HomeMy WebLinkAboutPermit M12-177 - TUKWILA FIRE PUMP ROOMTUKWILA FIRE PUMP ROOM
5795 S 130 PL
M12 -177
City oil- Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 -431 -3670
Inspection Request Line: 206- 431 -2451
Web site: http: / /www.TukwilaWA.gov
MECHANICAL PERMIT
Parcel No.: 0001400005
Address: 5795 S 130 PL TUKW
Project Name: TUKWILA FIRE PUMP ROOM
Permit Number: M12 -177
Issue Date: 12/18/2012
Permit Expires On: 06/16/2013
Owner:
Name: BAKER COMMODITIES INC
Address: 4020 BANDINI BLVD , LOS ANGELES CA 90023
Contact Person:
Name: BILL LIEBSACK
Address: 1400 AIRPORT WAY S #202 , SEATTLE WA 98134
Email:
Contractor:
Name: UNITED SYSTEMS MECHANICAL LLC
Address: 1400 AIRPORT WY S #202 , SEATTLE WA 98134
Contractor License No: UNITESM962QA
Phone: 206 604 -2168
Phone: 206 933 -6036
Expiration Date: 11/01/2014
DESCRIPTION OF WORK:
INSTALL VENTILATION FAN / HVAC
Value of Mechanical: $4,000.00
Type of Fire Protection: UNKNOWN
Electrical Service Provided by:
Permit Center Authorized Signature:
I hereby certify that I have read and ex
governing this work will be complied
Fees Collected: $233.13
International Mechanical Code Edition: 2009
Date:
this permit and know the same to be true and correct. All provisions of law and ordinances
ether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign and obtain this mechanical permit and agree to the conditions on the
back of this permit.
Signature:. pi _
Print Name: (4 t 1 Pi S 3 c/ G
Date: `
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
rinr IM( -4/1n
M12 -177 Printart• 17- 1R -2n19
PERMIT CONDITIONS
Permit No. M12-177
1: ** *BUILDING DEPARTMENT CONDITIONS * **
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431 - 3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
6: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap the sanitary
sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks, wells, and other
excavations. Final inspection approval will be determined by the building inspector based on satisfactory completion of
this requirement.
7: Manufacturers installation instructions shall be available on the job site at the time of inspection.
8: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the City of Tukwila
Building Department (206- 431- 3670).
9: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206- 431 - 3670).
10: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
rinr. IM(: -4/1(1
M12 -177 Printarl• 17 -1R -7017
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd . Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Mechanical Permit No. ni 1 a ' 11:4-
Project No.
'Date Application Accepted:
Date Application Expires: 'l7
(For office use onit)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
* *please print **
SITE LOCATION
r(�/� King Co Assessor's Tax No.: O 1 ^ 0405
Site Address: J� 5 S 61, ) (-�C� e 1 ace Suite Number: Floor:
Tenant Name: kw i l3 fore QU tie' 660m New Tenant: ❑ Yes
PROPERTY OWNER
Name: e I (l l., eb7 a
c„, 'e
Address: (.ILCU te,t roO� 2.,0 9,
�a yv
Name:
Phone:
Email:
Address:
City:
State:
Zip:
CONTACT PERSON - person receiving all project
communication
Name: e I (l l., eb7 a
c„, 'e
Address: (.ILCU te,t roO� 2.,0 9,
�a yv
,
City: 5 eat} -1 State: Zip: c I Jki
W v
Phone:
Email:
0
MECHANICAL CONTRACTOR INFORMATION
�
Company Name: u nr ,Q 5 5 0 f kC P
f /5tem
Address: (ItR7 hire 4D� 5Oc,( t
City: S State: Zip:
e��l e cola a,st3y
Phone: •7 v /'_ Cj� Q &O ax:
`x1J,c-65.16(e
Contr Reegg+No..' lDate: f C „ 1 , �1 ojt-
