ELECTRICAL PERMIT
0003400018
9725 E MARGINAL WAY S BLDG 9-
098
BOEING #9-98.2
Permit Number: EL13-1216
Issue Date: 12/13/2013
Permit Expires On: 6/11/2014
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
License No:
Lender:
Name:
Address:
BOEING COMPANY THE
PO BOX 3707 M/C 20-00 , SEATTLE,
WA, 98124
ROLANDO MARTIN
15135 NE 92 ST, REDMOND, WA,
98052
SEQUOYAH ELECTRIC LLC
15135 NE 92ND ST, REDMOND, WA,
98052
SEQUOEL977S9
111
Phone: (425) 814-5874
Phone: (425) 814-6000
Expiration Date: 1/29/2015
DESCRIPTION OF WORK:
BOEING NCO SIF LAB RELOCATION: PROVIDE AND INSTALL NEW LIGHTING AND POWER SYSTEMS
Valuation of single family: $0.00
Valuation of mf/comm: $24,672.67
Type of Work: REMODEL
Fees Collected: $671.63
Electrical Service Provided by: SEATTLE CITY LIGHT
Water District: TUKWILA
Sewer Distric: TUKWILA SEWER SERVICE,VALLEY VIEW
SEWER SERVICE
Current Codes adopted by the City of Tukwila:
Internations Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
2012
2012
2012
2012
International Fuel Gas Code:
WA Cities Electrical Code:
WA State Energy Code:
2012
2012
2012
Permit Center Authorized Signature:
Date: 12-
k 13
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit and agree to the conditions attached to this permit.
Signature: Date:
Print Name: "-oe......6%—i/a//-1/7/'Y
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or
if the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: ***ELECTRICAL PERMIT CONDITIONS***
2: A copy of the electrical work permit shall be posted or otherwise made readily accessible to the Electrical
Inspector at each work site.
3: Approved plans shall be maintained at the construction site and shall be readily available to the Electrical
Inspector.
4: All electrical work shall be in accordance with NFPA 70 - NEC, and requirements for electrical installations,
Chapter 296-46B WAC.
5: When any portion of the electrical installation is to be hidden from view by permanent placement of parts
of the building, such equipment shall not be concealed until it has been inspected and approved by the
Electrical Inspector.
6: The issuance of an electrical work permit shall not be construed to be a permit for, or an approval of, any
violation of the provisions of the electrical code or other ordinances of the jurisdiction. Permits or related
documentation that presumes to grant this authority are therefore not valid.
7: Any change in the scope of work described by the electrical work permit shall require additional work
permits. Where approved plans have been issued, revisions to the plans and additional review may be
required.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
2100 ELECTRICAL FINAL
7003 ROUGH -IN ELECTRICAL
7002 SERVICE
7001 UNDERGROUND/SLAB
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Electrical Permit No. t L� ?j " 12-1 U'
Project No,
Date Application Accepted: 0.111P;
Expires:
Date Application Ex
p 21 I 11
(For office use only)
ELECTRICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**Please Print**
SITE LOCATION
Site Address:
Tenant Name:
,I4i, ?j King Co Assesspr's Tax No.: 28240490009
9725 East Marginal Way So. Bldg. 9,5, 9-53, 9 — "lite Number:
Boeing Company
PROPERTY OWNER
Name: Rolando Martin
Name: Boeing Company
City: Redmond State: WA Zip: 98052
Address: PO Box 3707 M/C 20-00
Email: rolando.martin@sequoyah.com
City: Seattle State: WA
Zip: 98124
CONTACT PERSON — person receiving all project
communication
Name: Rolando Martin
Address: 15135 NE 92nd Street
City: Redmond State: WA Zip: 98052
Phone: (425) 814-5874 Fax: (425) 814-6003
Email: rolando.martin@sequoyah.com
Valuation of Project (contractor's bid price): $
Scope of Work (please provide detailed information):
Boeing NCO SIF Lab Relocation. Provide and install new lighting and power systems
