HomeMy WebLinkAboutPermit M08-219 - RPIRPI
12720 GATEWA
M08 -219
DR
Parcel No.: 1023049069
Address:
Suite No:
3311 S 120 PL TUKW
Tenant:
Name: RPI
Address: 3311 S 120 PL , TUKWILA WA
Owner:
Name:
Address:
Contact Person:
Name: KEO TORRE
Address: 727 S KENYON ST , SEATTLE WA
Contractor:
Name: EVERGREEN REFRIGERATION LLC
Address: 727 S KENYON ST , SEATTLE WA
Contractor License No: EVERGRL954R2
DESCRIPTION OF WORK:
INSTALL (4) PACKAGED HVAC ROOFTOP UNITS, 8 EXHAUST FANS, DUCTWORK, GRILLES,
DIFFUSERS AND (2) INTAKE HOODS
Value of Mechanical: $80,000.00
Type of Fire Protection:
Citylif Tukwila
SABEY CORPORATION
12201 TUKWILA INTL BLVD 4THFL , SEATTLE WA
Furnace: <100K BTU
>100K BTU
Floor Furnace
Suspended/Wall/Floor Mounted Heater
Appliance Vent
Repair or Addition to Heat/Refrig /Cooling System....
Air Handling Unit <10,000 CFM
>10,000 CFM
Evaporator Cooler
Ventilation Fan connected to single duct
Ventilation System
Hood and Duct
Incinerator: Domestic
Commercial/Industrial
doc: I MC -10/06
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
MECHANICAL PERMIT
EOUIPMENT TYPE AND QUANTITY
0
0
0
0
0
0
4
0
0
8
0
0
0
0
* *continued on next page **
M08 -219
Permit Number:
Issue Date:
Permit Expires On:
Phone:
Phone: 206 - 763 -1744
Phone: 206 763 -1744
Expiration Date: 01/06/2010
M08 -219
09/19/2008
03/18/2009
Fees Collected: $1,013.75
International Mechanical Code Edition: 2006
Boiler Compressor:
0 -3 HP /100,000 BTU 0
3 -15 HP /500,000 BTU 0
15 -30 HP /1,000,000 BTU.. 0
30 -50 HP /1,750,000 BTU.. 0
50+ HP/1,750,000 BTU 0
Fire Damper 0
Diffuser 0
Thermostat 4
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment 2
Printed: 09 -24 -2008
Permit Center Authorized Signature:
The granting of this permit
construction or the perfo
Signature:
Print Name:
doc: I MC - 10/06
d
S
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
es not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
e of work. I am authorized to sign and obtain this mechanical permit.
54171,
Date: - 1 - D-M
/tA
Permit Number: MO8 -219
Issue Date: 09/19/2008
Permit Expires On: 03/18/2009
Date: c - 2 / — o O
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
M08 -219 Printed: 09 -24 -2008
Parcel No.: 2716000070
Address:
Suite No:
doc: I MC - 10/06
12720 GATEWAY DR TUKW
CitAbf Tukwila
Tenant:
Name: RPI
Address: 12720 GATEWAY DR , TUKVW,A WA
Contact Person:
Name: KEO TORRE
Address: 727 S KENYON ST , SEATTLE WA
Value of Mechanical: $80,000.00
Type of Fire Protection:
Furnace: <100K BTU
>100K BTU
Floor Furnace
Suspended/Wall/Floor Mounted Heater
Appliance Vent
Repair or Addition to Heat/Refrig /Cooling System....
Air Handling Unit <10,000 CFM
>10,000 CFM
Evaporator Cooler
Ventilation Fan connected to single duct
Ventilation System
Hood and Duct
Incinerator: Domestic
Commercial/Industrial
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http://www.ci.tulcwila.wa.us
Owner:
Name: RREEF AMERICA REIT II CORP/
Address: PO BOX 4900 #207 , SCOTTSDALE AZ
Contractor:
Name: EVERGREEN REFRIGERATION LLC
Address: 727 S KENYON ST , SEATTLE WA
Contractor License No: EVERGRL954R2
MECHANICAL PERMIT
EQUIPMENT TYPE AND OUANTITY
0
0
0
0
0
0
4
0
0
8
0
0
0
0
* *continued on next page **
M08 -219
Permit Number:
Issue Date:
Permit Expires On:
DESCRIPTION OF WORK:
INSTALL (4) PACKAGED HVAC ROOFTOP UNITS, 8 EXHAUST FANS, DUCTWORK, GRILLES,
DIFFUSERS AND (2) INTAKE HOODS
Phone:
Phone: 206 - 763 -1744
Phone: 206 763 -1744
Expiration Date: 01/06/2010
M08 -219
09/19/2008
03/18/2009
Fees Collected: $1,013.75
International Mechanical Code Edition: 2006
Boiler Compressor:
0 -3 HP /100,000 BTU 0
3 -15 HP /500,000 BTU 0
15-30 HP /1,000,000 BTU.. 0
30 -50 HP/ 1,750,000 BTU.. 0
50+ HP /1,750,000 BTU 0
Fire Damper 0
Diffuser 0
Thermostat 4
Wood/Gas Stove 0
Water Heater 0
Emergency Generator 0
Other Mechanical Equipment 2
Printed: 09 -19 -2008
Permit Center Authorized Signature:
Print Name:
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
" /4 r'1 AA.DP/LScr7l/
Permit Number: M08 -219
Issue Date: 09/19/2008
Permit Expires On: 03/18/2009
LJJL • Date: r - Og
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the perfo ance of work. I am authorized to sign and obtain this mechanical permit.
Signature: '� ^— C Date: ( ,(?-0,g(
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: IMC -10/06 M08 -219 Printed: 09 -19 -2008
Parcel No.: 1023049069
Address: 3311 S 120 PL TUKW
Suite No:
Tenant: RPI
1: ** *BUILDING DEPARTMENT CONDITIONS * **
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
PERMIT CONDITIONS
Permit Number: M08 -219
Status: ISSUED
Applied Date: 09/04/2008
Issue Date: 09/19/2008
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
4: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
5: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the Cityof Tukwila
Permit Center.
6: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431 - 3670).
7: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
8: ** *FIRE DEPARTMENT CONDITIONS * **
9: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
10: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
11: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
12: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
13: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
14: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
15: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
doc: Cond -10/06
M08 -219 Printed: 09 -24 -2008
104.2)
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
16: An electrical permit from the City of Tukwila Building Department Permit Center (206- 431 -3670) is required for this
project.
17: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
18: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
19: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: Cond -10/06
* *continued on next page **
M08 -219 Printed: 09 -24 -2008
Signature:
Print Name:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
1 1
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating
construction or the performance of work.
514/17 4.0 erue
Date:
doc: Cond -10/06 M08 -219 Printed: 09 -24 -2008
Parcel No.: 2716000070
Address: 12720 GATEWAY DR TUKW
Suite No:
Tenant: RPI
1: ** *BUILDING DEPARTMENT CONDITIONS * **
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
PERMIT CONDITIONS
Permit Number: M08 -219
Status: ISSUED
Applied Date: 09/04/2008
Issue Date: 09/19/2008
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
4: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
5: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the Cityof Tukwila
Permit Center.
6: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431 - 3670).
7: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
8: ** *FIRE DEPARTMENT CONDITIONS * **
9: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
10: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
11: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
12: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
13: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
14: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
15: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
doc: Cond -10/06 M08 -219 Printed: 09 -19 -2008
104.2)
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
16: An electrical permit from the City of Tukwila Building Department Permit Center (206- 431 -3670) is required for this
project.
17: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
18: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
19: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: Cond - 10/06
* *continued on next page **
M08 -219 Printed: 09 -19 -2008
Signature:
Print Name:
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http : / /www.ci.tukwila.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating
construction or the performance of work.
sq,„.1A,
Date: r ^
doc: Cond -10/06 M08 -219 Printed: 09 -19 -2008
SITE LOCATION
121 LU Gai`^
1g- P
Property Owners Name: . p
' Reif /
pc Wi 1 j 6)
Site Address:
Tenant Name:
Mailing Address:
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
OG LE
72, 7 S ew+ sf
E -Mail Address: ` FV4/CI 1 fl ✓it
Name:
Mailing Address:
•
INFO
Contract())
Information onbacl
Company Name:
Mailing Address:
Zip
Contact Person:
E -Mail Address:
Contractor Registration Number: Expiration Date:
* *An original or notarized copy of current Washington State Contractor License must be presented at the time of permit issuance **
wet stamped by Architect. of R.ecor
Company Name:
Mailing Address:
City
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
ENGINEER OF RECORD - All plans must be wet stamped by Engineer. of Record
Company Name:
Mailing Address:
City
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
q: \\permits plus \icc changes \permit application (7 - 2004)
Revised: 6 -8 -05
bh
Page 1
Building Permit No.
Mechanical Permit No. moo- a t 9
Public Works Permit No.
Project No.
(For office use only)
King Co Assessor's Tax No.: 1 woo 70
co
Suite Number: - 7 , i 2..
City
Floor:
New Tenant: El Yes ❑ ..No
State
Zip
Day Telephone: "ub ( 1
ri44 .- 14 'Ma
City State Zip
Fax Number: 7,-A- -_ 7 G 1 Z 1
City
Day Telephone:
Fax Number:
State
State
State
Zip
Zip
Unit Type:
Qty
Unit Type:
Qty
Unit Type:
Qty
Boiler /Compressor:
Qty
Furnace <100K BTU
Air Handling Unit >10,000
CFM
Fire Damper
0 -3 HP /100,000 BTU
Furnace >100K BTU
Evaporator Cooler
Diffuser
3 -15 HP /500,000 BTU
Floor Furnace
Ventilation Fan Connected
to Single Duct
Q
O
Thermostat
y
15 -30 HP /1,000,000 BTU
Suspended/Wall/Floor
Mounted Heater
Ventilation System
Wood /Gas Stove
30 -50 HP /1,750,000 BTU
Appliance Vent
Hood and Duct
Water Heater
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Refrig/Cooling
System
Incinerator - Domestic
Emergency
Generator
Air Handling Unit
<10,000 CFM
Incinerator – Comm/Ind
Other Mechanical
Equipment
(..i(,(
MECHANICAL PERMIT INFORMATION — 206 - 431 -3670
MECHANICAL CONTRACTOR INFORMATION
tc v Fr/ -e/al rte., 1 r • ( urn
Contractor Registration Number: .GV EI?.-fel ri I �tZ
* *An original or notarized copy of current Washington State Contractor License must be presented at the time of permit issuance **
C ',
Valuation of Project (contractor's bid price): $ �O c 0
Scope of Work (please provide detailed information): 11 ") I I ( 1) f ' c '' q i, i 4 ✓ Aw c.P # Fl 61
' fh m i tt &'t 1;44,410 l i ( d 6'40 S tr inj CZ I Tell (-1 td,
Company Name:
Mailing Address:
Contact Person:
E -Mail Address:
Use: Residential: New .... ❑ Replacement .... ❑
Commercial: New ...tea.. Replacement .... ❑
Fuel Type: Electric ® Gas....[ Other:
Indicate type of mechanical work being installed and the quantity below:
plicable to all permits in' this appltcatio
Value of Construction – In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review – Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested
in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING 0 1g' O' i, THO ED AGENT:
Signature:
Print Name:
J Tort
Mailing Address: '1v1 5.
Date Application Expires:
?-- 9 -0
Date Application Accepted: 9
q:\ \permits plus \icc changes \permit application (7 -2004)
Revised: 6.8 -05
bh
Page 4
City State Zip
Day Telephone: 't!' _1 ' i y c f
Fax Number: 'Z-s - 74. ? — Z 1 c)
Expiration Date: I C/ /" d
Day Telephone:
City
Wf- X121 (� C1
Date: 4 1 / y / v B
= 710
State
Staff Initials: , I , n
g'Truce'
Zip
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 2716000070 Permit Number: M08 -219
Address: 12720 GATEWAY DR TUKW Status: PENDING
Suite No: Applied Date: 09/04/2008
Applicant: RPI Issue Date:
Receipt No.: R08 -03138
Initials: WER Payment Date: 09/04/2008 02:41 PM
User ID: 1655 Balance: $0.00
Payee: EVERGREEN REFRIGERATION
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 003221 1,013.75
ACCOUNT ITEM LIST:
Description
MECHANICAL - NONRES
PLAN CHECK - NONRES
Account Code Current Pmts
000.322.102.00.0 811.00
000/345.830 202.75
Total: $1,013.75
Payment Amount: $1,013.75
P19 39/04 ?707 TOTAL 103Z 73
I 00-
doc: Receipt -06 Printed: 09 -04 -2008
COMMENTS:
c lj5 WO Ve SIN di,) -- A P41/0 0
Typeraf Inspection: �� �
�
P � � ,re w`i J 4 `4 sA kol,eN14✓45 15
Zt -f
j P e , r v, 0 V 1 c E F; N 1
Address:
1 .
12Q9L
Date Called:
Special Inst_ructions:
Date Wa ted:
1 1 � .1 c1
oject:
Typeraf Inspection: �� �
�
Zt -f
Address:
1 .
12Q9L
Date Called:
Special Inst_ructions:
Date Wa ted:
1 1 � .1 c1
8
Cart1
P.m.
Requester.
Phone No
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA BUILDING DIVISION
63 00 Southcenter Blvd., #100, Tukwila, WA 98188
PERMIT NO.
(206)431 -3670
Inspecto is i Date:
\ idtA 1 1 , 15 I '-
REINSPECTION FEE REQ (RED. Prior to inspection, fee must be
6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
❑.$60.
paid
(Receipt
TZ Rpproved per applicable codes. Corrections required prior to approval.
'Date:
Project: .j
cf 45 a X74
Type of Inspection:
.�� a .- ...541/1.
Address:
'3 // . S i,2-0 r'L
Date Called:
Special Instructions:
n _
X 2/11
,fix ,J763 - - /7 4/ y
Date Wanted:
/ /- IS -dZ)
a.m.
A.
Requester:
Phone No:
.2.1) e - 6 7 F- 765
D Approved per applicable cones
/14g / 9
INSPECTION RECORD
Retain a d opy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431-
Corrections required prior to approval.
