MECHANICAL PERMIT
8700200020 Permit Number: M14-0173
4445 S 134TH PL BLDG D
Project Name: FOSTORIA PARK ASOCIATION
Issue Date: 9/24/2014
Permit Expires On: 3/23/2015
Owner:
Name:
Address:
Contact Person:
Name:
Address:
Contractor:
Name:
Address:
FOSTORIA PARK ASSOC LLC
15100 SE 38TH ST #792 C/O ESM
PROPERTIES INC, BELLEVUE, WA,
98006
LAURA SMITH
1221 SECOND VE N , KENT, WA, 98032
HERMANSON CO LLP
1221 2ND AVE N , KENT, WA, 98032-
2945
License No: HERMACL005BJ
Lender:
Name:
Address:
III
Phone: (206) 920-1690
Phone: (206) 575-9700
Expiration Date:
DESCRIPTION OF WORK:
REPLACEMENT OF (1) EXISTING ROOF -TOP UNIT LIKE FOR LIKE
Valuation of Work: $7,560.00
Type of Work: REPLACEMENT
Fuel type: GAS
Fees Collected: $298.16
Electrical Service Provided by: SEATTLE CITY LIGHT
Water District: 125
Sewer District: TUKWILA SEWER SERVICE
Current Codes adopted by the City of Tukwila:
International Building Code Edition:
International Residential Code Edition:
International Mechanical Code Edition:
Uniform Plumbing Code Edition:
Permit Center Authorized Signature:
2012
2012
2012
2012
International Fuel Gas Code:
WA Cities Electrical Code:
WA State Energy Code:
2012
2014
2012
Date: vl 4)—_4_( 14
hearby certify that I have read and examined this permit and know the same to be true and correct. All
provisions of law and ordinances governing this work will be complied with, whether specified herein or not.
The granting of this permit does not presume to give authority to violate or cancel the provisions of any other
state or local laws regulating construction or the performance of work. I am authorized to sign and obtain this
development permit an agree to the conditions attached to this permit. (�
Signature: j Date: q)1.14 1
1
Print Name: L l*`l'CCU PM 1 �1/\
This permit shall become null and void if the work is not commenced within 180 days for the date of issuance, or
if the work is suspended or abandoned for a period of 180 days from the last inspection.
PERMIT CONDITIONS:
1: Work shall be installed in accordance with the approved construction documents, and any changes made
during construction that are not in accordance with the approved construction documents shall be
resubmitted for approval.
2: All permits, inspection record card and approved construction documents shall be kept at the site of work
and shall be open to inspection by the Building Inspector until final inspection approval is granted.
3: Readily accessible access to roof mounted equipment is required.
4: All construction shall be done in conformance with the Washington State Building Code and the
Washington State Energy Code.
5: Remove all demolition rubble and loose miscellaneous material from lot or parcel of ground, properly cap
the sanitary sewer connections, and properly fill or otherwise protect all basements, cellars, septic tanks,
wells, and other excavations. Final inspection approval will be determined by the building inspector
based on satisfactory completion of this requirement.
6: All plumbing and gas piping work shall be inspected and approved under a separate permit issued by the
City of Tukwila Building Department (206-431-3670).
7: All electrical work shall be inspected and approved under a separate permit issued by the City of Tukwila
Permit Center.
8: VALIDITY OF PERMIT: The issuance or granting of a permit shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the building code or of any other ordinances of the
City of Tukwila. Permits presuming to give authority to violate or cancel the provisions of the code or
other ordinances of the City of Tukwila shall not be valid. The issuance of a permit based on construction
documents and other data shall not prevent the Building Official from requiring the correction of errors in
the construction documents and other data.
9: ***MECHANICAL PERMIT CONDITIONS***
10: All mechanical work shall be inspected and approved under
Tukwila Permit Center (206/431-3670).
11: Manufacturers installation instructions shall be available on
PERMIT INSPECTIONS REQUIRED
Permit Inspection Line: (206) 438-9350
1800
0705
0701
MECHANICAL FINAL
REFRIGERATION EQUIP
ROUGH -IN MECHANICAL
a separate permit issued by the City of
the job site at the time of inspection.
CITY OF TUKWI
Community Development Department
Permit Center
6300 Southcenter Blvd., Suite 100
Tukwila, WA 98188
http://www.TukwilaWA.gov
Mechanical Permit No. f-4 173
Project No. n
Date Application Accepted: R` -[L
Date Application Expires: S'14—[
(For office use only)
MECHANICAL PERMIT APPLICATION
Applications and plans must be complete in order to be accepted for plan review.
Applications will not be accepted through the mail or by fax.
**please print**
SITE LOCATION
King Co Assessor's Tax No.: 8700200020
Site Address: 4445 S 134th P1 Tukwila, WA 98168 Suite Number: Floor:
Tenant Name:
Fostoria Park Association
PROPERTY OWNER
Name: ESM Properties
Address: 15100 SE 38th St
City: Bellevue State: WA
Zip: 98006
CONTACT PERSON — person receiving all project
communication
Name: Laura Smith
Address: 1221 2nd Ave N
City: Kent State: WA Zip: 98032
Phone: (206) 920-1690 Fax:
Email: LSmith@hermanson.com
New Tenant: ❑ Yes J ..No
MECHANICAL CONTRACTOR INFORMATION
Company Name: Hermanson
Address: 1221 2nd Ave N
City: Kent State: WA Zip: 98032
Phone: (206) 920-1690 Fax:
Contr Reg No.: HERMACLOO5BJ Exp Date: 08/25/2016
Tukwila Business License No.: 09-459
Valuation of project (contractor's bid price): $ 7,560
Describe the scope of work in detail:
Replacement of (1) existing RTU, like for like.
Use: Residential: New ❑ Replacement ❑
Commercial: New r Replacement
Fuel Type: Electric ❑
Gas 1
Other:
H:\Applications\Forms-Applications On Line\2011 Applications\Mechanical Permit Application Revised 8-9-1 I.docx
Revised: August 2011
bh
Page 1 of 2
Indicate type of mechanical work being installed and the quantity below:
Unit Type
Qty
Furnace <100k btu
Furnace > l 00k btu
Floor furnace
Suspended/wall/floor
mounted heater
Appliance vent
Repair or addition to
heat/refrig/cooling
system
Air handling unit
<10,000 cfm
1
Unit Type
Qty
Air handling unit
>10,000 cfm
Evaporator cooler
Ventilation fan
connected to single duct
Ventilation system
Hood and duct
Incinerator — domestic
Incinerator —
comm/industrial
Unit Type
Qty
Fire damper
Diffuser
Thermostat
Wood/gas stove
Emergency generator
Other mechanical
equipment
Boiler/Compressor
Qty
0-3 hp/100,000 btu
3-15 hp/500,000 btu
15-30 hp/1,000,000 btu
30-50 hp/1,750,000 btu
50+ hp/1,750,000 btu
PERMIT APPLICATION NOTES -
Value of construction — in all cases, a value of construction amount should be entered by the applicant. This figure will be reviewed and is subject
to possible revision by the permit center to comply with current fee schedules.
Expiration of plan review — applications for which no permit is issued within 180 days following the date of application shall expire by limitation.
The building official may grant one extension of time for additional periods not to exceed 90 days each. The extension shall be requested in writing
and justifiable cause demonstrated. Section 105.3.2 International Building Code (current edition).
I HEREBY CERTIFY THAT I HAVE READ AND EXAMINED THIS APPLICATION AND KNOW THE SAME TO BE TRUE UNDER
PENALTY OF PERJURY BY THE LAWS OF THE STATE OF WASHINGTON, AND I AM AUTHORIZED TO APPLY FOR THIS PERMIT.
BUILDING OWNER 0 ..0 HO' _ ED. GENT:
Signature:
Date: 09/03/2014
Print Name: Laura Smith Day Telephone: (206) 920-1690
Mailing Address: 1221 2nd Ave N
Kent WA 98032
City State Zip
H:\Applications\Forms-Applications On Line\201 I Applications\Mechanical Permit Application Revised 8-9-1 I.docx
Revised: August 2011
bh
Page 2 of 2
DESCRIPTIONS
PermitTRAK
Cash Register Receipt
City of Tukwila
ACCOUNT
QUANTITY PAID
$366.41
EL14-0855 Address: 4445 S 134TH PL BLDG D Apn: 8700200020
$68.25
ELECTRICAL
$65.00
PERMIT FEE MULTI-FAM/COMM
R000.322.101.00.00
0.00
$65.00
TECHNOLOGY FEE
$3.25
TECHNOLOGY FEE
R000.322.900.04.00
0.00
$3.25
M14-0173 Address: 4445 S 134TH PL BLDG D
Apn: 8700200020!
29816'
MECHANICAL
$286.69
PERMIT ISSUANCE BASE FEE
R000.322.100.00.00
0.00
$32.50
PERMIT FEE
R000.322.100.00.00
0.00
$196.85
PLAN CHECK FEE
R000.322.102.00.00
0.00
$57.34
TECHNOLOGY FEE
$11.47
TECHNOLOGY FEE
TOTAL FEES PAID BY RECEIPT: R3000
R000.322.900.04.00
0.00
$11.47
$366.41
Date Paid: Thursday, September 04, 2014
Paid By: LAURA SMITH HERMANSON COMPANY
Pay Method: CREDIT CARD 263672
Printed: Thursday, September 04, 2014 8:46 AM 1 of 1
CAIIIWYSTEMS
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION C-}f(
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451 q 1
1'114-003
Project:,, r
r )S I v f , .� ,Pj�.,it� 11--WOC,
Type of I spection:
dvi e c x� .
.
,`U A L..-
Address: Ili
C. /.3lest,
Date Called:
fI fvf,
1
3 G E --
Special Instructions:
//`-- \\
E )
/
Date Wanted:
! n _ 24
/ a.m
� � 4, p.m:.
Requester:
Phone;06 No
7 5 5
7 3 t si
Approved per applicable codes. Corrections required prior to approval.
COMMENTS:
t
t
`
-
jj
1
i�
f/
/,/
%
Inspector:
Date: j /, ./ 4
"7
� r
REINSPECTION FEE REQUIRED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule'reinspection.
INSPECTION RECORD
Retain a copy with permit
INSPECTION NO. PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
�yl ICI of?3
Project-.- 5\ !Ai A sPA�
Type ofr pe of: 1
Apes 4 .s
1,3 Litiii
Date Called:
Special Instructions:
Date Wanted: a.m.
