MECHANICAL PERMIT
Parcel No.: 2616600035
Address: 4600 S 134 PL TUKW
Project Name: HOLADAY PARKS INC
Permit Number: M13-129
Issue Date: 07/29/2013
Permit Expires On: 01/25/2014
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Email:
Contractor:
Name:
Address:
HOLADAY-PARKS INC
4600 S 134TH PL , SEATTLE WA 98168
CONNIE HARDIN
4600 S 134 PL , TUKVVILA WA 98168
C ONNIEH@HOLDAYPARKS. C OM
Phone: 206 250-4530
HOLADAY PARKS, INC. Phone: 206 248-9700
PO BOX 69208 , SEATTLE, WA 98188
Contractor License No: HOLADPI379NO
Expiration Date: 09/03/2013
DESCRIPTION OF WORK:
INSTALL (1) NEW SPLIT SYSTEM IN DATA ROOM
Value of Mechanical: $5,000.00
Type of Fire Protection: UNKNOWN
Electrical Service Provided by:
Fees Collected: $249.00
International Mechanical Code Edition: 2012
Permit Center Authorized Signature: '/ , Date: O7/d' /73
!/ 7
I hereby certify that I have read and examined this permit and know the same to be true and correct. All provisions of law and ordinances
governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign and obtain this mechanical permit and agree to the conditions on the
back of this pe
Signature:
Print Name:
•
Date:
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
-. urn A1.1"
Printari• n7 -7Q -7n11
PERMIT CONDITIONS
Permit No. M13-129
1: ***BUILDING DEPARTMENT CONDITIONS***
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431-3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: Readily accessible access to roof mounted equipment is required.
6: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
7: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap the sanitary
sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks, wells, and other
excavations. Final inspection approval will be determined by the building inspector based on satisfactory completion of
this requirement.
8: Manufacturers installation instructions shall be available on the job site at the time of inspection.
9: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the City of Tukwila
Building Department (206-431-3670).
10: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206-431-3670).
11: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
doc: IMC -4/10
M13-129 Printed: 07-29-2013
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd.. Suite 100
Tukwila, 11'A 98188
http://www.TukwilaWA.gov
Mechanical Permit No.
Project No
Date Application -Accepted: V t
Date ApplicationExpires: oq
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
4' Apr. �xdtX'
Site Address: q 10 DO s () p,
Tenant Name: 1Q[' c (� PCIA"k c
PROPERI'1' OWNER
Name: 0,0•
Ah to Nctr-Ji
Address:) / 00 �. 1-,44A. P %�
�i
Name:
Sta
at (es
Phone: its to.zz 3DFax: zo(0.7 9 7 06
Address-, /pOO S 1t 3
I,
(�
j✓
City�l.) , nQ State
ZiiCal i C
(ONTACT.PERSON - person receiving all -project
communication
Name: 0,0•
Ah to Nctr-Ji
Address:) / 00 �. 1-,44A. P %�
�i
City: b , n"
e
Sta
at (es
Phone: its to.zz 3DFax: zo(0.7 9 7 06
Email: eibvtA 04_‘ 0 .tuLarituA Darks aosi
King Co Assessor's Tax No.:20 0 I 66,6003.5-
Suite Number: Floor:
New Tenant: ❑ Yes
E<o
MECHANICAL CONTRACTOR INFORMATION
Company Name:
I I ♦ I I pa,,,,,ta.
_Address:t J�p 0oI3J.
"��
City: State: Zip: 21
Phone: 7,0/0 Log Fax:Z zagi.l1
G�/R� �J
Contr Reg No.:
�Q Exp DateliO : _a0
Tukwila Business License Nort ,C ,_Di ()Ds)
Valuation of project (contractor's bid p ice): $ 5l7DD t..�
Describe the scope of work in detail:
SAN' •
Use: Residential: New.........0 Replacement
Commercial: New ., Replacement
Fuel Type: Electric L' Gas
Other:
11:\Applications\Forms-Applications On Line \2011 Applications\Mechanical Permit Application Revised 8-9-I Ldocx
Revised: August 2011
Oh
Page I of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
-Qty
Furnace <100k btu
Furnace >100k btu
Floor furnace
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
hcatlrefrig/cooling
system
Air handling unit
1
<10,000 cfm
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system
Flood and duct
Incinerator – domestic
1
Incinerator–
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
Thermostat
Wood/gas stove
Emergency generator
Other mechanical
equipment
IS,
1
a
Boiler/Compressor
Qty
0-3 hp/I00,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/I,750,000 btu
Value of construction – in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review – applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDIN D AGENT:
Signature:
Print Name:
&Ave A•Lrti
Mailing Address: LttDQO S.
II: \Applications\Forms-Applications On Line\2011 ApplicationsUvtechanical Permit Application Revised 8-9-I (.does
Revised: August 2011
bh
Date:
1-1
at
Day Telephone: 0* Z JU "'L Sib
fit 4. 1CB
City State Zip
Page 2 of 2
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206-431-3665
Web site: http://www.TukwilaWA.ov
RECEIPT
Parcel No.: 2616600035 Permit Number: M13-129
Address: 4600 S 134 PL TUKW Status: APPROVED
Suite No: Applied Date: 07/11/2013
Applicant: HOLADAY PARKS INC Issue Date:
Receipt No.: R13-02233
Initials:
User ID:
LAW
1632
Payment Amount: $199.20
Payment Date: 07/29/2013 02:39 PM
Balance: $0.00
Payee: HOLADAY PARKS
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 05583G
ACCOUNT ITEM LIST:
Description
199.20
Account Code Current Pmts
MECHANICAL - NONRES
000.322.102.00.00 199.20
Total: $199.20
rinr• Raraint-11R
Printed: 07-29-2013
• f
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206-431-3665
Web site: http://www.TukwilaWA.00v
Parcel No.: 2616600035
Address: 4600 S 134 PL TUKW
Suite No:
Applicant: HOLADAY PARKS INC
RECEIPT
Permit Number: M13-129
Status: PENDING
Applied Date: 07/11/2013
Issue Date:
Receipt No.: R13-02115
Initials: JEM
User ID: 1165
Payment Amount: $49.80
Payment Date: 07/11/2013 03:14 PM
Balance: $199.20
Payee: CONNIE HARDIN, HOLADAY PARKS FAB INC
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 00603G
ACCOUNT ITEM LIST:
Description
49.80
Account Code Current Pmts
PLAN CHECK - NONRES
000.345.830 49.80
Total: $49.80
,•Inn• Rorcin4_nR
Printed: 07-11-2013
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd:, #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
011 3-ia9
Project:
KOLA �� LI t34RKS
Typ of Inspection:
I.v-=nIC,,-EATrON I(Sl
Address:
'- 6700 S 13 q -pi-
Date Called:
Special Instructions:
Date Wanted:7e5 i
C�
a.m:"
p.m.
Requester:
Phone No:
1360 -SDI-,130 Z,
KApproved per applicable codes.
ElCorrections required prior to approval.
COMMENTS:
-/11 y.:
/29
Date: 0
n REINSPECTION FEE REQUIRED. Prior to next inspection: fee must be
paid at 6300 Southcenter Blvd., Suite.100. Call to schedule reinspection.
