HomeMy WebLinkAboutPermit M08-190 - BANK OF AMERICABANK OF AMERICA 320 STRANDER BL M08 -190 Parcel No.: 6364200010 Address: Suite No: Tenant: Name: Address: Owner: Name: Address: 320 STRANDER BL TUKW CitAf Tukwila BANK OF AMERICA 320 STRANDER BL , TUKWILA WA WESTFIELD PROPERTY TAX DEPT PO BOX 130940 , CARLSBAD CA Contact Person: Name: BRIAN VAN STIPDONK Address: 1200 6 AV, STE 500 , SEATTLE WA Value of Mechanical: 155,900.00 Type of Fire Protection: Furnace: <100K BTU 0 >100K BTU 0 Floor Furnace 0 Suspended/Wall/Floor Mounted Heater 0 Appliance Vent 0 Repair or Addition to Heat/Refrig /Cooling System.... 0 Air Handling Unit <10,000 CFM 5 >10,000 CFM 0 Evaporator Cooler 0 Ventilation Fan connected to single duct 1 Ventilation System 0 Hood and Duct 0 Incinerator: Domestic 0 Commercial/Industrial 0 doc: IMC -10/06 Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 - 431 -3670 Fax: 206 - 431 -3665 Web site: http://www.ci.tuicwila.wa.us Contractor: Name: OKITSU CONSTRUCTION INC. Address: 1428 WHITWORTH AV S , RENTON WA Contractor License No: OKITSCI959L8 MECHANICAL PERMIT EQUIPMENT TYPE AND OUANTITY * * continued on next page ** M08 -190 Permit Number: Issue Date: Permit Expires On: Phone: Phone: 206 654 -2129 Phone: 206 714 -9969 Expiration Date: 06/28/2009 DESCRIPTION OF WORK: MECHANICAL FOR NEW STAND ALONE BUILDING: PACKAGED ROOFTOP UNITS WITH GAS HEAT. EACH UNIT WILL INCLUDE SUPPLY FAN, GAS FURNACE, DIRECT EXPANSION (DX), COOLING COIL, MERV 8 FILTERS, AND FULL AIR -SIDE ECONOMIZER. M08 -190 12/09/2008 06/07/2009 Fees Collected: $1,726.25 International Mechanical Code Edition: 2006 Boiler Compressor: 0 -3 HP /100,000 BTU 0 3 -15 HP /500,000 BTU 0 15 -30 HP /1,000,000 BTU.. 0 30 -50 HP /1,750,000 BTU.. 0 50+ HP /1,750,000 BTU 0 Fire Damper 0 Diffuser 0 Thermostat 5 Wood/Gas Stove 0 Water Heater 0 Emergency Generator 0 Other Mechanical Equipment Printed: 12 -09 -2008 Permit Center Authorized Signature: doc: IMC -10/06 • City of Tukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 - 431 -3670 Fax: 206 - 431 -3665 Web site: http: / /www.ci.tukwila.wa.us Permit Number: M08 -190 Issue Date: 12/09/2008 Permit Expires On: 06/07/2009 Date: () 'V 0 I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances governing this work will be complied with, whether specified herein or not. The granting of this permi does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating construction or the perfo ance / f work. I am authorized to sign and obtain this mechanical permit. Signature: 0 Date: 1 / 61 - 9- Print Name: This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended or abandoned for a period of 180 days from the last inspection. M08 -190 Printed: 12 -09 -2008 Parcel No.: 6364200010 Address: Suite No: Tenant: doc: Cond -10/06 BANK OF AMERICA 1: ** *BUILDING DEPARTMENT CONDITIONS * ** 11: ** *FIRE DEPARTMENT CONDITIONS * ** City of Tukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 - 431 -3670 Fax: 206 - 431 -3665 Web site: http: / /www.ci.tukwila.wa.us 320 STRANDER BL TUKW PERMIT CONDITIONS Permit Number: Status: Applied Date: Issue Date: M08 -190 ISSUED 07/18/2008 12/09/2008 2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the Building Official. 3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center (206/431- 3670). 4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to start of any construction. These documents shall be maintained and made available until final inspection approval is granted. 5: Readily accessible access to roof mounted equipment is required. 6: All construction shall be done in conformance with the approved plans and the requirements of the International Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code. 7: Manufacturers installation instructions shall be available on the job site at the time of inspection. 8: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the Cityof Tukwila Permit Center. 9: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building Department (206- 431 - 3670). 10: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the Building Official from requiring the correction of errors in the construction documents and other data. 12: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051) 13: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the manufacturer's installation instructions. (IMC 606.1, 606.2.1) 14: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051) 15: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051) M08 -190 Printed: 12 -09 -2008 doc: Cond -10/06 • City of Tukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 - 431 -3670 Fax: 206 - 431 -3665 Web site: http: / /www.ci.tukwila.wa.us 17: Local U.L. central station supervision is required. (City Ordinance #2051) * * continued on next page ** 16: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC 104.2) 18: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and #2051) 19: All electrical work and equipment shall conform strictly to the standards of the National Electrical Code. (NFPA 70) 20: This review limited to speculative tenant space only - special fire permits may be necessary depending on detailed description of intended use. 21: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of such condition or violation. 22: These plans were reviewed by Inspector 0700. If you have any questions, please call Tukwila Fire Prevention Bureau at (206)575 -4407. M08 -190 Printed: 12 -09 -2008 Signature: Print Name: doc: Cond -10/06 4 00 9 .A e y • City of Tukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 - 431 -3670 Fax: 206 - 431 -3665 Web site: http: / /www.ci.tukwila.wa.us I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing this work will be complied with, whether specified herein or not. The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating construction or the performance of work. Date: / 4 q - q8 M08 -190 Printed: 12 -09 -2008 SITE LOCATION ! Site Address: Tenant Name: Property Owners Name: Mailing Address: g CITY OF TUKWILA Community Development Department Permit Center 6300 caL;thcenter Blvd., Suite 100 Tukwila, WA 98188 i'ato:.Ywww el, tukwilawa.24 r cp,NTACT,PERSON --iiho do4e ctin6ct %s:lien .oar erieli • " d r 6' • . - •-• • t .4 - ' • - '''''''. '''' 1 ...„:,:. ,. ...,,„..,, .., .:.., . _:. 0:. p S I ey. o be Issud.t . .. .4... . . r p.. . .. r .,. . .., .'. . , , - . ' -.: • ' . .-. .. , !:P ' - u.... Name: 3(11 4, pel ie Day Telephone: 2_04 (Tft Zi Z.1 Mailing Address: t2;.)0 41/ AVC .,/i 4 ,<, 5 el 4-t k t..,A ; City State ziapi I ••••• — V L6.5 If" C-fh'''''' V , Fax Number: E-Mail Address: 1 MECTIANICAL.CONTRA.crogINFoRiviAltoN --, ‘: -- , ..... ,., .r.. ' lei3, I. :4.— " '' ' l'• ' ' + ,7 ' ■ ' ,;1 a ' .. r ' ' '', ' • 4 ., ' ' , ' '' . ' .. ,.: Company Name: Mailing Address: T 0 Contact Person: E-Mail Address: Contractor Registration Number: Company Name: 4 ) 1 .App 1 ■estions ,, Forrns-Applications Oa Line:3.204e - Mechanical Paint! Application 4,,c v.5ed hit • or MECIIA.NICAL PERMIT APPLICATION Applications and plans must be complete in order to be accepted for plan review. Applications will not be accepted through the mail or by fax. **Please Print* * 4rAndse thi C z : JO'N 1d5 j A 9 City late 1.-iSzt161.te__ ZOO 1 AIC 3.1 500 Mailing Address: t ENGINEER OF RECORtc.:-0piaiii nii.tt be vykstaid byEritinei-0 e I7 • • • - • Nteehaiii0.2.1 Permit No. Project No MV or o co ris:e only) ••••••■••••■■■■■ _ • .. •• np• • - • •• • '7:: ' , • . • • • _ King Co Assessor's Tax No.: Suite Number: New Tenant: /c1 .... Yes D..fo City Day Telephone: Fax Number: Expiration Date: State ARCOITECT. OF RECORif-ifAIIplaiis..muit .-Aife'l Record ' Z i p Zi City State Zip Contact Person: r: 0 OVA , Day Telephone: X 6- ( 2.1 E-Mail Address: . rt e V 6D, tig e Fax Number: Company' Name: Mailing Address: 1)2-T A AVN Ave_ t, e Icic" .eel-i-f-ft LiA, cit id I City State Zip . Contact Person: l -fryirA Al ‹)e, . Day Telephone: ZO C. 24,2, 010 E-Mail Address: I'M 1 31 , j ‘( 3 limn 4.L..,g....b-N Fax Number: ZO C. 2z (II:CT Page 1 of 2 Date Application Accepted: a J Date Application Expires: Qty Sl tf f Initials: (� 11 Qty Ot t (3 I 9 � Unit Type: Qty nit Type: Qty -Unit T e Yp . Qty Boi1erlComp'ressor: Qty Furnacc<100K UTU Air andling nit > I0,000 CFM I Fire Damper 0-3 HP 100,000 BTU / Furnace >l01K B'fU I$I Eva orator ' oler WJJ D ' iser p .r , -15'1IPt500,000 B'1i. 1! F1oorFurnace Ventilation Fan Connected to Single Duct Thermostat 15- 301IP /1,000, 13 Suspended/lrall/Floor Mounted heater MI Ventilation System Hood and Duct ) Val Wood/Gas Stove Water' Heater I 30 -50 HP!1.750,0001311J 50* II:/1,750,0 STU f 101 Ap Vent Repair or Addition to Hent/RefrigiCooling System ( nctnerator - Domestic Y' Y' Emergency Generator T r Air Handling Unit <10,000 CFM Incinerator — Comm /Ind ,� Other Mechanical Equipment Valuation of Project (contractor's bid price): s 100 Scope of Work (please ravide detailed information): Tile l „! # } } be p�^;� t CO I'{i t4r-e � "mi ' L, i r---5; liy e (yy t' .of. Use: Residential: New ....❑ Replacement .... Commercial: New ... Replacement .... ❑ BUILDING 0 Signature: Print N Mailing Address: Fuel Type: Electric ❑ G Fgt.: APV;ICATI a „ -fit AUTHORIZE 0 1APplienti nsW.rru.Applie, ism on Uno3.a006 • f,leehatrcal Permit Applka[bn don ItsvlaN 4 "2(Kl, th Other Indicate type of mcchanicai work being installed and the quantity below: Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Permit Center to comply with current fee schedules. .Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation. 1 he Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition). I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS. APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. Date: 69 / Day Te leh p one: `1!v V0 �'— Q Vb r0 c74 4 /0° 3 City state Zip Page 2of2 n....