HomeMy WebLinkAboutPermit EL13-0894 - WINGSTOP - TENANT IMPROVEMENTWINGSTOP
17424 SOUTHCENTER PY
EL1 3-0894
Parcel No:
Address:
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Inspection Request Line: 206-438-9350
Web site: http://www.TukwilaWA.gov
ELECTRICAL PERMIT
2623049110
17424 SOUTHCENTER PKWY
Project Name: WINGSTOP
Permit Number: EL13-0894
Issue Date: 12/11/2013
Permit Expires On: 6/9/2014
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
KIR TUKWILA 050 LLC
C/0 KIMCO REALTY CORP_3333 NEW
HYDE PARK RD #100 PO , NEW HYDE
PARK, WA, 11042
ROD BUTLER
3218 EASTLAKE AV E #113 , SEATTLE,
WA, 98102
CROSS CREEK ELECTRIC
Address: 22732 61 AV E , SPANAWAY, WA,
98387
Phone: (206) 402-5783
Phone: (206) 255-2104
License No: CROSSCE907KK Expiration Date: 5/12/2014
Lender:
Name:
Address:
/ 1 /
DESCRIPTION OF WORK:
SUBTYPE: NRES STATUS: APPROVEDDESCRIPTION: TENANT IMPROVEMENT FOR NEW RESTAURANT
PROVIDING ELECTRICAL FOR NEW LIGHTING, POWER FOR HVAC, AND POWER FOR KITCHEN EQUIPMENT.
Valuation of single family: $0.00
Valuation of mf/comm: $20,000.00
Type of Work: TENANT IMP
Fees Collected: $561.00
Electrical Service Provided by: PUGET SOUND ENERGY
Water District: HIGHLINE,TUKWILA
Sewer Distric: TUKWILA SEWER SERVICE
Current Codes adopted by the City of Tukwila:
Internations Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
2012
2012
2012
2012
International Fuel Gas Code:
WA Cities Electrical Code:
WA State Energy Code:
2012
2012
2012
Permit Center Authorized Signature: pv \
S
Date: lWO
t
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the co tions attached to this permit.
i n
Signature:
Print Name:
I-J�vl�t-4
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or
if the work is suspended or abandoned for a period of 180 days from the last inspection.
Date:/ -1—/1—&/3
PERMIT CONDITIONS:
1: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical
Inspector at each work site.
2: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical
Inspector.
3: All electrical work shall be in accordance with NFPA 70 - NEC, and requirements for electrical installations,
Chapter 296-46B WAC.
4: When any portion of the electrical installation is to be hidden from view by permanent placement of parts
of the building, such equipment shall not be concealed until it has been inspected and approved by the
Electrical Inspector.
5: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any
violation of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related
documentation that presumes to grant this authority are therefore not valid.
6: Any change in the scope of work described by the electrical work permit shall require additional work
permits. Where approved plans have been issued, revisions to the plans and additional review may be
required.
7: EMERGENCY/EXIT LIGHTING TO BE ON LOCAL LIGHTING CIRCUIT 700.12 (F).
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
<NONE>
CITY OF TUKWiiii
Community Developm epartment
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Eteetrical Pert No. �:rlii_ U D :l
Project No:
Date>A •plication Accepted:
Date Application Expires "
-(For office use only)
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
Site Address:
King Co Assessor's Tax No.:
17 4.10 �T�F G �1L. Pikauitty Suite Number:
Tenant Name: " LV t N Cr STV)
PROPERTY OWNER
Name: m t"2 07_
Name:
Address: 3 2143 e4FRA. or ,44Jt
c,t C. /c"
LG
City: SE,¢CiG,. State:(AAA
Zip: ? iSL v2
Phone:20(e efoz. 57 cb3 Fax:
Address:
.-S . co.,.
'$ ��
0 S Zc,
City:�� ,`�
Fax:
State:
��
Zip: M St
Contr Reg No.:
= CONTACT PERSON .= person receiving.all project`:' ,
communication ;
Name: m t"2 07_
,
Address: 3 2143 e4FRA. or ,44Jt
Cr 4+((3
City: SE,¢CiG,. State:(AAA
Zip: ? iSL v2
Phone:20(e efoz. 57 cb3 Fax:
Email: p,.0 2, oc�- 1\1 3 0.444. ,Tt
.-S . co.,.
Z e 230 4 iiso
New Tenant:
Floor:
-Ea Yes El „No
ELECTRICAL CONTRACTOR. INFORMATION; ..
Company Name:
,
Address:
City:
State:
Zip:
Phone:
Fax:
Contr Reg No.:
Exp Date:
Tukwila Business License No.;
Valuation of Project (contractor's bid price): $ 010"v
Scope of Work (please provide detailed information): 1'A“—r t 144,P 0.0 vv'twc+...r — e --S j ,t4u R.4...T,
p2A.nit0d jJcw Lt4K%I.Q4- 1 Thw'X- Not. N VAG to s k iTU. Qvl
Will service be altered? ❑ Yes
Type of Use:
Type of work:
❑ New 0 Addition 0 Service Change 0 Remodel tir Tenant Improvement
❑ Low Voltage 0 Generator 0 Fire Alarm 0 Telecommunication 0 Temporary Service
❑ No Adding more than 50 amps? ❑ Yes ❑ No
Property Served by:
'VI Puget Sound Energy 0 Seattle City Light
H:WpplicationsWorms-Applications On Line \2013 ApplicationslElectrical Permit Application Revised 7-1-13.docx
Revised: July 2013
bh
Page 1of2
•
411
RESIDENTIAL
NEW RESIDENTIAL SERVICE
❑ New single family dwellings $152.85
(including an attached garage)
❑ Garages, pools, spas and outbuildings $81.90 ea
❑ Low voltage systems
(alarm, furnace thermostat) $59.85 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
❑ Service change or alteration $81.90
(no added/altered circuits)
❑ Service change with added/altered circuits $81.90
number of added circuits $11.55 ea
❑ Circuits added/altered without service change $54.60
(up to 5 circuits)
❑ Circuits added/altered without service change $54.60
(6 or more circuits) $7.65 ea
❑ Meter/mast repair $68.25
❑ Low voltage systems $59.85
(alarm, furnace thermostat)
MULTI -FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
❑ Temporary service (residential) $65.00
❑ Temporary service (generator) $80.90
❑ Manufactured/mobile home service $86.25
(excluding garage or outbuilding)
❑ Carnivals $80.60
Number of concessions $10.80 ea
Each ride and generator truck $10.80 ea
PERM IT.-= APPLICATION'NOTES -
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR ELECTRICAL CONTRACTOR:
Signature:
Print Name:
Mailing Address:
37 SO— /? Cr:
H:1Applications\Fonns-Applications On Line12013 Applicauons\Electncal Permit Application Revised 7-1-13.docx
Revised: July 2013
bh
Date: 7/4 �13
Day Telephone: 4,121"-- %37Gs�
c/tin/44•004 600
City
Gam- 9ga7
State Zip
Page 2 of 2
Cash Register Receipt
City of Tukwila
DESCRIPTIONS
ACCOUNT QUANTITY PAID
PermitTRAK
$448.80
EL13-0894 Address: 17424 SOUTHCENTER PKWY Apn: 2623049110
$448.80
ELECTRICAL PERMIT - NONR
$448.80
ELECTRICAL PERMIT - NONR
TOTAL FEES PAID BY RECEIPT: R324
R000.322.101.00.00
$448.80
$448.80
Date Paid: Wednesday, December 11, 2013
Paid By: MATT'S REMODELING/REPAIR INC
Pay Method: CHECK 17452
Printed: Wednesday, December 11, 2013 10:54 1 of 1
AM
CRW YSTEMS
•
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670
Fax: 206-431-3665
Web site: http://www.Tukwila WA.Qov
RECEIPT
Parcel No.: 2623049110 Permit Number: EL13-0894
Address: 17424 SOUTHCENTER PY TUKW Status: PENDING
Suite No: Applied Date: 09/17/2013
Applicant: WINGSTOP Issue Date:
Receipt No.: R13-02647
Initials: JEM
User ID: 1165
Payment Amount: $112.20
Payment Date: 09/17/2013 11:11 AM
Balance: $448.80
Payee: RODERICK BUTLER, N3 ARCHITECTS LLC
TRANSACTION LIST:
Type Method Descriptio Amount
Payment Credit Crd VISA
Authorization No. 390443
ACCOUNT ITEM LIST:
Description
112.20
Account Code Current Pmts
ELECTRICAL PLAN - NONRES
000.345.832.00.00 112.20
Total: $112.20
Prin}ori• n0_17_7n14
INSPECTION -RECORD
Retain a copy with permit
6/6-aW(
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Project: /r`�CSrd�
Type of Inspection:
��
(((��� -
Address: �tti 1 ! t • IS1,
Date Called:
Special Instructions:
Date Wanted:
l(
a.m:
Requester:
Phone No:
*Sn(, Approved per applicable codes. Corrections required prior to approval.
COR,Valaj5
COMMENTS:
-
Inspector:
Date: 0).--/r
).--i
n REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION'RECORD
Retain a copy with permit
- , P RMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188\, (206) 431-3670
Permit Inspection Request Line (206) 431-2451
INSPECTION N0.
Project: 1
Type of Inspection:
¶l
— 7?4 rLoC G.,i,.1F-Gr 5/Goct4Ju't 04
Address: �/
l ?NZ`/ i:C. i .
Date Called:
- itit•ift Sccies) 4 a dor-fCCdEATE /u hif"v4(-
—..
Special Instructions:
,ckr.
Date Wanted:
�/
-f %i-
ls+:"
p.m.
Requester:
A) t1Nt1 tly-ti (AS R(--i-Cc T t is\J PA/40
Phone No:
ElApproved per applicable codes. (Corrections required prior to approval.
COMMENTS:
ge CA++ S. V-001qP}
¶l
— 7?4 rLoC G.,i,.1F-Gr 5/Goct4Ju't 04
-76p dC coLeic Fes. M E--iJ krE i3�..itr4C1
— i t40( GICs {-rS -T0 Btu ed Loc -4L Lott*f' .hi r
- itit•ift Sccies) 4 a dor-fCCdEATE /u hif"v4(-
- vstat AS rho 6C -F 110E -Tir(cnikL 51('PLI
AtL4cA.4tJ U'
- L x 5 C Em 140 o,4. kw Ji.1rr5
-- cc:4)Jt T SJPPckT" Rk- ok
- f2(lov( TAA Ar 4141ST ('4 C)Alosirr
- ?--tx.c. L t4 ,5 'rte i t t' dAt r A-M0�- (r 7qZ-4)
A) t1Nt1 tly-ti (AS R(--i-Cc T t is\J PA/40
Inspector:
N1
&rJA L\
Date: ,7102„
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD 644;14
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Project: `, t
W( �l 5 T'o
Type of Inspection:
,t Ali . f
Address: pays.Date
Called:
Special Instructions:
Date Wanted:
3 /t) I
�.m�
p.m.
