HomeMy WebLinkAboutPermit EL12-0957 - WESTFIELD SOUTHCENTER MALL - EXPRESS SHOPEXPRESS SHOP
458 SOUTHCENTER MALL
EL1 2-0957
City okukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.TukwilaWA.gov
Parcel No.: 9202470010
Address: 458 SOUTHCENTER MALL TIIKW
Project Name: EXPRESS SHOP
ELECTRICAL PERMIT
Permit Number:
Issue Date:
Permit Expires On:
EL12 -0957
10/15/2012
04/13/2013
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
Contractor
WESTFIELD PROPERTY TAX DEPT
PO BOX 130940 , CARLSBAD CA 92013
JT BATTERSON Phone: 206 - 419 -4568
16825 230 AV SE , MAPLE VALLEY WA, 98038
CEDAR GROVE ELECTRIC INC
16825 230 AV SE , MAPLE VALLEY WA 98038
License No: CEDARGE955BC
Phone: 425 427 -9218
Expiration Date: 01/21/2013
DESCRIPTION OF WORK:
POWER FOR NEW CONVENIENCE STORE WITHIN MALL. USE EXISTING FIXTURES FOR
LIGHTING. MAINTAIN/EXTEND EXISTING CIRCUITRY AS NEEDED. REVISE LAYOUT. INSTALL
(1) 75KVA TRANSFORMER. INSTALL (1) 200 AMP PANEL. INCLUDE THE RELOCATION,
REMOVAL, AND INSTALLATION OF MISCELLANEOUS ELECTRICAL SYSTEMS PERTAINING TO THE
AFOREMENTIONED SCOPE OF WORK.
Value of Electrical: NRES: $19,000.00 Fees Collected:
RES: $0.00
Type of Fire Protection: SPRINKLERS /AFA National Electrical Code Edition:
Electrical service provided by: PUGET SOUND ENERGY
Permit Center Authorized Signature:
$524.13
2008
VpA(' Date: 12I IOII2
I hereby certify that I have read and amii ed this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not pres 1It a to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or performance of work. I am authorized to sign and obtain this electrical permit.
Signature:
Date:l 2 -70-7Z.
r
Print Name:
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: EL -4/10
EL12 -0957 Printed: 12 -10 -2012
• PERMIT CONDITIONS •
Permit No. EL 12 -0957
* *ELECTRICAL **
1: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical Inspector
at each work site.
2: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical Inspector.
3: All electrical work shall be in accordance with NFPA TO - NEC, and requirements for electrical installations, Chapter
296 -46B WAC.
4: When any portion of the electrical installation is to be hidden from view by permanent placement of parts of the
building, such equipment shall not be concealed until it has been inspected and approved by the Electrical Inspector.
5: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any violation
of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related documentation that
presumes to grant this authority are therefore not valid.
6: Any change in the scope of work described by the electrical work permit shall require additional work permits. Where
approved plans have been issued, revisions to the plans and additional review may be required.
doc: EL -4/10
EL12 -0957 Printed: 12 -10 -2012
City #fukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.TukwilaWA.gov
Parcel No.: 9202470010
Address: 458 SOUTHCENTER MALL TUKW
Project Name: EXPRESS SHOP
ELECTRICAL PERMIT
Permit Number: EL12 -0957
Issue Date: 10/15/2012
Permit Expires On: 04/13/2013
Owner:
Name: WESTFIELD PROPERTY TAX DEPT
Address: PO BOX 130940 , CARLSBAD CA 92013
Contact Person:
Name: COREY MCKINNON Phone: 253 867 -2354
Address: 7056 5 220 ST , KENT WA, 98032
Contractor:
Name: SEA TAC ELECTRIC INC
Address: 7056 S 220TH ST , KENT WA 98032
Contractor License No: SEATAEI077RW
Phone:
Expiration Date: 12/17/2013
DESCRIPTION OF WORK:
POWER FOR NEW CONVENIENCE STORE WITHIN MALL. USE EXISTING FIXTURES FOR
LIGHTING. MAINTAIN/EXTEND EXISTING CIRCUITRY AS NEEDED. REVISE LAYOUT. INSTALL
(1) 75KVA TRANSFORMER. INSTALL (1) 200 AMP PANEL. INCLUDE THE RELOCATION,
REMOVAL, AND INSTALLATION OF MISCELLANEOUS ELECTRICAL SYSTEMS PERTAINING TO THE
AFOREMENTIONED SCOPE OF WORK.
Value of Electrical: NRES: $19,000.00 Fees Collected: $524.13
RES: $0.00
Type of Fire Protection: SPRINKLERS /AFA
Electrical service provided by: PUGET SOUND ENERGY
Permit Center Authorized Signature:
I hereby certify that I have read and a ;• ed this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied 'th, hether specified herein or not.
A
National Electrical Code Edition: 2008
Date: P (N (I C—
The granting of this permit does not pres e to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign and obtain this electrical permit.
Signature:
Date: / o /i.5 /� / 2
Print Name: -4' Amt ti 0 5
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: EL -4/10
EL12 -0957
Printed: 10 -15 -2012
11.
PERMIT CONDITIONS
Permit No. EL12 -0957
* *ELECTRICAL **
1: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical Inspector
at each work site.
2: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical Inspector.
3: All electrical work shall be in accordance with NFPA 70 - NEC, and requirements for electrical installations, Chapter
296 -46B WAC.
4: When any portion of the electrical installation is to be hidden from view by permanent placement of parts of the
building, such equipment shall not be concealed until it has been inspected and approved by the Electrical Inspector.
5: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any violation
of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related documentation that
presumes to grant this authority are therefore not valid.
6: Any change in the scope of work described by the electrical work permit shall require additional work permits. Where
approved plans have been issued, revisions to the plans and additional review may be required.
doc: EL -4/10
EL12 -0957 Printed: 10 -15 -2012
r
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http: / /www.TukwilaWA.gov
•
Electrical Permit No. L�2" o11
Project No.
Date Application Accepted: 10 lo l ti
Date Application Expires: IO
(For office use only)
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *Please Print **
SITE LOCATION
Site Address:
Tenant Name:
X33' SOUTHCENTER P'K-WY
EXPRESS SHOP
PROPERTY OWNER
Name: COREY MCKINNON
Name: EXPRESS SHOP
City: KENT State: WA Zip: 98032
Address: 633 SOUTHCENTER PKWY
Email: corey.m @seatacelectric.com
City: TUKWILA State: WA
Zip: 98188
CONTACT PERSON — person receiving all project
communication
Name: COREY MCKINNON
Address: 7056 S. 220TH STREET
City: KENT State: WA Zip: 98032
a67-
Phone: (253) . -2354 Fax: (253) 872 -4112
Email: corey.m @seatacelectric.com
King Co Assessor's Tax No.: °1`)/v2-4 1- 7 \O
Suite Number: Floor:
New Tenant: ❑ Yes m..No
ELECTRICAL CONTRACTOR INFORMATION
Company Name: SEA -TAC ELECTRIC, INC.
Address: 7056 S. 220TH STREET
City: KENT State: WA Zip: 98032
Phone: (253) 867 -2354 Fax: (253) 872 -4112
Contr Reg No.: SEATAEI077RW Exp Date: 12/01/2013
Tukwila Business License No.: orZT2 bikt, 0 X 001 1)
Valuation of Project (contractor's bid price): $ 19,000
Scope of Work (please provide detailed information):
POWER FOR NEW CONVENIENCE STORE. USE EXISTING FIXTURES FOR LIGHTING. MAINTAIN /EXTEND
EXISTING CIRCUITRY AS NEEDED. REVISED SERVICE LAYOUT. INSTALL (1) 75Kva TRANSFORMER. INSTALL
(1) 200 AMP PANEL. INCLUDE THE RELOCATION, REMOVAL AND INSTALLATION OF MISC ELECTRICAL
SYSTEMS PFD,TAINING TO THE AFOREMENTIONED SCOPE OF WORK.
Jr Use: LUME
Type of work:
❑ New ❑ Addition ❑ Service Change ❑ Remodel ® Tenant Improvement
❑ Low Voltage ❑ Generator ❑ Fire Alarm ❑ Telecommunication ❑ Temporary Service
Property Served by:
• Puget Sound Energy ❑ Seattle City Light
H:Wpplications\Forms- Applications On Line VA! I Applications\Electrical Permit Application Revised 8- 9- 1I.docx
Revised: August 2011
bh
Page 1 of 2
RESIDENTIAL
NEW RESIDENTIAL SERVICE
❑ New single family dwellings $152.85
(including an attached garage)
❑ Garages, pools, spas and outbuildings $81.90 ea
❑ Low voltage systems
(alarm, furnace thermostat) $59.85 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
❑ Service change or alteration $81.90
(no added /altered circuits)
❑ Service change with added /altered circuits $81.90
number of added circuits $11.55 ea
❑ Circuits added /altered without service change $54.60
(up to 5 circuits)
❑ Circuits added /altered without service change $54.60
(6 or more circuits) $7.65 ea
❑ Meter /mast repair $68.25
❑ Low voltage systems $59.85
(alarm, furnace thermostat)
MULTI - FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
❑ Temporary service (residential) $63.00
❑ Temporary service (generator) $78.75
❑ Manufactured /mobile home service $84.00
(excluding garage or outbuilding)
❑ Carnivals $78.75
Number of concessions $10.50 ea
PERMIT;: APPLICATION NOTES -
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
1 HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR ELECTRICAL CONTRACTOR:
Signature:
Date: 10/10/2012
Print Name: IAN EDMUNDS Day Telephone: (253) 867 -2354
Mailing Address: 7056 S. 220TH STREET KENT WA 98032
City
H: \Applications\Forms- Applications On Line\2011 Applications\Eleetrical Permit Application Revised 8 -9 -I I.docx
Revised: August 2011
bh
State Zip
Page 2 of 2
• •
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.TukwilaWA.gov
RECEIPT
Parcel No.: 9202470010 Permit Number: EL12 -0957
Address: 458 SOUTHCENTER MALL TUKW Status: PENDING
Suite No: Applied Date: 10/10/2012
Applicant: EXPRESS SHOP Issue Date:
Receipt No.: R12 -02823
Payment Amount: $524.13
Initials: JEM Payment Date: 10/10/2012 12:36 PM
User ID: 1165 Balance: $0.00
Payee: COREY MCKINNON, SEATAC ELECTRIC
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 010830
ACCOUNT ITEM LIST:
Description
524.13
Account Code Current Pmts
ELECTRICAL PERMIT - NONR
ELECTRICAL PLAN - NONRES
000.322.101.00.00 419.30
000.345.832.00.00 104.83
Total: $524.13
doc: Receipt-06 Printed: 10 -10 -2012
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
PERMIT NO.'
