HomeMy WebLinkAboutPermit EL08-0151 - WESTFIELD SOUTHCENTER MALL - CHICKEN NOWCHICKEN NOW
2600 SC MALL
FC 11
07-21-08
ELO8-151
CitAf Tukwila •
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206 - 431 -3665
Web site: http://www.ci.tukwila.wa.us
ELECTRICAL PERMIT
Parcel No.: 6364200010
Address: 2600 SOUTHCENTER MALL TUKW
Suite No:
Permit Number: EL08 -151
Issue Date: 06/10/2008
Permit Expires On: 12/07/2008
Tenant:
Name: CHICKEN NOW
Address: 2600 SOUTHCENTER MALL FC -11 , TUKWILA WA
Owner:
Name: WESTFIELD PROPERTY TAX DEPT Phone:
Address: PO BOX 130940 , CARLSBAD CA
Contact Person:
Name: BOB ROBINSON Phone: 253 - 677 -6874
Address: 37936 23 PL S , FEDERAL WAY WA
Contractor:
Name: C & R ELECTRIC INC.
Address: 919 SW 150 ST , SEATTLE WA
Contractor License No: CRELEI *415DW
Phone: 206 937 -3654
Expiration Date: 03/31/2010
DESCRIPTION OF WORK:
NEW ELECTRICAL TO INCLUDE HOOD, REFRIGERATION EQUIPMENT, LIGHTING AND
MISCELLANEOUS ELECTRICAL
Value of Electrical: $22,000.00
Fees Collected:
$553.50
Type of Fire Protection: National Electrical Code Edition: 2005
Electrical Service provided by: PUGET SOUND ENERGY
Permit Center Authorized Signature:
Date:
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied wi wl%fiei ed herein or not.
The granting of t
construch'
Signature:
••-s not pr- :umeto
- o ork. c '�
III _1011_1W., III
Print Name: v7..."32C, 6:2-"e77-1/
ority to violate or cancel the provisions of any other state or local laws regulating
ed to sign and obtain this electrical permit.
Date:
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: EL -4/07
EL08 -151 Printed: 06-10 -2008
• •
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
PERMIT CONDITIONS
Parcel No.: 6364200010
Address: 2600 SOUTHCENTER MALL TUKW
Suite No:
Tenant: CHICKEN NOW
Permit Number: EL08 -151
Status: ISSUED
Applied Date: 02/15/2008
Issue Date: 06/10/2008
1: ** *ELECTRICAL * **
2: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical Inspector
at each work site.
3: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical Inspector.
4: All electrical work shall be in accordance with NFPA 70 - NEC, and requirements for electrical installations, Chapter
296 -46B WAC.
5: When any portion of the electrical installation is to be hidden from view by permanent placement of parts of the
building, such equipment shall not be concealed until it has been inspected and approved by the Electrical Inspector.
6: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any violation
of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related documentation that
presumes to grant this authority are therefore not valid.
7: Any change in the scope of work described by the electrical work permit shall require additional work permits. Where
approved plans have been issued, revisions to the plans and additional review may be required.
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and
ordinances governing this work will be complied with, whether specified herein or not.
The granting of this pe ..'t does not pres - e to give a ty to violate or cancel the provision of any other work or local
laws regulatin • _ = tru • on or the perf • rmance of
Signature: /ter
Print Name:
Date:
doc: Cond -Elec
EL08 -151
Printed: 06 -10 -2008
CITY OF TUKWIL.
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http: //www. ci. tukwila. wa. us
Electrical Permit No. ti--0
% S
CO
Project No.
(For office use only)
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
SITE LOCATION
Site Address:
59o1) 090 /or //
Tenant Name: MA6(0— MorVG //,exe Alpri/
Property Owners Name: WtSTF( ErLD (DAP
Mailing
)
Mailing Address: (l (DD I W L514I 2e 13 W
King Co Assessor's Tax No.: b 'T20 _D / D
Suite Number: tC— I I Floor:
New Tenant: Yes ❑..No
inS 9n.E1.e5
City
CA
State
�o0GC
Zip
CONTACT PERSON - Who do we contact when your permit is ready to be issued
Name: 1398 Fe, Mon ( 17 -) Day Telephone:
Mailing Address: ci 36 Z3rd PL • S. FEDePAL,Wkif INA cieDD3
City State Zip
E -Mail Address: j) ('YY) l t4) It ocpr i(Lf • /'I d Fax Number: 2 S -66/ - 64x/
ELECTRICAL CONTRACTOR INFORMATION
Company Name:
Mailing Address:
City State Zip
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date:
Valuation of Project (contractor's bid price): $ '9_21 000 ( f
Scope of Work (please provide detailed }formation): n � e 4r I ti �° �e
Yp ' eQutf0, )1 -t ►/1c. rhr` ,e(e-eA1riczxr
Will service be altered? ❑ Yes No Adding more than 50 amps? cg Yes ❑ No
Type of Use: 1? . 41)Y/3'1-
Type of work:
❑ New ❑ Addition ❑ Service Change ❑ Remodel Tenant Improvement
❑ Low Voltage ❑ Generator ❑ Fire Alarm ❑ Telecommunication ❑ Temporary Service
Property Served by:
XrPuget Sound Energy
❑ Seattle City Light
HR Applications\Forms- Applications On Line'4 -2007 - Electncal Permit Apphmtion.doc
bh
Page 1 of 2
i
RESIDENTIAL
NEW RESIDENTIAL SERVICE
❑ New single family dwellings $140.00
(including an attached garage)
❑ Garages, pools, spas and outbuildings $75.00 ea
❑ Low voltage systems
(alarm, furnace thermostat) $55.00 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
❑ Service change or alteration $75.00
(no added/altered circuits)
❑ Service change with added/altered circuits $75.00
number of added circuits $10.00 ea
❑ Circuits added/altered without service change $50.00
(up to 5 circuits)
❑ Circuits added/altered without service change $50.00
(6 or more circuits) $7.00 ea
❑ Meter /mast repair $65.00
❑ Low voltage systems $55.00
(alarm, furnace thermostat)
MULTI- FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
❑ Temporary service (residential) $58.00
❑ Temporary service (generator) $75.00
❑ Manufactured/mobile home service $80.00
(excluding garage or outbuilding)
❑ Carnivals $75.00
Number of concessions $10.00 ea
PERMIT APPLICATION NOTES -
Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review - Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
A- Vii; r E74 ,ice
BUILDING OWNER OR ELECTRICAL CONTRACTOR
Signature: 1411 Date:
Print Name: 130,8 aR9 / tii�� (PeRMIT PL e) Day Telephone: Z7 7--64. 71fr
Mailing Address:371369 Z33v ( P r S
' E12/1-L lV w qeD 3
City State Zip
IDate Application Accepted: _ OQ
Date Application Expires: ( S-_ OQ Staff Initials: l44
H:\Applications'Fonns- Applications On Lineal -2007 - Electrical Permit Application doc
bb
Page 2 of 2
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 6364200010 Permit Number: EL08 -151
Address: 2600 SOUTHCENTER MALL TUKW Status: APPROVED
Suite No: Applied Date: 02/15/2008
Applicant: CHICKEN NOW Issue Date:
Receipt No.: R08 -02063
Initials: BLH
User ID: ADMIN
Payment Amount: $442.80
Payment Date: 06/10/2008 03:38 PM
Balance: $0.00
Payee: C & R ELECTRIC INC
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 27065 442.80
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
ELECTRICAL PERMIT - NONR
000.322.101.00.0 442.80
Total: $442.80
3536 06/11 9711 TOTAL 442.80
doc: Receiot -06 Printed: 06 -10 -2008
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Fax: 206 -431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 6364200010 Permit Number: EL08 -151
Address: 2600 SOUTHCENTER MALL TUKW Status: PENDING
Suite No: Applied Date: 02/15/2008
Applicant: CHICKEN NOW Issue Date:
Receipt No.: R08 -00441
Payment Amount: $110.70
Initials: WER Payment Date: 02/15/2008 10:49 AM
User ID: 1655 Balance: $442.80
Payee: HOSPITALITY INTERNATIONAL GROUP
TRANSACTION LIST:
Type Method Description Amount
Payment Check 2537 110.70
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
ELECTRICAL PLAN - NONRES
000.345.832.00.0 110.70
Total: $110.70
P.172 02/15 ?710 TOTAL 975.80
doc: Receiot -06 Printed: 02 -15 -2008
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
A -I5t
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION =
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Project: cal dQ�
czoti
Type of Inspection:
2/01:)
Address: � �� ilttki
Date Called:
Special Instructions:
Date Wanted:
Z I
m
P.m.
Requester:
Phone No:
0 Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
N
cr'thik-T
Inspector:
Date:
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
'Date:
ett,teselne6 _
.� - �-
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION IL
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Project . <:
(1 j G i /"
,U )
Type of Inspectioc
.e,'�
,lac.%
Addr ss: .-�
72 s")'
A
f �,a
Date Called:
Special Instructions:
Date Wanted:
a.m.
p.m.
Requester:
Phone No:
ElApproved per applicable codes.
or ctions required prior to approval.
COMMENTS:
ip..//)/2
Insp ctgr:
,0- -f/f,; /`/
Date'
�/f ? /O'
Ei $58.00 REINSPECTION FEE REQUIRED. Prior to inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call the schedule reinspection.
Receipt No.:
Date:
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
.T7
F��B- Is1
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION g
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Project: not
Type of Inspection:
WOO
Address:
7,o
Date Called:
Special Instructions:
Date Wanted:
t
1 112
a.m�
`per
Requester:
Phone No:
Approved per applicable codes.
/1
Corrections required prior to approval.
COMMENTS:
17A- 5-rocx /5-7-4f-f
-t, 5 154 kcocitr attP P Jr
(Je,t f&'LP, Ai- r u P
- 5 /PPoe r rc4oJIr /rc_(r -r
(.�1I u•Jr,
pc o )1 ?n/ God Pe d)
Inspector:
664Aleis
Date:
0.30/0\Ir
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION Ne'
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Project:
e , ` A%v+J
�i t
Ty pe of Inspection:
.�
o0 3
Address:
�2 i
Date Called:
Special Instructions:
Date Wanted:
7 p
(,mom'
��-p
Requester:
Phone No:
Approved per applicable codes. 0 Corrections required prior to approval.
COMMENTS:
Inspector:
1ti 6(4A)Cie.
(Date: O7(i /c
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
.4 _t ... .
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
INSPECTION RECORD
Retain a copy with permit
1,01?- BSI
PERMIT NO.
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Project: cal ce.c.4 40W
Type of Inspection:
/001--
Aq .
Address: ZG I
ao " 1�t�
Date Called:
_...�.
Special Instructions:
Date Wanted:
f
c3.4r
Requester:
Phone No:
Approved per applicable codes. El Corrections required prior to approval.
COMMENTS:
— k aaIE 604o141 ju s1 P6
1,4 PAilta.
Inspector:
&Alec,
Date: 0?
❑ $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
INSPECTION RECORD
Retain a copy with permit
VaA-/ 5-,
PERMIT NO.
(206)431 -3670
Project:
GI /IC. iee-,v Ai O '
Type of Inspectio
/O?53
Address:
;� tJ C1 C-- 41//1
Date Called:
Special Instructions:
Date Wanted:
/.. , /
.4.zpk
Requester:
Phone No:
roved per applicable codes. 0 Corrections required prior to approval.
OMMENTS:
2 5 #411-1 c-14 /64/
77. Ad6f
Inspect6 6
Date: . /.2 t/06.
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
Date:
Li,.�sr a 4dr1.ss _ v r.� _1.ic ti... „ , r:►.., ....... +.sue ..rah... _. - •�. ' —.w� as...,.ti , a • r�.rt.'�SI
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188
INSPECTION RECORD
Retain a copy with permit
PERMIT NO.
(206)431 -3670
P cto4e� ,v0 'Type
of Inspection:
.�
ri G /11/17e6i.
Date Called:
Special Instructions:
Date Wanted:
//
(/
p.m.
Requester:
Phone No:
ed per applicable codes. ❑ Corrections required prior to approval.
MMENTS: /3%4
D,K —�✓�tt5 / //Mn yin
Inspect •'��L
irrWA/6y
Date:6 /#0?...
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
rate:
••.7riakla .. �... .. .s. _... _amt .. . • . Al... A.ir_w.J
2006 Washin ton State Nonresidential Ener Code Com•liance Form
•
Interior Lighting Summary
•
LTG -INT
2006 Washington State Nonresidential Energy Code Compliance Forams
Project Info
Project Address CHICKEN NOW
Date *FA)
or &REA ptaippil
CG l-1
NRA
i
r� R 1
, ,mot
t? AM
- NE
O 0
633 SOUTHCENTER SPACE #CF11
SEATTLE, WA 98188
Applicant Name: 3421 N.LAKEVIEW DR
BOBBY SABAS
Applicant Address: TAMPA, FL 33618
Applicant Phone: 813-265-3955
819
KITCHEN
CLG. HIGHT ABOVE 9'
Project Description
• New Building • Addition • Alteration
K1 ans Inc
f Tub
C.
Refer to WSEC Section 1513 for controls and commissionin• require s
Compliance Option
0 Prescriptive b Lighting Power Allowance 0 S ', to '
(See Qualification Checklist (over). Indicate Prescriptive & LPA spaces clearly on plans.)
SALES
Alteration Exceptions
(check appropriate box - sec. 1132.3)
3
50
150
• No changes are being made to the lighting
EMERGENCY LIGHT
• Less than 60% of the fixtures new. installed wattage not increased, & space use not changed.
20
Maximum Allowed Lighting Wattage
Location
(floor /room no.)
Occupancy Description
Allowed
Watts per fl2 ""
Area in ft2
Allowed x Area
SALES/
FAST FOOD ESTABLISHMENT
1.365
600
819
KITCHEN
CLG. HIGHT ABOVE 9'
5
32
160
KITCHEN
2X4 FLUORECENT BOX "A"
4
64
256
" From Table 15 -1 (over) - document all exceptions on form LTG -LPA
Proposed Lighting Wattage
Total Allowed Watt
819
Location
(floor /room no.)
Fixture Description
Number of
Fixtures
Watts/
Fixture
Watts
Proposed
SALES
COMACT FLUORESCENT "E"
16
13
208
SALES
LINEAR FLUORECENT "C"
5
32
160
KITCHEN
2X4 FLUORECENT BOX "A"
4
64
256
SALES
INCAN. PENDANT LIGHT "F"
3
50
150
KITCHEN
EMERGENCY LIGHT
2
20
40
Total Proposed Watts may not exceed Total Allowed Watts for Interior
Total Proposed Watts 814
Notes:
1. For proposed Fixture Description, indicate fixture type, lamp type (e.g. T -8), number of lamps in the fixture, and ballast type (if
included). For track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
2. For proposed Watts /Fixture, use manufacturer's listed maximum input wattage of the fixture (not simply the lamp wattage) and
other criteria as specified in Section 1530. For hard -wired ballasts only, the default table in the NREC Technical Reference Manual
may also be used. For track lighting, list the greater of actual luminaire wattage or length of track multiplied by 50, or as applicable,
the wattage of current limiting devices or of the transformer.
