HomeMy WebLinkAboutPermit M13-058 - ORKIN - REPLACE ROOF TOP UNITORKIN
925 INDUSTRY DR
M13-058
City Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-431-2451
Web site: http://www.TukwilaWA.gov
MECHANICAL PERMIT
Parcel No.: 2523049034
Address: 925 INDUSTRY DR TUKW
Project Name: ORKIN
Permit Number: M13-058
Issue Date: 04/11/2013
Permit Expires On: 10/08/2013
Owner:
Name: WALTON CWWA TUKWILA 1 LLC
Address: C/O CTMT - WALTON RE TAX , 4678 WORLD PARKWAY CIR 63134
Contact Person:
Name: JOFFRE SECHIER
Address: 3202 C ST NE , AUBURN WA 98002
Email: JOFFRE@COMFORTMECH.COM
Contractor:
Name: COMFORT MECHANICAL INC
Address: 6617 S 193 PL, #P-105 , KENT, WA 98032
Contractor License No: COMFOMI015LA
Phone: 425 251-9840
Phone: 425-251-9840
Expiration Date: 04/25/2014
DESCRIPTION OF WORK:
REPLACE (1) EXISTING 5 -TON ELECTRIC ROOFTOP UNIT WITH NEW 5 -TON PACKAGED HEAT
PUMP.
Value of Mechanical: $5,550.00
Type of Fire Protection: UNKNOWN
Electrical Service Provided by:
Permit Center Authorized Signature:
Fees Collected: $257.06
International Mechanical Code Edition: 2009
t'6A•1 �IXJC Date:
ot-titib
I hereby certify that I have read and = amin d this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, hether specified herein or not.
The granting of this permit does not pre u - to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the erfoijcn4nce of work. I am authorized to sign and obtain this mechanical permit and agree to the conditions on the
back of this permit.
Signature:
Print Name:
Date: 4 u /i
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
IAI') AMC'
Drin+crl• nd_11_9n1R
PERMIT CONDITIONS
Permit No. M13-058
1: ***BUILDING DEPARTMENT CONDTfIONS***
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431-3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: Readily accessible access to roof mounted equipment is required.
6: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
7: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap the sanitary
sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks, wells, and other
excavations. Final inspection approval will be determined by the building inspector based on satisfactory completion of
this requirement.
8: Manufacturers installation instructions shall be available on the job site at the time of inspection.
9: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the City of Tukwila
Building Department (206-431-3670).
10: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206-431-3670).
11: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
doc: IMC -4/10
M13-058 Printed: 04-11-2013
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila. 1V4 98188
http://www.TukwilaWA.Rov
Mechanical Permit No.
Project. No.
t 3
Date Application Accepted CPA 20
� .
Date Application Expires MATO
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
King Co Assessor's Tax No.: 2523049034
Site Address: 925 INDUSTRY DRIVE Suite Number: Floor:
Tenant Name:
ORKIN
PROPERTY OWNER
Name: JOFFRE SECHIER
Name: CWWA TUKWILA 1 LLC
City: AUBURN State: WA Zip: 98002
Address: 825 INDUSTRY DR
Zip: 98002
City: TUKWILA- State: WA
Zip: 98188
CONTACT PERSON - person receiving all project ,:.. .
communication
Name: JOFFRE SECHIER
Address: 3202 C ST NE
City: AUBURN State: WA Zip: 98002
City: AUBURN State: WA
Zip: 98002
Phone: (425) 251-9840 Fax: (253)
736-6598
Email: joffre@comfortmech.com
New Tenant: ❑ Yes m..No
MECHANICAL CONTRACTOR INFORMATION
Company Name: COMFORT MECHANICAL
Address: 3202 C ST NE
City: AUBURN State: WA Zip: 98002
Phone: (425) 251-9840 Fax: (253) 736-6598
Contr Reg No.: COMFOMI015LA Exp Date: 04/25/2014
Tukwila Business License No.: BUS -0993365
Valuation of project (contractor's bid price): $
Describe the scope of work in detail:
REPLACE (1) EXISTING 5 -TON ELECTRIC/ELECTRIC ROOFTOP UNIT WITH NEW 5 -TON PACKAGED HEAT PUMP.
5,550
Use: Residential: New ❑ Replacement ❑
Commercial: New ❑ Replacement
Fuel Type: Electric m Gas
Other:
H:\Applications\Forms-Applications On Line \2011 Applications\Mechanical Permit Application Revised 8-9.1 I.docx
Revised: August 2011
bh
Page 1 of 2
indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Furnace >100k btu
Floor furnace
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cooling
system
1
Air handling unit
<10,000 cfm
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system
Hood and duct
Incinerator — domestic
1
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
Thermostat
Wood/gas stove
Emergency generator
Other mechanical
equipment
1
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/I,750,000 btu
50+ hp/1,750,000 btu
PERMIT APPLICATION. NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF P RJU Y tY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING 1 E' 1.' AUTHORIZED AGENT:
Signature: Date: 03/20/2013
Print Name: I 'a F ''►ECHIER Day Telephone: (425) 251-9840
Mailing Address: 3202 C ST NE AUBURN WA 98002
City State Zip
F1:\Applications\Forms-Applications On Line \2011 Applications\Mechanical Permit Application Revised 8-9-I I.docx
Revised: August 2011
bh
Page 2 of 2
r
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206-431-3665
Web site: http://www.TukwilaWA.gov
Parcel No.: 2523049034
Address: 925 INDUSTRY DR TUKW
Suite No:
Applicant: ORKIN
RECEIPT
Permit Number: M13-058
Status: PENDING
Applied Date: 03/20/2013
Issue Date:
Receipt No.: R13-01091
Payment Amount: $257.06
Initials: JEM Payment Date: 03/20/2013 11:36 AM
User ID: 1165 Balance: $0.00
Payee: JOFFRE T SECHIER, COMFORT MECHANICAL
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 310253
ACCOUNT ITEM LIST:
Description
257.06
Account Code Current Pmts
MECHANICAL - NONRES
PLAN CHECK - NONRES
000.322.102.00.00 205.65
000.345.830 51.41
Total: $257.06
.Inn• Dnnninl_rla
Printarl• n3 -9n -9n13
FINSPECTION RECORD
etain a copy with permit
INSPEC110'N NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
piis_ 0-sE
Project:
0R1{LN
Type of Inspection:
riz Awl -7W C., -- C -73 -...Ni A L._
Address:
Ste. _ gym. ttS i P 4 ..fl2-
Date Called:
Special Instructions:
Date Wanted:. _a.m� .
Requester:
Phone No:
aocs-% 3 3 8 Z .
''Approved per applicable codes.
ElCorrections required prior to approval.
COMMENTS:
i t
iii -)014-1-1
.,y i b /----/
/-7,4,
4
/
.s....1)
:0- 1
N
r
Inspect � Date: 2 '
:3/tem
nAAA, jui/l! / (� l
n REIN PS ECTION FEE REQUIRED. rior to net inspection. fee mus e
e/d/ait 6300 Southcenter Blvd.. Suite 100,Call to schedule reinspection.
i
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF T.UKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila: WA 98188 �, (206).431-3670
Permit Inspection Request Line (206) 431-2451
M13-0,.5°
Project:
0Ril-.-tki
Type of Inspection:
i S•A
0 R17/ 7: J --7)'.,m —
k)J,2/'/P
Address: (
`i 2S ...tu'.l(
� it....✓
Date Called:
•
Special Instructions:
—
1.4 Date Wanted:. C
,
arm:
Requester:
-�
D • s • ,-Sr.7"/,
PhoneNo:
--fid 4/4/41/
JApproved per applicable codes. Corrections required prior to approval.
COMMENTS: i.r
0 R17/ 7: J --7)'.,m —
k)J,2/'/P
...!., Re-ir1 5 ,,,,, A7 ►o..., —-
' � Njei i , 5 (. – iv!,
7) p,P6_ f N SLrL4 -/, tS &
_ ///,`z/
5-- A r b (7�2vs3 00.4)4/
77
D • s • ,-Sr.7"/,
5
--fid 4/4/41/
Inspect f: 1
roVA t-(il 1 )L4
r1/11EI1SPECTION FEE REQUIRE. Prior to ne inspection, feemustbe'
i,Paid at 6300 Southcenter Blvd. Suite 100. all to schedule reinspection.