Requester:
7— 0 IQ t--.(
Phone No: ,_. (}
�ss Z3�Li
Approved per applicable codes. El Corrections required prior to approval.
COMMENTS:
4 f t' J
%16ti`--1
AcF( c:/ 6.1/
ti.'-e
l� t ; ��_
-R ',
V i'L.) 1 r
ettor: Date:
;LAVAQ-r1 (.act. ! c Jt��t t► l i� —�j'" C
IREINSPECTION FEE REARED. Prior to next inspection, fee must be
paid at 6300 Southcenter Blvd., Suite 100. Call to schedule reinspection.
INSPECTION NO.
INSPECTION RECORD
Retain a copy with permit
Mf4-6/73
PERMIT NO.
CITY OF TUKWILA BUILDING DIVISION
6300 Southcenter Blvd., #100, Tukwila. WA 98188 (206) 431-3670
Permit Inspection Request Line (206) 431-2451
7ject� r
Type of Inspection:
u
Address: _
�
7-1
Date Called:
Special Instructions
13
S (/U/i
/\.
``
-
Date Wanted: 1
2.
_ '4--p
Requester:
Phone No:
Approved per applicable codes.
Corrections required prior to approval.
COMMENTS:
f,E n 1 '\ r1 )
, `-i N t1 A
') r
6 LA , MA
,
:(vrA
cne.c_IZ
C
t
A\ ',lVsr-
,,1, w)Q,.d Z.VI,.;, (-,i,
A:11'A (LD) II I11--?) ,•',-, t r f r.\ (� n A
, 41r
ttN.n
I).11
n
APn,,
),)
t'�0
n/ / r1
S /�
i
n
l
,4
Inspector:
Date:1 1-9 r / 4
REINSPECTION FEE REQUIRED. Prior to next inspection. fee must be
paid at 6300 Southcenter Blvd.. Suite 100. Call to schedule reinspection.
No changes shall beREVISIONS made to the scope
of wort without out prior
—, P or approval of
''!` iiia Building Division.
`` OTy: € _ , wiil require a new plan
cnJ may it;c ede additional plan review feesa of
.
FILE COPY
Permit No. M ('30(73
Plan review approval is subject to errors and omissions.
Approval of con,:truot ion documents does not authorize
t' .3 violation of any adopted code or ordinance. Receipt
of ppps o tt. d Fuld Copy d conditions is acknowledged:
By:
Date:
City of Tukwila
BUILDING DIVISION
M 1 14. 0 173
SEPARATE PERMIT
REQUIRED FOR:
0 Mechanical
&Electrical
&Plumbing
C�Gas Piping
City of Tukwila
F(,:'L 'NG DIVISION
REVIEWED FOR
CODE COMPLIANCE
APPROVED
SEP 12 2014
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
SEP. 0 4 2014
PERMIT CENTER
A
AC
ACH
ACT
AD
ADD'L
MECHANICAL ABBREVIATIONS
AMPS
AIR CONDITIONING
AIR CHANGES PER HOUR
ACOUSTICAI CFR!NG TILE
ACCESS DOOR
ADDI IIONAL
AFF ABOVE FINISHED FLOOR
AFG ABOVE FNISHED GRADE
AHU AIR HANDLING UNIT
ALUM ALUMINUM
AMP/AMPS AMPERAGE
AP ACCESS PANEL
ARCH
BC
BDD
BF
BHP
BLDG
BOD
BOP
BOT
BS
BTU
BTUH
CAP
CC
CD
CDWR
COWS
CFM
CHWR
CHWS
CLG
COL
CONC
COND
CONN
CONE
CONTR
COORD
COP
CT
CU
CW
DB
DDC
DEL
DEG
DIA
DMPR
DN
DWG
EXH
EA
EAT
EC
EER
EF
EFF
ARCHITECT
BEADED COLLAR
3ACKDRAFT DAMPER
BELOW FLOOR
BRAKE HORSEPOWER
BUILDING
BOTTOM OF DUCT
BOTTOM OF PIPE
BOTTOM
BIRD SCREEN / BLACK STEEL
BRITISH THERMAL UNIT
BRITISH THERMAL UNITS PER HOUR
CAPACITY
CONTROLS CONTRACTOR
CEILING DIFFUSER/CONDENSATE DRAIN
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CUBIC FEET PER MINUTE
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CEILING
COLUMN
CONCRETE
CONDENSATE
CONNECT/CONNECTED/CONNECTION
CONTI N UO JS/CONTINUATION
CONTRACTOR
COORDINATE
COEFFICIENT OF PERFORMANCE
COOLING TOWER
CUBIC/CONDENSER UNIT
DOMESTIC COLD WATER/CONDENSER WATER
DUCTBOARD/DRY BULB/DECIBEL
DIRECT D.GITAL CONTROL
DEFLECTOR
DEGREE/DEGREES
DIAMETER
DAMPER
DOWN
DRAWING
EXHAUST
EACH
ENTERING AIR TEMPERATURE
EGGCRATE GRILLE/END CAP/ELEC CONTRACTOR
ENERGY EFFICIENT RATING
EXHAUST FAN
EFFICIENCY
EL ELEVATION
ELEC/ELECT ELECTRICAL/ELECTRIC
EMCS ENERGY MANAGEMENT CONTROL SYSTEM
ENT
EQUIP
ESP
EWT
EXIST
EXH
FAC
FD
FDC
FF
FIC
FIO
FLA
FLEX
FLR
F03
FO C
FOS
FOT
FP
FPM
FSD
FT
FUT
FV
GA
GA_V
GC
GPM
GRD
GWB
HD
HORIZ
HP
HR
HSPF
HT
HWTG
HWR
HWS
HX
HZ
IBC
ICw
ID
ENTERING
EQUIPMENT
EXTERNAL STATIC PRESSURE
ENTERING WATER TEMPERATURE
EXISTING
EXHAUST
FAHRENHEIT
FIRE ALARM CONTRACTOR
IRE DAMPER
FIRE DEPARTMENT CONNECTION
FINISHED FLOOR
FURNISHED AND INSTALLED BY CONTRACTOR
FURNISHED AND INSTALLED BY OWNER
FULL LOAD AMPS
FLEXIBLE
FLOOR
FLAT ON BOTTOM
FURNISHED BY OTHERS,
NSTALLED 3Y CONTRACTOR
FLAT ON SIDE
FLAT ON TOP
FIRE PROTECTION
FEET PER MINUTE
FIRE/SMOKE DAMPER
FOOT/FEET
FUTURE
FACE VELOCITY
GRILLE
GAUGE/GALLON
GALVANIZED
GENERAL CONTRACTOR
GALLONS PER MINUTE
GRILLE/REGISTER/DIFFUSER
GYPSUM WALL BOARD
HEAD
HORIZONTAL
HORSEPOWER
HOUR
HEATING SEASONAL PERFORMANCE FACTOR
• EIGHT
GH WALL TRANSFER GRILLE
OT WATER RETURN
OT WATER SUPPLY
EAT EXCHANGER
ERTZ
TERNATIONAL BUILDING CODE
DUSTRIA_ COLD WATER
SIDE DIAMETER/DIMENSION
EER
MC
N WG
PLV
KW
LAT
LB/LBS
LF/LIN FT
LPG
LPS
LVG
LWA
LWG
LWT
MAX
MAU
MBH
MCA
MD
MFR
MISC
MIN
MPS
MT
MTD
MUW
NA
NC
NG/NGAS
NIC
NO
NPW
N-R
OA/OSA
OBD
OD
PCF
PD
PH
POC
P/PRESS
PSI
PSIG
QTY
RA
RD/HND
REF
REQ
RESID
RF
RG
RL
RPM
RS
SA
SAT
SD
S/D
S_C
SEER
SENS
SL
SM
SPEC
SO
SOG
SP
SF
SS
STRUC
TA
TEMP
TBD
TOD
TOS
TOT
TSP
TSTAT
TYP
UH
UNO
V
VD
VEL
VERT
VED
VOL
W
W3
WG
W/
W/0
W/SF
WSEC
NVERT ELEVATION
NTEGRATED ENERGY EFFICIENCY RATIO
NTERNATIONAL MECHANICAL CODE
NCHFS
NCHES WATER GAUGE
NTEGRATED PART LOAD VALUE
KILOWATTS
LEAVING AIR TEMPERATURE
POUND/POUNDS
LINEAL FOOT/FEET
LIQUID PROPANE GAS
LOW PRESSURE STEAM
LEAVING
SOUND POWER RATING LEVEL (IN DB)
LOW WALL GRIT I E
LEAVING WATER TEMPERATURE
MAXIMUM
MAKE UP AIR UNIT
1000 BRIT'SH THERMAL UNITS/HOUR
MINIMUM CIRCUIT AAPACITY
MOTORIZED DAMPER
MANUFACTURER
MISCELLANEOUS
MINIMUM/MINUTE
MEDIUM PRESSURE STEAM
MOUNT
MOUNTED
MAKE-UP WATER
NOT APPLICABLE
NORMALLY CLOSED/NOISE CRITERIA
NATURAL GAS
NOT IN CONTRACT
NORMALLY OPEN/NUMBER
NON -POTABLE WATER
NON-RESIDENTIAL
OUTSIDE AIR
OPPOSED BLADE DAMPER
OUTSIDE DIAMETER/DIMENSION
POUNDS PER CUBIC FOOT
PRESSURE DROP
PHASE
POINT OF CONNECTION
PRESSURE
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH GAUGE
QUANITY
RETURN GRILLE/RELOCATED/RETURN
RETURN AIR
ROUND
REFERENCE
REQUIRED
RESIDENTIAL
RELIEF
REFRIGERANT DISCHARGE GAS
REFRIGERANT LIQUID
REVOLUTIONS PER MINUTE
REFRIGERANT SUCTION
SUPPLY
SUPPLY AIR
SATURATION/SUPPLY AIR TEMPERATURE
SMOKE DETECTOR
SLIP & DRIVE CONNECTION
SEATTLE __ CODE
SEASONAL ENERGY EFFICIENCY RATING
