HomeMy WebLinkAboutPermit M11-075 - WESTFIELD SOUTHCENTER MALL - PAC SUNPAC SUN 650 SOTJTHCENTER MALL Mi 1 -075 City oftukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 -431 -3670 Inspection Request Line: 206- 431 -2451 Web site: http: / /www.TukwilaWA.gov MECHANICAL PERMIT Parcel No.: 9202470010 Address: 650 SOUTHCENTER MALL TUICW Project Name: PAC SUN Permit Number: M11 -075 Issue Date: 08/22/2011 Permit Expires On: 02/18/2012 Owner: Name: WESTFIELD PROPERTY TAX DEPT Address: PO BOX 130940 , CARLSBAD CA 92013 Contact Person: Name: AMY DIEKEVERS Address: 75 60 ST SW , WYOMING MI 49548 Email: AMYD @PRECISIONPERMITS.COM Phone: 616- 493 -9334 Contractor: Name: HARDESTY & ASSOCIATES INC Phone: 760 - 944 -0499 Address: 1991 VILLAGE PARY WAY 180 , ENCINITAS, CA 92024 Contractor License No: HARDEAI066PP Expiration Date: 11/17/2011 DESCRIPTION OF WORK: TENANT IMPROVEMENT TO INCLUDE (1) NEW NOMIAL 10 -TON SPLIT SYSTEN HEAT PUMP, ALL NEW DUCT DISTRIBUTION AND (2) TOILET EXHAUST FANS. Value of Mechanical: $11,500.00 Type of Fire Protection: UNKNOWN Electrical Service Provided by: Permit Center Authorized Signature: Fees Collected: $330.56 International Mechanical Code Edition: 2009 Date: Mini l I hereby certify that I have read and ed this permit and know the same to be true and correct. All provisions of law and ordinances governing this work will be complied with, hether specified herein or not. The granting of this permit does not pr . - to give authority to violate or cancel the provisions of any other state or local laws regulating construction or the performance of work. am authorized to sign and obtain this mechanical permit and agree to the conditions on the back of this permit. Signature: % , -- -. " Print Name: J 037--/ '/t u Q/'3 Date: 8-2 2 —// This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended or abandoned for a period of 180 days from the last inspection. doc: IMC -4/10 M11-075 Printed: 08 -22 -2011 • • PERMIT CONDITIONS Permit No. M11-075 1: ** *BUILDING DEPARTMENT CONDITIONS * ** 2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the Building Official. 3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Thkwila Permit Center (206/431- 3670). 4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to start of any construction. These documents shall be maintained and made available until final inspection approval is granted. 5: Readily accessible access to roof mounted equipment is required. 6: All construction shall be done in conformance with the approved plans and the requirements iof the International Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code. 7: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground,iproperly cap the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks, wells, and other excavations. Final inspection approval will be determined by the building inspector based on satisfactory completion of this requirement. 8: Manufacturers installation instructions shall be available on the job site at the time of inspection. 9: All plumbing and gas piping work shall be inspected and approved under a separate permitiissued by the City of Thkwila Building Department (206- 431 - 3670). 10: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building Department (206- 431 - 3670). 11: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of the building code or of any other ordinances of the City :of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the Building Official from requiring the correction of errors in the construction documents and other data. 12: ** *FIRE DEPARTMENT CONDITIONS * ** 13: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the following concerns: 14: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051) (ALL FIRE ALARM COMPONENTS TO BE TIED TO THE MAIN MALL FIRE ALARM PANEL.) 15: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaceslwithin buildings shall be equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the air- moving equipment upon detection of smoke in the main return-air duct served by such equipment. Smoke detectors shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the manufacturer's installation instructions. (IMC 606.1, 606.2.1) 16: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051) 17: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051) 18: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051) 19: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC 104.2) doc: IMC -4/10 M11-075 Printed: 08 -22 -2011 20: An electrical permit from the CCf Tukwila Building Department Permit Cent4106- 431 -3670) is required for this project. 21: All electrical work and equipment shall conform strictly to the standards of the National Electrical Code. (NFPA 70) 22: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and #2051) 23: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of such condition or violation. 24: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at (206)575 -4407. doc: IMC -4/10 M11 -075 Printed: 08 -22 -2011 CITY OF TUKWILA Community Development Department Public Works Department Permit Center 6300 Southcenter Blvd., Suite 100 Tukwila, WA 98188 tzrklvila.wa. us Building Permit No. t)/- Mechanical Permit No. t t (' �. Plumbing/Gas Permit No. 11'07' Public Works Permit No. ; 1 Project No. (For office use only) Applications and plans must be complete in order to be accepted for plan review. Applications will not be accepted through the mail or by fax. * *Please Print ** SITE LOCATION Site Address: King Co Assessor's Tax No.: 26z 30q Floor: New Tenant: .....Yes Jh 5004 c-ev1 i /14 . Suite Number: Tenant Name: PAC— j Ll fJ yy Property Owners Name: VU' e-. Mailing Address: .2 toc) 3 0 ❑ ..No 4/L City q( e) /€a , State Zip CONTACT PERSON — ho do we contact when your permit is ready to be issued Name: Mailing Address: 7rJ (-r 014% c5 'I-- Day Telephone: l67 / el ("T 3 L,@) y bt!!Jl //1 c1 :4 / `'� it 5 tl «'3 y ,/c212 State Zip E -Mail Address: Cl C e -ec l.:' IC? f nh / 7: C lrtit_ Fax Number: (c) 1(o `-f 9 9 55 GENERAL CONTRACTOR INFORMATION — (Contractor Information for Mechanical (pg 4) for Plumbing and Gas Piping (pg 5)), Company Name: Mailing Address: City Day Telephone: Fax Number: Expiration Date: Contact Person: E -Mail Address: Contractor Registration Number: State Zip ARCHITECT OF RECORD — All plans must be wet stamped by Architect of Record Company Name: Mailing Address: �} j Contact Person: l C % l ���� /� d� d E -Mail Address: F City Day Telephone: Fax Number: State Zip Lit90 ci `t'6 ” 4/zoo ENGINEER OF RECORD All plans must be wet stamped by Engineer of Record Company Name: ' c ui / e eli•/ ' Mailing Address: IVY /31-k Contact Person: Jai *e 6 „'41v4- e E -Mail Address: PA0 .ell i, Ate- H:\Applications \Forms - Applications On Line\2009 Applications \1 -2009 - Permit Application. doc Revised' 1 -2009 bh City State Zip 60Z Zv /5 .5eJ Day Telephone: Fax Number: Page 1 of 6 BUILDING PERMIT INFOR1 .11ON 206 - 431 -3670 Valuation of Project (contractor's bid price): $ 196 000 Existing Building Valuation: $ Scope of Work (please provide detailed information): Tenant improvement of entire existing retail space including storefront, sales area, fitting rooms, stock room, toilet rooms, and hallway. Will there be new rack storage? W Yes 0.. No If yes, a separate permit and plan submittal will be required. to / /id?J >�ie/L)e ' — 'vr p %dis Provide All' Building Areas in Square Footage Below Ist Floor 2n° Floor Interior Remodel Addition to Existing Structure Type of Construction per IBC Type of Occupancy per IBC 3OSa.. c) d 3' Floor` Floors Basement Accessory Structure *. Attached Garage Detached Garage Attached Carport Detached Carport Covered Deck Uncovered Deck PLANNING DIVISION: Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches) *For an Accessory dwelling, provide the following: Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling: *Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence. Number of Parking Stalls Provided: Standard: Compact: Handicap: Will there be a change in use? ❑ Yes m No If "yes ", explain: FIRE PROTECTION /HAZARDOUS MATERIALS: m Sprinklers m Automatic Fire Alarm ❑ None ❑ Other (specify) Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes No If 'yes', attach list of materials and storage locations on a separate 8-1/2" x I1 " paper