HomeMy WebLinkAboutPermit M11-024 - WESTFIELD SOUTHCENTER MALL - THINGS REMEMBEREDTHINGS REMEMBERED
1011 S0LJ'THCEN'1'ER MALL
M11-024
Parcel No.:
Address:
City ATukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Inspection Request Line: 206- 431 -2451
Web site: http: //www.ci.tukwila.wa.us
MECHANICAL PERMIT
9202470010
1011 SOUTHCENTER MALL TUKW
Project Name: THINGS REMEMBERED
Permit Number: M11 -024
Issue Date: 03/23/2011
Permit Expires On: 09/19/2011
Owner:
Name: WESTFIELD PROPERTY TAX DEPT
Address: PO BOX 130940 , CARLSBAD CA 92013
Contact Person:
Name:
Address:
Email:
KRAIG ROLLINS Phone: 314 - 721 -1340
1155 OLIVETTE EXECUTIVE PY, SUITE 100 , ST LOUIS MO 63132
ROLLINS @EPOCHDESIGNGROUP.NET
Contractor:
Name: WASHINGTON HEATING & A/C INC
Address: PO BOX 3427 , SEATTLE WA 98114
Contractor License No: WASHIHA012LQ
Phone: 206 - 860 -3832
Expiration Date: 06/16/2012
DESCRIPTION OF WORK:
INSTALL NEW SPLIT SYSTEM, AIR HANDLER AND CONDENSOR ON ROOF. INSTALLATION OF
NEW DUCT WORK.
Value of Mechanical: $9,500.00
Type of Fire Protection: UNKNOWN
Electrical Service Provided by: PUGET SOUND ENERGY
Permit Center Authorized Signature:
I hereby certify that I have read and
governing this work will be complie
The granting of this permit does not p
construction or the performance of work
back of this permit.
xami
with,
s
Signature:
Fees Collected: $306.06
International Mechanical Code Edition: 2009
Date: VII
ed this permit and know the same to be true and correct. All provisions of law and ordinances
hether specified herein or not.
to give authority to violate or cancel the provisions of any other state or local laws regulating
• am authorized to sign and obtain this mechanical permit and agree to the conditions on the
Date:
Print Name: M D OIJ C
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: IMC -4/10
M11-024 Printed: 03 -23 -2011
• •
PERMIT CONDITIONS
Permit No. M11 -024
1: ** *BUILDING DEPARTMENT CONDITIONS * **
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
4: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
5: Ventilation is required for all new rooms and spaces of new or existing buildings and shall be in conformance with the
International Building Code and the Washington State Ventilation and Indoor Air Quality Code.
6: Water heaters shall be anchored or strapped to resist horizontal displacement due to earthquake motion. Strapping shall
be at points within the upper one -third and lower one -third of the water heater's vertical dimension. A minimum
distance of 4- inches shall be maintained above the controls with the strapping.
7: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the City of Tukwila
Building Department (206- 431- 3670).
8: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431 - 3670).
9: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or art approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
doc: IMC -4/10
M11 -024 Printed: 03 -23 -2011
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila. WA 98188
htto://www.citukwila.wa.us
Building Permit No
Mechanical Permit No.
03S-
Plumbing/Gas Permit No. VG IA-- 0 36
Public Works Permit No.
Project No.
(For ofiee use mtlri
•
Applications and plans must be complete in order to be accepted for plan review_
Applications will not be accepted through the mail or by fax.
"Please Print*
ISITE LOCATION
Site Address: 1011 Southcenter Mall Tukwila WA 98188
Tenant Name: Things Remembered
Property Owners Nana': Westfield Corp (Southcenter Mail)
Mailing Address: 11601 Wilshire Blvd. 11th Floor
oo b 1
King Co Assessor's Tax No.: ��-
Suite Number: 428 Floor 1
New Tenant: ..._Yes la. No
Los Angeles, CA
c;tt
CONTACT PERSON -- who do we contact when your permit is ready to be issued
90025
Slat- /qt
Name: Kraig Rollins
Mailing Address: 1155 Olivette Executive Pkwy, Suite 100
Day 'Telephone: (314) 721 -1340
St.Louis, MO
63132
ti -Mail Address: rollins@epochdesigngroup.net
City tit;ll�`
Fax Number. (314) 721 -0344
GENERAL. CONTRACTOR INFORMATION -
(Contractor Information tor Mechanical (pg 4) for Plumbing and Gas Piping (pg $))
Company Name: TBD
Mailing Address:
Contact Person: TBD
E -Mail Address:
Contractor Registration Number
City Sl t,
Day Telephone:
Fax Number.
Expiration Date:
ARCHITECT OF RECORD - AU plans must be stamped by Architect of Record
C'ontpany Name: Epoch Design Group
Madill!! Address: 1155 Olivette Executive Pkwy, Suite 100
Contact Persoa: Kraig Rollins
F -Mail Address: rollins@epochdesigngroup.net
St. Louis, MO
city . sulk:
Day 'Telephone: (314) 721 -1340
1-ax Number. (314) 721 -0344
63132
>5D
ENGINEER OF RECORD - All plans must be stamped by Engineer of Record
Company Name: Randall A. Nelson, PE_
Mailing Address: 14817 West 95th Street
Contact Person: Same
E -Mail Address:
H >.pp] ;.;n um. F, u11 „- Arrh•.:n.nr• ( h; 1 mu. 1A dua,nnn .7.2010 - Prima .yZdran.w du'
Acwcd 7.2a D.
bit
Lenexa, KS
66215
C Ay star
Day Telephone: (913) 322 -5150
Fax Number:
i'JCC 1 o1.6
• •
BUILDING PERMih INFORMATION - 206-431-3670
Valuation of Project (contractor's bid price): g 66,200.00 Existing Building Valuation: S
Scope of Work (please provide derailed information): Tenant space improvement for retail storefront, full interior remodel;
install ducting to new split system; install new condensing unit on roof update sprinkler system layout; connect elec. iO4p
existing, but relocated panelboard, and install electrical and lighting, including low voltage connections to emergency
lighting and new audio system; relocate plumbing.
Will there he new rack storage? fa Yes
❑.. No If yes, a separate permit and plan submittal will he required.
Provide All Building Areas in Square Footage Below
PLANNING DIVISION:
Single fancily lxsilding footprint (area of the foundation of all structures. plus any decks over 18 inches and overhangs greater than I s inches)
'For an Accessory dwelling. provide the following:
Lot Asia Isq fil: Floor area of principal dwelling: Floor area ofaccessu,n dwelling:__
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard_ Compact: Handicap:
Will there be a change in use'! ❑..... -. Yes ..... No If "yes -, explain:
FIRE PROTECTION /HAZARDOUS MATERIIALS:
® Sprinklers M....... Automatic Fire Alarm ❑ Ntme ❑ Other t sped lyi
Will ,here be siorage or use of flanituable, combustible or hazardous materials in the building? ❑ Yes m No
11 -yes . amid! I s1 4rnalerials and sialage llarafianc an a xeparaft 8-1)2- x 11- paper 'whaling gitanfifies and t 1au'rial Solely Data SYIiY'1.,..
SEPTIC SYSTEM
❑ .......On -site Septic System -- Fur on -site septic system, provide 2 cxtpie. of a current septic design approved by King County Health
Department.
+1 .1prl I:,nnno,.x u:... \111d1:.a:•11, a a:11 me _0111 .,pj,1PaH(uaa'A.?,1141 - P0,11111 Acipiwem.n.l.�w
P.a. r.d: 7.21110
55
Page 2 of A
Lx istinn
Interior Remodel
Addition to
Existing,
Structure
New
Type of t
Construction per
IBC
Type of
Occupancy per
IBC
t" Floor
1,253
1,253
118
M
2'` Floor
3Tfoor
Floors thru
Basement
Accessory Structure*
Attached Garage
Detached Garage
Attached Carport
Dotachod Carport
1
C'evcred Deck
Uncovered Deck
PLANNING DIVISION:
Single fancily lxsilding footprint (area of the foundation of all structures. plus any decks over 18 inches and overhangs greater than I s inches)
'For an Accessory dwelling. provide the following:
Lot Asia Isq fil: Floor area of principal dwelling: Floor area ofaccessu,n dwelling:__
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard_ Compact: Handicap:
Will there be a change in use'! ❑..... -. Yes ..... No If "yes -, explain:
FIRE PROTECTION /HAZARDOUS MATERIIALS:
® Sprinklers M....... Automatic Fire Alarm ❑ Ntme ❑ Other t sped lyi
Will ,here be siorage or use of flanituable, combustible or hazardous materials in the building? ❑ Yes m No
11 -yes . amid! I s1 4rnalerials and sialage llarafianc an a xeparaft 8-1)2- x 11- paper 'whaling gitanfifies and t 1au'rial Solely Data SYIiY'1.,..
SEPTIC SYSTEM
❑ .......On -site Septic System -- Fur on -site septic system, provide 2 cxtpie. of a current septic design approved by King County Health
Department.
+1 .1prl I:,nnno,.x u:... \111d1:.a:•11, a a:11 me _0111 .,pj,1PaH(uaa'A.?,1141 - P0,11111 Acipiwem.n.l.�w
P.a. r.d: 7.21110
55
Page 2 of A
NI I;CH A N ICA 1. PERMIT INFORMATION - 206431 -3670
MECHANICAL. CONTRACTOR INFORMATION
Company Name: TBD
Mailing Address:
city
Day Telephone:
Fax Number.
('ontact Person:
E -Mail Address:
Contractor Registration Number: Expiration Date:
Sldt:
!qi
Valuation of Mechanical work (contractor's bid pricer_ S 9.500
Scope of Work (please provide detailed information,: Install new split system, air handler in space and condensor on roof:
installation of new duct work
L se: Residential: New ._.. ❑
C't mmerctal: New ....0
Replacement .. --
Replacement ....
Fuel Type: Electric.....1 Cias....® Other:
Indicate type of mechanical work being installed and the quantity below:
Unit Type:
Qty
Unit Type:
Qty
Unit Type:
Fire tamper
Qty
Boiler Compressor:
0 -3 11P/100.000 rill;
Qty- _
l
Fumacl <100K $TUl
Air Handling Unit >10.000
CFM
Fum. c > 1001: till
Evaporator Cooler
t)ifTuser
6
3.15 11P/500.000 RTI:
Floor Fumaix
Ventilation Fan Connoctcd
to Suede Duct
1
Thermostat
1
15- 3011P'1.000,000 RTit
Suspended/Wa11:'i to or
Mounted Heater
Appliance Vent
Ventilation System
llood and Duet
Wood /Gas Stove
30 -50 HP11.750.000 BTU
Emergency
Generator
50- Hr'/ 1,75(3.000 BTU
Repair or Addition to
1 ratlRefri}tiCcx+ling.
System
Incinerator - Domestic
Other Mechanical
Equipment
1
Air i landling Unit
<10.000 CFM
Incinerator - Cuuuu/Ind
n!. Appl .mone'r.,nnr )*; true, :o{ r1 Atgdumaa+:7 -: O IU - tor ma Applu-surz.A*:
Lori
rwe.
et
Pag.: •t of fr
• •
PTUNIRiNG AND GAS PIPING: PERMIT INFORMATION- 206 -431 -3670
PLUMiBING AND (.AS PIPING CONTRACTOR INFORMATION
Company Name: TBD
Mailing Address:
city stale
Contact Person: Day telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date:
'I,.
Valuation of Plumbing work (contractor's bid price): s 8.900
Valuation of ( ias Pipinn work (contractor's bid price): S
Scope: of Work (please provide detailed information): Relocate existing plumbing lines to accomodate new location
of lavatory and water closet.
Building Use (pox Int -1 Budding Code): 11. 12)
Occupancy (per lite1 Building Code):
utility Purveyor: Water:
Sewer:
Indicate type of plumbing fixtures and/or gas piping outlets lain" installed and the quantity below:
Fixture Type:
Qty ,
Fixture Type:
Qty
Fixture Type:
Qty
Fixture Type:
Qty
Bathtub or combination
hath,sto wer
Bidet
Clothes washer. dornestic
Dental unit. cuspidor
Dishwasher. domestic-
e1 ith independent drain
:
Drinking fountain or
at cooler tper head)
Food -waste grinder.
commercial
Floor Drain
Slower. single hetid imp
lavatory
1
Wash fountain
Receptor, indirect waste
Sinks
Urinals
Water Closet
1
Building sewer and each
trailer park server
Rain water system per
drain (inside building)
Water heater andlor vent
Industrial waste treatment
interceptor, including trap
and vent- except for kitchen
Each grease trap
(connected to not more
than 4 fixtures - <750
gallon capacity)
Medical as piping
system seivine 1 -5
inlets /outlets for a
specific Las
Each lawn sprinkler
system on any one rotor
including backllow
protection devices
1 ,4 ease knew tars
Grease interceptor for
commercial kitchen ( >750
gallon capacity)
Repair or alteration of
water piping and/or water
treatment equipment
1
Repair or alteration of
drainage or vent piping
Each additional medical
gas inlets /outlets greater
than 5
Backflow protective
device other than
a1mo phenc -type vacuum
breakers 2 inch (51 mm)
diameter or smaller
Backflow protective device
outer than atntospt a-ic -type
vacuum breakers over 2
inch (51 mm) diameter
Atnxnpiuric -type vacuum
breakers not included in
lawn sprinkler backflow
protection; (1 -5)
i
Ainxnpheric -type
v'acuurtt breakers not
included in lawn
sprinkler hackllenv
protections over 5
Gas piping outlets
11_,0•11com•In AIV+tr. tam• 1'. 1 um Y +111 Arrlicanan <,7.21114, rcrrna,lrgs'licasimue
11,41,11 '.`4711
1.1.
Page - •t t,
• •
PERMIT APPLICATION NOTES — Applicable to MI permits in this application
Value of Construction - In all cases, a value of construction amount should be entered by the applicant. This figure will he re t iewed and k ubj ect
w possible re>, itii.m by it:e Permit Center to cxmapty with cattail fit; scttcxdukcs.
Expiration of Plan Review -Applications litr which no permit is issued within 1710 iktys futlowino the date of application shalt expire by tin Mallon.
Building and Mechanical Permit
11tc Building Official may grant one or more: extensions of time for additional periods not exceeding 90 days each. The extents inn shall be
requested in writing and justifiable cause denumstrated. Section 105.3.2 international Building Code (current edition).
Plumbino Peanat
The Building Official may rodent one extension of bone for an additional period net cxcaxding 1440 days. The extension shall be rtgttesied
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing C'odc lcurrent edition).
I HEREBY CERTIFY T AT 1 HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE. SAME TO RE. TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR TIIIS PERMIT.
BEHA INC OWNER OR AUTHORIZED AGENT:
Signature: f� , . l ' L ,` ' - Date: 02/10/2008
Print Name: Kraig Rollins Day Telephone: (314)721 -0344 x118
Mailing Address: 1155 Olivette Executive Pkwy St.Louis MO 63132
- - - Crly St ax' Lip
IDate Application Accepted:
Date Application Expires::
11 Ardkuumn twoo- 1ppD.aSUm +{ )In a.mc 21(0.i4y.6oa1 nmn•7- 2(1111 . Ppnm Algdsefln¢, due
atc:ia3• 7-2,.1
Sta1T I nniai,_
< i
Pase 1+ of h
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone : 206-431-3670
Fax: 206 - 431 -3665
Web site: http. //www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 9202470010 Permit Number: M11 -024
Address: 1011 SOUTHCENTER MALL TUKW Status: APPROVED
Suite No: Applied Date: 02/11/2011
Applicant: THINGS REMEMBERED Issue Date:
Receipt No.: R11 -00568
Initials:
User ID:
Payee:
JEM
1165
Payment Amount: $61.21
Payment Date: 03/23/2011 04:11 PM
Balance: $0.00
MONTHEA LONG, WASHINGTON HEATING & AIR
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 031364
ACCOUNT ITEM LIST:
Description
61.21
Account Code Current Pmts
MECHANICAL - NONRES
000.322.102.00.00 61.21
Total: $61.21
doc: Receiot -06 Printed: 03 -23 -2011
• •
City of Tukwila
r�Z Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 9202470010 Permit Number: M11 -024
Address: 1011 SOUTHCENTER MALL TUKW Status: PENDING
Suite No: Applied Date: 02/11/2011
Applicant: THINGS REMEMBERED Issue Date:
Receipt No.: R11 -00275 Payment Amount: $183.64
Initials: WER Payment Date: 02/11/2011 02:19 PM
User ID: 1655 Balance: $61.21
Payee: EPOCH DESIGN GROUP
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 13011 183.64
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
MECHANICAL - NONRES
000.322.102.00.00 183.64
Total: $183.64
doc: Receiot -06 Printed: 02 -11 -2011
• 1
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http://www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 9202470010 Permit Number: M11 -024
Address: 1011 SOUTHCENTER MALL TUKW Status: PENDING
Suite No: Applied Date: 02/11/2011
Applicant: THINGS REMEMBERED Issue Date:
Receipt No.: R11 -00274
Payment Amount: $61.21
Initials: WER Payment Date: 02/11/2011 02:17 PM
User ID: 1655 Balance: $244.85
Payee: EPOCH DESIGN GROUP
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 10311 61.21
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
PLAN CHECK - NONRES
000.345.830 61.21
Total: $61.21
doc: Receiot -06 Printed: 02 -11 -2011
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO.
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION &(-1.
6300 Southcenter Blvd., #100, Tukwila. WA 98188 „ (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
p
A„ a )\[\ b
Type f Inspectioon: C
Address:
ALL
Date Called:
Special Instructions:
/ ii- 0-- /1__/11
Date Wanted:
`a.m.
—4-- I' p.m.
Requester:
Phone No
7,e) (49
— 3 5‘. -57-2,y
Approved per applicable codes. fl Corrections required prior to approval.