Requester:
v '
Phone No:
Zsir 21 of
Approved per applicable codes. El Corrections required prior to_approval.
COMMENTS:
e6(144
Zo
Inspector: (f_io
Date:
oar°7..I-.
REINSPECTION FEE REQUIRED.. Prior to next inspection, fee must be.
paid at 6300 Southcenter Blvd., Suite 100: Call to schedule reinspection:
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
(M1 -q
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206).431-2451
Project: -•
( la166 DP
Type of Inspection: •l
vt t4 i
Address:/7
y� J /)
I -i2 l 5.Ci;j`
Date Called:
Special Instructions: "
-
Date Wanted:///
-
2/ 0
��aa.l1,
\ 0111
i
Requester:
f
Phone No:
LJApproved per applicable codes.
Corrections required prior to approval. ..
COMMENTS:
c.,1-10dS tvi-be
uJo-w5 ra-0 Se,FF(�
n REIN SPECTION FEE REQUIRED: Prior to next inspection, fee must be
..paid at -6300 Southcenter 81vd., Suite 100. Call to schedule reinspection.
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
643-04'1
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Project: t 1
Type of Inspection:
OA a 14
- litt i tv ' • 61 to okA s*c (, W 41.4/
Address: I7 it 24 5. cii
Date Called:
Special Instructions: f
Date Wanted:
24
a.m
p.m.
Requester:
d (4P Cao
Phone No:
EJApproved per applicable codes. J3 Corrections required prior to approval.
COMMENTS:
- litt i tv ' • 61 to okA s*c (, W 41.4/
- 44 (rtoAJkL --c - _Maar ke.9410
- (1J phi' of ,.Sr'ip »t
-
- e -o i�IF
d (4P Cao
Inspector:•/t\
Date: 62"07 t.
I REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
HERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
ACTIVITY NUMBER: EL13-0894
PROJECT NAME: WINGSTOP
DATE: 09/18/13
SITE ADDRESS: 17424 SOUTHCENTER PY
X Original .Plan Submittal Response to Incomplete Letter #
Response to Correction Letter #•
_
Revision # after Permit Issued
DEPARTMENTS:
PC pad•2,-10
Building Division
Public Works
n
Fire Prevention
Structural
Planning Division
Permit Coordinator
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete
Incomplete
DUE DATE: 09/24/13
Not Applicable
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg 0 Fire ❑ Ping 0 PW 0 Staff Initials:
TUES/THURS ROUTING:
Please Route
REVIEWER'S INITIALS: DATE:
Structural Review Required ❑
No further Review Required n
APPROVALS OR CORRECTIONS:
DUE DATE: 10/22/13
Approved ❑ Approved with Conditions 1K1 Not Approved (attach comments) ❑
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
CROSS CREEK ELECTRIC
n
•
Washington State Department of
Labor & Industries
•
Page 1 of 2
CROSS CREEK ELECTRIC
Owner or tradesperson
BENSON, ERLING D
Principals
BENSON, ERLING D
Doing business as
CROSS CREEK ELECTRIC
WA UBI No.
600 456 944
22732 61ST AVE E
SPANAWAY, WA98387
206-255-2104
PIERCE, County
Business type
Individual
Governing persons
ERLINGDEANBENSON
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Electrical Contractor
License specialties
GENERAL
License no.
CROSSCE907KK
Effective — expiration
05/12/2010 — 05/12/2014
Designated administrator
BENSON, ERLING D
License type
Master Electrician
Bond
RLI INS CO
Bond account no.
LSM0193650
Received by L&I
05/12/2010
Insurance
No insurance accounts during the previous 6 year period.
Savings
No savings accounts during the previous 6 year period.
License Violations
No license violations during the previous 6 year period.
Active.
Meets current requirements.
ACTIVE
License no.
BENSOED960MB
$4,000.00
Effective date
04/22/2010
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=600456944&LIC=CROSSCE907KK& S... 12/11/2013
THRU LIGHTING 00
PANEL TO C/46
THIN LIGHTING
PANEL ;TO C/
THRU 1gHTING CONTROL
PANEL TO' c/52
47b
47a
47b
3 3 D D
cc
Sa$DSCSd
DDDD
$9$h$i $k
$m •
COOKING
i los
// '// : I/ ./// //• //• // /•-• ;i/ ' //' //; //
SWITCHES FOR
HOOD LIGHTS
AND E.FI-1
/�.
/ `%/://.:J/
PREP
106
-4'1a
REVIEWED
E PLIANCE WITH
COMPLIANCE
70 - NEC
OCT 0 3 2013
City of 1 ila
BUILDING ' 1 ISION
50k
HALLW
103
50k
JANITOR.
107
47b
47a
/7/
//
/
l
e
47e
0E/
,.
Ji
LL
47b
0/47
MO
//' /I' /// // // //' i%: :/; .. // // ' %/' / . ' // / . //`
SEPARATE PERMIT
REQUIRED FOR:
VMechanica1
Electrical
Iumbing
Gas Piping
■
City of Tukwila
BUILDING DIVISION
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
t T : rSvisior n will require a new plan submittal
r' in,:.de rdditional plan re'':ewfZ€3.
FLAN NO 1 E5
OINTERLOCK WITH EXHAUST FAN SERVING THIS ROOM.
XPROVIDE DOUGLAS LITEPAK PANEL, MODEL #
WPAK-33518—S WITH ASTRONOMICAL CONTROLER, OR
APPROVED EQUAL AT THIS LOCATION FOR CONTROL OF
DEVICES AND LIGHTING AS INDICATED ON ELECTRICAL
DRAWINGS.
OMASTER OVERRIDE SWITCH FOR LIGHTING CONTROL PANEL.
FILE COPY
Plan review approval Is , Ii a . il_ t dk
Approval of constn cOon documents } , - not authorize
the violation of any e, code or oakum Receipt
of approved Fief!
Is
City Of
ING DIVISION
SYMBOL LEGEND
MK.
SYMBOL
SPECIFICATIONS
MOUNTING I -1T.
NOTES
A
FIXTURE: JUNO LIGHTING
1'-0 TRACK W/ (2) FIXTURES (HEADS)
TRACK MODEL NO. R2BL (BLACK)
CONNECTOR MODEL NO. R388L (BLACK)
TRACK HEAD MODEL NO. R51115 -BL (BLACK)
LAMPS: GE ENERGY SMART NO. LED1DP2OS 1111
SUPPLIER: MELETIO ELECTRICAL SUPPLY.
MOUNT TO SCHEDULED CEILING
BOTTOM OF TRACK MOUNTED TO OF
BOTTOM OF FRAMING AND 3'-0"
FROM ADJACENT WALLS UNLESS
NOTED OTHERWISE.
SUSPEND FROM THE
CEILING WITH 3/5"
ALL -THREAD.
A A
B
0
FIXTURE: HILITE LIGHTING
15" ROUND PENDANT W/ 15'-0" CORD (BLACK)
MODEL: H -16116 -101 -CBIS -91 BRUSHED ALUMINUM
(30 WATT MAX LABEL)
LAMPS: (1) GE ENERGY SMART NO. LED1DP2OS 11.1
SUPPLIER: MELETIO ELECTRICAL SUPPLY
MOUNT TO SCHEDULED CEILING AS
FOLLOWS:
N/A
ALL AREAS SUSPEND TO 8'-0" AFF.
C
FIXTURE: METALUX
2'X4' FLUORESCENT TROFFER W/ ACRYLIC LENS
MODEL NO. CR5-232A-UNIV-Lai33
LAMPS: (2) 32W/T8 55W
SUPPLIER: MELETIO ELECTRICAL SUPPLY
MOUNT TO SCHEDULED ACOUSTICAL
CEILING
N/A
p
O
FIXTURE: ELITE LIGHTING
5" ROUND RECESSED CAN LIGHT
MODEL NO. 1361C 35 WATT SOCKET, 6630 -P -WH
(WHITE TRIM 4 BLACK BAFFLE) (35 WATT MAX LABEL)
LAMPS: (1) SHATTERPROOF 35W R30FL
SUPPLIER: MELETIO ELECTRICAL SUPPLY
MOUNT TO SCHEDULED ACOUSTICAL
CEILING NOTE: CEILING INSULATION
MUST BE 3" AWAY ALL SIDES
N/A
E
FIXTURE: ELITE LIGHTING
5" ROUND RECESSED CAN LIGHT
MODEL NO. 155IC 35 WATT SOCKET, 6530 -P -WH
(WHITE TRIM 4 BLACK BAFFLE) (35 WATT MAX LABEL)
LAMPS: (1) GE ENERGY SMART NO. LED12DP30R 12W
SUPPLIER: MELETIO ELECTRICAL SUPPLY
MOUNT TO SCHEDULED CEILING.
NOTE: CEILING INSULATION MUST BE
3" AWAY ON ALL SIDES
N/A
F
®
FIXTURE: JUNO LIGHTING
ADJUSTABLE RECESSED LIGHT
MODEL NO. IC44N-445-WH (WHITE)
LAMPS: (1) SHATTERPROOF 50W MR16/C/NFL
SUPPLIER: MELETIO ELECTRICAL SUPPLY
MOUNT TO SCHEDULED CEILING.
NOTE: CEILING INSULATION MUST BE
3" AWAY ON ALL SIDES
N/A
G
®
FIXTURE: NAYILITE
SURFACE MOUNTED EXIT LIGHT
MODEL NO. NXPS-3-R-IUP
LOCATIONS 4 QUANTITIES PER LOCAL
INSPECTION AGENCY, 4 FIRE MARSHALL.
SUPPLIER: MELETIO ELECTRICAL SUPPLY
MOUNT TO BTM OF SCHEDULED
ACOUSTICAL CEILING OR GYPSUM
BOARD FURR-DOWN
EXIT LIGHT WITH LED
LAMPS ANP MINIMUM
90 MINUTE BATTERY
BACKUP
H
®
FIXTURE: MULE LIGHTING
SURFACE MTD EXIT LIGHT UJ/ REMOTE EGRESS HEADS
MODEL NO. MXBRU-REM WITH H254W6V-WP BASE 4
(2) REMOTE HEADS
LOCATIONS 4 QUANTITIES PER LOCAL
INSPECTION AGENCY, 4 FIRE MARSHALL.
SUPPLIER: MELETIO ELECTRICAL SUPPLY
MOUNT TO BTM OF SCHEDULED
ACOUSTICAL CEILING OR GYPSUM
BOARD FURR-DOWN MOUNT
EMERGENCY HEAD OYER DOORWAY
TO ILLUMINATE THE PATH OF EGRESS
TO THE PUBLIC WAY
EXIT LIGHT WITH LED
LAMPS, TWO REMOTE
HEADS CAPACITY
AND MINIMUM 50 MIN.
BATTERY BACKUP
I
I
FIXTURE: NAYILITE
SURFACE MOUNTED EMERGENCY LIGHT
MODEL NO. NIWH (2 HEAD)
LOCATIONS d QUANTITIES PER LOCAL
INSPECTION AGENCY, 4 FIRE MARSHALL.
