ELECTRICAL PERMIT
Permit Number: EL12 -0615
Issue Date: 07/20/2012
Permit Expires On: 01/16/2013
Owner:
Name: GRA INVESTMENTS LLC
Address: 4702 FOREST AVE SE , MERCER ISLAND WA 98040
Contact Person:
Name: WAYNE TEDROW
Address: PO BOX 24567 , SEATTLE WA, 981245
Contractor:
Name: MCKINSTRY ELECTRIC
Address: PO BOX 24567 , SEATTLE WA 98124
Contractor License No: MCKINE *982KG
Phone: 206 - 786 -1943
Phone: 206 832 -8513
Expiration Date: 05/10/2014
DESCRIPTION OF WORK:
INSTALL NEW 600A 480V MAIN SERVICE PANEL, 75 KVA TRANSFORMER AND POWER TO
MACHINES
THIS PERMIT ACCOMPANIES CONDUIT ONLY EL 12 -0596
Value of Electrical: NRES: $25,000.00
RES: $0.00
Type of Fire Protection: UNKNOWN
Electrical service provided by: PUGET SOUND ENERGY
Permit Center Authorized Signature:
701.
Fees Collected:
National Electrical Code Edition:
$653.13
2008
Date: ? r!-0 - I 2.
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of permit does not p -sume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction o erformance of w•�k. /: am authorized to sign and obtain this electrical permit.
Signature:
Print Name:
- lJ/-i-eJo 6-44 rtir.4s�J
Date: 7/2(Y/ Z
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: EL -4/10
EL12 -0615 Printed: 07 -20 -2012
PERMIT CONDITIONS
Permit No. EL12 -0615
* *ELECTRICAL **
1: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical Inspector
at each work site.
2: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical Inspector.
3: All electrical work shall be in accordance with NFPA 70 - NEC, and requirements for electrical installations, Chapter
296 -46B WAC.
4: When any portion of the electrical installation is to be hidden from view by permanent placement of parts of the
building, such equipment shall not be concealed until it has been inspected and approved by the Electrical Inspector.
5: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any violation
of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related documentation that
presumes to grant this authority are therefore not valid.
6: Any change in the scope of work described by the electrical work permit shall require additional work permits. Where
approved plans have been issued, revisions to the plans and additional review may be required.
doc: EL -4/10
EL12 -0615 Printed: 07 -20 -2012
CITY OF TUKW
Community Developmen Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
littp://www.TukwilaWA.gov
Electrical Permit No.
Project No.
Date Application Accepted: ,.
Date Application Expires:
(For office use only),
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
SITE LOCATION
King Co Assessor's Tax No.: 3365901650
Site Address: 14600 INTERURBAN AVE. S. Suite Number: Floor:
Tenant Name:
MACHINE TOOLWORKS
PROPERTY OWNER
Name: WAYNE TEDROW
Name: GRA INVESTNENTS LLC
City: SEATTLE State: WA Zip: 98124
Address: 4702 FOREST AVE SE
Email: waynet @mckinstry.com
City: MERCER ISLAND State: WA
Zip: 98124
CONTACT. PERSON — person receiving all project
communication
Name: WAYNE TEDROW
Address: PO BOX 24567
City: SEATTLE State: WA Zip: 98124
Phone: (206) 786 -1943 Fax:
Email: waynet @mckinstry.com
New Tenant: m Yes ❑..No
ELECTRICAL CONTRACTOR INFORMATION
Company Name: MCKINSTRY ELECTRIC
Address: PO BOX 24567
City: SEATTLE State: WA Zip: 98124
Phone: (206) 832 -8513 Fax:
Contr Reg No.: MCKINE *982kg Exp Date: 05/10/2014
Tukwila Business License No.: BUS - 0993232
Valuation of Project (contractor's bid price): $ 25,000
Scope of Work (please provide detailed information):
INSTALL NEW 600A 480V MAIN SERVICE PNL, 75KVA TRANSFORMER AND POWER TO MACHINES
Will service be altered?
D
Yes ❑ No Adding more than 50 amps? 0 Yes ❑ No
Type of Use: SALES SHOWROOM SET UP WITH MACHINES FOR DEMONSTRATION
Type of work:
❑ New ❑ Addition ❑ Service Change
❑ Low Voltage ❑ Generator ❑ Fire Alarm
Property Served by:
m Puget Sound Energy ❑ Seattle City Light
H:\Applications\Forms- Applications On Line \2011 Applications \Electrical Permit Application Revised 8- 9- 11.docx
Revised: August 2011
bh
• Remodel
❑ Telecommunication
❑ Tenant Improvement
❑ Temporary Service
Page I of 2
RESIDENTIAL
NEW RESIDENTIAL SERVICE
❑ New single family dwellings $152.85
(including an attached garage)
❑ Garages, pools, spas and outbuildings $81.90 ea
❑ Low voltage systems
(alarm, furnace thermostat) $59.85 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
❑ Service change or alteration $81.90
(no added /altered circuits)
❑ Service change with added /altered circuits $81.90
number of added circuits $11.55 ea
❑ Circuits added /altered without service change $54.60
(up to 5 circuits)
❑ Circuits added /altered without service change $54.60
(6 or more circuits) $7.65 ea
❑ Meter /mast repair $68.25
❑ Low voltage systems $59.85
(alarm, furnace thermostat)
MULTI - FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
❑ Temporary service (residential) $63.00
❑ Temporary service (generator) $78.75
❑ Manufactured /mobile home service $84.00
(excluding garage or outbuilding)
❑ Carnivals $78.75
Number of concessions $10.50 ea
PERMI>TK,APPLICATION NOTES -
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR ECTRICAL CONTRA 'OR:
Signature:
/6i —L(,
Print Name:
Date: 07/02/2012
WAYNE EDROW Day Telephone: (206) 786 -1943
Mailing Address: PO BOX 24567 SEATTLE WA 98124
City
H:Wpplications\Forms- Applications On Line \2011 Applications\Electrical Permit Application Revised 8- 9- 11.docx
Revised: August 2011
bh
State Zip
Page 2 of 2
Parcel No.:
Address:
Suite No:
Applicant:
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -43 1 -3670
Fax: 206-431-3665
Web site: http: / /www.TukwilaWA.gov
3365901650
14600 INTERURBAN AV S TUKW
MACHINE TOOLWORKS
RECEIPT
Permit Number:
Status:
Applied Date:
Issue Date:
EL12 -0615
ISSUED
07/02/2012
07/20/2012
Receipt No.: R12 -02174
Initials: WER
User ID: 1655
Payment Amount: $378.00
Payment Date: 07/20/2012 02:50 PM
Balance: $0.00
Payee:
MCKINSTRY CO
TRANSACTION LIST:
Type Method Descriptio
Amount
Payment Check
Authorization No.
