HomeMy WebLinkAboutPermit D06-200 - Upland Distribution - Building 425 - Seismic RetrofitUPLAND DISTRIBUTION
BUILDING 425
305 ANDOVER PK W
D06 -200
City of Tukwila
Department of Community Development / 6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
Parcel No.: 8836500050
Address: 305 UPLAND DR TUKW
Suite No:
Tenant:
Name: UPLAND DISTRIBUTION - BLDG 425
Address: 305 ANDOVER PK W, TUKWILA WA
Owner:
Name: COOMBS DON W TRUSTEE
Address' 1325 FOURTH AVE SUITE 1940, SEATTLE WA
Contact Person:
Name: HEATHER LEAMAN
Address: 603 STEWART ST #707, SEATTLE WA
Contractor:
Name: SAUNDERS CONSTRUCTION INC Phone: 949 646 -0034
Address' 1760 MONROVIA AV UNIT A -1, COSTA MESA CA
Contractor License No: SAUNDCI953ND Expiration Date:08 /04/2007
DESCRIPTION OF WORK:
VOLUNTARY SEISMIC RETROFIT OF WALL ANCHORAGE AND CONTINUITY TIES.
Value of Construction: $34,202.00 Fees Collected: $1,011.30
Type of Fire Protection: SPRINKLERS Uniform Building Code Edition:
Type of Construction: IIB Occupancy per UBC: 0011
Public Works Activities:
Channelization / Striping: N
Curb Cut / Access / Sidewalk / CSS: N
DEVELOPMENT PERMIT
doe: Devperm
Water Main Extension: N Private: Public:
Water Meter: N
** Continued Next Page **
Permit Number: D06 -200
Issue Date' 07/06/2006
Permit Expires On: 01/02/2007
Phone:
Phone: 206 624 -3210
Fire Loop Hydrant: N Number: 0 Size (Inches): 0
Flood Control Zone: N
Hauling: N Start Time: End Time:
Land Altering: N Volumes: Cut 0 c.y. Fill 0 c.y.
Landscape Irrigation: N
Moving Oversize Load: N Start Time: End Time:
Sanitary Side Sewer: N
Sewer Main Extension: N Private: Public:
Storm Drainage: N
Street Use: N Profit: N Non - Profit: N
006 -200 Printed: 07-06-2006
City of Tukwila
Department of Community Development / 6300 Southcenter BL, Suite 100 / Tukwila, WA 98188 / (206) 431 -3670
Permit Center Authorized Signature:
Signature:
Print Name:
doc: Devperm
AlP
Date: d.Plag
I hereby certify that 1 have read and a i ed t 's permit and know the same to be true and correct. All provisions of law and
ordinances governing this work will b c mp ith, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws
regulating construction or the performance of work. I am authorized to sign and obtain this development permit.
J ANN A % IN MCI PROP. MGR.
Date: 7-6-OG
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is
suspended or abandoned for a period of 180 days from the fast inspection.
D06 -200 Printed: 07-06-2006
City aidTukwila
Parcel No.: 8836500050
Address: 305 UPLAND DR TUKW
Suite No:
Tenant: UPLAND DISTRIBUTION • BLDG 425
1: ***BUILDING DEPARTMENT CONDITIONS***
14: ***FIRE DEPARTMENT CONDITIONS "'
doc: Conditions
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: ci.tukwila.wa.us
PERMIT CONDITIONS
Steven M. Mullet, Mayor
Steve Lancaster, Director
Permit Number: D06 -200
Status: ISSUED
Applied Date: 05/31/2006
Issue Date: 07/06/2006
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431- 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: The special inspections and verifications for concrete construction shall be required.
6: The special inspections for steel elements of buildings and structures shall be required. All welding shall be done by
a Washington Association of Building Official Certified welder.
7: Installation of high- strength bolts shall be periodically inspected in accordance with AISC specifications.
8: The special inspection of bolts to be installed in concrete prior to and during placement of concrete.
9: When special inspection is required, either the owner or the registered design professional in responsible charge,
shall employ a special inspection agency and notify the Building Official of the appointment prior to the first
building inspection. The special inspector shall furnish inspection reports to the Building Official in a timely manner.
10: A final report documenting required special inspections and correction of any discrepancies noted in the inspections
shall be submitted to the Building Official. The final inspection report shall be prepared by the approved special
inspection agency and shall be submitted to the Building Official prior to and as a condition of final inspection
approval.
11: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
12: All electrical work shall be inspected and approved under a separate permit issued by the Washington State Department
of Labor and Industries (206/248- 6630).
13: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
15: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
D06 -200 Printed: 07 -06 -2006
following concerns:
doc: Conditions
City okr'Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206431 -3670
Fax: 206 -431 -3665
Web site: ci.tukwila.wa.us
**continued on next page**
Steven M. Mullet, Mayor
Steve Lancaster, Director
16: Maintain existing sprinkler system piping, bracing and coverage. New brackets, beams, etc. must not obstruct sprinkler
head discharge in any way.
17: All new sprinkler systems and all modifications to existing sprinkler systems shall have fire department review and
approval of drawings prior to installation or modification. New sprinkler systems and all modifications to sprinkler
systems involving more than 50 heads shall have the written approval of the W.S.R.B., Factory Mutual, Industrial Risk
Insurers Kemper or any other representative designated and /or recognized by the City of Tukwila, prior to submittal to
the Tukwila Fire Prevention Bureau. No sprinkler work shall commence without approved drawings. (City Ordinance #2050)
18: Any overlooked hazardous condition and /or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
19: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
006 -200 Printed: 07 -06 -2006
City or'Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: ct.tukwtla.wa.us
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local laws
regulating construction or the performance of work.
