HomeMy WebLinkAboutPermit D12-130 - CHASING FIREFLIES - PALLET RACKSCHASING FIREFLIES
1121 ANDOVER PK W
EXPIRED 11 -07 -12
D12-130
City dtrukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206 - 431 -2451
Web site: http: / /www.TukwilaWA.gov
Parcel No.: 3523049102
Address: 1121 ANDOVER PK W TUKW
Suite No:
Project Name: CHASING FIREFLIES
DEVELOPMENT PERMIT
Permit Number: D12 -130
Issue Date: 05/04/2012
Permit Expires On: 10/31/2012
Owner:
Name: AMB PROPERTY CORP
Address: 60 STATE ST STE 1200 C/O RE TAX , BOSTON MA 02109
Contact Person:
Name: MIKE SORENSON
Address: 1100 SW 7 ST , RENTON WA 98057
Contractor:
Name: NORTH WEST HANDLING SYSTEMS INC
Address: 1100 S.W. 7TH STEET , RENTON, WA 98055
Contractor License No: NORTHWH275JF
Lender:
Name:
Address:
Phone: 206 - 818 -4488
Phone: 206 255 -0500
Expiration Date: 10/09/2013
DESCRIPTION OF WORK:
INSTALLATION OF NEW AND USED PALLET RACKING. PLEASE SEE ATTACHED DRAWINGS, ENGINEERING AND
SUPPLEMENT FOR BUILDING, SPRINKLER, COMMODITY AND LOCATION INFORMATION.
Value of Construction: $0.00 Fees Collected: $1,215.02
Type of Fire Protection: SPRINKLERS International Building Code Edition: 2009
Type of Construction: Occupancy per IBC: 0025
Electrical Service Provided by: PUGET SOUND ENERGY
* *continued on next page **
doc: IBC -7/10
D12 -130 Printed: 05 -04 -2012
Public Works Activities:
Channelization / Striping: N
Curb Cut / Access / Sidewalk / CSS: N
• •
Fire Loop Hydrant: N Number: 0 Size (Inches): 0
Flood Control Zone:
Hauling: N Start Time: End Time:
Land Altering: Volumes: Cut 0 c.y. Fill 0 c.y.
Landscape Irrigation:
Moving Oversize Load: Start Time: End Time:
Sanitary Side Sewer:
Sewer Main Extension: Private: Public:
Storm Drainage:
Street Use: Profit: N Non - Profit: N
Water Main Extension: Private: Public:
Water Meter: N
Permit Center Authorized Signature:
pin
Date: b
I hereby certify that I have read and e • ed this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign and obtain this development permit and agree to the conditions attached
to this permit.
Signature:
Print Name:
Date: C-741/(
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, o:c if the work is suspended
or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: ** *BUILDING DEPARTMENT CONDITIONS * **
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
4: When special inspection is required, either the owner or the registered design professional in responsible charge,
shall employ a special inspection agency and notify the Building Official of the appointment prior to the first
building inspection. The special inspector shall furnish inspection reports to the Building Official in a timely manner.
5: A final report documenting required special inspections and correction of any discrepancies noted in the inspections
shall be submitted to the Building Official. The final inspection report shall be prepared by the approved special
inspection agency and shall be submitted to the Building Official prior to and as a condition of final inspection
approval.
doc: IBC -7/10
D12 -130 Printed: 05 -04 -2012
6: All construction shall be done in confor e with the approved plans and the require m! of the International
Building Code or International Residential e, International Mechanical Code, Washington State Energy Code.
7: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
8: ** *FIRE DEPARTMENT CONDITIONS * **
9: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
10: Clearance between ignition sources, such as light fixtures, heaters and flame - producing devices, and combustible
materials shall be maintained in an approved manner. (IFC 305.1)
11: Where storage height exceeds 15 feet and ceiling sprinklers only are installed, fire protection by one of the following
methods is required for steel building columns located within racks: (a) one -hour fire proofing, (b) sidewall sprinkler
at the 15 foot elevation of the column, (c) ceiling sprinkler density minimums as determined by the Tukwila Fire
Prevention Bureau. (NFPA 13)
12: Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18
inches below sprinkler head deflectors in sprinklered areas of buildings. (IFC 315.2.1)
13: Flue spaces shall be provided in accordance with International Fire Code Table 2308.3. Required flue spaces shall be
maintained.