ACCOUNT ITEM LIST:
Description
12130
378.00
Account Code
Current Pmts
ELECTRICAL PERMIT - NONR
000.322.101.00.00
Total: $378.00
378.00
doc: Receiot -06
Printed: 07 -20 -2012
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -43 1 -3670
Fax: 206-431-3665
Web site: http: / /www.TukwilaWA.gov
Parcel No.: 3365901650
Address: 14600 INTERURBAN AV S TUKW
Suite No:
Applicant: MACHINE TOOLWORKS
RECEIPT
Permit Number: EL12 -0615
Status: PENDING
Applied Date: 07/02/2012
Issue Date:
Receipt No.: R12 -02031
Initials:
User ID:
Payee:
WER
1655
Payment Amount: $653.13
Payment Date: 07/02/2012 01:29 PM
Balance: $0.00
MCKINSTRY CO
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 12104 653.13
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
ELECTRICAL PERMIT - NONR
ELECTRICAL PLAN - NONRES
000.322.101.00.00 522.50
000.345.832.00.00 130.63
Total: $653.13
doc: Receipt-06 Printed: 07 -02 -2012
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
6,1-06(c
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451 �r
Project:
ti
Type of Inspection:
Address. /14$00
/A
,g
�d
Date Called:
Special Instructions:
Date Wanted:.
(t ZO
a.m
p.m.
Requester:
Phone No:
Approved per applicable codes. EJ Corrections required prior to approval.
COMMENTS:
l
Inspector:
I,t 2-0�(�
I I REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
D ate:
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION `p
6300 Southcenter Blvd., #100, Tukwila: WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
Project: p� t j d/
0.5
Type of Inspection:
Address: it ! 00
ii
„ p
Date Called:
Special Instructions:
Date Wanted:.
: p.m.
Requester:
Phone No:
Approved per applicable codes.
VICorrections required prior to approval.'
COMMENTS:
t6J1Prientr-,
roAia/ t",045
4, sr ice'
Inspector: _ %rl A6 l t(
Date: vi
F-7 REINSPECTION FEE REQUIRED. Prior to next inspection, fee must ,.be:
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection:.
INSPECTION RECORD.
Retain copy with permit 7/
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila: WA 98188 (206)431 -3670'
Permit Inspection Request Line (206) 431 -2451
Project:
14 es/ HIA/
9ie
Type of Inspection:
171,v2.:,.
Address:
/1.4/0 .r.j7 '
,lr
lifr $
Date Called:
Special Instructions:
Date Wanted:.
..2:7--/ 2.- ,
a.m.
tp:m.
Requester:
Phone No:. -...
NApproved per applicable codes. El Corrections required prior to approval:
COMMENTS:
/C ✓n tit cc"--
Inspector: c Y
Env/ h7
r
REINSP TION FEE REQUIRED. Prior to next inspection 'gee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection
;2 : (9- 78U0-L1793
•
OFF HOURS INSPECTION
Reimbursement authorization/approval to conduct inspection activities during off hours.
Date: -7/Z.40 20 /1
Requested By: 01 CK ;r5t✓*c)__ €fir.4rir
Firm /Company: (i4 C K s t
Permit Number: EL / Z /S
Fat. / An/oCA)
Inspection Information
Project Name: 114 I4-Gv1 i N-C TO o ( Goo
Project Address /Location:
y (0 OD J,N -1-e r- u r bp,.) 14u . S
Requested Date for Inspection: 71 Z2-( Zo I Z
Contact Name: 0 4v 7 u ,,,,, a-..1
Requested Time: 3 00 A
Phone Number: Zt to — 784,- bgyy
Special Conditions for Consideration:
** Contractor will be charged a minimum for four (4) hour inspection time for
any off -hours inspection work at $94.50 per hour (minimum total of $378.00).
This is to be paid at the time of request. **
The undersigned, as an authorized representative of the above firm, hereby agrees to reimburse the City for its
overtime inspections on the above referenced project. A separate invoice will be issued for all inspection time in
excess of (4) ho rs.
Signature: 1n
Printed Name: PAtJ ' qt cr 4/.1
Date: ‘7/2-2 Zo/ Z
!StMOWED
ov TUKWILA
CitvUs Oniyn
Approved: Disapproved: Remarks:
Date of Approval /Disa • II • al:
Authorized Reviewer:
1AL20 nizi
effitig COVER
W: \Permit Center \Templates \Forms \Off Hours Inspection.docx
PERIrMT GOOIiD'COPY
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: EL12 -0615 DATE: 07 -02 -12
PROJECT NAME: MACHINE TOOL WORKS
SITE ADDRESS: 14600 INTERURBAN AV S
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # After Permit Issued
DEPARTMENTS:
( '�'�
� ilding 'vision
Public Works
n
Fire Prevention
Structural
n
Planning Division
Permit Coordinator
u
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Incomplete
DUE DATE: 07 -03-12
Not Applicable
n
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROUTING:
Please Route % Structural Review Required ❑ No further Review Required n
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
DUE DATE: 07 -31 -12
Approved In Approved with Conditions Not Approved (attach comments)
Notation:
REVIEWER'S INITIALS: DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents /routing slip.doc
2- 28 -02-
Contractors or Tradespeople Peer Friendly Page
•
Electrical Contractor
A business licensed by L &I to contract electrical work within the scope of its specialty. Electrical
Contractors must maintain a surety bond or assignment of savings account. They also must have a
designated Electrical Administrator or Master Electrician who is a member of the firm or a full -time
supervisory employee.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent Company
MCKINSTRY ELECTRIC
2067623311
Po Box 24567
Seattle
WA
98124
King
Limited Liability Company
FACILITY ELECTRICAL SRVCS LLC
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Specialty 1
Specialty 2
602198837
Active
MCKINE *982KG
Electrical Contractor
5/7/2002
5/10/2014
General
Unused
Electrical Administrator INFORMATION
License LANDIEE923J9
Name LANDIN, EDWARD E
Status Active
Business Owner Information
Name
Role
Effective Date
Expiration Date
CT CORPORATION SYSTEMS
Agent
05/07/2002
Bond Amount
BLACK, STEPHEN
Partner /Member
05/07/2002
929495258
ALLEN, DEAN C
Partner /Member
05/07/2002
ELECTRICAL CITATION
MOORE, DOUGLAS J.