including quantities and Material Safety ata Sheets. SEPTIC SYSTEM ❑ On -site Septic System – For on -site septic system, provide 2 copies of a current septic design approved by King County Health Department. H:\Applications\Forms- Applications On Line\2009 Applications \I -2009 - Permit Application.doc Revised: 1 -2009 bh Page 2 of 6 MECHANICAL PERMIT..INF ATION 206- 431: = 3:670:: MECHANICAL CONTRACTOR INFORMATION Company Name: Mailing Address: City State Zip Contact Person: Day Telephone: E -Mail Address: Fax Number: Contractor Registration Number: Expiration Date: Valuation of Mechanical work (contractor's bid price): $ 1 I S-00 • ° Scope of Work (please provide detailed information): Tenant improvement to include (1) new nominal 10 -ton split system heat pump, all new duct distribution, (2) toilet exhaust fans Use: Residential: New .... ❑ Replacement .... ❑ Commercial: New .... ❑ Replacement .... Fuel Type: Electric ® Gas ....0 Other: Indicate type of mechanical work being installed and the quantity below: Unit Type: Qty Unit Type: Qty Unit Type: Qty Boiler /Compressor: Qty Furnace <100K BTU o Air Handling Unit >10,000 CFM o Fire Damper o 0 -3 HP /100,000 BTU 0 Furnace >100K BTU O Evaporator Cooler 0 Diffuser 19 3 -15 HP /500,000 BTU 0 Floor Furnace 0 Ventilation Fan Connected to Single Duct 2 Thermostat 1 15 -30 HP /1,000,000 BTU o Suspended/Wall/Floor Mounted Heater o Ventilation System 1 Wood/Gas Stove r, 30 -50 HP /1,750,000 BTU r, Appliance Vent o Hood and Duct 0 Emergency Generator 0 50+ HP /1,750,000 BTU 0 Repair or Addition to Heat/Refrig/Cooling System 0 Incinerator - Domestic 0 Other Mechanical Equipment 0 Air Handling Unit <10,000 CFM 1 Incinerator — Comm/Ind 0 H:\Applications\Forms- Applications On Line \2009 Applications \I -2009 - Permit Application.doc Revised: 1 -2009 bh Page 4 of 6 `;PERMIT APP ICATIONNOTES - Applicable'to all .permits:�in'this application Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject to possible revision by the Permit Center to comply with current fee schedules. Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation. Building and Mechanical Permit The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition). Plumbing Permit The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing Code (current edition). I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT. BUILDING OWNER OR THORIZE A : Signature: 01 sENT/�-e ( Date: (C)1Wii Print Name: %-'� e4ei �Ll D � � Day Telephone: (v � fG % q J 5 Mailing Address: 75 LI/✓✓ ON /9,t /i% _Al/ y (15(/8 City State Zip Date Application Accepted: 1E` ( ( Date Application Expires: 0.......k. t Staff Initials: 1 W H:\Applications\Forms- Applications On Line\2009 Applications \I-2009 - Permit Application.doc Revised: 1 -2009 bh Page 6 of 6 Cit of Tukwila, Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 - 431 -3670 Fax: 206-431-3665 Web site: http: //www. ci. tukwila.wa. us SET RECEIPT Copy Reprinted on 08 -22 -2011 at 12:48:41 08/22/2011 RECEIPT NO: R11 -01824 Initials: WER Payment Date: 08/22/2011 User ID: 1655 Total Payment: 2,810.80 Payee: HARDESTY & ASSOCIATES SET ID: 0822 SET NAME: PAC SUN SET TRANSACTIONS: Set Member Amount D11 -161 M11 -075 PG11 -079 TOTAL: 2,284.90 264.45 261.45 264.45 TRANSACTION LIST: Type Method Description Amount Payment Check 71908 2,810.80 TOTAL: 2,810.80 ACCOUNT ITEM LIST: Description Account Code Current Pmts BUILDING - NONRES MECHANICAL - NONRES PLUMBING - NONRES STATE BUILDING SURCHARGE 000.322.100 000.322.102.00.0 000.322.103.00.0 640.237.114 TOTAL: 2,280.40 264.45 261.45 4.50 2,810.80 CHI, of Tukwila. Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 -431 -3670 Fax: 206-431-3665 Web site: http: //www. ci. tukwila. wa. us SET RECEIPT RECEIPT NO: R11 -01163 Initials: WER Payment Date: 06/08/2011 User ID: 1655 Total Payment: 1,735.76 Payee: PRECISION PERMIT SERVICE SET ID: 6 -8 -11 SET NAME: PAC SUN SET TRANSACTIONS: Set Member Amount D11 -161 EL11 -0523 M11 -075 PG11 -079 TOTAL: 1,482.26 122.03 66.11 65.36 1,482.26 TRANSACTION LIST: Type Method Description Amount Payment Check 8036 1,735.76 TOTAL: 1,735.76 ACCOUNT ITEM LIST: Description Account Code Current Pmts ELECTRICAL PLAN - NONRES 000.345.832.00.0 PLAN CHECK - NONRES 000.345.830 TOTAL: 122.03 1,613.73 1,735.76 INSPECTION RECORD Retain a copy with permit MI ( INSPECTION NO. PERMIT NO. CITY OF TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila. WA 98188 bt. (206) 431 -3670 Permit Inspection Request Line (206) 431 -2451 Proiert: V Su Type insp;ctii ✓"(,eC Address; &,30 SC 144114( Date Called: Special instructions: Date Wanted:. • �: G m Requester: Phone No 1 (0 0 -Y4 0 -0373 ‘TAAppr43ved per applicable codes. E Corrections required prior to approval. COMMENTS: w' i -4-0e t /WeAe / t i &I A- Date: (i SPECTION FEE REQ IRED. Prior t. next inspection, fee must be , d at 6300 Southcenter : #vd., Suite 10". Call to schedule reinspection. q INSPECTION NO. INSPECTION RECORD Retain a copy with permit M(I - 0^75 PERMIT NO: CITY OF' TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670 Permit Inspection Request Line (206) 431 -2451 Project -•SkA Typ of Inspection: ts :A,AL AAeJ+, Address. o ss 1 �"� 1' 1 Dated s Wanted:. Okk. s Harm k Special Instructions: - AL !l/ #, A5 7"-, Date i n — .-- ! P.m. Requester: Phone No: Approved per applicable codes. Corrections required prior to approval. COMMENTS: A 4 (0, As7A14 4.4 � ,T oz..A,/ - 4,to /dve -1 '/,RI! 31f?'s►7 ssq/ J AL !l/ #, A5 7"-, Insp - c or: �..�ar'E., — _, __ _ _ - _ _ Date: / — 2 -- INSPECTION FEE RE IRED Prior t next inspection. fee must be paid at 6300 Southcenter lvd.. Suite 10 . Call to schedule reinspection. • INSPECTION RECORD Retain a copy with permit INSPECTION NO. PERMIT NO. CITY OF TUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670 ;Permit Inspection Request Line (206) 431 -2451 /,)/44 ►rY�►�-o�15 Project: PAC co Ut Type of Inspection: SUMOtq._ SHIII tf,R.A.Pd Address: 0 SO0IT (VI A11 Date Called: Special Instructions: • Date Wanted:. ll — 1 —il Ate: ( Requester: e .6,v 4t.„ Phone No: t:9 IJApproved per applicable codes. Corrections required prior to approval. COMMENTS: CID Ckel 0" A cb n"'o t,-P._ S MAI DQwr..r L c e .6,v 4t.„ t:9 er no 4Ui — •J I W cto • Date: — - -1 NSPECTION FEE REQUIRED. Prior'to next inspection. fee must be d at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection. .7 ____INSPECTION RECORD Retain a copy with permit INSPECTION N0. (v1 / / -b75 PERMIT NO. CITY OFTUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 - 3670,_., Permit Inspection Request Line (206) 431 -2451 Prop ln C Typ�,of nii" *r/ , 1/1/7 �/ Address: G s d ,n // DaJtpe(Called: Special Instructions: • Date Wantted:. an /0 /0 2- G -// .m Requester: Phone,: o- /1 -037 -� roved per applicable codes. 0 Corrections required prior to approval. COMMENTS: 24v /: N0",40 5 rQ 45,4 AINlilOPdelj 210 4 70 T. A/4 I Date: / C]-- { / J R-1 R CNSPECTION FEE REQUI ED. Prior to next inspection. fee must be paid at 6300`Southcenter Blvc.. Suite 100. Call to schedule reinspectioh. INSPECTION NO. INSPECTION RECORD Retain a copy with permit s�� i / -o 75 PERMIT NO. CITY OFTUKWILA BUILDING DIVISION 6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 43173670 Permit Inspection Request Line (206) 431 -2451 Project: )D/I0 sly/&/ Type of Inspection: /?,e)//2 -_,z AJ Address: GSQ sdVr.