HomeMy WebLinkAboutPermit M12-019 - SAHALE SNACKSSAHALE SNACKS
3411 S 120 PL
M12 -019
City oftukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Inspection Request Line: 206 - 431 -2451
Web site: http: / /www.TukwilaWA.gov
MECHANICAL PERMIT
Parcel No.: 1023049069
Address: 3411 S 120 PL TUKW
Project Name: SAHALE SNACKS
Permit Number: M12 -019
Issue Date: 03/02/2012
Permit Expires On: 08/29/2012
Owner:
Name: SABEY CORPORATION
Address: 12201 TUKWILA INTL BLVD 4THFL , SEATTLE WA 98168
Contact Person:
Name: HEATH HAMBLEN
Address: 4102 B PL NW , AUBURN WA 98001
Email: HEATH @UNIVERSALREFRIG.COM
Contractor:
Name: UNIVERSAL REFRIGERATION INC
Address: PO BOX 614 , AUBURN WA 98071 -0614
Contractor License No: UNIVERI159RF
Phone: 253- 939 -5501
Phone: 253 939 -5501
Expiration Date: 04/01/2012
DESCRIPTION OF WORK:
INSTALL (3) GAS FURNACES WITH COOLING COILS, (3) ROOF MOUNTED AIR CONDITIONING
UNITS, AND DUCT WORK WITH GRILLES
Value of Mechanical: $33,107.00
Type of Fire Protection: UNKNOWN
Electrical Service Provided by:
Permit Center Authorized Signature:
Fees Collected: $600.06
International Mechanical Code Edition: 2009
Date:
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign and obtain this mechanical permit and agree to the conditions on the
back of this permit.
Signature.
Print Name: tr ` ^ (f ("jam h
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
Date: Z Zo /C._
doc: IMC -4/10
M12-019
Printed: 03 -02 -2012
• •
PERMIT CONDITIONS
Permit No. M12-019
1: ** *BUILDING DEPARTMENT CONDITIONS * **
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431- 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
6: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap the sanitary
sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks, wells, and other
excavations. Final inspection approval will be determined by the building inspector based on satisfactory completion of
this requirement.
7: Manufacturers installation instructions shall be available on the job site at the time of inspection.
8: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the City of Tukwila
Building Department (206- 431 - 3670).
9: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431- 3670).
10: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
11: ** *FIRE DEPARTMENT CONDITIONS * **
12: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
13: H.V.A.C. units rated at greater than 2,000 cfm require auto - shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2051)
14: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air- moving equipment upon detection of smoke in the main return -air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall be installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
15: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2051)
16: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2051)
17: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2051)
18: All new fire alarm systems or modifications to existing systems shall have the written approval of The Tukwila Fire
Prevention Bureau. No work shall commence until a fire department permit has been obtained. (City Ordinance #2051) (IFC
104.2)
19: An electrical permit from the City of Tukwila Building Department Permit Center (206- 431 -3670) is required for this
project.
doc: IMC -4/10
M12 -019 Printed: 03 -02 -2012
20: Contact The Tukwila Fire Prev n Bureau to witness all required inspections tests. (City Ordinances #2050 and
#2051)
21: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
22: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575 -4407.
doc: IMC -4/10
M12 -019 Printed: 03 -02 -2012
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Mechanical Permit No.
t/t() —ore/
Project No.
Date Application Accepted: -` 3
Date Application Expires: 8— 6— 119—■
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *please print **
SITE LOCATION
Site Address:
Tenant Name:
51// S, l2i ij /7c
�aGla le— jh.ac.k5
PROPERTY OWNER
Name: % c 4 v%
Address: 4102 B Plc NW
Address: / 2 Z O/ / tw iYq 417%. Z'tiii 4t
City: *I.{ee..., State: h44. Zip:ge f6
CONTACT PERSON — person receiving all project
communication
,�/
Name: %/�, l vl L/R4N b /eiii
Address: 4102 B Plc NW
Address: 4102 B Plc NW
Phone: (253) 939 -5501 Fax: (253) 735 -3432
City: Auburn State: WA
Zip: 98001
Phone: (253) 939 -5501 Fax:
Email: theta universalrefrig.com
King Co Assessor's Tax No.: 70 Z-'jO'/' 906R
Suite Number: 700 Floor:
New Tenant: ❑ Yes ❑..No
MECHANICAL CONTRACTOR INFORMATION
Company Name: Universal Refrigeration
Address: 4102 B Plc NW
City: Auburn State: WA Zip: 98001
Phone: (253) 939 -5501 Fax: (253) 735 -3432
Contr Reg No.: UNIVERI159RF Exp Date: 04/01 /2012
Tukwila Business License No.: l us - 099,3/2 y
Valuation of project (contractor's bid price): $
Describe the scope of work in detail:
1014 () u(►
0 old t / oft (.6
Use: Residential: New ❑
Commercial: New
Fuel Type: Electric ❑
A /07 M. (eiudes as / /
/o w Vo ffat cue S .
edollnq 0,0I15/ (5) - vu6uvI4 i
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Furnace >100k btu
Floor furnace
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cooling
system
3
Air handling unit
<10,000 cfin
Unit Type
Qty
Air handling unit
>10,000 cfim
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system
Hood and duct
3
Incinerator — domestic
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
Thermostat
Wood /gas stove
Emergency generator
Other mechanical
equipment A , c..
3
NN if
Boiler /Compressor
Qty
0 -3 hp /100,000 btu
3 -15 hp /500,000 btu
15 -30 hp /1,000,000 btu
30 -50 hp /1,750,000 btu
50+ hp /1,750,000 btu
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDI 1 WNER OR • THORIZE P - EN
Signatur //
Print Name: Gl%!�5 e4 O`l
Mailing Address: 4102 B Plc NW
Date: 2— S -
Day Telephone: (253) 939 -5501
Auburn WA 98001
H:Wpplications\Forms- Applications On Line\2011 Applications \Mechanical Pernut Application Revised 8- 9- 11.docx
Revised: August 2011
bh
City State Zip
Page 2 of 2
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206-431-3665
Web site: http: / /www.TukwilaWA.2,ov
RECEIPT
Parcel No.: 1023049069 Permit Number: M12 -019
Address: 3411 S 120 PL TUKW Status: APPROVED
Suite No: Applied Date: 02/08/2012
Applicant: SAHALE SNACKS Issue Date:
Receipt No.: R12 -00886
Initials:
User ID:
WER
1655
Payment Amount: $366.93
Payment Date: 03/02/2012 11:38 AM
Balance: $0.00
Payee: UNIVERSAL REFRIGERATION
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 44072 366.93
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
MECHANICAL - NONRES
PLAN CHECK - NONRES
000.322.102.00.00 293.55
000.345.830 73.38
Total: $366.93
doc: Receiot -06 Printed: 03 -02 -2012
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206-431-3665
Web site: http: / /www.TukwilaWA.gov
Parcel No.: 1023049069
Address: 3411 S 120 PL TUKW
Suite No:
Applicant: SAHALE SNACKS
RECEIPT
Permit Number: M12 -019
Status: PENDING
Applied Date: 02/08/2012
Issue Date:
Receipt No.: R12 -00560
Initials:
User ID:
WER
1655
Payment Amount: $233.13
Payment Date: 02/08/2012 03:24 PM
Balance: $0.00
Payee: UNIVERSAL REFRIGERATION
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 43979 233.13
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
MECHANICAL - NONRES
PLAN CHECK - NONRES
000.322.102.00.00 186.50
000.345.830 46.63
Total: $233.13
doc: Receiot -06 Printed: 02 -08 -2012
INSPECTION NO
CITY'OF:TUKWILA BUILDING DIVISION
6300 Southcenter.Blvd., #100, Tukwila. WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
X11
.I■SPECTION RECORD
Retain a copy with permit
/7?/2- 7/S
PERMIT NO.
Project:, .
..c' r7, -ifltc ,`..5.%1 /Icl k S
Type of Inspection:
F7 n/ 71 t'
Address:
?4)iii s g)-'6? P4,__
Date Called:
Special Instructions:
g/9 $41 _
/?A/t/. �t 5s'-2‘4- y�
Date W nted:.
4.7— 23 - /2
(a{rn`
pow.
Requester:
Phone No:
U 4---57 6 — /4/7
3
Approved per applicable codes. Corrections required prior to approval. a
COMMENTS o s--/ 7 /9 ",20 /..01/e'v
?'/ '11;7'/ .' j,./J/Fi /ice'AJr1
Date:
423 --1?
n R IN PECTION. FEE REQUIjED. Prior to next inspection, fee must be
p id t 6300•Southcenter 13l d.. Suite 100. Call to schedule reinspection.
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451 z
Project:
SE, 14 P■k,
S t4 4\Ca.S
Type of Inspection:
1 OMG 1 \ — _l 0
(Za`k,(vyJ A:r_
Address:
341 j, c
1 20 P f
Date Called:
®-
Special Instructions:
Date Wanted:.
3 — 3 0- IZ
a.m.
p.m.
Requester:
Phone No: J
2O( -�5I0— !x-173
DApproved per applicable codes. El Corrections required prior to approval.
COMMENTS:
CO P c3",t-c k - — AD 4 ✓IVeS — ALA,
A v vws%J e ck -4 it v+.! 4 c> Al..,(-1 R "`^ b1 : i 4
(Za`k,(vyJ A:r_
-
Date:
—
INSPECTION FEE REQUIRED. Prior t next inspection, fee must be
aid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
Ma-01
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
Projech
�.. - (I SkP -mss
Type-of of Inspection:
(.3C, t{--
t,(
Address:
q a ! Z-o -,'.-
Date Called:
j -
Special Instructions:
v 1 ? �6(
Date Wanted:.
—� -r
( .m;
P.m.
Reque t�„et CIA(
6 1IJ\-t "
Phone o: ,
°s 10 ^1473
Co .-
0 Approved per applicable codes. E Corrections required prior to approval.
COMMENTS: le ,9-
f.//140 Li D n/S?ec 47,
j -
p...vve tB
o? f 7k % 0 ..1 )✓S ?(e 4 r
_4)2/(77
6 1IJ\-t "
2
Inspect
Date:
TVSPECTION FEE REQUIRE Prior to n xt inspection. fee must be
g id at 6300 Southcenter Blvd.. uite 100. all to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMFY■0.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcerter Blvd., #100, Tukwila. WA 98188 tz. (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
Project:
Type of Inspection:
1,
Address:
Ii
`t t
7,0 PL
Date Called:
Special Instr ctions:
Date Wanted
F I 1 T ' mm
p.m.
Requester: -
Phone � -- _g o
.- /4 7 3
Approved per applicable codes. E Corrections required prior to approval.
COMMENTS:
1-4rk
Ont
i
Inspbcto
Date: ? t' --0
r REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
1
1
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
tailgaracaloaa
.i. 7i 5
!'lii t
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
444 Andover Park East, Tukwila, Wa. 98188 206- 575 -4407
Project:
Si't, i
€.ip..,v (c c
Fire Alarm:-.
Hood & Duct:
Type of Inspection:
' 1I ( r 1ec. rte -i‘ C`v1.1 -,rk NM c,'-)
Address: y i i
Suite #:
- / a-
- ±-
%j
Contact Person:
'
Special Instructions:
Phone No.:
;Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers:
Fire Alarm:-.
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
(.). r
`‘'.i. : 4- PAL
•>
0 l l
' j r 3 n )3
FJ sr
!J,..J -N . r;e r --1
V.
°' `i
c , .- -
e. c.-.1 t b ;M' IL d ic , t. y
.i. 5 r
- t1,.i I j t
Needs Shift Inspection:
Sprinklers:
Fire Alarm:-.
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type:
Ins ector:
r,
�- �.�
Date:
t !I
f i
Hrs.:
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word /Inspection Record Form.Doc
6/11/10
T.F.D. Form F.P. 113
MN ASSOCIATED AIR BALANCE CO(JNCIL
r Date: 4/19/12
� Page: 1 of 1
Project Name: SAHALE SNACKS
System: GF -1.2.3
AIR DISTRIBUTION DATA
TERMINAL
NUMBER
I ROOM
NUMBER
TERMINAL
DESIGN
TEST (FPM OR CFM)
FINAL
TYPE
I SIZE
FACTOR
FPM
I CFM
TEST 1
I TEST 2
I TEST 3
FPM
I CFM
GF -1
1
-
CD
10x10
-
-
225
275
250
230
-
230
2
-
CD
10x10
-
-
225
270
245
230
-
230
3
-
CD
10x10
-
-
225
180
205
220
-
220
4
-
CD
8x8
-
-
175
220
195
180
-
180
5
-
CD
10x10
-
-
325
375
350
335
-
335
6
-
CD
8x8
-
-
200
140
160
190
-
190
7
-
CD
10x10
-
-
325
265
300
320
-
320
8
-
CD
8x8
-
_ -
200
145
175
190
-
190
GF -2
1
-
CD
8x8
-
-
150
100
130
140
-
140
2
-
CD
8x8
-
-
150
105
135
145
-
145
3
-
CD
8x8
-
-
200
245
220
205
-
205
4
-
CD
10x10
-
-
325
280
300
320
-
320
5
-
CD
10x10
-
-
325
260
285
315
-
315
6
-
CD
i
10x10
-
-
325
370
345
335
-
335
7
-
CD
10x10
-
-
325
375
350
335
-
335
8
-
CD
8x8 _
- _
-
200
250
235
205
-
205
GF -3
1
-
CD
10x10
-
-
250
300
275
260
-
260
2
-
CD
10x10
-
-
250
295
265
255
-
255
3
-
CD
10x10
-
-
250
290
275
260
-
260
4
-
CD
10x10
-
-
250
200
220
240
-
240
5
-
CD
10x10
-
-
250
205
225
240
-
240
6
-
CD
10x10
-
-
250
205
220
245
-
245
7
-
CD
10x10
-
-
250
305
270
255
-
255
8
-
CD
10x10
-
-
250
310
270
255
-
255
Remarks:
58STA /STX
4 —WAY MULTIPOISE INDUCED — COMBUSTION
GAS FURNACE
Input Capacities: 45,000 thru 155,000 Btuh
Series 140
FELE c PY
Product Data
A10247
REVIEWED FOR
CODE COMPLIANCE
APPROVED
turn to the experts
THE CARRIER 58STA/STX GAS FURNACE
The 58STA/STX 4 -way Multipoise Gas Furnaces feature Carrier's
QuieTech'" noise reduction system for incredibly quiet induced
draft operation. Applications are easy with 4 -way multipoise
design, through- the - furnace downflow venting, 13 different
venting options, and designed for easy service access. An inner
blower door is provided for tighter sealing in sensitive applications.
The 58STA/STX fumaces are approved for use with natural or
propane gas, and the 58STX is approved for use in Low NOx Air
Management Districts.
STANDARD FEATURES
• QuieTech°' noise reduction system
• Microprocessor based control center
Enhanced diagnostics with LED and reflective sight glass.
Stores fault codes during power outages.
Adjustable heating air temperature rise
Adjustable cooling airflow
• 4 -way Multipoise furnace, 13 vent applications
• Compact design - only 33 -1/3 in. (847 mm) tall
• Power Heat' Igniter
• Draft safeguard switch to ensure proper furnace
venting
• Inner door for tighter sealing
• Certified to leak 2 percent or less of its nominal air
conditioning CFM delivered when pressurized to 1 -In.
Water Gauge with all present air inlets, air outlets, and
condensate drain port(s) sealed.
• HYBRID HEAT® Dual Fuel System compatible
• All models are chimney friendly when used with
accessory vent kit
• Twinning in Upflow, Downflow and Horizontal
• Residential installations eligible for consumer
financing through the Retail Credit Program
FEB 2 9 2012 RECEIVED
FEB 08 2012
City of Tukwila
PERMIT
BUILDING DIVISION
.8 TA/ T
MODEL NUMBER NOMENCLATURE
58STA 045 100 08
58STA 4 -Way Multfpoise
58STX Low NOx version
Input Capacity
045 - 44,000 Btuh 110 - 110,000 Btuh
070 - 66,000 Btuh , :.135 - 132,000 Btuh
090 - 88,000 Btuh 155 - 154,000 Btuh
Nominal Cooling Size
(Airflow at .5 e.s.p.)