COMMENTS:
,2c 35 3 8,6
CA-kfai / «/7 Ad e°
t
nspecto
t No.:
Date:
60. 0 REINSPECTION ` E REQ� #RED. Prior to inspection, fee must be
paiat 6300 Southcenter : lvd.,,Suite 100. Call to schedule reinspection.
Date:
Project:
Type of Inspection:
Add ( 1 SoU `
17 0 V 1p_ Date
Called:
Special Instructions:
a 0 (
,S{
/ 2Tt/S e
Date Wanted:
a.m.
Requester:
Gti
INSP
INSPECTION RECORD
Retain a copy with permit
Q -2I1
PERMIT NO.
ON NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
D Approved per applicable codes. u " Corrections required prior to approval.
COMMENTS:
8,01.4e,X• 11 c.
/1.49
/5 I I-- J /t/ C._._ c4
/--
, J
''p ,L I .off 7®, , k7'4 1
1 t7 s ue. /,/ :4-
j
€- J- � Ir> ev / , 6
/, I,.o.�,/ 4,
"kelt, . ;
Inspect r :
El $60.1 1 REINSPECTI0 FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Ite2 y - oo
Receipt No.:
'Date:
ProJec
Type of Inspection: ;w
Address:
2 ? 1 S Z a P L._
Date Called :,ry��_ !- .
tKK �/
—
Special Instructions:
Date Wanted:
" - 7..
"C1 d
6a): m.
Requester:
Phone No:
INSPECTION RECORD
Retain a copy with permit t' ,art we 2
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION R-
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
El Approved per applicable codes.
❑ Corrections required prior to approval.
COMMENTS:
A
Inspector:
(Date:
J
$60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
'Date:
Project: 7 T
Type of r Ins ection: /l
tirlipv
v
Addv / / S / . fin 1
c 3 4CJ �"
Date Called:
Special Instructions:
Date Wanted:
.m.
Requester:
Phone No:
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA BUILDING DIVISION f1
5
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 - 6
may'
PERMIT NO.
COM TS:
Inspector:
2
0 ' 0 REINSPEG ION FEE ' EQ - RED. Prior to inspection fee must be
d at 6300 Southcenter s vd., = uite 100. Call to schedule reinspection.
Re&2c ipt No.:
'Date:
pproved per applicable codes. Corrections required prior to approval.
iJ IJ STRUCTURAL
ENGINEERS
Engineers Northwest Inc., P.S.
Mob - zict
August 29, 2008
ENW Project No. 99- 149007
CODE: 2006 IBC
WIND: 85 mph (3 Second Gust)
Exposure "B"
SEISMIC: S = 1.501 SDS = 1.001
S = 0.518 SD1 = 0.518
Seismic Design Category D
SNOW: 25 psf
^ a
.72 C . 7r1 q
id f8a.
RR' "T.I:
INTERGATE EAST BUILDING 2
3311 S
Tukwila, WA 98169
ROOFTOP HVAC ADDITION
STRUCTURAL CALCULATIONS
i ce .- .. ^
REVIEWED FOR 1
CODE COMPLIANCE
APPS' £ VED
SEP 1 8 2008
City Of Tukwila
alai
BUILDING DIVISION
RECEIVED
. SEP 04 2008
PERMIT CENTEF,
6869 Woodlawn Avenue NE . Seattle, WA 98115
206.525.7560 . fax 206.522.6698
www.enwseattle.com
Rfl T. /
,
O
: .<\<<
$�.1�.;
.: a I�
' \> %-. r i !/
v j
j? != , 1 � Y +
" ' x
e °' !' ` v
4fr
DWN: D.G.
ENG'D:H.PANGELJNAN
PARTIAL ROOF FRAMING PLAN
JOB NO: 99
'
DATE: 8 -29 -08
!' 2184 � W
,' STRU • v .
I ONAL -
'
SHEET:
S 1 • O 1
,
ENGINEERS NORTHWEST, INC.
6869 WOODLAWN AVE. N.E.
SEATTLE, WASHINGTON 98115
C
8
PARTIAL ROOF FRAMING PL N
- = 1' -0-
1. VERIFY ALL DIMENSIONS & ELEVATIONS w /ARCH.
2. ALL ITEMS ARE NEW (N) UNLESS NOTED AS EXISTING (E).
3. VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION. NOTIFY ENW IF EXISTING CONDITIONS ARE
NOT AS SHOWN ON DRAWINGS.
0
60' -0'
8' -10'
6' -0'
W
tg
o
f0
*
es
O
x
&
EXIST
i i
N
o
m
Es
o
j
R
EXI
TYP.
EXIST.
U.N.O.
6x36
NEW
e x
157
-'
1
/.
N
T
o
ro
4
O.
6
.:
0
=
x
LE
EXIST.
_
�'
NEW
AC
48 [
HU48
TYP.
EXIST"
2
157 '/
6ix21
6x36 - \
NEW
N
w
0
co
0
=
a
c
EXIST.
F -3.1
IYP
�■11-
1DD
AS
TYP.
SIMPSON
LOC{PTIONS
6 PLAC
SHOWN
1575#
MAX
es
6x36,
EXIST
6jx2
EXIST. 4x8 D.F.
#2
-3.1
TYP
IV
® 8' -0' MAX.
TYP. ,
I
N
C
8
PARTIAL ROOF FRAMING PL N
- = 1' -0-
1. VERIFY ALL DIMENSIONS & ELEVATIONS w /ARCH.
2. ALL ITEMS ARE NEW (N) UNLESS NOTED AS EXISTING (E).
3. VERIFY EXISTING CONDITIONS PRIOR TO CONSTRUCTION. NOTIFY ENW IF EXISTING CONDITIONS ARE
NOT AS SHOWN ON DRAWINGS.
0
.0 7:r.
KAE `
DWN: D.G.
Q ti ii, . o ' 1
1 n
-4. ..
% G r 21 , ' '
8
SiRU� �
� sl ONAL Erb'
"' `13,,q—o2.
ENG'D: H.PANGEUNAN
SECTION F -3.1
JOB NO: 99149007
DATE: 8 -29 -08
SHEET:
S 3 i _ 1
ENGINEERS NORTHWEST, INC.
6869 WOODLAWN � AVE. N.E.
SEATTLE, WASHINGTON 98115
•
GALV. 8— "0 LAG BOLTS
(3 EA SID )
NOTE: -
4 -4 "0 LAG BOLTS
AC -4 (1 ® EA. CORNER)
ogrNN
rich
r / //,
FAMMAV
XMAWO
.iii,
OWEN
OWWNN
OW NRA
' :mom
iii
W IMP
02100 • .r
LOCATE C.G. OVER
GLB
EXIST. GLB PER
PLAN
SECTION F -3.1
EXIST. 4x ® NEW 4x8 DF #2
8' -0 "o /c w /HU HGRS EA
END
i " 1' -O"
MECH. UNIT BY
OTHERS
ATTACH UNIT TO
CURB PER MFR'S
RECOMMENDATIONS
CURB BY OTHERS
4x P.T. TYP.
ENW ENGINEERS NORTHWEST, INC., P.S. ^ STRUCTURAL ENGINEERS
• 6869 WOODLAWN AVE. N. E., #205, SEATTLE, WA 98115 (206) 525 -7560 FAX (206) 522-6698
•
•
PROJECT # PROJECT RPL TT • DATE
SUBJECT SHEET / OF
BY
- M/N
E�/st
4x/4- Rou ;/{ 61 �''•
Dr 4' 2 'D.�/" E
A. 50. 2°j //v'
S = //4. 2
77 13. L3
1
• L o cd
/b-
zI1 P , �
c.. .
/N
/N
o� vw/
$, (./. 12 00 Fi "EG
z 4 el 24
/A/S ✓
owl
4•4 I4 •, • r2' "s`
s/'a - /Nk
A cLN
/Y/ /SG
2011.0#
t 33o d
G/✓ cf;c-R f /IV4c
0.7t
o.�psl
/ S
2. rs
a s
I. 04
"7- o p,f -f GL.13
W D�- t�SiVo = �b -rZS�� 28a
ISO
1'6= C, 5 c CZ Cr.
B 12.0 (1.,5) (Lod 1 , o - 13A�,� Ai
ov& x 4 rs . ; / too Ai-el Avo / p a.,t - ew 3r gk
0) ENW
• '
•
PROJECT # PROJECT gf - Tl DATE
SUBJECT ,.o .0 r T'P 4N /?•S SHEET . OF
BY
we
(iv-f z s 4- t 95 = 8'5 5
(� o. 5ti4 S ( 42-.3 4- 18.15
rf
tV' D1,ac,
A/ o c/A1 11"
( M)DMCI
ENGINEERS NORTHWEST, INC., P.S. STRUCTURAL ENGINEERS
11
v
6869 WOODLAWN AVE. N. E., #205, SEATTLE, WA 98115 (206) 5257560 FAx (206) 522 -6698
/1c -oNS ca./ vs G. , (¢J , al)
L o cA'fm. UNIT o E" rLA 'I l�
(34 Gk, Si*"/ orv14
Gv r.gvD -I
(e) c.' /4x 3 /4 le '`
L . __.._._... -. ( Esc 333 r , - -
1
4z 3q# 2.83" 55.1 t'
4 o'
w� reri- 434o* 94.)O e(
GNcc& $NS7o1L
VmAw
2� u-11 PTA- rc-OcU4 cN��t�L
3
tic= Z (2 8. It 37
2 3
(& (o /4x zJ
2'1
4 rt 2 6.9 (3') % Z-6. 14
P ti 0.87S (z9X..)12.7r
(5) G 3 /4x 74
24-r pr/or VI?
f b = 24oe r
A = 24.3 /A.)
S* /4 55 /N
O - # 2 $ . > 2 . r 35 gm ear
r,,. 1•is- (o44,1'); 1b93)
•1� k,
ENW ENGINEERS NORTHWEST, INC., P.S. ^' STRUCTURAL ENGINEERS
® ) 6869 WOODLAWN Ave. N. E.. #205, SEATTLE, WA 98115 (206) 525 -7560 FAx (206) 5226698
•
PROJECT # PROJECT g PI T i
SUBJECT SHEET 3 OF
(E) (0
CNEk FL jg M- 2197
(E (0 1/4.- -
p= .183 -(01- 2.24)4 kS� < b' /. �S z400) (o. 3 •
446.12.1
! 46
Ca) 6 I
L -i�
11./ 5i K •lit t 4-6-25- � ?II .51
V MA1c' 12•0 t O. . = 1/• *''t! k-
UNiT
DATE
BY
,-+ 1Z °.1 (
w� ( ,) ( G 9T� ` 4g I O. �70Z
UAn1 Co) - rowel
4210
A. 14-1 - Id L
5 = 4°14.12 s IN
c i; 98. S 1(It) Z.35 9 Ic,; = I• Itt i4oa> o.89 °47) = 2.45-e 0 1-
Its
5"`) 0,11161 F 0.14s x( .IS = 0.11377r frs ok
141.4 s
�,I v l
c as‘ o./ I °•
ENW
•
PROJECT #
•
Iq`
(z ! f¢.oM
ENGINEERS NORTHWEST, INC., P.S. — STRUCTURAL ENGINEERS
SUBJECT SHEET 4 OF
PROJECT
&.i3 G1 G-/) BY
p�.g)' ' (ia
(E')
6869 WOODLAWN AVE. N. E., #205, SEATTLE, WA 98115 (206) 525-7560 FAX (206) 522-6698
RFT !1
CNZ�K M!0 SP.v/•-/
\11 4 4 9
# rrA
�6 LgO. S 22Z(a kf� /u G1 l �1�2.zr k
IfSB _nv
12 .f
TK-'7` ) F2-0
M/
�l max= °°' SA4 ` /
/ „,,m 26.4.142. k.-1; —_. G 2.14T k
GN`Ck UG1 1” F
30.1-0'5 1 v' i c3 0.7 3 ( R> J
243
DATE
•� r b - 2. Z! k) '
0. 173 ks;
r/i 0,189,
d II
®t
•
ENW
PROJECT # PROJECT RP( T
SUBJECT
[3.th—s-q) 4z .rf
4 ssJ j
9.1 l:)
ENGINEERS NORTHWEST, INC., P.S. STRUCTURAL ENGINEERS
GL6 ALasti' Ci 2.,t!
■
6869 WOODLAWN AVE. N. E., #205, SEATTLE, WA 98115 (206) 525-7560 FAx (206) 522 -6698
- 11 2 413: 25.41
8 P 9 fi 4o = `lYztp4
G v ,
•45°--4 84G<< SPAN QrucY
V 4 3°- '
/Cam f i.w
DATE
SHEET S OF
BY
f r ZQr
'L3s(zs t�� r 3 13.41'
•
•
ENW
•
PROJECT # PROJECT RFC r1 . DATE //--
SUBJECT /✓Vroc . -, r '- SHEET 6 P OF
BY
ENGINEERS NORTHWEST, INC., P.S. STRUCTURAL ENGINEERS
50 1 C ( = 0.7 (0. 0,, oo ") /
r mA "
r - O.`F (2.$) / .ao/ w /i
/ 4 "
1t///V/7 CnJT9cLN
�vrc f CUPc. IF r=
6869 WOODLAWN AVE. N. E., #205, SEATTLE, WA 98115 (206) 525-7560 FAx (206) 5226698
1.J/it/Of SS rim / ,1/4,? ' 3"
Ar z 35
Qr a 0inv.( 0.13) (,. o> (o- B- ('. o,= /1. 977 rs f
r I G c r
ri.¢7 -7)(6.a i3 (i -9)=' 24. /
0. � (6, (,) 6. 00
7 •LAS'
/.12
n f.A.1 fp O.S t /& ou Yj01,
tt
I/ r9 /' s ,o� s 56.) U
lI S9 (3') — 0. (s (I 5 ti ), 4.133)
9. S
Cri
7fA'EboeV
4 =0, 434 / t. EmaarctiJ`
Cooling Equipment Schedule
Equip.
ID
Brand Name'
Model No.'
