HomeMy WebLinkAboutPermit PG10-174 - PACIFIC COURT COMMUNITY BUILDINGPACIFIC COURT
COMMUNITY BUILDING
4028 S 146 ST
PG1O-174
City ATukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Inspection Request Line: 206 - 431 -2451
Web site: http: //www.ci.tukwila.wa.us
PLUMBING /GAS PIPING PERMIT
Parcel No.: 0040000250
Address: 4028 S 146 ST TUKW
Project Name: PACIFIC COURT COMMUNITY BUILDING
Permit Number:
Issue Date:
Permit Expires On:
PG10 -174
01/04/2011
07/03/2011
Owner:
Name: HOUSING AUTH
Address: 600 ANDOVER PARK W , TUKWILA WA 98188
Contact Person:
Name: LARRY THOMAS
Address: 9505 NE 84 CT , VANCOUVER WA 98662
Email: LARRY @THEGRINNELGROUPINC.COM
Contractor:
Name: UNLIMITED MECHANICAL INC
Address: PO BOX 1457 , MARYSVILLE WA 98270
Contractor License No: UNLIMMI093M6
Phone: 360 367 -1753
Phone: 360 - 657 -2182
Expiration Date: 05/13/2012
DESCRIPTION OF WORK:
PLUMBING FOR NEW SINGLE STORY 1454 SF COMMUNITY BUILDING WITH (2) BATHROOMS AND
A SMALL KITCHEN FACILITY
Value of Plumbing /Gas Piping: $8,500.00 Uniform Plumbing Code Edition: 2009
Fees Collected: $242.81 International Fuel Gas Code Edition: 2009
Permit Center Authorized Signature:
Date: U/ /G' `t' ///
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work.will- be-complie• with, whether specified herein or not.
The grant g of this permit doe presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction
on the back o this • - t.
ormance of work. I am authorized to sign and obtain this plumbing /gas piping permit and agree to the conditions
Signature:
Print Name:
Date: 4 -2v3(
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: UPC -4/10
PG10 -174 Printed: 01 -04 -2011
• •
PERMIT CONDITIONS
Permit No. PG 10 -174
1: ** *PLUMBING AND GAS PIPING * **
2: No changes shall be made to applicable plans and specifications unless prior approval is obtained from the Tukwila
Building Division.
3: All permits, inspection records and applicable plans shall be maintained at the job and available to the plumbing
inspector.
4: All plumbing and gas piping systems shall be installed in compliance with the Uniform Plumbing Code and the Fuel Gas
Code.
5: No portion of any plumbing system or gas piping shall be concealed until inspected and approved.
6: All plumbing and gas piping systems shall be tested and approved as required by the Plumbing Code and Fuel Gas Code.
Tests shall be conducted in the presence of the Plumbing Inspector. It shall be the duty of the holder of the permit to
make sure that the work will stand the test prescribed before giving notification that the work is ready for inspection.
7: No water, soil, or waste pipe shall be installed or permitted outside of a building or in an exterior wall unless,
adequate provision is made to protect such pipe from freezing. All hot and cold water pipes installed outside the
conditioned space shall be insulated to minimum R -3.
8: Plastic and copper piping running through framing members to within one (1) inch of the exposed framing shall be
protected by steel nail plates not less than 18 guage.
9: Piping through concrete or masonry walls shall not be subject to any load from building construction. No plumbing
piping shall be directly embedded in concrete or masonry.
10: All pipes penetrating floor /ceiling assemblies and fire - resistance rated walls or partitions shall be protected in
accordance with the requirements of the building code.
11: Piping in the ground shall be laid on a firm bed for its entire length. Trenches shall be backfilled in thin layers to
twelve inches above the top of the piping with clean earth, which shall not contain stones, boulders, cinderfill,
frozen earth, or construction debris.
12: The issuance of a permit or approval of plans and specifications shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the Plumbing Code or Fuel Gas Code or any other ordinance of the
jurisdiction.
doc: UPC -4/10
PG10 -174 Printed: 01 -04 -2011
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
httn://www.ci.tukwila.wa.us
Building Permit No.