COMMENTS:
P
PT,? k T" (/3 0 � r' O
it
Inspef`r:
A„ a )\[\ b
Date: s _ 4 — `(
u �7
❑ REINSPECTION FEE REQUIRED. Pridr to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
:; - "
INSPECTION RECORD
Retain a copy with permit
INSPECT ON NO. PERMIT NO.,
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
Mr► -0z�
FILM ; 4
ki-Aeit4u
of Inspection:
c, /J Me •
Address: 1
1 0 ( l Sc. A4
Date Called:
S M d6� ,Sf i ✓�/� 0 c.�}� `T�
Special Instructions:
-"-1 ifeilh
Date Wanted
�_ a.m`'
_ p.m.
Requester:
`
Pho e N
.17 —9oCZ
ElApproved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Li.
AJ t„aDik> �4
S M d6� ,Sf i ✓�/� 0 c.�}� `T�
A.,r /I 4-v ((,`
...---. e 4
‘
Inspector:
Dates-- 3
..•• y
n REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
-.;
INSPECTION 0.
INSPECTION RECORD
Retain a copy with permit
PERMIT NO.
CIT OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 z (206) 431-3670
Permit Inspection Request Line (206) 431-2451
PM, ,Typepf*Inspection:
ro
i A62—C kr-}-ke 4,6e-feli
t.g /1/4)
Address:
ID it .S. MALL
Date Called:
Special Instructions:
Date Wanted:,
.5 — '2.--
If
a • .
_.-%
Requester:
Phone No:
552
EApproved per applicable codes.
orrections required prior to approval. •
COMMENTS:
oa (-; r MLM
• i- ),A1 e.)3
Insp c)r.L_
Jp
1-1 REINSPECTION FEE REQUIRED. Prio to next inspection, fee must be
I paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Date:
• --1■".
INSP CTION NO.
INSPECTION RECORD
Retain a copy with permit
it...40z.q
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
-:—/
• INSPECTION RECORD
•
INSPECTION NO.
Retain a copy with permit
PERMIT N
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
Project:
77? / /e. I ?C'n'trwoanz
Type of Inspection:
TV_l'7 - 2. /KU/ •
Address:
/0/1 044/i
Date Called:
Special Instructions:
Date Wanted:
4-/- R -//
a.m.
eft
Requester:
Phone No:
,2,6 — 39
-5527
1( Approved per applicable codes. El Corrections required prior to approval.
COMMENTS:
•
specto
Date:
SPECTION FEE REJIUIRED. Prior to next inspection. fee must be
at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION 12' -
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
INSPECTION RECORD
Retain a copy with permit
'PERMIT N0.
Pro
j -./v 6.s (fieAehv
yp of Inspection:
(<0�, 4 ti- . �.. \
A.e
Address:
i0rl ( 5
Alt --..„—
Date Called:
Special Insttructions:
11 �l ✓.l
f {CCJJ
3 /A
-yl,-'
—, '11 �1
r
Date Wanted:3
24
_ 1 1
Requester:
Phonnee,,/No: `�
S.-5 2(rye'
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
I ns pecfor:
Date/ ti
REINSPECTION FEE REQUIRED. (P.ribr to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
•
2006 Washington State Nonresidential Energy Code Compliance Form
Project Summary
PRJ -SUM
2006 Washington State Nonresidential Energy Code Compliance Forms
Revised July 2007
Project Info
Project Address
THINGS REMEMBERED
Date 1/27 /2011
WESTFIELD SODTHCENTER,
SPACE #
428
For Building Department Use
TUKWILA, WA
Applicant Name:
Applicant Address:
Applicant Phone:
CCODE FOR
E COMPLIANCE
Anonym
MAR 212iiu
City of Tukwila
BUILDINS fll nq nro
M vz1-1
- r-441 COP -81‘,41,.
Permit No,
RECEIVED
FEB 112011
WANT CENTER
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical Summary
MECH -SUM
2006 Washington State Nonresidential Energy Code Compliance Forms
Revised July 2007
Project Info
Project Address
THINGS REMEMBERED
Model No.1
Date 1/27/2011
Total CFM
WESTFIELD SOUTHCENTER,
SPACE # 428
For Building Dept. Use
Location
TUKWILA, WA
TRANE
Applicant Name:
47000
1500
Applicant Address:
13.25 SEE:
NA
Applicant Phone:
Project Description
Briefly describe mechanical
system type and features.
Includes Plans
Existing split sytem to be re -used.
Drawings must contain notes requireing compliance with commissioning requirements - Section 1416
Compliance Option
Q Simple System 0 Complex System 0 Systems Analysis
(See Decision Flowchart (over) for qualifications. Use separate MECH -SUM for simple & complex systems.)
Equipment Schedules
The following information is required to be incorporated with the mechanical equipment schedules on the
plans. For projects without plans, fill in the required information below.
Cooling Equipment Schedule
Equip.
ID
Brand Name'
Model No.1
Capacity2
Btu /h
Total CFM
OSA CFM
or Econo?
SEER
or EER
IPLV3
Location
CU -1
TRANE
4TTA03048A
47000
1500
OSA CFM
13.25 SEE:
NA
OUTDOORS
Heating Equipment Schedule
Equip.
ID
Brand Name'
Model No.1
Capacity2
Btu /h
Total CFM
OSA cfm
or Econo?
Input Btuh
Output Btuh
Efficiency's
ABU -1
TRANE
4TEC3P55B
51195
1500
OSA CFM
15 KW
15 KW
1.000
Fan Equipment Schedule
Equip.
ID
Brand Name'
Model No.1
CFM
SP'
HP /BHP
Flow Control5
Location of Service
EF -1
COOK
GC -140
100
0.50
NA
CV
RESTROOM
11f available. 2 As tested according to Table 14 -1A through 14 -1G. 3 If required. 4 COP, HSPF, Combustion Efficiency, or AFUE, as
applicable. 5 Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS).
2006 Washington State Nonresidential Energy Code Compliance Form
Mechanical. Surnmary (back) •
MECH -SUM
System Description
See Section 1421 for full description
of Simple System qualifications.
If Heating/Cooling
or Cooling Only:
4
Constant vol?
Split system?
J Air cooled? .i Packaged sys? <20,000 Btuh?
0 Economizer included?
a
If Heating Only:
<5000 cfm?
<70% 70 /° outside air?
Decision Flowchart
Use this flowchart to determine if project qualifies for Simple System Option. If not, either the
Complex System or Systems Analysis Options must be used.
Heating Only
Heating /Cooling
or Cooling Only
Reference
Section 1421
Yes —
Yes
Yet:
Air Cooled,
Constant Vol?
ingle
Package
Unit?
plit Syste
<= 84,000
Btu h?
<70% OSA
Yes*
Econo
ncluded?
•ol Ca
<20,000
Btuh?
Outd
or
Adjacent to
utdoo
Yes
Reference
Section 1423
Simple System
Allowed
(section 1420)
Yes
oI Ca
<54,000
Btuh?
otal Ca..
wo economize
<240,000 Btuh
or 10 %?
Yes
Use Complex
Systems
(section 1430)
Complex Systems
Refer to MECH -COMP Mechanical Complex Systems for assistance in determining which
Complex Systems requirements are applicable to this project.
2006 Washington State Nonresidential Energy Code Compliance Form
it g3:
ummarj
2006 Washington State Nonresidential Energy Code Compliance Forms
Revised July 2007
Project Info
Project Address Things Remembered - Westfield Southcenter
Date 1/27/2011
Tukwila, WA
For Building Department Use
Space No. 428
Applicant Name: Randall A. Nelson, P.E.
Applicant Address: 14817 West 95th Street, Lenexa, KS 66215
Applicant Phone: 913- 322 -5150
Project Description
Space No. 428
❑ plans Included
requirements.
❑ New Building ❑ Addition a Alteration
Refer to WSEC Section 1513 for controls and commissioning
Compliance Option .
O Prescriptive Q Lighting Power Allowance 0 Systems Analysis
(See Qualification Checklist (over). Indicate Prescriptive & LPA spaces clearly on plans.)
Alteration Exceptions
(check appropriate box - sec. 1132.3)
❑ No changes are being made to the lighting
❑ Less than 60% of the fixtures new, installed wattage not increased, & space use not changed.
Maximum Allowed Lighting Wattage
Location
(floor /room no.)
Occupancy Description
Allowed
Watts per ft2**
Area in ft2
Allowed x Area
Space No. 428
Retail
1.50
1253.0
1879.5
Space No. 428
C - Two lamp recessed adjustable spot
2
88.0
176.0
Space No. 428
D - Two lamp 8' strip fluorescent
1
61.0
61.0
" From Table 15 -1 (over) - document all exceptions on form LTG -LPA Total Allowed Watts
1879.5
Proposed Lighting Wattage
Location
(floor /room no.)
Fixture Description
Number of
Fixtures
Watts/
Fixture
Watts
Proposed
Space No. 428
B - Single lamp recessed adjustable spot
15
44.0
660.0
Space No. 428
C - Two lamp recessed adjustable spot
2
88.0
176.0
Space No. 428
D - Two lamp 8' strip fluorescent
1
61.0
61.0
Space No. 428
FC - Single lamp under cabinet 4' fluorescent
2
30.0
60.0
Space No. 428
H - Recessed LV puck light
3
20.0
60.0
Space No. 428
T - Track Fixture
42
45.0
1890.0
Additional 1.5w /af exempt for track lighting
-2
1253.0
- 1879.5
Total Proposed Watts may not exceed Total Allowed Watts for Interior Total Proposed Watts
1027 .5
Notes:
1. For proposed Fixture Description, indicate fixture type, lamp type (e.g. T -8), number of lamps in the fixture, and ballast type (if
included). For track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
2. For proposed Watts /Fixture, use manufacturer's listed maximum input wattage of the fixture (not simply the lamp wattage) and
other criteria as specified in Section 1530. For hard -wired ballasts only, the default table in the NREC Technical Reference Manual
may also be used. For track lighting, list the greater of actual luminaire wattage or length of track multiplied by 50, or as applicable,
the wattage of current limiting devices or of the transformer.
3. List all fixtures. For exempt lighting, note section and exception number, and leave Watts /Fixture blank.
2006 Washington State Nonresidential Energy Code Compliance Form
yLi `htin ` ,1Motor sand fTr .1.1 , orme`r PwermitsvP<Ians Chxecklist`; w- LT,G =_CHK
2006 Washington State Nonresidential Energy Code Compliance Forms Revised July 2007
Project Address Things Remembered - Westfield Southcenter
Date 1/27/2011
The following information is necessary to check a permit application for compliance with the lighting, motor, and transformer requirements
in the 2006 Washington State Nonresidential Ene gy Code.
Applicability
(yes, no, n.a.)
Code
Section
Component
Information Required
Location
on Plans
Building Department
Notes
LIGHTING CONTROLS (Section 1513)
yes
1513.1
Local control /access
Schedule with type, indicate locations
El. o
yes
1513.2
Area controls
Maximum limit per switch
E1.0
n.a.
1513.3
Daylight zone control
Schedule with type and features, indicate locations
n.a.
vertical glazing
Indicate vertical glazing on plans
n.a.
overhead glazing
Indicate overhead glazing on plans
yes
1513.4
Display /exhib /special
Indicate separate controls
El. o
1513.5
Exterior shut -off
Schedule with type and features, indicate location
n.a.
(a) timer w /backup
Indicate location
n.a.
(b) photocell.
Indicate location
1513.6
Inter. auto shut -off
Indicate location
n.a.
1513.6.1
(a) occup. sensors
Schedule with type and locations
n.a.
1513.6.2
(b) auto. switches
Schedule with type and features (back -up, override capability);
Indicate size of zone on plans
n.a.
1513.7
Commissioning
Indicate requirements for lighting controls commissioning
EXIT SIGNS (Section 1514)
yes I
1514 (Max.
watts 'Indicate
watts for each exit sign 1E1.0
I
LIGHTING POWER ALLOWANCE (Section 1530 -1532)
yes
1531
Interior Lighting
Summary Form
Completed and attached. Schedule with fixture types,
lamps, ballasts, watts per fixture
n.a.
1532
Exterior Lighting
Summary Form
Completed and attached. Schedule with fixture types,
lamps, ballasts, watts per fixture
MOTORS (Section 1511)
n.a. I
1511 IElec
motor efficiency IMECH
-MOT or Equipment Schedule with hp, rpm, efficiency I
TRANSFORMERS (Section 1540)
n.a. I
1540 (Transformers
(Indicate
size and efficiency
1
I
If "no" is circled for any question, provide explanation:
• Si
eetion copy
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: M11 -024 DATE: 02 -11 -11
PROJECT NAME: THINGS REMEMBERED
SITE ADDRESS: 1011 SOUTHCENTER MALL
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # After Permit Issued
DEPARTMENTS:
6u�ldirlg Division
�
Public Works ❑
A) JA_ )._,=1,(s41
Fire Prevention igg
Structural
Planning Division
❑ Permit Coordinator
DETERMINATION OF COMPLETENESS: (Tues., Thurs.) DUE DATE: 02-15-11
Complete Vi Incomplete n
Comments:
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
LETTER OF COMPLETENESS MAILED:
TUES /THURS ROUTING:
Please Route
Structural Review Required
No further Review Required
n
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS: DUE DATE: 03-15-11
Approved Approved with Conditions NI Not Approved (attach comments) n
Notation:
REVIEWER'S INITIALS: DATE:
. Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents /routing slip.doc
2 -28 -02
Contractors or Tradespeople P' ter Friendly Page
•
General /Specialty Contractor
A business registered as a construction contractor with L &I to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name WASHINGTON HEATING &
A/C INC
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent
Company
2068603832
13620 First Ave S
Seattle
WA
98168
King
Corporation
UBI No.
Status
License No.
License Type
Effective Date
Expiration
Date
Suspend Date
Specialty 1
Specialty 2
601962099
Active
WASHIHA012LQ
Construction Contractor
6/18/1999
6/16/2012
Heating /Vent /Air - Conditioning And Refrig
(Hvac /R)
Unused
Licenses
License
Name
Type
yp
Specialty 1
p y
Specialty 2
p y
Effective
Date
Expiration
Date
Status
WASHIHA023MH
WASHINGTON
HEATING & A/C
Construction
Contractor
Metal
Fabrication
Air
Conditioning
7/8/1998
7/6/1999
Archived
Business Owner Information
Name
Role
Effective Date
Expiration Date
TRAN, STEVEN C
President
01/01/1980
Bond Amount Received Date
LONG, MONTHEA R
Vice President
06/11/2008
06/16/2006
LONG, MAKARA
President
06/17/2008
06/17/2008
PECH, MAKARA
Secretary
01/01/1980
05/30/2008
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount Received Date
3
INS CO OF THE WEST
2186958
06/16/2006
Until Cancelled
06/16/2011
$6,000.0005/16/2006
2
RLI INS CO
SRS1016730
06/16/2002
Until Cancelled
06/16/2006
06/16/2007
$6,000.0005/22/2006
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
7
HARTFORD CAS
INS CO
52SBAUM6074
06/16/2007
06/16/2011
$2,000,000.00
05/14/2010
6
HARTFORD CAS
INS CO
52SBANK2319
06/16/2006
06/16/2007
$2,000,000.00
05/12/2006
5
HARTFORD
CASUALTY INS
CO
52SBANK2319
06/16/2003
06/16/2006
$2,000,000.0005
/13/2005
Summons /Complaint Information No unsatisfied complaints on file within prior 6 year period
Warrant Information No unsatisfied warrants on file within prior 6 year period
https://fortress.wa.gov/lni/bbip/Print.aspx
03/23/2011
'TENANT SUB - METER,
COORDINATE LOCATION AND
METER MODEL WITH LANDLORD
LEVEL 2
-3/4."
CEILING
LAV -1
1/2"
WC -1
LEVEL 2
CEILING.
FLOOR LINE
3"
3"
WC -1 1
1/2"
WATER RISER DIAGRAM
FD -1
2"
1
FURNISH AND INSTALL
TRAP PRIMER FOR
FLOOR DRAIN (TYP)
WASTE RISER DIAGRAM
EWH -1
FLOOR LINE
'D FROM STRUCTURE
PER LANDLORD REQUIREMENTS. FIELD INSTALL MIXING BOX AND CONNECT OUTDOOR AIR
DUCT TO LANDLORD PROVIDED OUTDOOR AIR MAIN DUCT, FIELD VERIFY EXACT LOCATION.
��
(3) FURNISH AND INSTALL GALVANIZED STEEL DUCTWORK, SIZES AS NOTED ON DRAWINGS.
��'° DUCTWORK SIZES ARE CLEAR INSIDE DIMENSIONS. REFER TO SPECIFICATIONS FOR
INSULATION REQUIREMENTS,
• SPRINKLER SYSTEM SHALL BE _MODIFIED AS REQUIRED TO SERVE THE NEW LAYOUT SHOWN
ON THE DRAWING. NOTIFY THE MALL MANAGER 72 HOURS BEFORE SPRINKLER SHUTDOWN
IS REQUIRED AND PAY ALL MALL CHARGES FOR SPRINKLER SHUTDOWN.
5 CONNECT TO LANDLORD'S EXISTING SPRINKLER LINE AND TO CONNECTIONS THAT EXIST IN
THE SPACE TO ACCOMMODATE THE NEW SPRINKLER LOCATIONS.
O CONCEALED SPRINKLER HEAD IN TOILET ROOM, AND PENDANT HEAD ABOVE TOILET ROOM.
O7 INSTALL NEW RESTROOM EXHAUST FAN, ROUTE 6 "0 ROUND DUCT TO LANDLORD PROVIDED
EXHAUST MAIN DUCT..
K INSTALL SENSOR AT 60 "AFF, SENSOR SHALL BE COMPATIBLE WITH THERMOSTAT.
KI ROUTE 3/4" COLD WATER LINE BACK TO COLD WATER MAIN IN SPACE, FIELD VERIFY
EXACT LOCATION.
10 ROUTE 4" SANITARY LINE BACK TO SANITARY MAIN IN SPACE, FIELD VERIFY EXACT
0 NEW CONDENSING UNIT ON ROOF, COORDINATE LOCATION AND INSTALLATION WITH
LANDLORD. ROUTE REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS, DO
NOT EXCEED MAXIMUM LINE LENGTH.