• PERMIT COORD COPYf
PLAN REVIEW/ROUTING SLIP
ACTIVITY NUMBER: M13-129 DATE: 07/11/13
PROJECT NAME: HOLADAY PARKS
SITE ADDRESS: 4600 S 134 PL
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # after Permit Issued
DEPARTMENTS:
9� teltio Cd -148-1>
Building Division II
Public Works
Aw\k1
Fire Prevention
Structural
7-kgv("5
Planning Division
❑ Permit Coordinator ❑
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete 71
Comments:
Incomplete
DUE DATE: 07/16/13
Not Applicable ❑
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg 0 Fire 0 Ping ❑ PW 0 Staff Initials:
TUES/THURS ROUTING:
Please Route t43 Structural Review Required ❑ No further Review Required ❑
REVIEWER'S INITIALS:
DATE:
APPROVALS OR CORRECTIONS:
Approved ❑
Notation:
Approved with Conditions
DUE DATE: 08/13/13
Not Approved (attach comments) n
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
Contractors or Tradespeople Peer Friendly Page
•
General/Specialty Contractor
A business registered as a construction contractor with L&I to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name HOLADAY PARKS INC UBI No. 578004089
Phone 2062489700 Status Active
Address 4600 5 134Th Pl License No. HOLADPI379NO
Suite/Apt. License Type Construction Contractor
City Seattle Effective Date 1/21/1983
State WA Expiration Date 9/3/2013
Zip 98168 Suspend Date
County King Specialty 1 General
Business Type Corporation Specialty 2 Unused
Parent Company
Other Associated Licenses
License
Name
Type
Specialty 1
Specialty
2
Effective
Date
Expiration
Date
Status
HOLADI.00105
HOLADAY PARKS
INC
Electrical
Contractor
Hvac/Rfrg Ltd
Energy
Unused
9/25/2000
4/29/2015
Active
HOLADPF376NO
HOLADAY PARKS
FABRCTRS INC
Construction
Contractor
General
Unused
8/20/1963
1/1/1983
Archived
Business Owner Information
Name
Role
Effective Date
Expiration Date
PARKS, GERALD T JR
Chief Executive Officer
01/21/1983
Amount
VAN DER VEEN, JULIE ELIZABETH
Member
08/26/2011
A1CG96431203
CONNELL, DANIEL AARON
Member
08/26/2011
GIRT, BUIT
Member
08/26/2011
Old Republic
Ins Co
KIEL, RINALD HOWARD
Member
08/26/2011
WHITMYRE, CHRISTIAN
Member
08/26/2011
24
BECK, DAVID CLARENCE
Vice President
01/21/1983
11/01/2012
OCONNOR, BONNY K
Vice President
01/21/1983
10/28/2011
NAILON, JUNE ANNETTE
Vice President
01/21/1983
VAN DER VEEN, ERIC M
Vice President
11/04/2010
PIZZEY, GRACE KATHERINE
Vice President
08/26/2011
NELSON, MICHAEL
Secretary
01/01/1980
11/04/2010
PARKS, DAVID L
Treasurer
01/01/1980
11/04/2010
TALBOT, PAUL
Treasurer
01/01/1980
11/04/2010
Bond Information
Page 1 of 2
Bond
7
Bond Company Name
LIBERTY MUTUAL INS
CO
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
23000452
09/01/2002
Until Cancelled
$12,000.00
08/23/2002
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
26
Old Republic
Ins Co
A1CG96431203
11/01/2012
11/01/2013
$1,000,000.00
10/30/2012
25
Old Republic
Ins Co
A1CG96431102
11/01/2011
11/01/2012
$1,000,000.00
10/28/2011
24
Old Republic
Ins Co
A1CG96431102
11/01/2011
11/01/2012
$1,000,000.00
10/28/2011
httns://fortress.wa. srov/lni/bbip/Print.aspx
07/29/2013
HVAC LEGEND
rr
r
/10
OD/
XXXX
12"x12"/SL
12"x12" SM
12x12
1
12"x12" SM/W
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
DUCT UNDER POSITIVE PRESSURE
DUCT UNDER NEGATIVE PRESSURE
TURNING VANES
ELEVATION FROM F.F.L
EQUIPMENT IDENTIFICATION
THERMOSTAT
SENSOR
CEIUNG OR INUNE EXHAUST FAN
24" x 12" RETURN AIR GRILLE W/SOUNDUNED CAN
SUPPLY AIR ARROW
RETURN AIR ARROW
SPEED SWITCH: FURNISHED BY HOLADAY-PARKS,
INSTALLED BY ELECTR. CONTR.
FLEXIBLE CONNECTION
DUCT HEATER
MANUAL VOLUME DAMPER
MOTORIZED DAMPER
BACK DRAFT DAMPER
SMOKE DETECTOR
VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
SMOKE DAMPER
COMBINATION SMOKE AND FIRE DAMPER
SPIN -IN TAKE -OFF & VOLUME DAMPER
REVIEWED. FOR.
CODE COMPLIANCE,
APPROVED
JUL 94 2013
City of Tukwila
BUILDING DIVISION!
INDICATES 14" x 14" O.D. SHEETMETAL WITH
1" SOUNDUNER (U.N.O.), 12" x 12" NET I.D.
INDICATES UNUNED 12" x 12" S.M. DUCT
INDICATES 12" x 12" I.D. DUCTBOARD
INDICATES UNLINED 12" x 12" S.M. DUCT
WITH INSULATED WRAP
RISE OR DROP IN DIRECTION OF FLOW
FLEXIBLE DUCT
INDICATES FLAT OVAL DUCT
SPIN -IN TAKE -OFF & VOLUME DAMPER WITH
RIGID ROUND FIBERGLASS DUCT
SHEET INDEX
,,,'?TE PERMIT
'°IRED FOR:
❑ Mechanical
CIectrical
(plumbing
Cas Piping
City of Tukwila
El.rl1_01NG DIVISION
REV # SHEET #
* 8 M0.01
5 M0.02
M1.01
5 M2.01
* 8 M2.02
* 8 M2.03
6 M6.01
* 8 M7.01
SHEET TITS
LEGENDS AND NOTES
LEGENDS AND SEQUENCE OF OPERATION
SITE PLAN
FIRST FLOOR HVAC PLAN
SECOND FLOOR HVAC PLAN
ROOF HVAC PLAN _
DETAILS
SCHEDULES
* INDICATES SHEETS INCLUDED IN THIS ISSUE
1. INSTALL 1.5 TON SPUT SYSTEM FOR IDF ROOM COOLING.
nntt NO. till k 415.a.
GENERAL NOTES
1. ALL TRADES TO LEAVE 36" CLEARANCE IN FRONT OF MECHANICAL EQUIPMENT
ACCESS PANELS FOR SERVICING.
2. CUTTING, FRAMING, PATCHING AND PAINTING OF WALL, CEILING AND FLOOR
OPENINGS SHALL BE BY GENERAL CONTRACTOR. THIS INCLUDES OPENINGS THROUGH
AREA SEPARATION WALLS.
3. ROOF CURBS, FLASHINGS, SLEEPERS, PITCH POCKETS, AND CUTTING AND PATCHING
OF ROOF OPENINGS SHALL BE BY GENERAL CONTRACTOR,
4. ROOF CURBS, SLEEPERS, AND CANT STRIPS TO BE BUILT AND FASTENED TO THE
ROOF BY GENERAL CONTRACTOR. CURBS TO BE CONSTRUCTED ACCORDING TO SIZES
PROVIDED BY HOLADAY-PARKS' FIELD MECHANIC. SHIM AS REQUIRED TO MAKE ROOF
CURBS AND SLEEPERS LEVEL TOP OF CURB MUST BE TRUE (FLAT) TO PROVIDE AN
ACCEPTABLE SEALING SURFACE. MAXIMUM ALLOWABLE DEVIATION FROM LEVEL OR
FLAT SHALL BE 1/4" IN 10'. ROOF CURBS AND SLEEPERS MUST BE SECURELY
FASTENED TO STRUCTURAL SUPPORT MEMBERS.
