp . 9
F: 106.34.9m
Sr v. lifinairriruccont
Harrison French and
Associates
809 S.W. "A" Street
Bentonville, AR 72712
(479) 273 -7780
fax (479) 273-9436
DATE:
141
02 - - PRELIMINARY MALL REVIEW
ISSUED FOR:
PROJECT NUMBER: 05 - - 02008
ZUMIEZ STORE NUMBER: 19
PRELIMINARY MALL
REVIEW
SHEET TITLE:
1 EXPIRES: 02/23/10 ,
ENERGY
CODE FORMS
SHEET NUMBER:
M2
DIVISION 15
15A: GENERAL
15A 1 -1 GENERAL REQUIREMENTS
REQUIREMENTS UNDER DIVISION ONE AND THE
GENERAL AND SUPPLEMENTARY CONDITIONS OF THESE
SPECIFICATIONS SHALL BE A PART OF THIS SECTION.
CONTRACTOR SHALL BECOME THOROUGHLY
ACQUAINTED WITH ITS CONTENTS AS TO
REQUIREMENTS THAT AFFECT THIS DIVISION OR
SECTION. THE WORK REQUIRED UNDER THIS SECTION
INCLUDES MATERIAL, EQUIPMENT, APPLIANCES,
TRANSPORTATION, SERVICES, AND LABOR REQUIRED TO
COMPLETE THE ENTIRE SYSTEM AS REQUIRED BY THE
DRAWINGS AND SPECIFICATIONS.
THE SPECIFICATIONS AND DRAWINGS FOR THE
PROJECT ARE COMPLEMENTARY, AND PORTIONS OF
THE WORK DESCRIBED IN ONE, SHALL BE PROVIDED
AS IF DESCRIBED IN BOTH. IN THE EVENT OF
DISCREPANCIES, NOTIFY THE ENGINEER AND /OR
OWNER AND REQUEST CLARIFICATION PRIOR TO
PROCEEDING WITH THE WORK INVOLVED.
15A 1 -2 INSPECTION OF SITE
PRIOR TO SUBMITTING BID, VISIT THE SITE OF THE
PROPOSED WORK AND BECOME FULLY INFORMED AS
TO THE CONDITIONS UNDER WHICH THE WORK IS TO
BE DONE. FAILURE TO DO 50 WILL NOT BE
CONSIDERED SUFFICIENT JUSTIFICATION TO REQUEST
OR OBTAIN EXTRA COMPENSATION OVER AND ABOVE
THE CONTRACT PRICE.
15A 1 -3 MATERIAL AND WORKMANSHIP
PROVIDE NEW MATERIAL, EQUIPMENT, AND APPARATUS
UNDER THIS CONTRACT UNLESS OTHERWISE STATED
HEREIN, OF BEST QUALITY NORMALLY USED FOR THE
PURPOSE IN GOOD COMMERCIAL PRACTICE, AND FREE
FROM ANY DEFECTS. MODEL NUMBERS LISTED IN THE
SPECIFICATIONS OR SHOWN ON THE DRAWINGS ARE
NOT NECESSARILY INTENDED TO DESIGNATE THE
REQUIRED TRIM, WRITTEN DESCRIPTIONS OF THE TRIM
GOVERN MODEL NUMBERS.
WORK PERFORMED UNDER THIS CONTRACT SHALL
PROVIDE A NEAT AND "WORKMANLIKE" APPEARANCE
WHEN COMPLETED, TO THE SATISFACTION OF THE
ARCHITECT AND ENGINEER. WORKMANSHIP SHALL BE
THE FINEST POSSIBLE BY EXPERIENCED MECHANICS.
INSTALLATIONS SHALL COMPLY WITH APPLICABLE
CODES AND LAWS.
THE COMPLETE INSTALLATION SHALL FUNCTION AS
DESIGNED AND INTENDED WITH RESPECT TO
EFFICIENCY, CAPACITY, NOISE LEVEL, ETC. ABNORMAL
NOISE CAUSED BY RATTLING EQUIPMENT, PIPING,
DUCTS, AIR DEVICES, AND SQUEAKS IN ROTATING
COMPONENTS WILL NOT BE ACCEPTABLE. IN GENERAL,
MATERIALS AND EQUIPMENT SHALL BE OF
COMMERCIAL SPECIFICATION GRADE IN QUALITY.
LIGHT DUTY AND RESIDENTIAL TYPE EQUIPMENT WILL
NOT BE ACCEPTED.
REMOVE FROM THE PREMISES WASTE MATERIAL
PRESENT AS A RESULT OF WORK, INCLUDING
CARTONS, CRATING, PAPER, STICKERS, AND /OR
EXCAVATION MATERIAL NOT USED IN BACKFILLING,
ETC. CLEAN EQUIPMENT INSTALLED UNDER THIS
CONTRACT TO PRESENT A NEAT AND CLEAN
INSTALLATION AT THE TERMINATION OF THE WORK.
REPAIR OR REPLACE PUBLIC AND PRIVATE PROPERTY
DAMAGED AS A RESULT OF WORK PERFORMED UNDER
THIS CONTRACT TO THE SATISFACTION OF
AUTHORITIES AND REGULATIONS HAVING JURISDICTION.