• pprcr c_rm RECEIPT NO: R08 -02643 Initials: JEM User ID: 1165 Payee: GENSLER SET ID: S000001082 SET TRANSACTIONS: Set Member Amount EL08 -1018 HMO8 19Q PG08 -210 TOTAL: TRANSACTION LIST: Type Method Payment ACCOUNT ITEM LIST: Description • City of Tukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 -431 -3670 Fax: 206 -431 -3665 Web site: http: //www.ci.tukwila.wa.us 4,340.00 1,726.25 582.00 6,648.25 ELECTRICAL PERMIT - NONR ELECTRICAL PLAN - NONRES GAS - NONRES MECHANICAL - NONRES PLAN CHECK - NONRES PLUMBING - NONRES Description Check 110577 SET RECEIPT TOTAL: Payment Date: 07/18/2008 Total Payment: 6,648.25 SET NAME: Tmp set/Initialized Activities Amount 6,648.25 6,648.25 Account Code Current Pmts 000.322.101.00.0 3,472.00 000.345.832.00.0 868.00 000.322.103.00.0 90.00 000.322.102.00.0 1,381.00 000/345.830 421.25 000.322.103.00.0 416.00 TOTAL: 6,648.25 017 07/18 9716 TOTAL 66/03.25 Proje � ar aitACl•JTYP?Off��3 do : S14 Address: '2 ` S lq A-k Z r �--/ Date eS _ A `^ 4 Special Instructions: 03 tS 9C` O ('Z' � A ' 8 ``' A `.+ Date Wanted: ,- f? ij 9 / ( rape p.m. Requester: Phone No: 2Q - ' 5 ) 7 INSPECTION NO. INSPECTION RECORD Retain a copy with permit PERMIT NO. CITY OF TUKWILA BUILDING DIVISION le- 6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670 Approved per applicable codes. Corrections required prior to approval. COMMENTS: nee �r l.� � � (-eX- I SJ P rbJ - A. 44- Afpf o _ ri $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection. Receipt No.: 'Date: 4 COMMENTS: Type of Inspection: )- -I, / 4 ,I h,xv/ , 1.7 4 7-A / / - fv. 9 xi ,-. .- 2/4,; & a1/ ide, 17k' dai¢a 7'G S PC.v'° 4 /2 , ‘> A- 1- / - d,%.,5/,-'7' %/19---e-- - ,2/# i0 Requester: Phone No: _ 0C- ;f..?-z Ne --� .. N Proj ct: . Ate. of 4,9G47»'4 Type of Inspection: )- -I, / Address: 3L0 Sr1?Al/Op a Date Called: Special Instructions: Date Wanted: 2 _ 6 9 p.m. Requester: Phone No: _ 0C- ;f..?-z G/ INSPECTION NO. CITY OF TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila, WA 98188 lnsp r: INSPECTION RECORD Retain a copy with permit m0,° - /9v PERMIT NO. I4 (206)431 -3670 El Approved per applicable codes. Corrections required prior to approval. D>re---: 2 ._ $60.00 REINSPECTION FE REQUIRED. Prior to inspection, fee must be paid at 6300 Southcenter B vd., Suite 100. Call to schedule reinspection. Receipt No.: 'Date: COMMENTS:, d Type cA Ins ectii n: Adcirrei :n sTrQ ( r c(- 76^-S MA a fr • - 0 (-r ,S , ) -P Act ,r4 (1 AW /4 It Bo: (6Q,,, ----- ti i. 1 t _St ( e C-1 t hel. g Requester: _ Phone No: /AO I0- '71°3 - 25 .-----., f\ 1 ( Pro e t: 31- d Type cA Ins ectii n: Adcirrei :n sTrQ StiA Date Called: Special Instructions: / Date Wanted: -5- g Requester: Phone No: /AO I0- '71°3 - 25 INSPECTION RECORD Retain a copy with permit M0$ rERMIT NO. CITY OF TUKWILA BUILDING DIVISION ( 6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -36 INSPECTION NO. A pproved per applicable codes. Corrections required prior to approval. 7 r V `Date: -eV'Oy El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection. Inspect'; r: Receipt No.: Date: COMMENTS: p 4 . �/} ..„ RAI b - •../ / 4 1 / 1 04 g O 7' At ' _ 4 5 e ' ¢fir sr Cif s %rte .. i s i so„/ /¢ Q a ; A l .& c Address: .3Lo •S T,Qit a/vQ Date Called: ) /?- -- -9 -0.- 09 - / / �}','- /�t/er- 7 - � ' �v ' A/ D Tie' % ,�aaa� /�f /" /.%7 Ai L / Q Requester: / r4 ! / AtA .4,ve z , r/mur/ tor✓ i ;e2r -- . f1 /).\\, 2ro ct: li A,t/K v F #1,v/'e -- Type of Inspection:, AZ rn,C 4 --/iv Address: .3Lo •S T,Qit a/vQ Date Called: Special Instructions: Date Wanted: — / 8_. dq p.m. Requester: Phone No: Ok 06 -7.13 _2.5.4.,y, INSPECTION RECORD Retain a copy with permit INSPECTION NO. PERMIT NO. CITY OF TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670 A. El per applicable codes. Corrections required prior to approval. e pector I Date., ^ , k .00 REINSPECTION FEE R EQUIRED. Prior to inspection, fee must be aid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection. ceipt No.: Date: i Project: v /9- Type of Inspe tion: /.Z e� /5i — Address: 37- D S T /2AN�,x,- Date Called: f Special Instructions: Date Wanted: 5-- 5 — 0 , s a.m. p.m. Requester: Phone No: /hee—/F0 INSPECTION RECORD Retain a copy with permit INSPECTION NO. PERMIT NO. CITY OF TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670 Approved per applicable codes. Ei Corrections required prior to approval. COMMENTS: p /20t,t7 --`•./ - 4,,hir.d.,,z/Ariaikttes V i/1 j L l 0 .00 REINSPECTION F REQ RED. Prior to inspection, must be . id at 6300 Southcenter :,vd., uite 100. Call to schedule reinspection. f Re eipt No.: Date: MEMORANDUM Date: August 1, 2008 To: Barry Zimmerman Company Gensler 1200 Sixth Avenue, Suite 500 Seattle, WA 98101 206 -654 -2129 C: Narrative: End of Narrative 1601 Fifth Avenue, Suite 900 • Seattle, Washington • 98101 (206) 623 -0717 Phone (206) 624-3775 FAX ,LAS Gs- creativity:I results J relationships !' A EOFFMAN Project: B of A South Center 3XX Strander BI Tukwila WA Project No.: 08040 ptmi. e From: Arvind Nerurkar 1. Permit #M08 -190 Regarding item 1 in the Determination of Completeness Memo, Structural framing members supporting mechanical units at the roof have been determined to adequately resist gravity and lateral induced loads. See attached supporting calculations on sheet MF -7 and detail 1 on sheet MF -8 for further clarification. REVIEWED FOR CODE COMPLIANCE APPROVED AUG 18 2008 City Of Tukwila BUILDING DIVISION INCOMPLETE LTR # �_ 11O9. 190 RECEIVED AUG 052008 PERMIT CENTER s- CH Eex Zoo; •g`i 4 g Mui-i vAia R2 C v'tog -S Cyst Y Ig 210 1 65 2 5 S6 v1141 2 100 /(z + /44 v.l1L t- 3A- pLF 1 4412 = • 5l).? Lev' r'-i v� L 11 ui/ F 1 v 312 LATE RA-L P 9U L65 = S.g3 FLt= IR ?1,1. ■/M■ < 1 f If T ` 903 x 49 zoite3 utk= 6(9%1- I 03E 3/ SDS ScRiv -13 ecA cca t . t4q r■ \- . .;p 1 0 0 :1sb 2t00 ( S.Z uloR_,FT A COFFMAN N G I N E E R S prole« 5 F A < , i) L,NTI sa location (i/ K �,(i t / w { A client 61 by d date k checked date sheet no F - job no. 6t646 (4) If u 3 / SD EA Cok.N C:k l3l aC k k nJG1 A S k A TK? 0 )4 LeA AN k c,4 L //DD F A A x 4 6 t 3 LIC.tNG —, >4� to , Eb�zr S ALCOFFM�4N N G I N E E R S Project /),:: l4 So v rF /6_,Ai C PZ.. location (✓ vi A- dient en r ,jZ by S4 date (t / checked date sheet no. MF - job no. O4 •.b MINE 36 c9'A 6PRP�G 78 (3 4 4• cm46 Ce qe. fic5 Figure 18. Roof Curb * All dimensions are In Inches /millimeters. Dimensional Data csl Nb Cooling with Optional Electric Heat and Gas /Electric Models - 6-10 Tons Standard and High Efficiency C(411:4431,4,_ q '`'c 06. Ie. r f 89 7/8' 4 a . (scsomm) ) . Op ALL FLANGES 1 1/4" (31 MM) Figure 19. Cooling with Optional Electric Heat and Gas /Electric Models 6-10 Tons - Downflow Duct Connections Field Fabricated * All dimensions are in Inches /millimeters. (RTU -R.2. O,p y RT- PRCO25 -EN 125 Cooling Equipment Schedule Equip. ID Brand Name' Model No.' Capacity Btu/h Total CFM OSA CFM or Econo? SEE�ZIC �l� Kopp, �l! ctl o n Tukwilla, WA 98188 Applicant Name: clumac, Michael Aliaga � COP CITY p���� I Applicant Phone: 206- 262 -8375 r Ali . MOt Jill A i v 1 8 8 vutiviIT CENTER CO Of 75 ��a ,', Fan Equipment Schedule Equip. ID Brand Name' Model No.' CFM SP' HP /BHP Flow Control Location of Service Equip. ID Tukwilla, WA 98188 Applicant Name: clumac, Michael Aliaga � COP CITY RECEIVEC VF i UKW1L.PI /NS Applicant Phone: 206- 262 -8375 r Ali . MOt Jill 18 2C08 Heating Equipment Schedule Brand Name' Model No.' Capacity Btu/h Total CFM OSA cfm or Econo? it „pi Input Btuh t1 Div Output Btuh Efficiency` Equip. ID Tukwilla, WA 98188 Applicant Name: clumac, Michael Aliaga � COP CITY RECEIVEC VF i UKW1L.PI /NS Applicant Phone: 206- 262 -8375 r Ali . Jill 18 2C08 vutiviIT CENTER Project Info . Project Address BoA- Southcenter Branch Relocation Date 320 Strander Blvd. For Building Dept. Use Tukwilla, WA 98188 Applicant Name: clumac, Michael Aliaga � COP Applicant Address: 1325 4th Ave. Seattle, WA 98101 /NS Applicant Phone: 206- 262 -8375 r Ali . II. £ Y Y••I Mechanical Summary ►•Y - •-Y - _Y • .• •11} . • 11 MECH -SUM 2006 Washington State Nonresidential Energy Code Compliance Forms Project Description Briefly describe mechanical system type and features. Indudes Plans Building will be conditioned with packaged rooftop,lmitwi full a economizers. Drawings must contain notes requireing compliance with commissioning requirements - Section 1416 • Revised July 2007 Compliance Option Q Simple System 0 Complex System O Systems Analysis (See Decision Flowchart (over) for qualifications. Use separate MECH -SUM for simple & complex systems.) Equipment Schedules The following information is required to be incorporated with the mechanical equipment schedules on the plans. For projects without plans, fill in the required information below. 'If available. 2 As tested according to Table 14 -1A through 14-1G. 3 If required. ` COP, HSPF, Combustion Efficiency, or AFUE, as applicable. 5 Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS). System Description If Heating/Cooling 51 Constant vol? Q Air cooled? 5 Packaged sys? ■ <20,000 Btuh? See Section 1421 for full description of Simple System or Cooling Only: Split system? • Q Economizer included? qualifications. If Heating Only: 9 M � 5000 cfm? <5000 � <70 /o outside air? <70% 1,. 1 • 1 1• 01 • \•1 - 11 "1 • _1 • ••- •11} .1: • 11 , Mechanical Summary (back) MECH -SUM, Decision Flowchart Use this flowchart to determine if project qualifies for Simple System Option. If not, either the Complex System or Systems Analysis Options must be used. ( START ) otal Ca wo economize <240,000 Btuh or 10 %? Heating Only Reference Section 1421 Heating/Cooling or Cooling Only Simple System # Allowed (section 1420) I Reference Section 1423 Complex Systems I Refer to MECH -COMP Mechanical Complex Systems for assistance in determining which Complex Systems requirements are applicable to this project. Mechanical Permit Plans Checklist 2006 Washington State Nonresidential Energy Code Compliance Forms MECH -CHK Revised July 2007 Project Address BoA-Southcenter Branch Relocation 'Date The following information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the Washington State Nonresidential Energy Code. Applicability (yes, no, n.a.) Code Section Component Information Required Location on Plans Building Department Notes HVAC REQUIREMENTS (Sections 1401 -1424) 1411 Equipment performance yes 1411.4 Pkg. elec. htg.