HomeMy WebLinkAboutPermit M08-156 - SMILES AT SOUTHCENTERSMILES @ SOUTHCENTER
15425 53 AV S
M08 -156
Parcel No.: 1157200033
Address:
Suite No:
15425 53 AV S TURIN
Tenant:
Name: SMILES AT SOUTHCENTER
Address: 15425 53 AV S , TUKWILA WA
CitAbf Tukwila
Owner:
Name: QUESTAR PARTNERSHIP
Address: PO BOX 98210 , LAKEWOOD WA
Contact Person:
Name: KEO TORRE
Address: 727 S KENYON ST , SEATTLE WA
Contractor:
Name: EVERGREEN REFRIGERATION LLC
Address: 727 S KENYON ST , SEATTLE WA
Contractor License No: EVERGRL954R2
DESCRIPTION OF WORK:
INSTALL (2) ROOFTOP PACKAGED HVAC UNITS, (7) EXHAUST FANS, DUCTWORK, GRILLES,
AND DIFFUSERS. (1) VVT ZONE DAMPER, BYPASS AND CONTROLS.
Value of Mechanical: $38,000.00
Type of Fire Protection:
Furnace: <100K BTU 0
>100K BTU 0
Floor Furnace 0
Suspended/Wall/Floor Mounted Heater 0
Appliance Vent 0
Repair or Addition to Heat/Refrig /Cooling System.... 0
Air Handling Unit <10,000 CFM 0
>10,000 CFM 2
Evaporator Cooler 0
Ventilation Fan connected to single duct 7
Ventilation System 0
Hood and Duct 0
Incinerator: Domestic 0
Commercial/Industrial 0
doc: I MC -10/06
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: hq•://www.ci.tukwila.wa.us
MECHANICAL PERMIT
Fees Collected: $597.50
International Mechanical Code Edition: 2006
EQUIPMENT TYPE AND QUANTITY
* *continued on next page **
M08 -156
Permit Number:
Issue Date:
Permit Expires On:
Phone:
Phone: 206 763 -1744
Phone: 206 763 -1744
Expiration Date: 01/06/2010
M08 -156
06/18/2008
12/15/2008
Boiler Compressor:
0 -3 HP /100,000 BTU 0
3 -15 HP /500,000 BTU 0
15 -30 HP /1,000,000 BTU.. 0
30 -50 HP /1,750,000 BTU.. 0
50+ HP /1,750,000 BTU 0
Fire Damper 0
Diffuser 0
Thermostat 0
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment 1
Printed: 06-18 -2008
Permit Center Authorized Signature:
doc: I MC -10/06
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.
[A)
Permit Number: M08 -156
Issue Date: 06/18/2008
Permit Expires On: 12/15/2008
Date: l� Tl` D
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the perform ce of work. I am authorized to sign and obtain this mechanical permit.
Signature: o� Date: (0 ft $ ` /
01 7
Print Name: 16 �U U �
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
M08 -156 Printed: 06-18 -2008
Parcel No.: 1157200033
Address: 15425 53 AV S TUKW
Suite No:
Tenant:
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
SMILES AT SOUTHCENTER
1: ** *BUILDING DEPARTMENT CONDITIONS * **
PERMIT CONDITIONS
Permit Number:
Status:
Applied Date:
Issue Date:
M08 -156
ISSUED
05/29/2008
06/18/2008
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431- 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
6: Manufacturers installation instructions shall be available on the job site at the time of inspection.
7: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the Cityof Tukwila
Permit Center.
8: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431 - 3670).
9: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
10: ** *FIRE DEPARTMENT CONDITIONS * **
11: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
12: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
13: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
14: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
15: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
doc: Cond -10/06
M08 -156 Printed: 06-18 -2008
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
16: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (ITC
104.2)
17: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
18: Local U.L. central station supervision is required. (City Ordinance #2051)
19: The installation of wiring and equipment shall be in accordance with N.F.P.A. 70, Article 760, Fire Protective
Signaling Systems. (NFPA 72- 1.3.3)
20: Live or "Hot" parts of electrical equipment operating at 50 volts or more shall be guarded against accidental contact.
Install a cover plate to prevent this. (NEC 110.27(2))
21: To schedule all construction fire - related inspections send an e -mail to fireinsprequest @ci.tukwila.wa.us. Include your
name, telephone number, permit number, project name and address and type of inspection requested.
22: This review limited to speculative tenant space only - special fire permits may be necessary depending on detailed
description of intended use.
23: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
24: These plans were reviewed by Inspector 0700. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
* *continued on next page **
doc: Cond -10/06 M08 -156 Printed: 06-18 -2008
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating
construction or the performance of work.
Signature:
doc: Cond -10/06
P ------- Date: m 051‘6
Print Name: ye' Take '
M08 -156 Printed: 06-18 -2008
SITE LOCATION
15yLf s3/c
snnl fro
Property Owners Name: QVQS {a Po V t►1& 5h. r
Mailing Address: � 6o at $z ( U
Site Address:
Tenant Name:
CONTACT PERSON - who do we contact when your permit is ready to be issued
Name: 7
Mailing Address: —
S
-Mail Address:
MECHANICAL CONTRACTOR INFORMATION -
Company Name:
Mailing Address:
S�ntact Person:
E -Mail Address:
Contractor Registration Number: F VF (C7 g L 1s-ti c 2
ARCHITECT OF RECORD - All plans must be wet stamped by Architect of Record
Company Name:
Mailing Address:
Contact Person:
E -Mail Address:
ENGINEER OF RECORD - All plans must be wet stamped by Engineer of Record
Company Name:
Mailing Address:
Contact Person:
E -Mail Address:
CITY OF TUKWIL•
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
hitp://www.ci.tukwila.wa.us
I re, f-ti .
f:vf gefrti7ki1vri Lc
1 s- !znio, SI.
Q \Applications'Forms- Applications On Line'3 -2006 - Mechanical Permit Applicatioadoc
Revised: 4 -2006
bh
MECHANICAL PERMIT APPLICATION
Mechanical Pe mi No.
Project No.
(For office use only)
Mock (St°
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
King Co Assessor's Tax No.: f f7 200
Suite Number:
LU tie '-Cad
City
Day Telephone: 706 -1f jr (7(1 t4
fame, L q pycj
City State Zip
Fax Number: 2 3 — z', $7
City State Zip
Day Telephone: ZC7(o 'fee 1 —
Fax Number: Za6 - 7( 2311
Expiration Date: t / Ca / l c✓
City
Day Telephone:
Fax Number:
City
Day Telephone:
Fax Number:
Floor:
New Tenant: ''.... Yes El ..No
State
State
State
V
�j 7144
Zip
Zip
Zip
Page 1 of 2
Unit Type:
Qty
Unit Type:
Qty
Unit Type:
Qty
Boiler /Compressor:
Qty
Furnace <100K BTU
Air Handling Unit >10,000
CFM
2
Fire Damper
0 -3 HP /100,000 BTU
Furnace >100K BTU
Evaporator Cooler
Diffuser
3 -15 HP /500,000 BTU
Floor Furnace
Ventilation Fan Connected
to Single Duct
Thermostat
15 -30 HP /1,000,000 BTU
Suspended /Wall/Floor
Mounted Heater
Ventilation System
Wood /Gas Stove
30 -50 HP/1,750,000 BTU
Appliance Vent
Hood and Duct
Water Heater
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Refrig/Cooling
System
Incinerator - Domestic
Emergency
Generator
Air Handling Unit
<10,000 CFM
Incinerator - Comm /Ind
Other Mechanical
Equipment
``
t
�t,
VVI ?4Q, 1�GI/'t f
Valuation of Project (contractor's bid price): $ .3
Scope of Work (please provide detailed information): - TM J f J (Z-) ('f Plaoy-e., kv'l . 11 11J
(I) cl- Ian S I - G'- awvrl� , q t :II.e J s (I ) V✓ 7 on't
dcMfN ht fa5l 'net re4-1- I
Use: Residential: New .... Replacement ....
