MECHANICAL PERMIT
Parcel No.: 7888920020
Address: 17100 SOUTHCENTER PY TUKW
Project Name: SEE'S CANDIES
Permit Number: M10 -153
Issue Date: 11/29/2010
Permit Expires On: 05/28/2011
Owner:
Name: WIG PROPERTIES LLC -SS
Address: 4811 134TH PL SE , BELLEVIJE WA 98006
Contact Person:
Name: TIM KIRCHER
Address: 400 ALLAN ST , DALY CITY CA 94014
Email: TKIRCHER @SEES.COM
Contractor:
Name: BOGART CONSTRUCTION INC
Address: 12 MAUCHLY BLDG F , IRVINE CA 92618
Contractor License No: BOGARCI934CO
Phone: 650 245 -3193
Phone: 949 453 -1400
Expiration Date: 02/21/2011
DESCRIPTION OF WORK:
REDUCT EXISTING HVAC UNIT
Value of Mechanical: $8,000.00
Type of Fire Protection: SPRINKLERS /AFA
Permit Center Authorized Signature:
I hereby certify that I have read and
governing this work will be complie
Fees Collected: $281.56
International Mechanical Code Edition: 2009
Date:
xa ned this permit and know the same to be true and correct. All provisions of law and ordinances
with whether specified herein or not.
The granting of this permit does not pre e to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign and obtain this mechanical permit and agree to the conditions on the
back of this permit.
Signature: .2 Date: /7/2 f1'/ 0
Print Name: Z' 41 ,'4-1 a
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: IMC -4/10
M10-153 Printed: 11 -29 -2010
• •
PERMIT CONDITIONS
Permit No. M10-153
1: ** *BUILDING DEPARTMENT CONDITIONS * **
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
4: Readily accessible access to roof mounted equipment is required.
5: Insulating materials, where exposed as installed in buildings of any type of construction, shall have a flame spread
index of not more than 25 and a smoke development index of not more than 450. Where facings are installed in concealed
spaces in buildings of Type III, IV, or V construction, the flame spread and smoke - developed limitations do not apply
to facings, that are installed behind and in substantial contact with the unexposed surface of the ceiling, wall or
floor finish.
6: All construction shall be done m conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
7: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
doc: IMC -4/10
M10-153 Printed: 11 -29 -2010
CITY OF TUIEWLA
Community DevOnrpment Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.ci.tukwila.wa.us
Building Per To.
Mechanical Permit No.
Plumbing/Gas Permit No.
Public Works Permit No.
Project No.
1AQ 4-15
V:1 V 1
RHO— L4
(For office use only)
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
SITE LOCATION
King Co Assessor's Tax No.: '1t G <b6\ 2—C 0024)
Site Address: 1) 1 O 3s) • Cc -.' n r.: -V L Suite Number: loci' o
New Tenant: 151 Yes
Tenant Name: c -
Property Owners Name: \,, / 1 \ )',- 0(5,-
Mailing Address: ..5 e s
Floor:
1
❑ ..No
Qdc_1 0 ZjC_a1 Fr '111`7
City State
Zip
CONTACT PERSON — who do we contact when your permit is ready to be issued
Name:
1 "ikv,J(1V.Q1_�y
Mailing Address: "Li 00 ,.■ 3. I
E -Mail Address:
Day Telephone: Co—S-0 43
l
6v..-,/ L= State C)-1/L1
z
Fax Number: 4))5'
GENERAL CONTRACTOR INFORMATION —
(Contractor Information for Mechanical (pg 4) for Plumbing and Gas Piping (pg 5))
Company Name: 1-9
Mailing Address:
City
Day Telephone:
Fax Number:
Expiration Date:
Contact Person:
E -Mail Address:
Contractor Registration Number:
State
Zip
ARCHITECT OF RECORD — All plans must be stamped by Architect of Record
Company Name: PA ;p
Mailing Address: �' ►r^ �c�L� 1 G� % )-4_91__m c- r‘ kitT. 5 1'J 6
City state
i Zip
Contact Person: 1�' 5 01.6 QM Day Telephone: (,.tUc "] -- .7 C, 0
E -Mail Address: 0 1601,-. Q , YM ce.:(S 'c fax Number: L 1 '5.5— 41 .5-- 0
ENGINEER OF RECORD — All plans must be stamped by Engineer of Record
Company Name: 2y mow- �Ci c4 r
Mailing Address: O Dn fJ ? x f L, �j I S.I lob
Contact Person: J, ;r1 S 0--,f; c. r rr),
E -Mail Address:
H:1Applications \Forms - Applications On t.ine\2010 Applications \7 -2010 - Permit Applicalion.doe
Revised: 7 -2010
bh
Ylf:rnk <T6 i5. City State Zip
Day Telephone: / r . 214.5- 7.5-90
Fax Number: 6.- Lf 66— 7 I
Page 1 of 6
BUILDING PERMIT INFORMATION — 206 -431 -3670
Valuation of Project (contractor's bid pr ): $ ✓f J 0 )(.')C7") , C)'D
Existing Bn Ii ding Valuation: $
Scope of Work (please provide detailed information): G�w, ���� fir' ' I. i i h s;` u — t....i nit
V (,) ��,a. �1— i,� \ C- i' 1 v",') $ I 0 0 0 r �� ,,J P? rl S 1 C� l�
y', \y a ✓
Will there be new rack storage? ❑ Yes. No If yes, a separate permit and plan submittal will be required.
Provide All Building Areas in Square Footage Below
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
'Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes ❑.......No If `yes ", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
Sprinklers Automatic Fire Alarm
❑ None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes ❑ No
If "yes', attach list of materials and storage locations on a separate 8 -1/2 "x 11 " paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
❑ .......0n-site Septic System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
H:1Apphcauom\Fortm- Appliceuom On Irne\2010 Appbcauons\7 -2010 - Permit Applicotion.doe
Revised: 1.2010
bh
Page 2 of 6
■
Existing
Interior Remodel
Addition to
Existing
Structure
New
Type of
Construction per
IBC
Type of
Occupancy per
IBC
1s` Floor
L
rd Floor
NI
3'" Floor
Floors thru
J4
Basement
Accessory Structure*
Attached Garage
Vr_pti
Detached Garage
d\/ .Q,
Attached Carport
Detached Carport
Covered Deck
N A
N
Uncovered Deck
�
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
'Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes ❑.......No If `yes ", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
Sprinklers Automatic Fire Alarm
❑ None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes ❑ No
If "yes', attach list of materials and storage locations on a separate 8 -1/2 "x 11 " paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
❑ .......0n-site Septic System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
H:1Apphcauom\Fortm- Appliceuom On Irne\2010 Appbcauons\7 -2010 - Permit Applicotion.doe
Revised: 1.2010
bh
Page 2 of 6
■
PUBLIC WORKS PERMIT INF,IATION — 206 - 433 -0179
Scope of Work (please provide detailed information): 60 t gr -'zS, c -1C -<w 10 'is-
Call before you Dig: 1- 800 -424 -5555
Please refer to Public Works Bulletin #1 for fees and estimate sheet.
Water District
Tukwila ❑ ...Water District #125
❑ ...Water Availability Provided
Sewer District
'...Tukwila
❑ ...Sewer Use Certificate
❑ .. Highline
❑ ...Valley View ❑ .. Renton
❑ ... Sewer Availability Provided
❑ .. Renton
❑ .. Seattle
Septic System:
❑ On -site Septic System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health Department.
Submitted with Application (mark boxes which apply):
❑ ...Civil Plans (Maximum Paper Size — 22" x 34 ")
❑ ...Technical Information Report (Storm Drainage) ❑ .. Geotechnical Report ❑ ...Traffic Impact Analysis
❑ ...Bond ❑ .. Insurance ❑ .. Easement(s) ❑ .. Maintenance Agreement(s) ❑ ...Hold Harmless — (SAO)
❑ ... Hold Harmless — (ROW)
Proposed Activities (mark boxes that apply):
❑ ...Right -of -way Use - Nonprofit for less than 72 hours ❑ .. Right -of -way Use - Profit for less than 72 hours
❑ ...Right -of -way Use - No Disturbance ❑ .. Right -of -way Use — Potential Disturbance
❑ ...Construction/Excavation/Fill - Right -of -way ❑
Non Right -of -way ❑
❑ ...Total Cut
❑ ...Total Fill
cubic yards
cubic yards
❑ .. Work in Flood Zone
❑ .. Storm Drainage
❑ ...Sanitary Side Sewer ❑ .. Abandon Septic Tank ❑ .. Grease Interceptor
❑ ...Cap or Remove Utilities ❑ .. Curb Cut ❑ .. Channefization
❑ ...Frontage Improvements ❑ .. Pavement Cut ❑ .. Trench Excavation
❑ ...Traffic Control ❑ .. Looped Fire Line ❑ .. Utility Undergrounding
❑ ...Backflow Prevention - Fire Protection "
Irrigation "
Domestic Water "
❑ ...Permanent Water Meter Size... 77 WO #
❑ ...Temporary Water Meter Size.. " WO #
❑ ...Water Only Meter Size >7 WO # ❑...Deduct Water Meter Size
❑ ...Sewer Main Extension Public ❑ Private ❑
❑ ...Water Main Extension Public ❑ Private ❑
FINANCE INFORMATION
Fire Line Size at Property Line Number of Public Fire Hydrant(s)
❑ ...Water ❑ ...Sewer ❑ ...Sewage Treatment
Monthly Service Billing to:
Name: Day Telephone:
Mailing Address:
Water Meter Refund/Billing:
Name:
Mailing Address:
City
State Zip
Day Telephone:
City
State Zip
H: Wpphcanons\ Forms - Applications On Line\2010 Applications \7 -2010 - Permit Apphennan.doc
Revised: 7 -2010
bh
Page 3 of 6
MECHANICAL PERMIT INFO ION — 206 -431 -3670
MECHANICAL CONTRACTOR INFORMATION
Company Name: -rr5 fl
Mailing Address:
Coy sate Zip
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date:
Valuation of Mechanical work (contractor's bid price): $ 4< PO c) . 00 `� J
Scope of Work (please provide detailed information): .}� ,St u Lc Win' % y�(' "� ` U t 1 j
1 , 1 60 `0) rusk \
Use: Residential: New .... ❑ Replacement .... ❑
Commercial: New .... ❑ Replacement ..