Project: Kidder -Mathews -5T Commercial PHP
Prepared By:
5T Pkg HP
03/13/2013
12:57PM
REVIEWED FOR
CODE COMPLIANCE
APPROVED
APR 0 9 2013
City of Tukwila
BUILDING DIVISION
A�-
5T Pkg HP
PZZE
e4 �� COPY
Tag Cover Sheet
Unit Report
Certified Drawing
Performance Report
Unit Feature Sheet
RECEIVED
CITY OF TUKWILA
MAR 2 0 2013
PERMIT CENTER
Packaged Rooftop Builder 1.34
Page 1 of 8
CO R-21-1
Unit Report For 5T Pkg HP
Project: Kidder -Mathews -5T Commercial PHP 03/13/2013
Prepared By:
12:57PM
Unit Parameters
Unit Model. 50TCQA06A0A3-0A0A0
Unit Size. 06 (5 Tons)
Volts -Phase -Hertz. 208-1-60
Heating Type. Heat Pump
Duct Cfg• Horizontal Supply / Horizontal Return
Standard One -Stage Cooling Refrigeration Coil
Lines and Filters
Condensate Drain Line Size. 3/4
Return Air Filter Type. Throwaway
Return Air Filter Quantity. 4
Return Air Filter Size. 16 x 16 x 2
Unit Configuration
Electric Drive X13
AI/Cu - AI/Cu
Base Electromechanical Controls
Standard Packaging
Warranty Information
1 -Year parts (STD.)
5 -Year Compressor (std.)
Dimensions (ft. In.) & Weight (Ib.)'**
Unit Length. 6' 2.375"
Unit Width. 3' 10.75"
Unit Height 3' 5.375"
— Total Operating Weight 660 Ib
•** Weights and Dimensions are approximate. Weight does
not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.
No optional warranties were selected.
NOTE: Please see Warranty Catalog 500-089 for explanation of policies and ordering methods.
Ordering Information
Part Number
Description
Quantity
50TCQA06A0A3-0A0A0
Rooftop Unit
1
Base Unit
Electromechanical control, No intake or exhaust option
None
Accessories
CRECOMZR024A02
Horizontal EconoMi$er IV with solid-state controller
1
Packaged Rooftop Builder 1.34
Page 2 of 8
Project: Kidder -Mathews -5T Commercial PHP
Prepared By:
Certified Drawing for 5T Pkg HP
03/13/2013
12:57PM
1 40 -ES:
. [N 4163(06AIN 6(6580D1NE45(ON5
2 CENTER OF GRAVITY
3 .110 DIREC1(014 OF AER FLOW
UNIT
301(0604
33 3/8
1847;
185/8
14723
501[0605
33 3/8
18411
147/8
(3111
50120006
41 3/8
111511
141/8
13171
50120607
41 3/8
110511
14 1/8
3311/
FILTER ACCESS PANEL
(TOOL -LESS)
•
•
CONP.•
ACCESS
' PANEL '
CONDENSER
COIL
INDOOR COIL
ACCESS PANEL
CONDUIT SIZE
USE
BAC((
2-5/8
1611
TIP
CURB
WIDTH
CONDENSER
C016
OPTIONAL
FACTORY
INSTALLED
CONVENIENCE
OUTLET
41
4-5/8
11181
ELECTRICAL
DISCONNECT
LOCATION
0
UNITED P2. 301 OM
TECHNOLOGIES 1186161. If
CARRIER 11847
18(1 30314-81 11 147 8x03111' Y C8811713 COM0110104
6133 (011 13 (03[1( 11 1l1010[¢p3 61143(n11(8xNMLA1FE
x60M011110113sn
:MM.
168((11881 081311(IrI 8611 811(81141
81(1108(1 p
ICC[nIEC[ 01 6(1188(1.
1- 333/8
18481
ECONOMIZEN HOOD
(OPTIONAL/
16-(/8
11 91
19-1/2
(4941
F 3-3/l
I 6951
46 3/4
111871
_EFT
12-1/4
(3121
SEE T4RU THE -
BASE CHART
•
25 TJ
66361
32 1/4
18161
25-5/8 ---•'
16521
RETURN AIR
E ALT. .
CONDENSATE
DRAIN OPENING
IN BASEPAM
16
14061
1
10-7/8
(2771
6.I/4
J1571
4-
11.3/4
14511
SUPPLY
AIR
l
TOP
12-1/8
(3011
18-1/2
(4701
1 29-3/8
411
RETURN
I AIR
11411
26-1/2
16731
f 3-3/8
OPTIONAL CONTROL BOX
FACTORY ACCESS PANEL
INSTALLED
DISCONNECT I
INDOOR BLOWER
ACCESS
.Roo
HANDL
14 3/8
118881
FP,ONT
HANDLE
1851
y
503331
AIR
11-318
6-178
CONNECTION SIZES
A 1 3/8• (351 DIA FIELD POWER SUPPLY NILE
2' 1511 DIA POWER SUPPLY 660260UT
1 3/1' 1441 DIA GAUGE ACCESS PLUG
D 17/8' 1221 DIA FIELD CONTROL WIRING HOLE f
[ 3/l•-14 1171 CONDENSATE DRAIN
2 1/2 ' 1641 DIA POWER SUPPLY KNOCK -OUT
TNRU-THE-BA E CHAR
THESE HOLES REQUIRED FOR USE
CRBTMPWR00IAD1
THREADED
WIRE
REO'D HOLE
CONDUIT SIZE
USE
SIZES IMAX.1
W
1/2'
ACC.
1/6' 122.21
X
1/2'
24V
1/8' 122.21
T •
3/4' 10011
POWER
1 1/8' 128.11
FOR 'THRU-THE-BASE
AN' FA TORY OPTION.
7111(4G5 FOR ONLY R 6 1 ARE
PROVIDED
SELECT EITHER 3/4' OR 1/2'
•
FOR POWER. DEPENDING OM WIRE SIZE
E STD.
CONDENSATE
DRAIN
'
25-1/8
16381
16-3/4 .-I
RETURN
1211
AIR
SUPPLY AIR
ILTER
OUTSIDE
14(8
31 /4-+
314333' 1197]
A(R RE10RN
RIGHT AIR
BAROMETRIC
RELIEF
FLOW
11([1 I HT[
1 OF 2 103-10-C9
30[1(13[3
01-23-09
50TC0 04-07 SINGLE ZONE ELECTRIC
HEAT POMP
48TA1501 501
818
5.0
Packaged Rooftop Builder 1.34
Page 3 of 8
(t') WY- 4-f-1
Project: Kidder -Mathews -5T Commercial PHP
Prepared By:
Certified Drawing for 5T Pkg HP
03/13/2013
12:57PM
Uh]1
STD. UN11
WEIGHT
CORNER i CORNER
WEIGHT IA1 ; I8)
CORNER 1 CORNER
RIC) WEIGHT ID)
REAM
1
C G.
HEIGHT 1
190.
KG.
195.
KG. 1 LBS.
KG.
L85.
NG. i LBS.
6G.
X
1
2
501(0404
505
229
136
62 ' 130
59
117
53
'23
56
136
1/4
(9211122
1/8
15621
16 3/8
;4161
502(0405
510
231
138
63
131
59
118
SA
124
56
136
135
1/4
19211;22
1/8
15621
16 1/2
14191
501(0606
590
258
159
72
146
66
131
62
149
68
5/8
19051'22
5/8
15151
20 1/8
1511)
501(0407
630
288
166
75
156
75
119 1 68
149
1 68
37
1/4
19461122
7/8
25621
20 3/4
15271
CORNER A
I I
680IED 1 O. hoc 0101
TECH.OLOGIES Stt(WSE. n
CARRIER um
1X11 0 )0/II1 ;1100 1R01*.11 00 GR:01 CCOGtl110N
0 0 10 00010010( %000 100 0011001 *00011;00 1X11 100
81;4;124 WA,604,1 0* *000 r[l0pf Gen*.
00.'110(04 01 1x000 01/01040 0* 0010.60"1!
0021101 0000n1P0 1001 00100 **N(( 01 4
406(7000( 01 *0411101, i
CORNER B
CORNER C
: 000
FRONT
64021 I RATE
. 2 or 2 1 03-10-09
sm(1Gsu
01-23-09
50TCO 04-07 SINGLE ZONE ELECTRIC
HEAT PUMP
48TM501501
771
5.0
Packaged Rooftop Builder 1.34
Page 4 of 8
Performance Summary For 5T Pkg HP
Project: Kidder -Mathews -5T Commercial PHP 03/13/2013
Prepared By:
12:57PM
Part Number: 50TCQA06A0A3-0A0A0
ARI SEER: . ..