Commercial: New ....p Replacement ....0
Fuel Type: Electric 0 Gas ....0 Other:
Indicate type of mechanical work being installed and the quantity below:
PERMIT APPLICATION NOT-ES — Applicable to all permits in this application
Value of Construction - in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review - Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested
in writing and justifiable'cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND 1 AM AUTHORIZED TO APPLY FOR THIS PERMIT.
Signature:
BUILDING Orbs NER OR.AUTHORIZED AGENT:
Print Name:
y, — root,
Mailing Address: 17 } • 11A S •
Date Application Accepted:
6/9-01
Q 1Applications\Forms- Applications On Line13 -2006 - Mechanical Permit Application doc
Revised 4 -2006
bh
a v
Date Application Expires:
City
Day Telephone:
<<
Date: C J / z c /
State
Staff Initials:
Zip
Page 2 of 2
Doc: RECSETS -06
RECEIPT NO: R08 -01854
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: //www.ci.tukwila.wa.us
Initials: JEM Payment Date: 05/29/2008
User ID: 1165
Payee: EVERGREEN REFRIGERATION, LLC
SET ID: S000001038 SET NAME: Tmp set/Initialized Activities
SET TRANSACTIONS:
Set Member Amount
EL08 -656 82.00
M0'8"1�56 597.50
TOTAL: 679.50
TRANSACTION LIST:
Type Method Description
ACCOUNT ITEM LIST:
Description
ELECTRICAL PERMIT - NONR
MECHANICAL - NONRES
PLAN CHECK - NONRES
SET RECEIPT
Total Payment: 679.50
Amount
Payment Check 003111 679.50
TOTAL: 679.50
Account Code Current Pmts
000.322.101.00.0 82.00
000.322.102.00.0 478.00
000/345.830 119.50
TOTAL: 679.50
3023 05/30 9711 TOTAL 679.50
Proje
Type of Inspection:
Address:
/
.5 ..4 v5
Date Called:
Special Instructions:
/
Date Wanted:
&°
Requester:
Phone No / :
2-* ".
6 "7i ' - .3 . a 9'
6 (
7 INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION '-
6300 Blvd., #100, Tukwila, WA 98188 (206)431 =3 7
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
r
1
el M'r L,D it-/1 p i
f
k „1/
❑ $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Date:
24 or
Receipt No.:
!Date:
Project
S W\ i le S
Type of Inspection: �--
Semo tc s,k 1
- ``
J
Address:
Date Called:
Special I structions:
lS 5 A y
5t4 ✓t'1
/xi i X
Date nted: r
-2- -oe,
a.m`'
p
Requester:
C rvrC-P
Phone No:
UC, -76 3 171-0_
2
35
.2-
INSPECTION RECORD
Retain a copy with permit
DE -15 (00 -
PERMIT NO.
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd:, #100, Tukwila, WA 98188 (206'431 -36
LI $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
COMMENTS:
Inspector: -
imAktA
Date: - -� -v ‘
Receipt No.:
'Date:
IA
Approved per applicable codes. 0 Corrections required prior to approval.
efi
Project
S rv1 ! ! -c.
Type of Inection:
1- 1,..)/1
Address:
Date Called:
Special InsZuc ony
LIZ
v C
Date W� a�nted:
— I Z Z -
a.m.
p .m.
Requester:
Phone G -7
-3 r Z 8
�
t'
inA 0 e
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION I'
6300 Southcenter Blvd.; #100, Tukwila, WA 98188 (206)431 -3
Approved per applicable codes.
Corrections require prior to approval.
COMMENTS:
fr
i
Inspec br:
Date:
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100'. Call to schedule reinspection:
Receipt No.:
= Date:
Project: e
Type of : ; P
A
Address:
1547-r 5VA0E So .
Date Called:
Special Instructions:
•
Date Wanted:
7 -15 -4
-�C a.
p.m. m.
Requester:
Phone No:
7/ — (P I N — 31 ff 7--
Aitoi _1
INSPECTION RECORD
Retain a copy with permit
INSPE I ON NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcente;' BIVd., #100, Tukwila, WA 98188 (206)431 -3670
Approved per applicable codes. El Corrections required prior to approval.
COMMENTS:
Pk- 'ID (A;4<
A
(Inspect
Date:
I
El $60.00 REINSPECTION FEE EMUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
(Receipt No.:
Date:
Project: „S. , 1.G
Sprinklers:
Fire Alarm:
Type of Inspection: 1�
�.1) A4e, .517_ .s4.�' Oe. , ✓/ 7
Address: /5 2 s
Suite #:
,c3 4v,
s .
Contact Person:
Special Instructions:
Phone No.:
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre - Fire:
Permits:
Occupancy Type:
INSPECTION NUMBER
( 'Approved per applicable codes.
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA FIRE DEPARTMENT
Date: 9 / `/
Word /Inspection Record Form. Doc 1/13/06
e City of Tukwila Finance Department. Call to schedule a reinspection.
re) 67,9 _ j s c`;
PERMIT NUMBERS
444 Andover Park East, Tukwila, Wa. 98188 206 - 575 -4407
Corrections required prior to approval.
COMMENTS:
�-- )-e 1 e & - 'v a v IGe..- ive4 ..'
Inspector:
Hrs.:
$80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
T.F.D. Form F.P. 113
CT
E N G I N E E R I N G
May 28, 2008
Jason Stanton
Evergreen Refrigeration
727 South Kenyon St
Seattle, WA 98108
Dear Jason,
Yours truly,
Rick Hudson, P.E.
Structural Engineers
INC
Re: Two Replacement HVAC at Smile Building
15425 53 Ave S.
Tukwila, Washington
ALE C% Y
Permit No. ,
crirrnf
I have reviewed the support of two new roof top HVAC unit that replaces existing units and
find that it may be supported on the existing roof structure according to the attached detail.
Please contact me if there are any further questions about this matter.
— REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUN - 6 2008
Of Tukwila
IN D . I 9N
180 Nickerson St.
Suite 302
Seattle, WA 98109
(206) 285-4512(V)
(206) 285- 0618(F)
CITY OF TU�LA
MAY 2 9IUUd
PERMIT CENTER
AO is 166
Project:
5 witU_ z PLLC ��
54.00 - 15Lt25 5 32 'V
D , S - Tuk- w /ck
Ev 2.EEI\ (L 1 bag. 4 - n0 nJ
Structural Engineers
3 ?
Client: Page Number:
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285 -4512
FAX:
(206) 285-0618
Project:
Client:
goof! N
Er i
I y 4 25
Structural Engineers
Sw►I1,2s c . - 53 r (A
vetZc.2jLfm ,Q. i -16 E/Zb'9
/ L
► toTo 4(G
NE/A) 4xfa
IA)) Lu544 ti
N ?rpiL 'Dr )
�X t Sr i 1"12 -u Ss 2f
vs) 2x(. — r 4't ct-o -nS
T'10
4/
.4 12- rEK. 5CO- -
I a
p -�rEre n►9r"1�-
1 .0 GA 4
celt5
Date: cl za tog
Page Number: 5
P t U kl iT
7-07 1
e. 2 5 10 0() r m ;c.
+,AL
EXPiRc3 5/12/
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
FAX:
(206) 285-0618
:N G E R-I N
Project: 154 Z S J r& Q L L
Client:
�v� v Re grt rcuh, tN✓
P•P(( 2,
• . PLYwr) 2,2
'17ws5 , 2 , 5
PI24N►_ 2L
G L(2
,3 r5.
Structural Engineers
.080 (s,
a
4 mwo ti 0.vuc ci
ST,
. ..fr *2 2095 tvhS
« } y fi e. - , -
S vh l 64 14
re gae.. e
4
3 1,3(0 + 4'(a
tK In
S2Fjx
o) ► I S
5' z 210,222.
Page Number: CA-LC, I
Date:
J - 64a o
• V1/1154... 91)
�
Y-(0 T t3 2 z
5 30v& L - 4a (3 he c
31,3 6 IL- z
11'6. ,1'O Z.
Lr eip
Vv\- •c7i (“;s\- a1 3
M #r . = 3 2 , 8
C+= , 8 < • 102
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
FAX:
(206) 285-0618
s e.
/ Gf
1, 15 x 1.3= 1 1a 1 .-
L d era i� �✓
Cooling Equipment Schedule
Equip.