// ,ltrpi2 /71A i Date Called: Special Instructions: Date Wanted:. /D -2( —/ a. Requester: Phone No: 7/) —ccg q6 -03 7 Approved per applicable codes. ❑ Corrections required prior to approval. COMMENTS: El ai Date: //.7- z6 ~ l/ PECTION FEE REQUVRED. Priorr o.next inspection. fee must be at 6300 Southcenter Bl d.. Suite 100. Call to schedule reinspection. a INSPECTION NUMBER INSPECTION RECORD Retain a copy with permit PERMIT NUMBERS ti CITY OF TUKWILA FIRE DEPARTMENT 444 Andover Park East, Tukwila, Wa. 98188 206 - 575 -4407 Project: . PicSuk Sprinklers: • Type of Inspection: Ad eci Fill c,1,FAFigI Contact Person: Address: S Suite #: S L A44 ( Special Instructions: Phone No.: Approved per applicable codes. COMMENTS: r-N Corrections required prior to approval. PA- ri �.4 r_ 01< Needs Shift Inspection: Sprinklers: Fire Alarm: Hood & Duct: Monitor: Pre -Fire: Permits: Occupancy Type: Inspector: i Date: /U -i -1/ Hrs.: / $100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from the City of Tukwila Finance Department. Call to schedule a reinspection. r....... Billing Address Attn: Company Name: Address: City: State: Zip: Word /Inspection Record Form.Doc r 6/11/10 T.F.D. Form F.P. 113 rti hI NO AN ex PACSUN SOUTHCENTER SHOPPING MALL SPACE #208 TUKWILLA, WA FINAL TAB REPORT ARCHITECT FITCH 16435 N. SCOTTSDALE RD SUITE 195 - SCOTTSDALE, AZ 85254 PROJECT NO: 11 -145 DATE: 10/31/2011 TECHNICIAN: ROB COALLIER MECHANICAL ENGINEER: NP MECHANICAL, INC 1717 W. NORTHERN AVE. SUITE 116 - PHOENIX, AZ 85021 MECHANICAL CONTRACTOR: TNT MECHANICAL, LLC 2020 MALTBY ROAD, SUITE 7 - BOTHELL, WA 98021 GENERAL CONTRACTOR: HARDESTY & ASSOCIATES, INC 500 E. BALBOA BLVD. - NEWPORT BEACH, CA 92661 IMIVP AAESC TAC SERVICES, LLC 4811 DESMOND STREET BELLINGHAM, WA 98229 PH: (360) 224 -8555 FAX: (360) 464 -9973 ADMIN@TESTANDCX.COM 10/31/2011 Page 2 of 12 AABC National Performance Guaranty Pursuant to the agreement between TAC Services, LLC AABC Certified Testing & Balancing Agency TNT Mechanical, LLC All systems shall be tested and balanced in accordance with the project plans and specifications and to the optimum performance capabilities of the equipment. Testing and balancing shall be done in accordance with the standards published by the Associated Air Balance Council. If the Agency listed above fails to comply with the specifications for any reason other than termination of business by the AABC agency or equipment malfunction or inadequacy which prevents proper balancing of the systems, AABC will investigate and, if warranted, will provide supervisory personnel to assist the member Agency to perform work in accordance with AABC Standards. This supervision will be provided at no additional cost to the building owner. This Guaranty is valid for one year from the date of submission of a test and balance report, provided the Agency is a current member of AABC, and may only be invoked in writing by the building owner, architect, or engineer of record. The Guaranty is limited to the terms and conditions as stated Project Name Address SPACE #208 - SOUTHCENTER SHOPPING MALL PACSUN - SOUTHCENTER Name of Engineer Louie C. Panopio Engineering Firm NP MECHANICAL, INC Email Address unknown Address 1717 W. NORTHERN AVE - SUITE 116 Associated Air Balance Council 1518 K Street, N.W. Washington, D.C. 20005 202 - 737 -0202 • Fax 202 - 638 -4833 info @aabc.com • www.aabc.com TABLE OF CONTENTS 10/31/2011 Page 3 of 12 AABC DESCRIPTION PAGE COVER PAGE 1 AABC NATIONAL PERFORMANCE GUARANTY 2 TABLE OF CONTENTS 3 PROJECT SUMMARY 4 LEGEND SHEET 5-7 AHU -1 8-9 EF -1 10 EF -2 10 SCHEMATIC DIAGRAMS 11 -12 1.0 10/31/2011 Page 4 of 12 v NIIII AABC PROJECT SUMMARY THE AIR SYSTEMS WERE TESTED AND THE RESULTS ARE AS TABULATED ON THE ATTACHED DATA SHEETS 2.0 COMMENTS ON SPECIFIC EQUIPMENT IS INCLUDED UNDER REMARKS SECTION ON INDIVIDUAL DATA FORMS CONTAINED HEREIN. LEGEND SHEET AHU AIR HANDLING UNIT AC OR ACU AIR CONDITIONER UNIT ACCU AIR COOLED CONDENSING UNIT AD) P.D. ADJUSTED PITCH DIAMETER AMP AMPERE AVG AVERAGE B.H.P. BRAKE HORSEPOWER C.D. CEILING DIFFUSER CFM CUBIC FEET PER MINUTE C.E. CEILING EXHAUST CH CHILLER CHWR CHILLED WATER RETURN CHW OR CHWS CHILLED WATER SUPPLY C.R. CEILING RETURN CT COOLING TOWER CWR CONDENSER WATER RETURN CW OR CWS CONDENSER WATER SUPPLY DB DRY BULB D.D. DIRECT DRIVE D.P. DIFFERENCE, NET DECREASE OR INCREASE DLL DIAMETER DISP DISPLACEMENT D.N.A. DATA NOT AVAILABLE D.N.L DATA NOT LISTED EAT ENTERING AIR TEMPERATURE EDC ELECTRIC DUCT COIL EDH ELECTRIC DUCT HEALER EF EXHAUST FAN EMCS ENERGY MANAGEMENT CONTROL SYSTEM (S) EWT ENTERING WATER TEMPERATURE FCU FAN COIL UNIT FH FUME HOOD FG FLOOR GRILLE F.E. FLOOR EXHAUST OR RETURN F.LA FULL LOAD AMPERAGE FPB FAN POWERED BOX FPM FEET PER MINUTE F.S. FLOOR SUPPLY F.S.R FLOOR SUPPLY REGISTER FT. HD FEET OF HEAD FTU FAN TERMINAL UNIT GPM GALLONS PER MINUTE GFH GAS FIRED HEATER HC HEATING COIL HEATER O.L. THERMAL OVERLOAD PROTECTION FOR MOTORS LOCATED AT THE MOTOR STARTER HEPA HIGH EFFICIENCY PARTICULATE AIR H.F. HEPA FILTER HOA HAND /OFF /AUTO SWITCH H.P. HORSEPOWER HPS HIGH PRESSURE STEAM HRC HEAT RECOVERY COIL OR HEAT RECLAIM COIL HVAC HEATING , VENTILATION AND AIR CONDITIONING HWR HOT WATER RETURN OR HEATING WATER RETURN HWS HOT WATER SUPPLY OR HEATING WATER SUPPLY HX HEAT EXCHANGER LD. INSIDE DIAMETER LAT LEAVING AIR TEMPERATURE LD. LINEAR SUPPLY DIFFUSER LPS LOW PRESSURE STEAM LT. LIGHT TROFFER LWG LOW WALL GRILLE LWR LOW WALL RETURN LWT LEAVING WATER TEMPERATURE MAU /MUA MAKE UP AIR UNIT MBH 1,000 BTU'S PER HOUR N.A. NOT ACl FSSIBLE N.L NOT INSTALLED N.T. NOT TAKEN N.V.L NO VALID LOCATION N.Z. NOZZLE 0.0. OUTSIDE DIAMETER OPEN NO TERMINAL DEVICE INSTALLED O.S.A. MIN OUTSIDE AIR MINIMUM OAT OUTSIDE AIR TEMPERATURE PF POWER FACTOR PHC PREHEAT COIL PHC PHASE (S) PMP CIRCULATING PUMP P.P PERFORATED PLATE PSI POUNDS PER SQUARE INCH P.T. PITOT TRAVERSE RA RETURN AIR RF RETURN AIR FAN R.G. RETURN GRILLE RHC REHEAT COIL RPM REVOLUTIONS PER MINUTE SA SUPPLY AIR SAT SUPPLY AIR TEMPERATURE S.D. SUPPLY DIFFUSER SEF SMOKE EXHAUST FAN SF (AIR) SUPPLY FAN S.F. (ELECT) SERVICE FACTORS SHC STEAM HEATING COIL S.P. °W.C.' STATIC PRESSURE RESISTANCE, MEASURED IN INCHES OF WATER COLUMN S.W.E. SIDEWALL EXHAUST S.W.R. SIDEWALL RETURN S.W.S. SIDEWALL SUPPLY TAB TESTING, ADJUSTING, AND BALANCING TSP TOTAL STATIC PRESSURE UH UNIT HEATER ✓ VOLTS VAV VARIABLE AIR VOLUME VD VOLUME DAMPER VFD VARIABLE FREQUENCY DRIVE VP VELOCITY PRESSURE W WATTS WB WET BULB W.G. WATER GAUGE °F DEGREES FAHRENHEIT DP DIFFERENTIAL (DELTA) PRESSURE OR PRESSURE DROP DT DIFFERENTIAL (DELTA) TEMPERATURE, NET TEMPERATURE DECREASE OR INCREASE PSI POUNDS PER SQUARE 11401 PROJECT: AREA SERVED: AIR MOVING EQUIPMENT DATA PACSUN - SOUTHCENTER SHOPPING MALL RETAIL STORE FAN AHU -1 EQUIPMENT LOCATION SROCK ROOM - HIGH LEVEL TYPE / SIZE CENTRIFUGAL / 290 10/31/2011 Page 8 of 12 AABC EQUIPMENT MFG. TRANE MODEL TWE120D300AA SERIAL NUMBER 11342NBWBA FAN DATA FAN SHEAVE SIZE SPECIFIED FAN SHAFT ACTUAL TOTAL CFM- FAN 4000 QUANTITY 4060 TOTAL CFM - OUTLET 4025 MOTOR FRAME# 4060 R/A CFM 2955 1725 2934 O/A CFM 1070 1.00 1126 FAN RPM 745 386 703 ESP 0.50 2 0.41 SUCTION SP 0 18 - DISCHARGE SP 0.23 99 FAN SHEAVE SIZE AK79 FAN SHAFT 1" BELT SIZE A -50 QUANTITY 1 SHAFT C / C 18" MOTOR SHEAVE SUE 1VL40 MOTOR SHAFT 7/8" SHEAVE AD]. 3.0 T.O. MOTOR DATA MOTOR MFG. MARATHON MOTOR HP 2 SERVICE FACTOR 1.15 PHASE / Hz 3 / 60 HEATER SIZE / RATING THERMAL MOTOR FRAME# 145T DIFFUSER AND GRILLE TEST DATA AREA SERVED SPECIFIED ACTUAL VOLTAGE 208 -230 209/208/208 AMPERAGE 5.8 4.1/4.0/4.1 CFM FPM CFM MOTOR RPM 1725 1725 SPEED - - DIFFUSER AND GRILLE TEST DATA AREA SERVED NO. CODE SIZE AK DESIGN INITIAL FINAL FPM CFM FPM CFM FPM CFM STOCKROOM 1 CD-3 10 1.00 - 400 - 386 - 408 HALLWAY 2 CD-4 8 1.00 - 100 - 99 - 106 FITTING ROOM 3 (D-2 6 1.00 - 75 - 77 - 75 FITTING ROOM 4 CD-2 6 1.00 - 75 - 83 - 79 FITTING ROOM 5 CD-2 6 1.00 - 75 - 90 - 80 FITTING ROOM 6 CD-2 6 1.00 - 75 - 99 - 77 FITTING ROOM 7 a)-2 6 1.00 - 75 - 111 - 76 REAR SALES 8 CD-1 12 1.00 - 375 - 401 - 376 REAR SALES 9 CD-1 12 1.00 - 375 - 390 - 381 SUBTOTAL 1625 1736 1658 REMARKS: PROJECT: AREA SERVED: 10/31/2011 Page 9 of 12 e MEW AA BC DIFFUSER AND GRILLE TEST DATA PACSUN - SOUTHCENTER SHOPPING MALL RETAIL STORE AREA SERVED NO. CODE SIZE AK DESIGN INITIAL FINAL FPM CFM FPM CFM FPM CFM FRONT SALES 10 CO-1 12 1.00 - 400 - 254 - 406 FRONT SALES 11 CD-1 8 1.00 - 400 - 352 - 392 FRONT SALES 12 CD-1 6 1.00 - 400 - 388 • 403 FRONT SALES 13 CD-1 6 1.00 - 400 - 406 - 421 FRONT SALES 14 CD-1 6 1.00 - 400 - 262 - 386 FRONT SALES 15 CD-1 6 1.00 - 400 - 221 - 394 SUBTOTAL 2400 1883 2402 SUPPLY TOTAL 4025 3619 4060 STOCK ROOM R1 RG -3 16X16 1.19 - N/A 276 328 HALLWAY R2 RG -2 18X18 1.00 - N/A - 78 SALES R3 RG-1 30X24 3.52 - N/A 325 1144 SALES R4 RG-1 30X24 3.52 - N/A 393 1383 RETURN 2955 2934 OSA 1070 1126 REMARKS: PROJECT: 10/31/2011 Page 10 of 12 DIRECT DRIVEN CEILING EXHAUST FAN TEST SHEET PACSUN - SOUTHCENTER SHOPPING MALL NMI AA BC FAN DATA UNIT ID EF -1 EF-2 AK DESIGN INITIAL FINAL AREA SERVED STAFF R.R. _ STAFF R.R. CFM FPM CFM STAFF RESTROOM MANUFACTURER BROAN BROAN 1.00 - , - MODEL # 684- D2684 -F 684-D2684 -F SERIAL # NONE PROVIDED NONE PROVIDED DESIGN CFM 80 80 11X11 1.00 - 80 ACTUAL CFM 85 77 77 TSP .13 .13 . FAN RPM 1550 1550 MOTOR DATA MANUFACTURER BROAN-NUTONE BROAN- NUTONE HORSE POWER FRACTIONAL FRACTIONAL - VOLTS 115 115 AMPS .58 .58 SERVICE FACTOR 1.00 1.00 MOTOR RPM 1550 1550 SPEED SINGLE SPEED SINGLE SPEED FRAME N/App N/APP , PHASE /HZ 1 /60 1/60 HEATER SIZE THERMAL THERMAL RHEOSTAT SETTING NONE PROVIDED NONE PROVIDED AREA SERVED NO. CODE SIZE AK DESIGN INITIAL FINAL FPM CFM FPM CFM FPM CFM STAFF RESTROOM EF-1 EG 11X11 1.00 - 80 - 85 - 85 STAFF RESTROOM EF-2 EG 11X11 1.00 - 80 - 77 - 77 REMARKS: ,[ 13111E1 ■Ub9IMIPI I =11 B - CMir-Telliis_!7 laMV7ae -I9EP' .7 ` rww13 wVlNIwNIPS:Z= 4 Ginr2 i_miiimi_i_raEIIoI �I =IGr.