M12-109
Measurement Systems International
14240 Interurban Avenue South
RECORDS DIGITAL D- ) EXEMPTION LOG
THE ABOVE MENTIONED PERMIT FILE INCLUDES THE FOLLOWING REDACTED INFORMATION
F,age # Code
Exemption � � �� Brief Explsnatoty Description, Statute /Rule
The Privacy Act of 1974 evinces Congress' intent that
Personal Information —
social security numbers are a private concern. As
such, individuals' social security numbers are
Social Security Numbers
redacted to protect those individuals' privacy pursuant
5 U.S.C. sec.
DR1
Generally — 5 U.S.C. sec.
to 5 U.S.C. sec. 552(a), and are also exempt from
552(a); RCW
552(a); RCW
disclosure under section 42.56.070(1) of the
42.56.070(1)
42.56.070(1)
Washington State Public Records Act, which exempts
under the PRA records or information exempt or
prohibited from disclosure under any other statute.
Redactions contain Credit card numbers, debit card
Personal Information —
numbers, electronic check numbers, credit expiration
17
DR2
Financial Information —
dates, or bank or other financial account numbers,
RCW
RCW 42.56.230(4 5)
which are exempt from disclosure pursuant to RCW
42.56.230(5)
42.56.230(5), except when disclosure is expressly
required by or governed by other law.
MEASUREMENT SYSTEMS
INTERNATIONAL
14240 INTERURBAN AV S
SUITE 200
M12 -109
City oikukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -43 1 -3670
Inspection Request Line: 206- 431 -2451
Web site: http: / /www.TukwilaWA.gov
MECHANICAL PERMIT
Parcel No.: 3365901881
Address: 14240 INTERURBAN AV S TUKW
Project Name: MEASUREMENT SYSTEMS INTERNATIONAL
Permit Number: M12 -109
Issue Date: 07/23/2012
Permit Expires On: 01/19/2013
Owner:
Name: BELLTOWN INVESTMENT PARTNER
Address: 2505 2ND AVE #520 , SEATTLE WA 98121
Contact Person:
Name: PAUL GOTO
Address: 3132 NE 133 ST , SEATTLE WA 98125
Email: PAUL.GOTO @PSRMECHANICAL.COM
Contractor:
Name: PSR -HVAC & MECHANICAL SERVICES
Address: PO BOX 27073 , SEATTLE WA 98165
Contractor License No: PSRHVMS922NJ
Phone: 206 367 -2500
Phone: 206 - 367 -2500
Expiration Date: 04/21/2014
DESCRIPTION OF WORK:
SUITE 200: INSTALL (1) NEW DUCTLESS SPLIT A/C ONLY SYSTEM FOR NEW SERVER ROOM
Value of Mechanical: $4,206.00
Type of Fire Protection: UNKNOWN
Electrical Service Provided by:
Permit Center Authorized Signature:
I hereby certify that I have read and e
governing this work will be complied
Fees Collected: $244.88
International Mechanical Code Edition: 2009
Date:
amin d this permit and know the same to be true and correct. All provisions of law and ordinances
vith, hether specified herein or not.
The granting of this permit does not pre s m to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign and obtain this mechanical permit and agree to the conditions on the
back of this permit.
Print Name:
Date:
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
doc: IMC -4/10
M12 -109 Printed: 07 -23 -2012
PERMIT CONDITIONS
Permit No. M12 -109
1: ** *BUILDING DEPARTMENT CONDITIONS * **
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431- 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: Readily accessible access to roof mounted equipment is required.
6: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap the sanitary
sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks, wells, and other
excavations. Final inspection approval will be determined by the building inspector based on satisfactory completion of
this requirement.
7: Manufacturers installation instructions shall be available on the job site at the time of inspection.
8: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the City of Tukwila
Building Department (206- 431 - 3670).
9: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431 - 3670).
10: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
doc: IMC -4/10
M12 -109 Printed: 07 -23 -2012
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http:ilwww.TukwilaWA.gov
Mechanical Permit No.
Project No.
Date Application Accepted: 01 77
0I ?213.
M ()Pt
Date Application. Expires:
(For office; use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *please print **
King Co Assessor's Tax No.: 33 6.5 1O — lg'$1
Site Address: 114240 In -et-a ain) Avg, 5.
Tenant Name: IAONSV17-6mewr SySttfAS Itvtatt4mot,Jert._
Suite Number: 200
New Tenant:
PROPERTY OWNER
Name: ?Aix. 601.-0
Name: getitbtal inv+GTwieVIr PAnryVt
22f1
Address: 2555 24/v 6- 0520
Email: rAoL . eiCAp a 'PERM FCCuA'Y►108L , coo
City:zE State: l
Zip: a$LZ)
CONTACT PERSON. - person receiving all project
communication
Name: ?Aix. 601.-0
Address: 3132 146-133¢9 p!'
City: e State: ev Zip: art
Phone:) 34 7_ Z,SD..z, Fax: (2,0 368'% eigo
Email: rAoL . eiCAp a 'PERM FCCuA'Y►108L , coo
Floor: 2
❑ Yes [X. No
MECHANICAL CONTRACTOR INFORMAT ION
Company Name:
r5(L N•ECAnA'1V Kest..
Address:
3'137_ 146 I3'142A ST
City: 3 le State: Zip: agtZ$
Phone:( � X67- v Fax: ) 368' -68
Contr Reg No.: aitkivIvt,012,E4 Jr xp Date / 30! ty
Tukwila Business License No.: als --Oct934gg
Valuation of project (contractor's bid price): $ 411206
Describe the scope of work in detail:
tn9i i (1) "641 Dttcxtess �fs 'td SPLrr Pr/ avtk ;ppt-Grn (F„IL Plena! S .w rum.) -
Use: Residential: New
Commercial: New
Fuel Type: Electric
E
g
Gas
Replacement
Replacement
Other:
II: \Appl icaliois'.Forns•Appl icat ions On Linc12011 Applicel tuns Nle..haniwl Permit Appl di tun Res iseJ 3 -0 -1 Ldoc.