3. List all fixtures. For exempt lighting, note section and exception number, and leave Watts /Fixture blank.
FILE COPY EL..0B. I
R-o..x:119w D
FEB 15 2008
PEt-.lcrt I eENTEh
2006 Washin ton State Nonresidential Ener Code Com•liance Form
•
Interior Lighting Summary (back)
LTG -INT
2006 Washington State Nonresidential Energy Code Compliance Form
Revised July 2007
Prescriptive Spaces
Occupancy:
0 Warehouses, storage areas or aircraft storage hangers 0 Other
Q ualification Checklist
Lighting
0.9
o
• Check if 95% or more of fixtures comply with 1,2 or 3 and rest are ballasted.
Note: If occupancy type is "Other" and
Fixtures:
1.2
fixture answer is checked. the number of
(Section
1. Fluorescent fixtures which are non - lensed with a) 1 or 2 two lamps, b) reflector
fixtures in the space is not limited by Code.
1521)
or louvers, c) 5 -60 watt T -1, T -2, T-4, T -5, T -8 lamps, and d) hard -wired elec-
Clearly indicate these spaces on plans. If
not qualified. do LPA Calculations.
1.3
Ironic dimming ballasts. Screw -in compact fluorescent fixtures do not qualify.
1.1
Dormitory
2. Metal Halide with a) reflector b) ceramic MH lamps <= 150w c) electronic ballas
Retail1', retail banking, mall concourses, wholesale
stores (pallet rack shelving)
1.5
3. LED lights.
TABLE 15 -1 Unit Lighting Power Allowance (LPA
s
Use'
LPAZ (W /sf)
Use'
LPAZ (W /sf)
Automotive facility
0.9
Office buildings, office/administrative areas in
facilities of other use types (including but not limited
to schools, hospitals, institutions, museums, banks,
churches)5 2:1'
1.0
Convention center
1.2
Penitentiary and other Group 1 -3 Occupancies
1.0
Courthouse
1.2
Police and fire stations'
1.0
Cafeterias, fast food establishments',
restaurants/bars'
1.3
Post office
1.1
Dormitory
1.0
Retail1', retail banking, mall concourses, wholesale
stores (pallet rack shelving)
1.5
Exercise center
1.0
School buildings (Group E Occupancy only), school
classrooms, day care centers
1.2
Gymnasia', assembly spaces'
1.0
Theater, motion picture
1.2
Health care clinic
1.0
Theater performing arts
1.6
Hospital, nursing homes, and other Group I -1 and
1 -2 Occupancies
1.2
Transportation
1.0
Hotel /motel
1.0
Warehouses ", storage areas
0.5
Hotel banquet /conference/exhibition hall3 4
2.0
Workshops
1.4
Laboratory spaces (all spaces not classified
"laboratory' shall meet office and other appropriate
categories)
1.8
Parking garages
0.2
Laundries
1.2
Libraries5
1.3
Plans Submitted for Common Areas Only'
Manufacturing facility
1.3
Main floor building lobbies' (except mall concourses)
,
1.2
Museum
1.1
Common areas, corridors, toilet facilities and
washrooms, elevator lobbies
0.8
Footnotes for Table 15 -1
1) In cases in which a general use and a specific use are listed, the specific use shall apply. In cases in which a use is not mentioned
specifically, the Unit Power Allowance shall be determined by the building official. This determination shall be based upon the most
comparable use specified in the table. See Section 1512 for exempt areas.
2) The watts per square foot may be increased, by two percent per foot of ceiling height above twenty feet, unless specifically directed
otherwise by subsequent footnotes.
3) Watts per square foot of room may be increased by two percent per foot of ceiling height above twelve feet.
4) For all other spaces, such as seating and common areas, use the Unit Light Power Allowance for assembly.
5) Watts per square foot of room may be increased by two percent per foot of ceiling height above nine feet.
6) Reserved.
7) For conference rooms and offices less than 150ft2 with full height partitions, a Unit lighting Power Allowance of 1.10 w /ft2 may be used.
8) Reserved.
9) For indoor sport tournament courts with adjacent spectator seating over 5.000, the Unit Lighting Power Allowance for the court area is
2.60 W/ft2.
10) Display window illumination installed within 2 feet of the window, provided that the display window is separated from the retail space by
walls or at least three - quarter- height partitions (transparent or opaque). and lighting for free-standing display where the lighting moves
with the display are exempt.
An additional 1.5 wfft2 of merchandise display luminaires are exempt provided that they comply with all three of the following:
a) located on ceiling- mounted track or directly on or recessed into the ceiling itself (not on the wall).
b) adjustable in both the horizontal and vertical axes (vertical axis only is acceptable for fluorescent and other fixtures with two points
of track attachment).
c) fitted with LED, tungsten halogen, fluorescent, or high intensity discharge lamps.
This additional lighting power is allowed only if the lighting is actually installed.
11) Provided that a floor plan, indicating rack location and height, is submitted, the square footage for a warehouse may be defined, for
computing the interior Unit Lighting Power Allowance, as the floor area not covered by racks plus the vertical face area (access side only)
of the racks. The height allowance defined in footnote 2 applies only to the floor area not covered by racks.
• •
PERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: EL08 -151
DATE: 02 -15 -08
PROJECT NAME: CHICKEN NOW
SITE ADDRESS: 2600 SOUTHCENTER MALL - FC -11
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # After Permit Issued
DEPART ENTS:
Bui ng Ii ision klit5
u
Public Works
Fire Prevention
Structural
Planning Division
Permit Coordinator
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Incomplete
n
DUE DATE: 02-21 -08
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
LETTER OF COMPLETENESS MAILED:
TUES/THURS ROUTING:
Please Route
Structural Review Required
REVIEWER'S INITIALS:
No further Review Required
DATE:
APPROVALS OR CORRECTIONS:
Approved Approved with Conditions
Notation:
REVIEWER'S INITIALS:
DUE DATE: 03 -20 -08
Not Approved (attach comments) n
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents/routing slip.doc
2 -28 -02
Look Up a Contractor, Electron or Plumber License Detail
Washington State Department of Labor and Industries
Electrical Contractor
A business licensed by L &I to contract electrical work within the scope of
its specialty. Electrical Contractors must maintain a surety bond or
assignment of savings account. They also must have a designated
Electrical Administrator or Master Electrician who is a member of the
firm or a full -time supervisory employee.
License Information
License
CRELEI *415DW
Licensee Name
C & R ELECTRIC INC
Licensee Type
ELECTRICAL CONTRACTOR
UBI
600316021
Ind. Ins. Account Id
Business Type
CORPORATION
Address 1
919 SW 150Th ST #A
Address 2
City
BURIEN
County
KING
State
WA
Zip
98166
Phone
2069373654
Status
ACTIVE
Specialty 1
GENERAL
Specialty 2
UNUSED
Effective Date
3/16/1959
Expiration Date
3/31/2010
Suspend Date
Separation Date
Parent Company
Previous License
Next License
Associated License
GARTICW2537T
Electrical Administrator Information
License
GARTICW2537T
Name
GARTIN, CECIL W
Status
ACTIVE
Business Owner Information
Name
Role
Effective Date
Expiration Date
GARTIN, CECIL W
01/01/1980
GARTIN, MARC S
01/01/1980
GARTIN, REVA M
01/01/1980
•
Page 1 of 2
https: // fortress. wa. gov /lni/bbip /printer.aspx ?License= CRELEI *415DW 06/10/2008
- .._ ▪ -._._
an::::... `..
PANEL "H"
PANEL "A"
A -16(1)
A -20(1)
—_
TEL BD. "TTB"
A -27,29
A -16(2)
TYP
P
A -14
H -1,3,5
TYP
0U -1
(AT ROOF)
R
GA
TYP
ELECTRICAL O PLAN
SCALE: 1 /4" = 1' -0"
....t�. .- • �••�� �� LCD T
�� -�
11,1crRacar,
NG PLAN
SCALE: 1/4" = 1'--0"
A -9
A -7
self service
ordering
FILE COPY
Penult No.
wappr�atts le gnat
wof _n�gondoA menu _
ths *Mon ca any *Opted
Olsond
of Tukwila
BULD%NG ENVISION
NOTE: 2006 IBC — Sec. 1006
Provide an average of one
foot - candle illumination at the
6?
floor along the entire egress
pathway and exit discharge
SEPARATE PERMIT
REQUIRED
filecItanloal
actsical
W umbing
EB Gas PiP
City ING DIVISION
Bull.
REVIEWED FOR
CODE COMPLIANCE
NFPA
MAR 1 () 23O
City
OfTuiwta
Q ILDING DP/ ION
NOTES:
1. CONTRACTOR SHALL REVIEW THE SPECIFICATIONS, GENERAL NOTES, KEY
NOTES, ELECTRICAL PLANS AND THE LANDLORD DESIGN CRITERIA
BEFORE BIDDING AND STARTING ANY CONSTRUCTION WORK.
2. ALL INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF THE
DESIGN DOCUMENTS, LANDLORD DESIGN CRITERIA AND N.E.C.
REQUIREMENTS.
3. CONTRACTOR SHALL COORDINATE WITH THE LANDLORD'S CRITERIA AND
SHALL FURNISH AND INSTALL NEW POWER SUPPLY AND ALL POWER
SUPPLY EQUIPMENT IN COMPUANCE WITH THE RISER DIAGRAM, KEY
NOTE #22 AND PANEL SCHEDULES.
4. CONTRACTOR FURNISH AND INSTALL ALL NEW WIRING AS SHOWN ON
THE ELEC. PLANS AND RISER DIAGRAM. ALL NEW WIRING SHALL BE IN
COMPLIANCE WITH N.E.C. TABLE 310 -16, AND PANEL SCHEDULES.
5. PULL STRINGS SHALL BE PROVIDED IN ALL EMPTY CONDUIT. FOR
TELEPHONE AND LOW VOLTAGE SYSTEM.
6. INTERIOR TELEPHONE WIRING SHALL INCLUDE FURNISHING AND
INSTALLING ALL TELEPHONE JACKS, AND COVER PLATES AS REQUIRED.
COORDINATE WITH THE TENANT.
7. LABEL ALL ELECT. EQUIPMENT WITH ENGRAVED BAKELITE NAMEPLATE OR
EMBOSSED PLASTIC NAME STRIP. LABEL ALL PANELS AS SHOWN ON THE
RISER DIAGRAM.
8. FURNISH A TYPE WRITTEN CIRCUIT DIRECTORY CARD FOR ALL PANELS,
LISTING ALL USED AND SPARE CIRCUITS.
9. CONTRACTOR SHALL VERIFY AND COORDINATE ALL ELECTRICAL
REQUIREMENTS AND LOCATIONS OF ALL HVAC EQUIPMENT PRIOR TO
INSTALLATION.
10. ALL OUTLET AND SWITCH COVER PLATES SHALL BE STAINLESS STEEL.
ALL OUTLET BOXES SHALL BE MOUNTED FLUSH IN WALLS AND SHALL
BE MOUNTED AT HEIGHT AS INDICATED ON THE EQUIP. PLAN.
COORDINATE ALL LOCATIONS WITH EQUIPMENT INSTALLATION AND
ARCHITECTURAL DRAWINGS.
11. ALL ELECTRICAL DEVICES AND EQUIPMENT SHALL BE EFFECTIVELY
GROUNDED IN ACCORDANCE WITH N.E.C. REQUIREMENTS. ALL BRANCH
CIRCUITS SHALL HAVE A SEPARATE GREEN INSULATED GROUND WIRE IN
EACH CONDUIT RUN.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ELECTRICAL
CONNECTIONS UNLESS NOTED OTHERWISE.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR COMMUNICATION WITH THE
PROPERTY OWNER'S PERSONNEL TO REVIEW CONTRACT DOCUMENTS
PRIOR TO INSTALLATION.
14. CONTRACTOR TO SEAL ALL WALL PENETRATIONS IN AN APPROVED
MANNER TO INSURE THE FIRE RATING INTEGRITY OF THE INVOLVED
AREAS.
15. COORDINATE FINAL INSTALLATION REQUIREMENTS WITH PROPER
AUTHORITIES. AND LANDLORD'S MANAGER.
16. CONTRACTOR, UPON COMPLETION OF HIS WORK , SHALL BE
RESPONSIBLE TO PROVIDE ANY AND ALL CERTIFICATIONS.
17. CONTRACTOR SHALL COMPLY WITH THE LANDLORD'S DESIGN CRITERIA
FOR ELECTRICAL AND FIRE ALARM SYSTEMS. MAKE NECESSARY
CONNECTIONS BETWEEN TENANT'S FIRE DETECTING DEVICES AND THE
LAND LORD'S FIRE ALARM STATION.
18. ALL CONDUIT RUNS ABOVE CEILING SHALL BE PARALLEL OR
PERPENDICULAR TO THE COLUMN LINES.
19. ALL CABLES AND WIRES SIZES SHALL COMPLY WITH N.E.C. TABLE
310 -16, 2005. MINIMUM SIZE OF CONDUCTOR SHALL BE #12 AWG CU.
NO. 10 WIRES SHALL BE USED IN PLACE OF #12 FOR CIRCUITS LONGER
THAN 100 FEET FROM PANEL TO LOAD. ALUMINUM CONDUCTOR SHALL
NOT BE PERMITTED. WIRE INSULATION SHALL BE THHN OR THWN.
20. ALL INTERIOR WIRING SHALL BE CONCEALED AND IN GAL. STEEL OR EMT
COND. AND IN COMPUANCE WITH THE N.E.C. AND LAND LORD'S DESIGN
CRITERIA.
21. CONTRACTOR MAY USE FL XIBLE CONDUIT FROM JUNCTION BOX TO THE
LIGHTING FIXTURE, BE-TEN LIGHTING FIXTURES, AND TO OTHER DEVICES
PROVIDED THE LENGTH OF THE FLEX. CONDUIT IS NOT MORE THAN 6
FEET.
22. MC CABLES SHALL NOT BE USED FOR HOME RUN CIRCUITS AND FOR
THE WIRING WITHIN PARTITION OR DEMISING WALL CONSTRUCTION. ALL
IN -WALL CONCEALED WIRING MUST BE RUN IN RIGID CONDUITS.
23. THE GROUND ON THE SEPARATELY DERIVED SERVICE SHALL BE BONDED
TO THE BUILDING STEEL AND TO THE INCOMING COLD WATER METAL
PIPING WITH CAD WELD CONNECTION. REFER TO KEY NOTE #22.