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
Project: / 5 640P
Type of Inspection:
Address. ii .17 ��,
Date Called:
Special Instructions: .-
i7
Date Wanted:.
a.m.
.m.
Requester:
f
Phone No:
Approved per applicable codes.
COMMENTS:
ElCorrections required prior to approval. -
tw&-
Inspector:
4 6c Date:
14 3
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must :be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection. :
s
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 t , (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
Project: Opaerps joor
Type of Inspection:
-- 6 4'P&De53 £-+: 'J1 bG,c 4 eu s ok
Address: f�
5Y titivi
Date Called:
if• j1fir.. c.444/(r Mark &a
Special Instructions:
2537
:::::: ed: .
1 �
:
P hone No:
1
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
-- 6 4'P&De53 £-+: 'J1 bG,c 4 eu s ok
Wc-v.; avi (A-A ,j4 Ar.46 L GZ,
if• j1fir.. c.444/(r Mark &a
-C&
2 €c rr L 1I n/oT t'/04.t .W
- 4
Inspector:
Date: 01 101
3
n REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD (u2157
Retain a copy with permit INSPECTION NO. PEO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 yrz.. (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
Project: ` n5 C p
J( ,� j
Type of Inspection:
7o5
Address: { c--)
Date Called:
//
Special Instructions:
(/
25 37
Date Wanted:.
oy
a6
Requester:
Phone No:
f 1�
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
/2
yAtextotNis
rcelt,tici
cot,-6.
//
.. v\c.).4,04. t corif)rkTE
Inspector:
t'
Date:
oti 13
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
IN ECTION NO. PERMIT NO. '
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206)'431 -3670
Permit Inspection Request Line (206) 431 -2451
6L-0151
Project: qq 5 514.0 p
`h,
Type of Inspection:
7063
Address:
// cV ��
Date Called:
Special Instructions:
lJ7
Date Wanted:.
.m
Requester:
Phone No:
0 Approved per applicable codes. Corrections required prior to approval •
COMMENTS:
ray �
- ADDrrw' A� c fNtT sL /AvZ,
3 F or f9<
A6 s ofro Roi- 607
iitrkl t1 G 0,1 trv-tisi iZ " of
SC c d iw X 0. S- AFi ,{fit', l y -
t'ssoftl :7-6,c Polec
Inspector:
n REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection..:
INSPECTION RECORD
Retain a copf with permit
INSPECTION NO. PERMIT NO.,
CITY OF TUKWILA BUILDING DIVISION: .
6300 Southcenter Blvd., 100, Tukwila. WA 98188 le_ (206).431 -3670
Permit Inspection Request Line (206) 431 -2451 -
Project: fs� �� �}
Type of Inspection:
,-0
Address: � * tf
Date Called:
=
�
Special Instru bons:
Date Wanted:.
21C?
(a`.m
Requester:
Phone No:
Approved per applicable codes. Ei Corrections required prior to approval. ..
COMMENTS:
- - Psesm,(1—.1
Y ?�'F`� Cad eal ohis ,
A-0,4 ninl t o c,P
Inspector:
rr
ZlirtheAftskit
n REINSPECTION FEE REQUIRED. Prior to next inspection; fee: mustbe;
paid at 6300 Southcenter Blvd., Suite 100. Call' to: schedule, reinspection:.'.
-
INSPECTION. RECORD
Retain a copy with permit,
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION :
6300 Southcenter Blvd., #100, Tukwila: WA 98188 _ (206).431 -3670`
Permit Inspection Request Line (206) 431 -2451
Project: Pkt55,c1-1.0P
Type of Inspection:..
I
Address: , �t ,�
Date Called: .
Special Instructions:
Date Wanted:. ``
a.
Requester:
Phone No:
IApproved per applicable codes.
COMMENTS:
/)
OCorrections required prior to approval:
dd9t(\s-L.Ab 'ccabl f r5
Inspector:
n REINSPECTION FEE REQUIRED. Prior to next inspection" fee must be-
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule: reinspection..:
•
• •
Jennifer Marshall
From: Jt Batterson <jtb319 @msn.com>
Sent: Monday, December 10, 2012 11:18 AM
To: Jennifer Marshall
Subject: Fwd: Permit number eI- 120957
Sent from my iPhone
Begin forwarded message:
From: hsingh86 <hsingh86 @Hotmail.com>
Date: December 10, 2012 11:13:39 AM PST
To: Jennifer.marshal @tukwilawa.gov, jtb319 @msn.com
Subject: Permit number el- 120957
Reply -To: hsingh86 <hsingh86 @Hotmail.com>
Hey Jennifer
This is Hardeep Singh and I m the owner of the Express shop going in the Southcenter Mall. I
authorized JT from Cedar Grove Electric to take over the electric work and he has full
authorization to make changes to the existing permit and had his name on it. If you have any
question please call me at 4252682088.
Thank you
Hardeep Singh
From my Galaxy Note 2 Phone!!
1
`*ERMIT COORD COfO
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: EL12 -0957 DATE: 10/10/12
PROJECT NAME: EXPRESS SHOP
SITE ADDRESS: 458 SOUTHCENTER MALL
X Original Plan Submittal Response to Incomplete Letter #
_ Response to Correction Letter
Revision #
after Permit Issued
DEPARTMENTS: �1
D' sb
B Ing Ivislon
19.6
Public Works
Fire Prevention
Structural
Planning Division
Permit Coordinator
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete Ni Incomplete ❑
DUE DATE: 10/11/12
Not Applicable ❑
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED:
LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROUTING:
Please Route k Structural Review Required ❑ No further Review Required ❑
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
DUE DATE: 11/08/12
Approved ❑ Approved with Conditions 2- Not Approved (attach comments) ❑
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Contractors or Tradespeople Pry-lter Friendly Page
Electrical Contractor
A business licensed by L &I to contract electrical work within the scope of its specialty. Electrical
Contractors must maintain a surety bond or assignment of savings account. They also must have a
designated Electrical Administrator or Master Electrician who is a member of the firm or a full -time
supervisory employee.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent Company
CEDAR GROVE ELECTRIC INC
4254279218
16825 230Th Ave Se
Maple Valley
WA
98038
King
Corporation
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Specialty 1
Specialty 2
602254353
Active
CEDARGE955BC
Electrical Contractor
1/21/2005
1/21/2013
General
Unused
Associated Licenses
License
Name
Type
Specialty
1
Specialty
2
Effective
Date
Expiration
Date
Status
CEDARGE995DW
CEDAR GROVE
ELECTRIC
Electrical
Contractor
General
Unused
3/16/2001
3/16/2005
Archived
Master Electrician INFORMATION
License BATTEJT967C5
Name BATTERSON, J T
Status Active
Business Owner Information
Name
Role
Effective Date
Expiration Date
BATTERSON,J T
Agent
01/03/2005
Bond Amount
BATTERSON, J T
President
01/03/2005
9805393
Bond Information
Page 1 of 1
IN4c
cg 9A
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
3
Lexon Ins Co
9805393
04/29/2011
Until Cancelled
19.28.101 RCW
ELECTRICAL CITATION
$4,000.00
04/20/2011
2
COLONIAL AM CAS &
SURETY OF
MARYLAND
LPM4068727
04/29/2005
Until Cancelled
06/03/2011
$4,000.00
05/09/2005
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information No records found for the previous 6 year period
. Summons /Complaint Information Summons and Complaints are not filed with the department for this contractor type
Warrant Information Warrants are not filed with the department for this contractor type
Infractions /Citations Information
Infraction / Citation
Date
RCW Code
Type
Status
Violation Amount
EHOUD00355
3/22/2008
19.28.271 RCW
ELECTRICAL CITATION
Satisfied
$250.00
EMABQ03686
10/22/2011
19.28.101 RCW
ELECTRICAL CITATION
Satisfied
$250.00
https: // fortress .wa.gov /lni/bbip/Print.aspx 12/10/2012
Contractors or TradespeopleJ',ter Friendly Page
Page 1 of 2
Electrical Contractor
A business licensed by L I to contract electrical work within the scope of its specialty. Electrical
Contractors must maintain a surety bond or assignment of savings account. They also must have a
designated Electrical Administrator or Master Electrician who is a member of the firm or a full -time
supervisory employee.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent Company
SEA TAC ELECTRIC INC
2538725553
7056 S 220Th St
Kent
WA
98032
King
Corporation
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Specialty 1
Specialty 2
601510212
Active
SEATAEI077RW
Electrical Contractor
12/16/1993
12/17/2013
General
Unused
Other Associated Licenses
License
Name
Type
Specialty
1
Specialty
2
Effective
Date
Expiration
Date
Status
LIGHTSJ897QN
LIGHTHORSE SEATAC
JV
Construction
Contractor
General
Unused
11/9/2011
11/9/2013
Active
SEATAEC131QC
SEA TAC ELECTRICAL
CONTRACTORS
Electrical
Contractor
General
Unused
11/3/1987
11/3/1995
Archived
Master Electrician INFORMATION
License HARGRT *974CD
Name HARGREAVES, TOM
Status Active
Business Owner Information
Name
Role
Effective Date
Expiration Date
HARGREAVES, TOM
Agent
12/17/1993
HARGREAVES, TOM
President
12/17/1993
BEAN, ERIC
Secretary
12/10/2008
BEAN, ERIC
Treasurer
12/10/2008
JORDAN, TOM
Vice President
01/01/2002
HARGREAVES, KATHERINE
Secretary
12/17/1993
12/10/2008
BURKS, ROY
Vice President
12/17/1993
12/15/1995
Bond Information
https://fortress.wa.gov/lni/bbip/Print. aspx
10/15/2012
10/10/2012 7:47 AM
(12134) \SHOP DRAWINGS \CAD \E0.01.DWG
J: \JOBS PENDING \PENDING DEF \EXPRESS SHOP- SOUTHCENTER MALL
SYMBOLS & ABBREVIATIONS
CIRCUITING SYMBOLS
NEW WIRING. HASH MARKS INDICATE NUMBER OF #12 AWG WIRE
UNLESS NOTED OTHERWISE, NO HASH MARKS INDICATES
TWO WIRES PLUS GROUND UNLESS NOTED OTHERWISE. LONG HASH
MARKS DENOTES NEUTRAL
�— INDICATES GROUND WIRE.
