HomeMy WebLinkAboutPermit EL12-0381 - TOTAL WINETOTAL WINE
300 ANDOVER PK W
EL12 -0381
City oftukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206-431-3665
Web site: http: / /www.TukwilaWA.gov
Parcel No.: 2623049001
Address: 300 ANDOVER PK W TUKW
Project Name: TOTAL WINE
ELECTRICAL PERMIT
Permit Number: EL12 -0381
Issue Date: 05/10/2012
Permit Expires On: 11/06/2012
Owner:
Name: SEGALE PROPERTIES LLC
Address: PO BOX 88028 , TUKWILA WA
Contact Person:
Name: STEVE NELSON
Address: PO BOX 88028 , TUKWILA WA
Contractor:
Name: R -C TRUE LINE CORPORATION
Address: 15321 105 AV CT E , PUYALLUP WA
Contractor License No: RCTRULC038QG
Phone: 206 575 -5200
Phone: 253 845 -8775
Expiration Date: 11/07/2013
DESCRIPTION OF WORK:
ELECTRICAL FOR TENANT IMPROVEMENT
Value of Electrical: NRES: $225,000.00
RES: $0.00
Type of Fire Protection: SPRINKLERS
Electrical service provided by: PUGET SO GY
Permit Center Authorized Signature:
Fees Collected:
National Electrical Code Edition:
I hereby certify that I have read and examined this pe
governing this work will be complied with, whether spec
The granting of t
construction or
Signature:
$3,948.00
2008
Date: › ... C `[ C
d know the same to be true and correct. All provisions of law and ordinances
ed herein or not.
ority to violate or cancel the provisions of any other state or local laws regulating
ed to sign and obtain this electrical permit.
Date: 5.--/0
This permit ll become null and void (he work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: EL -4/10
EL12 -0381
Printed: 05 -10 -2012
• •
PERMIT CONDITIONS
Permit No. EL 12 -0381
* *ELECTRICAL **
1: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical Inspector
at each work site.
2: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical Inspector.
3: All electrical work shall be in accordance with NFPA 70 - NEC, and requirements for electrical installations, Chapter
296 -46B WAC.
4: When any portion of the electrical installation is to be hidden from view by permanent placement of parts of the
building, such equipment shall not be concealed until it has been inspected and approved by the Electrical Inspector.
5: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any violation
of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related documentation that
presumes to grant this authority are therefore not valid.
6: Any change in the scope of work described by the electrical work permit shall require additional work permits. Where
approved plans have been issued, revisions to the plans and additional review may be required.
doc: EL -4/10
EL12 -0381 Printed: 05 -10 -2012
CITY OF TUKWA
Community Development Department
Permit Center
6300 Southcenter Blvd, Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
41
- ---1 2 -09-)S
Electrical permit No. b-- ' 1
.Project No
.
Date Application Accepted: i14 12-
'Date Application Expires. 191114 1 11
(For office use only) •
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
King Co Assessor's Tax No.: 262304-9001
Site Address: 300 Andover Park West Suite Number: 500
Tenant Name:
Total Wine
PROPERTY OWNER
Name: Steve Nelson
Name: Segale Properties LLC
Address: PO Box 88028
Address: PO Box 88028
City: Tukwila State: WA
City: Tukwila State: WA
Zip: 98138
CONTACT PERSON— person receiving all project
communication -
Name: Steve Nelson
Address: /5$ ( /2 c,...e_Crie:
Address: PO Box 88028
PholA‹ _099 tp,36._ -3 , f'y'r
City: Tukwila State: WA
Zip: 98138
Phone: (206) 575-2000 Fax: (206)
575-1662
Email: snelson@segaleproperties.com
New Tenant:
Floor: 1
Yes D..No
ELECTRICAL CONTRACTOR INFORMATION
Company Name: T4)49dcteamiae4 ? ...C._ •b..,
Address: /5$ ( /2 c,...e_Crie:
.02
City: /,..- State,/4 ZiT93 7
PholA‹ _099 tp,36._ -3 , f'y'r
Conti Reg No. :"6%635,88pte: /( .... 7-73
Tukwila Business License No.:6 QvB- -,,
Valuation of Project (contractor's bid price): $ 225,000
Scope of Work (please provide detailed information):
Tenant improvement in an existing 28,272 square foot retail space.
Will servicebe altered? 0 Yes J1 No
Type of Use: Retail store
Tyne of work:
O New 0 Addition
O Low Voltage 0 Generator
Property Served by:
IZI Puget Sound Energy 0 Seattle City Light
HA.ApplicationsWorms-Applications On Line .1 2011 ApplicationskElectrical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
Adding more than 50 amps? 0 Yes No
O Service Change
O Fire Alarm
O Remodel
O Telecommunication
O Tenant Improvement
O Temporary Service
Page 1 of 2
•
RESIDENTIAL
NEW RESIDENTIAL SERVICE
❑ New single family dwellings
(including an attached garage)
❑ Garages, pools, spas and outbuildings
❑ Low voltage systems
(alarm, furnace thermostat)
$152.85
$81.90 ea
$59.85 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
❑ Service change or alteration $81.90
(no added /altered circuits)
❑ Service change with added/altered circuits $81.90
number of added circuits $11.55 ea
❑ Circuits added /altered without service change $54. 60
(up to 5 circuits)
❑ Circuits added /altered without service change $54.60
(6 or more circuits) $7.65 ea
❑ Meter /mast repair $68.25
❑ Low voltage systems $59.85
(alarm, furnace thermostat)
PERM IT APPLICATION NOTES -
MULTI - FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
❑ Temporary service (residential) $63.00
❑ Temporary service (generator) $78.75
❑ Manufactured /mobile home service $84.00
(excluding garage or outbuilding)
❑ Carnivals $78.75
Number of concessions $10.50 ea
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR ELECTRICAL CONTRACTOR:
Signature:
*P/72,6_
Date: 04/24/2012
Print Name: Steven R. Nelson Day Telephone: (206) 396 -2011
Mailing Address: PO Box 88028 Tukwila WA 98138
City
H: \4pplications Torms- Applicatiwss On Linc\201 I Applications\Electrical Permit Application Revised S -9-11 ducx
Revised: August 2011
bh
State Zip
Page 2 of 2
Cit, of Tukwila,
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: //www.ci.tukwila.wa.us
SET RECEIPT
RECEIPT NO: R12 -01406
Initials:
Payment Date: 04/24/2012
User ID: 1670 Total Payment: 5,220.75
Payee: SEGALE PROPERTIES LLC
SET ID: 0424 SET NAME: TOTAL WINE
SET TRANSACTIONS:
Set Member Amount
EL12 -0381 3,948.00
M12 -071 827.81
PG12 -061 444.94
TOTAL: 3,948.00
TRANSACTION LIST:
Type Method Description Amount
Payment Check 2111 5,220.75
TOTAL: 5,220.75
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
ELECTRICAL PERMIT - NONR
ELECTRICAL PLAN - NONRES
MECHANICAL - NONRES
PLAN CHECK - NONRES
PLUMBING - NONRES
000.322.101.00.0
000.345.832.00.0
000.322.102.00.0
000.345.830
000.322.103.00.0
TOTAL:
3,158.40
789.60
662.25
254.55
355.95
5,220.75
INSPECTION RECORD.
Retain a copy with permit
INSPE TION NO. PERMIT NO:
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 V—::` (206) 431- 3670_.
Permit Inspection Request Line (206) 431 -2451
Project: aTkL-'J IJC
Address'
446)-IdeAN
Special Instructions:
Type of Inspection:
ate Called:
Date Wanted:
Requester:
Phone No:
T-4 Approved per applicable codes.
COMMENTS:
ElCorrections required prior to approval.
I
Inspector:
J" 1
n REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection'
Date:
Molt 2--
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -367
Permit Inspection Request Line (206) 431 -2451 '';
INSPECTION RECORD
Retain a copy with permit
611-0311
PERMIT NO.
Project: 1;-;:lYtt . IAA A)e-
Type of Inspection:
7 ,
Address: 33o / jboi
IA/
Date Called:
Special Instructions:
Date Wanted:.
g O /
�p
p �.
Requester:
Phone No:
r
,Approved per applicable codes. El Corrections required prior to approval.
COMMENTS:
((ot/4 t4 ids eD,fittit
Inspector:
�H
�/r
� A'r��
�
Date: y o�
if � I
❑ REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
!(
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT N0.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 1iL (206) 431 -367
Permit Inspection Request Line (206) 431 -2451 X -
Project` / (j'���.� ` r�
Type of Inspection:
/� /'
2
Address:30 ��
Date Called:
Special Instructions:
Date Wanted:..
<3
(ap:mm:
Requester:
Phone No:
ElApproved per applicable codes.
ECorrections required prior to approval. 9
COMMENTS:
bJrR,�f Vies-00,6 co%
r
&Alec
E
Date: 07 /f7 I
n REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Inspector:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION'
6300 Southcenter Blvd., #100, Tukwila. WA 98188 _ (206) 431 -367
Permit Inspection Request Line (206) 431 -2451
0.12. lo3g
Project: _ . '
-larsia. itJt46
Type of Inspection:
Address:
o44IjtA
Date Called:
Special Instructions: i
Date Wanted:.:
_ a.m\
.m.
Requester:
Phone No
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
1A1 41A/ P.oJa MikitoJltae.I4(
Inspector:
n REINSPECTION FEE REQUIRED. Prior to next inspection fee must:be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection. -.
INSPECTION, RECORD
Retain a copy with permit
INSPECTION NO. PERMIT 0.
CITY.OF'TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 T.- (206) 431 -3670
Permit" Inspection Request Line (206) 431 -2451
Project -
A!6
Type of Inspection:
7
3
Address:
-� __ �l!
Date Called:
—
Special Instructions:
Date Wanted:.
6/2-
a.m.
fre
Requester:
/
Phone No
;Approved - per applicable codes. 1 Corrections required prior to approval.
COMMENTS:
Date:
iC2(1Z—
n REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila: WA 98188 R (206) 431 -36
Permit Inspection Reggest Line (206) 431 -2451
Eti7-03?,
Project: �'?, jit�!
W G
Type of Inspection:
�ev/
Address:
360 mho
Date Called:
11
Special Instructions: !
Date Wanted:.
5/r
:m
m.
Requester:
Phone No:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
t2 kSI-PAS l 16) JrT,
Inspector: 4.41 64/16k.
Date: 05118 J�
•
n REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
SPERMITCO
PLAN REVIEW9RuNG SLIP
ACTIVITY NUMBER: EL12 -0381
PROJECT NAME: TOTAL WINE
SITE ADDRESS: 300 ANDOVER PK W, STE 500
DATE: 04/24/12
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # after Permit Issued
DEPARTMENTS:
Ivlslon
o o 'IZ
Bull to
Public Works
Fire Prevention
Structural
n
Planning Division
Permit Coordinator
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
DUE DATE: 04/26/12
Incomplete ❑ Not Applicable ❑
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROUTING:
Please Route % Structural Review Required n No further Review Required n
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
DUE DATE: 05/24/12
Approved n Approved with Conditions kr Not Approved (attach comments) ❑
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents /routing slip.doc
02/29/12
Contractors or Tradespeople 140ter Friendly Page
1
Electrical Contractor
A business licensed by L &I to contract electrical work within the scope of its specialty. Electrical
Contractors must maintain a surety bond or assignment of savings account. They also must have a
designated Electrical Administrator or Master Electrician who is a member of the firm or a full -time
supervisory employee.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent Company
R -C TRUE LINE CORPORATION
2538458875
15321 105Th Ave Ct E
Puyallup
WA
98374
Pierce
Corporation
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Specialty 1
Specialty 2
601828382
Active
RCTRULC038QG
Electrical Contractor
11/7/1997
11/7/2013
General
Unused
Other Associated Licenses
License
Name
Type
Specialty
1
Specialty
2
Effective
Date
Expiration
Date
Status
TRUEL "035KH
TRUE
LIN
LINE
Electrical
Contractor
General
Unused
5/8/1997
5/8/1999
Archived
Master Electrician INFORMATION
License RAU *RRH967C3
Name RAU, ROBERT H
Status Active
Business Owner Information
Name
Role
Effective Date
Expiration Date
RAU, ROBERT H
Violation Amount
01/01/1980
8/10/2009
RAU, CARLOTTA
ELECTRICAL CITATION
01/01/1980
$250.00
RAU, ROBERT H
Agent
01/01/1980
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
1
DEVELOPERS SURETY
& INDEM CO
445594C
11/01/1997
Until Cancelled
$4,000.00
06/15/2001
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information No records found for the previous 6 year period
Summons /Complaint Information Summons and Complaints are not filed with the department for this contractor type
Warrant Information Warrants are not filed with the department for this contractor type
Infractions /Citations Information
Infraction / Citation
Date
RCW Code
Type
Status
Violation Amount
EREEB00414
8/10/2009
19.28.161 RCW
ELECTRICAL CITATION
Satisfied
$250.00
https: // fortress .wa.gov /lni /bbip /Print.aspx 05/14/2012
ELECTRICAL SYMBOLS
NOTE: LEGEND ALL SYMBOLS,
ABBREVIATIONS, ETC. ARE NECESSARILYUS USED ON THE DRAWINGS.
ABBREVIATIONS
(ALL ABBREVIATIONS SHOWN ARE NOT
NECESSARILY USED ON THE DRAWINGS.)
UGHTING
WIRING DEVICES & OUTLETS
ELECTRICAL ONE —UNE & RISER
IBM
FLUORESCENT LIGHT FIXTURE: (SEE LIGHT FIXTURE SCHEDULE)
a = SWITCHED BY SWITCH "a"
A = LIGHT FIXTURE TYPE "A"
LIGHT FIXTURE WITH NIGHT LIGHT
LIGHT FIXTURE WITH EMERGENCY LIGHTING BATTERY PACK
LIGHT FIXTURE WITH DUAL BALLASTS CIRCUITED SEPARATELY.
(SHADING IMPLIES EMERGENCY BALLAST WITH BATTERY PACK)
AV V V LIGHTING TRACK WITH LIGHT FIXTURE TYPES AS INDICATED
-0-11-0-0- MIRROR LIGHTS (SEE LIGHT FIXTURE SCHEDULE)
0A LIGHT FIXTURE - CEILING / WALL MOUNTED.
Q A = LIGHT FIXTURE TYPE "A"
0A WALL WASHER LIGHT FIXTURE - ARROW INDICATES DIRECTION.
A = LIGHT FIXTURE TYPE "A"
�
A WALL MOUNTED LIGHT FIXTURE.
A = LIGHT FIXTURE TYPE "A"
g SITElil
LIGHTING FIXTURE (SEE LIGHT FIXTURE SCHEDULE)
031A EXIT / AL M, .
A = LIGHT SIGN - IXTCEILING FURE TYPE W "LA" (SEE OUNTED LIGHT ARROWS FIXTURE AS SCHEDULE) INDICATED
A EMERGENCY BATTERY PACK LIGHT FIXTURE - CEILING /WALL
MOUNTED. (SEE LIGHT FIXTURE SCHEDULE)
EtAFEA (AREA FOR EVACUATION ASSISTANCE) SIGN - CEILING /WALL
® @MOUNTED, ARROWS AS INDICATED, A = LIGHT FIXTURE TYPE "A"
(SEE LIGHT FIXTURE SCHEDULE)
SECURITY
8
Clo
�PTZ
CPU & MONITOR (ELEVATION) WITH PERIPHERAL DEVICES
CPU & MONITOR (PLAN VIEW) WITH PERIPHERAL DEVICES
CLOSED CIRCUIT TELEVISION
CCTV (PAN TILT ZOOM)
REQUEST TO EXIT BUTTON
ELECTRIC DOOR LOCK
PANIC BUTTON (D= DESK W= WALL F= FLOOR)
CARD READER
DOOR MONITOR
GLASS BREAK
KEY PAD
MOTION DETECTOR
WATCH TOUR
SINGLE POLE WALL SWITCH (NO LETTER DESIGNATION)
SWITCH LETTER DESIGNATIONS AS FOLLOWS:
2 = TWO POLE WALL SWITCH
3 = THREE -WAY WALL SWITCH
4 = FOUR -WAY WALL SWITCH
D = DIMMER TYPE SWITCH
OS = OCCUPANCY SENSOR
P = SPST PILOT LIGHT SWITCH
K = KEYED LIGHT SWITCH
M = MOTOR RATED SWITCH
WP = WEATHER PROOF
f = CEILING MOUNTED OCCUPANCY SENSOR WITH POWER SUPPLY
4))) AND LOAD RELAY AS REQUIRED OR SPECIFIED.
cb
•
SIMPLEX RECEPTACLE - NEMA 5 -20R, UNO
DUPLEX RECEPTACLE - NEMA 5 -20R, UNO
DOUBLE DUPLEX RECEPTACLE - NEMA 5 -20R, UNO
SPECIAL RECEPTACLE — NEMA TYPE AS NOTED
TWIST -LOCK TYPE RECEPTACLE
GFCI
OR d� GFCI TYPE RECEPTACLE*
0
tLV
® v
® V
0A
OA
CD
•
m
a
ISOLATED GROUND TYPE RECEPTACLE*
EMERGENCY RECEPTACLE*
RECEPTACLE INSTALLED 6" ABOVE COUNTER OR BACKSPLASH*
RECEPTACLE INSTALLED IN CEILING*
RECEPTACLE INSTALLED IN FLOOR*
RECEPTACLE INSTALLED VIA DROP CORD*
*DUPLEX RECEPTACLE SHOWN, SIMILAR FOR OTHERS
RECEPTACLE LETTER DESIGNATIONS AS FOLLOWS:
C = CLOCK HANGER TYPE
E = EMERGENCY POWER
S = SWITCHED
IG = ISOLATED GROUND
TR = TAMPER RESISTANT
WP = WEATHERPROOF
MULTI - OUTLET SURFACE RACEWAY WITH NEMA 5 -20R
RECEPTACLES 12" ON CENTER, UNO.
TELEPHONE OUTLET - FLOOR OR WALL MOUNTED. INSTALL
AT SAME ELEVATION AS ADJACENT RECEPTACLE, UNO.
DATA OUTLET - FLOOR OR WALL MOUNTED. INSTALL AT
SAME ELEVATION AS ADJACENT RECEPTACLE, UNO.
MULTI - SERVICE OUTLET; TELEPHONE AND DATA - FLOOR OR
WALL MOUNTED. INSTALL AT SAME ELEVATION AS ADJACENT
RECEPTACLE, UNO.
MULTI- SERVICE POWER POLE WITH TELEPHONE, DATA AND POWER
OUTLETS A = TYPE, REFER TO TWM OUTLINE SPECIFICATIONS
MULTI - SERVICE FLOOR BOX WITH TELEPHONE, DATA AND POWER
OUTLETS A = TYPE, SEE SCHEDULE IN SPECIFICATIONS
POKE THROUGH, A = TYPE, SEE SCHEDULE IN SPECIFICATIONS
THERMOSTAT
JUNCTION BOX /OUTLET BOX
JUNCTION BOX /OUTLET BOX
BLANK FACE GFCI FEED THROUGH DEVICE
EMERGENCY SHUNT RELAY
STANDARD MOUNTING HEIGHTS
POWER EQUIPMENT & DEVICES
(AFF, AFG, UNLESS NOTED OTHERWISE)
ELECTRICAL
AUDIBLE APPLIANCES (CENTERLINE)
ALARMS
ANNUNCIATOR PANELS
CLOCK OUTLETS (CENTERLINE)
CONTROLS (CENTERLINE)
EXIT SIGNS (WALL MOUNTED, BOTTOM)
FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)
FIRE ALARM BELL (EXTERIOR)
FIRE ALARM CONTROL PANEL /UNIT (DISPLAY)
INTERCOM (AFEA ONLY)
INTERCOMS
PANELS /PANELBOARDS (TOP)
PULL STATIONS (HANDLE)
PHOTOCELLS
RECEPTACLES (CENTERLINE)
RECEPTACLES (EXTERIOR)
RECEPTACLES (GARAGES)
RECEPTACLES IN EQUIPMENT ROOMS
REMOTE INDICATING LIGHT (EQUIPMENT ROOMS)
REMOTE INDICATING LIGHT (FINISHED AREAS)
SAFETY SWITCHES
STARTERS
SWITCHES (CENTERLINE)
TELEPHONES (PUBLIC)
TELEPHONE, DATA OUTLETS (CENTERLINE)
TELEPHONE TERMINAL BOARD (BOTTOM)
TELEVISION OUTLETS
VISIBLE APPLIANCES (CENTERLINE)
84"
48"
48"
84"
48"
80"
60"
120"
60"
36"
48"
72"
48"
144"
18"
24"
26"
48"
48"
CEILING
48"
48"
48"
1 0 48 ", 1 0 36"
18"
6"
18"
84"
ANNOTATION
O
O
El
O
MECHANICAL OR FIRE PROTECTION PLAN CALLOUT
PLUMBING PLAN NOTE CALLOUT
ELECTRICAL PLAN NOTE CALLOUT
TECHNOLOGY PLAN CALLOUT
PLUMBING EQUIPMENT DESIGNATION. (CONTRACTOR FURNISHED
AND INSTALLED). REFER TO PLUMBING FIXTURE OR EQUIPMENT
SCHEDULES
EQUIPMENT DESIGNATION (OWNER FURNISHED,
CONTRACTOR INSTALLED)
MECHANICAL EQUIPMENT DESIGNATION (CONTRACTOR FURNISHED
AND INSTALLED UNLESS NOTED OTHERWISE)
CONNECTION POINT OF NEW WORK TO EXISTING
DETAIL REFERENCE UPPER NUMBER INDICATES DETAIL NUMBER
LOWER NUMBER INDICATES SHEET NUMBER
SECTION CUT DESIGNATION
MOW ELECTRICAL SERVICE PANELBOARD
(SURFACE OR FLUSH MOUNT)
TERMINAL CABINET (SURFACE OR
FLUSH MOUNT), TYPE AS NOTED
PLYWOOD TERMINAL BOARD FOR TELEPHONE
SYSTEM, UNO. SIZE AS NOTED.
ELECTRICAL DISTRIBUTION PANELBOARD
SWITCHBOARD OR MOTOR CONTROL
CENTER ON HOUSEKEEPING PAD
TRANSFORMER
<> MOTOR
200/3/150
DISCONNECT SWITCH - "200/3/150" DENOTES
AMPERES /POLE /FUSE NF= NON -FUSED CB= CIRCUIT
BREAKER (200/3/CB)
COMBINATION DISCONNECT (SAFETY) SWITCH AND
30/41i3/1 MOTOR STARTER "30/3/15/1" DENOTES
AMPERES /POLE /FUSE /NEMA STARTER SIZE NF=
NON -FUSED CB= CIRCUIT BREAKER (30/3/CB/1)
®2
Eno
0
L
MAGNETIC MOTOR STARTER, NEMA
SIZE AS NOTED. 3 -POLE, UNO.
MANUAL STARTER
VARIABLE FREQUENCY DRIVE
RELAY OR CONTACTOR (IN SCHEMATICS)
MAGNETIC CONTACTOR, SIZE, COIL VOLTAGE AND
NUMBER OF POLES AS INDICATED (L= LIGHTING
CONTACTOR, P= POWER CONTACTOR)
TIME SWITCH
CURRENT LIMITER
O PHOTOCELL
INDICATING LIGHT
I• PUSH BUTTON
m
STOP -START PUSH BUTTON CONTROL STATION
HAND -OFF -AUTO PUSH BUTTON CONTROL STATION
'I'D MUSHROOM -TYPE PUSH BUTTON
OVERHEAD PADDLE FAN
1 800A SWITCH
3P RATING AS SHOWN
200AS FUSED SWITCH
3P RATING,POLES AND
200AF FUSE TYPE AS SHOWN
FRS
1 225A CIRCUIT BREAKER
(3P RATINGS AS SHOWN
PANELBOARD
(SEE SCHEDULES)
�
1TX# TRANSFORMER
t i TYPE AND RATINGS
I °' AS SHOWN
r- AT1 AUTOMATIC TRANSFER
i O 1200A SWITCH. RATINGS AS
L_ _J3P SHOWN
EIVM
UTILITY
METER
GENERATOR,
SEPARATELY
DERIVED SOURCE
RATINGS AS SHOWN
T 400A
C3P
200AS
3P
200AF
FRS
NEMA 1
C1 225A
3P
.L
} NEMA 1
1
- - -- TX#
tt
L_ _J
ATV(W/ YPASS)^
DRAWOUT CIRCUIT
BREAKER. RATINGS
AS SHOWN
COMBINATION FUSED
SWITCH /STARTER AND
STARTER SIZE
COMBINATION CIRCUIT
BREAKER /STARTER AND
STARTER SIZE
MULTI- SECTION
PANELBOARD
(SEE SCHEDULES)
SHIELDED
TRANSFORMER
TYPE AND RATINGS
AS SHOWN
AUTOMATIC TRANSFER
SWITCH WITH BYPASS.
RATINGS AS SHOWN
-J 200A, 3P
GENERATOR,
NON- SEPARATELY
DERIVED SOURCE,
RATINGS AS SHOWN
COMBINATION DIGITAL VOLT METER /AMMETER
CIRCUIT IDENTIFICATION - SEE CIRCUIT SCHEDULE
GROUND FAULT RELAY
KIRK -KEY INTERLOCK
SHUNT TRIP
AMMETER, RANGE AS SPECIFIED OR REQUIRED
VOLTMETER, RANGE AS SPECIFIED OR REQUIRED
UTILITY METER (AS REQUIRED BY UTILITY)
0 AMMETER SWITCH
O VOLTMETER SWITCH
D WATT -HOUR METER, "D" DENOTES DEMAND REGISTER,
WH 15 "15" DENOTES MINUTES OF DEMAND INTERVAL
4 CURRENT TRANSFORMER RATING AS
SPECIFIED OR REQUIRED
�E- POTENTIAL TRANSFORMER RATING AS
SPECIFIED OR REQUIRED
TVSS
##
TRANSIENT VOLTAGE SURGE SUPPRESSOR
GROUND CONNECTION
GROUND CONNECTION WITH TEST WELL
GROUND ROD
LIGHTNING ARRESTER
CAPACITOR
CONTACT (OPEN OR CLOSED)
HEATER
MOTOR
BLOCK LOAD KW OR KVA
COMPLIANCE `1�V
NFPA ?O -NEC
MAY 0 9 2012
City of Ila
BUILDING IVISION
CIRCUITING & WIRING
SWITCHED HOT CONDUCTORS (SHOWN TRAILING NEUTRAL)
NEUTRAL CONDUCTOR
UNSWITCHED HOT CONDUCTORS (SHOWN LEADING NEUTRAL)
HOMERUN TO PANELBOARD, ARROWS INDICATE NUMBER
OF. CIRCUITS, HASH MARKS INDICATE NUMBER OF
CONDUCTORS. INFORMATION AT ARROWS ARE CIRCUIT
NUMBERS AND PANELBOARD.
EQUIPMENT GROUNDING CONDUCTOR IN CONDUIT
(GREEN INSULATION OR BARE)
ISOLATED GROUNDING CONDUCTOR IN CONDUIT
(GREEN INSULATION WITH YELLOW TRACER)
CONDUIT CONCEALED
CONDUIT IN /UNDER FLOOR /GROUND CONSTRUCTION
EXPOSED CONDUIT
FLEXIBLE CONDUIT
- LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)
CONDUIT TURNING DOWN
0 CONDUIT TURNING UP
CONNECTION POINT OR EQUIPMENT TERMINATION
EQUIPMENT TERMINATION
FILE COPY
rte. 2 —o97 44 l
Plan t+ it his #o amend on*sionn
Approval
documents • i : not authorize
the violation of any adopted code # + ►`` * . ReceI0
el approved Y4 '1 iedged:
City i lbta
BUILDING DIVISION
SEPARATE PERMIT
REQUIRED FOR:
'Mechanical
Eiectrical
Plumbing
a'Gas Pig
City of Tukwila
LBUILDING DIVISION
A
A AMPERES
A AIR (COMPRESSED)
A/C AIR CONDITIONING
ACC AIR COOLED CHILLER
ACCU AIR COOLED CONDENSING
UNIT
ADA AMERICANS WITH DISABILITIES
ACT
AF AMPERE -FUSE
AFC ABOVE FINISHED CEIUNG
AFCI ARC FAULT CIRCUIT
INTERRUPTER
AFEA AREA FOR EVACUATION
ASSISTANCE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING
JURISDICTION
AHU AIR HANDLING UNIT
Al ANALOG INPUT
AIC AMPERE INTERRUPTING
CURRENT
AL ALUMINUM
AO ANALOG OUTPUT
AP ACCESS PANEL
AP ACCESS POINT
ATL ACROSS- THE -UNE
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
B B BOILER
BAS BUILDING AUTOMATION
SYSTEM
BB BACKBONE
BD BACKDRAFT DAMPER
BD BLOWDOWN
BD BUILDING DISTRIBUTOR
BDF BUILDING DISTRIBUTION
FRAME
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
BFP BOILER FEED PUMP
BI BINARY INPUT
BKR BREAKER
BO BINARY OUTPUT
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BOS BOTTOM OF STRUCTURE
BTU BRITISH THERMAL UNIT
C C CONDUIT
CAT CATEGORY
CAN CABLE TELEVISION SYSTEM
CD CANDELA
CD CAMPUS DISTRIBUTOR
CT CURRENT TRANSFORMER
CCTV CLOSED CIRCUIT TELEVISION
CH CHILLER
CFM CUBIC FEET PER MINUTE
CKT CIRCUIT
CMP COMMUNICATIONS PLENUM
CABLE
CMR COMMUNICATIONS RISER
CABLE
CP CONDENSATE PUMP
CPT CONTROL POWER
TRANSFORMER
CPVC CHLORINATED POLYVINYL
CHLORIDE
CRAC COMPUTER ROOM AIR
CONDITIONING UNIT
CRU COMPUTER ROOM UNIT
CT COOLING TOWER
CTP
CU
CU
CVD
CWP
COOUNG TOWER PUMP
COPPER
CONDENSING UNIT
CUMULATIVE VOLTAGE DROP
CHILLED WATER PUMP
DB D DECIBELS
DDC DIRECT DIGITAL CONTROL
DFU DRAINAGE FIXTURE UNIT
DI DIGITAL INPUT
DI DUCTILE IRON
DN DOWN
DPDT DOUBLE -POLE,
DOUBLE -THROW
DPI DIFFERENTIAL PRESSURE
INDICATOR
DPST DOUBLE -POLE,
SINGLE -THROW
DS DOWNSPOUT
DS DUCT SILENCER
DX DIRECT EXPANSION
E
(E)
EA
EAT
EC
EXISTING
EXHAUST AIR
ENTERING AIR TEMPERATURE
ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EIA ELECTRONIC INDUSTRIES
ASSOCATIONS
EL ELECTRIFIED LOCK OR LATCH
EM EMERGENCY
EMI ELECTROMAGNETIC
INTEFERENCE
EMS ENERGY MANAGEMENT
SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
ER EQUIPMENT ROOM
ESFR EARLY SUPPRESSION FAST
RESPONSE
ETR EXISTING TO REMAIN
EWB ENTERING WET BULB
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER
TEMPERATURE
F
FACP ARE ALARM CONTROL PANEL
FBO FURNISHED BY
OTHERS /OWNER
FCA FAULT CURRENT AMPS
FCU FAN COIL UNIT
FD
FD
FFA
FFB
FF
FHC
FLOOR DISTRIBUTOR
FLOOR DRAIN
FROM FLOOR ABOVE
FROM FLOOR BELOW
FINISHED FLOOR
FIRE HOSE CABINET
FL FLOW UNE
FLA FULL LOAD AMPS
FIR FLOOR
FU FURNACE
FVNR FULL- VOLTAGE,
NON- REVERSING
GC G GENERAL CONTRACTOR
GE GROUNDING EQUAUZER
GFCI GROUND FAULT CIRCUIT
INTERRUPTER
GFR
G
GND
GPM
GRS
GYP
GROUND FAULT RELAY
GROUND
GROUND
GALLONS PER MINUTE
GALVANIZED RIGID STEEL
GYPSUM BOARD
H
HC HORIZONTAL
CROSS- CONNECT
HD HEAD
HD HUB DRAIN
HOA HAND -OFF- AUTOMATIC
HTG HEATING
HTR HEATER
HVU HEATING AND VENTILATING
UNIT
HWP HEATING WATER PUMP
HZ HERTZ
IC INTERMEDIATE
CROSS- CONNECT
IE INVERT ELEVATION
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IN WC INCHES OF WATER COLUMN
IP INTERNET PROTOCOL
ISC SHORT CIRCUIT CURRENT
ISDN INTEGRATED SERVICES DIGITAL
NETWORK
ISP INTERNET SERVICE PROVIDER
ISP INSIDE PLANT CABLE
J
JB JUNCTION BOX
J -BOX JUNCTION BOX
K
kcmil
KK
kV
kVA
kVAR
kW
kWH
L
L
LAN
LAT
LCC
LDB
LEC
LED
LF
LP
LRA
LWB
LWT
1000 CIRCULAR MILS.
KIRK KEY
KILOVOLT
KILOVOLT -AMPS
KILOVOLT -AMPS REACTIVE
KILOWATT
KILOWATT -HOUR
LOUVER
LOCAL AREA NETWORK
LEAVING AIR TEMPERATURE
LIMITED COMBUSTIBLE CABLE
LEAVING DRY BULB
LOCAL EXCHANGE CARRIER
UGHT- EMITTING DIODE
UNEAR FEET
LOW PRESSURE
LOCKED ROTOR AMPS
LEAVING WET BULB
LEAVING WATER
TEMPERATURE
M -M MULTIMODE
MAN METROPOLITAN AREA
NETWORK
MATV MASTER ANTENNA TELEVISION
SYSTEM
MAU MAKE -UP AIR UNIT
MAX MAXIMUM
MBH 1000 BTU PER HOUR
MC MAIN CROSS- CONNECT
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC ' MOTOR CONTROL CENTER
MD MOTORIZED DAMPER
MDF .; MAIN DISTRIBUTION FRAME
MDP MAIN DISTRIBUTION PANEL
MFR :MANUFACTURER
MG MOTOR GENERATOR
MH MAINTENANCE HOLE
MH MANHOLE
MIN MINIMUM
MLO ` MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT
PROTECTION
MPOE MAIN POINT OF ENTRANCE
MPOP: • MAIN POINT OF PRESENCE
MSB ? MAIN SWITCHBOARD
MSWB _.MAIN SWITCHBOARD
MS/TP MASTER SLAVE/TOKEN
PASSING :"= COMMUNICATION TRUNK
MTD :: MOUNTED
MU MAKE -UP
N
N/A
N/C
N/O
NC
NEC_
NF
NFPA
NIC
NL
NM
0
OA
OC
ORD
OS
OSHA
OSP
NOT APPUCABLE
NORMALLY CLOSED
NORMALLY OPEN
NOISE CRITERIA
NATIONAL ELECTRICAL CODE
NON -FUSED
NATIONAL FIRE PROTECTION
ASSOCIATION, INC.
NOT IN CONTRACT
NIGHT UGHT
NANO METER
OUTSIDE AIR
ON CENTER
OVERFLOW ROOF DRAIN
OCCUPANCY SENSOR
OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION
OUTSIDE PLANT
P.
P POLE
PBX PRIVATE BRANCH EXHANGE
PCR PUMPED CONDENSATE
RETURN
PDI PLUMBING DRAINAGE
INSTITUTE
PDU POWER DISTRIBUTION UNIT
PH PHASE
O PHASE
PIV POST INDICATOR VALVE
PNL PANEL
PNLBD PANELBOARD
POE POWER OVER ETHERNET
POTS STANDARD ANALOG
TELEPHONE LINE
POTS PLAIN OLD TELEPHONE
SERVICE
PROVIDE FURNISH AND INSTALL
PRV PRESSURE REDUCING VALVE
PSTN PUBLIC SWITCHED
TELELPHONE NETWORK
PT POTENTIAL TRANSFORMER
PTP POINT -TO- POINT
PTZ PAN, TILT, ZOOM
PVC POLYVINYL CHLORIDE
0
QTY QUANTITY
R
RA RETURN AIR
RC ROOM CRITERIA
RCP REINFORCED CONCRETE PIPE
RCPT RECEPTACLE
RD ROOF DRAIN
RD RETURN DUCT
REV
RF
RH
REVISION
RETURN FAN
RELATIVE HUMIDITY
RH ROOF HOOD
RHG REFRIGERANT HOT GAS
RLA RUNNING LOAD AMPS
RMC RIGID METAL CONDUIT
RPM REVOLUTIONS PER MINUTE
RTU ROOFTOP UNIT
RU RACK UNIT
SA S SUPPLY AIR
SAN SYNCHRONOUS OPTICAL
NETWORK
SD SMOKE DUCT DETECTOR
SD SUPPLY DUCT
SEER SEASONAL ENERGY
EFFICIENCY RATIO
SF SQUARE FEET
SF SUPPLY FAN
SPDT SINGLE -POLE,
DOUBLE -THROW
SPST SINGLE -POLE,
SINGLE - THROW
SP STATIC PRESSURE
SP SUMP PUMP
SS STAINLESS. STEEL
SS SANITARY SEWER
SS SOIL STACK
ST SHUNT TRIP
ST STEAM TRAP
STC SOUND TRANSMISSION CLASS
STM STEAM
SWBD SWITCHBOARD
T
TBB TELECOMMUNICATIONS
BONDING BACKBONE
TBD TO BE DETERMINED
TC /C TEMPERATURE CONTROLS
CONTRACTOR
TDH TOTAL DYNAMIC HEAD
TFA TO FLOOR ABOVE
TFB TO FLOOR BELOW
TGB TELECOMMUNICATIONS
GROUND BUS BAR
TIA TELECOMMUNICATIONS
INDUSTRY ASSOCIATION
TL TWISTLOCK
TMGB TELECOMMUNICATIONS MAIN
GROUND BUS BAR
TR TAMPER RESISTANT
TR TELECOMMUNICATIONS ROOM
TT TEMPERATURE TRANSMITTER
TWU THROUGH WALL AIR
CONDITIONING UNIT
TX TRANSFORMER
TYP TYPICAL
u
U/F UNDERFLOOR
U/G UNDERGROUND
U/S UNDERSLAB
UH UNIT HEATER
UL UNDERWRITERS
LABORATORIES, INC.
UNO UNLESS NOTED OTHERWISE
UPS UNINTERRUPTIBLE POWER
SUPPLY
UTP UNSHIELDED TWISTED PAIR
v
V
VAC
VD
VDC
VAV
VCP
VFD
VS
VTR
w *
W/
W/O
WAN
WAP
WB
WC
WG
WPD
WP
WS
WSFU
WT
WT
XP
X
VOLT(S)
VOLTS ALTERNATING
CURRENT
VOLTAGE DROP
VOLTS DIRECT CURRENT
VARIABLE AIR VOLUME
VITRIFIED CLAY PIPE
VARIABLE FREQUENCY DRIVE
VENT STACK
VENT THROUGH ROOF
WIRE
WITH
WITHOUT
WIDE AREA NETWORK
WIRELESS ACCESS POINT
WET BULB
WATER COLUMN
WATER GONG
WATER PRESSURE DROP
WEATHERPROOF
WASTE STACK
WATER SUPPLY FIXTURE UNIT
WATERTIGHT
WEIGHT
EXPLOSION -PROOF
REVISIONS
NO shall be made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
c1YV i�
APR 2 4 2012
PERMIT CENTER
ALL CONTRACTORS PRIOR TO BID SUBMISSION PROCESS
SHALL VISIT PROPOSED WORK SITE AND FIELD VERIFY ALL
EXISTING CONDITIONS. ANY CONDITION THAT DIFFERS FROM
THAT SHOWN ON THESE PLANS SHALL BE REPORTED TO
THE TENANT'S ARCHITECT /ENGINEER SO THAT NEW AND
REVISED BID DRAWINGS OR INFORMATION MAY BE ISSUED.
MODIFICATIONS TO THE SCOPE OF WORK WHICH RESULTS
FROM THE CONTRACTORS NEGLECT TO VISIT THE SITE
PRIOR TO SUBMITTING BID, SHALL BE THE CONTRACTOR'S
SOLE RESPONSIBILITY.
a a
0
ZQ
re E p
1- 01
W d
• rn
m
V x <2 o o
�
'5 u_<
ce
O L
ce U 1-
0 in
w Ca,
N
IL 4 0
0mto
w
w g
NI
5 ¢ a
aW
0
0
N
J
N
S
LAS VEGAS :: IRVINE :: PHOENIX :: SALT
W ON
EMEIBUcil
ZOgfbp O=
E2Z11•1 =WZZ9Ct
OMNI
oss
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE: E01 SYMBOLS.DWG
of coetk,O `L t P'
• • •^r lam/ •� +
E 113-
1 • Tn o 0:
• 1, z:
ii• AN a•I'; sresee:44,64,
essonsi sags°
SHEET NAME
ELECTRICAL SYMBOLS AND
LEGEND
SHEET NUMBER:
EO.1
0
SINK DISPOSAL
LC
39
{E) HA
I(E) LE 10
HA
16 PUSHBUTTON
T 3/3
k\
ICE MACHINES
F = = = =�
F = = = =�
= = : : = =z
4
6___ =r
6___ =�
drZiff../1,7
ROUTE CONDUIT
VIA TRENCH
-=
=1
_
12
LC
PART 2/3
LB
12
LC
PART 1%3
rarA,
LA
34
PART 1/2
= =�
LB
LB
LB
6
LB
4
LB
12 LB
LA
3
PART 2/2
39
PART 1/2
36
14 LA PART 2/2
1
5
LC `
==
p = - ==
= ==
_
= ==
HUMIDIFIER POWER,
+96" AFF
9
rl 'II LC
429
O
10
LC
27�
J
m
0
16
10
lam'
ELECTRICAL PO ER PLAN
SCALE: 1 /8" =1' -0"
REVIEWED 10h
COMPLIANCE WITH
NFPA70 - NEC
MAY 0 9 2012
City of Tukwila
BUILDING DIVISION
0-
GENERAL POWER NOTES:
1
PROVIDE ALL TERMINATIONS INCLUDING POWER AND CONTROL
WIRING TO ALL WALK -IN BOXES AND TO THE REMOTE
COMPRESSORS. COORDINATE WITH EQUIPMENT SUPPLIER FOR
SPECIFIC REQUIREMENTS.
2 PROVIDE SEAL -OFF'S FOR ALL CONDUITS ENTERING OR
LEAVING WALK -IN BOXES PER NEC, ARTICLE 300 -7(a).
3 RIGID CONDUITS ENTERING THE WALK -INS SHALL BE
PROVIDED WITH EXPANSION JOINTS PER NEC, ARTICLE 300 -
7(b).
5
CONTRACTOR TO VERIFY MOCP REQUIREMENTS FOR ALL
CHECKSTANDS WITH SUPPLIER PRIOR TO RELEASING
PANELBOARD INFORMATION TO PANELBOARD MANUFACTURER.
SEE PANELBOARD SCHEDULES ON SHEET E4.2 FOR CONDUIT
AND WIRE SIZE.
THE ISOLATED GROUND CONDUCTOR OF EACH ISOLATED
GROUND CIRCUIT SHALL BE CONTINUOUS (N0 SPLICES) THE
ENTIRE LENGTH OF THE CIRCUIT.
UNLESS OTHERWISE NOTED, ALL CIRCUITRY SHALL BE #12
AWG IN 3/4" CONDUIT.
8 PROVIDE CODE SIZE EQUIPMENT GROUND CONDUCTOR WITHIN
EACH LINE VOLTAGE CONDUIT.
POWER PLAN KEY NOTES:
11
6
8
9
10
m
16
m
18
19
POWER CONNECTION FOR UNDERCOUNTER DISHWASHER, MOYER
DEIBEL 351 HT WITH 70 DEGREE RISE BOOSTER, HARD WIRED, 40A
CIRCUIT. REFER TO PLUMBING SHEETS FOR ADDITIONAL INFORMATION.
PROVIDE 60A /2P NEMA 1 LOCKABLE DISCONNECT SWITCH
PROVIDE 40A SP TOGGLE SWITCH AND A DEDICATED
277V/10 CIRCUIT FOR INSTANTANEOUS WATER HEATER. FROM
WATER HEATER, CONCEAL THE CONDUIT IN THE WALL TO A
FLUSH J -BOX LOCATED NEAR THE WATER HEATER. PROVIDE
FLEXIBLE CONDUIT FOR FINAL CONNECTIONS FROM THE
J -BOX TO THE WATER HEATER. REFER TO PLUMBING SHEETS
FOR ADDITIONAL INFORMATION.
FROM THE WATER HEATER, CONCEAL THE CONDUIT IN THE WALL
TO A FLUSH J- BOX ( +66" AFF) LOCATED NEAR THE WATER
HEATER. PROVIDE FLEXIBLE CONDUIT FOR FINAL CONNECTIONS
FROM THE J -BOX TO THE WATER HEATER. REFER TO PLUMBING
SHEETS FOR ADDITIONAL INFORMATION. PROVIDE 30A /3P NEMA 1
LOCKABLE DISCONNECT SWITCH
PROVIDE 2 "X2" DOUBLE COMPARTMENT POWER POLE FROM ROOF
DECK TO COUNTERTOP WITH RECEPTACLE POWER, TELEPHONE,
AND DATA NETWORK CONNECTION. WIREMOLD CAT # 25DTP -415
COLOR: IVORY
PROVIDE (1) 4 "C.O. FOR TELE /DATA TO MPOE.
PROVIDE JUNCTION BOX FOR CONDENSATE HEATER.
