HomeMy WebLinkAboutPermit PG13-091 - BUFFALO WILD WINGS - ALTERATIONBUFFALO WILD WINGS
295 TUKWILA PKWY
PG13-091
City okukwila
f
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-431-2451
Web site: http://www.TukwilaWA.gov
Parcel No.: 9202470100
Address: 295 TUKWILA PY TUKW
Project Name: BUFFALO WILD WINGS
PLUMBING/GAS PIPING PERMIT
Permit Number:
Issue Date:
Permit Expires On:
PG13-091
10/01/2013
03/30/2014
Owner:
Name: WESTFIELD PROPERTY TAX DEPT
Address: PO BOX 130940 , CARLSBAD CA 92013
Contact Person:
Name:
Address:
Email:
JARED TAYLOR
10 S GRANT , ROSEVILLE CA 95401
JARED@GOLDENPD.COM
Contractor:
Name: SERVICE PLUMBING & HEATING INC
Address: 2100 196TH ST SW , LYNNWOOD WA 98036
Contractor License No: SERVIPH953QD
Phone: 805 440-7537
Phone: (425)640-2121
Expiration Date: 11/11/2013
DESCRIPTION OF WORK:
ABOVE THE SLAB PLUMBING AND GAS PIPING
AND KITCHEN WORK. SEE ALSO PG 13-073
NO SANITARY SEWER WORK OUTSIDE OF THE
PERMITTED UNDER THIS PLUMBING PERMIT.
FOR NEW RESTAURANT TO INCLUDE RESTROOMS
BUILDING INCLUDING GREASE INTERCEPTOR IS
Value of Plumbing/Gas Piping:
Fees Collected:
Electrical Service Provided by:
Permit Center Authorized Signature
I hereby certify that I have read and
governing this work will be complie
$30,000.00
$630.00
Uniform Plumbing Code Edition:
International Fuel Gas Code Edition:
2009
2009
Date: D
exami ed this permit and know the same to be true and correct. All provisions of law and ordinances
with, hether specified herein or not.
The granting of this permit does not pre e to give authority to violate or cancel the provisions of any other state or local laws regulating
construction or the performance of work. I am authorized to sign and obtain this plumbing/gas piping permit and agree to the conditions
on the back of this permit.
Signature:
Print Name:
Date: /
This permit shall become null and void if the work is not commenced within 180 days from the date of issuance, or if the work is suspended
or abandoned for a period of 180 days from the last inspection.
d.... 1 In!n A/1/1
P( 1 Q_no1
Printari• 1n_n1_7n1
PERMIT CONDITIONS
Permit No. PG 13-091
1: ***PLUMBING AND GAS PIPING***
2: No changes shall be made to applicable plans and specifications unless prior approval is obtained from the Tukwila
Building Division.
3: All permits, inspection records and applicable plans shall be maintained at the job and available to the plumbing
inspector.
4: All plumbing and gas piping systems shall be installed in compliance with the Uniform Plumbing Code and the Fuel Gas
Code.
5: No portion of any plumbing system or gas piping shall be concealed until inspected and approved.
6: All plumbing and gas piping systems shall be tested and approved as required by the Plumbing Code and Fuel Gas Code.
Tests shall be conducted in the presence of the Plumbing Inspector. It shall be the duty of the holder of the permit to
make sure that the work will stand the test prescribed before giving notification that the work is ready for inspection.
7: No water, soil, or waste pipe shall be installed or permitted outside of a building or in an exterior wall unless,
adequate provision is made to protect such pipe from freezing. All hot and cold water pipes installed outside the
conditioned space shall be insulated to minimum R-3.
8: Plastic and copper piping running through framing members to within one (1) inch of the exposed framing shall be
protected by steel nail plates not less than 18 guage.
9: Piping through concrete or masonry walls shall not be subject to any load from building construction. No plumbing
piping shall be directly embedded in concrete or masonry.
10: All pipes penetrating floor/ceiling assemblies and fire -resistance rated walls or partitions shall be protected in
accordance with the requirements of the building code.
11: Piping in the ground shall be laid on a firm bed for its entire length. Trenches shall be backfilled in thin layers to
twelve inches above the top of the piping with clean earth, which shall not contain stones, boulders, cinderfill,
frozen earth, or construction debris.
12: All new plumbing fixtures installed in new construction and all remodeling involving replacement of plumbing fixtures
and fittings in all residential, hotel, motel, school, industrial, commercial use or other occupancies that use
significant quantities of water shall comply with Washington States Water Efficiency and Conservation Standards in
accordance with RCW 19.27.170 and the 2006 Uniform Plumbing Code Section 402 of Washington State Amendments.
13: The issuance of a permit or approval of plans and specifications shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the Plumbing Code or Fuel Gas Code or any other ordinance of the
jurisdiction.
14: ***PUBLIC WORKS DEPARTMENT CONDITIONS***
15: Contractor shall notify Public Works Inspector Mr. Dave Stuckle at (206)433-0179 of commencement and completion of work
at least 24 hours in advance.
16: Sanitary side sewers shall be 6 -inch min. and no outside sanitary sewer work including 3 -inch waste vent is permitted
under this Plumbing Permit. Sanitary sewer work outside of the Building shall be part of a future Building Permit (or)
Public Works Permit.
17: Grease Interceptor installation is not permitted under this Plumbing Permit. Grease Intercpetor shall be part of future
Building Permit (or) future Public Works permit.
doc: UPC -4/10
PG 13-091 Printed: 10-01-2013
•
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd. Suite 100
Tukwila, IVA 98/88
http://ww•w.TukwilaW A.gov
PIu m bing/ras Permit'No.
Project No. f
Date Application Accepted: C(.#1)1.--. 13
I2- -13
Date Application Expires:
(For once use only)
PLUMBING / GAS PIPING PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
'SITE LOCATION
King Co Assessor's Tax No.: 9202470100
Site Address: Tikwila Parkway Suite Number: Floor: 1
Tenant Name: Buffalo Wild Wings
P,RQPERTY OWNER .
Name: Terry Womack
Name: Northwest Westfield Southcenter
Address: 10 S Grant Street
Address: 2800 Southcenter
City: Roseville State: CA
City: Seattle State: WA
Zip: 98188
CONTACT PERSON — person receiving all project
communication
Name: Terry Womack
Address: 10 S Grant Street
City: Roseville State: CA
Zip: 95678
Phone: (858) 652-0336 Fax:
Email: terry@goldenpd.com
State:
New Tenant: Yes ❑ ..No
PLUMBING CONTRACTOR INFORMATION
Company Name: TBD
Address:
City:
State:
Zip:
Phone:
Fax:
Contr Reg No.:
Exp Date:
Tukwila Business License No.:
Valuation of Project (contractor's bid price): $ 80,000
Scope of Work (please provide detailed information):
Demolition of existing building. The existing building pad will remain and new exterior walls and roof will be constructed with a
new fire sprinkler system. The new tenant will be a full service sit down restaurant with outdoor patio.
Building Use (per Int'I Building Code)- Restaurant
Occupancy (per lnt'1 Building Code): A2
Utility Purveyor: Water:
City of Tukwila
H:\Applications\Forms-Applications On Line \2011 Applications \Plumbing Permit Application Revised 8.9.11.docx
Revised: August 2011
bh
Sewer: City of Tukwila
Page 1 of 2
M
•
Indicate type of plumbing fixtures and/or gas piping outlets being installed and the quantity below:
Fixture Type
Qty
Bathtub or combination
bath/shower
0
Dishwasher, domestic with
independent drain
0
Shower, single head trap
0
Sinks
0
Rain water system — per
drain (inside building)
0
Grease interceptor for
commercial kitchen (>750
gallon capacity)
0
Each additional medical
gas inlets/outlets greater
than 5
0
Atmospheric -type vacuum
breakers not included in
lawn sprinkler backflow
protections (1-5)
1
Fixture Type
Qty
Bidet
0
Drinking fountain or water
cooler (per head)
0
Lavatory
0
Urinal
0
Water heater and/or vent
1
Repair or alteration of
water piping and/or water
treatment equipment
0
Backflow protective device
other than atmospheric-
type vacuum breakers 2
inch (51 mm) diameter or
smaller
1 1
Atmospheric -type vacuum
breakers not included in
lawn sprinkler backflow
protections over 5
0
Fixture Type
Qty
Clothes washer,
domestic
0
Food -waste grinder,
commercial
0
Wash fountain
0
Water closet
0
Industrial waste
treatment interceptor,
including trap and vent,
except for kitchen type
grease interceptors
0
Repair or alteration of
drainage or vent piping
0
Backflow protective
device other than
atmospheric -type
vacuum breakers over 2
inch (51 mm) diameter
0
Gas piping outlets
10
Fixture Type
Qty
Dental unit, cuspidor
0
Floor drain
0
Receptor, indirect waste
0
Building sewer and each
trailer park sewer
0
Each grease trap
(connected to not more
than 4 fixtures - <750
gallon capacity
0
Medical gas piping
system serving 1-5
inlets/outlets for a specific
gas
0
Each lawn sprinkler
system on any one meter
including backflow
protection devices
0
PERMIT APPLICATION NOTES -
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 186 days. The extension shall be requested in writing
and justifiable cause demonstrated. Section 103.4.3 International Plumbing Code (current edition).
1 HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND 1 AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER.DWAUTHORIZED AGENT:
Signature:
Print Name: Terry Womack
Mailing Address: 10 S. Grant Street
H:\Applications\Forms-Applications On Line \2011 Applications \Plumbing Permit Application Revised 8-9-1 I.docx
Revised: August 2011
bh
Date: 05/08/2013
Day Telephone: (858) 652-0336
Roseville CA 95678
City State Zip
Page 2 of 2
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-43 1-3670
Fax: 206-431-3665
Web site: http://www.Tukwila WA.gov
Parcel No.: 9202470100
Address: 295 TUKWILA PY TUKW
Suite No:
Applicant: BUFFALO WILD WINGS
RECEIPT
Permit Number: PG13-091
Status: APPROVED
Applied Date: 06/24/2013
Issue Date:
Receipt No.: R13-02784
Initials:
User ID:
JEM
1165
Payment Amount: $504.00
Payment Date: 10/01/2013 12:25 PM
Balance: $0.00
Payee: SERVICE PLUMBING & HEATING
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Check 6154 504.00
Authorization No.
ACCOUNT ITEM LIST:
Description
Account Code Current Pmts
GAS - NONRES
PLUMBING - NONRES
000.322.103.00.00 131.25
000.322.103.00.00 372.75
Total: $504.00
dr,-• Roroint-(1A
Printed: 10-01-2013
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206-431-3665
Web site: http://www.TukwilaWA.gov
RECEIPT
Parcel No.: 9202470100 Permit Number: PG13-091
Address: 225 TUKWILA PY TUKW Status: PENDING
Suite No: Applied Date: 06/24/2013
Applicant: BUFFALO WILD WINGS Issue Date:
Receipt No.: R13-01946
Payment Amount: $254.62
Initials: JEM Payment Date: 06/24/2013 09:35 AM
User ID: 1165 Balance: $1,018.50
Payee: JACOB FLYNN, GOLDEN PROP DEV LLC
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 02696G
ACCOUNT ITEM LIST:
Description
254.62
Account Code Current Pmts
PLAN CHECK - NONRES
000.345.830 254.62
Total: $254.62
a....• Dnnein!_11A
Printed: 06-24-2013
INSPECTION N0.