Mechanical Permit No.
Plumbing /Gas Permit No.
Public Works Permit No.
Project No.
AAA
•
pttno --o
(For office use only)
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
SITE LOCATION 1L.1.11_gt
King Co Assessor's Tax No.:S47c9-)
Site Address: 4507U S 14041 --77--\(-"""∎ I ti•P• Suite Number:
Floor:
Tenant Name: ` New Tenant: ❑ Yes ..11-.".N..11-.".No Property Owners Name: ¥ Lb p - '■-'"l I`-J` 4"‘,Nte..... (
Mailing Address: CesM lr;3)- `....fh'-c-0.-- , \ t_is, t t \# 9,1Vv
City State Zip
CONTACT PERSON - who do we contact when your permit is ready to be issued
Name: L- Day Telephone ..C-07
Mailing Address: — 84'r7-1 "Ik G%8 692,z.
City State Zip
E -Mail Address:iOk t^I"r C' �'/ Y� /� �7 e iiCx r., SAL , C-J Fax Number: 7� (2,4C0
GENERAL CONTRACTOR INFORMATION -
(Contractor Information for Mechanical (pg 4) for Plumbing and Gas Piping (pg 5))
Company Name: 1
Mailing Address:
Contact Person:
E -Mail Address:
Contractor Registration Number:
City
Day Telephone:
Fax Number:
Expiration Date:
State
Zip
ARCHITECT OF RECORD - All plans must be stamped by Architect of Record
Company Name:
Mailing Address:
City
Contact Person: Day Telephone:
Fax Number:
E -Mail Address:
State
Zip
ENGINEER OF RECORD - All plans must be stamped by Engineer of Record
Company Name:
Mailing Address:
City
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
State
Zip
H:\Applicalions \Forms- Applications On Line \2010 Applications\ 7-2010 - Permit Application.doc
Revised: 7- 2(111)
bh
Page 1 of 6
PLUMBING AND GAS PIPING PERMIT INFORMATION — 206 - 431 -3670
PLUMBING AND GAS PIPING CONTRACTOR INFORMATION
Company Name:
/j`.i t LL.�
Mailing Address: l4 j 7
Contact Person: \i6,,1�` -t \ i ' " S
E -Mail Address:INFO.a) tr-d( Lo
City
State Zip
Day Telephone: 1 tDZC
Fax Number: �Z-
Contractor Registration Number:13 t.I t 41-�1 1'b 1" 10 Expiration Date: a
Valuation of Plumbing work (contractor's bid price): $ 8
Valuation of Gas Piping work (contractor's bid price): $ tD
Scope of Work (please provide detailed information): tiZ�d' ��` f"`
r
lMn•51..) 1-,-, '-ya,3L.Liz,L 2 �1 r- �9- s? -v�MS {L � � {' S -1 Ott 1L t tip z `r\1
Building Use (per Intl Building Code): ce-ok_A-
Occupancy (per lnt'l Building Code): fB'
Utility Purveyor: Water: 1j1 Sewer:�W- L�- -L�`•1 ��1v
Indicate type of plumbing fixtures and /or gas piping outlets being installed and the quantity below:
Fixture Type:
Qty
Fixture Type:
Qty
Fixture Type:
Qty
Fixture Type:
Qty
Bathtub or combination
bath /shower
Bidet
Clothes washer, domestic
Dental unit, cuspidor
Dishwasher, domestic,
with independent drain
1
Drinking fountain or
water cooler (per head)
Food -waste grinder,
commercial
Floor Drain
Shower, single head trap
Lavatory
Wash fountain
Receptor, indirect waste
Sinks
(
Urinals
Water Closet
Building sewer and each
trailer park sewer
r
Rain water system — per
drain (inside building)
Water heater and /or vent
1
Industrial waste treatment
interceptor, including trap
and vent, except for kitchen
type grease interceptors
Each grease trap
(connected to not more
than 4 fixtures - <750
gallon capacity)
Grease interceptor for
commercial kitchen ( >750
gallon capacity) ,
Repair or alteration of
water piping and/or water
treatment equipment
Repair or alteration of
drainage or vent piping
Medical gas piping
system serving 1 -5
inlets /outlets for a
specific gas
Each additional medical
gas inlets /outlets greater
than 5
Backflow protective
device other than
atmospheric -type vacuum
breakers 2 inch (51 mm)
diameter or smaller
Backflow protective device
other than atmospheric -type
vacuum breakers over 2
inch (51 mm) diameter
Each lawn sprinkler
system on any one meter
including backflow
protection devices
Atmospheric -type vacuum
breakers not included in
lawn sprinkler backflow
protections (1 -5)
1
Atmospheric -type
vacuum breakers not
included in lawn
sprinkler backflow
protections over 5
Gas piping outlets
H: \ApplicationsWorms- Applications On Line \2011) Applications \7 -2010 - Permit Application.doc
Revised: 7- 2010
bh
Page 5 of 6
PERMIT APPLICATION NOTES — Applicable to all permits in this application
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
Building and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
Plumbing Permit
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing Code (current edition).