New Tenant:
Floor:
❑ Yes Qf ..No
ELECTRICAL CONTRACTOR INFORMATION
Company Name: Sequoyah Electric
Address: 15135 NE 92nd Street
City: Redmond State: WA Zip: 98052
Phone: (425) 814-6000 Fax: (425) 814-6003
Contr Reg No.: SEQUOEL977S9 Exp Date: 01/29/2015
Tukwila Business License No.: BUS -0100327
lr'I2.41 &)
Will service be altered? ❑ Yes 0 No
Type of Use:
Tyne of work:
❑ New ❑ Addition 0 Service Change 0 Remodel ❑ Tenant Improvement
D Low Voltage ❑ Generator ❑ Fire Alarm 0 Telecommunication 0 Temporary Service
Adding more than 50 amps? ❑✓ Yes 0 No
Property Served by:
❑ Puget Sound Energy ® Seattle City Light
H \ Applications \Forms -Applications On Line \2011 Applications \Electrical Pernut Application Reused 8-9.11 doc\
Revised: August 2011
bh
Page 1 of 2
RESIDENTIAL
NEW RESIDENTIAL SERVICE
❑ New single family dwellings $152.85
(including an attached garage)
❑ Garages, pools, spas and outbuildings $81.90 ea
O Low voltage systems
(alarm, furnace thermostat) $59.85 ea
RESIDENTIAL REMODEL AND SERVICE CHANGES
❑ Service change or alteration $81.90
(no added/altered circuits)
❑ Service change with added/altered circuits $81.90
number of added circuits $11.55 ea
❑ Circuits added/altered without service change $54.60
(up to 5 circuits)
❑ Circuits added/altered without service change $54.60
(6 or more circuits) $7.65 ea
O Meter/mast repair $68.25
❑ Low voltage systems $59.85
(alarm, furnace thermostat)
MULTI -FAMILY AND COMMERCIAL
Fees are based on the valuation of the electrical contract.
MISCELLANEOUS FEES
O Temporary service (residential) $63.00
O Temporary service (generator) $78.75
O Manufactured/mobile home service $84.00
(excluding garage or outbuilding)
O Carnivals $78.75
Number of concessions $10.50 ea
PERM ITAPPLICATION .NOTE
,, .';N ".yi, It" ' .«
Value of Construction — In all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the Permit Center to comply with current fee schedules.
Expiration of Plan Review — Applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The Building Official may grant one extension of time for an additional period not to exceed 90 days. The extension shall be requested in writing
and justifiable cause demonstrated.
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR ELECTRICAL CONTRACTOR:
Signature:
L CSC
Date:
11/26/2013
Print Name: Rolando Martin Day Telephone: (206) 7934957
Mailing Address: 15153 NE 92nd St. Redmond WA 98052
City
H:\Applications\Fornss-Applications On Line \2011 Applications \Electrical Permit Application Revised 8-9-11.docx
Revised: August 2011
bh
State Zip
Page 2 of 2
Cash Register Receipt
City of Tukwila
DESCRIPTIONS
I ACCOUNT I QUANTITY I PAID
PermitTRAK
$671.63
EL13-1216 Address: 9725 E MARGINAL WAY S BLDG 9-098 Apn: 0003400018
$671.63
ELECTRICAL
$671.63
PLAN CHECK FEE
PERMIT FEE MULTI-FAM/COMM
TOTAL FEES PAID BY RECEIPT: R214
R000.345.832.00.00
R000.322.101.00.00
$134.33
$537.30
$671.63
Date Paid: Wednesday, November 27, 2013
Paid By: SEQUOYAH ELECTRIC LLC
Pay Method: CHECK 538860
Printed: Wednesday, November 27, 2013 8:46 AM 1 of 1
CRWYSTEMS
z
INSPECTION RECORD
Retain a copiVvith permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Project:
*7_/34.,
[. �K
Type of Inspection:
ln�
Address:
Date Called:
ruct
Special Ins ions: I
C�� 1 D kioN
Date Wanted:
10
a.
p.m.
Requester: �/'
evoq
Phone No:
lac Was, 2112Z
pApproved per applicable codes. LJ Corrections required prior to approval.
COMMENTS:
K
.y -
I b()gill
n REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Inspector:
Date:
INSPECTION RECORD.
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Project: !� ti a....82
Z
Type of Inspection:
t
Stglj
Address: 977.1.0-6
� _
Date Called:
Special Instructions:-
/1���
tf �nn k
Date Wanted:
//�/ 3.r-
��-
a.r
p:m.
