MECHANICAL PERMIT
9202470010
535 SOUTHCENTER MALL TUKW
Project Name: J CREW
Permit Number: M13-136
Issue Date: 08/23/2013
Permit Expires On: 02/19/2014
Owner:
Name: WESTFIELD PROPERTY TAX DEPT
Address: PO BOX 130940 , CARLSBAD CA 92013
Contact Person:
Name:
Address:
Email:
GARY PALMER
PO BOX 23534 , EUGENE OR 97492
NOT PROVIDED
Contractor:
Name:
Address:
Contractor License No:
Phone: 541-603-4191
Phone:
Expiration Date:
DESCRIPTION OF WORK:
REMOVE ALL EXISTING VENTS, DUCTING, PIPING, CONTROLS ETC RELATED TO TENANT
IMPROVEMENT. REPLACE REMOVED AND INSTALL NEW DUCTING, RTU'S AND RELATED
CONTROLS. ALSO INSTALL NEW RESTROOM EXHAUST FAN.
Value of Mechanical: $42,000.00
Type of Fire Protection: UNKNOWN
Electrical Service Provided by:
Permit Center Authorized Signature:
I hereby certify that I have read and
governing this work will be complie
Fees Collected:
$713.81
International Mechanical Code Edition: 2012
xami
with,
The granting of this permit does not pres
construction or the performance of work.
back of this permit.
Signature:
Date:
oti(24)
ed this permit and know the same to be true and correct. All provisions of law and ordinances
whether specified herein or not.
e to give authority to violate or cancel the provisions of any other state or local laws regulating
I am authorized to sign and obtain this mechanical permit and agree to the conditions on the
Print Name: A6- 13wit, `0r''
Date: 11 2j ((3
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
a..,.. Ines .A11n
RA1a_1za
Print.d. nR_91_')ni
PERMIT CONDITIONS
Permit No. M13-136
1: ***BUILDING DEPARTMENT CONDITIONS***
2: No changes shall be made to the approved plans unless approved by the design professional in responsible charge and the
Building Official.
3: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila Permit Center
(206/431-3670).
4: All permits, inspection records, and approved plans shall be at the job site and available to the inspectors prior to
start of any construction. These documents shall be maintained and made available until final inspection approval is
granted.
5: Readily accessible access to roof mounted equipment is required.
6: All construction shall be done in conformance with the approved plans and the requirements of the International
Building Code or International Residential Code, International Mechanical Code, Washington State Energy Code.
7: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap the sanitary
sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks, wells, and other
excavations. Final inspection approval will be determined by the building inspector based on satisfactory completion of
this requirement.
8: Manufacturers installation instructions shall be available on the job site at the time of inspection.
9: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the City of Tukwila
Building Department (206-431-3670).
10: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila Building
Department (206-431-3670).
11: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of the building code or of any other ordinances of the City of Tukwila. Permits
presuming to give authority to violate or cancel the provisions of the code or other ordinances of the City of Tukwila
shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the
Building Official from requiring the correction of errors in the construction documents and other data.
12: ***FIRE DEPARTMENT CONDITIONS***
13: H.V.A.C. units rated at greater than 2,000 cfm require auto -shutdown devices. These devices shall be separately zoned
in the alarm panel and local U.L. central station supervision is required. (City Ordinance #2328)
14: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings shall be
equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the power source of the
air -moving equipment upon detection of smoke in the main return -air duct served by such equipment. Smoke detectors
shall be labeled by an approved agency for air -duct installation and shall Joe installed in accordance with the
manufacturer's installation instructions. (IMC 606.1, 606.2.1)
15: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City Ordinance #2328)
16: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2328)
17: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2328)
18: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances #2327 and
#2328)
19: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply approval of
such condition or violation.
20: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention Bureau at
(206)575-4407.
doc: IMC -4/10
M13-136 Printed: 08-23-2013
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-43 1-3670
Fax: 206-431-3665
Web site: http://www.Tukwila WA.Eov
RECEIPT
Parcel No.: 9202470010 Permit Number: M13-136
Address: 535 SOUTHCENTER MALL TUKW Status: APPROVED
Suite No: Applied Date: 07/22/2013
Applicant: J CREW Issue Date:
Receipt No.: R13-02434
Payment Amount: $571.05
Initials: JEM Payment Date: 08/23/2013 10:04 AM
User ID: 1165 Balance: $0.00
Payee: EVERGREEN REFRIGERATION, LLC
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 006079 571.05
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
MECHANICAL - NONRES
000.322.102.00.00 571.05
Total: $571.05
Printed: 08-23-2013
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd, Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Mechanical Permit No. M
Project No. A 13-'0 S
Date Application Accepted:
Date Application Expires:
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
King Co Assessor's Tax No.:
Site Address: 535 Southcenter Mall Suite Number: 676 Floor: Ground
Tenant Name:
J Crew
PROPERTY OWNER
Name: Westfield
Address: 11601 Willshire Blvd, 11th Floor
City: Los Angeles State: CA Zip: 90025
CONTACT PERSON — person receiving all project
communication
Name: Gary Palmer, Property Service
I
Address: PO Box 23534
City: Eugene State: OR
Zip: 97492
Phone: (514) 603-4191 Fax:
Email: psconsultants@sbcglobal.net
State:
New Tenant:
0 Yes ..No
MECHANICAL CONTRACTOR INFORMATION
Company Name: TBD
Address:
City:
State:
Zip:
Phone:
Fax:
Contr Reg No.:
Exp Date:
Tukwila Business License No.:
Valuation of project (contractor's bid price): $
Describe the scope of work in detail:
Remove all existing vents, ducting, piping, controls etc related to TI. Replace removed and install new ducting, RTU's and related
controls. Also install new restroom exhaust fan
42,000
Use:
Residential: New ❑ Replacement ❑
Commercial: New ❑ Replacement m
Fuel Type: Electric 0 Gas ❑
Other:
H:\Applications\Forns-Applications On Line\201 I Applications Mechanical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
2
Furnace >100k btu
32
Floor furnace
2
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cooling
system
Air handling unit
<10,000 cfm
1
Unit Type
Qty
Air handling unit
2
>10,000 cfm
32
Evaporator cooler
2
Ventilation fan
connected to single duct
Ventilation system
Hood and duct
Incinerator — domestic
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
2
Diffuser
32
Thermostat
2
Wood/gas stove
Emergency generator
Other mechanical
equipment
Boiler/Compressor
Qty
0-3 hp/100,000 btu
2
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR AUTHORIZED A
Signature:
G e."1 }�� , .,�► y �� � �� Date: 7/41 z//
Print Name: Gary Palmer, Property Service Day Telephone: (514) 6034191
Mailing Address: PO Box 23534 Eugene OR 97492
H:\Applications\Forns-Applications On Line \2011 Applications\Mechanical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
City State Zip
Page 2 of 2
411 •
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206-431-3665
Web site: http://www.TukwilaWA.gov
RECEIPT
Parcel No.: 9202470010 Permit Number: M13-136
Address: 535 SOUTHCENTER MALL TUKW Status: PENDING
Suite No: Applied Date: 07/22/2013
Applicant: J CREW Issue Date:
Receipt No.: R13-02184
Initials: WER
User ID: 1655
Payment Amount: $142.76
Payment Date: 07/22/2013 04:32 PM
Balance: $571.05
Payee: GARY R PALMER
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 00966G
ACCOUNT ITEM LIST:
Description
142.76
Account Code Current Pmts
PLAN CHECK - NONRES
000.345.830 142.76
Total: $142.76
..lnr• Renaint_nn
Printed• 07-22-2013
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION C
6300 Southcenter Blvd., #100, Tukwila. WA 98188
Permit Inspection Request Line (206) 431-2451
M(3 -13r
(206) 431-3670
ProjecJi: t V�/
TYP f In o` +- i•JA_�
Address: , r1
CC
Date Called:
S A
Special Instructions:
d
_/�
..14 ,�
Date Wanted: 1 t Z .ate-
-.ate--.ate-..14--A,/(4
` 1 - CO — t J P.m.
Requester:oon
Ph5-4 1 - 44 (o33t )
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
?m vT Lo-tpiae
r
Insped` r:
n REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTIONO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-367
Permit inspection Request Line (206) 431-2451
M13-13 �
Project,,..
LIT—V.!
Type of Inspection:
S M0i‘e-.-. eJ cc I ok
Addr 3 S .L. AA( 1
Date Called:
Special Instructions:
Date Wanted:r / Wim._
(1_(O ( p:m.
sequester:
Phone No:
54( - 48--433 Cs
Approved per applicable codes.:
Corrections required prior to approval.
COMMENTS:
MAt- .OA- (-- c : c pr0��
19 (A)14 ,# f'() \i
Insp ctor:
Dat?
REINSPECTION FEE REQUIRE[. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
"3-i3(a
Project: C rev./Typet-
i it
1
Jul eC�-
Addres :\l
Date Called:
Special Instructions:
Date Wanted:((
_ , �13 ..
Requester:
Phone No.
f ,
o' - t633c
ElApproved per applicable codes. 2 Corrections required prior to approval.
COMMENTS:
!tnt. 1/.1 kit not Jn
In
pector:
Date:
I(' S—" --
REINSPECTION
--
REINSPECTION FEE 'E4 MED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188
Permit Inspection Request Line (206) 431-2451
(206) 431-3670
Project:
,.. CJ.t/U
Type of Inspection:
RChicH-=-N
Address:
5a S.C.
N 1 v (k
Date Called:
Special Instructions:
Date Wanted:
tC-) /Z Z //
a.m'
p.m.
requester:
Phone No:
aC-)6-6.7-.3/
37
VI -Approved per applicable codes. Q Corrections required prior to approval.
COMMENTS:
6'
(17-, f'° ,l//,1
Ins secttoor:
n REINSPECTION FEE REQtkIRED. Prior to nxt inspection, fee must be
paid at 6300 Southcenter B d.. Suite 100. Call to schedule reinspection.
INSPECTIO NO.
INSPECTION RECORD
Retain a copy with permit
M (3 -
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Project:'; c f C.... v1/
TYp��°f InspU
j
1
Addr s: ,�.
5i $c_ A44(/
Sj
i'"
Date Called:------
6vC.-I .
Special Instructions: .
Date Wanted,
- 2....c:
-- 1 3
.
".a a.m..
p.m.
requester:
Phone No:.
["
(P
/
7
Approved per applicable codes. Corrections required prior to approval.
F
COMMENTS:
d
Inspector:
Dater
-7.' )f f j
\
n REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
--4k3
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-367
Permit Inspection Request Line (206) 431-2451
X13 -1.31
Project-; - c rc
Type / Ir�s�ctio
t
! 4
t
Addre..3 J milt'
Date Called:
Special Instructions:
Date Wanted:(�j
/
%
`
a.m.
I'i—equester:
Gc5✓efCe) S4'Ce_„J
Phone No:
lair/'(,
.S i e ci i a
pr I LJ
Approved per applicable codes.
Corrections required prior to approval. 4
COMMENTS:
A --
01‹...e, e (
Gc5✓efCe) S4'Ce_„J
foo! c.)A.(
lair/'(,
.S i e ci i a
pr I LJ
d .
._sr' .k fc. f us
a
.
Inspectl'br:
Date � ()
n REINSPECTION FEE REQUIRED. rior to next inspection, fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
Me -06
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-36.70
Permit Inspection Request Line (206) 431-2451
Projecttil
Type of Inspec on:
Mem
JO -c, ,
Addres • A
4
X51 SC Al/
Date Called:
Special Instructions:
Date Wanted: 5
23 43
Pim
reiuester:
Phone No:
Approved per applicable codes.
COMMENTS:
Corrections required prior to approval.
aiLC i -D. Ai hoAt Thr ? .
t
,t)
(
REINSPECTION FEE REQUIRED. Prior Ito next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Mia- / 3 b
Project:...-
J e r e vV
Type/of Inspection:
i< 0 G a --LA/
Address:
.. 35 )c
MA -I1
Date Called:
Special Instructions:
Date Wanted:!
I
` (�
`�.----
P.m.
Requester:
Approved per applicable codes.
Corrections required prior to approval. 2 -
COMMENTS: COMMENTS:
Insp'ect or: li
Date
i&-- i_3
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
m' -V3C,
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd:, #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Proje :
Mak)
Typ of Inspection:
Ou6H M, N
Address:
53.E S C mALL
Date Called:
Special Instructions:
Dates Wanted:
- t — 11— l3
p.m.
Requester:
Phone No:
a.CD c7- (0-79 - 3 ►3
`7
Approved per applicable codes. 0 Corrections required prior to approval.
COMMENTS: A
CIS .mak-; K, - AP Qi6k/PA' o lu ► 0 sia,476
D kc- % +J rv\ -- S 1 tcAAJ yr) - INN t tJ u. S
b Are_ t�
l
Dat
E SPECTION FEE 4EQUIRED. Prior next inspection. fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION NUMBER
INSPECTION RECORD
Retain a copy/with permit
b1? -2S-7
rY► 3 36_�
PERMIT NUMBERS
CITY OF TUKWILA (FIRE DEPARTMENT
444 Andover Park East, Tukwila, Wa. 98188 206-575-4407
Project:
C r....Q.-ch_.J
Type of Inspection: ,
reAL /Z -- ////1 C
Address:
Suite #: 93.5
?C "WV/
Contact Person:
Special Instructions:
Phone No.:
(Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
Sprinklers: S
Date: %/ 6dl.2
Fire Alarm:
d Ye
Hood & Duct: /v0
Monitor:
-6;,-rP/U.,._._._
'Pre -Fire: A/c)
l` 31 e' /.A-
Permits:
aZ 7,�-,--) .:.��s •�€ .i�r. /Ace-
Occupancy Type:
f
"r�S/,-..-� 2€ A�1- �fd.07 - ot/-'7 �
/ifce
LJ
his ,¢v.i 14.24-- ✓/tri ` 7 r-44277
� e, .
d' -''tet •
4,-
i /G 10.el..,, <<-F-% 'S`�247 G fJG� --- ` O
i `,
.
•
Needs Shift Inspection: /
Sprinklers: S
Date: %/ 6dl.2
Fire Alarm:
d Ye
Hood & Duct: /v0
Monitor:
-6;,-rP/U.,._._._
'Pre -Fire: A/c)
Permits:
Occupancy Type:
f
Inspector
Date: %/ 6dl.2
Hrs.:
/
0
„.�55
/
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
the City of Tukwila Finance Department. Call to schedule a reinspection.
Billing Address
Attn:
Company Name:
Address: '
City:
State:
Zip:
Word/Inspection Record Form.Doc 6/11/10 T.F.D. Form F.P. 113
•
PLAN PF&MW/ROTING SLIP
ACTIVITY NUMBER: M13-136 DATE: 07-22-13
PROJECT NAME: J CREW
SITE ADDRESS: 535 SOUTHCENTER MALL
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #
Revision # After Permit Issued
DEPAR/T�M,�ENTS•
_wilding- Divislon,'31��
Public Works n
o °1'11,
Fire Prevention
Structural
Planning Division
Permit Coordinator
Fl
a
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Incomplete
DUE DATE: 07-25-13
Not Applicable
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
TUES/THURS ROUTING:
Please Route
Structural Review Required
REVIEWER'S INITIALS:
No further Review Required n
DATE:
APPROVALS OR CORRECTIONS:
Approved
Notation:
n
Approved with Conditions
DUE DATE: 08-22-13
Not Approved (attach comments) n
REVIEWER'S INITIALS: DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
Documents/routing slip.doc
2-28-02
Contractors or Tradespeople Pr Friendly Page
General/Specialty Contractor
A business registered as a construction contractor with LEI to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name EVERGREEN REFRIGERATION LLC UBI No. 602512953
Phone 2067631744 Status Active
Address 727 S Kenyon St License No. EVERGRL954R2
Suite/Apt. License Type Construction Contractor
City Seattle Effective Date 1/6/2006
State WA Expiration Date 1/6/2014
Zip 98108 Suspend Date
County King Specialty 1 General
Business Type Limited Liability Company Specialty 2 Unused
Parent Company
ther Associated Licenses
License
Name
Type
Specialty
1
Specialty
2
Effective
Date
Expiration
Date
Status
EVERGHH910J0
EVERGREEN HOME
HEATING & ENGY
Construction
Contractor
General
Unused
4/20/2009
4/20/2015
Active
EVERGI'201D7
EVERGREEN
REFRIGERATION INC
Construction
Contractor
General
Unused
3/27/1980
7/31/2006
Re
Licensed
Business Owner Information
Name
Role
Effective Date
Expiration Date
EVERGREEN REFRIGERATION LLC
Partner/Member
12/22/2005
Bond Amount
PATTON, DAVID
Partner/Member
01/06/2006
WA1 5097
PATTON, RODGER
Partner/Member
01/06/2006
PATTON, MATTHEW
Partner/Member
01/06/2006
TRAVELERS CAS a
SURETY CO
Bond Information
Page 1 of 1
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
2
Merchants Bonding Co
(Mutual)
WA1 5097
01/01/2012
Until. Cancelled
$12,000.00
12/15/2011
1
TRAVELERS CAS a
SURETY CO
104667361
01/01/2006
Until. Cancelled
$12,000.00
01/03/2006
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
3
AMERICAN FIRE
AND CASUALTY
COM
BAW54192293
07/31/2010
07/31/2014
$1,000,000.0007/30/2013
2
Continental
Western Ins Co
CWP2640663
07/31/2006
07/31/2010
$1,000,000.00
03/23/2009
Summons/Complaint Information No unsatisfied complaints on file within prior 6 year period
Warrant Information No unsatisfied warrants on file within prior 6 year period
Infractions/Citations Information No records found for the previous 6 year period
https://fortress.wa.gov/lni/bbip/Print.aspx
08/23/2013
GENERAL HVAC NOTES
SP
SP
NOTICE TO CONTRACTOR
RETURN AIR PLENUM PROTECTION REQUIRED
(This only applies to those spaces that share return air plenums)
Before any mall Tenant space Improvements or alterations are to begin, where
plenum ceilings are removed, altered or return air ceiling grills are open/exposed
to construction dust contamination, a "plenum protection plan" shall be required
to show procedures and methods for protecting and sealing the return air
plenums of any contamination fromconstruction dust and combustibles prior to
and during construction work. No inspections shall be performed until mitigation
procedures are made to protect any shared ceiling plenums.
•
RG -2.
RG -2
O
0
N
N
N
SD -1
240
0
0
O
0
SD -1'
240.
r10"0 10"0
0
0
X10"0
•
X10"0
240
H
SD -1,
240
(TYP
("1
D
200
SD -5
200
n
6"0
s.s
8"0
VAV-1
T -STAT
RTU -1
T -STAT
SD -
200
8"0
SD -5
200
l_
8"0
14 10
100
SENSOR
II s~
SD -4
100
SD -3
50
r"6"0
RG -1
SD -3
50
100
D-3
0
SD -3
50
0
0
0
0
20x12
TYP
loot
26x12
loot
N
SP
R
(001
N
N
N
SD -1
a 240
0
0
ORTU
5500
A
VAV-1
T
650
•
Ili
i
00
XOa
O
Xo
42x12
N
°t
p
p
RG -3
1
SP
0
0
s
P
A
A
ir-10"0
N
G
N
N
X
Co
SD -1
240
0
0
SP
RG -2
A
10"0
_RG -2
i
SP
SD -1
240
0
0
SD -1
240
ID!
