HomeMy WebLinkAboutPermit EL08-0165 - WESTFIELD SOUTHCENTER MALL - PUMPKIN PATCHPUMPKIN PATCH
1026 SC MALL
07 -10.08
ELO8-165
Cit*f Tukwila •
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tulnvila.wa.us
ELECTRICAL PERMIT
Parcel No.: 6364200010
Address: 1026 SOUTHCENTER MALL TUKW
Suite No:
Permit Number: EL08 -165
Issue Date: 04/09/2008
Permit Expires On: 10/06/2008
Tenant:
Name: PUMPKIN PATCH
Address: 1026 SOUTHCENTER MALL , TUKWILA WA
Owner:
Name: WESTFIELD PROPERTY TAX DEPT Phone:
Address: PO BOX 130940 , CARLSBAD CA
Contact Person:
Name: TIM SCHENK Phone: 800 541 -0821
Address: 1120 E 80 ST, STE 211 , BLOOMINGTON MN
Contractor:
Name: RIVIERA ELECTRIC LLC
Address: 7312 NE PAR LN , VANCOUVER WA
Contractor License No: RIVIEEL942D8
Phone: 503 - 740 -2291
Expiration Date: 03/28/2010
DESCRIPTION OF WORK:
ELECTRICAL FOR NEW TI
Value of Electrical: $24,000.00
Fees Collected:
$594.50
Type of Fire Protection: SPRINIU,ERS /AFA National Electrical Code Edition: 2005
Electrical Service provided by: PUGET SOUND ENERGY
Permit Center Authorized Signature:
I hereby certify that I have read and exed this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied h, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or t1 pe rmance o ork. am authorized to sign and obtain this electrical permit. /J
Signature: Date: % /F7(2J2
Print Name: V ► 11— 0 (3 E-C
ime-7
Date: li . Y V L 1
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: EL -4/07
EL08 -165 Printed: 04 -09 -2008
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
PERMIT CONDITIONS
Parcel No.: 6364200010
Address: 1026 SOUTHCENTER MALL TUKW
Suite No:
Tenant: PUMPKIN PATCH
Permit Number: ELO8 -165
Status: ISSUED
Applied Date: 02/19/2008
Issue Date: 04/09/2008
1: ** *ELECTRICAL * **
2: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical Inspector
at each work site.
3: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical Inspector.
4: All electrical work shall be in accordance with NFPA 70 - NEC, and requirements for electrical installations, Chapter
296 -46B WAC.
5: When any portion of the electrical installation is to be hidden from view by permanent placement of parts of the
building, such equipment shall not be concealed until it has been inspected and approved by the Electrical Inspector.
6: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any violation
of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related documentation that
presumes to grant this authority are therefore not valid.
7: Any change in the scope of work described by the electrical work permit shall require additional work permits. Where
approved plans have been issued, revisions to the plans and additional review may be required.
I hereby certify that I have read these conditions and will comply with them as outlined. All provisions of law and
ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provision of any other work or local
laws regulating construction or the performance of work.
Signature:
Print Name: / t t1
Date: - /7 0
doc: Cond -Elec
EL08 -165 Printed: 04 -09 -2008
CITY OF TUKWILik
Community DevelopmarDepartment
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
htto://www.ci.tukwila.wa.us
Electrical PereNo. EL,(71
Project No.
rot - 0 Flo
(For office use only)
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
SITE LOCATION
Site Address: -S
King Co Assessor's Tax No.: b3G,y20 - 0010
Tenant Name: R.a.nprAyN
Property Owners Name: \ W∎eka C't bCta:k∎ VI
Mailing Address: 11C90 1/41`1% \sr ce crick . \elcx Los Ac e \es, GA ct40Z5
City
Suite Number: 1 Z I S Floor: 1
New Tenant: ® Yes ❑ .. No
State
Zip
CONTACT PERSON - Who do we contact when your permit is ready to be issued
Name: Tim ScywyNt. Day Telephone: KOO ) S41 • OS? L1
Mailing Address: 1 I •PO Ea 4Owi - 'Q 9 t - Sv.kke- Z 11 i g \OCXVN %rig At n 1 M 1•1 2(2)
City a State Zip
Fax Number: °ISZl 4 - VI 09
E -Mail Address: -}A * v S e \C` (2-16evneS . C
ELECTRICAL CONTRACTOR INFORMATION
Company Name: -C; Qt).
Mailing Address:
State
Contact Person:
E -Mail Address:
Contractor Registration Number: Expiration Date:
City
Day Telephone:
Fax Number:
Zip
Valuation of Project (contractor's bid price): $ Z41 060
Scope of Work (please provide detailed information): Nev1_C e kO-c4e S, StA kc. eS, 1kg1nh
CraShvx0p , c L... ∎ t-
Will service be altered? ❑ Yes 1if No Adding more than 50 amps? ❑ Yes in No
Type of Use: MerCAr 'k 11 e_
Type of work:
❑ New ❑ Addition ❑ Service Change ❑ Remodel ® Tenant Improvement
❑ Low Voltage ❑ Generator ❑ Fire Alarm ❑ Telecommunication ❑ Temporary Service
Property Served by:
it Puget Sound Energy
❑ Seattle City Light
H:'\Applicalions \Fortes- Applications On Line4 -2007 - Iilecvical Permit Applicannn. doc
Page 1 of 2
d
RESIDENTIAL
NEW RESIDENTIAL SERVICE
❑ New single family dwellings 5140.00
(including an attachcd garage)
❑ Garages, pools, spas and outbuildings $75.00 ea
$55.00 ea
Low voltage systems
(alarm, furnace thermostat)
RESIDENTIAL REMODEL AND SERVICE CHANCES
❑ Service change or alteration $75.00
(no added /altered circuits)
❑ Service change with added /altered circuits $75.00
number of added circuits 510.00 ea
❑ Circuits added /altered without service change S50.00
(up to 5 circuits)
❑ Circuits added /altered without service change $50.00
(6 or more circuits) $7.00 ca
❑ Meter /mast repair $65.00
❑ Low voltage systems $55.00
(alarm, furnace thermostat)
MULTI- FAMII.,Y AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
❑ Temporary service (residential) S58.00
❑ Temporary service (generator) $75.00
❑ Manufactured /mobile home service 580.00
(excluding garage or outbuilding)
❑ Carnivals $75.00
Number of concessions $10.00 ea
PERMIT APPLICATION NOTES -
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 1 SO days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR ELECTRICAL CONTRACTOR:
Signature:
Print Name:
Day Telephone:
Mailing Address: 1 $ .21) t &Iv trt0 C1v
City
Date:
t-vf. (3i Zoos
( Too Td- l Og zi
State
Zip
Date Application Accepted:
Date Application Expires:
Staff Initials:
n AApplicatinns \Forms- Applications On Lme,4 -2007 - Elecnical Permit Application.doc
hh
Page 2 of 2
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http. / /www. ci. tukwila. wa. us
SET RECEIPT
RECEIPT NO: R08 -01091
Initials: JEM Payment Date: 04/09/2008
User ID: 1165
Payee: BANK OF AMERICA
Total Payment: 565.60
SET ID: 0409
SET TRANSACTIONS:
Set Member Amount
5
475.60
EL08 -377 90.00
TOTAL: 565.60
SET NAME: PUMPKIN PATCH
TRANSACTION LIST:
Type Method Description Amount
Payment Check 10735890 565.60
TOTAL: 565.60
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
ELECTRICAL PERMIT - NONR
000.322.101.00.0 565.60
TOTAL: 565.60
Doc: RECSETS -06
• •
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 -431 -3665
Web site: http: / /www. ci. tukwila. wa. us
SET RECEIPT
RECEIPT NO: R08 -00472
Initials: JEM Payment Date: 02/19/2008
User ID: 1165 Total Payment: 1,408.35
Payee: ELDER -JONES
SET ID: 5000000966 SET NAME: Tmp set/Initialized Activities
SET TRANSACTIONS:
Set Member Amount
D08 -095 1,129.70
LEwO.Se"165) 118.90
M08 -048 130.75
PGO8 -052 29.00
TOTAL: 1,408.35
TRANSACTION LIST:
Type Method Description Amount
Payment Check 50782 1,408.35
TOTAL: 1,408.35
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
ELECTRICAL PLAN - NONRES
PLAN CHECK - NONRES
000.345.832.00.0 118.90
000/345.830 1,289.45
TOTAL: 1,408.35
C779 02/19 9710 TOTAL 1400.35
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION r
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
Project:
fi ! �1„ f'4.
Type of Inspection: Zioo
Address: ` Og( ilfrtit
Date Called:
Special Instructions:
Date Wanted:
7 I
a.m.
p.m.
Requester:
Phone No:
IX Approved per applicable codes. ❑ Corrections required prior to approval.
COMMENTS:
r i
Inspector1
�1
Date:
I Q1I4o
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
'Date:
.01179•415arsalfflalstx48•,..— At_
1
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
643- tuc
Project: [J'jPKJ pt
Type of Inspection:
Address:
Date Called:
Special Instructions:
Date Wanted:
? /Io
P.m.
Requester:
Phone No:
JApproved per applicable codes. EJ Corrections required prior to approval.
COMMENTS:
6/situ ii--414\
Fey DeflarnENtr APFLoJat_-
Pt-0+1r D g -colS
bleu
Inspector:
17 6(4",
Date: 07 ft 4 Oz.
ri $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
IDate:
osnld. ad __ _ ..r..: ° .s - - - ,psi{ � �1 '. -�v *1: wca. -J•'. ..y «>L: �e....or efw.` w- •yS.a_
I
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
61.4%-1475-
Project:
Type of Inspection: 7003
Address:
qu,,144
Date Called:
Special Instructions:
Date Wanted:
6114.,
a.m:
Requester:
Phone No:
Approved per applicable codes. ID Corrections required prior to approval.
COMMENTS:
Pa
04. -
1\10-tt - 'cat-
Inspector:
6(4/46-ik
Date: ail r I O1
El $60.00 REINSPECTION FEE REQUIRED. Prior to inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Receipt No.:
'Date:
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
114-/‘,H
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION -
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)431 -3670
�0
Pr ect:
ri/P /L (m if
Type of Inspection:
"70 0J
Address: ��jj
Date Called:
Special Instructions:
Date Wanted:
�„ /
,I/
a.m.
p.m.
Requester:
Phone No:
proved per applicable codes. ❑ Corrections required prior to approval.
COMMENTS: /0/'%
- 14 //fi AZ/1 /R4iff
Inspecto„f1/2/iL aa7-,6/7,64/6H
Dat -4 # 0
$58.00 REINSPECTION FEE REQUIRED. Prior o inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call the schedule reinspection.
Receipt No.:
Date:
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #1 00, Tukwila, WA 9 81 88
INSPECTION RECORD
Retain a copy with permit
PERMIT NO.
4R.
(206)431 -3670
Pr�ye,ct:
if SAW /N fi r G//
Type of Inspection:
�C /
Address- ,..-
i0,2 6 c /e��/491.
Called:
Special Instructions:
Date Wanted:
1//./-
Requester:
Phone No:
proved per applicable codes. Corrections required prior to approval.
OMMENTS:
f
Inspectors:' GC �' �l 4� /� /'
�cc (!,! C r/
Date: &///,..k y
$58.00 REINSPECTION FEE REQUIRED. Prior o inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call the schedule reinspection.
Receipt No.:
Date:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila, WA 98188 (206)43 1 -3670
11.0E-x r
r
Po
/�
Type of Inspection:
7
Address:
/( SairfX
.Vreit ,
LL
Date Called:
e:
Instructions:
Date Wanted:
OSpecial
.
p.m
�-/
Requester:
Phone No:
❑ Approved per applicable codes. ❑ Corrections required prior to approval.
COMMENTS:
,i6.1". .f.-,AV
f�
(9/4-- cif- /4' _ M ix
nspecto,
/ CertitAll We 11
Date: /fr
El $58.00 REINSPECTION FEE REQUIRED. Prior to inspection. fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call the schedule reinspection.
