HomeMy WebLinkAboutPermit EL11-0394 - TUKWILA SOUTH - SEGALE PROPERTTUKWILA SOUTH
SEGALE PROPERTIES
SOUTHCENTER BL
EL1 1 -0394
Parcel No.: 0322049006
Address:
City* Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Inspection Request Line: 206 -431 -2451
Web site: http: / /wwwci.tukwila.wa.us
ELECTRICAL PERMIT
Tenant Name: TUKWILA SOUTH - SEGALE PROPERTIES
Permit Number: EL11 -0394
Issue Date: 05/16/2011
Permit Expires On: 11/12/2011
Owner:
Name:
Address:
Contact Person:
Name:
Address:
BARRY BENNETT
PO BOX 88028 , TUKWILA WA 98188
Contractor:
Name: WILSON CONSTRUCTION COMPANY
Address: PO BOX 1190 , CANBY OR 97013
Contractor License No: WILSOCC066RK
Phone: 206 - 396 -2012
Phone: 509 374 -1455
Expiration Date: 12/12/2012
DESCRIPTION OF WORK:
INSTALL TEMPORARY POWER TO REGIONAL TESC POND #5. THIS IS A CONTINUATION OF
PERMIT NO. EL 10 -080 (TUKVVILA SOUTH PROJECT).
Value of Electrical Work: NRES: $12,500.00
RES: $0.00
Type of Fire Protection: NONE
Electrical Service Provided by: PUGET SOUND ENERGY
Permit Center Authorized Signature:
I hereby certify that I have read and
governing this work will be complie
Fees Collected: $395.13
National Electrical Code Edition: 2008
Date:
ed this permit and know the same to be true and correct. All provisions of law and ordinances
whether specified herein or not.
The granting of this permit does not pres
construction or the performance of work.
of this permit.
Signature: en_,
e to give authority to violate or cancel the provisions of any other state or local laws regulating
I am authorized to sign and obtain this electrical permit and agree to the conditions on the back
Date: 5- 25 -0
Print Name: fir 1/ an 018ccAy
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doe: EL -9/09
EL11 -0394 Printed: 05 -25 -2011
• •
PERMIT CONDITIONS
Permit No. EL11 -0394
* *ELECTRICAL **
1: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical Inspector
at each work site.
2: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical Inspector.
3: All electrical work shall be in accordance with NFPA 70 - NEC, and requirements for electrical installations, Chapter
296 -46B WAC.
4: When any portion of the electrical installation is to be hidden from view by permanent placement of parts of the
building, such equipment shall not be concealed until it has been inspected and approved by the Electrical Inspector.
5: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any violation
of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related documentation that
presumes to grant this authority are therefore not valid.
6: Any change in the scope of work described by the electrical work permit shall require additional work permits. Where
approved plans have been issued, revisions to the plans and additional review may be required.
doc: EL -9/09
EL11 -0394 Printed: 05 -25 -2011
Site Address:
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
httal/www.ci.tukwita.wa.us
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
South of 200th Street and West of Frager RD
Tenant Name: N/A
Property Owners Name: Segale Properties LLC
King Co Assessor's Tax No.: 03,2 yq / (.7,2: )4{9 ors
Suite Number: N/A Floor: N/A
New Tenant: ❑ Yes 0 .. No
Mailing Address: PO Box 88028
Tukwila
WA
98188
City
State
Zip
CONTACT PERSON ' Who do w
ct
when your permit
s ready to be issued
Name: Barry Bennett
Mailing Address: PO Box 88028
Day Telephone: (206) 396 -2012
Tukwila WA 98188
E -Mail Address: BBennett @segaleproperties.com
City State
Fax Number: (206) 575 -1662
Zip
ELECTRICAL CONTRACTOR INFORMATION
Company Name:
Mailing Address:
Bryan Moody
PO Box 1190
Canby
OR 97013
Contact Person: Bryan Moody
E -Mail Address: Bmoody @wilsonconst.com
Contractor Registration Number: WILSOC''"Z53'P3'
LO(lU, t lL
City State
Day Telephone: (360) 280 -6152
Fax Number: (503) 263 -6946
Expiration Date: 07/07/2012
Zip
Valuation of Project (contractor's bid price): $ 12,500
Scope of Work (please provide detailed information): Install temporary power to regional TESC pond #5. This is a
continuation of permit # EL10 -0808. This is for the Tukwila South project.
Will service be altered? ❑ Yes 10 No
Type of Use: New lines will power TESC pond #5
Tvpe of work:
VI New ❑ Addition ❑ Service Change
❑ Low Voltage ❑ Generator ❑ Fire Alarm
Property Served by:
m Puget Sound Energy
❑ Seattle City Light
H:\Applications\Forms- Applications On Line\2010 Applications \7 -2010 - Electrical Permit Application.doc
bh
Page 1 of 2
Adding more than 50 amps? m Yes ❑ No
❑ Remodel ❑ Tenant Improvement
❑ Telecommunication VI Temporary Service
RESIDENTIAL
NEW RESIDENTIAL SERVICE
❑ New single family dwellings $152.85
(including an attached garage)
❑ Garages, pools, spas and outbuildings $81.90 ea
❑ Low voltage systems
(alarm, furnace thermostat) $59.85 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
❑ Service change or alteration $81.90
(no added/altered circuits)
❑ Service change with added/altered circuits $81.90
number of added circuits $11.55 ea
❑ Circuits added/altered without service change $54.60
(up to 5 circuits)
❑ Circuits added/altered without service change $54.60
(6 or more circuits) $7.65 ea
❑ Meter /mast repair $68.25
❑ Low voltage systems $59.85
(alarm, furnace thermostat)
MULTI - FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
❑ Temporary service (residential) $63.00
❑ Temporary service (generator) $78.75
❑ Manufactured/mobile home service $84.00
(excluding garage or outbuilding)
❑ Carnivals $78.75
Number of concessions $10.50 ea
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR ELECTRICAL CONTRACTOR:
Signature:
Print Name: 17Gt l3€b\ Ae-
Mailing Address: Bbennett@segaleproperties.com
Date: 05/03/2012
Day Telephone: (206) 396 -2012
Tukwila
WA
City
IDate Application Accepted: i4 1
Date Application Expires:
1I -4 -11
H:\ Applications\Forms- Applications On Line\2010 Applications \7 -2010 - Electrical Permit Application.doc
bh
Page 2 of 2
State
98188
Zip
Staff Initials: r 1
• •
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: Permit Number: EL11 -0394
Address: Status: PENDING
Suite No: Applied Date: 05/04/2011
Applicant: SEGALE PROPERTIES - TUKWILA SOUTH Issue Date:
Receipt No.: R11 -00889
Initials: BLH
User ID: ADMIN
Payment Amount: $395.13
Payment Date: 05/04/2011 01:01 PM
Balance: $0.00
Payee: SEGALE PROPERTIES
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 629843 395.13
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
ELECTRICAL PERMIT - NONR
ELECTRICAL PLAN - NONRES
000.322.101.00.00 316.10
000.345.832.00.00 79.03
Total: $395.13
doc: Receiot -06 Printed: 05 -04 -2011
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -36
Permit Inspection Request Line (206) 431 -2451
INSPECTION RECORD
Retain a copy with permit
PERMIT
Project- 14 5 __seat(
Type of Inspection:
00 ,
Address:
Date Called:
Special Instructions:
Date Wanted:
t
6 1
a:m
Requester:
77
Phone No:
MApproved per applic}le code
COMMENTS:
r
aCorrections required prior to approval.