14: Maintain fire alarm system audible /visual notification. Addition/relocation of walls or partitions may require
relocation and /or addition of audible /visual notification devices. (City Ordinance #2051)
15: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
16: The total number of fire extinguishers required for an ordinary hazard occupancy with Class A fire hazards is
calculated at one extinguisher for each 1,500 sq. ft. of area. The extinguisher(s) should be of the "All Purpose" (2A,
20B:C) dry chemical type. Travel distance to any fire extinguisher must be 75' or less. (IFC 906.3) (NFPA 10, 3 -2.1)
17: Portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or
brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation
instructions. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so
that its top is not more than 5 feet (1524 mm) above the floor. Hand -held portable fire extinguishers having a gross
weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the
floor. The clearance between the floor and the bottom of the installed hand -held extinguishers shall not be less than 4
inches (102 mm). (IFC 906.7 and IFC 906.9)
18: Fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot
be completely avoided, means shall be provided to indicate the locations of the extinguishers. (IFC 906.6)
19: Extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available
for use. These locations shall be along normal paths of travel, unless the fire code official determines that the
hazard posed indicates the need for placement away from normal paths of travel. (IFC 906.5)
20: Fire extinguishers require monthly and yearly inspections. They must have a tag or label securely attached that
indicates the month and year that the inspection was performed and shall identify the company or person performing the
service. Every six years stored pressure extinguishers shall be emptied and subjected to the applicable recharge
procedures. If the required monthly and yearly inspections of the fire extinguisher(s) are not accomplished or the
inspection tag is not completed, a reputable fire extinguisher service company will be required to conduct these
required surveys. (NFPA 10, 4 -3, 4 -4)
21: Maintain fire extinguisher coverage throughout.
22: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2050 and
#2051)
23: Any overlooked hazardous condition and /or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
doc: IBC -7/10
D12 -130 Printed: 05 -04 -2012
24: These plans were reviewed by Inspector X11. If you have any questions, please call Tukw re Prevention Bureau at
(206)575 -4407.
doc: IBC -7/10
D12 -130 Printed: 05 -04 -2012
•
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
_AP
Building Permit No. bt)
Project No.
Date Application Accepted:
Date Application Expires:
(For office use. only)
CONSTRUCTION PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
SITE LOCATION
L King Co Assessor's Tax No.:
Site Address: ! i I 4 nd toes rL( �ZS! Suite Number: Floor:
Tenant Name: C.—k4 S i nQ rire. 4-1/ t es
PROPERTY OWNER
`.
Name: 4,4 5
City: 77 w / State: (/4 Zipp9 4-7
Address: i ._70 cridv.1442_1 Dr; 04 #e p0
1100 00 Sw 7 S%
City: 7 k,,,,, is State: 1,j,er Zip18 L6
.
CONTACT PERSON – person receiving all project
communication
Company Name:/ ,4/ Wes/ 74 //.,^ S
Name: A// �reviS —•1
City: 77 w / State: (/4 Zipp9 4-7
Phone: ��`,a. '0S- Fax:tei.S a i G 1 ih
''ii
1100 00 Sw 7 S%
Tukwila Business License No.: u S_ 6 g 9 304 7
City: •R r Ale) State: i4
Zip ues., 7
Phone: a06' cllg_ (pig? Fax: iii_sA
'‘
7 ,v6
Email: tr'1.Sorer, Son c r►k/4 S• CO o'
,
GENERAL CONTRACTOR INFORMATION
Company Name:/ ,4/ Wes/ 74 //.,^ S
Address: moo fiA/ (/
City: 77 w / State: (/4 Zipp9 4-7
Phone: ��`,a. '0S- Fax:tei.S a i G 1 ih
''ii
Contr Reg No.: Exp Date:
g Nc��,w% ��5�' lv qbo/3
Tukwila Business License No.: u S_ 6 g 9 304 7
H: \Applications \Forms - Applications On Line \201 1 Applications\Permit Application Revised - 8 -9 -1 I.docx
Revised: August 2011
bh
New Tenant: 'Yes ❑..No
ARCHITECT OF RECORD
Company Name:R P.os)f k- 6%Ag `
Engineer Name: ✓
Company Name:
City: 6.(€414;6.. State: q Zip 9 /,U
!� 7
Phone:g /g y0 gia Faxx1g 0 3Rl
Architect Name:
Address:
City:
State:
Zip:
Phone:
Fax:
Em.' .
