MECHANICAL PERMIT
Permit No: M95 -0050
Type: B -MECH
Category: NRES
Address: 550 ANDOVER PK W
Location:
Parcel #: 262304 -9015
Contractor License No: PARSLEI07ZMK
TENANT UNITED PARCEL SERVICE
550 ANDOVER PK W, TUKWILA, WA 98188
ROFFE, INC Phone: 206 622 -0456
SONNY JONES, 808 HOWELL ST, SEATTLE WA 98101
PARSLEY ENGINEERING INC. Phone: 206 836 -2926
4620 232ND AVENUE N.E., REDMOND, WA 98053
RONN PARSLEY Phone: 206 836 -2926
4620 232 AV NE, REDMOND, WA 98053
OWNER
CONTRACTOR
CONTACT
Status: ISSUED
Issued: 03/31/1995
Expires: 09/27/1995
Suite:
•
********************************************* * * * * * * ** * * * * * * *** * ** * * * * *,r * * **
Permit Description:
INSTALL TWO ROOFTOP AC UNITS, DUCTWORK, EXHAUST
FANS, THERMOSTATS, CHECK STESTS, START UP AC, AND
AIR BALANCE SYSTEMS.
UMC Edition: 1991
Valuation: 8;405.00
Total Permit Fee: 49.38
******************************************* * * * * * * * * ** * * * * * * * * * * * * * * * * * ** **
Permit Center Authorized Signature Date
I hereby certify that I have read and examined this permit and know the
same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate
or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign for and
obtain this building permit.
0
Signature : __ _
Date: .3 3L,�1J
Print Name: __,N/4N19!__,T __e_L4t �_�( Ti tie:___. e:x,_.pLAsiztea _
This permit shall become null and void if the work is not commenced within
180 days from the date of issuance, or if the. .work is suspended or
abandoned for a period of 180 days from the last inspection.
CITY OF TUKW'
Department of Community Development -- Permit Center
6300 Southcenter Boulevard - #100, Tukwila, WA 98188
(206) 431 -3670
Mechanical Permit Application Tracking
PLAN CHECK
NUMBER
Mg5-1�50
PR•JEC
NA
SITE ADDRESS
550 ii- Aldo0EK PK 1AI
SUITE NO.
INSTRUCTIONS TO STAFF
• Contacts with applicants or requests for information should be summarized in writing by staff so
that the status of the project may be ascertained at any time.
• Plan corrections shall be completed and approved prior to sending to the next department.
• Any conditions or requirements for the permit shall be noted in the Sierra system or summarized
concisely in the form of a formal letter or memo, which will be attached to the permit.
• Please fill out your section of the tracking chart completely. Where information requested is not
applicable, so note by using "N /A ", date and initial.
DEPARTMENTAL REVIEW
"X" in box indicates which departments need to review, the project.
BUILDING -
initial review 3-)315 3 tt
RO ED
O FIRE
Q.UIREMENTS
CONSULTANT: Date Sent
COMMENT;
Date Approved -
FIRE PROTECTION:
Sprinklers • Detectors
N/A
INIT:
FIRE DEPT. LETTER DATED:
INSPECTOR:
O PLANNING
ZONING:
BAR/LAND USE CONDITIONS? • Yes
INIT:
SCREENING REQUIRED? D Yes Q No
REFERENCE FILE NOS.:
O OTHER
BUILDING -
final review
ABUILDING
OFFICIAL
INIT:
WES
INIT:
5s1 y INIT:
REVIEW COMPLETED
UMC EDITION (year):
AMOUNT
OWING:
4 A
t
(161 ,
CONTACTED
���
DATE NOTIFIED
qq5
BY: `
(Init.)
D
2nd NOTIFICATION
BY:
(init.)
3RD NOTIFICATION
BY:
(init.)
01/07/93
CITY OF TUKWILA
MECHANLAL PERMIT
APPLICATION
Department of Community Development - Building Division
6300 Southcenter Boulevard, Tukwila WA 98188
(206) 431 -3670
PLAN CHECK
NUMBER McscsC)
APPLICATION MUST BE FILLED OUT COMPLETELY
FEES (for staff use only)
DESCRIPTION:::-:: .:
- ;:AMOUNT :::
RCPT::•#
'< >:;:< DATE::;•: ::
BASIC PERMIT FEE
:' $15:00
>.:.............. :.:.:.:;. NUMBER:Of =:: N TS ..:.............:
. ,, • - ,r
2 i?uoFr –Pr Ac unvl'TS D0c.-r-4- - ,4-.. - •
UNIT(S) FEE.::::': ; ::
PLAN CHECK FEE
BUILDING USE (office, warehouse, etc.) / -
PA-izc e / p�e 6` v / :c it rerwic-
OTHER
WILL THERE BE A CHANGE IN USE? ®-No ❑ Ye8 IF YES, EXPLAIN:
WILL THERE BE STORAGE OR USE OF FLAMMABLE, COMBUSTIBLE OR HAZARDOUS MATERIALS IN THE BUILDING?
(>3-No ❑ Yes
IF YES, EXPLAIN:
• TOTAL; .
SITE ADDRESS SUITE #
.550 A nip D yet. I°fitle 14 PsT
VALUE OF CONSTRUCTION - $
g` 05-
ASSESSOR ACCOUNT #
2 . 6 ?. 3 o y- q 0.) 5.—
PROJECT NAME/TENANT
i J N Z : r d f ‘ 2 , 1 . 2 - e - ( e 4 Sett. v / c. e.
TYPE OF WORK: ❑ New /Addition (R)- Modifications ❑ Repair ❑ Other:
DESCRIBE WORK TO BE DONE:
>. TYPE .: :....RATING/ SIZE:: >;;;: >: =. <:s:' :< >' <:`:
>.:.............. :.:.:.:;. NUMBER:Of =:: N TS ..:.............:
. ,, • - ,r
2 i?uoFr –Pr Ac unvl'TS D0c.-r-4- - ,4-.. - •
,.
BUILDING USE (office, warehouse, etc.) / -
PA-izc e / p�e 6` v / :c it rerwic-
NATURE OF BUSINESS:
PAg'G - de Lva�j
WILL THERE BE A CHANGE IN USE? ®-No ❑ Ye8 IF YES, EXPLAIN:
WILL THERE BE STORAGE OR USE OF FLAMMABLE, COMBUSTIBLE OR HAZARDOUS MATERIALS IN THE BUILDING?
(>3-No ❑ Yes
IF YES, EXPLAIN:
PROPERTY OWNER l/rY p Tao
PHONE
,�G/
ADDRESS S p,), e A5 A 61 V
ZIP
CONTRACTOR �� / P�
PHQNE _7,3
�� --��''
EXP. DATE
aR
ZIP 9 g D 3
7/k / 1S---
ADDRESS ( �D a 3 a n.c.i a Ve !U, E. .. A. - ►•...ri 1/1 f
WA, ST. CONTRACTOR'S LICENSE # A LET 0 '?7 Mk
I:HEREBY CERTIFYTHAT I;HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THESAMETO
AND CORRECT, AND I.AM <AUTHORIZED`.TO APPLY:FOR THIS PERMIT
DATE
3/2- 3/9 s'^
PHONE
BUILDING OWNER
OR
AUTHORIZED
AGENT
SIGNATURE
PRINT NAME
ryGy S QS fry
ADDRESS yG } 2 2 �� ✓P _�
v
CONTACT PERSON
B E :TRUE
CITY/ZIP /ra 3
PHO E
APPLICATION SUBMITTAL In order to ensure that your application is accepted for plan review, please make sure to fill out the
application completely and follow the plan submittal checklist on the reverse side of this form. Application and plans
must be complete in order to be accepted for plan review.
BUILDING OWNER /AUTHORIZED AGENT If the applicant is other than the owner, registered architect/engineer, or contractor licensed
by the State of Washington, a notarized letter from the property owner authorizing the agent to submit this permit
application and obtain the permit will be required as part of this submittal.