Receipt No.:
Date:
March 12, 2008
•
Cizy of Tukwila
•
Jim Haggerton, Mayor
Department of Community Development Jack Pace, Director
Tim Schenk
1120 East 80th Street, Suite 211
Bloomington, MN 55420
RE: CORRECTION LETTER #1
Electrical Permit Application Number EL08 -165
Pumpkin Patch— 1026 Southcenter Mall
Dear Mr. Schenk,
This letter is to inform you of corrections that must be addressed before your electrical permit can be
approved. All correction requests from the Building Department must be addressed and reflected on your
drawings.
Building Department: Bill Buterbaugh, at 206 973 -4758, if you have questions regarding
the attached memo.
Please address the attached comments in an itemized format with applicable revised plans,
specifications, and /or other documentation. The City requires that three (3) sets of revised plans,
specifications and /or other documentation be resubmitted with the appropriate revision block.
In order to better expedite your resubmittal, a `Revision Submittal Sheet' must accompany every
resubmittal. I have enclosed one for your convenience. Corrections /revisions must be made in person
and will not be accepted through the mail or by a messenger service.
If you have any questions, please contact me at (206) 433 -7165.
Sincerely,
Brenda Holt
Permit Coordinator
encl
xc: File No. EL08 -165
P:\Permit Center \Correction Letters\2008\EL08 -165 Correction Ltr #1.DOC
jest
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206- 431 -3665
,
Building Division Review Memo
Date: March 11, 2008
Project Name: Pumpkin Patch
Permit #: EL08 -165
Plan Reviewer: Bill Buterbaugh
1. Overcurrent protection on plans does not meet code. Provide
overcurrent protection for the transformer per NEC Table 450..3(B)
� PERMIT COORD COPY •
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: E1_08 -165 DATE: 03 -20 -08
PROJECT NAME: PUMPKIN PATCH
SITE ADDRESS: 1026 SOUTHCENTER MALL
Original Plan Submittal
X Response to Correction Letter # 1
Response to Incomplete Letter #
Revision # After Permit Issued
DEPARTMENTS:
Buil ing i ision 4
Public Works
Fire Prevention
Structural
Planning Division
Permit Coordinator
DETERMINATIO» OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Incomplete n
DUE DATE: 03-27-08
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES/THURS ROUTI G:
Please Route Structural Review Required
REVIEWER'S INITIALS:
❑ No further Review Required
DATE:
APPROVALS OR CORRECTIONS:
Approved Approved with Conditions
Notation:
REVIEWER'S INITIALS:
DUE DATE: 04 -24-08
Not Approved (attach comments)
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents/routing slip.doc
2 -28 -02
OAERMIT COORD COPY
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: EL08 -165 DATE: 02 -19 -08
PROJECT NAME: PUMPKIN PATCH
SITE ADDRESS: 1026 SOUTHCENTER MALL
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # After Permit Issued
DEPARTMENTS: , ,1 3 f 1'D�
Buil mg Division
Public Works
Fire Prevention
Structural
Planning Division
❑ Permit Coordinator
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete [V1
1
Comments:
Incomplete
DUE DATE: 02-26 -08
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
LETTER OF COMPLETENESS MAILED:
TUES/THURS ROUTING:
Please Route
REVIEWER'S INITIALS:
Structural Review Required
n
No further Review Required
DATE:
n
APPROVALS OR CORRECTIONS:
Approved n Approved with Conditions
Notation:
REVIEWER'S INITIALS:
DUE DATE: 03-25-08
Not Approved (attach comments)
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
3.12 .op
Bldg' Fire ❑ Ping ❑ PW ❑ Staff Initial
Documents/routing slip.doc
2 -28 -02
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
REVISION SUBMITTAL
Revision submittals must be submitted in person at the Permit Center. Revisions will not be accepted through
the mail, fax, etc.
Date: 3.19 .0 u
Plan Check/Permit Number: ELO8-165
❑ Response to Incomplete Letter #
• Response to Correction Letter # 1
❑ Revision # after Permit is Issued
❑ Revision requested by a City Building Inspector or Plans Examiner
Project Name: PUMPKIN PATCH
Project Address: 1026 Southcenter Mall
Contact Person: Tim Schenk Phone Number: I •`340.9 .0 $Z I
Summary of Revision: fZtahS •f (hGC �3 Iv PoRtess ComM ,ICS Frukt -.
(Stu-- NI reezawcf
^rpVFiEre:: dr :0
MAR, :).0 1 7P. R
Sheet Number(s): E 3
"Cloud" or highlight all areas of revision including date of revision
Received at the City of Tukwila Permit Center by:
11 Entered in Permits Plus on 7�Z-6—()5
\applications\forms - applications on line \revision submittal
Crcated: 8 -13 -2004
Revised:
Look Up a Contractor, Electen or Plumber License Detail
Washington State Department of Labor and Industries
Electrical Contractor
A business licensed by L &I to contract electrical work within the scope of
its specialty. Electrical Contractors must maintain a surety bond or
assignment of savings account. They also must have a designated
Electrical Administrator or Master Electrician who is a member of the
firm or a full -time supervisory employee.
License Information
License
RIVIEEL942D8
Licensee Name
RIVIERA ELECTRIC LLC
Licensee Type
ELECTRICAL CONTRACTOR
UBI
602597971
Ind. Ins. Account Id
Business Type
LIMITED LIABILITY COMPANY
Address 1
7312 NE PAR LN
Address 2
City
VANCOUVER
County
CLARK
State
WA
Zip
98662
Phone
5037402291
Status
ACTIVE
Specialty 1
GENERAL
Specialty 2
UNUSED
Effective Date
3/28/2006
Expiration Date
3/28/2010
Suspend Date
Separation Date
Parent Company
Previous License
Next License
Associated License
BECK *M *9440L
Electrical Administrator Information
License
BECK *M *944OL
Name
BECK, MIRCHA
Status
ACTIVE
Business Owner Information
Name
Role
Effective Date
Expiration Date
BECK, MIRCHA
PARTNER/MEMBER
03/28/2006
Bond Information
Bond Bond I
Page 1 of 2
https: // fortress. wa. gov /lni/bbip /printer.aspx ?License= RIVIEEL942D8 04/09/2008
TC
2
PROVIDE FLUSH MOUNTED SHO
WINDOW RECEPTACLE IN;CEILIN
-ABOVE PER NEC REQUIREFMENTSj
'
-' TYPICAL FOR (2). 1 I
i
_____11 �L.__�_J I{1 . _.!
I
CLG
ABV
Z.:
1
'12" CONDUIT w/PULLSTRING
TO ALARMIPANEL. FIELD
VERIFY LQ�CATIONS
•
LIGHTING CONTRQL CABINET "LCC"
PROVIDE WITH 2HR MAX OVERRIDE &
ASTRO TIMECLOCK AND ALL REQUIRED
PROGRAMMING AND TESTING PER
ENERGY CODE REQ'MTS.
(PCI # LITEKEEPER -16), OR EQUAL
r-
r
I iiW l
L —_O
120V
CONTROLS
PANEL "LV"
120/208V -30-4W
TRANSFORMER "TA"
"LV.-8
-I } l __ _... _ � —..
4
Imm_i_
L
PROVIDE - DELIVERY BUZZER
MOUNTED ABOVE CEILING.
CONNECT TO TRANSFORMER
MOUNTED IN STOCKROOM.
SEE ARCHITECTURAL DRAWINGS
FOR -EX CT LOCATION AND TYPE.
SECURITY PANEL
COORDINATE WITH PUMPKIN PATCH
PROJECT MANAGER FOR EXACT
LOCATION PRIOR TO ROUGH -IN.
"LV"- 26,28,30
"LV "- 20,22,24
LOCATE AND INTERCEPT EXISTING TELEPHONE
CONDUIT STUBBED FROM MAIN TELEPHONE
BOARD BY LANDLORD AND EXTEND TO NEW
TENTANLTELEHQNE.B.QARD'�'TTB." FIELD
VERIFY EXACT ENGTH PRIOR TO BIDDING.
6I
26 IG L1. +18'
26 10
28 1G
18
"LV" -16,18 16
-
— - TF7'9 TB"
APPROVED P' 1P,D Cr.'77,;T :Orriltn
r- - :- 'c MODIFIED CR ALTERS)
wimo JI AUTHORIZATION FROM THE BUILDING
, AL' WORK SHALL BE DONE IN
ACCORDANCE •N. r' THE APPROVED PLANS AND
is 2.:' ;T TO F;: =' D'!i PrC11OH3.
CAT5E 11TP CABLE
COUNTER
FOR INQUIRIES PLEASE
CONTACT:
colinsppumpkinpatch.co.nz
+649 272 0765
+6421 607 770
LJ LJ LJ LJ LJ
EFT DATA1 PHONE DATA2 EFT
POS1 POS2
ALL COUNTER OUTLETS ARE FACEPLATES WITH DUAL RJ45 CAT5E
SOCKETS.
DATA1 & DATA2 ON COUNTER TO NORMAL TCP /IP STANDARDS
EFTPOS1 & EFTPOS2 ON COUNTER CABLE TO CONNECTING DEVICE
STANDARD
8 PORT ADSL ROUTER
SWITCH (P/P CABLE (P/P
SUPPUED) (P/P SUPPUED)
SUPPUED)
CAT5E PATCH CABLE
DATA1 PHONE
ADSL DATA2
t] �
El
STOCKROOM
CONTROLLER
SUPPLIED)
FAX
CAT5E UTP CABLE
AU STOCKROOM OUTLETS ARE FACEPLATES WITH DUAL RJ45 CAT5E
SOCKETS
DATA1 & DATA2 IN STOCKROOM TO NORMAL TCP /IP STANDARDS
PHONE/FAX/ADSL IN STOCKROOM CABLE TO CONNECTING DEVICE
MAIN STOCKROOM STANDARD
E1
PHONE LINE
FAX AND ADSL OR
BROADBAND
EFTPOS /ALARM
MONITORING
EFTPOS
ALARM CONTROL UNIT
(SECURITY COMPANY
SUPPUED)
TYPICAL WIRING DIAGRAM
NO SCALE
1"C. TO MGR DESK (DATA)
1"C. TO "TTB" (TELE)
"LV "-10,12
#10
"LV" -38/40
L
1 20V
CONTROLS
"LV" -2,4,6
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
POWER & SIGNAL PLAN
SCALE: 1/4" =11-0"
1.
GENERAL NOTES:
SECURITY ALARM AND TELEPHONE SYSTEMS SHALL BE INSTALLED BY THE
TENANT AFTER FIXTURE INSTALLATION. CONDUIT (WHERE REQUIRED BY
LOCAL CODE), BOXES AND PULLWIRES TO BE PROVIDE BY THE ELECTRICAL
CONTRACTOR. COORDINATE WITH SECURITY AND TELEPHONE SYSTEMS
INSTALLER AT JOBSITE.
2. REFER TO MECHANICAL DRAWINGS FOR EXACT HVAC EQUIPMENT LOCATIONS
AND SPECIFICATIONS. VERIFY EQUIPMENT WIRE SIZE, CONDUIT SIZES, CIRCUIT
BREAKER AND DISCONNECT SIZES WITH MECHANICAL CONTRACTOR PRIOR TO
ROUGH -IN OF ELECTRICAL.
3. ALL CONNECTIONS TO HVAC EQUIPMENT SHALL MADE WITH COPPER COND-
DUCTORS ONLY. SIZE CONDUCTORS PER UNIT NAMEPLATE SPECIFICATIONS.
VERIFY PRIOR TO INSTALLATION OF CONDUCTORS.
4. ALL DISCONNECT SWITCHES SHALL BE FUSIBLE, SIZE AS REQUIRED. ALL
HVAC UNITS SHALL BE FUSED PER EQUIPMENT NAMEPLATE SPECIFICATIONS.