INSPECTION RECORD
Retain a copy with permit'
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION G
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
\
Permit Inspection Request Line (206) 431-2451
Project:
P)U F=,a. IL, . ck.w:„7s
Type of Inspection:
P 1., . f-; ,va
Address:Date
Z__ 6i S l _ V iC D AI A
Called:
Special Instructions: I
Date Wanted:
rr ,,//
I — Zr — 1"C"
`.
P.m.
Requester:
Phone No:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:.
r) JM'.1,5 A, ltYP
I a
Inspector:
Date:
1- z 4- -(4
REINSPECTION FE ' EQUIRED. Prior to next inspection. fee must be
paid at 6300 Southce ter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retaina copy with permit
INSPECTION -NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Project: t +
Type of lnspectio -1
Add s - 1
Z. l D i v 1- p4rlcw,t .
Date a led:
r lv A.k. RLC
ri /
Special. Instructions:. ' Y
DPhone
Date.Wanted:— �} _ I -
G..i �:
!air
p.m.
Requester:
No:
Approved per applicable codes.
Corrections. required prior to approval.
COMMENTS:
r
O,,t,JN (A) I t
A--i\5u ( AI r (c; t(: .-e/ttilic2Do
Inspectgf:
REINSPECTION FEE REQtJIRED.'
.Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Date:
INSPECTION RECORD
J. Retain a copy with permit
INS CTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Projec : +
U N& 1-_ Ali iJ.,.. 7
Type off Inspection:
4 Iki rL.--
Address: A-
.1--1444,0'L,
-•`-'1 1--1444,0'
-
i
Date Called:
Special. Instructions:
Date Wanted:
a.m.
Requester:
Phone No:
EJApproved per applicable codes.Corrections required prior to approval.
COMMENTS:
r1 �ttLi,o t 1Cs — Y y1�l ,tJ6c
,), 13*.rilac --10-1;‘J Oe S
t P6n (LIY--43.peo-,I .
Da e_ s.- - ' I
RENSP CTION FEE REQUIRED. Prior t next inspection. fee must be
pai s - 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206)431-2451
pG t3 -oq 1•.
Projeu:TYP
(5L(i—rh(- I(J.
of Inspection: _
RtSM21 —ihJ
Address:_ r. j(�
')..Ct-5 11;�4�l�llA. + "_ t
Date Called:
Special Instructions:
Date W nted:.
Z-•�
2�
t ,sp.m.
!...).n
Requester:
Phone No:
•
Approved per applicable codes '\
Corrections required prior to approval.
COMMENTS:
• 1
Inspector
Date:
1Z
2v
litEq PECTION_ FEE.REQUI.RED' rior..to next hspection. fee must be
04at 6300 Southcenter Blvd.. Suite 100. Dalt to schedule reinspection.
INSPECTION N0.
CITY OF TUKWILA- BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit_ Inspection Request Line (206) 431-2451
INSPECTION RECORD
Retain a copy with permit
p&t -093
PERMIT NO.
Pr ect .r
6.–/VI—A-1--0 .4•1 �/�&S
.
Tyjof Inspectioni S.
i �--1�' 6a 1V (\i 6-
Addre ,,_
b "uta
(
irk
Au._
Date Called:
--
Special Instructions:
..
/
///
Date Wanted:
' Z
(41 13
p.m.
Requester:
Phone No:
ElApproved per applicable codes.
Corrections required prior to approval.
COMMENTS:
1;
z_s (--oco-rdp
(s DA ( .
Q) c3K-
40.
Inspector:
Date - (0
n REINSPECTION .EE REQUIRED. Prior to nextinspection. fee must be ._
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection:
�ERMIT COORS COPP
PLAN REVIEW/ROUTING SLIP
ACTIVITY NUMBER: PG13-091 DATE: 06/24/13
PROJECT NAME: BUFFALO WILD WINGS
SITE ADDRESS: 225 TUKWILA PY
X Original Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #_
Revision # after Permit issued
DEPARTMENTS:
02'13
Building Division
Pub it c Works t- °if 9-11
Fire Prevention
Structural
❑
Planning Division
❑ Permit Coordinator ❑
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete Ur
Incomplete ❑
DUE DATE: 06/25/13
Not Applicable ❑
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED:
Departments determined incomplete: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
LETTER OF COMPLETENESS MAILED:
TUES/THURS ROUTING:
Please Route Structural Review Required ❑ No further Review Required ❑
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved ❑
Notation:
DUE DATE: 07/23/13
Approved with Conditions Not Approved (attach comments) ❑
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections:
Bldg 0 Fire 0 Ping 0 PW 0
Staff Initials:
Contractors or Tradespeople Ater Friendly Page
General/Specialty Contractor
A business registered as a construction contractor with MI to perform construction work within the scope of
its specialty. A General or Specialty construction Contractor must maintain a surety bond or assignment of
account and carry general liability insurance.
Business and Licensing Information
Name
Phone
Address
Suite/Apt.
City
State
Zip
County
Business Type
Parent Company
SERVICE PLUMBING a HEATING INC
4256402121
2100 196Th St Sw
Ste 136
Lynnwood
WA
98036
Snohomish
Corporation
UBI No. 602238671
Status Active
License No. SERVIPH953QD
License Type Construction Contractor
Effective Date 11/4/2005
Expiration Date 11/11/2013
Suspend Date
Specialty 1 General
Specialty 2 Unused
Other Associated Licenses
License
Name
Type
Specialty
1
Specialty
2
Effective
Date
Expiration
Date
Status
WASSEP*95108
LLQ SER PLUMBING
Contractor
Plumbing
Unused
9/28/2005
9/28/2009
Expired
AKAMAHL955KZ
LLCAMAI HOMES
Contractor
General
Unused
5/9/2005
5/9/2009
Expired
MILLEBC999CZ
MILLENNIUM
BUILDING CO INC
Contractor
General
Unused
2/9/2001
2/9/2008
Expired
SERVIPH982P2
SERVICE PLUMBING
& HEATING
51,000,000.00
General
Unused
10/22/2002
10/22/2006
L e-
Licensed
Business Owner Information
Name
Role
Effective Date
Expiration Date
DICKINSON, PATRICK C
President
11/04/2005
Amount
PRUITT, CYNTHIA M
Secretary
11/04/2005
BKA54871662
Bond Information
Page 1 of 2
Bond
Bond Company Name
Bond Account Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Bond Amount
Received Date
1
RLI INS CO
SRS1008634
10/05/2005
Until Cancelled
$12,000.00
11/04/2005
Assignment of Savings Information No records found for the previous 6 year period
Insurance Information
Insurance
Company Name
Policy Number
Effective Date
Expiration Date
Cancel Date
Impaired Date
Amount
Received Date
5
American Fire
a Casualty Co
BKA54871662
09/01/2012
09/01/2014
51,000,000.00
07/31/2013
4
Continental
Western Ins Co
CNP2772886
09/01/2008
09/01/2012
51,000,000.0008/02/2011
3
AMERICAN
STATES INS CO
01CG909337
10/21/2007
10/21/2008
51,000,000.00
09/21/2007
2
AMERICAN
STATES INS CO
01CG909337
10/21/2006
10/21/2007
$1,000,000.0009/21/2006
Summons/Complaint Information No unsatisfied complaints on file within prior 6 year period
Warrant Information No unsatisfied warrants on file within prior 6 year period
Infractions/Citations Information
httos: //fortress. wa. aov/lni/bbip/Print. aspx
10/01/2013
2410 Mariner Square Loop
Alameda,CA 94501
Tel 510 865 8663
Fax 510 865 1611
Elmendorf & Associates
Mechanical Engineers
2518 East Bay Drive, NW
Gig Harbor, WA 98335
253-514-6036
PROVIDE NEW 2\ PSI C A5 METER PER OAS
COMPANY STAND RDS OAS LOAD 15
2055 MBH, DISTANCE FROM METER TO
OST REMOTE \S\PRESSURE
UR
RESULATORT ULATORT 15 LESS THAN 200 FEET
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL 0 3 2013
City of u ifa
BUILDING !SION
STORE DESIGN
5500 WAYZATA BLVD. STE 1600
MINNEAPOLIS, MN ; 55416
PHONE 952.593.9943
FAX 952.593.9787
DO NOT SCALE DRAWINGS
CONTRACTOR TO VERIFY
ALL EXISTING CONDITIONS
AND DIMENSIONS—NOTIFY
ARCHITECT OF ANY
DISCREPANCIES PRIOR TO
BEGINNING CONSTRUCTION
FILE COPY
Pont* No. 1? r'l 4 \
Pkss review approval is subject to errors and omissions.
Ap?roval of con ruction documents does not auttrs
thEiolation of any adopted code or ordinanc6.
of approved FieldCopy and consisac u wledga
Bykc;,*. S 1W\w'vt31.5
D i (D-1-- VS
City Of lbla
BUILDING DIVISION
r7
CO
LJ
(f)
Cf)
DESCRIPTION
O
z
J
m-
J
cki
w
0
m
D
J
0
O
W
BUILDING SUBMITTAL
SEPARATE PERRLT
(gyREDU1RED POR;.
e t, at
Metrical
Plumbing
o Gas Piping
City of Tukwila
BUP.PING DIVISION
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
Nle: F v s;ons;wiil require a new plan submittal
and may in:;:ude additional plan review f es.
CONDENSATE DRIAN
PIPING IN WALL FRAMING
OR EXPOSED
SPILL CONDENSATE
DRAIN PIPING INDIRECTLY
OVER FLOOR SINK
ill
" PROVIDE
P -TRAP WHEN
REQUIRED.
PROVIDE ROUND SECURED NICKEL BRONZE ADJUSTABLE
TOP WITH "CO" CAST IN COVER. PROVIDE CLEANOUT TOP
WITH VARIATIONS SUITABLE FOR FLOOR COVERING (CARPET
MARKER, RECESSED FOR TILE, SCORIATED FOR UNFINISHED.
FLOORS). PROVIDE BRONZE PLUG IN CAST IRON BODY.
MEMBRANE CLAMP
AS REQUIRED FOR
DEPTH OF SEWER
HUB AND SPIGOT
SCHEDULE 40 PVC 1
BELOW FLOOR
SANITARY OR STORM
SEWER' LINE
•. •
SAME SIZE A5 SEWER
UP TO 4" MAXIMUM
LONG SWEEP ELBOW AT
END OR TURN OF RUN
COMBINATION WE AND
EIGHTH BEND IN RUN:
ENTER TOP OF PIPE
• — • i•i �0�� Q DIRECTION
OF FLOW
LOCATE AT BUILDING EXIT, AT ENDS OF RUNS, AT TURNS
OF PIPE GREATER THAN 45 DEGREES, AT 50' INTERVALS
ON STRAIGHT RUNS, AND WHERE SHOWN ON PLANS.