SENSIBLE
SOUND LINED
SHEETMETAL
SPECIFICATION
SCREENED OPENING
SLAB ON GRADE
STATIC PRESSURE
SQUARE FEET
STAINLESS STEEL
STRUCTURAL
TRANSFER AIR
TEMPERATURE/TEMPORARY
TO BE DETERMINED
TOP OF D'JCT
TOP OF STEEL/TOP OF SLAB
TOTAL
TOTAL STATIC PRESSURE
THERMOSTAT
TYPICAL
UNIT HEATER
UNLESS NOTED OTHERWISE
VOLT
VOLUME DAMPER
VELOCITY
VERTICAL
VARIABLE FREQUENCY DRIVE
VOLUME
WRAPPED DUCT
WET BULB
WATER GAUGE
WITH
WITHOUT
WATTS PER SQUARE FOOT
WASHINGTON STATE ENERGY CODE
MECHANICAL LEGEND
t10X10
1 X10 Ezi
fi0X10; I
10X10
floxiofri
0X LJ
t 1ox10 'I
10X10
RECT SUPPLY AR DUCT
UP/TOWARD
RECT SUPPLY AIR DUCT
DN/AWAY
RECT EXHAUST OR RETURN DUCT
CP/TOWARD
RECT EXHAUST OR RETURN DUCT
DN/AWAY
6 to. 0
100 0 ROUND DUCT - UP/TOWARD
b IN )
100 0
scan
S12X1001
ROUND DUCT - DN/ AWAY
FLATOVAL DUCT - UP/ TOWARD
FLATOVAL DUCT - DN/ AWAY
100 .-,t DUCT OVERLAP
100 T
16X16SL
BOOT TAP
45' TAP
VOLUME DAMPER
RISE(R) & DROP(D)
TRANSITION
TURNING VANES/SPLITTERS
DUCT MOUNTED SMOKE DETECTOR
SACK DRAFT DAMPER
FLEXIBLE DUCT
AIR FLOW (FORCED AIR)
COMBINATION FSD
FIRE DAMPER
SMOKE DAMPER
MOTOR OPERATED DAMPER
ACCESS DOORS
SOUND TRAP
FLEX CONNECTION
ACOUSTICALLY UNED DUCT (SL)
FABRIC DUCT
CLEARANCE
SUPPLY AIR DIFFUSER
(WITH CORE Bl+NKCFF)
CEILING RETURN, TRANSFER OR
EXHAUST AIR CRLLE
SLOTTED DIFFUSER (PLAN VIEW)
CD0 REVISION CLOUD & TRIANGLE
n0 ROUND DUCT SYMBOL
0 FLATOVAL DUCT SYMBOL
H. DEGREES SYMBOL
B POINT OF CONNECTION
CD1-100 GRD TAG IDENTIFIER =TYPE-CFM
80 SIZE
8 TSTA-/TEMP SENSOR ®D CARBON DIOXIDE
HUMIDITY SENSOR SENSOR
®° SMOKE DETECTOR ()CARBON MONOXIDE
0 STATIC PRESSURE SENSOR SENSOR
1- mED 2
t oV 2
1-CHWS /CHWR-S
RL/RS-
1- NG-6
2-- LPG -5
2-CDWS /CDWR-5
2-HWS/HWR-S
t- COND -5
2- FOV -5
2- FOS /FOR -s
2- RDG -5
EXISTING DUCTWORK
DEMO DUCTWORK
WALL -MOUNTED GRILLE
PIPE ELBOW UP
PIPE ELBOW DN
DIRECTION OF FLOW
DIRECTION OF SLOPE DOWN
PLUG CR CAP
PRESS REDUCING ASSEMBLY
SOLENOID VALVE
PUMP
CHILLED WATER SUPPLY/RETURN
REFRIGERANT LIQUID/SUCTION
NATURAL GAS
LIQUID PROPANE GAS
CONDENSER WATER SUPPLY/RETURN
HEATING WATER SUPPLY/RETURN
CONDENSATE
FUEL OIL VENT
FUEL OIL SUPPLY/RETURN
REFRIGERANT DISCHARGE GAS
MECHANICAL GENERAL NOTES
1. WORK SHALL CONFORM TO APPLICABLE CODES AND REGULATIONS, INCLJDING, BUT NOT LIM TED TO THE 2012 IBC, 2012 WSEC, & 2012 IMC.
2. DIMENSIONS ARE TO FACE OF STUD, CONCRETE, OR MASONRY JNLESS NOTED OTHERWISE.
3. DO NOT SCALE DRAWINGS. DIMENSIONS GOVERN.
4. VERIFY EXISTING CONDITIONS, DIMENSIONS, DETAILS, ETC. NOTIFY ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK.
5. WHEN CONSTRUCTION DETAILS ARE NOT SHOWN OR NOTED FOR ANY PART OF THE WORK, DETAILS SHALL BE THE SAME
AS FOR OTHER SIMILAR WORK. IF ADDITIONAL QUESTIONS REMAIN, CONTACT THE ENGINEER PRIOR TO PROCEEDING.
6. ALL STRUCTURAL OPENINGS AND PLATFORMS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR UNLESS NOTED OTHERWISE.
7. DUCT SEALING AND CONSTRUCTION TO MEET SMACNA AND ENERGY CODE REQUIREMENTS. UNLESS OTHERWISE NOTED, LOW PRESSURE DLCTWORK
(DOWNSTREAM OF VAV BOXES, CONSTANT VOLUME AC SYSTEMS, TOILET EXHAUSTS, ETC.) TO MEET 2 CONSTRUCTION STANDARDS WITH
SEAL CLASS C. MEDIUM PRESSURE DUCTWORK (UPSTREAM OF VAV BOXES, HIGH VELOCITY XHAJSTS, ETC.) TO MEET 4" CONSTRUCTION STANDARDS
WITH SEA_ CLASS A. DUCT RISERS IN SHAFTS WITH DAMPERED PENETRATIONS TO MEET 6" CONSTRUCTION STANDARDS WITH SEAL CLASS A.
8. ALL CEILING DIFFUSERS ARE 4-WAY THROW UNLESS NOTED OTHERWISE.
9. ALL DUCT DIMENSIONS ARE CLEAR INSIDE DIMENSIONS AFTER LINING HAS BEEN ACCOUNTED TOR.
10. OUTSIDE AIR INTAKES ON ALL AIR HANDLING UNITS SHALL BE 10 FEET AWAY FROM ANY FUEL BURNING EQUIPMENT OR 3 FEET BELOW
ANY PLACING VENT OR EXHAUST OUTLET WITHIN 10 FEET
11. ALL AIR ECONOMIZERS SHALL BE CAPABLE OF THE FOLLOWING:
- 0% TO 100% OF THE DESIGN SUPPLY AIR
- CONTROLLED BY A CONTROL SYSTEM DETERMINING IF THE OJTSIDE AIR CAN MEET PART OR ALL OF THE BUILDING COOUNG LOADS.
- INTEGRATED TO PROVIDE PARTIAL COOLING EVEN WHEN MECHANICAL COOLING IS REQUIRED.
12. OUTSIDE AIR INTAKE, RELIEF, AND EXHAUST OPENINGS SHALL BE EQUIPPED WITH MOTOR:ZED (OR GRAVITY DAMPERS PER
EXCEPTIONS IN C403.2.4.4) WHICH CLOSE AUTOMATICALLY WHEN SYSTEM IS OFF OR UPON POWER FAILURE.
13. THE CONTROL SYSTEM SHALL BE 7-DAY PROGRAMMABLE, CAPABLE OF BEING SET FOR SEVEN (7) DIFFERENT DAY TYPES PER WEEK,
AND CAPABLE OF A DEADBAND SETTING OF AT LEAST 5'F 10'F FOR RESIDENTIAL),BETWEEN THE HEATING AND COOING SETPOINTS. AHU CONTROL
SYSTEM SHALL INCLUDE A MICROPROCESSOR AND BE CAPABLE OF RESETTING SUPPLY AIR TEMPERATURES BY REPRESENTATIVE BUILDING LOADS.
14. RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS OF THE DATE
OF SYSTEM ACCEPTANCE PER THE WASHINGTON STATE ENERGY CODE. AN OPERATING MANUA_ AND MAINTENANCE MANUAL
SHALL BE PROVIDED TO THE BUILDING OWNER. ALL HVAC SYSTEMS SHALL BE BALANCED AND A WRTTEN BALANCING REPORT
SHALL BE PROVIDED TO THE OWNER. HVAC CONTROL SYSTEMS SHALL BE TESTED TO ENSURE THAT THEY OPERATE IN ACCORDANCE
WITH APPROVED PLANS. A PRELIMINARY COMMISSIONING REPORT OF TEST PROCEDURES AND RESULTS SHALL
BE PREPARED PRIOR TO ISSUANCE OF A FINAL CERTIFICATE OF OCCUPANCY. A COMPLETE F NAL COMMISSIONING REPORT OF
TEST PROCEDURES AND RESULTS SHALL BE PROVIDED TO THE OWNER. COMMISSIONING, SYSTEM BALANCING, RECORD DRAWINGS
AS REQUIRED PER THE WASHINGTON STATE ENERGY CODE C408.
15. SAFETYNIORLHAZARDOUS MATERIAL RELATED SYSTEMS RESTRAINT
LNBE REQUIREMENTS
IpOF =11.5TFOR BUILDING SMACNA
OR AS NO EED 7. ALL
REFER TO CODES FOR INSTALLATION REQUIREMENTS AND EXCEPTIONS BASED ON SIZING, WEIGHTS AND MOUNTING HEIGHTS.
16. PROVIDE EARTHQUAKE RESTRAINTS FOR HVAC EQUIPMENT AS REQUIRED BY SMACNA SEISMIC RESTRAINT MANUAL, SEISMIC HAZARD B.
WIRES FOR CEILING SYSTEM ETC. SHALL NOT BE HUNG OFF HVAC EQUIPMENT OR HVAC EQUIPMENT SUPPORTS.
17. PROVIDE FIRE AND COMBINATION FIRE/SMOKE DAMPERS WHERE SHOWN ON PLANS AND WHERE REQUIRED PER CODE.
DRAWING INDEX
SHOOT NO.