Signature:
a,m 0. icc-flu,„_)
Print Name: .o ANN k 6A IMF , MOE PREP MGR
doc: Conditions
Steven M. Mullet, Mayor
Steve Lancaster, Director
Date: 7 -G-ao
D06 -200 Printed: 07-06 -2006
CITY OF TUKW/L
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
h t tp:ll www. ci. tkwila. wa. us
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print**
Site Address:?( &f x)y� 11C
Tenant Name:
Building Permit No. ` f -1
Mechanical Permit No
Plumbing/Gas Permit No
Public - Works:Permit No:�
;ojebt No.
or of use only)
King Co Assessor's Tax No.: 3 2- 41 I n2.
Floor: —
Suite Number:
VS .. is. " ...y►G.:atalf New Tenant: ❑ Yes KNo
Property Owners Name: AiM2 ¶ROP�1" f Car- PLR-#c1fd) 4
Mailing Address: 212:1 / Al to 4f i t WI (O "Thar-WI, w A- q bz`lis
City State Zip
i t:
Name: ft-EaTh q--
Mailing Address:
E-Mail Address:: [ejrk-.\l - c a✓t
GENERAL "CONTRACTOR INFORMATION
(Contractorinformation for Mechanical (pg 4 )for Plumbing and Gas Piping (pg 5)
Company Name:
Mailing Address:
Contact Person:
E-Mail Address:
Contractor Registration Number:
Day Telephone: '" I1- *
City State
Fax Number: qap IQ / ,,- ta \ 2 /n s
City
Day Telephone:
Fax Number:
Expiration Date:
State
Zip
ARCHITECT OF RECORD All plans must be wet stamped by Architect of Record
Company Name:
Mailing Address:
Contact Person:
E -Mail Address:
ENGINEER OF RECORD -A11 plans must be we stamped by Engineer of Record
Company Name:
Mailing Address:
Contact Person
Je
E-Mail Address:
QMpplic.tio sWonni- Appaations On tine 3- 2006 -Permit Applicntion.doc
Revised: 4-2006
bb
City
Day Telephone:
Fax Number:
State
Zip
tat VS
ity State Zip
Day Telephone: i at: /
Fax Number: t� l Pita en YIP
Page 1 of 6
( `BUILDING PERMIT' INFORM 1ON - 206- 431 -3670
Valuation of Project (contractor's bid price): $ o'202- cO Existing Building Valuation: $
Scope of Work (please provide detailed information): vd44 tm yr P '4i &'t' fic
Will there be new rack storage? ❑ ..Yes VNo (If yes, a separate permit and plan submittal will be required)
Provide All Building Areas in Square Footage Below
1 Floor
Z°0- Floor.
3"° Floor
asement
' Accessory. Structure* _
Attached Garage
Detached Garage _
Attached Carport
Detached Carport - '. ;
Covered Deck
Uncovered Deck
isting
Interior
Remodel
Addition to
Existing
Structure
New
Type of
Construction
per IBC
i t -�
Type of
Occupancy per
IBC
4.
PLANNING DIVISION:
Single - family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
'For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area for accessory dwelling:
'Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ ....Yes ❑ ..No If "yes ", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
l Sprinklerss ❑..Automatic Fire Alarm ❑..None ❑ -Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? 0.. Yes .No
If 'yes'; attach list of materials and storage locations on a separate 8-1/2 x 11 paper indicating quantities and Material Safety Data Sheets.
SEPTIC SYSTEM:
❑ On -site Septic System - For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
Q AppIicatioa cans- Applinlions an IiiwU -2006 - Pernil Appacation.doc
Revised: 0-2006
bh
Page 2 of 6
( PUBLIC WORKS PERMIT IN SRMATION - 206 -433 -0179
Scope of Work (please provide detailed information):
Water District
❑...Tukwila ❑...Water District #125
❑ ...Water Availability Provided
Sewer District
b ...Tukwila
❑ ...Sewer Use Certificate
❑ ...Total Cut
❑ ...Total Fill
Please refer to Public Works Bulletin #1 for fees and estimate sheet.
❑ ...Permanent Water Meter Size...
❑ ...Temporary Water Meter Size
❑ ...Water Only Meter Size
❑ ...Sewer Main Extension Public
❑ ...Water Main Extension Public
❑... ValVue
0... Sewer Availability Provided
ubmitted with Application (mark boxes which applv):
.. .Civil Plans (Maximum Paper Size — 22" x 34")
❑ ...Technical information Report (Storm Drainage)
❑ ...Bond ❑ .. Insurance ❑ .. Easement(s)
reposed Activities (mark boxes that apply);
0 ...Right-of-way Use - Nonprofit for less than 72 hours
❑ ...Right-of-way Use - No Disturbance
❑ ...Construction/Excavation/Fill - Right-of-way
Non Right -of -way
cubic yards
cubic yards
❑ ...Sanitary Side Sewer ❑ .
❑ ...Cap or Remove Utilities ❑ .
❑ ...Frontage Improvements ❑ .
❑ ...Traffic Control ❑ .