Capacity
Btu/h
Total CFM
OSA CFM
or Econo?
SEER
or EER
IPLV
Location
RTU -1
LENNOX
TGA150S2BH
145000
5000
1000
9.5EER
192000
ROOF
RTU -2
LENNOX
TGA15OS2BH
145000
5000
1000
9.5EER
192000
ROOF
RTU -3
LENNOX
TGA150S2BH
145000
5000
1000
9.5EER
192000
ROOF
RTU -4
LENNOX
TGA048S2DM
50000
1135
320
13SEER
84000
ROOF
PERMIT CEN1
a.
I 4
Heating Equipment Schedule
Equip.
ID
Brand Name'
Model No.'
Capacity
Btu/h
Total CFM
OSA cfm
or Econo?
Input Btuh
Output Btuh
Efficiency
RTU -1
LENNOX
TGA150S2BH
192000
5000
1000
240000
192000
80.000
RTU -2
LENNOX
TGA15OS2BH
192000
5000
1000
240000
192000
80.000
RTU -3
LENNOX
TGA150S2BH
192000
5000
1000
240000
192000
80.000
RTU -4
LENNOX
TGAO48S2DM
84000
1135
320
105000
84000
80.000
PERMIT CEN1
a.
I 4
Fan Equipment Schedule
Equip.
ID
Brand Name'
Model No.'
CFM
Sp'
HP /BHP
Flow Control
Location of Service
REF
1,2,3,4
ILO
CRBA 13
2300
0.25
1 /2HP
REF -5,5
ILG
CRBA 24
5600
0.25
1 /8HP
Applicant
PP
EI
RECEIVE'
EF
1,2,3
BROAN
L150
130
0.38
1.4A
-f
PRA
��]
SF 04
PERMIT CEN1
a.
I 4
Project Info
Project Address
RPI
Date 9/4/2008
33 11 S 1).0 ? i
For Building Dept. Use
Tukwila, WA
Applicant Name:
Evergreen Refrigeration
rt f"nu
Applicant
PP
727 S Kenyon St.
{
Applicant Phone:
206- 763 -1744 -
-f
PRA
•
•
•
2006 Washington State Nonresidential Energy Code Compliance Forms
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Summary
MECH -SUM
L
Revised July 2007
Project Description
Briefly describe mechanical
system type and features.
❑ Includes Plans
Compliance Option
Include documentation requiring compliance with commissioning requirerr
Install (4) rooftop packaged HVAC units and.($), -ceo
K! 1/ (2)
QQ Simple System 0 Complex System Q Systems Ahalys City Of Tukwila_ ..
(See Decision Flowchart (over) for qualifications. Use separate MECH -S M 3, i'I'i YID
ents, ecaRF14t'6. 2008
1503 1":1-91.
PPRovE®
Equipment Schedules
The following information is required to be incorporated with the mechanical equipment schedules on the
plans. For projects without plans, fill in the required information below.
'If available. 2 As tested according to Table 14 -1A through 14 -1G. 3 If required. ° COP, HSPF Combustion Efficiency, or AFUE, as
ER
•
•
•
avallaule. na I C O L C U awvi anG New L & O f d u rn v � Y ' , & iP,rtse. ilsf i , 1-111LACI y I.J1 n, VI-, as
applicable. 5 Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS).
System Description
See Section 1421 for full description
of Simple System qualifications.
If Heating/Cooling
or Cooling Only:
❑ Constant vol?
❑ Split system?
❑ Air cooled? .i Packaged sys? ❑ <20,000 Btuh?
❑ Economizer included?
If Heating Only:
9 Y
❑ <5000 cfm?
❑ <70 /o outside air?
<70%
•
•
Mechanical S O mmary (back)
MECH -SUM
Decision Flowchart
Use this flowchart to determine if project qualifies for Simple System Option. If not, either the
Complex System or Systems Analysis Options must be used.
2006 Washington State Nonresidential Energy Code Compliance Form
<5000
cfm?
Simple System
Allowed
(section 1420)
Air Cooled,
Constant Vol?
ingle
Package
Unit?
Econo
Included?
<70% OSA
<20,000
otal Ca .
wo economize
<240,000 Btuh
or 10 %?
Use Complex
Systems
(section 1430)
plit Syste
<= 84,000
Btuh?
Outd
or
Adjacent to
utdoor
ool Ca
<54,000
Btuh?
Heating Only
Reference
Section 1421
Yes -
Yes*
Heating/Cooling
or Cooling Only
Yes
Yes
Yes
No
Complex Systems
Refer to MECH -COMP Mechanical Complex Systems for assistance in determining which
Complex Systems requirements are applicable to this project.
Mechanical Permit Plans
2006 Washington State Nonresidential Energy Code Compliance Forms
Checklist
I ,
MECH -CHK
Revised July 2007
Project Address RPI 'Date
9/4/2008
The following information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the
Washington State Nonresidential Energy Code.
Applicability
(yes, no, n.a.)
Code I
Section
Component I
Information Required I
Location I
on Plans
Building Department
Notes
HVAC REQUIREMENTS (Sections 1401 -1424)
1411
Equipment performance
1411.4
Pkg. elec. htg.& clg.
List heat pumps on schedule
1411.1
Minimum efficiency
Equipment schedule with type, capacity, efficiency
Ml
1411.1
Combustion htg.
Indicate intermittent ignition, flue/draft damper & jacket loss
1412
HVAC controls
1412.1
Temperature zones
Indicate locations on plans
Ml, M2
1412.2
Deadband control
Indicate 5 degree deadband minimum
Ml
1412.3
Humidity control
Indicate humidistat
1412.4
Automatic setback
Indicate thermostat with night setback and 7 diff. day types
Ml
1412.4.1
Dampers
Indicate damper location and auto. controls & max. leakage
Ml
1412.4.2
Optimum Start
Indicate optimum start controls
1412.5
Heat pump control
Indicate microprocessor on thermostat schedule
1412.6
Combustion htg.
Indicate modulating or staged control
1412.7
Balancing
Indicate balancing features on plans
Ml
1412.8
Ventilation Control
Indicate demand control ventilation for high - occupancy areas
1422
Thermostat interlock
Indicate thermostat interlock on plans
1423
Economizers
Equipment schedule
1413
Air economizers
1413.1
Air Econo Operation
Indicate 100% capability on schedule
1413.1
Wtr Econo Operation
Indicate 100% capacity at 45 degF db & 40 deg F wb
1413.2
Water Econo Doc
Indicate clg load & water econoe & clg tower performance
1413.3
Integrated operation
Indicate capability for partial cooling
1413.4
Humidification Indicate direct evap or fog atomization w/ air economizer
1414
Ducting systems
1414.1
Duct sealing
Indicate sealing necessary
Ml
1414.2
Duct insulation
Indicate R -value of insulation on duct
Ml
1415.1
Piping insulation
Indicate R -value of insulation on piping
1416
Completion Requirements
1416.2.1
Commissioning
Provide commissioning plan
1416.2.2 -3
Sys.Bal & Func.Test
Indicate air and water system balancing & functional testing
1416.2.4
Commissioning
Indicate O &M manuals, record drawings, staff training
1416.2.5
Comm. Report
Indicate requirements for prelim. & final commissioning report
Ml
1434
Separate air sys.
indicate separate systems on plans
' Mechanical
S Form
Completed and attached. Equipment schedule with types,
input/output, efficiency, cfm, hp, economizer IM1
SERVICE WATER HEATING AND HEATED POOLS (Sections 1440 -1454)
1440
Service water htg.
1441
Elec. water heater
Indicate R -10 insulation under tank
1442
Shut -off controls
Indicate automatic shut -off
1443
Pipe Insulation
Indicate R -value of insulation on piping
1452
Heat Pump COP
Indicate minimum COP of 4.0
1452
Heater Efficiency
Indicate pool heater efficiency
1453
Pool heater controls
Indicate switch and 65 degree control
1454
Pool covers
Indicate vapor retardant cover
1454
Pools 90+ degrees
Indicate R -12 pool cover
2006 Washington State Nonresidential Energy Code Compliance Form
•
•
•
2006 Washington State Nonresidential Energy Code Compliance Form
If "no" is circled for any question, provide explanation:
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Permit Plans Checklist
MECH -CHK
2006 Washington State Nonresidential Energy Code Compliance Forms
Revised July 2007
Mechanical - General Requirements
1411.1 General: Equipment shall have a minimum performance at the specified
rating conditions not less than the values shown in Table 14-1A through 14 -1G. If a
rating recognized certification program exists for a product covered in Tables
4 -1A through 14-1G, and it includes provisions for verification and challenge of
equipment efficiency ratings, then the product shall be listed in the certification
program.
Gas -fired and oil -fired forced air furnaces with input ratings > 225,000 Btu/h (65
kW) and all unit heaters shall also have an intermittent ignition or interrupted device
(IID), and have either mechanical draft (including power venting) or a flue damper. A
vent damper is an acceptable alternative to a flue damper for furnaces where
combustion air is drawn from the conditioned space. All furnaces with input ratings >
225,000 Btu/h (65 kW), including electric furnaces, that are not located within the
conditioned space shall have jacket losses not exceeding 0.75% of the input rating.
1411.2 Rating Conditions: Cooling equipment shall be rated at ARI test conditions
and procedures when available. Where no applicable procedures exist, data shall
be furnished by the equipment manufacturer.
1411.3 Combination Space and Service Water Heating: For combination space
and service water heaters with a principal function of providing space heat, the
Combined Annual Efficiency (CAE) may be calculated by using ASHRAE Standard
124 -1991. Storage water heaters used in combination space heat and water heat
applications shall have either an Energy FActor (EF) or a CAE of not less than the
following:
1411.4 Packaged Electric Heating and Coo ing Equipment: Packaged electric
equipment providing both heating and cooling with a total cooling capacity greater
than 20, Btu/h shall be a heat pump.
Exception: Unstaffed equipment shaelters or cabinets used solely for
personal wireless service facilities.
1412 Controls
1412.1 Temperature Controls: Each system shall be provided with at least one
temperature control device. Each zone shall be controlled by individual thermostatic
controls responding to temperature within the zone. At a minimum, each floor of a
building shall be considered as a separate zone.
1 412.2 Deadband Controls: When used to control both comfort heating and
ooling, zone thermostatic controls shall be capable of a deadband of at least 5
degrees F within which the supply of heating and cooling energy to the zone is shut
off or reduced to a minimum.
Exceptions:
1. Special occupancy, special usage, or code requirements where
deadband controls are not appropriate.
2. Buildings complying with Section 1141.4, if in the proposed building
energy analysis, heating and cooling thermostat setpoints are set to
the same temperature between 70 degrees F and 75 degrees F
inclusive, and assumed to be constant throughout the year.
3. Thermostats that require manual changeover between heating and
cooling modes.
1412.3 Humidity Controls: If a system is equipped with a means for adding
moisture, a humidistat shall be provided.
1412.4 Setback and Shut -Off: HVAC systems shall be equipped with automatic
controls capable of accomplishing a reduction of energy use through control setback
or equipment shutdown during periods of non -use or alternate use of the spaces
served by the system. The automatic controls shall have a minimum seven -day
clock and be capable of being set for seven different day types per week. It must
retain programming and time for a power loss of 10 hours and include an accessible
manual override of up to 2 hours.
Exceptions:
1. Systems serving areas which require continuous operation at the
same temperature setpoint.
2. Equipment with full load demands of 2 kW (6,826 Btu/h) or less may
be controlled by readily accessible manual off -hour controls.
3. Systems controlled by an occupant sensor that is capable of shutting
the system off when no occupant is sensed for a period of up to 30
minutes.
4. Systems controlled solely by a manually operated timer capable of
operating the system for no more than two hours.
1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets serving
conditioned spaces shall be equipped with dampers which close automatically when
the system is off or upon power failure. Stair shaft and elevator shaft smoke relief
openings shall be equipped with normally open (fails to open upon loss of power)
dampers. These dampers shall remain closed until activated by the fire alarm
es ystem or other approved smoke detection system.
Exceptions:
1. Systems serving areas which require continuous operation.
2. Combustion air intakes.
3. Gravity (nonmotorized) dampers are acceptable in buildings less
than 3 stories in height.
4. Gravity (nonmotorized) dampers are acceptable in exhaust and relief
outlets in the first story and levels below the first story of buildings
1412.8 Ventilation Controls for High - Occupancy Areas: Demand control
ventilation (DCV) is required for spaces that are larger than 500 ft2, have a design
occupancy for ventilation of greater than 40 people for 1000 ff2 of floor area, and are
served by systems with one or more of the following:
a. An air -side economizer,
b. Automatic modulating control of the outdoor air damper, or
c. A design outdoor airflow greater than 3000 cfm.
Exceptions:
1.Systems with energy recovery complying with Section 1436.
2. Multiple -zone systems without direct - digital control of individual zones
communicating with a central control panel.
3. Systems with a design outdoor airflow less than 1200 cfm.
4. Spaces where the supply airflow rate minus any makeup or outgoing
transfer air requirement is less than 1200 cfm.
1413 Air Economizers
1413.1 Operation: Air economizers shall be of automatically modulating outside and
return air dampers to provide 100 percent of the design supply air as outside air to
reduce or eliminate the need for mechanical cooling. Water economizers shall be
capable of providing the total concurrent cooling load served by the conneted
terminal equipment lacking airside economizer, at outside air temperatures of 45 ° F
dry- bulb /40 ° F wet -bulb and below. For this calculation, all factors including solar and
internal load shall be the same as those used for peak load calculations, except for
the outside temperatures.
Exception: Water economizers using air - cooled heat rejection equipment
may use a 35 ° F dry-bulb outside air temperature for this calculation. This
exception is limited to a maximum of 20 tons per building.
1413.2 Documentation: Water economizer plans submitted for approval shall
include the following information:
1. Maximum outside air conditions for which economizer is sized to provide
full cooling.
2. Design cooling load to be provided by economizer at this outside air
condition.
3. Heat rejection and terminal equipment performance data including model
number, flow rate, capacity, entering and leaving temperature in full
economizer cooling mode.