Fuel Type: Electric ❑ Gas..\ Other:
Indicate type of mechanical work being installed and the quantity below:
Unit Type:
Qty
Unit Type:
Qty
Unit Type:
Qty
Boiler /Compressor:
Qty
Fumace<100K BTU
Air Handling Unit >10,000
CFM
Fire Damper
0-3 HP /100,000 BTU
Furnace>100K BTU
Evaporator Cooler
Diffuser
3 -15 HP /500,000 BTU
Floor Furnace
Ventilation Fan Connected
to Single Duct
Thermostat
15 -30 HP /1,000,000 BTU
Suspended/Wall/Floor
Mounted Heater
Ventilation System
Wood/Gas Stove
30 -50 HP /1,750,000 BTU
Appliance Vent
Hood and Duct
Emergency
Generator
50+ HP /1,750,000 BTU
Repair or Addition to
Heat/Refrig/Cooling ___"X
System
Incinerator - Domestic
Other Mechanical
Equipment
Air Handling Unit
<10,000 CFM
Incinerator — Comm/1nd
H: VApplications\Fotms- Applications On Line12010 Applicationsl7 -2010 - Pemut Application.doc
Revised: 7 -2010
bh
Page 4 of 6
PLUMBING AND GAS PIPING PE T INFORMATION — 206 -431 -3670
1
PLUMBING AND GAS PIPING CONTRACTOR INFORMATION
Company Namen.
Mailing Address:
city State Zip
Contact Person: Day Telephone:
E -Mail Address: Fax Number:
Contractor Registration Number: Expiration Date:
Valuation of Plumbing work (contractor's bid price): $ / 0 I'o c'J
pb
Valuation of Gas Piping work (contractor's bid price): $
Scope of Work (please provide detailed information): ! ref Lam,._ ;c■- •\.I.,rO rlx, 'JR. /icy7yyl c.n
c.�a:ti \ \ nc_ Siv.Gr2 'r)
_ � �
! ,•/ �v�
Building Use (per Int'1 Building Code): V P)
Occupancy (per Int'l Building Code): Y»
Utility Purveyor: Water:; IC it- is 1 �.
Sewer: j i; -
Indicate type of plumbing fixtures and/or gas piping outlets being installed and the quantity below:
p Fixture Type:
Qty
Fixture Type:
Qty
Fixture Type:
Qty
Fixture Type:
Qty
Bathtub or combination
bath/shower
Bidet
Clothes washer, domestic
Dental unit, cuspidor
Dishwasher, domestic,
with independent drain
Drinking fountain or
water cooler (per head)
Food -waste grinder,
commercial
Floor Drain
Shower, single head trap
Lavatory
Wash fountain
Receptor, indirect waste
Sinks
,---
J
Urinals
Water Closet
Building sewer and each
trailer park sewer
Rain water system — per
drain (inside building)
Water heater and/or vent
`
/
Industrial waste treatment
interceptor, including trap
and vent, except for kitchen
type grease interceptors
Each grease trap
(connected to not more
than 4 fixtures - <750
gallon capacity)
Grease interceptor for
commercial kitchen ( >750
gallon capacity)
Repair or alteration of
water piping and/or water
treatment equipment
i
Repair or alteration of
drainage or vent piping
Medical gas piping
system serving 1 -5
inlets/outlets for a
specific gas
Each additional medical
gas inlets/outlets greater
than 5
Backflow protective
device other than
atmospheric -type vacuum
breakers 2 inch (51 mm)
diameter or smaller
Backflow protective device
other than atmospheric -type
vacuum breakers over 2
inch (51 mm) diameter
Each lawn sprinkler
system on any one meter
including backflow
protection devices
Atmospheric -type vacuum
breakers not included in
lawn sprinkler backflow
protections (1-5)
Atmospheric -type
vacuum breakers not
included in lawn
sprinkler baclrilow
protections over 5
Gas piping outlets
H:\Applicatians\Fotsns- Applications On Lm62010 Applications \7 -2010 -Permit Application -doc
Revised 7 -2010
bh
Page 5 of 6
PERMIT APPLICATION NOTES - plicable to all permits in this application
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
Building and Mechanical Permit
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
Plumbing Permit
The Building Official may grant one extension of time for an additional period not exceeding 180 days. The extension shall be requested
in writing and justifiable cause demonstrated. Section 103.4.3 Uniform Plumbing Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF 1 STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNE R A 0 5 II! / - ENT:
Signature: �- Date: / �� I `! 1 0
Day Telephone: I-(/ S 4 0 S -i 9 C
Print Name: 1 i vin \ � sr 1. 7-
Mailing Address: )11 ?O A \ v . '5 j
1 Date Application Accepted: tv n /�
117)c—L'O CCiN{} Ct`
H:\Applicatiom\Forms- Applications On Lme\2010 Applications \7 -2010 - Permit Applicalioa.doc
Revised: 7 -2010
bh
Stair Zip
Staff Initials: (,_ 1
Page 6 of 6
Ciff of Tukwila,
•
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206-431-3665
Web site: http: //www. ci. tukwila. wa. us
SET RECEIPT
RECEIPT NO: R10 -02378
Initials: JEM
Payment Date: 11/29/2010
User ID: 1165 Total Payment: 2,164.48
Payee: BOGART CONSTRUCTION INC.
SET ID: 1129 SET NAME: SEE'S CANDIES
SET TRANSACTIONS:
Set Member Amount
D10 -283
EL10 -0861
M10 -153
PG10 -148
TOTAL:
1,445.93
350.50
225.25
142.80
1,445.93
TRANSACTION LIST:
Type Method Description Amount
Payment Check 5308 2,164.48
TOTAL: 2,164.48
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
BUILDING - NONRES
ELECTRICAL PERMIT - NONR
MECHANICAL - NONRES
PLUMBING - NONRES
STATE BUILDING SURCHARGE
000.322.100
000.322.101.00.0
000.322.102.00.0
000.322.103.00.0
640.237.114
TOTAL:
1,441.43
350.50
225.25
142.80
4.50
2,164.48
Cit, of Tukwila,
•
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: hup://www.ci.tukwila.wa. us
SET RECEIPT
RECEIPT NO: R10 -02156
Initials: JEM
Payment Date: 10/25/2010
User ID: 1165 Total Payment: 1,080.04
Payee: SEE'S CANDIES, INC.
SET ID: S000001437 SET NAME: Tmp set/Initialized Activities
SET TRANSACTIONS:
Set Member Amount
D10 -283 988.03
M10 -153 56.31
PG10 -148 35.70
TOTAL: 988.03
TRANSACTION LIST:
Type Method Description Amount
Payment Check 549984 1,080.04
TOTAL: 1,080.04
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
BUILDING - NONRES
PLAN CHECK - NONRES
000.322.100 30.97
000.345.830 1,049.07
TOTAL: 1,080.04
INSPECTION RECORD
Retain a copy with permit
INSPEeI'ION NO. PERMIT NO
CITY.OF TUKWILA BUILDING DIVISIONS !2 .
6300.Southcenter Blvd., #10.0, Tukwila. WA 98188 (206) 43.1 =3670
Permit Inspection Request Line (206) 431 -2451
/ /K 2,
Project:
ER ( ,4 -w 9
Type of Inspection: -
/^'f9 L -
Address:
/ 7 /', a S`�/ .r/ of
Date Called:
_
Special Instructions:
•
Clare-Wanted:
/.2 —z5 —16
p.m.
Requester:
Phone No:
a 6l.— 4/V — esz.
Approved per applicable codes. Corrections required prior_to approval.
CO MENTS:
Pe -m;-1-4 4
0
INS ECTION FEE RE UIRED. P Ior to next inspection; fee must be
aid at 6300 Southcenter.'Blvd.. 5, ite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
V�IO -�51�
'CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
Project:
S F 1$ 0 lito bees
Type4f Inspection: .
c t+ f .+
rick!
Address: "
t 7100 4ioNE-t6�,N I?
Y
D to Called:
Pc4
Special Instructions:
Date Wanted:
tom.- -8--)0
a m
p.m.
Requester:
Phone No:
3G0 _ Li "7 I —03
v
ElApproved per applicable codes.- • D Corrections required prior•tn approval.
COMMENTS: c) a, /\ .