& clg. List heat pumps on schedule M00.02 yes 1411.1 Minimum efficiency Equipment schedule with type, capacity, efficiency moo. 02 n.a. 1411.1 Combustion htg. Indicate intermittent ignition, flue/draft damper & jacket loss 1412 HVAC controls yes 1412.1 Temperature zones Indicate locations on plans MO2.01 yes 1412.2 Deadband control Indicate 5 degree deadband minimum Moo .01 n.a. 1412.3 Humidity control Indicate humidistat yes 1412.4 Automatic setback Indicate thermostat with night setback and 7 diff. day types Moo .02 n.a. 1412.4.1 Dampers Indicate damper location and auto. controls & max. leakage yea 1412.4.2 Optimum Start Indicate optimum start controls M00.02 n.a. 1412.5 Heat pump control Indicate microprocessor on thermostat schedule n.a. 1412.6 Combustion htg. Indicate modulating or staged control yes 1412.7 Balancing Indicate balancing features on plans MO2.01 1412.8 Ventilation Control Indicate demand control ventilation for high - occupancy areas n.a. 1422 Thermostat interlock Indicate thermostat interlock on plans yes 1423 Economizers Equipment schedule M00.02 1413 Air economizers yes 1413.1 Air Econo Operation Indicate 100% capability on schedule Moo .02 n.a. 1413.1 Wtr Econo Operation Indicate 100% capacity at 45 degF db & 40 deg F wb n.a. 1413.2 Water Econo Doc Indicate clg load & water econoe & clg tower performance yes 1413.3 Integrated operation Indicate capability for partial cooling M00.02 n.a. 1413.4 Humidification Indicate direct evap or fog atomization w/ air economizer 1414 Ducting systems yes 1414.1 Duct sealing Indicate sealing necessary M00.02 yes 1414.2 Duct insulation Indicate R -value of insulation on duct Moo . 02 yes 1415.1 Piping insulation Indicate R -value of insulation on piping m00.02 1416 Completion Requirements yes 1416.2.1 Commissioning Provide commissioning plan Moo . 01 yes 1416.2.2 -3 Sys.Bal & Func.Test Indicate air and water system balancing & functional testing M00.01 yes 1416.2.4 Commissioning Indicate O &M manuals, record drawings, staff training M00.01 yes 1416.2.5 Comm. Report Indicate requirements for prelim. & final commissioning report M00.01 yes 1434 Separate air sys. Indicate separate systems on plans MO2.01 yes Mechanical Summary Form Completed and attached. Equipment schedule with types, input/output, efficiency, cfm, hp, economizer M00.02 SERVICE WATER HEATING AND HEATED POOLS (Sections 1440 -1454) 1440 Service water htg. n.a. 1441 Elec. water heater Indicate R -10 insulation under tank yes 1442 Shut -off controls Indicate automatic shut -off P00.1 yes 1443 Pipe Insulation Indicate R -value of insulation on piping P00. 1 n.a. 1452 Heat Pump COP Indicate minimum COP of 4.0 yes 1452 Heater Efficiency Indicate pool heater efficiency M00.02 n.a. 1453 Pool heater controls Indicate switch and 65 degree control n.a. 1454 Pool covers Indicate vapor retardant cover n.a. 1454 Pools 90+ degrees Indicate R -12 pool cover 2006 Washinton State Nonresidential Energy Code Compliance Form 2006 Washin•ton State Nonresidential Ener. Code Corn liance Form Mechanical Permit Plans Checklist MECH CHK 2006 Washington State Nonresidential Energy Code Compliance Forms Revised July 2007 Mechanical - General Requirements 1411.1 General: Equipment shall have a minimum performance at the specified rating conditions not less than the values shown in Table 14-1A through 14-1G. If a nationally recognized certification program exists for a product covered in Tables 14-1A through 14-1G, and it includes provisions for verification and challenge of equipment efficiency ratings, then the product shall be listed in the certification program. Gas -fired and oil -fired forced air furnaces with input ratings? 225,000 Btu/h (65 kW) and all unit heaters shall also have an intermittent ignition or interrupted device (IID), and have either mechanical draft (including power venting) or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings > 225,000 Btu/h (65 kW), including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75% of the input rating. 1411.2 Rating Conditions: Cooling equipment shall be rated at ARI test conditions and procedures when available. Where no applicable procedures exist, data shall be furnished by the equipment manufacturer. 1411.3 Combination Space and Service Water Heating: For combination space and service water heaters with a principal function of providing space heat, the Combined Annual Efficiency (CAE) may be calculated by using ASHRAE Standard 124 -1991. Storage water heaters used in combination space heat and water heat applications shall have either an Energy FActor (EF) or a CAE of not less than the following: 1411.4 Packaged Electric Heating and Coo ing Equipment: Packaged electric equipment providing both heating and cooling with a total cooling capacity greater than 20, Btu/h shall be a heat pump. Exception: Unstaffed equipment shaelters or cabinets used solely for personal wireless service facilities. 1412 Controls 1412.1 Temperature Controls: Each system shall be provided with at least one temperature control device. Each zone shall be controlled by individual thermostatic controls responding to temperature within the zone. At a minimum, each floor of a building shall be considered as a separate zone. 1412.2 Deadband Controls: When used to control both comfort heating and cooling, zone thermostatic controls shall be capable of a deadband of at least 5 degrees F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. Exceptions: 1. Special occupancy, special usage, or code requirements where deadband controls are not appropriate. 2. Buildings complying with Section 1141.4, if in the proposed building energy analysis, heating and cooling thermostat setpoints are set to the same temperature between 70 degrees F and 75 degrees F inclusive, and assumed to be constant throughout the year. 3. Thermostats that require manual changeover between heating and cooling modes. 1412.3 Humidity Controls: If a system is equipped with a means for adding moisture, a humidistat shall be provided. 1412.4 Setback and Shut - Off: HVAC systems shall be equipped with automatic controls capable of accomplishing a reduction of energy use through control setback or equipment shutdown during periods of non -use or alternate use of the spaces served by the system. The automatic controls shall have a minimum seven -day clock and be capable of being set for seven different day types per week It must retain programming and time for a power loss of 10 hours and include an accessible manual override of up to 2 hours. Exceptions: 1. Systems serving areas which require continuous operation at the same temperature setpoint. 2. Equipment with full load demands of 2 kW (6,826 Btu /h) or less may be controlled by readily accessible manual off -hour controls. 3. Systems controlled by an occupant sensor that is capable of shutting the system off when no occupant is sensed for a period of up to 30 minutes. 4. Systems controlled solely by a manually operated timer capable of operating the system for no more than two hours. 1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets serving conditioned spaces shall be equipped with dampers which dose automatically when the system is off or upon power failure. Stair shaft and elevator shaft smoke relief openings shall be equipped with normally open (fails to open upon loss of power) dampers. These dampers shall remain dosed until activated by the fire alarm system or other approved smoke detection system. Exceptions: 1. Systems serving areas which require continuous operation. 2. Combustion air intakes. 3. Gravity (nonmotorized) dampers are acceptable in buildings less than 3 stories in height. 4. Gravity (nonmotorized) dampers are acceptable in exhaust and relief outlets in the first story and levels below the first story of buildings 1412.8 Ventilation Controls for High - Occupancy Areas: Demand control ventilation (DCV) is required for spaces that are larger than 500 ft2, have a design occupancy for ventilation of greater than 40 people for 1000 ft2 of floor area, and are served by systems with one or more of the following: a. An air -side economizer, b. Automatic modulating control of the outdoor air damper, or c. A design outdoor airflow greater than 3000 cfm. Exceptions: 1.Systems with energy recovery complying with Section 1436. 2. Multiple -zone systems without direct - digital control of individual zones communicating with a central control panel. 3. Systems with a design outdoor airflow less than 1200 cfm. 4. Spaces where the supply airflow rate minus any makeup or outgoing transfer air requirement is less than 1200 cfm. 1413 Air Economizers 1413.1 Operation: Air economizers shall be of automatically modulating outside and return air dampers to provide 100 percent of the design supply air as outside air to reduce or eliminate the need for mechanical cooling. Water economizers shall be capable of providing the total concurrent cooling load served by the conneted terminal equipment lacking airside economizer, at outside air temperatures of 45 ° F dry- bulb /40 ° F wet -bulb and below. For this calculation, all factors including solar and internal load shall be the same as those used for peak load calculations, except for the outside temperatures. Exception: Water economizers using air- cooled heat rejection equipment may use a 35 ° F dry-bulb outside air temperature for this calculation. This exception is limited to a maximum of 20 tons per building. 1413.2 Documentation: Water economizer plans submitted for approval shall include the following information: 1. Maximum outside air conditions for which economizer is sized to provide full cooling. 2. Design cooling load to be provided by economizer at this outside air condition. 3. Heat rejection and terminal equipment performance data including model number, flow rate, capacity, entering and leaving temperature in full economizer cooling mode. 1413.3 Integrated Operation: Air economizers shall be capable of providing partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. Exceptions: 1. Individual, direct expansion units that have a rated capacity less than 65,000 Btu/h and use nonintegrated economizer controls that preclude simultaneous operation of the economizer and mechanical cooling. 