COORDINATE EXACT LOCATION WITH COOLER MANUFACTURER,
OWNER AND ARCHITECT PRIOR TO ROUGH -IN. REFERENCE
SHEET E2.2 FOR LIGHTING INFORMATION.
PROVIDE POWER FOR DETEX LOCK.
PROVIDE CEILING MOUNTED RECEPTACLE AT JOIST HEIGHT.
COORDINATE EXACT LOCATION WITH ARCHITECT PRIOR TO
ROUGH -IN.
PROVIDE JUNCTION BOX MOUNTED ON WALL ABOVE DOOR
FOR AUTOMATIC SLIDING DOOR CONTROL. PROVIDE ALL
REQUIRED HARDWARE FOR A COMPLETE SYSTEM. VERIFY
EXACT REQUIREMENTS WITH MANUFACTURER PRIOR TO
ROUGH -IN.
PROVIDE WEATHERPROOF JUNCTION BOX AND DEDICATED
120V/10 CIRCUIT WITH PAD - LOCKABLE -OFF DISCONNECT
SWITCH MOUNTED ABOVE CEILING FOR FUTURE SIGNAGE.
COORDINATE EXACT LOCATION WITH OWNER AND ARCHITECT
PRIOR TO ROUGH -IN.
ROUTE CIRCUIT THROUGH CONTACTOR. REFER TO
PANELBOARD SCHEDULES ON SHEET E4.2 FOR CONTACTOR
DESIGNATIONS.
POWER FOR DOOR LIGHT.
PROVIDE 4'x8'x3 /4"THK PLYWOOD BKBD. AND 3/4 "C., 1#6
GRND. TO MAIN SERVICE GROUND.
ELECTRICAL CONTRACTOR TO VERIFY REQUIREMENTS OF
CUSTOMER SERVICE DESK MILLWORK PRIOR TO BID OF
ELECTRICAL DEVICES FOR CUSTOMER SERVICE DESK.
PROVIDE 30A, 120V., NEMA 5 -30R RECEPTACLE FOR
SERVER.
DELIVERY BUZZER SYSTEM: PROVIDE AND INSTALL BUZZER
SYSTEM AS DETAILED IN DELIVERY BUZZER SCHEMATIC 2,
THIS SHEET.
PROVIDE J -BOX FOR HARD WIRE CONNECTION TO 120V.
2.4KW HAND DRYER. MOUNT AT HEIGHT DIRECTED BY
ARCHITECT /OR GENERAL CONTRACTOR TO COMPLY WITH
LOCAL CURRENT, NEC AND ADA APPLICABLE CODES
REGULATIONS AND /OR AMENDED CITY CODES PROVIDE
(2) #10, (1) #10 CU. BOND 1/2"C.
PROVIDE FLUSH CEILING MOUNTED RECEPTACLE FOR
SHOW WINDOW. COORDINATE EXACT LOCATION WITH
ARCHITECT PRIOR TO ROUGH -IN.
ALL EMPTY 3/4" CONDUITS INSTALLED BY THE
ELECTRICAL CONTRACTOR FOR TELEPHONE AND DATA
SHALL BE LEFT WITH A PULL STRING IN PLACE.
20 PROVIDE RECEPTACLE MOUNTED IN WALK -IN AT CEILING.
PROVIDE DOUBLE THROW SWITCH AND CONNECT
EVAPORATOR, THERMOSTAT, SOLENOID, AND SWITCH PER
MANUFACTURER WIRING DIAGRAM. COORDINATE EXACT
LOCATION WITH OWNER AND ARCHITECT PRIOR TO
ROUGH -IN.
PROVIDE RECEPTACLE MOUNTED IN WALK -IN AT CEILING.
PROVIDE DOUBLE THROW SWITCH AND CONNECT
EVAPORATOR, THERMOSTAT, SOLENOID, SWITCH, AND
DEFROST CLOCK PER MANUFACTURER WIRING DIAGRAM.
COORDINATE . EXACT LOCATION WITH OWNER AND ARCHITECT
PRIOR TO ROUGH -IN.
PROVIDE POWER FOR RPPA HEAT. COORDINATE WITH
OWNER FOR ALL ELECTRICAL REQUIREMENTS
CONNECT TO
RECEPTACLE SHOWN
ON PLANS
DO NOT LOCATE ABOVE
CEILING PER NEC.
1 PUSHBUTTON, SEE FLOOR
PLAN FOR LOCATION.
EDWARDS #852
24V, SYSTEM
24V
SEC
SALES BUZZER AT
COUNT OFFICE,
EDWARDS #340- 4G5 -24VAC
120V TO 24V SYSTEM
TRANSFORMER IN NEMA 1
ENCLOSURE. EDWARDS #592
DELIVERY BUZZER SCHEMATIC
SCALE: NO SCALE
LL)O361
cm�iSAWx
APR 2 4 2012
PERMIT CENTER
ac
as
•
Aro
u
•
0
Ln
Uo
Z N
c C
o°i
Wain
o°i
N
U
5 L
ce
m Ln
re (3,' Ln
0 N 1-n
N
a a, O
0mko
1- W
w o0.
1L-
aw
0
0
N
1.111111 0 CO
N e-
a) ¢ m
N p bC 'L �
U c V1
to, OD
z • w
MEM C 5 rz. y
N
4) o z
8=
�
o v °c�
5c
I-O)
I-
w n
N
LAS VEGAS :: IRVINE :: PHOENIX :: SALT LAKE
Z �+
MOiggo Nf/l�Vjpp, pp Vj� 1
094.0 KWON
ZOg O 1=
gLamace 0V,2
gEiKomni2
°RZW =WZZ2*
14
0 03
•
3
iS
§R
1
STORE NUMBER
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE: El 1 POWER.DWG
oil II I Must.
.•%! p 'O' *,
kv..••F ' "
• CO : � Nii�'vs
:: :A. Air . . - -- iss
—1•
2 .u) Y . •
- O
• Z;
�1, A,„-... STE ..•� �∎��
, #ss /ON4l .E....
NWIlIBO O
SHEET NAME
ELECTRICAL POWER
PLAN
SHEET NUMBER:
E1.1
rd
re w4
ILO,
I�
P•A
P.474
P1
'7/
•
(7-12)-
(7()
t
J a
Rm
fl
CE
A -2
Era
X1
=MEI r-- i/
:�_
1
wr
SiklaIMUMMU7EN
r11-1 't14
._,. 1a
W'
■
rarandrarnsi
a
liaan
F.7".
H
A
ii
lignmadm
NL
F AE
A t4
II Ma
if
NL
AE
0 Mg
reArtwrp--ot__ 1,c,:ii
re#,AFTZVAr 11,--
PA
dr-
-
A
ii
lignmadm
NL
F AE
A t4
II Ma
if
NL
AE
0 Mg
reArtwrp--ot__ 1,c,:ii
re#,AFTZVAr 11,--
.-,',.:
t
-1
A.
AE
NL
ro— I-- T - -r -7i
_4
Pe"
.;`,64
ror.
r
i
SIN
.#1
�Ir
T 'i
411..‘k
AE
NL
13 15
Aiu
ryr
Artio
os
L
�HA -21
11
aI
wicral
i�
I
Ir
iffA
r �
10
Mt F
FI
I
r,„
re' A
400;�
-''
13 151
111Im IIIIIimlI IIIJIiIII1111 1
11111111111,7 : :p.;1.;:R� 5111
!!!!rn1tI 111111111111 11111111
1111111111111 I11111MMIIiiiiii nI.
11
1
X1
7
9
19
P o o
lHA 17
A
AE
NL
AE
NL
17
19
AE
NL
17
19
17
19 AE
NL
11
23
25
HA -577
utk
9i A 111
25
23
25
11
25
23
a'1
13 15 13 15
23
25
23
25
23
25
25
raw
jj- ow
Pr A
L
►H
4.
A
i
AE
NL
(E) T225 -1
(E) SB _
(E) LA
(E) LB
E) LP
{E) HA
(E) LE
D
a
El
31 33
23 23
25 25
AE
AE
NL
AE
NL
23
23
25 25
25
A +V
Ks
HA -31,3
CE
CE
-3/941
NL
1 X1 39
39
41
I
I�
s
39
41
S =S SE "' "_ S =' =S
33
4i
13 15 13 15
X
AE
X1
11
N
AE
I:
1 IIHA -35,37
x
%A A
a
r p
� ITO
A ea
Ir
op
Aim
0/
NL
F = = = =9
==
35
37
35
37
35
37
35
r - - - -1
6 =- _1 37
A
L
A
37
13 15
4
11
35
37
35
7
39 41
37
F = = = =9
35
37
35
37
r--- tr - --1
6____�
39 41
NL SE
39
/a
AE
NL
i-
1
3
3
I 39
35
37
AE
35
37
3
37
35
37
HA -13,15
ti
11
AE
NL
-1
13
15
HA -9,11
• NL
.� AE
11
NEN
39
S
39
S
41
S
39
s
41
•L
4
S
39
4
S
41
4
S
39
4
s
41
4
39
41
4
39
4
NL -SE
4
s
39
S
41
4
4
NL SE
39
4
39
4
NL SE
41
4.
39
C' Q 0
O
CE
= -.-
NL SE
39
___0
--1
s
41
S
39
4
4
X72)
ELECTRICAL LIGHTING PLAN
SCALE: 1 /8 " =1' -0"
II L►
•.1 1..
MM 1...
L..1 ,..t
„ , A'
.► 11
.. I►
REVIEWED FOR ,
COMPLIANCE WITH
City of Tukwila,
GENERAL NOTES:
1. COORDINATE EXACT LOCATION OF ALL FIXTURES WITH
ARCHITECTURAL RACK PLAN.
2. REFER TO SHEET E6.1 FOR LIGHT FIXTURE SCHEDULE.
3. OFFSET LIGHT FIXTURES AS NEEDED TO CLEAR STRUCTURE
BRIDGING ACROSS THE BUILDING.
4. KEEP ALL CONDUIT AS CLOSE TO WALLS AND AS HIGH TO
UNDERSIDE OF ROOF DECK AS POSSIBLE (NOT LESS THAN
38 MM (1-1/2" IN.) PER 2008 NEC 300.4(E)) FROM
THE NEAREST SURFACE OF THE ROOF DECKING, WITHIN
THE STEEL JOIST FRAMING.
5. COORDINATE ALL MOUNTING HEIGHTS OF ALL FIXTURES
WITH OWNER AND ARCHITECT PRIOR TO INSTALLATION.
6. CONTRACTOR TO CHALK OUT LOCATIONS OF SHELVING
FIXTURES TO ENSURE PROPER ALIGNMENT WITH LIGHTING
FIXTURES. REF. FIXTURE PLAN.
7. CONTRACTOR TO VERIFY LOCATIONS OF EXISTING GLU-LAM
BEAMS AND COORDINATE FIXTURE HEIGHTS WITH THEM.
RUN ALL ELECTRICAL SERVICE AND CONDUITS AGAINST
DEEPER GLU-LAMS WHERE POSSIBLE.
LIGHTING PLAN KEY NOTES:
LI NOT USED.
CONNECT EXISTING LIGHT FIXTURES IN MOP 107 TO NEW CIRCUIT AS
DESIGNATED.
ROUTE CIRCUIT THROUGH CONTACTOR. PROVIDE UNSWITCHED 'HOT' FOR
EMERGENCY, NIGHT LIGHT, AND LOCALLY CONTROLLED FIXTURES. REFER TO
PANELBOARD SCHEDULES ON SHEET E4.2 FOR CONTACTOR DESIGNATIONS.
COMBINED NIGHT LIGHT AND EMERGENCY FIXTURES: CONNECT THE
UNSWITCHED HOT TO BOTH THE NORMAL OPERATION BALLAST AND THE
EMERGENCY BACKUP BALLAST. DO NOT SWITCH.
EL 1)-43
crrifIBMWIIA
APR 2 4 2012
PERMIT CENTER
•
1.
0
0
o
o • tit)
0
0
Loll 'ba-
t113
8
co
0 al
0 ix
CO
LAS VEGAS :: IRVINE :: PHOENIX :: SALT LAKE
x04..eio
0.wo,. .wtg
clo
gt
•
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE: E21 LIGHTING.DWG
011111/11/8/
-.0 ,....--_-- ,
�� kk5"• O -Ottog 'fir•
,' J. �, — „ ''•"ti':
r
•�� ,` •
.U) �•
.. • al
• •
IlD Z
• •
'• F6 ••.•••••• \Cc' ` STE s•
SHEET NAME:
ELECTRICAL GENERAL
LIGHTING PLAN
SHEET NUMBER:
E2.1
0
WW
CI B B g
WW
B B B
TYP
3
D O ]
t7
(E) T225 -1
=(E) SB.
(E) LA
(E) LB ji
C
1F E) L
(E) H
(E) L�
D
ArA
Arid
A/A
A A
rr
= = = =9
-1
ZirrtArAr A
B B B SIB
B B B B
WW
G
W
LA
20
F = = y
•
B
_� 5
AI�IIII!!1®f.wws �iy�.
BD
Adr.,,'"1",,,i
vv
B B B
T
1111111N 111111111111111111111
111111111111111111111111111111111111
0
0
O
0
__ =_=
1
F = = ==
r===.=
= = ==
___
ELECTRICAL LIGHTING PLAN
SCALE: 1 /8" =1' —O"
•1 1•
JI.1 1.\
MM MM 1...
,..'
,,
I. ..
•• ..
REVIENNED FOR WITH
COMPLIANCE EC
NFPA70
MAC 0g 2012
City of Tutotida
BUILDING DIVISIO
GENERAL NOTES:
COORDINATE EXACT LOCATION OF ALL FIXTURES WITH
ARCHITECTURAL RACK PLAN.
2. REFER TO SHEET E4.1 FOR LIGHT FIXTURE SCHEDULE.
3. OFFSET LIGHT FIXTURES AS NEEDED TO CLEAR STRUCTURE
BRIDGING ACROSS THE BUILDING.
4. KEEP ALL CONDUIT AS CLOSE TO WALLS AND AS HIGH TO
UNDERSIDE OF ROOF DECK AS POSSIBLE (NOT LESS THAN
38 MM (1 -1/2" IN.) PER 2008 NEC 300.4(E)) FROM
THE NEAREST SURFACE OF THE ROOF DECKING, WITHIN
THE STEEL JOIST FRAMING.
5. COORDINATE ALL MOUNTING HEIGHTS OF ALL FIXTURES
WITH OWNER AND ARCHITECT PRIOR TO INSTALLATION.
LIGHTING PLAN KEY NOTES:
11
0
PROVIDE LIGHTING CONTACTOR SWITCHES, S1, S2, S3, AND S4.
SWITCH S1 SHALL CONTROL CONTACTOR C1 FOR 50% OF SALES
FLOOR LIGHTS, 50% OF STOCKROOM LIGHTS, WALK IN BEER COOLER,
FINE WINE COOLER, HUMIDOR, AND CLASSROOM. SWITCH S2 SHALL
CONTROL CONTACTOR C2 FOR 50% OF SALES FLOOR LIGHTS AND
50% OF STOCKROOM LIGHTS. SWITCH S3 SHALL CONTROL CONTACTOR
C3 FOR SALES FLOOR TRACK DISPLAY LIGHTING AND CHECKOUT
TRACK LIGHTING. SWITCH S4 SHALL CONTROL CONTACTOR C4 FOR
GONDOLA DISPLAY LIGHTING AND CLIMATE CONTROLLED BOX
REACH -IN DOOR LIGHTS. SWITCHES SHALL BE LOCATED AT CUSTOMER
SERVICE DESK. COORDINATE EXACT LOCATION AND OPERATION WITH
OWNER AND ARCHITECT PRIOR TO ROUGH -IN.
PROVIDE JUNCTION BOX MOUNTED IN HUMIDOR ABOVE
SHELVING 96" AFF FOR HUMIDOR LIGHTING. COORDINATE EXACT
REQUIREMENTS FROM MANUFACTURER PRIOR TO ROUGH -IN.
ROUTE CIRCUIT THROUGH CONTACTOR. REFER TO PANELBOARD
SCHEDULES ON SHEET E4.2 FOR CONTACTOR DESIGNATIONS.
TYPE 'FL' LIGHTING FIXTURE 120V SINGLE TUBE ELECTRONIC
FLUORESCENT CHANNEL MOUNTED ON FULL LENGTH OF STORE
FIXTURES.
MC CABLE, LENGTH
AS REQUIRED, NOT
LONGER THAN 10' -0"
STEEL JOIST
MOUNTING ROD,
DIAMETER AS
REQUIRED PER MFMA
GUIDELINES FOR THE
USE OF METAL
FRAMING. PAINT
SAME AS CEILING.
REFER TO LIGHT FIXTURE
SCHEDULE AND ARCHITECT'S
PLANS FOR MOUNTING HIEGHT AND
OTHER INFORMATION CONCERNING
TRACK LIGHTING FIXTURES.
GRAPHICAL REPRESENTATIONS OF
VARIOUS TRACK FIXTURES MOUNTED ON
OR HUNG BELOW TRACK. REFERENCE
LIGHTING PLAN FOR SPECIFIC FIXTURE
TYPES.
UNI -STRUT AS REQUIRED,
PAINTED SAME AS CEILING,
COORDINATE WITH TENANT
REQUIREMENTS & ARCH PLANS
HALO TRACK SYSTEM OPTIONS.
REFER TO LIGHT FIXTURE SCHEDULE
AND ARCHITECT'S PLANS FOR MOUNTING
HEIGHTS AND REQUIREMENTS.
GENERIC TRACK LIGHTING MOUNTING DETAIL
FOR "B" FIXTURES
NO SCALE
\ MC CABLE, LENGTH
`� AS REQUIRED, NOT
LONGER THAN 10' -0"
BOTTOM OF TRELLIS
AT 10' -0" AFF
2' -0" 1 2' -0"
r
BOTTOM OF FIXTURE 'P' AT 7' -0" AFF AT
CHECK -OUT. G.C. & E.C. COORDINATE WITH
STRUCTURAL FIELD CONDITIONS AND CEILING
TRELLIS AS REQUIRED. REFER TO LIGHTING
FIXTURE PLAN /SCHEDULE FOR MORE
INFORMATION.
TRELLIS HUNG FROM
STRUCT. BY G.C.
UNI -STRUT AS REQUIRED,
PAINTED SAME AS CEILING,
COORDINATE WITH TENANT
REQUIREMENTS & ARCH PLANS
JOIST
MOUNTING ROD, DIAMETER AS REQUIRED
PER MFMA GUIDELINES FOR THE USE OF
METAL FRAMING. PAINT SAME AS CEILING.
UNI -STRUT AS REQUIRED
HALO TRACK SYSTEM
VERIFY ALL DIMENSIONS WITH
APPROVED LIGHTING PLAN AND
FIELD CONDITIONS
MOUNTING DETAIL FOR 'P' FIXTURES
COORDINATE WITH APPROVED LIGHTING PLAN
POSITIONING DETAIL FOR 'P' FIXTURES OVER CHECKOUTS
NO SCALE: COORDINATE WITH APPROVED LIGHTING PLAN
MC CABLE, LENGTH
AS REQUIRED, NOT
LONGER THAN 10' -0"
STEEL JOIST
MOUNTING ROD,
DIAMETER AS
REQUIRED PER MFMA
GUIDELINES FOR THE
USE OF METAL
FRAMING. PAINT
SAME AS CEILING.
REFER TO LIGHT FIXTURE
SCHEDULE AND ARCHITECT'S
PLANS FOR MOUNTING HIEGHT AND
OTHER INFORMATION CONCERNING
TRACK LIGHTING FIXTURES.
GRAPHICAL REPRESENTATIONS OF
VARIOUS TRACK FIXTURES MOUNTED ON
OR HUNG BELOW TRACK. REFERENCE
LIGHTING PLAN FOR SPECIFIC FIXTURE
TYPES.
UNI -STRUT AS REQUIRED,
PAINTED SAME AS CEILING,
COORDINATE WITH TENANT
REQUIREMENTS & ARCH PLANS
HALO TRACK SYSTEM OPTIONS.
REFER TO LIGHT FIXTURE SCHEDULE
AND ARCHITECT'S PLANS FOR MOUNTING
HEIGHTS AND REQUIREMENTS.
GENERIC TRACK LIGHTING MOUNTING DETAIL
FOR FIXTURES
NO SCALE
LI. -o38 i
CITY OFTUK'MLA
APR 242012
PERMIT CENTER
as
•
a.
•
to
0
0
U
Z Q
W E
12 o a'
wa.uai
I- o
rn
U m o
a 113 ,X
W 5Li
N
cv
0 T2 0
O U in
U EL
w 0O'
u_ o
0m`D
Gw
m
w o0
1
Ce
aw
0
0
N
N
8
ce
CO
CNIr.
¢ rt.
Z
0 0)
X00
Q q
Vow
0
z�w
z
a)z
N
UJ X
--0CD
5•�
CO
W n
N
LAS VEGAS :: IRVINE :: PHOENIX :: SALT LAKE
::z 4j0°p tagtN@Ce
hiceomni20
06
MEM
fts
*NA
1
STORE NUMBER:
sca
ISSUE BLOCK
B B B SIB
B B B B
WW
G
W
LA
20
F = = y
•
B
_� 5
AI�IIII!!1®f.wws �iy�.
BD
Adr.,,'"1",,,i
vv
B B B
T
1111111N 111111111111111111111
111111111111111111111111111111111111
0
0
O
0
__ =_=
1
F = = ==
r===.=
= = ==
___
ELECTRICAL LIGHTING PLAN
SCALE: 1 /8" =1' —O"
•1 1•
JI.1 1.\
MM MM 1...
,..'
,,
I. ..
•• ..
REVIENNED FOR WITH
COMPLIANCE EC
NFPA70
MAC 0g 2012
City of Tutotida
BUILDING DIVISIO
GENERAL NOTES:
COORDINATE EXACT LOCATION OF ALL FIXTURES WITH
ARCHITECTURAL RACK PLAN.
2. REFER TO SHEET E4.1 FOR LIGHT FIXTURE SCHEDULE.
3. OFFSET LIGHT FIXTURES AS NEEDED TO CLEAR STRUCTURE
BRIDGING ACROSS THE BUILDING.
4. KEEP ALL CONDUIT AS CLOSE TO WALLS AND AS HIGH TO
UNDERSIDE OF ROOF DECK AS POSSIBLE (NOT LESS THAN
38 MM (1 -1/2" IN.) PER 2008 NEC 300.4(E)) FROM
THE NEAREST SURFACE OF THE ROOF DECKING, WITHIN
THE STEEL JOIST FRAMING.
5. COORDINATE ALL MOUNTING HEIGHTS OF ALL FIXTURES
WITH OWNER AND ARCHITECT PRIOR TO INSTALLATION.
LIGHTING PLAN KEY NOTES:
11
0
PROVIDE LIGHTING CONTACTOR SWITCHES, S1, S2, S3, AND S4.
SWITCH S1 SHALL CONTROL CONTACTOR C1 FOR 50% OF SALES
FLOOR LIGHTS, 50% OF STOCKROOM LIGHTS, WALK IN BEER COOLER,
FINE WINE COOLER, HUMIDOR, AND CLASSROOM. SWITCH S2 SHALL
CONTROL CONTACTOR C2 FOR 50% OF SALES FLOOR LIGHTS AND
50% OF STOCKROOM LIGHTS. SWITCH S3 SHALL CONTROL CONTACTOR
C3 FOR SALES FLOOR TRACK DISPLAY LIGHTING AND CHECKOUT
TRACK LIGHTING. SWITCH S4 SHALL CONTROL CONTACTOR C4 FOR
GONDOLA DISPLAY LIGHTING AND CLIMATE CONTROLLED BOX
REACH -IN DOOR LIGHTS. SWITCHES SHALL BE LOCATED AT CUSTOMER
SERVICE DESK. COORDINATE EXACT LOCATION AND OPERATION WITH
OWNER AND ARCHITECT PRIOR TO ROUGH -IN.
PROVIDE JUNCTION BOX MOUNTED IN HUMIDOR ABOVE
SHELVING 96" AFF FOR HUMIDOR LIGHTING. COORDINATE EXACT
REQUIREMENTS FROM MANUFACTURER PRIOR TO ROUGH -IN.
ROUTE CIRCUIT THROUGH CONTACTOR. REFER TO PANELBOARD
SCHEDULES ON SHEET E4.2 FOR CONTACTOR DESIGNATIONS.
TYPE 'FL' LIGHTING FIXTURE 120V SINGLE TUBE ELECTRONIC
FLUORESCENT CHANNEL MOUNTED ON FULL LENGTH OF STORE
FIXTURES.
MC CABLE, LENGTH
AS REQUIRED, NOT
LONGER THAN 10' -0"
STEEL JOIST
MOUNTING ROD,
DIAMETER AS
REQUIRED PER MFMA
GUIDELINES FOR THE
USE OF METAL
FRAMING. PAINT
SAME AS CEILING.
REFER TO LIGHT FIXTURE
SCHEDULE AND ARCHITECT'S
PLANS FOR MOUNTING HIEGHT AND
OTHER INFORMATION CONCERNING
TRACK LIGHTING FIXTURES.
GRAPHICAL REPRESENTATIONS OF
VARIOUS TRACK FIXTURES MOUNTED ON
OR HUNG BELOW TRACK. REFERENCE
LIGHTING PLAN FOR SPECIFIC FIXTURE
TYPES.
UNI -STRUT AS REQUIRED,
PAINTED SAME AS CEILING,
COORDINATE WITH TENANT
REQUIREMENTS & ARCH PLANS
HALO TRACK SYSTEM OPTIONS.
REFER TO LIGHT FIXTURE SCHEDULE
AND ARCHITECT'S PLANS FOR MOUNTING
HEIGHTS AND REQUIREMENTS.
GENERIC TRACK LIGHTING MOUNTING DETAIL
FOR "B" FIXTURES
NO SCALE
\ MC CABLE, LENGTH
`� AS REQUIRED, NOT
LONGER THAN 10' -0"
BOTTOM OF TRELLIS
AT 10' -0" AFF
2' -0" 1 2' -0"
r
BOTTOM OF FIXTURE 'P' AT 7' -0" AFF AT
CHECK -OUT. G.C. & E.C. COORDINATE WITH
STRUCTURAL FIELD CONDITIONS AND CEILING
TRELLIS AS REQUIRED. REFER TO LIGHTING
FIXTURE PLAN /SCHEDULE FOR MORE
INFORMATION.
TRELLIS HUNG FROM
STRUCT. BY G.C.
UNI -STRUT AS REQUIRED,
PAINTED SAME AS CEILING,
COORDINATE WITH TENANT
REQUIREMENTS & ARCH PLANS
JOIST
MOUNTING ROD, DIAMETER AS REQUIRED
PER MFMA GUIDELINES FOR THE USE OF
METAL FRAMING. PAINT SAME AS CEILING.
UNI -STRUT AS REQUIRED
HALO TRACK SYSTEM
VERIFY ALL DIMENSIONS WITH
APPROVED LIGHTING PLAN AND
FIELD CONDITIONS
MOUNTING DETAIL FOR 'P' FIXTURES
COORDINATE WITH APPROVED LIGHTING PLAN
POSITIONING DETAIL FOR 'P' FIXTURES OVER CHECKOUTS
NO SCALE: COORDINATE WITH APPROVED LIGHTING PLAN
MC CABLE, LENGTH
AS REQUIRED, NOT
LONGER THAN 10' -0"
STEEL JOIST
MOUNTING ROD,
DIAMETER AS
REQUIRED PER MFMA
GUIDELINES FOR THE
USE OF METAL
FRAMING. PAINT
SAME AS CEILING.
REFER TO LIGHT FIXTURE
SCHEDULE AND ARCHITECT'S
PLANS FOR MOUNTING HIEGHT AND
OTHER INFORMATION CONCERNING
TRACK LIGHTING FIXTURES.
GRAPHICAL REPRESENTATIONS OF
VARIOUS TRACK FIXTURES MOUNTED ON
OR HUNG BELOW TRACK. REFERENCE
LIGHTING PLAN FOR SPECIFIC FIXTURE
TYPES.
UNI -STRUT AS REQUIRED,
PAINTED SAME AS CEILING,
COORDINATE WITH TENANT
REQUIREMENTS & ARCH PLANS
HALO TRACK SYSTEM OPTIONS.
REFER TO LIGHT FIXTURE SCHEDULE
AND ARCHITECT'S PLANS FOR MOUNTING
HEIGHTS AND REQUIREMENTS.
GENERIC TRACK LIGHTING MOUNTING DETAIL
FOR FIXTURES
NO SCALE
LI. -o38 i
CITY OFTUK'MLA
APR 242012
PERMIT CENTER
as
•
a.
•
to
0
0
U
Z Q
W E
12 o a'
wa.uai
I- o
rn
U m o
a 113 ,X
W 5Li
N
cv
0 T2 0
O U in
U EL
w 0O'
u_ o
0m`D
Gw
m
w o0
1
Ce
aw
0
0
N
N
8
ce
CO
CNIr.
¢ rt.
Z
0 0)
X00
Q q
Vow
0
z�w
z
a)z
N
UJ X
--0CD
5•�
CO
W n
N
LAS VEGAS :: IRVINE :: PHOENIX :: SALT LAKE
::z 4j0°p tagtN@Ce
hiceomni20
06
MEM
fts
*NA
1
STORE NUMBER:
sca
ISSUE BLOCK
vv
B B B
T
1111111N 111111111111111111111
111111111111111111111111111111111111
0
0
O
0
__ =_=
1
F = = ==
r===.=
= = ==
___
ELECTRICAL LIGHTING PLAN
SCALE: 1 /8" =1' —O"
•1 1•
JI.1 1.\
MM MM 1...
,..'
,,
I. ..
•• ..
REVIENNED FOR WITH
COMPLIANCE EC
NFPA70
MAC 0g 2012
City of Tutotida
BUILDING DIVISIO
GENERAL NOTES:
COORDINATE EXACT LOCATION OF ALL FIXTURES WITH
ARCHITECTURAL RACK PLAN.
2. REFER TO SHEET E4.1 FOR LIGHT FIXTURE SCHEDULE.
3. OFFSET LIGHT FIXTURES AS NEEDED TO CLEAR STRUCTURE
BRIDGING ACROSS THE BUILDING.
4. KEEP ALL CONDUIT AS CLOSE TO WALLS AND AS HIGH TO
UNDERSIDE OF ROOF DECK AS POSSIBLE (NOT LESS THAN
38 MM (1 -1/2" IN.) PER 2008 NEC 300.4(E)) FROM
THE NEAREST SURFACE OF THE ROOF DECKING, WITHIN
THE STEEL JOIST FRAMING.
5. COORDINATE ALL MOUNTING HEIGHTS OF ALL FIXTURES
WITH OWNER AND ARCHITECT PRIOR TO INSTALLATION.
LIGHTING PLAN KEY NOTES:
11
0
PROVIDE LIGHTING CONTACTOR SWITCHES, S1, S2, S3, AND S4.
SWITCH S1 SHALL CONTROL CONTACTOR C1 FOR 50% OF SALES
FLOOR LIGHTS, 50% OF STOCKROOM LIGHTS, WALK IN BEER COOLER,
FINE WINE COOLER, HUMIDOR, AND CLASSROOM. SWITCH S2 SHALL
CONTROL CONTACTOR C2 FOR 50% OF SALES FLOOR LIGHTS AND
50% OF STOCKROOM LIGHTS. SWITCH S3 SHALL CONTROL CONTACTOR
C3 FOR SALES FLOOR TRACK DISPLAY LIGHTING AND CHECKOUT
TRACK LIGHTING. SWITCH S4 SHALL CONTROL CONTACTOR C4 FOR
GONDOLA DISPLAY LIGHTING AND CLIMATE CONTROLLED BOX
REACH -IN DOOR LIGHTS. SWITCHES SHALL BE LOCATED AT CUSTOMER
SERVICE DESK. COORDINATE EXACT LOCATION AND OPERATION WITH
OWNER AND ARCHITECT PRIOR TO ROUGH -IN.
PROVIDE JUNCTION BOX MOUNTED IN HUMIDOR ABOVE
SHELVING 96" AFF FOR HUMIDOR LIGHTING. COORDINATE EXACT
REQUIREMENTS FROM MANUFACTURER PRIOR TO ROUGH -IN.
ROUTE CIRCUIT THROUGH CONTACTOR. REFER TO PANELBOARD
SCHEDULES ON SHEET E4.2 FOR CONTACTOR DESIGNATIONS.
TYPE 'FL' LIGHTING FIXTURE 120V SINGLE TUBE ELECTRONIC
FLUORESCENT CHANNEL MOUNTED ON FULL LENGTH OF STORE
FIXTURES.
MC CABLE, LENGTH
AS REQUIRED, NOT
LONGER THAN 10' -0"
STEEL JOIST
MOUNTING ROD,
DIAMETER AS
REQUIRED PER MFMA
GUIDELINES FOR THE
USE OF METAL
FRAMING. PAINT
SAME AS CEILING.
REFER TO LIGHT FIXTURE
SCHEDULE AND ARCHITECT'S
PLANS FOR MOUNTING HIEGHT AND
OTHER INFORMATION CONCERNING
TRACK LIGHTING FIXTURES.
GRAPHICAL REPRESENTATIONS OF
VARIOUS TRACK FIXTURES MOUNTED ON
OR HUNG BELOW TRACK. REFERENCE
LIGHTING PLAN FOR SPECIFIC FIXTURE
TYPES.
UNI -STRUT AS REQUIRED,
PAINTED SAME AS CEILING,
COORDINATE WITH TENANT
REQUIREMENTS & ARCH PLANS
HALO TRACK SYSTEM OPTIONS.
REFER TO LIGHT FIXTURE SCHEDULE
AND ARCHITECT'S PLANS FOR MOUNTING
HEIGHTS AND REQUIREMENTS.
GENERIC TRACK LIGHTING MOUNTING DETAIL
FOR "B" FIXTURES
NO SCALE
\ MC CABLE, LENGTH
`� AS REQUIRED, NOT
LONGER THAN 10' -0"
BOTTOM OF TRELLIS
AT 10' -0" AFF
2' -0" 1 2' -0"
r
BOTTOM OF FIXTURE 'P' AT 7' -0" AFF AT
CHECK -OUT. G.C. & E.C. COORDINATE WITH
STRUCTURAL FIELD CONDITIONS AND CEILING
TRELLIS AS REQUIRED. REFER TO LIGHTING
FIXTURE PLAN /SCHEDULE FOR MORE
INFORMATION.
TRELLIS HUNG FROM
STRUCT. BY G.C.
UNI -STRUT AS REQUIRED,
PAINTED SAME AS CEILING,
COORDINATE WITH TENANT
REQUIREMENTS & ARCH PLANS
JOIST
MOUNTING ROD, DIAMETER AS REQUIRED
PER MFMA GUIDELINES FOR THE USE OF
METAL FRAMING. PAINT SAME AS CEILING.
UNI -STRUT AS REQUIRED
HALO TRACK SYSTEM
VERIFY ALL DIMENSIONS WITH
APPROVED LIGHTING PLAN AND
FIELD CONDITIONS
MOUNTING DETAIL FOR 'P' FIXTURES
COORDINATE WITH APPROVED LIGHTING PLAN
POSITIONING DETAIL FOR 'P' FIXTURES OVER CHECKOUTS
NO SCALE: COORDINATE WITH APPROVED LIGHTING PLAN
MC CABLE, LENGTH
AS REQUIRED, NOT
LONGER THAN 10' -0"
STEEL JOIST
MOUNTING ROD,
DIAMETER AS
REQUIRED PER MFMA
GUIDELINES FOR THE
USE OF METAL
FRAMING. PAINT
SAME AS CEILING.
REFER TO LIGHT FIXTURE
SCHEDULE AND ARCHITECT'S
PLANS FOR MOUNTING HIEGHT AND
OTHER INFORMATION CONCERNING
TRACK LIGHTING FIXTURES.
GRAPHICAL REPRESENTATIONS OF
VARIOUS TRACK FIXTURES MOUNTED ON
OR HUNG BELOW TRACK. REFERENCE
LIGHTING PLAN FOR SPECIFIC FIXTURE
TYPES.
UNI -STRUT AS REQUIRED,
PAINTED SAME AS CEILING,
COORDINATE WITH TENANT
REQUIREMENTS & ARCH PLANS
HALO TRACK SYSTEM OPTIONS.
REFER TO LIGHT FIXTURE SCHEDULE
AND ARCHITECT'S PLANS FOR MOUNTING
HEIGHTS AND REQUIREMENTS.
GENERIC TRACK LIGHTING MOUNTING DETAIL
FOR FIXTURES
NO SCALE
LI. -o38 i
CITY OFTUK'MLA
APR 242012
PERMIT CENTER
as
•
a.
•
to
0
0
U
Z Q
W E
12 o a'
wa.uai
I- o
rn
U m o
a 113 ,X
W 5Li
N
cv
0 T2 0
O U in
U EL
w 0O'
u_ o
0m`D
Gw
m
w o0
1
Ce
aw
0
0
N
N
8
ce
CO
CNIr.
¢ rt.
Z
0 0)
X00
Q q
Vow
0
z�w
z
a)z
N
UJ X
--0CD
5•�
CO
W n
N
LAS VEGAS :: IRVINE :: PHOENIX :: SALT LAKE
::z 4j0°p tagtN@Ce
hiceomni20
06
MEM
fts
*NA
1
STORE NUMBER:
sca
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: Th/RO /SJ
DRAWN BY: RRR
FILE:
luaus
•cf) ! 0•
ii 113- tri 2:
:'• A• •r /sTEC • /;,•
. ••
SHEET NAME
ELECTRICAL DISPLAY
LIGHTING PLAN
SHEET NUMBER:
E2.2
(91
7
0
C}
arm a
_11.x_
(E) CA
P2 -1
(E) T225 -1
(E) SB
(E) LA
(E) LB
E) LP L-
(E) H�4
(E) LE
= = = ==
E LD
PROVIDE 60A /3P, NEMA 3R
DISCONNECT SWITCH FUSED
PER MANUFACTURER'S
RECOMMENDATIONS
= = =
n
I
I
's i
RTU
8
ON ROOF
(E)
ON ROOF
F_ __ rj LA x=
i
(E CA- 1-20,22,24; (E)
n
PROVIDE 6OA /3FH, NEVIA 3R
= = == DISCONNECF=SWtT zFUSED
PER MAN UFACTU,II�ER'.
RECOMMENDATIONS
(E)
ROOF
LA-47
�P, RT 8/9
x = —v
ON ROOF'
LC
(E) CA- 26,28,30
19
(E
ON ROOF
RTIJ
(E
6
ON ROOF
x ==
25
LC
====
= = = =�
ON ROOF - (E)
(E) CA- 13,15,17
(E)
(E)
(E) CA- 14,16,18
(E) CA- 19,21,23
- -ir - -y
6 = = =_J
(Th
PROVIDE 30A /2P, NEMA 3R
DISCONNECT SWITCH FUSED
PER MANUFACTURER'S
RECOMMENDATIONS
(C4U)
fl'
LC
0 22
LA -27
PART
ON ROOF
0 0 J •
(E) CA -2,4,6
PROVIDE 30A /3P, NEMA 3R
DISCONNECT SWITCH FUSED
PER MANUFACTURER'S
,331 LC RECOMMENDATIONS
ON ROOF
(E)
(E) CA- 7,9,11
ON ROOF
a
8.29
0
1
•
(E) CA- 8,10,12
1
====
== ==
= = =
= = =
= = =. ==
r
==I
-. = =z
PROVIDE 30A /1P NEMA 3R
DISC NNECT SWITCH FUSED
-LC PER MANUFACTURER'S
11 ' RECO MENDATIONS
ON ROOF
0
0
HVAC PO ER PLAN
SCALE: 1/8"=V-0"
' -0"
M )\
I.) 1.\
,.., MW
).., )..)
,, , ,,
.■ AI
\\ AV
1
RE PL A FOR
FPA
70 NEC
MAY 092012
City o Tukwila .
BUILDING DIVISION
■
HVAC /PLUMBING EQUIPMENT GENERAL NOTES:
1. FUSE TYPES SHALL BE PROVIDED PER ELECTRICAL
SPECIFICATIONS.
2. ALL ROOF PENETRATIONS AND REPAIRS SHALL BE DONE BY
LANDLORD'S ROOFING CONTRACTOR TO MAINTAIN
ROOFING WARRANTIES.
3. REFER TO MECHANICAL DRAWINGS FOR MORE
INFORMATION.
4. ALL ELECTRICAL DEVICE OUTSIDE OF BUILDING SHALL BE
RATED NEMA 3R.
5. VERIFY ELECTRICAL REQUIREMENTS WITH MECHANICAL DESIGN.
6. PROVIDE G.F.I. RECEPTACLE AT EACH NEW ROOF TOP UNIT.
HVAC PLAN KEY NOTES:
I ' 1 EXHAUST FAN TO BE CONTROLLED BY ROOM LIGHT SWITCH VIA
277/120 VOLT RELAY.
ELI./-0 4381
WW W6
I LA
APR 242012
PERMIT CENTER
as
0
U0
W co
Usrn
warn
o
rn
U M o
Q y X
w 7 LL
ac
672
O U• NLO
UJ • 0°'
N
aL o
omtD
w
w go
I
cc aw
0
0
N
co
N
O)
g N.
LI
coo
U
Vocc
z0
z w
z
ca5
rnz
N w H
S
F- o
D:3 re
W N-
z
a
LAS VEGAS :: IRVINE : PHOENIX :: SALT LAKE
W ON E
,,4*E0)54
egulatio 741
CD la- 0 ge 211
ZOMejo
4141181°
UZy WZZ��
m
•
m
z
it
m
2
a
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE: E31 HVAC POWER.DWG
• •u' '` 0: •
ow
••• "z9/0.. ..........
4444/moii0111°
SHEET NAME
HVAC POWER
PLAN
SHEET NUMBER:
E3.1
TO EXISTING METERED
SERVICE DISTRIBUTION'
15C = 14.&K4
VD = 0.50
PANEL
CA
(E)
ISC = 13KA
VD = 0.5%
4NEL
1-{4
(E)-
(E)
600 AMP
TENANT SERVICE PANEL
• 450'1/211V 30 4W
22 KAIC
15C = 1.8K4
(E)
225KVA
XFMR T225-1
480V PRI
208`'1120V SEC
(E)
8OO4MP
DISTRIBUTION BOARD SB (NEMA 1)
20517120V 30 4W
10 KAIC
ONE -LINE GENERAL NOTES:
1. THE DESIGN PROFESSIONAL HAS PERFORMED ALL REQUIRED SHORT CIRCUIT
CALCULATIONS AND THE AIC RATING INDICATED FOR EACH DEVICE IS ADEQUATE TO
PROTECT THE EQUIPMENT AND THE ELECTRICAL SYSTEM.
2. THE DESIGN PROFESSIONAL HAS PERFORMED ALL REQUIRED VOLTAGE DROP
CALCULATIONS AND ALL BRANCH CIRCUITS AND FEEDERS COMPLY WITH NEC 210 -19(A)
FPN NO. 4.
3. EACH SERVICE DISCONNECTING MEANS SHALL BE PERMANENTLY MARKED WITH A 1
FOOT SQUARE YELLOW SIGN WITH 1" HIGH X 1/4" STROKE BLACK LETTERING OR
NUMBERS AS REQUIRED BY CODE AND THE AUTHORITY HAVING JURISDICTION.
4. FAULT CURRENT CALCULATIONS ASSUME UTILITY PROVIDED 750KVA UTILITY
TRANSFORMER WITH 17021A OF AVAILABLE FAULT CURRENT LOCATED A MINIMUM OF
30 FEET FROM MAIN SWITCHBOARD. REFER TO POWER UTILITY DRAWINGS FOR EXACT
SIZE AND LOCATION. NOTIFY ENGINEER IN WRITING IF TRANSFORMER SIZE IS
INCREASED OR DISTANCE IS DECREASED.
ONE -LINE KEY NOTES:
C PANEL SHALL BE ABANDONED IN PLACE FOR THIS SCOPE OF WORK.
NO LOAD SHALL BE CONNECTED AT THIS TIME.
L
ISC = 6.1K4
VD = 02%a \
(E)
IOO4
3P
PANEL
LA
(E
LOAD CALCULATION - EXISTING PANEL 'CA'
ISC = 6.1K4 \
VD = 02% \
PANEL
LB
()
ISC = 13K4
VD _ 0 a
(F)
2504
J 3P
PANEL
LC
(E)
SC = 13KA
VD = 0.1%
-\\2.50/4
13P
PANEL
LD
0
(F)
DATE: 4/3/2012 SERVICE VOLTAGE:
PROJECT: MN120321 PHASE & WIRE:
SERVICE DESIGNATION: CP EXISTING SERVICE SIZE
CALCULATION BY: JRF KVA AVAILABE:
(AMPS):
TOTAL
LOAD (VA)
480Y/211V
30,4W
600
499
LOAD
DESCRIPTION
PANEL
NAME
DEMAND
FACTOR
TOTAL
DEMAND (VA)
EXISTING MECHANICAL
(E) RTU -1
21,300
1.00
21,300
EXISTING MECHANICAL
(E) RTU -2
21,300
1.00
21,300
EXISTING MECHANICAL
(E) RTU -3
21,300
1.00
21,300
EXISTING MECHANICAL
(E) RTU -4
21,300
1.00
21,300
EXISTING MECHANICAL
(E) RTU -5
21,300
1.00
21,300
EXISTING MECHANICAL
(E) RTU -6
21,300
1.00
21,300
EXISTING MECHANICAL
(E) RTU -1
12,180
1.00
12,180
EXISTING MECHANICAL
(E) RTU -S
21,300
1D0
21,300
EXISTING PANEL
PANEL "WA"
44,413
1.00
44,413
EXISTING DIST.
