HomeMy WebLinkAboutPermit EL08-1153 - NEWMAN BURROWSNEWMAN BURROWS
1000 ANDOVER PK E
ELO8-1 153
Parcel No.:
Address:
Suite No:
CitAbf Tukwila •
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
2623049101
1000 ANDOVER PK E TUKW
ELECTRICAL PERMIT
Permit Number:
Issue Date:
Permit Expires On:
EL08 -1153
09/11/2008
03/10/2009
Tenant:
Name:
Address:
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
NEWMAN BURROWS
1000 ANDOVER PK E , TUKWILA WA
1006 ANDOVER ASSOCIATES
C/O CABLE MANAGEMENT , 9844 40TH AVE S
KEVIN LEWIS
804 W MEEKER ST STE 102 , KENT WA
A C ELECTRIC SERVICE INC
804 W MEEKER ST STE 102 , KENT WA
Contractor License No: ACELESI025DF
Phone:
Phone: 253 - 852 -0225
Phone: 253 852 -0225
Expiration Date: 03/06/2010
DESCRIPTION OF WORK:
INSTALL NEW 600 AMP SERVICE 480V
Value of Electrical:
$26,000.00 Fees Collected:
Type of Fire Protection: National Electrical Code Edition:
Electrical Service provided by: PUGET SOUND ENERGY
Permit Center Authorized Signature:
$635.50
2005
Date: PI (Uc' 101)
I hereby certify that I have read and amiied this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied thll whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign and obtain this electrical permit.
Signature:
Print Name:
IL
P *v E-TTE
Date: v` L I I l G
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: EL -4/07
EL08 -1153 Printed: 09 -11 -2008
Parcel No.: 2623049101
Address:
Suite No:
Tenant:
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
1000 ANDOVER PK E TUKW
NEWMAN BURROWS
PERMIT CONDITIONS
Permit Number:
Status:
Applied Date:
Issue Date:
EL08 -1153
ISSUED
08/21/2008
09/11/2008
1: ** *ELECTRICAL * **
2: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical Inspector
at each work site.
3: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical Inspector.
4: All electrical work shall be in accordance with NFPA 70 - NEC, and requirements for electrical installations, Chapter
296 -46B WAC.
5: When any portion of the electrical installation is to be hidden from view by permanent placement of parts of the
building, such equipment shall not be concealed until it has been inspected and approved by the Electrical Inspector.
6: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any violation
of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related documentation that
presumes to grant this authority are therefore not valid.
7: Any change in the scope of work described by the electrical work permit shall require additional work permits. Where
approved plans have been issued, revisions to the plans and additional review may be required.
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and
ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local
laws regulating construction or the performance of work.
Signature:
Print Name:
tW%iv Piaue TIE
Date:
doc: Cond -Elec
EL08 -1153 Printed: 09 -11 -2008
•
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Btvd., Suite 100
Tukwila, WA 98188
httal/www.ci.tukwila.wa.us
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
SITE LOCATION
King Co Assessor's Tax No.: 240-10 —1 — 410
Site Address: I G U t:2) AN.) L1 L CQ_ ai (2. U.. E t.S t Suite Number: Floor.
Tenant Name: k Ct.1Jme.s%U Btt2Q6(. New Tenant: [l Yes ❑..No
Property Owners Name: J1 i M l ►.a ct I C. / F tOALI leQ A SSC) C
Mailing Address: 9 � 1 DS AL' E SG 5L^Ai* 1 ' L A ° eb l 1$
City
State Zip
CONTACT PERSON - Who do we contact when your permit is ready to be issued
Name: L&- Day Telephone: )-S - 5 Z ^ b -2. 2 5
G
Mailing Address: 1 L , EE �t'� � s� L \ b L l �i A °1 `46
City State Zip
E -Mail Address: Fax Number. Z5 3- g (3 - 5 811
ELECTRICAL CONTRACTOR INFORMATION
Company Name: r 1 C f LE L + Q 1 LsQ t L f . L L.