2. Water - cooled water chillers with waterside economizer. 1413.4 Humidification: If an air economizer is required on a cooling system for which humidification equipment is to be provided to maintain minimum indoor humidity levels, then the humidifier shall be of the adiabatic type (direct evaporative media or fog atomization type). Exceptions: 1. Health care facilities where WAC 246 - 320 -525 allows only steam injection humidifiers in ductwork downstream of final filters. 1412.6 Combustion Heating Equipment Controls: Combustion heating equipment with a capacity over 225,000 Btu/h shall have modulating or staged combustion control. 2. Systems with water economizer 3. 100% outside air systems with no provisions for air recirculation to the central supply fan. 4. Nonadiabatic humidifiers cumulatively serving no more than 10% of a building's air economizer capacity as measured in cfm. This refers to the system cfm serving rooms with stand alone or duct mounted humidifiers. 1414 Ducting Systems 1414.1 Sealing: Duct work which is designed to operate at pressures above 1/2 inch water column static pressure shall be sealed in accordance with Standard RS-18. Extent of sealing required is as follows: 1. Static pressure: 1/2 inch to 2 inches; seal transverse joints. 2. Static pressure: 2 inches to 3 inches; seal all transverse joints and longitudinal seams. 3. Static pressure: above 3 inches; seal all transverse joints, longitudinal seams and duct wall penetrations. Duct tape and other pressure sensitive tape shall not be used as the primary sealant where ducts are designed to operate at static pressures of 1 inch W.C. or greater. 1414.2 Insulation: Ducts and plenums that are constructed and function as part of the building envelope, by separating interior space from exterior space, shall meet all applicable requirements of Chapter 13. These requirements include insulation installation, moisture control, air leakage, and building envelope insulation levels. Unheated equipment rooms with combustion air louvers must be isolated from the conditioned space by insulating interior surfaces to a minimum of R -11 and any exterior envelope surfaces per Chapter 13. Outside air ducts serving individual supply air units with less than 2,800 cfm of total supply air capacity shall be insulated to a minimum of R -7 and are not considered building envelope. Other outside air duct runs are considered building envelope until they, EF CAE < 50 gal storage 0.58 0.71 50 to 70 gal storage 0.57 0.71 > 70 gal storage 0.55 0.70 2006 Washin•ton State Nonresidential Ener. Code Corn liance Form Mechanical Permit Plans Checklist MECH CHK 2006 Washington State Nonresidential Energy Code Compliance Forms Revised July 2007 Mechanical - General Requirements 1411.1 General: Equipment shall have a minimum performance at the specified rating conditions not less than the values shown in Table 14-1A through 14-1G. If a nationally recognized certification program exists for a product covered in Tables 14-1A through 14-1G, and it includes provisions for verification and challenge of equipment efficiency ratings, then the product shall be listed in the certification program. Gas -fired and oil -fired forced air furnaces with input ratings? 225,000 Btu/h (65 kW) and all unit heaters shall also have an intermittent ignition or interrupted device (IID), and have either mechanical draft (including power venting) or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings > 225,000 Btu/h (65 kW), including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75% of the input rating. 1411.2 Rating Conditions: Cooling equipment shall be rated at ARI test conditions and procedures when available. Where no applicable procedures exist, data shall be furnished by the equipment manufacturer. 1411.3 Combination Space and Service Water Heating: For combination space and service water heaters with a principal function of providing space heat, the Combined Annual Efficiency (CAE) may be calculated by using ASHRAE Standard 124 -1991. Storage water heaters used in combination space heat and water heat applications shall have either an Energy FActor (EF) or a CAE of not less than the following: 1411.4 Packaged Electric Heating and Coo ing Equipment: Packaged electric equipment providing both heating and cooling with a total cooling capacity greater than 20, Btu/h shall be a heat pump. Exception: Unstaffed equipment shaelters or cabinets used solely for personal wireless service facilities. 1412 Controls 1412.1 Temperature Controls: Each system shall be provided with at least one temperature control device. Each zone shall be controlled by individual thermostatic controls responding to temperature within the zone. At a minimum, each floor of a building shall be considered as a separate zone. 1412.2 Deadband Controls: When used to control both comfort heating and cooling, zone thermostatic controls shall be capable of a deadband of at least 5 degrees F within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum. Exceptions: 1. Special occupancy, special usage, or code requirements where deadband controls are not appropriate. 2. Buildings complying with Section 1141.4, if in the proposed building energy analysis, heating and cooling thermostat setpoints are set to the same temperature between 70 degrees F and 75 degrees F inclusive, and assumed to be constant throughout the year. 3. Thermostats that require manual changeover between heating and cooling modes. 1412.3 Humidity Controls: If a system is equipped with a means for adding moisture, a humidistat shall be provided. 1412.4 Setback and Shut - Off: HVAC systems shall be equipped with automatic controls capable of accomplishing a reduction of energy use through control setback or equipment shutdown during periods of non -use or alternate use of the spaces served by the system. The automatic controls shall have a minimum seven -day clock and be capable of being set for seven different day types per week It must retain programming and time for a power loss of 10 hours and include an accessible manual override of up to 2 hours. Exceptions: 1. Systems serving areas which require continuous operation at the same temperature setpoint. 2. Equipment with full load demands of 2 kW (6,826 Btu /h) or less may be controlled by readily accessible manual off -hour controls. 3. Systems controlled by an occupant sensor that is capable of shutting the system off when no occupant is sensed for a period of up to 30 minutes. 4. Systems controlled solely by a manually operated timer capable of operating the system for no more than two hours. 1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets serving conditioned spaces shall be equipped with dampers which dose automatically when the system is off or upon power failure. Stair shaft and elevator shaft smoke relief openings shall be equipped with normally open (fails to open upon loss of power) dampers. These dampers shall remain dosed until activated by the fire alarm system or other approved smoke detection system. Exceptions: 1. Systems serving areas which require continuous operation. 2. Combustion air intakes. 3. Gravity (nonmotorized) dampers are acceptable in buildings less than 3 stories in height. 4. Gravity (nonmotorized) dampers are acceptable in exhaust and relief outlets in the first story and levels below the first story of buildings 1412.8 Ventilation Controls for High - Occupancy Areas: Demand control ventilation (DCV) is required for spaces that are larger than 500 ft2, have a design occupancy for ventilation of greater than 40 people for 1000 ft2 of floor area, and are served by systems with one or more of the following: a. An air -side economizer, b. Automatic modulating control of the outdoor air damper, or c. A design outdoor airflow greater than 3000 cfm. Exceptions: 1.Systems with energy recovery complying with Section 1436. 2. Multiple -zone systems without direct - digital control of individual zones communicating with a central control panel. 3. Systems with a design outdoor airflow less than 1200 cfm. 4. Spaces where the supply airflow rate minus any makeup or outgoing transfer air requirement is less than 1200 cfm. 1413 Air Economizers 1413.1 Operation: Air economizers shall be of automatically modulating outside and return air dampers to provide 100 percent of the design supply air as outside air to reduce or eliminate the need for mechanical cooling. Water economizers shall be capable of providing the total concurrent cooling load served by the conneted terminal equipment lacking airside economizer, at outside air temperatures of 45 ° F dry- bulb /40 ° F wet -bulb and below. For this calculation, all factors including solar and internal load shall be the same as those used for peak load calculations, except for the outside temperatures. Exception: Water economizers using air- cooled heat rejection equipment may use a 35 ° F dry-bulb outside air temperature for this calculation. This exception is limited to a maximum of 20 tons per building. 1413.2 Documentation: Water economizer plans submitted for approval shall include the following information: 1. Maximum outside air conditions for which economizer is sized to provide full cooling. 2. Design cooling load to be provided by economizer at this outside air condition. 3. Heat rejection and terminal equipment performance data including model number, flow rate, capacity, entering and leaving temperature in full economizer cooling mode. 1413.3 Integrated Operation: Air economizers shall be capable of providing partial cooling even when additional mechanical cooling is required to meet the remainder of the cooling load. Exceptions: 1. Individual, direct expansion units that have a rated capacity less than 65,000 Btu/h and use nonintegrated economizer controls that preclude simultaneous operation of the economizer and mechanical cooling. 2. Water - cooled water chillers with waterside economizer. 