— INDICATES ISOLATED GROUND WIRE, WHERE SHOWN.
NEW WIRING RUN IN OR BELOW SLAB OR BELOW GRADE.
EXISTING RACEWAY OR WIRING (IF HASH MARKS ARE SHOWN
PULL NEW CONDUCTORS)
RACEWAY STUB -OUT WITH BUSHING
HOME RUN TO PANEL OR LOCATION NOTED
CIRCUIT CONTINUATION
0/1.0 JUNCTION BOX, CEILING /WALL
PULL BOX
HANDHOLE
int
---- P/r /� - --- UNDERGROUND UTILITY SERVICE -
POWER, TELEPHONE & CABLE AS INDICATED
P/T /c OVERHEAD UTILITY SERVICE -
POWER, TELEPHONE & CABLE AS INDICATED
C— 0 POWER POLE /GUY
�-- G --t GROUND WIRE
IRREVERSIBLE COMPRESSION TYPE CONNECTION
11.11
epep
Os
0
a
xy
C�}
0
CADWELD TYPE GROUND CONNECTION
GROUND TEST WELL
GROUND ROD
POWER SYMBOLS
DUPLEX RECEPTACLE 120V
DOUBLE DUPLEX RECEPTACLE 120V
DUPLEX / QUAD RECEPTACLE - EMERGENCY POWER
DUPLEX RECEPTACLE - GROUND FAULT CIRCUIT INTERRUPTER TYPE
DUPLEX RECEPTACLE - GROUND FAULT CIRCUIT INTERRUPTER TYPE, STANDBY POWER
DOUBLE DUPLEX RECEPTACLE - GROUND FAULT CIRCUIT INTERRUPTER TYPE
DEDICATED DUPLEX / QUAD RECEPTACLE
DUPLEX RECEPTACLE - SAFETY TYPE
DUPLEX RECEPTACLE - ABOVE COUNTER: MOUNT +6" ABOVE
COUNTER /SINK/ BACKSPLASH OR MOUNT +54" AFF AS APPLICABLE
GFI DUPLEX RECEPTACLE - ABOVE COUNTER: MOUNT +6" ABOVE
COUNTER /SINK/ BACKSPLASH OR MOUNT +54" AFF AS APPLICABLE
SPECIAL RECEPTACLE, NEMA /VOLTAGE AS INDICATED ON PLAN - ATTACH
TO DROP CORD FROM CEILING
SINGLE RECEPTACLE 120V
TRIPLE RECEPTACLE
SPLIT SWITCHED DUPLEX RECEPTACLE
FLUSH FLOOR BOX WITH DEVICE AS INDICATED
FLUSH MOUNTED CEILING RECEPTACLE
PEDESTAL TYPE FLOOR BOX WITH DEVICES AS SHOWN
FLUSH FLOOR POKE THROUGH - DEVICES AS INDICATED
SPECIAL RECEPTACLE, NEMA /VOLTAGE AS INDICATED
SPECIAL RECEPTACLE, NEMA /VOLTAGE AS INDICATED
DRYER RECEPTACLE
DISCONNECT SWITCH
FUSED DISCONNECT
MOTOR STARTER
COMBINATION MOTOR STARTER, DISCONNECT
MOTOR CONNECTION
EQUIPMENT CONNECTION
CLOCK HANGER AND OUTLET ON CRITICAL BRANCH CIRCUIT
CONTACTOR
MOTOR RATED SWITCH
GENERATOR REMOTE ANNUNCIATOR PANEL
PANEL - 208/120 VOLT SYSTEM, +6' TO TOP U.N.O.
PANEL - 480 VOLT SYSTEM, +6' TO TOP U.N.O.
RISER SYMBOLS
TRANSFER SWITCH
— s a-- CIRCUIT BREAKER
-4: %- DRAW OUT CIRCUIT BREAKER
FEEDER DESIGNATION
FUSED SWITCH
-L-
-= GROUND
PANS.
PANEL
GROUND FAULT CIRCUIT BREAKER
{III
y
TRANSFORMER
CABLE TO BUS CONNECTION
AVAILABLE SHORT CIRCUIT CURRENT
METER
XX NL
O
0
NL
NL
rr 4J
�os
os
PC
4
0
'0' AI
14
LIGHTING SYMBOLS
FLUORESCENT. FIXTURE, TYPE AS INDICATED ON PLAN
"XX" INDICATES FIXTURE TYPE, "NL" INDICATES 24HR NIGHTLIGHT OPERATION
FLUORESCENT STRIP FIXTURE, DRAWN TO SCALE
FIXTURE CEILING MOUNTED
FIXTURE WALL MOUNTED
FULL- SHADED FIXTURES SHALL BE CONNECTED TO STANDBY POWER
SERVICE PANEL, "NL" INDICATES 24HR NIGHTLIGHT OPERATION
HALF - SHADED FIXTURES SHALL HAVE INTEGRAL BATTERY BALLASTS
"NL" INDICATES 24HR NIGHTLIGHT OPERATION
POLE MOUNTED EXTERIOR LIGHT FIXTURE
BATTERY PACK EMERGENCY LIGHTING UNIT
BATTERY POWERED EXIT SIGN - ARROWS AS INDICATED, SHADING
INDICATES SIDE(S) ILLUMINATED.
BATTERY POWERED EXIT SIGN WITH INTEGRAL EMERGENCY LIGHTS, .
ARROWS AS INDICATED
SINGLE POLE SWITCH (LETTER INDICATES SWITCH LEG)
OCCUPANCY SENSOR WALL SWITCH
3 WAY SWITCH
INCANDESCENT DIMMER /SWITCH
FLUORESCENT DIMMER /SWITCH
DAYLIGHT SENSOR, # INDICATES CONTROLLED CIRCUIT DESIGNATION
CEILING OCCUPANCY SENSOR
PHOTO -CELL SWITCH MOUNTED UNDER SOFFIT, ORIENT NORTH
IIMECLOCK
FIXTURE PENDANT MOUNTED
WALL SCONCE
SURFACE MOUNT 2X4
TRACK LIGHTING
SIGNAL & COMMUNICATION SYMBOLS
MAGNETIC DOOR HOLD -OPEN. INTERNAL TO CLOSER HARDWARE
WHERE SHOWN AT HINGE.
FIRE ALARM MANUAL STATION +48"
SMOKE DETECTOR
"D" SUBSCRIPT INDICATES DUCT DETECTOR
"H ". SUBSCRIPT INDICATES HEAT DETECTOR
"R" SUBSCRIPT INDICATES 120V RESIDENCE DEVICE WITH AUDIBLE
TONE ALARM, BATTERY BACK -UP
DO COMBINATION HORN /STROBE, WALL MOUNTED AT +80"
UNLESS NOTED OTHERWISE
DO COMBINATION HORN /STROBE, CEILING MOUNTED
?13 FIRE ALARM STROBE ONLY, WALL MOUNTED AT +80"
UNLESS NOTED OTHERWISE
FARA
FIRE ALARM STROBE ONLY, CEILING MOUNTED
FIRE ALARM REMOTE ANNUNCIATOR PANEL
TELEPHONE OUTLET:
"W" INDICATES WALL PHONE AT +54"
D DATA OUTLET
MD
E ■ MC
COMBINATION TELE /DATA OUTLET
COMBINATION FIRE /SMOKE DAMPER CONNECTION
MOTORIZED DAMPER - 120V
MAGNETIC CONTACTS FOR WINDOW OR DOOR MONITORING
PEDESTAL TYPE FLOOR BOX WITH DEVICE TYPE AS SHOWN
—o CABLE RING ROUTE
6
ELECTRIC CLOCK
TV OUTLET
OO CEILING MOUNTED SPEAKER
WALL MOUNTED SPEAKER
MICROPHONE
TELEPHONE RISER
® FLOOR CORE FOR VOICE /DATA ONLY
CARD READER
AUDIBLE DOOR ALARM
VOLUME CONTROL AT +54"
EMERGENCY POWER OFF BUTTON
oTR
CR
DSI
CALL SYSTEM
RESIDENCE BATHROOM PULL CORD STATION
RESIDENCE BED STATION CALL CORD
RESIDENCE CALL /COMMUNICATION STATION
CALL SYSTEM MASTER COMMUNICATION STATION
CALL SYSTEM DOME LIGHT
"Z" INDICATES ZONE DOME LIGHT
DUTY STATION
STAFF CALL STATION
STAFF STATION r••
/1/ XXX
SEPARATE PERMIT
REQUIRED FOR:
IS[ mechanical
CI sichical
t Plumbing
trees Piping
City of Tukwila
BUILDING DIVISION
MISCELLANEOUS
FLAG NOTE
REVISION SYMBOL
EXISTING EQUIPMENT OR DEVICE
REMOVE EXISTING ELECTRICAL EQUIPMENT
EQUIPMENT IDENTIFIER
TYPICAL ROOM DETAIL REFERENCES:
XX - INDICATES DETAIL NUMBER
M - INDICATES THAT DETAIL IS MIRROR IMAGE
OF REFERENCED LOCATION
EY.Y - INDICATES SHEET WHERE DETAIL IS FOUND
DIRECTION OF ARROW INDICATES PLAN
ORIENTATION IN RELATION TO DETAIL
- — PROPERTY LINE
x-11114-- FENCING
REVISIONS
No oheroes shall be made to the scope
of work without prior approv4 # of
Tukwila Building Divi,,►nn
NOTE: Revisions will
crr..1 may in_., jdo c dCtiond p'o'i I .