CO e V-- -r0 . -, so 'ELI
rick!
s f
1
I Date:
PECTION FEE REQU ' ED: Prior tofext inspection: fee must be
at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
R
P ET CO COPYf
t
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: M10 -153 DATE: 10/25/10
PROJECT NAME: SEE'S CANDIES
SITE ADDRESS: 17100 SOUTHCENTER PY, STE 108
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter # Revision # after Permit Issued
PAR M NTS :Iq�
ui ding ivision
Works Li
I. NIA il7A419
Prevention
Structural n
Planning Division
Permit Coordinator
DETERMINATION OF COMPLETENESS: (Tues., Thurs.) DUE DATE: 10/26/10
Complete IX
Comments:
Incomplete ❑
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROUTING:
Building
Please Route tkl Structural Review Required ❑ No further Review Required n
REVIEWER'S INITIALS:
DATE:
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
Notation:
REVIEWER'S INITIALS:
DUE DATE: 11/23/10
Not Approved (attach comments) n
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents/routing slip.doc
2 -28 -02
Contractors or TradespeopP,er Friendly Page
•
General /Specialty Contractor
A business registered as a construction contractor with LE t1 to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name BOGART CONSTRUCTION INC UBI No. 602694207
Phone 9494531400 Status Active
Address 12 Mauchly Bldg F License No. B0GARC1934CO
Suite /Apt. License Type Construction Contractor
City Irvine Effective Date 2/21/2007
State CA Expiration Date 2/21/2011
Zip 92618 Suspend Date
County Out Of State Specialty 1 General
Business Type Corporation Specialty 2 Unused
Parent Company
Business Owner Information
Name
Role
Effective Date
Expiration Date
BOGART CONSTRUCTION, INC.
02/20/2007
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
1
GREAT AMERICAN INS
CO
FS8017341
01/26/2007
Until Cancelled
$12,000.00
02/21/2007
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
4
VALLEY FORGE
INS CO
4013738877
03/01/2010
03/01/2011
$1,000,000.00
03/04/2010
3
VALLEY FORGE
INS CO
4013738877
03/01/2009
03/01/2010
$1,000,000.00
02/27/2009
2
AXIS SURPLUS
INS CO
EAP73124108
03/01/2007
03/01/2009
$1,000,000.00
03/04/2008
1
LANDMARK
AMERICAN INS
CO
LHA129399
03/01/2006
03/01/2007
$1,000,000.00
02/21/2007
Summons /Complaint Information No unsatisfied complaints on file within prior 6 year period
Warrant Information No unsatisfied warrants on file within prior 6 year period
https: // fortress .wa.gov /lni/bbip /Print.aspx 11/29/2010
IF YOU HAVE ANY QUESTIONS REGARDING THE
MECHANICAL PLANS PLEASE CALL THE MECHANICAL
DESIGNER.
DESIGNER: DAN SJOSTRAND 612- 465 -7689
E —MAIL: dan.sjostrand@dunhameng.com
EXISTING ROOFTOP UNIT SCHEDULE (RTU -1)
MFGR: & MODEL EXISTING 6 TON GAS RTU WITH ECONOMIZER TO
REMAIN. (YORK MODEL DF078N1OP2AAA4A)
CFM
O.A. CFM
2,200
240
S.P
H.P
VOLTAGE
UNIT WEIGHT EXISTING TO REMAIN
0.6" (EXT)
SEE ELECTRICAL
SEE ELECTRICAL
HEATING CAPACITY (EXISTING)
TOTAL MBH 64.8 MBH OUTPUT
(81 MBH INPUT)
THE MECHANICAL CONTRACTOR SHALL PERFORM SERVICE AND REPAIR
OF THE EXISTING EQUIPMENT AND ITS ACCESSORIES AS FOLLOWS:
CLEAN ALL COILS, REPLACE THE FILTERS AND BELTS, INSPECT, REPAIR
OR REPLACE THE ECONOMIZERS, DRIVES, FAN BEARINGS, MOTORS,
CONTROL COMPONENTS, VALVES AND ANY OTHER ITEM NECESSARY FOR
A COMPLETE AND PROPER OPERATING SYSTEM. THIS CONTRACTOR
SHALL ALSO VISIT THE SITE PRIOR TO BIDDING AND VERIFY ALL
EXISTING SITE CONDITIONS.
OUTDOOR AIR CALCULATION
BASED ON 2009 INTERNATIONAL MECHANICAL CODE TABLE 403.3
(WAC 51 -52 -0403. SECTION 403 - MECHANICAL VENTILATION.
TABLE 403.3)
RETAIL AREAS: BASEMENT AND STREET 0.30 CFM /SQ. FT.
595 SQ. FT. X 0.30 = 179 CFM
RETAIL AREAS: STORAGE ROOMS 0.15 CFM /SQ. FT.
382 SQ. FT. X 0.15 = 57 CFM
OUTSIDE AIR REQUIRED =
OUTSIDE AIR PROVIDED =
236 CFM
240 CFM
ROUND BALANCING DAMPER
ROUND RIGID METAL DUCT
PED INSULATION COVERING
CONNECTION OF FLEX DUCT
SUPPORT WITH METAL STRAPPING, DO NOT KINK
INSULATED FLEXIBLE DUCT
BALANCING HANDLE LOCK
INTO POSITION AND
MARKED PERMANENTLY.
CEILING
7-1/
EXTENDED LENGTH OF ANY
FLEXIBLE DUCT SHALL NOT
EXCEED 5' —O" MAXIMUM
OR LOCAL CODE.
DIFFUSER STARTER COLLAR
N
LAY —IN DIFFUSER
NOTES;
1. PROVIDE AT FLEXIBLE DUCT CONNECTION METAL OR "PANDUIT" DRAWBAND
ON THE INTERIOR FLEXIBLE DUCT HELIX. SECURE THE INSULATION OVER
THE DRAW BAND WITH AN ADDITIONAL DRAWBAND.
2. PROVIDE BEADING ON ROUND METAL DUCT 12" OR LARGER IN DIAMETER.
3. PROVIDE MINIMUM 2" COLLARS FOR ATTACHMENT OF THE FLEX DUCT TO
ROUND DUCT, DAMPERS AND DIFFUSERS.
4. BAND RIGID ROUND DUCT INSULATION TO DUCT AND PROVIDE TAPE FOR
INSULATION OVERLAP.
DIFFUSER /DUCT DETAIL
M� NO SCALE
M 1 NO SCALE
EXHAUST FAN
TAG
MANUFACTURER
MODEL NO.
TYPE
CFM
S.P.
WATTS
VOLTAGE
ACCESSORIES
EF -1
GREENHECK
SP -B110
CEILING
100
.25
80
SEE ELEC
BACKDRAFT DAMPER
NOTE:
TOILET EXHAUST FAN SHALL BE INTERLOCKED WITH TOILET ROOM LIGHT SWITCH.
REVISIONS
No changes shall bo made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
SEPARATE PERMIT
REQUIRED FOR:
Q Mechanical
a Electrical
D Plumbing
Gas Piping
City of Tukwila
BUILDING DIVISION
DIFFUSER, GRILLE & REGISTER SCHEDULE
EQUIP.
TAG
SERVICE
TYPE
MODULAR /FACE SIZE
BACKPAN
MANUF. .
MODEL
DESCRIPTION
MOUNTING TYPE
PATTERN
NOTES
A
SUPPLY
SQUARE
24 " �� x24
18 "x18"
CORE AREA
TITUS
PAS
PERFORATED FACE
LAY -IN
4 -WAY
1, 2
B
RETURN .
SQUARE
24 "x24"
SEE PLAN
TITUS
PAR
PERFORATED FACE
LAY -IN
-
1
C
SUPPLY
SQUARE
12 "x12"
CORE 6"x6"
TITUS
PAS
PERFORATED FACE
GYP. BRD.
4 -WAY
1, 2
NOTES:
1. ALL GRILLES, REGISTERS & DIFFUSERS MUST BE PAINTED TO MATCH CEILING TILE COLOR. VERIFY EXACT COLOR WITH ARCHITECT.
2. PROVIDE WITH OPPOSED BLADE DAMPER.
VOLUME DAMPER AND SPIN -IN.
TYPICAL FOR ALL.
EXTERIOR INSULATED ROUND RIGID DUCT
(APPROPRIATELY SIZED) CAN BE
SUBSTITUTED FOR RECTANGULAR DUCT
SHOWN ON PLANS.. (TYP)
FLEX. DUCT 5' -0" MAX. LENGTH.
TYPICAL FOR ALL.
NEW TOILET EXHAUST FAN - ROUTE 6"
RIGID DUCT W/ BACKDRAFT DAMPER UP
THRU ROOF. TERMINATE IN A GOOSENECK
W/ BIRD SCREEN •- A MINIMUM OF 10' -0"
FROM ALL O.A. INTAKES. VERIFY ROUTING
AND LOCATION ON SITE - (100 CFM)
EXISTING LANDLORD PROVIDED 5 TON GAS
ROOF TOP UNIT (RTU -1) TO REMAIN.
BALANCE AS SHOWN IN SCHEDULE.
FELE COPY
Permit No. /U P
Plan review approval Is subject to errors and omissions.
Approval of construction documents does not authorize
the violation of any adopted code or ordinance. Receipt
of approved Reid Copy and conditions is acknowledged:
By
4'/ ,f
city Of fI dcwila
BUILDING DIVISION
MECHANICAL SYMBOLS
X
A -10 "0
300
N
SUPPLY DIFFUSER
RETURN GRILLE
VOLUME DAMPER
so SMOKE DETECTOR
A -10 "o
450
N
DIFFUSER TYPE /NECK SIZE
CFM REQUIRED
Q THERMOSTAT
e POINT OF CONNECTION
N
N
_.
.tan.i.�. ��.• ...�
souldhit
C -6 "0
50
A -10 "0
\ 200
B
1 O0Q .
N.L. Ij
18/18
A -10 "0
375
IF NOT ALREADY INSTALLED, FURNISH AND INSTALL
A RETURN AIR DUCT SMOKE DETECTOR IN RTU -1
PER LOCAL CODE REQUIREMENTS.
EF -1
SPACE LOAD CALCULATIONS
DESIGN TEMPS
SUMMER
85
65
70
O.A.D.B.