DISTRIBUTION PANEL "SIB"
86,591
1.00
86,591
LARGEST MOTOR
(E) RTU -1
21,300
025
5,325
TIMED
TOTAL DEMAND LOAD 2983 KVA 3588 A
REMAINING LOAD 200.6 KVA 241.2 A
NOTES:
EXISTING SWITCHBOARD IS ADEQUATE
1SC = 6.1K4
VD = 02%
(E)
1004
3P
PANEL
LE
n
(F)
(E)
1104
J 3P
ISC = 62KA
VD = 02%
PANEL
LP
0
(F)
REVIEWED FOR
COMPLIANCE WITH
NFPA 70 -NEC
MAY 0 9 2012
City of Tukwila
BUILDING DIVISION
ONE -LINE DIAGRAM
NO SCALE
A WARNING
Arc Flash Hazard.
Appropriate PPE Required.
Failure To Comply Can Result in Death or Injury.
Refer to NFPA 70 E.
NOTES:
A. ALL PANELBOARDS SHALL HAVE A COMMERCIALLY
PRODUCED PERMANENT LABEL APPLIED, SIMILAR TO THE
ABOVE, TO WARN OF POTENTIAL ARC FLASH HAZARDS, IN
ACCORDANCE WITH NEC 110.16 AND NFPA 70E.
B. LABELING MAY BE COMPLETED BY EQUIPMENT
MANUFACTURER, EQUIPMENT VENDOR /SUPPLIER, OR THE
CONTRACTOR. THE CONTRACTOR SHALL VERIFY THAT ALL
NEW PANELBOARDS ARE PROPERLY LABELED IN THE FIELD.
ARC FLASH DETAIL
NO SCALE
LIGHTING CONTACTOR SCHEDULE
CONTACTOR
NUMBER
I
PERMIT SET
CONTACTOR
NT
CONTROL CIRCUIT
NAMEPLATE DESCRIPTION
AMPS
POLES
VOLTS
CIRCUIT NO.
VOLTS
VIA
CONTROL
CONTACTOR CABINET
C1
30
8
277
REFER TO PANELBOARD SCHEDULES
24
TS
TIMED
7:30a - 10:OOp
STOCKROOM LTG AND SALES FLOOR LTG "A" 50%
C2
30
8
277
REFER TO PANELBOARD SCHEDULES
24
TS
TIMED
7:30a - 10:OOp
STOCKROOM LTG AND SALES FLOOR LTG "B" 50%
C3
30
8
120
REFER TO PANELBOARD SCHEDULES
24
TS
TIMED
7:30a - .10:OOp
SALES FLOOR TRACK DISPLAY LTG
C4
30
12
120
REFER TO PANELBOARD SCHEDULES
24
TS
TIMED
7:30a - 10:OOp
GONDOLA DISPLAY LTG, COOLER LTG
C5
30
8
277
REFER TO PANELBOARD SCHEDULES
24
TS
TIMED
5:OOp - 11:OOp
EXTERIOR BUILDING MOUNTED SIGN LTG
uGHTING CONTACTOR GENERAL NOTES:
1. ALL CONTACTORS SHALL BE LABELED INSIDE THE FRONT COVER INDICATING THE LOADS THAT ARE CONTROLLED AS WELL AS CONTROL CIRCUITS AS STATED ABOVE.
2. NUMBER ALL CONTACTOR WIRES AT CONTACTOR.
3. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION ON CONTACTORS.
4. SHORT CIRCUIT CURRENT RATING OF CONTACTORS SHALL MATCH THE RATING OF THE PANELBOARD FROM WHICH THE LOAD IS SERVED.
5. PROVIDE ENCLOSURE FOR ALL CONTACTORS AND CONTROL ACCESSORIES AS REQUIRED FOR INSTALLATION.
6. TIMED = TIMED CONTROL "ON" AND "OFF" WITH MANUAL OVERRIDE.
7. VERIFY ALL CONTROL SEQUENCING WITH OWNER.
8. CONTACTOR SHALL HAVE INDICATOR SIGNIFYING WHETHER THE LIGHTS CONTROLLED ARE ON OR OFF MOUNTED ON THE CONTACTOR ENCLOSURE.
9. CONTACTOR SHALL HAVE SWITCHES CONTROLLING MANUAL OVERRIDE OPERATION AT CUSTOMER SERVICE DESK.
10. CONTRACTOR TO PROVIDE ALL NECESSARY EQUIPMENT AND CONTROL WIRING FOR COMPLETE AND FULLY OPERATIONAL SYSTEM.
L /
RE.
CITY OF CEIV 0. TU LA
APR 2 4 2012
PERMIT CENTER
NOTE:
EXISTING CONDITIONS WERE TAKEN FROM ORIGINAL DRAWINGS & SITE VISITS
AND MAY NOT REFLECT EXACT "AS- BUILT" CONDITIONS. FIELD VERIFY ALL
EXISTING CONDITIONS PRIOR TO SUBMITTING FINAL BIDS. CAREFULLY
COORDINATE NEW WORK AND DEMOLITION WITH ALL OTHER DISCIPLINES
AND EXISTING CONDITIONS.
oa
0
0
of
(Joe
Z N
Q
OwC Ep
1 0
LU in
I- o°i
g f r) 0
Q y X
5 LL
ue
to
m � 1f1
6 1:2,9
cL OUtn
U i)Ln
w • O O'
N
lL i. 0
p To--
m
w
w go
I
a ui
0
0
N
N
H
2
ce
co
m
0)
a�
Z ri
Cn
LL 0 o 2
0090
Vo
Z W
Z
oO) E Z
N
i-o2
D
r
v
Z�
w °-
LAS VEGAS :: IRVINE :: PHOENIX :: SALT LAKE
oe
z
cc
*14
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: XM /RO /SJ
DRAWN BY: Atitli
FILE:
Immo
..
_ :I_ •� • ....
• • o. ::
•
isessoissa 600
SHEET NAME:
ELECTRICAL ONE -LINE
AND SCHEDULES
SHEET NUMBER:
E4.1
LO,HT,C1
LO,HT,C2
LO,HT,C 1
LO,HT,C2
LO,HT,C 1
LO, HT, C2
LO,HT,C1
LO,HT,C2
LO,HT,C1
LO,HT,C2
LO,HT,C 1
LO,HT,C2
LO,HT,C1
LO,HT,C2
LO,HT,C 1
LO,HT,C2
PANEI.BOARD HA
SERVICE ENTRANCE
PERMIT SET
SLIP ON CIRCUIT BREAKERS
VOLTS: 480Y/211V
METER SOCKET
X
BOLT ON CIRCUIT BREAKERS
MIN. BUS AMP RATING: 100
X
NEMA 1
ALUMINUM BUS
MIN. AIC: 22,000
NEMA 3R
X
COPPER BUS
MAIN: MLO
X
SURFACE MOUNT
LOCATION:
Electrical Room
PHASE: 3
Pl4ASE: 3
FLUSH MOUNT
FLUSH MOUNT
WIRE: 4
FREE STANDING
CKT.
CRCUf'T DESCRPTION
AMPACITY
POLE
LOAD
LOADS (VA)
LOAD
LOADS (VA)
AMPACITY
POLE
CRCUI•T DESCRIPTION
CKT.
A
B
C
1
SALES EAST LTS
/ ///
///I
/ //I
!/1I
///I
1111
1111
///I
//I/
I //I
11)14-1 -
2
20
1
L
1218
////
////
////
////
////
////
3
SALES EAST LTS
//!I
1111
1111
1150
IN
///I
R
////
20
3
15
1
L
////
1218
/1/I
////
////
////
1111
X
4
5
SALES EAST LTS
!1/I
1//1
////
////
3000
1111
R
////
- --
- --
20
1
L
////
////
951
////
462
////
////
X
6
1
SALES EAST LTS
// /I
////
///I
////
////
1150
R
612
- --
- --
20
1
L
951
////
////
////
/1//
////
////
SPAR
8
9
SALES NORTH LTS
/ //l
///I
I//1
1100
/ //I
1//1
M
////
20
1
20
1
L
////
1218
////
////
////
////
////
WH -3
10
11
SALES NORTH LTS
/I/1
// /l
////
//1/
2604
////
R
/11/
25
3
20
1
L
////
////
1218
////
141
////
////
X
12
13
SALES NORTH LTS
////
////
////
////
////
4481
R
- --
- --
20
1
L
696
////
// /l
I///
////
////
////
X
14
15
SALES NORTH LTS
/ //l
////
////
2604
////
////
R
///I
- --
- --
20
1
L
////
696
/ /l/
///I
////
1///
1///
1.1.11-1-2
16
11
SALE CENTER LTS
I ///
I///
////
1//I
10000
////
R
////
50
1
20
1
L
////
////
1218
1111
861
1111
///I
SPARE
18
19
SALE CENTER LTS
11/1
/III
///I
/ /I/
I /11
1100
M
1056
20
1
20
1
L
1218
////
////
////
I //I
////
////
SPARE
20
21
BOH NORTH LTS
////
1 //I
////
4260
////
/ /l/
11
////
20
I
20
1
L
I///
430
/1 /I
///l
////
1111
l ///
SPARE
22
23
SALE CENTER LTS
////
/ ///
/ ///
////
4260
////
M
I //l
20
1
20
1
L
////
/ //l
1480
////
348
1//I
////
SPARE
24
25
SALE CENTER LTS
////
/1 /l
l ///
I //I
////
4260
M
120
20
1
20
1
L
1480
////
I//I
II/I
////
/ /II
1//1
SPARE
26
21
5014 SOUTH LTS
/l//
11/1
/ //I
1100
//II
1//1
M
///I
20
1
20
I
L
/ ///
516
/ ///
////
////
/ ///
/ ///
SPARE
28
29
WINE TRAINING LTS
////
////
////
1111
1100
I ///
M
////
20
1
20
1
L
////
////
12W
////
1111
////
SPARE
30
31
SALE CENTER LTS
NI
1111
1///
1111
I/ /I
1100
11
20
1
20
I
L
609
////
////
////
////
I ///
////
SPARE
32
33
SALE CENTER LTS
////
/ //l
1111
2918
////
1111
M
////
20
I
20
I
L
////
609
/ /l/
/I//
////
/ /l/
I///
SPARE
34
35
SALE CENTER LTS
////
////
////
////
2918
////
M
1//1
20
I
20
I
L
////
////
1218
////
3328
IN
l /l/
SPARE
36
31
SALE CENTER LTS
////
////
////
////
/ //I
1000
L
360
20
I
20
1
L
1218
////
////
////
I///
////
////
SPARE
38
39
RECEIVING LTS
////
////
////
1920
////
////
R
////
20
1
20
1
L
I /l/
W4
I //I
///l
////
////
////
SPARE
40
41
RECEIVING LTS
/ //l
///I
////
l /l/
1920
////
R
////
20
I
20
1
L
////
////
132
////
150
////
////
SPARE
42
SPARE
42
/I //
///I
////
////
////
1000
///1
20
1
PHASE CONNECTED LOAD (VA)
PHASE DEMAND LOAD (VA)
TOTAL PANEL DEMAND (VA)
MAX PHASE AMPS
PANEL DEMAND AMPS
11150
21195
14350
15005
LOAD,
1954
PERCENT BALANCE
12253
11169
14450
16550
69%
98%
44413
48991
L= LIGHTING
P =PANEL
64
53
LOAD ABBREVIATIONS: C= CONTINUOUS, K= KITCHEN EQUIPMENT LOAD, L= LIGHTING
M =MOTOR LOAD, N= NON - CONTINUOUS LOAD, P =PANEL LOAD, R= RECEPTACLE LOAD
SPECIAL PROVISIONS:
Cs - ROUTE THROUGH CONTACTOR NUMBER AS SHOWN.
HT - PROVIDE HANDLE -TIE BETWEEN BREAKERS PER WEC 2009.
LO - BREAKER HANDLE LOCK "OFF" CLAMP PER NEC 42231(8).
SPECIAL PROVISIONS:
N,LO
N,LO
N,LO
N
ETR
C5
C5
N
PANEJ.BOARD CA
SERVICE ENTRANCE
PERMIT SET
SLIP ON CIRCUIT BREAKERS
VOLTS: 480Y/211V
METER SOCKET
X
BOLT ON CIRCUIT BREAKERS
MIN. BUS AMP RATING: 600
X
NEMA 1
ALUMINUM BUS
MN. AIC: 22,000
NEMA 3R
X
COPPER BUS
MAIN: 600A MCB
X
SURFACE MOUNT
LOCATION:
Electrical Room
PHASE: 3
Pl4ASE: 3
FLUSH MOUNT
FLUSH MOUNT
WIRE: 4
FREE STANDING
CKT.
CIRCUIT DESCRIPTION
AMPACITY
POLE
LOAD
LOADS (VA)
LOAD
LOADS (VA)
AMPACITY
POLE
CIRCUIT DESORPTION
CKT.
A
B
C
1
(E) PANEL HA
// //
////
///1
/1//
////
////
////
///I
////
////
(E) RTU -1
2
100
3
P
12253
////
1111
////
////
////
1111
3
X
////
11/1
1111
1100
1//1
////
M
////
40
3
- --
- --
P
////
11169
////
////
////
////
////
X
4
5
X
////
////
////
////
1100
1111
M
////
- --
- --
- --
- --
P
////
////
14450
////
462
////
////
X
6
1
(E) RTU -2
////
////
////
////
////
1100
M
612
- --
- --
40
3
M
1100
////
////
////
/1//
////
////
(E) RTU -3
8
9
X
////
////
////
1100
////
////
M
////
40
3
- --
- --
M
1111
1100
1111
////
////
////
////
X
10
11
X
////
1111
1111
////
1100
1111
M
/11/
- --
- --
- --
- --
M
1///
////
1100
////
141
////
/1/1
X
12
13
(E) RTU -4
////
////
////
/ //I
1111
1100
M
- --
- --
40
3
M
1100
1111
////
////
////
////
////
(E) RTU -5
14
15
X
////
////
////
1100
////
////
M
///I
40
3
- --
- --
M
////
1100
////
////
////
I///
1111
X
I6
it
X
////
////
////
////
1100
////
M
////
- --
- --
- --
- --
M
////
////
1100
////
861
////
////
X
15
19
(E) RTU -6
////
////
////
////
////
1100
M
1056
- --
- --
40
3
M
1100
1111
////
////
I //I
////
////
(E) RTU -1
20
2I
X
/ //l
1///
////
4260
////
////
11
////
30
3
- --
- --
M
////
1100
HI/
I/ //
////
1111
1111
X
22
23
X
I//1
1111
1/11
1///
4260
////
M
I //l
- --
- --
- --
- --
11
////
////
1100
////
348
////
////
X
24
25
(E) T225 -1
////
////
////
////
////
4260
M
120
- --
- --
350
3
M
43508
1111
////
////
////
////
////
(E) RTU -S
26
21
X
////
////
////
1100
////
////
M
///I
40
3
- --
- --
11
////
45911
////
////
////
////
////
X
28
29
X
////
////
////
////
1100
////
M
////
- --
- --
- --
- --
M
////
////
48519
////
////
////
X
30
31
SPACE
////
////
////
////
////
1100
11
- --
- --
20
3
M
1440
////
////
//// •
////
////
////
SPACE
32
33
SPACE
////
////
////
2918
////
////
M
////
- --
- --
- --
- --
11
////
1440
////
////
////
////
////
SPACE
34
35
SPACE
////
////
////
////
2918
////
M
1//1
- --
- --
- --
- --
M
////
////
1440
////
3328
////
////
SPACE
36
31
SPACE
////
////
////
////
////
1000
L
360
20
1
20
1
11
460
////
////
////
I///
////
////
SPACE
38
39
SPACE
////
////
////
1920
////
////
R
////
20
I
20
I
N
1111
500
1111
////
////
////
1111
SPACE
40
41
SPACE
////
////
////
////
1920
////
R
////
20
1
20
1
N
////
////
1000
////
150
////
////
SPACE
42
SPARE
42
////
////
////
////
////
1000
///1
20
I
PHASE CONNECTED LOAD (VA)
PHASE DEMAND LOAD (VA)
TOTAL PANEL DEMAND (VA)
MAX PHASE AMPS
PANEL DEMAND AMPS
109121
111100
116929
15005
LOAD,
1954
PERCENT BALANCE
121221
129200
128429
16550
94%•
98%
318850
48991
L= LIGHTING
P =PANEL
R= RECEPTACLE
466
456
LOAD ABBREVIATIONS: C= CONTNUOUS, K= KITCHEN EQUIPMENT LOAD, L= LIGHTING
M =MOTOR LOAD, N= NON - CONTINUOUS LOAD, P =PANEL LOAD, R= RECEPTACLE LOAD
SPECIAL PROVISIONS:
LOAD ABBREVIATIONS:
PANELBOARD LC
SERVICE ENTRANCE
PERMIT SET
SLIP ON CIRCUIT BREAKERS
VOLTS: 208Y /120V
METER SOCKET
X
BOLT ON CIRCUIT BREAKERS
MIN. BUS AMP RATING: 250
X
NEMA 1
ALUMINUM BUS
MIN. AIC: 10,000
NEMA 3R
X
COPPER BUS
MAIN: MLO
X
SURFACE MOUNT
LOCATION:
Electrical Room
PHASE: 3
Pl4ASE: 3
FLUSH MOUNT
FLUSH MOUNT
WIRE: 4
FREE STANDING
CKT.
CIRCUIT DESCRIPTION
AMPACITY
POLE
LOAD
LOADS (VA)
LOAD
LOADS (VA)
AMPACITY
POLE
CIRCUIT DESCRIPTION
CKT.
A
B
C
1
CLASS RM RECEPT
////
////
////
////
////
////
////
///I
////
////
CLEAN -UP R11
2
20
1
R
540
////
////
////
////
////
////
3
CLASS RM RECEPT
////
////
////
360
////
////
R
////
20
1
15
1
R
////
1380
////
////
////
////
////
CLEAN -UP fd'1
4
5
514OW WINDOW
////
////
////
////
360
////
R
////
20
1
20
1
L
/ /l/
l //l
1000
////
462
////
////
GARBAGE DISPOSER
////
1
CLASS R 1 RECEPT
///I
////
////
I ///
////
864
M
612
20
I
20
I
R
120
1111
////
////
/1//
////
////
WINE DAR RECEPT
8
9
CLASS RM RECEPT
////
////
////
540
////
////
R
////
20
I
20
I
R
//l/
540
I /l/
/1 /l
////
// /l
1111
COUNT 1 RECEPT
10
11
CU- 3/FCU -3
1111
////
I ///
I ///
120
////
R
/11/
20
1
20
1
11
1111
////
1465
IN
141
////
I ///
SECURITY
12
13
CONDENS. HTR
1111
1111
1111
1111
/ //I
540
R
20
1
20
1
M
1200
1111
IN
////
////
1111
//l/
WINE COOLER RECEPT
14
15
HAND DRYER
1111
////
////
180
////
////
R
///I
20
1
20
1
M
////
1000
////
////
////
////
////
CONDENS. HTR
16
11
HAND DRYER
/ /l/
/ /l/
l /l/
////
1200
////
M
////
20
1
20
1
M
I //1
//1I
1000
I1//
861
1111
1111
WINE COOLER RECEPT
18
19
FCU- IA
1111
////
111I
////
////
180
R
1056
20
I
20
1
M
1310
////
////
////
I //I
////
////
CU- 4/FCU -4
20
21
EWC
////
////
////
1210
/ //I
J///
M
////
20
2
20
1
R
////
180
////
////
////
////
////
X
22
23
BREAK ROOM RECEPT
////
////
////
////
1210
///I
M
I //l
- --
- --
20
1
R
////
////
360
////
348
////
////
CU- lA
24
25
FCU- IB
/ //I
/ //I
I ///
////
////
2918
M
120
40
3
20
1
M
1310
////
////
////
////
////
////
X
26
21
SIGNAGE
////
////
////
2918
////
////
M
///I
- --
- --
20
1
L
////
1200
////
////
////
////
////
X
28
29
SIGNAGE
////
////
////
////
2918
////
M
////
- --
- --
20
I
L
////
////
1200
////
////
////
CU- iB
30
31
CU -2
////
////
////
////
////
2918
M
40
3
20
3
M
1440
////
////
////
////
////
////
X
32
33
X
/I//
////
////
2918
////
////
M
////
- --
- --
- --
- --
11
////
1440
1111
////
////
////
1111
X
34
35
X
1111
////
////
1111
2918
////
M
1//1
- --
- --
- --
- --
M
////
////
1440
////
3328
////
////
HUMIDOR LIGHTING CNXN
36
31
FCU -3
////
// /l
////
/ //l
////
1000
L
360
20
1
20
1
11
460
////
////
////
I///
////
////
ICE MACHINE .1
38
39
DETEX LOCK
////
////
////
1920
////
////
R
////
20
I
20
I
N
////
500
////
////
////
////
////
ICE MACHINE *2
40
41
BREAK RM. MICROWAVE
////
////
////
////
1920
////
R
////
20
1
20
1
N
1111
////
1000
////
150
/ //l
////
BREAK Rh1. FRIDGE
42
SPARE
42
////
////
////
////
////
1000
///1
20
I
PHASE
PHASE
TOTAL
CONNECTED LOAD (VA)
DEMAND LOAD (VA)
PANEL DEMAND (VA)
MAX PHASE AMPS
PANEL DEMAND AMPS
C= CONTINUOUS, K= KITCHEN
M =MOTOR LOAD, N= NON - CONTINUOUS
15406
15246
15005
LOAD,
1954
LOAD,
PERCENT BALANCE
LOAD
16151
16291
16550
11041
98%
EQUIPMENT
48991
L= LIGHTING
P =PANEL
R= RECEPTACLE
138
136
LOAD,
LOAD,
LOAD ABBREVIATIONS:
SPECIAL PROVISIONS:
Cl - ROUTE, THR'xOUH CONTACTOR NUMBER AS SHOWN.
LO - BREAKER HANDLE LOCK "OFF" CLAMP PER NEC 422318).
LOAD ABBREVIATIONS:
LO
N
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
C3
LO
REVIEWED � FOR
WITH
NFPA 70 - NEC
MAY 0 9 2012
PANEIBOARD LA
SERVICE ENTRANCE
PERMIT SET
SLIP ON CIRCUIT BREAKERS
VOLTS: 208Y/120V
METER SOCKET
X
BOLT ON CIRCUIT BREAKERS
MIN. BUS AMP RATING: 100
X
NEMA I
ALUMINUM BUS
MN. AIC: 10,000
NEMA 3R
X
COPPER BUS
MAIN: MLO
X
SURFACE MOUNT
LOCATION:
Electrical Room
Pl4ASE: 3
FLUSH MOUNT
FLUSH MOUNT
WIRE: 4
WIRE: 4
FREE STANDING
CIRCUIT DESCRIPTION
CKT.
CIRCUR DESCRIPTION
AMPACITY
POLE
LOAD
LOADS (VA)
LOAD
POLE
AMPACITY
POLE
CIRCUIT DESCRIPTION
CKT.
A
B
C
1
AUTOMATIC DOORS
////
////
////
////
////
///I
////
////
////
////
DISPLAY LIGHTING A
2
20
I
R
150
////
////
////
////
////
1111
3
AUTOMATIC DOORS
1//1
////
////
480
///l
////
L
1
20
1
20
I
R
////
150
////
////
I ///
////
////
DISPLAY LIGHTING B
4
5
EAST WALL TRACK
////
////
////
////
612
////
L
1
20
1
20
1
L
1//I
///l
462
/ /l/
////
////
////
DISPLAY LIGHTING C
6
l
NORTH AISLE TRACK
////
////
////
////
////
612
L
1
20
i
20
1
L
903
////
/1//
////
////
////
////
DISPLAY LIGHTING D
8
I///
NORTH AISLE TRACK
////
////
////
612
////
////
L
1
20
1
20
1
L
////
612
////
Ill/
////
1111
////
DISPLAY LIGHTING E
10
11
HUMIDOR TRACK
1//I
11/1
1111
l/ //
480
/11/
L
I
20
1
20
1
L
////
////
141
////
/ //I
////
IN
SPARE
12
13
NORTH WALL TRACK
////
I ///
I ///
I ///
1111
20
1
20
1
20
I
L
154
////
////
////
////
////
1111
DISPLAY LIGHTING Cx
14
15
EAST WALL TRACK
////
////
////
1056
I //I
///I
L
1
20
I
20
I
L
////
348
////
////
////
////
////
DISPLAY LIGHTING H
16
11
CENTER AISLE TRACK
////
////
////
////
1056
////
L
1
20
1
20
1
L
////
////
861
1111
////
/ //I
1111
DISPLAY LIGHTING I
18
19
SOUTH AISLE TRACK
I/ //
I ///
I/1/
I //I
// /I
1056
L
1
20
1
20
1
L
400
/1//
I //I
1111
////
////
1111
DISPLAY LIGHTING J
20
21
SOUTH WALL TRACK
/ //I
////
I ///
432
////
////
L
20
I
20
I
L
////
2W
////
////
////
////
////
DISPLAY LIGHTING K
22
23
WEST WALL TRACK
////
////
// //
////
612
I //l
L
20
1
20
I
L
////
////
348
////
////
////
////
DISPLAY LIGHTING F
24
25
DUCT DETECTORS
////
////
////
////
////
120
L
20
1
20
1
R
200
////
////
////
1111
////
////
TRAIN. RM. FRIDGE
26
21
RTU RECEPT
////
///I
////
1000
///I
///I
N
20
1
20
1
R
////
120
////
////
////
////
////
TRAIN. RI. FRIDGE
28
29
SPARE
////
////
////
1///
1000
////
N
20
i
20
1
////
////
////
////
////
////
////
SPARE
30
31
SPARE
////
////
////
////
////
20
I
20
I
1111
////
///I
////
////
1111
// //
////
SPARE
32
33
DISHWASHER
////
////
////
////
////
////
20
1
40
2
R
////
3328
////
////
////
////
////
HUMIDOR PUMPS
34
35
X
////
////
/l//
////
660
1//1
M
20
1
- --
- --
R
////
////
3328
////
////
////
////
BEER COOLER PUMPS
36
31
SPARE
l ///
////
////
////
////
360
11
20
1
20
1
1111
////
////
I///
////
1111
////
////
SPARE
38
39
AUTOMATIC DOORS
////
///1
////
////
///I
////
20
1
20
1
R
////
150
////
////
////
////
////
WINE COOLER PUMP
40
41
AUTOMATIC DOORS
////
l///
//1/
////
180
////
M
20
1
20
1
R
////
////
150
////
////
////
////
SPARE
42
////
////
////
////
1//1
1//1
///1
20
1
PHASE
PHASE
TOTAL
CONNECTED LOAD (VA)
DEMAND LOAD (VA)
PANEL DEMAND (VA)
MAX PHASE AMPS
PANEL DEMAND AMPS
C= CONTINUOUS, K=KITCHEN
M =MOTOR LOAD, N= NON - CONTINUOUS
6223
9828
1954
LOAD,
PERCENT BALANCE
LOAD
4800
PERCENT BALANCE
LOAD
1391
11041
9021
EQUIPMENT
61%
EQUIPMENT
21458
L= LIGHTING
P =PANEL
R= RECEPTACLE
92
16
LOAD,
LOAD,
LOAD ABBREVIATIONS:
SPECIAL PROVISIONS:
C. - ROUTE THROUGH CONTACTOR NUMBER AS SHOWN.
PAM BOARD LB
SERVICE ENTRANCE
PERMIT SET
SLIP ON CIRCUIT BREAKERS
VOLTS: 208Y /120V
METER SOCKET
X
BOLT ON CIRCUIT BREAKERS
MN. BUS AMP RATING: 100
X
NEMA 1
ALUMINUM BUS
MN. AIC: 10,000
NEMA 3R
X
COPPER BUS
MAIN: MLO
X
SURFACE MOUNT
LOCATION:
Electrical Room
PHASE: 3
FLUSH MOUNT
WIRE: 4
FREE STANDING
CKT.
CIRCUIT DESCRIPTION
AMPACTTY
POLE
LOAD
LOADS (VA)
LOAD
E4.2
AMPACITY
POLE
CIRCUIT DESCRIPTION
CKT.
A
B
C
1
OUST SERV RECEPT IG
/ //l
I/!/
////
////
II //
1///
l /l/
1 /1/
////
CHECKSTAND POWER
2
20
I
R
360
////
////
////
////
////
3
OUST SERV RECEPT
////
////
////
120
////
////
R
20
1
20
I
R
////
120
////
1111
I //l
I ///
ISOLATED GROUND
CHECKSTAND RECEPT
4
5
GUST SERV RECEPT
////
// //
/ //I
////
120
// //
R
20
1
20
I
R
////
/1//
120
////
///1
////
CHECKSTAND POWER
6
1
OUST SERV RECEPT IG
////
///1
////
////
////
120
R
20
1
20
1
R
360
////
////
////
////
////
SPARE
8
9
SERVER RECEPT
I///
WI
1111
120
1111
////
20
1
* 30
1
////
1500
////
////
////
////
CHECKSTAND POWER
10
11
SERVER RM RECEPT
////
////
////
////
120
////
R
20
I
20
1
////
// //
120
// //
I ///
/ //I
ISOLATED GROUND
CHECKSTAND RECEPT
12
13
RPPA HEAT
////
////
I///
////
////
120
R
20
1
20
1
1920
////
////
////
////
////
CHECKSTAND POUE:R
14
15
RPPA HEAT
////
////
////
120
////
////
R
20
1
20
1
1111
1920
1111
////
1111
////
ISOLATED GROUND
CHECKSTAND RECEPT
16
11
RPPA HEAT
////
////
////
////
120
////
R
20
1
20
1
////
////
1920
////
////
////
SPARE
18
19
SPACE
////
////
////
I ///
////
20
1
////
////
////
1111
////
SPACE
20
21
SPACE
////
/11/
1111
////
////
////
////
////
////
////
SPACE
22
23
SPACE
////
////
I ///
////
I ///
// /I
////
////
////
////
SPACE
24
25
SPACE
1111
1111
IN
I ///
1111
////
1111
///i
I///
1111
SPACE
26
21
SPACE
////
////
////
////
////
////
////
////
////
////
SPACE
28
29
SPACE
////
////
1///
////
////
////
////
////
////
////
SPACE
30
31
SPACE
////
////
////
////
////
1111
////
1111
1111
1111
SPACE
32
33
SPACE
////
////
////
////
////
////
////
////
////
////
SPACE
34
35
SPACE
////
////
////
////
////
////
////
1111
////
////
SPACE
36
31
SPACE
////
////
////
////
////
1111
////
////
1111
1111
SPACE
38
39
SPACE
////
////
////
////
////
////
////
////
////
////
SPACE
40
41
SPACE
////
////
////
////
////
////
////
////
////
////
SPACE
42
////
////
////
////
////
PHASE
PRASE
TOTAL
CONNECTED LOAD (VA)
DEMAND LOAD (VA)
PANEL DEMAND (VA)
MAX PHASE AMPS
PANEL DEMAND AMPS
C= CONTINUOUS, K= KITCHEN
M =MOTOR LOAD, N= NON - CONTINUOUS
4800
6300
4800
LOAD,
PERCENT BALANCE
LOAD
4800
6300
4800
66%
EQUIPMENT
15900
L= LIGHTING
P =PANEL
R= RECEPTACLE
44
28
LOAD,
LOAD,
LOAD ABBREVIATIONS:
SPECIAL PROVISIONS:
* - BREAKER HANDLE LOCK "OFF" CLAMP PER NEC 42231(B)
PROVIDE PANEL WITH ISOLATED GROUND BUS
City of Tukwila
BUILDING DIVISION .
L12O3
CEIV
CITY RE OFTUK'MLA
APR 242012
PERMIT CENTER
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
C4
O
Li co
za
E
oo+
• U °c n
waIn
0 CA
- M O
as
w p0
=QcL
U
ui
0
0
N
CONSULTANT
Immo (.12 co
LAS VEGAS :: IRVINE :: PHOENIX :: SALT LAKE
E
loa50%
Vr�p�0 �
pp r
. ow
zomra �$a°o�ti
19gZN RWZZno
PaNnEmPOROM
cte
STORE NUMBER:
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE: E42 PANELBOARDS.DWG
,'�//NI. WW,
• �, G) 'J
• lii �
at ;�� �, r •e •u'' o: r. • • o•
• �•
. •, • o ft
� •• /STEM •
SHEET NAME
ELECTRICAL SCHEDULES
SHEET NUMBER:
E4.2
SECTION 16A GENERAL ELECTRICAL REQUIREMENTS — REV 121709:
16A 1 GENERAL INSTRUCTIONS
16A 1 -1 GENERAL REQUIREMENTS
ALL REQUIREMENTS UNDER DIVISION 1 AND THE GENERAL AND SUPPLEMENTARY
CONDITIONS OF THESE SPECIFICATIONS APPLY TO THIS SECTION AND DIVISION.
WHERE THE REQUIREMENTS OF THIS SECTION AND DIVISION EXCEED THOSE OF
DIVISION 1, THIS SECTION AND DIVISION TAKE PRECEDENCE. BECOME
THOROUGHLY FAMILIAR WITH ALL THEIR CONTENTS AS TO REQUIREMENTS THAT
AFFECT THIS DIVISION, SECTION OR BOTH. WORK REQUIRED UNDER THIS DIVISION
INCLUDES ALL MATERIAL, EQUIPMENT, APPLIANCES, AND LABOR REQUIRED TO
COMPLETE THE ENTIRE ELECTRICAL SYSTEM AS REQUIRED BY THE DRAWINGS
AND SPECIFICATIONS, OR REASONABLY INFERRED TO BE NECESSARY TO
FACILITATE EACH SYSTEM'S FUNCTIONING AS IMPLIED BY THE DESIGN AND THE
EQUIPMENT SPECIFIED.
THE SPECIFICATIONS AND DRAWINGS FOR THE PROJECT ARE COMPLEMENTARY,
AND PORTIONS OF THE WORK DESCRIBED IN ONE, SHALL BE PROVIDED AS IF
DESCRIBED IN BOTH. IN THE EVENT OF DISCREPANCIES, NOTIFY THE ENGINEER
AND REQUEST CLARIFICATION PRIOR TO PROCEEDING WITH THE WORK INVOLVED.
DRAWINGS ARE GRAPHIC REPRESENTATIONS OF THE WORK UPON WHICH THE
CONTRACT IS BASED. THEY SHOW THE MATERIALS AND THEIR RELATIONSHIP TO
ONE ANOTHER, INCLUDING SIZES, SHAPES, LOCATIONS, AND CONNECTIONS. THEY
ALSO CONVEY THE SCOPE OF WORK, INDICATING THE INTENDED GENERAL
ARRANGEMENT OF THE EQUIPMENT, FIXTURES, OUTLETS AND CIRCUITS WITHOUT
SHOWING ALL OF THE EXACT DETAILS AS TO ELEVATIONS, OFFSETS, CONTROL
LINES, AND OTHER INSTALLATION REQUIREMENTS. USE THE DRAWINGS AS A
GUIDE WHEN LAYING OUT THE WORK AND TO VERIFY THAT MATERIALS AND
EQUIPMENT WILL FIT INTO THE DESIGNATED SPACES, AND WHICH, WHEN
INSTALLED PER MANUFACTURERS' REQUIREMENTS, WILL ENSURE A COMPLETE,
COORDINATED, SATISFACTORY AND PROPERLY OPERATING SYSTEM.
DRAWINGS ARE SCHEMATIC IN NATURE, SHOW THE VARIOUS COMPONENTS OF
THE SYSTEMS APPROXIMATELY TO SCALE AND ATTEMPT TO INDICATE HOW THEY
SHALL BE INTEGRATED WITH OTHER PARTS OF THE WORK. FIGURED DIMENSIONS
TAKE PRECEDENCE TO SCALED DIMENSIONS. DETERMINE EXACT LOCATIONS BY
JOB MEASUREMENTS, BY CHECKING THE REQUIREMENTS OF OTHER TRADES, AND
BY REVIEWING ALL CONTRACT DOCUMENTS. CORRECT ERRORS THAT COULD
HAVE BEEN AVOIDED BY PROPER CHECKING AND INSPECTION, AT NO ADDITIONAL
COST TO THE OWNER.
SPECIFICATIONS DEFINE THE QUALITATIVE REQUIREMENTS FOR PRODUCTS,
MATERIALS, AND WORKMANSHIP UPON WHICH THE CONTRACT IS BASED.
16A 1 -2 DEFINITIONS
WHENEVER USED IN THESE SPECIFICATIONS OR DRAWINGS, THE FOLLOWING
TERMS SHALL HAVE THE INDICATED MEANINGS:
FURNISH: "TO SUPPLY AND DELIVER TO THE PROJECT SITE, READY FOR
UNLOADING, UNPACKING, ASSEMBLING, INSTALLING, AND SIMILAR OPERATIONS."
INSTALL: "TO PERFORM ALL OPERATIONS AT THE PROJECT SITE, INCLUDING, BUT
NOT LIMITED TO, AND AS REQUIRED: UNLOADING, UNPACKING, ASSEMBLING,
ERECTING, PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING,
CURING, PROTECTING, CLEANING, TESTING, COMMISSIONING, STARTING UP AND
SIMILAR OPERATIONS, COMPLETE, AND READY FOR THE INTENDED USE."
PROVIDE: "TO FURNISH AND INSTALL COMPLETE, AND READY FOR THE INTENDED
USE."
FURNISHED BY OWNER (OR OWNER- FURNISHED) OR FURNISHED BY OTHERS: "AN
ITEM FURNISHED BY THE OWNER OR UNDER OTHER DIVISIONS OR CONTRACTS,
AND INSTALLED UNDER THE REQUIREMENTS OF THIS DIVISION, COMPLETE, AND
READY FOR THE INTENDED USE, INCLUDING ALL ITEMS AND SERVICES INCIDENTAL
TO THE WORK NECESSARY FOR PROPER INSTALLATION AND OPERATION. INCLUDE
THE INSTALLATION UNDER THE WARRANTY REQUIRED BY THIS DIVISION.
ENGINEER: WHERE REFERENCED IN THIS DIVISION, "ENGINEER" IS THE ENGINEER
OF RECORD AND THE DESIGN PROFESSIONAL FOR THE WORK UNDER THIS
DIVISION, AND IS A CONSULTANT TO, AND AN AUTHORIZED REPRESENTATIVE OF,
THE ARCHITECT, AS DEFINED IN THE GENERAL AND /OR SUPPLEMENTARY
CONDITIONS. WHEN USED IN THIS DIVISION, IT MEANS INCREASED INVOLVEMENT
BY, AND OBLIGATIONS TO, THE ENGINEER, IN ADDITION TO INVOLVEMENT BY, AND
OBLIGATIONS TO, THE "ARCHITECT ".
AHJ: THE LOCAL CODE AND /OR INSPECTION AGENCY (AUTHORITY) HAVING
JURISDICTION OVER THE WORK.
NRTL: NATIONALLY RECOGNIZED TESTING LABORATORY, AS DEFINED AND LISTED
BY OSHA IN 29 CFR 1910.7 (E.G., UL, ETL, CSA), AND ACCEPTABLE TO THE AHJ OVER
THIS PROJECT.
HOMERUN: THAT PORTION OF AN ELECTRICAL CIRCUIT ORIGINATING AT A
JUNCTIO N BOX, TERMINATION BOX, R ECEP T ACL E OR SWITC H WITH TE RMINATIO N
AT AN ELECTRICAL PANELBOARD. NOTE: WHERE MC CABLE IS UTILIZED FOR
RECEPTACLE AND /OR LIGHTING BRANCH CIRCUITING LOADS, THE ORIGINATING
POINT OF THE HOMERUN SHALL BE AT THE FIRST LOAD IN THE CIRCUIT OR AT A
JUNCTION BOX IN AN ACCESSIBLE CEILING SPACE IMMEDIATELY ABOVE THE FIRST
LOAD.
THE TERMS "APPROVED EQUAL ", "EQUIVALENT ", OR "EQUAL" ARE USED
SYNONYMOUSLY AND SHALL MEAN "ACCEPTED BY OR ACCEPTABLE TO THE
ENGINEER AS EQUIVALENT TO THE ITEM OR MANUFACTURER SPECIFIED ". THE
TERM "APPROVED" SHALL MEAN LABELED, LISTED, CERTIFIED, OR ALL THREE, BY
AN NRTL, AND ACCEPTABLE TO THE AHJ OVER THIS PROJECT.
16A 1 -3 PRE -BID SITE VISIT
PERSONALLY INSPECT THE SITE OF THE PROPOSED WORK AND BECOME FULLY
INFORMED OF CONDITIONS UNDER WHICH THE WORK IS TO BE DONE. FAILURE TO
DO SO WILL NOT BE CONSIDERED SUFFICIENT JUSTIFICATION TO REQUEST OR
OBTAIN EXTRA COMPENSATION OVER AND ABOVE THE CONTRACT PRICE.
16A 1 -4 MATERIAL AND WORKMANSHIP
PROVIDE ALL MATERIAL AND EQUIPMENT NEW AND IN FIRST CLASS CONDITION.
PROVIDE MARKINGS OR A NAMEPLATE FOR ALL MATERIAL AND EQUIPMENT
IDENTIFYING THE MANUFACTURER AND PROVIDING SUFFICIENT REFERENCE TO
ESTABLISH QUALITY, SIZE AND CAPACITY. ALL WORKMANSHIP SHALL BE OF THE
FINEST POSSIBLE BY EXPERIENCED MECHANICS OF THE PROPER TRADE. IN
GENERAL, PROVIDE THE FOLLOWING QUALITY GRADE(S) FOR ALL MATERIALS AND
EQUIPMENT
COMMERCIAL SPECIFICATION GRADE
PROVIDE ALL HOISTS, SCAFFOLDS, STAGING, RUNWAYS, TOOLS, MACHINERY AND
EQUIPMENT REQUIRED FOR THE PERFORMANCE OF THE ELECTRICAL WORK.
STORE AND MAINTAIN MATERIAL AND EQUIPMENT IN CLEAN CONDITION, AND
PROTECTED FROM WEATHER, MOISTURE, AND PHYSICAL DAMAGE.
FURNISH ONLY MATERIAL AND EQUIPMENT THAT ARE LISTED, LABELED, CERTIFIED,
OR ALL THREE, BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL),
WHENEVER ANY LISTING OR LABELING EXISTS FOR THE TYPES OF MATERIAL AND
EQUIPMENT SPECIFIED.
AT A MINIMUM, GENERAL WORK PRACTICES FOR ELECTRICAL CONSTRUCTION
SHALL BE IN ACCORDANCE WITH:
NECA 1 (LATEST EDITION), "STANDARD PRACTICES FOR GOOD
WORKMANSHIP IN ELECTRICAL CONSTRUCTION ".
16A 1 -5 MANUFACTURERS
IN OTHER ARTICLES WHERE LISTS OF MANUFACTURERS ARE INTRODUCED,
SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF
THE MANUFACTURERS SPECIFIED.
WHERE A LIST IS PROVIDED, MANUFACTURERS ARE LISTED ALPHABETICALLY AND
NOT IN ACCORDANCE WITH ANY RANKING OR PREFERENCE.
WHERE MANUFACTURERS ARE NOT LISTED, PROVIDE PRODUCTS SUBJECT TO
COMPLIANCE WITH REQUIREMENTS FROM MANUFACTURERS THAT HAVE BEEN
ACTIVELY INVOLVED IN MANUFACTURING THE SPECIFIED PRODUCT FOR NO LESS
THAN 5 YEARS.
16A 1 -6 COORDINATION
COORDINATE ALL WORK WITH OTHER DIVISIONS AND TRADES SO THAT VARIOUS
COMPONENTS OF THE ELECTRICAL SYSTEMS ARE INSTALLED AT THE PROPER
TIME, FIT THE AVAILABLE SPACE, AND ALLOW PROPER SERVICE ACCESS TO ALL
EQUIPMENT. REFER TO ALL DRAWINGS, INCLUDING, BUT NOT LIMITED TO, CIVIL,
ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND PLUMBING, AND TO RELEVANT
EQUIPMENT SUBMITTALS AND SHOP DRAWINGS TO DETERMINE THE EXTENT OF
CLEAR SPACES. MAKE ALL OFFSETS REQUIRED TO CLEAR EQUIPMENT, BEAMS
AND OTHER STRUCTURAL MEMBERS, AND TO FACILITATE CONCEALING RACEWAYS
IN THE MANNER ANTICIPATED IN THE DESIGN. PROVIDE MATERIALS- WITH TRIM
THAT WILL FIT PROPERLY THE TYPES OF CEILING, WALL, OR FLOOR FINISHES
ACTUALLY INSTALLED.
16A 1 -7 ORDINANCES. CODES. AND STANDARDS
COMPLY, AT A MINIMUM, WITH NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
STANDARDS, STATE AND LOCAL BUILDING CODES, AND ALL OTHER APPLICABLE
CODES AND ORDINANCES FOR PERFORMANCE, WORKMANSHIP, EQUIPMENT, AND
MATERIALS. ADDITIONALLY, COMPLY WITH RULES AND REGULATIONS OF PUBLIC
UTILITIES AND MUNICIPAL DEPARTMENTS AFFECTED BY CONNECTION OF
SERVICES.
WHERE CONFLICTS BETWEEN VARIOUS CODES, ORDINANCES, RULES, AND
REGULATIONS EXIST, COMPLY WITH THE MOST STRINGENT. WHEREVER
REQUIREMENTS OF THESE SPECIFICATIONS, DRAWINGS, OR BOTH, EXCEED THOSE
OF THE ABOVE ITEMS, THE REQUIREMENTS OF THESE SPECIFICATIONS,
DRAWINGS, OR BOTH, SHALL GOVERN. CODE COMPLIANCE, AT A MINIMUM, IS
MANDATORY. CONSTRUE NOTHING IN THESE CONSTRUCTION DOCUMENTS AS
PERMITTING WORK NOT IN COMPLIANCE, AT A MINIMUM, WITH THESE CODES.
