HomeMy WebLinkAboutPermit PG08-092 - AT&T MOBILITYAT &T MOBIUTY
16425 SOUTHCENTER PY
PGO8-092
Parcel No.:
Address:
Suite No:
CitAf Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
PLUMBING /GAS PIPING PERMIT
5379200290
16425 SOUTHCENTER PY TUKW
Permit Number:
Issue Date:
Permit Expires On:
PG08 -092
05/13/2008
11/09/2008
Tenant:
Name:
Address:
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
AT &T MOBILITY
16425 SOUTHCENTER MALL , TUKWILA WA
ARGUS GROUP LTD
C/O METROVATION , 225 108TH AVE NE #520
SAMSON HU
4 HUTTON CENTER DR STE 800 , SANTA ANA CA
C B BOVENKAMP
9002 SW 152ND ST , MIAMI FL
Contractor License No: CBBOVI *006D8
Phone:
Phone: 714- 327 -4203
Phone:
Expiration Date: 08/30/2009
DESCRIPTION OF WORK:
INSTALL TWO NEW RESTROOMS
Value of Plumbing /Gas Piping:
Fees Collected:
$15,000.00
$226.00
Plumbing
Bathtub or combination bath/shower
Bidet
Clothes washer, domestic
Dental unit, cuspidor
Dishwasher, domestic, with independent drain
Drinking fountain or water cooler (per head)
Food -waste grinder, commercial
Floor drain
Shower, single head trap
Lavatory
Wash fountain
Receptor, indirect waste
Sinks
Urinals
Water Closet
Uniform Plumbing Code Edition: 2006
International Fuel Gas Code Edition: 2006
FIXTURE TYPE AND QUANTITY
Plumbing (cont.)
0 Building sewer and each trailer park sewer 0
0 Rain water system - per drain (inside bldg) 0
0 Water heater and/or vent 1
0 Industrial waste treatment interceptor, including
0 its trap and vent, except for kitchen type
1 grease interceptors 0
0 Repair or alteration of water piping and/or water
0 treatment equipment 0
0 Repair or alteration of drainage or vent piping 0
2 Medical gas piping system serving (1 -5)
0 inlets /outlets for a specific gas 1
0 Medical gas piping (6 +) inlets /outlets 1
1 Gas Piping
0 Gas piping outlets (0 -5) 0
2 Gas piping outlets (6 +) 0
* *continued on next page **
doc: UPC -10/06
PG08 -092 Printed: 05 -13 -2008
City ot Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: htql://www.ci.tukwila.wa.us
Permit Number: PG08 -092
Issue Date: 05/13/2008
Permit Expires On: 11/09/2008
Permit Center Authorized Signature:
Date:
611,31,z
I hereby certify that I have read and e : - ed this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied , whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or t erformance yf work. J9am authorized to sign and obtain this plumbing /gas piping permit.
Signature:
Print Name:
k2 L J
C1' 0114/2-5
Date: /3 Dg
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: UPC -10/06
PG08 -092 Printed: 05-13 -2008
Parcel No.: 5379200290
Address:
Suite No:
Tenant:
• 0
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
16425 SOUTHCENTER PY TUKW
AT &T MOBILITY
PERMIT CONDITIONS
Permit Number:
Status:
Applied Date:
Issue Date:
PG08 -092
ISSUED
03/21/2008
05/13/2008
1: ** *PLUMBING AND GAS PIPING * **
2: No changes shall be made to applicable plans and specifications unless prior approval is obtained from the Tukwila
Building Division.
3: All permits, inspection records and applicable plans shall be maintained at the job and available to the plumbing
inspector.
4: All plumbing and gas piping systems shall be installed in compliance with the Uniform Plumbing Code and the Fuel Gas
Code.
5: No portion of any plumbing system or gas piping shall be concealed until inspected and approved.
6: All plumbing and gas piping systems shall be tested and approved as required by the Plumbing Code and Fuel Gas Code.
Tests shall be conducted in the presence of the Plumbing Inspector. It shall be the duty of the holder of the permit to
make sure that the work will stand the test prescribed before giving notification that the work is ready for inspection.
7: No water, soil, or waste pipe shall be installed or permitted outside of a building or in an exterior wall unless,
adequate provision is made to protect such pipe from freezing. All hot and cold water pipes installed outside the
conditioned space shall be insulated to minimum R -3.
8: Plastic and copper piping running through framing members to within one (1) inch of the exposed framing shall be
protected by steel nail plates not less than 18 guage.
9: Piping through concrete or masonry walls shall not be subject to any load from building construction. No plumbing
piping shall be directly embedded in concrete or masonry.
10: All pipes penetrating floor /ceiling assemblies and fire - resistance rated walls or partitions shall be protected in
accordance with the requirements of the building code.
11: Piping in the ground shall be laid on a firm bed for its entire length. Trenches shall be backfilled in thin layers to
twelve inches above the top of the piping with clean earth, which shall not contain stones, boulders, cinderfill,
frozen earth, or construction debris.
12: The issuance of a permit or approval of plans and specifications shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the Plumbing Code or Fuel Gas Code or any other ordinance of the
jurisdiction.
* *continued on next page **
doc: Cond -10/06
PG08 -092 Printed: 05 -13 -2008
• •
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances governing
this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws regulating
construction or the performance of work.
Signature:
Print Name:
4
fOs -,-G 0/0,14 /35
Date: /3-t08
doc: Cond -10/06
PG08 -092 Printed: 05-13 -2008
CITY OF TUKWIL
Community De velopmen.department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.ci.tukwila.wa.us
Plurnbing/G Permit No. -V63 `L�CI.�
Project No
(For office use only,
PLUMBING / GAS PIPING PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
SITE LOCATION
King Co Assessor's Tax No.:
Site Address: t /' 4� 5 �j 1 T� G-V-N1V2, r i IA/A Y Suite Number:
Tenant Name: AT 8 T.
Property Owners Name: $ M /V 4 L r(
17-0 - t,t -r kt2- , k-c
Mailing Address:
Floor:
New Tenant: [5.... Yes ❑ ..No
City
State
Zip
CONTACT PERSON
—Who do
hen, your permit is ready to b
Name:
4 M 'fN H1A . Day Telephone: —74 7j2 7 4--ZO �??
Mailing Address: (-{-t (TTT ZW1 f7i21 vt gam% .,a , w, (4 . 1;7
City State p
E -Mail Address: Fax Number: 7/4 •? 1
PLI M S PIP NG CON'T'RACTOR INFOI
Company Name:
T7 t2
Mailing Address:
City
Day Telephone:
Fax Number:
Expiration Date:
Contact Person:
E -Mail Address:
Contractor Registration Number:
Company Name: t-1-0.-1-1M4 f�
Mailing Address: 4 Gof 170 V.� Q- PU e -4t i. A if 41 0 • 17,70,
City State zip
Contact Person: Day Telephone: 714 i 7
E -Mail Address: Fax Number: r
State
Zip
Company Name: _ �1
Mailing Address: 4 4-kirj" rn\I i t Vt 4rV 0 AIA • 1; %/%
City State `Lip
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
+ tip
LiG7•
Q:\Applications\Forms- Applications On Line \3 -2006 - Plumbing -Gas Piping Permit Application.doc
Revised: 4 -2006
bh
Page 1 of 2
Valuation of Project (contractor's bid price): $ 7 to 1,
Scope of Work (please provide detailed information): , kJ 4f A i (. -fj /
Building Use (per Intl Building Code): 1 C-`'j'jv tt 43:14 1 L
Occupancy (per Int'l Building Code): Nl _ nit v_12..eA 1.1
Utility Purveyor: Water: Sewer:
Indicate type of plumbing fixtures and/or gas piping outlets being installed and the quantity below:
Fixture Type:
Qty
Fixture Type:
Qty
Fixture Type:
Qty
Fixture Type:
Qty
Bathtub or combination
bath/shower
Drinking fountain or water
cooler (per head)
Wash fountain
Gas piping outlets
Bidet
Food -waste grinder,
commercial
Receptor, indirect
waste
Clothes washer, domestic
Floor drain
Sinks
J
Dental unit, cuspidor
Shower, single head trap
Urinals
Dishwasher, domestic,
with independent drain
Lavatory
Water Closet
Z.
Building sewer or trailer
park sewer
Rain water system — per
drain (inside building)
Water heater and /or
vent
Additional medical gas
inlets /outlets — six or more
Industrial waste
pretreatment interceptor,
including its trap and vent,
except for kitchen type
grease interceptors
Repair or alteration of water
piping and /or water treating
equipment
Repair or alteration
of drainage or vent
piping
I
Medical gas piping system
serving one to five
inlets /outlets for specific gas
PERMIT APPLICATION A
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 180 days. The extension shall be requested in writing
and justifiable cause demonstrated. Section 103.4.3 International Plumbing Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWN OR 60,00 UTHO RIIIZEDAGENT:
Print Name: 4,i, V M .
Signature:
Mailing Address:
Date: 7tt
Day Telephone:
City
State
Zip
Date Application Accepted:
.S--€?` 1 -
Date Application Expires:
9--)-( -U E/
Staff Initials:
Q:Wpplications\Forms- Applications On Line'3 -2006 - Plumbing -Gas Piping Permit Application doc
Revised. 4 -2006
bh
Page 2 of 2
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http../Iwww.ci.tukwila.wa.us
SET RECEIPT
RECEIPT NO: R08 -01579
Initials: WER
User ID: 1655
Payee: CB BOVENKAMP, INC.
Payment Date: 05/13/2008
Total Payment: 1,515.50
SET ID: 0513 SET NAME: AT &T MOBILITY
SET TRANSACTIONS:
Set Member Amount
D08 -149 1,056.50
M08 -087 271.00
PG078:50794 188.00
TOTAL: 1,515.50
TRANSACTION LIST:
Type Method Description Amount
Payment Check 42109
ACCOUNT ITEM LIST:
Description
TOTAL:
1,515.50
1,515.50
Account Code Current Pmts
BUILDING - NONRES
MECHANICAL - NONRES
PLUMBING - NONRES
STATE BUILDING SURCHARGE
000/322.100 1,052.00
000.322.102.00.0 271.00
000.322.103.00.0 188.00
000/386.904 4.50
TOTAL: 1,515.50
2339 05/13 9711 TOTAL 1515°50
Doc: RECSETS -06
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 5379200290 Permit Number: PG08 -092
Address: 16425 SOUTRCENTER PY TUKW Status: PENDING
Suite No: Applied Date: 03/21/2008
Applicant: AT &T MOBILITY Issue Date:
Receipt No.: R08 -00978
Payment Amount: $38.00
Initials: WER Payment Date: 03/31/2008 09:48 AM
User ID: 1655 Balance: $188.00
Payee: DAN GRUBB
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 1013 38.00
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
PLAN CHECK - NONRES
000/345.830 38.00
Total: $38.00
53 03/31 Till TOTAL. 789.55
ti))
rtnc: Renaint -OA
Printed. 03- 31 -2nnR
3 INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
PERMIT NO.
(206)431 -3640
Project:
Type of Inspection:
Address:
1(,L125 S
kke
APL,
Date Called:
Special Instructions:
/
Date Wanted:
io -2O -ems
m
Requester:
Phone No:
-305 -es-le,
Approved per applicable codes. El Corrections required prior to approval.
COMMENTS:
e U
Inspe tor: Date: r
ri $60.00 REINSPECTION FEE REQ IRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., S ite 100. Call to schedule reinspection.
Receipt No.: !Date:
I_.INSPECTION RECORD n�oz n��
((Retain a copy with permit J/
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION Y-
6300•Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -36 ?0
Project: �, ... .`
Type Inspec ion: _
Address: I
6445 S( P4'
Date Called:l
A- (otJ,.n ,,-) do
Special Instructions:
Date Wanted:
• 1 • v�
(a.m.
p.m.
Requester:
`l/CJc---
7
Phone Phone -
I Q ' Y3S
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
60 pJ-,)
?-07)0
,_)A„
1? / ,y f i_i_L__ 4 -44__.
' Alp/ :i (Pe-.S. d 1
T
r
`l/CJc---
7
r
S- , 71 p J
t
A
Inspect':
Dater r? C
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
•
Date:
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
PGo.s 1
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
(206)431 -36(7
Pro'e.t: .Tr
� Type of Inspection: / ``
Address:
14 ZS� c- , P
Date Called:
_.-
Special Instructions:
Date Wanted: Fa m'
X'- 2 I- v r p.m.
Requester:
Phone No:
_ 305 '?1( -'r ?3I -
Approved per applicable codes.
Correc • • equ
r o‘Woval.
COMMENTS:
r/%
J or/fit
I Ca" /-
f
I:13 nsr-Q
4
6 IAAJ
A.9 r rv‘ie.t)'
IJ`
liNe__AO
>1-,
, iL p o
4,--
.Q
,G- 1-; ( F
` `'
, G Jri
Inspect
kak
Date:
0 $60.00 REINSPECTION FEE EdUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
oP ERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: PG08 -092 DATE: 04 -01 -08
PROJECT NAME: AT &T MOBILITY
SITE ADDRESS: 16425 SOUTHCENTER PY
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # After Permit Issued
DEPARTMENTS.
,4-
:U1 A in• Division
P.Dblip Works �f � 0
Fire Prevention n Planning Division
Structural
n Permit Coordinator
1_i
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Incomplete
n
DUE DATE: 04 -03 -08
Not Applicable
n
Permit Center Use Only
INCOMPLETE LETTER MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
LETTER OF COMPLETENESS MAILED:
TUES/THURS ROUTING:
Please Route
Structural Review Required
REVIEWER'S INITIALS:
No further Review Required
DATE:
APPROVALS OR CORRECTIONS:
Approved
Notation:
DUE DATE: 05-01 -08
Approved with Conditions Not Approved (attach comments)
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents /routing slip.doc
2 -28 -02
Look Up a Contractor, Electri n or Plumber License Detail
Washington State Department of Labor and Industries
General/Specialty Contractor
A business registered as a construction contractor with L &I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
License Information
License
CBBOVI *006D8
Licensee Name
C B BOVENKAMP MC
Licensee Type
CONSTRUCTION CONTRACTOR
UBI
601998279
Ind. Ins. Account Id
#2
Business Type
CORPORATION
Address 1
9002 SW 152ND ST
Address 2
City
MIAMI
County
OUT OF STATE
State
FL
Zip
33157
Phone
3052334438
Status
ACTIVE
Specialty 1
GENERAL
Specialty 2
UNUSED
Effective Date
3/28/2000
Expiration Date
8/30/2009
Suspend Date
Separation Date
Parent Company
Previous License
Next License
Associated License
Business Owner Information
Name
Role
Effective Date
Expiration Date
BOVENKAMP, ESTHER
Cancel
Date
01/01/1980
Bond
Amount
BOVENKAMP, GERALD
#2
01/01/1980
08473969
Bond Information
Bond
Bond
Company
Name
Bond
Account
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Bond
Amount
Received
Date
#2
FIDELITY &
DEPOSIT CO
OF MD
08473969
08/30/2001
Until
Cancelled
$12,000.00
08/30/2001
Page 1 of 2
https: // fortress. wa. gov /lni/bbip /printer.aspx ?License= CBBOVI *006D8 05/13/2008
HVAC SYMBOLS
DUCTWORK
z
12 "o ( ROUND DUCTWORK. DIAMETER INDICATED IN INCHES
20X12
x
MIX
MP%
MIR
MEW
lir
LAI
e
BDD
i
UP
i
DN
RE: I 2/M0.01 i
LINEAR SLOT
(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)
SUPPLY DIFFUSER, 4 -WAY
SUPPLY DIFFUSER, 2 -WAY
RETURN GRILLE
EXHAUST GRILLE
SUPPLY WALL REGISTER
RETURN /EXHAUST WALL REGISTER
RECTANGULAR DUCTWORK. SIZE INDICATED IN
INCHES FIRST NUMBER IS SIDE SHOWN
RECTANGULAR DUCTWORK. SIZE INDICATED IN
INCHES FIRST NUMBER IS SIDE SHOWN. DASHED
LINES INDICATE ACOUSTICAL LINER. DIMENSIONS
INDICATES CLEAR INSIDE DIMENSIONS
SUPPLY OR OUTSIDE AIR DUCT
RETURN AIR DUCT
RELIEF OR EXHAUST AIR DUCT
SUPPLY OR OUTSIDE AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT DOWN
RETURN AIR DUCT UP
RETURN AIR DUCT DOWN
RELIEF OR EXHAUST AIR DUCT UP
RELIEF OR EXHAUST AIR DUCT DOWN
IN -LINE 90 DEGREE DROP (RISE) IN DUCT
INCLINED RISE IN DUCT
INCLINED DROP IN DUCT
ELBOW WITH VANES
FLEXIBLE DUCT
FIRE DAMPER
MOTORIZED DAMPER
BACKDRAFT DAMPER
POINT OF DISCONNECT
POINT OF CONNECTION - NEW TO EXISTING
TERMINAL AIR UNIT
HHW (AS APPLICABLE)
DEMOLITION
TEMPERATURE SENSOR
THERMOSTAT
DUCT MOUNTED SMOKE DETECTOR
DRAWING /DETAIL REFERENCE KEY
REFER TO
DRAWING /DETAIL NUMBER
2
M0.01
SHEET NUMBER OF DRAWING /DETAIL
PLAN NOTE REFERENCE
FURNISHED & INSTALLED BY MECHANICAL
FURNISHED BY MECHANICAL INSTALLED BY ELECTRICAL
FURNISHED BY ELECTRICAL INSTALLED BY MECHANICAL
FURNISHED & INSTALLED BY ELECTRICAL
c
12 "0 )
c
.) 20X12
20X12
C �C
P
C
DN
HVAC ABBREVIATIONS (ALL ABBREVIATIONS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)
A
ABV
AC
ACCU
ADJ
AD
AFF
AH
AL
AMPS
AP
APD
APPROX
ARCH
AS
ASHRAE
AUX
AV
B
B
BDD
BD
BEL
BFF
BFV
BFW
BHP
BKR
BLDG
BOD
BOP
BOS
BTU
BV
C
CA
CAP
CAV
CC
CD
CFH
CFM
CH
CHWR
CHWS
CHWP
CI
CIRC
CLG
CMU
CO
COL
COP
COND
CP
CPVC
CR
CT
CU
CW
CWS
CWR
CWP
'C
D
D
DB
dB
DDC
DESIG
DEG
DIA
DIM
DISC
DISCH
DN
DP
DPS
DS
DWG(S)
DX
E
(E)
EER
EA
EAT
ECC
EDB
EF
EFF
EG
EL
ELEC
ENCL
EQUIP
ESP
ET
EV
EWB
EWR
EWT
EXH
EXT
EXP. JOINT
ABOVE
AIR CONDITIONING
AIR COOLED CONDENSING UNIT
ADJUSTABLE
ACCESS DOOR
ABOVE FINISHED FLOOR
AIR HANDLING
ALUMINUM
AMPERES
ACCESS PANEL
AIR PRESSURE DROP
APPROXIMATE
ARCHITECT, ARCHITECTURAL
AIR SEPARATOR
AMERICAN SOCIETY OF HEATING, REFRIGERATING
AND AIR CONDITIONING ENGINEERS
AUXILIARY
AIR VENT
BOILER
BACKDRAFT DAMPER
BLOW -DOWN
BELOW
BELOW FINISHED FLOOR
BUTTERFLY VALVE
BOILER FEED WATER
BRAKE HORSEPOWER
BREAKER
BUILDING
BOTTOM OF DUCT
BOTTOM OF PIPE
BOTTOM OF STEEL
BRITISH THERMAL UNIT
BALL VALVE
COMPRESSED AIR
CAPACITY
CONSTANT AIR VOLUME
COOLING COIL
CEILING DIFFUSER
CUBIC FEET PER HOUR
CUBIC FEET PER MINUTE
CHILLER
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER PUMP
CAST IRON
CIRCULATING
CENTERLINE
CEILING
CONCRETE MASONRY UNIT
CLEANOUT
COLUMN
COEFFICIENT OF PERFORMANCE
CONDENSATE
CONDENSATE PUMP
CHLORINATED POLYVINYL CHLORIDE
CONDENSATE RECEIVER
COOLING TOWER
CONDENSING UNIT
COLD WATER
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER PUMP
DEGREES CELSIUS
DEPTH
DRY BULB
DECIBEL
DIRECT DIGITAL CONTROL
DESIGNATION
DEGREE
DIAMETER
DIMENSION
DISCONNECT
DISCHARGE
DOWN
DIFFERENTIAL PRESSURE
DIFFERENTIAL PRESSURE SWITCH
DOWNSPOUT
DRAWING(S)
DIRECT EXPANSION
EXISTING TO REMAIN
ENERGY EFFICIENCY RATIO
EXHAUST AIR, EACH
ENTERING AIR TEMPERATURE
ECCENTRIC
ENTERING DRY BULB
EXHAUST FAN
EFFICIENCY
EXHAUST GRILLE
ELEVATION
ELECTRICAL
ENCLOSURE
EQUIPMENT
EXTERNAL STATIC PRESSURE
EXPANSION TANK
EXHAUST VALVE
ENTERING WET BULB
EXHAUST WALL REGISTER
ENTERING WATER TEMPERATURE
EXHAUST
EXTERNAL
EXPANSION JOINT
FA
FACP
FC
FCO
FD
FLA
FLR
FPI
FPM
FS
FSD
FT
F
FV
FW
G
G
GA
GAL
GALV
GC
GPH
GPM
GV
H
H
HB
HC
HD
HHWR
HHWS
HHWP
HOA
HORIZ
HP
HS
HSTAT
HSTM
HTG
HTR
HVAC
HW
HYD
HX
HZ
ID
IE
IN
IN WG
IN WC
J
J -BOX
K
KW
KWH
L
LAT
LB(S),#
LDB
LF
LP
LRA
LSTM
LTG
LWB
LWT
M
MAX
MBH
MCA
MCC
MD
MECH
MFR
MG
MH
MIN
MTD
MU
MUA
MZ
N
N/A
NC
NEMA
NIC
NO
NO.
