HomeMy WebLinkAboutPermit M08-112 - WESTFIELD SOUTHCENTER MALL - OKI DOKIOKI DOKI
2897 SOUTHCENTER MALL
M08-1 12
Parcel No.: 6364200010
Address:
Suite No:
Tenant:
Name:
Address:
Owner:
Name:
Address:
DESCRIPTION OF WORK:
NEW VAV, CONTROLS, AND DUCT DISTRIBUTION
Value of Mechanical: $35,000.00
Type of Fire Protection: SPRINKLES /AFA
doc: I MC -10/06
CiAf Tukwila
Furnace: <100K BTU
>100K BTU
Floor Furnace
Suspended/Wall/Floor Mounted Heater
Appliance Vent
Repair or Addition to Heat/Refrig /Cooling System....
Air Handling Unit <10,000 CFM
>10,000 CFM
Evaporator Cooler
Ventilation Fan connected to single duct
Ventilation System
Hood and Duct
Incinerator: Domestic
Commercial/Industrial
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
2897 SOUTHCENTER MALL TUKW
OKI DOKI
2897 SOUTHCENTER MALL , TUKWILA WA
WESTFIELD PROPERTY TAX DEPT
PO BOX 130940 , CARLSBAD CA
Contact Person:
Name: KEITH SMITH
Address: 1725 WESTLAKE AV N, STE 210 , SEATTLE WA
Contractor:
Name: OKITSU CONSTRUCTION INC.
Address: 1428 WHITWORTH AV S , RENTON WA
Contractor License No: OICITSCI959L8
MECHANICAL PERMIT
EQUIPMENT TYPE AND QUANTITY
0
0
0
0
0
0
0
0
0
1
0
0
0
0
* *continued on next page **
M08 -112
•
Permit Number:
Issue Date:
Permit Expires On:
Phone:
Phone: 206 713 -4076
Phone: 206 714 -9969
Expiration Date: 06/28/2009
M08 -112
06/11/2008
12/22/2008
Fees Collected: $683.75
International Mechanical Code Edition: 2006
Boiler Compressor:
0 -3 HP /100,000 BTU 0
3 -15 HP /500,000 BTU 0
15-30 HP /1,000,000 BTU.. 0
30 -50 HP /1,750,000 BTU.. 0
50+ HP /1,750,000 BTU 0
Fire Damper 0
Diffuser 0
Thermostat 0
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment
Printed: 07 -21 -2008
Permit Center Authorized Signature:
I hereby certify that I have read and e
governing this work will be complied
The granting of this p
doc: I MC -10/06
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
•
Permit Number: MO8 -112
Issue Date: 06/11/2008
Permit Expires On: 12/22/2008
Date: N"
ed this permit and know the same to be true and correct. All provisions of law and ordinances
hether specified herein or not.
t does not presume to give au to violate or cancel the provisions of any other state or local laws regulating
construction or the ce of work I am - uthorize sign and obtain this mechanical permit.
Signature:
Print Name:
d
Date: 7r /- 0
This permit shall become null and void if the work is not c mmenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
M08 -112 Printed: 07 -21 -2008
Parcel No.: 6364200010
Address:
Suite No:
DESCRIPTION OF WORK:
NEW VAV, CONTROLS, AND DUCT DISTRIBUTION
Value of Mechanical: $35,000.00
Type of Fire Protection: SPRINKLES /AFA
Furnace: <100K BTU
>100K BTU
Floor Furnace
Suspended/Wall/Floor Mounted Heater
Appliance Vent
Repair or Addition to Heat/Refrig /Cooling System....
Air Handling Unit <10,000 CFM
>10,000 CFM
Evaporator Cooler
Ventilation Fan connected to single duct
Ventilation System
Hood and Duct
Incinerator: Domestic
Commercial/Industrial
doc: IMC-10/06
Citytf Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
2897 SOUTHCENTER MALL TUKW
Tenant:
Name: WESTFIELD VANILLA BOX
Address: 2897 SOUTHCENTER MALL , TUKWILA WA
Owner:
Name: WESTFIELD PROPERTY TAX DEPT
Address: PO BOX 130940 , CARLSBAD CA
Contact Person:
Name: KEITH SMITH
Address: 1725 WESTLAKE AV N, STE 210 , SEATTLE WA
Contractor:
Name: OKITSU CONSTRUCTION INC.
Address: 1428 WHITWORTH AV S , RENTON WA
Contractor License No: OKITSCI959L8
MECHANICAL PERMIT
Fees Collected: $563.75
International Mechanical Code Edition: 2006
EQUIPMENT TYPE AND QUANTITY
0
0
0
0
0
0
0
0
0
1
0
0
0
0
* *continued on next page **
•
Permit Number: M08 -112
Issue Date: 06/11/2008
Permit Expires On: 12/08/2008
Phone:
Phone: 206 713 -4076
Phone: 206 714 -9969
Expiration Date: 06/28/2009
Boiler Compressor:
0-3 HP /100,000 BTU 0
3 -15 HP /500,000 BTU 0
15-30 HP /1,000,000 BTU.. 0
30 -50 HP/1,750,000 BTU.. 0
50+ HP /1,750,000 BTU 0
Fire Damper 0
Diffuser 0
Thermostat 0
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment
M08 -112 Printed: 06-11 -2008
Permit Center Authorized Signature:
governing this work will be complie
Signature:
Print Name:
doc: IMC-10/06
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
aeve4/ 46
, whether specified herein or not.
•
Permit Number: M08 -112
Issue Date: 06/11/2008
Permit Expires On: 12/08/2008
VJ "-_` Date: tigt ( /,
I hereby certify that I have read and x ed this permit and know the same to be true and correct. All provisions of law and ordinances
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the .erformance of work. authorized to sign and obtain this mechanical permit.
Date: (fike)
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
M08 -112 Printed: 06 -11 -2008
•
City of Tukwila
Parcel No.: 6364200010
Address: 2897 SOUTHCENTER MALL TUKW
Suite No:
Tenant: OKI DOKI
1: ** *BUILDING DEPARTMENT CONDITIONS * **
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
PERMIT CONDITIONS
•
Permit Number: M08 -112
Status: ISSUED
Applied Date: 04/24/2008
Issue Date: 06/11/2008
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431 - 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
6: Manufacturers installation instructions shall be available on the job site at the time of inspection.
7: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431- 3670).
8: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
9: ** *FIRE DEPARTMENT CONDITIONS * **
10: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
11: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
12: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
13: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
14: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
15: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
doc: Cond -10/06
M08 -112 Printed: 07 -21 -2008
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
•
16: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
17: An electrical permit from the City of Tukwila Building Department Permit Center (206- 431 -3670) is required for this
project.
18: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
19: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
20: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: Cond -10/06
* *continued on next page **
M08 -112 Printed: 07 -21 -2008
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http://www.ci.tukwila.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating
construction or the performance of work.
Signature:
Print Name:
doc: Cond -10/06
7
6 4-v-6 (,)D ,
Date: -2- Z f -o
M08 -112 Printed: 07 -21 -2008
Parcel No.: 6364200010
Address:
Suite No:
Tenant:
1: ** *BUILDING DEPARTMENT CONDITIONS * **
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
2897 SOUTHCENTER MALL TUKW
WESTFIELD VANILLA BOX
PERMIT CONDITIONS
•
Permit Number:
Status:
Applied Date:
Issue Date:
M08 -112
ISSUED
04/24/2008
06/11/2008
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431- 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
6: Manufacturers installation instructions shall be available on the job site at the time of inspection.
7: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431- 3670).
8: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
9: ** *FIRE DEPARTMENT CONDITIONS * **
10: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
11: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
12: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
13: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
14: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
15: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
doc: Cond -10/06
M08 -112 Printed: 06 -11 -2008
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
•
16: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
17: An electrical permit from the City of Tukwila Building Department Permit Center (206- 431 -3670) is required for this
project.
18: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
19: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
20: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: Cond - 10/06
* *continued on next page **
M08 -112 Printed: 06-11 -2008
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
•
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work
construction or the performance of work.
Signature:
Print Name: . aa- Pt^PJ4 1 4-
doc: Cond -10/06 M08 -112
Date: 3/` 1/c.)
ordinances governing
or local laws regulating
Printed: 06-11 -2008
Site Address:
Tenant Name:
Property Owners Name:
Mailing Address:
,. X �-i r rr "�' i.. "�' c.�^J ' if �+ ' PO-f' ,
,who,0o+we contact when yodr permit tis be issued .:
f :d r.r r . s iy.
.. S R.. .. J• � ...'•:a �.. d� s ... G: 3. �.. �r.rJr :.., , r ..h.... :./, .L. 4,i
Name:
Mailing Address:
E -Mail Address: KSi'1' 1� G �/ S G 1 !�1 CQver :Number: � Q stat 464 O J
GE f CONi'RAC I OR { INFORMATION
(Gong actonformahon for "`Mecb'anlcal (pg 4) for Plumbing and
Mailing Address:
City
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date:
Company Name:
Mailing Address:
Contact Person:
E -Mail Address:
ENGINEER ; 1') A EC
Company Name:
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http: //www. ci. tukwila. wa. us
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
KALTIIIIIIIMMIIEZMT 44
LA Day T lephone:
17A5 f ie ' S 4 Z e 5We Vo % 09
=TECT14)F•: tke.
Sill
not
/.d
1 p lan s ,mu 9
Af
City
p t r td �'4'4N �.r , ,.. t. '� - .. J•L f, +' s> f r Y
lans ( must be wet st of ]
1;1..
Pe
I
King Co Assessor's Tax No.: 63020 - -Ocfl 2) ,
Suite Number: .34 -a ! Floor: 2.Jet
New Tenant: Yes El „No
ngmmeer obReco
City
Day Telephone:
Fax Number:
tate
State
�ecorn
State
State
Zip
p
Mailing Address:
City
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Q:wppllations\Pom s- Appbcadons On L nM3 -2006. Permit Application.doe
Revise& 9-2006
bb
Zip
Page 1 of 6
" .A ar`
'uv. /•'^ i �'- r',. t t' a
i � : r Jr f4fe !! t �' Sti '1i _
"a' )l h �hitl :1,46 t .r.
^� 4 fi t . i t ,
3 5` r )/ rS}w{
.� l
_
i - . !
Y _} }'" .. ;,,
k A.p ra ... SIY. 6
in norRemo de1
• h Additiont[l. ,y`
J ar r, r.
{t }�.. f
Jf EXlstmgY 1.
, -1, :Structure
a r : r a s�
t _�, ..,�
S r T - nid' � �,
New . _. ,!
;'"`'Type"'of
.. y -
rC a s
ConstlUCt�on'per
„ .. '18C.,. ,; .or..
. rt Tv , >.;ofre
-,., y �
.✓r / yea,... en
OCCUpanCy]pen�
'r, 1B -` 4
1rt orT hG $T °( f.i
e a
lO ''17 �
'`fMe a�iT f: y�.: «, •'�
(�
..• O
I -
f
FFloors °.a J`' thril ", :i ry° 4
t r r }
:J....,cf: ?ea.t?`ih4 Nr:l•i /r t,Y '::ft':
°Accesso Strucnire *' ';
k x c ., N- v r>s<, c•�i �::%Y�., ..Y•s' 4 -d •.✓.'r.T,
'Attached •Garage+ rrw F
g.
Detadied:Oiirige :,' �'i`��
jAttacbed:Cai OftYT r *•" <'; e"
r5}6?F,..44 1 J:ty.a: 2: .l�i.'.t
•rDetaclied Gault ""
F: Cove'ie$ Deck
',.. i:.pr as , y ,._
.
Uncgvered'Dee * ,ai.
DINGwPER]VIITSINFO TIO1CPCIO A LT W
Valuation of Project (contractor's bid price):
Scope of Wo k (p e prov' 'e detailed • formation):
a.ke plv�bih�
Will there be new rack storage? ❑ Yes
Existing Building Valu ° ion: $
[No If yes, a separate permit and pl submittal will be required.
ovide�All�Building `Ar tnSq uare
j. • 4.k.. yr .s. f..; M 1� n,l• 1 "
PL Pi 11 G D SIO
Single family building fo • +• tint (area of the foundation of all structures, plus any decks over 18 inc s and overhangs greater than 18 inches)
'For an Accessory d g „ a ide the following:
Lot Area (sq : ♦ 1 Floor area of principal dwelling: ' or area of accessory dwelling:
'Provide d . r entation that shows that the principal owner lives in one of the dwellings as his or ' primary residence.
Number of Par • : Stalls Provided: Standard: Compact: Handicap:
Will there be ange in use? ❑ Yes No If `yes ", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
IV Sprinklers t. )••' Automatic Fire Alarm None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materia in the building? ❑ Yes 12/ No
If 'yes', attach list of materials and storage locations on a separate 8 -1/2 "x 11 " paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
❑ On -site Septic System —For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
o:\AwlicationsWorms-Applications On LineO -2006 - Permit AWlieal on.doe
Revise& 9 -2006
bh
Page 2 of 6
Unit.Type :.
Qty
Unit.Type:.. - ` ; .
Qty,
, .Unit:Type:.
Qty .
Boiler /Compiessor
Qty»
Furnace<100K BTU
Air Handling Unit >10,000
CFM
Fire Damper
0-3 HP /100,000 BTU
Fumace>100K BTU
Evaporator Cooler
Diffuser
3 -15 HP /500,000 BTU
Floor Furnace
Ventilation Fan Connected
to Single Duct
(
Thermostat
15 -30 HP /1,000,000 BTU
Suspended/Wall/Floor
Mounted Heater
Ventilation System
Wood/Gas Stove '
30 -50 HP /1,750,000 BTU
Appliance Vent
Hood and Duct
Emergency
Generator
.
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Refrig/Cooling
System
Incinerator - Domestic
Other Mechanical
uip e D✓
TVt ItT 1
Air Handling Unit
<10,000 CFM
Incinerator — Command
t1VIECHANICAL` PERMIT INFURMATION'' 206- 431 " 3670
c..: .,. u1'4 t .r ,
...Iv. '. .., .� : ,vs` - y, ':v ••• ads..:" . C*4, L.'"tQ7� us5a
MECHANICAL CONT INFORMATION
Company Name:
Mailing Address:
City State Zip
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date:
Valuation of Mechanical work (contractor's bid price): $
Scope of Work (plpase pryide etailpd information):
/
Use: Residential: New .... ❑ Replacement .... ❑
Commercial: New ... Replacement .... ❑
Fuel Type: Electric
Gas .... ❑ Other:
Indicate type of mechanical work being installed and the quantity below:
Q; Applications\Fomu- Applications On Lineu -2006 - Permit Appliwdon.doc
Revised 9 -2006
bh
Page 4 of 6
j'iiiture Type.. ° a ?� Y
t.Qty :�
Vikture ; Type , . . =47.`
of , - *
iii t pe! 0 : ,
Q !'
ii,' : ' *
Gas piping outlets
Qh'
Bathtub or combination
bath/shower
Drinking fountain or water
cooler (per head)
W : ` , fountain
Bidet
Food -waste grinder,
commercial
Receptee, indirect
waste
Clothes washer, domestic
Floor drain
/
Sinks
Dental unit, cuspidor
Shower, single he • . • p
Urinals
Dishwasher, domestic,
with independent drain
Lavatory
/
Water Closet
/
Building sewer or trailer
park sewer
Rain water sy m — per
drain (insid , . uiding)
Water heater and/o ' ,
vent
Additional medical gas
inlets/outlets — six or more
Industrial waste
pretreatment interceptor,
including its trap and vent,
except for kitchen type
grease interceptors
Repair or alteration of water
piping and/or water treating
equipment
Repair or alteration
of drainage or vent
piping,
Medical gas piping system
serving one to five
inlets/outlets for specific gas
PLUMBING AND GAS PIPING CONTRACTOR INFORMATION
Company Name:
D
Mailing Address:
City
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Nu ' ber: Expiration Date:
Building Use (per Int'l Building Code):
Occupancy (per Int'1 Building Code):
Utility Purveyor: Water: 7'v
Q: 1ApplicationsWoma- Applications On Linel3 -2006 - Permit Application.doe
Revised 9-2006
bb
State
Valuation of Plumbing work (con or's bid price): $ 2 000
Valuation of Gas Piping work (contra ar's bid price): $
Scope of Work (please provide detailed i ' ormation):
Indicate type of plumbing fixtures and/or gas piping outlets being
new cref-,
Sewer:
led and the quantity below:
Zip
Page 5 of 6
LICATIO (NOTES' ; A`' �licatil
`i 1h�a ".ti5?s:ck!`�j.? ASS PPw c1
o allpermits n thls 'appLcat
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
Building and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
Plumbing Permit
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNE
Signature:
.r. WHIPII III L
Print Name:
Mailing Address:
Date Application Expires:
[01?)-(toL
Date Application Accepted:
RIZED AGENT:
QMpplicffilonsWomu- Applications On Line3 -2006 - Permit Application.doc
Revised: 9 -2006
bb
ephone:
Date: 4(4-(e
A / ,
Il / 0 /
State
Staff Initials:
Page 6 of 6
RECEIPT NO: R08 -02677
Initials: JEM
User ID: 1165
Payee: DAVID R. WORLEY
SET ID: 0717 SET NAME: WESTFIELD REVISIONS
SET TRANSACTIONS:
Set Member Amount
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
D08 -143 71.88
D08 -168 618.36
D08 -169 60.00
D08 -218 71.88
D08 -219 60.00
D08 -221 60.33
D08 -225 60.33
D08 -240 71.88
M08 -081 60.00
M08 -082 60.00
M08 -083 60.00
M08 -095 71.25
M08 120.00
M08 -113 60.00
M08 -114 60.00
M08 -115 60.00
M08 -116 60.00
M08 -124 60.00
TOTAL: 1,745.91
SET RECEIPT
TRANSACTION LIST:
Type Method Description Amount
Payment Check 1115 1,745.91
TOTAL: 1,745.91
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
Payment Date: 07/21/2008
Total Payment: 1,745.91
5109 07 /31 71) TOTO 1745,91
nom..• RP1 im_nn
BUILDING - NONRES
MECHANICAL - NONRES
PLAN CHECK - NONRES
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: //www.ci.tukwila.wa.us
000/322.100 360.40
000.322.102.00.0 669.00
000/345.830 716.51
TOTAL: 1,745.91
RECEIPT NO: R08 -02074
Initials: WER
User ID: 1655
SET TRANSACTIONS:
Set Member
M08 -081
M08 -082
M08 -083
M08 -095
M08 -096
1F2
MO8
1
1
MO8-
MO8 -114
M08 -115
MO8 -116
M08 -152
TOTAL:
ACCOUNT ITEM LIST:
Description
MECHANICAL - NONRES
PLAN CHECK - NONRES
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http. //www.ci.tukwila.wa.us
Payee: OKITSU CONSTRUCTION, INC.