PROVIDE BACKFILL PER ARCHITECTURAL SPECIFICATIONS.
LOCATE CLEANOUTS WHERE THERE I5. I8" CLEAR AROUND.
CONSULT LOCAL CODES FOR OTHER FCO REQUIREMENTS.
FLOOR
- TURN ELBOW
OUT OVER DRAIN
FLOOR SINK
GOND. TERMINATION
Scale: NONE
PROVIDE CLEANOUTS IN
TURNS/ENDS OF PIPE. US
DWV FITTINGS IF SIZE
IS LARGER THAN 1"
SLOPE PIPE
AS MUCH AS
POSSIBLE
TOWARD
DISCHARGE
MAKE CONNECTION
TO EQUIPMENT.
AS REQUIRED
MAKE PIPE MINIMUM ONE SIZE
LARGER THAN EQUIPMENT CON-
NECTION, MINIMUM 3/4". USE "M"
OR "L" HARD COPPER UP TO 1"
AND TYPE DWV FOR LARGER
FLOOR CLEANOUT
Scale: NONE
2'-0"x 2'-O"x 4" THICK—
CONCRETE COLLAR WITH
#4 RE -BAR EACH WAY
UNLESS SET IN SLAB.
CHAMFER EDGE
COMPACTED EARTH
SCHEDULE 40 PVC
NOTE:
THIS DETAIL SIMILAR
FOR ONE-WAY. CLEAN
OUT TO GRADE.
DISCHARGE INTO CENTER
.HOLE OF GRATE OF WASTE
RECEPTICALE WITH AIR GAP
SUFFICIENT TO REMOVE GRATE
AND STRAINER. MINIMUM
GAP = TWO PIPE DIAMETERS
VERIFY WITH LOCAL
CODES IF/WHEN TRAP
AND/OR VENT ARE RE-
QUIRED FOR THE LENGTH
OF DRAIN PIPE INSTALLED
ROUTE PIPE INCONSPICUOUSLY AND UNOBTRUSIVELY. HANG
PIPE AS REQUIRED. DO NOT INSULATE INDIRECT DRAIN PIPE
WHEN INSTALLED EXPOSED IN FOOD SERVICE FACILITY.
REFER TO LOCAL CODES FOR FURTHER INFORMATION.
TYPICAL INDIRECT DRAIN FROM EQUIPMENT. 7
ALL INDIRECT WASTE DRAIN PIPING SHALL
TERMINATE WITH A 45' ANGLE CUT,
TYPICAL REMOVE ALL BURS AND FILE DOWN
SHARP EDGES.
PROVIDE ONE PIECE SPUN ALUMINUM BASE WITH, GRADULATED
STEPPED PVC BOOT, AND ADJUSTABLE STAINLESS STEEL CLAMPS.
SET BASE IN BED OF MASTIC
REFER TO ARCHITECT'S
DRAWING FOR APPLICATION
OF VENT PIPE BOOT
INSTALLATION WITH
ROOFING MATERIAL
MINIMUM 12" ABOVE ROOF
III III
III III
ROOF DECK
PROVIDE SLEEVE IF
REQUIRED BY TYPE
OF ROOF DECK
MINIMUM 12" BELOW ROOF
ANCHOR PIPE. TO ROOF
DECK OR JOISTS WITH
U -BOLT AROUND PIPE
AND ANGLE IRON
WELDED OR SCREWED TO
DECK OR JOIST
REFER TO PLANS FOR VTR PIPE SIZES AND LOCATIONS. LOCATE VTR
MINIMUM TEN FEET HORIZONTAL OR THREE FEET VERTICAL ABOVE ANY
BUILDING OPENING OR FRESH AIR INTAKE, AND ONE FOOT FROM ANY
VERTICAL SURFACE. PROVIDE 1" FIBERGLASS INSULATION WITH ALL
SERVICE JACKET ON VENT PIPEINSIDE BUILDING WITHIN SIX FEET OF VENT
THRU ROOF LOCATION. VERIFY FLASHING AND CONTERFLASHING WITH
ROOFING CONTRACTOR.
ND I iZEGT RA I N
Scale: NONE
VENT PENETRATION
Scale: NONE
ANCHOR -. PER NEPA
NOTE:
EIALDI146 STRUCTURE MAY VARY
MATCH INSTALLATION TO BALDING
STRICTURE REFER TO STRUCIURAL DRAWING FOR
ATTACWENT.
3/8" ALL -THREAD ROD FOR <-4" PIPE.
FOR LARGER PIPE SIZES SLC NFPA 15.
HANGER - GRINNEL FIG. EA
ON INSULATED PIPE. PROVIDE
PIPE SUPPORT SHIELD.
PIPE HANGER DETAIL
Scale: NONE
PVC TRAFFIC RATED
CLEANOUT FITTING
FINISH
GRADE
IF llilljar/leV
QIII IMI4\`4
IIS
DEPTH AS
REQUIRED
SEE PLANS FOR
MAIN SIZE
CAST IRON
TWO-WAY CLEANOUT
Scale: NONE
NOTE: 2-1^1AY CLEANOUT SHALL ALL SE
CAST IRON
J
FINISHED WALL SURFACE
1
✓
THREADED CLEANOUT
FLUSH CLEANOUT CAF
SCHED. 40 PVC
2' CLEANOUT
TEE FITTING.
ACCESS COVER
AND FRAME
A
CLEANOUT WITH ACCESS
COVER INSTALLED IN A
STANDARD 3W METAL
STUD WALL
WALL CLEANOUT
Scale: NONE
DWV COPPER ONLY,
NO PVC ALLOWED
TYPICAL INDIRECT
DRAIN FROM
EQUIPMENT.
4
•
.44
• 'A•
•
n•
— WALL MOUNTED PIPE
SUPPORT REF. 9/P101
Il Il ll II Il l
J
FLOOR UNE
e: p p:
�r
A'
A
>' c• P
A
—I I
1 I I- I 1=111=111=11
111-11 1111-111—
=111=111 I=111 11
111-111=111 I- FLOOR SINK
111-111-111-111—I 11
111-111-111-111-111-111
—111-111-111-111-111-1
111=111-111-111-111111
FLOOR SINK DETAIL
Scale: NONE
SILICONE SEAL
AROUND' PIPE
PENETRATION
PROVIDE TRAP
AT BOTTOM OF
RISER AND DIS-
CHARGE INTO
FLOOR SINK WITH
AIR GAP OF TWO
PIPE DIAMETERS
FLOOR
FLOOR
SINK
CO.
PROVIDE 1" ELASTOMERIC INSULATION OVER HEAT
TRACING ON CONDENSATE UNE - IF/WHEN FREEZER/
COOLER BOX ONLY - (ELEC.`HEATING CABLE IS BY OTHERS)
DX COIL
CO
\'''`•- PROVIDE CLEANOUT
IN TURNS AND ENDS
OF PIPE
MAKE CONNECTION
TO COIL AS REQUIRED
NO INSULATION ON PIPE RISER
WALK-IN COOLER OR FREEZER BOX
SEE FLOOR
PLAN FOR RECEPTACLE LOCATION.
INSTALL PIPE HIGH AS POSSIBLE, ANCHORED TO WALL OF BOX WITH SUPPORTS AT
MAXIMUM SIX FOOT CENTERS. USE TYPE "M" HARD COPPER TUBE AND FITTINGS WITH
LEAD-FREE SOLDER JOINTS. SLOPE HORIZONTAL PIPE AT MINIMUM TWO PERCENT.
REFER TO LOCAL CODE FOR INDIRECT DRAIN REQUIREMENTS.
CONDENSATE DRAIN
Scale: NONE
WALL/EQUIVALENT STRUCTURE
WASTE PIPE TO
SINK/FIXTURE . ABOVE
FASTEN 3-5/16" X 1-3/8" CEILING
FLANGE TO WALL STRUCTURE 6" AFF
3/8" MINIMUM
THREADED ROD
IIllUII111Ulilll IUlIL1111(11(llIIIIIIW1
Ilnlnu►ui u
�OI
PIPE CLAMP '
NOTE: TRIANGULATE BRACING
WASTE PIPE TO
FLOOR SINK BELOW
PIPE SUPPORT DETA I L
Scale: NONE
VENT HEIGHT TO BE
1/2' LOWER THAN TOP
OF DRAIN PAN
2410 Mariner Square loop
Alameda, CA 94501
T e I 510 865 8663
Fax 510 865 1611
Elmendorf &Associates
Mechanical Engineers
2518 East Bay Drive, NW
Gig Harbor, WA 98335
253-514-6036
STORE DESIGN
5500 WAYZATA BLVD. STE 1600
MINNEAPOLIS, MN 55416
PHONE 952.593.9943
FAX 952.593.9787
ON DRAW THRU UNITS
X = UNIT TOTAL STATIC
PRESSURE + 2
Y = 3" MIN.
ROOF
c) 1:-: 2 ce cc'g
o Wa>
_ W
UH " § -
p N :I—
CO CI
INSULATED CONDENSATE
//N//g
PIPING
RUN CONDENSATE PIPING DOWN
THRU ROOF TO JOIST SPACE
GONDNSATE CONNECTION
Scale: NONE
REVIEWED FOR
CODE COMPLI
APPROVED
JUL 0 3 :.2013...
City of Tukwila
BUILDING DIVISION
DO NOT SCALE DRAWINGS
CONTRACTOR TO VERIFY
ALL EXISTING CONDITIONS
AND DIMENSIONS—NOTIFY
ARCHITECT OF ANY
DISCREPANCIES PRIOR TO
BEGINNING CONSTRUCTION
W
r()
L l
z
0
W
I—
Q
0
K)
CO
M
CO
DESCRIPTION
DEMO, PLUMBING & HEALTH SUBMITTALS
BUILDING SUBMITTAL
O
z
PROJECT NUMBER
RECEIVED
CITY OF TUKWILA
JUN 242013
PERMIT CENTER
SHEET NUMBER .
P101
2410 Mariner Square loop
Alameda, CA 94501
T e I 510 865 8663
Fax 510 865 1611
Elmendorf & Associates
Mechanical Engineers
2518 East Bay Drive, NW
Gig Harbor, WA 98335
253-514-6036
.1/4" 6AS SEE CIVIL
DRAHIN65 FOR GONTINJATION
REVIEWED FO's
CODE COMPLIANC
APPROVED
'— 2-1/2" CH SEE CIVIL
DRAWIN65 FOR
CONTINUATION
u3JCfs , ,�
1.1/4' 6A5 UP TO
2-1/2"GW
I/2"FCN
1/2"GW
2'GW
,;%' j
6
STORE DESIGN
5500 WAYZATA BLVD. STE 1600
MINNEAPOLIS, MN 55416
PHONE 952.593.9943
FAX 952.593.9787
2'HH,
I'GH, 8 FU
"HH, 8 W
I'CH, 13 RJ
1"HW,12FU
54 FU
2'F114, 72 R1
11/2" CA5
14M$H
I/2'CN4HW
3/4'GWBHW
I"GW,8FU
'EGOLAB FOR
DISHMACHINE
J
0J
LL
CO
>-
J
Q 0�0
IL: Q SS
Q Q
o w�w
Q w.
o
On
(/) N
TO EGOLA5 •.-
CLASS HASHER
,4 COMP SINK
- I
-I/2"011, 40
2'4W, 54 FU
"GH, 18 FU
"HW, 28 PU
3/4"HWR
1/2"PGH
(334)
DO NOT SCALE DRAWINGS
CONTRACTOR TO VERIFY
ALL EXISTING CONDITIONS
AND DIMENSIONS—NOTIFY
ARCHITECT OF ANY
DISCREPANCIES PRIOR TO
BEGINNING CONSTRUCTION
32
V RACK
3/4"GH, b PU
I"HH,10Fl)
I-I/4'GW, Ia
0
CT -0
U)
F)
co
GK VALVES
)VE CEILING
�). /
3/4"GW, 6 R1
"H11, 10 FL)
I-I/2'GW, 30
-1/2"HW, 44
DESCRIPTION
O
BUILDING SUBMITTAL
PROJECT NUMBER
RECEIVED-
CITY OF TUKWILA
JUN 2 4 2013
PERMIT CENTER
1317
SHEET NUMBER
P200
x
X
X
X
CEILING
CHECK VALVES TO
STOP HOT 4 COLD
WATER TRANSFER.