�f R 1 6 v� `�C
Tukwila Business License No.:
Valuation of project (contractor's bid price): $ — 0 0 /
Describe the scope of work in detail:
ItAgW\ VtAil ktlb°1/1 1/1/
Use: Residential: New
Commercial: New
Fuel Type: Electric Gas
❑
Replacement
Replacement
❑
E
Other:
H:\ApplicationsTorms- Applications On Line \2011 Applications\Mechanical Permit Application Revised 8 -9 -1 I.docx
Revised: August 2011
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Furnace >100k btu
Floor furnace
Suspended/wall /floor
mounted heater
I
Appliance vent
`
Repair or addition to
heat/refrig /cooling
system
Air handling unit
<10,000 cfm
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
I
connected to single duct
`
Ventilation system
Hood and duct
Incinerator — domestic
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
Thermostat
Wood /gas stove
Emergency generator
Other mechanical
equipment
Boiler /Compressor
Qty
0 -3 hp /100,000 btu
3 -15 hp /500,000 btu
15 -30 hp /1,000,000 btu
30 -50 hp /1,750,000 btu
50+ hp /1,750,000 btu
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING O NER R A HO IZED AG NT:
Signature: 0 LV,6' Date: j 1 lJ • Print Name: ( 1 L1 eb $ ck Day Telephone: 3, 3(p '6(f n16,
Mailing Address: 1400 A-I 1 (?or -t, W91 SOf 4 9,v,)'+ 5e3 t 1 e i U& 15
City State Zip
H. \Applications\Forms- Applications On Line \201 I Applications\Mechanical Permit Application Revised 8-9-11 docx
Revised August 2011
bh
Page 2of2
1
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206 - 431 -3670
Fax: 206 - 431 -3665
Web site: http: / /www.TukwilaWA.gov
RECEIPT
Parcel No.: 0001400005 Permit Number: M12 -177
Address: 5795 S 130 PL TUKW Status: PENDING
Suite No: Applied Date: 11/14/2012
Applicant: TUKWILA FIRE PUMP ROOM Issue Date:
Receipt No.: R12 -03116
Payment Amount: $233.13
Initials: TLS Payment Date: 11/14/2012 02:16 PM
User ID: 1670 Balance: $0.00
Payee: UNITED SYSTEMS MECHANICAL LLC
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 21004 233.13
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
MECHANICAL - NONRES
PLAN CHECK - NONRES
000.322.102.00.00 186.50
000.345.830 46.63
Total: $233.13
doc: Receiot -06 Printed: 11 -14 -2012
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 PP'.. (206)431 -3670 -
Permit Inspection Request Line (206) 431 -2451
Project:
TiIZb.)rLA FIQF
t (�U
Type of.lnJ
i' ✓k
f
Addres :
5?-195 c a b
L
Date Called:
Special Instructions:
Date Wanted .
--
a.m.
4.157t
Requester:
Phone No..
on
.f) ti, --
(j�
`4! A -
r�
'' / --
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
U) r9prrn;vCD - NDP /hpd
? rT: tc ,1r. - i +t) -
� Q lu11,
nt004..."A9 -k' % t— i'I J
Ins ector:
REIN PECTIO
t
Date:
N FEE REQUI2ED. Prior td next inspection. fee must be
�paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection:_,.
UNITED
SYSTEMS
1
MECHANICAL, LLC
CONTRACTOR REG IUNITESM962QA
• HEATING & AIR CONDITIONING
• CONTROLS
• TEST, ADJUST, & BALANCE
• SERVICE & MAINTENANCE
♦ ENERGY MANAGEMENT
• ENERGY SAVINGS PROGRAMS
1400 AIRPORT WAY SOUTH, SUITE 202 • SEATTLE, WASHINGTON 98134
PHONE (206) 933 -6036 FAX (206) 937 -3084
November 7, 2012
Mac McNamara
Controlled Environments Construction
1542 Edinger Avenue, Ste. E
Tustin, CA 92780
RE: Tukwila Fire Pump Ventilation
REVIEWED FOR -
CODE COMPLIANCE
APPROVED pep. Prle copy
NOV 2 8 212
City of Tukwila
BUILDING DIVISION
The following is our HVAC proposal for the above referenced project based on the information in your email to
Chuck Grouws dated 10/18/12.