NOM
NTS
0
OBD
OC
OD
OF
OH
OPNG
OPER
OSA
OSHA
FIRE ALARM
FIRE ALARM CONTROL PANEL
FAN COIL
FLOOR CLEANOUT
FIRE DAMPER, FLOOR DRAIN
FULL LOAD AMPS
FLOOR
FINS PER INCH
FEET PER MINUTE
FLOW SWITCH, FLOOR SINK
FIRE -SMOKE DAMPER
FOOT, FEET
DEGREE FAHRENHEIT
FACE VELOCITY
FEED WATER
(NATURAL) GAS
GAUGE
GALLON
GALVANIZED
GENERAL CONTRACTOR
GALLONS PER HOUR
GALLONS PER MINUTE
GRAVITY VENTILATOR
HEIGHT, HUMIDISTAT
HOSE BIBB
HEATING COIL
HEAD, HUB DRAIN
HEATING HOT WATER RETURN
HEATING HOT WATER SUPPLY
HEATING HOT WATER PUMP
HAND -OFF- AUTOMATIC
HORIZONTAL
HORSEPOWER, HEAT PUMP
HUMIDITY SENSOR
HUMIDISTAT
HIGH PRESSURE STEAM
HEATING
HEATER
HEATING, VENTILATING AND AIR CONDITIONING
HOT WATER
HYDRANT
HEAT EXCHANGER
HERTZ
INSIDE DIAMETER
INVERT ELEVATION
INCH
INCHES WATER GAUGE
INCHES OF WATER COLUMN
JUNCTION BOX
KILOWATT
KILOWATT -HOUR
LENGTH
LEAVING AIR TEMPERATURE
POUND(S)
LEAVING DRY BULB
LINEAR FEET
LOW PRESSURE
LOCKED ROTOR AMPS
LOW PRESSURE STEAM (15 PSIG)
LIGHTING
LEAVING WET BULB
LEAVING WATER TEMPERATURE
MAXIMUM
1000 BTU PER HOUR
MINIMUM CIRCUIT AMPACITY
MOTOR CONTROL CENTER
MOTORIZED DAMPER
MECHANICAL
MANUFACTURER
MOTOR GENERATOR
MANHOLE, METAL HALIDE
MINIMUM
MOUNTED
MAKE -UP
MAKE -UP AIR UNIT
MULTI -ZONE UNIT
NOT APPLICABLE
NOISE CRITERIA, NORMALLY CLOSED
NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NOT IN CONTRACT
NORMALLY OPEN
NUMBER
NOMINAL
NOT TO SCALE
OPPOSED BLADE DAMPER
ON CENTER
OUTSIDE DIAMETER
OVERFLOW
OVERHEAD
OPENING
OPERATING
OUTSIDE AIR
U.S. DEPARTMENT OF LABOR OCCUPATIONAL
SAFETY AND HEALTH ORGANIZATION
P
P
PC
PD
PH
PIV
PLBG
PNL
POC
POD
PRESS
PRS
PRV
PS
PSF
PSI
PSIA
PSIG
PSV
PV
PVC
Q
QTY
R
RAD
RA
RCP
RD
RE:
RECIRC
REFRIG
REINF
REQD
REV
RG
RH
RHG
RL
RLA
RM
RPM
RS
RTU
RWR
S
SA
SAN
SD
SECT
SEER
SF
SQFT
SHT
SIM
SHT MTL
SMACNA
SOV
SP
SPEC
SO
SS
ST
STM
STD
STL
STRUC
SURF
SUSP
SV
SWR
SYM
T
TAU
TEMP
TDH
THRU
TP
TS
TSP
TYP
U
U/C
U/F
U/G
U/S
UTR
UL
UON
UPS
V
V
VAC
VAV
VD
VEF
VEL
VERT
VFD
VTR
W
W/
W/0
WB
WC
WPD
WP
WR
WSHP
WT
PUMP
PUMPED CONDENSATE
PRESSURE DROP
PHASE
POST INDICATOR VALVE
PLUMBING
PANEL
POINT OF CONNECTION
POINT OF DISCONNECT
PRESSURE
PRESSURE REDUCING STATION
PRESSURE REDUCING VALVE
PRESSURE SWITCH
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH ABSOLUTE
POUNDS PER SQUARE INCH GAUGE
PRESSURE SAFETY VALVE
PLUG VALVE
POLYVINYL CHLORIDE
QUANTITY
RADIANT
RETURN AIR
REFLECTED CEILING PLAN,
REINFORCED CONCRETE PIPE
ROOF DRAIN
REFERENCE, REFER
RECIRCULATE
REFRIGERANT
REINFORCING
REQUIRED
REVISION, REVISE
RETURN GRILLE
RELATIVE HUMIDITY
REFRIGERANT HOT GAS
REFRIGERANT LIQUID
RUNNING LOAD AMPS
ROOM
REVOLUTIONS PER MINUTE
REFRIGERANT SUCTION
ROOF TOP UNIT
RETURN WALL REGISTER
SUPPLY AIR
SANITARY SEWER
SMOKE DAMPER, STORM DRAIN
SECTION
SEASONAL ENERGY EFFICIENCY RATIO
SUPPLY FAN
SQUARE FEET
SHEET
SIMILAR
SHEET METAL
SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
SHUT OFF VALVE
STATIC PRESSURE
SPECIFICATION
SQUARE
STAINLESS STEEL, SERVICE SINK
SOUND TRAP, STEAM TRAP
STEAM
STANDARD
STEEL
STRUCTURAL
SURFACE
SUSPEND
SUPPLY VALVE
SUPPLY WALL REGISTER
SYMBOL
THERMAL AIR UNIT
TEMPERATURE
TOTAL DYNAMIC HEAD
THROUGH
TOTAL PRESSURE
TEMPERATURE SENSOR
TOTAL STATIC PRESSURE
THERMOSTAT
TYPICAL
UNDER CUT
UNDERFLOOR
UNDERGROUND
UNDERSLAB
UP THROUGH ROOF
UNDERWRITERS LABORATORIES, INC.
UNLESS OTHERWISE NOTED
UNINTERRUPTIBLE POWER SUPPLY
VOLT, VENT
VACUUM
VARIABLE AIR VOLUME
VOLUME DAMPER
VEHICLE EXHAUST FAN
VELOCITY
VERTICAL
VARIABLE FREQUENCY DRIVE
VENT THROUGH ROOF
WATT, WIDTH
WITH
WITHOUT
WET BULB
WATER COLUMN
WATER PRESSURE DROP
WEATHER PROOF
WATER RISER
WATER SOURCE HEAT PUMP
WATERTIGHT, WEIGHT
PLUvBING GENERAL NOTES:
1. THESE DOCUMENTS WERE PREPARED PER AVAILABLE AS -BUILT DOCUMENTS. CONTRACTOR SHALL VISIT SITE
TO BECOME FULLY FAMILIAR WITH THE SCOPE OF WORK AND REVIEW EXISTING CONDITIONS PRIOR TO BID.
2. EXACT LOCATION OF PLUMBING FIXTURES SHALL BE DETERMINED FROM ARCHITECTURAL DRAWINGS.
3. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING CONDITIONS (SIZE, LOCATION, ETC.)
PRIOR TO THE START OF CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE TO NOTIFY THE
ARCHITECT /ENGINEER OF ANY DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND EXISTING CONDITIONS.
4. CONTRACTOR SHALL VERIFY IN FIELD, EXACT SEWER WASTE AND COLD WATER PIPE LOCATIONS.
5. CONTRACTOR SHALL VERIFY INVERT ELEVATIONS OF SEWER POINTS OF CONNECTION PRIOR TO THE
INSTALLATION OF NEW WASTE SYSTEM.
6. CONTRACTOR SHALL VERIFY AND COORDINATE LOCATION OF ALL PLUMBING LINES WITH DUCT WORK AND
ELECTRICAL SERVICES.
7. THE INSTALLATION OF ALL VALVES, UNIONS, THERMOMETERS, GAUGE, OR OTHER INDICATING OR RECORDING
EQUIPMENT, OR SPECIALTIES REQUIRING FREQUENT READING, REPAIRS, ADJUSTMENT, INSPECTION, REMOVAL
OR REPLACEMENT SHALL BE CONVENIENTLY AND ACCESSIBLY LOCATED WITH REFERENCE TO THE FINISHED
BUILDING.
8. ALL VENTS THROUGH ROOF SHALL BE 1O' -0" FROM ALL A/C UNITS OR AIR INTAKES, ETC.
9. CONTRACTOR SHALL NOT CUT, NOTCH AND /OR BORE EXISTING JOIST, BEAMS AND /OR JOIST WITHOUT FIRST
SECURING WRITTEN APPROVAL FROM ARCHITECT.
10. CONTRACTOR SHALL INSTALL DIELECTRIC UNIONS AT ALL CONNECTIONS WITH DISSIMILAR METALS.
11. CONTRACTOR SHALL ROUGH -IN ALL WASTES AND SUPPLIES TO SPECIAL EQUIPMENT ACCORDING TO
MANUFACTURER'S SHOP DRAWINGS AND MAKE FINAL CONNECTIONS. ALL SUPPLIES SHALL BE VALVED.
12. SEISMIC RESTRAINTS SHALL BE REQUIRED ON SEVERAL PIECES OF EQUIPMENT WITHIN THIS PLUMBING FLOOR
PLAN AND ALL REQUIREMENTS SHALL BE OBTAINED FROM THE AUTHORITY HAVING JURISDICTION.
13. INSULATE ALL EXPOSED SUPPLY AND WASTE PIPING AT HANDICAPPED ACCESSIBLE SINKS.
14. REFER TO SHEET M -003 AND M -004 FOR ALL PLUMBING SPECIFICATIONS AND WORK REQUIREMENTS.
15. CONTRACTOR SHALL PERFORM ALL WORK IN A COMPLETE AND WORKMANLIKE WAY IN COMFOMANCE WITH
ALL CODES, AND MANUFACTURER'S RECOMMENDATIONS. CONTRACTOR SHALL COORDINATE WITH ARCHITECTS,
ELECTRICAL AND STRUCTURAL. ALL WORK TO BE PERFORMED TO PROVIDE A COMPLETE AND WORKING
SYSTEM.
16. CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS, FEES, TESTING, ETC. CONTRACTOR SHALL PROVIDE A ONE
YEAR WARRANTY /GURANTEE FOR ALL WORK PERFORMED UNDER THIS CONTRACT.
HVAC GENERAL NOTES:
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
nd may include additional plan review fees
1. PRIOR TO STARTING THE WORK, CONTRACTOR SHALL VERIFY THAT EXISTING AIR CONDITIONING UNITS WORK
PROPERLY AND CAN DELIVER THE CFM SPECIFIED. SUBMIT TO ENGINEER FOR REVIEW.
2. COORDINATE LOCATIONS OF DIFFUSERS AND GRILLES WITH SUSPENDED CEILING AND LIGHT FIXTURES.
3. WHERE DUCTS ARE USED FOR BOTH HEATING AND COOLING, THE MINIMUM INSULATION SHALL BE PER
SECTION 15250 OF THE SPECIFICATION ON M -003.
4. TRANSVERSE JOINTS FOR ALL AIR SUPPLY DUCTS INSTALLED SHALL BE SEALED WITH APPROVED MASTIC.
5. VERIFY LOCATIONS AND SIZES OF EXISTING EQUIPMENT PRIOR TO COMMENCEMENT OF THE WORK.
INFORM THE ENGINEER OF DISCREPANCIES.
6. COORDINATE THE LOCATION AND ELEVATION OF EQUIPMENT, DUCTWORK AND PIPING WITH OTHER TRADES, TO
AVOID INTERFERENCES.
7. CONNECTION, DEMOLITION OR INTERRUPTION TO EXISTING SERVICES SHALL BE MINIMIZED AND COORDINATED
WITH THE OWNER'S REPRESENTATIVE.
8. EQUIPMENT SHALL BE INSTALLED, DUCTED AND /OR PIPED IN ACCORDANCE WITH APPLICABLE CODES AN
MANUFACTURERS RECOMMENDATIONS.
9. EQUIPMENT DESIGNED TO BE FIXED IN POSITION SHALL BE SECURELY FASTENED IN PLACE.
10. ALL SHEET METAL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH SMACNA DESIGN
AND CONSTRUCTION STANDARDS.
11. AT COMPLETION OF INSTALLATION, BALANCE MECHANICAL UNITS AND DIFFUSERS /REGISTERS TO PROVIDE
SUPPLY AIR CFM INDICATED ON PLANS. BALANCE UNIT TO PROVIDE OUTSIDE AIR AS STATED. SUBMIT 4
COPIES OF AIR BALANCE REPORT FOR APPROVAL.
12. THE LOCATION OF ACCESS PANELS FOR CONCEALED VALVES, FUSIBLE LINKS, DAMPER OPERATORS AND
EQUIPMENT SHALL BE COORDINATED WITH THE ARCHITECTURAL TRADES.
13. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR PATCHING AND REPAIRING WORK AREAS, AS A RESULT
OF THEIR WORK. REPAIR TO MATCH EXISTING FINISHES.
14. ACCURATE "AS- BUILT" DRAWINGS SHALL BE MAINTAINED DURING CONSTRUCTION AND SUBMITTED FOR
APPROVAL UPON COMPLETION OF INSTALLATION. INDICATE DUCT AND EQUIPMENT SIZES AND LOCATIONS.
15. CONTRACTOR SHALL PERFORM ALL WORK IN A COMPLETE AND WORKMANLIKE WAY IN CONFORMANCE WITH ALL
CODES, AND MANUFACTURER'S RECOMMENDATIONS. CONTRACTOR SHALL COORDINATE WITH ARCHITECTS,
ELECTRICAL AND STRUCTURAL. ALL WORK TO EE PERFORMED TO PROVIDE A COMPLETE AND WORKING SYSTEM.
16. CONTRACTOR IS RESPONSIBLE FOR ALL PERMITS, FEES, TESTING, ETC. CONTRACTOR SHALL PROVIDE A ONE
YEAR WARRANTY /GUARANTEE FOR ALL WORK PERFORMED UNDER THIS CONTRACT.
17. THIS TENANT IMPROVEMENT PROJECT HAS NOT MODIFIED THE THERMAL CHARACTERISTICS OF THE ENVELOPE.
18. CONTRACTOR SHALL VERIFY THE EXISTING BUILDING'S OUTSIDE AIR SHAFT INTO THE BUILDING.
ADJUST DAMPERS TO MATCH THE MECHANICAL VENTILATION REQUIREMENTS IN THESE DRAWINGS.
19. THESE DOCUMENTS WERE PREPARED PER AVAILABLE AS -BUILT DOCUMENTS. CONTRACTOR SHALL VISIT SITE TO
BECOME FULLY FAMILIAR WITH THE SCOPE OF WORK AND REVIEW EXISTING CONDITIONS PRIOR TO BID.
20. CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING CONDITIONS (SIZE, LOCATION, ETC)
PRIOR TO THE START OF CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE TO NOTIFY THE
ARCHITECT /ENGINEER OF ANY DISCREPANCIES BETWEEN CONTRACT DOCUMENTS AND EXISTING CONDITIONS.
21. CONTRACTOR SHALL NOT CUT, NOTCH AND /OR BORE EXISTING JOIST, BEAMS AND /OR JOIST WITHOUT FIRST
SECURING WRITTEN APPROVAL FROM ARCHITECT.
FILE C i PY
Permit 1 1v.
Plar review apprc val is subject to errors and omissions.
Approval of consl ruction documents does not authorize
the violation of ar y adopted code or ordinance. Receipt
of approved Field C y and cone 17 acknowledged:
By .� r
Dater
City of Tukwila
BUILDING DIVISION
SEPARATE PERMIT
REQUIRED FOR:
J Mechanical
IL Electrical
0 Plumbing
0 Gas Piping
City of Tukwila
` iG DIVISION
>t_6l `DI
RECEIVED
APR 01 2008
PERMIT CENTER
?GO3 072
Arc
\S
I onia
icI0t
coPyRIG rr 0 200e CARTER & BURGESS, INC.
1 03 -29 -08 TENANT CHANGES
at &t
Carteriturgess
Carter & Burgess, Inc.
4 Hutton Centre Drive, Suite 800
Santa Ana, California 92707
TEL: (714) 327 -1600
FAX: (714) 327 -1601
EXPIRES 03/15/10
ISSUES /REVISIONS
03 -19 -08 ISSUE FOR PERMIT
NO. DATE
DESCRIPTION
16425 Southcenter Parkway
TU KW I LA, WA
DESIGNED BY:
KL
CHECKED BY:
MV
DRAWN BY:
KL
PROJECT NUMBER:
SCALE:
APPROVED BY:
MV
441805.011.039.0001
NONE
MECHANICAL AND
PLUMBING LEGEND,
SYMBOLS AND
ABBREVIATIONS
M -0
2006 IECC
Report Date: 03/14/08
Data filename: R :WOB1Cingular\Washington State116425 Southcenter, WAlcalcslmech.cck
Section 1: Project Information
Project Title: at &t
Construction Site: Owner /Agent:
16425 Southcenter Parkway at &t Mobility, L.L.C.
Tukwila, WA 1920 Customer Care Way
Atwater, CA 95301
Section 2: General Information
Building Location (for weather data):
Climate Zone:
Heating Degree Days (base 65 degrees F):
Cooling Degree Days (base 50 degrees F):
Project Type:
Section 3: Mechanical Systems List
Quantity System Type & Des pt_.iQn
1 HVAC System 1: Heating: Central Furnace, Gas / Cooling: Rooftop Package Unit, Capacity > =90 - <135 kBtu /h,
Air - Cooled Condenser / Single Zone
1 HVAC System 2: Split System Heat Pump, Cooling Capacity <54 kBtu /h, Air- Cooled Condenser 1 Single Zone
Section 4: Requirements Checklist
Requirements Specific To: HVAC System 1
1. Newly purchased heating equipment meets the heating efficiency requirements
. Z 2. Equipment minimum efficiency: Rooftop Package Unit: 10.1 EER
A 3. Cooling system provides a means to relieve excess outdoor air during economizer operation.
O 4. Integrated air economizer required
Requirements Specific To: HVAC System 2 :
ZxS 1. Equipment minimum efficiency: Heat Pump: 6.8 HSPF, 10,0 SEER
A 2. Heat pump thermostat required when supplemental electric resistance heat is installed
Generic Requirements: Must be met by all systems to which the requirement is applicable:
1. Load calculations per 2001 ASHRAE Fundamentals
1 2. Plant equipment and system capacity no greater than needed to meet loads
- Exception: Standby equipment automatically off when primary system is operating
- Exception: Multiple units controlled to sequence operation as a function of load
t 3. Minimum one temperature control device per system
O 4. Minimum one humidity control device per installed humidification/dehumidification system
O 5. Thermostatic controls has 5 degrees F deadband
Exception: Thermostats requiring manual changeover between heating and cooling
6. Automatic Controls: Setback to 55 degrees F (heat) and 85 degrees F (cool); 7-day clock, 2 -hour occupant override, 10 -hour
backup
COMcheck Software Version 3.4.1
Mechanical Compliance Certificate
Tukwila, Washington
40
5524
1686
Addition
Designer /Contractor:
Jacobs Cater Burgess
4 Hutton Centre Drive, Suite 800
Santa Ana, OA 92707
Page 1 of 2
- Exception: Continuously operating zones
Exception: 2 kW demand or Tess, submit calculations
/. Outside -air source for ventilation; system capable of reducing OSA to required minimum
8. R -5 supply and return air duct insulation in unconditioned spaces R -8 supply and retum air duct insulation outside the building R -8
insulation between ducts and the building exterior when ducts are part of a building assembly
Exception: Ducts located within equipment
Exception: Ducts with interior and exterior temperature difference not exceeding 15 degrees F.
Exception: Continuously welded and locking -type longitudinal joints and seams on ducts operating at static pressures less than
2 inches w.g. pressure classification
"K9. Mechanical fasteners and sealants used to connect ducts and air distribution equipment
r10.Ducts sealed - longitudinal seams on rigid ducts; transverse seams on all ducts; UL 181Aor 181B tapes and mastics
0 11. Hot water pipe insulation: 1 in. for pipes < =1.5 in. and 2 in. for pipes >1.5 in. Chilled water /refrigerant/brine pipe insulation: 1 in. for
pipes < =1.5 in. and 1.5 in. for pipes >1.5 in. Steam pipe insulation: 1.5 in. for pipes < -1.5 in. and 3 in. for pipes >1.5 in.
Exception: Piping within HVAC equipment
Exception: Fluid temperatures between 55 and 105 degrees F
Exception: Fluid not heated or cooled
Exception: Runouts <4 ft in length
12.Operation and maintenance manual provided to building owner
13.Balancing devices provided in accordance with IMC 603.15
!`14.Motorized, automatic shutoff dampers required on exhaust and outdoor air supply openings
( - Exception: Gravity dampers acceptable in buildings <3 stories
- Exception: Gravity dampers acceptable in systems with outside or exhaust air flow rates less than 300 cfm where dampers are
interlocked with fan
0 15.Stair and elevator shaft vents are equipped with motorized dampers
Section 5: Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications and other calculations submitted with this permit application. The proposed mechanical systems have been designed to
meet the 2006 IECC requirements in COMcheck Version 3.4.1 and to comply with the mandatory requirements In the Requirements
Checklist.
Name - Title" Signature
s -( 0-0 )( 7
7- i Y -o1
Date
Page 2 of 2
RECEIVED
APR '01 2008
PERMIT CENTER
COPYRIGHT 0 2008 CARTER & BURGESS, INC,
at &t
Carter::Burgess
Carter & Burgess, Inc.