(400 CFM per 12,000 Btuh)
08 -800 CFM
12 -1200 CFM
100 14 -1400 CFM
110 16 -1600 CFM
120 20 -2000 CFM.
130 22 -2200 CFM
140
Series Number
SEE NOTES 1,2,4,5,7,8,9
HORIZONTAL RIGHT
A02068
O
SEE NOTES 1,2,4,7,8,9
HORIZONTAL RIGHT
A02069
SEE NOTES 1,2,4,7,8,9
HORIZONTAL LEFT
A02064
SEE NOTES 1,2,4,5,7,8,9
HORIZONTAL LEFT
A02066
9
SEE NOTES 1,2,4,5,7,8,9
HORIZONTAL RIGHT
A02070
1f
O
SEE NOTES 1,2,4,5,7,8,9
HORIZONTAL LEFT
A02065
SEE NOTES 1,2,4,5,7,8,9
HORIZONTAL LEFT
A02067
PHYSICAL DATA
UNIT SIZE
090
110
135
156
20
12
18
22
10
22
20
OUTPUT CAPACITY BTUH*
(Nonweatherized ICS) t
58STX Upflow; all 68STA
71,000
89,000
89,000
89,000
107,000
107,000
125,000
58STX Downflow/Horizontal
68,000
85,000
85,000
85,000
102,000
102,000
119,000
INPUT BTUH*
58STX Upflow; all 58STA
88,000
110,000
110,000
110,000
132,000
132,000
154,000
58STX Downflow /Horizontal
84,000
105,000
105,000
105,000
126,000
126,000
147,000
AFUE %* Nonweatherlzed ICS
80.0
80.0
80.0
80.0
80.0
80.0
80.0
SHIPPING WEIGHT - LB. (KG)
146 (66)
135 (61)
146 (66)
152 (69)
149 (68)
163 (74)
170 (77)
CERTIFIED TEMP RISE RANGE - °F (°C)
25 -55
(14 -30)
50 -80
(28 -44)
40 -70
(22 -39)
30 -60
(17 -33)
50 -80
(28 -44)
40 -70
(22 -39)
45 -75
(25 -41)
CERTIFIED EXT Heating
STATIC PRESSURE
0.15
0.20
0.20
0.20
0.20
0.20
0.20
Cooling
0.50
0.50
0.50
0.50
0.50
0.50
0.50
Heating
AIRFLOW CFM#
1990
1335
1515
1900
1525
1850
1790
Cooling
2025
1355
1680
2220
1710
2110
2230
LIMIT CONTROL
SPST
HEATING BLOWER CONTROL
Solid -State Time Operation
BURNERS (Monoport)
4
5
5
5
6
6 1
7
GAS CONNECTION SIZE
1 /2 -in. NPT
GAS VALVE (Redundant) Manufacturer
White- Rodgers
Minimum Inlet Pressure (In. W.C.)
4.5 (Natural Gas)
Maximum Inlet Pressure (In. W.C.)
13.6 (Natural Gas)
IGNITION DEVICE
* G
Hot Surface
as input ratings are certrfied for elevations to 2000 ft. (610 M). in U.S., for elevations above 2000 ft. (610 M), reduce ratings 4 percent for each 1000 ft. (305
M) above sea level. Refer to National Fuel Gas Code NFPA 54 /ANSI 2223.1 -2009 F.4 or furnace Installation Instructions.
t Capacity in accordance with U.S. Government DOE test procedures.
# Airflow shown is for bottom only return -air supply. For air delivery above 1800 CFM, see Air Delivery Table for other options. A filter is required for each
return -air supply. An airflow reduction of up to 7 percent may occur when using a Carrier 4 -5/16 in. (110 mm) high efficiency media fitter.
ICS - Isolated Combustion System
BLOWER PERFORMANCE DATA
7
58STAr'STX
090
110
155
165
UNITS1Z
20
12
1f}
, 18
22 .
2p
DIRECT -DRIVE MOTOR Hp (PSC)
3/4
1/3
1/2
3/4
1/2
3/4
3/4
MOTOR FULL LOAD AMPS
11.1
5.2
7.9
11.1
7.9
11.1
11.1
RPM (Nominal)- Speeds
1075 -3
1075 -3
1075 -3
1075 -3
1075 -3
1075 -3
1075 -3
BLOWER WHEEL DIAMETER X WIDTHS - IN. (mm)
11 x 11
(279 x 279)
10 x 8
(254 x 203)
10x 10
(254 x 254)
11 x 11
(279 x 279)
10x 10
(254 x 254)
11 x 11
(279 x 279)
11 x 11
(279 x 279)
7
58STAr'STX
DIMENSIONS
A10270
NOTES:
1. Two additional 7 /8 —in. (22 mm) diameter holes are located in the top plate.
2. Minimum return —air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters.
a. For 800 CFM- 16 —in. (406 mm) round or 14 1/2 x 12 —in. (368 x 305 mm) rectangle.
b. For 1200 CFM- 20 —in. (508 mm) round or 14 1/2 x 19 1 /2 —in. (368 x 495 mm) rectangle.
c. For 1600 CFM- 22 —in. (559 mm) round or 14 1/2 x 22 1/16 —in. (368 x 580mm) rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets,
a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
FURNwk�
.
Y
045 -08
14 -3/16 (360)
12 -9/16
(319)
9 -5/16
(237)
12 -11/16
(322)
4 (102)
104
(47)
045 -12
14 -3/16 (360)
12 -9/16
(319)
9 -5/16
(237)
12 -11/16
(322)
4 (102)
107
(49)
070 -08
14 -3/16 (360)
12 -9/16
(319)
9 -5/16
(237)
12 -11/16
(322)
4 (102)
111
(50)
070 -12
14 -3/16 (360)
12 -9/16
(319)
9 -5/16
(237)
12 -11/16
(322)
4 (102)
115
(52)
070 -16
17 -1/2 (445)
15 -7/8
(403)
11 -9/16
(294)
16 -1/8
(410)
4 (102)
126
(57)
090 -14
17 -1/2 (445)
15 -7/8
(403)
11 -9/16
(294)
16 -1/8
(410)
4 (102)
127
(58)
090 -16
21 (533)
19 -3/8
(492)
13 -5/16
(338)
19 -1/2
(495)
4 (102)
140
(64)
090 -20
21 (533)
19 -3/8
(492)
13 -5/16
(338)
19 -1/2
(495)
4 (102)
146
(66)
110 -12
17 -1/2 (445)
15 -7/8
(403)
11 -9/16
(294)
16 -1/8
(410)
4 (102)
135
(61)
110 -16
21 (533)
19 -3/8
(492)
13 -5/16
(338)
19 -1/2
(495)
4 (102)
146
(66)
110 -22
21 (533)
19 -3/8
(492)
13 -5/16
(338)
19 -1/2
(495)
4 (102)
152
(69)
135 -16
21 (533)
19 -3/8
(492)
13 -5/16
(338)
19 -1/2
(495)
4 (102)*
149
(68)
135 -22
24 -1/2 (622)
22 -7/8
(581)
15 -1/16
(383)
23 (584)
4 (102)*
163
(74)
155 -20
24 -1/2 (622)
22 -7/8
(581)
15 -1/16
(383)
23 (584)
4 (102)*
170
(77)
*135 and 155 size furnaces require a 5 or 6 —in (127 or 152 mm) vent.
complete installation requirements.
Use a vent adapter between furnace and vent stack. See Installation Instructions for
11
TYPICAL WIRING SCHEMATIC
BLK
w
FIVE
WIRE
BLOWER THREE -WIRE
DOOR HEATING -
SWITCH 1 ONLY
NOTE 2
- - -- FIELD 24 -V WIRING
- - -- FIELD 115 -, 208/230 -, 460 -V WIRING
- FACTORY 24 -V WIRING
- FACTORY 115 -V WIRING
THERMOSTAT
TERMINALS
FIELD - SUPPLIED
DISCONNECT
208/230- OR
460 -V
-- THREE
PHASE
115 -V
FIELD - SUPPLIED
DISCONNECT
AUXILIARY
J -BOX
CONTROL
BOX
24 -V
TERMINAL
BLOCK
FURNACE
ELECTRICAL DATA
NOTE 1
CONDENSING
UNIT
TWO
WIRE
- GND
-1 208/230 -V
=1 SINGLE
1 PHASE
NOTES: 1. Connect Y terminal as shown for proper operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
A02186
58STA/STX
UNIT SIZE
VOLTS HERTZ
PHASE
OPERATING
VOLTAGE RANGE
MAXIMUM
UNIT AMPS
MAXIMUM
WIRE
LENGTH
FT (M)*
MAXIMUM
FUSE OR CKT
BKR AMPSt
MINIMUM
WIRE GAGE
Maximum*
Minimum*
045-08
115 -60 -1
127
104
5.4
49 (14.9)
15
14
045-12
115 -60-1
127
104
7.0
39 (11.8)
15
14
070-08
115 -60-1
127
104
5.0
52 (15.8)
15
14
070-12
115 -60 -1
127
104
6.8
40 (12.1)
15
14
070-16
115 -60-1
127
104
9.5
29 (8.8)
15
14
090-14
115 -60-1
127
104
8.2
34 (10.3)
15
14
090 -16
115 -60-1
127
104
10.0
28 (8.5)
15
14
090-20
115 -60-1
127
104
13.6
32 (9.7)
20
12
110 -12
115 -60 -1
127
104
8.2
34 (10.3)
15
14
110-16
115 -60-1
127
104
10.1
28 (8.5)
15
14
110 -22
115 -60-1
127
104
14.8
30 (9.1)
20
12
135 -16
115 -60 -1
127
104
10.2
27 (8.2)
15
14
135 -22
115 -60-1
127
104
14.4
30 (9.1)
20
12 40
155 -20
115 -60-1
127
104
15.0
29 (8.8)
20
12
* Permissible limits of the voltage range at which unit operates satisfactorily.
t Time -delay type is recommended.
$ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
13
4:-MiE3INIO
qF- /, 2., .5
Project: -Untitledl2
Prepared By:
Performance Summary For AC
02/07/2012
01:22PM
System: 24ABBICNPH .
System Quantity 3
Altitude* 0.0 ft
Fumace Type: Carrier Non ECM Furnace
Linear Pipe Length* 0.0 ft
Actual SEER* 13.0
EER ARI Conditions 11.0
Outdoor Unit Parameters
Unit Quantity______ ....
Unit Model* _24ABB360A006
Unit Size (Nominal) :________5 Tons High Efficiency
Voltage: 460-3-60
CIg Ent Air DB Ambient: 95.0
V-Ph-Hz
°F
Outdoor Electrical Data
Unit Voltage' 460-3-60 V-Ph-Hz
Fan Motor FLAB 0.70 Amps
MCA: 10.5 Amps
Max Fuse* 15 Mips
Operating Range Min:___ V
Operating Range .... ____.....506 V
Compressor RL.A. 7.8 Amps
Compressor LRA. 52.0 Amps
Min Wire Size @ 60C..
Min Wire Size @ 75C* 14
Max Length Wire Size @ 60C: 173 ft
Max Length Wire Size @ 75C:. 165 ft
Acoustics
Sound Power Levels, db re 10E-12 Watts
2-1>
Indoor Unit Parameters
Unit Quant 1
Unit ModeI. CNPHP6024ACA
Unit Size (Nominal): _5 Tons Size 60
Actual Airflow* _2000.0 CFM
Standard Airflow:. 2000.0 CFM
Total Net CIg Capacity: 57.69 MBH
Net Sensible CIg Capacity:_ _42.93 MBH
Ent Air DB* _80.00 °F
Ent Air WIFI. 67.00 °F
Ent Enthalpy:_ _31.44 BTU/lb
Lvg Air DB: 60.13 °F
Lvg Air VVB: _______ ____58.00 °F
Lvg Enthalpy: _25.03 BTU/lb
Indoor Unit Extemal Static: .0.50 in wg
Total System Power._ 5.34 kW
ooftt, ott(
Residential Carrier Products Bldr 1.19d
Page 5 of 13
Outdoor Unit (dB)
Indoor Unit (dB)
'DBA Level
,, 78.0
NA
63Hz
NA
NA
125Hz
59.0
NA
250Hz
67.5
NA
500Hz
71.5
NA
1000Hz
73.5
NA
2000Hz
69.0
NA
4000Hz
66.0
NA
8000Hz
63.5
NA
Sound Message
No Indoor sound
data available.
Residential Carrier Products Bldr 1.19d
Page 5 of 13
INSTALLATION
INSTRUCTIONS
ECONOMIZER FOR
FURNACES UP TO 2,000 CFM
PART NUMBER:
MB- BP- FURN -5TON
Please read instructions thoroughly before beginning.
1.> Mount or secure furnace into place.
2.) Attach mixing box to the return end of the
furnace with sheet metal screws provided.
NOTE: Screw length should be short enough so
damage or blockage to the filter racks,
coils, heat exchangers, and wiring does
not occur.
3.) Attach return air duct and outside air duct to
the other side of the mixing box as shown with
screws provided.
4.) If energy management control system is used,
wire system per wiring instuctions provided.
THIS DOCUMENT IS THE PROPERTY OF MICROMETL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MICROMETL S WRTITEN CONSENT.
MANUFACTUER RESERVES THE RIGHT TO DISCONTINUE, OR CHANGE AT ANYTIME, SPECIFICATIONS & DESIGNS WITHOUT ANY NOTICE AND WITHOUT INCA/RING OBLIGATIONS. COPYRIGHT MICROMETL CORPORATION 1999. ALL RIGHTS RESERVED
24ABB3
Base n's 13 Air Conditioner
with Puron® Refrigerant
Product Data
Puron -
Carrier's Air Conditioners with Puron® refrigerant provide a
collection of features unmatched by any other family of
equipment. The 24ABB has been designed utilizing Carrier's
Puron refrigerant. The environmentally sound refrigerant allows
you to make a responsible decision in the protection of the earth's
ozone layer.
As an Energy Stare Partner, Carrier Corporation has determined
that this product meets the Energy Star® guidelines for energy
efficiency. Refer to the combination ratings in the Product Data
for system combinations that meet Energy Stare guidelines.
NOTE: Ratings contained in this document are subject to
change at any time. Always refer to the AHRI directory
(www.ahridirectory.org) for the most up -to -date ratings
information.
eic —6 2_ et-
Carrie
Turn to the Experts.
INDUSTRY LEADING
FEATURES / BENEFITS
Efficiency
• 13.0 - 13.2 SEER/10.8- 11.0 EER (based on tested
combinations)
• Microtube Technology " refrigeration system
• Indoor air quality accessories available
Sound
• Sound level as low as 75 dBA
• Sound level as low as 74 dBA with accessory sound
blanket
Comfort
• System supports Edge® Thermidistat" or standard
thermostat controls
Reliability
• Puron® refrigerant - environmentally sound, won't
deplete the ozone layer and low lifetime servce cost.
• Scroll compressor
• Internal pressure relief valve
• Internal thermal overload
• Filter drier
• Balanced refrigeration system for maximum reliability
Durability
WeatherArmor" protection package:
• Solid, durable sheet metal construction
• Dense wire coil guard available
(3 -phase units come standard with dense wire coil
guard)
• Baked -on, complete outer coverage, powder paint
Applications
• Long -line - up to 250 feet (76.20 m) total equivalent
length, up to 200 feet (60.96 m) condenser above
evaporator, or up to 80 ft. (24.38 m) evaporator above
condenser (See Longline Guide for more information.)