- -aa_ _aains: al hfIIQ; 41MINI.0 ... mi II .II: �ii�i - . .1111 111111 1.1111111 -. iHi1.101I,IIIIIII!I U•i1iI . i_.... ..... rtidergiumEmolulMicisii Southcenter Shopping Mall 650 Southcenter Mali Tukwila, Washington MECHANICAL FLOOR PLAN rI Southcenter Shopping Mall 650 Southcenter Mall Tukwila. Washington MECHANICAL SCHEDULES AND DETAILS g a \ T' s / 1 !pig pl! 11 Z, 3 6 1 its 6 111 {`I 9E ikl lull- ;lf & �� !li j,l l9a! if' pi E�`lppi4 liI 11� tl ilii. j °ilgl ti i1} EegE,li �l'9 l bl Ti P qa EP a 'i 8i P 2 Ill -. 1 ill aJr 5 /' s �� o °s t Z r : —% e3' �� i 1'9 1 ��i1 1 11! F1° \ 1 T Amok I m .� el 1a g �� 1' 811 iE 1, i l P1 sa o >>I R E iI iI i 5::0 a I fi • Ili l; 1 ail . E PPi !ii li!!1t 1IIt a 1 + =l� lei ' 1�i % ill i aP 4 �1 �11 l i h° d3 �i lc i I ;1 0 P _ .i �lli';���i l� • i# I.l i�li1!j igi 1 ! i l it i lli P�a E l e te(,B ei t 1111 ...� llii 01 g 1i5i� ill; 111 t �al� pa -1. 1 P g I g I Ii e 1 sF e ":� _ PONS&LIT 1111 -If 1 ! ! i 1 • , 1 iila a 1E Pa DRAW - THROUGH CONDENSATE DRAM DETN a y U 0 II !!!1 Ii 2 1 aE 1!! ! g !,1 ar iiiiigi 11 t iiia i ,11111 1 ° ' �i .11 I D if 11 1 111i E E 11 a! ' l B l e ll ! trS ;� E i! iI 11` as 1111 ; 1 1 �' 4 Ff' it l lla wi4 'II E[t ii iEpill 'i 10 ©L' gonnll a 1 l 1� .di gIldm 111 i i! .. ... �I.1J`3tiUJ i1 li lli ' lF Ili I 1 5 up . t l l9 i ill !li s !l4 id A a i !1! 111 1 Pl iii HE pi a i 0 !1IIPP11F HA !S`li l Ili! Iii Pl ILI i ql 'Ili Via* 1 f+ 1" C11 i7, t Fi %�ie iv i tgl a� 1!" f!i �1 1, !4 1 ;1t',a'!g � !11i N li . . . . r 1; 'i a l r 3 ,ll I! 1, ya'i Hs lP S Ee is E ;II, i, ai � aP t 1 11�i i t 1 it 5 iI Pi {1 i l'i NI 11 ! i11ilF 1�, it 1! 1.14 i 1 5 ill y alpl, ,ilk 11i! Ii ! r P ai ¢� !e 1 _ 1' t pi 'ii °i�61 Li Il al !1 1:I 1=.;, i ?pi,! 1111 it 1 i i,i Ilk ! lf i 0ii ii s Il { l : 1 i i :aa;a P ! i ! a yay ! ;. i Il s 1 !Si i 1 P ! 1p': l i i 1 l i l ti11 P li . s 1 l i !T i4; ;1 i, � i (}`a WI 11 .P: ii /l $ l Pil AI ��[j,°j,°jjlg llri;:1oil; ai y ,ill 1 P 11V16tab`i ie7 a! l ' l II ,III 33 F i 1 Southcenter Shopping Mall 650 Southcenter Mall Tukwila. Washington MECHANICAL SCHEDULES AND DETAILS 1 2009 Washington state tnergy.t;oae t;ompuance rorms Tor rvonresioenuai anu ivluw hammy r.caiucnmai tVleh`anical Summa 2009 Washington State Energy Code Compliance Forms for Nonresidential and Multifamily Residential ECH -SUM Revised December 2010 r Project Info ®� 01 Project Address Date 50 Vg- - .L- 5ldoPP11,1 s *200 For Building Dept. Use il or- 01111 Applicant Name: p1(y6e Stic,t4 tub Applicant Address: ` 711 W. NO'e-'Q- AVE. n• A-z. Applicant Phone: l>O z— G! 4.311 Project Description Briefly describe mechanical system type and features. ❑ Includes Plans Spur ./ STEA Regr -Pij W Include documentation requiring compliance with commissioning requirements, Section 1416. Compliance Option 0 Simple System ej'Complex System Q Systems Analysis (See Decision Flowchart (over) for qualifications. Use separate MECH -SUM for simple & complex Equipment Schedules The following information is required to be incorporated with the mechanical equipment schedules on the plans. For projects without plans, fill In the required Information below. Cooling Equipment Schedule Equip. ID Equip Type Brand Name' Model No.1 Capacity2 Btu /h OSA CFM or Econo? SEER or EER IPLV3 Econmizer Option or Exception Heat Recovery Y/N Heating Equipment Schedule Equip. ID Equip Type Brand Name Model No.1 Capacity2 Btu /h O`, - or :'cono CO II E1 I IE E COM "I Heat Recovery Y/N 11. GIRtuh JA IJCE Efficiency' APPRO Ea. ULI9►Oil 1 . iiy of MI '1 ila • 6. % v Fan Equipment Schedule Equip. ID Equip Type Brand Name' Model No.1 CFM sp1 HP /BHP Flow Controls Location of Service • 11f available. 2 As tested according to Table 14-1A through 14 -1G. 3 If required. ° COP, HSPF, Combustion Efficiency, or AFUE, as applicable. 5 Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS). 6 Exception number from Section CORRECTION LTR# 1 M 11 -015 RECEIVE) JUL 08 2011 PERMIT CENTER Mechanics ummar 2009 Washington State Energy Code Compliance Forms for Nonresidential and Multifamily Residential H -SUN M Revised December 2010 System Description See Section 1421 for full description of Simple System qualifications. All Systems: ❑ No humidification? ❑ No Reheat? If Heating /Cooling or Cooling Only: sA Constant vol? a Split system? ❑ <= 84,000 Btuh? j Economizer ��" Air rnnIarl? ❑ Parkaned sus? k< =13S 000 min? included? • Coolino Cao < =15 Btuh /ft2? ❑ Heating Cap. > 0 & < =10 Btuh /ft2? If Heating Only: ❑ <10n0 rfm'' ❑<30% outside air? ❑ Heating Cap. < =10 Btuh /ft2? Decision Flowchart Use this flowchart to determine if project qualifies for Simple System Option. If not, either the Complex System or Systems Analysis Options must be used. Humidification or Reheat? ap < =15 B Heat/Cool Eq. with Cap < =10 System Type Heating /Cooling or Cooling Only Air Cooled, onstant Volu Heating Only Reference Section 1421 <1000 Total CFM Serving Single Roo .0 Yes <30% OSA Yes Package Unit Cap <= 135,000 Btuh Split System <= 84,000 Btuh' Econo ncluded? Simple System Allowed (section 1420) Use Complex Systems (section 1430) Complex Systems Refer to MECH -COMP Mechanical Complex Systems for assistance in determining which Complex Systems requirements are applicable to this project. 2009 Washington State Energy Code Compliance Forms for Nonresidential and Multifamily Residential Mechanicai Permit Piant-. Checklist MECH CHK'. 2009 Washington Stale Energy Code Compliance Forms for Nonresidential and Multifamily Residential Revised December 2010 Project Address el, 041 ce w 5 \la?' wet mA� 'Date its _. ..„� 4 t The following information necessary to check a mechanical permit application for compliance with the mechanical requirements in the Washington State Nonresidential Energy Code. Applicability (yes, no, na) Code Section I Component I Information Required . Location I l on Plans Building Department Notes HVAC REQUIREMENTS (Sections 1401 -1424) 1411 Equipment Performance yg,.. 1411.1 Minimum efficiency Equipment schedule with type, capacity, efficiency Niue> N/A 1411.1 Combustion htg. Indicate intermittent ignition, flue/draft damper & jacket loss OA 1411.1 Air - cooled chiller Provide total air and water chiller capacity tJ /A 1411.2.1 Water - cooled chiller Full -load and NPLV values adjusted for any non - standard conditions — ye.s . 1411.4 Pkg. elec. htg.& clg. List heat pumps on schedule iaz. IVA 1411.5 Unenclosed Heat Indicate radiant heat system and occupancy controls • 1412 HVAC Controls ' yes 1412.1 Temperature zones Indicate locations on plans • M 100 '!(, 1412.2 Deadband control Indicate 5 degree deadband minimum M2.0Q (J /A} 1412.3 Humidity control Indicate humidistat Vg.,s 1412.4 Setback and Shutoff Indicate thermostat with 7 day program capability & required setback Muni, Yes 1412.4.1 Dampers Indicate damper location, leakage rate, control type, & max. leakage /I\1op \ as 1412.4.2 Optimum Start Indicate optimum start controls 1\4200 y E., , 1412.5 Heat pump control Indicate heat pump thermostant & outdoor lockout on schedule Nl'2.00 Pip, 1412.6 Combustion heating Indicate modulating or staged control m yE6 1412.7 Balancing Indicate balancing features on plans 11h' (00 (.1 /A, 1412.8 Ventilation Control Indicate demand control ventilation for high - occupancy areas f�/lti 1412.9 Loading Dock & Garage Ventilation Indicate enclosed loading dock & parking garage ventilation system activation and control method. o y 5 1422 Thermostat interlock Indicate thermostat interlock on plans M' 00 HA 1432.2.1 Temperature Reset Indicate temperature reset method 1413 Air/Water Economizers Yes 1412.1 Single zone systems Indicate multiple cooling stage control capability. M100 1 es 1413.1 Air Econo Operation Indicate 100% capability on schedule N*1'L000 (q /{k 1413.1 Wtr Econo Operation Indicate 100% capacity at 45 degF db & 40 deg F wb 1,10, 1413.2 Wtr Econo Document Indicate max. OSA condition for design clg load & equipment performance data. — N /t, 1413.3 Integrated operation Indicate capability for partial cooling ° Pt /ice 1413.4 Humidification Indicate direct evap or fog atomization w/ air economizer -'m- 1414 Ducting Systems Ve6 1414.1 Duct sealing Indicate duct design pressures, sealing, and testing requirements . iA20o ' 4 E.S 1414.1.2 Low press. duct test Indicate applicable low pressure duct systems shall be leak tested MtoO pot 1414.1.3 1414.1.3 High press. duct test Indicate high pressure duct systems shall be leak tested, and identify the of this ductwork on plans — '1 4 1414.2 Duct insulation Indicate R -value of insulation on duct Mae) 1415 Piping Systems y(; 1415.1 Piping insulation Indicate R -value of insulation on piping P100 1416 Completion Requirements A ess 1416.3.2 System Balancing Indicate air and water system balancing requirements 1\41-00 .)