1
...,:...:
• • -4
• J Y
Inspector:
Date:
17 1•
n REINSPECTION FEE REQUIR D. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
•
• •
PE T
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: EL11 -0394 DATE: 05 -04 -11
PROJECT NAME: SEGALE SOUTH - TUKWILA PROPERTIES
SITE ADDRESS: SOUTH OF 200 ST WEST OF FRAGER RD
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # After Permit Issued
DEPARTMENTS:
ding Divi Is on
Public Works
Fire Prevention
Structural
n
Planning Division
Permit Coordinator
n
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Incomplete
DUE DATE: 05 -05 -11
Not Applicable
n
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROUTING:
Please Route
Structural Review Required
No further Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
DUE DATE: 06-02-11
Approved Approved with Conditions ® Not Approved (attach comments) n
Notation:
REVIEWER'S INITIALS: DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents /routing slip doc
2 -28 -02
Contractors or Tradespeople P ter Friendly Page
•
Electrical Contractor
A business licensed by L &I to contract electrical work within the scope of its specialty. Electrical
Contractors must maintain a surety bond or assignment of savings account. They also must have a
designated Electrical Administrator or Master Electrician who is a member of the firm or a full -time
supervisory employee.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent Company
WILSON CONSTRUCTION COMPANY
5032636882
1190 Nw Third Ave
PO BOX 1190
Canby
OR
97013
Out Of State
Corporation
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Specialty 1
Specialty 2
409008687
Active
WILSOCC066RK
Electrical Contractor
12/12/1994
12/12/2012
General
Unused
Electrical Administrator INFORMATION
License SZENDM'055LC
Name SZENDRE, MONTE
Status Active
Business Owner Information
Name
Role
Effective Date
Expiration Date
C T CORPORATION,
Agent
11/15/2002
5/19/2009
WILSON, DONALD M
President
01/01/1980
$250.00
WILSON, KIM E
Secretary
01/01/1980
ELECTRICAL CITATION
WILSON, STACY A
Treasurer
11/22/2004
3/8/2011
WILSON, NORMA E
Vice President
01/01/1980
$250.00
SZENDRE, MONTE R
Agent
01/01/1980
11/15/2002
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
3
WESTERN SURETY CO
58624396
12/07/2004
Until Cancelled
$4,000.00
11/11/2004
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information No records found for the previous 6 year period
Summons /Complaint Information Summons and Complaints are not filed with the department for this contractor type
Warrant Information Warrants are not filed with the department for this contractor type
Infractions /Citations Information
Infraction / Citation
Date
RCW Code
Type
Status
Violation Amount
ECUNE00330
5/19/2009
19.28.101 RCW
ELECTRICAL CITATION
Satisfied
$250.00
EHUDR00237
3/8/2011
19.28.101 RCW
ELECTRICAL CITATION
Satisfied
$1,000.00
EHUDR00238
3/8/2011
19.28.101 RCW
ELECTRICAL CITATION
Satisfied
$250.00
https: // fortress .wa.gov /lni/bbip/Print.aspx 05/25/2011
11:27am I: \Shared \NorthSky \A5 Engineering Work \Working \134000090__ — Segale_OH South of 200th NEW_NSE Design 04262011.dwg
Apr 29,. 2011
Segale Properties -Phase II
Customer Owned Temporary OH & UG Medium Voltage 12.5kV 3-PhaseLine Extension
PLEASE NOTE:
FOR INFORMATION NORTH OF THIS PROJECT PLEASE SEE SEGALE PROPERTIES - NORTH SKY
WORK ORDER NUMBER 13400009032 or TUKWILA PERMIT NUMBER EL10 -0808
WORKZONE 1
POLES 14, 17 - 21 & VO4, V05
SEE SHEET 3
08 4
COMPREHENSIVE PROJECT OVERVIEW
NOT TO SCALE
LOAD DATA SCHEDULE - PHASE I CONSTRCUTION
SEPARATE PERMIT
REQUIRED FOR:
I 'Mechanical
❑ Electrical
ID� �Plumbing
[,,, iaas Piping
(7y of Tukwila
DIVISION
INSPECTOR NOTE:
• CUSTOMER IS INSTALLING MOTORS THAT WILL CYCLE AND PUMP ON DEMAND ONLY
AND ARE NOT CONTINUOUSLY RUNNING.
LOAD DATA SCHEDULE - PHASE II CONSTRCUTION
Service
Phase and
Voltage
Panel
Size
Estimated
Demand
Factor
Estimated kW Demand Per Panel
Calculation Methodology
Estimated kVA Required Per Panel
Calculation Methodology
NEW Proposed
Transformer Size
Transformer "V01"
30 480Y/277
100A
80%
100A X 1.73 X 480 X 95% 78888
79kW
100A X 480 X 1.73 83040
84kVA
112.5kVA
= =
1000 1000
=
1000 1000
Transformer "V02"
30- 480Y/277
200A
80%
200A X 1.73 X 480 X 95% 157776
158kW
200A X 480 X 1.73 166080
167kVA
225kVA
= =
1000 1000
= =
1000 1000
Transformer "V03"
30- 480Y/277
400A
80%
400A X 1.73 X 480 X 95% 315552
316kW
400A X 480 X 1.73 332160
333kVA
500kVA
= =
1000 1000
= =
1000 1000
Total Estimated kW
553kW
Total Estimated kVA
584kVA
INSPECTOR NOTE:
• CUSTOMER IS INSTALLING MOTORS THAT WILL CYCLE AND PUMP ON DEMAND ONLY
AND ARE NOT CONTINUOUSLY RUNNING.
LOAD DATA SCHEDULE - PHASE II CONSTRCUTION
INSPECTOR NOTE:
• CUSTOMER IS INSTALLING MOTORS THAT WILL CYCLE AND PUMP ON DEMAND ONLY
AND ARE NOT CONTINUOUSLY RUNNING.
PROJECT SCOPE OVERVIEW
THIS PROJECT ENCOMPASSES THE DESIGN AND CONSTRUCTION OF A NEW 12,470 VOLT 3 -PHASE CUSTOMER OWNED MEDIUM VOLTAGE OVERHEAD AND UNDERGROUND FUSED DISTRIBUTION SYSTEM
(3 -WIRE UNGROUNDED WYE AND A GROUND CONDUCTOR) TO SERVE THE STORM WATER PUMPS FOR THE SOUTHCENTER PARKWAY EXTENSION PROJECT, LOCATED IN TUKWILA, WASHINGTON. THE
NEW 3 -PHASE OVERHEAD DISTRIBUTION SYSTEM STARTS AT THE LOAD -SIDE OF THE EXISTING UTILITY MASTER (PRIMARY) METER AND TERMINATES AT THE 600V SECONDARY TERMINAL BUS IN THE
CUSTOMER OWNED TRANSFORMERS WHERE NORTH SKY'S ELECTRICAL DESIGN ENDS.
SPECIFICALLY, THIS IS PHASE II OF THE PROJECT WHICH STARTS AT AN EXISTING POLE ON THE NORTH SIDE OF SOUTH 200TH STREET AND EXTENDS SOUTH APPROX. 1,220'. THE PROJECT CONSISTS
OF INSTALLING 5 NEW FULLY PRESSURE TREATED WOOD POLES AND RESPECTIVE GUYING, ANCHORING AND GROUNDING. IT INCLUDES APPROX. 1,325 LINEAR FEET OF NEW #2 ACSR ( ALUMINUM
CONDUCTOR STEEL REINFORCED) PRIMARY OVERHEAD CONDUCTORS, AND #2 ACSR PRIMARY GROUND IN THE HORIZONTAL (PRIMARY) POSITION.
ALSO INCLUDED ARE (3) NEW 200 AMP FUSED DISCONNECTS FOR THE OVERHEAD TO UNDERGROUND TERMINATION ASSEMBLIES. FROM THE NEW 30 TERMINATIONS, THE NEW CUSTOMER OWNED
MEDIUM VOLTAGE UNDERGROUND DISTRIBUTION SYSTEM WILL DISTRIBUTE VIA A 4" SCH40 DUCT SYSTEM WITH (3)1/0 CU. MV105 CABLES WITH A SEPARATE 600V COVERED GROUND IN THE SAME
CONDUIT TO SERVE (2) NEW PAD MOUNTED 300KVA 480Y/277V PAD MOUNTED TRANSFORMERS (NEMA 3R, OUTDOOR, TYPE) WHICH WILL SET ON A CONCRETE LID AS INDICATED ON THE ENCLOSED
DRAWINGS.
POLES AND EQUIPMENT TO BE BUILT PER THE LOCAL UTILITY (PUGET SOUND ENERGY) STANDARDS FOR EASE OF FUTURE REPLACEMENT AND MAINTENANCE UNLESS OTHERWISE NOTED
REVISIONS PROJECT CONTACT LIST
No changes shall be made to the scope
of Work without prior approval of SEGALE PROPERTIES
Tukwila Building Division.
"7: ; :visions will require a new plan submittal
-,J may include additional plan review fees. 1
FILE COPY
Permit No., CAA I 0 t11
Pte!t review approval is subject to errors and omission.
of construction documents does not authorize
fr►(, `4' olation of any adopted code or ordinance. Receipt
of approved Field Copy and conditions is acknowledged:
By 114
Date: 5 -2 s— 14
City Of Tukwila
BUILDING DIVISION
TABLE OF CONTENTS
DESCRIPTION
Service
Phase and
Voltage
Panel
Size
Estimated
Demand
Factor
Estimated kW Demand Per Panel
Calculation Methodology
Estimated kVA Required Per Panel
Calculation Methodology
NEW Proposed
Transformer Size
Transformer "VO4"
30- 480Y/277
300A
80%
300A X 1.73 X 480 X 95% : 236664
237kW
300A X 480 X 1.73 249120
250kVA
300kVA
_ =
1000 1000
= =
1000 1000
Transformer "V05"
30- 480Y/277
300A
80%
300A X 1.73 X 480 X 95% 236664
237kW
300A X 480 X 1.73 249120
250kVA
300kVA
= =
1000 1000
= =
1000 1000
Total Estimated kW
474kW
Total Estimated kVA
500kVA
INSPECTOR NOTE:
• CUSTOMER IS INSTALLING MOTORS THAT WILL CYCLE AND PUMP ON DEMAND ONLY
AND ARE NOT CONTINUOUSLY RUNNING.
PROJECT SCOPE OVERVIEW
THIS PROJECT ENCOMPASSES THE DESIGN AND CONSTRUCTION OF A NEW 12,470 VOLT 3 -PHASE CUSTOMER OWNED MEDIUM VOLTAGE OVERHEAD AND UNDERGROUND FUSED DISTRIBUTION SYSTEM
(3 -WIRE UNGROUNDED WYE AND A GROUND CONDUCTOR) TO SERVE THE STORM WATER PUMPS FOR THE SOUTHCENTER PARKWAY EXTENSION PROJECT, LOCATED IN TUKWILA, WASHINGTON. THE
NEW 3 -PHASE OVERHEAD DISTRIBUTION SYSTEM STARTS AT THE LOAD -SIDE OF THE EXISTING UTILITY MASTER (PRIMARY) METER AND TERMINATES AT THE 600V SECONDARY TERMINAL BUS IN THE
CUSTOMER OWNED TRANSFORMERS WHERE NORTH SKY'S ELECTRICAL DESIGN ENDS.