O
0
0
0
e-10"0
SD -1
240
N
N
N
N
N
240
x-1ONO
A
N
22x12
X10"0
0
0
SD -1
240
0
0
Tr --10"0 N
240
"0
O
0
0
0
ovv
001 001
cif`-
041
0'
!l
,N"
O~eo
osoSo
O�u
IRG-2
RG
SD -5
100
1. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR DEMOLITION AND REMOVAL OF
EXISTING DUCTWORK, DIFFUSERS, GRILLES, CONTROLS, ETC., AS REQUIRED TO FACILITATE
NEW INSTALLATIONS.
2. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL TRADES,
LANDLORD REQUIREMENTS, CEILING HEIGHTS AND EXISTING STRUCTURAL CONDITIONS PRIOR
TO FABRICATION OF ANY DUCTWORK OR ORDERING OF ANY EQUIPMENT.
3. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH ALL FEDERAL STATE AND LOCAL
CODES AND ORDINANCES.
4. FURNISH ALL LABOR, MATERIALS, TOOLS, INCIDENTALS AND DETAILS NECESSARY TO
PROVIDE A COMPLETE HEATING, VENTILATING, AIR CONDITIONING SYSTEM. INCLUDE ANY
LABOR AND MATERIAL NOT SPECIFICALLY MENTIONED, BUT NECESSARY TO PROVIDE A
COMPLETE AND OPERATING SYSTEM. ALL WORK SHALL BE INSTALLED IN A PROFESSIONAL
MANNER AND SHALL MEET ALL THE REQUIREMENTS OF THE STATE BUILDING CODE, CITY
BUILDING CODE, SAFETY AND HEALTH CODES, NFPA CODES AND ALL OTHER APPLICABLE
CODES AND REQUIREMENTS. ALL COSTS FOR SAID REQUIREMENTS SHALL BE INCLUDED IN
THIS CONTRACTORS BID PRICE.
5. THIS CONTRACTOR SHALL SECURE AND PAY FOR ALL REQUIRED PERMITS AND INSPECTIONS
AND PERFORM ALL TESTS CALLED FOR OR REQUIRED AS A PART OF HIS WORK.
FURNISHED APPROVED CERTIFICATE OF FINAL INSPECTION, AND TURN OVER TO OWNER AT
COMPLETION OF PROJECT.
6. MECHANICAL PLANS ARE DIAGRAMMATIC, NOT SHOWING EVERY ITEM IN EXACT LOCATION
OR DETAIL MEASUREMENTS AND LOCATIONS MUST BE FIELD VERIFIED AND COORDINATED
WITH ARCHITECTURAL HVAC, ARE PROTECTION, STRUCTURAL ELECTRICAL AND OTHER
BUILDING DRAWINGS.
7. MECHANICAL CONTRACTOR TO PROVIDE TENANT WITH AS -BUILT DRAWINGS, ALL
EQUIPMENT SHOP DRAWINGS, INFORMATION ON THERMOSTATS, CONTROL WIRING DIAGRAMS
AND OTHER PERTINENT INFORMATION AT COMPLETION OF PROJECT.
8. CONTRACTOR SHALL VERIFY ALL EXISTING SITE CONDITIONS PRIOR TO BID AND INCLUDE IN
BID ALL COSTS TO MAKE FIELD COORDINATION AND ADJUSTMENT TO DUCTWORK FOR FIT
INTO EXISTING STRUCTURE. CONTRACTOR SHALL VERIFY AND FIELD COORDINATE FINAL
LOCATION OF MECHANICAL EQUIPMENT.
9. ALL DUCTWORK SHALL BE SHEET METAL FABRICATED IN ACCORDANCE WITH ASHRAE
GUIDE AND SMACNA MANUAL LATEST EDITIONS.
10. DUCT LININGS (THERMAL AND ACOUSTICAL), VIBRATION ISOLATION CONNECTORS, FLEXIBLE
DUCT CONNECTORS, AND DUCT TYPE TO BE APPROVED BY CODE AND LANDLORD.
11. DUCT DIMENSIONS SHOWN ARE INSIDE NET DIMENSIONS, ADD TO SHEET METAL SIZE FOR
INSULATION. IN GENERAL, DUCTWORK TIGHT TO UNDERSIDE OF STRUCTURE UNLESS
OTHERWISE NOTED OR REQUIRED BY FIELD CONDITIONS. COORDINATE EXACT MOUNTING
HEIGHT IN FIELD WITH GENERAL CONTRACTOR. ROUND RIGID SUPPLY, RETURN, ALL RELIEF
AIR AND ALL OUTSIDE AIR DUCTS SHALL BE EXTERNALLY INSULATED WITH 1 1/2" THICK,
1.5 LBS. DENSITY FOIL FACED FIBERGLASS INSULATION. ROUND DUCTWORK IN CONDITIONED
SPACE DOES NOT REQUIRE I! SULATION UNLESS OTHERWISE NOTED.
12. ALL BRANCH TAKE -OFFS SHALL BE PROVIDED WITH MANUAL BALANCING DAMPERS.
13. FLEXIBLE INSULATED DUCTS SHALL BE MAXIMUM 5'-0" LONG AND SHALL MEET
INSTALLATION AND MATERIAL REQUIREMENTS OF LOCAL CODES.
14. THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE TEMPERATURE
CONTROL SYSTEM TO INCLUDE: PANELS, MODULES, RELAYS, WIRING, THERMOSTATS,
SENSORS, DAMPERS, ACTUATORS AND ALL MISCELLANEOUS ITEMS AS REQUIRED TO FULFILL
THE DESIGN INTENT AS INDICATED ON THE PLANS AND IN THE CODED NOTES.
15. ALL TEMPERATURE CONTROLS, FIRE ALARM COMPONENTS, EQUIPMENT NAMEPLATES,
LABELS, OR COLOR CODED COMPONENTS SHALL BE MASKED DURING PAINTING TO PREVENT
DAMAGE FROM OVER -SPRAY OR OBSCURING INFORMATION.
16. ALL LOW VOLTAGE WIRING AND CONDUIT REQUIRED FOR MECHANICAL EQUIPMENT SHALL BE
FURNISHED AND INSTALLEDBy MECHANICAL CONTRACTOR. CONTRACTOR SHALL BE
RESPONSIBLE FOR COORDINANG WITH ELECTRICAL CONTRACTOR ALL WIRING AND CONDUIT
REQUIRED FOR EQUIPMENT OERATION AND CONTROL
17. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT THE MECHANICAL EQUIPMENT
COMPONENTS ARE INSTALLED, AT LOCATIONS AND ELEVATIONS WHICH MAKE THEM READILY
ACCESSIBLE FOR ROUTINE MAINTENANCE WITHOUT REQUIRING ANY EXTRAORDINARY
MEASURES.
MECHANICAL PLAN
1 /4"=1'-O"
MECHANICAL CODED NOTES;
0 OWNER SHALL FURNISH AND CONTRACTOR SHALL INSTALL A "LIGHT STAT"
PROGRAMMABLE THERMOSTAT WITH SUB -BASE AND REMOTE
TEMPERATURE SENSOR AT 5'-0" A.F.F. COORDINATE EXACT LOCATION
WITH TENANTS CONSTRUCTION MANAGER. THERMOSTATS TO BE MOUNTED
ON LIGHT STAT CONTROL PANEL LIGHTSTAT THERMOSTATS AND SENSORS
ARE TO CONTROL HEATING AND COOLING MODES.
O RTU -1 - NEW ROOFTOP UNIT INSTALLED IN SAME LOCATION ,AS EXISTING
UNIT. MECHANICAL CONTRACTOR SHALL REMOVE AND DISPOSE OF EXISTING
ROOFTOP UNITS AND SHALL FURNISH AND INSTALL A ROOF MOUNTED
ELECTRIC COOLING/ GAS HEATING HVAC UNIT. SEE ROOF TOP UNIT
SCHEDULE FOR FURTHER INFORMATION. UNIT TO SIT ON EXISTING CURB
AND ROOF OPENING. UNIT SHALL BE FURNISHED WITH TWO SETS OF
STANDARD FILTERS. CONTRACTOR TO REPLACE FILTERS PRIOR TO TURNING
STORE OVER TO TENANT. ALL ROOF WORK INVOLVED WITH SETTING OF
THE ROOF CURB AND UNIT SHALL BE DONE BY THE LANDLORD'S ROOFING
CONTRACTOR AT THE G.C. EXPENSE UNLESS NOTED OTHERWISE. GENERAL
CONTRACTOR SHALL PROVIDE ANY ADDITIONAL STRUCTURAL STEEL
REQUIRED TO SUPPORT RTU, PER LANDLORD'S REQUIREMENTS. COORDINATE
LOCATIONS OF ROOF TOP UNITS AND EXISTING ROOF EQUIPMENT WITH
LANDLORD. PROVIDE CLEAR ACCESS TO ALL EQUIPMENT AND
CODE -REQUIRED CLEARANCES FOR OUTSIDE AIR INTAKES. STENCIL
TENANTS NAME AND SPACE NUMBER ON RTU. UNIT SHALL BE HORIZONTAL
DISCHARGE . DUCTED DOWN INTO SPACE THROUGH EXISTING ROOF OPENING.
FIELD VERIFY EXACT: SIZE AND LOCATION OF EXISTING ROOF CURB AND
OPENING.
0 THE CONTRACTOR SHALL FURNISH AND INSTALL CONDENSATE DRAINS FROM
HVAC UNIT AS SHOWN ON PLANS. MINIMUM DRAIN SIZE TO BE 1" OR AS
SPECIFIED ON PLANS. CONDENSATE DRAIN TO BE TRAPPED WITH A
MINIMUM 5" TRAP DEPTH. DRAINS SHALL BE EXTENDED AT A SLOPE OF
1" PER 40'. ROUTE RTU CONDENSATE DRAINS TO SPLASH BLOCK ON
ROOF OR NEAREST ROOF DRAIN AS REQUIRED BY LANDLORD AND LOCAL
CODE.
® PROVIDE FULL SIZE DUCT CONNECTION TO RETURN AIR WITH ELBOW FOR
SOUND ATTENUATION OF RETURN AIR, AND WIRE MESH AT OPENING.
O SMOKE DETECTOR IN RETURN AIR DUCT SHALL SHUT DOWN UNIT SUPPLY
FAN AND SIGNAL THE LANDLORD FIRE ALARM SYSTEM UPON SENSING
SMOKE. SMOKE DETECTOR TO BE FURNISHED BY ELECTRICAL CONTRACTOR
AND INSTALLED BY MECHANICAL CONTRACTOR. WIRING TO FIRE ALARM
SYSTEM BY ELECTRICAL CONTRACTOR. COORDINATE REQUIREMENTS WITH
LANDLORD.
® MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL A BROAN
EXHAUST FAN (120V., 1 PH., 60 HZ) COMPLETE WITH INTEGRAL
BACKDRAFT DAMPER AND ON-OFF SWITCH. EXHAUST CAPACITY SHALL BE
75 CFM AT .5" S.P. CONTRACTOR TO FURNISH AND INSTALL EXHAUST
DUCT, AND ACCESSORIES AS REQUIRED INCLUDING SPEED CONTROLLER
CONCEALED A'n ArrrcctRLL, CONNECT TO EXISTING LANDLORD EXHAUST
CONNECTION IN SPACE. FIELD VERIFY EXACT SIZE AND LOCATION.
O7 CONTRACTOR SHALL UNDERCUT DOOR 1" FOR AIR RETURN.
® PROVIDE NEW ELECTRONIC THERMOSTAT AND SENSOR FOR VAV BOX, AND
ASSOCIATED WIRING, ETC. TO BE THE SAME MANUFACTURER AS VAV BOX.
O9 VAV-1
MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL A SERIES FAN
POWERED, VARIABLE -AIR -VOLUME (VAV) BOX WITH ELECTRIC HEATING, ECM
MOTOR, AND ELECTRONIC CONTROL WITH AUTOCHANGE-OVER. VAV BOX
SHALL BE CONNECTED TO THE MAIN AIR DISTRIBUTION SYSTEM WITH DUCT
SIZES AS SHOWN. VERIFY BOX INLET AND OUTLET CONNECTION SIZES AND
INCLUDE DUCT TRANSITIONS AND FLEX DUCT CONNECTIONS IN BID. SEE
VARIABLE AIR VOLUME BOX SCHEDULE FOR FURTHER INFORMATION. MOUNT
VAV BOX AT MAXIMUM POSSIBLE HEIGHT ABOVE FINISHED FLOOR.
<D4UGHTSTAT SUPPLY AIR SENSOR MOUNTED IN DUCTWORK.
11 HORIZONTAL DISCHARGE DUCTWORK TO DROP DOWN THROUGH ROOF
THROUGH EXISTING CURB AND OPENING. PROVIDE WEATHERPROOF
INSULATED ENCLOSURE AROUND DUCTS AND ROOF OPENING TO MATCH
EXISTING INSTALLATION. FIELD VERIFY EXACT SIZE AND LOCATION OF
EXISTING CURB AND OPENING TO BE REUSED.
FIELD VERIFY ALL CONDITIONS BEFORE BID.
!SEPARATE PERMIT
REQUIRED FOR:
0 Mechanical
glitleotrical
el6Numbing
as Piping
City of Tukwila
EU!L. 3ING DIVISION
REVISIONS
No changes sha'I be made to the scope
of work witho#.t prior approval of
Tukwila ,lila Building Division.
r avisions will require a new plan submittal
and may include additional plan review fees.
FILE COPY
Permit No. IA (S-1$4)
firm Inflow approval is subject to errors and omissions.
k; 4 of construction documents does not authorize
, or<
of any adopted code or ordinance. Receipt
o►iipproveci Field Copy and cot ons isadmowledged:
BY
V)"3
City OfTukwila
BUILDING DIVISION
FIELD VERIFY ALL CONDITIONS
DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT THE SITE
PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING FIELD
CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL LABOR AND MATERIALS
NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING CONDITIONS.
THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER
PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN
AND INCLUDE IN HIS BID ALL COSTS TO MEET THE DESIGN INTENT.
CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER AFTER
BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS COST.
BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES
AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL
W iRK INSTALLED IN STRICT ACCORDANCE WITH GOVERNING CODES, THE PLANS
AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT
ARCHITECT, ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN
GOVERNING CODES AND DESIGN INTENT.
SYMBOL LEGEND
SYMBOL
00
00
DESCRIPTION
42x12
N
SD -1
240
0
0
SP
RG -2
A
10"0
_RG -2
i
SP
SD -1
240
0
0
SD -1
240
ID!
O
0
0
0
e-10"0
SD -1
240
N
N
N
N
N
240
x-1ONO
A
N
22x12
X10"0
0
0
SD -1
240
0
0
Tr --10"0 N
240
"0
O
0
0
0
ovv
001 001
cif`-
041
0'
!l
,N"
O~eo
osoSo
O�u
IRG-2
RG
SD -5
100
1. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR DEMOLITION AND REMOVAL OF
EXISTING DUCTWORK, DIFFUSERS, GRILLES, CONTROLS, ETC., AS REQUIRED TO FACILITATE
NEW INSTALLATIONS.
2. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL TRADES,
LANDLORD REQUIREMENTS, CEILING HEIGHTS AND EXISTING STRUCTURAL CONDITIONS PRIOR
TO FABRICATION OF ANY DUCTWORK OR ORDERING OF ANY EQUIPMENT.
3. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH ALL FEDERAL STATE AND LOCAL
CODES AND ORDINANCES.
4. FURNISH ALL LABOR, MATERIALS, TOOLS, INCIDENTALS AND DETAILS NECESSARY TO
PROVIDE A COMPLETE HEATING, VENTILATING, AIR CONDITIONING SYSTEM. INCLUDE ANY
LABOR AND MATERIAL NOT SPECIFICALLY MENTIONED, BUT NECESSARY TO PROVIDE A
COMPLETE AND OPERATING SYSTEM. ALL WORK SHALL BE INSTALLED IN A PROFESSIONAL
MANNER AND SHALL MEET ALL THE REQUIREMENTS OF THE STATE BUILDING CODE, CITY
BUILDING CODE, SAFETY AND HEALTH CODES, NFPA CODES AND ALL OTHER APPLICABLE
CODES AND REQUIREMENTS. ALL COSTS FOR SAID REQUIREMENTS SHALL BE INCLUDED IN
THIS CONTRACTORS BID PRICE.
5. THIS CONTRACTOR SHALL SECURE AND PAY FOR ALL REQUIRED PERMITS AND INSPECTIONS
AND PERFORM ALL TESTS CALLED FOR OR REQUIRED AS A PART OF HIS WORK.
FURNISHED APPROVED CERTIFICATE OF FINAL INSPECTION, AND TURN OVER TO OWNER AT
COMPLETION OF PROJECT.
6. MECHANICAL PLANS ARE DIAGRAMMATIC, NOT SHOWING EVERY ITEM IN EXACT LOCATION
OR DETAIL MEASUREMENTS AND LOCATIONS MUST BE FIELD VERIFIED AND COORDINATED
WITH ARCHITECTURAL HVAC, ARE PROTECTION, STRUCTURAL ELECTRICAL AND OTHER
BUILDING DRAWINGS.
7. MECHANICAL CONTRACTOR TO PROVIDE TENANT WITH AS -BUILT DRAWINGS, ALL
EQUIPMENT SHOP DRAWINGS, INFORMATION ON THERMOSTATS, CONTROL WIRING DIAGRAMS
AND OTHER PERTINENT INFORMATION AT COMPLETION OF PROJECT.
8. CONTRACTOR SHALL VERIFY ALL EXISTING SITE CONDITIONS PRIOR TO BID AND INCLUDE IN
BID ALL COSTS TO MAKE FIELD COORDINATION AND ADJUSTMENT TO DUCTWORK FOR FIT
INTO EXISTING STRUCTURE. CONTRACTOR SHALL VERIFY AND FIELD COORDINATE FINAL
LOCATION OF MECHANICAL EQUIPMENT.
9. ALL DUCTWORK SHALL BE SHEET METAL FABRICATED IN ACCORDANCE WITH ASHRAE
GUIDE AND SMACNA MANUAL LATEST EDITIONS.
10. DUCT LININGS (THERMAL AND ACOUSTICAL), VIBRATION ISOLATION CONNECTORS, FLEXIBLE
DUCT CONNECTORS, AND DUCT TYPE TO BE APPROVED BY CODE AND LANDLORD.
11. DUCT DIMENSIONS SHOWN ARE INSIDE NET DIMENSIONS, ADD TO SHEET METAL SIZE FOR
INSULATION. IN GENERAL, DUCTWORK TIGHT TO UNDERSIDE OF STRUCTURE UNLESS
OTHERWISE NOTED OR REQUIRED BY FIELD CONDITIONS. COORDINATE EXACT MOUNTING
HEIGHT IN FIELD WITH GENERAL CONTRACTOR. ROUND RIGID SUPPLY, RETURN, ALL RELIEF
AIR AND ALL OUTSIDE AIR DUCTS SHALL BE EXTERNALLY INSULATED WITH 1 1/2" THICK,
1.5 LBS. DENSITY FOIL FACED FIBERGLASS INSULATION. ROUND DUCTWORK IN CONDITIONED
SPACE DOES NOT REQUIRE I! SULATION UNLESS OTHERWISE NOTED.