13.20
Base Unit Dimensions
Unit Length' 74.4 in
Unit Width. 46.8 in
Unit Height 41.4 in
Operating Weight
Base Unit Weight 590 Ib
Accessories
Horizontal EconoMi$er IV with solid-state controller 70 Ib
Total Operating Weight 660 Ib
Unit
Unit Voltage -Phase -Hertz' 208-1-60
Air Discharge. Horizontal
Fan Drive Type. Direct
Actual Airflow. 1970 CFM
Site Altitude' 0 ft
Cooling Performance
Condenser Entering Air DB. 95.0 F
Evaporator Entering Air DB'80.0 F
.................
Evaporator Entering Air WB. 67.0 F
Entering Air Enthalpy 31.44 BTU/Ib
Evaporator Leaving Air DB. 58.0 F
Evaporator Leaving Air WB. 57.2 F
Evaporator Leaving Air Enthalpy. 24.54 BTU/Ib
Gross Cooling Capacity. 61.13 MBH
Gross Sensible Capacity 46.91 MBH
Compressor Power Input 5.50 kW
Coil Bypass Factor 0.203
Heating Performance
Outdoor Ambient Temperature 47.0 F
Entering Air Indoor Coil DB. 70.0 F
Leaving Air Indoor Coil DB. 97.4 F
Total Heating Capacity. 58.31 MBH
Integrated Heating Capacity. 58.31 MBH
Heating Power Input 4.67 kW
HSPF 7.7
Supply Fan
External Static Pressure. 0.60 in wg
Options / Accessories Static Pressure
EconoMi$erlV / EconoMi$er2. 0.12 in wg
Total External Static. 0.72 in wg
Fan RPM. 1200
Fan Power 1.00 BHP
Fan Motor Size, hp' 1
NOTE:. Motor Speed Tap 2, Horz, Direct Drive
Electrical Data (Before July 30, 2012)
Minimum Voltage. 187
Maximum Voltage.253
...............
Compressor #1 RLA. 26.2
Compressor #1 LRA' 134
Outdoor Fan Motor Qty:.. __ . 1
Packaged Rooftop Builder 1.34 Page 5 of 8
Performance Summary For 5T Pkg HP
Project: Kidder -Mathews -5T Commercial PHP 03/13/2013
Prepared By:
12:57PM
Outdoor Fan FLA (ea).
Indoor Fan Motor Type. Direct Drive
Indoor Fan Motor FLA. 7.4
Power Supply MCA* 41.7
Power Supply MOCP (Fuse or HACR):. 60
Min. Unit Disconnect FLA. 40
Min. Unit Disconnect LRA. 145
Electrical Convenience Outlet None
1.5
Electrical Data (July 30, 2012 and Beyond)
Indoor Fan Motor FLA' 7.4
Power Supply MCA. 42
Power Supply MOCP: .... 60
Disconnect Size FLA. 40
Disconnect Size LRA. 145
July 30th and beyond units can be identified by serial number 3112XXXXXXXXX and higher
Control Panel SCCR: 5kA RMS at Rated Symmetrical Voltage
Acoustics
Sound Rating
80.0 db
Sound Power Levels, db re 10E-12 Watts
Discharge Inlet Outdoor
63 Hz NA NA 92.7
125 Hz NA NA 84.9
250 Hz NA NA 79.0
500 Hz NA NA 76.7
1000 Hz NA NA 73.8
2000 Hz NA NA 69.6
4000 Hz NA NA 66.4
8000 Hz NA NA 62.8
Advanced Acoustics
Advanced Accoustics Parameters
1. Unit height above ground: 30.0 ft
2. Horizontal distance from unit to receiver 50.0 ft
3. Receiver height above ground. 5.7 ft
4. Height of obstruction' 0.0 ft
5. Horizontal distance from obstruction to receiver 0.0 ft
6. Horizontal distance from unit to obstruction. 0.0 ft
Detailed Acoustics Information
Octave Band Center Frequency, Hz
63
125
250
500
1k
2k
4k
8k
Overall
Sound Power Levels at Units Acoustic Center (Lw), dB
92.7
84.9
79.0
76.7
73.8
69.6
66.4
62.8
93.7 Lw
A -Weighted Sound Power Levels at Units Acoustic Center (LwA), dBA
66.5
68.8
70.4
73.5
73.8
70.8
67.4
61.7
79.5 LwA
Sound Pressure Levels at Distance Specified above (Lp), dB
60.3
52.5
46.6
44.3
41.4
37.2
34.0
30.4
61.3 Lp
A -Weighted Sound Pressure Levels at Distance Specified above (LpA), dBA
34.1
36.4
38.0
41.1
41.4
38.4
35.0
29.3
47.1 LpA
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
Packaged Rooftop Builder 1.34
Page 6 of 8
Performance Summary For 5T Pkg HP
Project: Kidder -Mathews -5T Commercial PHP 03/13/2013
Prepared By:
12:57PM
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
Packaged Rooftop Builder 1.34 Page 7 of 8
Unit Feature Sheet for 5T Pkg HP
Project: Kidder -Mathews -5T Commercial PHP 03/13/2013
Prepared By: 12:57PM
e
Vl�eatherMakef- SOTCQ
PACKAGED ROOFTOP HEAT PUMP UNITS
3, 4, 5, 6, 7-112, 8-112,10 and 12.5 TONS
50TCQunits are high -efficiency single -packaged heat pump units
that are pre -wired and prechargedwith PURON (HFC)
refrigerant. Electricheatis availableas a field -installed accessory.
The units arefully fadorytestedand agency certified
US
Ai CFFl1tFIE0.
lir rib •xPM*MIN
iiis• made.
moolkatarlp
t•M•400o e.
tl•at•rego W •mktheianclonvali.
Certified to ISO 9001
PERFORMANCE FEATURES
• PURON (R -410A) HFC refrigerant
• ASHRAE.90.1 energy compliant
• SEERsupto13.4.EERsupto 11 2
• IEER'supto 12.2
• HSPF's up to 1.7 and COP's up to 3 3
• Single stage cooing cap ear/ control on04-07 models
• Two-stage cooling cap acdycontrol on 08 - 14 models
• Exotusrve noncorrosive composite condensate pan an accordance with
ASHRAE 62 Standard. sloping design: side or center dram
• Field convertible from vemcal to honrontalanflow on as models. No
specialke recurred on 04-12 models. Supply duct lit required
for 14 size model only
• Coppertube atuminumfn coils with optional corrosion resistant cods
• Pre -painted extenorpanetsand primer ooated interior panetstested to
500 hours salt spray protection
• Aoutmtru refrigerant metering system
• Cooling operating range up to 115F (46C) and down to 25F (4C)
• Solid-state control board and easy access terminal board
• Refrigerant filter drier and accumulator on each refrigerant circuit
• Fully insulated cabinet
• Automatic changeoverwiien used with autochangeove:thermostat
• Rated in accordance with AHRI Standards240 (04-06 saes) and
340 (07-14)
• Dasigned in accordance with Underwviters" Laboratories Standard 1995
• Listed by UL and UL, Canada
MAINTENANCE FEATURES:
• Access panelsWith easy grip handles
• Innovative, easy starling, no strip strew features on unit access panels.
