HomeMy WebLinkAboutPermit M13-053 - FUSE NETWORKS - REPLACE ROOF TOP UNITS
This record contains information which is exempt from public disclosure
pursuant to the Washington State Public Records Act, Chapter 42.56 RCW
as identified on the Digital Records Exemption Log shown below.
M13-053
Fuse Networks
12628 Interurban Ave S
DIGITAL RECORDS (DR) EXEMPTION LOG
THE ABOVE MENTIONED PERMIT FILE INCLUDES THE FOLLOWING REDACTED INFORMATION
Page # Code Exemption Brief Explanatory Description Statute/Rule
The Privacy Act of 1974 evinces Congress'
intent that social security numbers are a private
concern. As such, individuals’ social security
Personal Information –
numbers are redacted to protect those
Social Security Numbers 5 U.S.C. sec.
individuals’ privacy pursuant to 5 U.S.C. sec.
DR1 Generally – 5 U.S.C. sec. 552(a); RCW
552(a), and are also exempt from disclosure
under section 42.56.070(1) of the Washington
552(a); RCW 42.56.070(1)
State Public Records Act, which exempts under
42.56.070(1)
the PRA records or information exempt or
prohibited from disclosure under any other
statute.
Redactions contain Credit card numbers, debit
card numbers, electronic check numbers, credit
Personal Information –
expiration dates, or bank or other financial
RCW
60 DR2 Financial Information –
account numbers, which are exempt from
42.56.230(5)
disclosure pursuant to RCW 42.56.230(5)
RCW 42.56.230(4 5)
,
except when disclosure is expressly required by
or governed by other law.
FUSE NETWORKS
12628 INTERURBAN AV S
M13-053
City ahukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-431-2451
Web site: http://www.TukwilaWA.gov
MECHANICAL PERMIT
Parcel No.: 0004800003
Address: 12628 INTERURBAN AV S TUKW
Project Name: FUSE NETWORKS
Permit Number: M13-053
Issue Date: 03/18/2013
Permit Expires On: 09/14/2013
Owner:
Name: GATEWAY OLYMPIA INC
Address: PO BOX 4900 #207 , SCOTTSDALE AZ 85261
Contact Person:
Name: DAWNA PETET
Address: 899 W MAIN ST , AUBURN WA 98001
Email: DAWNAP@SEATTLEMECHANICAL.COM
Contractor:
Name: IECS INC.
Address: P.O. BOX 19252 , SEATTLE, WA 98109
Contractor License No: IECS***044QL
Phone: 253 939-9495
Phone: 206 939-9495
Expiration Date: 11/20/2014
DESCRIPTION OF WORK:
ADD (3) NEW ROOFTOP HVAC UNITS. INSTALL EXHAUST FANS FOR LUNCHROOM AND (2) NEW
RESTROOMS. PROVIDE DUCT SYSTEMS FOR NEW OFFICE AREA.
Value of Mechanical: $10,000.00
Type of Fire Protection: UNKNOWN
Electrical Service Provided by:
Permit Center Authorized Signature:
I hereby certify that I have read and
governing this work will be complied
Fees Collected: $306.06
International Mechanical Code Edition: 2009
Date:
amin-d this permit and know the same to be true and correct. All provisions of law and ordinances
'th, hether specified herein or not.
The granting of this permit does not pres e to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign and obtain this mechanical permit and agree to the conditions on the
back of this permit.
Date: 34 g-13
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
...-. 11A!" A14"
RA4'A AC 1
D...de.l• A1_1111_O/111
PERMIT CONDITIONS
Permit No. M13-053
1: ***BUILDING DEPARTMENT CONDITIONS***
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431-3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
6: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap the sanitary
sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks, wells, and other
excavations. Final inspection approval will be determined by the building inspector based on satisfactory completion of
this requirement.
7: Manufacturers installation instructions shall be available on the job site at the time of inspection.
8: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the City of Tukwila
Building Department (206-431-3670).
9: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206-431-3670).
10: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
doe: IMC -4/10
M13-053 Printed: 03-18-2013
•
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
•
Mechanical Permit No.
Project No.
Date Application Accepted:
Date Application Expires:
02)17g 3
PC 11
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
/1444K King Co Assessor's Tax No.: 000410 0 0 0
Site Address: /09-6(9t 8 11 r' ur bical totoeSD s Suite Number: _ Floor:
Tenant Name: ) SC n f yS New Tenant: i Yes ❑ ..No
PROPERTY OWNER
Name:6 iLe toad6I yifis Tryr
Address:/0/ ca/i.(rlG_y'-
-Plow
City/If1 c SCOState: 04
Zi 111
CONTACT PERSON — person receiving all project
communication
II '' q t ay- (
Name:/,hr0s to k / uomp.Q,%'i'
Address:: scri lio ►VI's 0. .v`J S . 0153136
City: illi.
State `' Zipb1RODi
Phone: 0N
/
'r S- O2.., _fax: 0153—Q. - . 6.1)
Email: _ nr
di risc..rJ(d s-ea-l - 2.117.ee [lX ti)
MECHANICAL CONTRACTOR INFORMATION
G{ __iii, /► _
Company Name:x5 J 10
'
r
Address: qq IV , , , lnwL ..
D U &
City: , %lam 1
PhoneG ,...t3 9l/4T7 Ea x:0158` -q 0
Conteg _No 4 w_Q 1..... Exp Da/f: ^ / 3
Tukwila Business License No.: p) ,s ... Onnop b
-9'95
e.G : da wlnq rpe1)&a ico Q . tan
Valuation of project (contractor's bid price): $ (0, 000 . 00
Describe the scope of work in detail:
ktd. 3 (J W ROaOap 14vel-c, USL-ks . E44&us+ Fps For ILA -AA roam ; a hew r-ese-rn.s
P -v gat-ck\k 4 5y54-- Aims for 1w3 o
Use: Residential: New ❑ Replacement ❑
Commercial: New ¶I Replacement
Fuel Type: Electric
Gas 91 Other:
H:Wpplications\Forms-Applications On Lme2011 Applications\Mechanical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Furnace >100k btu
Floor furnace
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cooling
system
Air handling unit
<10,000 cfm
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system
Hood and duct
Incinerator — domestic
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
Thermostat
Wood/gas stove
Emergency generator
Other mechanical
equipment
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDI NER OR AUAIOVIZED A ENT: q
Signatur )0041 'L L5't1 L (keen ?O Date: ' i 3
Print Name:
wfut
Mailing Address: S 1 ; Mai& 5±
Day Telephone: 0?53 9 3q -
H:\Applications\Forms-Applications On Line \2011 Applications\Mechanical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
City State Zip
Page 2 of 2
C* of Tukwila,
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206-431-3665
Web site: http://www. ci. tukwila. wa. us
SET RECEIPT
RECEIPT NO: R13-01069
Initials: JEM
User ID: 1165
Payee: IECS, INC.
Payment Date: 03/18/2013
Total Payment: 341.45
SET ID: 0318 SET NAME: FUSE NETWORKS
SET TRANSACTIONS:
Set Member Amount
M13-053 244.85
PG13-032 96.60
TOTAL: 2T2171113—
TRANSACTION LIST:
Type Method Description Amount
Payment Check 54014 341.45
TOTAL: 341.45
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
GAS - NONRES 000.322.103.00.0
MECHANICAL - NONRES 000.322.102.00.0
96.60
244.85
TOTAL: 341.45
SET RECEIPT
RECEIPT NO: R13-00960
Initials: JEM
User ID: 1165
Payee: IECS, INC.
Payment Date: 03/05/2013
Total Payment: 85.36
SET ID: S000001938 SET NAME: Tmp set/Initialized Activities
SET TRANSACTIONS:
Set Member Amount
M13-053 61.21
PG13-032 24.15
TOTAL:
TRANSACTION LIST:
Type Method Description
Amount
Payment Check 53922 85.36
TOTAL: 85.36
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
PLAN CHECK - NONRES
000.345.830
TOTAL:
85.36
85.36
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
rn3-653
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila: WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Project:
Project:
81WOR S
Type of Inspection:
} Ir..iAi._
Address:Date
! 2-(29 _%-NI;i.Q11Rt,ik1
Called:
Special Instructions:
Date Wanted:.
3 -13
a.m�
p.m.
Requester:
Phone No:
l•Approved per applicable codes. El Corrections required prior to approval.
COMMENTS:
4)efir i --franvt - 4' //7--a/4
r:
Dat_
ErEINSPECTION FEE REQUIRED. Prior t9 ext inspection. fee must be
aid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION NO.
CITY OF TUKWILA BUILDING DIVISION7/,'
6300 Southcenter Blvd., #100, Tukwila. WA 98188 e-. (206),431-3670
Permit Inspection Request Line (206) 431-2451
INSPECTION RECORD
Retain a copy with permit
613-653
PERMIT NO.
Project:
t-- .1N‘CIV OR14 i
Type of Inspection:
Q.01t6i-1 —.11N/1
Address:
1 P.4, -2—P)
%
1 Q.
Date Called:
?J
Special Instructions:
Date Wanted:.
3 ---ick ..i2)
, a€ .m':
p.m:
Requester:
Phone No:
,a_533 r ft^y LIC
[pproved per applicabletcodes.
Corrections required prior to approval.
COMMENTS:
t,r t RAnr1;
; 7(LI t4 --)J_'
(N
f�
r6.de
csle
jisspectoi
r7REpi
pa, at
f .
ECTION FEE REQIJ\RED. Prior to n xt inspection, fee. must:be;
6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Date:
CT
ENGINEERING
INC.
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512(V)
(206) 285-0618(F)
STRUCTURAL CALCULATIC� - ettrol1
New RTUs and Window Openings
Fuss Networks at Tukwila Commerce Park
Building C: 12628 Interurban Ave.
Tukwila, WA
Scope of Work: Provide support as required for (2) 5 -Ton and (1) 3 -Ton roof
top mounted mechanical units. Design lateral support system from seismic
forces. Design two window openings in the exterior concrete wall.
Code: IBC 2009 Edition
Loads: Snow 25 PSF
Wind 85 MPH, Exp B
Seismic SDs= .986
Structural Engineers
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAR 1 3 2013
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
MAR 0 5 2013
PERMIT CENTER
MLrO3
C T
ENGINEERING
Project• FOSC klel*lor1
1 N C.
Client:
L.: F.-k(s11'r4 cl : 1\ Q- - - 4 ►- / • T-lluroRti l
Date:
Page Number;
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
PAX:
(206) 285-0618
►o
1o00 •3I4aL-43
SNo.)
S(15+- )
or
WO S3.
zo
`VI, : -F - . 1 T = to -64
��.
c) MoD 5\(e S _ �`15,`i.5
I.& ..
s Q`
Tett
?.l
_: 157. rb\.
b 19 mob . . 4
lt—IL
t1114Lew Go° '
Structural Engineers
C T
ENGINEERING
Project: FvsE- ► 12.e—
1 N C.
Client:
Date: 74/1.3
Page Number:
2
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
PAX:
(206) 285-0618
Structural Engineers
C T
ENGINEERING
INC.1'
Prolcct: FVS iE1\11/Cf ..S Tuk.WILI
Client:
Date:
u/�3
2124
Page Number: Sy-_`
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
PAX:
(206) 285-0618
Structural Engineers
C T
ENGINEERING
�` `' 1NC.
-SSS
Project: NI1 �J00.X 1614—Ni t ll -44
Date:
21243
Client: Page Number: e'
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
rAx:
(206) 285-0618
Structural Engineers
C T
ENGINEERING
1 N C.
Project: FO Sim K�1 \ luta - ` TOV
Client:
Date:
z/ zo'i3
Page Number:
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
PAX:
(206) 285-0618
Structural Engineers
C T
EN GIN EERING
1 N C.
Project: Fi N���n10 S — TukwfL/�
Client:
u/�3
Date: a/20(13
Page Number: SiV-- 1
180 Nickerson St.
Suite 302
Seattle, WA
98109 '
(206) 285-4512
FAX:
(206) 285-0618
Structural Engineers
C T
ENGINEERING
I N C.
Project: FOSS' NE:1W01 .— TikwI1..%
Client:
Date: 2-1W`i ,
Page Number: 6 14'2.
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285-4512
FAX:
(206) 285-0618
Z7CToik FL5
2$' i'660ele- Nc,.
01417
Nv1c.N Z7,10 dk"10 ls S c 2am s
S I. U NI 11 e :CvnPS Ml.l 8.•
� Lurr To
n2x4-
LE' PuRLi)a
(..-) s7E►- a o)s
a., o
Structure! Engineers
C T
ENGINEERING
Project:
INC.
Z) 5 twE.1 v� — Tuk.m Lat..
2122113
Date: 70/13
Client: Page Number: 516-3
180 Nickerson St,
Suite 302
Seattle, WA
98109
(206) 285-4512
FAX:
(206) 285-0618
Structural Engineers
C T
ENGINEERING
�`INC.
