HomeMy WebLinkAboutPermit M14-0120 - FAIRWAY CENTER - BUILDING A - ROOFTOP GAS HEATING AND AIR CONDITIONING UNITSFAIRWAY CENTER
BUILDING A
14220 INTERURBAN AVE S
M14-0120
City of Tukwila
Department of Community Development
6300 Southcenter Boulevard, Suite #100
Tukwila, Washington 98188
Phone: 206-431-3670 ,
Inspection Request Line: 206-438-9350
Web site: httD://www.TukwilaWA.eov
MECHANICAL PERMIT
Parcel No: 3365901881 Permit Number: M14-0120
Address: 14220 INTERURBAN AVE S Issue Date: 7/2/2014
Permit Expires On: 12/29/2014
Project Name: FAIRWAY CENTER - BUILDING A
Owner:
Name: BELLTOWN INVESTMENT PARTNER
Address: 2505 2ND AVE #520 , SEATTLE, WA,
98121
Contact Person:
Name: ADRIANA BONILLA Phone: (206) 367-2500
Address: 3132 NE 133 ST, SEATTLE, WA, 98125
Contractor:
Name: PSR-HVAC & MECHANICAL SERVICES Phone: (206) 367-2500
Address: PO BOX 27073 , SEATTLE, WA, 98165
License No: PSRHVMS924JT Expiration Date: 4/30/2016
lender:
Name:
Address: , , ,
DESCRIPTION OF WORK:
REPLACE (1) ROOFTOP GAS HEATING/ELECTRIC AIR CONDITIONING PACKAGE UNIT
Valuation of Work: $10,766.00
Type of Work: REPLACEMENT
Fuel type: GAS
Fees Collected: $337.36
Electrical Service Provided by: PUGET SOUND ENERGY
Water District: TUKWILA
Sewer District: TUKWILA SEWER SERVICE
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
2012 International Fuel Gas Code:
2012 WA Cities Electrical Code:
2012 WA State Energy Code:
2012
Permit Center Authorized Signature: 111-)-A---
2012
2012
2012
Date: -7 _.)---- ! LI
I hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or th performance of work. I am authorized to sign and obtain this
development permi d agree tarh" co s attached to this permit.
Signature:
Print Name: PA I fY1aLr yaeC.,k$
Date: /7—/2..49/
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or if
the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
2: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
3: Readily accessible access to roof mounted equipment is required.
4: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
5: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap
the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks,
wells, and other excavations. Final inspection approval will be determined by the building inspector based
on satisfactory completion of this requirement.
6: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the
City of Tukwila Building Department (206-431-3670).
7: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
8: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the City
of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or other
ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
9: ***MECHANICAL PERMIT CONDITIONS***
10: All mechanical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center (206/431-3670).
19: The attached set of building plans have been reviewed by the Fire Prevention Bureau and are acceptable
with the following concerns:
12: Remote indicator lights are required on all above ceiling smoke detectors. (City Ordinance #2437)
14: H.V.A.C. units rated at greater than 2,000 cfm require auto -shutdown devices. These devices shall be
separately zoned in the alarm panel and local U.L. central station supervision is required. (City Ordinance
#2437)
15: H.V.A.C. systems supplying air in excess of 2,000 cubic feet per minute to enclosed spaces within buildings
shall be equipped with an automatic shutoff. Automatic shutoff shall be accomplished by interrupting the
power source of the air -moving equipment upon detection of smoke in the main return -air duct served by
such equipment. Smoke detectors shall be labeled by an approved agency for air -duct installation and shall
be installed in accordance with the manufacturer's installation instructions. (IMC 606.1, 606.2.1)
16: Duct smoke detectors shall be capable of being reset from a single point near the alarm panel. (City
Ordinance #2437)
17: Duct detectors shall send a supervisory signal only upon activation. (City Ordinance #2437)
13: All new fire alarm systems or modifications to existing systems shall have the written approval of The
Tukwila Fire Prevention Bureau. No work shall commence until a fire department permit has been
obtained. (City Ordinance #2437) (IFC 901.2)
18: An electrical permit from the City of Tukwila Building Department Permit Center (206-431-3670) is required
for this project.
11: Contact The Tukwila Fire Prevention Bureau to witness all required inspections and tests. (City Ordinances
#2436 and #2437)
20: Any overlooked hazardous condition and/or violation of the adopted Fire or Building Codes does not imply
approval of such condition or violation.
21: These plans were reviewed by Inspector 511. If you have any questions, please call Tukwila Fire Prevention
Bureau at (206)575-4407.
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1400 FIRE FINAL
0703 MECH EQUIP EFF
1800 MECHANICAL FINAL
0705 REFRIGERATION EQUIP
0701 ROUGH -IN MECHANICAL
0702 SMOKE DETECTOR TEST
CITY OF TUKWILA
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Mechanical Permit No.
Project No.
Date Application Accepted: (`•t O ^ I L
Date Application Expires:
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
King Co Assessor's Tax No.: 3365901881
Site Address: 14220 Interurban Avenue South Suite Number: Floor: Roof
Tenant Name: Fairway Center, Buildings A New Tenant: ❑ Yes m..No
PROPERTY OWNER
Name: BELLTOWN INVESTMENT PARTNER
Address: 14220 INTERURBAN AVE S 98168
City: Tukwila State: WA Zip: 98188
CONTACT PERSON - person receiving all project
communication
Name: Adriana Bonilla
Address: 3132 NE 133rd Street
City: Seattle state: WA Zip: 98125
Phone: (206) 367-2500 Fax: (206) 368-6856
Email: adriana.bonilla@psrmechanical.com
MECHANICAL CONTRACTOR INFORMATION
Company Name: PSR Mechanical
Address: 3132 NE 133rd Street
City: Seattle State: WA Zip: 98125
Phone: (206) 367-2500 Fax: (206) 368-6856
Contr Reg No.: PSRHVMS924JT Exp Date: 04/30/2014
Tukwila Business License No.: 602811195
Valuation of project (contractor's bid price): $ 10,766
Describe the scope of work in detail: Replace 1 RTU gas heating/electric air conditioning package unit
Use: Residential: New ❑ Replacement ❑
Commercial: New ❑ Replacement
Fuel Type: Electric
Gas m
Other:
H:\Applications\Forms-Applications On Line\201 I Applications\Mechanical Permit Application Revised 8-9-I I.docx
Revised: August 201 I
bh
Page 1 of 2
r
•
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Furnace >100k btu
Floor furnace
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cooling
system
Air handling unit
<10,000 cfiu
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system
Hood and duct
Incinerator — domestic
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
Thermostat
Wood/gas stove
Emergency generator
Other mechanical
equipment
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER OR AU )4HO
Signature:
GENT:
Date: 06/09/2014
Print Name: Adriana Bonilla Day Telephone: (206) 367-2500
Mailing Address: 3132 NE 133rd Street
H:\Applications\Forms-Applications On Line\201 I Applications\Mechanical Permit Application Revised 8-9-1I.docx
Revised: August 2011
bh
Seattle WA 98125
City State Zip
Page 2 of 2
Cash Register Receipt
City of Tukwila
DESCRIPTIONS I ACCOUNT
PermitTRAK
QUANTITY
I PAID
$337.36
M14-0120 Address: 14220 INTERURBAN AVE S Apn: 3365901881
$337.36
MECHANICAL
$324.38
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$32.50
PERMIT FEE
R000.322.100.00.00
0.00
$227.00
PLAN CHECK FEE
R000.322.102.00.00
0.00
$64.88
TECHNOLOGY FEE
$12.98
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R2319
R000.322.900.04.00
0.00
$12.98
$337.36
Date Paid: Tuesday, June 10, 2014
Paid By: PSR MECHANICAL
Pay Method: CHECK 013016
Printed: Tuesday, June 10, 2014 11:11 AM 1 of 1
SYSTEMS
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION 61
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Type of Inspection:
Special Instructions:
Date Wanted:
Requester:
Phone No:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION . 11
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
INSPECTION RECORD
Retain a copy with permit
Project: ,
Type of Inspection:
Address:
Special 'Instructions:
ElApproved per applicable codes. rrections required prior to approval.