SHEET TIRE
CURREM
REVISION
N0.00
LFCEND ABBREVIATIONS GFNFRAI. NOTES & SHOT INDEX - MAC
1/2.R1
PARTIAL ROOF PUNS & SCHEDULE - HVAC
APN NUMBER
8700200020
LEGAL DESCRIPTION
TUKWILA BSIP NO L08-061 REC #2C090731000740
18. ALL PIP'NG PENETRATIONS THROUGH RATED ASSEMBLIES SHALL BE SEALED WITH AN UL APPROVED FIRE CAULKING.
19. SMOKE DETECTORS PROVIDING AUTOMATIC SHUTDOWN SHALL BE PROVIDED FOR HVAC EQUIPMENT DELIVERING IN EXCESS OF 5133rd3 s
2000 CFM [INCLUDING MULTIPLE UNITS DJCTED INTO COMMON DISTRIBUTION OR RETURN, WITH AN AGGREGATE SUPPLY E
THAN 2000 CEPA] OR OF RETURN SYSTEMOVERPE
SMOKE DETECTORS SHALLHBETFIFICY(ELEC) LINO. POWER -WI WIRING 1ANDCINTERLOCK TOCFM IN AUFIRESALARM NMTISYST BY ELECTRIICCAL CONTRART EP1/`tIE
20. MECHANICAL ACCESS PANELS SHALL BE PROVIDED BY MECHANICAL CONTRACTOR AND INSTALLED BY GENERAL CONTRACTOR. (FLOE COIII�PLIAj•CE
21. ALL MOTOR STARTERS NOT SHOWN IN EQUIPMENT SCHEDULES SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL COlO .
MOTOR EFFICIENCIES TO MEET OR EXCEED CODE MINIMUM.
22. FOR ALL "SEALED AIR TIGHT" SHAFTS OR ROOMS, THE FOLLOWING SHALL OCCUR:
- ALL VERTICAL JOINTS & CORNERS INSIDE THE SHAFT SHALL BE PROVIDED WITH A CONTINUOUS SEAL FOR THE LENGTH F THE JOINT, (BY GC).
-TOP AND BOTTOM WALL TRACKS SHOULD BE CAULKED ALONG THEIR ENTIRE LENGTH (BY GC). ^�°-n(
- ANY FLOCK DECKING PERPENDICULAR TO THE SHAFT SHALL BE CAULKED (BY GC). FILLING WITH ROCK WOOL IS NOT ACEPTABLE SEP �
U
-ANY PENETRATIONS OF THE SHAFT CONSTRUCTION DUCTWORK, CONDUIT, PIPING, ... SHALL BE SEALED ON BOTH SIDES
- USE SECTION 909.5 OF THE 2012 IBC FOR MAX ALLOWABLE LEAKAGE AREA, FOLLOWING THE GUIDELINES FOR TIGHT STFS SHAFT CONSTRUCTION.
- ALL DOORS SHALL BE PROVIDED WITH TIGHT FITTING CASKETS, AND OPEN AGAINST THE DIRECTION OF ROOM/SHAFT PRE SURE.
23. MAXIMUM LENGTH OF FLEXIBLE DUCT SHALL BE 12 FEET. REFER TO INSTALLATION DETAILS FOR SUPPORT REQUIREMENT.
FLEXIBLE DUCT FLAME SPREAD RATING SHALL BE < 25 AND SMOKE DEVELOPED RATING SHALL BE < 50. USE FLEXIDUC City/ of Tukwila
MODEL G-KM FOR LOW AND MEDIUM PRESSURE APPLICATIONS OR APPROVED EQUAL.
24. LOCATION AND DETAILS OF EQUIPMENT DUCT ROUTING AND CONNECTIONS ARE APPROXIMATE. COORDINATE FINAL LOCATT
OTHER -RADES. INSTALL IN ACCORDANCE WITH APPROVED SUBMITTALS AND DETAIL DRAWINGS WHEN APPLICABLE.
D FOR
25. FOR RESIDENTIAL INSULATION ON DUCTWORK AND PIPING SEE ENERGY CODE CHAPTER R403.
APPROVED
5BtJILDING
26. ELECTRICAL METERING OF SYSTEMS AS REQLIRED BY ENERGY CODE SECTION C409 IS BY ELECTRICAL THE ELECTRICAL DESIGN & CONTRACTOR TEAM
WILL FURNISH THE NECESSARY ELECTRICAL DISTRIBUTION AND METERING COMPONENTS - SEE ELECTRICAL DRAWINGS. "HE MECHANICAL CONTRACTOR
WILL FURNISH A BUILDING MANAGEMENT SYSTEM CAPABLE OF COLLECTING AND STORING THE INFORMATION. A PERMANENT AND VISIBLE DISPLAY IS
TO BE PROVIDED FOR EACH BUILDING, READILY ACCESSIBLE TO OPERATION AND MANAGEMENT PERSONNEL
MINIMUM DUCT INSULATION
LAST UPDATED 01/10/14
INSULATION
DUCT' TYPE DUCT LOCATION IN HEATED AND MECHANICALLY COOLED DUCT STSIbM R-VAUJE , REMARKS
SUPPLY & RETURN NOT WITHIN CONDITIONED SPACE, INSIDE BUILDING R-8 1,2,3
OUTSIDE AIR WITHIN CONDITIONED SPACE, INSIDE BUILDING SEE NOTES 4 & 5 1,2,3,4,5
SUPPLY & RETURN NOT WITHIN CONDITIONED SPACE: INSIDE BUILDING R-6
SUPPLY AIR
<55° OR >105° WITHIN CONDITONED SPACE R-3.3
1 REFER TO ENERGY CODE SECTION C4D3.2.7 FOR FURTHER REQUIREMENTS
2 INSULATED COOLED DUCTS REQUIRED A VAPOR RETARDER (PERM < 0.5) AND SEALED JOINTS
3 WEATHERPROOF BARRIER REQUIRED AROUND DUCTWORK TO MAINTAIN WATER TIGHTNESS
4 INSULATE OUTSIDE AIR DUCTS TO BUILDING EXTERIOR WALL LEVEL PER ENERGY CODE SECTION( C403.2.7.1 UNTIL
CONNECTED TO EQUIPMENT SERVED OR TO THE CODE REQUIRED SHUTOFF DAMPER (THEN R-6 FOR REST OF
INSTALLATION) OR HEATING & COOLING EQUIPMENT
5 R-7 CAN BE USED IN LIEU OF BUILDING ENVELOPE INSULATION LEVEL IF:
DEDICATED OUTSIDE AIR SYSTEM AND LESS THAN 2,800 CFM SUPPLY AIR
1,2
1,2
MINIMUM PIPE INSULATION LAST UPDATED: 01/10/14
FWTD DESIGN INSULATION CONDUCTIVITY NOMINAL PIPE DIAMETER (INCH)
OPERATING . CONDUCTIVITY MEAN TEMP 1 TO 1-1/2 TO 4 TO
TEMP °F RANGE RATING °F <1 I <1-1/2 <4 <8 >8
HEATING SYSTEMS (STEAM, CONDENSATE, HYDRONIC HOT WATER, DOMESTIC HOT WATER)
>350 0.32-0.34 250
251-350 0.29-0.32 200
201-250 0.27-0.30 150
141-200 0.25-0.29 125
105-140 0.21-0.28 100
,DOMESTIC COLD WATER AND HORIZONTAL RAIN LEADERS TO FIRST VERTICAL RAIN LEADER
4446 S 134th PI. Tukwaa. WA
9816E
Pim.. Saw Zuun Surd
/ICINITY MAP
NO SCALE
AREA OF WORK
RECEIVED SITE MAP
4.5 5.0 5.0 5.0 5.0 CITY OF TUKWILA
3.0 4.0 4.5 4.5 4.5
2.5 2.5 1.5 3.0 . 3.0 al SEP 2014
1.5 1.5 2.0 2.0 2.0
1.0 1.D 1.5 1.5 1.5
NO SCALE
cgk
40-60 0.21-0.27W 75 0.5 0.5 1.0 1.0 1-D ;ERM T CENTER
ISSUE FOR PERMIT
COOLING SYSTEMS (CHILLED0WATER, BRINE AND REFRIGERANTO, WATERSIDE ECONOOMIZER SYSTEMS).* T 1.0 1.0 �+I •.. I ■
<40 I 0.20-0.26 : 75 1- 0.5
0.5 1.0 1.0 L 1.0 1.5
NOT REQUIRED FOR STRAINERS, CONTROL VALVES & BALANCING VALVES ASSOCIATED WITH PIPING 1" OR LESS IN DI0.
v° TYPICAL CONDENSER WATER PIPE IN NON -ECONOMIZER SYSTEMS DOES NOT REQUIRE INSULATION
3,)
Hermanson
Hennueon Company UP
1221 2na Avenue North
Kern. 9084 gtoo 96032
Tel: (206) 575-9700
Fax: (206) 575-9800
www.hennanson.com
Contmetor Reg f; HERWCID0513I
FOSTORIA PARK
ASSOCIATES LLC
4445 SOUTH 134TH PL.
TUKWILA, WA 98168
Revisions
09/04/14 MIG ISSUE FOR PERMIT
No. Dote By Description
Design Team
Design MIG
Drawn FVP
Checked OTN
Scale AS NOTED
Drawing Number C-0475-04869
Project Number 14-14-04869
Issue Date 09/04/14
LEGEND, ABBREVIATIONS,
GENERAL NOTES & SHEET
INDEX - HVAC
M0.00
AREA OF WORK
t
DEMO EXIST UNIT
PARTIAL ROOF DEMO PLAN - HVAC
SCALE: " /6. 1' 3'
(� REPLACE EXIST ROOFTOP UNIT W/ NEW UNIT,
1 OF THE SAME CAPACITY RE -CONNECT TO
I EXIST DUCIWORK & UIIUIIES. SEE EQUIPMENT
J SCHEDULE FOE DETAILS ON NEW UNIT
RTU- I I
PARTIAL ROOF PLAN - HVAC
SCALE I/6' - 1'-0'
GAS PACKAGED ROOFTOP UNIT SCHEDULE (DEMO UNIT) LAST UPDATED: 08/27/14
UNIT
TAG
LOCATION
SERVES
BASIS OF
DESIGN
SUPPLY
CFM
ESP
IN
WG
SEERJEER
COOLING CAPACITY
GAS HEATING CAPACITY
SUPPLY FAN
EEC
SOUND '.OPERATING
PER ARI 270/370 WEIGHT
(D6a) (LBS)
UNIT SIZE
(W/O CURB)
HxWxL
REMARKS
TOTAL
MBH
SENS
MBH
INPUT
MBH
OUTPUT AFUE
MBH
NG
CONN
I TYPE
HP
MCA
MAX FUSE
V/PH
RTU-1
ROOF
TRANE YSC036E3EM
1,030
0.80
-
-
-
-
-
1/2
DOWNFLOW
1
22.0
30
208-230/1
- I -
31.5"x32.75"x59"