Partner /Member
05/07/2002
TRAVELERS CAS &
SURETY CO
TEPLICKY, J. WILLIAM
Partner /Member
05/07/2002
05/04/2010
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
2
WESTERN SURETY CO
929495258
05/04/2010
Until Cancelled
19.28.101 RCW
ELECTRICAL CITATION
$4,000.00
04/05/2010
1
TRAVELERS CAS &
SURETY CO
103737415
04/29/2002
Until Cancelled
05/04/2010
$4,000.0005/07/2002
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information No records found for the previous 6 year period
Summons /Complaint Information Summons and Complaints are not filed with the department for this contractor type
Warrant Information Warrants are not filed with the department for this contractor type
Infractions /Citations Information
Infraction / Citation
Date
RCW Code
Type
Status
Violation Amount
ESWAT00252
5/11/2009
19.28.010 RCW
ELECTRICAL CITATION
Satisfied
$250.00
ESWAT00251
5/11/2009
19.28.101 RCW
ELECTRICAL CITATION
Satisfied
$150.00
EBOES00609
10/21/2011
19.28.101 RCW
ELECTRICAL CITATION
Satisfied
$250.00
https: // fortress .wa.gov /lni /bbip /Print.aspx 07/20/2012
LIGHTING
w-1
FLUORESCENT FIXTURE, DRAWN TO SCALE ON PLANS - LETTER IN FIXTURE
INDICATES SWITCH LEG CONTROL
FLUORESCENT STRIP FIXTURE, DRAWN TO SCALE
0 FIXTURE CEILING MOUNTED
FIXTURE WALL MOUNTED
FIXTURE RECESSED WALL MOUNTED
BATTERY PACK
LIGHTING FIXTURE, WALL WASHER
TRACK UGHT
FIXTURE SUPPLIED FROM EMERGENCY CIRCUIT
I EXIT SIGN - DIRECTIONAL ARROWS AS INDICATED, SHADED SIDES ILLUMINATED
0-4 0-* UGHTING STANDARD - FIXTURE(S), POLE & BASE
0 UGHT FIXTURE TYPE - SEE FIXTURE SCHEDULE
1 a
a
• 0
$o b SWITCH - SINGLE POLE SUBSCRIPTS a,b, etc., DENOTES CIRCUIT CONTROLLED
$3 3 WAY SWITCH
$4 4 WAY SWITCH
$ic SWITCH - KEY OPERATED
$P SWITCH - WITH PILOT LIGHT
DIMMER
DIMMER W /OCCUPANCY SENSOR
$I.v MOMENTARY CONTACT LOW VOLTAGE SWITCH
t'® RELAY - NEC CLASS II
LOW VOLTAGE TRANSFORMER
Q OCCUPANCY SENSOR
$oa SWITCH - OCCUPANCY SENSOR
Q SWITCH - PHOTO SENSOR
SWITCHBANK
0
■
CIRCUITS
14\\
E
RACEWAY CONCEALED IN CEILING OR WALL HASH MARKS INDICATE NUMBER
OF WIRES. #12 AWG WIRE UNLESS OTHERWISE NOTED. THREE WIRES IF NO
HASH MARK SHOWN. LONG HASH MARK DENOTES NEUTRAL —fir INDICATES
GROUND WIRE. EXPOSED RACEWAY IS ALLOWED ONLY WHERE NOTED.
EXISTING RACEWAY (IF HASH MARKS ARE SHOWN, PULL NEW CONDUCTORS)
RACEWAY BELOW SLAB OR UNDERGROUND
EXPOSED CONDUIT RUN ON SURFACE OF WALL OR CEIUNG
RACEWAY UP
RACEWAY DOWN
RACEWAY STUB -OUT WITH BUSHING
HOME RUN TO PANEL OR LOCATION NOTED
CIRCUIT CONTINUATION
D JUNCTION BOX
® PULL BOX
0 GROUNDING ROD
FILE COPY
Penult No. f-1-17-'-13t0K.