❑ ...Backflow Prevention - Fire Protection
Irrigation
Domestic Water
PP
QMIptica iooN'ans-Applicatiau Oo Line V- 2006 -Permit Application.doc
Revised: 4-2006
b0
Call before you Dig: 1- 800 -424 -5555
. Abandon Septic Tank
. Curb Cut
. Pavement Cut
. Looped Fire Line
Private
Private
❑ .. Highline
❑ .. Renton ❑ .. Seattle
❑ .. Approved Septic Plans Provided
❑ .. Geotechnical Report
❑ .. Maintenance Agreement(s)
❑ .. Renton
❑ .. Right -of -way Use - Profit for less than 72 hours
❑ .. Right-of-way Use — Potential Disturbance
❑ .. Work in Flood Zone
❑ .. Storm Drainage
❑ .. Grease Interceptor
❑ .. Channelization
❑ .. Trench Excavation
❑ .. Utility Undergrounding
❑ ...Deduct Water Meter Size
❑...Traffic Impact Analysis
❑ ...Hold Harmless — (SAO)
❑ ...Hold Harmless — (ROW)
FINANCE INFORMATION
Fire Line Size at Property Line Number of Public Fire Hydrant(s)
❑ ...Water ❑...Sewer ...Sewage Treatment
Monthly Service Billing to:
Name:
Day Telephone:
Mailing Address:
City State Zip
Water Meter Refund/Billing;
Name: Day Telephone:
Mailing Address:
City
.State
Zip
Page 3 of 6
PERMIT APPLICATION NO1Nb - Applicable to all permits in this application
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING
Signature:
Print Name:
Building and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 international Building Code (current edition).
Plumbing Permit
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing code (current edition).
I Date Application Accepted:
Day Telephone: 20(e , l 272-to
Mailing Address: Ce0 htq .0A et. *1(n �� (/7
City State Zip
Date Application Expires:
vs I ltfce
QMppac tion.WFonnsAppliwYoes On Line\- 2006 - Permit Applicaaoa.6ae
Revised: 42006
bh
Date:
Staff' Initials:
•
I
Page 6 of 6
RECEIPT NO: R06 -00978
Initials: JEM
Payment Date: 07/06/2006
User ID: 1165 Total Payment: 2,767.88
Payee: AMB ALLIANCE FUND III, LLC
SET ID: 0706 SET NAME: SEISMIC RETROFITS
SET TRANSACTIONS:
Set Member Amount
D06 -200
D06 -201
D06 -202
D06 -203
TOTAL:
TRANSACTION LIST:
Type Method Description
Payment Check 0200136
ACCOUNT ITEM LIST:
Description
614.68
602.16
739.88
811.16
2,767.88
BUILDING - NONRES
STATE BUILDING SURCHARGE
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
SET RECEIPT
TOTAL:
Amount
2,767.88
2,767.88
Account Code Current Pmts
000/322.100 2,749.88
000/386.904 18.00
TOTAL: 2,767.88
71.35 07/07 7710 TOTAL 2767.88
Steven M. Mullet, Mayor
Steve Lancaster, Director
RECEIPT NO: R06 -00769
Initials: JEM
Payee: R. 1 HALLISSEY CO, INC.
SET TRANSACTIONS:
Set Member Amount
D06 -200 396.62
006 -201 388.48
D06 -202 478.00
D06 -203 524.33
TOTAL: 1,787.43
ACCOUNT ITEM LIST:
Description
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206- 431 -3670
Fax: 206 - 431 -3665
SET RECEIPT
Copy Reprinted on 05 -31 -2006 at 15:20:46 05/31/2006
Payment Date: 05/31/2006
User ID: 1165 Total Payment:1,787.43
SET ID: 053106 SET NAME: SEISMIC RETROFIT
TRANSACTION LIST:
Type Method Description Amount
Payment Check 7129 1,787.43
TOTAL: 1,787.43
PLAN CHECK - NONRES 000/345.830
TOTAL:
Account Code Current Pmts
1,787.43
1,787.43
5975 06/01 9716 TOTAL 1787.43
Steven M. Mullet, Mayor
Steve Lancaster, Director
Project: 9 r
V : 1_4 1/4.1b 'I`nl('
Type of Inspection:
r/ Al
U
/
Address:
rj( AKA Net Pu u,
Date Called:
Special Instructions:
Date Want d:
/ 2 l / kU to
a.m.
Requester:
Phone No:
3
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
Doer zoo
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431-
'1 Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
�'a r 1 4 - C &vv (f 4 e (P I rJ a
Date:
/z /i z d6
8.00 REINSPECTIO FEE REQUI5EO. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., ite 100. Call to sechedule reinspection.
Receipt No.:
'Date:
Project:
2/ , )LAn/0 23 /6
Type of Inspection: ,
A b
V
Address: „,
3 L /PGANi .v
Called:
_
Special Instructions: -
Date Wanted:
/ 0 — 1 - 5 - - 0
(a.m..
P.m.
Requester:
Phone No:
&o6 - z5/ - v 1 3
3
Z-
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
16
PERMIT NO.
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)4 113670
Approved per applicable codes.
COMMENTS:
m i/4 -t, * s r' el/ re Ad, ks UM)
Si/ f
ector:
$58.00 REINSPECTION F1cE REQUIRED. r to inspection, fee must be
paid at 6300 Southcenter ' glvd., Suite 100. Call to sechedule reinspection.
Receipt No.:
CA” / <.t 1 / - z 5 - dy
Date:
❑ Corrections required prior to approval.
ProU
L �� am/
Type of InsPe
1P
n:
- t c9
.
•
Address: � �p t �
a j fa+�L? ( Y c.
Date Called:
LA —I
Special Instructions:
Date Wanted:
c��
—1 I --d e
a.m�
P.m.
Requester:
Phone No:
ba -zoO
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION PE
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3
rn AO p roved per applicable codes. 0 Corrections required prior to approval.