Revised: August 2011
bh
Page 1 or2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Furnace >100k btu
Floor furnace
Suspended/wall /floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig /cooling
system
Air handling unit
/
<10,000 cfm
1
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system
Hood and duct
Incinerator — domestic
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
Thermostat
Wood/gas stove
Emergency generator
Other mechanical
equipment
Boiler /Compressor
Qty
0 -3 hp /100,000 btu
3 -15 hp /500,000 btu
15 -30 hp /1,000,000 btu
30 -50 hp /1,750,000 btu
50+ hp /1,750,000 btu
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED AGENT:
Signature:
Date: -r /t3 i/Z-
Print Name: PAL Gen Day Telephone:r(2O) SG 7- ZaTO
Mailing Address: '1'2. Aft !'332Q Sr"
FI: \Applicaiions \Porn Applic.tions On Line \2011 Appli..aioit.;\Tkchaui.al Permit Appli..aliun Res is J S -9 -I 1.Jo.x
Res'ised. August 2011
bh
Setrine t.et QB`t zS
City State Zip
Page 2 of 2
C City of Tukwila
•
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -43 1 -3670
Fax: 206 -431 -3665
Web site: http: / /www.TukwilaWA.ov
RECEIPT
Parcel No.: 3365901881 Permit Number: M12 -109
Address: 14240 INTERURBAN AV S TUKW Status: PENDING
Suite No: Applied Date: 07/13/2012
Applicant: MEASUREMENT SYSTEMS INTERNATIONAL Issue Date:
Receipt No.: R12 -02122
Initials: JEM
User ID: 1165
Payment Amount: $244.88
Payment Date: 07/13/2012 01:00 PM
Balance: $0.00
Payee: PSR HVAC & MECHANICAL SERVICES
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 011769 244.88
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
MECHANICAL - NONRES
PLAN CHECK - NONRES
000.322.102.00.00 195.90
000.345.830 48.98
Total: $244.88
doc: Receiot -06 Printed: 07 -13 -2012
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 F (206) 431 -3670
Permit Inspection Request Line (206) 431 -2451
Project:
P a rIJ 18 tit eik \ S tc (e4f
Type of Insp ection:
LA
JG� u G - i Jt
Addr4 7.4 a :F_Are u tw -A.ate
Cal - /4. f,r 6C/
' %9 V
Special Instructions:
•ti �--
S �
Date Wanted: _
a.m.
1
Requester:
k.
(�
_
Approved per applicable codes.
Corrections required prior to approval. l�
COMMENTS:
"TarkpprbJ c,ei
,31
due,c),\ i-i- /Ar.)k,_ 4 . r ‘e.,k
_
-.,/i
` „4.-
1
_ a
.... 1 r
Inspec or:
Date: 2
I I REINSPECTION FEE REQUIRED. rior to next inspection, fee must be
paid at 6300 Southcenter Blvd.; Suite 100..Catl to schedule reinspection.
7
Air System Sizing Summary for Ductless Split
Project Name: Fairway Center Ductless Split
Prepared by: PSR
07/13/2012
10:34AM,
Air System Information
Air System Name* Ductless Split
Air System Type. Single Zone CAV
FILE COPY
Number of zones{ . 1
Floor Area' �'Ci!..p-, No. 1540 sgft
Location. Seattle IAP, m
as g
P'-
Sizing Calculation Information
Calculation Months. Jan to Dec Calculation method. Transfer Function Method
Central Cooling Coil Sizing Data
Total coil load. 1.9 Tons Load occurs at Jun 1800
Total coil Toad. 22.3 MBH OA DB / WB: 80.2/63.7 F
Sensible coil load. 22.3 MBH Entering DB / WB: 72.7/72.7 F
Coil airflow 1500 CFM Leaving DB / WB: 58.7/58.7 F
Sensible heat ratio: 1.000 Coil ADP. 57.1 F
Area per unit Toad* 82.8 sqft/Ton Bypass Factor' 0.100
Load per unit area: 144.9 BTU /(hr -sqft) Resulting RH• 0 %
Design supply temp. 58.0 F
Supply Fan Sizing Data
Actual max airflow: 1500 CFM Fan motor BHP. 0.00 BHP
Standard airflow:. 1476 CFM Fan motor kW. 0.00 kW
Actual max airflow per unit area 9.74 CFM /sqft Fan static. 0.00 in wg
Outdoor Ventilation Air Data
Design airflow:.. 0 CFM Airflow per person. 0.00 CFM /person
Airflow per unit floor area 0.00 CFM /sqft
Space Sizing Data
Space Name
Maximum
Cooling
Sensible
MBH
Design
Airflow.
°'CFM
Time of Peak
Load
'.