ENGINEER OF RECORD
Company Name:R P.os)f k- 6%Ag `
Engineer Name: ✓
Address: to?. w 73_0,4,7 d y
City: 6.(€414;6.. State: q Zip 9 /,U
!� 7
Phone:g /g y0 gia Faxx1g 0 3Rl
Email:
LENDER/BOND ISSUED (required for projects
greater per RCW 19.27.095)
Name:
Address:
C. State: Zip:
Page 1 of 4
• •
BUILDING PERMIT INFORMATION — 206 - 431 -3670
Valuation of Project (contractor's bid price): $ .3 , 006 Existing Building Valuation: $
Describe the scope of work (please provide detailed information): 2-4 s.4 f(4 f jc,.i o f nc( cis_ f
Ge � cc( ((Q0 # St.Q Ge4r / �e c-. 4 c741. c•,a,, . �cr
6 44 Spy ��lLe�° (0,41,4,061 :47 /-y / L' l
Will there be new rack storage? 12(ces
E.. No If yes, a separate permit and plan submittal will be required.
Provide All Building Areas in Square Footage Below
PLANNING DIVISION:
1
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes No If "yes ", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
Pre Sprinklers ❑ Automatic Fire Alarm ❑ None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes No
If `yes', attach list of materials and storage locations on a separate 8-1/2" x 11 " paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
❑ On -site Septic System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
H:\Applications\Forms- Applications On Line \2011 Applications\Permit Application Revised - 8 -9 -1 I.docx
Revised: August 2011
bh
Page 2 of 4
Existing
Interior Remodel
Addition to
Existing
Structure
New
Type of
Construction per
IBC
Type of
Occupancy per
IBC
1a Floor
1 (2°C)
I ?-O0O
--
2 "d Floor
-
3rd Floor
Floors thru
Basement
Accessory Structure*
Attached Garage
Detached Garage
Attached Carport
Detached Carport
Covered Deck
Uncovered Deck
PLANNING DIVISION:
1
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided: Standard: Compact: Handicap:
Will there be a change in use? ❑ Yes No If "yes ", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
Pre Sprinklers ❑ Automatic Fire Alarm ❑ None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? ❑ Yes No
If `yes', attach list of materials and storage locations on a separate 8-1/2" x 11 " paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
❑ On -site Septic System — For on -site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
H:\Applications\Forms- Applications On Line \2011 Applications\Permit Application Revised - 8 -9 -1 I.docx
Revised: August 2011
bh
Page 2 of 4
PERMIT APPLICATION NOTES —
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT 1 HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR AUTJ J.7 TJ AGENT:
Signature:
Print Name:
Date: y/i 9/0)-4' ��--
Day Telephone: a06 - 8i ce " G `f ge
Mailing Address: ((be) Six/ 7 -§7
H: \ApplicationsWorms- Applications On Line \2011 Applications\Permit Application Revised - 8 -9 -I I.docx
Revised: August 2011
bh
City
%Sit)-S?'
State Zip
Page 4 of 4
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.TukwilaWA.aov
Parcel No.: 3523049102
Address: 1121 ANDOVER PK W TUKW
Suite No:
Applicant: CHASING FIREFLIES
RECEIPT
Permit Number: D12 -130
Status: APPROVED
Applied Date: 04/20/2012
Issue Date:
Receipt No.: R12 -01508
Payment Amount: $738.15
Initials: JEM Payment Date: 05/04/2012 01:59 PM
User ID: 1165 Balance: $0.00
Payee: NORTHWEST HANDLING SYSTEMS, INC.
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 292573 738.15
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
BUILDING - NONRES
STATE BUILDING SURCHARGE
000.322.100 733.65
640.237.114 4.50
Total: $738.15
doc: Receiot -06 Printed: 05 -04 -2012
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO: PERMIT NO.
•CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 k.IR. (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
IL\42-/3
Project: ':
r'?.Fr/ 7$ y /c; ,t- /-"r:ILf s
Type of Inspection:
7:----, /1-7'/ L..
Address:
/ /e2 / r1Az) /c.,2 pe e.1,,
Date Called:
Special Instructions:
� ��L
%
_
j /ii�'' / /r .r ? a p3s2/ -2ss3
C 96640 -0 /
Date Wanted ::.
!/r %/om
a.m. .
Requestera
�li /tee
Phone No:
d6. - ;S/(° - .4/y92
ElApproved per applicable codes. E Corrections required prior to approval. 1
COMMENTS:.;
C
(24 Zei7O
/ /to-X , -- ,I-7'2€m )w
Date:
r•. . /
REINSPECTION FEE REQUIRED. Prior o next inspection. fee must be
paid at 6300 Southcenter Blvd Suite 100. Call to schedule reinspection.