I HEREBY
PENALTY OF
TIFY THAT 1 HAV
RJURY B
BUILDING OWNER OR AUT
Signature:
READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
AWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
ZEDA
Pri ame:
Mailin
Date: _ /( —1 (-75
Day Telephoner 73— -3
\/fr V i V gegLoCvZ
Date Application Accepted:
121Iu If
City State Zip
Date Application Expires:
H:\Applications \Forms- Applications On Line \2010 Applications \7 -2010 - Permit Application.doc
Revised: 7 -2010
bh
tle(
Staff Initials:
Page 6 of 6
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
RECEIPT
Parcel No.: 0040000250 Permit Number: PG 10 -174
Address: 4028 S 146 ST TUKW Status: PENDING
Suite No: Applied Date: 12/16/2010
Applicant: PACIFIC COURT COMMUNITY BUILDING Issue Date:
Receipt No.: R10 -02511
Initials:
User ID:
Payee:
JEM
1165
Payment Amount: $242.81
Payment Date: 12/16/2010 11:56 AM
Balance: $0.00
GREG GRINNELL
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 075514
ACCOUNT ITEM LIST:
Description
242.81
Account Code Current Pmts
PLAN CHECK - NONRES
PLUMBING - NONRES
000.345.830 48.56
000.322.103.00.00 194.25
Total: $242.81
doc: Receiot -06 Printed: 12 -16 -2010
INSPECHON NO.
INSPECTION RECORD
R etain a co with P- p ermit
PERMIT NO. ',
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
P�o,I'ect:
6 it_ ` 1' L
...... ----
Lry J i-/
Type of Inspection:
JAL - P u /t2 %� r
Address:
4O2ir
i4
i44 sr-
Date Called:
Special Instructions:
6 S (3 3 2---zo t -r
/
Date Wanted: ( .m.
-7 -- (5 --( p.m.
Requester:
Phone No:
? S3 — gF2,-7 St) c
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
nP t t 7 „> dL. nL n
P
InspectC r:
0,4 fik--8
Date:-7 � ( S—((
n REINSP OICTE N FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
I
6300
Permit Inspection Request Line (206) 431 -2451
— ��,�INSPECTION RECORD
Retain a copy with permit t /e' /7 '
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
Southcenter Blvd., #100, Tukwila. WA 98188 (206) 439' -3670
Pro' t:
` 4C nrie
Ir7"--
Type of Inspection:
i7 Oil 4 - / Ai )04/01A
Address:
- 1/0.26 t..
/1/6
Date Called:
`
Special Instructions:
0,1-462-
6 !
Date Wanted:
p A -19 ri 4
a.:f`
Requester:
i (\,,, ie.___, t.,-.
Phone No:
-moo— 726
- * --
$tt-o
Approved per applicable codes.