Maximum
=- Heating
Load MBH
Space
Floor
Area
sqft
Space
CFM/sqft
Server Room
22.3
1500
Jun 1800
0.7
154.0
9.74
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL 2 0 2012
City of Tukwila
BUILDING DIVISION
R CEIED
Crrf OF Tt V IEALA
JUL 1 S 7012
PERMIT CENTER
Block Load 4.15
AM9---
Page 1 of 3
System Design Load Summary for Ductless Split
Project Name: Fairway Center Ductless Split
Prepared by: PSR
07/13/2012
10:34AM
Block Load 4.15 Page 2 of 3
DESIGN COOLING
DESIGN HEATING
Jun 1800
OA DB / WB 80.2 F / 63.7 F
Design Heating Day
OADB1WB23F/192F
Zone Loads based on TFM
.,
Details
Sensible
BTU/hr
Latent BTU /hr
Details
Sensible
BTU/hr
Latent BTU /hr
Window and Skylight Solar Loads
0 sqft
0
-
O'sgft
-
-
Wall Transmission
0 sqft
0
-
0 sqft
0
-
Roof Transmission
154 sqft
584
-
154 sqft
659
-
Window Transmission
0 sqft
0
-
0 sqft
0
-
Skylight Transmission
0 sqft
0
-
0 sqft
0
-
Door Loads
0 sqft
0
-
0 sqft
0
-
Floor Transmission
0 sqft
0
-
0 sqft
0
-
Partitions/Ceilings
0 sqft
0
-
0 sqft
0
-
Overhead Lighting
200 W
683
-
0 W
0
-
Electric Equipment
308 W
1051
-
0 W
0
-
People
0
0
0
0
0
0
Infiltration
-
0
0
-
0
0
Miscellaneous
-
20000
0
-
0
0
Safety Factor
0% / 0%
0
0
0%
0
0
»Total Zone Loads
-
22317
0
-
659
0'
Thermostat and Pulldown Adjustment
-
-7
0
-
-585
0
Plenum Wall Load
0%
0
-
0
0
-
Plenum Roof Load
0%
0
-
0
0
-
Plenum Lighting Load
0%
0
-
0
0
-
Ventilation Load
0 CFM
0
0
0 CFM
0
0
Supply Fan Load
1500 CFM
0
-
1500 CFM
0
-
» Total System Loads
' 22311
0
-
73
0
Central Cooling Coil
-
22311
0
-
0
0
Total Coil Loads'
-
. - • 22311
0
Key:
Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are c g loads
Block Load 4.15 Page 2 of 3
"'PERMIT COORD COOP
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: M12 -109 DATE: 07/13/12
PROJECT NAME: MEASUREMENT SYSTEMS INTERNATIONAL
SITE ADDRESS: 14240 INTERURBAN AV S, STE 200
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # after Permit Issued
DEPARTMENTS: �' 12 bit\ 1/Bai ing- Division Fire ' Preve�nti/on I�
Public Works
Structural
Planning Division
Permit Coordinator
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Incomplete
DUE DATE: 07/17/12
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES/THURS ROUTING:
Please Route lgtj
REVIEWER'S INITIALS:
Structural Review Required
No further Review Required
DATE:
APPROVALS OR CORRECTIONS:
DUE DATE: 08/14/12
Approved Approved with Conditions Jf Not Approved (attach comments)
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
Contractors or Tradespeople Pf ter Friendly Page
•
General /Specialty Contractor
A business registered as a construction contractor with Lai to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name PSR -HVAC 8 MECHANICAL SERVICES UBI No. 602811195
Phone 2063672500 Status Active
Address Po Box 27073 License No. PSRHVMS924JT
Suite /Apt. License Type Construction Contractor
City Seattle Effective Date 4/30/2008
State WA Expiration Date 4/30/2014
Zip 98165 Suspend Date
County King Specialty 1 General
Business Type Corporation Specialty 2 Unused
Parent Company
Other Associated Licenses
License
Name
Type
Specialty 1
Specialty 2
Effective
Date
Expiration
Date
Status
PUGETI`261CG
PUGET SOUND
REFRIGERATION
INC
Construction
Contractor
Air
Conditioning
Commercial /Industrial /Refrig2
/7/1974
2/1/1984
Archived
PUGETSR169CB
PUGET SOUND
REFRIGERATION
INC
Construction
Contractor
General
Unused
2/2/1984
12/31/2008
Inactive
PSR " "936JP
P S R
Construction
Contractor
General
Unused
4/17/200712/31
/2008
Re-
Licensed
Business Owner Information
Name
Role
Effective Date
Expiration Date
O'MALLEY, JAMES J
Member
04/30/2008
Amount
HOGERTY, REAGAN P
Member
04/30/2008
GL0488649702
O'DONNELL,STEPHEN 0
04/01/2013
04/30/2008
04/12/2012
RIST, STEVEN L
04/05/2012
04/30/2008
04/12/2012
Bond Information No records found for the previous 6 year period
Assignment of Savings Information
Page 1 of 2
Savings
Assignment of Savings Account Number
Effective Date
Release Date
Assignment Type
Impaired Date
Amount
Received Date
1
4/30/2008
Until
Released
Bond
$12,000.00
4/30/2008
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
6
Zurich
American Ins Co
GL0488649702
04/01/2012
04/01/2013
$1,000,000.00
04/05/2012
5
Zurich
American Ins Co
GL0488649701
04/01/2011
04/01/2012
$1,000,000.00
04/04/2011
4
ZURICH
AMERICAN INS
CO
GL0488649700
04/01/2010
04/01/2011
$1,000,000.00
04/05/2010
3
HARTFORD CAS
INS CO
37UUNN03345
04/01/2009
04/01/2010
$1,000,000.00
03/31/2009
2
HARTFORD FIRE
INS CO
37UUNN03345
06/01/2008
06/01/2009
$1,000,000.0006
/06/2008
https: // fortress .wa.gov /lni /bbip /Print.aspx
07/23/2012
Foster
Golf #.intrs
5 144th St
arfire Sports
Cnrnj)lex
Farrl -y Fun Center
R Bullvrink"e's
Restaurant
}Pacifir1
'64Fi oirteer
Meld
Southcenter
1:t1
California
SITE VIC\ITY
NTS
SITE INFO
ADDRESS:
OWNER:
PARCEL /TAX #
LEGAL:
14240 INTERURBAN AVE. S.
TUKWILA, WA 98168
BELLTOWN INVESTMENT PARTNER
3365901881
HILLMANS SEATTLE GARDEN TRS
POR OF LOT 1 & ALL OF LOTS 2
THRU 7 & POR ADJ IN SE 1/4 OF
SECTION 14 -23 -04 DAF - BEG SE
COR OF SAID LOT 7 TH NLY ALG
ELY LN 315 FT TO LFT BANK OF
DUWAMISH RIVER AS ORIGINALLY
PLATTED TH CONTG ON NLY PROD
OF SD ELY 220 FT M/L TO LFT
BANK AS EXISTED UNDER
SUPERIOR COURT CAUSE NO
81 -2- 05910 -4 TH WLY ALG SD
BANK TO AN INTSN WITH NELY
PROD OF SELY LN OF NWLY 72 FT
OF SD LOT 1 TH SWLY ALG SD LN
PROD 200 FT M/L TO LFT BANK
OF DUWAMISH RIVER AS PLATTED
IN ORIGINAL PLAT TH CONTG IN
SWLY DIRECTION ALG SELY LN OF
NWLY 72 FT OF SD LOT 1
DISTANCE OF 55 FT M/L TO SWLY
LN OF SD LOT 1 TH SELY ALG SD
LN TO INTSN WITH N MGN OF S
143RD ST FIRST AVE TH ELY ALG
SD MGN TO TPOB -TGW POR
FOSTER JOSEPH DC #39 BEING
POR OF ABANDONED PUGET.SOUND
ELECTRIC RR R/W IN THE SW 1/4
OF SE 1/4 OF SD SEC 14 SD RR
R/W BOUNDED ON NE BY MAULE
AVE ON SW BY A LN 20 FT NE OF
& PLT NELY MGN OF SR 181
UNDER REC #8905231113 ON THE
SEBYR /W #5 &ON THE NW BY
R/W #6 BOTH R/W DEFINED IN
QCD AUD FILE # 6557639 - TGW
VAC MAULE AVE ADJ TGW POR
VAC ST ADJ
Y PLA
SCALE
NOTE:
\NJ
2009 WASHI
\CTON STATE E
\ERGY CODE \OTES
GENERAL NOTES
1411.1: EQUIPMENT SHALL HAVE A MINIMUM PERFORMANCE AT THE SPECIFIED RATING
CONDITIONS NOT LESS THAN THE VALUES SHOWN IN TABLES 14 -1A THROUGH 14 -1G.
1411.4: PACKAGED ELECTRICAL EQUIPMENT PROVIDING BOTH HEATING AND COOLING WITH
A TOTAL COOLING CAPACITY GREATER THAN 20,000 BTU /H SHALL BE A HEAT PUMP.
1412.1: EACH SYSTEM SHALL BE PROVIDED WITH AT LEAST ONE TEMPERATURE CONTROL
DEVICE. EACH ZONE SHALL BE CONTROLLED BY INDIVIDUAL THERMOSTATIC CONTROL
RESPONDING TO TEMPERATURE WITHIN THE ZONE. AT A MINIMUM, EACH FLOOR OF A
BUILDING SHALL BE CONSIDERED AS A SEPARATE ZONE.
1412.4: HVAC SYSTEMS SHALL BE EQUIPPED WITH AUTOMATIC CONTROLS CAPABLE OF
ACCOMPLISHING A REDUCTION IN OF ENERGY USE THROUGH CONTROL SETBACK OR
EQUIPMENT SHUTDOWN DURING PERIODS OF NON -USE OR ALTERNATE USE OF THE
SPACES SERVED BY THE SYSTEM.
1412.4.1: OUTSIDE AIR INTAKES, EXHAUST OUTLETS AND RELIEF OUTLETS SERVING
CONDITIONED SPACES SHALL BE EQUIPPED WITH MOTORIZED DAMPERS WHICH CLOSE
AUTOMATTICALLY WHEN THE SYSTEM IS OFF OR UPON POWER FAILURE. STAIR SHAFT
AND ELEVATOR SHAFT SMOKE RELIEF DAMPERS SHALL REMAIN CLOSED UNTIL ACTIVATED
BY SMOKE DETECTION SYSTEM.
DAMPERS INSTALLED TO COMPLY WITH THIS SECTION, INCLUDING DAMPER INTEGRAL TO
HVAC EQUIPMENT, SHALL HAVE A MAXIMUM LEAKAGE REATE WHEN TESTED IN
ACCORDANCE WITH AMCA STANDARD 500 OF:
A. MOTORIZED DAMPERS: 10 CFM /SQ. FT. OF DAMPER AREA AT 1.0 IN. W.G.
B. NONMOTORIZED DAMPERS: 20 CFM/ SQ. FT. OF DAMPER AREA AT 1.0
INCH W.G., EXCEPT THAT FOR NONMOTORIZED DAMPER SMALLER THAN 24
INCHES IN EITHER DIMENSION: 40 CFM/ SQ.FT. OF DAMPER AREA AT 1.0
INCH W.G.
1412.4.1.1: DAMPERS FOR OUTDOOR AIR SUPPLY AND EXHAUST SHALL AUTOMATICALLY
SHUT WHEN THE SYSTEM IS NOT IN USE OR DURING BUILDING WARM -UP COOLDOWN
AND SETBACK.
1412.5: UNITARY AIR COOLED HEAT PUMPS SHALL INCLUDE MICROPROCESSOR
CONTROLS THAT MINIMIZE SUPPLEMENTAL HEAT USAGE DURING START -UP, SET -UP AND
DEFROST CONDITIONS.
1412.7: EACH AIR SUPPLY OUTLET OR AIR OR WATER TERMINAL DEVICE SHALL HAVE
MEANS FOR BALANCING, INCLUDING BUT NOT LIMITED T0, DAMPERS, TEMPERATURE AND
PRESSURE TEST CONNECTIONS AND BALANCING VALVES.
1413.1: AIR ECONOMIZERS SHALL BE CAPABLE OF AUTOMATICALLY MODULATING OUTSIDE
AND RETURN AIR DAMPERS TO PROVIDE 100% OF THE DESIGN SUPPLY AIR AS OUTSIDE
AIR TO REDUCE OR ELIMINATE THE NEED FOR MECHANICAL COOLING.
1413.3: AIR AND WATER ECONOMIZERS SHALL BE CAPABLE OF PROVIDING PARTIAL
COOLING EVEN WHEN ADDITIONAL MECHANICAL COOLING IS REQUIRED TO MEET THE
COOLING LOAD.