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
-i3o
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
444 Andover Park East, Tukwila, Wa. 98188 206 - 575 -4407
Project: /
GhGS,\,c, n+-e -i�r 1 frS .
of Inspection:
k4c,k F; ,,a, J
Address:
Suite #: I /)- I I hc:� 1c- Pk W
Contact Person:
Special Instructions:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
F o-c f;.„ 1 OI(
Needs Shift Inspection:
Al,,,, 3 ) 1
Sprinklers:
Hrs.:
Fire Alarm:
Hood & Duct:
Pre -Fire: /11//-
Occupancy Ty6e:
Monitor: %
�/
Permits: N /
Inspector:
Al,,,, 3 ) 1
Date: .s -/i -/
Hrs.:
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. CaII to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word /Inspection Record Form.Doc
6/11/10
T.F.D. Form F.P. 113
Fireproofing
Aggregates
Shot.crete
Concrete
Masonry December 21,2012
Asphalt
Roofing
P i l i n g
S t e e l
S o i l s File: 12 -310
W o o d
A.A.R. TESTING
LABORATORY, INC.
CONSTRUCTION INSPECTION AND LIATERIAL TESTING
NATIONALLY, ACCEPTED LABORATORY
Building Official
City of Tukwila Building Department
6300 Southcenter Blvd.
Tukwila, WA 98188 C11419
LA
OEC 2 62012
Project: Chasing Fireflies PERMIT CENT
Address: 1121 Andover Park W.
Permit No.: D12A30.
This is to advise you that special inspections are completed on the above
referenced project. The following inspection was required and a copy of our
inspection report has already been forwarded to you.
1. Proprietary anchor installation
To the .best of our knowledge all work inspected `conforrhed'to Tukwila Building
Department'a,pproved plans, specifications, IBC and related codes and /or verbal
or written instructions from the Engineer of Record.
Sincerely,
A.A.R. TESTING LABORATORY, INC.
v
Aia
Kimberle.Anderson
President
CC: NorthWest Handing Systems, Inc.- Mike.Sotenson
Tel: (425) 881 -5812 Fax (425) 881 -5441 e 7126 180th Ave. NE* P.O. Box 2523* .Redmond, WA 9.8073
BY G. OHANIAN
DATE 4-13-12
SUBJECT
RAdK DEOI(N & ENdINEERINd do.
412 WEST BROADWAY, SUITE #204
dLENDALE, dA. 91204
TEL:(818)240 -3810 FAX:(818)240 -3813
SHEET NO. 1
JOB NO.. RD -16016
STRUCTURAL CALCULATIONS OF STORAGE
RACKS FOR:
CHASING FIREFLIES
1121 ANDOVER PARK WEST
TUKWILA, WA. 98188
PER IBC 2009 EDITION
SECTION 2208
STORAGE RACKS CAPACITY:
3500 # / LEVEL
CALCS. 1 THRU 4
DRAWINGS: RD -16016
FILE COPY
P rmft No..
EXPIRES 12 -26 -13
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAY 01 2012
City of Tukwila
BUILDING DIVISION
t• 130
RECEIVED
APR 20 2012
PERMIT CENTER
BY G. OHANIAN
DATE 4 -13 -12
SUBJECT
RACK DEOIG1N & EN(4INEERINd CO.
412 WEST BROADWAY, BUITE #204
OLENDALE, dA. 91204
TEL:(818)240 -3810 FAX:(818)240 -3813
SHEET NO. 2
JOB NO.. RD -16016
0
O
FRONT VIEW
BEAM
SEISMIC DESIGN
S pS X l
V- _ Rx 1.4
Ix =1.63
Sx =.77
-
F Y =55 KSI.
SIDE VIEW
LOAD PER BEAM + 25% IMPACT LOAD
(4.0 Kx.88) +(2.0 Kx.25) = 4.0- 2.0 K
2 BEAMS
M= 8 =21 "K
SR= .64 <.77
4
A 384.1 L =.42 "< 180 =.53"
x E
xW IBC 2009 (SEC. 2208), RMI SPECS.
ASCE 7 -05 (SEC. 15.5.3)
S Os =0.94 (USGS WEB SITE, "SITE CLASS 0 ")
1 =1 NO PUBLIC ACCESS
R =6 MOM. CONN.
