HomeMy WebLinkAboutPermit D13-257 - J CREW - TENANT IMPROVEMENTJ CREW
535 SOUTHCENTER MALL
EXPIRED
06/07/2014
D13-257
City oftukwila •
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206.431-3670
Inspection Request Line: 206-431-2451
Web site: http://www.TukwilaWA.gov
DEVELOPMENT PERMIT
Parcel No.: 9202470010
Address: 535 SOUTHCENTER MALL TUKW
Suite No:
Project Name: J CREW
Permit Number: D13-257
Issue Date: 10/31/2013
Permit Expires On: 04/29/2014
Owner:
Name: WESTFIELD PROPERTY TAX DEPT
Address: PO BOX 130940 , CARLSBAD, CA 92013
Contact Person:
Name: GARY PALMER
Address: PO BOX 23534 , EUGENE, OR 98492
Contractor:
Name: J D BUILDERS
Address: PO BOX 2458 , CAPISTRANO BEACH, CA 98624
Contractor License No: JDBUI**037JLT
Lender:
Name: SELF FUNDED - J CREW
Address: 770 BROADWAY, 14TH FLOOR , NEW YORK, NY 10003
Phone: 541-603-4191
Phone: 714 240-1340
Expiration Date: 03/01/2015
DESCRIPTION OF WORK:
INSTALL RACKING TYPICAL TO TENANT IMPROVEMENT INCLUDING MOBILE AND FIXED RACKING SYSTEMS.
Value of Construction: $0.00 Fees Collected: $476.90
Type of Fire Protection: SPRINKLERS International Building Code Edition: 2012
Type of Construction: III -B Occupancy per IBC: 0019
Electrical Service Provided by: PUGET SOUND ENERGY
**continued on next page**
doc: IBC -7/10
D13-257 Printed: 10-31-2013
Public Works Activities:
7,hannelization / Striping: N
:.urb Cut / Access / Sidewalk / CSS: N
?ire Loop Hydrant:
Flood Control Zone:
iauling:
:,and Altering:
i,andscape Irrigation:
'loving Oversize Load:
N
N
Number: 0 Size (Inches): 0
Start Time:
Volumes: Cut 0 c.y.
Start Time:
End Time:
Fill 0 c.y.
End Time:
Sanitary Side Sewer:
Sewer Main Extension: Private: Public:
Storm Drainage:
Street Use: Profit: N Non -Profit: N
Nater Main Extension: Private: Public:
Nater Meter: N
Permit Center Authorized Signature:
Date:/�D 31-13
IS
[ hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
rhe granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
:onstruction or the perform ce of work. I am authorized to sign and obtain this development permit and agree to the conditions attached
:o this permit.
Signature:
Print Name:
JJ45&.-' mhI Aim
Date:
lo -7(_/3
Phis permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
Dr abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
I: ***BUILDING DEPARTMENT CONDITIONS***
No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
3uilding Official.
3: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
;tart of any construction. These documents shall be maintained and made available until final inspection approval is
;ranted.
I: When special inspection is required, either the owner or the registered design professional in responsible charge,
;hall employ a special inspection agency and notify the Building Official of the appointment prior to the first
Duilding inspection. The special inspector shall furnish inspection reports to the Building Official in a timely manner.
5: A final report documenting required special inspections and correction of any discrepancies noted in the inspections
;hall be submitted to the Building Official. The final inspection report shall be prepared by the approved special
nspection agency and shall be submitted to the Building Official prior to and as a condition of final inspection
approval.
ioc: IBC -7/10
D13-257 Printed: 10-31-2013
6: All construction shall be done in conformanr the approved plans and the requiremen-the International
Building Code or International Residential Co ternational Mechanical Code, Washington Energy Code.
7: Manufacturers installation instructions shall be available on the job site at the time of inspection.
8: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
9: ***FIRE DEPARTMENT CONDITIONS***
10: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable with the
following concerns:
11: Install mechanical stops between mobile shelving so that when shelving is rolled together, a minimum 6 inch transverse
flue space is maintained every 4 ft. along the length of the track. If there are questions, contact Al Metzler at
206-971-8718.
12: Sprinklers shall be installed under fixed obstructions over 4 feet (1.2 m) wide such as ducts, decks, open grate
flooring, cutting tables, shelves and overhead doors. (NFPA 13-8.6.5.3.3)
13: All new sprinkler systems and all modifications to existing sprinkler systems shall have fire department review and
approval of drawings prior to installation or modification. New sprinkler systems and all modifications to sprinkler
systems involving more than 50 heads shall have the written approval of Factory Mutual or any fire protection engineer
licensed by the State of Washington and approved by the Fire Marshal prior to submittal to the Tukwila Fire Prevention
Bureau. No sprinkler work shall commence without approved drawings. (City Ordinance No. 2327).
14: Clearance between ignition sources, such as light fixtures, heaters and flame -producing devices, and combustible
materials shall be maintained in an approved manner. (IFC 305.1)
15: Storage shall be maintained 2 feet or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18
inches below sprinkler head deflectors in sprinklered areas of buildings. (IFC 315.2.1)
16: Nominal 6" transverse flue spaces between loads and at rack uprights shall be maintained in single row, double row, and
multiple row racks. Random variations in the width of flue spaces or in their vertical alignment shall be permitted.
(NFPA 13-12.3.1.13)
17: Contact The Tukwila Fire Prevention Bureau to witness, all required inspections and tests. (City Ordinances #2327 and
#2328)
18: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
19: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575-4407.
doc: IBC -7/10
D13-257 Printed: 10-31-2013
•
CITY OF TUKWILA
Community Development Department
Public Works Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Building Permit No. 1) 3 ;_S 7
Project No.
Date Application Accepted:
Date Application Expires:
(For office use only)
CONSTRUCTION PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
SITE LOCATION
Site Address: 535 Southcenter Mall
Tenant Name: J Crew
King Co Assessor's Tax No.:
Suite Number: 676 Floor: 1
New Tenant: j Yes El „No
PROPERTY OWNER
Name: Westfield
Address: 11601 Wiltshire Blvd, 11th Floor
City: Los Angeles State: CA Zip: 98025
CONTACT PERSON — person receiving all project
communication
Name: Gary Palmer, Property Service
Address:
Address: PO Box 23534
City: Bend State: OR Zip: 97701
City: Eugene State: OR
Zip: 97492
Phone: (514) 603-4191 Fax:
Email: psconsultants@sbcglobal.net
Phone:
GENERAL CONTRACTOR INFORMATION
Company Name: TBD
Address:
Company Name:
City: Bend State: OR Zip: 97701
Phone: (541) 389-9659 Fax: (541) 312-8708
City:
State:
Zip:
Phone:
Fax:
City:
State:
Contr Reg No.:
Phone:
Exp Date:
Tukwila Business License No.:
H:SApplimtionsirorms-Applications On L nei2011 Applications SPamd Application Revised - SA -I 1 dnac
Revisal: Augua 2011
bh
ARCHITECT OF RECORD
Company Name: Eclipse Engineering Inc
Engineer Name: Rolf Armstrong
Company Name:
City: Bend State: OR Zip: 97701
Phone: (541) 389-9659 Fax: (541) 312-8708
Architect Name:
Address:
City:
State:
Zip:
Phone:
Fax:
Email:
ENGINEER OF RECORD
Company Name: Eclipse Engineering Inc
Engineer Name: Rolf Armstrong
Address: 155 N Revere Ave
City: Bend State: OR Zip: 97701
Phone: (541) 389-9659 Fax: (541) 312-8708
Email: www eclipse-engineering.com
LENDER/BOND ISSUED (required for projects $5,000 or
greater per RCW 19.27.095)
Name: J Crew
Address: 770 Broadway, 14th Floor
City: New York State: NY Zip: 10003
Page 1of4
BUILDING PERMIT INFORMATION — 206-431-3670
Valuation of Project (contractor's bid price): $ 10,000
Describe the scope of work (please provide detailed information):
Install racking typical to retail TI including mobile and fixed racking systems
Existing Building Valuation: $
Will there be new rack storage? ® Yes ❑.. No If yes, a separate permit and plan submittal will be required
Provide All Building Areas in Square Footage Below
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided Standard:
Compact Handicap:
Will there be a change in use? ❑ Yes ❑ No If `yes", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
❑ Sprinklers ❑ Automatic Fire Alarm ❑ None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? D Yes ❑ No
If "yes', attach list of materials and storage locations on a separate 8-1/2" x 11" paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
❑ On-site Septic System — For on-site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
HAApplieaiwslForms-Applications On L ne12011 Applicu1mns1P'amd Application Revised - 8-9-11.docx
Revised: August 2011
en
Page 2 of 4
Existing
Interior Remodel
Addition to
Existing
Structure
New
Type of
Construction per
IBC
Type of
Occupancy per
IBC
1n Floor
2,538
IIB
M
2nd Floor
Yd Floor
Floors thru
Basement
Accessory Structures
Attached Garage
Detached Garage
Attached Carport
Detached Carport
Covered Deck
Uncovered Deck
PLANNING DIVISION:
Single family building footprint (area of the foundation of all structures, plus any decks over 18 inches and overhangs greater than 18 inches)
*For an Accessory dwelling, provide the following:
Lot Area (sq ft): Floor area of principal dwelling: Floor area of accessory dwelling:
*Provide documentation that shows that the principal owner lives in one of the dwellings as his or her primary residence.