`e,S 1416.3.3 Functional Testing Provide sequence of operations and test procedures. M2o0 . . YO 1416.3.4 Documentation Indicate O &M manuals, record drawings, staff training (1^ 1416.3.5 Comm. Report Indicate requirements for final commissioning report �'ZQO { l 1416.4 Compliance Chklist Submit to building official upon substantial completion. 11‘4142, )1(�. Mechanical Summary Form Completed and attached. Equipment schedule with types, input/output, efficiency, cfm, hp, economizer e, Mecha iia... ' ermit Plans Chet st COntinued MECH CHK; Revised December 2010 • 2009 Washington State Energy Code Compliance Fonns for Nonresidential and Multifamily Residential Project Address 6VTt:,A - Q FP6i,1C 0 Octet. `Date /_, 30 _It The following information is necessary to check a mechanical permit application for compliance with the mechanical requirements in the Washington State Nonresidential Energy Code Applicability es no na Code Section Com•onent Information Re•uired Location on Plans Building Department Notes SERVICE WATER HEATING AND HEATED POOLS (Sections 1440 -1454) 1440 Service water htg. y lis 1441 Elec. water heater . Indicate R -10 insulation under tank P 1 00 1 &S 1442 Shut -off controls Indicate automatic shut -off of circulators or heat trace Q100 y 1443 Pipe Insulation Indicate R -value of insulation on piping flop Nr /Pr 1444 Pump Energy Indicate method of pump energy management (Sec 1438) I•%A 1445 Heat Recovery Indicate preheat capacity as % of peak service water demand. 1460 Heated Pools t1 /A 1452 Heat Pump COP Indicate minimum COP of 4.0 '°' tW /y. 1452 Heater Efficiency Indicate pool heater efficiency WA, 1453 Pool heater controls Indicate switch and 65 degree control WA 1454 Pool covers Indicate vapor retardant cover ftl /A: 1454 Pools 90+ degrees Indicate R -12 pool cover OM 1455 Heat Recovery Indicate method and capacity of exhaust air temperature reduction , COLD STORAGE (Sections 1460 -1465) 1460 Cold Storage 0/A- 1463 Evaporators Indicate motor type and speed control -- N/A 1464 Condensors Indicate condenser cooling type, design wb temp and control °- N!A 1465 Compressors Indicate design minimum condensing temp and control. -' If "no" is indicated for any item in Sections 1401 -1424 or 1440 -1465 , provide explanation: June 16, 2011 d of Tukwila • Jim Haggerton, Mayor Department of Community Development Jack Pace, Director Amy Diekevers 75 — 60 Street SW Wyoming, MI 49548 RE: Correction Letter #1 Mechanical Permit Application Number M11 -075 Pac Sun — 650 Southcenter Mall Dear Ms. Diekevers, This letter is to inform you of corrections that must be addressed before your mechanical permit can be approved. All correction requests from each department must be addressed at the same time and reflected on your drawings. I have enclosed comments from the Building Department. The Fire Department has no corrections at this time. Building Department: Dave Larson at 206 431 -3678 if you have questions regarding the attached memo. Please address the attached comments in an itemized format with applicable revised plans, specifications, and/or other documentation. The City requires that two (2) sets of revised plans, specifications and/or other documentation be resubmitted with the appropriate revision block. In order to better expedite your resubmittal, a `Revision Submittal Sheet' must accompany every resubmittal. I have enclosed one for your convenience. Corrections /revisions must be made in person and will not be accepted through the mail or by a messenger service. If you have any questions, please contact me at (206) 431 -3670. Sincerely, Jenni erm er Marshall Technician encl File: M11 -075 W:\Perrnit Center \Correction Letters \2011\M11 -075 Correction Letter #1.doc 6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665 Tukwila Building Division Dave Larson, Senior Plan Examiner Building Division Review Memo Date: M11 -075 Project Name: Pac Sun Permit #: 650 Southcenter Mall Plan Review: Dave Larson, Senior Plans Examiner The Building Division conducted a plan review on the subject permit application. Please address the following comments in an itemized format with revised plans, specifications and /or other applicable documentation. (GENERAL NOTE) PLAN SUBMITTALS: (Min. size 11x17 to maximum size of 24x36; all sheets shalllbe the same size). (If applicable) Structural Drawings and structural calculations sheets shall be original signed wet stamped, not copied.) 1. Please complete a Mechanical Summary form as required by the 2009 Washington State Energy Code. One has been included with this review memo. Should there be questions concerning the above requirements, contact the Building Division at 206 -431- 3670. No further comments at this time. • 41 PE -1 PLAN REVIEW /ROUTING SLIP ACTIVITY NUMBER: M11 -075 DATE: 07 -08 -11 PROJECT NAME: PAC SUN SITE ADDRESS: 650 SOUTHCENTER MALL Original Plan Submittal Response to Incomplete Letter # X Response to Correction Letter # 1 Revision # After Permit Issued DEPARTMENTS: kiNit/ u1d ng Division Public Works 111 Fire Prevention Structural Planning Division n Permit Coordinator DETERMINATION OF COMPLETENESS: (Tues., Thurs.) Complete Incomplete DUE DATE: 07-12-11 Not Applicable Comments: 'Permit Center,klse Only INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED: Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials: TUES/THURS ROUTING: Please Route Structural Review Required nNo further Review Required n REVIEWER'S INITIALS: DATE: APPROVALS OR CORRECTIONS: DUE DATE: 08 -09 -11 Approved ❑ Approved with Conditions X Not Approved (attach comments) ❑ Notation: REVIEWER'S INITIALS: DATE: Permit Center Use Only CORRECTION LETTER MAILED: Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials: Documents/routing slip.doc 2 -28 -02 1 PLAN REVIEW /ROUTING SLIP ACTIVITY NUMBER: M11 -075 DATE: 06 -08 -11 PROJECT NAME: PAC SUN SITE ADDRESS: 650 SOUTHCENTER MALL X Original Plan Submittal Response to Incomplete Letter # Response to Correction Letter # Revision # After Permit Issued DEPARTMENTA Bu lding I5ivis on v'' Public Works ❑ tr‘felf\Prevention j Structural Planning Division ❑ Permit Coordinator DETERMINATION OF COMPLETENESS: (Tues., Thurs.) Complete Incomplete DUE DATE: 06-14-11 Not Applicable Comments: -Permit Center Use Only INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED: Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials: TUES/THURS ROUTING: Please Route Structural Review Required REVIEWER'S INITIALS: No further Review Required DATE: APPROVALS OR CORRECTIONS: DUE DATE: 07 -12-11 Approved ❑ Approved with Conditions ❑ Not Approved (attach comments) 11 Notation: REVIEWER'S INITIALS: DATE: Permit Center Use Only CORRECTION LETTER MAILED: I: / Departments issued corrections: Bldg Fire ❑ Ping ❑ PW ❑ Staff Initials: Documents /routing slip.doc 2 -28 -02 City of Tukwila Department of Community Development 6300 Southcenter Boulevard, Suite #100 Tukwila, Washington 98188 Phone: 206 - 431 -3670 Fax: 206 - 431 -3665 Web site: http: / /www.ci.tukwila.wa.us Revision submittals must be submitted in person at the Permit Center. Revisions will not be accepted through the mail, fax, etc. Date: rAAQ -l\ Plan Check/Permit Number: M11-075 ❑ Response to Incomplete Letter # ® Response to Correction Letter # 1 111 Revision # after Permit is Issued ❑ Revision requested by a City Building Inspector or Plans Examiner Project Name: Pac Sun Project Address: 650 Southcenter Mall Contact Person: \-at.n� \ �,-( Q v el S Phone Number: `Q16- L4 et3- X33I4 Summary of Revision: go u trle ,)'% �'l ��� �7t P S D.»rnl ary Ft, r-rq RECEIVED CITY OF TUKWIL A ;JUL 08 2011 PERMIT CENTER Sheet Number(s): "Cloud" or highlight all areas of revision including date of revisio Received at the City of Tukwila Permit Center by: -- Entered in Permits Plus on \applications \forms- applications on Iine\revision submittal Created: 8 -13 -2004 Revised: Contractors or Tradespeople liter Friendly Page 0 General /Specialty Contractor A business registered as a construction contractor with L &I to perform construction work within the scope of its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of account and carry general liability insurance. Business and Licensing Information Name HARDESTY & ASSOCIATES INC UBI No. 601423943 Phone 9497232230 Status Active Address 500 E Balboa Blvd License No. HARDEAI066PP Suite /Apt. License Type Construction Contractor City Newport Beach Effective Date 10/17/1994 State CA Expiration Date 11/17/2011 Zip 92661 Suspend Date County Out Of State Specialty 1 General Business Type Corporation Specialty 2 Unused Parent Company Other Associated Licenses License Name Type Specialty 1 Specialty 2 Effective Date Expiration Date Status HARDES1099DG HARDESTY & STONE INC Construction Contractor General Unused 3/7/1991 7/2/1993 Archived Business Owner Information Name Role Effective Date Expiration Date HARDESTY, ROBERT D Cancel Date 01/01/1980 Bond Amount HARDESTY, ROBERT E 7 01/01/1980 wa13466 HARDESTY, WILLIAM S Until Cancelled 01/01/1980 HARDESTY, LORI A /2009 01/01/1980 PLATTE RIVER INS CO ALLEY, RICHARD Agent 01/01/1980 09/01/2009 Bond Information Page 1 of 2 Bond Bond Company Name Bond Account Number Effective Date Expiration Date Cancel Date Impaired Date Bond Amount Received Date 7 MERCHANTS BONDING CO (MUTUAL) wa13466 09/08/2009 Until Cancelled $12,000.0009/14 /2009 6 PLATTE RIVER INS CO 40069657 09/01/2003 Until Cancelled 09/01/2009 $12,000.0009/08 /2003 Assignment of Savings Information No records found for the previous 6 year period Insurance Information Insurance Company Name Policy Number Effective Date Expiration Date Cancel Date Impaired Date Amount Received Date 16 SCOTTSDALE INS CO BCS0023302 10/25/2010 10/25/2011 $1,000,000.00 10/25/2010 15 SCOTTSDALE INS CO BCS0020742 10/25/2009 10/25/2010 $1,000,000.00 10/27/2009 14 FIRST SPECIALTY INS CORP IRG57154 10/25/2008 10/25/2009 $1,000,000.0010 /31/2008 13 STEADFAST CO D INS 5C03557421 08 10/25/2006 10/25/2008 $1,000,000.00 10/25/2007 12 TOEADFASTINS SC03557421 07 10/25/2006 10/25/2007 $1,000,000.00 10/30/2006 11 CO ADFAST INS SC03557421 06 10/25/2004 10/25/2006 $1,000,000.00 10/27/2005 Summons /Complaint Information No unsatisfied complaints on file within prior 6 year period https://fortress.wa.gov/lni/bbip/Print.aspx 08/22/2011 EQ. EQ. 25' -0" NOTE: MOUNT ALL DIFFUSERS IN SALES AREA AT 12' -6" A.F.F. 25' -0" 20' -0" 10' -6 1/4" l.. +i4 :t±i4t v iti\ .L. ,. i:'� \ :v, .v v ... v ..... o::ay. n...n:.. aL,va +J \�vvt.,tn4Jti L A \:v :: {:: 'vvv:L. ti♦: :J:IX +J:J:J-. » >}:;}:L.}L\} -: n. '�cv_::v "vv v; .:tvL::ti•. n.: >pv:�it t ..':v: n:v ^n +�.. • 26X24 24X24 1:0 0 16X24 12 "0 24"0 16X24 (D 6 "0 MECHANICAL FLOOR PLAN 12 "0 1001111 I.' "::::=3.-....7.-5=,:::::: 4410 • • • • • tiff : •.:¢:,` -\ ti \v ?;ti? �ti• ; < \'t v \:ti• ^.': Pi4:v: vi:\ j� 6:v4iS ti4:: +.: ::::.\ t0 v 3� .. ,t , : `•: \'Li- ..: ..:. \ -v •i :•v. :- :tAt�:. +'iitYi£ iii :i ?v::'.iLtS ?L ?::i ?: ?ij ?L. :}.v .:vv:::n...• ....... .v.. ..... .. . . v0.\ \. t \n;J:J:,J: Oft+' t:?.?..: ti:' i�+:>..: v:' a' xi:: a\ J: ti\ S'• QiiQ: Q: ti:: J :v:J\ \::iU +it:J:J:i }i;4ti + <��:�. '.,n.,: , :: :,v \ \vv ..ivv +J��,.::•v:• v. .: .... o +.:.Laada.LV. vHaaay.hc .,.o::tiv!yl..»..,,.,. o.a »va.nv ..vvL aL L:Lvv..v.:.tavaL.ta. at.:t ..:!v \}�v :. .:,.,L.,.,.v..,,..,,., v.. vvvvavvv. v.s.::vav,v. vv.:.. .. .. . v.L vvv v.... v -... :.:. v- .v:....t ..,. vx., ..:vvv v v:vv 375 12 "0 'nv v vv. v v v\ v v u v LL t vvv v.vvv- v- v -t' -:: •. ....... v .. .. ..........,........nn. ..,: n, n:n..:nn 12 "0 • 410 fig) \CC :i0 1- \. ...' .....: ?: ?`:::ani`:::? i:• "ti::iiiii::t2 "c........: ............... ......:: �.;v:.; ?•.;.:.:5' - ?: :.�:v ?2j22: ..\ .. \L:v N \::ii v4i ... .t... nt..tiiT iii: ioiv.: J: v... i::: �ovM1.: ii.:itiii::.. \uu:::::.�..nn:n.\ v:vv ?.�,,.. :�:::..... :.., ` •t' . ......... .... .... ......::::::.... ........ ..... .n.,: nn:v: ntve.,..,..,..: a:. \..:.:.v.'v vv :•:....... ... :.mot:: �>':..........:'v': \ \: :, Lt.L LLLLLL.....: t. t,: t. :t,...:...t »..L..,.::.�,,..,,.. 12 "0 ., a- :.aki•:t::i •i: \::�.i� :i., ..............,.,.,, ..':c i:.v!.::.v :i :`:: \`:•. J: 6i::: 375 400 ■ 12 "0 12 "0 t APP 12 "0 (c) 400 NOTE: (EX) = EXISTING -x- = EXISTING TO BE REMOVED NOTE: THE RENOVATED OR REPAIRED ASPECTS OF THE EXISTING SYSTEM SHALL CONFORM TO THE SAME MANNER AND ARRANGEMENT AS WAS IN THE EXISTING SYSTEM, AND SHALL NOT CAUSE THE EXISTING SYSTEM TO BECOME UNSAFE, HAZARDOUS OR OVERLOADED. . i>.:: vti:: i\. vi�Ji{:: iJ: 3:•}: i;: i4::. Y..:: R.::>>.:: Jl JlviiJv' v::: i::YJi \t^^v:�i'.:.v':ti:JYL \ \ \ii :`iii +!i \ilA \S! iii\ i:$•iJ \:: \v:}'Jip}:vjSVyv::i•4: NOTE: • CONTRACTOR SHALL KEEP ALL MECHANICAL, PLUMBING AND ELECTRICAL ITEMS OVER THE FITTING ROOMS, HALLWAY AND TOILET ROOM AND PLATFORM AS TIGHT TO THE SIDE WALLS AS POSSIBLE. KEEP THE MAIN AREA OF THE PLATFORM CLEAR. LANDLORD NOTES KEYED NOTES 1. ALL EQUIPMENT, DUCTWORK, CONTROLS ETC. NOT BEING REUSED SHALL BE REMOVED. DO NOT JUST ABANDON. 2. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND ESTABLISH A DISCREPANCY RESOLUTION PROCEDURE. 3. ALL SYSTEMS SHALL BE CHARGED AND OPERATIONAL WHEN THE CONTRACTOR IS NOT ON THE PREMISES. 4. ALL ROOF WORK SHALL BE PERFORMED BY LANDLORD'S DESIGNATED ROOFER. 5. ALL WORK SHALL BE SCHEDULE WITH LANDLORD'S FIELD REPRESENTATIVE. 0 27 "0, 12 "0 NECK CD -1. BALANCE TO CFM NOTED. 0 2 13.5 "0, 6 "0 NECK CD -2. BALANCE TO CFM NOTED. 0 15x15, 12 "0 NECK CD -3. BALANCE TO CFM NOTED. O 12x12, 8 "0 NECK CD -4. BALANCE TO CFM NOTED. 0 32x26, 30x24 NECK RG -1. MOUNT AS HIGH AS POSSIBLE. COORDIANTE EXACT PLACEMENT WITH PAC SUN CONSTRUCTION MANAGER. ® 18x18, 16x16 NECK RG -2. 0 24V. DUCT SMOKE DETECTOR TO SHUTDOWN UNIT WITHOUT DELAY. 0 3/4" CONDENSATE DRAIN LINE DOWN IN WALL TO LAVATORY TAILPIECE. 9 PROGRAMMABLE T —STAT W/ REMOTE TEMPERATURE SENSOR. T —STAT SHALL BE LOCATED IN METAL LOCKING ENCLOSURE. 10 REMOTE TEMPERATURE SENSOR. COORDINATE EXACT LOCATION WITH ARCHITECT'S INTERIOR ELEVATION. SENSOR SHALL BE LOCATED IN A CLEAR PLASTIC LOCKING COVER. 11 8 "0 TOILET EXHAUST DUCT UP THROUGH ROOF TO CAP. LOCATE CAP. MINIMUM 10' -0" AWAY FROM ANY FRESH AIR INTAKES. FIELD VERIFY. © 3/4" SECONDARY CONDENSATE DRAIN LINE DOWN THRU CEILING TO DISCHARGE OVER LAVATORY. EXTEND PIPE 1" BELOW CEILING AND PROVIDE ESCUCHEON PLATE TO MATCH CEILING. 13 SECONDARY DRAIN PAN, 16 GA. GALV. STEEL WITH 3/4" DRAIN LINE. 14 26x24 OUTSIDE AIR DUCT UP THRU ROOF TO ROOF CAP. CAP SHALL BE EQUAL TO "GREENHECK" FABRAHOOD. 15 26x24 RELIEF AIR DUCT UP THRU ROOF TO ROOF CAP. CAP SHALL BE EQUAL TO "GREENHECK" FABRAHOOD. 16 MOTORIZED OUTSIDE AIR DAMPER WITH 24V., NORMALLY CLOSED ACTUATOR. MECHANICAL CONTRACTOR SHALL PROVIDE TRANSFORMER. 17 MOTORIZED RETURN AIR DAMPER WITH 24V., NORMALLY OPEN ACTUATOR. MECHANICAL CONTRACTOR SHALL PROVIDE TRANSFORMER. 18 MOTORIZED RELIEF AIR DAMPER WITH 24V., NORMALLY OPEN ACTUATOR. MECHANICAL CONTRACTOR SHALL PROVIDE TRANSFORMER. 19 NEW ROOF MOUNTED CONDENSING UNIT TO REPLACE EXISTING CONDENSING UNIT. FIELD VERIFY. 20 NEW AIR HANDLING UNIT TO REPLACE EXISTING AIR HANDLING UNIT. FIELD VERIFY. 1 0 EXISTING FIRE SPRINKLER LINE TO REMAIN AS IS. FIELD VERIFY. 