15A 1 -4 COORDINATION
COORDINATE WORK WITH THAT OF OTHER TRADES 50
THAT THE VARIOUS COMPONENTS OF THE SYSTEMS
WILL BE INSTALLED AT THE PROPER TIME, WILL FIT
THE AVAILABLE SPACE, AND WILL ALLOW PROPER
SERVICE ACCESS TO THOSE ITEMS REQUIRING
MAINTENANCE. COMPONENTS WHICH ARE INSTALLED
WITHOUT REGARD TO THE ABOVE SHALL BE
RELOCATED AT NO ADDITIONAL COST TO THE OWNER.
UNLESS OTHERWISE INDICATED, THE GENERAL
CONTRACTOR WILL PROVIDE CHASES AND OPENINGS IN
BUILDING CONSTRUCTION REQUIRED FOR INSTALLATION
OF THE SYSTEMS SPECIFIED HEREIN. CONTRACTOR
SHALL FURNISH THE GENERAL CONTRACTOR WITH
INFORMATION WHERE CHASES AND OPENINGS ARE
REQUIRED. KEEP INFORMED AS TO THE WORK OF
OTHER TRADES ENGAGED IN THE CONSTRUCTION OF
THE PROJECT, AND EXECUTE WORK IN A MANNER AS
TO NOT INTERFERE WITH OR DELAY THE WORK OF
OTHER TRADES.
FIGURED DIMENSIONS SHALL BE TAKEN IN PREFERENCE
TO SCALE DIMENSIONS. CONTRACTOR SHALL TAKE
HIS OWN MEASUREMENTS AT THE BUILDING, AS
VARIATIONS MAY OCCUR. CONTRACTOR WILL BE HELD
RESPONSIBLE FOR ERRORS THAT COULD HAVE BEEN
AVOIDED BY PROPER CHECKING AND INSPECTION.
PROVIDE MATERIALS WITH TRIM THAT WILL PROPERLY
FIT THE TYPES OF CEILING, WALL, OR FLOOR FINISHES
ACTUALLY INSTALLED. MODEL NUMBERS LISTED IN
THE SPECIFICATIONS OR SHOWN ON THE DRAWINGS
ARE NOT INTENDED TO DESIGNATE THE REQUIRED
TRIM.
15A 1 -5 ORDINANCES AND CODES
WORK PERFORMED UNDER THIS CONTRACT SHALL, AT
A MINIMUM, BE IN CONFORMANCE WITH APPLICABLE
NATIONAL, STATE AND LOCAL CODES HAVING
JURISDICTION. EQUIPMENT FURNISHED AND
ASSOCIATED INSTALLATION WORK PERFORMED UNDER
THIS CONTRACT SHALL BE IN STRICT COMPLIANCE
WITH CURRENT APPLICABLE CODES ADOPTED BY THE
LOCAL AHJ INCLUDING ANY AMENDMENTS AND
STANDARDS AS SET FORTH BY THE NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA), UNDERWRITERS
LABORATORIES (UL), OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION (OSHA), AMERICAN SOCIETY
OF MECHANICAL ENGINEERS (ASME), AMERICAN
SOCIETY OF HEATING, REFRIGERATION, AND AIR
CONDITIONING ENGINEERS (ASHRAE), AMERICAN
NATIONAL STANDARDS INSTITUTE (ANSI), AMERICAN
SOCIETY OF TESTING MATERIALS (ASTM) AND OTHER
NATIONAL STANDARDS AND CODES WHERE
APPLICABLE. WHERE THE CONTRACT DOCUMENTS
EXCEED THE REQUIREMENTS OF THEIR REFERENCED
CODES, STANDARDS, ETC., THE CONTRACT DOCUMENTS
SHALL TAKE PRECEDENCE.
PROCURE AND PAY FOR PERMITS AND LICENSES
REQUIRED FOR THE ACCOMPLISHMENT OF THE WORK
HEREIN DESCRIBED. WHERE REQUIRED, OBTAIN, PAY
FOR AND FURNISH CERTIFICATES OF INSPECTION TO
OWNER. CONTRACTOR WILL BE HELD RESPONSIBLE
FOR VIOLATIONS OF THE LAW.
15A 1 -6 PROTECTION OF EQUIPMENT AND MATERIALS
STORE AND PROTECT FROM DAMAGE EQUIPMENT AND
MATERIALS DELIVERED TO JOB SITE. COVER WITH
WATERPROOF, TEAR— RESISTANT, HEAVY TARP OR
POLYETHYLENE PLASTIC AS REQUIRED TO PROTECT
FROM PLASTER, DIRT, PAINT, WATER, OR PHYSICAL
DAMAGE. EQUIPMENT AND MATERIAL THAT HAS BEEN
DAMAGED BY CONSTRUCTION ACTIVITIES WILL BE
REJECTED, AND CONTRACTOR IS OBLIGATED TO
FURNISH NEW EQUIPMENT AND MATERIAL OF A LIKE
KIND.