Amount
406.00
406.00
406.00
406.00
406.00
811.00
811.00
811.00
811.00
811.00
244.00
6,329.00
Payment Check 1664
SET RECEIPT
Payment Date: 06/11/2008
Total Payment: 6,329.00
SET ID: 0611 SET NAME: WESTFIELD MECHANICAL
TRANSACTION LIST:
Type Method Description Amount
TOTAL:
6,329.00
6,329.00
Account Code Current Pmts
000.322.102.00.0 4,529.00
000/345.830 1,800.00
TOTAL: 6,329.00
3540 06/11 9711 TOTAL 6329.00
irprIq mil
RECEIPT NO: R08 -01303
Initials: JEM
User ID: 1165
Payee: WESTFIELD
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http. //www.ci.tukwila.wa.us
SET ID: 5000001008 SET NAME: Tmp set /Initialized Activities
SET TRANSACTIONS:
Set Member Amount
D08 -218 895.70
EL08 - 460 123.00
MQ8'- �1L1a2 112.75
PG08 -128 29.00
TOTAL: 1,160.45
TRANSACTION LIST:
Type Method Description
Payment Check 06012499
ACCOUNT ITEM LIST:
Description
ELECTRICAL PLAN - NONRES
PLAN CHECK - NONRES
SET RECEIPT
TOTAL:
•
Payment Date: 04/24/2008
Total Payment: 1,160.45
Amount
1,160.45
1,160.45
Account Code Current Pmts
000.345.832.00.0 123.00
000/345.830 1,037.45
TOTAL: 1,160.45
1594 04/24 9711 TOTAL 1160445
COMMENTS:
R IMJN- ; &-1 - A.p av 0
p er n -A- o ew P 1 a: , f 1= I N et ......
Address:
2 e 1M A I t
Date Called:
NoTg: 73)11,A Retort -A v fir°
Special Instructions:
Date Wanted:
7 - z
- '
&
_a
p.m.
Project:
dIC`r - Do
Type Inspection:
1`it.a4 1
V
Address:
2 e 1M A I t
Date Called:
Special Instructions:
Date Wanted:
7 - z
- '
&
_a
p.m.
Requester:
Phone No:
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION le,
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -36
Approved per applicable codes. El Corrections required prior to approval.
INSPECTION RECORD
Retain a copy with permit
0 I is
PERMIT NO.
Date:
"7- Zg- '
EJ $60 +0 REINSPECTION FEE R QUIRED. Prior to inspection, fee must be
pa at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
(Receipt No.:
'Date:
Project: t • L7o I.
T Inspection:
ectio�n Qw r
Address: e '7
141/1‘
Date Called:
Special Instructions:
Date Wanted /
/ $ 1 D r
a.m.
p.m.
Requester:
Phone No:
I •
3
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION 4 -
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
.Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
SerJeS Z - vivii -1
Inspecto
$60.00 REINSPECTION FEE REQ IRE
Date: — 7/ $/
El D. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
'Receipt No.:
'Date:
Projgga
• Type Inspection
Addr P fi — i,�^� o-'
Date Called:
Special Instructions:
Date Wa�� :
O�
a.m.
Requester:
Phone A( - 8 -5
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
0
PERMIT NO.
r. y
(206)431 -36(70
Approved per applicable codes.
El Corrections required prior to approval.
Inspector: _ a (Date: 2s 1 p
$60.00 REINSPECTION FEE REQUIRED. Prior to inspedtion, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
'Date:
COMMENTS:
4
a(L
tzcen B . r
sap
Project:
Type of Inspection:
14
Address:
c 7 pidgi r
Date Called:
Special Instructions:
Date Wanted:
'—er �a m
Requester:
Phone N
206 - L/(
- 0g6 5'
1
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
�fZ
CITY OF TUKWILA BUILDING DIVISION le-
PERMIT NO.
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
a pproved per applicable codes. Corrections required prior to approval.
COMMENTS: eA
.,, rrEpic a lc i a X44/4_
Inspector: Date: /^ 23,
$60.00 R INSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
'Date:
COMMENTS:
Sprinklers:
Type of Inspection:
F,' N rc t, F; hc. 1 i. r j f
t
0) FA O K
. ce el l Hr
4 CC( v
C , ( e (c (c-vr v „A.-2 --- or c GC'�
� .JS e'
L-,- Q
1ec -s O
�J , I 0.r`} Chvv,* a. of dc-r rl
eh,e,t�. 1 7
i?k, nz<-.
1,.Srt - c
4 , -rv4( ,c .
c ,ec4,.
,,.,„1 OL<- _
Project: // //
c)A ' Do /� I
Sprinklers:
Type of Inspection:
F,' N rc t, F; hc. 1 i. r j f
t
Monitor:
Address: G s t
Suite #:
�` i(
Conta Person: J
& F Gc 04,+1,
J
1
Special Instructions:
Phone No.:
o(..- 3 l _ . Ua2cp
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
INSPECTION NUMBER
444 Andover Park East, Tukwila, Wa. 98188 206- 575 -4407
CITY OF TUKWILA FIRE DEPARTMENT
Approved per applicable codes.
INSPECTION RECORD
Retain a copy with permit
r) (- r
PERMIT NUMBERS
Corrections required prior to approval.
Inspector:
Date: - 7 -) 5-6
Hrs.:
n $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Word /Inspection Record Form.Doc 1/13/06
T.F.D. form F.P,
Project Info
Project Address
2897 Southcenter Mall
Date 4/4/2008
Tukwila, WA 98188
For Building Department Use
Applicant Name:
Keith L. Smith
Applicant Address:
1725 WestlakeAve.
N. ,
Suite
210
Applicant Phone:
Seattle, WA 98109
Project Summary
PRJSUM
2006 Washington State Nonresidential Energy Code Compliance Forms
2006 Washington State Nonresidential Energy Code Compliance Form
CITYROF TUKWILA
APR 2 4 2008
PERMIT CENTER
Revised July 2007
Fan Equipment Schedule
Equip.
ID
Brand Name'
Model No.
CFM
SP
HP /BHP
Flow Control
Location of Service
EF -1
GREENHECK
SP -B110
100
80
80 W
CV
M -1
Applicant Name:
M -1
Applicant Address:
1725 WestlakeAve.
N.,
Suite
210
Applicant Phone:
Seattle, WA 98109
Cooling Equipment Schedule
Equip.
ID
Brand Name
Model No.
Capacity
Btu /h
Total CFM
OSA CFM
or Econo?
SEER
or EER
IPLV
Location
FMB -1
TITUS
DTFS SIZE D
80
500
Econo
Applicant Name:
M -1
Applicant Address:
1725 WestlakeAve.
N.,
Suite
210
Applicant Phone:
Seattle, WA 98109
Heating Equipment Schedule
Equip.
ID
Brand Name
Model No.
Capacity
Btu /h
Total CFM
OSA cfm
or Econo?
Input Btuh
Output Btuh
Efficiency°
FMB-1
TITUS
3
Applicant Name:
Keith L. Smith
Applicant Address:
1725 WestlakeAve.
N.,
Suite
210
Applicant Phone:
Seattle, WA 98109
Project Info
Project Address
2897 Southcenter Mall
Date 4/4/2008
Tukwila, WA 98188
For Building Dept. Use
Applicant Name:
Keith L. Smith
Applicant Address:
1725 WestlakeAve.
N.,
Suite
210
Applicant Phone:
Seattle, WA 98109
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Summary
MECH;SUM
2006 Washington State Nonresidential Energy Code Compliance Forms
Project Description
Briefly describe mechanical
system type and features.
Includes Plans
Drawings must contain notes requireing compliance with commissioning requirements - Section 1416
tlf available. 2 As tested accord ng to Table 14-1A through 14-1G. 3 If required. 4 COP, HSPF, Combustion Efficiency, or AFUE, as
applicable. 5 Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS).
Revised July 2007
Compliance Option
Simple System 0 Complex System 0 Systems Analysis
(See Decision Flowchart (over) for qualifications. Use separate MECH -SUM for simple & complex systems.)
Equipment Schedules
The following information is required to be incorporated with the mechanical equipment schedules on the
plans. For projects without plans, fill in the required information below.
System Description
See Section 1421 for full description of
Simple System qualifications.
If Heating /Cooling
or Cooling Only:
❑ Constant vol?
❑ Split system?
❑ Air cooled? ❑ Packaged sys? ❑ <20,000 Btuh?
❑ Economizer included?
If Heating Only:
<
� <5000 dm?
❑ <70% outside air?
( START )
Heating Only
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Summary (back)
MECH -SUM
Decision Flowchart
Use this flowchart to determine if project qualifies for Simple System Option. If not, either the
Complex System or Systems Analysis Options must be used.
Simple System
Allowed
(section 1420)
otal Ca .
wo economize
<240,000 Btuh
or 10 %?
Reference
Section 1421
Heating /Cooling
or Cooling Only
C Reference
Section 1423
Use Complex
Systems
(section 1430)
Complex Systems
Refer to MECH -COMP Mechanical Complex Systems for assistance in determining which Complex
Systems requirements are applicable to this project.
Mechanical Permit Plans Checklist
2006 Washington State Nonresidential Energy Code Compliance Forms
MECH; CHK
Revised July 2007
Project Address 2897 Southcenter Mall
Date 4/4/2008
The following information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the
Washington State Nonresidential Energy Code.
Applicability
PP tY
(yes, no, n.a.)
Code
I Section
I Component
I Information Required
Location
on Plans
Building Department
9 P
Notes
HVAC REQUIREMENTS (Sections 1401 -1424)
1411
Equipment performance
1411.4
Pkg. elec. htg.& clg.
List heat pumps on schedule
yes
1411.1
Minimum efficiency
Equipment schedule with type, capacity, efficiency
M -2
1411.1
Combustion htg.
Indicate intermittent ignition, flue /draft damper & jacket loss
1412
HVAC controls
yes
1412.1
Temperature zones
Indicate locations on plans
M -1
1412.2
Deadband control
Indicate 5 degree deadband minimum
1412.3
Humidity control
Indicate humidistat
1412.4
Automatic setback
Indicate thermostat with night setback and 7 diff. day types
1412.4.1
Dampers
Indicate damper location and auto. controls & max. leakage
1412.4.2
Optimum Start
Indicate optimum start controls
1412.5
Heat pump control
Indicate microprocessor on thermostat schedule
1412.6
Combustion htg.
Indicate modulating or staged control
1412.7
Balancing
Indicate balancing features on plans
1412.8
Ventilation Control
Indicate demand control ventilation for high - occupancy areas
1422
Thermostat interlock
Indicate thermostat interlock on plans
1423
Economizers
Equipment schedule
1413
Air economizers
1413.1
Air Econo Operation
Indicate 100% capability on schedule
1413.1
Wtr Econo Operation
Indicate 100% capacity at 45 degF db & 40 deg F wb
1413.2
Water Econo Doc
Indicate clg load & water econoe & clg tower performance
1413.3
Integrated operation
Indicate capability for partial cooling
1413.4
Humidification Indicate direct evap or fog atomization w/ air economizer
1414
Ducting systems
1414.1
Duct sealing
Indicate sealing necessary
1414.2
Duct insulation
Indicate R -value of insulation on duct
1415.1
Piping insulation
Indicate R -value of insulation on piping
1416
Completion Requirements
1416.2.1
Commissioning
Provide commissioning plan
1416.2.2 -3
Sys.Bal & Func.Test
Indicate air and water system balancing & functional testing
1416.2.4
Commissioning
Indicate O &M manuals, record drawings, staff training
1416.2.5
Comm. Report
Indicate requirements for prelim. & final commissioning report
1434
Separate air sys.
Indicate separate systems on plans
yes Mechanical
(Summary Form
Completed and attached. Equipment schedule with types,
input/output, efficiency, cfm, hp, economizer
I I
SERVICE WATER HEATING AND HEATED POOLS (Sections 1440 -1454)
1440
Service water htg.
1441
Elec. water heater
Indicate R -10 insulation under tank
1442
Shut -off controls
Indicate automatic shut -off
1443
Pipe Insulation
Indicate R -value of insulation on piping
1452
Heat Pump COP
Indicate minimum COP of 4.0
1452
Heater Efficiency
Indicate pool heater efficiency
1453
Pool heater controls
Indicate switch and 65 degree control
1454
Pool covers
Indicate vapor retardant cover
1454
Pools 90+ degrees
Indicate R -12 pool cover
2006 Washington State Nonresidential Energy Code Compliance Form
no is circles for any question, proviae explanation:
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Permit Plans Checklist
MECH -CHK
2006 Washington State Nonresidential Energy Code Compliance Forms
Revised July 2007
Mechanical - General Requirements
1411.1 General: Equipment shall have a minimum performance at the specified
rating conditions not less than the values shown in Table 14 -1A through 14 -1G. If a
nationally recognized certification program exists for a product covered in Tables
14 -1A through 14-1G, and it includes provisions for verification and challenge of
equipment efficiency ratings, then the product shall be listed in the certification
program.
Gas -fired and oil -fired forced air furnaces with input ratings > 225,000 Btu /h (65
kW) and all unit heaters shall also have an intermittent ignition or interrupted device
CID), and have either mechanical draft (including power venting) or a flue damper. A
vent damper is an acceptable alternative to a flue damper for furnaces where
combustion air is drawn from the conditioned space. All furnaces with input ratings >
225,000 Btu/h (65 kW), including electric furnaces, that are not located within the
conditioned space shall have jacket losses not exceeding 0.75% of the input rating.
1411.2 Rating Conditions: Cooling equipment shall be rated at ARI test conditions
and procedures when available. Where no applicable procedures exist, data shall
be furnished by the equipment manufacturer.
1411.3 Combination Space and Service Water Heating: For combination space
and service water heaters with a principal function of providing space heat, the
Combined Annual Efficiency (CAE) may be calculated by using ASHRAE Standard
124 -1991. Storage water heaters used in combination space heat and water heat
applications shall have either an Energy FActor (EF) or a CAE of not less than the
following:
1411.4 Packaged Electric Heating and Cooling Equipment: Packaged electric
equipment providing both heating and cooling with a total cooling capacity greater
than 20, Btu /h shall be a heat pump.
Exception: Unstaffed equipment shaelters or cabinets used solely for
personal wireless service facilities.
1412 Controls
1412.1 Temperature Controls: Each system shall be provided with at least one
temperature control device. Each zone shall be controlled by individual thermostatic
controls responding to temperature within the zone. At a minimum, each floor of a
building shall be considered as a separate zone.
1412.2 Deadband Controls: When used to control both comfort heating and
cooling, zone thermostatic controls shall be capable of a deadband of at least 5
degrees F within which the supply of heating and cooling energy to the zone is shut
off or reduced to a minimum.
Exceptions:
1. Special occupancy, special usage, or code requirements where
deadband controls are not appropriate.
2. Buildings complying with Section 1141.4, if in the proposed building
energy analysis, heating and cooling thermostat setpoints are set to
the same temperature between 70 degrees F and 75 degrees F
inclusive, and assumed to be constant throughout the year.