COMMENTS:
A
Inspector:
Date:
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
Type of iinsspecttioonn: - /^' j `! A-)/
Address: (
Date Called:
Special Instructions:
Date Wanted
Requester:
Phone No
ElApproved per applicable codes. 12 ections required prior to approval.
COMMENTS:
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
Bi
lling Address
INSPECTION RECORD
Retain a copy with permit
INSPECTION NUMBER
/IA
,l -1- TX,
PERMIT NUMBERS
CITY OF TUKWILA FIRE DEPARTMENT
446, Andover Park East, Tukwila, Wa. 98188 206-575-4407
Project: of/di 0,(44r-
Type of nspe tion:
Suite #: 4-A--1
Contact Person:
Special Instructions:
Phone No.:
%.,,Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
/1 ii7-e
cf ey 710 AI/
Needs Shift Inspection:
Sprinklers:
Fire Alarm:
Hood & Duct:
Monitor:
Pre -Fire:
Permits:
Occupancy Type: ,
Inspector:
/3 3
Date: j0/2_0 y
Hrs.:
% b
$100.00 REINSPECTION FEE REQUIRED. You will receive an invoice from
e City of Tukwila Finance Depaytme t. Call to schedule a reinspection.
`I(
Attn:
Company Name:
Address:,7Q3 0 ,4/7 .P' i2 7 W f-
City: S Q44 7T'
A ,4'%A72- rvc
`(State: t4J
Zip:
Word/Inspection Record FormDoc
6/11/10
T.F.D. Form F.P. 113
CWA CONSULTANTS, P.S.
STRUCTURAL ENGINEERING
BUILDING CODE CONSULTANTS
PILE COPY
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUN 2 7 2014
8675 E. Caraway Road, Port Orchard, WA 98366 (360) 871-5433 FAX: (360) 871-5633 E Mail: chuck r)cwaoon.
June 9, 2014
HVAC Roof Attachment
l'SR HVAC and Mechanical Services
Fairway Center Unit A4
Seattle, WA
Fp=_(0_.4apxSDs)(1+2z/h) Wp
Rp/Ip
ASCE 7 Table 13.6-1 ap=2.5, Rp=6.0
SPs = 0.846
z/h = 1.0 max
Connect new metal curb
of HVAC unit to existing
wood framing #12
screws (4 min) @ 24" oc
at perimeter
Connect HVAC unit to
curb per manufacturer's
installation instruction
Fp = (0.4x2.5x0.846x3.0) Wp = 0.423 Wp
6.0/1.0
Fp max
=1.6x0.846 =1.35
Fp min
= 0.3x0.846 = 0.25
Use 0.423
`stity of Tukwila
BUILDING DIVISION
Fp@CG— ¢
Wp
4x6 at curb support with
5A48 top flange hanger each
end (Existing)
Existing 16" TJI Type Roof
Joists
Existing 8-3/4"x36" GIu-Lam
Carrier 48HCED08B2A6-0B0130
HVAC Unit — Wt =1119# + 110# =1229# total including curb
L=88" W = 60" H = 49" Cg = 22" +14" curb = 36" above base
Fp = 0.423x1229 = 520#
Wind X = .85x1.3x(4.0x6.5)(13) = 373#
Wind Y = .85x1.3x(4.0x4.0)(13) =172# USE 520# for all talcs
cet
OT (worst case) = 520x36 — 0.6x1229 x (60-34) _ -452"# no net overturning RECEIVED
CITY OF TUKWILA
Attachment
HVAC Unit connection to existing wood framing- #12 Wood screws
Cap = (130x1.6)# x 4 (min) = 832# min > 520# OK
Max Corner Weight = 278# (4x6 span 4' OK)
JUN 102014
PERMIT CENTER
MI3oI2o
R:\Documents\Word Fiies\PSR\PSR Fairway Center HVAC Installation A4.doc
Performance Summary For A4
Project:—Untitled2
Prepared By:
05/09/2014
07:24PM
Part Number:48HCED08B2A6.0B0B0
ARI EER• _ 12.00
IEER 13.0
Base Unit Dimensions
Unit Length. 88.1 in
Unit Width. 59.5 in
Unit Height 49.4 in
Operating Weight
Base Unit Weight . 925 Ib
Medium Heat 15 Ib
RA Smoke Detector_ 5 lb
Medium Static Option - Belt Drive. 15 Ib
Temperature Economizer w/ Barometric Relief. 74 Ib
HACR Breaker:___. 10 Ib
Accessories
Power Exhaust System'
Total Operating Weight
Unit
Unit Voltage -Phase -Hertz. _460-3-60
Air Discharge' Vertical
Fan Drive Type* Belt
Actual Airflow. 3000 CFM
Site Altitude:. 0 ft
Cooling Performance
Condenser Entering Air DB• 95.0 F
Evaporator Entering Air DB• 80.0 F
Evaporator Entering Air WB• 67.0 F
Entering Air Enthalpy 31.44 BTU/Ib
Evaporator Leaving Air DB• 57.7 F
Evaporator Leaving Air WB• 57.2 F
Evaporator Leaving Air Enthalpy• 24.53 BTU/Ib
Gross Cooling Capacity 93.30 MBH
Gross Sensible Capacity 72.19 MBH
Compressor Power Input. 6.24 kW
Coil Bypass Factor 0.198
Heating Performance
Heating Airflow. 3000 CFM
Entering Air Temp:.. 70.0 F
Leaving Air Temp. 115.7 F
Gas Input Capacity. 120.01180.0 MBH
Gas Heating Capacity' 148.00 MBH
Temperature Rise- 45.7 F
NOTE- Second Stage
Supply Fan
External Static Pressure. 1.00 in wg
Options / Accessories Static Pressure
EconoMi$erlV / EconoMi$er2• 0.11 in wg
Power Exhaust' (Fan Data Includes Drop)
Total External Static* 1.11 in wg
Fan RPM. 913.