24. ALL BREAKERS IN ALL PANELS SHALL BE BOLTED THERMAL MAGNETIC
TYPE. TWO (2) AND THREE (3) POLE MOLDED CASE CIRCUIT BREAKERS
SHALL BE WITH COMMON TRIP.
25. UNLESS NOTED OTHERWISE, WIRE AND CABLE SIZES SHALL BE IN
COMPLIANCE WITH KEY NOTE # 22, RISER DIAGRAM AND THE N.E.C.
TABLE 310 -16.
26. ROMAX, TYPE AC AND NM CABLES SHALL NOT BE PERMITTED.
27. CONDUCTORS SHALL BE COPPER PER LL CRITERIA.
28. ALL BREAKERS USED FOR LIGHTING CIRCUITS SHALL BE CONTINUOUS
DUTY, UGHT SWITCHING RATING.
DLO 'S SPCC NOTES:
TENANTS LIGHTING AND LIGHTING CONTROLS SYSTEM SHALL COMPLY WRITHE WASHINGTON STATE NON - RESIDENTIAL ENERGY CODE
STOREFRONT SIGNAGE AND LIGHTING TIME CLOCKS SHALL BE SET TO MAIL'S OPERATING HOURS.
ALL LIGHTING IN FORWARD SELLING AREA MUST BE INCANDESCENT WITH LOW IRON TEMPERED GLASS SAFETY LENS, PER FOOD PREPARATION AND
LOCAL CODES, ON SEPARATE CIRCUIT WITH A 7 DAY TIME CLOCK SET TO MALL'S OPERATING HOURS. FOOT -CANDLE LEVEL, AT COUNTER HEIGHT,
MUST BE AN AVERAGE OF 50 MAINTAINED.
ALL TRACK LIGHTS MUST BE IN RECESSED TROFFERS,
LANDLORD WILL PROVIDE A COMMUNICATION CABLE TRAY LOCATED IN THE UTILITY CORRIDOR FOR TENANTS USE NO CONDUIT WILL BE PROVIDED,
LANDLORD WILL PROVIDE A COMMUNICATIONS TERMINAL BOARD WITHIN EACH LANDLORD ELECTRICAL ROOM. TENANT SHALL PROVIDE AND INSTALL
A COMPLETE TELEPHONE SERVICE SUPPORT FACILITIES AS REQUIRED BY THE SERVING TELEPHONE COMPANY. ALL TENANT TELEPHONE
EQUIPMENT SHALL BE CONTAINED WITHIN THE TENANTS SPACE. TENANTS TELEPHONE EQUIPMENT IS NOT PERMITTED IN LANDLORD'S TELEPHONE
EQUIPMENT ROOM. TENANT SHALL PROVIDE PLENUM RATED WIRE FROM THE TELEPHONE ROOM TO THE TENANT'S TELEPHONE EQUIPMENT WITHIN
THE DEMISED PREMISES UTILIZING THE LANDLORD SUPPLIED CABLE TRAY. ANY CORRIDOR WALL PENETRATIONS WILL NEED TO BE FIRE CAULKED
AS REQUIRED.
TRANSFORMERS ARE TO BE FLOOR MOUNTED_ COORDINATE WITH WESTFIELDS ONSITE COORDINATOR.
ELECTRICAL CONTRACTOR SHALL UTILIZE LANDLORD PROVIDED FUSED DISCONNECT SWITCH LOCATED WITHIN THE TENANT SPACE, ON BACK WALL,
FOR TEMPORARY ELECTRICAL FOR CONSTRUCTION.
ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY TRANSFORMER AND PANEL AS REQUIRED WITHIN TENANT SPACE,
LANDLORD PROVIDED MAIN DISCONNECT MEANS FOR TENANT IN A LANDLORD ELECTRICAL ROOM AS WELL AS CONDUIT AND CONDUCTORS
(FEEDER) FROM THE MAIN DISCONNECT MEANS TO A LANDLORD PROVIDED FUSED DISCONNECT SWITCH LOCATED WITHIN THE TENANT SPACE, IF
NEEDED TO ACCOMMODATE TENANT CONSTRUCTION, THE TENANT SHALL RELOCATE THE LANDLORD PROVIDED DISCONNECT SWITCH AND
ASSOCIATED FEEDER, TENANT SHALL FURNISH AND INSTALL CONDUIT AND CONDUCTORS FROM FUSED DISCONNECT SWITCH TO TENANTS' MAIN
FUSED DISCONNECT SWITCH OR MAIN CIRCUIT BREAKER EQUIPPED PANELBOARD.
LANDLORD PROVIDED MASTER METERING EQUIPMENT IN THE LANDLORD'S ELECTRICAL ROOM. THE LANDLORD -OWNED NETWORK METERING
SYSTEM WILL METER TENANT POWER CONSUMPTION,
TENANTS ELECTRICAL CONTRACTOR SHALL FURNISH AN IDENTIFICATION NAMEPLATE ON TENANTS MAIN DISCONNECT SWITCH IN LANDLORD'S
SWITCHBOARD. NAMEPLATES SHALL BE ONE - EIGHTH INCH (118) THICK PLASTIC, BLACK ON WHITE AND ETCHED LETTERS. RS. THE MINIMUM SIZE SHALL
BE ONE INCH (1 ') WITH ONLY THE TENANT'S SPACE NUMBER ENGRAVED ON SUCH, PERMANENTLY AFFIXED,
NO ATTACHMENT OR SUPPORT FROM ANY ROOF DECK IS ALLOWED. HANGERS, CLAMPS AND SUPPORTS SHALL BE FASTENED TO BAR JOISTS OR
BEAMS ONLY.
KEYNOTES:
• PROVIDE LOCK TAB AT CIRCUIT # A -8 IN 'ON' POSITION. EXIT, NIGHT AND
EMERGENCY LIGHTS SHALL BE WIRED AHEAD OF ANY LOCAL SWITCHES.
O CONTRACTOR MUST COORDINATE AND VERIFY LIGHT FIXTURE MODEL NUMBERS
WITH THE TENANT BEFORE PURCHASING ANY NEW UGHT FIXTURES. LIGHT
SCHEDULE IS FOR REFERENCE ONLY.
V COORDINATE EXACT LOCATION OF LCD MONITORS AND INSTALL POWER OUTLETS
FOR THEM AS REQUIRED. MAKE ALL CONNECTIONS AS REQUIRED.
�4 INSTALL JUNCTION BOX AND SINGLE POLE 120V. TOGGLE SWITCH IN SOFFIT FOR
CONNECTION OF SIGNAGE XFRMR. COORDINATE EXACT LOCATION WITH
ARCHITECTURAL PLANS AND DETAILS.
ROUTE MENU AND STORE SIGN CIRCUITS THROUGH A TIME CLOCK TIC.
�-� COORDINATE TIME SETTINGS WITH THE LANDLORD.
ALL LIGHTS SHALL BE CONTROLLED BY THE BREAKERS INSIDE THE PANEL. ALL
BREAKERS WHICH SUPPLY POWER TO THE LIGHTING CIRCUITS SHALL BE LIGHT
DUTY RATED. THIS IS TYPICAL.
�7 PROVIDE A MINIMUM 1/2" CONDUIT W /WIRE FROM TELEPHONE OUTLET BACK
TO TELEPHONE BOARD LOCATED IN WORK AREA. THIS IS TYPICAL FOR ALL
TELEPHONE OUTLETS.
O8 CONTRACTOR SHALL FURNISH AND INSTALL TELEPHONE CONDUIT TO TENANT'S
TEL BD "TTB ". FURNISH AND INSTALL TEL. CABLE FROM TO LANDLORD'S
DISTRIBUTION POINT TO THE TENANT'S TEL. BOARD "TTB ". COORDINATE ALL
TELEPHONE REQUIREMENTS WITH TENANT. CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING ALL CABLES AND DATA /TEL. OUTLETS. THE
TELEPHONE SYSTEM SHALL BE COMPLETE AND FUNCTIONAL.
• ALL OUTLETS WITHIN 6' OF ANY SINK SHALL BE GFI OUTLETS. ALL KITCHEN
AREA OUTLETS SHALL BE WITH GFI TO COMPLY WITH N.E.C. STD. #210.8(B)(2).
TO ECONOMIZE THE COST THE CONTRACTOR SHALL INSTALL FIRST OUTLET AT
WHICH THE HOME RUN IS CONNECTED, WITH GFI AND ALL OTHER DOWN STREAM
OUTLET NORMAL WITHOUT GFI.
1 Q THE CONTRACTOR SHALL FURNISH AND INSTALL FA SYSTEM INCLUDING ALL
DEVICES IN COMPUANCE WITH THE POWER PLAN AND ANSUL WIRING DIAGRAM,
LANDLORD'S CRITERIA, NFPA AND LATEST APPLICABLE CODE REQUIREMENTS.
COORDINATE WITH THE LANDLORD AND DETERMINE FA DEVICES MODEL NUMBER.
TENANTS FA SYSTEM TIE CONNECTIONS TO THE BASE BUILDING FA SYSTEM
SHALL BE PROVIDED BY THE LANDLORD'S CONTRACTOR AT TENANT'S EXPENSE.
11 VERIFY WITH LANDLORD AND FURNISH AND INSTALL DUCT SMOKE DETECTOR,
RELAY AND REMOTE INDICATOR. TIE RELAY INTO DUCT MT'D SMOKE DETECTOR
WHICH WHEN ACTIVATED WILL SHUT DOWN RTU -1, HOOD SUPPLY FAN. TIE
TENANT'S FA SYSTEM TO LANDLORD'S FIRE ALARM CONT. PANEL PROVIDE
CONDUIT, WIRES AND MAKE ALL CONNECTIONS AS REQUIRED.
12 DETERMINE EXACT LOCATION OF DUCT REMOTE INDICATOR AT SITE AND MAKE
ALL CONNECTIONS AS REQUIRED.
13 THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL CABLES AND
CONNECTIONS OF ALL COMPONENTS THAT ARE PART OF THE REFRIGERATION
EQUIPMENT.
14 COORDINATE WITH TENANT AND INSTALL NEW BELL /BUZZER AS REQ'D., INSTALL
BELL BUTTON AS SHOWN ON THE DRAWING. INSTALL BUZZER XFRMR, IN CEILING
AND WIRIN
+.
FURNISH AND INSTALL A 20A OUTLETS FOR THE HEAT LAMP STRIP AND A 40
AMP, 208V, 3P, TWIST LOCK OUTLET FOR THE ELECTRIC GRIDDLE AS REQUIRED.
DETERMINE EXACT LOCATION OF OUTLETS AT SITE WITH KITCHEN CONTRACTOR.
MAKE ALL CONNECTIONS AS REQUIRED.
16 CONTRACTOR SHALL COORDINATE WITH KITCHEN EQUIP. CONTRACTOR AND
ROUTE 208V, 10, CIRCUIT WITH NEUTRAL AND GRND CONDUCTORS FOR ICE
MACHINE. FURNISH JB OR SPECIAL OUTLET AS REQ'D AND MAKE NECESSARY
CONNECTIONS OF REMOTE CONDENSER.
.0 CONTRACTOR SHALL COORDINATE WITH KITCHEN AND REFRIGERATION
CONTRACTORS AND DETERMINE EXACT RATING OF ALL EQUIPMENT AND TYPE OF
REQUIRED POWER LEAD CONNECTIONS AT EACH EQUIP. MUST ADJUST SIZE OF
BREAKERS IF OR AS REQUIRED. THIS IS TYPICAL.
1$ DETERMINE EXACT LOCATION OF HOOD AND ANSUL PANELS AT SITE WITH HOOD
PACKAGE. CONTRACTOR SHALL ROUTE POWER CIRCUIT FOR EXH. & SUPPLY
FANS FROM POWER PANEL TO THE HOOD PANEL AND FROM HOOD PANEL TO
THE EXHAUST AND SUPPLY FANS. COORDINATE WITH HOOD MFG. DRAWINGS FOR
ADDITIONAL INFORMATION. THE CONTRACTOR SHALL FURNISH AND INSTALL 20A,
480V, 3 POLE, FUSED NEMA 3R, DISC. SWITCHES FOR EXHAUST AND SUPPLY
FANS. MAKE ALL CONNECTIONS AS REQUIRED.
0 THE CONTRACTOR SHALL FURNISH AND INSTALL A NEW 20A FUSED, 480V, 3P,
NEMA 3R DISC. SWITCH FOR CU -1 AND NEMA 1 DISC SW FOR AHU -1. AHU -1
SHALL BE A SINGLE POINT CONNECTION. ROUTE #10, CU, CONDUCTORS AS
SHOWN. FURNISH AND INSTALL A WEATHER PROOF, GFI, OUTLET NEAR CU -1
UNIT AS SHOWN ON THE POWER PLAN.
20 ALL CONDUIT PENETRATIONS THROUGH CASEWORK SHALL BE CLEAN, TIGHT AND
SEALED WITH WHITE SILICONE. THIS IS TYPICAL.
21 PROVIDE KEY -LOCK TABS AT CIRCUITS ROUTE CIRCUITS
A -7 AND A -9 WITH ISOLATED GROUND CONDUCTORS. I
22 THE CONTRACTOR SHALL COORDINATE WITH THE LANDLORD AND SHALL FURNISH
AND INSTALL A NEW 200 AMP, 277/480V, 30, 4W, POWER SUPPLY AS
SCHEDULED BY THE LANDLORD IN COMPUANCE WITH LL'S CRITERIA, RISER DIAG.,
PANEL SCHEDULES AND AS DETAILED BELOW:
a) COORDINATE WITH THE LANDLORD AND FURNISH AND INSTALL ALL POWER
SUPPLY EQUIPMENT AS REQUIRED. REFER TO LANDLORD'S SPECIFIC NOTES.
b) THE CONTRACTOR SHALL VERIFY WITH THE LANDLORD THAT THE MAIN
SUPPLY FEEDER IS INSTALLED BY THE LANDLORD. REFER TO LANDLORD'S
SPECIFIC NOTES. EXTEND EXISTING CONDUIT AND FEEDER TO THE PANEL "H"
AS SHOWN ON THE RISER DIAGRAM.
c) FURNISH AND INSTALL NEW PANELS "H" AND "A" IN COMPUANCE WITH
RISER DIAGRAM AND PANEL SCHEDULES. PANEL "H" SHALL BE 277/480V,
30, 4W, WITH 200 AMP MCB. PANEL "A" SHALL BE 120/208V, 30, 4W, WITH
150 AMP MCB. BOTH PANELS SHALL BE WITH FULL SIZE GROUND, NEUTRAL
BUSSES AND WITH BOLTED TYPE BREAKERS.
d) FURNISH AND INSTALL A NEW DRY TYPE, 45 KVA XFRMR ABOVE PANELS.