Mailing Address: il)O L. . MEE VECL IG Z ktt LOO G 9)032_
1 City Stets Zip
Contact Person: K L� 11� T . L I Day Telephone: 2 S3 " S S -�.-- C)2 ? . 5
E -Mail Address: Fax Number: 2_.5 3 -' 13- 5 911
C o n t r a c t o r Registration Number: A L E 2.5 D F Expiration Date: k 2.3 ` 1 O
Valuation of Project (contractor's bid price): $ 2_61 b IDL &
Scope of Work (please provide detailed information): �10 SA A L k kk1..) &) A (V .SL U 1 L E
eqQV
Will service be altered? ❑ Yes No
Type of Use: LDrnrn €Q L
Type of work:
[r New ❑ Addition
❑ Low Voltage ❑ Generator
Property Served by:
12( Puget Sound Energy
❑ Seattle City Light
Adding more than 50 amps? 0' Yes ❑ No
❑ Service Change
❑ Fire Alarm
HAApplicatiomVFo Appfimtiom On tme14-2007 - Electrical Ewell Appliearim.doc
m
❑ Remodel ❑ Tenant Improvement
❑ Telecommunication ❑ Temporary Service
Page 1of2
RESIDENTIAL
PIEW RESIDENTIAL SERVICEt
❑ New single family dwellings $140.00
(including an attached garage)
❑ Garages, pools, spas and outbuildings $75.00 ea
❑ Low voltage systems
(alarm, furnace thermostat) $55.00 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
❑ Service change or alteration $75.00
(no added/altered circuits)
❑ Service change with added/altered circuits $75.00
number of added circuits $10.00 ea
❑ Circuits added/altered without service change $50.00
(up to 5 circuits)
❑ Circuits added/altered without service change $50.00
(6 or more circuits) $7.00 ea
❑ Meter /mast repair $65.00
❑ Low voltage systems $55.00
(alarm, furnace thermostat)
MULTI- FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract
MISCELLANEOUS FEES
❑ Temporary service (residential) $58.00
❑ Temporary service (generator) $75.00
❑ Manufactured/mobile home service $80.00
(excluding garage or outbuilding)
❑ Carnivals $75.00
Number of concessions $10.00 ea
PERMIT APPLICATION NOTES -
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER ORE,,LEC I RICAL CONMC FOR:
Signature: .`` 4.144
Print Name: 'KEN/
Mailing Address: S ME 6 kez \- . "Sid" 10 -7-
Date: QS- ZO `OB
Day Telephone: 2.53 -
k -c* WF 82031
City State Zap
IDate Application Accepted: 60...)4
Date Application Expires: Y� _3 7
Staff Initials:
H :MyplicatiansWon - Applicah On lbne.4 -2007 - Elahical Mnat Applicanondnc
bb
Page 2 of 2
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
Parcel No.: 2623049101
Address: 1000 ANDOVER PK E TUKW
Suite No:
Applicant: NEWMAN BURROWS
RECEIPT
Permit Number: EL08 -1153
Status: PENDING
Applied Date: 08/21/2008
Issue Date:
Receipt No.: R08 -03019
Initials: WER
User ID: 1655
Payment Amount: $635.50
Payment Date: 08/21/2008 11:01 AM
Balance: $0.00
Payee: AC ELECTRIC
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 10926 635.50
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
ELECTRICAL PERMIT - NONR
ELECTRICAL PLAN - NONRES
000.322.101.00.0 508.40
000.345.832.00.0 127.10
Total: $635.50
doc: Receiot -06 Printed: 08-21 -2008
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
(Lod -115)
PERMIT NO.
d�-
CITY OF TUKWILA BUILDING DIVISION "
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Project:1401404
5
Type of Inspection: ,QU
Address:
IDoD 1 JE
£
Date Called:
-f�
Special Instructions:
Date Wanted:
01 / I 2
l a
Requester:
Phone No:
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
riA
Inspector:
Date:
Dp t
$60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
. - -�•.�• - Laurie -
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
INSPECTION RECORD
Retain a copy with permit
�(JoY -1153
PERMIT NO.
Project:4 �����w�
Type of Inspection:
7002..
Address:
1000 AJt»i i 6.
Date Called:
Special Instructions:
Date Wanted:
/
77
a:m:
u ster:
Requester:
Phone No:
Approved per applicable codes. Corrections required prior to approval.
•
COMMENTS:
Q.�;. - dbttoze
Betii9mici
Inspector:
AleiS
Date:
09 ti 2- Jd
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 SouthcentercBlvd., Suite 100. Call to schedule reinspection.
Receipt No.:
•ti
- - 1Date:
3
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION g
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Egg - I IS3
Projectt
._ 464 j #60 Izzo
Type of Inspection:
70o2,_
Address:
/O0O k4Pb4K
Date Called:
Special Instructions:
Date Wanted:
/
9 /s
a.m.
p.m.