4 Hutton Centre Drive, Suite 800
Santa Ana, California 92707
TEL: (714) 327-1600
FAX: (714) 327 -1601
1 EXPIRES 03/15/10
ISSUES /REVISIONS
1 03- 29-08 TENANT CHANGES
03 -19 -08 ISSUE FOR PERMIT
NO. DATE DESCRIPTION
DRAWN BY:
KL
PROJECT NUMBER:
SCALE:
MECHANICAL
COMPLIANCE
FORMS
16425 Southcenter Parkway
TU KW I LA, WA
DESIGNED BY:
KL
CHECKED BY:
MV
APPROVED BY:
MV
441805.011.039.0001
NONE
M -002
SECTION 15010 GENERAL PROVISIONS
PART 1.00 - GENERAL
1.01 GENERAL REQUIREMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
B. INCLUDE ALL LABOR, MATERIAL EQUIPMENT, TRANSPORTATION AND SERVICES TO FURNISH AND INSTALL COMPLETE MECHANICAL
SYSTEMS AND ALTERATIONS AS SHOWN ON THE DRAWINGS AND HEREIN SPECIFIED. THE WORK INCLUDES, BUT IS NOT LIMITED TO:
1. ALL PLUMBING WORK.
2. CONNECTION TO ALL UTILITIES.
3. HEATING AND AIR CONDITIONING.
4. INSULATION.
5. TEMPERATURE CONTROLS.
1.02 DESCRIPTION OF WORK
A. EXTENT OF MECHANICAL WORK IS INDICATED ON DRAWINGS OR SPECIFIED IN DIVISION 15 SECTIONS OF THE SPECIFICATION.
PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, SUPERVISION AND SERVICE NECESSARY FOR A COMPLETE MECHANICAL SYSTEM.
1.03 QUALITY ASSURANCE
A. ALL WORK ACCOMPLISHED UNDER THESE SPECIFICATIONS SHALL BE IN ACCORDANCE WITH REQUIREMENTS AND RECOMMENDATIONS
OF THE LOCAL COUNTY, STATE, ACCEPTED MECHANICAL CODE, PLUMBING CODE, BUILDING CODE, ETC. UNDER THIS JURISDICTION
B. IN ADDITION, FOLLOW ALL REQUIREMENTS PERTAINING TO THE MALL TENANT DESIGN MANUAL.
1.04 SUBMITTALS
A. CONTRACTOR SHALL SUBMIT FOR REVIEW, SIX COPIES OF SHOP DRAWINGS, LITERATURE, AND EQUIPMENT LIST WITHIN 30 DAYS
AFTER CONTRACT IS LET. FIRE PROTECTION DRAWINGS SHALL BE SUBMITTED PER DIVISION 1.
B. SUBMIT PRIOR TO FABRICATION OR DELIVERY.
C. SUBMIT COMPLETE, AT ONE TIME. PARTIAL SUBMITTALS WILL NOT BE CONSIDERED (EXCEPT AS NOTED ABOVE FOR CONTROLS AND
DUCTWORK).
D. CATALOG SHEETS SHALL BE COMPLETE AND THE ITEM OR MODEL TO BE USED SHALL BE CLEARLY MARKED.
E. LIST SUBSTITUTE ITEMS SEPARATELY AND SO IDENTIFIED.
PART 2.00 - PRODUCTS
2.01 MATERIALS
A. ALL MATERIALS SHALL BE NEW AND OF MANUFACTURERS SPECIFIED HEREIN. THEY SHALL BE U.S. MADE (EXCEPT CANADIAN
COPPER PIPE IS ACCEPTABLE) AND BEAR THE U.L., ETL OR CSA LABEL WHERE POSSIBLE.
B. ALL EQUIPMENT SHALL BE REGULARLY CATALOGUED ITEMS OF THE MANUFACTURER AND IN USE FOR AT LEAST TWO YEARS AND
SHALL BE SUPPLIED AS A COMPLETE UNIT IN ACCORDANCE WITH THE MANUFACTURER'S STANDARD SPECIFICATIONS AND ANY
OPTIONAL ITEMS REQUIRED FOR PROPER INSTALLATION FOR THE EQUIPMENT UNLESS OTHERWISE NOTED. ALL EQUIPMENT AND
MATERIALS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND BEST TRADE PRACTICES.
2.02 SUBSTITUTIONS
A. IN ALL CASES IN THIS SPECIFICATION WHERE AN ARTICLE IS FOLLOWED BY THE WORDS 'OR APPROVED EQUAL ", THE ARCHITECT
IS THE SOLE JUDGE OF THE QUALITY OF THE PROPOSED SUBSTITUTION.
B. WHEN THE ARCHITECT /OWNER APPROVES A SUBSTITUTION, THE APPROVAL IS GIVEN WITH THE UNDERSTANDING THAT THE
CONTRACTOR GUARANTEES THE ARTICLE OR MATERIAL SUBSTITUTED TO BE EQUAL TO OR BETTER IN EVERY RESPECT THAN THE
ARTICLE OR MATERIAL SPECIFIED. THE CONTRACTOR SHALL ALSO ASSUME COMPLETE RESPONSIBILITY THAT THE ARTICLE OR
MATERIAL WILL FIT THE JOB AS FAR AS SPACE, ACCESS AND SERVICING REQUIREMENTS.
C. WHERE SEVERAL MATERIALS ARE SPECIFIED BY NAME FOR ONE USE, SELECT FOR USE ANY OF THOSE SO SPECIFIED. NOTE
THAT EQUIPMENT LAYOUT IS BASED ON EQUIPMENT LISTED IN EQUIPMENT SCHEDULES. ANY OTHER EQUIPMENT USED MUST FIT IN
AVAILABLE SPACE WITH ALL ACCESS AND SERVICING REQUIREMENTS MAINTAINED. IT IS THE CONTRACTOR'S RESPONSIBILITY TO
CHECK THAT THIS EQUIPMENT WILL MEET THESE REQUIREMENTS.
D. WHENEVER ITEM OR CLASS OF MATERIAL IS SPECIFIED EXCLUSIVELY BY DETAIL SPECIFICATION, TRADE NAME, MANUFACTURER'S
NAME OR BY CATALOG REFERENCE, USE ONLY SUCH ITEM, UNLESS WRITTEN APPROVAL IS GIVEN FOR SUBSTITUTION PRIOR TO
BID.
PART 3.00 - EXECUTION
3.01 DRAWINGS
A. THE MECHANICAL DRAWINGS ARE GENERALLY DIAGRAMMATIC. COMPLETE DETAILS OF THE BUILDING WHICH AFFECT THE MECHANICAL
INSTALLATION MAY NOT BE SHOWN. FOR ADDITIONAL DETAILS, THE CONTRACTOR IS REFERRED TO THE ARCHITECTURAL,
STRUCTURAL, & ELECTRICAL DRAWINGS.
3.02 CODES, ORDINANCES AND PERMITS
A. ALL WORK SHALL COMPLY WITH ALL APPLICABLE CODES AND ORDINANCES. TAKE OUT AND PAY FOR ALL INSPECTION FEES AND
PERMITS. COMPLIANCE WITH CODES AND ORDINANCES SHALL BE AT THE CONTRACTOR'S EXPENSE. INCLUDE ALL CONNECTION
AND PERMIT FEES IN BID. CONTRACTOR SHALL CONTACT L &I FOR INSPECTION OF ALL PRESSURE VESSELS IN A TIMELY MANNER
BEFORE OCCUPANCY OF THE BUILDING.
3.04 TESTING
A. WATER PIPING
TEST ALL WATER PIPING SYSTEMS AT 125 PSI WATER PRESSURE AND HOLD FOR FOUR (4) HOURS. TEST IN SECTIONS BEFORE
COVERING. TEST ENTIRE SYSTEM WHEN COMPLETELY INSTALLED. REPAIR ANY DEFECTS SHOWN BY TEST AND RETEST UNTIL
ENTIRELY TIGHT.
B. WASTE AND SEWER PIPING
TEST ALL WASTE, SEWER AND VENT PIPING BY FILLING WITH WATER TO ROOF. HOLD FOR FOUR HOURS. TEST IN SECTIONS AS
WORK PROGRESSES. REPAIR ANY DEFECTS SHOWN BY TEST AND RETEST UNTIL ENTIRELY TIGHT.
C. VALVES
TEST ALL VALVE BONNETS FOR TIGHTNESS. OPERATE ALL VALVES AT LEAST ONCE FROM CLOSED -TO- OPEN -TO- CLOSED WHILE
UNDER PRESSURE.
3.05 CLEAN UP AND HOUSEKEEPING
A. LEAVE ALL EQUIPMENT CLEAN AND READY FOR USE.
B. REMOVE ALL LABELS, PAINT, PLASTER, ETC., FROM FIXTURES, EQUIPMENT AND PIPING.
3.06 OPERATING INSTRUCTIONS AND MAINTENANCE MANUALS
A. SCOPE:
1. PROVIDE COMPLETE OPERATING AND MAINTENANCE INSTRUCTIONS AND
2. PROVIDE FOUR COPIES OF EACH BOUND INTO BOOKLET FORM.
3. DELIVER BOOKLETS TO THE ARCHITECT BEFORE FINAL INSPECTION.
B. CONTENTS: EACH BOOKLET SHALL CONTAIN AT LEAST, BUT NOT LIMITED TO MAINTENANCE INSTRUCTIONS AND PARTS LIST AS
FOLLOWS:
1. BASIC DESCRIPTION OF ALL SYSTEMS.
2. DESCRIPTION OF ROUTINE MAINTENANCE REQUIRED FOR EACH COMPONENT,
3. SUGGESTED FREQUENCY OF MAINTENANCE.
4. PARTS LIST OF ALL EQUIPMENT.
5. OPERATING INSTRUCTIONS AND WARRANTIES ON ALL EQUIPMENT.
6. CONTROLS: AS -BUILT WIRING DIAGRAMS
7. MECHANICAL AS -BUILT DRAWINGS.
8. TROUBLE - SHOOTING LIST.
9. NAME, ADDRESS, PHONE NUMBER OF ALL CONTRACTORS AND SUPPLIERS
3.07 RECORD DRAWINGS
A. PROVIDE THE ARCHITECT WITH RECORD DRAWINGS. RECORD DRAWINGS SHALL BE NEW, REPRODUCIBLE MYLARS AND SHALL SHOW
THE MEASURED LOCATIONS OF ALL CONCERNED PORTIONS OF THE WORK AND SHALL SHOW ALL CHANGES THE CONTRACTOR HAS
MADE.
B. DRAWINGS MUST SHOW ALL ADDENDUM ITEMS, CHANGE ORDERS AND DEVIATIONS FROM THE PLANS.
3.08 INTERFERENCE
A. THE MECHANICAL CONTRACTOR'S ATTENTION IS CALLED TO THE RESTRICTED SPACE FOR INSTALLATION OF MECHANICAL SYSTEMS.
OFFSETS, REROUTING AND COORDINATION WILL BE REQUIRED TO FIT ALL ELEMENTS IN AVAILABLE SPACE AND THE MECHANICAL
CONTRACTOR SHALL INCLUDE PROVISIONS FOR SUCH IN HIS BID.
B. DUCTWORK AND PIPING SHALL BE ROUTED TO CLEAR LIGHT FIXTURES. COORDINATE ROUTING OF DUCTWORK AND PIPING WITH
EACH OTHER SO GRADE OF PIPING CAN BE ACCOMPLISHED, AND TO FIT IN AVAILABLE SPACE.
C. DUCTWORK SHALL BE INSTALLED AS REQUIRED TO CLEAR LIGHT FIXTURES AND TO FIT IN AVAILABLE SPACE. PROVIDE OFFSETS,
V OR SLEEVES AS REQUIRED. MAINTAIN EQUIVALENT FREE AREA OF DUCTWORK.
D. DUCTWORK TAKES PRECEDENCE OVER PIPING FOR AVAILABLE SPACE AND ROUTING. COORDINATE INSTALLATION BASED ON THIS
PRECEDENCE.
E. DUCTWORK AND /OR PIPING SHALL NOT BE RUN OVER ELECTRICAL PANELS.
3.09 WORKMANSHIP
A. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH BEST TRADE PRACTICE. ANY SUBSTANDARD WORKMANSHIP SHALL BE
REMOVED AND REPLACED AT NO EXTRA COST TO THE OWNER,
3.10 SEISMIC RESTRAINTS
A. PROVIDE SEISMIC RESTRAINTS ON ALL PIPING AND DUCTWORK IN ACCORDANCE WITH THE "GUIDLINES FOR SEISMIC RESTRAINTS OF
MECHANICAL SYSTEMS AND PLUMBING PIPING SYSTEMS" AS PREPARED BY SMACNA AND THE PLUMBING PIPING INSTITUTE
COUNCIL.
B. PROVIDE SEISMIC RESTRAINTS ON ALL EQUIPMENT AND PROVIDE SLACK CABLE RESTRAINTS ON ALL SUSPENDED EQUIPMENT.
COMPLETE RESTRAINT SYSTEM SHALL BE SELECTED, SHOP DRAWINGS SEALED BY AND CERTIFICATION PROVIDED BY A
PROFESSIONAL STRUCTURAL ENGINEER.
END OF SECTION 15010
SECTION 15030 ELECTRICAL PROVISIONS TO MECHANICAL WORK
PART 1.00 - GENERAL
1.01 DESCRIPTION
A. GENERAL REQUIREMENTS
DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 STANDARDS
A. FOR ELECTRICAL EQUIPMENT AND PRODUCTS, EMPLOY WITH APPLICABLE NEMA STANDARDS, AND REFER TO NEMA STANDARDS FOR
DEFINITIONS OF TERMINOLOGY HEREIN. COMPLY WITH NATIONAL ELECTRICAL CODE (NFPA 70) FOR WORKMANSHIP AND
INSTALLATION REQUIREMENTS AND TO APPLICABLE SECTIONS OF DIVISION 16 OF THE SPECIFICATIONS.
PART 2.00 - PRODUCTS
A. MANUFACTURER
1. EXCEPT WHERE ITEM OF MECHANICAL EQUIPMENT (WHICH OTHERWISE COMPLIES WITH REQUIREMENTS) MUST BE
INTEGRALLY EQUIPPED WITH MOTOR PRODUCED BY ANOTHER MANUFACTURER, PROVIDE MOTORS FOR MECHANICAL
EQUIPMENT.
CHARACTERISTICS M OTOR CH
1. EXCEPT WHERE MORE STRINGENT REQUIREMENTS ARE INDICATED, AND EXCEPT WHERE REQUIRED ITEM OF MECHANICAL
EQUIPMENT CANNOT BE OBTAINED WITH FULLY COMPLYING MOTOR, COMPLY WITH THE FOLLOWING REQUIREMENTS FOR MOTORS
OF MECHANICAL WORK:
A. TEMPERATURE RATING: RATED FOR 40 DEG. C ENVIRONMENT WITH MAXIMUM 50 DEG. C TEMPERATURE RISE FOR
CONTINUOUS DUTY AT FULL LOAD (CLASS A INSULATION).
B. STARTING CAPABILITY: PROVIDE EACH MOTOR CAPABLE OF MAKING STARTS AS FREQUENTLY AS INDICATED BY
AUTOMATIC CONTROL SYSTEM, AND NOT LESS THAN 5 STARTS /HOUR FOR MANUALLY CONTROLLED MOTORS.
C. PHASES AND CURRENT CHARACTERISTICS : PROVIDE SQUIRREL -CAGE INDUCTION POLYPHASE MOTORS FOR 1 HP
AND LARGER, AND PROVIDE CAPACITOR -START SINGLE -PHASE MOTORS FOR 3/4 HP AND SMALLER, EXCEPT 1/6
HP AND SMALLER MAY, AT EQUIPMENT MANUFACTURER'S OPTION, BE SPLIT-PHASE TYPE. COORDINATE CURRENT
CHARACTERISTICS WITH POWER SPECIFIED IN DIVISION -16 SECTIONS, AND WITH INDIVIDUAL EQUIPMENT
REQUIREMENTS SPECIFIED IN OTHER DIVISION -15 REQUIREMENTS. FOR 2 -SPEED MOTORS PROVIDE 2 SEPARATE
WINDINGS ON POLYPHASE MOTORS. DO NOT PURCHASE MOTORS UNTIL POWER CHARACTERISTICS AVAILABLE AT
LOCATIONS OF MOTORS HAVE BEEN CONFIRMED, AND UNTIL ROTATION DIRECTIONS HAVE BEEN CONFIRMED.
D. SERVICE FACTOR: 1.15 FOR POLYPHASE MOTORS, AND 1.35 FOR SINGLE -PHASE MOTORS.
C. MOTOR CONSTRUCTION
1. PROVIDE GENERAL PURPOSE, CONTINUOUS DUTY MOTORS, DESIGN " B " ,
EXCEPT " C " WHERE REQUIRED FOR HIGH STARTING TORQUE.
A. FRAMES: NEMA NO. 48.
B. BEARINGS: BALL OR ROLLER BEARINGS WITH INNER AND OUTER SHAFT SEALS, PERMANENTLY SEALED. WHERE
BELT DRIVES AND OTHER DRIVES PRODUCE LATERAL OR AXIAL THRUST IN MOTOR, PROVIDE BEARINGS DESIGNED
TO RESIST THRUST LOADING. REFER TO INDIVIDUAL SECTIONS OF DIVISION -15 FOR FRACTIONAL -HP LIGHT -DUTY
MOTORS WHERE SLEEVE -TYPE BEARINGS ARE PERMITTED.
C. ENCLOSURE TYPE: EXCEPT AS OTHERWISE INDICATED PROVIDE OPEN DROP -PROOF MOTORS FOR INDOOR USE
WHERE SATISFACTORILY HOUSED OR REMOTELY LOCATED DURING OPERATION, AND PROVIDE GUARDED DRIP PROOF
MOTORS WHERE EXPOSED TO CONTACT BY EMPLOYEES OR BUILDING OCCUPANTS. PROVIDE WEATHER- PROTECTED
TYPE I FOR OUTDOOR USE, TYPE II WHERE NOT HOUSED. REFER TO INDIVIDUAL SECTIONS OF DIVISION -15 FOR
OTHER ENCLOSURE REQUIREMENTS.
D. OVERLOAD PROTECTION: PROVIDE BUILT -IN THERMAL OVERLOAD PROTECTION FOR 120V MOTORS.
E. EFFICIENCY: MOTORS ARE TO BE "ENERGY EFFICIENT" HAVING MINIMUM EFFICIENCY AS SCHEDULED IN
ACCORDANCE WITH IEEE STANDARD 112, TEST METHOD B.
F. PROVIDE MOTORS WITH MINIMUM 85% POWER FACTOR. WHERE LESS THAN 85 %, PROVIDE POWER FACTOR
CORRECTION TO MINIMUM 90% PER ENERGY CODES.
D. NAMEPLATE
PROVIDE METAL NAMEPLATE ON EACH MOTOR, INDICATING FULL IDENTIFICATION OF MANUFACTURER, RATINGS, CHARACTERISTICS,
CONSTRUCTION, SPECIAL FEATURES, AND SIMILAR INFORMATION.
2.02 STARTERS, ELECTRICAL DEVICES AND WIRING
A. MOTOR STARTER MANUFACTURER
1. EXCEPT WHERE ITEM OF MECHANICAL EQUIPMENT MUST BE INTEGRALLY FURNISHED WITH MOTOR STARTER PRODUCED BY
ANOTHER MANUFACTURER, PROVIDE MOTOR STARTERS FOR MECHANICAL EQUIPMENT MANUFACTURED BY ONE OF THE
FOLLOWING: CUTLER - HAMMER, GE OR SQUARE D.
B. MOTOR STARTER CHARACTERISTICS
1. COMPLY WITH NEMA STANDARDS AND NEC. PROVIDE TYPE I GENERAL PURPOSE ENCLOSURES WITH PAD LOCK EARS, AND
WITH FRAMES AND SUPPORTS FOR MOUNTING ON WALL, FLOOR OR PANEL AS INDICATED. PROVIDE TYPE AND SIZE OF
STARTER RECOMMENDED BY MOTOR MANUFACTURER AND EQUIPMENT MANUFACTURER FOR APPLICABLE PROTECTION AND
START -UP CONDITION; REFER TO INDIVIDUAL EQUIPMENT SECTIONS FOR BASIC LOAD REQUIREMENTS.
A. MANUAL SWITCHES: PROVIDE MANUAL SWITCH AND PILOT LIGHT FOR MOTORS 1/2 HP AND SMALLER, EXCEPT W
HERE INTERLOCK OR AUTOMATIC OPERATION IS INDICATED.
1) OVERLOAD PROTECTION: PROVIDE MELTING ALLOY TYPE THERMAL OVERLOAD RELAYS.
B. MAGNETIC STARTERS: PROVIDE MAGNETIC STARTERS FOR 3 PHASE MOTORS AND FOR SMALLER MOTORS WHERE
INTERLOCK OR AUTOMATIC OPERATION IS INDICATED. INCLUDE THE FOLLOWING:
1) HAND - OFF -AUTO SWITCH AND PILOT LIGHTS, PROPERLY ARRANGED FOR SINGLE -SPEED OR MULTI -SPEED
OPERATION AS INDICATED.
2) TRIP -FREE THERMAL OVERLOAD RELAYS, EACH PHASE.
3) INTERLOCKS, PNEUMATIC SWITCHES, AND SIMILAR DEVICES AS REQUIRED FOR COORDINATION WITH CONTROL
REQUIREMENTS OF DIVISION -15 CONTROLS SECTIONS.
4) BUILT -IN 120 -VOLT CONTROL CIRCUIT TRANSFORMER, FUSED FROM LINE SIDE, WHERE SERVICE EXCEEDS
240 VOLTS. WHEN A TRANSFORMER ISN'T USED THE CONTROL COIL SHALL BE FUSED.
5) EXTERNALLY OPERATED MANUAL RESET.
6) UNDERVOLTAGE RELEASE OR PROTECTION FOR EACH PHASE.