3. Thermostats that require manual changeover between heating and
cooling modes.
1412.3 Humidity Controls: If a system is equipped with a means for adding
moisture, a humidistat shall be provided.
1412.4 Setback and Shut -Off: HVAC systems shall be equipped with automatic
controls capable of accomplishing a reduction of energy use through control setback
or equipment shutdown during periods of non -use or alternate use of the spaces
served by the system. The automatic controls shall have a minimum seven -day
clock and be capable of being set for seven different day types per week. It must
retain programming and time for a power loss of 10 hours and include an accessible
manual override of up to 2 hours.
Exceptions:
1. Systems serving areas which require continuous operation at the
same temperature setpoint.
2. Equipment with full load demands of 2 kW (6,826 Btu /h) or less may
be controlled by readily accessible manual off -hour controls.
3. Systems controlled by an occupant sensor that is capable of shutting
the system off when no occupant is sensed for a period of up to 30
minutes.
4. Systems controlled solely by a manually operated timer capable of
operating the system for no more than two hours.
1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets serving
conditioned spaces shall be equipped with dampers which close automatically when
the system is off or upon power failure. Stair shaft and elevator shaft smoke relief
openings shall be equipped with normally open (fails to open upon loss of power)
dampers. These dampers shall remain closed until activated by the fire alarm
system or other approved smoke detection system.
Exceptions:
1. Systems serving areas which require continuous operation.
2. Combustion air intakes.
3. Gravity (nonmotorized) dampers are acceptable in buildings less
than 3 stories in height.
4. Gravity (nonmotorized) dampers are acceptable in exhaust and relief
outlets in the first story and levels below the first story of buildings
three or more stories in height.
1412.4.2 Optimum Start Controls: Heating and cooling systems with design supply
1412.8 Ventilation Controls for High- Occupancy Areas: Demand control
ventilation (DCV) is required for spaces that are larger than 500 ft2, have a design
occupancy for ventilation of greater than 40 people for 1000 ft2 of floor area, and are
served by systems with one or more of the following:
a. An air -side economizer,
b. Automatic modulating control of the outdoor air damper, or
c. A design outdoor airflow greater than 3000 cfm.
Exceptions:
1.Systems with energy recovery complying with Section 1438.
2. Multiple -zone systems without direct - digital control of individual zones
communicating with a central control panel.
3. Systems with a design outdoor airflow less than 1200 cfm.
4. Spaces where the supply airflow rate minus any makeup or outgoing
transfer air requirement is less than 1200 cfm.
1413 Air Economizers
1413.1 Operation: Air economizers shall be of automatically modulating outside and
return air dampers to provide 100 percent of the design supply air as outside air to
reduce or eliminate the need for mechanical cooling. Water economizers shall be
capable of providing the total concurrent cooling load served by the conneted
terminal equipment lacking airside economizer, at outside air temperatures of 45 ° F
dry- bulb /40 ° F wet -bulb and below. For this calculation, all factors including solar and
internal load shall be the same as those used for peak load calculations, except for
the outside temperatures.
Exception: Water economizers using air - cooled heat rejection equipment
may use a 35 ° F dry-bulb outside air temperature for this calculation. This
exception is limited to a maximum of 20 tons per building.
1413.2 Documentation: Water economizer plans submitted for approval shall
include the following information:
1. Maximum outside air conditions for which economizer is sized to provide
full cooling.
2. Design cooling load to be provided by economizer at this outside air
condition.
3. Heat rejection and terminal equipment performance data including model
number, flow rate, capacity, entering and leaving temperature in full
economizer cooling mode.
1413.3 Integrated Operation: Air economizers shall be capable of providing partial
cooling even when additional mechanical cooling is required to meet the remainder
of the cooling load.
Exceptions:
1. Individual, direct expansion units that have a rated capacity less than
65,000 Btu /h and use nonintegrated economizer controls that
preclude simultaneous operation of the economizer and mechanical
cooling.
2. Water - cooled water chillers with waterside economizer.
1413.4 Humidification: If an air economizer is required on a cooling system for
which humidification equipment is to be provided to maintain minimum indoor
humidity levels, then the humidifier shall be of the adiabatic type (direct evaporative
media or fog atomization type).
Exceptions:
1. Health care facilities where WAC 246- 320 -525 allows only steam
injection humidifiers in ductwork downstream of final filters. 1412.6
Combustion Heating Equipment Controls: Combustion heating
equipment with a capacity over 225,000 Btu /h shall have modulating
or staged combustion control.
2. Systems with water economizer
3. 100% outside air systems with no provisions for air recirculation to the
central supply fan.
4. Nonadiabatic humidifiers cumulatively serving no more than 10% of a
building's air economizer capacity as measured in cfm. This refers to
the system cfm serving rooms with stand alone or duct mounted
humidifiers.
1414 Ducting Systems
1414.1 Sealing: Duct work which is designed to operate at pressures above 1/2 inch
water column static pressure shall be sealed in accordance with Standard RS -18.
Extent of sealing required is as follows:
1. Static pressure: 1/2 inch to 2 inches; seal transverse joints.
2. Static pressure: 2 inches to 3 inches; seal all transverse joints and
longitudinal seams.
3. Static pressure: above 3 inches; seal all transverse joints, longitudinal
seams and duct wall penetrations.
Duct tape and other pressure sensitive tape shall not be used as the primary
sealant where ducts are designed to operate at static pressures of 1 inch W.C. or
greater.
1414.2 Insulation: Ducts and plenums that are constructed and function as part of
the building envelope, by separating interior space from exterior space, shall meet all
applicable requirements of Chapter 13. These requirements include insulation
installation, moisture control, air leakage, and building envelope insulation levels.
Unheated equipment rooms with combustion air louvers must be isolated from the
conditioned space by insulating interior surfaces to a minimum of R -11 and any
exterior envelope surfaces per Chapter 13. Outside air ducts serving individual
supply air units with less than 2,800 cfm of total supply air capacity shall be insulated
to a minimum of R -7 and are not considered building envelope. Other outside air
duct runs are considered building envelope until they,
1. connect to the heating or cooling equipment, or
2. are isolated from the exterior with an automatic shut -off damper complying
EF
CAE
< 50 gal storage
0.58
0.71
50 to 70 gal storage
0.57
0.71
> 70 gal storage
0.55
0.70
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Permit Plans Checklist
MECH -CHK
2006 Washington State Nonresidential Energy Code Compliance Forms
Revised July 2007
Mechanical - General Requirements
1411.1 General: Equipment shall have a minimum performance at the specified
rating conditions not less than the values shown in Table 14 -1A through 14 -1G. If a
nationally recognized certification program exists for a product covered in Tables
14 -1A through 14-1G, and it includes provisions for verification and challenge of
equipment efficiency ratings, then the product shall be listed in the certification
program.
Gas -fired and oil -fired forced air furnaces with input ratings > 225,000 Btu /h (65
kW) and all unit heaters shall also have an intermittent ignition or interrupted device
CID), and have either mechanical draft (including power venting) or a flue damper. A
vent damper is an acceptable alternative to a flue damper for furnaces where
combustion air is drawn from the conditioned space. All furnaces with input ratings >
225,000 Btu/h (65 kW), including electric furnaces, that are not located within the
conditioned space shall have jacket losses not exceeding 0.75% of the input rating.
1411.2 Rating Conditions: Cooling equipment shall be rated at ARI test conditions
and procedures when available. Where no applicable procedures exist, data shall
be furnished by the equipment manufacturer.
1411.3 Combination Space and Service Water Heating: For combination space
and service water heaters with a principal function of providing space heat, the
Combined Annual Efficiency (CAE) may be calculated by using ASHRAE Standard
124 -1991. Storage water heaters used in combination space heat and water heat
applications shall have either an Energy FActor (EF) or a CAE of not less than the
following:
1411.4 Packaged Electric Heating and Cooling Equipment: Packaged electric
equipment providing both heating and cooling with a total cooling capacity greater
than 20, Btu /h shall be a heat pump.
Exception: Unstaffed equipment shaelters or cabinets used solely for
personal wireless service facilities.
1412 Controls
1412.1 Temperature Controls: Each system shall be provided with at least one
temperature control device. Each zone shall be controlled by individual thermostatic
controls responding to temperature within the zone. At a minimum, each floor of a
building shall be considered as a separate zone.
1412.2 Deadband Controls: When used to control both comfort heating and
cooling, zone thermostatic controls shall be capable of a deadband of at least 5
degrees F within which the supply of heating and cooling energy to the zone is shut
off or reduced to a minimum.
Exceptions:
1. Special occupancy, special usage, or code requirements where
deadband controls are not appropriate.
2. Buildings complying with Section 1141.4, if in the proposed building
energy analysis, heating and cooling thermostat setpoints are set to
the same temperature between 70 degrees F and 75 degrees F
inclusive, and assumed to be constant throughout the year.
3. Thermostats that require manual changeover between heating and
cooling modes.
1412.3 Humidity Controls: If a system is equipped with a means for adding
moisture, a humidistat shall be provided.
1412.4 Setback and Shut -Off: HVAC systems shall be equipped with automatic
controls capable of accomplishing a reduction of energy use through control setback
or equipment shutdown during periods of non -use or alternate use of the spaces
served by the system. The automatic controls shall have a minimum seven -day
clock and be capable of being set for seven different day types per week. It must
retain programming and time for a power loss of 10 hours and include an accessible
manual override of up to 2 hours.
Exceptions:
1. Systems serving areas which require continuous operation at the
same temperature setpoint.
2. Equipment with full load demands of 2 kW (6,826 Btu /h) or less may
be controlled by readily accessible manual off -hour controls.
3. Systems controlled by an occupant sensor that is capable of shutting
the system off when no occupant is sensed for a period of up to 30
minutes.
4. Systems controlled solely by a manually operated timer capable of
operating the system for no more than two hours.
1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets serving
conditioned spaces shall be equipped with dampers which close automatically when
the system is off or upon power failure. Stair shaft and elevator shaft smoke relief
openings shall be equipped with normally open (fails to open upon loss of power)
dampers. These dampers shall remain closed until activated by the fire alarm
system or other approved smoke detection system.
Exceptions:
1. Systems serving areas which require continuous operation.
2. Combustion air intakes.
3. Gravity (nonmotorized) dampers are acceptable in buildings less
than 3 stories in height.
4. Gravity (nonmotorized) dampers are acceptable in exhaust and relief
outlets in the first story and levels below the first story of buildings
three or more stories in height.
1412.4.2 Optimum Start Controls: Heating and cooling systems with design supply
1412.8 Ventilation Controls for High- Occupancy Areas: Demand control
ventilation (DCV) is required for spaces that are larger than 500 ft2, have a design
occupancy for ventilation of greater than 40 people for 1000 ft2 of floor area, and are
served by systems with one or more of the following:
a. An air -side economizer,
b. Automatic modulating control of the outdoor air damper, or
c. A design outdoor airflow greater than 3000 cfm.
Exceptions:
1.Systems with energy recovery complying with Section 1438.
2. Multiple -zone systems without direct - digital control of individual zones
communicating with a central control panel.
3. Systems with a design outdoor airflow less than 1200 cfm.
4. Spaces where the supply airflow rate minus any makeup or outgoing
transfer air requirement is less than 1200 cfm.
1413 Air Economizers
1413.1 Operation: Air economizers shall be of automatically modulating outside and
return air dampers to provide 100 percent of the design supply air as outside air to
reduce or eliminate the need for mechanical cooling. Water economizers shall be
capable of providing the total concurrent cooling load served by the conneted
terminal equipment lacking airside economizer, at outside air temperatures of 45 ° F
dry- bulb /40 ° F wet -bulb and below. For this calculation, all factors including solar and
internal load shall be the same as those used for peak load calculations, except for
the outside temperatures.
Exception: Water economizers using air - cooled heat rejection equipment
may use a 35 ° F dry-bulb outside air temperature for this calculation. This
exception is limited to a maximum of 20 tons per building.
1413.2 Documentation: Water economizer plans submitted for approval shall
include the following information:
1. Maximum outside air conditions for which economizer is sized to provide
full cooling.
2. Design cooling load to be provided by economizer at this outside air
condition.
3. Heat rejection and terminal equipment performance data including model
number, flow rate, capacity, entering and leaving temperature in full
economizer cooling mode.
1413.3 Integrated Operation: Air economizers shall be capable of providing partial
cooling even when additional mechanical cooling is required to meet the remainder
of the cooling load.
Exceptions:
1. Individual, direct expansion units that have a rated capacity less than
65,000 Btu /h and use nonintegrated economizer controls that
preclude simultaneous operation of the economizer and mechanical
cooling.
2. Water - cooled water chillers with waterside economizer.
1413.4 Humidification: If an air economizer is required on a cooling system for
which humidification equipment is to be provided to maintain minimum indoor
humidity levels, then the humidifier shall be of the adiabatic type (direct evaporative
media or fog atomization type).
Exceptions:
1. Health care facilities where WAC 246- 320 -525 allows only steam
injection humidifiers in ductwork downstream of final filters. 1412.6
Combustion Heating Equipment Controls: Combustion heating
equipment with a capacity over 225,000 Btu /h shall have modulating
or staged combustion control.
2. Systems with water economizer
3. 100% outside air systems with no provisions for air recirculation to the
central supply fan.
4. Nonadiabatic humidifiers cumulatively serving no more than 10% of a
building's air economizer capacity as measured in cfm. This refers to
the system cfm serving rooms with stand alone or duct mounted
humidifiers.
1414 Ducting Systems
1414.1 Sealing: Duct work which is designed to operate at pressures above 1/2 inch
water column static pressure shall be sealed in accordance with Standard RS -18.
Extent of sealing required is as follows:
1. Static pressure: 1/2 inch to 2 inches; seal transverse joints.
2. Static pressure: 2 inches to 3 inches; seal all transverse joints and
longitudinal seams.
3. Static pressure: above 3 inches; seal all transverse joints, longitudinal
seams and duct wall penetrations.
Duct tape and other pressure sensitive tape shall not be used as the primary
sealant where ducts are designed to operate at static pressures of 1 inch W.C. or
greater.
1414.2 Insulation: Ducts and plenums that are constructed and function as part of
the building envelope, by separating interior space from exterior space, shall meet all
applicable requirements of Chapter 13. These requirements include insulation
installation, moisture control, air leakage, and building envelope insulation levels.
Unheated equipment rooms with combustion air louvers must be isolated from the
conditioned space by insulating interior surfaces to a minimum of R -11 and any
exterior envelope surfaces per Chapter 13. Outside air ducts serving individual
supply air units with less than 2,800 cfm of total supply air capacity shall be insulated
to a minimum of R -7 and are not considered building envelope. Other outside air
duct runs are considered building envelope until they,
1. connect to the heating or cooling equipment, or
2. are isolated from the exterior with an automatic shut -off damper complying
__.._._ ......_ ...... _...� ...._ ._._._ __._....._ ... _. _._.� _. __.._... •
- three or more stories in he 6 Washington State Nonresidential Eher §S"G�b� ® EI�12 f Rij equipment, or
1412.4.2 Optimum Start Controls: Heating and cooling systems with design supply 2. are isolated from the exterior with an automatic shut -off damper complying
air capacities exceeding 10,000 cfm shall have optimum start controls. Optimum with Section 1412.4.1.
start controls shall be designed to automatically adjust the start time of an HVAC Once outside air ducts meet the above listed requirements, any runs within
system each day to bring the space to desired occupied temperature levels conditioned space shall comply with Table 14 -5 requirements.
immediately before scheduled occupancy. The control algorithm shall, as a Other ducts and plenums shall be thermally insulated per Table 14 -5.
minimum, be a function of the difference between space temperature and occupied Exceptions:
setpoint and the amount of time prior to scheduled occupancy. 1. Within the HVAC equipment.
1412.5 Heat Pump Controls: Unitary air cooled heat pumps shall include
microprocessor controls that minimize supplemental heat usage during start-up, set- 2. Exhaust air ducts not subject to condensation.
up, and defrost conditions. These controls shall anticipate need for heat and use 3. Exposed ductwork within a zone that serves that zone.
compression heating as the first stage of heat. Controls shall indicate when 1415 Piping Systems
supplemental heating is being used through visual means (e.g., LED indicators). 1415.1 Insulation: Piping shall be thermally insulated in accordance with Table 14 -8.
1412.6 Combustion Heating Equipment Controls: Combustion heating equipment Exception: Piping installed within unitary HVAC equipment.
with a capacity over 225,000 Btu /h shall have modulating or staged combustion Water pipes outside the conditioned space shall be insulated in accordance with
control. 000 Washington State Plumbing Code (WAC 51 -26)
EXCEPTIONS: 1. Boilers. 2. Radiant heaters. 1416 Completion Requirements (Refer to NREC Section 1416 and the Building
1412.7 Balancing: Each air supply outlet or air or water terminal device shall have Commissioning Guidelines, published by the Building Commissioning Association,
a means for balancing, including but not limited to, dampers, temperature and for complete text and guidelines for building completion and commissioning
pressure test connections and balancing valves. requirements.)