CABLE TRAY
INDICATES COMBINATION POWER /TELE /DATA
POKE -THRU FLUSH
0 FURNITURE FEED JUNTION BOX.
ABBREVIATIONS
AC INDICATES ABOVE COUNTER MOUNTING
AT +4" ABOVE BACKSPLASH OR +6"
ABOVE COUNTERS WITHOUT BACKSPLASH
AFF ABOVE FINISHED FLOOR
A, AMP AMPERE
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAGE
(BTS) BASE TRANSFER STATION
CB CIRCUIT BREAKER
CKT CIRCUIT
DED DEDICATED
DW DISHWASHER
(E) EXISTING
EPO EMERGENCY POWER OFF
EWC ELECTRIC WATER COOLER
FA FIRE ALARM
FBOIC FURNISHED BY OTHERS,
INSTALLED BY CONTRACTOR
Fl FILM ILLUMINATOR
G, GND GROUND
GD GARBAGE DISPOSAL
GFI, GFCI GROUND FAULT CIRCUIT INTERRUPTER
HT HEIGHT
HWT HOT WATER TANK
IGN IGNITION
IH INSTA HOT
J -BOX JUNCTION BOX
MW MICROWAVE - COORDINATE
MOUNTING HEIGHT
N NEUTRAL
NC NURSE CALL
P POLE
PNL PANEL
PROVIDE FURNISH AND INSTALL
(R) RELOCATED (INDICATES EXISTING
EQUIPMENT TO BE RE- INSTALLED
AS SHOWN)
RO RACEWAY ONLY
RECPT RECEPTACLE
REF REFRIGERATOR
S SAFETY TYPE
SWBD SWITCHBOARD
TELCO TELEPHONE COMPANY
TELE TELEPHONE
TR TELEPHONE RISER
TYP TYPICAL
UC UNDERCABINET
UNO UNLESS NOTED OTHERWISE
✓ VOLT
W WIRE OR WATT
0 PHASE
W/0 WITHOUT
WP WEATHERPROOF
NOTE REGARDING DRAWINGS:
THESE DRAWINGS ARE PROVIDED FOR YOUR USE RELATING EXCLUSIVELY TO THE PROJECT
CONTAINED HEREIN. SEA -TAC ELCTRIC, INC. PROVIDES THESE DRAWINGS WITH THE FOLLOWING
STIPULATIONS:
1. THESE DRAWINGS, DOCUMENTS & DESIGN ARE PROTECTED BY THE RULES AND REGULATIONS
OF U.S. COPYRIGHT LAWS.
THESE DRAWINGS AND DOCUMENTS WERE COPIED FROM COMPUTER DATA CREATED AS A STEP
IN THE PRODUCTION OF PHYSICAL DATA FOR THIS PROJECT. THERE MAY BE DISCREPANCIES
BETWEEN THESE DOCUMENTS AND THE COMPUTER DATA. WHERE SUCH DISCREPANCIES EXIST,
ONLY THE PHYSICAL DOCUMENTS AND DRAWINGS CAN BE RELIED ON TO REFLECT THE WORK
OF SEA -TAC ELECTRIC, INC., WHO MAKES NO GUARANTEES OR WARRANTIES REGARDING THESE
DOCUMENTS OR THE DATA THEREIN.
3. IN ACCEPTING THESE DOCUMENTS, YOU ASSUME ALL LIABILITY FOR THE ACCURACY, UTILITY,
OR SUITABILITY FOR ANY PURPOSE FOR ANY DATA THESE DRAWINGS CONTAIN.
REVIEWLD.FOI
COMPLIANCE WITH
PA 70 -NEC
OCT 1 2 2012
City of
BUILDING
ila
ISICN
FXLE COPY
Permit No. y)—' O'\ I
Pon review approl ,i6 subject bloats and omissions.
I,, l oval o f c o n s t r u o t t o n dominant/Aloes oot au . :73 -
l;K y oratiof of any adopted code or ordinance. Rec4c.a, t
of approved Field Copy andconditions is acanowiadg cl:
Bys 4.1>70x.... -�
Date:
fd /;" ZQ /2-
Cif' Of Tukwila
BUI.D.:NiG DIVISION
'ELIE oc;'1
RECEIVED
CITY OF TUK'UVIL.A
OCT 10 2012
PERMIT CENTER
E0.01
E0.02
E0.03
E2.01
E3.01
E5.01
DRAWING INDEX
- SYMBOLS AND ABBREVIATIONS
- ELECTRICAL NOTES
- ELECTRICAL SCHEDULES
- POWER PLAN
- LIGHTING PLAN
- ONE -LINE RISER DIAGRAM &
PANEL SCHEDULES
I--
w
(1)
w
0
PHONE (253) 872 -5553
7056 SOUTH 220TH STREET
FAX (253) 872 -4112
KENT, WA 98032
REV #
633 SOUTHCENTER PARKWAY
(0
00
N
00
00
CO
C3�
5
DATE
DRAWN CM
CHECKED CM
DATE 10/10/2012
SYMBOLS &
ABBREVIATIONS
E0.01
GENERAL
NOTE: "CONTRACTOR" MEANS "ELECTRICAL CONTRACTOR" WHEN REFERENCED ANYWHERE
IN THE ELECTRICAL CONSTRUCTION DOCUMENTS UNLESS WORK AND EQUIPMENT HAS
BEEN COORDINATED BETWEEN THE ELECTRICAL AND GENERAL CONTRACTORS TO BE
PROVIDED BY THE GENERAL CONTRACTOR. "NEEDED ", "PROVIDE" AND "INSTALL" MEANS
ALL ITEMS CALLED OUT IN THE CONTRACT DOCUMENTS AND ANY ADDITIONAL ITEMS
NOT CALLED OUT BUT REQUIRED TO MAKE A COMPLETE AND OPERATIONAL SYSTEM.
SCOPE
THE INTENT OF THE SPECIFICATIONS AND THE DRAWINGS IS TO PROVIDE A COMPLETE
AND FULLY OPERATIONAL ELECTRICAL SYSTEM. THE ELECTRICAL CONTRACTOR SHALL
FURNISH AND INSTALL ALL LABOR, MATERIAL AND EQUIPMENT NECESSARY TO
COMPLETE THE ELECTRICAL WORK UNDER THE TERMS OF THE CONTRACT,
PERMITS AND FEES
THE ELECTRICAL CONTRACTOR SHALL PROCURE AND PAY FOR ALL PERMITS, FEES AND
INSPECTIONS NECESSARY TO COMPLETE THE ELECTRICAL SCOPE OF WORK PRIOR TO
STARTING THE WORK.
WARRANTY
THE ELECTRICAL CONTRACTOR SHALL UNCONDITIONALLY WARRANTY ALL WORK TO BE
FREE OF DEFECTS IN MATERIAL AND WORKMANSHIP FOR A PERIOD OF ONE (1) YEAR
FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER OR OWNER'S REPRESENTATIVE
AND WILL REPAIR OR REPLACE ANY DEFECTIVE WORK PROMPTLY AND WITHOUT CHARGE.
CODES
PERFORM ALL WORK IN ACCORDANCE WITH THE CURRENT NATIONAL ELECTRICAL CODE,
STATES, CITY ELECTRICAL CODES, AND ALL OTHER APPLICABLE CODES INCLUDING ANY
STATE OR LOCAL ENERGY CODES. ALL WORK SHALL ALSO BE IN COMPLIANCE WITH
BUILDING OWNER'S CRITERIA. IN CASE OF CONFLICT BETWEEN THE DRAWINGS,
SPECIFICATIONS, CODES, ORDINANCES, AND AUTHORITIES HAVING JURISDICTION, THE
MOST STRINGENT STANDARD (IN THE OPINION OF THE ENGINEER) SHALL APPLY. THE EC
SHALL SATISY CODE, AHJ, DRAWINGS, AND SPECIFICATIONS AS A MINIMUM STANDARD
WITHOUT ANY EXTRA COST.
STANDARDS
EQUIPMENT AND MATERIALS SHALL CONFORM WITH APPROPRIATE PROVISIONS OF NEC,
WAC, ASTM, UL, ETL, NEMA, ANSI, ASHRAE AND OTHER APPLICABLE AGENCY AS THEY
APPLY TO EACH INDIVIDUAL UNIT OR ASSEMBLY.
LEED (IF APPLICABLE)
ALL WORK, MATERIALS AND EQUIPMENT SHALL MEET LEED REQUIREMENTS & CODE. IN
CASE OF CONFLICT, THE HIGHER STANDARD SHALL APPLY.
GENERAL ELECTRICAL NOTES:
1. EC SHALL VERIFY THE LOCATION OF ALL EXISTING UTILITIES PRIOR TO CONSTRUCTION
AND BE RESPONSIBLE FOR SITE INVESTIGATION PRIOR TO START OF WORK TO REVEAL
THE FULL SCOPE OF WORK. IN ADDITION, THE EC SHALL THOROUGHLY EXAMINE ALL
AREAS WHERE EQUIPMENT, CONDUIT, AND WIRING WILL BE INSTALLED AND WILL REPORT
ANY CONDITION THAT PREVENTS THE PROPER INSTALLATION OF THE ELECTRICAL WORK.
2. EC SHALL COORDINATE WITH THE GC TO PATCH AND REPAIR ALL EXISTING WALLS,
FLOORS, CEILINGS OR OTHER SURFACES IDENTIFIED TO REMAIN THAT MAY BECOME
DAMAGED DURING THE COURSE OF WORK.
EXPOSED /SURFACE MOUNTED CONDUITS SHALL ONLY BE ALLOWED WHERE NECESSARY
IN EXPOSED CEILING AREAS. IF CONDUITS NEED TO BE SURFACE MOUNTED TO WALLS,
COORDINATE WITH OWNER OR OWNER'S REPRESENTATIVE FOR APPROVAL.
VERIFY LOCATION OF ALL OUTLETS AND SWITCHES WITH ARCHITECTURAL DRAWINGS,
INTERIOR DETAILS, FINISH SCHEDULES, GENERAL CONTRACTOR, EQUIPMENT VENDORS,
OWNER OR OWNER'S REPRESENTATIVE AND EXISTING SITE CONDITIONS. VERIFY FINAL
DOOR HINGE LOCATION PRIOR TO SWITCH INSTALLATION AND ADJUST SWITCH LOCATION
IF NEEDED. DO NOT MOUNT RECEPTACLES /SWITCHES IN LOCATIONS THAT WOULD
CONFLICT WITH MIRRORS, SEAMS OF WALLS, WAINSCOTS, 11LE TRANSITIONS, ETC.
DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL INTENT OR ARRANGEMENT OF
5. SYSTEM(S). FOLLOW DRAWINGS IN LAYING OUT WORK AND COORD. WITH OTHER TRADES
TO VERIFY SPACE CONDITIONS AND CLEARANCES. MAINTAIN HEADROOM AND SPACE
CONDITION. MAKE APPROPRIATE ADJUSTMENTS AT OWNER OR OWNER'S CONTRACTOR'S
DIRECTION.
COORDINATE WITH OTHER TRADES FOR ANY NEEDED LOW VOLTAGE CONTROL WIRING
6. AND DEVICES THAT IS NEEDED BUT MAY NOT BE SHOWN IN THESE DRAWINGS.
TEMPORARY POWER: REUSE EXISTING PANEL (IF IN GOOD CONDITION) AND SERVICE FOR
7. TEMPORARY CONSTRUCTION POWER. ALL RECEPTACLES TO BE USED DURING
CONSTRUCTION SHALL BE GFI PROTECTED.
ALL ELECTRICAL SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. BALANCE ALL
BRANCH CIRCUITS LOADS BETWEEN THE PHASES OF THE SYSTEM TO WITHIN 109 OF
THE HIGHEST PHASE LOAD IN EACH PANELBOARD.
THE EC SHALL SCHEDULE ALL ELECTRICAL SYSTEM(S) SHUTDOWNS WITH THE GENERAL
CONTRACTOR AND LANDLORD AT LEAST 24 HOURS IN ADVANCE. UNLESS APPROVED
OTHERWISE ALL SHUTDOWNS SHALL OCCUR BETWEEN 11: OOPM AND 5: OOAM.
ALL CONDUCTORS ARE A MINIMUM OF #12 AWG CU UNLESS NOTED OTHERWISE. MC
10. FEEDER CAN BE USED WHERE APPROPRIATE AND AT CONTRACTOR'S DISCRETION. MC
FEEDER SHALL BE SIZED PER NEC REQUIREMENTS.
MULTI -WIRE BRANCH CIRCUITS SHALL MEET NEC 210.4 REQUIREMENTS.
BASIC MATERIALS AND METHODS
MATERIALS: PROVIDE ALL NEW MATERIAL AND EQUIPMENT UNLESS NOTED OTHERWISE.
ALL EQUIPMENT SHALL BE UL APPROVED, LABELED, AND LISTED OR OTHER APPROVED
TESTING ORGANIZATION WHICH HAS ACCEPTANCE BY THE AUTHORITIES HAVING
JURISDICTION FOR THE PURPOSE FOR WHICH THEY ARE USED. IN ADDITION, MEETING
ALL REQUIREMENTS OF THE CURRENT APPLICABLE CODES AND REGULATIONS. NO
SUBSTITUTION OF MATERIALS SPECIFIED WILL BE ALLOWED UNLESS NOTED OTHERWISE.
ALL ITEMS ARE NEW UNLESS OTHERWISE NOTED.
CUTTING AND FITTING: ALL CUTTING, CORING, FITTING OR TRENCHING OF THE WORK
NECESSARY FOR THE INSTALLATION OF THE EQUIPMENT SHALL BE EXCLUDED FROM THE
SCOPE OF WORK UNLESS NOTED OTHERWISE.
RACEWAYS
PROVIDE CODE APPROVED WIRING METHODS FOR BRANCH CIRCUITING INDOORS, SUCH
AS EMT CONDUIT WITH COPPER CONDUCTORS ORR MC CABLE (PROVIDED IT IS
CONCEALED FROM VIEW AND NOT EXPOSED). ALL ABOVE GROUND CONDUITS SHALL BE
EMT OR RIGID, MINIMUM 1/2" IN SIZE (UNO). CONDUITS SHALL BE SIZED PER CODE
AND AS NEEDED TO INSTALL CONDUCTORS. CONDUIT CONNECTORS SHALL BE DOUBLE
LOCKNUT TYPE, UL LISTED AND LABELED, WITH COMPRESSION OR SET SCREW FITTINGS.
PVC CONDUITS ARE NOT ALLOWED ABOVE SLAB UNLESS CODE AND AHJ
APPROVED /LISTED FOR THAT USE.
CONDUIT RUNS ON EXTERIOR OF BUILDING SHALL BE CONCEALED AND BE RIGID STEEL
CONDUIT WITH WEATHER TIGHT, CORRISION- RESISTANT FITTINGS (OR PVC WHERE LISTED
FOR EXTERIOR- SUNLIGHT USE). CONDUIT SHALL NOT BE RUN EXPOSED WITHOUT
SPECIFIC PERMISSION FROM THE CONSTRUCTION MANAGER.
WHERE RACEWAYS ARE INSTALLED FOR OTHERS TO USE, OR FOR FUTURE USE,
PROVIDE NYLON PULL STRINGS END TO END WITH A LABEL ON BOTH ENDS STATING
USE AND LOCATION OF OTHER STUB (E.G. DATA -FRONT POS).
PENETRATIONS THROUGH FIRE RATED CONSTRUCTION SHALL BE SEALED USING A
METHOD APPROVED THE ARCHITECT AND LAHJ.
CONDUIT RUNS CONCEALED IN CONCRETE OR UNDERGROUND SHALL BE 3/4" MINIMUM,
UNLESS OTHERWISE NOTED W /RIGID STEEL ELBOWS. CONDUIT CONNECTORS SHALL BE
DOUBLE LOCKNUT TYPE, UL LISTED AND LABELED, WITH COMPRESSION OR SET SCREW
FITTINGS.
IF CONDUIT RACEWAYS CANNOT BE RECESSED IN WALLS DUE TO CONSTRUCTION OR
EXISTING CONDITIONS, PROVIDE A STEEL SURFACE MOUNTED RACEWAY SYSTEM WITH
ALL COMPATIBLE DEVICES. THIS TYPE OF SYSTEM IS ONLY ALLOWED WHERE APPROVED
BY OWNER OR OWNER'S REPRESENTATIVE INCLUDING LAYOUT. CONFIRM COLOR AND
ANY CUSTOM FINISHES WITH OWNER OR OWNER(S) REPRESENTATIVE.
CONDUCTORS AND TERMINATIONS
CONDUCTORS: ALL CONDUCTORS ARE A MINIMUM OF #12 AWG CU UNLESS NOTED
OTHERWISE. MC FEEDER CAN BE USED WHERE APPROPRIATE AND AT CONTRACTOR'S
DISCRETION. MC FEEDER SHALL BE SIZED PER NEC REQUIREMENTS.
MOTORS AND OTHER WIRING: THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL
NEEDED CONDUIT, WIRING, CONNECTIONS, AND SAFETY SWITCHES FOR ALL MOTORS, AND
EQUIPMENT, EVEN IF THE MOTORS AND EQUIPMENT ARE SUPPLIED BY OTHERS. MOTORS,
CONTROLS, ETC. MAY BE FURNISHED BY THE SUPPLIER OF THE DRIVEN EQUIPMENT.
THE ELECTRICAL CONTRACTOR SHALL INCLUDE ALL WORK AND CONNECTIONS NEEDED
TO MAKE THE SYSTEM COMPLETE AND OPERATIONAL.
ALL CONNECTIONS TO MECHANICAL EQUIPMENT SHALL BE DONE BY THE ELECTRICAL
CONTRACTOR.
THE ELECTRICAL CONTRACTOR SHALL VERIFY EQUIPMENT LOCATION AND SIZES WITH
THE TRADE AND VENDOR SUPPLYING THE EQUIPMENT PRIOR TO ROUGH -IN.
GROUNDING
ALL MAJOR PARTS NOT CARRYING CURRENT, INCLUDING BUT NOT LIMITED TO,
SECONDARY FEEDER CIRCUIT, EQUIPMENT AND PANELBOARD ENCLOSURES, PULL AND
JUNCTION BOXES AND OTHERS DEFINED BY CODE, SHALL BE PROPERLY GROUNDED.
METALLIC RACEWAYS SHALL UTILIZE DOUBLE LOCKNUTS AND OTHER FITTINGS TO
PROVIDE GROUND CONTINUITY.
SWITCHES AND RECEPTACLES
SWITCHES: CONTRACTOR CHOSEN OWNER /OWNER(S) REPRESENTATIVE APPROVED WITH
DURABLE COVERPLATES. COORDINATE WITH OWNER OR OWNER'S REPRESENTATIVE FOR
COVERPLATE TYPE (E.G. STAINLESS STEEL) AND FOR COLOR OF SWITCH AND PLATE.
RECEPTACLES: CONTRACTOR CHOSEN OWNER /OWNER(S) REPRESENTATIVE APPROVED
WITH DURABLE COVERPLATES. COORDINATE WITH OWNER OR OWNER'S REPRESENTATIVE
DM FOR FOR COVERPLATE TYPE (E.G. STAINLESS STEEL) AND FOR COLOR OF
RECEPTACLE AND PLATE. INSTALL RECEPTACLES PLUMB, LEVEL, AND SECURE TO
J -BOX. PROVIDE GFCI TYPE WHERE INDICATED AND WHERE REQUIRED BY CODE AND
LAHJ. GFCI RECEPTACLES SHALL BE CLASS A RATED FOR PERSONNEL PROTECTION.
OCCUPANCY SENSORS: CONTRACTOR TO DESIGN CODE BASE MINIMUM SYSTEM.
LOW VOLTAGE
ALL LOW VOLTAGE WORK SHALL COMPLY, BE PERMITTED AND INSPECTED PER STATE
(AND LAHJ) REQUIREMENTS. ALL LOW VOLTAGE WORK SHALL BE INSTALLED BY A
LICENSED • CONTRACTOR IN ACCORDANCE WITH THE STATE AND LAHJ REQUIREMENTS.
ALL LOW VOLTAGE CABLING INSTALLED UNDERGROUND SHALL BE ROUTED IN A CONDUIT
RACEWAY AND CABLING /CONDUCTORS SHALL BE LISTED FOR USE IN WET LOCATIONS,
FOR LOW VOLTAGE APPLICATION AND PER LAHJ.