Number of Parking Stalls Provided Standard:
Compact Handicap:
Will there be a change in use? ❑ Yes ❑ No If `yes", explain:
FIRE PROTECTION/HAZARDOUS MATERIALS:
❑ Sprinklers ❑ Automatic Fire Alarm ❑ None ❑ Other (specify)
Will there be storage or use of flammable, combustible or hazardous materials in the building? D Yes ❑ No
If "yes', attach list of materials and storage locations on a separate 8-1/2" x 11" paper including quantities and Material Safety Data Sheets.
SEPTIC SYSTEM
❑ On-site Septic System — For on-site septic system, provide 2 copies of a current septic design approved by King County Health
Department.
HAApplieaiwslForms-Applications On L ne12011 Applicu1mns1P'amd Application Revised - 8-9-11.docx
Revised: August 2011
en
Page 2 of 4
PERMIT APPLICATION NOTES —
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be
requested in writing and justifiable cause demonstrated. Section 105.32 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED A ...
Signature: 6. Pik/1„ .01 1), j � � G �J Date: Who /3
Gary Palmer, Property Service Day Telephone: (514) 603-4191
Print Name:
Mailing Address: PO Box 23534
H:1AppliezionslPonms-Appli®timts On r.ine12011 ApplicationaPerinit Application Revised - 8-9-1 I.docx
Revised: Aag is 2011
bh
Eugene OR 97492
City State Zip
Page 4 of 4
• •
wq� City of Tukwila
\yam Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206-431-3665
Web site: http://www.TukwilaWA.gov
-RECEIPT
Parcel No.: 9202470010 Permit Number: D13-257
Address: 535 SOUTHCENTER MALL TUKW Status: APPROVED
Suite No: Applied Date: 08/06/2013
Applicant: J CREW Issue Date:
Receipt No.: R13-03028
Initials:
User ID:
WER
1655
Payment Amount: $249.85
Payment Date: 10/31/2013 04:16 PM
Balance: $0.00
Payee: TOP RISE CONSTRUCTION
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 111867
ACCOUNT ITEM LIST:
Description
249.85
Account -Code Current Pmts
BUILDING - NONRES
STATE BUILDING SURCHARGE
000.322.100
640.237.114
Total: $249.85
245.35
4.50
Printorl• 1n_31_9M3
r •
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-43 1-3670
Fax: 206-431-3665
Web site: http://www.TukwilaWA.ov
RECEIPT
Parcel No.: 9202470010 Permit Number: D13-257
Address: 535 SOUTHCENTER MALL TUKW Status: PENDING
Suite No: Applied Date: 08/06/2013
Applicant: J CREW Issue Date:
Receipt No.: R13-02301
Initials:
User ID:
WER
1655
Payment Amount: $227.05
Payment Date: 08/06/2013 02:11 PM
Balance: $353.80
Payee: GARY PALMER (PHONE)
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 015001
ACCOUNT ITEM LIST:
Description
227.05
Account Code Current Pmts
PLAN CHECK - NONRES
000.345.830 227.05
Total: $227.05
a,...• oe..ejnr_na
Printed: 08-06-2013
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy with permit
hit 13 - /56
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
444 Andover Park East, Tukwila, Wa. 98188. 206-575-4407
Project:
''--- cc. --_,2)
Type of Inspection:
/6-4-(z - /A c
Address:
Suite #: 53s- sc "WV/
Contact Person:
Special Instructions:
Phone No.:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers: )/e.S
Hrs.:
Fire Alarm:
yes
Hood & Duct: N0
-A.-c‘4 fr,-,.,4-1
- 0,Z -7;: .,,30,77,-- .%e
„1/
Pre -Fire: A/c)
.Ar• . .�� - pyo/ —
/a/,
NI/41r4'/,€
.��, 2-sw
.5
&,-.e
/0,.
. Pte% .
.i,h,,,„(7 s4
4.n —
Needs Shift Inspection: yob
Sprinklers: )/e.S
Hrs.:
Fire Alarm:
yes
Hood & Duct: N0
Monitor:
' t7 Ger-d/0,
Pre -Fire: A/c)
Permits:
Occupancy Type:
/"l
Inspector c--,"--3
Date: //Ah
Hrs.:
/
0
$100.00,REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address:
City:
State:
Zip:
Word/Inspection Record Form.Doc
6/11/10
T.F.D. Form F.P. 113
FILE COPY
ECLIPSE ri—%14
ENGINEERING INC.
August 22, 2013
City of Tukwila
Department of Community Development
Attn: Allen Johannessen
6300 Southcenter Blvd., Suite #100
Tukwila, WA 98188
REVIEWED FOR
CODE COMPLIANCE
APPROVED
SEP 0 4 2013
Re: J Crew — Westfield Southcenter Mall — Space #676
Tukwila, WA City of Tukwila
EEI Project Number: 13-07-244 BUILDING DIVISION
Tukwila Permit Application Number = D13-257
To Allen:
AUG 222013
This letter was prepared, in an effort to assist your review, with our responses to the building department
comments that were recently created by the Tukwila Department of Community Development. Please note that
Eclipse Engineering, Inc. is only re -submitting structural details for the shelving racks. All other submittal
requirements shall be provided by the project architect or their consultants.
Revisions to the Calculations and Plans:
1) We have updated our plans and calculations to show compliance with the 2012 International Building Codes
with the Washington State Amendments and current local City of Tukwila codes.
2) We have added the specification of special inspections for the post -installed anchors per the referenced
ICC/ES report.
Eclipse Engineering, Inc. has only reviewed the structural components within our scope of services, and we do
not take any responsibility for any other portion of the project or plan submittal. Please feel free contact us with
any questions on this portion of the project — (541) 389-9659.
Sincerely,
Eclipse Engineering, Inc.
Nick Bumam, PE
Project Engineer
CORRECTION
LTR#_t___
b13% -)s7
Enclosed: shelving calculations, detail sheet.
RECEIVED
CITY OF TUKWILA
AUG 2 8 2013
PERMIT CENTER
O� 9`
1t)C4T-U
155 NE REVERE AVENUE, SUITE A, BEND, OR 97701 /o �\ 1
S��LU�/��NS
PHONE: (541) 3891659 FAX: (541) 312-8708
WWW.ECLIPSE-ENGINEERING.COM ' . ,
ECLIPSE
ENGINEERING INC.
Structural Calculations
Steel Storage Racks
By Pipp Mobile Storage Systems, Inc.
PIPP P.O. #104060 5.0. #317784
J. Crew #807
Westfield Southcenter Mall
535 Southcenter Mall - Space #676
Tukwila, Washington 98188
Prepared For:
Pipp Mobile Storage Systems, Inc.
2966 Wilson Drive NW
Walker, MI 49544
Please note: The calculations contained within justify the seismic resistance of
the shelving racks, the fixed and mobile base supports, and the connection to
the existing partition walls for both lateral and overturning forces as required
by the 2012 International Building Code with Washington State Amendments
and current local City of Tukwila codes. These storage racks are not accessible
to the general public.
155 NE REVERE AVENUE, SUITE A, BEND, OR 97701
PHONE: (541) 389-9659 FAX: (541) 312-8708
WWW.ECLIPSE-ENGINEERING.COM
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
Pipp Mobile STEEL STORAGE RACK DESIGN
2012 IBC & ASCE 7-10 - 15.5.3
Design Vertical Steel Posts at Each Corner : plf := Ib•ft 1
Shelving Dimensions: psf := Ib•ft 2
Total Height of Shelving Unit - ht := 10.00.ft pcf := Ib•ft 3
Width of Shelving Unit - w := 4.00.ft ksi := 1000•Ib•in 2
Depth of Shelving Unit - d:= 2.(1.25.ft) kips := 1000•Ib
Number of Shelves - N := 10
Vertical Shelf Spacing - S := 13.33.in
Shelving Loads:
Maximum Live Load on each shelf is 50 lbs:
Weight per shelf -
Load in psf -
Design live Load on Shelf -
Dead Load on Shelf -
Wu := 2•(50•Ib)
Wtj
LLj :_ —
w•d
LL := LLj
DL:= 1.50.psf
Section Properties of Double Rivet 'L' Post :
Modulus of Elasticity of Steel - E := 29000.ksi
Steel Yield Stress - Fy := 33 • ksi
Section Modulus in x and y - Sx := 0.04.in3
Moment of Inertia in x and y - IX := 0.06•in4
Full Cross Sectional Area - Ap := 0.22.in2
Length of Unbraced Post -
Effective Length Factor -
Wtj = 100lb
LLj = 10. psf
LL= 10.psf
b:= 1.5•in
h:= 1.5•in
r := 0.47•in
rX := 0.47•in
t:= 0.075•in
h� := 1.42•in
b� := 1.42•in
L.„:= S= 13.33•in Ly:= S= 1333.in Lt:= S= 13.33•in
Kx := 1.0 Ky := 1.0 Kt := 1.0
Section Properties Continued:
Density of Steel - psteel := 490.pcf
Weight of Post - Wp := psteel•Ap•ht
Vertical DL on Post- Pd := DL•w•.125d•N + Wp
Vertical LL on Post - P1:= LL•w•.125•d•N
Total Vertical Load on Post - Pp := Pd + PI
Wp = 7.49•Ib
Pd = 26.24Ib
P1= 1251b
Pp = 151.24•Ib
1
Eclipse Engineering, Inc.