SUPPLIER: MELETIO ELECTRICAL SUPPLY
MOUNT TO SCHEDULED PARTITION AT
S" BELOW FINISHED CEILING
DUAL LAMP
EMERGENCY FIXTURE
WITH MINIMUM 50
MINUTE BATTERY
BACKUP
J
D
SPEAKER MOUNTED ON TRACK LIGHTS
WITH BLACK SPEAKER BRACKETS PROVIDED BY
OWNER (N.I.C.) WIRING BY GENERAL CONTRACTOR
WIRE EACH SPEAKER TO 'J' BOX g EQUIP. NO. 1
PROVIDE MIN. 6" ADDITIONAL WIRE PER SPEAKER
AT 'J' BOX.
MOUNT TO LIGHTING TRACK, OR TO
THE EXISTING STRUCTURE ABOVE
THE SCHEDULED HVAC DUCT WITH
BLACK SPEAKER BRACKETS.
BLACK SPEAKERS
W/ MATCHING GRILL
N/A
0REFER
0DUCT
SUPPLY REGISTER AT ROUND DUCT
TO MECHANICAL DRAWINGS FOR SUPPLY
REGISTER AND DUCT SIZE
MOUNT TO SCHEDULED DUCT AT A
MINIMUM OF 8'-0" AFF.,
SUPPORTS SHALL BE
STANDARD HVAC STYLE 2" WIDTH
SUPPLY REGISTERS
AND EXPOSED DUCT
TO BE PAINTED REF.
TO PAINT SCHEDULE
SHEET A.4.
N/A/
LAY -IN HVAC SUPPLY REGISTER PROVIDED BY
HVAC CONTRACTOR
MOUNT TO SCHEDULED
ACOUSTICAL CEILING
PAINTED, REFER TO
PAINT SCHEDULE
SHEET A.4
X
EF
EXHAUST FAN: GROAN "HDSO SOCFM
SUPPLIER: MELETIO ELECTRICAL SUPPLY
MOUNT TO SCHEDULED
ACOUSTICAL CEILING
STANDARD WHITE
COVER
N/A
LAY -IN HVAC PERORATED SUPPLY REGISTER
PROVIDED BY HVAC CONTRACTOR
MOUNT TO SCHEDULED
ACOUSTICAL CEILING
PAINTED, REFER TO
PAINT SCHEDULE
SHEET A.4
°'°""
SUPPLIER NOTE
MELETIO ELECTRICAL SUPPLY: 10930 HARRY PINES, DALLAS, TEXAS 13220 / MAIN: PHONE 1-500-111-4553
CONTACT: JIM ELLIS (SALES MANAGER), EXT. 1143 OFFICE, 512-555-5543 DIRECT, 214-333-3425 FAX, JELLISGMELETIO.COM
Consultants
TRES WEST ENGINEERS, INC.
2702 SOUTH 42ND STREET, SUITE 301
TACOMA, WA 98409-7315
TELEPHONE (253) 472 3300
FAX (253) 472 9493
RECEIVED
CITY OF TUKWILA
SEP 18 2013
PERMIT CENTER
N 3 ARCHITECTS Lc
3218 EASTLAKE AVE. EAST
SUITE 1B
SEATTLE . WA . 98102
206.402.5783
info@n3architects.com
Project
Sheet Title
WINGSTOP
17410 SOUTHCENTER PARKWAY
TUKWILA, WA 98188
LIGHTING PLAN
DRAWINGS, SPECIFICATIONS AND OTHER VISUAL MATERIALS, AS INSTRUMENTS OF
SERVICE ARE THE PROPERTY OF THE ARCHITECT WHETHERTHE PROJECT FOR WHICH
THEY ARE MADE BE EXECUTED OR NOT. THE ARCHITECT RETAINS ALL COMMON LAW,
STAMORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
Revisions
Date
9.10.13
Project No.
090312
N 3 ARCHITECTS, LLC
COPYRIGHT 2013
Scale
1/4 "=1'-0"
Sheet No.
E1.0
ON ROOF
C/39
0/14,16,18
40
./for ororeo
•
ON ROOF
C/41
C/39
C/2,4,6
+84" +84
\•
4
THRU LIGHTING CONTROL
PANEL TO C/40'
WI
0
THRU LIGHTING CONTROL
PANEL TO 0/40:
C/39
0/8,10,12
}
C/45
42
ON ROOF
C/39
0/20,22,24
THRU LIGHTING CON
PANEL TO C/42
C/43
A
0
Ir
C/35,37
%�
w
0.
+54"
3541
loll NOTES
1. COORDINATE EXACT LOCATION OF KITCHEN AND HVAC
EQUIPMENT PRIOR TO PERFORMING WORK.
FLAN \OT
5
0 INTERLOCK FAN WITH LIGHT SWITCH.
2 RECEPTACLE MOUNTED WITHIN 18" OF TOP OF WINDOW TO
MEET NEC SHOW WINDOW REQUIREMENTS.
OCONTRACTOR TO REMOVE COMPLETELY EXISTING POWER
PANEL AND REPLACE WITH NEW. REMOVE EXISTING
FEEDERS AND BREAKERS AT BUILDING SERVICE. REPLACE
BREAKER WITH 225/3 AND WIRE WITH (4) #4/0 COPPER
THIN.
OMAINTAIN EXISTING TELEPHONE SERVICE AT THIS LOCATION.
ROUTE ALL NEW TELEPHONE TO THIS LOCATION AND MAKE
ALL CONNECTIONS FOR COMPLETE OPERATION.
NEPA /( -
CCj 03 2013
City of -Tukwila
BUILDING DIVISICO .
RECEIVED
CITY OF TUKWILA
SEP 18 2013
PERMIT CENTER
Consultants
TRES WEST ENGINEERS, INC.
2702 SOUTH 42ND STREET, SUITE 301
TACOMA, WA 98409-7915
TELEPHONE (2531 472 3300
FAX 1253) 472 9483
N 3 ARCHITECTS Lc
3218 EASTLAKE AVE. EAST
SUITE 1B
SEATTLE . WA . 98102
206.402.5783
info@n3architects.com
Project
Sheet Title
WINGSTOP
17410 SOUTHCENTER PARKWAY
TUKWILA, WA 98188
POWER PLAN
DRAWINGS, SPECIFICAI1ONSAND OTHER VISUAL MATERIALS, AS INSTRUMENTS OF
SERVICE ARE THE PROPERTY OF THE ARCHITECT WHETHERTHE PROJECT FOR WHICH
THEY ARE MADE BE EXECUTED OR NOT. THE ARCHITECT RETAINS ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
Revisions
Date
9.10.13
Project No.
090312
N 3 ARCHITECTS, LLC
COPYRIGHT 2013
Scale
1/4 "=1'-0"
Sheet No.
E2.0
� L CTR
CAL S
D
- C 1I-
CATO\S
SECTION 260010: GENERAL ELECTRICAL
This General Conditions, Supplementary Conditions, and Division 1 apply to work
under this Section.
GENERAL:
1.01 DESCRIPTION:
A. General: furnish all labor, materials, apparatus, tools, equipment,
transportation,temporary construction and special or occasional services as
required to make a complete working electrical installation, as shown on the
drawings or described in these specifications.
B.
Work included:
1. Installation and assembly of lighting fixtures and lamps.
2. Grounding.
3. Connections of smoke detectors furnished and installed by Mechanical.
4. Panels and overcurrent devices.
5. Branch circuit wiring.
6. Exit signs and emergency lighting system.
7. Installation of convenience outlets.
8. Installation of telephone and data outlets and raceways.
9. Furnishing, support and installation of new transformer.
10. Rough -in wiring for display case lighting.
11. Demolition and removals.
12. Lighting controls, and time switches.
13. Connections of, and power wiring to, HVAC equipment and food service
equipment.
14. Conduit for data, telephone and alarm systems.
C. Related Work Specified Elsewhere:
1. Perform the following work, in accordance with appropriate sections of
the specifications cited, where and as necessary to furnish a complete,
working electrical installation.
D.
a. Concrete:
b. Painting:
c. Door hardware:
d. Mechanical:
e. Food Service Equipment:
Division 3
Division 9
Division 11
Division 15
Division 15
Related Work Not Included in Contract:
1. Installation
2. Installation
3. Installation
of primary and secondary utility cables.
of telephone instruments and equipment.
of data cable or computer equipment.
1.02 CODES AND STANDARDS:
A. Specific
1. The following publications or latest enacted editions
throughout construction shall apply:
a.
b.
c.
National Electrical Code.
State and Local Building and Energy Codes
Uniform Building Code.
of the
document
2. Equipment and Materials specified under this division shall conform to the
following standards where applicable.
a.
b.
c.
d.
e.
UL Underwriters' Laboratories.
ASTM American Society for Testing Materials.
CBM Certified Ballast Manufacturers.
ANSI American National Standards, Institute.
NEMA National Electrical Manufacturers Association.
1.03 DRAWINGS:
A. Layout: General layout shown on the drawings shall be
where other work may conflict with the drawings.
followed except
B. Accuracy:
1. Drawings for the work under section are diagrammatic.
2. Contractor shall verify lines, levels, and dimensions shown on drawings and
shall conformance with existing conditions at the site.
1.04 SUBSTITUTIONS: Refer to the General Conditions, supplementary general conditions
and division 1 for substitution.
1.05 SUBMITTALS:
A. General: refer to the general conditions, supplementary general conditions
and division 1 for requirements.
B. Format: furnish submittal data neatly bound in an 8-1/2" x 11" folder or
binder with a table of contents listing in order of specification section and
paragraph number.
C. Submittals shall consist of detailed shop drawings, specifications, catalog
'cuts" and data sheets containing physical and dimensioned information,
performance data, electrical characteristics, materials used in fabrication,
material finish and those optional accessories which are included and those
which are excluded.
E. Each submittal shall be thoroughly reviewed by the contractor. the cover
letter accompanying submittal letter shall list in full the items and data
submitted and shall contain a statement acknowledging that the contractor
has performed a detailed review of the submittal documents prior to
submission. failure to comply with this requirement shall constitute grounds
for return of data for resubmission without review.
E. Contractor agrees that shop drawing submittals processed by the engineer
are not change orders, that the purpose of shop drawing submittals by the
contractor is to demonstrate to the engineer that the contractor
understands the design concept, that he demonstrates his understanding by
indicating which equipment and material he intends to furnish and install
and by detailing the fabrication and installation methods he intends to use.
1.06 PRODUCT DELIVERY, STORAGE AND HANDLING:
Equipment and materials shall
be properly stored and adequately protected and carefully handled to prevent
damage before and during installation. Equipment and materials shall be handled,
stored, and protected in accordance with the manufacturers's recommendations and
as approved by the Owner's Representative. Electrical conduit shall be stored to
provide protection from the weather and accidental damage. Plastic conduit shall
be stored on even supports and in locations not subject to direct sun rays or
excessive heat. Cables shall be sealed, stored and handled carefully to avoid
damage to the outer covering or insulation and damage from moisture and weather.