12 16X14 RETURN AIR DUCT, END OPEN WITH 1/2 "x1/2" WIRE MESH SCREEN.
2.
REVIEWED FOR
CODE COMPLIANCE
APPPMED
MAR 2 1 2011
City of Tukwila
13UILDING1TVIRInN
ALL OF THE MECHANICAL WORK IS NOT NECESSARILY SHOWN OR NOTED ON THESE
DRAWINGS. THE CONTRACTORS SHALL VISIT THE JOB SITE AND VERIFY ALL EXISTING
CONDITIONS RELATED TO THEIR WORK BEFORE BIDDING. NOTIFY THE OWNER OF ANY
DISCREPANCIES. THOSE ITEMS NOT SHOWN OR NOTED BUT WHICH ARE DEEMED
NECESSARY FOR REMOVAL OR RELOCATION BY OWNER'S REPRESENTATIVE SHALL BE PART
OF THIS CONTRACT,
THE SUBMISSION OF PROPOSALS SHALL BE CONSIDERED EVIDENCE THAT THE
CONTRACTORS HAVE VISITED THE SITE. NO EXTRA PAYMENTS. WILL BE ALLOWED THESE
CONTRACTORS CLAIMS FOR EXTRA WORK MADE NECESSARY BY THEIR FAILURE TO VISIT
THE SITE.
GUARANTEE ALL EQUIPMENT AND MATERIAL INSTALLED UNDER THIS CONTRACT TO BE FREE
FROM DEFECTS FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE AND
REPAIR OR REPLACE WITHOUT COST TO THE OWNER ANY EQUIPMENT WHICH IS DEFECTIVE,
OR IMPROPERLY INSTALLED. IN ADDITION, ASSUME FULL RESPONSIBILITY FOR ANY DAMAGE
TO THE BUILDING AND ITS CONTENTS OR OTHER EQUIPMENT CAUSED BY DEFECTS OR
IMPROPER INSTALLATION OF EQUIPMENT OR MATERIALS INSTALLED UNDER THIS PORTION OF
THE WORK.
4. ALL WORK SHALL BE COMPLETED AND INSTALLED ACCORDING TO STATE AND OR LOCAL
CODES, AND ALL LANDLORD CRITERIA.
PAY FOR ALL REQUIRED PERMITS AND INSPECTIONS AND PROVIDE A CERTIFICATE OF
INSPECTION.
REVIEW ALL LANDLORD REQUIREMENTS AND INSTALL ALL MATERIALS AND EQUIPMENT AS
DIRECTED BY THE LANDLORD'S REPRESENTATIVE AND AS REQUIRED BY THE LEASE
DOCUMENTS. VERIFY THE REQUIREMENTS BEFORE SUBMITTING A BID.
VERIFY THE SIZE, LOCATION AND CONDITION OF THE EXISTING DUCTWORK, EQUIPMENT AND
CONTROLS THAT ARE TO REMAIN. NOTIFY THE OWNER OF ANY DISCREPANCIES. REPLACE
EXISTING COMPONENTS IF INADEQUATE FOR THE NEW REQUIREMENTS OR INOPERABLE.
COORDINATE REPLACEMENT COMPONENT SPECIFICATIONS WITH THE LANDLORD'S FIELD
REPRESENTATIVE.
8. FIVE (5) COPIES OF ALL SHOP OR EQUIPMENT DRAWINGS SHALL BE SUBMITTED TO THE
OWNER. THESE DRAWINGS SHALL BE CLEARLY MARKED INDICATING WHICH ITEMS ARE TO
BE SUPPLIED AND SHALL STATE CAPACITIES, SIZES, REQUIRED INSPECTION LABELS AND
GENERAL DESCRIPTION OF ALL EQUIPMENT AND FIXTURES.
9. ALL AIR INTAKES AND EXHAUSTS NEED TO BE SEPARATED BY A MINIMUM OF 10' -0 ".
10. NO COMPONENTS MAY BE ABANDONED IN PLACE WITHOUT PERMISSION FROM THE OWNER.
ALL COMPONENTS THAT ARE NOT REUSED MUST BE REMOVED.
11. VERIFY ALL CLEARANCES AROUND NEW AND EXISTING EQUIPMENT.
12. ALL WORK SHALL BE COMPLETED ACCORDING TO STATE AND OR LOCAL CODES AND
TENANT CRITERIA HANDBOOK,
PLUMBING PLAN
SCALE: 1 /4 =
PLUMBING RISERS.
KEY NOTES
GENERAL NOTES
MECHANICAL SYMBOLS LEGEND
OS THERMOSTAT
-OM- FLEXIBLE DUCT
VOLUME DAMPER
FD '-- FIRE DAMPER
CEILING SUPPLY AIR DIFFUSER
CEILING RETURN AIR GRILLE
SIDEWALL AIR DIFFUSER OR GRILLE
NEW DUCTWORK
EXISTING DUCTWORK
— D — CONDENSATE DRAIN
— G — GAS PIPING
D PIPE TURNING DOWN
0 PIPE TURNING UP
--4-- BALL VALVE
0 CONNECTION OF NEW TO EXISTING
—jv CHECK VALVE
GAS COCK
•
—+y+— STRAINER
AFF ABOVE FINISHED FLOOR
AIR DEVICE # S - SUPPLY
RETURN
R -
CFM E - EXHAUST
FIRE PROTECTION SYMBOLS LEGEND
OE
EXISTING SPRINKLER HEAD
CHROME PENDANT SPRINKLER HEAD
O
UPRIGHT SPRINKLER HEAD
O
CONCEALED SPRINKLER HEAD
1
SIDEWALL SPRINKLER HEAD
PLUMBING SYMBOLS LEGEND
HOT V
SANITARY VENT
VTR
VENT THROUGH ROOF
PLUMBING TRAP
CO
CLEAN OUT
O
PRESSURE REGULATING VALVE(PRV) 50 PSI
— CA —
COMPRESSED AIR
FCO
FLOOR CLEAN OUT
SEPARATE PERMIT
REQUIRED FOR:.
D Mebhanlad
IfsElectrical
Plumbing
as Piping
City of Tukwila
F a,ral .r- ING DIVISION
NOTE:
EXISTING CONDITIONS WERE TAKEN FROM SITE VISITS AND MAY NOT REFLECT EXACT "AS- BUILT"
CONDITIONS. FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS.
CONTRACTOR SHALL CAREFULLY COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER
DISCIPLINES AND EXISTING CONDITIONS.
REVISIONS
No changes shall be made to the scope
Of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
ALL HVAC EQUIPMENT AND CONTROLS MUST BE LOCATED FOR PROPER
ACCESS FOR MAINTENANCE AND REPAIR, WHETHER INSTALLATION IS
EXISTING OR NEW. EXISTING EQUIPMENT AND CONTROLS SHALL BE
RELOCATED BY THIS CONTRACTOR IF REQUIRED.
FILE COPY
Parniit 1
Pan review �Is j errors and
Approval of documents does not authorize
the _violation of any adopted code or ordinance.
of approved Field Copy and conditions Is acknowledged:
RECEIVED
FEB 112011
PERMIT CENTER
20
LEGEND
19
MECHANICAL & SPRINKLER PLAN
SCALE: 1 /4" = 1' -0"
H
M O
PROJECT TEAM:
Architect Epoch Design Group, Inc
1 155 Olivette Exec. Pkwy.
Suite 100
St. Louts, MO 63132
TEL: 314.721.1340
FAX: 314.721.0344
M. E. P. & F.P.
Engineer:
Randall A. Nelson, P.E.
14817 West 95th Street
Lenexa, KS 66215
TEL 913.322.5150
FAX: 913.322.5155
COPYRIGHT DISCLAIMER:
THIS DOCUMENT IS THE PROPERTY OP EPOCH DESIGN GROUP,
COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION
FROM EPOCH DESIGN GROUP FOR USE OF THIS DOCUMENT IS
NOT TRANSFERABLE. THE RECIPIENT OP THIS DOCUMENT I5
HEREBY ADVISED THAT IT IS RELEASED FOR USE UNDER 5111
FOLLOWING TERMS AND CONDITIONS,
THE DOCUMENT I5 TO SE USED ONLY IN CONIUNCRON WITH
THIS PROTECT. REUSE OP ANY PORTION OF THE DOCUMENT M
ANY OTHER CIRCUMSTANCE CONSTITUTES COPYRIGHT
INPRINO!MENT. .
THE DOCUMENT IS FOR DESIGN INTENT AND INFORMATION ONLY,
AND DOES INIQCONSTITUTE AS•SURT CONDITIONS. THE
RECIPIENT ROANS TRF15111.10ATION TO VERIFY THE CONDITIONS
OF THE SUBJECT PROPERTY AND TO COMPLETELY COORDINATE
ALL DIMENSIONS, FABRICATION METHODS, RELATED AND
INTEGRATED SYSTEMS, ETC, WITH RESPECT TO ALL ASPECTS OP
THE WORK,
EPOCH DESIGN GROUP MAKES NO WARRANTY AS 70111E
SUITABILITY OF 711E DOCUMENT FOR TH! RECIPIENT'S INTENDED
U5!. THE RECIPIENT SPECIFICALLY AGREES TO WAIVE AND TO
INDEMNIFY AND DEPEND ANY AND ALL CAMS AGAINST EP001
. DESIGN GROUP, ITS CONSULTANTS, ANY OF ITS RELATED ENTRIES,
VENDORS, OR CONTRACTORS, POR ANY LOSS INCURRED ASA
' RESULT OF PROPER OR IMPROPER USE OF THIS DOCUMENT.
THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT
UPON COMPLETION OE TERMINATION OF WORK PERFORMER IN
_ w no CANTUNCION WITH THIS PROJECT.
PROJECT TITLE:
1-
W
No.O Revision Description Date
SHEET TITLE:
MECHANICAL
FLOOR PLAN
PROJECT NO.: SHEET NUMBER:
10313
DRAWN BY:
JCC
ISSUE DATE: M
01/26/11
1.0
SEE HEAT PUMP SERVICE VALVES
UNIT ON ROOF
MOUNTING DETAIL
SIGHT GLASS
FAN GUARD
CONDENSER COL
INSTALL UNIT ON
ROOF PER
LANDLORDS
REQUIREMENTS
CONDUIT
POWER
CONTROL
N
( .40001141.
���
`IJJIII�
®
CONDENSING
REFRIG.GA.
UNIT
ROOF
ROOF
"'
REFRIGERANT PIPING
Cu
FILTER
DRYER
►� RS
SEE PIPE
PENETRATION DETAIL
-ROOF
PENETRATION
PER LANDLORD
4.�
e ,
/�` `�
�``
6 "
ANGLE OR UNISTRUT
SEENOTE1.
��
6
RL
►
`N
■ • o;
111
J,
�l
\
\
_ i�'
Roof �
/
RECTANGULAR DUCT
THREADED
It
IT
AND
-
/-
c
.
CONN.
CO
`�
I
�,
„
r
•_
I
`
SIGHT GLASS WITH
MOISTURE INDICATOR
E _
FILTER-DRYER
REFRIGERANT LIQUID
LINE
SUCTION LINE
WITH INSULATION
ROOF CAP AND
CURB
^
J
�,�►
BOTTOM OF
STRUCTURE
LOADS MUST BE
ROD (TYP)
1,, MIN
IIIIIIMI
.illik 1
SHEET METAL
SCREWS SEE
NOTE 2. (TYP)
15 DEG
F
AHU
HUNG WITHIN 6" umismaii
60" (MAX)
OF PANEL POINTS
ANGLE OR UNISTRUT
RECTANGULAR DUCT
RECTANGULAR DUCT
SUPPORT RODS WITH
UL
PERPENDICULAR TO STRUCTURE PARALLEL TO STRUCTURE
BELL MOUTH
-
FITTING _ D +3
Ceiling VIBRATION ISOLATORS
NOTE:
COND. DRAIN. REF.
PLUMBING PLANS
Floor
ALL DUCTS USE THREADED
1. ADED ROD FOR AL D T LARGER THAN
L GE HAN 60 o WIDE.
2. SHEET METAL SCREWS MAY BE OMITTED IF HANGER STRAP IS CONTINUOUS AND
LOOPS UNDER ENTIRE DUCT.
3
0
Q
D
T SUPPORT
RECTANGULAR D UC SU DETAIL
7
SPLIT SYSTEM AIR HANDLER DETAIL
6
CONDENSING UNIT DETAIL
HIGH EFFICIENCY TAKEOFF NYLON BAND OVER
EXTERNALLY INSULATED INSULATION (TYPICAL)
PROVIDE FULL SIZE
CONNECTION
ROUND DUCT
SINK OR LAV.
FLOW
HARD ELBOW FOR
TRANSITION TO VERTICAL
INSULATED DUCT
EWH -1
j1
CONTROL
5 GPM
COLD WATER
PRE- INSULATED
FLEXIBLE DUCT AS
o
d
REQUIRED, INSTALL
4411
S TOP VALVE
DUAL
(DUAL
Almmili
FULLY STRETCHED,
PERMANENTLY SEALED
SUPPORTED TO
PREVENT KINKING
AND SHARP TURNS
PROVIDE FIRE RATED
SUPPLY DIFFUSERS
AND RETURN
GRILLES FOR FIRE
RATED CEILINGS.
CEILING DIFFUSER
WITH DAMPER AS
SCHEDULED
6111,
V
- SQUARE TO ROUND
TRANSITION
-
` _ OUTLET)
FULL SIZE OF
RETURN AIR
GRILLE
1/2 x W
AIR FLOW
-
_1_0
II
WORM GEAR
DRAWBAND
(TYPICAL)
VOLUME DAMPER AND DAMPER
LOCK WITH EXTENSION
FIN. FLOOR
11e
�'
SQUARE DUCT
3
O
a
-OFF
ROUND DUCT
-OFF
I 24" MIN
(
RETURN AIR
GRILLE
iiuullil lam'
45' TAKE - At 45' TAKE
SQUARE DUCT
s
S
BRA NC I-
DUCT TAKEOFFS &TRANSITIONS
NOTE: POINT OF USE WATER HEATER SHALL BE POSITIONED SO
AS NOT TO ENCROACH INTO ANY REQUIRED WHEELCHAIR ACCESS
CLEARANCES BENEATH THE LAVATORY AND SHALL BE SHEILDED
AGAINST HUMAN CONTACT
kt \ .......-
0 2,mm.
�J/
7
DIFFUSER DETAILS
10
RETURN GRIL LE BOOT DETAIL
9
POINT OF USE WATER HEATER
A. ALL
SPACING
PIPING
ACCEPTABLE
OF
B. PREPARE
THE
C. TWO
AND
D. PROVIDE
D
JURISDICTION
E. PROVIDE
REPRESENTATIVE,
F. HOLD
STOCK
G. SPRINKLER
PLATES.
PENDANT
AREAS
TEMPERATURE
DISPLAY
INSURANCE
RESPONSE
H. VISIT
PROVIDE
COMPLETE
AUTHORITIES.
SPRINKLER
AND
LANDLORD
J L
MODIFICATIONS
REPRESENTATIVE.
K. ALL
MALL'S
MARSHALL.
PIPING AND HEADS SHALL BE INSTALLED PER LATEST EDITION OF NFPA 13, HEAD
SHALL BE BASED UPON THE ORDINARY HAZARD SCHEDULE. ALL SPRINKLER
SHALL BE SCHEDULE 40 BLACK IRON. SCHEDULE 10 PIPING IS PERMISSIBLE IF
TO THE LANDLORD. HYDRAULICALLY CALCULATE SYSTEM AND SUBMIT COPIES
THE CALCULATIONS TO THE AUTHORITY HAVING JURISDICTION AND THE LANDLORD.
SHOP DRAWNGS FOR SUBMITTAL TO THE AUTHORITY HAVING JURISDICTION AND
LANDLORD BEFORE FABRICATION.
COPIES OF THE APPROVED SHOP DRAWINGS SHALL BE SUBMITTED TO THE OWNER
THE LANDLORD PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
FOR INSPECTION TESTING AND APPROVAL BY THE AUTHORITY HAVING
AND THE STATE INSPECTION BUREAU AS REQUIRED.
SIGNED CERTIFICATE OF COMPLETION COPIES TO BE GIVEN TO OWNER'S
INSURANCE REPRESENTATIVE, AND PROJECT OFFICE.
ALL SPRINKLER LINES AS HIGH AS POSSIBLE TO MAINTAIN 18 CLEARANCE ABOVE
SHELVING.
HEADS IN SALES AREA SHALL BE CONCEALED TYPE WITH WHITE COVER
UPRIGHT PENDANT HEADS SHALL BE USED IN ALL AREAS WITHOUT A CEILING.
HEADS WITH ESCUTCHEON PLATES SHALL BE USED IN ALL STOCKROOM
/RESTROOMS WITH LAY -IN OR GYPSUM BOARD CEILINGS. SPRINKLER HEAD
RATINGS SHALL BE 165'F IN SALES AND STOCK AREAS AND 212T IN
WINDOWS AND LIGHTING FIXTURE CANOPIES OR AS REQUIRED BY LANDLORD'S
AGENCY AND LOCAL AUTHORITIES. SPRINKLER HEADS SHALL BE QUICK
TYPE. ALL SEMI - RECESSED AND CONCEALED HEADS SHALL BE WHITE.
THE SITE AND EDRPIP ALL ED OR CONDITIONS TO WHICH WILL AFFECT THE WORK,
ALL REQUIRED PIPING AND OR REVISIONS TO PIPING AS NEEDED FOR A
SPRINKLER SYSTEM WHICH IS APPROVED AND ACCEPTED BY LOCAL
SHOP DRAWNGS UNDER SEPARATE COVER. SUPPLY SPRINKLER SHOP DRAWINGS
APPLY TO BUILDING DEPARTMENT (REQUIRED).