Consulting Engineers
Floor Load Calculations :
Weight of Mobile Carriage:
Total Load on Each Unit:
Area of Each Shelf Unit:
J. CREW #807
TUKWILA, WA
We := 90•Ib
W := 8.Pp + Vic
A„ := w•(d + 1.5in)
Floor Load under Shelf: PSF := A PSF = 124.psf
Au
NOTE: SHELVING LIVE LOAD IS CONSISTENT WITH 200 psf ALLOWABLE FOR SLAB LOADING
8/22/2013
Rolf Armstrong, PE
W = 1299.89lb
Au = 10.5 ft2
Find the Seismic Load using Full Design Live Load :
ASCE-7 Seismic Design Procedure:
Importance Factor -
Determine Ss and Si from maps -
Determine the Site Class -
Determine Fa and Fv -
Determine SMS and SM1 _
Determine Sps and SDI _
IE := 1.0
SS := 1.426
Class D
Fa := 1.000
SMs := Fa • Ss
SMs = 1.426
2
SDS -•SMS
SDs = 0.951
Structural System - Section 15.5.3 ASCE-7:
4. Steel Storage Racks R := 4.0
RP := R
Total Vertical LL Load on Shelf - W1:= LL•w•d
Total Vertical DL Load on Shelf -
120 := 2
ap := 2.5
WP
Wd := DL•w•d + 8• N
Seismic Analysis Procedure per ASCE-7 Section 13.3.1:
Average Roof Height - hr := 20.0•ft
Height of Rack Attachment - z := 0 ft
Seismic Base Shear Factor -
Shear Factor Boundaries -
0.4.ap SDs
Vt:— C1+2•h
r
RP
Ip
Vin := 0.3•Sps•Ip
Vtmax:= 1.6•Sm. Ip
Vt := if (Vt > Vtmax , Vtmax . Vt)
Vt := if (Vt < Vtmin , Vtmin , Vt)
Si := 0.488
Fv := 1.512
SM1 := Fv•Si
SMi = 0.7379
2
SDI 3 •SM1
SDI = 0.492
Cd := 3.5
Ip := 1.0
WI= 100lb
Wd = 20.99 lb
(0'-0" For Ground floor)
Vt = 0.238
Vtmin = 0.285
Vtmax = 1.521
Vt = 0.285
2
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
Seismic Loads Continued :
For ASD, Shear may be reduced -
Seismic DL Base Shear -
DL Force per Shelf :
Seismic LL Base Shear -
LL Force per Shelf :
0.67 * LL Force per Shelf :
TUKWILA, WA Rolf Armstrong, PE
Vt
:= t = 0.204
p 1.4
Vtd := Vp•Wd•N = 42.76lb
Fd := Vp•Wd = 4.28Ib
Vtl := Vp•WI•N = 203.711b
F1 := Vp•WI = 20.37Ib
F1.67:= 0.67•Vp•W1= 13.65 lb
Force Distribution per ASCE-7 Section 15.5.3.3:
Operating Weight is one of Two Loading Conditions :
Condition #1: Each Shelf Loaded to 67% of Live Weight
Cumulative Heights of Shelves -
H1:= 0.0•S + 1.0•S + 2.0•S + 3.0•S + 4.0•S + 5.0•S + 6.0•S + 7.0•S + 8.0•S + 9.0•S
H2 := 0
Total Moment at Shelf Base -
H := H1 + H2
Mt:= H•Wd + H 0.67•Wl
Vertical Distribution Factors for Each Shelf -
Total Base Shear - Vtotal Vtd + 0.67•Vtl
Wd •0.0.S + W1.0.67.0.0•S
C1:= M = 0
t
F1 C1.(Vtotal) = 0
Wd •2.0.S + W1.0.67.2.0•S
C3:= M — 0.044
t
F3 C3•(Vtotal) = 7.97Ib
Wd•4.0•S + W1.0.67.4.0•S
C5:— M — 0.089
t
F5 C5•(Vtotal) = 15.93Ib
Wd •6.0•S + W1.0.67.6.0•S
C7:= M — 0.133
t
F7 C7•(Vtotal) = 23.9 lb
Wd•8.0•S+W10.678.0S
C9:—— 0.178
Mt
F5 Cg•(Vtotal) = 31.87Ib
Wd • 10.0•S + W1.0.67.10.0•S
C11 := frit
— 0.222
H = 49.99ft
Mt= 4398.34ft•lb
Vtotai = 179.25 lb
Wd•1.0.S+ W1.0.67.1.0.5
C2:— M = 0.022
t
F2 C2•(Vtotal) = 3.98lb
Wd•3.0•S+ W1.0.67.3.0•S
C4:— M — 0.067
t
F4:= C4•(Vtotal) = 11.951b
Wd•5.0•S+ W1.0.67.5.0•S
C6:=— 0.111
Mt
F6 C6•(Vtotal) = 19.92Ib
Wd•7.0•S + WI.0.67.7.0.S
C8:— = 0.156
C10
:—
Mt
F8 C8•(Vtotal) = 27.88Ib
Wd•9.0•S+ WI.0.67.9.0•S
— 0.2
Mt
Flo := C10•(Vtotal) = 35.85 lb
Wd•11.0•S+ W1.0.67.11.0•S
C12:= — 0.244
Mt
3
Eclipse Engineering, Inc.
Consulting Engineers
J. CREW #807
TUKWILA, WA
8/22/2013
Rolf Armstrong, PE
F11 := Cil'(Vtotal) = 39.83 lb F12 := C12'(Vtotal) = 43.82 lb
Wd • 12.0.S + WI.0.67.12.0.S
C13 :_ — 0.267 C14 :—
Mt Mt
F13 := C13.(Vtotal) = 47.8lb F14 := C14'(Vtotal) = 51.78 lb
C1+C2+C3+C4+C5+C6+C7+C8+C9+Cio= 1
Force Distribution Continued :
Wd•13.0•S+ WI.0.67.13.0•S
— 0.289
Coefficients Should total 1.0
Condition #2: Top Shelf Only Loaded to 100% of Live Weight
Total Moment at Base of Shelf - Mta := (N — 1) •S•Wd + (N — 1) •S•WI = 1210ft•Ib
Total Base Shear -
Vtotal2 := Vtd + FI
Vtotal2 = 63.13Ib
Wd•0.0•S+ 0•WI.0.0•S Wd•(N — 1).S + Wi.(N — 1)•S
Cia :_ — 0 Cioa :_ — 1
Mta Mta
Fia := Cla'(Vtota12) = 0
Fioa := C1oa'(Vtotal2) = 63.13 lb
Condition #1 Controls for Total Base Shear
By Inspection, Force Distribution for intermediate shelves without LL are negligible.
Moment calculation for each column is based on total seismic base shear.
Column at center of rack is the worst case for this shelving rack system.
Column Design in Short Direction : Ms:= 8 2 •(Vtd + Vtl) = 17.11ft•Ib
Bending Stress on Column - fbx:= M5.Sx-1 = 5.13•ksi
Allowable Bending Stress - Fb := 0.6.Fy = 19.8•ksi
Bending at the Base of Each Column is Adequate
Deflection of Shelving Bays - worst case is at the bottom bay
0 (Vtd + Vd) S — 0.03. in S = 476.76
12. E.
At:= 0•(N — 1) = 0.25•in Da:= 0.05•ht= 6•in
if(At < Da, "Deflection is Adequate" , "No Good") = "Deflection is Adequate"
Moment at Rivet Connection:
Shear on each rivet -
Ms dr2.3.14
dr := 0.25•inVr :_ — 136.89lb Ar := — 0.0491 •int
1.5.in 4
Vr
Stress on Rivet - f� := Ar = 2 79 ksi
Tr
4
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
Allowable Stress on Rivet - F„r := 0.4.80•ksi = 32•ksi
RIVET CONNECTION IS ADEQUATE FOR MOMENT CONNECTION FROM BEAM TO POST
Seismic Uplift on Shelves :
Seismic Vertical Component:
Vertical Dead Load of Shelf:
:= 0.2•Sps•(DL+ LL)•w•d
D := (DL+ LL)•w•d
E„ = 21.8653 Ib
D = 115Ib
Note: since the shelf LL is used to generate the seismic uplift force, it may also be used to
calculate the net uplift load. For an empty shelf, only the DL would be used, but the ratio
of seismic uplift will be the same.
Net Uplift Load on Shelf:
Fu := E„ — 0.6•D Fu = —47.1347 lb
Note: This uplift load is for the full shelf. Each shelf will be connected at each corner.
Number of Shelf Connections:
Uplift Force per Corner:
Nc := 4
F„
Fuc :=
NIC
Fuc = —11.7837 lb
NOTE: Since the uplift force is negative, a mechanical connection is not required.