1413.4 Humidification: If an air economizer is required on a cooling system for which humidification equipment is to be provided to maintain minimum indoor humidity levels, then the humidifier shall be of the adiabatic type (direct evaporative media or fog atomization type). Exceptions: 1. Health care facilities where WAC 246 - 320 -525 allows only steam injection humidifiers in ductwork downstream of final filters. 1412.6 Combustion Heating Equipment Controls: Combustion heating equipment with a capacity over 225,000 Btu/h shall have modulating or staged combustion control. 2. Systems with water economizer 3. 100% outside air systems with no provisions for air recirculation to the central supply fan. 4. Nonadiabatic humidifiers cumulatively serving no more than 10% of a building's air economizer capacity as measured in cfm. This refers to the system cfm serving rooms with stand alone or duct mounted humidifiers. 1414 Ducting Systems 1414.1 Sealing: Duct work which is designed to operate at pressures above 1/2 inch water column static pressure shall be sealed in accordance with Standard RS-18. Extent of sealing required is as follows: 1. Static pressure: 1/2 inch to 2 inches; seal transverse joints. 2. Static pressure: 2 inches to 3 inches; seal all transverse joints and longitudinal seams. 3. Static pressure: above 3 inches; seal all transverse joints, longitudinal seams and duct wall penetrations. Duct tape and other pressure sensitive tape shall not be used as the primary sealant where ducts are designed to operate at static pressures of 1 inch W.C. or greater. 1414.2 Insulation: Ducts and plenums that are constructed and function as part of the building envelope, by separating interior space from exterior space, shall meet all applicable requirements of Chapter 13. These requirements include insulation installation, moisture control, air leakage, and building envelope insulation levels. Unheated equipment rooms with combustion air louvers must be isolated from the conditioned space by insulating interior surfaces to a minimum of R -11 and any exterior envelope surfaces per Chapter 13. Outside air ducts serving individual supply air units with less than 2,800 cfm of total supply air capacity shall be insulated to a minimum of R -7 and are not considered building envelope. Other outside air duct runs are considered building envelope until they, III , WWI ,, ,. .2Q.06 Washington S tatalloziresidential- Energy .Gode Eornplianee•Form- -- .._..., _.. -. outlets in the first story and levels below the first story of buildings duct runs are considered building envelope until they, three or more stones in height. 1. connect to the heating or cooling equipment, or 1412.4.2 Optimum Start Controls: Heating and cooling systems with design supply air capacities exceeding 10,000 cfm shall have optimum start controls. Optimum start controls shall be designed to automatically adjust the start time of an HVAC system each day to bring the space to desired occupied temperature levels immediately before scheduled occupancy. The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied setpoint and the amount of time prior to scheduled occupancy. 1412.5 Heat Pump Controls: Unitary air cooled heat pumps shall include microprocessor controls that minimize supplemental heat usage during start-up, set- up, and defrost conditions. These controls shall anticipate need for heat and use compression heating as the first stage of heat. Controls shall indicate when supplemental heating is being used through visual means (e.g., LED indicators). 1412.6 Combustion Heating Equipment Controls: Combustion heating equipment with a capacity over 225,000 Btu/h shall have modulating or staged combustion control. 000 EXCEPTIONS: 1. Boilers. 2. Radiant heaters. 1412.7 Balancing: Each air supply outlet or air or water terminal device shall have a means for balancing, including but not limited to, dampers, temperature and pressure test connections and balancing valves. 2. are isolated from the exterior with an automatic shut-off damper complying with Section 1412.4.1. Once outside air ducts meet the above listed requirements, any runs within conditioned space shall comply with Table 14-5 requirements. Other ducts and plenums shall be thermally insulated per Table 14 -5. Exceptions: 1. Within the HVAC equipment. 2. Exhaust air ducts not subject to condensation. 3. Exposed ductwork within a zone that serves that zone. 1415 Piping Systems 1415.1 Insulation: Piping shall be thermally insulated in accordance with Table 14.6. Exception: Piping installed within unitary HVAC equipment. Water pipes outside the conditioned space shall be insulated in accordance with Washington State Plumbing Code (WAC 51 -26) 1416 Completion Requirements (Refer to NREC Section 1416 and the Building Commissioning Guidelines, published by the Building Commissioning Association, for complete text and guidelines for building completion and commissioning requirements.) 05 -04 -2009 BRIAN VAN STIPDONK 1200 6 AV, STE 500 SEATTLE WA 98101 RE: Permit No. M08 -190 320 STRANDER BL TUKW Dear Permit Holder: Thank you for your cooperation in this matter. Sincerely, Bill Rambo Permit Technician xc: Permit File No. M08 -190 Guy of Tukwila Jim Haggerton, Mayor Department of Community Development Jack Pace, Director In reviewing our current records the above noted permit has not received a final inspection by the City of Tukwila Building Division. Per the International Building Code and/or the International Mechanical Code, every permit issued by the Building Division under the provisions of this code shall expire by limitation and become null and void if the building or work authorized by such permit is not commenced within 180 days from the date of such permit, or if the building or work authorized by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days. Based on the above, you are hereby advised to: Call the City of Tukwila Inspection Request Line at 206 - 431 -2451 to schedule for the next or final inspection. This inspection is intended to determine if substantial work has been accomplished since issuance of the permit or last inspection; or if the project should be considered abandoned. If such determination is made, the Building Code does allow the Building Official to approve one or more extensions of time for additional periods not exceeding 90 days each. Extension requests must be in writing and provide satisfactory reasons why circumstances beyond the applicants control have prevented action from being taken. In the event you do not call for the above inspection and receive an extension prior to 06/07/2009 , your permit will become null and void and any further work on the project will require a new permit and associated fees. 6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665 12 -03 -2008 BRIAN VAN STIPDONK 1200 6 AV, STE 500 SEATTLE WA 98101 Dear Permit Applicant: RE: Permit Application No. M08 -190 320 STRANDER BL TUKW Department of Community Development Jim Haggerton, Mayor Jack Pace, Director In reviewing our current permit application files, it appears that your permit application applied for on 07/18/2008 , has not been issued by the City of Tukwila Permit Center. Per the International Building Code and/or the International Mechanical Code, every permit application not issued within 180 days from the date of application shall expire by limitation and become null and void. Your permit application expires on 01/14/2009 . If you choose to pursue your project, a written request for extension of your application addressed to the Building Official, demonstrating justifiable cause, will need to be received at the Permit Center prior to your expiration date of 01/14/2009. If it is determined that an extension is granted, your application will be extended for an additional 90 days from the expiration date. In the event we do not receive your written request for extension, your permit application will become null and void and your project will require a new permit application, plans and specifications, and associated fees. Thank you for your cooperation in this matter. Sincerely, r Marsh • 1 Technician xc: Permit File No. M08 -190 6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665 J . July 22, 2008 Brian VanStipdunk 1200 Sixth Avenue, Suite 500 Seattle, WA 98101 RE: Letter of Incomplete Application # 1 Development Permit Application M08 -190 Bank of America — Strander BI Dear Mr. Van Stipdunk, This letter is to inform you that your permit application received at the City of Tukwila Permit Center on July 18, 2008 is determined to be incomplete. Before your application can continue the plan review process the following items from the following department needs to be addressed: Building Department: Allen Johannessen at 206 433 -7163 if you have any questions concerning the attached comments. Please address the comment above in an itemized format with applicable revised plans, specifications, and /or other documentation. The City requires that two (2) sets of revised plans, specifications and/or other documentation be resubmitted with the appropriate revision block. In order to better expedite your resubmittal a `Revision Submittal Sheet' must accompany every resubmittal. I have enclosed one for your convenience. Revisions must be made in person and will not be accepted through the mail or by a messenger service. If you have any questions, please contact me at the Permit Center at (206) 431 -3670. Brenda Holt Permit Coordinator Enclosures File: M08 -190 Department of Community Development Jack Pace, Director P: \Permit Center\Incomplete Letters\2008\M08 -190 Incomplete Ltr # 1.DOC jem • Jim Haggerton, Mayor 6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665 • Determination of Completeness Memo Date: July 22, 2008 Project Name: Bank of America Permit #: M08 -190 Plan Review: Allen Johannessen, Plans Examiner Tukwila Building Division Allen Johannessen, Plan Examiner The Building Division has deemed the subject permit application incomplete. To assist the applicant in expediting the Department plan review process, please forward the following comments. (GENERAL NOTE) PLAN SUBMITTALS: (Min. size 11x17 to maximum size of 24x36; all sheets shall be the same size). (If applicable) Structural Drawings and structural calculations sheets shall be original signed wet stamped, not copied.) 