(((
Requester: kev4
Phone No:
Approved per applicable codes: t_J Corrections required prior to approval.
COMMENTS:
D�'
(ft44.cod
6 = Rbu(44 (Ai evir-)a-Te
Ppi-dccr
Date:. Z 31 13
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd., Suite 100: Call to schedule reinspection.
HERMIT COORD COPY 111-
PLAN REVIEW/ROUTING SLIP
ACTIVITY NUMBER: EL13-1216
PROJECT NAME: BOEING #9-98.2
DATE: 11/27/13
SITE ADDRESS: 9725 EAST MARGINAL WY S
X Original Plan Submittal
Response to Correction Letter #
Response to Incomplete Letter #
Revision # after Permit Issued
DEPARTMENTS:
C =AO (73
Building Division
Public Works
Fire Prevention
Structural
Planning Division
❑ Permit Coordinator ❑
DETERMINATION OF COMPLETENESS: (Tues., Thurs.)
Complete n
Incomplete
DUE DATE: 12/03/13
Not Applicable
Comments:
Permit Center Use Only
INCOMPLETE LETTER MAILED: LETTER OF COMPLETENESS MAILED:
Departments determined incomplete: Bldg ❑ Fire ❑ Ping ❑ PW 0 Staff Initials:
TUES/THURS ROUTING:
Please Route jk
REVIEWER'S INITIALS: DATE:
Structural Review Required ri
No further Review Required ❑
APPROVALS OR CORRECTIONS:
DUE DATE: 12/26/13
Approved I 1 Approved with Conditions g Not Approved (attach comments) n
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg 0 Fire 0 Ping 0 PW 0 Staff Initials:
SEQUOYAH ELECTRIC LLC
•
0 Washington State Department of
Labor & Industries
1
Page 1 of 3
SEQUOYAH ELECTRIC LLC
Owner or tradesperson
NICHOLS, DAVID E
Principals
NICHOLS, DAVID E
Doing business as
SEQUOYAH ELECTRIC LLC
WA UBI No.
602 252 591
15135 NE 92ND ST
REDMOND, WA98052
425-814-6000
KING, County
Business type
Limited Liability Company
Governing persons
DAVIDENICHOLS
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Electrical Contractor
License specialties
GENERAL
License no.
SEQUOEL977S9
Effective — expiration
01/29/2003 — 01/29/2015
Designated administrator
NICHOLS, DAVID E
License type
Master Electrician
Bond
HARTFORD CAS INS CO
Bond account no.
52BSBAB5541
Received by L&I
01/29/2003
Insurance
No insurance accounts during the previous
Savings
No savings accounts during the previous 6
6 year period.
year period.
Active.
Meets current requirements.
ACTIVE
License no.
NICHODE97406
$4,000.00
Effective date
01/29/2003
httns://secure.lni.wa. gov/verifv/Detail.astx?UBI=602252591 &amo;LIC=SEQUOEL977S9& S... 12/13/2013
MATCH LINE -FOR CONTIN. _)
SEE SHEET 2A11
C1-01
CONFE ENCE
CONFEREN
E
CONFERENCE
R
0
VF
VF
MAI L
(±3
CV
STORAGE
STORAGE
2M11-2
2M11-1
PCTABLE
30X60
NCO OFFIE
2N11-1.3
2M11-3
2N10-1.3 2N10-1.4
TOOLING
2N11-3
2N11-1
2N10-12 2N10-1.1
NCO RECEPT.
2N11-4
/11111111/[1*
CAR M GROUND
#2/ou
MAIN �LDG
2P10-1.3 2P10-1.4
2P11-2
2P11-3
#6 cu To
GROUN B
2P11-1.2 2P11 1.1
08L
CSL
02L
78C
78C
78C
2R11-1.3 2R11-1.
2R10-1.3 2R10-1.4
+£XOE llLlrll
MirElil'Gl*E lraElitt;
RE11Alfillii:Gii_
REVIEWED FOR
CONEPAMPLIANCE70-ITH
NECN
DEC 0 6 2013
la
DI ! !ON
MATCH LINE -FOR CONTIN.