5
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
Find Allowable Axial Load for Column :
Allowable Buckling Stresses -
2
•
aex.x E – 355.82 • ksi
(Kj2
rx
Oex crex.x = 355.82 • ksi
Distance from Shear Center t• hc2 • bc2
2
to CL of Web via X-axis ec :=
4•Ix ec = 1.2706 • in
Distance From CL Web to Centroid - xc := 0.649•in – 0.51 xc = 0.6115•in
Distance From Shear Center x0:= xc + ec xo = 1.8821 • in
to Centroid -
Polar Radius of Gyration - r0 := J rx2 + ry2 + x,2 r0 = 1.996•in
Torsion Constant - 3 := 3 •(2•b•t3 + h•t3) 3 = 0.00063•in4
Warping Constant - CW := t•b3 h2 C 3 b•t + 2 h tl C = 0.0339 • in6
12 64)1+ h•t /I
Shear Modulus - G := 11300•ksi
1 Tr2•E•C,,,
Qt:= 2• G..3+2
Ap • r0 (Kt. Lt)
Qt = 70.4601 • ksi
xo)2
p:=1– — p=0.1109
ro
Fet:= 21p [(°ex+ Qt) – J((Tex+ Qt)2 – 4•p•Qex•0•t] Fet = 59.7422•ksi
Elastic Flexural Buckling Stress - Fe := if (Fet < 0ex, Fet , (Tex) Fe = 59.7422 • ksi
F
Allowable Compressive Stress - Fn := if Fe > 2 , Fy• 1– 4FF , Fe Fn = 28.4429 • ksi
e
Factor of Safety for Axial Comp. - Lto := 1.92
6
Eclipse Engineering, Inc.
Consulting Engineers
J. CREW #807
TUKWILA, WA
Find Effective Area -
Determine the Effective Width of Flange -
Flat width of Flange - wf := b - 0.51
Flange Plate Buckling Coefficient - kf := 0.43
1.052 wf
Fn
Xf :_ —
,f t E
1
pf:= 1- —
0.22
%f Xf
Effective Flange Width - be := if (Xf > 0.673, pf•Wf, wf) be = 1.1576.in
Determine Effective Width of Web -
Flat width of Web - ww := h - t ww = 1.425.in
Web Plate Buckling Coefficient - kw := 0.43
1.052 ww Fn
xw:= t E
pw := 1- — pw = 0.8061
0.22 1
%w %w
Effective Web Width - he := if(Xw > 0.673, pw-ww, ww) he = 1.1487.in
Effective Column Area -Ae t•(he + be) Ae = 0.173•in2
Nominal Column Capacity - Pn := Ae•F„ Pn = 4920 lb
Pn
Allowable Column Capacity - Pa :_ Pa = 2562 lb
0
Check Combined Stresses -
Flange Slenderness Factor -
8/22/2013
Rolf Armstrong, PE
wf = 1.4625 . in
Xf = 0.9797
pf = 0.7915
Web Slenderness Factor -
Xw = 0.9546
Pc, :_
(Kx tx)2
Pcr Pcrx
Magnification Factor -
7r2•E•Ix
Combined Stress:
Pc, = 9.66 .104 lb
Pcr = 96647.07 lb
a := 1 — 11o' PP a = 0.997 Cm := 0.85
Pcr
Pp +- Cm f bx - 0.28 MUST BE LESS THAN 1.0
Pa Fb•a
Final Design: 'L' POSTS WITH BEAM BRACKET ARE ADEQUATE FOR
REQD COMBINED AXIAL AND BENDING LOADS
NOTE: Pp is the total vertical load on post, not 67% live load, so the design is conservative
7
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
Pipp Mobile STEEL STORAGE RACK DESIGN
2012 IBC & ASCE 7-10 - 15.5.3
Find Overturning Forces :
Total Height of Shelving Unit - Ht := ht = 10ft Width of Shelving Unit - w = 4ft
Depth of Shelving Unit - d = 2.5ft WORST CASE
Number of Shelves - N = 10 Vertical Shelf Spacing - S = 13.33 -in
Height to Top Shelf Center of G - htop := Ht htop = 10ft
Height to Shelf Center of G - he :_ (N 2 1) s he = 6.1096•ft
From Vertical Distribution of Seismic Force previously calculated -
Controlling Load Cases -
Weight of Rack and 67% of LL - W := (Wd + 0.67•Wi)•N W = 879.89 lb
Seismic Rack and 67% of LL - V := Vtd + 0.67•Vt1 V = 179.25 lb
Ma:= F1.0.0•S + F2.1.0•S + F3.2.0•S + F4.3.0•S + F5.4.0•S + F6.5.0•S + F7.6.0•S + F8.7.0•S
Mb := Fg.8.0•S + F10.9.0.S
Overturning Rack and 67% of LL - M := Ma + Mb = 1261.04 ft•Ib
Weight of Rack and 100% Top Shelf - Wa := Wd • N + W1 Wa = 309.89 lb
Seismic Rack and 100% Top Shelf - Va := Vtd + F1 Va = 63.13 lb
Overturning Rack and 100% Top Shelf - Ma := Vtd•hc + FI htop Ma = 464.94ft•lb
Controlling Weight - We := if (W > Wa, W , Wa) We = 879.89 lb
Controlling Shear - Vc := if (V > Va , V , Va) Vc = 179.25 lb
Controlling Moment - Mot := if(M > Ma , M , Ma) Mot = 1261.04 ft• Ib
Tension Force on Column Anchor - T := Mot — 0.60• We T = 240.45 lb
per side of shelving unit d 2
T:= if(T <0•Ib,0•Ib,T) T = 240.45 lb
V
Shear Force on Column Anchor - V := �2 V = 89.62 lb
USE: HILTI KWIK BOLT TZ ANCHOR (or equivalent) -
USE 3/8"4) x 2" embed installed per the requirements of Hilti
Allowable Tension Force -
Allowable Shear Force -
Per ASCE 13.4.2
Combined Loading -
Ta := 1006•Ib For 2500psi Concrete
Va:= 999•Ib
Tal+(Va)=0.427
p := 1.3
MUST BE LESS THAN 1.00
8
Eclipse Engineering, Inc.
Consulting Engineers
J. CREW #807
TUKWILA, WA
8/22/2013
Rolf Armstrong, PE
STEEL ANTI -TIP CLIP AND ANTI -TIP TRACK DESIGN
Tension (Uplift) Force on each side - T = 240.45 lb
Connection from Shelf to Carriage = 1/4" diameter bolt through 14 ga. steel:
Capacity of #12 screw (smaller than 1/4" diam. bolt) 349•1b
in 16 ga. steel (thinner than 14 ga. posts and clips) - �'_
if(T < 2•Zt, "(2) 1/4" Bolts are Adequate" , "No Good") = "(2) 1/4" Bolts are Adequate"
Use 3/16" Diameter anti -tip device for connection of carriage to track
Yield Stress of Angle Steel - Fy := 36•ksi
Thickness of Anti -tip Head - to := 0.090•in
Width of Anti -tip Rod + Radius - br := 0.25•in
Width of Anti -tip Head - ba := 0.490•in
ba — br
Width of Anti -tip Flange - La := 2 La = 0.12•in
Tension Force per Flange leg - Ti := 0.5•T Ti = 120.23 lb
Bending Moment on Leg - Mi := T2 M1= M1= 0.6•ft•Ib
baLa2
Section Modulus of Leg - Si :=6 S1= 0.0007•in3
M1
Bending Stress on Leg - fb := Sfb = 10.9•ksi
I
Ratio of Allowable Loads - fb — 0.404 MUST BE LESS THAN 1.0
0.75. Fy
Width of Anti -Tip track - L := 5.1. in
Thickness of Aluminum Track- tt:= 0.25•in Average Thickness
Spacing of Bolts - Stb := 22.5•in
Section Modulus of Track -
Design Moment on Track -
for continuous track section
Bending Stress on Track -
Allowable Stress of Aluminum -
Ratio of Allowable Loads -
St := 0.0921 • in3
T•Stb
M :=
8
M
fb . St
Fb := 21•ksi
fb•Fb 1 = 0.35
St= 0.092•in3
M = 56.36ft•Ib
fb = 7.34 • ksi
MUST BE LESS THAN 1.0
ANTI -TIP CLIP STEEL CONNECTION AND TRACK ARE ADEQUATE
9
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA
Connection from Steel Racks to Wall
Seismic Analysis Procedure per ASCE-7 Section 13.3.1:
Average Roof Height -
Height of Rack Attachments -
Seismic Base Shear Factor -
Shear Factor Boundaries -
Seismic Coefficient -
Number of Shelves -
Weight per Shelf -
Total Weight on Rack -
Rolf Armstrong, PE
hr = 20 ft
zb := z + ht= 10 ft At Top for fixed racks connected to walls
0.4.ap•Sos zb
Vt :_ 1 + 2 h Vt = 0.475
Rp r
Seismic Force at top and bottom
Connection at Top:
Standard Stud Spacing -
Width of Rack -
Number of Connection Points -
on each rack
Ip
%%Tim := 0.3•SDs. Ip
Vtmax 1.6•SDs. Ip
Vt := if (Vt > Vtmax , Vtmax , Vt)
Vt := if (Vt < Vtmin , Vtmin , Vt)
Force on each connection point -
Capacity per inch of embedment -
Required Embedment -
For Steel Studs:
Vt = 0.475
N = 10
Wtj = 100lb
WT:= 0.667.4. Pp
0.7•Vt.WT
Tv :-
2
Saud := 16•in
w = 4ft
w
Nc := floor
H)
Tv
Fc N
c
Ib
Ws := 135•—
in
Fc
ds. W
s
Vtmin = 0.285
Vtmax = 1.521
Vt = 0.475
WT = 403.51b
T„ = 67.131b
Nc = 3
Fc = 22.381b
ds= 0.166•in
Pullout Capacity in 20 ga T20 := 84 -lb For #10 Screw - per Scafco
studs - per Scafco
MIN #10 SCREW ATTACHED TO EXISTING WALL STUD IS
ADEQUATE TO RESIST SEISMIC FORCES ON SHELVING UNITS.