ALL LOW VOLTAGE CABLING ROUTED INDOORS SHALL BE ROUTED CONCEALED IN
WALLS /CEILINGS IN A CONDUIT RACEWAY (UNLESS OWNER AND LAHJ AUTHORIZE IT TO
BE ROUTED EXPOSED THROUGH WALL /CEILING). IF APPROVED BY OWNER & LAHJ TO BE
ROUTED EXPOSED, CABLING SHALL BE PROPERLY FASTENED /SUPPORTED PER CODE,
LAHJ, AND INDUSTRY STANDARDS. CABLING NOT ROUTED IN CONDUIT SHALL BE
PLENUM RATED WHERE REQUIRED BY CODE OR LAHJ (CONFIRM WHETHER CEILING
SPACE IS BEING USED AS AN AIR PLENUM.)
ALL LOW VOLTAGE CABLING OUTDOORS (E.G. ON ROOF) SHALL BE ROUTED IN CONDUIT
PER CODE AND LAHJ REQUIREMENTS UNLESS SPECIFICALLY LISTED AND LABELED FOR
EXTERIOR USE.
PANELBOARDS
PANELBOARDS SHALL HAVE PLUG -IN OR BOLT ON BREAKERS AND MAIN LUGS ONLY OR
MAIN BREAKERS AS NEEDED OR REQUIRED. PANELBOARDS SHALL BE CONSTRUCTED
WITH ALUMINUM BUS AND BE ENCLOSED IN NEMA 1 HOUSING (OR AS REQ'D BY CODE).
ENCLOSURE(S) SHALL BE COMPLETE WITH A HINGED DOOR, CYLINDER LOCK, AND A
NEATLY TYPED CIRCUIT BREAKER DIRECTORY UNDER PLASTIC COVER IN EACH PANEL.
ALL MULTIPLE POLE BREAKERS (AND OTHER BREAKERS REQ'D BY CODE) SHALL HAVE
A COMMON TRIP HANDLE.
FUSED SWITCHES
FUSED SWITCHES: HEAVY DUTY TYPE, HORSE POWER RATED WITH INTERLOCKING COVER.
NEMA 1 TYPICAL. OUTDOORS AND WET LOCATION SWITCHES SHALL BE RAINTIGHT TYPE
NEMA 3R. ALL SWITCHES SHALL BE LOCKABLE. FUSES IN CIRCUITS RATED AT 600A OR
LESS SHALL BE UL CLASS RK1 DUAL- ELEMENT, TIME DELAY, CURRENT LIMITING FUSES.
FUSES IN CIRCUITS RATED AT 601A OR LARGER SHALL BE UL CLASS L TIME- DELAY,
CURRENT LIMITING SWITCHES.
MOUNTING
MOUNT DISCONNECTS TO STRUCTURE, INDEPENDENT OF THE MECHANICAL UNIT HOUSING
OR WITH INDEPENDENT UNISTRUT SUPPORT. DISCONNECTS MOUNTED TO UNITS ARE
ONLY ALLOWED WHERE ACCEPTED BY THE LAHJ AND LOCATED SO AS TO NOT BLOCK
ACCESS OR LABELS OF UNIT.
NAMEPLATES
PROVIDE PHENOLIC NAMEPLATES ON ELECTRICAL DEVICES SUCH AS DISCONNECTS AND
PANELS WITH THEIR DESIGNATION (E.G. "PANEL H1 "). PROVIDE DIRECTORY FOR PANELS
AND LABEL ALL BREAKERS. IF A TRANSFORMER IS INSTALLED, PROVIDE NAMEPLATE ON
TRANSFORMER AS FOLLOWS: "HOT SURFACE, DO NOT PLACE ANY ITEMS ON TOP OR
ON SIDES OF TRANSFORMER ".
REVIEWED 1-Oh
COMPLIANCE WITh
NFPA 70 - NEC
OCT 1 2 2012
City of Tukwila
BUILDING DIVIS!Oc';
FLIP -� 09s7
RECWVIE
CITY OF TUKWIL.A.
OCT 10 2012
PERMIT CENTER
w
w
0
0
0
w
J
w
PHONE (253) 872 -5553
7056 SOUTH 220TH STREET
FAX (253) 872 -4112
KENT, WA 98032
J
J
0 2
ct ct c\I
u a. co
F"" w�
WZ <
vs
a.
X I-
W O M
CI)
REV#
DATE
DRAWN CM
CHECKED CM
DATE 10/10/2012
ELECTRICAL NOTES
E0.02
SHOP- SOUTHCENTER MALL
J: \JOBS - PENDING \PENDING DEF \EXPRESS
TYPE
F1.
F2
F3
F4
F5.
F5X;
P1
X1.
GE NE
1.
!LIGHT FIXTURE SCHEDULE:
MANUFACTURER
... _.._..__.. .......... _...
............_...._...
TERIOR LN
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
TFID
EXISTING
EXISTING
INCA!
SERIES NO.
(CATALOG NO.)
EX EXIST NG
EXISTING'.
EXISTING
EXISTING
EXISTING
EXISTING
TBD
EXISTING<
EXISTING!
VOLT
120
120
120
120
120
120
120
120.
120
LAMP
TYPE
26V : CFL
26W CFL
F32T8,
1.5 W LED •
F32T8
F32Ta
50W:
INCAND.
6W HALOGEN:`
J HALOGEN
AST
Electronic
<1.0. %THE)
Electronic
X10 %TH D
El ectronic
<10 %THID
LED
DRIVER
EI
ectronic
<10%THD
Electronic
<10 %THD
FIXTURE
WATTS
26.
26
30
30
30
30
11
11
EXISTING:
EXISTING
EXISTING:
....................
EXISTING
EXISTING
EXISTING -<SAME AS FIXTURE F5
DECORATIVE PENDANT FIXTURE
EXISTING":
EXISTING
1L NOTES'
AIL IN:DICATED;CATALOG NUMBERS" REPRESENTA DESIGN BASIS ONLYAND CORRESPOND TO THE LISTED MANUFACTURERS SERIES NUMBER..
ALL OPTIONS, ACCESSORIES AND /OR FIXTI.IRE COMPONENTS MAY NOT'8E REFLECTED IN THIS-NUMBE;R AND CONTRACTOWRESPONSIOLE CONTRACTOR FOR: PROVIDI NG
ALL SUCH ITEMS DISCLOSED IN FIXTURE DESCRIPTION: AND /OR'SPECIFICATIONS. SUBSTITUTION OF FIXTURE TYPES WILL ONLY BE ACCEPTED IF
PHOTOIMIETRICS, CONSTRUCTION /COM,PONE'NT QUALITYAN? DESIGN INTEGRITY ARE;: SHOWN TO BE EQUAL TOrTHE pE5ippi INTENT. FINAL D)SCREfION.
TO BE DETERMINED BYENGINEER,.ALLSUBSTITUTIONS SHALL INCLUDE PHOTOMETRICSAND BE RECEIVED (5) BUSINESS DAYS: PRIOR TO
CLOSING FOR ENGINEERING ANALYSIS
PROVIDE COLD WEATHER BALLASTS FOR ALL OUTDOOR FIXTURES::
ALL FLUORESCEIN AND HID LIGHTING FIXTURES SHALL BE PROVIDED WITH IN-LINE CSLtt FUSE.
4. CONTRACTOR T4i VERIFY CEI LI NG c9N,PITIQId$ FQR P ROPER :QiiNTIN6 t-IAFit3WARE
INHERE; FIXTURES ARE SHOWN SHADED PROVIDE BATTERY BALLAST WITH REMOTE TEST BUTTON.
REVIEWED FOf
COMPLIANCE WITH
NFPA70 -NEC
OCT 1 2 2012
City of Tukwila
B UILDING DIVISION
NLY;1
2009 Washington State Nonresidential Energy Cade Camplianee Fiirms.
Project Info
*et
Project: Address
ICI
CRI
TtQ.N
TII EMERGENCYOPERATION
FLAG;
NOTES
IMPRESS SHOP - SOUTHCB1TERMALL
1458 SOUTHOENTER,M ALL.- .T NT SPACE .# 1584
TLIKWILA; WA $81$828'
Applicant Nance: t C, INC.
Applicant Address: 17055 S. 220TH STREET
SEA TAO ELECTRI
Applicant Phone: ?(253j 872 - 6553
Iescrip ion ..wa..
'oxnpiianceptlori
ew Building 1 I 1 (Alteration
k 98032:
Date
For Building"Qi
10
0/2012
Addition'
Plans Included
Refer to WSEC Section 1513 for controls and commissioning requirements.
Prescrcptnre Lighicng R erAliow ancelDSyste s Anaiysis
((See Qualitication,Checklist (over). Indicate Rescriptive & LPA spines c:leariy eri plans.)
Alteration Ex :eptons 'w
(c heckappropFi ebox -sec 1132..31
No changes are being made to the IltitIng
s a t 3
Less than 60% 4f fixtures new , installed lighting w attage is it6f not increased and space use is not changed
Maximum
Location
(floor /room n0.)
i01VC
Lighting Wattage (Inletior
RETAIL •
gQccupancy Description
*" From Table 15- (over) - docurtti n
alt eicceptions an form LTG -LPA •
;Allow edl
Waits per ft ? "
1 .3.
_ Total*
Arai
AIIoWed'x Area
12450
1655:9:
1655:9
Proposed Lighting Wattage
Location;
(floor(room na,),
Fl
Fixture Owription:
EXISTING DOWNLIGHT -:IL 26W`CFL
t
hiuinber o €.
Fixtures
1
F2 EXISTING WALL WASH E)t3WNLIGHT -1L 26W AFL i 9
F3 EXISTING RECESSED LINEAR WALL WASH - 2L F321 11
F4 EXISTING RECESSED SPOT LIGHT
F5 EXISTING 2X2 REGESSEDPRISMMMATIP -'2L F32T8'
F5X
P1
EXISTING 2X2' RECESSE PRISMATIC - 2L F32T8i
DECORATIVE PENDANT FIXTURE
Xt EXISTING EXIT BOOM COMBO
X2 : EXISTING EM ER. slier RUGEYEE •
Total Proposed Watls-iney not •exceed TotalAllawed Watts for Interior
Watts/
Fixture
26
30
30
30
30
111
11
Total Proposed Wafts
Watts
Proposed'
26.0
234.0
330.0
240.0'
240:0
60:0.