WATTS MODEL
OOgOT-S (1/2")
REDUCED PRE-5SUF
ZONE BACKFLOW
PREVENTER . WITH
"Y" STRAINER
FLOOR"
MOP SINK
FAUCET
MOPSINK
EGOL
RPZ
1/2" TEMPERED
WATER SUPPLY
TO EGOLAB
-1/2'
DRAIN:
1/2" QUARTER
TURN BALL
VALVE
'-0' A.F.F. MAX'
FRONT VIEW
AT MOP SINK
NOTE:
CEILING
1/2" HW
1/2" GW -
ECOLAB
RPZ VALVE AT
ECOLAB WATER
SUPPLY: GONNiCTIO
THERMOSTATIO-
MIXING VALVE
MOP SINK
FAUCET
42" A.F.F.
MOP SINK
L:
0
OPTIONAL VERIFY WITH OWNER.
SIDE VIEW
AT MOP SINK
R1 C1
R2C1
R1C3
R2C3
OWER 114E THERMOSTATIC MIXING VALVE WITH MAXIMUM TEMPERATURE FACTORY PRE SET AT120°F.
ECOLAS
WATER SUPPLY DPTAIL
Scale: NONE
4"m AL2414C 5TAINLE55 STEEL
FLUE WITH GOOSENECK
ROOF
EXPANSION` TANK
AMTROL ST -12-C :
INSULATE WATER PIPING
FLUE THRU ROOF
SEE INSTALLED
BY PLUMBER
COMBUSTION AIR THRU RR
INSTALLED BY PLUMBER
A.S.M.E. TEMP.
PRESS. RELIEF VALVE
SIZE A5 SHOWN—
ON FLOOR PLAN
FULL SIZE T • P RELIEF
LINE TERMINATE AT FLOOR
DRAIN IN G
GAS VALVE
t
DIRT LE
1
,
cI�
WH -1
11
4". AL2'I4C STAINLESS .STEEL
OUTSIDE AIR INTAKE WITH GOOSENECK
-TEMPERATURE
GAUGE (TYPICAL)
GATE VALVE (TYP)
SIZE AS SHOWN ON FLOOR PLAN
140•F .WATER SUPPLY TO FIXTURES
CHECK VALVE (TYP.)
SOFTENED WATER TO
WATER HEATER
RECIRCULATING PUMP
GRUNFOS CIRCULATING PUMP
MODEL * UPI5-165F (3/.�")
6 6PM 0 1'-O" OF HEAD
120V/10/60Hz
VA
4" P .AL294C STAINLESS
STEEL COMBUSTION AIR AND
FLUE
CHECK VALVE (TVP.)
BALL VALVE (TVP)
AIR RELEASE VALVE
SECURE WATER HEATER WITH TWO 14 6A X 2"
IJJSTRAPS AND SECURE TO WALL FRAMING USING
3/6" X 2-1/2" LA& BOLTS, STRAPS TO BE AT
UNION (TYPICAL) TOP I/3 OF TANK AND .BOTTOM I/3 OF TANK
DRAIN VALVE W/HOSE CONNECTION
FLOOR
FLOOR SINK'
NOTES:
— 5/4" DRAIN PAN LINE
TERMINATE AS SHOWN
ON FLOOR PLAN
• INSTALL WATER HEATER ON 4"x36"x36
CONCRETE TILED CURS. CURB BY
6ENERAL.CONTRACTOR
PAN BY PLUMBING CONTRACTOR
1. PROVIDE AND INSTALL CONDENSATE DRAIN PIPING FROM WATER HEATER VENT PIPING PER
MANUFACTURES RECOMMENDATIONS.
2. PROVIDE AND INSTALL EXHAUST AND COMBUSTION AIR PIPING AS REQUIRED PER MANUFACTURES
SPECIFICATIONS.
3. CONTACT MANUFACTURE FOR START UP AND TO CONFIRM WATER HEATER HAS BEEN PROPERLY
INSTALLED.
DESIGNATION
GFH
INPUT
DOMESTIC WATER HEATER
GPM. RECOVERY
100°F
WTR HTRJ
STORAGE TANK
WH -1
Idiot
NATURAL GAS
A.O. SMITH CYCLONE MODEL * BTH - IP{g
PRESSURE RELIEF 125 PSI 100 GALLON STORAGE
SEALED DIRECT VENT AND COMBUSTION AIR
EXPANSION TANK - AMTROL MODEL * ST -12-C
NOTES:
I. THIS SYSTEM 15 TO BE SET UP TO DELIVER I40°F HOT WATER.
2. CONTACT MANUFACTURE FOR START UP AND INSTALLATION INSPECTION..
5. PROVIDE AQUASTAT PUMP CONTROLLER AND TIME CLOCK FOR NIGHT SHUT DOWN CONTRD
WATER HEATERS 1=IPIN6 DETAIL
Scale: NONE
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUL 0 3 2013.
City of Tukwila'
BUILDING DIVISION
2-1/2" C
PRES
GAUGE
WATTS 3/4" 530
C PRESSURE
RELIEF VALVE
WATTS ' I", 223 PRESSURE
REDUCING VALVE WITH
STRAINER SET AT 61 P5
" GW
1" CW
FULL PORTED
BALL VALVE
2" GW
2-I/2". GW
FULL - PORTED
BALL VALVE
"I
_ G
1
2" CW
MOUNT A55EWM15LY
TO WALL
ql
2-1/2" CW
PRESSURE
GAUGE
FULL PORTED
BALL VALVE
NOTE: CONTRACTOR
SHALL CONFIRM
EXISTING
PRESSURES AND
ADJUST PRESSURE
REDUCING VALVES `.
FOR PROPER
OPERATION
2-I/"
WATTS
GW
WATTS 2 ", x`225 PRESSURE
REDUCING VALVE WITH
STRAINER'SET AT 51 P5I
PRESSURE REDUG I NG SrrATI ON
Scale: NONE
NOTE: CONTRACTOR SHALL
PROVIDE B -LINE SUPPORTS
AT SPACING INTERVALS A5
SCHEDULED IN THE
PLUMBING SPECIFICATION
B -LINE STV SERIE
PIPE CLAMP
5 -LINE G -PORT
G-6 SERIES
ROOF SUPPORT.
6A5, CONDENSATE,
REFRIGERATION PIPING:
P1 PE ON ROOD SUPPORT
Scale: NONE
PROVIDE SHUTOFF VALVE ON ROUGH -.IN
BACKFLOW PREVENTOR
CONNECT TO CUBER
AND ICE BIN DRAIN
OUTLETS AS
REQUIRED
TRUN DOWN AND
SPILL INDIRECTLY
INTO FLOOR SINK
FLOOR
CUBER
ICE BIN
IW
IW
- FILTERED WATER
SUPPLY DOWN IN
PARTITION! WHERE
SHOWN ON PLAN
-ADAPTER AND SIX
FOOT LONG, 1/2"0
REINFORCED FOOD
GRADE PLASTIC
TUBING TO CURER
WATER INLET.
INDIRECT DRAIN OPEN
TO ATMOSPHERE AT
UPPER END
FLOOR SINK
PROVIDE AIR GAP OF
TWICE PIPE DIAMETER
PROVIDE FILTERED WATER ROUGH -IN AT TOP OF ICE MACHINE. ARRANGEMENT
SHOWN IS SCHEMATIC._ ADJUST AS REQUIRED TO SUIT CONDITIONS. VERIFY
CONNECTIONS WITH :MANUFACTURER.
ICE MACHINE
Scale: NONE
SUPPLY`
UNION
UNION
GAS COCK
-1/
—A.C.UNIT
///
DRIP/DIRT LEG
r—,
ROOF-
PIPE SUPPORT
SEE DETAIL
RTU'' GA5
CONNECT ON
Scale: NONE
1' DOMESTIC COLD WATER P
HARD COPPER EINE
(---3/4"
-L�
r
3/4' FILTERED COLD WATER--
W,RD COPPER UNE
3/4"
REDUCE TO
1/2' PRIOR
TO FILTER
•I■.
SHUT OFF VALVE
BY GC 1YP
3/4'
TEMPORARY FILTERS TO BE
INSTALLED BY BWW VENDOR I
DURING INSTALLATION MID
REPLACED WITH' NEW PERMANENT •
FILTERS DURING TRAINING 1
-IN NI
•Inomisr
I DL�1I WCHINE
1 SELLITO
EQUPWENT-PROVIDED BY BWW
FURNISFED AND NSTALLED 0113OR INSTALLED BY CC
BY GENERAL CONRRACTOR LOCATED NEAR ICE WENN&
3/4'
REDUCE TO
1/2' PRIOR
TO FILTER
3/4'
LOCATED NEAR COKE STATION
FURNISHED ANO INSTAUED EQUPIENI PROMDED BY ea FURNISHED MD INSIAUB
BY GENERAL-COMRACTTOR ; VENDOR INSTALLED BY GC BY'COKE VENDOR
�BYGC�
REDUCE 1D
1/2' PRIOR
TO FUER
(75L -1I
- SHUT OFF VALVE
BY GC 1YP
MANIFOLD
•TEWFORARY FILTERS TO BE
INSTALLED BY BWW VENDOR
1
TEMPORARY FILTER TO BE INSTALLED
BY MI VENDOR DURING NSFALLATION
MD REPUCED WITH 2 NEW PEMAIIENT I
FLIERS EARNING TRAINING —..