EXPANSION BOLT IS ADEQUATE BY INSPECTION AT THE BASE
10
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
Pipp Mobile STEEL STORAGE RACK DESIGN
2012 IBC & ASCE 7-10 - 15.5.3
Design Vertical Steel Posts at Each Corner : pif := Ib•ft1
Shelving Dimensions: psf := lb•fr 2
Total Height of Shelving Unit - ht := 10.00•ft pcf := Ib ft 3
Width of Shelving Unit - w := 4.00.ft ksi := 1000•Ib•in 2
Depth of Shelving Unit - d := 2.(1.25.ft) kips:= 1000•Ib
Number of Shelves - N := 3
Vertical Shelf Spacing - S := 60.00•in
Shelving Loads:
Maximum Live Load on each shelf is 100 lbs:
Weight per shelf -
Load in psf -
Design Live Load on Shelf -
Dead Load on Shelf -
Wti:= 2•(100•Ib)
Wtj
LL; j :_
w•d
LL := LLj
DL:= 1.50•psf
Section Properties of Double Rivet 'L' Post :
Modulus of Elasticity of Steel - E := 29000•ksi
Steel Yield Stress - Fy := 33•ksi
Section Modulus in x and y - SX := 0.04•in3
Moment of Inertia in x and y - IX := 0.06•in4
Full Cross Sectional Area - Ap := 0.22•in2
Length of Unbraced Post -
Effective Length Factor -
Section Properties Continued:
Density of Steel -
Weight of Post -
Vertical DL on Post -
Vertical LL on Post -
Total Vertical Load on Post -
Lx := S= 60.in
KX := 1.0
Wtj = 200lb
LLj = 20•psf
LL = 20•psf
b:= 1.5•in
h:= 1.5•in
ry:= 0.47•in
rx:= 0.47•in
t:= 0.075. in
hc:= 1.42.in
bc:= 1.42•in
Ly := S= 60•in
Ky := 1.0
psteel := 490 • pcf
Wp := psteel•Ap•ht
Pd := DL•w•.125d•N + Wp
P1:= LL•w•.125•d•N
Pp := Pd + PI
Lt:= S= 60•in
Kt:= 1.0
Wp = 7.49•Ib
Pd = 13.11lb
P� = 751b
Pp = 88.11•lb
11
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
Floor Load Calculations :
Weight of Mobile Carriage:
Total Load on Each Unit:
Area of Each Shelf Unit:
TUKWILA, WA Rolf Armstrong, PE
Wc := 90•Ib
W := 8•Pp + We W = 794.891b
Au := w.(d + 1.5in) Au = 10.5ft2
Floor Load under Shelf: PSF := A PSF = 76. psf
Au
NOTE: SHELVING LIVE LOAD IS CONSISTENT WITH 200 psf ALLOWABLE FOR SLAB LOADING
Find the Seismic Load using Full Design Live Load :
ASCE-7 Seismic Design Procedure:
Importance Factor - IE := 1.0
Determine Ss and S1 from maps - Ss := 1.426 S1:= 0.488
Determine the Site Class - Class D
Determine Fa and Fv - Fa := 1.000 Fv := 1.512
Determine SMS and SMi _ SMs := Fa•Ss SM1 Fv•Si
SMS = 1.426 SM1 = 0.7379
Determine SDS and SDI _ SDS 3 '31•01S SDI 3 •SM1
SDs = 0.951 SDI = 0.492
Structural System - Section 15.5.3 ASCE-7:
4. Steel Storage Racks R := 4.0 no := 2 Cd := 3.5
Rp := R ap := 2.5 Ip := 1.0
Total Vertical LL Load on Shelf - W1:= LL•w•d Wi = 200lb
W
Total Vertical DL Load on Shelf - Wd := DL•w•d + 8.— Np Wd = 34.961b
Seismic Analysis Procedure per ASCE-7 Section 13.3.1:
Average Roof Height -
Height of Rack Attachment -
Seismic Base Shear Factor -
Shear Factor Boundaries -
Vt
hr := 20.0•ft
z:= 0•ft
(0'-0" For Ground floor)
0.4•ap•SDs z
1+2•h Vt=0.238
Rp r
Ip
Vtmin := 0.3•5Ds•Ip
Vtmax 1.6•5Ds•Ip
Vt := if (Vt > Vtmax , Vtmax , Vt)
Vt := if (Vt < Vtmin Vtmin , Vt)
Vtmm = 0.285
Vtmax = 1.521
Vt = 0.285
12
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers TUKWILA, WA
Seismic Loads Continued :
Vt
ASD, Shear may be reduced - Vp := t1.4 = 0.204
Seismic DL Base Shear -
DL Force per Shelf :
Seismic LL Base Shear -
LL Force per Shelf :
0.67 * LL Force per Shelf :
Vtd :=Vp•Wd•N=21.371b
Fd := Vp•Wd = 7.12Ib
Vti := Vp•WI•N = 122.23 lb
F1:= Vp•WI= 40.74lb
F1.67:= 0.67•Vp•WI = 27.3Ib
Force Distribution per ASCE-7 Section 15.5.3.3:
Operating Weight is one of Two Loading Conditions :
Condition #1: Each Shelf Loaded to 67% of Live Weight
Cumulative Heights of Shelves -
H1:= 0.0•S + 1.0•S + 2.0•S
H2:= 0
Total Moment at Shelf Base -
H := H1 + H2
Mt:= H•Wd + H•0.67•Wl
Vertical Distribution Factors for Each Shelf -
Total Base Shear - Vtotal Vtd + 0.67•Vd
Wd.0.0•S + WI. 0.67.0.0.S
C1:=— 0
Mt
F1 C1•(utotal) = 0
Wd•2.0•S + WI.0.67.2.0•S
C3 :=— 0.667
Mt
F3 C3.(Vtotal) = 68.84 lb
Wd•4.0•S + W1.0.67.4.0•S
C5:== 1.333
Mt
F5 C54Vtotal) = 137.68 lb
Wd•6.0•S + W1.0.67.6.0•S
C7:= — 2
Mt
F7 := C7•(Vtotai) = 206.52 lb
Wd•8.0•S + W1.0.67.8.0•S
C9:—— 2.667
Mt
Fg := Cg•(Vtotal) = 275.36 lb
Wd • 10.0.S + W0.67.10.0.S
C11:=— 3.333
Mt
Rolf Armstrong, PE
H = 15ft
Mt = 2534.44 ft • lb
Vtotai = 103.26 lb
Wd•1.0•S+ WI.0.67.1.0•S
C2:=— 0.333
Mt
F2 := C2•(Vtotai) = 34.42Ib
Wd•3.0•S + WI.0.67.3.0•S
C4:= — 1
Mt
F4:= C4•(Vtotal) = 103.26 lb
Wd•5.0•S + WI.0.67.5.0•S
C6:= — 1.667
Mt
F6 C6•(Vtotal) = 172.1Ib
Wd•7.0•S + WI.0.67.7.0•S
C$ :—= 2.333
Mt
F9 := C8•(Vtotal) = 240.94 lb
Wd•9.0•S + WI.0.67.9.0•S
C10 := — 3
Mt.
Flo C1o•(Vtotal) = 309.78 lb
Wd•11.0•S+ WI.0.67.11.0.S
C12:= — 3.667
Mt
13
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
F11 := Cll.(Vtotal) = 344.21b F12 := C12'(Vtotal) = 378.62 lb
Wd•12.0•S+W10.6712.0S
Wd•13.0•S+ WI.0.67.13.0•S
C13 :_ — 4 C14 :_ — 4.333
Mt Mt
F13 := C13•(Vtotal) = 413.04 lb F14 := CIA '(Vtotal) = 447.46 lb
Cl+C2+ C3 = 1
Force Distribution Continued : Coefficients Should total 1.0
Condition #2: Top Shelf Only Loaded to 100% of Live Weight
Total Moment at Base of Shelf - Mta := (N — 1) •S•Wd + (N — 1) •S•W, = 2350ft•Ib
Total Base Shear -
Cia
Wd•0.0•S+ 0•WI.0.0•S
—0
Mta
Fia := Cia'(Vtotal2) = 0
Vtota12 := Vtd + FI Vt0012 = 62.11Ib
Wd•(N — 1).S+ W1•(N — 1).S
M — 1
to
F3a := C3a'(Vtotal2) = 62.11lb
Condition #1 Controls for Total Base Shear
By Inspection, Force Distribution for intermediate shelves without 11 are negligible.
Moment calculation for each column is based on total seismic base shear.
Column at center of rack is the worst case for this shelving rack system.
Column Design in Short Direction : MS:= 8 2 •�Vtd + Vtl) = 44.87ft•Ib
Bending Stress on Column - fbX:= MS•SX 1 = 13.46•ksi
Allowable Bending Stress - Fb := 0.6•Fy = 19.8•ksi
Bending at the Base of Each Column is Adequate
Deflection of Shelving Bays - worst case is at the bottom bay
3
Q :_ (Vtd + Vu).S — 1.49•in S = 40.39
12•E•IX
Ot:= 0•(N — 1) = 2.97•in Aa := 0.05•ht= 6•in
if(ot < oa, "Deflection is Adequate" , "No Good") = "Deflection is Adequate"
Moment at Rivet Connection:
Shear on each rivet -
MS dr2.3.14
dr := 0.25•in Vr := — 358.99 lb Ar — 0.0491•in2
1.5•in 4
Steel Stress on Rivet -
Vr
:= = 7.32.ksi
Ar
14
Eclipse Engineering, Inc.