22 18x18, 16x16 NECK RG -3. CALCULATION O U TS I D E AIR SALES: AREA = 2434 SF REQUIRED VENTILATION RATE = 0.30 CFM /SF CFM = 2434 SF x 0.30 CFM /SF CFM = 730 FITTING ROOMS: AREA = 175 SF REQUIRED VENTILATION RATE = 0.20 CFM /SF CFM = 175 SF x 0.20 CFM /SF CFM = 35 STOCK /BACK AREA: AREA = 443 SF REQUIRED VENTILATION RATE = 0.15 CFM /SF CFM = 443 SF x 0.15 CFM /SF CFM = 66 TOTAL CFM REQUIRED = 831 TOTAL CFM PROVIDED = 835 CALCULATED AS PER I.M.C. SECTION 403, TABLE 403.3. I SEPARATE PERMIT REQUIRED FOR: ❑ Mechanical Electrical Plumbing Gas Pig City of Tukwila BUILDING DIVISION AHU • 3/4" • CD r, CD S SCALE: 1/4" = 1' -0" 12 "0 • 3/4" • 26 "0 24 "0 12. "0 MECHANICAL FLOOR PLAN - CONTINUED REVISIONS No changes shall be made to the scope of work without prior approval of Tukwla Building Division. NOTE: Revisions will require a new plan subrn t! and may include additional plan review fees. I SCALE: 1/4" = 1' -0" REVIEWED FOR CODE COMPLIANCE APPROVED JUL 1 9 2011 City of u iia BUILDIN DI ISION FILE COPY Permtt No. N I<< -01EC , Plan review approval is abject to ero,s art ins. Approval of construction documents does not authorize the violation of any adopted code or ordinance. Receipt of approved Field Copy and col' Is is admowledged: Date. , $_0 ?_// City Of TiukwiUa BUILDING DIVISION 11WO75 RECEIVED JUN 08 2011 PERMIT CENTER 530 pncsuri• • COPYRIGHT NOTICE: These drawings and specifications are copyrighted and subject to copyright protection as an "architectural work" under sec. 102 of the copyright act, 17 u.S.C. As amended January 2003. The protection includes, without limitation, the overall form, arrangement and composition of spaces, and elements of the design. Under such protection, unauthorized use of these drawings and specifications may result in cessation of construction, building seizure, and/or monetary liability. co -J 0 0 J J Z 2 U w • NP MECHANICAL INC. U NGBRAVE 11717 W. OHEBNAVE. SUf1E 116 ��PHOEND(,MmONA85021 • (602) 249.6311 MELT No. 11089 EXPIRES 08/12/12 DATE: 5/24/2011 SHEET: AS -NOTED M 1 0 0 ALE: DROWN BY: AR PROJECT Nos PSN -10 -016 TRANE HVAC EQUIPMENT PACKAGE HEAT LOSS CALCULATION SPLIT SYSTEM HEAT PUMP UNIT MECHANICAL GENERAL NOTES EQUIPMENT PACKAGE INCLUDES ALL TRANE HVAC EQUIPMENT AND RELATED ACCESSORIES SUCH AS CURBS, THERMOSTATS, HEATERS, ETC., AS SPECIFIED ON THE PLANS AND SPECIFICATIONS FOR PACIFIC SUNWEAR. FOR COMPLETE INFORMATION ON THE PACIFIC SUNWEAR EQUIPMENT PACKAGE CONTACT THE NATIONAL ACCOUNT EXECUTIVE AT TRANE NATIONAL ACCOUNTS: PATRICK BRONSON TRANE NATIONAL ACCOUNTS 17760 ROWLAND STREET CITY OF INDUSTRY, CA 91748 PHONE: (866) 882 -1611 - TOLL FREE PHONE: (626) 435 -1176 - DIRECT LINE FAX: (626) 913 -2489 EMAIL: pbronson@trane.com TOM CALLAGHAN TRANE NATIONAL ACCOUNTS 17760 ROWLAND STREET CITY OF INDUSTRY, CA 91748 PHONE: (866) 882 -1611 -; TOLL FREE PHONE: (626) 435 -1181 -' DIRECT LINE FAX: (626) 913 -2489 EMAIL: tcallaghan©trane.com ANY CHANGES OR VARIATIONS TO THE ORIGINAL EQUIPMENT PACKAGE THAT WOULD AFFECT THE HVAC EQUIPMENT PACKAGE SHOULD BE BROUGHT TO THE ATTENTION OF THE ACCOUNT EXECUTIVE AT TRANE NATIONAL ACCOUNTS. NOTE: ORDERING PROCEDURES HVAC PACKAGE IS PROVIDED BY PACSUN AND INSTALLED BY G.C. G.C. SHALL CONTACT TRANE PRIOR TO BID SUBMITTAL TO RECEIVE UST OF ADDITIONAL MATERIALS/LABOR REQUIREMENTS THAT ARE TO BE INCLUDED IN THEIR BID DOCUMENTS. PARTS WARRANTIES TRANE WARRANTIES ALL PARTS FOR A PERIOD OF ONE (1) YEAR FROM INITIAL STARTUP OR 18 MONTHS FROM DATE OF SHIPMENT, WHICHEVER OCCURS FIRST. CERTAIN EQUIPMENT HAVE COMPONENTS THAT INCLUDE AND EXTENDED WARRANTY LONGER THAN ONE (1) YEAR. TRANE PARTS WARRANTIES BELONG TO THE EQUIPMENT OWNER. THE HVAC CONTRACTOR WILL BE RESPONSIBLE FOR FIRST YEAR LABOR WARRANTY, DEUVERY COORDINATION, RECEIVING AND INSTALLATION AS DESCRIBED IN THE SPECIFICATIONS. ROOF (AREA IN SQ. FT.) 4616 x 46.84 x 0.121 OUTSIDE WALL (AREA IN SQ. FT.) x60x0.08 = 0 26162 OUTSIDE AIR (0.25 CFM /SF) (CFM) 835 x 45.88 x 1.085 = 41566 ADD ANY SPECIAL LOADS SUCH AS EXTERIOR GLASS, CUSTOMER ENTRANCES IN EXTERIOR WALLS, ETC. TOTAL HEAT LOSS (BTUH) = 67728 INDOOR UNIT OUTDOOR UNIT MARK MODEL CFM E S.P. WEIGHT AUX. HEAT WP HP (LB) (Kw) MARK MODEL COOLING CAPACITY (MBH) ENT. AIR ('F) HEATING CAP. SENSIBLE TOTAL (MBH) DB WB WEIGHT (LB) AHU -1 TWE120 4000 0.5 2 444 9.96 CU -1 TWA120 123.4 129.45 85 63 64.3 438 HEAT GAIN CALCULATION TRANE HVAC EQUIPMENT PACKAGE ROOF (AREA IN SQ. FT.) 4616 x 49.32 x 0.121 27549 OUTSIDE WALL (AREA IN SQ. FT.) x 0.08 (EQUIVALENT TEMP. DIFF. FROM ASHRAE) _ 0 LIGHTING ( WATTS) 9270 x 3.412 ▪ 31629 PEOPLE ( #) 83x 245 20335 OUTSIDE AIR (SAME AS FOR HEATING) (CFM) 835 x 8.74 x 1.095 EQUIPMENT OR OTHER SPECIAL LOADS AS APPLICABLE TOTAL SENSIBLE HEAT PEOPLE ( #) x 205 OUTSIDE AIR LATENT HEAT OTHER SPECIAL LOADS AS APPLICABLE 7991 9463 93967 17015 -3500 _ 0 TOTAL LATENT HEAT • 13515 GRAND TOTAL 107482 NOTES: 1. UNITS SHALL BE AS MANUFACTURED BY: TRANE. 2. UNITS ARE SIZED FOR 857 SUMMER AMBIENT TEMPERATURE, 237 WINTER TEMPERATURE. 3. COOLING CAPACITY, MINIMUM HEAT CAPACITY AND CFM ARE MINIMUM OUTPUT REQUIRED. ALL UNITS SHALL HAVE NO LESS THAN 98% OF THESE CAPACITIES. COOLING CAPACITY IS GROSS COIL CAPACITY REQUIRED (FAN HEAT NOT DEDUCTED). 4. PROVIDE FAN COIL UNIT WITH FILTERS AND FILTER RACK SIZED AT 500 FPM VELOCITY. 5. PROVIDE WITH PROGRAMMABLE THERMOSTAT: TRANE BAYSTAT052A AND THE REMOTE SENSOR IS A BAYSTAT060A. 6. PROVIDE WITH LOW AMBIENT OPERATION TO: 23 F. 7. UNITS VOLTAGE: 208V /3PH 8. PROVIDE CONDENSING UNITS WITH HAILGUARDS. NOTE: ALL DX SPLIT SYSTEM FAN COIL WITH REMOTE CONDENSING UNIT WITH REFRIG. LINES EXTENDING OVER "50" FT. IN LENGTH TO HAVE HARD START KIT, CRANK CASE HEATER, TIME GUARD, AND LIQUID SOLENOID VALVE AT CONDENSER. INSTALL AND ADJUST REFRIG. AND OIL CHARGE PER MFR'S RECOMMENDATIONS. NEW EXHAUST FAN SCHEDULE DAMPER OPERATOR ADJUST FROM FACE SIDE OF DIFFUSER. OPENING B OPPOSED BLADE DAMPER "TITUS" # D -75 MOUNT DIRECTLY TO DIFFUSER PRIOR TO INSTALLATION. MOUNT TIGHT TO GYP BOARD CEILING REMOVABLE INNER CORE ASSEMBLY. SPIRAL ROUND S.A. DUCTWORK ABOVE CEILING. SEE PLAN FOR DUCT SIZE. FASTEN ROUND DIFFUSER TO ROUND DUCT FROM INSIDE $ VARIES S.A. DIFFUSER BALANCE TO CFM NOTED ON PLAN. NOMINAL ROUND DUCT SIZE D B 6 12 8 16 10 20 12 24 N.T.S. MEP LOAD DATA TABULATION MARK AREA SERVED MANUFACTURER MODEL CFM E.S.P. ( "w.C.) MOTOR BAROMETRIC HP V /PH DAMPER DRIVE SPACE # : 208 EF -1 TOILET ROOM BROAN 684 80 0.125 FRAC. 120/1 YES DIRECT NAME OF TENANT: PAC SUN EF -2 TOILET ROOM BROAN 684 80 0.125 FRAC. 120/1 YES DIRECT GROSS LEASED AREA IN SQ. FT. 4616 MECHANICAL CALCULATED DESIGN HEATING LOAD MBH 67.7 NEW GRILLE, REGISTER, AND DIFFUSER SCHEDULE CALCULATED DESIGN COOLING LOAD MBH 107.5 MARK DESCRIPTION MANUFACTURER MODEL MATERIAL MODULE BACK PAN/ NECK SIZE BORDER TYPE FRONT BLADES DAMPER LANDLORD ALLOCATED AIR SUPPLY MBH N/A CD -1 CEILING DIFFUSER TITUS TMRA -AA ALUMINUM 27 "0 12 "0 ROUND FIXED CONE OPPOSED BLADE CALCULATED AIR SUPPLY CFM 4000 CD -2 CEILING DIFFUSER TITUS TMRA STEEL 13.5 "0 6 "0 ROUND FIXED CONE OPPOSED BLADE MAKE -UP AIR SYSTEMS(S)(IF APPLICABLE) CFM N/A CD -3 CEILING DIFFUSER TITUS TDC -AA ALUMINUM 15x15 SEE PLAN TYPE -1 FLANGE 4 -WAY FIXED OPPOSED BLADE TOTAL AIR SUPPLY CFM 4000 CD -4 CEILING DIFFUSER TITUS TD C STEEL 12x12 SEE PLAN TYPE -1 FLANGE 4 -WAY FIXED OPPOSED BLADE TOILET EXHAUST CFM+ 160 RG -1 RETURN GRILLE TITUS 3F ALUMINUM 32 "x26" 30 "x24" TYPE -1 SURFACE LONG NONE 1. ALL WORK SHAD_ COMPLY WITH ALL APPUCABLE FEDERAL, STATE AND LOCAL CODES, LAWS, ACTS AND ALL AUTHORITIES HAVING JURISDICTION, AND LANDLORD'S CRITERIA. 2. THE COMPLETED INSTALLATION SHALL BE IN ACCORDANCE WITH ALL APPUCABLE INDUSTRY STANDARDS OF GOOD PRACTICE AND SAFETY AND THE MANUFACTURER'S STRICTEST RECOMMENDATIONS FOR EQUIPMENT AND PRODUCT APPUCATION AND INSTALLATION. 3. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, UCENSES, DOCUMENTS AND SERVICES' RELATED TO INSTALLATION OF THE WORK AS REQUIRED. 4. PRIOR TO SUBMITTING A PROPOSAL, THE CONTRACTOR SHALL VISIT THE SITE AND THOROUGHLY INSPECT ALL EXISTING CONDITIONS TO INSURE THAT THE WORK REPRESENTED ON THE DRAWINGS AND IN THESE SPECIFICATIONS CAN BE INSTALLED AS INDICATED. 5. DUCTWORK SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH ASHRAE AND LATEST SMACNA STANDARDS. PROVIDE TURNING VANES IN ALL ELBOWS AND MANUAL VOLUME DAMPERS; IN ALL BRANCHES, SPUTTER DAMPERS, AIR EQUALIZERS, EXTRACTORS, AND SIMILAR DEVICES WHEREVER NECESSARY TO PROPERLY BALANCE THE SYSTEM AND PRODUCE A QUIET AND DRAFTLESS OPERATION. 6. DUCTWORK SHALL BE SPIRAL ROUND GALVANIZED SHEET METAL OF LOCK FORMING QUAUTY. ALL JOINTS AND SEAMS SHALL BE SEALED IN A MANNER TO PROVIDE A COMPLETE VAPORT1GHT ENCLOSURE. 24ga: UP TO 36 1'0, 22ga: 36 "0 AND OVER. FIRST 15 FEET OF DUCT FROM EQUIPMENT SHALL BE UNED 1" HEAVY DENSITY ACOUSTICAL INSULATION. 