KEEP PREMISES ROOM CLEAN FROM FOREIGN
MATERIAL CREATED DURING WORK PERFORMED UNDER
THIS CONTRACT. PIPING, EQUIPMENT, ETC., SHALL
HAVE A NEAT AND CLEAN APPEARANCE AT THE
TERMINATION OF THE WORK.
PLUG OR CAP OPEN ENDS OF DUCTWORK AND PIPING
SYSTEMS WHILE STORED OR INSTALLED DURING
CONSTRUCTION WHEN NOT IN USE TO PREVENT THE
ENTRANCE OF DEBRIS INTO THE SYSTEMS.
KEEP THE MANUFACTURER PROVIDED PROTECTIVE
COVERINGS ON FLOOR DRAINS, FLOOR SINKS, AND
TRENCH DRAINS DURING CONSTRUCTION. REMOVE
COVERINGS AT THE TERMINATION OF THE WORK AND
POLISH EXPOSED SURFACES.
15A 1 -7 OPERATION AND MAINTENANCE INSTRUCTIONS
COLLECT AND COMPILE A COMPLETE BROCHURE OF
FIXTURES, MATERIALS, AND EQUIPMENT FURNISHED
AND INSTALLED ON THIS PROJECT. INCLUDE
OPERATIONAL AND MAINTENANCE INSTRUCTIONS,
MANUFACTURER'S CATALOG SHEETS, WIRING DIAGRAMS.
PARTS LISTS, APPROVED SHOP DRAWINGS, AND
DESCRIPTIVE LITERATURE FURNISHED BY THE
MANUFACTURER. INCLUDE AN INSIDE COVER SHEET
THAT LISTS THE PROJECT NAME, DATE, OWNER,
ARCHITECT, ENGINEER, GENERAL CONTRACTOR,
SUBCONTRACTOR, AND AN INDEX OF CONTENTS.
SUBMIT COPIES OF LITERATURE BOUND IN APPROVED
BINDERS TO THE ARCHITECT AND OWNER AT THE
TERMINATION OF THE WORK. PAPER CLIPS, STAPLES,
RUBBER BANDS, AND MAILING ENVELOPES ARE NOT
CONSIDERED APPROVED BINDERS. FINAL APPROVAL
OF PLUMBING SYSTEMS WILL BE WITHHELD UNTIL THIS
EQUIPMENT BROCHURE IS DEEMED COMPLETE BY THE
ARCHITECT, ENGINEER, AND OWNER.
15A 1-8 WARRANTIES
WARRANT EACH SYSTEM AND EACH ELEMENT THEREOF
AGAINST ALL DEFECTS DUE TO FAULTY WORKMANSHIP,
DESIGN OR MATERIAL FOR A PERIOD OF 12 MONTHS
FROM DATE OF SUBSTANTIAL COMPLETION, UNLESS
SPECIFIC ITEMS ARE NOTED TO CARRY A LONGER
WARRANTY IN THE CONSTRUCTION DOCUMENTS OR
MANUFACTURER'S STANDARD WARRANTY EXCEEDS 12
MONTHS. REMEDY ALL DEFECTS, OCCURRING WITHIN
THE WARRANTY PERIOD(S), AS STATED IN THE
GENERAL CONDITIONS AND DIVISION 1.
WARRANTIES SHALL INCLUDE LABOR AND MATERIAL.
MAKE REPAIRS OR REPLACEMENTS WITHOUT ANY
ADDITIONAL COSTS TO THE OWNER.
PERFORM THE REMEDIAL WORK PROMPTLY, UPON
WRITTEN NOTICE FROM THE ENGINEER OR OWNER.
AT THE TIME OF SUBSTANTIAL COMPLETION, DELIVER
TO THE OWNER ALL WARRANTIES, IN WRITING AND
PROPERLY EXECUTED, INCLUDING TERM LIMITS FOR
WARRANTIES EXTENDING BEYOND THE ONE YEAR
PERIOD, EACH WARRANTY INSTRUMENT BEING
ADDRESSED TO THE OWNER AND STATING THE
COMMENCEMENT DATE AND TERM.
15A 1 -9 CUTTING AND PATCHING
PERFORM CUTTING OF WALLS, FLOORS, CEILINGS, ETC.
AS REQUIRED TO INSTALL WORK UNDER THIS SECTION.
OBTAIN PERMISSION FROM THE ARCHITECT PRIOR TO
CUTTING. DO NOT CUT OR DISTURB STRUCTURAL
MEMBERS WITHOUT PRIOR APPROVAL FROM THE
ARCHITECT. CUT HOLES AS SMALL AS POSSIBLE.
GENERAL CONTRACTOR SHALL PATCH WALLS, FLOORS,
ETC. AS REQUIRED BY WORK UNDER THIS SECTION.
PATCHING SHALL MATCH THE ORIGINAL MATERIAL AND
CONSTRUCTION. REPAIR AND REFINISH AREAS
DISTURBED BY WORK TO THE CONDITION OF ADJOINING
SURFACES IN A MANNER SATISFACTORY TO THE
ARCHITECT.