Damaged or defective items, in the opinion of the Owner's Representative, shall be
replaced with new items at no cost to the Owner.
1.07 PERMITS AND FEES:
PART 2
PART 3
3.01
Provide, procure and pay for all permits, licenses and fees
required to carry on and complete the work.
PRODUCTS (Not Applicable)
EXECUTION:
INSTRUCTIONS AND MANUALS
A. Refer to Division 1.
B. At the time of completion, an adequate period shall be allotted by the
contractor for instruction of building operating and maintenance personnel in the use
of all systems. All personnel shall be instructed at one time, the Contractor making
all necessary arrangements with manufacturers's representatives. The equipment
manufacturer shall provide product literature and application guides for the Users'
reference.
C.
Costs, if any, for the above service shall be paid by the Contractor.
3.02 PROJECT RECORD DOCUMENTS (AS -BUILT)
A. Provide Project Record Drawings and Specifications as required by other Sections of
Specifications and as required herein. Such drawings shall fully represent
installed conditions including actual location of outlets, correct conduit and wire
sizing as well as routing, revised fixture scheduling listing the manufacturer and
products actually installed.
B. All changes to drawings shall be made by qualified draftspersons to match
existing line work and lettering as closely as possible.
3.03 WORKMANSHIP
A. Preparation, handling and installation shall be in accordance with manufacturer's
written instructions and technical data particular to the product specified and/or
approved except as otherwise specified. Coordinate work and cooperate with other
in furnishing and placing this work. Work to approved shopdrawings for work by
others and to field measurements as necessary to properly fit the work.
Conform to the National Electrical Contractor's Association Standard of
Installation for general installation practice.
3.04 SCHEDULE OF WORK:
Arrange work to conform to the schedule which has been
established for the progress of the work. Advise regarding shipping schedule of
major equipment.
3.05 SUPERVISION:
3.06
Contractor shall personally or through an authorized and
competent representative constantly supervise the work form beginning to completion
and, within reason, keep the same workmen and foreman on the project throughout the
project duration.
PROTECTION:
Keep conduits, junction boxes, outlet boxes, and other openings
closed to prevent entry of foreign matter. Cover fixtures, equipment and apparatus
and protect against dirt, paint, water, chemical or mechanical damage, before 4A6I
during construction period. Restore to original condition any fixture, apparatus, or
equipment damaged prior to final acceptance. Protect bright finished surfaces and
similar items until in service. No rust or damage will be permitted.
3.07 SPECIAL TOOLS:
All special tools for proper operation and maintenance of
the equipment provided under this section shall be delivered to the Owner's
representative.
3.08 CUTTING AND PATCHING
A. Install all required sleeves, forms and insets before walls or partition are built.
Cutting and patching of walls, partitions, ceilings and floor necessary for reception
of work, cause by failure to provide or properly located sleeves, forms and insets,
incorrect location of work or failure to cooperate with other trades, shall be done at
expense of trade responsible.
B. No cutting of finished or structural work may be done without acceptance. When
Necessary to have finished material or stuctural work cut, finsh necessary drawings
to trade whose materials are out to be cut.
3.09 CLEARANCES: Provide working clearance in front of, in back of, and to sides
for all electrical equipment as required by National Electrical Code Article 110.
3.10 DEMOLITION: Demolition and removal of existing electrical services to the
existing tenant space to be demolished by the Contractor.
END OF SECTION
SECTION 260050: BASIC MATERIALS AND METHODS
The General Conditions, Supplementary Conditions, and Division 1 apply to work under
this Section.
PART 1 GENERAL
1.01 DESCRIPTION
A.
Work specified in this section encompasses products, assemblies and basic
installation methods required for electrical project systems specified under this
Division and includes, but is not limited to:
1. Conduit, raceways, and fittings.
2. Wire and cables.
3. Wire connections and devices.
4. Outlet boxes.
5. Pull and junction boxes.
6. Switches and receptacles.
7. Device plates.
8. Overcurrent protective devices.
9. Telephone terminal backboard.
10. Door buzzer and pushbutton system.
11. Background sound system equipment installation and wiring.
12. Empty raceway provisions for burglar alarm and security system detection units
and switches.
B. Work Not Included:
1. Background sound system equipment furnished by FDI.
2. Burglar alarm and security system equipment and wiring.
1.02 SUBMITTALS
A. Submit in conformance with the
requirements of Section 16050 the following items:
1. Switches, receptacles and device plates.
2. Conductors and cables.
3. Overcurrent protective devices.
4. Raceways.
5. Door buzzers and pushbutton.
PART 2 PRODUCTS
2.01 CONDUIT AND FITTING
A.
Rigid Steel Conduit
1. Conduit, rigid steel: full weight, threaded, hot -dip galvanized, inside enameled,
conforming to ANSI C80.1.
2. Three-piece couplings: electroplated, cast malleable iron. Efcor 165 series,
0.Z./Gedney 4-50 series or equal.
3. Threadless couplings: electroplated, cast malleable iron, with integral conduit
stop. Efcor 1760.
4. Threadless connectors: electroplated, cast malleable iron, on threaded male hub
plastic insulated throat rated 90 degrees C minimum. Efcor 1750B series,
0.Z./Gedney 31-050 1T series or equal.
5. Insulated bushings: threaded polypropylene or thermosetting phenolic rated 150
degrees C minimum.
6. Insulated grounding bushings: threaded cast malleable iron body with insulated
throat and steel, "lay -in" ground lug with compression screw. O.Z./Gedney BLG
series, Thomas & Betts 3870 series or equal.
7. Insulated metallic bushings: threaded cast malleable iron body with plastic
insulated throat rated 105 degrees C. O.Z./Gedney Type B, Thomas & Betts
1222series or equal.
B. Electrical Metallic Tubing (EMT)
1. Conduit: Shall be formed of cold rolled strip steel, electrical resistance welded
continuously along the longitudinal seam and hot -dip galvanized after
fabrication.
Conduit shall conform to ANSI C80.3 specifications and shall meet U.L.
requirements.
2. Couplings: Electroplated, cast malleable iron, gland compression type, U.L. listed
rain and concrete tight through 1-1/4 inch trade size, O.Z./Gedney 6050W
series, Efcor 760 series or equal. Set screw type couplings may be used in dry
locations, 0.Z./Gedney 5050 series or equal.
3. Connectors: Gland compression type with cast malleable iron body with male
hub and insulated plastic throat 150 degrees C. temperature rated. 0.Z./Gedney
4050 series or equal.
C. Flexible Metallic Conduit
1. Conduit: Shall be fabricated in continuous lengths from galvanized steel strip,
spirally wound and formed to provide an interlocking design. 6' MAX. LENGTH
Flexible conduit is not permitted in walls.
2. Fittings: Connectors shall be made of the screw clamp with cast malleable iron
bodies and threaded male hubs with insulated throats.
D. Liquid Tight Flexible Metallic Conduit
1. Conduit: Anaconda Type U.A., Coleman Type Uxt1 or equal.
2. Fittings: Connector body and gland nut shall be of cadmium plated cast
malleable iron, with insulated throat, MAX. 24", T & B 5331 series, O.Z./Gedney
4Q -38-1T series,or equal.
E.
Minimum acceptable conduit size shall be 3/4 inch.
2.02 WIRE AND CABLE
A.
General
Acceptable manufacturers: General Electric Co., Rome Cable, Southwire, Triangle,
PWC Inc., or equal.
2. Conductor material: All wire and cable shall be insulated copper conductors for
all wire sizes. Aluminum wire and cable shall not be used.
3. Insulation: Insulation shall be THWN-THHN for wire sizes through size 1/0 AWG.
For larger wire sizes insulation shall be THWN, XHHW, THW or as required to
suit application.
4. Minimum conductor size:
Power and lighting branch circuits:
Signal and control circuits under 100 volts:
Any 120V./ 20A. circuits over 75 L.F. must be:
2.03 OUTLET BOXES AND COVERS
#12 AWG
#14 AWG.
#10 AWG.
A. Standard Outlet Boxes: Galvanized, one-piece, drawn steel, knock -out type of
size and configuration best suited to the application indicated on the plans. Minimum
box size, 4 inch square by 1-1/2 inch deep.
B. Switch Boxes: Two inch by 3 -inch long, galvanized steel switch boxes shall be
used only for the installation of single switches, Install multiple switches in standard
gang boxes with raised device covers suitable for the application indicated.
2.04 SWITCHES AND RECEPTACLES
A.
General: Color of devices shall be white at painted walls, ivory when installed in
fixtures,and orange for dedicated I.G. receptacles unless otherwise noted on
Drawings.
1. All general purpose 15 and 20 ampere, 125-250 volt receptacles and 120-277
volt switches shall conform to NEMA WD 1 and applicable U.L. tests.
B.
Receptacles:
1. Ground fault circuit interrupter receptacle: NEMA type 5-15R LEVITON #6598-1
or equal.
2. Duplex receptacles: NEMA type 5-15R, and 5-20R, heavy duty specification
grade, side wired only, LEVITON #5242-W AND 5243-W or equal.
3. Cash register receptacles: NEMA type 5-20R, heavy duty specification grade,
side wired only, Hubbell #IG -5262, provided with green insulated ground wire,
and with engraved cover plate -For Cash Registers Only"".
C. Switches: Twenty ampere, 120-277 volts, fast make -slow break, quiet type switch
with silver cadmium alloy contacts, binding head terminal screws, side wired only. All
switches shall be white in color.
1. Single pole, single throw, LEVITON #1221-W or equal.
2. Three-way, LEVITON #1223-W or equal.
2.05 DEVICE PLATES
A. Flush Device Plates: Plates shall be smooth plastic, color, LEVITON #8600
series or equal.
B. Surface Mounted Devices, indoor: Galvanized metal to fit box.
C. Outdoor, Weatherproof: Die cast aluminum construction, corrosion resistant,
heavy duty, hinged cover flap, and gasket, LEVITON #6196, horizontal mounting.
2.06 DISCONNECT SWITCHES
A. Switch Interior: Dead -front construction with hinged arc suppressor and switch
blades which are fully visible in the "OFF"" position and with door open.
B. Switch Mechanism: Quick -make and quick -break operating handle and mechanism
with dual cover interlock to prevent unauthorized opening of the switch door in
the "ON" position or closing the switch mechanism while the door is open.
C. Ratings: Switches shall be horsepower rated for the operating voltage and with
fused or non-fused arrangements as shown on the drawings.
D. Enclosures: NEMA 1, code gauge sheet steel with hinged cover, or NEMA 3R as
shown on Drawings, and as required by application.
REVIEWED .FOIA
COMPLIANCE WITH
NFP► 74 - NEC
OCT 0 3 2013
City of.Tukwila
BUILDING DIVISION
Le --
RECEIVED
CITY OF TUKWILA
SEP t 8 2013
PFRMIT CENTER
Consultants
TRES WEST ENGINEERS, INC.