PROMPTLY BRING ALL CONFLICTS OBSERVED BETWEEN CODES, ORDINANCES,
RULES, REGULATIONS, REFERENCED STANDARDS, AND THESE DOCUMENTS TO
THE ENGINEER'S ATTENTION FOR FINAL RESOLUTION. CONTRACTOR WILL BE HELD
RESPONSIBLE FOR ANY VIOLATION OF THE LAW.
PROVIDE AND MAINTAIN ALL NECESSARY SIGNAL LIGHTS AND GUARDS FOR THE
SAFETY OF THE PUBLIC. OBTAIN AND PAY FOR ALL PERMITS FOR WORK IN THIS
DIVISION.
16A 1 -8 PROTECTION OF EQUIPMENT AND MATERIALS
STORE AND PROTECT FROM DAMAGE EQUIPMENT AND MATERIALS DELIVERED TO
JOB SITE, IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS. FOR
MATERIALS AND EQUIPMENT SUSCEPTIBLE TO CHANGING WEATHER CONDITIONS,
DAMPNESS, OR TEMPERATURE VARIATIONS, STORE INSIDE IN CONDITION SPACES.
FOR MATERIALS AND EQUIPMENT NOT SUSCEPTIBLE TO THESE CONDITIONS,
COVER WITH WATERPROOF, TEAR- RESISTANT, HEAVY TARP OR POLYETHYLENE
PLASTIC AS REQUIRED TO PROTECT FROM PLASTER, DIRT, PAINT, WATER, OR
PHYSICAL DAMAGE. EQUIPMENT AND MATERIAL THAT HAS BEEN DAMAGED BY
CONSTRUCTION ACTIVITIES WILL BE REJECTED, AND CONTRACTOR SHALL
FURNISH NEW EQUIPMENT AND MATERIAL OF A LIKE KIND.
PLUG OR CAP OPEN ENDS OF CONDUITS WHILE STORED AND INSTALLED DURING
CONSTRUCTION WHEN NOT IN USE TO PREVENT THE ENTRANCE OF DEBRIS INTO
THE SYSTEMS.
16A 1 -9 SUBSTITUTIONS
INCLUDE IN THE BASE BID THE PRODUCTS SPECIFICALLY NAMED IN THESE
SPECIFICATIONS OR ON THE DRAWINGS. SUBMIT, IN THE FORM OF ALTERNATES,
WITH BID, PRODUCTS OF ANY OTHER MANUFACTURERS FOR SIMILAR USE,
PROVIDED THE DIFFERENCES IN COST, IF ANY, ARE INCLUDED FOR EACH
PROPOSED ALTERNATE.
PRIOR TO THE BID DATE, SUBSTITUTIONS WILL NOT BE CONSIDERED UNLESS
SUBMITTED TO THE ARCHITECT, FOR ENGINEER'S REVIEW, AT LEAST TEN
CALENDAR DAYS PRIOR TO THE DATE FOR RECEIPT OF BIDS. INCLUDE THE NAME
OF THE MATERIAL OR EQUIPMENT FOR WHICH IT IS TO BE SUBSTITUTED AND A
COMPLETE DESCRIPTION OF THE PROPOSED SUBSTITUTE INCLUDING CUTSHEETS,
PHOTOMETRIC DATA, AND ALL OTHER INFORMATION NECESSARY FOR AN
EVALUATION FOR EACH SUCH REQUEST. PROVIDE FACTORY GENERATED POINT -
BY -POINT CALCULATIONS FOR ALL EXTERIOR LIGHT FIXTURES (PHOTOMETRIC
FILES SUPPLIED SO THE ENGINEER CAN GENERATE A POINT -BY -POINT DO NOT
SUFFICE FOR THE POINT -BY -POINT CALCULATIONS). PROVIDE INTERIOR POINT -BY-
POINT CALCULATIONS AT THE DISCRETION OF THE ENGINEER. SUBMIT A $100.00
REVIEW FEE TO THE ENGINEER WITH EACH SUCH POINT -BY -POINT CALCULATION
FOR USE OF ELECTRONIC BASE FILES.
AFTER THE BID DATE, PROPOSALS TO SUBSTITUTE LIGHT FIXTURES FOR THOSE
SHOWN ON THE DRAWINGS OR SPECIFIED HEREIN, WILL ONLY BE CONSIDERED AS
A DEDUCT. SUBMIT PROPOSED SUBSTITUTIONS SEPARATELY, IN SUBMITTAL
FORM, WITH A LIST OF PROPOSED SUBSTITUTIONS TOGETHER WITH A DEDUCT
PRICE FOR EACH SUBSTITUTION. THE ARCHITECTWILL THEN REVIEW PROPOSED
SUBSTITUTIONS.
THE ENGINEER WILL HAVE THE FINAL AUTHORITY AS TO WHETHER THE LIGHT
FIXTURE IS AN ACCEPTABLE REPLACEMENT TO THE SPECIFIED ITEM. THE
PROPOSED SUBSTITUTION MAY ALSO BE REJECTED BY THE ARCHITECT FOR
AESTHETIC REASONS IF FELT NECESSARY OR DESIRABLE. IN THE EVENT THE
PROPOSED SUBSTITUTIONS HEREIN DESCRIBED ARE REJECTED, FURNISH THE
SPECIFIED ITEM.
16A 1 -10 SUBMITTALS
1. ?ASSEMBLE AND SUBMIT TO THE ARCHITECT, FOR ENGINEER'S REVIEW,
MANUFACTURERS' PRODUCT LITERATURE FOR MATERIAL AND EQUIPMENT TO BE
FURNISHED, INSTALLED, OR BOTH, UNDER THIS DIVISION, INCLUDING SHOP
DRAWINGS, MANUFACTURERS' PRODUCT DATA AND PERFORMANCE SHEETS,
SAMPLES, AND OTHER SUBMITTALS REQUIRED BY THIS DIVISION. HIGHLIGHT,
MARK, LIST OR INDICATE THE MATERIALS, PERFORMANCE CRITERIA AND
ACCESSORIES THAT ARE BEING PROPOSED. PROVIDE THE NUMBER OF
SUBMITTALS REQUIRED BY DIVISION 1; HOWEVER, AT A MINIMUM, SUBMIT SEVEN
(7) SETS. BEFORE SUBMITTING, VERIFY THAT ALL MATERIALS AND EQUIPMENT
SUBMITTED ARE MUTUALLY COMPATIBLE AND SUITABLE FOR THE INTENDED USE,
FIT THE AVAILABLE SPACES, AND ALLOW AMPLE AND CODE- REQUIRED ROOM FOR
ACCESS AND MAINTENANCE. SUBMITTALS SHALL CONTAIN THE FOLLOWING
INFORMATION. SUBMITTALS NOT SO IDENTIFIED WILL BE RETURNED TO THE
CONTRACTOR WITHOUT ACTION:
THE PROJECT NAME.
THE APPLICABLE SPECIFICATION SECTION AND PARAGRAPH.
THE SUBMITTAL DATE.
THE CONTRACTOR'S STAMP, WHICH SHALL CERTIFY THAT THE STAMPED
DRAWINGS HAVE BEEN CHECKED BY THE CONTRACTOR, COMPLY WITH THE
DRAWINGS AND SPECIFICATIONS, AND HAVE BEEN COORDINATED WITH OTHER
TRADES.
SUBMITTALS AND SHOP DRAWINGS SHALL NOT CONTAIN THE ENGINEERS' FIRM NAME
OR LOGO, NOR SHALL IT CONTAIN THE ENGINEERS' SEAL AND SIGNATURE. THEY
SHALL NOT BE COPIES OF THE ENGINEERS' WORK PRODUCT.
TRANSMIT SUBMITTALS AS EARLY AS REQUIRED TO SUPPORT THE PROJECT
SCHEDULE. ALLOW FOR TWO WEEKS ENGINEER REVIEW TIME, PLUS MAILING TIME,
PLUS A DUPLICATION OF THIS TIME FOR RESUBMITTALS, IF REQUIRED. TRANSMIT
SUBMITTALS AS SOON AS POSSIBLE AFTER NOTICE TO PROCEED AND BEFORE
CONSTRUCTION STARTS. THE ENGINEER'S SUBMITTAL REVIEWS WILL NOT
RELIEVE THE CONTRACTOR FROM RESPONSIBILITY FOR ERRORS IN DIMENSIONS,
DETAILS, SIZE OF MEMBERS, OR QUANTITIES; OR FOR OMITTING COMPONENTS OR
FITTINGS; OR FOR NOT COORDINATING ITEMS WITH ACTUAL BUILDING
CONDITIONS.
REFER TO DIVISION 1 FOR ACCEPTANCE OF ELECTRONIC SUBMITTALS FOR THIS
PROJECT. FOR ELECTRONIC SUBMITTALS, CONTRACTOR SHALL SUBMIT THE
DOCUMENTS IN ACCORDANCE WITH THE PROCEDURES SPECIFIED IN DIVISION 1.
NT
CO RACTOR SHALL NOTIFY THE ARCHITEC T AND ENGINEER THAT THE SHOP
DRAWINGS HAVE BEEN POSTED. IF ELECTRONIC SUBMITTAL PROCEDURES ARE
NOT DEFINED IN DIVISION 1, CONTRACTOR SHALL INCLUDE THE WEBSITE, USER
NAME AND PASSWORD INFORMATION NEEDED TO ACCESS THE SUBMITTALS. FOR
SUBMITTALS SENT BY E -MAIL, CONTRACTOR SHALL COPY THE ARCHITECT AND
ENGINEER'S DESIGNATED REPRESENTATIVES. CONTRACTOR SHALL ALLOW THE
ENGINEER REVIEW TIME AS SPECIFIED ABOVE IN THE CONSTRUCTION SCHEDULE.
CONTRACTOR SHALL SUBMIT ONLY THE DOCUMENTS REQUIRED TO PURCHASE
THE MATERIALS AND /OR EQUIPMENT IN THE ELECTRONIC SUBMITTAL AND SHALL
CLEARLY INDICATE THE MATERIALS, PERFORMANCE CRITERIA AND ACCESSORIES
BEING PROPOSED. GENERAL PRODUCT CATALOG DATA NOT SPECIFICALLY NOTED
TO BE PART OF THE SPECIFIED PRODUCT WILL BE REJECTED AND RETURNED
WITHOUT REVIEW.
16A 1 -11 ELECTRONIC DRAWING FILES
IN PREPARATION OF SHOP DRAWINGS OR RECORD DRAWINGS, CONTRACTOR
MAY, AS AN OPTION, OBTAIN ELECTRONIC DRAWING FILES IN AUTOCAD OR DXF
FORMAT FROM THE ENGINEER FOR A SHIPPING AND HANDLING FEE OF $200 FOR A
DRAWING SET UP TO 12 SHEETS AND $15 PER SHEET FOR EACH ADDITIONAL
SHEET. CONTACT THE ARCHITECT FOR WRITTEN AUTHORIZATION; AND, CONTACT
THE ENGINEER TO OBTAIN THE NECESSARY RELEASE AGREEMENT FORM AND TO
INDICATE THE DESIRED SHIPPING METHOD AND DRAWING FORMAT. IN ADDITION
TO PAYMENT, ARCHITECT'S WRITTEN AUTHORIZATION AND ENGINEER'S RELEASE
AGREEMENT FORM MUST BE RECEIVED BEFORE ELECTRONIC DRAWING FILES WILL
BE SENT.
16A 1 -12 OPERATION AND MAINTENANCE INSTRUCTIONS
SUBMIT TO THE ARCHITECT, FOR ENGINEER'S REVIEW, COPIES EACH OF
OPERATIONS AND MAINTENANCE INSTRUCTION MANUALS, APPROPRIATELY
BOUND INTO MANUAL FORM INCLUDING APPROVED COPIES OF THE FOLLOWING,
REVISED IF NECESSARY TO SHOW SYSTEM AND EQUIPMENT AS ACTUALLY
INSTALLED. PROVIDE THE NUMBER OF SUBMITTALS REQUIRED BY DIVISION 1;
HOWEVER, AT A MINIMUM, SUBMIT THREE (3) SETS, AND INCLUDE, AT A MINIMUM,
THE FOLLOWING INFORMATION:
MANUFACTURERS' CATALOGS AND PRODUCT DATA SHEETS
WIRING DIAGRAMS
MAINTENANCE INSTRUCTIONS
OPERATING INSTRUCTIONS
PARTS LISTS
TEST REPORTS AS DEFINED IN NETA ATS FOR THE SYSTEMS AND EQUIPMENT
PROVIDED OR FURNISHED OR INSTALLED UNDER THIS CONTRACT.
NAMES, ADDRESSES, TELEPHONE NUMBERS, AND E -MAIL ADDRESSES OF
LOCAL CONTACTS FOR WARRANTEE SERVICES AND SPARE PARTS.
SUBMIT MANUALS PRIOR TO REQUESTING THE FINAL PUNCH LIST AND BEFORE
ANY REQUESTS FOR SUBSTANTIAL COMPLETION. ALSO PROVIDE ADEQUATE
VERBAL INSTRUCTIONS OF SYSTEM OPERATIONS TO OWNER'S REPRESENTATIVE
AT THE COMPLETION OF, AND BEFORE FINAL ACCEPTANCE OF, THE WORK.
16A 1 -13 TRAINING
AT A TIME MUTUALLY AGREED UPON BETWEEN THE OWNER AND CONTRACTOR,
PROVIDE THE SERVICES OF A FACTORY TRAINED AND AUTHORIZED
REPRESENTATIVE TO TRAIN OWNER'S DESIGNATED PERSONNEL ON THE
OPERATION AND MAINTENANCE OF THE EQUIPMENT PROVIDED FOR THIS
PROJECT.
PROVIDE TRAINING TO INCLUDE BUT NOT BE LIMITED TO AN OVERVIEW OF THE
SYSTEM AND /OR EQUIPMENT AS IT RELATES TO THE FACILITY AS A WHOLE;
OPERATION AND MAINTENANCE PROCEDURES AND SCHEDULES RELATED TO
STARTUP AND SHUTDOWN, TROUBLESHOOTING, SERVICING, PREVENTIVE
MAINTENANCE AND APPROPRIATE OPERATOR INTERVENTION; AND REVIEW OF
DATA INCLUDED IN THE OPERATION AND MAINTENANCE INSTRUCTIONS.
SUBMIT A CERTIFICATION LETTER TO THE ARCHITECT STATING THAT THE OWNER'S
DESIGNATED REPRESENTATIVE HAS BEEN TRAINED AS SPECIFIED HEREIN. LETTER
SHALL INCLUDE DATE, TIME, ATTENDEES AND SUBJECT OF TRAINING. THE
CONTRACTOR AND THE OWNER'S REPRESENTATIVE SHALL SIGN THE
CERTIFICATION LETTER INDICATING AGREEMENT THAT THE TRAINING HAS BEEN
PROVIDED.
SCHEDULE TRAINING WITH OWNER WITH AT LEAST 7 DAYS' ADVANCE NOTICE.
16A 1 -14 WARRANTIES
WARRANT EACH SYSTEM AND EACH ELEMENT THEREOF AGAINST ALL DEFECTS
DUE TO FAULTY WORKMANSHIP, DESIGN OR MATERIAL FOR A PERIOD OF 12
MONTHS FROM DATE OF SUBSTANTIAL COMPLETION, UNLESS SPECIFIC ITEMS ARE
NOTED TO CARRY A LONGER WARRANTY IN THE CONSTRUCTION DOCUMENTS OR
MANUFACTURER'S STANDARD WARRANTY EXCEEDS 12 MONTHS. REMEDY ALL
DEFECTS, OCCURRING WITHIN THE WARRANTY PERIOD(S), AS STATED IN THE
GENERAL CONDITIONS AND DIVISION 1.
ALSO WARRANT THE FOLLOWING ADDITIONAL ITEMS:
ALL RACEWAYS ARE FREE FROM OBSTRUCTIONS, HOLES, CRUSHING, OR
BREAKS OF ANY NATURE.
ALL RACEWAY SEALS ARE EFFECTIVE.
THE ENTIRE ELECTRICAL SYSTEM IS FREE FROM ALL SHORT CIRCUITS AND
UNWANTED OPEN CIRCUITS AND GROUNDS.
THE ABOVE WARRANTIES SHALL INCLUDE LABOR AND MATERIAL MAKE REPAIRS
OR REPLACEMENTS WITHOUT ANY ADDITIONAL COSTS TO THE OWNER.
PERFORM THE REMEDIAL WORK PROMPTLY, UPON WRITTEN NOTICE FROM THE
ENGINEER OR OWNER.
AT THE TIME OF SUBSTANTIAL COMPLETION, DELIVER TO THE OWNER ALL
WARRANTIES, IN WRITING AND PROPERLY EXECUTED, INCLUDING TERM LIMITS
FOR WARRANTIES EXTENDING BEYOND THE ONE YEAR PERIOD, EACH WARRANTY
INSTRUMENT BEING ADDRESSED TO THE OWNER AND STATING THE
COMMENCEMENT DATE AND TERM.
6A 1 -15 MISCELLANEOUS REMODELING WORK
PROVIDE ALL DEMOLITION OF EXISTING ELECTRICAL SYSTEMS AND NEW
ELECTRICAL SYSTEM MODIFICATIONS REQUIRED BECAUSE OF BUILDING
REMODELING, AS NOTED ON THE DRAWINGS, OR NECESSARY FOR PROPER
OPERATION AND NEW CONSTRUCTION. REMOVE ALL ABANDONED CABLES AND
WIRING ABOVE ACCESSIBLE CEILINGS AND VENTILATION SHAFTS.
16A 2 ELECTRICAL WORK
16A 2 -1 BUILDING OPERATION
COMPLY WITH THE SCHEDULE OF OPERATIONS AS OUTLINED IN THE
ARCHITECTURAL PORTIONS OF THIS SPECIFICATION. BUILDING SHALL BE IN
CONTINUOUS OPERATION. ACCOMPLISH WORK THAT REQUIRES INTERRUPTION
OF BUILDING OPERATION AT A TIME WHEN THE BUILDING IS NOT IN OPERATION,
AND ONLY WITH WRITTEN APPROVAL OF BUILDING OWNER AND /OR TENANT.
COORDINATE INTERRUPTION OF BUILDING OPERATION WITH THE OWNER AND /OR
TENANT A MINIMUM OF 7 DAYS IN ADVANCE OF WORK.
16A 2 -2 COINCIDENTAL DAMAGE
REPAIR ALL STREETS, SIDEWALKS, DRIVES, PAVING, WALLS, FINISHES, AND OTHER
FACILITIES DAMAGED IN THE COURSE OF THIS WORK. REPAIR MATERIALS SHALL
MATCH EXISTING CONSTRUCTION. ALL BACKFILLING AND REPAIRING SHALL MEET
ALL REQUIREMENTS OF THE OWNER, CITY AND OTHERS HAVING JURISDICTION.
REPAIR WORK SHALL BE THOROUGHLY FIRST CLASS. CONFORM TO ALL
REQUIREMENTS OF DIVISION 2 OF THESE SPECIFICATIONS.
16A 2 -3 CUTTING AND PATCHING
FOLLOWING THE REQUIREMENTS IN DIVISION 1, CUT WALLS, FLOORS, CEILINGS,
AND OTHER PORTIONS OF THE FACILITY AS REQUIRED TO PERFORM WORK UNDER
THIS DIVISION. OBTAIN PERMISSION OF THE ENGINEER, OWNER, OR BOTH,
BEFORE DOING ANY CUTTING. CUT ALL HOLES AS SMALL AS POSSIBLE. PATCH
WALLS, FLOORS, AND OTHER PORTIONS OF THE FACILITY AS REQUIRED BY WORK
UNDER THIS DIVISION. ALL PATCHING SHALL BE THOROUGHLY FIRST CLASS AND
SHALL MATCH THE ORIGINAL MATERIAL AND CONSTRUCTION, INCLUDING FIRE
RATINGS IF APPLICABLE.
16A 2 -4 ROUGH -IN
COORDINATE WITHOUT DELAY ALL ROUGHING -IN WITH OTHER DIVISIONS.
CONCEAL ALL RACEWAYS EXCEPT IN UNFINISHED AREAS AND WHERE OTHERWISE
INDICATED ON THE DRAWINGS.
16A 2 -5 SUPPORT SYSTEMS
STEEL SLOTTED SUPPORT SYSTEMS SLOTTED CHANNEL): COMPLY WITH MFMA-3,
1 FACTORY- FABRICATED COMPONENTS FOR FIELD ASSEMBLY; 12- GAUGE, 1 -5/8 -INCH
BY 1 -5/8 -INCH; COOPER B -LINE, ERICO INTERNATIONAL CORPORATION, HILTI, INC.,
POWER- STRUT, THOMAS & BETTS CORPORATION, UNISTRUT.
FINISHES:
A. METALLIC COATINGS: HOT -DIP GALVANIZED AFTER FABRICATION AND APPLIED
ACCORDING TO MFMA -3.
2. ALUMINUM SLOTTED SUPPORT SYSTEMS (SLOTTED CHANNEL): COMPLY WITH
MFMA -3, TYPE 6063 -T6, PER ASTM B221; FACTORY- FABRICATED COMPONENTS FOR
FIELD ASSEMBLY; 12- GAUGE, 1 -5/8 -INCH BY 1 -5/8 -INCH; COOPER B -LINE, ERICO
INTERNATIONAL CORPORATION, HILTI, INC., POWER- STRUT, THOMAS & BETTS
CORPORATION, UNISTRUT.
FIELD FABRICATION:
WHERE FIELD CUTTING OF STANDARD LENGTHS OF CHANNEL ARE REQUIRED,
MAKE CUTS STRAIGHT AND PERPENDICULAR TO MANUFACTURED SURFACES.
FOR FIELD -CUT OR DAMAGED SURFACES OF COATED CHANNELS, DRESS CUT
ENDS, DAMAGED SURFACES, OR BOTH, WITH AN ABRASIVE MATERIAL (E.G., FILE,
GRINDING STONE, OR SIMILAR) AND CLEANSER TO REMOVE OILS, RUST, SHARP
EDGES AND SHARDS.
FOR CHANNEL WITH A FACTORY- APPLIED COATING, RE- FINISH CUT EDGES WITH
A COATING COMPATIBLE WITH THE FACTORY FINISH AND AS RECOMMENDED BY
THE MANUFACTURER (E.G., MANUFACTURER'S TOUCH -UP PAINT OR ZINC -RICH
COLD- GALVANIZING COMPOUND, AS APPLICABLE).
16A 2 -6 PENETRATIONS
COORDINATE SLEEVE SELECTION AND APPLICATION WITH SELECTION AND
APPLICATION OF FIRE - STOPPING SPECIFIED IN DIVISION 7 SECTION 'THROUGH -
PENETRATION FIRESTOP SYSTEMS."
ROOFS:
COORDINATE ALL ROOF PENETRATIONS WITH ENGINEER, OWNER, AND AS
APPLICABLE, THE ROOFING CONTRACTOR PROVIDING A ROOF WARRANTY.
KEEP ALL RACEWAY PENETRATIONS WITHIN MECHANICAL EQUIPMENT CURBS
WHEREVER POSSIBLE. COORDINATE WITH DIVISION 15 WORK.
FLASH AND COUNTERFLASH ALL OPENINGS THROUGH ROOF, AND /OR PROVIDE
PRE - FABRICATED MOLDED SEALS COMPATIBLE WITH THE ROOF CONSTRUCTION
INSTALLED, OR AS REQUIRED BY THE ENGINEER, OWNER, OR ROOFING
CONTRACTOR. ALL ROOF PENETRATIONS SHALL BE LEAKTIGHT AT THE
TERMINATION OF THE WORK AND SHALL NOT VOID ANY NEW OR EXISTING ROOF
WARRANTIES.
WALLS AND FLOORS:
SLEEVES FOR RACEWAYS AND CABLES
1. STEEL PIPE SLEEVES: ASTM A 53/A 53M, TYPE E, GRADE B, SCHEDULE 40,
GALVANIZED STEEL, PLAIN ENDS AND DRIP RINGS.
2. CAST -IRON PIPE SLEEVES: CAST OR FABRICATED "WALL PIPE," EQUIVALENT TO
DUCTILE -IRON PRESSURE PIPE, WITH PLAIN ENDS AND INTEGRAL WATERSTOP,
UNLESS OTHERWISE INDICATED.
SLEEVES FOR RECTANGULAR OPENINGS: GALVANIZED SHEET STEEL WITH
MINIMUM 0.138 INCH THICKNESS AND OF WIDTH AND LENGTH TO SUIT
APPLICATION.
16A 2 -7 FIRE- STOPPING THROUGH PENETRATIONS
FIRE- RESISTANT THROUGH PENETRATION SEALANTS: TWO -PART, FOAMED -IN-
PLACE, SILICONE SEALANT FORMULATED FOR USE IN THROUGH - PENETRATION
FIRE - STOPPING AROUND CABLES, RACEWAYS, AND CABLE TRAY PENETRATIONS
THROUGH FIRE -RATED WALLS AND FLOORS. SEALANTS AND ACCESSORIES SHALL
HAVE FIRE - RESISTANCE RATINGS INDICATED, AS ESTABLISHED BY TESTING
IDENTICAL ASSEMBLIES IN ACCORDANCE WITH ASTM E 814, BY UNDERWRITERS'
LABORATORIES, INC., OR OTHER NRTL ACCEPTABLE TO AHJ.
ACCEPTABLE MANUFACTURERS:
HILTI, INC.
3M CORP.
RECTORSEAL.
SPECIFY TECHNOLOGY INC.
UNITED STATES GYPSUM COMPANY.
SUBMITTALS
SUBMIT PRODUCT DATA, MANUFACTURER'S SPECIFICATIONS AND TECHNICAL
DATA FOR EACH MATERIAL INCLUDING THE COMPOSITION AND LIMITATIONS,
DOCUMENTATION OF UL FIRESTOP SYSTEMS TO BE USED AND MANUFACTURER'S
INSTALLATION INSTRUCTIONS TO COMPLY WITH DIVISION 1.
MANUFACTURER'S ENGINEERING JUDGMENT IDENTIFICATION NUMBER AND
DRAWING DETAILS WHEN NO UL SYSTEM IS AVAILABLE FOR AN APPLICATION.
ENGINEERING JUDGMENT SHALL INCLUDE BOTH PROJECT NAME AND
CONTRACTOR'S NAME WHO WILL INSTALL FIRESTOP SYSTEM AS DESCRIBED IN
DRAWINGS.
SUBMIT MATERIAL SAFETY DATA SHEETS PROVIDED WITH PRODUCT DELIVERED TO
JOB -SITE.
16A 2 -8 CONCRETE BASES
PROVIDE CONCRETE BASES (E.G., HOUSEKEEPING PADS) FOR EQUIPMENT WHERE
INDICATED ON THE DRAWINGS AND AS SPECIFIED HEREIN. CONCRETE BASES
SHALL HAVE CHAMFERED EDGES. SIZE OF BASE SHALL BE A MINIMUM OF 2 INCHES
GREATER THAN THE FOOTPRINT OF THE EQUIPMENT THAT IT IS SUPPORTING.
CONSTRUCT EQUIPMENT BASES OF A MINIMUM 28 -DAY, 4000 -PSI CONCRETE
CONFORMING TO AMERICAN CONCRETE INSTITUTE STANDARD BUILDING CODE
FOR REINFORCED CONCRETE (ACI 318 -99) AND THE LATEST APPLICABLE
RECOMMENDATIONS OF THE ACI STANDARD PRACTICE MANUAL. CONCRETE
SHALL BE COMPOSED OF CEMENT CONFORMING TO ASTM C 150 TYPE I,
AGGREGATE CONFORMING TO ASTM C33, AND POTABLE WATER. EXPOSED
EXTERIOR CONCRETE SHALL CONTAIN 5 TO 7 PERCENT AIR ENTRAINMENT.
UNLESS OTHERWISE SPECIFIED OR SHOWN ON THE STRUCTURAL DRAWINGS,
REINFORCE EQUIPMENT BASES WITH NO. 4 REINFORCING BARS CONFORMING TO
ASTM A 615 OR 6X6 - W2.9 X W2.9 WELDED WIRE MESH CONFORMING TO ASTM
A185. PLACE REINFORCING BARS 24 INCHES ON CENTER WITH A MINIMUM OF TWO
BARS EACH DIRECTION.
PROVIDE GALVANIZED ANCHOR BOLTS FOR EQUIPMENT PLACED ON CONCRETE
BASES OR ON CONCRETE SLABS. ANCHOR BOLTS SIZE, NUMBER AND PLACEMENT
SHALL BE AS RECOMMENDED BY THE MANUFACTURER OF THE EQUIPMENT.
CONCRETE EQUIPMENT BASES SHALL HAVE A MINIMUM HEIGHT OF 4 INCHES AND
SHALL BE POURED -IN- PLACE.
16A 2 -9 ACCESS DOORS
PROVIDE ACCESS DOORS IN CEILINGS AND WALLS, WHERE INDICATED OR
REQUIRED FOR ACCESS OR MAINTENANCE TO CONCEALED EQUIPMENT
INSTALLED UNDER THIS SECTION. PROVIDE CONCEALED HINGES, SCREWDRIVER -
TYPE LOCK, AND ANCHOR STRAPS.
MANUFACTURED BY MILCOR, ZURN, TITUS, OR EQUAL. OBTAIN ARCHITECT'S
APPROVAL OF TYPE, SIZE, LOCATION AND COLOR BEFORE ORDERING.
16A 2 -10 EQUIPMENT FURNISHED BY OTHERS
PROVIDE NECESSARY EQUIPMENT AND ACCESSORIES THAT ARE NOT PROVIDED
BY THE EQUIPMENT SUPPLIER OR OWNER TO COMPLETE INSTALLATION OF
EQUIPMENT FURNISHED BY OTHERS, IN LOCATIONS AS INDICATED ON THE
DRAWINGS, SPECIFIED HEREIN, OR BOTH. EQUIPMENT AND ACCESSORIES NOT
PROVIDED BY THE EQUIPMENT SUPPLIER MAY INCLUDE SUCH ITEMS AS FLEXIBLE
CORDS AND PLUGS, AS REQUIRED FOR PROPER OPERATION OF THE COMPLETE
SYSTEM, IN ACCORDANCE WITH THE MANUFACTURERS' INSTRUCTIONS.
BE RESPONSIBLE FOR CORRECT ROUGH -IN DIMENSIONS, AND VERIFY THEM WITH
ENGINEER, OWNER'S REPRESENTATIVE, EQUIPMENT SUPPLIER, OR ALL THREE,
PRIOR TO ROUGH -IN AND SERVICE INSTALLATIONS.
16A 2 -11 CLEANING
IN ADDITION TO THE REQUIREMENTS OF DIVISION 1, REMOVE FROM THE PREMISES
DIRT AND REFUSE RESULTING FROM THE PERFORMANCE OF THE ELECTRICAL
WORK, AS REQUIRED, TO PREVENT ACCUMULATION. COOPERATE IN MAINTAINING
REASONABLY CLEAN PREMISES AT ALL TIMES. IMMEDIATELY PRIOR TO FINAL
INSPECTION, MAKE A FINAL CLEANUP OF DIRT AND REFUSE RESULTING FROM THE
WORK. CLEAN ALL MATERIAL AND EQUIPMENT INSTALLED UNDER THIS DIVISION.
REMOVE DIRT, DUST, PLASTER, STAINS AND FOREIGN MATTER FROM ALL
SURFACES. TOUCH UP AND RESTORE ALL DAMAGED FINISHES TO THEIR ORIGINAL
CONDITION.
16A 2 -12 ADJUSTING. ALIGNING AND TESTING
ADJUST, ALIGN, AND TEST ALL ELECTRICAL EQUIPMENT ON THIS PROJECT
PROVIDED UNDER THIS DIVISION AND ALL ELECTRICAL EQUIPMENT FURNISHED BY
OTHERS FOR INSTALLATION OR WIRING UNDER THIS DIVISION, FOR PROPER
OPERATION.
TEST ALL SYSTEMS AND EQUIPMENT ACCORDING TO THE REQUIREMENTS IN NETA
ATS (LATEST EDITION) AND ALL ADDITIONAL REQUIREMENTS SPECIFIED IN.
FOLLOWING SECTIONS.
MAINTAIN THE FOLLOWING ON THE PROJECT PREMISES AT ALL TIMES: A TRUE RMS
READING VOLTMETER, A TRUE RMS READING AMMETER, AND A MEGOHMMETER
INSULATION RESISTANCE TESTER. PROVIDE TEST DATA READINGS AS REQUESTED
OR AS REQUIRED BY THE ENGINEER.
16A 2 -13 EQUIPMENT IDENTIFICATION .
PROVIDE EQUIPMENT IDENTIFICATION NAMEPLATES:
ON ALL PANELBOARDS, SWITCHES, STARTERS, DIMMERS, SWITCHES IN
DISTRIBUTION PANELBOARDS AND SWITCHBOARDS.
NAMEPLATES:
ENGRAVED, CONTRASTING COLOR, THREE - LAYER, LAMINATED PLASTIC
INDICATING THE NAME OF THE EQUIPMENT, LOAD, OR CIRCUIT AS DESIGNATED
ON THE DRAWINGS AND IN THE SPECIFICATIONS:
FIELD - APPLIED PERMANENT EPDXY ADHESIVE, COMPATIBLE WITH THE
EQUIPMENT FINISH.
ATTACHMENT METHOD SHALL BE ACCEPTABLE TO THE MANUFACTURERS OF THE
EQUIPMENT TO WHICH THE NAMEPLATES ARE BEING APPLIED.
COLOR: BLACK BACKGROUND WITH WHITE LETTERS FOR NORMAL POWER; RED
BACKGROUND WITH WHITE LETTERS FOR EMERGENCY
POWER. LETTER HEIGHT: 1/2 -INCH MINIMUM
16A 2 -14 SYSTEM START UP
PRIOR TO STARTING UP THE ELECTRICAL SYSTEMS:
1. CHECK ALL COMPONENTS AND DEVICES.
2. LUBRICATE ITEMS ACCORDINGLY.
3. TIGHTEN SCREWS AND BOLTS FOR CONNECTORS AND TERMINALS ACCORDING TO
MANUFACTURER'S PUBLISHED TORQUE- TIGHTENING VALUES. IF
MANUFACTURER'S TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED
IN UL 486A AND UL 486B.
4. ADJUST TAPS ON EACH TRANSFORMER FOR RATED SECONDARY VOLTAGE WHEN
THE TRANSFORMER IS AT MINIMUM LOAD.
5. CHECK AND RECORD BUILDING'S SERVICE ENTRANCE VOLTAGE, GROUNDING
CONDITIONS, GROUNDING RESISTANCE, AND PROPER PHASING.
6. REPLACE ALL BURNED -OUT LAMPS AND LAMPS USED FOR TEMPORARY
CONSTRUCTION LIGHTING IN PERMANENT LIGHT FIXTURES.
7. AFTER ALL SYSTEMS HAVE BEEN INSPECTED AND ADJUSTED, CONFIRM ALL
OPERATING FEATURES REQUIRED BY THE DRAWINGS AND SPECIFICATIONS AND
MAKE FINAL ADJUSTMENTS AS NECESSARY.
16A 3 EXISTING EQUIPMENT REUSE AND REMOVAL
REMOVE ALL EXISTING WIRING, LIGHT FIXTURES, EXPOSED CONDUITS AND OTHER
ELECTRICAL INSTALLATIONS NOT REUSED PRIOR TO SUBSTANTIAL COMPLETION
OF THE WORK.
EXISTING RACEWAYS MAY BE REUSED IF THEIR POINTS OF TERMINATIONS ARE
SUITABLE; IF THEY ARE CLEAN INSIDE WITH NO EVIDENCE OF RUST OR BURRS: IF
FREE FROM CRACKS, FLATTENED SECTIONS OR SHARP BENDS; AND, IF SUITABLY
LOCATED TO AVOID CONFLICTS WITH OTHER TRADES OR INSTALLATIONS.
CAREFULLY "FISH" ALL EXISTING CONDUITS REUSED UNDER THIS CONTRACT TO
REMOVE ALL DEBRIS AND OBSTRUCTIONS, AND SWAB UNTIL ALL MOISTURE IS
REMOVED.
CUT, PATCH, AND REPAIR WHERE REQUIRED FOR NEW ELECTRICAL
INSTALLATIONS, AND PATCH AND REPAIR ALL SURFACE DAMAGE RESULTING FROM
THIS WORK. CUT FLUSH WITH THE FLOOR AND PLUG AT BOTH ENDS, RACEWAYS
STUBBED ABOVE THE FLOOR AND NOT USED AT SUBSTANTIAL COMPLETION OF
THE WORK.
RELOCATE ALL EXISTING ELECTRICAL SYSTEMS REQUIRED TO BE IN OPERATION
AT SUBSTANTIAL COMPLETION OF THE CONTRACT, IF REQUIRED, AS A RESULT OF
WORK INCLUDED UNDER THIS CONTRACT, EVEN IF NOT SPECIFICALLY INDICATED
IN THE DRAWINGS OR SPECIFICATIONS.
16A 4 ALTERNATES
INCLUDE ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY FOR
AND INCIDENTAL TO THE COMPLETION OF ALL WORK UNDER EACH PARTICULAR
ALTERNATE. FURNISH SEPARATE BIDS FOR EACH APPLICABLE ALTERNATE,
STATING THE AMOUNT TO BE ADDED TO OR DEDUCTED FROM THE BASE BID FOR
EACH ALTERNATE ACCEPTED. APPLICABLE SECTIONS OF THE BASE
SPECIFICATIONS APPLY TO ALL WORK REQUIRED BY THE ALTERNATES UNLESS
OTHERWISE SPECIFIED. REFER TO THE ARCHITECTURAL PORTION OF THE
SPECIFICATIONS FOR THE LIST OF ALTERNATES.
REVIEWED FOR
COMPLIANCE WITH
NFPA 70 - NEC
MAY 092012
City of Tukwila
!ILOING DIVISION
EL>O3.. I
RECC�v u
CITY OFTU LA
APR 242012
PERMIT CENTER
as
0
Ln
U m
�
Q
LL XObi
0
rn
Ln
Ln
CL)
N
0
VD
LL
c
1— o
-c
Lu a-
l— a
ti)
Q y
cc N
CO Ln
6 i
o '
U N w
W
om'D
co
w
L.) c0
=Qa
ce
Q 1-1-1 •
0
0
N
J
N
8
N
L_
1)
a)
N
CO
rn
a,.
-00
a 0
o_
oW
z w
z
w 0
oa
N aF
x
F 0 0
rk-
co W I-
"4:
za
140) 64u
W m
titt
1110101
0 Imit
y
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE: E51 SPECS.DWG
%Willi 17*
��, � � . OF ;51/.• • .j`��i . .
't' rr1-1•
•� p•
- • Z;
• -0 •. /STEF� •. • -i.yo; ...........
.44 ti ■ I sts•t°
SHEET NAME
ELECTRICAL SPECIFICATIONS
SHEET NUMBER:
E5.1
SECTION 1 6B BASIC ELECTRICAL MATERIALS AND
060810
16B 1 METHODS
16B 1 -1 RACEWAYS
METALLIC CONDUIT AND TUBING:
METHODS — REV :
ELECTRICAL METALLIC TUBING, COUPLINGS AND FITTINGS (EMT): ANSI C80.3, UL
797. ONLY STEEL PRODUCTS ALLOWED.
REDUCED WALL EMT IS NOT ALLOWED.
FLEXIBLE METAL CONDUIT (FMC): ZINC — COATED STEEL OR ALUMINUM, UL 1.
REDUCED —WALL FMC IS NOT ALLOWED.
INTERMEDIATE METAL CONDUIT (IMC): HOT —DIP GALVANIZED RIGID STEEL
CONDUIT: ANSI C80.6, UL 1242.
LIQUIDTIGHT FLEXIBLE METAL CONDUIT (LFMC): FLEXIBLE STEEL CONDUIT WITH
PVC JACKET: UL 360
RIGID METAL CONDUIT (RMC): HOT —DIP GALVANIZED RIGID STEEL CONDUIT
(GRS): ANSI C80.1, UL 6.
PLASTIC— COATED IMC, RMC, AND FITTINGS: NEMA RN 1, UL LISTED.
IMC AND RMC FITTINGS: NEMA FB 1; COMPATIBLE WITH CONDUIT TYPE AND
MATERIAL, UL LISTED
NON— METALLIC CONDUIT AND TUBING:
RIGID NONMETALLIC CONDUIT (RNC): SCHEDULE 40 PVC, 90 DEG C RATED,
NEMA TC -2, UL 651; FITTINGS: NEMA TC 3, TC 6; UL 514, COMPATIBLE WITH
CONDUIT/TUBING TYPE AND MATERIAL, UL LISTED.
16B 1 -2 RACEWAY INSTALLATION
ABOVE GROUND USE
INSTALL ALL CIRCULAR RACEWAYS CONCEALED ABOVE SUSPENDED CEILINGS
OR CONCEALED IN WALLS OR FLOORS WHEREVER POSSIBLE EXCEPT WHERE
OTHERWISE INDICATED.
PROVIDE GRS FOR ALL CONDUITS RUN EXPOSED TO WEATHER, OR EXPOSED
TO OTHER HAZARDOUS CONDITIONS.
ALL OTHER RACEWAY MAY BE EMT WHERE APPROVED BY LOCAL CODE. USE
COMPRESSION TYPE FITTINGS FOR EMT, WITH ALL FITTINGS UL LISTED FOR THE
ENVIRONMENT IN WHICH THEY ARE USED.
UNDERGROUND USE
PROVIDE GRS INSTALLED BELOW GRADE WITH A CORROSION RESISTANT
BONDED — PLASTIC OR APPROVED MASTIC COATING. THIS SHALL INCLUDE THE
90— DEGREE ELBOW BELOW GRADE AND THE ENTIRE VERTICAL TRANSITION TO
ABOVE GRADE.
EQUIPMENT CONNECTIONS
USE FMC FOR FINAL CONNECTION TO EACH TRANSFORMER, N MOTOR AND T ORMER, AND
TO ANY DEVICE THAT WOULD OTHERWISE TRANSMIT MOTION, VIBRATION, OR
NOISE. USE LFMC WHERE EXPOSED TO LIQUIDS, VAPORS OR SUNLIGHT, AND
TO CONNECT TO KITCHEN AND FOOD SERVICE EQUIPMENT. PROVIDE ALL FMC
AND LFMC WITH AN INSULATED BONDING CONDUCTOR.
USE ONLY METAL RACEWAYS FOR ALL POWER WIRING FROM THE OUTPUT OF
VARIABLE FREQUENCY DRIVES TO THEIR RESPECTIVE MOTORS.
GENERAL RACEWAY INSTALLATION REQUIREMENTS
INSTALL RACEWAYS PARALLEL AND PERPENDICULAR TO BUILDING LINES.
INSTALL RACEWAYS TO REQUIREMENTS OF STRUCTURE AND TO
REQUIREMENTS OF ALL OTHER WORK ON THE PROJECT; TO CLEAR ALL
OPENINGS, DEPRESSIONS, PIPES, DUCTS, REINFORCING STEEL, AND OTHER
IMMOVABLE OBSTACLES.
INSTALL RACEWAYS SET IN FORMS FOR CONCRETE STRUCTURE IN SUCH A
MANNER THAT INSTALLATION WILL NOT AFFECT THE STRENGTH OF THE
STRUCTURE.
EXCEPT WHERE APPROVED IN WRITING BY THE ENGINEER, INSTALL NO
RACEWAY IN A SLAB —ON— GRADE. LOCATE RACEWAY BELOW GRANULAR FILL
BELOW SLABS —ON— GRADE.
INSTALL RACEWAYS CONTINUOUS BETWEEN CONNECTIONS TO OUTLETS,
BOXES AND CABINETS WITH A MINIMUM POSSIBLE NUMBER OF BENDS AND NOT
MORE THAN THE EQUIVALENT OF FOUR 90— DEGREE BENDS BETWEEN
CONNECTIONS. USE MANUFACTURED ELBOWS FOR ALL 45— AND 90— DEGREE
BENDS, UNLESS APPROVED BY THE ENGINEER IN ADVANCE. MAKE OTHER
BENDS SMOOTH AND EVEN AND WITHOUT FLATTENING RACEWAY OR FLAKING
GALVANIZING OR ENAMEL RADII OF BENDS SHALL BE AS LONG AS POSSIBLE
AND NEVER SHORTER THAN THE CORRESPONDING TRADE ELBOW.
USE LONG RADIUS ELBOWS FOR ALL UNDERGROUND INSTALLATIONS, WHERE
NECESSARY OR INDICATED.
SECURELY FASTEN RACEWAYS IN PLACE WITH APPROVED STRAPS, HANGERS
AND STEEL SUPPORTS AS REQUIRED. ATTACH RACEWAY SUPPORTS TO THE
BUILDING STRUCTURE. HANG SINGLE RACEWAYS FOR FEEDERS WITH
MALLEABLE SPLIT RING HANGERS WITH ROD AND TURNBUCKLE SUSPENSION
FROM INSERTS SPACED NOT OVER 10 FEET APART IN CONSTRUCTION ABOVE.