• Low ambient (down to - 20 °F /- 28.9 °C)) with
accessory kit
MODEL NUMBER NOMENCLATURE
1 2 3 4 5 8 7 8 9 10 11 12 13
N N A A A/N N N N NN A/N A N N N
2 4 A B B 3 3 8 A 0 0 3 0
Product Product Tier Major SEER Cooling Variations Open Open Voltage Series
Series Family Series Capacity
3= 208/230 -1 0 =
24 =AC A =RES AC B =Base B =Puron 3 =13 SEER 1.000 Btuh A =Dense Grille 0 =Not 0 =Not 5= 208/230 -3 Original
(nominal) W =Wide Grille Defined Defined 8 =480/3 Belles
1 = 575/3
Puron.
d».mAronnwMOIIy.amd r.hp.rsrd
ARI Stnndud 2101200
Unitary Air Conditioners
ISO 9001:2000
c
AWE
Uttk
COMPLIANT
STANDARD FEATURES
us
ENERGY STAR
This product has been designed end manufactured to
meet Energy Start criteria for energy efficiency when
matched with appropriate coil components. However,
proper refdgerent charge and proper air flow are critical
to achieve rated capacity and efficiency. Installation of
this product should follow all manufacturing refrigerant
charging and air flow instructions. Failure to confirm
proper 00.rge and air Sow may reduce energy
efficiency end shorten equipment 0r..
Feature
18
24
30
36
42
48
60
Puron Refrigerant
X
X
X
X
X
X
X
Maximum SEER
14.50
14.25
15.0
14.0
14.0
14.0
13.5
Scroll Compressor
X
X
X
X
X
X
X
Field Installed Filter Drier
X
X
X
X
X
X
X
Front Seating Service Valves
X
X
X
X
X
X
X
Internal Pressure Relief Valve
X
X
X
X
X
X
X
Internal Thermal Overload
X
X
X
X
X
X
X
Long Line capability
X
X
X
X
X
X
X
Low Ambient capability with Kit
X
X
X
X
X
X
X
Dense Grille (standard on 3 —Phase only)
X
X
X
X
X
X = Standard
2
PHYSICAL DATA
UNIT SIZE SERIES
18 -31
24 -31
30- 31,61
38- 31,61,81
42- 30,60,60
48- 31,61,61,11
di-32
60- 62,62,12
Operating Weight Ib (kg)
107
(48.5)
110
(50.0)
111
(50.3)
141
(84.0)
190
(88.2)
188
(84.4)
190
(88.2)
215
(97.5)
Shipping Weigh Ib (kg)
130
(60.0)
134
(60.8)
136
(61.7)
170
(77.1)
218
(98.9)
224
(101.6)
226
(102.5)
250
(113.4)
Compressor type
Scroll
REFRIGERANT
Purone (R -410A)
Control
TXV (Purone Hard Shutoff)
Charge Ib (kg)
3.50
(1.6)
3.80
(1.7)
4.10
(1.9)
5.34
(2.4)
5.84
(2.7)
7.00
(3.2)
8.19
(3.7)
8.00
(3.6)
COND FAN
Propeller Type, Direct Drive
Air Discharge
Vertical
Air City (CFM)
1792
2218
2218
2954
3167
3385
3365
3365
Motor HP
1/12
1/10
1/10
1/4
1/5
1/4
1/4
1/4
Motor RPM
1100
1100
1100
1100
1100
1100
800
1100
COND COIL
Face Area (Sq ft)
8.40
8.40
9.80
13.13
17.25
19.40
12.93
15.09
Fins per In.
20
25
25
25
25
25
20
20
Rows
1
1
1
1
1
1
2
2
Circuits
3
3
3
3
4
5
5
6
VALVE CONNECT. (In. ID)
Vapor
3/4
3/4
3/4
7/8
7/8
7/8
7/8
7/8
Liquid
3/8
3/8
3/8
3/8
3/8
3/8
3/8!
3/8
REFRIGERANT TUBES* (In. OD)
Rated Vapor*
3/4
7/8
1 -1/8
Max Liquid Linet
3/8
* Units are rated with 25 ft (7.6 m) of ineset length. See Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset
Note: See unit Installation Instruction for proper installation.
t See Liquid Line Sizing For Cooling Only Systems with Puron Rehigerant tables.
3
ELECTRICAL DATA
UNIT SIZE-
VOLTAGE,
SERIES
V/PH
OPER VOLTS*
COMPR
FAN
MCA
MIN
WIRE
SIZEt
MIN
WIRE
SIZEt
MAX
LENGTH
it. (m)#
MAX
LENGTH
E. (m)#
MAX
FUSE**
or CKT
BRK
AMPS
MAX
MIN
LRA
RLA
FLA
60° C
76' C
60° C
75° C
18 -31
208/230/1
253
197
48.0
9.0
0.5
11.8
14
14
67 (20.4)
63 (19.2)
20
24 -31
58.3
13.5
0.77
17.6
14
14
45 (13.7)
43 (13.1)
25
30 -31
64.0
12.8
0.77
16.8
14
14
47 (14.3)
45 (13.7)
25
38 -31
77.0
15.3
1.4
21.5
12
12
58 (17.7)
55 (16.8)
30
42 -30
112.0
17.9
1.1
23.5
12
12
53 (162)
51 (15.5)
40
48 -31
109.0
19.9
1.4
26.2
10
10
76 (232)
73 (22.3)
40
60 -32
134.0
26.4
12
34.2
8
10
91 (27.7)
56 (17.1)
50
30 -61
208/230 -3
253
197
58.0
8.3
0.77
11.2
14
14
81 (24.7)
77 (23.5)
20
38 -51
71.0
10.5
1.4
14.5
14
14
63 (19.2)
60 (18.3)
20
42-60
88.0
13.5
1.1
18.0
14
14
51 (15.5)
48 (14.6)
30
48 -61
83.1
13.1
1.4
17.8
10
10
130 (39.6)
123 (37.5)
30
60 -62
110.0
16.0
1.4
21.4
12
12
67 (20.4)
64 (16.5)
30
38 -61
460 -3
506
414
38.0
5.6
0.7
7.7
14
14
236 (71.9)
225 (68.5)
15
42 -60
44.0
6.0
0.6
8.1
14
14
225 (68.5)
214 (65.2)
15
48 -81
41.0
6.1 _
0.7
8.3
14
14.
219 (68.8)
208 (63.4)
15
�80 -62.
52.0
7.83
0.7
10:5
14
14
173 (52.7)
165 (50:3)_,
15
38 -11
575 -3
532
518
36.5
3.8
0.5
5.3
14
14
343 (104.5)
326 (99.4)
15
48 -11
33.0
4.4
0.5
6.0
14
14
303 (92.4)
288 (87.8)
15
60 -12
38.9
5.7
0.5
7.6
14
14
239 (72.8)
228 (69.5)
15
* Permissible imits of the voltage range at which the unit will operate satisfactorily
t tf wire is applied at ambient greater than 30 °C , consult table 310 -16 of the NEC (NFPA 70). The ampacity of non - metallic- sheathed cable (NM), trade
name ROMEX, shall be that of 60 °C conditions, per the NEC (NFPA 70) Article 336 -26. If other than uncoated (no- plated), 60 or 75 °C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
# Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
°° Time -Delay fuse.
FLA - Full Load Amps
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
RLA - Rated Load Amps
NOTE: Control circuit is 24 -V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors /compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1
A- WEIGHTED SOUND POWER LEVEL
UNIT SIZE
STANDARD
RATING
dBA
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
126
260
600
1000
2000
4000
8000
18 -31
72
53.5
59.5
63.5
67.0
63.5
59.0
52.5
24 -31
76
55.0
61.5
67.0
71.5
69.0
61.0
55.0
30 -31, 51
74
55.0
63.5
68.5
68.5
65.5
61.0
54.0
38 -31, 61,62, 12
75
59.5
63.0
68.5
70.0
65.5
61.5
53.5
42 -30, 50, 80
78
57.5
65.0
71.0
73.0
70.5
67.5
62.5
48 -31, 61,62, 12
80
58.5
67.5
73.5
75.0
70.5
67.5
64.5
60 -32
78
59.0
67.5
71.5
73.5
69.0
66.0
63.5
60.62, 62,12 -;
79
59.5
69.5
72.5
73.5
71.0
68.0
63.5
OTE: Tested in accordance with ARI Standard 270 -2008 (not listed in AHRI).
A- WEIGHTED SOUND POWER LEVEL WITH SOUND SHIELD
UNIT SIZE
STANDARD
RATING
dBA
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125
250
600
1000
2000
.004666-
8000
18 -31
71
55.5
60.5
64.0
66.0
83.0„40'.
58.5
52.0
24 -31
74
55.5
60.5
66.5
70.0
„ i#67.0
61.0
53.5
30 -31, 51
73
55.5
64.0
68.0
67.0 .. or"
64.0
60.0
52.5
36 -31, 51,62,12
74
59.5
63.0
68.0
69 :5'.
65.0
60.5
50.5
42 -30, 60, 60
77
57.5
65.0
70.5
or"' 72.0
70.0
87.0
62.0
48 -31, 51, 62, 12
79
60.5
67.5
73.500'
74.5
71.0
68.0
63.5
60 -32
78
59.0
68.0
,70:5
72.5
68.0
67.0
63.0
60 -62, 62, 12
78
60.5
69.5 oft- 72.5
73.0
71.0
67.5
61.5
NOTE: Tested in accordance with ARI Standard 270 -2008 (not listed in AHRI).
CHARGING SUBCOOLING (TXV -TYPE EXPANSION DEVICE)
UNIT SIZE- VOLTAGE &`SERIES
REQUIRED SUBCOOUNG °F ( °C)
18 -31 '
10
(5.6)
24 -31
10
(5.6)
30 -31, 61
10
(5.6)
38 -31, 51, 62, 12
14
(7.8)
'
42 -30, 60, 60
10
(5.6)
48- 31,51,62,12
15(8.3)
60 -32
13
(7.2)
60 -62, 62, 12
10
(5.6)
9
m
m
N
24ABB3
DIMENSIONS - ENGLISH
UNIT
SERIES
ELECTRICAL
CHARACTERISTICS
MO mo PAD
A
B
C
D
E
26' X 26'
F
0
K
L
M
N
P
OPERATING
WEIGHT (bs)
SHIPPING
WEIGHT (bs)
SHIPPING
DIMENSIONS (L x W x H)
24466318
1,2
X
0
0
0
23
1/8'
25 5/16'
3 3/4'
3/4'
4 7/16'
18
1/16'
7 13/16'
2 13/16'
1/2'
16 1/2'
15'
12'
101
130
24 1/4" X 27 3/8' X 33 1/2'
24486324
1
X
0
0
0
23
1/8'
25 5/16'
3 3/4'
3/4'
4 7/16'
18
1/16'
1 13/16'
2 13/16'
1/2'
16 1/2'
15'
12'
110
134
24 1/4" X 27 3/8' X 33 1/2'
24499330
1
X
0
X
0
23
1/8'
28 11/16'
3 3/4'
3/4'
4 7/16'
18
1/16'
7 13/16'
2 13/16'
1/2'
16 1/2'
15'
14'
111
136
24 1/4" X 21 3/8' X 33 1/2'
24466336
1
X
X
X
X
25
3/4'
32 5/16'
3 1/8'
7/6'
4 7/16'
21
1/4'
9 1/8'
2 15/16'
5/8'
14 1/4'
10 1/2'
16'
141
170
26 1/8' X 30 1/16" X 35 15/16'
24486342
0
X
0
X
X
31
3/16'
32 5/16'
3 7/8'
7/8'
6 9/16'
24
11/16'
9 1 /6'
2 15/16'
5/8'
15 3/4'
16 1/4'
13 3/4'
190
218
32 3/8' X 35 1/2' X 35 15/16'
24486348
1
X
X
X
X
31
3/16'
35 3/4'
3 7/8'
1/8'
6 9/16'
24
11/16'
9 1/8'
2 15/16'
5/8'
16 3/8"
15 3/8'
15 1/4'
186
224.
32 3/8' X 35 1/2' X 39 3/8'
1, 24488360
1,2
X
0
0
0
31
3/16'
25 I/O'
3 7/8'
7/8'.
6 9/16'
24
11/16'
9 1/8'
2 15/16'
5/6'
14 1/8'
„15 3/8'
11 3/8'
190
226.
32 3/8'X 35 1/2" X 32 9/16'
24498360
2
0
X
X
X
31
3/16'
28 15/16'
3 7/8'
7/8'
6 9/16'
24
11/16'
9 1/8'
2 15/16'
5/8'
16"
15 1/2'
12 3/4'
198
230
32 3/8' X 35 1/2" X 32 9/16'
6
X =YE
0 =N0
A
S0.
AIR DISCHARGE
f I
B
FIELD CONTROL
SU PLY CONN.
7 /8' HOLE
FIELD POWER SUPPLY CONN.
7/8' HOLE WITH
1 1/8' KNOCKOUT
3/8"
LIOUID LINE CONN.
C
3 11/2'
0D VAPOR LINE CONN.
1 7/8'
AIR INS
M
NOTES:
1. ALLOW 24" CLEARANCE TO SERVICE END OF UNIT.
48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE,
AND 18' BETWEEN UNITS FOR PROPER AIRFLOW.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
MODE IS 55 °F, MAX. 125 °F.
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER.
4. CENTER OF GRAVITY 0.
5. ALL DIMENSIONS ARE IN :INCHES" UNLESS NOTED.
AIR IN
AIR
DISCHARGE
5/16'
03/8' TIEDOWN KNOCKOUT
(21 PLACES
116 I8
- -A1R IN
MMMUN
UNIT SIZE
MO mo PAD
DIMENSIONS
18,24,30
23 1/2' X 23 1/2'
36
26' X 26'
48,60
31 1/2' X 31 1/2'
35' X 35'
1 7/8'
AIR INS
M
NOTES:
1. ALLOW 24" CLEARANCE TO SERVICE END OF UNIT.
48" ABOVE UNIT, 6" ON ONE SIDE, 12" ON REMAINING SIDE,
AND 18' BETWEEN UNITS FOR PROPER AIRFLOW.
2. MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING
MODE IS 55 °F, MAX. 125 °F.
3. SERIES DESIGNATION IS THE 13TH POSITION OF THE
UNIT MODEL NUMBER.
4. CENTER OF GRAVITY 0.
5. ALL DIMENSIONS ARE IN :INCHES" UNLESS NOTED.
AIR IN
AIR
DISCHARGE
5/16'
03/8' TIEDOWN KNOCKOUT
(21 PLACES
116 I8
- -A1R IN
N
CLEARANCES
24ABB3
Clearances (various examples)
24"
(609.6)
Service
12"
(304.8)
12"
(304.8)
24"
(609.6)
Service
12"
(304.8)
Wall
24"
(609.6)
Service
18"
(457.2)
Note: Numbers in () = mm
18"
(457.2)
24"
(609.6)
Service
i
18"
(457.2)
24"
(609.6)
Service
IMPORTANT: When installing multiple units in an alcove, roof well, or partially enclosed area, ensure there is adequate ventilation to prevent re- circulation of discharge air.
AHRI COMBINATION RATINGS* CONTINUED A G" (r 2 � 3
ARI Ref. No.