PART 3.00 - EXECUTION
3.01 STARTERS
A. PROVIDE STARTERS AND WIRING DEVICES FOR MOTORS. INSTALLATION BY DIVISION 16000.
3.02 MOTORS
A. INSTALL MOTORS ON MOTOR MOUNTING SYSTEMS IN ACCORDANCE WITH MOTOR MANUFACTURER'S INSTRUCTIONS, SECURELY
ANCHORED TO RESIST TORQUE, DRIVE THRUSTS, AND OTHER EXTERNAL FORCES INHERENT IN MECHANICAL WORK. SECURE
SHEAVES AND OTHER DRIVE UNITS TO MOTOR SHAFTS WITH KEYS AND ALLEN SET SCREWS, EXCEPT MOTORS OF 1/3 HP AND
LESS MAY BE SECURED WITH ALLEN SCREWS ON FLAT SURFACES OF SHAFT. UNLESS OTHERWISE INDICATED, SET MOTOR SHAFTS
PARALLEL WITH MACHINE SHAFTS.
3.03 EQUIPMENT FABRICATION
A. FABRICATE MECHANICAL EQUIPMENT FOR SECURE MOUNTING OF MOTORS AND OTHER ELECTRICAL ITEMS INCLUDING IN WORK.
PROVIDE EITHER PERMANENT ALIGNMENT OF MOTORS WITH EQUIPMENT, OR ADJUSTABLE MOUNTINGS AS APPLICABLE FOR BELT
DRIVES, GEAR DRIVES, SPECIAL COUPLINGS AND SIMILAR INDIRECT COUPLING OF EQUIPMENT. PROVIDE SAFE, SECURE, DURABLE,
AND REMOVABLE GUARDS FOR MOTOR DRIVES, ARRANGED FOR LUBRICATION AND SIMILAR RUNNING MAINTENANCE WITHOUT
REMOVAL OF GUARDS.
END OF SECTION 15030
SECTION 15050 MECHANICAL IDENTIFICATION
PART 1.00 - GENERAL
1.01 GENERAL REQUIREMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 STANDARDS
A. ANSI COMPLIANCE
COMPLY WITH ANSI A13.1 FOR LETTERING SIZE, COLORS, AND INSTALLED VIEWING ANGLES OF IDENTIFICATION DEVICES.
PART 2.00 PRODUCTS
2.01 ENGRAVED PLASTIC - LAMINATE SIGNS
A. PROVIDE ENGRAVED STOCK MELAMINE PLASTIC LAMINATE, COMPLYING WITH FS L- P -387, ENGRAVED WITH ENGRAVER'S STANDARD
LETTER STYLE OF SIZES AND WORDING, BLACK WITH WHITE CORE (LETTER COLOR) EXCEPT AS OTHERWISE INDICATED, PUNCHED
FOR MECHANICAL FASTENING EXCEPT WHERE ADHESIVE MOUNTING IS NECESSARY BECAUSE OF SUBSTRATE. PROVIDE 1/16"
THICKNESS FOR UNITS UP TO 20 SQ. IN OR 8" LENGTH; 1/8" FOR LARGER UNITS. PROVIDE FASTENING PER SELF - TAPPING
STAINLESS STEEL SCREWS, EXCEPT CONTACT -TYPE PERMANENT ADHESIVE WHERE SCREWS CANNOT OR SHOULD NOT PENETRATE
SUBSTRATE. PROVIDE FOR ALL EQUIPMENT.
2.02 ELECTRICAL EQUIPMENT
A. ON ALL MECHANICAL EQUIPMENT THAT HAS POWER CONNECTORS, PROVIDE WITH PERMANENT MARKER, THE ELECTRICAL PANEL
AND BREAKER NUMBER. MARK ON DISCONNECT.
PART 3.00 - EXECUTION
3.01 MECHANICAL EQUIPMENT IDENTIFICATION
A. MECHANICAL EQUIPMENT IDENTIFICATION
INSTALL ENGRAVED PLASTIC LAMINATE SIGN ON OR NEAR EACH MAJOR ITEM OF MECHANICAL EQUIPMENT AND EACH OPERATING
DEVICE. PROVIDE SIGNS FOR WATER HEATERS, FANS, HVAC UNITS AND OTHER OPERATIONAL DEVICES.
END OF SECTION 15050
SECTION 15060 PIPE TUBE & FITTINGS
PART 1.00 - GENERAL
1.01 GENERAL REQUIREMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 QUALITY ASSURANCE
A. CERTIFY BRAZING PROCEDURES, BRAZERS, AND OPERATORS IN ACCORDANCE WITH ANSI B31.5.
PART 2.00 - PRODUCTS
2.01 PIPING MATERIALS
A. COPPER TUBE: ASTM B88.
B. DWV COPPER TUBE: ASTM B 306.
C. HUBLESS CAST -IRON SOIL PIPE: CISPI 301, WITH COUPLING ASSEMBLY, CISPI 310.
D. STEEL PIPE: ASTM 106B, SCH 40, TREADED.
2.02 PIPE /TUBE FITTINGS
A. CAST -IRON FLANGED FITTINGS: ANSI B16.1.
B. CAST -IRON THREADED FITTINGS: ANSI B16.4.
C. MALLEABLE IRON THREADED UNIONS: ANSI B16.3; GALVANIZED PIPING SYSTEMS.
D. MALLEABLE IRON THREADED UNIONS: ANSI B16.39.
E. DUCTILE IRON PRESSURE PIPING FITTINGS: ANSI A21.10; AWWA C110
F. THREADED PIPE PLUGS: ANSI 816.14.
G. CAST -IRON THREADED DRAINAGE FITTINGS: ANSI B16.12.
H. PIPE NIPPLES:
SAME PIPING MATERIAL AS CONNECTING PIPING; SCHEDULE 80 FOR 1 -1/2 UNTHREADED LENGTH WITH PIPE SIZES LESS THAN
1 -1/4 "; NO CLOSE NIPPLES ALLOWED.
L WROUGHT - COPPER SOLDER -JOINT FITTINGS: ANSI B16.22.
J. CAST - COPPER SOLDER -JOINT DRAINAGE FITTINGS: ANSI B16.23.
K. WROUGHT - COPPER SOLDER -JOINT DRAINAGE FITTINGS: ANSI 816.29.
L. COPPER -TUBE UNIONS: ANSI B16.15.
M. RUBBER - GASKET JOINTS: ANSI A21.11; AWWA C111.
N. HUBLESS CAST -IRON SOIL PIPE FITTINGS: CISPI 301.
0. HUB -AND SPIGOT CAST -IRON PIPE FITTINGS: ASTM A74.
2.03 MISCELLANEOUS PIPING MATERIALS /PRODUCTS
A. SOLDERING MATERIALS: PROVIDE ONE OF THE FOLLOWING FOR EACH SERVICE: TIN -LEAD SOLDER: ASTM B32, GRADE 50A; FOR
DRAINAGE PIPING OR TIN - ANTIMONY SOLDER: ASTM 832, GRADE 95TH FOR PRESSURE PIPING.
B. PIPING CONNECTORS FOR DISSIMILAR NON - PRESSURE PIPE
ELASTOMERIC ANNULAR RING INSERT, OR ELASTOMERIC FLEXIBLE COUPLING SECURED AT EACH END WITH STAINLESS STEEL
CLAMPS, SIZED FOR EXACT FIT TO PIPE ENDS AND SUBJECT TO APPROVAL BY PLUMBING CODE.
PART 3.00 - EXECUTION
3.01 GENERAL
A. INSTALL PIPE, TUBE AND FITTINGS IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES WHICH WILL ACHIEVE PERMANENTLY
LEAKPROOF PIPING SYSTEMS, CAPABLE OF PERFORMING EACH INDICATED SERVICE WITHOUT PIPING FAILURE. INSTALL EACH RUN
WITH MINIMUM JOINTS AND COUPLINGS, BUT WITH ADEQUATE AND ACCESSIBLE UNIONS FOR DISASSEMBLY AND MAINTENANCE
REPLACEMENT OF VALVES AND EQUIPMENT. REDUCE SIZES (WHERE INDICATED) BY USE OF REDUCING FITTINGS. ALIGN PIPING
ACCURATELY AT CONNECTIONS, WITH 1/16" MISALIGNMENT TOLERANCE.
3.02 THREAD PIPE
A. THREAD PIPE IN ACCORDANCE WITH ANSI B2.1. APPLY PIPE JOINT COMPOUND OR PIPE JOINT TAPE (TEFLON) ON MALE THREADS
AND TIGHTEN JOINT TO LEAVE NOT MORE THAN 3 THREADS EXPOSED.
3.03 SOLDER JOINTS
A. COMPLY WITH APPLICABLE PROVISIONS OF "COPPER TUBE HANDBOOK" BY CDA.
3.04 HUBLESS CAST -IRON JOINTS
A. COMPLY WITH CISFI 310.
3.05 CLEANING, FLUSHING, AND INSPECTING
A. GENERAL
CLEAN EXTERIOR SURFACES OF INSTALLED PIPING SYSTEMS OF SUPERFLUOUS MATERIALS, AND PREPARE FOR APPLICATION OF
SPECIFIED COATINGS (IF ANY). FLUSH OUT PIPING SYSTEMS WITH TEST MEDIA BEFORE PROCEEDING WITH REQUIRED TESTS.
INSPECT EACH RUN OF EACH SYSTEM FOR COMPLETION OF JOINTS, SUPPORTS, AND ACCESSORY ITEMS.
1. INSPECT PRESSURE PIPING IN ACCORDANCE WITH PROCEDURES OF ANSI B31.
2. DISINFECT WATER MAINS AND WATER SERVICE PIPING IN ACCORDANCE WITH AWWA C601.
3.06 PIPING TESTS
A. GENERAL
PROVIDE EQUIPMENT FOR TESTING, TEST BEFORE INSULATION IS INSTALLED, REMOVE CONTROL DEVICES BEFORE TESTING. TEST
EACH SECTION OF EACH PIPING SYSTEM INDEPENDENTLY. FILL EACH SECTION WITH WATER, AND TEST PER SECTION 15010 3.04.
B. REPAIR PIPING SYSTEMS SECTION WHICH FAIL TEST, BY DISASSEMBLY AND RE- INSTALLATION, USING NEW MATERIALS TO
OVERCOME LEAKAGE. DO NOT USE CHEMICALS, STOP -LEAK COMPOUNDS, MASTICS, OR OTHER TEMPORARY REPAIR METHODS.
END OF SECTION 15060
SECTION 15100 VALVES
PART 1.00 - GENERAL
1.01 DESCRIPTION
A. GENERAL REQUIREMENTS
DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
PART 2.00 - PRODUCTS
2.01 GENERAL
A. PROVIDE FACTORY - FABRICATED VALVES RECOMMENDED BY MANUFACTURER FOR USE IN SERVICE INDICATED. PROVIDE VALVES OF
TYPES AND PRESSURE RATINGS INDICATED; PROVIDE PROPER SELECTION AS DETERMINED BY INSTALLER TO COMPLY WITH
INSTALLATION REQUIREMENTS. PROVIDE SIZES AS INDICATED, AND CONNECTIONS WHICH PROPERLY MATE WITH PIPE, TUBE, AND
EQUIPMENT CONNECTIONS. WHERE MORE THAN ONE TYPE IS INDICATED, SELECTION IS INSTALLER'S OPTION.
2.02 BALL VALVES
A. SELECT WITH PORT AREA EQUAL TO OR GREATER THAN CONNECTING PIPE AREA, INCLUDE SEAT RING DESIGNED TO HOLD
SEALING MATERIAL. COMPLY WITH THE FOLLOWING STANDARDS:
1. BRONZE VALVES: MILWAUKEE "BUTTERBALL" OR EQUAL.
2. MANUFACTURER: CRANE, FAIRBANKS, MILWAUKEE OR NIBCO.
2.03 AUTOMATIC FLOW CCNTROL VALVES
PART 3.00 - EXECUTION
3.01 INSTALLATION
A. INSTALL VALVES WHERE REQUIRED FOR PROPER OPERATION OF PIPING AND EQUIPMENT, INCLUDING VALVES IN BRANCH LINES
WHERE NECESSARY TO ISOLATE SECTIONS OF PIPING. LOCATE VALVES SO AS TO BE ACCESSIBLE AND SO THAT SEPARATE
SUPPORT CAN BE PROVIDED WHEN NECESSARY.
B. INSTALL VALVES WITH STEMS POINTED UP, IN VERTICAL POSITION DOWNWARD FROM HORIZONTAL PLANE.
END OF SECTION 15100
SECTION 15250 MECHANICAL INSULATION
PART 1.00 - GENERAL
1.01 GENERAL REQUIREMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION. AT A MINIMUM, INSULATION VALUES SHALL
MEET THE REQUIREMENTS OF THE STATE ENERGY CODE, IF APPLICABLE.
1.02 FLAME /SMOKE RATINGS
A. PROVIDE COMPOSITE MECHANICAL INSULATION (INSULATION, JACKETS, COVERINGS, SEALER, MASTICS AND ADHESIVES) WITH FLAME
SPREAD INDEX AT 25 OR LESS, AND SMOKE DEVELOPED INDEX OF 50 OR LESS, AS TESTED BY ASTM [84 (NFPA 225) METHOD.
PART 2.00 - PRODUCTS
2.01 MATERIALS
A. GLASS FIBER PIPE INSULATION: ASTM C 1136 & 547 TYPE I.
B. GLASS FIBER PIPE FITTING INSULATION: ASTM C 553.
2.02 MANUFACTURERS
A. ONE OF THE FOLLOWING:
1. CERTAINTEE) CORP., KNAUF FIBER GLASS, MANVILLE CORP., OWENS- CORNING FIBERGLASS CORP., IMCOA, NOMACO.
02 69
2.03 PIPING INSULATION
A. OMIT INSULATION ON EXPOSED PLUMBING FIXTURE RUN -OUTS, (EXCEPT AT HANDICAPPED FIXTURES) FROM FACE OF WALL OR
FLOOR TO FIXTURE; ON UNIONS, FLANGES, STRAINERS, FLEXIBLE CONNECTIONS, AND EXPANSION JOINTS.
1. INSULATE THE FOLLOWING COLD PIPING SYSTEMS:
A) DOMESTIC COLD WATER AND CONDENSATE DRAIN PIPING.
2. INSULATE THE ABOVE COLD PIPING WITH THE FOLLOWING INSULATION:
A) GLASS FIBER, 1" THICK ON ALL PIPE SIZE EXCEPT 1" DIAMETER AND LESS PIPE AND RUNOUTS UP TO 2"
DIAMETER PIPE SIZE.
3. INSULATE THE FOLLOWING HOT PLUMBING PIPING SYSTEMS:
A) DOMESTIC HOT WATER PIPING.
4. INSULATE THE ABOVE HOT PIPING WITH ONE OF THE FOLLOWING INSULATIONS:
A) DOMESTIC FIBERGLASS: 1 THICK FOR UP TO 2" DIAMETER PIPE SIZE AND 1.5" THICK FOR 2 -1/2" DIAMETER AND
LARGER PIPE SIZES.
5. PROVIDE ASJ (ALL SERVICE JACKET) ON ALL PIPING, EXCEPT PIPING EXPOSED TO THE OUTSIDE SHALL HAVE AN
ALUMINUM JACKET.
6. ALL PLUMBING SYSTEMS SHALL MEET OR EXCEED THE INSULATION REQUIREMENTS OF THE APPLICABLE CALIFORNIA
ENERGY CODE. WHERE INSULATION THICKNESS SPECIFIED ARE LARGER THAN THOSE LISTED IN THE ENERGY CODE, THE
LARGER VALUES SHALL BE USED.
2.04 DUCT SYSTEM INSULATION
A. INSULATE ALL SUPPLY & VENTILATION AIR DUCTWORK WITH FSK GLASS FIBER INSULATION HAVING A MINIMUM INSTALLED R -VALUE
OF 7.
B. DO NOT WRAP SOUNDUNED DUCT.
PART 3.00 - EXECUTION
3.01 INSTALLATION - PIPE AND DUCT INSULATION
A. EXAMINE AREAS AND CONDITIONS UNDER WHICH MECHANICAL INSULATION WILL BE INSTALLED. DO NOT PROCEED WITH WORK
UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED.
B. INSTALL INSULATION PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS, AND IN ACCORDANCE WITH
RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT INSULATION SERVES ITS INTENDED PURPOSE.
C. INSTALL INSULATION ON MECHANICAL SYSTEMS SUBSEQUENT TO TESTING AND ACCEPTANCE OF TESTS.
D. CLEAN AND DRY MECHANICAL SURFACES PRIOR TO INSULATING. BUTT INSULATION JOINTS FIRMLY TOGETHER TO ENSURE
COMPLETE AND TIGHT FIT OVER SURFACES TO BE COVERED.
E. MAINTAIN INTEGRITY OF VAPOR - BARRIER JACKETS ON MECHANICAL INSULATION, AND PROTECT TO PREVENT PUNCTURE OR OTHER
DAMAGE.
F. COVER VALVES, FITTINGS AND SIMILAR ITEMS IN EACH PIPING SYSTEM WITH EQUIVALENT THICKNESS AND COMPOSITION OR
EFFICIENCY OF INSULATION AS APPLIED TO ADJOINING PIPE RUN.
G. EXTEND MECHANICAL INSULATION WITHOUT INTERRUPTION THROUGH WALLS, FLOORS AND SIMILAR PIPING PENETRATIONS, EXCEPT
WHERE OTHERWISE INDICATED.
H. INSTALL PROTECTIVE METAL SHIELDS AND INSULATED SADDLES TO PREVENT COMPRESSION OF INSULATION.
I. REPAIR DAMAGED SECTIONS OF EXISTING MECHANICAL INSULATION, DAMAGED DURING THIS CONSTRUCTION PERIOD. USE
INSULATION OF SAME THICKNESS AS EXISTING INSULATION, INSTALL NEW JACKET LAPPING AND SEALED OVER EXISTING.
END OF SECTION 15250
SECTION 15401 WATER PIPING
PART 1.00 - GENERAL
1.01 GENERAL REQUIREMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIV 1 - GENERAL
REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 COMPLIANCE
A. COMPLY WITH APPLICABLE PLUMBING CODE STANDARDS PERTAINING TO MATERIALS, PRODUCTS, AND INSTALLATION OF DOMESTIC
WATER PIPING. COMPLY WITH APPLICABLE PLUMBING AND MECHANICAL CODE STANDARDS PERTAINING TO MATERIALS, PRODUCTS,
AND INSTALLATION OF PROCESS WATER PIPING (INCLUDING CONDENSER WATER).
PART 2 - PRODUCTS
2.01 GENERAL
A. BASIC PIPING MATERIALS AND PRODUCTS REQUIRED FOR WORK OF THIS SECTION, ARE SPECIFIED IN DIVISION -15 BASIC
MATERIALS AND METHODS SECTIONS. PROVIDE PRODUCTS OF SIZES, RATINGS, AND CHARACTERISTICS INDICATED, WHICH COMPLY
WITH MANUFACTURER'S STANDARD MATERIALS, DESIGN, AND CONSTRUCTION IN ACCORDANCE WITH PUBLISHED PRODUCT
INFORMATION; PROVIDE PROPER QUANTITY OF PIPING AND EQUIPMENT AS REQUIRED FOR COMPLETE INSTALLATION.
2.02 PIPE, TUBE AND FITTINGS
A. DOMESTIC WATER PIPING
1. COPPER TUBE: TYPE L HARD -DRAWN TEMPER; WROUGHT - COPPER FITTINGS; SOLDERED JOINTS WITH 95 -5 SOLDER.
2.03 PIPING SPECIALTIES
A. PIPE ESCUTCHEONS
INSTALL ON EACH PIPE PENETRATION EXPOSED TO VIEW IN OCCUPIED SPACES.
B. DRIP PANS
INSTALL UNDER PIPES PASSING OVER ELECTRICAL EQUIPMENT.
C. SUPPORTS, ANCHORS, AND SEALS
D HANGERS, SUPPORTS, -
PROVIDE FACTORY FABRICATE_ HANGER_ ORTS AND ANCHOR COMPLYING WITH MSS SP 69. INSTALL COMPLYING WITH MSS
SP -89.
PART 3.00 - EXECUTION
3.01 PIPING RUNOUTS TO FIXTURES
A. PROVIDE HOT AND COLD WATER PIPING RUNOUTS TO FIXTURES OF SIZES INDICATED, BUT IN NO CASE SMALLER THAN REQUIRED
BY THE PLUMBING CODE,
3.02 MECHANICAL EQUIPMENT CONNECTION
A. CONNECT HOT AND COLD WATER PIPING SYSTEM TO MECHANICAL EQUIPMENT AS INDICATED, AND COMPLY WITH EQUIPMENT
MANUFACTURER'S INSTALLATION INSTRUCTIONS. PROVIDE SHUTOFF VALVE AND UNION FOR EACH CONNECTION, PROVIDE DRAIN
VALVE ON DRAIN CONNECTION.
END OF SECTION 15401
SECTION 15405 SOIL & WASTE PIPING SYSTEM
PART 1.00 - GENERAL
1.01 GENERAL REQUIREMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 STANDARDS
A. COMPLY WITH APPLICABLE PLUMBING CODE STANDARDS PERTAINING TO MATERIALS, PRODUCTS, AND INSTALLATION OF DRAINAGE
PIPING AND EQUIPMENT.
B. COMPLY WITH APPLICABLE PDI STANDARDS PERTAINING TO PRODUCES AND INSTALLATION OF SOIL AND WASTE PIPING SYSTEMS.
PART 2.00 - PRODUCTS
2.01 GENERAL
A. BASIC PIPING MATERIALS AND PRODUCTS REQUIRED FOR THIS SECTION, ARE SPECIFIED IN DIVISION 15 PIPE, TUBE & FITTINGS
SECTION. PROVIDE PRODUCTS OF TYPES, SIZES, RATINGS, AND CHARACTERISTICS INDICATED, WHICH COMPLY WITH
MANUFACTURER'S STANDARD MATERIALS, DESIGN, AND CONSTRUCTION IN ACCORDANCE WITH PUBLISHED PRODUCT INFORMATION;
PROVIDE PROPER QUANTITY OF PIPING AND EQUIPMENT AS REQUIRED FOR COMPLETE INSTALLATION.