O.A.W.B
I.A.D.8.
DEG F
DEG F
DEG F
GAINS
SOLAR LOAD
ROOF LOAD
GLASS LOAD
WALL LOAD
LIGHTS
PEOPLE
PEOPLE (SENS)
PEOPLE (LAT)
MISCELLANEOUS
VENT.
VENTILATION (SENS)
VENTILATION (LAT)
4,044
7,101
2,940
3,360
12,387
21
5,200
4,160
885
240
3,888
1,568
SENS. LOAD
TOTAL LOAD
TOTAL CFM
WINTER
O A D B 23 DEG F
I A D B 70 DEG F
BTU H
BTUH
BTUH
BTU H
BTUH
BTUH
BTU H
BTU H
CFM
BTU H
BTU H
39,917 BTUH TOTAL
45,882 BTUH
2,200
LOSS
2,437 BTUH
9,870 BTUH
3,948 BTUH
12,182 BTUH
28,437 BTUH
FURNISH AND INSTALL A NEW THERMOSTAT FOR RTU -1.
THERMOSTAT SHALL BE A HONEYWELL COMMERCIAL VISION
PRO #TB8220U1003 OR APPROVED EQUAL. MOUNT AT
4'- 0 "A.F.F.
— REVIEWED FOR
CODE COMPLIANCE
APPROVED
NOV 0 3 2010
pL
440'
City otakwila
BUILDING DIVISION
MECHANICAL NOTES
1. ALL EQUIPMENT, INSTALLATION AND MATERIALS SHALL COMPLY WITH ALL
APPLICABLE LANDLORD CRITERIA.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING, PRIOR TO
FINAL BID, ALL EXISTING STUB -INS, TAPS, ETC. FOR PLUMBING AND
MECHANICAL SYSTEMS WITHIN TENANT SPACE.
3. BRANCH DUCT RUN OUTS TO DIFFUSERS SHALL BE SAME SIZE AS DIFFUSER
NECK UNLESS OTHERWISE SPECIFIED.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL FINAL CONNECTIONS
TO THE LANDLORD'S BASE SYSTEMS. COORDINATE ALL SYSTEMS IN THE
FIELD.
6. VERIFY LOCATION OF ANY PENETRATION OF ROOF WITH LANDLORD. ALL
ROOF PENETRATIONS, PATCHING AND FLASHING SHALL BE BY LANDLORD
APPROVED ROOFING CONTRACTOR AT TENANT CONTRACTOR'S EXPENSE.
7. ALL FIRE PROTECTION AND SPRINKLER WORK SHALL BE PERFORMED BY
LANDLORD- APPROVED FIRE PROTECTION CONTRACTOR AT THE TENANT'S
EXPENSE.
8. CONTRACTOR SHALL SUBMIT CERTIFIED AIR BALANCE REPORT INCLUDING ALL
ASSOCIATED AIR TEMPERATURES AND PRESSURES AS APPLICABLE. SEND TWO
COPIES TO OWNER FOR APPROVAL.
9. CEILING CONTRACTOR TO PROVIDE ADEQUATE ACCESS IN OPEN CEILING GRID
AT DIFFUSER /DAMPER LOCATIONS FOR PURPOSE OF AIR BALANCING.
10. ALL SUPPLY AND RETURN AIR DUCTS IN PLENUM TO BE INSULATED PER
LOCAL CODE REQUIREMENTS.
11. REMOVE ALL UNUSED HVAC EQUIPMENT, DUCTWORK, ACCESSORIES AND
PIPING. DO NOT ABANDON. VERIFY CONDITIONS IN FIELD.
DUNHAM rAI
Dunham Associates, Inc.
50 South Sixth Street I Suite 1100
Minneepctls, Minnesota 55402-1.540
PWJriE 4 12.465.7550 FAX 612.465,7551
VQQES dunharner g.car
mechanical + electrical consulting engir
MBA Architects, Inc.
3823 Creekside Lane
Holmen, WI. 54636
608- 785 -2760 FAX: 608-785 -
E -mail: officeOmba- architects.cc
DEVELOPER'S
SPACE NO.
SUITE #
CLIENT'S
STORE NUMBER
WA-
SEE'S CANDIES
SOUTHCENTER SQUi
17100 SOUTHCENTER PI(
TUKWILA, WA 9818f
SEE'S CANDIES
400 ALLAN STREET
DALY CITY, CA., 94014
PH: 415/ 405 -7965
FAX: 415/ 586 -8557
TIM KIRCHER
CLIENT CONTACT
(415) 405 -7965
Tim R. Benson
ARCHITECT'S PROJECT MANAG
608/ 785 -2760
date
c
0
.3
landlord
permits
contractor
vendor
comr
REVD
10/07/10
0
BID /
B
PERMIT
10/13/10
0
0
0
0
0
drawn by:
DS
checked by:
GS
THIS SHEET CONTAINS:
HVAC Plan
RECEIVED
CITY OF TUKWILA
OCT 252010
PERMIT CENTER
V
1
ARCHITECT'S COMMISSION NUME
10- 725.0E
3" V.T.R.
4
O
2°
I
INDIRECT WASTE LINE
FOR SKULLERY SINK
SHALL BE COPPER
WASTE & VENT PIPING RISER DIAGRAM
NOT TO SCALE
FIXTURE AND WATER CALCULATION
TAG
HOT AND COLD WATER
WASTE
CAPACITY (GAL)
No OF
FIXTURES
F.U. PER
FIXTURE
TOTAL
FIXTURE
UNITS
COMBINED
a- w
No OF
FIXTURES
F.U. PER
FIXTURE
TOTAL
FIXTURE UNITS.
30
9
1
MARK
DESCRIPTION
CW
HW
P1
WATER CLOSET
1
5
5
1 /2"
5
4"
1
4
4
P2
LAVATORY
1
2
1.5
PROVIDE W/ MR -371 FAUCET, HOSE,
HOSE BRACKET, MOP HANGER, MR -375
STRAINER, & MR -374 LOK SEAL.
HOSE ATTACHEMENT ON FAUCET SHALL
BE EQUIPPED WITH AN ANTI — SIPHON
VACUUM BREAKER.
(BY TENANT'S PLUMBING CONTRACTOR)
2
11/2"
1
1
1
1 1 /2"
1 /2"
1 /2"
FAUCET: AMERICAN STANDARD 7402.000
& #972
COLOR TO BE WHITE.
(BY TENANT'S PLUMBING CONTRACTOR)
P5
SCULLERY
SINK
RJ FABRICATORS MODEL NO.
RJ- 1818 -18D
(OWNER FURNISHED)
FLOOR MOUNT
2" COPPER INDIRECT
WASTE TO FS W/ 1"
MIN. AIR GAP)
—
3/4"
P4, P6
HAND SINK
2
2
3
WALL HUNG
4
11/2"
2
2
4
P3
MOP SINK
1
4
3
1-1/2"
4
3"
1
3
3
FS
FLOOR SINK
—
►
44
—
-
3"
1
5
5
P5
3 —COMP SINK
1
4
3
3
4
3"
1
3
3
TOTAL F.U.
►
15.5
10.519
;<
<- 20
TOTAL F.U. 19
RANGE
FT.x.43
ASSUMED 50 P.S.I.
G.P.M 13
STREET STATIC PRESSURE
LOSSES
10
LBS /100FT)
LOSSES
5.00 PSI
4.30 PSI
3.00 PSI
WATER METER
STATIC HEIGHT
PIPE LOSS (6
TOTAL
12.30 PSI
ALL WATER SUPPLY
LINES SHALL BE
COPPER
WATER PIPING RISER DIAGRAM
NOT TO SCALE
SYMBOLS/ ABBREVIATIONS
p1 KEY NOTE
UNDERGROUND SANITARY SEWER
VENT
HOT WATER
COLD WATER
BALL VALVE
GATE VALVE
ABOVE FINISHED FLOOR
SHUT OFF VALVE
POINT OF CONNECTION TO EXISTING
A.F.F.
S.O.V.
0
ELECTRIC WATER HEATER SCHEDULE
TAG
MANUFACTURER
MODEL NO.
CAPACITY (GAL)
KW
STAGES
OUTPUT
(GPH ® 100 'F RISE)
VOLTS
NOTES
WH -1
A.O. SMITH
DEN -30
30
9
1
49
SEE ELEC
(2) 4500 W HEATING ELEMENTS HEATING
SIMULTANEOUSLY.
(BY TENANT'S PLUMBING CONTRACTOR)
PLUMBING FIXTURE SCHEDULE
MARK
TYPE
MODEL ANUMBER AND
SUPPORT
W
V
CW
HW
REMARKS
P1
WATER CLOSET
PRESSURE ASSIST
AMERICAN STANDARD
CADET (WHITE)
2168.100
FLOOR MOUNT
4"
2"
1/2"
—
(BY TENANT'S PLUMBING CONTRACTOR)
P2
LAVATORY
AMERICAN STANDARD
LUCERNE (WHITE)
0355.012
WALL HUNG
1 1 /2"
1 1 /2"
1 /2"
1/i"
FAUCET: RELIANT 2385.404
(BY TENANT'S PLUMBING CONTRACTOR)
P3
MOP SINK
BASIN
FLORESTONE MSR -2424
(MOLDED STONE)
FLOOR MOUNT
3"
1 1/2"
3/4"
3/4"
PROVIDE W/ MR -371 FAUCET, HOSE,
HOSE BRACKET, MOP HANGER, MR -375
STRAINER, & MR -374 LOK SEAL.