15A 1 -10 ROUGH —IN
COORDINATE WITHOUT DELAY ROUGHING —IN WITH
GENERAL CONSTRUCTION. CONCEAL PIPING AND
CONDUIT ROUGH —IN EXCEPT IN UNFINISHED AREAS
AND WHERE OTHERWISE SHOWN.
15A 1-11 STRUCTURAL STEEL
STRUCTURAL STEEL USED FOR PIPE SUPPORTS,
EQUIPMENT SUPPORTS, ETC., SHALL BE NEW, CLEAN,
AND CONFORM TO ASTM DESIGNATION A -36.
SUPPORT PLUMBING AND MECHANICAL EQUIPMENT AND
PIPING FROM THE BUILDING STRUCTURE. DO NOT
SUPPORT PLUMBING EQUIPMENT FROM CEILINGS,
OTHER MECHANICAL OR ELECTRICAL COMPONENTS,
AND OTHER NON — STRUCTURAL ELEMENTS.
15A 1 -12 ACCESS DOORS
PROVIDE ACCESS DOORS IN CEILINGS AND WALLS
WHERE INDICATED OR REQUIRED FOR ACCESS TO
CONCEALED VALVES AND EQUIPMENT INSTALLED
UNDER THIS SECTION. PROVIDE CONCEALED HINGES,
SCREWDRIVER —TYPE LOCK, ANCHOR STRAPS;
MANUFACTURED BY MILCOR, ZURN, T1TUS, OR EQUAL.
OBTAIN ARCHITECT'S APPROVAL OF TYPE, SIZE,
LOCATION, AND COLOR BEFORE ORDERING.
15A 1 -13 PENETRATIONS
SEAL FLOOR, EXTERIOR WALL AND ROOF
PENETRATIONS WATER AND WEATHER TIGHT WITH
APPROPRIATE NON— SHRINK, NON— HARDENING
COMMERCIAL CONSTRUCTION SEALANT. SEAL ROOF
PENETRATIONS WITH 4 POUND PER SQUARE FOOT
LEAD FLASHING. PROVIDE A SLEEVE, AND SEAL
NON —F1RE —RATED FLOOR AND WALL PENETRATIONS
WITH FIBERGLASS PACKING AND SILICONE CAULK (FOR
ACOUSTICAL INSULATION).
COORDINATED FIRE RATING REQUIREMENTS AND
LOCATIONS WITH THE ARCHITECT. SEAL
PENETRATIONS OF FIRE —RATED ASSEMBLIES WITH 3M
# CP -25 FIRE BARRIER CAULK (PROVIDE THICKNESS
AND METHOD AS REQUIRED AND RECOMMENDED BY
MANUFACTURER) TO MAINTAIN THE FIRE RESISTANCE
RATING OF FIRE—RATED ASSEMBLIES.
SEAL EXTERIOR WALL PENETRATIONS BELOW GRADE
WITH CAST IRON WALL PIPES AND MODULAR
MECHANICAL SLEEVE SEALS, MANUFACTURED BY
THUNDERLINE /LINK SEAL, CALPICO, INC AND
METRAFLEX.
PROVIDE SLEEVES FOR HORIZONTAL PIPE PASSING
THROUGH OR UNDER FOUNDATION. SLEEVES SHALL
BE CAST IRON SOIL PIPE TWO NOMINAL PIPE SIZES
LARGER THAN THE PIPE SERVED.
PROVIDE SLEEVES FOR VERTICAL PIPE PASSING
THROUGH SLAB ON GRADE. SLEEVES SHALL BE
SCHEDULE 40 PVC PIPE, TWO NOMINAL PIPE SIZES
LARGER THAN THE PIPE SERVED. SEAL WATER —TIGHT
WITH SILICONE CAULK.
158: HEATING, VENTILATION. AND AIR CONDITIONING
15B 1 -1 DUCTWORK
ALL DUCTWORK SHALL BE CONSTRUCTED IN
ACCORDANCE WITH ASHRAE AND SMACNA STANDARDS
CORRESPONDING TO THE SYSTEM PRESSURE.
DUCTWORK SHALL BE CONSTRUCTED IN ACCORDANCE
WITH THE STANDARDS FOR A TWO—INCH PRESSURE
RATING AND SEAL CLASS B.
SUPPLY AND RETURN DUCTWORK INSIDE THE BUILDING
SHALL BE INSULATED WITH 1" THICK ACOUSTICAL
LINING WITH A MINIMUM R- -VALUE OF 5 OR
EXTERNALLY WRAPPED WITH 2" THICK GLASS FIBER
DUCT WRAP. INSULATE SUPPLY AND RETURN
DUCTWORK LOCATED OUTSIDE THE BUILDING WITH 2"
LINER AND SEAL SEAMS WEATHER TIGHT. DEDICATED
OUTSIDE AIR SUPPLY DUCTWORK LOCATED WITHIN THE
BUILDING SHALL BE INSULATED WITH 2" DUCT WRAP.
EXPOSED DUCTWORK IN SALES AREA SHALL NOT HAVE
ANY INSULATION.
FLEXIBLE DUCTWORK MAINS ARE NOT PERMITTED.