5. ROOFTOP HEAT PUMP NO. HP -1 ARE FURNISHED WITH FACTORY CURB REQUIRING
INSULATION AND CANT STRIP BY GENERAL CONTRACTOR. CURB SHALL BE ASSEMBLED
AND SET IN PLACE BY MECHANICAL CONTRACTOR. LEVEUNG, TRUING, AND FASTENING
OF CURBS TO ROOF STRUCTURE SHALL BE BY GENERAL CONTRACTOR. TOP OF CURB
MUST BE TRUE (FLAT) TO PROVIDE AN ACCEPTABLE SEALING SURFACE. MAXIMUM
ALLOWABLE DEVIATION FROM LEVEL OR FLAT SHALL BE 1/4" IN 10'. ROOF CURB
MUST BE SECURELY FASTENED TO STRUCTURAL SUPPORT MEMBERS.
6. FINAL PAINTING OF GRILLES, REGISTERS, AND DIFFUSERS, AS MAY BE REQUIRED BY
ARCHITECT, SHALL BE DONE BY GENERAL CONTRACTOR
7. GENERAL CONTRACTOR IS RESPONSIBLE FOR TEMPORARY HEAT DURING
CONSTRUCTION.
8. UNIT WEIGHTS AND LOCATIONS HAVE BEEN COORDINATED WITH ARCHITECT AND
STRUCTURAL ENGINEER TO DETERMINE BUILDING STRUCTURAL ADEQUACY. IF IT IS
NECESSARY TO RELOCATE A UNIT, NOTIFY HOLADAY-PARKS' ENGINEERING
DEPARTMENT FOR RE -COORDINATION.
9. BEAM PENETRATIONS ARE REQUIRED FOR DUCTWORK CLEARANCE AND FUTURE
TENANT IMPROVEMENT. GENERAL CONTRACTOR IS TO PROVIDE ALL BEAM
PENETRATIONS PER HOLADAY-PARKS' DRAWINGS AND FIELD MARKINGS AS APPROVED
BY THE STRUCTURAL ENGINEER.
10. IN NO INSTANCE SHALL OTHER TRADES HANG OR SUPPORT EQUIPMENT, CEIUNG
WIRES, LIGHT FIXTURE HANGERS, ETC., FROM HVAC EQUIPMENT OR DUCTWORK.
PROJECT COMPLETION NOTES
1. DRAWINGS:
A. UPON PROJECT COMPLETION INSTALLERS SHALL PROVIDE ACCURATE AS -BUILT
REDLINES TO H -P ENGINEERING DEPARTMENT FOR INCORPORATION INTO ELECTRONIC
FILES. REDUNE DRAWINGS WILL INCLUDE:
1. ALL DIFFUSERS SHOWN IN FINAL EXACT LOCATIONS.
2. ALL VAV BOXES AND SMALL FANS SHOWN WITHIN 12" OF ACTUAL LOCATIONS
3. ALL LARGE EQUIPMENT SHOWN IN EXACT LOCATIONS
4. ALL DUCTWORK SHOWN WITHIN 12" TO 18" OF ACTUAL LOCATIONS
5. ALL PIPING SHOWN WITHIN 12" OF ACTUAL LOCATIONS
6. ALL DIMENSIONS SHOWN ON ENGINEERED DRAWINGS TO BE REVISED TO ACTUAL
7. ALL ELEVATIONS AFF SHOWN ON ENGINEERED DRAWINGS TO BE REVISED TO ACTUAL
8. ALL HVAC AND PIPING DETAILS REVISED PER ACTUAL INSTALLATION
AS - BUILTS SHALL BE RETURNED TO ENGINEERING WITHIN 5 DAYS OF SCHEDULED
COMPLETION DATE.
RECORD DRAWINGS OF THE ACTUAL INSTALLATION WILL BE PROVIDED TO THE BUILDING
OWNER BY THE AGREED UPON SCHEDULE DATES.
2. MANUALS:
A. OPERATION AND MAINTENANCE MANUAL SHALL BE PROVIDED TO THE BUILDING
OWNER BY THE AGREED UPON SCHEDULE DATES.
THE MANUAL SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING:
1. SUBMITTAL DATA STATING EQUIPMENT SIZE AND SELECTED OPTIONS FOR EACH
PIECE OF EQUIPMENT REQUIRING MAINTENANCE.
2. OPERATION AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT
REQUIRING MAINTENANCE, EXCEPT EQUIPMENT NOT FURNISHED AS PART OF THE
PROJECT. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED.
3. NAMES AND ADDRESSES OF AT LEAST ONE SERVICE AGENCY.
4. HVAC CONTROLS SYSTEM MAINTENANCE AND CALIBRATION INFORMATION,
INCLUDING WIRING DIAGRAMS, SCHEMATICS, AND CONTROL SEQUENCE DESCRIPTIONS.
DESIRED OR FIELD DETERMINED SET POINTS SHALL BE PERMANENTLY RECORDED ON
CONTROL DRAWINGS AT CONTROL DEVICES, OR, FOR DIGITAL CONTROL SYSTEMS, IN
PROGRAMMING COMMENTS.
5. A COMPLETE NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE
INCLUDING SUGGESTED SET POINTS. (SEQUENCE OF OPERATIONS)
3. SYSTEM BALANCING:
A. GENERAL: HVAC SYSTEMS SHALL BE BALANCED IN ACCORDANCE WITH GENERALLY
ACCEPTED ENGINEERING STANDARDS. AIR AND WATER FLOW RATES SHALL BE MEASURED
AND ADJUSTED TO DELIVER FINAL FLOW RATES WITHIN 10% OF DESIGN RATES. A
WRITTEN BALANCE REPORT SHALL BE PROVIDED TO THE OWNER BY THE AGREED UPON
SCHEDULE DATES.
B. AIR SYSTEM BALANCING: AIR SYSTEMS SHALL BE BALANCED IN A MANNER TO
FIRST MINIMIZE THROTTLING LOSSES THEN, FOR FANS WITH SYSTEM POWER OF GREATER
THAN 1 HP, FAN SPEED SHALL BE ADJUSTED TO MEET DESIGN FLOW CONDITIONS.
ADDITIONAL REQUIREMENTS INCLUDE:
4. SYSTEMS COMMISSIONING
A. SIMPLE SYSTEMS: FOR SIMPLE SYSTEMS, AS DEFINED IN SECTION 1421, AND FOR
WAREHOUSES AND SEMIHEATED SPACES, HVAC CONTROL SYSTEMS SHALL BE TESTED TO
ENSURE THAT CONTROL DEVICES, COMPONENTS, EQUIPMENT AND SYSTEMS ARE
CALIBRATED, ADJUSTED AND OPERATE IN ACCORD WITH APPROVED PLANS AND
SPECIFICATIONS. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO
ENSURE THEY OPERATE IN ACCORD WITH APPROVED PLANS AND SPECIFICATIONS. A
COMPLETE REPORT OF TEST PROCEDURES AND RESULTS SHALL BE PREPARED AND FILED
WITH THE OWNER BY THE AGREED UPON SCHEDULE DATES.
B. OTHER SYSTEMS: ALL OTHER HVAC CONTROL SYSTEMS, AND OTHER
AUTOMATICALLY CONTROLLED SYSTEMS FOR WHICH ENERGY CONSUMPTION,
PERFORMANCE, OR MODE OF OPERATION ARE REGULATED BY THIS CODE, SHALL BE
TESTED TO ENSURE THAT CONTROL DEVICES, EQUIPMENT AND SYSTEMS ARE
CALIBRATED, ADJUSTED AND OPERATE IN ACCORD WITH APPROVED PLANS AND
SPECIFICATIONS. SEQUENCES OF OPERATION SHALL BE FUNCTIONALLY TESTED TO
ENSURE THEY OPERATE IN ACCORD WITH APPROVED PLANS AND SPECIFICATIONS.