Plan raw approval is subject to effOr3 and Wei t ,
Approval of construction documents does not aooth, 0.73
the violation of any adopted code or ordinance. Ref• 'I
t1f ttDD1OV d �I0Id BODY ' 16 aG 'i0��6td 4
RECEPTACLES
SINGLE RECEPTACLE 120V
V1+ DUPLEX RECEPTACLE 120V
DUPLEX RECEPTACLE 120V, MOUNTED 3' ABOVE COUNTER BACKSPLASH
4
4
•
4
DOUBLE DUPLEX RECEPTACLE 120V
DOUBLE DUPLEX RECEPTACLE 120V, MOUNTED 3" ABOVE COUNTER BACKSPLASH
TWIST LOCK RECEPTACLE 120V
DUPLEX RECEPTACLE 120V, EMERGENCY CIRCUIT
DOUBLE DUPLEX RECEPTACLE 120V, EMERGENCY CIRCUIT
c• CLOCK RECEPTACLE 120V
�P SPOT. WIRED RECEPTACLE, 120V, TOP SWITCHED
COMBINATION RECEPTACLE 120/208V, 120/240V
RECEPTACLE 208V OR 240V, SINGLE PHASE
RECEPTACLE 208V, THREE PHASE (TWIST LOCK)
O RECEPTACLE 208V OR 240V, THREE PHASE
• RECEPTACLE 480V, SINGLE PHASE
® RECEPTACLE 480V, THREE PHASE
▪ COMBINATION RECEPTACLE 480V, SINGLE PHASE
RECEPTACLE 208V, SINGLE PHASE (TWIST LOCK)
I. RECEPTACLE 480V, SINGLE PHASE (TWIST LOCK)
ff RECEPTACLE 480V, THREE PHASE (TWIST LOCK)
O CEILING CORD DROP, 120V, SINGLE PHASE
CEIUNG CORD DROP, 120V, SINGLE PHASE, EMERGENCY CIRCUIT
FLUSH FLOOR OUTLET (DEVICES AS INDICATED)
FLOOR OUTLET - POKE THROUGH (DEVICES AS INDICATED)
0 TELEPHONE / POWER POLE
MULTI- OUTLET ASSEMBLY - LENGTH PER PLAN, DEVICE(S) AS INDICATED
COMBINATION OUTLET (DEVICES AS INDICATED)
DUPLEX RECEPTACLE - SURGE PROTECTOR TYPE
DUPLEX RECEPTACLE - ISOLATED GROUND TYPE
DUPLEX RECEPTACLE - SAFETY TYPE
DUPLEX RECEPTACLE - GROUND FAULT CIRCUIT INTERRUPTER TYPE
r!1
EQUIPMENT
0
Av
Tvss
BY
PANEL - 208 VOLT SYSTEM
PANEL - 480 VOLT SYSTEM
EQUIPMENT CONNECTION
MOTOR CONNECTION SINGLE PHASE
MOTOR CONNECTION 3 PHASE
TRANSFORMER
TRANSIENT VOLTAGE SURGE SUPPRESSOR
1/20/z ° /z-
City Of Tlukwila
BUILDING DIVISION
CONTROL
El FUSED DISCONNECT SWITCH (FUSE RATING INDICATED)
Di DISCONNECT SWITCH
® MOTOR STARTER - MAGNETIC
MANUAL STARTER
El COMBINATION MOTOR STARTER DISCONNECT SWITCH
$M MANUAL STARTER SWITCH WITH THERMAL OVERLOAD
® ENCLOSED CIRCUIT BREAKER
® THERMOSTAT
11ME CLOCK
▪ CONTACTOR
® RELAY - CONTROL TYPE
O PHOTOCELL CONTROL
PUSH BUTTON CONTROL STATION
H AUTO DOOR PUSHPLATE
H
SEPARATE PERMIT
REQUIRED FOR:
Mechanical
D Electrical
Plumbing
Gas Piping
City of Tukwila
BUILDING DIVISION
TELEPHONE &.COMPUTER SYSTEMS
■ TELEPHONE OUTLET
TELEPHONE OUTLET - WALL MOUNTED
t` 1111'` CABLE TRAM
ELECTRICAL RISER
0
FUSED SWITCH
CIRCUIT BREAKER
DRAWOUT CIRCUIT BREAKER
CIRCUIT BREAKER - GROUND FAULT PROTECTION
CABLE TO BUS CONNECTION
FUSE OR CURRENT UMITER
GROUND CONNECTION
IDENTIFICATION SYMBOL FOR FEEDER SIZES
TRANSFORMER
WATT -HOUR METER
AMMETER
VOLTMETER
t:;;1- TRANSFER SWITCH
O ENGINE- GENERATOR
1 xxx > AVAILABLE SHORT CIRCUIT CURRENT
GENERAL INFORMATION SYMBOLS
, ®
j
CONSTRUCTION NOTE.
REVISION SYMBOL
UGHT LINE INDICATES EXISTING DEVICES
REMOVE EXISTING ELECTRICAL EQUIPMENT
�/ / / / //
V �
♦ ♦ ♦ ♦ ♦♦
1
X
X
X
X
X
NEC CODE REQUIRED CLEAR WORKING SPACE
EQUIPMENT DESIGNATION
ELECTRICAL INFORMATION
EQUIPMENT DISCONNECT
AD -AMP DISCONNECT
AF -AMP FUSES
DETAIL OR DIAGRAM NUMBER
SHEET NUMBER
WHERE DETAIL/DIAGRAM SHOWN
SECTION LETTER
SHEET NUMBER WHERE SECTION SHOWN
PLAN NUMBER
SHEET NUMBER WHERE, PLAN SHOWN
REVISION NUMBER - DENOTES NUMBER
AND DATE WHEN REVISION OR ISSUE
OCCURED
REVISION CLOUD - DENOTES AREA OF
CHANGE
DETAIL REFERENCE OUTLINE
WITH NUMBER AND SHEET LOCATION
VICINITY MAP
PSE TRANSFORMER
PROJECT AREA
OUTLET MOUNTING HEIGHTS
SPECIAL OUTLET HEIGHTS ARE SHOWN ON THE ELECTRICAL DRAWINGS OR ON THE ARCHITECTURAL
DRAWINGS. IF SPECIAL OUTLET HEIGHTS ARE NOT SHOWN OR REQUIRED, THEN LOCATE OUTLETS AS
NOTED BELOW. OUTLET HEIGHTS ARE MEASURED FROM THE FINISHED FLOOR TO THE CENTERLINE OF
THE OUTLET UNLESS OTHERWISE NOTED.