2.02 PIPES, TUBES AND FITTINGS
GENERAL: PROVIDE ONE OF THE FOLLOWING SELECTIONS AT INSTALLER'S OPTION
A. ABOVE GROUND BUILDING PIPING AND FITTINGS:
1. CAST -IRON HUB - AND - SPIGOT SOIL PIPE: SERVICE WEIGHT, CAST IRON HUB - AND - SPIGOT SOIL PIPE FITTINGS WITH
COMPRESSION GASKETS.
2. CAST -IRON HUBLESS SOIL PIPE: SERVICE WEIGHT CAST -IRON HUBLESS SOIL PIPE FITTINGS; HUBLESS JOINTS.
B. UNDERGROUND BUILDING DRAIN PIPING
1. CAST -IRON HUB - AND - SPIGOT SOIL PIPE FITTINGS, COMPRESSION GASKETS.
2. CAST -IRON HUBLESS SOIL PIPE: SERVICE WEIGHT; CAST -IRON HUBLESS SOIL PIPE FITTINGS; HUBLESS JOINTS.
C SUPPORTS, ANCHORS AND SEALS
PROVIDE FACTORY- FABRICATED HANGERS, SUPPORTS AND ANCHORS COMPLYING WITH MSS SP -69. INSTALL, COMPLYING WITH
MSS SP -89.
D. DRAINAGE PIPING PRODUCTS
1. CLEANOUT PLUGS: CAST - BRONZE OR BRASS, THREADS COMPLYING WITH ANSI B2.1, COUNTERSUNK HEAD. INSTALL IN
CLEANOUTS AS INDICATED AND AS REQUIRED BY THE PLUMBING CODE.
E. FLOOR CLEANOUTS
CAST -IRON BODY AND FRAME; ADJUSTABLE ROUND TOP AS FOLLOWS:
1. NICKEL - BRONZE TOP: PATTERN TO SUIT ADJACENT FLOOR FINISH. INSTALL IN OCCUPIED AREAS.
2. CAST -IRON TOP: PATTERN TO SUIT ADJACENT FLOOR FINISH. INSTALL IN UNOCCUPIED AREAS.
F. WALL CLEANOUTS
CAST -IRON BODY ADAPTABLE TO PIPE WITH CLEANOUT PLUG, STAINLESS STEEL ROUND COVER AND SCREW.
G. DRAINAGE PIPING PRODUCTS MANUFACTURER JOSAM, SMITH, WADE OR ZURN.
H. FLOOR DRAINS: AS SPECIFIED ON DRAWINGS. PROVIDE TRAP PRIMER CONNECTION.
11.ECEIVED
APR 012006
PERMIT CENTER
COPYRIGHT 0 2008 CARTER & BURGESS, INC.
at &t
Carter:Burgess
Carter & Burgess, Inc.
4 Hutton Centre Drive, Suite 800
Santa Ana, California 92707
TEL: (714) 327- 1600
FAX: (714) 327 -1601
CODE COMPLIANCE
PR VED
ApIR
City Of TukwNii I,
D
1 03 -29 -08 TENANT CHANGES
03 -19 -08 ISSUE FOR PERMIT
NO. DATE
16425 Southcenter Parkway
T U KW I LA, WA
DESIGNED BY:
KL
CHECKED BY:
MV
DRAWN BY:
KL
PROJECT NUMBER:
SCALE:
1 EXPIRES 03/15/10
ISSUES /REVISIONS
DESCRIPTION
MECHANICAL AND
PLUMBING
SPECIFICATIONS
APPROVED BY:
MV
441805.011.039.0001
NONE
M -003
PART 3.00 - EXECUTION
3.01 GENERAL
A. EQUIPMENT CONNECTIONS
PROVIDE SOIL AND WASTE PIPING RUNOUTS TO PLUMBING FIXTURES AND DRAINS, WITH APPROVED TRAP, OR SIZES INDICTED;
BUT IN NO CASE SMALLER THAN REQUIRED BY THE LOCAL PLUMBING CODE.
B. LOCATE PIPING RUNOUTS AS CLOSE AS POSSIBLE TO BOTTOM OF FLOOR SLAB SUPPORTING FIXTURES OR DRAINS.
C. TEST SOIL AND WASTE PIPING SYSTEM IN ACCORDANCE WITH REQUIREMENTS OF LOCAL PLUMBING CODES.
D. COORDINATE WITH SOIL AND WASTE PIPING AS NECESSARY TO INTERFACE FLOOR DRAINS WITH DRAINAGE PIPING SYSTEMS.
E. INSTALL FLOOR DRAINS IN ACCORDANCE WITH WRITTEN MANUFACTURER'S INSTRUCTIONS, AT LOW POINTS OF SURFACE AREAS TO
BE DRAINED, OR AS INDICATED. SET TOPS OF DRAINS FLUSH WITH FINISHED FLOOR. COORDINATE WITH ARCHITECTURAL
DRAWINGS.
F. INSTALL DRAIN FLASHING COLLAR OR FLANGE SO THAT NO LEAKAGE OCCURS BETWEEN DRAIN AND ADJOINING FLOORING.
MAINTAIN INTEGRITY OF WATERPROOF MEMBRANES, WHERE PENETRATED.
3.02 SEWER LINES
A. INSTALLATION
INSTALL UNDERGROUND BUILDING DRAINS AS INDICATED AND IN ACCORDANCE WITH THE PLUMBING CODE. LAY UNDERGROUND
BUILDING DRAINS BEGINNING AT LOW POINT OF SYSTEMS, TRUE TO GRADES AND ALIGNMENT INDICATED WITH UNBROKEN
CONTINUITY OF INVERT. PLACE BELL ENDS OF PIPING FACING UPSTREAM. INSTALL REQUIRED GASKETS IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS FOR USE OF LUBRICANTS, CEMENTS, AND OTHER SPECIAL INSTALLATION REQUIREMENTS.
OUS MATERIAL AS WORK PROGRESSES. MAINTAIN SWAB OR DRAG IN
CLEAN INTERIOR OF PIPING OF DIRT AND OTHER SUPERFL U MATE _ R L A W R
LINE AND PULL PAST EACH JOINT AS IT IS COMPLETED. PLACE PLUGS IN ENDS OF UNCOMPLETED PIPING AT END OF DAY OR
WHENEVER WORK STOPS.
B. INSTALL SOIL AND VENT PIPING PITCHED TO DRAIN AT MINIMUM SLOPE OF 1/4" PER FOOT (2%) AND 1/8" PER FOOT WHERE
INDICATED ON DRAWINGS.
VENT PIPING MAY BE INSTALLED HORIZONTAL IF REQUIRED TO AVOID CONFLICT WITH BUILDING ELEMENTS.
C. PROVIDE TRAP PRIMER AT ALL FLOOR DRAINS. TRAP PRIMERS SHALL HAVE EASY MAINTENANCE ACCESS.
D. CONDENSATE DRAIN PIPING SHALL BE PVC, UNLESS LANDLORD REQUIRES COPPER PER TENANT CRITERIA.
3.03 PIPING SPECIALITIES
A. PIPE ESCUTCHEONS: INSTALL ON EACH PIPE PENETRATION EXPOSED TO VIEW IN OCCUPIED SPACES.
B. DRIP PANS: INSTALL UNDER PIPES PASSING OVER ELECTRICAL EQUIPMENT.
END OF SECTION 15405
SECTION 15410 PLUMBING
PART 1.00 - GENERAL
1.01 DESCRIPTION
A. GENERAL REQUIREMENTS
DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 WORK INCLUDED
A. PROVIDE AND INSTALL ALL PLUMBING FIXTURES AND EQUIPMENT SPECIFIED HEREIN AND INDICATED ON THE DRAWINGS.
1.03 SUBMITTALS
A. SUBMIT MANUFACTURER'S TECHNICAL PRODUCT DATA, ASSEMBLY -TYPE SHOP DRAWINGS, AND MAINTENANCE DATA, IN ACCORDANCE
WITH SECTION 01300 IF SUBMITTING AS APPROVED EQUAL.
PART 2.00 - PRODUCTS
2.01 PLUMBING FIXTURES
A. PROVIDE ALL PLUMBING FIXTURES INDICATED AND SPECIFIED ON DRAWINGS. ALL FAUCETS AND DRINKING FOUNTAINS, ETC., SHALL
BE LEAD FREE AS DEFINED BY THE SAFE DRINKING WATER ACT AMENDMENTS FO 1986 AND THE LEAD CONTAMINATION CONTROL
ACT OF 1988. CONTAMINATION CONTROL ACT OF 1988.
2.02 ELECTRIC WATER HEATER
A. PROVIDE ALL WATER HEATERS INDICATED AND SPECIFIED ON DRAWINGS.
2.03 WATER HAMMER ARRESTOR
A. PROVIDE ALL WATER HAMMER ARRESTORS INDICATED AND SPECIFIED ON DRAWINGS.
PART 3,00 - EXECUTION
3.01 FIXTURES
A. FIXTURES SHALL BE INSTALLED WHERE SHOWN ON PLANS, COMPLETE WITH TRAPS, VALVES, STOPS AND ALL FITTINGS. ALL
FIXTURES SHALL BE FIRMLY ANCHORED AGAINST MOVEMENTS. LOCATE IN CENTER OF AREA ALLOWED UNLESS NOTED OTHERWISE.
FIXTURES SHALL BE INSTALLED COMPLETE WITH ALL FITTINGS AND NUMBERS SHALL INCLUDE THE FITTINGS AS IF THEY WERE
COMPLETELY LISTED AND SPECIFIED WITH EACH FIXTURE. PROVIDE CAULKING BETWEEN WALL AND FIXTURE ON ALL WALL HUNG
FIXTURES. USE RESILIENT (FLEXIBLE) PRODUCT SUCH AS GE SILILCONE BATHTUB SEALANT. PROVIDE SEALED WATER HAMMER
ARRESTORS ON HW AND CW SUPPLY PIPES AT EACH FIXTURE OR BANK OF FIXTURES. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS.
B. SEE ARCHITECTURAL PLANS FOR MOUNTING HEIGHTS OF ALL FIXTURES NOT NOTED IN THIS SPECIFICATION. COMPLY WITH
HANDICAPPED ACCESSIBILITY CODE REQUIREMENTS.
C. TRAP PRIMERS SHALL BE EASILY ACCESSIBLE. PROVIDE ACCESS PANEL IN WALL.
END OF SECTION 15410
SECTION 15820 AIR DISTRIBUTION EQUIPMENT
PART 1.00 - GENERAL
1.01 GENERAL REQUIREMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 COMPLIANCE
A. AMCA COMPLIANCE: TEST AND RATE AIR DISTRIBUTION EQUIPMENT IN ACCORDANCE WITH AMCA STANDARDS, AND PROVIDE AMCA
CERTIFIED RATINGS SEAL.
B. UL COMPUANCE: PROVIDE ELECTRICAL COMPONENTS OF AIR DISTRIBUTION EQUIPMENT WHICH HAVE BEEN LISTED AND LABELED
BY UL
1.03 SUBMITTALS
A. SUBMIT MANUFACTURER'S TECHNICAL PRODUCT DATA OF APPROVED EQUALS (SUBMITTALS ARE NOT REQUIRED IF PRODUCT
MATCHES SPECIFIED ITEMS ON DRAWINGS), ASSEMBLY - TYPE SHOP DRAWINGS, LADDER -TYPE WIRING DIAGRAMS DIFFERENTIATING
BETWEEN PORTIONS OF WIRING THAT ARE FACTORY INSTALLED AND PORTIONS TO BE HELD-INSTALLED, AND MAINTENANCE DATA.
PART 2,00 - PRODUCTS
2.01 HVAC SYSTEMS
A. PROVIDE EQUIPMENT AS SCHEDULED WITH ALL OPTIONS AS DESCRIBED ON THE MECHANICAL SCHEDULES ON THE MECHANICAL
DRAWINGS.
B. WHEREVER POSSIBLE, PROVIDE BELT DRIVEN EQUIPMENT AS SCHEDULED OR PROVIDED BY THE MANUFACTURER WITH ALL
OPTIONS INCLUDED IN THE SCHEDULES OR REQUIRED TO MEET THE PERFORMANCES NOTED ON THE MECHANICAL DRAWINGS.
PART 3.00 - EXECUTION
3.01 INSTALLATION
A. UNITS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS, INSTRUCTIONS AND DETAILS ON
DRAWINGS.
B. ALL EXHAUST FAN SYSTEMS TO HAVE BACKDRAFT OR MOTORIZED DAMPERS IN THE SYSTEM.
C. PROVIDE FLEXIBLE DUCT CONNECTIONS TO ALL FANS.
D. PROVIDE ROOF CURBS FOR ALL ROOF HOODS, ROOF MOUNTED EQUIPMENT AND DUCT PENETRATIONS THRU ROOF.
E. PROVIDE FACTORY AUTHORIZED STARTUP OF ALL EQUIPMENT.
END OF SECTION 15820
SECTION 15840 DUCTWORK
PART 1.00 - GENERAL
1.01 DESCRIPTION
A. GENERAL REQUIREMENTS
DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND CONDITIONS AND DIVISION 1 - GENERML
REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 WORK INCLUDED
A. INCLUDE ALL LABOR, MATERIALS, EQUIPMENT TRANSPORTATION AND SERVICES TO FURNISH AND INSTALL COMPLETE ALL
DUCTWORK AND RELATED SYSTEMS SPECIFIED HEREIN AND INDICATED ON THE DRAWING.
PART 2.00 - PRODUCTS
2.01 SHEETMETAL WORK
A. FURNISH ALL DUCTWORK AS SHOWN ON PLL■NS. ALL DUCTWORK CONSTRUCTION SHALL COMPLY WITH SMACNA STANDARDS AND
LOCAL MECHANICAL CODE STANDARDS, WHICHEVER IS MORE STRINGENT. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE
FOLLOWING PRESSURE VELOCITY CLASSIFICATIONS FOUND IN SMACNA HVAC DUCT CONSTRUCTION STANDARDS, FIRST EDITION
(1985).
1. DUCTWORK BETWEEN VAV AIR HANDLING UNITS AND TERMINAL BOXES: MAXIMUM +6" W.G., 4,000 F.P.M., VARIABLE AIR
VOLUME.
DOWNSTREAM 0 TERMINAL BOXES: +2"W.G., 2 500 F.P.M. VARIABLE AIR VOLUME.
2. DUCTWORK __ OF F.P.M.,
3. EXHAUST DUCTWORK (ALL EXHAUST FAN SYSTEMS WHERE DESIGN FAN STATIC IS LISTED AT 1.0" W.G. OR ABOVE): +2"
TO -2"W.G., 2500 F.P.M., CONSTANT VOLUME.
4. RETURN, RELIEF OR EXHAUST DUCTWORK WHERE FAN DESIGN STATIC IS LISTED BELOW 1.0"W.G.: +1" TO -1" W.G.,
2,500 F.P.M., CONSTANT VOLUME.
5. SUPPLY DUCTS NOT LISTED ABOVE: +2" TO -2" W.G., 2,500 F,P.M., CONSTANT VOLUME.
6. TRANSFER DUCTS: +0.5" TO -0.5" W.G., 2,000 F.P.M., CONSTANT VOLUME.
B. PRIOR TO ANY FABRICATING OF SHEET METAL WORK, THE MECHANICAL CONTRACTOR SHALL CAREFULLY MEASURE (AT THE SITE)
AVAILABLE SPACE FOR SHEET METAL WORK. HE SHALL PREPARE LARGE SCALE SHOP DRAWINGS OF SHEET METAL WORK
SHOWING ALL OTHER ELEMENTS OF THE BUILDING INCLUDING PIPING, STRUCTURAL AND ELECTRICAL SO ALL ARE COORDINATED
AND FIT AVAILABLE SPACE, THE SHOP DRAWINGS WILL NOT GO THROUGH A FORMAL SUBMITTAL PROCESS, BUT 2 COPIES SHALL
BE GIVEN TO THE ARCHITECT AS EVIDENCE OF THEIR BEING COMPLETED.
C. LONGITUDINAL SEAMS IN DUCTS SHALL BE FLAT, DOUBLE LOCK TYPE. S AND DRIVE TYPE.
D. TRANSVERSE SEAMS SHALL BE OF TYPE AND SPACING AS FOLLOWS:
MAX. SIDE TYPE SPACING
UP TO 30" DRIVE SUP 7' -10"
31" TO 60" 1 -1/2" POCKET SUP 7' -10"
61" AND UP 1 -1/2" POCKET SLIP 3'- 9"
CROSS BREAK PANELS 18" AND OVER IN WIDTH.
E. STANDING SEAMS ARE NOT ACCEPTABLE ON ANY DUCTWORK.
F. JOINT LOCKING: THE SLIPJOINT IN POCKET SLIP SEAMS SHALL BE SCREWED USING NOT LESS THAN ONE SCREW PER FACE AND
MAXIMUM SPACING OF 2' -0 ".
G. DAMPERS
PROVIDE DAMPERS AND QUADRANTS IN DUCTWORK AS NECESSARY FOR BALANCING. PROVIDE ONE DAMPER IN THE DUCT
LEADING TO EACH SUPPLY OR RETURN /EXHAUST OPENING. DAMPERS SHALL BE LOCATED IN AN ACCESSIBLE LOCATION.
DAMPERS SHALL BE FITTED WITH PARKER KALON DAMPER BEARINGS AND PARKER KALON NO, 195T QUADRANTS. DAMPERS
SHALL BE OF 20 GA. G.I. SINGLE PLATE TYPE WITH EDGES HEMMED. FOR DAMPERS ABOVE "HARD" (GYPBOARD OR
NON- ACCESSIBLE) CEILINGS, PROVIDE BOWDEN CABLE CONTROLLER WITH CONCEALED OPERATORS IN NEAREST RETURN GRILLE.
SHOW LOCATION OF ALL REMOTE DAMPER OPERATORS & VOLUME DAMPERS ON RECORD DRAWINGS. INCLUDE DRAWING
W /BALANCING REPORT. ADUSTABLE SPLITTER DAMPERS TO BE YOUNG REGULATOR 8908.
H. ACCESS DOORS SHALL BE PROVIDED BY THIS CONTRACTOR IN FINISHED WALLS AND CEILINGS WHERE REQUIRED TO REACH
MECHANICAL EQUIPMENT, MILCOR OR EQUAL.
I. INSULATED LOW PRESSURE FLEXIBLE DUCT SHALL BE A FACTORY FABRICATED ASSEMBLY CONSISTING OF A ZINC - COATED SPRING
STEEL HELIX, NON- PERFORATED INNER LINER, WRAPPED WITH A NOMINAL 1 THICK BY 1 LB /CU. FT. DENSITY FIBERGLASS
INSULATION. THE ASSEMBLY SHALL BE SHEATHED IN A VAPOR BARRIER JACKET, FACTORY SEALED AT BOTH ENDS OF EACH
SECTION, THUS ASSURING THE VAPOR RESISTANCE OF EACH SECTION AS WELL AS THE COMPLETED INSTALLATION. THE
COMPOSITE ASSEMBLY INCLUDING INSULATION AND VAPOR BARRIER SHALL MEET THE CLASS 1 REQUIREMENTS OF NFPA BULLETIN
NO. 90 -A AND BE LABELED BY UL WITH A FLAME SPREAD RATING OF 25 OR LESS AND A SMOKE DEVELOPED RATING OF 50
OR UNDER. FLEXIBLE DUCTS SHALL BE INSTALLED IN A FULLY EXTENDED LENGTH REQUIRED TO MAKE THE CONNECTION. WHERE
HORIZONTAL SUPPORT IS REQUIRED, FLEXIBLE DUCT SHALL BE SUSPENDED ON 36" CENTERS WITH A MINIMUM 3/4" WIDE FLAT
BANDING MATERIAL. ALL JOINTS AND CONNECTIONS SHALL BE MADE WITH 1/2" WIDE POSITIVE LOCKING STEEL STRAPS.
INSULATED LOW PRESSURE FLEXIBLE DUCT SHALL BE GREENFLEX TYPE SL -1 OR EQUAL. PROVIDE SPIN -IN FITTINGS FOR
CONNECTION TO TRUCK DUCT. MAXIMUM LENGTH OF FLEX DUCT 5 5 FEET WITH ONE 90 DEGREE BEND.
J. OFFSETS
PROVIDE OFFSETS AND TRANSITIONS AS REQUIRED TO FIT DUCTWORK INTO AVAILABLE SPACE. MAINTAIN EQUIVALENT FREE AREA
OF DUCTWORK, AND TRANSITION SHALL BE SMOOTH (LESS THAN 15 DEGREES).
2.02 DUCT LINING
A. JOHNS MANSVILLE 1 THICK 1.5 LB /CU.FT. DENSITY (WHERE CALLED OUT ON DRAWINGS AND OR WHERE SPECIFIED) LINACOUSTIC
R -4 MIN. OR 1.5" THICK 1.5 LB /CU.FT. DENSITY LINACOUSTIC R -5 MIN. WHERE "SOUNDLINED" OR "LINED" DUCT IS CALLED
OUT ON DRAWINGS OR SPECIFIED. SERVICE WITH GLUE AND CLIPS. SPACE CLIPS A MAXIMUM OF 18 "0.C. LINE ALL
RECTANGULAR DUCTS (INCLUDES OUTSIDE AIR, SUPPLY, RETURN, EXHAUST AND TRANSFER DUCTS). THE NET FREE AREA OF THE
DUCT DIMENSIONS GIVEN ON THE DRAWINGS SHALL BE MAINTAINED. INCREASE METAL DUCT DIMENSIONS AS NECESSARY TO
COMPENSATE FOR ADDITION OF THE LINER.