1
1 EXISTING UNIT TO BE DEMOLISHED.
GAS PACKAGED ROOFTOP UNIT SCHEDULE (REPLACEMENT UNIT) LAST UPDATED: 08/27/14
UNIT
TAG
LOCATION
SERVES
BASIS OF
DESIGN
SUPPLY
CFM
ESP
1N
WG
SEER/ER
COOLING CAPACITY
GAS HEATING CAPACITY
SUPPLY FAN ELEC
SOUND OPERATING
PER ARI 270/370 WEIGHT
(DSO) (LBS)
UNIT SIZE
(W/O CURB)
HxWxL
REMARKS
TOTAL SENS
MBH I MBH
INPUT
MBH
OUTPUT
MBH
AFUE
NG
CONN
TYPE
HP MCA
MAX FUSE
V/PH
RTU-1
ROOF
TRANE YSC036E3EM
1,200
0.80
13/11.2
37,150 36
80
60
80
1/2
DOWNFLOW
1 21.5
30
208/3
81 558
36.25'x44.25"x70"
1,2,3,4,5,6
GENERAL UNIT CAPACITY RATED AT 85/67 OUTSIDE AIR DESIGN TEMPERATURES
1 FOR TRADE COORDINATION REFER TO APPROVED EQUIPMENT SUBMITTALS
2 INSTALL PER MANUFACTURER RECOMMENDATION
3 PROVIDE FULL ECONOMIZER CYCLE.
4 PROVIDE SCCR MINIMUM RATING OF (5 kA) 1N ACCORDANCE WITH NEC 2005 ARTICLE 409 AND NFPA 70 SECTION 409.110
5 REUSE EXISTING ELECTRICAL CONNECTIONS. WIRING CHANGES AND MODIFICATIONS BY ELECTRICAL
6 SEE STRUCTURAL CALCULATIONS FOR MOUNTING DETAILS.
REVIEWED FOR
CODE COMPLIANCE
APPROVED
SEP 12 2014
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
SEP 0 4 2014
PERMIT CENTER
ISSUE FOR PERMIT
•
Hermanson
he -meson Company LL=
1221 2nd Meese North
Kent WasNngtan 99032
Tel: (206) 575-9700
her. (206) 575-9E00
www.nemenson.com
Contractor Reg 0: NERNACL00511J
FOSTORIA PARK
ASSOCIATES LLC
4445 SOUTH 134Th PL.
TUKWILA, WA 98168
Revisions
09/04/14 MIS ISSUE FOR PERMIT
No. Date By Description
Design Team
Design MIG
Drown FVP
Checked DIN
Scale AS NOTED
Drawing Number C-0475-04669
Project Number 14-14-04869
Issue Date 09/04/14
PARTIAL ROOF PLANS
& SCHEDULES
- HVAC
M2.R1
FILE COPY
Permit No.
STRUCTURAL CALCULATIONS
Seattle Bagel Bakery
4445 South 134th Place
Tukwila, WA 98168
PROJECT NO.: 14-400
DATE: August 28, 2014
CODE: IBC 2012 & ASCE/SEI 7-10
D.S. Engineering
Consulting Structural Engineers
3121 147th Place SE
Mill Creek, WA 98012
T: 425-338-4776
E-Mail: dshin@engineer.com
t111 0173
REVIEWED FOR
CODE COMPLIANCE
APPROVED
SEP 12 2014
City of Tukwila
BUILDING DIVISION
RECEIVED
CITY OF TUKWILA
SEP 0 4 2014
PERMIT CENTER
n0—.I -ng�I
NVId 001 77' I l b`.=:!
:J carozld
s
'1O0 8 979 1.X3N Ol
.PJ-,Cn
/ .9-,0Z
/ .9-,Z `�
D to
tr_ Q?
µ
0
•
.A.
0
11
1
:EPLACING UINT W/ CURE
MAX. WT.: 650 Ib.)
8'-0' 8'-0. 8'-0' 8'-0' 8'-0' 8'-0' 8'-0'
v
L‘Cl
(E) 51/ex30 GLB
w
0
es
t
1\1
0
m Iu
0
0
z
'1c3rOld
m3los aoom „s x mlo-rI)
z« '3a 9xp maN
'.lb`9 s13NO-1 i7
powi
. ▪ 1
Itl
■I
.I
Up.
11Ni1 NIO'd-ld3zl
cc D -
z N z '�
D�O
-
.O
0n m„m
rn SOX
A E 3 3 m
��
N 0 0 0
m rn m 0
Z A m
E
r
O
m
D
Design Analysis
(TYP)
GLIB
I (E) 51rex30
GLB
REPLACING
(MAX.
UINT
WT.: 650
LW CURB
(E) 5'70x21
GLB
(E) 51/0x30
GLB
40' 0'
(E) 8' P/C
WALL (TYP)
PROJECT:
Seattle Bagel Bakery
4445 South 134th Place
Tukwila, WA 98168
FART I AL ROOF FRAMING FLAN
SCALE: I/8'= I'-0'
Model Number YSC036E3EMA**C00000000300000000000000000
Customer :
Project :
Name : 'Y4C 1
Unit function
Airflow
Fresh air selection
Cooling Entering DB
Ambient Temp
Voltage
DX Cool
3-10 Ton R410A PKGD Unitary Gas/Electric Rooftop
DX cooling, gas heat
Unit efficiency
Convertible configuration Airflow Application
Econ-dry bulb 0-100% 3hp Tonnage
80.00F Cooling Entering WB
95.00F Heating capacity
208-230/60/3 Major design sequence
ng, Gas, Heat 3-10 Ton
Unit controls
Standard efficiency
Downflow
3 Ton
67.00F
Medium gas heat 3ph
E - R-410A
Electro mechanical controls Refrigeration controls Frostat and crankcase heater
3ph 3ph
EVAPORATOR
SECTION ACCESS PANEL
CONDENSATE DRAIN (ALT)
314"•14 NPT DIA. HOLE
4 1 /4"
THROUGH THE BASE
CONDENSATE
i
42 114"
2312"
OP PANEL
\-
1 /2" NPT GAS CONNECTION
CONDENSER FAN
CONDENSER COIL
NIT CONTROLWIRE 7/8" DIA.HOLE
SERVICE GAUGE PORT ACCESS 1 3/8" DIA. HOLE
NIT POWER WIRE
ONTROL AND COMPRESSOR ACCESS PANEL
NOTES:
1. THRU -THE -BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS.
2. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH
43/16" INSTALLER DOCUMENTS BEFORE INSTALLATION
r
RETURN
24"
1
L_1512" 91/4" 14"
PLAN VIEW UNIT
DIMENSION DRAWING
7
RETURN
SUPPLY
1433/4"
7-`
00
00
3 5/8"
23 1/4"
4 314"
171/4" / 87/8" b-13114"--
CONDENSATE
69 7f3"
3/16"
36
1/4"
20 1/4"
95/8
5 5/8"
4 1/4"
5 9/16"
750"
441/4"
PACKAGED GAS / ELECTRICAL
DIMENSION DRAWING
HORIZONTAL
AIR FLOW
Watt
W.-
PACKAGED GAS / ELECTRICAL
CORNER WEIGHT
INSTALLED ACCESSORIES NET WEIGHT DATA
ACCESSORY
,... - WC1GH S
ECONOMIZER
v 26.01b P
MOTORIZED OUTSIDE AIR DAMPER
'"
MANUAL OUTSIDE AIR DAMPER
BAROMETRIC RELIEF
OVERSIZED MOTOR
BELT DRIVE MOTOR
POWER EXHAUST
THROUGHT THE BASE ELECTRICAL/GAS(FIOPS)
UNIT MOUNTED CIRCUIT BREAKER (FIOPS)
UNIT MOUNTED DISCONNECT (FIOPS)
POWERED CONVENIENCE OUTLET (FIOPS)
HINGED DOORS (FIOPS)
HAIL GUARD
SMOKE DETECTOR, SUPPLY/RETURN
NO'VAR CONTROL
STAINLESS STEEL HEAT EXCHANGER
REHEAT
ROOF CUR
BASIC UNIT WEIGHTS
CORNER WEIGHTS I
CENTER OF GRAVITIY
SHIPPINGere
^
`I��
165.0Ib
()
95.01b I
(E)LENGHT
(F)WIDTH
607.016
532.01b
gr.
137.016
134.01b
31"
19^
NOTE:
1. CORNER WEIGHTS ARE GIVEN FOR INFORMATION ONLY.
2. TO ESTIMATE SHIPPING WEIGHT ADD 5 LBS TO NET WEIGHT.
3. BASIC UNIT WEIGH T DOES NOT INCLUDE ACC ESSORY W EIGHT. T 0 ODT AIN TOTAL
WEIGHT, ADD ACCESSORY NET WEIGHT TO BASIC UNIT WEIGHT.
4. WEIGHTS FOR OPTIONS NOT LIST ED ARE <5 LBS.
PACKAGED GAS /ELECTRICAL
RIGGING AND CENTER OF GRAVITY
J�j
.Wood Beam.
Description : (e) Purlin
CODE REFERENCES
Calculations per
Load Combination Set : IBC 2012
Material Properties
Analysis Method : Allowable Stress Design
Load Combination iBC 2012
Wood Species
Wood Grade
Fb - Tension
Fb - Compr
Fc - Prll
Fc - Perp
Fv
Ft
Beam Bracing : Beam is Fully Braced against lateral -torsion buckling
: Douglas Fir - Larch
: Select structural
D(0.165)
D(0.07) S(0.175)
File = C:IPROGRA-11ENERCA-2
ENERCALC, INC.1983-2014, Build:8.14.8.25, Ver:6.14.8.25
1:iaensee >,H s -engineering pc
1500 psi E : Modulus of Elasticity
1500 psi Ebend- xx 1900 ksi
1700psi Eminbend -xx 690ksi
625 psi
180 psi
1000 psi Density 32.21 pcf
Applied Loads
Uniform Load : D = 0.070, S = 0.1750 , Tributary Width = 1.0 ft
Point Load: D=0.1650k(a,3.50ft
DESIGN SUMMARY _yr.
Maximum Bending Stress Ratio =
Section used for this span
fb : Actual
FB : Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
Maxirnum Deflection
Max Downward L+Lr+S Deflection
Max Upward L+Lr+S Deflection
Max Downward Total Deflection
Max Upward Total Deflection
AA,‘" 0.84Fx 1
4x16
58.69 psi
1,y25.00 psi
D+S+H
11.416ft
Span # 1
Span = 23.0 ft
Service loads entered. Load Factors will be applied for calculations.