CLAMP GROUPS OF HORIZONTAL FEEDER RACEWAYS TO STEEL CHANNELS
THAT ARE SUSPENDED FROM INSERTS SPACED NOT OVER 10 FEET APART IN
CONSTRUCTION ABOVE. SECURELY CLAMP VERTICAL FEEDER RACEWAYS TO
STRUCTURAL STEEL MEMBERS ATTACHED TO STRUCTURE. INSTALL CABLE
CLAMPS FOR SUPPORT OF VERTICAL FEEDERS WHERE REQUIRED. ADD
RACEWAY SUPPORTS WITHIN 12 INCHES OF ALL BENDS, ON BOTH SIDES OF THE
BENDS: - DO NOT SUPPORT RACEWAYS FROM SUSPENDED CEILING
COMPONENTS.
REAM RACEWAY ENDS, THOROUGHLY CLEAN RACEWAYS BEFORE
INSTALLATION, AND KEEP CLEAN AFTER INSTALLATION. PLUG OR COVER
OPENINGS AND BOXES AS REQUIRED TO KEEP RACEWAYS CLEAN DURING
CONSTRUCTION AND FISH ALL RACEWAYS CLEAR OF OBSTRUCTIONS BEFORE
PULLING CONDUCTORS WIRES. PROVIDE RACEWAYS OF AMPLE SIZE FOR
PULLING OF WIRE AND NOT SMALLER THAN CODE REQUIREMENTS AND NOT
LESS THAN 1/2 —INCH IN SIZE, UNLESS INDICATED OTHERWISE ON DRAWINGS.
H OMERUNS SHA LL NOT BE LESS THAN 3/4— INCH IN SIZE.
PROTECT ALL RACEWAY INSTALLATIONS AGAINST DAMAGE DURING
CONSTRUCTION. REPAIR ALL RACEWAYS DAMAGED OR MOVED OUT OF LINE
AFTER ROUGHING —IN TO MEET ENGINEER'S APPROVAL WITHOUT ADDITIONAL
COST TO THE OWNER.
ALIGN AND INSTALL TRUE AND PLUMB ALL RACEWAY TERMINATIONS AT
PANELBOARDS, SWITCHBOARDS, MOTOR CONTROL EQUIPMENT AND JUNCTION
BOXES.
INSTALL APPROVED EXPANSION /DEFLECTION FITTINGS WHERE RACEWAYS
PASS THROUGH (IF EMBEDDED) OR ACROSS (IF EXPOSED) EXPANSION JOINTS.
ALSO WHEN USING RNC OR RAC IN EXPOSED ENVIRONMENTS IN ACCORDANCE
WITH THE NEC AND EXPANSION /CONTRACTION PROPERTIES OF RNC OR RAC.
INSTALL A PULL WIRE IN EACH EMPTY RACEWAY THAT IS LEFT FOR
INSTALLATION OF CONDUCTORS OR CABLES UNDER OTHER DIVISIONS OR
CONTRACTS. USE POLYPROPYLENE OR MONOFILAMENT PLASTIC LINE WITH
NOT. LESS. THAN 200 —LB TENSILE STRENGTH. LEAVE AT LEAST 24 INCHES OF
SLACK AT EACH END OF PULL WIRE.
MAKE ALL JOINTS AND CONNECTIONS IN A MANNER THAT WILL ENSURE
MECHANICAL STRENGTH AND ELECTRICAL CONTINUITY.
RACEWAYS PENETRATING FREEZER AND COOLER WALLS:
EFFECTIVELY SEAL RACEWAYS, BY INSTALLING A CONDUIT FITTING AT THE
BOUNDARY OF THE TWO SPACES, AND FILLING IT WITH AN APPROVED PLIABLE
MATERIAL, AFTER CONDUCTORS OR CABLES HAVE BEEN INSTALLED AND
TESTED, WHEN EVER:
RACEWAYS PASS FROM NON— COOLED TO COOLED SPACES.
RACEWAYS TRANSITION FROM OUTSIDE A FACILITY OR ENCLOSURE TO
INSIDE, WHETHER BURIED OR EXPOSED.
16B 1 -3 BUSHINGS AND LOCKNUTS
RIGIDLY TERMINATE CONDUITS ENTERING SHEET METAL ENCLOSURES TO THE
ENCLOSURE WITH A BUSHING AND LOCKNUT ON THE INSIDE AND A LOCKNUT
OR AN APPROVED HUB ON THE OUTSIDE. CONDUIT SHALL ENTER THE
ENCLOSURE SQUARELY.
PROVIDE BUSHINGS AND LOCKNUTS MADE OF GALVANIZED MALLEABLE IRON
WITH SHARP, CLEAN —CUT THREADS.
WHERE EMT ENTERS A BOX, PROVIDE APPROVED EMT COMPRESSION
CONNECTORS.
USE INSULATED, GROUNDING, OR COMBINATION, BUSHINGS WHEREVER
'CONNECTION IS SUBJECT TO VIBRATION OR MOISTURE, WHEN REQUIRED BY
NFPA 70, OR BOTH.
16B 1 -4 CONDUCTORS AND CABLES
CONDUCTOR MATERIAL:
ANNEALED (SOFT) COPPER COMPLYING WITH ICEA S -95- 658 /NEMA WC70;
CONDUCTOR INSULATION TYPES: 90— DEGREE C— RATED, TYPE THHN /THWN -2 OR
XHHW -2 COMPLYING WITH ICEA 5 -95- 658 /NEMA WC70.
SIZES OF CONDUCTORS AND CABLES INDICATED OR SPECIFIED ARE IN
AMERICAN WIRE GAGE (AWG — BROWN AND SHARPE).
ALL FEEDER AND BRANCH CIRCUIT CONDUCTORS NO. 8 AWG AND LARGER:
STRANDED.
ALL CONDUCTORS, NO. 10 AWG AND SMALLER: SOLID COPPER
ALL BRANCH CIRCUIT WIRING: NOT SMALLER THAN NO. 12 AWG. IF NO
CONDUCTOR SIZE IS INDICATED ON THE DRAWINGS FOR A BRANCH CIRCUIT,
PROVIDE CONDUCTORS AND CONDUIT SIZED PER NFPA 70 AND BASED ON THE
INDICATED BRANCH CIRCUIT OVERCURRENT PROTECTIVE DEVICE (OCPD)
RATING AND NUMBER OF POLES. WHERE NO CIRCUIT SIZE (I.E., CONDUCTORS
AND OCPD) IS INDICATED ON THE DRAWINGS FOR A BRANCH CIRCUIT, PROVIDE
THREE NO. 12 AWG CONDUCTORS, IN 3/4 —INCH RACEWAY, AND A 20A CIRCUIT
BREAKER.
CONTROL WIRING: STRANDED COPPER CONDUCTORS, 600V INSULATION, OF
THE PROPER TYPE, SIZE AND NUMBER AS REQUIRED TO ACCOMPLISH
SPECIFIED FUNCTION. MINIMUM SIZE: NO. 14 AWG, UNLESS NOTED OTHERWISE.
STRANDED FOR ALL FLEXIBLE CORDS AND CABLES, OR AS OTHERWISE
INDICATED.
UNLESS INDICATED OTHERWISE, SPECIAL PURPOSE CONDUCTORS AND
CABLES, SUCH AS LOW VOLTAGE CONTROL AND SHIELDED INSTRUMENT
WIRING, SHALL BE AS RECOMMENDED BY THE SYSTEM EQUIPMENT
MANUFACTURER.
TYPE MC CABLE: 600V, UNJACKETED; ANSI E119 AND E814, UL STANDARDS 44 OR
83 (AS APPLICABLE), AND 1569, NFPA 70 ARTICLE 330; ALUMINUM OR GALVANIZED
STEEL INTERLOCKED ARMOR; THHN— OR XHHW— INSULATED CONDUCTORS;
COLOR CODE: ICEA METHOD 1, WITH GREEN INSULATED GROUNDING
CONDUCTOR
16B 1 -5 INSTALLATION OF CONDUCTORS AND CABLES
INSTALL ALL WIRING IN APPROVED RACEWAY AND ENCLOSURES.
SUPPORT ALL CONDUCTORS AND CABLES IN VERTICAL INSTALLATIONS, AS
REQUIRED BY NFPA 70, BY INSTALLING CABLE SUPPORTS OR PLUG —TYPE
CONDUIT RISER SUPPORTS, OR WIRE —MESH SAFETY GRIPS.
INSTALL ALL CONDUCTORS AND CABLE IN RACEWAYS CONTINUOUS WITHOUT
TAPS OR SPLICES. SPLICE OR TAP ONLY IN APPROVED BOXES AND
ENCLOSURES WITH APPROVED SOLDERLESS CONNECTORS, OR CRIMP
CONNECTORS AND TERMINAL BLOCKS FOR CONTROL WIRING, AND KEEP TO
THE MINIMUM INSULATE ALL REQUIRED. SPLICES, LA E LL SPL CES, TAPS, AND JOINTS AS
REQUIRED BY CODES.
ALL MATERIALS USED TO TERMINATE, SPLICE OR TAP CONDUCTORS: DESIGNED
FOR, PROPERLY SIZED FOR, AND UL LISTED FOR THE SPECIFIC APPLICATION
AND CONDUCTORS INVOLVED, AND INSTALLED IN STRICT ACCORDANCE WITH
THE MANUFACTURER'S RECOMMENDATIONS, USING THE MANUFACTURER'S
RECOMMENDED TOOLS.
WHERE WIRING IS INDICATED AS INSTALLED, BUT THE CONNECTION IS
INDICATED "FUTURE" OR "BY OTHER DIVISION, TRADES, OR CONTRACTS ", LEAVE
A MINIMUM 3 —FOOT "PIGTAIL" AT THE BOX, TAPE THE ENDS OF THE
CONDUCTORS, AND COVER THE BOX.
THE NUMBER OF CONDUCTORS IN A SPECIFIC RACEWAY "HOME RUN" IS
INDICATED WITH CROSS LINES (TICK MARKS) ON EACH "CIRCUIT RUN" ON THE
DRAWINGS. IN GENERAL, THE DIRECTION OF BRANCH CIRCUIT "HOME RUN"
ROUTING IS INDICATED ON THE DRAWINGS, COMPLETE WITH CIRCUIT NUMBERS
AND PANELBOARD DESIGNATION. CONTINUE ALL SUCH "HOME RUN" WIRING TO
THE DESIGNATED PANELBOARD, AS THOUGH "CIRCUIT RUNS" WERE INDICATED
IN THEIR ENTIRETY.
MULTI —WIRE BRANCH CIRCUITS (I.E., SHARED NEUTRAL) SHALL BE PROVIDED
WITH A MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED
CONDUCTORS AT THE POINT THE BRANCH CIRCUIT ORIGINATES. MULTI —POLE
BREAKERS OR 3 SINGLE POLE BREAKERS WITH A HANDLE TIE ARE TWO
EXAMPLES.
WHEN MULTIPLE HOME RUNS ARE COMBINED INTO A SINGLE RACEWAY SUCH
THAT THE NUMBER OF CONDUCTORS EXCEEDS CTORS EXCE FOUR U (CONDUCTOR COUNT IS
(
MADE UP OF ANY COMBINATION OF PHASE AND NEUTRAL CONDUCTORS), THE
FOLLOWING RESTRICTIONS APPLY, WHICH ARE IN ADDITION TO THOSE IN NFPA
70:
NORMAL OR NON— ESSENTIAL CIRCUITS.
MAXIMUM OF 16 CONDUCTORS IN A SINGLE RACEWAY. • FOR UP TO EIGHT
CONDUCTORS IN A RACEWAY, MINIMUM RACEWAY SIZE: 3/4 —INCH. FOR
GREATER THAN EIGHT CONDUCTORS, MINIMUM RACEWAY SIZE: 1 —INCH. DO
NOT INSTALL ANY OTHER TYPE OF CIRCUIT IN THIS RACEWAY.
THE MINIMUM WIRE SIZE FOR ALL CONDUCTORS IN THIS RACEWAY: NO. 10
AWG.
ONLY 15A AND 20A BRANCH CIRCUIT HOMERUNS MAY BE COMBINED INTO
ONE
RACEWAY.
GFCI CIRCUITS.
DO NOT USE MULTI — CONDUCTOR CIRCUITS, WITH A SHARED NEUTRAL, FOR
ANY GFCI CIRCUIT BREAKER OR RECEPTACLE CIRCUIT.
EMERGENCY POWER CIRCUITS — INCLUDES ALL CIRCUITS COVERED UNDER
ARTICLES 700, 701 AND 702.
ONE
MAXIMUM OF EIGHT CONDUCTORS IN A SINGLE RACEWAY. MINIMUM
RACEWAY SIZE: 3 /4— INCH. DO NOT INSTALL ANY OTHER TYPE OF CIRCUIT IN
THIS RACEWAY.
ONLY 15A AND 20A BRANCH CIRCUIT HOMERUNS MAY BE COMBINED INTO
RACEWAY.
FOR BRANCH CIRCUITS FED FROM GFCI CIRCUIT BREAKERS, LIMIT THE ONE —
WAY CONDUCTOR LENGTH TO 100 FEET BETWEEN THE PANELBOARD AND THE
MOST REMOTE RECEPTACLE OR LOAD ON THE GFCI CIRCUIT.
PROPERLY IDENTIFY ALL TERMINAL BLOCKS AND WIRE TERMINALS FOR
CONTROL WIRING WITH VINYL STICK —ON MARKERS OR EQUIVALENT. PROVIDE
ENGINEER WITH A LIST OF PROPOSED IDENTIFYING NUMBERS FOR REVIEW
PRIOR TO INSTALLING MARKERS.
PROVIDE AN EQUIPMENT — GROUNDING CONDUCTOR, OR BONDING JUMPER, AS
APPLICABLE, IN ALL FEEDERS AND BRANCH CIRCUITS, SIZED IN ACCORDANCE
WITH NFPA 70 TABLES 250.66 OR 250.122, AS APPLICABLE, UNLESS INDICATED AS
LARGER ON THE DRAWINGS.
WIRING SHALL HAVE INSULATION OF THE PROPER COLOR TO MATCH COLOR
CODE SYSTEM IN THE TABLE BELOW UNLESS THERE IS A COLOR SYSTEM
CURRENTLY IN USE BY THE FACILITY, IN WHICH CASE THE COLORS ARE TO
MATCH THE EXISTING SYSTEM. IN LARGER SIZES, WHERE PROPERLY COLORED
INSULATION IS NOT AVAILABLE, USE VINYL PLASTIC ELECTRICAL TAPE OF THE
APPROPRIATE COLOR AROUND EACH CONDUCTOR AT ALL TERMINATION
POINTS, JUNCTION AND PULL BOXES.
SYSTEM VOLTAGE
240V AND UNDER — 208Y/120, 120/240, 120/208, 240D/120
PHASE A — BLACK, PHASE B — RED, PHASE C — BLUE, NEUTRAL — WHITE,
EQUIPMENT GROUND GREEN, ISOLATED GROUND — GREEN W /YELLOW STRIPE.
480V AND 480Y/277V
PHASE A - BROWN, PHASE B — ORANGE, PHASE C — YELLOW, NEUTRAL — GRAY,
EQUIPMENT GROUND — GREEN.
USE OF MC CABLE
MAY ONLY BE USED:
IN LIEU OF FLEXIBLE CONDUIT AND WIRING FROM LIGHT FIXTURES IN
ACCESSIBLE CEILINGS TO JUNCTION BOXES (ATTACHED TO BUILDING
STRUCTURE) ABOVE THE CEILING. PROVIDE CABLE WHIPS OF SUFFICIENT
LENGTHS TO ALLOW FOR RELOCATING EACH LIGHT FIXTURE WITHIN A 5 -FOOT
RADIUS OF ITS INSTALLED LOCATION, BUT NOT EXCEEDING 6 FEET IN
UNSUPPORTED LENGTHS.
FOR VERTICAL DROPS IN STUD WALLS.
IN LIEU OF EMT, ONLY FOR 15A AND 20A BRANCH CIRCUITS (WITH UP TO FOUR
(4) CONDUCTORS, NOT INCLUDING GROUND CONDUCTOR), AND ONLY IN DRY
CONCEALED LOCATIONS ABOVE GRADE, EXCEPT WHERE SPECIFICALLY NOT
PERMITTED BY NFPA 70.
DO NOT USE FOR THE FOLLOWING:
HOMERUNS TO PANELBOARDS.
WHERE EXPOSED TO VIEW.
WHERE EXPOSED TO DAMAGE.
HAZARDOUS LOCATIONS.
WET LOCATIONS.
WHEN RESTRICTED OTHERWISE ABOVE, AND WHEN SPECIFICALLY DISALLOWED
BY THE LOCAL AHJ, LANDLORD, OR BOTH.
CIRCUITS THAT CAN BE SUPPLIED BY AN EMERGENCY OR STANDBY POWER
SOURCE.
16B 1 -6 JUNCTION BOXES. PULL BOXES. CABINETS AND WIREWAYS
PROVIDE JUNCTION BOXES, PULL BOXES, CABINETS AND WIREWAYS
WHEREVER NECESSARY FOR PROPER INSTALLATION OF VARIOUS ELECTRICAL
SYSTEMS ACCORDING TO NFPA 70 AND WHERE INDICATED ON THE DRAWINGS.
SIZE AS REQUIRED FOR THE SPECIFIC FUNCTION OR AS REQUIRED BY NFPA 70,
WHICHEVER IS LARGER. CONSTRUCTION SHALL BE OF A NEMA DESIGN
SUITABLE FOR THE ENVIRONMENT INSTALLED.
JUNCTION BOXES INSTALLED BEHIND WALL CASES, AND IN OR ON OTHER
STORE FIXTURES, EXCEPT WHERE OTHERWISE SPECIFIED, SHALL BE 4 —INCH
SQUARE OR LARGER, WITH GALVANIZED COVERS.
HORIZONTALLY MOUNT JUNCTION BOXES UNDER CENTER FIXTURES (AND
CASES), HANDY BOXES OR 4 —INCH SQUARE BOXES WITH TOPS OF BOXES NOT
MORE THAN 3 -1/2 INCHES ABOVE THE FLOOR. SIZE JUNCTION BOXES TO
ADEQUATELY CONTAIN ALL REQUIRED CONDUCTORS AND SPLICES.
16B 1 -7 OUTLET BOXES
ALL OUTLETS INCLUDING LIGHT FIXTURE, SWITCH, RECEPTACLE, AND SIMILAR
OUTLETS: NATIONAL ELECTRICAL, APPLETON, STEEL CITY, RACO, OR APPROVED
EQUAL, GALVANIZED STEEL KNOCKOUT BOXES, SUITABLE IN DESIGN TO THE
PURPOSE THEY SERVE AND THE SPACE THEY OCCUPY.
SIZE AS REQUIRED FOR
THE SPECIFIC FUNCTION OR AS REQUIRED BY NFPA 70, WHICHEVER IS LARGER.
SET ALL OUTLET BOXES IN WALLS, COLUMNS, FLOORS, OR CEILINGS SO THEY
ARE FLUSH WITH THE FINISHED SURFACE, ACCURATELY SET, AND RIGIDLY
SECURED IN POSITION. PROVIDE PLASTER RINGS, EXTENSION RINGS AND /OR
MASONRY RINGS AS REQUIRED FOR FLUSH MOUNTING. PROVIDE APPROVED
CAST OUTLET BOXES, WITH HUBS AND WEATHERPROOF COVERS, IN ALL AREAS
SUBJECT TO DAMP, WET, OR HARSH CONDITIONS.
16B 1 -8 OUTLET LOCATIONS
COORDINATE LOCATIONS OF OUTLET BOXES. OUTLETS ARE ONLY
APPROXIMATELY LOCATED ON THE SMALL SCALE DRAWINGS. USE GREAT
CARE IN THE ACTUAL LOCATION BY CONSULTING THE VARIOUS LARGE SCALE
DETAILED DRAWINGS USED BY OTHER DIVISION TRADES, AND BY SECURING
DEFINITE LOCATIONS FROM THE ARCHITECT.
16B 1 -9 MOUNTING HEIGHTS
UNLESS NOTED OTHERWISE, INSTALL WIRING DEVICES AS INDICATED BELOW
(NOTE: ALL DIMENSIONS ARE TO THE BOTTOM OF THE OUTLET BOX UNLESS
NOTED OTHERWISE):
RECEPTACLES:
VERTICALLY ALIGNED WITH THE GROUND SLOT MOUNTED AT THE TOP: 16
INCHES ABOVE FINISHED FLOOR.
HORIZONTALLY ALIGNED, WITH NEUTRAL SLOT MOUNTED AT THE TOP: 16
INCHES ABOVE FINISHED FLOOR.
FOR 36 —INCH HIGH COUNTER TOPS: 44 INCHES ABOVE FINISHED FLOOR,
VERTICALLY ALIGNED.
FOR 34 —INCH HIGH COUNTER TOPS: 40 INCHES ABOVE FINISHED FLOOR,
VERTICALLY ALIGNED.
MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS AND JANITORS CLOSETS: 44
INCHES ABOVE FINISHED FLOOR, VERTICALLY ALIGNED.
GARAGES: 24 INCHES ABOVE FINISHED FLOOR, VERTICALLY ALIGNED.
WEATHERPROOF EXTERIOR RECEPTACLES: 24 INCHES ABOVE FINISHED
GRADE, VERTICALLY ALIGNED.
GFCI RECEPTACLES: SAME AS GENERAL RECEPTACLES.
ISOLATED GROUND RECEPTACLES: SAME AS GENERAL RECEPTACLES.
SPD RECEPTACLES: SAME AS GENERAL RECEPTACLES.
CLOCK RECEPTACLES: 84 INCHES ABOVE FINISHED FLOOR.
CONCRETE BLOCK WALLS: DIMENSIONS ABOVE MAY BE ADJUSTED SLIGHTLY,
AS REQUIRED TO COMPENSATE FOR VARIABLE JOINT DIMENSIONS, SUCH THAT
BOTTOM OR TOP OF BOXES, AS APPLICABLE, ARE AT BLOCK JOINTS.
SWITCHES:
GENERAL: 46 INCHES ABOVE FINISHED FLOOR.
ABOVE COUNTERS: SAME AS FOR RECEPTACLES.
CONCRETE BLOCK WALLS: 40 INCHES ABOVE E FINISHED FLOOR (DIMENSION MAY
BE ADJUSTED SLIGHTLY AS JOINT
REQUIRED TO COMPENSATE FOR VARIABLE J
Q 0
DIMENSIONS, SUCH THAT BOTTOM OF BOXES ARE AT BLOCK JOINTS).
WALLS WITH WAINSCOTING: 6 INCHES MINIMUM ABOVE WAINSCOTING, BUT NOT
EXCEEDING 48 INCHES ABOVE FINISHED FLOOR.
TELEPHONE /DATA OUTLET BOXES:
GENERAL: MATCH MOUNTING HEIGHT OF ADJACENT WIRING DEVICE LISTED
ABOVE.
WALL — MOUNTED TELEPHONE: 40 INCHES ABOVE FINISHED FLOOR.
FOR OTHER THAN WIRING DEVICES, REFER TO PARAGRAPHS, ARTICLES,
SECTIONS, DIVISIONS, OR DRAWINGS TO OBTAIN MOUNTING HEIGHTS FOR
SPECIFIC EQUIPMENT OR SYSTEMS.
16B 1 -10 WIRING DEVICES
THE CATALOG NUMBERS LISTED FOR WIRING DEVICES ARE GENERALLY FOR
20A RATED DEVICES. WHERE 15A RATED DEVICES ARE INDICATED ON THE
DRAWINGS OR REQUIRED FOR CIRCUIT RATING LIMITATIONS, PROVIDE WIRING
DEVICES EQUIVALENT TO THOSE SPECIFIED FOR 20A, BUT RATED FOR 15A.
PROVIDE THE FOLLOWING WIRING DEVICES WHERE SHOWN ON DRAWINGS OR
REQUIRED. MINOR CHANGES RELATIVE TO THE LOCATION OF ELECTRICAL
EQUIPMENT MAY BE MADE TO COMPLY WITH STRUCTURAL AND BUILDING
REQUIREMENTS AS DETERMINED IN THE COURSE OF CONSTRUCTION.
PROVIDE ALL WIRING DEVICES OF THE SAME MANUFACTURER AND NOT MIXED
ON THE PROJECT, TO THE MAXIMUM EXTENT POSSIBLE. PROVIDE COLOR OF
TOGGLES AND RECEPTACLES AS REQUESTED BY THE ENGINEER: REFER TO
DETAIL SHOWING RECEPTACLES TABLE.
Type of Device
HutenU
Pass t
Seymour
Leeiton
Cooper M r g
Devices
Duplex Receptacle
CR5352
5362A
5352
5352Q
GFCI Receptacle
GF5352
2095
7899
VFG20B
Isolated Ground (IG)
Receptacle
IG5362
IG6300
8300 -01G
IG5362RN
Quad /4 —Plex
HBL 420
42Q8
21254
N/A
Single Pole Switch
CS1221
PS 20AC1
1221 -2
2221B
Double Pole Switch
CS1222
PS 20AC2
1222 -2
222R'
Three —way Switch
CS1223
PS 20AQ
1223 -2
22238
Pilot Light Switch
HBL1221PL
PS2OAC1 —RPL
1221 —PLR
1221 -7PR
2221 P1.
Key Switch
HBL1221I.
PS2OAC1 —l.
1221 -2L
2221L
Momentary SPDT,
Center —Off Switch
HBL 1557
12.5
1257
1995
Recessed Concealed Floor
Box — (1) Duplex,
(1) Tele /Data, Slab On
Grade
3SFBQ
Wiremold
RFB2 -0Q
Steel City
664 -CI
N/A
3SFBCBKA
3SFBRP
S38CCTCBI(
6R4— CST —CW —RI K
3SFBTP
RFB2DP
Rte@
664 —RP
664 —BP
Recessed Floor Box —
Furniture Feed Power and
Communication, Slab On
Grade
B423341
Wiremold
880CS2 -1
Steel City
17442.1
N/A
S2425
SB3084
829CK -1
8278
P 64 3/4 2
P 64 2G CP
Power Pole
HBLPPOAI
.
EMERGENCY SHUNT RELAY: UL LISTED TO STANDARD 924 AS EMERGENCY
LIGHTING AND POWER EQUIPMENT. CONNECT EMERGENCY SHUNT RELAY IN
PARALLEL WITH A WALL SWITCH. LOSS OF NORMAL POWER SHALL CAUSE
RELAY TO AUTOMATICALLY SHUNT EMERGENCY POWER TO LIGHTING CIRCUIT
REGARDLESS OF WALL SWITCH POSITION. EMERGENCY LIGHTING CIRCUIT
SHALL CONTINUE TO OPERATE AT FULL POWER UNTIL NORMAL POWER HAS
BEEN RESTORED. PROVIDE A TWO —GANG JUNCTION BOX WITH SEPARATION
BARRIER AND PLASTER RING FOR THE EMERGENCY. SHUNT RELAY, AND
INSTALL IT ADJACENT TO ITS ASSOCIATED LIGHT SWITCH. PROVIDE LIGHTING
CONTROLS AND DESIGN MODEL GR2001 E /S, EMERGENCY SHUNT RELAY, OR
EQUIVALENT BY BODINE .
16B 1 -11 SWITCH AND OUTLET COVER PLATES
SWITCH AND OUTLET PLATES:PER THE ARCHITECT; BY THE SAME
MANUFACTURER AS THE WIRING DEVICES, WHEREVER POSSIBLE. VERIFY
DESIRED MATERIALS AND COLORS WITH ARCHITECT BEFORE INSTALLATION.
SWITCH PLATES IN UNFINISHED ROOMS AND SPACES: STAMPED STEEL,
CADMIUM PLATED. INSTALL GROUPS OF SWITCHES UNDER ONE GANGED —
PLATE, USUALLY HORIZONTALLY; OR, WHERE REQUIRED BY DETAILS,
VERTICALLY. SET ALL COVER PLATES PLUMB, PARALLEL, AND FINISHED FLUSH
WITH THE WALL
16B 1 -12 WEATHERPROOF COVER PLATES
PROVIDE GFCI RECEPTACLES FOR DESIGNATED WEATHERPROOF
RECEPTACLES, UNLESS INDICATED OTHERWISE ON THE DRAWINGS.
FOR EXTERIOR UNATTENDED, WET LOCATIONS OR OTHER LOCATIONS AS
INDICATED: IN —USE NEMA 3R RECESSED OR FLUSH MOUNT, UL— LABELED PLATES
MOLDED FROM A CLEAR HIGH IMPACT ULTRAVIOLET STABILIZED
POLYCARBONATE MATERIAL FOR EASY VERIFICATION THAT CORDS ARE
PLUGGED IN AND THAT THE GFCI IS FUNCTIONING. BACK BOX MUST BE
SUITABLE FOR CONDUIT CONNECTING. COORDINATE BACK BOX WITH WALL
DEPTH. INTERMATIC WP1000RC /HRC OR EQUAL
FOR ATTENDED WET OR DAMP LOCATIONS: WEATHERPROOF COVER PLATES,
UL— LISTED FOR WET LOCATIONS WITH COVER(S) CLOSED; DIE —CAST ALUMINUM
OR TYPE 302 STAINLESS STEEL; SINGLE —COVER FOR SWITCHES AND
VERTICALLY MOUNTED RECEPTACLES; DOUBLE —COVER FOR HORIZONTALLY
MOUNTED RECEPTACLES; SELF — CLOSING COVERS.
COVER PLATES: BY THE SAME MANUFACTURER AS THE WIRING DEVICES;
COMPLYING WITH NFPA 70 406.8 (A) OR (B) REQUIREMENTS FOR ATTENDED OR
UNATTENDED USE AS APPLICABLE.
16B 2 ELECTRICAL SERVICE AND GROUNDING
16B 2 -1 ELECTRICAL SERVICE
SEE DRAWINGS FOR TYPE, SIZE, VOLTAGE, PHASE, AND OTHER
REQUIREMENTS.
PROVIDE, OR ARRANGE WITH THE SERVING UTILITY FOR INSTALLATION TO
PROVIDE, A RECORDING VOLTMETER AT THE SERVICE POINT, ON THE FIRST
DAY THE FACILITY IS OPEN FOR BUSINESS, FOR A 24 —HOUR VOLTAGE TEST. IF
VOLTAGE AND REGULATION ARE NOT WITHIN ACCEPTABLE LIMITS, ARRANGE
WITH THE UTILITY FOR PROPER VOLTAGE. SUBMIT TO THE OWNER A REPORT
OF MAXIMUM AND MINIMUM VOLTAGE AND A COPY OF THE RECORDING
VOLTMETER CHART.
16B 2 -2 CONNECTION TO SERVING UTILITIES
PROVIDE RACEWAYS, TERMINATIONS, METERING PROVISIONS, AND
MISCELLANEOUS EQUIPMENT, AS REQUIRED, FOR ELECTRICAL AND
TELEPHONE SERVICES FOR CONNECTION BY THE SERVING UTILITY, IN STRICT
COMPLIANCE WITH THE REQUIREMENTS OF ALL APPLICABLE CODES AND OF
THE SERVING UTILITY INVOLVED. VERIFY ALL SERVICE TERMINATIONS AND
CONNECTION POINTS IN THE FIELD AND WORK IN CONJUNCTION WITH THE
UTILITY INVOLVED IN THE INSTALLATION OF ALL SERVICES. PROVIDE ALL
MATERIALS AND EQUIPMENT REQUIRED FOR COMPLETE UTILITY CONNECTION
BUT NOT FURNISHED BY THE SERVING UTILITY. NOTIFY THE UTILITY
COMPANIES INVOLVED WITHIN TWO WEEKS AFTER NOTICE TO PROCEED, OF
ALL REQUIRED INFORMATION NECESSARY FOR THE UTILITY TO SUPPLY THE
PROJECT WITHOUT DELAY. PAY ALL CHARGES OF THE SERVING UTILITY FOR
THE ELECTRICAL SERVICE(S).
16B 2 -3 GROUNDING
PERMANENTLY AND EFFECTIVELY GROUND AND BOND THE ELECTRICAL
INSTALLATION IN A THOROUGH AND EFFICIENT MANNER, AND IN
CONFORMANCE, AT A MINIMUM, WITH NFPA 70, OR THESE DOCUMENTS, WHERE
THEY EXCEED CODE REQUIREMENTS. USE BARE OR INSULATED CONDUCTORS,
AS SPECIFIED HEREIN, AND OTHER MATERIALS INDICATED ON THE DRAWINGS.
16B 3 DISTRIBUTION AND CONTROL EQUIPMENT
16B 3 -1 SERVICE ENTRANCE AND POWER DISTRIBUTION SWITCHBOARDS —
1600A AND LARGER
SERVICE ENTRANCE AND POWER DISTRIBUTION SWITCHBOARDS:
1. CONFORM WITH THE REQUIREMENTS OF THE LOCAL CODES AND SERVING
UTILITY; MANUFACTURED ACCORDING TO CURRENT REQUIREMENTS OF UL 891,
"DEADFRONT SWITCHBOARDS "; UL— LISTED AND PERMANENTLY LABELED FOR
SERVICE ENTRANCE USE WHEN APPLICABLE; SHORT CIRCUIT INTERRUPTING
AND BRACING RATING AS SHOWN ON THE DRAWINGS.
2. MAIN CIRCUIT BREAKER AND FEEDER CIRCUIT BREAKERS AS INDICATED ON
THE DRAWINGS.
3. INTEGRAL GROUND FAULT RELAYS AND OPERATORS, SELF — POWERED, WHERE
INDICATED OR REQUIRED BY NFPA 70.
4. CONTAINED IN A SINGLE FACTORY— ASSEMBLED DEAD —FRONT ENCLOSURE WITH
FRONT ACCESSIBLE CONNECTIONS TO INCOMING MAINS AND OUTGOING
FEEDER CIRCUIT BREAKERS.
5. MANUFACTURER: SQUARE D QED TYPE OR APPROVED EQUAL BY GENERAL
ELECTRIC, SIEMENS OR CUTLER — HAMMER.
CIRCUIT BREAKERS: BOLT —ON, THERMAL MAGNETIC, "QUICK MAKE —QUICK
BREAK" TYPE; TOGGLE SWITCHING MECHANISM TO PROVIDE MANUAL AND
AUTOMATIC OPERATION; AND AUTOMATIC TRIPPING CLEARLY INDICATED BY A
NEUTRAL HANDLE POSITION IN— BETWEEN THE "ON" AND "OFF" POSITIONS.
FUSED SWITCHES: QUICK —MAKE, QUICK — BREAK, AND FUSIBLE; FUSE CLIPS OR
PROVISIONS FOR BOLT —IN FUSES AS APPROPRIATE FOR THE FUSES SPECIFIED;
INTERLOCKED COVERS AND A CARD HOLDER FOR CIRCUIT IDENTIFICATION.
16B 3 -2 SERVICE ENTRANCE SWITCH — FUSIBLE. 400A — 4000A
FUSIBLE SWITCH: SQUARE D TYPE BP BOLT —LOC OR EQUIVALENT BY SIEMENS,
CUTLER — HAMMER, OR GENERAL ELECTRIC; NUMBER OF PHASES AND RATINGS
OF SWITCH AND FUSES AS INDICATED ON THE DRAWINGS; PERMANENTLY
LABELED AS SUITABLE FOR USE AS SERVICE ENTRANCE EQUIPMENT; INTEGRAL
GROUND FAULT RELAY AND OPERATOR WHERE INDICATED OR REQUIRED BY
NFPA 70; PROVISIONS FOR BOLT —IN FUSES AS APPROPRIATE FOR THE FUSES
SPECIFIED; INTERLOCKED COVER AND AN ENGRAVED NAMEPLATE FOR
IDENTIFICATION. PROVIDE WITH INTEGRAL AND SEPARATE NEUTRAL AND
GROUND ASSEMBLIES, SUITABLE FOR THE SIZES OF CONDUCTORS INDICATED.
DO NOT DOUBLE —LUG ANY TERMINATIONS NOT SPECIFICALLY LISTED AS
SUITABLE FOR MORE THAN ONE CONDUCTOR. ENCLOSURE: FREE — STANDING
SWITCHBOARD SECTION OF NEMA DESIGN SUITABLE FOR THE ENVIRONMENT IN
WHICH INSTALLED OR AS INDICATED.
16B 3 -3 POWER DISTRIBUTION PANELBOARDS — FUSIBLE. 1600A BUS OR
SMALLER
PANELBOARDS: SQUARE D TYPE QMB, OR EQUAL BY SIEMENS, CUTLER—
HAMMER, OR GENERAL ELECTRIC; FUSIBLE TYPE DEAD FRONT DISTRIBUTION
PANELBOARDS WITH NUMBER AND SIZES OF SWITCHES AND FUSES AS
INDICATED ON THE DRAWINGS; WHERE INSTALLED AS SERVICE ENTRANCE
EQUIPMENT, LA
PERMANENTLY BEL AS SUITABLE FOR USE AS SERVICE
ENTRANCE EQUIPMENT; BRACED FOR AVAILABLE FAULT CURRENT (MINIMUM
75,000A). FUSED SWITCHES: QUICK —MAKE, QUICK — BREAK, WITH FUSE CLIPS OR
PROVISIONS FOR BOLT —IN FUSES AS APPROPRIATE FOR THE FUSES SPECIFIED;
INTERLOCKED COVERS AND ENGRAVED NAMEPLATES FOR CIRCUIT
IDENTIFICATION OF EACH SWITCH.
16B 3 -4 LIGHTING AND APPLIANCE PANELBOARDS
PANELBOARDS: SQUARE D TYPE NQOD OR NF, AS APPLICABLE, BASED ON
VOLTAGE AND AMPERE RATINGS AND REQUIRED SHORT— CIRCUIT
INTERRUPTING RATINGS AS SCHEDULED ON THE DRAWINGS, OR APPROVED
EQUAL BY SIEMENS, CUTLER HAMMER, OR GENERAL ELECTRIC; COMPLETE
WITH BOLT —ON THERMAL MAGNETIC, MOLDED CASE CIRCUIT BREAKERS
ASSEMBLED IN A DEAD —FRONT FINISHED CABINET CONTAINING A TYPEWRITTEN
CARD DIRECTORY INDICATING EXACTLY WHAT EACH CIRCUIT BREAKER
CONTROLS; FULLYRATED AND WITH THE INTEGRATED SHORT CIRCUIT
CURRENT RATINGS INDICATED ON THE DRAWINGS. PLUG —IN. TYPE BREAKERS
WILL NOT BE ACCEPTABLE. ALL TWO AND THREE POLE BREAKERS: COMMON
TRIP TYPE. BREAKERS USED AS SWITCHES FOR 120V OR 277V LIGHTING
CIRCUITS: APPROVED FOR THE PURPOSE AND MARKED "SWD ". BREAKERS
USED FOR THE PROTECTION OF HVAC AND REFRIGERATION EQUIPMENT: HACR
TYPE.
16B 3 -5 CIRCUIT BREAKERS IN EXISTING PANELBOARDS
PROVIDE NEW CIRCUIT BREAKERS, FOR INSTALLATION IN EXISTING
PANELBOARDS , OF THE SAME MANUFACTURER, TYPE AND SHORT CIRCUIT
CURRENT INTERRUPTING RATINGS AS THE EXISTING PANELBOARD CIRCUIT
BREAKERS.
WHEN THERE IS NOT ENOUGH ROOM IN THE EQUIPMENT TO SHOW ALL THE
LEGITIMATE SERIES RATED COMBINATIONS, REFERENCE A BULLETIN SUPPLIED
WITH THE PANELBOARD, PER UL 67.
SERIES RATINGS SHALL COVER ALL TRIP RATINGS OF INSTALLED FRAMES.
16B 3 -6 DISCONNECT (SAFETY) SWITCHES
DISCONNECT (SAFETY) SWITCHES: SQUARE D, SIEMENS, CUTLER HAMMER, OR
GENERAL ELECTRIC FUSED OR NON —FUSED (AS INDICATED ON DRAWINGS OR
REQUIRED) NEMA KS1, HEAVY DUTY, EXTERNALLY OPERATED, VISIBLE —BLADE
SAFETY SWITCHES; NEMA ENCLOSURE TYPE INDICATED ON THE DRAWINGS OR
SUITABLE FOR THE ENVIRONMENT IN WHICH INSTALLED. BASED ON FUSIBLE
SWITCH AND FUSE SIZES INDICATED, INCLUDE CLASS R, J, OR L FUSE
PROVISIONS AS APPLICABLE.
WHERE INDICATED, PROVIDE FUSIBLE SWITCHES PERMANENTLY LABELED AS
SUITABLE FOR USE AS SERVICE ENTRANCE EQUIPMENT, WITH INTEGRAL AND
SEPARATE NEUTRAL AND GROUND ASSEMBLIES, SUITABLE FOR THE SIZES OF
CONDUCTORS INDICATED. DO NOT DOUBLE —LUG ANY TERMINATIONS NOT
SPECIFICALLY LISTED AS SUITABLE FOR MORE THAN ONE CONDUCTOR.
PROVIDE SWITCHES WHERE NOT FURNISHED WITH THE STARTING EQUIPMENT,
AT ALL OTHER POINTS REQUIRED BY NFPA 70, AND WHERE INDICATED ON THE
DRAWINGS.
16B 3 -7 FUSES
PROVIDE EACH CIRCUIT AND SET OF FUSE CLIPS THROUGHOUT THE WORK
WITH BUSSMANN, FERRAZ SHAWMUT, OR LITTLEFUSE FUSES, SIZES AND TYPES
AS REQUIRED OR INDICATED. ALL FUSES LARGER THAN 600A: UL CLASS L,
SIMILAR TO TYPE KRP —C BUSSMANN LOW PEAK OR EQUAL FUSES USED TO
PROTECT MOTORS: UL CLASS RK5, BUSSMANN FUSETRON OR EQUAL FUSES
USED TO PROTECT ALL OTHER ELECTRICAL EQUIPMENT: UL CLASS RK1, DUAL
ELEMENT, BUSSMANN LPS /LPN OR EQUAL ALL FUSED DEVICES SHALL BE
LABELED AS TO TYPE AND SIZE OF FUSE REQUIRED.
FURNISH THREE SPARE FUSES OF EACH SIZE AND TYPE USED ON THE PROJECT
(EXCEPT FOR MAIN SWITCH FUSES, FURNISH ONE SPARE), NEATLY CONTAINED
IN A PROPERLY LABELED CABINET.
16B 3 -8 DRY —TYPE TRANSFORMERS
TRANSFORMERS: GENERAL PURPOSE, UL— LISTED /LABELED. COMPLY WITH
NEMA ST -020 STANDARDS.
INSULATION CLASS: FOR THREE PHASE TRANSFORMERS LESS THAN 15 KVA
AND ALL SINGLE PHASE — 185 DEGREES C, UL— COMPONENT — RECOGNIZED
INSULATION SYSTEM WITH A MAXIMUM OF 115 DEGREE C RISE ABOVE A 40
DEGREE C AMBIENT TEMPERATURE; FOR THREE PHASE TRANSFORMERS 15
KVA AND LARGER — 220 DEGREES C, UL— COMPONENT — RECOGNIZED INSULATION
SYSTEM WITH A MAXIMUM OF 150 DEGREE C RISE ABOVE A 40 DEGREE C
AMBIENT TEMPERATURE. UL— COMPONENT — RECOGNIZED INSULATION SYSTEM
REPLACES THE UL1446 INSULATION RATING SYSTEM THAT USED LETTERS.
PHASES, VOLTAGES, AND SIZES: AS INDICATED ON THE DRAWINGS.
SOUND LEVEL: NOT EXCEEDING NEMA STANDARDS FOR THE SIZES INDICATED.
FULL — CAPACITY PRIMARY TAPS: BELOW 25 KVA —ONE 5 PERCENT TAP ABOVE
AND ONE 5 PERCENT TAP BELOW; 25 KVA TO 500 KVA — SIX 2.5 PERCENT TAPS
ABOVE, 4 BELOW); ABOVE 500 KVA — FOUR 2.5 PERCENT (2 ABOVE, 2 BELOW).
TRANSFORMER CORE AND COIL ASSEMBLIES: MOUNTED ON INTEGRAL
VIBRATION— ABSORBING PADS.
TRANSFORMERS 75 KVA AND LARGER SHALL BE FLOOR MOUNTED UNLESS
INDICATED OTHERWISE. TRANSFORMERS 45 KVA AND SMALLER MAY BE WALL
MOUNTED WHERE WALL CONSTRUCTION IS SUITABLE FOR THE LOAD. FLOOR
MOUNTED TRANSFORMERS SHALL BE SECURELY BOLTED TO A 4 INCH HOUSE
KEEPING PAD WITH VIBRATION ISOLATION PADS. WALL MOUNTED OR
SUSPENDED TRANSFORMERS SHALL HAVE A MEANS OF ISOLATING VIBRATION
FROM THE SUPPORT.
TRANSFORMERS UP THROUGH 1000 KVA SHALL BE MOUNTED ON ELASTOMERIC
VIBRATION ISOLATION PADS. PAD SHALL BE CONSTRUCTED OF NEOPRENE,
RUBBER, GLASS FIBER, OR A COMBINATION THEREOF. PADS SHALL BE "RIBBED"
OR "WAFFLED" IN TEXTURE. PADS SHALL BE SELECTED FOR SMALLEST
DUROMETER (HARDNESS), PREFERABLY LESS THAN 50. DEFLECTION OF PAD
SHALL BE .25" STATIC MINIMUM. STACK PADS UNTIL THE DESIRED DEFLECTION
IS ACHIEVED.
MAKE FINAL CONDUIT CONNECTIONS TO TRANSFORMERS WITH FLEXIBLE
CONDUIT, WITH AT LEAST 6 INCHES OF SLACK IN ALL DIRECTIONS.
TRANSFORMER ENCLOSURES: FULLY ENCLOSED (EXCEPT FOR VENTILATION
OPENINGS), NEMA 2, DRIP — PROOF, FABRICATED OF HEAVY GAUGE SHEET STEEL
CONSTRUCTION
PROVIDE ENERGY — EFFICIENT TRANSFORMERS COMPLYING WITH NEMA TP -1,
WHEN TESTED IN ACCORDANCE WITH NEMA TP -2.