ACTIVITY NUMBER: M08 -112
PROJECT NAME: OKI DOKI
SITE ADDRESS: 2897 SOUTHCENTER MALL
DATE: 7 -15 -08
Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter # X Revision # 2 After Permit Issued
DEPARTMENTS:
B i rJ ng D'vision
Public Works
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
v1
TUES /THURS ROUTING:
Please Route
Documents/routing slip.doc
2 -28 -02
PERMIT COORD COPY •
PLAN REVIEW /ROUTING SLIP
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
0100 NA.1
Fire Prevention
Structural
Incomplete n
n Permit Coordinator ❑
Planning Division
DUE DATE: 7-17-08
Not Applicable
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Structural Review Required
n
No further Review Required
DATE:
DUE DATE: 8-14 -08
Approved -44 Approved with Conditions n Not Approved (attach comments)
Notation:
REVIEWER'S INITIALS:
DATE:
n
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
ACTIVITY NUMBER: M08 -112 DATE: 06 -25 -08
PROJECT NAME: WESTFIELD VANILLA BOX
SITE ADDRESS: 2897 SOUTHCENTER MALL
Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
X Revision # 1 after Permit Issued
DEPARTMENTS:
Public Works ❑ Structural
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Please Route
TUES/THURS ROUTING:
REVIEWER'S INITIALS:
Incomplete ❑
Documents routing slip.doc
2 -28 -02
PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
C ,Opb jc
Fire Prevention
Permit Center,Use Only : • • • ' ' `.'
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Structural Review Required
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
Notation:
REVIEWER'S INITIALS:
❑
Planning Division
❑ Permit Coordinator
DUE DATE: 06-26-08
Not Applicable ❑
No further Review Required
DATE:
DATE:
n
DUE DATE: 07-24-08
Not Approved (attach comments) ❑
Permit Center Use Only '
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
PLAN REVIEW /ROUTING SUP
PERMIT COORD COPY
ACTIVITY NUMBER: M08 -122 DATE: 04 -24 -08
PROJECT NAME: WESTFIELD VANILLA BOX
SITE ADDRESS: 2897 SOUTHCENTER MALL
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter # Revision # After Permit Issued
DEPARTMENTS:
Buil.4 g'D'vision
Public Works ❑
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Incomplete n
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES/THURS ROUT NG:
Please Route Structural Review Required
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
Notation:
REVIEWER'S INITIALS:
Documents/routing slip.doc
2 -28-02
Fire Prevention Planning Division
Structural ❑ Permit Coordinator
DUE DATE: 04-29-08
DATE:
DATE:
n
Not Applicable ❑
No further Review Required
DUE DATE: 0527-08
Not Approved (attach comments) n
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
REVISION
NO.
DATE RECEIVED
STAFF
INITIALS
ISSUED DATE
STAFF
IN ALS
I
OLQ 171012
c .,
r
./P
JC
Summary of Revision: KI (cam- 7 OW-1114 Er l,A''tvinT / U'ti/ IT i
Received by: ,(14... v-c /,-)0 �C.,
REVISION
NO.
DATE RECEIVED
STAFF
INITIALS
ISSUED DATE
STAFF
INITIALS
Summary of Revision:
Received by:
REVISION
NO.
DATE RECEIVED
STAFF
INITIALS
ISSUED DATE
STAFF
INITIALS
Summary of Revision:
Received by:
REVISION
NO.
DATE RECEIVED
STAFF
INITIALS
ISSUED DATE
STAFF
INITIALS
Summary of Revision:
Received by:
REVISION
NO.
DATE RECEIVED
STAFF
INITIALS
ISSUED DATE
STAFF
INITIALS
Summary of Revision:
Received by:
REVISION
NO.
DATE RECEIVED
STAFF
INITIALS
ISSUED DATE
STAFF
INITIALS
Summary of Revision:
Received by:
PROJECT NAME: �1 t �; �,►P
SITE ADDRESS: 'V f(VjT i
ORIGINAL ISSUE DATE:
REVISION LOG
I
PERMIT NO: AkDlr U2
(please print)
(please print)
(please print)
(please print)
(please print)
Revision submittals must be submitted in person at the Permit Center. Revisions will not be accepted through
the mail, fax, etc.
Date: 7/ 1,08' Plan Check/Permit Number: /7'l D8 - f f
❑ Response to Incomplete Letter #
❑ Response to Correction Letter #
[Revision # 2. after Permit is Issued
❑ Revision requested by a City Building Inspector or Plans Examiner
a g7--,v7 e.4-/ Weser -L alo( kJ. , 11 i
&o -h C e , - /114 //
Q.9't�t�a P-e'_. d; ceyr.Q Phone Number: 487 g" ----4 1 1 e ) 2 8
Project Name: t)k,t L/p /ci
Project Address: ...21 7
Contact Person:
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: //www.ci.tukwila.wa.us
Summary of Revision:
e V4 n /342c Te.ri 7`-
/,15e.: ltiarn ' . )4-- a eecs2,rM'c3 6vie.6
06.4.4 1 L 4 4/6, ,
Sheet Number(s):
"Cloud" or highlight all areas of revision including date of revisio
Received at the City of Tukwila Permit Center by:
Entered in Permits Plus on 1' 4-40&
\applications\forms - applications on line\revision submittal
Created: 8-13-2004
•
4 4 4 0
Steven Ail Mullet, .Mayor
Steve Lancaster, Director
2.5 1 Shirk s)
FIECEfVED
OF T t3KW! A
JUL 15 2003
PERMIT CENTE
Revision submittals must be submitted in person at the Permit Center. Revisions will not be accepted through
the mail, fax, etc.
Date: (o (2_54 Plan Check/Permit Number:
❑ Response to Incomplete Letter #
❑ Response to Correction Letter #
[1Y Revision # 1 after Permit is Issued
❑ Revision requested by a City Building Inspector or Plans Examiner
Project Name:
•
City of Tukwila
(Ve6�4e /c 1 ) X
Project Address: 2-Sg 7 '3) i n 7/
Contact Person: rha v cc Q .G,(/ Phone Number:
Summary of Revision:
g e-e.), r 5 -4 re (.0 Ga ` — c( cc
r ter).'ts.` m-, o f s ? 4 7�
Sheet Number(s): – /
"Cloud" or highlight all areas of revision including date of revision
Received at the City of Tukwila Permit Center by:
iikr Entered in Permits Plus on a/ (
lapplicationslfonns- applications on linelrevision submittal
Created: 8 -13 -2004
rvi cni•
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: //www.ci.tukwila.wa. us
•
Steve Lancaster, Director
8EcErvE
CITY OP TU1,A
JUN 2 5 1008
°ERm17 czNTER
Steven M. Mullet, Mayor
License Information
License
OKITSCI959L8
Licensee Name
OKITSU CONSTRUCTION INC
Licensee Type
CONSTRUCTION CONTRACTOR
UBI
602515973
Ind. Ins. Account Id
PRESIDENT
Business Type
CORPORATION
Address 1
1428 WHITWORTH AVE S
Address 2
City
RENTON
County
KING
State
WA
Zip
98055
Phone
2067149969
Status
ACTIVE
Specialty 1
GENERAL
Specialty 2
UNUSED
Effective Date
6/28/2005
Expiration Date
6/28/2009
Suspend Date
Separation Date
Parent Company
Previous License
OKITSC*030R3
Next License
Associated License
Business Owner Information
Name
Role
Effective
Date
Expiration
Date
OKITSU, RODNEY
STERLING
AGENT
06/28/2005
Bond
Amount
OKITSU, RODNEY
STERLING
PRESIDENT
06/28/2005
Bond Information
Bond
Bond Company
Name
Bond
Account
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Bond
Amount
Received
Date
Look Up a Contractor, Electrl or Plumber License Detail
Washington State Department of Labor and Industries
GeneraUSpecialty Contractor
A business registered as a construction contractor with L &I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
I
Page 1 of 2
https: // fortress. wa. gov /lni/bbip /printer.aspx ?License= OKITSCI959L8 06/11/2008
■ ■ ■W
■11111111v111
rea
SHEET METAL NOTES
1. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE
GENERAL INTENT OF THE WORK, PR ❑VIDE SHEET METAL
SYSTEMS COMPLETE AND PER APPLICABLE CODES INCLUDING
ALL NECESSARY OFFSETS, FITTINGS, SPECIAL RADIUS OR
MITERED ELBOWS WHICH ARE REQUIRED DUE TO SPACE
CONSTRAINTS OR OTHER C❑NDITI ❑NS,
2. CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF
ALL OTHER TRADES, VERIFY ALL CLEARANCES PRI ❑R TO THE
FABRICATION OF ANY WORK,
3. DUCTWORK SHALL NOT BE LOCATED OVER ELECTRICAL
EQUIPMENT /PANELS, PROVIDE REQUIRED CLEARANCE IN FRONT
OF ELECTRICAL EQUIPMENT. DUCTWORK SHALL NOT INTERFERE
WITH ELECTRICAL EQUIPMENT CLEARANCE.
4, THE CONTRACTOR SHALL PR ❑VIDE ALL MISCELLANEOUS
SUPPORTING STEEL, ETC, FOR THE PROPER INSTALLATION OF
ALL MECHANICAL SYSTEMS.
5. COORDINATE FLOOR, WALL, ROOF PENETRATIONS, LOUVER SIZES,
PAD LOCATIONS, ETC. WITH ARCHITECTURAL TRADES.
6, THE CONTRACTOR SHALL REFER TO ARCHITECTURAL REFLECTED
CEILING PLANS FOR EXACT L ❑CATION OF GRILLES, REGISTERS,
AND DIFFUSERS.
7, INSTALL MANUAL VOLUME DAMPERS AT ALL SUPPLY AIR BRANCH
DUCTS TO THE DIFFUSER, BRANCH RETURN AIR DUCT, EXHAUST
AIR DUCT, AND OTHER L❑CATI ❑NS AS SHOWN ON PLANS.
8. PROVIDE FLEXIBLE C❑NNECTI ❑N AT DIFFUSER NECK, ALL
FLEXIBLE DUCT SHALL BE INSULATED AND LIMITED TO 5' -0" IN
LENGTH.
9, DUCTED EXHAUST AND RETURN GRILLES SHALL BE HARD
CONNECTED,
10,C ❑ORDINATE AND PROVIDE ACCESS DOORS IN HARD CEILING
AREAS FOR ACCESS TO TERMINAL UNITS, BALANCING DAMPERS,
TERMINAL UNIT HEATING COIL PIPING, ETC, REFER TO
ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
1L CONTRACTORS SHALL VERIFY THERE ARE NO COMBUSTIBLES IN
THE RETURN AIR PLENUM. IF COMBUSTIBLES ARE PRESENT
CONTRACTOR SHALL COORDINATE WITH
ARCHITECT /ENGINEER /OWNER'S REPRESENTATIVE COURSE OF
ACTI ❑N (HARD DUCT RETURN SYSTEM OR ELIMINATE
COMBUSTIBLES - FIREPR ❑OF, WRAP, ETC.)
12,ALL SHEET METAL DUCT SIZES SHOWN ARE CLEAR INSIDE
DIMENSI ❑NS.
PROVIDE AND INSTALL NEW DUCT SMOKE DETECTOR
IN SA /RA DUCT AS REQUIRED BY LOCAL CODE TO
PROVIDE FAN SHUTDOWN
MECHANICAL PLAN
MECHANICAL NOTES
1, DUCT LINING IS NOT ALLOWED
2. ALL SUPPLY AIR DUCTWORK SHALL BE WRAPPED WITH 1'
INSULATI ON TO MATCH EXISTING,
3. PROVIDE AND INSTALL FIRE DAMPERS WHERE DUCTS PENETRATE
RATED C❑NSTRUCTI ❑N. ALL DUCTS PENETRATING SHAFTS (SMOKE
BARRIERS) SHALL HAVE COMBINATION FIRE /SMOKE DAMPERS
ACTIVATION OF DAMPER SHALL BE SIGNALED TO FIRE ALARM
PANEL.
4, MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CUTTING, CORING AND PATCHING REQUIRED FOR PROPER
INSTALLATI ❑N OF THE SYSTEM.
5, PROVIDE BALANCING DAMPERS IN ALL BRANCH DUCTWORK AS
REQUIRED FOR PROPER BALANCING OF THE SYSTEM.
6, THE ENTIRE CONSTRUCTI ❑N SHALL CONFORM TO THE LATEST
EDITI ❑N OF N.F,P,A, SMACNA, THE LOCAL MECHANICAL CODE,
LOCAL ORDINANCE, AND AUTHORITIES HAVING JURISDICTI ❑N.
7. EACH CONTRACTOR SHALL COORDINATE INSTALLATI ❑N OF HIS
WORK WITH ALL OTHER TRADES TO AVOID CONFLICTS AND
INTERFERENCES DURING CONSTRUCTI ❑N,
8, CONTRACTOR SHALL NOT RUN ANY PVC, PLASTIC MATERIALS OR
ANY OTHER COMBUSTIBLE MATERIAL INSIDE THE RETURN AIR
PLENUM,
9. MECHANICAL CONTRACTOR SHALL COORDINATE ALL MECHANICAL
EQUIPMENT ELECTRICAL REQUIREMENTS WITH ELECTRICAL
CONTRACTOR PRIOR TO ANY EQUIPMENT PURCHASE,
10, TESTING & BALANCING - ENGAGE THE SERVICES OF AN
INDEPENDENT CERTIFIED TEST AND BALANCE AGENCY THAT
SPECIALIZED IN AND WHO'S BUSINESS IS LIMITED TO THE
TESTING AND BALANCING OF HVAC SYSTEMS AND HYDR❑NIC
SYSTEMS. THE AGENCY SELECTED SHALL BE CERTIFIED BY
ASSOCIATED AIR BALANCE COUNCIL (A ABC) OR NATIONAL
ENVIRONMENTAL BALANCING BUREAU (NEBB), AGENCY SHALL
SUBMIT A COMPLETE REPORT BASED ON SMACNA °BALANCING
AND ADJUSTMENT MANUAL'. THE HVAC SYSTEM SHALL BE
TESTED AND BALANCED TO DEMONSTRATE THAT SPECIFIED
CAPACITY AND PROPER CONTROL FUNCTIONING HAS BEEN
ATTAINED.
11,START -UP FOR ALL EQUIPMENT SHALL BE CONDUCTED BY EACH
MANUFACTURER'S START -UP REPRESENTATIVE, INCLUDE FINAL
REPORT AND CERTIFICATE. PR ❑VIDE OWNER'S MANUAL AND
TRAINING FOR MAINTENANCE PERSONNEL FOR EACH TYPE OF
EQUIPMENT.
1aALL EQUIPMENT AND COMBUSTION VENT TERMINATI ❑N ETC,
SHALL BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS.
VERIFY AND LOCATE EQUIPMENT BASED ON MANUFACTURERS
RECOMMENDED CLEARANCES.
13,C❑NTRACTOR SHALL PROVIDE RETURN AIR TRANSFER DUCTWORK
FOR ALL ROOMS WITH WALLS FROM FINISHED FLOOR TO BOTTOM
OF DECK, COORDINATE WALL LOCATIONS WITH ARCHITECTURAL
TRADES,
GENERAL NOTES
1. CONTRACTORS SHALL PR ❑VIDE EQUIPMENT AND SPECIALTIES
INDICATED HERE -IN TO PR ❑VIDE A COMPLETE AND WORKING
SYSTEM,
2. CONTRACTORS SHALL COMPLY WITH ALL LAWS, LOCAL
ORDINANCES AND CODES OF THE STATE, FEDERAL AGENCIES
AND MUNICIPALITY. CONTRACTORS SHALL SECURE AND PAY FOR
ALL NECESSARY FEES AND PERMITS REQUIRED IN THE
PERFORMANCE OF HIS WORK. ALL CUTTING AND PATCHING FOR
NEW WORK SHALL BE DONE BY THIS CONTRACTOR WITH THE
APPROVAL OF THE OWNER'S REPRESENTATIVE.
3. CONTRACTOR SHALL VISIT THE SITE AND CHECK THE EXISTING
CONDITIONS BEFORE SUBMISSI ❑N OF BIDS, NO ALLOWANCE
SHALL BE MADE IN BEHALF OF EXTRA EXPENSES DUE TO THE
FAILURE TO MAKE SUCH AN EXAMINATI ❑N.