Corrections required prior to approval. 54
;
COMMENTS:
`
Crude
n vu u A'
p A -19 ri 4
,,,) ,a,„ Lfe.,,,i-u
i (\,,, ie.___, t.,-.
$tt-o
b r
1
A
Inspectq
Date: 1 — — +(
n REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
(r=
INSPECTION RECORD
Retain a copy with permit
INSPECTION 0. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION ‘42'
6300 Southcenter Blvd., #100, Tukwila. WA 98188
Permit Inspection Request Line (206) 431 -2451
(206) 431 '3670
Project:
P�0 %.f'.( &A .edT6�< t, • �3,,,/
Type of Inspection:
/u -,e
Address:
�42g 3
O`L/.6 37
Date Called:
O r f —r
Special Instructions:
'
Date Wanted:
® e. .5.---- /
rn'
Requester:
Phone No:
...7a--772-6,32?...
�-
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
I rr ik — cu p I) Cdr u . . 1 o 1Q.
,- _ n A : rivl , (tit 11(>,p ` J , F
.---5 ,. i I- .. (71-1;`,,-1
O r f —r
''',sr us e.-d ,
1 A n
-,
Inspector:
i�
Date: g _I/
n REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
06 -01 -2011
City of Tukwila
Jim Haggerton, Mayor
Department of Community Development Jack Pace, Director
LARRY THOMAS
9505 NE 84 CT
VANCOUVER WA 98662
RE: Permit No. PG10 -174
4028 S 146 ST TUKW
Dear Permit Holder:
In reviewing our current records, the above noted permit has not received a final inspection by the City of
Tukwila Building Division. Per the International Building Code, International Mechanical Code, Uniform
Plumbing Code and /or the National Electric Code, every permit issued by the Building Division under the
provisions of these codes shall expire by limitation and become null and void if the building or work authorized
by such permit has not begun within 180 days from the issuance date of such permit, or if the building or work
authorized by such permit is suspended or abandoned at any time after the work has begun for a period of 180
days. Your permit will expire on 07/27/2011.
Based on the above, you are hereby advised to:
1) Call the City of Tukwila Inspection Request Line at 206 - 431 -2451 to schedule for the next or final
inspection. Each inspection creates a new 180 day period, , provided the inspection shows progress.
-or-
2) Submit a written request for permit extension to the Permit Center at least seven (7) days before it is
due to expire. Address your extension request to the Building Official and state your reason(s) for
the need to extend your permit.
The Building Code does allow the Building Official to approve one extension of up to 180 days. If it is
determined that your extension request is granted, you will be notified by mail.
■
In the event you do not call for an inspection and /or receive an extension prior to 07/27/2011, your permit will
become null and void and any further work on the project will require a new permit and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
dc)(.- -V—_,L
Bill Rambo
Permit Technician
File: Permit File No. PG10 -174
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665
HERMIT COORD COPY •
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: PG10 -174 DATE: 12/16/10
PROJECT NAME: PACIFIC COURT COMMUNITY BUILDfNG
SITE ADDRESS: 4028 S 146 ST
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter # Revision # after Permit Issued
DEPARTMENTS: `.� � CD
Building 414, vision
22Vicr s \111
Fire Prevention
Structural
Planning Division
❑ Permit Coordinator ❑