R =4 BRACED
W =D.L.+ 3 PALLET LOAD
LOAD PER COL. = 2x3.5 K =3.5 K
2 COL.
P =.2 DL+ (3.5Kx0.75) =2.8K
W =•2DL+ (3.4<1.x0.67)= 2.5 K
\L= '28 K
ONGIT.
V = .42K
TRANS.
LONGIT. SEISMIC
Conterminous 48 States
2009 International Building Code
Latitude = 47.4442
Longitude = — 122.25790000000002
Spectral Response Accelerations SMs and SM1
SMs = Fax Ss and SM1 = Fv x S1
Site Class D — Fa = 1.0 ,Fv = 1.521
Period Sa
(sec) (g)
0.2 1.403 (SMs, Site Class 0)
1.0 0.729 (SM1, Site Class 0)
Conterminous 48 States
2009 International Building Code
Latitude = 47.4442
Longitude = — 122.25790000000002
Design Spectral Response Accelerations SDs
and SD1
SDs = 2/3 x SMs and SD1 = 2/3 x SM1
Site Class D — Fa = 1.0 ,Fv = 1.521
Period So
(sec) (g)
0.2 0.935 (SDs, Site Class 0)
1.0 0.486 (SD1, Site Class D)
.28 K
9.9'K
6.5 -K
9.9 K
BY G. OHANIAN RACK DE$I(N & ENdINEERIN(# CO.
DATE . 4 -13 -12 412 WET BROADWAY, gUITE #204
SUBJECT LENDALE, dA. 91204
TEL:(818)240 -3810 FAX:(818)240 -3813
SHEET NO 3
JOB NO. RD -16016
COLUMN ANALYSIS
M
3" a
1I '
U ,
tt =.070"
COMBINED STRESS RATIO
Pex= (KE)12 = 18.0
ax =1 Pex .72
Fy =55 KSI
Ae =.62
Ix =.95
Se =.6
rx =1.2
ry =1.1
Qc =1.8
Qb =1.67
Cmx =.85
BASE PLATE
ANCH. TENSION = .25 K
ANCHOR SHEAR - .14 K
KL= 72x1.7 =102
rx 1.2
KL =1 =47
Y
Mn =Se .Fy= 35
f2c.P + f2b.Cmx.M = .93 <1
Pn M, .ax
(2)-1/2"0 ANCHORS PER BASE PL., 3 1/4" EMB.
HILTI KWIK BOLT -TZ ESR -1917
SPECIAL INSPECTION IS REQUIRED
MOMENT AT BEAM CONNECTION
2
Fe =rr KLj2 =28
r
2
F n =F y(.658 c ) =24 KSI
Pn= Fr, .Ae = 15 K
2.8K 9.9 )
I Q�� %- BASE PLATE
I
A c = N/Fy /Fe = 1.40
Ac<1.5
7 3/4 "x5 "x3/8"
.5x.07x 1x65 =2.3 K BEARING CAPACITY
OF COL. HOLE 6.5 "K
7/16 "0 RIVET
A =.1 Fy =79KSI
Pa = .1x79x.4 = 3 K
8.2-K
Ma = (2.3'x4 ") +(1.1 Kx2 ") = 11.4 "K 3 PIN CONN.
CONN.
M END= • 01 )(WI 2= 1.6 "K
M - _ 8.2 "K M= 9.8 K
SEISMIC TOTAL
8.2 "K
9.9 "K
1 6"
7 3/4"
BY G. OHANIAN RAdK DEOI(1N & EN(IINEERIN( do.
DATE . 4 -13 -12 412 WET BROADWAY, QUITE #204
SUBJECT LEND• dA. 91204
TEL:(818)240 -3810 FAX:(818)240 -3813
SHEET NO 4
JOB NO.. RD -16016
OVERTURNING
MOT = .42'&2cxL170 "x0.66 =94 -K
MR = 2.8 Kx44 "= 123 "K
NO UPLIFT
LOAD TO DIAGONAL
P = .42 Kx2 x 58 = 1.1 K
COL. 44
FY =55 KSI
Ae =.26
rx =.48
Q =.74
L= 58"
P° = 2.5 K
CHECK WELDS
P°= (1_.01L)L.t.F„ =5.36K
0= 2.55
= 2.1Kx2 = 4.2K
SIDES
CHECK SLAB
2800 =2 8 °'
1000
403 =20"
.42K
2.8x144=403 °"
2
M= 1 ( 12 ) x1000x 2 x12 =666 "#
S= 12x62 = 72
6
666 = 9 <1.6 V2500 =80
72
28K 28K
I x
L� \J
44"
.42K
n
TOP LEVEL LOADING
W= 0.2m+1.750 1.95K LOAD PER COL.