VALUATION OF CONSTRUCTION The valuation is for the work covered by this permit and must be filled in by the applicant. This
figure is used for budget reporting purposes only and not to calculate your fees.
EXPIRATION OF PLAN REVIEW Applications for which no permit is issued within 180 days following the date of application shall
expire by limitation. The Building Official may extend the time for action by the applicant for a period not exceeding 180
days upon written request by the applicant as defined in Section 304(d) of the Uniform Mechanical Code (current
edition). No application shall be extended more than once.
1f you have any cimgabout our process or plan submittal requirements,
please contggitrihilt0Aent of Community Development at 431 -3670.
DATE APPLICATION ACCEPTED
MAR 2 3 1995
DATE APPLICATION EXPIRES
03/14/94
SUBMITTAL CHECKLIST
MECHANICAL
pi Completed mechanical permit application (one for each structure or tenant)
Two (2) sets of mechanical plans, which include:
• Floor plan
• System layout
• Elevations (for roof mounted equipment)
• Heat Loss Calculations
Structural calculations stamped by a Washington State licensed engineer may be
required if structural work is to be done (2 sets)
Note: Hood and duct systems require a building permit for the duct shaft.
Water heaters and vents are included in the UMC — Please inclUde any water heaters or
vents being installed or replaced.
•
PLEASE DETACH AND SIGN
CERTIFICATE, BEFORE PLACING
IN BILLFOLD.. _,..
;t ,: i` '.REGI$TRATION
NUMBER' r'..'' •,:1`{
ti =t lPARBLE,TO'!:711 N .•
EF0 EC;,T; f NE,' DA T6 ,
,r; E I.F.1 T(Q)1 D
Y.9!%oG `f{�i!.5..
� !; ., , ,- :3
,, ° =. . C' .
,., ;,;
PARSLEY ;ENGINEER
4620 -232ND ' AVE N E
REDMOND ' WA 98453
SIGNATURE
ISSUED BY DEPA
F625. 052.000 (3.92)
I '
4
!t
, 411A u A. 4 4.,341012.4:441.4“.AV,J.,4124,w14.,.,
INSPECTION RECORD (
Retain a copy with permit
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
mci.5
00s0
PERMIT NO.
6)-43
• IV act: up5
ype o nspection: (\ea-717:(7,
/Date Called: )q5
5 c•Re--
Address:550
,
aA0Vet(- FLAN
Special Instructions:
Date Wanted:6) ‘..1 lc( ......
am.
Requeste,..,r:
phone No.:5_75_,c( a
gliApproved per applicable codes. _ _D—Corriktio-rifricliiired-prior-t prove'.
COMMENTS: '
Inspector:
f
.o fiat
El $30.00 REINSPECTION FE REQUIRED. Prior to reinstection, fee must be paid at
6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
IRecept No.:
• ••••••.- • — - '
Jrie..4,,.. 14,.. 7JtO praHkti; ozsrtokulawatVVV:4/',L'xPPK'st
0.
CITY OP TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98-18
.0 INSPECTION RECORD
Retain a copy with permit
PERMIT N0.
(206) 431 -3670
ro ect: , /y�-
Type of Inspection:
Date Called:
-�
Address: ...„
/-y
Special ii st
Ions:
/
Date Wanted:
"'
23 -' 7) am p.m.
Requester:
Phone No.:
❑ Approved per applicable codes. Ni Corrections required prior to approval.
❑ $30.00 REINSPECTION FEE REQUIRED. Prior to reinspection, fee must be paid at
6300 Southcenter Blvd., Suite 100. Call to schedule re(nspect(on.
ReceOt No.:
Die;
INSPE
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
o INSPECTION RECORD
Retain a copy with permit
A/1 ?,5.
(945-0
PERMIT NO. I
(206) 431-3670 '
Project: / 1 i/j S
Type ot Inspection: /
Date Called:
L5- A "" 9 ic•-•
Address: Li 0 ,4_f24}
SpeciaNtr
Ions:
t ,
Date Wanted :.5.--... i r
I (0—
... c
."4.,... am. p.m.
)
Requester:
.404....,
,441,•
Phone No.:
C _.
El Approved per applicable codes. Corrections required prior to approval.
COMMENTS: '
. c_.■ <.'"' j,-- (9 Grr---
6
C>fr)//<,_
‘...f
pit, 6,/,14 )4-2 4
4 e , /
,441,•
P ted_I-i--, t,,,f./
2......?
--5 Ps- 7::-xffi5 /-ef.
,e0.0
• ..z.,-e,/ '7.--1
2-'
9 Pe--L i--/-7 4... 4 7/2-. 5
4_,I 17:7 ,4..e
,se..."--40z,...
.0,--2 4,,C /'.
12-7 4 e__
l 4,' fry ?
it
z,
sh.e..,-e
f
,
z.t 1,-7.4,7e.
4:,•_.
6.61.44
•dr .. ./4(..0 .-- ... logr.
— ■AV
/
'
Inspector:
(6%.1
Date --/A95
o $30.00 REINSPECTION FEE REQUIRED. Prior to reinspection, fee must be paid at
6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Dale:
..
•
acm. G.... « �N a, �,,,: e. v- �-.. �m.. rxr,; �, wx. �r: t;. wch=, t�✓ suu: xk:' uxoY. �Ax:. �.:c',:.rwt +J�J:r75iit'4�Stcfl� '.c.•;Sk:'d.",i!ii�l4 i.'�•:T
INSPECTION RECORD
Retain a copy with permit
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
(206) 431 -3670
Project: V p 5
- Type of Inspe Age.cil n
Address;
Date Called:
Special Instructions:
/
i/
��
Date Vllanted;...,.,.
�j -�/s-
i p.m.
Requester: "" '"
Phone No.:
O Approved per applicable codes. Y4 Corrections required prior to approval.
O $30.00 REINSPECTION FEE REQUIRED. Prior to reinspection, fee must be paid at
6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Date:
INSPECTION RECORD
Retain a copy with permit
INSPECTION O.
CITY- OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
1
c050
PERMIT NO.
(206) 431-3670
rOJGC1: S
ype o nspection: rylec. hain t c a. 1
Address: SD 121 tic 10 «r 6-10( j
Date Called: 9-1}0)
Special Instructions:
Date Wante—Al"... 1 q s.....
am. El;
Requester:3.
Phone No,:
Approved per applicable codes. ti,Corrections required prior to approval.
MMENTS:
614-0.0," a 3
1:;;fre_ k&4'64 c5
p.--,712.b;54 114 ee
447 v 4 /I 44-AfA
4 6. .-,sc
e-01 ?--foe s chi/eat-,
C/et /14(0* dee/ 14
7-7 (,,Zep /72,-,-A, 4, la
IInspector:
"6,Z101,971
El $30.00 REINSPECTION FEE REQUIRED. Prior to relnspection, fee must be paid at
6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
1
+n +.z.u....d .+ au. wu. r.... v... u.. r++. a:. e_ vairrnn�.: u 1. vt. ceRw. �L61- s,: Yu h3-42z7 dtu, 4; Y7 ]:trL:�;.;iC`:.:i:..::m.6i1
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
(206) 431 -3670
Project: P
ype o nspect on:
Date Called: � J uc'
Address: "5
Special Instructions:
Date Wanted:
�{
`i - j /-
3
a its p.m.
Requester:
f._....
Phone No.:
❑ Approved per applicable codes.
Q Corrections required prior to approval.