ID
Brand Name'
Model No.'
Capacity
Btu/h
Total CFM
OSA CFM
or Econo?
SEER
or EER
IPLV
Location
RTU -1
CARRIER
50HJ0007 -5
76000
2400
480
10.5 eer
ROOF
I
r
milamail
immasm■f
Tram
ffd!i Ii i
• 1 iia r
Mr
_
Fan Equipment Sche . fll
Equip.
ID
Brand Name'
Model No.'
CFM
Sp'
HP /BHP
Flow Control Location of Service
EF -1 -5
BROAN
QTR110
90
0.20
71 WATTS
CEILING
EF -6
GREENHECK
G -080 -D
300
0.25"
SPRINKLER ROOM
EF -7
Project Info
Project Address
Smiles
Date 5/29/2008
Total CFM
15425 53rd Ave South
For Building Dept. Use
Output Btuh
Tukwila, WA
Applicant Name:
Evergreen Refrigeration
Applicant Address:
727 S Kenyon St.
Applicant Phone:
206- 763 -1744
Heating Equipment Schedule
Equip.
ID
Brand �!• '
Capacity
Btu/h
Total CFM
OSA cfm
or Econo?
Input Btuh
Output Btuh
Efficiency
RTU -1
CARRIER � -0•• • l ;.- W
. 121500
2400
480
N/A
69000
80.000
LLr�r'' _ '
I
r
milamail
immasm■f
Tram
ffd!i Ii i
• 1 iia r
Mr
_
Fan Equipment Sche . fll
Equip.
ID
Brand Name'
Model No.'
CFM
Sp'
HP /BHP
Flow Control Location of Service
EF -1 -5
BROAN
QTR110
90
0.20
71 WATTS
CEILING
EF -6
GREENHECK
G -080 -D
300
0.25"
SPRINKLER ROOM
EF -7
BROAN
L400
434
0.36"
LOUNGE
ij
Mechanical Summary
MEC;H;SUM
2006 Washington State Nonresidential Energy Code Compliance Forms
Project Description
Briefly describe mechanical
system type and features.
❑ Includes Plans
Compliance Option
2006 Washington State Nonresidential Energy Code Compliance Form
Install (2) rooftop heat pumps units, (7) exhasut fans
Include documentation requiring compliance with com Issioning eq r ments, Section 1416.
ork
Simple System 0 Complex System 0 Systems Analysis
FILE COPY
Revised July 2007
- ..t.•.- . ' r - r •..r+•^. nVol S t~
(See Decision Flowchart (over) for qualifications. Use separate MECH -SUM for simple & complex sydterne.
Equipment Schedules
•
The following information is required to be incorporated with the mechanical equipment schedules on the''
plans. For projects without plans, fill in the required information below.
'If available. 2 As tested according to Table 14-1A through 14-1G. 3 If required. " COP, FTSPF Combustion Efficiency, or AFUE, as
applicable. 5 Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS).
II avaliavic. .,a icaicu MAAJ18109c1A StRig. M40 rwi i ° "1i9F„nPtr1/49." r . ". 4 .°..Y - , T J ?,lie.. sespoi. u, P I VI-, a0
applicable. 5 Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS).
System Description
See Section 1421 for full description
of Simple System qualifications.
If Heating/Cooling
or Cooling Only:
❑ Constant vol?
❑ Split system?
❑ Air cooled? ✓ Packaged sys? ❑ <20,000 Btuh?
❑ Economizer included?
If Heating Only:
9 Y
❑ <5000 cfm?
❑ <70 /o outside air?
<70%
Heating Only
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Summary (back)
MECH -SUM
Decision Flowchart
Use this flowchart to determine if project qualifies for Simple System Option. If not, either the
Complex System or Systems Analysis Options must be used.
Simple System
Allowed
(section 1420)
( Reference
Section 1421
otal Ca..
wo economize
<240,000 Btuh
or 10 %?
Heating/Cooling
or Cooling Only
Reference
Section 1423
Use Complex
Systems
(section 1430)
Complex Systems
Refer to MECH -COMP Mechanical Complex Systems for assistance in determining which
Complex Systems requirements are applicable to this project.
Mechanical
2006 Washington State
Permit
Nonresidential
Plans Checklist MEC,H ;CHK
Energy Code Compliance Forms Revised July 2007
Project Address Smiles 'Date
5/29/2008
The following information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the
Washington State Nonresidential Energy Code.
Applicability
(yes, no, n.a.)
Code
Section
Component
Information Required
Location
on Plans
Building Department
Notes
HVAC REQUIREMENTS (Sections 1401 -1424)
1411
Equipment performance
1411.4
Pkg. elec. htg.& clg.
List heat pumps on schedule
1411.1
Minimum efficiency
Equipment schedule with type, capacity, efficiency
Mi
1411.1
Combustion htg.
Indicate intermittent ignition, flue/draft damper & jacket loss
1412
HVAC controls
1412.1
Temperature zones
Indicate locations on plans
Ml,
1412.2
Deadband control
Indicate 5 degree deadband minimum
Ml
1412.3
Humidity control
Indicate humidistat
1412.4
Automatic setback
Indicate thermostat with night setback and 7 diff. day types
Ml
1412.4.1
Dampers
Indicate damper location and auto. controls & max. leakage
Ml
1412.4.2
Optimum Start
Indicate optimum start controls
1412.5
Heat pump control
Indicate microprocessor on thermostat schedule
1412.6
Combustion htg.
Indicate modulating or staged control
1412.7
Balancing
Indicate balancing features on plans
Ml
1412.8
Ventilation Control
Indicate demand control ventilation for high - occupancy areas
1422
Thermostat interlock
Indicate thermostat interlock on plans
1423
Economizers
Equipment schedule
1413
Air economizers
1413.1
Air Econo Operation
Indicate 100% capability on schedule
1413.1
Wtr Econo Operation
Indicate 100% capacity at 45 degF db & 40 deg F wb
1413.2
Water Econo Doc
Indicate clg load & water econoe & clg tower performance
1413.3
Integrated operation
Indicate capability for partial cooling
1413.4
Humidification Indicate direct evap or fog atomization w/ air economizer
1414
Ducting systems
1414.1
Duct sealing
Indicate sealing necessary
Ml.
1414.2
Duct insulation
Indicate R -value of insulation on duct
Ml.
1415.1
Piping insulation
Indicate R -value of insulation on piping
1416
Completion Requirements
1416.2.1
Commissioning
Provide commissioning plan
1416.2.2 -3
Sys.Bal & Func.Test
Indicate air and water system balancing & functional testing
1416.2.4
Commissioning
Indicate O &M manuals, record drawings, staff training
1416.2.5
Comm. Report
Indicate requirements for prelim. & final commissioning report
Ml
1434
Separate air sys.
Indicate separate systems on plans
Mechanical
Summary Form
Completed and attached. Equipment schedule with types,
input/output, efficiency, cfm, hp, economizer
Mi
SERVICE WATER HEATING AND HEATED POOLS (Sections 1440 -1454)
1440
Service water htg.
1441
Elec. water heater
Indicate R -10 insulation under tank
1442
Shut -off controls
Indicate automatic shut -off
1443
Pipe Insulation
Indicate R -value of insulation on piping
1452
Heat Pump COP
Indicate minimum COP of 4.0
1452
Heater Efficiency
Indicate pool heater efficiency
1453
Pool heater controls
Indicate switch and 65 degree control
1454
Pool covers
Indicate vapor retardant cover
1454
Pools 90+ degrees
Indicate R -12 pool cover
2006 Washington State Nonresidential Energy Code Compliance Form
2006 Washington State Nonresidential Energy Code Compliance Form
If "no" is circled for any question, provide explanation:
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Permit Plans Checklist
MEC;H -CHK
2006 Washington State Nonresidential Energy Code Compliance Forms
Revised July 2007
Mechanical - General Requirements
1411.1 General: Equipment shall have a minimum performance at the specified
rating conditions not less than the values shown in Table 14 -1A through 14 -1G. If a
nationally recognized certification program exists for a product covered in Tables
14 -1A through 14-1G, and it includes provisions for verification and challenge of
equipment efficiency ratings, then the product shall be listed in the certification
program.