XFRMR SHALL BE WITH 6 STANDARD VOLTAGE REGULATION TAPS (2 TAPS
+2.5% AND 4 TAPS - 2.5 %). INSTALL XFRMR ABOVE PANELS ON SUPPORTS
IN COMPLIANCE WITH MANUFACTURER AND LL'S RECOMMENDATIONS. THE
CONTRACTOR SHALL BOND THE TRANSFORMER NEUTRAL TO THE BUILDING
STEEL AND AND TO THE COLD WATER METAL PIPE WITH EXOTHERMIC WELD
CONNECTIONS AS SHOWN ON THE RISER DIAGRAM.
e) THE CONTRACTOR SHALL INSTALL GROUNDING IN COMPUANCE WITH N.E.C.
STD. #250, 2005. ALL UGHT FIXTURE AND OTHER EQUIPMENT SHALL BE
GROUNDED.
f) UNLESS NOTED OTHERWISE THE CONTRACTOR SHALL FOLLOWING SIZE OF
WIRES PER N.E.C. TABLE 310 -16.
(1) USE # 12 AWG, COPPER, THWN OR THHN, FOR 20A BRKRS.
(2) USE # 10 AWG, COPPER, THWN OR THHN, FOR 25A AND 30A
BREAKERS.
(3) USE MINIMUM SIZE OF # 10 AWG, CU, THWN OR THHN WIRES
FOR EXH /SUPPLY FANS AND HVAC EQUIPMENT CIRCUITS.
(4) USE # 8 AWG, COPPER, THWN OR THHN, FOR 35A AND 50A
BREAKERS.
(5) USE # 6 AWG, COPPER, THWN OR THHN, FOR 60A BREAKERS.
BREAKERS.
APPROVE,.' P' r.._, ,�- 1r1pIC eL7nt
t,".". 7'7 MuD,r''Li) CR FALTERED
WITHOUT AU1 HORI7ATid FROM THE BUILDING
OrF! I, .L, AU WORK SHA '..L BE DONE IN
ACCORDANCE WITH THE APPROVED PLANS AND
IS 7J'3.'::CT TO F;EI D INSPECTIONS
SYMBOLS
2'X4' FLUORESCENT
i O
2'X4' FLUORESCENT NIGHT LT (N /L)
2'X2' FLUORESCENT
0 1
2'X2' FLUORESCENT NIGHT UGHT
1'X4' FLUORESCENT
0
(0)
CEILING MOUNTED LT FIXTURE.
GOOSENECK WALL MOUNTED LIGHT
FIXTURE
HEX
EXIT UGHT
114m
EMERGENCY UGHT
7_7/0D,
TRACK LIGHT
dib
DUPLEX RECEPTACLE WITH
120 V, 20 AMPERE RATING.
HEIGHT 16" TO BOTTOM UNLESS
NOTED OTHERWISE. (TYP.)
u 40"
®
DUPLEX RECEPT. OUTLET ABOVE
COUNTER SHALL BE 40" AFF TO
BOTTOM UNLESS NOTED OTHERWISE
GFI
DUPLEX W /GRND F. INTERRUPTER
AT COUNTER SHALL BE 42" AFF TO
BOTTOM UNLESS NOTED OTHERWISE
dibIG
DUPLEX W /ISOL. GRND CONDUCTOR
AT A HEIGHT TO THE BOTTOM AS
NOTED.
4".
;;;
QUADRUPLEX WITH 120V, 20 A.
HEIGHT AS NOTED
@
SPECIAL "TWIST LOCK RECEPT" WTR
PROOF, 480V, 30, OR 240V, 30, OR
240V, 10, FOR KITCHEN EQUIP. WITH
AMPERE RATING AS SHOWN AT
PANEL SCHEDULE AND AT DRAWING.
0 F
FLOOR RECEPTACLE
0 C
CEILING RECEPTACLE
JUNCTION BOX
REST ROOM EXHAUST FAN.
0�
DISCONNECT SWITCH
SP
-
SOUND SYSTEM SPEAKER
2
TELEPHONE JACK
yCOMPUTER
/DATA JACK
FLUSH MOUNTED POWER PANEL
0
SURFACE MOUNTED POWER PANEL
t3(4)
THREE OR FOUR WAY SWITCH
t
DIMMER SWITCH
TWO WAY SWITCH
' 9
WATER HEATER
FACP
FIRE ALARM CONTROL PANEL -LSS 4/12
F
MANUAL PULL STATION - 270 -SPO
42" A.F.F.
.
F
HORN /STROBE- 792 -7A -006 80" A.F.F.
M
MAGNETIC DOOR HOLDER- 1504 -AQ
R
FAN SHUT DOWN RELAY W/
ENCLOSURE- MR- 199X -13/C
L
DUCT SMOKE DETECTOR 6264B -001/
6260A- 100/6261- 003- 6251B -001A
R;
Ir1L
REMOTE INDICATOR /TEST STATION ---
6262A -001
STROBE -- 202 -7A -001 80" AFF
F
0
HEAT DETECTOR -2816
SMOKE DETECTOR - 62506/6251B -001A
0 )
REFER TO THE CODED NOTE NUMBER.
Lu�
CONCEALED IN WALL, CEILING OR
UNDER GROUND CONDUIT RUN
CONSISTING OF:
Z - GROUND CONDUCTOR
III - SMALL LINES INDICATE POWER
NON GROUNDED CONDUCTORS.
I - BIG LINE INDICATES
NEUTRAL CONDUCTOR
III
Public works, Building Division
PERMIT NUMBER
� w
FEB 15 2008
PERMIT CENTEh
EL0B-iSI
FILE COPY
DATE: 12 -24 -07
JOB NO: 0734
DRAWN:
CHECKED:
SOUTHCENTER
SPACE FC 1 1
633 SOUTHCENTER
WA 98188
REVISIONS
AREVISED PER LANDLORD /OWNER
1/23/08
DAVID HIATT
ARCHITECT
4410 W. Melrose Avenue
Tampa, Florida 33629
p. 813.289.3336
f. 813.289.3332
REGISTERED
ARCHITECT
DAVID W. HIATT
STATE OF WASHINGTON
ME `s POWER &
UGHTING PAN
SHEET NUMBER
togl
MCB: 200 AMP
MLO: N/A
A.I.C.: 22,000 AMP
VOLTS: 277/480 V PHASE: 3, S/N WIRE: 4
WITH GROUND BUSS
ELECTRICAL Imo- TENANT
ROOM SPACE
BLDG: SOUTH CENTER, SEATTLE, WA, SP # FC -11
MTD: SURFACE
DESCRIPTION OF LOAD BRKR KVA PH LOAD CIR PHASE CIR KVA PH LOAD BRKR DESCRIPTION OF LOAD
AMP P WA 03 0C NO A B C NO � �B �C P AMP
M COND UNIT CU -1 20 3 2.10 1 • 2 1.74 3 70 45 KVA XFRMR T
2.10 3 • 4 11.68
v v v 2.10 5 • 6 11.87 v v
W AHU -1 W/8 KW HTR 30 3 3.52 7 • 8 ''-- ..-- -" SPACE
3.52 9 • 10
.�. �. \, ,_, 3.52 11
• 12
M WATER HEATER 20 3 4.00 13 • 14
4.00 15 • 16
v v 4.00 17 ■ 18
SPACE 19 • 20
21 • 22
23 • 24
25 • 25
27 • 28
TOTAL 19.62 19.62 9.62
TOTAL CONNECTED KVA OA OB OC
L LIGHTING:
R RECEPTACLE
W WATER HEATER: 4.00 4.00 4.00
H HEATING: 3.52 3.52 3.52
M MOTOR /HVAC /FAN .10x2.10 2.10
T TRANSFORMER /PANEL /ATS: 11.7411.6811.87
K KITCHEN EQUIPMENT
E EQUIPMENT
1 MISCELLANEOUS
x11.7411.6$11.87 TOTAL
7 DAY, 24 HRS
PROGRAMMABLE TIME
CLOCK T/C
LL'S DISC SW
WITH 200A FUSES AT
LL'S DIST. MTR CENTER
FOR 480V, 30, SERVICE
FOR SPACE# FC -1
EXIST
DISC
SW
NEW 4 # 3/0,
CU, 1 - #6, CU,
GRND, THHN OR
THWN IN exist
2 "C. I--. i--
200AF
200 AMP
MCB
45 KVA DRY TYPE
XFRMR. 480 V. "DELTA"
PRIMARY 120/ 208 V.
"WYE" SECONDARY
EXIST ELEC. MTR
150 AMP
MCB
OA 0B oC
21.36 21.30 21.49 TOTAL CONNECTED KVA
78 77 78 TOTAL CONNECTED AMPS
EXIST LANDLORD'S WIRE WAY
VERIFY LOCATION AT SITE
COLD WTR
METAL
PIPE
(1) REFER TO PANEL "A" SCHEDULE FOR THESE LOADS DETAIL.
4 - #1 /0, CU,
1-- #6, CU, GRND
IN 2" C. 00
EXIST 1 # 4, CU, TO GRND,
BLDG. STEEL AND COLD WTR
METAL PIPE PER N.E.C. #250.
MCB: 150 AMP
MLO: N/A
A.I.C.: 10,000 AMPS PHASE: 3, S/N WIRE: 4 BLDG: SOUTH CENTER, SEATTLE, WA, SP # FC-11
VOLTS: 120/208 V
WITH ISO & EQUIP. GROUND BUSES MTD: SURFACE
ELECTRICAL POWER RISER DIAGRAM
RISER DIAL. NOTES:
V COORDINATE WITH LANDLORD (LL) AND FURNISH AND INSTALL A
NEW POWER SUPPLY AND EQUIPMENT IN COMPLIANCE WITH RISER
DIAGRAM, PANEL SCHEDULES AND KEY NOTE #22 ON SHEET E1.
INSTALL GROUNDING SYSTEM AS REQUIRED TO COMPLY WITH RISER
DIAGRAM AND WITH N.E.C. STD. #250, REQUIREMENTS.
FURNISH AND INSTALL NEW PANELS "H AND A" IN COMPLIANCE
WITH THE KEY NOTE #22, RISER DIAGRAM AND PANEL SCHEDULE.
PANELS SHALL BE WITH BOLTED TYPE BREAKERS.
FURNISH AND INSTALL A 45 KVA XFRMR AS SHOWN AND AS
DESCRIBED IN KEY NOTE #22 ON SHEET El AND IN SPECIFICATIONS.
MAKE SURE THAT THE NEUTRAL OF THE TRANSFORMER I5 BONDED
WITH THE BUILDING STEEL AND TO THE INCOMING COLD WATER METAL
PIPE WITH EXOTHERMIC WELD CONNECTIONS AS SHOWN ON THE RISER
DIAGRAM.
DESCRIPTION OF LOAD BRK KVA PH LOAD CIR PHASE CIR KVA PH LOAD BRKR DESCRIPTION OF LOAD
AMP P OA OB OC NO A B C NO 0A OB OC !AMP
K 2 DOOR FREEZER (#47A) 20 1 1.79 1 ■ 2 0.29 20 L S KITCHEN L
WORK TOP FREEZER ( #39B) 0.60 3 ■ 4 0.25 � RECESS / PENDANT E,F)
DRINK DISPENSER (( #12) 1.02 5 • 6 1.20 SIGN /UC COVE (C) (T /C)
R POINT OF SALE SYSTEM ( #2)(IG) 0.80 7 • 8 0.19 EMERGENCY/NT/EXIT
'1, POINT OF SALE SYSTEM ( #2)(IG) 0.40 9 • 10 1.35 RACE S G
S�NDWICH TOP REFI G. 39) T 0.56 11 • 12 + 0.36 Mr 'LCD MONITORS e
K ODA DISPENSER_ 7 0.60 13 • 14 0.80 `�r�� BAG & is' S K
R KITCHEN 'ACT' CLE 0.50_ _ 15 • 16 0.50 _IIU SALES AREA RECEPT R
1 Q0 �k� P N S 26 _ _ 1 OD 17 • 18 1.10 fl HEAT LAMP STRIP ( #17) E
K 2 DOOR COOLER ( #47B) 1.25 19 • 20 0.50 TIME CLOCK /TRIP REL /BUZZER 1
2 DOOR COOLER ( #47B) v 1.25 21 • 22 0.56 20 SANDWICH TOP REFRIG (#39) K
HV GAS FRYER ( #24) 20 1 0.36 23 • 24 RESERVED FOR SHUNT TRIP
RESERVED FOR SHUNT TRIP 25 ■ 26 3.24 3 35 L G R CXL` G iID' LE ( #18)
ICE MACHINE ( #29) 20 2 0.75 27 • 28 3.24
.L .�. 0.75 29 • 30 3.24 i i
M EXH /SUPPLY FANS ( #26) 40 3 2.28 31 • 32 RESERVED FPR SHUNT TRIP v
2.28
2.28 35 •
• 36 SPACE
i
SPACE 37 • 38
39 • 40
`. 41 • 42 v
TOTAL 6.72 5.78 5.97
TOTAL CONNECTED KVA OA 0B OC
L LIGHTING: 0.48 1.60 1.56
R RECEPTACLE 0.80 1.40
W WATER HEATER:
H HEATING:
M MOTRO /HVAC /FAN: 2.28 2.28 2.28
T TRANSFORMER /PANEL /ATS:
K KITCHEN EQUIPMENT 7.68 6.40 5.93
E EQUIPMENT /FOOD HEAT LAMP 1.10
1 MISCELLANEOUS 0.50 1.00
5.021 5.90 1 5.90 ITOTAL
OA OB OC
11.74 11.68 11.87 OTAL CONNECTED KVA
98 98 99 OTAL CONNECTED AMPS
(1) PROVIDE LOCK TAB AT THESE BREAKERS IN "ON" POSITION.
(2) INSTALL THIS BREAKER WITH SHUNT TRIP DEVICE.
(3) ROUTE THIS CIRCUIT THROUGH A TIME CLOCK
(4) ROUTE THIS CIRCUIT WITH ISO. GROUND CONDUCTOR.