Consulting Engineers
J. CREW #807
TUKWILA, WA
Allowable Stress on Rivet - F„r := 0.4.80•ksi = 32•ksi
8/22/2013
Rolf Armstrong, PE
RIVET CONNECTION IS ADEQUATE FOR MOMENT CONNECTION FROM BEAM TO POST
Seismic Uplift on Shelves :
Seismic Vertical Component:
E,,:= 0.2•Sos•(DL + LL)•w•d E„= 40.8787 lb
Vertical Dead Load of Shelf: D:= (DL + LL) • w •d D = 215Ib
Note: since the shelf LL is used to generate the seismic uplift force, it may also be used to
calculate the net uplift load. For an empty shelf, only the DL would be used, but the ratio
of seismic uplift will be the same.
Net Uplift Load on Shelf:
Fu:=E„-0.6•D F„=-88.1213lb
Note: This uplift load is for the full shelf. Each shelf will be connected at each corner.
Number of Shelf Connections:
Uplift Force per Corner:
Nc := 4
Fu
Fuc:= ---
NC
Fuc = —22.0303 lb
NOTE: Since the uplift force is negative, a mechanical connection is not required.
15
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
Find Allowable Axial Load for Column :
Allowable Buckling Stresses -
,K2•E
– 17.56 • ksi
(Tex.x
KxLx 2
rx
Distance from Shear Center e� := ec = 1.2706 • in
to CL of Web via X-axis 4.1
Distance From CL Web to Centroid - xc := 0.649 -in – 0.51 xc = 0.6115.in
t•hc2 b�2
(rex Oex.x = 17.56 • ksi
Distance From Shear Center xa := xc + ec xo = 1.8821 . in
to Centroid -
Polar Radius of Gyration - ro := J rx2 + ry2 + xo2 ro = 1.996• in
Torsion Constant - J := 3 .(2.b13 + h13) 3 = 0.00063•in4
:= t•b3 h2 r 3 b t + 2 h t
Warping Constant - C = 0.0339 • in6
12 l 6.b1+ h.t
Shear Modulus - G := 11300.ksi
1 �2'E'G,v
at := • G•3+
Ap•r 2 (Kt•4)2
Qt= 11.2335.ksi
xo 2
j3:= 1– — (=0.1109
ro
Fet := 21a [(aex + Qt) – J ((rex + 012 – 4.13'vex' Qt] Fet = 7.0423 • ksi
Elastic Flexural Buckling Stress - Fe := if(Fet< Uex, Fet > (Tex) Fe = 7.0423 • ksi
Fy
Allowable Compressive Stress - Fo := if Fe > Zy 4•F , Fy• 1 – , Fe F„ = 7.0423. ksi
e
Factor of Safety for Axial Comp. - f20 := 1.92
16
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
Find Effective Area -
Determine the Effective Width of Flange -
Flat width of Flange - wf := b - 0.51 wf = 1.4625•in
Flange Plate Buckling Coefficient - kf := 0.43
w F
Flange Slenderness Factor - Xf := 1 f
.052 tE %
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers TUKWILA, WA
Pipp Mobile STEEL STORAGE RACK DESIGN
2012 IBC & ASCE 7-10 - 15.5.3
Find Overturning Forces :
Total Height of Shelving Unit -
Depth of Shelving Unit -
Number of Shelves -
Height to Top Shelf Center of G -
Height to Shelf Center of G -
Ht := ht. loft
d = 2.5ft
N=3
htop := Ht
h :-(N+1) S
c
From Vertical Distribution of Seismic Force previously calculated -
Controlling Load Cases -
Weight of Rack and 67% of LL - W := (Wd + 0.67•WI)•N
Seismic Rack and 67% of LL - V := Vtd + 0.67•Vd
Ma:= F1.0.0•S+ F2.1.0•S+ F3.2.0•5
Mb := 0
Rolf Armstrong, PE
Width of Shelving Unit - w = 4ft
WORST CASE
Vertical Shelf Spacing - S = 60.in
htop = loft
he = 10•ft
Overturning Rack and 67% of LL -
Weight of Rack and 100% Top Shelf - Wa := Wd • N + W1
Seismic Rack and 100% Top Shelf - Va := Vtd + F1
Overturning Rack and 100% Top Shelf - Ma := Vtd • he + Fr htop
Controlling Weight -
Controlling Shear -
Controlling Moment -
Tension Force on Column Anchor -
per side of shelving unit
We := if (W > Wa, W , Wa)
Vc := if (V > Va , V , Va)
Mot := if(M > Ma, M , Ma)
T := Mot — 0We
.60•
d 2
T:= if(T <0•Ib,0•Ib,T)
W = 506.891b
V = 103.26 lb
M:=Ma+Mb=860.5ft-lb
Wa = 304.89 lb
Va = 62.11 lb
Ma = 621.1ft•Ib
We = 506.89 lb
Vc = 103.26 Ib
Mot = 860.5ft•Ib
T = 192.14 lb
T = 192.14 lb
Vc
Shear Force on Column Anchor - V
:= V = 51.63 lb
2
USE: HILTI KWIK BOLT TZ ANCHOR (or equivalent) -
USE 3/8"0 x 2" embed installed per the requirements of Hilti
Allowable Tension Force -
Allowable Shear Force -
Per ASCE 13.4.2
Combined Loading -
Ta:= 1006•Ib
Va:= 999•Ib
(Ta)+rVa1=0.315
For 2500psi Concrete
p := 1.3
MUST BE LESS THAN 1.00
18
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
FIXED BEAM DESIGN: Single Hanger Bar Beam
Design criteria:
Steel Yield Stress - Fy = 33•ksi
Width of
Rack -
Live Load
per shelf -
Dead Load on
Shelves -
w = 4ft
Wtj
wu 2•max(w,d) — 25•plf
wdi := 0.80 • plf
Point Loads on Beam -
Moments for Each Load -
wd•max(w,d)2
Mw := 8 — 51.6ft•Ib Mp:= wdi max(w,d)2 (P.max(wd))8 + 4 — 101.6ftIb
Maximum Design Moment - M := max(M, M) = 101.6ft•Ib
Modulus of
Elasticity -
Depth of
Rack -
Live Load on
Shelves -
E= 2.9x 104.ksi
d = 2.5ft
LL = 20 • psf
Minimum Dist
Load Req'd - wd := wdi + wi1 = 25.8•plf
Wt
P :_ = 100 lb
2
Shear for Each
Load -
Maximum Design
Shear -
wd•max(w, d) wdl•max(w, d)
VW: -2 — 51.6Ib Vp:= 2 + P= 101.6Ib
Allowable Shear
Stress -
V := max(Vp , VW) = 101.6Ib F,, := 0.4. Fy = 13.2 • ksi
Allowable Bending
Stress -
Fb := 0.66•Fy = 21.78•ksi
Section Properties: Hanger Bar Beam
A:= 0.233412 S:= 0.066•in3 I:= 0.041•in4
Actual Shear Stress - Actual Bending Stress -
f
fv:= A = 0.436.ksi F = 0.033
v
Deflections for Each -
f
OK fb := M = 18.473•ksii F = 0.848 OK
Fb
5•wd•max(w,d)4 5•wdl•max(w,d)4 P.max(w,d)3
AW:— — 0.125.in Op :_ + — 0.198.in
384•E•I 384•E•I 48•E•I
Total Load Deflection - o := max(op, Aw) = 0.198•in max(w, d) — 243 OK
A
Hanger Bar Beam is Adequate
19
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
FIXED BEAM DESIGN: Double Rivet Std. Profile Beam
Design criteria:
Steel Yield Stress - Fy = 33•ksi
Width of
Rack -
Total Load
per Bar -
Dead Load on
Shelves -
w = 4ft
Pti := V = 101.6ft.plf
wdl :-
Modulus of
Elasticity -
Depth of
Rack -
Live Load on
Shelves -
E= 2.9x 104.ksi
d = 2.5 ft
LL = 20•psf
DL•max(w,d)- 1.5.plf a - Distance from End a - min(w,d) - 0.625ft
2.2 of Shelf to Point 2.2
Load -
(min(w,d))2 (min(wd))wdl•2 Ptl
Total Moments - M :_ + - 16.07ft•Ib
12 8
Lateral Moment from Post -
Total Shear -
M5= 44.8737ft•Ib page 4 of original caics
wdl (min(w,d)1
/I P
V := 2 + Pt! = 51.7375 lb
2 2
Allowable Shear Stress - Allowable Bending Stress -
F„ = 13.2.ksi Fb = 21.78•ksi
Section Properties: Double Rivet Standard Profile Beam
A:= 0.264•in2
S:= 0.126•in3 I:= 0.211•in4
Actual Shear Stress - Actual Bending Stress -
V f„ M+MS fb
f" := A = 0.196•ksi F = 0.015 OK fb := S - 5.804.ksi — = 0.266
v b
Total Load Deflection -
OK
wdl (min(w,d)1J4 Pt!