DESIGNATED CONTRACTOR TO PERFORM ALL SPRINKLER MODIFICATIONS. SYSTEM
SHALL BE SCHEDULED IN ADVANCE WITH THE LANDLORD'S FIELD
THE SPRINKLER SYSTEM SHALL BE FULLY CHARGED AND OPERATIONAL
THE CONTRACTOR TH NTRACTOR IS OFF THE SITE.
FIRE PROTECTION AND SPRINKLER SYSTEM WORK SHALL BE IN ACCORDANCE WITH
INSURANCE AGENCY REQUIREMENTS, NFPA, STATE, COUNTY AND LOCAL FIRE
GRILLE, REGISTER, AND DIFFUSER SCHEDULE
PLUMBING FIXTURE SCHEDULE
-- REVIEWED FOR
CODE COMPLIANCE
APParIVEn
• ,
MAR �� I�
MARK
MANUFACTURER
MODEL
FACE
TYPE
MOUNTING
LOCATION
NECK SIZE
IN
FACE SIZE
IN
NOTE
TAG
MANUFACTURER
MODEL
ACCESSORIES / COMMENTS
WC -1
AMERICAN STANDARD
"CADET 3" #3305.000
16 -1/2" HIGH ELONGATED (BARRIER FREE), 1.6 GPF, PRESSURE ASSISTED TOILET, VIRTEOUS CHINA
COMPLETE TOILET WITH COLOR MATCHED PLASTIC SEAT AND COVER
S1
TITUS
OMNI
PLAQUE
LAY -IN
100
24 x24
A,B,C,D,E
R1
TITUS
350RL
LOUVERED
LAY -IN
22x22
22"x22"
C,E
NOTES:
A. NECK SIZE SHOWN ON DRAWINGS.
B. 4 -WAY THROW PATTERN UNLESS OTHERWISE SHOWN ON DRAWINGS.
C. BAKED ENAMEL FINISH; WHITE. PAINT PER ARCHITECTS RECOMMENDATIONS.
D. PROVIDE NECK FOR DUCT CONNECTION.
E. FRAME TYPE TO MATCH CEILING CONSTRUCTION, COORDINATED WITH ARCHITECTURAL REFLECTED CEILING PLAN,
LAV -1
AMERICAN STANDARD
"LUCERNE" #0355.012
, WHITE.
WALL HUNG (BARRIER FREE) LAVATORY, 4" CENTERS FAUCET HOLES, VIRTEOUS CHINA,
FAUCET: "MONTEREY" 7501.170, 1.5 GPM WITH WRIST BLADE HANDLES AND GRID STRAINER
FD -1
J.R. SMITH
#2005
6 „ 0 DIAMTER, CAST IRON BODY WITH FLASHING COLLAR AND ADJUSTABLE STRAINER
TP-1
PRECISION PLUMBING
"PRIME RITE" PR -500
CORROSION RESISTANT BRASS BODY, "0" RING SEALS, 1/2" INLET & OUTLET AND INTEGRAL
VACUUM BREAKER. PROVIDE DISTRIBUTION AS REQURIED,
WCO
J.R. SMITH
4530S
CAST IRON CLEAN OUT TEE, COUNTER SINK PLUG WITH GASKET AND STAINLESS STEEL COVER,
City of Tukwila
EWH -1
EEMAX
#SP3012
INSTANTANEOUS, 3.0 KW, 25 AMPS, 120V ELECTRIC WATER HEATER INSTALLED UNDER LAVATORY
INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SET OUTLET TEMPERATURE TO 110'F
^ A
BUILDING IVI 11/�
1
FAN SCHEDULE
NOTES:
1, COORDINATE WITH CONSTRUCTION MANAGER FOR SUBSTITUTIONS.
MARK
MANUFACTURER
MODEL
MOUNTING
CFM
ESP
(IN)
DRIVE
(BELT /DIRECT)
POWER
HP
FAN
RPM
ELECTRICAL
VOLTS /PH
DISC. TYPE
NOTE
EF -1
COOK
GC -144
CEILING
100
0.5
DIRECT
80.8 W
1054
120/1
SWITCH
A -C
NOTES:
A. EXHAUST FAN SHALL BE INTERLOCKED WITH LIGHT SWITCH,
B. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
C. PROVIDE WITH BACK DRAFT DAMPER.
CONDENSING. UNIT SCHEDULE
MARK
SERVICE
MANUFACTURER
MODEL
NOMINAL
TONNAGE
COOLING CAPACITY
ELECTRICAL
NOTES
TOT.
SENS.
MCA
MOCP
V /PH /HZ
CU -1
AHU -1
TRANE
4TTA3048A
4
47
34.3
20
30
208/3/60
A -G
NOTES:
A. EQUIPMENT SIZED FOR 95'F AMBIENT TEMP
C. INSTALL CONDENSING UNIT ON ROOF IN APPROVED
D. DIVISION 16 SHALL PROVIDE DISCONNECT SWITCH,
E. PROVIDE STARTERS FOR ALL MOTORS.
F. SIZE AND INSTALL REFRIGERANT LINES PER
AND SIZE.
G. PROVIDE LIQUID LINE FILTER DRYER AND SIGHT
RATURE SUMMER DB a 85F WB 65F AND WINTER DESIGN TEMPERATURE OF 25'F
/
LANDLORD LOCATION, ROUTE REFRIGERANT LINES DOWN THROUGH LANDLORD PROVIDED CHASE.
THE MANUFACTURERS RECOMMENDATIONS, VERIFY WITH EQUIPMENT SUPPLIER REFRIGERATION LINE LENGTH
GLASS.
AIR HANDLING UNIT
S C H E D U L E
MARK
MANUFACTURER
MODEL
NOMINAL
TONNAGE
SUPPLY FAN
COOLING COIL
HEATING
MIN
0/A
CFM
ELECTRICAL
CFM
ESP
(IN)
MIN.
HP
TH
(MBH)
SH
(MBH)
EAT
(DB /WB)
EER
(SEER)
INPUT
KW
MCA
MOCP
45
V /PH/HZ
208/3/60
NOTE
A -F
AHU -1
TRANE
4TEC3F55B
4
1500
0.70
0.50
47
34.3 '
80 / 67
(13.25)
15
400
45
NOTES:
A. EQUIPMENT SIZED FOR AMBIENT TEMPERATURE OF 957, SUMMER DB = 857, WB = 65.F, WINTER DB = 23T.
B. PROVIDE WITH TWO SETS OF 2" THICK THROW -AWAY FILTERS.
C. PROVIDE UNIT WITH FACTORY MOUNTED DISCONNECT.
D. PROVIDE SECONDARY DRAIN PAN WITH FLOAT SWITCH, UNIT SHALL SHUT DOWN UPON ALARM FROM FLOAT SWITCH.
E. SUSPEND UNIT FROM STRUCTURE, PROVIDE SPRING VIBRATION ISOLATORS AND SEISMIC BRACING PER IBC..
F. FIELD INSTALLED, FACTORY PROVIDED MIXING BOX WITH DRY BULB CONTROLLER FOR ECONOMIZER CONTROL:
RECEIVED
- FEB 11 2011
PERMITCENTER
20
FIRE PROTECTION SPECIFICATION
19
HVAC / PLUMBING SCHEDULES
PROJECT TEAM:
Architect: Epoch Design Group, Inc.
1155 011vette Exec. Pkwy.
Suite 100
St. Louts, MO 63132
TEL: 314.721.1340
FAX: 314.721.0344
M. E. P. & F.P.
Engineer: Randall A. Nelson, P.E.
14817 West 95th Street
Lenexa, KS 66215
TEL 913.322.5150
FAX: 913.322.5155
COPYRIGHT DISCLAIMER:
THIS DOCUMENT IS THE PROPERTY OF EPOCH DESIGN GROUP,
COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION
FROM EPOCH DESIGN GROUP FOR USE OP THIS DOCUMENT 15
NOT TRANSFERABLE. THE RECIPIENT OF THIS DOCUMENT I5
HEREBY ADVISED THAT IT IS RELEASED FOR USE UNDER THE
FOLLOWING TERMS AND CONDITIONS,
THE DOCUMENT 15 TO BE USED ONLY IN CONJUNCTION WITH
THIS PROJECT. REUSE OF ANY PORTION OP THE DOCUMENT M
ANY OTHER CIRCUMSTANCE CONSTITUTES COPYRIGHT
INFRINGEMENT.
THE DOCUMENT IS FOR DESIGN MEET AND INFORMATION ONLY,
AND DOES1Qj.�CONSTITUTE AS•BURT CONDITIONS. THE
RECIPIENT RETAINS TRMILIGATION TO VERIFY THE CONDITIONS
OF THE SUBJECT PROPERTY AND 70 COMPLETELY COORDINATE
ALL DIMENSIONS, FABRICATION METHODS, RELATED AND
INTEGRATED SYSTEMS, ETC, WITH RESPECT TO ALL ASPECTS OF
THE WORK
EPOCH DESIGN GROUP MAKES NO WARRANTY AS TO THE
SUITABILITY OF THE DOCUMENT FOR THE RECIPIENT'S MENDED
USE. THE RECIPIENT SPECIFICALLY AGREES TO WAIN AND TO
INDEMNIFY AND DEFEND ANY AND ALL CLAMS AGAINST EPOCH
DESIGN GROUP, ITS CONSULTANTS, ANY OF ITS RELATED ENTITIES,
VENDORS, OR CONTRACTORS, FOR ANY LOSS INCURRED AS A
RESULT OP PROPER OR IMPROPER 115! OP TIES DOCUMENT.
THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT
UPON COMPLETION OR TERMINATION OP WORK PERFORMED IN
CONJUNCTION WITH THIS PROJECT.
r EXPINEs C' %L /f //
PROJECT TITLE:
1-
.W
v
E-
(J O CO
�W O z
W
pg
o In O
W F-
No.O Revision Description Date
SHEET TITLE:
MECHANCIAL
DETAILS AND
SCHEDULES
PROJECT NO.:
10313
SHEET NUMBER:
DRAWN BY:
JCC M 2 O
ISSUE DATE:
01/26/11
•
A. GENERAL CONDITIONS
1. DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY CON D ITN 0 NS AND ALL
OTHER SPECIFICATION SECTIONS (IF PROVIDED AS PART OF THE CONTRACT) ARE A PART OF THIS CONTRACT.
2. THE TERM "CONTRACTOR" SHALL MEAN THE "MECHANICAL CONTRACTOR HIRED TO COMPLETE THE WORK OUTLINED IN
THESE PLANS AND SPECIFICATIONS'. UNLESS OTHERWISE SPECIFIED.
3. THE CONTRACTOR FOR THIS WORK IS REQUIRED TO REVIEW ALL DRAWINGS FOR ALL OTHER TRADES.
IS RESPONSIBLE NSI
4. THE GENERAL CONTRACTOR I R P LE FOR PROVIDING ITS SUBCONTRACTORS WITH A FULL SET OF BID DOCUMENTS
B
INCLUDING SPECIFICATIONS AND MUST COORDINATE ITS WORK AND INSPECTIONS AND THE WORK AND INSPECTION OF THEIR
SUBCONTRACTORS WITH ALL OTHER TRADES ON SITE TO CONFORM WITH THE GENERAL CONTRACTOR'S TIME SCHEDULE.
5. BY SUBMITTING A QUOTATION OR PROPOSAL THE MECHANICAL CONTRACTOR EXPRESSLY STATES AND WARRANTS THAT: ALL
DRAWINGS AND SPECIFICATIONS HAVE BEEN THOROUGHLY REVIEWED, CONTRACTOR HAS BECOME FAMILIARIZED WITH JOB SITE
CONDITIONS AND IS TOTALLY QUALIFIED TO PERFORM ALL OF THE WORK REQUIRED.
P
6. BEFORE SUBMITTING A FINAL PROPOSAL THE CONTRACTOR SHALL EXAMINE THE SITE OF THE PROPOSED WORK TO
DETERMINE THE EXISTING CONDITIONS THAT MAY AFFECT THE PROPOSAL. IF DISCREPANCIES ARE NOTED BETWEEN THE
DOCUMENTS AND THE EXISTING CONDITIONS THE ARCHITECT SHALL BE NOTIFIED AND THE CONTRACTOR SHALL RECEIVE
CLARIFICATION BEFORE SUBMITTING A BID. THE SUBMISSION OF A PROPOSAL SHALL INDICATE THAT ALL CHARGES AND COSTS
MADE NECESSARY BY EXISTING CONDITIONS ARE INCLUDED AND THAT THE COMPLETE SYSTEM AS DESCRIBED HEREIN WILL BE
FURNISHED AT THE PROPOSED COST.
7. WHEN USED, THE TERM "PROVIDED BY CONTRACTOR" SHALL BE INTERPRETED AS MEANING "FURNISHED AND INSTALLED BY
CONTRACTOR" WITH THE EXCEPTION WHERE ITEMS ARE PROVIDED BY TENANT" SHALL BE INTERPRETED AS MEANING
"FURNISHED BY TENANT (INSTALLED BY CONTRACTOR) ", EXCEPT WHERE NOTED OTHERWISE.
B. GENERAL REQUIREMENTS
SHALL PROVIDE ALL LABOR MATERIALS EQUIPMENT, SERVICES TOOLS, TRANSPORTATION, INCIDENTALS
1. THE CONTRACTOR ,
AND DETAILS NECESSARY TO PROVIDE COMPLETE AND FULLY FUNCTIONAL MECHANICAL SYSTEMS AS SHOWN ON THE
IR
DRAWINGS, CALLED FOR IN THE SPECIFICATIONS (IF SUPPLIED) AND AS REQUIRED BY WORK JOB CONDITIONS. ALL 0 NOT
SPECIFICALLY NOTED AS BEING BY THE LANDLORD SHALL BE PROVIDED THE BY E MECHANICAL CONTRACTOR. CLOSELY
COORDINATE THE ENTIRE INSTALLATION WITH LANDLORD AS REQUIRED. FIELD VERIFY THE EXACT TYPE, SIZE, LOCATION.
REQUIREMENTS, ETC. OF EXISTING EQUIPMENT, PIPE AND DUCTS SERVING THE TENANT SPACE PRIOR TO SUBMISSION OF BID.
2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED
FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR WHICH IS
NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH 15 NECESSARY TO COMPLETE THE
WORK OR WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE PROVIDED AS PART OF THE CONTRACT.
A FOR ITEMS WHI H EXCEED CODES OR THE LANDLORD'S TENANT
3. WHERE THE DRAWINGS AND / OR SPECIFICATIONS CALL FO WHICH
THE CONTRACTOR IS STILL RESPONSIBLE FOR PROVIDING THE SYSTEM AS DESIGNED AND DESCRIBED ON THE
DRAWINGS, UNLESS SPECIFICALLY NOTED OTHERWISE.
4. THE CONTRACTOR SHALL OBTAIN AND COMPLY WITH DETAILED REQUIREMENTS OF LEASE EXTRACTS FROM THE LANDLORD
AND TENANT.
5. COORDINATE LOCATIO N S OF A LL AIR OUTLET S WITH ALL WALLS, LIGHTS S PRINK LE R HEADS, CEILING IN G TI LES
AN D DECORATIVE
CEILING FIXTURES PRIOR TO INSTALLATION.
6. ALL MECHANICAL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATION, SERVICE, MAINTENANCE
AND REPAIR. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS TO ALL EQUIPMENT FOR SERVICE.
7. THE CONTRACTOR SHALL DO ALL CUTTING, CORE DRILLING, CHASING, OR CHANNELING AND PATCHING REQUIRED FOR ANY
R APPROVAL WORK UNDER THIS CONTRACT. CUTTING SHALL HAVE PRIG OV L BY THE TENANT'S CONSTRUCTION MANAGER AND THE
LANDLORD OR LANDLORD'S REPRESENTATIVE. PATCHING SHALL MATCH FINISH OF SURROUNDING AREA.
C. CODES
1, ALL WORK SHALL BE PERFORMED IN A NEAT AND PROFESSIONAL MANNER USING GOOD CONSTRUCTION PRACTICES. ALL
WORK SHALL CONFORM TO THE LATEST ADOPTED EDITION OF THE LANDLORDS CRITERIA; PROVINCE, COUNTY AND LOCAL
CODES AND ORDINANCES; THE LATEST EDITIONS OF ASHRAE STANDARDS, THE LIFE SAFETY CODE, THE APPLICABLE BUILDING
CODE, UNDERWRITERS LABORATORIES, THE NATIONAL ELECTRICAL CODE, NFPA 70, 90A AND 96 AND ALL OTHER APPLICABLE
CODES ENFORCED BY AUTHORITIES HAVING JURISDICTION. THE CHANGES REQUIRED BY ANY APPLICABLE CODES SHALL BE
INCLUDED IN THE BID. AFTER THE CONTRACT IS ISSUED, NO ADDITIONAL COST DUE TO CODE ISSUES SHALL BE REIMBURSED
BY THE TENANT TO THE CONTRACTOR.
D. LICENSES. PERMITS. INSPECTIONS AND FEES
1, THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS, INSPECTIONS AND FEES REQUIRED OR RELATED
TO THIS WORK.
2. FURNISH TO THE TENANT'S CONSTRUCTION MANAGER ALL CERTIFICATES OF INSPECTION AND FINAL INSPECTION APPROVAL
AT COMPLETION OF PROJECT.
E. DRAWINGS
1. DRAWINGS (PLANS AND SPECIFICATIONS) ARE DIAGRAMMATIC AND INDICATE THE GENERAL LOCATION AND INTENT OF THE
MECHANICAL SYSTEMS. BECAUSE OF THE SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL DUCT AND PIPE
OFFSETS, FITTINGS AND ACCESSORIES THAT MAY BE REQUIRED. THE MECHANICAL CONTRACTOR MUST OBTAIN APPROVED
CONSTRUCTION DRAWINGS FROM THE GENERAL CONTRACTOR BEFORE BEGINNING ANY WORK.