4. CONTRACTOR SHALL PROVIDE A COMPLETED OPERABLE SYSTEM
AS HERE -IN DESCRIBED. IF THE DOCUMENTATION IS UNCLEAR
OR INCOMPLETE TO THE CONTRACTOR HE SHALL SO STATE IN
WRITING TO THE OWNER'S REPRESENTATIVE /ENGINEER AND
REQUEST CLARIFICATI ❑N ON THOSE ITEMS REQUIRING
CLARIFICATI ❑N, IF NO SUCH STATEMENT IS MADE IT SHALL BE
PRESUMED THAT THE CONTRACTOR FULLY UNDERSTANDS THE
INTENT OF A FUNCTI ❑N OF THE SYSTEM DESCRIBED.
5, ANY CLAIMS FOR ADDITIONAL SERVICES BASED UPON
UNDERSTANDING OF THE SYSTEMS WILL NOT BE ALLOWED.
CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO
CONVEY THE SCOPE OF WORK AND GENERAL ARRANGEMENT OF
EQUIPMENT. DO NOT SCALE DRAWINGS.
6, CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER
TRADES. CONTRACTOR SHALL SECURE FINAL OCCUPANCY
INSPECTION AND SUBMIT CERTIFICATES TO THE OWNER'S
REPRESENTATIVE, CONTRACTOR SHALL FURNISH THE OWNER
WITH A WRITTEN GUARANTEE TO CORRECT ALL IMPERFECTIONS
IN MATERIALS AND WORKMANSHIP, WHICH MAY DEVELOP IN THE
SYSTEMS INSTALLED AND UNDER NORMAL USE FOR A PERIOD OF
ONE YEAR AFTER FINAL ACCEPTANCE BY THE OWNER,
7. BASE BID FOR EQUIPMENT IS TO BE UNITS SCHEDULED.
PRICING USING ALTERNATE ACCEPTED AND LISTED
MANUFACTURES SHALL STATE ALTERNATE MANUFACTURER AND
MODEL NUMBER AS PART OF BID. VOLUNTARY ALTERNATES FOR
EQUIPMENT NOT LISTED SHALL ONLY BE WITH WRITTEN
ACCEPTANCE OF THE ENGINEER PRI ❑R TO BIDDING, VOLUNTARY
ALTERNATES WILL NOT BE REVIEWED FOR ACCEPTANCE BY THE
ENGINEER DURING THE 7 DAYS PRI ❑R TO BID DATE.
8. CONTRACTOR SHALL PROVIDE, STORE, PLACE AND INSTALL ALL
NECESSARY EQUIPMENT REQUIRED, ALL EQUIPMENT SHALL BE
INSTALLED PER THE MANUFACTURER'S RECOMMENDATIONS AND IN
SUCH A MANNER AS TO FUNCTION IN ITS INTENDED USE,
8. CONTRACTOR SHALL SUBMIT SUBMITTALS FOR ALL EQUIPMENT
AND MATERIALS FOR REVIEW PRI ❑R TO PURCHASE,
9. AFTER INSTALLATION IS COMPLETE, CONTRACTOR SHALL BE
RESPONSIBLE FOR STARTUP, INSPECT ❑RS' APPROVAL AND
CLEAN UP.
0 0 0 0 0
CONTROLS NOTE
FMB CONTROLS SHALL MATCH MALL CONTROLS SYSTEM.
CONTROLS CONTRACTOR SHALL TIE -INTO EXISTING CONTROLS
FOR ❑PERATI ❑N.
MECHANICAL KEYED NOTES:
(MECHANICAL KEYED NOTES APPLY TO THIS SHEET
ONLY)
MECHANICAL SYMBOL LEGEND:
N❑TEI THE FOLLOWING SYMBOLS SHALL BE AS
INDICATED, UNLESS NOTED OTHERWISE ON PLANS.
CONNECT TO EXISTING SUPPLY AIR MAIN (VERIFY
IN FIELD).
CONNECT EXHAUST FROM TOILET EXHAUST FAN TO
MALL EXHAUST DUCT MAIN (VERIFY IN FIELD).
SD -11 24 °x24' SUPPLY
DIFFUSER
RG - 11 24 °x24° RETURN
GRILLE
0 THERMOSTAT
_r'I DUCT FLEX
CEILING MOUNTED INLINE
EXHAUST FAN,
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL 01 2008
City Of kwila
B ILDIN ' IVISION
:z
L L
T mlft No
(77
rw PE''I�iCtNS om File
'.�''''?" ~es shall be made to the scope
F t
,,, P. - )7k without prior approval of
ul�s�iia Building Division. Scald
Al! ideas,
2897 Southcenter Mall
Tukwila, WA 98188
smith co.
1725 westlake ave. n.
suite 210
seattle, washington 98109
206.838.5485 p
206.713.4076 m
206.464.0700 f
ksmith @smithco.org
http: / /www.smithco.org/
Consultant
Consultant Registration
Issues and Revisions
No. Date
1 03.31.08
2 04.15.08
3 05.28.08
4 06.15.08
Date.
Tula
E-UILDINe DIVIVON
Project Name
NOTE: Revisions will require a new plan subrnfa!
and may include additional plan review feesTemplate • I
represented
AS NOTED
KEITH L SMITH
STATE OF WASHINGTON
Issues
Project Number 02008018.00
6294
Architect Registration
REGISTERED
ARCHITECT
PERMIT KLS
PERMIT CORRECTIONS KLS
ISSUE KLS
CONSTRUCTION SET KLS
rw v approval is subject to
>! `"pro'. of construction documents does not euthofize CITY OF TUKWILA
t"IC "iiOlation of any adopted code or Gramm. Receipt JUN 2 5 ZOD8
n
WESTFIELD SOUTHCENTER MALL
Description MECHANICAL PLAN
CW05- 2008— M1,DWG
and
by this drawing are owned by and the property of
smith co. Ilc and were created, evolved, and developed
for use on and in connection with the specified project. None of
such ideas, designs, arrangements or plans shall be used
by or disclosed to any person, firm, or corporation for any
purpose whatsoever without the written permission of smith co. Ilc.
designs, arrangements,
M -1
plans indicated
By Check
or
�'//////Q//0/D%
SHEET METAL NOTES
1. THESE DRAWINGS ARE DIAGRAMMATIC AND t1VDICATE THE
GENERAL INTENT OF THE WORK. PR ❑VIDE SHEET METAL
SYSTEMS COMPLETE AND PER APPLICABLE CODES INCLUDING
ALL NECESSARY OFFSETS, FITTINGS, SPECIAL RADIUS OR
MITERED ELBOWS WHICH ARE REQUIRED DUE TO SPACE
CONSTRAINTS OR OTHER CONDITIONS.
3, DUCTWORK SHALL NOT BE LOCATED OVER ELECTRICAL
EQUIPMENT /PANELS. PROVIDE REQUIRED CLEARANCE IN FRONT
OF ELECTRICAL EQUIPMENT. DUCTWORK SHALL NOT INTERFERE
WITH ELECTRICAL EQUIPMENT CLEARANCE.
4. THE CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS
SUPPORTING STEEL, ETC. FOR THE PROPER INSTALLATION OF
ALL MECHANICAL SYSTEMS.
6. THE CONTRACTOR SHALL REFER TO ARCHITECTURAL REFLECTED
CEILING PLANS FOR EXACT LOCATION OF GRILLES, REGISTERS,
AND DIFFUSERS.
10.C❑❑RDINATE AND PROVIDE ACCESS DOORS IN HARD CEILING
AREAS FOR ACCESS TO TERMINAL UNITS, BALANCING DAMPERS,
TERMINAL UNIT HEATING C ❑IL PIPING, ETC. REFER TO
ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
11. CONTRACTORS SHALL VERIFY THERE ARE NO COMBUSTIBLES IN
THE RETURN AIR PLENUM. IF COMBUSTIBLES ARE PRESENT
CONTRACTOR SHALL COORDINATE WITH
ARCHITECT /ENGINEER /OWNER'S REPRESENTATIVE COURSE OF
ACTION (HARD DUCT RETURN SYSTEM OR ELIMINATE
COMBUSTIBLES — FIREPRO ❑F, WRAP, ETC)
12.ALL SHEET METAL DUCT SIZES SHOWN ARE CLEAR INSIDE`
DIMENSIONS.
RG -1
2. CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF
ALL OTHER TRADES. VERIFY ALL CLEARANCES PRIOR TO THE
FABRICATI ❑N OF ANY WORK,
5, COORDINATE FLOOR, WALL, ROOF PENETRATIONS, LOUVER SIZES,
PAD LOCATIONS, ETC. WITH ARCHITECTURAL TRADES.
7. INSTALL MANUAL VOLUME DAMPERS AT ALL SUPPLY AIR BRANCH
DUCTS TO THE DIFFUSER, BRANCH RETURN AIR DUCT, EXHAUST
AIR DUCT, AND OTHER LOCATIONS AS SHOWN ON PLANS.
8, PR ❑VIDE FLEXIBLE CONNECTION AT DIFFUSER NECK, ALL
FLEXIBLE DUCT SHALL BE INSULATED AND LIMITED TO 5' —O' IN
LENGTH.
9. DUCTED EXHAUST AND RETURN GRILLES SHALL BE HARD
CONNECTED,
PROVIDE AND INSTALL NEW DUCT SMOKE DETECTOR
IN SA /RA DUCT AS REQUIRED BY LOCAL CODE TO
PROVIDE FAN SHUTDOWN
n X I
lJ
I9
.
/�4 (,, //// // / /// //////./.
/. /
0
SCALE:1 /4" — 1
1. DUCT LINING IS NOT ALLOWED
MECHANICAL PLAN
MECHANICAL NOTES
1
//
2. ALL SUPPLY AIR DUCTWORK SHALL BE WRAPPED WITH 1'
INSULATI ❑N TO MATCH EXISTING.
3. PROVIDE AND INSTALL FIRE DAMPERS WHERE DUCTS PENETRATE
RATED CONSTRUCTION, ALL DUCTS PENETRATING SHAFTS (SMOKE
BARRIERS) SHALL HAVE COMBINATION FIRE /SMOKE DAMPERS
ACTIVATION OF DAMPER SHALL BE SIGNALED TO FIRE ALARM
PANEL.
4, MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
CUTTING, C ❑RING AND PATCHING REQUIRED FOR PROPER
INSTALLATI ❑N OF THE SYSTEM.
5. PR ❑VIDE BALANCING DAMPERS IN ALL BRANCH DUCTWORK AS
REQUIRED FOR PROPER BALANCING OF THE SYSTEM.
6. THE ENTIRE CONSTRUCTION SHALL CONFORM TO THE LATEST
EDITI ❑N OF N.F.P.A. SMACNA, THE MICHIGAN MECHANICAL CODE,
LOCAL ORDINANCE, AND AUTHORITIES HAVING JURISDICTI ❑N.
7. EACH CONTRACTOR SHALL COORDINATE INSTALLATION OF HIS
WORK WITH ALL OTHER TRADES TO AV ❑ID CONFLICTS AND
INTERFERENCES DURING CONSTRUCTION.
8. CONTRACTOR SHALL NOT RUN ANY PVC, PLASTIC MATERIALS OR
ANY OTHER COMBUSTIBLE MATERIAL INSIDE THE RETURN AIR
PLENUM.
9. MECHANICAL CONTRACTOR SHALL COORDINATE ALL MECHANICAL
EQUIPMENT ELECTRICAL REQUIREMENTS WITH ELECTRICAL
CONTRACTOR PRI ❑R TO ANY EQUIPMENT PURCHASE.
10,TESTING & BALANCING — ENGAGE THE SERVICES OF AN
INDEPENDENT CERTIFIED TEST AND BALANCE AGENCY THAT
SPECIALIZED IN AND WHO'S BUSINESS IS LIMITED TO THE
TESTING AND BALANCING OF HVAC SYSTEMS AND HYDR❑NIC
SYSTEMS, THE AGENCY SELECTED SHALL BE CERTIFIED BY
ASSOCIATED AIR BALANCE COUNCIL (AABC) OR NATIONAL
ENVIRONMENTAL BALANCING BUREAU (NEBB). AGENCY SHALL
SUBMIT A COMPLETE REPORT BASED ON SMACNA 'BALANCING
AND ADJUSTMENT MANUAL'. THE HVAC SYSTEM SHALL BE
TESTED AND BALANCED TO DEMONSTRATE THAT SPECIFIED
CAPACITY AND PROPER CONTROL FUNCTIONING HAS BEEN
ATTAINED.
11.START —UP FOR ALL EQUIPMENT SHALL BE CONDUCTED BY EACH
MANUFACTURER'S START —UP REPRESENTATIVE, INCLUDE FINAL
REPORT AND CERTIFICATE. PROVIDE OWNER'S MANUAL AND
TRAINING FOR MAINTENANCE PERSONNEL FOR EACH TYPE OF
EQUIPMENT.
12,ALL EQUIPMENT AND COMBUSTION VENT TERMINATI ❑N ETC.
SHALL BE INSTALLED PER MANUFACTURERS REC❑MMENDATI ❑NS.
VERIFY AND LOCATE EQUIPMENT BASED ON MANUFACTURERS
RECOMMENDED CLEARANCES.
13.0 ❑NTRACT ❑R SHALL PR ❑VIDE RETURN AIR TRANSFER DUCTWORK
FOR ALL ROOMS WITH WALLS FROM FINISHED FLOOR TO BOTTOM
OF DECK. COORDINATE WALL L ❑CATIONS WITH ARCHITECTURAL
TRADES.
///e///%
aaa//ai
•
//aaa���///ia�/aaa i���/��/��///��//,�i�///a.. .� e.�////��/�/,/�/�/ aim /i iiiiiiia��ii��iy ai�i�iiiia�/�aiaa�/�/i i �rri��y�� �ai�i ' ` d. /////
0 , ,
S
GENERAL NOTES
S
•
//a////O /// %/ ////%%%%%'///' %/// //7 -
1. CONTRACTORS SHALL PR ❑VIDE EQUIPMENT AND SPECIALTIES
INDICATED HERE —IN TO PR ❑VIDE A COMPLETE AND WORKING
SYSTEM.
2. CONTRACTORS SHALL COMPLY WITH ALL LAWS, LOCAL
ORDINANCES AND CODES OF THE STATE, FEDERAL AGENCIES
AND MUNICIPALITY, CONTRACTORS SHALL SECURE AND PAY FOR
ALL NECESSARY FEES AND PERMITS REQUIRED IN THE
PERFORMANCE OF HIS WORK. ALL CUTTING AND PATCHING FOR
NEW WORK SHALL BE DONE BY THIS CONTRACTOR WITH THE
APPROVAL OF THE OWNER'S REPRESENTATIVE.
3. CONTRACTOR SHALL VISIT THE SITE AND CHECK THE EXISTING
CONDITI ❑NS BEFORE SUBMISSI ❑N OF BIDS, NO ALLOWANCE
SHALL BE MADE IN BEHALF OF EXTRA EXPENSES DUE TO THE
FAILURE TO MAKE SUCH AN EXAMINATI ❑N.
4, CONTRACTOR SHALL PROVIDE A COMPLETED OPERABLE SYSTEM
AS HERE —IN DESCRIBED. IF THE DOCUMENTATION IS UNCLEAR
OR INCOMPLETE TO THE CONTRACTOR HE SHALL SO STATE IN
WRITING TO THE OWNER'S REPRESENTATIVE /ENGINEER AND
REQUEST CLARIFICATION ON THOSE ITEMS REQUIRING
CLARIFICATION, IF NO SUCH STATEMENT IS MADE IT SHALL BE
PRESUMED THAT THE CONTRACTOR FULLY UNDERSTANDS THE
INTENT OF A FUNCTI ❑N OF THE SYSTEM DESCRIBED.
5. ANY CLAIMS FOR ADDITIONAL SERVICES BASED UPON
UNDERSTANDING OF THE SYSTEMS WILL NOT BE ALLOWED.
CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO
CONVEY THE SCOPE OF WORK AND GENERAL ARRANGEMENT OF
EQUIPMENT. DO NOT SCALE DRAWINGS.
6. CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER
TRADES. CONTRACTOR SHALL SECURE FINAL OCCUPANCY
INSPECTI ❑N AND SUBMIT CERTIFICATES TO THE OWNER'S
REPRESENTATIVE. CONTRACTOR SHALL FURNISH THE OWNER
WITH A WRITTEN GUARANTEE TO CORRECT ALL IMPERFECTI ❑NS
IN MATERIALS AND WORKMANSHIP, WHICH MAY DEVELOP IN THE
SYSTEMS INSTALLED AND UNDER NORMAL USE FOR A PERIOD OF
ONE YEAR AFTER FINAL ACCEPTANCE BY THE OWNER.
7, BASE BID FOR EQUIPMENT IS TO BE UNITS SCHEDULED.
PRICING USING ALTERNATE ACCEPTED AND LISTED
MANUFACTURES SHALL STATE ALTERNATE MANUFACTURER AND
MODEL NUMBER AS PART OF BID. VOLUNTARY ALTERNATES FOR
EQUIPMENT NOT LISTED SHALL ONLY BE WITH WRITTEN
ACCEPTANCE OF THE ENGINEER PRI ❑R TO BIDDING. VOLUNTARY
ALTERNATES WILL NOT BE REVIEWED FOR ACCEPTANCE BY THE
ENGINEER DURING THE 7 DAYS PRIOR TO BID DATE.