RECEPTACLES
18 INCHES VERTICALLY MOUNTED
UGHT SWITCHES
48 INCHES VERTICALLY MOUNTED
PANELBOARDS
72 INCHES TO TOP OF PANELBOARD
TELEPHONE OUTLET - DESK
18 INCHES VERTICALLY MOUNTED
TELEPHONE OUTLET - WALL
54 INCHES VERTICALLY MOUNTED
COMPUTER OUTLET - DESK
18 INCHES VERTICALLY MOUNTED
ABBREVIATIONS
ACH ABOVE COUNTER HEIGHT
AFF ABOVE FINISHED FLOOR
AG ABOVE GRADE
AHJ AUTHORITY HAVING JURISDICTION
A, AMP AMPERE
ATR ALL THREAD ROD
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
CB CIRCUIT BREAKER
CKT CIRCUIT
CTB COMMUNICATIONS TERMINAL BOARD
DED DEDICATED
DTT DRY TYPE TRANSFORMER
DW DISHWASHER
E EXISTING, (E) EXISTING
EA EACH
EC ELECTRICAL CONTRACTOR
EWC ELECTRIC WATER COOLER
FA FIRE ALARM
FBOIC FURNISHED BY OTHERS,
INSTALLED BY CONTRACTOR
FT FILM ILLUMINATOR
G, GND GROUND
GD GARBAGE DISPOSAL
GFEP GROUND FAULT EQUIPMENT PROTECTION
GFI, GFCI GROUND FAULT CIRCUIT INTERRUPTER
GEN GENERATOR
HP HORSEPOWER
IG ISOLATED GROUND
IH INSTA -HOT WATER DISPENSER
J -BOX JUNCTION BOX
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MCB MAIN CIRCUIT BOARD
MEZZ MEZZANINE
MLO MAIN LUG OUT
MRS MOTOR RATED SWITCH
MW MICROWAVE
N NEUTRAL
NEC NATIONAL ELECTRICAL CODE
NIC NOT IN CONTRACT
PHASE
PNL PANEL
PSE PUGEI• SOUND ENERGY
R RACEWAY
RO RACEWAY ONLY
RECEPT RECEPTACLE
REF REFRIGERATOR
SCH SCHEDULE
SCL SEATTLE CITY LIGHT
SPECS SPECIFICATIONS
SW SWITCH
SWBD SWITCHBOARD
TELE ` TELEPHONE
TSP TWISTED SHIELDED PAIR
TYP TYPICAL
V VOLT
VFD VARIABLE FREQUENCY DRIVE
VP VANDALPROOF
W WATT
WC WARMING CABINET
WP WEATHERPROOF
XFMR TRANSFORMER
GENERAL NOTES
1. COMPLY WITH NATIONAL ELECTRICAL CODE LATEST ADOPTED EDITION AND APPLICABLE STATE
CODES.
2. SYMBOLS ARE BASED ON A STANDARD PACKAGE PER CATAGORY. NOT ALL SYMBOLS MAY
APPEAR ON DRAWINGS.
• THE LOCATIONS OF ELECTRICAL DEVICES OR UGHTING FIXTURES IN AREAS WITH OPEN CEIUNG
INDICATED ON MECHANICAL PLANS ELEVATIONS OR SECTIONS TAKE PRECEDENCE OVER
LOCATIONS INDICATED ON THE ELECTRICAL DRAWINGS.
COORDINATE WORK WITH THAT OF ALL CONTRACTORS AND /OR OTHER TRADES DOING WORK
ON THE PROJECT. EXAMINE ALL DRAWINGS AND SPECIFICATIONS OF OTHER TRADES FOR
CONSTRUCTION DETAILS AND COORDINATION.
5. OBTAIN AND REVIEW ALL SUBMITTALS AND SHOP DRAWINGS OF EQUIPMENT WITH ELECTRICAL
CONNECTIONS INCLUDING EQUIPMENT FURNISHED BY OTHER DIVISIONS OR BY THE OWNER.
PROVIDE ALL WIRING IN ACCORDANCE WITH SPECIFIC EQUIPMENT REQUIREMENTS. IMMEDIATELY
ADVISE THE ENGINEER OF ANY CHANGES WHICH MAY AFFECT THE CONTRACT.
FUSED DISCONNECT SWITCHES SHALL NOT BE REMOVED FROM THIS INSTALLATION WITHOUT
FIRST CONFIRMING THE AIC RATINGS AT THAT CONNECTION POINT IN THE SYSTEM AND
CONFIRMING THAT THE RATING OF ALL DEVICES IN THE SYSTEM MEET OR EXCEED THE
AVAILABLE AIC FAULT CURRENT. CALCULATIONS SHALL BE TAKEN DOWN TO 4,000 AIC.
7. THE DRAWINGS AND SPECIFICATIONS ARE COMPUMENTARY AND WHAT 1S CALLED FOR (OR
SHOWN) IN OTHER. IS REQUIRED TO BE PROVIDED AS IF CALLED FOR IN BOTH.
DRAWING INDEX
E0.0 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E1.0 ELECTRICAL ONE -LINE DIAGRAM
E1.1 LOAD CALC, SCHEDULES
E2.0 FIRST & MEZZANINE FLOOR PLANS - ELECTRICAL
REVISIONS —_
No changes shall�be mmada to the coops
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
REVIEWED iiOH
COMPLIANCE WITH
NFPA70 -NEC
JUL 1 1 2012
CityofT ila
BUILDING ' ISION
RECEIVED
JUL 022012
PERMIT CENTER
For Th
instry
ife Of Your Building
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1 -800- 669 -6223
PORTLAND:
16790 NE MASON ST
SUITE 100
PORTLAND, OR 97230
503- 331 -0234
www.mckinstry.com
PROJECT:
MACHINE
TOOLWORKS
14600 INTERURBAN AVENUE S
TUKWILA, WA 98168
REGISTRATION:
REVISIONS:
6/28/12 PERMIT SET
NO. DATE DESCRIPTION
McKINSTRY DIVISION:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
JOB NUMBER:
DATE:
SCALE:
SHEET TITLE:
ENGINEERING
60612
6/28/2012
AS SHOWN
ELECTRICAL SYMBOLS
AND ABBREVIATIONS
SHEET NUMBER:
E0.0
CT CABINET
EXISTING MAIN SERVICE PANEL
PANEL B
208V/30, 42 CKT 600A BUS
a¢
0
00
EZZANINE
PSE
TRANSFORMER
112.5 KVA
615AS
PANEL
C
208Y/120V
125A
1ST FLOOR
1 615AS 1
120A4
EXISTING ELECTRICAL ONE -LINE DIAGRAM
NOT TO SCALE
TXF A
480V: 208Y/120V
75 KVA
10' MAX.