Project: FU Se" NE-114°Q.� TUV--\#41(LA•
Date'
-2/70/t3
Client: Page Number: S
180 Nickerson St.
Suite 302
Seattle, WA
98109
(206) 285.4512
FAX:
(206) 285-0618
•
•
•
.1/1{-k 3:y. 0`,.%
vi/ a- Ye 4))0;
S rthc.Lcs. ,
0
I -s$ 4 4x1
•,,
3=c�:
to
3/8:.)..492.74.c.1 -1:o " -
W/ 2-V2 4>r 3 TITMN Hip
Structural Engineers
SUBMITTAL
Project
Untitled 17
Date
Wednesday, February 13, 2013
PI�F
COPY
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAR 13 2013
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
MAR 0 5 2013
PERMIT CENTER
Project:-Untitledl7
Prepared By:
Table Of Contents
02/13/2013
12:52PM
5 Ton..
Unit Report ............ .
Certified Drawing ...............
Performance Summary..... .
Unit Feature Sheet . ... . .
3 Ton ............ .. .......
Unit Report ........... .
Certified Drawing ......... .
Performance Summary....
Unit Feature Sheet .............
3
4
5
8
11
12
13
14
17
20
Packaged Rooftop Builder 1.34 Page 2 of 20
Project:-Untitledl7
Prepared By:
5 Ton
02/13/2013
12:52PM
5 Ton
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Spec Sheet
Unit Feature Sheet
Packaged Rooftop Builder 1.34 Page 3 of 20
Project:—Untitledl7
Prepared By:
Unit Report For 5 Ton
02/13/2013
12:52PM
Unit Parameters
Unit Model: 48TCDA06A2A6-0A0A0
Unit Size: ............ ...... 06 (5 Tons)
Volts -Phase -Hertz: . 460-3-60
Heating Type:. Gas
Duct Cfg:.... .. Vertical Supply / Vertical Return
Low Heat
Round Tube Plate Fin Coils
Lines and Filters
Gas Line Size: ..... .......
Condensate Drain Line Size:
Return Air Filter Type:....
Return Air Filter Quantity:
Return Air Filter Size:....
Unit Configuration
Medium Static Option
AI/Cu - AI/Cu
Base Electromechanical Controls
Standard Packaging
1/2
3/4
Throwaway
2
16x25x2
Warranty Information
1 -Year parts(std.)
5 -Year compressor parts(std.)
10 -Year heat exchanger - Aluminized(std.)
No optional warranties were selected.
Dimensions (ft. in.) & Weight (Ib.) •.t
Unit Length:. ........
Unit Width:....... ...
Unit Height: .............
••• Total Operating Weight: .. ....
6' 2375"
3' 8"
T 9375"
744 Ib
"' Weights and Dimensions are approximate. Weight does
not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number
Description
Quantity
48TCDA06A2A6-0A0A0
Rooftop Unit
2
Accessories
CRECOMZR020A02
Vertical EconoMi$er IV with solid-state controller
2
CRRFCURBOOIA01
14 -inch Tall Roof Curb
2
Packaged Rooftop Builder 1.34
Page 4 of 20
Project: -Untitledl7
Prepared By:
Certified Drawing for 5 Ton
02/13/2013
12:52PM
NOTES:
1. DINEN5I005 ARE IN INCNES DIMENSIONS
IN 1 1 ARE IN MILL(M010 S.
2. S CENTER OF GRAVITY
3. MO. DIRECTION OF AIR FLOW
UNIT
48TC-ADA
33 3/5
(8471
185/5
11721
48TC-505
33 3/8
(8471
141/5
13711
487C -A06
33 3/8
(8/47
147/5
13171
481C -A07
41 3/8
11051]
14 7/8
13711
FILTER ACCESS PANEL
(TOOL-LE531
-
COMP.
ACCESS
• PANEL '
0
•_
CONDENSER
COIL
1
INDOOR COIL
ACCESS PANEL
t ,r a (1(3
tTI 1T1 7 �
BACK
2-5/5
1611
TOP
CURB
WIDTH
44
4-5/8
11181
LECTRICAL
DISCONNECT
LOCATION
OPTIONAL
FACTORY
INSTALLED
CONVENIENCE
OUTLET
10-1/2
144/
3-3/4
(951
463/4
LEFT
33 are
18/51
0
UNITED 1.0, 00I 4506
TECHN0106(E511uau, 11
CARRIER 15011
1
1
0 (0 553N1Y11E1[0 4005 115*5555055]11ACORPORATION
1 5r1
15411111 rlll 1011[ DG5l01D OR5 UN[0 /ITNOR 15RA7[0
10000151101 01rr11 1015111.
NLNNI1IION 0r 1505[ 1511110 54 001010111
0010 001 101111010 0511 I[1101AIOR 011
51110151[[ a 10110101.
ECONOMIZER HOOD
(OPTIONAL)
1
SEE THRU THE
BASE CHART
25
(6361 —^
25-5/8 —�
16521
RETURN AIR
16
14061
10-7/8
(2771
4.
RETURN
AIR
0
E ALT. J
CONDENSATE
DRAIN OPENING
IN BASEPAN
17-3/4
(1511
SUPPLY
AIR
6. 7A
J1571
/ —i LH
(1001 /4000
TOP
12-1/6
13071
18-1/2 --�.
(4701
CONTROL BOR
ACCESS PANEL
INDOOR BLOWER
ACCESS
OPTIONAL
FACTORY
INSTALLED
DISCONNECT
HANDLE
(18581
FRONT
26-1/2
(6737
21-3/6
(7611 SUPPLY
AIR
3-3/5
(851
THRU-THE-BA E CHART
THESE HOLES 6102)600 FOR USE
CRBTMPWR001A01, 003A01
CONNECTION SIZES
A
1 3/0' 1351 DIA FIELD POWER SUPPLY HOLE
B
2' (501 DIA POWER SUPPLY KNOCKOUT
C
1 3/4' (511 DIA GAUGE ACCESS PLUG
0
1/8' 1221 DIA FIELD CONTROL WIRING ROLE
E
3//'-11 NPT CONDENSATE DRAIN
F
1/2'-11 680 GAS CONNECTION
G
2 1/2 ' (611 DIA POWER SUPPLY KNOCK -OUT
THRU-THE-BA E CHART
THESE HOLES 6102)600 FOR USE
CRBTMPWR001A01, 003A01
THREADED
WIRE
600'D HOLE
CONDUIT SIZE
USE
SIZES 1MA6.1
N
1/2'
ACC.
7/8' (12.27
I
1/2'
24V
7/8. 122.21
1 1
3/4' 1001,0031
POWER
1 1/8. 128.41
215
(0031 1/2' FPT
GAS
1 3/16' 130.01
FOR 'THRU-THE-DASEPAN' FACTORY OPTION
FITTINGS FOR ONLY 2,1, 1 2 ARE PROVIDED
SELECT EITHER 3/4' OR 1/2'
0
FOR POWER, DEPENDING ON WIRE SIZE
5110011
PROVIDES 3/4' FPT DOWCURB
FLANGE 6 FITTING.
11-3/8
OUTSIDE
AIR
401111
21-1/4
15311
17931
SUPPLY
AIR 4061355
RIGHT
BAROMETRIC
RELIEF
FLOW
SKIT
10F2
011
11-24-08
10(1111011
09-29-08
48TC 04-07 SINGLE ZONE ELECTRICAL
COOLING WITH GAS HEAT
48714500993
5.0
Packaged Rooftop Builder 1.34
Page 5 of 20
Certified Drawing for 5 Ton
Project:-Untitledl7
Prepared By:
02/13/2013
12:52PM
UNIT
STD. UNIT
WEIGHT
CORNER
WE1GN1 (41
CORNER
WEIGHT 181
CORNER
WEIGHT ICI
CO NER
WEIGHT (DI
C.G.
HEIGHT
L85.
K0,
LBS.
KG.
LBS.
KG,
LBS.
KG.
LBS.
KG.
8
T
2
491C -*04
463
211
111
50
125
51
131
59
111
53
30 [9911
23 (5841
16 3/8
[1111
481C -A05
531
244
124
56
139
63
145
86
129
59
39 (9911
23 (5841
17 (4321
481C-606
569
256
131
58
141
67
154
70
137
62
39 (9911
23 (5841
17 1/4
04361
487C-407
852
296
150
68
169
76
176
80
157
71
39 09911
23 25841
20 1/8
(5111
CORNER A
TOP
1
CI
00
0
UNITED I.D. ICI OOP
TECHNOL061ES Minn, 8T
CARRIER ,8n1
TNII 80(25011 15 TIE 001(111 0 an1E1 0080811101
115 I5 1(1InI8 0701 116 I51DEu 10/810108 5X.11 171
C01E115 8511 107 1E 81581(0 0 5058 015x1(1 (0808085[5
02008A1101 5591710 (28(11.
31.41111/1011 01 0158[ 81A70185 0 OCU12nS
01(5 NOT (08511T01E PANT rc1/0ANINCT m
ACCEPT/AI Of (0118011.
CORNER 8
CORNER C
FRONT
MET
2 OF 2
m0E
11-24-08
501(1(11(5
09-29-08
48TC 04-07 SINGLE ZONE ELECTRICAL
COOLING WITH GAS HEAT
481M500993
5.0
Packaged Rooftop Builder 1.34
Page 6 of 20
Certified Drawing for 5 Ton
Project:-Untitled17
Prepared By:
02/13/2013
12:52PM
RCCFCURIJ
ACCEESCRYA
A
aaau1em11m
AOt
24
�+rn
I1
1
14
NTMES
1
2187AT®Ra85 MTWYCLYL/ETM8EFOWAM1$1346Ma•G1IY
APCCR1f8t8C,AC SIS
5AT7
rDN.
�TnrFAasnE
. A10P10FAAC
sfcRntalT76Cl.R8GASIYPE
pADRIECREITMANRIPAOUSFCRIMILRFERTIMTATIPEGISMAI,ECTIONS
5A2
1137.71
1
21.74
MA
1}
P
—�
11B
Pmol
1
1
s- l
498 J
7087*
Sema
19
1r".-2124.E
oPe�lG
�4'44
E
t
3219
1 f
Fe
1
1 �
9-FPLYAR
c�+�G
1 1
21
1877LI
1.75.
E
1_2141 --4..
81831
0099
— 3DP
1179
P534
CORNERDETAL
GASOOJ 2C11CF 1'PE
POA6NR3G
RTT7•C
OONIRCUAIR JC
FMNG
ACCECCCRICCNVDECE
CUTLEMAIRNOON=iOR
3'4S91PPT
nnmEEorTCR4
12p2.11141
311i13PPT
1/2112.71WT
12t12.7PPT
1+11314
sEc11oN E E
41U Fm4
A
IM1•031101r41S/@
NaMPm19NDOUNRc9
ffHD31718a
tm t
M.0
11311/25851wfE
731ATMES
8918 2I75JW87E
►31A713:CEO4PMEL
SEE VIEW"B"
CERWEDDRAWNG
57-718"
n72191
1314"
ORANNORBFAYtEN1
PRODUCTION
11YOMliE
11011
1AA19a"L
RI4E900ERWSESEis®
W6BpR4FRaaiNETEJa
lusty 6nw
SLIPS: 2QFS 21£6 !!2
.1 "1A *OS 12'
Cala
AURedTeYrbbjesCmpsy
TaaoaAaR RDRIERlo Awric )vrtNW11EREN
ispfrpREraRyitrAPAIEROMKR.,1O1N69M11Of
rTQrn£ARIII.V. ICWAna4i A
A1111O VA11W11ffA
1041738
EtoREERNOMoIRElen
T -005•Y-002
vN.F.Cita o
SY,Ra r
153400
EfurrER
A4c 011701
1NEoaA
ERE
D
oRayitatAAam
4
mom 565
REV
A
OR2
REV
REMYWRE00f0
[ATE
5..
oc•0
Wf..5
arwln
AVRACER®1j AfTAIOI
I tel/
IEEtxn
PetTORAVANO
Nr.
osIRanICN
Packaged Rooftop Builder 1.34
Page 7 of 20
Project:—Untitledl7
Prepared By:
Performance Summary For 5 Ton
02/13/2013
12:52PM
Part Number:48TCDA06A2A6-0A0A0
ARI SEER:....
Base Unit Dimensions
Unit Length:..
Unit Width:
Unit Height:.
Operating Weight
Base Unit Weight:.........
...........
Medium Static Option:.
Accessories
Vertical EconoMi$er IV with solid-state controller:
14 -inch Tall Roof Curb:
Total Operating Weight:..
Unit
Unit Voltage -Phase -Hertz:..
Air Discharge:
Fan Drive Type:.. ... . .
Actual Airflow:... ....
Site Altitude:......... .. .... ..
Cooling Performance
Condenser Entering Air DB:.. .. .
Evaporator Entering Air DB:... . .
Evaporator Entering Air WB:... . ..
Entering Air Enthalpy: ..
Evaporator Leaving Air DB:... . ..
Evaporator Leaving Air WB:..........
Evaporator Leaving Air Enthalpy:...
Gross Cooling Capacity:...... .. .