12. ALL BRANCH TAKE -OFFS SHALL BE PROVIDED WITH MANUAL BALANCING DAMPERS.
13. FLEXIBLE INSULATED DUCTS SHALL BE MAXIMUM 5'-0" LONG AND SHALL MEET
INSTALLATION AND MATERIAL REQUIREMENTS OF LOCAL CODES.
14. THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE TEMPERATURE
CONTROL SYSTEM TO INCLUDE: PANELS, MODULES, RELAYS, WIRING, THERMOSTATS,
SENSORS, DAMPERS, ACTUATORS AND ALL MISCELLANEOUS ITEMS AS REQUIRED TO FULFILL
THE DESIGN INTENT AS INDICATED ON THE PLANS AND IN THE CODED NOTES.
15. ALL TEMPERATURE CONTROLS, FIRE ALARM COMPONENTS, EQUIPMENT NAMEPLATES,
LABELS, OR COLOR CODED COMPONENTS SHALL BE MASKED DURING PAINTING TO PREVENT
DAMAGE FROM OVER -SPRAY OR OBSCURING INFORMATION.
16. ALL LOW VOLTAGE WIRING AND CONDUIT REQUIRED FOR MECHANICAL EQUIPMENT SHALL BE
FURNISHED AND INSTALLEDBy MECHANICAL CONTRACTOR. CONTRACTOR SHALL BE
RESPONSIBLE FOR COORDINANG WITH ELECTRICAL CONTRACTOR ALL WIRING AND CONDUIT
REQUIRED FOR EQUIPMENT OERATION AND CONTROL
17. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT THE MECHANICAL EQUIPMENT
COMPONENTS ARE INSTALLED, AT LOCATIONS AND ELEVATIONS WHICH MAKE THEM READILY
ACCESSIBLE FOR ROUTINE MAINTENANCE WITHOUT REQUIRING ANY EXTRAORDINARY
MEASURES.
MECHANICAL PLAN
1 /4"=1'-O"
MECHANICAL CODED NOTES;
0 OWNER SHALL FURNISH AND CONTRACTOR SHALL INSTALL A "LIGHT STAT"
PROGRAMMABLE THERMOSTAT WITH SUB -BASE AND REMOTE
TEMPERATURE SENSOR AT 5'-0" A.F.F. COORDINATE EXACT LOCATION
WITH TENANTS CONSTRUCTION MANAGER. THERMOSTATS TO BE MOUNTED
ON LIGHT STAT CONTROL PANEL LIGHTSTAT THERMOSTATS AND SENSORS
ARE TO CONTROL HEATING AND COOLING MODES.
O RTU -1 - NEW ROOFTOP UNIT INSTALLED IN SAME LOCATION ,AS EXISTING
UNIT. MECHANICAL CONTRACTOR SHALL REMOVE AND DISPOSE OF EXISTING
ROOFTOP UNITS AND SHALL FURNISH AND INSTALL A ROOF MOUNTED
ELECTRIC COOLING/ GAS HEATING HVAC UNIT. SEE ROOF TOP UNIT
SCHEDULE FOR FURTHER INFORMATION. UNIT TO SIT ON EXISTING CURB
AND ROOF OPENING. UNIT SHALL BE FURNISHED WITH TWO SETS OF
STANDARD FILTERS. CONTRACTOR TO REPLACE FILTERS PRIOR TO TURNING
STORE OVER TO TENANT. ALL ROOF WORK INVOLVED WITH SETTING OF
THE ROOF CURB AND UNIT SHALL BE DONE BY THE LANDLORD'S ROOFING
CONTRACTOR AT THE G.C. EXPENSE UNLESS NOTED OTHERWISE. GENERAL
CONTRACTOR SHALL PROVIDE ANY ADDITIONAL STRUCTURAL STEEL
REQUIRED TO SUPPORT RTU, PER LANDLORD'S REQUIREMENTS. COORDINATE
LOCATIONS OF ROOF TOP UNITS AND EXISTING ROOF EQUIPMENT WITH
LANDLORD. PROVIDE CLEAR ACCESS TO ALL EQUIPMENT AND
CODE -REQUIRED CLEARANCES FOR OUTSIDE AIR INTAKES. STENCIL
TENANTS NAME AND SPACE NUMBER ON RTU. UNIT SHALL BE HORIZONTAL
DISCHARGE . DUCTED DOWN INTO SPACE THROUGH EXISTING ROOF OPENING.
FIELD VERIFY EXACT: SIZE AND LOCATION OF EXISTING ROOF CURB AND
OPENING.
0 THE CONTRACTOR SHALL FURNISH AND INSTALL CONDENSATE DRAINS FROM
HVAC UNIT AS SHOWN ON PLANS. MINIMUM DRAIN SIZE TO BE 1" OR AS
SPECIFIED ON PLANS. CONDENSATE DRAIN TO BE TRAPPED WITH A
MINIMUM 5" TRAP DEPTH. DRAINS SHALL BE EXTENDED AT A SLOPE OF
1" PER 40'. ROUTE RTU CONDENSATE DRAINS TO SPLASH BLOCK ON
ROOF OR NEAREST ROOF DRAIN AS REQUIRED BY LANDLORD AND LOCAL
CODE.
® PROVIDE FULL SIZE DUCT CONNECTION TO RETURN AIR WITH ELBOW FOR
SOUND ATTENUATION OF RETURN AIR, AND WIRE MESH AT OPENING.
O SMOKE DETECTOR IN RETURN AIR DUCT SHALL SHUT DOWN UNIT SUPPLY
FAN AND SIGNAL THE LANDLORD FIRE ALARM SYSTEM UPON SENSING
SMOKE. SMOKE DETECTOR TO BE FURNISHED BY ELECTRICAL CONTRACTOR
AND INSTALLED BY MECHANICAL CONTRACTOR. WIRING TO FIRE ALARM
SYSTEM BY ELECTRICAL CONTRACTOR. COORDINATE REQUIREMENTS WITH
LANDLORD.
® MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL A BROAN
EXHAUST FAN (120V., 1 PH., 60 HZ) COMPLETE WITH INTEGRAL
BACKDRAFT DAMPER AND ON-OFF SWITCH. EXHAUST CAPACITY SHALL BE
75 CFM AT .5" S.P. CONTRACTOR TO FURNISH AND INSTALL EXHAUST
DUCT, AND ACCESSORIES AS REQUIRED INCLUDING SPEED CONTROLLER
CONCEALED A'n ArrrcctRLL, CONNECT TO EXISTING LANDLORD EXHAUST
CONNECTION IN SPACE. FIELD VERIFY EXACT SIZE AND LOCATION.
O7 CONTRACTOR SHALL UNDERCUT DOOR 1" FOR AIR RETURN.
® PROVIDE NEW ELECTRONIC THERMOSTAT AND SENSOR FOR VAV BOX, AND
ASSOCIATED WIRING, ETC. TO BE THE SAME MANUFACTURER AS VAV BOX.
O9 VAV-1
MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL A SERIES FAN
POWERED, VARIABLE -AIR -VOLUME (VAV) BOX WITH ELECTRIC HEATING, ECM
MOTOR, AND ELECTRONIC CONTROL WITH AUTOCHANGE-OVER. VAV BOX
SHALL BE CONNECTED TO THE MAIN AIR DISTRIBUTION SYSTEM WITH DUCT
SIZES AS SHOWN. VERIFY BOX INLET AND OUTLET CONNECTION SIZES AND
INCLUDE DUCT TRANSITIONS AND FLEX DUCT CONNECTIONS IN BID. SEE
VARIABLE AIR VOLUME BOX SCHEDULE FOR FURTHER INFORMATION. MOUNT
VAV BOX AT MAXIMUM POSSIBLE HEIGHT ABOVE FINISHED FLOOR.
<D4UGHTSTAT SUPPLY AIR SENSOR MOUNTED IN DUCTWORK.
11 HORIZONTAL DISCHARGE DUCTWORK TO DROP DOWN THROUGH ROOF
THROUGH EXISTING CURB AND OPENING. PROVIDE WEATHERPROOF
INSULATED ENCLOSURE AROUND DUCTS AND ROOF OPENING TO MATCH
EXISTING INSTALLATION. FIELD VERIFY EXACT SIZE AND LOCATION OF
EXISTING CURB AND OPENING TO BE REUSED.
FIELD VERIFY ALL CONDITIONS BEFORE BID.
!SEPARATE PERMIT
REQUIRED FOR:
0 Mechanical
glitleotrical
el6Numbing
as Piping
City of Tukwila
EU!L. 3ING DIVISION
REVISIONS
No changes sha'I be made to the scope
of work witho#.t prior approval of
Tukwila ,lila Building Division.
r avisions will require a new plan submittal
and may include additional plan review fees.
FILE COPY
Permit No. IA (S-1$4)
firm Inflow approval is subject to errors and omissions.
k; 4 of construction documents does not authorize
, or<
of any adopted code or ordinance. Receipt
o►iipproveci Field Copy and cot ons isadmowledged:
BY
V)"3
City OfTukwila
BUILDING DIVISION
FIELD VERIFY ALL CONDITIONS
DESIGN DRAWINGS ARE SCHEMATIC. THIS CONTRACTOR SHALL VISIT THE SITE
PRIOR TO BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING FIELD
CONDITIONS. THIS CONTRACT SHALL INCLUDE ALL LABOR AND MATERIALS
NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING CONDITIONS.
THE CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER
PRIOR TO BIDDING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN
AND INCLUDE IN HIS BID ALL COSTS TO MEET THE DESIGN INTENT.
CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER AFTER
BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT CONTRACTORS COST.
BIDDING CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES
AND ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL
W iRK INSTALLED IN STRICT ACCORDANCE WITH GOVERNING CODES, THE PLANS
AND SPECIFICATIONS NOT WITHSTANDING. THE CONTRACTOR SHALL ALERT
ARCHITECT, ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES BETWEEN
GOVERNING CODES AND DESIGN INTENT.
SYMBOL LEGEND
SYMBOL
DESCRIPTION
SYMBOL
DESCRIPTION
SUPPLY
SHADING
DUCT MOUNTED
SIDEWALL.'MOUNTED
RETURN
CEILING
RETURN
SUPPLY
SIMILAR
SUPPLY
SIMILAR
DEMO EXISTING
DEVICE
EXISTING
RE -USE
CONNECT
AIR DIFFUSER
DENOTES BLANK -OFF
AIR GRILLE OR DUCT
DIFFUSER
SUPPLY OR
AIR LINEAR DIFFUSER
MOUNTED SUPPLY OR
MR LINEAR DIFFUSER
AIR DUCT RISE
FOR RETURN AIR
AIR DUCT DROPF.D.
FOR RETURN AIR
DUCT AND AIR
TO EXISTING
(� �\ L I
\ /
ROOF MOUNTED EQUIPMENT
AS NOTED
CEILING EXHAUST FAN GRILLE
-DENOTES
S -DENOTES SENSOR
TURNING VANES
DUCT TRANSITIONS
BRANCH DUCT WITH SPIN -IN
FITTING AND VOLUME DAMPER
- FIRE DAMPER
DUCT SMOKE DETECTOR
MECHANICAL CONTRACTOR
ELECTRICAL CONTRACTOR
HIGH SIDE WALL
LOW SIDE WALL
Or
0
/
pRETURN
/T
\ I
=
O
JJ
JJJ
;
JTV
MOM
_/
i
\_
i
A
y +
T
X +
0
alt
M.C.
E.C.
HSW
LSW
X„. � %
'
E
R
0
x``113-136
CITREVOF iIUK WiLp
VERIFY ALL CONDITIONS IN FIELD PRIOR TO BIDS. ,�<<<ma
PERMIT CENTER
M -Engineering
750 Brooksedge Blvd.
Westerville, Ohio 43081
phone: 614.839.4639
fax: 614.839.P 22
WWW. MENGINEERING. US. COM
All rights reserved. No part of these drawings
or specifications may be copied, reproduced
or used in connection with any work, other
than the specific project for which they have
been prepared, without prior written
authorization from the Architect.
ENGINEER OF RECORD:
ICFEW
Southcenter Mall
633 Southcenter Mall
Space No. 676
Seattle, WA 98188
Level: Ground Floor
Project No. 1339
Project No. 13411114
NO.
DATE
ISSUE
07-17-13
Issue for Permit
07-17-13
Issue for Bid
07-17-13 Issue for LL & Client
Review
REVIEWED FOR
:ODE COMPLIANCE
APPROVED
AUG 02 2013
gie
LCi#y of Tukwila
BUILDING DIVISION
Mechanical Plan
M-100
HVAC LOAD CALCULATIONS
Design Parameters:
City Name - _.Seattle IAP
Location Washington
Latitude 47.5 Deg.
122.3 Deg.
449.0 ft
85.0 °F
Summer Coincident VL@tilb 65.0 °F
Summer Daily Range 18.3 °F
Winter Design Di9ulb 23.0 °F
Winter Design VVaulb ._ _ 19.2 °F
Atmospheric Clearness Number __ 1.05
Average Ground Reflectance. 0.20
Soil Conductivity - _ 0.800 BTU/(hift °F)
Local Time Zone (GMT -My hours) 8.0 hours
Consider Daylight Savings Time- No
Simulation Weather Data _ __ Seattle IAP (TM2)
Current Data is __..2001 ASHRAE Handbook
Design Cooling Months. January to December
Longitude
Elevation
Summer Design DQulb
Air System Information
Air System Name Total Load
Equipment Class _.. PKG ROOF
Air System Type. SZCAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM Sum of space airflow rates
Space CFM Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 13.6 Tons
Total coil load 163.7 MBH
Sensible coil load 159.0 MBH
Coil CFM at Jun 13QQ 5465 CFM
Max block CFM 5465 CFM
Sum of peak zone CEM ...5465 CFM
Sensible heat ratio 0.971
ft2/Ton 346.4
BTU/(hift2) 34.6
Water flow @ 10.0 °F rise N/A
Central Heating Coil Sizing Data
Max coil load 1325 MBH
Coil CFM at Des Htg 5465 CFM
Max coil CFM. 5465 CFM
Water flow @ 20.0 °F drop __. N/A
Supply Fan Sizing Data
Actual max CFM 5465 CFM
Standard CFM 5377 CFM
Actual max CFM/ft2 1 16 CFM/ft2
ZONE LOADS
Window & Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions
Ceiling
Overhead Lighting
Task Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
» Total Zone Loads
Zone Conditioning
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Return Fan Load
Ventilation Load
Supply Fan Load
Space Fan Coil Fans
Duct Heat Gain / Loss
» Total System Loads
Central Cooling Coil
Central Heating Coil
» Total Conditioning
Key:
Number of zones 1
Floor Area 4727.0 ft2
Location Seattle IAP, Washington
Calculation Months . Jan to Dec
Sizing Data Calculated
Load occurs at Jun 1300
OA DB/WB. 82.0/64.4°F
Entering DB / WB. 86.6 / 67.1 °F
Leaving DB / WB 59.2 / 57.4 °F
Coil ADP 56.1- °F
Bypass Factor 0.100
Resultin0H 56 %
Design supply temp - 56.0 °F
Zone Tstat Check 1 of 1 OK
Max zone temperature deviation Q.0 °F
Load occurs at Des Htg
BTU/(hift2) _ 28.0
Ent. DB / Lvg DR 57.9 / 80.8 °F
Fan motor BHP - 1 59 BHP
Fan motor kW 1.19 kW
Fan static 1.00 in wg
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1300 HEATING DATA AT DES HTG
COOLING OA DB / WB 82.0 °F / 64.4 °F HEATING OA DB / WB 23.0 °F / 19.2 °F
Sensible Latent Sensible Latent
Details (BTU/hr)
O ft2 0
Oft2 0
4727 ft2 33153
Oft2 0
O ft2 0
O ft2 0
4727 ft2 0
O ft2 0
Oft2 0
2321 W 4195
8608 W 22225
4550 W 15525
53 9329
- 0
- 0
10% /10% 8443
92869
83373
0% 0
70% 77358
30% 2376
5465 CFM 0
1274 CFM -8110
5465 CFM 4052
0
0% 0
159048
- 159048
0
159048
(BTU/hr) Details
O ft2
0ft2
4727 ft2
O ft2
O ft2
0 ft2
4727 ft2
Off
O ft2
0
0
0
0
10695
0
0
1070 10%
11765
11765 -
0
0
0
5465 CFM
-7067 1274 CFM 61699
5465 CFM -4052
- 0
0% 0
4698 - 132508
4700 - 0
132508
4700 132508
Positive values are htg loads
Negative values are clg loads
(BTU/hr) (BTU/hr)
0
71987
0
0
0
0
0
0
0
0
0
0
0
0
7199
79186
74860
0
0
0
0
Positive values are clg loads
Negative values are htg loads
0
0
0
0
0
0
0
0
0
VENTILATION REQUIREMENTS
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 1274 CFM
2. Space Ventilation Analysis Table
Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft2) Occupants(CFM) (CFM/person) (CFM/ft2) (CFM) (% of supply) (CFM)
Zone 1
JCrew Non Sales 1 959.0 4.8 1298.8 0.00 0.15 0.0 0.0 143.9
JCrew Sales 1 3768.0 50.2 4166.5 0.00 0.30 0.0 0.0 1130.4
Totals (incl. Space Multipliers) 5465.3 1274.3
METAL GAUGE FOR DUCTWORK TO BE AS FOLLOWS:
ROUND DUCT 3 TO 19 INCHES TO BE 26 GAUGE
RECTANGULAR DUCT UP TO 12 INCHES WIDE TO BE 26 GAUGE
RECTANGULAR DUCT 13 TO 30 INCHES WIDE TO BE 24 GAUGE.
RECTANGULAR DUCT ABOVE 30 INCHES WIDE TO BE 22 GAUGE.
STEEL STRAP HANGER
DUCTWORK
SELF -TAPPING, SHEET METAL SCREW
HANGER SPACING
DUCT FACE AREA FROM 0 TO 4 SQ. FT. HANGERS 98" O.C. MAX
DUCT FACE AREA FROM 4 TO 10 SQ. FT. HANGERS 72" O.C. MAX
DUCT FACE AREA FROM 10 AND GREATER HANGERS 48" O.C. MAX
WHERE DUCTS ARE LESS THAN 2 SQ. FT. IN FACE AREA, HANGERS
SHALL BE NOT LESS THAN 1"x1/16" STRAP STEEL
WHERE DUCT ARE GREATER THAN 2 SQ. FT. IN FACE AREA. HANGERS
SHALL BE NOT LESS THAN 1"x1/8" STRAP STEEL
WHERE DUCT ARE 8 SQ. FT. IN FACE AREA. HANGERS SHALL BE
BRACED BY 1'x1"x1/8" STEEL ANGLES ALL AROUND, SPACED NO
MORE THAN FOUR FEET ON CENTERS.
WHERE DUCTS ARE OVER 48" WIDE. THE HANGERS SHALL BE BROUGHT
DOWN UNDER THE DUCT SIDES 4" AND FASTENED TO THE BOTTOM.
SECURE HANGERS TO STRUCTURAL MEMBERS OR TO UNITSTRUT
BETWEEN MEMBERS. DO NOT ATTACHE TO DECK.
DUCT SUPPORT SCHEMATIC
NTS
ALL DUCT LINER TRANSVERSE
EDGES TO BE COATED W/
ADHESIVE IN ACCORDANCE
W/ SMACNA STANDARDS
(TYP.)