WE INCLUDE:
♦ Furnish and install one (1) in -line cabinet exhaust fan attached to the structure inside the pump house.
♦ Furnish and install one (1) in -take weather louver with motorized low- leakage damper.
♦ Furnish and install exhaust ducting from cabinet fan to one (1) vertical mount exhaust damper termination in the
exterior wall. Wall exhaust penetration will have a hooded cover to prevent rain entering the building.
♦ Furnish and install a bird screen frame over the inlet of the cabinet fan.
• Hole Cutting.
♦ City of Tukwila mechanical permit.
♦ Mechanical design engineering and drawing.
♦ Washington State Sales Tax.
• Standard one year warranty.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS Ar 1tJIN htw ntvV V. t t ,�...,� • - - -_ _
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON. AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER R��IZED AG�NT:
Signature: �VI,C.I/
Print Name:
Date:
'Silt Lj, th$G7 Day Telephone: 2,062 4'6tf nit'
Mailing Address: [ 400 f'Cll �%Oi"'ti w!S Sc a �0)' �1ra le Oa U) 5 7
1 City State Zip I
H:\Applications'Forms- Applications On Line \20I I ApplicationsVvfechanical Permit Application Revised 8-9.1 I .dots
CITY OF TUK1'1,9! -1':.
NOV 1 4 2012
PERMIT CENTER
VU2H1I
°PERMir COORD coPit
PLAN REVIEW /ROUTING SLIP
ACTIVITY NUMBER: M12 -177 DATE: 11/14/12
PROJECT NAME: TUKWILA FIRE PUMP ROOM
SITE ADDRESS: 5795 S 130 PL
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # after Permit Issued
DEPARTMENTS:
�C
4-uTcling' Division
Public Works
- ii-
°Are Prevention
Structural
Planning Division
❑ Permit Coordinator ❑
DETERMINATION OF COMPLETENESS: (Tues., Thurs.) DUE DATE: 11/15/12
Complete g
Incomplete ❑
Not Applicable ❑
Comments:
Perm& Center Use Only
INCOMPLETE LETTER MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
LETTER OF COMPLETENESS MAILED:
TUESITHURS ROUTING:
Please Route
REVIEWER'S INITIALS: DATE:
Structural Review Required ❑ No further Review Required ❑
APPROVALS OR CORRECTIONS:
DUE DATE: 12/13/12
Approved ❑ Approved with Conditions Not Not Approved (attach comments) ❑
Notation:
REVIEWER'S INITIALS:
DATE:
PermitCenterUse Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Bldg ❑ Fire ❑
Ping ❑ PW ❑
Staff Initials:
Contractors or Tradespeople Printer Friendly Page
General /Specialty Contractor
A business registered as a construction contractor with LEI to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name
Phone
Address
Suite /Apt.
City
State
Zip
County
Business Type
Parent Company
UNITED SYSTEMS MECHANICAL LLC
2069336036
1400 Airport Way S #202
Seattle
WA
98134
King
Corporation
UBI No.
Status
License No.
License Type
Effective Date
Expiration Date
Suspend Date
Specialty 1
Specialty 2
602439405
Active
UNITESM962QA
Construction Contractor
11/1/2004
11/1/2014
General
Unused
Business Owner Information
Name
Role
Effective Date
Expiration Date
SARGEANT, LESLIE E
President
11/01/2004
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
3
American States
Insurance Co
32s205383
04/20/2012
Until Cancelled
$12,000.00
05/07/2012
2
American States
Insurance Co
6455227
11/01/2006
04/20/2012
$12,000.00
11/01/2006
1
AM STATES INS
6315649
11/01/2004
Until Cancelled
12/28/2006
$6,000.0011
/13/2006
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
6
Scottsdale lns
BCS0026166
11/01/2011
11/01/2013
$1,000,000.00
10/29/2012
5
LEXINGTON I INS
4392517801
11/01/2009
11/01/2011
$1,000,000.00
10/27/2010
4
CEOXINGTON INS
8762281
11/01/2007
11/01/2009
$1,000,000.00
10/30/2008
3
NAVIGATORS
INSURANCE
COMPANY
SE06CGL00572000
11/01/2006
11/01/2007
$1,000,000.00
11/01/2006
Summons /Complaint Information No unsatisfied complaints on file within prior 6 year period
Warrant Information No unsatisfied warrants on file within prior 6 year period
Infractions /Citations Information No records found for the previous 6 year period
https://fortress.wa.gov/lni/bbip/Print.aspx
12/18/2012
-40x12 EXHAUST BDD. MNT AS HIGH AS
POSSIBLE IN WALL. FLD COORDINATE:
UNITED '
SYSTEMS
MECHANI 1 CAA— 1.-1—
40x12 -SM'
HANG EF -1 AS HIGH AS POSSIBLE IN . ROOM
WITH ! " ALL - THREAD AND RUBBER
ISOLATORS. FLD DETAIL EXACT LOCATION.