K —RATED TRANSFORMERS SHALL BE PROVIDED AS INDICATED ON THE
DRAWINGS AND BE LISTED FOR 115 DEGREE C RISE.
MANUFACTURERS: SQUARE D, CUTLER HAMMER, GENERAL ELECTRIC,
HAMMOND, ACME OR SIEMENS
16B 4 LIGHT FIXTURES. LAMPS AND BALLASTS
16B 4 -1 LIGHT FIXTURE LOCATIONS
LIGHT FIXTURES SHOWN ON THE ELECTRICAL DRAWINGS REPRESENT GENERAL
ARRANGEMENTS ONLY. REFER TO ARCHITECTURAL DRAWINGS FOR MORE
EXACT LOCATIONS. COORDINATE LOCATION WITH ALL OTHER TRADES BEFORE
INSTALLATION TO AVOID CONFLICTS. COORDINATE LIGHT FIXTURE LOCATIONS
IN MECHANICAL ROOMS WITH FINAL INSTALLED PIPING AND DUCTWORK
LAYOUTS.
16B 4 -2 LIGHT FIXTURES
PROVIDE UGHT FIXTURES AS SCHEDULED ON DRAWINGS, INCLUDING ALL
LAMPS, ALL NECESSARY ACCESSORIES, MATERIAL AND LABOR TO SECURELY
HANG, CLEAN, AND MAKE LIGHT FIXTURES COMPLETELY READY FOR USE.
UGHT FIXTURE MODEL NUMBERS SCHEDULED ON THE DRAWINGS SHOW ONLY
THE MANUFACTURER, GRADE AND STYLE OF LIGHT FIXTURES REQUIRED.
PROVIDE: ALL HANGERS, SUPPORTS, AND MISCELLANEOUS HARDWARE
REQUIRED TO INSTALL LIGHT FIXTURES; PROPER TRIM TO FIT EACH CEILING
CONDITION ACTUALLY ENCOUNTERED; ADDITIONAL TIE WIRES CONNECTED TO
STRUCTURE TO CONFORM TO SEISMIC REQUIREMENTS WHERE REQUIRED BY
THE APPLICABLE BUILDING CODE.
PACKAGING OF LIGHT FIXTURES WILL NOT BE ALLOWED. ONLY THOSE
LUMINARES LISTED IN THE LIGHT FIXTURE SCHEDULE, OR APPROVED IN
ACCORDANCE WITH SUBSTITUTIONS OF THESE SPECIFICATIONS, WILL BE
ACCEPTED. WHERE THE LIGHT FIXTURE SCHEDULE INDICATES AN ALLOWANCE
FOR A SPECIFIC LIGHT FIXTURE, THE PRICE IS A CONTRACTOR PRICE. INCLUDE
ALL ADDITIONAL COSTS FOR FREIGHT, LAMPS, AND INSTALLATION OF LIGHT
FIXTURE AND LAMPS.
SURFACE —MOUNT ALL FLUORESCENT LIGHT FIXTURES LOCATED IN AREAS
WITHOUT SUSPENDED CEILINGS UNLESS OTHERWISE INDICATED ON THE
DRAWINGS. PROVIDE RIGID METAL SPACERS FINISHED IN WHITE ENAMEL
BETWEEN THE TOP OF EACH LIGHT FIXTURE AND THE CEILING ABOVE TO
MAINTAIN A 1-1/2—INCH SPACE. SPACERS SHALL BE APPROVED BEFORE
INSTALLATION.
INSTALL FLUORESCENT LIGHT FIXTURES HUNG IN CONTINUOUS ROWS ON
CHANNEL STRUTS SPECIFICALLY DESIGNED FOR THIS PURPOSE.
INSTALL ALL FLUORESCENT LIGHT FIXTURES LOCATED IN AREAS WITHOUT
CEILINGS IMMEDIATELY BELOW THE ROOF— FRAMING MEMBERS, OR
SUSPENDED FROM CHAIN HANGERS SUITABLE IN LENGTH TO PROVIDE THE
INDICATED MOUNTING HEIGHT. HANGERS: "HYDEE" HANGER TYPE FOR OUTLET
BOX MOUNTING, COMPLETE WITH GROUNDING RECEPTACLE, PLUG, 3 —WIRE
CORD AND NECESSARY CHAIN.
THROUGH WIRING OF RECESSED LIGHT FIXTURES, IN SUSPENDED CEILINGS, IS
NOT PERMITTED. CONNECT EACH LIGHT FIXTURE BY A WHIP TO A JUNCTION
BOX. PROVIDE CABLE WHIPS OF SUFFICIENT LENGTHS TO ALLOW FOR
RELOCATING EACH LIGHT FIXTURE WITHIN A 5 —FOOT RADIUS OF ITS INSTALLED
LOCATION, BUT NOT EXCEEDING 6 FEET IN UNSUPPORTED LENGTHS.
16B 4 -3 EMERGENCY LIGHTING UNITS AND EXIT SIGNS
DESCRIPTION: SELF — CONTAINED UNITS COMPLYING WITH UL 924.
BATTERY: SEALED, MAINTENANCE — FREE, LEAD —ACID TYPE. THE BATTERIES
SHALL BE OF SUITABLE RATING AND CAPACITY TO SUPPLY AND MAINTAIN AT
NOT LESS THAN 87 1/ 2 PERCENT OF THE NOMINAL BATTERY VOLTAGE FOR THE
TOTAL LAMP LOAD ASSOCIATED WITH THE UNIT FOR A PERIOD OF AT LEAST 1 1/
2 HOURS, OR THE UNIT EQUIPMENT SHALL SUPPLY AND MAINTAIN NOT LESS
THAN 60 PERCENT OF THE INITIAL EMERGENCY ILLUMINATION FOR A PERIOD OF
AT LEAST 1 1/ 2 HOURS.
CHARGER: FULLY AUTOMATIC, SOLID —STATE TYPE WITH SEALED TRANSFER
RELAY.
OPERATION: RELAY AUTOMATICALLY TURNS LAMP ON WHEN POWER SUPPLY
CIRCUIT VOLTAGE DROPS TO 80 PERCENT OF NOMINAL VOLTAGE OR BELOW.
LAMP AUTOMATICALLY DISCONNECTS FROM BATTERY WHEN VOLTAGE
APPROACHES DEEP — DISCHARGE LEVEL. WHEN NORMAL VOLTAGE IS
RESTORED, RELAY DISCONNECTS LAMPS FROM BATTERY, AND BATTERY IS
AUTOMATICALLY RECHARGED AND FLOATED ON CHARGER.
TEST PUSH BUTTON: PUSH —TO —TEST TYPE, IN UNIT HOUSING, SIMULATES LOSS
OF NORMAL POWER AND DEMONSTRATES UNIT OPERABILITY.
LED INDICATOR LIGHT: INDICATES NORMAL POWER ON. NORMAL GLOW
INDICATES TRICKLE CHARGE; BRIGHT GLOW INDICATES CHARGING AT END OF
DISCHARGE CYCLE.
INTEGRAL TIME —DELAY RELAY: HOLDS UNIT ON FOR FIXED INTERVAL OF
15MINUTES WHEN POWER IS RESTORED AFTER AN OUTAGE.
equipment
power
REMOTE TEST: SWITCH IN HAND —HELD REMOTE DEVICE AIMED IN DIRECTION
OF TESTED UNIT INITIATES CODED INFRARED SIGNAL. SIGNAL RECEPTION BY
FACTORY— INSTALLED INFRARED RECEIVER IN TESTED UNIT TRIGGERS
SIMULATION OF LOSS OF ITS NORMAL POWER SUPPLY, PROVIDING VISUAL
CONFIRMATION OF EITHER PROPER OR FAILED EMERGENCY RESPONSE.
required
INTEGRAL SELF —TEST: FACTORY— INSTALLED ELECTRONIC DEVICE
AUTOMATICALLY INITIATES CODE— REQUIRED TEST OF UNIT EMERGENCY
OPERATION AT REQUIRED INTERVALS. TEST FAILURE IS ANNUNCIATED BY AN
INTEGRAL AUDIBLE ALARM AND FLASHING RED LED.
16B 4 -4 LAMPS
PROVIDE LAMPS AS INDICATED ON THE DRAWINGS FOR ALL LIGHT FIXTURES;
OR, IF NOT INDICATED, AS RECOMMENDED BY THE LIGHT FIXTURE
MANUFACTURER. IN ALL CASES, LAMPS SHALL BE COMPATIBLE WITH THE
SPECIFIED LIGHT FIXTURE. ACCEPTABLE LAMP MANUFACTURERS: GENERAL
ELECTRIC, OSRAM /SYLVANIA, PHILIPS, OR VENTURE.
ALL FLUORESCENT LAMPS SHALL BE MINIMUM OF 3500 DEGREES K, WITH A
MINIMUM COLOR— RENDERING INDEX OF 70, UNLESS NOTED OR DIRECTED
OTHERWISE. ALL FLUORESCENT LAMPS IN SALES AREAS SHALL BE 3000
DEGREES K WITH A COLOR— RENDERING INDEX OF 80. ALL METAL HALIDE LAMPS
IN SALES AREAS SHALL BE COATED, 3000 DEGREES K WITH A COLOR —
RENDERING INDEX OF 70.
INCANDESCENT LAMPS: TYPE AND WATTAGE AS SHOWN ON THE DRAWINGS;
RATED 130V UNLESS OTHERWISE SCHEDULED OR SPECIFIED.
16B 4 -5 BALLASTS
FLUORESCENT BALLASTS: LOW HEAT TYPE; THERMALLY PROTECTED AGAINST
OVERHEATING; ETL —CBM, CLASS P TO MEET ALL REQUIREMENTS OF SECTION
410 -73 (E) OF THE NFPA 70 AS A MINIMUM; COMPLY WITH THE NATIONAL BALLAST
ENERGY LAW; 90— PERCENT POWER FACTOR OR GREATER; SOUND LEVELS NOT
EXCEEDING CLASS A AMBIENT NOISE LEVELS. BALLASTS IN INDOOR LOCATIONS
SHALL HAVE DISCONNECTING MEANS EITHER INTERNAL OR EXTERNAL TO THE
LUMINAIRE.
INDOOR FLUORESCENT BALLASTS: ELECTRONIC TYPE SUITABLE FOR
OPERATION OF T8 LAMPS; TOTAL HARMONIC DISTORTION LESS THAN 20
PERCENT; FREQUENCY OF OPERATION OF 20 KHZ OR GREATER WITH NO
VISIBLE FLICKER; LINE TRANSIENT WITHSTAND RATINGS AS DEFINED IN
ANSI /IEEE C62.41, CATEGORY A; MANUFACTURERS: ADVANCE REL /VEL SERIES
OR APPROVED EQUAL BY MAGNETEK, MOTOROLA, OR OSRAM.
EXTERIOR AND LOW TEMPERATURE FLUORESCENT BALLASTS: SHALL BE
ELECTRONIC TYPE SUITABLE FOR OPERATION OF F72T12/HO AND F96T12/HO
LAMPS; SHALL HAVE A TOTAL HARMONIC DISTORTION LESS THAN 20 PERCENT;
SHALL HAVE A FREQUENCY OF OPERATION OF 20 KHZ OR GREATER AND
OPERATE WITH NO VISIBLE FLICKER; SHALL WITHSTAND LINE TRANSIENTS AS.
DEFINED IN ANSI /IEEE C62.41, CATEGORY A; SHALL HAVE A MINIMUM STARTING
TEMPERATURE OF —20 DEGREES F; AND SHALL BE ADVANCE REL/VEL SERIES
OR EQUAL OF MAGNETEK OR MOTOROLA.
EXTERIOR AND LOW TEMPERATURE FLUORESCENT BALLASTS: SHALL BE
MAGNETIC TYPE SUITABLE FOR OPERATION OF T12 LAMPS; SHALL HAVE A
MINIMUM STARTING TEMPERATURE OF 0 DEGREES F FOR RAPID START LAMPS
AND A MINIMUM STARTING TEMPERATURE OF —20 DEGREES F FOR 800MA AND
1500MA LAMPS; AND SHALL BE ADVANCE REL SERIES OR EQUAL OF MAGNETEK.
COMPACT FLUORESCENT BALLASTS: SHALL BE THERMALLY PROTECTED
AGAINST OVERHEATING; SHALL BE CLASS P; SHALL HAVE A MINIMUM 90
PERCENT POWER FACTOR; SOUND LEVELS SHALL NOT EXCEED CLASS A
AMBIENT NOISE LEVELS; AND SHALL BE LOW HEAT TYPE. ALL BALLASTS SHALL
BE BY ADVANCE. BALLASTS FOR 36W THRU 55W LAMPS SHALL BE MARK V
ELECTRONIC TYPE.
(2 HIGH — INTENSITY DISCHARGE (HID) BALLASTS (INCLUDES HIGH PRESSURE
SODIUM (HPS) AND METAL HALIDE (MH)): SHALL HAVE A POWER FACTOR
GREATER THAN 90 PERCENT; COMPLY WITH UNDERWRITERS LABORATORY (UL)
1029; PROVIDE NORMAL OPERATION AND LIGHT OUTPUT WITH THE INPUT
VOLTAGE IS WITHIN ±10 PERCENT OF NOMINAL BALLAST RATING (EXCEPT
HPS LAMPS SMALLER THAN 250W WHICH MUST HAVE THE INPUT VOLTAGE
WITHIN +5 PERCENT); SHALL HAVE A MINIMUM STARTING TEMPERATURE OF —20
DEGREES F. PROVIDE ENCAPSULATED AND REMOTE TYPES WHERE INDICATED
ON THE DRAWINGS.
EMERGENCY FLUORESCENT BALLASTS: SHALL BE BODINE B50 OR IOTA 1 -232
FOR FOUR —FOOT FLUORESCENT LAMPS; SHALL BE BODINE B30 OR IOTA 1 -160
FOR EIGHT —FOOT FLUORESCENT LAMPS; OR AS NOTED ON THE FIXTURE
SCHEDULE OR ELSEWHERE ON THE DRAWINGS.
16B 5 MISCELLANEOUS ELECTRICAL
16B 5 -1 WIRING OF MECHANICAL EQUIPMENT
PROVIDE ALL RACEWAYS AND POWER WIRING FOR ALL DIVISION 15 EQUIPMENT
REQUIRING ELECTRICAL CONNECTIONS, INCLUDING, BUT NOT LIMITED TO,
PUMPS, WATER HEATERS, AND HVAC EQUIPMENT, AND ALL LINE — VOLTAGE
CONTROL AND INTERLOCK WIRING NOT PROVIDED UNDER DIVISION 15.
CONNECT PER MANUFACTURERS' WIRING DIAGRAMS. COORDINATE WITH
DIVISION 15 FOR DISCONNECTS FURNISHED WITH EQUIPMENT, AND PROVIDE
ALL DISCONNECT SWITCHES AS REQUIRED. AFTER INSTALLING WIRING, VERIFY
THAT EACH MOTOR LOAD HAS THE CORRECT PHASE ROTATION.
VERIFY THE ACTUAL "MAXIMUM OVERCURRENT PROTECTION" (MOCP) DEVICE
RATINGS AND "MINIMUM CIRCUIT AMPACITY" (MCA) CONDUCTOR SIZING FOR
MECHANICAL EQUIPMENT FROM THE EQUIPMENT NAMEPLATE. BASE
ELECTRICAL INSTALLATIONS ON ACTUAL REQUIRED AMPERAGES, WHICH MAY
VARY SOMEWHAT FROM THE CONDUCTOR AND EQUIPMENT SIZES SHOWN ON
THE DRAWINGS; HOWEVER, IN NO CASE, REDUCE THE SIZE OF CONDUCTORS
INDICATED ON THE DRAWINGS WITHOUT AUTHORIZATION FROM THE ENGINEER.
PROVIDE PROPERLY SIZED ELECTRICAL WIRING AND EQUIPMENT WITHOUT
EXTRA COST TO THE OWNER. NOTIFY THE ENGINEER OF ALL CHANGES
REQUIRED IN THE ELECTRICAL INSTALLATION DUE TO EQUIPMENT VARIANCES
SO THAT THE EFFECTS ON FEEDERS, BRANCH CIRCUITS, PANELBOARDS, FUSES
AND CIRCUIT BREAKERS CAN BE CHECKED PRIOR TO PURCHASING AND
INSTALLATION. BE RESPONSIBLE FOR COORDINATING WITH DIVISION 15 TO
VERIFY THE ACTUAL AMPACITIES AND CORRECT SIZES OF ALL CONDUCTORS
AND OVERCURRENT PROTECTIVE DEVICES FOR ALL EQUIPMENT, AND
CORRECT OVERLOAD HEATERS FOR ALL MOTORS, WHEN STARTERS ARE
PROVIDED UNDER DIVISION 16.
16B 5 -2 WIRING OF THERMOSTATS. TIME AND TEMPERATURE
CONTROLS
PROVIDE ALL RACEWAYS, POWER WIRING, AND UNE— VOLTAGE CONTROL AND
INTERLOCK WIRING NOT PROVIDED UNDER DMSION 15, FOR ALL
THERMOSTATS, TEMPERATURE CONTROL DEVICES, AND CONTROLS,
INCLUDING, BUT NOT LIMITED TO, NIGHT — STATS, WATER HEATER INTERLOCKS,
TIME SWITCHES AND OVERRIDE TIMERS. SEE MECHANICAL DRAWINGS FOR
LOCATIONS AND TEMPERATURE CONTROL DIAGRAMS. LOW— VOLTAGE
CONDUCTORS FOR THERMOSTATS AND TEMPERATURE CONTROL SYSTEM MAY
BE RUN EXPOSED ABOVE FINISHED ACCESSIBLE CEILINGS, IF APPROVED AND
LISTED FOR THIS PURPOSE, BUT SHALL BE INSTALLED IN CONDUIT WITHIN
WALLS AND WHERE EXPOSED IN THE WORK AREAS.
16B 5 -3 TELEPHONE SYSTEM PROVISIONS
PROVIDE INCOMING TELEPHONE SERVICE RACEWAYS AS INDICATED ON
DRAWINGS OR AS REQUIRED BY THE SERVING TELEPHONE COMPANY.
PROVIDE 3/4 —INCH THICK PLYWOOD BOARD, FIRE — RETARDANT — TREATED AND
STAMPED FRT, SECURELY ANCHORED TO THE WALL, AT THE LOCATION AND OF
THE SIZE AS INDICATED ON THE DRAWINGS. PROVIDE FLUSH MOUNTED
TELEPHONE OUTLET BOXES WITH 3/4 —INCH EMT STUB —UP CONCEALED TO
ACCESSIBLE CEILING SPACE AT LOCATIONS AS INDICATED ON THE DRAWINGS.
16B 5 -4 DATA SYSTEM PROVISIONS
PROVIDE FLUSH MOUNTED DATA OUTLET BOXES WITH 3/4 —INCH CONDUIT STUB —
UP CONCEALED TO ACCESSIBLE CEILING SPACE AT LOCATIONS AS INDICATED
ON THE DRAWINGS.
16B 5 -5 TIME SWITCHES
TIME SWITCHES: ELECTRONIC DIGITAL TYPE AS INDICATED, WITH MANUAL
BYPASS SWITCH, NEMA ENCLOSURE SUITABLE FOR THE ENVIRONMENT
INSTALLED; NUMBER AND TYPES OF CONTACTS, SEQUENCE, AND VOLTAGE AS
INDICATED ON THE DRAWINGS, OR AS REQUIRED, BASED ON THE TIME SWITCH
FUNCTION AND THE NUMBER OF BRANCH CIRCUITS OR CONTACTORS
CONTROLLED. PROVIDE WIRING TO PHOTOCELLS, CONTACTORS, RELAYS OR
OTHER CONTROL POINTS AS REQUIRED. MANUFACTURERS: INTERMATIC,
PARAGON OR TORK.
16B 5 -6 PHOTO CONTROL
THE PHOTO CONTROL SHALL:
PROVIDE AUTOMATIC SWITCHING FOR LIGHTING LOADS USING A THERMAL
DESIGN WITH BUILT —IN DELAY TO ENSURE THAT THE CONTROLLED LIGHTING
DOES NOT SWITCH OFF DUE TO AMBIENT LIGHT OR LIGHTNING STRIKING THE
PHOTOCELL.
HAVE A RATING BASED ON UL TESTING AT 50% POWER FACTOR FOR BALLAST
LOADS, BE UL LISTED, AND MEET ALL APPLICABLE AGENCY REQUIREMENTS
BE STEM — MOUNTING TYPE WITH ALL NECESSARY MOUNTING HARDWARE AND
INSTRUCTIONS; HAVE A HOUSING CONSTRUCTED OF HIGH IMPACT POLY-
CARBONATE; PHOTO CONTROL COMPONENTS CONSISTING OF A METAL FILM
RESISTOR, DUAL TEMPERATURE COMPENSATING BI —METAL BLADES, SNAP
ACTION CONTACT BLADES, CHEMICALLY TREATED /POLYMER ENCAPSULATED
CADMIUM SULFIDE PHOTOCELL AND SILVER ALLOY CONTACTS TO ENSURE
RELIABLE 5 YEAR MANUFACTURER WARRANTED OPERATION. PHOTO CONTROL
SHALL BE 100% FACTORY TESTED FOR FUNCTION WITHIN MANUFACTURER'S
SPECIFIED LIGHT LEVELS.
BE FROM THE SAME MANUFACTURER OF AND TOTALLY COMPATIBLE WITH THE
TIME SWITCHES SPECIFIED ABOVE.
16B 5 -7 LIGHTING CONTACTORS
INDUSTRIAL DUTY TYPE; SILVER ALLOY, DOUBLE BREAK CONTACTS,
CONVERTIBLE WITH NO AND NC INDICATORS; CAPABLE OF ADDING POLES IN
THE FIELD; NUMBER AND RATING OF POLES AS INDICATED ON THE DRAWINGS
OR REQUIRED BY THE LOAD CONTROLLED; TYPED DIRECTORY AFFIXED TO THE
INSIDE OF THE ENCLOSURE DOOR LISTING ALL BRANCH CIRCUITS SWITCHED
AND THE CONTROL POWER BRANCH CIRCUIT.
SHORT CIRCUIT CURRENT RATING:
277V
22,000A AT 240V MAXIMUM
ENCLOSURES: NEMA 1
COIL VOLTAGEAS INDICATED ON THE DRAWINGS
MECHANICALLY —HELD TYPE, CONTROL INTERFACE SHALL BE 2 —WIRE INPUT
MODULE WITH 3 —WIRE OUTPUT;SQUARE D CLASS 8903 LX OR EQUIVALENT OF
GENERAL ELECTRIC, SIEMENS, CUTLER HAMMER OR ASCO.
ELECTRICALLY —HELD TYPE, CONTROL INTERFACE SHALL BE 2 —WIRE; SQUARE D
CLASS 8903 L, OR EQUIVALENT OF GENERAL ELECTRIC, CUTLER HAMMER,
SIEMENS OR ASCO.
ACCESSORIES:
ON —OFF —AUTO (OOA) SELECTOR SWITCH
16B 5 -8 SIGNALING SYSTEM
PROVIDE A COMPLETE AND FUNCTIONING 24V SIGNALING SYSTEM FOR
LOADING DOOR SIGNALS, AND OTHERS AS INDICATED ON THE DRAWINGS.
LOW— VOLTAGE CONDUCTORS FOR SIGNALING SYSTEM MAY BE RUN EXPOSED
ABOVE FINISHED CEILINGS, BUT SHALL BE INSTALLED IN CONDUIT WITHIN
WALLS AND WHERE EXPOSED IN THE WORK AREAS.
SIGNAL BELL UNITS SHALL BE 4 —INCH, SINGLE — STROKE TYPE, EDWARDS
SIGNALING & SECURITY SYSTEMS (EDWARDS) NO. 332 -4G5, OR EQUAL, FOR 24V
AC OPERATION, INSTALLED ON A STANDARD SINGLE —GANG BOX.
TRANSFORMERS SHALL BE EDWARDS 590 SERIES, OR EQUAL„ HAVING
ADEQUATE CAPACITY FOR THE CONNECTED LOAD, PLUS 10— PERCENT AT 24V
AC, AND MOUNTED IN A STANDARD TWO —GANG BOX. EXTERIOR PUSH BUTTON
SHALL BE EDWARDS NO. 1786 —C WITH SOLID BRASS CAP.
CUSTOMER SIGNAL UNITS SHALL CONSIST OF AN EDWARDS NO. 620 —B
PUSHBUTTON IN A 5/8 INCH ID CHROME PLATED PIPE OR CONDUIT WITH AN
EDWARDS NO. C -75 "CADET" TWO —NOTE CHIME AND TRANSFORMER CONTAINED
IN A WEATHERPROOF ENCLOSURE AS REQUIRED, AS LOCATED ON THE
DRAWINGS.
16B 5 -9 MISCELLANEOUS EQUIPMENT AND CONNECTIONS
PROVIDE WIRING OF FIRE EXTINGUISHING SYSTEM FOR EXHAUST HOODS,
INCLUDING, BUT NOT LIMITED TO, ELECTRICAL INTERLOCK OF AUTOMATIC FUEL
SHUT —OFF VALVES AND /OR PROVISION OF SHUNT TRIP BREAKERS FOR SHUT-
OFF OF ELECTRICAL EQUIPMENT UNDER HOODS.
ALL WIRING AND CONNECTIONS FOR REFRIGERATED CASES AND BOXES,
INCLUDING LIGHTING, SUPERSTRUCTURE LIGHTING, AND CONTROL CABLE AND
WIRING AS REQUIRED BY REFRIGERATION WIRING DIAGRAMS.
ALL WIRING AND CONNECTIONS TO ILLUMINATED CASES.
ALL WIRING AND CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS,
INCLUDING, BUT NOT LIMITED TO, BAKERY EQUIPMENT, DELI EQUIPMENT, MEAT
ROOM EQUIPMENT, KITCHEN EQUIPMENT, CHECKSTAND AND SCANNERS,
EXHAUST HOOD FIRE EXTINGUISHING SYSTEM, ETC. INSTALL SCAN SYSTEM
ELECTRONIC COMMUNICATION CABLE IN UNDERFLOOR DUCT (CABLE
PROVIDED BY OTHERS).
ALL RACEWAYS, AND ALL WIRING AND CONNECTIONS OF DEVICES TO ENERGY
MANAGEMENT SYSTEM THAT ARE NOT THE RESPONSIBILITY OF DIVISION 15.
ALL WIRING AND CONNECTIONS OF EXIT DOOR ALARMS.
16B 5 -10 AUTOMATIC DOOR OPERATORS
MAKE CONNECTION FROM JUNCTION BOXES TO THE ENTRY DOOR OPERATORS
LOCATED IN THE TRANSOM ABOVE SLIDING DOORS, FROM DOOR OPERATORS
TO ACTUATION DEVICES AS REQUIRED. PROVIDE KEY — OPERATED SWITCHES AT
LOCATIONS SHOWN ON THE DRAWINGS, AND PROVIDE ALL OTHER REQUIRED
ELECTRICAL CONNECTIONS FOR DOOR SYSTEMS.
16B 5 -11 EXISTING FIRE ALARM SYSTEM MODIFICATIONS
PROVIDE THE FOLLOWING NEW EQUIPMENT, COMPATIBLE WITH, OR OF THE
SAME MANUFACTURER AS, THE EXISTING FIRE ALARM CONTROL PANEL AND
SYSTEM, AT LOCATIONS INDICATED ON THE DRAWINGS, AS REQUIRED BY
BUILDING CODES, THE LANDLORD, OR ALL THREE, AND CONNECT TO THE
EXISTING FIRE ALARM CONTROL PANEL:
1. ADDITIONAL INITIATING DEVICES, INDICATING APPLIANCES, AND
INTERCONNECTING CIRCUITS.
2. ADDITIONAL ZONE MODULES REQUIRED BY NEW ZONING.
3. NEW AMPLIFIERS AND OTHER EQUIPMENT THAT MAY BE REQUIRED TO
INCORPORATE THE NEW INITIATING DEVICES AND INDICATING APPLIANCES
INTO THE EXISTING SYSTEM.
4. A NEW ZONE MAP, INCLUDING ALL EXISTING ZONES AND ALL NEW ZONES,
FRAMED, MOUNTED UNDER GLASS, AND INSTALLED ADJACENT TO THE FIRE
ALARM CONTROL PANEL HORN /STROBES SHALL MEET ALL REQUIREMENTS OF
THE • AMERICANS WITH DISABILITIES ACT.
5. PROVIDE ALL PROGRAMMING OF EXISTING SYSTEMS TO INCLUDE NEW AND /OR
RELOCATED DEVICES.
6. PROVIDE ALL TESTING OF NEWLY INSTALLED DEVICES AND SYSTEM
PROGRAMMING.
INSTALL ALL WIRING IN RACEWAY.
168 5 -12 AREA OF RESCUE ASSISTANCE COMMUNICATIONS SYSTEM
GENERAL; PROVIDE ALL LABOR, EQUIPMENT, MATERIALS, AND PERFORM ALL
OPERATIONS IN CONNECTION WITH THE INSTALLATION OF THE AREA OF
RESCUE ASSISTANCE SYSTEM AS SPECIFIED, AS INDICATED ON THE DRAWINGS,
OR BOTH, AND CONFORMING TO APPLICABLE LOCAL CODE REQUIREMENTS,
THE AMERICANS WITH DISABILITIES ACT, AND NFPA 70.
DESCRIPTION; PROVIDE A COMPLETE AND FUNCTIONING AREA OF RESCUE
ASSISTANCE COMMUNICATION SYSTEM AS OUTLINED IN THE AMERICANS WITH
DISABILITIES ACT GUIDELINES, INCLUDING A MASTER CALL STATION, REMOTE
CALL STATIONS, ALL WIRING, CONNECTIONS TO DEVICES, OUTLET BOXES,
JUNCTION BOXES, RACEWAYS, AND ALL OTHER NECESSARY MATERIALS.
OPERATION; THE SYSTEM SHALL ALLOW TWO —WAY COMMUNICATIONS
BETWEEN THE REMOTE CALL STATIONS AND THE MASTER CALL STATION VIA
BOTH VOICE AND VISUAL INDICATING LIGHTS. LABEL EACH "AREA OF RESCUE
ASSISTANCE" WITH A LIGHTED SIGN, AND INCLUDE OPERATING INSTRUCTIONS,
ADJACENT TO IT, ON USE OF THE CALL STATION.
CALL STATIONS; MASTER CALL STATION: CORNELL A4204, REMOTE CALL
STATIONS: CORNELL 4201.
TESTING; FULLY TEST THE COMPLETE AREA OF RESCUE ASSISTANCE SYSTEM
IN THE PRESENTS OF THE OWNER'S REPRESENTATIVE. CERTIFY IN WRITING TO
THE OWNER AND ENGINEER THAT THE SYSTEM HAS BEEN SUCCESSFULLY
TESTED.
REVIEWED FOR
COMPLIANCE WITH
NFPA7O- NEC
MAY 0 9 2012
City of.Tukwila
BUILDING DIVISION
RECE1vEu
CITY OF TUKWILA
APR 242012
PERMIT CENTER
x
as
•
•
•
a+
•
is
•
J
Z
8
CO
a
Z
01
co q
Q U
VCS
0
Z :w
z
ec
ooz
N
X0(7
.7 s
co
wr.
w
>
N
Y.
w
S
z
w
0
z
5
U
w
(zo
*NA
Z
a
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE: E52 SPECS.DWG
at •fT �`'
• ' } —1
2•
% •.c� .• /STEFt;. 4-•
i� oNA L E to
�it11//a /siol
SHEET NAME
ELECTRICAL SPECIFICATIONS
SHEET NUMBER:
E5.2
UGHT FIXTURE SCHEDULE
TYPE
MANUFACTURER /MODEL #
LAMPS
INPUT
WATTS
INPUT
VA
DESCRIPTION
MOUNTING
HEIGHT
NOTES
Project Description
NO.
TYPE
VOLT .
A
CORELITE / SB- WB- 4T8 -2 -C- UNV- A- C- AC120 -ST -8
8
GE F28T8XLSPX35ECO
277
174
174
8'xlx3" DIRECT /INDIRECT LINEAR FLUORESCENT FIXTURE SUSPENDED WITH 120"
14' -0" AFF
1,2,3
44.0
352.0
24,000 HRS
654
25.0
16350.0
AIRCRAFT CABLE FOR USE WITH HIGH CEILINGS WITH (8) T8 LAMPS. STANDARD WHITE
P- (1) 18W COMPACT FLUORESCENT
4,5,7
20.0
800.0
S- (1) -4FT FLUORESCENT T8 INSTANT START
34
25.0
850.0
PERFORATED BAFFLE WITH ELECTROSTATICALLY APPLIED POLYESTER POWDER COAT
WW- (2) 40W COMPACT FLUORESCENT TWIN 4 PIN ELEC
32
61.0
1952.0
STANDARD WHITE FINISH PAINT. UL LISTED. STRAIGHT CORD POWER FEED WITH
TWO GE ULTRAMAX LOW .77 BALLAST FACTOR BALLASTS FOR TWO CIRCUITS FOR
USE WITH BI -LEVEL SWITCHING. EACH BALLAST CONTROLS FOUR LAMPS.
AE
CORELITE / S4- WB- 4T8 -2 -C- UNV- A- C- AC120 -ST -8
8
GE F28T8XLPX35ECO
277
174
174 +4
SAME TYPE AND OPERATION AS FIXTURE TYPE A. CONNECT AS DESCRIBED IN FIXTURE
14' -0" AFF
1,2,3
W/ IOTA ISD -80 EMERGENCY BATTERY PACK
85 CRI, 3500K
TYPE A FOR SWITCHED BALLASTS. INCLUDE EMERGENCY BALLAST IOTA ISD -80 OR
4,5,7
OR EQUIVALENT
2750 LUMENS
EQUIVALENT, PRODUCING 1175 LUMENS PER TWO LAMPS FOR 90 MINUTES. CONNECT
24,000 HRS
THE TWO INSIDE LAMPS ON ONE SIDE OF THE FIXTURE TO EMERGENCY BATTERY
BACKUP BALLAST.
B
COOPER / L3705P
1
LSGC- DFN38WW -V2-
120
21
21
4" LED FLOOD LIGHT FIXTURE MOUNTED ON TRACKWITH LOCKABLE AIMING AND QUICK-
AT
1,2,3
FL -120
LOCK ADAPTER WITH 6" MOUNTING ARM. DIE CAST AND EXTRUDED ALUMINUM
STRUCTURE
4,5,7
HOUSING. EQUIPPED WITH (7) 3 WATT WHITE LEDS CONTROLLED BY LED LIGHT ENGINE.
UL LISTED FOR USE WITH HALO POWER TRACK
11' -0" AFF, 3' -0"
BACK FOR
END CAPS
C
METALUX / 2AC- 232T8- UNV -EB81
2
3E F28T8XLSPX35ECO
277
43
44
4'x2'x3.25" RECESSED LINEAR FLUORESCENT TROFFER WITH (2) T8 BULBS FOR USE
10' -0" AFF
1,2,3
85 CRI, 3500K
IN GRID OR HARD CEILINGS. FROSTED ACRYLIC LENS WITH 3.25" DEEP HOUSING CONSTRUCTED
4,5,7
2750 LUMENS
FROM CODE GAUGE COLD ROLLED STEEL AND END PLATES WITH WHITE ENAMEL FINISH.
24,000 HRS
(1) T8 ELEC INSTANT START ULTRAMAX NORMAL BF BALLAST. UL LISTED FOR DAMP LOCATIONS.
CE
METALUX / 2AC - 232T8- UNV -EB81
2
GE Fl 7T8SLSPX35ECO
277
43
46 +4
SAME AS FIXTURE TYPE C. INCLUDE EMERGENCY BALLAST IOTA ISD -80 OR EQUIVALENT,
10' -0" AFF
1,2,3
W/ IOTA ISD -80 EMERGENCY BATTERY PACK
PRODUCING 1175 LUMENS PER TWO LAMPS FOR 90 MINUTES. CONNECT THE TWO LAMPS
4,5,7
OR EQUIVALENT
TO EMERGENCY BATTERY BACKUP BALLAST.
C2
METALUX / 2AC- 217T8- UNV -EB81
2
GE F17T8XLSPX35ECO
277
43
46 +4
2'x2'x3.25" RECESSED LINEAR FLUORESCENT TROFFER WITH (2) T8 BULBS FOR USE
10' -0" AFF
1,2,3
W/ IOTA ISD -80 EMERGENCY BATTERY PACK
IN GRID OR HARD CEILINGS. FROSTED ACRYLIC LENS WITH 3.25" DEEP HOUSING CONSTRUCTED
4,5,7
OR EQUIVALENT
FROM CODE GAUGE COLD ROLLED STEEL AND END PLATES WITH WHITE ENAMEL FINISH.
(1) T8 ELEC INSTANT START ULTRAMAX NORMAL BF BALLAST. UL LISTED FOR DAMP LOCATIONS.
D
METALUX / VT232 -DR
2
GE F28T8XLSPX35ECO
277
43
44
4'x7 "x6" LINEAR FLUORESCENT WITH (2) T8 BULBS FOR USE WITH
16' -0" AFF
1,2,3
85 CRI, 3500K
SURFACE OR CHAIN MOUNTING. FULL METAL FIXTURE LINER INSIDE FIBERGLASS
4,5,7
2750 LUMENS
HOUSING WITH INTERNAL PRISMATIC LENS WITH 15% DR HIGH IMPACT ADDITIVE.
24,000 HRS
(1) T8 ELEC INSTANT START ULTRAMAX NORMAL BF BALLAST. UL LISTED FOR
WET LOCATIONS.
DE
METALUX / VT- 232 - DR- UNV -EB81
2
GE F28T8/SP35
277
43
44 +4
SAME AS FIXTURE TYPE D. INCLUDE EMERGENCY BALLAST IOTA ISD -80 OR EQUIVALENT,
16' -0" AFF
1,2,3
W/ IOTA ISD -80 EMERGENCY BATTERY PACK
85 CRI, 3500K
PRODUCING 1175 LUMENS PER TWO LAMPS FOR 90 MINUTES. CONNECT THE TWO LAMPS
4,5,7
OR EQUIVALENT
2750 LUMENS
TO EMERGENCY BATTERY BACKUP BALLAST.
24,000 HRS
-
DL
LUMARK / INDD60 -30R- 200- WLG- 120V -LA
1
MSI iPAR38 -22.5 LED
120
16
16
60" ARM LENGTH ADJUSTABLE, LOCKABLE DOCK LIGHT DOUBLE WALL MOUNTED
5' -0" AFF
1,3
83CRI, 3000K
WITH 22.5 DEGREE LED FLOOD AND WIRE LAMP GUARD. 1.5" CROSS SECTION
4,5,7
800 LUMENS
12 GAUGE STEEL TUBING ARMS AND POLYCARBONATE LAMP HEADS WITH
50,000 HRS
SAFETY YELLOW POLYESTER POWDER COAT. FIXTURE AND LED UL LISTED.
22.5 DEG FLOOD
5000 CBCP
FL
LAMP ONLY: 28W T8 LAMP FOR GONDOLA
1
GE F28T8/SP35
120
24
25
120V SINGLE TUBE ELECTRONIC FLUORESCENT CHANNEL MOUNTED ON FULL LENGTH
ON
1,3
DISPLAY LIGHTING
85 CRI, 3500K
OF STORE FIXTURES.
DISPLAYS
4,5,7
2750 LUMENS
24,000 HRS
H
COOPER L3703M13
1
LSGC- DFN- 30 -WW-
120
21
21
4" LED SPOT LIGHT FIXTURE MOUNTED ON TRACKWITH ADJUSTABLE ARM AND HEAD.
10' -0" AFF
1,2,3
TRACK: HALO POWER TRACK
V2 -FL -120
POLYCARBONATE CASING BODY. UL LISTED FOR USE WITH HALO POWER TRACK
4,5,7
HALO L652
CURRENT LIMITER LC901CB120
0
METALUX / 2GR8- 232 - UNV -EB81
2
GE F28T8XLSPX35ECO
277
43
44
4'x2'x3.25" RECESSED LINEAR FLUORESCENT TROFFER WITH (2) T8 BULBS FOR USE
10' -0" AFF
1,2,3
85 CRI, 3500K
IN GRID OR HARD CEILINGS. #12 PATTERN ACRYLIC WITH 3.75" DEEP HOUSING
4,5,7
2750 LUMENS
CONTRUCTED FROM CODE GAUGE COLD ROLLED STEEL AND END PLATES WITH WHITE
24,000 HRS
ENAMEL FINISH AND PREMIUM REFLECTANCE. (1) T8 ELEC INSTANT START ULTRAMAX
NORMAL BF BALLAST. UL LISTED FOR DAMP LOCATIONS.
OE
METALUX / 2GR8- 232 - UNV -EB81
2
GE F28T8XLSP35ECO
277
43
44 +4
SAME AS FIXTURE TYPE 0. INCLUDE EMERGENCY BALLAST IOTA ISD -80 OR EQUIVALENT,
10' -0" AFF
1,2,3
W/ IOTA ISD -80 EMERGENCY BATTERY PACK
85 CRI, 3500K
PRODUCING 1175 LUMENS PER TWO LAMPS FOR 90 MINUTES. CONNECT THE TWO LAMPS
4,5,7
OR EQUIVALENT
2750 LUMENS
TO EMERGENCY BATTERY BACKUP BALLAST.
24,000 HRS
P
FORECAST LIGHTING / L957P/F5100- 70NV/F5177NV
1
GE F18TBX /835/ECO
120
21
20
PENDANT MOUNTED DOMPACT FLUORESCENT FIXTURE SUSPENDED FROM TRACK WITH
7' -0" AFF
1,2,3
TRACK: HALO POWER TRACK
18W CFL
ADAPTER AND 10 FOOT CORD. EQUIPPED WITH APAPTER FOR COMPACT FLUORESCENT
4,5,6,7
HALO L652, HALO 653
82CRI, 3500K
USAGE. GLASS SHADE FINISH TO BE COORDINATED WITH ARCHITECT. CONTRACTOR
CURRENT LIMITER LC901 CB300
1200 LUMENS
TO PROVIDE ALL COMPONENTS FOR A FULLY FUNCTIONING INSTALLATION.
ADAPTER L957
12,000 HRS
ADAPTER UL LISTED FOR USE WITH HALO POWER TRACK
S
METALUX / MB- 132 -TB- UNV -EB81
1
GE F28T8XLSPX35ECO
277
24
25
4'x8.25 "x5.5" LINEAR FLUORESCENT WITH (1) T8 BULB FOR USE WITH
16' -0" AFF
1,2,3
W/ IOTA ISD -80 EMERGENCY BATTERY PACK
85 CRI, 3500K
CHAIN MOUNTING. DIE FORMED CHANNEL FROM 20 GAUGE PRIME COLD ROLLED STEEL
4,5,7
OR EQUIVALENT
2750 LUMENS
AND TASK BEAM REFLECTOR. (1) T8 ELEC INSTANT START ULTRAMAX NORMAL BF
24,000 HRS
BALLAST. UL LISTED FOR DAMP LOCATIONS.
SE
METALUX / MB- 132 -TB- UNV -EB81
1
GE F28XLSP35EC0_
277
25
26 +4
SAME AS FIXTURE TYPE S. INCLUDE EMERGENCY BALLAST IOTA ISD -80 OR EQUIVALENT,
16' -0" AFF
1,2,3
PRODUCING 1215 LUMENS FOR ONE LAMP FOR 90 MINUTES.
4,5,7
SS
METALUX / SSF- 232 - UNV- EB81 -U
2
GE F28T8XLPX35ECO
277
43
44
4', 2 -LAMP STRIP
16' -0" AFF
1,2,3
4,5,7
WW
METALUX / L3240EP- LV3240SC
2
GE F40 /25BXWM
120
58
61
2'x6 "X8" COMPACT FLUORESCENT LINEAR WALL WASHER MOUNTED ON HALO
AT
1,2,3
82 CRI, 3500K
3500 LUMENS
POWER TRACK FOR USE WITH (2) 40W TWIN -TUBE 4 -PIN COMPACT FLUORESCENT.
SOLID ALUMINUM EXTRUSION WITH DIE -CAST ALUMNIUM END CAPS WITH SPECULAR
STRUCTURE,
5' -0" OFF WALL
4,5,7
10,000 HRS
REFLECTOR. UL LISTED FOR USE WITH HALO POWER TRACK. STANDARD ELECTRONIC
BALLAST
WS
METALUX / WS- 3- 32- A- UNV- EB -8 -1
3
GE F32T8/SP35
120
86
87
4'x15.5 "x2.5" LINEAR FLUORESCENT WRAPAROUND FIXTURE. DIE FORMED CODE
SURFACE
1,2,3
78 CRI, 3500K
GAUGE PRIME COLD ROLLED STEEL AND 100% CLEAR FULL THICKNESS VIRGIN
MOUNTED
4,5,7
2800 LUMENS
ACRYLIC PRISMATIC REFRACTOR /LENS. ELECTRICAL INSTANT START BALLAST.
ON CEILING
30,000 HRS
UL LISTED FOR DAMP LOCATIONS.