Maximum Shear Stress Ratio
Section used for this span
fv : Actual
Fv : Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
Vit*Ildr 0.000 in Ratio =
0.000 in Ratio =
0.806 in Ratio =
0.000 in Ratio =
Overall Maximum Deflections
Load Combination Span Max. "-" Defl Location in Span
+D+S+H
Vertical Reactions
Load Combination
Overall MAXimum
Overall MlNimum
+D+H
+D+L+H
+D+Lr+H
+ D+S 41
+ D+0.750Lr+0.750L+H
+D+0.7.50L+0.750S+H
489
0 <360
342
0 <180
Load Combination
1 0.8059 11.500
Support notation Far left is #1
Support 1 Support 2
2.957 2.843
0.567 0.498
0.945 0.830
0.945 0.830
0.945 0.830
2.957 2.843
0.945 0.830
2.454 2.339
0.360 : 1
4x16
74.44 psi
207.00 psi
+D+S+H
0.000 ft
Span # 1
Max. "+" Defl Location in Span
0.0000 0.000
Values in KIPS
Wood Beam
Description : (e) Pubin
Vertical Reactions
Load Combination
+D+0.60W+H
+D+0.70E+H
+D+0.750Lr+0.750L+0.450W+H
+D+0.750L+0.750S+0.450 W+H
+D+0.750L+0.750S+0.525E+H
+0.60D FO.6OW+0.60H
+0.60D+0.70E+0.60H
D Only
LrOnly
L Only
S Only
W Only
E Only
H Only
Support 1 Support 2
0.945 0,830
0.945 0.830
0.945 0.830
2.454 2.339
2.454 2.339
0.567 0.498
0.567 0.498
0.945 0.830
2.013 2.013
Support notation : Far left is #1
File = CIPROGRA-11ENERCA-2
ENERCALC, INC. 1983-2014, Build:5.14.8.25, Ver:6:14:8.25
w :t t ensee .t enginiteritig. PC';
Values in KIPS
Wood Beam
KW-060t0224.
Description : (e) beam
CODE REFERENCES
Calculations per
Load Combination Set : IBC 2012
Material Properties
Analysis Method : Allowable Stress Design
Load Combination IBC 2012
Wood Species
Wood Grade
Beam Bracing
Applied Loads
Beam self weight c I ed a ded to loads
Point Load : 1. 70, 3.850 k 7.50 ft
Point Load: D = 1.870, S = 3.850 k p 13.50 ft
Point Load: D=1.760,S=4.40k(o 21.50ft
File- C:\PROGRA-1IENERCA-2
ENERCALC, INC. 1983-2(114 Build:6:14.8.25, Ver6.14.8.25
Licensee d.s. engineering pc"
Fb - Tension
Fb -Compr
Fc - Prll
DF/DF Fc - Perp
: 24F - V4 Fv
Ft
: Beam is Fully Braced against lateral -torsion buckling
D(1.87) S(3.85)
Point Load : D =1.760,
DESIGN SUMMARY i
Maximum Bending Stress Ratio
Section used for this span
fb : Actual
FB : Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
Maximum Deflection
Max Downward L+Lr+S Deflection
Max Upward L+Lr+S Deflection
Max Downward Total Deflection
Max. Upward Total Deflection
4.40 k 29.50fft
0.820 1
5.125x27
2,004.00 psi
2,443.89psi
+p+S+H
13.566ft
Span#1
Oft
Service loads entered. Load Factors wit be applied for calculations.
2400 psi
1850 psi
1650 psi
650 psi
265 psi
1100 psi
D(1.75) S(4 4)
E : Modulus of Elasticity
Ebend- xx
Eminbend - xx
Ebend- yy
Eminbend - yy
Density
1800 ksi
930 ksi
1600 ksi
830 ksi
32.21 pcf
0(1.76) S(4.4)
6
Maximum Shear Stress Ratio
Section used for this span
fv : Actual
Fv : Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
0.803 in Ratio =
0.000 in Ratio =
1.211 in Ratio =
0.000 in Ratio =
470
0 <360
312
0 <180
Overall Maximum Deflections
Load Combination Span Max. "-" Defl Location in Span Load Combination
+D+S+H 1 1.2106 15.750
Vertical Reactions Support notation : Far left is #1
Load Combination Support 1 Support 2
Overall MAXimum 10.461 14.274
Overall MINimum 2.191 2.750
+D+H 3.651 4.584
+D+L+hI 3.651 4.584
+D+Lr+li 3.651 4.584
Design OK:;
0.370:1
5.125x27
112.66 psi
304.75 psi
+p+S+H
0.000 ft
Span #1
Max. "+ Defl Location in Span
0.0000 0.000
Values in KIPS
Z
Wood Beam
Lsc; W=O6010ZZ¢:
Description : (e) beam
Vertical Reactions Support notation : Far left is #1
Load Cornbination Support 1 Support 2
+D+S+Fi 10.461 14.274
+D+0.750Lr+0.750L+H
+D+0.750L+0.750S+H
+D+0.60W+H
+ D+0.70E+H
+D+0.750Lr+0.750L+0.450W+H
+ D+0.750L+0,750S+0.450W+H
+D+0.750L+0.750S+0.525E+H
+0.60D+0.60W+0.60H
+0.60D+0.70E+0.60H
D Only
Lr Only
L Only
S Only
W Only
E Only
H Only
3.651 4.584
8.758 11.852
3.651 4.584
3.651 4.584
3.651 4.584
8.758 11.852
8.758 11.852
2.191 2.750
2.191 2.750
3.651 /4.584
6.810
9.690
File = C:IPROGRA-11ENERCA-2
ENERCALC I.NC..1983;2014, Build:6.148.25 Ver.6.14.8.25
Licensee : J:s "engtieeringfj
Values in KIPS
:Wood - Beam
Description :
(e) beam
CODE REFERENCES
Calculations per
Load Combination Set : IBC 2012
Material Properties
Analysis Method : Allowable Stress Design
Load Combination iBC 2012
Wood Species
Wood Grade
Fb - Tension
Fb - Compr
Fc - Prll
Fc - Perp
Fv
Ft
Beam E;racing : Beam is Fully Braced against lateral -torsion buckling
D(4.584
DF/DF
24F - V4
S(9.69) D(1.76) S(4.4)
5.125x30
Span = 7.660 ft
Applied Loads
D(1.76
Li
Beam self weight calculated and added to loads
Load for Span Number 1
Point Load : D = 4.584, S = 9.690 k an, 0.0 ft
Point Load : D = 1.760, S = 4.40 k an, 5.670 ft
Load for Span Number 2
Point Load: D=1.760, S = 4.40 k 0, 6.0 ft
Point Load : D =1.760, S = 4.40 k na, 14.0 ft
Point Load : D = 1.760, S = 4.40 k (o? 22.0 ft
DESIGN SUMMARY
Maximum Bending Stress Ratio =
Section used for this span
fb : Actual
FB : Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
Maximum Deflection
Max Downward L+Lr+S Deflection
Max Upward L+Lr+S Deflection
Max Downward Total Deflection
Max Upward Total Deflection
Overall Maximum Deflections
Load Combination Span Max. "" Del Location in Span
+D+S+H 1 0.4180 0.000
+O+S+H 2 0.1165 �,_ 19 4,44 .1 +D+S+H
Vertical Reactions Suppa notation: , F
Load Combination Support 1 Support 2 Support 3
Overall MAXimum 35.041 5.145
S(4.4)
File =C:\PROGRA-1\ENERCA-2
ENERCALC, INC. 1983-2014, Bulld:6.14.8.25, Ver 6.14.8.25
Ltc Sfic, .d.s, engineering pc>.
2400 psi E : Modulus of Elasticity
1850 psi Ebend- xx
1650 psi Eminbend - xx
650 psi Ebend- yy
265 psi Eminbend - yy
1100 psi Density
D(1,76) S(4.4)
5.125x30
Span = 29.330 ft
1800 ksi
930 ksi
1600 ksi
830 ksi
32.21 pcf
D(1.76) S(4.4)
Service loads entered. Load Factors will be applied for calculations.
1.019 1 ' Maximum Shear Stress Ratio
125x 0 Section used for this span
1,913.85 psi fv : Actual
1,877.44 psi Fv : Allowable
+D+S+H Load Combination
0.000ft Location of maximum on span
Span # 2 Span # where maximum occ rs
n Ratio = 65i
0.0 5 in Ratio = 10061
0.418 in Ratio = 438
-0.054 in Ratio = 6490
Load Combination
is #1
Desien N.G.
0.463 : 1
5.125x30
141.00 psi
304.75 psi
+D+S+H
5.178 ft
# 1
Description : (e) beam
Vertical Reactions
Load Cornbination Support 1 Support 2 Support 3
Overall M(Nimum ..T 6.733 1.004
+D+H 11.222 1.674
+D+1_+H 11.222 1.674
+D+Lr+H 11.222 1.674
+D+S+H 35.041 5.145
+D+0.750Lr+0.750L+H 11.222 1.674
+D+0.750L+0.750S+H 29.086 4.277
+D+0.60W+H 11.222 1.674
+D+0.70E+H 11.222 1.674
+D+0.750Lr+0.750L+0.450W+H 11.222 1.674
+D+0.750L+0.750S+0.450W+H 29.086 4.277
+D+0.750L+0.750S+0.525E+H 29.086 4.277
+0.60D-43 60W+0.60H 6.733 1.004
+0.60D+0.70E+0.60H 6.733 1.004
D Only 11.222 1.674
Lr Only
L Only
S Only 23.819 3.471
W Only
E Only
H Only
Support notation : Far left is #1
File = C:IPROGRA-11ENERCA.-2
ENERCALC):INC.,1983-2014, Build16:14.8.25, Ver:6.14.8.25
• Licensee < d.s..Qpgit eying pc:
Values in KIPS
1 o
.j./ mapquest
Latitude/Longitude Finder
To locate a IaUlorg coordinate, enter a starting address,
STREET
4445 S. I34th Place
CITY STATE ZIP
Tukwila WA 98168
COUNTRY
United States
Cisa'
in j Create Arcour t Contact J.
U1KIt ..iar' euslt _...> Soluiorts ,'Pis °:+: ":;oi: Resources ,
NOTE. Drag the POI or click on the map to update marker location and latitude/longitude. Quality refers to the Gex;,.e
Quo!'tr
LATITUDE. 47.484746, LONGITUDE. -122.276778, ouALrrv: L1W
.S1
Platform & Technologies
Quick Sart for Developers
Quick Start for Easy Mapping Tools
Licensed Data APIs
Open Data APIs
POss
E.11:.err h\TJLQ..Q.
a:t
SATELLITE
Tdi
.Some deco Ttatiror 7Lrn,5-
Get MapQuest AppKeyy,
Related
Distame C.347,.. .