LIGHTING noun SCHEDULE 0000
st
8
431He
TTA
-
i
i
DESCRIPTION OF LOAD BRKR KVA PH LOAD CIR PHASE CIR KVA PH LOAD BRKR DESCRIPTION OF LOAD
AMP P WA 03 0C NO A B C NO � �B �C P AMP
M COND UNIT CU -1 20 3 2.10 1 • 2 1.74 3 70 45 KVA XFRMR T
2.10 3 • 4 11.68
v v v 2.10 5 • 6 11.87 v v
W AHU -1 W/8 KW HTR 30 3 3.52 7 • 8 ''-- ..-- -" SPACE
3.52 9 • 10
.�. �. \, ,_, 3.52 11
• 12
M WATER HEATER 20 3 4.00 13 • 14
4.00 15 • 16
v v 4.00 17 ■ 18
SPACE 19 • 20
21 • 22
23 • 24
25 • 25
27 • 28
TOTAL 19.62 19.62 9.62
TOTAL CONNECTED KVA OA OB OC
L LIGHTING:
R RECEPTACLE
W WATER HEATER: 4.00 4.00 4.00
H HEATING: 3.52 3.52 3.52
M MOTOR /HVAC /FAN .10x2.10 2.10
T TRANSFORMER /PANEL /ATS: 11.7411.6811.87
K KITCHEN EQUIPMENT
E EQUIPMENT
1 MISCELLANEOUS
x11.7411.6$11.87 TOTAL
7 DAY, 24 HRS
PROGRAMMABLE TIME
CLOCK T/C
LL'S DISC SW
WITH 200A FUSES AT
LL'S DIST. MTR CENTER
FOR 480V, 30, SERVICE
FOR SPACE# FC -1
EXIST
DISC
SW
NEW 4 # 3/0,
CU, 1 - #6, CU,
GRND, THHN OR
THWN IN exist
2 "C. I--. i--
200AF
200 AMP
MCB
45 KVA DRY TYPE
XFRMR. 480 V. "DELTA"
PRIMARY 120/ 208 V.
"WYE" SECONDARY
EXIST ELEC. MTR
150 AMP
MCB
OA 0B oC
21.36 21.30 21.49 TOTAL CONNECTED KVA
78 77 78 TOTAL CONNECTED AMPS
EXIST LANDLORD'S WIRE WAY
VERIFY LOCATION AT SITE
COLD WTR
METAL
PIPE
(1) REFER TO PANEL "A" SCHEDULE FOR THESE LOADS DETAIL.
4 - #1 /0, CU,
1-- #6, CU, GRND
IN 2" C. 00
EXIST 1 # 4, CU, TO GRND,
BLDG. STEEL AND COLD WTR
METAL PIPE PER N.E.C. #250.
MCB: 150 AMP
MLO: N/A
A.I.C.: 10,000 AMPS PHASE: 3, S/N WIRE: 4 BLDG: SOUTH CENTER, SEATTLE, WA, SP # FC-11
VOLTS: 120/208 V
WITH ISO & EQUIP. GROUND BUSES MTD: SURFACE
ELECTRICAL POWER RISER DIAGRAM
RISER DIAL. NOTES:
V COORDINATE WITH LANDLORD (LL) AND FURNISH AND INSTALL A
NEW POWER SUPPLY AND EQUIPMENT IN COMPLIANCE WITH RISER
DIAGRAM, PANEL SCHEDULES AND KEY NOTE #22 ON SHEET E1.
INSTALL GROUNDING SYSTEM AS REQUIRED TO COMPLY WITH RISER
DIAGRAM AND WITH N.E.C. STD. #250, REQUIREMENTS.
FURNISH AND INSTALL NEW PANELS "H AND A" IN COMPLIANCE
WITH THE KEY NOTE #22, RISER DIAGRAM AND PANEL SCHEDULE.
PANELS SHALL BE WITH BOLTED TYPE BREAKERS.
FURNISH AND INSTALL A 45 KVA XFRMR AS SHOWN AND AS
DESCRIBED IN KEY NOTE #22 ON SHEET El AND IN SPECIFICATIONS.
MAKE SURE THAT THE NEUTRAL OF THE TRANSFORMER I5 BONDED
WITH THE BUILDING STEEL AND TO THE INCOMING COLD WATER METAL
PIPE WITH EXOTHERMIC WELD CONNECTIONS AS SHOWN ON THE RISER
DIAGRAM.
DESCRIPTION OF LOAD BRK KVA PH LOAD CIR PHASE CIR KVA PH LOAD BRKR DESCRIPTION OF LOAD
AMP P OA OB OC NO A B C NO 0A OB OC !AMP
K 2 DOOR FREEZER (#47A) 20 1 1.79 1 ■ 2 0.29 20 L S KITCHEN L
WORK TOP FREEZER ( #39B) 0.60 3 ■ 4 0.25 � RECESS / PENDANT E,F)
DRINK DISPENSER (( #12) 1.02 5 • 6 1.20 SIGN /UC COVE (C) (T /C)
R POINT OF SALE SYSTEM ( #2)(IG) 0.80 7 • 8 0.19 EMERGENCY/NT/EXIT
'1, POINT OF SALE SYSTEM ( #2)(IG) 0.40 9 • 10 1.35 RACE S G
S�NDWICH TOP REFI G. 39) T 0.56 11 • 12 + 0.36 Mr 'LCD MONITORS e
K ODA DISPENSER_ 7 0.60 13 • 14 0.80 `�r�� BAG & is' S K
R KITCHEN 'ACT' CLE 0.50_ _ 15 • 16 0.50 _IIU SALES AREA RECEPT R
1 Q0 �k� P N S 26 _ _ 1 OD 17 • 18 1.10 fl HEAT LAMP STRIP ( #17) E
K 2 DOOR COOLER ( #47B) 1.25 19 • 20 0.50 TIME CLOCK /TRIP REL /BUZZER 1
2 DOOR COOLER ( #47B) v 1.25 21 • 22 0.56 20 SANDWICH TOP REFRIG (#39) K
HV GAS FRYER ( #24) 20 1 0.36 23 • 24 RESERVED FOR SHUNT TRIP
RESERVED FOR SHUNT TRIP 25 ■ 26 3.24 3 35 L G R CXL` G iID' LE ( #18)
ICE MACHINE ( #29) 20 2 0.75 27 • 28 3.24
.L .�. 0.75 29 • 30 3.24 i i
M EXH /SUPPLY FANS ( #26) 40 3 2.28 31 • 32 RESERVED FPR SHUNT TRIP v
2.28
2.28 35 •
• 36 SPACE
i
SPACE 37 • 38
39 • 40
`. 41 • 42 v
TOTAL 6.72 5.78 5.97
TOTAL CONNECTED KVA OA 0B OC
L LIGHTING: 0.48 1.60 1.56
R RECEPTACLE 0.80 1.40
W WATER HEATER:
H HEATING:
M MOTRO /HVAC /FAN: 2.28 2.28 2.28
T TRANSFORMER /PANEL /ATS:
K KITCHEN EQUIPMENT 7.68 6.40 5.93
E EQUIPMENT /FOOD HEAT LAMP 1.10
1 MISCELLANEOUS 0.50 1.00
5.021 5.90 1 5.90 ITOTAL
OA OB OC
11.74 11.68 11.87 OTAL CONNECTED KVA
98 98 99 OTAL CONNECTED AMPS
(1) PROVIDE LOCK TAB AT THESE BREAKERS IN "ON" POSITION.
(2) INSTALL THIS BREAKER WITH SHUNT TRIP DEVICE.
(3) ROUTE THIS CIRCUIT THROUGH A TIME CLOCK
(4) ROUTE THIS CIRCUIT WITH ISO. GROUND CONDUCTOR.
LIGHTING noun SCHEDULE 0000
8
431He
TTA
TYPE DESCRIPTION MANUFAC. CATALOG LAMP MTG. VOLT REMARKS LAMPS/ BALLASTS BALLAST/ TOTAL
A 2 -LAMPS 2x4 W /ELECTRONIC RAPID 2 ELECTRONIC 1 64
O RECESS TROFFER MERCURY 35E2320CT9A125ELB (2) F032T8/841 RECESSED 120 START BALLAST SYLVANIA
_ QTP2X32T8 /UNV PSX -SC
2 -LAMPS 2x4 W /ELECTRONIC RAPID 2 ELECTRONIC 1 1 64
B r7 RECESS TROFFER MERCURY 35E2320CT9A125ELB (2) FO32T8/841 RECESSED 120 START BALLAST SYLVANIA
QTP2X32T8 /UNV PSX-SC
COUNTER BARTCO BFLSLM -14/6 28W T5 UNDER MINIATURE UNEARE T: INTEGRAL
C I 0 1 COVE UGHT LIGHTING 46 1/16" LAMP COUNTER 120 FLUORESCENT SINGLE 1 BALLAST. 1 28
TELL- 230 -3200 COVE UGHT WIDTH STAGGERED.
6" LAMP OVERLAP.
E ' RECESSED HALO H274HP -•120V F13DTT -Halo Z64 RECESSED 120 1 1 13
DOWN UGHT
DECORATIVE VAXCEL PD30119SN - (1)5DW B10 MPT COORD W /OWNER
LAVA SWIRL MINI CAND C MONOPOINT 120 CALL UGHTING 1 N/A N/A 50
F
CD UGHT PENDANT PENDANT UNIVERSE
INCANDESCENT (800) 801 -2207
EX EXIT UGHT ATUTE PNLRU FURNISHED UNIVERSAL 120 90 MINUTE BAIT. N/A N/A N/A 20
W /UNIT BACKUP POWER
RECESSED PAR 36 SEALED FULL LIGHT OUTPUT ' -
EMERGENCY ENCORE ERG-630-R ERG SE � RECESSED 12 FOR OP TO 4 HOURS N/A N/A N/A
EM LIGHT UGHTING AM LAMP BATTERY CAPACITY 30
OTES:
1 ELECTRICAL CONTRACTOR TO INQUIRE ABOUT LOCAL REBATES ON LIGHT ALL LAMPS TO BE SYLVANIA UNLESS NOTED OTHERWISE.
FIXTURES. �--�
Q2 INSTALLATION OF LIGHT FIXTURES SHALL BE ACCORDING TO PROVIDE UGHT TUBE COVERS, LENSES, ETC., AS REQUIRED TO PROTECT FOOD
MANUFACTURER'S RECOMMENDATIONS AND ACCORDING TO CODE SERVICE AREA.
REQUIREMENTS.
EQUIPM041
-
UST
MARX RESPONSIBILITY QNTY DIMS SPECIFICATIONS: REMARKS:
ITEM/
POINT OF SALE COORD. W /OWNER
2 SYSTEM 3
(SSCI)
6 BOX • -IN 1 COKE CO.
(SSCI)
SODA DISPENSER/ "SITES" #WRD -6 ; REQ. 11OV/20 AMP FIELD VERIFY EQUIP. BEFORE MAKING ANY CUTS IN THE
7 ICE BIN 2 GRND. OUTLET ' 1/2" CW REDUCED COUNTER TOP. FITS CUT OUT MEASURING 23 -1/4 "x23 -1/4"
(SSCI) TO 3/8" W /GAT VALVE. 1 -1/2" DRAIN CONTACT SANDY MANUEL(813)973 -3465 TO COORD. DELIV.
10 MENU BOARD 1 VARIES CUSTOM FABRICATED LCD MONITORS
SEE COORDINATE WITH OWNER
(SSCI) PLAN
DRINK CRATHCO D35
12 DISPENSER 1 115V/fi0 HZ, 8.5 AMPS
(SSCI)
17
ST• RIPE 1 48" W HATCO GRAN -48 SINGLE OVERHEAD GLO -RAY® INFRARED FOODWARMER, HIGH WATTAGE,
6" D WARMER HEAT LAMP TUBULAR METAL HEATER ROD, SINGLE HEATER ROD
(SSCI) 2„ H HOUSING, ALUMINUM CONSTRUCTION, 1100 WATTS, 48"
LONG
ELECTRICAL 1 12` W TAYLOR COMPANY 208 VOLT/ 60 HZ / 30 PROVIDED W/ L15 -30P
18 GRILL 35' D QS12 9.fi KW, 27 AMP
(SSCI) ) 15` 11
i..s �
HIGH VOLUME 20.83 "W FRYMASTER #MJCF UNIT TO BE VENTED UNDER CANOPY W /MECH. EXHAUST
24 GAS FRYER 1 39.86" D. 150,000 BTU /HR SYS. 3/4" I.P.S. MANIFOLD AND GAS CONNECTION.
46" H. PROVIDE "DORMONT"' QUICK DICONNECT SYSTEM. GAS
(SSCI) PRESSURE TO BE 6" W.C. FOR NATURAL OR 11" W.C. FOR
PROPANE.
120/24V SUPPLY GOHZ 1 AMP
26 EXH. HOOD 1 24 "H W /LIGHT FIXTURES LENGTH & WIDTH VARY, SEE PLAN AND HOOD SHOP DWGS.
(SSCI) SEE HOOD DRAWING EXHAUST /SU SMOKE FROM BE CUSTOM SIZED FOR
ANSUL SYSTEM i "ANSUL" PRE -ENG. LIQUID CHEMICAL ASSEMBLY, TESTING AND CERTIFICATION BY GEN. CONTR.
TANKS AND FIRE SUPPRESSION SYS. W /FIXED INSTALL SYSTEM AS CLOSE TO CEILING AS POSSIBLE.
CONTROL NOZZELS. SYS. TO BE UL CLASSIFIED MIN HGT. TO BO-TT. OF UNIT TO BE 6' -6" AFF.
PANEL AND INSTALLED PER NFPA #96 REQ. NOTE: NOZZELS AND PIPING IN PUBLIC VIEW
SYSTEM SHALL BE CAPABLE OF SHALL BE CHROME FINISHED.
AUTOMATIC AND MECH. OPERATION EL.EC: FOR EMERGENCY SHUT OFF, CONNECT CONTROL
W /AUTO SOUNOID GAS VALVE PANEL TO SOLINOID FOR. SHUT DOWN OF GAS SUPPLY
SHUT DOWN. UPON ACTIVATION.
PLUMB:CONNECT ANSUL TANKS TO HOOD W/ RED PAINTED
PIPE. INSTALL GAS SOLINOID VALVE SIZED PER PIPE SIZE.
29 ICE MAKER CUBER "HOSHIZAKI" #KM -630 MAE CUBER ALLOW 6" ATR0V/ ARAN 7EAMB SIMPLEX UNIT. 80" AFF
ICE BIN 22" W. AIR COOLED:
1 30 -1/4" H. 208- 230/60/1 15.0 AMPS (3 WIRE WITH NEUTRAL FOR 115V)
3 WIRE W /NEUTRAL FOR 115V PROVIDE 6' CORD AND PLUG TO UNIT.
BIN B -500PD W/ 6" LEGS: PROVIDE 3/4" INDIRECT WASTE DRAINS FROM BIN &
30" W. CUBER. 3/8" O.D. CONDENSATE AND 1/2" INDERECT
31 -1/2" D WASTE FROM CONDENSER TO FLOOR DRAIN.
( SSCI) 46" H. MAINFOLD AS REQUIRED.