2. THE LAYOUT SHOWN ON THE DRAWINGS IS BASED ON A PARTICULAR MAKE OF EQUIPMENT. IF ANOTHER MAKE OF
EQUIPMENT IS USED WHICH REQUIRES MODIFICATION OR CHANGE OF ANY DESCRIPTION FROM THE DRAWINGS OR
SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE AS PART OF THIS WORK, FOR MAKING ALL SUCH MODIFICATIONS
AND CHANGES, INCLUDING THOSE INVOLVING OTHER TRADES WITH THE COST THEREOF INCLUDED IN THE BID. IN SUCH CASE,
CONTRACTOR SHALL SUBMIT DRAWINGS AND SPECIFICATIONS PRIOR TO STARTING WORK SHOWING ALL SUCH MODIFICATIONS
AND CHANGES. THE PROPOSAL SHALL BE SUBJECT TO THE APPROVAL OF THE TENANT'S CONSTRUCTION MANAGER.
F. EXISTING LEASE SPACE CONDITIONS
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE DEMOLITION OF EXISTING MECHANICAL WORK IN
THE SPACE NOT SHOWN TO BE REUSED IN THE NEW TENANT SPACE.
2. THE CONTRACTOR SHALL INCLUDE AND WILL BE HELD RESPONSIBLE FOR, THE REMOVAL OF ALL EXISTING FIRE
PROTECTION, PLUMBING FIXTURES, PIPING, HVAC UNITS, REFRIGERANT RECAPTURE, EXHAUST FANS, DUCTWORK, ETC. AND
ASSOCIATED ROOF CURBS NOT TO BE REUSED ON THIS PROJECT, UNLESS SPECIFICALLY NOTED OTHERWISE. CONTRACTOR
MUST VERIFY WITH THE LANDLORD ALL PRESUMED ABANDONED EQUIPMENT, PIPES, DUCTWORK AND EQUIPMENT PRIOR TO
REMOVAL. ROOF CURBS SHALL BE REMOVED AND THE ROOF PATCHED UNLESS NOTED FOR REUSE OR RECONFIGURATION ON
PLANS. ROOF PATCHING SHALL BE PERFORMED AT THE CONTRACTOR'S EXPENSE BY A ROOFING CONTRACTOR APPROVED BY
THE LANDLORD. ALL EXTRANEOUS ITEMS IN THE SPACE OR ON THE ROOF (ABOVE THIS SPACE) NOT APPLICABLE TO THE NEW
WORK OR PART OF THE LANDLORD'S OR ANOTHER TENANT'S ACTIVE SYSTEM MUST BE REMOVED AND ROOF/WALL /FLOOR
PATCHED /REPAIRED TO MATCH THE EXISTING STRUCTURE. EXISTING ABANDONED PIPES, DUCTS OR EQUIPMENT IN THE FLOOR,
EMBEDDED IN CONCRETE OR OTHERWISE INACCESSIBLE ARE TO BE CUT OFF AND SEALED BELOW OR WITHIN FLOOR OR WALL
LEVEL WHEN THEY ARE NOT REUSED IN THIS PROJECT.
IF REQUIRED BY THE LANDLORD OR CODES, ABANDONED PIPING AND/OR DUCTWORK MUST BE REMOVED TO POINT OF ORIGIN.
CONFIRM THE EXTENT OF DEMOLITION
EQ PRIOR TO BID AND INCLUDE IN BID PROPOSAL.
3. ACTIVE LANDLORD OR OTHER TENANT SERVICES ENCOUNTERED IN WORK SHALL BE PROTECTED AND SUPPORTED. IF
EXISTING SERVICES NOT ANTICIPATED REQUIRE RELOCATION, CONTACT THE TENANT'S CONSTRUCTION MANAGER IMMEDIATELY.
ALL COSTS FOR REPAIR OF DAMAGES TO ACTIVE LANDLORD OR OTHER TENANT SERVICES DURING CONSTRUCTION SHALL BE
PAID FOR BY THE CONTRACTOR CAUSING THE DAMAGE.
ST BE DONE WITH MINIMUM INTERRUPTION 0
N OF LANDLORD E
4. TIE -INS AND MODIFICATIONS TO EXISTING LANDLORD SERVICES MUST
OPERATION AND DURING HOURS SPECIFIED BY THE LANDLORD. THE CONTRACTOR IS RESPONSIBLE FOR CONFIRMING EXACT
WORKING HOURS OF THIS WORK WITH THE LANDLORD PRIOR TO SUBMITTING THEIR BID. THE CONTRACTOR SHALL INCLUDE IN
THEIR BID, ALL PREMIUM TIME REQUIRED TO PERFORM MODIFICATIONS DURING OTHER THAN NORMAL WORKING HOURS. ALL
SUCH WORK MUST BE COORDINATED WITH THE LANDLORD.
5. EQUIPMENT AND MATERIALS IN TRANSIT SHALL UTILIZE FREIGHT ELEVATOR OR STAIRS. SAID EQUIPMENT OR MATERIALS
SHALL BE DISASSEMBLED AS REQUIRED TO MEET THE RESTRICTIONS IMPOSED BY THE BUILDING OR ITS COMPONENT
CONSTRAINTS AND THEN REASSEMBLED IN THE NEW WORK AREA.
6. ALL WORK SHALL BE DONE WITH A MINIMUM OF NOISE AND DISTURBANCE TO BUSINESS ROUTINE. ALL WORK SCHEDULES
SHALL BE COORDINATED WITH AND APPROVED BY, THE TENANTS CONSTRUCTION MANAGER.
7. SINCE THESE ARE SECURE FLOORS, ALL DELIVERIES, WORKERS, WORK OPERATORS, ETC., REQUIRED BY THE CONTRACTOR
FOR WORK PERFORMED IN ANY AREA OR SITE BUILDING SHALL BE IN STRICT CONFORMANCE TO THE RULES AND
REGULATIONS OF THE OWNER.
8. CONTRACTOR SHALL PROTECT THEIR WORK AND EQUIPMENT FROM DAMAGE, VANDALS, ETC. ANY ITEM THAT IS DAMAGED,
VANDALIZED OR STOLEN PRIOR TO ACCEPTANCE OF BUILDING BY OWNER AND ARCHITECT SHALL BE REPLACED BY RESPECTIVE
CONTRACTOR AT NO CHARGE TO TENANT.
9. IT IS SPECIFICALLY THE INTENTION OF THIS SPECIFICATION TO HOLD THE CONTRACTOR RESPONSIBLE FOR ALL DAMAGE
DONE TO ANY EXISTING FACILITIES, EQUIPMENT, PAINTING, OR ARCHITECTURAL AND STRUCTURAL FEATURES OF THE BUILDING,
PAIR ANY DAMAGE
BY EITHER THEIR OWN WORKMEN OR BY ANY OF THEIR SUBCONTRACTORS. THE CONTRACTOR SHALL REPAIR
DONE BY THEIR OWN WORKMEN OR SUBCONTRACTORS AND THE OWNER AT THEIR DISCRETION, MAY WITHHOLD PAYMENTS
EQUAL TO THE REASONABLE COST OF THE REPAIRS.
10. THIS CONTRACTOR OR THEIR WORKMEN SHALL NOT BE PERMITTED TO USE ANY PART OF THE EXISTING BUILDING AS A
SHOP WITHOUT THE APPROVAL OF THE OWNER AND ARCHITECT.
11. WHERE THE WORK MAKES TEMPORARY SHUTDOWN OF SERVICES UNAVOIDABLE, THEY SHALL BE MADE AT NIGHT OR AT
SUCH TIMES AS WILL CAUSE THE LEAST INTERFERENCE WITH THE ESTABLISHED OPERATING ROUTINE.
12. THIS CONTRACTOR SHALL ARRANGE THE WORK SO AS TO ASSURE THAT SERVICES WILL BE SHUT DOWN ONLY DURING
THE TIME ACTUALLY REQUIRED TO MAKE THE NECESSARY CONNECTION TO THE EXISTING WORK. THIS CONTRACTOR SHALL GIVE
AMPLE WRITTEN NOTICE IN ADVANCE TO THE OWNER OF ANY REQUIRED SHUT DOWN.
13. ALL MOTORS, FANS, CONTROLS, FIXTURES. HVAC UNIT, DUCTWORK AND OTHER EQUIPMENT FOR USE IN THIS CONTRACT
SHALL BE PROTECTED BY TARPAULIN OR BY BOXING AS SOON AS DELIVERED TO THE SITE AND SHALL BE KEPT CLEAN AND
DRY. THE MOTORS, UNITS, FIXTURES, FANS, DUCTWORK AND MOVING PARTS SHALL BE KEPT COVERED SO AS TO ELIMINATE
DIRT, DUST AND OTHER MATERIALS ENTERING THE PARTS DURING ERECTION AND CONSTRUCTION WORK ON THE BUILDING.
SHOULD R BE FOUND THAT ANY PARTS ARE DAMAGED DUE TO CARELESSNESS ON THE PART OF THE CONTRACTOR IN NOT
PROVIDING PROPER PROTECTION, SUCH PART OR PARTS SHALL BE REPLACED BY THE CONTRACTOR AT THEIR OWN COST AND
EXPENSE. ALL OPENINGS IN DUCTS, PIPING, CONDUITS, ETC., SHALL BE PROPERLY PROTECTED WITH TEMPORARY CAPS OR
PLUGS AT ALL TIMES,
G. DISCREPANCIES IN DOCUMENTS
1. DRAWINGS (PLANS. SPECIFICATIONS AND DETAILS) ARE DIAGRAMMATIC AND INDICATE THE GENERAL LOCATION AND INTENT
OF THE MECHANICAL SYSTEMS. WHERE DRAWING. EXISTING SITE CONDITIONS: SPECIFICATIONS OR OTHER TRADES CONFLICT OR
ARE UNCLEAR. ADVISE THE GENERAL CONTRACTOR IN WRITING. PRIOR TO SUBMITTAL OF BID. THE GENERAL CONTRACTOR IS
RESPONSIBLE TO ADVISE THE TENANT'S CONSTRUCTION MANAGER. IN WRITING. OF VARIATIONS TO THE CONTRACT DOCUMENTS
PRIOR TO SUBMISSION OF BID. OTHERWISE. TENANT'S CONSTRUCTION MANAGER'S INTERPRETATION OF CONTRACT DOCUMENTS
OR CONDITIONS SHALL BE FINAL WITH NO ADDITIONAL COMPENSATION PERMITTED.
H. TRADE NAMES AND MANUFACTURERS
1. WHERE TRADE NAMES AND MANUFACTURERS ARE USED ON THE DRAWINGS OR IN THE SPECIFICATIONS, THE EXACT
AN EQUIVALENT
EQUIPMENT SHALL BE USED AS
A MINIMUM STANDARD FOR THE BASE BID. MANUFACTURERS CONSIDERED AS EQ E
OR BETTER IN ALL ASPECTS TO THAT SPECIFIED WILL BE SUBJECT TO REVIEW IN WRITING BY THE TENANT'S CONSTRUCTION
MANAGER PRIOR TO ACCEPTANCE, THE USE OF ANY UNAUTHO R IZED EQUIPMENT S HA LL BE
SUBJEC T TO REMOVAL
AND
REPLACEMENT AT THE CONTRACTOR'S EXPENSE.
DRAWINGS
S G
THREE COPIES 0
1. SUBMIT THR PI OF MATERIAL LISTS AND SHOP DRAWINGS FOR ALL EQUIPMENT AND DUCT FABRICATION DRAWINGS
TO THE TENANT'S CONSTRUCTION MANAGER FOR REVIEW PRIOR TO ORDERING EQUIPMENT. SUBMISSIONS MUST BE EARLY
ENOUGH TO ALLOW THE TENANT'S CONSTRUCTION MANAGER EIGHT WORKING DAYS FOR REVIEW WITHOUT CAUSING DELAYS OR
CONFLICTS TO THE JOB'S PROGRESS. SUBMITTALS SHALL BE IN ACCORDANCE WITH THE GENERAL CONDITIONS USING THE
MANUFACTURER'S LISTED ON THE DRAWINGS. SHOP DRAWINGS SHALL INCLUDE ALL DATA THAT PERTAINS TO THE
REQUIREMENTS SET FORTH ON THE DRAWINGS AND IN THE SPECIFICATIONS. THE SUBMITTAL SHALL INCLUDE BUT NOT BE
LIMITED TO CUTS OR CATALOGS INCLUDING DESCRIPTIVE LITERATURE AND CHARACTERISTICS OF EQUIPMENT SHALL SHOW
MAJOR DIMENSIONS, R OUG HIN G IN D AT A, CAPACITY, CURVES, PRESSURE DROPS , CODE COMPLIANCE, MOTOR AND DRIVE DATA
AND ELECTRICAL DATA. OBSERVE SPECIAL INSTRUCTIONS WHEN REQUIRED. SUBMITTALS SHALL BEAR THE STAMP OF THE
GENERAL AND SUBCONTRACTOR SHOWING THAT HE HAS REVIEWED AND CONFIRMED THAT THEY ARE IN CONFORMANCE WITH
THE CONTRACT DOCUMENTS OR INDICATE WHERE EXCEPTIONS TAKE PLACE. LACK OF SUCH CONTRACTOR'S REVIEW WILL BE
CAUSE FOR REJECTION WITHOUT REVIEW BY TENANT'S CONSTRUCTION MANAGER, ALL SHOP DRAWINGS MUST APPEAR IN THE
OPERATION AND MAINTENANCE MANUALS LEFT ON SITE AT JOB COMPLETION.
2. TENANT'S CONSTRUCTION MANAGERS OR ARCHITECTS REVIEW OF SHOP DRAWINGS OR SCHEDULES SHALL NOT RELIEVE
THE CONTRACTOR FROM RESPONSIBILITY FOR ERRORS, OMISSIONS OR OTHER DE FICIENCIES OR DEVIATIONS IN THE SHOP
DRAWINGS FROM THE CONSTRUCTION DOCUMENTS.
TO FURNISH SHOP
CONTRACTOR AND OR THEIR SUBCONTRACTORS
I F THE GENERAL CO R
E P NSIB LITY 0
3. IT ISTHER50 /
DRAWINGS AND SUBMITTALS ON ANY AND ALL EQUIPMENT, DUCT, DAMPERS. CONTROLS ETC. TO THE ARCHITECT FOR THEIR
REVIEW PRIOR TO CONSTRUCTION.
J. RECORD DRAWINGS
1, THE CONTRACTO R SHALL MAINTAIN ONE COPY OF DRAWINGS AND SPECIFICATIONS ON THE JOB SITE TO RECORD
LL
DEVIATIONS FROM CONTRACT DRAWINGS, SUCH AS LOCATIONS OF CONCEALED PIPING VALVES AND DUCTS, REVISIONS,
ADDENDUM'S AND CHANGE ORDERS, SIGNIFICANT DEVIATIONS MADE NECESSARY BY FIELD CONDITIONS, APPROVED EQUIPMENT
SUBSTITUTIONS AND CONTRACTOR'S COORDINATION WITH OTHER TRADES AND EXACT ROUTING OF ALL. SANITARY AND DOMESTIC
WATER PIPING UNDER FLOOR.
2. AT COMPLETION OF THE PROJECT AND BEFORE FINAL APPROVAL, THE CONTRACTOR SHALL MAKE ANY FINAL CORRECTIONS
TO DRAWINGS AND CERTIFY THE ACCURACY OF EACH PRINT BY SIGNATURE THEREON. THE DRAWINGS ARE TO BE TURNED
OVER TO THE TENANT.
K. GUARANTEE. WARRANTY
1. THE MECHANICAL CONTRACTOR SHALL INCLUDE IN THE PROPOSAL A ONE YEAR GUARANTEE, WARRANTY ON ALL EQUIPMENT
AND MATER I AL INSTALLED I T OR REFURBISHED ALL MATERIALS AND WORK UNDER THE CONTRACT AND SHALL MAKE GOOD,
REPAIR, OR REPLACE AT THEIR OWN EXPENSE, ANY DEFECTIVE WORK, MATERIAL OR EQUIPMENT WHICH MAY BE DISCOVERED
WITHIN A PERIOD OF 12 MONTHS FROM THE DATE OF WRITTEN ACCEPTANCE OF THE INSTALLATION BY THE TENANT'S
CONSTRUCTION MANAGER. IN CASE OF REPLACEMENT OR REPAIR OF EQUIPMENT DUE TO FAILURE WITHIN THE GUARANTEE
PERIOD. THE GUARANTEE ON THAT PORTION OF WORK SHALL BE EXTENDED FOR A PERIOD OF 12 MONTHS FROM THE DATE.
OF SUCH REPLACEMENT OR REPAIR. THIS GUARANTEE, WARRANTY IS TO INCLUDE ALL LABOR, MATERIAL, PARTS, ETC.
NECESSARY TO MAINTAIN THE SYSTEM IN SATISFACTORY OPERATION FOR A PERIOD OF ONE YEAR STARTING FROM THE DATE
OF ACCEPTANCE OF THE SYSTEM BY THE TENANT. IT SHALL ALSO INCLUDE ONE SUMMER TO WINTER CHANGEOVER AND ONE
WINTER TO SUMMER CHANGEOVER, A NEW SET OF FILTERS AT THE TIME OF STARTUP AND TWELVE (12) MONTHLY FILTER
CHANGES DURING THE FIRST YEAR. THE NORMAL PREVENTATIVE MAINTENANCE WORK SHALL BE PERFORMED AT THE TIME OF
THE FILTER CHANGES. USE ONLY #40 PLEATED TYPE AIR FILTERS.
L. OPERATIONS MANUALS
1. ONE COPY OF EACH OPERATION AND MAINTENANCE MANUAL FOR ALL EQUIPMENT FURNISHED ON THE JOB SHALL BE
PROVIDED TO THE TENANT BOUND TOGETHER IN A 3 INCH, THREE RING BINDER. THE BINDER SHALL INCLUDE BUT NOT BE
LIMITED TO INSTALLATION, MAINTENANCE AND OPERATING INSTRUCTIONS, PAMPHLETS OR BROCHURES, REVIEWED SHOP
AND WARRANTIES AN S OBTAINED FROM EACH MANUFACTURER OF PRINCIPAL ITEMS OF EQUIPMENT.