COMMENTS: '
Pu s
71---z) CcAilyr
4 - ) �) , - ' ( ' ' A L - sn o i3 r'p
f J c� ^► J) to c�- + Fi e F {'A „• eta Ld c 4317.4a.1-5
r
,/
v
❑ $30.00 REINSPECTION FEE REQUIRED. Prior to reinspection, fee must be paid at
6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
OC=
Date:
******• k*****4** A•********** k********** * * * * * * * * * *k *,% * ** ***•A• *4 *•* *4*
CITY OF TultWILA., WA TRANSMIT
** * *•A•* *k * **•A• ** * * **4 *a1 * \ *•*• * * * ** *4 * * *A *4 * *44 ** * * **• * * * *�l * * * * *•44 **
TRANSMIT Number: 94062066 Amount: 49.30 03/31/95 10 :47:.
Payment Method: CHECK Notation: PARSLEY ENGINEER Iriit: SLB
Permit Nn. M95- ,0050' Type: .U. -MIZCH . .MECHANICAL PERMIT.
P.arcel•No: 262304 -9015:
.Site Addres's: 550 :ANDOVER PK W
This Payment
'fatal Fees; .. . 49.30.
49.38 Total ALL Pmts:- 43.38
Balance: .00
* * * ** ** * ** * * * * * ** * * * *k *•* * *•* **4 * *4 * *** **i;.4 k* * * * * **4 *JI•at * *A *4 ** * * * *,.
GENERA
GENERA
TOTAL
CEIECIt
CH4NGE
9.88
39.50
49.38
49.38
0.00
/ 1483A000 16:17
t .
Accnunt.Cade
000/345.83V'
0.00/322.100
Description
PLAN CHECK t NONRES.
KEEHANICAL - NONRES.
Amount
9.8.0
39..50..
CITY OF TUKWILA
Address: 550 ANDOVER PI( W
Suite:
Tenant: UNITED PARCEL SERVICE
Type: B -MECH
Parcel #: 262304 -9015
Permit No: M95 -0050
Status: ISSUED
Applied: 03/23/1995
Issued: 03/31/1995
****** * * ***•k * *** k• k*• k' k************ * * * *•k'k *•k * **•k *'k,* *-k * **•k ** b'k•k'b *•k•k•* * *:k-k** * ** *-k
Permit Conditions:
1. No changes will be made. t:cr= :t'he plann1'ess° approved by the
Architect or Engineers- and'` the... Tukwi la "Buil;e :0),# D.ivision.
2. All permits, ins.peic :t.i'oi recor,ds,, and s: approved plans shall be
available at e :e' `:fob site : r i�'or: to ? :the start of "en con -
struct i on . These
»a ta d ocumen•t's are<to be ,ma i ntai ned
able until l 1n pectan appfoval granted ' a `
3. Al 1 construct ion be done conforrance wi thapp'ov e v°
plans and ,l equ i r'ements of the'; Uri,i,form Bu i i"d i ng Code. (1991
Edition° :es amended, ..Uniform• Mechanical Code • ( 1991 Eiiition)
and Wa,sh,i'ngton State Ener,g,'Code (1094 Edition)':,
4. Va l i d.l ty a ;f ,Fermi(`. The ,i ss-uance of 'a permit or `'approva' I
plans,. spec;i,fications, `;and computations shall not'be :con=
strued to + =be; `a permit '"for, or n approval of, any vi,ol,aon
of any of the provisions of.- th4e building code or of Any",„,.
other( `ord'i.nanc.e of the '-gurisd��iction No`: permit presurnln'gto
give` authority to ,•:•vi,olate °o,r; camel, thepr.'ov•isions of;:, this':'.
c o di e`j ;s h a l) 'b e v a l i•d .._ "
5. MANUFACTURERS ,)INSTALLAT,,,ION„r I;N'STRUCtTIOfS—REOUIRED .ON SITE" f
FOR,',.THE BUILDING 'INSPECTORS' REVIEW. ,}' -
6. P1u'��b4n '•_ a mi?ts shall 'be/obit'a;i °ned' through the Seattle -KI °`
County Department of� iPut i ic�� Hea "l.;t•Itif., ` un,b'in.g,ywill be
r',,.h
inspe'cte,d ;pa!`, that agency, includingw a�.11 gas - p�lping r'
C 2 9 64�: 4.7 2 �,, , ..:, ... - it ..,.
7. E1ec kcal pe .rmlts shall be obtai*d ough` the W,ash,1;ti°gton
State '1D,ivl�siion of', Labor and Indu tr 'es �anda1,l,�electricl:
work will be inspe•c,,ted by that agency.,,(2 8 b63O)�•���
E. Reads ly ccess�lble access to ro ff mount�e. e u'i dent fs .
r e u i red, - ''3. +;N,=r, ,. r gtrA
9. VENTILATIQN� ;sIS 'REQUIRED 'FOR .ALL NEW ROO�y{.S LANG
OR EXISTINGt> ,U,ILDINGS IN CONFORMANCE WITH THE UNIFORM/
BUILDING. CODE .AND THE WASHINGTON STA1 E VENTILATION
INDOOR AIR OUAL•:I'TY., CODE, CHAPTER, 5'1'` 1;;3„ =WAC.
t ff
PARSLEY ENGINEERING, INC.
PROFESSIONAI MECIIANICAI EMiNEERIN4
4620 -- 232Nd AVENUE NE
REdMONd, WA 98053
yy\ S 225 o Gsa
MIW 1 U 1995
OLv LJr11VlENT
PHONE: (206) 836 -2926
Fnx: (206) 836 -2806
FAX TRANSMISSION COVER SHEET
DATE: . 51 c li S PAGES (INC. THIS SHEET): Li
TO: G A.Tzdi S c -
COMPANY: cA,'r`1 0r_ 'Cl?y.. c.,,,1 t,pv FAX #: 1.{'3 3 r. 1649
FROM: �--� 1-1'3 (_ 3 6
` , �% _ k�(11 -S LE ..
PROJECT: u . ? . s . — 14 i
SUBJECT: '..,..i.Jst 1.,,E L A OLri"'
COMMENTS:
... • In 1, E. 1.-A> o (7-4.6 tna . A
_ lra o F '"Di n t44— f• TZ.sov 1S %1�
A 1: C o tai. L i _ _f► Lk, ;A...
LA_ CO csttbtt.bileTEA- > L. 1._x lob 1... AIrt.co -trL4X
Ac$ b ' n v.+J 6 H-4- 2.
11.. ►5E.. CALL. 4 V. \-101 .01/4 t- vt. A4441_
GisoM1.01.4 S (3R. NF.at la►eW'1 ■■ortc. t,tJ-F6
--r ;4 attJk Uhl
, •,. • ,•••:-. • .
A.
cra 0
(r-
`\4
j
• I
t • • **1
• la..0 • • • • 4
• • ri
t••- •
4
1
tfki
,e/er pare
,V)4/
a-070v1`
tk,
41.:.tMCV.r. nYt.fl? ":
r. in nv.. r,ei. rn. 1..V., 31. 0C. e, 1nia:mr w•o eir, VtV. 77u iy.+tt¢ +n.rR.Sa:M:.:CWer,;1Rh 0+•••. C' r} ".dY`!rA14.+ttt74Vw,11,1,M..
\w
* ** FULL COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC * **
* * * ** WASHINGTON * **
UPS Kent - 03/17/95 PAGE 12
* * * * * * * * * * ** AIR SYSTEM # 1 (Package Gas /Electric) ZONE SUMMARY * * * * * * * * * * **
ZN. ZONE - DESCRIPTION FLOOR HTG.LOSS SEN.GAIN LAT.GAIN HTG.CFM CLG.CFM
NO. PEAK TIME & MONTH AREA O.A. CFM O.A. CFM EXH. CFM CFM /SF. CFM /SF.
1 STAFF OFFICE #2 260 7,015 7,442 677 220 343
6 PM SEPTEMBER 0 60 . 0 0.85 1.32
2 MGR. 130 2,422 3,491 451 76 161
6 PM SEPTEMBER 0 40 0 0.58 1.24
3 CENTER #2 322 11,307 12,145 902 354 559
6 PM AUGUST 0 80 0 1.10 1.74
HALL 224 7,151 7,209 0 224 332
2 PM SEPTEMBER 0 0 0 1.00 1.48
ZONE PEAK TOTALS 936 27,895 30,287 2,030 874 1,395
TOTAL ZONES: 4 0 180 0 0.93 1.49
* ** FULL COMMERCIAL HVAC
* .