ELECTRICAL CONTRACTOR SHALL VERIFY DISCONNECT AND FUSE SIZING
WITH MECHANICAL CONTRACTOR PRIOR TO ORDERING MATERIALS.
5. ALL FUSES FOR THIS PROJECT SHALL BE BUSSMAN CLASS RK5 DUAL
ELEMENT CURRENT LIMITING WITH AMPERAGES AS INDICATED OR REQUIRED.
6. REFER TO MECHANICAL DRAWINGS FOR CONTROL WIRING. ELECTRICAL
CONTRACTOR SHALL PROVIDE CONDUIT FOR CONTROL WIRING AS
REQUIRED. COORDINATE WITH MECHANICAL CONTRACTOR AT JOBSITE.
7. FIRE SEAL ALL FIRE WALL PENETRATIONS FOR CONDUITS WITH AN
APPROVED FIRE SEALANT AFTER CONDUIT INSTALLATION. FIRE SEAL
SHALL PROVIDE EQUAL FIRE RATING AS WALL.
8. 20A, 120V RECEPTACLE AND LIGHTING CIRCUIT CONDUCTORS OVER 75 FT.
LONG SHALL BE #10 AWG CONDUCTORS IN LIEU OF #12 AWG.
9. MOUNT ALL FIXTURE JUNCTION BOXES ABOVE ACCESSIBLE CEILING WHEN
APPLICABLE.
L
REVIEWED FOR
CODE FP OP COMPLIANCE
N A NEC E
APR - 7 2008
"LV" -36
PROVIDE 1W
EXTENSION
RINC3 E R
OUTLETS @
MANAGER'S
DESK TO
ALLOW FOR
CABINETRY.
+40" A.F.F.-
PROVIDE PUSH - BUTTON, TRANSFORMER,
WIRING, BU77FRS & CONNECTIONS FOR
DELIVERY CALL SYSTEM.
')LV " -14
C
City -Of Tukwila
BUILDING D ION •
SEPARATE PERMIT
REQUIRED FOR:
Et:Mechanical
❑ Electrical
lumbing
Gas Piping
City of Tukwila
BUILDING DIVISION
--1
NOTE:
ELECTRICAL CONTRACTOR TO PROVIDE
AND INSTALL ALL INTERCONNECTING
CONTROL WIRING, CONTACTORS AND
CONDUIT FOR HVAC UNITS AS REQUIRED.
PROVIDE SLAVE RELAY AFTER TIMECLOCK
w/ NORMALLY OPEN & NORMALLY CLOSED
CONTACTS FOR HVAC CONTROL. SEE
MECHANICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
NOTE TO CONTRACTOR
THE CONTRACTOR SHALL THOROUGHLY REVIEW THESE
ELECTRICAL CONSTRUCTION DOCUMENTS PRIOR TO
PREPARING A BID FOR THE ELECTRICAL WORK SHOWN.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD
VERIFICATION OP EXISTING ELECTRICAL SERVICES AND
CONNECTION REQUIREMENTS. THE CONTRACTOR SHALL
NOTIFY THE ENGINEER IMMEDIATELY OF ANY CONFLICTS
OR DISCREPANCIES FOUND PRIOR TO BID. BY SUBMITTING
A BID FOR THE ELECTRICAL WORK THE CONTRACTOR IS
AFFIRMING THAT THE REQUIRED FIELD VERIFICATION OF
EXISTING CONDITIONS HAS BEEN COMPLETED AND
ASSUMES FULL RESPONSIBILITY FOR CONFLICTS FOUND
AFTER THE AWARD OF THE ELECTRICAL CONTRACT. NO
ADDITIONAL COMPENSATION WILL BE CONSIDERED FOR
CONFLICTS AND /OR DISCREPANCIES FOUND TO EXIST
AFTER THE AWARD OF THE ELECTRICAL CONTRACT.
Permit No.
PIar review approval Is object to enzirs and ohs.
Approval of construction doh does not authorize
the violation of any act code or ordnance. Receipt
of approved Field Copy and conditions is :
BY
Date :,
City of Tukwila
BUILDING DIVISION
Public Works, Building Division
PERMIT NUMBER
RECEIVED
CITY OF TUKWILA
FEB 19 2008
PEKMIT CENTER
*LN--
INT
ELECTRICAL ENGINEERING, INC
1786 Augusta Ls Ste B. Yuba City, CA 95993
Pk 530.790.0620 Fax: 530.67t9792
ISMEEMMMI
DATE: 1 -28 -08
JOB NO: 07142
DRAWN: JP
CHECKED: JL
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635 -5696
FAX: (817) 635 -5699
z
U
z
SOUTHCENTER
J
W
L.�
N M
W M
SOUTHCENTER MALL
TUKWILA, WA
EXPIRES 06- 23-08
REVISIONS
ISSUED FOR PERMIT /CONSTRUCTION
28 JAN. 08
INEEMMM
POWER AND SIGNAL
PLAN
SHEET NUMBER
E -1
PROVIDE DISCONNECT, J -BOX AND
CONNECTION TO TENANT SIGNAGE.
COORDINATE EXACT LOCATION AND
REQUIREMENTS WITH SIGNAGE
CONTRACTOR IN FIELD PRIOR TO
ROUGH -IN OF ELECTRICAL.
15
r —
13
9.9. .91299,9 91:mcwas.19:999.9
sw
lI
iV
O�7c
17d,e
"LV " -1,3 VIA
"LCC"
sw
17
'
-- 17
[ EKfffVL_
®1 3b
17d,e
PORTAL SHOWN HERE FOR CLARITY
PORTAL LIGHTING AND
SIGNAGE POWER TO BE
ROUTED FROM BOTTOM. NO
CONNECTIONS AVAILABLE
FROM ABOVE.
I 1
L PROVIDE UN- SWITCHED CIRCUIT
FOR EMERGENCY AND NIGHTLIGHT
FIXTURES AS REQUIRED, TYPICAL.
17d.e
PROVIDE OUTLET MOUNTED ABOVE
ACCESSIBLE CEILING. FIELD VERIFY
EXACT LOCATION.
J JIM
r
17d,e
"LV" -13,15 VIA
"LCC"
PROVIDE FLUSH MOUNTED J -BOX WITH FLEX
CONNECTION T DISPLAY CABINET MOUNTED LIGHTING.
CONDUIT TO BE CONCEALED IN WALL, TYPICAL
NOTE:
E.C. TO FIELD ADJUST OR STAGGER COVE STRIP FIXTURES AND
CABINET FIXTURES AS REQUIRED. FIELD VERIFY.
NOTE: 2006 IBC — Sec. 1006
Provide an average of one
foot - candle illumination at the
floor along the entire egress
pathway and exit discharge
LIGHTING PLAN
SCALE- -u4" = 1' -0"
FIXTURE SCHEDULE
TAG
DESCRIPTION
MANUFACTURER
VOLTS
LAMPS
VA
MOUNTING
REMARKS
CAM)
ROUND SEMI - RECESSED
METAL HALIDE ADJUSTABLE
WALL WASHER
LITON
# LHMB6070A w/ LR6277 -23W
120
1 -70W MH
86
RECESSED
(I;)
8" DIA RECESSED TWIN
LAMP FLUOR. DOWNLIGHT
WITH GLASS TRIM
LITON
# LFHN8242UE w/ LR852W -FR
120
(2) 42W CFL 841
84
RECESSED
SAME AS TYPE "B"
EXCEPT WITH BATTERY
BACKUP.
LITON
# LFHN8232UE -EM w/ LR852W -FR
120
(2) 32W CFL 841
64
RECESSED
CONNECT TO UN-
SWITCHED CIRCUIT
AS REQUIRED
BE
RECESSED LOW VOLTAGE
DOWNLIGHT w /ELEC TRANS.
LITON
# LR1424W w/ LH99 -GU10
120
1 -16W LED
16
RECESSED
O4"
RECESSED LOW LEVEL
AISLE STEPLIGHT
DABMAR
# DSL- 1043SS w/ 13WPU841
120
1 -13W PL
13
RECESSED
4 FT, SINGLE LAMP
FLUORESCENT
STRIPLIGHT
SIMKAR
# CH132 -BII -UNV w/ (1) WG140
120
1 -F32T8 -741
40
CHAIN HUNG
PROVIDE SURFACE
MOUNT WHERE
REQUIRED.
0
4 FT, SINGLE LAMP
FLUORESCENT
STRIPLIGHT
SIMKAR
# CH132-BII-UNV
120
1 -F32T8 -741
40
COVE
0
LOW VOLTAGE PENDANT
LIGHT WITH INDIVIDUAL
TRANSFORMER
LITON
# LPR1012N -N w/ RS12 -80M
120
1 -16W LED
16
PENDANT
0
RECESSED LED EDGE -LIT
EXIT SIGN w/BATT. BACK -UP
ROYAL
# RXL21GA
120
w /FIXTURE
5
RECESSED
CONNECT TO UN-
SWITCHED CIRCUIT
AS REQUIRED
0
0
COMBO EXIT AND TWIN
HEAD EMERGENCY LIGHT
WITH BATTERY BACK -UP
# NEX- 705 -LED /G
120
w /FIXTURE
5
RECESSED
CONNECT TO UN-
SWITCHED CIRCUIT
AS REQUIRED
1
MASTER SWITCH LOCATION
"a" - 50% SALES LIGHTING
"b" - 50% SALES LIGHTING
"c" - SALES DISPLAY LIGHTS
"d" - BON LIGHTING
PROVIDE 3- POSITION LOW
VOLTAGE SWITCHING.
PROVIDE WALL MOUNTED
OCCUPANCY SENSOR
(HUBBELL #IWSZPM) OR
EQUIVALENT.
(AUTO ON /OFF 30 MIN MAX)
t4
b LV
c LV
d LV
#14
TO "LCC"
NL
17
17d
TOGGLE SWITCH TO
BE DOWNSTREAM OF
M k ER CONTROL
SWITCH "d ".
EM X1 1,
REVIEWED FOR
CODE COMPLIANCE
NFPAi0 -NEC
APR - 7 2008
BUILDING �i� flf Tukwila
DIVV ION
1(eC
EED
CITY TUKWILA
FEB 19 2008
PtriMi f LENTER
IMMIMMME
DATE: 1 -28-08
JOB NO: 07142
DRAWN: JP
CHECKED: JL
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635 -5696
FAX: (817) 635-5699
L J
z
n�
0
SOUTHCENTER
J
W
L.�
N
W
SOUTHCENTER MALL
TUKWILA, WA
EXPIRES 06 -23-08
REVISIONS
ISSUED FOR PERMIT /CONSTRUCTION
28 JAN. 08
LIGHTING
PLAN
SHEET NUMBER
IiHT E - 2
ELECTRICAL ENGINEERING. INC
1786 Augusta Ln Ste B, Yuba City, CA 95993
Ph: 530.790.0620 Fa= 530.671.9792
1
MALL ELECTRICAL ROOM
J
2
TENANT SPACE
N./
EPM-
4000
- EXISTING LANDLORD PANEL "1 F"
800A, 277/480V, 30-4W, 800A
(FIELD VERIFY AIC)
14,801
T1215
(E)
200AF o
(E) EPM -4000
INTERFACE-
EXISTING LANDLORD METER CENTER -
PROVIDE 200A FUSES IN LANDLORD'S
SWITCH (FIELD VERIFY REQUIREMENTS)
EXISTING (4) #250KCMIL,
(1)#4G,AL MC CABLE.
(E) 2 "C. w/ NEW 3 # 1 THWN CU
& 1 # 8 CU GROUND
BY ELEC. CONTRACTOR
PROVIDE #4 AWG CU GND.
TO NEAREST BLDG. STEEL
PER NEC REQUIREMENTS.
(E)
200AS
100AF
EXISTING (3) #3, 1 - #8G, 1 1 /4 "C (CONDUIT
STUB TO TENANT SPACE BY L.L.)
ELECTRICAL CONTRACTOR TO PROVIDE
NEW FUSES TO MATCH EXISTING
LANDLORD EQUIPMENT. FIELD VERIFY
EXACT REQUIREMENTS.