1
1-
I
1
BEVERAGE FLTRATKNN
5E1E10
SMF IC614-2
COKE VENDOR SCOPE NOTES:
3/4' TUBE --)1
STAINLESS . STEEL RPZ BFP
WATTS SSOO9QT--S BY GC
1YP AT EQUIP. COIINECIION
COI(: TECHS NIL INSTALL 1/2' BEVERAGE UNE FROM THE BEVERAGE FLIER SYSTEM TO 1W MANFOU)
CONTE-TECHS.VAL INSTALL BEVERAGE ERNE FROM THE MNELD TO HE CATBINATORS
COKE TECHS WILL NLSTALL LINES TO VARIOUS SODA STATIONS
COKE TECHS WILL START UP THE BEVERAGE. SYSTEM MD—CHECK FOR LENS AND PROPER OPERATION
BEVERAGE INNES WILL RUN OVER HEAD - GC TO PRONE LIFT FOR VENDOR USE IN UISTAL1AI)ON
GC PWMBER SCOPE NOTES:
� 10 CONTRICT SEIM i 7JEUNG ARAM w RBS
GC PLUMBER *11 TEST: WATER PRESSURE 1O VERIFY LONGEMY OF FILTERS
KITCHEN EQUIPMENT VENDORWILLSTART UP 1HE ICE MAKER AND CIECI( FOR LEAKS
REMANWG SCOPE, SCHEDULING AND COORDINATION BY GENERAL MD PWMBNG CONTRACTOR
FRANCHISEES NOTES:
WATER FL1RATION AND ROVING OF LANES OPTIONAL FOR FRANCHISEES
CONTACT COCA-COLA F THE FRANCHISEE WOULD LIKE TO PURCHASE A WATER FILTRATION SYSTEM
DCV BFP WATTS 007QT BY GC
TYP AT EQUIP. CONNECTION
FURNISHED MD INSTALLED
BY GENERAL CONTRACTOR
SHIM OFF VALVE
BY GC 1YP
.
3/4
DURING INSTALLATION AND
REPLACED WITH NEW PERMANENT
1
ANEN
FILTERS DURING TRNNNG 1 I
u
ICE MAX R FILIRATIDN
SELECTO
SMF 11614
1
1
3/8' TUBE J
3/8■.TUBE-'
-'3/8" TUBE
3/8' TUBE.
SHUT OFF VALVE TYP
1/2' TUBE
3/8" TUBE
0
r
-11111)
3/8' TUBE
0
®
CARBONATOR PUMP CARBONATOR PUMP
WF -
WATER FILTER
Scale: NONE
3/4" LINE TO DISH MACHINE
- DCV BFP WATTS SS007QT-S BY
GC TYP AT EQUIP. CONNECTION
�-- 3/4' UNE TO ICE MAKER
SHUT OFF VALVE TYP
��.--38'
BY GC UNE 1O lEA/COFIEE BREWERS
DCV BFP WATTS SD -3
BY CC TYP AT EQIJU
COINECITON
• - COKE DISPENSER AT ORDERING COUNTER
-- COKE DISPENSER BACK BAR
DCV BFP WATTS SD -3 BY GC
1YP AT EQUIP. CQNIECTION
' T -
POWER BY GC, REF ELECT DINGS
BACKFLOW PREVENIOR NWES:
BAR GUN
BAR GUN
SYSTEM PROVIDED BY COKE VENDOR COICE
VENDOR TO PROVIDE BACKFLOW PREVENTORS
AS REQUIRED BY LOCA. JURISDICTION -
VENDOR TO VERIFY REQUREIENIS
-► DISPENSER AT SERVER STATIONS ON DINING FLOOR
DLY BFP WATTS SD -3 BY GC IL
1YP AT EQUP. CONNECTION
PIPING
SCHEMATIC'
COLD WATER SUPPLY
TO WATER HEATER
PIPE UNION:
DIELECTRIC IF
DISSIMILAR METALS
BUTYL ;DIAPHRAGM
AIR CHARGING VALVE
FILL TANK WITH AIR
PRESSURE TO MATCH
WATER PRESSURE,
THEN OPEN VALVE
PIPE HANGER
NEXT TO PIPE TEE
WELDED STEEL
EXPANSION TANK
WITH POLYPRO-
PYLENE LINING
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT
FIELD CONDITIONS. MAKE PIPE SAME SIZE AS TANK FITTING.
FOLLOW MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION
PROCEDURE. VERIFY PROPER OPERATION WHEN : INSTALLED.
EXPANSION TANK INSTALLATION SHALL OCCUR ONLY WHEN THERE
IS ;A BACK FLOW PREVENTION DEVICE INSTALLED WITHIN THE
TENANT SPACE WATER SYSTEM OR BUILDING WATER SYSTEM.
EXPANSION TANK
Scale: NONE
ANCHOR - PER NFPA
MOTE:
EIILDING 5Tid1GTUiE MAY VAT '
MATCH IP TAI.LAIION TO BUILDING
STRUCTURE NEITR TO 5TRUGTURAL PR141N65 FOR
ATTA 111411T.
5/15" ALL -THREAD ROD FOR <=4" PIPE.
FOR LARGER PIPE 512E5 SEE NFPA 15.
HANGER - GRINNEL • FIG. 6g
ON INSULATED PIPE. PROVIDE
PIPE SUPPORT .SHIELD.
PIPE HANGER
DETA I L
Scale: NONE:
PIPE
STAND
J
SATE VAL
WATTS 2-1/2", a57 RPDA OSY
REDUCED PRESSURE
BACKFLOW
�1!_�1l1��,11E11111 IIIIlmaio 1
-17
0
DETAIL SHOWS GENERAL SCHEMATIC REQUIREMENTS. INSTALL ITEMS
FURNISHED BY WATER COMPANY, PAY ANY FEES REQUIRED BY WATER
COMPANY, FURNISH AND INSTALL ITEMS NOT PROVIDED BY THE WATER
COMPANY. PROVIDE BACKFLOW PREVENTER OF TYPE $ MANUFACTURER
APPROVED BY LOCAL AUTHORITIES.
PROVIDE ANY REQUIRED CERTIFICATION OF TESTING
OF THE BACKFLOW .PREVENTER TO LOCAL AUTHORITIES.
WATER SERVICE ENTRANG
Scale: NONE
I TINSTALL PER PDI
PDI 1 'STANDARDS AND
SIZE (MANUFACTURER'S
INSTRUCTIONS
HA-
HA
HA -
H A-;
HA
HA -
SINGLE FIXTURE
PDI .
SIZE
PIPE •
SIZE.
FIXTURE
UNIT LOAD
A:
1/2"
1-11
B
3/4"
12-32
C
1" `
33-60
D
1-1/4"
"' 61-113
E :
1-1/2"
114-154
F
2"
154-330
IF HORIZONTAL BRANCH IS LESS THAN 20'
LONG, PROVIDE ONE HA AT END OF LINE
IF BRANCH IS GREATER THAN 20' LONG,
PROVIDE ANOTHER HA IN MIDDLE, EACH
SIZED FOR HALF THE FIXTURE UNITS
MULTIPLE FIXTURES
FIXTURE UNIT TABULATION
FIXTURE
COLD
HOT
VALVE WATER CLOSET •
10 '•
-- ..
TANK WATER CLOSET
5
--
URINAL
5 :
--
LAVATORY/SINK
1.5
1.5
JANITOR'S SINK
3 •
3
SHOWER/BATHTUB
2
2
PC TO PROVIDE WATER HAMMER ARRESTERS BY SIOUX CHIEF, PRECISION
PLUMBING PRODUCTS, WATTS OR APPROVED EQUIVALENT WITH PISTON
AND 0 -RING CONSTRUCTION, HAVING PDI #WH- 201, ASSE #1010 AND
ANSI #A112.26.1M CERTIFICATION. INSTALL IN HORIZONTAL OR VERTICAL
POSITION, BUT NEVER UPSIDE DOWN. INSTALL IN LINE WITH WATER
FLOW DIRECTION IF POSSIBLE. SIZE THE UNITS AS SHOWN ON THE
DRAWINGS AND/OR PER THE TABLES SHOWN ABOVE. PROVIDE ACCESS
PANEL FOR SERVICING OR REPLACEMENT, WHERE REQUIRED.
HAMMER ARRESTERS
Scale: NONE
D
NOT U5E17:
Scale: NONE
TP -2
1/2" MIN. G.W. SUPPLY
(AVOID DIRECT
CONNECTIONS TO PREVENT
FOREIGN MATERIAL FROM
ENTERING PRIMER VALVE)
TRAP PRIMER
ASSEMBLY TO BE
MOUNTED EXPOSED IN
AN ACCESSIBLE
LOCATION FOR PROPER
MAINTENANCE.
"PPP". PRIME RITE PR 500
TRAP PRIMER VALVE
IN/INTEGRAL VACUUM
BREAKER
°------' VACUUM
BREATHER
PORTS
J " TRAP PRIMER
LINE TO DRAIN
ARRANGEMENT .SHOWN 15 SCHEMATIC. MODIFY TO SUIT
MANUFACTURER'5 STANDARDS,MEET LOCAL CODE
REQUIREMENTS, AND ALL OTHER APPLICABLE CODES AND
REQUIREMENTS. FOR INSTALLATION IN MECHANICAL AND UTILITY
ROOMS.
TRAP :PRI MSR DETA I L
Scale: NONE
GAS PIPE IN CEILING SPACE
SUPPORTED PER DETAIL
CEILING
UNION•
DO NOT INSTALL VALVES
IN CEILING SPACE
EXHAUST HOOD
GAS PIPE HEADER ALONG WALL BEHIND
COOKING EQUIPMENT, APPROXIMATELY
12" ABOVE FLOOR, WITH SCREWED
FITTINGS, SIZE AS SHOWN ON PLANS.
PROVIDE QUANTITY AND SIZE OF
CONNECTIONS AS REQUIRED FOR
EQUIPMENT BEING SERVED
MANUAL GAS-
VALVE (TYP)
FLOOR
TURN BACK INTO WALL CAVITY
EE ARCHITECTURAL DETAIL FOR
OKLINE WALL PIPING INSTALLATION.
UNION - MANUAL GAS VALVE
L GAS SHUT-OFF VALVE,
PROVIDED BY HOOD VENDOR,
INSTALLATED BY P.C.
INTERCONNECT TO HOOD
FIRE SUPPRESSION SYSTEM
BY F.P.C.
FLEXIBLE APPLIANCE
CONNECTOR FURNISHED
BY. KEV AND INSTALLED
BY PLUMBING CONTRACTOR
.TYPICAL 6" DIRT LEG
TO 6" ABOVE FLOOR
TYPICAL 6" DIRT LEG
TO 6" ABOVE ' FLOOR
TYPICAL PIPE SUPPORT
ANCHORED TO WALL.
ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT ACTUAL CONDITIONS.'
INSTALL PIPING HEADER IN WALL CAVITY PROVIDED,' SEE ARCHITECTURAL.
ATTACH RISER & HEADER TO WALL WITH 1" CLEARANCE BEHIND PIPE. MAKE
FINAL CONNECTION TO EQUIPMENT:. AS RECOMMENDED BY MANUFACTURER.
PROVIDE WELDED FITTINGS/JOINTS IN ANY CONCEALED, UNSLEEVED LOCATION:
GAS APPLIANCE
Scale: NONE
'Y" STRAINER
DRAIN LINE
mmm
O1 I" GH SUPPLY TO HATER
FILTER SYSTEM SEE FLOOR
PLANS AND HATER FILTER
PIPING SCHEMATIC.