Gas -fired and oil -fired forced air furnaces with input ratings > 225,000 Btu/h (65
kW) and all unit heaters shall also have an intermittent ignition or interrupted device
(IID), and have either mechanical draft (including power venting) or a flue damper. A
vent damper is an acceptable alternative to a flue damper for furnaces where
combustion air is drawn from the conditioned space. All furnaces with input ratings >
225,000 Btu/h (65 kW), including electric furnaces, that are not located within the
conditioned space shall have jacket losses not exceeding 0.75% of the input rating.
1411.2 Rating Conditions: Cooling equipment shall be rated at ARI test conditions
and procedures when available. Where no applicable procedures exist, data shall
be furnished by the equipment manufacturer.
1411.3 Combination Space and Service Water Heating: For combination space
and service water heaters with a principal function of providing space heat, the
Combined Annual Efficiency (CAE) may be calculated by using ASHRAE Standard
124 -1991. Storage water heaters used in combination space heat and water heat
applications shall have either an Energy FActor (EF) or a CAE of not less than the
following:
1411.4 Packaged Electric Heating and Cooling Equipment: Packaged electric
equipment providing both heating and cooling with a total cooling capacity greater
than 20, Btu /h shall be a heat pump.
Exception: Unstaffed equipment shaelters or cabinets used solely for
personal wireless service facilities.
1412 Controls
1412.1 Temperature Controls: Each system shall be provided with at least one
temperature control device. Each zone shall be controlled by individual thermostatic
controls responding to temperature within the zone. At a minimum, each floor of a
building shall be considered as a separate zone.
1412.2 Deadband Controls: When used to control both comfort heating and
cooling, zone thermostatic controls shall be capable of a deadband of at least 5
degrees F within which the supply of heating and cooling energy to the zone is shut
off or reduced to a minimum.
Exceptions:
1. Special occupancy, special usage, or code requirements where
deadband controls are not appropriate.
2. Buildings complying with Section 1141.4, if in the proposed building
energy analysis, heating and cooling thermostat setpoints are set to
the same temperature between 70 degrees F and 75 degrees F
inclusive, and assumed to be constant throughout the year.
3. Thermostats that require manual changeover between heating and
cooling modes.
1412.3 Humidity Controls: If a system is equipped with a means for adding
moisture, a humidistat shall be provided.
1412.4 Setback and Shut -Off: HVAC systems shall be equipped with automatic
controls capable of accomplishing a reduction of energy use through control setback
or equipment shutdown during periods of non -use or alternate use of the spaces
served by the system. The automatic controls shall have a minimum seven -day
clock and be capable of being set for seven different day types per week. It must
retain programming and time for a power loss of 10 hours and include an accessible
manual override of up to 2 hours.
Exceptions:
1. Systems serving areas which require continuous operation at the
same temperature setpoint.
2. Equipment with full load demands of 2 kW (6,826 Btu/h) or less may
be controlled by readily accessible manual off -hour controls.
3. Systems controlled by an occupant sensor that is capable of shutting
the system off when no occupant is sensed for a period of up to 30
minutes.
4. Systems controlled solely by a manually operated timer capable of
operating the system for no more than two hours.
1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets serving
conditioned spaces shall be equipped with dampers which close automatically when
the system is off or upon power failure. Stair shaft and elevator shaft smoke relief
openings shall be equipped with normally open (fails to open upon loss of power)
dampers. These dampers shall remain closed until activated by the fire alarm
system or other approved smoke detection system.
Exceptions:
1. Systems serving areas which require continuous operation.
2. Combustion air intakes.
3. Gravity (nonmotorized) dampers are acceptable in buildings less
than 3 stories in height.
4. Gravity (nonmotorized) dampers are acceptable in exhaust and relief
outlets in the first story and levels below the first story of buildings
1412.8 Ventilation Controls for High - Occupancy Areas: Demand control
ventilation (DCV) is required for spaces that are larger than 500 ft2, have a design
occupancy for ventilation of greater than 40 people for 1000 ft2 of floor area, and are
served by systems with one or more of the following:
a. An air -side economizer,
b. Automatic modulating control of the outdoor air damper, or
c. A design outdoor airflow greater than 3000 cfm.
Exceptions:
1.Systems with energy recovery complying with Section 1436.
2. Multiple -zone systems without direct - digital control of individual zones
communicating with a central control panel.
3. Systems with a design outdoor airflow less than 1200 cfm.
4. Spaces where the supply airflow rate minus any makeup or outgoing
transfer air requirement is less than 1200 cfm.
1413 Air Economizers
1413.1 Operation: Air economizers shall be of automatically modulating outside and
return air dampers to provide 100 percent of the design supply air as outside air to
reduce or eliminate the need for mechanical cooling. Water economizers shall be
capable of providing the total concurrent cooling load served by the conneted
terminal equipment lacking airside economizer, at outside air temperatures of 45 ° F
dry- bulb /40 ° F wet -bulb and below. For this calculation, all factors including solar and
internal load shall be the same as those used for peak load calculations, except for
the outside temperatures.
Exception: Water economizers using air - cooled heat rejection equipment
may use a 35 ° F dry-bulb outside air temperature for this calculation. This
exception is limited to a maximum of 20 tons per building.
1413.2 Documentation: Water economizer plans submitted for approval shall
include the following information:
1. Maximum outside air conditions for which economizer is sized to provide
full cooling.
2. Design cooling load to be provided by economizer at this outside air
condition.
3. Heat rejection and terminal equipment performance data including model
number, flow rate, capacity, entering and leaving temperature in full
economizer cooling mode.
1413.3 Integrated Operation: Air economizers shall be capable of providing partial
cooling even when additional mechanical cooling is required to meet the remainder
of the cooling load.
Exceptions:
1. Individual, direct expansion units that have a rated capacity less than
65,000 Btu/h and use nonintegrated economizer controls that
preclude simultaneous operation of the economizer and mechanical
cooling.
2. Water cooled water chillers with waterside economizer.
1413.4 Humidification: If an air economizer is required on a cooling system for
which humidification equipment is to be provided to maintain minimum indoor
humidity levels, then the humidifier shall be of the adiabatic type (direct evaporative
media or fog atomization type).
Exceptions:
1. Health care facilities where WAC 246- 320 -525 allows only steam
injection humidifiers in ductwork downstream of final filters. 1412.6
Combustion Heating Equipment Controls: Combustion heating
equipment with a capacity over 225,000 Btu/h shall have modulating
or staged combustion control.
2. Systems with water economizer
3. 100% outside air systems with no provisions for air recirculation to the
central supply fan.
4. Nonadiabatic humidifiers cumulatively serving no more than 10% of a
building's air economizer capacity as measured in cfm. This refers to
the system cfm serving rooms with stand alone or duct mounted
humidifiers.
1414 Ducting Systems
1414.1 Sealing: Duct work which is designed to operate at pressures above 1/2 inch
water column static pressure shall be sealed in accordance with Standard RS -18.
Extent of sealing required is as follows:
1. Static pressure: 1/2 inch to 2 inches; seal transverse joints.
2. Static pressure: 2 inches to 3 inches; seal all transverse joints and
longitudinal seams.
3. Static pressure: above 3 inches; seal all transverse joints, longitudinal
seams and duct wall penetrations.
Duct tape and other pressure sensitive tape shall not be used as the primary
sealant where ducts are designed to operate at static pressures of 1 inch W.C. or
greater.
1414.2 insulation: Ducts and plenums that are constructed and function as part of
the building envelope, by separating interior space from exterior space, shall meet all
applicable requirements of Chapter 13. These requirements include insulation
installation, moisture control, air leakage, and building envelope insulation levels.