ELECTRICAL CONTRACTOR TO INTERCEPT
EXISTING TENANT FEEDER & CONDUIT
AND EXTEND TO RELOCATED EQUIPMENT
AS REQUIRED. PROVIDE NEW PRIMARY
DISCONNECT AND FUSES AS SHOWN
NEW 1 "C.wl3 #4THWNCU &1
# 8 CU GROUND
NEW TRANSFORMER 'TA"
1 _ , 1 45 KVA DRY -TYPE, 30 TRANSFORMER,
480V DELTA - 120/208 WYE FLOOR
MOUNTED. CLASS 1 EFF. (NEMA TP -1)
2
NEW 2 "C. w/4 # 1/0 THWN CU
& 1 # 6 CU GROUND
0
150A
3P
NEW
PANEL
"LV"
ONE LINE DIAGRAM
NO SCALE
NOTE:
E.C. TO FIELD VERIFY ALL ELECTRICAL EQUIPMENT AND SIZES FOR CONDUIT,
WIRE, AND BREAKERS. E.C. SHALL MAKE APPROPRIATE ADJUSTMENTS SO THAT
WORK COMPLIES WITH THE NEC.
TC
TC
TC
TC
TC
TC
SW
SW
LO
GENERAL NOTES:
1. ALL THE ELECTRICAL SERVICE SHOWN ON THE ONE LINE DIAGRAM IS THE TENANT ELECTRICAL
CONTRACTOR'S RESPONSIBILITY. RESPONSIBILITY INCLUDES COORDINATION WITH THE LOCAL
SERVING POWER COMPANY.
2. CIRCUIT BREAKER TYPE PANELBQARDS WITH BOLT -ON TYPE CIRCUIT BREAKERS WITH ADEQUATE
INTERRUPTING CAPACITY SHALL BE INSTALLED.
3. THE GROUNDING SYSTEM WITHIN THE PREMISE SHALL BE CONTINUOUS FROM THE SYSTEM GROUND
IN THE METER ROOM. THE SECONDARY OF THE TENANT TRANSFORMERS SHALL BE GROUNDED IN
ACCORDANCE WITH THE N.E.C.
4. ALL WIRING METHODS SHALL BE IN ACCORDANCE WITH LOCAL AND NATIONAL CODES. ALL POWER
WIRE IN THE PREMISE SHALL BE INSTALLED IN CONDUIT. CONDUCTOR INSULATION SHALL BE THW,
THHN, OR THWN. NO ROMEX WIRES ARE ALLOWED. LOW VOLTAGE CABLES MAY BE INSTALLED
WITHOUT CONDUIT WHERE PERMITTED BY LOCAL CODE AND INSPECTION AGENCIES.
5. ALL ELECTRICAL MATERIALS SHALL BE NEW AND SHALL BE NATIONAL ELECTRICAL CODE STAN-
DARD UNLESS BETTER GRADE IS REQUIRED BY LOCAL CODE, AND SHALL BEAR THE UNDER-
WRITERS' LABORATORIES LABEL.
6. ALL TELEPHONE SERVICES SHALL BE PROVIDED BY THE TENANTS ELECTRICAL CONTRACTOR. ALL
TELEPHONE CHARGES SHALL BE PAID BY THE TENANT'S ELECTRICAL CONTRACTOR DIRECTLY TO
THE TELEPHONE UTILITY COMPANY FURNISHING THE SERVICE. COMPLETE CONDUIT SYSTEM, IF
REQUIRED, SHALL BE PROVIDED BY TENANTS ELECTRICAL CONTRACTOR FOR UTILITY COMPANY
WITH PULL WIRES INSTALLED IN ALL CONDUIT.
7. WHEN SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM. PLENUM NONCOMBUSTIBLE.
CONSTRUCTION MATERIALS TO BE USED ABOVE CEILING, INCLUDING EXISTING AND NEW WIRING
EXCEPT INSULATION OF 25 FLAME SPREAD AND 50 SMOKE DEVELOPMENT FINISH RATING. LOW
VOLTAGE OR LIMITED POWER WIRING MAY BE LABELED PLENUM RATED TYPE ALL PER OMC M -3032.
LOAD CALCULATIONS:
NEW PANEL "LV"
LIGHTING (CONNECTED)
SIGNAGE =
SHOW WINDOW - 20' @ 200W/LF
RECEPTACLES - 28 @ 180W EACH
INST WATER HEATER "WI-1"-1
MICROWAVE
REFRIGERATOR
SUB -TOTAL
25% CONTINUOUS LOAD
25% LARGEST MOTOR
TOTAL
FOR 120/208V -30-4W SYSTEM
31,553W- (208VxV3)= 87.6AMPS
THEREFORE A 150 AMP FEEDER IS ADEQUATE.
FOR 277/480V -30-4W SYSTEM
31,553 W - (480V xV3) = 38.0 AMPS
THEREFORE A 100 AMP FEEDER IS ADEQUATE.
10,170 W
1,200 W
4,000 W
5,040 W
3,000 W
1,500 W
700 W
28,610 W
2,843 W
100 W
31,553 W
SW
LO
LO
LO
LO
LO
SYMBOL LEGEND
•
•
2
3
M
acc
V
0
La
LEI
LD
0
EMI
FLUORESCENT LIGHT FIXTURE - SURFACE MOUNTED
INCANDESCENT LIGHT FIXTURE - PENDANT MOUNTED
FLUORESCENT STRIP LIGHT - SURFACE MOUNTED UNO
INCANDESCENT / FLUORESCENT / HID LIGHT FIXTURE - RECESSED
INCANDESCENT LIGHT FIXTURE - SURFACE MOUNTED
INCANDESCENT LIGHT FIXTURE - WALL MOUNTED
EXIT LIGHT - CEILING MOUNTED WITH EMERGENCY LIGHTS
EXIT LIGHT - WALL MOUNTED WITH ARROWS AS SHOWN
EMERGENCY LIGHTING FIXTURE - SURFACE MOUNTED
SINGLE POLE TOGGLE SWITCH, @ +46" UNO
TWO POLE TOGGLE SWITCH, @ +46" UNO
THREE -WAY TOGGLE SWITCH, @ +46" UNO
MOTOR RATED SINGLE POLE SWITCH, @ UNIT UNO
MASTER LIGHTING CONTROL STATION
OCCUPANCY SENSOR @ +46" UNO (LEVITON # 00515)
FIXTURE TAG: LETTER INDICATES TYPE
JUNCTION BOX, SIZE & TYPE AS INDICATED OR AS REQUIRED
15 OR 20 AMP 125V 3W DUPLEX RECEPTACLE, @ +16" UNO
15 OR 20 AMP 125V 3W DOUBLE DUPLEX RECEPTACLE, @ +16" UNO
CEILING MOUNTED DUPLEX RECEPTACLE
NON -FUSED DISCONNECT SWITCH
CIRCUIT BREAKER DISCONNECT SWITCH
FUSED DISCONNECT SWITCH, SIZE PER UNIT LABEL
MOTOR, N.I.E.S. CONNECT AS REQUIRED, NUMBER INDICATES HP
CONTROL EQUIPMENT, N.I.E.S. CONNECT AS REQUIRED
PANELBOARD - SEE SCHEDULE
MAIN SWITCHBOARD OR MOTOR CONTROL CENTER, SEE ONE LINE DIAGRAM
DISTRIBUTION TRANSFORMER, MOUNTING AS NOTED
TERMINAL CABINET, SIZE & TYPE AS NOTED
CEILING EXHAUST FAN
DATA OUTLET, 4" SQ. BOX w/ SINGLE DEVICE RING & PLATE @ +16" UNO
TELEPHONE OUTLET, 4" SQ. BOX w/ SINGLE DEVICE RING & PLATE @ +16" UNO
DUPLEX RECEPTACLE FLUSH w/ FINISHED FLOOR
CEILING MOUNTED DATA OUTLET
TELEPHONE TERMINAL BOARD: 4' x 8' x r PLYWOOD OR AS NOTED
w/ DOUBLE DUPLEX RECEPTACLE & 1 #6 GND
-LV-- LOW VOLTAGE WIRING IN CONDUIT
[" CONDUIT RUN CONCEALED BELOW FLOOR OR FINISHED GRADE, U.N.O.
r CONDUIT CONCEALED IN CEILING OR WALL, U.N.O.
HOMERUN TO RESPECTIVE PANEL OR TERMINAL CABINET - OVERHEAD
HOMERUN TO RESPECTIVE PANEL OR TERMINAL CABINET - UNDERGROUND
CONDUIT RISER - UP
CONDUIT RISER - DOWN
BRANCH CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES A 2 #12 WIRE CIRCUIT
ADDITIONAL NO. OF #12:-1-11--, 3 #12;-- 1-!-f, 2 #12 &
1 #12 GND, 1I I I1( , 5 #12 & 1 #12 GND, ETC. OTHER WIRE
SIZES: 2 #10 & 1 #12 GND;-f# -•F, 3 #4 & 1 #8 GND, ETC.
#10 #12 #4 #8
MT
EL
NL
(E)
(N)
(R)
C.
WP
FACP
0
PFB
EMPTY CONDUIT WITH PULLSTRING
EMERGENCY LIGHT
NIGHT LIGHT
EXISTING
NEW
RELOCATE
CONDUIT
WEATHERPROOF
FIRE ALARM CONTROL PANEL
SMOKE DETECTOR, MOUNTING AS NOTED
FIRE ALARM MANUAL PULLSTATION
DUCT SMOKE DETECTOR
FIRE ALARM STROBE UNIT, WALL MOUNTED
FIRE ALARM COMBINATION HORN /STROBE UNIT, WALL MOUNTED
REVIEWED FOR
CODE COMPLIANCE
NFPA 70 - NEC
APR - 7 2088
�tY -0f Tukwii�
B ILDIN DIVISION
PROVIDE FOR FUTURE BREAKER
FLAG NOTE SHOWN ON SAME SHEET
SECTION DESIGNATION: TOP LETTER INDICATES SECTION,
BOTTOM LETTER/NUMBER INDICATES SHEET
DETAIL DESIGNATION: TOP NUMBER INDICATES DETAIL,
BOTTOM LETTER/NUMBER INDICATES SHEET
MECHANICAL & PLUMBING EQUIPMENT DESIGNATION
NOTE: SYMBOLS INDICATED ABOVE MAY NOT NECESSARILY
APPEAR AS PART OF THESE DRAWINGS IF NOT REQUIRED.