• Two-inch disposable return air filters
• Toot4ess fitter access door
• Belt drive evaporator -fan motor and pulley combinations available an at
sizes to meet any application
• Electric Drive x13 (5 speed/torque)motoron 04 to 06 models
• Canneltennvnal board facilitating simple safety circuit troubleshooting
and sunpkfred comml box arrangement
iN STALLATION FEATURES:
• Thmthe-bottampowerentrycapabiity standard
• Single point eleddcconnedions
• Full perimeter base rod with built-in rigging adapters and fork truck slots
RELIABILITY FEATURES:
• Scroll compressors with intemet linebreak overload protection
• Dependable Time /Temperature defrost board and logic
• 24-valtcontrol cicala protected with resettabtecucuitbreaker
• Permanentlytubricated evaporator -fan motor
• Totally endosedGond enserr motors With permanently lubricated
bearings
• Loss of charge, freeze protection, and high-pressure switches
STANDARD WARRANTY:
• 5-yesreiectric heaters
• 5-yearcompressor
• 1-yearparts
Many optional warranties also available
OPTION S INCLUDE BUTARE NOT UMITEDTO:
• Multi Protocol (RTU Open)and PremierL ,kT• Med Digital Contro4ers
• Non-fused disoonned switch
• Economizer options forelectro-mechan-ncaland DDC control
• Corrosion resistant cod options for evaporator and condenser
• Option attndoorfen motors for expanded airfbwcapability
• Accessory electric heat (field -in stalled option only)
• Smoke detectors— Supply and Return as
• lunged access panels
Packaged Rooftop Builder 1.34 Page 8 of 8
SUBMITTAL
FORM NO. 2502-11 P
SUBMITTED TO
COMPANY:
DRAWN BY:
JOB NAME:
EQUIPMENT
NOTES:
M. HARGIS
Horizontal economizer with built-in relief damper for Carrier
48150TC A/B04-A1B07; 50TCQ A04 -A07; 48/50TC A/D08,A09,A1D12,D14;
50TCQ D08 -D12; 48150HC A04-A07,D08-D12; 50HCQ A04-A07,D08-D09;
48/50TF,TM,HJ 004-014; 48150HE 003-005;
50TFQ 004-014; 5OHJQ 008-009 Units
FEATURES:
• Gear driven dampers, eliminates slippage associated
with standard linkage.
• Factory assembled hood.
• Direct coupled actuator.
• Low static pressure loss through economizer.
• 100% barometric relief capability.
• Top of hoods are sloped to allow for water run-off.
• Hoods are constructed of pre paint steel,
matching the finish of the HVAC unit. Water
entrainment filter provided.
Horizontal
E onomizer
ctuator
Part Number:
0849 Series
Carrier Units
MIcroMeti
Economizer No.
Weight
48150TC A/B04 A/B07;
50TCO A04 -A07; 48/50HC A04 -A06;
50HCQ A04 -A06:
48/50TF,TM,HJ,TFQ 004007;
48/50HE 003-006
0849-0101
86 lbs
48/50TC A/D08A09,A/D12,014;
50TCQ 008-012; 48150HC A07,
008-012, 50HCQ A07,008-009;
48/50TF.TM,HJ 008-014; 50TFQ
008-014; 5OHJQ 008-009
0849-0201
135 lbs
•; ECOnomRer includes• "<:.
Honeywell W7212. -
coirtrolier capable, of CO2,.
,; demand control and power
exhaust control.
Filter door
24 3/4"
Static Pressure Drop through Dampers - In w.g.
0849-0101
0849.0201
CFM
1200
1600
2000
2400
2800
3000
3400
4000
5000
Return Air
0.055
0.088
0.14
0.22
0.11
0.14
0.17
0.25
0.38
Outside Air
0.024
0.043
0.073
0.098
0.10
0.11
0.15
0.20
0.31
Outside air /
relief air hood
1. Return air test performed with
outside air damper 100% closed.
2. Relief air and outside air test
performed with retum air damper
100% closed.
NOTE A: This horizontal blank off is shipped with
the 0849-0201, but Is only used on the taller 8 1/2,
10, 12 1/2 ton units.
NOTE B: This panel extender is shipped with the
0849-0201, but is only used on the taller 8 1/2, 10,
12 1/2 ton units. If using the 0849-0101 with the
taller HJ007, the optional 0840-0100-FRBO panel
must be ordered.
THIS DOCUMENT IS THE PROPERTY OF MICROMETL CORPORATION AND IS DELIVERED UPON THE EXPRESS CONDITION THAT THE CONTENTS WILL NOT BE DISCLOSED OR USED WITHOUT MICROMETL'S WRITTEN CONSENT.
MICROMETL 3035 NORTH SHADELAND AVENUE, SUITE 300 • INDIANAPOIJS, IN 45226 • 1.800.662-4822 •• MICROMETL WEST 202 SOUTH 18TH ST. • SPARKS, NV 89431 • 1.800.884-4862
ED FOR
REVIEWMPLIANCE
CODE
DAPPROVED
APR 0g 2013
City NGDila
IVISION
BUILD
�� OF ‘,‘ \IN 4if-C-V3/7//
WAsy GOO(
zlrn4/, l
Q' `�R�;99 �'�.
46. ` FGISTER7, �k,� v
�6Z9/ONALEN z>
_ _ NS
EXPIRES 1p hzh3
D -
STRUCTURAL
CALCULATIONS
Orkin RTU
925 Industry Drive
Tukwila, Washington
MARCH 18, 2013
PREPARED FOR:
Comfort Mechanical
3202 C Street NE
Auburn, Washington 98002
PREPARED BY:
Moore Engineering Group
21902 96th Avenue SE
Snohomish, Washington
RECEIVED
CITY OF TUKWILA
MA2 2 3 20:3
PERMIT CENTER
Moore
Engineering
Group
M o�
GENERAL STRUCTURAL NOTES:
1. ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO
THESE NOTES AND THE INTERNATIONAL BUILDING CODE (IBC), 2009 EDITION.
2. DESIGN LOADING CRITERIA:
ROOF LIVE LOAD 25 PSF
MECHANICAL UNIT 660 POUNDS
EARTHQUAKE SDS = 0.912
SITE CLASS D to E
WIND 85 MPH, EXPOSURE B
3. STRUCTURAL CALCULATIONS AND SKETCHES SHALL BE USED IN CONJUNCTION
WITH MECHANICAL DRAWINGS FOR BIDDING AND CONSTRUCTION. CONTRACTOR
SHALL VERIFY DIMENSIONS AND CONDITIONS FOR COMPATIBILITY AND SHALL
NOTIFY ENGINEER OF ALL DISCREPANCIES PRIOR TO CONSTRUCTION.
4. CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES AND
CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING
CONSTRUCTION SHOWN ARE INTENDED AS GUIDELINES ONLY AND MUST BE
VERIFIED. THE EXISTING CONDITIONS SHOWN ON THE SKETCHES ARE BASED
EITHER ON SITE OBSERVATION, ORIGINAL DRAWINGS OR WERE ASSUMED BASED ON
EXPECTED CONDITIONS. IF THE EXISTING CONDITIONS DO NOT CLOSELY MATCH
THE CONDITIONS SHOWN ON THE SKETCHES, OR IF THE EXISTING MATERIALS ARE
OF QUESTIONABLE OR SUBSTANDARD QUALITY, NOTIFY THE ENGINEER PRIOR TO
COMMENCING ANY WORK.
5. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR THE STRUCTURE AND
STRUCTURAL COMPONENTS UNTIL ALL FINAL CONNECTIONS HAVE BEEN
COMPLETED IN ACCORDANCE WITH THE DRAWINGS.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL SAFETY PRECAUTIONS AND THE
METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES REQUIRED FOR THE
COMPLETION OF THE WORK.
7. FRAMING LUMBER SHALL BE KILN DRIED OR MC -19, AND GRADED AND MARKED IN
CONFORMANCE WITH W.C.L.B. STANDARD GRADING RULES FOR WEST COAST
LUMBER NO. 17. FURNISH TO THE FOLLOWING MINIMUM STANDARDS:
JOISTS: (4x MEMBERS)
HEM -FIR NO. 1 Fb = 975 PSI, Fv = 150 PSI
8. TIMBER CONNECTORS CALLED OUT BY LETTERS AND NUMBERS SHALL BE "STRONG -
TIE" BY SIMPSON COMPANY, AS SPECIFIED IN THEIR CATALOG NO. C-2012. INSTALL
NUMBER AND SIZE OF FASTENERS AS SPECIFIED BY MANUFACTURER. CONNECTORS
SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
9. SHEET METAL SCREWS SHALL CONFORM TO THE AMERICAN IRON AND STEEL
INSTITUTE (AISI) "SPECIFICATIONS FOR THE DESIGN OF COLD -FORMED STEEL
STRUCTURAL MEMBERS".
10. WOOD SCREWS SHALL CONFORM TO ANSI/ASME STANDARD B 18.6.1.
11. METAL STRAPS FOR ANCHORAGE OF MECHANICAL UNITS SHALL CONFORM TO ASTM
A446 GRADE A WITH A MINIMUM YIELD STRESS OF 33 KIPS PER SQUARE INCH.