SEE SHEET 2A13
PARTIAL 2ND FLOOR GROUNDING PLAN
SCALE: 1/8"= 1'—O"
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
'SEPARATE PERMIT
I kLQUIRED FOR:
Mechanical
0 Electrical
Plumbing
Gas Piping
City of Tukwila
Bl-i°i,D1NG DIVISION
SUPERCEDES IFC SET
DATED 09.23.13
LEGEND
T T COMMUNICATIONS GROUND BAR —
COOPER B—LINE PART #SBTGBK OR APPROVED EQUAL
FOR CONSTRUCTION
GENERAL NOTES
FILA COPY
Permit No. tU;— 121(v
Plan review approval is subject to errors and omissions,
Approval of construction documents does ncy. aLq.!*!•:-Th71
the v:o ation of any adopted code or ordinanc :. ` t;,3, -•
of approved Field Copy and conditions is acknowledg uu.
By
Date: l0 -7/i2
City Of Tukwila
BUILDING DIVISION
CO
S
RU
TI
N \0 -ES
PROVIDE WALL MOUNTED GROUND BAR MOUNTED
AT 18"AFF. PROVIDE #2/0 BONDING WIRE TO
EXISTING BUILDING GROUNDING SYSTEM.
PROVIDE BONDING GROUND WIRE. FROM EXISTING
BENCH GROUND STRAPS/BAR TO COMM GROUND
BAR.
PROVIDE BONDING GROUND WIRE FROM CABLE
TRAY TO GROUND BAR.
��13-12I1�
RECEIVED
CITY OF TUKWILA
NOV 2 7 2013
PERMIT CENTER KEY PLAN
SCALE: NONE
8' 4' 0 4' 8'
16'
SCALE 1/8"=1'-0"
SYM
REVISION
NCO SIF RELOCATION — 60% IFR WH_13063 W1844093
A
NCO SIF RELOCATION — 80% IFR WH_13063 W1844093
8
NCO SIF RELOCATION — IFC WH_1 3063
W1844093
BY
WH
WH
WH
APPROVED
DATE
SYM
REVISION
BY
APPROVED
DATE
MAS
MAS
MAS
09.03.13
09.11.13
11.04.13
ACCEPTABILITY
THIS DESIGN AND/OR
SPECIFICATION IS APPROVED
APPROVED BY
DEPT.
DATE
DRAWN
DATE
CHECKED
SUBTITLE
PARTIAL 2ND FLOOR GROUNDING PLAN
CURRENT REVISION
W1844093
SYMBOL
3
DATE
11.04.13
ENGINEER
CHECKED
APPROVED
APPROVED
TITLE
ELECTRICAL MASTER
NCO SIF RELOCATION
BUILDING 9-98.2
COL. L—S/1-13
DEV: CENTER, W
SHEET
2E9C
JOB NO.
W1844093
COMP NO.
DWG NO.
09-098-2E9C
MATCH LINE -FOR CONTIN.
SEE SHEET 2A11
0
16b
16t
14a
14a
2E7-5/
20a,22b 14a
#8
22b�DEA il
14a
9b
•
12c
2T7-1/
l a,3b,5c
#8
2T7-2/
2a,4b,6c
F- —
2T7 -2/7a
MATCH LINE -FOR CONTIN. _
SEE SHEET 2A13
ct
0
,9b
1a
14a16b
36c
16b 3 b 12c
12c
#8
2E7-4/34b,36c
#8yela
2T7-2/
8a,10b,12c
8
T7-1/
1I4a,16b,18c
14a
14a
#8
c 2T7-1/
2a,4b,6c
D -
#
#8
2T7-2/
2T7-2/ 5c
1 a,3b
2E7
12c
� 1
2E62 2E45
/13a,15b,
1a
1/12b
26a
2E62 I 451
2P3/13a
9.111 2P3
2P3/17c
16"BELOW CLG.
2T7-1/7a,9b
#10 2T7-1/
8a,1 0,12c
39b
10
2T7-2/
37a,39b,41 c
2S6/6c,8a
C/1l9a
0
T7=1/
9a, 1 b
2P3/21b
2P3/16b
22b
10
•
26a
#10
2T7-2/
14a,16b,18c
28b
•
18c
b
2E6212E452
SEE SHEET 2E6
PARTIAL 2ND FLOOR 208Y/120V POWER P_AN
SCALE: 1/8"= V-0"
C
CONNECTION FOR CARD READER AND/OR
ELECTRONIC STRIKE/MAG LOCK.