SPECIFICALLY, THIS IS PHASE II OF THE PROJECT WHICH STARTS AT AN EXISTING POLE ON THE NORTH SIDE OF SOUTH 200TH STREET AND EXTENDS SOUTH APPROX. 1,220'. THE PROJECT CONSISTS
OF INSTALLING 5 NEW FULLY PRESSURE TREATED WOOD POLES AND RESPECTIVE GUYING, ANCHORING AND GROUNDING. IT INCLUDES APPROX. 1,325 LINEAR FEET OF NEW #2 ACSR ( ALUMINUM
CONDUCTOR STEEL REINFORCED) PRIMARY OVERHEAD CONDUCTORS, AND #2 ACSR PRIMARY GROUND IN THE HORIZONTAL (PRIMARY) POSITION.
ALSO INCLUDED ARE (3) NEW 200 AMP FUSED DISCONNECTS FOR THE OVERHEAD TO UNDERGROUND TERMINATION ASSEMBLIES. FROM THE NEW 30 TERMINATIONS, THE NEW CUSTOMER OWNED
MEDIUM VOLTAGE UNDERGROUND DISTRIBUTION SYSTEM WILL DISTRIBUTE VIA A 4" SCH40 DUCT SYSTEM WITH (3)1/0 CU. MV105 CABLES WITH A SEPARATE 600V COVERED GROUND IN THE SAME
CONDUIT TO SERVE (2) NEW PAD MOUNTED 300KVA 480Y/277V PAD MOUNTED TRANSFORMERS (NEMA 3R, OUTDOOR, TYPE) WHICH WILL SET ON A CONCRETE LID AS INDICATED ON THE ENCLOSED
DRAWINGS.
POLES AND EQUIPMENT TO BE BUILT PER THE LOCAL UTILITY (PUGET SOUND ENERGY) STANDARDS FOR EASE OF FUTURE REPLACEMENT AND MAINTENANCE UNLESS OTHERWISE NOTED
REVISIONS PROJECT CONTACT LIST
No changes shall be made to the scope
of Work without prior approval of SEGALE PROPERTIES
Tukwila Building Division.
"7: ; :visions will require a new plan submittal
-,J may include additional plan review fees. 1
FILE COPY
Permit No., CAA I 0 t11
Pte!t review approval is subject to errors and omission.
of construction documents does not authorize
fr►(, `4' olation of any adopted code or ordinance. Receipt
of approved Field Copy and conditions is acknowledged:
By 114
Date: 5 -2 s— 14
City Of Tukwila
BUILDING DIVISION
TABLE OF CONTENTS
DESCRIPTION
SHEET
TABLE OF CONTENTS
COMPREHENSIVE PROJECT OVERVIEW
PROJECT SCOPE
PROJECT CONTACT LIST
VICINITY MAP
1
GENERAL CONSTRUCTION NOTES
ELECTRICAL SYMBOLS LEGEND •
ABBREVIATION KEY
2
SITE PLAN WORKZONE 1
CONSTRUCTION NOTES
3
ONE -LINE CIRCUIT SCHEMATIC
ONE -LINE CONDUIT AND CABLE DIAGRAMS
TRENCH DETAIL
CABLE TAG DETAIL
4
POLE DETAILS
TRANSFORMER DETAILS
5
TECHNICAL SCHEDULES
6
PRO
1
REVIEWED FOR
COMPLIANCE OC N�WCITH
MAY 122011
t1.37Ci of .Tukwila
BUILDING DIVISION
l;, 5
.1ZOTH
5171St ST
.172ND'.
MARIO SEGALE
MARK SEGALE
TODD COVEY
OWNER
OWNER
PROJECT MANAGER
(206) 575 -2000
(206) 575 -2000
(206) 575 -2000
NORTH SKY ENGINEERING (PRIVATE MV ELECTRIC SYSTEM)
CLINT TH■YER - ENGINEER - (425) 864 -0566
5
1:5100
173RD$ Q;3: <ST`,
5 1.1311,1 511
26
C
CORPORAT_
n DR .N
m
%D MINKLER
I1. J%� Q' �
WI' r I i -cH.
� JSjLH$A � 1 GREEYAFI r
\ -PARK
ST 1.
s `T 50Th 4QW .
�s .r,ls IOW
is `� L L 0110178TH"
.BON
5 SO- __,__�i 174tH
to-
,LANDS t 's
I sw
. ST
a�
41
1'I SW
38TH
ST
RENTON
WETLANDS
L - TR1l1AND bR
5E00 S
L_ LA
SW 43RD
5T
19151
ST
s 118280
ST
fi"SPRI NC,9,R ppl(,ni
GREENBELIT
7550/7/5
INPLA
8111118.
BY
M RRIOTT
S^
ti> o
CUR
ST
190TH .6800
�T
S 191ST
PL
S 1193RD.
f rL
5600
196TH
182ND ST
184TH ST
186TH ---Pt
5.188TH ST
190TH_ST
— S- 192ND
ST
o
s 194TH c°
Si j
ST
200TH
:204TH
ST
NGINEERING
A `u, UANTA SERVICES COMPANY
2224 104th Avenue East
Suite 1
Edgewood, WA 98372
Office (253) 952 -2128
Fax (253) 952 -2140
13400009037
NSC Job Number:
Clint Thayer
Engineer.
Clint Thayer
Drafter.
Barry Eronson
Checked:
Wayne Hagan
Approved:
. _.
-; w I S'F ?: 07
(iG�`f
C?\ . 1
302.3?
• „;r Y,..16-+ c /2 q /il
EXPIRES 11/19/ Z.0 11
Revisions
No. Date Description
Segale Properties
Phase 11
Customer Owned Temporary
OH & UG Medium Voltage
12.5kV 30 Line Extension
From South 200th Street,
South to just North of South
204th Street
ECEIVED
MAY 04 20i1.
RMIT CENTE
S
- -
1 16
08TH ST
5 209TH ST+
1I
0L420o S: . <.Z16 i
216TH ST
VICINITY MAP
NOT TO SCALE
12
0 I 1 IV 216TH
039'1
Cover Sheet
Project Overview
Project Scope
Table of Contents
Contact List
Vicinity Map
Sheet 1 of 6
11:28am I: \Shared \NorthSky \A5 Engineering Work \Working \134000090__ — Segale_OH South of 200th\ NEW_NSE Design 04262011.dwg
GENERAL CONSTRUCTION NOTES
PRE - CONSTRUCTION:
• AN ON -SITE PRE CONSTRUCTION MEETING IS REQUIRED PRIOR TO THE START OF
CONSTRUCTION. THE PROJECT ENGINEER WILL BE SCHEDULED TO ATTEND THIS MEETING TO
PROVIDE INPUT AND CLARIFICATION.
• LOCATE & MARK ALL UTILITIES PRIOR TO CONSTRUCTION, UTILIZING THE LOCAL "ONE- CALL"
SYSTEM AND ANY UTILITIES WHICH DO NOT PARTICIPATE OR "PRIVATE LOCATORS ".
PERMIT REQUIREMENTS:
• PRIOR TO CONSTRUCTION, CONTRACTOR SHALL SECURE ALL NECESSARY CONSTRUCTION
PERMITS DEEMED NECESSARY .
• NOTIFY LOCAL L &I AUTHORITIES 48 TO 72 HOURS OR AS REQUIRED BY PERMITTING AGENCY
BEFORE STARTING WORK.
QUALIFIED WORKERS:
• ALL CONSTRUCTION SHALL BE PERFORMED BY QUALIFIED ELECTRICAL WORKERS.
SAFETY:
• EMPLOYEES SHALL ADHERE TO ALL SAFETY REQUIREMENTS AT ALL TIMES
• USE PROPER VEHICLE GROUNDING AND BARRICADING PER STATE AND FEDERAL
REQUIREMENTS.
• SYSTEM GROUNDING REQUIREMENTS, PER STATE AND FEDERAL CODES SHALL BE USED.
• PERSONAL PROTECTIVE GROUNDING REQUIREMENTS, PER STATE AND FEDERAL CODES
SHALL BE USED.
WORKING DRAWINGS:
• LOCATIONS OF EXISTING FEATURES AND FACILITIES ARE BASED ON DRAWINGS PROVIDED BY
THE OWNER. FIELD VERIFICATION SHOULD BE MADE BEFORE STARTING PROJECT.
• MAINTAIN ON SITE, IN GOOD CONDITION, A COMPLETE FILE OF CONSTRUCTION DRAWINGS.
• THESE DRAWINGS SHALL BE AVAILABLE AT ALL TIMES TO THE OWNER'S SITE
REPRESENTATIVE, AND THE ELECTRICAL INSPECTOR.
• CORRECTIONS AND CHANGES MADE DURING CONSTRUCTION SHALL BE RECORDED
CONTINUOUSLY ON THESE DRAWINGS.
• ANY CHANGES TO THIS DESIGN SHALL FOLLOW NOTIFICATION AND APPROVAL FROM THE
OWNER OR THE DESIGN ENGINEER PRIOR TO ANY CONSTRUCTION REVISIONS.
MATERIAL:
• ALL MATERIALS SHALL BE UL LISTED AND RATED IN COMPLIANCE WITH NEC, NESC AND ANSI
STANDARDS.
• OVERHEAD PRIMARY AND SYSTEM GROUNDING CONDUCTORS SHALL CONSIST OF #2 ACSR
(PHASES) AND #2 ACSR GROUND. (MULTI- GROUNDED AT EACH POLE)
• UNDERGROUND MEDIUM VOLTAGE CONDUCTORS TO CONSIST OF (3) 1/0 STRANDED C.U.