UPS Kent
* * * * * * * ** AIR SYSTEM # 1
LOADS PROGRAM BY ELITE
03/17/95
(Package Gas /Electric)
SOFTWARE DEVELOPMENT INC * **
* ** WASHINGTON * **
PAGE 13
TOTAL LOAD SUMMARY * * * * * * * **
AIR HANDLER DESC: Package Gas /Electric WITH CV (PROPORTION) TERMINALS
SUPPLY AIR FAN: DRAW -THRU WITH PROGRAM ESTIMATED HORSEPOWER OF 0.88 HP.
FAN INPUT: 50% COMBINED FAN AND MOTOR EFF. WITH 2.00 IN WATER ACROSS THE FAN
SENSIBLE HEAT RATIO: 0.94 THIS SYSTEM OCCURS 1 TIME(S) IN THE BUILDING
AIR SYSTEM PEAK TIME: 6 PM IN AUGUST
OUTDOOR CONDITIONS: 79 DB, 65 WB, 71.23 GRAINS INSIDE: 78 DB, 50% RH
SUMMER: VENT CONTROLS OUTSIDE AIR WINTER: NONE CONTROLS OUTSIDE AIR
ZONE SPACE SEN.LOSS:
INFILTRATION SEN.LOSS:
OUTSIDE AIR SEN.LOSS:
SUPPLY DUCT SEN.LOSS:
RETURN DUCT SEN.LOSS:
TOTAL SYSTEM SEN.LOSS:
• 23,074 BTUH
4,821 BTUH
0 BTUH
0 BTUH
0 BTUH
SUPPLY AIR: 27,895 / (0.986 X 1.08 X 30) = (
WINTER VENT OUTSIDE AIR (0.00% OF SUPPLY): (
ZONE SPACE SEN.GAIN: 28,045 BTUH
INFILTRATION SEN.GAIN: 0 BTUH
DRAW -THRU FAN SEN.GAIN: 2,195 BTUH
SUPPLY DUCT SEN.GAIN: 0 BTUH.
TOTAL SEN.GAIN ON SUPPLY SIDE OF COIL:
SUPPLY AIR: 30,240 / (0.986 X 1.10 X 20) = (
SUMMER VENT OUTSIDE AIR (12.9% OF SUPPLY):
RETURN DUCT SEN.GAIN: 0 BTUH
RETURN PLENUM SEN.GAIN: 0 BTUH
OUTSIDE AIR SEN.GAIN: 195 BTUH
BLOW -THRU FAN SEN.GAIN: 0 BTUH
TOTAL SEN.GAIN ON RETURN SIDE OF COIL:
TOTAL SEN.GAIN ON AIR HANDLING SYSTEM:
ZONE SPACE LAT.GAIN: 2,030 BTUH
INFILTRATION LAT.GAIN: 0 BTUH
OUTSIDE AIR LAT.GAIN: -162 BTUH
TOTAL LAT.GAIN ON AIR HANDLING SYSTEM:
TOTAL SYSTEM SENSIBLE AND LATENT GAIN:
TOTAL TONNAGE REQUIRED WITH OUTSIDE AIR:
84 CFM)
0 CFM)
874 CFM)
0 CFM)
0 CFM)
1,395 CFM)
180 CFM)
180 CFM)
0 CFM)
180 CFM)
27,895 BTUH
30,240 BTUH
195 BTUH
30,435 BTUH
1,868 BTUH
32,303 BTUH
2.69 TONS
* ** FULL COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC * **
* * ** WASHINGTON * **
*
UPS Kent 03/17/95 PAGE 14
* * * * * * * * * * ** AIR SYSTEM # 2 (Package Gas /Electric) ZONE SUMMARY * * * * * * * * * * **
ZN. ZONE - DESCRIPTION FLOOR HTG.LOSS SEN.GAIN LAT.GAIN HTG.CFM CLG.CFM
NO. PEAK TIME & MONTH AREA O.A. CFM O.A. CFM EXH. CFM CFM /SF. CFM /SF.
5 TRAINING 448 11,922 15,279 2,706 373 697
6 PM AUGUST 0 240 0 0.83 1.56
6 MANAGER 180 3,576 4,903 451 112 224
6 PM AUGUST 0 40, 0 0.62 1.24
7 MEN'S 256 3,684 4,386 0 115 200
4 PM JUNE 0 0 0 0.45 0.78
8 WOMEN'S 144 2,240 2,716 0 70 124
3 PM JUNE 0 0 0 0.49 0.86
9 HALL UP 120 1,877 2,263 0 59 103
3 PM JUNE 0 0 0 0.49 0.86
ZONE PEAK TOTALS 1,148 23,299 29,547 3,157 729 1,348
TOTAL ZONES: 5 0 280 0 0.64 1.17
* ** FULL COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC * **
* * * ** WASHINGTON * **
UPS Kent - 03/17/95 PAGE 15
* * * * * * * ** AIR SYSTEM # 2 (Package Gas /Electric) TOTAL LOAD SUMMARY * * * * * * * **
AIR HANDLER DESC: Package Gas /Electric WITH CV (PROPORTION) TERMINALS
SUPPLY AIR FAN: DRAW -THRU WITH PROGRAM ESTIMATED HORSEPOWER OF 0.85 HP.
FAN INPUT: 50% COMBINED FAN AND MOTOR EFF. WITH 2.00 IN WATER ACROSS THE FAN
SENSIBLE HEAT RATIO: 0.91 THIS SYSTEM OCCURS 1 TIME(S) IN THE BUILDING
AIR SYSTEM PEAK TIME: 5 PM IN AUGUST
OUTDOOR CONDITIONS: 81 DB, 66 WB, 72.99 GRAINS
INSIDE: 78 DB, 50% RH
BECAUSE OF THE DIVERSITY IN ZONE, PLENUM, AND VENT. LOADS, THE ZONE SENSIBLE
PEAK TIME IN AUGUST AT 6 PM IS DIFFERENT FROM THE TOTAL SYS. PEAK TIME
HENCE, THE AIR SYSTEM CFM WAS COMPUTED USING A ZONE SEN. LOAD OF 28,576
SUMMER: VENT CONTROLS OUTSIDE AIR WINTER: NONE CONTROLS OUTSIDE AIR
ZONE SPACE SEN.LOSS:
INFILTRATION SEN.LOSS:
OUTSIDE AIR SEN.LOSS:
SUPPLY DUCT SEN.LOSS:
RETURN DUCT SEN.LOSS:
TOTAL SYSTEM SEN.LOSS:
17,389 BTUH
5,910 BTUH ( 103 CFM)
0 BTUH ( 0 CFM)
0 BTUH
0 BTUH
SUPPLY AIR: 23,299 / (0.986 X 1.08 X 30) = ( 730 CFM)
WINTER VENT OUTSIDE AIR (0.00% OF SUPPLY): ( 0 CFM)
ZONE SPACE SEN.GAIN: 27,647 BTUH
INFILTRATION SEN.GAIN: 0 BTUH ( 0 CFM)
DRAW -THRU FAN SEN.GAIN: 2,123 BTUH
SUPPLY DUCT SEN.GAIN: 0 BTUH
TOTAL SEN.GAIN ON SUPPLY SIDE OF COIL:
SUPPLY AIR: 30,699 / (0.986 X 1.10 X 21) = ( 1,348 CFM)
SUMMER VENT OUTSIDE AIR (20.8' OF SUPPLY): ( 280 CFM)
RETURN DUCT SEN.GAIN: 0 BTUH
RETURN PLENUM SEN.GAIN: 0 BTUH
OUTSIDE AIR SEN.GAIN: 911 BTUH ( 280 CFM)
BLOW -THRU FAN SEN.GAIN: 0 BTUH
TOTAL SEN.GAIN ON RETURN SIDE OF COIL:
TOTAL SEN.GAIN ON AIR HANDLING SYSTEM:
ZONE SPACE LAT.GAIN: 3,157 BTUH
INFILTRATION LAT.GAIN: 0 BTUH ( 0 CFM)
OUTSIDE AIR LAT.GAIN: 77 BTUH ( 280 CFM)
TOTAL LAT.GAIN ON AIR HANDLING SYSTEM:
TOTAL SYSTEM SENSIBLE AND LATENT GAIN:
TOTAL TONNAGE REQUIRED WITH OUTSIDE AIR:
23,299 BTUH
29,770 BTUH
911 BTUH
30,681 BTUH
3,234 BTUH
33,915 BTUH
2.83 TONS
* ** FULL COMMERCIAL HVAC LOADS
* *
UPS Kent
* * * * * * * * * * * * * * * * * * * * * * ** TOTAL
PROGRAM BY ELITE
03/17/95
BUILDING LOAD S
BUILDING PEAKS IN AUGUST AT 6 PM
SOFTWARE DEVELOPMENT INC * **
* ** WASHINGTON * **
PAGE 16
UMMARY * * * * * * * * * * * * * * * * * * * * * **
BLDG. LOAD AREA SEN.