RECEPTACLE FOR DIGITAL CLOCK.
LOCATION OF SHIELDING PENETRATION FOR NCO
LAB ELECTRICAL PANEL WITH 75A 4W FILTER.
1 4 >LOCATION OF SHIELD PENETRATION FOR
STANDBY CIRCUIT FOR ALARM/ACCESS SYSTEMS
WITH 20A 2W FILTER.
LOCATION OF SHIELDING PENETRATION FOR SST
LAB ELECTRICAL PANEL WITH 30A 4W FILTER.
OA
m
t FCI
g
._.■
0
(Di2
2
AC
m
LEGEND
15A, 125V, 1
20A, 125V, 1
15A, 125V, 1
15A, 125V, 1
WITH GROUND
15A, 125V, 1
15A, 125V, 1
15A, 125V, 1
PHASE, DUPLEX RECEPTACLE
PHASE DUPLEX RECEPTACLE
PHASE DUPLEX RECEPTACLE (DEDICATED)
PHASE, DUPLEX RECEPTACLE
FAULT CIRCUIT INTERUPT.
PHASE, 4—PLEX RECEPTACLE
PHASE, FLOOR MOUNTED DUPLEX
PHASE, FLOOR MOUNTED 4—PLEX
POWER OR TELEPHONE OUTLET MOUNTED
IN DOUBLE BOX MOUNTED IN FLOOR
WITH ISOLATED GROUND.
15A, 125V, 1 PHASE, CEILING MOUNTED DUPLEX
30A, 208V, 1 PHASE RECEPTACLE
30A, 208V, 1 PHASE TWIST LOCK RECEPTACLE
POWER LINE FILTER
120/208V DISTRIBUTION PANEL
SPLIT CHANNEL TELE/POWER POLE.
JUNCTION BOX, CEILING/WALL MTD.
EQUIPMENT CONNECTION.
ABOVE COUNTER MOUNTED
FILTER
GENERAL NOTES
1.) ALL CONDUIT TO BE 1/2" EMT UNLESS OTHERWISE NOTED.
2.) ALL WIRE TO BE #12 THHN/THWN UNLESS OTHERWISE NOTED.
3.) THE FOLLOWING COLOR CODING OF CONDUCTORS SHALL BE
OBSERVED ON ALL CIRCUITS 600 VOLTS OR LESS.
120/208V 277/480V
"A" PHASE (LEFT BUS IN PANEL) BLACK BROWN
"B" PHASE (CENTER BUS IN PANEL) RED ORANGE
"C" PHASE (RIGHT BUS IN PANEL) BLUE YELLOW
NEUTRAL WHITE GRAY
EQUIPMENT GROUND GREEN
4.) LARGE SIZE CONDUCTORS WHICH DO NOT HAVE COLORED
JACKETS SHALL BE IDENTIFIED WHEREVER VISIBLE BY
APPROPRIATELY COLORED TAPE.
5.) ALL UNUSED CONDUIT AND WIRE TO BE REMOVED BACK TO
SOURCE. INCLUDING PLUG-IN CIRCUIT BREAKERS ON BUSWAY.
6.) FEEDERS TO PANELS AND BUSWAYS SHOWN ON SHEETS E2
AND E3
7.) PERMANENTLY LABEL ALL RECEPTACLES, JUNCTION BOXES, SWITCHES,
ETC., WITH CIRCUIT IDENTIFICATION.
8.) INSTALL REVISED PANEL SCHEDULES UPON COMPLETION OF
JOB.
9.) VERIFY ROTATION OF ALL 3 PHASE MOTORS.
CO\STRUCTION NOTES
REVIEWED .FOR
COMPLIANCE WITH
NEPA 70 - NEC
DEC 0 6 2013
City of Tukwila
BUILDING DIVISION
SUPERCEDES IFC SET
DATED 09.23.13
FOR CONSTRUCTION
ELl3 (IR?