Model Number
Indoor Model
Fumace Model
Capacity
EERA
SEER
3492078
24ABB348A11
CNPV *4821A ** +TDR
45,500
11.0
132
3492079
24ABB348A11
CNPV *4824A ** +TDR
45,500
11.0
13.2
3492080
24ABB348A11
CNPV *6024A ** +TDR
48,500
11.2
13.2
3492084
24ABB348A11
CSPH *4812A " +TDR
48,000
11.0
13.2
3492085
24ABB348A11
CSPH*6012A**+TDR
48,500
11.2
13.2
3491328
24ABB348A51
tCAP * *4821A* *+TDR
46,000
11.0
13.2
3491329
24ABB348A51
CAP * *4817A ** +TDR
45,000
11.0
132
3491330
24ABB348A51
CAP * *4824A* *+TDR
45,500
11.0
13.2
3491331
24ABB348A51
CAP * *6021A ** +1DR
48,000
112
132
3491332
24ABB348A51
CAP**6024A**+TDR
48,500
112
13.2
3491338
24ABB348A51
CNPF *4818A* *+TDR
45,000
11.0
13.2
3491338
24ABB348A51
CNPH *4821A ** +TDR
45,500
11.0
132
3491337
24ABB348A51
CNPH *6024A* *+TDR
46,500
112
132
3491333
24ABB348A51
CNPV *4821A ** +TDR
45,500
11.0
132
3491334
24ABB348A51
CNPV*4824A ** +TDR
45,500
11.0
132
3491335
24ABB348A51
CNPV *6024A ** +TDR
48,500
112
13.2
3491339
24ABB348A51
CSPH *4812A " +TDR
46,000
11.0
13.2
3491340
24ABB348A51
CSPH *6012A* *+TDR
46,500
11.2
13.2
liellMillail
11111111151
MINIM
3491758
24ABB348A61
tCAP * *4821A ** +TDR
46,000
11.0
132
3491759
24ABB348A61
CAP * *4817A ** +TDR
45,000
11.0
132
3491760
24ABB348A61
CAP * *4824A* *+TDR
45,500
11.0
132
3491761
24ABB348A61
CAP * *6021A ** +1DR
48,000
112
132
3491762
24ABB348A61
CAP * *6024A ** +TDR
46,500
112
132
3491768
24ABB348A61
CNPF *4818A ** +TDR
45,000
11.0
13.2
3491766
24ABB348A61
CNPH *4821A* *+TDR
45,500
11.0
132
3491767
24ABB348A61
CNPH*6024A**+TDR
46,500
112
132
3491763
24ABB348A61
CNPV*4821A ** +TDR
45,500
11.0
132
3491764
24ABB348A61
CNPV*4824A ** +TDR
45,500
11.0
132
3491765
24ABB348A61
CNPV *6024A ** +TDR
46,500
11.2
13.2
3491769
24ABB348A61
CSPH *4812A ** +TDR
46,000
11.0
132
3491770
24ABB348A61
CSPH *6012A ** +1DR
48,500
112
132
®EMI=
3285396
24ABB360(A,W)32
tCAP* *6024A ** +TDR
57,500
11.0
13.0
3285405
24ABB360(A,W)32
CAP * *6021A **
58PH *110 -20
56,500
112
13.2
3285404
24ABB360(A,W)32
CAP * *6021A ** +TDR
56,500
11.0
13.0
3285407
24ABB360(A,W)32
CAP * *6024A **
58CV(A,X)155 -22
57,000
11.2
13.2
3285398
24ABB360(A,W)32
CAP * *6024A **
58MEB120 -20
56,500
11.0
132
3285400
24A8B360(A,W)32
CNPH *6024A **
58MEB100 -20
56,500
11.0
132
3285401
24ABB360(A,W)32
CNPH *6024A **
58MEB120 -20
56,500
11.0
132
3285414
24ABB360(A,W)32
CNPH•6024A **
58PH *110 -20
56,500
112
132
3285411
24ABB360(A,W)32
CNPH *6024A* *+1DR
57,000
11.0
13.0
3285409
24ABB360(A,W)32
CNPV *6024A **
58CV(A,X)135 -22
58,500
11.2
132
3285410
24ABB380(A,W)32
CNPV *6024A **
58CV(A,X)155 -22
57,000
112
13.2
3285408
24A8B360(A,W)32
CNPV*6024A ** +TDR
57,000
11.0
13.0
3285417
24ABB360(A,W)32
CSPH *6012A"
58CV(A,X)155 -22
56,500
112
132
3285403
24ABB360(A,W)32
CSPH *6012A **
58MEB120 -20
56,500
11.0
132
3285418
24ABB360(A,W)32
CSPH *6012A**
58PH *110 -20
56,500
112
132
3285415
24ABB360(A,W)32
CSPH *6012A* *+TDR
57,500
11.0
13.0
3285422
24ABB360(A,W)32
FV48NB006
57,500
11.5
13.5
3404614
24ABB360(A,W)32
FV4CNB006
57,500
11.5
13.5
24A13B360Al2
tCAP * *6024A ** +TDR
57,500
11.0
13.0
3492188
3492189
24ABB360Al2
CAP * *6021A ** +TDR
58,500
11.0
13.0
3492191
24ABB360Al2
CNPH *6024A ** +TDR
57,000
11.0
13.0
3492190
24ABB360Al2
CNPV*6024A* *+TDR
57,000
11.0
13.0
3492192
24ABB360Al2
CSPH *6012A ** +TDR
57,500
11.0
13.0
®111=111111
3491443
24ABB360A52
tCAP * *6024A ** +TDR
57,500
11.0
13.0
3491444
24ABB360A52
CAP * *6021A ** +TDR
56,500
11.0
13.0
3491446
24ABB360A52
CNPH*6024A**+TDR
57,000
11.0
13.0
3491445
24ABB360A52
CNPV*6024A* *+TDR
57,000
11.0
13.0
3491447
24ABB360A52
CSPH *6012A ** +TDR
57,500
11.0
13.0
IMMENIMENOMMERYS
3491874
24ABB360A62
tCAP * *6024A ** +TDR
57,500
11.0
13.0
3491875
24ABB360A62
CAP**6021A**+TDR
56,500
11.0
13.0
3491877
24ABB360A62
CNPH *6024A ** +TDR
57,000
11.0
13.0 E�
13.0
3491876
24ABB360A62
CNPV *6024A "* +TDR
57,000
11.0
3491878
24ABB360A62
CSPH *6012A **+TDR
57,500
11.0
13.0
• AHRI = Air Conditioning, Heating & Refrigeration Institute
t Tested combination
EERA - Energy Efficiency Ratio - 'A' conditions - 80 °F (26.6 °C) indoor db/67 °F
(19.4 °C) Indoor wb & 95 °F (35 °C) outdoor wb.
SEER - Seasonal Energy Efficiency Ratio
TDR - Time -Delay Relay. In most cases, only one method should be used to
achieve TDR function. Using more than one method in a system may cause
degradation in performance. Use either the accessory lime-Delay Relay,
KAATD0101TDR, or a furnace equipped with TDR. Most Carrier furnaces are
equipped with TDR.
UI - User Interface
21
NOTES:
1. Ratings are net values reflecting the effects of circulating fan motor heat.
Supplemental electric heat is not Included.
2. Tested outdoorfindoor combinations have been tested in accordance with DOE test
procedures for central air conditioners. Ratings for other
combinations are determined under DOE computer simulation procedures.
3. Determine actual CFM values obtainable for your system by referring to fan
performance data in fan cal or fumace cal literature.
4. Do not appty with capillary tube coils as performance and reliability are significantly
affected.
•
City of Tukwila
Jim Haggerton, Mayor
Department of Community Development Jack Pace, Director
February 22, 2012
Heath Hamblen
Universal Refrigeration
4102BP1NW
Auburn, WA 98001
RE: Correction Letter #1
Mechanical Permit Application Number M12 -019
Sahale Snacks — 3411 S 120 PI
Dear Mr. Hamblen,
This letter is to inform you of corrections that must be addressed before your mechanical permit can be
approved. All correction requests from each department must be addressed at the same time and
reflected on your drawings. I have enclosed comments from the Building Department. The Fire
Department has no corrections at this time.
Building Department: Allen Johannessen at 206 433 -7163 if you have questions regarding
the attached memo.
Please address the attached comments in an itemized format with applicable revised plans, specifications,
and /or other documentation. The City requires that two (2) sets of revised plans, specifications and /or
other documentation be resubmitted with the appropriate revision block.
In order to better expedite your resubmittal, a `Revision Submittal Sheet' must accompany every
resubmittal. I have enclosed one for your convenience. Corrections /revisions must be made in person
and will not be accepted through the mail or by a messenger service.
If you have any questions, please contact me at (206) 431 -3670.
Sincerely,
Bill Rambo
Permit Technician
encl
File: M12 -019
W:\Permit Center \Correction Letters \2012\M12-019 Correction Letter #1.doc
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone: 206 - 431 -3670 • Fax: 206 - 431 -3665
Tukwila Building Division
Allen Johannessen, Plan Examiner
Building Division Review Memo
Date: February 22, 2012
Project Name: Sahale Snacks
Permit #: M12 -019
Plan Review: Allen Johannessen, Plans Examiner
The Building Division conducted a plan review on the subject permit application. Please address the
following comments in an itemized format with revised plans, specifications and /or other applicable
documentation.
(GENERAL NOTE)
PLAN SUBMITTALS: (Min. size 11x17 to maximum size of 24x36; all sheets shall be the same size).
(If applicable) Structural Drawings and structural calculations sheets shall be original signed wet
stamped, not copied.)
1. On the front sheet (M -C), Mechanical schedule CFM column specifies 2000 CFM. The manufactures
packet specifies a 135 furnace highlighted in yellow, which indicates 2200 CFM. Also observed on
the cover sheet were other columns that are not consistent with manufactures specifications. Correct
the schedule on the cover sheet to show consistency with manufactures specifications for the
furnaces.
2. In addition to item 1), the economizer specified in the mechanical documents shows "for furnaces up
to 2000 CFM" which does not meet manufacturer's specifications for the 2200 CFM furnaces shown.
Provide the correct economizer to be consistent with manufacturer's specifications for the furnace
sizes shown.
Should there be questions concerning the above requirements, contact the Building Division at 206-
431 -3670. No further comments at this time.
t'EHMII GOON COP)
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: M12 -019 DATE: 02 -27 -12
PROJECT NAME: SAHALE SNACKS
SITE ADDRESS: 3411 S 120 PL
Original Plan Submittal Response to Incomplete Letter #
X Response to Correction Letter # 1 Revision # After Permit Issued
DEPARTMENTS.
S J CC�'�
Building_ Division
Public Works
Fire Prevention
Structural
Planning Division
❑ Permit Coordinator •
DETERMINATION OF COMPLETENESS: (Tues., Thurs.) DUE DATE: 02-28-12
Complete 4 Incomplete
Comments:
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES /THURS ROUTING:
Please Route Structural Review Required
REVIEWER'S INITIALS:
No further Review Required
DATE:
n
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions
DUE DATE: 03 -27 -12
Not Approved (attach comments)
Notation:
REVIEWER'S INITIALS: DATE:
Permit Center "Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Bldg ❑ Fire ❑
Ping ❑ PW ❑
Staff Initials:
Documents /routing slip.doc
2 -28 -02
•
*PEWIT COON COPY
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: M12 -019
PROJECT NAME: SAHALE SNACKS
SITE ADDRESS: 3411 S 120 PL
X Original Plan Submittal
Response to Correction Letter #
DATE: 02 -08 -12
Response to Incomplete Letter #
Revision # After Permit Issued
DEPA TMENTS:
&inion
Public Works n
AV\ Auc • k1-
Fire Prevention
Structural
Planning Division
Permit Coordinator
1
DETERMINATION OF COMPLETENESS: (Tues., Thurs.) DUE DATE: 02 -14 -12
Complete I. Incomplete
Comments:
Not Applicable
n
Permit Center Use Only
INCOMPLETE LETTER MAILED:
LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials: -
TUES /THURS ROUTING:
Please Route 171 Structural Review Required n No further Review Required
REVIEWER'S INITIALS:
DATE:
n
APPROVALS OR CORRECTIONS:
DUE DATE: 03 -13-12
Approved n Approved with Conditions n Not Approved (attach comments) n
Notation:
REVIEWER'S INITIALS: DATE:
Permit Center Use Only
CORRECTION LETTER MAILED: -)-4--).-.)" -I�-
Departments issued corrections: Bldg Fire ❑ Ping ❑ PW ❑ Staff Initials:
Documents /routing slip.doc
2 -28 -02
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.ci.tukwila.wa.us
REVISION SUBMITTAL
Revision submittals must be submitted in person at the Permit Center. Revisions will not be accepted through
the mail, fax, etc.
Date: Z— 2,7 — Z o/ Z
Plan Check/Permit Number: M12-0 1 9
❑ Response to Incomplete Letter #
Response to Correction Letter # 1
❑ Revision # after Permit is Issued
❑ Revision requested by a City Building Inspector or Plans Examiner
Project Name: Sahale Snacks
Project Address: 3411 S 120 P1
Contact Person: 11/4414 6 /414 Phone Number:
Summary of Revision: 1- e 1
bnaG✓Ce- �o c JortdQJ et s eere- (e[ , 4// GawcpooreA o`► o&14/'
a,- u/G s,4 e-f CMG) are- Car e - •ria74.Ae`Q c.omrofric- .i
iHeCued , fhe e cO i DwrCjef wGlfc.A /4 ,Me fcr) CCcww;e-r Vern liar
o e- . , oo: ra oar
aOw e r 76 7%274 iem../ i '7'y o f 4 /v` 7L4PY.1 Q7- • ki/e- S r`tae A/
Ot4 " elt4 !7/Y eM � se/ex-150;4 eppre/CarJ�^tee' ergo- fiia t ou r C-14 aids Q•�
lorwal�eK rew•tee Goee N,to7 e ed . 4/o `/ffe., /NeK- 7.5 wrvixe. .004.
Sheet Number(s): ! /9/7.- !, fr?
"Cloud" or highlight all areas of revision including date of revis n
Received at the City of Tukwila Permit Center by:
Entered in Permits Plus on
REFCE VED
FEB 2 4 20121
COMMUNITY
DEVELOPMENT
\applications \forms - applications on Tine \revision submittal
Created: 8 -13 -2004
Revised:
Contractors or Tradespeople Pr Friendly Page
•
General /Specialty Contractor
A business registered as a construction contractor with Lai to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent Company
UNIVERSAL REFRIGERATION INC
2539395501
Po Box 614
Auburn
WA
980710614
King
Corporation
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Specialty 1
Specialty 2
600599723
Active
UNIVERI159RF
Construction Contractor
12/6/1985
4/1/2012
Commercial/ Industrial/ Refrig
Unused
Business Owner Information
Name
Role
Effective Date
Expiration Date
RAEDER, STEVEN C
Cancel Date
01/01/1980
Amount
VERNON, GUY E
25
01/01/1980
01/01/1980
JACKSON, SHELDON G
04/01/2012
01/01/1980
01/01/1980
OSENBAUGH, CHARLES R
03/07/2011
01/01/1980
01/01/1980
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
5
AMERICAN STATES INS
CO
EX903622
12/06/2001
Until Cancelled
$6,000.00
03/18/2002
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
25
American
States
Insurance Co
01CG7497627
04/01/2010
04/01/2012
$1,000,000.00
03/07/2011
24
AMERICAN
STATES INS CO
01CG7497625
04/01/2009
04/01/2010
$1,000,000.00
03/09/2009
23
AMERICAN
STATES INS CO
01CG7497624
04/01/2008
04/01/2009
$1,000,000.00
03/11/2008
22
FIRST NAT'LINS
CO OF AMERICA
01CG7497623
04/01/2007
04/01/2008
$1,000,000.00
03/01/2007
21
FIRST
NATIONAL INS.
CO. OF AME
01CG7497622
04/01/2006
04/01/2007
$1,000,000.00
03/13/2006
20
FIRST
NATIONAL
INSURANCE CO
OF
01CG749762
04/01/2006
04/01/2007
$1,000,000.00
03/10/2006
19
AMERICAN CAS
INS CO
C2026115262
04/01/2005
04/01/2006
$1,000,000.00
03/23/2005
Summons /Complaint Information No unsatisfied complaints on file within prior 6 year period
Warrant Information No unsatisfied warrants on file within prior 6 year period
https://fortress.wa.gov/lni/bbip/Print.aspx
03/02/2012
ABBREVIATIONS:
AB
AC
A/C
ACP
ACT
ADH
ADJ
ADJT
AFF
AL
ALT
ANGLE
CENTER LINE
DIAMETER OR ROUND
NUMBER OR POUND
PENNY `:`
PERPENDICULAR'
PLATE
ANCHOR BOLT
ACOUSTICAL
AIR CONDITIONING
ACOUSTICAL PANEL
ACOUSTICAL TILE
ADHESIVE
ADJACENT
ADJUSTABLE '.