1414.1: DUCTWORK (OTHER THAN ROUND OR FLAT OVAL) WHICH IS DESIGNED TO
OPERATE AT PRESSURES ABOVE 1/2" WATER COLUMN STATIC PRESSURE SHALL BE
SEALED.
1414.1.2: ALL LOW PRESSURE DUCT SYSTEMS SHALL BE SEALED TO A LEAKAGE RATE
NOT TO EXCEED 6% OF THE FAN FLOW IF THE DUCT SYSTEM HAS MORE THAN 25%
DUCT SURFACE AREA LOCATED IN ANY UNCONDITIONED SPACE. THE LEAKAGE RATE
SHALL BE CONFIRMED THROUGH FIELD VERIFICATION AND DIAGNOSTIC TESTING, IN
ACCORDANCE WITH SMACNA DUCT LEAKAGE TEST PROCEDURES - 1985.
1414.1.3: DUCT WORK DESIGNED TO OPERATE IN EXCESS OF 3" WATER COLUMN SHALL
BE LEAK TESTED IN ACCORDANCE WITH SMACNA DUCT LEAKAGE TEST PROCEDURES -
1985.
1414.2: INSULATION OF SUPPLY, RETURN AND OUTSIDE AIR DUCTWORK SHALL MEET THE
REQUIREMENTS OF CHAPTER 13, DAMPERS SHALL COMPLY WITH SECTION 1412.4.1 BE
INSULATED IN ACCORDANCE WITH TABLE 14 -5.
1416.2.1: BUILDINGS WHICH REQUIRE A COMMISSIONING PROCESS IN ACCORDANCE WITH
WSEC SECTION 1416 AND SHALL INCLUDE:
1. COMMISSIONING PLAN
2. SYSTEMS TESTING AND BALANCING
3. HVAC EQUIPMENT AND CONTROLS FUNCTIONAL TESTING
4. SUPPORTING DOCUMENTATION IN THE FORM OF OPERATION AND MAINTENANCE
AND RECORD DOCUMENTS
5. COMMISSIONING REPORT.
1416.3.3: ALL HVAC SYSTEMS, EQUIPMENT AND CONTROLS SHALL BE TESTED TO
ENSURE THAT CONTROL DEVICES, COMPONENTS, EQUIPMENT AND SYSTEMS ARE CALIBRATED,
ADJUSTED AND OPERATE IN ACCORDANCE WITH SEQUENCES OF OPERATION PRESCRIBED IN
THE CONSTRUCTION DOCUMENTS. WRITTEN PROCEDURES WHICH CLEARLY DESCRIBE THE
INDIVIDUAL SYSTEMATIC TEST PROCEDURES, THE EXPECTED SYSTEMS' RESPONSE OR
ACCEPTANCE CRITERIA FOR EACH PROCEDURE, THE ACTUAL RESPONSE OR FINDINGS, AND
ANY PERTINENT DISCUSSION
1416.3.4.2: TRAINING OF THE MAINTENANCE STAFF FOR EACH EQUIPMENT TYPE AND /OR
SYSTEM SHALL INCLUDE AS A MINIMUM:
1. REVIEW OF SYSTEM DOCUMENTATION.
2. HANDS -ON DEMONSTRATION OF ALL NORMAL MAINTENANCE PROCEDURES,
NORMAL OPERATING MODES, AND ALL EMERGENCY SHUTDOWN AND START -UP
PROCEDURES.
3. TRAINING COMPLETION REPORT.
1416.3.5: THE COMMISSIONING REPORT SHALL BE COMPLETED AND PROVIDED TO THE
OWNER. THE COMMISSIONING REPORT SHALL INCLUDE:
1: COMPLETED FUNCTIONAL TEST FORMS INCLUDING MEASURABLE CRITERIA FOR
TEST ACCEPTANCE.
2: ISSUES LOG OF CORRECTED AND UNCORRECTED DEFICIENCIES WITH THE
ANTICIPATED DATE OF CORRECTION.
3: DEFERRED TESTS, WHICH CANNOT BE PERFORMED AT THE TIME OF REPORT
PREPARATION, WITH ANTICIPATED DATE OF COMPLETION.
4: RECORD OR PROGRESS AND COMPLETION OF OPERATOR TRAINING.
5: COMPLETED COMMISSIONING COMPLIANCE FORM.
1416.4: A COMMISSIONING, COMPLIANCE CHECKLIST SHALL BE SUBMITTED TO THE BUILDING
OFFICIAL UPON SUBSTANTIAL COMPLETION OF THE BUILDING. THE CHECKLIST SHALL BE
COMPLETED AND SIGNED BY THE BUILDING OWNER OR OWNER'S REPRESENTATIVE.
COMPLETION OF THE COMMISSIONING COMPLIANCE CHECKLIST IS DEEMED TO SATISFY THIS
REQUIREMENT.
1432.2.1: AIR SYSTEMS SERVING MULTIPLE ZONES SHALL HAVE CONTROLS TO
AUTOMATICALLY RESET SUPPLY AIR TEMPERATURE BY REPRESENTATIVE BUILDING LOADS OR
OUTSIDE AIR TEMPERATURE.
1435: SYSTEMS WHICH PROVIDE HEATING AND COOLING TO THE SAME ZONE
SIMULTANEOUSLY ARE PROHIBITED EXCEPT AS NOTED IN SECTION 1435.
1437: THREE PHASE ELECTRIC MOTORS NOT INCLUDED IN EQUIPMENT EFFICIENCY RATINGS
(LE., EXHAUST FANS, PUMPS, COOLING TOWER FANS) SHALL MEET MINIMUM EFFICIENCY
RATINGS LISTED IN WSEC TABLE 14 -4A & B.
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL L22 0 2012
City of vile,
BUILDING !SION
PROTECT ALL DUCT OPENINGS OF FIRE RATED ASSEMBLIES PER I.B.C. 716.