12. CONNECT THE NEW UNIT TO THE EXISTING WOOD SLEEPERS WITH FOUR (4)
GALVANIZED METAL STRAPS, 1-1/2" IN WIDTH. CONNECT THE STRAPS TO THE UNIT
WITH #10 SHEET METAL SCREWS AND TO THE WOOD SLEEPERS WITH (2) #10 x 2"
LONG WOOD SCREWS.
M7PRo ro-rpWkrr
oF- F cF-roF UNIT" -Z,
s DEA.E
4-hC goo b
>✓os 462.
A�tilc-� c R.5
17 1 L, F -4,44A q * Pi. -I
•
Moore
Engineering
Group
PROJECT:
rJ r.l KT -Li
ENGR: \.\6V
DATE: 571V13
SCALE:
3/
SHEET
PROTECT DESCRIPTION: The project consists of the replacement of an existing rooftop
mechanical unit with a new unit.
LOADS: LIVE 25 PSF
DEAD
Roofing and re -roof 5.0
Plywood sheathing 1.5
2x4 @ 24" o.c. 0.7
4x14 @ 8' o.c. 1.5
Insulation 1.0
MEP 1.0
Ceiling & Lights 2.0
Total Dead 12.7
DEAD + LIVE
WIND 85 mph, Exposure B
SEISMIC
Latitude 47.449
Longitude -122.249
Site Class D to E
SDs (D) = 0.960
SDS (E) = 0.864
SDs = 0.912
EQUIPMENT
Existing New
Unit 565# 660#
Dimensions 52"x28"x28" high 74"x47"x42"
37.7 PSF
Moore
Engineering
Group
PROJECT:
ENGR:
DATE:
SCALE:
11/
SHEET
Design Maps Summary Report http://geohazards.usgs.gov/designmaps/us/summary.php?template=mi...
(GS Design Maps Summary Report
User -Specified Input
Report Title Orkin RTU
Mon March 18, 2013 14:00:54 UTC
Building Code Reference Document ASCE 7-10 Standard
(which makes use of 2008 USGS hazard data)
Site Coordinates 47.449°N, 122.249°W
Site Soil Classification Site Class D - "Stiff Soil"
Risk Category I/II/III
Rivennn-Baie•iard.
.ko Park's
Highline
011
USGS-Provided Output'
SS = 1.440 g
S1 = 0.536 g
fry
S = 1.440 g
SM3 = 0.803 g
(! )
23x.3
"1'61 41Saill
IJi
1" East Renton
Highlands
Cascade•FairAlvd
Mari!
• I. P.Igh13-Lake
a raaM
East
HiII Merid9a
SE 2101
SDs = 0.960 g
SDl = 0.536 g
For Information on how the SS and S1 values above have been calculated from probabilistic (risk -targeted) and
deterministic ground motions in the direction of maximum horizontal response, please return to the application and
select the "2009 NEHRP" building code reference document.
1.65
1.50
1.35
1.20
1.05
• 0.90
111 0.75
0.60
0.45
0.30
0.15
0.00
0.00
MCER Response Spectrum
0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80
Period. T (sec)
2.00
1.10
1.00
0.90
0.80
0.70
▪ 0.60
0.50
0.40
0.30
0.20
0.10
0.00
0.00
For PGAM, TI, CRs, and CRI values, please view the detailed report.
Design Response Spectrum
0.20 0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80
Period. T (sec)
2.00
1 of 2 3/18/2013 7:00 AM
Design Maps Summary Report http://geohazards.usgs.gov/designmaps/us/summary.php?template mi...
riU GS Design Maps Summary Report
User -Specified Input
Report Title Orkin RTU
Mon March 18, 2013 14:01:08 UTC
Building Code Reference Document ASCE 7-10 Standard
(which makes use of 2008 USGS hazard data)
Site Coordinates 47.449°N, 122.249°W
Site Soil Classification Site Class E - "Soft Clay Soil"
Risk Category I/11/III
Salmon
greet
Rivenen,Bi .vaid
Park
o
ar
H-tigiline
it rssa•rr
r. r
"i East Renton
Higlihnds.-
Scyliak i
State' E
114 gal
Burien
en
Cascade<Fainv ado Maple
East
Hill•Meridia
Des Moines
USGS-Provided Output
S = 1.440 g
S = 0.536 g
St4s = 1.296 g
SM1 = 1.286 g
Sps = 0.864 g
Sol = 0.857 g
Mexico
For information on how the SS and S1 values above have been calculated from probabilistic (risk -targeted) and
deterministic ground motions in the direction of maximum horizontal response, please return to the application and
select the "2009 NEHRP" building code reference document.
1.43
1.30
1.17
1.04
0.91
0.78
0.65
0.52
0.39
0.26
0.13
0.00
0.00 0.20
MCER Response Spectrum
0.40 0.60 0.80 1.00 1.20 1.40 1.60 1.80
Period. T (sec)
2.00
Design Response Spectrum
0.99-
0.90
.99-
0.90 -
0.91 -
0.72 -
0.63 -
I
O� 0.54-
V1 0.45
0.36
0.27 -
0.18 -
0.09 -
0.00 1 1 1 1 1 1 I 1 1 I
0.00 0.20 0.40 0.60 0.20 1.00 1.20 1.40 1.60 1.80 2.00
Period. T (sec)
For PGAM, To CRS, and CR1 values, please view the detailed report.
6/3
1 of 2 3/18/2013 7:01 AM
,r 8(1
ANo
e
cialtnolitt
nbt --
Azat
IN?
531 Tilt I5
r14=T
1—E.
"y0
-
'
akk
I
(Nj
7 Qi {%
Kial
w.xfr.
lil
c15 ,102
b�..
5
% 1b. P'\ ` ''^�c'.LKus
-tQ
1--. tZ - W- 4ro.'.
x3;;
Nka
FEATURES
Optional Duct Endosute — The RT10-65 duct endosure is required
for installation of the unit with the RMF9-65 roof mounting frame.
Duct enclosure is completely insulated with a baked -on enamel
finish and is shipped knocked down for field assembly. Supply and
retum air openings are located in the bottom of the enclosure. Field
assembled return air plenum is furnished for ceiling diffuser applica-
tions. Plenum connects to unit retum air opening segregating return
air within the enclosure.
Optional POWER SAVER* — The complete RD10.65 POWER -SAVER
and control system is shipped factory assembled and wired. The
Lennox POWER SAVER system consists of: duct enclosure, mechan-
ically linked outdoor air and recirculated air dampers with pressure
operated exhaust air dampers. The positioning of these dampers is
accomplished by a 24 vofl 3 position spring retum damper motor
with adjustable minimum damper positioner and controlled by the
room thermostat, adjustable mixed air controller, adjustable com-
pressor monitor and adjustable enthalpy control. The enthalpy con-
trol allows 0 to 100% outdoor air to be used for "free cooling" when
outdoor humidity and temperature are acceptable. The Lennox
POWER SAVER will co-operate with any heating -cooling thermostat.
A outdoor air intake hood is furnished and field installs over the
outdoor air dampers. Shipped knocked down, it is easily field as-
sembled. A cleanable polyurethane media frame fitter is fumished
with the hood providing extra air filtering and bird screen protection.
Optional RT10 Adapter Kit—Adapter kit (LB -2947568) includes fil-
ler panels and securing brackets to mate the duct enclosure and roof
mounting frame to CHA10-261, CHA10-311 and CHA10-410 models.
CO At- 23-, I
Optional Roof Mounting Frame— The RMF9-65 roof mounting
frame mates to the unit and duct enclosure providing an automatic
weather sealed installation. A mounting frame deck enclosure is
furnished to provide a weatherproof deck for mounting the unit on
the roof mounting frame. Approved by National Roofing Contractors
Association.
Optional Minimum Fresh Air Damper — OAD3-46165 minimum
fresh air damper mounts external to the RTU) -65 duct enclosure.
Equipped with manually operated damper and fittings for installing.
Optional SP11 Remote Status Panel -- The operation of the unit can
be checked on the Remote Status Panel (12F83) located within the
conditioned area. Signal lights on the panel indicate "Cool Mode,"
"Heat Mode," "Compressor 1," "Compressor 2," "No Heat" and
"Filter." The cool mode signal light is green when lit and indicates
cooling operation. Heat Mode light is green and reflects heating
operation and will tum red if there is an operational mulfunction_
Compressor 2 Tight is not required and should be disregarded. The
No Heat and Filter lights will show red and indicate a requirement for
service. Additional controls are required for use with the Status
Panel and must be specified when ordering. Fitter switch kit (97C85)
is used in conjunction with the Filter light. Operation of No Heat light
requires an additional control. see Price Book. Wiring Junction Box
(14F92) is required to interface status panel with unit operation. Box
field installs in unit.