2702 SOUTH 42ND STREET. SUITE 301
TACOMA. WA 98409-7315
TELEPHONE 1263) 472 9900
FAX (263) 472 9483
N 3 ARCHITECTS LLC
3218 EASTLAKE AVE. EAST
SUITE 1B
SEATTLE . WA . 98102
206.402.5783
info@n3architects.com
Project
Sheet Title
WINGSTOP
17410 SOUTHCENTER PARKWAY
TUKWILA, WA 98188
SPECIFICATIONS PLAN
DRAWINGS, SPECIFICATIONS AND OTHER VISUAL MATERIALS, AS INSTRUMENTS OF
SERVICE ARE THE PROPERTY OF THE ARCHITECT WHETHERTHE PROJECT FOR WHICH
THEY ARE MADE BE EXECUTED OR NOT. THE ARCHITECT RETAINS ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
Revisions
Date
9.10.13
Project No.
090312
N 3 ARCHITECTS, LLC
COPYRIGHT 2013
Scale
NONE
Sheet No.
E3.1
- L - CTR
(coni)
CAL SDI- C P CAT
0\S
2.07 PANELBOARDS
A.
Ratings: See panel schedules.
B. Finish: All painted steel work shall be treated with a primer coat and finish coat
of the manufacturer's standard gray color or ANSI 61.
C. Bussing
1. Bussing shall be rectangular cross section full length tin plated
2. Bussing shall be rectangular cross section full length tin plated
Each panelboard shall be equipped with a ground bus secured to the interior
of the enclosure. The bus shall be equal to the panelboard neutral bus and
shall have a seperate lug for each ground conductor. Not more than one
conductor shall be installed per lug.
2.08 PROTECTIVE DEVICES
A. Circuit Breakers: Molded case, bolt -on, thermal magnetic type, 40 degrees C.
ambient temperature compensated, fixed mounting, with quick -make and quick -break
switching mechanism mechanically trip -free from the operating handle.
B. Ratings: Refer to drawings and panel schedules for trip frame and poles
required. Minimum short circuit rating for 120/240 volt breakers is 10,000 A,
277/480 volt breakers is 22,000 A, if not indicated otherwise.
C. Manual motor starters: Fractional H.P. 1 phase motors shall be protected by
thermal 0.L. relay integral with the disconnect: "Motor -Minder", or equal.
2.09 ELECTRICAL SUPPORTING DEVICES
A. Conduit Straps: Hot -dip galvanized, cast malleable iron, one hole type strap
with cast clamp -backs and spacers as required. 0.Z./Gedney #14-50G strap and
#141G spacer, Refcor #231 strap and #131 spacer, or equal.
B. Construction Channel: 1-1/2 inch by 1-1/2 inch 12 gauge galvanized steel
channel with 17/32 inch diameter bolt holes, 1-1/2 inches on center, in base of
the channel.Kindorf 905 series, Unistrut P -1000 -HS, or equal.
C. Fasteners (General): Wood screws for fastening to wood. Machine screws for
fastening to steel. Toggle bolts for fastening to hollow concrete block, gypsum
board or plaster wall. Expansion anchors for attachments to pre -poured concrete.
2.10 IDENTIFYING DEVICES
A. Panelboard Directories: Shall be typewritten, arranged in numerical order and
shall show the number of the circuit is indicated. The room numbers used shall
be verified with the Owner and shall not necessarily be those used in the
drawings. Mount directories in a 6" x 8" metal frame under plexiglass inside each
panelboard.
B. Wire & Terminal Markers: Self -adhering, pre-printed vinyl with self -laminating wrap
ground strip Brady B191 series, Thomas & Betts WSI series, or equal.
2.11 PLYWOOD BACKBOARDS
A. Where indicated for telephone or communication system terminals, or for motor
control or other equipment assembles, provide backboards of size indicated.
1. Use Douglas Fir plywood, exterior grade with "B" face, prime and finished
painted.
2. Unless otherwise indicated, provide 3/4 inch thick plywood.
3. All plywood shall be fire resistant.
2.12 GROUNDING
A. Enclosures of equipment, raceways, and fixtures shall be permanently and
effectively grounded. Provide code -sized, (unless otherwise indicated) copper,
insulated green equipment ground with all branch and feeder circuit runs.
Equipment ground shall originate at panelboard ground bus and shall be bonded
all switch and receptacle boxes and electrical equipment enclosures.
B. Building services shall be grounded to building steel and to cold metallic water
piping.
C. Isolated ground conductors shall terminate on isolated ground bus
and receptacle isolated ground lugs only.
2.13 DOOR BUZZER AND PUSHBUTTON SYSTEM
A.
B.
C.
D.
Provide a complete and operating door buzzer system with all necessary
accessories, transformer and wiring.
3.02 CONDUIT INSTALLATION
A.
General
1. Conduit system shall be concealed unless exposed work is clearly called for
on drawings.
2. Conduits shall be tightly covered and well protected during construction using
metallic bushings and bushing "pennies" to seal open ends.
3.
In all empty conduits or ducts, install a 200 -pound tensile strength
polyethylene pulling rope.
4. Conduit systems shall be electrically continuous throughout. Install code size,
insulated, copper, green grounding conductor in all conduit runs pulled with
phase and netural conductors.
B.
Layout
Locations of conduit runs shall be planned in advance of the installation and
coordinated with the ductwork, plumbing, ceiling and wall construction in the
same areas and shall not unnecessarily cross other conduits or pipe, nor
prevent removal of ceiling or tiles or panels, nor block access to mechanical
or electrical equipment.
2. Where practical, install conduits in groups, in parallel, for vertical and
horizontal runs and at elevations that avoid unnecessary offsets.
3.
Exposed conduit shall be run parallel or at right angles to the centerlines of
columns and beams.
4. Conduits shall not be placed closer than 12 inches from a parallel hot water
or steam line or 3 inches from such lines crossing perpendicular to the runs.
C. Supports
1. All raceway systems shall be secured to the building structures using specified
fasteners, clamps and hangers spaced according to code requirements.
2. Support single runs of conduit using one hole pipe straps. Where run horizontally
on walls in damp or wet location, install "clamp -backs" to space conduit of the
surface.
3.
Multiple conduit runs shall be supported using "trapeze" hangers fabricated from
specified construction channel, mount to 3/8 inch diameter, threaded steel rods
secured to building structures. Fasten conduit to construction channel with
standard one hole pipe clamps or the equivalent.
D. Termination and Joints
Raceways shall be joined using specified coupling or transition coupling where
dissimilar raceway systems are joined.
2. Conduits shall be securely fastened to cabinets, boxes and gutters using two
locknuts and insulating bushing or specified insulated connectors. Install
grounding bushing or bonding jumpers on all conduits terminating at concentric
knockouts
3. Conduit terminations exposed at weatherproof enclosures and cast outlet boxes
shall be made watertight using specified connectors and hubs.
4. Install expansion coupling where any conduit crosses a building separation or
expansion joint.
E. Penetrations
All floor penetrations shall be sealed water -tight. Maintain fire rating as
required.
2. Fire -safe all rated wall penetrations using 3M listed fire-safing sealants and
assemblies.
to 3.03 CABLE AND WIRE INSTALLATION
A. General
Buzzers, three required, shall be Edwards #1064-G5, mounted 8' AFF in stock and
mezzanine areas, and 2' AFF under cash wrap counter.
Pushbutton shall be Edwards #1786-B, mount at 4' AFF.
Transformer rated 20 VA, 24VAC shall be Edwards #592, mount at 8' AFF, and
connect to local general purpose receptacle circuit.
PART 3 EXECUTION
3.01 CONDUIT AND RACEWAY APPLICATIONS
A. Rigid Steel Conduit: For all exposed and U/G conduit exposed to mechanical
damage.
Minimum size is 3/4".
B. Electrical Metallic Tubing (EMT): Interior power
where run concealed above suspended ceiling,
where not exposed to mechanical damage, or
and lighting branch circuits
in stud walls, furred spaces, and
above 6' from floor.
C. Flexible Metallic Conduit: In dry locations connection to transformers,
(6' MAX.), vibrating equipment (24" MAX.), and to recessed lighting fixtures.
D. Liquid -Tight Flexible Metallic Conduit: In damp and wet locations for
connection to all pump motors, solenoid valves, HVAC equipment and similar
devices shall be made using liquidtight flexible metallic conduit. Provide
separate ground wire independent of conduit, run inside conduit and bonded at
both ends to enclosures. Maximum length of 24 inches.
Conductors shall not be installed in conduit until all work of any nature that
may cause damage is completed. Care shall be taken in pulling conductors
that insulation is not damaged. U.L. approved non -petroleum base and
insulating type pulling compound shall be used as needed.
2. All cables shall be installed and tested in accordance with manufacturer's
requirements and warranty.
B. Splicing and Terminating
1. All aspects of splicing and terminating shall be in accordance with cable
manufacturer's published procedures.
2. Make up all splices in outlet boxes with connectors as specified herein with
separate tails of correct color to be made up to splice. Provide at least six
(6) inches of tails packed in box after splice is made up.
3. All wire and cable in panels, terminal cabinets and equipment enclosures
shall be bundled and clamped.
C. 'Metallic sheathed type MC Cable: Installed for branch circuit wiring as allowed
by local building code and tenant manual. Cable shall not be run exposed in f
inished spaces. Cable shall be supported in accordance with NEC article 334.
Use only U.L. listed fittings for terminations at boxes and cabinets.
3.04 INSTALLATION OF BOXES AND WIRING SERVICES
A. General
1. All outlets shall finish FLUSH with building walls and ceiling, except where
exposed work is called for. There shall be no gap between box and wall or
ceiling material. Any opening between box and wall or ceiling shall be
caulked airtight.
2. install raised device on all outlet boxes as required to finish flush with
surface.
3. leave no unused openings in any boz. install close-up plugs as required to seal
opening.
4. exposed outlet boxes and boxes in damp and wet locations shall be cast
metal with gasketed cast metal cover plates.
B. Boxes Layout
1. Outlet boxes shall be installed and elevations shown on the drawings or s
pecified herein. Make adjustments to locations as required by structal
sonditions and to suit coordination requrements of other trades.
2. Outlet boxes in stud wall and partitions shall not be mounted
back-to-back nor shall through -wall boxes be permitted.
B. Supports
1. Boxes installed in stud walls shall be equipped with brackets designed for
attaching directly to the studs or shall be mounted on heavy gauge
galvanized steel box supports.
2. Fixture outlet boxes installed in suspended ceilings of gypsum board or
lath and plaster construction shall be mounted to 16 gauge metal channel
bars attached to main ceiling runners.
3. Fixture outlet boxes installed in suspended ceilings systems supporting
acoustical tiles or panels shall be supported directly from the structures
above wherever pendant -mounted fixtures are installed from the box.
C. Mounting Heights: Mounting heights from finished floor to center line of
device box shall be as follows, and in accordance with handicapped accessibility
requirements of State Code.