MV -105 EPR 15kV RATED JACKETED 133% INSULATED, AND (1) COVERED #2 STRANDED C.U.
MULTI - GROUNDED 600V INSULATED COVERED (THHW) GROUND CONDUCTOR.
EXCAVATION, FRAMING & INSTALLATION OF WOOD POLES:
• POLE EXCAVATIONS SHALL BE MAINTAINED IN A SAFE CONDITION AT ALL TIMES TO PROTECT
THE WORKERS.
• OPEN EXCAVATIONS LEFT OPEN OVERNIGHT OR NON WORKING DAYS SHALL BE COVERED OR
SECURED BY MEANS ACCEPTABLE TO THE OWNER.
• EXCAVATION IN EARTH SHALL HAVE CLEAN LEVEL SURFACES OF UNDISTURBED MATERIAL
WITH ADEQUATE BEARING CAPACITY.
• POLES ARE TO BE INSTALLED OR RELOCATED AS STAKED. UNLESS OTHERWISE NOTED, ALL
POLE LOCATION MEASUREMENTS ARE FROM THE CENTER OF THE POLE.
• NEW POLES SET SHALL BE THE CLASS INDICATED ON THE SKETCH, OR BETTER.
• POLES AND ANCHORS WILL BE STAKED PRIOR TO CONSTRUCTION.
• ALL POLE TO BE SET AT 10% +2' UNLESS OTHER WISE INDICATED.
• IF SOIL IS UNSUITABLE FOR BACK -FILL AROUND POLES, USE 5/8" CRUSHED ROCK.
• TREAT HOLES DRILLED IN THE FIELD WITH COPPER NAPHTHENATE.
• IF POSSIBLE, ORDER POLES PREDRILLED AND FULLY TREATED FROM THE MANUFACTURE.
• FRAME POLES PER LOCAL UTILITY STANDARDS FOR EASE OF REPLACEMENT IN THE CASE OF
EMERGENCY. SEE FRAMING DETAILS.
• APPLY GRIT INHIBITOR ON ALL STIRRUP, AND DEAD -END CONNECTIONS.
• ALL GROUND CONDUCTOR CONNECTIONS TO BE MADE WITH SOLID COMPRESSION
CONNECTORS. CONNECT ALL POLE GROUNDS TO COMMON NEUTRAL.
• ALL PRIMARY AND SYSTEM GROUND CONDUCTORS SHALL BE PULLED IN USING THE
APPROPRIATE RULING SPAN AND SAG TABLES PROVIDED ON THE DESIGN.
• ALL CONNECTIONS TO THE SYSTEM GROUND CONDUCTOR WIRE WILL BE COMPRESSION TYPE
PRESSED CONNECTIONS FOR EFFECTIVE BONDING
GUYING:
• DEAD ENDING THE PRIMARY AND GROUND CONDUCTORS REQUIRES MULTIPLE 3/8" GUYS WITH
A MINIMUM LEAD OF 20', UNLESS OTHERWISE NOTED.
• ANCHORS TO BE TRIPLE -HELIX SCREW IN TYPE WITH A 1 1/2" ROD EXTENSIONS .
• YELLOW PLASTIC GUY GUARDS TO BE ON ALL DOWN GUYS. (FROM GROUND LEVEL UP TO 8'
ABOVE GRADE)
EQUIPMENT, VAULTS, ETC.:
• EQUIPMENT, EQUIPMENT PADS, SPLICE VAULTS, PEDESTALS, ETC. SHALL BE INSTALLED
PLUMB AND TRUE, AND SHALL BE SQUARE WITH THE ADJACENT STREETS, SIDEWALKS,
PROPERTY LINES, ETC. THE LOCATION OF SIMILAR ITEMS SHALL BE CONSISTENT.
• EQUIPMENT, EQUIPMENT PADS, SPLICE VAULTS, PEDESTALS, ETC, BEDDING MATERIAL SHALL
CONSIST OF A MINIMUM OF 3 TO 6 INCHES. USE 5/8" MINUS CRUSHED ROCK. BACKFILL SHALL
BE GOOD COMPATIBLE MATERIAL WITHOUT LARGE ROCKS, CHUNKS OR STICKS. BACKFILL
SHALL BE PROGRESSIVELY COMPACTED FROM THE BOTTOM TO THE TOP SURFACE, AND
SHALL BE WITHOUT VOIDS.
• CONDUIT AND CABLE ENTRANCES, ETC. SHALL BE SUITABLY SEALED AND /OR GROUTED TO
MAINTAIN THE INTEGRITY OF THE CONDUIT SYSTEM.
• ALL VAULTS SHALL BE PRECAST CONCRETE, WITH ONE -PIECE COVER, LOCKING GALVANIZED
STEEL ENTRANCE HATCH, KNOCKOUTS, DRAINS, EMBEDDED CHANNELS, ETC.
• MEDIUM VOLTAGE CABLE TERMINAL BLOCKS (JUNCTION BOXES) SHALL BE 15 kV, 4 POINT LOAD
BREAK CONNECTORS FOR USE WITH ELBOW TYPE HOT -STICK OPERABLE DEVICES WITH TEST
POINTS (SEE HIGH VOLTAGE CABLE SECTION FOR TYPE), WALL MOUNTED WITH MOUNTING
BRACKETS, 2 GROUND LUGS AND A MINIMUM OF 2 PARKING STANDS. MOUNTING HARDWARE,
ETC. SHALL BE STAINLESS STEEL. ELASTIMOLD 163J4R -7 STAINLESS STEEL, OR APPROVED
EQUAL.
• TRANSFORMER PADS SHALL BE PRE -CAST CONCRETE, MINIMUM 6" THICK, SIZE AS REQUIRED
WITH CABLE ENTRANCE OPENING(S) TO MATCH EQUIPMENT.
CONDUITS:
• CONDUITS SHALL BE SCHEDULE 40 PVC OR BETTER, FLAME RETARDANT, SUITABLE FOR USE
WITH 90 °C CABLE, SHALL NOT DISTORT FROM HEAT IT WILL NORMALLY ENCOUNTER AND
SHALL BE RESISTANT TO LOW TEMPERATURE AND SUNLIGHT EFFECTS, IMPACT AND
CRUSHING. FITTINGS, COUPLINGS, ETC. SHALL BE OF THE SAME MANUFACTURER AS THE
CONDUIT. ELECTRICAL POWER CONDUITS TO BE ELECTRICAL GRAY IN COLOR.
• CONDUITS SHALL BE INSTALLED WITH A MINIMUM 36" COVER TO FINAL GRADE UNLESS
OTHERWISE NOTED IN PLANS.
• JOINTS IN THE UNDERGROUND PVC CONDUIT SYSTEM SHALL BE SOLVENT WELDED TO
PREVENT THE ENTRANCE OF MOISTURE. PRIOR TO APPLYING SOLVENT, CONDUITS ENDS AND
CONNECTORS SHALL BE PREPPED WITH PURPLE ETCHING PRIMER.
• POWER CONDUIT ELBOWS AND BENDS SHALL BE MINIMUM 36 INCH RADIUS WHEN CONTAINING
15 kV CABLES AND MINIMUM 24" RADIUS WHEN CONTAINING 600 VOLT CABLES.
• ALL CONDUIT ENTRIES INTO VAULTS TO BE MORTAR GROUTED AND SMOOTHLY FINISHED.
CONDUITS TO ENTER AT A PERPENDICULAR (90) ANGLE TO VAULT FACE.
• ALL CONDUITS IN TRENCH TO BE INSPECTED PRIOR TO BACKFILL FOR CORRECT DEPTH,
SEPARATION SAND - BEDDING AND COVER.
PRIMARY POWER CABLES:
• PRIMARY POWER CABLES SHALL BE 15 kV UNDERGROUND RESIDENTIAL DISTRIBUTION (URD)
CABLE, MV -105, COPPER, CLASS B STRANDED (COMPACTED) WITH AN EXTRUDED ETHYLENE
PROPYLENE RUBBER (EPR) SEMI - CONDUCTING STRESS CONTROL LAYER OVER THE
CONDUCTOR, MINIMUM 220 MIL EPR INSULATION (133% INSULATION LEVEL), EPR
SEMI - CONDUCTING INSULATION SHIELD, AND HMW BLACK POLYETHYLENE COMPOUND OUTER
JACKET.
• PRIMARY POWER CABLES SHALL BE SUITABLE FOR INSTALLATION IN UNDERGROUND CONDUIT
AT MAXIMUM CONDUCTOR TEMPERATURES OF 105 °C FOR CONTINUOUS NORMAL OPERATION,
130 °C FOR EMERGENCY OVERLOAD CONDITIONS AND 250 °C FOR SHORT CIRCUIT CONDITIONS.
• PRIMARY POWER CABLES SHALL BE FACTORY TESTED IN ACCORDANCE WITH THE
REQUIREMENTS OF ICEA AND AEIC, AND INCLUDE WITH EACH SHIPMENT OF CABLE A
CERTIFIED TEST REPORT IN DUPLICATE TOGETHER WITH A STATEMENT THAT THE CABLE
MEETS ALL THE REQUIREMENTS OF THIS SPECIFICATION AND INDUSTRY STANDARDS.