SANDWICH TOP 27" W TRUE
39 REFRIG. 2 34 "D TRUTSSU2712MBA
46 "H 115/60/1 4.6 AMPS 1/5 HP
WORK TOP 1 48 3/8" W TRUE
39B FREEZER TWT -48F
33 "H 115/60/1 5 AMPS 1/5 HP
40 WATER HEATER SEE PLUMBING
1
(CSCI)
2 DOOR 1 5�" TRAULSEN #G22010
47A FREEZER 35" D. 115/60/1 NEMA L14 -20P PLUG
(SSCI) 83" H. 14.9 AMP 3/4 HP
2 DOOR 2 58" L TRAULSEN #RHT232WUT -FHG
47B COOLER 35" D. 115/60/1 NEMA L14 -20P PLUG
(SSCI) 83" H. 10.4 AMP 1/2 HP
51 ELECT. PANELS i SEE ELECTRICAL DWG.
(CSCI)
DATE: 12 -24 -07
JOB NO: 0734
DRAWN:
CHECKED:
U
La-
W
U
(X 44(
W
z�
U f-
Z
L.L.
U
O
D
0
WA 98188
LLJ
J
w
REVISIONS
REVISEP PER LANDLORD
I/23/08
A -20(2)
CONTACT FROM
FIRE DETECTION
SYSTEM.
RELAY SQ. "D" CLASS
8501 TYPE
XM040-V02 120 VAC
COIL, NEMA 1
ENCLOSURE, CLASS -
9991-UE7. _ _
CONTACT
LOCATED IN
ANSUL SYSTEM
CONTROL HEAD.
TO AHU UNIT FAN
CONTROL CIRCUIT
(CONTRACTOR TO
VERIFY)
SHUNT TRIP BREAKER
USED FOR UNDER HOOD
COOKING EQUIPMENT _.
THE TENANT'S FIRE ALARM /PROTECTION. CONTRACTOR TO
VERIFY WITH THE LANDLORD'S ON -SITE REPRESENTATIVE,
EARLY IN PROJECT, THE TYPE OF FIRE LIFE SAFETY SYSTEM
TO BE USED AND THE COMPONENTS THAT WILL BE REQUIRED
TO TIE INTO THE LANDLORD'S SYSTEM. MAKE CONNECTIONS IN
COMPLIANCE WITH NFPA 72 AND LANDLORD'S CRITERIA.
EF1
(3HP)
LANDLORD'S JUNC. BOX.
VERIFY LOCATION. CONNECTIONS
TO THE BASE BUILDING SHALL
BE PROVIDED BY THE LANDLORD'S
CONTRACTOR AT TENANT'S
EXPENSE.
SHUNT TRIP
BREAKERS (TYP)
#10 AWG
GAS SOLENOID
VALVE
HOOD
CONTROL
PANEL
�:=.i
A -17(1) (FOR HOOD
CONT. AND LTS
ANSUL
SYSTEM
CONTROL
PANEL
.-- --PULL STATIONS FURNISHED
3 WITH UNIT. VERIFY LOCATION.
TO HOOD CONTROL
PANEL FOR FAN
SHUT DOWN
SMOKE DET.
VERIFY LOCATION.
TO ANSUL
PANEL
NOTES:
OI ALL WIRING SHALL BE #12 THWN IN 1/2" CONDUIT.
O REFER TO SHEET E -2 FOR SHUNT RELAY TRIP DIAGRAM
AT THIS SHEET
O MAKE ALL CONNECTION OF DUCT DETECTORS AND OTHER FA DEVICES PER
NFPA --72.
ANSUL SYSTEM WIRING DIAGRAM
NOTES:
O1 ALL WIRING SHALL BE #12 THWN IN 3/4" CONDUIT
UNLESS NOTED OTHERWISE.
O2 THE CONTRACTOR SHALL FURNISH AND INSTALL 30A,
208V, 3P, NEMA 3R, DISC SWITCHES AND WIRING FOR
FANS. THE COMPLETE SYSTEM SHALL BE WORKING
AS REQUIRED. REFER KEY NOTE #18 ON SHEET El.
HOOD WIRING DIAGRAM
TOAD `CSS
LOAD VOLT CONNECTED (KVA) FACTOR DEMAND (KVA)
SIGNAGE 120 1.56 125% 1.95
UGHIING (INLAND) 120 1.60 a 125% 2.00
UGHTING (FLUOR) 120 0.48 125% 0.60
TRACK LIGHTS 120 - -- 125% : - ---
HEAT LAMPS 120 1.10 125% 1.38
CONY. OUTLETS 120 2.20 100% 2.20
MISC. 120 1.50 100% 1.50
KITCHEN EQUIP. 120/208 20.01 a 65% 13.00 __21.01 (2)
480 12.00 7.80 �, _
WATER HEATER 480 (1) 65% (1)
AIR COND. OR HT 480 10.56 100% 10.56
MOTORS 208 6.84 100% _ 6.84
LARGEST MOTORS 208 : 3.42 (3) 25% 0.86
XFRMR LOSSES 480 • 45.00 KVA 1.50% 0.68
TOTAL , ( 5785 (3) 1 5a.2
(1) WATER HTR 1S 12 KW, 480V, 30. THIS LOAD IS INCLUDED IN THE
IT H. 0 c _O D
(2) THE KITCHEN LOADS PER N.E.C. TABLE 22 -20, AFTER USING THE
DIVERSITY FACTORS, COME OUT TO BE 20.80 KVA WHICH ARE
LESS THAN THE SUM OF THE TWO LARGEST LOADS (9.72 + 12.0
= 21.72 KW). HENCE TO COMPLY WITH N.E.C. 220 -20 WE
CONSIDERED 21.72 KW FOR KITCHEN APPLIANCES LOADS IN THE
FOLLOWING CALCULATIONS. -
(3) LARG • T MOTOR LOAD IS NOT INCLUDED IN THE CONNECTED
LOAD TOTAL IT 15 NOTED FOR DEMAND LOAD CALCULATIONS
ONLY.
120/2 8. 3� POWER SUPPLY CALCULATIONS:
1. TOTAL DEMAND LOADS = 30.33 KVA
2. DEMAND CURRENT/0 = : : u `5 c 120/208V,30
3. DESIGNED XFRMR = 45 KVA , 480/120- -208V, 3o, 4W.
4. DESIGNED PANEL "A" = 150 AMPS, MCB, 120/208V, 30, 4W
277/480. 30 POWER SUPPLY CALCULATIONS:
1. TOTAL DEMAND LOADS = 50.29 KVA
2. DEMAND CURRENT/0 = 61 AMP C' 277/480V,30
3. LT'S PROVIDED POWER SUPPLY = 200 AMPS, 277/48OV, 30, 4W.
4. DESIGNED NEW PANEL "H" = 200 AMPS, 277/480V, 30, 4W.
GAS SUPPLY SOLENOID
VALVE
SHUNT TRIP RELAY CONTROL
(1) SEQUENCE OF OPERATION: UPON ACTIVATION OF THE ANSUL SYSTEM, AND /OR FIRE
DETECTION SYSTEM. ALL EQUIPMENT UNDER HOOD, AHU UNIT FAN AND GAS SUPPLY
SOLENOID VALVE SHALL AUTOMATICALLY SHUT OFF. EXH FANS SHALL BE LOCKED IN
"ON" POSITION.
DAVID H I ATT
ARCHITECT
4410 W. Melrose Avenue
Tampa, Florida 33629
p. 813.289.3336
f. 813.289.3332
REGISTERED
ARCHITECT
DAVID W. t4IATY
STATE OF WASHINGTON
MAR 1 () 2008
City Of Tukwila
D IiLDING DIVISION
RIM/ SCHEIDS,
CALM AND DETAIL!
SHEET NUMBER
1E4
PERVai i CENTER
CODE COMKiANCe.
NFPA 70 - NEC
BAR 1 25c S3
City Of Tukwila
BUILDING DWISION
CAL S
O
1.0 GENERAL
1.1 BIDDERS QUALIFICATIONS AND INSTRUCTIONS:
1.1.1 QUALIFICATIONS:
THE BIDDERS SHALL BE QUALIFIED, EXPERIENCED, AND LICENSED ELECTRICAL
CONTRACTORS. THEY MUST BE FAMILIAR WITH ALL FEDERAL, STATE, AND LOCAL LAWS,
ORDINANCES, RULES, AND REGULATIONS THAT MAY, IN ANY MANNER, AFFECT THE TASK.
1.1.2 BIDDING INSTRUCTIONS:
BEFORE SUBMITTING THE BID, THE BIDDERS MUST REVIEW THE TENANT INFORMATION AND
CRITERIA MANUAL, SPECIFICATIONS, PLANS, DRAWINGS, AND ALL OTHER CONDITIONS AND
REQUIREMENTS THAT MAY, IN ANY MANNER AFFECT THE WORK UNDER CONTRACT. THEY
MUST VISIT THE SITE OF THE PROPOSED PROJECT TO FAMILIARIZE THEMSELVES WITH THE
LOCAL CONDITIONS, FIRE RATING REQUIREMENTS, AND THE NATURE OF THE PROJECT. THE
PRICING SHALL BE BASED ON THESE SPECIFICATIONS AND THE MATERIALS SHOWN ON THE
DRAWINGS. SUBMISSION OF THE BIDS SHALL BE CONSIDERED AS THE EVIDENCE THAT THE
BIDDER IS FAMILIARIZED TO ALL THE FACETS OF THE SPECIFIED PROJECT. CONTRACTOR
SHALL USE APPLICABLE SECTIONS OF THIS SPEC.
1.1.3 EXCEPTIONS:
ANY EXCEPTIONS, OMISSIONS, DISCREPANCIES, AND DOUBTS REGARDING PLANS, DRAWINGS,
AND SPECIFICATIONS, IF ANY, SHALL BE COMMUNICATED PROMPTLY IN WRITING TO THE
ARCHITECT OR TO THE ENGINEER FOR THEIR REVIEW AND RESPONSE BACK BEFORE THE
BID SUBMISSION DATE. NO ORAL COMMUNICATION REGARDING THE EXCEPTIONS OR
CHANGES SHALL BE ACCEPTED. BIDDERS SHALL BE NOTIFIED OF ANY CHANGES, IF MADE,
DUE TO THE ACCEPTANCE OF EXCEPTIONS BEFORE THE BID SUBMITTAL DATE.
1.1.4 MATERIAL TAKE OFF:
ALL MATERIAL TAKE OFFS, OTHER THAN THE EXISTING DEVICES, SHALL BE MADE USING
THE LIGHT & POWER WIRING AND CONDUIT DRAWINGS AND THEIR ASSOCIATED REFERENCES
INCLUDING THE SPECIFICATIONS OF THIS PROJECT ON THIS DRAWING. ALL LIGHTING
MATERIALS INCLUDING TRANSFORMER, PANELS, FIXTURES, SWITCHES, RECEPTACLES, WIRES
AND RACEWAYS, ETC. SHALL BE PURCHASED BY THE CONTRACTORS PER SECTION NO. 2,
UNLESS NOTED OTHERWISE.
1.1.5 BID PRICE:
THE BID PRICE SHALL INCLUDE LABOR AND MATERIAL COSTS, NECESSARY INSURANCE
COSTS AND PERMITS FEES AS REQUIRED TO INSTALL THE COMPLETE ELECTRICAL SYSTEM
IN COMPLIANCE WITH THE DESIGN REQUIREMENTS OF THIS PROJECT.
1.1.6 SUCCESSFUL BIDDER:
THE SUCCESSFUL BIDDER WILL BE REFERENCED AS THE CONTRACTOR FROM THIS POINT
ONWARDS THROUGHOUT THE REST OF THE SPECIFICATION.
1.2 THE ELECTRICAL CONTRACTOR REQUIREMENTS AND INSTRUCTIONS:
1.2.1 THE CONTRACTOR SHALL USE EXPERIENCED AND SKILLED PERSONS TO PERFORM ALL THE
ELECTRICAL INSTALLATION WORK UNDER THE CONSTANT SUPERVISION OF LICENSED
ELECTRICIANS AND /OR LICENSED JOURNEYMAN ELECTRICIANS.
1.2.2 THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL REQUIRED PERMITS, PAYING
ALL FEES, AND PROVIDING ALL NECESSARY INSPECTIONS INCIDENTAL TO THE ELECTRICAL
PORTION OF THE WORK.
1.2.3
1.2.4
THE CONTRACTOR SHALL BE RESPONSIBLE FOR CARRYING NECESSARY INSURANCE AS
REQUIRED BY LAW TO PROTECT EMPLOYEES, OTHER PERSONS, EQUIPMENT, AND MATERIAL.
THE INSTALLATION WORK SHALL COMPLY WITH ALL APPLICABLE STATE, COUNTY, AND
LOCAL BUILDING CODES. APPLICABLE CODES, AS A MINIMUM, WILL INCLUDE THE LATEST
EDITION OF THE FOLLOWING. THESE WILL BE CONSIDERED PART OF THE SPECIFICATION OF
Tki1IPDOECTCODE OF THE APPLICABLE CITY AND COUNTY.
BB)) NATIONAL ELECTRIC CODE NFPA 70, 2005
C LIFE SAFETY CODE NFPA 101, 2006
D S.B.C.C.I. LATEST EDITION.
1.2.5 IN CASE OF SUBSTITUTIONS THE CONTRACTOR SHALL PROVIDE A WRITTEN REQUEST TO THE
ARCHITECT FOR HIS REVIEW . THE CONTRACTOR SHALL IDENTIFY CLEARLY THE
DIFFERENCE BETWEEN THE SPECIFIED ITEMS AND THE SUBSTITUTE ITEMS, INCLUDING THE
ECONOMIC IMPACT ON THE PROJECT. THE SUBSTITUTE ITEM SHALL NOT BE ORDERED OR
USED UNLESS APPROVED BY THE ARCHITECT AND /OR BY THE OWNER IN WRITING.
1.2.6 THE CONTRACTOR SHALL SUBMIT FIVE SETS OF SHOP DRAWINGS FOR SPECIFIED PRODUCTS ,
AT ONE TIME WITHIN THIRTY (30) DAYS FROM THE OFFICIAL NOTICE TO PROCEED.
SHOP DRAWING SUBMITTAL SHALL BE MADE FOR THE FOLLOWING MATERIALS AND SYSTEMS:
A. LIGHTING FIXTURES, DIMMERS, LAMPS, AND SAFETY SWITCHES.
B. TRANSFORMERS, SWITCH BOARDS, DISTRIBUTION PANELS , DISCONNECTS, AND WIREWAYS
IF PURCHASED NEW.
C. METER CENTERS, CIRCUIT BREAKERS, FUSES, MOTOR STARTERS IF PURCHASED FOR
THIS PROJECT.