SPECIFICATIONS
.Vt
Model No.
t:HA/0.261
CHA70 311
CHA10.411
CHA10d13
CHA10-461
CHA10.463
CHA10-511
CHAj0-513
CHA1oB-651
CHA10B-683
*ARI Standard 270 SRN .
19
20
?Q
21
ia.21
•ARI
Total cooling capacity (Btuh)
2000
29,000
34,00Q
-
43,000
47,500
,
56,500
Total unit watts
2590
3450
4090
5100
5950
6940
Standard
210
Ratings
tSEER (Mull/Watts) 1 phase model only-
8.85
8.25
8.2
8.9
8.15
8.2
ttEER (BtuhiWatts) 3 phase model only
----
---8.0
8.45
8.0
8.15
Dehumidifyingpiaty
26%
26%
28%
26%
25%
26%
Refrigerant
IR -22) charge
+5 lbs. 0 oz.
5 it's. 0 oz.
5 lbs. 13 oz-
Sibs. 10 oz.
8 lbs. 7 oz.
10 lbs. 0 oz.
Evaporator
Coil
Net face area (so. ft.)
2.9
3.0
3.0
45
4.5
5.75
Tube diem. (in.) & No. of rows
112 — 2
318 — 3
3/8 - 3
3/8 — 3
3/8 — 4
3)8 — 4
Fins per inch
15
10x9
16
10x9
1,8
11 x9
16
10x10
l4
12 x 12
14
10x10
Evaporator
Blower
Wheel nominal diam. x width (in.)
Motor horsepower
1/4
1rg
112
112
3/4
1
RPMFactory installed drives
----
----
----
----
-- -
980— 1230
ranfte •'Optional mofor-pul v
----
---
--
---
----
1175 —1450
Net face area (sq. ft.)
11.6
11.6
11.6
115.3
15.3
18.1
Condenser
Coit
Tube diem_ (in.) & No. of rows
318-2
3/8-2
318-2
318-2
3(8-2
3)8 — 2
Fins per inch
13
15
15
13
15
15
Diameter (in.) and N9. of blades
20-4
20-4
20-4
•24-4
24-4
24-4
Air volume (factory setting)
3200
3200
420Q
4100
4100
5500
Condenser
Fan
Rpm Jfactory setting)
1035
1035
1035
825
825
1065
Motor horsepower
1/4
1/4
114
1)4
1/4
1(2
Motor watts (factory setting) -i390
300
300
320
32Q
580
Condensate drain size mot (in.)
314
3/4
3)4
314
3/4
3/4
No. & size of filters (in.)
(1)16x25x1
(1)16x25x1
(1)16x25x1
(2)16x20x1
(2)16x20x1
(2)20x20x1 i
Net weight of basic unit (lbs.) (1 package)
310
330
335
495
515
565 al,
LB -379658
Optional Condenser Coil Guard - 3 required per unit
LB -33656B
LB -34491B
Optional Duct Enclosure (Net weight)
RT10-0 (5 lbs.)
RT10-65 (85 lbs.)
RT10B-65 (95 lbs.)
RD10B-65 (190 lbs.)
.(1)-20x25x1
Optional POWER SAVER (Net weight)
andNo.&sizeoffilter(in.)
RD10.65 (180 lbs.)
(1)-20x25x1
RD10-65 (180 lbs.)
- (1)-20x25x1
Optional Roof Mounting Frame (Net weigh
RMF9-65 (110 141
RMF9-65 (110 lbs.)
RT1 OIRD10 Adapter Kit (Net weight)
LB -2947588 (4 lbs.)
--- 4
-
Optional Minimum Fresh Air Damper (Net weight!
OA03-46165 (7 lbs.1
OA03.46165 7 lbs.)
Optional Comb. Supply & Return Transition (Net wt.)
SRT10-65 (20 lbs.)
SRT10.65 (20 lbs.)
Optional Combination Ceiling Supply
And Retum Step -Down Diffuser (Net weight)
RTD9-65 (67 lbs.)
RTD9-65 (67 lbs.)
Optional Combination Ceiling Supply
And Retum Flush Diffuser (Net weight)
FD9-65
(33 lbs.)
FD9-65
(33 lbs.)
*Rated in accordance with ARI Standard 270.
*Rated in accordance with ARI Standard 210: 450 dm (maximum) evaporator air volume per ton of cooling capacity, 95F outdoor air temperature and 80F db/67F wb
entering evaporator air.
••Optional motor pulley is furnished and must be field installed to obtain rpm range shown.
t Seasonal Energy Efficiency Ratio based on DOE test procedures.
ttEnergy Efficiency Ratio in accordance with ARI Standard 210.
— 11 —
DIMENSIONS (inches)
FILTER UNIT
ACCES8 cosnitot sox
PANEL \
COMPRESSOR
1 L.,11
,_.
.
:.
-N-)
‘
i I chi% ytR, xr _ 1 7.:...filiWGUARri ._. ; • '
L1\
l i :
RLTER i 1 ir I . , t 1
II
1
11 Is i 11
. I I, I.-. ,A,,-A.G.p.ar.austi rfirEargis' 11` IV
LJ
NCTION . ,
TIPTIONAL
ELECTRIC HEAT
(opposite sido)
CONDENSER cox
ENTERING AIR
(Both Wm & End)
0
1-112
CONDENSER COIL
EXHAUST AIR
Model No. A
0
C
D
8
F
G
H
J
K
CHA10-261. 311 & 41 ' ?-11116
a.
28-314
24
1-13116-4
7
15
4-71ET
2-3113-
22
CHA10-460 & 510 59-1118
40-314
Z1:1 -Li
34
2-314
8
15
6
2-112
34-314
CHA106-65.9 _59-15/16
40-314
33-3/4
34
2-314
8
20
6
2-1/2
. 34-314
CENTER OF GRAVITY (in.)
Model No.
L
M
CHA10-261
29-11116
11-3/4
CHA10-311
,
29-11116
11-314
CHA10-411-413
29-11/16
11-314
CHA10-461-483
34-518
17-112
CHA10-511-513
34-518
17-112
CHA1013-651-653 0
34-5/8
17-112
INSTALLATION CLEARANCES (inches)
313
35
•
12 tn
_.01.1AT.INCLOSUBE
..ERNAUST
AIR:OUTLET
24
NOTE —60 inches clearance
, recharge! an top of
CORNER WEIGHTS (lbs.)
Model No.
N
0
P
R
CHA10-261
77
106
83
59
CHA10-311
82
113
87
63
CHA10-411-413
83
115
89
64
CHA10-461-463
130
173
126
94
CHA10-511-513
135
178
131
99
CHA108-651-653
I 147
196
143
107
NOTE— Corner weights of basic unit with elec-
tric heat.
OPTIONAL OAD346185 MINIMUM
FRESH MR DAMPER
/
12-12
9-743
itKrt445:c.
1
— 12 —
FRONT VIEW
AIR f FLOW
SIDE. VIEW
1
0\6
Unit Report For 5T Pkg HP
Project Kidder -Mathews -5T Commercial PHP
Prepared By:
03/13/2013
12:57PM
Unit Parameters
Unit Model:.____.___....__._ _._..50TCQA06A0A3-0A0A0
Unit Size -- _ ----------....__06 (6 Tons)
Volts -Phase -Hertz: .__—_ __.__.__....__—_---208-1-00
Heating Type: ------_-----..._......_..__.._Heat Pump
Duct Cfg:__..._Horlzontal Supply /Horizontal Return
Standard One -Stage Cooling Refrigeration Coil
Lines and Filters
Condensate Drain Line Size. __._.-_314
Retum Air,Filter Type: Throwaway
Retum Air Filter Quantity:._.___..._..._..........__._._..._...__._4
Retum Air Filter Size:_._.—.__._._.__..._.__..._.._ 16 x 16 x 2
Unit Configuration
Electric Drive X13
Al/Cu - AI/Cu
Base Electromechanical Controls
Standard Packaging
Warranty Information
1 -Year parts (STD.)
5 -Year Compressor (std.)
No optional warranties were selected.
Dimensions (ft In.) & Weight (Ib.)