8. CONTRACTOR SHALL PROVIDE, STORE, PLACE AND INSTALL ALL
NECESSARY EQUIPMENT REQUIRED. ALL EQUIPMENT SHALL BE
INSTALLED PER THE MANUFACTURER'S REC❑MMENDATI ❑NS AND IN
SUCH A MANNER AS TO FUNCTION IN ITS INTENDED USE.
8, CONTRACTOR SHALL SUBMIT SUBMITTALS FOR ALL EQUIPMENT
AND MATERIALS FOR REVIEW PRI ❑R TO PURCHASE.
9. AFTER INSTALLATI ❑N IS COMPLETE, CONTRACTOR SHALL BE
RESPONSIBLE FOR STARTUP, INSPECTORS' APPROVAL AND
CLEAN UP.
CONTROLS NOTE
FMB CONTROLS SHALL MATCH MALL CONTROLS SYSTEM.
CONTROLS CONTRACTOR SHALL TIE — INTO EXISTING CONTROLS
FOR ❑PERATI ❑N.
MECHANICAL KEYED NOTES:
(MECHANICAL KEYED NOTES APPLY TO THIS SHEET
ONLY)
El
MECHANICAL SYMBOL LEGEND: REviEP;NOE
NOTE. THE F ❑LL ❑WING SYMBOLS SHALL BE AS CODE CO �
INDICATED, UNLESS NOTED OTHERWISE ON PLANS. APPR
x
0 THERMOSTAT
1vzl DUCT FLEX
SD -1: 24'x24' SUPPLY
DIFFUSER
RG -1: 24'x24' RETURN
GRILLE
711 CEILING MOUNTED INLINE
EXHAUST FAN.
PER 2006 IMC SECTION 606
Install smoke detector to shut down air distribution
by VAV's when the total combined C F M of all
VAV's (to include other tenants) sharing the same
plenum space exceeds 2000 CFM.
(See LI IC 606.2.2 for approved method of detection)
CONNECT TO EXISTING SUPPLY AIR MAIN (VERIFY
IN FIELD).
CONNECT EXHAUST FROM TOILET EXHAUST FAN TO
MALL EXHAUST DUCT MAIN (VERIFY IN FIELD).
Permit No
FILE COPY
Consultant
Plar review approval is subject to errors and omits.
Approval of construction documents does not authorize
the violation of any adopted code or ordnance. Receipt
of approved Fi• =:d . opy and candid • - acknowledged:
By
Date: / //�
City of Tukwila
BUILDING DIVISION
Consultant Registration
.�- E1SIOtiS Q scope
No changes shall be made to the of
of work without prior app
Tukwila Building Division n sobm tat ,
Revisions 0 require a new plan
NO include additional pan review flees
and may - --- ----.—
j SEPARATE PERMIT
I REQUIRED FOR:
C7 Mechanic
Electrical
J:g lumbing
Elf Gas Piping
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
APR 2 4 2008
PERMIT CENTER
M O ( V7-
2897
Southcenter Mall
Tukwila, WA 98188
aaith co.
1725 westlake ave. n.
suite 210
seattle, washington 98109
206.838.5485 p
206.713.4076 m
206.464.0700 f
ksmith @smithco.org
http: / /www.smithco.org/
Issues and Revisions
No. Date
1 03.31.08
Project Number 02008018.00
Description MECHANICAL PLAN
Scale AS NOTED
Template 4.3 (120101)
M -1
6294
Architect Registration
El
REGISTERED
ARCHi7ECT
STATE OF WASHINGTON
Issues By Check
PERMIT KLS
Project Name WESTFIELD SOUTHCENTER MALL
Computer File CW05- 2008- M1.DWG
All ideas, designs, arrangements, and plans indicated or
represented by this drawing are owned by and the property of
smith co. IIc and were created, evolved, and developed
for use on and in connection with the specified project. None of
such ideas, designs, arrangements or plans shall be used
by or disclosed to any person, firm, or corporation for any
purpose whatsoever without the written permission of smith co. IIc.
FAN POWERED VARIABLE AIR VOLUME BOX SCHEDULE
MARK
FMB-1
FMB -2
FMB -3
FMB-4
FMB -5
INLET SIZE
6" 0
8 "0
10 "0
12 "0
14 "0
PRIMARY AIR CFM RANGE: MINIMUM
80
145
230
325
450
MAXIMUM
500
900
1400
2000
3000
DESIGN PRIMARY AIR FLOW (MAXIMUM
COOLING CFM)
SEE PLAN
SEE PLAN
SEE PLAN
SEE PLAN
SEE PLAN
MINIMUM DESIGN PRIMARY AIR INLET S.P. (in.
w.g.)
0.5"
0.5"
0.5"
0.5"
0.5"
FAN DESIGN AIR FLOW (CFM)
300
500
700
950
1500
MINIMUM DOWNSTREAM S.P. (in. w.g.) (FAN
S.P.)
0.5"
0.5"
0.5"
0.5"
0.5"
NC DISCHARGE @ PRIMARY AIR
A PS =1.5"
15
20
22
26
26
REHEAT COIL: TYPE
ELECTRIC
ELECTRIC
ELECTRIC
ELECTRIC
ELECTRIC
KW
3.0
5.0
10.0
15.0
15.0
VOLT /PHASE
277/10
277/10
480/30
480/30
480/30
ELECTRICAL DATA: HP
1/6
1/4
1/4
1/3
1/3
VOLT /PHASE
277/10
277/10
277/10
277/10
277/10
F.L.A.
0.8
1.4
1.4
3.0
3.0
BASED ON: MANUFACTURER
TITUS
TITUS
TITUS
TITUS
TITUS
DTFS
DTFS SIZE B
DTFS SIZE C
DTFS SIZE C
DTFS SIZE D
DTFS SIZE D
APPLICABLE NOTES
1,2,3,4,5,6,7
1,2,3,4,5,6,7
1,2,3,4,5,6,7
1,2,3,4,5,6,7
1,2,3,4,5,6,7
AIR DEVICE SCHEDULE
MARK
DESCRIPTION
SIZE
MAXIMUM CFM
MAX. P.D.
(in. w.g.)
MAXIMUM
NC LEVEL
BASED ON
APPLICABLE
NOTES
MANUFACTURER
MODEL
SD -1
SQUARE LOUVER FACED CEILING DIFFUSER
24 "x24"
SEE CAPACITY
SCHEDULE
0.1"
30
TITUS
TMSA
1, 2, 3
SR -1
WALL AND /OR DUCT MOUNTED SUPPLY REGISTER, DOUBLE DEFLECTION
SEE PLANS
SEE PLANS
0.1"
30
TITUS
300RL
1, 3, 4
RG -1
EGGCRATE RETURN GRILLE
SEE PLANS
SEE PLANS
0.1"
30
TITUS
50F
1, 3, 4
EG -1
EGGCRATE EXHAUST GRILLE
12 "x12°
SEE PLANS
0.1"
30
TITUS
50F
1, 2, 3, 4
FAN SCHEDULE
MARK
EF -1
SERVES
RESTROOM
LOCATION
CEILING
TYPE
CEILING
CFM
100
EXTERNAL STATIC PRESSURE (in. w.g.)
0.6"
ELECTRICAL DATA DRIVE
DIRECT
HP
80 WATTS
VOLTS /PHASE
115/10
FAN RPM
950
BASED ON: MANUFACTURER
GREENHECK
MODEL
SP -B110
APPLICABLE NOTES
1, 2
AIR DEVICE
CAPACITY SCHEDULE
MARK
CFM RANGE
FACE SIZE
(inches)
SR -1
(272 RL)
0 -135
6 "x6"
136 - 240
10"x6"
241 - 340
14"x6"
341 - 450
18 "x6"
451 - 775
18 "x10"
AIR DEVICE
CAPACITY SCHEDULE
MARK
CFM RANGE
NECK SIZE
(inches)
SD -1
0 - 250
8 "0
251 - 425
10 "0
426 - 700
12 "0
701 -1000
14 "0
AIR DEVICE NOTES:
1. DESIGN CFM AS NOTED ON PLANS.
2. SEE AIR DEVICE CAPACITY SCHEDULE FOR NECK SIZE. DUCT SIZE TO DIFFUSER/REGISTER /GRILLE SHALL BE
EQUAL TO NECK NECK SIZE, UNLESS OTHERWISE NOTED.
3. PROVIDE MOUNTING FRAME AND BORDER STYLE TO ACCOMMODATE THE ARCHITECTS REFLECTED CEILING 8. ALL AIR DEVICES SHALL HAVE OFF -WHITE FINISH UNLESS OTHERWISE NOTED.
PLAN AND /OR WALL CONSTRUCTION.
4. PROVIDE VOLUME DAMPER.
5. RETURN, EXHAUST, AND TRANSFER GRILLES SHALL BE 24 "x24 ", UNLESS OTHERWISE NOTED ON PLANS.
FAN MIXING BOX PLAN INFORMATION:
REHEAT COIL
MAXIMUM
DESIGN
PRIMARY
AIR CFM
500 (50)
OTHERWISE NOTED
MIN. STOP @O%
OF DESIGN PRIMARY
AIR CFM
«FAN MIXING BOXES ARE ALSO AVAILABLE
IN 208 -240 VOLTS AND 277 VOLTS. THE
FLA WILL CHANGE ACCORDINGLY. SEE CATALOG
FOR CHANGES. »»
6. PROVIDE WITH MODULINEAR DIFFUSER PLENUM.
7. TRANSFER GRILLES ON PLANS INDICATED BY TG -1 (XX°0) SHALL BE PROVIDE WITH A RECTANGULAR TO
ROUND NECK ADAPTER.
FAN MIXING BOX NOTES:
1. FURNISH WITH IN THROWAWAY FILTERS, INTAKE PLENUM, HANGER RODS, AND SINGLE
POINT POWER CONNECTION.
2. DESIGN PRIMARY COOLING AIR CFM MINIMUM STOP @ 33% OF DESIGN PRIMARY COOLING
AIR, FOR ALL EXPOSURES OTHER THAN NORTH (USE 66% FOR NORTH).
3. PROVIDE DISCONNECTS. STARTER MOUNTED AT THE UNIT SUITABLE FOR THE MOTOR
HORSEPOWER.
4. DDC BOX CONTROLLER TO BE FURNISHED BY T.C.C. TO THE BOX MANUFACTURER, TO BE
INSTALLED AS FACTORY. FIELD CONTROL WIRING AND CONTROL TRANSFORMER BY T.G.C.
5. CONTRACTOR SHALL NUMBER ALL FAN MIXING BOXES, SO THAT EACH BOX HAS AN UNIQUE
NUMBER. COORDINATE NUMBERING SYSTEM WITH ELECTRICAL TRADES.
6. FOR THOSE FMB BOXES, WHICH AT THIS TIME ARE NOT PROVIDED WITH THERMOSTAT
LOCATIONS AND SUPPLY AIR DUCTWORK, PROVIDE 50' -0" OF CONTROL WIRING/TUBING AND
THERMOSTAT COILED UP AT FMB BOX.
7. PROVIDE INLET AIR PROVING SWITCH TO PROTECT ELECTRICAL REHEAT COIL.
FAN NOTES:
1. PROVIDE DISCONNECT.
2. PROVIDE THE FOLLOWING ACCESSORIES:
A. DESIGNER GRILLE.
B. BACKDRAFT DAMPER.
C. MOUNTING BRACKETS.
CEILING
RECTANGULAR
SUPPLY DUCT
NOT TO SCALE
45" CLINCH COLLAR OR ROUND
SPIN -IN FITTING CONNECTION WITH
MANUAL VOLUME DAMPER AND
LOCKING QUADRANT. (SEE PLAN)
TRANSITION TO ROUND OR ROUND
DUCT SAME AS DIFFUSER NECK
UNLESS NOTED OTHERWISE.
(SEE PLAN)
MAX. 5-0" LONG (EXTENDED) ROUND
FLEXIBLE DUCT CONNECTION SAME AS
DIFFUSER NECK DIA.
(1 -90 BEND. MAX.)
II
CEILING
DIFFUSER
(SEE PLAN)
STANDARD DIFFUSERAND DUCT CONNECTION DETAIL
MANUAL AIR VOLUME
DAMPER W/ LOCKING
QUADRANT (TYPICAL)
TRANSITION TO ROUND
WHEN REQUIRED (SEE PLAN)
fr/
2897 Southcenter Mall
Tukwila, WA 98188
smith ci.
1725 westlake ave. n.
suite 210
seattle, washington 98109
206.838.5485 p
206.713.4076 m
206.464.0700 f
ksmith@smithco.org
http: / /www.smithco.org/
Consultant
M (2
CLAMP (TYP)
Ii
RECEIVED
CITY OF TUKWIIA
APR 2 4 2008
PERMIT CE.'I ER
Consultant Registration
Issues and Revisions
No. Date
1 03.31.08
Architect Registration
REGISTERED
ARCHITECT
E i
STATE OF WASHINGTON
6294
Issues By Check
PERMIT KLS
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAY - 5 1008
City Of Tukwila
B ILDING DIVISI! N
Project Name WESTFIELD SOUTNCENTER MALL
Project Number
02006088.00
Description GENERAL INFORMATION
Computer File CW05- 2008- T1.DWG
Scale AS NOTED
Template 4.3 (120101)
All ideas, designs, arrangements, and plans indicated or
represented by this drawing are owned by and the property of
smith co. Ilc and were created, evolved, and developed
for use on and in connection with the specified project. None of
such ideas, designs, arrangements or plans shall be used
by or disclosed to any person, firm, or corporation for any
purpose whatsoever without the written permission of smith co. 11c.
M -2
MECHANICAL SPECIFICATIONS
15010:
GENERAL PROVISIONS: (THE WORD "CONTRACTOR" IN THIS ACTION SHALL REFER TO TENANTS PLUMBING,
FIRE SPRINKLER AND HVAC MECHANICAL CONTRACTORS).
A. GENERAL
1. THE GENERAL CONDITIONS OF THE CONTRACT, CURRENT EDITION PUBLISHED IN STANDARD FORM BY
AMERICAN INSTITUTE OF ARCHITECTS, SHALL BE PART OF THIS CONTRACT.
2. THE ARTICLES CONTAINED IN THIS DIVISION AND IN ARCHITECTURAL SPECIFICATIONS MAY AMEND,
MODIFY, SUPERSEDE, VOID OR SUPPLEMENT THE ARTICLES OF THE GENERAL CONDITIONS NOTED IN
PARAGRAPH 15010(A) ABOVE, AND SHALL TAKE PRECEDENCE OVER THE PROVISIONS OF THE GENERAL
CONDITIONS IN 15010(A).
3. THIS CONTRACTOR IS REFERRED TO THE ARCHITECTURAL, STRUCTURAL AND ELECTRICAL PLANS AND
SPECIFICATIONS WHICH ARE HEREBY MADE PART OF THE CONTRACT.
4. THIS CONTRACTOR SHALL TAKE OUT ALL NECESSARY PERMITS, LICENSES AND CERTIFICATES AND PM
ALL FEES CONNECTED THEREWITH.
5. BIDDERS SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES, WITH ALL CONDITIONS SURROUNDING
THE WORK PRIOR TO SUBMITTING THE BID.
6. DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW APPROXIMATE LOCATIONS UNLESS
SPECIFICALLY DIMENSIONED. COORDINATE THE WORK WITH THE OTHER TRADES TO AVOID INTERFERENCE.
SHOULD MECHANICAL WORK BE INSTALLED SUCH THAT IT INTERFERES WITH THE WORK OF OTHER
CONTRACTORS, SUCH WORK SHALL BE REDONE AT NO ADDITIONAL COST TO TENANT.
7. AT THE COMPLETION OF THE WORK THIS CONTRACTOR SHALL REMOVE ALL RUBBISH, DIRT AND STAINS
CAUSED BY HIS WORK AND SHALL THOROUGHLY CLEAN ALL MECHANICAL WORK INCLUDING EQUIPMENT,
FIXTURES, DUCTWORK, PIPING, APPLIANCES, ETC.
8. THIS CONTRACTOR SHALL TOUCH UP OR REFINISH THE FACTORY FINISH OF EQUIPMENT MARRED
DURING SHIPMENT OR INSTALLATION.
9. THIS CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR SUCH EQUIPMENT AND MATERIAL AS THE
OWNER MAY REQUIRE FOR HIS REVIEW. THE OWNERS REVIEW MUST TAKE PLACE BEFORE CONSTRUCTION
BEGINS. ' . •
10. "RECORD" DRAWINGS SHALL BE PROVIDED BY THE CONTRACTOR IF INSTALLATION DEVIATES FROM THE
ORIGINAL LAYOUT.