• PRIMARY POWER CABLE TERMINATIONS AT TRANSFORMERS, SPLICE VAULTS, ETC. SHALL BE
MADE WITH DEAD -END SUBMERSIBLE, HOT -STICK OPERABLE 200 AMP, 8.3/14.4kV LOAD BREAK
ELBOW TYPE TERMINATORS WITH TEST POINTS. TERMINATORS SHALL BE MOLDED OF EPDM
RUBBER ENCLOSED IN A MOLDED SEMI - CONDUCTIVE JACKET THAT IS GROUNDED DURING
OPERATION, AND PROVIDED WITH A STAINLESS STEEL REINFORCED PULLING EYE.
ELASTIMOLD TYPE 166LR, OR APPROVED EQUAL; COMPLETE WITH ALL NECESSARY
COMPONENTS AND /OR ACCESSORIES TO MAKE UP A COMPLETE AND OPERATIONAL SYSTEM.
• CABLE PULLING LUBRICANTS SHALL BE OF THE BEST QUALITY AND SHALL HAVE NO DAMAGING
EFFECT ON THE INSULATION AND CABLE JACKET.
• INSTALLATION OF ALL NEW MEDIUM VOLTAGE CABLE SHALL BE MEASURED AND RECORDED
WITH A CALIBRATED TENSION DEVICE AND SHALL NOT EXCEED THE MANUFACTURER'S
MAXIMUM ALLOWABLE PULLING TENSION, SIDEWALL PRESSURE AND BENDING RADIUS. THE
RECORDED TENSIONS CAN BE DIGITAL AND OR MANUAL.
GROUNDING:
• GROUND RODS TO BE 3/ INCH DIAMETER BY 8 FEET LONG COPPER -CLAD STEEL.
• THE MULTI - GROUNDED NEUTRAL CONDUCTOR SHALL BE 600V RATED CABLE, COPPER, CLASS
B STRANDED (COMPACTED), WITH POLYETHYLENE COMPOUND OUTER JACKET (THHW) IN THE
SAME CONDUIT AS THE PRIMARY CABLES. BLACK INSULATION WITH GREEN PHASE TAPE ON
EXPOSED SECTION AT EACH END.
• BEFORE GROUNDING CONNECTIONS ARE MADE, CONTACT SURFACES SHALL BE THOROUGHLY
CLEANED. CONNECTIONS SHALL BE BOTH MECHANICALLY AND ELECTRICALLY SECURE.
• INSTALL A GROUND MAT IN THE VICINITY OF ALL 600 AMP GANG OPERATED SWITCH HANDLES
AND BOND TO GROUND LOOP.
• GROUND RODS SHALL BE DRIVEN AT OPPOSITE CORNERS AT EACH VAULT AND VISIBLE FOR
INSPECTION. THE SEPARATION DISTANCE BETWEEN GROUND RODS TO BE A MINIMUM 6 FEET
• CONNECTIONS AT GROUND RODS SHALL BE INSTALLED PER MECHANICAL CONNECTIONS WITH
A #2 CU BARE GROUND WIRE ENTERING EACH VAULT AND BONDED TO THE GROUND LOOP
INSIDE.
TESTING:
• ALL ELECTRICAL ACCEPTANCE TESTING TO BE PERFORMED BY A VERIFIED TESTING
TECHNICIAN OR TESTING ENGINEER.
• ALL ELECTRICAL ACCEPTANCE TESTING OF EQUIPMENT, APPARATUS AND MATERIAL TO BE
PERFORMED IN ACCORDANCE WITH THE MOST CURRENT N.E.T.A. TESTING STANDARDS,
REQUIREMENTS AND PRACTICES.
• ALL UL EQUIVALENCY TESTING I.E. 'FIELD CERTIFICATION' TESTING TO BE PERFORMED BY A
QUALIFIED AND REGISTERED TESTING COMPANY AND TESTING ENGINEER.
ELECTRIC SYMBOLS LEGEND
•
NEW 30 TRANSFORMER / PADMOUNT
PSE PRIMARY METERING POINT
30 600A DISCONNECT SW G/O
15 kV RATED 'LOAD BREAK'
—t— OVERHEAD FUSE DISCONNECT SWITCH (SINGLE THROW SINGLE POLE)
—G —G —
A
•
O
DOWN GUY & ANCHOR
NEW OVERHEAD OR UNDERGROUND DISTRIBUTION SYSTEM
EXISTING OH UTILITY PRIMARY SYSTEM
GROUND LOOP IN VAULT, # 2 CU. BARE SOLID
NEW OH TO UG TERMINATION
FUSES
NEW POLE
EXISTING POLE
WOOD POLE PUSH BRACE
ABBREVIATIONS
kV
30
AAC
ACSR
ANCH
ASSY
AWG
CIR
C/O
CU
DBL
DE ,
FPT
G/O
MOV
MP
MV
OH
PRI
SCH.
SEC
SVC
SW
TYP
TW
UG
XFMR
- 1,000 VOLTS
THREE PHASE
- ALL ALUMINUM CONDUCTOR
ALUMINUM CONDUCTOR STEEL REINFORCED
ANCHOR
ASSEMBLY
AMERICAN WIRE GAUGE
- CIRCUIT
CUT -OUT (FUSED)
- COPPER
- DOUBLE
DEAD END
FULLY PRESSURE TREATED
- GANG- OPERATED
METAL OXIDE VARISTOR
METERING POINT
- MEDIUM VOLTAGE
OVERHEAD
PRIMARY 30 (12,470 VOLTS 0 TO 0 AND 7,200
VOLTS 0 TO GROUND)
SCHEDULE
- SECONDARY / LOW VOLTAGE 480Y/277 30
LESS THAN 600 VOLTS
- SERVICE
- SWITCH
TYPICAL
TREE WIRE
- UNDERGROUND
TRANSFORMER
REVIEWED FOR Y
COMPLIANCE 0� NECTH
MAY 12 2011
City of Tukwila
BUILDING DIVISION
RECEIVED
MAY 0 4 2011
PERMIT CENTER
EL\kO3P-
A
t'� UANTA SERVICES COMPANY
2224 104th Avenue East
Suite 1
Edgewood, WA 98372
Office (253) 952 -2128
Fax (253) 952 -2140
13400009037
NSC Job Number:
Clint Thayer
Engineer.
Clint Thayer
Drafter.
Barry Eronson
Checked:
Wayne Hagan
Approved:
''N'
, . ,
30331
1 f 0NA L, ,♦
/2 9///
EXPIRES 11/13/ 2O //
Revisions
No. Date Description
Segale Properties
Phase 11
Customer Owned Temporary
OH & UG Medium Voltage
12.5kV 30 Line Extension
From South 200th Street,
South to just North of South
204th Street
General Notes
Electrical Symbols Legend
Abbreviation Key
Sheet 2 of 6
rn
-o
0
N
0
. _
Q)
0
w
1
w
z
s
0
0
0
0
0
I
0
on
0
0•)
0
0
0
0
ro
0'
0
rn
.17
.61
C
w
U7
s
0
z
a)
0
s
E
0
SPECIFIC OH SITE CONSTRUCTION NOTES
P14 - (Customer Pole) -
- EXISTING 45' CLASS 3 PRIMARY POLE
EXISTING 10' 8 PIN SINGLE LINE ARM
INSTALL 10' 8 PIN DOUBLE LINE ARMS (IN THE BUCK POSITION)
INSTALL (3) #2ACSR ARM MOUNTED FULL TENSION DEADENDS (SOUTH TO "P17 ")
INSTALL (1) #2ACSR ARM MOUNTED FULL TENSION OH GROUND CONDUCTOR DEADEND (SOUTH TO "P17 ")
INSTALL (2) 3/8" PRIMARY DOWN GUY ASSEMBLIES (NORTH L =15')
INSTALL 10" TRIPLE HELIX ANCHOR (NORTH )
FOREMAN NOTE: HORIZONTAL CONSTRUCTION FOR ADDED CLEARANCE
P17 - (Customer Pole) -
INSTALL 60' CLASS 3 PRIMARY POLE
INSTALL 10' 8 PIN DOUBLE LINE ARMS
INSTALL (3) #2ACSR ARM MOUNTED FULL TENSION DEADENDS (NORTH TO "P14 ")
- INSTALL (1) #2ACSR ARM MOUNTED FULL TENSION OH GROUND CONDUCTOR DEADEND
- INSTALL 10' 8 PIN DOUBLE LINE ARMS (IN THE BUCK POSITION)
- INSTALL (3) #2ACSR ARM MOUNTED FULL TENSION DEADENDS (SOUTHEAST TO "P18 ")
- INSTALL (1) #2ACSR ARM MOUNTED FULL TENSION OH GROUND CONDUCTOR DEADEND
- INSTALL (2) 3/8" PRIMARY DOWN GUY ASSEMBLIES (SOUTH L =15')
- INSTALL 10" TRIPLE HELIX ANCHOR (SOUTH)
- INSTALL (2) 3/8" PRIMARY DOWN GUY ASSEMBLIES (NORTHWEST L =15')
INSTALL 10" TRIPLE HELIX ANCHOR (NORTHWEST)