1. New mechanical equipment to be installed on the roof exceeding 400 pounds shall require an engineer's analysis for the roof structure with calculations to show the roof structural members are sufficient for the combined loads imposed by all the mechanical equipment. Provide specific details with the engineer's calculations. In addition, details shall show how units secure to the curbs to resist wind and seismic loads. All engineer's documents shall be original wet stamped and signed by the engineer. (IMC 106.3.1, 301.12, Section 302, IBC 1606.2) Should there be questions concerning the above requirements, contact the Building Division at 206 - 431 -3670. No further comments at this time. ACTIVITY NUMBER: M08-190 DATE: 08-05-08 PROJECT NAME: BANK OF AMERICA SITE ADDRESS: '1e0 STRANDER BL Original Plan Submittal X Response to Incomplete Letter # 1 Response to Correction Letter # Revision # After Permit Issued DEP RTM NT • , 0 ill ding Division Public Works El DETERMINATION OF COMPLETENESS: (Tues., Thurs.) Complete Comments: PERMIT COORD COPY 41 PLAN REVIEW/ROUTING SLIP . • . , , INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED: Departments determined incomplete: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials: Please Route Documents/routing slip.doc 2-28-02 TUES/THURS RO TING: APPROVALS OR CORRECTIONS: Fire Prevention Structural Incomplete Structural Review Required LI n Planning Division LI Permit Coordinator DUE DATE: 08-07-08 Not Applicable LI No further Review Required LI REVIEWER'S INITIALS: DATE: DUE DATE: 09-04-08 LI LI Approved 0 Approved with Conditions 0 Not Approved (attach comments) n Notation: REVIEWER'S INITIALS: DATE: Peimit Center Use Only '• • .: •••• - .• . CORRECTION LETTER MAILED: Departments issued corrections: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials: ACTIVITY NUMBER: M08 -190 DATE: 07 -18 -08 PROJECT NAME: BANK OF AMERICA SITE ADDRESS: X Original Plan Submittal Response to Correction Letter # Response to Incomplete Letter # Revision # after Permit Issued DEPARTMENTS: to Public Works DETERMINATION OF COMPLETENESS: (Tues., Thurs.) Complete Comments: Please Route Permit Center Use Only INCOMPLETE LETTER MAILED: � LETTER OF COMPLETENESS MAILED: Departments determined incomplete: Bldg V Fire ❑ Ping ❑ PW ❑ Staff Initial TUES/THURS ROUTING: n REVIEWER'S INITIALS: APPROVALS OR CORRECTIONS: PLAN REVIEW /ROUTING SLIP r o5 Structural Incomplete Structural Review Required Approved 1 Approved with Conditions Notation: REVIEWER'S INITIALS: Documents/routing slip.doc 2 -28 -02 "'PERMIT COORD COPY Eli �(pr7 c. 1. S.06 Fire Prevention IN Planning Division DATE: DATE: Permit Coordinator No further Review Required Not Approved (attach comments) n DUE DATE: 07-22-08 Not Applicable ❑ DUE DATE: 08-19-08 Permit Center Use Only CORRECTION LETTER MAILED: Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials: • City of Tukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 - 431 -3670 Fax: 206 - 431 -3665 Web site: http: / /www.ci.tukwila.wa.us Revision submittals must be submitted in person at the Permit Center. Revisions will not be accepted through the mail, fax, etc. Date: 'I J a Plan Check/Permit Number: M08-190 • Response to Incomplete Letter # 1 _ ❑ Response to Correction Letter # ❑ Revision # after Permit is Issued ❑ Revision requested by a City Building Inspector or Plans Examiner Project Name: BANK OF AMERICA Project Address: 3XX Strander B1 Contact Person: Brian VanStipdonk Summary of R vision: la AV RECEIVED OITVS TUKWILA AUG 0.5' HOS Sheet Number(s): "Cloud" or highlight all areas of revision including date o revisio Received at the City of Tukwila Permit Center by: Entered in Permits Plus on e-s- -U 8 \applications\forms- applications on line\revision submittal Created: 8 -13 -2004 Revised: Phone Number: PERMIT CENTER Bond Bond Company Name Bond Account Number Effective Date Expiration Date Cancel Date Impaired Date Bond Amount Received Date 2 AMERICAN CONTRACTORS INDEM CO 100018683 02/17/2007 Until Cancelled $12,000.00 02/26/2007 1 ACCREDITED SURETY It CAS CO 10034059 06/27/2005 Until Cancelled 02/17/2007 $12,000.0006/28 /2005 Name Role Effective Date Expiration Date OKITSU, RODNEY STERLING AGENT 06/28/2005 Amount OKITSU, RODNEY STERLING PRESIDENT 06/28/2005 CPP1002918 Insurance Company Name Policy Number Effective Date Expiration Date Cancel Date Impaired Date Amount Received Date 5 WESTERN NATIONAL ASSUR CO CPP1002918 10/13/200810/13 /2009 $1,000,000.0010 /13/2008 4 OHIO CAS INS CO BL053526359 08/13/200708/13 /2009 $1,000,000.0008 /11/2008 Untitled Page General /Specialty Contractor A business registered as a construction contractor with L&I to perform construction work within the scope of its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of account and carry general liability insurance. Business and Licensing Information Name Phone Address Suite /Apt. City State Zip County Business Type Parent Company OKITSU CONSTRUCTION INC 2067149969 1428 WHITWORTH AVE S RENTON WA 98055 KING CORPORATION UBI No. Status License No. License Type Effective Date Expiration Date Suspend Date Previous License Next License Associated License Specialty 1 Specialty 2 602515973 ACTIVE OKITSCI959L8 CONSTRUCTION CONTRACTOR 6/28/2005 6/28/2009 OKITSC*030R3 GENERAL UNUSED Business Owner Information Bond Information Insurance Information S • Page 1 of 2 https: // fortress .wa.gov /lni/bbip/Detail. aspx ?License= OKITSCI959L8 12/09/2008 FAN SCHEDULE TAG DESIGN BASIS LOCATION AREA /SYSTEM SERVED TYPE DRIVE FAN ELECTRICAL CHARACTERISTICS NOM UNIT •IZE (LxWxH, IN OPERATING WT (LBS) NOTES AIRFLOW (CFM) ESP (IN WC) RPM RPM VOLT/ PH BHP MOTOR (HP) STARTER FUSED DISC UNIT VOL CONTROL POWER SOURCE PTS OF CONN DIV 23 DIV 26 DIV 23 DIV 26 AEF -R.1 GREENHECK CSP ATM ROOM ATM ROOM CEIUNG DIRECT 380 0.5 1070 24x24 115/1 - 217 W 1 THUR 5 - X - CONSTANT NORMAL ONE (1) 14x18x14 40 1 TITUS 25RL SIDEWALL RETURN GRILLE SEE DRAWING 1/2* SPACING, 30 DEGREE DEFLECTION Y T WHITE 1 THRU 6 S ■ EEL G TTTUS 355ZRS EXHAUST GRILLE SEE DRAWING 1/2" SPACING, 0 DEGREE DEFLECTION ALUMINUM WHITE WHITE 1 THRU 6 1 THRU 6 H TITUS MLR -39 LINEAR SLOT RETURN 4' LONG 2 -SLOT, 1" WIDTH STEEL Heat pump control REF -R.2 CANFAB ROOF RTU -R.2 - POWER EXHASUTER DOWNBLAST BELT 4000 0.2 902 1750 208/3 Balancing Indicate balancing features on plans VFD - -- NM VFD BY DIV 15 NORMAL ONE (1) 48x36x24 400 1,4 REF -R.3 CANFAB ROOF RTU -R.3 - POWER EXHASUTER DOWNBLAST BELT 790 0.4 865 1750 208/3 1413 VFD ,, 1413.1 VFD BY DIV 15 NORMAL ONE (1) 42x30x22 300 1,4 Mr Econo Operation Indicate 100% capacity at 45 degF db & 40 deg F w b JC /RESTROOM /BREAKROOM DOWNBLAST BELT 730 0.5 1193 1725 1110131111 0.11 Integrated operation - - X IIII CONSTANT NORMAL ONE (1) 24 DIAx24 60 1 THRU 3 TEF -R.1 GREENHECK GB ROOF Indicate sealing necessary M00.02 Y „„ 1414.2 Duct insulation Indicate R -value of insulation on duct 111111111.1111.11111111111111 Y „ 11111111111111M Piping insulation Indicate R -value of insulation on piping m00.02 r ` ^ 1416 Completion Requirements NOTES: IN COMPLIANCE Wff-1 MECHANICAL AND ELECTRICAL CODE REQUIRED WORKING CLEARANCES. 4. PROVIDE WITH ROOFTOP UNIT, SEE RTU SCHEDULE. ROOF CURB. MOTORIZED DAMPER. 1416.2.1 Commissioning 5/20/2008 8:30 1. INSTALL 2. PROVIDE 3. PROVIDE DIFFUSER SCHEDULE TAG DESIGN BASIS DESCRIPTION MODULE SIZE FACE MATERIAL COLOR - - NOTES A TITUS OMNI CEILING DIFFUSER 24x24 SQUARE PLAQUE STEEL WHITE 1 THUR 5 B TITUS ML -38 W/ MPI -38 LINEAR SLOT DIFFUSER 4' LONG WI INSULATED PLENUM 2 -SLOT, 3/4" WIDTH PTS OF CONN WHITE 1 THUR 5 S 1 EEL C TITUS 272RS SIDEWALL SUPPLY GRILLE SEE DRAWING 3/4" SPACING, DOUBLE DEFLECTION STEEL WH ITE 1 THUR 5 D ACCUTHERM THERMA-FUSER CEIUNG DIFFUSER -VAV 24x24 SQUARE PLAQUE STEEL WHITE 1 THUR 5 E TITUS 50F RETURN /EXHAUST GRILLE SEE DRAWING 1/2 x 1/2 x 1/2 EGGCRATE ALUMINUM CORE, ALUMINUM BORDER WHITE 1 THRU 6 F TITUS 25RL SIDEWALL RETURN GRILLE SEE DRAWING 1/2* SPACING, 30 DEGREE DEFLECTION Y T WHITE 1 THRU 6 S ■ EEL G TTTUS 355ZRS EXHAUST GRILLE SEE DRAWING 1/2" SPACING, 0 DEGREE DEFLECTION ALUMINUM WHITE WHITE 1 THRU 6 1 THRU 6 H TITUS MLR -39 LINEAR SLOT RETURN 4' LONG 2 -SLOT, 1" WIDTH STEEL Heat pump control Indicate microprocessor on thermostat schedule NOTES: CONDENSATE PUMP, COORDINATE 1/8 HP 120V/1PH CONNECTION WITH DIV 26. 4. ROUTE REFRIGERANT LINES IN WALL. 7. PROVIDE 100% ECONOMIZER WITH MIXING BOX AND DELUXE MA CONTROLLER PUMPED CONDENSATE TO JANITOR'S CLOSET MOP SINK. 5. INSTALL UNIT PER MANUFACTURER'S SPECIFICATIONS. EQUIVALENT LENGTH OF REFRIGERANT LINES TO BE 100 FEET. 6. ROVIDE HFC REFRIGERANTS; R -410A 4/17/2008 8:17 1. PROVIDE 2. PROUTE 3. MAXIMUM Combustion htg. Indicate modulating or staged control NOTES: NC TO BE 35. 5. REVIEW ARCHITECTURAL REFLECTED CEILING PLANS FOR BORDER TYPES. TOTAL PRESSURE TO BE 0.1 W.G. 6. SIZE DUCT BRANCH CONNECTION PER GRILLE SIZE . INDICATED ON PLAN. CLEAR ANODIZED FINISH. COLOR WM-I ARCHIECT. 4/17/2008 8:17 1. MAX 2. MAX 3. PROVIDE 4. COORDINATE SPLIT SYSTEM HEAT PUMP UNIT SCHEDULE TAG FCU -1.1 DESIGN BASIS MITSUBISHI MSZ -A15 LOCATION ATM AREA SERVED ATM SUPPLY CFM 640 COOLING COOLING SEER - ELECTRICAL CHARACTERISTICS NOM UNIT SIZE (LxWxH, IN) OPERATING WT (LBS) NOTES TOTAL MBH 36 TOTAL MBH 4O VOLT/ PH 208/1 LOAD MCA MEMINIESI MOCP STARTER FUSED DISC UNIT VOL CONTROL POWER SOURCE PTS OF CONN DIV 23 X DIV 26 - DIV 23 -a- DIV 26 X CONSTANT NORMAL TWO (2) 31x60x14 130 1 THRU 5, 7 CU -R.1 MITSUBISHI PUMY -P36 ROOF ATM - 36 40 16 208/1 26 40 X - M00.01 x CONSTANT NORMAL ONE (1) 38x14x54 320 3 THRU 6 Y T 412.4 Automatic setback Indicate thermostat w ith night setback and 7 diff. day types Mo o . 0 n a „. 1412.4.1 Dampers Indicate damper location and auto. controls & max. leakage m00 . 0 Y „ 1412.4.2 Optimum Start Indicate optimum start controls n a. „ 1412.5 Heat pump control Indicate microprocessor on thermostat schedule NOTES: CONDENSATE PUMP, COORDINATE 1/8 HP 120V/1PH CONNECTION WITH DIV 26. 