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Incomplete ❑
DUE DATE: 12/21/10
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROUTING:
Building
Please Route
REVIEWER'S INITIALS:
Structural Review Required ❑ No further Review Required ❑
DATE:
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
Notation:
REVIEWER'S INITIALS:
DUE DATE: 01/18/11
Not Approved (attach comments) ❑
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents/routing slip.doc
2 -28 -02
Contractors or Tradespeople Peter Friendly Page
Page 1 of 1
General /Specialty Contractor
A business registered as a construction contractor with LEti to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent Company
UNLIMITED MECHANICAL INC
3606572182
Po Box 1457
Marysville
WA
98270
Snohomish
Corporation
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Specialty 1
Specialty 2
601329467
Active
UNLIMMI093M6
Construction Contractor
7/26/1991
5/13/2012
Fire Protect System
Unused
iated Licenses
License
Name
Type
Specialty
1
Specialty
2
Effective
Date
Expiration
Date
Status
WWPLU "159MJ
W W PLUMBING
Construction
Contractor
Plumbing
Unused
7/11 /1985
3/12/1987
Archived
EMERACP150DL
EMERALD CITY
PLUMBING
Construction
Contractor
Plumbing
Unused
3/13/1985
3/12/1986
Archived
Business Owner Information
https: // fortress .wa.gov /lni/bbip /Print.aspx 01/03/2011
MECHANICAL LEGEND-
CD
RL
- RS REFRIGERANT SUCTION PIPING
SANITARY WASTE
SANITARY VENT
DOMESTIC HOT WATER
DOMESTIC HOT WATER RECIRCULATION
DOMESTIC COLD WATER
CONDENSATE DRAIN
REFRIGERANT UQUID PIPING
Cis - x)
ELBOW, 90•
ELBOW, 45•
ELBOW, TIJRNING UP OR TOWARD
ELBOW, TURNING DOWN OR AWAY
BALL VALVE
EXHAUST FAN
MECHANICAL. EQUIPMENT
CFM
OA
RA
CROSSING LINES: NON--CONNECTING
(TOP OR FRONT PIPE IS SHOWN AS soup LiNq
BREAK IN PIPE (USE WHERE SECTION OF PIPING
IS OMITTED FROM DRAWING FOR CLARITY)
PLUMBING FIXTURE CALL-OUT
EQUIPMENT CALL-OUT
CUBIC FEET PER MINUTE
OUTSIDE AIR
RETURN AIR
SA SUPPLY AIR
WH WALL HYDRANT
001
GC
EC
MC
THERMOSTAT
CARBON DIOXIDE SENSOR
GENERAL CONTRACTOR
ELECTRICAL CONTRACTOR
MECHANICAL CONTRACTOR
GENERAL NOTES
1. DO NOT SCALE PLANS. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATION AND INSTALLATION OF MECHANICAL sTbIEMS.
2. MECHANICAL DRAWINGS ARE DIAGRAMMATIC ONLY. ACTUAL SIZE AND LOCATION OF EQUIPMENT,. DUCTWORK AND PIPING MAY
VARY DUE TO MANUFACTURER OR ACTUAL FIELD CONDMONS. rr SHALL BE THE CONTRACTOR S RESPONSIBILITY TO
COORDINATE THE INSTALLATION OF MECHANICAL SYSTEMS WITH OTHER TRADES AND SYSTEMS SO AS TO PROVIDE ADEQUATE
CLEARANCE AND ACCESSIBILITY AS REQUIRED BY MANUFACTURER'S RECOMMENDATIONS AND AS SHOWN ON PLANS.
3. ALL DUCTWORK SHALL BE SEALED PER IMC AND SMACNA.
4. CONCEAL ALL PIPING AND DUCTWORK INSIDE WALLS AND ABOVE CEILINGS UNLESS SHOWN OTHERWISE
5. REFER TO ARCHITECTURAL PLANS AND ELECTRICAL PLANS PRIOR TO INSTALLING MECHANICAL SYSTEMS TO VERIFY LOCATIONS
OF OTHER BUILDING SYSTEMS.
6. REFER TO ARCHITECTURAL PLANS TO VERIFY ALL LOCATIONS OF NEW FIRE RATED ASSEMBLIES. ALL DUCT PENETRATIONS
OF FIRE RATED ASSEMBUES SHALL BE PROTECTED BY FIRE DAMPERS.
7. FIRE SAFE ALL DUCT AND PIPE PENETRATIONS THROUGH FIRE RATED ASSEMBLIES.
8. G.C. SHALL PROVIDE PRELIMINARY REPORT AND COMPLETE SYSTEM COMMISSIONING PER WASHINGTON STATE ENERGY CODE SECTION 1416, AND THE
COMMISSIONING GUIDEUNES, AS PUBLISHED BY THE BUILDING COMMISSIONING ASSOCIATION.