V= .32 K
MOT= .32Kx2 x144 = 92 "K
COL.
MR = 1.95K x44"= 86 "K
UPLIFT = 92 "K -86 "K = ,13
44"
BOTH SIDES TYP.
t =.07"
2800 #
6" CONCRETE SLAB
2500 PSI. CONC.
1000 PSF. SOIL
10 -01 -2012
MIKE SORENSON
1100 SW 7 ST
RENTON WA 98057
City of Tukwila Ji.m Haggerton, Mayor
Department of Community Development Jack Pace, Director
RE: Permit No. D12 -130
CHASING FIREFLIES
1121 ANDOVER PK W TUKW
Dear Permit Holder:
In reviewing our current records, the above noted permit has not received a final inspection by the City of Tukwila Building
Division. Per the International Building Code, International Mechanical Code, Uniform Plumbing Code and /or the National
Electric Code, every permit issued by the Building Division under the provisions of these codes shall expire by limitation and
become null and void if the building or work authorized by such permit has not begun within 180 days from the issuance date
of such permit, or if the building or work authorized by such permit is suspended or abandoned at any time after the work has
begun for a period of 180 days. Your permit will expire on 11/07/2012.
Based on the above, you are hereby advised to:
1) Call the City of Tukwila Inspection Request Line at 206 -431 -2451 to schedule for the next or final inspection.
Each inspection creates a new 180 day period, provided the inspection shows progress.
-or-
2) Submit a written request for permit extension to the Permit Center at least seven (7) days before it is due to
expire. Address your extension request to the Building Official and state your reason(s) for the need to extend
your permit.
The Building Code does allow the Building Official to approve one extension of up to 180 days. If it is determined that your
extension request is granted, you will be notified by mail.
In the event you do not call for an inspection and /or receive an extension prior to 11/07/2012, your permit will become null
and void and any further work on the project will require a new permit and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
Jenne
- r
tyLiv
er Marshall
t Technician
File: Permit File No. D12 -130
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone 206 -431 -3670 • Fax 206 -431 -3665
NORTHWEST
H A N D L I N G S Y S T E M S , I N C.
The Material Handling Experts
•
FILE COPY
Prir'ir Jt No. ,
1100 SW 7th St
Renton, WA 98057
(425) 255 -0500 ph
(425) 228 -6946 fax
ATTENTION FIRE AND BUILDING DEPARTMENTS
RACK INFORMATION SUPPLEMENT
SITE ADDRESS: 1121 Andover PK W
TENANT NAME: Chasing Fireflies
DATE: April 19, 2012
APPLICANT: Mike Sorenson / (206) 818 -4488
1. Load application and rack and shelving configuration drawings attached.
2. Attached plans detail the rack /shelving locations, dimensions, and specifications.
3. Stamped engineering calculations attached.
4. Vertical members of storage racks are designed and installed so that failure of one vertical
member will not cause collapse of more than the bay or bays directly supported by that
member.
5. Commodities stored: Childrens clothing. Shirts, pants, dresses, coats. Made mostly of cotton
and polyester. Stored in open top boxes or on wood pallets.