Unit Length: . 6' 2.376"
Unit Width: 3' 10.76"
Unit Height__....----...---_---------....__._ 3' 5.375"
Total Operating Weight.__.____.__.___.. -_660
"' VVaights and Dimensions are approximate. VYeight does
not include unit packaging. Approximate dimensions are
provided primarily for shipping purposes. For exact
dimensions and weights, refer to appropriate product
data catalog.
NOTE: Please see Warranty Catalog 500-088 for explanation of policies and ordering methods.
Ordering Information
4
bi
Part Number
Description
Quantity
50TCQA06AOA3-0AOA0
Rooftop Unit
1
Base Unit
Electromechanical control, No intake or exhaust option
None
Accessories
CRECOMZR024A02
Horizontal EconoMi$er IV with solid-state controller '
1
Packaged Rooftop Builder 1.34
Page 2 of 8
Project: Kidder -Mathews -5T Commercial PHP
Prepared By:
Certified Drawing for 5T Pkg HP
03/13/2013
12:57PM
VD'Cd:
1 01+(3/310/15 A3C IN '8[x15 :(3/2151083
(3 1 I AR6 E6 N1LLI8ET14S.
2. S CC4101 OF 0841171
3. * DIRECT:ON 3r AIR riOB
F:LI33 ACCESS PANEL
(T000-LCSSl
UNIT
501E03/[/ 1617733 3/8
33 3/8
MI)
501(34.05
M1
18 5/6
.4121
147/0
73711
$OTC0A06
41 3/6 (1 7/8
110311 13711
571(0301
(341 03(13/6 14 1/6
:317:
RACK
1 ---1
i.- 4-5/0
11101
0
081110 '.3. 101 4141
1EC63C7.00113 31117171. 41
CURIES 3337
11008 • 1 :1 -11 Pan ITT M Ulu LQVNr
17011,13.4 6311131 :06317.
ar Ulb O. 811311614;1 a 41,1*
>Dli D1K:f1r)u.l 81st. 161 U
33 338
18411
0[023812)4 3/003 1
10PT10NAL)
16
(4311
I
.. j` 23.3/3
16521 I 10.1/8
RUM 8)8 ` 1873) RITURI
4.3
41
11131)
1011
OPTIONAL
3401348
INSTALLED
006YEN1'NCE
CUTLET
13.115
11111
14-0/0 13-711 11
1450) I 363) If)2)12I
1
SEC T4RU TNS
BASE CHART
E AL1.1-
COADENSATE
PAIN OPIUM 31-3)4
7.N 3ASEPA8 1151)
SOPPIT
A3i
LL_
AL -
6.114
1151
usrelcrt
OISCOInal
LOCATION
(9.I/2
14641
411,51))1
.'
=FT
75
70 381
32 1/4
18151
TOP
(
89-3/B
11111 y
26.1/2
13 31
f 3- /8
1857
72.118 -2
73113
- 18-1/2 --)
14701
00)11681
f4C"011
(ASIALLC3
DISCONNECT
INDOOR 81.04:8
ACCC50
14.3/6
::6611
FRONT
38/013
3/11
CONNECTION 51/ES
A 11 3/0. 1331 DIA Fitt) 70368 SUPPLE ROLE
B 12. 1511 0(4 706[8 SUPPLY 040((001
C 11 3/4. 1441 DIA DA05E ACCESS P7U3
D 1718. 1281 DIA FI1L0 CONTROL 47(146 833E
[ 13/4•-l4 I.P1 [0/3(x5171 OAA74
0 12 1/2' 1641 01A P0068 SOHIT 3/80[1.001
'HAU-INE-BASF CHARI
TRESS NOLIS 3/1[11(03 003/ USE
CIBTHP18001401
788(3312
CONDUIT 0051
03)
RE0'D 601.E
SITES IIUC.)
3/2'
ACC.
118. 178.81
7/2'
(4/
138. 182.0)
3/4. 11013
Pone
1 1/6. 124.41
[08 •T1I11-T30.8151 3/1• [ACTOR) OPTION.
0(1111165 TO 04LE 1 S I ARE
PROVIDED
3(1[01 TITN1:)4"3R14)23•3110
R ). 3R 1)3•
3/01 001Ei- 010130)70 08 814E 312[
(
31 1/4
SU%LN 11011
AIR RETURN
RIG41 . AIR
BAS38EI11C
821:E4
FL08
•
lou UR
1 Cr 2 03-10-09
17111(1171
01.23-39
50TCO 04-07 5:NGLE ZONE ELECTRIC
4[.47 Pi -P
481x501531
If
5.0
„Packaged Rooftop Builder 1.34
11J
Page 3 of 8
(NO ‘41? -23-1
Project: Kidder -Mathews -5T Commercial PHP
Prepared By:
Certified Drawing for 5T Pkg HP
03/13/2013
12:57PM
0S ry
0'0. 6451
1(IG11
COAEA 1 60 1E0 1 COCAEA GORIER 1
1423117 (41 .11,.1010 1011 *6IGNi 161 .5Ei651 (01 C
6•
'
KE 166'
155.
A0.
65S.
CO. 1105.
16. LOS. 6.
605.
(G.
R
1
6
2
50160401
535
221
131
42 1 130
51 111 SS i '.23 151
134
1/4
1421;'22
1/2
15121
11 S/6
14111
50166800
$15
211
132
13 : 111
51
j 111
SI 1174.
50 30
1/4
14251122
'/5
(5621
11 1/2
141111
SOIC0464
510
210
151
72
1141
5/11
3/0
13151
20 I/8
111
30160/07
130
201
161
13 1141
15
10
1 141 1
4I 131
1/4
7111/33
122
1/5
12121
21 3/4
120
1271
CORNER A
441162 r 1. Ice 5S15
776660.00:(5 64312). n
C4111E4 tan
lM,�II N�j iilfi / trtii i CO IR;d11M1,1t1
CovoII:,I, sunt.:0121, pun glgd41114
wo!'t7'Dyijli!t°iui'ilr!Ftt l
50 10.66 Of 101746).
CORNER 8
CORNER C
!IMF
i
FRONT
. 0 O
a¢] 4a
2 or 2 1 03-10-09
A6)110n6
01-23-39
50%0 04-07 SINGLE ZONE ELECTRIC ,
HEAT PUMP I 48T51501501 1570!
Packaged Rooftop Builder 1.34
Page 4 of 8
.CDL 6 E .,1I
SPS( o '
A..55' beAp cu. „n es •2 ! 041
170 CC IA_
=
6/c) -t.
'7 = 3400'1
ikto I (4 LAA z-1
iloRp
r -g
3074
/OCo.r� �/S"D jJC�
l►ic_t-u-c.e -
0.4 (z,S) (o5 t-4-( lace
Se C3 NwZ — Ca / = 3 0 (
per.
--QC_3401 K:0
Wo ce r -e fico t -C) n.(;
(-74. ,4 4 -4-)/44'
(44) 14; (.440 c.