INSTALL COMBINATION SMOKE FIRE DAMPERS AT ALL PENETRATIONS OF SHAFT
ENCLOSURES PER I.B.C. SECTION 707.
INSTALL COMBINATION SMOKE FIRE DAMPERS AT ALL PENETRATIONS OF FIRE PARTITIONS,
FIRE WALLS, FIRE BARRIERS AND SMOKE PARTITIONS PER I.B.C. CHAPTER 7.
ALL FIRE DAMPERS SHALL BE DYNAMIC TYPE, U.L. 555 RATED. ALL CEILING RADIATION
DAMPERS SHALL BE U.L. 555C RATED. ALL COMBINATION SMOKE FIRE DAMPERS SHALL
BE U.L. 555S RATED.
INSTALL SEISMIC BRACING FOR ALL DUCTWORK, EQUIPMENT AND PIPING PER I.B.C.
REQUIREMENTS.
INSTALL ALL PIPING ON ROOM SIDE OF BUILDING INSULATION.
MECHANICAL DRAWINGS ARE DIAGRAMMATIC IN NATURE, AND DO NOT NECESSARILY
REFLECT EVERY REQUIRED OFF -SET, FITTING OR ACCESSORY.
COORDINATE INSTALLATION OF MECHANICAL SYSTEMS WITH BUILDING STRUCTURE AND
ALL OTHER TRADES.
THE MECHANICAL CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BEGINNING WORK IN
ORDER TO OBSERVE EXISTING CONDITIONS. VERIFY EXACT SIZE, LOCATION AND
CONDITION OF ALL EXISTING SYSTEMS, DUCTS, PIPES, UTILITIES AND BUILDING
STRUCTURE.
VERIFY VOLTAGES AT THE SITE PRIOR TO ORDERING ANY EQUIPMENT.
ALL MECHANICAL EQUIPMENT LOCATED IN CEILING CAVITIES THAT REQUIRE ELECTRICAL
CONNECTION SHALL HAVE AN 8 -1/2 "x11" LAMINATED SIGN PERMANENTLY MOUNTED ON
THE ELECTRICAL ENCLOSURES THAT INDICATES: "THIS EQUIPMENT MUST HAVE A MINIMUM
ACCESS OF 36" (LESS THAN 460V) AND 42" (460V AND ABOVE) ". NO TRADE SHALL
BLOCK THIS SPACE EVEN IF SHOWN ON THE DRAWINGS. INSTALL SIGN PRIOR TO
INSTALLATION OF EQUIPMENT.
ALL MECHANICAL EQUIPMENT THAT REQUIRES ACCESS FOR COIL PULL, FILTER CHANGE,
MOTOR CHANGE, COMPRESSOR CHANGE, LUBRICATION, SHEAVE AND BELT CHANGE, FAN
CHANGE OUT, ETC. SHALL HAVE AN 8 -1/2 "x11" LAMINATED SIGN PERMANENTLY MOUNTED
ON THE EQUIPMENT ACCESS PANELS THAT INDICATES "THIS EQUIPMENT MUST HAVE A
MINIMUM ACCESS OF 36 ". NO TRADE SHALL BLOCK THIS SPACE.
DUCTLESS SPLIT SYSTEM EQUIPMENT SCHEDULE
MARK
LOCATION
COOLING CAPACITY
REFRIGERATION CONNECTION
ELECTRICAL
OPER. WEIGHT
SOUND (DBA)
BASIS OF DESIGN
SERVES
REM ARKS
BTUH
REFRIGERANT
CFM
LIQUID
SUCTION
VOLT /PHASE
MOCP
MCA
SEER
INDOOR
OUTDOOR
INDOOR
OUTDOOR
MANUFACTURER
MODEL
AC- 1 /CU -1
SERVER ROOM
24,000
R410A
659
1/4
5/8
208 -230/1
20
11.5
17.5
31
88
48
56
FUJITSU
24CL
SERVER ROOM
1,2,3
1) SELF CONTAINED CONTROLS. PROVIDE PERMANENT MOUNT FOR WIRED THERMOSTAT
2) PUMP CONDENSATE TO APPROVED LOCATION
3) OUTDOOR UNIT (CU -1 LOCATED ON TREATED, GALV. SHEETMETAL CAPPED ROOF SLEEPERS. MOUNT SLEEPERS ON APPROVED
ROOF PADS
AREA OF WORK
SEPARATE PERMIT
REQUIRED FOR:
% ❑ Mechanical
Electrical
14plumbing
10Gas Piping
City of Tukwila
BURPING DIVISION
No changes shall lelmade to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review foes.
LEGEND
~O
I
l
11
OFD
r20051
129ft2
SUPPLY DIFFUSER
RETURN GRILLE
EXHAUST FAN
VOLUME DAMPER
CAP
FLEX DUCT
DIRECTION OF AIRFLOW
THERMOSTAT
POINT OF CONNECTION
DEMO
MOTORIZED DAMPER
FIRE DAMPER
ROOM
NUMBER
AREA
OF ROOM
TYPE
AND NOTE
[R] _
[N] _
[E] _
SIZE
\--CUBIC FEET
PER MINUTE
r
RAG
12x2
FILE COPY
Permit No.. i1AV2 - -1V °1
plan review approval is to errors and omissions.
Approval of construction documents does not authorise
the violation of any adopted axle or ordinance. Receipt
of approve! Field !edged:
RELOCATED
NEW
EXISTING
City Of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
UL 13
2012
J
PERMIT CENTER
MlLHO
�
NOTE:
r
0
U
ro
U
(3)
ro
ro
0
ro
a
a)
■. U
T
4--
CS
0
co
1
3132 N.E. 133 ST
Seattle, Washington 98125 -4423
PO Box 27073
Seattle, Washington 98165 -1473
(206) 367-2500
Fax (206) 368 -6856
PSRHVMS924JT
D �
Z
W Z
w
O
D
Z °
Q
~
W W W > ct
= W
ct
W ?�
O w
UZ
NTERNATIONAL
FOR MEASUREMENT SYSTEMS
z
0
J
w
z
w
ILA, WA 98168
COPYRIGHT NOTICE
THIS LAYOUT /DESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
General Notes 1
11 "x17" SHEET SIZE
NTS.