1413.3 Integrated Operation: Air economizers shall be capable of providing partial
cooling even when additional mechanical cooling is required to meet the remainder
of the cooling load.
Exceptions:
1. Individual, direct expansion units that have a rated capacity less than
65,000 Btu/h and use nonintegrated economizer controls that
preclude simultaneous operation of the economizer and mechanical
cooling.
2. Water - cooled water chillers with waterside economizer.
1413.4 Humidification: If an air economizer is required on a cooling system for
which humidification equipment is to be provided to maintain minimum indoor
humidity levels, then the humidifier shall be of the adiabatic type (direct evaporative
media or fog atomization type).
Exceptions:
1. Health care facilities where WAC 246- 320 -525 allows only steam
injection humidifiers in ductwork downstream of final filters. 1412.6
Combustion Heating Equipment Controls: Combustion heating
equipment with a capacity over 225,000 Btu/h shall have modulating
or staged combustion control.
2. Systems with water economizer
3. 100% outside air systems with no provisions for air recirculation to the
central supply fan.
4. Nonadiabatic humidifiers cumulatively serving no more than 10% of a
building's air economizer capacity as measured in cfm. This refers to
the system cfm serving rooms with stand alone or duct mounted
humidifiers.
1414 Ducting Systems
1414.1 Sealing: Duct work which is designed to operate at pressures above 1/2 inch
water column static pressure shall be sealed in accordance with Standard RS -18.
Extent of sealing required is as follows:
1. Static pressure: 1/2 inch to 2 inches; seal transverse joints.
2. Static pressure: 2 inches to 3 inches; seal all transverse joints and
longitudinal seams.
3. Static pressure: above 3 inches; seal all transverse joints, longitudinal
seams and duct wall penetrations.
Duct tape and other pressure sensitive tape shall not be used as the primary
sealant where ducts are designed to operate at static pressures of 1 inch W.C. or
greater.
1414.2 Insulation: Ducts and plenums that are constructed and function as part of
the building envelope, by separating interior space from exterior space, shall meet all
applicable requirements of Chapter 13. These requirements include insulation
installation, moisture control, air leakage, and building envelope insulation levels.
Unheated equipment rooms with combustion air louvers must be isolated from the
conditioned space by insulating interior surfaces to a minimum of R -11 and any
exterior envelope surfaces per Chapter 13. Outside air ducts serving individual
supply air units with less than 2,800 cfm of total supply air capacity shall be insulated
to a minimum of R -7 and are not considered building envelope. Other outside air
duct runs are considered building envelope until they,
EF
CAE
< 50 gal storage
0.58
0.71
50 to 70 gal storage
0.57
0.71
> 70 gal storage
0.55
0.70
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Permit Plans Checklist
MECH -CHK
2006 Washington State Nonresidential Energy Code Compliance Forms
Revised July 2007
Mechanical - General Requirements
1411.1 General: Equipment shall have a minimum performance at the specified
rating conditions not less than the values shown in Table 14-1A through 14 -1G. If a
rating recognized certification program exists for a product covered in Tables
4 -1A through 14-1G, and it includes provisions for verification and challenge of
equipment efficiency ratings, then the product shall be listed in the certification
program.
Gas -fired and oil -fired forced air furnaces with input ratings > 225,000 Btu/h (65
kW) and all unit heaters shall also have an intermittent ignition or interrupted device
(IID), and have either mechanical draft (including power venting) or a flue damper. A
vent damper is an acceptable alternative to a flue damper for furnaces where
combustion air is drawn from the conditioned space. All furnaces with input ratings >
225,000 Btu/h (65 kW), including electric furnaces, that are not located within the
conditioned space shall have jacket losses not exceeding 0.75% of the input rating.
1411.2 Rating Conditions: Cooling equipment shall be rated at ARI test conditions
and procedures when available. Where no applicable procedures exist, data shall
be furnished by the equipment manufacturer.
1411.3 Combination Space and Service Water Heating: For combination space
and service water heaters with a principal function of providing space heat, the
Combined Annual Efficiency (CAE) may be calculated by using ASHRAE Standard
124 -1991. Storage water heaters used in combination space heat and water heat
applications shall have either an Energy FActor (EF) or a CAE of not less than the
following:
1411.4 Packaged Electric Heating and Coo ing Equipment: Packaged electric
equipment providing both heating and cooling with a total cooling capacity greater
than 20, Btu/h shall be a heat pump.
Exception: Unstaffed equipment shaelters or cabinets used solely for
personal wireless service facilities.
1412 Controls
1412.1 Temperature Controls: Each system shall be provided with at least one
temperature control device. Each zone shall be controlled by individual thermostatic
controls responding to temperature within the zone. At a minimum, each floor of a
building shall be considered as a separate zone.
1 412.2 Deadband Controls: When used to control both comfort heating and
ooling, zone thermostatic controls shall be capable of a deadband of at least 5
degrees F within which the supply of heating and cooling energy to the zone is shut
off or reduced to a minimum.
Exceptions:
1. Special occupancy, special usage, or code requirements where
deadband controls are not appropriate.
2. Buildings complying with Section 1141.4, if in the proposed building
energy analysis, heating and cooling thermostat setpoints are set to
the same temperature between 70 degrees F and 75 degrees F
inclusive, and assumed to be constant throughout the year.
3. Thermostats that require manual changeover between heating and
cooling modes.
1412.3 Humidity Controls: If a system is equipped with a means for adding
moisture, a humidistat shall be provided.
1412.4 Setback and Shut -Off: HVAC systems shall be equipped with automatic
controls capable of accomplishing a reduction of energy use through control setback
or equipment shutdown during periods of non -use or alternate use of the spaces
served by the system. The automatic controls shall have a minimum seven -day
clock and be capable of being set for seven different day types per week. It must
retain programming and time for a power loss of 10 hours and include an accessible
manual override of up to 2 hours.
Exceptions:
1. Systems serving areas which require continuous operation at the
same temperature setpoint.
2. Equipment with full load demands of 2 kW (6,826 Btu/h) or less may
be controlled by readily accessible manual off -hour controls.
3. Systems controlled by an occupant sensor that is capable of shutting
the system off when no occupant is sensed for a period of up to 30
minutes.
4. Systems controlled solely by a manually operated timer capable of
operating the system for no more than two hours.
1412.4.1 Dampers: Outside air intakes, exhaust outlets and relief outlets serving
conditioned spaces shall be equipped with dampers which close automatically when
the system is off or upon power failure. Stair shaft and elevator shaft smoke relief
openings shall be equipped with normally open (fails to open upon loss of power)
dampers. These dampers shall remain closed until activated by the fire alarm
es ystem or other approved smoke detection system.
Exceptions:
1. Systems serving areas which require continuous operation.
2. Combustion air intakes.
3. Gravity (nonmotorized) dampers are acceptable in buildings less
than 3 stories in height.
4. Gravity (nonmotorized) dampers are acceptable in exhaust and relief
outlets in the first story and levels below the first story of buildings
1412.8 Ventilation Controls for High - Occupancy Areas: Demand control
ventilation (DCV) is required for spaces that are larger than 500 ft2, have a design
occupancy for ventilation of greater than 40 people for 1000 ff2 of floor area, and are
served by systems with one or more of the following:
a. An air -side economizer,
b. Automatic modulating control of the outdoor air damper, or
c. A design outdoor airflow greater than 3000 cfm.
Exceptions:
1.Systems with energy recovery complying with Section 1436.
2. Multiple -zone systems without direct - digital control of individual zones
communicating with a central control panel.
3. Systems with a design outdoor airflow less than 1200 cfm.
4. Spaces where the supply airflow rate minus any makeup or outgoing
transfer air requirement is less than 1200 cfm.
1413 Air Economizers
1413.1 Operation: Air economizers shall be of automatically modulating outside and
return air dampers to provide 100 percent of the design supply air as outside air to
reduce or eliminate the need for mechanical cooling. Water economizers shall be
capable of providing the total concurrent cooling load served by the conneted
terminal equipment lacking airside economizer, at outside air temperatures of 45 ° F
dry- bulb /40 ° F wet -bulb and below. For this calculation, all factors including solar and
internal load shall be the same as those used for peak load calculations, except for
the outside temperatures.
Exception: Water economizers using air - cooled heat rejection equipment
may use a 35 ° F dry-bulb outside air temperature for this calculation. This
exception is limited to a maximum of 20 tons per building.
1413.2 Documentation: Water economizer plans submitted for approval shall
include the following information:
1. Maximum outside air conditions for which economizer is sized to provide
full cooling.
2. Design cooling load to be provided by economizer at this outside air
condition.
3. Heat rejection and terminal equipment performance data including model
number, flow rate, capacity, entering and leaving temperature in full
economizer cooling mode.
1413.3 Integrated Operation: Air economizers shall be capable of providing partial
cooling even when additional mechanical cooling is required to meet the remainder
of the cooling load.
Exceptions:
1. Individual, direct expansion units that have a rated capacity less than
65,000 Btu/h and use nonintegrated economizer controls that
preclude simultaneous operation of the economizer and mechanical
cooling.
2. Water - cooled water chillers with waterside economizer.
1413.4 Humidification: If an air economizer is required on a cooling system for
which humidification equipment is to be provided to maintain minimum indoor
humidity levels, then the humidifier shall be of the adiabatic type (direct evaporative
media or fog atomization type).
Exceptions:
1. Health care facilities where WAC 246- 320 -525 allows only steam
injection humidifiers in ductwork downstream of final filters. 1412.6
Combustion Heating Equipment Controls: Combustion heating
equipment with a capacity over 225,000 Btu/h shall have modulating
or staged combustion control.
2. Systems with water economizer
3. 100% outside air systems with no provisions for air recirculation to the
central supply fan.
4. Nonadiabatic humidifiers cumulatively serving no more than 10% of a
building's air economizer capacity as measured in cfm. This refers to
the system cfm serving rooms with stand alone or duct mounted
humidifiers.
1414 Ducting Systems
1414.1 Sealing: Duct work which is designed to operate at pressures above 1/2 inch
water column static pressure shall be sealed in accordance with Standard RS -18.
Extent of sealing required is as follows:
1. Static pressure: 1/2 inch to 2 inches; seal transverse joints.
2. Static pressure: 2 inches to 3 inches; seal all transverse joints and
longitudinal seams.
3. Static pressure: above 3 inches; seal all transverse joints, longitudinal
seams and duct wall penetrations.
Duct tape and other pressure sensitive tape shall not be used as the primary
sealant where ducts are designed to operate at static pressures of 1 inch W.C. or
greater.
1414.2 Insulation: Ducts and plenums that are constructed and function as part of
the building envelope, by separating interior space from exterior space, shall meet all
applicable requirements of Chapter 13. These requirements include insulation
installation, moisture control, air leakage, and building envelope insulation levels.
Unheated equipment rooms with combustion air louvers must be isolated from the
conditioned space by insulating interior surfaces to a minimum of R -11 and any
exterior envelope surfaces per Chapter 13. Outside air ducts serving individual
supply air units with less than 2,800 cfm of total supply air capacity shall be insulated
to a minimum of R -7 and are not considered building envelope. Other outside air
duct runs are considered building envelope until they,
•
•
,,,a.,,,, ,,,,,, „.,„, „,,« ,, „ .g4,gf31 ,Un p, platy ,1,Iocg§lgpntial_Energy..Code Campliance.Form. __. _ , _
outlets in the first story and levels below the first story of buildings duct runs are considered building envelope until they,
three or more stories in height. 1. connect to the heating or cooling equipment, or
1412.4.2 Optimum Start Controls: Heating and cooling systems with design supply 2. are isolated from the exterior with an automatic shut-off damper complying
air capacities exceeding 10,000 cfm shall have optimum start controls. Optimum with Section 1412.4.1.
start controls shall be designed to automatically adjust the start time of an HVAC Once outside air ducts meet the above listed requirements, any runs within
system each day to bring the space to desired occupied temperature levels conditioned space shall comply with Table 14-5 requirements.
immediately before scheduled occupancy. The control algorithm shall, as a Other ducts and plenums shall be thermally insulated per Table 14 -5.
rnimum, be a function of the difference between space temperature and occupied Exceptions:
etpoint and the amount of time prior to scheduled occupancy. 1. Within the HVAC equipment.
1 412.5 Heat Pump Controls: Unitary air cooled heat pumps shall include
microprocessor controls that minimize supplemental heat usage during start-up, set- 2. Exhaust air ducts not subject to condensation.
up, and defrost conditions. These controls shall anticipate need for heat and use 3. Exposed ductwork within a zone that serves that zone.
compression heating as the first stage of heat. Controls shall indicate when 1415 Piping Systems
supplemental heating is being used through visual means (e.g., LED indicators). 1415.1 Insulation: Piping shall be thermally insulated in accordance with Table 14 -6.
1412.6 Combustion Heating Equipment Controls: Combustion heating equipment Exception: Piping installed within unitary HVAC equipment.
with a capacity over 225,000 Btu/h shall have modulating or staged combustion Water pipes outside the conditioned space shall be insulated in accordance with
control. 000 Washington State Plumbing Code (WAC 51 -26)
EXCEPTIONS: 1. Boilers. 2. Radiant heaters. 1416 Completion Requirements (Refer to NREC Section 1416 and the Building
1412.7 Balancing: Each air supply outlet or air or water terminal device shall have Commissioning Guidelines, published by the Building Commissioning Association,
a means for balancing, including but not limited to, dampers, temperature and for complete text and guidelines for building completion and commissioning
pressure test connections and balancing valves. requirements.)
ACTIVITY NUMBER: M08 -219
PROJECT NAME: RPI
SITE ADDRESS: 12720 GATEWAY DR
X Original Plan Submittal
Response to Correction Letter #
DATE: 09 -04 -08
Response to Incomplete Letter #
Revision # After Permit Issued
DEPARTMENTS:
p L &)c.
Building Division
Public Works n Structural
DETERMINATION OF COMPLETENESS: (Tues., Thurs.) DUE DATE: 09-09 -08
Complete
Comments:
TUES/THURS ROUTING:
Please Route
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Approved n Approved with Conditions
Notation:
REVIEWER'S INITIALS:
Documents/routing slip.doc
2 -28-02
•
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
[7?