O.2 STAINLESS STEEL RPZ VALVE
60" AFF MAX. WITH FULL SIZE
DRAIN LINE, TERMINATE DRAIN
LINE AT .CODE APPROVED
RECEPTOR WITH CODE
REQUIRED AIR-6AP
3 , GPVG PIPING AND FITTING
O-
BETWEEN BEVERAGE .
EQUIPMENT AND BACKFLOW
PREVENTER (NO COPPER
PIPING ALLOWED)
SODA
EQUIPMENT
SEE FLOOR
PLANS
FLOOR SINK
SEVERA6E SYSTEM B.F.P.
Scale: NONE
PIPEST
GAS PIPING
ROOF 5TRUC
I. PIPING SHALL BE SUPPORTED AT ALL ELBOWS AND
TEES AND AT SPACING SPECIFIED IN TABLE BELOW.
PIPING SHALL BE $LOPED AND ROUTED TO PREVENT
TRAPPING CONDENSATE (EXCEPT AT DIRT LEGS) AND
TO: FACILITATE CONDENSATE DRAINAGE.
2. - GAS PIPING AND PENETRATIONS THRU ROOF SHALL
BE AS GALLED FOR IN SPECIFICATIONS SECTION 15
OR AS REQUIRED BY LOCAL GODES.
5. PIPESTAND SHALL BE MIRO, INC. 'PILLOHBLOGK'
MODEL I5 (UP TO 1 1/2"), 5-R (UP TO 5"), AND
4-R • 4 -RAH FOR 4", 6-RA1-1 (5" TO 6").
4. DO NOT ATTACH PIPESTANDS TO ROOF.
PIPE SIZE
O1 I" GH SUPPLY TO HATER
FILTER SYSTEM SEE FLOOR
PLANS AND HATER FILTER
PIPING SCHEMATIC.
O.2 STAINLESS STEEL RPZ VALVE
60" AFF MAX. WITH FULL SIZE
DRAIN LINE, TERMINATE DRAIN
LINE AT .CODE APPROVED
RECEPTOR WITH CODE
REQUIRED AIR-6AP
3 , GPVG PIPING AND FITTING
O-
BETWEEN BEVERAGE .
EQUIPMENT AND BACKFLOW
PREVENTER (NO COPPER
PIPING ALLOWED)
SODA
EQUIPMENT
SEE FLOOR
PLANS
FLOOR SINK
SEVERA6E SYSTEM B.F.P.
Scale: NONE
PIPEST
GAS PIPING
ROOF 5TRUC
I. PIPING SHALL BE SUPPORTED AT ALL ELBOWS AND
TEES AND AT SPACING SPECIFIED IN TABLE BELOW.
PIPING SHALL BE $LOPED AND ROUTED TO PREVENT
TRAPPING CONDENSATE (EXCEPT AT DIRT LEGS) AND
TO: FACILITATE CONDENSATE DRAINAGE.
2. - GAS PIPING AND PENETRATIONS THRU ROOF SHALL
BE AS GALLED FOR IN SPECIFICATIONS SECTION 15
OR AS REQUIRED BY LOCAL GODES.
5. PIPESTAND SHALL BE MIRO, INC. 'PILLOHBLOGK'
MODEL I5 (UP TO 1 1/2"), 5-R (UP TO 5"), AND
4-R • 4 -RAH FOR 4", 6-RA1-1 (5" TO 6").
4. DO NOT ATTACH PIPESTANDS TO ROOF.
PIPE SIZE
MODEL 140.
MAX SPACING
3/4"
15
6'
I"
15
1'
1 1/4"
15
6'
11/2"
15
10'
2"
5-R
10'
2 1/2"
3-R
15'
5"
5-R
15'
4"
4-R 4 4 -RAH
g'
5'
6 -RAH
13'
6"
6 -RAH
10'
MIRO INDUSTRIES, INC.
PARKWAY INDUSTRIAL PARK
566 1E5T 6560 SOUTH
SANDY, UTAH 64010
e,45 SUPPORT
DETAIL
Scale: NONE
n'
STOP VAL'
LAVATORY
STOP VALVE
G.W. SUPPLY
TRAP PRIMER VAL
J.R. SMITH 266141
4
ll�l
li
ELEVATI ON
PENETRATE HALL AND ROUTE
BELOW SLAB TO FLOOR DRAIN.
PROVIDE CHROME ESCUTCHEON.
1/2" TO FLOOR DRAIN
FINISHED FLOOR
TRAP PRI MSR DETA lL
Scale: NONE
STEPPED FLEXIBLE
PVC BOOT CLAMPED
TO FLASHING BASE
AND PIPE WITH
STAINLESS STEEL
SCREW CLAMPS
PROVIDE
SPUN ALUMINUM'
BASE .IN BED
OF MASTIC
COORDINATE
WITH ROOFER
I
II
- ROOFING OVER
METAL FLASHING
BY ROOFING
CONTRACTOR
GROUND -JOINT PIPE UNION
GAS COCK (VALVE)
ELBOWS TO
COMPENSATE
FOR PIPE
EXPANSION
PIPE SUPPORT
REFER TO DETAIL
II II ROOF INSULATION
II II ROOF DECK
i n
SLEEVE ROOF -
IF REQUIRED ANCHOR PIPE TO ROOF DECK OR JOISTS
REFER TO PLANS FOR PIPE SIZE(5) AND LOGATION(5). USE
I^ELDED OR SCREWED FITTINGS AS SPECIFIED FOR PIPE SIZE.
LOCATE PENETRATION MINIMUM 15" FROM ADJACENT WALLS.
ROOF PENETRATION
Scale: NONE
BFP
WATTS 007QT.
"Y" STRAINER
COLD WATER
SUPPLY
DISCHARGE TO
APPROVED DRAIN
AND ROUTE TO
APROVED DRAIN.
BY PASS VALVE 3/4" SOW TO
SW DISH MACHINE
• SOFTENED WATER TO
-VALVE (TYP.)
WATER A -EATER
P.C./G.C.
UNION (TYP.) CULLIGAN
CULLIGAN
EQUIPMENT
SOFTENER
BRINE
TANK
- 4' CONC. PAD
FLOOR r. • - .:_.,.... . 'FLOOR
\____/ G.C.:.AND PLUMBING CONTRACTOR TO HAVE WATER SUPPLY ANS SHUT-OFF
FLOOR SINK VALVES INSTALLED BEFORE THE CULLIGAN EQUIPMENT PROVIDER IS ON SITE
TO INSTALL WATER SOFTENER.
WATER SOFTENER
Scale: NONE
BRADED: PIPE
UNION EYP.
RIDGID PIPE
NIBCO #460
SPRING CHECK
VALVE
1/2"HWWITH
1/4 TURN STOP.
RIDGID PI
.4
MV -I MIXING
SLOAN MIX -70-A VALVE
VALVE SET AT MI5°F, INSTALL
TIGHT TO UNDERSIDE OF SINK
RIDGID PIPE
1/4 TRUN STOP
RECEIVED
CITY OF TUKWILA
JUN 2 4 2'S13
PERMIT CENTER
VALVE
Alameda, CA 94501
Tel 510 865 8663
Fax 510 865 1611
Mechanical Engineers
2518 East Bay Drive, NW
Gig Harbor, WA 98335
253-514-6036
STORE DESIGN
5500 WAYZATA BLVD. STE 1600
MINNEAPOLIS, MN 55416
PHONE 952.593.9943
FAX 952593.9787
DO NOT SCALE DRAWINGS
CONTRACTOR TO VERIFY
ALL EXISTING CONDITIONS
AND DIMENSIONS -NOTIFY
ARCHITECT OF ANY
DISCREPANCIES PRIOR TO
BEGINNING CONSTRUCTION
Lai
r4)
co
DESCRIPTION
(13
03
(73
0
TAG
DEMAND
BTU
AC'S
AC UNITS
1,040,000
119
4 BANK FRYER
320;000
120
3: BANK FRYER
300,000
122
GRIDDLE
150,000
188
CONVECTION OVEN
44,000
GWH
GAS WATER HEATER
199,000
TOTAL BTU DEMAND
2,053,000
NOTE'
SEE KITCHEN EQUIPMENT PLANS FOR
FINAL CONNECTION REQUIREMENTS OF
EQUIPMENT.
TOTAL DEVELOPED LENGTH OF TENANT SYSTEM = 200'-0"
2 :PSI' PRESSURE GAS
GAS PIPING SYSTEM SIZED : FROM THE
PLUMBING CODE (2010 :'UPC.), TABLE 12-11
NOTE:
ALL COOKING SURFACES, KITCHEN EXHAUST SYSTEMS,
GREASE REMOVAL DEVICES AND HOODS SHALL BE
PROTECTED WITH AN : APPROVED :AUTOMATIC_ FIRE.
SUPPRESSION SYSTEM AS SHOWN ON KITCHEN AND HOOD
DRAWINGS. THE ACTUATION OF THE FIRE SUPPRESSION
SYSTEM SHALL AUTOMATICALLY SHUT DOWN THE FUEL
SUPPLY TO THE COOKING EQUIPMENT AS SHOWN IN "BOTH
KITCHEN AND PLUMBING DRAWINGS. THE FIRE
SUPPRESSION SYSTEM SHALL BE INTERLOCKED WITH THE
GAS ;SOLINOID VALVES.
J
:2vENT'UNE
CONNECT TO
BUILDING -VENT
7. OR LARGER,
24' DIA. LOCKING ME 6 COVER
AIR.& GAS TIGHT
3 PLCS (21:1601+ N 5774AI
GROUT, ALL AROU .
BOTH:SI
NOTES: SECTION A -A k�
1. REFER TO CHAPTER 8 OF THESE STANDARDS.
2. CONCRETE: 28 DAY COMP . SSIVE. STRENGTH Pc = 4500 PSI'.
3. REBAR: ASTM A-615 G E 60.
4. MESH: ASTM A-185 G E 65.
4. DESIGN: ACI -318-83 IILDING CODE
ASTM C-8 'MINIMUM STRUCTURAL DESIGN LOADING F • ONOLITHIC OR SECTIONAL
PRECAST CONCRETE WATER AND WASTEWA STRUCTURES".
5. LOADS: H-20 T CK WHEEL WITH 30% IMPACT PER AASHTO.:
6. FILL WITH CL WATER PRIOR TO START UP OF SYSTEM.
7. CONTRACT TO SUPPLY & INSTALL ALL PIPING & SAMPLING TEES.
8. ONLY G WATER, EXCEPT DISHWASHERS. BLACK WATER SHALL BE CA IED BY SEPARATE SIDE
SEWER.
SIZING CHART
/DESIGN Number Of Meals x Waste Flow x Retention x Storage _ parity.
FORMULA: Per Peak Hours Rate Time Factor Ir aIIons:
GALLON CAPACHY
- 1000
1250
1500
1750
200021
2500 `
2750
32000
4000j
C.H.
UV CO. M
441.8'-0" A
4fi
A
DOMESTIC HOT HATER
'12'OA
�A
HJ^I.R
A
05000
$60000A
M A'
h.. 5-0"
GA
5'-0'
11-2'
54"
11'-A
5'4"
6'4" _
1
6'41"
12'$
6'$`.