PERMIT SET
7/11/12
Revision /Issue
Drawn By
P. GOTO
Date,
1
Date
11 JULY 2012
Lead Tech
Engineered By
Date
Project
P4729
Project Manager
SIN
sale
VARIE
[1] PROVIDE RUN -OUT DUCT AND ER
FLEXIBLE CONNECTION SAME SIZE S
AS DIFFUSER NECK DIAMETER.
(FIELD VERIFY BEST LOCATION)
0'
Sheet
M 0.0
di
•
./
,/
SITE N
/
AP
1
177' -10"
►
1 /32 " =1'
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL 2 0 2012
City of Tukwila
BUILDING DIVISION
1
►
1
1
►
1
1
1
►
1
1
►
►
1
1
1
1
►
1
►
RECEIVED
CITY OF TUKWILA
JUL 13 2012
PERMIT CENTER
3132 N.E. 133 ST
Seattle, Washington 98125 -4423
PO Box 27073
Seattle, Washington 98165 -1473
(206) 367 -2500
Fax (206) 368 -6856
PSRHVMS924JT
J
Q
Z
0
E -
H
Z o
Z n 0
N
D W w
H
I- m =
2 Z 0
0 Z
0- °o
%I u m co
2 � w
�'
WW
W
I--Wvz
- > am
W Ce ce
iii L H
Z
cp
d-
ill u) V'
Z
FOR MEA
TUKWILA, WA 98168
COPYRIGHT NOTICE
THIS LAYOUT /DESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
General Notes
1. 11 "x17" SHEET SIZE
NTS.
Date
11 JULY 2012
Lead Tech
Engineered By
Date
1
PERMIT SET
7/11/12
No.
Revision /Issue
Date
Drawn By
P. GOTO
Date
11 JULY 2012
Lead Tech
Engineered By
Date
Project
P4729
Project Manager
N. SINGER
Scale
1 /32 " =1'0"
Sheet
M 0.1
KEY PLAN
SCALE
NOTE:
AREA OF WORK
1
#100
RSC
2 -3
\
4 -60
ZD
�0/ 3A \\
'� �� 2 -3A \
� 4-48 )
i TQ'
\ .
0
\
\O!
J \
2D
ZD
ZD
3B
�RSC>
2 -3
//‘,
1
4B
ZD
RSC
2 -4
ZD
3C
\O�
t \
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL 2 0 2012
City of Tukwila
BUILDING DIVISION
ZD
3D \\
\
\
\o
. \
1
•
RSC
2 -14
NO/
o
/ \
2 -4A
PARTIAL 2ND FLOOR
DE\40 PLA\
2 -14B
BPD
\
■
i A/C 3
2 -14B /
BPD
4A
ZD
- - - -- I - __
3/16 " =1'
DEMO NOTES
1) RELOCATE (1) SUPPLY AIR DIFFUSER OUT OF NEW SERVER ROOM
AND INTO ADJACENT AREA.
M(i (o'
CITYECEIVED
OF TUKWILA
JUL 1 3 2012
PERMIT CENTER
l
• Mooing=
1
3132 N.E. 133 ST
Seattle, Washington 98125 -4423
PO Box 27073
Seattle, Washington 98165 -1473
(206) 367-2500
Fax (206) 368 -6856
` PSRHVMS924JT
z
a. J I— Oz
w�
00
ct0
O Q
O D
J w
ce
zw
N U)
J
aw
I..V
0
z
0
i-
<
z
w
z
FOR MEASUREMENT SYSTEMS
CO
z
0
5
m
w
1-
z
w
u_
O
0
N
w
1-
5
1-
0)
w
z
m
Z
TUKWILA, WA 98168
COPYRIGHT NOTICE
THIS LAYOUT /DESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
l General Notes 1
1. 11"x17" SHEET SIZE
NTS.
Date
11 JULY 2012
Lead Tech
Engineered By
Date
1
PERMIT SET
7/11/12
`No.
Revision /Issue
Date,
Drawn By
P. GOTO
Date
11 JULY 2012
Lead Tech
Engineered By
Date
Project
P4729
Project Manager
N. SINGER
Scale
3/16 " =1'0"
Sheet
M 1.0
KEY PLAN
SCALE
NOTE:
AREA OF WORK
1— 1
u \
00J
�R C)
2 -3
'0
I N.
ZD
3A N\\
2 -3A
4 -48
4 -60
4 2 -3B
I
1
AC -1
2D
ZD
/'
2-4B
4-41 lei
4B
ZD
3B
7
it
/\\Allim
RSC
2 -3 )
2 -3C
4 -59
3C
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL 2 0 2012
City of Tukwila
BUILDING DIVISION
ZD
3D \o
REFRIGERANT PIPING \
UP TO ROOF
\
PIPE CONDENSATE TO
NEAREST APPROVED LOCATIN
1
■
1
i
6 4-49
T 2 -2D
ZD
RSC )
2 -4
'O
/
I0.
•
RSC
2 -14
O
. .
I '
2 -4A
4 -43
PARTIAL 2ND FLOOR
HVAC PLAN
2 -14B
BPD
(RO13
\
2 -14B �i
BPD
JA/C3
- - - - - - - - - . ► _ 1
4A
ZD
N.
-r
3/16 " =1'
2 -3D
4 -58
-
HVAC NOTES
1) INSTALL NEW 2 TON COOLING ONLY DUCTLESS SPLIT SYSTEM TO
NEW SERVER ROOM.
2) INSTALL REFRIGERANT PIPING TO CONDENSING UNIT ON ROOF.