7. FLEXIBLE DUCTWORK SHALL BE THERMAFLEX "M -KE" WITH ONE INCH EXTERNAL INSULATION FINISHED WITH A VAPOR BARRIER, UL AND 90A USTED, SHALL BE EQUIPPED WITH DAMPER - EXTRACTOR AT THE SHEET METAL DUCT AND CIRCULAR COLLAR AT THE DIFFUSER, MECHANICALLY SECURED. NO FLEX DUCT SHALL BE USED IN "OPEN" CEIUNG AREAS. 8. FLEXIBLE DUCTWORK SHALL NOT EXCEED 4 FEET IN LENGTH; BENDS SHALL NOT RESTRICT THE INSIDE CROSS- SEC11ONAL AREA OF THE DUCT, AND CONNECTION SHALL BE MADE AS DIRECT AS POSSIBLE TO THE MAIN SUPPLY. NO FLEX DUCT SHALL BE USED IN "OPEN" CEIUNG AREAS, 9. ALL WORK SHALL BE LOCATED TO AVOID CONFUCTS WITH OTHER TRADES, PROVIDE ADEQUATE CLEARANCE FOR ARCHITECTURAL DESIGN, PROPER OPERATION AND SERVICE OF EQUIPMENT. 10. PROVIDE 'A READY -TO -USE SYSTEM WITH ALL WORK GUARANTEED IN WITTING AGAINST DEFECTIVE WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM TURN OVER TO TENANT. 11. CONDENSATE DRAINS: TYPE "M" HARD DRAWN COPPER FOR UNES 1" AND SMALLER, "DWV" HARD DRAWN COPPER FOR 1 -1/4" AND LARGER, CONFORMING TO ASTM B88 -72. WROUGHT COPPER FITTINGS, DRAINAGE TYPE FOR UNES 1-1/4" AND LARGER. SOLDER WITH 50/50 SOLDER. 12. DUCTWORK SHALL BE "FACTORY MADE" CLASS 1 GALVANIZED SHEET METAL WITH IRON SUPPORTS SECURED TO OVERHEAD MEMBERS AT 5' -0." DUCTWORK MATERIALS SHALL BE PER APPUCABLE MECHANICAL CODE. 13. PROVIDE DUCT SMOKE DETECTORS IN SA DUCTS, TO OVERRIDE UNIT AND PROVIDE SHUTDOWN UPON DETECTION OF SMOKE AS REQUIRED. THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM IF REQUIRED. THE ACTUATION OF THE SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND AUDIBLE SIGNAL AT A CONSTANTLY ATTENDED LOCATION. 14. PROVIDE, AS PART OF THE MECHANICAL CONTRACT, SERVICES OF AN INDEPENDENT AIR/WATER BALANCING CONTRACTOR CERTIFIED BY THE ASSOCIATED AIR BALANCE COUNCIL. SUBMIT (3) COPIES OF THE BALANCE REPORT TO THE CONSTRUCTION MANAGER. SPECIAL EXHAUST CFM 0 TOTAL EXHAUST CFM+ 160 RG -2 RETURN GRILLE TITUS 23R STEEL 18 "x18" 16 "x16" TYPE -1 SURFACE NONE HVAC NOTES NEGATIVE /POSITIVE PRESSURE (AIR SUPPLY - EXHAUST) CFM+ 3840 RG -3 RETURN GRILLE TITUS 3F ALUMINUM 18 "x18" 16 "x16" TYPE -1 SURFACE NONE CALCULATED LOSS IN DUCTWORK 0.35 CALCULATED S.P. LOSS IN DIFFUSERS AND DAMPERS ETC. 0.15 TOTAL EXTERNAL STATIC PRESSURE IN WATER COLUMN 0.5 ROUND SUPPLY AIR DIFFUSER DETAIL PLUMBING (EXISTING) SPIRAL ROUND S.A. DUCTWORK ABOVE CEILING. SEE PLAN FOR DUCT SIZE. MANUAL BALANCING DAMPER. TRANSITION S.A. DUCTWORK TO 12 "0 TO FIT 12 "0 NECK OF DIFFUSER. • 12' -6" A.F.F. S.A. DIFFUSER WITH 12 "0 NECK & 27 "0 TOTAL OUTSIDE DIAMETER. BALANCE TO CFM NOTED ON PLAN. N.T.S. DOMESTIC H_W_ HEATERS STORAGE GALLONS 0 NUMBER OF W.C. FIXTURE UNITS 10 F.U. NUMBER OF LAVATORIES FIXTURES UNITS 4 F.U. NUMBER OF COMMERCIAL SINKS 0 OTHER EQUIPMENT USAGE GPM 0.5 NOTES: 1. ALL SALES AREA AND STOCK ROOM DIFFUSERS AND GRILLES SHALL BE ALUMINUM AND REMAIN UNPAINTED. 2. ALL OTHER DIFFUSERS AND GRILLES SHALL BE STEEL AND BE STANDARD #26 WHITE FINISH. RESPONSIBILITY SCHEDULE ITEM FURMSIED MSTALLED EXIST. CONTRACTOR CONTRACTOR 0 v REMARKS MECHANICAL 1 AIR HANDLING UNIT 1 CONDENSING UNIT L T C L T C • • VAV BOXES CONTROLS SUPPLY AND DUCTWORK PER PLAN _13/A • • • • ALL DIFFUSERS / GRILLES • • THERMOSTATS • • W/ REMOTE SENSOR MECHANICAL EQUIPMENT DRAW - THROUGH UNIT Ste_ H 2 H 2 S EXTEND AIR VENT TO ATMOSPHERE NOTE: H= TOTAL FAN STATIC PRESSURE S= SAFETY ALLOWANCE = 1" UNION TO INDIRECT WASTE RECEPTOR N.T.S. ROUND SUPPLY AIR DIFFUSER DETAIL METAL LOCKING COVER(S) TOILET ROOM EXHAUST FAN TAPE AROUND SNUGGLY Z WRAPS PRIOR TO INSTALLING LINE STRAP FLEXIBLE DUCT MAX. 4' -0" LENGTH GYP BOARD CEILING -\ 2" i ROUND S.A. DUCTWORK ABOVE CEILING. SEE PLAN FOR DUCT SIZE. 1" WIDE x 20 GA.I STRAP W/ TIGHTENING SCRE�J SECURE STRAP W/ SHEET METAL SCREWS 3 O.C. MAX. 24 "x24" "TITUS" TRM -RAPID MOUNT FRAME 24 "x24" "TITUS" MODEL # TDC, ROUND NECK (SEE SHEET M1 FOR NECK SIZE) BORDER TYPE 3- LAY -IN DIFFUSER N.T.S. AIR BALANCE REPORT BY INDEPENDENT CONTRACTOR • • • FIRE DAMPERS • • • • • AS REQUIRED DRAW- THROUGH CONDENSATE DRAIN DETAIL SMOKE REMOVAL SYSTEM • INCL ALL CONTROLS AND STARTER MOTORS MODIFY SPRINKLER SYS. • • SEQUENCE OF CONTROL ROUND SUPPLY AIR DIFFUSER DETAIL 1. SELECTOR SWITCH IN "ON" POSITION, SYSTEM IS RUNNING. A. OUTSIDE AIR TEMPERATURE ABOVE 60 DEG. 1. OUTSIDE AIR DAMPER TO BE AT MINIMUM POSITION (BALANCE TO 835 CFM FOR AHU -1) 2. RETURN AIR DAMPER FULLY OPEN. 3. RELIEF AIR DAMPER CLOSED. 4. ROOM THERMOSTAT MODULATES COOLING CYCLE (CU -1) TO MAINTAIN 75 DEG. F. B. OUTSIDE AIR TEMPERATURE BELOW 60 DEG. F. 1. COOLING CYCLE (CU -1) DE- ENERGIZED. 2. OUTSIDE AIR DAMPER FULLY OPEN. 3. RETURN AIR DAMPER FULLY CLOSED. 4. RELIEF AIR DAMPER FULLY OPEN. 5. ROOM THERMOSTAT CYCLE SUPPLY FAN TO MAINTAIN 75 DEG. F. 6. WHEN OUTSIDE AIR DAMPER IS AT MINIMUM POSITION RETURN AIR DAMPER FULLY OPEN AND ROOM TEMPERATURE FALLS BELOW 70 'F, THERMOSTAT SHALL ACTIVATE HEATING CYCLE (HEATPUMP & ELECT. HEAT) TO MAINTAIN ROOM TEMPERATURE OF 70 F. C. SMOKE IS DETECTED. 1. A/C SYSTEM DE- ENERGIZED. 2. OUTSIDE AIR DAMPER FULLY CLOSED. 1 NOTE: PRIOR TO CONSTRUCTION/ BID THE CONTRACTOR SHALL VISIT THIS SITE AND FIELD VERIFY THE EXISTING LOCATIONS AND SIZES OF ANY LANDLORD PROVIDED, OR EXISTING, OUTSIDE AIR INTAKES THROUGH ROOF, LANDLORD PROVIDED CHILLED/HOT WATER PIPING MAINS, TOILET EXHAUST MAINS, OUTSIDE AIR DUCTWORK, CONDENSATE UNE MAINS, ETC. THE CONTRACTOR SHALL FIELD VERIFY ANY/ CONDITIONS WHICH MAY CONFLICT WITH THE DESIGN SHOWN ON THESE PLANS. NOTIFY ARCHITECT IMMEDIATELY. REVIEWED FOR CODE COMPLIANCE APPROVED JUL 19 2011 City of Tukwila BUILDING DIVISION 1. ALL WORK TO BE PER THE LANDLORD REQUIREMENTS, AS WELL AS ALL LOCAL CODES, RULES AND REGULATIONS. ALL WORK TO BE PER ASHRAE AND SMACNA GUIDEUNES. 2. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE. ALL DUCTS TO BE SHEET METAL DUCTS PER ASHRAE AND SMACNA GUIDEUNES. 3. PROVIDE NECESSARY TURNING VANES, SPUTTER DAMPERS. VOLUME EXTRACTORS AND OTHER FEATURES NEEDED FOR A SMOOTH AND CONTROLLED FLOW OF AIR. 4. LOCATIONS SHOWN OF HVAC EQUIPMENT AND DUCTS ARE SCHEMATIC ONLY (EXCEPT AS NOTED). VERIFY STRUCTURAL AND OTHER DETAILS THAT WILL AFFECT ROUTING AND PLACEMENT OF THESE COMPONENTS. IF MORE SUPPORTS ARE NEEDED FOR HVAC EQUIPMENT, COORDINATE WITH THE ARCHITECT. 5. PROVIDE PROPER DUCT TRANSITIONS FOR ACTUAL HVAC UNITS INSTALLED. ROOF PENETRATIONS (IF ANY) TO BE MADE PER LANDLORD REQUIREMENTS. VERIFY DETAILS WITH MALL MANAGEMENT. 6. PROVIDE AND INSTALL THERMOSTATS AS SHOWN ON SHEET M100. VERIFY EXACT LOCATIONS WITH CONSTRUC110N MANAGER. 7. COORDINATE ACTUAL LOCATIONS OF DIFFUSERS, REGISTERS AND GRILLES WITH CEIUNG DETAILS AND OTHER FEATURES SUCH AS UGHTING FIXTURES, ETC. THAT MAY AFFECT PLACEMENT OF THE HVAC SYSTEM COMPONENTS. 8. TENANT GC SHALL SUPPLY ALL EQUIPMENT CONTROLS AND WIRING. COORDINATE WITH MALL MANAGEMENT FOR INTERLOCKING WITH MALL CONTROL SYSTEM (AS REQUIRED). DUCTWORK SYMBOLS SINGLE DOUBLE ABBR. DESCRIPTION • RECTANGULAR DUCT C Pd • ROUND DUCT Jr 4- • 45 DEG. TAP: USE AT BRANCH DUCTS ONLY • • • DUCT SPUT W/DAMPER: USE AT ELBOWS AND TEES: PROPORTION DUCT AREAS BY CFM'S CURVED ELBOW -MIN. RADIUS R: 1.5 WIDTH 90 DEG. ELBOW WITH SINGLE RADIUS TURNING VANES • FLEXIBLE DUCT CONNECTION L r 7 FD FIRE DAMPER err BD EALANCING DAMPER (USE 0.B.D. UNLESS NOTED OTHERWISE) NEW TO EXISTING CONNECTION • SPIN -IN FLEX DUCT TAKE -OFF W/DAMPER • SA SUPPLY AIR • EXH EXHAUST AIR • RA RETURN AIR • REL REUEF AIR OSA OUTSIDE AIR • REMOTE TEMPERATURE SENSOR X: UNIT OR ZONE NUMBER T THERMOSTAT W/ METAL LOCKING COVER SD DUCT SMOKE DETECTOR RECEIVED JUN 08 2011 PERM TCENTEF 530 Pncsun. COPYRIGHT NOTICE: These drawings and specifications are copyrighted and subject to copyright protection as an "architectural work" under sec. 102 of the copyright act, 17 u.S.C. As amended January 2003. The protection includes, without limitation, the overall form, arrangement and composition of spaces, and elements of the design. Under such protection, unauthorized use of these drawings and specifications may result in cessation of construction, building seizure, and /or monetary liability. 0_ a_ i (/) � co al � N a) cu.% o 0 "5 co O u) • REVISION NUMBER AND DATE 1NP MEC ANICAL, INC. 1717 W NORTHERN AVE. SUITE 116 PHOEP1 ARIZONA 85021 PROJECT NO. 11089 EXPIRES 08/12/12 DATE: SHEET: 5t2412011 AS NOTED m200 DRAWN BY: AR SCALE: PROJECT No.: PSN -10 -016