B. THE DUCT LINER SHALL BE APPLIED WITH 100% COVERAGE OF APPROVED FIRE RESISTANT ADHESIVE. LINER SHALL BE
ADDITIONALLY SECURED WITH MECHANICAL FASTENERS ON MAXIMUM 15" CENTERS. FASTENERS SHALL START WITHIN 2" OF THE
LEADING EDGE OF EACH SECTION AND WITHIN 3" OF THE LEADING EDGE OF ALL CROSS JOINTS WITHIN THE DUCT SECTION. ALL
EXPOSED EDGES AND THE LEADING EDGE OF ALL CROSS JOINTS OF THE LINER SHALL BE HEAVILY COATED WITH AN APPROVED
FIRE RESISTANT ADHESIVE. THE DUCT LINER SHALL BE CUT TO ASSURE SNUG CLOSING CORNER JOINTS, THE BLACK SURFACE
OF THE LINER SHALL FACE THE AIR STREAM, TRANSVERSE JOINTS SHALL BE NEATLY BUTTED, AND ANY DAMAGED AREAS SHALL
BE HEAVILY COATED WITH AN APPROVED FIRE RESISTANT ADHESIVE.
2.03 BACKDRAFT DAMPERS
A. GENERAL
PROVIDE DAMPERS AT ALL OUTSIDE AIR AND RELIEF DUCTS INTAKING OR EXHAUSTING TO ATMOSPHERE.
B. TYPE
1. BACKDRAFT DAMPERS ON FAN SYSTEMS SHALL BE GALVANIZED STEEL OR ALUMINUM MULTIBLADE TYPE. BLADES SHALL
HAVE FELT STRIPS RIVETED OR CRIMPED IN PLACE. BLADES SHALL BE JOINED TOGETHER WITH CONNECTION BARS.
EACH BLADE SHALL BE RIGIDLY ATTACHED TO A PIVOT ROD. THE ROD SHALL EXTEND INTO OIL- IMPREGNATED BRONZE
BUSHINGS, OR ANTIFRICTION BEARINGS, LOCATED IN THE FRAMES. RUSKIN CBD2 OR EQUAL.
2. FABRIC BACKDRAFT DAMPERS ON RELIEF DUCTS SHALL BE CONSTRUCTED TO INDUSTRY STANDARDS.
C. MANUFACTURER
2.04 LOUVERS
A. FURNISH WONDER METAL MODEL 'SDL -4" DRAINABLE FORMED GALVANIZED STEEL STORM -PROOF MULLION NON- MECHANICAL
FIXED WALL LOUVERS, OR AIR LOUVERS INC., THE AIROLTTE CO., CONSTRUCTION SPECIALTIES INC., RUSKIN, OR INDUSTRIAL
LOUVERS INC. EQUIVALENT, OR APPROVED; SIZES AND CONFIGURATIONS AS SHOWN, COMPLETE WITH FLAT BAR ORNAMENTAL
SHAPES WERE SHOWN; REFER TO EXTERIOR BUILDING ELEVATIONS AND LOUVER SCHEDULE, SECTION 22 OF PROJECT MANUAL
VOLUME II. PROVIDE WITH BIRD SCREEN AND COLOR AS DESIGNATED BY ARCHITECT.
B. LOUVERS SHALL HAVE BEEN TESTED AND RATED TO HAVE MINIMUM 45% FREE OPENING BASED ON A 4X4 FOOT SIZE LOUVER.
C. FRAME AND BLADES TO BE 16 GAUGE GALVANIZED STEEL.
D. HEADS, SILLS AND JAMBS TO BE ONE PIECE STRUCTURAL MEMBERS AS DETAILED AND SECURELY ANCHOR TO WALL
CONSTRUCTION AS APPROVED.
E. SLIDEABLE INTERLOCKED MULLIONS TO HAVE PROVISION TO EXPANSION AND CONTRACTION.
F. FURNISH COMPLETE WITH MANUFACTURER'S STANDARD BIRD SCREEN MOUNTED IN FOLDED "U" TYPE FRAME AND ATTACH TO
INSIDE FACE OF LOUVER FRAME WITH STEEL SCREWS AT ACTIVE (OPEN) PORTIONS OF LOUVERS AND WITH 20 GAUGE
GALVANIZED STEEL FACED INSULATED 'BLANK -OFF' PANELS AT INACTIVE LOUVER AREAS, COMPLETE WITH PERIMETER GASKETS
AND FINISHED TO MATCH LOUVER. INSULATION CORE SHALL BE 1 INCH THICK EXTRUDED POLYSTRYENE HAVING A MINIMUM
THERMAL RESISTANCE "R" VALUE OF 5.0.
G. ALL LOUVERS TO BE FREE OF SCRATCHES AND BLEMISHES AND SHALL BE FINISH PAINTED WITH BAKED -ON ENAMEL POWDER
COATING.
2.05 FIRE DAMPERS
A. DYNAMIC FIRE DAMPERS SHALL BE CONSTRUCTED AND TESTED IN ACCORDANCE WITH UL SAFETY STANDARD 555. EACH DAMPER
SHALL HAVE A 1 1/2 HOUR RATING WITH 165 DEGREE F FUSABLE LINK AND BE LABLED PER UL 555 STANDARD.
B. DYNAMIC COMBINATION FIRE /SMOKE DAMPERS,RUSKIN FSD36, SHALL BE CONSTRUCTED OF MIN. 16 GAUGE GALVANIZED STEEL
WITH STAINLESS STEEL BEARINGS, JAMB SEALS AND 450 DEG. F RATED BLADE EDGE SEAL. DAMPERS SHALL BE 1 HR. RATED
UNDER UL STANDARD 555 AND UL 5555. ALL DAMPERS USED UNDER THIS SPECIFICATION MUST BE UL TESTED & QUALIFIED IN
THE COMPLETE RANGE OF SIZES USED. A SINGLE DAMPER TESTED WITHIN THIS RANGE IS NOT ACCEPTABLE. LEAKAGE RATING
SHALL BE CLASS 11. INCLUDE A UL CLASSIFIED FIRE STAT. FIRESTAT SHALL ELECTRICALLY AND MECHANICALLY LOCK DAMPER
CLOSED WHEN DUCT TEMPERATURE EXCEEDS 165 DEG. F. DAMPER MUST BE OPERABLE ABOVE 250 DEG. F. FIRESTAT SHALL
BE EQUIPPED WITH TWO DAMPER POSITION INDICATORS FOR REMOTE INTERFACING WITH SMOKE DETECTORS & FIRE ALARM
SYSTEM. ALSO PROVIDE INTEGRAL FLOW RATED DUCT SMOKE DETECTORS FOR DUCTED FIRE/ SMOKE DAMPERS AND NO -FLOW
DUCT SMOKE DETECTORS FOR NON- DUCTED FIRE SMOKE DETECTORS.
C. CEIUNG FIRE DAMPERS SHALL BE INSTALLED IN ALL CEILING REGISTERS AND GRILLES. IN THE RATED CEILING. FIRE DAMPERS
CONSIST OF A RADIANT DAMPER IN THE DIFFUSER NECK AND THERMAL INSULATING BLANKET COVERING THE DIFFUSER PAN. THE
ENTIRE SYSTEM SHALL BE UL RATED FOR FLOOR /CEILING AND ROOF /CEILING SYSTEM.
PART 3.00 - EXECUTION
3.01 SHEET METAL WORK
A. PARTITIONS FORMING PLENUMS OR CASINGS SHALL BE #18 GA., WITH GALVANIZED IRON ANGLES AND RIVETS FOR SEAM
CONNECTION AND STIFFENING. ALL JOINTS AND STANDING SEAMS SHALL BE SEALED WITH APPROVED DUCT SEALANT.
B. CORK GASKETS SHALL BE INSTALLED BETWEEN ALL CONNECTIONS OF SHEET METAL TO COIL AND FILTER CASINGS.
C. SHEET METAL CONNECTIONS OF PLENUMS AND AIR CHAMBERS TO WALL AND FLOORS SHALL BE MADE WITH GALVANIZED ANGLES
ANCHORED TO WALL OR FLOOR CONSTRUCTION WITH ANCHOR BOLTS WITH SHEET METAL BOLTED OR RIVETED TO ANGLES.
MASTIC SEALER SHALL BE INSTALLED AT CONNECTION OF ANGLES TO SHEET METAL TO PROVIDE AIR -TIGHT JOINTS. PROVIDE
ACCESS DOORS IN PLENUMS AND CHAMBERS WITH HANDLES OPERATED FROM BOTH SIDES, VENTLOCK NO. 205 OR APPROVED
SUBSTITUTE.
D. HINGED ACCESS DOORS IN SHEET METAL DUCT FOR ACCESS TO DAMPERS SHALL BE #18 GA., FRAMED WITH STEEL ANGLE AND
HEMMED EDGES.
E. CONNECT ALL GRILLES TO DUCTWORK. PAINT THE INSIDE OF THE DUCT A DULL BLACK AT ALL GRILLES.
F. ALL AIR INLETS AND OUTLETS TO OUTSIDE SHALL HAVE BIRDSCREENS. BACKDRAFT DAMPER SHALL BE PROVIDED WHERE
MOTORIZED DAMPER IS NOT INDICATED.
G. ALL DUCTS THROUGH ROOF SHALL BE FLASHED WATER - TIGHT. SEE DETAIL. ALL DUCTS THRU WALLS AND FLOORS /ROOFS SHALL
HAVE ANGLE ENCLOSURES.
H. CONNECTIONS OF ALL DUCTS TO ALL EQUIPMENT SHALL BE MADE WITH NEOPRENE.
I. ELBOWS SHALL HAVE AN INSIDE RADIUS EQUAL TO 1/2 THE DUCT WIDTH. RECTANGULAR ELBOWS SHALL HAVE DUCT TURNS, T &B
OR APPROVED EQUAL. USE RECTANGULAR ELBOWS WHEREVER A ROUND ELBOW CANNOT BE USED AND WHERE SHOWN ON
DRAWINGS. SQUARE INSIDE ELBOW AND ROUND OUTSIDE ELBOW ARE NOT PERMITTED. DO NOT INSTALL TURNING VANES IN
GREASE EXHAUST DUCTWORK.
J. SUPPORTERS SHALL BE GALVANIZED STRAP OR ANGLE IRON HANGERS, ARRANGED TO PREVENT ANY BULGING, BENDING, OR
SAGGING OF DUCTWORK. UNDER NO CONDITION SHALL HANGERS PIERCE THE DUCTS. VERTICAL DUCTS SHALL BE SUPPORTED AT
EACH FLOOR WITH 18 GA. FORMED ANGLE.
K. SEAL ALL DUCT JOINTS WITH APPROVED DUCT SEALANT.
L HANGERS
1. PROVIDE HANGERS AND SEISMIC RESTRAINTS ON ALL DUCTWORK.
2. HANGERS FOR CIRCULAR DUCTS AND TUBING: A #18 GAUGE GALVANIZED SHEET STEEL STRAP SHALL BE WRAPPED
AROUND THE DUCT AT EACH POINT OF SUPPORT. FOR CONCEALED WORK THIS STRAP SHALL BE BOLTED TO A STRAP
HANGER OF SIMILAR GAUGE AND WIDTH; FOR EXPOSED WORK, BOLTED TO A STEEL ROD HANGER IN EACH CASE, ROD
HANGER 1/4" SIZE FOR DUCTS UP TO 10" SIZE, 3/8" SIZE FOR LARGER DUCTS. WIDTH OF GALVANIZED STEEL STRAP
WRAPPED AROUND THE DUCT SHALL NOT BE LESS THAN 1" IN ANY CASE; WHERE DUCTS ARE IN EXCESS OF 10" IN
DIAMETER SHALL BE 2 ".
3. SPACING OF HANGERS SHALL NOT EXCEED 10' -0" ON CENTERS IN ANY CASE; WHERE DUCTS ARE INSULATED AND ARE IN
EXCESS OF 10" IN SIZE, SPACING SHALL NOT EXCEED 8' -0 ".
M. A MAXIMUM OF 5 FEET LENGTH OF FLEX DUCT WITH ONE 90 DEGREE BEND WILL BE ALLOWED AT CONNECTIONS TO DIFFUSERS,
WHERE FLEX DUCT IS SHOWN ON DRAWINGS.
N. PROVIDE FIRE STOP AROUND DUCTWORK AT ALL DUCT PENETRATION OF RATED CONSTRUCTION. "FIRE STOP SEALANT" BY DOW
CORNING.
0. BACKDRAFT DAMPERS ON RELIEF DUCTS SHALL BE METAL BLADE TYPE.
P. PROVIDE DUCT TRANSITIONS AS REQUIRED TO SOUND TRAPS AND ALL EQUIPMENT CONNECTIONS.
Q. PROVIDE DUCT LINING ON RECTANGULAR DUCTS WHERE INDICATED ON DRAWINGS (OUTSIDE AIR, SUPPLY, RETURN, EXHAUST AND
TRANSFER AIR DUCTS). THE NET FREE AREA OF THE DUCT DIMENSION GIVEN ON THE DRAWINGS SHALL BE MAINTAINED.
INCREASE METAL DUCT DIMENSIONS AS NECESSARY TO COMPENSATE FOR ADDITION OF THE LINER.
R. ALL DUCTWORK, INCLUDING, BUT NOT LIMITED TO DUCTS, HANGERS, BRACKETS, FITTINGS AND JOINTS, SHALL BE INSTALLED IN A
MANNER WHICH NEITHER REDUCES HEADROOM AND WALKWAY WIDTH NOR PROJECTS ANY SHARP EDGES INTO A CATWALK OR
PASSAGE AREA. ANY DUCTWORK WHICH, IN THE OPINION OF THE ARCHITECT, PRESENTS A POSSIBLE HAZARD TO PEOPLE IN THE
CATWALK AREA, SHALL BE CHANGED TO AN ACCEPTABLE AND SAFE MANNER, SUCH CHANGES MAY INCLUDE: MOVING THE
EQUIPMENT, CHANGING ITS CONFIGURATION, AND /OR ADDING PROTECTIVE PADDING TO THE EQUIPMENT.
S. INTAKE BACKDRAFT DAMPERS SHALL BE INSTALLED AT THE ENVELOPE OF THE BUILDING.
T. INSTALL FIRE DAMPERS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
END OF SECTION 15840
SECTION 15870 OUTLETS AND INLETS
PART 1.00 - GENERAL
1.01 DESCRIPTION
A. GENERAL REQUIREMENTS
DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 COMPLIANCES
A. ADC COMPLIANCE
TEST AND RATE REGISTERS, GRILLES, AND DIFFUSERS IN ACCORDANCE WITH ADC EQUIPMENT TEST CODE 1062R4, PROVIDE
CERTIFIED RATINGS SEAL ON EACH UNIT.
B. AMCA COMPLIANCE
TEST AND RATE LOLVERS, DAMPERS, AND SHUTTERS IN ACCORDANCE WITH AMCA STANDARD 500, PROVIDE CERTIFIED RATINGS
SEAL ON EACH UNIT.
1.03 SUBMITTALS
A. SUBMIT MANUFACTURER'S TECHNICAL PRODUCT DATA UNLESS AS SPECIFIED ON DRAWINGS, ASSEMBLY -TYPE SHOP DRAWINGS,
AND MAINTENANCE DATA.
PART 2.00 - PRODUCTS
2,01 CEILING AIR DIFFUSERS
A. GENERAL
EXCEPT AS OTHERWISE INDICATED, PROVIDE MANUFACTURER'S STANDARD CEILING AIR DIFFUSERS WITH FIRE DAMPERS; OF SIZE,
SHAPE, CAPACITY AND TYPE INDICATED; CONSTRUCTED OF MATERIALS AND COMPONENTS INDICATED AND AS INDICATED ON
DRAWINGS FOR COMPLETE INSTALLATION.
B. CEILING COMPATIBILITY
PROVIDE DIFFUSERS WITH BORDER STYLES THAT ARE COMPATIBLE WITH ADJACENT CEILING SYSTEMS, AND THAT ARE SPECIFICALLY
MANUFACTURED TO FIT INTO CEILING MODULE WITH ACCURATE FIT AND ADEQUATE SUPPORT. REFER TO GENERAL CONSTRUCTION
DRAWINGS AND SPECIFICATIONS FOR TYPES OF CEILING SYSTEMS WHICH WILL CONTAIN EACH TYPE OF CEILING AIR DIFFUSER.
C. TYPES
PROVIDE TITUS CEILING DIFFUSERS OF TYPE, CAPACITY, AND WITH ACCESSORIES AND FINISHES AS SCHEDULED.
2.02 REGISTERS AND GRILLES
A. GENERAL
EXCEPT AS OTHERWISE INDICATED, PROVIDE MANUFACTURER'S STANDARD WALL REGISTERS AND GRILLES WITH FIRE DAMPERS; OF
SIZE, SHAPE, CAPACITY AND TYPE INDICATED; CONSTRUCTED OF MATERIALS AND COMPONENTS AS INDICATED ON DRAWINGS, AND
AS REQUIRED FOR COMPLETE INSTALLATION.
B. PERFORMANCE
PROVIDE WALL REGISTERS AND GRILLES THAT HAVE, AS MINIMUM, TEMPERATURE AND VELOCITY TRAVERSES, THROW AND DROP,
AND NOISE CRITERIA RATINGS FOR EACH SIZE DEVICE AS LISTED IN MANUFACTURER'S CURRENT DATA.
C. COMPATIBILITY
PROVIDE REGISTERS AND GRILLES WITH BORDER STYLES THAT ARE COMPATIBLE WITH ADJACENT WALL OR CEILING SYSTEMS, AND
THAT ARE SPECIFICALLY MANUFACTURED TO FIT INTO CONSTRUCTION WITH ACCURATE FIT AND ADEQUATE SUPPORT. REFER TO
GENERAL CONSTRUCTION DRAWINGS AND SPECIFICATIONS FOR TYPES OF CONSTRUCTION WHICH WILL CONTAIN EACH TYPE OF
WALL REGISTER AND GRILLE.
D. TYPES
PROVIDE WALL REGISTERS AND GRILLES OF TYPE, CAPACITY, AND WITH ACCESSORIES AND FINISHES AS SCHEDULED.
E. MANUFACTURERS:
1. TITUS
PART 3.00 - EXECUTION
3.01 INSTALLATION
A. GENERAL
INSTALL OUTLETS AND INLETS IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND IN ACCORDANCE WITH
RECOGNIZED INDUSTRY PRACTICES TO INSURE THAT PRODUCTS SERVE INTENDED FUNCTIONS. REFER TO INSTALLATION DETAILS
REFERENCED IN PARAGRAPH 2.03A ABOVE.
B. COORDINATE WITH OTHER WORK, INCLUDING DUCTWORK AND DUCT ACCESSORIES, AS NECESSARY TO INTERFACE INSTALLATION OF
OUTLETS AND INLETS WITH OTHER WORK.
C. LOCATE CEILING AIR DIFFUSERS, REGISTERS, AND GRILLES, AS INDICATED ON GENERAL CONSTRUCTION "REFLECTED CEILING
PLANS" AND "INTERIOR ELEVATIONS ". UNLESS OTHERWISE INDICATED, LOCATE UNITS IN CENTER OF ACOUSTICAL CEILING
MODULES.
END OF SECTION 15870
SECTION 15880 FILTERS
PART 1.00 - GENERAL
1.01 GENERAL REQUIREMENTS
A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 COMPLIANCE
A. NFPA COMPLIANCE: INSTALL AIR TREATMENT EQUIPMENT IN ACCORDANCE WITH NFPA 90A AND 900.
B. UL COMPLIANCE: PROVIDE AIR FILTER UNITS WHICH HAVE BEEN LISTED AND LABELED BY UL.
C. ASHRAE COMPLIANCE: TEST AIR FILTER UNITS IN ACCORDANCE WITH ARI 850.
PART 2.00 - PRODUCTS
2.01 AIR FILTERS
A. EXTENDED SURFACE FILTERS
PROVIDE FACTORY - FABRICATED, DRY, EXTENDED SURFACE FILTERS; WHERE SHOWN, IN SIZES INDICATED. EQUIP WITH UL CLASS 1
FIBROUS MEDIA MATERIAL FORMED INTO 2" DEEP V- SHAPED PLEATS AND HELD BY SELF- SUPPORTING FRAMES. FARR 30/30
OR EQUAL.
2.02 FILTER FRAMES
A. PROVIDE METAL FILTER FRAMES AS DETAILED ON DRAWINGS,
PART 3.00 - EXECUTION
3.01 INSTALLATION
A. INSTALL AIR FILTERS AND HOLDING DEVICES OF TYPES INDICATED, AND WHERE SHOWN; IN ACCORDANCE WITH AIR FILTER
MANUFACTURER'S WRITTEN INSTRUCTIONS AND WITH RECOGNIZED INDUSTRY PRACTICES; TO ENSURE THAT FILTERS COMPLY WITH
REQUIREMENTS AND SERVE INTENDED PURPOSES. COMPLY WITH APPLICABLE PORTIONS OF NFPA 70, 90A AND B, PERTAINING TO
INSTALLATION OF AIR FILTERS. PROVIDE AS SCHEDULED ON THE DRAWINGS.
B. INSTALL FILTERS IN PROPER POSITION TO PREVENT PASSAGE OF UNFILTERED AIR.
C. PROVIDE CLEAN SET OF FILTERS FOR ALL PIECES OF EQUIPMENT:
1. IMMEDIATELY PRIOR TO AIR BALANCING.
2. WHEN FINAL PUNCHLIST IS DONE.
3. IN ADDITION, FURNISH ONE COMPLETE EXTRA SET OF FILTERS TO OWNER WHEN FINAL PUNCHLIST IS DONE. THREE SETS OF
FILTERS ARE REQUIRED (TWO INSTALLED, ONE TURNED OVER TO OWNER). LOCATE EXTRA SET IN MECHANICAL ROOMS
WHERE FILTERS ARE LOCATED.