9. ALL DOMESTIC WATER PIPING SHALL BE INSULATED PER WASHINGTON STATE ENERGY CODE.
FAN SCHEDULE
MARK
SERVICE
LOCATION
FAN DATA
MOTOR DATA
WHEEL
TYPE
WHEEL
DIA(IN)
BLADE
TYPE
CFM
TOTAL
S.P.
IN W.G.
DRIVE
TYPE
AMPS
V.
PH.
MAX.
SONES
BASIS OF DESIGN
NOTES'
EF-1
TOILET
CEILING
CENT
6
BI
50
EF-2
RANGE HOOD
KITCHEN
CENT
7
BI
100
DIRECT
DIRECT
.2
120
.3
1.2
120
.9
EF-3
MEETING RM
CEILING
CENT
BI
150
.1
DIRECT
.5
120
1.4
BROAN QTXE050
BROAN QDE 30SS
1
2
BROAN QTXE150
3
NOTES:
1. SWITCH WITH UGHTS.
2. INTEGRAL FAN AND LIGHT SWITCH TO BE RE-WIRED TO WALL SWITCHES BY E.C. FOR ADA OPERATION.
3. PARALLEL CONTROL WITH WALL SWITCH AND CO2 DETECTION: GET8012
ELECTRIC HEATER SCHEDULE
MARK
EH -1
EH-2
SENS
CAP
(MBH)
41 4732
74
ELECTRICAL DATA
KW
STEPS
VOLT
PH
BASIS OF DESIGN
NOTES
.42
1.4
1
1
240
240
KING KCV 2404
1
KING KCV 2415
1,2
EH-3
.3387
0.7
1
EH-4
3188
.94
1
240
240
KING KCV . 2407
1,2
1
KING KCV 2410
1,2
EH-5
716
.21
1
120
1
KING KCV 1202
1,2
NOTES:
1. PROVIDE WITH REMOTE LINE VOLTAGE THERMOSTAT TH110P
2. (2) OF THESE.
FAN COIL UNIT SCHEDULE
MARK
FC -1
CFM
350
EXT.
STATIC
PRESS.
(IN. W.G.)
0.00
DX COIL DATA (13410A)
E.A.T SENS. TOTAL E.A.T 0.A
DB/WB CAP. CAP. DB HEATING CFM
(CLG) (MBH) (MBH) HTG. (MBH)
75/63
6.0
9.0
70
8.6
0
ELECT. DATA
HP. V. PH. MCA
(W)
0.02
240
0.4
CON FIG.
WALL
BASIS OF DESIGN
EMI - WLHGO9D0
NOTES
1
NOTES:
1. EXTEND CONDENSATE DOWN INSIDE OF WALL TO 6" ABOVE GRADE.
HEAT PUMP SCHEDULE -- AIR SOURCE - R41OA
MARK.
CONDENSER DATA
CFM S.P
(IN.
W.G.)
HP-1
600
0.0
E.A.T. E.A.T.
DEG.F. DB/WS
LG.
(DEG.F.)
C
80
21
80/67
TOOLING
TOT.
OAP.
(MBH)
9.0
DATA
SENS.
CAP.
(MBH)
6.0
ELEC.
INPUT
(KW)
.7
HEATI
E,kT.
DB
(DEG.F.)
70'
NG DATA
SENS.
CAP.
(MBH)
8.6
ELEC.
INPUT
(KW)
ELECTRICAL DATA
V. PH. RLA MCA
MOCP
SEER
COP
EQUIP
SOUND
DATA
DB
BASIS OF DESIGN
NOTES
.7
240
4.7
5.7
15
13
3.3
45
EMI - S1 HG9000D
NOTES: 1. INSTALL ON GRADE NORTH OF BUILDING. PROVIDE WITH 10' UINE SET AND WALL MOUNTED PROGRAMMABLE THERMOSTAT.
PLUMBING FIXTURE CONNECTION SCHEDULE
UNIT NO.