DESCRIPTIONS QUAN LOSS
%TOT
LOSS
ROOF
WALL
GLASS
1,372
1,548
378
LAT.
GAIN
+ SEN.
GAIN
'= TOTAL *TOT
GAIN GAIN
5,177 10.11
8,345 16.30
21,596 42.18
O 3,908
O 2,816
0 20,591
3,908 5.90
2,816 4.25
20,591 31.10
SKIN LOADS 3,298
35,118 68.60
O 27,315
27,315 41.25
LIGHTING
EQUIPMENT
PEOPLE
PARTITION
VENT 0
INFL 187
DRAW -THRU FAN
BLOW -THRU FAN
SUPPLY DUCT
RETURN DUCT
3,126
2,084
23
1,620
460
0
.0 0.00
O 0.00
O 0.00
5,346 10.44
O 0.00
10,731 20.96
O 0.00
0 0.00
O 0.00
0 0.00
0
0
5,187
0
-414
0
0
0
0
0
11,728
7, 817
6,199
3,564
499
0
4,318
0
0
0
11,728 17.71
7,817 11.81
11,386 17.20
3,564 5.38
85 0.13
0 0.00
4,318 6.52
0 0.00
0 0.00
0 0.00
BUILDING TOTALS
51,195 100.00 4,773
61,440
66,213 100.00
BUILDING SUMMARY
LOAD DESCRIPTIONS
SEN. %TOT LAT.
LOSS LOSS GAIN
+ SEN.
GAIN
= TOTAL
GAIN
%TOT
GAIN
VENTILATION
INFILTRATION
ZONE LOADS
PLENUM LOADS'
FAN & DUCT LOADS
O 0.00
10,731 20.96
40,464 79.04
.0 0.00
O 0.00
-414
0
5,187
0 .
0
499
0
56, 623
0
4,318
85 0.13
0 0.00
61,810 93.35
0 0.00
4,318 6.52
BUILDING TOTALS 51,195 100.00
4,773
' 61,440
66,213 100.00
TOTAL BUILDING SUPPLY AIR (BASED ON A 20.9 TD):
TOTAL BUILDING VENT AIR (16.76% OF SUPPLY):
TOTAL CONDITIONED AIR SPACE:
SUPPLY AIR CFM /SQ.FT. OF CONDITIONED SPACE:
SQ.FT OF CONDITIONED AIR SPACE PER TON:
TONNAGE PER SQ.FT OF CONDITIONED AIR SPACE:
TOTAL HEATING REQUIRED WITH OUTSIDE AIR;
TOTAL TONNAGE REQUIRED WITH OUTSIDE AIR:
2,743
460
2,084
1.3162
377.6902
0.0026
CFM
CFM
SQ.FT
CFM / SQ.FT
SQ. F..T /TON
TONS / SQ.FT
51.20 MBH
5.52 TONS
(
* ** FULL COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC * **
* ' * * ** WASHINGTON * **
UPS Kent 03/17/95 PAGE 13
* * * * * * * ** AIR SYSTEM # 1 (Package Gas /Electric) TOTAL LOAD SUMMARY * * * * * * * **
AIR HANDLER DESC: Package Gas /Electric WITH CV (PROPORTION) TERMINALS
SUPPLY AIR FAN: DRAW -THRU WITH PROGRAM ESTIMATED HORSEPOWER OF 0.88 HP.
FAN INPUT: 50% COMBINED FAN AND MOTOR EFF. WITH 2.00 IN WATER ACROSS THE FAN
SENSIBLE HEAT RATIO: 0.94 THIS SYSTEM OCCURS 1 TIME(S) IN THE BUILDING
AIR SYSTEM PEAK TIME: 6 PM IN AUGUST
OUTDOOR CONDITIONS: 79 DB, '65 WB, 71.23 GRAINS
INSIDE: 78 DB, 50% RH
SUMMER: VENT CONTROLS OUTSIDE AIR WINTER: NONE CONTROLS OUTSIDE AIR
ZONE SPACE SEN.LOSS:
INFILTRATION SEN.LOSS:
OUTSIDE AIR SEN.LOSS:
SUPPLY DUCT SEN.LOSS:
RETURN DUCT SEN.LOSS:
TOTAL SYSTEM SEN.LOSS:
23,074 BTUH
4,821 BTUH
0 BTUH (
0 BTUH
0 BTUH
84 CFM)
0 CFM)
SUPPLY AIR: 27,895 / (0.986 X 1.08 X 30) _ ( 874 CFM)
WINTER VENT OUTSIDE AIR (0.00% OF SUPPLY): ( 0 CFM)
ZONE SPACE SEN.GAIN: 28,045 BTUH
INFILTRATION SEN.GAIN: 0 BTUH ( 0 CFM)
DRAW -THRU FAN SEN.GAIN: 2,195 BTUH
SUPPLY DUCT SEN.GAIN: 0 BTUH
TOTAL SEN.GAIN ON SUPPLY SIDE OF COIL:
SUPPLY AIR: 30,240 / (0.986 X 1.10 X 20) = ( 1,395 CFM)
SUMMER VENT OUTSIDE AIR (12.9% OF SUPPLY): ( 180 CFM)
RETURN DUCT SEN.GAIN: 0 BTUH
RETURN PLENUM SEN.GAIN: 0 BTUH
OUTSIDE AIR SEN.GAIN: 195 BTUH ( 180 CFM)
BLOW -THRU FAN SEN.GAIN: 0 BTUH
TOTAL SEN.GAIN ON RETURN SIDE OF COIL:
TOTAL SEN.GAIN ON AIR HANDLING SYSTEM:
ZONE SPACE LAT.GAIN: 2,030 BTUH
INFILTRATION LAT.GAIN: 0 BTUH ( 0 CFM)
OUTSIDE AIR LAT.GAIN: -162 BTUH ( 180 CFM)
TOTAL LAT.GAIN ON AIR HANDLING SYSTEM:
TOTAL SYSTEM SENSIBLE AND LATENT GAIN:
TOTAL TONNAGE REQUIRED WITH OUTSIDE AIR:
27,895 BTUH
30,240 BTUH
195 BTUH
30,435 BTUH
1,868 BTUH
32,303 BTUH
2.69 TONS
C:•
* ** FULL COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC * **
* . * * ** WASHINGTON * **
UPS Kent 03/17/95 PAGE 14
* * * * * * * * * * ** AIR SYSTEM # 2 (Package Gas /Electric) ZONE SUMMARY * * * * * * * * * * **
ZN. ZONE - DESCRIPTION FLOOR HTG.LOSS SEN.GAIN LAT.GAIN HTG.CFM CLG.CFM
NO. PEAK TIME & MONTH AREA O.A. CFM O.A. CFM EXH. CFM CFM /SF. CFM /SF.