C. DOCUMENTATION: THE WITNESS TEST CHECKLIST SHALL IDENTIFY THE
FOLLOWING FOR EACH TEST:
1. EQUIPMENT AND SYSTEMS TO BE TESTED, INCLUDING THE EXTENT OF
SAMPLING TESTS,
2. FUNCTIONS TO BE TESTED (FOR EXAMPLE CALIBRATION, ECONOMIZER
CONTROL, ETC.),
3. CONDITIONS UNDER WHICH THE TEST SHALL BE PERFORMED (FOR
EXAMPLE WINTER DESIGN CONDITIONS, FULL OUTSIDE AIR, ETC.),
4. MEASURABLE CRITERIA FOR ACCEPTABLE PERFORMANCE.
5. COMMISSIONING REPORTS
A. PREUMINARY COMMISSIONING REPORT: A PREUMINARY COMMISSIONING REPORT
OF TEST PROCEDURES AND RESULTS SHALL BE PREPARED. THE PRELIMINARY REPORT
SHALL IDENTIFY:
1. DEFICIENCIES FOUND DURING TESTING REQUIRED BY THIS SECTION WHICH HAVE
NOT BEEN CORRECTED AT THE TIME OF REPORT PREPARATION AND THE ANTICIPATED
DATE OF CORRECTION.
2. DEFERRED TESTS WHICH CANNOT BE PERFORMED AT THE TIME OF REPORT
PREPARATION DUE TO CUMATIC CONDITIONS.
3. CLIMATIC CONDITIONS REQUIRED FOR PERFORMANCE OF THE DEFERRED TESTS,
AND THE ANTICIPATED DATE OF EACH DEFERRED TEST.
B. FINAL COMMISSIONING REPORT: A COMPLETE REPORT OF TEST PROCEDURES AND
RESULTS SHALL BE PREPARED AND FILED WITH THE OWNER BY THE AGREED UPON
SCHEDULE DATES.
SHEET METAL NOTES
1. DUCT SIZES INDICATED ON PLANS ARE NET INSIDE DIMENSIONS. A CALL -OUT SUCH
AS 12" X 12"/SL MEANS A 14" X 14" SHEET METAL DUCT WITH 1"
SOUNDUNER, GIVING A NET INSIDE DIMENSION OF 12" X 12".
2. DUCTWORK SHALL BE CONSTRUCTED TO DIMENSIONS INDICATED ON PLANS. THE
TOLERANCE OF THESE DIMENSIONS SHALL BE AS SPECIFIED IN HOLADAY-PARKS, INC.
SHOP STANDARDS MANUAL LENGTHS, AND CRITICAL DIMENSIONS BETWEEN DUCTWORK
AND OTHER BUILDING/SYSTEM ELEMENTS ARE INDICATED WHERE A LOCATION OR
DIMENSION SCALED FROM THE DRAWING WILL NOT BE ADEQUATE. THE TOLERANCE OF
CRITICAL DIMENSIONS, IF NOT INDICATED, SHALL DEFAULT TO THAT OF THE INSTAWNG
MECHANIC'S MEASURING DEVICES. SCALED LOCATIONS OR DIMENSIONS ARE NOT
SUBJECT TO TOLERANCE GUIDELINES.
3. THESE PLANS HAVE BEEN COORDINATED WITH THE ARCHITECTURAL, STRUCTURAL,
SPRINKLER AND ELECTRICAL DRAWINGS. ANY CHANGES IN THIS LAY -OUT MUST BE
REVIEWED BY HOLADAY-PARKS' ENGINEERING DEPARTMENT.
4. FINISHED CEIUNG HEIGHT IN OFFICE AREAS WILL BE ___8' 6" ABOVE
FINISHED FLOOR (AFF) TO BOTTOM OF CEILING.
5. ROOFTOP PACKAGED AIR CONDITIONING SYSTEMS' DUCT CONSTRUCTION SHALL
BE AS FOLLOWS:
a. VERTICAL DROPS FROM ROOFTOP A/C UNITS SHALL BE RECTANGULAR
GALVANIZED SHEET METAL WITH 1" SOUNDUNER. FABRICATE AND INSTALL PER
SMACNA 1/2* PRESSURE CLASSIFICATION.
b. SUPPLY AIR DISTRIBUTION DUCTWORK FROM VERTICAL DROPS TO DIFFUSER
RUNOUTS SHALL BE 1" THICK, U.L LISTED, CLASS 1 FIBERGLASS DUCTBOARD EXCEPT
WHERE LINED SHEET METAL IS INDICATED. FABRICATE AND INSTALL PER SMACNA 1/2"
PRESSURE CLASSIFICATION.
c. RUNOUTS TO DIFFUSERS SHALL BE LOW PRESSURE INSULATED FLEX DUCT (AND
RIGID ROUND DUCT WHERE INDICATED). USE UNINSULATED FURNACE PIPE FITTINGS
WHERE FITTINGS ARE INDICATED IN RIGID ROUND DUCT. FLEX DUCT SHALL BE LIMITED
TO 8 FEET AND TWO 45 DEGREE TURNS.
d. WHERE RETURN AIR IS DUCTED, RETURN AIR DUCTWORK SHALL BE THE SAME AS
FOR SUPPLY.
6. MATERIALS:
a. SOUNDUNER (INDOORS): 1" THICK, 1-1/2 LB. DENSITY FIBERGLASS DUCTUNER
WITH BLACK MAT FACING. SCHULLER-MANVILLE "PERMACOTE UNACOUSTIC
STANDARD", OR OWENS CORNING "AEROFLEX PLUS". (MINIMUM INSTALLED R -
VALUE = 3.3)
b. SOUNDUNER (OUTDOORS): 2" THICK, 1-1/2 LB. DENSITY FIBERGLASS
DUCTUNER WITH BLACK MAT FACING. SCHULLER-MANVILLE "PERMACOTE
UNACOUSTIC STANDARD", OR OWENS CORNING "AEROFLEX PLUS". (MINIMUM
INSTALLED R -VALUE = 7.0)
LOW PRESSURE INSULATED FLEX DUCT: THERMAFLEX MK -E.
d. DUCT INSULATION (INDOORS): 1-1/2* THICK, 3/4 LB. DENSITY FIBERGLASS WITH
F.S.K. VAPOR BARRIER JACKET. (MINIMUM INSTALLED R -VALUE = 3.
PROJECT COMPLETION REQUIREMENTS
HVAC ABBREVIATIONS
AFF
AP
BDD
BHP
BOD
BOU
BT
CB BDD
CLG
CONN.
DB
DMPR.
DN.
DR.
EA
EAT
EC.
ELEV.
ESP
EXH.
EXTR.
FC
FD
FFL
FLA
FIR DR.
FNL DR.
FOB
FOT
ABOVE FINISHED FLOOR
ACCESS PANEL
BACK DRAFT DAMPER
BRAKE HORSE POWER
BOTTOM OF DUCT
BOTTOM OF UNIT
BYPASS TIMER
COUNTER -BALANCED
BACK DRAFT DAMPER
CEIUNG
COMNCT/COMffCTION
DUCTBOARD
DAMPER
DOWN
DRAIN
EACH
ENTERING AIR TEMP
ELECTRICAL CONTRACTOR
ELEVATION
EXTERNAL STATIC PRESSURE
EXHAUST
EXTRACTOR
FLEX CONNECTION
FIRE DAMPER
FINISHED FLOOR LEVEL
FULL LOAD AMPS
FLOOR DRAIN
FUNNEL DRAIN
FLAT ON BOTTOM
FLAT ON TOP
FUT
G
GC
HP
ID
INSUL
LAT
MCA
N/A
NC
NIC
NO
NOM.