MAIN DUCT
PROVIDE INTERNAL
LINER OR EXTERNAL
WRAP INSULATION AS
SPECIFIED
FLANGED AND GASKETED JOINT
OR DUCT CONNECTION AND RE -
ENFORCEMENT IN ACCORDANCE
W/ SMACNA 2" W.G. CLASS,
SEAL NON-GASKETED TRANS-
VERSE JOINTS IN ACCORDANCE
W/ SMACNA CLASS "C" (TYP.)
TAPE. DOWN EXTERNAL
INSULATION
FASTEN W/ MIN. (3)
SHT. MTh. SCREWS,
SEAL W/ DUCT TAPE
AND MASTIC
TYP. ROUND DUCT TAKE
NTS
ROOFTOP UNIT SCHEDULE
F
zUNIT
aa
NUMBER
TRANE
MODEL #
cn
m z
00
z F-
EER
SUPPLY FAN
VOLTAGE
HEAT
PUMP
OUTPUT
ELEC
HTG.
COIL
TOTAL
CLG
SENSIBLE
CLG
;I O.A.
CFM
NOTES
HP
m m
z c)
SP
RPM
1
RTU -1
WSH180E3
15
10.6
5
5500
1.0
3450
208V/30
93
13.5 KW
186
163
; 1300
Q(2) CD®
208 3
000
•
A
•
A
00000
SD -3
TITU
OMNIS
12"X12"
6"O
•
•
•
1
A
NOTE:
1. UNITS SHALL BE HI -EFFICIENCY, EER AS SHOWN IN SCHEDULE.
2. PROVIDE THE FOLLOWING FACTORY INSTALLED ACCESSORIES
- ECONOMIZER WITH REFERENCE ENTHALPY CONTROL
- THROUGH THE BASE ELECTRIC/GAS CONNECTIONS.
- UNIT MAIN POWER DISCONNECT SWITCH.
- FIELD POWERED CONVENIENCE OUTLET.
- HINGED ACCESS DOORS.
- HEAT PUMP UNIT WITH SECOND STAGE HEAT ELECTRIC COIL 13.5 KW
3. PROVIDE THE FOLLOWING FIELD INSTALLED ACCESSORIES.
- KNOCKDOWN ROOFCURB.
- POWER EXHAUST
- PROGRAMMABLE NIGHT SETBACK THERMOSTAT.
- HORIZONTAL DISCHARGE
4. START-UP AND ONE YEAR LABOR WARRANTY SHALL BE PROVIDED BY INSTALLING
CONTRACTOR.
AIR
FLOW
CONICAL OR BELLMOUTH SPIN -
IN FITTING, SEAL AIRTIGHT W/
MASTIC
MANUAL BALANCING DAMPER
ROUND RIGID DUCT
1" WRAPPED INSULATION
TO S.A. MAIN INSULATED ROUND
DUCT
VOLUME
DAMPER
FLEXIBLE CONNECTIO
(MAX. 5 FT.) -
ALL HANGER WIRES TO STRUCTURAL SUPPORT
MUST BE VERTICAL (TYP)
PROVIDE SUPPORT FROM STRUCTURAL SUPPORTS
ABOVE. DO NOT REST AIR, DEVICE ON CEILING.�
PROVIDE 16 GA. X 1 1/2 IN. STEEL CHANNELS (WITHti
9/16 IN. MINIMUM ANGLES) AS NECESSARY, AND METAL I1 I I I
SCREWS FORM INSIDE PER MANUFACTURER'S PRINTED'
INSTRUCTIONS
OFF SCHEMATIC
SUPPLY AIR
DIFFUSER
STRAP CLAMP
(TYPICAL)
INSTALL DAMPER AND EQUALIZING GRID
PER AIR DEVICE SCHEDULE AND
MANUFACTURER'S PRINTED
INSTRUCTIONS. INSTALL ALL SHEET
METAL SCREWS FROM INSIDE OF NECK.
DRYWALL
CEILING
SURFACE MOUNT WITH
NO EXPOSED FASTENERS
ROUND DIFFUSER MOUNTING SCHEMATIC
NTS
8" OR 10"0 FLEX
(5' MAX. LENGTH
,11 or'
YOUNG REGULATOR BOWDE
CABLE CONTROLS 5020CC
DAMPER WITH 270/275
DRIVE CONTROL KIT. OR
EQUAL
YOUNG REGULATOR DAMPER
WITH CABLE TO FACE OF
REGISTER
PLENUM PROVIDED
BY MECH. CONTR.
TRANSITION AS REQUIRED
LINEAR DIFFUSER
SCREW DRIVER
ADJUSTMENT AT FACE
OF DIFFUSER
FIELD COORDINATE INSTALLATION
WITH GENERAL CONTRACTOR.
LINEAR DIFFUSER SCHEMATIC
B NTS NOTES
1. DIFFUSER SHALL APPEAR CONTINUOUS.
2. ALL CORNERS SHALL BE MITERED.
VANES PRE -ASSEMBLED ON RUNNER PLATES.
USE GALVANIZED VANES FOR GALVANIZED
OR ALUMINUM DUCTS.
PLATE SAME GAUGE AS DUCT.
DUCT SIZE OVER 36"X36"
SQ. ELBOW WITH TYPE "A"
DOUBLE THICKNESS
VANES
R=2"
DUCT SIZE 36"X36" OR
UNDER SQ. ELBOW WITH
SINGLE THICKNESS VANES
TURNING VANE SCHEMATIC
NTS
VARIABLE AIR VOLUME BOX SCHEDULE
TAG
MANUFACTURER &
MODEL
PRIMARY
AIR INLET
SIZE ("0)
BOX PRIMARY CFM
FAN (SERIES)
ELECTRIC HEATING COIL
NOTES
LIMITATIONS
DESIGN OPERATION
CFM
E.S.P.VOLTS
(IN WC)
HP
PHASE
KW
STEPS
VOLTS
PHASE
MAX.
MIN.
DESIGN
COOLING
DESIGN
HEATING
VAV-1
TRANE VSEF
10
700
300
650
650
650
0.5
0.25
120 1
5
2
208 3
000
NOTES;
1. MINIMUM STATIC PRESSURE DROP ACROSS THE VAV BOX FOR PROPER OPERATION SHALL BE BETWEEN 0.1' AND 0.15", AS
TESTED PER ARI 880.
2. PROVIDE FACTORY MOUNTED ELECTRIC HEATER AIR FLOW SWITCH, POWER FUSE AND DISCONNECT SWITCH.
3. PROVIDE ELECTRONIC CONTROLS, REVERSE ACTING TYPE WITH MAGNETIC CONTACT FOR ELECTRIC HEATING COIL
THERMOSTAT CONTROLS BY SAME MANUFACTURER AS UNIT.
AIR DEVICE SCHEDULE
NOTES
1. SYMBOL KEY - 4. VOLUME DAMPER -
FIRST LETTER: S -SUPPLY R -RETURN E-EXH T -TRANSFER FACTORY FURNISHED. OPPOSED BLADE OR BUTTERFLY
SECOND LETTER: D -DIFFUSER R -REGISTER G -GRILLE WHERE AVAILABLE. ADJUSTABLE FROM FACE.
2.PROVIDE OPTIONAL DIRECTIONAL BLOW FEATURE FOR 5. BORDER STYLE -
OTHER THAN 4 -WAY. "A" SURFACE MOUNTED
3. FINISH -"B" LAY -IN, PROVIDE WITH PLASTER FRAME
"A" WHITE FOR DRYWALL CEILING MOUNTING.
"B" WHITE - G.C. TO FIELD PAINT "C" LAY -IN FRAME FOR T -BAR CEILING.
TO MATCH CEILING OR WALL WITH ENAMEL FINISH. 6. PROVIDE BOOT FOR DUCT MOUNTING.
SYMBOL
(1)(2)
MANUFACTURER/
CATALOG
NUMBER
NOMINAL SIZE
MOUNTING
MATERIAL
FINISH
(3)
DPR.
(4)
BORDER
(5)
REMARKS
MOD.
NECK
CLG.
OTHER
STEEL
ALUM.
SD -1
AIR
22"0
10"0
•
•
A
•
A
00
SD -2
TUS
FL -1O -HT
48" LENGTH
8"0
•
•
A
•
A
00000
SD -3
TITU
OMNIS
12"X12"
6"O
•
•
•
CONDENSING UNITS -
A
•
A
00
SD -4
-MS
OMNI
12"X12"
8"0
•
•
•
•
A
•
A
00
SD -5
TMSS
24'X24"
8"0
•
411
STRUCTURAL SUPPORTS FOR RTU•
AS REQUIRED.
A
•
C
00
•
SEE CODED NOTES
1
•
•
SEE CODED NOTES
DIFFUSERS AND GRILLES
RG -1 '
TITUS 350 RL
12"x12"
10"x10"
•
•
DIFFUSERS/GRILLES FIRE DAMPERS
A
•
A
0
RG -2
3T50 RL
24"X12"
2,2'x10"
•
•
A
•
B
00
RG -3
mus
350 RL
24"X24"
22"x22"
•
•
•
LOW PRESSURE DUCTWORK
A
•
C
0
1
EQUALS SHALL BE BY PRICE OR KRUEGER. G.C. TO CONFIRM AVAILABILITY WITHIN CONSTRUCTION SCHEDULE.
PROVIDE AIR DEVICES WITH SHORTEST LEAD TIME.
2 ALL SURFACE MOUNTED AIR DEVICES SHALL BE INSTALLED WITH NO EXPOSED FASTENERS.
3 PROVIDE FRAME & BORDER TYPE ?66 PLENUM AND ALL HARDWARE. PROVIDE WITH END BORDERS.
4 INSTALL RECTANGULAR DUCT ROTO TWIST BY METROPOLITAN AIR RT -150 DAMPER WITH CABLE CONTROLS
MOUNTED INSIDE PLENUM OF SLOT- DIFFUSER WITH PLENUM BRACKET. EQUALS BY YOUNG'S.
5 USE POSITION 1 SETTING
6 PROVIDE LENGTH OF AIR DEVICE AS SHOWN ON ARCHITECTURAL SHEETS. PROVIDE CONTINUOUS INSULATED
PLENUM WITH MULTIPLE 8" INLETS AS SHOWN FOR SUPPLY AIR.
MECHANICAL/PLUMBING RESPONSIBILITY SCHEDULE
ITEM
FURNISHED BY
-�-
INSTALLED BY
REUSE
EXISTING
N/A
REMARKS
TENANT
ANDLORD
CONTR.
ANDLORD
CONTR.
AIR HANDLING UNITS (WSHP)
•
STRUCTURAL & VIBRATION SUPPORTS
FOR AHU AS REQUIRED (WSHP)
•
AHU MIXING BOX AND MIXING BOX
MOTOR OPERATED DAMPERS
•
AHU MIXING BOX MOTOR OPERATED
DAMPER ACTUATOR
•
CONDENSING UNITS -
•
ROOF TOP UNITS
•
•
ROOF CURB AND/OR CURB ADAPTER
FOR RTU AS REQUIRED
•
•
•
SEE CODED NOTES
STRUCTURAL SUPPORTS FOR RTU•
AS REQUIRED.
•
•
SEE CODED NOTES
V.A.V. BOXES
•
•
SEE CODED NOTES
DIFFUSERS AND GRILLES
•
•
SEE CODED NOTES
DIFFUSERS/GRILLES FIRE DAMPERS
•
WALL FIRE DAMPERS AND/OR
COMBINATION SMOKE/FIRE DAMPERS
•
HYDRONIC PIPING
•
LOW PRESSURE DUCTWORK
•
•
SEE CODED NOTES
HIGH/MEDIUM PRESSURE DUCTWORK
•
TEMPERATURE CONTROL SYSTEM
•
•
SEE CODED NOTES
RELIEF AIR/MAKE UP AIR
MOTOR OPERATED DAMPERS
•
RELIEF AIR/MAKE UP AIR
MOTOR OPERATED DAMPER ACTUATORS
•
SMOKE DETECTOR(S) IN RETURN
AND/OR SUPPLY AIR DUCT
•
•
ZONE DAMPERS
•
DUCT HEATER(S)
•
UNIT/BASEBOARD HEATER(S)
•
RETURN AIR FAN
•
OUTSIDE AIR MOTORIZED DAMPER &
DUCTWORK
•
RELIEF AIR FAN OR HOOD
•
TOILET EXHAUST FAN(S)
•
•
SEE CODED NOTES
TOILET EXHAUST DUCTWORK
WALL OR ROOF CAP
•
•
•
SEE CODED NOTES
AIR BALANCE REPORT
•
AABC OR NEBB CERTIFIED
AS -BUILT DRAWINGS
5
PLUMBING FIXTURES
•
•
SEE CODED NOTES
SAN, CW, HW, PIPING AND
WATER METER
•
•
SEE CODED NOTES
SPRINKLER PIPING AND HEADS
•
•
SPRINKLER DRAWINGS AND
CALCULATIONS AND HUNG
•
•
GENERAL NOTE
REFERENCE. ALL ITEMS LISTED HERE ARE SPECIFIED AND DETAILED
ENCOUNTERS ITEMS THAT ARE CONTRADICTORY THEN IT IS HIS
MANAGER SO THAT THESE ITEMS CAN BE CLARIFIED
THIS SCHEDULE IS INTENDED AS A "QUICK"
ON THESE DRAWINGS. IF THE CONTRACTOR
RESPONSIBILITY TO INFORM TENANT'S CONSTRUCTION
FOR THE CONTRACTOR.
t'U3 j34
REVIEWED FOR
CODE COMPLIANCE
APPROVED
AUG 02 2013
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JUL 2 2013
PERMIT CENTER
M -Engineering
750 Brooksedge Blvd.
Westerville, Ohio 43081
phone: 614.839.4639
fax: 614.839.2222
WWW.MENG/NEERING.USCOM
All rights reserved. No part of these drawings
or specifications may be copied, reproduced
or used in connection with any work, other
than the specific project for which they have
been prepared, without prior written
authorization from the Architect.
ENGINEER OF RECORD:
ICREW
Southcenter Mall
633 Southcenter Mall
Space No. 676
Seattle, WA 98188
Level: Ground Floor
Project No. 1339
Project No. 13411114
NO.
DATE
ISSUE
07-17-13
Issue for Permit
07-17-13
Issue for Bid
07-17-13 Issue for LL & Client
Review
Mechanical
Schedules
Details
M-200
DIVISION 15 - MECHANICAL
SECTION 15000
MECHANICAL GENERAL PROVISIONS
A. GENERAL CONDITIONS I .
SHOP DRAWINGS A.
1. DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND 1.
SUPPLEMENTARY CONDITIONS AND ALL OTHER SPECIFICATION SECTIONS ARE A
PART OF THIS CONTRACT AND APPLY TO THIS AND THE OTHER SECTIONS OF
DIVISION 15.
2. THE CONTRACTOR FOR THIS WORK IS REQUIRED TO READ THE ENTIRE
SPECIFICATIONS AND REVIEW DRAWINGS FOR ALL OTHER TRADES.
3. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING HIS SUBCONTRACTORS WITH
A FULL SET OF BID SET DOCUMENTS (INCLUDING SPECIFICATIONS) AND THE
COORDINATION OF HIS WORK AND INSPECTIONS AND THE WORK AND INSPECTIONS
OF HIS SUBCONTRACTORS WITH ALL OTHER TRADES ON SITE CONFORMING TO THE
GENERAL CONTRACTOR'S TIME SCHEDULE.
4. THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTING HIS BID TO
DETERMIINE CONDITIONS AFFECTING THE WORK. BIDS SHALL SERVE AS EVIDENCE
OF KNCAM.EDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE
REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND SPECIFICATIONS.
FAILURE TO VISIT THE SITE DOES NOT RELIEVE THE CONTRACTOR ODF
RESPONSIBILITY IN_ PERFORMANCE OF WORK.
5. WHEN USED, THE TERM 'PROVIDED BY CONTRACTOXR' SHALL BE INTERPRETED AS
MEANING 'FURNISHED AND INSTALLED' WITH THE EXCEPTION WHERE ITEMS ARE
'PROVIDED' BY TENANT' WHICH MEANS 'FURNISHED ONLY' (INSTALLED BY
CONTRACTOR), EXCEPT AS SPECIFICALLY NOTED OTHERWISE.
B. GENERAL REQU I REMENNTS
1. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT,
SERVICES, TOOLS. TRANSPORTATION, INCIDENTALS AND DETAILS NECESSARY TO
PROVIDE A COMPLETE AND FULLY FUNCTIONAL MECHANICAL SYSTEM AS SHIOWN ON
THE DRAWINGS, CALLED FOR IN THE SPECIFICATIONS, AND AS REQUIRED BY JOB
CONDITIONS. ALL WORK NOT SPECIFICALLY NOTED AS BEING BY THE LANDLORD
SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. CLOSELY COORDINATE
THE ENTIRE INSTALLATION WITH THE LANDLORD, AS REQUIRED. FIELD VERIFY
THP EXACT TYPE, SIZE AND LOCATION, ETC. OM: EXISTING PIPE AND DUCTS IN
THE TENANT SPACE PRIOR TO BID.
2. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER
AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SWILL BE PROVIDED EVEN
THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY MATERIAL OR LABOR
WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE
SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK,
AND WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE
PROVIDED AS PART OF CONTRACT.
3. WHERE TIE DRAWINGS OR SPECIFICATIONS CALL FOR ITEMS WHICH EXCEED CODES
OR THE LANDLRD'S TENANT CRITERIA, THE CONTRACTOR IS STILL RESPONSIBLE
FOR PROVIDING THE SYSTEM AS DESIGNED AND DESCRIBED ON�N THESE DRAWINGS,
UNLESS SPECIFICALLY NOTED OTHERWISE.
4. ALL MECHANICAL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE
FOR OPERATING. SERVICING, MAINTAINING, AND REPAIRING. THE CONTRACTOR
IS RESPONSIBLE FOR PROVIDING SUFFICIENT ACCESS TO ALL EQUIPMENT FOUR
SERVICE.
2.
SUBMIT SIX COPIES OF MATERIAL LISTS AND SHOP DRAWINGS FOR ALL
EQUIPMENT AND DUCT FABRICATION DRAWINGS TO THE TENANT'S CONSTRUCTION
MANAGER FOR APPROVAL PRIOR TO ORDERING EQUIPMENT. SUBMISSIONS MUST
BE EARLY ENOUGH TO ALLOW THE TENANT'S CONSTRUCTION MANAGER EIGHT
WORKING DAYS FOR REVIEW WITHOUT CAUSING DELAYS OR CONFLICTS TO THE
JOB'S PROGRESS. SUBMITTALS SHALL BE IN ACCORDANCE WITH THE GENERAL
CONDITIONS USING THE MANUFACTURER'S LISTED ON THE DRAWINGS. SHOP
DRAWINGS SHALL INCLUDE ALL DATA THAT PERTAINS TO THE REQUIREMENTS SET
FORTH ON THE DRAWINGS AND IN THE SPECIFICATIONS:. THE SUBMITTAL SHALL
INCLUDE BUT NOT LIMITED TO CUTS OR CATALOGS INCLUDING DESCRIPTIVE
LITERATUE AND CHARACTERISTICS OF EQUIPMENT SHALL SHOW MAJOR
DIMENSIONS, ROUGHING -IN DATA, CAPACITY, CURVES,; PRESSURE DROP, CODE
COMPLIANCE, MOTOR AND DRIVE DATA AND ELECTRICALjDATA. OBSERVE SPECIAL
INSTRUCTIONS WHEN REQUIRED. SUBMITTALS SHALL BEAR THE STAMP OF THE
GENERAL AND.SUB-CONTRACTOR SHOWING THAT HE HAS REVIEWED AND CONFIRMED
THAT THEY ARE IN CONFORMANCE WITH THE CONTRACT DRAWINGS AND
SPECIFICATIONS OR INDICATE WHERE EXCEPTIONS TAKEfPLACE. LACK OF SUCH
CONTRACTOR'S REVIEW AND APPROVAL WILL BE CAUSE FOR REJECTION WITHOUT
REVIEW BY TENANT'S CONSTRUCTION MANAGER. ALL SHOP DRAWINGS MUST
APPEAR IN THE OPERATION AIB. MAINTENANCE MANUALS LEFT ON SITE AT JOB
COMPLETION.`
TENANTS CONSTRUCTION MANAGERS REVIEW OF SHOP DRAWINGS OR SCHEDULES
SHALL'NOT RELIEVE THE CONTRACTOR FROM RESPONLSIBI'LITY FOR ERRORS,
OMISSIONS OR OTHER DEFICIENCIES OR DEVIATIONS IN THE SHOP DRAWING FROM
THE CONTRACT DRAWINGS AND SPECIFICATIONS.