HOSE ATTACHEMENT ON FAUCET SHALL
BE EQUIPPED WITH AN ANTI — SIPHON
VACUUM BREAKER.
(BY TENANT'S PLUMBING CONTRACTOR)
P4
MINI —HAND
SINK
AMERICAN STANDARD — CHANDLER
MODEL NO. 7182.803
COUNTER TOP
1 1/2" /2"
1 1 /2"
1 /2"
1 /2"
FAUCET: AMERICAN STANDARD 7402.000
& #972
COLOR TO BE WHITE.
(BY TENANT'S PLUMBING CONTRACTOR)
P5
SCULLERY
SINK
RJ FABRICATORS MODEL NO.
RJ- 1818 -18D
(OWNER FURNISHED)
FLOOR MOUNT
2" COPPER INDIRECT
WASTE TO FS W/ 1"
MIN. AIR GAP)
—
3/4"
3/4"
TENANT'S CONTRACTOR TO INSTALL
OWNER SUPPLIED SCULLERY SINK,
FAUCET (T &S B266) AND TRIM.
P6
HAND SINK
W/ SIDE
SPLASH
GUARDS
ADVANCE
ADVANCE MODEL NO. 7 —PS -66
WALL HUNG
1 1/2"
1 1/2"
1/2"
1/2"
(BY TENANT'S PLUMBING CONTRACTOR)
FS
FLOOR SINK
(SQUARE)
COMMERCIAL ENAMELING
MODEL NO. 908 -3
_
3"
1-1/2"
—
—
12 "x12 " TOP, 8" DEEP BODY, ALUMINUM
DOME STRAINER, AND E -934 3/4 TOP
GRATE (FLUSH WITH SLAB /FLOOR).
(BY TENANT'S PLUMBING CONTRACTOR)
WCO
WALL CLEAN OUT
ZURN MODEL #ZB -1443
—
—
—
—
—
W/ SQUARE POLISHED BRONZE ACCESS
COVER AND FRAME.
(BY TENANT'S PLUMBING CONTRACTOR)
NOTE: EXCEPT FOR THE 3 —COMP SINK (P5), ALL PLUMBING FIXTURES AND ACCESORIES ARE TO BE SUPPLIED & INSTALLED BY CONTRACTOR.
II
VACUUM BREAKER
GATE /BALL VALVE
(TYP.)
CW
3/4'-
PLUMBING PLAN
M2
SCALE: 1/4" = 1' -0"
HW
3/4"
THERMAL EXPANSION TANK: AMTROL;
MODEL AST -5, OR EQUAL. TANK TO
BE DIAPHRAGM TYPE, .
PRE — PRESSURIZED TO 40 PSIG AND
RELIEF VALVE SET AT 150 PSIG.
TANK SHALL BE ASME CERTIFIED.
INSTALL PER MANUFACTURER'S
RECOMMENDATIONS & LOCAL CODE
REQUIREMENTS.
1" RUN FULL SIZE TO
SERVICE SINK PER LOCAL
CODE REQUIREMENTS
DRAIN VALVE
REFER TO ARCHITECTURAL
DRAWINGS FOR WATER HEATER
PLATFORM FRAMING DETAIL
6"
III
WATER HEATER DETAIL
INSULATE ALL PIPING
IN ACCORDANCE WITH
SPECIFICATIONS.
UNION (TYP.)
1" T & P RELIEF
VALVE
WATER HEATER
2" WIDE, 20 GA. SHEET
METAL BAND, SECURE
TO WALL FOR SEISMIC
BRACING WHERE
REQUIRED BY CODE.
GALV. DRIP PAN
1" DRAINS RUN IN
WALL & PUNCHED
OUT 1" ABOVE MOP
SINK W/ AIR GAP
NO SCALE
— REVIEWED FOR
CODE COMPLIANCE
APPROVED
NUv o 3 2010
City of Tukwila
BUILDING nivISICN
KEY NOTES
• CONNECT 4" SANITARY WASTE LINE TO EXISTING 4" SANITARY WASTE SERVICE. VERIFY TIE —IN
LOCATION IN FIELD.
EXTEND AND CONNECT NEW 2" VENT AND TERMINATE AT ROOF WITH 3" V.T.R.. TERMINATE A
MIN. OF 10' -0" FROM ANY FRESH AIR INTAKES. VERIFY LOCATION IN FIELD.
EXTEND AND CONNECT NEW 3 /4 "CW LINE TO EXISTING MIN. 3/4" DOMESTIC COLD WATER
SERVICE FOR TENANT'S SPACE. FIELD VERIFY EXISTING CONDITIONS.
• ELECTRIC WATER HEATER TO BE INSTALLED ABOVE MOP SINK ON THE PLATFORM. SEE
ARCHITECTURAL DRAWINGS FOR PLATFORM INFORMATION.
• VERIFY WATER METER REQUIREMENTS WITH LANDLORD AND LOCAL WATER UTILITY CO.
REQUIREMENTS.
• ROUTE 3/4" CW DN IN WING WALL AND INSTALL MAIN SHUT —OFF VALVE AT 60" A.F.F..
AFTER SHUT —OFF VALVE, ROUTE 3/4" COLD WATER UP INTO CEILING PLENUM SPACE.
REFER TO ARCHITECTURAL DETAIL 1/A5 AND WATER PIPING RISER DIAGRAM. COORDINATE
ROUTING IN FIELD.
GENERAL NOTES:
1. WELDING OR DRILLING OF STRUCTURAL MEMBERS IS NOT ALLOWED.
2. ABANDONED FLOOR DRAINS TO BE REMOVED PER STATE AND LOCAL CODES.
3. DO NOT RUN PIPING THRU, OVER OR UNDER ELECTRICAL EQUIPMENT AREA. PROVIDE
CLEARANCE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE.
4. ALL PIPING SHALL BE CONCEALED. SURFACE MOUNTED PIPING IS NOT ALLOWED.
5. PLUMBING CONTRACTOR SHALL COORDINATE WITH ARCHITECTURAL FOR EXACT FIXTURE
LOCATION PRIOR TO ANY SAW CUTTING OR PLUMBING INSTALLATION.
6. THE TRENCH SHALL BE COMPACTED PRIOR TO POURING BACK AND THE SLAB SHALL BE
PINNED AFTER ALL UNDERGROUND PLUMBING IS COMPLETED.
7. ALL IN —FLOOR MOUNTED FIXTURES ARE TO BE MOUNTED FLUSH WITH FLOOR.
8. PLUMBING WORK SHALL CONSIST OF FURNISHING AND INSTALLING ALL LABOR, MATERIALS
AND EQUIPMENT TO COMPLETE ALL PLUMBING WORK SHOWN ON THE DRAWINGS AND /OR
SPECIFIED.
9. INSTALL CLEAN —OUTS AT ALL BENDS, ANGLES AND ENDS OF ALL WASTE LINES AND ABOVE
ALL CONNECTIONS IN WALLS OF SINK WASTE LINES.
10. ALL TRAPS, HOT WATER PIPES AND DRAIN PIPES SHALL BE INSULATED OR COVERED, BELOW
LAVATORIES, AS PER CODE.
11. ALL WATER LINES SHALL BE COPPER.
12. PROVIDE CONTROL VALVES, ALL OF THE MIXING VARIETY, AS MANUFACTURED BY "AMERICAN
STANDARD" OR APPROVED EQUAL.
13. PROVIDE SHUT —OFF VALVE INCOMING COLD WATER LINE AT PLUS 60" IN WING WALL
ADJACENT TO 3 COMPARTMENT SINK WITH APPROVED ACCESS PANEL.
14. REMOVE ALL UNUSED PLUMBING FIXTURES, ACCESSORIES AND PIPING. DO NOT ABANDON.
DUNHAM El
Dunham Associates, Inc.
50 South Sixth Street /Suite 1100
Minneapolis, Minnesota 55402 -1540
PHONE 612.465.7550 F ,x: 612,465.7551
wte dunhameng.cornr
mechanical + electrical consulting engineering
MBA Architects, Inc.
3823 Creekside Lane
Holmen, WI. 54636
608 - 785 -2760 FAX: 608 - 785 -2750
E —mail: office @mba— architects.com
DEVELOPER'S
SPACE NO.
SUITE #108
CLIENT'S
STORE NUMBER
WA -11
SEE'S CANDIES
SOUTHCENTER SQUARE
17100 SOUTHCENTER PKY.
TUKWILA, WA 98188
SEE'S CANDIES
400 ALLAN STREET
DALY CITY, CA., 94014
PH: 415/ 405 -7965
FAX: 415/ 586 -8557
TIM KIRCHER
CLIENT CONTACT
(415) 405 -7965
Tim R. Benson
ARCHITECT'S PROJECT MANAGER
608/ 785 -2760
date
c
m
13
landlord
permits
contractor
vendor
comments
REVIEW
10/07/10
O
BID /
PERMIT
10/13/10
00000
drawn by:
DS
checked by:
GS
THIS SHEET CONTAINS:
FLOOR PLAN
PLUMBING WORK
RECEIVED
CITY OF TI.IKIIVILA
OCT 2 52010
PERMIT CENTER
M2
ARCHITECT'S COMMISSION NUMBER
10- 725.069
MECHANICAL
WORK INCLUDED: EACH CONTRACTOR SHALL VERIFY LANDLORD
REQUIREMENTS. BID AND INSTALLATION SHALL BE BASED ON SUCH REQUIREMENTS. DRAWINGS
AND SPECIFICATIONS.
MECHANICAL CONTRACTOR SHALL COORDINATE ALL MECHANICAL WORK WITH THAT OF OTHER
TRADES ON THE PROJECT PREVENTING UNNECESSARY CONFLICTS OR DELAYS DURING
CONSTRUCTION.