Gross Sensible Capacity:. .. ......
Compressor Power Input:... .. .
Coil Bypass Factor:....
13.00
74.4 in
44.0 in
33.4 in
569 Ib
10 Ib
50 Ib
115 Ib
744 Ib
460-3-60
Vertical
Belt
2000 CFM
0 ft
95.0 F
80.0 F
67.0 F
31.44 BTU/lb
57.9 F
57.3 F
24.56 BTU/Ib
61.90 MBH
47.70 MBH
4.43 kW
0.055
Heating Performance
Heating Airflow: 2000 CFM
Entering Air Temp:..... 70.0 F
Leaving Air Temp 97.3 F
Gas Input Capacity72.0 MBH
Gas Heating Capacity:... 59.00 MBH
Temperature Rise:.... ... 27.3 F
Supply Fan
External Static Pressure -
Options / Accessories Static Pressure
Economizer:...
Total Extemal Static:
Fan RPM:...
Fan Power:.....
NOTE:...__ ... ........ . .
1.00 in wg
0.12 in wg
1.12 in wg
1442
1.64 BHP
Selected IFM RPM Range: 1035 -1466
Electrical Data (Before July 30, 2012)
Minimum Voltage:.. 414
............ .
Maximum Voltage:...... 506
Compressor RLA• 7.7
Compressor LRA 52
Outdoor Fan Motor Qty: 1
Packaged Rooftop Builder 1.34 Page 8 of 20
Project:-Untitledl7
Prepared By:
Performance Summary For 5 Ton
02/13/2013
12:52PM
Outdoor Fan FLA (ea)'
Indoor Fan Motor Type:.
Indoor Fan Motor FLA:.... ...
Combustion Fan Motor FLA (ea):
Power Supply MCA: ............. ............
Power Supply MOCP (Fuse or HACR):.
Min. Unit Disconnect FLA:.
Min. Unit Disconnect LRA:...
Electrical Convenience Outlet:
Electrical Data (July 30, 2012 and Beyond)
Indoor Fan Motor FLA:
Power Supply MCA: .. .
Power Supply MOCP:
Disconnect Size FLA:
Disconnect Size LRA:
0.8
MED
2.6
024
13
20
13
69
None
July 30th and beyond units can be identified by serial number 3112XXXXXXXXX and higher
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 89.6 88.5 84.0
125 Hz 84.6 81.9 82.2
250 Hz 78.1 69.3 76.3
500 Hz 73.6 65.9 74.8
1000 Hz 69.9 65.0 72.5
2000 Hz 64.7 59.5 68.8
4000 Hz 66.5 55.2 65.6
8000 Hz 62.2 48.7 61.8
A -Weighted 77.0 71.3 78.0
Advanced Acoustics
Advanced Accoustics Parameters
1. Unit height above ground- 30.0 ft
2. Horizontal distance from unit to receiver: 50.0 ft
3. Receiver height above ground:... 5.7 ft
4. Height of obstruction 0.0 ft
5. Horizontal distance from obstruction to receiver 0.0 ft
6. Horizontal distance from unit to obstruction. 0.0 ft
Detailed Acoustics Information
3.4
14
20
14
82
Octave Band Center Frequency, Hz
63
125
250
500
1k
2k
4k
8k
Overall
Sound Power Levels at Unit's Acoustic Center (Lw), dB
84.0
82.2
76.3
74.8
72.5
68.8
65.6
61.8
87.2 Lw
A -Weighted Sound Power Levels at Unit's Acoustic Center (LwA), dBA
57.8
66.1
67.7
71.6
72.5
70.0
66.6
60.7
77.7 LwA
Sound Pressure Levels at Distance Specified above (Lp), dB
51.6
49.8
43.9
42.4
40.1
36.4
33.2
29.4
54.8 Lp
A -Weighted Sound Pressure Levels at Distance Specified above (LpA), dBA
25.4
33.7
35.3
39.2
40.1
37.6
34.2
28.3
45.3 LpA
Packaged Rooftop Builder 1.34
Page 9 of 20
Project:—Untitled17
Prepared By:
Performance Summary For 5 Ton
02/13/2013
12:52PM
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
20
18
16
GI
02
FanCurve
03 C6 Q9 12 15
Actbw(CFM-th cusands)
RPM= 1442 BHP= 1.64 MaximumRPM= 1466MaximumHP=2.90
Note: Please contactapplica1ion eeringforselectionsoutsidetheshadedregion.
SC-SystemQnveRP-RatedPoint
18 21
24
27
Packaged Rooftop Builder 1.34 Page 10 of 20
k
w
a
-
r ylr •`1.4...-
1100RFN1
4 "
\
Ido
%
/..
.
\
t \�
soORFiv1•
11�„
a
°
a 3.00BHP
70(iiPM
���
a
tss
U75BHP °
It 00BIfl
t
1
1
1
I --- I
\m _
4. _ j�1 2:t
nE .;
\_
:. J1
,
I' ' 11 1'
_ _ L
03 C6 Q9 12 15
Actbw(CFM-th cusands)
RPM= 1442 BHP= 1.64 MaximumRPM= 1466MaximumHP=2.90
Note: Please contactapplica1ion eeringforselectionsoutsidetheshadedregion.
SC-SystemQnveRP-RatedPoint
18 21
24
27
Packaged Rooftop Builder 1.34 Page 10 of 20
Project:—Untitledl7
Prepared By:
Unit Feature Sheet for 5 Ton
02/13/2013
12:52PM
WeatherMaker — 48TC
PACKAGED ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
3, 4, 5, 6, 7.5, 8.5, 10, 12.5, 15 TONS
Optional Louvered Hail Guard Showa
WEATHERMAKER SERIES
WeatherMaker(48TC) units are one-piece gas heating, eledric
cooling units that are pre -wired and charged with Puron
(R-410) refrigerant They are factorytested in both heating
and cooling modes, and rated in accordance with AHRI
Standards 210/240(04-06 sizes) and 340/360 (07-16 sizes).
WeatherMaker units are designed in accordance with UL
Standard 1995, and listed by the Underwriters' Laboratories.
Approved and certifiedby:
us
Certified to ISO 9001
STANDARD FEATURES INCLUDE:
• Phan (R-413A)HFC ref event
• AS$ RAE33.1 tnerayoomolsni
• ScroI comoressos wan internei b eskand ovenoad protection
• 5;n;4 -stage coo ling cepoorly cont•oion•34.12model
• Two-stspecorAngcepa aayxnt.cron09.15models
• SEER3 up to 13:3. EER's up to 11.1 end IEER's up to 11.9
• Acuter?". re frlaemni.metering systern
• Exc.:11we npngprros!ve compai tecondensete pan in 1071rdanae a�th
ASHRAE Standa+d 52. sipping desian, side orcanterdrain
• Stanch Jcpcenaoperstion up to 115'F;46'C; and down to 43'F
- down to 25'F (4' C; %with winter start kit.
• P•e-o•intedextera:pane!send prime•-:astad intoro•pane 4tested to
533hours silt spray protection
• F,, 1nautstedeabinet
• ExpusiveIGCsold-stet trontro'fpror+-boald°agnastios'.w1hLEC
er.-orcodedesianstian bumercont•ol49c .id .r.y,J v19 indoo•
fen nobrdeSty
• LowI'3x model that meet fora A r aua`ty Management
• Induced d7ftgoo heat combustion design
• Red,ndent gas valves wan Jp 10 nvo stages of heating
• Low prase;!le and pian p!essu:e switch p'ptect.ed.
MAINTENANCE FEATURES:
• Amos* panels with essygrio handles
• Innovative •asy'starting, no -stet.) s0IDwi on tint sooess pane';
• Two -incl d1posab7e atum air files and To!asss f114. 80x55 dap!
• Belt dri'eevaoorstor-fan motor and ouiaycombinations
• 1 ewterminai boardfaclitat:ng simo4 safelycirciii4 troJbieshpotin•a and
s!rnpifed contra; box arrangement
• ExoiJave1Gt; said -state contro:for on-boarddiagnostics with LEC
em7rcodedes, nation• burnercontrp!hgo and energy saving indoor
fan rrotordelay.
IN STALLATION FEATURES:
• Th a cine-4attompawsrentrycapsbiidy.
• Singe point gots and eectr. connections
• Furpenrnster base roil wlh built-in nag 'mg ad aptens and fork vats
• F40 convertibefom venicai to norzo nteiaiihw for slab mounting.
(15 sit models require fetid instaratd supply duct cover;.
STANDARD WARRANTY:
• l3yeerhest exchlinger -15-yearsts:nessstee option
• 5•yearcompressa•
• 1 -year parts
• 3yearports on IdovationCondense•coys-where sysi!abe
• Msnyoptians' upgrades also available
OPTIONS INCLUDE BUT ARE NOT UNWED TO:
• PrernerLrnk"' and TR/ Open Multi Protocol DCC Contra's
• Suoo!ysnd Return Air Smoke Ceteotors. high state. motors
• Louvered oondensercoilguards
• Econom¢er. daconnect and convenience outlet options
• Sts iniessSteel hest excite nae•opt'on
• Carrosion.raextent 'L costing.
• Hu mid i-lel2er• ads obi. deh timidfcetion systemaysiiabie on all
modelswrth R7PF condtneer cors - Motor Master Icont•oter incLided
• singed gooses pane3
Fo• a compete list of options and aoaestones refer to the ProdJN Cats
C01s1ag fortnib unit.
Packaged Rooftop Builder 1.34 Page 11 of 20
Project:-Untitledl7
Prepared By:
3 Ton
02/13/2013
12:52PM
3 Ton
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Spec Sheet
Unit Feature Sheet
Packaged Rooftop Builder 1.34 Page 12 of 20
Project:—Untitledl7
Prepared By:
Unit Report For 3 Ton
02/13/2013
12:52PM
Unit Parameters
Unit Model :.. ...... .. ...... . 48TCDA04A2A6-0A0A0
Unit Size 04 (3 Tons)
Volts -Phase -Hertz: . 460-3-60
Heating Type: Gas
Duct Cfg:.... . Vertical Supply / Vertical Return
Low Heat
Round Tube Plate Fin Coils
Lines and Filters
Gas Line Size:. . . . .
Condensate Drain Line Size:
Return Air Filter Type:.
Return Air Filter Quantity:.
Return Air Filter Size:
Unit Configuration
Medium Static Option
AI/Cu - AI/Cu
Base Electromechanical Controls
Standard Packaging
1/2
3/4
Throwaway
2
16x25x2
Warranty Information
1 -Year parts(std.)
5 -Year compressor parts(std.)
10 -Year heat exchanger - Aluminized(std.)
No optional warranties were selected.
Dimensions (ft. in.) & Weight (Ib.) ***
Unit Length :...... _ .. . _ . _ ........... .....6' 2.375"
Unit Width:. 3' 8"
Unit Height:.. 2' 9.375"
*** Total Operating Weight:. . .... . 658 Ib
*** Weights and Dimensions are approximate. Weight does
not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number
Description
Quantity
48TCDA04A2A6-0A0A0
Rooftop Unit
1
Accessories
CRECOMZR020A02
Vertical EconoMi$er IV with solid-state controller
1
CRRFCURBOOIA01
14 -inch Tall Roof Curb
1
Packaged Rooftop Builder 1.34
Page 13 of 20
Project:-Untitledl7
Prepared By:
Certified Drawing for 3 Ton
02/13/2013
12:52PM
NOTES:
1. DIMENS1ONS ARE IN INCHES DIMENSIONS
INE 1 ARE IN MILL(I*0t0 S.
2. S CENTER OF GRAVITY
3. •
DIRECTION OF AIR FLOW
U1[13
/BTC -A01
33 3/8
[847]
18 5/8
[1121
18TC-A05
333/8
[8471
147/8
13771
48TC-806
33 3/8
[847]
147/8
[3111
18TC-A07
41 3/8
[10511
14 1/8
[371)
FILTER ACCESS PANEL
(TOOL -LESS)
COMP. ACCESS
• PANEL
0
CONDENSER
COII
'
INDOOR COIL
* ACCESS PANEL
qj(7L1 ] 37 �r r OG4J
BACK
2-5/8
[671
TIP
CURD
WIDTH
14
4-5/8
[1181
LECTRICAL
DISCONNECT
LOCATION
OPTIONAL
FACTORY
INSTALLED
CONVENIENCE
OUTLET
19-1/2
14941
3-3/1
[851 16 3/1
111315
LEFT
32 1/4
18181
•
333/8
18481
0
UNITED P.O. 301 1306
TECHNOLOGIES nn(1AT. IT
CARRIER 13221
1111 931843) 23 113 1108110/ 91 (111111 C010R103
131 11 0(31133181103 113 131423 1011110 01831 011
(0313113 RSL IDT 11 1231183(8 3 8119 I[TN03T coon
(811 1*110Y !Minn. 0081110.