Public Works, Buil
PERMIT NU 4,1
%1g Division
BER
08-
CORRECT
LTR#
?ifie
RECEIVED
CITY OF TUKWILA
MAR 2 4 2008
PERMIT CENTER
DATE: 1 -28-08
JOB NO:
DRAWN:
CHECKED:
07142
JP
JL
EINEMESIONIMMIENIM
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635 -5696
FAX: (817) 635 -5699
IMMINIMMEMINEMINIME
W
D
z
0
0
ELD SOUTHCENTER
W
SOUTHCENTER MALL
t)
06
o3
V ,
EXPIRES 06 -23-08
REVISIONS
ISSUED FOR PERMIT /CONSTRUCTION
28 JAN. 08
PLAN CHECK COMMENTS
12, MARCH. 08
ONE LINE DIAGRAM
LEGEND, NOTES
AND DETAILS
JC-3 MENEMENEMMMEEME
SHEET NUMBER
OPIiT
ELECTRICAL ENGINEERING. INC
1786 Augusta Ln Ste B. Yuba City, CA 95993
Pic 530.790.0620 Fax 530.671.9792
E -3
FILE coPr
NEW ❑ EXISTING
P A N E L "LV" LVI I
AIC: 10,000
VOLTAGE: 120/208V -30-4W
MAIN: 150A MAIN CKT BRKR
BUS: 200 AMP
MOUNTING: SURFACE
LOCATION: STOCKROOM
8g z
KVA LOAD
LOAD DESCRIPTION
CKT BRKR
BUS
CKT BRKR
LOAD DESCRIPTION
L KVA LOAD
p..
x 6
0 z
PH A
PH B
PH C
TRIP
POLES
A B C
TRIP
POLES
PH A
PH 0
PH C
1
1.4
GEN. SALES DOWNLIGHTS
20
1
20
1
SHOW WINDOW RECS
0.4
2
„
„
3
1.3
GEN. SALES DOWNLIGHTS
20
1
20
1
SECURITY TRANSFORMER
02
4
5
1.3
SALES DISPLAY LIGHTS
20
1
20
1
SALES CONV RECEPTACLES
0.5
6
;,
7
1.4
SALES DISPLAY LIGHTS
20
1
20
1
SALES CONV RECEPTACLES
0.5
8
9
0.9
DISPLAY CASE LIGHTING
20
1
20
1
CASHWRAP CONV RECEPTS
0.4
10
is;
11
1.1
COVE LIGHTING
20
1
20
1
CASH REGISTERS
1.8
12
„
13
0.7
SHOW WINDOW LIGHTING
20
1
20
1
RESTROOM GFCI RECEPT
0.2
14
;;
15
1.2
SIGNAGE
20
1
20
1
BACK OFFICE RECEPTACLES
0.4
16
17
1.0
EMERGBACK AREA LIGHTS
20
1
20
1
BACK OFFICE RECEPTACLES
0.2
18
19
SPARE
20
1
20
1
MICROWAVE
1.5
20
in
21
20
1
20
1
FRIDGE
0/
22
;,
23
J ,
20
1
20
1
AN RACK
0.5
24
„
25
SPACE
PFB
20
1
"TTB" RECEPTACLES
0.4
26
&&I; ,
27
20
1
"TTB" RECEPTACLE
0.2
28
29
20
1
SECURITY PANEL
0.4
30
ii
31
20
1
LIGHTING CONTROL "LCC"
0.1
32
33
35
1
VAV CONTROL
0.2
34
1
35
20
1
VAV CONTROL
02
36
„
37
20
INST WATER HEATER
1.5
38
i1
39
2
\1,
1.5
40
11
41
u
�
PFB
SPARE
42
NOTES
- LINE TOTALS
25% CONT. LOAD
TOTAL KVA/PH.
UNE AMPS
TOTAL KVA LOAD
8.1
7.0
7.0
sw = SHOW WINDOW, PROGRAM CIRCUIT IN "LCC" PER MALL REQUIREMENTS.
TC = TIME -CLOCK CONTROL PROGRAM CIRCUIT FOR AFTER HOURS SHUT -OFF PER ENERGY CODE REQUIREMENTS
NL = NIGHT LIGHT, PROVIDE ADDITIONAL UN- SWITCHED, NON -LCC CONTROLLED CIRCUIT.
LO = LOCK -ON, PROVIDE LOCK ON DEVICE AND UN- SWITCHED, NON --LCC CONTROLLED CIRCUIT.
0.9
0.9
0.9
9.0
7.9
7.9
75
66
66
24 8 / 68.8A
SW
LO
LO
LO
LO
LO
SYMBOL LEGEND
•
•
2
3
M
acc
V
0
La
LEI
LD
0
EMI
FLUORESCENT LIGHT FIXTURE - SURFACE MOUNTED
INCANDESCENT LIGHT FIXTURE - PENDANT MOUNTED
FLUORESCENT STRIP LIGHT - SURFACE MOUNTED UNO
INCANDESCENT / FLUORESCENT / HID LIGHT FIXTURE - RECESSED
INCANDESCENT LIGHT FIXTURE - SURFACE MOUNTED
INCANDESCENT LIGHT FIXTURE - WALL MOUNTED
EXIT LIGHT - CEILING MOUNTED WITH EMERGENCY LIGHTS
EXIT LIGHT - WALL MOUNTED WITH ARROWS AS SHOWN
EMERGENCY LIGHTING FIXTURE - SURFACE MOUNTED
SINGLE POLE TOGGLE SWITCH, @ +46" UNO
TWO POLE TOGGLE SWITCH, @ +46" UNO
THREE -WAY TOGGLE SWITCH, @ +46" UNO
MOTOR RATED SINGLE POLE SWITCH, @ UNIT UNO
MASTER LIGHTING CONTROL STATION
OCCUPANCY SENSOR @ +46" UNO (LEVITON # 00515)
FIXTURE TAG: LETTER INDICATES TYPE
JUNCTION BOX, SIZE & TYPE AS INDICATED OR AS REQUIRED
15 OR 20 AMP 125V 3W DUPLEX RECEPTACLE, @ +16" UNO
15 OR 20 AMP 125V 3W DOUBLE DUPLEX RECEPTACLE, @ +16" UNO
CEILING MOUNTED DUPLEX RECEPTACLE
NON -FUSED DISCONNECT SWITCH
CIRCUIT BREAKER DISCONNECT SWITCH
FUSED DISCONNECT SWITCH, SIZE PER UNIT LABEL
MOTOR, N.I.E.S. CONNECT AS REQUIRED, NUMBER INDICATES HP
CONTROL EQUIPMENT, N.I.E.S. CONNECT AS REQUIRED
PANELBOARD - SEE SCHEDULE
MAIN SWITCHBOARD OR MOTOR CONTROL CENTER, SEE ONE LINE DIAGRAM
DISTRIBUTION TRANSFORMER, MOUNTING AS NOTED
TERMINAL CABINET, SIZE & TYPE AS NOTED
CEILING EXHAUST FAN
DATA OUTLET, 4" SQ. BOX w/ SINGLE DEVICE RING & PLATE @ +16" UNO
TELEPHONE OUTLET, 4" SQ. BOX w/ SINGLE DEVICE RING & PLATE @ +16" UNO
DUPLEX RECEPTACLE FLUSH w/ FINISHED FLOOR
CEILING MOUNTED DATA OUTLET
TELEPHONE TERMINAL BOARD: 4' x 8' x r PLYWOOD OR AS NOTED
w/ DOUBLE DUPLEX RECEPTACLE & 1 #6 GND
-LV-- LOW VOLTAGE WIRING IN CONDUIT
[" CONDUIT RUN CONCEALED BELOW FLOOR OR FINISHED GRADE, U.N.O.
r CONDUIT CONCEALED IN CEILING OR WALL, U.N.O.
HOMERUN TO RESPECTIVE PANEL OR TERMINAL CABINET - OVERHEAD
HOMERUN TO RESPECTIVE PANEL OR TERMINAL CABINET - UNDERGROUND
CONDUIT RISER - UP
CONDUIT RISER - DOWN
BRANCH CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES A 2 #12 WIRE CIRCUIT
ADDITIONAL NO. OF #12:-1-11--, 3 #12;-- 1-!-f, 2 #12 &
1 #12 GND, 1I I I1( , 5 #12 & 1 #12 GND, ETC. OTHER WIRE
SIZES: 2 #10 & 1 #12 GND;-f# -•F, 3 #4 & 1 #8 GND, ETC.
#10 #12 #4 #8
MT
EL
NL
(E)
(N)
(R)
C.
WP
FACP
0
PFB
EMPTY CONDUIT WITH PULLSTRING
EMERGENCY LIGHT
NIGHT LIGHT
EXISTING
NEW
RELOCATE
CONDUIT
WEATHERPROOF
FIRE ALARM CONTROL PANEL
SMOKE DETECTOR, MOUNTING AS NOTED
FIRE ALARM MANUAL PULLSTATION
DUCT SMOKE DETECTOR
FIRE ALARM STROBE UNIT, WALL MOUNTED
FIRE ALARM COMBINATION HORN /STROBE UNIT, WALL MOUNTED
REVIEWED FOR
CODE COMPLIANCE
NFPA 70 - NEC
APR - 7 2088
�tY -0f Tukwii�
B ILDIN DIVISION
PROVIDE FOR FUTURE BREAKER
FLAG NOTE SHOWN ON SAME SHEET
SECTION DESIGNATION: TOP LETTER INDICATES SECTION,
BOTTOM LETTER/NUMBER INDICATES SHEET
DETAIL DESIGNATION: TOP NUMBER INDICATES DETAIL,
BOTTOM LETTER/NUMBER INDICATES SHEET
MECHANICAL & PLUMBING EQUIPMENT DESIGNATION
NOTE: SYMBOLS INDICATED ABOVE MAY NOT NECESSARILY
APPEAR AS PART OF THESE DRAWINGS IF NOT REQUIRED.
Public Works, Buil
PERMIT NU 4,1
%1g Division
BER
08-
CORRECT
LTR#
?ifie
RECEIVED
CITY OF TUKWILA
MAR 2 4 2008
PERMIT CENTER
DATE: 1 -28-08
JOB NO:
DRAWN:
CHECKED:
07142
JP
JL
EINEMESIONIMMIENIM
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635 -5696
FAX: (817) 635 -5699
IMMINIMMEMINEMINIME
W
D
z
0
0
ELD SOUTHCENTER
W
SOUTHCENTER MALL
t)
06
o3
V ,
EXPIRES 06 -23-08
REVISIONS
ISSUED FOR PERMIT /CONSTRUCTION
28 JAN. 08
PLAN CHECK COMMENTS
12, MARCH. 08
ONE LINE DIAGRAM
LEGEND, NOTES
AND DETAILS
JC-3 MENEMENEMMMEEME
SHEET NUMBER
OPIiT
ELECTRICAL ENGINEERING. INC
1786 Augusta Ln Ste B. Yuba City, CA 95993
Pic 530.790.0620 Fax 530.671.9792
E -3
FILE coPr
44"
El
V
El
li9
v
IN
•
El
0
0
PROVIDE QUADPLEX CONVENIENCE
RECEPTACLE. TYPICAL OF (3).
PROVIDE SINGLE -GANG J -BOX
CONTAINING (2) DATA JACKS AND (1)
PHONE JACK.
1
0
TYPICAL MANAGER'S DESK ELEVATION
SCALE: NONE
FLOOR
1
PROVIDE SINGLE -GANG J -BOX
CONTAINING (2) DATA JACKS.
FLEXIBLE CONDUIT AND CONDUCTORS BY E.C..
PROVIDE PULLSTRING IN ALL EMPTY CONDUITS.
TYPICAL. • �_
>-C
0
ao
>C
up
•
•
11
PROVIDE ISOLATED GROUND
RECEPTACLE. TYPICAL OF (2)
PROVIDE QUADPLEX CONVENIENCE
RECEPTACLE. TYPICAL OF (2).
PROVIDE SINGLE -GANG J -BOX
CONTAINING (2) DATA JACKS AND (1)
PHONE JACK.
PROVIDE AND CONNECT J -BOXES TO
CONDUIT STUB -OUTS. PLACE J -BOXES IN
TOE -KICK CABINET SPACE WHERE
POSSIBLE. PROVIDE PULLSTRING IN ALL
EMPTY PHONE/DATA CONDUITS.