D. TIME CLOCK AND OTHER DEVICES. E) SCHEMATIC DIAGRAMS FOR THE ABOVE ITEMS.
1.2.7 THE CONTRACTOR SHALL PROVIDE FOLLOWING DOCUMENTS BEFORE THE CLOSING OF THE
PROJECT AND PRIOR TO THE FINAL PAYMENT:
A. ONE YEAR WRITTEN WARRANTY FOR ANY DEFECT IN WORKMANSHIP, MATERIAL, AND
EQUIPMENT.
B. TWO SETS OF MANUFACTURER'S OPERATIONAL AND MAINTENANCE MANUALS IF
APPLICABLE.
C. MANUFACTURER'S WARRANTIES AND WARRANTY CERTIFICATES.
D. TWO SETS OF REPRODUCIBLE OR RED MARKED UP PRINTS OF "AS- BUILT" DRAWINGS,
ONE FOR THE ARCHITECT AND ONE FOR THE OWNER OF THE PROJECT.
1.2.8 THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE THE NECESSARY TEMPORARY
ELECTRICAL POWER, AT HIS EXPENSE, AS REQUIRED BY HIS TRADE AND BY THE GENERAL
CONTRACTOR.
1.2.9 THE CONTRACTOR SHALL MAKE SURE ON A DAILY BASIS THAT ALL UNNECESSARY
MATERIAL AND TRASH CONTRIBUTED BY HIS TRADE ARE REMOVED.
1.2.10 THE CONTRACTOR SHALL CONCEALED ALL THE CONDUIT IN THE FINISHED AREAS.
2.0 PRODUCTS:
2.1 GENERAL:
THE ELECTRICAL CONTRACTOR SHALL PURCHASE AND USE ALL "NEW" MATERIAL AS
SPECIFIED AND SHOWN ON THE ELECTRICAL PLAN OF THIS PROJECT. ALL THE MATERIAL
SHALL BE FREE FROM DEFECTS AND SHALL CARRY A "UL" LABEL.
2.2 CONDUCTORS:
ALL INSULATED CONDUCTORS SHALL BE UNCOATED COPPER OF 98% CONDUCTIVITY, 600 VOLT
AC, DUAL RATED, TYPE THHN /THWN AS NECESSARY TO MEET THE DESIGN REQUIREMENTS
AND THE APPLICABLE CODES. THW (FOR # 4 AWG AND LARGER) AND THERMO PLASTIC
WIRES RATED FOR 75 DEGREES CENTIGRADE OPERATIONS IN WET AND DRY LOCATIONS AND
9Q DEGREES CENTIGRADE WITHIN ELECTRIC DISCHARGE LIGHTING EQUIPMENT MAY BE USED.
CONDUCTORS NUMBER # 10 AWG AND LOWER SHALL BE SOLID COPPER AND #8 AWG AND
ABOVE SHALL BE STRANDED COPPER. THE MINIMUM SIZE OF WIRE SHALL BE # 12 AWG FOR
20 AMP BREAKER, # 10 AWG FOR 30 AMP BREAKER, # 8 AWG FOR 40 AMP BREAKER.
2.3 CABLE:_
SIGNAL CABLES, IF USED, SHALL BE COPPER AND SHALL MEET ALL UL AND N.E.C. CODE
REQUIREMENTS. METAL CLAD (TYPE MC), ARMORED (TYPE AC) AND NON- METALLIC (NM)
CABLES SHALL NOT BE USED. ALL CABLE ASSEMBLIES SHALL CONTAIN COPPER GROUND
CONDUCTOR.
2.4 CONDUITS:
THE CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT) AND HOT DIPPED GALVANIZED
STANDARD STEEL AS MANUFACTURED BY WHEATLAND TUBE COMPANY OR EQUIVALENT.
2.5 OUTLET BOXES AND FITTINGS:
OUTLET BOXES, FITTING CLAMPS AND HANGERS ETC. SHALL BE GALVANIZED STEEL, RUST
RESISTANT AND COMPATIBLE WITH THE RACEWAY. OUTLET BOXES FOR FIXTURES, SWITCHES,
AND RECEPTACLES SHALL HAVE SMOOTH ROUND EDGES AND SHALL BE WITH COVER PLATES.
BOXES SHALL BE "STEEL CITY" OR EQUIVALENT. FITTINGS FOR EMT CONDUITS SHALL BE
COMPRESSION TYPE. NO SET SCREW WILL BE USED. UNUSED HOLES SHALL BE COVERED WITH
APPROVED INSERT CAPS.
2.6 SWITCHES AND DIMMERS:
SWITCHES AND DIMMERS SHALL BE TOTALLY ENCLOSED, RATED AT 120/277 VOLTS AC, 20
AMPS, 2000 WATTS WITH GRAY TOGGLE AND DEVICE PLATE. THESE SHALL BE QUIET
OPERATION, COMMERCIAL GRADE AS MANUFACTURED BY LEVITON, LUTRON OR EQUIVALENT.
PLATES SHALL MATCH THE SWITCHES. FURNISH IN GANGS AS NECESSARY.
2.7 RECEPTACLES:
RECEPTACLE SHALL BE COMMERCIAL GRADE, 125 VOLTS AC, AND 20 AMPERE RATING WITH
GROUNDED POLE AND TWO CIRCUIT OPTION, AS MANUFACTURED BY LEVITON OR EQUIVALENT.
PLATES SHALL MATCH THE RECEPTACLES. FURNISH IN GANGS AS NECESSARY.
2.8 DEVICE PLATES:
PROVIDE DEVICE PLATE FOR EACH AND EVERY OUTLET BOX. FURNISH IN GANGS AS
NECESSARY. PLATES AND SCREWS SHALL BE GRAY UNLESS THE OWNER PREFERS SOME
OTHER COLOR, AND SHALL BE OF THE SAME MANUFACTURER AS OF THE DEVICES.
2.9 BALLASTS:
BALLASTS FOR FLUORESCENT FIXTURES SHALL BE RAPID START, SYLVANIA ELECTRONIC
ENERGY SAVING, HIGH POWER FACTOR AND SHALL BE CLASS "P," CBM, TITLE 24 CERTIFIED
WITH INTERNAL THERMAL PROTECTOR WITH AUTOMATIC RESET AND CLASS "A" SOUND RATING
NOISE LEVELS LESS THAN 30 dB MAXIMUM. BALLASTS SHALL BE MANUFACTURED BY
SYLVANIA AS SHOWN ON THE LIGHTING SCHEDULE OR EQUAL EQUAL AND SHALL SHALL BE
GUARANTEED AT LEAST FOR FIVE (5) YEARS OF OPERATION AFTER THE ACCEPTANCE. THE
BALLAST MODEL NUMBER SHALL BE "2 OR 4 LAMP PSX -SYL Xtreme AS REQUIRED ".
2.10 LAMPS:
LAMPS SHALL BE MANUFACTURED BY SYLVANIA MODEL # SYL "F028 /841XP /SS /ECO OR
EQUIVALENT. ALL LAMPS SHALL BE GUARANTEED FOR AT- LEAST 4 YEARS OF OPERATION
AFTER THE ACCEPTANCE.
2.11 LIGHTING DEVICES:
ALL LIGHTING FIXTURES, EMERGENCY & EXIT LIGHTS SHALL BE AS LISTED ON THE LIGHT
FIXTURE SCHEDULE; HOWEVER BEFORE PURCHASING ANY LIGHT FIXTURES, SUBMIT FIXTURE.
CUT SHEETS FOR THE ARCHITECT AND THE OWNER'S APPROVAL
2.12 TIME CLOCK OR TIME SWITCH:
TIME CLOCK SHALL BE ELECTRO - MECHANICAL 24 HOURS SEVEN DAYS TYPE WITH RESERVE
POWER AND CONTACTS RATED 40 A. 4 PST AND N.E.M.A. TYPE 1 OR 3R ENCLOSURE. IT
SHALL BE SELF POWERED BY A SELF STARTING SYNCHRONOUS MOTOR WITH MINIMUM 16 HR
SPRING DRIVEN RESERVE POWER AND A DAY OMITTING DEVICE. TIME CLOCK SHALL BE
PARAGON 7007 -0, TORK "W" SERIES, OR APPROVED EQUAL.
2.13 GUARANTEE:
ALL ELECTRICAL EQUIPMENT, MATERIAL AND WORKMANSHIP SHALL BE GUARANTEED FOR A
PERIOD OF ONE (1) YEAR FROM THE DATE OF ACCEPTANCE.
3.0 INSTALLATION INSTRUCTIONS:
3.1 GENERAL:
THE PLAN LOCATION OF LIGHTING FIXTURES, JUNCTION BOXES, CONVENIENCE OUTLETS, AND
PANEL BOARDS ARE APPROXIMATE UNLESS DIMENSIONED AND ARE TO BE ADJUSTED BY THE
CONTRACTOR AS REQUIRED IN THE AREAS WHERE CEILING GRID AND OTHER OBSTRUCTIONS
DETERMINE FIXTURE LOCATIONS. THE CONTRACTOR SHALL COORDINATE WITH OTHER
ARCHITECTURAL, MECHANICAL AND OTHER SYSTEMS TO AVOID INTERFERENCE. ALL CUTTING
AND CONSEQUENT REPAIRS IN CONJUNCTION WITH THE WORK SHALL BE THE RESPONSIBILITY
OF THE CONTRACTOR. BEAMS OR OTHER STRUCTURAL COMPONENT SHALL NOT BE CUT
WITHOUT THE KNOWLEDGE AND WRITTEN CONSENT OF THE ARCHITECT.
3.2 THE CONTRACTOR SHALL PROVIDE ALL NECESSARY MATERIALS, LABOR, TRANSPORTATION,
RIGGING & HOISTING, TOOLS, AND STORAGE, ETC. FOR ALL WORK INDICATED AND REQUIRED
FOR COMPLETE INSTALLATION.
3.3 THE ELECTRICAL WORK SHALL BE EXECUTED IN ACCORDANCE WITH ALL APPLICABLE CODES
AND SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING. WORKMANSHIP
SHALL BE THE HIGHEST QUALITY AS ESTABLISHED BY TRADE STANDARD.
3.4 THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING NECESSARY PERMITS AND
COMMUNICATIONS WITH THE LOCAL BUILDING DEPARTMENT AND INSPECTION PERSONNEL TO
REVIEW CONTRACT DOCUMENTS PRIOR TO INSTALLATION.
3.5 OWNER WILL NOT BE HELD RESPONSIBLE FOR FIELD CHANGES THAT ARISE FROM
CONTRACTOR'S ERROR OR OMISSION OF MATERIALS OR WORKMANSHIP IN WORK
PERFORMANCE.
3.6 THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL UTILITIES PLACEMENT,
AS IDENTIFIED ON THE RISER DIAGRAM, AND LOCATION OF THE ELECTRICAL SERVICE
EQUIPMENT. THE CONTRACTOR SHALL PAY ALL NECESSARY CHARGES ASSOCIATED WITH
INSTALLATION OF ALL UTILITIES TO THE POWER COMPANY PRIOR TO THE CONSTRUCTION. A
LETTER SHALL BE PROVIDED FROM THE POWER COMPANY THAT ALL THE CHARGES HAVE
BEEN PAID IN FULL.
3.7 NECESSARY AND OBVIOUSLY REQUIRED, ELECTRICAL ITEMS THAT ARE NOT SHOWN ON THE
DRAWINGS, SHALL NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILITIES TO INSTALL A
COMPLETE AND SAFE ELECTRICAL SYSTEM.
3.8 THE ELECTRICAL CONTRACTOR SHALL FOLLOW THE SAME COLOR CODE IDENTIFICATION FOR
EACH PHASE THROUGHOUT THE SYSTEM FROM SERVICE SWITCH OR TRANSFORMER THROUGH
ALL BRANCH CIRCUITS.
3.9 ALL SLAB OR ROOF PENETRATIONS SHALL BE MADE WITH APPROVED FIRE RATED SMOKE
BARRIER FITTINGS. PROVIDE ACCESSORIES (PITCH POCKETS, SLEEVES, ETC.) AS REQUIRED.
3.10 JUNCTION BOXES FOR NEON SIGN LIGHTS, SWITCHES, UGHTING FIXTURES, RECEPTACLES AND
FOR PULLING WIRES SHALL BE AS APPROXIMATE AS SHOWN ON THE PLANS BUT EXACT
LOCATIONS SHALL BE GOVERNED BY THE ARCHITECTURAL PLANS.
3.11 ALL OUTLET BOXES SHALL HAVE SQUARE CUT CORNERS. AIR SPACE GREATER THAN 1/8"
AROUND OUTLET BOXES, AND ADJACENT DRYWALL WILL NOT BE PERMITTED. THE
CONTRACTOR SHALL COORDINATE WITH DRYWALL INSTALLER PRIOR TO INSTALLATION. CAULK
AROUND BOXES TO ELIMINATE STEEL OUTLET.
3.12 LIGHTING SWITCHES AND CONVENIENCE RECEPTACLES SHALL BE FLUSH MOUNTED IN
SECTIONAL SWITCH BOXES WITH MATCHING COVER PLATES UNLESS NOTED OTHERWISE.
3.13 THE MOUNTING ARRANGEMENT OF EACH FIXTURE WILL BE DETERMINED BY THE CONTRACTOR
EXCEPT WHERE THE MANUFACTURER HAS GIVEN SPECIFIC MOUNTING INSTRUCTIONS.
3.14 THE CONTRACTOR SHALL FURNISH AND INSTALL ALL LUMINARIES, DEVICES, AND EQUIPMENT
AS SPECIFIED AND SHOWN ON THE PLAN DIAGRAMS. PROVIDE ALL CABLES, CONDUCTORS,
CONDUITS, AND CONNECTIONS AS REQUIRED TO PROVIDE COMPLETE AND OPERATIONAL
ELECTRICAL AND MECHANICAL SYSTEMS. ALL CONDUITS SHALL BE RUN CONCEALED IN
FINISHED AREAS.
3.15 INDIVIDUAL BREAKERS WILL SUPPLY ELECTRICAL POWER TO INDIVIDUAL SIGN OR NEON LIGHT
CIRCUITS. NEON TRANSFORMER EQUIPMENT IS TO BE CONCEALED ABOVE ADJACENT COLUMN
ENCLOSURE OR TO BE INSTALLED AS SHOWN ON ARCHITECTURAL DRAWINGS.
3.16 ALL JOINTS IN CONDUIT AND RACEWAY SHALL BE MADE TIGHT AND BENDS SHALL BE MADE
OVER LONG RADIUS WHERE ENTERING A CABINET AND JUNCTION BOX. THE CONTRACTOR
SHALL SUPPORT ALL CONDUIT AND RACEWAYS SECURELY FROM JOISTS AND /OR BEAMS (TIE
WIRES ARE NOT ACCEPTABLE). THE CONTRACTOR SHALL VERIFY ALL RACEWAY SIZES IN
ACCORDANCE WITH THE N.E.C. CODE. NO CONDUIT SHALL CARRY MORE THAN THREE (3)
CURRENT CARRYING CONDUCTORS. NOTE: ALL JOB CUT THREADS SHALL BE COATED WITH
RUST RESISTANT ZINC CHROMATE FOR THIN WALL EMT.