Device:
Convenience receptacle
Convenience receptacles above
Counters unless otherwise noted
Switches, light
Telephone outlet, wall
SECTION 260500:
PART 1 GENERAL
1.01 DESCRIPTION
A. Work Include
Height(inches)
15
36
48
15
END OF SECTION
LIGHTING FIXTURES
1. Installation and connection of all fixtures, lamps, ballasts, lighting control
devices, relays, related components and accessory wiring as shown on the
plans, Fixture Schedule or as specified herein.
2. Owner to provide lighting fixtures and lamps. Contractor to install all
lighting fixtures and lamps.
3. Final aiming and adjustment of recessed adjustable fixtures and track
mounted fixtures shall be by the Electrical Contractor, as directed by the
Owner's Representative.
B. Related Work Specified Elsewhere: Refer to Section 16050 for requirements
applicable to this Section.
1.02 COORDINATION: Refer to Architectural Plans for exact location of lighting
fixtures.
1.03 SUBMITTALS: Submit in conformance with the requirements of Section 16050:
Time switches, control devices, relays and cabinets and wiring diagrams.
PART 2 PRODUCTS
2.01 LAMPS
A. Incandescent Lamps: General purpose A base lamps shall be inside frosted,
rated 120 VAC, or as noted on Fixture Schedule. Reflector style lamps, R and
PAR, as noted on Fixture Schedule. MR16 lamps shall be G.E. Precise constant
color type.
B. Fluorescent Lamps
1. 24, 36 and 48 inch long lamps shall be T-8 energy saving DELUXE
warm -white 735 K in color.
2. Compact twin -tube and double twin -tube, 9, 13 and 18 watts nominal,
735 KSPX35.
C. LED lamps shall be GE Energy Smart type as noted on fixture schedule.
D. Lamps shall be as manufactured by G.E., Osram, Venture, Sylvania only.
2.02 BALLASTS
A.
Fluorescent Lamp Ballasts
1. Ballasts for all single tube fluorescent lamps shall be U.L. approved, CBM
certified or ETL tested, Class P, Sound Rated A, "full -output" energy-saving,
electronic ballasts for Octron lamps as manufactured by Magnetek.
2. Ballasts for compact fluorescent lamps shall have high power factor.
3. Ballasts shall be approved for use with energy saving lamps by the lamp
manufacturer.
2.03 REFRACTORS, REFLECTORS AND LOUVERS
A.
All glassware, plaster and metal shall be uniform, free from defects, and
photometrically tested for distribution by an independent testing laboratory.
B Plastic diffusers shall be of virgin acrylic plastic.
C.
Polished reflectors used with triphosphor compact lamps shall have
anti -iridescent optical coating.
2.04 LIGHTING CONTROL SYSTEM
A. Lighting Control system shall consist of 20A mechanical latching type lighting
contactors, interconnecting wiring, a master switch station, time clocks and switches
all housed within a Nema 1 enclosure.
B. Lighting Contactor shall be housed in a code gage cabinet with time clocks
and have hinged screw cover. Provide one or more as required cabinets Hoffman,
or equal. Provide one or more Lighting Contactors as required ""Square -D" 8903
or equal.
C. Master switch station shall consist of 20A, 120/277VAC momentary contact single
pole double throw, center OFF, toggle switches, Hubbell #1557-I and multiple
channel outputs, or equal. Quantity as indicated on Drawings. Provide engraved
multigang stainless steel cover plate for switches.
2.05 TIME SWITCHES
A. Time switches shall be programmable 7 -Day, 24 hour electronic type with backup
battery as manufactured by Tork, Rainbird, or Intermatic. Time switches shall be wired
to control lighting via Lighting contactors of lighting control system. Typical for HVAC
system.
PART 3 EXECUTION
3.01 INSTALLATION
A. Contractor shall be responsible for handling, and fixtures shall be plumb, level,
in straight lines without distortion and clean.
B. Install each fixture in a manner recommended by the fixture manufacturer and
approved by the Owner's Representative. Under this Section of the work, furnish
and install all additional ceiling bracing, hanger supports and other structural
reinforcements to the building require to properly and safely suspend fixtures, all
as approved by the Owner's Representative.
C. Fixtures in areas of exposed duct and pipe work shall be suspended to avoid
conflict with same.
D. Pendant fixtures shall be provided with ball aligners and sway adapters. Fixture
chain shall not be used for supporting fixtures.
3.02 FIXTURE SUPPORT - SUSPENDED CEILINGS
A. Provide four wire supports for each suspended fixture, secured to the building structure
independent of the ceiling supporting system.
°E. 1, 1 3
END OF SECTION
REVIEWED FOH
COMPLIANCE WITH
NFPA 70 - NEC
OCT 0 3 2013
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
SEP 18 2013
PERMIT CENTER
Consultants
TRES WEST ENGINEERS, INC.
2702 SOUTH 42ND STREET. SURE 301
TACOMA. WA 98409-7315
TELEPHONE (263) 472 3300
FAX (253) 472 3483
N 3 ARCHITECTS Lc
3218 EASTLAKE AVE. EAST
SUITE 1B
SEATTLE . WA . 98102
206.402.5783
info@n3architects.com
Project
Sheet Title
WINGSTOP
17410 SOUTHCENTER PARKWAY
TUKWILA, WA 98188
SPECIFICATIONS PLAN
DRAWINGS, SPECIFICATIONS AND OTHER VISUAL MATERIALS, AS INSTRUMENTS OF
SERVICE ARE THE PROPERTY OF THE ARCHITECT WHETHERTHE PROJECT FOR WHICH
THEY ARE MADE BE EXECUTED OR NOT. THE ARCHITECT RETAINS ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
Revisions
Date
9.10.13
Project No.
090312
N 3 ARCHITECTS, LLC
COPYRIGHT 2013
Scale
NONE
Sheet No.
E3.2
Lighting, Motor,
202 Washington State Energy Code
and Transformer Permit Plans ,Checklist
Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3
�TGCHK
Revised June 2013
Project Address
W ingstop 'Date
9/11/2013
The follow ing information is
the 2012 Washington State
necessary to check a permit application for compliance ith the lighting, motor, and transformer
Nonresidential Energy Code.
requirements in
Applicability I
(yes, no, n.a.)
Code I
Section
Component
I
Information Required
Location I
on Awls
Building Department
Notes
LIGHTING CONTROLS (Section C405.2)
Interior Lighting
Compliance Option
i:�, _
C405.2.1Yes
Manual lighting
controls
Lighting control schedule w ith type, locations served, 50%
lighting reduction method
E1.0
area or Change of Space Use area complies w ith all applicable provisions as stand alone project
area or Change of Space Use area is combined w ith existing building lighting systems to demonstrate
w ith all applicable provisions
Building Area Method (LTG -INT -BLD) or Space -By -Space Method (LTG -INT -SPACE) Compliance Form. Document
allowed and proposed (including existing if applicable) lighting wattage of Addition or Change of Use scope. Provide
lighting controls per C405.2 and commissioning of lighting controls per C405.13.
❑ Addition
compliance
Provide
maximum
applicable
Yes ::;::
C405.2.2.1
Automaticmethod
SW itch controls
Lighting systems automatic shut-off capability - indicate
and location served on plans. Note locations w here
automatic shutoff is provided by other method (occupancy
sensor, daylight controls, etc)
E1. 0
❑ Less than 60% of luminaires in space replaced
Provide Space -by -space Method (LTG -INT -SPACE) Compliance Form. Document existing total wattage in space and proposed
(including existing) lighting wattage of project scope
Y ,,
❑ New w iring installed to serve added fixtures and/or fixtures relocated to new circtit
Provide applicable manual lighting controls (C405.2.1), occupancy sensors (C405.2.2.2), daylight zone controls (C405.2.2.3),
specific application controls (C405.2.3), and commissioning of lighting controls per C405.13
Override
Schedule w ith locations served - no single override switch
exceeds an area of 5,000 SF
El . 0
Ftestxcom
Yes >
C405.2.2.2
• •-
Schedule of locations served
E1. .0
Restrooms
;mss.
C405.2.2.3
Daylight
0.63
203
128
•
c o rado r/tranaibo n
Vertical fenestration
Arimary and secondary daylight zone areas indicated on
plans
0.66
91
+►:'Skylights
'.:4 .... ... . .... :
ii 310 ef,?a7 :jai i3iggi, Y ficT :'laG"..i'. t'J4 F.:.IAX
Skylight daylight zone areas indicated on plans
•5'is .f{w..,..'
a/`
Proposed Watts
':::
05.2.2.3. •
D_
controlsserved
Lighting control schedule w ith dimming method and locations
- no single daylight control zone exceeds 2,500 SF
i_:::
C405.2.3
_
Specific application lighting controls are independent of
general area lighting and controls for other lighting
applications
14ta 10;'8 Aa t!dlS�1G'ate::r::4'0:71,47:::-41i''.7:St:iii
,: ....:.::.: ....�., �,... ...: om.. .:.: .: ..: ..\..,... .. ...:...... ..
'.::✓.111'.1'.: ...
Yes i
i:: •/
�'tft: .
Means of egress
lightingNote
Lighting control schedule w ith method and locations served.
luminaires that function as both normal and egress.
E1.0
Yes
Display li•
Lighting control schedule with type and locations served
E1.0
IF
Accent lightingLighting
control schedule w ith type and locations served
HoteVmotel guest
rooms
Lighting control schedule w ith type and locations served
�,
Supplemental task
lighting
Lighting control schedule with type and locations served
Yes ,�
Non-exempt lighting
equipment
Lighting control schedule with type, applications served and
locations
E1. o
1 ,'_
Non-exempt lighting
equipment
Lighting control schedule w ith type, applications served and
locations
0405.2.4
Exterior lighting
controls
Lighting control schedule w ith type, features and location
served
INTERIOR LIGHTING POWER (Section C405.5)
Yes
0405.5.1
Total connected
lighting power
Schedule w ith fixture types, lams, ballasts, watts per
fixture
+i►::
Space exceptions
Space exceptions taken noted on plans or compliance form
Lighting equipment
exceptions
Equipment exceptions taken noted on plans or compliance
form
Yes :;
C405.5.2
Lighting pow er
calculations
Building Area Method
Compliance form completed - proposed w attage per building
area does not exceed maximxam allow ed w attage
'
Yes
Space -By -Space
Method
Compliance form completed - total proposed w attage does
not exceed maximum allow ed w attage
Ye, I*. C405.4
Exit signs
All internally illuminated exits sign are < 5 w atts per side
E1.0
EXTERIOR LIGHTING POWER (Section C405.6)
0405.6.2
Total connected
lighting pow er
Schedule w ith fixture types, lamps, ballasts, watts per
fixture
�,.