CT CABINET
EXISTING MAIN SERVICE PANEL
PANEL B
208V/30, 42 CKT 600A BUS
0
CD
0
NEW MAIN SERVICE PANEL
PANEL A
480V/30, 4W, 600A BUS
MEZZANINE
PSE
TRANSFORMER
300 KVA
615AS
1 100C3 1
'cexl
200C4
XIX X15X - X X
2
PANEL
208Y/120V
125A
ST FLOOR
1 615AS 1
1 120A4 1
NEW ELECTRICAL ONE -LINE DIAGRAM
NOT TO SCALE
FLAG NOTES
01 REMOVE MAIN BONDING JUMPER IN PANEL. DISCONNECT GROUNDING ELECTRODE
CONDUCTORS FROM GROUNDED (NEUTRAL) BUS. (PANEL B IS NO LONGER THE
SERVICE EQUIPMENT.)
02 PROVIDE CONCRETE ENCASEMENT OF EXISTING SERVICE CONDUCTORS WHERE THEY
ARE ROUTED VERTICALLY BETWEEN THE 1ST FLOOR AND MEZZANINE.
(BASED ON EST. PSE TXF SIZE OF 300 KVA, AND EST. 3% Z.)
LV Momentary Report
Vpu = 1.00
FEEDER AND BRANCH CIRCUIT
75- DEGREE C ALUMINUM /COPPER THHN
SCHEDULE
/THWN CONDUCTORS
TAG
(NOTE 1)
OCPD
AMPS
(NOTE 2)
WIRE
AMPS
(NOTE 3)
RACEWAY
CONDUCTORS PER SET
NO.
SETS
SIZE (NOTE 4)
PHASE
NEUTRAL
CONDUCTOR
CU GROUND
(NOTE 5)
EMT
PVC SCH. 40
CONDUCTORS
615AS
600
615
3
2 -1/2"
2 -1/2"
(3)- 250kcmil
(1)- 250kcmil
OTS -250
200C4
200
200
1
2"
2 -1/2"
(3)43/0
(1) -310
(1)-#4
120A4
100
120
1
2"
2"
(3)41/0
(1)41/0
(1)-#6
100C3
100
100
1
1"
1"
(3)-#3
--
(1)48
GENERAL NOTES
OF FEEDER TAG: 1240A4
= FEEDER WIRE AMPACITY
= ALUMINUM CONDUCTORS (C = COPPER)
= 4 -WIRE (3 = 3 -WIRE)
FEEDERS:
SERVICE CONDUCTORS
FEEDER TO TRANSFORMER
FEEDER FROM TRANSFORMER
FEEDER TO PNL C
OVERCURRENT PROTECTIVE DEVICE RATING (BASED
IN NEC 240 -6).
AMPACITY IS BASED ON NEC TABLE 310 -16
OR ADJUSTMENT REQUIRED FOR VOLTAGE
IS SIZED TO INCLUDE AN EQUIPMENT GROUNDING
RACEWAY TO BE USED AS 'EQUIPMENT GROUNDING
CIRCUITS WHERE PERMITTED BY CODE. COPPER
TO BE RUN IN ALL OTHER BRANCH CIRCUITS
ELECTRODE CONDUCTOR.
\Projects \605 - SPG Electrical - Series 60)00X160612
ON STANDARD
WITH NO CORRECTION FACTORS
DROP.
CONDUCTOR.
CONDUCTOR' IN ALL
WIRE 'EQUIPMENT GROUNDING
AND ALL FEEDERS.
Machine Toolworks \060 Engineering
1A'C
REVISO R
COMPLIAN
NFPA70
JUL 1
11, 1. EXAMPLE
1240
A
4
SPECIAL
615AS
200C4
120A4
100C3
r 2. MAXIMUM
RATINGS
' 3. CONDUCTOR
FOR TEMPERATURE
r 4. RACEWAY
r 5. METALLIC
BRANCH
CONDUCTOR'
r 6. GROUNDING
\mckinstry\seattle■Electrical
—City of
'"`77
BUILDING
\[Mach
(BASED ON EST. PSE TXF SIZE OF 300 KVA, AND EST. 3% Z.)
LV Momentary Report
Vpu = 1.00
3 PHASE Fault
Available Fault Current
Bus Name
Bus kV
Duty Amps
AIR COMP.
0.208
1865.7
CT- CABINET
0.48
12000
EXIST. PNL B
0.208
2521.6
EXIST. PNL C
0.208
2450.5
HCN -6000
0.48
9077.7
I NTEREX
0.48
9077.7
OTS -250
0.48
10568
PANELA
0.48
11577.8
STUDER
0.48
9055.8
TXF -A (PRI.)
0.48
9333.2
TXF -A (SEC.)
0.208
2558.6
VAR. 1 -600
0.48
8830.3
VCS -530C
0.48
8830.3
D FOR
CE WITH
NEC
2012
ukwila
DIVISION,
t O(o15
RECEIVED
JUL 02 2012
PERMIT CENTER
For Th
instry
ife Of Your Bu1lgling
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1 -800- 669 -6223
PORTLAND:
16790 NE MASON ST
SUITE 100
PORTLAND, OR 97230
503- 331 -0234
www.mckinstry.com
PROJECT:
MACHINE
TOOLWORKS
14600 INTERURBAN AVENUE S
TUKWILA, WA 98168
REGISTRATION:
REVISIONS:
6/28/12 PERMIT SET
NO. DATE DESCRIPTION
McKINSTRY DIVISION:
ENGINEERING
DESIGNED BY:
DRAWN BY:
CHECKED BY:
JOB NUMBER: 60612
DATE: 6/28/2012
SCALE: AS SHOWN
SHEET TITLE:
EXISTING & NEW
ELECTRICAL ONE -LINE
DIAGRAM & SCHEDULES
SHEET NUMBER:
E1.0
11mckinstrylseattlelEIectrical \Projec1s1605 - SPG Elec cal Series 60XXX160612 Machine Toolworks1060 Engineering \Equipment [Machine Works 3.xlslEauip. Schedule
EQUIPMENT SCHEDULE
CATEGORY
ITEM
NUMBER -
QTY.