150.0
33.0
44.0
135T:0
RECEIVED
CITY OF TUKIMLA
OCT 102012
PERMIT CENTER
W
U)
w
0
U_
ce
U
w
J
w
J
J
0 2
rt
uw) W
U)
UJ Z
W w
Ce
CL W
(I)
REV #
PHONE (253) 872 -5553
7056 SOUTH 220TH STREET
FAX (253) 872 -4112
KENT, WA 98032
Q
(4)
op
1
a. 03
cc 07,
w 0)
Q
Z�
w
UQ
�O
VJ
M
co
DATE
DRAWN CM
CHECKED CM
DATE 10/10/2012
ELECTRICAL
SCHEDULES
E0.03
10/10/2012 7:48 AM
TELE /DATA
BACKBOARD
PANEL L1
75kVA XFMR
00,
0
00d
REFRIGERATED
BEVERAGE CASE
REFRIGERATED
BEVERAGE CASE
00 .
L1 -2
L1 -4
L1 -11
REACH -IN FOOD CASE
O
L1 -13�
L1 -15 J
Li -17,19
L1 -21
L1 -2:
L1 -25,2i
L1 -29,31
BAKERY
DISPLAY
POS
L1 -3
REACH -IN FOOD CASE
SLURPEE MACHINE
NEMA 5 -15P
POP MACHINE
a
ICED TEA MACHINE
�-® CAPPUCCINO MACHINE
NEMA 5 -15P
-F— SELF -SERVE
COFFEE MACHINE
L1 -37
POWER PLAN
SCALE: 1 /4" = 1' -0"
COFFEE WARMER
-•-- MICROWAVE
NEMA 5 -15P
GENERAL NOTES:
ALL CONDUCTORS ARE #12 AWG CU UNLESS NOTED OTHERWISE. MC • FEEDER
CAN BE USED WHERE APPROPRIATE AND AT CONTRACTOR'S DISCRETION. MC
FEEDER SHALL BE SIZED PER NEC REQUIREMENTS.
2. MULTI-WIRE BRANCH CIRCUITS SHALL MEET NEC 210.4 REQUIREMENTS.
3. NEW 8 -DOOR COOLER TO BE PERMITTED AND COORDINATED SEPARATELY.
4. ALL POWER AND LIGHTING TO BE CIRCUITED TO PANEL "L1" UNLESS NOTED
OTHERWISE.
FLAG NOTES:
NOT USED
RECEPATACLE FOR FUTURE INFRASTRUCTURE AT SALES COUNTER.
RE -FEED EXISTING HAND DRYER TO NEW PANEL "L1 ".
RE -FEED EXISTING RECEPTACLE TO NEW PANEL "L1 ".
REVIE'V11t1) .I -0I't
CO FPA OC
WITH
OCT 1 2 2012
City of Tukwila
BUIL . IN c DIVISIn I
Li)O'157
1--
w
0)
RECEIVED „ 1-
CITY OF TUKWILA
OCT 10 2012 w
PERMIT CENTER LOU_
PHONE (253) 872 -5553
7056 SOUTH 220TH STREET
KENT, WA 98032
J
J >-.
o_ < <
O2 �
Z ct a c 10
(0 W cc 07,
(1) I— w o)
(I) W w
Ill
�
C,C 0 i _,
W �Q
X F' ° �
W O M
CO
REV # DATE
DRAWN CM
CHECKED CM
DATE 10/10/2012
POWER PLAN
E2.01
PANEL L1
75kVA XFMR
F3 16b t";7 O
16b1I I$ F4
LJ16c
F3f
II
X2 16b1
-gyp I o IF4
L°_J16c
16 F3n
II
16b1
F3I-I
16b1
F2
I-074
L°J16c
9160
F3 1
C4]
16c
0
F4
16c
X1
�
P1
16d
44P1
'16d
�
P1
16d
0
,,F1
16a
6
F3 16b
C._ nF3
g1F4 1 I
LJ16c U16b
f F3
11
I-1F4 U16b X2
LgJ16c F3 .4-
f 16
II
116b
4 1-1F3
L°J16c 1J16b
e
coo
LIGHTING PLAN
SCALE: 1/4" = 1' -0"
COMPLIANCE. . NEC N'�PA
of Tukwila
GPI G plvlsr .
GENERAL NOTES:
ALL CONDUCTORS ARE #12 AWG CU UNLESS NOTED OTHERWISE. MC FEEDER
CAN BE USED WHERE APPROPRIATE AND AT CONTRACTOR'S DISCRETION. MC
FEEDER SHALL BE SIZED PER NEC REQUIREMENTS.
MULTI -WIRE BRANCH CIRCUITS SHALL MEET NEC 210.4 REQUIREMENTS.
ENERGY CODE NOTES:
1. ALL LIGHTING NOT INDICATED AS A 24 -HOUR NIGHT LIGHT SHALL BE
CONTROLLED BY TIMECLOCK OR OCCUPANCY SENSORS. ALL LOCAL
SWITCHES SHALL BE DOWNSTREAM OF AUTOMATIC CONTROLS.
COMMISSIONING REQUIREMENTS: IN ACCORDANCE WITH WSEC 1513.7, ALL
AUTOMATIC LIGHTING CONTROLS (INCLUDING TIMERS & OCCUPANCY
SENSORS) SHALL BE TESTED TO ENSURE THAT CONTROL DEVICES,
COMPONENTS, EQUIPMENT AND SYSTEMS ARE CALIBRATED, ADJUSTED AND
OPERATE IN ACCORDANCE WITH APPROVED PLANS AND SPECIFICATIONS.
SEQUENCES OF OPERA -10N SHALL BE FUNCTIONALLY TESTED TO ENSURE
THEY OPERATE IN ACCORDANCE WITH APPROVED PLANS AND
SPECIFICATIONS. A COMPLETE REPORT OF TEST PROCEDURES AND
RESULTS SHALL BE PREPARED AND FILED WITH THE OWNER.
ELP—%--0c15-7
RECEIvED
CITY OF TUI(WIL,A
OCT 102012
PERMIT CENTER
U
Q
W
U
w
J
w
7056 SOUTH 220TH STREET
KENT, WA 98032
J
0 2
U) Ill] CL a00o
w
W U
Ct
X 1-
W 1 D 02M ~
Cn
REV #
DATE
DRAWN CM
CHECKED CM
DATE 10/10/2012
LIGHTING PLAN
E3.01
PANEL SCHEDU:
PANEL ILI:
AMP: • 200 PAP.
TYPE EXISTING.
ATI9N:
STOCK ROOM. 003:
NEW
STYLE-.
VOLTS;: :208 Y.
AIC RATING . 14,000 .,...
NEUTRAL 140
I SURFACE. ❑ FLUSH:....
M $ -:kk EAR (VIA 75kVAA FMR }.
•
CIRCUIT DESC' IP
LOAD
TYPE
LOAD
KVA
GK
1
REC STOCK 00
REC RESTROOM 002
HANND DRYER.
,
C:
REC GONDOLA.
REC GONDOLA.
REFRIGERATED BEVERAGE CASES
FACE FUTURE 8 DOflR COU}:ER :
REACH IN REFER FOOD CASE
REACH=IN REFER FOO[} CASE
14
LTG LTG - RESTROOM 002 STOCK GE3
TEA MACHINE
CAPPUCCINO O MACHINE
SEEP SERVE'COFFEEMACHIrIE _._...:..__...s _......._. _.
COFFEE WARMER _ ;..:.,,'
MICROWAVE
MISC 16$ 14.
MSC ' 168
MISC. 180
MISC 3:80
MISG
MISC 1.50 20 1 :., 33,
MISC. 1.00 20' 1.. 35_
MISC: 0:12: 20 1 37,
REC 0.18' 2k 1 38
MISC 1 :.00: 20 1
28 1 21
40 2 25
A
A
POS
BAKERY DISPLAY
REC SALES: COUNTER
ESTIMATED MAXIMUM REMAND (EMD) CALCULATIO! 5
•
•
•
:...........
LOAD SUMlMARYp
_...,._.,
RESIDENTLTG1RECiT i RES::,_...
SMALL APPLIANCE ..... +RES;.,
LARGEST MOTOR .
REMM4ING MOTORS. MTR '
GE PURP N OSE RECPT REC
COMPUTER RECPf ... MISC,,. .
EQUIPIOTHER... MSC,;
HEATING A ..... MISC:_.,.....
ELEVATOR E.LEV .....
KITCHEN EGII'T KFrCH'<
..
TOTALS
'TYPE:, ?
CONNECTED•
B
B
LTG-SALES 001:..:.....,
SPACE'
2...... .......... ..... :......._......__.....__ ,,...... AE :,
j.
:, : SPACE
PACE: I
2 ; SPACE 1
$ :. FAE' .,....
3D' SPACE,
2 SPACE , ,c c •
Ii: SPACE:
'3& SPACE
38 3 60; 4.32 MTR U 1,4 :IETINO? ,, :..,,,,.,,... • _..,.,
40 ,..'132 ;....,.. ? ........ HI
127 ,KVA: 159 KVA (125 %}
tt_0i1' FCVA
,,,�GONNECTED PHASE' LOADING''
PHASE B ' 141C t4W,4 . ..:...
PHASE C 1603 K .A
PAP:. KVA 1.10ttP35C25_1 ....
0.00 KVA (1,G0/305: 54.
1296 ICVA 1620 KVA {125% },,
1 6k A 1 S0,KVA(10%V
2.52 KVA
2.52. (51096;? 1QKVAl :
0.00
KVA : COO' KVA (100% 4;
3410 ,KVA ..,t...., 3010 KV11(1,44°le }...,
G.:14/;, KVA 0 00 6411005g
0 0 KVA 0 k4 KVA 100%
41: KVA, „ P,0.4 I{VA, 05°fa, .
4646' iKy.6 52 01 KVA
13443 :.,AMPS :.... :........._144.37.. AM.PS!