Unheated equipment rooms with combustion air louvers must be isolated from the
conditioned space by insulating interior surfaces to a minimum of R -11 and any
exterior envelope surfaces per Chapter 13. Outside air ducts serving individual
supply air units with less than 2,800 cfm of total supply air capacity shall be insulated
to a minimum of R -7 and are not considered building envelope. Other outside air
duct runs are considered building envelope until they,
EF
CAE
< 50 gal storage
0.58
0.71
50 to 70 gal storage
0.57
0.71
> 70 gal storage
0.55
0.70
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Permit Plans Checklist
MEC;H -CHK
2006 Washington State Nonresidential Energy Code Compliance Forms
Revised July 2007
Mechanical - General Requirements
1411.1 General: Equipment shall have a minimum performance at the specified
rating conditions not less than the values shown in Table 14 -1A through 14 -1G. If a
nationally recognized certification program exists for a product covered in Tables
14 -1A through 14-1G, and it includes provisions for verification and challenge of
equipment efficiency ratings, then the product shall be listed in the certification
program.
Gas -fired and oil -fired forced air furnaces with input ratings > 225,000 Btu/h (65
kW) and all unit heaters shall also have an intermittent ignition or interrupted device
(IID), and have either mechanical draft (including power venting) or a flue damper. A
vent damper is an acceptable alternative to a flue damper for furnaces where
combustion air is drawn from the conditioned space. All furnaces with input ratings >
225,000 Btu/h (65 kW), including electric furnaces, that are not located within the
conditioned space shall have jacket losses not exceeding 0.75% of the input rating.
1411.2 Rating Conditions: Cooling equipment shall be rated at ARI test conditions
and procedures when available. Where no applicable procedures exist, data shall
be furnished by the equipment manufacturer.
1411.3 Combination Space and Service Water Heating: For combination space
and service water heaters with a principal function of providing space heat, the
Combined Annual Efficiency (CAE) may be calculated by using ASHRAE Standard
124 -1991. Storage water heaters used in combination space heat and water heat
applications shall have either an Energy FActor (EF) or a CAE of not less than the
following:
1411.4 Packaged Electric Heating and Cooling Equipment: Packaged electric
equipment providing both heating and cooling with a total cooling capacity greater
than 20, Btu /h shall be a heat pump.
Exception: Unstaffed equipment shaelters or cabinets used solely for
personal wireless service facilities.
1412 Controls
1412.1 Temperature Controls: Each system shall be provided with at least one
temperature control device. Each zone shall be controlled by individual thermostatic
controls responding to temperature within the zone. At a minimum, each floor of a
building shall be considered as a separate zone.
1412.2 Deadband Controls: When used to control both comfort heating and
cooling, zone thermostatic controls shall be capable of a deadband of at least 5
degrees F within which the supply of heating and cooling energy to the zone is shut
off or reduced to a minimum.
Exceptions:
1. Special occupancy, special usage, or code requirements where
deadband controls are not appropriate.
2. Buildings complying with Section 1141.4, if in the proposed building
energy analysis, heating and cooling thermostat setpoints are set to
the same temperature between 70 degrees F and 75 degrees F
inclusive, and assumed to be constant throughout the year.
3. Thermostats that require manual changeover between heating and
cooling modes.
1412.3 Humidity Controls: If a system is equipped with a means for adding
moisture, a humidistat shall be provided.
1412.4 Setback and Shut -Off: HVAC systems shall be equipped with automatic
controls capable of accomplishing a reduction of energy use through control setback
or equipment shutdown during periods of non -use or alternate use of the spaces
served by the system. The automatic controls shall have a minimum seven -day
clock and be capable of being set for seven different day types per week. It must
retain programming and time for a power loss of 10 hours and include an accessible
manual override of up to 2 hours.
Exceptions:
1. Systems serving areas which require continuous operation at the
same temperature setpoint.
2. Equipment with full load demands of 2 kW (6,826 Btu/h) or less may
be controlled by readily accessible manual off -hour controls.
3. Systems controlled by an occupant sensor that is capable of shutting
the system off when no occupant is sensed for a period of up to 30
minutes.
4. Systems controlled solely by a manually operated timer capable of
operating the system for no more than two hours.
1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets serving
conditioned spaces shall be equipped with dampers which close automatically when
the system is off or upon power failure. Stair shaft and elevator shaft smoke relief
openings shall be equipped with normally open (fails to open upon loss of power)
dampers. These dampers shall remain closed until activated by the fire alarm
system or other approved smoke detection system.
Exceptions:
1. Systems serving areas which require continuous operation.
2. Combustion air intakes.
3. Gravity (nonmotorized) dampers are acceptable in buildings less
than 3 stories in height.
4. Gravity (nonmotorized) dampers are acceptable in exhaust and relief
outlets in the first story and levels below the first story of buildings
1412.8 Ventilation Controls for High - Occupancy Areas: Demand control
ventilation (DCV) is required for spaces that are larger than 500 ft2, have a design
occupancy for ventilation of greater than 40 people for 1000 ft2 of floor area, and are
served by systems with one or more of the following:
a. An air -side economizer,
b. Automatic modulating control of the outdoor air damper, or
c. A design outdoor airflow greater than 3000 cfm.
Exceptions:
1.Systems with energy recovery complying with Section 1436.
2. Multiple -zone systems without direct - digital control of individual zones
communicating with a central control panel.
3. Systems with a design outdoor airflow less than 1200 cfm.
4. Spaces where the supply airflow rate minus any makeup or outgoing
transfer air requirement is less than 1200 cfm.
1413 Air Economizers
1413.1 Operation: Air economizers shall be of automatically modulating outside and
return air dampers to provide 100 percent of the design supply air as outside air to
reduce or eliminate the need for mechanical cooling. Water economizers shall be
capable of providing the total concurrent cooling load served by the conneted
terminal equipment lacking airside economizer, at outside air temperatures of 45 ° F
dry- bulb /40 ° F wet -bulb and below. For this calculation, all factors including solar and
internal load shall be the same as those used for peak load calculations, except for
the outside temperatures.
Exception: Water economizers using air - cooled heat rejection equipment
may use a 35 ° F dry-bulb outside air temperature for this calculation. This
exception is limited to a maximum of 20 tons per building.
1413.2 Documentation: Water economizer plans submitted for approval shall
include the following information:
1. Maximum outside air conditions for which economizer is sized to provide
full cooling.
2. Design cooling load to be provided by economizer at this outside air
condition.
3. Heat rejection and terminal equipment performance data including model
number, flow rate, capacity, entering and leaving temperature in full
economizer cooling mode.
1413.3 Integrated Operation: Air economizers shall be capable of providing partial
cooling even when additional mechanical cooling is required to meet the remainder
of the cooling load.
Exceptions:
1. Individual, direct expansion units that have a rated capacity less than
65,000 Btu/h and use nonintegrated economizer controls that
preclude simultaneous operation of the economizer and mechanical
cooling.
2. Water cooled water chillers with waterside economizer.
1413.4 Humidification: If an air economizer is required on a cooling system for
which humidification equipment is to be provided to maintain minimum indoor
humidity levels, then the humidifier shall be of the adiabatic type (direct evaporative
media or fog atomization type).
Exceptions:
1. Health care facilities where WAC 246- 320 -525 allows only steam
injection humidifiers in ductwork downstream of final filters. 1412.6
Combustion Heating Equipment Controls: Combustion heating
equipment with a capacity over 225,000 Btu/h shall have modulating
or staged combustion control.
2. Systems with water economizer
3. 100% outside air systems with no provisions for air recirculation to the
central supply fan.
4. Nonadiabatic humidifiers cumulatively serving no more than 10% of a
building's air economizer capacity as measured in cfm. This refers to
the system cfm serving rooms with stand alone or duct mounted
humidifiers.
1414 Ducting Systems
1414.1 Sealing: Duct work which is designed to operate at pressures above 1/2 inch
water column static pressure shall be sealed in accordance with Standard RS -18.
Extent of sealing required is as follows:
1. Static pressure: 1/2 inch to 2 inches; seal transverse joints.
2. Static pressure: 2 inches to 3 inches; seal all transverse joints and
longitudinal seams.
3. Static pressure: above 3 inches; seal all transverse joints, longitudinal
seams and duct wall penetrations.
Duct tape and other pressure sensitive tape shall not be used as the primary
sealant where ducts are designed to operate at static pressures of 1 inch W.C. or
greater.
1414.2 insulation: Ducts and plenums that are constructed and function as part of
the building envelope, by separating interior space from exterior space, shall meet all
applicable requirements of Chapter 13. These requirements include insulation
installation, moisture control, air leakage, and building envelope insulation levels.