Fan Power _ 1.69 BHP
NOTE Selected IFM RPM Range: 690 - 936
Power Exhaust
Packaged Rooftop Builder 1.39i Page 7 of 32
Certified Drawing for A4
Project: -Untitled2
Prepared By:
05/09/2014
07:24PM
NOTES:
is 5
11
9
91EA04 14ILCIVFTEGSOINEN310N5
2. CENTER OF GRAVITY
3. 1.10, DIRECTI04 OF AIR FLOW
UNIT J ) N
H
48RC-A01 41 114
((0481
33 3(4
1A571
(S 1/9
1491E
46HC•D9 49 3/8
[12531,
34 3/8
18233
15 7/8
1403E
48�'1[ 123118
9ra 2
(403 8
FILTER ACCESS PANEL
I T001-LESS1
INDOOR COIL.
ACCESS PANEL
CONDENSER
COIL
BACK
3.374
lf51 59 1/2
(15107
/ I LSE'
OPTIONAL
FACTORY
INSTALLED
CONVENIENCE
OUTLET
Packaged Rooftop Builder 1.391
LEFT
4-5/8
0181
1
1:1151 (1121 11557 111
1 j (2781
ECTRICAL
DISC0N9EC1
LOCATION
27.7/9
l7 9I
7-5/
(671
T7P
CURB
VIDE
1
29 5/8
(7511
E ALT.
CONDENSATE
AIN OPEM]NO
1h11'4 IN SASEPAN
V
[�— ID 3/8
110211
URETER P.o. eo1 am
TECH10E061ES 4140D1t, 11
CARRIER t0721
111Ii1 >(lY(1tt(11C ACNPT1t 8110E [MDifi10 9N11T114
108?EIIF Fill TOT 11 D(Nt10fTD 0R 0110 YIfNOtt.CAM'[[
<OIIOIA1104Y FA1hCF CO'fFXi.
514F1111C1 01 7A[11 F475879P1s1 04 f011RR4
D0F3 0? 00111/1m51 �411]IYIIK04 4NC0 0R
ECONDNIIER H000
IOPTI0NAL1
ti8
EE THRU
THE BASE
CHART
36-3/0
(9251
RETURN AIR
20-3/4
(731I
SUPPLY
Alt
20-3.4
(3211
12-5/9
[3211
31-316 40-3/8
1953E [1 211
cm, \--FLUE
HOOD
TOP
3.1/4
—" 14 .�..- 183E
(3581
2S 1/2 —6,
0140
8
CONTROL BOX
ACCESS PANEL
OPTIONAL
T0CNAL
FACIORY
INSTALLED
•DISCONNECT
F
NANDLE�.b
N• • t•�5�m
—
iii
0-3/8
INDOOR BLOWER
ACCESS
: �NANOLE •
C/7/
• _ 2
N
37 12141
8910E
09-1/8
[2t301
FRONT
4011
RETURN
AIR
SUPPLE
AIR
(321
13-7/8
I3 30
5-3/4
I1461
6-1/4
(140)
(1591
CONNECTION SIZES
A
1 3/8. 1)51 DIA FIELD POWER SUPPLY ROLE
8
t 1/2' 1141 01A POKER SUPPLY KNOCKOUT
C
1 3/4' (511 0(A GAUGE ACCESS PLUG
D
1/S' (227 D[A FIELD CONTROL WIRING ROLE
E
3/4'-I4 KEPT C09DENSATE DRAIN
1/2--14 8PT DA3 CONNECTION
3/4'-74 KEPT GAS CONNECTION
0
2 ' 131E REA POWER SUPPLY RHCC4-OUT
THRU THE -BASE CHART (FIELD INST)
THESE HOLES REQUIRED FOR USE 91TH AM BITS:
C981700001A01: 01 - GAS THRU CURB
CRBTNF9R102A01: 08,09 - 6AAS TRIM CRAB
C191NF9A003A01: 01 - GAS TIIRU MOAN
CIBTVP 11004A01: 08,09 - GAS TR1U BASEPAN
THREADED
HIRE.
REO'D ROLE
CONDUIT 312E
USE
STIES (MIA
V
1/2'
ACC,
7/0' 122.21
T
1/2'
24V
7/8' [22.21
3/4' (001,0031
1 1/8' 128.51
T
1 1/4' (002.D041
POWER
1 311' (44.41
(0031 1/2' FPT
1 1/8' (28.61
(0041 3/00/1
OAS
1 311' 144.41
- Y
(001 1 002) PROV10
FLAKE 1 FITTING.
9 3/4' FIT TRRU C098
4)0.E SITE: 2' 130.8E
THRU-THE-BASE CHART (FIOPI
FOR •T4RU-I11E-BASEPAN' FACTORY-0PT101,
FITTINGS FOR ONLY X, T, 1 2 ARE PROVIDED. I'
IFOR BELOW LISTED ROOFER. A FIE1O
1 UPPIIED 1/2' ADAPTER IS REOVIREO
i4
SEMEN BASE PAN FITTING AND OAS VALVE(
9NCO,E,S,1-01
0(00,5-08
40HCO,G-09
12•518
I)211
E BYO..
CONDENSATE
DAMN
+--- 28-I/8
MN)
SUPPLY AIR
'
RETURN.
N
AR
•
37 7/8
1942E
SUPPLY
AIR
11771 5-41
1148E
41 7/B
E10051 Aik
RIGHT
RETURN
AIR
LEER
t 4.519
(1131
BAAONE7RIC
RELIEF
FLOW
SKEET
10F2.
41t
10-05-10
annuls
10-16-09
48HC 07-09 SINGLE ZONE ELECTRICAL
COOLING WITH GAS HEAT
48T11502708
A
Page 5 of 32
Certified Drawing for A4
Project:-Untitled2
Prepared By:
05/09/2014
07:24PM
OMIT
STD. UNIT
RE(6N( 9
COINER
WEIGHT SA1
CORNER
WEIGHT (87
C0RNE1
9EI6NT ICI
CORNER
MOAT (D1
C.O.
LDS.
AG.
LN1.
KG.
OS.
AG.
LISS',
E6.
US.
KG.
A
T
2
1186-407
765
341
165.3
15
152.7
i9.3
214.7
91,4
232.3
105.4
42 5/8 510141
34 314 (882.61
19
718
15051
48)00-008
025
410.5
204.1
/2.4
190.0
06.6
251.1
116.2
2/3.9
124.2
42 5/8 E14421
34 1/4 (8671
22
1/0
75816
42864104
525
419.2
204.1
42.6
100.0
98.0
256.1
116.2
273.9
124.2
02 5/3 (10621
34 110 11271
22
118
(5911
CORNER A
6-
`r-1
o
{
}
l
IJ
100
i
1
1
:
00
0
UNITE4 9.8, 101 4103
TECHNOLOGIES 14n90Q, 91
1:0119T50188919 0 a 04I1*91 97 a C/u001 79 t4i111[
4N960 1(09l 1 NNIno 1 1, a SYE4 Ni79air 9A9aa
1994199104 99 I1111 MA4(469 M1 00RRR9
e0E1 491 1419016 9A41 41410AY44N 08
397A9a_0( 044(1417.