SEP RAT
A FULL SERVICE COMMERCIAL
HVAC CONTRACTOR
1400 AIRPORT WAY SOUTH
SUITE 202
SEATTLE, WASHINGTON 98134
(206)933 - 6036 /FAX 937 -3084
SM CAN ON BACK OF. FAN WITH EXPANDED
METAL GRILLE. FLD MATCH FAN OPENING SIZE.-
REVIEWED FOR
CODE COMPLIANCE
APPROVED
NOV 2 8 2012
City of ila
SUILDIN ISION
EXPIRES 05 -09 -2014.
REVISIONS
DATE.
DISCRIPTION
SLSM CAN ` ON BACK OF . LOUVER.
44x34 INTAKE LOUVER. MNT AS HIGH AS
POSSIBLE IN WALL. FLD COORDINATE.
-24x24-SM SLEEVE AND
MOTORIZED DAMPER.'.:
EXHAUST 1 SUPPLY FAN SCHEDULE
UNIT ID AREA OF SERVICE MAKE & MODEL TYPE CFM ESP VOLT /PH RPM WATTS / AMPS WT / LBS SOUND Dba NOTES
EF -1 PUMP HOUSE GREENHECK #CSP -A3600 INLINE 3150 0.4 120 / 1: 830 1330 / 14.2 130. 46. :, 1, 2'
NOTES:
1. POWER WIRING, MOTOR STARTERS AND DISCONNECTS BY E.C.
2. CONTROL FAN WITH INTERLOCK TO PUMP. FAN TO RUN WHEN PUMP` IS RUNNING. BY OTHERS.
PTl pprovall is subject to errors and omissions.
of construction documents door not c iSSIO 3
VIC . =:)i .tion of any adopted code ar ordinance. Recc pt
of approved Field Copy and ►• • - irsa�dcnovi+ledgad:
ADDRESS OF PROJECT
5795` SOUTH '130TH PLACE
TUKWILA WASHINGTON
PERMIT
REQUIRED FOR:
[ Mechanical
D Electrical
Plumbing
Gas Piping
City C of- Tukw la
Riil R °3'y6 4 tkR1
LEGAL DISCRIPTION
BROWNELL C E -D C # 41 POR OF D C LY W OF N P R/W & NLY OF A
LN BEG 1410.74 FT S ' & 2143.89 FT W OF NE COR D C TH W 1715.29
FT` TO PT 1 FT W OF WLY RAIL OF N P R/W TH N 27 -21 -30 W 779.68
FT TO TRUE BEG OF THIS LIMITING LN BEARING S 69-22-40 W TGW POR
BEG 1510.74 FT S & 2143.89 FT W OF NE COR DC TH W 1715.29 FT
TO PT 1 FT W OF MOST WLY RAIL OF NP RY TN N 27 -21 -30 W . 779.68
n. TH S 69 -22 -40 W 47.44 FT TO TRUE BEG TH S 69 -22 -40 W 544
FT TO E BANK OF DUWAMISH RIVER TH SELY ALG SD E BANK TO WLY LN
OF NP R/W TH NWLY ALG SD R/W 401.07 FT M/L TO TRUE BEG
VICINITY MAP
RECtivto
ITV OF TUKtkiii_.'