3.17 LIGHTING CONDUITS SHALL BE SUPPORTED AT EVERY 8 FEET.
3.18 MOUNTING HEIGHT OF LIGHTING EQUIPMENT, UNLESS NOTED OTHERWISE ON ARCHITECTURAL
PLANS SHALL BE APPROXIMATELY AS FOLLOWS:
A. LIGHTING SWITCHES CENTERLINE
B. CONVENIENCE OUTLETS CENTERLINE
C. LIGHTING & POWER PANELS TOP
D. EMERGENCY LIGHT FIXTURES
4 FEET ABOVE A.F.F
1 FEET, 6 INCHES A.F.F
6 FEET, 6 INCHES ABOVE A.F.F
9' ABOVE A.F.F TO BOTTOM OF THE UNIT.
3.19 ELECTRICAL RACEWAYS AND SHALL BE SIZED IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
(N.E.C.), ARTICLE 250. ALL BRANCH CIRCUITS SHALL HAVE A SEPARATE GREEN INSULATED
GROUND WIRE IN EACH CONDUIT RUN. ISOLATED GROUND CONDUCTORS SHALL BE ROUTED TO
THOSE CIRCUITS WHICH NEED ISOLATED GROUND SPECIALLY FOR COMPUTERS AND CASH
REGISTERS.
3.20 THE CONTRACTOR SHALL PROVIDE LIGHTNING PROTECTION VOLTAGE SURGE PROTECTOR FOR
ALL SERVICE PHASE CONDUCTORS TO GROUND (IF IT IS NOT ALREADY THERE IN CASE OF
RENOVATIONS). DEVICE SHALL BE APT TE 400 OR APPROVED EQUIVALENT.
3.21 LUMINARIES SHALL BE AS SPECIFIED IN THE "LIGHTING FIXTURE SCHEDULE ". ALL RECESSED
AND LAY -IN FIXTURES SHALL BE SUPPORTED FROM THE FOUR CORNERS WITH SUPPORTS
CAPABLE OF CARRYING TWICE THE WEIGHT OF THE FIXTURE. ALL SUPPORTS SHALL BE
ATTACHED TO THE JOISTS AND /OR BEAMS. NO LIGHTING FIXTURE SHALL BE INSTALLED
WITHIN 2 FEET OF ANY SPRINKLER HEAD.
3.22 THE CONTRACTOR SHALL INSTALL ALL TELEPHONE JACKS AND WIRING FROM THE MAIN
TELEPHONE TERMINAL BOARD TO THE FINAL TELEPHONE OUTLETS. WIRING SHALL BE
INSTALLED IN A MINIMUM 1/2 INCH CONDUIT.
3.23
3.24
3.25
THE CONTRACTOR SHALL COORDINATE WITH THE FIRE PROTECTION CONTRACTOR AND SHALL
MAKE ALL NECESSARY CONNECTIONS BETWEEN DUCT SMOKE DETECTORS AND HVAC UNITS.
ALL JUNCTION BOXES SHALL BE ACCESSIBLE FROM BELOW. OTHERWISE, CONTRACTOR SHALL
PROVIDE ACCESS PANEL AT ALL JUNCTION BOX LOCATIONS AND SMOKE DETECTORS.
IF NOT ALREADY EXISTING, THE CONTRACTOR SHALL FURNISH ALL THE NECESSARY
DISCONNECT SWITCHES, RELAY BOXES, AND CONTROL BOXES AS REQUIRED AND
RECOMMENDED BY THE HVAC MANUFACTURER FOR THE HVAC UNIT AND WATER HEATER. THE
ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR AND MAKE
ALL NECESSARY CONNECTIONS TO MAKE THE HVAC SYSTEM FUNCTIONAL.
3.26 A PLASTIC COVERED TYPE WRITTEN IDENTIFICATION CARD FOR ALL MAIN AND BRANCH
CIRCUITS INCLUDING SPARES SHALL BE POSTED AT THE INSIDE OF THE PANEL DOOR.
3.27 LOCK-ON DEVICES ON PANEL CIRCUIT BREAKERS FOR NIGHT, EXIT AND EMERGENCY LIGHTING
CIRCUITS SHALL BE PROVIDED AND THE SHALL BE GIVEN TO THE OWNER.
4.0 TRANSFORMER AND PANEL BOARD SPECIFICATIONS
THIS SECTION SHALL APPLY TO THE NEW TRANSFORMER, PANEL BOARDS, CIRCUIT BREAKERS,
PANEL BOXES & TRIMS, DISCONNECT SWITCHES, AND FUSES.
4.1 PANEL BOARDS:
PANEL BOARDS SHALL BE GENERAL PURPOSE N.E.M.A. TYPE 1 OR TYPE 3R ENCLOSURES
SUITABLE FOR SPECIFIED INDOOR OR OUT DOOR LOCATIONS AND AND FLUSH OR SURFACE
MOUNTING APPLICATIONS AS INDICATED ON THE PANEL SCHEDULE. PANEL BOARDS AND THE
INTERNAL COMPONENTS SHALL BE RATED TO PERFORM THEIR FUNCTIONS CONTINUOUSLY AT
40'C AMBIENT AND 50% RELATIVE HUMIDITY. BUSSES, TERMINALS, AND LUGS SHALL BE RATED
AND CAPABLE TO FUNCTION CONTINUOUSLY AT 75 DEGREES CENTIGRADE. PANEL BOARDS
SHALL BE AS MANUFACTURED BY WESTINGHOUSE ELECTRIC CORP., GENERAL ELECTRIC,
SQUARE 'D', CHALLENGER, OR APPROVED EQUAL.
A NAMEPLATE LISTING PANEL NUMBER, TYPE, MANUFACTURER'S NAME, NUMBER OF
PROTECTIVE AND SWITCHING DEVICES, VOLTAGE, CURRENT, PHASE AND AIC RATINGS SHALL
BE PROVIDED.
BRANCH CIRCUITS SHALL BE ARRANGED USING DOUBLE ROW CONSTRUCTION. ALL INTERIORS
SHALL BE COMPLETELY FACTORY ASSEMBLED WITH SWITCHING AND PROTECTIVE DEVICES, WIRE
CONNECTORS, ETC. ALL WIRE CONNECTORS, EXCEPT SCREW TERMINALS, SHALL BE OF THE
ANTI -TURN SOLDERLESS TYPE AND ALL SHALL BE SUITABLE FOR COPPER WIRE OF THE SIZES
INDICATED ON DRAWINGS OR IN THE PANEL SCHEDULES AND CONTINUOUSLY FUNCTIONING AT
75 DEGREE CENTIGRADE.
ALL BREAKERS, SIZED AS SHOWN ON PANEL SCHEDULE, SHALL BE BOLT -ON BREAKERS.
INTERIORS SHALL BE SO DESIGNED THAT SWITCHING AND PROTECTIVE DEVICES CAN BE
REPLACED WITHOUT DISTURBING ADJACENT UNITS AND WITHOUT REMOVING THE MAIN BUS
CONNECTORS AND SHALL BE SO DESIGNED THAT CIRCUITS MAY BE CHANGED WITHOUT
MACHINING, DRILLING, OR TAPPING.
BUS BARS FOR THE MAINS SHALL BE OF COPPER AND SIZED IN ACCORDANCE WITH
UNDERWRITERS' LABORATORIES STANDARDS. UNLESS NOTED OTHERWISE, FULL SIZE NEUTRAL
BARS SHALL BE INCLUDED. BUS BAR TAPS FOR PANELS WITH SINGLE POLE BRANCHES SHALL
BE ARRANGED FOR SEQUENCE PHASING OF THE BRANCH CIRCUIT DEVICES.
THE SHORT CIRCUIT RATING OF THE ASSEMBLED PANEL BOARD SHALL BE IN ACCORDANCE
WITH UL. INC. STANDARDS AND THEIR TEST VERIFICATION.
PHASE BUSSING SHALL BE FULL HEIGHT WITHOUT REDUCTION. CROSS AND CENTER
CONNECTORS SHALL BE COPPER.
NEUTRAL AND GROUND BUSSING SHALL HAVE SUITABLE LUGS FOR OUTGOING FEEDERS
REQUIRING A NEUTRAL AND GROUND CONNECTIONS.
SPACES FOR FUTURE SWITCHING AND PROTECTIVE DEVICES ON LIGHTING AND APPLIANCE
DISTRIBUTION PANELS SHALL BE BUSSED FOR THE MAXIMUM DEVICE THAT CAN BE FITTED
INTO THEM.
PROVIDE BLANK FILLER PLATES IN THE EMPTY SPACES.
4.2 CIRCUIT BREAKER:
THE CIRCUIT BREAKERS ARE TO BE INDUSTRIAL MOLDED CASE BOLT ON TYPE, STANDARD
THERMAL, MAGNETIC, WITH TRIP FREE MECHANISM, THREE POSITION
HANDLES INDICATING "ON" "OFF" AND "TRIPPED" CONDITION.
EACH POLE SHALL PROVIDE INVERSE TIME DELAY AND INSTANTANEOUS CIRCUIT PROTECTION.
THE BREAKER RATING AND CONFIGURATION SHALL BE AS INDICATED ON THE PANEL BOARD
SCHEDULE. ALL MULTI POLE BREAKERS SHALL HAVE AN INTERNAL COMMON TRIP.
ALL BREAKER LUGS SHALL BE SUITABLE TO WITHSTAND 75 DEGREE CENTIGRADE WITHOUT
MALFUNCTIONING.
4.3 PANEL TRIM:
HINGED DOORS IN PANEL TRIMS SHALL COVER ALL SWITCHING DEVICE HANDLES AND SHALL
CONFORM TO THE FOLLOWING REQUIREMENTS:
1. DOORS SHALL NOT UNCOVER ANY UVE PARTS WHILE MAKING SWITCHING DEVICE HANDLES
ACCESSIBLE.
2. DOORS SHALL HAVE FLUSH -TYPE CYLINDER LOCK AND CATCH, EXCEPT THAT DOORS OVER
48" IN HEIGHT SHALL HAVE AUXILIARY FASTENERS AT TOP AND BOTTOM OF DOOR IN
ADDITION TO FLUSH -TYPE CYLINDER LOCK AND CATCH. DOOR HINGES SHALL BE
CONCEALED. ALL LOCKS SHALL BE KEYED ALIKE. DIRECTORY FRAME AND CARD HAVING A
TRANSPARENT COVER SHALL BE FURNISHED ON EACH DOOR.
THE TRIMS SHALL BE FABRICATED FROM CODE GAUGE SHEET STEEL ALL EXTERIOR AND
INTERIOR STEEL SURFACES OF THE PANEL BOARDS SHALL BE PROPERLY CLEANED PRIMED
AND PAINTED IN ACCORDANCE WITH THE MANUFACTURER'S STANDARD SPECIFICATIONS AND
COLOR.
TRIMS FOR FLUSH MOUNT PANELS SHALL OVERLAP THE BOX BY AT LEAST 3/4" ALL
AROUND. SURFACE MOUNT PANELS TRIMS SHALL HAVE THE SAME WIDTH AND HEIGHT AS OF
THE BOX. TRIMS SHALL BE MOUNTABLE BY A SCREW DRIVER WITHOUT THE NEED FOR
SPECIAL TOOLS.
4.4 PANEL BOXE
BOXES SHALL BE MADE FROM UNPAINTED GALVANIZED CODE GAUGE STEEL HAVING MULTIPLE
KNOCKOUTS ON THE TOP AND THE BOTTOM EXCEPT WHERE NOTED OTHERWISE. BOXES SHALL
BE OF SUFFICIENT SIZE TO PROVIDE A MINIMUM GUTTER SPACE OF 4" ON ALL SIDES.
WHERE FEEDER CABLES SUPPLYING THE MAINS OF A PANEL ARE CARRIED THROUGH ITS BOX
TO SUPPLY OTHER ELECTRICAL EQUIPMENT, THE BOX SHALL BE SO SIZED AS TO INCLUDE
THIS WIRING SPACE. THIS WIRING SPACE SHALL BE IN ADDITION TO
THE MINIMUM GUTTER SPACE SPECIFIED ABOVE AND THE LIMITING WIDTH MAY BE INCREASED
ACCORDINGLY. AT LEAST FOUR (4) INTERIOR MOUNTING STUDS SHALL BE PROVIDED.
ALL UNUSED HOLES IN THE BOXES SHALL BE PLUGGED WITH APPROVED INSERT CAPS. BOXES
SHALL BE "STEEL CITY" OR EQUAL.
4.5 DISCONNECT SWITCHES:
THE CONTRACTOR SHALL INSTALL N.E.M.A. TYPE 1 DISC. SWITCHES FOR INDOOR AND N.E.M.A.
TYPE 3R DISC. SWITCHES FOR OUT DOOR APPLICATIONS. ALL DISCONNECT SWITCHES FOR
SERVICE CONDUCTOR ENTRANCES SHALL BE RATED AT LEAST 100K AIC. DISCONNECT
SWITCHES FOR MOTOR CIRCUIT AND FIXED LOAD (SUCH AS HVAC EQUIPMENT, AND WATER
HEATER ETC.) CIRCUITS SHALL BE FUSIBLE OR NON FUSIBLE AS SHOWN ON THE DRAWINGS
OR REQUIRED BY THE MANUFACTURER.
4.6 FUSE:
THE CONTRACTOR SHALL USE DUAL ELEMENT, TIME DELAY CURRENT LIMITING, 100,000 AMP
AIC RATED, CLASS RK -1 FUSES WHEN PROTECTING PANEL BOARDS AND TRANSFORMERS AND
100,000 AMP AIC RATED CLASS RK -5 FUSES WHEN PROTECTING MOTORS UNLESS NOTED
OTHERWISE OR REQUIRED DIFFERENTLY BY THE MANUFACTURER. ALL FUSES IN ANY DISC.. SW
SHALL BE OF THE SAME MANUFACTURER AND SHALL BE MANUFACTURED BY BUSSMANN,
GOULD SHAWMUT OR EQUIVALENT.
.EL01•-- 161
FEB 15 ZOO
PER v i E Ew a` -' 1 .
DATE: 12 -24 -07
JOB NO: 0734
DRAWN:
CHECKED:
REVISIONS
DAVID HIATT
ARCHITECT
4410 W. Melrose Avenue
Tampa, Florida 33629
p. 813.289.3336
f. 813.289.3332
REGISTERED
ARCHITECT
DAVID W. HIATT
STATE OF WASHINGTON
ELECTRICAL
SPECIFICATIONS
SHEET NUMBER
1E4