ACCESS FLOOR
ABOVE FINISH FLOOR ,
ALUMINUM.
ALTERNATE:
AP ;: ACCESS PANEL
APPROX APPROXIMATE:
ARCH ARCHITECTURAL
ASPH: ASPHALT
BOARD
BETW ` BETWEEN.
BLDG BUILDING
BLK BLOCK
BLDG BUILDING
BM BEAM
BRG. BEARING.
BOT : • BOTTOM
BSMT:. BASEMENT .
BUR BUILT UP ROOF
CAB CABINET
CB CATCH BASIN
CBU CEMENTITIOUS BACKER
CEM ` .; > CEMENT
CER CERAMIC
CFM :. CUBIC FEET PER MINUTE
CFT CONDUCTIVE FLOOR TILE
CG CORNER, GUARD
CHBD CHALK BOARD
CI CAST IRON
CJT CONTROL JOINT :.
CLF CHAIN LINK FENCE
CLG CEILING
CJ CONSTRUCTION JOINT
CLK CAULKING
UNIT:
CLO
CLR
CNTR
CO
COL
CONC
CONSTR.
CONT
CORR
CPT
CT
CTR
CY
DBL
DEPT
DET.
DF
DIA
DIAG
DIM
DISP ..
DN
DR
DWR
DW
DWG.
CLOSET
CLEAR
CONCRETE MASONRY
COUNTER
CLEANOUT
COLUMN
CONCRETE
CONSTRUCTION
CONTINUOUS
CORRIDOR
CARPET
CERAMIC TILE
CENTER YARD
DOUBLE
DEPARTMENT
DETAIL
DRINKING FOUNTAIN W 0 COOLER
DIAMETER
..
DIMENSION
DISPENSER
DOWN
DOOR. OR DRAIN
DRAWER
DOWNSPOUT `.
DISHWASHER
DRAWING
UNIT
EAST:
EACH
EXPANSION BOLT
EXPANSION JOINT
ELEVATION
FL
FLG
FLUOR
FM
FOC
FOF
FOIC
F010
FOS
FS
FT
FTG
FTIC
FTIO
FURR
FUT
FUTURE
RIO
FX:
GA:
GALV
GB
GL
FLOOR
FLASHING
FLUORESCENT
FACTORY MUTUAL.
FACE OF CONCRETE.
FACE OF FINISH
FURNISH BY OWNER
INSTALL BY CONTRACTOR
FURNISH BY OWNER
INSTALL BY OWNER
FACE OF STUD
FULL SIZE
FEET
FOOTING
FURNISHED BY TENANT
INSTALLED BY CONTRACTOR
FURNISHED BY TENANT.
INSTALLED BY. OWNER
FURRING
FUTURE
FUTURE ROUGH IN ONLY
FIXED:
GAGE
GALVANIZED
GRAB BAR
GLASS OR GLAZING..
GLBM GLU -LAM BEAN
GEN CONTR GENERAL CONTRACTOR
GND GROUND
GR GRADE
GWB GYPSUM WALL BOARD
HB
HC
HDR
HDWD.
HDWE
HM
HORIZ
HR
HT
HTG
HVAC
HWH
HOSE BIB
HOLLOW CORE OR HANDICAP
HEADER
HARDWOOD
HARDWARE
HOLLOW METAL
HORIZONTAL
HOUR
HEIGHT
HEATING
HEATING /VENTI LIATION/
AIR CONDITIONING
HOT WATER HEATER
ID INSIDE DIAMETER /.
DIMENSION
IG INSULATED GLAZING
IHM INSULATED HOLLOW METAL
IN INCH
INCL INCLUDE
INSUL INSULATION
INT INTERIOR
JAN . JANITOR
JT JOINT
KIT KITCHEN
KO . KNOCK OUT
KS KNEE SPACE
LAM
LAV
LB
LF
LG
LH
LINO
LKR.
LT
MACH
MATL
MAX
MECH
ELEC , ELECTRIC
ELEV ELEVATOR
ENTRY MAT
EMER EMERGENCY
LAMINATE
LAVATORY
LAG BOLT
LINEAL FOOT
LENGTH
LEFT HAND
LINOLEUM
LOCKER
LIGHT
MACHINE:
MATERIAL
MAXIMUM
MECHANICAL
MET OR MIL METAL
MEZZANINE
MANUFACTURER
MANHOLE
MINIMUM
MIRROR
MISCELLANEOUS.
MOLDING
MOISTURE RESISTANT GYP
MOUNTED
MULLION
MEZZ.
MFR
MH
MIN
MIR
MISC
MLD
MRGWB
MTD
MULL
N
NIC
NO/#
NOM
NTS
ENCL
EP
EWC.
EPX
EQ
EQPT
EST
EX
ENCLOSURE OR ENCLOSED
ELECTRICAL PANEL
ELECTRIC WATER COOLER
EPDXY
EQUAL
EQUIPMENT ..
ESTIMATE.
EXPANSION
EXIST. EXISTING
EXTERIOR
FA FIRE ALARM
FBO FURNISHED BY OTHERS
FCIC FURNISHED . BY CONTRACTOR
INSTALLED BY CONTRACTOR
FCTY FACTORY
FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FIN FINISH
OA
OC
OD
OFF
OH
OPH
OPNG:
OPP
PERP.
PFN
PL
P LAM
PLYWD
PNL
PNT
PR
SYMBOLS
WINDOW BUG
PS PAINT SYSTEM
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTD /R PAPER TOWEL DISPENSER
AND RECEPTACLE
PTN PARTITION
PTR PAPER TOWEL RECEPTACLE
PVMT PAVEMENT
COLUMN LINE /GRID LINE
INTERIOR ELEVATION(S).
ELEVATION IDENTIFICATION
SHEET WHERE ELEVATION IS
DRAWN
CRAFT ARCHITECTS, PLLC.
2505 THIRD AVE, STE. 324
SEATTLE, WASHINGTON 98121
KATHRYN M. CRAFT
SARAH DEVLIN
(206) 720 -7001
SARAH @CRAFTARCHITECTS.COM
QT:.
R
RA :'
RAD
RB
R&S
RD
RD /0.
REBAR.
REF
REFR
REINF
REQ'D
REV
RH
RESIL
R0
RT `..
RUB
RVS
RW
QUARRY TILE.
DOOR NUMBER TO CORRESPOND
TO ROOM ENTERING
RISER
RETURN AIR
RADIUS
RESILIENT BASE
ROD & SHELF
ROOF DRAIN
ROOF DRAIN OVERFLOW
REINFORCING BAR
REFERENCE
REFRIGERATOR
REINFORCED
REQUIRED
REVISION
RIGHT HAND OR ROBE HOOK
RESILIENT
ROOM
ROUGH OPENING
RESILIENT TILE
RUBBER
REVERSE
RAIN WATER
RWL RAIN WATER LEADER
S. SOUTH
SC. SOLID CORE,
SCD SEAT COVER DISPENSER
SCHD
SD
SECT
SF.
SHTG
SIM
KEY NOTE
TITLEI-,, ROOM IDENTIFICATION
TITLE2
TITLES ROOM NAME
ROOM ROOM NO.
ROOM FINISH GRADE
SABEY CORPORATION
12201 TUKWILA INTERNATIONAL BLVD.
FOURTH FLOOR
SEATTLE WA, 98168
GLENN PARRY
(206) 277-5212
GLENNPOSABEY.COM
APPROVED BY:
SAHALE SNACKS
3411 SOUTH 120TH PLACE, SUITE 100
SEATTLE, WA 98168
MIKE DEVLIN
(206) 947 -4463
MDEVLIN @SAHALESNACKS.COM
PARTITION TYPE
REVISION NUMBER
REVISION
CLOUD AROUND REVISION
MATCH LINE
SHADED PORTION IS THE SIDE
CONSIDERED 71
EXISTING GRADE
PROPERTY LINE
NEW OR FINISHED CONTOURS
NORTHWAY CONSTRUCTION
1433 VALENTINE AVE SE, STE. 102
PACIFIC, WA 98047.
KYLE FRY
(206) 551 -1416
KYLE ®NORTHWAYINC.COM
2505 Third Avenue
Suite 324
Seattle, VILA 9.8121.
SITE PLAN
• WORK. POINT, CONTROL POINT
OR DATUM POINT
EQUIPMENT NUMBER
SCHEDULE
SOAP DISPENSER
SECTION
SQUARE FEET
SHEATHING
SIMILAR
EXISTING CONTOURS
TOP OF. WALL
TOP OF CURB
AREA OF WORK
SK. SINK
SLR ,SEALER:
SND SANITARY NAPKIN
DISPENSER
SNR SANITARY NAPKIN
RECEPTACLE
SNT . SEALANT
SPEC. SPECIFICATION
SQ SQUARE
SST STAINLESS STEEL
SSK SERVICE SINK
ST STONE /STONE TILE
STA STATION
STC SOUND TRANSMISSION
CLASS
STD STANDARD
STL STEEL,
STOR STORAGE.
STRL STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
BUILDING SECTION (IDENTIFY ON PLAN)
SECTION IDENTIFICATION
SHEET WHERE SECTION IS DRAWN
TOP OF PAVEMENT
WALL SECTION (IDENTIFY ON ELEVATIONS)
SECTION IDENTIFICATION
SHEET WHERE SECTION IS DRAWN
PROJECT NORTH
DETAIL
DETAIL IDENTIFICATION
SHEET WHERE DETAIL IS DRAWN
TAX PARCEL
1023049069
LEGAL
FINISH BUG
SYM
SYMMETRICAL
.T TREAD
• TB • TOWEL BAR
T &B TOP & BOTTOM
TG TEMPERED GLASS
THK THICK
• THR. THRESHOLD
TIG
TEMPERED INSULATED
GLAZING
TO TOP OF
TOC TOP OF CONCRETE.
TOP TOP. OF PAVEMENT
TOS TOP OF STEEL.
TOSL • TOP OF SLAB
TOW TOP OF WALL.
TPD TOILET PAPER DISPENSER
`TPH TOILET PAPER HOLDER:
GENERAL NOTES
NORTH
NOT IN CONTRACT
NUMBER
NOMINAL
NOT. TO SCALE
OVERALL
ON CENTER
OUTSIDE DIAMETER/
DIMENSION
OFFICE
OVERHEAD
OPPOSITE HAND
OPENING.
OPPOSITE
TPTN.
TS
TV
TYP
UL
TOILET PARTITION
TUBULAR STEEL
TELEVISION
TYPICAL
UNDERWRITERS LABORATORY
UNF UNFINISHED
UON UNLESS OTHERWISE NOTED
UR URINAL
VAR VARIES
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIN : VINYL
VWC VINYL WALL COVERING
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET.
WD. WOOD.
WF WIDE FLANGE
WG WIRE GLASS
WP WATER PROOF
WR WATER RESISTANT
WSCT WAINSCOT
WT WEIGHT
XFMR. TRANSFORMER
THE CONTRACTOR SHALL BE SOLELY AND COMPLETELY RESPONSIBLE FOR CONDITIONS ON THE JOB SITE, INCLUDING THE SAFETY OF ALL PERSONS,
PROPERTY AND FOR ALL NECESSARY INDEPENDENT ENGINEERING REVIEWS OF THESE CONDITIONS, AND FOR COMPLIANCE WITH 0.5.H.A.' SAFETY
STANDARDS. ARCHITECTS AND THEIR CONSULTANTS' JOB SITE OBSERVATIONS ARE NOT INTENDED TO INCLUDE REVIEW OF THE ADEQUACY OF THE
CONTRACTOR'S SAFETY MEASURES.
EA CH CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH ALL SPECIFIED PRODUCTS RELATING TO THEIR WORK. THEY ARE TO SUBMIT WRITTEN
OBJECTIONS PRIOR TO BIDDING, IF THE CONTRACTOR HAS AN OBJECTION TO ANY PRODUC T AND/OR / OR DISCREPANCIES BETWEEN DRAWINGS AND
SPECIFICATIONS.
. ' THE GENERAL CONTRACTOR SHALL COORDINATE THEIR WORK WITH THAT OF OTHER SEPARATE CONTRACTS SUCH AS . SIGNS, & OWNER FURNISHED
I DONE Y OTH
ERS.
WHICH
ARE BEING B
ITEMS,
THE GENERAL CONTRACTOR SHALL VERIFY ALL EXISTING CO NDITIONS IN THE FIELD: THE ARCHITECT SHALL BE NOTIFIED IMMEDIATELY OF ANY
DISCREPANCIES BETWEEN ACTUAL FIELD CONDITIONS AND CONSTRUCTION DOCUMENTS. ALL WORK IN THAT AREA SHALL BE HELD UNTIL SUCH
DISCREPANCIES ARE RESOLVED:
. THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION, A.I.A. DOCUMENT A201, THE LATEST EDITION, SHALL BE INSPECTED AT THE
ARCHITECTS OFFICE:
SEPARATE PERMITS, WHEN REQUIRED AND /OR WHEN WORK ITEMS ARE DESIGN /BUILD IN NATURE, SHALL BE OBTAINED. BY THE CONTRACTOR FOR
MECHANICAL, PLUMBING, FIRE SPRINKLERS, ELECTRICAL AND FIRE ALARM. DESCRIPTIVE, DETAILED DESIGN AND REQUIRED SUBMITTAL DOCUMENTS
INFORMATION SHALL BE PROVIDED FOR REVIEW BY THE REGULATING AUTHORITIES AND BY THE OWNER /TENANT /ARCHITECT FOR APPROVAL PRIOR TO
WORK BEING PERFORMED. SEE SPECIFICATIONS FOR REQUIREMENT FOR DESIGN/BUILD ANY Q FIRE SPRINKLER SYSTEM. SUBMIT PLAN TO AND OBTAIN /
PERMIT FROM THE FIRE PREVENTION BUREAU FOR FIRE SPRINKLER SYSTEM INSTALLATION OR MODIFICATION.
COMPLETE FIRE SPRINKLER DRAWINGS WILL BE SUBMITTED BY THE FIRE PROTECTION CONTRACTOR.
8. THE INSTALLATION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SHALL COMPLY WITH THE INTERNATIONAL BUILDING CODE
9. SPECIAL INSPECTIONS WHERE REQUIRED BY THE BUILDING OFFICIAL. SHALL BE PERFORMED BY INSPECTORS APPROVED BY THE BUILDING OFFICIAL.
10. ALL WORK DONE SHALL BE IN CONFORMANCE WITH THE APPROVED PLANS AND PROJECT SPECIFICATIONS. THE APPROVED, .PERMITTED STAMPED
PLANS ARE TO REMAIN ON SITE AT ALL TIMES.
11. DIMENSIONS ARE TO FACE OF STUD CONCRETE, OR MASONRY UNLESS OTHERWISE NOTED:
12: DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN:
13. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK, DETAILS SHALL BE THE SAME AS FOR OTHER SIMILAR
WORK. IF QUESTIONS CAN NOT BE RESOLVED IN THIS MANNER, CONTACT THE ARCHITECT PRIOR TO PROCEEDING:
14: GENERAL CONTRACTOR SHALL PROVIDE OWNER WITH DETAILED CRITICAL PATH SCHEDULE FOR REVIEW AND APPROVAL PRIOR TO START OF
C
CONSTRUCTION. UPDATES OF SCHEDULE SHALL BE MADE AS NECESSARY WITH COPIES PROVIDED TO OWNER.