3) PUMP CONDENSATE TO NEAREST APPROVED DISPOSAL LOCATION.
4) MOUNT FACTORY WIRELESS THERMOSTAT ON WALL OF NEW
SERVER ROOM.
5) NEW UNIT CONFORMS WITH SECTION 1344 OF THE 2009
WASHINGON STATE ENERGY CODE EXCEPTION 9. UNIT IS MORE THAN
15% OVER MINIMUM EFFICIENCY IN TABLE 14-1A, AND USED FOR A
DEDICATED SERVER ROOM.
Mir -ia�
c r1 OflUKWIIA
JUL 1 32012
PERMIT CENTER
3132 N.E. 133 ST
Seattle, Washington 98125 -4423
PO Box 27073
Seattle, Washington 98165 -1473
(206) 367 -2500
Fax (206) 368 -6856
PSRHVMS924JT
Z
J
a_ ~
0
Q
_0
oC O
0 C
0
-I W
LL >
0Q
Z W
N (/)
J
17(
Z
LL
0
FOR MEASUREMENT SYSTEMS
m
c9
z
0
m
w
1-
z
w
TUKWILA, WA 98168
COPYRIGHT NOTICE
THIS LAYOUT /DESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
General Notes 1
1. 11 "x17" SHEET SIZE
NTS.
Date
11 JULY 2012
Lead Tech
Engineered By
Date
1
PERMIT SET
7/11/12
`No.
Revision /Issue
Date
Drawn By
P. GOTO
Date
11 JULY 2012
Lead Tech
Engineered By
Date
Project
P4729
Project Manager
N. SINGER
Scale
3/16 " =1'
Sheet
M 2.0
J
KEY PLAN
SCALE
NOTE:
AREA OF WORK
NEW SLEEPERS
ROOFED IN MY OTHERS
CU -1
REFRIGERANT LINES
UP FROM 2ND FLOOR
Unit #B -3
EXISTING UNIT
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL 2 0 2012
City of Tukwila
BUILDING DIVISION
PARTIAL ROOF
HVAC PLA
3/16 " =1'
ROOF NOTES
1) INSTALL NEW WOOD SLEEPERS WITH SHEET METAL CAPS ON ROOF.
2) ROOF SLEEPERS ONTO ROOF (BY OTHERS)
3) INSTALL DOG HOUSE AROUND REFRIGERANT PIPING PENETRATION
IN ROOF.
4) ROOF IN DOGHOUSE (BY OTHERS)
R CEiVEi� ,.
CITY' F TUPNVILA
JUL 13 2012
PERMIT CENTER
r
ro
ft,
U
V
N
CZ
til
•
3132 N.E. 133 ST
Seattle, Washington 98125 -4423
PO Box 27073
Seattle, Washington 98165 -1473
(206) 367 -2500
Fax (206) 368 -6856
` PSRHVMS924JT
Z F.
Q —
^J Z
2
<0
>O
OW
O>
L.1.
_I W
QC!)
I—
w
1..� Z
J
z
0
1-
Q
z
cc
w
z
FOR MEASUREMENT SYSTEMS
0
0
N
W
H
CO co
�_
Z
J
5
mW
W z
w
wa
o ZZ
Q m
C4
�W
E-
Z
0
N
TUKWILA, WA 98168
COPYRIGHT NOTICE
THIS LAYOUT /DESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
General Notes
1. 11 "x17" SHEET SIZE
NTS.
Date
11 JULY 2012
Lead Tech
Engineered By
Date
1
PERMIT SET
7/11/12
No.
Revision /Issue
Date
Drawn By
P. GOTO
Date
11 JULY 2012
Lead Tech
Engineered By
Date
Project
P4729
Sheet
M 2.1
Project Manager
N. SINGER
Scale
3/16 " =1'0"
28'
26' -4"
A
24'
27'
EXISTING 3'6" PARAPET
AC -1
-s"
v
16
Project Manager
EXISTING 3'6" PARAPET
1 1
1 1
M 3.0
1
1
PERMIT SET
n
1 I
I I
Revision /Issue
Date,
•
' 26'
-4" 2f
EXISTING ROOF
_,I_b
24
' 15
i
„
-6
1
I
I
L
EXISTING ROOF'
NORTH ELEVATION
3/32 " =1'
AC -1
1
EXISTING 3'6" PARAPET
EXISTING ROOF
EXISTING GRADE
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL 2 0 2012
City of Tukwila
BUILDING DIVISION
EXISTING 3'6" PARAPET
EXISTING ROOF'
L _1
15' -6"
6'
27'
6"
EXISTING GRADE
WEST ELEVATION
3/32 " =1'
ti 1 to
Rt CEIV
CITY OF TO
JUL 1 3 2012
PERMIT CENTER
›.
rO = • ro
O E
L)lrDI O
• I— .c V
C -2
O
ra C/) N
V
t 8
a) I)
•
: U)
wcrt
4-
Ul •—
a.=
CO
3132 N.E. 133 ST
Seattle, Washington 98125 -4423
PO Box 27073
Seattle, Washington 98165 -1473
(206) 367 -2500
Fax (206) 368 -6856
PSRHVMS924JT
J
J
z
0
z
1-
z
V)
U)
(1)
z
w
w
v,
Cw
NG
I.L
0
m
z
0
5
w
z
w
a
Q
O
0
N
w
5
m
1-
0
w
z
w
z
w
1-
z
O
N
TUKWILA, WA 98168
COPYRIGHT NOTICE
THIS LAYOUT /DESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
, General Notes \
1. 11 "x17" SHEET SIZE
NTS.
Sheet
Project Manager
N. SINGER
M 3.0
Scale
1
PERMIT SET
7/11/12
`No.
Revision /Issue
Date,
Drawn By
P. GOTO
Date
11 JULY 2012
Lead Tech
Engineered By
Date
Project
P4729
Sheet
Project Manager
N. SINGER
M 3.0
Scale
3/32 " =1'0"