NTS
OA
OBD
OD
PRIM
PSI
R
RA
SA
SL
SM
SP
Tv's
TYP
VD
W/
/W.
FUTURE
GAS
GENERAL CONTRACTOR
HORSE POWER
INSIDE DIMENSION/DIAMETER
INSULATION
LEAVING AIR TEMP
MINIMUM CIRCUIT AMPACITY
NOT APPLICABLE
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOMINAL
NOT TO SCALE
OUTSIDE AIR
OPPOSED BLADE DAMPER
OUTSIDE DIMENSION
PRIMARY
POUNDS PER SQUARE INCH
RISE
RETURN AIR
SUPPLY AIR
SOUND UNING
SHEET METAL
STATIC PRESSURE
TURNING VANES
TYPICAL
VOLUME DAMPER
WITH
WITH WRAP (IE: DUCT INSULATION)
ELECTRICAL COORDINATION NOTES
ELECTRICAL COORDINATION
1. WHERE INDICATED ON EQUIPMENT SCHEDULES, THE EQUIPMENT COMES COMPLETE
FROM THE FACTORY WITH MOTOR CONTROLS AS REQUIRED. ELECTRICIAN SHALL
PROVIDE SERVICE AND A DISCONNECT PER CODE, AND DO ALL POWER WIRING,
INCLUDING CONNECTING TO EQUIPMENT.
2. WHERE INDICATED ON EQUIPMENT SCHEDULES, THE EQUIPMENT REQUIRES FIELD
INSTALLED MOTOR STARTERS. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL
MOTOR STARTERS (OR CONTACTORS WHERE INDICATED), PROVIDE SERVICE AND
DISCONNECT PER CODE, AND DO ALL POWER WIRING, INCLUDING CONNECTING TO
EQUIPMENT. HOLDING COIL CIRCUIT SHALL BE POWERED BY ELECTRICAL CONTRACTOR
(120 VOLT/1 PH. UNLESS INDICATED OTHERWISE). ALL STARTERS SHALL BE PROVIDED
WITH H -O -A SWITCH:
SEISMIC RESTRAINING NOTES
SEISMIC RESTRAINING NOTES
(U.B.C. SEISMIC ZONE 3, SMACNA SEISMIC HAZARD LEVEL B)
1. ANY EQUIPMENT MOUNTED RIGIDLY TO THE BUILDING STRUCTURE SHALL NOT
REQUIRE ADDITIONAL SEISMIC RESTRAINT.
2. RESTRAIN ALL RECTANGULAR DUCTS 6 SQ. FT. OF AREA AND LARGER AND ALL
ROUND DUCTS 28" IN DIAMETER AND LARGER. RESTRAINTS SHALL OCCUR 30 FEET O.C.
MAXIMUM AND SHALL BE INSTALLED AT EVERY DUCT TURN AND AT THE END OF THE
DUCT RUN. SIZE AND INSTALL RESTRAINTS PER SMACNA SEISMIC RESTRAINT MANUAL.
3. ALL CEIUNG MOUNTED DIFFUSERS SHALL HAVE WIRES (16 GA.) ATTACHED TO THE
ABOVE FLOOR SLAB OR STRUCTURE. SAFETY WIRES SHALL BE LEFT PARTIALLY SLACK.
ALTERNATE METHOD SHALL BE TO ATTACH DIFFUSERS TO T -BAR GRID WITH SCREWS,
RIVETS, OR CEIUNG CUPS FOR TERMINALS WEIGHING LESS THAN 20 POUNDS.
GRILLES, REGISTER, DIFFUSER LEGEND
NOTE:
NOTE:
X"xX" CD
CFM
X"xX" CD/FD
CFM
X"xX" CD/P
CFM
X"xX" CD/P/FD
CFM
X"xX" CD/PF
CRM
¥SLOT-INLETO
CFM
#SLOT-INLETO/FD
CFM
#SLOT-INLETO/P
CFM
#SLOT-IN.O/FD/P
CFM
S.S.R.
S.S.G.
LN.W.S.G.
R.A.G.
R.A.G./P.
S.R.G.
LN.W.R.G.
E.G.
E.G./P.
3
7
_S
I
EXHAUST
LOUVER
INTAKE
LOUVER
BDD
BDD
BDD
THE "/FD" CALLOUT INDICATES A GRILLE WITH U.L CLASSIFIED
RADIATION DAMPER TO BE INSTALLED IN RATED FLOOR/CEIUNG
OR ROOF/CEIUNG ASSEMBUES. USE RUSKIN MODEL CFD. INCLUDE
THERMAL INSULATION BLANKET FOR LAY -IN T -BAR CEILINGS.
ALL SUPPLY DIFFUSERS ARE TO BE INSTALLED WITH A DIFFUSER CAN
W/ PERF DIVIDER, GENSCO REGISTER BOX W/ FLEX COLLAR & DIFF,
MODEL COLDC21 OR EQUIV.
CEILING DIFFUSER (LAY -IN T -BAR CEILING)
4 CORE ADJUSTABLE, WITH FILLER FOR 24" x 24" LAY -IN MODULE
TITUS MODEL MCD, BORDER TYPE 3 - KRUEGER SERIES 1244, FRAME 23
(USE X"O RUNOUT)
CEIUNG DIFFUSER WITH FIRE DAMPER (LAY -IN T -BAR CEIUNG)
4 CORE ADJUSTABLE, ALL STEEL CONSTRUCTION, RADIATION
DAMPER SHALL BE RUSKIN MODEL CFD W/ THERMAL INSULATING
BLANKET (USE X"O RUNOUT)
CEIUNG DIFFUSER (PLASTER CEIUNG)
4 CORE ADJUSTABLE, "V" FRAME
TITUS MODEL MCD, BORDER TYPE 6 - KRUEGER SERIES 1244, FRAME 21
CEIUNG DIFFUSER (PLASTER CEIUNG) WITH FIRE DAMPER
SAME AS C.D./P WITH RADIATION DAMPER AS NOTED ABOVE
(USE X"O RUNOUT)
CEIUNG DIFFUSER WITH PERFORATED FACE (LAY -IN T -BAR CEIUNG)
4 CORE ADUSTABLE, WITH FILLER FOR 24" x 24" LAY -IN MODULE
kRUEGER SERIES 1244P, FRAME 23 (USE X" RUNOUT)
(USE X" RUNOUT)
SLOT DIFFUSER FOR LAY -IN CEIUNG
KEES-100
SLOT DIFFUSER FOR RATED LAY -IN CEIUNG WITH FIRE DAMPER
TEMPMASTER FRD
SLOT DIFFUSER (PLASTER CEIUNG)
KEES K-100, FRAME OPTION II
SLOT DIFFUSER WITH FIRE DAMPER (PLASTER CEIUNG)
TEMPMASTER MODEL TFD-F OR FRD-F FOR SURFACE MOUNTING
SIDEWALL SUPPLY REGISTER
DOUBLE DEFLECTION, HORIZONTAL FRONT BLADES, WITH O.B.D.
TITUS MODEL 272RL O.B.D. - KRUEGER MODEL 880H O.B.D.
SIDEWALL SUPPLY GRILLE
DOUBLE DEFLECTION, HORIZONTAL FRONT BLADES
TITUS MODEL 272RL - KRUEGER MODEL 880H
UNEAR WALL SUPPLY GRILLE
FIXED 15 DEGREE DEFLECTION BLADES
KRUEGER MODEL 1515, FRAME 415, ALUMINUM CONSTRUCTION
RETURN AIR GRILLE
ALUMINUM EGGCRATE WITH 1/2" x 1/2" x 1/2" CORE
TITUS MODEL 5OF - KRUEGER EG -5
RETURN AIR GRILLE (PLASTER CEIUNG)
FIXED 35 DEGREE DEFLECTION BLADES
KRUEGER MODEL S8OH
SIDEWALL RETURN GRILLE
FIXED 35 DEGREE DEFLECTION BLADES, WITHOUT O.B.D.