D. FILTERS SHALL BE EASILY CHANGED FROM FRAMES AND SHALL SLIDE FREELY ON TRACKS WITHOUT BINDING. MAINTAIN CLEAR
ACCESS IN FRONT OF FILTER ACCESS DOOR TO FULL WIDTH OF THE FILTER.
E. FILTER SECTIONS SHALL HAVE HINGED ACCESS DOORS WITH LATCHES.
END OF SECTION 15880
SECTION 15980 BALANCING
PART 1.00 - GENERAL
1.01 DESCRIPTION
A. GENERAL REQUIREMENTS
DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND OTHER CONDITIONS AND DIVISION 1 -
- GENERAL REQUIREMENTS SECTIONS, APPLY TO THE WORK SPECIFIED IN THIS SECTION.
1.02 INDUSTRY STANDARDS
A. ALL TESTING, ADJUSTING AND BALANCING OF ALL WORK SHALL BE PERFORMED BY AN INDEPENDENT CONTRACTOR WHO IS
CURRENTLY LICENSED ASSOCIATED AIR BALANCING COUNCIL (MBC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB)
BALANCING CONTRACTOR. NO OTHER BALANCE REPORTS WILL BE REVIEWED OR ACCEPTED. ALL BALANCING WORK MUST BE
COMPLETE AND DONE IN ACCORDANCE WITH THE MOST RECENT STANDARDS OF THEIR SOCIETY. PAYMENT OF ALL COSTS FOR
TESTING AND BALANCING SHALL BE BY THE GENERAL CONTRACTOR. ALL BALANCING WORK SHALL BE PERFORMED WITH
ACCORDANCE WITH LOCAL CODES AND THIS SECTION.
1.03 SUBMITTALS
A. SUBMIT CERTIFIED TEST REPORTS SIGNED BY TEST AND BALANCE SUPERVISOR WHO PERFORMED TAB WORK, SUBMIT RECORD
HVAC PLAN SHOWING ALL VOLUME DAMPER & REMOTE VOLUME DAMPER OPERATOR LOCATIONS & CONNECTION LINKAGE.
B. THE BALANCE REPORT SHALL BE ON THE MBC NATIONAL STANDARD REPORT FORMS OR THE NEBB CERTIFIED REPORT FORMS
AS PUBLISHED IN THEIR MOST CURRENT EDITIONS AND SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION.
1. MBC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF BALANCING CONTRACTOR.
2. COPY OF A CERTIFICATE OF CONFORMANCE WITH NATIONAL STANDARDS FOR THIS PROJECT.
3. INSTRUMENTATION LIST WITH LAST CALIBRATION DATES.
4. MAKE AND MODEL NUMBERS OF ALL HVAC EQUIPMENT.
5. AIR CFM AND STATIC PRESSURE READINGS (DISCHARGE AND SUCTION) AS MEASURED BY PITOT TUBE DUCT TRAVERSE AT THE
UNIT.
6. MOTOR NAMEPLATE DATA WITH ACTUAL FIELD VOLTAGE AND AMPERAGE READINGS FOR EACH LEG.
7. MOTOR AND FAN R.P.M.'S, SHEAVE SIZES AND BELT SIZES.
8. OUTSIDE, RETURN, MIXED AND SUPPLY AIR TEMPERATURES AND VOLUMES SHALL BE MEASURED AT FULL COOLING WITH MINIMUM
OUTSIDE AIR. RETURN /RELIEF /SMOKE EVACUATION AIRFLOW SHALL BE BALANCED AND MEASUREMENTS RECORDED BY PITOT
DUCT TRAVERSE AT FULL ECONOMIZER AND POWER EXHAUST.
9. MAKE AND MODEL NUMBERS OF ALL AIR DISTRIBUTION EQUIPMENT.
10. FINAL BALANCED AIR VOLUMES AT ALL OUTLETS (INCLUDING RETURNS WHERE DUCTED).
11. INDEXED PLAN WITH DIFFUSER AND RETURN LOCATIONS. ALSO INDICATE IF DIFFUSER IS 3 -WAY OR 2 -WAY.
A. FIVE COPIES OF THE BALANCE REPORT SHALL BE SUBMITTED TO HOLD EVERYTHING PROJECT MANAGER FOR APPROVAL PROVIDE
ONE COPY OF APPROVED REPORT TO LANDLORD UPON COMPLETION OF CONSTRUCTION FOR THE PREMISE AS A REQUIREMENT
TO OPEN FOR BUSINESS.
1.04 JOB CONDITIONS
A. WORK WILL NOT PROCEED WITH TESTING, ADJUSTING AND BALANCING WORK UNTIL WORK HAS BEEN COMPLETED AND IS
OPERABLE. ENSURE THAT THERE IS NO LATENT RESIDUAL WORK STILL TO BE COMPLETED. INFORM ARCHITECT IN WRITING WHEN
PROJECT IS READY FOR ADJUSTING AND BALANCING.
B. REFER TO LANDLORD TENANT CRITERIA MANUAL FOR SYSTEM BALANCING REQUIRED AS PART OF TENANT WORK.
PART 2.00 - PRODUCTS
2.01 GENERAL
A. MECHANICAL SUB CONTRACTOR SHALL PROVIDE ALL MOTORS, SHEAVES, BELTS, LADDERS, ETC. AS REQUIRED FOR BALANCER TO
ACCOMPLISH WORK.
B. BALANCING SUB CONTRACTOR SHALL BE HIRED BY THE DIVISION 0 AT THE DIVISION 0 EXPENSE. BALANCING CONTRACTOR SHALL
BE AN INDEPENDENT CONTRACTOR, SEPARATE COMPANY FROM THE MECHANICAL SUB CONTRACTOR. COORDINATE WITH LANDLORD,
LANDLORD MAY REQUIRE SPECIFIC CONTRACTOR FOR BALANCING.
PART 3.00 - EXECUTION
3.01 GENERAL
A. EXAMINE INSTALLED WORK AND CONDITIONS UNDER WHICH TESTING IS TO BE DONE TO ENSURE THAT WORK HAS BEEN
COMPLETED, CLEANED AND IS OPERABLE. DO NOT PROCEED WITH TAB WORK UNTIL UNSATISFACTORY CONDITIONS HAVE BEEN
CORRECTED IN MANNER ACCEPTABLE TO TESTER.
B. TEST, ADJUST AND BALANCE AIR CONDITIONING SYSTEMS AND COMPONENTS, AS INDICATED, IN ACCORDANCE WITH PROCEDURES
OUTLINED IN APPUCABLE STANDARDS. REFER TO LANDLORD TENANT CRITERIA MANUAL FOR SYSTEM BALANCING REQUIRED AS
PART OF TENANT WORK.
C. PREPARE REPORT OF TEST RESULTS IN FORMAT RECOMMENDED BY APPLICABLE STANDARDS.
D. PATCH HOLES IN INSULATION, DUCTWORK AND HOUSING, WHICH HAVE BEEN CUT OR DRILLED IN MANNER RECOMMENDED BY THE
ORIGINAL INSTALLER.
E. MARK EQUIPMENT SETTINGS, INCLUDING DAMPER CONTROL POSITIONS, VALVE INDICATORS, FAN SPEED CONTROL LEVERS, AND
SIMILAR CONTROLS AND DEVICES, TO SHOW FINAL SETTINGS AT COMPLETION OF BALANCE WORK. PROVIDE MARKINGS WITH PAINT
OR OTHER SUITABLE PERMANENT IDENTIFICATION MATERIALS.
F. INITIAL BALANCING SHALL INCLUDE BALANCING ALL AIR QUANTITIES TO WITHIN 10% OF THOSE LISTED ON THE DRAWINGS.
G. BALANCER SHALL THEN CHECK ALL BUILDING TEMPERATURES AND READJUST AIR QUANTITIES TO EVEN OUT SPACE TEMPERATURES
TO WITHIN 1 DEG. F WITHIN SPACES.
H. TESTING, ADJUSTING AND BALANCING REPORT MUST BE COMPLETE AND TURNED OVER TO HOLD EVERYTHING PROJECT MANAGER 1
WEEK PRIOR TO STORE TURNOVER.
I. THE HVAC SUB CONTRACTOR SHALL BE PRESENT FOR AIR BALANCE TO VERIFY ACCESSIBILITY TO ALL DEVICES, VERIFY ALL
OPERATING SEQUENCES AND INSTALL NEW FILTERS IN ALL UNITS JUST PRIOR TO THE AIR BALANCE. THE COMPLETE AIR BALANCE
SHALL TAKE PLACE WITH OUTSIDE AIR DAMPERS IN MINIMUM POSITION, EXCEPT AS NOTED OTHERWISE. HVAC SUB CONTRACTOR
SHALL ALSO INSTALL A NEW SET OF FILTERS AFTER PROJECT IS COMPLETE.
J. BALANCE AIR TO WITHIN PLUS /MINUS 10% OF THAT INDICATED ON THE DRAWINGS. ANY REQUIRED CHANGES IN SHEAVES, BELTS,
PULLEYS OR THE ADDITION OF DAMPERS REQUIRED TO ACHIEVE SPECIFIED FLOW RATES SHALL BE PERFORMED BY THE HVAC
SUB CONTRACTOR WITH NO ADDITIONAL COST TO HOLD EVERYTHING.
K. THE BALANCING SUB CONTRACTOR SHALL PERFORM ALL APPLICABLE TESTING AND BALANCING FUNCTIONS REQUIRED FOR THE
SYSTEM DESIGNED ON THESE DRAWINGS. ALL SYSTEMS UNABLE TO BE COMPLETELY BALANCED AT THE TIME OF ORIGINAL ,
BALANCE MUST BE BALANCED IN FUTURE AT NO ADDITIONAL EXPENSE TO HOLD EVERYTHING. THE BALANCING CON) �T�OR SHALL
RECHECK ANY ITEMS THAT HOLD EVERYTHING DEEMS NECESSARY AT NO ADDITIONAL COST TO HOLD EVES. G C
END OF SECTION 15980
tivx
vtto
SECTION 15990 CONTROLS OtI ' aF
1. IN ADDITION TO THERMOSTATS AND REMOTE ROOM TEMPERATURE SENSORS,
2. SET RTU'S & AHU'S THERMOSTATS FOR 73 D.F. COOLING AND 70 D.E. HEATING INITIALLY.
END OF SECTION 15990
SECTION 15995 COMMISSIONING: C,1 �N"'
PART 1.00 GENERAL ‘. � `"✓
1. PROVIDE MECHANICAL SYSTEMS COMMISSIONING IN ACCORDANCE WITH LOCAL ENERGY CODE 6NHE°REQUIREMENTS OF
THISSPECIFICATION. ALL CONTROL SEQUENCES SHALL BE FUNCTIONALLY TESTED TO ENSURE THEY OPERATE IN
ACCORDANCE WITH THE
2. HVAC UNITS: OPERATE SYSTEM IN COOUNG MODE; RECORD OUTSIDE TEMPERATURE, MIXED AIR TEMPERATURE, SUPPLY AIR
TEMPERATURE. WHERE ECONOMIZERS ARE SPECIFIED, DEMONSTRATE PROPER OPERATION OF CHANGEOVER FROM
ECONOMIZER DAMPER OPERATION (FREE COOLING WITH OUTSIDE AIR) TO MECHANICAL COOLING (MINIMUM OUTSIDE AIR
WITH COMPRESSOR COOLING). VERIFY THAT COOLING COIL SENSIBLE CAPACITY MATCHES THE TEMPERATURE DROP ON THE
COOLING COIL VIA THE FORMULA COOLING CAPACITY (BTUH) = AIRFLOW (CFM) X (1.1) X DELTA T (MIXED AIR TEMP -
SUPPLY AIR TEMP DEGREES F). OPERATE UNITS IN HEATING MODE: RECORD OUTSIDE AIR TEMPERATURE, MIXED AIR
TEMPERATURE, SUPPLY AIR TEMPERATURE. VERIFY THAT HEATING COIL CAPACITY MATCHES THE TEMPERATURE RISE ON THE
HEATING COIL VIA THE FORMULA HEATING CAPACITY (BTUH) = AIRFLOW (CFM) X (1.1) X DELTA T (MIXED AIR TEMP -
SUPPLY AIR TEMP DEGREES F). VERIFY THE OPERATION OF ANY CONTROL VALVES WHERE PRESENT (CHILLED WATER OR
HEATING WATER VALVES). VERIFY THAT EACH UNIT OPERATES WITH THE CORRECT THERMOSTAT/ SENSOR. SET
THERMOSTATS FOR 70 F HEATING SETPOINT AND 72 F COOLING SETPOINT. UNIT FANS SHALL RUN CONTINUOUSLY DURING
OCCUPIED MODE AND CYCLE ON /OFF DURING UNOCCUPIED MODE. SETUP AND VERIFY HOURS ON OPERATION (TIME
SCHEDULE) FOR OCCUPIED /UNOCCUPIED MODE AND HOLIDAY /WEEKEND SCHEDULING.
3. VERIFY SMOKE DETECTOR SHUTDOWN OF ANY FAN UNITS SCHEDULED FOR SMOKE DETECTOR SHUTDOWN.
4. VERIFY PROPER OPERATION OF ANY OTHER HVAC EQUIPMENT THAT IS INTERLOCKED WITH OTHER EQUIPMENT.
5. PROVIDE CHECK OUT OF ALL PLUMBING SYSTEMS FOR PROPER OPERATION, INCLUDING HOT AND COLD WATER AT ALL
FAUCETS, WATER HEATERS SET FOR PROPER TEMPERATURE, OPERATION OF ALL VALVES, GREASE TRAPS, GAS VALVES,
MIXING VALVES. RECORD DATA ON ALL DEVICES CHECKED AND THE STATUS OF THEIR OPERATION.
END OF SECTION 15995
w '0%
RECEIVE
APR n1ZO
PERMIT CENTER
1 03 -29 -08 TENANT CHANGES
DRAWN BY:
KL
COPYRIGHT 0 2008 CARD & BURGESS, II
03 -19 -08 ISSUE FOR PERMIT
PROJECT NUMBER:
SCALE:
at &t
Carter::Burgess
Carter & Burgess, Inc.
4 Hutton Centre Drive, Suite 800
Santa Ana, California 92707
TEL: (714) 327 -1600
FAX: (714) 327 -1601
1EXPIRES 03/15/10
ISSUES /REVISIONS
NO. DATE DESCRIPTION
16425 Southcenter Parkway
TUKWILA, WA
DESIGNED BY:
KL
CHECKED BY:
MV
APPROVED BY:
MV
441805.011.039.0001
NONE
MECHANICAL AND
PLUMBING
SPECIFICATIONS
M -004
�
200 CFM
(R
SCALE: 1/4" = 1' -0"
8 "0 �Q -1 8 °0
2 T
RG
2
12 "0
v-CHA\ICAL FLOOR PLA\
24 "0
3/4 "COND
24 "0
1
CD
3
200 CFM
24 "0
(7)
350 CFM
CD
� 1
75 CFM
-..
100 CFM 4 100 CFM
'1
0
RG
8 "0 5
6 "0
( -66- 2
200 CFM
/ CD
1
75 CFIIA
12 "0 DROP
8
10"0
RTU -1
CD
3
200 CFM
CD
3
200 CFM
20 "0
18"0
8 "0
G
1 2 "0`:
0 5 (TYP)
16 "0
CD
3
250 CFM
10 "0
1 0 "0
1
(
350 CFM
16 "0
12 "0
14 "0
RG
5
12
CD
4
350 CFM
10 "0
1 0"0
CD
4
350 CFM'
HVAC PLAN NOTES:
CD INSTALL NEW EXHAUST FAN. REFER TO SCHEDULE ON SHEET M -600 & DETAIL
6/M -400 FOR MORE INFORMATION.
0 INSTALL NEW THERMOSTAT AS SHOWN AT 48" AFF. SEE DETAIL 1/M -400. GANG
BOX AND CONDUIT BY ELECTRICAL.
0 INSTALL NEW ROOF TOP UNIT ON EXISTING 10 TON ROOF CURB. NOTIFY ENGINEER
OF ANY DISCREPANCIES.
E4 INSTALL NEW DIFFUSER. BORDER TO MATCH CEILING TYPE. REFER TO DIFFUSER
SCHEDULE ON SHEET M -600.
® INSTALL NEW RETURN REGISTER. BORDER TO MATCH CEILING TYPE. REFER TO
DIFFUSER SCHEDULE ON SHEET M -600.
• RUN R -410 REFRIGERANT LINES FROM FAN COIL UNITS UNDER ROOF TO CONDENSING
UNIT ON ROOF. SEE MECHANICAL SCHEDULE ON SHEET M -600 FOR LINE SIZES.
:ii: ROUTE 3/4" CONDENSATE LINE ABOVE CEILING TO THE TAIL PIECE OF THE LAVATORY.
SEE DETAIL 8/M -400.
0 FAN COIL UNIT LOCATED IN CEILING SPACE.
• REFRIGERANT LINES UP THRU ROOF TO CONDENSING UNIT.
10 THERMOSTAT TO TURN ON EXHAUST FAN WHEN TEMPERATURE REACHES 90`F.
11 8 "0 OUTSIDE AIR DUCT UP THROUGH ROOF W/ ROOF CAP. PROVIDE INSECT SCREEN
AT TERMINATION.
12 PROVIDE 1 -1/4" GAS PIPE CONNECTION TO UNIT. CONNECT TO EXISTING MAIN GAS
PIPING ON ROOF. VERIFY THAT GAS SERVICE IS OPERATIONAL. NOTIFY ENGINEER OF
ANY DISCREPANCIES.
13 UPON ACTIVATION OF THE SMOKE DETECTOR, THE UNIT SHALL AUTOMATICALLY SHUT
DOWN AND AN ALARM SHALL BE SENT TO THE FIRE ALARM SYSTEM.
COO s
vst
I�
Pp
0 WO
at &t WIRELESS — 16425 SOUTHCENTER PARKWAY
TUKWILA, WA
TOTAL FLOOR AREA —4368 S.F.
OUTSIDE AIR PROVIDED —
RTU —1:
SALES FLOOR
FC -1:
MANAGER'S OFFICE
OPEN OFFICE
INVENTORY
RESTROOMS
OUTSIDE AIR SCHEDULE
MINIMUM OA
0.20 CFM /S.F.
20 CFM /PERSON
50 CFM /TOILET
CALCULATION
3712 S.F. x
0.20 CFM /S.F.= 743
20 CFM /PERSON x
3 PERSON= 60
50 CFM /TOILET x
2 TOILETS= 100
TOTAL:
750 CFM
75 CFM
100 CFM
925 CFM
TABLE IS BASED FROM 2006 WASHINGTON STATE VENTILATION AND INDOOR AIR QUALITY CODE.
RECEIVED
APR 01 an
PERMIT CENTE
COPYRIGHT 0
CARTER & BURGESS. INC.
at &t
Carter:Burgess
Carter & Burgess, Inc.
4 Hutton Centre Drive, Suite 800
Santa Ana, California 92707
TEL: (714) 327 -1600
FAX: (714) 327 -1601
1 EXPIRES 03/15/10
ISSUES /REVISIONS
1 03 -29 -08 TENANT CHANGES
03 -19 -08 ISSUE FOR PERMIT
NO. DATE DESCRIPTION
16425 Southcenter Parkway
TUKWILA, WA
DESIGNED BY:
KL
CHECKED BY:
MV
DRAWN Y:
KL
PROJECT NUMBER:
SCALE:
NORTH
APPROVED BY:
MV
441805.011.039.0001
1 /4"=1'-0"
MECHANICAL FLOOR
PLAN
1 M -200
(N) 4 "SAN
PLUMBING PLAN NOTES:
0 FIND THE SHORTEST DISTANCE TO ROUTE THE SANITARY PIPING TO THE NEAREST SANITARY
MAIN. SLOPE AT A 1% MINIMUM. NOTIFY ENGINEER OF ANY DISCREPENCIES.
10 CONNECT NEW VENT TO EXISTING VENT IN CEILING SPACE. FIELD TO VERIFY EXACT LOCATION.
0 INSTALL NEW INSTANTANEOUS WATER HEATER (IWH -1) BELOW LAVATORY FOR HOT WATER
CONNECTION. SEE DETAIL 5/M -400.
PROVIDE NEW SHUT -OFF VALVE W /ACCESS.
SAWCUT FLOOR AND PATCH AS REQUIRED.
CONNECT NEW DOMESTIC WATER TO EXISTING DOMESTIC WATER IN CEILING SPACE. FIELD TO
VERIFY EXACT LOCATION.
APIA 0 1 2008
PERMIT CENTER
COPYRIGHT 0 2008 CARTER & BURGESS, INC.
1 03 -29 -08 TENANT CHANGES
at &t
Carter:Burgess
Carter & Burgess, Inc.
4 Hutton Centre Drive, Suite 800
Santa Ana, California 92707
TEL: (714) 327 -1600
FAX: (714) 327-1601
1 EXPIRES 03/15/10
ISSUES /REVISIONS
- 03- 19-08 ISSUE FOR PERMIT
NO. DATE
DESCRIPTION
16425 Southcenter Parkway
TU KW I LA, WA
NORTH
DESIGNED BY:
KL
CHECKED BY:
KL
DRAWN BY:
KL
PROJECT NUMBER:
SCALE:
APPROVED BY:
MV
441805.011.039.0001
AS NOTED
PLUMBING
FLOOR PLANS
M -201
COPYRIGHT 0 2006 CARTER & HURGE
Carter:Burgess
Carter & Burgess, Inc.