. RECXRRD DRAWINGS
K.
5. THE CONTRACTOR SHALL DO ALL CUTTING, CORE DRILLING, CHASING OR
CHANNELING AND PATCHING REQUIRED FOUR ANY WORK.UNDER THIS DIVISION. L.
CUTTING SHALL HAVE PRIOR APPROVAL BY THE TENANT'S CONSTRUCTION MANAGER
AND THE LANDLORD. PATCHING SHALL MATCH, FINISH OF SURROUNDING AREA.
C. CODES
1. ALL WORK SHALL BE PERFORMED IN A NEAT PROFESSIONAL MANNER USING GOOD
ENGINEERING PRACTICES. ALL WORK SHALL CONFORM TO THE LANDLORD'S
CRITERIA, THE STATE'S, COUNTY'S, CITY'S AND LOCAL CODES AND
ORDINANCES, SAFETY AND HEALTH CODES, NEPA CODES, ENERGY CODES AND ALL
OTHER APPLICABLE CODES AND REQUIREMENTS. THE CONTRACTOR SHALL INQUIRE M.
INTO AND COMPLY WITH ALL APPLICABLE CODES, (ORDINANCES, AND
REGULATIONS. AFTER CONTRACT IS ISSUED, NO ADDITIONAL COST DUE TO CODE
ISSUES SHALL BE REIMBURSED BY THE TENANT TO THE CONTRACTOXR.
D. LICENSES, PERMITS, INSPECTIONS NII FEES
1. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS,
INSPECTIONS, AND FEES REQUIRED OR RELATED TO HIS WORK.
2. FURNISH TO THE TENANT'S CONSTRUCTION MANAGER ALL CERTIFICATES OF
INSPECTION AND FINAL INSPECTION APPROVAL AT SUBSTANTIAL COMPLETION
DATE CF PROJECT.
E. DRAWINGS
1. DRAWINGS (PLANS, SPECIFICATIONS, AND DETAILS) ARE DIAGRAMMATIC AND .
INDICATE THE GENERAL LOCATION AND INTENT OF THE MECHANICAL SYSTEMS.
BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, ITIS NOT POSSIBLE TO
INDICATE ALL DUCT AND PIPING OFFSETS, FITTINGS AND ACCESSONRIES THAT
MAY BE REQUIRED.
2. THE LAYOUT SHOWN ON THE DRAWINGS IS BASED OHI A PARTICULAR MAKE OF
EQUIPMENT. IF ANOTHER MAKE OF EQUIPMENT IS USED WHICH REQUIRES
MOD I F I CAT I OFN OMR CHANGE OF ANY DESCRIPTION FROM THE DRAW I NGS OMR
SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE AS PART OF THIS
WORK, FOR MAKING ALL SUCH MODIFICATIONS AND CHANGES, INCLUDING THOSE
INVOLVING OTHER TRADES WITH THE COST THEREOF INCLUDED IN HIS BID. IN
SUCH CASE, CONTRACTOR SHALL SUBMIT DRAWINGS AND SPECIFICATIONS PRIOR
TO STARTING WORK SHOWING ALL SUCH MODIFICATIONS AND CHANGES. HIS
PROPOSAL SHALL BE SUBJECT TO THE APPROVAL OF THE TENANT'S CONSTRUCT I O7NN
MANAGER.
F. EXISTING SHELL SPACE CONDITAGS
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE
DEMOLITION OF EXISTING MECHANCIAL WORK SHOWN ON THE MECHANCIAL
DRAWINGS AND THE MECHANCIAL DEMOLITION SHOWN ON THE ARCHITECTURAL
DRAWINGS.
2. THE CONTRACTOR SHALL INCLUDE, AND WILL BE HELD RESPONSIBLE FOR, THE
REMOVAL OF ALL EXISTING FIRE PROTECTION, PLUMBING FIXTURES, PIPING,
HVAC UNITS, REFRIGERANT RECAPTURE, EXHAUST FANS, ETC. AND ASSOCIATED
ROOF CURBS NOT TO BE REUSED ON THIS PROJECT, UNLESS SPECIFICALLY NOTED
OTHERWISE. CONTRACTOR MUST VERIFY WITH THE LANDLORD ALL PRESUMED
ABANDONED EQUIPMENT, PIPES, DUCTWORK, AND EQUIPMENT PRIOR TO REMOVAL.
ROOF' CURBS SHALL BE REMOVED AND THE ROOF PATO2ED UNLESS NOTED FOUR
REUSE OMR RECONFIGURATION ON PLANS. ROOM" PATCHING SHALL BE PERFORMED
AT THE CONTRACTOR'S EXPENSE BY A ROOFING CONTRACTOR APPROVED BY THE
LANDLOXRD. ALL EXTRANEOUS ITEMS IN THE SPACE OR ON THE ROOF (ABOVE
THIS SPACE) NOT APPLICABLE TO THE NEW WORK OMR PART OF THE LANDLORD'S
OR MOTHER TENANT'S ACTIVE SYSTEM MUST BE REMOVED AND ROOF/WALL/FLOO R
PATCHED/REPAIRED TO MATCH EXISTING STRUCTURE. EXISTING ABANDONED
PIPES, DUCTS, OR EQUIPMENT IN THE FLOOR, EMBEDDED IN CONCRETE, OR
OTHERWISE INACCESSIBLE ARE TO BE CUT OFF AND SEALED BELOW OR WITHIN
FLOOR OMR WALL LEVEL WEEN THEY ARE NOT TO BE REUSED IN THIS PROJECT.
I F REQUIRED BY LANDLOXRD OMR CODES, ABA DONED PIPING ANO/OR DUCTWORK
MUST BE REMOVED TO POINT OF ORIGIN. CONFIRM THE EXTENT OF DEMOLITION
PRIOMR TO BID AND INCLUDE IN BID PROPOSAL.
3. ACTIVE LANDLORD OR OTHER TENANT SERVICES ENOUNTERED IN WORK SHALL BE
PROTECTED ANO SUPPORTED. IF EXISTING SERVICES NOT ANTICIPATED REQUIRE
RELOCA IO, CONTACT � TENANT'S iRUCTION ' - IH DIATELY.
ALL COSTS FOR REPAIR OF DAMAGES TO ACTIVE LANDLORD OMR OTHER TENANT
SERVICES DURING CONSTRUCTION SHALL BE PAID FOUR BY THE CONTRACTOR
CAUSING THE DAMAGE.
4. TIE-INS ANO MODIFICATIONS TO EXISTING LANDLORD SERVICES MUST BE DONE
WITH MINIMUM INTERRUPTION OF LANDLOXRD OPERATION AND DURING HOURS
SPECIFIED BY THE LANDLORD. THE CONTRACTOR IS RESPONSIBLE FOR
CONFIRMING EXACT WORKING HOURS OF THIS WORK WITH THE LA DLORD PRIOMR
TO SUBBMITTING HIS BID. THE CONTRACTOR SHALL INCLUDE IN HIS BID, ALL
PREMIUM TIME REQUIRED TO PERFORM MODIFICATIONS DURING OTHER THAN
NORMAL WORKING HOURS. ALL SUCH WORK MUST BE COORDINATED WITH THE
LANDLORD.
G. DISCREPANCIES IN DOCUUMENTS
1. DRAWINGS (PLANS, SPECIFICATIONS. AND DETAILS) ARE DIAGRAMMATIC AND
INDICATE THE GENERAL LOCATION AND INTENT OF THE MECHANICAL SYSTEMS.
WHERE DRAWINGS, EXISTING SITE CONDITIONS, SPECIFICATIONS OR OTHER.
TRADES CONFLICT OR ARE UNCLEAR, ADVISE THE GENERAL CONTRACTOR IN.
WRITING, PRIOR TO SUBMITTAL OF BID. THE GENERAL CONTRACTOR IS
RESPONSIBLE TO ADVISE THE TENANT'S CONSTRUCTION MANAGER, IN WRITING,
OF VARIATIONS TO CONTRACT DOCUMENTS PRIOR TO SUBMISSION OF BID.
OTHERWISE, TENANT'S CONSTRUCTION MANAGER'S INTERPRETATION OF CONTRACT
DOC1 ENTS OR CONDITIONS SHALL BE FINAL WITH NO ADDITIONAL COMPENSATION
PERMITTED.
H. TRADE NAMES AND MIAMFACTURERS
1. WHERE TRADE NAES AND MANUFACTURERS ARE USED OV THE DRAWINGS OR I N THE
SPECIFICATIONS. THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM
STANDARD FOR THE BASE BID. MANUFACTURERS CONSIDERED AS AN EQUAL OR
BETTER IN ALL ASPECTS TO. THAT SPECIFIED WILL BE SUBJECT TO APPROVAL
IN WRITING BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO ACCEPTANCE.
THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND
REPLACEMENT AT THE CONTRACTOR'S EXPENSE.
N.
1.
THE CONTRACTOR SH4ALL_MAINTAIN ONE COPY OF DRAWINGS AND SPECIFICATIONS
ON THE JOB SITE TO RECORD DEVIATIONS FROM CONTRACT DRAWINGS, SUCH AS:
LOCATION OF CONCEALED PIPING VALVES AND DIOTS.
REVISIONS, ADDENDUMS, AND CHANGE ORDERS.
SIGNIFICANT DEVIATIONS MADE NECESSARY BY FIELD CONDITIONS,
,
APPROVED EQU I RMENT SUBSTITUTIONS, AND CONTACTOR S-COORD-I NATI ON
WITH OTHER TRADES. �.
D. EXACT ROUTING OF ALL SANITARY AND DOAESTICIWATER PIPING UDER
FLOOR.
A.
B.
C.
B.
C.
DIVISION 15 - MECHANICAL
SECTION 15200
PLUMBING
SCOPE OF WORK A.
1.
THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT,
SERVICES, TOOLS. TRANSPORTATION AND FACILITIES NECESSARY FOR,
REASONABLY IMPLIED AND INCIDENTAL TO, THE FURNISHING, INSTALLATION,
COMPLETION AND TESTING OF ALL THE WORK FOR THE PLUMBING SYSTEMS AS
SHOWN ON THE DRAWINGS, CALLED FOR IN THE SPECIFICATIONS, AND AS
REQUIRED BY JOB CONDITIONS, TO INCLUDE,, BUT NOT BE LIMITED TO THE
FOLLOWING: (REFER TO RESPONSIBILITY SCHEDULE FOR EXACT RESPONSIBILITIES)
A.
B.
C.
D.
E.
COMPLETE SANITARY PIPING SYSTEMS OF WASTE, DRAINS, AND VENTS.
COMPLETE COLD AND HOT WATER PIPING SYSTEMS, APPURTENANCES AND
INSULATION.
PLUMBING FIXTURES AND EQUIPMENT AS SCHEDULED .
COMPLETE NATURAL GAS PIPING SYSTEMS (AS APPLICABLE, REFER TO
PLANS).
TESTS AND ADJUSTMENTS.
2. BEFORE STARTING WORK, THIS CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL,
STRUCTURAL, MECHANICAL AND ELECTRICAL PLANS AND SPECIFICATIONS TO
SEQUENCE, COORDINATE, AND INTEGRATE THE VARIOUS ELEMENTS OF THE
PLUMBING SYSTEM, MATERIALS, AND EQUIPMENT WITH OTHER CONTRACTORS TO
AVOID INTERFERENCES AND CONFRONTATIONS.
3. RELOCATION OF EXISTING WATER, GAS, WASTE, VENT, OR DRAINAGE LINES TO
FACILITATE STORE DESIGN CRITERIA MUST BE INCLUDED IN BID PROPOSAL.
PLUIrBING EQUIPMENT
GENERAL PIPING REQUIREMENTS
1. GENERALLY, SANITARY AND POTABLE WATER TAPS WILL BE PROVIDED BY THE
LANDLORD. FIELD VERIFY EXACT C{NNNECT I ON POINTS PR I OMR TO SUEN I TT I NG
BID AND NOTIFY THE TENANT'S CONSTRUCTION MANAGER IF CONDITIONS ARE NOT
AS SHOWN ON THE PLANS OR AS STATED IN THE SPECIFICATIONS. CONTRACTOR
MIUST VERIFY THE OPERABILITY OF ENTIRE SYSTEM PRIOR TO TIE IN AS
FOLLOWS:
A. SNAKE SANITARY FOR A DISTANCE OF 100 FEET AND REPORT ANY
BLOCKAGE.
B. TEST WATER PRESSURE TO INSURE MINIMUMI OF 50 PSI.
2. AT COMPLETION OF THE PROJECT AND BEFORE F I NAL AI tPROAL, THE CONTRACTOR
SHALL MAKE ANY FINAL CORRECTIONS TO DRAWINGS ANS CERTIFY THE ACCURACY
OM: EACH PRINT BY SIGNATURE THEREON. THE DRAWINGS'ARE TO BE TURNED
OVER TO THE TENANT.
GUARANTEE
1. THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AI�WORK UNDER HIS
CONTRACT AND SHALL MAKE GOOD, REPAIR OR REPLACE.AT HIS OWN EXPENSE,
ANY DEFECTIVE WORK, MATERIAL, OR EQUIPMENT WHICH MAY BE DISCOVERED
WITHIN A PERIOD OF 12 MONTHS FROM THE DATE OF.AC:IEPTANCE (IN WRITING)
OF THE INSTALLATION BY THE TENANT'S CONSTRUCTION MANAGER. PROVIDE
EXTENDED WARRANTIES AS SPECIFIED WITH INDIVIDUAL EQUIPMENT. IN CASE
OF REPLACEMENT OR REPAIR OR EQUIPMENT DUE TO FAILURE WITHIN GUARANTEE
PERIOD. GUARANTEE ON THAT PORTION�OF WORK SHALL BE EXTENDED FOR A
PERIOD OF ONE (1) YEAR FROM DATE OF SUCH.REPLACEIETN OR REPAIR.
OPERATIONS MANUALS
1.
ONE COPY OF EACH OPERATION AND MAINTENANCE MANUAL FOR ALL EQUIPMENT
FURNISHED ON JOB SHALL BE COLLECTED AND INSERTED IN A 3' THREE RING
BINDER AND TURNED OVER TO THE TENANT. EACH NOTEBOOK SHALL INCLUDE BUT
NOT BE LIMITED TO INSTALLATION, MAINTENANCE AND OPERATING
INSTRUCTIONS, PAMPHLETS OR BROCHURES APPROVED SHOP DRAWINGS AND
WARRANTIES OBTAINED FROM EACH MANUFACTUER OF PRINCIPAL ITEMS OF
EQUIPMENT.
SLEEVES
1. THE CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OMR
FACILITIES IN THE INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH IT'S
RESPECTIVE FLOOR, WALL OR PARTITION AND SHALL BE'CUT FLUSH WITH EACH
SURFACE EXCEPT SLEEVES TWAT PENETRATE THE FLOOR, WHICH SHALL EXTEND
2' ABOVE THE FLOOR.
2. ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND/OXR FLOORS SHALL
BE FIRE SEALED WITH CALCIUM SILICATE, SILICONE 'RTV' FOAM, '3M' FIRE
RATED SEALANTS OMR EQUAL, SO AS TO RETAIN THE FIRE RATING OF THE FLOOR
OR WALL. CONFORM TO U.L. ASSEMBLY RATING OF FLOOR OMR WALL.
3. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS, AND.PARTITIONIS SHALL BE
STANDARD WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOUR OTHER THAN
MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS, OCR FOR CONCEALED
VERTICAL PIPING, SLEEVES SHALL BE NO. 22 U.S.G. GALVANIZED STEEL
MINIMUM.
4. DUCT SLEEVES TO BE MINIMUM 14 GAUGE STEEL.
i
HANGERS I
HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL'SUCH AS ANGLE IRON,
BANDS, C -CLAMPS WITH RETAINING CLIPS, CHANNELS. HANGER RODS, ETC.,
NECESSARY FOR THE INSTALLATION OF WORK.
2. HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE, OR MASONRY, BUT
NOT TO PIPING OR DUCTWORK. HANGING FROM:METAL DECK IS NOT PERMITTED.
HANGERS MUST BE ATTACHED TO UPPER CHORD OF BAR JOIST. WHERE
INTERFERENCES O CUR, IN ORDER TO SUPPORT DUCTWORK OMR PIPING, THE
CONTRACTOR MUST INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL
BE LOCATED WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE DAMPERS.
VALVES, ACCESS DOORS AND OTHER EQUIPMENT SERVICE;' REQUIREMENTS AND/OR
OTHER TRADES. HANGER TYPES MID INSTALLATION METHODS ARE SUJBJECT TO
LANDLORD CRITERIA.
3. HANGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR THE
GRATER DIAMETER OF INSULATION. INSTALL 6' LONG SPLIT CIRCLE GALVANIZED
SADDLE BETWEEN THE HANGER AND THE PIPE INSULATION.
4. HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI -ELECTRICALLY
SEPARATED FROM ONE ANOTHER.
0. ACCESS DOORS
P.
FURNISH STEEL ACCESS DOORS AND FRAMES. MIN. 16' X 20' OR AS SHOWN ON
DRAWINGS, TO GENERAL CONTRACTOR FOR ALL LOCATIONS WHERE NECESSARY TO
PROVIDE ACCESS TO CONCEALED VALVES, AND OTHER EQUIPMENT REQUIRING
SERVICE OR INSPECTION. LOCATION, TYPE, SIZE AND NUMBER AS DETERMINED
BY CONTRACTOR AND APPROVED BY TENANT CONSTRICTION MANAGER TO SUIT
EQUIPMENT REQUIREMENTS. GENERAL CONTRACTOR WILL INSTALL ACCESS DOORS
AND FRAMES.
2. ACCESS DOORS LOCATED I N FIRE -RATED WALLS, FLOORS, CEILING -FLOOR OMR
CEILING, -ROOF ASSEMBLIES SHALL BE FIRE RATED, UNDERWRITER'S
LABORATORIES, INC., LISTED AND LABELED.
3. ACCESS DOORS SHALL BE FLUSH TYPE, MANUFACTURED FROM NO. 14 GAUGE
STEEL, COMPLETE WITH FLUSH FLANGE TYPE FRAMES MANUFACTURED FROM NO.