61 q.�o-Db
Fire Prevention
Incomplete
Structural Review Required
R1
a
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑
Fire ❑ Ping ❑ PW ❑ Staff Initials:
n No further Review Required
DATE:
Planning Division
Permit Coordinator
Not Applicable
C
DATE:
El
ij
n
DUE DATE: 10-07 -08
Not Approved (attach comments) 1
Permft,Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 - 431 -3665
Web site: http: //www.ci.tukwila.wa.us
Revision submittals must be submitted in person at the Permit Center. Revisions will not be accepted through
the mail, fax, etc.
Date: C k I Z 14 > G Plan Check/Permit Number: m a$ —2
❑ Response to Incomplete Letter #
❑ Response to Correction Letter #
'E Revision # r after Permit is Issued
❑ Revision requested by a City Building Inspector or Plans Examiner
Project Name: RP a-
Project Address: a 3 I I I20} 1ti L1 l I U t !I 07 7( (, c)
Contact Person: - yA 0 "Tv ✓v — Phone Number: - u ( e --- ie - 3 — 17 N
Summary of Revision: We of t7 g H ✓f f (~ I 'i1 -1- k c v''L e Lj re,P f
a r,K Plate ,
Sheet Number(s):
"Cloud" or highlight all areas of revision including date of revision /f
Received at the City of Tukwila Permit Center by:
12 in Permits Plus on ',)• - -0 r
lapplicationslforms- applications on linelrevision submittal
Created: 8 -13 -2004
Steven M. Mullet, Mayor
Steve Lancaster, Director
RECFIVFr
SEP 242008
�ERNIITCEFffE�
Bond
Bond
Company
Name
Bond
Account
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Bond
Amount
Received
Date
1
TRAVELERS
CAS Et
SURETY CO
104667361
01/01/2006
Until
Cancelled
01/06/2006
$12,000.00
01/03/2006
Name
Role
Effective Date
Expiration Date
EVERGREEN REFRIGERATION LLC
PARTNER /MEMBER
12/22/2005
Amount
PATTON, DAVID
PARTNER /MEMBER
01/06/2006
PATTON, RODGER
PARTNER /MEMBER
01/06/2006
PATTON, MATTHEW
PARTNER /MEMBER
01/06/2006
Insurance
Company
Name
Policy
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Amount
Received
Date
CONTINENTAL
Untitled Page
General /Specialty Contractor
A business registered as a construction contractor with LEtd to perform construction work
within the scope of its specialty. A General or Specialty construction Contractor must
maintain a surety bond or assignment of account and carry general liability insurance.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent
Company
EVERGREEN
REFRIGERATION LLC
2067631744
727 S KENYON ST
SEATTLE
WA
98108
KING
LIMITED LIABILITY
COMPANY
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Previous
License
Next License
Associated
License
Specialty 1
Specialty 2
602512953
ACTIVE
EVERGRL954R2
CONSTRUCTION
CONTRACTOR
1/6/2006
1/6/2010
EVERGI "201 D7
GENERAL
UNUSED
Business Owner Information
Bond Information
Insurance Information
•
https: / /fortress.wa. gov /lni/bbip/Detail. aspx ?License= EVERGRL954R2
Page 1 of 2
09/19/2008
1�
VICINITY MAP
SCALE:NONE
GAS PACKAGE EQUIPMENT SCHEDULE
- AIRFLOW SP MIN. OSA I Motor DRIVE COOLING HEATING ELECT ICAL WEIGHT
MARK MANF. MODEL TONS. CFM WC CFM Hp NUMBER TOTAL SEER EER INPUT OUTPUT AFUE VOLTS PHASE M.C.A. MOCP UNIT ECON CURB TOTAL FILTER SIZES NOTES
BTUH BTUH BTUH ( %) (V) (A) (A) LBS LBS LBS LBS NO (LxWxD)
RTU 1 LENNOX TGA 150S2BH 12.5 5,000 0.8" 1,000 5 #6 145,000 - - -- 9.5 240,000 192,000 80% 460 30 31 35 1,402 47 126 1,575 4 (18"x 24"x 2 ") 1,2,3,4
RTU 2 LENNOX TGA 150S2BH 12.5 5,000 0.8" 1,000 5 #6 145,000 - - -- 9.5 240,000 192,000 80% 460 30 31 35 1,402 47 126 1,575 4 (18"x 24"x 2 ") 1,2,3,4
RTU 3 LENNOX TGA 150S2BH 12.5 5,000 0.8" 1,000 5 #6 145,000 - - -- 9.5 240,000 192,000 80% 460 30 31 35 1,402 47 126 1,575 4 (18" x 24"x 2 ") 1,2,3,4
RTU 4 LENNOX TGA048S2DM 4 1135 0.4" 320 0.5 LOW 50,000 13.0 11.0 105,000 84,000 80% 460 30 11 15 633 36 100 769 4 (16" x 20" x 2 ") 1,2,3
NOTE: 1. PACKAGED ROOFTOP UNIT.
2. ALL POWER WIRING (BY E.C.)
3. PROVIDE 100% O.A. ECONOMIZER & ROOFCURB.
4. PROVIDE SMOKE DETECTOR IN MAIN RETURN DUCT (WIRING BY E.G.)
SCALE : 1 /32" = 1' -0"
HVAC FLOOR PLAN
EXHAUST FAN SCHEDULE
MARK MANE. MODEL CFM S.P. VOLTS PHASE Hp /A NOTES
REF 1 ILG NOT USED
REF 2 ILO NOT USED
REF 3 ILG CRBA 15 2300 0.25" 115 1 1/2 HP LOCATED ON ROOF
REF 4 ILO CRBA 15 2300 0.25" 115 1 1/2 HP LOCATED ON ROOF
REF 5 ILG CRBA -24 5600 0.25" 115 1 1 HP LOCATED ON ROOF
REF 5 ILG CRBA -24 5600 0.25" 115 1 1 HP LOCATED ON ROOF
EXHAUST FAN SCHEDULE
MARK MANF. MODEL CFM S.P. VOLTS PHASE Hp/A NOTES
EF 1 GROAN L150 130 0.375" 115 1 1.4 A LOCATED ON CEILING
EF 2 GROAN L150 130 0.375" 115 1 1.4 A LOCATED ON CEILING
EF 3 GROAN L150 130 0.375" 115 1 1.4 A LOCATED ON CEILING
SCOPE OF WORK(SEE M2)
1 -1/4" (PIPIE ON ROOF)
COMPLETION AND COMMISSIONING FOR
MECHANICAL SYSTEMS
RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE
BUILDING OWNER WITHIN 90 DAYS OF THE DATE OF SYSTEM ACCEPTANCE
PER WA ENERGY CODE (WSEC) SECTION 1416.1.
AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE
BUILDING OWNER PER WSEC SECTION 1416.2.4.1
ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRITTEN BALANCE REPORT SHALL BE
PROVIDED TO THE OWNER PER WSEC SECTION 14516.2.2.1,
FOR WAREHOUSES SEMIHEATED SPACES AND SIMPLE SYSTEMS AS DEFINED IN
n •+ 2 : ■r •� - • V •• ■ :: • .IS
ADJUSTED, SEQUENCES OF OPERATION SHALL BE TESTED TO ENSURE THAT THEY
OPERATE IN ACCORD WITH SPECIFICATIONS AND APPROVED PLANS, AND A COMPLETE
REPORT OF TEST PROCEDURES AND RESULTS SHALL BE FILED WITH THE OWNER
PER WSEC SECTION 1416.2.3.2.
FOR ALL OTHER SYSTEMS: HVAC CONTROL SYSTEMS SHALL BE TESTED, CALIBRATED
AND ADJUSTED, SEQUENCES OF OPERATION SHALL BE TESTED TO ENSURE THAT THEY
OPERATE IN ACCORD WITH SPECIFICATIONS AND APPROVED PLANS PER WSEC SECTION 1416.2.3.2;
NECESSARY TESTS SHALL BE IDENTIFIED PER WSEC SECTION 1416.2.3;
A PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE
PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY PER WSEC SECTION
1416.2.5.1 AND A COMPLETE FINAL COMMISSIONING REPORT OF TEST
PROCEDURES AND RESULTS SHALL BE FILED WITH THE OWNER PER WSEC SECTION 1416.2.5.2.
INTAKE HOOD SCHEDULE
MARK MANF. MODEL CFM SP SIZE WT NOTES
WG LB
IH -1 WESTERN VENTS AV -200 6,650 0.086 32 "x32" 139 ON ROOF
IH -2 WESTERN VENTS AV -200 6,650 0.086 32 "x32" 139 ON ROOF
Plar review approval is subject to errors anand on9issions.
Approval of construction documents does not authorize
the violation of any adopted code or ordinance. Rece pt
of approved Field19opy and conditipns is acknovdledsed:
Date: Y r '
RE \93iON i
No changes shall be rn ide tc th�` ^rnn
of work without prior approv �I
n! Tukwila Building Division
*L'o : e':ri io r•c� 1 . ✓i I' '1 �:t �. : I ;(- -••'R� r..'' : ' f 1^, t '.',. ..�
SEPARATE PEHM
REQUIRED FOR:
, 3S Pipit n
City 1 'jk , .ia
GENERAL NOTES
DUCTWORK
1.1 ALL DUCT DIMENSIONS ON PLAN ARE CLEAR INSIDE DIMENSIONS, ADD 2" TO EACH
DIMENSION TO OBTAIN OUTSIDE DIMENSION. ADD 4 "TO EACH DIMENSION IF
DUCTWORK IS ON THE EXTERIOR OF BUILDING.
1.2 THE FIRST NUMBER ON ALL DUCT DIMENSIONS IS THE WIDTH AND THE SECOND
NUMBER IS THE HEIGHT.
1.3 MATERIALS WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME SPREAD RATING
LESS THAN 25 AND A FLAME SMOKE DEVELOPMENT RATING LESS THAN 50, PER
IMC 602.2.1. W
1.4 SEAL ALL TRANSVERSE JOINTS FOR DUCTWORK WITH STATIC PRESSURE BETEEN
1/2 INCHES AND 2 INCHES. DUCTWORK WHICH IS DESIGNED TO OPERATE AT
PRESSURES ABOVE 1/2 INCH WATER COLUMN STATIC PRESSURE SHALL BE SEALED
IN ACCORDANCE WITH STANDARD RS -7.
1.5 ALL DUCT GAUGES PER SMACNA, IMC 603 -4.
1.6 ALL DUCT SUPPORTS PER SMACNA, IMC 603 -10.
1.7 ATTACH DIFFUSERS AND GRILLES TO T -BAR GRID PER WA STATE & LOCAL CODES.
1.8 BALANCING DAMPERS ARE TO BE INSTALLED ON ALL BRANCH DUCTS OR DIFFUSERS.
INSULATION
2.1 INSULATE OR LINE DUCTWORK PER WA. STATE ENERGY AND MECHANICAL CODES.
2.2 INSULATE REFRIGERANT & CONDENSATE PIPING PER STATE & LOCAL ENERGY CODES.
GENERAL CONTRACTOR
3.1 GENERAL CONTRACTOR TO PROVIDE AND CUT OPENINGS FOR ALL ROOFTOP,
CEILING, FLOOR, AND WALL PENETRATIONS, INCLUDING WEATHERPROOF SEALING
AND FIRE PROOF LINING PER IMC & IBC.
3.2 GENERAL CONTRACTOR TO VERIFY PENETRATION LOCATION AND DIMENSIONS
WITH ERL BEFORE FRAMING OPENINGS.
3.3 GENERAL CONTRACTOR TO PROVIDE ALL DEMOLITION, PATCHING, AND PAINTING
AS REQUIRED FOR MECHANICAL WORK.
3.4 GENERAL CONTRACTOR TO PROVIDE ADEQUATE STRUCTURAL SUPPORT AS
REQUIRED FOR MECHANICAL WORK.
3.5 GENERAL CONTRACTOR TO PROVIDE ADEQUATE ENGINEERING AS REQUIRED FOR
MECHANICAL WORK.
3.6 GENERAL CONTRACTOR TO PROVIDE SERVICE ACCESS PER CODE TO ALL
MECHANICAL EQUIPMENT.
3.7 GENERAL CONTRACTOR TO LEVEL ALL FACTORY CURBS PROVIDED BY ERL PROVIDE
ALL CANT STRIPS AND CURB INSULATION, AND SEAL AGAINST LEAKS.
3.8 GENERAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING OF T -BAR CEILING
AS REQUIRED FOR HVAC INSTALLATION.
3.9 GENERAL CONTRACTOR TO PROTECT ALL OPENINGS THROUGH FLOORS PROVIDED
FOR DUCTWORK INSTALLATION IN ACCORDANCE WITH TABLE 601 OF INTERNATIONAL
BUILDING CODE, WHERE REQUIRED BY SECTION 707 OF IBC.
ELECTRICAL
4.1 ERL TO INSTALL ALL LOW VOLTAGE CONTROL WIRING, CONDUIT WILL BE PROVIDED
BY ELECTRICAL CONTRACTOR.
4.2 ELECTRICAL CONTRACTOR TO PROVIDE ALL ELECTRICAL CONNECTIONS,
DISCONNECTS, AND STARTERS FOR MECHANICAL EQUIPMENT.
4.3 ELECTRICAL CONTRACTOR TO VERIFY EQUIPMENT SIZES, LOADS AND LOCATIONS
WITH ERL MECHANICAL PLAN AND WITH FIELD CONDITIONS.
4.4 ELECTRICAL CONTRACTOR TO INTERLOCK BATHROOM EXHAUST FANS WITH LIGHT
HT
SWITCH.
4.5 ERL TO PROVIDE 7 -DAY NIGHT SETBACK, PROGRAMMABLE TYPE T -STAT WITH
CAPABILITY OF 5 °F DEADBAND.
4.6 ERL TO VERIFY FINAL LOCATION OF THERMOSTAT WITH CUSTOMER.
4.7 ELECTRICAL CONTRACTOR TO PROVIDE ELECTRICAL GCFI OUTLET WITHIN 25 FT
OF EACH PIECE OF MECHANICAL EQUIPMENT.