1
—D-
TYPICAL CASHWRAP ELEVATION
E4
SCALE: NONE
FLOOR
0
0 0
[1
0 0
n
0
a
o 0
0 0
0
O
O 0
gg
s
0 0
0
a
o 0
1
o 0
0
TYPICAL REAR COUNTER ELEVATION
E4
SCALE: NONE
REVIEWED FOR
CODE COMPLIANCE
NFPA 70 - NEC
APR - 7 2008
Oty Of Tukwila
B ILDING DM ION
FC,041-ice
RECEIVED
CITY OF TUKWILA
FEB 1 9 2008
'EHMI f CENTER
DATE: 1-28-08
JOB NO: 07142
DRAWN: JP
CHECKED: JL
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635 -5696
FAX: (817) 635 -5699
L J
N
SOUTHCENTER
WESTFIELD
SOUTHCENTER \BALL
V)
TUKWILA, WA
EXPIRES 06 -23-08
REVISIONS
ISSUED FOR PERMIT /CONSTRUCTION
28 JAN. 08
ELECTRICAL
DETAILS
SHEET NUMBER
IHT E - 4
ELECTRICAL ENGINEERING. INC
1786 Augusta Ln Ste B, Yuba City, CA 95993
Ph: 530.790.0620 Far 530.671.9792
lal
•
t
gg
s
T
16"
,,
1
TYPICAL REAR COUNTER ELEVATION
E4
SCALE: NONE
REVIEWED FOR
CODE COMPLIANCE
NFPA 70 - NEC
APR - 7 2008
Oty Of Tukwila
B ILDING DM ION
FC,041-ice
RECEIVED
CITY OF TUKWILA
FEB 1 9 2008
'EHMI f CENTER
DATE: 1-28-08
JOB NO: 07142
DRAWN: JP
CHECKED: JL
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635 -5696
FAX: (817) 635 -5699
L J
N
SOUTHCENTER
WESTFIELD
SOUTHCENTER \BALL
V)
TUKWILA, WA
EXPIRES 06 -23-08
REVISIONS
ISSUED FOR PERMIT /CONSTRUCTION
28 JAN. 08
ELECTRICAL
DETAILS
SHEET NUMBER
IHT E - 4
ELECTRICAL ENGINEERING. INC
1786 Augusta Ln Ste B, Yuba City, CA 95993
Ph: 530.790.0620 Far 530.671.9792
ELECTRICAL SPECIFICATIONS
SECTION 16050: GENERAL ELECTRICAL
The General Conditions, Supplementary Conditions, and Division 1 apply to work under
this Section
PART 1 GENERAL:
1.01 DESCRIPTION
A. General: Furnish all labor, materials, apparatus, tools, equipment, transportation,
temporary construction and special or occasional services as required to make a
complete working electrical installation, as shown on the drawings or described in
these specifications.
B. Work included:
1. Installation and assembly of Owner furnished lighting fixtures and lamps.
2. Grounding.
3. Connections of smoke detectors furnished and installed by Mechanical.
4. Panels and overcurrent devices.
5. Branch circuit wiring.
6. Exit signs and emergency lighting system.
7. Installation of convenience outlets.
8. Installation of telephone and data outlets and raceways.
9. Furnishing, support and installation of new transformer.
10. Rough -in wiring for display case lighting.
11. Demolition and removals.
12. Lighting controls, and time switches.
13. Connections of, and power wiring to, HVAC equipment and food service
equipment.
14. Conduit for data, telephone and alarm systems.
C. Related Work Specified Elsewhere:
1.
Perform the following work, in accordance with appropriate sections of the
specifications cited, where and as necessary to furnish a complete, working electrical
installation.
a. Concrete:
b. Painting:
c. Door hardware:
d. Mechanical:
e. Food Service Equipment:
Division 3
Division 9
Division 11
Division 15
Division 15
D. Related Work Not included in Contract:
1. Installation of primary and secondary utility cables.
2. Installation of telephone instruments and equipment.
3. Installation of data cable or computer equipment.
1.02 CODES AND STANDARDS:
A. Specific
1. The following publications or latest enacted editions
throughout construction shall apply.
a. National Electrical Code.
b. State and Local Building and Energy Codes.
c. Uniform Building Code.
of the documents
2. Equipment and materials specified under this division shall conform to the
following standards where applicable.
a. UL Underwriters' Laboratories.
b. ASTM American Society for Testing Materials,
c. CBM Certified Ballast Manufacturers,
d. ANSI American National Standards. Institute.
e. NEMA National Electrical Manufacturers Association
1.03 DRAWINGS:
A. Layout: General layout shown on the drawings shall be followed except where
other work may conflict with the drawings.
B. Accuracy.
1. Drawings for the work under this Section are diagrammatic.
2. Contractor shall verify lines, levels and dimensions shown on the Drawings and shall
be responsible for the accuracy of the setting out of work and for its strict
conformance with existing conditions at the site.
1.04 SUBSTITUTIONS: Refer to the General Conditions, Supplementary Conditions and
Division 1 for substitution.
1.05 SUBMITTALS:
A. General: Refer to the General Conditions, Supplementary General Conditions and
Division 1 for requirements.
B. Format: Furnish submittal data neatly bound in an 8 -1/2" X 11" folder or binder with
a table of contents listing in order of specification section and paragraph number.
C. Submittals shall consist of detailed shop drawings, specifications, catalog "cuts"
and data sheets containing physical and dimensioned information, performance data,
electrical characteristics, materials used in fabrication, material finish and those
optional accessories which are included and those which are excluded.
D. Each submittal shall be thoroughly reviewed by the Contractor. The cover letter
accompanying submittal letter shall list in full the items and data submitted and shall
contain a statement acknowledging that the Contractor has performed a detailed
review of the submittal documents prior to submission. Failure to comply with this
requirement shall constitute grounds for return of data for resubmission without
review.
E. Contractor agrees that Shop Drawing submittals processed by the engineer are
not change orders, that the purpose of Shop Drawing submittals by the Contractor is
to demonstrate to the engineer that the Contractor understands the design concept,
that he demonstrates his understanding by indicating which equipment and material he
intends to furnish and install and by detailing the fabrication and installation methods
he intends to use.
1.06 PRODUCT DELIVERY, STORAGE AND HANDLING: Equipment and materials shall
be properly stored and adequately protected and carefully handled to prevent
damage before and during installation. Equipment and materials shall be handled,
stored, and protected in accordance with the manufacturers's recommendations and
as approved by the Owner's Representative. Electrical conduit shall be stored to
provide protection from the weather and accidental damage. Plastic conduit shall
be stored on even supports and in locations not subject to direct sun rays or
excessive heat. Cables shall be sealed, stored and handled carefully to avoid
damage to the outer covering or insulation and damage from moisture and weather.
Damaged or defective items, in the opinion of the Owner's Representative, shall be
replaced with new items at no cost to the Owner.
1.07 PERMITS AND FEES: Provide, procure and pay for all permits, licenses and fees
required to carry on and complete the work.
PART 2 PRODUCTS (Not Applicable)
PART 3 EXECUiiON:
3.01 TESTS:
A. Tests shall be conducted during the construction period and at completion to
determine conformity with applicable Codes and with these Specifications. Tests shall
be performed in the presence of the Architect and shall include, but are not limited
to the following:
1. Insulation Resistance: Perform 500 -volt D.C. tests for one minute on all feeder
conductors, including the neutral, and make a typed record of all readings to be
included in the maintenance instructions. Repair or replace circuits showing Tess than
40 megohms resistance to ground. Make tests using Biddle Insulation Resistance
Megger, or equal.
2. Ground Resistance: Test ground resistance per IEEE Standard No. 81.
3. Circuits Continuity. Test all feeder and branch for continuity. Test all neutrals for
improper grounds.
4. Equipment Operations: Test lighting circuits for correct operation through their
control devices. Test electric baseboard heaters for correct operations through
their control relays /thermostats.
5. Lighting Control Circuits: Perform operation tests for all lighting circuits.
6. Product Failure: Any products which fail during the tests or are ruled
unsatisfactory by the Owner's Representative shall be replaced, repaired, or
corrected as prescribed by the Owner's Representative at the expense of the
Contractor. Tests shall be performed after repairs, replacements or corrections until
satisfactory performance is demonstrated.
7. Physical Inspection of Electrical Equipment and Cables: Inspection shall be made
of all equipment to insure proper assembly and construction.
3.02 INSTRUCTIONS AND MANUALS
A. Refer to Division 1.
B. At the time of completion, an adequate period shall be allotted by the
contractor for instruction of building operating and maintenance personnel in the use
of all systems. All personnel shall be instructed at one time, the Contractor making all
necessary arrangements with manufacturers's representatives. The equipment
manufacturer shall provide product literature and application guides for the Users'
reference.
C. Costs, if any, for the above service shall be paid by the Contractor.
3.03 PROJECT RECORD DOCUMENTS (AS- BUILT)
A. Provide Project Record Drawings and Specifications as required by other
Sections of Specifications and as required herein. Such drawings shall fully represent
installed conditions including actual location of outlets, correct conduit and wire
sizing as well as routing, revised fixture scheduling listing the manufacturer and
products actually installed.
B. All changes to drawings shall be made by qualified draftspersons to match
existing line work and lettering as closely as possible.
3.04 WORKMANSHIP
A. Preparation, handling and installation shall be in accordance with manufacturer's
written instructions and technical data particular to the product specified and /or
approved except as otherwise specified. Coordinate work and cooperate with other
in furnishing and placing this work. Work to approved shopdrawings for work by
others and to field measurements as necessary to properly fit the work.
B. Conform to the National Electrical Contractor's Association Standard of
Installation for general installation practice.
3.05 SCHEDULE OF WORK: Arrange work to conform to the schedule which has been
established for the progress of the work. Advise regarding shipping schedule of
major equipment.
3.06 SUPERVISION: Contractor shall personally or through an authorized and
competent representative constantly supervise the work form beginning to completion
and, within reason, keep the same workmen and foreman on the project throughout the
project duration.
3.07 PROTECTION: Keep conduits, junction boxes, outlet boxes, and other openings
closed to prevent entry of foreign matter. Cover fixtures, equipment and apparatus
and protect against dirt, paint, water, chemical or mechanical damage, before and
during construction period. Restore to original condition any fixture, apparatus, or
equipment damaged prior to final acceptance. Protect bright finished surfaces and
similar items until in service. No rust or damage will be permitted.
3.08 SPECIAL TOOLS: All special tools for proper operation and maintenance of
the equipment provided under this section shall be delivered to the Owner's
representative.
3.09 CUTTING AND PATCHING
A. Install all required sleeves, forms and insets before walls or partition are built.
Cutting and patching of walls, partitions, ceilings and floor necessary for reception
of work, cause by failure to provide or properly located sleeves, forms and insets,
incorrect location of work or failure to cooperate with other trades, shall be done at
expense of trade responsible.
B. No cutting of finished or structural work may be done without acceptance. When
necessary to have finished material or stuctural work cut, finsh necessary drawings
to trade whose materials are out to be cut.
3.10 CLEARANCES: Provide working clearance in front of, in back of, and to sides
for all electrical equipment as required by National Electrical Code Article 110.
3.11 DEMOLITION: Demolition and removal of existing electrical services to the
existing tenant space to be demolished by the Contractor.
END OF SECTION
SECTION 16100: BASIC MATERIALS AND METHODS
The General Conditions, Supplementary Conditions, and Division 1 apply to work under
this Section.
PART 1 GENERAL
1.01 DESCRIPTION
A. Work specified in this section encompasses products, assemblies and basic
installation methods required for electrical project systems specified under this
Division and includes, but is not limited to:
1. Conduit, raceways, and fittings.
2. Wire and cables.
3. Wire connections and devices.
4. Outlet boxes.
5. Pull and junction boxes.
6. Switches and receptacles.
7. Device plates.
8. Overcurrent protective devices.
9. Telephone terminal backboard.
10. Door buzzer and pushbutton system.
11. Background sound system equipment installation and wiring.
12. Empty raceway provisions for burglar alarm and security system
and switches.
B. Work Not Included:
1. Background sound system equipment furnished by FDI.
2. Burglar alarm and security system equipment and wiring.
1.01 SUBMITTALS
A. Submit in conformance with the requirements
1. Switches, receptacles and device plates.
2. Conductors and cables.
3. Overcurrent protective devices.
4. Raceways.
5. Door buzzers and pushbutton.
detection units
of Section 16050 the following
items:
PART 2 PRODUCTS
2.01 CONDUIT AND FITTING
A. Rigid Steel Conduit
1. Conduit, rigid steel: full weight, threaded, hot -dip galvanized, inside enameled,
conforming to ANSI C80.1.
2. Three -piece couplings: electroplated, cast malleable iron. Efcor 165 series,
0.Z. /Gedney 4 -50 series or equal.
3. Threadless couplings: electroplated, cast malleable iron, with integral conduit stop.
Efcor 1760.