SIA90ARD SNIT WEIGHT IS WITH LOW OAS HEAT AND WITHOUT PACKAGIRO,
FOR OTHER OPTIONS Alp ACCESSORIES. REFER TO TIE PRODUCT DATA CATALOG.
CORNER B
4RE7
20F2
Ulf
10-05-10
410218260
10-16-09
488C 08-12 SINGLE ZONE ELECTRICAL
COOLING WITH GAS HEAT
48114502708
A
Packaged Rooftop Builder 1.391
Page 6 of 32
d YI i
S2130YVH f /M 11V3
0312f0ddOddnS 'O0 ,8b ft
(rl) !slot` ssnat ,9l
b-vi i!unr
d.l 'SYVV38 WV1-n10 1NOddfS 01
13)IO0d FW38 MA NWn103 1331S
-xoaaav o ,9-
jA1 'WV38 WV1-010 ,b/£-9x,6£
2130 H
® 031
180ddn
isior HlIM rl
ddOS ONIIW U
8n3 fHV 9xb
—11
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M14-0120 DATE: 06/10/14
PROJECT NAME: FAIRWAY CENTER - BUILDING A
SITE ADDRESS: 14220 INTERURBAN AVE S
X Original Plan Submittal
Revision #
before Permit Issued
Response to Correction Letter # Revision # after Permit Issued
DEPARTMENTS:
Building Division II
Public Works
AV imm009
Fire Prevention me
rk 01o1-Li•(LA
Structural
Planning Division
Permit Coordinator 1111
PRELIMINARY REVIEW:
Not Applicable
(no approval/review required)
DATE: 06/12/14
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved
Corrections Required
(corrections entered in Reviews)
Approved with Conditions
Denied
(ie: Zoning Issues)
DUE DATE: 07/10/14
n
Notation:
REVIEWER'S INITIALS:
DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg ❑ Fire ❑ Ping ❑ PW ❑ Staff Initials:
12/18/2013
PSR-HVAC & MECHANICAL SERVICES
Page 1 of 2
Washington State Department of
' Labor & Industries
PSR-HVAC & MECHANICAL SERVICES
Owner or tradesperson
O'MALLEY, JAMES J
Principals
O'MALLEY, JAMES J, MEMBER
HOGERTY, REAGAN P, MEMBER
BAVINS, NEIL JONATHAN, MEMBER
O'DONNELL, STEPHEN 0
(End: 04/12/2012)
RIST, STEVEN L
(End: 04/12/2012)
Doing business as
PSR-HVAC & MECHANICAL SERVICES
WA UBI No.
602 811 195
PO BOX 27073
SEATTLE, WA 98165
206-367-2500
KING County
Business type
Corporation
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor Active.
Meets current requirements.
License specialties
GENERAL
License no.
PSRHVMS924JT
Effective — expiration
04/30/2008— 04/30/2016
Bond
International Fidelity Ins Co
Bond account no.
0649932
$12,000.00
Received by L&I Effective date
03/28/2014 03/26/2014
Expiration date
Until Canceled
Insurance
Zurich American Ins Co $1,000,000.00
Policy no.
GL0488649704
https://secure.lni.wa.gov/verify/Detail.aspx?UBI=602811195&LIC=PSRHVMS924JT&SAW= 07/02/2014
LEGEND
ABBREVIATIONS
RISE
CUBIC FEET PER MINUTE
CENTER LINE
ROUND DUCT INDICATOR
OVAL DUCT INDICATOR
THERMOSTAT LINE
DIRECTION OF RISE FOR DUCT
DUCT (FIRST FIGURE DENOTES VIEW SHOWN)
SINGLE LINE DUCTWORK INDICATES DUCT
WITH VIEW DIMENSION LESS THAN 12 INCHES
SUPPLY OR EXHAUST TAKEOFF
SUPPLY DUCT TURNING TOWARD, UP
SUPPLY DUCT TURNING AWAY
EXHAUST DUCT TURNING TOWARD, UP
EXHAUST DUCT TURNING AWAY
ROUND DUCT TURNING TOWARD, UP
ROUND DUCT TURNING AWAY
OVAL DUCT TURNING TOWARD, UP
OVAL DUCT TURNING AWAY
CONICAL WYE
CONICAL TEE
VOLUME DAMPER(VD)
FIRE SMOKE DAMPER(FSD)
MOTORIZED DAMPER(FD)
FIRE DAMPER(FD)
3-WAY SUPPLY DIFFUSER
2-WAY SUPPLY DIFFUSER
2-WAY CORNER SUPPLY DIFFUSER
1-WAY SUPPLY DIFFUSER
DOUBLE LINE, LINED DUCT/ ACOUSTIC DUCT
RECTANGLE TO RECTANGLE FITTING (RIGHT)
RECTANGLE TO RECTANGLE FITTING (LEFT)
ROUND TO ROUND HIGH/ MEDIUM VELOCITY FITTING
ROUND TO ROUND FITTING
TO SUPPLY DIFFUSERS(DOUBLEULINED CT TAKE -OFF,
LOW VELOCITY (PRESSURE) ROUND QUCT TAKE -OFF,
TO SUPPLY DIFFUSER (SINGLE LINED)
RECTANGLE/ ROUND RADIUSED ELBOW DUCT
RECTANGULAR 90' ELBOW W/ TURNING VANES TYPICAL
ECCENTRIC CONICAL DUCT REDUCTION FITTING
CONCENTRIC CONICAL DUCT REDUCTION FITTING
RECTANGLE TO ROUND FITTING
SOUND ATTENUATOR
TURNING VANES
FLEXIBLE DUCT
THERMOSTAT OR TEMPERATURE SENSOR
THERMOSTAT OR TEMPERATURE SENSOR(CEILING)
DUCT SMOKE DETECTOR
SQUARE SUPPLY AIR DIFFUSER
ROUND SUPPLY AIR DIFFUSER
2'x2' RETURN AIR GRILLE
2'x4' RETURN AIR GRILLE
SIDEWALL SUPPLY AIR GRILLE OR
REGISTER
SIDEWALL RETURN/EXHAUST AIR GRILLE
OR REGISTER
AC
ACF
ADA
ADJ
AFF
AL
ALIGN