PLUMBING
5.1 PLUMBING CONTRACTOR TO FURNISH AND INSTALL ALL GAS PIPING FOR
MECHANICAL. EQUIPMENT PER CODE.
5.2 PLUMBING CONTRACTOR OFFSET VENTS 10 FEET MINIMUM FROM ALL HVAC FRESH
AIR INTAKES OR 2' ABOVE HIGHEST POINT OF INTAKE, IMC 401.5.1.
5.3 CONDENSATE DRAINS FROM RTU BY ERI TO DRAIN WITHIN 12" OF UNIT.
CONDENSATE DRAINS FOR AIR HANDLERS BY PLUMBER.
ENERGY CODE COMPLIANCE
6.1 AT A MINIMUM, EACH FLOOR IS TO BE CONSIDERED A SEPARATE ZONE. VERIFY
THERMOSTATIC CONTROL FOR EACH ZONE AS INDICATED ON PLANS.
6.2 OUTSIDE AIR INTAKES, EXHAUST OUTLETS, AND RELIEF OUTLETS SERVING
CONDITIONED SPACES SHALL BE EQUIPPED WITH DAMPERS WHICH CLOSE
AUTOMATICALLY WHEN THE SYSTEM IS OFF OR UPON POWER FAILURE,
PER WSEC SIoiC. 1412.4.1.
6.3 AIR ECONOMIZERS WHERE REQUIRED BY CODE ARE INDICATED BY THE EQUIPMENT
SCHEDULE PT 100% CAPABILITY, CONTROL AND OPERATION OF THE ECONOMIZER
SHALL COMPLY WITH WSEC SEC. 1423.
MECHANICAL CODE COMPLIANCE
7.1 WHERE REQUIRED PROVIDE AUTOMATIC SHUTOFF ACTIVATED BY SMOKE DETECTORS
IN EACH SYSTEM DELIVERING HEATING OR COOLING AIR IN EXCESS OF 2000 CFM.
DETECTORS SHALL BE LOCATED IN THE MAIN RETURN AIR PER IMC 606,
WA2004 #1
SYMBOL LEGEND
SYMBOL ABBV. DESCRIPTION
p „ DUCT SECTION SUPPLY
f/ I DUCT SECTION - RETURN /EXHAUST
RECTANGULAR DUCT (s ° °�
- ROUND DUCT V
FLEXIBLE DUCT c0'E l L .. 3
MVD MANUAL VOLUME DAMPER V ..� _�..._w._
' !L.. Ye n u
❑BDD �Ly X91 1�.,NLCl/41H
BDD BACKDRAFT DAMPER
M MD MOTORIZED DAMPER
- 4 FD FIRE DAMPER
FSD FIRE /SMOKE DAMPER (120V POWER REQ.)
CEILING RADIATION DAMPER
sn SD SMOKE DETECTOR
T THERMOSTAT
Q S SENSOR
- - - -R R R REFRIGERANT LINES
G G G NATURAL GAS LINES
Ea CEILING DIFFUSER (SUPPLY)
FA CEILING DIFFUSER (RETURN /EXHAUST)
EXHAUST FAN (CEILING MOUNTED)
[Q_ INLINE FAN RECEIVED
-U PROPELLER FAN SL' Z4 nib
� I � SIDEWALL DIFFUSER = , ,
L DUCT FITTING
�, ❑,J, 12' 2'' ____..-0 DATUM UNTAG t/
f DUCT RISER pF: 1
N a a Nap - r I i b W L
DATE
09/16/08
DWG. FILE:
DRAWING DATE:
JOB NO.:
58021
REVISIONS
GEN, REV.
08/27/08
58021M1-
NOT PUBLISHED. ALL RIGHTS RESERVED. THE
DRAWING AND SPECIFICATIONS, IDEAS, DESIGNS
AND ARRANGEMENTS REPRESENTED THEREBY
ARE AND SHALL REMAIN THE PROPERTY OF EVE-
RGREEN REFRIGERATION INC. NO PART THEREOF
SHALL BE REPRODUCED, COPIED, ADAPTED, DISC-
LOSED OR DISTRIBUTED Td OTHERS, SOLD, PUB-
LISHED OR OTHERWISE USED WITHOUT THE PRIOR
WRITTEN CONSENT OF AND APPROPRIATE COMPEN-
SATION TO EVERGREEN REFRIGERATION INC. VISUAL
CONTACT WITH ¶HE ABOVE DRAWINGS OR SPECIFIC-
ATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
CO
0
T
hl
CO
0
bJ
SHEET: M
W
D
(n
LL'
D
J
EL
z
Li
D
0
0
Q..
st
W
D
Li
D
• I J fl
OF 2 SHEETS
•
1�
VICINITY MAP
SCALE:NONE
GAS PACKAGE EQUIPMENT SCHEDULE
- AIRFLOW SP MIN. OSA I Motor DRIVE COOLING HEATING ELECT ICAL WEIGHT
MARK MANF. MODEL TONS. CFM WC CFM Hp NUMBER TOTAL SEER EER INPUT OUTPUT AFUE VOLTS PHASE M.C.A. MOCP UNIT ECON CURB TOTAL FILTER SIZES NOTES
BTUH BTUH BTUH ( %) (V) (A) (A) LBS LBS LBS LBS NO (LxWxD)
RTU 1 LENNOX TGA 150S2BH 12.5 5,000 0.8" 1,000 5 #6 145,000 - - -- 9.5 240,000 192,000 80% 460 30 31 35 1,402 47 126 1,575 4 (18"x 24"x 2 ") 1,2,3,4
RTU 2 LENNOX TGA 150S2BH 12.5 5,000 0.8" 1,000 5 #6 145,000 - - -- 9.5 240,000 192,000 80% 460 30 31 35 1,402 47 126 1,575 4 (18"x 24"x 2 ") 1,2,3,4
RTU 3 LENNOX TGA 150S2BH 12.5 5,000 0.8" 1,000 5 #6 145,000 - - -- 9.5 240,000 192,000 80% 460 30 31 35 1,402 47 126 1,575 4 (18" x 24"x 2 ") 1,2,3,4
RTU 4 LENNOX TGA048S2DM 4 1135 0.4" 320 0.5 LOW 50,000 13.0 11.0 105,000 84,000 80% 460 30 11 15 633 36 100 769 4 (16" x 20" x 2 ") 1,2,3
NOTE: 1. PACKAGED ROOFTOP UNIT.
2. ALL POWER WIRING (BY E.C.)
3. PROVIDE 100% O.A. ECONOMIZER & ROOFCURB.
4. PROVIDE SMOKE DETECTOR IN MAIN RETURN DUCT (WIRING BY E.G.)
SCALE : 1 /32" = 1' -0"
HVAC FLOOR PLAN
EXHAUST FAN SCHEDULE
MARK MANE. MODEL CFM S.P. VOLTS PHASE Hp /A NOTES
REF 1 ILG NOT USED
REF 2 ILO NOT USED
REF 3 ILG CRBA 15 2300 0.25" 115 1 1/2 HP LOCATED ON ROOF
REF 4 ILO CRBA 15 2300 0.25" 115 1 1/2 HP LOCATED ON ROOF
REF 5 ILG CRBA -24 5600 0.25" 115 1 1 HP LOCATED ON ROOF
REF 5 ILG CRBA -24 5600 0.25" 115 1 1 HP LOCATED ON ROOF
EXHAUST FAN SCHEDULE
MARK MANF. MODEL CFM S.P. VOLTS PHASE Hp/A NOTES
EF 1 GROAN L150 130 0.375" 115 1 1.4 A LOCATED ON CEILING
EF 2 GROAN L150 130 0.375" 115 1 1.4 A LOCATED ON CEILING
EF 3 GROAN L150 130 0.375" 115 1 1.4 A LOCATED ON CEILING
SCOPE OF WORK(SEE M2)
1 -1/4" (PIPIE ON ROOF)
COMPLETION AND COMMISSIONING FOR
MECHANICAL SYSTEMS
RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE
BUILDING OWNER WITHIN 90 DAYS OF THE DATE OF SYSTEM ACCEPTANCE
PER WA ENERGY CODE (WSEC) SECTION 1416.1.
AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE
BUILDING OWNER PER WSEC SECTION 1416.2.4.1
ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRITTEN BALANCE REPORT SHALL BE
PROVIDED TO THE OWNER PER WSEC SECTION 14516.2.2.1,
FOR WAREHOUSES SEMIHEATED SPACES AND SIMPLE SYSTEMS AS DEFINED IN
n •+ 2 : ■r •� - • V •• ■ :: • .IS
ADJUSTED, SEQUENCES OF OPERATION SHALL BE TESTED TO ENSURE THAT THEY
OPERATE IN ACCORD WITH SPECIFICATIONS AND APPROVED PLANS, AND A COMPLETE
REPORT OF TEST PROCEDURES AND RESULTS SHALL BE FILED WITH THE OWNER
PER WSEC SECTION 1416.2.3.2.
FOR ALL OTHER SYSTEMS: HVAC CONTROL SYSTEMS SHALL BE TESTED, CALIBRATED
AND ADJUSTED, SEQUENCES OF OPERATION SHALL BE TESTED TO ENSURE THAT THEY
OPERATE IN ACCORD WITH SPECIFICATIONS AND APPROVED PLANS PER WSEC SECTION 1416.2.3.2;
NECESSARY TESTS SHALL BE IDENTIFIED PER WSEC SECTION 1416.2.3;
A PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE
PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY PER WSEC SECTION
1416.2.5.1 AND A COMPLETE FINAL COMMISSIONING REPORT OF TEST
PROCEDURES AND RESULTS SHALL BE FILED WITH THE OWNER PER WSEC SECTION 1416.2.5.2.
INTAKE HOOD SCHEDULE
MARK MANF. MODEL CFM SP SIZE WT NOTES
WG LB
IH -1 WESTERN VENTS AV -200 6,650 0.086 32 "x32" 139 ON ROOF
IH -2 WESTERN VENTS AV -200 6,650 0.086 32 "x32" 139 ON ROOF
Plar review approval is subject to errors anand on9issions.
Approval of construction documents does not authorize
the violation of any adopted code or ordinance. Rece pt
of approved Field19opy and conditipns is acknovdledsed:
Date: Y r '
RE \93iON i
No changes shall be rn ide tc th�` ^rnn
of work without prior approv �I
n! Tukwila Building Division
*L'o : e':ri io r•c� 1 . ✓i I' '1 �:t �. : I ;(- -••'R� r..'' : ' f 1^, t '.',. ..�
SEPARATE PEHM
REQUIRED FOR:
, 3S Pipit n
City 1 'jk , .ia
GENERAL NOTES
DUCTWORK
1.1 ALL DUCT DIMENSIONS ON PLAN ARE CLEAR INSIDE DIMENSIONS, ADD 2" TO EACH
DIMENSION TO OBTAIN OUTSIDE DIMENSION. ADD 4 "TO EACH DIMENSION IF
DUCTWORK IS ON THE EXTERIOR OF BUILDING.
1.2 THE FIRST NUMBER ON ALL DUCT DIMENSIONS IS THE WIDTH AND THE SECOND
NUMBER IS THE HEIGHT.
1.3 MATERIALS WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME SPREAD RATING
LESS THAN 25 AND A FLAME SMOKE DEVELOPMENT RATING LESS THAN 50, PER
IMC 602.2.1. W
1.4 SEAL ALL TRANSVERSE JOINTS FOR DUCTWORK WITH STATIC PRESSURE BETEEN
1/2 INCHES AND 2 INCHES. DUCTWORK WHICH IS DESIGNED TO OPERATE AT
PRESSURES ABOVE 1/2 INCH WATER COLUMN STATIC PRESSURE SHALL BE SEALED
IN ACCORDANCE WITH STANDARD RS -7.
1.5 ALL DUCT GAUGES PER SMACNA, IMC 603 -4.
1.6 ALL DUCT SUPPORTS PER SMACNA, IMC 603 -10.
1.7 ATTACH DIFFUSERS AND GRILLES TO T -BAR GRID PER WA STATE & LOCAL CODES.
1.8 BALANCING DAMPERS ARE TO BE INSTALLED ON ALL BRANCH DUCTS OR DIFFUSERS.
INSULATION
2.1 INSULATE OR LINE DUCTWORK PER WA. STATE ENERGY AND MECHANICAL CODES.
2.2 INSULATE REFRIGERANT & CONDENSATE PIPING PER STATE & LOCAL ENERGY CODES.
GENERAL CONTRACTOR
3.1 GENERAL CONTRACTOR TO PROVIDE AND CUT OPENINGS FOR ALL ROOFTOP,
CEILING, FLOOR, AND WALL PENETRATIONS, INCLUDING WEATHERPROOF SEALING
AND FIRE PROOF LINING PER IMC & IBC.
3.2 GENERAL CONTRACTOR TO VERIFY PENETRATION LOCATION AND DIMENSIONS
WITH ERL BEFORE FRAMING OPENINGS.
3.3 GENERAL CONTRACTOR TO PROVIDE ALL DEMOLITION, PATCHING, AND PAINTING
AS REQUIRED FOR MECHANICAL WORK.
3.4 GENERAL CONTRACTOR TO PROVIDE ADEQUATE STRUCTURAL SUPPORT AS
REQUIRED FOR MECHANICAL WORK.
3.5 GENERAL CONTRACTOR TO PROVIDE ADEQUATE ENGINEERING AS REQUIRED FOR
MECHANICAL WORK.
3.6 GENERAL CONTRACTOR TO PROVIDE SERVICE ACCESS PER CODE TO ALL
MECHANICAL EQUIPMENT.
3.7 GENERAL CONTRACTOR TO LEVEL ALL FACTORY CURBS PROVIDED BY ERL PROVIDE
ALL CANT STRIPS AND CURB INSULATION, AND SEAL AGAINST LEAKS.
3.8 GENERAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING OF T -BAR CEILING
AS REQUIRED FOR HVAC INSTALLATION.