838111630 m 144 1183/3163 0 OOCp1[1T6
00[6 ttIPART
31NZ
93311111123 Of
0
ECONOMIZER HOOD
(OPTIONAL)
18-1/6 1 1
[359]
(11(18 (38311 [311I211
1 SEE THRU THE
BASE CHART
16
11061
JC_
25-5/8
1652]
RETURN AIR
10-7/8
[2771
411111
RN
AIR
0
E ALT. —,
CONDENSATE
DRAIN OPENING
IN BASEPAN
RJ/1
.[1571
25
[6361
1 3/4
[4511
SUPPLY
AIR
11 1
26.1/2 29-3/6 1.011111'
[6 3] (] 1] SUPPLY
3-3/8 /
12-1/8 (851
(3011
18-1/2
(1701
OPTIONAL
FACTORY
INSTALLED
DISCONNECT
100
0
HANDLE
301/8
07641
- 8-3/8
743/
(18881
FRONT
[2131
A
THNU-THE-BA E CHART
THESE HOLES 80001008 FOR USE
CRBTMPWROO1A01, 003401
CONNECTION SIZES
A
1 3/6' 1351 DIA FIELD POWER SUPPLY HOLE
6
2' 1501 DIA POWER SUPPLY KNOCKOUT
C
1 3/4' 1511 DIA GAUGE ACCESS PLUG
0
1/8. 1221 DIA FIELD CONTROL WIRING HOLE
E
3/4'-11 NPT CONDENSATE DRAIN
F
1/2'-14 111,1 GAS CONNECTION
0
2 1/2 ' 1641 DIA POWER SUPPLY KNOCK -OUT
THNU-THE-BA E CHART
THESE HOLES 80001008 FOR USE
CRBTMPWROO1A01, 003401
THREADED
WIRE
9E0'D HOLE
CONDUIT SIZE
USE
SIZES 1961.1
9
1/2'
ACC.
T/8' 122.21
I
1/2'
240
7/8' [22.21
3 3
3/4' 1001,003)
POWER
1 1/8' [28.4]
203
(0031 1/2' FPT
6A5
1 3/16' 230.01
FOR '1X60-THE-BASEPAN' FACTORY OPTION.
FITTINGS FOR ONLY I.Y. S 2 ARE PROVIDED
SELECT EITHER 3/4' OR 112'
P
FOR POWER, DEPENDING ON WIRE SIZE
0.
(001) PROVIDES 3/1' FPT TH9U CURB
FLANGE 6 FITTING.
1-1/4
11-3/8
OUTSIDE
AIR
40111,
21-1/4
(539]
4-5/9
11681 [111)
26 3/1
(9911 31 1/4
[1931
SUPPLY 41,
AIR
RIGHT
9E1389
AIR
BAROMETRIC
RELIEF
FLOW
SKEET
1 OF 2 _
9303
11-24-08
mums
09-29-08
48TC 04-01 SINGLE ZONE ELECTRICAL
COOLING WITH GAS HEAT
48TM500993
81Y
5.0
Packaged Rooftop Builder 1.34
Page 14 of 20
Project:—Untitled17
Prepared By:
Certified Drawing for 3 Ton
02/13/2013
12:52PM
UNIT
STD. UNIT
WEIGHT
CORNER
WEIGHT (A)
CORNER
WEIGHT 18)
CORNER
WEIGHT (C)
CORNER
WEIGHT (D)
C.G.
HEIGHT
LBS.
KG.
L85.
K6.
LBS.
KG.
160.
N.
LBS.
K6.
I
1
1
4810-401
483
216
111
50
125
57
131
59
116
53
39 (9111
23 (5811
11 3/8
11161
4510-405
537
244
124
56
138
63
145
66
121
59
38 (9111
23 (5841
17 (4321
481C -A06
569
258
131
59
147
67
154
70
137
62
36 (8911
23 (5841
17 1/4
(1381
41TC-407
652
296
150
68
161
76
176
BO
157
71
31 (9811
23 (5841
20 1/8
05111
CORNER A
TOP
:100
1
: oo
UNITED P.O. /05110/
TECHNOLOGIES ITMCISE. 11
CARRIER 11121
11)5 10001E11 11 TIE 5101(111 05 0A111E1 ttl10..110.
111 12 0[(11(1(5 0555 TIE [IMES/ 105011155 TMl1 TME
OMITS RILE 101 If DISCLOSED 01 01(0 RITI011 CAM11(1
CORMAT101.1 51111(1 COMP.
155/111155 01 01150 11A111W 55 0000RI11
0010 MOT COI1T11u11 FAIT MIT5511MCE 55
A10EM ICE 01 C55TIACT.
CORNER B
CORNER C
FRONT
351E1
2 O 2 _
DAT(
11-24-08
l*F[ICEDEI
09-29-08
48TC 04-07 SINGLE ZONE ELECTRICAL
COOLING WITH GAS HEAT
48TM500993
5.0
Packaged Rooftop Builder 1.34
Page 15 of 20
Project: -U ntitled 17
Prepared By:
Certified Drawing for 3 Ton
02/13/2013
12:52PM
ROZECU B
ACOSS5Qt 0
A
CFSECUR9:01A01
15
Psi
25
Pal
n
1
N71ES
1
21SU AMPMHS25i4117M4POL
SATE
7. d4OFARRUN.
BCHSEE
aCC4AECTORPAO(A9IECFSTNPARCOVOISR:RTMMECUMGASTYFE
PAOMECREMPARVAMERR114412YEBOTICSAWECASOZMECBONS
1737.71
2175
MA
1
t4ea
547 --4-4..
F
11-93"
F10319
—
1
I1
. .
•9/
'1971
7017
1110321
17
i FA
RERfANQi
CPB/IG
93 itA14451
�1n
E
E
¢1 t
f17E1
1i
5E1
sumo R
CPENBG
UM
�7A
I
1
1.75 —!
Wisi
~
PIM
40E7
P1321 yI
`
PE
none
CORNERDETAL
COV CCI[7 iPOG
&C0Ul.ECM:HOPE
G49T71NG
FOAERAFTG
ROM
OCNTROUWFNG
R11N3
ACMCCOWCCNOENECE
OUILETWIR SCONECIOR
CR3I1.4Nfm1Mt
1H311HEOJ B
34110(N5f
CR317.15.ACIID401
7/1d1114EBOf1dA
344119NP7
1?{127PP7
12112.71NPT
MCTICN E -E
A
M.0
1131/99fl5T
NSUAT®CEO6'MHS
E9112¢1751WDE
N31ATIMIECKPM8
7410
3.13'15
SEE VIEW 'B'
ps0
Med
Pe/
REVIRMECCIPD
Dare
BY
IPD1H3
239
R11
WNG
57.7!5
(17
)
DHANEDI@HA¢1EV8.
PROCUC110N
grzr. COPPENSICNELPIEMILLIMEie
uvm-nvawuErxa>En
.1
,
1 25159 /9
1 110 •050 • 2•
coallatr
AUr44ed7m}P1o6pI®Carpa y
1144DODADrt,IPPNE. „1D1COPRANFOTOPETI
P TWATDWA®1
104173a
T.005N-002
.vwsrcn4vo
Tea
aRBraSYPCCF
(00440
I.EC 07117/11
0E0031
SCE
D
aA...nr„wER
4M:0342%
EEEEf 5/ 5
1�v
A
elw.lfwlmll rwrsam.
PURC11
E1mea+reaaul>SEoan
letTORAYMPI
BPJLE
NA
asmella
AlLIC
Packaged Rooftop Builder 1.34
Page 16 of 20
Project:—Untitledl7
Prepared By:
Performance Summary For 3 Ton
02/13/2013
12:52PM
Part Number:48TCDAO4A2A6-0A0A0
ARI SEER: ..
Base Unit Dimensions
Unit Length:.
Unit Width:
Unit Height:.......
Operating Weight
Base Unit Weight
Medium Static Option: . . .
Accessories
Vertical EconoMi$er IV with solid-state controller:
14 -inch Tall Roof Curb:. ..... .
Total Operating Weight:
Unit
Unit Voltage -Phase -Hertz:
Air Discharge.
Fan Drive Type:.......
Actual Airflow:.. . ..
Site Altitude:
Cooling Performance
Condenser Entering Air DB:..
Evaporator Entering Air DB:.
Evaporator Entering Air WB:.....
Entering Air Enthalpy: ..... .
Evaporator Leaving Air DB:...
Evaporator Leaving Air WB:.....
Evaporator Leaving Air Enthalpy:
Gross Cooling Capacity:.........
Gross Sensible Capacity:.... . ..
Compressor Power Input:..
Coil Bypass Factor :
Heating Performance
Heating Airflow:
Entering Air Temp:....
Leaving Air Temp:....
Gas Input Capacity:....
Gas Heating Capacity:
Temperature Rise:...
Supply Fan
External Static Pressure:
Options / Accessories Static Pressure
Economizer:..
Total External Static:
Fan RPM: ...... ................... ... ....
Fan Power:.........
NOTE:. ....... ..
Electrical Data (Before July 30, 2012)
Minimum Voltage:.
Maximum Voltage: ........ .
Compressor RLA:.
Compressor LRA
Outdoor Fan Motor Qty:. ........
13.00
74.4 in
44.0 in
33.4 in
483 Ib
10 Ib
50 Ib
115 Ib
658 Ib
460-3-60
Vertical
Belt
1200 CFM
0 ft
95.0 F
80.0 F
67.0 F
31.44 BTU/lb
59.7 F
57.7 F
24.84 BTU/Ib
35.65 MBH
26.25 MBH
2.48 kW
0.186
1200 CFM
70.0 F
115.5 F
72.0 MBH
59.00 MBH
45.5 F
1.00 in wg
0.04 in wg
1.04 in wg
1041
0.70 BHP
Selected IFM RPM Range: 770 - 1175
414
506
5.8
38
1
Packaged Rooftop Builder 1.34 Page 17 of 20
Project:-Untitledl7
Prepared By:
Performance Summary For 3 Ton
02/13/2013
12:52PM
Outdoor Fan FLA (ea):........__._
Indoor Fan Motor Type:........_. _......... .
Indoor Fan Motor FLA.
Combustion Fan Motor FLA (ea):
Power Supply MCA:._
Power Supply MOCP (Fuse or HACR):
Min. Unit Disconnect FLA:_ ..... . .
Min. Unit Disconnect LRA:. _.. _ .... .
Electrical Convenience Outlet:..... ... .
Electrical Data (July 30, 2012 and Beyond)
Indoor Fan Motor FLA:.
Power Supply MCA:....
Power Supply MOCP:. ... .
Disconnect Size FLA:..
Disconnect Size LRA:
July 30th and beyond units can be identified by serial number 3112XX10CXX)00( and higher
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz 86.4 87.2 90.6
125 Hz 79.7 77.1 80.9
250 Hz 69.9 62.7 80.2
500 Hz 66.0 61.5 76.0
1000 Hz 62.5 60.7 74.6
2000 Hz 57.3 54.5 71.3
4000 Hz 58.7 49.7 68.5
8000 Hz 53.4 42.0 63.9
A -Weighted 70.1
Advanced Acoustics
67.1 80.0
Advanced Accoustics Parameters
1. Unit height above ground- 30.0 ft
2. Horizontal distance from unit to receiver:.. 50.0 ft
3. Receiver height above ground:......... 5.7 ft
4. Height of obstruction- 0.0 ft
5. Horizontal distance from obstruction to receiver ......0.0 ft
6. Horizontal distance from unit to obstruction: 0.0 ft
Detailed Acoustics Information
0.8
MED
2.1
0.24
10.2
15
10
46
None
2.6
11
15
11
49
Octave Band Center Frequency, Hz
63
125
250
500
1k
2k
4k
8k
Overall
Sound Power Levels at Unit's Acoustic Center (Lw), dB
90.6
80.9
80.2
76.0
74.6
71.3
68.5
63.9
91.7 Lw
A -Weighted Sound Power Levels at Unit's Acoustic Center (LwA), dBA
64.4
64.8
71.6
72.8
74.6
72.5
69.5
62.8
79.9 LwA
Sound Pressure Levels at Distance Specified above (Lp), dB
58.2
48.5
47.8
43.6
42.2
38.9
36.1
31.5
59.3 Lp
A -Weighted Sound Pressure Levels at Distance Specified above (LpA), dBA
32.0
32.4
39.2
40.4
42.2
40.1
37.1
30.4
47.5 LpA
Packaged Rooftop Builder 1.34
Page 18 of 20
Performance Summary For 3 Ton
Project:—Untitledl7
Prepared By:
02/13/2013
12:52PM
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
FanCurve
Airflow(CFM-thousands)
RPM=1041 BHP=0.70MaxnnumRPM=1175 MaximwnHP=2.40
Note: Pleasecontactapplicationengineeringforselectionsoutsidetheshadediegion.
SC-SystemQxrve RP-RatedPoint
Packaged Rooftop Builder 1.34 Page 19 of 20
•e`•••�i ::f nrif ff.�.