X1
COOPER / LPX- 7- 0- R -WH -DH
2
6 Vdc, 5.4W
120/277
8
8
RECESSSED WALL MOUNT LED EXIT SIGN AND HEADS WITH BATTERY BACKUP. INJECTION
AT
1,2,3
INCANDESCENT
MOLDED, HIGH IMPACT CLEAR ACRYLIC PLAQUE. EXTRUDED ALUMINUM HOUSING AND
STRUCTURE
4,5,7
WEDGE BASE
TRIM. WHITE HOUSING FINISH. RED LEDS. INTEGRAL NICKEL - CADMIUM BATTERY CAPABLE
LAMPS
OF 90 MINUTES OF EMERGENCY OPERATION. SOLID STATE CHARGER WITH LOW VOLTAGE
DISCONNECT. INTEGRAL LED INDICATING LIGHT AND TEST SWITCH. SELF DIAGNOSTIC.
1
RED LED
UNIVERSAL VOLTAGE 120/277 VAC OPERATION. SINGLE FACE ON CLEAR BACKGROUND.
INCLUDED
FACTORY- SCREENED DIRECTIONAL CHEVRON ARROWS. UL 924 COMPLIANT. UL
LISTED FOR DAMP LOCATIONS. REFER. TO PLANS FOR CHEVRON ARROWS AND NUMBER
OF FACES REQUIRED.
X2
MCPHILBEN / PDN
2
6 Vdc, 6W
120/277
13
13
WALL- MOUNTED EXTERIOR TWIN LAMP EMERGENCY FIXTURE WITH BATTERY BACKUP.
8' -0" AFF
1,2,3
HALOGEN
MARINE -GRADE DIE -CAST ALUMINUM HOUSING WITH MICRO REFLECTOR AND UV STABLE
4,5,7
8I -PIN
POLYCARBONATE LENS AND NEOPRENE GASKET. POLYESTER POWDER COAT FINISH.
113 LUMEN
COORDINATE FINISH COLOR WITH ARCHITECT. BATTERY IS 6V, MAINTENANCE FREE SEALED
NICKEL CADMIUM WITH 7 -9 YEAR SERVICE LIFE. UL LISTED FOR WET / DAMP LOCATIONS
UL924, NFPA 70, NFPA 101, ADA COMPLIANT.
NOTES:
1. PROVIDE UNIT - PRICING ALONG WITH MANUFACTURER AND MODEL NUMBER FOR ALL LIGHT FIXTURES. NO PACKAGING OR LUMP SUM PRICING OF LIGHT FIXTURES SHALL BE ALLOWED.
AT CONTRACTOR'S OPTION, ALTERNATE LIGHT FIXTURES MAY BE SUBMITTED. HOWEVER, ALTERNATE FIXTURES MUST BE SUBMITTED FOR REVIEW AT BID OPENING, MUST INCLUDE
UNIT - PRICING AND INCLUDE ALL APPLICABLE INFORMATION NECESSARY FOR REVIEW AND EVALUATION; REFER TO SPECIFICATION 16500.
2. VERIFY CEILING CONDITIONS AND COORDINATE LIGHT FIXTURE MOUNTING HARDWARE NEEDED TO SUIT CEILING CONDITIONS PRIOR TO ORDERING.
3. VERIFY MODEL NUMBERS AND DESCRIPTIONS WITH MANUFACTURER PRIOR TO PLACING ORDER.
4. VERIFY FINISH AND COLOR WITH ARCHITECT PRIOR TO PLACING ORDER.
5. REFER TO ARCHITECTURAL DRAWINGS AND DETAILS FOR EXACT LOCATIONS, MOUNTING HEIGHTS AND ADDITIONAL MOUNTING INFORMATION.
6. CONTRACTOR SHALL SUPPLY A COMPLETE AND OPERATIONAL SYSTEM TO COMPLY WITH DESIGN INTENT.
7. FIXTURE AND LIGHTING CONTROL DEVICES FOR FIXTURE SHALL BE CALIFORNIA TITLE 24 CERTIFIED.
2006 Washin ton State Nonresidential Ener Code Corn • Hance Form
Interior Lighting Summary
LTG -INT
2006 Washington State Nonresidential Energy Code Compliance Forms
Revised July 2007
Project Info
Project Address TOTAL WINS
Date 4/17/2012
300 ANDOVER PARK WEST, SUITE soo
For Building Department Use
TUKWILA, WA 98188
Applicant Name:
Applicant Address:
Applicant Phone:
Project Description
• New Building • Addition "-4 Alteration
74 Plans Included
Indicate controls (Sections 1513) including commissioning requirements on plans.
Compliance Option
O Prescriptive 0 Lighting Power Allowance Q Systems Analysis
(See Qualification Checklist (over). Indicate Prescriptive & LPA spaces clearly on plans.)
Alteration Exceptions
(check appropriate box - sec. 1132.3)
0 No changes are being made to the lighting
0 Less than 60% of the fixtures new, installed wattage not increased, & space use not changed.
Maximum Allowed Lighting Wattage
Location
(floor /room no.)
Occupancy Description
Allowed
Watts aer f **
Area in ftz
Allowed x Area
RETAIL
1.50
27780.0
41670.0
E- 18W INCANDESCENT LED
104
21.0
2184.0
C- (1) .4FT FLUORESCENT T8 INSTANT START
41
44.0
1804.0
** From Table 15-1 (over) - document all exceptions on form LTG -LPA
Proposed Lighting Wattage
Total Allowed Watt 41670 .0
Location
(floor /room no.)
Fixture Description
Number of
Fixtures
Watts!
Fixture
Watts
Proposed
A- 8FT FLUORESCENT T8
99
174.0
17226.0
E- 18W INCANDESCENT LED
104
21.0
2184.0
C- (1) .4FT FLUORESCENT T8 INSTANT START
41
44.0
1804.0
D- (1) 4FT FLUORESCENT T8 INSTANT START
8
44.0
352.0
FL- (1) 25W COMPACT FLUORESCENT
654
25.0
16350.0
P- (1) 18W COMPACT FLUORESCENT
40
20.0
800.0
S- (1) -4FT FLUORESCENT T8 INSTANT START
34
25.0
850.0
0011 t ft,
%' -• f' ," * �
- -
' •:i � 4) . •4• . -
C O•
• 2•
3?./ST k
WW- (2) 40W COMPACT FLUORESCENT TWIN 4 PIN ELEC
32
61.0
1952.0
Total Proposed Watts may not exceed Total Allowed Watts for Interior
Total Proposed Watts 41518.0
Notes:
1. For proposed Fixture Description, indicate fixture type, lamp type (e.g. T -8), number of lamps in the fixture, and ballast type (if
included). For track lighting, list the length of the track (in feet) in addition to the fixture, lamp, and ballast information.
2. For proposed Watts /Fixture, use manufacturer's listed maximum input wattage of the fixture (not simply the lamp wattage) and
other criteria as specified in Section 1530. For hard -wired ballasts only, the default table in the NREC Technical Reference Manual
may also be used. For track lighting, list the greater of actual luminaire wattage or length of track multiplied by 50, or as applicable,
the wattage of current limiting devices or of the transformer.
3. List all fixtures. For exempt lighting, note section and exception number, and leave Watts /Fixture blank.
REVIEWED FOR
CONFPA OC H
NEC C
MAY 0 9 2012
City of Tukwila
BUILDING DIVISION
ELI1 -03 8
ECCE.iYE�
CITY R FRKWILA
APR 2 4 2012
PERMIT CENTER
ota
1
0
tn
0
0
CONSULTANT
LAS VEGAS :: IRVINE :: PHOENIX :: SALT
MIN14
carig NON
ig4458111
04%141
Z
tai
2
Z
a
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE: E61 LIGHTING CALCS.DWG
0011 t ft,
%' -• f' ," * �
- -
' •:i � 4) . •4• . -
C O•
• 2•
3?./ST k
SHEET NAME:
ELECTRICAL LIGHTING
CALCULATIONS
SHEET NUMBER:
E6.1
ELECTRICAL
co,. M
MODEL
111 +a3�,,_r�xrar,_''
CONN. (0105, IN.)
.
1 Y .1.116„ 1_+� MPS 5!460/9160
Dimensions On.)
NUMBER
MODS
�'t I,. ];
r t:�
1:Of1D
TOTAL MCA
i.A. •.::�
COND TOTAL
MCA CO %'RESSOR
COND
TOTAL
MI:
NUMBER
•i
R`11090M44 RST64C1E 0.75
00
$ [
28.84 27.314 17-1/4 160
R.A
WIT t
FLA UNIT
FLA
UNIT
68
/2ti08cM44 RST55C1E
61
33.7 05
7'6 15 - '- --- -' --
-
��.
R'H(, IM4 RST64CIE
a.o
D.5
1, -- - -- -- -... -.-
1•111111Ewi1
111037fM '3i/11WiE}Tf 0111=11.111
7/8
Rhllnol.144 R57OC1E
e.3
05
15 4.2 310 0.5 5.7 15 2.4 15.0
+
3-
15
FM1125144. E
1,E1
51.0 1.0
11.9 Bin 35.0 1.0 ��� --
-
R144008444 0527K6E 4.00
24.3 112
CS1OK
R'Hts 14-4 CS
33 42-114 32 -114 390
58tr 0
17 8 51 0 1 0 25 D
0,8
24.3 1/2
1 -18 D
33 42 -1 /4 32 -114 405
111
�/'r f l�ii'�:i i�i4 ®�
0.50
5,1 318
6814K8E
�'
�yyyu���
�.gaa's �'l;X.aI7Z'a �1:7!i 28.0
Cr H0901144 RST64CIE 0.75
�,
5(8 A
28.114 27 -314 17-1/4 173
-
: � 118111110111111111111111111111.011 40.0
5.1 3/8
516
R°H4006M-1 CS27K6E
21,5
1210
25.6 12.1 toy0 3,1 16.2 20 7.8 52.0
t
92 1 5
R115001044 C533ft8E
27.6
125 0
31.7 R 16.8 102 0 3.1 20.9 28 8.8 48,0
I 1
10.4 15
E
R8090 RRS S
s 0
430 0.5
�1[^� 15 - 111 -- --
75
®1..
R111001-144 RS79CIE
8111513144 ;, IOK6E
6.9
ii.i
34.2 4.5
58.0 10
84 15 4.7 31.0 05 82 15 ®
13.1 18 7.2 51.0 1.0 9.2 15
-
�
R112511-144 C314K6E
12.4
810 1.0
144 85 55.0 1.0 105 75 -- --
-
- --
®
R1-13251444 iS2OK6Ir
.17.9
98 0 3 I
22 13.3 75.0 3.1 174 21 -- - --
-63150:4144
--
^I C533K6E
11*14165L44 CF46K6E
125 6 �y.
34.2 42 16 5 102.0 3.1 20 6 25 -- --
-
-
R"H215144 ' CF09K6E 2.00
ann= 05700
70 ...342
11111131111110111111111111 WEN 31.0 0.5 ®® , -
75
--
®'
R1-11001_44 RS97CIE
110
• 0.5
125 16 70 35.0 0.5 8.5 15 - -- --
-
R'3100M44
-
811185144 GFoOKKE
11 A
E�11� 1.0
13,1 18 7.0 52.0 1.0 9A 15 - -- - --
--
-•-
R'H215144 CF09K6E
16.7.
87.0 1.0
18.7 24 102 72.0 1.0 122 16 -- --
--
-- --
R11316144 CF12K6E
205
105.0 1.0
225 28 123. .85 .0 1.0 143 18 6.6 420
0.4
7.5 15
8•5/004-44
KAR -D10E
8.4
40.0
0.5
7.9
15
3.8
27.0
0.5
5.3
15
1.5
150
0.4
23
15
R'S240M44
KAK -020E
9.1
551
1.0
111
15
5.8
:. 50.0
i5
7.5
15
--
--
--
--
---
11•8250M44
ERC -021 E
-
---
---
_
--
--
7 6
46.0
10
5 9
15
3.1
230
O.8
4.4
15
R'S3001444
ERF-031E
153
86.0
to
172
22
112
820
10
132
16
5.2
415
O.8
65
15
R5050144
KAN -005E
36
24.0
OS
5.1
15.
22
132
a5.
3.7
15
---
'-
--
- -
- - -
1 1 ' 6 0 7 5 1 1 . 4 4
KAM -007E
5.6
35-0
05
7.1
15
3.2
19.9
05
4.7
15
--
--
--
--
---
R5100144
KAJ -010E
39
40.0
0.5
8.4
15
- 4 5
270
0S
6.0
15
- --
--
--
--
---
R'5150144
KAL -018E
9.9
55.0
1.0
11.9
16
56
500
1.0
36
15
--
--
--
--
--
R520/.44
EAVC21E
14.7
192.0
t0
16.7
2?
7.4-
500
1.0
9.4
15
- --
--
--
--
- - --
R "5300144"
IAH -(K12E
167
X05.0
15
193
24
128
1120
1.4
142
19
6.0
56.0
0.4
62
15
W02001.444
1S1-31(4E
136
55.0
1.0
156
20.0
9.3
55.0
1.0
11.3
15.0
4.3
27.0
0.4
5.2
15.0
R'c0�505144
ZS10K41
184
730
1.0
184
25.0
9.7
63 ..0
1.0
11.7
155
5.0
310
0.4
5.8
15.0
R *03151444
23211(4E
16A
88.0
32
202
25.0
111
77.0
32
15.3
17 0
5.7
39.0
21
82
15 0
R'Q350M44
7526K4P
20.7
103.0
32
24.9
30.0
13 ..6
BR. O
32
17,8
240
7,1
44 0
2.1
97
150
8'44064-44
Z53q(4E
26.8
1255
32
315
38.0
15.0
95.0
32
182
230.
8.2
45.5
2.1
10.8
15.0
11'06001,444
ZS-381(4E
31.8
14$.0
32
38.0
44.0
21.4
1235
32
250
210
58
620
21
122
15.o
R'0650M44
2645K4E
--
-__
- --
- --
--
23.9
1508
32
28.1
:340
9.3
70.0
2.1
112
15.0
11"0200L44
ZF06K4E
13.6
550
15.
15.6
200
• 93
55.0
15
11.3
180
4.3
27.0
0.4
52
15.0
R- 0250144
ZF081i4E
154
73.0
1
15.4
25,0
a 7
63 0
1 0
I I.7
16,0
5.0
31.0
04
59
150
R'1J300L4-4
ZFO9K4E
164
8a .D
15
134
25.0
11.I
77 d
15
13.1
17.0
5.7
39.0
0.4
BB
15.0
14'0301144
ZF11K4E
207
1090
15
227
30.0
136
85+1
1.0
156
200
7.1
44 0
a4
80
15.0
11'0400L44
2F13K4E
260
1265
32
315
38.0
15.0
095
32
192
230
82
57.0
2.1
10.0
19.0
R'0500144
ZFISK4E
31.5-
IMr D
32
35.7
44.0
21 4
123.0
3?
25.8
31.0
9.6
62.0
2.1
12.2
23.0
R'060OL44
ZF18K4E
--
---
- --
-
--
23 8
156.0
32
28.1
34 0
9 -3
70 0
21
11 -9
23.0
R'D
dt- -R78KE
16:/.0
32
35 8
44
138
85 0
1 7
15.4
20
R'I7300144
2OF- F16(E
,
.___
- -.
_ -_
__
_ -_
16.8
1020
3.1
2+9
26
8.1
520
1.1
9.7
P'D4001.44
211 -125KE
--
--
--
- --
- --
26.3
1610
3.1
30.4
38
102
&1.0
1,1
11.8
®,
R'D500L44
2DA -F23KE
-- -.
--
---_
--
-
28.8
161.0
3.1
32.9
41
1O '
110 L.
11
11.6
This compressor w rated Tor 23011(60 app1 cation orgy Use. aid( BnatsI transformer fa 2083;1 V
/. Total Unit Amps includes approximate albvran:e ft4 -cram; :Li Mini as Slows: 15 - 2081230V :0.55 -45W
t MCA Mi imam Cimui Amp -aty dos not inc5ade eraporalcr(s electriaaI reguiremeols. (Evaporator In motor antics, defrost heater amps)
12
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
FINE WINE COOLER DETAIL
NO SCALE
Wolk -In and Fine Wine
Refrigeration Wiring
To Any
Additional
Units
Wo k -In Controls
Evaporator, Thermostat, Solenoid,
Double Throw Switch (by EC), and
Defrost Clock, to be wired per
diagram above
Walk -In Condensing Unit
Walk -in condensing units to be
located on roof of building
above walk -in ovation.
Permits, as required, by CC.
Provide 230v 3 ph with fused disconnect and
1 20v service receptacle. Compressor(s)
equipped with PCS motor(s)
N
Norma Operation:
*Thermostat cycles solenoid
*Fans operate continously
ae..f�ro
*Clock kills t =stat and solenoid
*Fans operate continously
Fans Switched Off:
*Switch kills t stat and solenoid
whenever it turns off to avoid
liquid slug at compressor
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
FINE WINE COOLER DETAIL
NO SCALE
SPECIFICATIONS / R -404A
MODEL NOM.
COMPRESSOR
NUMBER
RECR
at 90%
R-40M
0-85)
CONN. (0105, IN.)
.
FIG
Dimensions On.)
APPROX.
54iIP wT-
OW
Sound Data
dbAt
IMMEMILE311
1111111111111131011111011.
R'H0555444 RST45C1E 0.50
5.1 318
543 A .
28414 27 -34 17 -1 /4 152
68
R`HOSOM44 RST55ClE 0.75
5.1 3M
518 A
28-114 27-3/4 17-1/4 152
68
R`11090M44 RST64C1E 0.75
5.1 318
518 A
28.84 27.314 17-1/4 160
68
R'4100M44 RS70C1 E 1.00
3.1 318
518 A
28-1/4 27 -3/4 17 -114 167
68
HERRX7171E
CS10KBE
125
1.50
8.6 318
8.6 318
58 B
718 8
28.114 38.114 17 -114 195
28-IM 38.1/4 17 -1/4. 205
1111_1 ai.,rI
58
..T
f a.
1•111111Ewi1
111037fM '3i/11WiE}Tf 0111=11.111
7/8
I .ii :1;431't,.tr lriWi CiaAri7lf
Irikiilli
ili�irl>
,4:biL$* ffa1 1 i
MPEL1
u: ti] . . CS20K8E
3 00
1,E1
-
inff i it 20 -1t4V
112
R144008444 0527K6E 4.00
24.3 112
1 -1/8 D
33 42-114 32 -114 390
73
1313500M44 0533KBE
5.00
24.3 1/2
1 -18 D
33 42 -1 /4 32 -114 405
73
R140654444 RST45C1E
0.50
5,1 318
5/8 A
28-1/4 27 -314 17 -114 165
e8
Cr H0901144 RST64CIE 0.75
5.1 318
5(8 A
28.114 27 -314 17-1/4 173
68
13.'14100H44 RS70C1E 1.00
5.1 3/8
516
28.114 27-9/4 17 -114 ' 180
88
R*141511144 CS10K6E 1,50
8.6 318
7/8 �::
28-1/4 38-1/4 17 -1/4 221
72
R'H2511-14-4 CS14K8E 2.50
8.6 3/8
718 B
28.141 38-1/4 17 -1(4 253
72
11*1325H44 CS20K8E 3.00
13.7 1/2
1 -1(8 D
3S 42 -14- 32 -114 297
75
R•H400H44 C827K6E 4.00
24.3 1/2
1 -118 D
33 42.1%4 32.13 418
73
R'H500144 CS33K6E 5.00
24.3 112
1 -1/8 D
33 42 -1/4 32 -1/4 433
73
R *11075144 RS7Oc1 E 0.75
Si 348
518 A
28.114 27 -314 17 -114 157
68
R`11100144 RS97C1E 1.00
5.1 318
813 A
28414 27 -3/4 17 -1/4 180
68
11*14165L44 CF46K6E
EXT
111101111 MEM
1 -118
R"H215144 ' CF09K6E 2.00
8.6 318
718 B
28-114 27.314 17 -114 24S
75
R14315144 CF12K6E 3.00
187 112
1 -118 C -
28414 38414 20.1/4
255
77
205
R'3100M44
KAR -010E
1.00
5.1
3•8
518
A
28-1/4
27-3/4
17 -114
65
R*S200M44
KAK -020E
2.00
8.6
318
7/8
B
28.1/4
38 -114
17-1/4 270
70
R"5250M44
ERC -021E
2.50
8,6
1/2
1 -1/8
B
23.9 (4
38.114
17- 114 360
70
8530014144
. ERF -031 E
3,00
24.3
_ 112
1 -118
D
33
42414
32 -114
415
70
R"5050144
KAN -005E
03
5.1
318
541
' A
28-114
27 -3/4
17 -1/4
189
67
315075144
KAM -007E
0.75
Si
3IS
5/8
A
28-IM
27-314
17 -1/4
205
67
R5100144
KM-010E
1.00
5.1
3/8
5/8
A
28.114
27 -314
17 -114
220
67
R'3150L44
KAL -016E
1.50
8.6
3/8
718
B
28-1/4
38-154
17 -1(4
248
70
R`S200L44
EAV -021E
2.00 `
8.6
3+8
7/8
B
28-1/4
38 -114
17 -1/4
290
70
R*5300144
1AH -032E
3,00
13.7
1/2
1 -1/8
C
28.1(4
38-1/4
20 -114
383
70
8`02004-44
ZS15K4E
2.00
13.7
1/2
718
C
28- 114
38-1 /4
20-1/4
215
71
R'0250M44
ZS19K4E
2.50
13.7
112
1 -1/8
C
28414
38- 114
20.1/4
230
72
R'0315M44
ZS21K4E
3.00
13.7
112
1 -1 /8
D
33
42.114
32 -114
315
74
R *0350Ot44
282664E
330
13.7
112
1 -VS
D
33
42- 114
32 -114
335
74
R'0402M44
ZS39K4E
4.00
24.3
1/2
1-1/8
' D
33
42-114
32 -114
352
74
R-0600M44
ZS381(4E
6.00
24.3
1/2
1 -1/8
0
33
42.1/4
32 -1/4
383
74
R'085014144
Z545K4E
6.50
24.3
54
1 -118
D
33
42 -1/4
32 -114
405
76
8`0200144
ZF06K4E
2.00
137
1/2
7/8
C
26114
38-1(4
20 -114
230
71
R *0250144
ZFO8K4E
2.50
13.7
1/2
7,8
C
28-114
384)4
20-1 /4
240
73
R'03001-44
ZFO9K4E
3.00
137
1/2
1 -11
C
28014
38-1/4
20-114
245
73
R *0301L44
ZFi1K4E
3.00
13.7
, 112
1418
0
28.114
38. 114
20-114
255
73
R *0400144
2F13K4E
4.90
243
1/2
1 -1/8
D
33
42.1/4
32 -1/4
352
74
R*0500144
ZFI SK4E
5.00
24.3
112
1.1/8
D
33
42.1/4
32 -1/4
367
74
R *0600144
2F18K4E
6.00
24.3
1/2
1 -1,8
D
33
42 -1/4
32 -114
383
76
P *0 as
2• .
5.00
243
1/2
D
c
42.1(4
32-1/4
630
R* r., 4
2DL -R78KE
600
24.3
543
D
33
42 -1(4
32 -1!4
630
F1'0310144
2DF -F16KE
3.00
243
1/2
1 -1)8
D 42 -114
32 -1 /4
575
78
8•0400144
• 2D1-F20KE
4.00
24.3
112
1-148
D `� 42.114
32 -114
600
78
R13500144
2DA -F23KE
5.00
24.3
1/2
1 -118
D 42 -114
32 -1.14
620
78
t Estimated dbA values at 10 feet from the unit. Correction fedora: Deduct 6 &A. for 20 to 40 teL 12 dbA 8 40 to 60 feet
Ratings at the outlet of the das:t arge air. The actual measurements may vary depending upon installation vadabies.
Environmental factors may have a significant influence on this data.
See page 15 for dimensional drawings.
13
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
2) NO
FINE SCALE WINE COOLER DETAIL
Physical Dimensions All Models
Heft .I
* Figure B - 17-114" might (Uses 2 grill pieces as shown).
Figure C - 20- 114" height (Single grill piece, not shown).
15
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
FINE WINE COOLER DETAIL
NO SCALE
REVIEWED T
COMPLIAN H
NFPA?0 - NEC
MAY 09 2012
City of Tukwila
BUILDING DIVISION
Russell
Physical Data
Models
RefrfgerantConnections
Na. (
of 1
D;nlensichs
(6 hes)
Ship
Wf-
Ol .
4
a
Ail
�L4iq!u�i�d/�,�
ii[ os
1/2
1/2
1/2
1)2
AA
Suction
543
518
58
7/8
AE/A1-11A0
Suction
-
-
-
-
-
--
-
-
-
AA
AE/A1-1/AG
Hangers
2
2
2
2
A
B
G
W
18-53B
18.68E
28-76B
28-97B
-
-
-
-
-
19
19
33
33
-
-
-
-
-
-
.-
-
2755
271.4;
271/2
411/2
411/2
34
36
48
51
128.1066
-
EXT
1/2
7/8
-
--
2
37
-
45 1/2
58
28.1228
-
EXT
112
7/8
-
2
33
-
MPEL1
411/2
60
28 -1346
-
EXT
112
7/8
-
-
2
37
-
-
4512
63
8 -1808
'
EXT
1/2
1.1/8
-
-
2
55
-
8311
79
38 -195B
-
EXT
112
1.1/8
-
2
55
-
-
8311
84
48 -2126
-
EXT
1/2
1 -1/8
-
-
3
3817
361/
-
81 1,4
254
48.264E
-
EXT
112
1 -118
-
-
3
3813
381/2
8111
262
58 -2756
-
EXT
1/2
1 -118
-
3
541/2
381/2
-
9911
312
68 -3183
-
EXT
1/2
1 -1/8
-
-
4
381/2
36
361/2
117'I2
354
68 -3903
-
EXT
1/2
1.1/8
-
-
4
:R, .
36
6'
1 if
370
16-39 d
16.36:
1 •6
: • •
5 :. i
: r ►
2
19
-
--
2742
41
16-48B
16.416
EXT
1/2
5/8
618
618
2
19
-
2711
44
18-586
16-468
EXT
112
5/8
518
5/8
2
19
--
-
2715
47
26-70B
26-806
EXT
112
5(8
7188
678
2
33
-
-
411/2
54
26-878
26. 758
EXT
1/2
718
7/8
5/8
2
33
-
-
411/2
55
26 -1156
26-926
EXT
1/2
7/8
718
5/6
2
37
-
-
451/2
62
36 -1458
36 -1208
EXT
112
718
7/8
5/8
2
55
-
-
6311
78
36.1708
38.1408
EXT
1/2
1.1/8
1.116
6/8
2
55
-
-
6311
85
46 -192B
48.1648
EXT
1/2
1-1l
1-1/8
5/8
3
381/2
361/2
-
811
255
46.2306
46-1868
EXT
1/2
1.1/8
1-1/8
5/8
3
361/2
381,/2
-
811/2
285
56 -2458
56 -2109
EXT
1/2
1 -1/8
1 -118
5/6
3
5412
361/2
-
9914
306
66 -2953
66-245B
EXT
1/2
1-118
1.1/8
518
4
36112
36
3611
1171/2
353
86 -3456
66 -2808
EXT
1/2
1.118
1.1/8
518
4
3814
36
361/2
11711
368
14-426
14-378
EXT
1/2 ODS
5/8 ODS
5/8 003
5/8 003
2
19
-
-
2Y2
42
24-846
24726
EXT
1/2
7M
7/8
5/8
2
37
-
-
4511
49
24 -1058
24 -858
EXT
1/2
718
7/8
548
2
37
-
-
451
55
34- 1308
34 -1058
EXT
1/2
7/8
7/8
518
2
55
-
-
8314
79
44 -1708
44 -140B
EXT
112
7/8
1.1/6
5/6
3
381/2
361
-
811/2
251
54.21513
54 -1808
EXT
112
1 -1/8
1-118
5/8
3
541/2
361/2
-
90 +1
299
64 -25513
84-2158
EXT
1/2
1 -118
1 -1/8
516
4
361
361/2
36114
117:/2
34
Installation Notes:
(1) Install 12" away from back wall.
(2) Drain connection on AA and AE units are centered on drain pan;
and on the left end (facing air discharge) on All and AG units.
(3) For long air throw requirements, specify high throw fan guard.
(4) Unit height at drain end of hot gas models is as follows: 1,2, and 3
fan models = 15 -7/8', 4,5, and 6 fan models = 16 -1/4 ".
3 101 -1.-15
110 1'1Af3*LORI
MAST CRAM
114-4 1114
715 j.... - A
0
LCAMn+'eoOMnnraacwrs ,.
jl, Yo[AIO r1r1gP
,6eAOCAMr PIMP
7gVM.48,44 N1i
6
wccuoKmn
NOTE' INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
FINE WINE COOLER DETAIL
NO SCALE
z
•
ise
0
•
v
II`
•
w
0
In
co
Z Q
X �
cL Cp
2 GI
o
al ar%
Rr
X m o
re
Q x
fx
;n In
a 0
cn
If)
U)
IT
N
0.
W
0
togil Tao
mew
CO
01 37
Qn
Z
0 •-•t
Q
Vamp[
0
Z w
z
Z
o
V m
N 01
1-00
cop
cv
V
Z
w
LO agiq
ZN
EgUitimE 011
°I1-5(tfr OR
ZOMb0 11)
q)'-0CraCg
tX0(OFS-852
!O =W OZZ O CD
� i� W O CR
BE CONTRARY TO THE
ELI --038 I
RfiCEIVEW
CITY OFTUKWII-A
APR 24 2012
PERMIT CENTER
NUMBER: XXXX
co
PROJECT NUMBER:
0
w
0
x
I-
0
v
U
a-
a
LU
w
0
z
0
W
rn
0
0
0
iJ-
0
0
U
0
O
CC
to
Z
0
U
2
0!
fn
U
J
lY
a
a_
0
to
U
r-
an
W
0
8
Ls-
0
A
0
lL
ISSUE BLOCK W
04/05/12
m
PERMIT SET W
4
a
a
C
I-
v
t
C
0
5
U
Q as
4
C
U
0
E
a
CHECKED BY: TA/RO /SJ t
d
DRAWN BY: RRR i
FILE:
r
�I
z:
o El
o w
��• ,' mo
SHEET NAME
MEP VENDOR COORDINATION
PLAN
SHEET NUMBER:
MPEL1
0
fn
W
0
W
0
0
0
r
M
U
W
U
Q
rn
1n
0
W
U,
0
U.
W
a
a-
s
0
0
!Precautions when using the control valvel
HUMIDOR WAI,K -IN
Walk -ins are assembled from components by various manufacturers all equipment
is supplied by Total Wine vendor Modern Store Equipment. All wiring, refrigeration,
and condensate drain piping, both labor and material (including refrigeration gas) are by
General Contractor.
WAILS & CEILINGS are manufactured by Kysor Panel Systems prefabricated
panels with 4" urethane insulation and finished in Non- painted 26 gauge galvanized steel.
Modern Store Equipment erects panels at site. Exposed panel exteriors are to be finished
in painted sheetrock by General Contractor.
ENTRANCE DOOR: Eliason FCG -1 provided and installed by Modern Store
Equipment
WINDOWS are manufactured by Schott Gemtron and will be erected at site by
Modern Store Equipment There are no electrical connections required on Humidor
Doors & Windows.
AC /HUMIDITY SYSTEMS are manufactured by Mitsubishi and supplied by
Modem Store Equipment, Wiring is to be as per standard Mitsubishi wiring diagram
(attached). Equipment located by Modem Store Equipment. lll Electrical, Plumbing and
Refrigeration Connections completed by appro riate contractor.
Condensing unit is to be located on top of Humidor Box above
Evaporator Blower inside Humidor.
Mitsubishi Model: MU -AO }WA
Dimensions: 11 114h'd x 31 112 "w
Electric: 115/1/60
Electric Load: MCA 14,0
Evaporator Blower located on inside center of bac
at ceiling. Modem Store Equipment will install unit at site.
Drain connection to Mitsubishi,Specs & local Code
Mitsubishi Model: MS -AO9WA
Dimensions: W 14 x D 15 x H10 x L 32
Electric: 11511
Electric Load: M CA1.2 Amps
rail in walk -in box
Humidifier: manufactured by Nortee and supplied by Modern Store
Equipment, Wiring is to be as per standard Nortec wiring diagram
(attached).
Modem Store Equipment will mount equipment and Wire Humidistat
Control Circuit (Low Voltage). All Electrical and Plumbing connections
Completed By Appropriate Contractor.
Nortee Model: RH Space #2548758
Electric: 115/1
Electric Load: 12.7 Amps
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR COOLER DETAIL
NO SCALE
2-4. PIPE FORMING AND DRAIN PIPING
2-4-1. PIPE FORMING
• Place the drain hose below the refrigerant piping.
• Make sure that the drain hose is not heaved or snaked.
• Do not pull the hose when appykig the tape.
• When the drain hose passes the roam, be sure to wrap insulation matedel (obtainable
at a store) around it.
Note•.
Screws may damage the cower of refrigerant pipe during left piping.
Make sure not to damage the ewer of refrigerant pipe_
Left or left-rear piping
Nate:
Be sure tv reattach the drain hose and the drain cap in case of left or left-rear piping.
Otherwise, it could cause drops Owner to dry down from the drain hose.
1) Put the refrigerant piping and the drain hose together, then finely apply felt tape (7)
from the end.
Felt tape (7) overlap width should be 1/3 the tape with. Use a bandage stopper at
the end of felt tape (7).
2) Pull out the drain cap at the rear right of the indoor unit (Fig. 1)
• Hold the convex section at the end and pull the drain cap.
3) Pull out the drain hose at the rear left of the indoor unit. (Fig. 2)
• Hold the claw marked by the arrows end pull out the drain hose forward.
d) Put the drain cap into the section to which the drain hose is to be attached at the rear
of the indoor unit. (Fig. 3)
• insert nit sharp -edged took such as screwdrivers into the hole at the end of the
harp and insert the cap fully into the drain pan.
6) Insert the drain hose fully into the drain pan at the rear right afthe ndoor unit. (Fig. 4)
• Check if the hose is hooked securely to the projection of its inserting part at the
drain pan.
6) Insert the drain hose into wall hole sleeve (C), and hook the upper part of indoor unit
on installation plate (1). Then, move the indoor unit completely to the left in order to
make placing the piping In the back space of the wit easier.
7) Cut out a piece or cardboard from the shipping box, roll it up, hook it onto the back
rib, and use it as a spacer to lilt the indoor unh- (Fig, 6)
Connect the refrigerant piping with the extension pipe (B).
9) Thrust the lower pan of the Indoor tine Into the Installation plate (1).
Roar or downward piping
1) Put the refrigerant piping and the drain hose together, then firmly apply piping tape (G)
tom the end.
2) Insert the piping and the dein hose into the wall hole sleeve (C), and hook the upper
part of the indoor unit on the installation plate (1),
3) Check if the indoor unit Is hooked securely on the installation plate (1) by moving the
unit to let and right.
4) Thrust the lower part of the Indoor unit into the Installaton plate (1).
Right piping
Note:
Before performing the following, make sure that wiring is completed, and the conduit
cover its installed. (Refer to 2-3.)
1) Put the refrigerant piping and the drain hose together, position them to let side, and
then firmly apply piping tape (G) from the end.
2) Insert the piping and the vein hose We the wall hole sleeve (C), and hook the upper
part of the indoor unit on the installation plate (1).
3) Check if the indoor unit is hooked secret' an the installation plate (1) by moving the
unit to at and right.
4) Thrust the lower pad of the indoor unit into the installation plate (1).
2-4.2. DRAIN PIPING
• lithe extension drain hose has to pass through a room, be sure to wrap it with corn-
mercialy sold insulation.
• The drain hose should point downward for easy drain flow. (Fig. 1)
• If the drain hose provided with the indoor unit is too short, connect it with drain hose
that should be provided at your site. (Fig. 2)
• When connecting the drain hose to the hard vinyl chloride pipe, be sure to insert it
securely into the pipe. (Fig. 3)
uqu,d pips
Gas pipe
fie:nmicxdd rr- and
unre.h'rq.uirr(A)
Fall two (71
Pining tape 151
le-�Fory f-
Ittape(7);� -.
1I .. rsirrwge
<<vt off cl case of let
wrong.
Drain cap
G«ra•1 cam,
- -
Fig. 1
MB.
AD9WA
MS.
Al2VfA
4 Drain re
Fig -2
H:
sue:. ^.
Fig 3
dr1i1 nose
/
Fig. •4
i4,. .Y
W., '
par
.e..
ore
f.�
Fig. 1
non hose ID
..,,,,�.., 19!432 in
, an mm)
Fg. 2
21-905 in
if 7g tmn)
or more
Drain hose
Hard vinyl chloride .
Wits
I.L'r 1.3516 in
30 mm)
rig
Fig. 3
o nit ma
piping a9 . own bet
11 kiant
Tip of drain 1 -31+32
nose dipped 0° me'
St water 0
r�.
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR COOLER DETAIL
NO SCALE
lllMINIaRl
1 -2. SELECTING THE INSTALLATION LOCATION
fp100015 UNIT
• Where airflow is notbiodted.
• Where cool air speeds arer the entire room.
• Rig d wall without vibration.
• Where t is not exposed to direct sunsilre.
• Where easily drained.
• Ate distance 3 IL (1 m) or more away from yew Te
and radio. Operation of the air conditioner may inter
fere with radio or IV reception_ An ampltier may be
required for the effected device.
• In a place as far away as possible from tluaeawnt
and incandescent fights (so the infrared remote coned
can operate the air condtionet normally).
• Inhere the air Etter can be removed and replaced
Note:
khetet indoor unit at a high position on the wall where air
tan distribute over the entire room.
REMOTE CONTROLLER
• Where 1 is easy to operate and easiy vie/Die.
• Where children cannot touch S.
• Select a position about 4 R (12 m) above the floor and
check that signals from the remote controller are surely
received by the indoor unit from that position (beep or
beep beep' receiving tone sounds). Ater that, attach
remote controller holder to a pillar or wall and install
wireless remote toneroler.
Mete:
in rooms whore inverts: type fluorescent lamps are used
the signet from the wireless remora ccntrdler may not be
ro.-awed.
OUTDt QRlUNIT
• Maria is not exposed to strong wind.
• Where inflow is good and dustless_
• Where neighbours are not annoyed by operation
sand or hot air.
• Where rigid well or support is available to prevent the
incites* of operation same or vibration.
• Where there is no risk of combustbte gee leakage.
• Men Lnstafng the unit at a high level, be sure to se-
cure the Unit less.
• Where ft is et Nett 10 ft. (3 m) away from the antenna
of TV set or radw. Operation of the air conditioner may
kder ere with radio or TV reception in arose where we
caption is weak. An emplUUrer may be reined fa the
effected device.
• Install the unit horizontaty.
• Please instal it in an flea not affected by snowfall or
blowing snow. In areas with heavy snow, please instal
a canopy. a pedestal anteor some baffle boards.
14. SPECIFICATIONS
1J -1. POWER SUPPLY AND INDOOR/OUTDOOR WIRE CONNECTION
• Power should be taken from an exclusive branched dreuB.
• Wiring work should be based on applicable technical standards,
• Wring connections should be made following the diagram.
• Screws should be tightened so they wit not loosen.
Connecting wires and connecting ground wire
Cm 119 91E
• 4 or stranded conductor AWG16 AWGi or AUt1G14.
Use solid condudaAWG1
• Use double Insulated copper wire with 300V insulation.
• Use copper conductors only.
' Follow local deddeai code.
Power supply cattle and ground wire
• Use said er stranded conductor AWGid.
• Use copper conductors only.
• Follow tacal electrical code.
Note:
Men the indoor unit is poyaed from the outdoor unit, a disconnect switch may need to
be instated to power supply circuit (between indoor and outdoor unit) depending on focal
code-
1.3-2. REFRIGERANT PIPES
• Eneers that the 2 refrigerant pipes are insulated to preonrit condensation,
• Refrigerant pipe trending radius must be 4 in. (1001 o- more.
+ CAUTION •
Be sure to use the insulation of specified thickness. Excessive thickness may cause
incorrect instalabon of the indoor unit and lack orthickness may cause dew ciippage.
• This unit has flared connections on both Indoor and outdoor sides.
• Remove the outdoor units valve cover, than connect the pipe.
• Refrigerant pipes are used to connect the Indoor and cttdoor units.
• Be careful net to Crush or bend the pipe F pipe bending.
• Refrigerant adjustment... If pipe length exceeds 25 ft. (7m), additional refrigerant
(R4f0A) charge is required.
/The outdoes unit is charged with refrigerant fa pipe Iangen up to 25 It [7 me
El
specifications
Note:
it is advisable to make a piping loop neer outdoor unit
so as to reduce vibration trensmkted from hare.
For increased efficiency, install the outdoor unit in a
neaten where costnuous direct sunlight or excessive
water can be avoided as much as pestle..
Note:
When operating the ac conditioner in low outside
temperature be sure to follow the Instructions describer
below.
• Never install the outdoor unit In a place where its air
inlet/outlet side may be exposed directly to wind.
• To prevent exposure to wind, install the of door unit
with its air inlet side facing the wall.
• To prevent exposure to wind, it is recommended to in
stall a bask board on the air outlet side piths outdoo
unit.
Amid the following places for Installation where air
mmardtioner trouble is liable to occur_
• Where flammable gas could leak.
• Where there is much machine oil,
• Salty pietas such as the seaside.
• Where sulfide gas Is generated such as a hot
spring.
• iAhere there is high - frequency or wireless equipment.
.
MODEL
MBE.
A09112NA
MBE-
A15117NA
MBY •
A15/17NA
MB.
AD9WA
MS.
Al2VfA
inch (mm)
H:
For liquid
11416.35)
Pow V PHASE, H
supply z)
1..
208!23 60�
f�
11 1 60
!
Min. Circuit Ampadty
1_0 I 1 o
1 2 1.2
Fan motor FLA.
076
005
Dt iiNPF,
e
Power supply (V, PHASE, Hz)
208230. 1, 80
116, 1, 80
Mex. Fuse stn (time delay) (A)
15
15
15
20
Men. Circus Anrpedly
12
14
14
16
Fan motor (F.LA.)
0.52
0.52
0.83
0.926
Compresses
(R.L.A)
7.8
10.1
9.30
10,82
(L.R.A)
92
12
47
56
Cornet voltage
Indoor uni - Remote
controller: ('Wireless)
indoor unit - Outdoor
unit. DC12 -24V (Polar)
Indoor uni - Remote
controller: (Wireless)
Indoor unit • Outdoor
unit: AC115V
Pipe
Outside
diameter
Minimum
wall thick-
rasa
Insulation
thiekrness
Insulation mate -
eel
inch (mm)
Height difference
For liquid
11416.35)
:::
5/16 (.
Heat resisting
foam plastic
0.045 Specific
gravity
For gas
A09112NA
MS- A09WA_
3/9 (9.52)
0
('�
6/16 (9)
MSZ-
A15/17NA
Msv -A15/
17NA
MS -Al2WA
12(iz.7)
0.0315
(0�
5I16(8)
Units
MB2- A69112f15/17NA
MBY•A14f17NA
tul6 ptlttl2WA
Pipe length
65R- (20 m) mead.
651t. (20 m) max.
Height difference
40 ft. (12 m) max.
35 ft. (10 m) max.
No. of bends
10 max.
10 max.
Pipe length
Up to Z5 ft. (7m)
No additional charge is
required.
Exceedng.25 It. (7m)
%+ddtional charge is required.
(Refer to the tube below.)
Refrigerant to be
added
MSZ- A09/12/15117NA
MSY-A15117NA
1,62 oz each 5 ft. (30ghn)
MS- AO9/12VIA
1.08 oz. each 5 ft (20gim)
NOTE INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR COOLER DETAIL
NO SCALE
1.4. INSTALLATION DIAGRAM
OR UNIT I
3 -1. CONNECTING WIRES FOR OUTDOOR UNIT
1) Remove the servke panel.
2) Remove the conduit cover.
3) Fix the conduit connecter to conduit plate (A models)/conduit cover (8 models) with lock nut
then secure it against unit with screws.
4) Loosen terminal screw, and conned Indoaloutdoor unit connecting wire (A) from the indoor
unit correctly on the terminal block. Be careful not to make rr- wining. Fix the wire to the ter-
minal Mock securely so that no pan ales core is appeared, and no external tree is conveyed
to the canoe-deg section of the terminal block.
5) Firmly tighten the terminal snows to prevent diem tom loosening. Atter tightening, put the
wires lightly to confirm that they do not move.
6) Connect power soppy cord (K).
7) Connect ground wires of indoor/outdoor unit connecting wire (A) and power supply cord ix)
to the TB support.
9) Install the conduit corer,
9) Install the einem panel securely.
MUY -A I51171JA
DI U Z- 409112;15, 1711A
MU -4,09WA
PA U Y -A 15.I71-1A
Pal UZ- AO9n2115.17r4A
• Make earth wire a little longer than others,
(More than 1.12/32 in. 36 mm)
• For future servicing, give extra length to
the connecting wires.
lhdoarfoutdoor and
connecting wire (A)
rower ss.1R,ly 5514 IV()
5514 fr()
CcnfJur newer
B
MU-Al2/NA
Tarninal Aleck
• Make earth wire a fide longer than otters.
(More than 1 -12/32 in. 36 mm)
• For future servicing, give extra length to
the connecting wires.
Power supply oast In)
I ndvor'butdoor unit
corroding sure (Ai
3 -2. FLARING WORK
1) Cut the copper pipe compete with pipe cuter. (Fig. 1. 2)
2) Completely remove al buns from the cut cross section of pipe. (Fig. 3)
• Putthe end of the copper pipe to downward direction as you remove buns in order to
avoid th lot burrs drop in the piping.
3) Remove flare nuts adaddred to indoor and outdoor units, than put them on pipe having corn-
Meted burr removal. (Not possible to put them on alter flaring work.)
4) Flaring work (Fig. 4, 6). Firmly hold copper pipe in the dimension shown in the table. Sated A
mm tom the table according to the tool you use.