3.9 GENERAL CONTRACTOR TO PROTECT ALL OPENINGS THROUGH FLOORS PROVIDED
FOR DUCTWORK INSTALLATION IN ACCORDANCE WITH TABLE 601 OF INTERNATIONAL
BUILDING CODE, WHERE REQUIRED BY SECTION 707 OF IBC.
ELECTRICAL
4.1 ERL TO INSTALL ALL LOW VOLTAGE CONTROL WIRING, CONDUIT WILL BE PROVIDED
BY ELECTRICAL CONTRACTOR.
4.2 ELECTRICAL CONTRACTOR TO PROVIDE ALL ELECTRICAL CONNECTIONS,
DISCONNECTS, AND STARTERS FOR MECHANICAL EQUIPMENT.
4.3 ELECTRICAL CONTRACTOR TO VERIFY EQUIPMENT SIZES, LOADS AND LOCATIONS
WITH ERL MECHANICAL PLAN AND WITH FIELD CONDITIONS.
4.4 ELECTRICAL CONTRACTOR TO INTERLOCK BATHROOM EXHAUST FANS WITH LIGHT
HT
SWITCH.
4.5 ERL TO PROVIDE 7 -DAY NIGHT SETBACK, PROGRAMMABLE TYPE T -STAT WITH
CAPABILITY OF 5 °F DEADBAND.
4.6 ERL TO VERIFY FINAL LOCATION OF THERMOSTAT WITH CUSTOMER.
4.7 ELECTRICAL CONTRACTOR TO PROVIDE ELECTRICAL GCFI OUTLET WITHIN 25 FT
OF EACH PIECE OF MECHANICAL EQUIPMENT.
PLUMBING
5.1 PLUMBING CONTRACTOR TO FURNISH AND INSTALL ALL GAS PIPING FOR
MECHANICAL. EQUIPMENT PER CODE.
5.2 PLUMBING CONTRACTOR OFFSET VENTS 10 FEET MINIMUM FROM ALL HVAC FRESH
AIR INTAKES OR 2' ABOVE HIGHEST POINT OF INTAKE, IMC 401.5.1.
5.3 CONDENSATE DRAINS FROM RTU BY ERI TO DRAIN WITHIN 12" OF UNIT.
CONDENSATE DRAINS FOR AIR HANDLERS BY PLUMBER.
ENERGY CODE COMPLIANCE
6.1 AT A MINIMUM, EACH FLOOR IS TO BE CONSIDERED A SEPARATE ZONE. VERIFY
THERMOSTATIC CONTROL FOR EACH ZONE AS INDICATED ON PLANS.
6.2 OUTSIDE AIR INTAKES, EXHAUST OUTLETS, AND RELIEF OUTLETS SERVING
CONDITIONED SPACES SHALL BE EQUIPPED WITH DAMPERS WHICH CLOSE
AUTOMATICALLY WHEN THE SYSTEM IS OFF OR UPON POWER FAILURE,
PER WSEC SIoiC. 1412.4.1.
6.3 AIR ECONOMIZERS WHERE REQUIRED BY CODE ARE INDICATED BY THE EQUIPMENT
SCHEDULE PT 100% CAPABILITY, CONTROL AND OPERATION OF THE ECONOMIZER
SHALL COMPLY WITH WSEC SEC. 1423.
MECHANICAL CODE COMPLIANCE
7.1 WHERE REQUIRED PROVIDE AUTOMATIC SHUTOFF ACTIVATED BY SMOKE DETECTORS
IN EACH SYSTEM DELIVERING HEATING OR COOLING AIR IN EXCESS OF 2000 CFM.
DETECTORS SHALL BE LOCATED IN THE MAIN RETURN AIR PER IMC 606,
WA2004 #1
SYMBOL LEGEND
SYMBOL ABBV. DESCRIPTION
p „ DUCT SECTION SUPPLY
f/ I DUCT SECTION - RETURN /EXHAUST
RECTANGULAR DUCT (s ° °�
- ROUND DUCT V
FLEXIBLE DUCT c0'E l L .. 3
MVD MANUAL VOLUME DAMPER V ..� _�..._w._
' !L.. Ye n u
❑BDD �Ly X91 1�.,NLCl/41H
BDD BACKDRAFT DAMPER
M MD MOTORIZED DAMPER
- 4 FD FIRE DAMPER
FSD FIRE /SMOKE DAMPER (120V POWER REQ.)
CEILING RADIATION DAMPER
sn SD SMOKE DETECTOR
T THERMOSTAT
Q S SENSOR
- - - -R R R REFRIGERANT LINES
G G G NATURAL GAS LINES
Ea CEILING DIFFUSER (SUPPLY)
FA CEILING DIFFUSER (RETURN /EXHAUST)
EXHAUST FAN (CEILING MOUNTED)
[Q_ INLINE FAN RECEIVED
-U PROPELLER FAN SL' Z4 nib
� I � SIDEWALL DIFFUSER = , ,
L DUCT FITTING
�, ❑,J, 12' 2'' ____..-0 DATUM UNTAG t/
f DUCT RISER pF: 1
N a a Nap - r I i b W L
DATE
09/16/08
DWG. FILE:
DRAWING DATE:
JOB NO.:
58021
REVISIONS
GEN, REV.
08/27/08
58021M1-
NOT PUBLISHED. ALL RIGHTS RESERVED. THE
DRAWING AND SPECIFICATIONS, IDEAS, DESIGNS
AND ARRANGEMENTS REPRESENTED THEREBY
ARE AND SHALL REMAIN THE PROPERTY OF EVE-
RGREEN REFRIGERATION INC. NO PART THEREOF
SHALL BE REPRODUCED, COPIED, ADAPTED, DISC-
LOSED OR DISTRIBUTED Td OTHERS, SOLD, PUB-
LISHED OR OTHERWISE USED WITHOUT THE PRIOR
WRITTEN CONSENT OF AND APPROPRIATE COMPEN-
SATION TO EVERGREEN REFRIGERATION INC. VISUAL
CONTACT WITH ¶HE ABOVE DRAWINGS OR SPECIFIC-
ATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
CO
0
T
hl
CO
0
bJ
SHEET: M
W
D
(n
LL'
D
J
EL
z
Li
D
0
0
Q..
st
W
D
Li
D
• I J fl
OF 2 SHEETS
4 '
r DRAWING DATE:
LI 08/27/08
,J DWG. BY:
GN
CHK. BY:
RD
JOB NO.:
58021
DWG. FILE:
58021 M2—
SHEET: m 2
2 OF
2
HFFTfi
HVAC FLOOR PLAN
0
0
UP
6 :.' ate -�
SCALE : 1/8"
uu nn ��--��,,
f-1 VA�.�
N��i.'��' //////mil M V
16"
I \ 1000 CFM
(TYP 5)
CHILLER
�.-- ---------------- - - - - -- —
._
IMM IF I riforimiii.z
1150 cfm
EXISTING
2300 CFM
20" VTR
14"
/R &)
2300 CFM
20" VTR
20"
14"
z
w
SPIRAL
24"
46 "x46"
6650 CFM
1150 cfm
5600 CFM
20" VTR
24 "
\I/
/ ! \
26"
r
46 "x46"
6650 CFM
3/4"
\ RIT /
IL — — —J
12.5 TON
12.5 TON
1000 CFM
(TYP 5)
\ 1 /
/1\
/
■
�26'
�1 I 24"
_CHILt_ER
•
'3/4"
- � —E
J
NCI
16"
LnJ
Ell
1
i
1
1
1
G
WAREHOUSE AND
FABRICATION
XISTING
ca
z
5600 CFM
20" VTR
4 TON
r
3/4"
10"
EXISTING
PIPE INSIDE
T
t .'106 CFnii =1\
4 N'S
ICI
SPACE
1 �35 CFM
VESTIBULE
DROP FROM ROOF
RI
PUL
CODE COMP $AN
APPROVED
SEP
City Of Tukwila
orocroh
7
RECEIV
SEP 24
PERMIT CE
VHION �
MO8-.219
U
0
w
w
z
w
w
08
1TE!-
NOT PUBLISHED. ALL RIGHTS RESERVED. THE
DRAWING AND SPECIFICATIONS, IDEAS, DESIGNS
AND ARRANGEMENTS REPRESENTED THEREBY
ARE AND SHALL REMAIN THE PROPERTY OF EVE-
RGREEN REFRIGERATION INC. NO PART THEREOF
SHALL BE REPRODUCED, COPIED. ADAPTED, DISC-
LOSED OR DISTRIBUTED TO OTHERS, SOLD, PUB-
LISHED OR OIHERVISE USED WITHOUT THE PRIOR
WRITTEN CONSENT OF AND APPROPRIATE COMPEN-
SATION TO EVERGREEN REFRIGERATION INC. VISUAL
CONTACT WITH THE ABOVE DRAWINGS OR SPECIFIC-
ATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.
SYMBOL LEGEND
SYMBOL
ABBV.
DESCRIPTION
PA
PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY PER W EC ECTION
DUCT SECTION SUPPLY
PROCEDURES AND RESULTS SHALL BE FILED WITH THE OWNER PER WSEC SECTION 1416.2.5.2.
Hp/A
DUCT SECTION - RETURN /EXHAUST_ C r' `�
.
I- : Qco
C
W
0
+.�
I
R ECTANGULAR DUCT . ���..
WG
a
C.
Ct
LB
NO
ROUND DUCT .Pr .,,T,
LOCATED ON CEILING
REF 1
ILG
FLEXIBLE DUCT SO) '�0�
i
-
MVD
MANUAL VOLUME DAMP R - '"'""�1\01J 14
� �� �� �� r
1
ific BIM
ODD
n \ VO
BACKDRAFT DAMPER - ° "'
ILG
m
MD
MOTORIZED DAMPER
115
FD
FIRE DAMPER
LOCATED ON ROOF
REF 3
FSD
FIRE /SMOKE DAMPER (120V POWER REQ.)
2300
0.25"
115
1
CEILING RADIATION DAMPER
0 S
REF 4
SMOKE DETECTOR
d
T
THERMOSTAT
115
S
SENSOR
R R
R
REFRIGERANT LINES
CRBA -24
5600
G
NATURAL GAS LINES
-G G
1/8 HP
11
REF 5
ILG
CEILING DIFFUSER (SUPPLY)
5600
Efi
115
1
CEILING DIFFUSER (RETURN /EXHAUST)
LOCATED ON ROOF
58021M1-
EXHAUST FAN (CEILING MOUNTED)
I Q I
OF 2 SHEETS
INLINE FAN 1FCEIVED
-U
PROPELLER FAN Ski 04 I " ' 'f
I;HiMII 1 uti\I I H
SIDEWALL DIFFUSER
1 f
DUCT FITTING
DATUM titeWinfl
UNIT TAG
4
B.O.J. 12' O
}
DUCT RISER
COMPLETION AND COMMISSIONING FOR
MECHANICAL SYSTEMS
RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE
BUILDING OWNER WITHIN 90 DAYS OF THE DATE OF SYSTEM ACCEPTANCE
PER WA ENERGY CODE (WSEC) SECTION 1416.1.
AN OPERATING MANUAL AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE
BUILDING OWNER PER WSEC SECTION 1416.2.4.1
ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRITTEN BALANCE REPORT SHALL BE
PROVIDED TO THE OWNER PER WSEC SECTION 14516.2.2.1.
SIMPLE
FOR SECTI
1421) HVAC CONTROL SYSTEMS BE TESTED, CALIBRATED AND
ADJUSTED, SEQUENCES OF OPERATION SHALL BE TESTED TO ENSURE THAT THEY
OPERATE IN ACCORD WITH SPECIFICATIONS AND APPROVED PLANS, AND A COMPLETE
REPORT OF TEST PROCEDURES AND RESULTS SHALL BE FILED WITH THE OWNER
PER WSEC SECTION 1416.2.3.2.
FOR ALL OTHER SYSTEMS: HVAC CONTROL SYSTEMS SHALL BE TESTED, CALIBRATED
AND ADJUSTED, SEQUENCES OF OPERATION SHALL BE TESTED TO ENSURE THAT THEY
OPERATE IN ACCORD WITH SPECIFICATIONS AND APPROVED PLANS PER WSEC SECTION 1416.2.3.2;
NECESSARY TESTS SHALL BE IDENTIFIED PER WSEC SECTION 1416.2.3;
A PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL BE
PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY PER W EC ECTION
1416.2.5.1 AND A COMPLETE FINAL COMMISSIONING REPORT OF TEST
PROCEDURES AND RESULTS SHALL BE FILED WITH THE OWNER PER WSEC SECTION 1416.2.5.2.
EXHAUST FAN SCHEDULE
MARK
MANF.
MODEL
CFM
S.P.
VOLTS
PHASE
Hp/A
NOTES
I- : Qco
C
W
0
+.�
I
va
0 co
0
r
N
,. H
WG
a
C.
Ct
LB
NO
1.4 A
LOCATED ON CEILING
REF 1
ILG
CRBA 13
2300
0.25"
115
1
1/2 HP
LOCATED ON ROOF
REF 2
ILG
CRBA 13
2300
0.25"
115
1
1/2 HP
LOCATED ON ROOF
REF 3
ILG
CRBA 13
2300
0.25"
115
1
1/2 HP
LOCATED ON ROOF
REF 4
ILG
CRBA 13
2300
0.25"
115
1
1/2 HP
LOCATED ON ROOF
REF 5
ILG
CRBA -24
5600
0.25"
115
1
1/8 HP
LOCATED ON ROOF
REF 5
ILG
CRBA -24
5600
0.25"
115
1
1/8 HP
LOCATED ON ROOF
EXHAUST FAN SCHEDULE
MARK
MANF.
MODEL
CFM
S.P.
VOLTS
PHASE
Hp /A
NOTES
I- : Qco
C
W
0
+.�
I
va
0 co
0
r
N
,. H
WG
a
C.
Ct
LB
NO
1.4 A
LOCATED ON CEILING
EF 1
BROAN
L150
130
0.375"
115
1
EF 2
BROAN
L150
130
0.375"
115
1
1.4 A
LOCATED ON CEILING
EF 3
BROAN
L150
130
0.375"
115
1
1.4 A
LOCATED ON CEILING
INTAKE HOOD SCHEDULE
MARK
MANF.