AP
APPROX
ARCH
ASME
AVG
BFF
BHP
BLDG
BOD
BOP
BTU
BTUH
BV
CD
CFM
CG
CI
CLG
CO
CONN
CONST
CON T
COORD
CORR
COTG
CU FT
CU IN
DB
DCVA
DEG
DET
DIA
DIFF
DIM
DISCH
DN
DR
DS
DSD
DWG
EA
EAT
EF
EFF
EG
ELECT
ELEV
EMERG
ENT
ESP
EXH
EXIST
EXP
FC
FCO
FD
FDC
FI O
FLA
FLEX
FLR
FOB
FOI C
FOT
FPM
FPS
FSD
FT
FU
G
GA
GAL
GALV
GEN
GND
GPH
GPM
H
HP
HR
HTG
HVAC
HZ
IBC
ID
IE
IMC
IN
INSUL
IW
AIR CONDITIONING
AIR CURTAIN FAN
AMERICAN DISABILITIES ACT
ADJACENT; ADJUST; ADJUSTABLE;
ADJUSTMENT
ABOVE FINISHED FLOOR
ACOUSTIC LINED
ALIGNMENT
ACCESS PANEL
APPROXIMATELY
ARCHITECTURAL
AMERICAN SOCIETY OF
MECHANICAL ENGINEERS
AVERAGE
BELOW FINISH FLOOR
BRAKE HORSEPOWER
BUILDING
BOTTOM OF DUCT
BOTTOM OF PIPE
BRITISH THERMAL UNIT
BRITISH THERMAL UNITS PER
HOUR
BALANCING VALVE
CEILING DIFFUSER
CUBIC FEET PER MINUTE
CEILING GRILLE
CAST IRON
CEILING
CLEANOUT
CONNECT; CONNECTED;
CONNECTION
CONSTRUCTION
CONTINUOUS; CONTINUATION
COORDINATE
CORRIDOR
CLEANOUT TO GRADE
CUBIC FEET
CUBIC INCHES
DRY BULB TEMPERATURE
DOUBLE CHECK VALVE ASSEMBLY
DEGREE
DETAIL
DIAMETER
DIFFERENTIAL
DIMENSION
DISCHARGE
DOWN
DRAIN
DOWNSPOUT
DUCT SMOKE DETECTOR
DRAWING
EACH
ENTERING AIR TEMPERATURE
EXHAUST FAN
EFFICIENCY
EXHAUST GRILLE
ELECTRI CAL
ELEVATION
EMERGENCY
ENTERING
EXTERNAL STATIC PRESSURE
EXHAUST
EXISTING
EXPANSION
FAHRENHEIT
FANCOIL
FLOOR CLEANOUT
FIRE DAMPER
FIRE DEPARTMENT CONNECTION
FURNISHED AND INSTALLED BY
OWNER
FULL LOAD AMP
FLEXIBLE
FLOOR
FLAT ON BOTTOM
FURNISHED BY OWNER INSTALLED BY
CONTRACTOR
FLAT ON TOP
FEET PER MINUTE
FEET PER SECOND
FIRE SMOKE DAMPER
FOOT, FEET
FIXTURE UNITS
GAS
GAGE
GALLON
GALVANIZED
GENERAL
GROUND
GALLONS PER HOUR
GALLONS PER MINUTE
HEIGHT, HIGH
HORSEPOWER
HOUR
HEATING
HEATING, VE NTILATING, AND AIR
HERTZ
INTERNATIONAL BUILDING CODE
INDIRECT DRAIN
INVERT ELEVATION
INTERNATIONAL MECHANICAL CODE
INCH
INSULATE; INSULATION
INDIRECT WASTE
KW
KWH
L
LAV
LAT
LB
LF
LVG
MA
MAX
MBH, MBTU
MCA
M CC
MD
MECH
MFR
MIN
MISC
MOD
MTD
MTG
NC
NIC
N TS
OAC
OAT
OD
OH
ORD
OA
P
PD
PH
POC
PRELIM
PRESS
PRV
PSI
PSIG
RA
RD
RECIRC
RECT
REF
REG
REQD
RND
RPBP
RPM
RV
SCHED
SF
SG
SO
SOV
SP
SPEC
SPECD
SST
SS
STRUCT
SWG
SWR
TBD
TEM P
TSTAT
THRU
TOD
TOP
TP
TS
TV
TYP
UPC
U TR
VD
VEL
VERT
VOL
VTR
W
WCO
WB
WEF
WG
W/
w/o
WT
KILOWATT
KILOWATT HOUR
LENGTH
LAVATORY
LEAVING AIR TEMPERATURE
POUNDS
LINEAL FOOT
LEAVING
MIXED AIR
MAXIMUM
THOUSAND BRITISH THERMAL UNITS
PER HOUR
MINIMUM CIRCUIT AMPACITY
MOTOR CONTROL CENTER
MOTORIZED DAMPER
MECHANICAL
MANUFACTURER
MINIMUM; MINUTE
MISCELLANEOUS
MOTOR OPERATED DAMPER
MOUNTED
MOUNTING
NOISE CRITERIA
NOT IN CONTRACT
NOT TO SCALE
OUTDOOR AIR CONDITIONER
OUTSIDE AIR TEMP
OUTSIDE DIAMETER; OVERALL
DIAMETER
OVERHEAD
OVERFLOW ROOF DRAIN
OUTSIDE AIR
PUMP
PRESSURE DROP; PIT DRAIN
PHASE
POINT OF CONNECTION
PRELIMINARY
PRESSURE
PRESSURE REDUCING VALVE
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH GAGE
RETURN AIR
ROOF DRAIN
RECIRCULATING
RECTANGULAR
REFERENCE
REGULATOR
REQUIRED
ROUND
REDUCED PRESSURE BACKFLOW
PREVENTER
REVOLUTIONS PER MINUTE
RELIEF VALVE DISCHARGE
SCHEDULE
SUPPLY FA, SQUARE FEET
SUPPLY GRILLE
SCREENED OPENING
SHUT OFF VALVE
STATIC PRESSURE
SPECIFICATION
SPECIFIED
STAINLESS STEEL
SOIL STACK, SANITARY SEWER
STRUCTURAL
SUPPLY WALL GRILLE
SUPPLY WALL REGISTER
TO BE DETERMINED
TEMPERATURE; TEMPORARY
THERMOSTAT
THROUGH
TOP OF DUCT
TOP OF PIPE
TRAP PRIMER
TEMPERATURE SENSOR
TURNING VANE
TYPICAL
UNIFORM PLUMBING CODE
UP THRU ROOF
VENT
VOLUME DAMPER
VELOCITY
VERTICAL
VOLUME
VENT TO ROOF
WASTE
WALL CLEAN OUT
WET BULB TEMPERATURE
WALL EXHAUST FAN
WATER GAGE
WITH
WITHOUT
WEIGHT
GENERAL NOTES: GENERAL HVAC NOTES:
1. COMPLETE INSTALLATION OF THE MECHANICAL SYSTEM SHALL BE PER THE LATEST ADOPTED VERSION OF INTERNATIONAL
BUILDING CODE (IBC), INTERNATIONAL MECHANICAL CODE (IMC), WASHINGTON STATE ENERGY CODE (WSEC), UNIFORM
PLUMBING CODE (UPC), INTERNATIONAL FUEL GAS CODE (IFGC), INTERNATIONAL FIRE CODE (IFC), NFPA AND HEALTH
CODES AND REGULATIONS AS ADOPTED BY THE LOCAL JURISDICTIONS.