WITH THE LATEST RULES AND REGULATIONS OF THE INTERNATIONAL BUILDING CODE,
ALL WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE W ,
NATIONAL ELECTRICAL CODE AND ALL OTHER APPLICABLE STATE 0
TAT OR LOCAL LAWS AND REGULATIONS: NOTHING IN THESE DRAWINGS IS TO BE
CONSTRUED AS TO PERMIT WORK WHICH IS NOT CONFORMING TO THE PREVIOUS LISTED CODES.
16. PROTECTIVE MEASURES SHALL BE TAKEN BY THE CONTRACTOR TO PROTECT ADJACENT PROPERTY AT ALL TIMES DURING CONSTRUCTION.
17. THE CONTRACTOR SHALL COMPLY WITH ALL CURRENT APPLICABLE LOCAL ORDINANCES FOR UTILITY SERVICES:
18. LIGHT AND VENTILATION SHALL COMPLY WITH I:B.C:, SECTION 1203, 1204 & 1205.
19. FIRE BLOCKING SHALL BE PROVIDED AT ALL FRAMED WALLS AT 10' -O' 0.C. AND ALSO AT ANY LOCATION WHERE WALL FRAMING PENETRATES
CEILINGS. REFER TO IBC SEC. 708 FIRE BLOCKING AND DRAFT STOPS FOR . CONSTRUCTION:
WATER CONSERVATION AND/OR ANY JURISDICTION'S PERFORMANCE STANDARDS.
20. ALL WATER. FIXTURES MUST COMPLY WITH WAC 51-26-180 WA C E /
HANGES TO THE MECHANICAL SYSTEM REQUIRE A MECHANICAL PERMIT THEY SHALL COMPLY WITH THE MOST CURRENT UNIFORM MECHANICAL
21. WHEN CHANGES Q
CODE AND WITH ANY LOCAL JURISDICTION REQUIREMENTS:
22. PROVIDE ILLUMINATED EXIT SIGNAGE AT ALL REQUIRED EXITS.
23. PATCH AND REPAIR ALL EXISTING WALLS, FLOORS AND CEILINGS THAT ARE ADJACENT TO AND AFFECTED BY NEW CONSTRUCTION.
24. CONTRACTOR IS TO COMPLY WITH CHAPTER 33 OF THE INTERNATIONAL BUILDING CODE CONCERNING PROTECTION OF PEDESTRIANS DURING
CONSTRUCTION.
25. PRIOR TO FINAL INSPECTION, A CERTIFICATE OF CONSTRUCTION COMPLIANCE SHALL BE READY FOR THE INSPECTOR. THE CERTIFICATE SHALL STATE
"BASED UPON PERSONAL KNOWLEDGE, THAT THE . WORK APPEARS TO HAVE. BEEN PERFORMED, AND THE MATERIALS USED AND INSTALLED APPEAR IN
EVERY MATERIAL RESPECT IN COMPLIANCE WITH THE PLANS". THE CERTIFICATE MUST BE SIGNED BY ONE OR MORE OF THE FOLLOWING
(A) OWNER, (B) GENERAL CONTRACTOR, (C) AN APPROVED INDEPENDENT INSPECTOR OR INSPECTION AGENCY.
26. ASBESTOS AND HAZARDOUS WASTE EXCLUSION:
THE ARCHITECT HEREBY STATES, AND THE OWNER ACKNOWLEDGES, THAT THE ARCHITECT HAS NO PROFESSIONAL LIABILITY OR OTHER INSURANCE,
(AND IS UNABLE TO REASONABLY OBTAIN SUCH INSURANCE) FOR CLAIMS ARISING OUT OF THE PERFORMANCE OF OR THE FAILURE TO PERFORM
PROFESSIONAL, SERVICES, INCLUDING BUT NOT LIMITED TO, THE PREPARATION OF REPORTS, DESIGNS, DRAWINGS, AND SPECIFICATIONS, AND
RELATED TO THE INVESTIGATION DETECTION.
PERPENDICULAR
PREFINISHED
PLATE OR PROPERTY LINE
PLASTIC . LAMINATE,
PLYWOOD
PANEL
PAINT
PAIR
YARD
FILE COPY
Permit No.
• omissions.
Y
9-
p,, r 1.
8
and ot�
approval
Is �Ii subject
: construction documents does not authorize
11. t, of any adopted code or ordinance. RecciPt
t ��� �° �jand is acknowledged:
�- . d :�°l� �n
.ic 1 1' 1L0 �i
t"' ewes shall be made to
1,.the scope
� without prior approval of
,, ; ;ta Building n9 sron.
will rE
�' anew tan s
f. A submittal
*1 include additional plan review fees.
3411 SOUTH 120TH PLACE, SUITE 100
SEATTLE, WA 98168
DESCRIPTION
PORTION OF GOV LOT 15 IN SW 1/4 OF SECTION 10 -23 -04 BEGIN NW
CORNER OF SW 1/4 TH S 01 -46 -02 W .107.22 FT TH S 87 -33 -12 E
512.24 FT TO POINT OF BEGINNING TH S 87 -33 -12 E 214.16 FT TH
N 78 -40 -52 E 415.05 FT TO WLY MARGIN OF E MARGINAL WAY TH S
16 -31 -41 E 241.92 FT . TH S 28 -02 -57 E 104.42 FT TH S
17 -01 -47 E 100.50 FT TH S 11-19-15 E 13.28 FT TH N 58- 13 -58.
W 473.87 FT TH S 01 -46 -02 W 37 FT TH N 88 -13 -58 W 307.80 FT
TH N 01 -46 -02 E 373.93 FT TO POINT OF BEGINNING . LOT 1 OF
CITY OF TUKWILA BOUNDARY LINE ADJUSTMENT NO L2000 -042
RECORDING NO 20000828900001
TENANT IMPROVEMENT CONSISTING OF: NEW AND RENOVATED NON - STRUCTURAL OFFICE,
SPACE, STRIPING OF NEW PARKING STALLS, THE ADDITION OF (2) ACCESSIBLE STALLS
AND NEW ENTRANCE SITE WORK.
NEW EXTERIOR OPENINGS, WINDOWS AND DOORS UNDER SEPARATE PERMIT.
CODE/ZONING INFORMATION
0
N
ZONING DISTRICT: MIC / / H
CODE EDITION: 2009 IBC / 2009. FIRE CODE
CONSTRUCTION TENANT IMPROVEMENT
CLASSIFICATION: (OFFICE)/F-1 -
EXISTING OCCUPANCY CLAS B (MANUFACTURING )/S-1 1 (WAREHOUSE)
TYPE OF CONSTRUCTION: III B
SPRINKLER SYSTEM: FULLY SPRINKLERED
kt
DE OF DRAWINGS
N X
AREA SEPARATION:
NON- SEPARATED, UNLIMITED :. PER 2009 IBC 302.3.1, SECTION 506, AND 507
ACTUAL FLOOR AREAS:
OFFICE (EXISTING) (B) 3,014 SQ FT
OFFICE (NEW) (B) 3,196 SQ FT
MANUFACTURING (EXISTING) (F -1) 16,550 SQ FT
WAREHOUSE (EXISTING (5-1) 18,307 SQ FT
TOTAL ACTUAL FLOOR AREA: 41,067 SQ FT
OCCUPANCY LOAD:
(SEC. 1004.1 TABLE 1004:1.1)
OFFICE (6)
MANUFACTURING (F-1)
WAREHOUSE (S -1)
TOTAL OCCUPANCY LOAD
EXIT REQUIREMENTS:
SEC. 1021 TABLE 1021.1 & 1021.2)
NUMBER REQ'D
a:;
SEPARATE PERMIT
REQUIRED FOR:
Mechanical
Iniectrkal
cri a mbin
!ri
Gas Pipes
City of Tukwila
DIVISION
6,210 SQ FT / 100 = 62
16,550 S Q FT / 100 = 165
18,307 SQ FT / 500 = 37
41,067 SQ FT _.
NUMBER PROVIDED
OFFICE 2 2
MANUFACTURING 2 2
WAREHOUSE 2 2
ENERGY REQUIREMENTS
NO ,BUILDING ENVELOPE MODIFICATIONS ARE PROPOSED.
= 264
LIGHTING REQUIREMENTS
SCOPE OF WORK TO MEET OR EXCEED LIGHTING REQUIREMENTS
SEPARATE PERMIT SUBMITTALS
ELECTRICAL, MECHANICAL FIRE ALARM /SPRINKLER
T1..1 GENERAL INFORMATION AND SITE PLAN
T1s2. ACCESSIBILITY GUIDELINES
A0.1 ARCHITECTURAL SITE /EGRESS /WAREHOUSE PLAN
, ENLARGED SITE PLAN
A1.1 ' DEMOLITION PLAN
A2.1 FLOOR PLAN
A2.2 REFLECTED CEILING PLAN
A2.3 POWER /COMM PLAN
A5.1 INTERIOR ELEVATIONS & DETAILS
A6.1 DOOR & FINISH SCHEDULES
A8.1 WALL TYPES & CEILING DETAILS
REVIEWED FOR
CODE COMPLIANCE
APPROVED
FEB 2 9
City of Tukwila
BUILDING I
aIV SION
CONSULTANT
PARKING REQUIREMENTS
NOTE: PARKING STALLS ARE EXISTING SCOPE OF WORK DOES NOT INVOLVE
OCCUPANCY CHANGES OR BUILDING SQUARE FOOTAGE AMENDMENTS:
6,210 SQ FT. OFFICE ®.1/250
16,550 SQ FT MANUFACTURING @ 1/1000
18,307 SQ FT WAREHOUSE @ 1/2000
TOTAL STALLS REQUIRED
25. STALLS
17 STALLS
9 STALLS
5.1 STALLS.
RECEIVED
ACCESSIBLE STALLS PROVIDED 2 STALLS
TOTAL STALLS PROVIDED 70 STALLS FEB 08 B0 2012
PERMIT C T Et�T E
PLUMBING FIXTU .R E REO'S
NOTE PLUMBING FIXTURES ARE EXISTING; THE FOLLOWING CALCULATIONS ARE TO
DEMONSTRATE EXISTING CONDITIONS COMPLIANCE
WASHINGTON STATE AMENDMENTS: CHAPTER 29, TABLE 2902.1.
PLUMBING FIXTURE REQUIREMENTS
WATER
CLOSET
URINAL
LAVATORY
DRINKING
FOUNTAIN
WAREHOUSE (S -1)
18,307 S.F. /5000 = 4
(1 OF EA. SEX)
1 PER 1-10
PEOPLE
1 FOR
>26
1 PER 40
PEOPLE
MANUFACTURING (F -1)
16,550 S.F. /2000 = 8
(1 OF EA. SEX)
1 PER 1 -10
PEOPLE
1 FOR
>26
1 : PER 40
PEOPLE
OFFICE (B) :
6,210 S.F./200 = 31
(2 OF EA. SEX).
1 PER 1 -15
PEOPLE
1 PER 2
WATER CLOSET
1 FOR >30
TOTAL REQUIRED
(4) FEMALE
(4) MALE
(0) MALE
(3) FEMALE
(3) MALE
(1) FOUNTAIN
TOTAL PROVIDED
(5) FEMALE
(4) MALE
(2) MALE
(6) FEMALE
(41 MALE
(1) FOUNTAIN
REVISIONS:
FOR PERMIT 12/05/11
FOR BID 12/08/11
FOR. CONSTRUCTION . 01/26/12
SHEET TITLE GEN
ERAL INFORMATION
DATE:
01/26/12
DRAWN:
PROJECT NO.
SAD
11 458.06
KMC
ORIGINAL DRAWING IS 24" x 36".
SCALE ENTITIES ACCORDINGLY IF REDUCED
SHEET NO:
T11
COPYRIGHT CRAFT ARCHITECTS 2011
/
i
AREA OF W , R.
///
//
//
/
R NiED FOR
CODE COMPLIANCE
APPROVED
FEB 2 9 2012:
City of Tukwila.
BUILDING DIVIVON
AREA OF WORK
x x x x x x x x
11- 458_A0.1 (SITE PLAN).dwg
ARCHITECTURAL SITE /EGRESS /WAREHOUSE PLAN
,, = 20' -0"
GENERAL NOTES:
1. ALL COLUMNS AND EXTERIOR WALLS ARE EXISTING TO REMAIN.
2. GC TO PROVIDE REQUIRED PORTABLE FIRE EXTINGUISHERS IN OCCUPANCIES AND
LOCATIONS AS REQUIRED PER SECTION 906 IN THE INTERNATIONAL FIRE CODE.
3. STRUCTURAL REVIEW IS REQUIRED FOR ANY ROOF TOP EQUIPMENT OR ROOF
PENETRATIONS.
4. SEE SHEET A2.1 FOR ROOM OCCUPANCY CALCULATIONS
EGRESS SUMMARY
A. MAX. TRAVEL DISTANCE B OCCUPANCY: 300' (TABLE 1016.1)
MAX. TRAVEL DISTANCE S -1, F -1 OCCUPANCY: 250' (TABLE 1016.1)
MAX. COMMON PATH OF EGRESS TRAVEL: 100' (1014.3 EXCEPTION 1)
MINIMUM CORRIDOR WIDTH: 44" (1018.2)
REQUIRED EGRESS WIDTH: 0.2 PER OCCUPANT (1005.1) = 78.8" REQUIRED
REQUIRED STAIR EGRESS WIDTH: 0.3 PER OCCUPANT (1005.1) = 118.2" REQUIRED
MINIMUM CLEAR DOOR OPENING: 32 INCHES (1008.1.1)
MAXIMUM DEAD END CORRIDOR: 50' (1018.4)
B.
C:
D.
LEGEND:
EXIT
EXIST. WALLS / PARTITION TO REMAIN
NEW PARTITION WALL
LIGHTED EXIT SIGNAGE W/ BATTERY BACKUP PER IBC
SECTION 1011, CONFIRM OPERATION FOR EXISTING. ADD
WHERE NOT EXISTING.
KEY NOTES:
1. EXISTING TENANT DEMISING WALL
2. NO WORK IN THIS AREA
3. EXISTING STOREFRONT SYSTEM AND ACCESSIBLE ENTRANCE /EXIT TO REMAIN
4. NEW STOREFRONT SYSTEM UNDER SEPARATE PERMIT
5. EXISTING FIRE RISER TO REMAIN
6. NEW EXIT SIGN PER IBC SECTION 1011
7. EXISTING EXIT SIGN TO REMAIN
8. EXISTING ELECTRICAL TRANSFORMER AND ELECTRICAL PANELS TO REMAIN
9. EXISTING PARKING STALLS TO REMAIN, TYP
10. NEW CONCRETE ENTRY SLAB
11. NEW ACCESSIBLE PARKING STALL W/ WHEELCHAIR SYMBOL AND (1) W/ VAN
DESIGNATION, ACCESS AISLE, SIGNAGE (SEE DTL 11/A8.1) AND WHEEL STOP,
TYP, TO MEET THE PROVISIONS OF ANSI A117.1 - 502/503, 406
12. STRIPE NEW PARKING STALLS THIS AREA
REQUIRED
14. NEW EXTRUDED CURB, FILL WITH GRAVEL TO MATCH EXISTING
15. NEW 10'X14' PASSAGE WAY THROUGH EXISTING DEMISING WALL, EXACT LOCATION
TO BE COORDINATED ON SITE WITH OWNER
16. NEW DOCK DOOR IN EXISTING OPENING
RECEIVED
FEB 08 2012
PERMIT CENTER
ENERGY CODE COMPLIANCE:
1. PROJECT SHALL COMPLY WITH 2009 WASHINGTON STATE ENERGY CODE
INCLUDING BUT NOT LIMITED TO THE FOLLOWING PROVISIONS:
A. 1310.2 SEMI - HEATED SPACES: FOR SEMI - HEATED SPACES HEATED BY
OTHER FUELS ONLY, WALL INSULATION IS NOT REQUIRED FOR THOSE WALLS
SEPARATE SEMI - HEATED SPACES FROM THE EXTERIOR PROVIDED THAT THE
SPACE IS HEATED SOLELY BY A HEATING SYSTEM CONTROLLED Y A
THERMOSTAT WITH A MAXIMUM SET POINT CAPACITY OF 45 DEGREES,
MOUNTED NO LOWER THAN THE HEATING UNIT.