6. Sprinkler System Information: .39gpm/5600 sq. ft. Head temp: 165*
7. Smoke and heat vents: In place, as shown on site plan picture.
8. Building egress and exits indicated on attached drawings.
9. Emergency egress paths indicated on attached drawing.
tso
RECEIVED
APR 20 2012
PERMIT CENTER
POW GO COPY
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: D12 -130 DATE: 04 -20 -12
PROJECT NAME: CHASING FIREFLIES
SITE ADDRESS: 1121 ANDOVER PK W
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # After Permit Issued
DEPARTMENTS:
Bu' Ildin> visiorY
Public Works
Fire Prevention
Structural
s
Planning Division
n Permit Coordinator
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Incomplete
DUE DATE: 04 -24-12
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
LETTER OF COMPLETENESS MAILED:
TUES /THURS ROUTING:
Please Route Structural Review Required ❑ No further Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
Notation:
REVIEWER'S INITIALS:
DUE DATE: 05-22 -12
Not Approved (attach comments) n
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents /routing slip.doc
2 -28-02
Contractors or Tradespeople Pr ter Friendly Page
•
General /Specialty Contractor
A business registered as a construction contractor with LEt1 to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name NORTH WEST HANDLING SYS INC UBI No. 600051641
Phone 4252550500 Status Active
Address 1100 Sw 7Th St License No. NORTHWH275JF
Suite /Apt. License Type Construction Contractor
City Renton Effective Date 4/6/1973
State WA Expiration Date 10/9/2013
Zip 980552939 Suspend Date
County King Specialty 1 General
Business Type Corporation Specialty 2 Unused
Parent Company
Business Owner Information
Name
Role
Effective Date
Expiration Date
FRANCK, JAMES JEROME
President
01/01/1980
Amount
KOSTY, CLARK RANDOLPH
Treasurer
01/01/1980
4015483385
THOMAS, KEVIN A
10/01/2012
01/01/1980
09/28/2011
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
TRAVS
81S103354822BCM
10/01/2001
Until Cancelled
$12,000.00
10/09/2001
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
31
CO ley Forge
4015483385
10/01/2011
10/01/2012
$1,000,000.00
09/27/2011
30
NATIONAL FIRE
ADV4015483385
10/01/2010
10/01/2011
$1,000,000.00
09/20/2010
29
ACE AMERICAN
INS CO
PMDG24651605002
10/01/2008
10/01/2010
$1,000,000.00
09/30/2009
28
ACE AMERICAN
INS CO
PMDG23858769
10/01/2007
10/01/2008
$1,000,000.00
09/28/2007
27
ACE AMERICAN
INSURANCE
COMPANY
PMDG22904279
11/01/2006
11/01/2007
$1,000,000.00
10/27/2006
26
BURLINGTON
INS CO
HGL0011190
11/01/2005
11/01/2006
$1,000,000.0011
/04/2005
Summons /Complaint Information No unsatisfied complaints on file within prior 6 year period
Warrant Information No unsatisfied warrants on file within prior 6 year period
https://fortress.wa.gov/lni/bbip/Print.aspx
05/04/2012
EXPIRED
NOV 02 2012
*-
EGRESS PATH
5' -6" typ
54'
CO
rn
CO CO CO CO
CO CO CO CO
0) rn rn 0)
1'
EGRESS PATH
iO)
CO
x
CO
0)
CO
0)
0)
CO
0)
CO
rn
x
CO
r
CO
rn
x
CO
CO
54'
CO
Q)
CO
v)
x
CO
rn
x
CO
0)
x
CO
0)
CO
0)
x
"4-
d-
CO
rn
x
CO
0)
x
CO i CO
0) ! rn
X 1 x
CO CO
CO
0)
1'
CO CO
0) 0)
CO
0)
x
CO
0)
CO
rn
CO
0)
x
0)
CO
0)
x
�t-
CO
rn
x
CO
01
CO
0)
x
CO
Co
16' —
CO
0)
CO
rn
x
If
CO
0)
x,
L----- ---- -J
CO
0)
x
0)
x
rn
x
�t-
CO
0)
CO
C)
x
1,11'
11' -8"
EGRESS PATH
EGRESS PATH
117
EF
oLIDJ
144'
49'
NORTH
w
49'
=PLAN VIEW
SCALE: 3/32" = 1' -0"
E1.77.)
50'
NOV 01 2012
24' -9"
24' -7"
24' -7"
24' -7"
21'—
7)
,SETAr TiE PERMIT
1 Ui;RED FOR
[i'ritedwical
le
®'Plumbing
131/Gas Piping
City of Tukwila
BUILDING DIVISION
REVISIONS
No changes shall be made to the scope
of work without prior approval of
1
Tukwila Building Division.
l `r T: 7.: %43!ofs will require a new plan submittal
L may include additional plan review fees.
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAY 01 2012
v
ty of Tukwila
BUILDING DIVISION
FILE COPY
Permit No.
Plan review approval is subject to errors and omissions.
x p 3ry jai of construction documents does not authorize
th volation of any adopted code or ordinance. Receipt
of t.pproved Field Copy and conditions is acknowledged:
By
Date:
City Of Tukwila
BUILDING DIVISION
SPECIAL INSPECTION FOR STORAGE RACKS
(OVER 8 FEET)
Periodic special inspection is required during the
anchorage of access floors and storage racks 8 feet
or greater in height in structures assigned to
Seismic Design Category D, E or F.
IBC 1707.5 and
TABLE 1704.4 (4) Inspection of anchors installed
in hardened concrete.