4. ROUTE REFRIGERANT LINES IN WALL. 7. PROVIDE 100% ECONOMIZER WITH MIXING BOX AND DELUXE MA CONTROLLER PUMPED CONDENSATE TO JANITOR'S CLOSET MOP SINK. 5. INSTALL UNIT PER MANUFACTURER'S SPECIFICATIONS. EQUIVALENT LENGTH OF REFRIGERANT LINES TO BE 100 FEET. 6. ROVIDE HFC REFRIGERANTS; R -410A 4/17/2008 8:17 1. PROVIDE 2. PROUTE 3. MAXIMUM LOUVER/RELIEF VENT SCHEDULE TAG DESIGN BASIS LOCATION AREA SERVED DUCT SIZE (IN) NOM UNIT SIZE (DIAxH, IN) AIRFLOW (CFM) OPERATING WT (LBS) NOTES GRV-R.1 GREENHECK GRSI -18 ROOF ATM ROOM 18 36DIAx12 3900 70 1 THRU 4 GRV-°-R.2 GREENHECK GRSR -18 ROOF CHILLER ROOM 18 36DIAx12 2000 30 1 THRU 4 n a 1411.1 Combustion htg. Indicate intermittent ignition, flue /draft damper & jacket loss 1412 HVAC controls NOTES: FAIL OPEN 24V MOTORIZED BACKDRAFT DAMPER. 3. PROVIDE GALVANIZED BIRDSCREEN. 12" HIGH ROOF CURB. 4. PROVIDE 0.5" THICK HOOD INSULATION. 4/23/2008 12:19 1. PROVIDE 2. PROVIDE NONRESIDENTIAL ENERGY CODE COMPLIANCE SCHEDULE COMPONENT INFORMATION THERMOSTAT DEADBAND CONTROL 5' F. THERMOSTAT AUTOMATIC SETBACK NIGHT SETBACK AND 7 DIFFERENT DAY TYPES COMPLY WITH STANDARD RS 18. SEALING DUCTWORK STATIC PRESSURE: 1/2" TO 3" ; SEAL TRANSVERSE JOINTS AND LONGITUDINAL SEAMS STATIC PRESSURE: ABOVE 3" ; SEAL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL PENETRATIONS DUCT INSULATION SUPPLY AND RETURN NOT WITHIN CONDITIONED SPACE: R -7 OUTSIDE AIR INTAKE WITHIN CONDITIONED SPACE: R-7 SUPPLY AND RETURN, OUTSIDE AIR INTAKE NOT WITHIN CONDITIONED SPACE; IN CONCRETE, IN GROUND: R -5.3 SUPPLY WITH SUPPLY AIR TEMP. < 55' F. OR >105' F. WITHIN CONDONED SPACE: R -3.3 PIPE INSULATION PIPING SHALL BE THERMALLY INSULATED IN ACCORDANCE WITH WASHINGTON STATE ENERGY CODE, 2006 EDITION, TABLE 14 -6 yes „ 3 /15/2006 1 Project Info Project Address BANK OF AMERICA Date 3.5.08 320 STRANDER BLVD. For Building Dept. Use TUKWILA, WA 98188 Applicant Name: GLUMAC Applicant Address: 1325 4TH AVE STE 1515, SEATTLE, WA 98101 Applicant Phone: 206,262.1010 Compliance Option 0 Simple System • Complex System Q Systems Analysis a (See Decision Flowchart (over) for qualifications. Use separate MECH- SUMfor simple & complex systems.) Mechanical Permit Plans Checklist K MECH -CHK Project Address BANK OF AMERICA - TUKWILA Date 3.5.08 The follow ing information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the Washinnton State Nonresidential Fnerav Code. Applicability (yes, no, n.a.) Code Section Component Information Required Location on Flans Building Department Notes HVAC REQUIREMENTS (Sections 14014424) 1411 Equipment performance yes „ 1411.4 Pkg. elec. htg.& clg, List heat pumps on schedule M00-02 yes „ 1411.1 Mnimum efficiency Equipment schedule with type. capacity, efficiency Mo 0. 02 n a 1411.1 Combustion htg. Indicate intermittent ignition, flue /draft damper & jacket loss 1412 HVAC controls Y ' 1412.1 Temperature zones Indicate locations on plans MO2.01 y ,, 1412.2 leadband control Indicate 5 degree deadband minimum M00.01 n.a. .r 1412.3 Humidity control Indicate humidistat Y T 412.4 Automatic setback Indicate thermostat w ith night setback and 7 diff. day types Mo o . 0 n a „. 1412.4.1 Dampers Indicate damper location and auto. controls & max. leakage m00 . 0 Y „ 1412.4.2 Optimum Start Indicate optimum start controls n a. „ 1412.5 Heat pump control Indicate microprocessor on thermostat schedule n.a. w 1412.6 Combustion htg. Indicate modulating or staged control Y- es „ 1412.7 Balancing Indicate balancing features on plans MO2.01 n.a. ,„ 1412.8 Ventilation Control Indicate demand control ventilation for high- occupancy areas n.e. -s 1422 Thermostat interlock Indicate thermostat interlock on plans Y 1423 Economizers Equipment schedule M00.02 1413 Air economizers ,, 1413.1 Air Econo Operation Indicate 100% capability on schedule Moo . 02 n a „ 1413.1 Mr Econo Operation Indicate 100% capacity at 45 degF db & 40 deg F w b n.a. „, 1413.2 Water Econo Doc Indicate clg load & w ater econoe & clg tow er performance yes 1413.3 Integrated operation Indicate capability for partial cooling M00.02 n a r 1413.4 Humidification Indicate direct evap or fog atomization w I air economizer 1414 Ducting systems Yes 1414.1 Duct sealing Indicate sealing necessary M00.02 Y „„ 1414.2 Duct insulation Indicate R -value of insulation on duct MO 0. 02 Y „ 1415.1 Piping insulation Indicate R -value of insulation on piping m00.02 r ` ^ 1416 Completion Requirements Y ,,, 1416.2.1 Commissioning Provide commissioning plan m00.01 yes „, 1416.2.2 -3 Sys.Bat & Func.Test Indicate air and w ater system balancing & functional testing MO 0.01 yes .' , 1416.2.4 Commissioning Indicate O &M manuals, record draw ings, staff training M00.01 yes - 1416.2.5 Comm. Report Indicate requirements for prelim. & final commissioning report MOO. 01 Separate air sys. Indicate separate systems on plans MO2.01 Y 1434 yes - " Mechanical Summary Form Completed and attached. Equipment schedule w ith types, input /output, efficiency, cfm, hp, economizer Moo . o 2 AREA SERVED WEST LOBBY SOUTH O NER NOM CAPACITY (TONS) 4 10 3 4 3 SUPPLY AIR FLOW (CFM) 1620 4000 1320 1760 1200 ESP (IN WG) 0.75 1 .0 0.8 1.0 0.5 OSA INTAKE (CFM) 360 1260 665 610 COOLING TOTAL SENS (MBH (MBH) 48.35 35.2 107.1 99.8 44.8 41.7 44.7 42.3 EAT (DB /WB) 73/63 76/62 77/65 74/61 LAT (DB /WB) 55/54 58/57 56/55 HEATING INPUT (MBH) 80 200 80 120 OUTPUT (MBH) 64 162 64 96 EAT (DB /WBI 59 46 59 108 AFUE ) ( %) 80 80 80 80 EER/ SEER VOLT/ PH MEIN ELECTRICAL CHARACTERISTICS 208/3 208/3 LOAD MOCP (MCA) 55.9 60 20.9 30 28.3 40 20.9 30 STARTER DIV 23 MEM X X 0 MEM DIV 26 FUSED DISC DIV 23 X X X DIV 26 MINIM UNIT VOL CONTROL CONSTANT CONSTANT CONSTANT CONSTANT CONSTANT POWER SOURCE NORMAL NORMAL NORMAL NORMAL NORMAL PTS OF CONN ONE (1) ONE (1) ONE (1) ONE (1) ONE (1) NOM UNIT SIZE (LxWxH, IN) 70x45x38 108x72x50 70x45x38 70x45x38 70x45x38 UNIT WEIGHT (LB) 800 2100 800 800 800 TAG RTU-R.1 RTU -R.2 RTU -R.3 RTU -R.4 RTU R.5 DESIGN BASIS TRANE YHC TRANE YHC TRANE YHC TRANE YHC TRANE THC LOCATION ROOF ROOF ROOF ROOF ROOF NOTES: 1. INSTALL IN COMPLIANCE WITH MECHANICAL AND ELECTRICAL CODE REQUIRED WORKING CLEARANCES. 2. PROVIDE PREMIUM EFFICIENCY MOTORS ON ALL FANS. 3. ALL UNITS TO BE HIGH EFFICIENCY. 4. PROVIDE SMOKE DETECTORS ON THE RETURN. PACKAGED ROOFTOP AIR CONDITIONING UNIT SCHEDULE 5. PROVIDE THROUGH- THE -CURB ELECTRICAL CONNECTION. 6. PROVIDE HFC REFRIGERANTS; R407C, or R - 410 7. PROVIDE POWER EXHAUST WITH 100% MODULATING ECONOMIZER, SEE FAN SCHEDULE. 8. PROVIDE 100% ECONOMIZER WITH BAROMETRIC RELIEF. . _ t �,.. ;)I� PU. I Au 6 2658 Em - f I,akkvwita SION NOTES 1,2,3,5,6,8 1 THRU 7 1 THRU 7 1,2,3,5,6,8 1,2,3,5,6,8 Project Description Briefly describe mechanical system type and features. Includes Plans PROJECT IS A NEW BRANCH BANK. HVAC SYSTEM CONSISTS OF MULTIPLE PACKAGED ROOFTOP GAS /ELECTRIC UNITS WITH 100% ECONOMIZERS & A DUCTLESS SPLIT SYSTEM HEAT PUMP TO SERVE THE FRONT VESTIBULE. Draw ings must contain notes requireing compliance w ith commissioning requirements - Section 1 416 RECEIVED CITY OF TUKWILA JUL 18 2008 PERMIT CENTER 4f' (Description I Scale SeallSignature Producfcn Copt Project Number 32.2177.089 Schedules - Mechanical ? 2006 Gensler z �' 1325 Fourth Ave, Suite 1515 Seattle, WA 98101 1'. 206.262.1010 F. 206.262.9865 M00.02 S outheenter Branch Relocation 320 Strander Blvd Tukwila, WA 98188 SERIAL NUMBER: NRSP VERSION: INCLUDES BULLETIN: Gensler Architecture, Design & Planning Worldwide G U MAC engineers for a sustainable future"' L 1 Rev Issue Date & Issue Description By Check 02/13/2008 Design Development MA / TM SPV / MAJ 04/30/2008 • CD Owner Review MA / TM SPV / MAJ 06/20/2008 Permit I Bid Set MA 1 TM SPV / MAJ SEAL OF q €NGR&EIING QUALITY av WO I Project Name Southcenter Branch Relocation 51 FA Job No.: 507023GEN Contact: Michael Aliaga www.glumac.com WA0049 2.0 21A [DrnrRes 03-24 -10 1 524 Fifth Avenue Suite 300 Seattle, WA 98101 Telephone 206.654.2100 Facsimile 206.654.2121 CENTRAL �8 �I - ii RTU —R. 6 "—A 120 E\ 26x20 16x12 NON 111 Ilk III; 14x14 12 6 " —D; -110 FCU -1.1 CONTROLLER 14x10 6 " —A -120 24x. ---E -190 :1 12 " —B -220 6x6 —F -80 III HMI IMO ■� 12x6 —B -240 C) 12`' - B -240 viR( \11 VE 1008 CD 12x6 —B -240 1 A08.02 6 " —A -100 24x1 0 8 " —A 8 "--A -220 (TYP 14) 16x16 —E --1300 nnlirlrrrnrl Fr rnr . rrrmrnu 6 "--A -100 10 " —A-300 24x 6---E -150 RTU —R.3 14x14—E-600 14x12 14x12 KIUT -K.5 Scale I Seal /Signature I Project Number 32.2177.089 Description ? 2006 Gensler 1325 Fourth Ave, Suite 1515 Seattle, WA 98101 T. 206.262.1010 F. 206.262.9865 # �� rr�� }S y tb� :23 x :AY L '� h iGA S outhcen ter Branch Relocation 320 Strander Blvd Tukwila, WA 98188 SERIAL NUMBER: WA0049 NRSP VERSION: 2.0 INCLUDES BULLETIN: 21A Gensler C i l_U IrYA engineers r en ineers for a sustainable future Rev Issue Date & Issue Description By Check 02/13/2008 Design Development MA / TM SPV 1 MAJ 04/30/2008 CD Owner Review MA 1 TM SPV / MAJ 06/20/2008 Permit / Bid Set MA 1 TM SPV / MAJ Project Engineer Project Name Southcenter Branch Relocation Level 01 Construction Plan - Mechanical Job No.: 507023GEN Contact: Michael Aliaga www.glumac.com 1524 Fifth Avenue Suite 300 Seattle, W.A. 98101 Telephone 206.654.2100 Facsimile 206.654.2121 EXFIRES 03 ---24 10 ATM 12x10 1 / (j�x8— E-215 �`(F 6 120 a 0 110 a' i1-S MO7.a1 R$ DUCT -E CE C ilk I (TYP) CE VAULT 12x12 —E --380 12x10 12x10—E-200 "0 UP TO RV —R.2 6 "---A -200 . I rrrTrrMEI =TIE= 6 " —A -120 \/A, LT LC 6 6Y " —A--80 SCALE: 1/4"— Q" 108 6" 6 " —A -160 LEVElARt TRUCTION PLAN - MECHANICA 8 " —A 300 T mrlrm Tarn ran r irrrrn nlrrr l 8x8 WC R (ri (TYP) R< V 18x10 —C -60 24x14 —E -1200 C.5 GENERAL NOTES A. COORDINATE ALL MECHANICAL WORK WITH THE ARCHITECTURAL, STRUCTURAL, AND ELECTRICAL PLANS. SHEET NOTES cip OUTLINE OF ROOFTOP EQUIPMENT ABOVE. 2. DUCTWORK UP TO PACKAGED ROOFTOP UNIT. SEE MO2.02. TRANSITION DUCT AS REQUIRED UP TO SUPPLIED RTU. . 12x12 UP TO EXHAUST FAN ON ROOF. FOR CONT. SEE MO2.02 4. RS 84 RL UP TO CONDENSER ON ROOF. 5. DSD IN DUCT RISER FURNISHED BY DIV. 26 AND INSTALLED BY DIV. 23. 6. SECURITY GRILLE LOCATION. SEE DETAIL 7 /MO7.01 7. MAINTAIN CLEARANCE FOR EQUIPMENT ACCESS PER LOCAL CODE AND MANUFACTURE'S INSTRUCTIONS. 8. PROVIDE OFFSET TO STEP IN STRUCTURE (COORD W/ ARCH AND STRUC). 