PROVIDE MAXIMUM 5' —O" FLEXIBLE DUCT CONNECTIONS
TO CEILING DIFFUSERS.
FURNISH AND INSTALL VOLUME /BALANCE DAMPERS AT
ALL BRANCH DUCTS TO DIFFUSERS. LOCATE
DAMPERS A MINIMUM OF 4' -0" AWAY FROM
DIFFUSERS.
INSTALL VTR'S, EXHAUST FANS, AND FLUES A
MINIMUM OF 5' —O" FROM PARAPET OR OUTSIDE WALL
AND 10' —O" MINIMUM FROM EQUIPMENT WITH OUTSIDE
AIR INTAKE.
156 1 -2 ELECTRICAL WIRING
LINE VOLTAGE WIRING SHALL BE FURNISHED BY
DIVISION 16. LINE VOLTAGE CONTROL AND INTERLOCK
WIRING FOR MECHANICAL SYSTEMS SHALL ALSO BE
FURNISHED BY DIVISION 16 CONTRACTOR. LOW
VOLTAGE CONTROL WIRING SHALL BE BY THE DIVISION
15 CONTRACTOR. PROVIDE WIRING DIAGRAMS TO THE
DIVISION 16 CONTRACTOR AS REQUIRED FOR PROPER
EQUIPMENT HOOKUP. COORDINATE WITH THE DIVISION
16 CONTRACTOR THE ACTUAL WIRE SIZING AMPS FOR
MECHANICAL EQUIPMENT (FROM THE EQUIPMENT
NAMEPLATE) TO ENSURE PROPER INSTALLATION.
ALL TEMPERATURE SENSORS, FAN SWITCHES, AND
SPEED CONTROLS SHALL BE INSTALLED 43" ABOVE
THE FLOOR FOR ADA REQUIREMENTS.
15B 1 -3 FINAL TESTING AND ADJUSTMENTS
AIR BALANCE SHALL BE PERFORMED BY AN
INDEPENDENT AIR BALANCE CONTRACTOR. BALANCE
EACH SUPPLY, RETURN, OUTSIDE AIR DEVICE WITHIN
5% OF REQUIREMENTS AND FURNISH A REPORT TO
THE CONSTRUCTION MANAGER. THE ENTIRE HVAC
SYSTEM MUST BE FULLY OPERABLE, BALANCED, AND
APPROVED BY OWNER'S REPRESENTATIVE ON THE DAY
TENANT OPENS FOR BUSINESS.
ADJUST THERMOSTATS AND CONTROL DEVICES TO
OPERATE AS INTENDED. ADJUST BURNERS, PUMPS,
FANS, ETC. FOR PROPER AND EFFICIENT OPERATION.
CERTIFY TO ARCHITECT THAT ADJUSTMENTS HAVE
BEEN MADE AND THAT SYSTEM IS OPERATING
SATISFACTORILY. CALIBRATE, SET AND ADJUST
AUTOMATIC TEMPERATURE CONTROLS. CHECK PROPER
SEQUENCING OF INTERLOCK SYSTEMS, AND OPERATION
OF SAFETY CONTROLS.
15C: PLUMBING
15C 1-1 PIPING MATERIALS
MATERIALS SPECIFIED OR NOTED ON THE DRAWINGS
ARE SUBJECT TO THE APPROVAL OF LOCAL CODE
AUTHORITIES. VERIFY APPROVAL BEFORE INSTALLING
ANY MATERIAL OR JOINING METHOD.
DOMESTIC WATER (COLD, HOT, SOFT): DOMESTIC
WATER PIPING INSTALLED ABOVE THE FLOOR SLAB
INSIDE THE BUILDING SHALL BE TYPE "L" HARD
TEMPER COPPER TUBE WITH WROUGHT COPPER.
FITTINGS AND SOLDERED CONNECTIONS MADE UP WITH
95/5 SOLDER. BRAZED MECHANICALLY FORMED TEE
CONNECTIONS (T— DRILL) MAY BE USED IN COPPER
LINES WHERE APPROVED BY CODE; CONNECTION
SHALL BE MADE WITH BRAZED SILVER SOLDER
(SILFOS) JOINTS IN CONFORMANCE WITH
MANUFACTURER'S INSTRUCTIONS.
UNDERGROUND DOMESTIC WATER PIPING SHALL BE
TYPE " K " SOFT TEMPER COPPER TUBING WITH FLARED
COPPER ALLOY FITTINGS AND CONNECTIONS, OR TYPE
"K" HARD TEMPER COPPER TUBING WITH
CONVENTIONAL WROUGHT COPPER FITTINGS AND
SILVER SOLDER (SILFOS) JOINTS. INSTALL AS FEW
UNDERGROUND COPPER PIPING JOINTS AS POSSIBLE.
AT BUILDING SERVICE ENTRANCE, NO JOINTS SHALL
BE INSTALLED UNDER OR WITHIN 5 FEET OF THE
BUILDING. INSTALL DOMESTIC WATER PIPING BELOW
GRADE OUTSIDE BUILDING AT ADEQUATE DEPTH TO
PREVENT FREEZING.