B.
C.
4. Threadless connectors: electroplated, cast malleable iron, on threaded male hub
plastic insulated throat rated 90 degrees C minimum. Efcor 17506 series, 0.Z. /Gedney
31 -050 1T series or equal.
5. Insulated bushings: threaded polypropylene or thermosetting phenolic rated 150
degrees C minimum.
6. Insulated grounding bushings: threaded cast malleable iron body with insulated
throat and steel, lay --in" ground lug with compression screw. 0.Z. /Gedney BLG series,
Thomas & Betts 3870 series or equal.
7. Insulated metallic bushings: threaded cast malleable iron body with plastic
insulated throat rated 105 degrees C. 0.Z. /Gedney Type B, Thomas & Betts 1222
series or equal.
Electrical Metallic Tubing (EMT)
1. Conduit: Shall be formed of cold rolled strip steel, electrical resistance welded
continuously along the longitudinal seam and hot -dip galvanized after fabrication.
Conduit shall conform to ANSI C80.3 specifications and shall meet U.L. requirements.
2. Couplings: Electroplated, cast malleable iron, gland compression type, U.L. listed
rain and concrete tight through 1 -1/4 inch trade size, 0.Z. /Gedney 6050W series, Efcor
760 series or equal. Set screw type couplings may be used in dry locations,
0.Z. /Gedney 5050 series or equal.
3. Connectors: Gland compression type with cast malleable iron body with male hub
and insulated plastic throat 150 degrees C. temperature rated. 0.Z. /Gedney 4050
series or equal.
Flexible Metallic Conduit
1.
Conduit: Shall be fabricated in continuous lengths from galvanized steel strip,
spirally wound and formed to provide an interlocking design. 6' MAX. LENGTH
Flexible conduit is not permitted in walls.
2. Fittings: Connectors shall be made of the screw clamp with cast malleable iron
bodies and threaded male hubs with insulated throats.
D. Liquid Tight Flexible Metallic Conduit
1. Conduit: Anaconda
2. Fittings: Connector
iron, with insulated
or equal.
Type U.A., Coleman Type Uxt1 or equal.
body and gland nut shall be of cadmium plated cast malleable
throat, MAX. 24 ", T & B 5331 series, 0.Z. /Gedney 4Q-38-1T series,
E. Minimum acceptable conduit size shall be 3/4 inch.
2.02 WIRE AND CABLE
A. General
1. Acceptable manufacturers:
PWC Inc., or equal.
General Electric Co., Rome Cable, Southwire, Triangle,
2. Conductor material: All wire and cable shall be insulated copper conductors for all
wire sizes. Aluminum wire and cable shall not be used.
3. Insulation: Insulation shall be THWN -THHN for wire sizes through size 1/0 AWG. For
larger wire sizes insulation shall be THWN, XHHW, THW or as required to suit
application.
4. Fixture wire: Type AF.
5. Minimum conductor size:
Power and lighting branch circuits:
Signal and control circuits under 100 volts:
Any 120V./ 20A. circuits over 75 LF. must be:
2.03 OUTLET BOXES AND COVERS
#12 AWG
#14 AWG.
#10 AWG.
A. Standard Outlet Boxes: Galvanized, one - piece, drawn steel, knock -out type of
size and configuration best suited to the application indicated on the plans. Minimum
box size, 4 inch square by 1 -1/2 inch deep.
B. Switch Boxes: Two inch by 3 -inch long, galvanized steel switch boxes shall be
used only for the installation of single switches, Install multiple switches in standard
gang boxes with raised device covers suitable for the application indicated.
2.04 SWITCHES AND RECEPTACLES
A. General: Color of devices shall be white at painted walls, ivory when installed in fixtures,
and orange for dedicated I.G. receptacles unless otherwise noted on Drawings.
1. All general purpose 15 and 20 ampere, 125 -250 volt receptacles and 120 -277 volt
switches shall conform to NEMA WD 1 and applicable U.L. tests.
B. Receptacles:
1. Ground fault circuit interrupter receptacle: NEMA type 5 -15R LEVITON #6598 -1 or
equal.
2. Duplex receptacles: NEMA type 5 -15R, and 5-20R, heavy duty specification grade,
side wired only, LEVITON #5242 -W AND 5243 -W or equal.
3. Cash register receptacles: NEMA type 5 -20R, heavy duty specification grade,
side wired only, Hubbell #IG -5262, provided with green insulated ground wire, and
with engraved cover plate "For Cash Registers Only ".
C. Switches: Twenty ampere, 120 -277 volts, fast make -slow break, quiet type switch with
silver cadmium alloy contacts, binding head terminal screws, side wired only. All
switches shall be white in color.
1. Single pole, single throw, LEVITON #1221 -W or equal.
2. Three -way, LEVITON #1223 -W or equal.
2.05 DEVICE PLATES
A. Flush Device Plates: Plates shall be smooth plastic, color, LEVITON #8600
series or equal.
B. Surface Mounted Devices, indoor: Galvanized metal to fit box.
C. Outdoor, Weatherproof: Die cast aluminum construction, corrosion resistant,
heavy duty, hinged cover flap, and gasket, LEVITON #6196, horizontal mounting.
2.06 DISCONNECT SWITCHES
A. Switch Interior. Dead-front construction with hinged arc suppressor and switch
blades which are fully visible in the "OFF " position and with door open.
B. Switch Mechanism: Quick -make and quick -break operating handle and mechanism
with dual cover interlock to prevent unauthorized opening of the switch door in
the "ON" position or closing the switch mechanism while the door is open.
C. Ratings: Switches shall be horsepower rated for the operating voltage and with
fused or non -fused arrangements as shown on the drawings.
D. Enclosures: NEMA 1, code gauge sheet steel with hinged cover, or NEMA 3R as
shown on Drawings, and as required by application.
REVIEWED FOR
CODE COMPLIANCE
NFPA 70 - NEC
APR - 7 2008
City of Tukwila
B . ILDING DIVI ION
RECIVED
cyry OFETUKWIL A
FEB 19 Z008
�E�{lvl►1 CENTER
DATE: 1 -28 -08
JOB NO: 07142
DRAWN: JP
CHECKED: JL
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635 -5696
FAX: (817) 635 -5699
SOUTHCENTER
WESTFIELD
SOUTHCENTER MALL
V)
t0
TUKWILA, WA
EXPIRES 06 -23-08
EIMMIESEMEMEI
REVISIONS
ISSUED FOR PERMIT /CONSTRUCTION
28 JAN. 08
ELECTRICAL
SPECIFICATIONS
SHEET NUMBER
OPI�T E - 5
ELECTRICAL ENGINEERING. INC
1786 Augusta Ln Ste B, Yuba City, CA 95993
Pk 530.790.0620 Fax 530.6719792
ELECTRICAL SPECIFICATIONS
(con't)
2.07 TRANSFORMERS
A. Transformers shall be indoor type, self cooled, 480V, three - phase, dual winding,
fully enclosed, ventilated, general purpose dry type, 480 volt primary, 120/208 volt
secondary, 60 hertz, equipped with two 2 1/2% full capacity taps above and below
rated voltage and shall be of the KVA rating shown on the drawings.
B. Transformers shall have copper or aluminum windings Class 'H' insulation group, with
temperature rise, when operated continuously at full load and rated frequency, not
exceeding 150 degree C. rise over 40 degree C. ambient, unless mentioned otherwise
on the one line diagram.
C. Transformer shall have a minimum of 10% overload capacity at rated voltage and
shall have a 10 KV BIL rating.
D. Sound level at any load shall not exceed 45 dB when tested in a room with ambient
sound level not exceeding 24 dB. Ecessively noisy transformers shall be replaced.
E. Transformer impedance shall not be less than 4% nor greater than 5 %. Transformers
shall conform to NEMA TRI-1974, NEC 450 -21 and all applicable state and local
codes.
F. Transformer shall not contain any PCB's (Polychlorinated Biphenyls).
G. Transformer size shall fit space allocated per Drawings.
2.08 PANELBOARDS
A. Ratings: See panel schedules.
B. Finish: All painted steel work shall be treated with a primer coat and finish coat of
the manufacturer's standard gray color or ANSI 61.
C. Bussing
1. Bussing shall be rectangular cross section full length tin plated
2. Each panelboard shall be equipped with a ground bus secured to the interior of
the enclosure. The bus shall be equal to the panelboard neutral bus and shall
have a seperate lug for each ground conductor. Not more than one conductor
shall be installed per lug.
2.09 PROTECTIVE DEVICES
A. Circuit Breakers: Molded case, bolt -on, thermal magnetic type, 40 degrees C.
ambient temperature compensated, fixed mounting, with quick -make and quick -break
switching mechanism mechanically trip -free from the operating handle.
B. Ratings: Refer to drawings and panel schedules for trip frame and poles
required. Minimum short circuit rating for 120/240 volt breakers is 10,000 A,
277/480 volt breakers is 22,000 A, if not indicated otherwise.
C. Manual motor starters: Fractional H.P. 1 phase motors shall be protected by
thermal 01. relay integral with the disconnect: "Motor- Minder ", or equal.
2.10 ELECTRICAL SUPPORTING DEVICES
A. Conduit Straps: Hot -dip galvanized, cast malleable iron, one hole type strap
with cast clamp-backs and spacers as required. O.Z. /Gedney #14 -500 strap and
#1410 spacer, Refcor #231 strap and #131 spacer, or equal.
B. Construction Channel: 1-1/2 inch by 1-1/2 inch 12 gauge galvanized steel channel
with 17/32 inch diameter bolt holes, 1-1/2 inches on center, in base of the channel.
Kindorf 905 series, Unistrut P- 1000 -HS, or equal.
C. Fasteners (General): Wood screws for fastening to wood. Machine screws for
fastening to steel. Toggle bolts for fastening to hollow concrete block, gypsum
board or plaster wall. Expansion anchors for attachments to pre - poured concrete.
2.11 IDENTIFYING DEVICES
A. Panelboard Directories: Shall be typewritten, arranged in numerical order and
shall show the number of the circuit is indicated. The room numbers used shall be
verified with the Owner and shall not necessarily be those used in the drawings.
Mount directories in a 6" x 8" metal frame under plexiglass inside each
panelboard.
B. Wire & Terminal Markers: Self -- adhering, pre-printed vinyl with self - laminating wrap
ground strip Brady B191 series, Thomas & Betts WSI series, or equal.
2.12 PLYWOOD BACKBOARDS
A. Where indicated for telephone or communication system terminals, or for motor
control or other equipment assembles, provide backboards of size indicated.
1. Use Douglas Fir plywood, exterior grade with "B" face, prime and finished
painted.
2. Unless otherwise indicated, provide 3/4 inch thick plywood.
3. All plywood shall be fire resistant.
2.13 GROUNDING
A. Enclosures of equipment, raceways, and fixtures shall be permanently and
effectively grounded. Provide code- sized, (unless otherwise indicated) copper,
insulated green equipment ground with all branch and feeder circuit runs. Equipment
ground shall originate at panelboard ground bus and shall be bonded to all
switch and receptacle boxes and electrical equipment enclosures.
B. Building services shall be grounded to building steel and to cold metallic water piping.
C. Isolated ground conductors shall terminate on isolated ground bus
and receptacle isolated ground lugs only.
2.14 DOOR BUZZER AND PUSHBUTTON SYSTEM
A. Provide a complete and operating door buzzer system with all necessary
accessories, transformer and wiring.
B. Buzzers, three required, shall be Edwards #1064 -05, mounted 8' AFF in stock and
mezzanine areas, and 2' AFF under cash wrap counter.
C. Pushbutton shall be Edwards #1786 -B, mount at 4' AFF.
D. Transformer rated 20 VA, 24VAC shall be Edwards #592, mount at 8' AFF, and
connect to local general purpose receptacle circuit.
PART 3 EXECUTION
3.01 CONDUIT AND RACEWAY APPLICATIONS
A. Rigid Steel Conduit: For all exposed and U/G conduit exposed to mechanical damage.
Minimum size is 3/4 ".