Requester:
Phone No:
csjApproved per applicable codes. • El Corrections required prior to approval.
COMMENTS:
0.14, serckk
Inspector:
. i ON1/4/6(
Date: 07 /14.-/ch
ri $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
CU
REVISIONS
No changes shall be made to th° crnr^
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new nIP.n s�ihr1 l
and may include additional plan re�fi^1'' ffcs
REVIEWED FOR
CODE COMPLIANCE
�NEC
NFPA
NOB
20'-0*
Of Tu ila
BUILDING DM. I� ON
MA��2.
5 c-l2 TC--R-
Nif
L.T. La
NacL
v :-,P- t 6CGA N. 4 An IZ`7-
x
211
Permit No.,
copy
&OB LL5'S
&; 17: a0;, .117 ;.I la
Approval of construction documents does not authorize
the violation of any adopted code or ordinance. Receipt
of approved Field Copy and conditions Is ac oaried ed:
By
Date:,
11 oc
City of Tukwila
BUILDING DIMSI
OB' 1)53
RECEIVED
AUG 21
PERMIT CENTER
111;
GEXPRO
MARK NELSON
GEXPRO GEAR SPECIALIST
Renton, WA 98092
Email: mark.nelson @gexpro.com
Bill of Material
AC- 600AMP
KEVIN @ AC
Date :
Telephone :
Fax :
Speeds Version :
8/20/2008
425 -254 -7171
425 -254 -7117
V 8.10
WIN Proposal # : 6N5 -M733B
Proposal /Quote Type : Alternative Bid
Item# Qty Description
1 1 Spectra Bolt -On Panel (101)
PANEL 111
Single Section Panel Top Feed Surface Mnt SE Label
3P4W 480Y/277V 65 KAIC Series Rated
800A 3 Pole SKLA8 Main
1 250A 3 Pole SFHA
6 250A 3 Pole SFHA Space
2 200A 3 Pole SFHA
1 125A 3 Pole SFHA
1 Copper Bus Heat Rated
1 Front Hinged To Box
1 Gmd -Box bonded AEG10
1 APB4075D Box
1 APF7523EMDH Front
1 APNB2308FH2B Interior
THIS PANEL WAS SERIES RATED AT 65 KAIC WITH A 800A
SKLA8 MAIN BREAKER. UL SERIES CONNECTED RATINGS
ARE IN PUBLICATION DET -008A.
2 1 Misc Product
1 364811HRTCT
1 6067HEEL
1 121413
E�E�ED-f
CODE CO�p SCE
ORA 70 NBC
'uua
OW ()MOAB
BODING DIMS._
ID.
RECEIVED
RUG 21
PERMIT CENTER
nr�;
Spectra Panelboard
Item 1 PANEL tat
Panel Description
GE Type SBO Panelboard
Qty 1
800 Amp.480Y/277V
3P4W
65 KAIC SC Series Rated
Copper Bus
Nema 1 Enclosure
Surface Mounted
Top Feed
Main Description
Amps: 800 Amp
Poles: 3 Pole
Type: Main Breaker
Cat No.: SKLA36AT0800+
Acc: SRPK800A 600
Rating Pig
3TCAL124
Lug Kit
Lugs: 1- lug/ph 3- cable /lug
300 mcm -750 mcm
Options
- Copper Bus Heat Rated
1 - Front Hinged To Box
1 - Gmd -Box bonded AEG10
Branch Devices
Q y Amps/P Cat#
1 250A/3P SFHA36AT0250+
1 Rating Pig SRPF250A250
1 Lug Kit 3TCAL29
6 250A/3P Spaces
2 200A/3P SFHA36AT0250+
2 Rating Pig SRPF250A200
2 Lug Kit 3TCAL29
1 125A/3P SFHA36AT0250+
1 Rating Plg SRPF250A125
1 Lug Kit 3TCAL29
Remarks
Suitable for service entrance
This panel was Series Rated
at 85 KAIC with a
800A SKLA8 Main breaker
UL Series connected ratings
are in publication DET-008A.