NEW (N),
EXIST.
(X), OR
FUTURE
(F)?
LVL.
DEMAND
FACTOR
LOAD
(SIZE)
LOAD
(UNITS)
VOLTS/
PHASE
TYPE OF
POWER
(NORMAL,
EMERGENCY,
OR OPTIONAL SBY
EQUIP.
FURN.
BY
EQUIP.
INSTALL
BY
DISCONN.
F & I
BY
COMMENTS
AIR COMP.
1
(N)
1.
SURFACE
15.00
HP
208/3
N
O.F.
0.1.
E.C.
25 KVA
VARIAXIS 1 -600
1
(N)
1
31 KVA
57.34
KVA
480/3
N
O.F.
0.1.
E.C.
0 KVA
INTEGREX-I 200S
1
(N)
1
25% FOR LARGEST MOTOR: CMF PUMP -100HP
78.74
KVA
480/3
N
O.F.
0.1.
E.C.
3
VCS -530C
1
(N)
1
1.00
53.96
KVA
480/3
N
O.F.
0.1.
E.C.
16
STUDER
1
(N)
1
28.00
KVA
480/3
N
O.F.
0.1.
E.C.
345 KVA
OTS -250
1
(N)
1
57 KVA
33.80
KVA
480/3
N
O.F.
0.1.
E.C.
83 KVA
HCN -6000
1
(N)
1
76.68
KVA
480/3
N
O.F.
0.1.
E.C.
B
70 KVA
17
C
497 KVA
20
PSESERVICEAMPS @ 480V, 3 -PH.:
415 AMPS
552 AMPS
30 AMPS
3
84 AMPS
445 AMPS
3
598 AMPS
SPACE
20
21
B
22
23
C
24
25
E
E
E
OTS -250
11.3
11.3
11.3
60
3
A
60
3
9.3
9.3
9.3
STUDER
E
E
E
26
27
B
28
29
C
30
31
A
32
33
B
34
35
EQUIPMENT SCHEDULE
NOT TO SCALE
MACHINE WORKS
SERVICE DEMAND CALCULATION
11mckinstrylseattle \Electrical\Projects1605 - SPG Elec
6/29/12 4:43 PM
rical - Series 60XXX160612 Machine Toolworks1060 Engineering\Equipmentl[Machine Works 3.xslLoad Calc. Two Svcs.
PANEL A
EXISTING PANEL B
TOTAL BUILDING LOAD
#
CATEGORY
CONNECTED
DEMAND
FACTOR
NEC DEMAND
CONNECTED
DEMAND
FACTOR
NEC DEMAND
CONNECTED
DEMAND
FACTOR
NEC DEMAND
BUS AMPERES: 600A
VOLTAGE:
480Y/277V
PHASE: 3
WIRE:
4
MLO / MC$: MLO
MOUNT:
SURFACE
NEMA: 1
A.I.0
7
EXISTING LOAD (PANEL B)
0 KVA
1.00
0 KVA
25 KVA
125
31 KVA
25.0 KVA
1.25
31 KVA
13
FURNISHED-BY-OTHERS EQUIPMENT
345 KVA
1.00
345 INA
0 KVA
1.00
0 KVA
345.2 KVA
1.00
345 KVA
14
25% FOR LARGEST MOTOR: CMF PUMP -100HP
CKT.
NO.
1
26 KVA
HCN -6000
26 KVA
100
3
26 KVA
15
3
KVA
1.00
0 KVA
0 KVA
1.00
0 KVA
0.0 KVA
1.00
0 KVA
16
6
7
E
E
E
VARIAXIS 1 -600
19.1
19.1
19.1
100
3
A
100
17
KVA- NO CONTINGENCY
345 KVA
376 KVA
25 KVA
9
57 KVA
370.2 KVA
11
407 KVA
18
CONTINGENCY: 18%
S
S
S
PANEL B (VIA T)<F -A)
83 KVA
5.8
5.8
5.8
100
13 KVA
A
89 KVA
19
KVA-WITH CONTINGENCY
458 KVA
15
B
70 KVA
17
C
497 KVA
20
PSESERVICEAMPS @ 480V, 3 -PH.:
415 AMPS
552 AMPS
30 AMPS
3
84 AMPS
445 AMPS
3
598 AMPS
SPACE
20
21
B
22
23
C
24
25
LOAD CALCULATION
NOT TO SCALE
345.2 KVA
415.3 AMPS
PROJECT: MACHINE TOOLWORKS
I McKINSTRY
/PANEL NAME: PANEL A
LOCATION: MEZZANINE
PANEL
FED FROM: C.T.
FEED -THRU TO: N/A '
PAGE:
BUS AMPERES: 600A
VOLTAGE:
480Y/277V
PHASE: 3
WIRE:
4
MLO / MC$: MLO
MOUNT:
SURFACE
NEMA: 1
A.I.0
(1): 25K
BUS MATL: AL
FEED
-THRU LUGS: N/A
T/B FED: TBD
CKT.
NO.
LOAD
TYPE
DESCRIPTION /
LOCATION
LOAD
(kVA)
OCPD
AMP
OCPD
POLE
PHASE
OCPD
AMP
OCPD
POLE
LOAD
(kVA)
DESCRIPTION I
LOCATION
LOAD
TYPE
CKT.
NO.