Vi\ -/C
Moore
Engineering
Group
PROJECT:
rV
ENGR:
DATE: 3/1S/11
SCALE:
SHEET
IPERMIT COORD COP
PLAN REVIEW/ROUTING SLIP
ACTIVITY NUMBER: M13-058 DATE: 03/20/13
PROJECT NAME: ORKIN
SITE ADDRESS: 925 INDUSTRY DR
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # after Permit Issued
DEPARTMENTS:
tor/04 -b1� ' (77 Ar * —--2-11-1
e-
Building Division " Fire Prevention IIII
Public Works
Structural
Planning Division
❑ Permit Coordinator ❑
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Incomplete ❑
DUE DATE: 03/21/13
Not Applicable ❑
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
TUES/THURS ROUTING:
Please Route Structural Review Required ❑ No further Review Required ❑
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
DUE DATE: 04/18/13
Approved ❑ Approved with Conditions g Not Approved (attach comments) ❑
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
Contractors or Tradespeople'nter Friendly Page
General/Specialty Contractor
A business registered as a construction contractor with L&I to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name COMFORT MECHANICAL UBI No. 601954041
INC
Phone 4252519840 Status Active
Address 3202 C St Ne License No. COMFOMI015LA
Suite/Apt. License Type Construction Contractor
City Auburn Effective Date 6/1/1999
State WA Expiration 4/25/2014
Date
Zip 98002 Suspend Date
County King Specialty 1 Heating/Vent/Air-Conditioning And Refrig
(Hvac/R)
Business Type Corporation Specialty 2 Unused
Parent
Company
Other Associated Licenses
License
Name
Type
Specialty 1
Specialty 2
Effective
Date
Expiration
Date
Status
FIVESM'010JT
FIVE STAR
MECHANICAL
Construction
Contractor
General
Unused
4/30/1999
5/1/2014
Active
COMFOP'064D2
COMFORT
PLUS
Construction
Contractor
Air
Conditioning
Air
Heat,Ventilation,Evaporat
3/22/1994
3/21/2000
Archived
FIVESSE941KU
FIVE STAR
ENERGY
SOLUTIONS
Construction
Contractor
General
Unused
5/24/2006
5/24/2008
Expired
Business Owner Information
Name
Role
Effective Date
Expiration Date
JACKSON, SHIRLEY A
President
01/01/1980
Bond Amount
JACKSON, HERB J
Vice President
01/01/1980
9815017
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
3
Lexon Ins Co
9815017
06/01/2012
Until Cancelled
$6,000.0006/04/2012
04/24/2012
2
COLONIAL AM CAS &
SURETY OF MD
LPM4041162
06/01/2002
Until Cancelled
06/01/2012
$6,000.00
05/15/2002
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
8
Federated
Mutual Ins Co
9849307
06/01/2010
06/01/2013
$1,000,000.00
04/24/2012
7
FEDERATED
MUTUAL INS CO
9849306
06/01/2006
06/01/2010
$1,000,000.00
05/01/2009
Summons/Complaint Information No unsatisfied complaints on file within prior 6 year period
Warrant Information No unsatisfied warrants on file within prior 6 year period
Infractions/Citations Information No records found for the previous 6 year period
httns://fortress. wa. eov/lni/bbin/Print. asnx
04/11/2013
PAK(.LL UA I A
Parcel
252304-9034
Name
Site Address
Geo Area
Spec Area
CWWA TUKWILA 1 LLC
825 INDUSTRY DR 98188
70-30
520-30 - m
Property Name.
Leal Description
Tukwila Commerce Center (Bldgs 19,
21,23,25,27,29,31)
Jurisdiction
Levy Code
Property Type
Plat Block / Building Number
Plat Lot / Unit Number
Quarter -Section -Township -Range
4
TUKWILA
2340
C
SW -25-23-4
BEG AT E 1/4 COR OF SEC 26-23-4 TH N 88-06-42 W 105.84 FT TH S 01-47-28. W 90.6p FT TO TPOB TH FR
TPOB S 88-12-32 E 233 FT TAP ON C/L OF A PRIVATE DRIVE TH ALG SD C/L S 01-47-28 W 577.17 FT TAP
OF CURVE TH TANGENT TO PRECEDING COURSE ALG ARC OF CURVE TO LFT 77.78 FT RAD 250 FT &
C/A 17-49-33 TAP OF REV CURVE TH FR A TANGENT WH BEARS S 16-02-05 E ALG / RC OF CURVE TO
RGT 77.78 FT RAD 250 FT & C/A 17-49-33 TAP OF TANGENCY TH TANGENT TO PRECEDING CURVE S 01-
47-28 W 430 FT TAP ON NLY MGN OF MINKLER BLVD TH LEAVING SD C/L ALG SD MGN N 88-12-32 W 257
FT TH LEAVING SD MGN N 01-47-28 E 1160.23 FT TO TPOB LESS UP RR OPER R/W
PLat Block:
Plat Lot:
ASSESSOR DATA
2009 Washington State Energy Code Compliance Forms for Nonresidential and. Multifamily Residential
Mechanical Summary
MECH-SUM
2009 Washington State Energy Code Compliance Forms for Nonresidential and Multifamily Residential
Revised February 2011
Project Info
Brand
Project Address ORKIN
Date 3/19/2013
CFM
925 INDUSTRY DRIVE
For Building Dept. Use
SP
TUKWILA, WA 98188
SEER
Applicant Name: JOFFRE SECHIER
Strip Heat
Applicant Address: 3202 C ST NE, AUBURN, WA 98002
Location
Applicant Phone: 425-251-9840
Project Description
Briefly describe mechanical
system type and features.
❑ Includes Plans
REPLACE (1) 5 -TON ELECTRIC/ELECTRIC PACKAGED ROOFTOP UNIT
WITH NEW 5 -TON HEAT PUMP WITH ECONOMIZER.
Include documentation requiring compliance with commissioning requirements, Section 1416.
Compliance Option
0 Simple System 0 Complex System 0 Systems. Analysis
(See Decision Flowchart (over) for qualifications. Use separate MECH-SUM for simple & complex
Equipment Schedules
The following information is required to be incorporated with the mechanical equipment schedules on
the plans. For projects without plans, fill in the required information below.
Cooling E. uipment Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
Capacity2
Btu/h
OSA CFM
or Econo?
SEER
or EER
IPLV3
Econmizer
Option or
Exception
Heat
Recovery
Y/N
27-1
HP
CARRIER
50TCQA06 -
61130
ECONO
13';
N
Heating Equipment Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
Capacity2
Btu/h
OSA cfm
or Econo?
Input Btuh
Output Btuh
Efficiency4
Heat
Recovery
Y/N
27-1
HP
CARRIER
50TCflA06
58310
ECONO
7.7 HSPF
Fan Equipment
Schedule
Equip.
ID
Equip
Type
Brand Name'
Model No.'
CFM
SP'
HP/BHP
Flow Controls
Location of Service
'If available. 2 As tested according to Table 14-1A through 14-1G. 3 If required. 4 COP HSPF, Combustion Efficiency, or AFUE, as applicable.
5 Flow control types: variable air volume(VAV), constant volume (CV), or variable speed (VS). 6 Exception number from Section 1433.
925 Industry Dr
Tukwila, WA 98188-3413
14013 M.piw .t - PoUomrn 1¢013 I Edna
SEPARATE PERMIT
REQUIRED FOR:
1Mec ani:aal
Electrical
Plumbing
Gas Piping
City of Tukwila
BUILDING DIVISION
REVIEWED FOR
CODE COMPLIANCE.
APPROVED
APR 09 2013
City of u iIa
BUILDING ISION
AI
PROJECT DESCRIPTION:
1. REPLACE (1) 5 -TON ELECTRIC/ELECTRIC PACKAGED
ROOFTOP UNIT WITH NEV! SAME CAPACITY HEAT PUMP
UNIT WITH ECONOMIZER.'
GENERAL NOTES:
1 E- 100%
TO PROVIDE OUTSIDE AIR WITH
PARTIAL COOLING AND MULTIPLE COOLING STAGES.
2. THERMOSTAT TO PROVIDE MINIMUM 5° DEADBAND.
3.7 -DAY PROGRAMMABLE THERMOSTAT WITH LOCKOUT.
e
4. INSTALL GFCI OUTLET WITHIN 25, OF UNIT.
5. INSTALL RETURN AIR DUC SMOKE DETECTOR FOR UNITS
WITH GREATER THAN 2,000 CFM
6. ROUTE CONDENSATE TO SPLASH BLOCK ON ROOF.
7. PROVIDE AIR BALANCE AND COMMISIONING REPORT.
8. PROVIDE O&M MANUALS WITH STAFF TRAINING.
9. VERIFY ALL DUCT DIMENSIONS PRIOR TO INSTALLATION.
10. ALL DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS.
11. INSULATE ALL DUCT PER WSEC TABLE 14-5.
12. SEAL ALL DUCT PER WSEC.
HVAC Equipment Schedule
Unit #
Brand
Model
Ton
CFM
OSA
Econo.
SP
Cap. Cool
SEER
Cap. Heat
Strip Heat
Weight
Location
HP -27-1
Carrier
50TCQA06
5.0
2000
120
0-100--
0.5
61,130
13.2
58,310
0
660
Roof
FILE C PY
Pit No. MI 1<
Plan review approval is wed to encs and omissions.
Mc
off construction documents does js�n�ott authorize
Mc Viiolation of any adopted code or ordinance. Receipt
of approved ld and =Mons is admowledged:
BY - -
Ti'4fuJ%
ADJACENT TENANT "NO WORK"
NEV 4x P.T. SLEEPERS
ROOF ACCESS BY EXT. LADDER
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan reviewfees
REV ISIONS
ti
z
MECHANICAL,
H
0
L�.
0
v
DATE:
SCALE:
DRAWN:
CHECKED:
RECEIVED
CITU OF TUKWILA
MAR 2 0 2013
PERMIT CENTER
00-000
1