6) Check
• Compare the flared work with Fig. 8.
• If flare is noted to be defective, out offthe flared section and do flaring work again_
Fire diameter n
Not .
..,....:____..- A
A inch (mm)
I
I TkghtenP19 t
torque
Die rA
-
Flare nut
r,e
C' a ar Pre
pp
Fig, 5
snood-,.1h al
around
Even:engin F
a around
lr;nde is share
Ing wstr ut only
o- Etches.
'
Fig. 8
2
(6)
aeltery (Mellor (6)
2
(6)
Wireless remote controller
t
fry
Felt tape (for telt or le t-reer piping)
I
(8)
Alr cleaning flier
1
_._ -.._.
Drain hose
C per
at
Fig. 1
Good
A0
In good
Tilted Uneven Bored
Fig- 2
Bur Copper pipe
pare rsarnar
1 ` * Fiat r,.uhar
rr�}�j-���
• I l i
!!! 1 Fig. 3
(�, r Pbring roc
qry
3 i i c.,(
Gluten ryp.o riling rapt tyie
Fig 4
Die rA
-
Flare nut
r,e
C' a ar Pre
pp
Fig, 5
snood-,.1h al
around
Even:engin F
a around
lr;nde is share
Ing wstr ut only
o- Etches.
'
Fig. 8
2
(6)
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
6 HUMIDOR COOLER DETAIL
NO
ACCESSORIES
Check die fotowing parrs before installation.
ended unite
(1)
tnaeettbn plate
1
(2)
:ooneon eate fixing screw 4- a' 5 mm
5
(3)
Remote controller holder
1
(4)
faxing screw tor (a) a. 5. 1Smm(B'ack)
2
(6)
aeltery (Mellor (6)
2
(6)
Wireless remote controller
t
fry
Felt tape (for telt or le t-reer piping)
I
(8)
Alr cleaning flier
1
PARTS TO DE PROVIDED
AT YOUR SITE
re. sine to use wait hole
sleeve (C) to prevent Indoor it
indoor/outdoor connecting
wire (A) from contacting
metal parts In the wall and
to prevent damage by
rodents h case the wall Is
hollow.
Wee hole cover (DI
..teal Ito wall hole
gap with putty fHI
deers lCl
Fig the pip to
loot with pipe (wing
band 1,01
Cut riddle
antra length.
Plea Nina band
tEl
(A)
ieabonoteceor clot cam ice ngWIre
1
(B)
Extension pipe
- --
1
(C)
Wail hole sieve
1
D)
WalI he tAW(
I
(E)
Pipe kxM5 band
2 to
(F)
if indpig screw fur (E) 4 • 20 mm
2 to 5
(0)
Pipktg tope
1.
(il)
Puy
1
_._ -.._.
Drain hose
I
;6
(a loll PVC hose, 1952 in_ [15 mm)
inner die; a herd PVC pipe VPIS)
210 5
(J)
RatrlgereSCn dia
1
1)Q
Power suppy and
1
- Note;
connecting wire
PPlace lnd04f /detdpa unit On
g
and Dower supply cord (I() atlas 3 R. (1 m)
away from the TV antenna wire,.
Units should be installed by licensed contractor
according to local code requirements.
(1)
(2)
i
Rnir?U screw (Fi
Ater the leak test, apply insuteting mate-
rial tightly so that there is no gap.
%Mien the piping is to be attached to a
well containing metals (tin plated) or metal
netting, use a chemically treated wooden
piece 26132 in_ (20 mm) or thicker between
the ws/ and the piping or wrap 7 to 8 time
of insulation vinyl tape around the piping.
To use existing piping, perform COOL
operation for 30 minutes and pump down
before removing the old air conditioner.
Remake tiara according to the dimension
for new refrigerant.
(F)
(4)
mU•enaWdid
MUY- 4.15'17NA
MUe -n 7
eat 2i1511 NA'
•
L calif <p n4,n.
(100mm1 MOM
l25pi1- any b£" Jik -Ell,yh
in Rent and on both
Has of the wit.
Open ton sides of
ten, nr#,t. nr rear
Unit: inch
2-10 mm - 21 mm sic.
Dips. rive sides or
lea. 03111. or,ear
Side.
Unit: inch
£50
Unit: mm
�NraWai �
500
4 -3110 min o 21 mm Slot
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR COOLER DETAIL
NO SCALE
34. PIPE CONNECTION
• Fasten flare nut with a torque wrench as epecihed in the table.
• When restarted too tight feere nut may brake alter a long period and cause refrigerant
leakage.
Indoor unit connection
Conned both liquid end gas pipings to indoor unit.
• Apply a thin coat ofrehigeratian oil (J) en the seat surface ofpipe.
• For connection, fret aign the center, then tighten the rust 3 to 4 tuns of flare nut.
• Use tightening torque table below an a guideline for indoor and side union joint section,
and tighten using two wrenches. Excessive tightening damages the flare section.
Outdoor unit connection
Coned pipes to stop valve pipe joint of the outdoor unit in the same manner applied for
indoor unit.
• For tigMening, use a torque wrench or spanner and use the same tightening torque ap-
plied for indoor unit.
3-4. INSULATION AND TAPING
1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using piping tape (G), apply taping starting from the entry of outdoor unit.
• Stop the and of piping tape (3) with tape (with adhesive agent attached).
• Wien piping haven be arranged through above ceil'm closet or where thetemper-
abure and hunidy are high, wind additional commercially sold insulation to prevent
randensation-
41. PURGING PROCEDURES AND LEAK TEST
1) Remove service pat cap of stop valve an the side of the outdoor unit gas pipe. (The stop
valve wit network in its initial state fresh out attire factory, totally dosed with cep en.)
2) Connect gauge manifold valve end vacuum pump to service port of stop valve on the
gas pipe side of the outdoor unit.
-0101 MPa
Stop vase cap I-33 h Hg
(Torque 19 fi to F -760 in HO
A4Intro 00 Otcove A'e ,
to 307 501.511) for l IOU D
Fiend
Low
Stan va
G
S.rlon pod cap
I Torqua 13 7 to
177 Ham, 140 to
180 531-owl
Adopter for pre-
venting the back
now
Cempnuna pn enure geigs
(6N R410.4)
Pressure ]r> Jga
(ea R41OA1
C -aJge manifr,id a ah,e
t1 ml' (for R4tCW,i
Handle High
Change hose
(for RS. IOA)
Varzlum pump ( the,cccuti ,
pump wtln the fundnin ro
prevent Ins bail, flow)
A
i_antroI valve
O pert -'+. y I
Close Charge hose
-Soon ce P
When attaching the control valve
to the service port, valve core may
defer or loosen dearness pressure
is appied. This may cause spas leak,
When attaching the control valve to
the services port make sure that the
valve care is in dosed position, and
then tighten peek Do not tighten
part A a tam the body when valve
core Is in open position.
3) Run the vacuum pump. (Vitae mint ra more than 16 minutes.)
4) Check the vacuum with gauge manifold valve, then dose gauge manifold valve, and
stop the vacuum pump.
6) Leave as it is for one or two minutes. Make sure pointer gauge m.ntdd valve remains in
the same posiban. Confirm that pressure gauge shows -0.101 Mpa [Gauge] (-30 blip
[ -760 mmHg[).
6) Remove gauge manifold valve quickly y tom service port of step valve.
7) Alter refrigerant pipes are connected and evcuated tally open el stop valves on both
sides of gas pipe and liquid pipe. Operating without RAY opening lowers the perform-
ance and this causes trouble.
8) Refer to 1.3., and charge the prescribed amount of refrigerant B needed. Be sure to
charge slowly with liquid refrigerant. Otherwise, composition of the r frigerent in the
system may be changed and affect performance of the air conditions.
9) Tighten cap of service port to obtain the initial status.
10) Leak test
4-2. TEST RUN
1) Insert power supply plug into the power outlet endfor
tum on the breaker. Check that all LED lamps are not
lit If they are blinking, check that the hori-sntal vane
is installed correct'. Refer to operating instructions for
details.
2) Press the E.O. SW. Test run all be performed for 30
minutes. 0 the let side lamp of the operation Indeator
blinks every 0.5 seconds, inspect the indoor/outdoor
ant connecting wire (A) for mis- wiring. After the test run, Ito pun
emergency COOL mode (75.F 124.C] COOL) wit start.
3) To, stop operation, press the E.O. SW several times until at LED tarps turn off. Refer to
operating instructions for detells..
Checking the remote (Infrared) signal reception
Press the ON/OFF button on the remote controller and check that an electronic sound is
heard from the Indoor unit. Press the ON/OFF button again to turn the air conditioner off.
• Once the compressor slops, the restart preventive device operates so the compressor
will net operate far 3 minutes to protect the ak condtioner.
44• AUTO RESTART FUNCTION
This product is equipped with an auto restart function. When the power supply Is stopped
during operation, such as during blackouts, the function outometaly stens operation In
the previous setting once the power supply Is resumed. (Refer to the operating Instructions
for details.)
Cwdten:
• Mar test run nr remote sired reception check, turn off the unit with the E.O. SW or
the remote controller before turning off the power supply. Not doing so wit cause the
unit to start operation automatically when power supply is resumed.
TO the user
• Father installing the uni, make sure to explain the user about auto restart icnction.
• if auto restart function is unnecessary, it can be deactivated. Consult the service rep-
resentative to deadvate the function. Refer to the service manual for details.
4-4. EXPLANATION TO THE USER
• Using the OPERATING INSTRUCTIONS, explain to the user how to use the all cond-
honer (how to use the remote controller, how to remove the all leers, how to remove or
put the remote controller in the remote controller holder, how to clean, precautions for
operation, etc.)
• Recommend the user to read the OPERATING INSTRUCTIONS carefully.
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR COOLER DETAIL
NO SCALE
2 -1. FIXING OF INSTALLATION PLATE
• Find a structural material (such as a stud) in the well and fix installation plate (1) horizon-
tally with flying screws (2).
• To prevent installation piste (1) from vibrating, be sure to instal the foing screws ka the
holes Indicated h the illustration, For added support. fixing screws may also be kistaiied
In other holes.
• When bolts recessed In the accrete wall are to be utilized. secure Installation plate (1)
using 7/1S In. x 13/16 In - 7116 itr. x 1 kn. (11 11x11 • 20 mm - 11 mm x 26 rope oval hole
(17.3/4 i n. [450 mm] pitch).
• lithe recessed bolt is too tong, change It for a shorter one available in the madder..
2 -2. WALL HOLE DRILLING
1) Determine the wall hole position.
2) Drill a die. 2 -9118 in. 066 mm) hole. The outdoor side should be 6(32 to 9/32 in. (6 to 7
ndn) lower than the indoor aide,
3) Insert wall hole sleeve (C).
24. CONNECTING WIRES FOR INDOOR UNIT
Note:
When the indoor unt is powered from the outdoor unit, a tits nned switch may need to
be Installed to power supply circuit (between indoor and outdoor unit) depending on local
code.
1) Remove the front panel, (Refer to 5.1.)
2) Hook the upper part of the indoor unit on the installation plate.
3 ) Remove
corner box and conduit cover.
4) Fix conduit pipe (for roar piping) I elbow joint (for right, let, or downward piping) to con-
y of n I elb olntappearing
duR cave with lock nut. The thread part o Instated concha ow
F
pipe 1
Inside should be less than 3/8 in. (10 roan)- (Fig. 1) Elbow )dim should appear lass. than
1 -3/16 in. (30 nert) outside. (Fig. 2)
5) Process the end of ground wire (Fig. 3). Connect It to the ground terminal of Afectncai
parts box.
6) Process the end of Indoordoutdoor unit connecting wee (A) (Fig. 3). Fir it to termktel
block. Be careful not to make mis- wiing. Fix the wee to the terminal block severely so
that no pen of its core is appeared, end no external force is conveyed to the connecting
section of the terminal bloc(.
7) Firmly tighten the terminal screws to prevent them from loosening. Alter lightening, put
the wires lightly to confirm that they do not move.
8) Secure Indoor /outdoor wit connecting wire (A) and the ground wire with conduit cover.
Never fail to hook the claw of the conduit tear to the electrical box. Attach the corriut
cover securely. (Fig. 4)
A) According to the piping direction, tut off the shaded pad of the left side of bite (Fig. 5) or
caner box (Fig.6). Reinstall tomer box and (rent panel,
NS-Ae9 /Al2WA
Iletimio
• Adadmne err tree
be ilqukett
Oiekt a bat redo.
" We arkhgbogie Waled
In orderte oaamd a
caned vim totemanaL
NSSVVA
'Owe new.
eten
INDOOR UNIT Goodin
TomiiNodc ytnrrinat'•
rxI
1150 AC
1piiaaa,atMla
OUTDOOR UNIT
MSY -Al WAl 7NA
MSZ- AOD/AI 2/A15/A17NA
Relate
° Adlseenneateette rem
.
dia required,
otitk thalami coda.
..
the scallawag wormer
Inanely comma
.email Ma to terminal
- iii, Stith
'Greg laminar-
tiPaT
Cican
,71-1-i -emit biota larndnar•
i
VOIMMIvA5
1pheee, Wtta
ammonia
Puere WRAY
2011210YAC. I OSHA
1Ni+2akelk l_ x` H .0 rn
MHz
'!.
- oCtaa4vprdr)
`r3imdhngtemNrer
rf /' /J.•l,�j1�� f r/ /"!f' �,,• r 2.1942 in. (96mm)nr ram
t; /,.f.i %!/i,� :� /of?! % %`f!!!'r �� `moiling±'ffj 9 -11 /a2 in (111 mm) or root non
cede..• 14, end left hack piping (using spacer?
Carr U- e Lento goo center ride tl
et
Irstallobno
Va4i
f
plate 1.11
Levet
�.
'...
/
Wei
r
3 an.
?75 hnm).
:r more
.aCb
o Ill: • l •
_ . I . I },
. - '•
e • ] . �.
I • _
g -•
.�•
.
:~tit `
o t
°311. -
"1o0 non;
3 m
(75 me)
or more
,
Fixing so- 421 �A1vy, n the purra 1
line btirlik mark) lj.,
gig, t',b
tins scadevmh
1BSeie. Moline."
renlerierr'ia:.
2- 9rto'In.
I Fluor
(ar rnm) ride
' Same fa let hat
-,-,
WWI
21' + -Y9$in
I
042 -9.32 s
r mail
side
(65 mm) I
f ,
Ai.,
C tdc•cr
0
If ti /
ill ■ -
)•f
• '
���
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
as
.....
.a 1
,tockrrul.
h
l
;
�_�
-�r
IF
r
:�ridJit
Irx140r [4nnlnai
0 ate.
±r downward pining]
sutras.
screw or
c - d,.it pip* p or 4 Era,: Dint
lint rear .i.,r ,iprn r/ 1.211
rp �1 .
• Connect wires to the matching numbers oft,rnmals
• F'or future semicklg, give mica length to tl'i connecting
t1
Condui cover
rr
Lass than 3/6 in.
ewe �� Less than 1.3/16 in.
- (30 mm)
-�
�.".147.11W r'M (10 mm)
rE
Lode put
•_ h
Elbow joint
(fur rigrt, let, or downward piping)
F0.2
Conduit pipe a
elbow:mint Fig I
0
r., r_
,fir.
I i1.
l
+
p
- r'
Hoak
Conduit corn,
Fig.4
11r
Iroed
,tm
• Make ground
others. (More than
wire
i'..mfl
a little longer then
1-9116 in F49 mmD
Fk2 3
-----P
r::
Box
Cut off in case of Cut off in case
left piping ofleftdovnward
PPe+g
ere 5
i carats kapP
tin.
!,.t
Cut off
downward
,�� (25 men)
Cut off in case of
in case of right piping
piping
Fig n
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR COOLER DETAIL
NO SCALE
COMPLIANCE WITH
NFPANCE WITH
NEC
MAY 0 9 2012
City o Tukwila
BUILDING DIVISION
ED 1.0900,
33(
RECEIVED
CITY OF TUKWILA
APR 242012
PERMIT CENTER
ISSUE BLOCK
04/05/12
PERMIT SET 1
h
,
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE:
J,4)
o
t kr,
.
V:- 1.4 w
ott
SHEET NAME:
MEP VENDOR COORDINATION
PLAN
SHEET NUMBER:
MPEO.2
Electrical
2 in.
(5 cm
min.
Stearn
Distribution -
Pg 10
Duct Model
T
1 ft (30 curl
min.
NOTE: Additional cicarant:s
required for elowerpack
2 in.(5 cm) screws
24 in.(6 crn)1
min. Height
Modulation C>y1i08
Controls < Conlrels
Figure 2: RH Models
Table 1: RH Speotfications
Controls
Pg 15
1- 24 VAC
2.On1Off Loop
3- Ground
4- Control Signs
a Fan Security
9- Fan security
19- Fan Slart
20- Fan Starl
Note: Power wires can
also be routed through
opening in back of cabinet
120 VAC (1 phase)
Model - Part No. Volts { Ca{ acrty KV3 Amps Phase Max Ext' Standard
d1i(kg) Fuse Cvtitidet
1 110 -120 l 4 (1.8) L5
RH Space - 254875:3 208 6.9 r 3.1) 213 r 12.7
1 220 -240 ! 8 (3 -0) i 3 -0
110 -120 5 (2.3) 19
RH Duct- 2548759 208 8 7 (4.0)T 3 3
220 -240 10 (98) 38
20 202
Plumbing- -
Pg9
(7.0 / 9.5)
1/8 NPT
to 1/4
com p-
ressian
Options and Accessories
Nortec provides a complete line of options and accessories for every humidification application.
The following options and accessories are available and may have been delivered with your RH
humidifier. Refer to the installation instructions that came with the accessories for their proper
installation and operation.
Table 2: Options and Accessories
Air gap
7t$ i
Cold potable water, 30.80 psig, 1/2 in. min
Dedicated
Circuit
breaker or
disconnect
Note: 120 V connection shown
Note:
1 Install jumper between P and
terminal that corresponds to
supply voltage.
2 Dedicated external fused
disconnect must be installed.
Fusing must not exceed max
circuit protection as indicated
on the specification label.
3 Ensure that adequate power
is available to carry full
humidifier amp draw as
indicated on the specification
label.
4 Do not use neutral wire as a
ground, connect to ground lug.
5 All Wiring to be in accordance
with national and local
electrical codes.
Ground
Ground .1
Neutral ,(
Hot
Note: Connect 120 VAC,.
„Rot ", to LI
120
208
240
L11N
208 VAC (1 phase)
Ground
Ground
Hot Cr.*
Hot " -r:
rsuT.r
P
120
208
240
L1/N
240 VAC (1 phase)
Ground
Option ; Accessory Used For
Steam C7i`stributors i Adding stearn into air ducts.
Electrical
Pg 14
Ground .iF- -t1 cif:
Hot
Hot
Remote Blower Pack : Adding steam into a space remote from the humidifier.
P
120
208
240
L1/N
Digital orModulating Control Hurnidistats Controllingthe output of the:thl:midifier based on sensed RH
DigitaI or Modulating High Limit
Hu mid istats
Preventing over humidification in a duct by shutting down or
throttling down the humidifier when duct RH gets high.
Figure 3: Typical Humidifier installation
Figure 14: Primary Power Connection
Air Proving Switches Insuring humidification only occurs when air is moving in a duct.
3 I Introduction
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR HUMIDIFIER DETAIL
NO SCALE
Installation 16
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR HUMIDIFIER DETAIL
NO SCALE
Installation 114
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR HUMIDIFIER DETAIL
NO SCALE
Water Filtration Systems & Replacement Cartridges
Any questions Please Call
Thank You Eric Miller 1 -609- 298 -2100
Humidity and controls in Humidor Box
1st; Humidity the Nortec RH Space (Steam Humidifier)
Adjustment of the "Capacity Adjustment" Control setting.
This a Potentiometer that is located on the Main PC Board (Near ON/OFF switch).
The potentiometer can be adjusted between 25% and 100% Capacity.
Ideal setting is 50% to 60 %. (just low of Center on the Adjustment Potentiometer)
2nd; Humidistat Controls of Nortec RH Space (Steam Humidifier)
The Humidistat Johnson Controls (SW42AA Type SPDT Humidistat for Low or
Line Voltage)
This mechanical Humidistat is Wired up to the "1" & "2" Terminals on the Nortec..
The control wire on the Johnson Humidistat are wired to the "C "Hot &"L—Neutral-
This controller is to be set at 60% RH.
2nd: Mitsubishi Electric Mr. Slim
Vox. Fuse size
15 Amp._
Min. Circuit
Ampccity
1.2 Amp._
110 -120 Vac
Hookup
10 Prefilter 20 PreMW&
9010 -A 9C20•A
MAY 092012
Check that
0
Set up of operation of the Mr. Slim Split -Type Air Conditioner. Using the Remote .
Control Settings should be.
MODE: Cool
TEMP: Set to 76 F Deg
FAN: Medium
VAIL: Swing
Humidistat
W42AA SPDT
Johnson Controls
MPORTANT: Must have minimum 2'!° creinnce tb`i ca
e mange.
Nortec RH Space
Steam Humidifier
Water Filter Systems
FIo.Ataa
oirrioiu ont
grins up to 6m ft,Odaers. taggers. oral nigger
SSMIA mxS9x29 ° /:° 713 tffipensers upb1.200Ih. 1.67
15'Ir" x Y /z" x 25Yr 1617 O bB.� Dien 1700Is, ry . 5.01
Coarse Pre - Fitters
Indoor unit_
110-120 Vac
Hookup
Mox. Fuse size
15 Am
Min. Circuit
Ampocity
12 Amp._
Terminal Block_
1 1
Start up Settings
rx7'x14`
7 x]'x24Yir
10" Coarse plaits to remove panicles
20" Cease prefilter tomes(' panicles
' krludes 2 1/2 clearance below.
REPLACEMENT CARTRIDGES
ssrabY 1 L1 SSMIA- SSM3-A
SSAPo 6 6 7!3 SSML -A SSM3 A
SC1 lC40 40 1718 SCIO -A
St2ORC20 20 ? 11 /8 SOO-
Sr 's ke =dines are nrt d®wred for midi. mdallalm
deggre Ixa¢deerins!diancnf
�'adine reams =allege mdotedon nun rinse prom Falues waned M ®nP
fazrtvy ddaisEriended periadgmt°gelaSm#temperavnesase glimn*/
terms et 5¢arsrs rrAsduers united Warranty. resulting in a Ins Of warm
ekggn are whit E vole althea at'lis.
IMPORTANT OPERATING REQUIREMENTS:
Nin®n Maximum
AirTemperatues 50'F (1&C) 100F (37.7C)
Water Temperatures 407(4.4'C) 100T (37.7%)
Water Pressures 20PSIG 80 ?SIG
Capacity Certified ror Ohl aitie raduaionitr yr ra 9000 gYlats
Flow Rate 1.67gpm {6.3 fpm) per cartridge
alert an innate candemers are
Consult Yaur Lmal SCOTSMAN Reprasarditiui>M:
xvrAteye are mr emsiderad
cuelitdes nti ese underline
corvage Specilabms and
Mitsubishi Electric
MS— A09 /Al2WA
i ++ ^Wit I
STO RE
E End Ut!PM EH! *,RT
Scale: NTS
Humidor Wiring
Totcl Wine & Marc
Humidor Equ €prnent
03 March 10
Rev::
YOU'LL VALUE THE DIFFERENCE:
775 Corporate Woods Parkway • Vernon Hills, IL 60061 • 1- 800 - SCOTSMAN • Fax: (847) 913 -9844
Visit our website at: ws scotsman- ice.com • E -mail: customer .servicea+scotsman- ice.com
SSSSIAA 101A8 -03
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR HUMIDIFIER DETAIL
NO SCALE
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
HUMIDOR WATER FILTER DETAIL
NO SCALE
RECEIVEU
GIN OF TUKWILA
APR 2 4 2012
PERMIT CENTER
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE:
SHEET NAME:
MEP VENDOR COORDINATION
PLAN
SHEET NUMBER:
MPEO.3
1-
rn
0
W
z
0
W
0
0
v
cn
fn
U
U
n_
rn
1-
z
0
rn
a
ce
a
Performance Data
Hermetic Models ; a
a'
MODEL
NUMBER
R'H050id44
R'H075M44
R'H101M44
R'H150M44
R112O11444
R•H300M44
R'H400M44
R "H5901144
R•ti050LA4
R1H075L44
R•H100L44
R•H166L44
R'H215L44
R`H315L44
NOM
HP
0.50
0.75
1.00
1:50
2.00
3.00
4.00
5.00
0.50
0.75
1:00
1.50
2.00
3.00
R'H061H22 0.50
R140751122 0.75
R°H100H22 1.00
R'H151H22 1.50
W11201H22 2.00
R`H251H22 250
R'H301H22 3.00
R'H401H22 4.00
R`1500H22 5.00
Scroll Models
MODEL HP
+40° +34°
•-- 6000
--- 8800
----- 12200
---- 15700
5400
8100
--- 23900
-- 28000
- 34700
- 42300
11300
14300
CAPACITY =TUH AT95°FAMBIENT
SUCTION TEMPERATURE°,
+20° +10° 0°
4800 3800
7400 6200
21100
25300
1600
37500
10500 8500 - ---
13000 10400 - - --
19300 15700 - - --
22700 18100 - - --
SEM
LIM
NUM
®iG111111
-30' 4W
R
ea
28500 22700 -
34300 27500 - - ---
MINIM
7550
8950
13000
16300
22850
29840 24530
37070 30800
52690 43010
56900 47100
-- 2650
--- 5700
••-- 10190
- -- 16420
- - -- 20870
6280 5810 5120
7300 6550 5800
10600 9550 8500
14640 12950 11560
19780 16390 14520
22300
27830
38720
42550
3990
4450
6550
8920
11100
2930
3200
4750
5675
7990
20250 14960 10670
24560 18580 13200
34650 24600 18100
38200 30000 22300
2010
3350
1200
1600
4300
7940
2950
5670
2250
4690
12030
15940
8870
11320
7360
9508
3770 - - --
5943 --
7610 -_•-
Physical Data
ECR
90%
.1
5.1
8.6
8.6
8.6
13,7
24.3
24.3
5.1
5.1
5.1
8.6
8.6
13.7
6.0
6.0
6.0
10.0
10,0
16.0
16.0
28.2
28.2
CONN.
ODS. IN.
LNG.
APPROX.
SHIP WT-
ba.
152
167
195
228
Sound
Data
dbA
68
68
112
1/2
1 -1/8
1 -1/8
2
2
3
3
3/8
3r8
318
3/8
3/8
1/2
1/2
12
1/2
7/8
-1/8
5/B
5/8
5/6
718
718
7/8
778
7/8
718
390
405
152
157
180
195
243
255
170
175
180
210
223
248
260
348
380
72
72
72
75
73
73
68
68
6a
74
7
77
68
63
68
72
72
72
72
73
75
-4W REC7R Fla. LIO. SUC. SHIP WT.
11'0200144
R'02509144
2.00
250
21930
27080
20350
25050
18820
23160
17360
21320
14630
17900
12160
14840
- - --
- - --
-
TOTAL
UNIT
-
--
-
13.7
13.7
2
2
1/2
112
718
1 -1/8
215
230
71
72
0'030014144
3.00
31110
29050
26940
24860
20850
17090
- -_
___
-_
__
_ _
13.7
2
1/2
1 -1/8
305
72
W03016144
3.00
37190
34790
32330
29540
25190
20770
-- -•-
--- --
-- --
- --
--- --
13.7
2
112
1 -1 /13
325
72
10.9
56.0
20
13.9
17.0
7.5
k
2 0
10.5
+W
.r^S WIN'n1$'^f'
BnTIX10
a x^
�� �0�i
+3 -..
„�
,{(
"' kC y s
� , it
4 t R'06
C
6
50400
47800
44200
41100
-s.
3450}
x
28800
28.1
35.0
15.3
82.0
3.2
243
3
12
1-1/8
30.7
74
4 4 ar':,i•_ '_s11
34.9
., {
.. 'S
?f�
32
24.9
31.0 8.6 45.0 2.1 11:2 150
-.._
. -..
.._
re6870
_._-
nw��
`•_
21.4
123.0
2
�a- .,.y�? r_
;�«uxlb
A 11'02001.44
11•02901.44
200
230
-
---
_ -•
- -
-•_
--
--
- --
- --
- --
11330
13800
9400
12100
7670,
10060
8980
6110
7 724
4390
5800
13.7
13.7
2
2
172
112
778
778
230
240
71
73
11'03001.44
• 3.00
-- --
_ -_-
--
__.._
_ --
15.960
13380
11360
9680
8670
6520
13,7
2
12
1.118
245
73
R00301L44
3.00
-
- --
2.0
--
--
18760
15530
12580
11250
10160
3110
13.7
2
1/2
1 -1/8
255
73
R•04001A4
4,00
----
- - --
--
--
- --
24090
19800
15940
14080
12430
8600
24.3
3
1+2
1.12
352
73
R•0500L44
5.00
-
--
R1H0751422
---
----
28490
23650
19250
17270
13200
11990
24.3
3
1/2
1 -1 /a
367
74
R•06001A14
6.00
-
- --
--
- ----
- ---
33400
27400
22100
19800
17600
13600
24.3
3
12
1 -1/8
383
76
R 001112
2.00
21020
19390
18270
16900
13960
----
---
---
- --
- ---
--
16.0
2
112
718
215
71
13'0250M22
250
25340
23400
21310
19940
16370
2.0
- - --
- --
- --
- - --
--
16.0
2
1(2
1 -1/8
230
72
11003006122
3.00
30440
28170
25840
23470
19330
- ---
- - --
- - --
- - --
-•--
- --
16.0
2
1/2
1 -118
305
72
2 R•0301M22
3.00
38180
34720
31890
28310
22730
- - --
- - --
- - --
- - --
--
- --
16.0
2
1/2
1 -1/8
325
72
2 R'0400M22
4.00
43320
39910
37460
33680
27750
- - ---
- - --
- --
- ----
- --
--
28.2
3
1/2
1 -1/8
352
74
R•0600M22
8.00
52390
48370
43930
41010
34010
- - --
99.0
-••
--
23.0
--
28.2
3
112
1 -118
383
74
11'06506122
6.50
63120
57830
51850
48280
41130
- -•-
25.6
31.0
9.6
--
--
28.2
3
5/8
1 -1/8
405
76
NOTE: For &0 °F ambient multiply capacity by 1,03. Reduce capacity by 3% for each 5° imireese in ambient terrperakn'e_ CorutdI factory for capacities above
t Estimated dbA values at 10 feet from the twit Correchcn factors: Deduct 6 dbA. for 20 to 40 feet, 12 dbA @ 40 to 60 feet.
Ratings at the outlet of the discharge air. The actual measurements may vary depending upon installation variables.
Entrtramental factors . may have a significant.initiferc nkl,this data
4
°F
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
BEER COOLER DETAIL
NO SCALE
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
BEER COOLER DETAIL
NO SCALE
Electrical Data
Hefinefic
MODEL
NUMBER
Models
COMP.
MODEL
NUMBER
•
AMPS 0 230/1/60
AMPS 42 208/230/3/60 AMPS (6480/3/60
LIN I2.1 .1-:-.=.• :l
COND
FLA
TOTAL
UNIT
All
LI -uld
COMPRESSO-
CON)
FLA
TOTAL
UNIT
AE
kt11, ,,, .•I- 1111
COND TOTAL
FLA UNIT
ALA
IRA
RIA
LRA
RLA LRA
R11-1050M44
R343C1 E
5.4
24.1
1.0
7.4
. 150
--- -
12.3
15.0
4.3
27.0
R "H075M44
RS70C1E
7.0
34.2
1.0
9.0
15.0
41
31.0
1.0
6.7
15.0 -- - -- -- --
R'H101 M44
RS97C1 E
11.0
51.0
20
14.0
17.0
70
35.0
0 0
10.0
--
15 0 - --
HIM --
R'H150M44
CS12K6E
10.9
56.0
20
13.9
17.0
7.5
51.0
2 0
10.5
-
15.0 - - -- - - ---
R'H201 M44
R1H300M44
CS18K6E
CS20K6E
160
18.0
820
06,0
2A
2.0
19,0
21.0
230
26.0
10.4
11-4
65.0
75.0
2.0
2.0
13,4
14.4
16.0 ®111111111111
19.0
R'H400M44
CS27K6E
23.9
95,4
3.2
28.1
35.0
15.3
82.0
3.2
19.5
24.0. -•_- ---- -- -- - -- -- _ -_
R'14500M44
CS33K6E
30.7
125.0
3.2
34.9
43.0
20.7
90.0
32
24.9
31.0 8.6 45.0 2.1 11:2 150
'
�
169.0
112
a"6.0
36.0
21.4
123.0
2
37
-
R 075L44
RS70C1E
7.0
34.2
1.0
9.0
15.0
4.7
31.0
1.0
arose
15.0
R•H100L44
RS97C1E
11.0
51.0
1.0
130
16.0
7.0
35.0
1.0
9,0
15.0 -
II
R'H166L44
CF06K6E
11.4
59.2
2.0
14.4
18.0
7.0
52.0
20
10.0
15.0' --
--
R1-1215L44
CFO9K6E
16.7
87.0
2.0
19.7
24.0
10.2
72.0
20
13.2
16.0 - - -- --
INII__--
R`1-1315L44
CF12KeE
20,5
105.0
2.0
215
28.0
123
85,0
2.0
15.3
18.0 42.0 1.0 15.0
R1-1051H22
ARTI32C1
5.9
30.0
1.0
7.9
15.0
-----
--
_ -__
__
-
- --
-_ --
- -_
23,7
30.0
R1H0751422
RSE -0075
7.1
35.5
1.0
9.1
15,0
- _
-_-
_ -__
- -_
____
_. -
__ -_
_-
- - -_
_
R•H100H22
RS70C1
7.0
342
1.0
9.0
15.0
4.7.
31.0
1.0
6.7
15.0
- --
169.0
- ---
--- --
44;0.
RI-1151E122
CRIBKQ-
9,0
4t0
2.0
120
150
6,0
44.2
20
9.0
15.0
- -
--
----
_-
---
R'H201 H22
CR24KQ
13.5
70.5
20
16.5
20.0
7.5
40.0
2.0
10.5
15.0
- --
- - --
20
17
20.0
R1H251 H22
CR33K0
16.0
75.0
2.0
19.0
23.0
10.6
69.0
20
13.6
17.0
41
31.6
1.0
6.2
15.0
R1-1301 H22
CR41 KQ
19.4
110.0
2.0
224
28.0
13.1
80.0
20
16.1
20.0
5.9
42.0
10
7.4
15.0
FrH4011-122
CR53K0
29.0
140,0
3.2
332
41.0
16.0
107,0
32
222
27,0
91
55.0
21
11.7
15.0
R`H500H22
CRN-0500
34.3
142.0
3.2
38.5
43.021.4
1
130.0
32
25.6
31.0
9.6
65.0
21
12.2
15.0
Scroll Models
Connections
Motor
Amps
230/1
Heater
Amps
230V
Heater
Amps
46011
Number
of
Ha • =ra
Unit Dimension.
Inches
All
LI -uld
AA
Suction
AE
Suction
AA
AE
O.
B
C
18418
131020011144
2815K4E
13 6
55.0
20
17,5
20,0
9.3
55.0
2.0
12.3
15.0
4.3
27.0
1.0
5.B
15.0
R10250444
2619K4E
16.4
73.0
20
20,3
25.0
9.7
63.0
2.0
12.7
15.0
5.0
31.0
1.0
6.5
15.0
R"0300M44
ZS21 K4E
16.4
88.0
20
20.6
25.0
11.1
770
2.0
14.1
17.0
5.7
39.0
1.0
®
150
R'O301M44
7S26K4E
20.7
109.0
20
24.9
30.0
13.6
88:a
2.0
16.6
200
71.
44.0
1.0
7/8
15.0
2
37
-
-
45-1/2
28 -i22B
112
718
-
2
.+.. -_
-
R °06t><}M4d
Z538K4E
�
169.0
112
a"6.0
36.0
21.4
123.0
2
37
-
9.6
62.0
38 -1608
1/2
. �...
w 3
3,0
2
arose
"or
s
63-1/2
u..
yw
a
1 -1/8
3.0
R°0200L44
ZFO6K4E
13.6
55.0
20
16:6
20.0
9.3
55.0
20
12.3
16.0
4.3
27,0
1,0
:
15.0
R10250144
ZFO8K4E
16.4
73.0
20
19.4
250
9.7
63.0
20
12.7
16.0
5.0
31.0
1.0
58 -275B
15.0
11'0300144
ZF09K4E
16.4
88.0
20
19.4
25,0
11.1
77.0
2.0
14.1
17.0
39.0
1.0
IN
15.0
R'03011.44
ZF11K4E
20.7
109.0
20
23,7
30.0
13.6
88.0
20
16.6
20.0
44.0
1.0
15.0
R`0400144
ZF13K4E
26.8
129.0
3.2
31,0
38.0
15.0
99.0
3.2
19.2
23.0
8.2
57.0
2.1
10.8
19.0
W05001.44
ZFt 5K4E
31.5
169.0
32
35.7
44;0.
21.4
123.0
3.2
25.6
31.0
9.6
62,0
2.1
12.2
23.0
R'0600L44
ZFIBK4E
- ----
-----
33
- --
23.9
156.0
3.2
28
340
9.3
700
2.1
11.9
23.0
R'0200M22
ZS15K4E
13.6
55.0
20
17
20.0
9.3
55.0
2.0
12,3
15.0
4,3
21.0
1.0
150
P'0250M22
ZS19K4E
16.4
73.0
20
20.3
25.0
9.7
63.0
2.0
12.7
15.0
50
31.0
1.0
112
15.0
R'0300M22
ZS21 K4E
16.4
880
20
20:6
25.0
11.1
77.0
2.0
14.1
170
5.7
39.0
1.0
7.2
15.0
R'0301M22
ZS26K4E
20.7
109.0
20
24.9
30.0
13.6
88.0
2.0
16.6
20.0
7.1
44.0
1
8,6
15.0
R'0400M22
Z330K4E
26,8
129,0
32
31 0
38.0
15.0
99.0
3.2
19.2
23.0
8.2
49,5
2,1
10.8
15.0
R"0600M22
Z838K4E
31.8
169.0
32
36.0
44.0
21.4
123.0
3.2
25.6
31.0
9.6
62,0
2.1
122
15.0
R'0650M22
ZS45K4E
- - --
----
- --
- - --
- --
23.9
156.0
3.2
28.1
34.0
9.3
700
2.1
11.9
15.0
5
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
2 BEER LE COOLER DETAIL
NO SCA
Walk -In and Fine Wine
Refrigeration Wiring
115
V
115
V
Defrost
Clock
ouble
Switch b
EC
olenai
Eva p
Fens
To Any
Additional
Units
We k -In Controls
Evaporator, Thermostat, Solenoid,
Double Throw Switch (by IC), and
Defrost Clock, to be wired per
diagram above
Walk -In Condensing Unit
Walk -in condensing units to be
located on roof of building
above walk -in location.
Permits, as required, by GC.
Provide 230v 3 ph with fused disconnect
120v service receptacle. Compressor(s)
equipped with PCS motor(s)
N
Normal Operation:
*Thermostat cycles solenoid
*Fans operate continously
Defrost:
*Clock kills t -stat and solenoid
*Fans operate continously
Fans Switched Off:
*Switch kills t -stat and solenoid
whenever it turns off to avoid
liquid slug at compressor
x';1[4]
and
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
) BEER COOLER DETAIL
6 NO SCALE
Physical Dimensions - All Models
Figure 2
r'>
21 do
W dnensi suf. ary in nkha
PI mounand hors are .°;
•177 " hilt td 2 H modes U_=es 2 Oece esdes slNe:vR
:KV high or .h add i -!P 2nd at Scot sexWls Uses pets 02;
5
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
3 BEER SCALE COOLER DETAIL
N
ALL- TEMP -- Low Profile unit coolers
MODEL
Connections
Motor
Amps
230/1
Heater
Amps
230V
Heater
Amps
46011
Number
of
Ha • =ra
Unit Dimension.
Inches
All
LI -uld
AA
Suction
AE
Suction
AA
AE
O.
B
C
18418
'MODS
5/SODS
-
1
-
2
19
-
-
27-1/2
18-538
1/2
5/8
-
1,0
-
2
19
-
-
27 -1/2
18 -668
MEP VENDOR COORDINATION
PLAN
112
518
1.0
--
2
19
-
27 -1/2
28-768
1/2
5/8
-
c‘i
2
33
-
-
41-1/2
28 -978
1/2
7/8
-
-
2
33
--
-
41 -1/2
28 -1068
1/2
7/8
2
37
-
-
45-1/2
28 -i22B
112
718
-
2
33
-
-
41 -1/2
28 -1348
112
718
-
2
37
-
-
45-1a
38 -1608
1/2
1 -1/8
3,0
2
55
-
63-1/2
38 -1956
1/2
1 -1/8
3.0
2
55
63-1/2
48 -2128
1/2
1 -1/8
4:0
3
36 -1/2
36 -1/2
81 -112
48 -2648
112
1 -1/8
4.0
3
36 -1/2
36-1/2
81 -1/2
58 -275B
112
1 -118
5.0
3
54 -1/2
36-1/2
99 -1/2
68-39013
36-1
36
�rT^rTT?4a�rr
T*r�wr
, :w ��.,
.a .:, r was
''�r�rw+�r*u��ri?-
!+!►�*i�a�
Ord *.,
16-48B
. 16-41B
1/2
5/8
5/8
1,0
4.4
2,2
19
27 -1/2
16 -586
16 -468
112
5/8
5/8
1.0
4.4
2.2
i9
27 -1/2
26 -702
26 -60B
1/2
5/8
7/8
20
7,0
3.5
33
41 -1/2
26 -876
26 -75B
1/2
7/8
7/8
2.0
7,0
3.5
33
41 -1/2
26 -1158
26 -92B
1/2
7/8
7/8
2:0
8.7
4,4
37
45 -1/2
36- 1458
36 -1206
1/2
7/8
7/8
3.fi
13.0
6.4
55
63 -1/2
36 -1708
36-1408
112
1-118
1 -1/8
3.0
13.0
6.4
55
63 -1/2
46 -1928
46.2308
46 -1648
46 -1658
1/2
1/2
1 -1/8
1.1/8
1 -1 /8
1 -1/8
4.0
4.0
EE
36.1 2
36 -1/2
--
81 1/2
56 -245B
56 -2108
1/2
1 -1/8
1 -1/8
5.0
18.8
10.9
54 -12
36 -1/2
-
99-12
63 -2956
66 -24581
112
1 -1/8
1 -1/8
60
22.61
13.0
36 -1/2
36
36 -1/2
117 -112
66 -3458
66 -2808'
1/2
1 -1/8
1 -1 /8
6.0
t
13.0
36 -12
36
36 -1/2
117 -1/2
14-428
14-37B
1120DS
5/8 ODS
5/8 ODS
1,0
stmlnis
2
19
-
-
27-1/2
37
-
-
45-1/2
24 0 B
24 -85B
7/8
2.0m
37
-
-
45-112
34 -130B
. 34 -1056
1/2
718
7/8
3.0
13.0
MIME
55
-
-
63 -1t2
44-170B
44 -14GB
112
7/8
1-1/8
4 0
1 7.4
36-1/2
36 -1/2
-
81 -1/2
54 -215B
54-1 80Bt
1 -118
1 -1/8
5.0
10.9 -
- 3
54 -1/2
36 -1/2
-
99 -1/2
64 -255E
64 -21581
1 -118
1 -1/8
6.0
13.0
4
36 -1/2
36
36 -1/2
117 -1/2
t 230/3/60 heaters are standard on these models. Heaters are wired single phase for all other models.
460 /1/60 motor amps = 1/2 the 230/1/60 value.
All models require externally equalized expansion valves.
Installation Notes:
(1) Inslnt 12 away from bock wall.
(2) Drain connection on AA and AE units ere located In the center, rear of the drain pan.
(3) For fang air throw requirements, specify high throw fan guard.
yr
12'111 l 112
1131 1'1T SLOTS
I- 2 74
.- 74 MFI CROON
I- +11:2 -4 I--1 it
10 AND 440 tWIN1o4ocI 0ur8
473 B&CK MID Taw
-
v
I U-
I^
�..{L .+..ti;
cif
Y01:
_ 1,yJ � ✓r7 �
.31
:T
r.
iY
,y l
1
y -�
O.
. -
1
,- ELE;:T rc*L KNt,.NOUTS
,q E41434 ,lc r a me
UFdIN -M A� W ITS
28
3VC:10NC011i 31!0
NOTE: INFORMATION SHOWN IS FOR REFERENCE ONLY AND IS TO BE REPLACED WITH SITE SPECIFIC
SPECIFICATIONS. VENDOR TO PROVIDE STANDARD DETAIL SUFFICIENT FOR GC INSTALLATION.
BEER COOLER DETAIL
NO SCALE
COMPLIANCE WITH
NFPA7QCE WITH
NEC
MAY 0 9 2012
iUILD of Tukwila
_______________BUILDING DIVISION
RECEIVES
CITY OFTUKW LA
APR 2 4 2012
PERMIT CENTER
■
04/05/12
PERMIT SET
■
....
300 ANDOVER PARK WEST
I e l TUKWILA, WA 98188
IRE
ISSUE BLOCK
04/05/12
PERMIT SET
CHECKED BY: TA/RO /SJ
DRAWN BY: RRR
FILE:
4/11.40,,t
fit#',Ag'rf,- 4 ,
•i
t•
WILY'
ISHEET NAME:
MEP VENDOR COORDINATION
PLAN
SHEET NUMBER:
i _
PE0.4
k