TITUS MODEL 350RL - KRUEGER MODEL S8OH
LINEAR WALL RETURN GRILLE
FIXED 0 DEGREE DEFLECTION BLADES
KRUEGER MODEL 1500, FRAME 415
ALUMINUM CONSTRUCTION
EXHAUST GRILLE
ALUNIMUM EGGCRATE WITH 1/2" x 1/2' x 1/2" CORE
TITUS MODEL 50F -KRUEGER EG -5
RETURN AIR GRILLE (PLASTER CEILING)
FIXED 35 DEGREE DEFLECTION BLADES
TITUS MODEL 350RL - KRUEGER MODEL S8OH
EXHAUST REGISTER
FIXED 35 DEGREE DEFLECTION BLADES
TITUS MODEL 350RL O.B.D. - KRUEGER MODEL S8OH O.B.D.
TRANSFER GRILLE
ALUNIMUM EGGCRATE WITH 1/2" x 1/2" x 1/2" CORE
TITUS MODEL 350RL - KRUEGER EG -5
TRANSFER GRILLE (PLASTER CEIUNG OR WALL)
FIXED 35 DEGREE DEFLECTION BLADES
TITUS MODEL 350RL - KRUEGER MODEL S8OH
4" STATIONARY LOUVER
STEEL CONSTRUCTION
RUSKIN MODEL ELF -375
4" STATIONARY LOUVER WITH DRAINABLE BLADES
GALVANIZED STEEL CONSTRUCTION
RUSKIN MODEL ELF -375D
FINISH: FACTORY APPLIED PRIME COAT
BACK DRAFT DAMPER
RUSKIN MODEL BD2/A1, LOCAL VELOCITY < 1500 FPM
RUSKIN MODEL BD2/A2, LOCAL VELOCITY < 2500 FPM
RUSKIN MODEL BD6, LOCAL VELOCITY < 3500 FPM
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
PI¢' r€mview approval is subject to errors and omisslbns.
..4 of construction documents does not authorize
pion 01 any adopted code or ordinance. Redelpt
Lp
pror►- �lanclwleced:
Date:
City Of 1'iukwtla
ma rrr r mi#
RECEIVED
CITY OF TUKWILA
JUL 112013
PERMIT CENTER
3-121
HOLADAY-PARKS, INC.
SMART Mechanical Solutions
Mechanical Solutions • Energy Services
Building Controls • Service & Maintenance
4600 S. 134TH PLACE
SEATTLE, WA 98168 • (206) 248-9700
HOLADAYPARKS.com
WA LICENSE NUMBER: HOLADPI379NO
PROJECT I
Cii W
0
'5
L.1. 0.
Q2 cep
0... F- T -
co
>1-11
M cm
r
Q
D
LLJ ��
J
V o�
0 U-- o�
1 0 (0 D
41- 1
DESIGN TEAM
Designed by: MJG
Drawn by: SLS
Approved by:
Job Number:
1286
Filename:
M001-4600. DWG
REGISTRATION
07/11/13
APPROVED
FOR CONSTRUCTION
ISSUE NAME/DATE
IDF ROOM PERMIT
PENDING CITY APPROVAL
07/11/13
I REVISIONS I
No. Date By Description
1 2/25/93 OFF. EXPANSION
2 4/21/96 AS -BUILT
3 7/30/99 SERVER ROOM COOLING
5 9/1/00 SERVER RM PERMIT/CONST.
6 5/05/06 REPRO RM COOLING PERMIT
7 7/15/08 REPLACE ROOFTOP UNITS
8 07/11/13 MJG IDF ROOM PERMIT
SHEET TITLE
LEGENDS &
NOTES
SHEET NUMBER
M0.01
ALL RIGHTS RESERVED. THESE DRAWINGS BELONG IN ANY FORM TO HOLADAY-PARKS, INO. NO PART OF THIS DOCUMENT MAY BE REPRODUCED IN ANY FORM OR BY ANY MEANS WITHOUT PERMISSION IN WRITING FROM HOLADAY PARKS, INC.
&x ®CD
75
215
270
8x8CD
1010_
Ox1O D
12"0
_24 4'
39x11/1 'SL RAG
D
8xE
DXFC-2
I it
lora
8x8CD
3/4" DOOR
U.C. BY G.C.
8x8CD
235
30x12
12x 2CD
(TYP.2)
24x2 "TG
2"0
D
3
D
3
-24-x6-E
(X1~2/1 "S
P -0,.-AC
►z�
8x8
2
x1/1'
UP TO_.,C
_8x8C
D
8x8CZ._..
10x1
2
_ 8x8
D
3
D
24x 4 --_—
RA
111 121A
sad
rime
III IIIIII
8CD
TYP.2)
3-12"0
325
4x12
AG
12)10' DN
ctIJNT'NC.i
1 l .",,....OAS
CO ELT
FIRLACE
16x10DB
6"EG
10xI10
325
190
SECOND FLOOR HVAC PLAN
SCALE 1/8' • 1-0'
80 ID
10-1/2" OD FACTORY CHIMNEY UP
3-12"0
265
typ. 3
M 13
REVIEWED FOR
ODE COMPLIANCE
APPROVED
'JUL 9 4 2013
City of Tukwila
BUILDING DIVISION
LZi
0 P.C. TO ROUTE 3/4' CONDENSATE DRAIN PIPE TO APPROVED
WASTE RECEPTACLE.
= EXISTING CONSTRUCTION
= NEW CONSTRUCTION
HOLADAY-PARKS, INC.
SMART Mechanical Solutions
Mechanical Solutions • Energy Services
Building Controls • Service & Maintenance
4600 S. 134TH PLACE
SEATTLE, WA 98168 • (206) 248-9700
HOLADAYPARKS.com
WA LICENSE NUMBER: HOLADPI379NO
PROJECT I
U
Z
� W co
a CO
' a �
Q
1-1-1 M
Qv �g
J �
OLL0o�
.1- 1 -
Designed by:
Drawn by:
DESIGN TEAM
MJG
PAT
Approved by:
Job Number:
1286
Filename:
M202-4600.DWG
07/11/13
APPROVED
FOR CONSTRUCTION
ISSUE NAME/DATE I
IDF ROOM PERMIT
PENDING CITY APPROVAL
07/11/13
REVISIONS
No. Date By Description
1 2/25/93 OFF. EXPANSION
2 4/21/93 AS -BUILT
3 7/30/99 SERVER ROOM COOLING
4 1/03/00 AC -4 REBALANCE
5 3/10/00 SERVER RM PERMIT/CONST.
6 5/05/06 REPRO RM COOLING PERMIT
8 07/11/13 MJG IDF ROOM PERMIT
RECEIVED
C -I -r ii Or T KWI w
JUL 1 1 2013
--PERMIT CENTER
SHEET TITLE
SECOND FLOOR
HVAC PLAN
M2.02
AU. RIGHTS RESERVED. THESE DRAWINGS BELONG IN ANY FORM TO HOLADAY-PARKS, INC.. NO PART OF THIS DOCUMENT MAY BE REPRODUCED IN ANY FORM OR BY ANY MEANS WITHOUT PERMISSION IN WRITING FROM HOLADAY PARKS, INC.