COMMENTS:
in0,--c st-e1,4 — /V
p■ r
Date:
7— I I -t37 .
$58100 REINSPECTION E REQUIR$ . Prior to inspection, fee must be
p d at 6300 Southcenter Blvd., Suite 100. Call to sechedule reinspection.
Receipt No.: (Date:
Project:
uPi hs\-. Goi-UC /po N P-S
Type of Inspection:
Rrt (,JAL
Address: 3o S u o kip DR—
Suite #:
Contact Person:
ckt ( [/}1J - 4 PG 4
Special Instructions:
Phone No.:
4 )-06 -. sl— of 3
Needs Shift Inspection: ;1
Sprinklers:
i
Fire Alarm:
Hood & Duct:
A/
Monitor: ftt1'
Pre -Fire:
Permits:
Occupancy Type:
5 (
1
INSPECTION NUMBER
CITY OF TUKWILA FIRE DEPARTMENT
444 Andover Park East, Tukwila, Wa. 98188 206 - 575 -4407
Approved per applicable codes.
INSPECTION RECORD
Retain a copy with permit
sF
Doh - ao0
PERMIT NUMBERS
in Corrections required prior to approval.
COMMENTS:
l
F t ti r t d .-7 oil . Se; Sr.. o
Inspector: s r
Date: NW
Hrs.: . S`
444- / 4- n $80.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the qty of Tukwila Finance Department. Call to schedule a reinspection.
Word /Inspection Record Form.Doc 1/13/06
T.F.D. Form F.P. 113
REVIEWED FOR
CODE COMPLIANCE
y
Ammo/won
JUN 1 4 2006
COty Of Tukwila
RUTLDTN( nItsION
CITY OF K ILA
MAY 31 2006
PERMIT CENTER
ciDGto —too
J.S. DYER & ASSOCIATES INC.
STRUCTURAL ENGINEERS
Voluntary Seismic Retrofit
for
Upland Distribution Center
Building 425
305 Andover Park West
Tukwila, Washington 98188
May 9,2006
JSD # 2006.111.00 phase 07
Prepared for
AMB Property Corporation
San Francisco, California
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
1
ENGINEER;
LW
DATE:
Apr -06
ANALYSIS:
Voluntary Seismic Retrofit
IBC See. 1616 Criteria Selection
Seismic Use Group = I Sec. 1616.2
Seismic Design Category = E Tables 1616.3(1) and (2)
_ . Importance Factor = I = = 1.00 Table 1604.5
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
2
ENGINEER
LW
DATE:
Apr -06
ANALYSIS:
Voluntary Seismic Retrofit
psf
psf
psf
psf
psf
psf
psf
psf
psf
Tributary Area (A,) Live Load
O to 200 ft 12
200 to 600 ft 1.2 - 0.001A,
over 600 ft 20
59.063
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
.3
ENGINEER:
LW
DATE:
Apr -06
ANALYSIS:
Voluntary Seismic Retrofit
of a one -story rigid wall / flexible diaphragm structure in accordance with the 2003 International Building Code
Tributary Wall Weight
Allowable Stress Design Basis
Top -Of -Wall Elevation = h top = 26.5 ft
Average Diaphragm Elevation = h„ = 26.5 ft
Bottom -Of -Wall Elevation = N = 0.0 ft
Wall Thickness = T = 5.5 inch
Wail Unit Weight = W = 145 pcf
Tributary Wall Height = H = 13.25 ft
Tributary Wall Weight = W 881 #/ft
IBC Sec. 1620.3.1 Anchorage Of Concrete Or Masonry Walls (Strength Design Basis)
Importance Factor = I = 1.00
Design Spectral Acceleration = SDS = 0.887
F = 280 #/ft
F 0.10W 88 #/ft
Fp3 = 0.8SDSIEW = 625 #/ft
F = 625 #/ft
2006.111.00 Upland Bldg 426- retrofit \Walls 1 and 12 4
H = (hrop - hn) + 0.5(hn +
W TWH /12
linked from Site
linked from Site
Sec. 1604.8.2
Sec. 1620.2.7
Eq. 16 -62
largest [F F F
Anchor Spacing = s = 8.19 ft
EASD = F 1.4 = 446 #/ft
F = sEASD = 3657 .ounds for non -steel elements
F „ = 1.4F = 5119 pounds for steel elements
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
'-1
ENGINEER:
LW
DATE:
Apr -06
ANALYSIS:
Voluntary Seismic Retrofit
Continuity Tie At Wall - Zone 4 Hardware
Continuity Tie At Wall - Simpson Hardware
2006.111.00 Upland Bldg 425-retrofit Walls 1 and 12 5
J.S. DYER & ASSOCIATES INC.