Panel Interior
800A 3P SKLA8
MAIN
Ckt
Type
Amps/P
Type
Amps/P
Ckt
1
SFHA
250/3
SPACE
250/3
2
3
SPACE
250/3
SPACE
250/3
4
5
SPACE
250/3
SPACE
250/3
6
LSPACE
1" 8
250/3
SFHA
200/3
10
9
SFHA
200/3 j
SFHA
125/3
2 X FILLER
• Drawing not to scale
REVIEWED FOR
CODE PA 70 - NEC
City Of Tukwila
BANG
RECEIVED
AUG 21 2008
PERMIT CENTER
Job Name: AC- 600AMP
Prop No:
PO#:
Marks: PANEL H1
6N5 -M733B I GE Req #:
Dated: 08/20/2008
A Interior
1 B Box
IC Front
APNB2308FH2B
APB4075D
APF7523EMDH
Dimensions
75.5 "H x 40"W x 14.25 "D
AC ELECTRIC
SERVICE, INC
Commercial Industrial Residential
804 West Meeker, Suite 102, Kent WA. 98032 Ph.253 -852 -0225 Fx253- 813 -5817
8 -27 -08
City Of Tukwila
6300 Southcenter Blvd, Suite 100
Tukwila, WA. 98188
Attn: Jim Benner
Re: Permit EL08 -1153
Job: Newman Burrows
Per letter for questions that you needed answered.
Service Conductors:
Parallel #350 thhn copper
Fax: 425- 413 -1329
Grounding Electrodes:
2- 5/8 x 8 galv. Ground rods
3/0 copper bonding and ground wire
Bonding to 2" water pipe, 1 1/4" gas pipe & sprinkler pipe
AC Electric Service, Inc.
804 West Meeker — Suite 102
Kent, WA. 98032
INCOMPLETE
LTR #J...__
X153
REVIEWED FOR
CODE COMPLIANCE
O NEC
NPP
City C• �t
f)f Tukwila
LID NG DIVISION
Thank You
Kevin Lewis
AC Electric
RECEIVED
SEP 05 2008
PERMIT CENTER
August 26, 2008
• •
City of Tukwila
Jim Haggerton, Mayor
Department of Community Development Jack Pace, Director
Kevin Lewis
804 West Meeker Street, Suite 102
Kent, WA 98032
RE: Letter of Incomplete Application 11 1
Electrical Permit Application EL08 -1153
Newman Burrows — 1000 Andover Park East
Dear Mr. Lewis,
This letter is to inform you that your permit application received at the City of Tukwila Permit Center on
August 21, 2008 is determined to be incomplete. Before your application can continue the plan review
process the following item from the following department needs to be addressed:
Building Department: Jim Benner, at 206 431 -3679, if you have any questions concerning the
attached comments.
Please address the comment above in an itemized format with applicable revised plans, specifications, and/or
other documentation. The City requires that three (3) sets of revised plans, specifications and/or other
documentation be resubmitted with the appropriate revision block.
In order to better expedite your resubmittal a `Revision Submittal Sheet' must accompany every resubmittal. I
have enclosed one for your convenience. Revisions must be made in person and will not be accepted
through the mail or by a messenger service.
If you have any questions, please contact me at the Permit Center at (206) 431 -3670.
Sincerely,
kg-
Brenda Holt
Permit Coordinator
Enclosures
File: EL08 -1153
P:U'ermit Center\lncomplete Letters\2008\EL08 -1153 Incomplete Ltr # 1.DOC
wer
R2/)/) C....rl,...,.,tar. D.,..r.,.,,...i C..Pfn #11111 . T..L.•,Ib, LI/a..1,:.,..r.,., nplQA . DA.,,..,. 911A_421_2A711 a r,... 111.4 411 2.CAC
• •
Tukwila Building Division
Jim Benner, Electrical Inspector
Building Division Review Memo
Date: August 26, 2008
Project Name: Newman Burrows
Permit #: EL08- 1153
Plan Review: Jim Benner, Electrical Inspector
The Building Division conducted a plan review on the subject permit application. Please address the
following comments in an itemized format with revised plans, specifications and/or other applicable
documentation.
(GENERAL NOTE)
PLAN SUBMITTALS: (Min. size 1 1x17 to maximum size of 24x36; all sheets shall be the same size).
Please include One Line Diagram, Load Summary, and Panel Directories (where applicable)
1. Specify size and type of service feeder conductors.
2. Include grounding electrode system particulars.
Should there be questions concerning the above requirements, contact the Building Division at 206 - 431 -3670.
No further comments at this time.