FIXTURE
LOCAL CONNECTIONS
CW.
HW.
WASTE
VENT
REMARKS
NOTES
P-1
WATER CLOSET
1/2
2
1.6 GPF TANK TYPE, ADA COMPLIANT
P-2
LAVATORY
1/2
1/2
1-1 /4
1-1/4
ADA COMPLIANT
P-3
FD
KITCHEN SINK
FLOOR DRAIN
1/2
TRAP PRIMER
1/2
1-1/2
1-1/2
2
1-1/2
ADA COMPLIANT
JR SMITH 2005 - 2"
WH
WALL HYDRANT
1/2
WOODFORD B65
2
NOTES: i . PROVIDE WITH TRAP PRIMER CONNECTION
2. MOUNT ON NORTH WALL BESICE KITCHEN
DOMESTIC WATER HEATER -- ELECTRIC
MARK S
SERVES L
LOCATION K
KW V
VOLTAGE G
GALLONS B
BASIS OF DESIGN N
NOTES
WH -1 B
BUILDING K
KITCHENETTE 2
2.5 2
240/1 2
20 A
A.O. SMITH EJCS-20 1
1,2
NOTES:
1. MOUNT UNDER KITCHEN COUNTER
2. PROVIDE WITH BLADDER TANK BT-1; AMTIROL. ST-5
MISCELLANEOUS MECHANICAL EQUIPMENT SCHEDULE
MARK
DESCRIPTION
SERVES
BASIS .OF DESIGN
NOTES
COS- 1
CARBON DIOXIDE SENSOR
M EMT NG ROOM
GE T8012
CP-1 HOT WATER RECIRCULATING PUMP
DOMESTIC HOT WATER
BELL AND GOSSETT NBF-8S/LW
NOTES: 1. BRONZE WET ROTER CIRCULATOR. 100% LEAD FREE. 3 GPM CD 6 FT HEAD. 39 WATTS 0 120v
2. PROVIDE WITH AQ-1/2 AO UA.STAT. CONNECT AQUASTAT UPSTEAM OF PUMP ON COPPER RECIRCULATION PIPE.
1,2
SEPARATE PERMIT
REQUIRED FOR:
<Mechanical
Electrical
0 Plumbing
t"Gas Piping
City of Tukwila
lEiljPJ?ING DIVISION
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE': Revisions will require a new plan submittal
and may include additional plan review fees. j
FI
Permit No.
COPY
Plan review approval is subject to errors and omissions.
kpproval of construction documents does not authorize
vio ed code or ordinance. Receipt
of approv anct1.s acknowledged
City Of Tukwila
BUILDING DIVISION
-REVIEWED FOR
CODE COMPLIANCE
APogNIVED
DEC 28 2010
utf---
City of Tukwila
BUILDING DIVISION
CITYRMILA
DEC 1 6 2010
PERMIT CENTER
Aardvark Engineering Services
2940 WESTLAKE AVE., SUITE: 301
Seattle, Washington 98109
(206) 281-7379 fax (206) 352-7231
a)
CO
cis
E
0
cr)
:=7L-
a)
a)
92
cs)
0
u_
<-
_c
o 0
0 06 0
_c
L.b)
0
c0
_J a)
75 :P-
o 5
'E ED
O • 0
o
Architecture & Urban Design
204 First Avenue South, Seattle, Washington 98104
PHONE: (206) 624 7880 / FAX: (206) 622 1766
Ca
143; 40
ti)
0 Z
P.
ST
ru
US
10
DRAWING ISSUE
BID SET: JULY 12,2010
DRAWING TITLE
MECHANICAL LEGENC
& SCHEDULES
SCALE: 1/4"
PLOT DATE: JULY 12 2010
CAD FILE: M-O.DWG
PROJ. MGR.: RL
DRAFTER: ELA
SHEET NO
I= 0
a)
CO
cis
E
0
cr)
:=7L-
a)
a)
92
cs)
0
u_
<-
_c
o 0
0 06 0
_c
L.b)
0
c0
_J a)
75 :P-
o 5
'E ED
O • 0
o
R-10
INSULATING
BASE
IE-ELECTRIC
WATERWAY
CONNECTORS
SIGHT GLASS
AQUA STAT
.71/2"HWR
- -
—THERMOMETER
NOTE:
G.C. TO PROVIDE CLOSURE PANEL
UNDER COUNTER
SEISMIC
BRACES
EXTEND P&T
TO F.D.