STRUCTURAL ENGINEERS
Wall Anchorage - Longitudinal Perimeter Walls (Walls 1 and 12)
24-6
2
1/2
3/4
1
6.75
5071
22503
1828
5071
22503
0.72
0.23
1
6.75
5500
0.3068
1627
1828
5550
8034
0.66
0.64
inches
inches
inches
pounds
pounds
pounds
pounds
pounds
OK
OK
HD2A
8034 psi
5/8 inches
2
5/8 inches
inches
pounds
m
2
pounds
pounds
pounds
pounds
OK
OK
AT BOWS ALL EMS{
ICBO ER -5302, Table 2
ICBO ER -5302, Table 2
V, = 2(0.33F„)As
.108 NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
.J
ENGINEER:
LW
DATE:
Apr-06
ANALYSIS:
Voluntary Seismic Retrofit
2006.111.00 Upland Bldg 425 - retrofit \Hilti 1
J. S. DYER & ASSOCIATES INC.
STRUCTURAL ENGINEERS
3.500 in Tension Caoacitv Reduction Factors
5.500 in Based on Anchor Spacing, fn = 0.700
Based on Anchor Edge Distance, fn = 0.600
4.867 Shear Canacitv Toward Edae Reduction Factors
Based on Anchor Spacing, fv = 0.700
1,396 Ibs Based on Anchor Edge Distance, fv = 0.200
0 Ibs Shear Canacity Not Toward Edae Reduction Factors
Based on Anchor Spacing, fv = 0.700
f 'c = 4,000 psi Based on Anchor Edge Distance, fv = 0.600
ASTM A36 Calculated Reductions for Concrete Capacity
s = 8.250 in Tension Caoacity Reduction
Based on Spacing, Rt1 =
Based on Edge Distance, Rt2 =
Reduction, Rt = Rt1 • Rt2 =
Shear Toward Edae Caoacitv Reduction
Based on Spacing, Re1 =
Based on Edge Distance, Re2 =
1.333 Reduction, Re = Re1 • Re2 =
Shear Not Toward Edae Capacity Reduction
Based on Spacing, Rn1 =
Based on Edge Distance, Rn2 =
Tc = 3,859 Ibs Reduction, Rn = Rn1 • Rn2
Ts = 8,455 Ibs
V c =
Vs =
4,543 Ibs
4,355 Ibs
Edge Distance & Spacing for Full Capacity from Table 6
7.000 in
5.250 in
Reduction Factors from Table 4
Min Anchor Spacing Distance, 1.750 in
Min Anchor Edge Distance Factor, 0.330
Min Anchor Edge Distance, 1.733 in
Adjusted Allowable Loads
Concrete Allowable@
Tension, Ptc = Tc • Inc • Rt =
V Toward Edge, Vtc = Vc • Inc" Re =
V Not Toward Edge, Vnc = Vc • Inc • Rn =
Rod Steel Allowables
Tension,
Shear,
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1.000
1 000
5,144 Ibs
6,056 Ibs
6,056 Ibs
Pts = Ts " Inc = 11,271 Ibs
Vts = Vs • Inc = 5,805 Ibs
Concrete Tension + Shear Toward Edge Interaction,
Uct = (Ps (Ptc) + (Vs (Vtc) = 0.271 OK
Concrete Tension + Shear Not Toward Edge Interaction,
Ucn = (Ps / Ptc) + (Vs / Vnc) = 0.271 OK
Rod Steel Tension + Shear Interaction,
Us = (Ps / Pts) + (Vs / Vts) = 0.015 OK
Concrete Thickness, Ut = t / e = 1.571 OK
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
(„
ENGINEER
LW
DATE:
Apr -06
ANALYSIS:
Voluntary Seismic Retrofit
of a one -story rigid wall / flexible diaphragm structure in accordance with the 2003 International Building Code
Top -Of -Wall Elevation = h = 26.5 ft
Average Diaphragm Elevation = h„ = 26.5 ft
Bottom -Of -Wall Elevation = h yor = 0.0 ft
Wall Thickness = T = 5.5 inch
Wall Unit Weight = W = 145 pcf
Tributary Wall Height = H = 13.25 ft
Tributary Wall Weight = W = 881 #/ft
IBC Sec. 1620.3.1 Anchorage Of Concrete Or Masonry Walls (Strength Design Basis)
Importance Factor = IE = 1.00
Design Spectral Acceleration = Sp = 0.887
F = 280 #/ft
F 0.10W..= 88 #/ft
F = 0.8S = 625 11/11
F = 625 #/ft
Anchor Spacing = s =
EASD = F / 1.4 =
F = sEASO =
=1.4F=
2006.111.00 Upland Bldg 425- retrofl6Walls A and G 7
H= (h h„) +0.5(h„ +h
W TWH /12
linked from Site
linked from Site
Sec. 1604.8.2
Sec. 1620.2.7
Eq. 16 -62
largest [F F Fps]
8.00 ft
446 #/ft
3572 ..unds for non -steel elements
5001 pounds for steel elements
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
a
ENGINEER:
LW
DATE:
Apr -06
ANALYSIS:
Voluntary Seismic Retrofit
Steel Capacity Unity Check = Fneel / F,„ (allow) = 0.62 OK
2006.111.00 Upland Bldg 425- retrofit \Walla A and G 8
ICBO ER -5302, Table 2
ICBO ER -5302, Table 2
V, = 2(0.33F „)Ar0d
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
8
ENGINEER:
LW
DATE:
Apr -06
ANALYSIS:
Voluntary Seismic Retrofit
Min Shear Not Toward Edge Distance, c = 12.000 in
Load Factors
Increase for Short-Term Loading, Inc = 1.333
3,859 Ibs
8,455 Ibs
4,543 Ibs
4,355 Ibs
Edge Distance & Spacing for Full Capacity from Table 6
7.000 in
5.250 in
Reduction Factors from Table 4
Min Anchor Spacing Distance Factor, 0.250
Min Anchor Spacing Distance, 1.750 in
Min Anchor Edge Distance Factor, 0.330