E
M. SLEEVES
1. THE CO NTRA CT O R SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN THE INSTALLATION. EACH SLEEVE
SHALL EXTEND THROUGH ITS RESPECTIVE FLOOR, WALL, OR PARTITION AND SHALL BE CUT FLUSH WITH EACH SURFACE
EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL EXTEND 2 INCHES ABOVE THE FLOOR.
2. ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND /OR FLOORS SHALL BE FIRE SEALED WITH APPROVED
SEALANTS RATED FOR THE APPLICATION SO AS TO MAINTAIN THE FIRE RATING OF THE ASSEMBLY, CONFORM TO THE U.L.
ASSEMBLY RATING OF THE FLOOR OR WALL.
3. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE STANDARD WEIGHT STEEL PIPE FINISHED
WITH SMOOTH EDGES. FOR OTHER THAN MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS OR FOR CONCEALED VERTICAL
PIPING, SLEEVES SHALL BE 22 GAUGE GALVANIZED STEEL MINIMUM.
4. DUCT SLEEVES SHALL BE MINIMUM 14 GAUGE STEEL
N. HANGERS
1. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, BANDS, C- CLAMPS WITH RETAINING CLIPS,
CHANNELS, HANGER RODS, ETC. NECESSARY FOR THE INSTALLATION OF WORK.
2. HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE. OR MASONRY, BUT NOT TO PIPING OR DUCTWORK,
DUCTWORK SHALL NOT BE SUPPORTED FROM ROOF DECKING AND /OR BRIDGING, BUT SHALL BE SUSPENDED FROM THE TOP
CHORD OF BAR JOISTS, STEEL OR OTHER STRUCTURE. DUCTWORK SHALL CLEAR ALL SPRINKLERS AND OTHER OBSTACLES
AND SHALL BE HUNG AS HIGH AS POSSIBLE IN WORK AND STORAGE AREAS. WHERE INTERFERENCE'S OCCUR, IN ORDER TO
SUPPORT DUCTWORK OR PIPING, THE CONTRACTOR MUST INSTALL TRAPEZE. TYPE HANGERS OR SUPPORTS WHICH SHALL BE
LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE DAMPERS, VALVES, ACCESS DOORS AND OTHER EQUIPMENT
SERVICE REQUIREMENTS AND /OR OTHER TRADES. HANGER TYPES AND INSTALLATION METHODS ARE SUBJECT TO LANDLORD
CRITERIA.
3. HANGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR THE OUTER DIAMETER OF INSULATION. INSTALL
6 INCH LONG SPLIT CIRCLE GALVANIZED SADDLE BETWEEN THE HANGER AND THE PIPE INSULATION.
4. HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI- ELECTRICALLY SEPARATED FROM ONE ANOTHER.
0. ELECTRIC MOTORS
i. FURNISH, INSTALL AND ALIGN ALL MOTORS REQUIRED FOR THI S EQUIPMENT, UNLESS THEY ARE FACTORY INSTALLED ON
THE UNIT. ALL STARTERS AND ASSOCIATED WIRING AND SAFETY SWITCHES FOR SUCH MOTORS SHALL BE FURNISHED AND
INSTALLED BY THE ELECTRICAL CONTRACTOR. STARTERS SHALL MEET ALL REQUIREMENTS AS DEFINED IN THE ELECTRICAL
SPECIFICATIONS.
2. DESIGN, CONSTRUCTION AND PERFORMANCE CHARACTERISTICS OF MOTORS SHALL CONFORM TO ALL APPLICABLE
PROVISIONS OF LATEST NEMA, ANSI, ISEE STANDARDS FOR ELECTRICAL EQUIPMENT. ALL MOTORS SHALL BE SUITABLE FOR
OPERATION ON VOLTAGE VARIATION OF PLUS OR MINUS 10 PERCENT, 40 DEGREES C AMBIENT TEMPERATURE AND HAVE A
SERVICE FACTOR OF NOT LESS THAN 1.15.
P. LOW VOLTAGE (24 VOLT1 WIRING
1. THE CONTRACTOR IS TO INSTALL ALL LOW VOLTAGE WIRING REQUIRED FOR THEIR EQUIPMENT. THIS WORK INCLUDES ALL
TRANSFORMERS AND DEVICES TO MAKE THIS A COMPLETE FUNCTIONAL SYSTEM.
2. ALL WORK IS TO CONFORM TO THE ELECTRICAL SPECIFICATIONS AND THE REQUIREMENTS OF THE AUTHORITIES HAVING
JURISDICTION,
3. ANY CONDUIT REQUIRED BY CODE OR THE LANDLORD WILL BE INSTALLED BY THE ELECTRICAL SUBCONTRACTOR.
4. SMOKE DETECTORS AND REMOTE TEST STATION
A. IONIZING TYPE ARE TO BE USED ON THE RETURN SIDE OF THE HVAC UNIT AND PHOTO -TYPE ARE TO BE USED ON THE
SUPPLY. SIDE. ON ALL OTHER TYPES OF HVAC UNITS WHERE SMOKE DUCT DETECTORS ARE REQUIRED, USE FIELD INSTALLED
IONIZING TYPE IN RETURN DUCTWORK AND PHOTO -TYPE ON THE SUPPLY LOCATED BEFORE THE FIRST TAKEOFF. ONCE
ACTIVATED, THE SMOKE DETECTOR WILL SHUT DOWN HVAC UNIT.
B. SMOKE DETECTORS SHALL HAVE THEIR OWN REMOTE KEY TEST STATION SYSTEM WITH AUDIBLE AND VISUAL ALARM,
SIMPLEX MODEL 4098 -9842 OR APPROVED EQUIVALENT. ALARM TO HAVE CANDELA SETTING OF 75 AND A HIGH VOLUME
HORN TONE SETTING.
M ECHANICAL
SPECIFICATIONS
A. HEATING. VENTILATION AND AIR CONDITIONING
1. BEFORE STARTING WORK, THIS CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL, STRUCTURAL, MECHANICAL AND
ELECTRICAL PLANS AND SPECIFICATIONS TO SEQUENCE, COORDINATE AND INTEGRATE THE VARIOUS ELEMENTS OF THE HVAC
SYSTEM, MATERIALS AND EQUIPMENT WITH OTHER CONTRACTORS TO AVOID INTERFERENCE'S AND CONFLICTS.
B. I-NAC EQUIPMENT (REFER TO PLANS FOR SCHEDULE OF EQUIPMENT)
1. PRIMARY HVAC UNITS ARE TO BE AS SCHEDULED. EQUIVALENTS MAY BE SUBSTITUTED WITH WRITTEN APPROVAL ONLY. ALL
COMPRESSORS ARE TO INCLUDE A 5 YEAR EXTENDED WARRANTY.
2. ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT WITH ALL DEVICES, APPURTENANCES AND ACCESSORIES PROVIDED
TO MEET THE DESIGN INTENT AND OPERATION OF THE SYSTEMS SHOWN ON THE DRAWINGS AND SPECIFIED.
3. EQUIPMENT SHALL BE I N STALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. ALL AIR CONDITIONING
EQUIPMENT MUST HAVE A CONDENSATE DRAIN AND BE TRAPPED IN ACCORDANCE WITH MANUFACTURER'S DATA. SEE
DRAWINGS FOR ADDITIONAL DETAILS.
4. SECONDARY DRAIN PANS. ARE REQUIRED TO BE INSTALLED BENEATH ALL INDOOR AIR CONDITIONING EQUIPMENT WITH THE
EXCEPTION OF AIR TERMINAL BOXES. SECONDARY PANS ARE TO PROTECT ENTIRE UNIT. PROVIDE CONDENSATE PUMPS AS
REQUIRED. CONDENSATE SHALL BE DIRECTED TO MOP SINK, LAVATORY TRAP OR OTHER APPROVED DRAIN.
C. TOILET EXHAUST FANS
1. WHERE SHOWN ON DRAWINGS PROVIDE A TOILET EXHAUST FAN COMPLETE WITH GRAVITY BACKDRAFT DAMPER. ALL
DUCTWORK, ROOF OPENINGS AND CAPS NECESSARY TO PROVIDE A COMPLETE EXHAUST SYSTEM SHALL BE PROVIDED BY THE
CONTRACTOR. REFER TO PLANS FOR APPLICABILITY.
D. VIBRATION ISOLATION DEVICES
1. VIBRATION ISOLATION DEVICES SHALL BE PROVIDED IN ALL SUPPORTS BETWEEN VIBRATING EQUIPMENT (FANS, ROOFTOP
UNITS, WATER SOURCE HEAT PUMPS, AIR HANDLERS, FAN POWERED VAV BOXES, ETC.) AND STRUCTURE.
2. VIBRATING EQUIPMENT HUNG FROM STRUCTURE SHALL BE ISOLATED WITH RUBBER AND SPRING DEVICES. VIBRATING
EQUIPMENT SUPPORTED FROM FLOOR OR DECK SHALL BE ISOLATED WITH HOUSED SPRING MOUNT DEVICES.
1 EXAMINE DEAD LOAD AND OPERATING LOAD CONDITIONS WHEN SELECTING DEVICES. ADJUST FOR PROPER ALIGNMENT AND
LO A AVOID GROUNDING THE ISOLATOR.
LOADING.
4. CHECK HANGER ROD SIZE FOR ALLOWABLE LOADS AT THE ISOLATING DEVICE AND THE UPPER AND LOWER ATTACHMENTS
TR T R T TO S UC U ES DUC S EQUIPMENT, ETC.
5. CONSULT MANUFACTURER FOR APPLICATION DATA
G. CURBS AND STEEL FRAMING FOR SUPPORT
1. THIS CONTRACTOR WILL PROVIDE ALL NECESSARY CURBS AND STEEL FRAMING REQUIRED TO INSTALL ALL HVAC EQUIPMENT.
CURBS SHALL BE A MINIMUM OF 14 INCHES HIGH AND OF THE SAME MANUFACTURER AS THE EQUIPMENT SUPPORTED.
INSULATE UNDER THE COMPRESSOR SECTION TO PR EVE NT CONDENSATION. ALL CUR BS M US T BE IN STALLED SO THAT THE TOP P
OF CURBS ARE "DEAD" LEVEL. ALL PENETRATIONS OF EXISTING STRUCTURE SHALL BE DONE IN ACCORDANCE WITH THE
LANDLORD'S GUIDELINES AT THIS CONTRACTOR'S EXPENSE. ALL CONNECTIONS TO ROOFTOP EQUIPMENT SHALL BE INSIDE THE
CURB (CONDENSATE DRAIN, POWER WIRING. CONTROL WIRING, ETC.).
H. METAL DUCTWORK - NO FIBERGLASS DUCT ALLOWED
1. NO DUCTWORK SHALL BE FABRICATED PRIOR TO APPROVAL BY THE TENANT'S CONSTRUCTION MANAGER. DEVIATIONS FROM
DESIGN MUST BE APPROVED BY TENANT'S CONSTRUCTION MANAGER PRIOR TO FABRICATION OR INSTALLATION. ALL DUCT MAINS
ARE TO BE RECTANGULAR. ALL DUCT BRANCHES TO DIFFUSERS ARE TO BE ROUND SPIRAL DUCT.
2. AL L DUCTWO R K SHALL BE PROVIDED AND IN S T ALLED IN A CCO RD AN CE WITH SMACNA LO W VELOC ITY AN D "HVA C DUC T
CONSTRUCTION STANDARDS MANUAL ", LATEST EDITION AND ASHRAE USING PRIME SHEETS OF GALVANIZED STEEL CONFORM TO
THE REQUIREMENTS IN THE REFERENCED STANDARD FOR METAL THICKNESS, REINFORCING TYPES AND INTERVALS, TIE ROD
APPLICATIONS AND JOINT TYPES AND INTERVALS. ALL SQUARE ELBOWS SHALL BE PROVIDED WITH DOUBLE WALLED VANES ON
MAXIMUM 3" CENTERS. PROVIDE SEAL CLASS "C" ON ALL TRAVERSE JOINTS UNLESS SUPERSEDED BY MORE STRINGENT LOCAL
CODES. ALL DUCT CONNECTIONS ARE TO BE RIGID AND LEAK FREE ASSEMBLIES.
3. DURING THE CONSTRUCTION PHASE OF THE PROJECT, ANY DUCTWORK INSTALLED IS TO BE COMPLETELY SEALED UP OF
ANY OPENINGS, EITHER AT THE BEGINNING OR END OF A DUCT RUN OR AT A BRANCH, COLLAR DIFFUSER OR REGISTER TO
AVOID DIRT OR OTHER CONTAMINANTS FROM ENTERING THE SYSTEM.
4. EXCEPT WHERE OTHERWISE INDICATED, CONSTRUCT DUCT SYSTEMS TO 2 INCH WATER GAUGE PRESSURE CLASSIFICATION
(VERIFY WHETHER RETURN OR EXHAUST DUCT IS POSITIVE OR NEGATIVE PRESSURE). PRESSURE TEST DUCTS FOR LEAKAGE.
REMAKE LEAKING JOINTS AND APPLY SEALANTS AS REQUIRED TO FABRICATE A SYSTEM THAT DOES NOT EXCEED 5 PERCENT
LEAKAGE OR LESS AS STATED BY PRESSURE CLASS RATINGS IN SMACNA STANDARDS.
5. AS A MINIMUM, CROSSBREAK ALL FLAT SURFACES OR REINFORCE WITH A BEAD APPROXIMATELY 3/8 INCH WIDE BY 3/16
INCH DEEP ON 12 INCH CENTERS TO PREVENT VIBRATIONS.
6. INSTALL RIGID ROUND AND RECTANGULAR METAL DUCT WITH SUPPORT SYSTEMS INDICATED IN SMACNA STANDARDS. NO
WOOD SHALL BE USED TO SUPPORT OR BRACE DUCTS. PROVIDE SWAY AND SEISMIC BRACING AS REQUIRED BY PROVINCE
AND LOCAL CODES OR BY LANDLORD.
7. WHERE DUCTS PASS THROUGH ROOFS, FLOORS AND FIRE RATED PARTITIONS, PROVIDE AS MINIMUM 1 -1/2 INCH BY
1 -1/2 INCH BY 1/8 INCH STEEL ANGLE FRAMES AT EACH SIDE OF OPENING. THE ANNULAR SPACE BETWEEN DUCT AND
ANGLE FRAMES SHALL BE CAULKED WITH SILICONE SEALANT OR FIREPROOFED AS REQUIRED BY THE ASSEMBLY FIRE RATING.
CONTRACTOR TO PROVIDE FIRE OR COMBINATION FIRE / SMOKE DAMPERS AT EACH PENETRATION WHERE REQUIRED BY CODE.
8. ALL TRAVERSE JOINTS AND SEAMS IN SUPPLY AIR DUCT SHALL BE SEALED AIR TIGHT WITH DAP CMC DUCT SEALER.
JOINTS ALSO SHALL BE RIVETED OR CONNECTED WITH SHEET METAL SCREWS.
9. SO FT ELAS T M R BUTYL GASKETS WITH ADHESIVE BACKING SHALL BE USED TO SEAL FLANGED JOINTS.
10. DUCT TRANSITIONS SHALL NOT EXCEED 30 DEGREES SLOPE EXCEPT AS SPECIFICALLY NOTED OTHERWISE.
11. PROVIDE ACCESS TO ALL MOTORIZED DAMPERS, FIRE DAMPERS, FIRE SMOKE DAMPERS, CONTROLS AND OTHER ITEMS
IN DUCTWORK THAT REQUIRE SERVICE OR INSPECTION. IF THE ACCESS PANEL LOCATION IS EXPOSED TO THE SALES AREA, IT
MUST BE APPROVED BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO INSTALLATION. LAY -IN SUPPLY AND RETURN AIR
DIFFUSERS, GRILLES AND REGISTERS WITH PLASTER FRAMES MAY BE USED AS ACCESS LOCATIONS.
12. ALL BRANCHES AND TAKEOFFS SHALL BE EQUIPPED WITH MANUAL VOLUME CONTROLLING DEVICES HAVING AN INDICATING
AND LOCKING DEVICE.
I, FLEXIBLE CONNECTIONS
1. FLEXIBLE COLLARS SHALL BE PROVIDED IN ALL CONNECTIONS BETWEEN VIBRATING EQUIPMENT (FANS, ROOFTOP UNITS,
WATER SOURCE HEAT PUMPS, AIR HANDLERS, FAN POWERED VAV BOXES, ETC.) AND DUCTS OR CASINGS. ALSO PROVIDE
FLEXIBLE CONNECTIONS WHERE DUCTS CROSS BUILDING EXPANSION JOINTS.
2. FLEXIBLE CONNECTIONS SHALL BE CONSTRUCTED OF NEOPRENE - COATED FLAMEPROOF FABRIC. PROVIDE ADEQUATE JOINT
FLEXIBILITY TO ALLOW FOR MOVEMENT AND PREVENT THE TRANSMISSION OF VIBRATION.
3. FLEXIBLE CONNECTIONS ARE TO BE RATED FOR THE OPERATING PRESSURE OF THE SYSTEM,
4. FINAL CONNECTIONS TO EXHAUST FAN(S) SHALL BE WITH A HEAVY AIRTIGHT ACID RESISTANT FIRE RETARDANT
FIBERGLASSED NEOPRENE CONNECTOR, A MINIMUM OF SIX (6) INCHES IN LENGTH. THE CONNECTOR SHALL BE FASTENED TO
EQUIPMENT AND DUCT WITH TWO FLEXIBLE REMOVABLE BRASS STRAPS OR ALTERNATE APPROVED METHOD.
J. THERMOSTATS
A. MOUNT THERMOSTATS 4' -0" (ADA COMPLYING), THERMOSTAT SENSORS 5' -0" ABOVE FINISHED FLOORS AND SET DATE,
TIME, TEMPERATURE, ETC. TURN OVER OPERATING INSTRUCTIONS TO TENANT REPRESENTATIVE.