13'4
_8'4".::.
13'-71A
54".
19 11
.9'-11".
19.1'1"-.-
1 ':1
DIM"6"
DIM "C"
1 7. -r7. -r7'-2-
T.P.RV.
7'-2"
7'-2"
8'-0"
8'4'
8'-0"
5'.T
W- "
8'.11"
O'd1"
'
DIM "D"
4•-2"
5•-2-
4.-0"
4-11"
4.7"
5. •
6%0"5.-0"
HB.
6'4"
6.nr.
7N2 -
WATER DEPTH DIME"
13'-10'
4'•10" :
; 4'4"
4'4"
3.10"
44"
5'4"
4•-T-
6'-1"
4.9"
5'-S
qi of
Tukwila
GREASE INTERCEPTOR'
SINGLE VAULT WITH DOUBLE BAFFLE
SHEET:
REVISION #1: '08.03
SS -14
I 'LAST REVISION: 04.08
APPROVAL:, BOB GIBERSON, CITY ENGINEER
GENERAL NOTES:
BEFORE COMMENCEMENT OF WORK, CONTRACTOR SHALL VERIFY EXACT
LOCATIONS, ELEVATIONS AND CHARACTERISTICS OF UTILITIES AND PIPING
AND SHALL IMMEDIATELY NOTIFY THE ARCHITECT OF ANY DISCREPANCIES.
EXACT LOCATIONS AND MOUNTING HEIGHTS OF PLUMBING FIXTURES SHALL BE
OBTAINED FROM ARCHITECTURAL AND KITCHEN EQUIPMENT DRAWING.
CONTRACTOR SHALL MAKE ALL ARRANGEMENTS WITH UTILITY COMPANIES FOR
SERVICE. AND CONNECTIONS AND SHALL PAY FOR ALL FEES, CHARGES,
PERMITS AND METERS.
ALL VENT AND FLUE OUTLETS SHALL BE 10'-0" MINIMUM FROM ANY FRESH AIR
INTAKES 4 EXTEND TO MATCH HGT OF PARAPET.
INSTALL ALL PLUMBING TO AVOID INTERFERENCE WITH ELECTRICAL AND
MECHANICAL EQUIPMENT AND STRUCTURAL FRAMING. NO WATER OR DRAIN
LINES PERMITTED OVER OR UNDER ELECTRICAL PANELS.
CONTRACTOR SHALL PROVIDE: FAUCETS, TRAPS, STOPS, GATE VALVES, GAS
COCKS, WATER HAMMER ARRESTORS, CLEANOUT COVERS AND INDIRECT
WASTE TO AN APPROVED RECEPTOR AND ALL NECESSARY TRIM FOR A
COMPLETELY CONNECTED PLUMBING SYSTEM.
ALL WORK SHALL BE DONE ` IN ACCORDANCE WITH . ALL LOCAL CODES, RULES AND
REGULATIONS GOVERNING THIS PROJECTS.
DURING THE PROGRESS OF THE WORK, MAINTAIN AN ACCURATE RECORD OF ALL
CHANGES MADE IN THE PLUMBING SYSTEMS. THE RECORD DRAWING SHALL SHOW
CHANGES IN MANUFACTURER (WITH NUMBERS AND TRADE NAMES). MATERIALS, SIZES,
LOCATIONS AND HOOK-UP POINTS. AS -GUILTS SHALL BE GIVEN TO OWNER'S
CONSTRUCTION MANAGER AT COMPLETION OF JOB.
9 UPON COMPLETION OF JOB, THIS CONTRACTOR SHALL INSPECT ALL EXPOSED POR-
TIONS OF THE PLUMBING INSTALLATION AND COMPLETELY REMOVE ALL EXPOSED
LABELS, SOIL, MARKINGS AND FOREIGN MATERIAL EXCEPT PRODUCT LABELS AND
THOSE REQUIRED BY LAW.
10. BEFORE ANY USE OF SYSTEM 15 MADE FOR DOMESTIC PURPOSES, IT SHALL BE
STERILIZED BY SLOWLY FILLING WITH WATER TO WHICH A STERILIZING AGENT HAS BEEN
APPLIED, AT A RATE GIVING 50 PPM OF CHLORINE, AS DETERMINED BY RESIDUAL
CHLORINE TEST AT EXTREMITIES OF THE LINE. AFTER LINES HAVE BEEN FILLED FOR A ` >
A PERIOD OF THREE (5) HOURS, TESTS FOR RESIDUAL CHLORINE SHALL SHOW NOT
NOT LESS THAN 50 PPM. IF LESS THAN 50 PPM I5. INDICATED, DRAIN OR FLUSH
OUT THE LINE AND REPEAT STERILIZATION TREATMENT UNTIL TESTS INDICATE
AT LEAST 50 PPM OF RESIDUAL CHLORINE AFTER THREE (3) HOURS. ` THE LINES SHALL
BE FLUSHED UNTIL ALL TRACES OF CHEMICAL HAVE BEEN REMOVED
FIRE FROTEGTION
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTING
WITH A CERTIFIED FIRE PROTECTION SPECIALIST. FIRE PROTECTION
SPECIALIST TO PROVIDE, FOR APPROVAL, CONSTRUCTION DOCUMENTS
AND SPECIFICATIONS TO THE GOVEPNING''AUTHORITIES HAVING
JURISDICTION. THE DOCUMENTS SHALL INCLUDE BUT NOT BE LIMITED TO
THE INSTALLATION OF A NEW FIRE PROTECTION SYSTEM AND/OR THE
ADJUSTMENT OF AN EXISTING S#RI ER' SYSTEM. ALL FIRE
PROTECTION SYSTEMS SHALL BE GCORDINATED WITH ALL OTHER
TRADES. AND ARCHITECTURAL CHARATERISTICS OF THE PROJECT.
EMPLOY LANDLORD'S APPROVED CONTRACTOR FOR ALL SPRINKLER
WORK, SUBMIT DESIGN TO LANDLORD'S INSURER FOR APPROVAL
PLUME3I NO NOTES:
A. ALL WATER PIPING IN BUILDING ABOVE CEILINGS, IN HALLS, AND BELOW
FLOORS SHALL BE INSULATED AS REQUIRED BY THE IECC ENERGY
CONSERVATION CODE. INSULATE PIPING TO PROTECT FROM FREEZING
AND PROVIDE SOUND PROOFING..:
B. CONTRACTOR TO COORDINATE WITH ALL REQUIREMENTS OF FOOD
SERVICE PLANS AND PROVIDE ALL WORK SHOWN, ON BOTH PLUMBING
AND KITCHEN PLANS:
C. ALL WORK TO BE IN COMPLIANCE WITH PREVAILING CODES.
D. - WATER LINES TO BE INSIDE OF WALLS, SURFACE MOUNTED WORK 15 NOT
ACCEPTABLE."
E ALL WATER LINES TO BE VALVED AT STUB -IN LOCATIONS.
F. PLUMBING CONTRACTOR TO PROVIDE AND INSTALL HATER HAMMER
ARRESTORS IN LINE BEFORE ALL SOLENOID VALVES. I.E. AT
DISHWASHER, DISPOSER(S), ICE MAKER(S), STEAMER(S), ETC.
G. COOKING EQUIPMENT GAS PRESSURE TO BE 1-14" N.C.. FOR. NATURAL
GAS AND 10" W.C. FOR LP GAS.
H.
PLUMBING CONTRACTOR TO PROVIDE AND INSTALL A GAS SOLENOID
VALVE WITH INTERLOCK TO EXHAUST VENTILATOR FIRE PROTECTION
SYSTEM
-• ' PLUMBING CONTRACTOR TO PROVIDE AND INSTALL A CHECK VALVE IN
CARBONATOR WATER SUPPLY LINE
K. PROVIDE AND INSTALL PIPE HANGERS; FOR ALL PIPING SYSTEMS,
CLL DETAIL ON SHEET P201
L. PLUMBER SHALL AMKE ALL FINAL CONNECTIONS TO ALL THE KITCHEN
AND BAR EQUIPMENT INCLUDING INSTALLATION OF SPRAYERS, FOUCETS
AND DRAINS.
SAGiGFIAW PREVENTER SGHEDIJLE
DESCRIPTION
TAG
VALVE MODEL
ASS!
HATER FL.ITER/GARBONATOR
RPBA
WATTS I" 55 OOq' QT -S
1013
HATER SOFTENER
DCV
WATTS 01 aT-S
1015
ICE MACHINE
DCV
WATI'5'3/4' SEMI/ -k r -S
1015
INSTALL ADDITIONAL BACKFLOW PREVENTERS AT EQUIPMENT
CONNECTIONS FOR THE ITEMS LISTED BELOW WHEN REQUIRED BY
LOCAL CODE CONTRACTOR TO FIELD VERIFY WITH LOCAL
CODE OFFICIAL THE LOCATIONS AND QUANTITIES OF POINT OF
USE BACKFLOW -PREVENTION PRIOR TO PERFORMING WORK.
DESCRIPTION
TAG
VALVE MODEL
ASSE
GARBONATOR
RPBA WATTS I" 550061 ` QT -S
1013
COFFEE / TEA BREWER
DCV WATTS 3/8" SDS -FN
1022
EGOLAB CHEMICAL DISPENSERS RPBA WATTS 1/2" * OOG QT -5
1013
CHECK VALVES
WATTS* LF600 SERIES.
NOTE:
I. VERIFY MAIN WATER SUPPLY BACKFLOW PREVENTION
REQUIREMENTS WITH LOCAL CODE AT START OF
CONSTRUCTION. PROVIDE BACKFLOW` PREVENTER' ON MAIN
SERVICE IF REQUIRED.
2 ALWAYS VERIFY BACKFLOW VALVE REQUIREMENTS AND
APPROVAL FOR, ALL EQUIPMENT' WITH AUTHORITIES HAVING
JURISDICTION PRIOR TO INSTALLATION
3. GARBONATOR'TO HAVE STAINLESS STEEL`RPZ VALVE.
4.: PROVIDE 'Y" STRAINERS FOR ALL RPZ. VALVES.
5.. ALL BACKFLOW PREVENTERS ON THE PROJECT NEW
AND OR EXISTING HAVE TO BE TESTED AND
INSPECTED. AS REQUIRED BY CODE AND THE
AUTHORITY HAVING JURISDICTION. PLUMBING
CONTRACTOR TO PROVIDE TESTING DOCUMENTATION
TO THE OWNER OPERATOR FOR T EIR RECORDS.
6• ALL REDUCED PRESSURE BACKFLO1/4 ASSEMBLIES
SHOWN HAVE USG APPROVALS
PLUMBING FIXTURE SCHEDULE
MARK
FIXTURE
MINIMUM CONNECTION SIZES
V
G.W.
Hi'L
GA5
DESCRIPTION
HDGP WATER
CLOSET
WATER
CLOSET
WALL
URINAL HOOP
WALL MT'D.