Quick Start . =pp•rg
Toos
Contact Us
Popular Products Support Products Fallow MapQuest
MapCuesl Plugins for Leaflet licensing MapOuest.com MapQuest Developer ebg
JavaScript Maps API Developer Forums Mobile Products MapQuest Blog
Flash Maps API Con'act Us Route Planner Mapouest on Facebook
Geocorfing API Web Service FAQ Gas Prices MspOuesl on Tauter
Directions API Web Service Join our Mailing Ust
701,1 Mapauesl, Inc. All rights reserved. Privacy Policy l Terms o&UJse
Site Map 'Help
ablUSGS Design Maps Summary Report
User -Specified Input
Building Code Reference Document 2012 International Building Code
(which utilizes USGS hazard data available in 2008)
Site Coordinates 47.48475°N, 122.27678°W
Site Soil Classification Site Class D - "Stiff Soil"
Risk Category I/II/III
maocipevt
I 00511111
50111 '
USGS-Provided Output
Ss = 1.494 g
Si = 0.560 g
t'Z'A
kt.
\'‘SeaTai
.
SMl
SMS = 1.494 g
= 0.840 g
•
Tukwila
Q
.East Rento
HigItlands
ittenton`- •
6-4
ff?,
02014 r
Sos = 0.996 g
Sol = 0.560 g
0111aptkuest
For information on how the SS and Si values above have been calculated from probabilistic (risk -targeted) and
deterministic ground motions in the direction of maximum horizontal response, please retum to the application and
select the "2009 NEHRP" building code reference document.
MCER Response Spectrum
1.95
1.50
1.35
1.20
1.05
c
0.30
t 0.75
cn
O. GO
0.45
0.20
0.15
0.00
0.00 0.20
1
0.40 0.60
0190
I t
1.00 1.20 1.40
Period, T (sec)
t I
1.60 1.90 2.00
1.10 T
1.00
0 00
'IGO
0.70
12% 0.60
•-•
0.50
0.40
0.'30
0.20
0.10
0.00
Design Response Spectrum
0.00 0.20 0.40
0.60 0.90 1.00 1.20
Period. T (sec)
1.40 1.60 1.90 2.00
Although this information is a product of the U.S. Geological Survey, we provide no warranty, expressed or implied, as to the accuracy of
the data contained therein. This tool is not a substitute for technical subject -matter knowledge.
Lateral Analysis: Trane Y4C
: Model: WT.= 532 #
Seismic Design:
Fp = {(0.4 a Sos )x(1 + 2z/h)xWp}/(Rp/Ip) = 0.50 Wp = 279 Ib.
FPMAX = 1.6 Sips Ip Wp = 1.59 Wp (Equation 13.3-2)
FPM,N = 0.3 Sps Ip Wp = 0.30 Wp (Equation 13.3-3)
From: a, = 2.5 Sos = 0.996 Rp = 6.0
(Critical ap and Rp per ASCE 7-10 Table 13.5-1 or 13.6-1)
I,= 1.0 per ASCE 7-10 Section 13.1.3 W, = 560.0 Ib.
Mean Roof Height (h): 30.0 ft. Comp. Attachment Height (z): 30.0 ft.
Ground Motion:
SMS = Fa*Ss = 1.494 SM1 = F„*Si = 0.840
Sos = (2/3)*SMS = 0.996 SMi = (2/3)*SM, = 0.560
Mech Unit: W =
D=
H=
Weight =
0.7 Fp =
Check Overturning (ASD) :
(Eq. 16-16) T1 = C1 = 0.7Fp* (H/2) / 43" =
(IEq. 16-16) T2 = C2 = 0.7Fp* (H/2) / 68.5" =
(Eq. 16-16) Res = (0.6-0.2Sosx0.7)x(Wp/2) =
44.250 in.
69.875 in. (D>W)
36.250 in.
560.00 lb.( Unit Weight + Misc)
195 Ib.
82 Ib.---> No Uplift
52 Ib.---> No Uplift
129 Ib.
(IBC 2012 Section 1605.3.1 Basic Combinations Equations)
Wind Design : Exposure 'B', 110 mph, 30 ft (Max. Height)
Pnet = 0.00256(K) (Kzt) (Chet) V2 =
21.68 psf > 16 psf. : Eq. 16-35
KZ = 0.70 : Velocity Presure Exposure Coefficient per ASCE 7-10 Table 27.3-1
Kn = 1.00 : Topographic Factor per ASCE 7-10 Section 26.8.2
Cnet = 1.00 : Wind Directionality Factor, in accordance with Table 1609.6.2 (per h/D ratio)
V = 110.00 : Basic Wind Speed from Section 1609.3 (Risk Category II) Fig.1609A
(ASD) : Fh = 0.6x(Pne) (Af) = 229 Ib. (Max.)
Check Overturning (ASD) :
(Eq. 16-15) T1 = C1 = 0.6x[Wind Load*W*H*[(H)/2] / 68.5" = 38 Ib.---> No Uplift
(Eq. 16-15) T2 = C2 = 0.6x[Wind Load*D*H*[(H)/2] / 43" = 96 Ib.---> No Uplift
(Eq. 16-15) Res = 0.6x(Unit Weight /2) = 168 Ib.
(IBC 2012 Section 1605.3.1 Basic Combinations Equations)
tr-t-03R r colz
tpiiitttI i4N111Jr1t`.
BUGLE HEAD - SELF DRILLING
For drywall attachment (0 melon studs ono io:5t5 Also used for
attaching cobinets throw?, gypsum board and insulation boars.
Melol Inickness - 20. 18 15 and 14 gauge
BUGLE HEAD
For drywall attachment to metal studs one joists. Also used for
attaching cabinets through gypsum board or,d insulation board
Metal thickness - 25 and 20 gouge.
WAFER HEAD - SELF DRILLING
For metal to melol Iroming connections when drywall, plywood and
other similar wall materials are used an mats! studs and joists.
Metoi Inickness - 20. 18. 16 and I4 gouge.
WAFER HEAD
For metal to metal framing connections when crywalt, plywood ond
other similar wall materials are used on rretol stuns and joists.
Metal thickness - 25 and 20 gouge.
HEX HEAD - SELF DRILLING
For attaching steel deck, backup plates. door frames, !others channel
to metal framing and structural connections
Metal thickness - 20. 18, 16 and 14 gouge.
PAN HEAD - SELF DRILLING
For ollocning steel deck, bockup plotes, door (tomes, lathers channel
to metal framing and structural connections.
Metal thickness - 18. 16 and 14 gouge.
Screw
Size
Section
Gouge
No. 12
(d=0.209")
No 10
(d=0.183")
No. 8
(d=C.161-)
No. 6
(d=0.135')
Sheor
Pullout
shear Pullout
Sheor
Pullout
Shear
Pullout
25
20
18
16
14
74
185
Z76
387
548
50
92
120
(51
190
69 44
173 8:
258 105
' 363 132
513 166
65
163
242
341
N/A
39
71
93
116
N/A _
60
149
222
N/A
N/A
32
60
78
N/A
N/A
Min. Edge
Dist. And
0.C. Spacing
1
t/16"
9/16'
1/2.
1/2"
Notes: 1. Al, volues based on connected parts having 0 minimum yield st.ess. Fy=33 ksi and
a minimum ultimate stress. Fu=45 ksi.
2. When connecting materials of different gouge thickness, use loads shown for the
tighter gouge.
3. Applied shear loads moy be multiplied by".n�; ,_ r wind or earthquake loods per
AISI A4.4. --
4, For screws in tension, the head of the screw, or washer if provided. sholl hove a
minimum diameter of 5/116 inch.
Lateral Analysis: Trane Y4C
: Model: WT. = 532 #
Seismic Design:
F, = {(0.4 ap Sos )x(1 + 2z/h)xWp}/(Rp/Ip) = 0.50 Wp = 324 Ib.
FF MAX = 1.6 SD$ Ip Wp = 1.59 Wp (Equation 13.3-2)
FoM,N = 0.3 S IpWp = 0.30 Wp (Equation 13.3-3)
From: ap = 2.5 Sos = 0.996 Rp = 6.0
(Critical ap and Rp per ASCE 7-10 Table 13.5-1 or 13.6-1)
IF= 1.0 per ASCE 7-10 Section 13.1.3
Mean Roof Height (h): 30.0 ft. Comp. Attachment Height (z): 30.0 ft.
Ground Motion:
Srns = Fa*Ss = 1.494 SM1 = Fv*Si = 0.840
Sps = (2/3)*SMs = 0.996 SM1 = (2/3)*SM1 = 0.560
Mech Unit: W = 44.250 in.
D = 69.875 in. (D>W)
H = 36.250 in. + 14" Max. Curb
Weight = 650.00 Ib.( Unit Weight + Misc)
0.7 Fp = 227 Ib.
Check Overturning (ASD) :
(Eq. 16-16)
(IEq. 16-16)
(Eq. 16-16)
T1 = C1 = 0.7Fp* (H/2+14") / 43" =
T2 = C2 = 0.7Fp* (H/2+14") / 68.5" =
Res = (0.6-0.2Spsx0.7)x(Wp/2) =
WP = 650.0 Ib.