B. 1314 AIR LEAKAGE: 1314.1 BUILDING ENVELOPE SEALING: THE FOLLOWING
AREAS OF THE BUILDING ENVELOPE SHALL BE SEALED, CAULKED, GASKETED
OR WEATHER- STRIPPED TO MINIMIZE AIR LEAKAGE:
• JOINTS AROUND FENESTRATION AND DOOR FRAMES;
• JUNCTIONS BETWEEN WALLS AND FOUNDATIONS, BETWEEN WALLS AT
BUILDING CORNERS, BETWEEN WALLS AND STRUCTURAL FLOORS OR
ROOFS, AND BETWEEN WALLS AND ROOF OR ROOF PANELS;
• OPENINGS AT PENETRATIONS OF UTILITY SERVICES THROUGH THE ROOFS,
WALLS AND FLOORS;
• SITE -BUILT FENESTRATION AND DOORS;
• BUILDING ASSEMBLIES USED AS DUCTS OR PLENUMS;
• JOINTS, SEAMS AND PENETRATIONS OF VAPOR RETARDERS; AND
• ALL OTHER OPENINGS IN THE BUILDING ENVELOPE.
C. 1314.2 GLAZING AND DOORS: AIR LEAKAGE FOR FENESTRATION AND DOORS
SHALL BE DETERMINED IN ACCORDANCE WITH NFRC 400 OR
AAMA /WDMA /CSA 101/IS2/A440 OR ASTM E283 AS SPECIFIED BELOW. AIR
LEAKAGE SHALL BE DETERMINED BY A LABORATORY ACCREDITED BY A SHEET TITLE:
NATIONALLY RECOGNIZED ACCREDITATION ORGANIZATION, SUCH AS THE
NATIONAL FENESTRATION RATING COUNCIL, AND SHALL BE LABELED AND
CERTIFIED BY THE MANUFACTURER. AIR LEAKAGE SHALL NOT EXCEED:
• 1.0 CFM /FT2 FOR GLAZED SWINGING ENTRANCE DOORS AND REVOLVING
DOORS, TESTED AT A PRESSURE OF AT LEAST 1.57 POUNDS PER
SQUARE FOOT (PSF) IN ACCORDANCE WITH NFRC 400, AAMA /WDMA /CSA
101/IS2/A440, OR ASTM E283.
• 0.04 CFM /FT2 FOR CURTAIN WALL AND STOREFRONT GLAZING, TESTED
AT A PRESSURE OF AT LEAST 1.57 POUNDS PER SQUARE FOOT (PSF) DRAWN:
IN ACCORDANCE WITH NFRC 400, AAMA /WDMA /CSA 101/IS2/A440, OR
ASTM E283.
• 0.2 CFM /FT2 FOR ALL OTHER PRODUCTS WHEN TESTED AT A PRESSURE PROJECT NO:
OF AT LEAST 1.57 POUNDS PER SQUARE FOOT (PSF) IN ACCORDANCE
WITH NFRC 400 OR AAMA /WDMA /CSA 101/IS2/A440, OR 0.3 CFM /F72 APPROVED:
WHEN TESTED AT A PRESSURE OF AT LEAST 6.24 POUNDS PER SQUARE
FOOT (PSF) IN ACCORDANCE WITH AAMA /WDMA /CSA 101/I.S/A440.
s 1 . 4
T rtt '. .
SNA
a r c h 1 t e c t s
2505 Third Avenue
Suite 324
Seattle, WA 98121
206.720.7001 phone.
206.720.2949 fax
www.craftarchitects.com
W
��nn D
VJ CO
111
U0t0
Q Q
CD
LLI
r Val
rQ
VJ D
O
CO
CONSULTANT
REVISIONS: FOR PERMIT 12/05/11
FOR BID 12/08/11
FOR CONSTRUCTION 01/26/12
ARCHITECTURAL SITE /EGRESS PLAN
DATE: 01/26/12
DESIGN:
D. 1314.6 CONTINUOUS AIR BARRIER: NOT REQUIRED FOR BUILDINGS LESS
THAN FIVE STORIES
SAD
11- 458.06
KMC
ORIGINAL DRAWING IS 24" x 36 ".
SCALE ENTITIES ACCORDINGLY IF REDUCED
SHEET NO:
A0.1
COPYRIGHT CRAFT ARCHITECTS 2011
SUPPLY AIR DUCT
FLUE VENT (THROUGH ROOF)
EVAPORATOR
COIL
GAS PIPING REGULATOR DETAIL
O0
0
PR
0.
10 409.4 MP REGULATOR VALVES
A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR
2 409.5 APPLIANCE SHUTOFF VALVE
EACH APPLIANCE SHALL BE PROVIDED WITH A SHUTOFF VALVE IN ACCORDANCE WITH SECTION 409.5.1, 409.5.0, OR 409.5.3
O3
VENT LIMITERS ARE DESIGNED F R E T S 0 USE INDOORS AND IN SPACES WHERE LIMITING THE AMOUNT OF GAS ESCAPEMENT DUE TO DIAPHRAGM FAILURE IS CRITICAL...
VENT LIMITERS ARE NOT TO BE USED OUTDOORS IF THEY ARE EXPOSED TO THE ENVIRONMENT. 13A15 VENT PROTECTOR IS AVAILABLE FOR OUTDOOR USE WHEN
VENT PROTECTION IS REQUIRED.
04 411.1.6 UNIONS
A UNION FITTING SHALL BE PROVIDED FOR APPLIANCES CONNECTED BY RIGID METALLIC PIPE. SUCH UNIONS SHALL BE ACCESSIBLE AND LOCATED WITHIN
6 FEET (1829 MM) OF THE APPLIANCE.
® 410.1 PRESSURE REGULATORS
A LINE PRESSURE REGULATOR SHALL BE INSTALLED WHERE THE APPLIANCE IS DESIGNED TO OPERATE AT A LOWER PRESSURE THAN THE SUPPLY PRESSURE.
LINE PRESSURE GAS REGULATORS SHALL BE LISTED AS COMPLYING WITH ANSIZ21.80. ACCESS SHALL BE PROVIDED TO PRESSURE REGULATORS. PRESSURE
REGULATORS SHALL BE PROTECTED FROM PHYSICAL DAMAGE. REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
OUDOOR INSTALLATION.
® 6 A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED SHALL BE INSTALLED BETWEEN THE MP REGULATOR AND ITS UPSTREAM SHUTOFF VALVE, SUCH TEE
FITTING SHALL BE POSITIONED TO ALLOW THE CONNECTION OF A PRESSURE - MEASURING INSTRUMENT AND TO SERVE AS A SEDIMENT TRAP.
0 A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED SHALL BE INSTALLED NOT LESS THAN 10 PIPE DIAMETERS DOWNSTREAM OF THE MP REGULATOR OUTLET.
SUCH TEE FITTING SHALL BE POSITIONED TO ALLOW THE CONNECTION OF A PRESSURE- MEASURING INSTRUMENT:
ECONOMIZER
,
GAS FURNACE (GF- 1,2,3)
OSA INTAKE (THROUGH ROOF)
0
0
RETURN AIR DUCT
MEZZANINE
DRAIN PAN SLEEPERS -
FILTER RACK
CEILING GRID
DETAIL - TYPICAL GAS FURNACE INSTALLATION
SCALE: NTS
AIR CONDITIONER SCHEDULE
AC -1,2,3
BRAND NAME
CARRIER
ING
24ABB360
GAS FURNACE (W/ COOLIN
BRAND NAME
MODEL NUMBER
TOTAL
MCA
MOCP
60,000
13.0
460/3/60
10.5
15.0
190 LBS.
ULE
AREA SERVED
GF -1
CARRIER
58STA135 -22
ENTRY /CONFEREN
GF -2
CARRIER
58STA135 -22;
NE QUADRANT
GF -3
CARRIER
58STA135 -22.
NW QUADRANT
NOTE: These plans are diagrammatical only.
Please verify all dimensions at job site
STANDARD
CFM
RATING
2,000*
2,000*
2,000*
* SYSTEM DESIGN
CFM LEVEL
OSA DISTRIBUTION /NON - DUCTED RETURN
HVAC ABBREVIATIONS
SECTION 302.3.53 WSIAQC - OUTDOOR AIR SHALL BE DISTRIBUTED TO EACH
ROOM /AREA. WHERE SUPPLY IS SEPARATED FROM EXHAUST POINTS BY
DOORS, PROVISIONS SHALL BE MADE TO ENSURE AIRFLOW BY UNDERCUTTING
DOORS, TRANSFER GRILLES, OR SIMILAR MEANS. DOORS SHALL BE UNDERCUT
A MINIMUM 1/2" ABOVE FLOOR COVERING (SEE BELOW).
CFM THROUGH DOOR - NO TRANSFER GRILLE
FIG. 15 SECTION 25.19 1997 ASHRAE
b
r ACW=
ABOVE FINISHED FLOOR
BACKDRAFT DAMPER
BRITISH THERMAL UNIT PER HOUR
CEILING DIFFUSER
CUBIC FEET PER MINUTE
DECIBEL
DEGREE
DUCT HEATER
DOWN
EXHAUST AIR
ENERGY EFFICIENCY RATIO
EXHAUST GRILLE
EXTERNAL STATIC PRESSURE
ENTERING WATER TEMPERATURE
EXHAUST
FAN COIL UNIT
FIRE DAMPER, FLOOR DRAIN
FEET PER MINUTE
FIRE AND SMOKE DAMPER
GAUGE
GAS FURNACE
GALLONS PER MINUTE
GRILLE, REGISTER, DIFFUSER
GYPSUM WALLBOARD
HORSEPOWER, HEAT PUMP
INSIDE DIMENSION
INFRARED HEATER
KILOWATT
THOUSAND BTU PER HOUR
MOTORIZED CONTROL DAMPER
NOISE CRITERIA
NOT IN CONTRACT
NOT TO SCALE
OPPOSED BLADE DAMPER
ON CENTER
OUTSIDE DIMENSION OR DIAMETER
OUTSIDE AIR
PRESSURE DROP
REVOLUTIONS PER MINUTE
RETURN AIR
RETURN AIR GRILLE
SUPPLY AIR
SUPPLY GRILLE
STATIC PRESSURE
SIDEWALL SUPPLY GRILLE
TO BE DETERMINED
TRANSFER GRILLE
TYPICAL
VARIABLE AIR VOLUME
VARIABLE FREQUENCY DRIVE
VENT TO ROOF
VARIABLE VOLUME AND TEMPERATURE
WITH ECONOMIZERS PER MANUFACTURER'S INSTALLATION
a +b +c +d
600
a
- - - --
1 P = 30 inches
I
i
I
I
I 4
Assume a, b, c = .1 inches
d =.5 inches
c ACW = .2 inches
I _
Average door
I measurements
I ACW .2 inches
1 =
av . crack width
.2 9 c ack Idth ACW- d
Now correlate to pressure differential of
acceptable oP =.15 inches H20
NOTE:
ROOMS SUPPLIED WITH 15 .55
CFM = CFM ( • 1 CFM *.683
=
400 CFM OR MORE .30
REQUIRE TRANSFER GRILLES (AP=.15i) 1 1
600 x .68 = 408 CFM
SETBACK WITH 5 DEGREE DEADBAND.
SUPPLY AIR DUCT
FLUE VENT (THROUGH ROOF)
EVAPORATOR
COIL
GAS PIPING REGULATOR DETAIL
O0
0
PR
0.
10 409.4 MP REGULATOR VALVES
A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR
2 409.5 APPLIANCE SHUTOFF VALVE
EACH APPLIANCE SHALL BE PROVIDED WITH A SHUTOFF VALVE IN ACCORDANCE WITH SECTION 409.5.1, 409.5.0, OR 409.5.3
O3
VENT LIMITERS ARE DESIGNED F R E T S 0 USE INDOORS AND IN SPACES WHERE LIMITING THE AMOUNT OF GAS ESCAPEMENT DUE TO DIAPHRAGM FAILURE IS CRITICAL...
VENT LIMITERS ARE NOT TO BE USED OUTDOORS IF THEY ARE EXPOSED TO THE ENVIRONMENT. 13A15 VENT PROTECTOR IS AVAILABLE FOR OUTDOOR USE WHEN
VENT PROTECTION IS REQUIRED.
04 411.1.6 UNIONS
A UNION FITTING SHALL BE PROVIDED FOR APPLIANCES CONNECTED BY RIGID METALLIC PIPE. SUCH UNIONS SHALL BE ACCESSIBLE AND LOCATED WITHIN
6 FEET (1829 MM) OF THE APPLIANCE.
® 410.1 PRESSURE REGULATORS
A LINE PRESSURE REGULATOR SHALL BE INSTALLED WHERE THE APPLIANCE IS DESIGNED TO OPERATE AT A LOWER PRESSURE THAN THE SUPPLY PRESSURE.
LINE PRESSURE GAS REGULATORS SHALL BE LISTED AS COMPLYING WITH ANSIZ21.80. ACCESS SHALL BE PROVIDED TO PRESSURE REGULATORS. PRESSURE
REGULATORS SHALL BE PROTECTED FROM PHYSICAL DAMAGE. REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
OUDOOR INSTALLATION.
® 6 A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED SHALL BE INSTALLED BETWEEN THE MP REGULATOR AND ITS UPSTREAM SHUTOFF VALVE, SUCH TEE
FITTING SHALL BE POSITIONED TO ALLOW THE CONNECTION OF A PRESSURE - MEASURING INSTRUMENT AND TO SERVE AS A SEDIMENT TRAP.
0 A TEE FITTING WITH ONE OPENING CAPPED OR PLUGGED SHALL BE INSTALLED NOT LESS THAN 10 PIPE DIAMETERS DOWNSTREAM OF THE MP REGULATOR OUTLET.
SUCH TEE FITTING SHALL BE POSITIONED TO ALLOW THE CONNECTION OF A PRESSURE- MEASURING INSTRUMENT:
ECONOMIZER
,
GAS FURNACE (GF- 1,2,3)
OSA INTAKE (THROUGH ROOF)
0
0
RETURN AIR DUCT
MEZZANINE
DRAIN PAN SLEEPERS -
FILTER RACK
CEILING GRID
DETAIL - TYPICAL GAS FURNACE INSTALLATION
SCALE: NTS
AIR CONDITIONER SCHEDULE
AC -1,2,3
BRAND NAME
CARRIER
ING
24ABB360
GAS FURNACE (W/ COOLIN
BRAND NAME
MODEL NUMBER
TOTAL
MCA
MOCP
60,000
13.0
460/3/60
10.5
15.0
190 LBS.
ULE
AREA SERVED
GF -1
CARRIER
58STA135 -22
ENTRY /CONFEREN
GF -2
CARRIER
58STA135 -22;
NE QUADRANT
GF -3
CARRIER
58STA135 -22.
NW QUADRANT
NOTE: These plans are diagrammatical only.
Please verify all dimensions at job site
STANDARD
CFM
RATING
2,000*
2,000*
2,000*
* SYSTEM DESIGN
CFM LEVEL
SECURE UNIT WITH (4) 3" x 1/2" LAG SCREWS
@ 4 CORNERS (UNIT WEIGHT - -- LBS.)
SHEET METAL SLEEPER COVERS
COUNTERSUNK 8" x 1/2" LAG SCREWS
INTO 6" x 27" GLB (TYP. 2)
ROOFING MATERIAL
3/4" PLYWOOD
INSULATION
1 -1/2" x 1 -1/2" 18 GA. ANGLE WITH
2" x 12 GA. LAG SCREWS @ 12" O.C.