RECEIVED
CITY OF TUKWILA
NOV 2 7 2013 KEY PLAN
SCALE: NONE
PERMIT CENR 4' 0 4' 8'
o
16'
IIIII
IIIII
SCALE 1/8"=1'-0"
SYM
K
B
REVISION
NCO SIF RELOCATION - IFC WH_13063
W1844093
DCN 1
J#140799-00
C
ASI 011
J# 140799-00
D
ASI 015
J# 140799-00
E
NCO - SST LAB SHIELDING
J# 140799-00
BY
WH
DLR GROUP
DLR GROUP
DLR GROUP
DLR GROUP
APPROVED
DATE
MAS
J. BECK
11.04.13
08.24.06
SYM
F
REVISION
RECORD DRAWING
4140799-00
G
J. BECK
10.25.06
H
J. BECK
02.07.07
D. JOHNS
04.06.07
J
INSTALL DUPLEX FOR WALL MTD. TV.
NCC RM TABLE OUTLETS
NCO SIF RELOCATION - 60% IFR WH_13063
NCO SIF RELOCATION - 80% IFR WH_13063
12532025
W1576707
W1844093
W1844093
BY
DLR GROUP
VAVREK
ESBROOK
WH
WH
APPROVED
DATE
J. BECK
VAVREK
TAE
MAS
MAS
07.23.07
11.30.11
11.14.12
09.03.13
09.11.13
BOE/iV0°
ACCEPTABILITY
THIS DESIGN AND/OR
SPECIFICATION IS APPROVED
APPROVED BY
DEPT.
DATE
DRAWN
EDDIE P. DUARTE
DATE
12.11.92
CHECKED
SUBTITLE
PARTIAL 2ND FLOOR 208Y/120V POWER PLAN
CURRENT REVISION
W1844093
SYMBOL K
DATE
11.04.13
ENGINEER
CHECKED
R. TUCKER
12.11.92
APPROVED
APPROVED
NAREN MEHTA
12.11.92
TITLE
ELECTRICAL MASTER
NCO SIF RELOCATION
BUILDING 9-98.2
COL. L -S/1-13
DEV. CENTER, WA
SHEET
2E62
JOB NO.
COMP NO.
DWG NO.
09-098-2E62
TJOHNSTON: 08/28/13
MATCH LINE -FOR CONTIN. _1
SEE SHEET 2A11
LABORATION
A
CONFE ENCE
III
CONFERENQE
CONi`� E
4
STAIR LOBBY
IQ
23L6
54"
Q
ISI°I _ _ Ott
I I
rairraimmilM
11
2K3-1.4
21(3-1.3
11
11
-1.1 212-1.2
212-1.3 212-1.4
REVIEWED .FOH
COMPLIANCE WITH
NEPA 70 - NEC
VF
VF
MAIL
-STORAGE
21410-
22L&
SIT°
2E362
2E451
CTABLE
30X60
OFFICE
OFFI+ E
2N11-1.3 21411-1.4
21410-1.3 21410-1.4
2`41
2112-1.4 2142-1.3
OOLIN
21410-1.2 21410-1.1
111111111111
NEMA 1
ENCL SURE
TIP.
R�T
21N3
NCO RECEP .
2N11-2.2 2N11-2.1
21410-22 21410-2,1 11
14;111 Ili1� (21 N9
e.,
CBL
an
an
an 1
an
an 1 5J,I
gA-1
t
2P11-3
SJR
RIDOR
2P10-1,3 2P10-1.4
i� Li 14
FIBER FILTER
WITH AVEGU
CORRID 111R
23C
ASSAGE
i212-1.1 2112-1.2
i:3
OPEN OFFICE
2P11-1.2
38L
CBL
38L
78C
78C
78C
SST LAB
21R7
�-ranra■� �-�r[a��■
21111-1.3
21110-1.3 2R1D-1.4
CI IMMIRVIP1
■.•..n:, -'n.,. ,.m. linin ,....r.64+.ria
MATCH LINE -FOR CONTIN.