Min Anchor Edge Distance, 1.733 in
Tension Capacity Reduction Factors
Based on Anchor Spacing, fn = 0.700
Based on Anchor Edge Distance, fn = 0.600
Shear Capacity Toward Edge Reduction Factors
Based on Anchor Spacing, fv = 0.700
Based on Anchor Edge Distance, fv = 0.200
Shear Canacitv Not Toward Edge Reduction Factors
Based on Anchor Spacing, fv = 0.700
Based on Anchor Edge Distance, fv = 0.600
Calculated Reductions for Concrete Capacity
Tension Capacity Reduction
Based on Spacing, Rt1 =
Based on Edge Distance, R12 =
Reduction, Rt = Rt1 • Rt2 =
Shear Toward Edge Capacity Reduction
Based on Spacing, Ret =
Based on Edge Distance, Re2 =
Reduction, Re = Re1 • Re2 =
Shear Not Toward Edge Capacity Reduction
Based on Spacing, Rn1 =
Based on Edge Distance, Rn2 =
Reduction, Rn = Rn1 • Rn2 =
Adjusted Allowable Loads
Concrete Allowables
Tension,
V Toward Edge,
V Not Toward Edge,
Rod Steel Allowables
Tension,
Shear,
Ptc = Tc • Inc " Rt =
Vtc = Vc " Inc Re =
Vnc =Vc` Inc • Rn =
0.886
1.000
0.886
0.886
1.000
0.886
0.886
1.000
0.886
4,556 Ibs
5,364 Ibs
5,364 Ibs
Pts = Ts • Inc = 11,271 Ibs
Vts = Vs • Inc = 5,805 Ibs
Concrete Tension + Shear Toward Edge Interaction,
Uct = (Ps / Ptc) + (Vs / Vtc) = 0.395 OK
Concrete Tension + Shear Not Toward Edge Interaction,
Ucn = (Ps / Plc) + (Vs / Vnc) = 0.395 OK
Rod Steel Tension + Shear Interaction,
Us = (Ps / Pts) + (Vs / Vts) = 0.025
Concrete Thickness, Ut = t / e = 1.571 OK
OK
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
q,
ENGINEER
LW
DATE:
Apr -06
ANALYSIS:
Wall Anchorage to Flexible Diaphragm, Rods
This spreadsheet performs supporting calculations for out -of -plane wall anchorage for the Voluntary Seismic Retrofit
of a one -story rigid wall / flexible diaphragm structure in accordance with the 2003 International Building Code
Rod Tension Capcity, T =
Steel Capacity Unity Check = F e , Fated (allow) =
2008.111.00 Upland Bldg 425- retrofitRods 10
J. DYER & AS SOCIA TES INC.
Wall Anchorage - Steel Anchor Rod
Importance Factor =1 = 1.00
Design Spectral Acceleration = SDS = 0.887
F =
F 0.10W
Fp3 = 0 . 8 SDSJEWw =
F =
Anchor Spacing = s =
Emr, /
F = sEASD =
Fsrxt =1.4F =
26.5 ft
26.5 ft
0.0 ft
5.5 inch
145 pef
13.25 ft
881 #/ft
280 #/ft
88 #/ft
625 #/ft
625 #/ft
8.19 ft
#/ft
pounds
pounds
446
3657
5119
ASTM A36
36 ksi
58 ksi
3/4 inches
0.442
0.334
in
in
1.33
12.692 k
12.900 k
5.119 k
12.692 k
0.40 OK
H = (h - hp) + 0.5(hp + hoot)
W TWH /12
linked from Site
linked from Site
Sec. 1604.8.2
Sec. 1620.2.7
Eq. 16 -62
largest [F F p2. F
for non -steel elements
for steel elements
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
ENGINEER:
LW
DATE:
Apr -06
ANALYSIS:
Wall Anchorage to Flexible Diaphragm, Rods
Based on Edge Distance, Rn2 = 1.000
Tension Capacity of Concrete, Tc = 3,859 lbs Reduction, Rn = Rn1 • Rn2 = 1.000
Tension Capacity of Rod Steel, Ts = 8,455 Ibs
Adjusted Allowable Loads
Concrete Allowables
4,543 Ibs Tension, Ptc = Tc * Inc • Rt = 5,144 Ibs
4,355 Ibs V Toward Edge, Vtc = Vc * Inc Re = 6,056 lbs
V Not Toward Edge, Vnc = Vc * Inc' Rn = 6,056 Ibs
Rod Steel Allowables
Spacing Distance for Full Capacity, 7.000 in Tension,
Edge Distance for Full Capacity, 5.250 in Shear,
Min Anchor Edge Distance Factor, 0.330
Min Anchor Edge Distance, 1.733 in
Pts = Ts' Inc = 11,271 Ibs
Vts = Vs' Inc = 5,805 Ibs
Concrete Tension + Shear Toward Edge Interaction,
Uct =(Ps /Ptc) +(Vs /Vtc)= 0.711 OK
Concrete Tension + Shear Not Toward Edge Interaction,
Ucn = (Ps / Ptc) + (Vs / Vnc) = 0.711 OK
Rod Steel Tension + Shear Interaction,
Us = (Ps / Pts) + (Vs / Vts) = 0.105 OK
Concrete Thickness, Ut = t / e = 1.571 OK
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
t
ENGINEER:
LW
DATE:
Apr -06
ANALYSIS:
Diaphragm Analysis
Bearing Wall System
Bearing Wall System
Ordinary Reinforced
Concrete Shear Walls
Ordinary Reinforced
Concrete Shear Walls
This spreadsheet summarizes the development of anchorage loads into the diaphragm for the Voluntary Seismic
Retrofit of a one -story rigid wall / flexible diaphragm structure in accordance with the 2003 International Building
ASCE 7 Sec. 9.5.5 Equivalent Lateral Force Procedure
IBC Sec. 1617.4 requires that the Equivalent Lateral Force Procedure of ASCE 7 -02, Sec. 9.5.5 be used.