®DETAIL OUTDOOR UNIT TIE -DOWN
SCALE: NTS
S.P.
OSA
GAS HEATING
COOLING COIL INFO
BTUH INPUT
BTUH OUTPUT
MODEL
SEER TO
1.5
5300
126,000
102,000
CNPHP6024ACA
13.0
1.5
5300
126,000
102,000
CNPHP6024ACA
13.0
1.5
5300
126,000
102,000
CNPHP6024ACA
13.0
57,000
57,000
57,000
A.F.U.E.
VENT OUTLET
VOLTAGE /PHASE
MCA
80%
4"0
115/1/60
14.4
80%
4 "0
115/1/60
14.4
80%
4 "0
115/1/60
14.4
MOCP
WEIGHT
163 LBS.
163 LBS.
163 LBS.
HVAC LEGEND.
m❑
INLINE EXHAUST FAN(S)
ROOFTOP EXHAUST FAN
SIDEWALL EXHAUST FAN
VAV FAN BOX
CEILING EXHAUST FAN
GAS METER
VVT DAMPER
X
T -BAR SUPPLY DIFFUSER
T -BAR RETURN GRILLE
HARDLID SUPPLY DIFFUSER
HARDLID RETURN GRILLE
FD �--
FSD ♦-
FIRE SMOKE DAMPER
SD ■
VOLUME DAMPER
SMOKE DETECTOR
FLEXIBLE DUCT SA/RA
ROUND DUCT UP
ROUND DUCT DOWN
(10x10 CD\
`300 CFM -10 "0
DIFFUSER TAG
HVAC NOTES
HVAC ABBREVIATIONS
1. DUCT INSULATION SHALL MEET REQUIREMENTS OF
SECTION 1414.2 OF THE 2009 WSEC AND TABLE 14 -5.
2. SMOKE DETECTOR(S) INSTALLED IN MAIN RETURN AIR
DUCTS PER SECTION 606 OF THE 2009 IMC. HVAC SMOKE
DUCT DETECTORS SHALL SHUT DOWN POWER TO THE
UNIT UPON ACTIVATION AND A "SUPERVISORY" ZONE SHALL
BE INITIATED AT FIRE ALARM PANEL UPON SMOKE DUCT
DETECTOR ACTIVATION. IMC SECTION 606.2.1.
3. DUCTWORK - MAINTRUNK IS R -4.2 IN CONDITIONED SPACES
AFF
BDD
BTUH
CD
CFM
DB
DEG
DH
DN
EA
EER
EG
ESP
EWT
EXH
FCU
FD
FPM
FSD
GA
GF
GPM
GRD
GWB
HP
ID
IRH
KW
MBH
MCD
NC
NIC
NTS
OBD
OC
OD
OSA
PD
RPM
RA
RAG
SA
SG
SP
SSG
TBD
TG
TYP
VAV
VFD
VTR
VVT
ABOVE FINISHED FLOOR
BACKDRAFT DAMPER
BRITISH THERMAL UNIT PER HOUR
CEILING DIFFUSER
CUBIC FEET PER MINUTE
DECIBEL
DEGREE
DUCT HEATER
DOWN
EXHAUST AIR
ENERGY EFFICIENCY RATIO
EXHAUST GRILLE
EXTERNAL STATIC PRESSURE
ENTERING WATER TEMPERATURE
EXHAUST
FAN COIL UNIT
FIRE DAMPER, FLOOR DRAIN
FEET PER MINUTE
FIRE AND SMOKE DAMPER
GAUGE
GAS FURNACE
GALLONS PER MINUTE
GRILLE, REGISTER, DIFFUSER
GYPSUM WALLBOARD
HORSEPOWER, HEAT PUMP
INSIDE DIMENSION
INFRARED HEATER
KILOWATT
THOUSAND BTU PER HOUR
MOTORIZED CONTROL DAMPER
NOISE CRITERIA
NOT IN CONTRACT
NOT TO SCALE
OPPOSED BLADE DAMPER
ON CENTER
OUTSIDE DIMENSION OR DIAMETER
OUTSIDE AIR
PRESSURE DROP
REVOLUTIONS PER MINUTE
RETURN AIR
RETURN AIR GRILLE
SUPPLY AIR
SUPPLY GRILLE
STATIC PRESSURE
SIDEWALL SUPPLY GRILLE
TO BE DETERMINED
TRANSFER GRILLE
TYPICAL
VARIABLE AIR VOLUME
VARIABLE FREQUENCY DRIVE
VENT TO ROOF
VARIABLE VOLUME AND TEMPERATURE
WITH ECONOMIZERS PER MANUFACTURER'S INSTALLATION
INSTRUCTIONS PER I.M.C. 2009, SECTION 403, CHAPTER 6,
SECURE UNIT WITH (4) 3" x 1/2" LAG SCREWS
@ 4 CORNERS (UNIT WEIGHT - -- LBS.)
SHEET METAL SLEEPER COVERS
COUNTERSUNK 8" x 1/2" LAG SCREWS
INTO 6" x 27" GLB (TYP. 2)
ROOFING MATERIAL
3/4" PLYWOOD
INSULATION
1 -1/2" x 1 -1/2" 18 GA. ANGLE WITH
2" x 12 GA. LAG SCREWS @ 12" O.C.
®DETAIL OUTDOOR UNIT TIE -DOWN
SCALE: NTS
S.P.
OSA
GAS HEATING
COOLING COIL INFO
BTUH INPUT
BTUH OUTPUT
MODEL
SEER TO
1.5
5300
126,000
102,000
CNPHP6024ACA
13.0
1.5
5300
126,000
102,000
CNPHP6024ACA
13.0
1.5
5300
126,000
102,000
CNPHP6024ACA
13.0
57,000
57,000
57,000
A.F.U.E.
VENT OUTLET
VOLTAGE /PHASE
MCA
80%
4"0
115/1/60
14.4
80%
4 "0
115/1/60
14.4
80%
4 "0
115/1/60
14.4
MOCP
WEIGHT
163 LBS.
163 LBS.
163 LBS.
HVAC LEGEND.
m❑
INLINE EXHAUST FAN(S)
ROOFTOP EXHAUST FAN
SIDEWALL EXHAUST FAN
VAV FAN BOX
CEILING EXHAUST FAN
GAS METER
VVT DAMPER
X
T -BAR SUPPLY DIFFUSER
T -BAR RETURN GRILLE
HARDLID SUPPLY DIFFUSER
HARDLID RETURN GRILLE
FD �--
FSD ♦-
FIRE SMOKE DAMPER
SD ■
VOLUME DAMPER
SMOKE DETECTOR
FLEXIBLE DUCT SA/RA
ROUND DUCT UP
ROUND DUCT DOWN
(10x10 CD\
`300 CFM -10 "0
DIFFUSER TAG
REVIEWED FOR
CODE COMPLIANCE
APPROVED
FEB 2 9 2012
City ofTulkvvila
BUILDING DIVISION
CORRECTION
LTR#
RECEIVED
FEB 27 2012
PERNTCENTER
(PEND ING CITY APPROVAL
IVE S L
REFRIGERATION
- AIR CONDITIONING HEAT PUMPS - REFRIGERATION
CONTRACTORS LICENSE NUMBER:
AUBURN: (253) 939 -5501 TACOMA: (253) 922 -3141
SEATTLE: (253) 839 -2126 FAX: (253) 735 -3432
UNIVERI 159RF
P.O. BOX 614 - AUBURN, WASHINGTON 98071
°UNIVERSAL REFRIGERATION DRAWING -2001
z
0
U
W
0
0
(J)_
W
i-
<
0
PROJECT MANAGER:
HH
HVAC NOTES
1. DUCT INSULATION SHALL MEET REQUIREMENTS OF
SECTION 1414.2 OF THE 2009 WSEC AND TABLE 14 -5.
2. SMOKE DETECTOR(S) INSTALLED IN MAIN RETURN AIR
DUCTS PER SECTION 606 OF THE 2009 IMC. HVAC SMOKE
DUCT DETECTORS SHALL SHUT DOWN POWER TO THE
UNIT UPON ACTIVATION AND A "SUPERVISORY" ZONE SHALL
BE INITIATED AT FIRE ALARM PANEL UPON SMOKE DUCT
DETECTOR ACTIVATION. IMC SECTION 606.2.1.
3. DUCTWORK - MAINTRUNK IS R -4.2 IN CONDITIONED SPACES
AND R -8 IN UNCONDITIONED SPACES AS PER THE WSEC.
4. ALL SINGLE PACKAGE HVAC UNITS SHALL BE INSTALLED
WITH ECONOMIZERS PER MANUFACTURER'S INSTALLATION
INSTRUCTIONS PER I.M.C. 2009, SECTION 403, CHAPTER 6,
AND SHALL OPERATE, PER W.S.E.C. 2009, SECTION 1413.
5. EQUIPMENT INSTALLATION INSTRUCTIONS TO BE ON -SITE
FOR INSPECTIONS.
6. ALL HVAC EQPM. TO BE LABELED TO THE SPACE SERVED.
7. DUCTS TO BE SUPPORTED AT EACH DIRECTION CHANGE
VERTICAL AT 12' -0" MAX., HORIZONTAL AT 10' -0" MAX.
WITH STRAP, OR 8' -0" MAX. F TRAPEZE SUPPORT.
8. THERMOSTAT TO BE SEVEN -SAY TYPE AND HAVE NIGHT
SETBACK WITH 5 DEGREE DEADBAND.
9. THE HVAC INSTALLATION SHALL BE COMPLETE WHEN ALL
SECTIONS OF 1416 WSEC HAVE BEEN SATISFIED. THIS
SHALL INCLUDE AS -BUILT DRAWINGS, SUBMITTALS, O &M
MANUALS, SYSTEM BALANCE REPORT, AND A COMM-
ISSIONING REPORT.
10. DUCT SEALING SHALL MEET REQUIREMENTS OF WSEC
1414.1. DUCT WORK WHICH 1S DESIGNATED TO OPERATE
AT PRESSURES ABOVE 1/2 " WATER COLUMN STATIC
PRESSURE SHALL BE SEALED IN ACCORDANCE WITH
STANDARD RS -18. EXTENT OF SEALING IS AS FOLLOWS:
a. STATIC PRESSURE: 1/2" TO 2 "; SEAL TRANSVERSE JOINTS.
b. STATIC PRESSURE 2: 2" TO 3 "; SEAL ALL TRANSVERSE
JOINTS AND LONGITUDINAL SEAMS.
c. STATIC PRESSURE: ABOVE 3"; SEAL ALL TRANSVERSE
JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL
PENETRATIONS.
11. NREC FORMS, DUCTING PLANS (BALANCING FEATURES), AS
WELL AS VIAQ INFORMATION IS REQUIRED ALONG WITH A
MECH. PERMIT AT THE TIME OF THE TENANT IMPROVEMENT
PERMIT.
12. PIPING INSULATION SHALL MEET THE REQUIREMENTS OF
1415 OF THE WSEC:
TABLE 14-0
IMAM PPE INSULATION
RANGE T
Btu40-Fr2- 7
MAP. 7
UP 10 2
LESS
HEATING SYMMS
NOUNAL OGU A1ION 1FIICIGESS
STEAM. STEM CONDENSATE MID HOT WATER
STEM
_I ..
1 , ik'
tir;
251 -350
0.29 -0.31
200
1.5
2.0
2.5
2.5
3.5
3.5
201 -250
0.27 -0.30
150
1.0
1.5
1.5
2.0
2.0
3.5
141 -200
0.25 -0.29
125
0.5
1.5
1.5
1.5
1.5 .
1.5
105 -140
024-0.28
100
1.5
1.0
1.0
1.0
1.5
1.5
CITT1 11.ii 'Y
,i: ►.4..,1 *'.. UziL
t:1l T^
D AV - ,Y l'.1
INEIZMY_IIIM
IIIIME111111 NUM REM =HI W11111 MIME Eh
i
8� �y um ... _
023-00.33 -b023-027 S
10
I 1�0
1 2
' 1.5
I 11
11.5
REVIEWED FOR
CODE COMPLIANCE
APPROVED
FEB 2 9 2012
City ofTulkvvila
BUILDING DIVISION
CORRECTION
LTR#
RECEIVED
FEB 27 2012
PERNTCENTER
(PEND ING CITY APPROVAL
IVE S L
REFRIGERATION
- AIR CONDITIONING HEAT PUMPS - REFRIGERATION
CONTRACTORS LICENSE NUMBER:
AUBURN: (253) 939 -5501 TACOMA: (253) 922 -3141
SEATTLE: (253) 839 -2126 FAX: (253) 735 -3432
UNIVERI 159RF
P.O. BOX 614 - AUBURN, WASHINGTON 98071
°UNIVERSAL REFRIGERATION DRAWING -2001
z
0
U
W
0
0
(J)_
W
i-
<
0
PROJECT MANAGER:
HH
SCOPE OF WORK
JOB #12029
1. INSTALL (3) GAS FURNACES WITH COOLING COILS.
2. INSTALL (3) ROOF- MOUNTED AIR CONDITIONING UNITS.
3. INSTALL DUCTWORK AND GRILLES:
REVIEWED FOR
CODE COMPLIANCE
APPROVED
FEB 2 9 2012
City ofTulkvvila
BUILDING DIVISION
CORRECTION
LTR#
RECEIVED
FEB 27 2012
PERNTCENTER
(PEND ING CITY APPROVAL
IVE S L
REFRIGERATION
- AIR CONDITIONING HEAT PUMPS - REFRIGERATION
CONTRACTORS LICENSE NUMBER:
AUBURN: (253) 939 -5501 TACOMA: (253) 922 -3141
SEATTLE: (253) 839 -2126 FAX: (253) 735 -3432
UNIVERI 159RF
P.O. BOX 614 - AUBURN, WASHINGTON 98071
°UNIVERSAL REFRIGERATION DRAWING -2001
z
0
U
W
0
0
(J)_
W
i-
<
0
PROJECT MANAGER:
HH
UN L
REFR GLUM
- AIR CONDITIONING - HEAT PUMPS REFRIGERATION -
CONTRACTORS LICENSE NUMBER: UNIVERI 159RF
AUBURN: (253) 939 -5501 TACOMA: (253) 922 -3141
SEATTLE: (253) 839 -2126 FAX: (253) 735 -3432
L �I■�� ' r E.. il_POPU11
P.O. BOX 614 - AUBURN, WASHINGTON 98071
°UNIVERSAL REFRIGERATION DRAWING -2001
z
0
EE
0
z
0
w
CFM 10°0
r
VALUND
II
wmassonislill
7111111311 I
CA 815
aka
PROJECT MANAGER:
HH
NOTE: These plans are diagrarnmatical only.
Please verify all dimensions at job site
•
SEE DETAIL 1 ON SHEET M -C FOR CONFIGURATION
SEE DETAIL 2 ON SHEET M -C FOR CONFIGURATION
229.0 CFH ' 40'
VERSAL
REF GE
- AIR CONDITIONING - HEAT PUMPS REFRIGERATION
CONTRACTORS LICENSE NUMBER: UNIVERI 159RF
AUBURN: (253) 939 -5501 TACOMA: (253) 922 -3141
SEATTLE: (253) 839- 2126 FAX (253) 735 -3432
P.O. BOX 614 AUBURN, WASHINGTON 98071
QUNIVERSAL REFRIGERATION DRAWING -2001
3/4 110 NAT. GAS
GF -. 114.5
18 "0 OSA INTAII
"0 NAT. GAS
Z
0
U
c1)
w
0
Z
0
w
cc
w
0
"0 NAT. GA
CFH @ 140'
18 "0 SA
WAKE
•
4 "0 NAT. GAS
EXI ` ING IUM P' URE
NA RAL METE
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MEZZANINE LEVEL NATURAL GAS PIPING PLAN
SCALE: 1/8" = 1' -0"
PROJECT MANAGER:
HH
NOTE: These plans are diagrammatical only.
Please verify all dimensions at job site