2. CONTRACTOR SHALL COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS AND DUCT ROUTING CLEARANCES WITH
THE STRUCTURAL REFLECTED CEILING AND LIGHTING PLANS.
1. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK (HVAC) ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND
GENERAL ARRANGEMENT ONLY.
2. LOCATE ALL TEMPERATURE, DEVICES IN DUCTWORK LOCATIONS WITH STRAIGHT SEC11ON OF DUCT UP AND DOWNSTREAM AS
RECOMMENDED BY THE MANUFACTURER FOR GOOD ACCURACY.
.-.3, DINATE AND PROVIDE ALL DUCT TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT.
REVIEWED FOR
VERIFY AND COORDINATE ALL DUCT DIMENSIONS BEFORE FABRICATION.
3. MAKE ACCEPTABLE ACCESS PROVISIONS FOR REMOVAL OF FILTER AND MAINTENANCE FOR ALL INDOOR UNITS. REFER CODE COMPLIANCE
MANUFACTURER'S INSTALLATION GUIDE. APPROVED AL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS REQUIRED TO PROVIDE A VIBRATION FREE INSTALLATION, AND
4. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE. JUN 2 7 2014 OF
SEI VIBRATION TOCBUILDING STRUCTUREED AS REQUIRED. OVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT TRANSMISSION
5. WHEN MECHANICAL WORK (HVAC, PLUMBING, SHEET METAL, FIRE PROTECTION, ETC.) IS SUBCONTRACTED, IT SHALL B
THE MECHANICAL CONTRACTOR'S RESPONSIBILITY TO COORDINATE SUBCONTRACTORS AND THE ASSOCIATED CONTRAC
WHEN DISCREPANCIES ARISE PERTAINING TO WHICH CONTRACTOR PROVIDES A PARTICULAR ITEM OF THE MECHANICA
CONTRACT OR WHICH CONTRACTOR PROVIDES FINAL CONNECTIONS FOR A PARTICULAR ITEM OF THE MECHANICAL
CONTRACT, IT SHALL BE BROUGHT TO THE ATTENTION OF THE MECHANICAL CONTRACTOR.
6. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE DOCUMENTS THAT ARE NOT
DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST
CONDITIONS AND RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE APPROVAL
OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.
7. ALL ROOF PENETRATIONS SHALL BE MINIMUM OF 5 FEET AWAY FROM THE AREA/OCCUPATION SEPARATION WALLS. ALL
PIPE, DUCT AND CONDUIT PENETRATIONS THROUGH RATED ASSEMBLIES SHALL BE FIRE AND SMOKE STOPPED PER CODE.
8. ALL EQUIPMENT, DAMPERS, PIPING, AND ACCESSORIES IN CONCEALED SPACES REQUIRING ACCESS SHALL HAVE ACCESS
DOORS. ALL ACCESS DOORS IN FIRE RATED STRUCTURE SHALL BE FIRE RATED. COORDINATE LOCATIONS WITH ARCHITECT.
CONTRACTOR TO PROVIDE ACCESS DOORS.
9. ALL EQUIPMENT SHALL BE FREE FROM DEFECTS IN MATERIAL, WORKMANSHIP, AND SHALL BE OF THE KIND AND QUALITY
DESCRIBED HEREIN.
10. ALL EQUIPMENT SHALL BE APPROVED FOR INSTALLATION IN THE STATE OF WASHINGTON AND SHALL HAVE ALL
CERTIFICATIONS AND RATINGS REQUIRED TO MEET ALL ENERGY, POLLUTION, ENVIRONMENTAL, SEISMIC, ETC. CODES AND
REGULATIONS.
11. VERIFY ALL THE MECHANICAL EQUIPMENT'S ELECTRICAL LOADS VOLTAGE/PHASE, ETC. WITH ELECTRICAL CONTRACTOR
PRIOR TO ORDERING.
12. WHERE MULTIPLE RISERS OR HORIZONTAL LOOPS ARE USED, BALANCING VALVES IN THE RETURN LINES ARE REQUIRED. A
CHECK VALVE SHALL BE PROVIDED IN EACH RETURN TO PREVENT TEMPORARY REVERSAL OF FLOW.
13. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE
MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY IMC, UPC, IBC,
WASHINGTON STATE ENERGY CODE AND ALL APPLICABLE LOCAL AMENDMENTS.
14. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS' RECOMMENDATIONS,
CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
15. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL STRUCTURAL, ELECTRICAL WORK, ETC.,
SHOWN ON CONTRACT DOCUMENT DRAWINGS.
16. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED.
17. WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED, THE PRODUCT OF ONE MANUFACTURER
SHALL BE USED.
18. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES
INVOLVED.
19. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.
20. RECORD DRAWINGS SHALL BE PROVIDED TO THE OWNER WITHIN 90 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE AS
REQUIRED BY SECTION 1416.1 OF THE WSEC. THE DRAWINGS SHALL INDICATE THE LOCATION AND PERFORMANCE DATA
OF EQUIPMENT, GENERAL CONFIGURATION OF DUCTWORK AND PIPING DISTRIBUTION SYSTEMS, INCLUDING FLOW RATES AS
A MINIMUM, THAT HAVE BEEN DEVIATED FROM THESE DOCUMENTS. A COMPLETE RECORD OF CHANGES SHALL BE KEPT
TO DATE ON A DAILY BASIS AND MADE ACCESSIBLE TO OWNER AND ENGINEER.
2012 WASHINGTON STATE
ENERGY CODE (WSEC) NOTES
1. HVAC EQUIPMENT SHALL HAVE MINIMUM PERFORMANCE AT SPECIFIED RATING CONDITIONS NOT LESS THAN THE VALUES
INDICATED IN C403.2.3.
2. HVAC SYSTEMS SHALL BE EQUIPPED WITH AUTOMATIC CONTROLS CAPABLE OF ACCOMPLISHING SETBACK OR SHUTDOWN
DURING UNOCCUPIED PERIODS AS REQUIRED BY SECTION C403.2.4.3.2 OF THE WSEC AND AS DESCRIBED IN THE
TEMPERATURE CONTROL SEQUENCES, IF PROVIDED.
3. PROVIDE BALANCING DEVICES IN ALL BRANCH DUCTS AND PIPE RUNS TO TERMINAL DEVICES AS REQUIRED BY SECTION
C403.2.7.3 OF THE WSEC AND AS INDICATED ON THE CONTRACT DOCUMENTS.
4. ALL DUCTWORK SHALL COMPLY WITH SMACNA STANDARDS FOR CONSTRUCTION OF GALVANIZED DUCTWORK. ALL DUCTWORK
SHALL BE SEALED AS REQUIRED BY SECTION C403.2.7 "DUCT AND PLENUM..." OF THE WSEC. DUCT TAPE NOT ALLOWED.