ELECTRIC WATER HEATER-1
CONNECTION DIAGRAM
NOT TO SCALE
1/4" LIQUID
1/2" SUCTION
SIGHT GLASS
R - 410A THERMOSTATIC HEAT PUMP EXPANSION VALVE
00(6, heal-ot ym)51--- he,
a cuod
UNDER.
COUN
1— 1 /2'1VIR
/ O 1/2"V
C
r-
10
WALL
CAP
0"X3— 1/4
PLAN NOTES:
0 INSTALL BOTH SHUT-OFF BALL VALVES
BEHIND LOCKING STEEL ACCESS PANEL.
MILCOR - 3601-014-4 OR EQUAL.
0 SPACE VENTILATED BY OPERABLE WINDOW.
0 SPACE VENTILATED BY EXHAUST FAN, ACTIVATED
BY CO2 SENSOR.
EXHAUST TO ROOF CAP
0 36"X1C" CONCRETE PAD BY G.C.
(1) INSTALL LOCKING WALL HYDRANT.
0 UNDERCUT DOORS 3/4" FOR VENTILATION
AIR FLOW.
RL
SCHRADER CHARGING VALVE
- RS
REFRIGERANT VALVE
HEAT PUMP
FILTER DRYER
REFRIGERANT VALVE
SCHRADER CHARGING VALVE
REFRIGERANT PIPING DETAIL
NOT TO SCALE
NOTE:
ALL REFRIGERATION PIPING
SPECIALTIES SHOWN SHALL
BE PROVIDED BY MECHANICAL
CONTRACTOR.
CONNECT TO
EXISTING SAN
SEWER
2
P-3
KITCHEN
HWR
UNDER
SLAB
INSULATE
2"
1/2" I-1W
UNDER
SLAB
\ INSULATE
M ETING
OOM
/ OF IkE
75 SF
/3"
AIL
COMMUNITY SPACE
620 SF
0
3/4" CW
UNDER SLAB
tri-1-7/
1
1
1
1
1
WO EN
3/4"CD
0 RADE
1 4''RL.
1/2''RS
1 OFFICE
I 220 SF
1
------ --
00
1.
,'MEETING ROOM
1 40 SF
4:411,
o AT7 •
P-2
HALL
STORAGE
ITCHEN BUIL
SHUT SHU
OF OFF
•
MEN
G
0
11
r
()--(Tt) LEu
-- / 4"
--Jo
3/4"WATER
FROM METER
(SEE CIVIL)
\ ,,
\ 2
\
i1/4 "......,,,,i4N . / ----........,...\
00
PACIFIC COURT COMMUNITY BUILDING FLOOR PLAN •
1,454 SF
REVIEWED FOR
CODE COMPUANCE
APPROVED
DEC 28 2010
City of Tukwila
BUILDING mem
AS$TUSILA
uEC 1 6 2010
PERMIT CENTER
Aardvark Engineering Services
2940 WESTLAKE AVE., SUITE: 301
Seattle, Washington 98109
(206) 281-7379 fax (206) 352-7231
Ioyi
Urb.
$v VAS '10
4•4.,*..n
03 •.., A `Z
Ift J3
OIST
ANAL
0
.1
10l
11T1
DRAWING ISSUE
BID SET: JULY 12,2010
DRAWING TITLE
MECHANICAL
FLOOR PLAN
SCALE: 1/4" =11-0"
PLOT DATE: JULY 12 2010
CAD FILE: M-1.DWG
PROJ. MGR.: RL
DRAFTER: ELA
SHEET NO
M-1