B. THERMOSTATS SHALL BE PROVIDED WITH KEY OPERATED SECURITY COVERS AND DESCRIPTIVE NAMEPLATES.
K. FIRE DAMPERS. SMOKE DAMPERS
1. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL FIRE DAMPERS AS REQUIRED BY LANDLORD AND / OR TENANT
CRITERIA AND / OR CODES. HAVING JURISDICTION. ALL FIRE DAMPERS SHALL COMPLY WITH THE REQUIREMENTS OF THE
BOARD OF FIRE UNDERWRITERS, THE LOCAL FIRE MARSHAL AND SHALL BE LABELED AND APPROVED BY UNDERWRITERS
LABORATORIES.
2. FIRE DAMPERS SHALL HAVE THE BLADES OUT OF THE AIR STREAM AND A 165 DEGREE F FUSIBLE LINK.
3. PROVIDE ALL NECESSARY FRAMING AND SLEEVES FOR DAMPER MOUNTING PER UL AND CODE REQUIREMENTS.
4. PROVIDE DUCT ACCESS DOORS IN AN ACCESSIBLE LOCATION FOR ALL FIRE DAMPERS. DOOR IS TO BE 20 GAUGE
GALVANIZED DOOR WITH QUICK - OPENING LATCH AND PIANO HINGE.
5. WHERE REQUIRED BY LOCAL CODES, LANDLORD AND IF INDICATED ON DRAWINGS, PROVIDE UL555S SMOKE DAMPER WITH
FIRE /HEAT /SMOKE SENSOR, REVERSIBLE MOTOR AND INTERLOCK WITH FIRE ALARM SYSTEM.
L FLEXIBLE AIR DUCT
1. FLEXIBLE DUCT FOR CONNECTIONS SHALL BE A FACTORY FABRICATED ASSEMBLY CONSISTING OF AN INNER SLEEVE,
INSULATION AND AN OUTER MOISTURE BARRIER. THE INNER SLEEVE SHALL BE CONSTRUCTED OF A CONTINUOUS VINYL
COATED SPRING STEEL WIRE HELIX FUSED TO A CONTINUOUS LAYER OF FIBERGLASS IMPREGNATED AND COATED VINYL. A 1
1/4" THICK LAYER OF INSULATING BLANKET OF FIBERGLASS WOOL SHALL ENCASE THE INNER SLEEVE AND BE SHEATHED
WITH AN OUTER MOISTURE BARRIER OF A BIDIRECTIONAL REINFORCED METALIZED VAPOR BARRIER. THE FLEXIBLE DUCT SHALL
BE RATED FOR A MAXIMUM WORKING VELOCITY OF 6000 FPM AND SHALL BE LISTED BY THE UNDERWRITERS LABORATORIES
UNDER THEIR UL -181 STANDARDS AS A CLASS 1 DUCT AND SHALL COMPLY WITH NFPA STANDARD - 90A. THE FLEXIBLE
DUCT SHALL BE THERMAFLEX M -KC OR APPROVED EQUIVALENT. FLEXIBLE DUCT SHALL ROUTE FROM SHEET METAL DUCTWORK
TO CEILING DIFFUSERS ONLY. THERE SHALL BE NO EXPOSED FLEXIBLE DUCT.
2. FLEXIBLE AIR DUCT MAY ONLY BE USED IN VERTICAL APPLICATIONS WITH PRIOR APPROVAL FROM THE TENANTS
CONSTRUCTION MANAGER.
3. FLEXIBLE DUCT SHALL NOT EXTEND OVER 5 FEET IN LENGTH AT ANY ONE LOCATION.
M. SUPPLY AND RETURN AIR TAKEOFF FITTINGS
A. RECTANGULAR DUCT
1, PROVIDE 45 DEGREE RECTANGULAR TAKEOFFS FROM MAIN DUCTWORK TO RECTANGULAR BRANCHES.
B. SPIRAL DUCT
1. PROVIDE SADDLE OR DIRECT CONNECTION OF A BRANCH DUCT INTO A LARGER DUCT. THE DIAMETER OF THE BRANCH
SHALL NOT EXCEED TWO THIRDS OF THE DIAMETER OF THE MAIN. PROTRUSIONS INTO THE MAIN ARE NOT ALLOWED.
N. DAMPERS
1. PROVIDE MANUAL LOCKING QUADRANT VOLUME CONTROL DAMPERS WITH HANDLE OPERATORS IN EACH BRANCH DUCT AND
AS SHOWN ON PLANS TO FACILITATE AIR BALANCING.
2. WHERE ACCESS TO BALANCING DAMPER IS RESTRICTED OR IN AREAS WITH SHEET ROCK CEILINGS, YOUNG REGULATORS
SHALL BE USED.
•
3. ALL RECTANGULAR DAMPERS IN OUTSIDE AIR AND RELIEF AIR DUCTS ARE TO BE OPPOSED BLADE TYPE. ALL RECTANGULAR
DAMPERS IN RETURN AIR DUCTS TO BE PARALLEL BLADE TYPE. ALL OUTSIDE AIR DUCT DAMPERS MUST ALSO BE OF THE
LOW LEAKAGE TYPE.
4. ALL MOTORIZED DAMPERS NOT FURNISHED WITH EQUIPMENT ARE TO BE HONEYWELL DAMPERS.
0. DIFFUSERS. GRILLES AND REGISTERS
1. PROVIDE DIFFUSERS, GRILLES AND REGISTERS AS SCHEDULED. DEVICES 10 BE COMPLETE WITH FRAMES AND ALL
ACCESSORIES. ALL DIFFUSERS, GRILLES AND REGISTERS IN SHEET ROCK CEILINGS TO BE PROVIDED WITH PLASTER FRAMES.
FINISH TO BE COORDINATED WITH INTERIOR FINISHES.
2. INSTALL ALL AIR DEVICES AS LOCATED ON THE ARCHITECTURAL REFLECTED CEILING PLAN OR THE MECHANICAL PLAN.
P. DUCTWORK INSULATION
NEW SUPPLY AIR TWO RK WITHIN 10' OF HVAC UNIT SHALL ACOUSTICALLY 1. ALL EW SU LY AND RETURN AI DUCTWORK 0 S LL BE COOS CALLY LINED. DUCT SIZES
SHOWN ON THE DRAWING ARE INTERNAL FREE AREA SIZES. INTERNAL LINER SHALL BE 1 1/2" THICK DUCT LINER
EQUIVALENT TO JOHNS MANVILLE "PERMACOTE LINACOUSTIC" ( "R VALUE" = 6.3) AND SHALL BE APPLIED TO THE DUCTWORK
WITH FIRE RESISTIVE ADHESIVES AND CADMIUM OR COPPER PLATED MECHANICAL FASTENERS.
2. ALL OUTSIDE AIR AND UNEXPOSED DUCTWORK WITHIN BUILDING, EXCEPT WHERE ACOUSTICALLY LINED, SHALL HAVE 2 INCH,
FIBERGLASS DUCT WRAP INSULATION WITH FSK FACING EQUIVALENT TO JOHNS MANVILLE "MICROLITE XG TYPE 75" (INSTALLED
"R VALUE" = 5.6).
3. LEADING EDGES OF DUCT INSULATION SHALL BE OVERLAPPED BY ADJOINING INSULATION FOR 6" MINIMUM AND THEN
SEALED WITH FOIL VAPOR BARRIER ADHESIVE NE AN D DUCT MASTIC SO THAT NO FIBERGLASS INSULATION IS VISIBLE.
BLE.
4. ALL INSULATION ON EXISTING PIPING OR DUCTS THAT IS WETTED, DAMAGED, DISTURBED OR REMOVED SHALL BE REPLACED.
5. INSTALL IN SULA T ION PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS AND IN A CCO RD AN CE WITH
RECOGNIZED INDUSTRY PRACTICES. INSULATION MUST COMPLY WITH NFPA 90A:
6. ALL I N SULAT I ON SHALL HAVE A FLAME SPREAD RATING NOT MORE THAN 25 A SMOKE DEVELO P ED RATING OF NO
HIGHER THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM C 411 OR AS REQUIRED BY LOCAL CODES.
7. EXTERIOR SUPPLY AND RETURN DUCT INSULATION
A. SERVICE: RECTANGULAR, SUPPLY -AIR AND RETURN -AIR DUCTS.
1. MATERIAL: INSULATION BOARD, 6 PSF MINIMUM AND PLAIN FACING.
2. THICKNESS: 2 INCHES.
3. NUMBER OF LAYERS: TWO. TOTAL THICKNESS = 4'
4. VAPOR RETARDER REQUIRED: YES.
1. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AN D CONTRACTORS FOR A COMPLETE, SAFE INSTALLATION OF PLUMBING
WORK IN FULL CONFORMITY WITH REQUIREMENTS OF ALL AUTHORITIES HAVING JURISDICTION AS INDICATED ON DRAWINGS
AND /OR HEREIN SPECIFIED, INCLUDING IN GENERAL THE FOLLOWING:
2. SANITARY DRAINAGE CONNECTIONS TO PLUMBING FIXTURES AND EQUIPMENT REQUIRING SAME WITH FINAL CONNECTIONS TO
EXISTING PREINSTALLED OUTLETS PROVIDED BY PRIOR TENANT(S) OR LANDLORD. PLUMBER SHALL VERIFY EXACT LOCATION
OF WASTE PIPE OUTLET BEFORE SUBMITTING BID AND NOTIFY THE ARCHITECT OF ANY LOCATION DISCREPANCIES. PLUMBING
CONTRACTOR SHALL BE RESPONSIBLE FOR ANY CONCRETE SAWCUTTING REQUIRED TO MAKE THE FINAL CONNECTION TO THE
EXISTING WASTE PIPING OR CAPPED OUTLET(S). SAWCUTTING EXCAVATING BACKFILLING AND NEW CONCRETE ETE MUST MEET
WITH THE LANDLORD'S APPROVAL
A. SNAKE SANITARY FOR A DISTANCE OF 100 FEET AND
REPORT ANY BLOCKAGE.
B. TEST WATER PRESSURE TO INSURE MINIMUM OF 30 PSI.
3. COMPLETE VENT SYSTEM, ALL FIXTURES INDIVIDUALLY VENTED WITH FINAL CONNECTION THROUGH ROOF OR TO EXISTING
LANDLORD SUPPLIED COMMON VENT. ROOF PENETRATION AND FLASHING TO BE PERFORMED BY LANDLORD'S ROOFER (IF
APPLICABLE). COST OF ROOF PENETRATION AND FLASHING TO BE PART OF THIS CONTRACT, UNLESS NOTED OTHERWISE IN
BID PROPOSAL (IF APPLICABLE).
4. DOMESTIC WATER SUPPLY SYSTEM INCLUDING CONNECTION TO EXISTING CAPPED OUTLET AND FINAL CONNECTIONS TO
PLUMBING FIXTURES AND EQUIPMENT REQUIRING SAME. VERIFY EXACT LOCATION AND SIZE BEFORE SUBMITTING BID.
5. INSULATION OF ALL HOT AND COLD WATER PIPING INCLUDING UNDER DE LAVATORY A .D.A. PIPE WRAPPINGS.
6, FURNISH AND INSTALL WATER METER (IF APPLICABLE) ACCESSIBLE TO UTILITY COMPANY OR LANDLORD'S REPRESENTATIVE
FOR MONITORING WATER BUT METER SHOULD IN NO WAY BE IN THE PATH OF THE A.D.A. / CABO -ANSI , 5'-0" CIRCULAR
PATTERN.
A. INORGANIC GLASS FIBERS PREFORMED AND BONDED BY THERMOSETTING RESIN. MUST COMPLY WITH ASTM C 612,
TYPE 1A AND 1B,
1 KNAUF INSULATION OR APPROVED EQUIVALENT.
ULA Q
A. INSULATION INSTALLED OUTDOORS: FLAME SPREAD RATING OF 25 OR LESS AND SMOKE DEVELOPED RATING OF 50
OR LESS.
B. APPLY INSULATION AS FOLLOWS:
A. APPLY TWO -LAYER INSULATION WITH JOINTS TIGHTLY BUTTED AND STAGGERED AT LEAST 3 INCHES. SECURE LAYERS
WITH ADHESIVE, MECHANICAL FASTENERS OR BANDING. FASTENERS SHALL BE LOCATED A MAXIMUM OF 3' FROM EACH EDGE
AND NO GREATER THAN 12" APART.
B. ON EXPOSED APPLICATIONS, FINISH INSULATION WITH A SKIM COAT OF MINERAL- FIBER, HYDRAULIC - SETTING
CEMENT TO SURFACE OF INSTALLED INSULATION. WHEN DRY, APPLY FLOOD COAT OF LAGGING ADHESIVE AND PRESS ON ONE
LAYER OF GLASS CLOTH OR TAPE. OVERLAP EDGES AT LEAST 1 INCH (25 MM). APPLY FINISH COAT OF LAGGING ADHESIVE
OVER GLASS CLOTH OR TAPE. THIN THE FINISH COAT TO ACHIEVE SMOOTH FINISH. OUTDOOR JACKET: POLYGUARD PRODUCTS.
INC. 'ALUMAGUARD 60' OR MFM BUILDING PRODUCTS CORP. 'FLEXCLAD 400 ":
Q. SYSTEM CLEANOUT
1. UPON COMPLETION OF INSTALLATION, CLEAN ENTIRE SYSTEM BEFORE INSTALLING AIR OUTLETS. CONTRACTOR TO PROVIDE A
CERTIFICATION THAT CLEANING WAS ACCOMPLISHED PRIOR TO PROJECT CLOSEOUT.
2. FILTERS MUST BE IN UNITS AT ANY TIME FANS ARE OPERATED.
R. SYSTEM TESTING. ADJUSTING AND BALANCING
1. TESTING, ADJUSTING AND BALANCING OF ALL WORK SHALL BE COMPLETED BY AN INDEPENDENT CONTRACTOR WHO IS
CURRENTLY LICENSED BY THE ASSOCIATED AIR BALANCING COUNCIL (AABC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU
(NEBB). NO OTHER BALANCE RE P ORTS WI LL BE REVIEWED OR ACCEPTED. ALL BALANCING WORK MU ST BE CO MP LETE AND
DONE IN ACCORDANCE WITH THE MOST RECENT STANDARDS OF THEIR SOCIETY. PAYMENT OF ALL COSTS FOR TESTING SHALL
BE MADE BY THE HVAC CONTRACTOR.
2. THE CONTRACTOR SHALL INSTALL NEW FILTERS IN ALL UNITS PRIOR TO THE AIR BALANCING. THE COMPLETE AIR BALANCE
SHALL TAKE PLACE WITH OUTSIDE AIR DAMPERS I N MINIMUM POSITION,
3. BALANCE AIR AND WATER QUANTITIES TO WITHIN PLUS OR MINUS 5 PERCENT OF THAT INDICATED ON THE , DRAWINGS. ANY
REQUIRED CHANGES IN SHEAVES, BELTS, PULLEYS OR THE ADDITION OF DAMPERS REQUIRED TO ACHIEVE SPECIFIED FLOW
RATES SHALL BE PROVIDED BY THE HVAC CONTRACTOR WITH NO ADDITIONAL COST TO THE TENANT.
4. THE BALANCE REPORT SHALL INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION:
A) AABC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF BALANCING CONTRACTOR.
B) INSTRUMENTATION LIST WITH LAST CALIBRATION DATES.
C) MAKE AND MODEL NUMBERS OF ALL HVAC EQUIPMENT TESTED.
D) AIR CFM AND STATIC PRESSURE READINGS (DISCHARGE AND SUCTION) AS MEASURED BY PITOT TUBE DUCT TRAVERSE AT
THE UNITS.
E) MOTOR NAMEPLATE DATA WITH ACTUAL FIELD VOLTAGE AND AMPERAGE READINGS FOR EACH LEG.
F) MOTOR AND FAN RPM, SHEAVE SIZES AND BELT SIZES AND LENGTHS.
G) OUTSIDE, RETURN, MIXED AND SUPPLY AIR TEMPERATURES AT FULL COOLING.
H) WATER BALANCE DATA INCLUDING GPM WITH INLET AND OUTLET TEMPERATURE AND PRESSURE READINGS.
I) MAKE AND MODEL NUMBERS OF ALL AIR DISTRIBUTION EQUIPMENT.
J) FINAL BALANCED AIR VOLUMES AT ALL OUTLETS (INCLUDING RETURNS WHERE DUCTED).
K) INDEXED PLAN WITH DIFFUSER AND RETURN LOCATIONS.
5. ALL CONTROL SEQUENCES SHALL BE TESTED AND OPERATING STATUS RECORDED IN THE REPORT.
6. THREE COPIES OF THE BALANCE REPORT SHALL BE SUBMITTED THROUGH THE GENERAL CONTRACTOR TO THE TENANT'S
CONSTRUCTION MANAGER FOR REVIEW AND COMMENT.
7. THE BALANCING CONTRACTOR SHALL PERFORM ALL APPLICABLE TESTING AND BALANCING FUNCTIONS REQUIRED FOR THE
SYSTEM DESIGNED IN THESE DRAWINGS. THE BALANCING CONTRACTOR SHALL RECHECK ANY ITEMS THAT THE TENANT DEEMS
NECESSARY AT NO ADDITIONAL COST TO THE TENANT.
8. FINAL BALANCE REPORT SHALL BE INCLUDED IN THE OPERATION AND MAINTENANCE MANUAL.
S. FINAL HVAC INSPECTIONS
1. ASIDE FROM NORMAL INTERIM INSPECTIONS OF WORK IN PLACE, THE TENANT SHALL HAVE THE RIGHT TO HAVE AN
INDEPENDENT HVAC CONTRACTOR INSPECT THE FINISHED HVAC INSTALLATION UPON COMPLETION FOR COMPLIANCE WITH THE
PLANS, SPECIFICATIONS AND CODES. THE INSTALLING CONTRACTOR WILL BE RESPONSIBLE TO BRING ALL ITEMS REPORTED BY
THE INDEPENDENT HVAC CONTRACTOR UP TO PLANS AND SPECIFICATIONS REQUIREMENTS AT NO ADDITIONAL COST TO THE
TENANT.