Soil Profile Type (Class) = D
Mapped Spectral Acceleration = S = 0.458
Design Spectral Acceleration = SDS = 0.887
Importance Factor = I = 1.00
Average Diaphragm Elevation = h = 26.5
Basic Seismic Force
Resisting System
Transverse
Response Modification Coefficient = R =
System Overstrength Factor = f 0 =
C =
redundancy factor = p =
T= C /4=
C3= S / (R/I) _
Cs(max) = SDI / T(R/I) =
C omm = 0.044S =
Cs(min • SDC E or F) = 0.5S1 / (R/1) =
Cs(min) =
C, =
IBC Sec. 1620.4.3 Diaphragms
Seismic Lateral Loads For Diaphragm Design
Tributary Wall Weight = W =
Roof Length = L =
Roof Unit Weight = U =
Roof Weight = LU = W,nnr =
Total Weight = 2W„„ + W nor = W p =
Roof Seismic Load = F = Vrnnr =
2006.111.00 Upland Bldg 425- retroflt\Dlaphragm
J.S. DYER & ASSOCIATES INC.
STRUCTURAL ENGINEERS
F =C,W
Finnan) = 0.4S =
Fp(min) = 0.2S =
F =
Fp(ASD) = F / 1.4 =
Diaphragms
12
4.0
g
g
ft
Longitudinal
2.0
0.020
1.00
0.23
0.222
0.950
0.039
0.000
0.039
0.222
4.0
2.0
0.020
1.00
0.23
0.222
0.950
0.039
0.000
0.039
0.222
seconds
W
W
W
Wp
W
#/ft
ft
psf
#/ft
#/ft
#/ft
linked from Site
linked from Site
linked from Site
linked from Site
Table 9.5.2.2
Table 9.5.2.2, footnote g
Table 9.5.5.3.2
code interpretation for diaphragms
Eq. 9.5.5.3.2 -1
Eq. 9.5.5.2 -1.1
Eq. 9.5.5.2 -1.2
Eq. 9.5.5.2 -1.3
Eq. 9.5.5.2 -1.4
Cs(min)= larger [Cs(minl). CS(SDC E or F)I
Cs(min) < Cs < Cs(max)
I Transverse
0.222
0.355
0.177
0.222
0.158
Longitudinal I
0.222
0.355
0.177
0.222
0.158
Eq. 16 -63
Fp(min) < F < Fp(max)
Transverse
881
123.25
11.45
1411
3173
503
Longitudinal
881
540
11.45
6183
7945
1259
previously calculated
previously calculated
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
1
ENGINEER:
LW
DATE:
Apr -06
ANALYSIS:
Diaphragm Analysis
47456
4427
503
1259
305
123
123
540
76708
77586
622
144
5848947
2390615
47456
4427
1259
503
25
24
24
24
15475
6036
645
252
95108
36216
3963
1509
w V..x = V oorL /2
= V.,x /W
DIAPHRAGM SHEARS
Mwx = VnoorL /8
T.o = Mwx /W
J.S. DYER & ASSOCIATES INC.
STRUCTLRAL ENGINEERS
Vroof
L
W
Vmex =
Vmu =
Mm�x =
Tmn =
Vmor=
L=
W =
Vmex =
Vmex =
Mmax _
Tmax =
2006.111.00 Upland Bldg 425 retroflnDiaphragm 13
Diaphragms
#/ft
ft
ft
pounds
#/ft
ft-#
pounds
#/ft
ft
ft
pounds
#/ft
ft-#
pounds
Seismic Lateral Load
Diaphragm Length
Diaphragm Depth
Maximum Shear
Maximum Shear
Maximum Moment
Maximum Chord Force
Seismic Lateral Load
Diaphragm Length
Diaphragm Depth
Maximum Shear
Maximum Shear
Maximum Moment
Maximum Chord Force
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO: t3
ENGINEER
LW
DATE:
Apr -06
ANALYSIS:
Diaphragm Continuity Ties
This spreadsheet performs supporting calculations for continuity ties for the Voluntary Seismic Retrofit of a one -story
rigid wall / flexible diaphragm structure in accordance with the 2003 International Building Code (IBC).
IBC Sec. 1616.4.2 Connections
IBC Sec. 1620.2.4 Connections
Wall Force
Allowable Stress Design Basis
J.S. DYER & ASSOCIATES INC.