(min(w,d)13 (min(w,d))
o := I\ 2 + 2 /I - 0 in 2 - 50923 OK
384•E•I 192•E•I 0
Double Rivet Standard Profile Beam is Adequate
1
20
Eclipse Engineering, Inc. J. CREW #807 8/22/2013
Consulting Engineers
TUKWILA, WA Rolf Armstrong, PE
STEEL ANTI -TIP CLIP AND ANTI -TIP TRACK DESIGN
Tension (Uplift) Force on each side - T = 192.14 lb
Connection from Shelf to Carriage = 1/4" diameter bolt through 14 ga. steel:
Capacity of #12 screw (smaller than 1/4" diam. bolt)
'_ 349•1b
in 16 ga. steel (thinner than 14 ga. posts and clips) -
if(T < 2•Z{, "(2) 1/4" Bolts are Adequate" , "No Good") = "(2) 1/4" Bolts are Adequate"
Use 3/16" Diameter anti -tip device for connection of carriage to track
Yield Stress of Angle Steel - Fy := 36.ksi
Thickness of Anti -tip Head - ta := 0.090.in
Width of Anti -tip Rod + Radius - br := 0.25.in
Width of Anti -tip Head - ba := 0.490•in
-
Width of Anti -tip Flange - Le := ba 2 br La = 0.12•in
Tension Force per Flange leg - T1:= 0.5•T Ti = 96.07 lb
Bending Moment on Leg - M1:= T121a MI = 0.48•ft•Ib
ba ta2
Section Modulus of Leg - 51:=6
SI = 0.0007 •in3
M1
Bending Stress on Leg - fb := S fb = 8.71 ksi
fb
Ratio of Allowable Loads - - 0.323 MUST BE LESS THAN 1.0
0.75. Fy
Width of Anti -Tip track - L := 5.1 • in
Thickness of Aluminum Track - tt:= 0.25.in Average Thickness
Spacing of Bolts - Stb := 22.5.in
Section Modulus of Track -
Design Moment on Track -
for continuous track section
Bending Stress on Track -
Allowable Stress of Aluminum -
Ratio of Allowable Loads -
St := 0.0921 •in3
T•Stb
M :=
8
M
fb. St
Fb := 21 • ksi
fb • Fb-1 = 0.279
St= 0.092.in3
M = 45.03ft.lb
fb = 5.87.ksi
MUST BE LESS THAN 1.0
ANTI -TIP CLIP STEEL CONNECTION AND TRACK ARE ADEQUATE
21
Eclipse Engineering Inc.
Consulting Engineers
J. CREW #807
TUKWILA, WA
Conterminous 48 States
2005 ASCE 7 Standard
Latitude = 47.458877
Longitude = -122.25864200000001
Spectral Response Accelerations Ss and S1
Ss and S1 = Mapped Spectral Acceleration Values
Site Class B - Fa = 1.0 ,Fv = 1.0
Data are based on a 0.05 deg grid spacing
Period Sa
(sec) (g)
0.2 1.426 (Ss, Site Class B)
1.0 0.488 (S1, Site Class B)
Conterminous 48 States
2005 ASCE 7 Standard
Latitude = 47.458877
Longitude = -122.25864200000001
Spectral Response Accelerations SMs and SM1
SMs = Fa x Ss and SM1 =FvxS1
Site Class D - Fa = 1.0 ,Fv = 1.512
Period Sa
(sec) (g)
0.2 1.426 (SMs, Site Class D)
1.0 0.738 (SM1, Site Class D)
Conterminous 48 States
2005 ASCE 7 Standard
Latitude = 47.458877
Longitude = -122.25864200000001
Design Spectral Response Accelerations SDs and SD1
SDs = 2/3 x SMs and SD1 =2/3xSM1
Site Class D - Fa = 1.0 ,Fv = 1.512
Period Sa
(sec) (g)
0.2 0.951 (SDs, Site Class D)
1.0 0.492 (SD1, Site Class D)
07/31/13
Nick Bumam, PE
60
111
129
33
50
55
Eclipse Engineering Inc.
Consulting Engineers
J. CREW #807
TUKWILA, WA
Fasteners (Screws and Welds)
Screw Table Notes
07/31/13
Nick Burnam, PE
Is!
SCAFCO.
Steer Scud Manufacturing Ca.
1. Screw spacing and edge distance shall not be less than 3 x D. (D = Nominal screw diameter)
2. The allowable screw values are based on the steel properties of the members being connected, per AISI section
E4.
3. When connecting materials of different metal thicknesses or yield strength, the lowest applicable values should be
used.
4. The nominal strength of the screw must be at least 3.75 times the allowable loads.
5. Values include a 3.0 factor of safety.
6. Applied loads may be multiplied by 0.75 for seismic or wind loading, per AISI A 5.1.3.
7. Penetration of screws through joined materials should not be less than 3 exposed threads. Screws should be
installed and tightened in accordance with screw manufacturer's recommendations.
Allowable Loads for Screw Connections (lbs/screw)
18
27
30
0.0188
0.0283
0.0312
33
43
54
0.0346
0.0451
0.0566
68
0.0713
33
33
33
45
45
45
33
33
33
45
45
45
280 124
156
394
557
156
151
76
177
263
370
84
109
137
523
173
66
121
141
39
59
65
164
244
344
72
94
118
Weld Table Notes
1. Weld capacities based on AISI, section E2.
2. When connecting materials of different metal thickness or tensile strength (Fu), the lowest applicable values
should be used.
3. Values include a 2.5 factor of safety.
4. Based on the minimum allowance load for fillet or flare groove welds, longitudinal or transverse loads.
5. Allowable loads based on E60xx electrodes
6. For material less than or equal to .1242" thick, drawings show nominal weld size. For such material, the effective
throat of the weld shall not be less than the thickness of the thinnest connected part.
Allowable Loads For Fillet Welds And Flare Groove Welds
48
Tt, nr
� # +
yield t
?ens to
E¢O�lecfrodes
l6slin
43
0.0451
33
45
609
54
0.0566
33
45
764
68
0.0713
33
45
963
97
0.1017
33
45
1373
118
0.1242
33
45
1677
54
0.0566
50
65
1104
68
0.0713
50
65
1390
97
0.1017
50
65
1983
118
0.1242
50
65
2422
48
Eclipse Engineering Inc.
Consulting Engineers
Page 11 of 14
J. CREW #807
TUKWILA, WA
07/31/13
Nick Bumam, PE
ESR -1917
TABLE .9 -KB -TZ CARBON AND STAINLESS STEEL ALLOWABLE SEISMIC TENSION (ASD), NORMAL -WEIGHT
CRACKED CONCRETE, CONDITION B(pounds)'A'
Nominal
Anchor
Diameter
Embedment
Depth l ei
(in.)
Concrete CompressIve Strength'
Vs = 4,500 psi
Pc = 3,000psi
f c = 4,000 psi
fc;=.8;000,psi
Carbon
steel
Stainless
steel
Carbon"
steel
Stainless
steel
Carbon'
steel
Stainless
steel
'Carbon
steel
Stainless
'steel
3f8
2
1,006
1,037
1,102
1,136'
1",273.
1,312
1;559
1,607
1/2
2
1,065
1,212
1,167
1,328
14348
1,533
'1,651
1,878
31/4
2,178;
2,207
2,386'
2,418
2;755
2,792
3,375
3,419
5/8
31/8
2,081
2,081
2,280
2;280
2;632
2,632
3,224
3,224
4.
3,014
2;588
3,301
2,835
3,812
3,274
4,669
4,010
3/4
'3 3/4
2;736
3;594
2;997
3,937
3,460
4,546
4;238
r 5,568
4 3/43,900
3;900
4;272
4,272
4,933
4,933
6,042
6,042
For Si: 1 ibf = 4.45 N, 1 psi "= 0.00689 MPa For pound -inch units: 1 mm = 0.03937 inches
'Values are or single anchors with' no edge distance or sparing reduction, For other cases;' calculation of Ru as per ACI 318-05 and conversion
to ASD in,accordance. with°Section 42.1 Eq. (5) is required.
2Values,are or normal weight concrete. For sand -lightweight concrete, multiply values by o.60.
'Condition'B applies where supplementary reinforcement in conformance with ACI 318-05 Section D: 4.4 is not provided, or where pullout or
pryout strength governs, For cases where the presence of supplementary reinforcement can be verified, the strength reduction factors
associated` with Condition A may be used.
TABLE 10 -KB -TZ CARBON AND STAINLESS
STEEL ALLOWABLE SEISMIC SHEAR LOAD (ASD),
(pounds)1
Nominal
Anchor
Diameter
Allowable Steel Capacity, Seismic Shear
Carbon Steel
Stainless Steel
3/8
9991,252
1/2
.2,839
3,049
5/8
4,678
5,245
3/4
6,313
6,477
For SI:' 1 Ibf = 4.45`N
'Values are or single anchors with no edge distance or
spacing reduction due to concrete failure.