Exterior application
exceptions
Exterior application exceptions taken noted on plans or
compliance form
Lighting pow er
calculations
Compliance form completed - proposed w attage for exterior
lighting plus base site allow ed does not exceed max. allow ed
+:
0405.6.1
Exterior building
grounds lighting
Schedule w ith fixture types, lamps, ballasts, w atts per
fixture; lumens per w att for fixtures > 100 w atts
ELECTRICAL POWER SYSTEMS (Sections C405.7 ,C405.9, C405.12, C409.2.1)
,,
C409.2.1
Bectrical energy
consumption -
w hole building
Meters provided for w hole building electric energy usage
i '
C405.7
Bectrical energy
9Y
consumption -
dw elling units
Individual dw elling unit electricity meters provided
1.7
C405.9
Transformers
Indicate transformer size and efficiency on plans
C405.12.1
Variable speed
escalators and
moving walks
Variable speed controls provided
1-1'0405.12.2
Regenerative drives
Variable frequency regenerative drives provided for
escalators
COMMISSIONING (Sections C405.13, C408.3, C409.4.4)
0405.13
CommissioningCommissioning
procedure developed for all applicable
systems
i r.
0408.3
Lighting controls
Commissioning plan and functional test procedure developed
C409.4.4
Bectrical energy
consumption meters
Commissioning plan and functional test procedure developed
i,;(,;
Escalators & moving
walks
Commissioning plan and functional test procedure developed
If "no" is circled for any question, provide explanation:
REVIEWEDE WITH
COMPLIANCE
70 - NEC
OCT 0 3 2013
City
of Tukwila
BUILDING DIVISION
Interior Lighting Summary
LGT-SUM
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3
Revised June 2013
Project Info
R-ojectAddress W jug stop
Date 9/11/2013
17410 SouthcenterPazicway
For Building Department Use
Tukwi]a,WA 98188
Applicant Name: D avid C ]em
Applicant Address: 2702 s.42nd StSte.301,Tacoma,WA 98409
Applicant Phone: 253-47 2 3300
Project Description
❑ New Building ❑ Addition ❑ Alteration
Maximum Allowed Lighting Wattage
V Plans Included
7
Lighting Compliance Path
0 Lighting Pow er Density Calculations 0 Total Building Performance Q Gear
(If Total Building Performance then onlyLGT-CHKis required.)
Interior Lighting
Compliance Option
0 Building Area Method C) Space -by -space Method Clear
Interior Lighting System
Description
Briefly describe lighting
system type and features.
Gross Interior
Area in ft2
Additions and Change of Space Use (C101.4.3 & C101.4.4)
`, Addition
area or Change of Space Use area complies w ith all applicable provisions as stand alone project
area or Change of Space Use area is combined w ith existing building lighting systems to demonstrate
w ith all applicable provisions
Building Area Method (LTG -INT -BLD) or Space -By -Space Method (LTG -INT -SPACE) Compliance Form. Document
allowed and proposed (including existing if applicable) lighting wattage of Addition or Change of Use scope. Provide
lighting controls per C405.2 and commissioning of lighting controls per C405.13.
❑ Addition
compliance
Provide
maximum
applicable
Alterations,
Renovations and Repairs (C101.4.3.1)
more of luminaires in space replaced
Building Area Method (LTG -INT -BLD) or Space -By -Space Method (LTG -INT -SPACE) Compliance Form. Document
allowed and proposed (including existing) lighting wattage of project scope
d 60% or
Provide
maximum
❑ Less than 60% of luminaires in space replaced
Provide Space -by -space Method (LTG -INT -SPACE) Compliance Form. Document existing total wattage in space and proposed
(including existing) lighting wattage of project scope
❑ Lamp and/or ballast replacementw ithin existing luminaires only - existing total interior building w attage not increased
❑ New w iring installed to serve added fixtures and/or fixtures relocated to new circtit
Provide applicable manual lighting controls (C405.2.1), occupancy sensors (C405.2.2.2), daylight zone controls (C405.2.2.3),
specific application controls (C405.2.3), and commissioning of lighting controls per C405.13
❑ New or moved lighting panel
Provide all applicable lighting controls as noted for New Wiring, automatic time switch controls (C405.2.2.1), and commissioning of
lighting controls per C405.13.
❑ Space is reconfigured - luminaires unchanged or moved only
Provide all applicable lighting controls as noted for New Wiring and commissioning of lighting controls per C405.13.
❑ No changes are being made to the interior lighting and space use not changed.
Interior L ghting Summary Space -by -Space
LTG -INT -SPACE
2012 Washington State Energy Code Compliance Forms for Commercial, Group R1, and > 3 story R2 and R3
Revised June 2013
Project Info
Project Address W 5ngstop
Number of
Fixtures
Date 9/11/2013
17410 9 outhcenterP axkway
E1.0
For Building Department Use
Tukwila ,WA 98188
50
Applicant Name: D avid c ]am
Maximum Allowed Lighting Wattage
12
7
Location (plan#,
room #, or ALL)
Space Type*
Allowed
Watts per ft2
Gross Interior
Area in ft2
Watts Allow ed
(w atts/ft2 x area)
Type C
D ming area:Fam i]rdining area
59
767
0.89
770
685
35
Food preparation
Type E
0.99
443
438
Ftestxcom
5
50
0.98
118
116
1
storage
3
0.63
203
128
12
c o rado r/tranaibo n
Type x
10
0.66
91
60
'.:4 .... ... . .... :
ii 310 ef,?a7 :jai i3iggi, Y ficT :'laG"..i'. t'J4 F.:.IAX
S ales area
•5'is .f{w..,..'
a/`
Proposed Watts
1.68
190
319
14ta 10;'8 Aa t!dlS�1G'ate::r::4'0:71,47:::-41i''.7:St:iii
,: ....:.::.: ....�., �,... ...: om.. .:.: .: ..: ..\..,... .. ...:...... ..
'.::✓.111'.1'.: ...
gd?%<
.q
"vf l.,.HF!/.:F. v�p
i:: •/
�'tft: .
* Select Table C405.5.2(2) categoryfrom drop down menu.
** For atriums, indicate height.Allowed wattage for first 40 feet is 0.03 W/ft. ht.,
above 40 feet is 0.02 WAY. ht.
Proposed Lighting Wattage
Total
Area
Allow ed Watts
1815
1746
Location (plan #,
room #, or ALL)
Fixture Description
(Include exempt equipment per Note 3)
Number of
Fixtures
Watts/
Fixture
Watts
Proposed
E1.0
Type A
7
50
350
Types
12
7
84
Type C
13
59
767
Type D
3
35
105
Type E
8
12
96
Type F
5
50
250
Types
1
3
3
Type H
2
6
12
Type x
10
3
34
'.:4 .... ... . .... :
ii 310 ef,?a7 :jai i3iggi, Y ficT :'laG"..i'. t'J4 F.:.IAX
t'ti'>:/ wG,r.: .,....r
✓s% 7/f 1%'.'`';
Total
•5'is .f{w..,..'
a/`
Proposed Watts
Total Proposed Watts maynot exceed Total Allowed Watts forinteriorLighting
1701
Notes:
1. For proposed Fixture Description, indicate fixture type, lamp type (e.g. T-8), number of lamps in the fixture, and ballast type (if
included). For tracklighting, list the length ofthe track (in feet) in addition to the fixture, lamp, and ballast information.
2. For proposed Watts/Fixture, use manufacturer's listed maximum input wattage of the fixture (not simplythe lamp wattage) and
other criteria as specified in Section C405.5.1. Forline voltage track lighting, list the greater of actual luminairewattage orlength of
track multipliedby50, or as applicable, the wattage of current limiting devices or of the transformer. For lowvoltage track lighting list
the transformer rated wattage.
3. List all fixtures. Forlightingequipment eligblefor exemption per C405.5.1, note exception number and leave Watts/Fixture blank
S 1
RECEIVED
CITY OF TUKWILA
SEP 18 2013
PERMIT CENTER
Consultants
TRES WEST ENGINEERS,
2702 SOUTH 42ND STREET, SUITE 301
TACOMA, WA 98408-7315
TELEPHONE (253) 472 3300
FAX (253) 472 3483
N 3 ARCHITECTS Lc
3218 EASTLAKE AVE. EAST
SUITE 1B
SEATTLE . WA . 98102
206.402.5783
info@n3architects.com
Project
WINGSTOP
17410 SOUTHCENTER PARKWAY
TUKWILA, WA 98188
Sheet Title
LIGHTING CODE COMPLIANCE
FORMS
DRAWINGS, SPECIFICATIONS AND OTHER VISUAL MATERIALS, AS INSTRUMENTS OF
SERVICE ARE THE PROPERTY OF THE ARCHITECT WHETHERTHE PROJECT FOR WHICH
THEY ARE MADE BE EXECUTED OR NOT. THE ARCHITECT RETAINS ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
Revisions
Date
9.10.13
Project No.
090312
N 3 ARCHITECTS, LLC
COPYRIGHT 2013
Scale
NONE
Sheet No.
E4.1
PANEL
LOCATION: PREP 106
208/120 VOLT 225 AMP BUS RATING SCCR: 22,000 A
SERVING: RESTAURANT
3 PHASE 225 AMP MAIN BREAKER AFC: 15,750 A
C
FED FROM: BUILDING SERVICE
4 WIRE MOUNTING: SURFACE
NO
EQUIP.
VOLT
CKT
HP
LOAD DESCRIPTION
TYPE
KVA
A/P
PHASE
GFCI
REC
A/P
KVA
TYPE
LOAD DESCRIPTION
CKT
1
GLASS DOOR MERCHANDISER
D
1.104
20/1
A
REC
MOUNTRECEPTICLEAT+60"
20/3
1.692
M
MAU-1
2
3
REACH -IN REFRIGERATOR
D
0.684
20/1
REC
B
K-04
;
120
1
4
5
FRYER 1
D
0.948
20/1
MOUNTRECEPTICLEAT+60"
K-06
C
120
1
6
7
FRYER 2
D
0.948
20/1
A
ICE MACH. W/STORAGE BIN
120
20/3
1.728
M
EF -1
8
9
FRYER 3
D
0.948
20/1
HOT FOOD WELL
B
1
6.7
10
11
FRYER 4
D
0.948
20/1
120
1
C
7.9
C
3/4"C, 2 #12
12
13
FRYER 5
D
0.948
20/1
A
40/3
10.800
M
RTU -1
14
15
WORKTOP FREEZER
D
1.308
20/1
B
j
16
17
CONVECTION OVEN
D
5.040
20/3
.■
6.0
C
3/4"C, 2 #12
REC
MOUNT RECEPTI CLEAT +24"AFF
18
19
120
1
A
■.
3/4"C, 2 #12
50/3
15.120
M
RTU -2
20
21
1
8.3
.
B
.