SEE SHEET 2A13
BASKET TYPE I 1
CABLE TRAY . (TYP)
PARTIAL 2ND FLOOR TELECO
SCALE: 1/8"= 1'-0"
V1MUNICATIONS P_AN
DEC 0 6 2013
City of Tukwila
BUILDINGFDIVISIDN
LEGEND
O SPLIT CHANNEL TELE/POWER POLE.
logi TELE/DATA OUTLET, RECESS 4" SQ. BOX WITH
SINGLE—GANG MUD RING AND BLANK COVERPLATE
N TELEPHONE OUTLET, RECESS SINGLE—GANG BOX
WITH MUD RING AND BLANK COVERPLATE.
0 CEILING MOUNTED DATA OUTLET, RECESS 4" SQ.
BOX WITH SINGLE—GANG MUD RING AND BLANK
COVERPLATE.
POWER/DATA FLOOR BOX, TYPE AS
NOTED AND SPECIFIED.
V
m CEILING MOUNTED SPEAKER
O JUNCTION BOX
2 EQUIPMENT CONNECTION, CEILING/WALL
U S oUI
CABLE TRAY COOPER B—LINE PART #FT2X 8X10 OR
APPROVED EQUAL
GENERAL NOTES
REFERENCE DRAWINGS
CONSTRUCTION NOTES
PROVIDE 8"X2" BASKET TYPE WIRE CABLE TRAY.
PROVIDE SUPPORT SPAN BETWEEN 6'-8' FOR
MINIMUM 25LBS/FT LOADING. REFER TO DETAIL
1 SHEET 9-53—E542.
EXISTING FIBER PASSAGE METAL PLATE IN
CEILING SPACE. PROVIDE NEW (4) WAVEGUIDE
WITH 6 CHANNEL. DRILL NEW HOLES TO
EXISTING METAL PLATE. COORDINATE EXACT
REQUIREMENT IN FIELD WITH BOEING IT.
REFER TO SHEET 9-53—E542 DETAIL 3 FOR
CABLE TRAY SUPPORT DETAILS.
MOUNT CABLE TRAY 12 INCHES BELOW FINISHED
CEILING.
EXISTING OUTLET SHOWN IN THIS ROOM TO
REMAIN.
SUPERCEDES IFC SET
DATED 09.23.13
FOR CONSTRUCTION
tL\? 121 (0
?
2E360
RECEIVED
CITY OF TUKWILA
NOV 2 7 2013
2E363
0
PERMIT CENTER KEY PLAN
SCALE: NONE
8' 4' 0 4' 8'
SCALE 1/8"=1'-0"
16'
SYM
A
B
C
REVISION
BY
APPROVED
DATE
D
9-98 RENOVATION ADDENDUM 1 J# 140799-00
ASI 011 J# 140799-00
ASI 012 J# 140799-00
RECORD DRAWING J#140799-00
NCO SIF RELOCATION - 60% IFR WH_13063 W1844093
DLR GROUP
DLR GROUP
DLR GROUP
DLR GROUP
WH
J. BECK
J. BECK
J. BEECK
J. BECK
MAS
08.24.06
SYM
E
10.25.06
F
REVISION
NCO SIF RELOCATION - 80% IFR WH_13063
NCO SIF RELOCATION - IFC WH_13063
W1844093
W1844093
BY
WH
WH
APPROVED
DATE
MAS
MAS
09.11.13
11.04.13
11.16.06
07.23.07
09.03.13
g)LISFAVEZAW ®
ACCEPTABILITY
THIS DESIGN AND/OR
SPECIFICATION IS APPROVED
DRAWN
DLR GROUP
CHECKED
JB
DATE
05.10.06
06.27.06
SUBTITLE
PARTIAL 2ND FLOOR TELECOMMUNICATIONS PLAN
CURRENT REVISION
W1844093
SYMBOL F
DATE
11.04.13
APPROVED BY
DEPT.
DATE
ENGINEER
CHECKED
APPROVED
APPROVED
TITLE
ELECTRICAL MASTER
NCO SIF RELOCATION
BUILDING 9-98.2
COL. L—S/1-13
DEV. CENTER, WA
SHEET
2E362
JOB NO.
140799-00
COMP NO.
DWG NO.