1
E
E
E
HCN -6000
25.6
25.6
25.6
100
3
A
100
3
26.2
26.2
26.2
INTEGREX-I 200S
E
E
E
2
3
B
4
5
C
6
7
E
E
E
VARIAXIS 1 -600
19.1
19.1
19.1
100
3
A
100
3
18.0
18.0
18.0
VCS -530C
E
E
E
8
9
B
10
11
C
12
13
S
S
S
PANEL B (VIA T)<F -A)
5.8
5.8
5.8
100
3
A
3
SPACE
14
15
B
16
17
C
18
19
SPACE
3
A
3
SPACE
20
21
B
22
23
C
24
25
E
E
E
OTS -250
11.3
11.3
11.3
60
3
A
60
3
9.3
9.3
9.3
STUDER
E
E
E
26
27
B
28
29
C
30
31
A
32
33
B
34
35
C
36
37
A
38
39
B
40
41
C
42
LOAD
TYPE
LOAD
DESCRIPTION
CONN. LOAD - THIS
SECTION 1 PAGE
CONN. LOAD -
DOWNSTREAM
CONN. LOAD -
TOTAL
DEMAND
FACTOR
DEM. LOAD -
TOTAL
PHASE BALANCE
(CONN. LOAD)
R
RECEPTACLES
0.0 KVA
0.0 KVA
0.0 KVA
[2]
0.0 KVA
PHASE
115.3
A:
KVA 416.3 AMPS
L
LIGHTING
0.0 KVA
0.0 KVA
0.0 KVA
125%
0.0 KVA
E
EQUIPMENT
328.5 KVA
17.4 KVA
345.9 KVA
100%
345.9 KVA
H
HEATING ONLY
0.0 KVA
0.0 KVA
0.0 KVA
125%
0.0 KVA
PHASE
115.3
B:
KVA 416.3 AMPS
C
COOLING ONLY
0.0 KVA
0.0 KVA
0.0 KVA
100%
0.0 KVA
K
KITCHEN
0.0 KVA
0.0 KVA
0.0 KVA
100%
0.0 KVA
PHASE
115.3
C:
KVA 416.3 AMPS
LARGEST MOTOR KVA
125%
0.0 KVA
TOTAL KVA
328.5 KVA
17.4 KVA
345.9 KVA
345.9 KVA
A
REVIEWED
COMPLIANCE
NFPA70
JUL
C o
BUILDING
FOR
WITH
- NEC
1 1 2012
TOTAL AMPS
395.3 AMPS
20.9 AMPS
416.3 AMPS
416.3 AMPS
SPARE ( %) 20%
TOTAL KVA WITH SPARE
432.4 KVA
TOTAL AMPS WITH SPARE
520.3 AMPS
REFERENCE NOTES:
(1)' MANUFACTURER TO PROVIDE EQUIPMENT
(2) RECEPTACLE DEMAND = LOAD < = 10KVA +
llmckinstrylseattle \Electrical \Projects1605 - SPG Electrical - Series
WITH THE LOWEST AIC RATING THAT EXCEEDS THE AVAILABLE FAULT CURRENT.
50% LOAD >10
60XXX160612 Machine Toolworks1060 Engineering\Panel Schedulesl[Machine Toolworks Panel Schedules.xlsx]PANEL
.Tukw11a
DIVISION ...
6/29/12 4:44 PM
E1.1
PANEL SCHEDULE
NOT TO SCALE
PowerS1
26000
22500
20000
17500
15000
12500
10000
7500
5000
2500
O Tobd Ave - 1433.0
Mc Machine Tooiwcrts - Peet Demanding
CI Wed YD: - 24972.0
D Yin • 4.4
Pose 2
Er,
I
0
10:244
1127112
11 :1223 11:34:01 11:54 :41 1216e20 123203
11:03:00 11:2237 11:44.17 1204:50 12:237
6127 6127 6127 0127 6127 0127 6127 611E 0127 6/27
auoti
EXISTING LOAD ON PANEL B
NOT TO SCALE
5
RECEIVED
JUL 022012
PERMIT CENTER
For Th
instry
ife Of Your Building
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1 -800- 669 -6223
PORTLAND:
16790 NE MASON ST
SUITE 100
PORTLAND, OR 97230
503- 331 -0234
www.mckinstry.com
PROJECT:
MACHINE
TOOLWORKS
14600 INTERURBAN AVENUE S
TUKWILA, WA 98168
REGISTRATION:
REVISIONS:
6/28/12 PERMIT SET
NO. DATE DESCRIPTION
McKINSTRY DIVISION:
ENGINEERING
DESIGNED BY:
DRAWN BY:
CHECKED BY:
JOB NUMBER: 60612
DATE: 6/28/2012
SCALE: AS SHOWN
SHEET TITLE:
LOAD CALC, SCHEDULES
SHEET NUMBER:
E1.1
PANEL A
(E) PANEL B
(E) CT
TXF A
MEZZANINE FLOOR PLAN - ELECTRICAL
SCALE: 1/8° = 1' -0" 0 4' 8'
•
,1#10G
"C -3 31 1#BG
INIEGREX—I 200S
480V 30, 78.74KVA
100AD
16'
SHEET NOTES
1. NOTE.
FLAG NOTES
01 NOTE.
MEZZANINE ABOVE
SEE DETAIL 1/E2.0
PSE TRANSFORMER
1...0__.
TRANSFORMER PAD
EXISTING SERVICE CONDUCTORS
4
J
FIRST FLOOR PLAN - ELECTRICAL
SCALE: 1/811 = 1' -0"
0
4'
8'
16'
W
- REVIEWED FpR H
COMPLIANCE
-NEC NFPA70
JUL 11 2012
City of TukvlSl0�1
BUILDING DI
leis
RECEIVED
JUL 02 2012
PERMIT CENTER
For Th
instry
ife Of Your Building
SEATTLE:
5005 3RD AVENUE S
PO BOX 24567
SEATTLE, WA 98124
1 -800- 669 -6223
PORTLAND:
16790 NE MASON ST
SUITE 100
PORTLAND, OR 97230
503 - 331 -0234
www.mckinstry.com
PROJECT:
MACHINE
TOOLWORKS
14600 INTERURBAN AVENUE S
TUKWILA, WA 98168
REGISTRATION:
REVISIONS:
6/28/12 PERMIT SET
NO. DATE DESCRIPTION
McKINSTRY DIVISION:
ENGINEERING
DESIGNED BY:
DRAWN BY:
CHECKED BY:
JOB NUMBER: 60612
DATE: 6/28/2012
SCALE: AS SHOWN
SHEET TITLE:
FIRST & MEZZANINE FLOOR
PLANS ELECTRICAL
SHEET NUMBER:
E2.0