REC
MOUNT RESCEPTICLE AT+60"AFF
K-42
12'-0" TYPE 1 EXHAUST HOOD
22
23
ICE MACHINE
D
0.660
20/1
3/4"C, 2 #12
C
LIGHT IN HOOD
K-84
WORKTOP FREEZER
120
24
25
HOT FOOD WELL
D
1.488
20/2
A
REC
MOUNT RECEPTI CAL AT +18"AFF
20/1
1.032
D
SALAD/SANDWICH UNIT
26
27
14.0
C
3/4 4 #12
C ,
RECMOUNT
B
20/1
1.000
D
CARBONATOR
28
29
COOKING AND HOLDING TIMER
D
0.744
20/1
C
20/1
1.000
D
6 -VALVE SELF SERVE SODA SYSTEM
30
31
COOLER / FREEZER
D
12.480
80/2
A
20/1
0.720
D
ICE TEA DISPENSER
32
33
B
20/1
0.360
0
KITCHEN HOOD FIRE SUPPRESSION
34
35
REC - SALES
R
0.720
20/1
C
20/1
0.530
M
WH -1, WH -2 & CP -1
36
37
REC - SALES
R
0.900
20/1
A
% 20/1
1.000
M
BATHROOM EF -2 & EF -3
38
39
REC - WP ROOFTOP
R
0.720
20/1
B
20/1
0.540
R
SE SHOW WINDOW
40
41
REC - DINING AREA DISPLAYS
R
0.540
20/1
C
20/1
0.900
R
N & NE SHOWWINDOW
42
43
REC - HALL WAY
R
0.180
20/1
A
20/1
1.000
L
LTG - EAST EXTERIOR SIGN
44
45
AIR CURTAIN
D
0.384
20/1
B
20/1
1.000
L
LTG - NORTH EXTERIOR SIGN
46
47
LTG - SALES, JAN, RR, PREP & COOK
L
1.354
20/1
C
20/1
1.150
L
LTG - TRACK & DOWN LIGHTS
48
49
LTG - EMERGENCY & EXITS
L
0.230
20/1
A
20/1
0.478
L
LTG - DINING
50
51
LTG - EMERGENCY& EXITS
L
0.290
20/1
B
20/1
0.500
L
LTG - OPEN TILL MIDNIGHT SIGN
52
53
SPARE
20/1
C
20/1
0.500
L
LTG - HOT WINGS TO GO SIGN
54
PHASE LOAD PHASE A= 26.98 KVA PHASE B= 26.18 KVA PHASE C= 21.45 KVA
LOAD TYPE
L
R
M
H
WH
P
D
A
K
LM
TOTAL LOADS
CONN. LOAD
6.50
4.50
30.87
32.74
15.12
74.62 KVA
207.11 AMP
CALC. LOAD
8.13
4.50
30.87
32.74
3.78
80.02 KVA
222.12 AMP
REQUIRED SERVICE -ENTRANCE RATED
OPTIONS:
REMARKS:
RFV FWED FUrS
PLANE WITH
NFPA Yfl - NEC,
Q�. I 3 2013 I
-704 of TukwilE -
!EiLIIMNG ®IVI, SIU_
MECHANICAL EQUIPMENT SCHEDULE
BUILDING C & D - MISC
EQUIP.
VOLT/
PHASE
LOAD
AMP
KVA/W
HP
CIRCUIT
BKR PANEL
CONDUIT/WIRE
SIZE
FUSED
..:.:.:..:.::.::.:.:..
DISC.
IANUAL MTF
STARTER
MAGNETIC
ITRSTATE
PILOT
SW,._
REMARKS
PACKAGED AIR CONDITIONING UNIT
RTU -1
208
30
10.8
40/3
C 1"C, 3#8
B.Y.E.0
RTU -2
208
13 42.0
15.100
50/3
C 1"C,3#8
B.Y.E.C.
MAKE UP AIR
MAU-1
208
3
4.7
1.693
20/3
C
3/4"C, 3 #12
B.Y.E.C.
FAN
EF -1
208
f3
1.4
0.500
20/3
C
3/4"C, 3 #12
B.Y.E.C.
EF -2
120
4.2
0.500
20/1
C
3/4"C, 2 #12
B.Y.E.C.
INTERLOCK WITH RESTROOM LIGHTING
E F-3
120
f1
4.2
0.500
20/1
C
3/4"C, 2 #12
B.Y. E.C.
INTERLOCK WITH RESTROOM LIGHTING
GAS WATER HEATER
WH -1
120
1€1
2.00
0.24
20/1
C
3/4"C, 2 #12
B.Y. E.C.
WH -2
280
2.00
0.24
20/1
C
3/4"C, 2 #12
B.Y.E.C.
PUMPS
CP -1
120
t1
0.7
0.080
20/1
C
3/4"C, 2 #12
BYE.C.
Consultants
TRES WEST ENGINEERS,
2702 SOUTH 42ND STREET, SUITE 301
TACOMA, WA 98409-7315
TELEPHONE (263) 472 9900
FAX 1263) 472 9483
\5
N 3 ARCHITECTS Lw
3218 EASTLAKE AVE. EAST
SUITE 1B
SEATTLE . WA . 98102
206.402.5783
info@n3architects.com
Project
WINGSTOP
17410 SOUTHCENTER PARKWAY
TUKWILA, WA 98188
Sheet Title
MECHANICAL EQUIPMENT AND
PANEL SCHEDULE
DRAWINGS, SPECIFICATIONS AND OTHER VISUAL MATERIALS, AS INSTRUMENTS OF
SERVICE ARE THE PROPERTY OF THE ARCHITECT WHETHERTHE PROJECT FOR WHICH
THEY ARE MADE BE EXECUTED OR NOT. THE ARCHITECT RETAINS ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
RECEIVED
CITY OF TUKWILA
SEP 18 2013
PERMIT CENTER
Revisions
Date
9.10.13
Project No.
090312
N 3 ARCHITECTS, LLC
COPYRIGHT 2013
Scale
NONE
Sheet No.
E4.2
KITCHEN EQUIPMENT SCHEDULE,
NO
EQUIP.
VOLT
PH
HP
LOAD 1
KW
AMPS
PANEL
CONDUIT/ WIRE SIZE
FUSE
DISC
GFCI
REC
REMARKS
K-01
GLASS DOOR MECHANDISER
120
1
9.2
C
3/4"C, 2 #12
REC
MOUNTRECEPTICLEAT+60"
K-03
SANDWICH/SALID UNIT
120
1
8.6
C
3/4"C,2#12
REC
MOUNTRECEPTICLEAT+24"
K-04
1 -DR. REACH -IN REFRIGERATOR
120
1
5.7
C
3/4"C, 3 #12
REC
MOUNTRECEPTICLEAT+60"
K-06
HOOD FIRE SUPPRESSION SYSTEM
120
1
3.0
C
3/4"C, 2 #12
it
K-14
ICE MACH. W/STORAGE BIN
120
1
5.5
C
3/4"C, 2 #12
REC
MOUNTRECEPTICLEAT+60"AFF
K-17
HOT FOOD WELL
240
1
6.7
C
3/4"C, 3 #12
REC
MOUNTRECEPTICLEAT+24"AFF
K-18
SOLSTICE SUPREME GAS FRYER
120
1
7.9
C
3/4"C, 2 #12
REC
MOUNTRECEPTICLEAT+24"AFF
K-20
COOKING AND HOLDING TIMER
120
1
6.2
C
3/4"C, 2 #12
REC
MOUNT RECEPTICLE AT +24"AFF
K-21
SOLSTICE SUPREME FILTER
UNIT IS INTEGRAL TO K-18
K-28
ICE TEA DISPENSER
120
1
6.0
C
3/4"C, 2 #12
REC
MOUNT RECEPTI CLEAT +24"AFF
K-34
6 -VALVE SELF -SERVE SODA SYSTEM
120
1
8.3
C
3/4"C, 2 #12
REC
MOUNT RECEPTI CLE AT +24"AFF
K-35
CARBONATOR
120
1
8.3
C
3/4"C, 2 #12
REC
MOUNT RESCEPTICLE AT+60"AFF
K-42
12'-0" TYPE 1 EXHAUST HOOD
120
1
4.0
C
3/4"C, 2 #12
LIGHT IN HOOD
K-84
WORKTOP FREEZER
120
1
10.9
C
3/4"C, 2 #12
REC
MOUNT RECEPTI CAL AT +18"AFF
_
K 89
CONVECTION OVEN
208
3
14.0
C
3/4 4 #12
C ,
RECMOUNT
NT EPTI AL AT 42 AFF
REC C
RFV FWED FUrS
PLANE WITH
NFPA Yfl - NEC,
Q�. I 3 2013 I
-704 of TukwilE -
!EiLIIMNG ®IVI, SIU_
MECHANICAL EQUIPMENT SCHEDULE
BUILDING C & D - MISC
EQUIP.
VOLT/
PHASE
LOAD
AMP
KVA/W
HP
CIRCUIT
BKR PANEL
CONDUIT/WIRE
SIZE
FUSED
..:.:.:..:.::.::.:.:..
DISC.
IANUAL MTF
STARTER
MAGNETIC
ITRSTATE
PILOT
SW,._
REMARKS
PACKAGED AIR CONDITIONING UNIT
RTU -1
208
30
10.8
40/3
C 1"C, 3#8
B.Y.E.0
RTU -2
208
13 42.0
15.100
50/3
C 1"C,3#8
B.Y.E.C.
MAKE UP AIR
MAU-1
208
3
4.7
1.693
20/3
C
3/4"C, 3 #12
B.Y.E.C.
FAN
EF -1
208
f3
1.4
0.500
20/3
C
3/4"C, 3 #12
B.Y.E.C.
EF -2
120
4.2
0.500
20/1
C
3/4"C, 2 #12
B.Y.E.C.
INTERLOCK WITH RESTROOM LIGHTING
E F-3
120
f1
4.2
0.500
20/1
C
3/4"C, 2 #12
B.Y. E.C.
INTERLOCK WITH RESTROOM LIGHTING
GAS WATER HEATER
WH -1
120
1€1
2.00
0.24
20/1
C
3/4"C, 2 #12
B.Y. E.C.
WH -2
280
2.00
0.24
20/1
C
3/4"C, 2 #12
B.Y.E.C.
PUMPS
CP -1
120
t1
0.7
0.080
20/1
C
3/4"C, 2 #12
BYE.C.
Consultants
TRES WEST ENGINEERS,
2702 SOUTH 42ND STREET, SUITE 301
TACOMA, WA 98409-7315
TELEPHONE (263) 472 9900
FAX 1263) 472 9483
\5
N 3 ARCHITECTS Lw
3218 EASTLAKE AVE. EAST
SUITE 1B
SEATTLE . WA . 98102
206.402.5783
info@n3architects.com
Project
WINGSTOP
17410 SOUTHCENTER PARKWAY
TUKWILA, WA 98188
Sheet Title
MECHANICAL EQUIPMENT AND
PANEL SCHEDULE
DRAWINGS, SPECIFICATIONS AND OTHER VISUAL MATERIALS, AS INSTRUMENTS OF
SERVICE ARE THE PROPERTY OF THE ARCHITECT WHETHERTHE PROJECT FOR WHICH
THEY ARE MADE BE EXECUTED OR NOT. THE ARCHITECT RETAINS ALL COMMON LAW,
STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.
RECEIVED
CITY OF TUKWILA
SEP 18 2013
PERMIT CENTER
Revisions
Date
9.10.13
Project No.
090312
N 3 ARCHITECTS, LLC
COPYRIGHT 2013
Scale
NONE
Sheet No.
E4.2