•
PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: EL08 -1153 DATE: 09 -05 -08
PROJECT NAME: NEWMAN BURROWS
SITE ADDRESS: 1000 ANDOVER PK E
Original Plan Submittal X Response to Incomplete Letter # 1
Response to Correction Letter #
Revision # After Permit Issued
DEPARTMENTS
444/6
Bul ing''Divon�
Public Works ❑
Fire Prevention
Structural
n
Planning Division
Permit Coordinator
u
LI rr
DETERMINATION OF COMPLETENESS: (Tues., Thurs.) DUE DATE: 09 -09 -08
Complete
Comments:
Incomplete
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
LETTER OF COMPLETENESS MAILED:
TUES/THURS R TING:
Please Route Structural Review Required
No further Review Required
n
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
DUE DATE: 10 -07 -08
Not Approved (attach comments) n
Notation:
REVIEWER'S INITIALS: DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents/routing slip.doc
2 -28-02
PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: EL08 -1153
PROJECT NAME: NEWMAN BURROWS
SITE ADDRESS: 1000 ANDOVER PK E
X Original Plan Submittal Response to Incomplete Letter #
DATE: 08 -21 -08
Response to Correction Letter #
Revision # After Permit Issued
DEPARTMENTS:
Btr ng `I44 Ion
Public Works ❑
Fire Prevention
Structural
u
Planning Division
Permit Coordinator
n
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
r
Incomplete
DUE DATE: 08 -26 -08
Not Applicable
Permit Center Use Only n
INCOMPLETE LETTER MAILED: '; 1V-0 LETTER OF COMPLETENESS M
Departments determined incomplete: Bldg 311 Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES/THURS ROUTING:
Please Route n Structural Review Required U No further Review Required
REVIEWER'S INITIALS:
DATE:
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
Notation:
REVIEWER'S INITIALS:
DUE DATE: 09-23-08
Not Approved (attach comments) n
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents/routing slip.doc
2 -28-02
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
REVISION SUBMITTAL
Revision submittals must be submitted in person at the Permit Center. Revisions will not be accepted through
the mail, fax, etc.
Date: l � DR
Plan Check/Permit Number: EL08 -1153
• Response to Incomplete Letter # 1
❑ Response to Correction Letter #
❑ Revision # after Permit is Issued
❑ Revision requested by a City Building Inspector or Plans Examiner
Project Name: NEWMAN EWMAN BURROWS
Project Address: 1000 Andover Park East
Contact Person: Kevin Lewis
Summary of Revision:
PLO- 1p
•
Phone Number: 21 -r C)_
c'
cA. aod (LCk
Z. L ;RTc L
ELL c_1P1 14i;> Z 5f G1nrk 2t�5
tidl L ct Lu I ZL
CITY OF TUKWILA
SEP 052
PERMIT CENTER
Sheet Number(s):
"Cloud" or highlight all areas of revision including date of revision
Received at the City of Tukwila Permit Center by:
Entered in Permits Plus on
9- s--o
\ applications \forms- applications on line\revision submittal
Created: 8 -13 -2004
Revised:
Untitled Page
•
•
Page 1 of 2
Electrical Contractor
A business licensed by L&I to contract electrical work within the scope of its specialty.
Electrical Contractors must maintain a surety bond or assignment of savings account.
They also must have a designated Electrical Administrator or Master Electrician who is a
member of the firm or a full -time supervisory employee.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent
Company
A C ELECTRIC SERVICE
INC
2538520225
804 W MEEKER ST STE
102
KENT
WA
98032
KING
CORPORATION
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Previous License
Next License
Associated
License
Specialty 1
Specialty 2
601858837
ACTIVE
ACELESI025DF
ELECTRICAL
CONTRACTOR
3/6/1998
3/6/2010
CHUTIAM960L8
GENERAL
UNUSED
MASTER ELECTRICIAN INFORMATION
License CHUTIAM960L8
Name CHUTICH, ALAN M
Status ACTIVE
Business Owner Information
Name
Role
Effective Date
Expiration Date
CHUTICH, ALAN
01/01/1980
Bond Information
Bond
Bond
Company
Name
Bond
Account
Number
Effective
Date
Expiration
Date
Cancel
Date
Impaired
Date
Bond
Amount
Received
Date
3
NATIONWIDE
MUTUAL INS
CO
7900313590
03/05/2007
Until
Cancelled
$4,000.00
02/02/2007
https:/ /fortress. wa.gov /lni/bbip/Detai 1. aspx ?License= ACELESI025DF
09/11/2008