5 TRAINING
6 PM AUGUST
6 MANAGER
6 PM AUGUST
448 11,922 15,279 2,706 373 697
0 240 0 0.83 1.56
180 3,576 4,903 451 112 224
0 40 0 0.62 1.24
7 MEN'S 256 3,684 4,386. 0 115 200
4 PM JUNE 0 0 0 0.45 0.78
8 WOMEN'S 144, 2,240 2,716 0 70 124
3 PM JUNE 0 0 0 0.49 0.86
9 HALL UP 120 1,877 2,263 ' 0 59 103
3 PM JUNE 0 0 0 0.49 0.86
ZONE PEAK TOTALS
TOTAL ZONES: 5
1,148 23,299 29,547 3,157 729 1,348
0 280 0 0.64 1.17
* ** FULL COMMERCIAL HVAC LOADS PROGRAM BY ELITE SQFTWARE DEVELOPMENT INC * **
* * * ** WASHINGTON * **
UPS Kent
03/17/95 PAGE 15
* * * * * * * ** AIR SYSTEM # 2 (Package Gas /Electric) TOTAL LOAD SUMMARY * * * * * * * **
AIR HANDLER DESC: Package Gas /Electric WITH CV (PROPORTION) TERMINALS
SUPPLY AIR FAN: DRAW -THRU WITH PROGRAM ESTIMATED HORSEPOWER OF 0.85 HP.
FAN INPUT: 50% COMBINED FAN AND MOTOR EFF. WITH 2.00 IN WATER ACROSS THE FAN
SENSIBLE HEAT RATIO: 0.91 THIS SYSTEM OCCURS 1 TIME(S) IN THE BUILDING
AIR SYSTEM PEAK TIME: 5 PM IN AUGUST
OUTDOOR CONDITIONS: 81 DB, 66 WB, 72.99 GRAINS INSIDE: 78 DB, 50' RH
BECAUSE OF THE DIVERSITY IN ZONE, PLENUM, AND VENT. LOADS, THE ZONE SENSIBLE
PEAK TIME IN AUGUST AT 6 PM IS DIFFERENT FROM THE TOTAL SYS. PEAK TIME
HENCE, THE AIR SYSTEM CFM WAS COMPUTED USING A ZONE SEN. LOAD OF 28,576
SUMMER: VENT CONTROLS OUTSIDE AIR WINTER:. NONE CONTROLS OUTSIDE AIR
ZONE SPACE SEN.LOSS:
INFILTRATION SEN.LOSS:
OUTSIDE AIR SEN.LOSS:
SUPPLY DUCT SEN.LOSS:
RETURN DUCT SEN.LOSS:
TOTAL SYSTEM SEN.LOSS:
17,389 BTUH
5,910 BTUH
0 BTUH
0 BTUH
0 BTUH
SUPPLY AIR: 23,299 / (0.986 X 1.08 X 30) = (
WINTER VENT OUTSIDE AIR (0.00% OF SUPPLY):
ZONE SPACE SEN.GAIN: 27,647 BTUH
INFILTRATION SEN.GAIN: 0 BTUH
DRAW -THRU FAN SEN.GAIN: 2,123 BTUH
SUPPLY DUCT SEN.GAIN: 0 BTUH
TOTAL SEN.GAIN ON SUPPLY SIDE OF COIL:
SUPPLY AIR: 30,699 / (0.986 X 1.10 X 21) -
SUMMER VENT OUTSIDE AIR (20.8* OF SUPPLY):
RETURN DUCT SEN.GAIN: 0 BTUH
RETURN PLENUM SEN.GAIN: 0 BTUH
OUTSIDE AIR SEN.GAIN: 911 BTUH
BLOW -THRU FAN SEN.GAIN: 0 BTUH
TOTAL SEN.GAIN ON RETURN SIDE OF COIL:
103 CFM)
0 CFM)
730 CFM)
0 CFM)
0 CFM)
1,348 CFM)
280 CFM)
280 CFM)
23,299 BTUH
29,770 BTUH
911 BTUH
TOTAL SEN.GAIN ON AIR HANDLING SYSTEM: 30,681 BTUH
ZONE SPACE LAT.GAIN: 3,157 BTUH
INFILTRATION LAT.GAIN: 0 BTUH
OUTSIDE AIR LAT.GAIN: 77 BTUH
TOTAL LAT.GAIN ON AIR HANDLING SYSTEM:
TOTAL SYSTEM SENSIBLE AND LATENT GAIN:
TOTAL TONNAGE REQUIRED WITH OUTSIDE AIR:
0 CFM)
280 CFM)
3,234 BTUH
33,915 BTUH
2.83 TONS
•
* ** FULL COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC * **
* * * ** WASHINGTON * **
UPS Kent 03/17/95 PAGE 12
* * * * * * * * * * ** AIR SYSTEM # 1 (Package Gas /Electric) ZONE SUMMARY * * * * * * * * * * **
ZN. ZONE - DESCRIPTION FLOOR HTG.LOSS SEN.GAIN LAT.GAIN HTG.CFM CLG.CFM
NO. PEAK TIME & MONTH AREA O.A. CFM O.A. CFM EXH. CFM CFM /SF. CFM /SF.
1 STAFF OFFICE #2
6 PM SEPTEMBER
2 MGR.
6 PM SEPTEMBER
3 CENTER #2
6 PM AUGUST
4 HALL
2 PM SEPTEMBER
ZONE PEAK TOTALS
TOTAL ZONES: 4
260 7,015
0
130 2,422
0
322 11,307
0
7,442 677 220 343
60 0 0.85 1.32
3,491 451 76 161
40 0 0.58 1.24
12,145
80 ,
224 7,151 7,209
0 0
936 27,895 30,287
0 180
902 354 559.
0 1.10 1.74
0 224 332
0 1.00 1.48
2,030
874 1,395
0 0.93 1.49
•
* ** FULL COMMERCIAL HVAC LOADS PROGRAM BY ELITE SOFTWARE DEVELOPMENT INC * **
* * * ** WASHINGTON * **
UPS Kent 03/17/95 PAGE 16
* * * * * * * * * * * * * * * * * * * * * * ** TOTAL BUILDING LOAD SUMMARY * * * * * * * * * * * * * * * * * * * * * **
BUILDING PEAKS IN AUGUST AT 6 PM
BLDG. LOAD AREA
DESCRIPTIONS QUAN
SEN. %TOT
LOSS LOSS
LAT.
GAIN
+ SEN.
GAIN
xo TOTAL %TOT
GAIN GAIN
ROOF
WALL
GLASS
1,372
1,548
378
5,177 10.11
8,345 16.30
21,596 42.18
0 3,908
0 2,816
0 20,591
3,908 5.90
2,816 4.25
20,591 31.10
SKIN LOADS 3,298 35,118 68.60 0 27,315
27,315 41.25
LIGHTING
EQUIPMENT
PEOPLE
PARTITION
VENT 0
INFL 187
DRAW -THRU FAN
BLOW -THRU FAN
SUPPLY DUCT
RETURN DUCT
3,126
2,084
23
1,620
460
0
0 0.00
0 0.00
0 0.00
5,346 10.44
0 0.00
10,731 20.96
0 0.00
O 0.00
0 0.00
0 0.00
0
0
5, 187
0
-414
0 •
0
0
0
0
11,728
7,817
6,199
3,564
499
0
4,318
0
0
0
11,728 17.71
7,817 11.81
11,386 17.20
3,564 5.38
85 0.13
0 0.00
4,318 6.52
0 0.00
O 0.00
O 0.00
BUILDING TOTALS
51,195 100.00 4,773
61,440 66,213 100.00
BUILDING SUMMARY
LOAD DESCRIPTIONS
SEN. %TOT LAT.