16 GAUGE STEEL, PROVIDED WITH ANCHORS. ACCESS DOORS SHALL BE SUITABLE
FOR INSTALLATION IN WALL OMR CEILING MATERIALS SHOWN IN ROOM FINISH
SCHEDULES.
ELLO:IKICAL WTORS
1. FURNISH, INSTALL AND ALIGN ALL MOTORS REQUIRED FGAR THIS EQUIPMENT.
UNLESS THEY ARE FACTORY INSTALLED ON THE UNIT, ALL STARTERS AID
ASSOCIATED WIRING AND SAFETY SWITCHES FOR SUCH MOTORS SHALL BE
FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. STARTERS SHALL
MEET ALL REQUIREMENTS AS DEFINED IN THE ELECTRICAL DIVISION OF THE
SPECIFICATIONS.
2. DESIGN. CONSTRUCTIOMN AND PERFORMANCE CHARACTERISTICS OF MOTORS SHALL
CONFORMI TO ALL APPL I CABLE PROV I S IONS OF LATEST NEMA, ANSI , I SEE
STANDARDS FOR ELECTRICAL EQUIPMENT. ALL MOTORS,SHALL BE SUITABLE FOR
OPERAT I ONN ON VOLTAGE VAR I AT I OV OF PLUS OMR MINUS ` 10X, 40 DEGREES C
AMBIENT TEMPERATURE; HAVE A SERVICE FACTOR O" NOT LESS THAN 1.15.
Q. LOW
1.
VOLTAGE (24 VOLT) WIRING
THE CONTRACTOR IS TO INSTALL ALL LOW VOLTAGE WIRING REQUIRED FOR HIS
EQUIPMENT. THIS WORK INCLUDES ALL TRANSFORMERS AND DEVICES TO MAKE
THIS A COMPLETE FUNCTIONAL SYSTEM.
2. ALL WORK IS TO CONFORM TO THE LATEST ADDITION N.E.0 AND TO DIVISION
16 ELECTRICAL SPECIFICATIONS.
3. ANY CONDUIT REQUIRED BY CODE OR THE LA DLORD WILL BE INSTALLED BY THE
ELECTRICAL SUBCONTRACTOR.
2. INSTALL ALL NECESSARY PIPE HANGERS, SADDLES, AND CARRIERS TO PROPERLY
SUPPORT ALL PIPING AND FIXTURES. HANGERS SHALL SUIT TYPE OF PIPING
PROVIDED AND BE SPACED AT A MAXIMUM SPAN OF 5 FEET. PROVIDE SWAY AND
SEISMIC BRACING WHERE REQUIRED BY CODES.
DIVISION 15 - MECHNICAL
SECTION 15300
FIRE PROTECTION
SCOPE OF WORK A.
1
DIVISION 15 - MECHANICAL
SECTION 15500
HEATING, VENTILATION, AND AIR CONDITIONING
SCOPE OF WORK
THE F.P. CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, 1.
SERVICES, TOOLS, TRANSPORTATION AND FACILITIES NECESSARY' FOR.
REASONABLY IMPLIED AND INCIDENTAL TO, THE FURNISHING, INSTALLATION.
COMPLETION AND TESTING OF ALL THE WORK FOR THE SPRINKLER SYSTEMS AS
SHOWN ON THE DRAWINGS, CALLED FOR IN THE SPECIFICATIONS, AND AS
REQUIRED BY JOB CONDITIONS, TO INCLUDE, BUT NOT BE LIMIITED TO THE
FOLLOWING: (REFER TO RESPONSIBILITY SCHEDULE FOR EXACT RESPONSIBILITIES)
A. INSTALLATION OF NEW WET SPRINKLER SYSTEM AS REQUIRED TO PROVIDE
COVERAGE IN ACCORDANCE WITH NFPA-13, LOCAL CODES, LANDLORD'S
CRITERIA, AND INSURANCE CARRIERS FOR THE MALL AND TENANT.
B. TAPS, RISERS, LATERALS, BRANCHES, VALVES, ALARMS, SPRINKLER HEADS
AND ALL COMPONENTS REQUIRED FOR A COMPLETE SYSTEM.
C. DESIGN DRAWINGS, CALCULATIONS, SUBMITTALS AND APPROVALS.
D. PERMITS, FEES, AND',CHARGES.
E. TESTS AND TEST CERTIFICATES.
F. COST FOR SHUT DOWN FEES.
2. THE CONTRACTOR THAT DOES THE ACTUAL SPRINKLER WORK IS REQUIRED TO BE
A LANDLORD APPROVED SPRINKLER CONTRACTOR.
3. BEFORE STARTING WORK, THE CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL,
STRUCTURAL, MECHANICAL AND ELECTRICAL PLANS AND SPECIFICATIONS TO
SEQUENCE, COORDINATE, AND INTEGRATE THE VARICUUS ELEMENTS OF THE FIRE
PROTECTIOV SYSTEM, MATERIALS, AND EQUIPMENT WITH OTHER CONTRACTORS TO
AVOID INTERFERENCES AND CONFRONTATIONS.
4. RELOCATION OF EXISTING MAINS, LATERALS, BRANCHES AND RISERS TO
FACILITATE STORE DESIGN CRITERIA MUST BE INCLUDED. IN BID, PROPOSAL.
. SHOP DRAWINGS
THE FIRE PROTECTION CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS
AND CALCULATIONS FOR HIS WORK. SUIBMIT SIX (6) COPIES TO GENERAL _.
CONTRACTOR FOR APPROVAL. NO WORK SHALL BEGIN UNTIL"TENANT'S
CONSTRUCTION MANAGER APPROVES HEAD AND PIPING LOCAT I ONS
3. ESCUTCHEONS SHALL BE CHROME PLATED, SIZE AS REQUIRED AND PLACED AT ALL
PIPE PENETRATIONS AT WALLS, FLO RRS. AND CEILINGS IN FINISHED AREAS.
FLASHING SHALL BE SEALED WATERTIGHT AND PERFO ED IN ACCORDANCE TO THE
LANDLORD'S CRITERIA. USE A LANDLORD APPROVED ROFING CONTRACTOR WHERE
APPLICABLE.
4.
D. PIPING
SANITARY PIPING - NO PVC ALLOWED (STORM PIPING AS REQUIRED)
A. WASTE, DRAIN AD VENT PIPING SHALL BE SERVICE WEIGHT, CAST IRON
SOIL PIPE. VENT PIPING ABOVE FLOOR 2' OR SMALLER MAY BE
GALVANIZED STEEL.
B. JOINTS: BELOW FLOOR SLAB - BELL AND SPIGOT WITH CAULKED JOINTS
PER CODE.
C. PITCH WASTE LINES 2' AND SMALLER NOT LESS THAN 1/4' PER FOOT.
PITCH LARGER MAINS NOT LESS THAN 1/8' PER FOOT.
D. INSTALL A CLEANOUT AT BASE OF EACH SOIL STACK, AT EACH CHANGE IN
DIRECTION, AT INTERVALS NOT OVER 50 FEET, AND ELSEWHERE AS SHOWN
ON DRAWINGS OR REQUIRED BY LOCAL CODE. CLEANOUTS SWILL NOT BE
INSTALLED IN PUBLIC AREAS WITHOXUT SPECIFIC PERMISSION BY TENANT'S
CONSTRUCTION MANAGER; BUT WHERE NECESSARY, THE WALL COVERS ARE
TO BE STAINLESS STEEL AND THE FLOOR COVERS ARE TO BE BRASS (FLUSH
WITH FINISHED FLOOR). PROVIDE COVERS WITH INSET AREA FOR
CARPETED FLOOR LOCATIONS. ALL CLEAN-OUT LOCATIONS SHALL BE
APPROVED BY THE TENANT'S CONSTRUCTION MANAGER.
E. INSULATE ALL HORIZONAL RUNS OF PIPING LOCATED IN CEILING SPACES
WHEN APPLICABLE. INSULATION TO BE AS SPECIFIED FOR WATER PIPING.
F. INSULATE THE TRAP, SANITARY AND SUPPLY PIPES UNDER LAVATORY WITH
1/2' ARMSTRONG 'ARMAFLEX' PIPING INSULATION OR TRUEBRO MODEL 102W
'HANDI LAV GUARD' INSULATION KIT.
2. CONDENSATE PIPING SHALL BE TYPE 'L' DRAWN COPPER TUBE WITH 955 TIN -
ANTIMONY SOLDERED JOINTS AND WROUGHT COPPER FITTINGS WITH DIELECTRIC
SEPARAT I ON BETWEEN DISSIMILAR METALS.
3. POTABLE WATER PIPING:
A. BELOW GRADE: TYPE 'K', ANNEALED TEMPERED COPPER TUBE FOR PIPE
SIZES 2 INCHES AND SMALLER. BRAZE ALL JOINTS.
B. ABOVE GRADE: TYPE 'L' DRAWN COPPER TUBE WITH WROUGHT COPPER
FITTINGS AND 95 5 TIN -ANTIMONY SOLDER..
C. INSTALL AIR CHAMBER SHOCK ABSORBERS IN PIPING SYSTEM TO PREVENT
NOISE AND DAMAGE DUE TO WATER HAMMER.
D. ALL BRANCH PIPING SYSTEM SHALL HAVE ACCESSIBLE SERVICE VALVE.
PROVIDE SHUT OFF VALVES IN THE SUPPLY PIPING TO EVERY FIXTURE.
PROVIDE ACCESS DOORS WHERE NECESSARY.
E. PROVIDE WATER METER AND REMOTE READER PER LANDLORD'S CRITERIA OR
LOCAL UTILITIES�REQUIREMENTS IF APPLICABLE. REFER TO PLANS TO
DETERMINED IF WATER METER IS REQUIRED.
F. SECURE PIPE AT ANGLE STOPS.
G. PROVIDE FLEXIBLE INSERTS AT ALL PIPE PENETRATIONS THROUGH FRAMING
TO KEEP PIPES FROM HITTING FRAME WHEN IN OPERATION.
4. GAS PIPING
2. THE FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR SUBMITTING
COORDINATED DRAWINGS, CALCULATIONS, HEAD TYPES AND COLORS TO ALL
AUTHORITIES HAVING JURISDICTION FOR APPROVAL. NO KR K SHALE BEGIN
UJNTIL ALL APPROVALS HAVE BEEN RECEIVED.
3. A COPY OF THE LETTER OF APPROVAL FROM THE LANDLORD'S INSURANCE RATING
BUREAU SHALL BE FORWARDED TO THE LANDLORD'S AGENT AND TO THE TENANT'S
CONrSTRUCTION MANAGER.
C. EQUIPMENT
SPRINKLER HEADS:
A. ALL SPRINKLER HEADS SHALL BE NEW (EXISTING HEADS SHALL BE
REPLACED AS NECESSARY), U.L., F.M. LISTED AND A PROVED AUTOMATIC
SPRAY TYPE AS MANUFACTURED BY CENTRAL SPRINKLER CO.. GLOBE,
GRINNELL, RELIABLE, STAR, OMR VIKING.
B. ALL SPRINKLER HEADS SHALL BE RATED FOR 165'F UNLESS INDICATED
OTHERWISE ON DRAWINGS OR REQUIRED BY LOCAL CODES.
C. ALL SALES FLOORS HEADS ARE TO HAVE BE FACTORY APPLIED�COLOR
FINISH TO MATCH ARCHITECTURAL CEILING FINISH. VERIFY HEAD TYPES
AND COLORS WITH TENANT'S CONSTRUCTION MANAGER AND SUBMIT WITH
SPRINKLER DRAWINGS FOR PERMIT.
D. SPRINKLER HEAD TYPES SHALL BE AS FOLLOWS:
1. FINISHED CEILING (SALES AREA) - FULLY' RECESSED/CONCEALED TYPE
2. FINISHED CEILING NON -SALES AREA) - SEMI -RECESSED TYPE
3. NO -CEILING - CHROME UPRIGHT TYPE.
NOTE:SEMI-RECESSED HEADS SHALL PROTRUDE NO MORE THAN 1'
BELOW LEVEL OF CEILING OF SOFFIT. ALL HORIZONTAL SPRINKLER
RUNS AT SIDEWALL SOFFITS SHALL BE CONCEALED WITHIN SOFFIT
FRAMING.
D. GENERAL PIPING
A. PROVIDE A COMPLETE GAS PIPING SYSTEM IF APPLICABLE. REFER TO
PLANS TO DETERMINE IF A GAS SYSTEM IS REQUIRED.
B. LOW PRESSURE (14' W.C. AND BELOW) GAS LINES SHALL BE BLACK STEEL,
SCHEDULE 40. ASTM A-120, WITH MALLEABLE THREADED FITTINGS FOR 2'
AND SMALLER, AND WITH WELDED JOINTS FOR X1/2' AND LARGER.
MEDIUM PRESSURE (ABOVE 14' W.C.) SHALL WOVE WELDED JOINTS.
C. PROVIDE A GAS COCK, DIRT LEG. AND UNION CONVECTION TO EACH PIECE
OF EQUIPMENT. PROVIDE GAS METER A D/OR REGLATOR AS REQUIRED .
REGLATOR TO BE VENTED TO THE EXTERIOR.
D. PITCH PIPING AT A UNIFORM GRADE OF 1/4' IN 15 FEET UPWARD IN E.
DIRECTION OF FLOW. SUPPORT PIPING EVERY 5 FEET. SUPPORT AS
REQUIRED BY LANDLORD CRITERIA, AS DETAILED ON DRAWINGS, OR BY
STANDARD INDUSTRY PRACTICE, WHICHEVER IS MORE STRINGENT.
E. GAS PIPING EXPOSED ON ROOF MUST BE PAINTED WITH RUST -INHIBITING
PAINT.
F. INSTALLATION, TESTING AND PURGING OF GAS PIPING SHALL BE DONE PER
THE REQUIREMENTS OF THE LOCAL GAS COMPANY, LOCAL CODES, AND
APPLICABLE NFPA 54 CODES.
G. CONTACT AND COORDINATE GAS SERVICE AND METER REQUIREMENTS WITH
THE LOCAL GAS COMPANY AND THE WILL'S MANAGER PRIOR TO BID.
5. INSULATION F.
A. INSULATE ALL WATER AND INTERIOR CONDENSATE PIPING WITH 1' THICK
(K=0.23 0 75 F) SNAP-ON FIBERGLASS PIPE INSULATION WITH AN ALL
SERV ICE JACKET TO MEET LOCAL COXES AND U. FLAE SPREAD RATING OF
25 AND SMOKE DEVELOPED RATINGS OF 50. APPROVED MAANIFACTURER:
MANVILLE MICRO -LOO.
6. TEST A STERILIZATION
A. LEAKAGE TESTS SHALL BE PER LOCAL CODES, MINIMUM AS FOLLOWS:
1. TEST POTABLE WATER PIPING AND CONDENSATE PIPING AT 125 PSIG
FOR SIX HOURS.
2. TEST DRAIN, WASTE, VENT PIPINNG BY A 10' WATER COLUMN FOR
TWO HOURS. ALL JOINTS SHALL BE GAS AD WATER TIGHT.
3. TEST GAS PIPING WITH PER TEPA 54 CODES.
4. STERILIZE POTABLE HOT A COLD WATER LINES UPON COMPLETION OF
SYSTEM. STERILIZE WATER SYSTEM IN ACCORDANCE WITH LOCAL
CODES.
1
A FIRE PROTECTION SYSTEM STUB IN SHALL BE FURNISHED a THE LANDLORD.
SPRINKLER SPACING SHALL NOT EXCEED 130 SQ. FT..IN 'SALES' AREAS AND
100 SQ. FT. IN 'STOCK' AREAS. COMPLY WITH LANDLORD'S DESIGN CRITERIA.
PIPE SIZING SHALL BE BASED OMI NFPA ORDINARY HAZARD.
2. ALL SPRINKLER LINES SHALL BE INSTALLED CONCEALED, AVOIDING
INTERFERENCE WITH LIGHTS, DUCTS, PIPES, STORAGE DECMK. ETC. FIRE
PROTECTION CONTRACTOR SHALL PREPARE COORDINATED SHOP DRAWINGS
INDICATING THE LOCATIONS OF ALL SPRINKLER HEADS,,SPRINKLER LINES,
LIGHTS, DIFFUSERS, GRILLES AND REGISTERS PRIOR TO .INZTALLATIOV.
HORIZONTAL SPRINKLER RUNS AT MERCHANDISE SOFFITS SHALL BE PLACED
INSIDE SOFFIT STRUCTURE. VERTICAL DROPS FROM CEILING TO MERCHANDISE
SOFFIT SHALL BE LOCATED FLUSH AGAINST DEMISING WALLS.
3. WHERE POSSIBLE, REWORK THE EXISTING SPRINKLER SYSTEM TO MEET THE NEW
REQUIREMENTS OF THIS DESIGN. RELOCATE ALL MAINS AND BRANCHES
INTERFERING WITH CEILING HEIGHTS, EQUIPMENT, AND MAJOR COMPONENTS
INCLUSIVE OF ADJACENT TENANTS AND MALL COI/MON AREAS. REMOVE ALL
UNUSED PIPING.
4. LOCATIONS OF ALL HEADS SHOULD BE APPROVED BY THE LOCAL FIRE PROTECTION
OFFICIAL AD THE TENANT'S CONSTRUCTIOINN MANAGER BEFORE INSTALLATION.
HEADS MUST BE LOCATED IN THE CENTER OF CEILING TILES A D IN A
SYMMETRICAL PATTERN WITH OTHER CEILING FIXTURES. ADDITIONAL MONIES
WILL NOT BE ALLOCATED FOR ADDITIONAL HEADS REQUIRED BY FIELD FIRE
INSPECTOR AFTER BIDS ARE ACCEPTED. HEADS IN MERCHANDISE BAYS SHALL
BE CENTERED SIDE TO SIDE AND FRONT TO BACK.
5 PROVIDE AND INSTALL A VALVED TEST CONVECTION FOR THE SPRINKLER SYSTEM
AS REQUIRED OR REQUESTED BY THE MALL. LOCAL INSPECTOR, OR INSURANCE
CARRIER. COORDINATE LOCATION WITH TENANT'S CONSTRUCTION MANAGER AND
LOCAL FIRE PROTECTION OFFICIAL PRIOR TO ROUGH -IN.
6. SPRINKLER HEADS LOCATED IN STOCK, CORRIDOR ON TOILET ROOM CEILINGS OR
WALLS BELOW 8'-0' ABOVE THE FINISHED FLOOR ARE TO BE PROTECTED WITH
APPROVED GUARDS.
PIPING:
1.
2.
3.
4.
SCHEDULE 40, BLACK STEEL PIPE, ASTM A-53 FOR FERROUS PIPING, WELDED
AND SEALESS, ANSI B-36-10-70 FOR WROUGHT STEEL PIPE.
CAST IRON OR MALLEABLE IRON SCREWED FITTINGS FOR PIPES 2 INCHES AND
SMALLER. SCREWED OR CAST IRON FLANGED JOINTS FOR PIPES LARGER THAN
2 INCHES.
GALVANIZED OR BLACK MALLEABLE IRON WITH BRASS SEAT SCREWED UNIONS FOR
PIPES 2 INCHES AND SMALLER.
VICTAULIC TYPE COUPLINGS ARE ACCEPTABLE, WHERE APPROVED BY (ODE AND
THE LANDLORD.