Project:-Untitled17
Prepared By:
Unit Feature Sheet for 3 Ton
02/13/2013
12:52PM
WeatherMaker — 48TC
PACKAGED ROOFTOP GAS HEATING/ELECTRIC COOLING UNITS
3, 4, 5, 6, 7.5, 8.5, 10, 12,5, 15 TON S
Optional Louvered Hail Guard Shown
WEATHERMAKER SERIES
WeatherMaker(48TC) units are one-piece gas heating. electric
cooling units that are pre -wired and charged with Puron
(R-410) refrigerant. They are factorytested in both heating
and cooling modes, and rated in accordance with AHRI
Standards 2101240(04-06 sizes) and 340/360 (07-16 sizes).
WeatherMaker units are designed in accordance with UL
Standard 1995, and listed by the Underwriters' Laboratories.
Approved and certified by:
US
Certified to ISO 9001
STANDARD FEATURES INCLUDE:
• Puron (R-413A)f;FC refrraarent
• ASMRAE83.1 energycomoiiant
• Scra' wmp'sasors :win interns: lint brisk end ave•as•d prote:ton
• Sang''a-semi•aecooling C9oicitycontra fon04.12r?VD des
• r D3t•aecDDhngc9D9cty'Ca 1 en9S•16model
• SEER'S uo to 13.0, EER's up to 11.1 and IEERs up to 11.5
• Acutrorr"refr"tgerent ieteringsystem
• ExcIus.•ve noncorosio't conpostecondensate pen In Dotards nee'wIth
ASI -RAE Standard 62, voping deign. sae or vanterdrsin
• Standard coo+.ng op eation up to 115'F (45'4:and down to 43'F ,4'G;.
• down to 25' F ,-4' voth winter sten krt.
• Pre-osInled *Mena rpinta and pnrae• costed interior oaneis tested to
533 bows salt spray prrtetion
• FuIiyinsu:atedcsD,1.1
• ExclusiveIG: soid-st9tecontra faron•bperidtan Dsticswith LED
errprcodedes.anstionbunerrntro'.logo and ene•gysevn9 indoo•
fen motor deify
• Low ItiOx mode's that mut Cp>fami4 A:• ausi:ty M9n•genent
• Induoeddraftgasheat corrrbustandesan
• Redund•ntget vai.eswan up to two stages of heitng
• Lp'a•p:essure end nign pressure swan protected.
MAINTENANCE FEATURES:
• ACcesstenet wrtn easygrip bandies
• Innovative easy starting. no•strp screws an un It sixes; panes
• Tw•o-ihchdIsoossa!ereturn sir fiat rsand Tooi-nessMar amssdoor
• eetdrveevsporetor--fen motor and pulpy combinations
• Newterninsl board fscilit•tina simple safetycircuit troubleshooting mind
s!mp;f;ed control box arengernent
• ExousveIGC soid•statecontra! for on -board dsanostiswith LEC
errarcode designetan. burnercontrp'. iogki. end energy saving indoor
fan motordel•y.
IN STALLATION FEATURES:
• Th rd the-botWmpo»ere ntri cepa bii1y
• Single point gas andeectri:connections
• Ful perimeter bast rail w•.th but -in rygrig adopters and fork sots
• Fed convertib*fram-vetics::toho!tontaisirfrow•fprsal bmounting.
(15ize mode isrGSluire Mid installed au pply'duct C3o'e j.
STANDARD WARRANTY:
• 10 -yes• nest etch enger- 15-ye•rits Inless gee' option
• 5-yesrc rnpressar
• 1 -year parts
• 3 -year parts on tiovtan CondensercoiS-where avaisbe
• Manyoptiono' Jog roles e=averebe
OPTIONS INCLUDE BUT ARE NOT LIMITED TO:
• PremerLmk^' and RTU' Open Muni Protocol CCC Controls
• Supply and Return Air Smoke Detectors. high stat: motors
• Lou'ventdcondensergaguards
• Eoonom¢er,disconnect and conventenoeoutetoptions
• Stainiess Steel he at exchange rowan
• Corrosion resistant co; costing.
• M4m;di-M2efadaptve de humi9dcafionsystem availsb4onell
mo•deswith RTPF condsnserco- Motor Master Icontrarier included
• fringed areas pant Is
Fara compete irrt of Dp0015 9r d secessona4 NOV to the Product Cats
:•atsiog forth s unit
Packaged Rooftop Builder 1.34 Page 20 of 20
. Table 2 - AHRI COOLING RATING TABLE
UNIT
COOLING
STAGES
NOM.
CAPACITY
(TONS)
NET
COOLING
CAPACITY
(MBH)
TOTAL
POWER (KW)
SEER
EER
IEER
A04
1
3
34.6
3.1
13.0
11.00
N/A
A05
1
4
45.0
4.0
13.0
11.00
N/A
A06
1
5
59.0
5.5
13.0
10.75
N/A
A07
1
6
70.0
6.4
N/A
11.00
11.2
A08
1
7.5
88.0
8.0
N/A
11.00
11.2
A09
1
8.5
97.0
8.8
N/A
11.00
11.2
Al2
1
10
117.0
10.6
N/A
11.00
11.2
UNIT
COOLING
STAGES
NOM.
CAPACITY
(TONS)
NET
COOLING
CAPACITY
(MBH)
TOTAL
POWER
(
EER
IEER WITH
SINGLE SPEED
INDOOR FAN
MOTOR
IEER WITH
2 SPEED
INDOOR FAN
MOTOR
D08
2
7.5
83.0
7.5
11.00
11.7
12.8
D09
2
8.5
97.0
9.0
11.00
11.2
12.8
D12
2
10
114.0
10.3
11.10
11.8
12.8
D14
2
12.5
140.0
12.9
10.80
11.0
11.8
D16
2
15
174.0
16.1
10.80
11.7
12.4
LEGEND
AHRI - Air Conditioning, Heating and Refrigeration
Institute Test Standard
ASHRAE - American Society of Heating, Refrigerating
and Air Conditioning, Inc.
EER - Energy Efficiency Ratio
IEER - Integrated Energy Efficiency Ratio
N/A - Not Applicable
SEER - Seasonal Energy Efficiency Ratio
Us
1w1
COMP LIANT
.;a " i CERTIFIED.
Use of the AHRI Certified
TM Mark indicates a
manufacturers
participation in the
program For verification
of certification for individual
products. go to
www.artridirectmµorp.
NOTES:
1. Rated in accordance with AHRI Standard 210/240 or
340/360, as appropriate.
2. Ratings are based on:
Cooling Standard: 80°F (27°C) db, 67°F (19°C) wb indoor
air temp and 95°F (35°C) db outdoor air temp.
IEER Standard: A measure that expresses cooling part -
load EER efficiency for commercial unitary air conditioning
and heat pump equipment on the basis of weighted opera-
tion at various Toad capacities.
3. All 48TC units comply with ASHRAE 90.1 Energy Standard
for minimum SEER and EER requirements.
4. 48TC units comply with US Energy Policy Act (2005). To eval-
uate code compliance requirements, refer to state and local
codes.
9
Load Express: Load Calculation Software
Version 2.2
Title Page
Load Express: Load Calculation Software
By: Seattle Mechanical
General Job
Job Description:
Building Owner:
Program User:
Comments:
Fuse Networks
Seattle Mechanical
Program was Run: 2/27/20133t 1:15:51 PM
Dataset Name: C:\CDS\LOADEXP\DATA\FUSE.LE
No
rite CODy
Alternative 1 AIt1
Geographical Data
Location:
Weather File:
Latitude:
Elevation:
Seattle, Washington
Seattle, Washington
47 deg
386 ft
Design Data
Summer Dsn Dry Bult
Summer Dsn Wet Bul
Winter Design Dry Bu
Density -Sp Heat Prod
Design Simulation per
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAR 13 2013
City of Tukwila
BUILDING DIVISION
80.0 deg F
64.0 deg F
26.0 deg F
1.0988 Btu-min/(hr-ft3-F)
Apr To Nov
Building Peak Data
Month/Hour: Jul / 14
Cooling Capacity: 140.8 Mbh
Cooling Sensible: 108.6 Mbh
Sensible Heat Ratio (SH 0.848
Heating Capacity -119.1 Mbh
RECEIVED
CITY OF TUKWILA
MAR 0 5 2013
PERMIT CENTER
MIU5
Loaa txpress: Loaa Lamination Jonware version 2.2
Zone/Air Handler Descriptions
Zone/Air Handler Descriptions
Alternative - 1 Alt1
Air Handler Type Description
1 CONSTANT AHU2
2 CONSTANT AHU3
3 CONSTANT AHU1
Zone Type Description
1 Commercial Retail Zone1
2 Commercial Retail Zone2
3 Commercial Retail Zone3
Load Express: Load Calculation Software
Alternative 1 Alt1
1-2 Story Office
Version 2.2
Zone Input Data
General Job Data
Weather Location: Seattle, Washington
Weather Region: Northwest
Clg Simulation Start Month: Apr
Clg Simulation End Month: Nov
Zone Data
Alternative Number: 1
Zone Number: 1
Floor Width: 28 ft
Floor Length: 74 ft
Ceiling Height: 10 ft
Fir -to -Fir Height: 16 ft
No. of Dup Zones: 1
Ceiling U -Factor: 0.04 Btu/(hr-F-ft2)
Floor Calculation Type: Slab -On -Grade
Floor Loss Coefficient: 0.73 Btu/(hr-F-ft)
Floor Perimeter Length130.00 ft
W H Type
ft ft
Building Opening Time: 8 am
Building Closing Time: 6 pm
Building Direction: 0
Clg Sensible SF: 10.00
Cooling Dry Bulb:
Relative Humidity:
Heating Dry Bulb:
People Density:
People Activity:
People Sensible Load:
People Latent Load:
Misc. Equip. Type:
Misc. Equip. Sensible Load
Misc. Equip. Latent Load:
Misc. Equip. Sensible to R.
Lighting Intensity:
Lighting Type: .ecessed fluorescent, not vented
74 deg F
50 %
70 deg F
100 ft2/pers
General Office Space
210 Btuh/pers
255 Btuh/pers
Microcomputers
350.00 Watt/pers
0.00 W att/ft2
0 Btuh
0.91 W att/ft2
Clg Latent SF: 10
Htg Sensible SF: 10
People Diversity: 100 %
Bldg Simulation Type: Cooling and Heating
Ballast Factor: 1.00
% Percent Light to RA: 50 %
Vent Type: General Office Space
Vent Cool Design: 20.00 cfm/pers
Vent Heat Design: 20.00 cfm/pers
Supply Cool Design: 0 cfm
Supply Heat Design: 0 cfm
Infiltration Type: Pressurized, Average Construction
Infilt. Cooling Desigi 0.30 ach/hr
Infilt. Heating Desigi 0.30 ach/hr
Room Exhaust: 0.00 cfm
U -Factor Color Percent (%) Direction Susp Ceil Tilt Cool Adj Heat Adj Dimension °A, Glass Shading Coeff Shading
Spc Temp Spc Temp
degF deg F
WALL
ROOF
PART
PART
1 30 x 9 8" L.W. Concrete Blk, 6" Ins
1 28 x 74 4" Wood deck, 6" Ins, SusClg
1 28 x 9 Frame, 0.75" gypsum board
2 74 x 7 Frame, 0.75" gypsum board
0.04 Light West
0.04 Light 0 RA North Yes
0.39
0.39
0 0
0 0
0 80
0 80
0
0
45
45
0.00
0.00
0.00
0.00
Load Express: Load Calculation Software
Zone Data
Alternative Number: 1
Zone Number:
2
Floor Width: 24 ft
Floor Length: 56 ft
Ceiling Height: 9 ft
Fir -to -Fir Height: 16 ft
No. of Dup Zones: 1
Ceiling U -Factor: 0.04 Btu/(hr-F-ft2)
Floor Calculation Type: None
W H Type
Cooling Dry Bulb:
Relative Humidity:
Heating Dry Bulb:
People Density:
People Activity:
People Sensible Load:
People Latent Load:
Misc. Equip. Type:
Misc. Equip. Sensible Load
Misc. Equip. Latent Load:
Misc. Equip. Sensible to RI
Lighting Intensity:
Lighting Type: .ecessed
72 deg F
50 %
70 deg F
100 ft2/pers
General Office Space
210 Btuh/pers
255 Btuh/pers
Microcomputers
350.00
0.00
0
0.91
Watt/pers
W att/ft2
Btuh
Watt/ft2
fluorescent, not vented
Version 2.2
Zone Input Data
Ballast Factor: 1.00
% Percent Light to RA: 50 oh.