LOSS LOSS GAIN
+ SEN.
GAIN
TOTAL %TOT
GAIN GAIN
VENTILATION
INFILTRATION
ZONE LOADS
PLENUM LOADS
FAN & DUCT LOADS
O 0.00
10,731 20.96
40,464 79.04
0 0.00
0 0.00
-414
0
5,187
0
0
499
0
56,623
0
4,318
85 0.13
0 0.00
61,810 93.35
O 0.00
4,318 6.52
BUILDING TOTALS
51,195 100.00 4,773
61,440 66,213 100.00
TOTAL BUILDING SUPPLY AIR (BASED ON A 20.9 TD):
TOTAL BUILDING VENT AIR (16.76% OF SUPPLY):
TOTAL CONDITIONED AIR SPACE:
SUPPLY AIR CFM /SQ.FT. OF CONDITIONED SPACE:
SQ.FT OF CONDITIONED AIR SPACE PER TON:
TONNAGE PER SQ.FT OF CONDITIONED AIR SPACE:
TOTAL HEATING REQUIRED WITH OUTSIDE AIR:
TOTAL TONNAGE REQUIRED WITH OUTSIDE AIR:
2,743 CFM
460 CFM
2,084 SQ.FT
1.3162 CFM /SQ.FT
377.6902 SQ.FT /TON
0.0026 TONS /SQ.FT
51.20 MBH
5.52 TONS
METAL NOTES
t11AI�NIBI .
1. U A ACI Men)ONHAMADAMOMS
C
UOI AS altar • 1' 5.1., MEAN A N'RN• SIREN•
Le
ANAi. mini' Nell l• SOUND wa OIVINO A� ri*siiimw Or
stair. DIICTBOAMlaARISMNOR .
ilia *aN away? Ooo,DgUnaw wan T)SAiumma111RM,
401Daz,DRAIVRICM MOMMar1IOVMH
MO PICAM CSNNOIS N ITO LAYOUT MUST BE
SY PRIREIMORINO 0wMTMMCT.
S. 0 L,,a auum DOR MEM uostf' CEILING MMUS
HIKNITTO 4 Wig mammas. RBCTANmIMR Duct *wows saw. es maw
TYPE WI IIAJLI. RADIUS THROAT anima RAIDS MEOWS MAY SR
TMNDDOWNTOAMBMt1%MIMII ALIMS TH RESAT. WISE SPACE
COPNMANTS DO NOT WOW AT LEASE HMS RADIUS, USE SQUARE
a.fs ovum u ms TURNING VANS MALI= IN EVERY
*OMITOP PACNAOBDAaCONBmONING SYS'RSMS
A
SUPPLY DItalaUTIONMal Hamm" Am coil:110NER8 AND AIR
CONDITSOMNO UNITS TO DIMMINs SHALL UM FOLLOWS:
A • Imam. moils vacMa00F1O /&cinanEHtatnIIIMANOUMR
DENT A *P AND
B. Si MLYA*RDuiRiEWKI ( DUCTWORK FROM VERTICAL MUSS TO
OMPUMRBSHMIL UNLINID, CAI.vMenm %STALDUCTWIORK
WM,DUCTNRAPASwBCEMD, iu*a RDSHEEIMRITALWIORR
INDICATED. PAMICATBANDg1TAU PR MUM 1.3' PRESSURE
CLAIRVICAT10Nr
C. PLEXTRUIDUCTRUNOMSTOIMPUMEM MALL HAVE r INSULATION.
US UNIMU LATw POMACE MPS FITTINGS WHERE FITTIJOS ARs
INDICATED M EIOD ROUND DUCT.
•
a MJORERR11101 MR TS DUCTED. WN[URN AIR D(IcTNODKsn*aes
THE SAWN IIMPAILY(NS'rAND "C• AEONS).
{. • 10¢ALT(ANDT111110iE1AligtaVe T10wKt ir
} y
1�tA1'a11s''
flea iMNI +:
'1iARD'C01lrcnf sTONING=CAN• DONOTUSE •
ILE >mNDUCTINTICIUMEEIQLWSTfttfTOO. PAERICATBANpNST/dS
PER SMADIAI rIEJES MRCILASNPICATTON.
' F1RIlDAMP1RR • #
7. MRDAMNSRIaIALL RSMTN MR STREAM TYPE, UNLESS NOTED
BUCTCOI' tation * •
t .suet weinaii ormarmucrearf =mo s:
A .sum miscA' IN Ducts, &vacua /month CWT. ANDWRA►PED
F/oavr1aFLt isDl ,cT$11ALLeaulnaANDMIMED114131
• s. taataiDucrttamance sHAa3 RUSTEDUL723,CIA181
NMARA EME ORATOIGiSSBTHAN2 7,APOSMOKEDEVELOPED
RATERINGT OVER 50.
C. DOMINO: NOT UMW.
D. SOUND LEHR: l•'nnCC, 11/2 Ls. Deafly MERMAID DUCT LINER
PATH BLACKMATPACN0. 2010I111UNVI18• ZIACOIJl o. 1
L RXw tom Ear: I• mac, atskut aouteFIBERaI/RSs
DUCT
3011/43-MANVILISICCRO•AIRB•.
F. 14UAT'RPLBilWUCR TIIBRMAfLIIIiS 1 L
0. UNNSWATZDFILXDUCT: 1I1wWLEXSzp
H. DUCrflea to at 1' THICK,1.112 LB. marry FIBERGLAS! Wmm P.S.R.
VAPORSARRNERJACKET.
L DUCTINSU.ATTON: 29111131 PHEROLASS. MINIMUM a LB. DENSITY
PATH VAPOR IARRIR AND WEATHERPROOF UCYBT.
9. ALL DUCTWORR SHAUN SEALED AS FOL OW&
A. ON LOw FRLNJRE DU(AW ORK STANDARD GRAY DUCT TAPE SHALL BE
DIED TO MAL ALL TRANSVERSE MINTS. LOW PRESSURE
TANW'n1DMAL JOINS DO NOT REQUIRE A T98 SEAL-
t
• V.
s�:t: •
/oto
93ger
66/'4W6 GIs
GISMOVER
ifee Oa'
.' ILA I- _iL ' Il
N.l
1004-i'U054/31
A444N4Nta$r
GO
- /4non°
SECOND /FLOOR
e.Y' =/ a•
J
• J6�
r t ti
1
in 4._95
40*FM
isn,.:• -
y6C. 27,4,F;;i,7
lAvic rc 1147414
Jr
,
�'.1
7t1Js�riy
este
'-t
CE-7..4.5e 44
m
ions \.r/ .r6 (4 W
?*/C/9i'
I>A 1-r_ -r.a
00", 10- UP )
?I4
hei q5- 0050
11IIIk ewtw raa/SY
j
/DTI
rt.s.
Ji . _
awe. FIRST s' OP Su'Pw 1 R6TUrtn
F /esr FL O Oaf'
aB t-/e •
AT ton 1,
QINIIRA. NOM
1. ALL MOD TO NAVE 31` CLEARANCE IN PROM' OP AiR CONDfllONMo
UNiT AND OTHR MECHANICAL UQIJ4PM VIT ACCESS PANELS FOR
SERVICING.
OENERM, CONnnAL'NORCODNDINATN)NI
3. ACCESS TOM DAMSR&',ALANCINO DAMPERS, DUCT ACCESS PANELS,
AND BlUiPMENT MIGHT TNECEUNO SHALL REASSURED AND PROVIDED
BY THE Of HRRAL CONTRACTOR. LANE CEILINGS CONSTITUTE SUITABLE
ACM& SHEET MUM, WOODEN, ETC, WALLS OR CEILINGS WOULD
REQUITE A MRMIUM fl23' /ALCOR (OR EQUAL) ACCESS DOOR OP SIMILAR
RATING TO WALLOW'S() PROVIDED BY THE GENERAL CONTRACTOR.