FOREMAN NOTE: HORIZONTAL CONSTRUCTION FOR ADDED CLEARANC E
P18 - (Customer Pole) -
INSTALL 60' CLASS 3 PRIMARY POLE
INSTALL 10' 8 PIN DOUBLE LINE ARMS
INSTALL (3) #2ACSR ARM MOUNTED FULL TENSION DEADENDS (NORTHWEST TO "P17 ")
INSTALL (1) #2ACSR ARM MOUNTED FULL TENSION OH GROUND CONDUCTOR DEADEND
INSTALL 10' 8 PIN DOUBLE LINE ARMS (IN THE BUCK POSITION)
INSTALL (3) #2ACSR ARM MOUNTED FULL TENSION DEADENDS (SOUTH TO "P19 ")
INSTALL (1) #2ACSR ARM MOUNTED FULL TENSION OH GROUND CONDUCTOR DEADEND
INSTALL (2) 3/8" PRIMARY DOWN GUY ASSEMBLIES (SOUTHEAST L =15')
INSTALL 10" TRIPLE HELIX ANCHOR (SOUTHEAST)
INSTALL (2) 3/8" PRIMARY DOWN GUY ASSEMBLIES (NORTH L =15')
INSTALL 10" TRIPLE HELIX ANCHOR (NORTH)
FOREMAN NOTE: HORIZONTAL CONSTRUCTION FOR ADDED CLEARANC E
P19 - (Customer Pole) -
INSTALL 60' CLASS 3 PRIMARY POLE
INSTALL 10' 8 PIN SINGLE LINE ARM
INSTALL (3) 13kV RATED ARM MOUNTED PIN INSULATORS
INSTALL (1) 8kV RATED ARM MOUNTED PIN INSULATOR FOR THE OH GROUND CONDUCTOR
FOREMAN NOTE: HORIZONTAL CONSTRUCTION FOR ADDED CLEARANCE
NORTH TO "P14 ")
SOUTHEAST TO "P18 ")
(NORTHWEST TO "P17 ")
(SOUTH TO "P19 ")
—4-
SITE PLAN VIEW - WORKZONE 1
SCALE: 1" = 60'
50° L
1
1
1
1
1
—1
1
1
35 °L
00+01
SOUTHCENTER PARKWAY
oo+ aI
00+oa1
45 °L
SPECIFIC OH SITE CONSTRUCTION NOTES
P20 - (Customer Pole) -
- INSTALL 60' CLASS 3 PRIMARY POLE
- INSTALL 10' 8 PIN SINGLE LINE ARM
INSTALL (3) 13kV RATED ARM MOUNTED PIN INSULATORS
FOREMAN NOTE: HORIZONTAL CONSTRUCTION FOR ADDED CLEARANC E
- INSTALL FIBERGLASS TRI -UNIT ARM
- INSTALL 30 1/0 CU MV105 -EPR PRIMARY TERMINATION ASSEMBLY (TO "VO4 ")
- INSTALL (3) 10kV METAL OXIDE VARISTOR (MOV)
- INSTALL (3) LOAD - INTERUPTER CUTOUTS AND FUSE AT 40T
FOREMAN NOTE: INSTALL SWITCH NUMBER SW07
- INSTALL (1) 4" PRIMARY RISER ASSEMBLY
(FULL W/ NEW 30 15kV 1/0 CU MV105 -EPR CABLES)
P21 - (Customer Pole) -
INSTALL 60' CLASS 3 PRIMARY POLE
INSTALL 10' 8 PIN DOUBLE LINE ARMS
INSTALL (3) #2ACSR ARM MOUNTED FULL TENSION DEADENDS (NORTH TO "P21 ")
INSTALL (1) #2ACSR ARM MOUNTED FULL TENSION OH GROUND CONDUCTOR DEADEND (NORTH TO "P21 ")
INSTALL (2) 3/8" PRIMARY DOWN GUY ASSEMBLIES (SOUTH L =15')
INSTALL 10" TRIPLE HELIX ANCHOR (SOUTH)
FOREMAN NOTE: HORIZONTAL CONSTRUCTION FOR ADDED CLEARANC E
- INSTALL FIBERGLASS TRI -UNIT ARM
- INSTALL 30 1/0 CU MV105 -EPR PRIMARY TERMINATION ASSEMBLY (TO "VO4 ")
- INSTALL (3) 10kV METAL OXIDE VARISTOR (MOV)
- INSTALL (3) LOAD - INTERUPTER CUTOUTS AND FUSE AT 40T
FOREMAN NOTE: INSTALL SWITCH NUMBER SW08
- INSTALL (1) 4" PRIMARY RISER ASSEMBLY
(FULL W/ NEW 30 15kV 1/0 CU MV105 -EPR CABLES)
SPECIFIC UG SITE CONSTRUCTION NOTES
VO4 -
INSTALL 4'- 8 "X5' -6 "X6" COVER WITH 20 "X44" XFMR ACCESS HOLE
INSTALL 30 300kVA PADMOUNTED TRANSFORMER 480Y/277
INSTALL (3) LOAD -BREAK ELBOWS
INSTALL (2) 8'x3/4" DRIVEN GROUND RODS
PLUMB (1) 4" SCH40 PVC 20' TO "P20"
(CONDUIT FULL WI 30 15kV 1/0 CU JACKETED CABLES)
V05 -
SPECIFIC UG SITE CONSTRUCTION NOTES
INSTALL 4'- 8 "X5' -6 "X6" COVER WITH 20 "X44" XFMR ACCESS HOLE
INSTALL 30 300kVA PADMOUNTED TRANSFORMER 480Y/277
INSTALL (3) LOAD -BREAK ELBOWS
INSTALL (2) 8'x3/4" DRIVEN GROUND RODS
PLUMB (1) 4" SCH40 PVC 20' TO "P21"
(CONDUIT FULL W/ 30 15kV 1/0 CU JACKETED CABLES)
P14TOP17-
- INSTALL
- INSTALL
P17 TO P18 -
- INSTALL
- INSTALL
P18 TO P21 -
- INSTALL
- INSTALL
SPECIFIC OH SPAN NOTES
(3) #2ACSR PRIMARY CONDUCTOR APPROX. 125'
(1) #2ACSR OH GROUND CONDUCTOR APPROX. 125'
(3) #2ACSR PRIMARY CONDUCTOR APPROX. 300'
(1) #2ACSR OH GROUND CONDUCTOR APPROX. 300'
(Via P19, P20)
(3) #2ACSR PRIMARY CONDUCTOR APPROX. 900'
(1) #2ACSR OH GROUND CONDUCTOR APPROX. 900'
SPECIFIC UG SPAN NOTES
P20 TO VO4 -
INSTALL
INSTALL
INSTALL
INSTALL
P21 TO V054
INSTALL
INSTALL
INSTALL
INSTALL
(1) 4" SCH40 PVC CONDUIT APPROX. 20'
30 15kV RATED 1/0 CU MV105 -EPR CABLES APPROX. 75'
600V INSULATED #2 CU THHW GROUND CONDUCTOR APPROX. 75'
CABLE TAGS SP013, SP014, SP015
(1) 4" SCH40 PVC CONDUIT APPROX. 20'
30 15kV RATED 1/0 CU MV105 -EPR CABLES APPROX. 75'
600V INSULATED #2 CU THHW GROUND CONDUCTOR APPROX. 75'
CABLE TAGS SP016, SP017, SP018
Q(1-,/11
C/) 2 0
cn 8
< Z o
a W
0Ow
0 II
O Z
0_
w
Z cD Q
W LL _ W
QOM¢
w • O�
iizo):
Z w
O FE `o
• W
N
2 0• o
O a. 0
zj°
�Qco
Q �w
AV■
REVIEWED FOR
COMPLIANCE
N A NC
MAY 12 2011
City of Tukwila
BUILDING DIVISION
ELI I- 0 394
RECEIVED
MAY 04 2011
PERMIT CENTER
60' 0' 60'
SCALE
120'
IN FEET
A y� *. UANTA SERVICES COMPANY
1 +:
2224 104th Avenue East
Suite 1
Edgewood, WA 98372
Office (253) 952 -2128
Fax (253) 952 -2140
13400009037
NSC Job Number:
Clint Thayer
Engineer.
Clint Thayer
Drafter.
Barry Eronson
Checked:
Wayne Hagan
Approved:
rOE 1
\.,j, 30237 /4)1,
4 *4,0 NA1, . 2 !!
u i 1//
EXPIRES 11119/ ??O 11
Revisions
No. Date Description
Segale Properties
Phase 11
Customer Owned Temporary
OH & UG Medium Voltage
12.5kV 30 Line Extension
From South 200th Street,
South to just North of South
204th Street
Workzone 1
Construction Notes
Sheet 3 of 6
0426201 1.dwg
o)
0
0
z
w
-c
0
0
N
0
s
0
0
(DI
0
U)
0
0
0
0
0
I..
I Ty-
0
`0
0)
C
L
c
w
u0
(1)
L
O
z
0
I')
0
s
0
CD
Apr 29, 2011
@ vo 1
SECONDARY VOLTAGE - 480Y/277V
DISCONNECT SIZE - 100 AMP
@ V03
SECONDARY VOLTAGE - 480Y/277V
DISCONNECT SIZE - 400 AMP
500kVA
12,470V
480Y/277V 1
A -Y SWO6
40T
40A (C12)
FUSE
15A (C08)
FUSE
112.5kVA
12,470V
480Y/277V
A -Y
SWO5
200A S.B.