11. MOTORS SHALL BE DESIGNED FOR SUPPLY VOLTAGES AS SCHEDULED AND SHALL COMPLY WITH AIEE
AND NEMA REQUIREMENTS. PROVIDE ACROSS THE LINE STARTERS AN ALL MOTOR UNLESS NOTED
OTHERWISE. MOTORS 1.0 HP AND LARGER SHALL BE HIGH EFFICIENCY.
B. CODES
ALL WORK SHALL CONFORM TO ALL NATIONAL, STATE, COUNTY, CITY, HEALTH AND SAFETY AND ENERGY
CODES THAT APPLY, AS WELL AS WITH ALL LANDLORD CRITERIA. THIS CONTRACTOR SHALL INQUIRE INTO
AND COMPLY WITH ALL APPLICABLE CODES, ORDINANCES, AND REGULATIONS. THIS CONTRACTOR SHALL
INCLUDE ANY CHANGES REQUIRED BY CODES IN THE BID AND IF THESE CHANGES ARE NOT INCLUDED IN
THE BID, THEY MUST BE QUALIFIED AS A SEPARATE LINE ITEM IN THE BID. AFTER CONTRACT IS ISSUED,
NO ADDITIONAL COST DUE TO CODE ISSUES SHALL BE REIMBURSED TO THE CONTRACTOR.
C. TRADE NAMES, MANUFACTURERS AND SHOP DRAWINGS
WHERE TRADE NAMES AND MANUFACTURES ARE USED ON THE DRAWINGS OR IN THE SPECIFICATIONS,
THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR THE BASE BID. MANUFACTURES CONSIDERED
AS AN EQUAL OR BETTER IN AT ASPECTS TO THAT SPECIFIED WILL BE SUBJECT TO APPROVAL IN
WRITING BY CLIENT'S PROJECT MANAGER OR ENGINEER THROUGH SHOP DRAWING SUBMITTAL PROCESS
FOR ACCEPTANCE PRIOR TO EQUIPMENT BEING ORDERED.
IF THE MECHANICAL CONTRACTOR WISHES TO SUBMIT ON ALTERNATE EQUIPMENT, THE CONTRACTOR
SHALL SUPPLY CUT SHEETS DESCRIBING DIMENSIONAL DATA, UNITS OPERATING WEIGHTS AND ELECTRICAL
CHARACTERISTICS TO THE ENGINEER. IN ADDITION, CONTRACTOR WILL SUPPLY ENGINEER WITH COMPUTER
GENERATED PERFORMANCE DATA FROM CONTRACTORS EQUIPMENT REPRESENTATIVE FOR ALTERNATE
EQUIPMENT. PERFORMANCE DATA SHALL BE CALCULATED FROM DESIGN CONDITIONS LISTED ON THE
EQUIPMENT SCHEDULES.
THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ADDITIONAL COSTS INCURRED BY OTHER
CONTRACTORS AS A RESULT OF USING EQUIPMENT NOT SPECIFIED OR SCHEDULED. EXAMPLES WOULD BE
LARGER WIRE OR CIRCUIT BREAKER SIZES OR ADDITIONAL STRUCTURAL SUPPORT.
THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT
THE CONTRACTS EXPENSE.
15020 DEMOLITION:
A. REMOVE ALL PIPING, DUCTWORK AND EQUIPMENT NOT BEING REUSED. PIPING AND ACCESSORIES
ASSOCIATED WITH EQUIPMENT BEING REMOVED, BUT NOT NECESSARILY NOTED ON DRAWINGS, SHALL
ALSO BE REMOVED.
B. EQUIPMENT AND MATERIALS BEING REMOVED SHALL REMAIN THE PROPERTY OF THE OWNER. THE
OWNER SHALL INDICATE WHICH ITEMS IF ANY ARE TO BE RETAINED. ITEMS TO BE SALVAGED SHALL BE
MOVED TO A STORAGE AREA THAT IS DESIGNATED BY THE OWNER. ALL OTHER MATERIALS AND
EQUIPMENT, NOT WANTED BY THE OWNER, SHALL BE REMOVED FROM THE SITE AND BE PROPERLY
DISPOSED OF.
C. WHERE EXISTING WALLS, FLOORS OR OTHER PORTIONS OF THE BUILDING REQUIRE PATCHING AFTER
REMOVAL OF MATERIAL OR EQUIPMENT, THE PATCHING SHALL BE THE RESPONSIBILITY OF THIS
CONTRACTOR.
D. NO ASBESTOS WORK OF ANY NATURE SHALL BE PERFORMED BY THE CONTRACTOR PURSUANT TO
THIS CONTRACT. IF DURING THE CONSTRUCTION OF THIS PROJECT, WORK INVOLVING ASBESTOS IS
SUSPECTED OR ENCOUNTERED, PROMPTLY NOTIFY THE OWNER, AND THE OWNER, WITH HIS OWN FORCES
OR BY SEPARATE CONTRACT SHALL BE RESPONSIBLE FOR COMPLETE REMOVAL AND DISPOSITION OF NE
ASBESTOS. IF THE CONTRACTOR CLAIMS THAT DELAY AND ADDITIONAL COST IS INVOLVED BECAUSE OF
THIS ACTION, HE SHALL MAKE CLAIM AS PROVIDED ELSEWHERE IN THE CONTRACT DOCUMENTS.
15400 PLUMBING:
(THE WORD CONTRACTOR IN THIS SECTION SHALL REFER TO TENANTS PLUMBING CONTRACTOR.)
A. SCOPE
UNLESS NOTED OTHERWISE, THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT
FOR THE INSTALLATION OF A COMPLETE AND TENANT ACCEPTABLE OPERATING PLUMBING SYSTEM HEREIN
DESCRIBED INCLUDING: HOT AND COLD WATER SYSTEMS, CONNECTION TO EXISTING SANITARY SEWER
SYSTEMS, PLUMBING FIXTURES, MISCELLANEOUS PLUMBING AND INSULATION.
B. MATERIALS
UNDERGROUND SANITARY SEWER AND VENT PIPING: BELL AND SPIGOT COST IRON WITH LEAD AND
OAKUM OR NEOPRENE COMPRESSION JOINTS OR HUBLESS CAST IRON WITH TYPE MG CAST IRON
COUPLINGS. STAINLESS STEEL BONDS ARE ACCEPTABLE IF COATED WITH BITUMASIIC. ABOVE GROUND
SANITARY SEWER AND VENT PIPING: BELL AND SPIGOT CAST IRON WITH LEAD AND OAKUM OR NEOPRENE
COMPRESSION JOINTS: OR HUBLESS CAST IRON PIPE AND JOINTING SYSTEM EXCEPT THAT TYPE MG
CAST COUPLINGS SHALL BE USED FOE STOCKS MANE THAN 25 FT. HIGH. VENT PIPING MAY ALSO BE
SCHEDULE 40 GALVANIZED STEEL WITH CAST IRON SCREWED DRAINAGE FITTINGS. VENT PIPING PASSING
THROUGH ROOF: CAST IRON WITH NOT LESS THAN 12" PROJECTION ABOVE ROOF WITH APPROVED FROST
JACKETS. WATER PIPING — TYPE L HARD COPPER WITH WROUGHT COPPER FITTINGS AND SHUT —OFF
VALVE AT EACH FIXTURE.
PIPING OF DISSIMILAR METALS MUST BE DIELECTRIC ALLY ISOLATED.
CONDENSATE DRAIN PIPING: SAME AS WATER PIPING.
PIPE HANGERS: CONFORM TO ANSI /MSS SP58. CONSTRUCT HANGERS OF CORROSION RESISTANT
GALVANIZED STEEL (MICHIGAN #100), EXCEPT PROVIDE COPPER PLATED HANGERS SUPPORTING COPPER
PIPING (MICHIGAN #100). SPACE HANGERS AS REQUIRED BY CODE, WITH A MINIMUM OF ONE HANGER
PER PIPE JOIST. SUPPORT HANGER FROM TOP OF STRUCTURAL MEMBER. DO NOT SUPPORT FROM ROOF
DECK OR OTHER EQUIPMENT.
VERTICAL PIPING SHALL BE SUPPORTED WITH STANDOUT HANGERS AT EACH JOINT AND RISER CLAMPS
AT FLOOR AND ROOF.
SMALL PIPING (3/4" OR LESS) IN WALLS MAY BE SUPPORTED FROM METAL WASTE OR VENT PIPING
USING WEJ —IT "ADJUSTABLE SPACER SYSTEM" COMPONENTS.
C. TESTING
TEST ALL PLUMBING PIPES AS REQUIRED BY STATE, CITY OR LOCAL CODES AND ORDINANCES. TESTS
SHALL BE MADE IN THE PRESENCE OF THE PROPER INSPECTION AUTHORITIES, AUTHORIZED
REPRESENTATIVE OF TENANTS ARCHITECT AND /OR THE LANDLORD'S ARCHITECT. FURNISH ALL
NECESSARY TEST CERTIFICATES TO THE ARCHITECT.
D. DISINFECTING WATER PIPES
DISINFECT THE ENTIRE WATER SUPPLY SYSTEM, FILLING WITH A SOLUTION OF 50 PPM OF AVAILABLE
CHLORINE AND ALLOW TO STAND SIX HOURS BEFORE FLUSHING AND RETURNING TO SERVICE.
E. PIPING INSULATION: EDIT FOR THICKNESS REQUIRED.
INSULATE DOMESTIC HOT WATER, COLD WATER AND CONDENSATE PIPING WITH 1/2" FIBERGLASS, WITH
ALL PURPOSE JACKET: SEAL ALL JOINTS. INSULATE FITTINGS WITH MITERED SEGMENTS AND VAPOR
SEALS, INSULATE ALL EXPOSED WASTE AND WATER PIPING ON HANDICAP FIXTURES USING TRUBRO KIT
NO. 102W WITH ACCESSORY NO. 105, OR APPROVED EQUAL.
F. CUTTING AND PATCHING
THIS CONTRACTOR SHALL DO ALL CUTTING AND PATCHING REQUIRED TO INSTALL ANY PORTION OF THIS
WORK. PATCH WITH NEW MATERIALS OF THE SAME TYPE THAT WAS REMOVED. REFINISH PATCHED
SURFACE TO MATCH EXISTING ADJACENT SURFACES. ALL ROOF PENETRATION BY LANDLORD'S ROOF
CONTRACTOR AT FIFE CONTRACTOR'S EXPENSE.
G. SANITARY SEWAGE
CONNECT NEW WASTE PIPING TO EXISTING SANITARY WASTE AT THE APPROXIMATE LOCATION SHOWN.
VERIFY EXACT LOCATION AND INVERT ELEVATION BEFORE COMMENCING WORK.
H. COLD WATER SERVICE
FURNISH AND INSTALL NEW COLD WATER PIPING FROM EXISTING PIPING TO, AND INCLUDING CONNECTION
TO, NEW PLUMBING FIXTURES AND HOT WATER HEATER AS SHOWN ON PLANS.
I. DOMESTIC HOT WATER
FURNISH AND INSTALL ONE (I) A.O. SMITH ELSE -10 OR EQUAL GLASS LINED ELECTRIC WATER HEATER
HAVING ONE 3000 WATT ELEMENT COMPLETE WITH SAFETY CONTROLS, AN ASME LABELED TEMPERATURE
AND PRESSURE RELIEF VALVE PIPED AS INDICATED ON PLANS AND TWO (2) SHUT —OFF VALVES. VERIFY
VOLTAGE WITH ELECTRICAL CONTRACTOR BEFORE ORDERING. OPERATING WEIGHT 80 LBS.
FURNISH AND INSTALL ONE (1) AMITROL, THERMAL EXPANSION TACK. 2 GALLON CAPACITY
MODEL: THERM —X— TROL —ST-5.
J. GAS PIPING
FURNISH AND METAL A COMPLETE GAS PIPING SYSTEM AS SHOWN ON PLANS. GAS LINES SHALL BE
BLACK STEEL, SCHEDULE 40. ASTM A -120, WITH MALLEABLE THREADED FITTINGS FOR 2" AND SMALLER,
AND WITH STANDARD BUTT — WELDED JOINTS FOR 2 -1/2" AND LARGER. FURNISH AND INSTALL A GAS
COCK, DIRT LEG, AND UNION CONNECTION TO EACH PIECE OF EQUIPMENT. PAINT ALL PIPING EXPOSED
ON ROOFTOP WITH RUST — INHIBITING PAINT.
PITCH PIPING AT A UNIFORM GRADE OF 1/4" IN 15 FEET UPWARD IN DIRECTION OF FLOW. SUPPORT
PIPING EVERY 5 FEET MIN. SUPPORT AS REQUIRED BY LANDLORD CRITERIA OR BY STANDARD INDUSTRY
PRACTICE, IF LANDLORD HAS NO REQUIREMENTS.
TESTING AND PURGING OF GAS PIPING SHALL BE DONE PER THE REQUIREMENTS OF THE LOCAL GAS
COMPANY, LOCAL CODES, AND APPLICABLE NPFA 54 CODES.
CONTACT AND COORDINATE GAS SERVICE, METER AND REGULATOR REQUIREMENTS WITH THE LOCAL GAS
UTILITY COMPANY AND THE MALL'S OPERATIONS MANAGER. INCLUDE INSTALLATION COST OF GAS METER
AND REGULATOR IN BID IF NOT PROVIDED BY UTILITY COMPANY.
K. MISCELLANEOUS PWM8ING ACCESSORIES
BACKFLOW PREVENTER: FURNISH AND INSTALL WATTS SERIES 7, OR APPROVED EQUAL BACKFLOW
PREVENTER WHERE SHOWN ON DRAWING.
15030 FIRE SPRINKLERS:
A. SYSTEMS
THE FIRE SPRINKLER SYSTEM AND HEAD LOCATIONS SHALL BE PER TENANTS FIXTURES, PARTITIONS,
SOFFITS, DROPS, CEILING HEIGHTS, ETC. SPRINKLER SYSTEM TO INCLUDE DROPS, HEADS AND FACILITIES
FOR PROPER DRAINAGE. DESIGN WET SPRINKLER SYSTEM FOR ORDINARY HAZARD GROUP 2 PER LATEST
EDITION OF NEPA 13.
THE SPRINKLER SYSTEM SHALL BE DESIGNED AND INSTALLED BY A LICENSED FIRE PROTECTION
CONTRACTOR IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF THE LANDLORD, LANDLORD'S FIRE
INSURANCE UNDERWRITER, AND ALL GOVERNMENTAL AGENCIES AND AUTHORITIES HAVING JURISDICTION
OVER THE PREMISES.
COMPREHENSIVE SHOP DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED BY THE CONTRACTOR FOR
THE APPROVAL BY THE OWNER LANDLORD. LANDLORDS FIRE INSURANCE UNDERWRITER, AND THE FIRE
RATING INSPECTION BUREAU (FACTORY MUTUAL). SPRINKLER SHOP DRAWINGS SHALL BE SUBMITTED TO
THE LOCAL FIRE MARSHALL'S OFFICE AND RECEIVE THEIR APPROVAL BEFORE ANY INSTALLATION CAN
BEGIN. APPROVED DRAWINGS MUST BE AT THE JOB SITE DURING CONSTRUCTION.
AFTER RECEIPT OF APPROVAL AND BEFORE PROCEEDING WITH ANY INSTALLATION WORK. TENANT SHALL
FORWARD TWO (2) SPRINKLER SHOP DRAWING BLUEHNE PRINTS BEARING THE FIRE INSURANCE
UNDERWRITERS STAMP OF APPROVAL TO THE LANDLORD FOR HIS RECORDS.
SPRINKLER HEADS LOCATED AT NE STOREFRONT, IN SHOWCASE WINDOWS AND IN HARD SURFACE
CEILINGS MUST BE CONCEALED TYPE. HEADS LOCATED IN ACOUSTIC CEILING MAY BE SEMI — RECESSED
TYPE. SURFACE MOUNTED HEADS ARE PERMITTED IN NON—CUSTOMER AREAS ONLY.
UNLESS OTHERWISE NOTED, ALL FIRE PROTECTION SPRINKLER HEADS SHALL BE QUICK RESPONSE (QR)
TYPE. SPRINKLER HEAD TYPES SHALL BE AS FOLLOWS: ALL SPRINKLER HEADS IN AREAS WITH FINISHED
CEILINGS TO BE RELIABLE MODEL G4QR CONCEALED PENDANT WITH STANDARD WHITE FINISH. ALL
SPRINKLER HEADS IN AREAS WITH UNFINISHED CEILING TO BE RELIABLE MODEL F1FR UPRIGHT WITH
CHROME FINISH. SPRINKLER IN TOILET ROOMS, OFFICE AND NON — CUSTOMER AREAS WITH FINISHED
CEILING TO BE RELIABLE MODEL F1FR SEMI — RECESSED PENDANT TYPE. VERIFY TYPES AND FINISHES WITH
ARCHITECT.