IF FOR ANY REASON EXISTING EQUIPMENT TO BE RE —USED NEEDS REPLACEMENT PARTS, THIS
COST IS TO BE COVERED UNDER ORIGINAL CONTRACT AMOUNT AND WILL NOT BE ACCEPTED AS
AN EXTRA COST OR EXPENSE.
CONTRACTOR MUST INSPECT ALL EQUIPMENT TO BE RE —USED AT TIME OF BIDDING OR
NEGOTIATING PERIOD.
CONTRACTOR SHALL EXAMINE THE SITE, COMPARE IT WITH DRAWINGS AND SPECIFICATIONS
AND BECOME FAMILIAR WITH EXISTING CONDITIONS BEFORE SUBMITTING A BID. NO
ALLOWANCE WILL SUBSEQUENTLY BE MADE IN BEHALF OF THIS CONTRACTOR BY REASON OF
ANY ERROR ON HIS PART.
CODES AND STANDARDS: ALL CODES, ORDINANCES, RULES, REGULATIONS, ORDERS, AND
OTHER LEGAL REQUIREMENTS WITH WHICH COMPLIANCE IS REQUIRED BY GOVERNING
AUTHORITIES SHALL BE ADHERED TO.
TENANTS CONTRACTORS SHALL VERIFY WITH HVAC PLAN TO COORDINATE THE REQUIREMENT
OF PLENUM RATED FIXTURES, PIPING, WIRING, ETC. FAILURE TO DO SO COULD RESULT IN
THE REMOVAL AND REPLACEMENT OF THESE ITEMS AT NO ADDITIONAL COST TO THE
TENANT.
SCOPE
A. THE WORK COVERED BY THIS. SPECIFICATION INCLUDES THE COMPLETE HEATING AND AIR
CONDITIONING SYSTEM.
B. THE WORK TO BE PERFORMED UNDER THE HEATING AND AIR CONDITIONING
SPECIFICATIONS AND DRAWINGS CONSISTS OF FURNISHING ALL LABOR AND MATERIAL FOR
THE COMPLETE INSTALLATION OF ALL HEATING AND AIR CONDITIONING SYSTEM FOR
TENANT SPACE.
THE WORK SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO, THE FOLLOWING:
1. HEATING /COOLING UNITS
2. TOILET ROOM EXHAUST SYSTEMS
3. AUTOMATIC TEMPERATURE CONTROL
4. DUCTWORK AND AIR CONTROL
5. USE OF CRANE TO PLACE ROOF TOP EQUIPMENT (WHEN REQUIRED)
GENERAL:
A. THIS SPECIFICATION IS INCLUSIVE FOR EACH ITEM REQUIRING ALL LABOR, MATERIAL,
AND EQUIPMENT NECESSARY TO PROPERLY INSTALL, ALTER, ADJUST, AND PUT IN
OPERATION, THE COMPLETE HEATING AND AIR CONDITIONING SYSTEM.
B. THE CONTRACTOR IS RESPONSIBLE FOR THE PROPER LAYOUT AND CONSTRUCTION OF THE
• WORK INCLUDED IN THIS CONTRACT.
LAWS, ORDINANCES AND REGULATIONS:
A. ALL SYSTEMS IN ALL AND /OR PART SHALL CONFORM TO ALL PERTINENT LAWS,
ORDINANCES AND REGULATIONS OF ALL BODIES HAVING JURISDICTION, AT ALL
GOVERNING LEVELS, NOTWITHSTANDING ANYTHING IN THESE DRAWINGS OR
SPECIFICATIONS TO THE CONTRARY. IN CASE OF CONFLICT BETWEEN GOVERNING LEVELS,
THE MORE STRINGENT LAWS SHALL APPLY.
B. THE CONTRACTOR SHALL PAY ALL FEES AND OBTAIN AND PAY FOR ALL PERMITS AND
INSPECTIONS REQUIRED BY ANY AUTHORITY HAVING JURISDICTION IN CONNECTION WITH
HIS WORK.
MATERIALS AND EQUIPMENT:
A. ALL MATERIALS SHALL BE NEW AND SHALL BE OF THE TYPE AND SHALL MEET THE
CAPACITIES OF EQUIPMENT SPECIFIED ON THE DRAWINGS. ALL MATERIALS AND
EQUIPMENT UTILIZED SHALL BE MANUFACTURED IN THE UNITED STATES OF AMERICA.
B. ALL EQUIPMENT OFFERED UNDER THESE SPECIFICATIONS SHALL BE LIMITED TO PRODUCTS
REGULARLY PRODUCED AND RECOMMENDED FOR SERVICE, IN ACCORDANCE WITH
ENGINEERING DATA, RATINGS, OR OTHER COMPREHENSIVE LITERATURE MADE AVAILABLE
TO THE PUBLIC AND IN EFFECT AT THE TIME OF OPENING OF BIDS.
C. EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS FOR TYPE AND CAPACITY OF EACH PIECE OF EQUIPMENT USED.
WORKMANSHIP:
A. ALL HEATING EQUIPMENT SHALL BE INSTALLED IN A WORKMANLIKE MANNER MEETING THE
ACCEPTED STANDARDS OF THE HEATING INDUSTRY. THE WORK SHALL BE DONE BY SKILLED
HEATING CRAFTSMAN, AND SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST EDITION
OF ASHRAE AND /OR THE SMACNA MANUAL.
CUTTING, PATCHING AND PAINTING:
UNLESS OTHERWISE DIRECTED BY THE LANDLORD CRITERIA, THE CONTRACTOR SHALL PERFORM
ALL CUTTING AND PATCHING REQUIRED IN CONNECTION WITH HIS WORK. ALL FINISHED
SURFACES THAT ARE CUT SHALL BE REPLACED IN KIND SO THAT THERE ARE NO VISIBLE
EVIDENCE OF "PATCH ".
PAINTING OF MECHANICAL WORK SHALL BE BY PRIME CONTRACTOR. ALL EQUIPMENT WHICH
HAS HAD THE FINISH DAMAGED BY INSTALLATION OR TRANSPORTATION SHALL BE
REFINISHED.
ROOF AND OTHER PENETRATIONS:
EACH CONTRACTOR REQUIRING OPENINGS IN THE ROOF OF THE BUILDING STRUCTURE (WHERE
REQUIRED) SHALL MAKE ARRANGEMENTS WITH THE LANDLORD FOR SUCH OPENINGS. PROCEDURE
AND COST ARRANGEMENTS SHALL BE OUTLINED IN THE LANDLORD CRITERIA. COMPLY WITH
ALL LANDLORD REQUIREMENTS. ALL ROOF PENETRATIONS SHALL BE ARRANGED TO PROVIDE A
WEATHER —TIGHT INSTALLATION. THE INSTALLATION SHALL INCLUDE, WHERE REQUIRED,
VENTILATING COLLARS TO GIVE PROPER CLEARANCE FROM COMBUSTIBLE ROOFS, FLOORS,
CEILINGS OR OTHER SUCH STRUCTURES. FIRE — PROOFING SHALL BE PROVIDED USING
MATERIALS CONFORMING WITH MUNICIPAL CODES AND ORDINANCES.
DUCTWORK:
A. ALL DUCTWORK SHALL BE INSTALLED AS SHOWN ON MECHANICAL DRAWINGS.
B. THE DUCTWORK SHALL BE CLEAR INSIDE OF THE SIZES SHOWN ON THE DRAWINGS.
ALL DUCTS TO BE SHEET METAL DUCTS AS PER ASHRAE AND SMACNA GUIDLINES.
C. FLEXIBLE DUCTS SHALL BE LIMITED TO 5' -0" MAX. FOR CONNECTION TO AIR DEVICES.
D. DUCTWORK SHALL BE "FACTORY MADE" CLASS 1 GALVANIZED SHEET METAL WITH IRON
SUPPORTS SECURED TO OVERHEAD MEMBERS AT 5' -0" ON CENTER. DUCTWORK
MATERIALS SHALL BE PER CURRENT MECHANICAL CODE.
DUCTWORK INSULATION:
SUPPLY FROM THE AIR CONDITIONING UNIT SHALL BE WRAPPED WITH 1-1/2" THICK 1 LB /CUFT
FIBERGLASS, FOIL BACKED INSULATION TO PREVENT CONDENSATION.
GRILLES AND DIFFUSERS:
GRILLES AND DIFFUSERS SHALL BE AS MANUFACTURED BY KREUGER, HART AND COOLEY,
BARBERCOLMAN, OR TITUS. EACH IS TO BE FITTED WITH A VOLUME DAMPER. (OPPOSED
BLADE DAMPER)
TESTING AND BALANCING CERTIFIED (AABC OR NABB)
INDEPENDENT TESTING COMPANY TO TEST AND BALANCE SYSTEM TO CFM AS SPECIFIED.
REPORT RESULTS TO TENANT AND ARCHITECT.
GUARANTEE:
A. EACH CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE IN WRITING ALL MATERIALS,
EQUIPMENT, AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE
OF OWNER. THE CONTRACTOR SHALL PROVIDE FREE SERVICE FOR ALL EQUIPMENT
INVOLVED IN HIS CONTRACT DURING THIS GUARANTEE PERIOD.
B. THE GUARANTEE SHALL INCLUDE RESTORATION OF ITS ORIGINAL CONDITION OF ALL
ADJACENT WORK THAT MUST BE DISTURBED IN FULFILLING THIS GUARANTEE.
C. ALL SUCH REPAIRS AND /OR REPLACEMENTS SHALL BE MADE WITHOUT DELAY, AND AT THE
CONVENIENCE OF THE OWNER.