5. ALL DUCTWORK SHALL BE INSULATED AS REQUIRED BY SECTION C403.2.7 OF THE WSEC.
6. MOTOR EFFICIENCY SHALL NOT BE LESS THAN THE MINIMUM CALLOUTS PER C403.3.1 AND SECTION C403.2.13 OF THE
WSEC FOR FULL LOAD EFFICIENCIES.
7. HVAC SYSTEMS SHALL BE BALANCED AS REQUIRED BY SEC11ON THE WSEC.
8. IF NOT SPECIFICALLY STATED ABOVE, CONTRACTOR SHALL COMPLY WITH THE WSEC ITEMS THAT DO APPLY TO THIS
PROJECT.
REVISIONS
No changes shall be made to the scope
of work without prior approval of
Tukwila Building Division.
NOTE: Revisions will require a new plan submittal
and may include additional plan review fees.
CE TAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME DAMPERS, ETC. ARE INDICATED ON THE
ila CO TRACT DOCUMENT DRAWINGS FOR CLARITY FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS
ISION EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.
6. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS 4'-0" (CENTERLINE) ABOVE FINISHED FLOOR. NOTIFY THE ENGINEER
OF ANY ROOMS WHERE THE ABOVE LOCATION CANNOT BE MAINTAINED OR WHERE THERE IS A QUESTION ON LOCATION.
7. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.
8. PROVIDE ALL 90 DEGREE SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES UNLESS OTHERWISE INDICATED. PROVIDE
ACCESS DOORS UPSTREAM OF ALL ELBOWS WITH TURNING VANES.
9. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF THE STRUCTURE (WITHIN TRUSSES), WITH
SPACE FOR INSULATION IF REQUIRED.
10. MAXIMUM LENGTH OF FLEXIBLE DUCTS LOCATED ABOVE HARD CEILINGS SHALL BE AS CODE PERMITS BUT NO LONGER THAN 4
FEET.
11. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS, INCLUDING DIVIDED DUCTS AND
TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER.
12. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL VOLUME DAMPERS AND OTHER ITEMS LOCATED IN THE
DUCTWORK WHICH REQUIRE SERVICE AND/OR INSPECTION.
13. ALL DUCTS SHALL BE GROUNDED ACROSS FLEXIBLE CONNECTIONS WITH FLEXIBLE COPPER GROUNDING STRAPS. GROUNDING
STRAPS SHALL BE BOLTED OR SOLDERED TO BOTH THE EQUIPMENT AND THE DUCT.
14. MAKE ACCEPTABLE ACCESS PROVISIONS FOR REMOVAL OF FILTER AND MAINTENANCE FOR ALL INDOOR UNITS.
15. ALL AIR DISTRIBUTION SUPPLY OUTLETS AND RETURN/EXHAUST INLETS SHALL HAVE VOLUME CONTROL DEVICES.
16. ALL 90 DEGREE TRUNK DUCT ELBOWS SHALL BE SMOOTH -ROUND OR SQUARE WITH TURNING VANES.
17. CONTRACTOR SHALL LOCATE AND COORDINATE EXACT LOCATION OF DUCTWORK WITHIN THE STRUCTURE AT SITE.
18. ALL FAN SYSTEMS WITH OVER 2000 CFM SHALL HAVE SMOKE/DUCT DETECTORS TO SHUT -DOWN FAN UPON DETECTION.
DUCT/SMOKE DETECTORS FURNISHED AND INSTALLED BY ELECTRICAL AND WIRED BY ELECTRICAL DUCT/SMOKE DETECTORS
SHALL BE LISTED BY AN APPROVED AGENCY AND FOR INSTALLATION IN AIR DUCTS PER IMC.
19. ALL MECHANICAL HEATING\ AND VENTILATION EQUIPMENT SHALL CONFORM TO SMACNA, LOCAL AND STATE REGULATIONS FOR
SEISMIC RESTRAINT (INCLUDING PIPING AND DUCTWORK). COORDINATE WITH STRUCTURAL
20. ALL RECTANGULAR DUCTWORK SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. SUPPLY AND RETURN DUCTWORK FOR HVAC TO
HAVE 1" SOUNDLINING FOR THE FIRST 10 FEET FROM UNIT DISCHARGE OUTLET. ALL DUCT LINING TOM T AND EXCEED MOLD,
HUMIDITY, EROSION RESISTANT, ETC. TO MEET 1MC CHAPTER 6. ALL DUCTWORK TO BEFUEICOTS. CLASS -II DUCTS
SHALL NOT BE USED.
SITE INFO
Permit No. M L O [2 O
Plan review approval is subject to errors and omissions.
ADDRESS:
OWNER:
14220 INTERURBAN AVE S
TUKWILA, WA 98168
BELLTOWN INVESTMENT PARTNER
Appruvel of construction documents does not authorize
the violation of any adopted code or ordinance. Receipt
of approved Field Copy moons is acknowledged:
By:
Date:
PARCEL/TAX # 3365901881 City of Tukwila
BUILDING DIVISION
HILLMANS SEATTLE GARDEN TRS POR OF LOT 1 & ALL OF LOTS 2 THRU 7 & POR ADJ IN SE 1/4
OF SECTION 14-23-04 DAF - BEG SE COR OF SAID LOT 7 TH NLY ALG ELY LN 315 FT TO LFT
BANK OF DUWAMISH RIVER AS ORIGINALLY PLATTED TH CONTG ON NLY PROD OF SD ELY 220 FT
M/L TO LFT BANK AS EXISTED UNDER SUPERIOR COURT CAUSE NO 81-2-05910-4 TH WLY ALG SD
BANK TO AN INTSN WITH NELY PROD OF SELY LN OF NWLY 72 FT OF SD LOT 1 TH SWLY ALG SD
LN PROD 200 FT M/L TO LFT BANK OF DUWAMISH RIVER AS PLATTED IN ORIGINAL PLAT TH CONTG
IN SWLY DIRECTION ALG SELY .LN -OF NWLY 72 FT OF SD LOT 1 DISTANCE OF 55 FT M/L TO SWLY
LN OF SD LOT 1 TH SELY ALG SD LN TO INTSN WITH N MGN OF S 143RD ST FIRST AVE TH ELY
ALG SD MGN TO TPOB-TGW POR FOSTER JOSEPH DC #39 BEING POR OF ABANDONED PUGET SOUND
ELECTRIC RR R/W IN THE SW 1/4 OF SE 1/4 OF SD SEC 14 SD RR R/W BOUNDED ON NE BY
MAULE AVE ON SW BY A LN 20 FT NE OF & PLT NELY MGN OF SR 181 UNDER REC #8905231113
ON THE SE BY R/W #5 & ON THE NW BY R/W #6 BOTH R/W DEFINED IN QCD AUD FILE #
6557639 - TGW VAC MAULE AVE ADJ TGW POR VAC ST ADJ
LEGAL:
SEPARATE PERMIT
REQUIRED FOR:
❑ Mechanical
4 Etectricai
Plumbing
ta-Gas Piping
City of Tukwila
BUILDING DIVISION
3132 N.E. 133 ST
Seattle, Washington 98125-4423
PO Box 27073
Seattle, Washington 98165-1473
(206) 367-2500
Fax (206) 368-6856
PSRHVMS924JT
a.