4 Hutton Centre Drive, Suite 800
Santa Ana, California 92707
TEL: (714) 327 -1600
FAX: (714) 327 -1601
1 EXPIRES 03/15/10
ISSUES /REVISIONS
1 03 -29 -08 TENANT CHANGES
03 -19 -08 ISSUE FOR PERMIT
NO. DATE
DRAWN BY:
KL
PROJECT NUMBER:
SCALE:
INC
DESCRIPTION
MECHANICAL AND
PLUMBING
DETAILS
at &t
16425 Southcenter Parkway
TU KWI LA, WA
DESIGNED BY:
KL
CHECKED BY:
MV
APPROVED BY:
MV
441805.011.039.0001
NONE
M -400
ROOFCAP WITH INTEGRAL
BIRDSCREEN (PROVIDED BY
FAN MFR)
ROOF
SEE ARCH FOR FLASHING
TWO SHEET METAL ROOF JOIST, SEE
SELF TAPPING ARCHITECTURAL FOR
SCREWS ROOF TYPE
RA DUCT W/
1" THICK LINER
EXISTING ROOF CURB
PACKAGED
ROOF TOP
UNIT
SA DUCT W/
1" THICK LINER
ROOF
q
I -r
SHEET METAL
TWO
SELF TAPPING
SCREWS I
TWIST STRAP
-
FLEX
CONNECTION
SOLID -LINED CEILING
EXHAUST FAN CABINET SEE
MECHANICAL EQUIP.
SCHEDULE FOR SIZE.
BRACING (TYP)
_
L
U
,--..Q
/
1
'
�� ��� M
�
�/� %�� / ////ate, .
--
� RECTANGULAR
DUCTWORK
ROUND DUCTWORK -\,/`
`I �
NOTES
FLEXIBLE CONNECTION
FOR FUTURE CONNECTIONS
SPLITTER FITTING
WWWWWWWWWWWWWWW
- -_
IIIN
A SEISMIC
NOTES
PROVIDE CAP
UNIT AND DUCTWORK.
EACH BRANCH DUCT SIZE THROUGH
FITTING.
i
1. ALL DUCT & SUPPORTS PER IMC.
-V,--
6" RIGID METAL
REFER TO ARCHITECTURAL
FOR CEILING
DUCT
BACKDRAFT DAMPER
TYPE
EXHAUST GRILLE
(PROVIDED BY FAN MFR)
1. PROVIDE FLEXIBLE DUCT CONNECTION BETWEEN AIR CONDITIONING
2. WHERE SINGLE SUPPLY DUCTS SPLIT INTO TWO DUCTS MAINTAIN
AND PROVIDE SINGLE TRANSITION ON UPSTREAM SIDE OF SPLITTER
3. PROVIDE CAP ON DUCT AFTER PENTRATION THRU ROOF.
NOT USED
SCALE:
12
DUCT PENETRATION DETAIL
SCALE:
9
CEILING MOUNTED EXHAUST FAN DETAIL
SCALE:
6
DUCT HANGER DETAIL
SCALE:
3
N.T.S.
N.T.S.
NONE
N.T.S.
HOT OUTLET
COLD INLET
INSTANT FLOW
110V BY ELEC
METAL
FAN COIL
P -TRAP REQUIRED W/
SEPARATE DRAIN TO
EXISTING TRAP
CONDENSATE --- ----LJ 1
SECURE TO
STRUCTURE ABOVE
3" WIDE SHEET METAL
STRAP
4" -0" OC
45'
(2) 12 GA HANGER
SCREWS PER
TIGHTECTION. SEAL AIR
DRAIN PAN
_ _ •
COPPER
THREE WAY
STOP VALVE
—��
OVERFLOW PIPED
SEPARATELY TO
CONSPICUOUS LOCATION
SUPPORT TO DECK
ABOVE, TYP
I
CONNECT TO
STRUCTURE ABOVE
,
SUSPENDED CEILING
II GALV CLAMP
CONDENSATE DRAIN
FROM ABOVE
3/8"
VIII
I l&
TUBING
ROUND METAL
HEATER - 1/2
-��
COLD
ANGLE
�-
DUCT, TYP
(1 -1/2" MAX SIZE)
1
ACOUSTICAL FLEX DUCT
CEILING DIFFUSER /RETURN GRILLE 5'-O" MAXIMUM LENGTH
SUSPENDED CEILING
4
J -BOX
EXISTING FIXTURE
I
1
ATTACH FLEX TO DUCT AND CEILING - - - - --
DIFFUSER USING MIN OF 3 SHEET
METAL SCREWS. SEAL AIR
w GASKET
1 .111
-�
lar
if*
AIR GAP FITTING
TIGHT
------. - EVIEVA tb \
CgD CM/WI-1°k
AppROVED \
R 9 70 ■
, : "" ^'
---------- Of 11 "...t
IF
EXISTING TRAP
EXISTING P- TRAP
NOT USED
SCALE:
SCALE:
INSTANTANEOUS WATER HEATER
PIPING DETAIL
SCALE
CEILING DIFFUSER/RETURN GRILLE L
CONNECTION DETAIL
2
NTS
N.T.S.
NONE
N.T.S.
BRASS CLEANOUT PLUG
WALL CONSTRUCTION
48"
30"
24"
MAIN SUPPLY DUCT (OR
MAIN EXHAUST RETURN DUCT OR
SUB -MAIN)
_
SUB -MAIN)
1/4 W, 4" MIN
W, 4"
1/4
MIN.
PROVIDE VOLUME
DAMPER
TAPPED CLEANOUT TEE
JR SMITH No. 4530,
ZURN No. Z -1446 OR
EQUAL
PROVIDE VOLUME
BRANCH DUCT—
DAMPER
—
BRANCH DUCT -
W
THERMOSTAT,
SUPPLY AIR DUCT EXHAUST / RETURN AIR DUCT
VOLUME DAMPER
AIR FLOW
DUCT MAIN
STAINLESS STEEL CLEANOUT
COVER
,
oo
SWITCH, OUTLET,
TOP OF THERMOSTAT,
CONTROL
SWITCH, OUTLET,
CONTROL
¢
xt
_�
_
.�
ro
�
i1�l ll�
erigirmin
_
FINISHED FLOOR
RECTANGULAR TO ROUND
�'
/
SIDE DUCT TAKE -OFF
1 8 GAUGE VOLUME DAMPER WITH
BRANCH
.0.„
CONICAL TAP
MAIN
LOCKING QUADRANT SET (TYP
FOR ALL SUPPLY / RETURN/
EXHAUST AIR BRANCH RUNOUTS)
qECEIVED
APR 01 MI
PERM T CENTER
NOT USED
SCALE:
10
WALL CLEAN OUT DETAIL
SCALE:
7
BRANCH TAKE -OFF DETAIL
SCALE:
4
MOUNTING HEIGHT OVER OBSTRUCTION
SCALE:
1
N.T.S.
NONE
N.T.S.
N.T.S
COPYRIGHT 0 2006 CARTER & HURGE
Carter:Burgess
Carter & Burgess, Inc.
4 Hutton Centre Drive, Suite 800
Santa Ana, California 92707
TEL: (714) 327 -1600
FAX: (714) 327 -1601
1 EXPIRES 03/15/10
ISSUES /REVISIONS
1 03 -29 -08 TENANT CHANGES
03 -19 -08 ISSUE FOR PERMIT
NO. DATE
DRAWN BY:
KL
PROJECT NUMBER:
SCALE:
INC
DESCRIPTION
MECHANICAL AND
PLUMBING
DETAILS
at &t
16425 Southcenter Parkway
TU KWI LA, WA
DESIGNED BY:
KL
CHECKED BY:
MV
APPROVED BY:
MV
441805.011.039.0001
NONE
M -400
DIFFUSER SCHEDULE
MARK NO.
MANUFACTURER
& MODEL NO.
TYPE
CFM
RANGE
MODULE
SIZE
(IN)
NECK
SIZE
(IN)
OPPOSE
BLADE
DAMPER
MAX
NC
MAX
PD
MATERIAL
MARK NO.
CD
TITUS
PCS
ADJUSTABLE BLADE
PERFORATED FACE
0 -100
24X24
6
NO
25
0.1
STEEL
FAN
RPM
1
TOTAL
CAPACITY
(MBH)
TITUS
PCS
ADJUSTABLE BLADE
PERFORATED FACE
101 -200
24X24
8
NO
25
0.1
STEEL
LAT
(,�)
( CD
2
CD
TITUS
PCS
ADJUSTABLE BLADE
PERFORATED FACE
201 ®325
24X24
10
NO
25
0.1
STEEL
TYPE
3
WB
(')
TITUS
PCS
ADJUSTABLE BLADE
PERFORMED FACE
326 -400
24X24
12
NO
25
0.1
STEEL
750
CD
4
900
TITUS
PCS
ADJUSTABLE BLADE
PERFORATED FACE
401 -550
24X24
14
NO
25
0.1
STEEL
120/180
( CD
5
K7)
PCS TITUS
ADJUSTABLE BLADE PERFORATED FACE
551 -700
24X24
16
NO
25
0.1
STEEL
49.4
RG
TITUS
PAR
PERFORATED FACE
0 -160
24X24
6
NO
25
0.1
STEEL
UNIT SHALL COMPLETE
PROVIDE SMOKE DETECTOR
SMOKE DETECTOR
FACTORY INSTALLED
(
RG
TITUS
PAR
PERFORATED FACE
161 -280
24X24
8
NO
25
0.1
STEEL
2
RG
TITUS
PAR
PERFORATED FACE
281 -380
24X24
W
NO
25
0.1
STEEL
( 3
(7)
PAR
PERFORATED FACE
381 -530
24X24
12
NO
25
0.1
STEEL
RG
TITUS
PAR
PERFORATED FACE
531 -640
24X24
14
NO
25
0.1
STEEL
RG
TITUS
PAR
PERFORATED FACE
641 -720
24X24
16
NO
25
0.1
STEEL
6
RG
TITUS
PAR
PERFORATED FACE
721 -1500
24X24
22X22
NO
25
0.1
STEEL
( 7
NOTES:
PROVIDE ROUND TO SQUARE ADAPTOR AS NEEDED. s
1'
PACKAGED ROOF TOP UNIT SCHEDULE
MARK NO.
MANUFACTURER
MODEL NO.
LOCATION
SERVICE
NOMINAL
CAPACITY
(TONS)
REFRIG
TYPE
AMBIENT
DRY BULB
('F)
MIN
OSA
CFM
SUPPLY FAN
COOLING
HEATING
COMPRESSOR
CONDENSER FAN
UNIT
ELECTRICAL
FILTERS
UNIT
DIMENSIONS
L x W x H
(IN)
OPER
WEIGHT
(LBS)
REMARKS
CFM
ESP
(IN WG)
FAN
RPM
BHP
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EER
EAT
LAT
MAX FACE
VELOCITY
(FPM)
INPUT
CAPACITY
(MBH)
MAX. OUTPUT
CAPACITY
(MBH)
AFUE
(/)
EAT
(�F)
LAT
(,�)
QUANTITY
RLA
LRA
QUANTITY
HP
(EA)
MOTOR
RPM
FLA
(EA)
MCA
MOCP
VOLTS /PH /HZ
%
EFF
TYPE
CO 'al"
WB
(')
DB
('F)
WB
(T)
2"
CARRIER
48TMD012
ROOF
SALES
10
R -22
80
750
4000
0.8
900
2.30
119.3
113.5
10.1
80.0
64.0
60.6
56.0
500
120/180
144
80.0
41.0
73.9
MODEL # 95 NEO ANGLE DROP FRONT TERRAllO MOP RECEPTOR.
16.0
125.0
2
1/4
1100
1.4
49.4
60
208/3/60
30%
PLEATED
88 X 58 X 50
1110
00001
RTU
1
NOTES:::
UNIT SHALL COMPLETE
PROVIDE SMOKE DETECTOR
SMOKE DETECTOR
FACTORY INSTALLED
WITH INTERNAL VIBRATION ISOLATORS AND ECONOMIZER. 0 PROVIDE BURGLAR BARS AT SUPPLY AND RETURN AIR DUCTS.
IN RETURN DUCT PER 2006 INTERNATIONAL MECHANICAL CODE. 0 PROVIDE MICRO METL #4682 -0202 POWER EXHAUST. INSTALL PER MANUFACTURER'S
SHALL BE INSTALLED PER MANUFACTURER'S RECOMMENDATIONS. RECOMMENDATIONS.
PACKAGE UNIT WITH ONE POINT POWER CONNECTION.
0
0
PLU'/BING FIXTURE SCHEDULE
ITEM
DESCRIPTION
MANUFACTURER
W
V
CW
HW
QTY.
W&V
CW
&MW
TOTAL
REMARKS AND SPECIFICATIONS
F.U.
TOTAL
F.U.
Ali
INSTANTANEOUS
WATER HEATER
CHRONOMITE
LABORATORIES, INC,
-
-
1/2"
1/2"
3
-
-
-
-
#M -20L, TANKLESS ELECTRIC WATER HEATER, FLOW ACTIVATED, STAINLESS STEEL
HEATING COILS, ONE -4160 WATT, 208/1/60 VOLT, SINGLE PHASE, 20 AMP, 1/2"
WATER CONNECTION, 6 "HX9 "WX2 -1/2 ", 80T -105T TEMPERATURE RANCE.
®
W
EF
TWIN CITY
T100
WATER CLOSET
KOHLER
4"
2"
3/4"
1
2
4
8
2.5
5
#K -3465, 16 -1/2" HIGH ELONGATED RIM VITREOUS CHINA TWO -PIECE TOILET,
COMPLETE WITH INGENIUM FLUSHING SYSTEM, BOWL: K -4278, TANK: K -4609,
2 -1/8" PASSAGEWAY, ULTRA -LOW CONSUMPTION TOILET, FLUSHES ON 1.6 GAL. OF
WATER.
®
Mr
TWIN CITY
T100
ELECTRICAL
ROOM
LAVATORY
KOHLER
2"
1-1/2"
1/2"
1/2"
2
1
2
1
2
#K -2005, VITREOUS CHINA WALL -HUNG LAVATORY WITH HANGER, DRILLED FOR
CONCEALED ARM CARRIER WITH FAUCET HOLES ON 4 CENTERS, FRONT OVERFLOW;
FAUCET: #501- WFHDF, SINGLE HANDLE LAVATORY DECK FAUCET; METAL POP -UP
DRAIN AND LIFT HOLE IN POLISHED CHROME. 1-1/4" TAILPIECE. PROVIDE 3/8" WALL
SUPPLIES WITH STOP AND 1 -1/4" OFFSET DRAIN, METAL GRID STRAINER. (FURNISH
AND INSTALL " BROCAR" #C500R -B TRAP WRAP FOR PF -2H) BROCAR TEL: (800)
827 -1207
INTERLOCK WITH LIGHT SWITCH. Q3 FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR.
PROVIDE BACKDRAFT DAMPER. 0 INTERLOCK WITH TEMPERATURE SENSOR.
0
®
MOP SINK
FLORESTONE
3"
2"
3/4"
-
1
4
4
2.5
2.5
MODEL # 95 NEO ANGLE DROP FRONT TERRAllO MOP RECEPTOR.
w
DRINKING
FOUNTAIN
HALSEY TAYLOR
HAC8FSBL-Q ADA
2"
1-1/2"
1/2 "
-
1
0.5
0.5
0.5
0.5
BI -LEVEL WATER COOLER: SURFACE MOUNT ELECTRIC WATER COOLER, 8.0 GPH AT
CO DEC F TE L 1 2 0 /1/ 4.0REQUIRE4000TWATTS ENTIRE INSTALLATION SHALL
DF
1
FIXTURE UNIT (F.U.) TOTALS
14.5
10.0
ALL FIXTURES TO BE SUPPLIED & INSTALLED BY PLUMBING CONTRACTOR.
EXHAUST
FAN SCHEDULE i
MARK NO.
MANUFACTURER
&MODEL NO.
SERVICE
LOCATION
TYPE
CFM
ESP
(IN WG)
QTY'
DRIVE
MOTOR
OPER
WEIGHT
(LBS)
REMARKS
WATTS
VOLTS /PH /HZ
Ali
TWIN CITY
T100
RESTROOM
CEILING
BATHROOM
ROOM
100
0.1
1
DIRECT
87
120/1/60
25
000
W
2
EF
TWIN CITY
T100
RESTROOM
CEILING
BATHROOM
ROOM
100
0.1
1
DIRECT
87
120/1/60
25
r.
( 2
PROVIDE 3/4" CONDENSATE DRAIN CONNECTION TO UNIT.
PROVIDE FACTORY INSTALLED 6.0KW SUPPLEMENTAL ELECTRIC HEATER
MODEL# KFCEH0501N05.
Lk
TWIN CITY
T100
ELECTRICAL
ROOM
CEILING
BATHROOM
ROOM
100
0.1
1
DIRECT
87
120/1/60
25
000
®
NOTES:
INTERLOCK WITH LIGHT SWITCH. Q3 FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR, WIRED BY ELECTRICAL CONTRACTOR.
PROVIDE BACKDRAFT DAMPER. 0 INTERLOCK WITH TEMPERATURE SENSOR.
0
PIPI \G MATERIAL LEGEND
DOMESTIC WATER
SS, VENT AND STORM PIPING
UNDERGROUND PIPING
UNDERGROUND PIPING
2" AND SMALLER -SOFT DRAWN COPPER, TYPE K, NO JOINTS BELOW FLOOR
2-1/2" AND LARGER -HARD DRAWN COPPER, TYPE K
SERVICE WEIGHT CAST IRON PIPING, HUB AND SPIGOT TYPE
ABOVE GROUND PIPING
ABOVE GROUND PIPING
1/2" AND LARGER - HARD DRAWN COPPER, TYPE L
1 .-1 /2" AND SMALLER - HARD DWV COPPER DRAINAGE TUBE
2" AND LARGER - SERVICE WEIGHT CAST IRON PIPING HUB AND SPIGOT TYPE,
HUBLESS SERVICE WEIGHT CAST IRON, PVC PIPE, SCHEDULE 40,
SOCKET TYPE DWV PATTERN (WHERE PERMITTED BY LOCAL
JURISDICTION).
AIR- COOLED CONDENSING UNIT SCHEDULE
MARK NO.
MANUFACTURER
& MODEL NO.
LOCATION
AMBIENT
DRY BULB
('F)
NOMINAL
CAPACITY
(TON)
COMPRESSOR
CONDENSER FAN
UNIT
ELECTRICAL
REFRIG. LINE SIZE
REFRIG.
TYPE
UNIT
DIMENSIONS
L x W x H
(IN)
OPER
WEIGHT
(LBS)
REMARKS
QUANTITY
RLA
(
LRA
(EA)
QUANTITY
HP
(EA)
MOTOR
RPM
MCA
(AMP)
MOCP
(AMP)
VOLTS /PH /HZ
GAS
LINE
LIQUID
LINE
CEILING
CARRIER
25HCA324A
ROOF
80
2
1
12.8
58.3
1
1/10
800
16.7
25
208/1/60
5/8
3/8
R -410
31X31X29
183
PROVIDE 3/4" CONDENSATE DRAIN CONNECTION TO UNIT.
PROVIDE FACTORY INSTALLED 6.0KW SUPPLEMENTAL ELECTRIC HEATER
MODEL# KFCEH0501N05.
AL
w
NOTES:
HEAT PUMP UNIT.
FAN COIL UNIT SCHEDULE
MARK NO.
MANUFACTURER
& MODEL N0.
LOCATION
MIN
OSA
CFM
ESP
(IN WC)
MOTOR
HP
COOLING COIL
ELECTRICAL
UNIT
UNIT
DIMENSIONS
L x W x H
(IN)
OPER
WEIGHT
(LBS)
REMARKS
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
EAT
LAT
VOLTS /PH /HZ
MCA
(AMP)
MOCP
(AMP)
DB
('F)
WB
('F)
DB
('F)
WB
'F)
2
CARRIER
FX4CNF024
CEILING
175
0.3
1/3
24
24
80
64
60
55
208/1/60
26.1
30
48X18X22
117
00
AIL
NOTES: c
PROVIDE 3/4" CONDENSATE DRAIN CONNECTION TO UNIT.
PROVIDE FACTORY INSTALLED 6.0KW SUPPLEMENTAL ELECTRIC HEATER
MODEL# KFCEH0501N05.
PIPE SIZE
GPM
FT /SEC
MAX FU
1/2"
2.3
2.9
3
3/4"
5.5
3.8
7
1"
12
4.5
16
1-1/4"
20
5.2
30
1-1/2"
30
6.0
54
2
70
7.5
225
NOTES:
MAX VELOCITY IN WATER PIPE 8 FT /SEC. FOR COLD WATER.
MAX VELOCITY IN WATER PIPE 5 FT /SEC. FOR HOT WATER.
PLUMBING CONTRACTOR TO VERIFY AND COORDINATE EXACT STREET PRESSURE AND NOTIFY ENGINEER OF ANY DISCREPANCIES.
PLUMBING CONTRACTOR TO PROVIDE A PRESSURE REDUCING VALVE (PRV) ON CUSTOMER SIDE OF WATER METER IF THE STREET
PRESSURE EXCEEDS 80 PSI, PRV TO BE SET AT 60 PSI.
THE FOLLOWING CHART IS USED TO SIZE THE TYPE L COPPER, COLD WATER PIPING IN ACCORDANCE WITH CPC APPENDIX A AT
4.0 P.S.I. / 100 FT. LOSS
T6---
9,73
ECE VE
APR ` 01 ZOO
pERMrr CENTER
DRAWN BY:
KL
COPYRIGHT 0 2000 CARTER & BURGESS. INC.
PROJECT NUMBER:
SCALE:
at &t
Carter:Burgess
Carter & Burgess, Inc.
4 Hutton Centre Drive, Suite 800
Santa Ana, California 92707
TEL: (714) 327- 1600
FAX: (714) 327-1601
1 EXPIRES 03/15/10
ISSUES /REVISIONS
1 03 -2908 TENANT CHANGES
03 -19 -08 ISSUE FOR PERMIT
NO. DATE DESCRIPTION
16425 Southcenter Parkway
TUKWILA, WA
DESIGNED BY:
KL
CHECKED BY:
MV
APPROVED BY:
MV
441805.011.039.0001
NONE
MECHANICAL AND
PLUMBING SCHEDULES
M -600