Unheated equipment rooms with combustion air louvers must be isolated from the
conditioned space by insulating interior surfaces to a minimum of R -11 and any
exterior envelope surfaces per Chapter 13. Outside air ducts serving individual
supply air units with less than 2,800 cfm of total supply air capacity shall be insulated
to a minimum of R -7 and are not considered building envelope. Other outside air
duct runs are considered building envelope until they,
cgp, Oft b0090,5tatg,NQ11 ggjOpntiaLEnergy Code Compliance Form. __ _ _
outlets in the first story and levels below the first story of buildings duct runs are considered building envelope until they,
1. connect to the heating or cooling equipment, or
2. are isolated from the exterior with an automatic shut-off damper complying
with Section 1412.4.1.
Once outside air ducts meet the above listed requirements, any runs within
conditioned space shall comply with Table 14 -5 requirements.
Other ducts and plenums shall be thermally insulated per Table 14 -5.
Exceptions:
1. Within the HVAC equipment.
2. Exhaust air ducts not subject to condensation.
3. Exposed ductwork within a zone that serves that zone.
1415 Piping Systems
1415.1 Insulation: Piping shall be thermally insulated in accordance with Table 14 -6.
Exception: Piping installed within unitary HVAC equipment.
Water pipes outside the conditioned space shall be insulated in accordance with
Washington State Plumbing Code (WAC 51 -26)
1416 Completion Requirements (Refer to NREC Section 1416 and the Building
Commissioning Guidelines, published by the Building Commissioning Association,
for complete text and guidelines for building completion and commissioning
requirements.)
three or more stories in height.
1412.4.2 Optimum Start Controls: Heating and cooling systems with design supply
air capacities exceeding 10,000 cfm shall have optimum start controls. Optimum
start controls shall be designed to automatically adjust the start time of an HVAC
system each day to bring the space to desired occupied temperature levels
immediately before scheduled occupancy. The control algorithm shall, as a
minimum, be a function of the difference between space temperature and occupied
setpoint and the amount of time prior to scheduled occupancy.
1412.5 Heat Pump Controls: Unitary air cooled heat pumps shall include
microprocessor controls that minimize supplemental heat usage during start-up, set-
up, and defrost conditions. These controls shall anticipate need for heat and use
compression heating as the first stage of heat. Controls shall indicate when
supplemental heating is being used through visual means (e.g., LED indicators).
1412.6 Combustion Heating Equipment Controls: Combustion heating equipment
with a capacity over 225,000 Btu /h shall have modulating or staged combustion
control. 000
EXCEPTIONS: 1. Boilers. 2. Radiant heaters.
1412.7 Balancing: Each air supply outlet or air or water terminal device shall have
a means for balancing, including but not limited to, dampers, temperature and
pressure test connections and balancing valves.
ACTIVITY NUMBER: M08 -156 DATE: 05 -29 -08
PROJECT"NAME: SMILES AT SOUTHCENTER
SITE ADDRESS: 15425 53 AV S
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # after Permit Issued
DEPARTM NTS:
c 60J-0
Buildi j g r Nis on
n
Public Works
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES/THURS ROU Z ING:
Please Route Structural Review Required
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Documents/routing slip.doc
2 -28 -02
OPERMIT COORD COPY 4111
PLAN REVIEW /ROUTING SLIP
Ono I31A)L ( Alkyl -ob
Fire Prevention
Structural n
Incomplete
DUE DATE: 06-03-08
No further Review Required
DATE:
DUE DATE: 07-01-08
Approved ❑ Approved with Conditions 1 Not Approved (attach comments)
Notation:
REVIEWER'S INITIALS:
DATE:
Planning Division
Permit Coordinator
Not Applicable
n
H
Permit Center Use Only • :
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
•
License Information
License
EVERGRL954R2
Licensee Name
EVERGREEN REFRIGERATION LLC
Licensee Type
CONSTRUCTION CONTRACTOR
UBI
602512953
Ind. Ins. Account Id
42245602
Business Type
LIMITED LIABILITY COMPANY
Address 1
727 S KENYON ST
Address 2
City
SEATTLE
County
KING
State
WA
Zip
98108
Phone
2067631744
Status
ACTIVE
Specialty I
GENERAL
Specialty 2
UNUSED
Effective Date
1/6/2006
Expiration Date
1/6/2010
Suspend Date
Separation Date
Parent Company
Previous License
EVERGI *201 D7
Next License
Associated License
Business Owner Information
Name
Role
Effective
Date
Expiration
Date
EVERGREEN
REFRIGERATION LLC
PARTNER/MEMBER
12/22/2005
PATTON, DAVID
PARTNER/MEMBER
01/06/2006
PATTON, RODGER
PARTNER/MEMBER
01/06/2006
PATTON, MATTHEW
PARTNER/MEMBER
01/06/2006
Look Up a Contractor, Electrician or Plumber License Detail
•
Washington State Department of Labor and Industries
General/Specialty Contractor
A business registered as a construction contractor with L &I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Bond Information
Bond 1 Bond
Company Account Effective
Expiration
Cancel
•
Impaired I Bond Received
Page 1 of 2
https: // fortress .wa.gov /lni/bbip /printer.aspx ?License= EVERGRL954R2 06/18/2008
Mark
SYMBOL
Airflow
(cfm)
Exhaust
Fan
Phase
Schedule
Amps
(A)
DUCT SECTION SUPPLY
Count
-_�-
Remarks
Mani.
Model
S.P.
(in. w.c.)
Volts
(V)
Location
EF -1
Broan
QTR -110
90
0.36"
115
1
0.9
Sterilization
1
1
EF -2
Broan
QTR -110
90
0.36"
115
1
0.9
Lab
1
1
EF -3
Broan
QTR -110
90
0.36"
115
1
0.9
Men's Restroom
1
1
EF-4
Broan
QTR -110
303
0.33"
115
1
2.6
Staff Restroom
1
1
EF -5
Broan
QTR -110
90
0.36"
115
1
0.9
Women's Restroom
1
1
EF-6
Greenheck
G -080 -D
300
0.25"
115
1
-
Sprinkler Room
1
1
EF 7
Remarks:
Broan
L-400
434
0.36"
115
1
1.4
Staff Lounge
1
1
SYMBOL LEGEND
SYMBOL
ABBY,
DESCRIPTION
3
DUCT SECTION SUPPLY
ra
DUCT SECTION - RETURN /EXHAUST
RECTANGULAR DUCT
ROUND DUCT
FLEXIBLE DUCT
L_
MVD
MANUAL VOLUME DAMPER
❑ BDD
BDD
BACKDRAFT DAMPER
M
MD
MOTORIZED DAMPER
ED
FIRE DAMPER
FSD
FIRE /SMOKE DAMPER (I20V POWER REQ.)
CEILING RADIATION DAMPER
SD
SD
SMOKE DETECTOR
:D
T
THERMOSTAT
S
SENSOR
- R
" - -R
R
REFRIGERANT LINES
_ -G
0
NATURAL GAS LINES
- G---
t•1
CEILING DIFFUSER (SUPPLY)
a
CEILING DIFFUSER (RETURN /EXHAUST)
EP
EXHAUST FAN (CEILING MOUNTED)
Ii
Er ill
INLINE FAN
_
PROPELLER FAN CITY OF TUKWILF
MAY
SIDEWALL DIFFUSER 2 9 LUO
I
L
DUCT FITTING PERMIT CEEN
B.D.J. 12' 2'
DATUM
- UNIT TAG 11/111
Q
DUCT RISER V
VICINITY MAP
SCALE : NONE
Mark Manf.
RTU -1
RTU -2
Carrier
Carrier
Model
5OHJQ007 -- -5
5OHJQ007 - -5
1.) Fan to be switched on by others
Tons
(1)
6
Airflow
(cfm)
2400
2400
Min. OSA
(cfm)
S.P.
(in w.c.)