REF -2
10" 10"/1 "SL DN
1/2" SL & 1/4" LL PIPING DN
CU -2
1-1/2" DN
1 -1/2" ---_may
SLEEPERS SUPPORTS
21.5"x38" DN
13.5"x38" DN
27.12"X9.5" DN
27"X10.5" ON
3/4"
3/4"
10.5"X27" DN
3/4"
REF -1
16"X16"/1 "SL DN
3-8"x13.5
38"x21.5" DN
AC -9
AC -3
3/4"
34"X13.5" DN
20"X20.5" DN
3/4"
AC -7
3/4"
0 -- 38"x21.5" DN
6" TYPE 'B' VENT
TO 3' ABOVE ROOF
3/4"
1"
"x13.5" DN
9.5"X27.12" DN
AC -1
SLEEPERS BY
G.C.
CU -1
3/4"
CD
AC -6
27.12"X9.5" DN
ril
REF -3
10"X10"/1 "SL DN
Y" RL DN
7¢"GDN
IP
3/4"
3/4"
AC -4
27"X10.5" DN
27.12"X9.5" DN
6" TYPE 'B' VENT
TO 3' ABOVE ROOF
8"X8"/1"SL DN
REF -4
SLEEPERS, FASTEN
TO ROOF AND UNIT
CU -3
3/4"
7A
3/4"
9.5"X27.12" DN
10.5"X27" DN
AC -5
3/4"
4"X4"/1 "SL DN
ROOF HVAC PLAN
SCALE 1/8' -tom'
RC -1
■
1" GAS
DN
1/2" GAS
CONNECT. TO
FIREPLACE
PRESSURE REGULATOR
80ID
10-1/2" OD FACTORY CHIMNEY,.
TO 2" ABOVE
PARAPET WALL
I�I,I 3
12?
REVIEWED FOR
CODE COMPLIANCE
APPROVED
1JUL742013
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JUL 112013
PERMIT CENTER
0 FIELD TO VERIFY AND INSTALL ADAPTER CURBS FOR NEW
ROOFTOP UNITS.
= EXISTING CONSTRUCTION
= NEW CONSTRUCTION
HOLADAY-PARKS INC.
SMART Mechanical Solutions
Mechanical Solutions • Energy Services
Building Controls • Service & Maintenance
4600 S. 134TH PLACE
SEATTLE, WA 98168 • (206) 248-9700
HOLADAYPARKS.com
WA LICENSE NUMBER: HOLADPI379NO
•
I PROJECT I
Designed by:
Drawn by:
DESIGN TEAM
MJG
MLG
Approved by:
Job Number:
46032
Filename: M203-4600.DWG
REGISTRATION
07/11/13
APPROVED
FOR CONSTRUCTION
I ISSUE NAME/DATE I
IDF ROOM PERMIT
PENDING CITY APPROVAL
07/11/13
No. Date
1 2/25/93
2 4/21/93
3 7/30/99
5 3/10/00
6 5/05/06
7 7/15/08
8 7/11/13
REVINS
i
By Description
OFF. EXPANSION
AS -BUILT
SERVER ROOM COOLING
SERVER ROOM PERMIT/CONST.
REPRO RM COOLING PERMIT
REPLACE ROOFTOP UNITS
MJG IDF ROOM PERMIT
SHEET TITLE
ROOF
HVAC PLAN
SHEET NUMBER
M2.03
ALL RIGHTS RESERVED, THESE DRAWINGS BELONG IN ANY FORM TO HOLADAY-PARKS, INC., NO PART OF THIS DOCUMENT MAYBE REPRODUCED IN ANY FORM OR BY ANY MEANS WITHOUT PERMISSION IN WRITING FROM HOLADAY PARKS, INC,
ROOFTOP AIR CONDITIONING UNIT SCHEDULE
AC #
AREA SERVED
MAKE
MODEL
NOM.
TONS
PREV.
TONS
DOWNFLOW/
HORIZONTAL
ECONOMIZER
ENTERING AIR
CONDENSING
TEMP 'F
ARI EFFICIENCY
COOLING CAPACITY
OUTSIDE
AIR CFM
SUPPLY FAN DATA
GAS HEAT MBH
WINTER
ELECTRICAL
WEIGHT
(LBS)
PREV. WEIGHT
(LBS)
FILTERS
REMARKS
Y/N
DB
WB
SEER / EER
TOTAL
SENSIBLE
CFM
ESP
RPM
BHP
MHP
IN
OUT
DESIGN T
VOLTS/PH
MCA
QTY
SIZE
AHU-1
-
AAON
HB005-3V-AA01-251
5
5
DOWNFLOW
Y
80
67
-
13
61210
48370
600
2000
.55
1625
.77
.88
125
100
-
460/3
14
647
710
-
-
1,2
AHU-2
-
AAON
HB005-3V-AA01-221
5
5
DOWNFLOW
Y
80
67
-
13
61210
48370
600
2000
.55
1625
.78
.88
60
48
-
460/30
14
628
710
-
-
1,2
AHU-3
-
AAON
RM006-30-BA01-231
6
6.25
DOWNFLOW
Y
80
67
-
11.8
78130
60310
720
2400
.55
1690
.98
2
180
145.8
-
460/3
19
958
800
-
-
1,2
AHU-4
-
AAON
HB004-3V-AA01-251
4
4
DOWNFLOW
Y
80
67
-
13.3
51510
44750
600
2000
.55
1625
.77
.88
125
100
-
460/3
12
636
680
-
-
1,2
AHU-5
-
AAON
HB002-3V-AA01-211
2
2
DOWNFLOW
Y
80
67
-
13.5
28180
20860
600
800
.35
1000
.17
.25
45
36
-
208/1
8
568
310
-
-
1,2
AHU-6
-
AAON
HB003-3V-1101-211
3
3
DOWNFLOW
Y
80
67
-
13.2
35440
27910
600
1200
.35
1160
.28
.88
45
36
-
460/3
11
571
670
-
-
1,2
AHU-7
-
AAON
RM010-30-BA02-232
10
10
DOWNFLOW
Y
80
67
-
11.1
111610
74060
720
4000
.55
1121
.80
2
180
145.8
-
460/3
23
1365
1370
-
-
1,2
AHU-8
-
AAON
RM010-30-BA02-232
10
8.5
DOWNFLOW
Y
80
67
-
11.1
111610
74060
720
4000
.55
1121
.80
2
180
145.8
-
460/3
23
1365
1020
-
-
1,2
AHU-9
-
AAON
RM010-30-BA02-232
10
10
DOWNFLOW
Y
80
67
-
11.1
111610
74060
720
4000
.55
1121
.80
2
180
145.8
-
460/3
23
1365
1370
-
-
1,2
1: WIRING AND DISCONNECTS BY E.C. SINGLE POINT POWER CONNECTION.
2: RETURN AIR SMOKE DETECTORS PROVIDED AND INSTALLED BY E.C. ALL FLS WIRING BY FLS CONTRACTOR.
HEAT PUMP SCHEDULE
HP #
SERVER ROOM
MAKE
MODEL
COOLING
HTG.
CAP.
FAN PERFORMANCE DATA
OSA,
HTR.
KW
ELECTRICAL
WGT.
SEER.
IPLV
FILTERS
REMARKS
TOTAL
SENS.
CFM
S.P.
RPM
MHP
VOLTS/PH
MCA
QTY
SIZE
HP -1
BASEMENT
TRANE
WCD036C
39.4
25.0
36.0
1200
.67
-
.34
-
6.0
208v/30
35.8
565
10.5
-
2
20X25X1
1,2,3,4,6,8,11
DXFC-2
REPRO ROOM
MITSUBISHI
PLAA18AA
CU -2
75/62
18000 BTUH
-
350
-
-
-
-
-
-
208/230/1
1
-
-
53
1,2,3,4,6,8,11
D.X. FAN COIL SCHEDULE (SPLIT SYSTEM)
TAG
AREA
SERVED
MAKE
MODEL
MATCHING
COND. UNIT
COOLING
FAN PERFORMANCE DATA
ELECTRICAL
FILTERS
WEIGHT
REMARKS
ENT. DB/WB
TOTAL
SENS.