MODEL
CFM
SP
SIZE
WT
NOTES
I- : Qco
C
W
0
+.�
I
va
0 co
0
r
N
,. H
WG
a
C.
Ct
LB
NO
IH -1
GREENHECK
FOR
6,650
0.086
46 "x46"
139
ON ROOF
IH 2
GREENHECK
FGR
6930
0.086
46 "x46"
139
ON ROOF
rh.71 727 SUU KLNYUN SEATTLE WASHINGTON 98108 (206) 763 - 1744 FAX (206) 763 - 2389
NOT PUBLISHED. ALL RIGHTS RESERVED. THE
DRAWING AND SPECIFICATIONS, IDEAS, DESIGNS.
AND ARRANGEMENTS REPRESENTED THEREBY
ARE AND SHALL REMAIN THE PROPERTY OF EVE-
RGREEN REFRIGERATION INC. NO PART THEREOF
SHALL BE REPRODUCED, COPIED, ADAPTED, DISC-
LOSED OR DISTRIBU TED TO OTHERS, SOLD, PUB-
LISHED OR OTHERWISE USED WITHOUT THE PRIOR
WRITTEN CONSENT OF AND APPROPRIATE COMPEN-
SATION TO EVERGREEN REFRIGERATION INC. VISUAL
CONTACT WITH THE ABOVE DRAWINGS OR SPECIFIC-
ATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE
OF ACCEPTANCE [IF THESE RESTRICTIONS.
I- : Qco
C
W
0
+.�
I
va
0 co
0
r
N
,. H
I-
a
C.
Ct
REVISIONS
NO
DATE
ITEM
r
Li
DRAWING DATE:
08/27/08
U
DWG. BY:
GN
CHK. BY:
R B
JOB NO.:
58021
DWG. FILE:
58021M1-
SHEET: M 1
OF 2 SHEETS
VICINITY MAP
;ALE : NONE
MARK
RTU 2
RTU 2
RTU 3
NOTE: 1. PACKAGED ROOFTOP UNIT.
2. ALL POWER WIRING (BY E.C.)
3. PROVIDE 100% O.A. ECONOMIZER & ROOFCURB.
4. PROVIDE SMOKE DETECTOR IN MAIN RETURN DUCT (WIRING BY E.C.)
0
0
0
0
5
�s®
0
0
0
MANE.
LENNOX
LENNOX
LENNOX
MODEL
TGA 150S2BH 12.5 5,000
TGA 150S2BH 12.5 5,000
TGA 150S2BH
TGA048S2DM
n 0
TONS.
12.5
4
AIRFLOW
CFM
5,000
1135
0
SP
WC CFM Hp NUMBER
0.8"
0.8"
0.8"
0.4"
SCALE : 1/32" = 1' -0"
17
MIN. OSA
1,000
1,000
1,000
320
0
0.5
HVAC FLOOR PLAN
Motor
GAS PACKAGE EQUIPMENT SCHEDULE
DRIVE
#6
#6
#6
LOW
TOTAL
BTUH
145,000
145,000
145,000
50,000
COOLING
SEER
13.0
EER
9.5
9.5
9.5
11.0
INPUT
BTUH
240,000
240,000
240,000
105,000
HEATING
OUTPUT
BTUH
192,000
192,000
192,000
84,000
80%
80%
80%
80%
SCOPE OF WORK(SEE M2)
fremmem
AFUE VOLTS PHASE
460
460
460
460
ELECTRICAL
30
30
30
30
M.C.A.
(A)
MO UNIT
m
� �
31
31
31
11
0
0
0
0
0
0
9
0
(PIPIE ON ROOF)
LBS
1,402
1,402
1,402
633
EGON
LBS
47
36
WEIGHT
CURB
LBS
126
126
126
100
TOTAL
LBS
1,575
1,575
1,575
769
Fi PIT
Permit No.
Mar roview approval Is subject to errors and orn!sslons.
Approval of construction documents does not authorize
the violation of any adopted code or ordinar!ce. Rnos1"t
of approved Field dopy and conditions is ack iew;r i z,: :
By Cc,�
g`,�iS ons
will roquiro a view nl n
h gat-
•c y include additional plan rn "■
NO. (LxWxD)
4 (18" x 24" x 2 ")
4 (18" x 24" x 2 ")
4 (18" x 24" x 2 ")
4 (16" x 20" x 2 ")
FILTER SIZES
Date:
City of Tukwila
6Uq NG D VON
NOTES
1,2,3,4
1,2,3
i
frARATE PEHMi °f
ffEQiu ;F1 D FOR:
l IVJeehanicat
i Electrical
i
1 / PIurnbi� (g
+LL.� Gas Pipinr,
DUCTWORK
GENERAL NOTES
1.1 ALL DUCT DIMENSIONS ON PLAN ARE CLEAR INSIDE DIMENSIONS, ADD 2" TO EACH
DIMENSION TO OBTAIN OUTSIDE DIMENSION. ADD 4 "TO EACH DIMENSION IF
DUCTWORK IS ON THE EXTERIOR OF BUILDING.
1.2 THE FIRST NUMBER ON ALL DUCT DIMENSIONS IS THE WIDTH AND THE SECOND
NUMBER IS THE HEIGHT.
1.3 MATERIALS WITHIN DUCTS OR PLENUMS SHALL HAVE A FLAME SPREAD RATING
LESS THAN 25 AND A FLAME SMOKE DEVELOPMENT RATING LESS THAN 50, PER
IMC 602.2.1.
1.4 SEAL ALL TRANSVERSE JOINTS FOR DUCTWORK WITH STATIC PRESSURE BETWEEN
1/2 INCHES AND 2 INCHES. DUCTWORK WHICH IS DESIGNED TO OPERATE AT
PRESSURES ABOVE 1/2 INCH WATER COLUMN STATIC PRESSURE SHALL BE SEALED
IN ACCORDANCE WITH STANDARD RS -7.
1.5 ALL DUCT GAUGES PER SMACNA, IMC 603-4.
1.6 ALL DUCT SUPPORTS PER SMACNA, IMC 603 -10.
1.7 ATTACH DIFFUSERS AND GRILLES TO T -BAR GRID PER WA STATE & LOCAL CODES.
1.8 BALANCING DAMPERS ARE TO BE INSTALLED ON ALL BRANCH DUCTS OR DIFFUSERS.
INSULATION
2.1 INSULATE OR LINE DUCTWORK PER WA. STATE ENERGY AND MECHANICAL CODES.
2.2 INSULATE REFRIGERANT & CONDENSATE PIPING PER STATE & LOCAL ENERGY CODES.
GENERAL CONTRACTOR
3.1 GENERAL CONTRACTOR TO PROVIDE AND CUT OPENINGS FOR ALL ROOFTOP,
CEILING, FLOOR, AND WALL PENETRATIONS, INCLUDING WEATHERPROOF SEALING
AND FIRE PROOF LINING PER IMC & IBC.
3.2 GENERAL CONTRACTOR TO VERIFY PENETRATION LOCATION AND DIMENSIONS
WITH ERL BEFORE FRAMING OPENINGS.
3.3 GENERAL CONTRACTOR TO PROVIDE ALL DEMOLITION, PATCHING, AND PAINTING
AS REQUIRED FOR MECHANICAL WORK.
3.4 GENERAL CONTRACTOR TO PROVIDE ADEQUATE STRUCTURAL SUPPORT AS
REQUIRED FOR MECHANICAL WORK.
3.5 GENERAL CONTRACTOR TO PROVIDE ADEQUATE ENGINEERING AS REQUIRED FOR
MECHANICAL WORK.
3.6 GENERAL CONTRACTOR TO PROVIDE SERVICE ACCESS PER CODE TO ALL
MECHANICAL EQUIPMENT.
3.7 GENERAL CONTRACTOR TO LEVEL ALL FACTORY CURBS PROVIDED BY ERL PROVIDE
ALL CANT STRIPS AND CURB INSULATION, AND SEAL AGAINST LEAKS.
3.8 GENERAL CONTRACTOR TO PROVIDE ALL CUTTING AND PATCHING OF T -BAR CEILING
AS REQUIRED FOR HVAC INSTALLATION.
3.9 GENERAL CONTRACTOR TO PROTECT ALL OPENINGS THROUGH FLOORS PROVIDED
FOR DUCTWORK INSTALLATION IN ACCORDANCE WITH TABLE 601 OF INTERNATIONAL
BUILDING CODE, WHERE REQUIRED BY SECTION 707 OF IBC.
ELECTRICAL
4.1 ERL TO INSTALL ALL LOW VOLTAGE CONTROL WIRING, CONDUIT WILL BE PROVIDED
BY ELECTRICAL CONTRACTOR.
4.2 ELECTRICAL CONTRACTOR TO PROVIDE ALL ELECTRICAL CONNECTIONS,
DISCONNECTS, AND STARTERS FOR MECHANICAL EQUIPMENT.
4.3 ELECTRICAL CONTRACTOR TO VERIFY EQUIPMENT SIZES, LOADS AND LOCATIONS
WITH ERL MECHANICAL PLAN AND WITH FIELD CONDITIONS.
4.4 ELECTRICAL CONTRACTOR TO INTERLOCK BATHROOM EXHAUST FANS WITH LIGHT
SWITCH.
4.5 ERL TO PROVIDE 7 -DAY NIGHT SETBACK, PROGRAMMABLE TYPE T -STAT WITH
CAPABILITY OF 5 °F DEADBAND.
4.6 ERL TO VERIFY FINAL LOCATION OF THERMOSTAT WITH CUSTOMER.
4.7 ELECTRICAL CONTRACTOR TO PROVIDE ELECTRICAL GCFI OUTLET WITHIN 25 FT
OF EACH PIECE OF MECHANICAL EQUIPMENT.
PLUMBING
5.1 PLUMBING CONTRACTOR TO FURNISH AND INSTALL ALL GAS PIPING FOR
MECHANICAL EQUIPMENT PER CODE.
5.2 PLUMBING CONTRACTOR OFFSET VENTS 10 FEET MINIMUM FROM ALL HVAC FRESH
AIR INTAKES OR 2' ABOVE HIGHEST POINT OF INTAKE, IMC 401.5.1.
5.3 CONDENSATE DRAINS FROM RTU BY ERI TO DRAIN WITHIN 12" OF UNIT.
CONDENSAT E DRAINS FOR AIR HANDLERS BY PLUMBER.
ENERGY CODE COMPLIANCE
6.1 AT A MINIMUM, EACH FLOOR IS TO BE CONSIDERED A SEPARATE ZONE. VERIFY
THERMOSTATIC CONTROL FOR EACH ZONE AS INDICATED ON PLANS.
6.2 OUTSIDE AIR INTAKES, EXHAUST OUTLETS, AND RELIEF OUTLETS SERVING
CONDITIONED SPACES SHALL BE EQUIPPED) WITH DAMPERS WHICH CLOSE
AUTOMATIC, ,LLY WHEN THE SYSTEM IS OFF OR UPON POWER FAILURE,
PER WSEC SEC. 1412.4.1.
6.3 AIR ECONOMIZERS WHERE REQUIRED BY CODE ARE INDICATED BY THE EQUIPMENT
SCHEDULE AT 100% CAPABILITY, CONTROL AND OPERATION OF THE ECONOMIZER
SHALL COMPLY WITH WSEC SEC. 1423.
MECHANICAL CODE COMPLIANCE
7.1 WHERE REQUIRED PROVIDE AUTOMATIC SHUTOFF ACTIVATED BY SMOKE DETECTORS
IN EACH SYSTEM DELIVERING HEATING OR COOLING AIR IN EXCESS OF 2000 CFM.
DETECTORS SHALL BE LOCATED IN THE MAIN RETURN AIR PER IMC 606.
WA2004 #1
U
w
riAY1
E
RT
Cry
Lil
CD
J
rz.A
12"
G
•
A
12.5 TON
HVA
SCALE : 1/8"
El-
1' -0"
/4 I I /""`" I Wil71,7# r
26"
16"
T\ 1000 CFM
(TYP 5)
z
24"
X 14" EXISTING
FLOOR PLAN
2300 CFM
20" VTR
SPIRAL
4 EF)
2300 CFM
20" VTR
i
22"
1
20"
12"
12"
SPIRAL
24"
ti
- - - -- - - -- - -- - - - - - -_ - - - - - -_ CHILLER—
46 "x46"
6650 CFM
5600 CFM
20" VTR
20" ` � 16 ,.
20"
26"
46 "x46"
6650 CFM
G
3/4"
r
P
1
13/4"
L_ 2300_CFM-
20" VTR I G
12"
1000 CFM
N f GYP 5)
12"
2300 CF VI
2p" VTR
20"
— _CHIL+ER
x;1I
4
� -1
G
WAREHOUSE AND
FABRICATION
1/4"
it
5600 CFM
20" VTR
r
12 "
r
--- XISTING
II
PIPE INSIDE
ELI
SPACE
G
L L)
1 -1/4"
EF
DROP FROM ROfF
V A
s _
a
cor j,
2 cl
SEP d4 2U10
PERMIT CENT
U
w
NOT PUBLISHED. ALL RIGHTS RESERVED. THE
DRAWING AND SPECIFICATIONS, IDEAS, DESIGNS
AND ARRANGEMENTS REPRESENTED THEREBY
ARE AND SHALL REMAIN THE PROPERTY OF EVE-
RGREEN REFRIGERATION INC. NO PART THEREOF
SHALL BE REPRODUCED, COPIED, ADAPTED, DISC-
LOSED OR DISTRIBUTED TO OTHERS, SOLD, PUB-
LISHED OR OTHERWISE USED WITHOUT THE PRIOR
WRITTEN CONSENT OF AND APPROPRIATE COMPEN-
SATION TO EVERGREEN REFRIGERATION INC. VISUAL
CONTACT WITH THE ABOVE DRAWINGS OR SPECIFIC-
ATIONS SHALL CONSTITUTE CONCLUSIVE EVIDENCE
OF ACCEPTANCE OF THESE RESTRICTIONS.