0.5"
Total
(BTU /H)
76,000
.III
Remarks:
1.) The unit comes complete with a factory installed economizer
2.) Provide with 7-day programmable night setback thermostat
3.) Provide with 12 -KW electric heater
4.) Provide with a single poing connection kit
5.) All power wiring and disconnects by electrical contractor
6.) Unit to be equipped with Honeywell VVT system and thermostats in locations as indicated on plans
Rooftop Heat Pump Unit Schedule
Cooling Capacity
SEER
PER 2006 IMC SECTION 606
Install smoke detector to shut down air distribution
by VAV's when the total combined C F M of all
VAV's (to include other tenants) sharing the same
plenum space exceeds 2000 CFM.
(See IMC 606.2.2 for approved method of detection)
EER
10.5
10.5
Mark
L -1
Suite
126
Location
Sprinkler Room
Position
Vertical
Louver Schedule
Airflow
(cam)
375
Flow Type
Intake
Max. Velocity
(fpm)
750
Free Area
(sq. ft.)
0.50
Count
Remarks:
1.) Louver to be furnished and installed by mechanical contractor
2.) Provide louver with barometric relief damper
3.) No information has been given regarding the loads of the room. This louver should be used for budgetary purposes only.
Input
(BTU /H)
69,000
69,000
C.O.P.
3.4
3.40
COMPLETION AND COMMISSIONING FOR
MECHANICAL SYSTEMS
RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE
BUILDING OWNER WITHIN 90 DAYS OF THE DATE OF SYSTEM ACCEPTANCE
PER WA ENERGY CODE (WSEC) SECTION 1416.1.
AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE
BUILDING OWNER PER WSEC SECTION 1416.2.
ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRITTEN BALANCE REPORT SHALL BE
PROVIDED TO THE OWNER PER WSEC SECTION 14516.2.2.2.
FOR WAREHOUSES SEMIHEATED SPACES AND SIMPLE SYSTEMS AS DEFINED IN
2 .
ADJUSTED, SEQUENCES OF OPERATION SHALL BE TESTED TO ENSURE THAT THEY
OPERATE IN ACCORD WITH SPECIFICATIONS AND APPROVED PLANS, AND A COMPLETE
REPORT OF TEST PROCEDURES AND RESULTS SHALL BE FILED WITH THE OWNER
PER WSEC SECTION 1416.4.1.
FOR ALL OTHER SYSTEMS: HVAC CONTROL SYSTEMS SHALL BE TESTED, CALIBRATED
AND ADJUSTED, SEQUENCES OF OPERATION SHALL BE TESTED TO ENSURE THAT THEY
OPERATE IN ACCORD WITH SPECIFICATIONS AND APPROVED PLANS PER WSEC SECTION 1416.2.3.2;
NECESSARY TESTS SHALL BE IDENTIFIED PER WSEC SECTION 1416.2.3;
A PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE
PREPARED PRIOR TO ISSUANCE Of FINAL CERTIFICATE OF OCCUPANCY PER WSEC SECTIOL
1416.2.5.1 AND A COMPLETE FINAL COMMISSIONING REPORT OF TEST
PROCEDURES AND RESULTS SHALL BE FILED WITH THE OWNER PER WSEC SECTION 1416.2.5.2.
Volts
(V)
208
208
SEPARATE PERMIT
REQUIRED FOR:
0 Mechanical
g Electrical
Plumbing
(Wpm Piping
City of Tukwila
BUILDING DIVISION
Phase
3
M.C.A.
(A)
74.5
74.5
Max Fuse
(A)
80
80
Weight
(Ibs)
660
660
REVISIONS
No changes shall be d to the scope
Of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
Remarks
1 , 2, 3, 4, 5
1,2,3,4,5,6
- REVIEWED
CODE COMPLIANCE
APPROVED
JUN - 6 200E
Of Tukwila
IN DWI,I N
FILE C r6F�
Permit No.
Plar review approval is subject to errors and omissions.
Approval of construction documents does not authorize
the violation of any adopted code or ordinance. Receipt
0? approved Fie! Copy d conditions is acicj owtedged:
Id�
By
Date: 8
City of Tukwila
BUILDING DIVISION
GENERAL NOTES
DUCTWORK
1.1 ALL DUCT DIMENSIONS ON PLAN ARE CLEAR INSIDE DIMENSIONS, ADD 2" TO EACH
DIMENSION TO OBTAIN OUTSIDE DIMENSION. ADD 4 "TO EACH DIMENSION IF
DUCTWORK IS ON THE EXTERIOR OF BUILDING.
1.2 THE FIRST NUMBER ON ALL DUCT DIMENSIONS IS THE WIDTH AND THE SECOND
NUMBER IS THE HEIGHT.
1.3 MATERIALS WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME SPREAD RATING
LESS THAN 25 AND A FLAME SMOKE DEVELOPMENT RATING LESS THAN 50, PER
IMC 602.2.1.
1.4 SEAL ALL TRANSVERSE JOINTS FOR DUCTWORK WITH STATIC PRESSURE BETWEEN
1/2 INCHES AND 2 INCHES. DUCTWORK WHICH IS DESIGNED TO OPERATE AT
PRESSURES ABOVE 1/2 INCH WATER COLUMN STATIC PRESSURE SHALL BE SEALED
IN ACCORDANCE WITH STANDARD RS -7.
1.5 ALL DUCT GAUGES PER SMACNA, IMC 603-4.
1.6 ALL DUCT SUPPORTS PER SMACNA, IMC 603 -10.
1.7 ATTACH DIFFUSERS AND GRILLES TO T -BAR GRID PER WA STATE & LOCAL CODES.
1.8 BALANCING DAMPERS ARE TO BE INSTALLED ON ALL BRANCH DUCTS OR DIFFUSERS.
INSULATION
2.1 INSULATE OR LINE DUCTWORK PER WA. STATE ENERGY AND MECHANICAL CODES.
2.2 INSULATE REFRIGERANT & CONDENSATE PIPING PER STATE & LOCAL ENERGY CODES.
GENERAL CONTRACTOR
3.1 GENERAL CONTRACTOR TO PROVIDE AND CUT OPENINGS FOR ALL ROOFTOP,
CEILING, FLOOR, AND WALL PENETRATIONS, INCLUDING WEATHERPROOF SEALING
AND FIRE PROOF LINING PER IMC & IBC.
3.2 GENERAL CONTRACTOR TO VERIFY PENETRATION LOCATION AND DIMENSIONS
WITH ERL BEFORE FRAMING OPENINGS.
3.3 GENERAL CONTRACTOR TO PROVIDE ALL DEMOLITION, PATCHING, AND PAINTING
AS REQUIREED FOR MECHANICAL WORK.
3.4 GENERAL CONTRACTOR TO PROVIDE ADEQUATE STRUCTURAL SUPPORT AS
REQUIRED FOR MECHANICAL WORK.
3.5 GENERAL CONTRACTOR TO PROVIDE ADEQUATE ENGINEERING AS REQUIRED FOR
MECHANICAL WORK.
3.6 GENERAL CONTRACTOR TO PROVIDE SERVICE ACCESS PER CODE TO ALL
MECHANICAL EQUIPMENT.
3.7 GENERAL CONTRACTOR TO LEVEL ALL FACTORY CURBS PROVIDED BY ERL PROVIDE
ALL CANT S " TRIPS AND CURB INSULATION, AND SEAL AGAINST LEAKS.
3.8 GENERAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING OF T -BAR CEILING
AS REQUIRED FOR HVAC INSTALLATION.
3.9 GENERAL CONTRACTOR TO PROTECT ALL OPENINGS THROUGH FLOORS PROVIDED
FOR DUCTWORK INSTALLATION IN ACCORDANCE WITH TABLE 601 OF INTERNATIONAL
BUILDING CODE, WHERE REQUIRED BY SECTION 707 OF IBC.
ELECTRICAL
4.1 ERL TO INSTALL ALL LOW VOLTAGE CONTROL WIRING, CONDUIT WILL BE PROVIDED
BY ELECTRICAL CONTRACTOR.
4.2 ELECTRICAL. CONTRACTOR TO PROVIDE ALL ELECTRICAL CONNECTIONS,
DISCONNECTS, AND STARTERS FOR MECHANICAL EQUIPMENT.
4.3 ELECTRICAL CONTRACTOR TO VERIFY EQUIPMENT SIZES, LOADS AND LOCATIONS
WITH ERL MCHANICAL PLAN AND WITH FIELD CONDITIONS.