CFM
OA CFM
ESP
RPM
BHP
MHP
HEAT KW
VOLTS/PH
MCA
QTY.
SIZE
DXFC-1
SERVER ROOM
TRANE
TWE048
CU -1
75/45
47500 BTUH
32100 BTUH
1600
-
0.055
1075
-
1.5
-
230/1
4.2
-
-
200
1,2,3,4,6,8,11
DXFC-2
REPRO ROOM
MITSUBISHI
PLAA18AA
CU -2
75/62
18000 BTUH
-
350
-
-
-
-
-
-
208/230/1
1
-
-
53
1,2,3,4,6,8,11
DXFC-3
IDF ROOM
MITSUBISHI
PDA-A18HA4
CU -3
80/67
18000 BTUH
-
370
-
-
-
-
-
-
230/1
0.33
-
-
30
2,4
1: WIRING AND DISCONNECT BY E.C. SINGLE POINT POWER CONNECTION.
2: OPTIONS TO INCLUDE: THERMAL EXPANSION VALVE.
3: 115V. 1.5 AMP CONDENSATE PUMP, BECKETT MODEL CL201 UL, FURNISHED BY M.C. SEPARATE POWER CONNECTION BY E.C. FIELD VERIFY THAT CONDENSATE PUMP IS REQUIRED.
4: FIELD VERIFY THAT CONDESATE PUMP IS REQUIRED.
5: BAS TO MONITOR CONDENSATE ALARM SWITCH.
6: PC TO ROUTE CONDENSATE TO APPROVED PLUMBING RECEPTICAL. SEE DETAIL 2 SHEET M6.01 FOR TRAP DIMENSIONS.
7: NO SPRING OR NEOPRENE ISOLATION REQUIRED.
8: HANG WITH MASON TYPE "DNHS" SPRING ISOLATORS WITH SEISMIC SLACK CABLING.
9: HANG WITH MASON TYPE "HD" NEOPRENE HANGERS.
10: SMOKE DETECTOR PROVIDED BY E.C,, INSTALLED IN DUCTWORK BY M.C., WIRED BY FLS CONTRACTOR.
11: LOW VOLTAGE CONTROL WIRING BETWEEN DXFC AND CONDENSING UNIT BY CONTROLS CONTRACTOR.
12: TWO ELECTRICAL CIRCUITS ARE REQUIRED.
13: T -STAT PROVIDED AND INSTALLED BY M.C.
14: OPTIONS TO INCLUDE: EVAPORATOR DEFROST CONTROLLER.
15: E.C. SHALL PROVIDE AND INSTALL PRIMARY AND SECONDARY POWER.
FAN SCHEDULE
TAG
FUNCTION
AREA SERVED
MAKE
TYPE
MODEL
CLASS
PERFORMANCE DATA
HP
ROTATION
CW/CCW
MOTOR
ACCESS
VOLTS/
PHASE
WGT.
LBS,
REMARKS
CFM
S.P.
RPM
BHP
EF -1
-
1ST FLOOR SERVER ROOM
GREENHECK
UTILITY
SWB-16-5
-
1800
0.75
1184
0.35
0.5
CW
CU -3
120/1
300
1,5,8
230/1
13
15.3
-
90
1,3,4
1: WIRING AND DISCONNECT BY E.C.
2: MANUAL STARTER W/OVERLOAD PROTECTION SHALL BE PROVIDED AND INSTALLED BY E.C.
3: AUTOMATIC MOTOR STARTER WITH HOA SWITCH SHALL BE PROVIDED AND INSTALLED BY E.C., COIL CIRCUIT POWERED BY E.C., COIL VOLTAGE TO BE 120V.
4: 7 -DAY PROGRAMMABLE T -STAT SHALL BE PROVIDED AND INSTALLED BY CONTROLS CONTRACTOR.
5: LINE VOLTAGE (120V) T -STAT WITH TEMPERATURE RANGE BETWEEN 60 AND 100 DEG. F SHALL BE PROVIDED BY M.C. AND INSTALLED BY E.C.
6: INSTALL ON SIESMIC SPRING ISOLATORS MASON MODEL SSLFH OR EQUIV.
7: HANG WITH SPRING ISOLATION MASON MODEL ____ W/ SEISMIC SLACK SPRINGS.
8: HANG WITH NEOPRENE ISOLATORS MASON MODEL
SPLIT SYSTEM CONDENSING UNIT SCHEDULE
TAG
MAKE
MODEL
DXFC
SERVED
ELECTRICAL
SEER
EER.
WEIGHT
REMARKS
VOLTS/PH
MCA
CU -1
TRANE
TTB048
DXFC-1
230/1
30
10.5
-
250
1,2,4,6,7
CU -2
MITSUBISHI
PUZA18NHA
DXFC-2
208-230/1
13
14.1
-
91
1,4,6,7
CU -3
MITSUBISHI
PUY-A18NHK4
DXFC-3
230/1
13
15.3
-
90
1,3,4
1: WIRING AND DISCONNECT BY E.C. SINGLE POINT POWER CONNECTION.
2: LOW AMBIENT KIT PROVIDED AND INSTALLED BY REFRIGERANT PIPING CONTRACTOR. PENN P66 SERIES.
3: FASTEN TO SLEEPERS ON MASON TYPE "W" WAFFLE PAD WITH BOLT ISOLATION BUSHINGS.
4: EER AND SEER RATINGS PER ARI 210 /240 -1989.
5: OPTIONS INCLUDE: CRANKCASE HEATER KIT, AND TSTAT.
6: CONTROLS WIRING BETWEEN DXFC, CU AND T -STAT IS BY CONTROLS CONTRACTOR.
7: OPTIONS INCLUDE: HARD START KIT
8: E.C. SHALL PROVIDE AND INSTALL PRIMARY AND SECONDARY POWER.
9: UNIT HUNG FROM SLAB ABOVE.
N1 13- (ar9
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL 9 4 2013
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JUL 112013
PERMIT CENTER
= EXISTING CONSTRUCTION
= NEW CONSTRUCTION
HOLADAY-PARKS, INC.
SMART Mechanical Solutions
Mechanical Solutions • Energy Services
Building Controls • Service & Maintenance
4600 S. 134TH PLACE
SEATTLE, WA 98168 • (206) 248-9700
HOLADAYPARKS.com
WA LICENSE NUMBER: HOLADPI379NO
( PROJECT
DESIGN TEAM
Designed by:
Drawn by:
MJG
SLS
Approved by:
Job Number:
1286
Filename:
M701-4600.DWG
REGISTRATION
07/11/13
APPROVED
FOR CONSTRUCTION
I ISSUE NAME/DATE I
IDF ROOM PERMIT
PENDING CITY APPROVAL
07/11/13
I REVISIONS
No. Date r� Description
1 2/25/93 OFF. EXPANSION
2 4/21/93
3 7/30/99
5 9/1/00
6 5/05/06
7 7/15/08
AS -BUILT
SERVER ROOM COOLING
SERVER RM PERMIT/CONST
REPRO RM COOLING PERMIT
REPLACE ROOFTOP UNITS
8 07/11/13 MJG IDF ROOM PERMIT
SHEET TITLE
SCHEDULES
M7.01
ALL RIGHTS RESERVED. THESE DRAWINGS BELONG IN ANY FORM TO HOLADAY-PARKS, INC.. NO PART OF THIS DOCUMENT MAY BE REPRODUCED IN ANY FORM OR BY ANY MEANS WITHOUT PERMISSION IN WRITING FROM HOLIDAY PARKS, INC.