RECEIVED
APR 2 0 2012
PERMIT CENTER
SHEET NUMBER
1
NOT PUBLISHED. ALL RIGHTS RESERVED. THESE DRAWINGS, SPECIFICATIONS, IDEAS, DESIGNS, AND ARRANGEMENTS
REPRODUCED, COPIED,
0
a
w
1-
s
0
x
w 3
III p
J W
N
aJ
2
0
�w
w r
=o
r
ce
o
o_ °w
o
z tn
N
• a
z o
J
O cn
W u)
a 1-
O 0
a O
w o
1- w
D
Z m
L
w
o
- o
(1) w
w
0
0
0
0
THEREBY ARE AND
WRITTEN CONSENT OF NORTHWEST HANDLING SYSTEMS.
LLI
Oow
< ZZ <
Er 0 D Q
vOww>-
N0RTHWEsT
w O O
Cr 000
(1) °' o
= I
F- Q�
N N
(J)0in
0 z N
.t
0 w
RACK LAYOUT
SHEET DESCRIPTION
REVISIONS
DRAWING NUMBER
D -1
to
7 3/4"
(2) -1/2 "0 ANCHOR BOLTS PER BASE PLATE
3 1/4" EMB., (SEE NOTE NO. 4)
r
e
W
• 4 1.
4.
A.
s
•
4
d.
•
O 4
. • O
r
M
a
e
BOTH SIDES TYP>
1/8 V1.5"
1 1/2"
.� ,% 3/8
t =.06"
SEC. A —A
SEC. B —B
1/4"o SAFETY LOCK
(1000 # CAPACITY)
7/16 "0 RIVET
ASTM A576 -90B
HOT— WROUGHT UNS
G10100 GRACE C -1010
3 PIN CONNECTION
ROW SPACER
GENERAL CONFIGURATION
N
a)
acv
N
N
N
\ \
96"
1
u
4
10\
N
N
N
L()
1
3
44"
3
r
N
N
1
44"
3
1
NOTES:
EXP RSA)
NOV 01, Z012
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAY 01 2012
City of Tukwila
BUILDING DIVISION
1— DESIGN OF STEEL STORAGE RACKS AS SHOWN BY THESE DRAWINGS
AND CALCULATIONS ARE IN COMPLIANCE WITH THE REQUIREMENTS
OF THE INTERNATIONAL BUILDING CODE 2009 EDITION, SECTION 2208
2 —STEEL FOR ALL SHAPES FY =55 KSI. ASTM A1011 GR.55 (EXCEPT AS NOTED)
3 —NO FIELD WELDING IN THIS PROJECT ALL WELDED CONSTRUCTION IN THE SHOP
OF THE APPROVED FABRICATOR #00777 (E70XX ELECTRODES)
4 —ALL ANCHORS HILTI KWIK BOLT —TZ ESR -1917
SPECIAL INSPECTION IS REQUIRED
5— CONCRETE SLAB 6" THICK 2500 PSI. SOIL BEARING CAPACITY 1000 PSF
6— STORAGE RACK CAPACITY 3500 # /LEVEL
7 —RACK INSTALLATIONS SHALL DISPLAY IN ONE OR MORE CONSPICUOUS LOCATIONS
A PERMANENT SIGN OF 50 SQUARE INCHES IN AREA, SHOWING THE CAPACITY
OF THE 3500 # /LEVEL
8— STORAGE RACKS SHALL BE INSTALLED WITH A MAXIMUM TOLERANCE FROM THE
VERTICAL OF 1/2" IN 1C-0" OF HEIGHT
9 —THE CLEAR SPACE BELOW SPRINKLERS SHALL BE A MINIMUM OF 18 INCHES
BETWEEN THE TOP OF THE STORAGE AND THE CEILING SPRINKLER DEFLECTOR.
10— STORAGE RACK AREA NOT OPEN TO PUBLIC, EMPLOYEE ACCESS ONLY
3
1
RECEIVED
APR 20 2012
PERMIT CENTER
RACK DESIGN AND ENGINEERING
412 WEST BROADWAY, SUITE #204, GLENDALE, CA. 91204
f
DATE: 4 -15 -12
PROJECT:
FRONT VIEW
SIDE VIEW
EXPIRES 12 -26 -13
CHASING FIREFLIES
1121 ANDOVER PARK WEST, TUKWILA, WA.
STORAGE RACK DETAILS JOB
RD-16016
SHEET NO.
1 OF 1