(3)1 POLE 1 THROW
SW03
/
/
/
I /
/
@ VO4
SECONDARY VOLTAGE - 480Y/277V
DISCONNECT SIZE - 200 AMP
DISCONNECT SIZE - 100 AMP
@ V05
SECONDARY VOLTAGE - 480Y/277V
DISCONNECT SIZE - 200 AMP
DISCONNECT SIZE - 100 AMP
17,200A>
300kVA
12,470V
480Y/277V
A -Y
SW02
65T
25A (C10)
FUSE
25A (C10)
FUSE
300kVA
12,470V
480Y/277V
A -Y
25A (C10)
FUSE
CUSTOMER OWNED
AND OPERATED
Swot
600A 30
3 POLE
1 THROW
SW07
40T
S W08
40T
<PSE 200A, 12.5kV
PRIMARY METER
PUGET SOUND ENERGY
Estimated Fault Current 0 to 0 - 7,500 Amps
Estimated Fault Current 0 to Ground - 5,500 Amps
SW04
40T
225kVA
12,470V
480Y/277V
A -Y
112,600A>
@ V02
SECONDARY VOLTAGE - 480Y/277V
DISCONNECT SIZE - 200 AMP
UNDERGROUND CABLE
(1/0 CU MV105, EPR)
OVERHEAD CONDUCTOR
(#2 ACSR)
90° L WITH 5'R
Pso OI
SW07
40T
(1) -4"
SP013
SP014
SP015
300kVA
12,470V
480Y/277
A -Y
110.i;
ONE LINE CONDUIT AND CABLE DIAGRAM
NOT TO SCALE / AFTER CONSTRUCTION
NOTE:
• ALL CONDUIT TO BE UL LISTED SCHEDULE 40 OR BETTER, ELECTRICAL GRADE,
GRAY
• CONDUIT DEFLECTION SHALL HAVE A 5' MINIMUM BENDING RADIUS
NOTES:
`.:J 15kV CABLE 1/0 AWG COPPER, STRANDED / SHIELDED (COMPACTED) 220 MIL EPR MV -105 WITH
600V RATED COVERED GROUND CONDUCTOR, COPPER, STRANDED (COMPACTED), WITH
THHW INSULATION IN THE SAME CONDUIT AS THE PRIMARY CABLE.
Xxxxxi> AVAILABLE 30 FAULT CURRENT (AMPS) AT SECONDARY LUGS IN TRANSFORMER. THESE
VALUES ARE BASED ON WORST CONDITION - ZERO LINE AND FAULT RESISTANCE WITH
INFINITE BUSS
ALL TRANSFORMERS ARE EQUIPPED WITH AN INTERNAL ISOLATION LINK IN SERIES WITH A
REMOVABLE REPLACEABLE EXPULSION (BAY -O -NET) FUSE
OVERHEAD & UNDERGROUND ONE -LINE CIRCUIT SCHEMATIC
NOT TO SCALE / AFTER CONSTRUCTION
e2D01
SW08
40T
(1) -4"
SP016
SP017
SP018
90° L WITH 5'R
300kVA
12,470V
480Y/277
L -Y
ONE -LINE CONDUIT AND CABLE DIAGRAM
NOT TO SCALE / AFTER CONSTRUCTION
tL1lO39'
SPXXX
NOTE:
1. POLYETHYLENE CABLE IDENTIFICATION TAG HAS
PHENOLIC 1/2" HIGH BLACK CHARACTERS ON A
CONTRASTING BACKGROUND.
2. ATTACH CABLE TAG WITH NYLON CABLE TIES TO
EACH END OF THE PRIMARY CABLE, ELBOW,
STRAIGHT SPLICE OR TERMINATION.
CABLE IDENTIFICATION TAG DETAIL
NOT TO SCALE
REVIEWED.FOR
COMPLIANCE WITH
NFPA 70 - NEC
18" Typical
MAY 12 2011
City of Tukwila
BUILDING DIVISION
Final Grade
36" Min
to
48" Max
Cover
Excavated Dirt Pile
24" Min -I
6" Sand Cover
4f
3" Sand Bedding
4" Sch40 PVC
RECEIVED
MAY 04 2011
PERMITCENTER
PRIMARY TRENCH EXCAVATION DETAIL
NOT TO SCALE
G /NEERI NG IN
A a UANTA SERVICES COMPANY
2224 104th Avenue East
Suite 1
Edgewood, WA 98372
Office (253) 952 -2128
Fax (253) 952 -2140
13400009037
NSC Job Number:
Clint Thayer
Engineer,
Clint Thayer
Drafter.
Barry Eronson
Checked:
Wayne Hagan
Approved:
ry) d� 0`
�:4 30,.37 � ' r, +
EXPIRES 11/19/ 2Q /j
Revisions
No. Date Description
Segale Properties
Phase 11
Customer Owned Temporary
OH & UG Medium Voltage
12.5kV 30 Line Extension
From South 200th Street,
South to just North of South
204th Street
Diagrams
One -Line Circuit Schematic
One -Line Conduit and
Cable Diagrams
Trench Excavation Detail
Cable Tag Detail
Sheet 4 of 6
11:29am I: \Shared \NorthSky \A5 Engineering Work \Working \134000090__ — Segale_OH South of 200th\ NEW_NSE Design 04262011.dwg
Apr 29, 2011
TANGENT POLE DETAIL
@ P19 & P20 / NOT TO SCALE
c�
DEAD END POLE DETAIL
@ P14 & P21 / NOT TO SCALE
NOTE:
FRAME POLES PER LOCAL UTILITY STANDARDS FOR EASE OF FUTURE MAINTENANCE
6"
Witatitaft
TRANSFORMER CONCRETE PAD DETAIL
@ VO4 AND V05 / NOT TO SCALE
NOTE: Provide 8" minimum of 5/8 - compacted
(100 %) crushed rock under pad for
transformer support.
DOUBLE DOUBLE DEAD -END POLE DETAIL
@ P17 & P19 / NOT TO SCALE
TRANSFORMER CASE
# 2 CU. BARE SOLID (TYP)
BOND TO TRANSFORMER CASE AND
BOTH GROUND RODS
(1) EA 8' LENGTH X 3/4" DIA CU. CLAD STEEL GROUND RODS
PLACE (1) ROD INSIDE SECONDARY (TYP)
TRANSFORMER PAD
36" Min
1 -4" PVC (TO TERM POLE)
GROUND ROD INSTALLATION DETAIL
@ VO4 & V05 FACING VAULT DOORS / NOT TO SCALE
CUSTOMER SUPPLIED CONDUIT (TYPICAL)
Install switchboard to be
black plastic w /white labels.
board dimensions = 24" high x 6"
wide using 5" high lettering mount
vertically and facing the road
12 ft min above ground
TERMINATION POLE DETAIL
AT P20 & P21 / NOT TO SCALE
30 TRANSFORMER CASE (VO4 & V05)
PRIMARY CABLE DRAIN WIRES
FROM CABLE SHIELDING
GROUND PAD ON
TRANSFORMER
E
PRIMARY
SECONDARY
'/C# 2 CU. COVERED GROUND IN
PRIMARY CONDUIT PERMITCENTER
NOTE: APPLY GREEN PHASE TAPE WHERE COVERED GROUND EXITS THE CONDUIT
REVIEWED. FOR
COMPLIANCE WITH
NFPA 74 - NEC
MAY 1 2 2011
City of Tukwila
BUILDING DIVISION
# 2 CU. SOFT DRAWN BARE CU. BUS
(TYP)
8' LENGTH X 3/4" DIA
GROUND ROD (INSIDE
TRANSFORMER DOORS
IN CABLE ACCESS AREA)
(TYP)
RECEIVED
MAY 04 2011
GROUNDING / BONDING SCHEMATIC
@ VO4 & V05 / NOT TO SCALE
A) UANTA SERVICES COMPANY
2224 104th Avenue East
Suite 1
Edgewood, WA 98372
Office (253) 952 -2128
Fax (253) 952 -2140
13400009037
NSC Job Number:
Clint Thayer
Engineer.
Clint Thayer
Drafter.
Barry Eronson
Checked:
Wayne Hagan
Approved:
3023? 44)
\.<!;/-,
STS . -'ceA
;1V l tr y %2q%l'
it
J
EXPIRES 11/19/ ?-011
Revisions
No. Date Description
Segale Properties
Phase II
Customer Owned Temporary
OH & UG Medium Voltage
12.5kV 30 Line Extension
From South 200th Street,
South to just North of South
204th Street
Pole Details
Tangent
Dead -End
Termination
Transformer Details
Sheet 5 of 6
11:30am I: \Shared \NorthSky \A5 Engineering Work \Working \134000090__ — Segale_OH South of 200th\ NEW_NSE Design 04262011.dwg
Apr 29, 2011
STRINGING SAG TABLE (P14 -P17)
Stringing Sag Table Using initial Sag
Ruling Span: 125.0 Feet
Conductor SPARROW
# 2 AWG 6/ 1 Stranding ACSR
NESC Medium Load Zone
Max Tension = 840 Lb
Design: 840. Lb @ 15. Deg F, .25 In Ice, 4.00 Psf Wind, Initial
H Tens 542. 513. 484. 455. 426. 397. 368. 340. 312. 285. 260.
(LBS)
Temp F> 40. 45. 50. 55. 60. 65. 70. 75. 80. 85. 90.