INTERIOR WASTE AND VENT BELOW SLAB: WASTE AND
VENT PIPE BELOW SLAB INSIDE BUILDING SHALL BE
STANDARD WEIGHT CAST IRON SOIL PIPE WITH HUB
AND SPIGOT FITTINGS WITH NEOPRENE GASKET JOINTS.
HUB LESS WASTE AND VENT PIPE IS NOT PERMITTED
BELOW BASE SLAB. PVC DWV PIPE WITH SOCKET
FITTINGS AND SOLVENT WELD JOINTS IS ALSO
PERMITTED WHERE APPROVED BY CODE.
INTERIOR WASTE AND VENT ABOVE SLAB: WASTE AND
VENT PIPE ABOVE SLAB INSIDE BUILDING SHALL BE
HUB LESS CAST IRON SOIL PIPE AND FITTINGS WITH
HUB LESS COUPLINGS. PVC DWV PIPE WITH SOCKET
FITTINGS AND SOLVENT WELD JOINTS IS ALSO
PERMITTED WHERE APPROVED BY CODE.
INTERIOR STORM DRAIN: INSIDE BUILDING SHALL BE
SAME AS SPECIFIED FOR INTERIOR WASTE AND VENT
PIPE.
INDIRECT AND CONDENSATE DRAIN INSIDE BUILDING:
INDIRECT AND CONDENSATE DRAIN PIPE INSTALLED
INSIDE THE BUILDING SHALL BE TYPE "M" HARD
COPPER WITH WROUGHT COPPER FITTINGS FOR 1" AND
SMALLER AND "DWV" COPPER WITH WROUGHT COPPER
DRAINAGE PATTERN FITTINGS FOR 1 -1/4 " AND
LARGER HARD TEMPER COPPER TUBE AND SOLDERED
CONNECTIONS MADE WITH 95/5 SOLDER. INSTALL
CLEANOUTS AT ELBOWS GREATER THAN 45 DEGREES.
GAS PIPING: GAS PIPING SHALL BE BLACK STEEL,
STANDARD WEIGHT, SCHEDULE 40 ASTM A53. PIPING
2" AND SMALL SHALL BE WELDED OR THREADED WITH
MALLEABLE IRON FITTINGS. PIPING 2 1/2" AND
LARGER SHALL BE WELDED WITH BUTT — WELDED
FITTING. FITTINGS SHALL CONFORM TO ASME B16.3,
MALLEABLE IRON OR ASTM A 234, FORGED STEEL
WELDED TYPE.
15C 1-2 PIPING AND EQUIPMENT INSULATION
DOMESTIC COLD WATER, HOT WATER, INDIRECT AND
CONDENSATE DRAIN PIPE (WITHIN BUILDING): 1"
ONE —PIECE FIBERGLASS COVERING WITH
FIRE — RESISTANT JACKET WITH SELF — SEALING LAP TO
PROVIDE A CONTINUOUS VAPOR BARRIER BY
CERTAINTEED, OWENS — CORNING OR ARMSTRONG. FOR
PIPING AT HANGERS PROVIDE 8" LONG SECTIONS OF
HIGH DENSITY, HIGH TEMPERATURE CALCIUM SILICATE
BY JOHNS—MANVILLE, FIBERGLASS BY KNAUF, OR 8"
LONG STYROFOAM BILLETS BY DOW. INSULATION
SHALL BE CONTINUOUS ALONG THE PIPE SURFACE,
EXCEPT AT VALVES, UNIONS, AND WHERE PIPING IS
EXPOSED AT FIXTURES.
FOR HOT AND COLD WATER PIPING INSTALLED INSIDE
MASONRY UNITS OF WALLS, PROVIDE Mfz" FLEXIBLE
UNICELLULAR INSULATION BY ARMACELL.
COVER FITTINGS WITH ZESTON, KNAUF, OR EQUAL
ONE —PIECE PVC PREMOLDED INSULATING COVERS.
FITTING COVERS, JACKETS AND ADHESIVES SHALL NOT
EXCEED FLAME SPREAD RATING OF 25 AND SMOKE
DEVELOPMENT RATING OF 50 PER ASTM E84. AT ALL
ELBOWS AND TEES, FILL VOIDS BETWEEN COVERS AND
PIPING WITH FIBERGLASS INSULATION AND TAPE
JOINTS. INSTALL PIPE INSULATION IN COMPLIANCE
WITH MANUFACTURER'S RECOMMENDATIONS. WHERE
PREMOLDED INSULATING FITTINGS ARE NOT APPROVED
BY LOCAL AUTHORITIES, MITER INSULATION AT
FITTINGS.
15C 1 -3 PIPING INSTALLATION
GENERAL: CLEAN PIPE THOROUGHLY PRIOR TO
INSTALLATION. REAM ENDS OF PIPE TO REMOVE
BURRS. CUT PIPE ACCURATELY TO MEASUREMENTS
TAKEN ON THE JOB. INSTALL WITH ADEQUATE
CLEARANCE FOR INSTALLATION OF COVERINGS WHERE
REQUIRED. PIPE SHALL NOT BE SPRUNG OR BENT.