5/1/2014
City of Tukwila
Department of Community Development
GARY PALMER
PO BOX 23534
EUGENE, OR 98492
RE: Permit No. D13-257
J CREW
535 SOUTHCENTER MALL
Dear Permit Holder:
Jim Haggerton, Mayor
Jack Pace, Director
In reviewing our current records, the above noted permit has not received a final inspection by the City of Tukwila Building
Division. Per the International Building Code, International Mechanical Code, Uniform Plumbing Code and/or the National
Electric Code, every permit issued by the Building Division under the provisions of these codes shall expire by limitation and
become null and void if the building or work authorized by such permit has not begun within 180 days from the issuance date of
such permit, or if the building or work authorized by such permit is suspended or abandoned at any time after the work has begun
for a period of 180 days. Your permit will expire on 6/7/2014.
Based on the above, you are hereby advised to:
1) Call the City of Tukwila Inspection Request Line at 206-438-9350 to schedule for the next or final inspection. Each
inspection creates a new 180 day period, provided the inspection shows progress.
-or-
2) Submit a written request for permit extension to the Permit Center at least seven(7) days before it is due to expire.
Address your extension request to the Building Official and state your reason(s) for the need to extend your permit.
The Building Code does allow the Building Official to approve one extension of up to 180 days. If it is determined that your
extension request is granted, you will be notified by mail.
In the event you do not call for an inspection and/or receive an extension prior to 6/7/2014, your permit will become null and void
and any further work on the project will require a new permit and associated fees.
Thank you for your cooperation in this matter.
Sincerely,
JJ\O9\LQ
Jennifer Marshall
erma Technician
File No: D13-257
6300 Southcenter Boulevard Suite #100 • Tukwila, Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
August 13, 2013
Gary Palmer
PO Box 23534
Eugene, OR 97492
•
City of Tukwila
Jim Haggerton, Mayor
Department of Community Development Jack Pace, Director
RE: Correction Letter #1
Development Permit Application Number D13-257
J Crew — 535 Southcenter Mall
Dear Mr. Palmer,
This letter is to inform you of corrections that must be addressed before your development permit can be
approved. All correction requests from each department must be addressed at the same time and reflected on
your drawings. I have enclosed comments from the Building Department. At this time the Fire, Planning, and
Public Works Departments have no comments.
Building Department: Allen Johannessen at 206 433-7163 if you have questions regarding the
attached comments.
Please address the attached comments in an itemized format with applicable revised plans, specifications,
and/or other documentation. The City requires that four (4) sets of revised plans, specifications and/or other
documentation be resubmitted with the appropriate revision block.
In order to better expedite your resubmittal, a `Revision Submittal Sheet' must accompany every resubmittal.
I have enclosed one for your convenience. Corrections/revisions must be made in person and will not be
accepted through the mail or by a messenger service.
If you have any questions, I can be reached at (206) 431-3670.
Sincerely,
Bill Rambo
Permit Technician
File No. D13-257
W::Permit CenterlCorrection Letters120131D13-257 Correction Letter #1.docx
6300 Southcenter Boulevard, Suite #100 • Tukwila, Washington 98188 • Phone 206-431-3670 • Fax 206-431-3665
• •
Tukwila Building Division
Allen Johannessen, Plan Examiner
Building Division Review Memo
Date: August 12, 2013
Project Name: J Crew
Permit #: D13-257
Plan Review: Allen Johannessen, Plans Examiner
The Building Division conducted a plan review on the subject permit application. Please address the following
comments in an itemized format with revised plans, specifications and/or other applicable documentation.
(GENERAL NOTE)
PLAN SUBMITTALS: (Min. size 11x17 to maximum size of 24x36; all sheets shall be the same size. New
revised plan sheets shall be the same size sheets as those previously submitted.)
(If applicable) Structural Drawings and structural calculations sheets by a registered engineer shall have a current
signed stamp -seal. Architectural design sheets and documents by a registered architect shall also have a current
signed stamp -seal.
1. Plan notes and engineering references outdated 2009 building codes. As of July 1 2013 City of Tukwila
adopted the 2012 International Building codes. Provide revised plan sheet and engineer's documents showing
compliance with the current 2012 International Building codes with Washington State Amendments to include
and current local City of Tukwila codes.
2. Specify on the plan special inspections for the bolts per the referenced ESR report.
Should there be questions concerning the above requirements, contact the Building Division at 206-431-3670.
No further comments at this time.
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
ACTIVITY NUMBER: D13-257 DATE: 08-28-13
PROJECT NAME: J CREW
SITE ADDRESS: 535 SOUTHCENTER MALL
Original Plan Submittal Response to Incomplete Letter #
X Response to Correction Letter # 1
Revision # After Permit Issued
DEPAR MENTS: 1
ui ding ivision
Public Works n
Fire Prevention
Structural
Planning Division n
n Permit Coordinator 111
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
DUE DATE: 08-29-13
Complete Incomplete n Not Applicable ❑
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
TUES/THURS ROUTING:
Please Route Structural Review Required
REVIEWER'S INITIALS:
❑ No further Review Required
DATE:
APPROVALS OR CORRECTIONS:
DUE DATE: 09-26-13
Approved n Approved with Conditions ir Not Approved (attach comments) n
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use• Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW 0 Staff Initials:
Documents/routing slip.doc
2-28-02
PERM T COORD COPY
PLAN REVIEW/ROUTING SLIP
ACTIVITY NUMBER: D13-257 DATE: 08-06-13
PROJECT NAME: J CREW
SITE ADDRESS: 535 SOUTHCENTER MALL
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # After Permit Issued
DEPA . TMENTS:
wilding Division
Public Works
Aw\ JJC -`
Fire Prevention
Structural
Planning Division
n
n Permit Coordinator �1
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Comments:
Incomplete n
DUE DATE: 08-08-13
Not Applicable
Permit Center Use Only
INCOMPLETE LETTER MAILED:
Departments determined incomplete: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
LETTER OF COMPLETENESS MAILED:
TUES/THURS ROUTING:
Please Route ql Structural Review Required ❑ No further Review Required n
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved ri Approved with Conditions
Notation:
REVIEWER'S INITIALS:
DUE DATE: 09-05-13
Not Approved (attach comments) ,Nt-
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED: l�
Departments issued corrections:
Bldg Fire 0 Ping 0 PW 0 Staff Initials:
Documents/routing slip.doc
2-28-02
REVISI:ON SUBMITTAL
•
•
City of Tukwila
•
Department of Community Development
6300 Southcenter Boulevard. Suite fF100
Tukwila. Washington 98188
Phone: 206-431-3670
Fax: 206-431-3665
Web site. //tip.i/www.ci.tui.-Iri/o.wa. us
Revision submittals utast be submitted) in person at the Permit Curter. Revisions will not be accepted through
the mail, fax, etc.
Date: 08/22/2013
Plan Cheek Permit Number: .D 13-257
Response to Incomplete Letter
f R• esponse to Correction Letter 1
7 Revision # after Permit is Issued
EI R• evision requested by a City Building Inspector or Plans Examiner
Project Name: J Crew
Project Address: 535 Southcenter Mall
Contact Person: k2J - Phone Number: -%03 - L 1 q
Summary ofRevision: We have updated our plans and calculations to be
compliant with the 2012 International Building Code with Washington
State Amendments and local City of Tukwila codes. We have also
added the required Statement Special Inspections to the plans.
0
r:IvvY �.
Sheet Number(s): 1
AtJ6 28 2013
"Cloud" or highlight all areas of revision including date of revisit
Received at the City of Tukwila Permit Center by:
Nj Entered in Permits Plus on (' (
,appli.r.ti.0 s'! i1 1 -dJ pli,rti >i2 un l;'nc`re\ iaiun ubniiUal
Crated: -1=-204
PERMIT CENTER
Contractors or Tradespeople Prier Friendly Page
•
General/Specialty Contractor
A business registered as a construction contractor with Lal to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name J D BUILDERS UBI No. 601801265
Phone 7142401340 Status Active
Address Po Box 2458 License No. JDBUI**037LT
Suite/Apt. License Type Construction Contractor
City Capistrano Beach Effective Date 6/30/1997
State CA Expiration Date 3/1/2015
Zip 926242458 Suspend Date
County Out Of State Specialty 1 General
Business Type Individual Specialty 2 Unused
Parent Company
Business Owner Information
Name
Role
Effective Date
Expiration Date
URICH-SCOLMAN, DENISE MARIE
Owner
01/01/1980
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
7
Platte River Ins Co
41258611
06/30/2012
Until Cancelled
$12,000.00
08/16/2012
6
AEGIS SECURITY
INSURANCE COMPANY
521001
06/30/2011
Until Cancelled
07/02/2012
$12,000.0007/18/2011
5
GREAT AMER INS CO
OF NY
790286532715
06/17/2010
Until Cancelled
06/19/2011
$12,000.00
06/21/2010
4
AMERICAN NATIONAL
FIRE INS CO
790286532715
06/05/2002
Until Cancelled
06/19/2010
$12,000.00
03/01/2006
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
9
Associated
Industries Ins
Co I
AES102453401
10/02/2013
10/02/2014
$1,000,000.0010/17/2013
8
ASSOCIATED
INDUSTRIES INS
CO I
AES1024534
10/02/2012
10/02/2013
$1,000,000.0003/01/2013
7
Essex Ins Co
CLS013398
09/21/2009
09/21/2011
$3,000,000.0005/17/2011
Summons/Complaint Information No unsatisfied complaints on file within prior 6 year period
Warrant Information No unsatisfied warrants on file within prior 6 year period
Infractions/Citations Information No records found for the previous 6 year period
https://fortress.wa.gov/lni/bbip/Print.aspx
10/31/2013