Sag Feet Feet Feet Feet Feet Feet Feet Feet Feet Feet Feet
Span
90.0 .17 .18 .19 .20 .22 .23 .25 .27 .30 .32 .35
100.0 .21 .22 .23 .25 .27 .29 .31 .33 .36 .40 .44
110.0 .25 .27 .28 .30 .32 .35 .37 .40 .44 .48 .53
120.0 .30 .32 .34 .36 .38 .41 .44 .48 .52 .57 .63
130.0 .35 .37 .40 .42 .45 .48 .52 .57 .62 .67 .74
140.0 .41 .43 .46 .49 .52 .56 .61 .66 .71 .78 .86
150.0 .47 .50 .53 .56 .60 .64 .69 .75 .82 .90 .98
160.0 .54 .57 .60 .64 .68 .73 .79 .86 .93 1.02 1.12
STRINGING SAG TABLE (P17 -P18)
Stringing Sag Table Using Initial Sag
Ruling Span: 300.0 Feet
Conductor SPARROW
# 2 AWG 6/ 1 Stranding ACSR
NESC Medium Load Zone
Max Tension = 840 Lb
Design: 840. Lb @ 15. Deg F, .25 In Ice, 4.00 Psf Wind, initial
H Tens 185. 180. 176. 172. 168. 165. 161. 158. 155. 152. 149.
(LBS)
Temp F> 40. 45. 50. 55. 60. 65. 70. 75. 80. 85. 90.
Sag Feet Feet Feet Feet Feet Feet Feet Feet Feet Feet Feet
Span
260.0 4.17 4.27 4.37 4.48 4.58 4.68 4.77 4.87 4.97 5.06 5.15
270.0 4.49 4.61 4.72 4.83 4.94 5.04 5.15 5.25 5.35 5.46 5.56
280.0 4.83 4.95 5.07 5.19 5.31 5.42 5.54 5.65 5.76 5.87 5.97
290.0 5.18 5.31 5.44 5.57 5.69 5.82 5.94 6.06 6.18 6.29 6.41
300.0 5.55 5.69 5.82 5.96 6.09 6.23 6.36 6.48 6.61 6.74 6.86
310.0 5.92 6.07 6.22 6.36 6.51 6.65 6.79 6.92 7.06 7.19 7.32
320.0 6.31 6.47 6.63 6.78 6.93 7.08 7.23 7.38 7.52 7.66 7.81
330.0 6.71 6.88 7.05 7.21 7.37 7.53 7.69 7.85 8.00 8.15 8.30
340.0 7.13 7.31 7.48 7.66 7.83 8.00 8.17 8.33 8.49 8.65 8.81
STRINGING SAG TABLE (P18 -P21)
Stringing Sag Table Using Initial Sag
Ruling Span: 300.0 Feet
Conductor SPARROW
# 2 AWG 6/ 1 Stranding ACSR
NESC Medium Load Zone
Max Tension = 840 Lb
Design: 840. Lb @ 15. Deg F, .25 In Ice, 4.00 Psf Wind, Initial
H Tens 185. 180. 176. 172. 168. 165. 161. 158 155. 152. 149.
(LBS)
Temp F> 40. 45. 50. 55. 60. 65. 70. 75. 80. 85. 90.
Sag Feet Feet Feet Feet Feet Feet Feet Feet Feet Feet Feet
Span
260.0 4.17 4.27 4.37 4.48 4.58 4.68 4.77 4.87 4.97 5.06 5.15
270.0 4.49 4.61 4.72 4.83 4.94 5.04 5.15 5.25 5.35 5.46 5.56
280.0 4.83 4.95 5.07 5.19 5.31 5.42 5.54 5.65 5.76 5.87 5.97
290.0 5.18 5.31 5.44 5.57 5.69 5.82 5.94 6.06 6.18 6.29 6.41
300.0 5.55, 5.69 5.82 5.96 6.09 6.23 6.36 6.48 6.61 6.74 6.86
310.0 5.92 6.07 6.22 6.36 6.51 6.65 6.79 6.92 7.06 7.19 7.32
320.0 6.31 6.47 6.63 6.78 6.93 7.08 7.23 7.38 7.52 7.66 7.81
330.0 6.71 6.88 7.05 7.21 7.37 7.53 7.69 7.85 8.00 8.15 8.30
340.0 7.13 7.31 7.48 7.66 7.83 8.00 8.17 8.33 8.49 8.65 8.81
TECHNICAL TRANSFORMER SCHEDULE
Site
Manufacturing
Serial Number
kVA
Phase
Type
Coding /
9
Class
HZ
30 Primary
'
Voltage
30 Secondary
''
Voltage
Windings
Fusin
Transformer
High Voltage
Feed Tiru
Bushings
Internal High
Voltage Switch
%
Impedance
Tap Changer
High Voltage
BIL kV
Low Voltage
BIL kV
Degree "C"
Rise
PCB
Remarks
VO4
1/0 CU MV105 -EPR
75
300
30
Padmount
(Dead - Front)
Oil 1 OA
60
12470
480Y/277V
,61,-Y
Internal
Bayonet
No
Yes
Min 2.10%
-
5.0% Max
Yes - In the
Primary
Compartment
95
30 '
65
Less than
1 PPM
30 Tangent Line Pole (Less than 3 °)
30 Primary Termination
Install 18" Switchboard - SW07 (To "VO4 ")
V05
P21
60
300
30
Padmount
(Dead- Front)
Oil 1 OA
60
12470
480Y/277V
p Y
Internal
Bayonet
No
Yes
Min 2.10%
-
5.0% Max
Yes - In the
Primary
Compartment
95
30
65
Less than
1 PPM
VAULT AND APPARATUS SCHEDULE
Site
Vault Size
Vault Cover Size
Type & Size of
Apparatus
Additional Material
Needed
Comments
VO4
-
5'- 6` "X4' -8 "x6"
Transformer Pad with
44'5f20" Access Hole
300kVA 30 PM Xfmr
12.47kV - 480Y/277
(3) 200A 15kV Rated
Load Break Elbow
from
V05
-
5'- 6 " "X4' -8 "x6"
Transformer Pad with
44 "x20" Access Hole
300kVA 30 PM Xfmr
12.47kV - 480Y/277
(3) 200A 15kV Rated
Load Break Elbow
VO4
MEDIUM VOLTAGE CONDUIT AND CABLE SCHEDULE
Location
CONDUIT
PRIMARY CABLE (15kV Rated)
Remarks
Size
(in)
Qty
Typ
Length
_ (.0)
Cable Size and Type
Length
(ft)
Cable Numbers
from
to
A
B
C
P20
VO4
4
1
Sch40 PVC
20
1/0 CU MV105 -EPR
75
SP013
SP014
SP015
30 Full Tension Double DE
3/8" Primary Down Guys (L =15')
P21
V05
4
1
Sch4O PVC
20
110 CU MV105 -EPR
75
SP016
SP017
SPO18
-
NOTE:
THE GROUND CONDUCTOR SHALL BE 600V RATED CABLE, COPPER, CLASS B STRANDED (COMPACTED), WITH POLYETHYLENE COMPOUND
OUTER JACKET (THHW) IN THE SAME CONDUIT AS THE PRIMARY CABLE.
POLE SCHEDULE
Site
Pole
Framing
Remarks
Height
Class
Year
Type
P14
45
3
-
Wood
30 Full Tension DE
3/8" Primary Down Guy (L =15)
See Dead -end Pole
Detail
P17
60
3
-
Wood
30 Full Tension Double DE
3/8" Primary Down Guys (L =15')
See Double- Double
Dead -end Pole
Detail
P18
60
3
-
Wood
30 Full Tension Double DE
3/8" Primary Down Guys (L =15')
See Double - Double
Dead -end Pole
Detail
P19
60
3
-
Wood
30 Tangent Line Pole (Less than 3 °)
See Tangent Pole
Detail
P20
60
3
-
Wood
30 Tangent Line Pole (Less than 3 °)
30 Primary Termination
Install 18" Switchboard - SW07 (To "VO4 ")
See Tangent Pole &
Termination Details
P21
60
3
-
Wood
30 Full Tension DE
3/8" Primary Down Guys (L =15')
30 Primary Termination
Install 18" Switchboard - SWO8 (To "V05 ")
See Dead -End Pole
& Termination Detail
NOTE:
FOR DETAILED FRAMING INSTRUCTIONS SEE SPECIFIC CONSTRUCTION NOTES ON RELATED WORKZONES
OVERHEAD WIRE INSTALLATION SCHEDULE
Span
Wire Size
Type
Number
of Phases
Footage
(ft)
Footage
(ft) Actual
Remarks
P14 to P17
(3) - #2
ACSR
30
125
Primary
(1) - #2
ACSR
Ground
P17 to P18
(3) -#2
ACSR
30
300
Primary
(1) - #2
ACSR
Ground
P18 to P21
(3) - #2
ACSR
30
900
Primary
(1) - #2
ACSR
Ground
REVIEWED FOR
COMPLIANCE WITH
NFPA70 -NEC
MAY 12 2011
City of Tukwila
BUILDING DIVISION
RECEIVED
MAY 042011
PERMIT CENTER
LtlO3'L1
A t''� UANTA SERVICES COMPANY
2224 104th Avenue East
Suite 1
Edgewood, WA 98372
Office (253) 952 -2128
Fax (253) 952 -2140
13400009037
NSC Job Number:
Clint Thayer
Engineer.
Clint Thayer
Drafter.
Barry Eronson
Checked:
Wayne Hagan
Approved:
A.
�w4
,p 3023?
EXPIRES 11/19/ O/I
Revisions
No. Date Description
Segale Properties
Phase 11
Customer Owned Temporary
OH & UG Medium Voltage
12.5kV 30 Line Extension
From South 200th Street,
South to just North of South
204th Street
Schedules
Technical
Stringing and Sag
Sheet 6 of 6