LOCATION OP SUCH ACCESS DOORS WILL RE COORDINATED BY
MECHANICAL CONTRACTOR.
3. CUTI'1NQ PRAMINO, PATCHING, SEALMO, AND PAINTING OF WALL, CEILING.
ROOF, AND FLOOR OPENINGS SHALL BE BY GENERAL CONTRACTOR.
4. ROOFTOP AIR CONDITIONERS MR A*MSNED PATH FACTORY CURBS
REQUIRING BY GENERAL�CONTRMACTCR, CURB SHALL DE ASSEMBLED SET IN4PLAOCE
BY MECHANICAL CONTRACTOL LEVELING, TRUING, AND FASTENING TO
ROOF STRUCTURE SHALL BE BY GENERAL 01411RACTDR. AS FOLLOWS:
A MAXIMUM ALLONABLB SLOPE END•TO•END 1314"
B. MAXIMUM ALLOWABLE SLOPE SIDDTO•SIDB IS I/2"
C. TOP OP CURB MUST BE mtm DIM TO PROVIDE ACCEPTABLE MATING
ANDMALMO SURFACE
D. ROOF CURB MUST BE SECURELY FASiENED TO STRUCTURAL SUPPORT
MINIMUL
S. THE GENERAL CONTRACTOR SHALL UNDER CUR' THE FOLLOWING DOORS:
22A, 24A.
ELECTRICAL COORDINATION:
6L LOCKER ROOM BXaAUSTSHALL BE CONTROLLED BY A SEPARATE WALL
SWITCH LOCATED ON THE WALL OUiaiDB THE LACIER ROOMS.
ELECTRICAL 1RICAL CONTRACTOR SHALL INSTALL SWITCH AND DO ALL WIRING.
7. BLBCI*ICALCO•NTRACTOR SHALL PROVIDE SERVICE POWER AT
711KM1EM030IAIQCRAL EQUIPMENT IN ACCORDANCE MTh 1991 UMC. AND CITY OF
nags � yeas so
A � Mt
10. PIE SHALL BIfTA1aAC1 >fASAlBTRAPATEACHROOPTOPAIR
CONDmONDIO Met MBRMUM TRAP DEPTH SHAD BE rue DEPTH).
11. OAS HMO FOR ROOFTOP AM CONDITIONING UNR8 SHALL BE BY
PLUM E° LOCATE OAS PIPE SERVOIO R3aSTINOUPS SPACE
AID.TIE 'MOTTOS UNIE
STRUCTURAL COMMINATTONt
12. UNIT VAIKIN'S AND LOCATiC 411 HAVE BEEN COORDINATED EMIT E
81EUCTURALv401 NHRTO DETERMINE BUILDINGSTRUCTURAL
ADEQUACY. RRiS NECESSARY TO RELOCATE AUNIT .RE000RDiNATiON
WITH THESE MIMES MILL BE NECESSARY.
13. ALL EQUiPMrfiATIDPIPING WHICH 11 TO BE SUSPENDED PROM ROOF
MALL BESUIFIN1ND FROM OWLMLI WHERE PRACTICAL, OR FROM
•SUER. DONOTSUMENC PROM RRPIRMRS. FOLLOW TRUSS
MANUFACTURER'S MU IMENTSWHENATTACHING HANGERS TO
,.4.
'
atitanianta. mniumaticiasuut
1 ar it*AYMT•URCILMo)
4+CTJmmuu TAIR "Amour on, WnHFILQPAi Lrat
• S WIDLAYINMODU,E.
-
•M1rpNBRAS;a
IIetaiii01S!�inpaM ! • 4 .
1taf } LA+O,MIIEBIAR1aN10J! ' .
�awCRAT1RL0UVR
aot AIdRICOMTeemanuTBp
• same 1'amoOaa
RO • tioloTlrracia
SAME AS R.A.O. ABOVE
TRAMPER MULS &
T.O. TRANSFERORKLB
SAME ASRA.O.ABOVE
NOTfa MARE AND MODEL NUMBERS ARS UST M) ONLY TO INDICATE
POIORMANCE AND STYLI EQUAL PRODUCTS BY 011MR
MAMWACTURERS MAY BE SUISTITUlED.
//NG:9 ✓9e Awe ;vex"'
./4q5/7%. 119 4w1-1"C•C'
.4104' 11/4,0 s.'s
BETE A'4 �. v Pc
SCOPE OF WORK
NOT& THE TIMM"PROUIDrMBANS TORJRMBa AND INSTAL..
1. PROVIDE TWO (2) NEW ROOFTOP, OM/ELECT1RIC AIR CONDmoMNO. PROVIDE NEW
DIMINUTION DUCTWORK, FLBXC RUNDUTS, CEIUNO DIFFUSERS, AND RETURN GRILLES
AND AS SHOWN TO ACCOMMODATE NEW TENANT LAYOUT.
2. PROVIDE ONE (1) NEW ROOFTOP EXHAUST PAN TO EXHAUST TOILET AND LOCKER ROOMS.
1. PROVIDE TWO ( 2)7•DAY,PROCtwMABLETHERMOSTATS.
4. PERFORM CHECK. TEST. AND START ON NEW AiR CONDIUONINO UNITE. AiR BALANCE
SYSTEMS TO M 10 OFCPMI SHOWNONDRAWMOS.
3. GAS PIPING FOR AIR CXNDMONINO UNITS SHALL BE BY PLUMBiNOCONTRACTOR.
PROJECTNA/4E:
JURISDICTION:
ASSESSOR NUMBER:
BUILDING PERMIT
PROJECT ADDRES3:
OWNER
TENANT:
GENERAL CONTRACTOR:
MJCH. CONTRACTOR:
PERMIT INFORMATION
TENANT IMPROVEMENT POR UNTIED PAIICEL PAS ' SERVICE, INC. (UPS)
CITY OP TUICWILA
261XOIA013
595.0031
550 ANDOVER PARK WEST
TUCWI.A, WA
*OFFS, INC.
SOS HOWELL STREET
SEATTLE, WA 91101
UNITED PARCEL SERVICE
SOA
PARSLEY ENOINEBRENQ INC.
4620- 232ND AVENUE NE
REDMOND. WA 91053
(206)1364926
CONTACT: BONN i4 PARSLEY. P8
WA STATE CONTRACTOR LC. f: PASL81077•MK
EQUIPMENT SCHEDULE
escataanotatausas
AC-1, 2 NOMINAL 3 TON. PACKAGE ROOFTOP OASiELECTIUC AIR CONDMONINO
UNIT, YORK MODEL D3000361I041. COOLING CAPACITY AT 934 F
owDOORS.10'F DM/BULB/67W WET BULB HITERDIG INDOOR COIL: 37.6
MEIN TOTAL 31.6 MBH SENSIBLE COOLING EFJR a 91 SEER • 10.10.
HEATING CAPACITY OF 50 MIan INPUT, 41 SUN OUTPUT. 1,200 CFM SRAPLY
AIR AT 0.70. ESP, LOW SPEED. 1/2 MDR. 460440, 12.3 MCA, IS IRE 15 AMP
MAX HACR BREAKER. WEIORT -124 LEE.
OPTIONS AND ACCESSORIES: FACTORY ROOP CURB, 2S% OUTSIDE AIR
INTAKE HOOD WITH FABRIC BACKDRAFT DAMPER.
THERMOSTATS
HONEYWELL T7200A1006.
damn PANS
EF•1 ROOFTOP, CENTRIFUGAL EXHAUST FAN. OREBNIiECC MODEL 0.70.D. 273
(NMI00.2S' SP; 1.550RMR;4.7/TONES. 11W1160;113010.
FIELD FABRICATED. 2ttl2 WOOD CURB BY GENERAL CONTRACTOR 1r a 13"
WITSIDEDMENSION.
HAR 131995