URINAL
CORIAN
LAVATORY
1,1/2'
1 I/2'
11/2'
FLOOR
SINK
-1/2"
FLOOR
DRAIN
FLOOR
DRAIN
FLOOR
DRAIN
TRENCH
DRAIN
I -I/2'
HOSE BIBS
HALL
TRAP
PRIMER
TRAP
PRIMER
HATER
HEATER
GREASE
INTERCEPTOR
ROOF DRAIN
-I/2'
1-1/2
3/4'
1/2'
3/4'
3/4"
1/2"
1/21
2' 5011
115
3/40
AVAFWALL' NO. 285g.I28'E ON6ATE0 I28.6PF TOILET
IlTH OPEN FRONT SEAT (NO Co)YEKAND ZURN NO Z-6000AV FLUSH VALVE
W/ (2)',SPLJT RINGS (YJ) PIPE SUPPORTS hU INTER6RAL VAr✓UUM BREAKER
PROVIDE WITH HALL CARRIER MOUNT AT HANDICAP HIEGHT
A5.'A--MIAIl.' NO. 28541.1223 ELONGATED 128 OFF TOILET
KITH OPEN FRONT SEAT NO GOV% AND ZURN NO Z-6000AV FLUSH VALVE
HI (2) SPLIT RINGS (YJ) FIFE SUPPORTS HI MGM. VACUUM BREAKER
PROVIDE WITH HALL CARRIER MOUNT AT STANDARD HIEGHT
A.S. 'WPSHBROOK' NO. 6510525 WITH Z JRN 7R-6003
FLUSH VALVE (0.125 6PF) AND (2) SPLIT RING
(YJ) PIFE SUPPORT AND INTERORAL VAGIMM BREAKER
MOUNT AT HANDIGAPE HIEGHT
A5.:' AASHBROOK" NO. 65.40525 WITH ZURN ZR -6003
FLUSH VALVE (0.125 6PF) AND (2) SPLIT RING
(YJ) PIPE SUPPORT AND INTERORAL`VACUJM BREAKER
MOUNT AT STANDARD HIEGHT
2410 Mariner Square Loop
Mechanical Engineers
2518 East Bay Drive, NW
Gig Harbor, WA 98335
253-514-6036
LAVATORY BY MILLWORK PROVIDE E..KAY LKT31AC SELF CLOSING
DRONE PLATED FAUCET , 120V/I4 SET AT 12'SEGOND TIME OUT
NTH SLOAN ETF -460A GROiE GRID STRAINER
EL TTE MODEL 65 M WITH CHICAGO. FAUCET Sell -CP WITH INTERGRAL
VACU$ BREAKER AND FAUCET HALL SUPPORTS MOP SINK FAUCET
WITH 5GOLAB CHEMICAL DIS BY VENDOR
ZURN bg50 WITH ALL WHITE BAKED ENAMEL G.I. FLOOR
SINK WJTBH HALF &RATE, AND STRAINER
12°-'b . X 8" DEEP
ZURN 1950 WITH ALL WHITE BAKED ENAMEL G.I. FLOOR
SINK 01115H HALF ORATE, AND STRAINER
12" ROUND X 8" DEEP
ZURN `;1150 WITH ALL WHITE BAKED ENAMEL G.I. FLOOR
SINK WUTBH HALF ORATE, AND STRAINER
12" ROUND X 8" DEEP
WADE' 1100 STD FLOOR SINK WITH NICKEL BRONZE STRAINER
6' ROUND
WADE 100 STD FLOOR SINK WITH NICKEL BRONZE STRAINER
6' ROUND
WADE 0100 STD FLOOR SINK WITH NICKEL BRONZE
6' ROUND
TABGO FTG -I248 STAINLESS STEEL WITH STAINLESS STEEL ORATE
AND STAINLESS STEEL STRAINER BASKET
1400DFORD 11861, HOSE BIBB IN HALL BOX WITH
VACUUM BREAKER, FREEZE PROOF
PROVIDE WITH ALL ROUGH BRASS EXTERIOR FINISHES
AO SMITH BTH-IGM, Iq9. MBH INPUT
230 OPH REC. a 100° RISE, 650 LBS, 115 V, I -PHASE ELECT,
6000 GALLON GREASE IN I LMGEPTOR
UV MODEL 6000 WITH SAMPLING MANHOLE
MIFAB R-II5O ROOF DRAIN / OVERFLOW
WITH NO HUB CONNECTIONS
'LUMBINC FIXTURES (WATER GLOESTS AND
URINALS) AND F=ITTINGS (PUAGETS) SHALL
MEET THE STANDARDS REFERENCED IN
TABLE 5.303.6
HOT WATER HEATER SIZING CALC.
FIXTURE
BAR 4 COMPARTMENT SINK
BLENDER STATION
DUMP AND HAND SINK
3 COMPARTMENT POT SINK
PREP SINK
HAND SINK
LAVATORY
MOP SINK
DISH MACHINE
GLASS MACHINE
QUANT. AND DEMAND
I 16 6PH
205 &PH EA
20`5 &PH EA.
I • 5q OPH
I056PH
5 0 5 6P14 E.A.
4 o 5 OPH EA.
lo106PH
0 28.8 OPH
I0 28.8 6PH
TOTAL HOT HATER DEMAND AT 100°F RISE
ENTERING HATER TEMPERATURE ADJUSTMENT FOR 50°F ENTERING HATER = 0.a
211.6 X .q = 116 GALLONS PER HOUR
k. SCHEDULES HATER HEATER HAS 230 GALLONS PER HOUR RECOVERY RATE
211.6 6P#f
NOTES TO CONTRACTOR:
A GATE VALVES SHALL NOT 13E1.6132 ON THIS JOB, ONLY BALL VALVES WILL BE APPROVED: AND THEY
SHALL BE _'NIBCO" *5-585 FOR SWEAT SOLDER OR "NIBCO" it .T-585 FOR THREADED. BOM ARE TESTED
FOR 600 P5114/ FULL PORT DIA. WHICH HILL NOT RESTRICT FLOW.
B ALL PLUMBING VALVES, LINES AND EQUIPMENT SHALL BE PROPERLY LABELED.
C
PLUMBING CONTRACTOR (PC) SHALL SUPPLY $ INSTALL MIXING VALVES ON ALL
HAND SINKS 4 LAVATORIES FOR ITIS DEG. F. (MAX) HOT WATER SUPPLY
PC SHALL SUPPLY $ INSTALL CHECK VALVES ON ALL BAR SINK SHINS FAUCETS, SERVICE SINK 4
PRE -RINSE
DOMESTIC COLD WATER
CALCULATION
LOSSES
P.5.1.
LEFT
PIPE
SIZE
CW
S.P.M.
GW
F.T.
F.U.
CW
F.V.
F.U.
GW
VEL.
'HW
O.P.M..
1 -IW
F.T.
F.U.
HW
VEL.
P.5.I. AVAILABLE WATER METER:
150'
1/2"
2.6
2
35
2.6,
2
3.5
P.5.I. AVAILABLE AFTER PRESSURE REDUCING STATION
51
3/4"
5.8
1
3.6
5.8
Sb
P.S.I. LOSS THRU WATER METER
WA
II.
II
14
4.0
14 ..
4.0
P.5.I. L055 THRU BACKFLOW PREVENTOR.
WA
-I/4
21
21
5.0
21
21
5.0
LOSS DUE TO BLDG. HT 16- FT. X .43
1
1-1/2°
31
55
12
5.5
28
50
5.0
P.5.I. REQUIRED FOR FIXTURE
35
2"
61
I82 .
82
6.0
52.
125
5.0
L055 THRU MIXING VALVE
WA
2-1/2"
100
315
250
6.0
TOTAL PRESSURE LOSS
42
3"
P.5.1 AVAILABLE :FOR FRICTION L055
II
AVAILABLE P.5.I. '61.0 X 100 =q00 P.5.1./ 100 FT.
LENGTH OF RUN = 250 FT. 000- 250 = Sb
OO FT. + 25% (FITTINGS) =.250 FT.
SYSTEM SIZED ON
3.6
LOSS PER 100 FT,.
5"
6"
8°
C
REVIEUIIEQ' FOR.
COD
COMPLIANCE
APPROVED
JUL 0 3 2013
C
BUl
itv of Tukwila
LD1NG DIVISION
STORE DESIGN
5500 WAYZATA BLVD. STE 1600
MINNEAPOLIS, MN 55416
PHONE 952.593.9943
FAX 95Z593.9787
PLUMBING LEGEND
SYMBOL
ABBREV.
DESCRIPTION
55
SOIL OR HASTE BELOW GRADE OR FLOOR
- - -
55
SOIL OR HASTE ABOVE GRADE OR FLOOR
C.H.
DOMESTIC -GOLD HATER
-
H.H.
DOMESTIC HOT HATER
- - -
HJ^I.R
HOT HATER RETURN
6.
GAS PIPING
G
CD
CONDENSATE DRAIN
GD
-
V.
SANITARY VENT
-
V.
SANITARY VENT BELOW FLOOR
V
$:1
T.P.RV.
TEMP. PRESS. RELIEF VALVE
-VI- -4E04
G.V.
GATE VALVE
5.O.V.
SHUT-OFF VALVE
l>4
G.C.
GAS COCK
I'-
U.
UNION
'
HB.
HOSE 5155
A.P.
ACCESS PANEL
-L_J
O
RD.
ROOF DRAIN
0
OD.
OVERFLOW DRAIN
F.G.O.
FLOOR CLEANOUT
-()
-1I
W.G.O.
HALL CLEANOUT
-�-(1)--
C.O.T.6.
CLEANOUT TO GRADE
SD.
STORM DRAIN
6H
GREASE WATSE
CH
CONDENSATE HASTE
V.T.R.
VENT THRU ROOF
•
P.O.G.
POINT OF CONNECTION
I.E.
INVERT ELEVATION
BEL.
BELOW
DN.
DOWN
FLR.'
FLOOR
ABV.
ABOVE
SFGW
SOFT FILTERED COLD HATER
6R.
• GRADE
(CT!)
CONNECT TO EXISTING, VERIFY LOCATION
(N)
NEW
(E) •
EXISTING
SCW
SOFT COLD HATER
INSULATION TABLE FOR WATER PIPING
INSULATION 3/4"
1) ( ; oq
.........
ALL iteuLATio SHALL BE lAVIR VALUES OF 4.0 TO 4.6
HASTE
HATER
HVAG
HATER HTG
DO NOT SCALE DRAWINGS
CONTRACTOR TO VERIFY
ALL EXISTING CONDITIONS
AND DIMENSIONS -NOTIFY
ARCHITECT OF ANY
DISCREPANCIES PRIOR TO
BEGINNING CONSTRUCTION
DESCRIPTION
0
cO
Ea
0
-J
crry
R CFETIuliKEwp zcic
J mNIT2c4E2\40T13Em: 5LL
KITCHEN
F.U.
GPM
MBH
MBH
MBH
EXIST.
NEN
127
157
1040
814
FUTURE
TOTAL
127
157
1040
814
TOTAL GAS DEMAND r. 2053 MBH
MAIN GAS PIPING SIZED BASED ON 2053 MBH DEMAND
LESS THAN 200 FEET FROM GAS METER TO MOST REMOTE
PRESSURE REGULATOR GAS PRESSURE 15 2 PSI GAS
SHEET NUMBER
P300