SUBSTITUTIONS:
A. APPROVALS OF SUBSTITUTIONS FOR "APPROVED EQUAL ", MUST BE IN WRITING AND
SUBSTITUTION MUST BE APPROVED BEFORE INSTALLATION. INSTALLATION WITHOUT PRIOR
APPROVAL MAY RESULT IN CONTRACTOR REMOVING SUBSTITUTION AND REPLACING IT WITH
SPECIFIED ITEM AT HIS EXPENSE.
B. APPROVAL MAY BE GIVEN BY ARCHITECT, ENGINEER OR OWNER.
TEMPERATURE CONTROL:
FURNISH AND INSTALL NEW COMPATIABLE THERMOSTAT AS LISTED BELOW.
A. THERMOSTAT SHALL BE A HONEYWELL COMMERCIAL VISION PRO #TB8220U1003 OR
APPROVED EQUAL.
TEMPERATURE CONTROL SHALL BE BY A WALL MOUNTED HEATING /COOLING THERMOSTAT,
WITH SUBBASE HAVING SELECTOR SWITCHES FOR "ON /AUTO" AND "HEAT /OFF /COOL"
TEMPERATURE RANGE FROM 50 DEGREES F. TO 90 DEGREES F.
B. THIS STANDARD SYSTEM TO BE USED UNLESS SPECIAL CONTROL SYSTEM IS CALLED FOR
OR SHOWN ON DRAWINGS.
MECHANICAL UNIT:
A. EXISTING LANDLORD PROVIDED GAS ROOF TOP UNIT (RTU -1) TO REMAIN. SEE SCHEDULE
ON SHEET M1 FOR AIR BALANCE.
B. SEQUENCE OF CONTROL (ROOF TOP UNIT)
1. OCCUPIED HOURS.
A. UNIT OUTDOOR AIR DAMPER SHALL OPEN TO ITS MINIMUM
POSITION AND UNIT SUPPLY FAN SHALL OPERATE CONTINUOUSLY.
B. UNIT COMPRESSOR(S) SHALL CYCLE FOR COOLING AND THE GAS
BURNER /FURNACE SHALL CYCLE FOR HEATING TO MAINTAIN
SPACE SETPOINT.
C UNIT ECONOMIZER CYCLE SHALL BE INITIATED UPON A SIGNAL
FROM OUT DOOR AIR SENSORS. OUTDOOR AIR DAMPER, RETURN
AIR DAMPER, AND UNIT COMPRESSOR(S) SHALL CYCLE TO MAINTAIN
SPACE SETPOINT.
2. UNOCCUPIED HOURS.
A. UNIT OUTDOOR AIR DAMPER SHALL REMAIN CLOSED AND UNIT
SUPPLY FAN SHALL CYCLE ON A SIGNAL FROM SPACE SENSOR.
B. UNIT COMPRESSOR(S) SHALL CYCLE FOR COOLING AND GAS
BURNER /FURNACE SHALL CYCLE FOR HEATING WITH THE UNIT
SUPPLY FAN TO MAINTAIN SPACE SETPOINT.
FIRE PROTECTION
EXECUTION — INSTALLATION:
A. GENERAL CONTRACTOR TO VERIFY MALL SPRINKLER CONTRACTOR REQUIREMENTS AND USE
SPECIFIED CONTRACTOR IF REQUIRED.
B. INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 13. INSTALL SPRINKLER
PIPING PRODUCTS WHERE REQUIRED IN ACCORDANCE WITH RECOGNIZED PRACTICES TO
ENSURE THAT FIRE PROTECTION SPRINKLER PIPING COMPLIES WITH GOVERNING
REQUIREMENTS AND SERVES THE INTENDED PURPOSES.
C. EXAMINE OTHER WORK SHOWN ON THE DRAWINGS AND CONDITIONS AT THE JOB SITE.
COORDINATE THE ROUTING OF WORK WITH OTHER TRADES TO AVOID INTERFERENCE WITH
OTHER INSTALLATIONS.
D. PIPE ROUTING AND SPRINKLER HEAD LOCATIONS SHALL BE LOCATED AS REQUIRED TO
AVOID EQUIPMENT, PLUMBING, HEATING AND AIR CONDITIONING PIPING, DUCTWORK,
LIGHTING FIXTURES, ELECTRICAL CONDUITS AND BUS DUCTS AND SIMILAR WORK.
E. PROVIDE PIPE OFFSETS AS REQUIRED TO COMPLETE THE INSTALLATION. MODIFY PIPE,
PREFABRICATED PIPING, PIPE HANGERS AND OTHER COMPONENTS AS REQUIRED TO FIT
THE: JOB SITE CONDITIONS.
CLEANING AND FLUSHING: PRIOR TO CONNECTING SPRINKLER PIPING FOR FLUSHING,
FLUSH WATER FEED MAINS, LEAD —IN CONNECTIONS AND CONTROL PORTIONS OF SPRINKLER
PIPING. AFTER FIRE SPRINKLER PIPING INSTALLATION HAS BEEN COMPLETED AND
BEFORE PIPING IS PLACED IN SERVICE, FLUSH ENTIRE SPRINKLER SYSTEM UNDER
PRESSURE, AS REQUIRED TO REMOVE FOREIGN SUBSTANCES AS REQUIRED BY NFPA 13.
CONTINUE FLUSHING UNTIL WATER IS CLEAR AND CHECK TO ENSURE THAT DEBRIS HAS
NOT CLOGGED SPRINKLERS.
TESTING:
A. AFTER FLUSHING SYSTEM, TEST FIRE SPRINKLER PIPING HYDROSTATIC ALLY IN
ACCORDANCE WITH NFPA 13, AT NOT LESS THAN 200 PSI OR AT 50 PSIG. CHECK SYSTEM
FOR LEAKAGE AT JOINTS. MEASURE HYDROSTATIC PRESSURE AT LOW POINT OF EACH
SYSTEM OR ZONE BEING TESTED.
B. REPAIR OR REPLACE PIPING SYSTEM AS REQUIRED TO ELIMINATE LEAKAGE IN
ACCORDANCE WITH NFPA STANDARDS FOR "LITTLE OR NO LEAKAGE" AND RETEST AS
SPECIFIED TO DEMONSTRATE COMPLIANCE.
SPRINKLER MANS AND BRANCHES
A. PIPING MATERIAL: BLACK STEEL, SCHEDULE 40 OR LIGHTWEIGHT SPRINKLER PIPE,
SCHEDULE 10 ASTM A 135 (IF ALLOWED BY LANDLORD AND LOCAL AUTHORITIES).
B. FITTINGS: THREADED, CLASS 175. MECHANICAL COUPLINGS AND TEES OF A ROLLED
GROOVED TYPE WILL BE ACCEPTED (IN LIEU OF THREADED) IF BOTH U.L. LISTED AND
FIRE MARSHAL APPROVED.
INSTALLATION:
C. ALL SPRINKLER PIPING SHALL BE CONCEALED UNLESS OTHERWISE INDICATED. ALL
PIPING SHALL BE LOCATED TO AVOID INTERFERENCE WITH ALL OTHER ELEMENTS ABOVE
CEILINGS, ETC.
D. SUPPORT ALL HORIZONTAL PIPING AT NOT GREATER THAN 10 FEET INTERVALS, EXCEPT
PIPES OF SIZE 1-1/2" AND LARGER WHICH SHALL BE SUPPORTED AT NOT GREATER
THAN FIFTEEN FEET INTERVALS, WITH APPROVED SWIVEL SPLIT RING HANGERS WITH ROD
SUPPORTS AND SWAY BRACES AT EVERY THIRD HANGER.
E. ALL SPRINKLER PIPING SHALL BE INSTALLED SO THAT IS CAN BE THOROUGHLY DRAINED
AND WHERE PRACTICAL, ARRANGE TO DRAIN THE MAIN VALVE.
SPRINKLER HEADS
A. SPRINKLER HEADS IN AREAS WITH LAY —IN AND DRYWALL CEILINGS SHALL BE RECESSED
TYPE: , 165 DEGREE RATED, CHROME PLATED HEAD WITH ESCUTCHEON COLOR TO
MATCH CEILING COLOR, VERIFY EXACT COLOR WITH ARCHITECT.
B. SPRINKLER HEADS IN AREA OF NO CEILING SHALL BE CHROME PLATED UPRIGHT.
C. ALL SPRINKLER HEADS SHALL BE 1/2" ORIFICE, RATED AT 165 DEGREES WITH A
K— FACTOR OF 5.65.
D. ALL SPRINKLER HEADS THAT ARE TO REMAIN AND BE REUSED SHALL BE PROTECTED
DURING CONSTRUCTION AND CLEANED THOROUGHLY TO INSURE THAT THEY ARE CLEAR
OF PAINT AND DEBRIS AND ARE IN GOOD WORKING CONDITION, PRIOR TO PROJECT
CLOSEOUT.
E. ALL SPRINKLER HEADS SHALL BE INSTALLED IN ACCORDANCE TO NFPA 13 AND ALL
LOCAL CODES AND AUTHORITIES HAVING JURISDICTION.