T. INDOOR AIR QUALITY
1. NO ANALYSIS HAS BEEN MADE WITH REGARD TO SOURCES OR POTENTIAL SOURCES OF INDOOR OR OUTDOOR AIR
CONTAMINANTS OR LEVELS OF CONTAMINATION.
2. IT IS THE RESPONSIBILITY OF THE GENERAL AND MECHANICAL CONTRACTOR TO INFORM THE TENANT'S REPRESENTATIVE,
LANDLORD AND TENANT'S ARCHITECT IF ANY SOURCE OR POTENTIAL SOURCE OF INDOOR AIR CONTAMINATION 15 IDENTIFIED.
3. PRIOR TO ENCLOSING SPACES SUCH AS PLUMBING CHASES, AIR SHAFTS AND RETURN AIR PLENUMS CLEAN ALL AREAS
THOROUGHLY. THE CONTRACTOR SHALL GUARANTEE THAT THE PLENUM CHAMBER USED FOR RECIRCULATING OF AIR WILL BE
OF TIGHT CONSTRUCTION AND THAT ALL SOURCES OF CONTAMINATION FROM TRAPS, SOIL STACKS, DOWNSPOUTS, VENTS.
EXHAUST DISCHARGES AND OTHER SOURCES WILL BE ENCLOSED SO THAT NO CONTAMINATED AIR WILL BE RECIRCULATED.
4. PRIOR TO COMMENCING CONSTRUCTION ACTMTIES SHUT OFF THE HVAC SYSTEM, BLOCK OFF ALL AIR GRILLS, DIFFUSERS
AND OTHER OPENINGS OUTSIDE THE IMMEDIATE CONSTRUCTION AREA. OPENINGS TO ADJACENT TENANT SPACES SHALL BE
COVERED WITH FILTER MEDIA TO PREVENT DUST AND OTHER AIRBORNE CONTAMINANTS FROM PASSING TO ADJOINING SPACES.
5. CONTRACTOR TO INSTALL TEMPORARY EXHAUST SYSTEM TO VENTILATE CONSTRUCTION SITE AND KEEP SITE UNDER SLIGHT
NEGATIVE PRESSURE DURING ALL HOURS OF CONSTRUCTION, EVEN IF AFTER NORMAL BUSINESS HOURS.
6. CONTRACTOR TO INSTALL TEMPORARY BARRIERS TO PROTECT ADJACENT SPACES FROM DUST, PARTICULATES, VAPORS AND
NOISE. WHERE TEMPORARY BARRIERS ARE INSTALLED ALWAYS MAINTAIN FIRE EXITS AND EXITWAYS. 11 -30 -06
PLUMBING SPECIFICATIONS
1. IT IS THE INTENT OF THESE SPECIFICATIONS TO PROVIDE A COMPLETE INSTALLATION FOR FINISHED WORK, TESTED AND
READY FOR OPERATION. THE WORK THROUGHOUT SHALL BE EXECUTED IN THE BEST AND MOST THOROUGH MANNER UNDER
THE DIRECTION OF AND TO THE SATISFACTION OF THE OWNER.
2. ALL MATERIALS REQUIRED FOR THIS WORK SHALL BE NEW, UNUSED. BEST OF ITS RESPECTIVE KINDS, AND FREE FROM
DEFECTS AND OF FIRST CLASS QUALITY. BASIS OF QUALITY SHALL BE LATEST STANDARDS OF ASTM, ANSI FEDERAL
SPECIFICATIONS OR OTHER ACCEPTABLE STANDARDS.
3. THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR THEIR WORK UNTIL ITS COMPLETION AND FINAL ACCEPTANCE
AND SHALL REPLACE ANY OF THE SAME WHICH MAY BE DAMAGED, LOST OR STOLEN WITHOUT ADDITIONAL COST TO THE
OWNER.
4. THE PLUMBING CONTRACTOR SHALL GUARANTEE ALL WORK PERFORMED AND MATERIALS INSTALLED TO BE FREE FROM
INHERENT DEFECTS AND SHALL KEEP IN REPAIR AND REPLACE ANY DEFECTIVE MATERIALS OF WORKMANSHIP, FREE OF
COST TO THE TENANT (OWNER) FOR A PERIOD OF ONE (1) YEAR AFTER THE OPENING FOR BUSINESS.
5. ALL WORK SHALL BE DONE ACCORDING TO THE REQUIREMENTS OF ALL APPLICABLE CODES AND LEASE CRITERIA (IF
APPLICABLE) AND SHALL RECEIVE THE APPROVAL OF ALL AUTHORITIES HAVING JURISDICTION. PREPARE ALL REQUIRED
DOCUMENTS, DRAWINGS AND PERFORM ALL REQUIRED TESTS AND PAY ALL REQUIRED CHARGES TO OBTAIN THESE
APPROVALS.
6. CONTRACTOR SHALL BE HELD TO HAVE EXAMINED THE SITE FOR THE WORK BEFORE HAVING SUBMITTED A PROPOSAL NO
ADDITIONAL COMPENSATION WILL BE ALLOWED FOR CONDITIONS FOUND DURING THE COURSE OF THE CONTRACT.
7. THIS CONTRACTOR MUST PROVIDE LANDLORD'S CONSTRUCTION REPRESENTATIVE WITH COPIES OF REQUIRED INSURANCE
AND COPIES TO BE FURNISHED TO THE OWNER BEFORE COMMENCING WORK:
8. SUBMIT THREE (3) SETS OF SHOP DRAWINGS IDENTIFIED WITH PROJECT NAME OF THE FOLLOWING (1) ELECTRIC HOT
WATER HEATER (2) PLUMBING FIXTURES AND TRIM. CONTRACTOR SHALL SUBMIT SHOP DRAWING OF PIPING LAYOUT TO THE
OWNER FOR THEIR FILE.
9. THE PLUMBING CONTRACTOR IS A SUBCONTRACTOR OF THE TENANT'S GENERAL CONTRACTOR.
10. NOTCHING AND BORING OF STRUCTURAL STEEL MEMBERS IS NOT PERMITTED. WHEN HANGING FROM STRUCTURAL STEEL
ONLY HANG FROM TOP FLANGE OF BEAMS AND TOP CHORDS ONLY AT PANEL POINTS OF JOISTS / TRUSSES.
I. WORK RESPONSIBILITY.
III. MATERIALS
1. DRAINAGE AND VENT PIPING: EXTRA HEAVY HUB AND SPIGOT CAST IRON RUBBER GASKETS ON SOI L WITH R UBBE G S ETS CONFORMING TO
ASTM C564. NO -HUB CAST IRON TO HAVE HEAVY DUTY, TYPE 304 STAINLESS STEEL COUPLINGS CONFORMING TO ASTM A
666 TYPE 304 STAINLESS I TYPE 304 STAINLESS STEEL BANDS AND E 30 LESS STEEL SHIELD, E 30 S LESS S EE 8 D NPS 1 1 TO NPS 4
L S D SLEEVE. S /2 0 S 3
WIDE SHIELD WITH 4 BANDS; NPS 5 " TO �NPS 10 ": 4" WIDE BAND MTH 6 BANDS.
2. WATER PIPING BELOW SLAB: TYPE K HARD COPPER TUBING, WITH CAST BRONZE OR WROUGHT COPPER SOLDER JOINT
FITTINGS USING 95 -5 SOLDER. WATER PIPING ABOVE SLAB: TYPE L COPPER TUBING USING SILVER SOLDER.
3. WATER HAMMER ARRESTORS: PROVIDE ON HOT AND COLD WATER BRANCHES TO FIXTURES, J. R. SMITH HYDROTROL
MODEL 5020 FOR UP TO 60 FIXTURE UNITS.
4. VALVES: GATE VALVE WATTS SERIES B -3000, CHECK VALVE WATTS SERIES B -5000, BALL VALVE WATTS SERIES B6080
OR B6081 FULL PORT. ALL VALVES 1/2" TO 2" BRONZE BODY.
5. PRESSURE AND TEMPERATURE RELIEF VALVE WATTS REGULATING CO. MODEL 10L.
6. PRESSURE REDUCING VALVE; WATTS SERIES 25AUB BRONZE BODY WITH INTEGRAL S/S STRAINER, SEALED CAGE FOR 1/2"
TO 2 1/2" DIA. TO 300 PSI.
7. PRESSURE GAUGE AMETEK DIV. OF U.S. GAUGE MODEL P5105, 3 1/2" DIAL, 1/4" STEM, ALUMINUM CA SE, BLACK FINISH.
8. AIR VENT: HOFFMAN /79 WATER MAIN VENT VALVE.
9. WATER METER HERSEY CO. MODEL 400 SERIES IIS.
10. VA CUU M RELIEF VA LVE WATTS M ODEL N3 6 M1 B RA SS BODY, 1/2" NPT LINE SIZE
11. TRAP PRIMER: PPP MODEL P1 -500 UP TO FOUR CONNECTIONS. OPTIONAL DISTRIBUTION UNIT 3 AND 2 FOR REQUIRED Q '
FOUR DRAIN LINES.
12. MIXING VALVE WATTS SERIES MMV MIXING VALVE 1/2" LINE SIZE.
1A P 1/2" 3 BACKFLOW REVENTOR: WATTS SERIES 719 DOUBLE CHECK VALVE ASSEMBLY BACKFLOW PREVENTOR. LINE SIZE 1/2 TO
2" TO MATCH INLET WATER LINE SIZE.
IV. INSULATION
1. ALL HOT AND COLD WATER PIPING AND FITTINGS SHALL BE INSULATED WITH 1" THICK RIGID FIBERGLASS WITH VAPOR
BARRIER UNIVERSAL JACKET PASTED WITH VAPOR BARRIER CEMENT. VAPOR BARRIER NOT REQUIRED ON HOT WATER PIPING.
2. ALL ADA CONFORMING, WHEELCHAIR ACCESSIBLE LAVATORY P -TRAP AND ANGLE VALVE ASSEMBLIES TO BE COVERED WITH
THE MOLDED, ANTIMICROBIAL TRUBRO, INC "LAV- GUARD" UNDERSINK PROTECTIVE PIPE COVER MODEL #103.
V SPECIFIC PLUMBING SPECIFICATIONS
1. INSTALL NEW ONLY IF EXISTING DOES NOT MEET CURRENT ADA /CABO -ANSI (AS APPLICABLE) STANDARDS, OR IS
DAMAGED, NOT IN WORKING ORDER OR NOT EXISTING AS APPLICABLE.
2. IT IS THIS CONTRACTOR'S RESPONSIBILITY TO SUPPLY HANDICAPPED TOILET FIXTURES, IF REQUIRED BY CODE OR NOTED
ON THE DRAWINGS, UTILIZING THE SPECIFICATION ABOVE AS A STANDARD AND MEETING CODE REQUIREMENTS. SPACING OF
FIXTURES TO BE COORDINATED WITH THE GENERAL CONTRACTOR AS WELL AS THE PLUMBING INSPECTOR'S REQUIREMENTS.
3. PVC PIPING IS NOT PERMITTED ABOVE GRADE.
4. INSTALL PLUMBING VENTS MINIMUM 10' -0" FROM BUILDING AIR INTAKES.
5. COSTS FOR WORKING BELOW TENANT'S SLAB IN ANOTHER TENANT'S SPACE.
6. INSTALLATION OF FLOOR DRAIN , BACKFLOW PREVENTER ( IF REQ. BY CODE ) AS PER LANDLORD REQUIREMENT
AND
CLEANOUT PER LOCAL CODE. COORDINATE ALL LOCATIONS WITH OPERATIONS MANAGER.
7. COMPLETE NATURAL GAS PIPING SYSTEMS (AS APPLICABLE, REFER TO PLANS)
II. GENERAL ITEMS
1. SLEEVES: PROVIDE #22 GAUGE GALVANIZED IRON PIPE SLEEVES FOR PIPING THROUGH WALLS AND FLOOR, PACK WITH
NON- ASBESTOS ROPE AND FILL WITH EXPANDO NON- SHRINKING CEMENT.
2. ESCUTCHEONS: PROVIDE EXPOSED PIPING, BOTH BARE AND COVERED, MTH CP CAST BRASS ESCUTCHEONS WHERE
PASSING THROUGH FLOORS, CEILINGS, WALLS OR PARTITIONS:
3. HANGERS AND SUPPORTS: SUPPORT HORIZONTAL DRAINAGE PIPING AT LEAST EVERY 5 FEET OR AT EVERY HUB, COPPER
TUBING EVERY 7 FEET AND STEEL PIPE EVERY 10 FEET WITH "CLEVIS" HANGERS AND INSULATION PROTECTION SHIELDS.
PIPING SHALL NOT BE SUPPORTED FROM BRIDGING OR OTHER PIPING. ONLY SUPPORT FROM TOP FLANGES OF BEAMS AND
TOP CHORDS AT PANELS OF JOIST AND TRUSSES, PROVIDE SWAY AND SEISMIC BRACING WHERE REQUIRED BY CODES.
4. TEST: TEST PIPING AND PROVE TIGHT FOR AT LEAST TWO HOURS IN ACCORDANCE WITH REQUIREMENTS OF AUTHORITIES
HAVING JURISDICTION AND /OR AS SPECIFIED. TEST SHALL BE PERFORMED IN THE PRESENCE OF OWNER'S REPRESENTATIVE
AND LOCAL INSPECTOR. TEST SHALL BE REPEATED IF NECESSARY UNTIL FINAL APPROVAL OF SYSTEM IS OBTAINED.
A. TEST DRAINAGE AND VENT PIPING BY FILLING WITH WATER TO
OVERFLOWING AT ROOF, WATER LEVEL TO REMAIN.
B. TEST WATER PIPING WITH WATER 1 1/2 TIMES THE WORKING
PRESSURE.
5. STERILIZATION OF DOMESTIC WATER SYSTEM: BEFORE BEING PLACED IN SERVICE, ALL WATER LINES SHALL BE
CHLORINATED TO TH E SATISFACTION OF THE ARCHITECT OR LANDLORD'S S REPRESENTATIVE, I
N ACCORDANCE WITH A.W.W.A,
SPECIFICATION C601 -53T.
6. SLOPE WASTE LINES 2 INCHES AND SMALLER NOT LESS THAN 1/4 INCH PER FOOT. SLOPE LARGER MAINS NOT LESS
THAN 1/8 INCH PRF PER 00T .
7. INSTALL A CLEANOUT AT BASE OF EACH SOIL STACK, AT EACH CHANGE IN DIRECTION, AT INTERVALS NOT OVER 50 FEET
AND ELSEWHERE AS SHOWN ON DRAWINGS OR REQUIRED BY LOCAL CODE. CLEANOUTS SHALL NOT BE INSTALLED IN PUBLIC
AREAS WITHOUT SPECIFIC PERMISSION BY TENANTS CONSTRUCTION MANAGER.
1
REVD .�
�OQG FOR
COMPlr
Apao ANC.
AN
Girl!
City of
BUILDING Tukwila
nn
RECEIVED
FEB 11.2011.
PERMIT CENTER
20
SPECIFICATIONS
cp
t:),o
an
rind
p.4
ra..4
U
U
N
IN 1,2
cv
•tt
W LL
Z=
u
W
1
LLI
1--
PROJECT TEAM:
Architect: Epoch Design Group, Inc.
p 8 p,
1 155 011vette Exec. Pkwy.
Suite 100
5t. Louis, MO 63132
TEL: 314.721 :1340
FAX: 314.721.0344
M. E. P. & F.P.
Engineer: Randall A. Nelson, P.E.
14817 West 95th Street
Lenexa, KS 66215
TEL: 913.322.5150
FAX: 913.322.5155
COPYRIGHT DISCLAIMER:
THIS DOCUMENT !SINE PROPERTY OP EPOCH DESION GROUP,
COPYRIGHTED AS DATED, ALL RIGHTS RESERVED. AUTHORIZATION
FROM EPOCH DESIGN GROUP FOR USE OP THIS DOCUMENT IS
NOT TRANSFERABLE. THE RECIPIENT OF THIS DOCUMENT IS
HEREBY ADVISED THAT IT IS RELEASED FOR USE UNDER THE
FOLLOWING TERMS AND CONDITIONS,
THE DOCUMENT IS TO E! USED ONLY IN CONJUNCTION WITH
THIS PROJECT. REUSE OF ANY PORTION OF THE DOCUMENT IN
ANY OTHER CIRCUMSTANCE CONSTITUTES COPYRIGHT
INFRINGEMENT.
THE DOCUMENT IS FOR DEMON INTENT AND INFORMATION ONLY,
AND DOES MILLCONSTITUT! AS -BUILT CONDITIONS. THE
RECIPIENT RETAINS 7MBLIGATION TO VERIFY THE CONDITIONS
OF THE SUIJ!CT PROPERTY AND TO COMPLETELY COORDINATE
ALL DIMENSIONS, FABRICATION METHODS, RELATED AND
INTEGRATED SYSTEMS, ETC, WITH RESPECT TO ALL ASPECTS OF
THE WORK.
EPOCH DESIGN GROUP MAKES NO WARRANTY AS TO THE
SUITABILITY OF THE DOCUMENT FOR THE RECIPIENT'S INTENDED
US!. THE RECIPIENT SPECIFICALLY AGREES TO WAIVE AND TO
INDEMNIFY AND DEPEND ANY AND AL GAMS AGAINST EPOCIN
DESIGN GROUP, ITS CONSULTANTS, MY OP ITS RELATED ENTRIES,
VENDORS, OR CONTRACTORS, FOR ANY LOSS INCURRED AS A
RESULT OP PROPER OR IMPROPER USE OF THIS DOCUMENT.
THE RECIPIENT AGREES TO RETURN OR DESTROY THIS DOCUMENT
UPON COMPLETION OK TERMINATION OP WORK PERFORMED IN
C • JUNCTION WITH THIS PROJECT.
PROJECT TITLE:
N Revision Description Date
SHEET TITLE:
MECHANICAL
SPECIFICATIONS
PROJECT NO.: SHEET NUMBER:
10313
DRAWN BY:
3.0
ISSUE ED DATE: M
JCC
0
1/26/11