NEATLY ALIGN PIPE, CONNECT IT SECURELY, AND
SUPPORT IT FROM THE BUILDING STRUCTURE WIN
HANGERS AS SPECIFIED BELOW. PROVIDE
CHROME — PLATED ESCUTCHEONS ON PIPES PASSING
THROUGH CEILINGS, FLOORS OR WALLS OF FINISHED
SPACES. RUN PIPES FREELY THROUGH FLOOR AND
WALL PENETRATIONS USING PIPE SLEEVES. DO NOT
GROUT IN PLACE UNLESS REQUIRED FOR STRUCTURAL
FIRE INTEGRITY. INSTALL PIPE CONCEALED IN
FINISHED SPACES WHEREVER POSSIBLE. USE A
DIELECTRIC UNION WHERE FERROUS AND COPPER PIPE
CONNECT. DIELECTRIC UNION SHALL HAVE A ZINC
STEEL BODY, A THREADED NYLON INSERT, AND
INSULATING PRESSURE GASKET. NO FERROUS
METAL —TO— COPPER CONNECTION MADE WITHOUT
INSULATING UNIONS WILL BE ALLOWED.
HANGER & SUPPORTS: PIPE HANGERS SHALL BE AS
DESCRIBED IN THE SPECIFICATIONS BY B —LINE OR
EQUAL BY ANVIL, MICHIGAN, TRUSCON, OR UNISTRUT.
CONNECT HANGERS TO THE STRUCTURE WITH SIDE
BEAM CONNECTORS AND ALL THREAD HANGER RODS.
PROVIDE ENGINEERED SUPPORT STRUTS BETWEEN
JOISTS AND OTHER STRUCTURAL MEMBERS AS
REQUIRED TO PROVIDE A RIGID HANGING INSTALLATION.
DO NOT HANG PIPES FROM OTHER PIPES, CONDUIT OR
DUCTWORK. PROVIDE HANGER RODS AND SPACE
HANGERS AT INTERVALS AS REQUIRED.
SOIL, WASTE AND STORM: GRADE SOIL AND WASTE
PIPING TO A UNIFORM SLOPE OF NOT LESS THAN
1/8" PER FOOT FOR PIPING 4" OR LARGER, AND NOT
LESS THAN W PER FOOT FOR PIPING 3" OR SMALLER.
SLOPE STORM PIPING AT 1/8" PER FOOT. LAY PIPE
AT UNIFORM SLOPE, FREE FROM SAGS, WITH HUB END
UPSTREAM. SUPPORT PIPE AT EACH JOINT. MAKE
CHANGES IN DIRECTION FROM HORIZONTAL TO
VERTICAL, AT FIXTURE BRANCHES AND OTHER BRANCH
CONNECTIONS IM SANITARY "TEES" OR SHORT
SWEEP "ELLS ". MAKE CHANGES IN DIRECTION FROM
VERTICAL TO HORIZONTAL OR IN THE HORIZONTAL
WITH LONG RADIUS FITTINGS, LONG SWEEPING "ELLS ",
COMBINATION " Y " FITTINGS, OR 45 DEGREE "ELLS"
(1/8 BEND FITTINGS) AND "Y" FITTINGS.
DOMESTIC WATER: ARRANGE COLD, HOT AND HOT
WATER RECIRCULATION PIPING TO DRAIN AT THE
LOWEST POINT IN EACH SYSTEM. INSTALL AT LEAST
ONE PIPE UNION ADJACENT TO ALL SHUTOFF VALVES,
AT CONNECTION POINT OF EACH PIECE OF EQUIPMENT,
AND ELSEWHERE IN THE SYSTEM WHERE REQUIRED TO
ALLOW PROPER MAINTENANCE. PROVIDE UNIONS OF
THE GROUND JOINT TYPE. MAKE ALLOWANCE FOR
EXPANSION AND CONTRACTION WHERE REQUIRED BY
THE INSTALLATION. WHERE WATER PIPING OCCURS IN
EXTERIOR WALLS, HOLD PIPE AS CLOSE AS POSSIBLE
TO THE INTERIOR FACE OF WALL AND INSTALL
INSULATION BATT OR OTHER INSULATION (MINIMUM R8)
BETWEEN PIPING AND THE EXTERIOR WALL FACE.
15C 1 -4 EXTERIOR UTILITY CONNECTIONS
TERMINATE DOMESTIC WATER, STORM, AND SEWER
LINES AT A POINT APPROXIMATELY FIVE FEET FROM
THE BUILDING WALL, OR AS SHOWN ON THE
DRAWINGS. MAKE CONNECTION TO THE VARIOUS
SERVICES PROVIDED BY OTHERS AND COORDINATE
CONNECTION REQUIREMENTS WITH CIVIL ENGINEER.
VERIFY THAT INSTALLATION WILL 11E INTO THE
VARIOUS SERVICED PROVIDED BY OTHERS AT THE
INDICATED INVERT ELEVATION POINT PRIOR TO
INSTALLATION. IF THE INSTALLATION WILL NOT TIE
INTO THE INDICATED INVERT ELEVATION POINT WHILE
MAINTAINING PROPER FALL, NOTIFY ARCHITECT AND
CIVIL ENGINEER SO THAT AN ALTERNATIVE MAY BE
DETERMINED.