9. COORDINATE SOFFIT CONSTRUCTION WITH ARCH. 10. ROUTE 6 "0 DUCT TO PRINTER CABINET AND BALANCE TO 100 CFM. 11. HVAC EMERGENCY SHUTDOWN BUTTON. ACTIVATION SHALL SHUTDOWN ALL MECHANICAL SYSTEMS. COORDINATE WITH CONTROLS AND ELECTRICAL. RECEIVED CITY OF TUKWILA JUL 18 2008 PERMIT CENTER (6) LLLLIUnuul U W1 L1 Iil:l 1119 LL1L1 Lu.tmV ■IL1L9 L1L1L- I MUM 9LL19 ROOF PLAN - MECHANICAL SCALE: 1 /8 " -1' -0" III 1.111111111INIIIIIII IIIIIIIIIIIIIIIIII I I I 111111111111111111111111111111111111 8' 16' - — t GENERAL NOTES A. COORDINATE ALL MECHANICAL WORK WITH THE ARCHITECTURAL, STRUCTURAL, AND ELECTRICAL PLANS. SHEET NOTES GD 1. MAINTAIN EQUIPMENT CLEARANCES PER MANUFACTURER'S INSTRUCTIONS. 2. REFRIGERANT LINES DOWN TO FCU. 3. PROPOSED LOCATION OF VFD. (COORD WITH DIV 26). RECEIVED (r - v nF TUKWILA , I I I 1 8 2008 RMiY CENTER er l� r < Southcenter Branch Relocation 320 Strander Blvd Tukwila, WA 98188 SERIAL NUMBER: WA0049 NRSP VERSION: 2.0 INCLUDES BULLETIN: 21A Gensler Architecture, Design & Planning Worldwide C LU NIAC engineers for a sustainable future' L 1325 Fourth Ave, Suite 1515 Seattle, WA 98101 '1'. 206.262.1010 F. 206.262.9865 Rev Issue Date & Issue Description By Check 02/13/2008 Design Development MA / TM SPV / MAJ 04/30/2008 CD Owner Review MA I TM SPV / MAJ 06/20/2008 Permit / Bid Set MA I TM SPV / MAJ SeallSignature I Project Name r q DOEAING QUALITY Production Dept Pro' Manager Pmpd Engineer Southcenter Branch Relocation Project Number 32.2177.089 Description Roof Plan - Mechanical I Scale MO2.02 ? 2006 Gensler B V s ty x g4 X7 a` Job No.: 501023G> N Contact: Michael Aliuga www.giumac.com 1524 Fifth Avenue Suite 300 Seattle, WA 98101 Telephone 206.654.2100 Facsimile 206.654.2121 EXPIRES 03-24-10 1 MAN R.C. PAD, BOLT THRU LEVEL PAD (TYP. OF 4) 6" EQUIPMENT RAILS NOTE: EXTERIOR GAS LINE TO HAVE 3/4" ARMAFLEX INSULATION WRAPPED WRAPPED W/ ALUMINUM JACKETING AND VAPOUR SEALED. CONDENSER UNIT DETAIL SCALE: NONE CONDENSING UNIT ON ROOF REFRIGERANT PIPING SCHEMATIC SCALE: NONE l EMIR aanr; ±urnr;,n;► nfitittlitt WALL — FOR TYPE REFER TO ARCH. DRAWINGS 1/4" MIN. GAP — FILL W/ CAULKING PIPE SUPPORT AT 48" OC (MAX), NEOPRENE COLLAR CLAMPED TO STRUT. PROVIDE 6" LONG SADDLE AROUND INSULATION. (TYP) TRAP AS REQUIRED BY EQUIPMENT MANUFACTURER LIQUID LINE SOLENOID VALVE, SPORLAN #ME— SERIES 1/2 "MIN. CLEARANCE — TYPICAL ALL AROUND 1/2" DEEP MASTIC SEAL TYP. BOTH SIDES GYPSUM VERMICULITE OR PERLITE INSULATION ALL AROUND NOTE: CU REFRIGERANT LIQUID LINE REFRIGERANT SUCTION LINE INSULATED ENTIRE LENGTH WITH ALUMINUM JACKET EXTERIOR TO BUILDING. RL X NOTE: SIZE REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS. SLEEVE ti j/jl /jiMA ....:. ,r >< RS-} a • • • • 3/4" GAS & 3/8" LIQUID REFRIGERANT LINES TO FC-1 GROUND LEVEL REFRIGERANT VALVE (TYP) FILTER DRIER, SPORLAN #C— SERIES WITH #RCW— SERIES CORE. VERIFY USE WITH EQUIPMENT MANUFACTURER. VIBRASORBER VIBRATION ISOLATOR (TYP) SIGHT GLASS, SPORLAN SA— SERIES THERMAL EXPANSION VALVE, SPORLAN #OVE— SERIES, WITH EQUALIZER. VERIFY USE WITH EQUIPMENT MANUFACTURER. DX COIL 1/4" GAP ALL AROUND CAULKING ALL AROUND 22GA RETAINING RING 1 //fv1IN.OVERLAP STAINLESS STEEL DUCT BAND MASTIC SEAL INSULATION (IF REQUIRED) Y. DUCT OR PIPE I SULATION ( REQUIRED) 22 GA. RETAINING FRAME OR RING BOTH SIDES OF WALL WHEN WALL IS HOLLOW, USE 22 GA SHEET METAL SLEEVE TO CONTAIN INSULATION 1. IF WALL IS FIRE RATED THE PACKING & SEALING MATERIALS AND SYSTEM INSTALLATION SHALL BE APPROVED BY THE FIRE MARSHALL. 2. COORDINATE SIZE & LOCATION OF PENETRATION WITH ARCHITECT AND /OR STRUCTURAL ENGINEER. DUCT OR PIPE WALL PENETRATION - TYPICAL SCALE: NONE AS REQUIRED 8" MINIMUM 12" MINIMUM PIPING SIZE AS INDICATED ON PLANS NOTE: SCALE: NONE ADDITIONAL SUPPORTS AS REQUIRED. SHEETMETAL BOOT WITH 1" ACOUSTICAL LINING. SUPPLY DIFFUSER SCALE: NONE 12" MINIMUM ti 4r4 4 10 .4 ROOF PENETRATION DETAIL 20 GAUGE SHEET METAL HOOD WITH 1-1/2" DUCT LINER INSIDE. SHEET METAL OR FLEX—TUBE COLLAR SEALED WATERTIGHT SECURE WITH #10 SCREWS (2 PER SIDE). SLOPE PIPES AWAY FROM HOOD. ROOFING BY ROOFING CONTRACTOR. 3" CANT STRIP. 1. REFER TO ARCHITECTURAL PLANS FOR ROOF CONSTRUCTION. 2. ALL EDGES SHALL BE ROLLED AND TURNED DOWN, SHARP EDGES WILL NOT BE ACCEPTED. 3. SEAL AS REQUIRED TO MAKE ALL JOINTS AND PENETRATIONS WATERTIGHT. 6 "MIN. CONICAL TAP ACOUSTICAL FLEX DUCT S.M. DUCT CEILING SUPPLY AIR ACOUSTICAL BOOT DETAIL UNIT UNION CONDENSATE DRAIN LINE WITH 3" TRAP 1" HIGH STUB OPEN TO ATMOSPHERE 5 2 1 /4" HILTI KIWK FLEX SCREWS PER HOLD DOWN CLIP 16 GAUGE "5" HOLD DOWN CLIP, 6" LONG, 4—PER UNIT (ONE PER SIDE) INSULATION COUNTER FLASHING BY MECHANICAL CONTRACTOR. FLASHING ROOFING ROOF BLOCKING — "M CANTS 3"MIN SCALE: NONE 1/2" DIA STAINLESS STEEL BARS. WELD AT EACH INTERSECTION 2"x1/4" STAINLESS STEEL FLAT BAR FRAME ASSEMBLY NOTE: SCALE: NONE DUCT NOTE: COORDINATE EXACT ROOF CONSTRUCTION MEANS AND METHODS WITH ARCHITECTURAL AND STRUCTURAL PLANS. 1. SIZE & LOCATION SHOWN ON PLANS 2. ALL WELDED CONSTRUCTION 3. USE FOR VERTICAL OR HORIZONTAL INSTALLATION SECURITY GRILLE UNIT BASE RAIL 1/2" X 2" NEOPRENE GASKET 2 0 1/4" HILTI KWIK FLEX SCREWS PER HOLD DOWN CLIP 16 GAUGE METAL ROOF CURB 4 "X FRT DF#1 LEVELING BLOCK. SHAPE TO LEVEL UNIT. 3" FLEXIBLE DUCT CONNECTION ROOF CURB DETAIL - WOOD ROOF 1/2" THRU BOLT, LOCK WASHER AND NUT AT 24" O.C. 2" ON CENTERS IN BOTH DIRECTIONS SECURE TO DUCT OR STRUCTURE, WITH SELF TAPPING SECURITY FASTENERS 5" ON CENTER. DUCT OR STRUCTURE PLUG WELD FLUSH TO SURFACE (TYP.) FRESH AIR WEATHERHOOD FACTORY ROOF CURB SCALE: NONE 1/2" X 2" NEOPRENE PAD ALL AROUND 1/4" HEX HEAD LAG BOLT INTO CURB (2 PER SIDE). ROOF DUCT r 3" MIN BLOCKING S .A. SCALE: NONE rI ROOF EXHAUST FAN r CONDENSATE DRAIN D R.A. DUCT THRU ROOF REFER TO MANE. FOR SIZE FLEXIBLE CONNECTION ROOFTOP UNIT DETAIL N WOOD 2 07.01 EXHAUST FAN NOTE: REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL INFORMATION. Arm t 1�1 a A its,‘ INSULATION ROOF ROOFING BY ROOFING CONTRACTOR 2" MIN HIGH FIRE TREATED DOUGLAS FIR #1 LEVELING BLOCK. SHAPE TO LEVEL UNIT. BACKDRAFT DAMPER 18 GAUGE STEEL CURB (8" HIGH MIN), CANTS AND COUNTER FLASHING BY MECHANICAL CONTRACTOR. 1/2" THRU BOLT, WASHER AND LOCKNUT (2 PER SIDE) THRU 2" X 4" FLAT BLOCKING AT PERIMETER. NAIL WITH 16d NAILS AT 6" OC TO FRAMING. Seal /Signature SEAL OF q ENGINEERING QUAIJTY Producton Copt I Project Name Southcenter Branch Relocation Project Number 32.2177.089 ay; EXPIRES 03 -24 -10 OPEN VENT TO ATMOSPHERE WITH PERFORATED (MINIMUM OF FOUR 1/8" HOLES) COPPER CAP. CAP SHALL BE REMOVABLE. 1% SLOPE (MIN) TRAP DEPTH SHALL BE 3" MINIMUM OR 1" GREATER THAN THE TOTAL STATIC PRESSURE OF THE SUPPLY FAN (IN.WG.), WHICHEVER IS GREATER. NOTES: CAPACITY SIZE UP TO 20 TONS 3/4" SCALE: NONE MINIMUM 1" ABOVE FLOOD RIM OF DRAIN PAN. UNIT WITH COIL DRAIN PAN DIELECTRIC UNION . TYPE "L" OR "M" COPPER TUBING WITH WROUGHT COPPER FITTINGS. 1. CONDENSATE PIPE TERMINATION SHALL BE LOCATED A MINIMUM OF 1" ABOVE THE FLOOD RIM OF AN APPROVED TRAPPED RECEPTOR, LANDSCAPING AREA OR OTHER LOCATION AS APPROVED BY THE AUTHORITY HAVING JURISDICTION. 2. ALL INTERIOR CONDENSATE DRAIN PIPING ABOVE CEILINGS SHALL BE INSULATED. 3. PROVIDE PIPE SUPPORTS AS REQUIRED TO MAINTAIN MINIMUM 1% SLOPE. 4. INSTALL TRAP PARALLEL TO UNIT, IF POSSIBLE. 5. MINIMUM CONDENSATE PIPE SIZES SHALL BE PER THE FOLLOWING TABLE UNLESS LARGER SIZE IS SHOWN ON PLANS OR AS REQUIRED BY AUTHORITY HAVING JURISDICTION AND /OR LOCAL BUILDING CODE REQUIREMENTS. COOLING COIL CONDENSATE TRAP USE 45' THROAT AT TAP SQUARE ELBOW WITH TURNING VANES ALLOWABLE IF DUCT VELOCITY IS LESS THAN 1500 FPM NOTE: CENTERLINE RADIUS EQUALS 1.5 TIMES "W". NO T.V.'S REQ'D. UNLESS OTHERWISE NOTED 15' TYP. 30' MAX. W/ PRIOR APPROVAL PROVIDE REDUCER UPSTREAM OF BRANCH INLET SIZE OF DUCT DROP TO MATCH NECK SIZE OF GRILLE (TYPICAL) SEE DETAILS. NO T.V.'S REQ'D. ON DUCT SIZES LESS THAN 16x10 IF DUCT VELOCITY IS LESS THAN 1500 FPM. USE RADIUS ELBOW IF VELOCITY EXCEEDS 1500 FPM. SPIN —IN FITTING W /VD OR 45' OVAL TAP PROVIDE REDUCER 0 CONNECTION TO GRILLE WHERE BRANCH DUCT IS OVERSIZED. SEE DETAILS. 1. PROVIDE DUCT LINER & /OR EXTERNAL DUCT INSULATION AS NOTED ON PLANS OR IN SPECIFICATIONS. 2. PROVIDE HANGERS AND SEISMIC BRACING PER SMACNA AND CODE REQUIREMENTS. 10' MAX. LENGTH. IF OVER 10' INCREASE ONE DUCT SIZE. TYPICAL LOW PRESSURE RETURN/ EXHAUST DUCT INSTALLATION DETAIL SCALE: NONE ROUND SHEET METAL DUCT LESS THAN 10' LONG FLEX CONN. 5' MAX LENGTH W /ONE 90' BEND REDUCER TO MATCH DIFFUSER NECK SIZE IF BRANCH DUCT IS OVERSIZED. LOCATE AT CONNECTION TO DIFFUSER. ROUND SHEET METAL DUCT. IF OVER 10' LG. INCREASE ONE DUCT SIZE VD TYPICAL ROUND NECK DIFFUSER. SEE DETAILS. FLEX CONN. 5' MAX LENGTH W /ONE 9O' BEND CONICAL SPIN —IN FITTING WITH V.D. VD TURNING VANES REQUIRED ON RECTANGULAR DUCT SYSTEM ELBOWS SQ. TO ROUND TRANSITION VD REDUCER 15' TYPICAL 30' MAX. W /PRIOR APPROVAL TYPICAL SQ. NECK DIFFUSER. SIZE OF DUCT DROP TO MATCH DIFFUSER NECK SIZE. SEE DETAILS. PLENUM ROUND DUCT < 5' MAX. LENGTH DOWNSTREAM OF REDUCER W/ ONE 90' BEND TRANS. FLEX VD N 45' OVAL TAP OR CONICAL SPIN —IN FITTING SPLITTER DAMPER WHERE SHOWN. DO NOTE: NOT USE ON VAV SYSTEMS 1. PROVIDE DUCT LINER & /OR EXTERNAL DUCT INSULATION AS NOTED ON RECEIVED PLANS OR IN SPECIFICATIONS. CITY OF TUKWILA 2. PROVIDE HANGERS AND SEISMIC BRACING PER SMACNA AND CODE REQUIREMENTS. JUL 1 8 2008 TYPICAL LOW PRESSURE SUPPLY ,'T CENT, DUCT INSTALLATION DETAIL SCALE: NONE 1325 Fourth Ave, Suite 1515 Seattle, WA 98101 '1'. 206.262.1010 F. 206.262.9865 Description Details - Mechanical !Scale 443 M07.01 ? 2005 Gensler R A 0 Southcenter Branch Relocation 320 Strander Blvd Tukwila, WA 98188 SERIAL NUMBER: WA0049 NRSP VERSION: 2.0 INCLUDES BULLETIN: 21A Gensler Architecture, Design & Planning Worldwide C «iiLU IVIPC r engineers for a sustainable future's Job No.: 507023G1;'N Contact: Michael Aliaga www.glumac.com Rev Issue Date & Issue Description L J 1524 Fifth Avenue Suite 300 Seattle, WA 98101 Telephone 206.654.2100 Facsimile 206.654.2121 By Check 02/13/2008 Design Development MA / TM SPV / MAJ 04/30/2008 CD Owner Review MA / TM SPV I MAJ 06/20/2008 Permit 1 Bid Set MA / TM SPV / MAJ