GENERAL NOTES •
1:,., PEi N€ 0210 4(A & (5) ALL MULTW. RE BRANCH CIRCU1rSSHF RINCA COMMON
MUST SE R4OVIDED WFTH A MEANS 7 IAT VYILL SIFa1l1LTANEOUSLY L]tS ONNECT ALLLINGSOUNQEC
CO IDUCTi1RS Al TFE POIf I OF (BRIG 14 CONTR SCTQR D CHbK E PROVIDE SEPARATE NEUTRALS
SRFA2K] R Ff}R SHAREt3 NEUTRt L.... .
LOAD TYPE
COMB 4=IPPIVelillglor LOAD T'1TEa O4:1NDjCATED CIRCUIT .
RES 4ESIQEFTIALLTGIRECPTORSMALL r4PPI:IANPE LOAD TAKEN ATNDICATED DEMAND
'`MISC "= iEciLiP. COMPUTERREC'OR HTG LOAD ON INDICATED. CIReUFtAT 100%
FEEDE'R-SCHEDULEALUMINUM
03N: 3/4 "
4 #8, 4069: 3Q / 30
03 314 ".
04N< 1"
4 -#6, 1 #8 G 40 t 40
04 1 " 3 w#6, 1 #8 G 40 / 4Q
0511 1 1/4" -77-417.44, 1 #8 55 / 50:..
1 #4, 1 #8 G 55 / 50
06N 11/4- 4 /4 "" 4 ,-#3,..1.#s'G 65160
06 1 1/4'" 3 #3, 1 #8 G .66t60:
60
07N '1 114'+ 4-#2, 1#6 G ...,,,,75 / 70 ...
7 1 1/4" 3--i2, 1#6. G. 75/70 '
08N 1 1/4" 4 #1, 1#6 G 55 / 8A
8.:.:. 1 114 3 #1, 1#'G 6 85 / 80:.
10N • 2" 4 -#1/0; 1 #6 G. 1201 10o
10 1 1 /2"
12N 2 "
13N
13
15N
15
18N 2 1/2'"
18 2 "
N
20., 21/2
20 21/2A1
21/2 "..,
22! 2 1/2"
25N
•
25.
27N;......_
3-# /0, 1 #6 G 120
4 #1 /0, 1#4 G. 1201 110 75-deg rating _:...m.,.
3 - #1'10, 1#4 G; 1201 110 75-deg rating
4 #2/0, 1 #4 G 1351 125 75- deg rating....- _...:,
3 . #210, 1 #4 G .w.., :. ,_.., •75 -+deg rating :..:.,:.., _,...
4 #3/0, 1 #4 G 155 / 150 75 -deg ratio
3 #3/0, 1 #4 G 155•115o 75-deg rating
4 #4/0, 1 #4 G 100 / 175 75-de rating
60-deg rating ,, :......,,.__..
60 -deg rating
6G -deg rating
60-deg rating
60-deg rating . ...._..........:.
60-deg rating
60-deg rating
60-deg rating
60-deg rating .._.. _.
60 -.deg rating
60-deg rating .... :.. :.....,
60-deg rating
75-deg rating
75-deg rating .................:
3 #4/0, 1 G 1801175 75-deg rating ,:.,....,
4 250kcmii, '1 #4 G 2051,204 __75 -+deg rating
3 250kcmil, 1 i4: 2051200 75-deg rating
4 - 300Kcnnil, • 1 #2:G• 23011:225 75-deg rating
3 .- 3OOkcmil,11 ##2 G 23011225 75- deg.ratin
4- 35D[ccmiI. 1 #2 G.:.__ :2 012510 _._ __.. 75 -deg rating _,_.,..
3- 350kemiI, 1 #2 G 2501250 75-de ratio
4- 460kcmil, 1 #2 G. 2701250: 75-deg rating
27 3- 400kcmil, 1 #2 G. 270 P250, ::,._ 75-deg rating
30 4500km 2 10/30! 75-deg rating ._ .:
, t . G .: 3
30 3" 3- 500kcmil, 1 #2 G. 310 1300 75-deg rating
34N 3 1/2 4- 600kcmil, 1 #1 G 3401rn30} 75 -7" rating‘-----------
3- 60t}CcctTlil, 1 : #'1 G. 3401301: 75-deg rating
40N (2) 2 1/2 "' 4 25okcmil, 1 #1 G ,,,,411.0.t. 400 7-deg rating
40 (2) 2 1/2'' 3 250kcm11, Iii G 4101400! 75 -eg rating
45N' (2) 2 112' 4 - 300kcmil, 1#1.10 G, 4601450 75-cieg rating _...:.:..:,....
45 (2).:,2 1/2`" 3 - 30okcmil, .1 #1/0 G 4601450 75-deg rating
50N' (2) 3 4- 350kcmiI, 1 #110 G 5001500
SA (2) 2,1/2" 3-0 ul cmil, 1 #110 G. 500 1 515
75-deg rating
75-deg. rating
60N
:_.�. ... : :.. 2) 3��M,.. m �_4- 500kcmll, 1 #210 G,.� M, 620 / 600 ,..,...; � ,,, ,.75 -deg rating�� ..�.. ::,
60 (2) 3 ' ' . _ 3�5o0kcmil, 1 #2/0 G 620 / 600 75-deg rating
75N! 3) 3 "' 4- 3a0kcmiI, '1 #310 G 7501750 75-de ratio
75 (3) 2 112 3- 35okcmii, 1 ##3 /0 G 750/ 750. 75-deg rating
80N (3) 3'" ," 4- 400kcmii, 1 #3/0 G • 5'101 800 75-de ratin
80 (3) 2m1/2' m3' -4o0kc rlii, 1 #310 G. 8101804 75 -deg rating
90N (3)3" 4:- 500kcmil, 1 #4 /0G 9301 0 , 75-deg rating
90 (3) 3" 3- 500kkcmil, 1 10 G 9301900 75 -deg rating
100N (3) 2 1/2 "' 4- 600kcmil, 1 #1 /0 G i:.,,-.;,'.: 0 201 1000 w N w y yM 75 -deg rating
100 , rc. ir3) 3 "" 3'- 60okcmil, 1 #410 G • 10201 1000 75-deg rating
.,. 120N (4) 3 ", 500kcr il, 1 #250 ,G . 12401 1240 .tt ,_ ,_ _7 -deg rating m,.....::.
120 µn ,,. :() 3" .w 3- 5o0kcmil, 1 #250 G 12401 1200 75- deg „rating ,
150N (5) 3 4- 500kcmil, 1 #350 G 155011500 75 =deg rating •
150 (5) 3 ". 3=50okcmii, 1 #350 G 1550/1500 75 -deg rating
160N (6) 3" 4.400kcmii, 1 #350 G 1620/1600 75-deg rating
160 (6) 2 112" 3- 400kcrnil, 1 #350 . 102011.5P0'
75-deg rating...,_,.,,,,. ,:,,
200N (6) 2 1/2 4- 600kcmil, 1 #400 G.: 2040 /2000 75-deg rating
200 (6)::3" 3- 600kcmil, 1.#400:a 2040/2000 m., 75-deg rating
and
ie 5a for compac
N instil tai
Indicates acceptable overcurrent device rating for s ngle feeder. This rating shall)
not be used for sizing parallel feeders
Indicates overcurrent protective device rating that may be used for this feeder
The Contractor shall install feeder size indicated even:: if Code allows,.
smaller to be used ,
GRADE
UTILITY PRIMARY �- - --
PSE UTILITY
TRANSFORMER
T
XFMR
VAULT
EXTERIOR
-NEMA 3R
INTERIOR
NEMA 1
1
EXIST.
R1U -1
1
REVI E
EWEV ru;
COMPLIANCE WITH
NFPA70 -NEC
KT 1 2 2012
City of Tukwila
BUILDING DIVISION
GENERAL NOTES:
ALL CONDUCTORS ARE #12 AWG CU UNLESS NOTED OTHERWISE.
CONTRACTOR CAN MODIFY TO MC FEEDER WHERE APPROPRIATE.
2. RISER DIAGRAM IS NOT REPRESENTATIVE OF ACTUAL SWITCHBOARD LAYOUT.
CONTRACTOR TO CONFIRM EXISTING CONDITIONS PRIOR TO ANY
CONSTRUCTION FOR PHYSICAL LAYOUT WITH RESPECT TO ACTUAL
MANUFACTURED AND POTENTIAL INSTALLED CONDITIONS.
. EQUIPMENT SHOWN BOLD IS NEW.
ALL SWITCHBOARDS AND PANELBOARDS SUPPLIED BY A FEEDER SHALL BE
MARKED TO INDICATE THE DEVICE OR EQUIPMENT WHERE THE POWER
SUPPLY ORIGINATES PER NEC 408.4(B).
INTERIOR EXTERIOR
NEMA 1 NEMA 3R
r
1
1 75kVA
XFMR
1
1
1
PANEL
L1
200A
MCB
L�
/WA
vw
AREA OF WORK
EXPRESS
SHOP
\ 1
r
1-
1
<,d
P5 I
Q '
o.
MAIN DISTRIBUTION SWBD (MSB)
65,000 AIC
ONE -LINE RISER DIAGRAM
SCALE: NTS
1,
195 I
I
Q
Ts
c)
N
MAIN WATER PIP
ELECTRICAL
ROOM
WO Cu
EXOTHERMIC WELD OR
PROVIDE UFER GROUND: 20'
BARE COPPER CABLE IN
CONCRETE FOOTING SIZED AND
INSTALLED PER NEC 250 -81(c)
OTHER APPROVED METHOD BOND TO MAIN WATER PIPE.
EL\) Oc7
RECEIVED
CITY OF TUKWILA
OCT 102012
PERMIT CENTER
1--
w
2
w
0
0
0
w
J
w
PHONE (253) 872 -5553
7056 SOUTH 220TH STREET
FAX (253) 872 -4112
KENT, WA 98032
J
Q. <
J
0
=
rt
W
�Z
W
0
X
(/)
REV #
Q
co
< CO
CL 00
Ct
co
w
1- Q
z
w
U Q
=
O
co
DATE
DRAWN CM
CHECKED CM
DATE 10/10/2012
ONE -LINE RISER
DIAGRAM
E5.01