TESTS
1. WHEN COMPLETED. THE ENTIRE FIRE PROTECTION PIPING SYSTEM SHALL BE
HYDROSTATICALLY TESTED AS REQUIRED BY THE RULES AND REGULATIONS OF THE
AUTHORITIES HAVING JURISDICTION. SYSTEM SHALL SHO AD SIGNS OF
LEAKAGE OR OTHER DEFECTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
DAMAGE TO THE WORK OF THE OTHER CONTRACTORS OR TO TIE BUILDING. OR TO
ITS CONTENTS, PEOPLE, ETC., CAUSED BY LEAKS IN ANY O" THE EQUIPMENT
INSTALLED BY HIM. ALL REPAIRS OR REPLACEMENT OF DAMAGES SHALL BE AT
THIS CONTRACTOR'S EXPENSE.
2. PROPERLY COMPLETED AND SIGNED 'SPRINKLER CONTRACTOR'S MATERIAL AND
TEST CERTIFICATES' SHALL BE FURNISHED TO THE LANDLORD, AUTHORITIES
HAVING JURISDICTION, AND TENANT'S CONSTRUCTION MANAGER.
B.
C.
THE HVAC CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT,
SERVICES, TOOLS, TRANSPORTATION AND FACILITIES NECESSARY FOR,
REASONABLY IMPLIED AND INCIDENTAL TO, THE FURNISHING, INSTALLATION,
COMPLETION AND TESTING OF ALL THE WORK FOR THE MECHANICAL SYSTEMS AS
SHOWN ON THE DRAWINGS, CALLED FOR IN THE SPECIFICATIONS, AND AS
REQUIRED BY JOB CONDITIONS, TO INCLUDE, BUT NOT BE LIMITED TO THE
FOLLOWING:(REFER TO RESPONSIBILITY SCHEDULE FOR EXACT RESPONSIBILITIES)
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
ROOFTOP UNITS, EQUIPMENT, AND APPURTENANCES.
DUCTWORK, FITTINGS, DAMPERS, AND INSULATION.
HYDRONIC PIPING AND INSULATION (AS APPLICABLE, REFER TO PLANS).
REFRIGERANT PIPING (AS APPLICABLE, REFER TO PLANS).
DIFFUSERS, GRILLES, AND REGISTERS.
CURBS AND STEEL FRAMING FOR SUPPORT (AS APPLICABLE, REFER TO
PLANS).
TESTING, ADJUSTING, AND BALANCING.
OPERATIONS MANUALS.
TEMPERATURE CONTROLS AND RELATED DIAGRAMS.
SEQUENCES Cf OPERAT I ODN .
CONNECTION TO ANY LANDLORD ENERGY MANAGEMENT SYSTEM.
3. BEFORE STARTING WIORK, THIS CONTRACTOR SHALL EXAMINE THE ARCHITECTURAL,
STRUCTURAL, MECHANICAL AND ELECTRICAL PLANS AD SPECIFICATIONS TO
SEQUENCE, COORDINATE, AND INTEGRATE THE VARIOUS ELEMENTS OF THE HVAC
SYSTEM, MATERIALS, AND EQUIPMENT WITH OTHER CONTRACTORS TO AVOID
INTERFERENCES AND CONFRONTATIONS.
HVAC EQUIPMENT
PRIMARY HEATING, VENTILATION AND AIR CONDITIONING UNITS.
A. PRIMARY HEATING, VENTILATION, AND AIR CONDITIONING UNITS ARE TO
BE BY CARRIER AS SCHEDULED. ALL COMPRESSORS ARE TO
INCLUDE A 5 -YEAR EXTENDED WARRANTY.
B. EQUALS EQUIPMENT AS MANUFACTURED BY TRANE OMR YORK ARE
ACCEPTABLE.
C. ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT WITH ALL
DEVICES, APPURTENANCES, AND ACCESSORIES PROVIDED TO MEET THE
DESIGN INTENT AND OPERATION OF THE SYSTEMS SHOWN ON THE DRAWINGS
AND SPECIFIED HEREIN.
D. EQUIPMENT SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE
MANUFACTURER'S INSTRUCTIONS. ALL AIR CONDITIONING EQUIPMENT MUST
HAVE A CONDENSATE DRAIN AND BE TRAPPED IN ACCORDANCE WITH
MANUFACTURERS DATA. SEE DRAWINGS FOR ADDITIONAL DETAILS.
E. SECONDARY DRAIN PANS ARE REQUIRED TO BE INSTALLED BENEATH ALL
INDOOR AIR CONDITIONING EQUIPMENT WITH THE EXCEPTION OF VAV
BOXES. SECONDARY PMIS ARE TO PROTECT ENTIRE UNIT. PROVIDE
CONDENSATE PUMPS, AS REQUIRED. CONDENSATE SHALL BE DIRECTED TO
MOP SINK OR AS SPECIFIED ON PLANS.
2. VARIABLE AIR VOLUME BOXES (VAV)
A. WHERE SHOWN ON DRAWINGS, PROVIDE VAV BOXES COMPLETE WITH
CONTROLS, HEATING COILS (FANS AS REQUIRED). ALL DUCT CONNECTIONS
FLEXIBLE DUCT/PIPE CONNECTIONS SWILL BE PROVIDED BY THE
CONTRACTOR.
3. TOILET EXHAUST FANS
A. WHERE SHOWN ON DRAWINGS, PROVIDE A TOILET EXHAUST FAN UNIT
COMPLETE WITH GRAVITY BACK DRAFT DAMPERS. ALL DUCTWORK, ROOF'
OPENINGS AND CAPS NECESSARY TO PROVIDE A COMPLETE EXHAUST SYSTEM
SHALL BE PROVIDED BY THE CONTRACTOR. REFER TO PLANS FOR
APPLICABILITY.
4. BASEBOARD, CABINET, AND UNIT HEATERS .
A. WHERE SHOWN ON DRAWINGS, PROVIDE ELECTRIC HEATERS COMPLETE WITH
ELECTRIC HEATING COIL, CONTROLS, AND INTEGRAL THERMOSTAT.
5. INLINE PUMPS
A. WHERE SHOWN ON DRAWINGS PROVIDE AN INLINE CLOSE COUPLED PUMP(S),
BRONZE FITTED, PUMPS SHALL BE FURNISHED WITH BRONZE CASE WEARING
RINGS, BRONZE SHAFT SLEEVE AND MECHANICAL SHAFT SEAL RATED FOR.
PUMPS TO BE SO CONSTRUCTED THAT THEY MAY BE MOUNTED IN A
HORIZONTAL OR VERTICAL PIPE LINE. MOTOR TO BE 1750 RPM UNLESS
NOTED OTHERWISE.
6. VIBRATION ISOLATION DEVICES
A. VIBRATION ISOLATION DEVICES SHALL BE PROVIDED IN ALL SUPPORTS
BETWEEN VIBRATING EQUIPMENT (FANS, ROOFTOP UNITS, AIR HANDLERS,
FAN POWERED VAV BOXES, ETC.) AND STRUCTURE.
B. VIBRATING EQUIPMENT HUNG FROM STRUCTURE SHALL BE ISOLATED WITH
RUBBER AND SPRING DEVICES. VIBRATING EQUIPMENT SUPPORTED FROM
FLOOR OR DECK SHALL BE ISOLATED WITH HOUSED SPRING MOU T DEVICES.
C. EXAMINE DEAD LOAD AND OPERATING LOAD CONDITIONS WHEN SELECTING
DEVICES. ADJUST FOUR PROPER ALIGNMENT AND LOADING. AVOID
'GROUNDING' THE ISOLATOR.
D. CHECK HANGER ROD SIZE FOR ALLOWABLE LOADS AT THE ISOLATING DEVICE
AND AT THE UPPER AND LOWER ATTACHMENTS TO STRUCTURES, DUCTS,
EQUIPMENT, ETC.
E. CONSULT MANUFACTURER FOR APPLICATION DATA.
7. CURBS AND STEEL FRAMING FOR SUPPORT
A. THIS CONTRACTOR WILL PROVIDE ALL NECESSARY CURBS MD STEEL
FRAMING REQUIRED TO INSTALL ALL HVAC EQUIPMENT AS DESCRIBED OR
IMPLIED ON THE DRAWINGS. CURBS SHALL BE A MINIMUM OF 14' HIGH,
OF THE SAME MANUFACTURER OF TIHE EQUIPMENT SUPPORTED. INSULATE
UNDER THE COMPRESSOR SECTION TO PREVENT CONDENSATION. ALL CURBS
MUST BE INSTALLED SO THAT TOP OF CURBS ARE 'DEAD' LEVEL. ALL
PENETRATIONS OF EXISTING STRUCTURE SHALL BE DONE IN ACCORDANCE
TO THE LANDLORD'S GUIDELINES AT THIS CONTRACTOR'S EXPEL.
METAL DUCTWORK - ND FIBERGLASS DUCT ALLOWED
1. NO DUCTWORK SHALL BE FABRICATED PRIOR TO APPROVAL BY THE TENANT'S
CONSTRUCTION MANAGER. SIGNIFICANT DEVIATIONS FROM DESIGN MiUST BE
APPROVED BY TENANT'S CONSTRUCTION MANAGER PRIOR TO FABRICATION OR
INSTALLATION. ALL DUCT MAINS ARE TO BE RECTANGULAR UNLESS NOTES
OTHERWISE. ALL DUCT BRANCHES TO DIFFUSERS ARE TO BE ROUND RIGID DUCT.
2. EXCEPT AS OTHERWISE INDICATED, FABRICATE AND INSTALL RECTANGULAR DUCTS
WITH GALVANIZED SHEET STEEL. IN ACCORDANCE WITH SMACNA 'HVAC DUCT
CONSTRUCTIOINN STANDARDS' OF THE LATEST EDITION. CONFORM TO THE
REQUIREMENTS IN THE REFERENCED STANDARD FOR METAL THICKNESS,
REINFORCING TYPES AND INTERVALS, TIE ROM) APPLICATIONS, AND JOINT TYPES
AMD INTERVALS.
3. EXCEPT WHERE OTHERWISE INDICATED, CONSTRUCT DUCT SYSTEMS TO THE
FOLLOWING PRESSURE CLASSIFICATIONS: (VERIFY WHETHER RETURN OR EXHAUST
DUCT IS POSITIVE OMR NEGATIVE PRESSURE).
A. SUPPLY DUCTS: 2 INCHES WATER GAUGE, POSITIVE PRESSURE
B. RETURN AND EXHAAUST DUCTS: 2 INCHES WATER GAUGE, NEGATIVE
PRESSURE.
PRESSURE TEST DUCTS FOUR LEAKAGE. REMAKE LEAKING JOINTS AND APPLY
SEALANTS AS REQUIRED TO FABRICATE A SYSTEM THAT DOES NOT EXCEED 5M
LEAKAGEEOMR LESS AS STATED BY PRESSURE CLASS RATINGS IN SMACNA
STANDARDS.
4. ASA MINIMUM. CROSSBREAK ALL FLAT SURFACES OR REINFORCE WITH A BEAD
APPROXIMATELY 3/8' WIDE X 3/16' DEEP ON 12' CENTERS TO PREVENT
VIBRATIONS.
5. INSTALL DOUBLE THICKNESS TURNING VANES IN ALL RIGHT ANGLE ELBOWS.
6. INSTALL RIGID ROUD AND RECTANGULAR METAL DUCT WITH SUPPORT SYSTEMS
INDICATED IN SMACNA STADARDS. SUPPORT HORIZONTAL DUCTS WITHIN 2 FEET
OF EACH ELBOW AND WITHIN 4 FEET OF EACH BRANCH INTERSECTION USING
DOUBLE STRAP HANGERS ON EACH SIDE OF FITTING. SUPPORT VERTICAL DUCTS
AT A MAXIMA INTERVAL OF 16 FEET AND AT EACH FLOOR. NO WOO) SHALL BE
USED TO SUPPORT OMR BRACE DUCTS. PROVIDE SWAY AND SEISMIC BRACING AS
REQUIRED BY STATE AND LOCAL CODES OR BY LANDLORD.
7. WHERE DUCTS PASS THROUGH ROOM'S MD FLOORS, PROVIDE AS M I N I MUMU 1-
1/2'X1-1/2' X1/8' STEEL ANGLE FRAMES AT EACH SIDE OF OPENING. THE
ANNULAR SPACE BETWEEN DUCT AND ANGLE FRAMES SHALL BE CAULKED WITH
SILICONE SEALANT OR FIREPROOFED AS REQUIRED BY ASSEMBLY FIRE RATING.
8. ALL TRAVERSE JOINTS AND SEAMS IN SUPPLY AIR DUCT SHALL BE SEALED AIR
TIGHT WITH DAP CMC DUCT SEALER. JOINTS ALSO SHALL BE RIVETED OR
CONNECTED WITH SHEET METAL SCREWS.
9. SOFT ELASTOMER BUTYL GASKET WITH ADHESIVE BACKING SHALL BE USED TO
SEAL FLANGED JOINTS.
10. DUCT TRANSITIONS SHALL NOT EXCEED 30 DEGREES SLOPE EXCEPT AS
SPECIFICALLY NOTED OTHERWISE.
11. PROVIDE ACCESS TO ALL MOTORIZED DAMPERS, FIRE DAPERS, CONTROLS, AND
OTHER ITEMS IN DUCTWORK THAT REQUIRE SERVICE OR INSPECTION. IF THE
ACCESS PANEL LOCATION IS EXPOSED TO THE SALES AREA, IT MUST BE
APPROVED BY THE TENANT'S CONSTRUCTION MANAGER PRIOR TO INSTALLATION.
LAY -IN SUPPLY AND RETURN AIR DIFFUSERS, GRILLES AND REGISTERS WITH
PLASTER FRAMES MAY BE USED AS ACCESS LOCATIONS.
D.
12. FLEXIBLE CONNECTIOrS
A. FLEXIBLE COLLARS SHALL BE PROVIDED IN ALL CONNECTIONS BETWEEN
VIBRATING EQUIPMENT (FANS, ROOFTOP UNITS, AIR HANDLERS, FAN
POWERED VAV BOXES. ETC.) AND DUCTS OR CASINGS. ALSO, PROVIDE
FLEXIBLE CONNECTIONS WHERE DUCTS CROSS BUILDING EXPANSION JOINTS.
B. FLEXIBLE CONNECTIONS SHALL CONSTRUCTED OF NEOPRENE -COATED
FLAMEPROOF FABRIC. PROVIDE ADEQUATE JOINT FLEXIBILITY; TO ALLOW
FOR MOVEMENT AND PREVENT THE TRANSMISSION OF VIBRATION.
C. FLEXIBLE CONNECTION IS TO BE RATED FOR THE OPERATING PRESSUARE OF
THE SYSTEM.
13. FIRE DAMPERS
A. PROVIDE PRIMARY FIRE DAMPERS WHERE INDICATED OR RE IVIED BY
QU..
CODES. DAMPERS SHALL BE DESIGNED FOR HORIZONTAL OR VERTICAL. FLOW
OF AIR AS REQUIRED. FIRE DAMPERS SHALL BE UL LABELED..',
B. FIRE DAMPERS SHALL HAVE THE BLADES OUT OF THE AIRSTREAM AND A
165'F FUSIBLE LINK, TYPE A, AS MINIMUM. 'j
C. PROVIDE ALL NECESSARY FRAMING AND SLEEVES FOR DAMPER'MOUNTING PER
UL AND CODE REQUIREMENTS.
D. PROVIDE DUCT ACCESS DOORS IN AN ACCESSABLE LOCATION FOR ALL FIRE
DAMPERS. DOOR IS TO BE 20 GA GALVANIZED DOOR WITH QUICK -OPENING
LATCH AND PIANO HINGE.
t
14. FLEXIBLE AIR DUCT
A. FLEXIBLE AIR DUCT SHALL BE 1' INSULATED CLASS 1 AND RATTED FGR THE
OPERATING PRESSURE OF THE SYSTEM. DUCT CONSTRUCTION TERIAL
(PLASTIC, CLOTH, ALUMINUM) MUST ADHERE TO LOCAL CODES 'AND
LANDLORDS REQUIREMENTS AND BE INCLUDED AS SUCH IN TIE BID.
B. FLEXIBLE AIR DUCT MAZY ONLY BE USED IN VERTICAL APPLICATIONS WITH
PRIOR APPROVAL FROM TENANT'S CONSTRUCTION MANAGER.
C. FLEXIBLE DUCT SHALL NOT EXTEND OVER 5'-0' IN LENGTH ATANY ONE
LOCATION.
15. SUPPLY AIR TAKE -OFF FITTINGS
A. PROVIDE CONICAL OR 'BELL -MOUTH' TAKE -OFFS FROM MAIN D`TWORK�TO
, ll,��
ROUND BRANCHES. INSTALL PER MANUFACTURERS I NSTRUCTI:ONS.
B. PROVIDE 45' RECTANGULAR TAKE -OFFS FROM MAIN DUCTWORK TJ
RECTANGULAR BRANCHES.
16. DAMPERS
A. PROVIDE MANUAL LOCKING QUADRANT VOLUME CONTROL DAMPERS WITH
HADLE OPERATORS IN EACH BRANCH DUCT AND AS SHOWN ONN PLANS TO
FACILITATE AIR BALANCING.
B. WHERE ACCESS TO BALANCING DAMPER IS RESTRICTED, YOUNG'S
REGULATORS SHALL BE USED.
C. ALL RECTANGULAR DAMPERS IN OUTSIDE AIR.. RELIEF AIR, CR RETURN AIR
DUCTS ARE TO BE OF OPPOSED BLADE TYPE. ALL OUTSIDE AIR DUCT
DAMPERS MUST ALSO BE OF THE LOW LEAKAGE TYPE.
D. ALL MOTORIZED DAMPERS NOT FURNISHED WITH EQUIPMENT ARE TO BE
HONEYWELL DAMPERS.
17. DIFFUSERS, GRILLES, AD REGISTERS
A. PROVIDE DIFFUSERS GRILLES AND REGISTERS AS SCHEDULED. 'DEVICES
TO BE COMPLETE WITH DAMPERS FRAMES AND ALL ACCESSORIES. FINISH
AS INDICATED.
B. INSTALL ALL AIR DEVICES AS LOCATED ON THE ARCHITECTURAL REFLECTED
CEILING PLAN.
C. APPROVED MANUFACTURERS: TITUS IS SPECIFIED, EQUALS BY ETALAIRE
OR KRUEGER IS ACCEPTABLE.
18. MEDIUM PRESSURE DUCT
A. WHERE DUCCTWORK IS SPECIFICALLY NOTED AS MEDIUM PRESSURE, IT SHALL
BE CONSTRUCTED IN ACCORDANCE WITH SMACNA STANDARDS FOR A PRESSURE
RATING OF 3 INCHES WATER COLUMN MINIMA OR LARGER AS REQUIRED BY
LANDLORD.
B. ALL GAUGES AND REINFORCEMENT MUST MEET WITH THE LATEST EDITION
OF SMACNA STADARDS FOR MEDIUM PRESSURE DUCT AND WITH THE
LANDLORD'S CRITERIA.
C. ALL OTHER ITEMS FROM METAL DUCTWORK SPECIFICATION SECTION APPLY
TO THIS SECTION
19. DUCTWORK INSULATION
A. INSTALL INSULATION PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S
WRITTEN INSTRUCTIONS, AD IN ACCORDANCE WITH RECOGNIZED INDUSTRY
PRACTICES. INLSULAT I ON MUST COMPLY WITH NEPA 90A.
B. DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE CLEAR DIMENSIONS.
INSULATE SUPPLY AND RETURN AIR RECTANGULAR DUCTWORK. DUCTWORK
SHALL BE INTERNALLY LINE WITH 1' THICK ACCOUSTICAL LINER.
IF REQUIRED, DUCTWORK SHALL BE EXTERNALLY WRAPPED WITH,1 1/2'
THICK, FOIL FACED FIBERGLASS INSULATION IN PLACE OF ACCOUSTICAL
LINER.
C. ALL ROUND AND OUTSIDE AIR DUCTWORK ABOVE THE CEILING SHALL BE
EXTERNALLY INSULATED WITH A MINIMA OF 1' THICK, 1-1/2LB. DENSITY
(R�.6) DUCT WRAP WITH VAPOR BARRIER. VAPOR BARRIER IS TO BE
MAINTAINED THROUGHOUT DUCT SYSTEM. ALL JOINTS MUST BE TAPED SO
THAT NO INSULATION FIBER IS VISIBLE. EXTEND DUCTWORK INSULATION
WITHOUT INTERRUPTION THROUGH WALLS, FLOORS, AND SIMILAR
PENETRATIONS.
D. DUCTWORK LOCATED IN THE CONDITIONED SPACE SHALL NOT BE INSULATED
UNLESS OTHERWISE NOTED OV PLANS. INSULATE ALL DUCT DROPS OR
THE FIRST 20 FEET OF DUCT AT THE HVAC UNITS IN ALL CASES.
E. ALL INSULATION SHALL HAVE A FLAME SPREAD RATING OF NOT MORE THOU
25 AND A SMOKE DEVELOPED RATING OF NO HIGHER THAN 50 WHEN TESTED
IN ACCORDANCE WITH ASTM C 411, OR AS REQUIRED BY LOCAL CODES.
20. SYSTEM CLEANOUT
A. DUCTWORK AND AIR HANDLING EQUIPMENT IS TO BE CLEANED OUT AND
BLOMM OUT BEFORE PAINTING IS STARTED BY THE GENERAL CONTRACTOR.
B. FILTERS MUST BE IN UNITS AT ANY TIME FANS ARE OPERATED.
HYDRONIC PIPING NSA
1. PROVIDE A COMPLETE HYDRONIC PIPING SYSTEM IF APPLICABLE. REFER TO
PLANS TO DETERMINE IF A HYDRONIC SYSTEM IS REQUIRED.
2. PIPING
A. HYDRONIC PIPING FOR CHILLED WATER AND/OR HEATING WATER AND/OR
CONDENSER WATER SHALL BE ASTM A-120, SCHEDULE 40, ERN,,BLACK
STEEL PIPE WITH PLAIN ENDS. INSTALL STEEL PIPE WITH WELDED
JOINTS WHERE PIPE IS 2-1/2 INCH AND LARGER. INSTALL STEEL PIPE
WITH THREADED JOINTS AND FITTINGS OR INSTALL TYPE 'K' ANNEALED
TEMPERED COPPER TUBE WITH SILFOS JOINTS FOR 2 INCH AND SMALLER
PIPE. PROVIDE DIELECTRIC UNIONS BETWEEN DISSIMILAR METALS. ALL
PIPING SHALL BE I N STRICT CONFORMIANCE WITH ASTM, ASA, AND
LANDLORD'S REQUIREMENTS, WHICHEVER IS MOST STRINGENT. 'UNIONS OR
FLANGES MUST BE USED AT EQUIPMENT CONNECTIONS WHERE SERVICE OR
REMOVAL MAY BE REQUIRED.
B. ALL PIPING AND EQUIPMENT SHALL BE PRESSURE TESTED WITHOUT LEAKAGE
AT A MINIMA PBEtagE OF 125 PSI.
C. ALL HYDRONIC PIPING AND EQUIPMENT CONNECTED TO THE HVAC PIPING
SYSTEM SHALL BE CLEANED AND FLUSHED. REMOVE, CLEAN, AN) REPLACE
STRAINER SCREENS. FILL TENANT'S SYSTEM WITH DOMESTIC�WATER AND
VENT ALL PIPING AND EQUIPMENT PRIOR TO CONNECTION TO THE
LANDLORD'S SYSTEM. CONTRACTOR SHALL NOT FILL TENANT'S','SYSTEM
WITH WATER FROM THE LANDLORD'S SYSTEM UNLESS SPECIFICALLY
INSTRUCTED TO DO SO FROM THE LANDLORD'S FIELD REPRESENTATIVE.
D. PRIOR TO CONVECTION TO THE LANDLORD'S SYSTEM, CONTRACTOR SHALL
OBTAIN WRITTEN CONFIRMATION FROM THE LANDLORD'S FIELD i
REPRESENTATIVE, THAT ALL TESTING, FLUSHING, AND PROPER FILLING
OF THE TENANT'S SYSTEM HAS BEEN COMPLETED IN ACCORDANCE .TO THE
LANDLORD'S REQUIREMENTS AND THAT THE TENANT'S SYSTEM IS READY TO
BE CONNECTED TO THE LANDLORD'S SYSTEM.
3. VALVES
A. GATE VALVES, 2 -INCH AND SMALLER: CLASS 150, BODY MD UNION
BONNET OF ASTM B 62 CAST BRONZE WITH THREADED OR SOLDEfR ENDS,
INTEGRAL SEAT, RENEWABLE SOLID BRONX WEDGE DISC, RISING STEM,
SCREWED BONNET AND RE -PACKABLE UNDER PRESSURE. BALL VALVES ARE
ACCEPTED AS AN EQUAL SUBSTITUTION.
B. GATE VALVES, 2-1/2 INCH AND LARGER: CLASS 125 CAST IROI,BODY,
RENEWABLE BRONZE SEATS AND SOLID WEDGE DISC, RISING STEM, FLANGED
ENDS, AND RE -PACKABLE UNDER PRESSURE.
C. SWING CHECK VALVES, 2 -INCH AND SMALLER: CLASS 150, CAST BRONZE
BODY AND CAP CONFORMING TO ASTM B 62 WITH HORIZONTAL SWING, Y -
PATTERN, RENEWABLE BRONZE DISC, AND HAVING THREADED OR SOLDERED
ENDS.
D. SWING CHECK VALVE, 2-1/2 INCH AND LARGER: CLASS 125 CAST IRON
EDDY AND BOLTED CAP, HORIZONTAL SWING, RENEWABLE BRONZE DISC,
FLANGED ENDS AND CAPABLE OF BEING REFITTED WHILE THE VALVE
REMAINS IN THE LINE.
E . COMBINATION BALANCING AND SHUT-OFF VALVES: BELL Al: GOSSETT
CIRCUIT SETTER WITH LOCKING SETPOINT. A CIRCUIT SETTER BALANCE
WHEEL MUST BE INCLUDED WITH 0 Alt M MANUAL.
F. FLOW METER: BELL AND GOSSETT THERMOFLO INDICATOR MODEL TFI..
E.
F.
G.
4. PIPING SPECIALTIES
A. PRESSURE/TEMPERATURE TEST PLUGS ( PETE'S PLUG) - 1/4 INCH NPT
FITTINGS TO RECEIVE EITHER A TEMPERATURE OR PRESSURE PROBE, 1/8
INCH O.D. FITTING AND CAPS SHALL BE BRASS WITH VALVE CORE OF
NORDEL, RATED AT 400 PSIG, O'F TO 200'F.
B. STRAINERS - 'Y' PATTERN STRAINERS, 125 PSIG, CAST IRON BODY WITH
PERFORATED STAINLESS STEEL SCREEN, THREADED FOR 2 INCHES AND
SMALLER, FLANGED FOR 2-1/2 INCHES AND LARGER. SCREEN OPENING
SIZE AT 0.033 INCH FOR HEATING AND 1/8 INCH FOR CHILLED OR
CONDENSER WATER. PROVIDE WITH BLOWDOWN VALVE WITH HOSE END
FITTING.
C. THERMOMETERS - DIE CAST ALUMINUM, 9' INDUSTRIAL MERCURY
THERMOMETER, FULLY ADJUSTABLE WITH CLEAR ACRYLIC WINDOW AND BRASS
SEPARABLE SOCKET.
D. MANUAL AIR VENTS - 1/8' COIN-OPERATED VENT. PROVIDE AN AIR
CHAMBER CONSISTING OM: A 3/4' NIPPLE AND BUSHINGS.
5. GENERAL I NSTALLAT I OMNI
A. INSTALL WATER MAINS WITHOUT PITCH. USE ECCENTRIC REDUCING
COUPLINGS AT CHANGES IN SIZE WITH THE TOP OF PIPES AT SAME
ELEVATION. MAKE CHANGES IN DIRECTION WITH FITTINGS.
B. BRANCHES TO UNITS BELOW MAINS TO BE TAKEN FROM BOTTOM OF MAINS
AT A 45 DEG EE ANGLE, PITCH DOWNWARD TOWARD UNITS. BRANCHES TO
UNITS ABOVE MAINS TO BE TAKEN FROM TOP OF MAINS AT A 45 DEGREE
ANGLE PITCHED UPWARD TOWNARDS UNITS. PITCH NOT LESS THAN 1' TO
10 FEET.
C. HANGERS SHALL BE SIZED AND INSTALLED FOR THE OUTSIDE DIAMETER OF
THE INSULATED PIPE. INSTALL 6' LONG SPLIT CIRCLE GALVANIZED
SADDLE BETWEEN THE HANGER AND PIPE INSULATION.
D. HANGERS AND PIPING (F DISSIMILAR METALS SHALL BE DIELECTRICALLY
SEPARATED FROM OBE ANOTHER.
E. SEE PLANS FOR APPLICABLE DETAILS.
F. ALL PRESSURE PIPING SYSTEMS INSTALLED SHALL CONFORM TO THE
REQUIREMENTS OF THE STATE PIPING AND WELDING CODES.
G. INSTALL VALVES AT LOW POINTS FOR DRAINING EACH SYSTEM AND INSTALL
MANUAL VENTS AT ALL HIGH POINTS OF EQUIPMENT AND PIPING IN` THE
SYSTEM TO PROPERLY REMOVE ENTRAPPED AIR.
6. I NSULAT I OMNI
A. ALL HYDROM�NIC PIPING FOR CHILLED WATER AND/OR HEATING WATER,
VALVES, FITTINGS, AD ACCESSORIES SHALL BE INSULATED. FOR PIPE
SIZES UP TO 2 INCHES, INSULATE WITH 1 INCH THICK (K-0.23 0 75'F
FIBERGLASS INSULATION WITH ALL SERVICE JACKET AND VAPOR BARRIER.
FOR PIPE SIZES 2-1/2 INCHES AND LARGER, INSULATE WITH 1-1/2 INCH
THICK (K4.23 0 75'F) FIBERGLASS INSULATION WITH ALL SERVICE
JACKET A) VAPOR BARRIER.
B. INSULATION AT ALL HANGERS FOUR PIPING 2-1/2 INCHES AND LARGER
SHALL BE HARD AND NON-COMESSIBLE.
C. ALL INSULATION SHALL HAVE A FLAME SPREAD RATING OF NOT MORE THAN
25 AND A SMOKE DEVELOPED RATING OF NO HIGHER THAT 50 TO CONFORM
WITH THE REQUIREMENTS OF THE NFPA.
REFRIGERANT PIPING NSA
1.
PROVIDE A COMPLETE REFRIGERANT PIPING SYSTEM BETWEEN INDOOR FAN UNITS
AND OUTDOOR CONDENSING, UNITS, IF APPLICABLE. PROVIDE OIL, REFRIGERANT
CHARGE AND TEST SYSTEM. REFER TO PLANS TO DETERMINE IF A REFRIGERANT
PIPING SYSTEM IS REQUIRED.
2. MATERIALS
A. REFRIGERANT PIPING SWILL BE TYPE 'L' DRAWN COPPER TUBING (ASTM
888), WROUGHT COPPER OR CAST BRONZE FITTINGS (ANSI B16.22), WITH
SILFOS 5 SOLDERED JOINTS.
B. SERVICE VALVES, CHARGING PORTS, FILTER -DRIER, SIGHT CLASS, AND
A THERMOSTATIC EXPANSION VALVE (TXV) SHALL BE INSTALLED FOR EACH
SYSTEM AS A MINIMUM.
3. INSTALLATION
A. SIZE LINES WITH ADEQUATE LIFT TRAPS AND DOUBLE SUCTION RISERS AS
NECESSARY TO MEET THE NEEDS OF EQUIPMENT SPECIFIED, FIELD
CONDITIONS, AND EQUIPMENT MANUFACTURER'S RECOMMENDATIONS.
B. PRESSURE TEST FOUR LEAKS WITH AN INERT GAS AT 250 PSIG. REDO
LEAKING JOINTS AND RETEST UNTIL SYSTEM IS TIGHT. EVACUATE GAS
AND CHARGE SYSTEM. RE -TEST SYSTEM AND CHECK FOR LEAKS WITH
HALIDE LEAK DETECTOR. ALL LEAKING JOINTS MUST BE COMPLETELY RE-
DONE UNTIL NO LEAKS EXIST.
C. UPON COMPLETION OF TESTING, BUT BEFORE INSULATION IS APPLIED,
PIPING MUST BE INSPECTED BY A REPRESENTATIVE OF THE LOCAL
GOVERNING AUTHORITY AS NECESSARY.
D. REFRIGERANT LINES SHALL BE INSULATED WITH 1 INCH THICK RUBATEX
OR ARMSTRONG REFRIGERANT PIPE INSULATION IN ACCORDANCE WITH
INDUSTRY STANDARDS.
SYSTEM TESTING, ADJUSTING, AND BALANCING
1
• TESTING, ADJUSTING AND BALANCING OF ALL WORK SHALL BE MME BY AN
INDEPENDENT CONTRACTOR WHO IS CURRENTLY LICENSED ASSOCIATED AIR
BALANCING COUNCIL (AABC) OR NATIONAL ENVIRONMENTAL BALANCING BUREAU
(NEBB) BALANCING CONTRACTOMR. NO OTHER BALANCE REPORTS WILL BE
REVIEWED OR ACCEPTED. ALL BALANCING WORK MUST BE COMPLETE AND DONE
IN ACCORDANCE WITH THE MOST RECENT STA DARDS OF THEIR SOCIETY.
PAYMENT OF ALL COSTS FOR TESTING SHALL BE MME BY THE HVAC CONTRACTOR.
2. THE HVAC CONTRACTOR SHALL INSTALL NEW FILTERS IN ALL UNITS PRIOR TO
THE AIR BALANCE. THE COMPLETE AIR BALANCE SHALL TAKE PLACE WITH
OUTSIDE AIR DAMPERS IN MINIMUM POSITION.
3. BALANCE AIR A D WATER QUANTITIES TO WITHIN + 5% OF THAT INDICATED ON
THE DRAWINGS. ANY REQUIRED CHANES IN SHEAVES, BELTS, PULLEYS, OR THE
ADDITION OF DAMPERS REQUIRED TO ACHIEVE SPECIFIED FLOW RATES SHALL BE
PERFORMED BY THE HVAC CONTRACTOR WITH NO ADDITIONAL COST TO THE
TENANT.
4. THE BALANCE REPORT SHALL INCLUDE AS A MINIMUM THE FOLLOWING
INFORMATION:
A. AABC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF BALANCING
CONTRACTOR.
B. INSTRUMENTATION LIST WITH LAST CALIBRATION DATES.
C. MAKE AND MODEL MIMBERS OF ALL (HVAC EQUIPMENT TESTED.
D. AIR CFM AND STATIC PRESSURE READINGS (DISCHARGE AND SUCTION) AS
MEASURED BY PITOT TUBE DUCT TRAVERSE AT THE UNIT.
E. MOTOR NAMEPLATE DATA WITH ACTUAL FIELD VOLTAGE AND AMPERAGE
READINGS FOR EACH LEG.
F. MOTOR AND FAN RPMS, SHEAVE SIZES AND BELT SIZES.
G. OUTSIDE, RETURN. MIXED AND SUPPLY AIR TEMPERATURES AT FULL
COOLING.
H. WATER BALJANCE DATA INCLUDING GPM WITH INLET AND OUTLET
TEMPERATURE AND PRESSUE READINGS (WHERE APPLICABLE).
I. MAKE AND MODEL NUMBERS OF ALL AIR DISTRIBUTION EQUIPMENT.
J. FINAL BALANCED AIR VOLUMES AT ALL OUTLETS (INCLUDING RETURNS
WHERE DUCTED) .
K. INDEXED PLAN WITH DIFFUSER AD RETURN LOCATIONS.
L. REPORT SHALL INCLUDE VAV BOX AIRFLOW SENSOR DIFFERENTIAL PRESSURE
READING AT MAX. AND MIN. COOLING.
5. ALL CONTROL SEQUENCES SHALL BE TESTED (INTERLOCKED EQUIPMENT, SMOKE
DETECTORS, SMOKE EVACUATION, ECONOMIZER, ETC.) AND OPERATING STATUS
RECORDED IN THE REPORT.
6. THREE COPIES OF THE BALANCE REPORT SHALL BE SUBMITTED THROUGH THE
GENERAL CONTRACTOR TO THE TENANT'S CONSTRUCTION MANAGER FOR APPROVAL.
7. THE BALANCING CONTRACTOR SHALL PERFORM ALL APPLICABLE TESTING AND
BALANCING FUNCTIONS REQUIRED FOR THE SYSTEM DESIGNED IN THESE
DRAWINGS. THE BALANCING CONTRACTOR SHALL RECHECK ANY ITEMS THAT THE
TENANT DEEMS NECESSARY AT NO ADDITIONAL COST TO THE TENANT.
8. FINAL BALANCE REPORT SHALL BE INCLUDED IN THE OPERATION AU: MAINTENANCE
MANUALS.
FINAL HVAC INSPECTIONS
1.
ASIDE FROM NORMAL INTERIM INSPECTIONS OF WORK IN PLACE, THE TENANT
SHALL HAVE THE RIGHT TO AN INDEPENDENT HVAC CONTRACTOR INSPECT THE
FINISHED HVAC INSTALLATION UPON COMPLETION FOR COMPLIANCE WITH THE
PLANS, SPECIFICATIONS, AND CODES. THE INSTALLING CONTRACTOR WILL BE
RESPONSIBLE TO BRING ALL ITEMS REPORTED BY THE INDEPENDENT HVAC
CONTRACTOR UP TO PLANS AND SPECIFICATION REQUIREMENTS AT NO COST TO
TENANT.
REVIEWED FOR
'CODE COMPLIANCE
APPROVED
} AUG 0 2 2013
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JUL222013
PERMIT CENTER
M -Engineering
750 Brooksedge Blvd.
Westerville, Ohio 43081
phone: 614.839.4639
fax: 614.839.2222
WWW. MENGINEERING. US COM
All rights reserved. No part of these drawings
or specifications may be copied, reproduced
or used in connection with any work, other
than the specific project for which they have
been prepared, without prior written
authorization from the Architect.
ENGINEER OF RECORD:
J.CREW
Southcenter Mall
633 Southcenter Mall
Space No. 676
Seattle, WA 98188
Level: Ground Floor
Project No. 1339
Project No. 13411114
NO.
DATE
ISSUE
07-17-13
Issue for Permit
07-17-13
Issue for Bid
07-17-13 Issue for LL & Client
Review
Mechanical
Specifications
M-300