Vent Type: General Office Space
Vent Cool Design: 20.00 cfm/pers
Vent Heat Design: 20.00 cfm/pers
Supply Cool Design: 0 cfm
Supply Heat Design: 0 cfm
Infiltration Type: Pressurized, Average Construction
Infilt. Cooling Desigi 0.30 ach/hr
Infilt. Heating Desigi 0.30 ach/hr
Room Exhaust: 160.00 cfm
U -Factor Color Percent (%) Direction Susp Cell Tilt Cool Adj Heat Adj Dimension % Glass Shading Coeff
Spc Temp Spc Temp
degF deg F
Shading
ROOF 1 24 x 56 4" Wood deck, 6" Ins, SusClg
PART 1 56 x 9 Frame, 0.75" gypsum board
0.04 Light 0 RA North
0.39
Yes 0 0
0 0.00
0 72 70 0.00
Load Express: Load Calculation Software
Zone Data
Alternative Number: 1
Zone Number:
3
Floor Width: 18 ft
Floor Length: 90 ft
Ceiling Height: 9 ft
Flr-to-Flr Height: 16 ft
No. of Dup Zones: 1
Ceiling U -Factor: 0.04 Btu/(hr-F-ft2)
Floor Calculation Type: Slab -On -Grade
Floor Loss Coefficient: 0.73 Btu/(hr-F-ft)
Floor Perimeter Length135.00 ft
W H Type
ft ft
Cooling Dry Bulb:
Relative Humidity:
Heating Dry Bulb:
People Density:
People Activity:
People Sensible Load:
People Latent Load:
Misc. Equip. Type:
Misc. Equip. Sensible Load
Misc. Equip. Latent Load:
Misc. Equip. Sensible to RV
Lighting Intensity:
Lighting Type: ecessed fluorescent, not vented
72 deg F
50 %
70 deg F
100 ft2/pers
General Office Space
210 Btuh/pers
255 Btuh/pers
Microcomputers
350.00 Watt/pers
0.00 Watt/ft2
0 Btuh
0.91 W att/ft2
Version 2.2
Zone Input Data
Ballast Factor: 1.00
% Percent Light to RA: 50 %
Vent Type: General Office Space
Vent Cool Design: 20.00 cfm/pers
Vent Heat Design: 20.00 cfm/pers
Supply Cool Design: 0 cfm
Supply Heat Design: 0 cfm
Infiltration Type: Pressurized, Average Construction
Infilt. Cooling Desigi 0.30 ach/hr
Infilt. Heating Desigi 0.30 ach/hr
Room Exhaust: 0.00 cfm
U -Factor Color Percent (%) Direction Susp Ceil Tilt Cool Adj Heat Adj Dimension % Glass Shading Coeff
Spc Temp Spc Temp
degF deg F
Shading
WALL 1
GLASS 1
ROOF 1
PART 1
135 x 9 8" L.W. Concrete Blk, 6" Ins
66 x 7 Double Coated 1/4 in.
18 x 90 4" H.W. Dk., 6" Ins
88 x 9 Frame, 0.75" gypsum board
0.04 Light North
0.50 0 Plenum
0.05 Light 0 RA North Yes
0.39
0 0
0 0
0 0
0 72
0
0 Area
0
70
0.00
0.55 External
0.00
0.00
Air Handler Input
Air Handler Input
Alternative 1
Air Handler 1
Fan Configuration: Draw
Fan & Motor Efficiency: 56.00 %
Cooling Supply Air Temp: 55.00 deg F
Heating Supply Air Temp: 0.00 deg F
Minimum Relative Humidity: 40 %
Supply Fan Static Pressure: 2.00 in H2O
Return Fan Static Pressure: 0.00 in H2O
CONSTANT AHU2
Supply Duct Location:
Supply Duct Insulation:
Supply Duct Temp Rise:
Return Duct Insulation:
Return Duct Temp Rise:
Terminal Type:
Total Cool Airflow:
Total Heat Airflow:
Zone(s) Connected:
Unvented Space
R4 Duct Insulation
0.5 degFTD
R4 Duct Insulation
0.3 degFTD
CONSTANT
0 cfm
0 cfm
1
Air Handler 2
Fan Configuration: Draw
Fan & Motor Efficiency: 56.00 %
Cooling Supply Air Temp: 55.00 deg F
Heating Supply Air Temp: 0.00 deg F
Minimum Relative Humidity: 0 %
Supply Fan Static Pressure: 2.00 in H2O
Return Fan Static Pressure: 0.00 in H2O
CONSTANT AHU3
Supply Duct Location:
Supply Duct Insulation:
Supply Duct Temp Rise:
Return Duct Insulation:
Return Duct Temp Rise:
Terminal Type:
Total Cool Airflow:
Total Heat Airflow:
Zone(s) Connected:
Unvented Space
R4 Duct Insulation
0.5 deg F TD
R4 Duct Insulation
0.3 deg F TD
CONSTANT
0
0
2
cfm
cfm
Air Handler 3
Fan Configuration: Draw
Fan & Motor Efficiency: 56.00 %
Cooling Supply Air Temp: 55.00 deg F
Heating Supply Air Temp: 0.00 deg F
Minimum Relative Humidity: 0 %
Supply Fan Static Pressure: 2.00 in H2O
Return Fan Static Pressure: 0.00 in H2O
CONSTANT AHU1
Supply Duct Location:
Supply Duct Insulation:
Supply Duct Temp Rise:
Return Duct Insulation:
Return Duct Temp Rise:
Terminal Type:
Total Cool Airflow:
Total Heat Airflow:
Zone(s) Connected:
Unvented Space
R4 Duct Insulation
0.5 degFTD
R4 Duct Insulation
0.3 degFTD
CONSTANT
0
0
3
cfm
cfm
Load Express: Load Calculation Software versio2.2
Peak Load Information
Altemative 1
Design Heating:
Airflow (cfm) Space Total Heating Coil
Total Outside % O.A. Sensible Sensible Entering Leaving
Humidification
Air Handler fl/Type Btuh Btuh DB DB Btuh
BLDG BLOCK -53,278.30 -119,078.00 -11,121.5
BLDG PEAK -53,278.30 -119,078.00 -11,121.5
1 CONSTANT 1,729.88 414.40 23.96 -22,335.30 -56,607.90 58.41 81.75 -11,121.5
2 CONSTANT 1,199.37 268.80 22.41 -5,493.24 -19,788.80 59.15 74.17
3 CONSTANT 2,021.06 324.00 16.03 -25,449.80 -42,681.00 62.24 81.46
Design Cooling:
Airflow (cfm)
Cooling Cooling Coil
Total Outside %O.A Total Sensible S.H.R. Entering Leaving ft2/ton cfm/ton cfrn/ft2 Total
Air Handler ft/Type Btuh Btuh DB WB DB WB tons
BLDG BLOCK 140,793.00 119,461.00 0.85 429.23 11.7
BLDG PEAK 140,793.00 119,461.00 0.85 429.23 11.7
1 CONSTANT 1,729.88 414.40 23.96 52,641.80 44,064.10 0.84 76.84 62.11 53.20 51.42 472.33 394.3 0.8 4.4
2 CONSTANT 1,199.37 268.80 22.41 34,329.90 28,723.60 0.84 75.40 61.54 53.20 51.42 469.80 419.2 0.9 2.9
3 CONSTANT 2,021.06 324.00 16.03 53,821.30 46,672.90 0.87 74.41 60.84 53.20 51.42 361.20 450.6 1.2 4.5
Building Peak Load Components
Cooling (Btuh) Heating (Btuh)
Mo/Hr: Solar Cond Internal OA+Inf Misc Total Cond OA+Inf Misc Total
Bldg 7/14 7,826.8 3,617.1 92,704.2 15,529.6 8,315.9 127,994.0 -36,977.3 -60,153.8 -11,121.9 -108,253.0
Air Hand 1 7/14 1,860.4 37,872.5 5,587.9 2,535.4 47,856.1 -15,295.9 -25,044.3 -11,121.5 -51,461.7
Zone 1 7/14 1,860.4 37,872.5 5,587.9 2,535.4 47,856.1 -15,295.9 -25,044.3 -11,121.5 -51,461.7
Air Hand 2 7/14 138.8 24,597.2 4,346.9 2,126.1 31,209.0 -2,069.8 -15,920.1 0.1 -17,989.8
Zone 2 7/14 138.8 24,597.2 4,346.9 2,126.1 31,209.0 -2,069.8 -15,920.1 0.1 -17,989.8
Air Hand 3 7/14 7,826.8 1,617.9 30,234.5 5,594.8 3,654.5 48,928.5 -19,611.6 -19,189.4 0.1 -38,800.9
Zone 3 7/14 7,826.8 1,617.9 30,234.5 5,594.8 3,654.5 48,928.5 -19,611.6 -19,189.4 0.1 -38,800.9
Loa° txpress: Loa° t;aicuIation sonware
Psychrometric State Points - Alternative 1 AIt1
Zone 1 Dry Bulb Wet Bulb Temp Diff.
Zone1 ( deg F ) ( deg F ) ( deg F )
Space 74.0 60.7
Zone
Return Air Heat Pickup
Retum Fan
Return Air 75.9 61.4
Outdoor Air 79.4 64.3
Retum/Outdoor Air Mix 76.8 62.1
Blow Through Fan
Entering Coil 76.8 62.1
Leaving Coil 53.2 51.4
Draw Through Fan
Supply Duct Heat Gain
Supply Air 55.0 52.2
Percent Outside Air 26.35 %
Space Sensible Heat Ratio (SHR) 0.869
Coil Airflow 1,573 cfm
1.9
0.0
0.0
1.3
0.5
Zone 2 Dry Bulb Wet Bulb Temp Diff.
Zone2 ( deg F ) ( deg F ) ( deg F )
Space 72.0 59.9
Zone
Retum Air Heat Pickup
Retum Fan
Return Air 74.1 60.7
Outdoor Air 79.4 64.3
Retum/Outdoor Air Mix 75.4 61.5
Blow Through Fan
Entering Coil 75.4 61.5
Leaving Coil 53.2 51.4
Draw Through Fan
Supply Duct Heat Gain
Supply Air 55.0 52.2
Percent Outside Air
Space Sensible Heat Ratio (SHR)
Coil Airflow
24.65 %
0.864
1,090 cfm
2.1
0.0
0.0
1.3
0.5
version z.z
Psychrometrics
Loaa txpress: Loaa L,aicuiauon aonware
Psychrometric State Points - Alternative 1 AIt1
Zone 3 Dry Bulb Wet Bulb Temp Diff.
Zone3 ( deg F ) ( deg F ) ( deg F )
Space 72.0 59.6
Zone
Return Air Heat Pickup 1.3
Retum Fan 0.0
Return Air 73.3 60.1
Outdoor Air 79.4 64.3
Return/Outdoor Air Mix 74.4 60.8
Blow Through Fan 0.0
Entering Coil 74.4 60.8
Leaving Coil 53.2 51.4
Draw Through Fan 1.3
Supply Duct Heat Gain 0.5
Supply Air 55.0 52.2
Percent Outside Air
Space Sensible Heat Ratio (SHR)
Coil Airflow
17.63 %
0.897
1,837 cfm
V CI L.L
Psychrometrics
Load Express: Load Calculation Software Version 2.2
Sensible Load Profile .