0
CC
U
0)
t
1
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
r 1
RECEIVED
CITY OF TUKWILA
JUN 1 0 2014
PERMIT CENTER
1
PERMIT SET
6.10-1,I
`No.
RevisionFlssue
Date'
Drawn By A. BONILLA
6-10-14
Lead Tech
Engineered By
Date
GAS PACKAGED ROOFTOP UMT EQUIPMENT S I-ED i E
IVIARK
A-4
LOCATION UNIT
ROOF
NCNVINAL TONS
7.5
TOTAL C OSA CFM ON CYCLE
3000300 a300 10ae
SP
0.5
HP/BI-P
/1.69
COOLING
TOTAL (MLA-1)
9(3,330
SENSIBLE (BTUH)
72,190
12
SEAT
INPUT (N HEATING (NBH)
1201180 I 148
TBVP RISE
45.7
CFM
3000
SOUND
DBA (DB)
82
ELECTRIC
VOLTAGBPHASE
460V / 3PH
MCA
21
MRCP (ANDS)
25
OPERATI NG
WEIGHT: Lbs
1119
BASIS OF DESIGN
IWANUFACr1.JRER
CARRIER
MODE_
SEFtVIES
CORE AREAS CIF STEs 105, 130, 134, 160
REMARKS
NEW UNIT
SITE PLAN ayl
NTS
+OI246
Project
P4909
Project anager
N. SINGER
VARIES
Sheet
M 0.0
<EY PLAN
NTS
NOTE:
AREA OF WORK
SITE
REVIEWED FOR
CODCOMPLIANCE
APPROVED
JUN 27 2014
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
JUN 1 0 2014
PERMIT CENTER
3132 N.E. 133 ST
Seattle, Washington 98125-4423
PO Box 27073
Seattle, Washington 98165-1473
(206) 367-2500
Fax (206) 368-6856
PSRHVMS924JT
LA, WA 98168
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
IN
1
PERMIT SET
6-10-14
`No. r
Revisionllssue
Date
"'awn By
A. B•NILLA
610-14
Lead Tech
Engineered By
Date
rojed
Sheet
P4909
Project Manager
N. SINGER
Mal
Scate
AS NOTED
�CIDER
A.5
KEY PLAN
SCALE
NOTE:
AREA OF WORK
DEN
1 /16"=1'
0 PLAN
/
28,_0"
Unit flA-2
Unit #A-4
Unit fA-3
REVIEWED ANCE
R
CODE COM
APPROVED
JUN 27 2014
City of Tukwila
BUILDING DIVISION
pi-Unit flA-6
12'-0" /--
b
CV
V('*O1i6
RECEIVED
CITY OF TUKWILA
JUN 1 0 2014
PERMIT CENTER
ro
L)
MI Ma
rri
4—
bJ
A Service Logic Company
3132 N.E. 133 ST
Seattle, Washington 98125-4423
PO Box 27073
Seattle, Washington 98165-1473
(206) 367-2500
Fax (206) 368-6856
PSRHVMS924JT
THE SCHUSTER GROUP
¢ u0
• w
Z�
of
�Q
w m
w
U W
• Z
tY N
N
LA, WA 98168
1
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
1
PERMIT SET
6-10-14
`No.
Revision/Issue
Date'
rawn By
A.BONILLA
6--10-14
Lead Tech
Engineered By
Date
roject
Sheet
P4909
Project Manager
N. SINGER
M 1 .0
Scale
AS NOTED
RMi1, �1 �A
<EY PLAN
SCALE
NOTE:
AREA OF WORK
0
0
0
0
Unit #A-2
28'-0"
a
rn
7— Unit fiA-4
n
Unit #A-3
L
ll
5 —0n
HVAC PLAN
1 /16"=1'
/
REVIEWED FOR
CODE COMPLIANCE
APPROVED
JUN 2 7 2014
City of Tukwila
BUILDING DIVISION
1111-1.---01).0
RECEIVED
CITY OF TUKWILA
JUN 1 0 2014
PERMIT CENTER
•
rB
co
U
N
•
•
(13
F(0
'a l
a)
(73
LLJ
CP
i E
A Service Logic Company
3132 N.E. 133 ST
Seattle, Washington 98125-4423
PO Box 27073
Seattle, Washington 98165-1473
(206) 367-2500
Fax (206) 368-6856
PSRHVMS924JT
1
0
D
0
0
(/)
0
TLLI
i
1
J
COPYRIGHT NOTICE
THIS LAYOUTIDESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
1' 1
1
PERMIT SET
6-10-14
�No.
Revisionllssue
Date,
Drawn By
A. BONILLA
1
6--10-14
Lead Tech
Engineered By
Date
44
4,
Project
Sheet
P4909
Project Manager
N. SINGER
M 2.0
Scale
AS NOTED
2
r EXISTING 3'-6" PARAPET
BUILDING A NORTH ELEVATION
1 /16" = 1'-0"
r EXISTING 3'-6" PARAPET
11
EXISTING ROOF
EXISTING ROOF
J L
lz
BUILDING A EAST ELEVATION
1 /16" = 1'-0"
BUILDI
f- EXISTING 3'-6" PARAPET
NG A SOUTH ELEVATION
1 /16" = 1'-0"
/- EXISTING 3'-6" PARAPET
EXISTING ROOF
REVIEWED FOR
CODE COMPLIANCE
A PoROVED
J;R. 7 ?014
!kwita
'VISION
L
EXISTING ROOF
BUILDING A WEST ELEVATION
1 /16" = 1'-0"
100'-0"
"CV
CO
1n
M 14m-0(2.0
RECEIVED
CITY OF TUKWILA
JUN 1 0 2014
PERMIT CENTER
•
ro
ro
ra
(!)
a)
4--
W
A Service Logic Company
3132 N.E. 133 ST
Seattle, Washington 98125-4423
PO Box 27073
Seattle, Washington 98165-1473
(206) 367-2500
Fax (206) 368-6856
PSRHVMS924JT
i
THE SCHUSTER GROUP
w
Z
ow
5>
z
WCa
Z
U w
N
LL r
TUKWILA, WA 98168
COPYRIGHT NOTICE
THIS LAYOUT/DESIGN IS AN UNPUBLISHED
WORK, AND PUGET SOUND
REFRIGERATION HEREBY RESERVES ITS
COMMON LAW RIGHT, PURSUANT TO TITLE
17 SECTION 2 OF THE USA CODE TO
PREVENT ANY UNAUTHORIZED COPYING,
PUBLICATION OR USE OF THIS DESIGN,
AND TO OBTAIN DAMAGES THEREOF.
i N
1
PERMIT SET
6-10-14
`No.
Revision/Issue
Date,
Drawn By
A. BONILLA
1
6 10-14
Lead Tech
Engineered By
Date
J
Project
P4909
Project Manager
N. SINGER
AS NOT
ED
Sheet
M 3.0
f