4.4 ELECTRICAL.. CONTRACTOR TO INTERLOCK BATHROOM EXHAUST FANS WITH LIGHT
SWITCH.
4.5 ERL TO PROVIDE 7 -DAY NIGHT SETBACK, PROGRAMMABLE TYPE T -STAT WITH
CAPABILITY OF 5 °F DEADBAND.
4.6 ERL TO VERIFY FINAL LOCATION OF THERMOSTAT WITH CUSTOMER.
4.7 ELECTRICAL CONTRACTOR TO PROVIDE ELECTRICAL GCFI OUTLET WITHIN 25 FT
OF EACH PIECE OF MECHANICAL EQUIPMENT.
PLUMBING
5.1 PLUMBING CONTRACTOR TO FURNISH AND INSTALL ALL GAS PIPING FOR
MECHANICAL EQUIPMENT PER CODE.
5.2 PLUMBING CONTRACTOR OFFSET VENTS 10 FEET MINIMUM FROM ALL HVAC FRESH
AIR INTAKES OR 2' ABOVE HIGHEST POINT OF INTAKE, IMC 401.5.1.
5.3 CONDENSATE DRAINS FROM RTU BY ERI TO DRAIN WITHIN 12" OF UNIT.
CONDENSATE DRAINS FOR AIR HANDLERS BY PLUMBER.
ENERGY CODE COMPLIANCE
6.1 AT A MINIMUM, EACH FLOOR IS TO BE CONSIDERED A SEPARATE ZONE. VERIFY
THERMOSTATIC CONTROL FOR EACH ZONE AS INDICATED ON PLANS.
6.2 OUTSIDE AIR : NTAKES, EXHAUST OUTLETS, AND RELIEF OUTLETS SERVING
CONDITIONS ) SPACES SHALL BE EQUIPPED WI`I'rt DAMPERS WHICt I CLOCE
AUTOMATIC,+ .LY WHEN THE SYSTEM IS OFF OR UPON POWER FAILURE,
PER WSEC ;.C. 1412.4.1.
6.3 AIR ECONOMIZERS WHERE REQUIRED BY CODE ARE INDICATED BY THE EQUIPMENT
SCHEDULE A r 100% CAPABILITY, CONTROL AND OPERATION OF THE ECONOMIZER
SHALL COMPLY WITH WSEC SEC. 1423,
MECHANICAL CODE COMPLIANCE
7.1 WHERE REQUIRED PROVIDE AUTOMATIC SHUTOFF ACTIVATED BY SMOKE DETECTORS
IN EACH SYSTEM DELIVERING HEATING OR COOLING AIR IN EXCESS OF 2000 CFM.
DETECTORS SHALL BE LOCATED IN THE MAIN RETURN AIR PER IMC 606.
WA2004 #1
r
Q
Lil
0
co
N
N.
NO
NOT PUBLISHED, ALL RIGHTS RESERVED, THE
DRAWING AND SPECIFICATIONS, IDEAS, DESIGNS
AND ARRANGEMENTS REPRESENTED THEREBY
ARE AND SHALL REMAIN THE PROPERTY OF EVE-
RGREEN REFRIGERATION INC. NO PART THEREOF
SHALL BE REPRODUCED, COPIED, ADAPTED, DISC-
LOSED OR DISTRIBUTED TO OTHERS, SOLD, PUB-
LISHED OR OTHERWISE USED WITHOUT THE PRIOR
WRITTEN CONSENT or AND APPROPRIATE COMPEN-
SATION TO EVERGREEN REFRIGERATION INC. VISUAL
CONTACT WITH THE ABOVE DRAWINGS OR SPECIFIC-
ATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
00
0
(v
w
U)
0
REVISIONS
DATE
DRAWING DATE:
DWG. BY:
CHK. BY:
JOB NO.:
SHEET: I I
DWG. FILE:
(1J I I LLI W
a a a a
JS /JP
GN
80240
E
ITEM
05/22/08
80240M1-
OF 2 SHEETS
O
210 CF
14" -
NAV
Frw
NLCIEPH
1�1
140 CFM
210 CF
200 CF
140
MOUE •
f20 -CFM -_ _._J.
00 CFM
2�.
BYPAS
300 CF
iSiSiSSiSSSi1SSSSiSiiG'S S iSiS°i► SS iS '��:i ® MOWS
EXISTING
SPRINKLER
STERI „
17" 0
--I • T` ON
19
RECEPTION
12 "x12"
STAFF ENTRY 2
(EXISTING)
STAFF ENTRY 3
HVAC FLOOR PLAN
SCALE : 1/4" = 1' -0"
STAFF ENTRY 1
(EXISTING)
9I-1 0"
CODE COMPLIANCE,
APPROVE
JU N • 6 Tai
CM ukwil 1 .
4 , N
(:y)
RECEIVED
CITY OF TUKIMLA
MAY 2 9 2008
PERMIT CENTER
U
4 rN
w
w
w
l
1, .
,,,A., ..
__.
n
sli
4
REVISIONS
NO
DATE
ITEM
O
210 CF
14" -
NAV
Frw
NLCIEPH
1�1
140 CFM
210 CF
200 CF
140
MOUE •
f20 -CFM -_ _._J.
00 CFM
2�.
BYPAS
300 CF
iSiSiSSiSSSi1SSSSiSiiG'S S iSiS°i► SS iS '��:i ® MOWS
EXISTING
SPRINKLER
STERI „
17" 0
--I • T` ON
19
RECEPTION
12 "x12"
STAFF ENTRY 2
(EXISTING)
STAFF ENTRY 3
HVAC FLOOR PLAN
SCALE : 1/4" = 1' -0"
STAFF ENTRY 1
(EXISTING)
9I-1 0"
CODE COMPLIANCE,
APPROVE
JU N • 6 Tai
CM ukwil 1 .
4 , N
(:y)
RECEIVED
CITY OF TUKIMLA
MAY 2 9 2008
PERMIT CENTER
U
4 rN
w
w
w
l
NOT PUBLISHED. ALL RIGHTS RESERVED. THE
DRAWING MID SPECIFICATIONS, IDEAS, DESIGNS
AND ARRANGEMENTS REPRESENTED THEREBY
ARE AND SHALL REMAIN THE PROPERTY OF EVE-
RGREEN REFRIGERATION INC. NO PART THEREOF
SHALL BE REPRODUCED, COPIED, ADAPTED, DISC -
LOSED OR DISTRIBUTED TO OTHERS, SOLD, PUB
LISHED DR OTHERWISE USED WITHOUT THE PRIOR
WRITTEN CONSENT OF AND APPROPRIATE COMPEN-
SATION TO EVERGREEN REFRIGERATION INC. VISUAL
CONTACT WITH THE ABOVE DRAWINGS OR SPECIFIC -
ATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE
OF ACCEPTANCE. OF THESE RESTRICTIONS.
1..1.E
w
H
z
III
REVISIONS
NO
DATE
ITEM
x
11
DRAWING DATE:
05/22/08
11
-
DWG. BY:
JS JP
CHK. BY:
GN
JOB NO.:
80240
DWG. FILE:
50240M2—
SHEET:
M 2
2 0F2 SHEETS
O
210 CF
14" -
NAV
Frw
NLCIEPH
1�1
140 CFM
210 CF
200 CF
140
MOUE •
f20 -CFM -_ _._J.
00 CFM
2�.
BYPAS
300 CF
iSiSiSSiSSSi1SSSSiSiiG'S S iSiS°i► SS iS '��:i ® MOWS
EXISTING
SPRINKLER
STERI „
17" 0
--I • T` ON
19
RECEPTION
12 "x12"
STAFF ENTRY 2
(EXISTING)
STAFF ENTRY 3
HVAC FLOOR PLAN
SCALE : 1/4" = 1' -0"
STAFF ENTRY 1
(EXISTING)
9I-1 0"
CODE COMPLIANCE,
APPROVE
JU N • 6 Tai
CM ukwil 1 .
4 , N
(:y)
RECEIVED
CITY OF TUKIMLA
MAY 2 9 2008
PERMIT CENTER
U
4 rN
w
w
w
l