PLUMBING
SCOPE:
A. THE WORK TO BE PERFORMED UNDER THE PLUMBING SPECIFICATIONS AND DRAWINGS
CONSISTS OF FURNISHING ALL LABOR AND MATERIAL FOR THE COMPLETE INSTALLATION
OF ALL PLUMBING SYSTEMS FOR TENANT SPACE. THE WORK SHALL INCLUDE, BUT NOT BE
LIMITED TO, THE FOLLOWING:
1. COLD AND HOT WATER SYSTEMS
2. DRAINAGE AND VENT SYSTEMS
3. INSULATION
GENERAL:
A. THIS SPECIFICATIONS IS INCLUSIVE FOR EACH ITEM REQUIRING ALL LABOR, MATERIAL,
AND EQUIPMENT NECESSARY TO PROPERLY INSTALL, ALTER, ADJUST, AND PUT INTO
OPERATION, THE COMPLETE PLUMBING SYSTEM .
B. THE CONTRACTOR IS RESPONSIBLE FOR THE PROPER LAYOUT AND CONSTRUCTION OF THE
WORK INCLUDED IN THIS CONTRACT.
WORKMANSHIP:
ALL WORK MUST BE DONE IN A WORKMANLIKE MANNER TO THE COMPLETE SATISFACTION OF
THE ENGINEERS AND SHALL BE PERFORMED BY QUALIFIED MECHANICS.
A. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, AND SHALL CONFORM TO THE GRADE,
QUALITY AND STANDARDS SPECIFIED HEREIN. ALL MATERIALS AND EQUIPMENT UTILIZED
SHALL BE MANUFACTURED IN THE UNITED STATES OF AMERICA.
B. ALL EQUIPMENT OFFERED UNDER THESE SPECIFICATIONS SHALL BE LIMITED TO PRODUCTS
REGULARLY PRODUCED AND RECOMMENDED FOR SERVICE, IN ACCORDANCE WITH
ENGINEERING DATA, RATINGS, OR OTHER COMPREHENSIVE LITERATURE MADE AVAILABLE
TO THE PUBLIC AND IN EFFECT AT THE TIME OF OPENING OF BIDS.
C. EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS FOR TYPE AND CAPACITY OF EACH PIECE OF EQUIPMENT USED.
LAW, ORDINANCES AND REGULATIONS:
A. ALL MECHANICAL SYSTEMS IN ALL AND /OR PART SHALL CONFORM TO ALL PERTINENT
LAWS, ORDINANCES AND REGULATIONS AND ALL BODIES HAVING JURISDICTION, AT ALL
GOVERNING LEVELS, NOTWITHSTANDING IN THESE PLANS AND SPECIFICATION TO THE
CONTRARY. IN CASE OF CONFLICT BETWEEN GOVERNING LEVELS, THE MORE STRINGENT
LAWS SHALL APPLY.
B. CONTRACTOR SHALL PAY ALL FEES AND OBTAIN AND PAY FOR ALL PERMITS AND
INSPECTIONS REQUIRED BY ANY AUTHORITY HAVING JURISDICTION IN CONNECTION WITH
HIS WORK.
C. WHERE APPLICABLE, ALL MATERIAL SHALL BEAR THE THE NATIONAL BOARD OF FIRE
UNDERWRITER'S SEAL OF APPROVAL. CERTIFICATES TO THIS EFFECT TO BE FURNISHED
TO ARCHITECT TO BE TO ARCHITECT UPON REQUEST.
ESCUTCHEONS:
A. ALL EXPOSED PIPES, EXCEPT AS OTHERWISE DESCRIBED, PASSING THRU WALLS, FLOORS,
CEILINGS, ETC. IN FINISHED SPACES, SHALL BE PROVIDED WITH SOLID PATTERN HEAVY
CEILING, FLOOR OR WALL ESCUTCHEONS WITH SET SCREW. ESCUTCHEONS AND PLATES
SHALL BE OF STEEL OR MALLEABLE IRON WITH PRIME COAT READY FOR PAINTING.
ESCUTCHEONS WILL NOT BE PROVIDED WHERE SLEEVES INTENTIONALLY EXTEND ABOVE
FINISHED FLOOR.
B. ALL EXPOSED PLUMBING SHORT BRANCH CONNECTIONS TO FIXTURES AND /OR EQUIPMENT
PASSING THROUGH WALL OR FLOORS SHALL BE EQUIPPED WITH PRESS BRASS, CHROMIUM
PLATED, SOLID TYPE ESCUTCHEONS.
GUARANTEE:
A. EACH CONTRACTOR SHALL UNCONDITIONALLY GUARANTEE IN WRITING ALL MATERIALS,
EQUIPMENT, AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE
BY OWNER. THE CONTRACTOR SHALL PROVIDE FREE SERVICE FOR ALL EQUIPMENT
INVOLVED IN HIS CONTRACT DURING THIS GUARANTEE PERIOD.
B. THE GUARANTEE SHALL INCLUDE RESTORATION TO ITS ORIGINAL CONDITION OF ALL
ADJACENT WORK THAT MUST BE DISTURBED IN FULFILLING THIS GUARANTEE.
C. ALL SUCH REPAIRS AND /OR REPLACEMENTS SHALL BE MADE WITHOUT DELAY, AND AT THE
CONVENIENCE OF THE OWNER.
TEMPORARY SERVICES:
A. THE CONTRACTOR, AT HIS OWN EXPENSE AND COST, SHALL INSTALL, OPERATE, PROTECT
AND MAINTAIN THE RESPECTIVE TEMPORARY SERVICES AS REQUIRED BY HIS WORK.
TEST OF PIPING AND SYSTEM:
A. THE SYSTEMS OF PIPING AS INSTALLED BY THIS CONTRACTOR MUST BE TESTED WITH
WATER OR AIR AND PROVEN TIGHT TO THE SATISFACTION OF REPRESENTATIVES OF THE
OWNER. TESTING INSTRUMENTS MUST BE FURNISHED BY THE PLUMBING CONTRACTOR.
B. TEST MUST BE MADE WITH WATER, EXCEPT WHEN THERE IS DANGER FROM FREEZING, THEN
TESTS MAY BE MADE WITH AIR. WOODEN PLUGS ARE NOT TO BE USED IN MAKING TESTS.
STERILIZATION OF DOMESTIC WATER SYSTEM:
A. BEFORE BEING PLACED IN SERVICE ALL WATER LINES SHALL BE CHLORINATED TO THE
SATISFACTION OF THE A.W.W.A SPECIFICATIONS C601 -53T.
SOIL WASTE AND VENT PIPING:
A. SOIL WASTE PIPING SHALL BE SERVICE WEIGHT CAST IRON PIPE, BELL Sc SPIGOT
TYPE AS REQUIRED.
B. VENT PIPE SHALL BE SERVICE WEIGHT CAST IRON BELL & SPIGOT TYPE AS REQUIRED
PER LOCAL CODE.
INSULATE —ALL LINES (ABOVE CEILING /IN WALLS INCLUDED):
A. INSULATION ON COLD WATER, HOT WATER, CONDENSATE LINES, ETC., SHALL BE
ARMAFLEX II, OR APPROVED EQUAL, WITH THICKNESS AS REQUIRED. MINIMUM THICKNESS
IS 1/2" INCH.
B. INSULATION ON ROOF DRAINS AND ROOF DRAIN LEADERS SHALL BE FIBERGLASS WITH
MULTI — PURPOSE WRAPPING.
SUBSTITUTIONS:
A. SUBSTITUTIONS WILL BE CONSIDERED FOR "OR EQUAL" BUT MUST BE APPROVED IN
WRITING, BY OWNER, ARCHITECT OR ENGINEER, PRIOR TO INSTALLATION.
B. IF, AFTER PLANS ARE COMPLETED, AUTHORITIES RULE THAT HANDICAPPED RESTROOM IS
REQUIRED, BUT NOT SHOWN, USE AMERICAN STANDARD 'CADET —HI" WATER CLOSETS AND
SET LAVATORY AT PROPER HEIGHT WITH LEVER HANDLES. (VERIFY ALL FINAL EQUIPMENT
SPECS WITH PLUMBING DRAWING).
WATER PIPING:
A. WATER PIPING UNDER FLOOR SHALL BE TYPE "K" SOFT COPPER WITH SILVER SOLDER
JOINTS.
B. WATER PIPING ABOVE FLOOR SHALL BE TYPE "L" HARD DRAWN COPPER WITH LEAD FREE
SOLDER JOINTS.
-
REVIEWED FOR
CODE COMPLIANCE
APPROVED
NOV 0 3 2010
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
OCT 2 52010
PERMIT CENTER
D U N H A► M ice►
Dunham Associates, Inc.
50 South Sixth Street /Suite 1100
Minneapolis, Minnesota 55402 -1540
PHONE 812.465.7550 FAx 612,465.7551
WEe dunhameng.c,rn
mechanical + electrical consulting engineering
MBA Architects, Inc.
3823 Creekside Lane
Holmen, WI. 54636
608 - 785 -2760 FAX: 608-785-2750
E —mail: office @mba— architects.com
DEVELOPER'S
SPACE NO. SUITE #108
CLIENT'S
STORE NUMBER
WA -11
SEE'S CANDIES
SOUTHCENTER SQUARE
17100 SOUTHCENTER PKY.
TU KWI LA, WA 98188
90
'S
3
SEE'S CANDIES
400 ` ALLAN STREET
DALY CITY, CA., 94014
PH: 415/ 405 -7965
FAX: 415/ 586 -8557.
11M KIRCHER
CLIENT CONTACT
(415) 405 -7965
Tim R. Benson
ARCHITECT'S PROJECT MANAGER
608/ 785 -2760
c
m
� .0
landlord I
A
E
a
contractor'
vendor
comments
CUE NT
PERMIT
10/13/10
0
0
0
0
0
drown by.
DS
checked by
GS
THIS SHEET CONTAINS:
SPECIFICATIONS
PLUMBING WORK
ARCHITECT'S COMMISSION NUMBER
10- 725.069