Sensible Load Profile (Mbh)- Alternative 1 AM
Hour
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Air Hand 1 2 1 0 0 0 0 0 28 30 33 35 37 39 40 41 41 40 39 11 8 6 5 3 3
Air Hand 2 1 1 0 0 0 0 0 18 20 21 23 24 25 26 27 27 26 26 7 5 4 3 2 2
Air Hand 3 2 1 0 0 0 0 2 25 30 33 36 39 41 42 43 43 42 40 16 10 8 6 4 3
Bldg 5 2 0 0 -1 0 1 71 80 87 94 101 105 109 110 110 108 105 34 24 18 13 10 7
Zone 1 2 1 0 0 0 0 0 28 30 33 35 37 39 40 41 41 40 39 11 8 6 5 3 3
Zone 2 1 1 0 0 0 0 0 18 20 21 23 24 25' 26 27 27 26 26 7 5 4 3 2 2
Zone 3 2 1 0 0 0 0 2 25 30 33 36 39 41 42 43 43 42 40 16 10 8 6 4 3
Loaa txpress Load uaicuiation sonware
version z.z
Peak Load Summary
Peak Load Summary - Alternative 1
Air Hand 1 AHU2
Areas ( ft2 )
Floor: 2,072.0
SlabOnG/ExFIr:
Roof:
Skylight:
Wall:
Wall Glass:
Partition:
130.0
2,072.0
0.0
270.0
0.0
770.0
AIt1
Space Sens Load
Spc Sens Ld W/Sfty Fctr
Cool Airflow
Cool Airflw W/Sfty Fctor
Cooling Check
Cool Check W/Sfty Fctr
Heat Airflow
Heat Airflw W/Sfty Fctr
32,832.5 Btuh
36,115.8 Btuh
1,573 cfm
1,730 cfm
0.76 cfm/ft2
0.83 cfm/ft2
1,573 cfm
1,730 cfm
Heating Coil Peak
Outside Air: OADB: 26
Cooling Coil Peak
Peaked at Time: Mo/Hr: 7 / 14
Outside Air: OADB: 79
WB: 64
RELHUM: 44.2%
Cooling Coil Peak
Heating Coil Peak
Total Load
Sens Load
Percnt of Tot
Peak Tot Sens
Percnt of Tot
( Btuh)
( Btuh )
(%)
( Btuh)
(%)
ENVELOPE LOADS
Solar
Skylight Solar
0.00
0.00
0.00
Glass Solar
0.00
0.00
0.00
Sub Total
0.00
0.00
0.00
0.00
0.00
Conducted
Skylight
0.00
0.00
0.00
Roof
71.75
71.75
-3,190.88
Glass
0.00
0.00
0.00
Wall
5.32
5.32
-498.96
Partition
1,783.32
1,783.32
-7,430.50
SlabOnG/ExFlr
0.00
0.00
-4,175.60
Sub Total
1,860.39
1,860.39
3.89
-15,295.90
29.72
INTERNAL LOADS
Lights
5,708.19
5,708.19
0.00
People
9,302.64
4,019.04
0.00
Misc
22,861.70
22,861.70
0.00
Sub Total
37,872.50
32,588.90
79.14
0.00
0.00
MISC LOADS
Outside Air
4,470.29
2,458.90
-20,035.50
Humidification
0.00
0.00
-11,121.50
Infiltration
1,117.57
614.73
-5,008.87
Sup. Fan Heat
2,246.60
2,246.60
0.00
Ret. Fan Heat
0.00
0.00
0.00
Duct Heat Pkup
1,382.42
1,382.42
0.00
Exhaust Heat
-1,093.62
-1,093.62
0.00
Sub Total
8,123.27
5,609.02
16.97
-36,165.80
70.28
OV/UNDR Sizing
0.00
0.00
0.00
Grand Total
47,856.10
40,058.30
-51,461.70
W/Safety Factor
52,641.80
44,064.10
-56,607.90
Loaa xpress: Loaa c;aicuiation 5onware
Version 2.2
Peak Load Summary
Peak Load Summary - Alternative 1
Air Hand 2 AHU3
Areas ( ft2 )
Floor:
SlabOnG/ExFIr:
Roof:
Skylight:
Wall:
Wall Glass:
Partition:
1,344.0
0.0
1,344.0
0.0
0.0
0.0
504.0
Alt1
Space Sens Load
Spc Sens Ld W/Sfty Fctr
Cool Airflow
Cool Airflw W/Sfty Fctor
Cooling Check
Cool Check W/Sfty Fctr
Heat Airflow
Heat Airflw W/Sfty Fctr
20,367.4 Btuh
22,404.1 Btuh
1,090 cfm
1,199 cfm
0.81 cfm/ft2
0.89 cfm/ft2
1,090 cfm
1,199 cfm
Heating Coil Peak
Outside Air: OADB: 26
Cooling Coil Peak
Peaked at Time: Mo/Hr: 7 / 14
Outside Air: OADB: 79
WB: 64
RELHUM: 44.2%
Cooling Coil Peak
Heating Coil Peak
Total Load
( Btuh)
Sens Load Percnt of Tot
( Btuh ) (%)
Peak Tot Sens
( Btuh)
Percnt of Tot
(%)
ENVELOPE LOADS
Solar
Skylight Solar
0.00
0.00
0.00
Glass Solar
0.00
0.00
0.00
Sub Total
0.00
0.00
0.00
0.00
0.00
Conducted
Skylight
0.00
0.00
0.00
Roof
138.80
138.80
-2,069.76
Glass
0.00
0.00
0.00
Wall
0.00
0.00
0.00
Partition
0.00
0.00
0.00
SlabOnG/ExFIr
0.00
0.00
0.00
Sub Total
138.80
138.80
0.44
-2,069.76
11.51
INTERNAL LOADS
Lights
3,733.88
3,733.88
0.00
People
6,034.15
2,606.95
0.00
Misc
14,829.20
14,829.20
0.00
Sub Total
24,597.20
21,170.00
78.81
0.00
0.00
MISC LOADS
Outside Air
3,548.52
2,185.69
-12,996.00
Humidification
0.00
0.00
0.00
Infiltration
798.42
491.78
-2,924.09
Sup. Fan Heat
1,557.62
1,557.62
0.00
Ret. Fan Heat
0.00
0.00
0.00
Duct Heat Pkup
958.46
958.46
0.00
Exhaust Heat
-390.03
-390.03
0.00
Sub Total
6,472.99
4,803.52
20.74
-15,920.10
88.50
OV/UNDR Sizing
0.00
0.00
0.00
Grand Total
31,209.00
26,112.30
-17,989.80
W/Safety Factor
34,329.90
28,723.60
-19,788.80
LULU C74JI ebb . LVdU L,dIUUIdLIVII JUILVVcilr.
vciawn c.c
Peak Load Summary
Peak Load Summary - Alternative 1 AIt1
Air Hand 3 AHU1
Areas ( ft2 ) Space Sens Load 34,321.3 Btuh Heating Coil Peak
Floor: 1,620.0 Spc Sens Ld W/Sfty Fctr 37,753.4 Btuh Outside Air: OADB: 26
SlabOnG/ExFIr: 135.0 Cool Airflow 1,837 cfm
Roof: 1,620.0 Cool Airflw W/Sfty Fctor 2,021 cfm Cooling Coil Peak
Skylight: 0.0 Cooling Check 1.13 cfm/ft2 Peaked at Time: Mo/Hr: 7 / 14
Wall: 753.0 Cool Check W/Sfty Fctr 1.25 cfm/ft2 Outside Air: OADB: 79
Wall Glass: 462.0 Heat Airflow 1,837 cfm WB: 64
Partition: 792.0 Heat Airflw W/Sfty Fctr 2,021 cfm RELHUM: 44.2%
Cooling Coil Peak
Heating Coil Peak
Total Load
Sens Load
Percnt of Tot
Peak Tot Sens
Percnt of Tot
( Btuh)
( Btuh )
(%)
( Btuh)
(%)
ENVELOPE LOADS
Solar
Skylight Solar
0.00
0.00
0.00
Glass Solar
7,826.76
7,826.76
0.00
Sub Total
7,826.76
7,826.76
16.00
0.00
0.00
Conducted
Skylight
0.00
0.00
0.00
Roof
40.42
40.42
-3,278.88
Glass
1,638.48
1,638.48
-10,604.90
Wall
-60.99
-60.99
-1,391.54
Partition
0.00
0.00
0.00
SlabOnG/ExFIr
0.00
0.00
-4,336.20
Sub Total
1,617.90
1,617.90
3.31
-19,611.60
50.54
INTERNAL LOADS
Lights
4,343.71
4,343.71
0.00
People
7,384.40
3,253.40
0.00
Misc
18,506.40
18,506.40
0.00
Sub Total
30,234.50
26,103.50
61.79
0.00
0.00
MISC LOADS
Outside Air
4,567.22
2,634.53
-15,664.80
Humidification
0.00
0.00
0.00
Infiltration
1,027.62
592.77
-3,524.58
Sup. Fan Heat
2,624.76
2,624.76
0.00
Ret. Fan Heat
0.00
0.00
0.00
Duct Heat Pkup
1,615.12
1,615.12
0.00
Exhaust Heat
-585.43
-585.43
0.00
Sub Total
9,249.29
6,881.75
18.90
-19,189.40
49.46
OV/UNDR Sizing
0.00
0.00
0.00
Grand Total
48,928.50
42,429.90
-38,800.90
W/Safety Factor
53,821.30
46,672.90
-42,681.00
Peak Load Summary
Peak Load Summary - Alternative 1 AIt1
Bldg 1
Areas ( ft2 )
Floor: 5,036.0
SlabOnG/ExFlr: 265.0
Roof: 5,036.0
Skylight: 0.0
Wall: 1,023.0
Wall Glass: 462.0
Partition: 2,066.0
Heating Coil Peak
Outside Air: OADB: 26
Cooling Coil Peak
Peaked at Time: Mo/Hr: 7 / 14
Outside Air: OADB: 79
WB: 64
RELHUM: 44.2%
Cooling Coil Peak
Heating Coil Peak
Total Load
Sens Load
Percnt of Tot
Peak Tot Sens
Percnt of Tot
( Btuh)
( Btuh )
(%)
( Btuh)
(%)
ENVELOPE LOADS
Solar
Skylight Solar
0.00
0.00
0.00
Glass Solar
7,826.76
7,826.76
0.00
Sub Total
7,826.76
7,826.76
6.11
0.00
0.00
Conducted
Skylight
0.00
0.00
0.00
Roof
250.97
250.97
-8,539.52
Glass
1,638.48
1,638.48
-10,604.90
Wall
-55.67
-55.67
-1,890.50
Partition
1,783.32
1,783.32
-7,430.50
SlabOnG/ExFIr
0.00
0.00
-8,511.80
Sub Total
3,617.09
3,617.09
2.83
-36,977.30
34.16
INTERNAL LOADS
Lights
13,785.80
13,785.80
0.00
People
22,721.20
9,879.39
0.00
Misc
56,197.30
56,197.30
0.00
Sub Total
92,704.20
79,862.40
72.43
0.00
0.00
MISC LOADS
Outside Air
12,586.00
7,279.12
-48,696.20
Humidification
0.00
0.00
-11,121.50
Infiltration
2,943.61
1,699.27
-11,457.50
Sup. Fan Heat
6,428.98
6,428.98
0.00
Ret. Fan Heat
0.00
0.00
0.00
Duct Heat Pkup
3,956.00
3,956.00
0.00
Exhaust Heat
-2,069.08
-2,069.08
0.00
Sub Total
23,845.50
17,294.30
18.63
-71,275.20
65.84
OV/UNDR Sizing
0.00
0.00
0.00
Grand Total
127,994.00
108,601.00
-108,253.00
W/Safety Factor
140,793.00
119,461.00
-119,078.00
Peak Load Summary
Peak Load Summary - Alternative 1
Zone 1 Zone1
Areas ( ft2 )
Floor: 2,072.0
SlabOnG/ExFIr:
Roof:
Skylight:
Wall:
Wall Glass:
Partition:
130.0
2,072.0
0.0
270.0
0.0
770.0
AIt1
Space Sens Load
Spc Sens Ld W/Sfty Fctr
Cool Airflow
Cool Airflw W/Sfty Fctor
Cooling Check
Cool Check W/Sfty Fctr
Heat Airflow
Heat Airflw W/Sfty Fctr
32,832.5
36,115.8
1,573
1,730
0.76
0.83
1,573
1,730
Btuh
Btuh
cfm
cfm
cfm/ft2
cfm/ft2
cfm
cfm
Heating Coil Peak
Outside Air: OADB: 26
Cooling Coil Peak
Peaked at Time: Mo/Hr:
Outside Air: OADB:
WB:
RELHUM:
7 / 14
79
64
44.2%
Cooling Coil Peak
Heating Coil Peak
Total Load
Sens Load
Percnt of Tot
Peak Tot Sens
Percnt of Tot
( Btuh)
( Btuh )
(%)
( Btuh)
(%)
ENVELOPE LOADS
Solar
Skylight Solar
0.00
0.00
0.00
Glass Solar
0.00
0.00
0.00
Sub Total
0.00
0.00
0.00
0.00
0.00
Conducted
Skylight
0.00
0.00
0.00
Roof
71.75
71.75
-3,190.88
Glass
0.00
0.00
0.00
Wall
5.32
5.32
-498.96
Partition
1,783.32
1,783.32
-7,430.50
SlabOnG/ExFlr
0.00
0.00
-4,175.60
Sub Total
1,860.39
1,860.39
3.89
-15,295.90
29.72
INTERNAL LOADS
Lights
5,708.19
5,708.19
0.00
People
9,302.64
4,019.04
0.00
Misc
22,861.70
22,861.70
0.00
Sub Total
37,872.50
32,588.90
79.14
0.00
0.00
MISC LOADS
Outside Air
4,470.29
2,458.90
-20,035.50
Humidification
0.00
0.00
-11,121.50
Infiltration
1,117.57
614.73
-5,008.87
Sup. Fan Heat
2,246.60
2,246.60
0.00
Ret. Fan Heat
0.00
0.00
0.00
Duct Heat Pkup
1,382.42
1,382.42
0.00
Exhaust Heat
-1,093.62
-1,093.62
0.00
Sub Total
8,123.27
5,609.02
16.97
-36,165.80
70.28
OV/UNDR Sizing
0.00
0.00
0.00
Grand Total
47,856.10
40,058.30
-51,461.70
W/Safety Factor
52,641.80
44,064.10
-56,607.90
7 / 14
79
64
44.2%
Peak Load Summary
Peak Load Summary - Alternative 1 AIt1
Zone 2 Zone2
Areas ( ft2 )
Floor:
SlabOnG/ExFIr:
Roof:
Skylight:
Wall:
Wall Glass:
Partition:
1,344.0
0.0
1,344.0
0.0
0.0
0.0
504.0
Space Sens Load
Spc Sens Ld W/Sfty Fctr
Cool Airflow
Cool Airflw W/Sfty Fctor
Cooling Check
Cool Check W/Sfty Fctr
Heat Airflow
Heat Airflw W/Sfty Fctr
20,367.4
22,404.1
1,090
1,199
0.81
0.89
1,090
1,199
Btuh
Btuh
cfm
cfm
cfm/ft2
cfm/ft2
cfm
cfm
Heating Coil Peak
Outside Air: OADB: 26
Cooling Coil Peak
Peaked at Time: Mo/Hr: 7 / 14
Outside Air: OADB: 79
WB: 64
RELHUM: 44.2%
Cooling Coil Peak
Heating Coil Peak
Total Load
Sens Load
Percnt of Tot
Peak Tot Sens
Percnt of Tot
( Btuh)
( Btuh )
(%)
( Btuh)
(%)
ENVELOPE LOADS
Solar
Skylight Solar
0.00
0.00
0.00
Glass Solar
0.00
0.00
0.00
Sub Total
0.00
0.00
0.00
0.00
0.00
Conducted
Skylight
0.00
0.00
0.00
Roof
138.80
138.80
-2,069.76
Glass
0.00
0.00
0.00
Wall
0.00
0.00
0.00
Partition
0.00
0.00
0.00
SlabOnG/ExFIr
0.00
0.00
0.00
Sub Total
138.80
138.80
0.44
-2,069.76
11.51
INTERNAL LOADS
Lights
3,733.88
3,733.88
0.00
People
6,034.15
2,606.95
0.00
Misc
14,829.20
14,829.20
0.00
Sub Total
24,597.20
21,170.00
78.81
0.00
0.00
MISC LOADS
Outside Air
3,548.52
2,185.69
-12,996.00
Humidification
0.00
0.00
0.00
Infiltration
798.42
491.78
-2,924.09
Sup. Fan Heat
1,557.62
1,557.62
0.00
Ret. Fan Heat
0.00
0.00
0.00
Duct Heat Pkup
958.46
958.46
0.00
Exhaust Heat
-390.03
-390.03
0.00
Sub Total
6,472.99
4,803.52
20.74
-15,920.10
88.50
OV/UNDR Sizing
0.00
0.00
0.00
Grand Total
31,209.00
26,112.30
-17,989.80
W/Safety Factor
34,329.90
28,723.60
-19,788.80
Peak Load Summary
Peak Load Summary - Alternative 1 AIt1
Zone 3 Zone3
Areas ( ft2 )
Floor: 1,620.0
SlabOnG/ExFlr: 135.0
Roof: 1,620.0
Skylight: 0.0
Wall: 753.0
Wall Glass: 462.0
Partition: 792.0
Space Sens Load
Spc Sens Ld W/Sfty Fctr
Cool Airflow
Cool Airflw W/Sfty Fctor
Cooling Check
Cool Check W/Sfty Fctr
Heat Airflow
Heat Airflw W/Sfty Fctr
34,321.3
37,753.4
1,837
2,021
1.13
1.25
1,837
2,021
Btuh
Btuh
cfm
cfm
cfm/ft2
cfm/ft2
cfm
cfm
Heating Coil Peak
Outside Air: OADB: 26
Cooling Coil Peak
Peaked at Time: Mo/Hr:
Outside Air: OADB:
WB:
RELHUM:
7 / 14
79
64
44.2%
Cooling Coil Peak
Heating Coil Peak
Total Load
Sens Load
Percnt of Tot
Peak Tot Sens
Percnt of Tot
( Btuh)
( Btuh )
(%)
( Btuh)
(%)
ENVELOPE LOADS
Solar
Skylight Solar
0.00
0.00
0.00
Glass Solar
7,826.76
7,826.76
0.00
Sub Total
7,826.76
7,826.76
16.00
0.00
0.00
Conducted
Skylight
0.00
0.00
0.00
Roof
40.42
40.42
-3,278.88
Glass
1,638.48
1,638.48
-10,604.90
Wall
-60.99
-60.99
-1,391.54
Partition
0.00
0.00
0.00
SlabOnG/ExFlr
0.00
0.00
-4,336.20
Sub Total
1,617.90
1,617.90
3.31
-19,611.60
50.54
INTERNAL LOADS
Lights
4,343.71
4,343.71
0.00
People
7,384.40
3,253.40
0.00
Misc
18,506.40
18,506.40
0.00
Sub Total
30,234.50
26,103.50
61.79
0.00
0.00
MISC LOADS
Outside Air
4,567.22
2,634.53
-15,664.80
Humidification
0.00
0.00
0.00
Infiltration
1,027.62
592.77
-3,524.58
Sup. Fan Heat
2,624.76
2,624.76
0.00
Ret. Fan Heat
0.00
0.00
0.00
Duct Heat Pkup
1,615.12
1,615.12
0.00
Exhaust Heat
-585.43
-585.43
0.00
Sub Total
9,249.29
6,881.75
18.90
-19,189.40
49.46
OV/UNDR Sizing
0.00
0.00
0.00
Grand Total
48,928.50
42,429.90
-38,800.90
W/Safety Factor
53,821.30
46,672.90
-42,681.00
7 / 14
79
64
44.2%
•PERMIr COORD.
COP
PLAN REVIEW/ROUTING SLIP
ACTIVITY NUMBER: M13-053 DATE: 03/05/13
PROJECT NAME: FUSE NETWORKS
SITE ADDRESS: 12628 INTERURBAN AV S
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # after Permit Issued
DEPARTMENTS:
0444 Bis (ding Division
Public Works
04,0
Fire Prevention
Structural
Planning Division
❑ Permit Coordinator ❑
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Incomplete ❑
Complete tyl
DUE DATE: 03/07/13
Not Applicable ❑
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
TUESITHURS ROUTING:
Please Route Structural Review Required ❑ No further Review Required ❑
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved ❑ Approved with Conditions k Not Approved (attach comments) ❑
DUE DATE: 04/04/13
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
Contractors or Tradespeople iliter Friendly Page
General/Specialty Contractor
A business registered as a construction contractor with L&l to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name
Phone
Address
Suite/Apt.
City
State
Zip
County
Business Type
Parent Company
IECS INC
2069399495
Po Box 19252
Seattle
WA
981091252
King
Corporation
UBI No. 601639846
Status Active
License No. IECS***044QL
License Type Construction Contractor
Effective Date 11/13/1996
Expiration Date 11/20/2014
Suspend Date
Specialty 1
Specialty 2 Unused
Heating/Vent/Air-Conditioning And Refrig (Hvac/R)
Other Associated Licenses
License
Name
Type
Specialty 1
Specialty
2
Effective
Date
Expiration
Date
Status
SEATTMI038NRSEATTLE
MECHANICAL INC
Construction
Contractor
Metal
Fabrication
Unused
8/19/1997
11/4/2001
Archived
Business Owner Information
Name
Role
Effective Date
Expiration Date
HUMPHREY, GEORGE
President
01/01/1980
Bond Information No records found for the previous 6 year period
Assignment of Savings Information
Page 1 of 2
Savings
Assignment of Savings Account Number
Effective Date
Release Date
Assignment Type
Impaired Date
Amount
Received Date
2
10/10/1996
3/4/2009
Bond
08/01/2011
$4,000.00
08/15/2012
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
14
Allied Property
a Cas Ins Co
ACP7505636456
08/01/2012
08/01/2013
$1,000,000.00
08/15/2012
13
Twin City Fire
Ins Co
52 UUN PE8855
08/01/2011
08/01/2013
08/15/2012
$1,000,000.0007/26/2012
12
WEST
AMERICAN INS
CO
BKW1153913555
08/01/2010
08/01/2011
$1,000,000.00
07/28/2010
11
LIBERTY
NORTHWEST
INS CORP
BKW1053913555
08/01/2009
08/01/2010
$1,000,000.00
07/21/2009
10
FEDERAL
MUTUAL INS CO
9821065
08/01/2007
08/01/2009
$1,000,000.00
06/26/2008
9
FEDERATED
MUTUAL INS CO
5090561
08/01/2006
08/01/2007
$1,000,000.00
07/31/2006
Summons/Complaint Information No unsatisfied complaints on file within prior 6 year period
Warrant Information No unsatisfied warrants on file within prior 6 year period
httns://fortress.wa. eov/lni/bbin/Print. asnx
03/18/2013
PROJECT #C-1014
REVIEWED FOR
CODE COMPLIANCE
APPROVED
MAR 13 2013
S 13
+__ S 4111
1374
it
IS 4300a '
siCo
514 i
CONSTRUCTION TYPE:
OCCUPANCY GROUP(5):
ZONE:
LOT AREA:
TENANT SUITE:
2-NE1.11 CARRIER (MODEL 48TC A06) ROOFTOP GAS/ELECTRIC HVAC UNIT AND CURB
1 -NEW CARRIER (MODEL 48TC A04) ROOFTOP GAS/ELECTRIC HVAC UNIT AND CURB
I -NEW HONEYWELL T-8000 THERMOSTATS
TUKWILA COMMERCE PARK, BUILDING A
12628 INTERURBAN AVE S
BUILDING'C
TUKWILA, WA
0004800003
0004800003ft
V-6 SPRINKLEREc
GROUP' 5 OFFICE
C /L I
465,295 SQ FT (10.68' ACRES)
8,046 OVERALL
5,069 SF OFFICE
LEGAL' DESCRIPTION'
LEWIS C C -D C * 31 BEG N 81-44-15 E 199.11 FT FROM He AT END
OF CURVE ON CENT LN OF DUWAMISH-RENTON JUNCTION RD 50 HUB
BEING APPROX 1200 FT N AND 440 FT W OF 1/4 COR BET, SECS 14 `4
15-23-4 114 N 49-24-00 UJ 2535 FT TN N 09-36-00 E 52 FT TO TRUE
BEG TH 5 82-40-30 E 590 FT T14 N 59-22-30 E 64335: FT 114 N
01-51-30 W 343 FT TO LEFT `BANK OF, DUWAMISH RIVER BEING NLY
BOUNDRY OF LEWIS D C TN SWLY ALG SD BANK OF RIVER TO PT N
00-39-40 W OF TRUE` BEG TH 5;:00-39-40 E TO TRUE BEG ALSO POR
OFDCLYWOFABOVE DESCRIBED LAND SLY 16.15FTAND AI6FT
STRIP ADJ AND PAR. TO ELY LN OF R/W OF P S ELEC CO FOR JOINT RE)
TGW LOT 41 OF PLAT OF RIVERSIDE INTERURBAN TR5
0. 4,
F-4 cq
� d
xW �c g .�
o n a�a
U �oo�
REVISION
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional pian review fees.
SEPARATE PERMIT
REQUIRED FOR.
Emporinoi
ggsebted
4e
City of Tukwila
BUILDING DIVISION
G.MO
DATE: 02-24-2013
RECEIVED
CITY OF TUKWILA
MAR 05 2013
PERMIT CENTER
C1
3
Iof
PROJECT #C-1014
HVAC PLAN KEYNOTES
1. INSULTATE ALL DUCTWORK PER 2009 WA. STATE ENERGY CODE
2. PROVIDE 7 DAY PROGRAMBLE THERMOSTATE.
3. BALANCE AND COMMISION SYSTEM. PROVIDE REPORT TO
OWNER WHEN COMPLETED
4. ROOF TOP UNIT TO BE PROVIDED WITH ECONOMIZER.
5. OUTSIDE AIR REQUIREMENTS WILL BE PROVIDED BY
ECONMIZER SEE CALCULATIONS BELOW.
6. THE PROPOSED OCCUPANCY OF 48 PEOPLE. FRESH AIR
REQUIMENTS FOR EACH PERSON IS 20CFM PER PERSON.
THE ECONMISER IN THE ROOF TOP UNITS WILL PROVE
955CFM OF OUTSIDE AIR.
COOLING
UNIT WEIGHT
CARRIER
CARRIER
CARRIER
RTU 1, NEW CARRIER
(MODEL #48TCD06)
5 TON GAS/ELECTRIC
HVAC UNIT AND CURB.
SEE UNIT SPECIFICATIONS
AND INSTALLATIOM
THIS SHEET
SYSTEM DESCRIPTION
PROVIDE ,5 MQW GAS/ELECTRIC ROOF TOP. tIM15WITH NEW WITH DUCTWORK
AND DIFFUSERS FOR NEW OFFICE SPACE. INSTALL 2 NEW EXHAUST FANS FOR NEW
RESTROOMS. RUN NEW GAS FROM EXISTING GAS LINE TO NEW ROOF TOP UNITS.,
NEW ROOFTOP UNIT
° ° 60 CFM
n —
RTU 3, NEW CARRIER
3M
TON LGAGAS/ELECTRIC
HVAC UNIT AND CURB.
SEE UNIT SPECIFICATIONS
AND INSTALLA11OM
THIS SHEET
RTU 2, NEW CARRIER
(MODEL #48TCD06)
5 TON GAS/ELECTRIC
HVAC UNIT AND CURB.
SEE UNIT SPECIFICATIONS
AND INSTALLA11OM
THIS SHEET
COD
U
ri4 1.6.1
4.4 VD bd
44 C4
REVISION
DATE: 02-25-2013
RECEIVED
CITY OF TUKWILA
MAR 0 5 2013
PERMIT CENTER
M1
Rof 3
REVISION
DATE: 02-25-2013