B. Electrical Metallic Tubing (EMT): Interior power and lighting branch circuits
where run concealed above suspended ceiling, in stud walls, furred spaces, and
where not exposed to mechanical damage, or above 6' from floor.
C. Flexible Metallic Conduit: In dry locations connection to transformers,
(6' MAX.), vibrating equipment (24" MAX.), and to recessed lighting fixtures.
D. Liquid -Tight flexible Metallic Conduit: In damp and wet locations for
connection to all pump motors, solenoid valves, HVAC equipment and similar
devices shall be made using liquidtight flexible metallic conduit. Provide
separate ground wire independent of conduit, run inside conduit and bonded at
both ends to enclosures. Maximum length of 24 inches.
3.02 CONDUIT INSTALLATION
A. General
1. Conduit system shall be concealed unless exposed work is clearly called for on
drawings.
2. Conduits shall be tightly covered and well protected during construction using
metallic bushings and bushing pennies to seal open ends.
3.
In all empty conduits or ducts, install a 200 -pound tensile strength polyethylene
pulling rope.
4. Conduit systems shall be electrically continuous throughout. Install code size,
insulated, copper, green grounding conductor in all conduit runs pulled with phase
and netural conductors.
B. Layout
1. Locations of conduit runs shall be planned in advance of the installation and
coordinated with the ductwork, plumbing, ceiling and wall construction in the same
areas and shall not unnecessarily cross other conduits or pipe, nor prevent
removal of ceiling or tiles or panels, nor block access to mechanical or electrical
equipment.
2. Where practical, install conduits in groups, in parallel, for vertical and horizontal runs
and at elevations that avoid unnecessary offsets.
3. Exposed conduit shall be run parallel or at right angles to the centerlines of
columns and beams.
4. Conduits shall not be placed closer than 12 inches from a parallel hot water or
steam line or 3 inches from such lines crossing perpendicular to the runs.
C. Supports
1.
All raceway systems shall be secured to the building structures using specified
fasteners, clamps and hangers spaced according to code requirements.
2. Support single runs of conduit using one hole pipe straps. Where run horizontally
on walls in damp or wet location, install "clamp- backs' to space conduit off the
surface.
3. Multiple conduit runs shall be supported using "trapeze" hangers fabricated
from specified construction channel, mounted to 3/8 inch diameter, threaded steel
rods secured to building structures., Fasten conduit to construction channel with
standard one hole pipe clamps or the equivalent.
D. Termination and Joints
1.
Raceways shall be joined using specified coupling or transition couplings where
dissimilar raceway systems are joined.
2. Conduits shall be securely fastened to cabinets, boxes and gutters using two
locknuts and an insulating bushing or specified insulated connectors. Install
grounding bushings or bonding jumpers on all conduits terminating at concentric
knockouts.
3. Conduit terminations exposed at weatherproof enclosures and cast outlet boxes
shall be made watertight using specified connectors and hubs.
4. Install expansion couplings where any conduit crosses a building separation or
expansion joint.
E. Penetrations
1.
All floor penetrations shall be sealed water - tight. Maintain fire rating as
required.
2. Fire -safe all rated wall penetrations using 3M listed fire - safing sealants and
assemblies.
3.03 CABLE AND WIRE INSTALLATION
A. General
1.
Conductors shall not be installed in conduit until all work of any nature that may
cause damage is completed. Care shall be taken in pulling conductors that insulation
is not damaged. U.L. approved non - petroleum base and insulating type pulling
compound shall be used as needed.
2. All cables shall be installed and tested in accordance with manufacturer's
requirements and warranty.
B. Splicing and Terminating
1.
All aspects of splicing and terminating shall be in accordance with cable
manufacturer's published procedures.
2. Make up all splices in outlet boxes with connectors as specified herein with
separate tails of correct color to be made up to splice. Provide at least six (6)
inches of tails packed in box after splice is made up.
3. All wire and cable in panels, terminal cabinets and equipment enclosures shall be
bundled and clamped.
C. Metallic sheathed type MC Cable: Installed for branch circuit wiring as allowed
by local building code and tenant manual. Cable shall not be run exposed
in finished spaces. Cable shall be supported in accordance with NEC article 334.
Use only U.L. listed fittings for terminations at boxes and cabinets.
3.04 INSTALLATION OF BOXES AND WIRING SERVICES
A.
General
1. All outlets shall finish FLUSH with building walls and ceiling, except where
exposed work is called for. There shall be no gap between box and wall or ceiling
material. Any opening between box and wall or ceiling shall be caulked airtight.
2. Install raised device covers on all outlet boxes as required to finish flush with
surface. Covers shall be of a depth to suit the wall or ceiling finish.
3. Leave no unused openings in any box. Install close -up plugs as required to seal
openings.
4. Exposed outlet boxes and boxes in damp and wet locations shall be cast metal
with gasketed cast metal cover plates.
B. Boxes Layout
1. Outlet boxes shall be installed at the locations and elevations shown on the
drawings or specified herein. Make adjustments to locations as required by
structural conditions and to suit coordination requirements of other trades.
2. Outlet boxes in stud wall and partitions shall not be mounted back -to -back nor
shall through -wall boxes be permitted.
C. Supports
1. Boxes installed in stud walls shall be equipped with brackets designed for
attaching directly to the studs or shall be mounted on heavy gauge galvanized
steel box supports.
2. Fixture outlet boxes installed in suspended ceilings of gypsum board or lath
and plaster construction shall be mounted to 16 gauge metal channel bars
attached to main ceiling runners.
3. Fixture outlet boxes installed in suspended ceilings systems supporting
acoustical tiles or panels shall be supported directly from the structures above
wherever pendant - mounted fixtures are installed from the box.
D. Mounting Heights: Mounting heights from finished floor to center line of device
box shall be as follows, and in accordance with handicapped accessibility
requirements of State Code.
Device: Height(inches)
Convenience receptacle 15
Convenience receptacles above
Counters unless otherwise noted 36
Switches, light 48
Telephone outlet, wall 15
3.05 TRANSFORMER INSTALLATION
A. Transformer shall be floor mounted as shown on the drawings. Furnish
and install all mounting hardware to safely carry the weight of the
transformer. Maintain adequate spacing for ventilation as recommended
by the manufacturer and required by code.
B. Provide Korfund type vibration isolation pads for each transformer.
C. Connections to transformer shall be made with flexible metallic conduit. Install
ground conductors in each conduit and provide grounding bushings as required.
D. Provide heat insulating barrier below transformer where installed on combustiable
surface.
END OF SECTION
SECTION 16510: LIGHTING FIXTURES
PART 1
1.01
A.
A.
GENERAL
DESCRIPTION
Work Included
1. Installation and connection of all fixtures, lamps, ballasts, lighting control devices,
relays, related components and accessory wiring as shown on the plans, Fixture
Schedule or as specified herein.
2. Owner to provide lighting fixtures and lamps. Contractor to install all
lighting fixtures and lamps.
3. Final aiming and adjustment of recessed adjustable fixtures and track mounted
fixtures shall be by the Electrical Contractor, as directed by the Owner's
Representative.
Related Work Specified Elsewhere: Refer to Section 16050 for requirements
applicable to this Section.
1.02 COORDINATION: Refer to Architectural Plans for exact location of lighting
fixtures.
1.03 SUBMITTALS: Submit in conformance with the requirements of Section 16050:
Time switches, control devices, relays and cabinets and wiring diagrams.
PART 2 PRODUCTS
2.01 LAMPS
A.
B.
Incandescent Lamps: General purpose A base lamps shall be inside frosted,
rated 120 VAC, or as noted on Fixture Schedule. Reflector style lamps, R and PAR,
as noted on Fixture Schedule. MR16 lamps shall be G.E. Precise constant color
type.
Fluorescent Lamps
1. 24, 36 and 48 inch long lamps shall be T-8 energy saving DELUXE warm -white
735 K in color.
2. Compact twin -tube and double twin -tube, 9, 13 and 18 watts nominal, 735 K
SPX35.
C. Lamps shall be as manufactured by G.E., Osram, Venture, Sylvania only.
2.02 BALLASTS
A. Fluorescent Lamp Ballasts
1. Ballasts for all single tube fluorescent lamps shall be U.L. approved, CBM
certified or ETL tested, Class P, Sound Rated A, "full- output energy- saving,
electronic ballasts for Octron lamps as manufactured by Magnetek.
2. Ballasts for compact fluorescent lamps shall have high power factor.
3. Ballasts shall be approved for use with energy saving lamps by the lamp
manufacturer.
2.03 REFRACTORS, REFLECTORS AND LOUVERS
A. All glassware, plaster and metal shall be uniform, free from defects, and
photometrically tested for distribution by an independent testing laboratory.
B.
C.
Plastic diffusers shall be of virgin acrylic plastic.
Polished reflectors used with triphosphor compact lamps shall have
anti-iridescent optical coating.
2.04 LIGHTING CONTROL SYSTEM
A. Lighting Control system shall consist of 20A mechanical latching type lighting
contactors, interconnecting wiring, a master switch station, time clocks and switches
all housed within a Nema 1 enclosure.
B. Lighting Contactor shall be housed in a code gage cabinet with time clocks
and have hinged screw cover. Provide one or more as required cabinets Hoffman,
or equal. Provide one or more Lighting Contactors as required m'Square -D" 8903
or equal.
C. Master switch station shall consist of 20A, 120/277VAC momentary contact single
pole double throw, center OFF, toggle switches, Hubbell #1557 -I and multiple
channel outputs, or equal. Quantity as indicated on Drawings. Provide engraved
multigang stainless steel cover plate for switches.
2.05 TIME SWITCHES
A. Time switches shall be programmable 7 -Day, 24 hour electronic type with backup battery
as manufactured by Tork, Rainbird, or Intermatic. Time switches shall be wired to
control lighting via Lighting contactors of lighting control system. Typical for HVAC system.
PART 3 EXECUTION
3.01 INSTALLATION
A. Contractor shall be responsible for handling, and fixtures shall be plumb, level,
in straight lines without distortion and clean.
B. Install each fixture in a manner recommended by the fixture manufacturer and
approved by the Owner's Representative. Under this Section of the work, furnish
and install all additional ceiling bracing, hanger supports and other structural
reinforcements to the building require to properly and safely suspend fixtures, all
as approved by the Owner's Representative.
C. Fixtures in areas of exposed duct and pipe work shall be suspended to avoid
conflict with same.
D. Pendant fixtures shall be provided with ball aligners and sway adapters. Fixture
chain shall not be used for supporting fixtures.
E. Ballasts: Ballasts judged by the Owner's Representative to be noisy, and
failed or malfunctioning ballasts shall be replaced at Owner's expense.
3.02 FIXTURE SUPPORT - SUSPENDED CEILINGS
A. Provide four wire supports for each suspended fixture, secured to the building structure
independent of the ceiling supporting system.
END OF SECTION
CODE CON1PLIPICE
APR _ 2 0
City Of 'Tukwila CS
ILDD1G DNI 10%
fl,OSH tec
RECEIVED
CITY OF TUKWILA
FEB 19 2008
PEF1MIT CENTER
DATE: 1-28-08
JOB NO: 07142
DRAWN: JP
CHECKED: JL
711 N. FIELDER RD.
ARLINGTON, TX 76012
PH: (817) 635 -5696
FAX: (817) 635 -5699
SOUTHCENTER
0
LLI
LL
(.% )
LLI
SOUTHCENTER MALL
CD
1
00
00
00
EXPIRES
06 -23-08
REVISIONS
ISSUED FOR PERMIT /CONSTRUCTION
28 JAN. 08
ELECTRICAL
SPECIFICATIONS
MSMENIMMEEMEIM
SHEET NUMBER
OP.FIT E - 6
ELECTRICAL ENGINEERING, INC
1786 Augusta Ln Ste 6, Yuba City, CA 95993
Ph: 530.790.0620 Fax 530.671.9792