STRUCTURAL ENGINEERS
Continuity Ties - Longitudinal Direction (NS Forces)
Dead = D = 11.45 psf
Live = L = 12.00 psf
Area = A = 6548 ft
F = 0.05(D+L)A = 7677 pounds
Design Spectral Acceleration = S = 0.887 g
w = DA = 74969 pounds
F = 0 . 133 SDSWp = 8847 pounds
F = 0.05w = 3748 pounds
Wall Anchorage Force = F = 881 #/ft
Tie Spacing = s = 24.58 ft
F = F = 21658 pounds
2006.111.00 Upland Bldg 425- retrofit \Tie (NS) 14
F = 7677 pounds
F = 8847 pounds
F = 3748 pounds
F = 21658 pounds
F 15475 pounds
F 21658 pounds
F = F / 1.4 = 15470 pounds
F, = 1.4F= 21658 pounds
ASD Basis
roof dead load
roof live load
area tributary to tie
strength level
previously calculated
weight tributary to tie
Eq. 16 -58
Eq. 16 -59
previously calculated
strength level
Subdiapbragm Force
Number Subdiaphragms = N = 1
Edge Reaction = V,,,., = 15475 pounds previously calculated
F N V = 15475 pounds strength level
largest [Fpt, Fp2, Fp3, Fp4, Fp5]
for non -steel elements
for steel elements
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
19_
ENGINEER
LW
DATE:
Apr -06
ANALYSIS:
Diaphragm Continuity Ties
•
•
Rod Area = Arod = 0.6013 in
Steel Capacity Each Pair = V, = 22400 pounds
F rog = F / 2N = 7735 pounds
• Total Wood Capacity p ty =NV = Fwaod (allow) = 19080 pounds
Total Steel Capacity = NV, = Fated ( = 22400 pounds
• Wood Capacity Unity Check = F / F wow) = 0.81 OK
Steel Capacity Unity Check = F s , ttl / Fsml (allow) = 0.97 OK
ICBO ER -5302, Table 2
ICBO ER -5302, Table 2
V, = 2(0.33Fu)Arad
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
15
ENGINEER:
LW
DATE:
Apr -06
ANALYSIS:
Diaphragm Continuity Ties
Continuity Ties - Transverse Direction (EW Forces)
rigid wall / flexible diaphragm structure in accordance with the 2003 International Building Code (IBC).
This spreadsheet performs supporting calculations for continuity ties for the Voluntary Seismic Retrofit of a one -story
IBC Sec. 1616.4.2 Connections
IBC Sec. 1620.2.4 Connections
Subdiaphragm Force
Number Subdiaphragms = N = 1
Edge Reaction = V,,,,, = 6036 pounds previously calculated
F = NV,„,, = 6036 pounds strength level
Allowable Stress Design Basis
2006.111.00 Upland Bldg 425- retrofinTie (EW) 16
J.S. DYER & ASSO INC.
Dead = D = 11.45 psf
Live = L = 12.00 psf
Area = A = 3092 ft
F = 0.05(D+L)A = 3625 pounds
roof dead load
roof live load
area tributary to tie
strength level
previously calculated
weight tributary to tie
Eq. 16 -58
Eq. 16 -59
previously calculated
strength level
F = 3625 pounds
F = 4178 pounds
F = 1770 pounds
F = 21144 pounds
F = 6036 pounds
F = 21144 pounds largest [Fpt, Fp, F F F
F = Fp / 1.4 = 15103 pounds 1ASD Basis for non -steel elements
Fi = 1.4F = 21144 pounds I for steel elements
JOB NAME:
Upland Distribution Center
Building 425
JOB NO:
2006.111.00
SHEET NO:
1(c.
ENGINEER
LW
DATE:
Apr -06
ANALYSIS:
Diaphragm Continuity Ties
Steel Capacity Unity Check = F „ ttl / F „„( = 0.94 OK
ICBO ER - 5302, Table 2
ICBO ER - 5302, Table 2
V, = 2(0.33Fo)Arod
ACTIVITY NUMBER: D06 -200 DATE: 05 -31 -06
PROJECT NAME: BUILDING 425
SITE ADDRESS: 305 ANDOVER PK W
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # After Permit Issued
DE k P G A y R L TMENTS: 4 , „.'
Building Division
Public Works 154. Structural
V1/4, (P-114436
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete d Incomplete ❑
Comments:
TUES/THURS ROUT NG:
Please Route Structural Review Required
REVIEWER'S INITIALS:
APPROVALS OR CORRECTIONS:
Approved ❑
Notation:
REVIEWER'S INITIALS:
Documents/routing slip.doc
2 -28-02
,,PERMIT COORD COPY �..
PLAN REVIEW /ROUTING SLIP
Approved with Conditions
5(1 t' 6th-ofr
Fire Prevention
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
E
DUE DATE: 06-06-06
No further Review Required
DATE:
DATE:
"ILL. t
Planning Division SW
Permit Coordinator
Not Applicable ❑
n
DUE DATE: 07 -04 -06
Not Approved (attach comments) ❑
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
License Information
License
SAUNDCI953ND
Licensee Name
SAUNDERS CONSTRUCTION INC
Licensee Type
CONSTRUCTION CONTRACTOR
UBI
602518261
Ind. Ins. Account Id
PRESIDENT
Business Type
CORPORATION
Address 1
1760 MONROVIA AVE UNIT A -1
Address 2
City
COSTA MESA
County
OUT OF STATE
State
CA
Zip
92627
Phone
9496460034
Status
ACTIVE
Specialty 1
GENERAL
Specialty 2
UNUSED
Effective Date
8/4/2005
Expiration Date
8/4/2007
Suspend Date
Separation Date
Parent Company
Previous License
Next License
Associated License
Business Owner Information
Name
Role
Effective Date
Expiration Date
CASILLAS, PATRICIA
AGENT
08/04/2005
SAUNDERS, STEVEN
PRESIDENT
08/04/2005
HILL, SUSAN
SECRETARY
08/04/2005
Look Up a Contractor, Electric or Plumber License Detail Page 1 of 2
Washington State Department of Labor and Industries
General/Specialty Contractor
A business registered as a construction contractor with L&I to perform
construction work within the scope of its specialty. A General or Specialty
construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Bond Information
Bond
Bond
Company
Name
Bond
Account
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Bond
Amount
Received
Date
DEVELOPERS
SURETY &
Until
https: // fortress .wa.gov /lni/bbip /printer.aspx ?License= SAUNDCI953ND 07/06/2006
x
x
x
x