169 Ib.---> Uplift
106 Ib.---> No Uplift
150 Ib.
(IBC 2012 Section 1605.3.1 Basic Combinations Equations)
Wind Design : Exposure 'B', 110 mph, 30 ft (Max. Height)
Pnet = 0.00256(KZ) (Kn) (Cne) V2 =
(kr-
21.68 psf > 16 psf. : Eq. 16-35
KZ = 0.70 : Velocity Presure Exposure Coefficient per ASCE 7-10 Table 27.3-1
Kz. = 1.00 : Topographic Factor per ASCE 7-10 Section 26.8.2
Cnei = 1.00 : Wind Directionality Factor, in accordance with Table 1609.6.2 (per h/D ratio)
V = 110.00 : Basic Wind Speed from Section 1609.3 (Risk Category II) Fig.1609A
(ASD) : Fh = 0.6X(Pne) (A)
Check Overturning (ASD) :
(IEq. 16-15) T1 = C1 = 0.6x[Wind Load*W*[(H+14")2 / 2] / 68.5" = 74 Ib.---> No Uplift
(Eq. 16-15) T2 = C2 = 0.6x[Wind Load*D*[(H+14)2 / 2] / 43" = 185 Ib.---> No Uplift
(Eq. 16-15) Res = 0.6x(Unit Weight /2) 95
(IBC 2012 Section 1 .3.1 Basic Combi ns Equations)
e*,6 t J-714;11
6% 14t
SUE t) , -
317 Ib. (Max.)
< D 0k.---
C., � \k` )
�tN cltb 4
1
DOWEL-7 PE FASTENERS
O
O
Table 11M WOOD SCREWS: Reference Lateral Design Values (Z)
for Single Shear (two member) Connections1,2r3
with ASTM A 653, Grade 33 steel side plate
U I
3
E
(( Y
N V
u. Z
N
O E•
g6
O n o
ydJJJ
N
N
rh dt
c
C i-
in
iG 3
m
N -- O ' C O
t7Y i to C O ... .. :70
Ibs Ibs I Ibs Ibs
'' 0 Q' S S. d' N G
C^O _ U' 2 i CO cn 0 ° 0w (r)33
' O
OZ
Ibs Ibs ` Ibs ibs
Ibs
Ib5
0.036
(20 gage)
0 138
0.151
0.164
6
7
8
89
99
113
76 70
84 78
97 89
69
76
87
66 62 { 60
72 68 ( 67
83 78 77
54
60
69
53
59
67
52
57
66
0.048
(18 gage)
• .0.138
.;'.Qe.15,1.;:7
': C.164'
:.„8 .
8
90 _
100
114 '
77
85.
. 98
71
79
AO
70
77
89
67
74
84
1 63 I 61
69 88
79 78
55. -
61, .
70
54
80
68' -.''
53
58
' '. 87 •
0 060
(16 gage)
0.138
0.151
0 164
0.177
0,190
6
7
6
9
10
92
101
116
136
146
79
87
100
116
125
81
92
107
116
72
79
90
j 105
114
}
68
75
86
100
108
64
71
81
1 94
102
53
70
79
93
100
57
63
71
83
90
56
61
70
. .82., ., , ,
88;`:':'
54
60
66
.(. 79 ,..., •
- :...-...68.:,-;'
0.075
(14 gage)
0.138
0.151
0.164
0.177
0.199..10
0418;.12
0r242
6
7
8
9
•14
' 95
105
119
139
•150
186. .
204:'
82
90
103
119
.128,
'159
.175
76
84
95
110
119
147
162
75
82
93
108
117
145
158
71
78
89
103
111
1,38
151.
67
74
84
97
105
130
•" 142 :
66 '
72
82
95
103
127
' 1;39
59
65
74
86
92
114
125,
$8
64
73
84
91
1*2 t;
14.,a
:': _ 'r57 ' .
62
71
82
88
109
r x •
#P4':.1:}
0 105
02 gage)
0.13E
0 151
0164
0.177
0.190
'0.216
0.242
6
7
8
9
10
12
14 !
104
114
129
148
160
198'
213
90
99
111
128
138
168
183
84
92
103
119
128
156
170
82
90
102
116
125
153
157
79
86
97
111
120
146
159
74
81
92
105
113
138
150
73
80
90
103
111
135
147
66
72
81
93
100
122
132
65
71
80
91
98
120'
130
63
69
77
''89
'. 96 "'
116.'•'-
126
0 120
(11 gage)
0 138
0.151
0,1,8.4
015P
t186
0.216
0 242
6 !
7
8
.,5 .
(0
12
14
• 110
120
135*
154..
16fi:`'
202
219
95
104
117
, 133 .
144
174
189
89
97
109
124
133
162
175
87
95
107
121
131"
159
172
83
91
102
118. ..
125
152
164
79 ..
66
98
110..
118
143
155
77
84
94
107
116
140
152
r 70
76
65
97
.104` . -
126
137
68
75
84
3 'I u
1d3 E'
124
134
67
73
82
,
> j0a.,
121
131
0 134
(10 gage)
0.138
0.151
0.164
0.177
0 190
0.216
0 242
6
7
8
9
10
12
14
116
126
141
160
173
209
226
100
110
122
139
149
180
195
93
102
114
129
139
167
181
92
100
112
127
136
164
177 I
r 88
96
107
1 121
130
157
169
83
91
101
114
123
148
160
81
89
99
112
121
145
157
73
80
89 .
101
109
131
141
72
79
88 '
100
107
129
139
70
77
': 86 .
.: 97 •
104
126
135
0.179
(7 gage)
Q 138
0151.'.7:
0.184'
0.177
0 190
0.216
0.,242
.-
8
8...
9
10
12
14
126 , .
.139
160'
184 ,
198
234
251
, .1.07
1;1$', '
:138
160
172
203
217
. 99
109 .
_ 126 -
148
159
189
202
97 . .
1:07 '
123
145 I
156
186
198
.82
102'
117
138
149
178
190
88. ..•
95 .',
110108
129
140
168
179
84.
93
127
137
165
176
78
64 .t
96
113
122
149
159
74
92
85 ;..
111
120
146
158 . '
72 ``..
86 .
. 92 ;'
108
117
143
152
0.239
(3 gage)
0.138
0.151
0 164
0 177
0 190
0.218
0.242
8.
7
8
9
10
12
14
126 '
139
160
188
204
256
283'.
.107
118 '
136
160
173
218
241
99
109
126
148
159
201
222
97
107
123
145
156
197
217
92
102
117
138
149
187
207
86
95
110
129
140
176
194
84
93
108
127
137
.172
190
76
84 ..
96
113
122
154
' 170 .'-1
74
82 •:,
95
111
120
151
' 1,87. •,-°'
72
80
92
108
117
.147::t ,
'f82.t:; .
Tabulated lateral design values IZ) shall he multiplied by all apphiahlc adjustment !actors (hee Table 10 l 11.
2. Tabulated lateral design values (Z) are for rolled thread wood crews (see Appends LI uuerteU m sick grain with .crew axis perpendicular to woad Ethers:
minimum screw penetraliun. p. into the main member equal to 1 OD. dowel bearing .Irength ! 1',1 uI (0.850 0,1 for ASTM A 653. Grade }) steel and aircu holding
yield strengths (p )' F., = 100.000 psi for 0009" < D 5 0 142 F,, = 9O.0(1) p., 1„1 0 142' c D < (1 177-. F„ = tin) (XX pa ':or () I'7" < D <_ (1 216'.
=70.(XX)palnr(1.21(1"<h50273
1 When (1f) < p < !(ID, tabulated Iaie;,l design \ alai. 1 / 1 .hall he t11u11'p Itl 117..12.(1l)l)
AMERICAN WOOD COUNCIL
DOWE'i TYPE FASTENERS
Table 11.20 Cut Thread or Rolled Thread Wood Screw Reference Withdrawal
Design Values, Wl
Tabulated withdrawal design values, W, are in pounds per inch of thread penetration into side grain of wood
member (see 11.2.2.1).
Specific
Gravity, 6
G2
f0.73 209
MO
0.68 181
[a; amF
0.58 132
0.51 102
0.49
0.46
0.43
0.41
0.39
0.37
7
229
199
144
1l2
94 103
83 91
rgitialk
73 79
tut'.
66 72
r
249
Wood Screw Number
9 f 10 12 I- 14
268
216 233
157 169
,���}}121 131 141
IT iYt �s sl'. eb
112 121
3kl'ir'
99 107
86 93
78 85 91
71 77 82
14471), �a.•r
64 69 74
66
�{{ 327 367
284 318
207
11*01
160
4.;
147
N4h ,Till ���0 i
93
1
P :d P`!"
84
75
16 18 20 24
1 i
406
352
256
198
183
161
141
116 128 141
105 116 127
94
387 421 489
281
217
201
446 485 564
153
114 125
356
178
161
145
84 93 102 111 130
Tabulated withdrawal design values, W, for wood screw connections shall be multiplied by all applicable adjustment facto s (see Table 0.3.1).
2. Specifc gravity, G, shall be determined in accordance ss th Table 113.3A
AMERICAN WOOD COUNCIL
�7
PERMIT COORD COPY
PLAN REVIEW/ROUTING SLIP
PERMIT NUMBER: M14-0173 DATE: 09/04/14
PROJECT NAME: FOSTORIA PARK ASSOCIATION
SITE ADDRESS: 4445 S 134 PL
X Original Plan Submittal
Response to Correction Letter #_
Revision # before Permit Issued
Revision # after Permit Issued
DEPARTMENTS:
S A w c
Building Division
Public Works
n
O(\)/4` ct cH9re Prevention Ili
Structural
n
Planning Division
Permit Coordinator
PRELIMINARY REVIEW:
Not Applicable n
(no approval/review required)
DATE: 09/09/14
Structural Review Required
REVIEWER'S INITIALS: DATE:
APPROVALS OR CORRECTIONS:
Approved
Corrections Required
n
DUE DATE: 10/07/14
Approved with Conditions NI —
Denied
(corrections entered in Reviews) (ie: Zoning Issues)
Notation:
REVIEWER'S INITIALS: DATE:
Permit Center Use Only
CORRECTION LETTER MAILED:
Departments issued corrections: Bldg D Fire ❑ Ping ❑ PW ❑
BUILDING OFFICIAL
APPROVAL FOR ISSUANCE
L/SIGN
DATE
12/18/2013
HERMANSON COMPANY LLP
Page 1 of 3
41111114 Washington State Department of
Labor & Industries
HERMANSON COMPANY LLP
Owner or tradesperson
NICOLAISEN, KNUT H
Principals
NICOLAISEN, KNUT H, PARTNER/MEMBER
BROCK, DANIEL L, PARTNER/MEMBER
FOX, DEAN M, PARTNER/MEMBER
HENGEL, STEPHEN A, PARTNER/MEMBER
DYCKMAN, KENNETH
A, PARTNER/MEMBER
ROBINETT, PAUL J, PARTNER/MEMBER
HERMANSON, RICHARD
L, PARTNER/MEMBER
ALMON, KEVIN, PARTNER/MEMBER
(End: 08/05/2010)
MACDONALD, JAMES, PARTNER/MEMBER
(End: 08/05/2010)
Doing business as
HERMANSON COMPANY LLP
WA UBI No.
602 004 844
1221 2ND AVE N
KENT, WA98032-2945
206-575-9700
KING County
Business type
Limited Liability Partnership
License
Verify the contractor's active registration / license / certification (depending on trade) and any past violations.
Construction Contractor Active.
Meets current requirements.