09-098-2E362
TJOHNSTON: 08/28/13 18:35
O8L
b8L
O8L
78C
78C
780
n NCO SIF SST AB ENLARGED 208V POWER P_AN
2E62 j 452 SCALE: SCALE: 1/4" = 1 '-0"
LEGEND
30A, 125V, L5 -30R
it DUPLEX RECEPTACLE 5-20R
QUAD RECEPTACLE 5-20R
GENERAL NOTES
1. ALL CONDUIT TO BE 3/4" MINIMUM.
2. ALL WIRE TO BE #12 THHN/THWN UNLESS OTHERWISE NOTED.
3. THE FOLLOWING COLOR CODING OF CONDUCTORS SHALL BE
OBSERVED ON ALL CIRCUITS 600 VOLTS OR LESS.
120/208V 277/480V
"A" PHASE LEFT BUS IN PANEL) BLACK
"B" PHASE CENTER BUS IN PANEL) RED
"C" PHASE RIGHT BUS IN PANEL) BLUE
NEUTRAL WHITE
EQUIPMENT GROUND GREEN
4. LARGE SIZE CONDUCTORS WHICH DO NOT HAVE COLORED
JACKETS SHALL BE IDENTIFIED WHEREVER VISIBLE BY
APPROPRIATELY COLORED TAPE.
5. ALL UNUSED CONDUIT AND WIRE TO BE REMOVED BACK TO
SOURCE. INCLUDING PLUG-IN CIRCUIT BREAKERS ON BUSWAY.
7. DYMO LABEL ALL RECEPTACLES, JUNCTION BOXES, SWITCHES,
ETC., WITH CIRCUIT IDENTIFICATION.
8. INSTALL REVISED PANEL SCHEDULES UPON COMPLETION OF
JOB.
9. VERIFY ROTATION OF ALL 3 PHASE MOTORS.
BROWN
ORANGE
YELLOW
GRAY
REFERENCE DRAWINGS
CONSTRUCTIO\
NOTES
PROVIDE SURFACE MOUNTED DUPLEX FOR ANTENNA TEST
RANGE ASSEMBLY. PROVIDE CIRCUIT AS SHOWN.
PROVIDE SURFACE MOUNTED QUAD RECEPTACLE. PROVIDE
CIRCUIT AS SHOWN.
� PROVIDE SURFACE MOUNTED L5-30 RECEPTACLE AND CIRCUIT
AS SHOWN.
4 EXISTING RECEPTACLES TO REMAIN.
EXISTING PANEL TO REMAIN. PROVIDE NEW CIRCUIT BREAKERS
TO COMPLETE THE WORK.
REVIEWED FOR
COMPLIANCE WIT H
NFPA 70 - NEC
DEC 0 6 2013
City of Tukwila
BUILDING DIVISION
SUPERCEDES IFC SET
DATED 09.23.13
FOR CONSTRUCTION
EL\ I�
RECEIVED
CITY OF TUKWILA
NOV 2 7 2013
PERMIT CENTER
4 2 0 2 4 8
N MI
SCALE: 1/4" = 1'-0"
SYM
REVISION
A
B
NCO SIF RELOCATION - 60% IFR WH_13063
NCO SIF RELOCATION - 80% IFR WH_13063
NCO SIF RELOCATION - IFC WH_13063
W1844093
W1844093
W1844093
BY
WH
WH
WH
APPROVED
DATE
SYM
REVISION
BY
APPROVED
DATE
MAS
MAS
MAS
09.03.13
09.11.13
11.04.13
gLAOE/NG'
ACCEPTABILITY
THIS DESIGN AND/OR
SPECIFICATION IS APPROVED
DRAWN
T. JOHNSTON
DATE
09.03.13
CHECKED
M. SANIDAD
09.03.13
SUBTITLE
NCO SIF SST LAB ENLARGED 208V POWER PLAN
CURRENT REVISION
W1844093
SYMBOL
DATE
11.04.13
APPROVED BY
DEPT.
DATE
ENGINEER
M. SANIDAD
09.03.13
CHECKED
APPROVED
APPROVED
TITLE
ELECTRICAL MASTER
NCO SIF RELOCATION
BUILDING 9-98.2
COL. 9 -8/P -S
DEV. CENTER, WA
SHEET
2E452
JOB NO.
W1844093
COMP NO.
DWG NO.
9-098-2E452
co
0
TJOHNSTON: 05/29/13