SHUT DOWN OF LANDLORD'S SPRINKLER MAIN SHALL BE ONLY DONE ON A SCHEDULE ESTABLISHED BY
LANDLORD. ANY DAMAGE CAUSED BY THIS CONTRACTOR TO LANDLORD'S SPRINKLER SYSTEM WILL BE
REPAIRED BY LANDLORDS CONTRACTOR AT THIS CONTRACTORS EXPENSE.
THE SPRINKLER SYSTEM SHALL BE TESTED AT WATER PRESSURE OF 200 PSIG FOR A PERIOD OF TWO
(2) HOURS IN THE PRESENCE OF LANDLORDS REPRESENTATIVE OR AS REQUIRED BY LANDLORD.
SPRINKLER PIPING SHALL BE SCHEDULE 10 AND SCHEDULE 40 BLOCK STEEL. HANGERS SHALL BE AS
REQUIRED BY NFPA 13.
UPON COMPLETION OF THE SYSTEM AND ON POSSESSION OF PREMISES, SUBMIT A WRITTEN CERTIFICATE
TO LANDLORD FROM THE UNDERWRITER STATING THAT THE SYSTEM WAS INSPECTED AND APPROVED.
15040 HEATING, VENTING AND AIR CONDITIONING:
(THE WORD CONTRACTOR IN THIS SECTION SHALL REFER TO TENANT MECHANICAL CONTRACTOR).
A. SCOPE
UNLESS STATED OTHERWISE, THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT
FOR THE INSULATION OF A COMPLETE AND TENANT ACCEPTABLE OPERATING HEATING AND AIR
CONDITIONING SYSTEM HEREIN DESCRIBED, AND AS SHOWN ON PLANS.
THE SPACE IN GENERAL SHALL BE HEATED AND COOLED BY MEANS OF A PACKAGED ROOFTOP AIR
CONDITIONING UNIT(S) WITH GAS HEAT AND UTILIZING A DX COIL AND PACKAGED AIR COOLED
CONDENSING COMPRESSING UNIT(S) FOR COOLING.
B. ROOFTOP AIR CONDITIONING UNIT(S)
PROVIDE CARRIER, TRANE, OR APPROVED EQUAL ROOFTOP AIR CONDITIONING UNIT(S) AS SCHEDULED ON
THE DRAWINGS. UNIT(S) SHALL BE COMPLETE WITH BELT — DRIVEN FAN, ADJUSTABLE DRIVE, INTERNALLY
INSULATED HOUSING, DIRECT EXPANSION COOLING COIL, GAS HEAT, COMPRESSOR, AIR COATED
CONDENSER, DRIP PAN, FILTER SECTION WITH THROWAWAY PLEATED FILTERS, INTERNAL VIBRATION
ISOLATORS, AND 14" HIGH ROOF CURB. FURNISH UNIT(S) WITH ADDITIONAL ACCESSORIES AS SCHEDULED
ON THE DRAWINGS. VERIFY OPERATING VOLTAGE WITH ELECTRICAL CONTRACTOR BEFORE ORDERING.
C. CONTROLS
PROVIDE ALL CONTROLS, WIRING, SENSORS, RELAYS. ETC. FOR A COMPLETE OPERATING SYSTEM THAT IS
COMPATIBLE WITH INSTALLED EQUIPMENT ARID ALL LANDLORD REQUIREMENTS, INCLUDING EMERGENCY
SHUTDOWN OF HVAC EQUIPMENT, UNLESS NOTED OTHERWISE.
PROVIDE MULTI—STAGE HEAT /COOLED PROGRAMMABLE THERMOSTAT COMPATIBLE WITH INSTALLED
EQUIPMENT AND LANDLORDS SYSTEM. THERMOSTAT SHALL BE HONEYWELL T -7300 OR EQUIVALENT
PRODUCT FURNISHED BY THE MANUFACTURER OF THE INSTALLED EQUIPMENT. THERMOSTAT SHALL BE
MOUNTED 5' -6" ABOVE FINISHED FLOOR, UNLESS NOTED OTHERWISE ON THE DRAWINGS.
D. SEQUENCE OF OPERATION
OCCUPIED HOURS: SUPPLY FAN SHALL OPERATE CONTINUOUSLY AND THE OUTSIDE AIR DAMPER SHALL
BE OPEN TO THE MINIMUM POSITION. DX COIL OR GAS SHALL CYCLE TO MAINTAIN SPACE TEMPERATURE
SETPOINT.
UNOCCUPIED HOURS: OUTSIDE AIR DAMPER SHALL BE CLOSED. SUPPLY FAN AND CONDENSING UNIT OR
ELECTRIC HEATING SHALL CYCLE TO MAINTAIN SPACE TEMPERATURE SETPOINT.
ECONOMIZER MODE: DIFFERENTIAL ENTHALPY CONTROLLED ECONOMIZER SHALL ACTIVATE WHENEVER THE
OUTSIDE AIR ENTHALPY IS LOWER THAN THE ENTHALPY CONTROL SETTING. ECONOMIZE, DAMPERS SHALL
MODULATE TO FULL OPEN POSITION, AS REQUIRED, TO MAINTAIN DISCHARGE AIR TEMPERATURE BETWEEN
52 AND 58 DEGREES FAHRENHEIT. MECHANICAL COOLING /HEATING SHALL BE LOCKED OUT OF
ECONOMIZER MODE. WHEN THE SPACE TEMPERATURE SETPOINT IS SATISFIED, THE DAMPER SHALL
RETURN TO THE MINIMUM OUTSIDE AIR POSITION DURING OCCUPIED MODE AND CLOSE COMPLETELY
DURING UNOCCUPIED MODE.
SMOKE ALARM MODE: UPON A SIGNAL FROM THE DUCT SMOKE DETECTORS OR ZONE SMOKE
EXHAUST /FIRE ALARM SYSTEM, UNIT(S) SHALL SHUT DOWN, AND THE OUTSIDE AIR DAMPER SHALL
CLOSE.
E. CUTTING AND PATCHING
THIS CONTRACTOR SHALL DO ALL CUTTING AND PATCHING REQUIRED TO INSTALL ANY PORTION OF THIS
WORK. PATCH NEW MATERIALS OF THE SAME TYPE THAT WAS REMOVED. REFINISH PATCHED SURFACE TO
MATCH EXISTING ADJACENT SURFACES. ALL ROOF PENETRATIONS BY LANDLORD ROOF CONTRACTOR AT
THIS CONTRACTOR'S EXPENSE.
F. DUCTWORK
CONSTRUCT ALL LOW VELOCITY DUCTWORK OF APPROPRIATE GAUGE SHEET METAL FOR INDICATED SIZES
IN ACCORDANCE WITH SMACNA STANDARDS. ROUTE DUCTWORK SUBSTANTIALLY AS SHOWN ON THE
CONTRACT DOCUMENTS. ALL BENDS AND CURVES SHALL BE LONG RADIUS. SEAL ALL DUCTWORK IN
ACCORDANCE WITH SMACNA STANDARDS: ABOVE 2 W.G. STATIC PRESSURE -- SEAL CLASS "A" BETWEEN
1" AND 2" W.G. — SEAL CLASS "B" LESS THAN 1" W.G. — SEAL CLASS "C" DUCT SIZES SHOWN ON
DRAWINGS OR INSIDE DIMENSIONS.
INSTALL RIGID ALL METAL DUCT SUPPORT SYSTEMS AS INDICATED IN SMACNA STANDARD. SUPPORT
HORIZONTAL DUCTS WITHIN 2 FEET OF EACH ELBOW AND WITHIN 4 FEET OF EACH BRANCH INTERSECTION
USING STRAP HANGERS ON EACH SIDE OF FITTING. SUPPORT VERTICAL DUCTS AT A MAXIMUM INTERVAL
OF 16 FEET AND AT EACH FLOOR. NO WOOD SHALL BE USED TO SUPPORT OR BRACE DUCTS. PROVIDE
SWAY AND SEISMIC BRACING AS REQUIRED BY STATE AND LOCAL CODES OR BY LANDLORD.
FLEXIBLE DUCTWORK SHALL BE WIREMOLD WCK OR WK. THERMAFLEX M —KE. FLEXMASTER 3M OR NORFLEX
NT -25M. MAXIMUM FLEXIBLE DUCT LENGTHS SHALL BE 5 FT. FLEXIBLE DUCTWORK SHALL BE EXTERNALLY
INSULATED WITH UL LISTED 1" FLEXIBLE FIBERGLASS AND NON — COMBUSTIBLE VAPOR BARRIER .
INSTALL ADJUSTABLE QUADRANT DAMPERS IN ALL BRANCH DUCTS, AND AS REQUIRED TO BALANCE THE
AIR SYSTEM.
G. BALANCING AIR SYSTEMS
TESTING, ADJUSTING AND BALANCING OF ALL WORK SHALL BE MADE BY AN INDEPENDENT CONTRACTOR
WHO A IS CURRENTLY LICENSED ASSOCIATED AIR BALANCING COUNCIL (AACD) OR NATIONAL
ENVIRONMENTAL BALANCING BUREAU (NEBB) BALANCING CONTRACTOR. THE MECHANICAL CONTRACTOR
CAN NOT BE USED TO BALANCE THE SYSTEM. ALL BALANCING WORK MUST BE COMPLETE AND DONE IN
ACCORDANCE WITH THE MOST RECENT STANDARDS OF THEIR SOCIETY. PAYMENT OF ALL COSTS FOR
TESTING AND BALANCING SHALL BE BY THE GENERAL CONTRACTOR.
THE HVAC CONTRACTOR SHALL BE PRESENT FOR THE AIR BALANCE TO VERIFY ACCESSIBILITY TO ALL
DEVICES, VERIFY ALL OPERATING SEQUENCES. THE MECHANICAL CONTRACTOR SHALL REMOVE AIR FILTER
USED DURING CONSTRUCTION AND INSTALL NEW FILTERS IN ALL UNITS JUST PRIOR TO THE AIR BALANCE
WORK BEING DONE. THE COMPLETE AIR BALANCE SHALL TAKE PLACE WITH OUTSIDE AIR DAMPERS IN
MINIMUM POSITION, EXCEPT AS NOTED OTHERWISE. HVAC CONTRACTOR SHALL ALSO INSTALL A NEW SET
OF FILTERS AT THE TIME OF PROJECT TURNOVER.
ALL CONTROL SEQUENCES SHALL BE TESTED AND CORRECTED /ADJUSTED AS REQUIRED FOR CORRECT
OPERATION AS SPECIFIED (INTERLOCKED EQUIPMENT SMOKE DETECTORS, SMOKE EVACUATION,
ECONOMIZER. ETC.) AND OPERATING STATUS RECORDED IN THE REPORT.
G.C. TO PROVIDE A COPY OF THE FIND BALANCING REPORT TO LANDLORD, TENANT, CODE OFFICIALS (IF
REQUIRED) AND 3 COPIES TO THE ENGINEER. NO OTHER BALANCE REPORTS WILL BE REVIEWED OR
ACCEPTED.
H. START UP OF SYSTEMS. GUARANTEE AND INSTRUCTIONS
THIS CONTRACTOR SHALL GUARANTEE AND MAINTAIN THE STABILITY OF ALL WORK AND MATERIALS FOR
A PERIOD OF ONE (I) YEAR AFTER THE FINAL PAYMENT FOR COMPLETION OF NE WORK AS EVIDENCED
BY FINAL APPROVAL OF TENANT'S ARCHITECT. DEFECTS OF ANY KIND DUE TO FAULTY WORK OR
MATERIALS APPEARING DURING THE ABOVE— MENTIONED PERIOD MUST BE IMMEDIATELY CORRECTED BY
THIS CONTRACTOR AT HIS OWN EXPENSE TO THE ENTIRE SATISFACTION. OF TENANT'S ARCHITECT AND
ENGINEERS. SUCH RECONSTRUCTION AND REPAIRS SHALL INCLUDE ALL DAMAGE TO THE FINISH OR
FURNISHINGS OF THE BUILDING RESULTING FROM THE ORIGINAL DETECTOR REPAIRS THERETO. TENANTS
DESIGNATED OPERATING PERSONNEL SHALL BE FULLY INSTRUCTED BY THIS CONTRACTOR IN THE
OPERATION OF EACH MECHANICAL SYSTEM AT THE TIME IT IS BEING PUT IN SERVICE. ASSEMBLE IN
PORTFOLIO FORM AND DELIVER TO TENANT BEFORE FINAL PAYMENT IS MADE FOUR (4) COMBINED SETS
OF SHOP DRAWINGS, MANUFACTURERS BULLETINS OR OTHER DATA AS REQUIRED COVERING THE CARE,
MAINTENANCE, AND OPERATION OF EACH PIECE OF EQUIPMENT FURNISHED.
I. DIFFUSERS. GRILLES AND REGISTERS
FURNISH AND INSTALL: TITUS, OR APPROVED EQUAL CEILING DIFFUSERS AS SCHEDULED. IF CONTRACTOR
WISHES TO SUBMIT DIFFERENT GRILLES, REGISTERS, OR DIFFUSERS, CONTRACTOR WILL SUBMIT SHOP
DRAWINGS TO ENGINEER PRIOR TO PURCHASING ANY MATERIAL.
L. EXHAUST SYSTEM
FURNISH AND INSTALL COOK. PENN, GREENHECK OR EQUAL, CEILING EXHAUST FAN WITH BACKDRAFT
DAMPERS AND DUCTWORK COMPLETE AS SHOWN ON DRAWINGS.
M. INSULATION
1. ALL CONCEALED SUPPLY DUCTWORK SHALL BE EXTERNALLY INSULATED.
a: MATERIAL: OWENS— CORNING OR APPROVED EQUAL 1/2" REINFORCED FOIL FACED FIBERGLASS
(VAPOR SEALED) INSULATION. INSTALL IN ACCORDANCE WIN MANUFACTURERS RECOMMENDATIONS.
2. EXPOSED SUPPLY DUCTWORK SHALL BE ACOUSTICALLY LINED 10' -0" MINIMUM FROM ANY FAN OR
SHOWN ON THE PLANS.
a. ACOUSTICAL INTERNAL INSULATION SHALL BE I" OWENS— CORNING FIBERGLASS COATED DUCT LINER
BOARD OR APPROVED EQUAL. DUCT SIZES SHOWN ON PLANS ARE INSIDE CLEAR DIMENSIONS. APPLY
INSULATION WITH MANUFACTURER'S APPROVED ADHESIVES, MASTICS AND MECHANICAL FASTENERS.
3. ALL RETURN EXPOSED OR CONCEALED SHALL BE ACOUSTICALLY LINED 1O' -0" MINIMUM FROM ANY
FAN OR AS SHOWN ON THE PLANS.
a: ACOUSTICAL INTERNAL INSULATION SHALL BE 1" OWENS — CORNING FIBERGLASS COATED DUCT LINER
BOARD OR APPROVED EQUAL. DUCT SIZES SHOWN ON PLANS ARE INSIDE CLEAR DIMENSIONS. APPLY
INSULATION WITH MANUFACTURER'S APPROVED ADHESIVES, MASTICS AND MECHANICAL FASTENERS.
N. SMOKE DETECTORS
CONTRACTOR TO FURNISH AND INSTALL PYROTRONICS OR APPROVED EQUAL, IONIZATION TYPE DUCT
SMOKE DETECTOR IN RETURN AIR DUCT TO DE— ENERGIZE SUPPLY AIR UNIT UPON ACTIVATION.
ELECTRICAL CONTRACTOR TO PROVIDE POWER TO SMOKE DETECTOR.
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAY - 5 2008
City Of Tukwila
BVILDING DIVISION
APR 2 4 /1
PERMIT Ctrs€ I.N
2897 Southcenter Mall
Tukwila, WA 98188
smith e*.
1725 westlake ave. n.
suite 210
seattle, washington 98109
206.838.5485 p
206.713.4076 m
206.464.0700 f
ksmith @smithco.org
http: / /www.smithco.org/
Consultant
Mg- (Q.--
Consultant Registration
Issues and Revisions
No. Date
1 03.31.08
Project Number 02008018.00
Computer File CW05- 2008— M2.DVG
Scale AS NOTED
Template 4.3 (120101)
M -3
Architect Registration
REGISTERED
ARCHITECT
KB
STATE OF WASHINGTON
6294
Issues By Check
PERMIT KLS
Project Name WESTFIELD SOUTHCENTER MALL
Description MECHANICAL SPECIFICATI ❑NS
All ideas, designs, arrangements, and plans indicated or
represented by this drawing are owned by and the property of
smith co. Ilc and were created, evolved, and developed
for use on and in connection with the specified project. None of
such ideas, designs, arrangements or plans shall be used
by or disclosed to any person, firm, or corporation for any
RECEi E0 purpose whatsoever without the written permission of smith co. IIc.
CITY OF TtJKWILA