PROVIDE SERVICE PIPING AND ACCESSORIES REQUIRED
TO COMPLETE UTILITY CONNECTIONS THAT ARE NOT
FURNISHED BY THE SERVING UTILITY.
15C 1 -5 SYSTEM TESTING AND ADJUSTING
UPON COMPLETION OF EACH PHASE OF THE
INSTALLATION, TEST EACH SYSTEM IN CONFORMANCE
WITH LOCAL CODE REQUIREMENTS AND AS NOTED
BELOW. FURNISH LABOR AND EQUIPMENT REQUIRED
TO TEST PLUMBING WORK INSTALLED UNDER THIS
CONTRACT, AND ASSUME COSTS INVOLVED IN MAKING
THE TESTS, AND REPAIRING AND /OR REPLACING
DAMAGE RESULTING THEREFROM.
NOTIFY THE ARCHITECT AND THE AUTHORITY HAVING
JURISDICTION, THREE (3) WORKING DAYS PRIOR TO
MAKING PLUMBING SYSTEM TESTS. LEAVE CONCEALED
WORK UNCOVERED UNTIL THE REQUIRED TESTS HAVE
BEEN COMPLETED, BUT IF NECESSARY DUE TO
CONSTRUCTION PROCEDURE, TESTS ON PORTIONS OF
THE WORK MAY BE MADE, AND WHEN SATISFACTORY,
THE WORK MAY BE CONCEALED. TEST PIPING BEFORE
INSULATION IS INSTALLED, AND BEFORE BACKFILL.
PIPES, JOINTS, FLANGES, VALVE STEMS, ETC., SHALL
BE LEAK TIGHT. REPAIR OR REPLACE SYSTEM
DEFECTS WITH NEW MATERIALS. CAULKING OF
DEFECTIVE JOINTS, CRACKS OR HOLES WILL NOT BE
PERMITTED. REPEAT TESTS AFTER DEFECTS HAVE
BEEN ELIMITATED. MAKE TESTS IN THE PRESENCE OF
THE ADMINISTRATIVE AUTHORITY AND /OR THE
OWNER'S AUTHORIZED REPRESENTATIVE.
15C 1 -6 GUARANTEE
THE WORK TO BE PERFORMED UNDER THIS CONTRACT
SHALL INCLUDE THE FURNISHING, INSTALLATION, AND
CONNECTION OF PLUMBING SYSTEMS INDICATED ON
THE DRAWINGS AND IN THE SPECIFICATIONS. BY
SIGNING THE CONTRACT, THE CONTRACTOR
ACKNOWLEDGES THAT HE HAS ACQUAINTED HIMSELF
WITH THE SITE AND THE EXISTING CONDITIONS UNDER
WHICH THE WORK IS TO BE PERFORMED, AND THE
DRAWINGS AND SPECIFICATIONS PERTAINING THERETO,
AND HE INDICATES THAT HE WILL COMPLY WITH THE
REQUIREMENTS AND INTENT OF PERTINENT DOCUMENTS
IN THE PERFORMANCE OF THE WORK.
GUARANTEE THAT THE PLUMBING INSTALLED UNDER
THIS CONTRACT IS FREE OF DEFECTS IN
WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE
(1) YEAR FROM THE DATE OF JOB ACCEPTANCE BY
THE OWNER. THIS SHALL INCLUDE A GUARANTEE OF
FREE CIRCULATION OF LIQUIDS THROUGHOUT THE
SYSTEM AS INTENDED WITHOUT LEAKS, EXCESSIVE
NOISE, OR WATER HAMMER.
IF DEFECTS OCCUR DURING THE ONE YEAR
GUARANTEE PERIOD, REPAIR OR REPLACE SUCH
DEFECTS AT NO EXPENSE TO THE OWNER, AND TO
THE SATISFACTION OF THE OWNER, ARCHITECT AND
ENGINEER.
CODE COMPLIANCE
APPRO
A PR 1 o 2008
City Ofi Tu�lla
BUILDING DIVISION
CITY
RECEIVED
MAR 2 8 2008
PERMIT CENTER
zumez
SOUTSCENTER MALL
SPACE # 2115
633 SOUIIMPINTER
SEATTLE, WA 98188
MURPHY m VAREY,8
DAVID J. MURPHY, AIA
S IM NM= Amas ems Ill
Buss. Tammuz 9m
T: sob . sg . 9$4s
W .9rn
• m. YssraY,arr.omc
Harrison French and
Associates
809 S.W. "A" Street
Bentonville, AR 72712
(479) 273 -7780
fax (479) 273 -943
PROJECT NUMBER: 05.08.02008
ZUMIEZ STORE NUMBER: 19
ISSUED FOR:
PRELIMINARY MALL
REVI Ew
DATE:
02 - - PRELIMINARY MALL REVIEW
SHEET TITLE:
MECHANICAL
SPECS
SHEET NUMBER:
1 EXPIRES: 02/23/10
/I
MP1